Liebert Challenger 3000 User Manual

Precision Cooling  
For Business-Critical Continuity  
Liebert Challenger3000  
Operation & Maintenance Manual - 3 & 5 Ton, 50 & 60Hz  
TABLE OF CONTENTS  
3.7  
i
ii  
iii  
FIGURES  
Figure 1  
TABLES  
2
2
Table 17 Recommended free area ft (m ) for grilles or perforated panels at output velocities  
of 550 and 600 fpm (2.8 and 3.1 m/s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
v
vi  
Introduction  
1.0 INTRODUCTION  
1.1 System Descriptions  
Challenger 3000 Liebert environmental control systems are available in several configurations.  
Each configuration can operate with either Advanced Microprocessor Controls (A), or Advanced  
Microprocessor Controls with Graphics (G). A brief description of each, including operational differ-  
ences, are listed below. Check model numbers to see what is supplied with your unit.  
1.1.1 Compressorized Systems  
NOTE  
Compressorized systems may be a self-contained system – with the compressor in the  
Challenger 3000 unit, or a split system – with the compressor in the separate condensing unit.  
These systems may be air, water, or glycol cooled, depending on the heat rejection method selected.  
Cooling—One stage standard; two stages of mechanical refrigeration with optional split coil.  
Heating—Two stages of electric reheat standard; SCR controlled electric reheat, hot water reheat,  
hot gas reheat on water and glycol cooled systems optional.  
Humidification—Infrared standard; steam generating optional.  
Dehumidification—Hot gas bypass locked out standard; part coil operation optional  
1.1.2 GLYCOOL™ (Chilled Glycol Cooling) Systems  
GLYCOOL™ systems have all of the features of a compressorized water or glycol system, plus a sec-  
ond cooling coil that is connected into the water circuit. When fluid temperature is sufficiently low  
(below room temperature), cooling is provided by circulating the fluid through the second cooling coil  
(flow is controlled by a motorized valve.) This is then the primary cooling source and it greatly  
reduces the compressor operation.  
Cooling—Modulated cooling valve opens proportionally to match room needs (primary), one or two  
stages of mechanical refrigeration (secondary)  
Heating—Two stages of electric reheat standard  
Humidification—Infrared standard; steam generating optional  
Dehumidification—Hot gas bypass locked out standard  
1.1.3 Chilled Water Systems  
These systems utilize a central chiller and control cooling by modulating a control valve in the chilled  
water line.  
Cooling—Proportional in response to room needs  
Heating—Two stages of electric reheat standard  
Humidification—Infrared standard; steam generating optional  
Dehumidification—Chilled water valve opens proportionally in response to room needs  
1
         
Introduction  
1.2  
Start-Up Procedure  
Before beginning start-up, make certain that unit was installed according to the instructions in the  
Installation Manual. Verify that the fan shipping bolt has been removed, the check valve has been  
installed (on air cooled units), and that the scroll compressor is rotating in the proper direction. All  
exterior panels must be in place with the front panel open.  
Locate the start-up form supplied with your unit documents. Complete the form during your start-up  
and mail it to Liebert when start-up is completed. Contact your Liebert supplier if you have any ques-  
tions or problems during your unit installation, start-up, or operation.  
WARNING  
!
Potentially lethal voltages exist within this equipment during operation. Observe all cautions  
and warnings on unit and in this manual. Failure to do so could result in serious injury or  
death. Only qualified service and maintenance personnel should work with this equipment.  
1. Disconnect all power to the environmental control unit.  
2. Tighten all electrical wiring connections that may have loosened during shipping (on electric  
panel and at all major components, such as compressor, reheats, humidifier and motor).  
3. Remove all line voltage fuses except the main fan fuses at the far right of the electric panel and  
the Control Voltage fuses at the far left of the electric panel. For units supplied with circuit  
breakers, open them instead of removing fuses.  
4. Turn on power and check line voltage on main unit disconnect switch. Line voltage must be  
within 10% of nameplate voltage.  
5. Turn ON main unit disconnect switch and check secondary voltage at transformer T1. Voltage at  
T1 must be 24 VAC ±2.5 VAC (check at TB1-1 and TB1-8). T1 voltage must not exceed 28 VAC.  
Change primary tap if necessary.  
6. Push ON button. Blower will start.  
7. If you do not want your unit to operate at factory default settings, set temperature and humidity  
setpoints and sensitivity, alarms, and other control functions. Refer to 2.0 - Operation with  
8. Stop unit by depressing ON/OFF button on the front display. Turn OFF main unit disconnect and  
main breaker.  
9. Replace all fuses (or reset circuit breakers) that were removed in Step 3.  
10. Restore power to unit; turn ON the main unit disconnect switch.  
11. Push ON button - putting the unit into operation.  
12. Check the current draw on all line voltage components and match with serial tag.  
13. Verify that the scroll compressor is rotating in the proper direction.  
CAUTION  
!
The scroll compressor must rotate in the proper direction. Rotation in the wrong direction  
will result in poor performance and compressor damage.  
14. Check for unusual noises and vibration.  
15. Check all refrigerant and fluid lines for leaks.  
16. Test all functions of your unit for proper operation.  
17. Close high voltage dead front cover and latch.  
18. Close front accent panel and latch.  
Return completed start-up form to:  
Liebert Corporation  
Warranty Registration  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
2
   
Operation with Advanced Microprocessor Controls  
2.0 OPERATION WITH ADVANCED MICROPROCESSOR CONTROLS  
The advanced microprocessor (A) control for your Liebert Challenger 3000 unit features an easy-to-  
use menu driven LCD display. The menus, control features, and circuit board details are described in  
this section. For more control details, refer to 4.0 - System Performance with Advanced Micro-  
processor Controls, and for more alarm information, refer to 5.0 - Alarm Descriptions.  
2.1  
Basics  
Control keys include ON/OFF, Menu/ESCape, Enter, Increase (UP) arrow, and Decrease (DOWN)  
arrow. Refer to Figure 1. These keys are used to move through the menus as prompted on the LCD  
display (refer to Figure 2).  
To turn the unit ON, press the ON/OFF key after power is applied. To turn the unit OFF, press the  
ON/OFF key before power is disconnected.  
Active alarms are displayed on the LCD screen. Alarms are also annunciated by an audible beeper. To  
silence an alarm, press the ENTER key as prompted on the display. The unit stores the 10 most  
recent alarms for review.  
Setpoints, DIP switch settings, and other selections were made on your unit before testing at the fac-  
tory. Setpoints were chosen based on typical operating experience. Other selections were made based  
on options included with your unit. Make adjustments to the factory default selections ONLY if they  
do not meet your specifications. When entering setpoints, time delays, etc., the allowable ranges are  
displayed and may require a password, if enabled.  
Figure 1 Advanced microprocessor control panel  
3
     
Operation with Advanced Microprocessor Controls  
Figure 2 Advanced microprocessor (A) control for Challenger 3000  
Main Menu  
72°F 50%RH  
Cooling  
Dehumidifying  
Normal Display  
Status/Alarm Data  
Setpoints/Setup  
Date and Time  
Status Display  
No Alarms Present  
Status Alarm Data  
Setpoints/Setup  
Date and Time  
Status Display  
View Setpoints  
Setup System  
Run Diagnostics  
Active Alarms  
15-APR-2004 09:30:00  
75°F 59%RH  
Cooling  
Dehumidifying  
No Alarms Present  
Operating Status  
Alarm History Log  
Run Hours Log  
ENTER to change  
ESCape to exit  
Change Passwords  
Alarm  
History Log  
Run  
Hours Log  
Analog  
Sensors  
View  
Setpoints  
Setup  
System  
Run  
Diagnostics  
Active  
Alarms  
Operating  
Status  
Change  
Password  
No Alarms Present  
Alarm History Log  
Analog Sensors  
Run Diagnostics  
OR  
Alarm 01 of 03  
15-APR 09:20:45  
High Humidity  
Show Inputs  
Test Outputs  
Test Control Board  
Analog in 1 (2,3,4):xx  
AD #1 (2,3,4)  
Alarm 01 of 01  
High Head PR  
Use  
/
to Scroll  
ESCape to exit  
Use  
/
to Scroll  
Use  
/
to Scroll  
Setup System  
Setup Operation  
Operating Status  
Run Hours Log  
Comp  
GLYCOOL** or CW Coil**  
Fan  
Hum  
RH1  
RH2  
Change Password  
Cold Start TD  
Restart TD  
IR Fill Rate  
F/C Degrees  
Min CW Temp**  
CW/HW Flush**  
Setpoint Password  
Setup Password  
DX Cool  
%
Heat  
%
%
%
Econo Cool  
CW Valve  
DX Deh / Hum  
Select Options  
Heating  
Humidifier  
View Setpoints  
Alarms Available  
Dehumidifier  
Heat Stages  
Calibrate Sensors  
Show DIP Switches (1-7)  
Select Control Type  
Intelligent  
Temp Setpoint  
Sensitivity  
Hum Setpoint  
Sensitivity  
High Temp  
Alarm  
Lo Temp Alarm  
High Hum Alarm  
Lo Hum Alarm  
Standard Alarms  
Humidifier Problems  
High Head Pressures  
Change Filter  
Loss of Air Flow  
Proportional  
Tunable PID  
Proportional Gain  
Derivative Gain  
Integral Gain  
High Temperature  
Low Temperature  
High Humidity  
Low Humidity  
Short Cycle  
Low Suction Pressure  
Compressor Overload  
Loss of Power  
Setup Alarms  
Set Time Delays  
Enable Alarms  
Enable Common Alarm  
Set Custom Alarm  
Select Alarm  
Custom Alarms 1 to 4  
Programmed Alarm Messages  
Water Under Floor  
Smoke Detected  
Change Custom TXT 1,2  
Hum Control Method  
Relative  
Standby GC Pump On  
Loss of Water Flow  
Standby Unit On  
User Customized Alarm Messages  
Available for Custom Alarms  
Absolute  
Analog Setup  
A/D Input 1 (2,3,4)  
Slope  
* Some alarms require optional equipment  
** Optional  
Text  
Intercept  
Set Status Display  
Calibrate Actuator  
4
 
Operation with Advanced Microprocessor Controls  
2.2  
2.3  
Status Display  
The display normally shown includes the present room temperature, humidity, active status func-  
tions (cooling, heating, dehumidifying, humidifying), and active alarms. If no keys are pressed within  
5 minutes, the system automatically returns to the Status Display. The Status Display may also be  
selected from the Main Menu.  
Main Menu <MENU/ESC>  
Press the MENU/ESC key to display the Main Menu. The Menu selections include:  
• Status/alarm data  
• Setpoints/setup  
• Date and time  
• Status display  
2.4  
Status/Alarm Data  
Selecting STATUS/ALARM DATA from the Main Menu will display the following selections:  
• Active alarms  
• Operating status  
• Alarm history log  
• Run hours log  
• Analog sensors  
2.4.1 Active Alarms  
This screen displays any active alarm. The alarms are numbered, #1 being the most recent. If there  
are no active alarms, then “NO ALARMS PRESENT” will be displayed.  
2.4.2 Operating Status  
The Operating Status is intended to provide the user with displayed information concerning what the  
control is calling for the system to do.  
NOTE  
There may be some time lapse before a specific component matches the displayed number.  
For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it  
takes several seconds for the valve to travel from fully closed to 68% open. So, when the display reads  
68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com-  
pressor is operating but the compressor has not yet turned on, it may be off because of the short cycle  
control (see 4.4.1 - Short Cycle Control).  
2.4.3 Alarm History Log  
A history of the 10 most recent alarms is kept in nonvolatile memory complete with the date and time  
that the alarms occurred. The first alarm in the history is the most recent and the 10th is the oldest.  
If the alarm history is full (10 alarms) and a new alarm occurs, the oldest is lost and the newest is  
saved in alarm history location 1. The rest are moved down the list by 1. Alarm history on new units  
may show the results of factory testing.  
5
           
Operation with Advanced Microprocessor Controls  
2.4.4 Run Hours Log  
The total operating hours of all major components in the unit can be monitored from the display and  
are retained in nonvolatile memory. Run times are available for the following:  
• Compressor  
• GLYCOOL Coil (or CW Coil as used on Dual Cooling Unit)  
• Fan  
• (HUM) humidifier  
• (RH1) reheat 1 (or Hot Water or SCR Reheat)  
• (RH2) reheat 2  
The component run hours for each individual component can be reset by selecting the run hours dis-  
play screen for the desired component, then pressing ENTER within 5 minutes of applying power to  
the control. The user will then be prompted to press ENTER to clear the selected component's run  
hours.  
NOTE  
Run hours for a component should be reset ONLY when the component has been replaced.  
2.4.5 Analog Sensors  
The four (4) analog sensor inputs can be monitored from the display. The inputs are filtered, then dis-  
played along with the text label assigned during setup. See Analog Setup on page 11.  
2.5  
Setpoints/Setup  
Selecting Setpoints/Setup from the Main Menu will display the following selections:  
• View setpoints  
• Setup system  
• Run diagnostics  
• Change passwords  
NOTE  
Setpoints and system setup parameters are kept in nonvolatile memory.  
2.5.1 View Setpoints  
Control and alarm setpoints can be reviewed and/or changed through the display. The following table  
lists the default setpoints and their allowable ranges.  
Table 1  
Default setpoints and ranges  
Setpoint  
Default  
72°F  
2.0°F  
50%  
Range  
Temperature Setpoint  
Temperature Sensitivity  
Humidity Setpoint  
40 to 90°F (5 to 32°C)  
1 to 9.9°F (0.6 to 5.6°C)  
20 to 80% RH  
Humidity Sensitivity  
5%  
1 to 30% RH  
High Temperature Alarm  
Low Temperature Alarm  
High Humidity Alarm  
Low Humidity Alarm  
80°F  
65°F  
60%  
35 to 95°F (2 to 35°C)  
35 to 95°F (2 to 35°C)  
15 to 85% RH  
40%  
15 to 85% RH  
6
         
Operation with Advanced Microprocessor Controls  
2.5.2 Setup System  
The Setup System menu includes the following selections:  
• SETUP OPERATION  
• SELECT OPTIONS  
• CALIBRATE SENSORS  
• SHOW DIP SWITCHES  
• SELECT CONTROL TYPE (Chilled Water or SCR Reheats only)  
• SETUP ALARMS  
• HUM CONTROL METHOD  
• ANALOG SETUP  
• SET STATUS DISPLAY  
• CALIBRATE ACTUATOR  
Setup Operation  
The Setup Operation menu permits the review and/or adjustment of the unit configuration. This may  
include:  
Cold Start—This feature, also referred to as Positive Start or Winter Start Kit, allows for the low  
pressure switch to be ignored for the programmed time during a cold start of the compressor. Enter-  
ing a “0” for this time will bypass this feature. A “1” will bypass the low pressure switch for one  
minute, a “2” for 2 minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is fac-  
tory set to 0 for water cooled, glycol cooled, and GLYCOOL units. Typically, only air cooled units need  
a “Winter Start” delay time.  
Restart—This feature allows for the unit to restart automatically after a loss of power. The pro-  
grammed value is in 0.1 minute (6 seconds) intervals. A programmed value of zero (0) would require  
the user to manually press the ON/OFF key to start the unit, i.e. no auto restart. The purpose of this  
feature is to prevent several units from starting at the same time after a loss of power. The message  
“Restart Delay -- Please Wait” will be displayed when the system is in the auto restart mode. Liebert  
suggests programming multiple unit installations with different auto restart times.  
IR Fill Rate (infrared humidifiers only)—An autoflush system automatically controls a water  
makeup valve to maintain the proper level in the infrared humidifier water pan during humidifier  
operation. If humidification is needed and 15 hours have elapsed since the last time the humidifier  
was on, the humidifier is held off until the valve completes an initial fill of the humidifier pan. This  
pre-fill is about 30 seconds. The valve continues to fill and flush the pan for about 4 minutes.  
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-  
odically to add water to the pan (about 40 seconds for every 9-1/2 minutes of humidifier operation).  
This adds enough water to the pan to cause about a third of the total water used to be flushed out the  
overflow standpipe located in the humidifier pan. This flushing action helps remove solids from the  
pan. The flush rate is adjustable from 110% to 500%. If the water quality is poor, it may be desirable  
to increase the water flushing action above the normal 150% rate. Also, if the supply water pressure  
is low, the flush rate adjustment can be increased so that sufficient water level is maintained during  
humidification.  
Chilled Water/Hot Water/Econ-O-Coil Flush—This feature will flush the respective coil for  
3 minutes after the programmed number of hours of non-use. For example, if the flush time is pro-  
grammed with 24 hours on a hot water reheat type system and heating is not required for a 24 hour  
period, the hot water valve will be open for 3 minutes to allow the coil to be flushed. The programmed  
value can be from 0 (no flush) to 99 (99 hours of non-use).  
C/F Degrees—The control can be selected to show readings and setpoints in either degrees Fahren-  
heit (F) or Celsius (C).  
7
 
Operation with Advanced Microprocessor Controls  
Table 2 lists the setup functions, their factory default values and the allowable programming ranges.  
Table 2  
Setup functions, default values and ranges  
Function  
Default  
Range  
Cold Start Time Delay*  
Restart Time Delay  
Infrared Fill Rate  
3
0.1  
150  
24  
F
0 to 3 min (0 = no delay)  
0 to 9.9 min (0 = manual restart)  
110 to 500%  
Chilled/Hot Water Coil Flush  
C/F Degrees  
0 to 99 hrs (also Econ-O-Coil)  
C or F  
*Factory set to 0 for water cooled, glycol, and GLYCOOL units.  
Select Options  
The following table lists options which should match the options installed with your unit and should  
not need to be changed during normal operation.  
Table 3  
Unit options  
Option  
Selection  
Yes or No  
Yes or No  
Yes or No  
Yes or No  
2
1
Heating  
Humidifier  
Dehumidifier  
Hot Gas Reheat  
2
3
Heat Stages  
1Heating cannot be disabled on units with SCR reheats.  
2Hot gas reheat not available on units with SCR reheats.  
3Heat stages not selectable on units with SCR reheats.  
Calibrate Sensors  
The temperature and humidity sensors can be calibrated by selecting this menu item. “SENSOR”  
shows the actual sensor reading or raw reading. “CALIBRATED” shows the sensor reading after the  
calibration offset has been added. The temperature sensor can be calibrated ±5 degrees Fahrenheit  
and the humidity sensor can be calibrated ±10%RH. When calibrating the humidity sensor, the value  
shown will always be % RH, even though absolute humidity control may be selected. If absolute  
humidity control is selected, the Normal Status Display will display the adjusted reading and may not  
agree with the relative humidity reading displayed while in calibration.  
Show DIP Switches  
The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires  
opening the upper panel for access to the DIP switches on the microprocessor control board.  
NOTE  
Power MUST be cycled OFF, then ON from the unit disconnect switch for the control  
system to update the DIP switch settings (with the exception of switch 8).  
Table 4  
Switch #  
DIP switch settings  
Off  
No Part Coil  
On  
Part Coil/Chilled Water  
Hot Water Reheat  
Not Used  
1
2
3
4
5
6
Electric/Hot Gas Reheat  
All  
No GLYCOOL  
No Dual Cooling  
Not Used  
GLYCOOL  
Dual Cooling  
Not Used  
a
7
Tight Control  
Standard Control  
a
SCR reheats only (with special software); otherwise, not used.  
The selections shown in Table 4 should match options installed on your unit and should not need to  
change during normal operation. Switches 1 through 7 are self explanatory. DIP switch 8, not shown in the  
table, enables the password feature when set to ON and disables the password feature when set to OFF.  
8
       
Operation with Advanced Microprocessor Controls  
Select Control Type  
• Intelligent (Chilled Water only)  
• Proportional (all unit types)  
• Tunable PID (Chilled Water or SCR Reheats only)  
The type of system control method used by the microprocessor can be selected from the front panel.  
The default setting is Intelligent, which approximates the actions that a human operator would take  
to maintain precise, stable control. The control logic uses Artificial Intelligence techniques including  
“fuzzy logic” and “expert systems” methods to maintain precise, stable control and increase reliability  
by reducing component cycles. Proportional is a standard control method that uses one gain factor  
(temperature sensitivity adjustment). Tunable PID (Proportional, Integral, and Derivative) uses  
three gain factors selected by the operator. PID allows precision tuning, but requires an experienced  
operator and seasonal adjustments. Note that if PID is selected, it is used for temperature control  
while humidity will continue to use Proportional control. Refer to 4.0 - System Performance with  
Advanced Microprocessor Controls for more detail on types of controls.  
Setup Alarms  
Selecting SETUP ALARMS will step to the following menu:  
• SET TIME DELAYS  
• ENABLE ALARMS  
• ENABLE COMMON ALARM  
• SET CUSTOM ALARMS  
Each individual alarm can be programmed with a time delay from 0 to 255 seconds. Each individual  
alarm can be ENABLED or DISABLED and each individual alarm can be programmed to energize or  
not to energize the Common Alarm Relay.  
Set Time Delays—By programming a time delay for an alarm, the system will delay the specified  
amount of time before recognizing the alarm. The alarm condition must be present for the amount of  
time programmed for that alarm before it will be annunciated. If the alarm condition goes away  
before the time delay has timed out, the alarm will not be recognized and the time delay timer will be  
reset. For software alarms such as Loss of Power, Short Cycle, and Low Suction Pressure, a time  
delay will only delay the annunciation of that alarm. The condition of the alarm is not applicable  
because the condition has already occurred. For these alarms the time delay should be left at the fac-  
tory default of 0. Table 5, below, shows the default time delays for each alarm.  
Table 5  
Alarm default time delays  
Default Time  
Delay (seconds)  
Alarm  
Humidifier Problem  
High Head Pressure  
Change Filter  
2
2
2
Loss of Air flow  
3
Custom Alarm #1  
Custom Alarm #2  
Custom Alarm #3  
Custom Alarm #4  
High Temperature  
Low Temperature  
High Humidity  
0
0
0
6
30  
30  
30  
30  
0
Low Humidity  
Low Suction Pressure  
Short Cycle  
0
Compressor Overload  
Main Fan Overload  
Loss of Power  
2
5
0
9
   
Operation with Advanced Microprocessor Controls  
Enable Alarms—Each individual alarm can be selected to be ENABLED (annunciated audibly, visu-  
ally, and communicated to a Site Products System) or DISABLED (ignored).  
Enable Common Alarm—Each individual alarm can be selected to energize or to not energize the  
common alarm relay. If the energize common alarm function is set to YES, the relay is energized  
immediately as the alarm is annunciated and de-energized when the alarm condition goes away (only  
after the alarm has been recognized). If the function is set to NO, the alarm has no effect on the com-  
mon alarm relay regardless of whether the alarm is ENABLED or DISABLED.  
Set Custom Alarms—The custom alarm messages can be from a list of standard alarm messages or  
you can write your own message.  
NOTE  
A maximum of two of the alarm messages can be your own message.  
They can be in any location(s) 1 through 4. The text for custom alarms can be changed at any time by  
selecting “SET CUSTOM ALARMS.” To change the text for a custom alarm, select “SELECT  
ALARM.” Then, select the alarm you would like to change, 1 through 4. Using the UP/DOWN arrows  
will step through the list of five standard alarm messages (see list below) and the two custom alarms.  
NOTE  
The two custom alarm messages will be shown with what was previously programmed in them  
and can be changed.  
Press ENTER to make your selection. To modify the two custom alarm messages, go back one screen  
and select “CHANGE CUSTOM TXT 1” (or 2). Text can be up to 20 characters in length and can be  
any of the following characters (or a blank space):  
ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.  
Standard Custom Alarm Messages  
• WATER UNDER FLOOR  
• SMOKE DETECTED  
• STANDBY GC PUMP ON  
• LOSS OF WATER FLOW  
• STANDBY UNIT ON  
For more information concerning alarms, see 5.0 - Alarm Descriptions.  
Humidity (HUM) Control Method  
The user may select between relative (direct) and absolute (predictive) humidity control. If relative is  
selected, the RH control is taken directly from the RH sensor. If absolute is selected, the RH control is  
automatically adjusted as the return air temperature deviates from the desired temperature setpoint.  
This results in a predictive humidity control. The display will indicate % RH for both methods of con-  
trol, but the adjusted humidity reading will be displayed if absolute is selected. With absolute humid-  
ity control, the humidity control is automatically adjusted approximately 2% RH for each degree  
difference between the return air temperature and the temperature setpoint.  
With relative humidity control, unnecessary dehumidification can result when overcooling occurs dur-  
ing a dehumidification cycle. This is because a higher than normal RH reading is caused by overcool-  
ing the room (about 2% RH for each degree of overcooling). This extends the dehumidification cycle.  
Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading  
falls. The final RH reading will then be lower than actually desired. If the overcooling was significant  
enough, the RH could be low enough to activate the humidifier.  
If absolute humidity control is selected, over-dehumidification is avoided. When overcooling occurs,  
causing an increase in the RH reading, the humidity control program “predicts” what the RH will be  
when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehu-  
midification cycle to end at the proper time. The predictive humidity control can reduce energy con-  
sumption by minimizing compressor and reheat operation, and eliminating unnecessary humidifier  
operation.  
10  
Operation with Advanced Microprocessor Controls  
Analog Setup  
For installation of analog sensors, see 4.5.1 - Connecting the Analog Sensors.  
After selecting a compatible sensor and properly wiring it to the terminals, set up the control to mon-  
itor the sensor as follows:  
Slope—The slope is a multiplier used to scale the input signal. The slope can be positive (rising) or  
negative (falling) and can range from 0 (resulting in a horizontal line) to ±999. The slope for a 0-5 volt  
input is per 1 volt input, for 0-10 volt input is per 2 volt input, and for 4-20 mA is per 4 mA input. For  
example, assuming an intercept of 0, for a 0-10 volt sensor input with a slope of 50, an input of 1 volt  
would be displayed as 25: 1x(50/2); 2 volts would be 50: 2x(50/2); 3 volts would be 75: 3x(50/2); etc.  
Intercept—The intercept is an offset from point 0 corresponding to 0 volts or 0 mA input. The inter-  
cept can be positive or negative and can be a point from 0 to ±999.  
Adding an intercept of 100 to the slope example above, 1 volt would be 125: 100 + (1x[50/2]); 2 volts  
would be 150: 100 + (2x[50/2]); 3 volts would be 175: 100 + (3x[50/2]); etc.  
NOTE  
For a 4-20 mA input sensor, if the desired reading at 4 mA input is 0, then an intercept of  
-1 x slope would be required. For example, assuming a slope of 50, the formula would be  
([-1 x 50] + 4 x [50/4]) = 0. The intercept is -50.  
Text—You may enter a custom label for each analog input. The text label can be 20 characters in  
length including any of the following:  
ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789, or space.  
Set Status Display  
The Status Display can be set to display the return air temperature and humidity SENSOR READ-  
INGS or the temperature and humidity control SETPOINTS through this selection. When SET-  
POINTS is selected, the status display indicates so by displaying “SETPTS.” If SENSOR READINGS  
is selected, the Status Display will show the return air sensor readings.  
Calibrate Actuator  
For systems that use a valve actuator for chilled water or GLYCOOL cooling, the actuator timing may  
be calibrated or adjusted. This is the time it takes for the valve to travel from full closed to full open.  
It is programmable from 0 to 255 seconds. The factory default time is 165 seconds and should not be  
changed unless the actual valve travel time is not correct. The full valve travel time is used by the  
control to determine the appropriate valve position. For example, if the valve travel time is 165 sec-  
onds and 50% cooling is being called for, the valve will open for 83 seconds to acheive 50% open. To  
change the valve travel time, first enter the “CALIBRATE ACTUATOR” screen. The display will show  
the present period used by the control for valve actuator full travel. Press ENTER and adjust the time  
using the UP/DOWN arrows. When the correct time is displayed, press ENTER to store the new time  
to memory.  
11  
 
Operation with Advanced Microprocessor Controls  
2.5.3 Run Diagnostics  
By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and complete  
a test of the microcontroller circuit board, all from the front panel. Review of the system inputs and  
the microcontroller test can be done without interrupting normal operation. To test the system out-  
puts, the normal system control is temporarily suspended. DO NOT leave the unit in the diagnostics  
mode any longer than is necessary for troubleshooting. The control system will return to normal oper-  
ation in 5 minutes, automatically, if no key is pressed.  
Show Inputs  
With the unit on and the fan running, the input state for the following devices may be displayed:  
• Air sail switch: normally off unless Loss of Air Alarm is active  
• Custom alarm #1: normally off unless this alarm is active  
• Custom alarm #2: normally off unless this alarm is active  
• Custom alarm #3: normally off unless this alarm is active  
• Custom alarm #4: normally off unless this alarm is active  
• Humidifier problem: normally on unless this alarm is active  
• Filter clog: normally off unless Change Filters Alarm is active  
• Main fan overload: normally on unless Main Fan Overload Alarm is active  
• Shutdown device: normally on unless unit is off through the Fire Stat or Remote Shutdown  
Device  
• Low press switch: normally on if compressor circuit is in operation  
• Comp overload: normally on unless Compressor Overload Alarm is active  
• High head comp: normally off unless High Head Pressure alarm Compressor is active  
Test Outputs  
When this feature is selected, the unit is effectively turned off. When stepping from one load to the  
next, the previous load, if on, is turned off automatically. The loads can also be toggled ON/OFF by  
selecting “ENTER.” Once turned on, the output will remain on for 5 minutes unless toggled off or the  
Test Outputs function is exited by selecting “MENU/ESC.” (The compressor is limited to 15 seconds  
on to prevent damage.) The outputs are as follows:  
• Main fan: main fan contactor  
• Comp: compressor contactor  
• LLSV: liquid line solenoid valve  
• HGBP/CUV: hot gas bypass or compressor unloader valve (on certain units)  
• Part coil: part coil solenoid valve  
• CWV/CGV: chilled water or GLYCOOL valve  
• R5 Relay: Relay 5 (heat rejection)  
• Reheat 1: Reheat 1 contactor (also energizes fan for safety) or SCR Reheats  
• Reheat 2: Reheat 2 contactor (also energizes fan for safety)  
• HWR: hot water solenoid valve  
• Humidifier: humidifier contactor (also energizes humidifier makeup valve and fan for safety)  
• HMV: humidifier makeup valve  
• Comm alarm: common alarm relay  
CAUTION  
!
Do not test a compressor output for more than a few seconds. Compressor damage could  
result!  
Test Control Board  
By selecting this function, the microcontroller will perform a self test lasting approximately 10 sec-  
onds. At the end of the test, the ROM checksum, ROM part number and version number will be dis-  
played.  
12  
 
Operation with Advanced Microprocessor Controls  
2.5.4 Change Passwords  
The display prompts you to enter a three digit password when making changes. The system includes  
two (2) passwords, one for setpoints and one for setup. The system allows the passwords to be changed  
by first entering the present password, factory set as “123” for setpoints and “321” for setup. The pass-  
word function provides system security, so only personnel authorized to make changes should know  
the passwords. If unauthorized changes are being made, the passwords may be compromised and new  
ones should be selected. The password function can be disabled by setting DIP switch 8 to OFF.  
2.6  
Date and Time  
The current date and time is available through the display. This feature allows the date and time to  
be read or changed and is accessed by selecting “DATE AND TIME” from the Main Menu.  
The “DATE AND TIME” is used only by the control for recording the Alarm History.  
NOTE  
The clock uses the 24 hour system (For example: 17:00 would be 5:00 PM). The date and time  
are backed up by battery.  
2.7  
2.8  
Status Display  
The Status Display selected from the Main Menu is the same Status Display that is normally on the  
screen. While the Main Menu is displayed, you can press the MENU/ESC key to return to the Status  
Display.  
NOTE  
The system automatically returns to the Status Display in five minutes if no  
control keys are pressed.  
Control Circuit Board  
The control circuit board is located inside the unit behind the LCD display and control key panel.  
Open the front panel for access to the board.  
The control board includes an adjustment for LCD display contrast, nonvolatile memory, DIP  
switches (which should not require customer changes), control output LEDs and jumpers for board  
configuration. The jumpers should be placed as follows:  
P5—removed  
P12—removed  
P19—installed on Pins 1 and 2  
P47—installed on Pins 1 and 2  
P48—installed on Pins 1 and 2  
P50—all jumpers installed for 4-20 mA analog inputs. See 4.5.1 - Connecting the Analog Sen-  
sors for other configurations  
P51—removed  
2.8.1 LCD Display Contrast  
The level of contrast due to viewing angle of the LCD display can be adjusted using a small thumb  
wheel at the upper left of the control board just under the cable going to the display. The control is  
labeled R6.  
NOTE  
The LED backlighting on the text (4 x 20) display is always lit.  
13  
         
Operation with Advanced Microprocessor Controls  
2.8.2 Non-Volatile Memory  
All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component  
run hours are kept inside the microcontroller in EEPROM. Information retained for the alarm history  
is kept in non-volatile RAM.  
2.8.3 DIP Switches  
Equipment options are selected and enabled using DIP switches 1 through 7. These are located at the  
upper left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory  
set and should not require any user changes. The setting and function of the switches can be read  
from the LCD display (see Show DIP Switches on page 8 or the accompanying Table 4).  
2.8.4 Control Outputs  
Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is  
lit if the control output is active (on). The LEDs assist in troubleshooting the system. Refer to the fol-  
lowing table.  
Table 6  
Control output LEDs  
LED  
R5  
Control Output  
Heat Rejection  
LLSV  
HGBP  
C1  
Liquid Line Solenoid Valve  
Hot Gas By-Pass or Compressor Unloader Valve  
Compressor  
RH1  
RH2  
HUM  
FAN  
HMV  
LLSV2  
Reheat Stage 1, Hot Gas, Hot Water Reheat Solenoid or SCR Reheats  
Reheat Stage 2  
Humidifier  
Main Fan  
Humidifier Make-Up Valve  
Part Coil Solenoid Valve  
14  
       
Operation with Advanced Microprocessor with Graphics Control  
3.0 OPERATION WITH ADVANCED MICROPROCESSOR WITH GRAPHICS CONTROL  
The advanced microprocessor with graphics (G) control for your Liebert Challenger 3000 unit features  
an easy to use, menu driven LCD Graphics Display. The menus, control features, and circuit board  
details are described in this section. For more details on the control refer to 4.0 - System Perfor-  
3.1  
Basics  
Control keys include ON/OFF, Menu/ESCape, ENTER, Increase (UP) arrow, and Decrease (DOWN)  
arrow. Refer to Figure 3. These keys are used to move through the menus as prompted on the LCD  
display (refer to Figure 4).  
To turn the unit ON, press the ON/OFF key after power is applied. To turn the unit OFF, press the  
ON/OFF key before power is disconnected.  
Active alarms are indicated on the LCD screen by a ringing bell. Alarms are also annunciated by an  
audible beeper. To silence an alarm, press the ENTER key as prompted on the display. The unit  
stores the 60 most recent alarms for review.  
Setpoints, DIP switch settings, and other selections were made on your unit before testing at the fac-  
tory and are kept in nonvolatile memory. Setpoints were chosen based on typical operating experi-  
ence. Other selections were made based on options included with your unit. Make adjustments to the  
factory default selections ONLY if they do not meet your specifications. When entering setpoints, time  
delays, etc., the allowable ranges are displayed and may require a password, if enabled.  
Figure 3 Advanced microprocessor with graphics (G) control panel  
15  
     
Operation with Advanced Microprocessor with Graphics Control  
Figure 4 Advanced microprocessor with graphics control menu  
Use UP/DOWN to move  
the cursor. Hit ENTER  
to select the menu item.  
Any key  
except  
ON/OFF  
72°F Unit On  
50%RH  
Dehumidifying  
Cooling  
Normal Display  
ESC key moves backward  
through menus toward the  
Main Menu  
ESC key  
***Main Menu***  
View/Set  
Control  
Setpoints  
Setup  
System  
Run  
Diagnostics  
Analog/  
Digital Inputs  
View/Set  
Alarms  
Date and  
Time  
View Run  
Hours Log  
Operating  
Status  
Plot Graphs  
Operating Status  
Date and Time  
View/Set Setpoints  
View Run Hours Log  
Set Clock  
Compressor Cooling %  
Heating %  
GLYCOOL %**  
Chilled Water Valve %**  
Dehumidification %  
Humidification %  
Temperature Setpoint  
Sensitivity Setpoint  
Humidity Setpoint  
View 24 Hour Run  
Time History  
Chilled Water**  
GLYCOOL**  
Compressor  
Reheat 1,2  
Run Diagnostics  
Sensitivity  
High Temperature Alarm  
Low Temperature Alarm  
High Humidity Alarm  
Low Humidity Alarm  
Show Inputs  
Air Sail Switch  
Custom Alarm 1  
Custom Alarm 2  
Custom Alarm 3  
Custom Alarm 4  
Humidifier Problem  
Filter Clog Switch  
Main Fan Overload  
Shutdown Device  
Low Pressure  
Switch  
Humidifier  
Main Fan  
View Total Run Hours  
Compressor  
GLYCOOL**  
Chilled Water Valve**  
Main Fan  
Humidifier  
Reheat 1,2  
View/Set Alarms  
Active Alarms  
Alarm History  
Setup Alarms  
Setup System  
Setup Operation  
Cold Start Delay  
Auto Restart Delay  
IR Flush Overfill  
CW / HW Coil Flush**  
Display in Degrees (F / C)  
Min Chilled Water Temp**  
Select Options  
High Temperature  
Low Temperature  
High Humidity  
Low Suction Pressure  
Short Cycle  
Compressor Overload  
Main Fan Overload  
Loss of Power  
Humidifier Problem  
High Head Pressure  
Change Filters  
Heat Rejection  
Compressor  
Overload  
High Head Pressure  
Test Outputs  
Main Fan  
Compressor  
Liquid Line SV  
HGBP/CUV  
CW/CGV  
Dehumidification***  
R5 Relay  
Reheat 1  
Analog/Digital Inputs  
Reheat  
Humidify  
Dehumidify  
Read Analog Inputs  
Analog Input 1  
Analog Input 2  
Analog Input 3  
Analog Input 4  
Set Analog Inputs  
Analog Input 1 (2,3,4)  
Slope  
Hot Gas Reheat  
Stages of Reheat  
Calibrate Sensors  
Temperature Sensor  
Humidity Sensor  
Calibrated Reading  
Calibrate Valve Actuator  
Select Control Algorithm*  
Proportional  
Intelligent  
Tunable PID  
Proportional Gain  
Derivative Gain  
Integral Gain  
Loss of Air Flow  
Custom Alarm 1  
Custom Alarm 2  
Custom Alarm 3  
Custom Alarm 4  
Setup Custom Alarms  
Setup Custom Alarm Text  
Change Custom Text 1  
Change Custom Text 2  
Change Custom Text 3  
Change Custom Text 4  
View Water  
Reheat 2  
RH3 Dehum  
Units  
Text  
Intercept  
Damper  
Humidifier  
Read Digital Inputs  
Setup Digital nputs  
(How-to Text)  
HMV  
Common Alarm  
Test Control Board  
Microcontroller  
Show DIP Switches  
Dipswitch 1  
Dipswitch 2  
Dipswitch 3  
Dipswitch 4  
Detect Floor Plan  
Setup Water  
Detect Floor Plan  
Plot Graphs  
Select Humidity  
Sensing Mode  
Relative  
Absolute  
Temperature Plot  
Humidity Plot  
Use  
/
to locate file  
Use ENTER to define file  
Analog Sensor #1 Plot  
Analog Sensor #2 Plot  
Analog Sensor #3 Plot  
Analog Sensor #4 Plot  
Modify Plot Scales  
Modify Temp Scales  
Modify Humidity Scales  
Modify Analog Sensor  
# 1 Scale  
Set Status Display  
Sensor Reading  
Setpoints  
Change Passwords  
Setpoint Password  
Setup Password  
Change Passwords  
Dipswitch 5  
Dipswitch 6  
Dipswitch 7  
*
**  
Select Control Algorithm available on Chilled Water only  
optional  
# 2 Scale  
# 3 Scale  
*** Himod units only  
# 4 Scale  
16  
 
Operation with Advanced Microprocessor with Graphics Control  
3.2  
Status Display  
The normal status screen is divided into two sections, a right half and a left half. The left half displays  
the return air temperature and humidity readings in large characters.  
NOTE  
The display can also be set to display the temperature and humidity setpoints.  
The right half of the screen is divided into four quadrants (top to bottom). In the four quadrants, six  
different graphic symbols may be displayed depending on the unit status. At the top there will be a  
moving hammer striking a bell that appears when an alarm is present. The word “Alarm” also  
appears next to the hammer and bell. The second quadrant down displays a rotating fan as long as  
the unit is turned on and the fan is running. The words “Unit on” appear next to the fan symbol. The  
third quadrant may display one of two symbols relating to heating or cooling. If the control is calling  
for cooling, a growing snowflake is shown next to the word “Cooling.” If the control is calling for heat-  
ing, three moving heat rays are displayed next to the word “Heating.” In the bottom quadrant, there  
may be one of two symbols relating to humidification and dehumidification. If the control is calling for  
humidification, a growing water drop is shown next to the word “Humidification.” If the control is call-  
ing for dehumidification, a shrinking water drop is shown next to the word “Dehumidification.”  
3.3  
Main Menu <MENU/ESC>  
Press the MENU/ESC key to display the Main Menu. The Menu selections include:  
• VIEW/SET ALARMS  
• OPERATING STATUS  
• VIEW/SET CONTROL SETPOINTS  
• SYSTEM SETUP  
• RUN DIAGNOSTICS  
• DATE AND TIME  
• PLOT GRAPHS  
• ANALOG/DIGITAL INPUTS  
• VIEW RUN HOURS LOG  
Pressing the MENU/ESC key while the Main Menu is displayed will return the screen to the Status  
Display.  
3.4  
View/Set Alarms  
Selecting VIEW/SET ALARMS will step to the following menu:  
• ACTIVE ALARMS  
• ALARM HISTORY LOG  
• SETUP ALARMS  
• SETUP CUSTOM ALARMS  
• VIEW WATER DETECT FLOOR PLAN  
• SETUP WATER DETECT FLOOR PLAN  
3.4.1 Active Alarms  
This screen displays any active alarm. The alarms are numbered, #1 being the most recent. The type  
of alarm (Urgent or Warning) is also displayed. If there are no active alarms, then “NO ALARMS  
PRESENT” will be displayed.  
3.4.2 Alarm History Log  
A history of the 60 most recent alarms is kept in nonvolatile memory complete with the type of alarm,  
the alarm name, and the date and time it occurred. The first alarm in the history is the most recent  
and the last (up to 60) is the oldest. If the Alarm History is full (60 alarms) and a new alarm occurs,  
the oldest is lost and the newest is saved in alarm history location 1. The rest are moved down the list  
by 1. Alarm history on new units may show the results of factory testing.  
17  
         
Operation with Advanced Microprocessor with Graphics Control  
3.4.3 Setup Alarms  
The list of alarms may be reviewed using the UP/DOWN keys. Any alarm may be selected to have it's  
parameters modified by pressing the ENTER key. All alarms have a time delay and alarm type  
parameter. The high/low temperature and humidity alarms also have a programmable Trip Point.  
The Trip Point is the point at which the alarm is activated. By programming a time delay for an  
alarm, the system will delay the specified amount of time before recognizing the alarm. The alarm  
condition must be present for the amount of time programmed for that alarm before it will be annun-  
ciated. If the alarm condition goes away before the time delay has timed out, the alarm will not be rec-  
ognized. For software alarms such as Loss of Power, Short Cycle, and Low Suction Pressure, a time  
delay will only delay the annunciation of that alarm. The condition of the alarm is not applicable  
because the condition has already occurred. For these alarms, the time delay should be left at the fac-  
tory default of 0.  
The following table shows the default time delays for each alarm.  
Table 7  
Alarm default time delays  
Default Time  
Delay (seconds)  
Alarm  
Humidifier Problem  
High Head Pressure  
Change Filter  
2
2
2
Loss of Air flow  
3
Custom Alarm #1  
Custom Alarm #2  
Custom Alarm #3  
Custom Alarm #4  
High Temperature  
Low Temperature  
High Humidity  
0
0
0
6
30  
30  
30  
30  
0
Low Humidity  
Low Suction Pressure  
Short Cycle  
0
Compressor Overload  
Main Fan Overload  
Loss of Power  
2
5
0
Each individual alarm can be selected as either DISABLED, WARNING, or URGENT. The four cus-  
tom alarms may also be selected to be a Status Only input. If the alarm is DISABLED, it is ignored. If  
the alarm is WARNING or URGENT, it will be annunciated audibly, visually, and communicated to a  
Site Products System if appropriate. When the alarm is selected to be a WARNING, the alarm will  
NOT activate the common alarm relay. When the alarm is selected to be URGENT, the alarm is first  
annunciated as a WARNING, and then annunciated again, after the programmed time delay. When  
the alarm becomes URGENT, the control will activate the common alarm relay. The common alarm  
relay is de-energized after the alarm has been recognized and when the alarm no longer exists. When  
the alarm type has been selected to be URGENT, the allowable range for the time delay from warning  
to urgent is 0 minutes to 999 hours. When any of the four custom alarm inputs have been selected as  
Status Only, they become digital inputs for monitoring only and are no longer treated as alarms.  
18  
   
Operation with Advanced Microprocessor with Graphics Control  
3.4.4 Setup Custom Alarms  
Selecting SETUP CUSTOM ALARMS will step to the following menu:  
• SETUP CUSTOM ALARM TEXT  
• CHANGE CUSTOM TEXT 1  
• CHANGE CUSTOM TEXT 2  
• CHANGE CUSTOM TEXT 3  
• CHANGE CUSTOM TEXT 4  
The custom alarm messages can be selected from a list of standard messages or you can write your  
own messages. The message selected for any custom alarm can be changed at any time by selecting  
SETUP CUSTOM ALARM TEXT. A list of five standard messages (see list below) and four custom  
messages are available to choose from. To modify the custom messages press CHANGE CUSTOM  
TEXT 1 (2, 3 or 4). Each message can be up to 20 characters in length and can be any of the following  
characters (or a blank space):  
ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.  
Standard Custom Alarm Messages  
• WATER UNDER FLOOR  
• SMOKE DETECTED  
• STANDBY GC PUMP ON  
• LOSS OF WATER FLOW  
• STANDBY UNIT ON  
For more information concerning alarms, see 5.0 - Alarm Descriptions.  
3.4.5 View Water Detect Floor Plan (for Optional LTM1000/LT750)  
When water is detected the alarm will sound and the WATER UNDER FLOOR alarm message will be  
displayed. To see where the water is in the room, select VIEW/SET ALARMS from the main menu,  
then VIEW WATER DETECT FLOOR PLAN. A tile will be highlighted and blinking to indicate the  
position of the detected water.  
3.4.6 Setup Water Detect Floor Plan  
The selected (i.e., cursor) floor tile will be highlighted and blinking. The UP and DOWN arrow keys  
are used to position the cursor tile. The UP key will move the cursor tile up and then it wraps around  
to the bottom of the next column to the right. The DOWN arrow key moves the cursor down, then to  
the top of the next column to the left. The cursor will also wrap around from the right top tile to the  
left bottom tile and back.  
There are three different types of tiles to be defined: the environmental unit, the LT750 and sensor  
cable tiles. To set up the cable layout, first move the cursor to the location of the environmental unit  
and press the ENTER key. A rectangular box will be drawn at that location. Then move the cursor to  
the location of the LT750 and press the ENTER key. A solid circle will be drawn on the display. No  
tile can have two definitions, so if the LT750 is physically directly under the unit it must be defined at  
least one tile away.  
The sensor cable should not be defined one tile at a time. The only sensor cable tiles that need to be  
defined are the tiles where the cable is going to change direction, and the last tile. The display will  
automatically define any tiles between two consecutively defined sensor tiles to be sensor tiles.  
The ENTER key is also used to undo tile definitions. If a tile is defined in the wrong place, position  
the cursor on that tile and press the ENTER key. It will undefine the tile under the cursor and move  
the cursor back to the last defined tile. The entire layout can be erased by successively pressing the  
ENTER key. When the last tile is defined, press the ESCape key to leave the setup screen.  
For more information and detailed installation instructions, see 4.5.2 - Water Detection Display.  
19  
     
Operation with Advanced Microprocessor with Graphics Control  
3.5  
Operating Status  
The Operating Status is intended to provide the user with displayed information about what the con-  
trol is calling for the system to do.  
NOTE  
There may be some time lapse before a specific component matches the displayed number.  
For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it  
takes several seconds for the valve to travel from full closed to 68% open. So when the display reads  
68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com-  
pressor is operating but the compressor has not turned on yet, it may be off because of the short cycle  
control (see 4.4.1 - Short Cycle Control).  
3.6  
View/Set Control Setpoints  
Control setpoints can be reviewed and/or changed through the display. Refer to the following table to  
see the list of default setpoints and their allowable ranges.  
Table 8  
Default setpoints and ranges  
Setpoint  
Default  
72°F  
2.0°F  
50%  
Range  
40 to 90°F (5 to 32°C)  
1 to 9.9°F (0.6 to 5.6°C)  
20 to 80% RH  
Temperature Setpoint  
Temperature Sensitivity  
Humidity Setpoint  
Humidity Sensitivity  
5%  
1 to 30% RH  
High Temperature Alarm  
Low Temperature Alarm  
High Humidity Alarm  
Low Humidity Alarm  
80°F  
65°F  
60%  
35 to 95°F (2 to 35°C)  
35 to 95°F (2 to 35°C)  
15 to 85% RH  
40%  
15 to 85% RH  
3.7  
System Setup  
Selecting SYSTEM SETUP will step to the following menu:  
• SETUP OPERATION  
• SELECT OPTIONS  
• CALIBRATE SENSORS  
• CALIBRATE VALVE ACTUATOR  
• SELECT CONTROL ALGORITHM (chilled water or SCR Reheats only)  
• SELECT HUMIDITY SENSING MODE  
• SET STATUS DISPLAY  
• CHANGE PASSWORDS  
3.7.1 Setup Operation  
The SETUP OPERATION menu permits the review and/or adjustment of the unit configuration. This  
may include:  
Cold Start Delay  
This feature, also referred to as Positive Start or Winter Start Kit, allows for the low pressure switch  
to be ignored for the programmed time during a cold start of the compressor. Entering a “0” for this  
time will bypass this feature. A “1” will bypass the low pressure switch for one minute, a “2” for two  
minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is factory set to 0 for  
water cooled, glycol cooled, and GLYCOOL units. Typically, only air cooled units need a “Winter  
Start” time.  
20  
         
Operation with Advanced Microprocessor with Graphics Control  
Auto Restart Delay  
This feature allows for the unit to restart automatically after a loss of power. The programmed value  
is .1 minute (6 seconds) intervals. A programmed value of zero (0) would require the user to manually  
press the ON/OFF switch to start the unit, i.e. no auto restart. The purpose of this feature is to pre-  
vent several units from starting at the same time after a loss of power. The message “Restart Delay --  
Please Wait” will be displayed when the system is in the auto restart mode. Liebert suggests pro-  
gramming multiple unit installations with different auto restart times.  
IR Flush Overfill (infrared humidifiers only)  
An autoflush system automatically controls a water makeup valve to maintain proper level in the  
infrared humidifier water pan during humidifier operation. If humidification is needed and 30 hours  
have elapsed since the last time the humidifier was on, then the humidifier is held off until the valve  
completes an initial fill of the humidifier pan. This pre-fill is about 15 seconds. The valve continues to  
fill and flush the pan for about 4 minutes.  
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-  
odically to add water to the pan (about 40 seconds for every 9-1/2 minutes of humidifier operation).  
This adds enough water to the pan to cause about a third of the total water used to be flushed out the  
overflow standpipe located in the humidifier pan. This flushing action helps remove solids from the  
pan. The flush rate is adjustable from 110% to 500%. If the water quality is poor, it may be desirable  
to increase the water flushing action above the normal 150% rate. Also, if the supply water pressure  
is low, the flush rate adjustment can be increased so that sufficient water level is maintained during  
humidification.  
Chilled Water/Hot Water/Econ-O-Coil Flush  
This feature will flush the respective coil for 3 minutes after the programmed number of hours of  
non-use. For example, if the flush time is programmed with 24 hours on a hot water reheat type sys-  
tem, and heating is not required for a 24 hour period, the hot water valve will be opened for 3 minutes  
to allow the coil to be flushed. The programmed value can be from 0 (no flush) to 99 (99 hours of  
non-use).  
Display in Degrees  
The control can be set to display readings and setpoints in either degrees Fahrenheit (F) or  
Celsius (C).  
Default Settings and Ranges  
The following table lists the setup functions, their factory default values, and the allowable ranges for  
which they can be programmed.  
Table 9  
Setup functions, default values and ranges  
Function  
Default  
Range  
Cold Start Time Delay*  
Restart Time Delay  
Infrared Fill Rate  
3
0.1  
150  
24  
F
0 to 3 min (0 = no delay)  
0 to 9.9 min (0 = manual restart)  
110 to 500%  
Chilled/Hot Water Coil Flush  
C/F Degrees  
0 to 99 hrs (also Econ-O-Coil)  
C or F  
*Factory set to 0 for water cooled, glycol, and GLYCOOL units.  
21  
 
Operation with Advanced Microprocessor with Graphics Control  
3.7.2 Select Options  
The following table is a list of options which should match the options installed with your unit and  
should not need to change during normal operation.  
Table 10 Unit options  
Option  
Selection  
YES or NO  
YES or NO  
YES or NO  
YES or NO  
2
1
Reheat  
Humidity  
Dehumidify  
Hot Gas Reheat  
2
3
Stages of Reheat  
1Heating cannot be disabled on units with SCR reheats.  
2Hot gas reheat not available on units with SCR reheats.  
3Heat stages not selectable on units with SCR reheats.  
3.7.3 Calibrate Sensors  
The temperature and humidity sensors can be calibrated by selecting this menu item. “SENSOR”  
shows the actual sensor reading or raw reading. “CALIBRATED” shows the sensor reading after the  
calibration offset has been added. The temperature sensor can be calibrated ±5°F and the humidity  
sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value shown will  
always be % RH, even though absolute humidity control may be selected. If absolute humidity control  
is selected, the Normal Status Display will display the adjusted reading and may not agree with the  
relative humidity reading displayed while in calibration.  
3.7.4 Calibrate Valve Actuator  
For systems that use a valve actuator for chilled water or GLYCOOL cooling, the actuator timing may  
be calibrated or adjusted. This is the time it takes for the valve to travel from full closed to full open.  
It is programmable from 0 to 255 seconds. The factory default time is 165 seconds and should not be  
changed unless the actual valve travel time is not correct. The full valve travel time is used by the  
control to determine the appropriate valve position. For example, if the valve travel time is 165 sec-  
onds and 50% cooling is being called for, the valve will open for 83 seconds to achieve 50% open. To  
change the valve travel time, first enter the “CALIBRATE ACTUATOR” screen. The display will show  
the present period used by the control for valve actuator full travel. Press ENTER and adjust the time  
using the UP/DOWN arrows. When the correct time is displayed, press ENTER to store the new time  
to memory.  
3.7.5 Select Control Algorithm (Chilled Water and SCR Reheats only)  
The type of system control method used by the microprocessor can be selected from the front panel.  
The default setting is INTELLIGENT, which approximates the actions that a human operator would  
take to maintain precise, stable control. The control logic uses Artificial Intelligence techniques  
including “fuzzy logic” and “expert systems” methods to maintain precise, stable control and increase  
reliability by reducing component cycles. PROPORTIONAL is a standard control method that uses  
one gain factor (temperature sensitivity adjustment). TUNABLE PID (Proportional, Integral, and  
Derivative) uses three gain factors selected by the operator. PID allows precision tuning, but requires  
an experienced operator and seasonal adjustments. Note that if PID is selected, it is used for temper-  
ature control while humidity will continue to use proportional control. For chilled water units with  
the optional Variable Speed Drive, Intelligent is required for proper operation. Refer to 4.0 - System  
Performance with Advanced Microprocessor Controls for more details on types of control.  
22  
         
Operation with Advanced Microprocessor with Graphics Control  
3.7.6 Select Humidity Sensing Mode  
The user may select between RELATIVE (direct) and ABSOLUTE (predictive) humidity control. If  
relative is selected, the RH control is taken directly from the RH sensor. If absolute is selected, the  
RH control is automatically adjusted as the return air temperature deviates from the desired temper-  
ature setpoint. This results in a predictive humidity control. The display will indicate % RH for both  
methods of control, but the adjusted humidity reading will be displayed if absolute is selected. With  
absolute humidity control, the humidity control is automatically adjusted approximately 2% RH for  
each degree difference between the return air temperature and the temperature setpoint.  
With relative humidity control, unnecessary dehumidification can result when overcooling occurs dur-  
ing a dehumidification cycle. This is because a higher than normal RH reading is caused by overcool-  
ing the room (about 2% RH for each degree of overcooling). This extends the dehumidification cycle.  
Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading  
falls. The final RH reading will then be lower than actually desired. If the overcooling was significant  
enough, the RH could be low enough to activate the humidifier.  
If absolute humidity control is selected, over-dehumidification is avoided. When overcooling occurs,  
causing an increase in the RH reading, the humidity control program “predicts” what the RH will be  
when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehu-  
midification cycle to end at the proper time. The predictive humidity control can reduce energy con-  
sumption by minimizing compressor and reheat operation, and eliminating unnecessary humidifier  
operation.  
3.7.7 Set Status Display  
The Status Display can be set to display the return air temperature and humidity SENSOR READ-  
INGS or the temperature and humidity control SETPOINTS through this selection. When setpoints  
are selected, the status display indicates so by also displaying “SETPOINTS.” If SENSOR READ-  
INGS is selected, the Status Display will show the return air sensor readings.  
3.7.8 Change Passwords  
Selecting CHANGE PASSWORDS will prompt the user to select one of the following:  
• SETPOINT PASSWORD  
• SETUP PASSWORD  
The display prompts you to enter a three digit password when making changes. The system includes  
two (2) passwords, one for setpoints and one for system setup. The system allows the passwords to be  
changed by first entering the present password, factory set as “123” for setpoints and “321” for setup.  
The password function provides system security, so only personnel authorized to make changes  
should know the passwords. If unauthorized changes are being made, the passwords may be compro-  
mised and new ones should be selected. The password function can be disabled by setting DIP switch  
8 to OFF.  
3.8  
Run Diagnostics  
By selecting RUN DIAGNOSTICS, maintenance personnel can check system inputs, outputs, and  
complete a test of the microcontroller circuit board, all from the front panel. Review of the system  
inputs and the microcontroller test can be done without interrupting normal operation.  
23  
       
Operation with Advanced Microprocessor with Graphics Control  
3.8.1 Show Inputs  
With the unit on and the fan running, the input state for the following devices may be displayed:  
• Air Sail Switch: normally off unless Loss of Air Alarm is active  
• Custom Alarm #1: normally off unless this alarm is active  
• Custom Alarm #2: normally off unless this alarm is active  
• Custom Alarm #3: normally off unless this alarm is active  
• Custom Alarm #4: normally off unless this alarm is active  
• Humidifier Problem: normally on unless this alarm is active  
• Filter Clog Switch: normally off unless Change Filters Alarm is active  
• Main Fan Overload: normally on unless Main Fan Overload Alarm is active  
• Shutdown Device: normally on unless unit is off through the Fire Stat or Remote Shutdown  
Device  
• Low Pressure Switch: normally on if compressor circuit 1 is in operation  
• Compressor Overload: normally on unless Compressor 1 Overload Alarm is active  
• High Head: normally off unless High Head Pressure alarm is active  
3.8.2 Test Outputs  
When this feature is selected, the unit is effectively turned off. When stepping from one load to the  
next the previous load, if on, is turned off automatically. The loads can also be toggled on/off by select-  
ing “ENTER.” Once turned on, the output will remain on for 5 minutes unless toggled off or the test  
outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 seconds on to pre-  
vent damage.) DO NOT leave the unit in the test outputs mode any longer than is necessary for trou-  
bleshooting. The outputs are as follows:  
• Main Fan: main fan contactor  
• Compressor: compressor contactor  
• LLSV: liquid line solenoid valve  
• HGBP/CUV: hot gas bypass or compressor unloader valve (on certain units)  
• Part Coil: Part Coil Solenoid Valve  
• CWV/CGV: chilled water or GLYCOOL valve  
• R5 Relay: Relay 5 (heat rejection)  
• Reheat 1: Reheat 1 contactor or SCR Reheats (also energizes fan for safety)  
• Reheat 2: Reheat 2 contactor (also energizes fan for safety)  
• HWR: hot water solenoid valve  
• Humidifier: humidifier contactor (also energizes humidifier makeup valve and fan for safety)  
• HMV: humidifier makeup valve  
• Common alarm: common alarm relay  
CAUTION  
!
Do not test a compressor output for more than a few seconds.  
Compressor damage could result!  
3.8.3 Test Control Board  
By selecting this function, the microcontroller will perform a self test lasting approximately 10 sec-  
onds. At the end of the test, the ROM checksum, ROM part number and version number will be dis-  
played.  
24  
     
Operation with Advanced Microprocessor with Graphics Control  
3.8.4 DIP Switches  
The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires  
opening the front panel for access to the DIP switches on the microprocessor control board.  
NOTE  
Power MUST be cycled off, then on, from the unit disconnect switch for the control system  
to update the DIP switch settings (except for switch 8).  
These selections should match options installed on your unit and should not need to change during  
normal operation. Switches 1 through 7 are self explanatory. DIP switch 8, not shown in Table 11,  
below, enables the password feature when set to ON and disables the password feature if set to OFF.  
Table 11  
Setting options  
Switch #  
Off  
No Part Coil  
Electric/Hot Gas Reheat  
All  
On  
Part Coil/Chilled Water  
Hot Water Reheat  
Not Used  
1
2
3
4
5
6
No GLYCOOL  
No Dual Cooling  
Not Used  
GLYCOOL  
Dual Cooling  
Not Used  
a
7
Tight Control  
Standard Control  
a
SCR reheats only (with special software); otherwise, not used.  
3.9  
Date and Time  
The current date and time is available through the display. This feature allows the date and time to  
be read or changed and is accessed by selecting “DATE AND TIME” from the Main Menu. The “DATE  
AND TIME” is used by the control for recording the Alarm History and plotting graphs.  
NOTE  
The clock uses the 24 hour system (For example: 17:00 would be 5:00 PM). The date and time  
are backed up by battery.  
3.10 Plot Graphs  
Selecting PLOT GRAPHS will step to the following menu:  
• TEMPERATURE PLOT  
• HUMIDITY PLOT  
• ANALOG SENSOR #1 PLOT  
• ANALOG SENSOR #2 PLOT  
• ANALOG SENSOR #3 PLOT  
• ANALOG SENSOR #4 PLOT  
• MODIFY PLOT SCALES  
Six different data types are recorded for graphing: temperature, humidity, and four user defined ana-  
log inputs. Each data type can be viewed over three different time scales and two different resolu-  
tions. The three time scales are 90 minutes, 8 hours, and 24 hours. The two resolutions are minimum  
and maximum. With minimum resolution selected, the full scale of the sensor is displayed. In other  
words, the largest and smallest possible sensor readings are shown. Maximum resolution shows a  
range that covers two-fifths of the full scale sensor range.  
3.10.1 Modify Plot Scales  
The MODIFY PLOT SCALES menu item adjusts the layout of the graph. This setup screen selects  
the time scale and resolution. It also adjusts the center of the graph for a maximum resolution graph.  
The time scale and resolution can also be changed while the graph is displayed. The DOWN arrow key  
changes the time scale from 90 minutes, to 8 hours, to 24 hours. The UP arrow key toggles the display  
between maximum and minimum resolution.  
25  
         
Operation with Advanced Microprocessor with Graphics Control  
3.11 Analog/Digital Inputs  
Selecting ANALOG/DIGITAL INPUTS steps to the following menu:  
• READ ANALOG INPUTS  
• SETUP ANALOG INPUTS  
• READ DIGITAL INPUTS  
• SETUP DIGITAL INPUTS  
3.11.1 Read Analog Inputs  
The four (4) analog sensor inputs can be monitored from the display. The inputs are filtered, then dis-  
played along with the text label assigned during setup.  
3.11.2 Setup Analog Inputs  
For installation of analog sensors, see Analog Setup on page 11.  
After selecting a compatible sensor and properly wiring it to the terminals, set the control to monitor  
the sensor according to the following instructions.  
Slope  
The slope is a multiplier used to scale the input signal. The slope can be positive (rising) or negative  
(falling) and can range from 0 (resulting in a horizontal line) to ±999. The slope for a 0-5 volt input is  
per 1 volt input; for 0-10 volt input, it is per 2 volt input; and for 4-20 mA, it is per 4 mA input. For  
example, assuming an intercept of 0, for a 0-10 volt sensor input with a slope of 50, an input of 1 volt  
would be displayed as 25: 1x(50/2); 2 volts would be 50: 2x(50/2); 3 volts would be 75: 3x(50/2); etc.  
Intercept  
The intercept is an offset from point 0 corresponding to 0 volts or 0 mA input. The intercept can be  
positive or negative and can be a point from 0 to ±999. Adding an intercept of 100 to the slope example  
above, 1 volt would be 125: 100 + (1x[50/2]); 2 volts would be 150: 100 + (2x[50/2]); 3 volts would be  
175: 100 + (3x[50/2]); etc.  
NOTE  
For a 4-20 mA input sensor, if the desired reading at 4 mA input is 0, then an intercept  
of -1 x slope would be required. For example, assuming a slope of 50, the formula would  
be ([-1 x 50] + 4 x [50/4]) = 0. The intercept is -50.  
Text  
You may enter a custom label for each analog input. The text label can be 20 characters in length  
including any of the following:  
ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789, or space.  
3.11.3 Read Digital Inputs  
The four custom alarm inputs can be defined to be digital inputs. Digital inputs are used to sense cus-  
tomer devices for status display purposes only and will not activate the audible alarm.  
3.11.4 Setup Digital Inputs  
A digital input is enabled by defining one of the four custom alarms to be STATUS ONLY type in the  
alarm setup screen. The digital input is given a name by specifying it to be one of the optional alarms  
or a custom text alarm. See 3.4.3 - Setup Alarms and 3.4.4 - Setup Custom Alarms.  
3.12 View Run Hours Log  
Selecting VIEW RUN HOURS LOG will step to the following menu:  
• VIEW 24 HOUR RUN TIME HISTORY  
• VIEW TOTAL RUN HOURS  
26  
           
Operation with Advanced Microprocessor with Graphics Control  
3.12.1 View 24 Hour Run Time History  
The history of each load for every hour during the past 24 hours is displayed in the run hour history.  
The percentage of each hour that the load was on is displayed from 0 to 100% in increments of 5% or  
3 minutes. Loads with a variable output are displayed as a percentage of their capacity for an hour.  
For example, a variable load that is 50% on for 1/2 of the hour will be displayed as 25% on for that  
hour.  
3.12.2 View Total Run Hours  
The total operating hours of all major components in the unit can be monitored from the display and  
are retained in nonvolatile memory. Run times are available for the following:  
• Compressor  
• GLYCOOL Coil (or Chilled Water Coil as used on Dual Cool Units)  
• Fan  
• Humidifier  
• Reheat 1 (or Hot Water Reheat or SCR Reheats)  
• Reheat 2  
• Heat Rejection  
The component run hours for each individual component can be reset by selecting the run hours dis-  
play screen for the desired component, then pressing ENTER within 5 minutes of applying power to  
the control. The user will then be prompted to press ENTER to clear the selected component's run  
hours.  
NOTE  
Run hours for a component should be reset ONLY when the component has been replaced.  
3.13 Control Circuit board  
The control circuit board is located inside the unit behind the LCD display and control key panel.  
Open the front panel for access to the board.  
The control board includes an adjustment for LCD contrast, nonvolatile memory, DIP switches (which  
should not require customer changes), control output LEDs, and jumpers for board configuration. The  
jumpers should be placed as follows:  
• P5—removed  
• P12—removed  
• P19—installed on Pins 1 and 2  
• P47— installed on Pins 1 and 2  
• P48—installed on Pins 1 and 2  
• P50—all jumpers installed for 4-20 mA analog inputs. See 4.5.1 - Connecting the Analog Sen-  
sors for other configurations.  
• P51—removed  
3.13.1 LCD Contrast  
The level of contrast due to the viewing angle of the LCD can be adjusted using a small thumb wheel  
at the upper left of the control board just under the cable going to the display. The control is labeled  
RA1.  
NOTE  
The LCD backlighting will turn on when any key is pressed and will go off 5 minutes after  
the last key is pressed.  
27  
       
Operation with Advanced Microprocessor with Graphics Control  
3.13.2 Nonvolatile Memory  
All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component  
run hours are kept inside the microcontroller in EEPROM. Information retained for data logging,  
24 hour component run hour graphs, alarm history, and the water detection floor plan is kept in non-  
volatile RAM.  
3.13.3 DIP Switches  
Equipment options are selected and enabled using DIP switches 1 to 7. These are located at the upper  
left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory set  
and should not require any user changes. The setting and function of the switches can be read from  
the LCD (see 3.8.4 - DIP Switches).  
3.13.4 Control Outputs  
Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is  
lit if the control output is active (on). Use these LEDs to assist in troubleshooting the system.  
Table 12 Control output LEDs  
LED  
R5  
Control Output  
Heat Rejection  
Liquid Line Solenoid Valve  
LLSV  
HGBP Hot Gas By-Pass  
C1  
Compressor  
RH1  
Reheat Stage 1 or Hot Gas, Hot Water Reheat Solenoid  
or SCR Reheats  
RH2  
HUM  
FAN  
HMV  
Reheat Stage 2  
Humidifier  
Main Fan  
Humidifier Make-Up Valve  
LLSV2 Part Coil Solenoid Valve  
28  
       
System Performance with Advanced Microprocessor Controls  
4.0 SYSTEM PERFORMANCE WITH ADVANCED MICROPROCESSOR CONTROLS  
This section provides details on how your Challenger 3000 unit responds to user inputs and room con-  
ditions. Refer to this section when you need specific information. This section includes details on con-  
trol.  
4.1  
Temperature Control  
4.1.1 Cooling/Heating Required, in Percent (%)  
The temperature control program for the advanced microprocessor is based on a calculated % require-  
ment for cooling/ heating.  
4.1.2 Response to Control Types  
Proportional Control  
The % requirement is determined by the difference between the return air temperature and the tem-  
perature setpoint. As the return air temperature rises above the temperature setpoint, the % cooling  
required increases proportionally (from 0 to 100%) over a temperature band equal to the temperature  
sensitivity plus 1°F. The % heating requirement is determined the same way as the temperature  
decreases below the setpoint. With this type of control the temperature at which the room is con-  
trolled increases as the room cooling load increases. At full cooling load the room would be controlled  
at a temperature equal to the setpoint plus the sensitivity.  
For systems with SCR Reheats, the % requirement is determined only by the difference between the  
return air temperature and the temperature setpoint. This permits tighter temperature control. The  
SCR Reheats are controlled in a proportional manner inversely as described above for cooling. When  
the return air temperature is at the temperature setpoint, the SCR Reheats will be on 100%. As the  
temperature increased to the temperature setpoint plus the temperature sensitivity, the SCR Reheats  
will be pulsed proportionally from full on to full off (0% to 100%) until the return air temperature  
reaches the temperature setpoint plus the temperature sensitivity.  
PID Control (Chilled Water or SCR Reheats only)  
If PID control is selected, the return air temperature is controlled at or near the temperature setpoint  
independent of the room load. The % cooling/heating requirement is calculated by adding together  
three individual terms - proportional, integral, and derivative.  
The proportional term is figured in a manner similar to the previously described proportional control.  
The integral term (sometimes called “reset action”) is figured by measuring how much and for how  
long the temperature has been above or below the setpoint. If the temperature is above the setpoint,  
the % cooling requirement is slowly but continuously increased until the total is sufficient to bring the  
temperature back to the setpoint. The derivative term provides an anticipation control for rapid  
changes in temperature. If the temperature is rising, the % cooling is increased temporarily until the  
temperature begins to stabilize. The % heating requirement is increased if temperature is falling.  
The proportional, integral, and derivative terms are all adjustable through the control selection menu  
and should be set or “tuned” to the characteristics of the room being controlled (see 4.3 - Control  
Types).  
Intelligent Control (Chilled Water only)  
If intelligent control is selected, the return air temperature is controlled at or near the temperature  
setpoint. The % cooling/heating required is calculated based on a set of logical “rules” that are pro-  
grammed into the control. These “rules” simulate the actions that an expert human operator would  
take if manually controlling the system (see 4.3 - Control Types).  
29  
       
System Performance with Advanced Microprocessor Controls  
4.1.3 Cooling Operation  
1-Step Cooling, Compressorized Direct Expansion (DX) Systems  
Cooling activates when the temperature control calculates a requirement for cooling of 100%. It is  
deactivated when the cooling requirement drops below 50%. The hot gas bypass is energized on a call  
for cooling unless there is also a call for dehumidification.  
To aid in lubricating the compressor, the hot gas bypass solenoid is delayed for 30 seconds on the ini-  
tial call for cooling and de-energized for 30 seconds during every 60 minutes of continuous operation.  
2-Step Cooling, Compressorized Direct Expansion (DX) Systems with Part Coil (optional)  
Cooling activates when the temperature control calculates a requirement for cooling of 50%. If the  
system is designed for part coil operation, part coil is active and the hot gas bypass would be acti-  
vated. At 100% cooling requirement, operation would be full coil and the hot gas bypass would be acti-  
vated. When the cooling requirement drops to 75%, the system returns to part coil, and turns off the  
compressor when the requirement drops to 25%.  
Table 13 Cooling/dehumidification load status response  
LLSV2  
LLSV1  
On  
Part Coil  
Off  
HGBP  
On  
1 Step Cooling Only  
2 Step Cooling Only  
On  
On  
On  
Dehumidifying Only  
On  
Off  
Off  
1 Step Cooling w/Dehumidifying  
2 Step Cooling w/Dehumidifying  
On  
Off  
Off  
On  
On  
Off  
GLYCOOL Cooling  
When GLYCOOL cooling is available, the temperature control will calculate a total cooling require-  
ment of 200% rather than 100%. Assuming that full GLYCOOL capacity is available, the GLYCOOL  
valve opens proportionally as the requirement for cooling rises from 0 to 100%. If more than 100%  
cooling is required, then the compressor is activated at 200%. If full GLYCOOL capacity is not avail-  
able, then the GLYCOOL valve will be opened proportionally over a cooling requirement band equal  
to the available GLYCOOL capacity. The compressor would be activated at a cooling requirement of  
100% above the available GLYCOOL capacity.  
For example, if the GLYCOOL capacity is 60%, then the GLYCOOL valve would be full open at 60%  
cooling requirement and the compressor would be in full cooling at 160%. In order to reduce compres-  
sor cycling and prevent hunting, GLYCOOL capacity first becomes available when the entering glycol  
temperature is at least 8°F (22% capacity) below the return air temperature, or 3°F below the return  
air temperature for 2 hours. GLYCOOL capacity approaches 100% when the glycol temperature is 25  
degrees F below the return air temperature. The system will continue to Econ-O-Cool as necessary as  
long as the entering glycol temperature remains at least 3°F (0% capacity) below the return air tem-  
perature. If GLYCOOL is not available, the temperature control will operate the compressor in the  
same manner as a 1-step or 2-step system without GLYCOOL. The control will not permit compressor  
operation if the chilled water temperature is below the minimum chilled water temperature selected  
through the SETUP OPERATION menu.  
Dual Cooling Source  
If dual cooling is available, the sensible cooling system operates in the same manner as a GLYCOOL  
system, except that it is assumed that 100% chilled water capacity is available any time the chilled  
water temperature is 3°F cooler than the return air temperature.  
Chilled Water Cooling  
The chilled water control valve is adjusted proportionally as the temperature control varies the  
requirement for cooling from 0% to 100%.  
30  
   
System Performance with Advanced Microprocessor Controls  
4.1.4 Heating Operation  
Electric Reheat  
The two heat stages are activated when the temperature control calculates a requirement of 50% and  
100%, respectively. Each stage is deactivated when the heat requirement is 25% less than the activa-  
tion point.  
Hot Water Reheat  
The solenoid valve opens when the requirement for heating is 100% and closes when the requirement  
drops below 50%.  
SCR Electric Reheat (Requires Special Control Software)  
The SCR (Silicon Controlled Rectifier) controller shall proportionally control the stainless steel  
reheats to maintain the selected room temperature. The rapid cycling made possible by the SCR con-  
troller provides precise temperature control, and the more constant element temperature improves  
heater life. During operation of the SCR control, the compressor operates continuously. The heaters  
are modulated to provide temperature control.  
On units equipped with SCR Reheats, unit operation can be controlled even further with DIP switch  
#7 on the control board. With DIP switch #7 in the “OFF” position, or “Tight Control,” the compressor  
is locked on and the SCR Reheats are modulated for very tight temperature control. In the event of a  
malfunction of the SCR Reheats, the compressor will be turned off if the temperature drops to the  
Low Temperature Alarm Setpoint. With DIP switch #7 in the “ON” position or “Standard Control,”  
the compressor will cycle on and off as required to satisfy the requirements for cooling and dehumidi-  
fication in a similar manner as a standard unit without SCR Reheats, i.e., Temperature Setpoint  
PLUS Temperature Sensitivity PLUS 1°F. The SCR Reheats are modulated from 0% to 100% as  
required to satisfy the requirements for heating over a control band from the Temperature Setpoint  
MINUS the Temperature Sensitivity MINUS 1°F.  
4.2  
Humidity Control  
4.2.1 Dehumidification/Humidification Required, in Percent  
The humidity control program for the Advanced Microprocessor is based on a calculated % require-  
ment for dehumidification/ humidification.  
4.2.2 Response to Control Types  
Proportional Control  
The % requirement is determined only by the difference between the return air humidity and the  
humidity setpoint. As the return air humidity rises above the humidity setpoint, the % dehumidifica-  
tion required increases proportionally from 0 to 100% over a humidity band equal to the humidity  
sensitivity setting. The converse is true for % humidification requirement.  
PID Control (Chilled Water or SCR Reheats only)  
If PID control is selected, humidity is controlled in the proportional mode with the sensitivity band  
being determined by the humidity sensitivity setpoint.  
Intelligent Control (Chilled Water only)  
If intelligent control is selected, the return air humidity is controlled at or near the humidity setpoint.  
The % dehumidification/humidification required is calculated based on a set of logical “rules” that  
simulate the actions of an expert human operator (see 4.3.3 - Intelligent Control (Chilled Water  
only)).  
4.2.3 Dehumidification Operation  
1-Stage Dehumidification, Compressorized Direct Expansion (DX) Systems  
Dehumidification with the standard configuration is accomplished by operating the compressor with-  
out hot gas bypass active. If system has part coil, dehumidification is accomplished by using only part  
coil. If the installation has a very light sensible load, dehumidification will be inhibited at the point at  
which 125% heating would be required to prevent overcooling. Dehumidification would be enabled  
when the temperature increases to the point where only 50% heating is required.  
31  
         
System Performance with Advanced Microprocessor Controls  
4.2.4 Humidification Operation  
System Activation  
The humidifier (infrared or steam) is activated when the humidity control calculates a requirement of  
100% humidification, and deactivated when the requirement falls below 50%.  
4.3  
Control Types  
4.3.1 Proportional Control  
This is a standard control method that maintains the room at a temperature proportional to the load.  
The temperature maintained increases as the room load increases. At full load the room would be con-  
trolled at a temperature equal to the temperature setpoint plus the temperature sensitivity. If propor-  
tional control is selected, the gain is factory set and cannot be adjusted by the user. Operator inputs  
are the usual setpoint and sensitivity adjustments.  
4.3.2 PID Control (Chilled Water or SCR Reheats only)  
The PID control combines three individual terms to determine the control output for a given set of  
conditions. Note that PID control is used only for temperature. If PID control is selected, humidity  
will continue to use proportional control.  
The proportional (P term) is determined by the difference between the current temperature and the  
control setpoint. This term is expressed in % cooling (heating) desired for each degree above (below)  
the setpoint. It is adjustable from 0% to 100% per degree. The purpose of this term is to adjust the  
control output for any deviation between the current temperature and the control setpoint.  
The integral (I term) is determined by two things: the difference between the temperature and control  
setpoint and the amount of time this difference has existed. This term is expressed in % cooling (heat-  
ing) desired for each minute and degree above (below) the setpoint. It is adjustable from 0% to 100%  
per degree-minute. The purpose of this term is to force the control to maintain the temperature  
around the setpoint by slowly but continuously adding (subtracting) a small amount of cooling (heat-  
ing) to the total control output until the temperature is at the setpoint.  
The derivative (D term) is determined by the rate of change of temperature. This term is expressed in  
% cooling (heating) desired for each degree per minute rise (fall) in temperature. It is adjustable from  
0% to 100% per degree/min. The purpose of this term is to adjust the control output for quickly chang-  
ing temperatures, thus providing an anticipation control.  
All three terms are adjusted through the “select control type” menu. If PID control is selected, the  
temperature sensitivity setting is not used by the control.  
For optimum performance, a PID control must be adjusted or tuned according to the characteristics of  
the particular space and load to be controlled. Improper tuning can cause the control to exhibit poor  
response and/or hunting. The characteristics of the space and load may change seasonally, so occa-  
sional retuning is required for optimum performance.  
32  
       
System Performance with Advanced Microprocessor Controls  
A suggested tuning procedure is as follows:  
1. Initially adjust the integral and derivative settings to 0%/ degree-min and 0% /degree/min.  
2. Starting with 20% /degree, adjust the proportional setting in small increments (10% steps) until  
the control sustains a constant hunting action (the temperature swings are approximately the  
same amplitude from one peak to the next).  
3. Note the time in minutes between peaks of adjacent temperature swings and the amplitude of the  
temperature swing (degrees above the setpoint).  
4. Adjust the proportional control setting to about 1/2 the value obtained in Step 2.  
5. Adjust the integral setting to a value calculated by the following equation:  
Approximate room load (in % full load)  
Time between peaks x peak amplitude x 4  
NOTE  
If this calculation results in a value of less than 1%, then set the integral to 1%.  
Adjust the derivative to a value calculated by the following equation:  
time between peaks x 5%  
The above tuning procedure is only an approximation for an initial set of adjustments and are based  
on the “average” room characteristics. Your particular settings may need to be further adjusted for  
optimum PID control performance. Some suggestions for additional tuning are as follows:  
• If cooling output overshoot is occurring on load changes, decrease the proportional setting or the  
derivative setting.  
• If system hunting occurs with constant room load, decrease the integral setting.  
• If the control responds too slowly, resulting in large temperature excursions on a load change,  
increase the proportional setting or the derivative setting.  
• If a constant temperature deviation exists between the temperature and setpoint, increase the  
integral setting.  
4.3.3 Intelligent Control (Chilled Water only)  
The intelligent control operates from a set of general rules that define how the control output should  
be adjusted for different system conditions. The rules are designed to duplicate the actions that an  
experienced human operator would take if manually controlling the system.  
Just as an operator might take several things into consideration before making a temperature control  
decision, the intelligent control can be programmed to do likewise. For example, not only is the cur-  
rent temperature used in making temperature control decisions, but also conditions such as:  
• How fast is the temperature changing?  
• What direction is the temperature changing?  
• What is the cooling output now?  
• What was the cooling output in the past?  
• How long ago was the cooling output changed?  
• and other factors.  
Any number of rules can be used in an intelligent control to define the controls operation under vari-  
ous operating conditions. Hence, several advantages are gained from this type of control over a more  
standard control approach that uses a fixed mathematical equation to define the operation of the con-  
trol for all conditions (such as a proportional or PID control). You can expect intelligent control to be  
more efficient and precise for most applications, but system performance based on room conditions is  
not as predictable as standard approaches that use a fixed equation.  
33  
   
System Performance with Advanced Microprocessor Controls  
4.4  
Load Control Features  
4.4.1 Short Cycle Control  
The control system monitors the compressor and prevents it from turning on within 3 minutes of  
being turned off. If this (on, off, on) occurs too often, 10 times in one hour, a Short Cycle alarm could  
occur.  
4.4.2 Sequential Load Activation Control  
The control allows only one load output to be energized at a time on a restoration of power or micro-  
controller reset. Each additional load output will be activated at one second intervals until desired  
operating conditions have been met.  
4.5  
Additional Features  
4.5.1 Connecting the Analog Sensors  
The sensor inputs are factory set to accept a 4 - 20 mA signal. However, the inputs can be changed by  
removing the appropriate jumpers on the control circuit board. See Table 14, Figure 5 and  
The user supplied analog sensors MUST have their own power supply. To reduce the effects of inter-  
ference from any noise source, the sensor input wiring should be shielded twisted pair and the shield  
tied to earth ground at one end.  
Analog input terminals for field connections are factory wired to the microprocessor board if specified  
when ordered. Eight terminals are located in the field wiring compartment of the unit. Wire sensors  
to the terminals as follows:  
Table 14 Analog input terminals  
Terminal  
Signal  
41  
42  
43  
44  
45  
46  
47  
48  
Input #1 (+)  
Input #1 (–)  
Input #2 (+)  
Input #2 (–)  
Input #3 (+)  
Input #3 (–)  
Input #4 (+)  
Input #4 (–)  
Consult your Liebert supplier for a field installation kit to add these connections after unit delivery, if  
required.  
Table 15 Additional connections available after unit delivery  
Input #1  
Input #2  
Input #3  
Input #4  
4–20 mA  
0–5 VDC  
Jumper P50.1 & 2  
and P50.3 & 4  
Jumper P50.5 & 6 Jumper P50.9 &10  
and P50.7 & 8 and P50.11 & 12  
Jumper P50.13 &14  
and P50.15 & 16  
Jumper P50.1 & 2  
Jumper P50.5 & 6 Jumper P50.9 & 10 Jumper P50.13 & 14  
0–10 VDC NO Jumper  
on P50.1 & 2  
NO Jumper  
on P50.5 & 6  
and P50.7 & 8  
NO Jumper  
on P50.9 &10  
and P50.11 & 12  
NO Jumper  
on P50.13 & 14  
and P50.15 & 16  
and P50.3 & 4  
34  
             
System Performance with Advanced Microprocessor Controls  
Figure 5 Analog input jumpers  
Analog input jumper location  
ENLARGED AREA  
4.5.2 Water Detection Display  
The water detection display is designed to graphically display the location of water under a raised  
floor when connected to an LT750 water detection system. The graphical floor plan screen shows a 30  
x 16 grid. Each square represents one standard floor tile (approximately 2 ft. x 2 ft.).  
Installation—LT750 DIP Switch Settings  
Install the LT750 following the instructions in the LT750 user manual. The following additional  
switch selections should be made when connecting to an Advanced Microprocessor control:  
• DIP SW3-4—Off-(water alarm relay energizes for alarm)  
• DIP SW3-5—Off-(cable fault relay energizes for alarm)  
• Switch 1—Off-(LT750 sources power for 4-20 mA loop)  
Figure 6 Connecting the LT750  
4 1  
-
+
4 2  
4 3  
4 4  
4 5  
4 6  
4 7  
4 8  
2
1
TB6  
NO  
3
2
1
TB5  
fault  
NC  
C
NO  
3
2
1
2 4  
5 0  
5 1  
5 5  
5 6  
NC  
C
TB4  
water  
LT750  
Environmental Unit  
35  
     
System Performance with Advanced Microprocessor Controls  
Physical Connections  
Figure 6 shows the 4-20 mA output of LT750 connected to Analog Input #1 (41 and 42) on the exter-  
nal inputs terminal strip. This strip is provided on units ordered with analog inputs. (If this strip is  
not installed, there is a field installation kit available from your Liebert representative.)  
The 4-20 mA output of the LT750 must be connected to the first analog input, as shown.  
TB4 is the water detected relay output. It can be connected to any one of the four special alarm inputs.  
TB5 is the cable fault relay output. It can also be connected to any one of the four special alarm  
inputs.  
Setup  
(The following description assumes the wiring connections as shown above.) First, verify that special  
alarms 1 and 2 are ENABLED to either WARNING or URGENT type. Do this by selecting VIEW/SET  
ALARMS from the Main Menu. Then, select SETUP ALARMS. Follow the instructions on the display  
to select the required type for CUSTOM ALARM #1 and CUSTOM ALARM #2 if not already set.  
Next, select the alarm message for CUSTOM ALARM #1 and #2. From the Main Menu, select VIEW/  
SET ALARMS. Then, select SETUP CUSTOM ALARMS. Then, select SETUP CUSTOM ALARM  
TEXT. Define CUSTOM ALARM #1 to be CUSTOM 1. (CUSTOM 1 is the default message that will be  
displayed if a message has never been programmed.) Next, select the text for custom alarm #2 to be  
WATER UNDER FLOOR. Now, change the message CUSTOM 1 to LT750 CABLE FAULT. This is  
done by selecting the CHANGE CUSTOM TEXT 1 menu item in the SETUP CUSTOM ALARMS  
menu. Follow the instructions on the screen to change the message.  
The slope and intercept values of Analog Input #1 are used to calculate the location of water. These  
values should initially be set to zero. The default values are zero, but it may be a good idea to verify  
those values. They can be viewed by selecting ANALOG/DIGITAL INPUTS from the Main Menu,  
then SETUP ANALOG INPUTS.  
See 3.4.6 - Setup Water Detect Floor Plan for more information.  
Calibration  
Calibration should not be required for most installations. The accuracy of this display is approxi-  
mately 1%.  
The display is calibrated by the slope and intercept values of Analog Input #1. The position of the  
water is calculated from the analog output of the LT750 using this formula:  
position = analog reading/full scale reading x (measured length + slope) + intercept  
position is the distance from the LT750 to the position of the detected water.  
measured length is the length of the cable which is calculated automatically when the layout is  
defined. The units for these values are in floor tiles.  
The intercept value read from Analog Input #1 is added to the measured position of a water indication  
to determine which tile to highlight. For example, if water is displayed under the seventh tile but  
determined to be under the fifth tile, set the offset value to -2 tiles. Use the intercept value to correct  
errors close to the start of the cable.  
Accuracy errors farther out on the cable should be corrected using Analog Input #1's slope value. This  
value effectively adjusts the measured length of the cable. Increasing the effective length of cable will  
increase the distance of the water and move the highlighted tile farther along the cable, and vice  
versa. Unlike the intercept, which adjusts by the same amount for all locations on the cable, the slope  
increases its effect for larger distances.  
The best procedure to calibrate the cable would be to first simulate water close to the LT750, about  
five tiles out. Adjust the intercept to get the correct reading. Next, simulate water five tiles from the  
end. Adjust the slope to get the correct reading.  
36  
System Performance with Advanced Microprocessor Controls  
4.6  
Communications  
The control system uses a two-wire, RS-422 channel to communicate with remote monitoring systems  
via Liebert Site Products. This communication, directly out of the control, uses a proprietary protocol.  
Your unit can have a variety of different Site Product devices wired to this port depending on the  
monitoring system you are using. Consult the user manual of the appropriate device for specific  
installation and operation information.  
Liebert Monitoring Devices and Software  
• SiteScan Centralized Monitoring System—Stand-alone facility monitoring system  
• SiteLink BMS Interface Module—For Modbus or BACnet communication to a third-party moni-  
toring system.  
• OpenComms Network Interface Card—For Ethernet connection using SNMP protocol.  
• OpenComms Nform—Software package to monitor SNMP devices  
• Environmental DO Interface Card—For discrete outputs of status and alarm conditions.  
• Mini-Remote—Stand-alone individual unit remote monitor  
• ECA2 Communication Adapter—For remote service monitoring directly or via a modem.  
37  
 
Alarm Descriptions  
5.0 ALARM DESCRIPTIONS  
The Advanced Microprocessor (A) and the Advanced Microprocessor with Graphics (G) Control sys-  
tems will audibly and visually annunciate all ENABLED alarms, including the four custom alarms.  
With the Advanced & Advanced with Graphics Controls, the customer alarms can be from the  
optional alarm list and/or can have their own fully custom text. Two alarms may be selected as cus-  
tom for the Advanced Microprocessor and four can be custom for Advanced Microprocessor with  
Graphics. The custom alarm inputs are 24 VAC, which is available from the Liebert unit. Alarms are  
wired from terminal 24 through a normally open contact to locations 50, 51, 55, and 56, respectively,  
for alarms 1 through 4.  
The Advanced and Advanced with Graphics alarms can be delayed from 0 to 255 seconds (for  
Advanced see Setup Alarms on page 9; for Advanced with Graphics, see 3.4.3 - Setup Alarms).  
The Advanced alarms can be ENABLED or DISABLED and can also be programmed to energize the  
Common Alarm Relay or to “alarm only” and not energize the Common Alarm Relay.  
The Advanced Microprocessor with Graphics alarms can be selected as WARNING, URGENT, or DIS-  
ABLED. If selected to be a WARNING, they are annunciated after the Time Delay, but do not ener-  
gize the Common Alarm Relay. If selected as URGENT, they are annunciated after the Time Delay as  
a WARNING alarm and then re-annunciated after a user programmable period from 0 minutes to 999  
hours as an URGENT alarm. When annunciated as an URGENT alarm, the Common Alarm Relay is  
activated. The custom alarm inputs of the Advanced Microprocessor with Graphics can be designated  
to be “Status Only.” As Status Only the custom alarm input is referenced as a digital input and is no  
longer treated as an alarm. It is for monitoring only and can be reviewed by selecting “ANALOG/DIG-  
ITAL INPUTS.”  
When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. If commu-  
nicating with a Liebert Site Product, the alarm is also transmitted. The display will also show a mes-  
sage to “PRESS ENTER KEY TO SILENCE” the alarm. After the alarm is silenced, the display will  
return to the Normal Status Display. For the Advanced Microprocessor with Graphics, the bell and  
hammer are shown at the top of the Normal Status Display. For the Advanced Microprocessor, the  
bottom line will display the number of Active Alarms. The active alarms can be reviewed on the  
Advanced Microprocessor Controls by selecting “ACTIVE ALARMS.”  
The alarms can also be silenced through communications with a Liebert Site Products unit. Most  
alarms will reset automatically when the alarm condition is no longer present and only after it has  
been acknowledged by being “Silenced.” The exceptions are:  
1. The three software alarms: Loss of Power, Low Suction Pressure, and Short Cycle, which reset  
automatically 90 minutes after being “Silenced” or acknowledged.  
2. Some alarms such as overloads and high pressure switches may require a manual reset  
depending on your model.  
A history of 10 alarms for Advanced (see 2.4.3 - Alarm History Log) and 60 alarms for Advanced  
with Graphics (see 3.4.2 - Alarm History Log) is retained in nonvolatile memory.  
This section provides a definition of each available alarm. Troubleshooting suggestions are included.  
Refer to 7.0 - Troubleshooting for more details. If you need assistance with your environmental con-  
trol system, contact your Liebert supplier.  
5.1  
Standard Alarms  
5.1.1 Change Filter  
Periodically, the return air filters in the environmental units must be changed. The Change Filter  
alarm notifies the user that filter replacement is necessary. A differential air pressure switch closes  
when the pressure drop across the filters becomes excessive. The switch is adjustable using the proce-  
dure on the switch label.  
38  
     
Alarm Descriptions  
5.1.2 Compressor Overload  
An optional tri-block overload device can be used for the compressor. Compressor overload may be  
manual or automatic reset, depending on your model. Overload is located at the electric connection  
box on the compressor.  
5.1.3 Custom Alarms  
Custom alarm messages are programmed at the LCD display. The alarms may be specified by the  
customer at the time of order. Additional devices and wiring may be required at the factory or by oth-  
ers. The message displayed may be included in this alphabetical list of alarms, or it may be custom-  
ized text (for up to two alarms). If customized text is used, customer maintenance personnel should be  
informed of the alarm function and corrective action required.  
5.1.4 High Head Pressure  
Compressor high head is monitored with a pressure switch. One SPDT pressure switch is used for the  
compressor in the unit. If head pressure exceeds 360 PSIG, the switch opens the compressor contactor  
and sends an input signal to the control. On a self-contained system, the head pressure switch located  
at the compressor requires a manual reset and the alarm condition to be acknowledged on the front  
display panel. On a split system, the high head pressure condition is acknowledged by pressing the  
alarm silence button that will clear the alarm if the high head pressure condition no longer exists. On  
a split system, if the compressor is off for 1 hour, the control goes into a special "cold start mode." In  
the cold start mode on a call for cooling or dehumidification, the Liquid Line Solenoid Valve (LLSV) is  
energized. If the high pressure switch does NOT trip within 10 seconds, the control returns to normal  
operation of monitoring the high head pressure switch for three occurrences in a 12-hour period. It is  
a rolling timer; and after the third high head alarm occurs and is acknowledged by the user, it will  
lock off the compressor. If while in the cold start mode, the high head pressure switch DOES trip  
within 10 seconds of the activation of the LLSV, the control does not annunciate the alarm. The con-  
trol will turn off the LLSV and delay 10 seconds. The control will permit this occurrence two more  
times or a total of three times. If on the fourth try the high head pressure switch trips within 10 sec-  
onds, the control will annunciate the alarm, turn off the LLSV, wait for the user to acknowledge the  
alarm, and hold the compressor off for three minutes, which is the normal short cycle control. On the  
third occurrence, the control will lock the compressor off until the control power is reset.  
On air cooled systems, check for power shut off to the condenser, condenser fans not working, defec-  
tive head pressure control valves, closed service valves, dirty condenser coils, and crimped lines. Also,  
make sure that when the compressor contactor is energized, the side switch on the contactor closes to  
energize the control circuit on the air cooled condenser.  
On water/glycol/GLYCOOL systems, check water regulating valves. Verify water/glycol flow (are  
pumps operating and service valves open?). Is water tower or drycooler operating? Is the coolant tem-  
perature entering the condenser at or below design conditions? Is relay R5 operating during cooling to  
turn on the drycooler?  
5.1.5 High Humidity  
The return air humidity has increased to the High Humidity Alarm setpoint. Is the unit setup for  
dehumidification (check DIP switch)? Check for proper setpoints. Does the room have a vapor barrier  
to seal it from outdoor humidity? Are doors or windows open to outside air? Run diagnostics to make  
sure the cooling system is working properly (the cooling system dehumidifies).  
5.1.6 High Humidity and Low Humidity (Simultaneously)  
If these two alarms are displayed at the same time, the humidity input signal is lost. Dashes will be  
displayed for the humidity reading. The control system will deactivate humidification and dehumidi-  
fication. Check for a disconnected cable or a failed sensor.  
5.1.7 High Temperature  
If the return air temperature has increased to the High Temperature Alarm setpoint, check for proper  
setpoints. Is the room load more than the unit can handle (is the unit capacity too small)? Run diag-  
nostics to make sure all cooling components are operating (compressor and/or valves).  
39  
           
Alarm Descriptions  
5.1.8 High Temperature and Low Temperature (Simultaneously)  
If these two alarms are displayed at the same time, the temperature input signal is lost (or the  
humidity is out of sensor range: 15 to 85% RH). Dashes will be displayed for the temperature reading.  
The control system will initiate 100% cooling. Check for a disconnected cable or a failed sensor.  
5.1.9 Humidifier Problem  
Infrared Humidifiers  
This alarm is activated by the high water float switch in the humidifier pan assembly. The high water  
float switch is normally closed and opens upon alarm condition. Check for drain clog and, if present,  
clean drain. Check for float switch stuck high; replace the switch as necessary. Check for proper oper-  
ation of the humidifier water makeup valve.  
Steam Generating (Canister) Humidifiers  
This alarm is activated by a signal from the humidifier control indicating that the canister needs to be  
replaced.  
5.1.10 Loss of Air Flow  
A differential air pressure switch is used to indicate loss of air flow in Challenger 3000 units.  
Check for blockage of unit air outlet or inlet. Check blower motor fuses and overload reset. Check for  
broken belts. Make sure blower wheels are tight to shaft. Run diagnostics to see if the fan contactor is  
working properly.  
5.1.11 Loss of Power  
If the unit has lost power, or the disconnect switch was turned off before the unit ON switch was  
pressed (to turn the unit Off), this local alarm will occur when power is restored to the unit. A Liebert  
remote monitoring unit (optional) will immediately indicate loss of power.  
5.1.12 Low Humidity  
If the return air humidity has decreased to the Low Humidity Alarm setpoint, check to make sure  
that the unit is setup for humidification (check DIP switch). Check for proper setpoints. Does the  
room have a vapor barrier to seal it from outdoor humidity? Are doors or windows open to outside air?  
Run diagnostics to make sure the humidifier system is working properly.  
5.1.13 Low Suction Pressure  
A pressure switch monitors the suction pressure at the compressor inlet to monitor whether pressure  
has dropped below a factory preset point while the compressor is in cooling operation. When pressure  
drops below a factory preset point, the switch opens. After the positive start kit time delay, and the  
switch stays open for five minutes, the alarm is activated. The alarm stays active for 90 minutes.  
Look for conditions that would cause loss of refrigerant. Check for piping problems such as leaks or  
crimped lines. Check for inoperative components such as liquid line solenoid valve, low pressure  
switch, expansion valve, and head pressure control valve. Check for closed service valves in the liquid  
line or at the condenser or receiver.  
5.1.14 Low Temperature  
If the return air temperature has decreased to the Low Temperature Alarm setpoint, check for proper  
setpoints. Run diagnostics to make sure all heating components are operating (contactors and  
reheats). Are reheats drawing the proper current? (See nameplate for amp rating.)  
5.1.15 Main Fan Overload  
An optional tri-block overload is required for this alarm, and may or may not replace internal motor  
overload, depending on your model. The overload device is located next to the main fan contactor in  
the line voltage section. The alarm is activated when the overload is tripped.  
40  
               
Alarm Descriptions  
5.1.16 Short Cycle  
On compressorized systems, if the compressor has exceeded 10 cooling starts in one hour or if the  
compressor has cycled five times in 10 minutes on the low pressure switch during non-cooling, the  
Short Cycle alarm will occur. This can be caused by low refrigerant level (but not low enough to acti-  
vate Low Suction Pressure alarm) or room cooling load is small compared to capacity of the unit.  
Check for leaks, crimped lines, and defective components. If room load is low, increase sensitivity to  
reduce cycling (proportional control). On GLYCOOL units, dirty filters can cause the coil freeze stats  
to cycle the compressor.  
5.2  
Optional/Custom Alarms  
5.2.1 Loss of Water Flow  
Available only with 3-way valves and occurs when no water flow is detected in the chilled water or  
condenser water supply line. An optional flow switch is required for this alarm. Check for service  
valves closed, pumps not working, etc.  
5.2.2 Smoke Detected  
Smoke is detected in the return air by an optional Liebert Smoke Detector. Check for source of smoke  
or fire, and follow appropriate emergency procedures.  
5.2.3 Standby GC Pump On  
The primary pump has failed, and the standby pump is activated (glycol cooled and GLYCOOL units  
only).  
Check for problems with the primary pump (fuses blown, motor burnout, service valve shut, stuck  
check valve, impeller damage, etc.).  
5.2.4 Standby Unit On  
The primary environmental control system has had an alarm condition, and the standby system is  
activated.  
5.2.5 Water Under Floor  
Water is detected by an optional Liebert Water Detection System. Check under the raised floor for  
water or other leaks.  
NOTE  
The alarms are specified by the customer at the time of order. All alarms will report to a  
Liebert remote monitoring unit. Additional devices and wiring may be required at the factory  
for some of the alarms.  
41  
             
Component Operation and Maintenance  
6.0 COMPONENT OPERATION AND MAINTENANCE  
6.1 System Testing  
6.1.1 Environmental Control Functions  
The performance of all control circuits can be tested by actuating each of the main functions. This is  
done by temporarily changing the setpoints.  
Cooling  
To test the cooling function, set the setpoint for a temperature of 10°F (5°C) below room temperature.  
A call for cooling should be seen and the equipment should begin to cool. A high temperature alarm  
may come on. Disregard it. Return setpoint to the desired temperature.  
Heating  
Reheat may be tested by setting the setpoint for 10°F (5°C) above room temperature. A call for heat-  
ing should be seen and the heating coils should begin to heat. Disregard the temperature alarm and  
return the setpoint to the desired temperature.  
Humidification  
To check humidification, set the humidity setpoint for an RH 10% above the room humidity reading.  
For infrared humidifiers, the infrared element should come on. For steam generating humidifiers, you  
will immediately hear the clicks as it energizes. After a short delay, the canister will fill with water.  
The water will heat and steam will be produced. Return the humidity setpoint to the desired humidity.  
Dehumidification  
Dehumidification can be checked by setting the humidity setpoint for an RH 10% below room relative  
humidity. The compressor should come on. Return humidity setpoint to the desired humidity.  
Proportional Heating/Cooling/ Dehumidification  
On Chilled Water, GLYCOOL (Econ-O-Cycle, Free Cool, GLYCOOLING cycle) models, and models  
with hot water reheat, the microprocessor is capable of responding to changes in room conditions.  
These systems utilize either a 2- or 3-way valve activated by a proportioning motor.  
For cooling and dehumidification, the microprocessor will respond by positioning the valve propor-  
tionally to match the needs of the room. Full travel of the valve takes place within the range of the  
sensitivity setting. During dehumidification, full travel of the valve takes place within 2% RH.  
For hot water reheat, the microprocessor will respond by positioning the hot water valve proportion-  
ally to match the needs of the room. Full travel of the valve takes place within 1°F with each 0.1°F  
resulting in 10% valve travel.  
Electric Panel  
The electric panel should be inspected for any loose electrical connections.  
CAUTION  
!
Be sure that power to the unit is shut down before attempting to tighten any  
fittings or connections.  
Control Transformer and Fuses  
The control system is divided into four separate circuits. The control voltage circuits are individually  
protected by fuses located on the transformer/fuse board. If any of the fuses are blown, first eliminate  
shorts, then use spare fuses supplied with unit. Use only type and size of fuse specified for your unit.  
The small isolation transformer on the board supplies 24 volts to the main control board. The trans-  
former is internally protected. If the internal protector opens, the transformer/fuse board must be  
replaced. Also check the control voltage fuse on the main control board before replacing the trans-  
former/fuse board.  
Fan Safety Switch  
The Fan Safety Switch is located in the low voltage compartment and consists of a diaphragm switch  
and interconnecting tubing to the blower scroll. The Fan Safety switch is wired directly to the control  
circuit to activate the alarm system if the airflow is interrupted  
42  
     
Component Operation and Maintenance  
Firestat  
The optional firestat is a bimetal operated sensing device with a normally closed switch. This device  
will shut down the entire unit when the inlet air temperature exceeds a preset point. It is connected  
between terminals 1 and 2 at plug P39.  
Smoke Detector  
The optional smoke detector power supply is located on the base of the upflow units, and at the top of  
downflow units. It is constantly sampling return air through a tube. No adjustments are required.  
Water Detection Sensor  
CAUTION  
!
Do not use near flammable liquids or for flammable liquid detection.  
The optional water detection devices available are a point leak detection sensor and a zone leak detec-  
tion kit.  
Figure 7 Liebert leak detection units  
LT460 Zone Leak  
Detection Kit  
Liquitect Point Leak  
Detection Sensor  
The point leak detection sensor provides leak detection at a critical point. A simple two-wire connec-  
tion signals the alarms at a Liebert environmental unit or at a monitoring panel. Run wires to the  
Liebert unit and connect them to terminals 24 and 51, 55 or 56. Use NEC Class 2, 24V wiring. The  
sensor contains a solid state switch that closes when water is detected by the twin sensor probes. The  
sensor is hermetically sealed in all thread PVC nipple and is to be mounted where water problems  
may occur. The sensor should be located 6-8 feet (2-2.5m) from the environmental control unit in a  
wet trap or near a floor drain. It should not be mounted directly under the unit.  
Figure 8 Recommended liquid sensor locations  
Liebert unit  
Recommended  
Liquitect location  
Floor drain  
43  
   
Component Operation and Maintenance  
The zone leak detection kit provides leak detection for a defined zone. This kit is ideal for perimeter  
sensing or serpentine coverage of small areas. A simple, two-wire connection signals the alarms at a  
Liebert environmental unit or at a monitoring panel. Run wires to the Liebert unit and connect them  
to terminals 24 and 51, 55 or 56. The sensor utilizes Liebert's LT500Y leak detection cable. The kit is  
offered with five different lengths of cable sized specifically for the type of Liebert Environmental unit  
(see matrix below). Refer to matrix below for the recommended location of leak detection cable.  
Table 16 Zone leak detection kit installation scenarios  
Scenarios  
Upflow Unit  
Detection  
around  
Upflow Unit  
Detection on sides  
and  
Downflow Unit  
Detection  
around  
Downflow Unit  
Detection on sides  
and  
entire unit  
in front of unit  
entire unit  
in front of unit  
2-ft clearance  
in front  
2-ft clearance  
in front  
6-ft clearance  
in front  
6-ft clearance  
in front  
Distance From Unit  
Distance:  
In back  
On sides  
In front  
2 ft  
2 ft  
2 ft  
No cable behind  
1 ft  
1 ft  
6 ft  
No cable behind  
2 ft  
2 ft  
1 ft  
6 ft  
Unit  
(footprint-  
in.)  
Part Number  
Challenge  
r
LT460-Z30  
LT460-Z20  
LT460-Z30  
LT460-Z25  
(32.5 x  
32.5)  
Remote Shutdown  
A connection point is provided for customer supplied remote shutdown devices. This terminal strip is  
located at the top of upflow units, and at the base of downflow units. Terminals 37 and 38 on the ter-  
minal strip are jumpered when no remote shutdown device is installed.  
6.2  
Filters  
Filters are usually the most neglected item in an environmental control system. To maintain efficient  
operation, they should be checked monthly and changed as required. Because replacement intervals  
vary with environmental condition and filter type, each unit is equipped with a filter clog switch. This  
warns of restricted airflow through the filter compartment by activating the Change Filter alarm.  
Turn power off before replacing filters.  
Challenger 3000 filters are 28-1/2" by 29-1/2", either 2" or 4" thick, plus an optional 2" thick pre-filter.  
The filter is replaced from the front of the unit. On upflow units, the filter is vertical, in front of the  
lower compartment. Pull the filter out toward you to remove it. On downflow units, the filter is hori-  
zontal, above the electrical panel. Slide the filter out toward you to remove it.  
After replacing the filter(s), test the operation of the filter clog switch. Turn the adjusting screw  
counter clockwise to trip the switch — this will energize the Change Filter alarm. To adjust the  
switch proceed as follows: With the fan running, set the switch to energize the light with clean filters.  
The unit panels must all be in place and closed to accurately find this point. Then turn the adjusting  
knob one turn clockwise, or to the desired filter change point.  
44  
   
Component Operation and Maintenance  
6.3  
Blower Package  
Periodic checks of the blower package include: belt, motor mounts, fan bearings, and impellers.  
6.3.1 Fan Impellers and Bearings  
Fan impellers should be periodically inspected and any debris removed. Check to see if they are  
tightly mounted on the fan shaft. Rotate the impellers and make sure they do not rub against the fan  
housing.  
Bearings used on the units are permanently sealed and self-lubricating. They should be inspected for  
signs of wear when the belt is adjusted. Shake the pulley and look for movement in the fan shaft. If  
any excessive movement is noticed, bearings should be replaced. However, the cause of the wear must  
be determined and corrected before returning the unit to operation.  
6.3.2 Belt  
The drive belt should be checked monthly for signs of wear and proper tension. Pressing in on belts  
midway between the sheave and pulley should produce from 1/2" to 1" (12 to 25 mm) of movement.  
Belts that are too tight can cause excessive bearing wear.  
Belt tension can be adjusted by raising or lowering the fan motor base. Loosen nut above motor  
mounting plate to remove belt. Turn nut below motor mounting plate to adjust belt tension. If belt  
appears cracked or worn, it should be replaced with a matched belt (identically sized). With proper  
care, a belt should last several years.  
NOTE  
After adjusting or changing the belt, always be certain that motor base nuts are tightened.  
The bottom adjustment nut should be finger tight. The top locking nut should be tightened  
with a wrench.  
6.3.3 Air Distribution  
All unit models are designed for constant volume air delivery. Therefore any unusual restrictions  
within the air circuit must be avoided. Refer to the following table for recommended free area for  
proper air flow.  
2
2
Table 17 Recommended free area ft (m ) for grilles or perforated panels at output velocities of  
550 and 600 fpm (2.8 and 3.1 m/s)  
550 FPM  
(2.8 m/s)  
600 FPM  
(3.1 m/s)  
Model  
60 Hz Units  
3 Ton  
5 Ton  
2.5 (0.22)  
3.8 (0.34)  
2.3 (0.21)  
3.5 (0.33)  
50 Hz Units  
3 Ton  
2.9 (0.27)  
3.5 (0.33)  
2.6 (0.24)  
3.3 (0.31)  
5 Ton  
Grilles used in raised floors vary in size, the largest being 18" x 6" (46 cm x 15 cm). This type of grille  
2
2
has approximately 56 in (361 cm ) of free area. Perforated Panels are usually 2' x 2' (61 cm x 61 cm)  
2
2
and have a nominal free area of approximately 108 to 144 in (697 to 929 cm ).  
NOTE  
Absolutely avoid any under-floor restrictions such as clusters of cables or piping. Whenever  
possible, cables and pipes should be run parallel to the air flow. Never stack cables or piping.  
45  
         
Component Operation and Maintenance  
6.4  
Refrigeration System  
Each month, the components of the refrigeration system should be inspected for proper function and  
signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri-  
odic inspections can be a major factor in the prevention of most system failures.  
Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors or the  
unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also  
inspect capillary and equalizer lines from the expansion valve and support as necessary.  
Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture.  
Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The  
moisture indicator changes from green to yellow when moisture is present in the system.  
6.4.1 Suction Pressure  
Suction pressure will vary with load conditions. The low pressure switch will shut the compressor  
down if suction pressure falls below the cut-out setting. High suction pressure reduces the ability of  
the refrigerant to cool compressor components and can result in compressor damage. Minimum (pres-  
sure switch cut-out setting) and maximum (design operating) suction pressures are in Table 18.  
Table 18 Suction pressures  
Minimum  
Maximum  
PSIG (kPa) PSIG (kPa)  
System  
Air w/FSC  
R–22  
R–22  
15 (103)  
90 (620)  
(Fan Speed Control)  
Air w/Lee-Temp Control  
(Floodback head  
20 (137)  
90 (620)  
pressure control)  
Water Cooled  
Glycol Cooled  
20 (137)  
20 (137)  
90 (620)  
90 (620)  
6.4.2 Discharge Pressure  
Discharge Pressure can be increased or decreased by load conditions or condenser efficiency. The high  
pressure switch will shut the compressor down at its cut-out setting. Refer to Table 19, below.  
Table 19 Discharge pressures  
Discharge Pressure  
System Design  
PSIG (kPa)  
260 (1795)  
210 (1450)  
225 (1550)  
295 (2035)  
330 (2275)  
360 (2482)  
Air Cooled  
Water/Glycol Cooled 65-75°F (18-24°C) fluid  
85°F (29°C) fluid  
115°F (46°C) fluid  
Maximum  
High Pressure Cut-Out  
6.4.3 Superheat  
Superheat can be adjusted by the Thermostatic Expansion Value (TEV). To determine superheat:  
1. Measure the temperature of the suction line at the point the TEV bulb is clamped.  
2. Obtain the gauge pressure at the compressor suction valve.  
3. Add the estimated pressure drop between bulb location and suction valve.  
4. Convert the sum of the two pressures to the equivalent temperature.  
5. Subtract this temperature from the actual suction line temperature. The difference is superheat.  
46  
           
Component Operation and Maintenance  
6.4.4 Thermostatic Expansion Valve  
Operation  
The thermostatic expansion valve performs one function. It keeps the evaporator supplied with  
enough refrigerant to satisfy load conditions. It does not effect compressor operation.  
Proper valve operation can be determined by measuring superheat. If too little refrigerant is being fed  
to the evaporator, the superheat will be high; if too much refrigerant is being supplied, the superheat  
will be low. The correct superheat setting is between 10 and 15°F (5.6 and 8.3°C).  
Adjustment  
To adjust the superheat setting, proceed as follows:  
1. Remove the valve cap at the bottom of the valve.  
2. Turn the adjusting stem counterclockwise to lower the superheat.  
3. Turn the adjusting stem clockwise to increase the superheat.  
NOTE  
Make no more than one turn of the stem at a time. As long as 30 minutes may be required  
for the new balance to take place.  
6.4.5 Hot Gas Bypass Valve  
Operation  
The hot gas bypass is inserted between the compressor discharge line and the leaving side of the  
expansion valve through the side outlet distributor. The system, with normal operation when the  
evaporator is under full load, will maintain enough pressure on the leaving side of the hot gas valve to  
keep the valve port closed.  
If the load on the evaporator decreases, the evaporator will get colder. When the coil is too cold, the  
internal pressure in the evaporator drops and allows the hot gas bypass valve to open. Hot gas then  
mixes with the liquid coolant on the discharge side of the expansion valve raising the temperature  
and pressure in the evaporator. The net result is a reduction in the cooling capacity of the unit to  
match the load.  
To aid in lubricating the compressor, the hot gas bypass solenoid is delayed for 30 seconds on the ini-  
tial call for cooling and de-energized for 30 seconds during every 60 minutes of continuous operation.  
Adjustment  
Upon deciding what evaporator temperature is desired, the following procedure should be used to  
adjust the hot gas bypass valve:  
1. Install the suction and discharge pressure gauge.  
2. Adjust the temperature setpoint to call for cooling so that the refrigeration compressor will run.  
3. Remove the TOP adjusting nut from the valve.  
4. Insert an Allen wrench in the brass hole at top of the valve in adjusting port, and turn  
CLOCKWISE if a higher evaporator temperature is required.  
5. After obtaining the suction pressure required, reinstall the cap tightly making sure there are no  
leaks.  
6. Let the evaporator operate for approximately 10 to 15 minutes to make sure the suction pressure  
is within the desired range.  
7. There will be a fluctuation of approximately 3 to 6 PSIG (21 to 41 kPa) on the evaporator due to  
the differential on the hot gas bypass.  
8. Return the temperature setpoint to desired number.  
47  
   
Component Operation and Maintenance  
6.4.6 Air Cooled Condenser  
Restricted airflow through the condenser coil will reduce the operating efficiency of the unit and can  
result in high compressor head pressure and loss of cooling.  
Clean the condenser coil of all debris that will inhibit air flow. This can be done with compressed air  
or commercial coil cleaner. Check for bent or damaged coil fins and repair as necessary. In winter, do  
not permit snow to accumulate around the sides or underneath the condenser.  
Check all refrigerant lines and capillaries for vibration isolation. Support as necessary. Visually  
inspect all refrigerant lines for signs of oil leaks.  
Checking Refrigerant Charge (Lee–Temp/Flood Back Head Pressure Control)  
The system refrigerant level must be checked periodically. To do so:  
1. Adjust temperature setpoint in the unit so that the compressor will run continuously.  
2. The refrigerant level is visible through two sight glasses on the receiver and will vary with  
ambient temperature.  
a. 40°F (4.4°C) and lower — Midway on the bottom sight glass.  
b. 40 to 60°F (4.4 to 15.6°C) — Bottom sight glass should be clear with liquid.  
c. 60°F (15.6°C) and above — Midway on the top sight glass.  
3. Return temperature setpoint to desired number.  
Figure 9 Outdoor fan/condenser configuration  
FAN SPEED CONDENSER  
Electric service  
supplied by others  
* B  
Hot gas line  
Secure each leg to condenser  
frame at all points shown using  
hardware provided.  
Liquid line  
LEE-TEMP CONDENSER  
Lee-Temp heater pad  
connection box  
* B  
Hot gas line  
Electric  
service  
supplied by  
others  
Liquid line  
*B - Inverted traps are to be field-supplied and installed (typ). When installing traps, provide  
clearance for swing end of access door. Traps are to extend above base of coil by a  
minimum of 7-1/2" (190 mm).  
48  
   
Component Operation and Maintenance  
6.4.7 Water/Glycol Cooled Condensers  
Coaxial Condenser  
Each water or glycol cooled module has a coaxial condenser which consists of a steel outside tube and  
a copper inside tube.  
Coaxial condensers do not normally require maintenance or replacement if the water supply is clean.  
If your system operates at high head pressure with reduced capacity, and all other causes have been  
eliminated, the coaxial condenser may be obstructed and needs to be replaced.  
Regulating Valve  
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat  
from the refrigeration system, permitting more fluid to flow when load conditions are high and less  
fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve  
seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.  
Standard Valve - 150 psig (1034 kPa) system for 3 & 5 ton units (Johnson Controls Valve)  
High Pressure Valve - 350 psig (2413 kPa) system for 5 ton units (Johnson Controls Valve)  
Adjustment—The valve may be adjusted with a standard refrigeration service valve wrench or  
screw driver. Refer to Table 19 for recommended refrigerant pressures.  
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure  
gauge indicates the desired setting.  
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired set-  
ting is obtained.  
Figure 10 Johnson Controls valve adjustment  
Range  
Spring  
Valve  
Spring  
Guide  
Range Adjustment Screw  
Top  
Retainer  
Insert screwdrivers under  
the valve spring guide.  
Manual Flushing—The valve may be flushed by inserting a screwdriver or similar tool under the  
two sides of the main spring and lifting. This action will open the valve seat and flush any dirt parti-  
cles from the seat. If this fails, it will be necessary to disassemble the valve and clean the seat.  
49  
   
Component Operation and Maintenance  
High Pressure Valve - 350 PSIG System (2413 kPa) for 3 Ton Units (Metrex Valve)  
Adjustment—The valve may be adjusted using a 1/8" diameter rod. Turn adjusting collar nut coun-  
terclockwise to raise head pressure. Turn it clockwise to lower head pressure. Rotation directions are  
as viewed from top of valve spring housing.  
Figure 11 Metrex valve adjustment  
Adjusting Collar Nut  
Manual Flushing—The valve may be flushed by rotating the socket head screw clockwise. This  
screw must be in the OUT position (counterclockwise) for normal valve operation.  
Valve Disassembly  
1. Shut off the water supply by using isolating valves.  
2. Relieve the tension on the main spring by turning the adjusting screw (or collar) as far as it will  
go (provide a container to catch water below the valve).  
3. Remove four screws extending through the main spring housing.  
4. Remove the center assembly screws for access to all internal parts.  
5. Clean the seat if possible. If the seat is pitted or damaged, replace the valve rubber disc and valve  
seat.  
6. After valve is reassembled check for leaks.  
7. Readjust head pressure control.  
Testing Function of Valve—When the refrigeration system has been off for approximately 10 to 15  
minutes, the water flow should stop.  
If the water continues to flow, the valve is either improperly adjusted (with head pressure too low) or  
the pressure sensing capillary is not connected properly to the condenser.  
Glycol Solution Maintenance  
It is difficult to establish a specific schedule of inhibitor maintenance since the rate of inhibitor deple-  
tion depends upon local water conditions. Analysis of water samples at time of installation and every  
six months should help to establish a pattern of depletion. A visual inspection of the solution and fil-  
ter residue is often helpful in judging whether or not active corrosion is occurring.  
The complexity of water caused problems and their correction makes it important to obtain the advice  
of a water treatment specialist and follow a regularly scheduled maintenance program. It is impor-  
tant to note that improper use of water treatment chemicals can cause problems more serious than  
using none.  
Proper inhibitor maintenance must be performed in order to prevent corrosion of the glycol system.  
Consult glycol manufacturer for testing and maintenance of inhibitors. Do not mix products from dif-  
ferent manufacturers. For further details, refer to filling instructions in the installation manual, Lie-  
bert part number SL-11925.  
50  
 
Component Operation and Maintenance  
6.4.8 Compressor Functional Check  
The following diagnostic procedure should be used to evaluate whether the compressor is working  
properly.  
1. Proper voltage to the unit should be verified.  
2. The normal checks of motor winding continuity and short to ground should be made to determine  
if the inherent overload motor protector has opened or if an internal motor short or ground fault  
has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to  
allow it to reset.  
3. Proper indoor and outdoor blower/fan operation should be verified. Condenser glycol flow should  
be verified.  
4. With service gauges connected to suction and discharge pressure fittings, turn on the compressor.  
If suction pressure falls below normal levels, the system is either low on charge or there is a flow  
blockage in the system.  
5. If suction pressure does not drop and discharge pressure does not rise to normal levels, reverse  
any two of the compressor power leads and reapply power to make sure compressor was not wired  
to run in reverse direction. If pressures still do not move to normal values, system is properly  
charged and solenoid valves function, the compressor is faulty. Reconnect the compressor leads as  
originally configured and use normal diagnostic procedures to check operation of the reversing  
valve.  
6. To test if the compressor is pumping properly, the compressor current draw must be compared to  
published compressor performance curves using the operating pressures and voltage of the  
system. If the measured average current deviates more than ±15% from published values, a faulty  
compressor may be indicated. A current imbalance exceeding 15% of the average on the three  
phases should be investigated further.  
7. Before replacing or returning a compressor: Be certain that the compressor is actually  
defective. At a minimum, recheck a compressor returned from the field in the shop or depot for  
Hipot, winding resistance and ability to start before returning. More than one-third of  
compressors returned for warranty analysis are determined to have nothing wrong. They were  
misdiagnosed in the field as being defective. Replacing working compressors unnecessarily costs  
everyone.  
6.4.9 Compressor Replacement  
Infrequently a fault in the motor insulation may result in a motor burn, but burnouts rarely occur in  
a properly installed system. Of those that do, most are the effects of mechanical or lubrication fail-  
ures, resulting in the burnout as a secondary consequence.  
If problems that can cause compressor failures are detected and corrected early, a large percentage  
can be prevented. Periodic maintenance inspections by alert service personnel on the lookout for  
abnormal operation can be a major factor in reducing maintenance costs. It is easier and far less  
costly to take the steps necessary to ensure proper system operation than it is to allow a compressor  
to fail and require replacement.  
When troubleshooting a compressor, check all electrical components for proper operation.  
1. Check all fuses and circuit breakers.  
2. Check Hi-Lo Pressure switch operation.  
3. If a compressor failure has occurred, determine whether it is an electrical or mechanical failure.  
Mechanical Failure  
A mechanical compressor failure will be not be indicated by a burned odor. The motor will attempt to  
run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.  
If a burnout does occur, correct the problem that caused the burnout and clean the system. It is  
important to note that successive burnouts of the same system are usually caused by improper clean-  
ing.  
51  
   
Component Operation and Maintenance  
Electrical Failure  
An electrical failure will be indicated by a distinct pungent odor. If a severe burnout has occurred, the  
oil will be black and acidic.  
In the event that there is an electrical failure and a complete burnout of the refrigeration compressor  
motor, the proper procedures must be performed in order to clean the system to remove any acids that  
would cause a future failure.  
CAUTION  
!
Damage to a replacement compressor caused by improper system cleaning constitutes  
abuse under the terms of the warranty, and the WARRANTY WILL BE VOID.  
There are two kits that can be used with a complete compressor burnout - Sporlan System Cleaner  
and Alco Dri-Kleener. Follow the manufacturer's procedure.  
CAUTION  
!
Avoid touching or contacting the gas and oils with exposed skin. Severe burns will  
result. Use long rubber gloves in handling contaminated parts.  
Compressor Replacement Procedure  
Replacement compressors are available from your Liebert supplier. They will be shipped in a reusable  
crate to the job site as required by the service contractor.  
Upon shipping a replacement compressor, the service contractor will be billed in full for the compres-  
sor until the replacement has been returned to the factory.  
The compressor should be returned in the same container used for shipping to the job. The possible  
damage causes or conditions that were found should be recorded by marking the compressor return  
tag.  
1. Disconnect power.  
2. Attach suction and discharge gauges to access fittings.  
3. Recover refrigerant using standard recovery procedures and equipment. Use a filter-drier when  
charging the system with recovered refrigerant.  
CAUTION  
!
Do not loosen any refrigeration or electrical connections before relieving pressure.  
NOTE  
Release of refrigerant to the atmosphere is harmful to the environment and is unlawful.  
Refrigerant must be recycled or discarded in accordance with federal, state, and local  
regulations.  
4. Front seat service valves to isolate the compressor. Reclaim charge from compressor.  
5. Remove service valves, pressure switch capillaries, and disconnect all electrical connections.  
6. Remove failed compressor.  
CAUTION  
!
A scroll compressor must rotate in the proper direction. Record compressor motor  
connections when removing failed compressor. Wire the replacement compressor motor  
the same way to maintain proper rotation direction.  
7. Install replacement compressor and make all connections.  
8. Pressurize and leak test the system at approximately 150 PSIG (1034 kPa) pressure.  
9. Follow manufacturer's instructions for clean-out kits.  
10. Follow charging instructions as stated in the installation manual, Liebert part number SL-11925.  
52  
Component Operation and Maintenance  
6.5  
Humidifier  
6.5.1 Infrared Humidifier  
During normal humidifier operation, deposits of mineral solids will collect in the humidifier pan. This  
should be cleaned out periodically to ensure efficient operation. Each water supply has different char-  
acteristics, so the time interval between cleanings must be determined locally. A monthly check (and  
cleaning if necessary) is recommended.  
Removing the Pan  
To remove humidifier pan, first open disconnect switch and open front panel. Allow time for pan and  
water to cool. Unlatch front retainer clip (or remove screw from bracket on some units). Pull pan for-  
ward. Remove stand pipe to allow pan to drain. Disconnect drain line. Pull pan forward to remove it.  
CAUTION  
!
Before removing pan, be sure power to unit is disconnected and water in the humidifier pan  
is no hotter than lukewarm.  
Cleaning the Pan  
An autoflush system can greatly increase the time between cleanings but does not eliminate the need  
for periodic checks and maintenance.  
Scale on the side and bottom can be loosened with a stiff brush. Flush with water and replace pan in  
humidifier.  
Changing Humidifier Lamps  
1. Open disconnect switch.  
2. Open front panel.  
3. Remove screws securing line voltage compartment cover, then remove the cover.  
4. In line voltage compartment, disconnect one end of the purple jumpers, then locate the burned out  
bulb with a continuity meter.  
5. Remove humidifier pan. Refer to Removing the Pan on page 53.  
6. Remove lamp brackets (2) under lamps.  
Figure 12 Infrared humidifier lamps  
Humidifier Lamps  
7. Loosen two screws securing bulb wires to junction block.  
8. Pull bulb straight down.  
9. Replace bulb. Wrap wires once loosely around bulb. This will support the bulb and also allow for  
thermal expansion. Make sure lamp wires are secure in the junction block.  
CAUTION  
!
Do not touch the quartz lamps with your bare hands. Oily deposits such as fingerprints will  
severely shorten bulb life. Use clean cotton gloves at all times.  
10. Reverse Steps 1 through 6 to reassemble.  
53  
           
Component Operation and Maintenance  
Autoflush Infrared Humidifier Cleaning System  
NOTE  
To operate properly, the Autoflush Humidifier requires a water source that can deliver at  
least 1 gpm (0.063 l/s) with a minimum pressure of 20 psig (138 kPa).  
The autoflush system will periodically flush the humidifier pan with water to prevent the buildup of  
water minerals due to saturation. Because water conditions vary, the amount of water flushing  
through the system may be programmed to match local needs.  
Water amounts between 110% and 500% of the amount needed for humidification may be selected.  
Operation of the flushing system is then automatic and no further adjustments need to be made.  
Autoflush Operation  
The operation of the autoflush is divided into four steps, beginning with a call for humidification.  
1. If the humidifier has not been activated for over 30 hours, the autoflush will flow water into the  
pan for about 30 seconds. This will provide a minimum amount of water in the pan and prevent  
heat damage to the humidifier pan. Humidifier lamps are OFF.  
2. If the humidifier has been activated within the last 30 hours, Step 1 is bypassed. The autoflush  
will flow water into the pan for about 4 minutes. The humidifier lamps are on and the humidifier  
is operational during this period. When the pan is filled (the fill cycle has timed out), the water  
make-up valve is closed.  
3. The water make-up valve remains OFF and the humidifier lamps are ON for a maximum of  
9-1/2 minutes.  
4. After the 9-1/2 minute delay, the autoflush adds water to the pan to replenish the water used in  
humidification and flush the pan of mineral solids. This amount of water is adjustable from 110%  
to 500% in increments of 10%. At the end of this cycle, the make-up valve is closed. Steps 3 and 4  
repeat as long as humidification is required.  
Autoflush Controls  
Use the LCD display, menu, and keys on the front control panel to program the autoflush controls.  
6.5.2 Steam Generating Humidifier  
Steam generating humidifiers are designed to operate in voltage ranges from 200 to 575 volts and  
generate 11 pounds (5 kg) of steam per hour. These humidifiers operate efficiently over a wide range  
of water quality conditions and automatically adjust to changes in the conductivity of water. The  
humidifiers drain and refill to maintain an amperage setpoint and alert the operator when the  
humidifier canister needs to be replaced. The humidifier is in the lower section of upflow units; it is in  
the middle section of downflow units.  
Figure 13 Steam generating humidifier  
54  
       
Component Operation and Maintenance  
Operation  
1. During start-up, when the humidity control calls for humidification, the fill valve opens and  
allows water to enter the canister. When the water level reaches the electrodes, current flows and  
the water begins to warm. The canister fills until the amperage reaches the setpoint and the fill  
valve closes. As the water warms, its conductivity increases and the current flow, in turn, rises. If  
the amperage reaches 115% of the normal operating amperage, the drain valve opens and flushes  
some of the water out of the canister. This reduces electrode contact with the water and lowers  
the current flow to the amperage setpoint. Boiling soon commences, and the canister operates  
normally.  
2. If the conductivity of the water is low, the canister fills and the water level reaches the canister  
full electrode before the amperage setpoint is reached. The humidifier stops filling to prevent  
overflow. Boiling should commence in time. As water is boiled off, the mineral concentration in  
the canister increases and current flow also increases. The canister eventually reaches full output  
and goes to normal operation. No drain is permitted until then.  
3. When full output is reached the circuit board starts a time cycle which is factory set at 60 seconds.  
During this repeating time cycle, the fill valve will open periodically to replenish the water being  
boiled off and maintain a “steady state” output at the set point. The amperage variance will  
depend on the conductivity of the water.  
4. After a period of time, the mineral concentration in the canister becomes too high. When this  
occurs, the water boils too quickly. As the water quickly boils off and less of the electrode is  
exposed, the current flow decreases. When the current crosses the low threshold point (factory set  
at 90%) before the end of the time cycle, the drain valve opens, draining the mineral laden water  
out and replacing it with fresh water. This lowers the mineral concentration and returns the  
canister to “steady state” operation and prolongs canister life. The frequency of drains depends on  
water conductivity.  
5. Over a period of time, the electrode surface will become coated with a layer of insulating material,  
which causes a drop in current flow. As this happens, the water level in the canister will slowly  
rise exposing new electrode surface to the water to maintain normal output. Eventually, the  
steady state water level will reach the canister full electrode and indicate so by activating the  
canister full alarm. At this point, all of electrode surface has been used up and the canister should  
be replaced.  
6. After the entire electrode surface has been coated, the output will slowly begin to fall off. This  
usually occurs in the last several hours of electrode life and should allow enough time to schedule  
maintenance. During these last hours, the mineral concentration can increase. If the mineral  
concentration is too high, arcing can occur. If the electrodes start to arc, turn off the humidifier  
immediately and replace the canister with the identical part.  
Controls  
The humidifier RUN/DRAIN switch is located at the upper right of the humidifier assembly. This  
switch should be in the RUN position when the humidifier is in normal operation, and in the DRAIN  
position when a manual drain sequence is required. The electronic control board for the humidifier is  
located on the right side of the humidifier assembly. When the main unit is energized, power is avail-  
able to the humidifier circuits.  
55  
Component Operation and Maintenance  
Replacing the Canister  
Over a period of operation, the humidifier electrodes become coated with mineral solids. This coating  
insulates the electrodes and decreases the current flow. To maintain humidifier capacity, the water  
level slowly rises to expose fresh electrode. Eventually, the entire electrode becomes coated and the  
water level reaches the top. At this point, the canister full alarm is activated and the output begins to  
fall. When this happens, it is necessary to replace the full canister.  
To replace the canister:  
1. Turn off the humidifier by lowering the humidity setpoint below the ambient humidity level.  
Record the original setpoint.  
2. Place the RUN/DRAIN switch in the DRAIN position to drain the water from the canister.  
3. Return the RUN/DRAIN switch to the RUN position after the canister has drained.  
WARNING  
!
To avoid a shock hazard, all power to the unit must be disconnected before proceeding with  
the canister replacement procedure.  
4. Turn OFF the power at the main unit.  
5. Remove the cover from the humidifier cabinet.  
CAUTION  
!
The canister and steam hose may be hot! Allow time for the humidifier to cool before  
replacing parts.  
6. Locate the power wires to the steam canister. They are connected to the canister with 1/4" quick  
connects. Make note of the wiring configuration before removing any wires. Refer to the schematic  
on the unit. Slide the rubber boot back to expose the connections. Remove the three power wires  
and the two canister full wires. Do not loosen the screws that secure the electrodes.  
7. Loosen the steam outlet hose clamp and slide the steam hose away from the canister top fitting.  
8. The canister is now ready to be removed. Pull the canister straight up and out of the cabinet  
toward you.  
9. Replace the canister with the part indicated in Table 20.  
Table 20 Humidifier canister part numbers  
Part  
Number  
Capacity  
lbs/hr (kg/hr)  
Voltage  
200-460*  
380-575  
136798P1  
136798P2  
11 (5)  
11 (5)  
* Can operate on 575 V unit with transformer  
10. Replace the canister by reversing the above procedure. Make special note of the following:  
NOTE  
When replacing the canister:  
1. Make sure the two “O” rings are lubricated and properly seated on the bottom neck.  
2. Always check the fill and drain solenoids for proper operation.  
NOTE  
When replacing the wiring, connect the red wire from terminal #1 on the interface to the red top  
terminal on the canister. It is in the middle of a group of three terminals. The black wire from  
terminal #2 on the interface connects to the power terminal farthest from the red terminal/  
wire. The power wire to this terminal is routed through the current sensing coil.  
56  
 
Component Operation and Maintenance  
Figure 14 Canister replacement  
Circuit Board Adjustments  
WARNING  
!
Circuit board adjustment should be performed by qualified personnel only. Hazardous  
voltages are present in the equipment throughout the procedure. Use extreme caution. If  
desired, power may be disconnected prior to the procedure.  
Humidifier operation is governed by the humidifier control board. This board is located on the right  
side of the humidifier compartment. There are three potentiometers mounted on the board. These  
pots can be used to adjust for extreme water conductivity conditions and capacity.  
The “%” pot controls the amperage at which the drain will energize. The pot is clearly marked in per-  
centages. This adjustment is factory set at 90%, which indicates that the unit will drain when the  
amperage falls off to 90% of the capacity setpoint. Raising the value increases the frequency of drain  
cycles. Lowering the value decreases the frequency of drain cycles. The frequency should be increased  
for highly conductive water and decreased for less conductive water. If adjustment is necessary, and a  
change of three to four percent in either direction does not permit normal operation of the unit, con-  
sult your Liebert supplier.  
The pot marked “SEC” controls the duration of the drain cycle. The pot is clearly marked in seconds.  
This adjustment is factory set at 60 seconds and should not be readjusted without consulting your  
Liebert supplier.  
The pot marked “CAP ADJ” is factory set at 100%. The maximum capacity is determined by a fixed  
resistor (R4) which is factory selected based on unit voltage.  
Drain Tempering Feature  
All units are equipped with a drain tempering feature which mixes cold fill water with hot drain  
water to protect drain piping. This feature can lower drain water temperature to as low as 140°F  
(60°C), depending on water pressure. To deactivate this feature, remove the diode from socket CR18  
on the circuit board (lower left, above LED).  
57  
 
Troubleshooting  
7.0 TROUBLESHOOTING  
Use this section to assist in troubleshooting your unit. Also refer to 5.0 - Alarm Descriptions. Sug-  
gestions are grouped by product function for convenience.  
WARNING  
!
Only qualified personnel should perform service on these units. Lethal voltage is present in  
some circuits. Use caution when troubleshooting with power on. Disconnect and lock out  
power before replacing components. Use caution and standard procedures when working with  
pressurized pipes and tubes.  
CAUTION  
!
When using jumpers for troubleshooting, always remove jumpers when maintenance is  
complete. Jumpers left connected could override controls and cause equipment damage.  
Table 21 Blower troubleshooting  
Symptom  
Possible Cause  
No main power  
Check or Remedy  
Check L1, L2 and L3 for rated voltage.  
Check fuses or CBs to main fan.  
Blower will not start  
Blown fuse or tripped circuit breaker (CB)  
Overloads tripped  
Push reset button on main fan overload. Check amp  
draw.  
No output voltage from transformer  
Check for 24 VAC between P24-2 and P24-1. If no  
voltage, check primary voltage.  
Control fuse blown or circuit breaker tripped Check for 24 VAC between P4-4 and E1. If no voltage,  
check for short. Replace fuse or reset circuit breaker.  
Table 22 Chilled water troubleshooting  
Symptom  
Possible Cause  
Check or Remedy  
Chilled water or hot  
water/steam valve  
not opening  
Motor operates but valve won’t open  
Check linkage for adjustment and be sure that it is  
tight on the valve.  
No 24 VAC power to motor  
No signal from control  
Check linkage for adjustment and be sure that it is  
tight on the valve.  
Modulating Motors  
Check DC voltage on printed circuit board in motor.  
Terminal No. 1 is grounded and No. 3 is positive. DC  
voltage should vary from 0.8 to 2.0 VDC or above as  
temperature control is varied below room temperature  
on cooling valve or above room temperature on  
heating valve.  
Motor not working  
Remove wires on terminal No. 1 and No. 3 from the  
motor (do not short). With 24 VAC power from TR to  
TR jumper terminal 1 and 2 on motor to drive open.  
Remove jumper to drive closed, if motor fails to work,  
replace it.  
Actuator Motors  
No 24 VAC power to motor  
Check for 24 VAC between P22-3 and P22-5 (open),  
or P22-1 and P22-5 (closed).  
58  
     
Troubleshooting  
Table 23 Compressor and refrigeration system troubleshooting  
Symptom  
Possible Cause  
Check or Remedy  
Power off  
Check main switch, fuses or CBs and  
wiring  
Compressor will not start  
Current overload open  
Re-set units with overload option  
manually. Allow compressor to cool for  
internal overloads to reset.  
Loose electrical connections  
Compressor motor burned out  
Tighten connections  
Check and replace compressor if  
defective.  
No call for cooling  
Check monitor status.  
Compressor will not operate,  
contactor not pulling in  
Solenoid valve not energizing  
Hold screwdriver over solenoid and check  
for magnetic field. This indicates solenoid  
is energized.  
Low pressure switch not making contact Check gas pressure - manually energize  
low pressure switch.  
Compressor will not operate,  
contact not pulling in  
High pressure switch open  
Reset switch. Refer to other refrigeration  
troubleshooting suggestions.  
Compressor contactor pulled in but  
compressor will not operate  
Blown fuse or tripped CB  
Check for line voltage after fuses or CBs,  
and after contactors.  
Low pressure switch not closing  
Check for low gas pressure. Compressor  
is running on Positive Start Kit (air cooled  
systems only)  
Compressor runs for three minutes  
then stops; contactor drops out.  
Liquid line solenoid valve not opening  
Dirty condenser or drycooler fins  
Condenser equipment not operating  
High refrigerant charge  
Check magnetic field to see if energized.  
Clean coil.  
High discharge pressure  
Check operation.  
Check refrigerant charge.  
Adjust properly.  
Hot gas bypass valve adjusted  
improperly  
Water regulating valve adjusted  
improperly  
Adjust properly.  
Excessive fluid flow through condenser  
Suction service valve partially closed  
Adjust fluid regulating valve  
Open the valve.  
Low discharge pressure  
Faulty head pressure control valve or  
condenser fan speed control  
Replace if defective.  
Compressor rotation in reverse direction Check for proper power phase wiring to  
unit and to compressor motor.  
Insufficient refrigerant in system  
Check for leaks, repair, and add  
refrigerant for air cooled. Evacuate and  
recharge for water/glycol unit.  
Low suction pressure  
Dirty air filters  
Change filters.  
Replace filter.  
Plugged filter-drier  
Improper superheat adjustment  
Reset expansion valve for 10-15°F  
(6-8°C)  
Defective expansion valve sensing  
element  
Replace element  
Poor air distribution  
Check duct work for closed dampers.  
Check for under-floor restrictions at or  
near the unit.  
Low condensing pressure  
Slipping belts  
Check head pressure control device.  
Inspect and adjust  
59  
 
Troubleshooting  
Table 23 Compressor and refrigeration system troubleshooting (continued)  
Symptom  
Possible Cause  
Check or Remedy  
Defective or improperly set expansion  
valve  
Increase superheat or replace valve  
Flooding  
Evaporator fan motor or belt  
Correct problem or replace fan motor and/  
or belts.  
Low condensing pressure  
Slipping belts  
Check head pressure control device  
Inspect and adjust  
Compressor rotation in reverse  
direction.  
Check for proper power phase wiring to  
unit and to compressor motor.  
Low compressor capacity or  
inability to pull down system  
Leaking liquid line solenoid valve or dirt  
in valve  
Replace valve if clean; clean out valve if  
dirty.  
Compressor noisy  
Pipe rattle  
Loose compressor or piping support  
Loose pipe connections  
Tighten clamps.  
Check pipe connections  
Compression ratio too high  
Check setting of high and low pressure  
switches. Check condenser -- is it  
Compressor running hot  
plugged? Check that all evaporator and  
condenser fans are operating properly.  
Low-pressure switch erratic in operation Check tubing to switch to see if clogged or  
Compressor cycles intermittently  
crimped. Check for proper switch  
operation.  
Insufficient refrigerant in system  
Check for leaks, fix, and add refrigerant on  
air cooled unit. Evacuate and recharge  
water/glycol unit.  
Suction service valve closed  
Open valve.  
Insufficient fluid flowing through  
condenser or clogged condenser, or  
dirty air cooled condenser coils  
Adjust fluid regulating valve to condenser.  
Flush the condenser.  
Discharge service valve not fully open  
Faulty low pressure switch  
Open valve  
Repair or replace.  
Check and clean tubing.  
Compressor cycles continually  
Dirt or restriction in tubing to pressure  
stat  
Defective liquid line solenoid valve  
Check valve and solenoid operator;  
replace if necessary.  
Plugged filter-drier  
Replace filter.  
High discharge pressure  
Check for loss of condenser water or  
blocked condenser fan or coil.  
Compressor motor protectors  
tripping or cycling  
Defective overload relay  
High suction temperature  
Replace.  
Reduce suction temperature by expansion  
valve adjustment or provide  
desuperheating.  
Loose power or control circuit wiring  
connection  
Check all power and control circuit  
connections.  
Defective motor  
Check for motor ground or short. Replace  
compressor, if either condition is found.  
Low line voltage  
Check line voltage and determine location  
of voltage drop.  
Compressor cycles on locked rotor  
Compressor motor defective  
Single phasing  
Check for motor winding short or ground.  
Check voltage across all 3 legs at  
contactor. Correct source problem.  
Check control panel for welded  
contactor contacts or welded overload  
contacts  
Replace defective components  
Motor burnout  
60  
Troubleshooting  
Table 24 Dehumidification troubleshooting  
Symptom Possible Cause  
Check or Remedy  
Check monitor status.  
Control not calling for  
dehumidification  
No dehumidification  
Compressor contactor not pulling in  
Compressor won't run; fuse blown or  
CB tripped  
Check and Table 23. Check fuses or  
CBs and contacts. Check line voltage  
Table 25 Glycol pump troubleshooting  
Symptom  
Possible Cause  
Check or Remedy  
Clean out debris.  
Suddenly stops pumping  
Suddenly slow pumping  
Clogged strainer or impeller  
Clogged impeller, diffuser, or line  
Worn seal or packing  
Clean out debris and use strainer.  
Replace seal or packing.  
Excessive leakage around the pump  
shaft while operating  
Worn impeller or seal  
Replace with new impeller or seal.  
Relocate pump closer to supply.  
Performance poor  
Suction lift too high  
Motor not up to speed; low voltage  
Larger lead wires may be required.  
Check for proper line voltage (±10%).  
Worn bearings  
Replace pump  
Replace pump  
Worn motor bearings  
Low discharge head  
Noisy operation  
Throttle discharge-improve suction  
conditions.  
Debris lodged in impeller  
Cavitating pumps  
Remove cover and clean out.  
Adjust system pressures.  
Table 26 Infrared humidifier troubleshooting  
Symptom Possible Cause  
Check or Remedy  
Check water supply.  
Humidifier pan not filling  
No humidification  
Check fill valve operation  
Check drain stand pipe adjustment  
Check for clogged waterline  
Check monitor status  
Control not calling for humidity  
Humidity contact not pulling in  
Check visually. If contact is made,  
check line voltage after contactor and  
fuses or CBs.  
Check for open humidifier safety stat.  
Jumper between terminals P35-6 and  
P35-15. If contactor pulls in, replace  
safety. Remove jumper.  
Humidifier bulb burned out  
Replace bulb. Loosen lead on old  
bulb. Trim excess lead length on new  
bulb to avoid shorts.  
61  
     
Troubleshooting  
Table 27 Steam generating humidifier troubleshooting  
Symptom  
Possible Cause  
Check or Remedy  
Check drain valve to ensure that it drains freely. Check and  
replace if defective.  
Foaming  
Check water supply. If commercially softened, reconnect to  
raw water supply. If connected to hot water reconnect to  
cold water.  
False canister full indication  
Shorts or loose connections  
Faulty circuit board  
Faulty solenoid  
Check the wiring connections of the 24 VAC circuit.  
Replace the circuit board.  
Main 24 VAC fuse or circuit  
breaker trips  
Check for magnetic field at coil.  
Main fuses blow  
approximately 15 seconds  
after unit is activated  
Check amp draw of humidifier on startup. If it exceeds rated  
amps, increase setting of the % pot on the circuit board  
Conductivity too high  
Mineral deposits obstruct  
drain valve  
Check drain valve for obstructions and clean if necessary.  
Main fuses blow when  
drain valve is activated.  
Faulty solenoid  
Check for magnetic field at coil.  
Faulty circuit board  
Replace circuit board.  
Verify that RUN/DRAIN switch is in the RUN position.  
Check fuses or CBs and replace or reset if necessary.  
Unit ON, humidifier will not  
operate  
Humidifier not receiving power  
Make sure molex connector is securely plugged into circuit  
board and that no wires are loose.  
No water available to unit  
Clogged fill line strainer  
Check external shut-off valves.  
Clean or replace fill line strainer.  
Contactor pulled in, but no  
water enters canister  
Wiring breaks or loose  
connections  
Check for faulty wiring and loose connections.  
Faulty circuit board  
Foaming  
Replace circuit board.  
Check drain valve and water supply.  
Check connection on component plate in humidifier cabinet.  
Terminal #1 on the square block interface device must be  
connected to L2 of the power terminal block. L2 must also  
be connected to the electrode closest to the steam outlet  
port.  
Canister interface connections  
incorrect  
Verify that the red wire from terminal #2 on the interface  
connects to the red top terminal on the canister. This is the  
one farthest from the steam outlet port and is the high water  
sensor probe.  
Water enters canister, but  
canister full circuit activates  
at a low water level  
Remove red canister full wire from canister. If normal  
operation resumes, canister must be replaced. Remove the  
wire from terminal #3 on the interface. If normal operation  
resumes, canister full interface must be replaced.  
Full isolation has broken down  
Drain assembly not operating  
freely  
Check and replace coil or valve if necessary.  
Replace circuit board  
Faulty circuit board  
Canister full circuit does not  
activate  
Canister fills but overflows  
Check wiring of canister full interface. Replace circuit board.  
62  
 
Troubleshooting  
Table 27 Steam generating humidifier troubleshooting (continued)  
Symptom  
Possible Cause  
Check or Remedy  
Verify that drain valve operates freely when activated. Clean  
valve and replace coil or valve if defective. Flush canister  
several times and replace if arcing persists.  
Drain valve clogged or  
defective  
If water is commercially softened, reconnect humidifier to  
raw water supply, drain canister, and restart If connected to  
hot supply, reconnect to cold water.  
Improper water supply  
Excessive arcing in the  
canister  
Increase drain rate by adjusting % pot on circuit board  
above the preset 70% to roughly 80%.  
Insufficient drain rate  
Excessive iron content in  
water  
Analyze iron content of water. If it exceeds 0.1 mg./l, install  
a filter to remove iron from water supply.  
Drain canister and add one Alka-Seltzer tablet to canister.  
Refill. Turn the % pot to roughly 60%. Restart humidifier. If  
amperage rises rapidly, it may be necessary to dilute the  
water to prevent blown fuses. If it rises too slowly, add  
another Alka-Seltzer tablet.  
On cold start-up, canister  
fills, high water alarm  
activates and humidifier  
Conductivity of water too low  
Fill solenoid not closing tightly  
fails to reach full amperage  
On cold start-up, canister  
fills, high water alarm  
activates and humidifier  
fails to reach full amperage  
If humidifier returns to canister full condition, verity that the  
fill solenoid closes tightly.  
Table 28 Reheat troubleshooting  
Symptom  
Possible Cause  
Control not calling for heat Check monitor status.  
Check or Remedy  
Reheat will not operate;  
contactor not pulling in  
Jumper between terminals P34-1 and P34-2. If reheat operates,  
safety is open. Remove jumper. Replace safety.  
Reheat safety stat open  
Heater burned out  
Reheat not operating;  
contactor pulling in  
Turn off power and check heater continuity with Ohm meter.  
NOTE:  
Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections  
are necessary to assure proper cleanliness of the reheating element. Should inspection reveal  
corrosion particles on the reheating element or adjoining surfaces (including ducts and  
plenums), appropriate cleaning should be performed. Periodic reheating element replacement  
may be required to meet specific application requirements.  
63  
 
Monthly Maintenance Inspection Checklist  
8.0 MONTHLY MAINTENANCE INSPECTION CHECKLIST  
Date:_______________________________________  
Model #:_____________________________________  
Prepared by:_________________________________  
Serial #:____________________________________  
Filters  
Steam Generating Humidifier  
___ 1. Restricted air flow  
___ 1. Check canister for deposits  
___ 2. Check filter switch  
___ 3. Wipe section clean  
___ 2. Check condition of steam hoses  
___ 3. Check water make-up valve for  
leaks  
Blower Section  
Infrared Humidifier  
___ 1. Impellers free of debris and move freely  
___ 1. Check pan drain for clogs  
___ 2. Check belt tension and condition  
___ 3. Bearings in good condition  
___ 2. Check humidifier lamps  
___ 3. Check pan for mineral deposits  
Compressor  
Refrigeration Cycle/Section  
___ 1. Check oil leaks  
___ 1. Check refrigerant lines  
___ 2. Check for leaks  
___ 2. Check for moisture (sight glass)  
___ 3. Check suction pressure  
Air Cooled Condenser (if applicable)  
___ 1. Condenser coil clean  
___ 4. Check head pressure  
___ 2. Motor mounts tight  
___ 5. Check discharge pressure  
___ 6. Check hot gas bypass valve  
___ 7. Check thermostatic exp. valve  
___ 3. Bearings in good condition  
___ 4. Refrigerant lines properly  
supported  
Reheat  
Air Distribution Section  
___ 1. Check reheat element operation  
___ 1. Restriction in grille free area  
___ 2. Inspect elements for cleanliness  
Refrigerant Charge  
___ 1. Check refrigerant level  
Notes  
Signature  
Make photocopies of this form for your records  
64  
 
Semiannual Maintenance Inspection Checklist  
9.0 SEMIANNUAL MAINTENANCE INSPECTION CHECKLIST  
Date:________________________________________  
Model #:_____________________________________  
Prepared by:_________________________________  
Serial #:_____________________________________  
Filters  
Steam Generating Humidifier  
___ 1. Restricted air flow  
___ 2. Check filter switch  
___ 3. Wipe section clean  
___ 1. Check canister for deposits  
___ 2. Check condition of steam hoses  
___ 3. Check water make-up valve for leaks  
___ 4. Inspect & tighten electrical connections  
Blower Section  
___ 1. Impellers free of debris and move freely  
___ 2. Check belt tension and condition  
___ 3. Bearings in good condition  
___ 4. Inspect & tighten electrical connections  
Infrared Humidifier  
___ 1. Check pan drain for clogs  
___ 2. Check humidifier lamps  
___ 3. Check pan for mineral deposits  
___ 4. Inspect & tighten electrical connections  
Compressor  
___ 1. Check oil leaks  
___ 2. Check for leaks  
___ 3. Inspect & tighten electrical connections  
Refrigeration Cycle/Section  
___ 1. Check refrigerant lines  
___ 2. Check for moisture (sight glass)  
___ 3. Check suction pressure  
___ 4. Check head pressure  
___ 5. Check discharge pressure  
___ 6. Check hot gas bypass valve  
___ 7. Check thermostatic exp. valve  
Air Cooled Condenser (if applicable)  
___ 1. Condenser coil clean  
___ 2. Motor mounts tight  
___ 3. Bearings in good condition  
___ 4. Refrigerant lines properly supported  
___ 5. Inspect & tighten electrical connections  
Air Distribution Section  
___ 1. Restriction in grille free area  
Water/Glycol Condenser (if applicable)  
___ 1. Copper tube clean  
Refrigerant Charge  
___ 2. Water regulating valves function  
___ 3. Glycol solution  
___ 4. Check for water/glycol leaks  
___ 1. Check refrigerant level  
Electrical Panel  
___ 1. Check fuses  
___ 2. Inspect & tighten electrical connections  
___ 3. Check operation sequence  
___ 4. Check contactor operation  
Glycol Pump  
___ 1. Glycol leaks  
___ 2. Pump operation  
___ 3. Inspect & tighten electrical connections  
Reheat  
___ 1. Check reheat element operation  
___ 2. Inspect elements for cleanliness  
___ 3. Inspect & tighten electrical connections  
Notes  
Signature  
Make photocopies of this form for your records  
65  
 
Semiannual Maintenance Inspection Checklist  
66  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2006 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert and the Liebert logo are registered trademarks of Liebert  
Corporation. All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-11935 _REV1_08-06  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power Systems  
Connectivity  
Embedded Computing  
Embedded Power  
Outside Plant  
Services  
Power Switching & Control  
Site Monitoring  
Surge Protection  
DC Power Systems  
Integrated Cabinet Solutions  
Precision Cooling  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2006 Emerson Electric Co.  

Multiquip Tamping Rammer Mikasa Mt 86d User Manual
Murphy Pneumatic Valves M2582 P User Manual
Panasonic 135fp User Manual
Panasonic Cu E12gkr User Manual
Samsung Ad19a1 B1 E12 User Manual
Sanyo Kms1872 User Manual
Vector Power City Vec029acy User Manual
Whirlpool Acs102xg User Manual
Xerox 240 Dc User Manual
Xerox All In One Printer Pe120i User Manual