Trane Air Conditioner trg trc005 en User Manual

Air Conditioning  
Clinic  
Refrigeration  
System Components  
One of the Fundamental Series  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NO POSTAGE  
NECESSARY  
IF MAILED  
IN THE  
UNITED STATES  
BUSINESS REPLY MAIL  
LA CROSSE, WI  
FIRST-CLASS MAIL  
PERMIT NO. 11  
POSTAGE WILL BE PAID BY ADDRESSEE  
THE TRANE COMPANY  
Attn: Applications Engineering  
3600 Pammel Creek Road  
La Crosse WI 54601-9985  
NO POSTAGE  
NECESSARY  
IF MAILED  
IN THE  
UNITED STATES  
BUSINESS REPLY MAIL  
LA CROSSE, WI  
FIRST-CLASS MAIL  
PERMIT NO. 11  
POSTAGE WILL BE PAID BY ADDRESSEE  
THE TRANE COMPANY  
Attn: Applications Engineering  
3600 Pammel Creek Road  
La Crosse WI 54601-9985  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigeration  
System Components  
One of the Fundamental Series  
A publication of  
The Trane Company—  
Worldwide Applied Systems Group  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preface  
Refrigeration  
System Components  
A Trane Air Conditioning Clinic  
Figure 1  
The Trane Company believes that it is incumbent on manufacturers to serve the  
industry by regularly disseminating information gathered through laboratory  
research, testing programs, and field experience.  
The Trane Air Conditioning Clinic series is one means of knowledge-sharing. It  
is intended to acquaint a nontechnical audience with various fundamental  
aspects of heating, ventilating and air conditioning. We have taken special care  
to make the clinic as uncommercial and straightforward as possible.  
Illustrations of Trane products only appear in cases where they help convey the  
message contained in the accompanying text.  
This particular clinic introduces the reader to the concept of vapor-compression  
refrigeration system components.  
© 1999 American Standard Inc. All rights reserved  
TRG-TRC005-EN  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction ........................................................... 1  
period one  
period two  
Refrigeration Cycle .............................................. 2  
Condensers ............................................................ 5  
Air-Cooled Condensers ..............................................5  
Evaporative Condensers ............................................7  
Water-Cooled Condensers .........................................8  
Condenser Control ...................................................10  
period three Evaporators .......................................................... 16  
Finned-Tube Evaporators .........................................16  
Shell-and-Tube Evaporators ......................................19  
Evaporator Control ...................................................20  
period four Expansion Devices ............................................. 26  
period five  
Accessories .......................................................... 34  
Solenoid Valve ..........................................................34  
Liquid-Line Filter Drier ..............................................36  
Moisture-Indicating Sight Glass ...............................38  
Suction Line Filter ....................................................39  
Hot Gas Muffler .......................................................40  
Shutoff Valve ............................................................41  
Access Port ..............................................................42  
period six  
Review ................................................................... 43  
Quiz ......................................................................... 48  
Answers ................................................................ 50  
Glossary ................................................................ 51  
TRG-TRC005-EN  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iv  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
notes  
Vapor-Compression Refrigeration  
condenser  
expansion  
device  
compressor  
evaporator  
Figure 2  
The major components of a vapor-compression refrigeration system include  
the compressor, condenser, expansion device, and evaporator. The latter three  
will be discussed in this clinic—the compressor is discussed in a separate  
clinic.  
This clinic will also discuss many of the common accessories used in a comfort-  
cooling refrigeration system.  
TRG-TRC005-EN  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Refrigeration Cycle  
notes  
Refrigeration  
System Components  
period one  
Refrigeration Cycle  
Figure 3  
First, a brief review of the vapor-compression refrigeration cycle will help to  
relate these components.  
Refrigeration Cycle  
B
A
evaporator  
enthalpy  
Figure 4  
A diagram of a typical vapor-compression refrigeration cycle can be  
superimposed on a pressure-enthalpy (P-h) chart to demonstrate the function  
of each component in the system. The pressure-enthalpy chart plots the  
properties of a refrigerant—refrigerant pressure (vertical axis) versus enthalpy  
(horizontal axis). Enthalpy is a measure of the heat content, both sensible and  
latent, per pound [kg] of refrigerant.  
The cycle starts with a cool, low-pressure mixture of liquid and vapor  
refrigerant entering the evaporator (A) where it absorbs heat from the relatively  
warm air, water, or other fluid that is being cooled. This transfer of heat boils  
the liquid refrigerant in the evaporator, and this superheated refrigerant vapor  
is drawn to the compressor (B).  
2
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Refrigeration Cycle  
notes  
Refrigeration Cycle  
C
compressor  
B
A
evaporator  
enthalpy  
Figure 5  
The compressor draws in the superheated refrigerant vapor (B) and  
compresses it to a pressure and temperature (C) high enough that it can reject  
heat to another fluid. This hot, high-pressure refrigerant vapor then travels to  
the condenser.  
Refrigeration Cycle  
condenser  
C
D
A
compressor  
B
evaporator  
enthalpy  
Figure 6  
Within the condenser, heat is transferred from the hot refrigerant vapor to  
relatively cool ambient air or cooling water. This reduction in the heat content  
of the refrigerant vapor causes it to desuperheat, condense into liquid, and  
further subcool before leaving the condenser (D) for the expansion device.  
TRG-TRC005-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
period one  
Refrigeration Cycle  
notes  
Refrigeration Cycle  
condenser  
C
D
expansion  
device  
compressor  
B
A
evaporator  
enthalpy  
Figure 7  
Finally, the high-pressure liquid refrigerant (D) flows through the expansion  
device, causing a large pressure drop that reduces the pressure of the  
refrigerant to that of the evaporator. This pressure reduction causes a small  
portion of the liquid to boil off, or flash, cooling the remaining refrigerant to the  
desired evaporator temperature.  
The cooled mixture of liquid and vapor refrigerant then enters the evaporator  
(A) to repeat the cycle.  
4
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Refrigeration  
System Components  
period two  
Condensers  
Figure 8  
The first major component to be discussed is the condenser. The condenser is  
a heat exchanger that rejects heat from the refrigerant to air, water, or some  
other fluid.  
The three common types of condensers are air-cooled, water-cooled, and  
evaporative.  
Air-Cooled Condenser  
propeller  
fan  
outdoor  
air  
condenser  
coil  
subcooler  
Figure 9  
Air-Cooled Condensers  
A typical air-cooled condenser uses propeller-type fans to draw outdoor air  
over a finned-tube heat transfer surface. The temperature difference between  
the hot refrigerant vapor that is flowing through the tubes and the cooler  
outdoor air induces heat transfer. The resulting reduction in the heat content of  
the refrigerant vapor causes it to condense into liquid. Within the final few  
lengths of condenser tubing (the subcooler), the liquid refrigerant is further  
cooled below the temperature at which it was condensed.  
TRG-TRC005-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
The air-cooled condenser is very popular in both residential and commercial  
applications because of its convenience. It requires very little maintenance and  
does not require the freeze protection and water treatment that is necessary  
with a water-cooled condenser. Additionally, it is favored in areas that have an  
inadequate or costly water supply, or where the use of water for air  
conditioning is restricted.  
notes  
Effect of Subcooling  
subcooling  
C
D
DI  
AI  
B
A
refrigeration  
effect  
enthalpy  
Figure 10  
The benefit of subcooling on system performance can be demonstrated by  
comparing the performance of a system with and without subcooling.  
The change in enthalpy (the line from A to B) that occurs in the evaporator is  
called the refrigeration effect. This is the amount of heat that each pound  
[kg] of liquid refrigerant will absorb when it evaporates.  
In comparison, the same system without subcooling produces less refrigeration  
effect (the line from Ato B). The system without subcooling must evaporate  
substantially more refrigerant within a larger coil to produce the same capacity  
as the system with subcooling.  
Instead of subcooling in the condenser, some packaged refrigeration  
equipment, such as water chillers, may use an economizer or liquid/vapor  
separator to increase this refrigeration effect.  
6
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Centrifugal Fan Air-Cooled Condenser  
condenser  
coil  
centrifugal  
fan  
Figure 11  
An alternative air-cooled condenser uses a centrifugal fan to draw or blow air  
over the condensing coil. The principal advantage of this design is that the  
centrifugal fan is capable of overcoming the higher static-pressure losses  
associated with ductwork. Therefore, if the condenser is to be located indoors  
and uses a duct system to deliver air to and from the condenser coil, the  
centrifugal fan air-cooled condenser is probably best suited for this  
application.  
Evaporative Condenser  
fan  
refrigerant  
vapor  
condenser  
coil  
pump  
sump  
Figure 12  
subcooler  
liquid refrigerant  
Evaporative Condensers  
A modification of the air-cooled condenser is the evaporative condenser.  
Within this device, the refrigerant flows through tubes and air is drawn or  
blown over the tubes by a fan. The difference is that water is sprayed on the  
tube surfaces. As the air passes over the coil, it causes a small portion of the  
water to evaporate. This evaporation process absorbs heat from the coil,  
TRG-TRC005-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
causing the refrigerant vapor within the tubes to condense. The remaining  
water then falls to the sump to be recirculated and used again.  
notes  
Subcooling of the refrigerant can be accomplished by piping the condensed  
liquid back through another few rows of coil tubing, located either in the  
condenser airstream or in the water sump, where additional heat transfer  
reduces the temperature of the liquid refrigerant.  
Water-Cooled Condenser  
hot, refrigerant vapor  
95ºF  
[35ºC]  
cooling water  
85ºF  
[29ºC]  
subcooler  
subcooled, liquid  
refrigerant  
Figure 13  
Water-Cooled Condensers  
The shell-and-tube is the most common type of water-cooled condenser.  
With this design, water is pumped through the tubes while the refrigerant vapor  
fills the shell space surrounding the tubes. As heat is transferred from the  
refrigerant to the water, the refrigerant vapor condenses on the tube surfaces.  
The condensed liquid refrigerant then falls to the bottom of the shell, where it  
flows through an enclosure that contains additional tubes (the subcooler). More  
heat is transferred from the liquid refrigerant to the water inside these tubes,  
subcooling the refrigerant.  
After the warm water leaves the condenser, it must either be disposed of (as in  
the case of using water from a well) or it must be cooled before it can be reused  
by the condenser. In this example, the condenser brings in 85°F [29°C] water  
and warms it up to 95°F [35°C]. Before this water can be used again, it must be  
cooled back down to 85°F [29°C].  
8
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Cooling Tower  
propeller  
fan  
sprays  
fill  
outdoor  
air  
sump  
85ºF  
[29ºC]  
95ºF  
[35ºC]  
to  
from  
condenser  
condenser  
Figure 14  
A cooling tower is a device commonly used to cool condensing water. In this  
design, warm water is sprayed over the fill inside the cooling tower while a  
propeller fan draws outdoor air upward through the fill. The movement of air  
through the spray causes some of the water to evaporate, a process that cools  
the remaining water. This cooled water then falls to the tower sump to be  
returned to the condenser.  
The final temperature of the water leaving the tower is determined, in part, by  
the humidity of the outdoor air. If the outdoor air is dry, the final water  
temperature can be considerably lower than the ambient dry-bulb temperature.  
If the outdoor air is humid, however, the final temperature will be near the  
ambient dry-bulb temperature.  
While a cooling tower can reclaim much of the condensing water, it cannot  
reclaim it all. The evaporation process uses up water to dissipate heat  
contributed by the cooling load plus the heat of compression. In addition, as the  
water evaporates, the dissolved minerals and water treatment chemicals  
become concentrated in the sump. To prevent this solution from becoming  
concentrated and possibly corrosive, water is periodically bled from the sump  
and an equal amount of fresh water is added.  
In the past, some water-cooled condensers used water from either a municipal  
or a natural water supply as the condensing water. After rejecting the  
condenser heat to this water, it was dumped into the sewer or back into the  
body of water. Environmental and economic restrictions have made this  
method uncommon.  
Finally, a geothermal well system can be used to reject the heat from the  
condenser by circulating the condensing water through a series of  
underground pipes . This method takes advantage of the naturally-cool ground  
temperatures.  
TRG-TRC005-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Condenser Control  
I
Condenser capacity is influenced by:  
K Temperature difference between refrigerant and  
cooling media  
K Flow rate of cooling media through condenser  
K Flow rate of refrigerant through condenser  
Figure 15  
Condenser Control  
The heat rejection capacity of a condenser is influenced by (1) the temperature  
difference between the refrigerant and the cooling media (air, water, or other  
fluid), (2) the flow rate of the cooling media through the condenser, and (3) the  
flow rate of the refrigerant through the condenser.  
To balance the rate of heat rejection (in the condenser) with the changing  
system load, at least one of these variables may be controlled.  
Condenser Capacity  
full load  
condenser heat  
rejection capacity  
full load  
part load  
condenser heat  
rejection capacity  
part load  
enthalpy  
Figure 16  
As the system load decreases, the heat rejection capacity of the condenser is  
greater than the load. Because of this excess capacity, the condenser matches  
the decreasing load by operating at progressively lower pressures. Additionally,  
a reduction in outdoor air temperature allows the temperature of the air or  
water flowing through the condenser to drop. This also has the effect of  
lowering the condensing pressure.  
10  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
A reduction in condensing pressure lessens the power required to compress  
the refrigerant. Unfortunately, if the condensing pressure falls too low, the  
expansion valve may not be able to produce the flow of liquid refrigerant  
needed to satisfy the demand at the evaporator. In some systems, as the  
condensing pressure drops, the compressor suction pressure also drops,  
resulting in evaporator frosting and possible compressor shutdown due to a  
low-pressure safety device.  
notes  
While it is not essential to control condensing pressure to a constant value,  
provisions should be made to control it within acceptable limits.  
Condensing Temperature Control  
flow-regulating  
valve  
condenser  
condenser  
water pump  
Figure 17  
One common method of controlling the capacity of a water-cooled condenser is  
to vary the rate at which water flows through the condenser.  
For example, assume a water-cooled condenser is piped to a municipal water  
system. To control the capacity of the condenser, a flow-regulating valve is  
installed on the leaving-water side of the condenser. As the load on the system  
decreases, the regulating valve senses the lowering condensing pressure. The  
valve reduces the flow rate of the water until the heat-rejection rate of the  
condenser balances the system load at an acceptable pressure and  
temperature.  
TRG-TRC005-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Vary Condenser Water Flow Rate  
cooling tower  
cooling tower  
condenser  
diverting  
valve  
bypass pipe  
condenser  
variable-speed  
drive  
Figure 18  
It is more common, however, for a water-cooled condenser to be connected to a  
cooling tower.  
In this case, typical methods for modulating the water flow through the  
condenser include either using a variable-speed drive on the condenser water  
pump or using a diverting valve and pipe to bypass the condenser. The  
variable-speed drive on the pump modulates the amount of water pumped  
through the condenser. The diverting valve modulates the water flow through  
the condenser bundle by diverting some of the cooling water around the  
condenser through the bypass pipe, directly back to the cooling tower.  
Each of these options has the effect of varying the flow rate of water through  
the condenser, ensuring an acceptable condensing pressure and temperature.  
Vary Entering Water Temperature  
variable-  
speed  
drive  
cooling tower  
cooling tower  
condenser  
diverting  
valve  
bypass pipe  
condenser  
Figure 19  
Another method of controlling the capacity of a water-cooled condenser is to  
vary the temperature of the water entering the condenser.  
12  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
Common methods of modulating this water temperature include controlling the  
cooling tower fans or using a cooling-tower bypass pipe. Controlling the  
cooling tower fans, either by cycling fans on and off or by using a variable-  
speed drive on the fans, allows the system to control the temperature of the  
water leaving the tower sump. The diverting valve on the cooling-tower bypass  
pipe diverts warmer water leaving the condenser and mixes it with cooler water  
from the cooling tower to modulate the temperature of the water entering the  
condenser.  
notes  
Each of these options has the effect of varying the temperature of the water  
entering the condenser, ensuring an acceptable condensing pressure and  
temperature.  
Cooling Tower Bypass  
40ºF  
[4ºC]  
cooling tower  
diverting  
valve  
bypass pipe  
55ºF  
[13ºC]  
65ºF  
[18ºC]  
condenser  
Figure 20  
Another example is a system that must start and operate during cooler weather.  
The cold tower water would force the condensing pressure down to the point  
where the system could not operate. In this example, the temperature of the  
water entering the condenser is controlled by a diverting valve and a cooling-  
tower bypass pipe.  
If the entering water temperature causes the condensing pressure to become  
too low, the valve begins to divert the warm water that is leaving the condenser  
and mixes it with the cool tower water, producing a controlled water  
temperature entering the condenser. In this example, by diverting 65°F [18°C]  
water leaving the condenser and mixing it with the 40°F [4°C] tower water, the  
condenser is provided with 55°F [13°C] condensing water. This warmer  
condensing water results in a higher condensing pressure.  
TRG-TRC005-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
notes  
Air-Cooled Condenser Control  
damper  
A
B
fan A  
fan B  
fan A  
heat rejection capacity  
Figure 21  
A common method of controlling the capacity of an air-cooled condenser is to  
vary the airflow across the condenser coil. The heat-rejection rate of a multiple-  
fan condenser is often controlled by cycling fans on and off to maintain  
acceptable condensing pressures. Alternatively, the airflow across the coil can  
be varied by using a damper or a variable-speed drive on one or more of the  
fans.  
In this example, a damper has been added to one of the two condenser fans.  
Capacity control is accomplished by cycling fan B on and off while varying the  
airflow of fan A by modulating the damper. Both the damper and the cycled fan  
are controlled by condensing pressure. As the heat-rejection requirement  
increases, fan A continues to open its damper farther to increase its airflow.  
When fan A reaches full airflow, fan B turns on and fan A modulates its damper  
to continue to match the desired heat rejection rate.  
Condenser Flooding Control  
condenser  
B
C
A
expansion  
valve  
liquid receiver  
evaporator  
discharge line  
compressor  
Figure 22  
Another, less common method of controlling the capacity of an air-cooled  
14  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period two  
Condensers  
condenser is to flood the condenser coil with liquid refrigerant. A condenser  
coil tube that is filled with liquid refrigerant no longer acts as a condensing  
surface. Progressive flooding of the condenser coil tubes reduces the capacity  
of the condenser and raises the condensing pressure.  
notes  
During normal, warm ambient conditions, valves B and C are open and valve A  
is closed. Assume that the system load is falling and, at the same time, the  
outdoor air temperatures has fallen to the point where the rate of heat rejection  
from the condenser balances the load at a condensing pressure less than  
desired. This minimum condensing pressure is the set point for valve A. As the  
condensing pressure decreases, so does the pressure in the discharge line.  
Valve B acts as a pressure regulator, and when the discharge-line pressure falls  
below its set point, valve B closes.  
This causes the condensing pressure to drop farther. Sensing this reduction in  
condensing pressure, valve A opens and directs hot, high-pressure refrigerant  
vapor into the receiver. This increases the pressure in the receiver, controlling it  
to the desired condensing pressure. Because the pressure in the receiver is now  
higher than the pressure in the condenser, the check valve C does not allow the  
refrigerant to flow back into the condenser.  
With valve B closed and valve A modulating to maintain the pressure in the  
receiver, the pressure in the discharge line begins to increase. When it exceeds  
the set point for valve B, the valve opens and again allows hot refrigerant vapor  
into the condenser. However, since the condensing pressure is still below the  
pressure in the receiver, the refrigerant cannot flow through valve C. This  
causes the condensed liquid to remain in the condenser, where it backs up, or  
floods, the condenser tubes.  
The flooding of tubes causes the condenser to progressively lose capacity.  
When it has flooded enough that its capacity is reduced to the point where the  
condensing pressure rises above the pressure in the receiver, the higher-  
pressure condensed liquid will flow through check valve C into the receiver.  
This increases the pressure in the receiver above the minimum condensing  
pressure set point, closing valve A.  
Condenser coil flooding provides the capacity modulation range needed to  
produce acceptable condensing pressures at reduced loads and  
correspondingly-low outdoor temperatures.  
TRG-TRC005-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Refrigeration  
System Components  
period three  
Evaporators  
Figure 23  
The second major component to be discussed is the evaporator. The  
evaporator is a heat exchanger that transfers heat from air, water, or some  
other fluid to the cool liquid refrigerant.  
Two common types of evaporators are the finned-tube and the shell-and-tube.  
Finned-Tube Evaporator  
liquid/vapor  
refrigerant  
airflow  
refrigerant vapor  
Figure 24  
Finned-Tube Evaporators  
A finned-tube evaporator includes rows of tubes passing through sheets of  
formed fins. Cool, liquid refrigerant flows through the tubes, cooling the tube  
and fin surfaces. As air passes through the coil and comes into contact with the  
cold fin surfaces, heat is transferred from the air to the refrigerant. This heat  
transfer causes the refrigerant to boil and leave the evaporator as vapor.  
16  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Turbulent Flow  
Figure 25  
The fins of the coil are formed to produce turbulence as the air passes through  
them. This turbulence enhances heat transfer, preventing stratification within  
the coil-leaving airstream.  
Finned-Tube Evaporator  
liquid/vapor  
refrigerant  
airflow  
liquid  
distributor  
suction  
refrigerant vapor  
header  
Figure 26  
To provide uniform heat transfer throughout the coil, the liquid refrigerant is  
distributed to the coil tubes in several parallel circuits. A distributor is used to  
ensure uniform refrigerant distribution through these multiple coil circuits. It  
distributes the liquid/vapor refrigerant mixture to the coil through several tubes  
of equal length and diameter.  
As the refrigerant passes through the tubes of the coil, the liquid refrigerant  
absorbs heat from the air, causing it to boil off into vapor. The refrigerant vapor  
leaves the coil tubes and collects in a suction header.  
TRG-TRC005-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
Each distributor has an allowable range of refrigerant flow rates that define its  
stable operating range. As the size of the evaporator coil increases, it may be  
necessary to use more than one distributor to feed liquid refrigerant to the coil.  
notes  
Superheat  
B
A
B
C
A
C
superheat  
Figure 27  
Inside the final length of tubesthe location where the temperature difference  
between the refrigerant and the air is highestthis larger temperature  
difference accelerates the rate of heat transfer and the refrigerant vapor  
absorbs even more heat. When the liquid refrigerant has completely  
evaporated, this additional heat gain to the vapor is called superheating.  
Superheating the refrigerant vapor (the line from B to C) shifts it away from the  
liquid/vapor region and ensures that the refrigerant vapor is completely free of  
liquid prior to traveling to the compressor.  
18  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Shell-and-Tube Evaporator  
chilled  
water  
supply  
chilled  
water  
return  
baffles  
refrigerant  
vapor  
liquid/vapor  
refrigerant  
tube bundle  
Figure 28  
Shell-and-Tube Evaporators  
Instead of producing cooled air, a shell-and-tube evaporator is used to  
produce chilled water. In this type of evaporator, the cool liquid refrigerant  
flows through the tubes and water fills the shell space surrounding the tubes.  
As heat is transferred from the water to the refrigerant, the refrigerant boils  
inside the tubes and the resulting vapor is drawn to the compressor. Water  
enters the shell at one end and leaves at the opposite end.  
This chilled water is pumped to one or more heat exchangers to handle the  
system cooling load. These heat exchangers could be coils used to cool air or  
they could be some other load that requires chilled water.  
Shell-and-Tube Evaporator  
baffles  
Figure 29  
Baffles within the shell direct the water in a rising and falling flow path over the  
tubes that carry the refrigerant. This results in turbulence that improves heat  
transfer.  
TRG-TRC005-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Evaporator Control  
I
Evaporator capacity is influenced by:  
K Temperature difference between refrigerant and air or  
water being cooled  
K Flow rate of air or water through evaporator  
K Flow rate of refrigerant through evaporator  
Figure 30  
Evaporator Control  
The rate of heat exchange within an evaporator is governed by (1) the  
temperature difference between the refrigerant and the air or water being  
cooled, (2) the flow rate of the air or water through the evaporator, and (3) the  
flow rate of the refrigerant through the evaporator.  
In comfort-cooling applications, it is necessary to balance the capacity of the  
system with the ever-changing load. The flow rate and temperature of the air or  
water being cooled are typically controlled to respond directly to the system  
load. A constant-volume system delivers a constant quantity of air to the space  
and, to maintain the required space temperature at all load conditions, varies  
the temperature of this air. In contrast, a variable-air-volume (VAV) system  
delivers air at a constant temperature and varies the airflow to maintain the  
required space temperature at all load conditions.  
These are variables that the evaporator must respond to rather than directly  
control. The most common method of controlling the capacity of the evaporator  
at part load is to control the temperature and/or flow rate of the refrigerant  
through the system by unloading or cycling compressors. To provide stable  
part-load operation and balance compressor unloading with the capacity of the  
evaporator, some direct form of evaporator capacity control may also be  
required.  
20  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Finned-Tube Evaporator Control  
expansion  
valve  
evaporator  
liquid  
refrigerant  
refrigerant  
vapor  
Figure 31  
Typically, an expansion valve is used to control the flow rate of refrigerant  
through the evaporator to maintain the proper amount of superheat, ensuring  
that the liquid refrigerant will be completely vaporized. Working in conjunction  
with the unloading or cycling compressors, the expansion valve allows the  
evaporator capacity to match the system load. The operation of the expansion  
valve will be discussed further in Period Four.  
Face-Split Arrangement  
distributors  
Figure 32  
When an evaporator contains more than one liquid-refrigerant distributor, it is  
split into independently-controlled sections, each being served by its own  
expansion valve. By turning on and shutting off these coil sections, the  
evaporator can further control its capacity to better match the system load.  
The three common arrangements for splitting finned-tube evaporator coils  
include: face-split, intertwined, and row-split.  
TRG-TRC005-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
The face-split coil configuration, also called horizontal-split or parallel-flow, is  
split into parallel sections. A portion of the air passes through the top section,  
the remainder passes through the bottom section, and the two airstreams mix  
downstream of the coil.  
notes  
Face-Split Arrangement  
80ºF  
[27ºC]  
55ºF  
[13ºC]  
80ºF  
[27ºC]  
30ºF  
[-1.1ºC]  
Figure 33  
At lower loads, only one section of the face-split coil is active. A portion of the  
air passes through the active lower section and is cooled, while the rest of the  
air passes through the inactive top section and remains unconditioned. The two  
airstreams mix downstream of the coil, producing average temperature and  
humidity conditions. At higher loads, both sections of the coil are activated,  
providing a more uniform leaving-air temperature.  
In a VAV application, where the leaving air is controlled to a constant  
temperature, the active section of coil must supply colder air than the desired  
average temperature at part load. Consequently, the refrigerant must get colder  
at part load, eventually reaching a condition where the coil surface is cold  
enough that the water condensing from the air will create frost on the coil.  
Resetting the supply air temperature upward can help to avoid this problem,  
but this may result in space humidity problems.  
In constant-volume applications, where the leaving-air temperature varies to  
respond to changing loads, this is not as much of a concern since the average  
mixed temperature rises at part-load conditions. Therefore, face-split coils are  
well suited for constant-volume applications. They provide better part-load  
humidity control than could be obtained from a large coil controlled by a single  
expansion valve. In a constant-volume application, the lower section of a face-  
split coil should be activated first and deactivated last. This sequence prevents  
moisture that has condensed from the air flowing through the active coil  
section from flowing over the fins of the inactive coil section, where it could  
carry over into the supply airstream.  
22  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Intertwined Arrangement  
Figure 34  
The intertwined coil configuration splits the coil sections by alternating the  
tubes fed in each row between two distributors.  
At lower loads, liquid refrigerant is fed to every other tube of the coil and,  
therefore, it behaves like a coil with substantially greater fin surface. At higher  
loads, refrigerant is fed to all of the tubes in the coil.  
Because of the increased fin surface available at part-load conditions, the coil  
surface does not have to be as cold to provide a constant leaving-air  
temperature. This reduces the potential for coil frosting. Therefore, intertwined  
coils are better suited for VAV applications.  
Part-load humidity control is less of an issue with VAV applications due to the  
constant, cold leaving-air temperature. In constant-volume applications,  
intertwined coils provide good part-load humidity control, although potentially  
not as good as face-split coils.  
TRG-TRC005-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
notes  
Row-Split Arrangement  
Figure 35  
Finally, the row-split coil configuration, also called vertical-split or series-flow,  
places the independently-controlled coil sections in series in the airstream. All  
of the air passes through both coil sections, one before the other.  
Typically, the first few upstream rows of the coil are served by one distributor,  
and the remaining downstream rows by another distributor. At lower loads,  
only the downstream section is active. At higher loads, the full depth of the coil  
is active.  
Row-Split Arrangement  
70ºF  
[21ºC]  
80ºF  
[27ºC]  
55ºF  
[13ºC]  
Figure 36  
Row-split coils are very difficult to split into equal-capacity sections. Since the  
air entering the downstream section of coil has already been cooled somewhat  
by the upstream section of coil, the air-to-refrigerant temperature difference is  
much smaller. Therefore, the downstream section of coil requires more rows of  
tubes to deliver about the same capacity as the upstream section of coil. A  
common row-split arrangement uses two rows for the upstream section and  
24  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period three  
Evaporators  
four rows for the downstream section. This is an attempt to ensure near-equal  
loading of the two coil sections when both are active.  
notes  
A second concern involves the control of superheat. The cooler temperatures  
leaving the upstream section of coil hamper the ability of the downstream  
section of coil to provide adequate superheat.  
Row-split coils are generally not recommended for comfort-cooling  
applications. When applied, they require careful coil selection, expansion valve  
sizing and selection, and control.  
Shell-and-Tube Evaporator Control  
shell-and-tube  
evaporator  
refrigerant  
vapor  
liquid  
refrigerant  
expansion  
valve  
Figure 37  
The capacity of a shell-and-tube evaporator is primarily controlled by the  
unloading or cycling of compressors. However, as with a finned-tube  
evaporator, it also uses an expansion valve to control the flow rate of  
refrigerant through the evaporator and ensure the proper amount of superheat  
in the system.  
A shell-and-tube evaporator may also contain more than one liquid refrigerant  
circuit, each served by one expansion valve.  
TRG-TRC005-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
Refrigeration  
System Components  
period four  
Expansion Devices  
Figure 38  
The final major component to be discussed is the expansion device.  
Expansion Device  
condenser  
C
D
expansion  
device  
compressor  
B
A
evaporator  
enthalpy  
Figure 39  
An expansion device is used to maintain a pressure difference between the  
high-pressure (condenser) and low-pressure (evaporator) sides of the system  
established by the compressor. This pressure difference allows the evaporator  
temperature to be low enough to absorb heat from the air or water to be  
cooled, while also allowing the refrigerant to be at a high enough temperature  
in the condenser to reject heat to air or water at normally available  
temperatures.  
There are several types of expansion devices, including expansion valves  
(thermostatic or electronic), capillary tubes, and orifices. This clinic will limit its  
discussion to thermostatic expansion valves (TXVs). Other expansion devices  
perform essentially the same function.  
26  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
Thermostatic Expansion Valve  
thermostatic  
expansion  
valve (TXV)  
liquid  
refrigerant  
evaporator  
liquid/vapor  
mixture  
A
refrigerant  
vapor  
Figure 40  
In addition to maintaining a pressure difference, the thermostatic expansion  
valve controls the quantity of liquid refrigerant entering the evaporator. It  
ensures that the refrigerant will be completely vaporized within the evaporator  
(A) and maintains the proper amount of superheat in the system.  
TXV Control  
liquid  
refrigerant  
liquid/vapor  
mixture  
A
refrigerant  
vapor  
Figure 41  
If not enough liquid refrigerant enters the evaporator, it vaporizes too quickly  
(A). As a result, the remaining coil tubes fill with vapor, producing very little  
refrigeration effect.  
TRG-TRC005-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
TXV Control  
liquid  
refrigerant  
liquid/vapor  
mixture  
Figure 42  
On the other hand, if too much liquid refrigerant enters the evaporator, not all of  
it will be vaporized. As a result, some liquid refrigerant gets into the  
compressor suction line. Since the compressor is designed to compress vapor  
and not liquid, liquid refrigerant can cause excess wear and damage to the  
compressor.  
Superheat  
85 psia, 41ºF  
[0.59 MPa, 5ºC]  
TXV  
liquid  
refrigerant  
290 psia, 109ºF  
[2 MPa, 42.8ºC]  
A
superheated  
vapor  
Figure 43  
The TXV meters refrigerant by measuring the condition of the refrigerant vapor  
leaving the evaporator. Superheat is the additional heat absorbed by the  
refrigerant in the evaporator after it has completely vaporized. It provides a  
safety factor by preventing liquid refrigerant from entering the compressor.  
In the example above, subcooled liquid refrigerant enters the TXV at a  
condensing pressure of 290 psia [2 MPa] and a temperature of 109°F [42.8°C].  
(The refrigerant condensed at 124.3°F [51.3°C] and was subcooled to 109°F  
[42.8°C].) Passing through the TXV causes a large pressure drop, reducing the  
refrigerant pressure to that of the evaporator. This pressure drop causes a small  
28  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
portion of the liquid to boil off, or flash, and has the effect of cooling the  
remaining liquid refrigerant to the desired evaporator temperature. The  
resulting pressure of the refrigerant is 85 psia [0.59 MPa], which corresponds to  
41°F [5°C].  
notes  
Inside the evaporator tubes, as heat is transferred to the liquid refrigerant it  
boils until only vapor remains (A). From this point, the vapor continues to  
absorb heat as it passes through the final lengths of coil tubing, superheating  
the vapor.  
Superheat  
85 psia, 41ºF  
[0.59 MPa, 5ºC]  
TXV  
290 psia, 109ºF  
[2 MPa, 42.8ºC]  
79 psia  
[0.54 MPa]  
49ºF  
[9.4ºC]  
Figure 44  
Continuing with this example, the refrigerant enters the evaporator coil at  
85 psia [0.59 MPa] and 41°F [5°C]. Assuming that the pressure drop through the  
coil tubes is 6 psi [0.04 MPa], the refrigerant vapor leaves the coil at 79 psia  
[0.54 MPa]. The temperature gauge at the outlet of the evaporator coil indicates  
that the superheated refrigerant vapor leaves at 49°F [9.4°C].  
A table of refrigerant properties, for Refrigerant-22 in this example, would show  
that the 79 psia [0.54 MPa] pressure corresponds to a 37°F [2.8°C] evaporating  
temperature. The 12°F [6.7°C] temperature difference between this evaporating  
temperature and the temperature measured at the outlet of the evaporator is  
the amount of additional heat, or superheat, absorbed by the refrigerant vapor  
in the final lengths of coil tubing. Notice that superheating the refrigerant vapor  
changed only its temperaturenot its pressure.  
These same propertiesthe evaporator pressure and the final refrigerant vapor  
temperatureare measured and used by the thermostatic expansion valve to  
control the quantity of liquid refrigerant entering the evaporator.  
TRG-TRC005-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
TXV Operation  
diaphragm  
evaporator  
spring  
remote  
bulb  
suction  
external equalizer  
line  
distributor  
Figure 45  
In a typical TXV application, the outlet of the valve is connected to the  
distributor. A remote bulb is attached to the suction line, where it senses the  
refrigerant vapor temperature leaving the evaporator. This bulb is charged with  
refrigerant and as heat is transferred from the suction line to the bulb, the  
refrigerant inside the bulb vaporizes. The resulting refrigerant vapor pressure is  
transmitted through a tube to the space above a diaphragm in the TXV.  
The pressure of the refrigerant vapor leaving the evaporator is transmitted to  
the space beneath the diaphragm through an external equalizing line that is  
tapped into the suction line downstream of the bulb.  
Finally, the valve contains an adjustable spring that applies a force to the lower  
side of the diaphragm.  
30  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
TXV Operation  
valve diaphragm  
97 psia  
[0.67 MPa]  
spring  
49ºF  
[94ºC]  
79 psia  
[0.54 MPa]  
18 psi  
[0.13 MPa]  
79 psia  
[0.54 MPa]  
suction  
line  
valve pin  
Figure 46  
Using the conditions from the previous example, the 49°F [9.4°C] refrigerant  
vapor leaving the evaporator boils the refrigerant in the bulb, generating  
97 psia [0.67 MPa] of pressure within the remote bulb. This pressure is  
transmitted to the top side of the valve diaphragm, creating a force that pushes  
down on the diaphragm.  
The 79 psia [0.54 MPa] evaporating pressure, on the other hand, is transmitted  
to the bottom side of the valve diaphragm, producing an opposing force.  
Since the difference between the evaporator pressure and the pressure within  
the remote bulb is due to superheat, the tension of the spring is adjusted to  
provide the difference in order to balance the forces and produce the desired  
amount of superheat. In this example, the spring tension is adjusted to produce  
an 18 psi [0.13 MPa] pressure difference, which corresponds to 12°F [6.7°C] of  
superheat.  
Any variation in evaporator pressure causes these forces to vary from this  
equilibrium and move the pin up or down, thus closing or opening the valve.  
Closing the valve reduces the flow of refrigerant to the evaporator, while  
opening the valve increases the flow. In other words, with this valve spring  
adjustment, the refrigerant vapor must absorb 12°F [6.7°C] of superheat before  
the forces that open and close the valve come into equilibrium, stabilizing the  
refrigerant flow rate to the evaporator.  
TRG-TRC005-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
TXV Operation  
external equalizer  
TXV  
remote  
bulb  
B
A
Figure 47  
C
For example, assume that an increasing system load causes the refrigerant  
within the coil to vaporize at a faster rate than desired. This moves the point at  
which the refrigerant becomes completely vaporized from A toward B. This  
increase in coil surface used for superheating results in the refrigerant vapor  
leaving the evaporator at a higher temperature. Sensing the rising superheat,  
the remote bulb transmits a higher pressure to the top side of the TXV  
diaphragm, causing the valve to open further and allow more refrigerant to  
flow into the evaporator.  
This increased flow of refrigerant moves the point of complete vaporization  
back toward A, until the desired superheat condition is reestablished and the  
opening and closing forces within the valve equalize at a refrigerant flow rate  
that balances the new system load.  
Conversely, a decreasing system load slows the rate at which the refrigerant  
vaporizes, moving the point of complete vaporization toward C. The resulting  
reduction in superheat creates a lower pressure inside the remote bulb and,  
therefore, on the top side of the diaphragm. This causes the valve to close  
more, reducing the flow of liquid refrigerant into the evaporator. This reduction  
in refrigerant flow moves the point of complete vaporization back toward A,  
reestablishing the desired superheat condition.  
32  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period four  
Expansion Devices  
notes  
Superheat Setting  
I
Too little superheat:  
K Risk of damage to compressor by liquid refrigerant  
I
Too much superheat:  
K Reduction of system efficiency  
K Potential of coil frosting  
K Risk of compressor damage due to overheating  
Figure 48  
A typical recommended superheat setting is from 8 to 12°F [4.4 to 6.7°C].  
Too little superheat is risky because it presents a danger of allowing refrigerant  
to leave the evaporator in the liquid state. As mentioned earlier, the compressor  
is designed to compress vapor, not liquid. Liquid refrigerant can cause damage  
to the compressor.  
Too much superheat dedicates too much of the tube surface to the production  
of superheat, reducing system efficiency. In extreme cases, it can lead to coil  
frosting; it may also cause the compressor to overheat, possibly shortening its  
service life.  
TRG-TRC005-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Refrigeration  
System Components  
period five  
Accessories  
Figure 49  
This period discusses several accessories used in comfort-cooling refrigeration  
systems.  
Solenoid Valve  
Figure 50  
Solenoid Valve  
A solenoid valve is used to stop the flow of refrigerant within the system.  
These valves are magnetically operated, and an electric winding controls the  
opening and closing of the valve. The valve is typically a normally-closed type  
of valve so that it is closed when it is deenergized.  
34  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Solenoid Valve  
expansion  
valve  
finned-tube  
evaporator  
solenoid  
valves  
Figure 51  
One common use of a solenoid valve is to control the flow of liquid refrigerant  
to multiple sections of the evaporator. In this application, a valve is installed in  
the liquid line, upstream of the expansion valve for each individually controlled  
section of the evaporator coil.  
Using the example of a face-split evaporator coil, at lower loads a solenoid  
valve may be used to shut off the flow of liquid refrigerant to the top section of  
the coil. A portion of the air passes through the active lower section and is  
cooled, while the rest of the air passes through the inactive top section and  
remains unconditioned. The two airstreams mix downstream of the coil. At  
higher loads, both sections of the coil are activated.  
Solenoid Valve  
discharge  
line  
liquid line  
condenser  
evaporator  
expansion  
valve  
compressor  
suction  
line  
solenoid  
valve  
Figure 52  
Another common use of a solenoid valve is to enable system pump-down and  
prevent the refrigerant from migrating through the system when the  
compressor is shut off. In this application, a single solenoid valve is installed in  
the liquid line, upstream of all expansion valves.  
TRG-TRC005-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
When the compressor is shut off, the evaporator contains a large quantity of  
liquid refrigerant. This can present a problem if some of the refrigerant drains  
into the suction line and slugs the compressor when it starts up again. To  
prevent this from occurring, many systems pump the refrigerant out of the  
evaporator and suction line before shutting the compressor off. This is called a  
pump-down cycle. Instead of shutting the compressor off right away, the  
solenoid valve is closed to stop the flow of liquid refrigerant into the  
evaporator, and the compressor is allowed to run for a short period of time. The  
compressor pumps the refrigerant from the low-pressure side of the system  
(evaporator and suction line) to the high-pressure side of the system (discharge  
line, condenser, and liquid line.)  
notes  
As the low-pressure side of the system is pumped free of refrigerant, the  
pressure in that part of the system drops. To end the pump-down cycle, a  
pressure sensor is used to shut the compressor off when this pressure reaches  
a predetermined set point. Prior to starting the compressor again, the solenoid  
valve is opened, allowing the pressure on the low-pressure side of the system  
to increase again.  
The solenoid valve should be installed as close to the expansion valve as  
possible. This will minimize the pump-down time and allow the liquid line to be  
used for storing refrigerant when the system is off.  
Liquid-Line Filter Drier  
liquid line  
liquid-line  
expansion  
filter drier  
valve  
solenoid  
valve  
evaporator  
Figure 53  
Liquid-Line Filter Drier  
The next accessory to be discussed, the liquid-line filter drier, is installed  
upstream of the solenoid valve and the expansion valve. It prevents moisture  
(water) and foreign matter, introduced during the installation process, from  
entering the expansion valve and the solenoid valve. Realize, however, that  
there is no substitute for cleanliness during system installation.  
Moisture and foreign matter can cause problems in any refrigeration system.  
When water is mixed with refrigerant and oil, and heat is added by the  
compressor, acids are formed that can damage the valves or compressor.  
Additionally, certain foreign materials such as copper and brass particles can  
36  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
act as a catalyst in chemical reactions that result in the formation of acids.  
These acids can corrode system components and cause the oil to sludge.  
notes  
The filter drier should be installed close to the solenoid valve to provide the  
most protection for the solenoid and expansion valves.  
Liquid-Line Filter Drier  
replaceable  
core type  
core  
sealed type  
Figure 54  
A typical liquid-line filter drier includes a molded, porous core. The core has a  
high affinity for moisture and removes foreign matter from the refrigerant.  
The two common types of filter driers are replaceable core and sealed. The  
replaceable core type allows the core to be easily replaced. The sealed type is  
completely closed, reducing the chances of refrigerant leaks.  
Ball-type shutoff valves are typically installed just upstream and downstream to  
allow the filter drier to be isolated and the core (or unit) replaced.  
TRG-TRC005-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Moisture-Indicating Sight Glass  
liquid line  
sight  
expansion  
glass  
valve  
Figure 55  
Moisture-Indicating Sight Glass  
A moisture-indicating sight glass is installed in the liquid line, upstream of  
the expansion valve, and permits the operator to observe the condition of the  
refrigerant prior to entering the expansion valve. The value of the sight glass is  
in its moisture indication abilitythe sight glass should not be used to  
determine system refrigerant charge or subcooling. Actual temperature and  
pressure measurements are required to determine proper charge and  
subcooling.  
With the sight glass installed directly ahead of the expansion valve, it can also  
be used to detect the presence of bubbles in the liquid line. This would indicate  
that some of the liquid refrigerant has flashed into vapor upstream of the  
expansion valve. Since the expansion valve is designed to control the flow of  
liquid refrigerant only, the presence of refrigerant vapor results in a reduction in  
the quantity of liquid refrigerant being fed to the evaporator. There are many  
potential causes of liquid refrigerant flashing. The sight glass can alert the  
operator to the condition.  
38  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Suction Line Filter  
suction  
line filter  
compressor  
suction  
line  
Figure 56  
Suction Line Filter  
Similar to the liquid-line filter drier, the suction line filter performs the task of  
removing foreign matter from the refrigeration system. It is installed in the  
suction line, just upstream of the compressor.  
The suction filter contains filter media to remove copper filings, flux, dirt, and  
other foreign matter that may have been introduced during the installation  
process or as the result of a compressor failure. It protects the compressor parts  
from the abrasive action that could result if these materials enter the  
compressor. Dirt can obstruct oil passages, robbing the compressor bearings of  
lubrication.  
Suction Line Filter  
replaceable  
core type  
sealed type  
Figure 57  
Similar to the liquid-line filter drier, the two common types of suction line filters  
are replaceable core and sealed. The replaceable core type allows the core to be  
easily replaced. The sealed type is completely closed, reducing the chances of  
refrigerant leaks.  
TRG-TRC005-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
Replaceable core suction filters are commonly installed after a compressor  
failure has occurred. The core is replaced after the foreign matter or acid has  
been removed from the system.  
notes  
Additionally, suction filters should be installed in all field-assembled systems.  
Hot Gas Muffler  
discharge  
reciprocating  
line  
compressor  
hot gas  
muffler  
shell  
Figure 58  
perforated tube  
Hot Gas Muffler  
The purpose of the hot gas muffler is to smooth out the pulsations associated  
with the refrigerant vapor being discharged from a reciprocating compressor,  
reducing noise and vibration.  
The pressure of the refrigerant vapor leaving a reciprocating compressor  
fluctuates rapidly because of the manner in which it is compressed by the  
reciprocating pistons. The muffler contains a perforated tube inside a shell. The  
pressure peaks cause some of the refrigerant vapor to pass from the perforated  
tube into the muffler shell. This shell is divided into chambers that allow it to  
absorb these peaks. In essence, the muffler shaves off the peaks of these  
pulsations and fills in the valleys, reducing the pulsating characteristic in the  
discharge line.  
When used, the hot gas muffler should be located in the discharge line, as close  
to the reciprocating compressor discharge as possible. This minimizes the  
sound emission from the unmuffled section of discharge line.  
40  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Shutoff Valve  
shutoff  
valve  
shutoff  
valve  
liquid line  
condenser  
evaporator  
liquid-line  
filter drier  
compressor  
shutoff  
valves  
Figure 59  
Shutoff Valve  
Shutoff valves are used to isolate one part of the refrigeration system from  
the rest. Additionally, they can be used to trap the refrigerant charge in one  
component of the system, the condenser for example, to permit service or  
repair to another part of the system.  
Common uses of shutoff valves include:  
I
I
I
Isolating the liquid-line filter drier and suction filter to allow easier core (or  
unit) replacement  
Isolating the compressor from the rest of the system to allow for repair or  
replacement  
Isolating the charge within the condenser or a receiver to allow access to the  
rest of the system  
TRG-TRC005-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period five  
Accessories  
notes  
Access Port  
condenser  
evaporator  
liquid line  
access port  
compressor  
suction line  
access ports  
Figure 60  
Access Port  
An access port is used to add refrigerant to the system or for measurement.  
An access port is typically installed in the liquid line in a convenient location  
and is used to charge the system with liquid refrigerant. It is also used to  
measure subcooling.  
The suction line typically includes two access ports. One is installed near the  
compressor and is used to measure suction pressure. The other is located near  
the external equalizer-line connection for the expansion valve, and is used to  
measure superheat when checking or adjusting the expansion valve setting.  
42  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
Refrigeration  
System Components  
period six  
Review  
Figure 61  
We will now review the main concepts that were covered in this clinic about the  
components in a vapor-compression refrigeration system.  
Review—Period One  
condenser  
C
D
expansion  
device  
compressor  
B
A
evaporator  
enthalpy  
Figure 62  
Period One reviewed the vapor-compression refrigeration cycle using the P-h  
chart.  
A cool, low-pressure mixture of liquid and vapor refrigerant enters the  
evaporator (A) and absorbs heat from the relatively warm air or water that is  
being cooled. This transfer of heat boils the liquid refrigerant in the evaporator  
and superheated refrigerant vapor (B) is drawn to the compressor.  
The compressor raises the pressure and temperature (C) high enough that the  
refrigerant vapor can reject heat to another fluid. This hot, high-pressure  
refrigerant vapor then travels to the condenser where heat is transferred to  
relatively cool ambient air or cooling water. This reduction in the heat content  
TRG-TRC005-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
of the refrigerant vapor causes it to desuperheat, condense into liquid, and  
further subcool before leaving the condenser (D) for the expansion device.  
notes  
Finally, the high-pressure liquid refrigerant flows through the expansion device,  
causing a large pressure drop (the line from D to A) that reduces the pressure  
of the refrigerant to that of the evaporator. This pressure reduction causes a  
small portion of the liquid to boil off, or flash, cooling the remaining refrigerant  
to the desired evaporator temperature. The cooled refrigerant then enters the  
evaporator (A) to repeat the cycle.  
Review—Period Two  
evaporative  
condenser  
air-cooled  
condenser  
water-cooled  
condenser  
Figure 63  
Period Two discussed the different types of condensers and methods of  
condenser control. The condenser rejects heat from the refrigerant to air, water,  
or some other fluid. The three common types of condensers are air-cooled,  
water-cooled, and evaporative.  
44  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
Review—Period Three  
finned-tube  
evaporator  
shell-and-tube  
evaporator  
Figure 64  
Period Three presented the different types of evaporators and methods of  
evaporator control. The evaporator transfers heat from air, water, or some other  
fluid to the cool liquid refrigerant. The two common types of evaporators are  
finned-tube and shell-and-tube.  
Review—Period Four  
distributor  
evaporator  
TXV  
remote  
bulb  
external equalizer  
Figure 65  
Period Four reviewed the operation of the expansion device, specifically the  
thermostatic expansion valve. The expansion device is used to maintain the  
pressure difference between the high-pressure (condenser) and low-pressure  
(evaporator) sides of the system established by the compressor.  
In addition, the thermostatic expansion valve (TXV) controls the quantity of  
liquid refrigerant entering the evaporator. It ensures that the refrigerant will be  
completely vaporized within the evaporator and maintains the proper amount  
of superheat in the system.  
TRG-TRC005-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
Review—Period Five  
shutoff  
valve  
access  
port  
condenser  
suction  
line filter  
solenoid  
valve  
TXV  
compressor  
sight  
glass  
liquid-line  
filter drier  
evaporator  
Figure 66  
Period Five discussed several accessories commonly used in comfort-cooling  
applications, including: solenoid valve, liquid-line filter drier, moisture-  
indicating sight glass, suction line filter, hot gas muffler, shutoff valve, and  
access port.  
The solenoid valve is used to stop the flow of refrigerant within the system. A  
liquid-line filter drier prevents moisture and foreign matter from damaging the  
valves or compressor. The moisture-indicating sight glass permits the operator  
to observe the condition of the refrigerant within the liquid line before it enters  
the expansion device. A suction line filter protects the compressor from foreign  
matter in the suction line. The hot gas muffler is used to reduce noise and  
vibration associated with reciprocating compressors. Shutoff valves are used to  
isolate one part of the refrigeration system, and access ports allow a technician  
to gain access to the system for charging or measurement.  
46  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
period six  
Review  
notes  
Figure 67  
For more information, refer to the following references:  
I
I
I
Trane Air Conditioning Manual  
Trane Reciprocating Refrigeration Manual  
The DX Refrigerant Cooling Coil Conundrum” (Trane Engineers Newsletter,  
1988volume 17, number 1)  
I
I
I
ASHRAE Handbook – Fundamentals  
ASHRAE Handbook – Refrigeration  
ASHRAE Handbook – Systems and Equipment  
For more information on additional educational materials available from Trane,  
contact your local Trane office (request a copy of the Educational Materials  
catalog – Trane order number EM-ADV1) or visit our online bookstore at  
TRG-TRC005-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quiz  
Questions for Period 1  
E
D
G
F
H
B
C
A
enthalpy  
Figure 68  
1
2
Using the pressure–enthalpy chart in Figure 68, which two points  
correspond to superheating the refrigerant vapor inside the evaporator?  
Again using Figure 68, which two points correspond to subcooling the  
liquid refrigerant inside the condenser?  
Questions for Period 2  
3
4
5
List the three common types of condensers.  
What two factors cause the condensing pressure to drop?  
What are two methods of control that can be applied to air-cooled  
condensers?  
Questions for Period 3  
6
What is the name of the device used to ensure uniform refrigerant  
distribution through the multiple-coil circuits of a finned-tube evaporator?  
7
8
What is the purpose of the baffles inside the shell-and-tube evaporator?  
What are the three common arrangements for splitting finned-tube  
evaporator coils?  
9
When using a face-split coil in a constant-volume application, which section  
(top or bottom) of the coil should be activated first and deactivated last?  
48  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quiz  
Questions for Period 4  
10 What are the two primary purposes of a thermostatic expansion valve?  
11 What are the risks of too much superheat in the system?  
Questions for Period 5  
12 During a pump-down cycle, the compressor pumps the refrigerant from the  
_____ (low or high)-pressure side of the system to the _____ (low or high)-  
pressure side.  
13 Is the moisture-indicating sight glass installed upstream or downstream of  
the expansion valve?  
TRG-TRC005-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Answers  
1
2
3
4
5
B to C  
F to G  
Air-cooled, evaporative, and water-cooled  
A decrease in system load and a reduction in the outdoor air temperature  
Varying the airflow through the condenser coil or flooding the condenser  
coil with liquid refrigerant  
6
7
A distributor  
To direct the water in a rising and falling flow path over the tubes that carry  
the refrigerant; resulting in turbulence that improves heat transfer  
8
9
Face-split, intertwined, and row-split  
Bottom section  
10 The thermostatic expansion valve a) maintains the pressure difference  
between the high-pressure and low-pressure sides of the system, and b)  
maintains the proper amount of superheat in the system by metering the  
quantity of liquid refrigerant entering the evaporator, ensuring it will be  
completely vaporized within the evaporator.  
11 Too much superheat dedicates too much of the tube surface to the  
production of superheat, reducing system efficiency. In extreme cases, it  
can lead to coil frosting and overheating of the compressor, compromising  
its longevity.  
12 Low-pressure side to the high-pressure side  
13 Upstream of the expansion valve  
50  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
access port A device that allows a technician to gain access to the  
refrigeration system for charging or measurement.  
air-cooled condenser A type of condenser where refrigerant flows through the  
tubes and rejects heat to air that is drawn across the tubes.  
ASHRAE American Society of Heating, Refrigerating and Air-Conditioning  
Engineers  
capillary tube A type of expansion device that uses a long, narrow tube to  
reduce the pressure and temperature of the refrigerant.  
centrifugal fan air-cooled condenser A type of air-cooled condenser that uses  
a centrifugal fan instead of a propeller fan, allowing it to overcome the larger  
static pressures associated with ductwork.  
compressor The mechanical device in the refrigeration system used to  
increase the pressure and temperature of the refrigerant vapor.  
condenser The component of the refrigeration system where refrigerant  
vapor is converted to liquid as it rejects heat to water or air.  
cooling tower A device used to reject the heat from a water-cooled condenser  
by spraying the condensing water over the fill while drawing outdoor air  
upward through the fill.  
distributor A device used to ensure uniform refrigerant distribution through  
the multiple-coil circuits of a finned-tube evaporator.  
electronic expansion valve A type of expansion device that uses an  
electronically-actuated valve to sense and control the flow rate of liquid  
refrigerant to the evaporator.  
enthalpy The property of a refrigerant indicating its heat content, both  
sensible and latent, per pound [kg] of refrigerant.  
evaporative condenser A type of condenser where refrigerant flows through  
the tubes and rejects heat to air. The air is drawn across the tubes, which are  
wetted on the outside by circulating water.  
evaporator The component of the refrigeration system where cool liquid  
refrigerant absorbs heat from air, water, or some other fluid, causing the  
refrigerant to boil.  
expansion device The component of the refrigeration system used to reduce  
the pressure and temperature of the refrigerant.  
expansion valve The type of expansion device that maintains the pressure  
difference between the high-pressure and low-pressure sides of the system. It  
also maintains the proper amount of superheat in the system by metering the  
quantity of liquid refrigerant entering the evaporator, ensuring that the  
refrigerant will be completely vaporized within the evaporator  
TRG-TRC005-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
face-split A type of finned-tube evaporator arrangement that splits the coil  
into parallel air paths.  
fill The heat transfer surface inside a cooling tower.  
finned-tube evaporator A type of evaporator where refrigerant flows through  
the tubes and air blows across the tubes and fins.  
flash The process of liquid refrigerant being vaporized by a sudden reduction  
of pressure.  
hot gas muffler A device installed at the discharge of the compressor to  
reduce noise and vibration associated with reciprocating compressors.  
intertwined A type of finned-tube evaporator arrangement that splits the coil  
by alternating the tubes fed in each row between two distributors.  
liquid-line filter drier A device installed in the liquid line to remove moisture  
(water) and foreign matter, introduced during the installation process, from the  
refrigeration system.  
moisture-indicating sight glass See sight glass, moisture indicating.  
orifice plate A type of expansion device that uses a fixed plate with holes  
drilled in it to reduce the pressure and temperature of the refrigerant.  
pressure–enthalpy chart A graphical representation of the saturated  
properties of a refrigerant, plotting refrigerant pressure versus enthalpy.  
pump-down cycle A control sequence used in a refrigeration system to pump  
the refrigerant from the low-pressure side of the system to the high-pressure  
side of the system.  
refrigeration effect The amount of heat that each pound [kg] of liquid  
refrigerant will absorb when it evaporates.  
row-split A type of finned-tube evaporator arrangement that splits the coil by  
placing the independently-controlled coil sections in series in the airstream.  
shell-and-tube evaporator A type of evaporator where refrigerant flows  
through the tubes and water fills the surrounding shell.  
shutoff valve Devices used to isolate one part of the refrigeration system from  
the rest.  
sight glass, moisture-indicating A device installed in the liquid line, upstream  
of the expansion valve, used to detect moisture in the system and determine if  
the liquid refrigerant has flashed into vapor before entering the expansion  
valve.  
solenoid valve A device used to stop the flow of refrigerant within the  
refrigeration system.  
52  
TRG-TRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
subcooler The lower portion of the condenser that further cools the saturated  
liquid refrigerant.  
suction header A section of pipe used to collect the refrigerant vapor when it  
leaves the tubes of a finned-tube evaporator coil.  
suction line filter A device installed in the suction line to remove foreign  
matter from the refrigeration system.  
superheat The amount of heat added to the refrigerant vapor after it has  
completely vaporized within the evaporator.  
thermostatic expansion valve A type of expansion device that uses a  
thermally-actuated valve to sense and control the flow rate of liquid refrigerant  
to the evaporator.  
water-cooled condenser A type of condenser where water flows through the  
tubes and absorbs heat from the refrigerant that fills the surrounding shell.  
TRG-TRC005-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
TRG-TRC005-EN  
E/AV-FND-TRG-TRC005-1199-EN  
2803-3-784 and 2803-5-1284  
Inland-La Crosse  
The Trane Company  
Supersedes  
Worldwide Applied Systems Group  
3600 Pammel Creek Road  
La Crosse, WI 54601-7599  
Stocking Location  
An American Standard Company  
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change  
design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tekram Technology Network Card TR 824 User Manual
Thermaltake Personal Computer Socket 478 User Manual
Toshiba Camcorder HDD2136 User Manual
Toshiba Scale EM 31061A User Manual
Tripp Lite Switch B119 302 R User Manual
Universal Power Group Battery Charger Jump Starters Battery Charger Solutions User Manual
ViewSonic Computer Monitor VX2265wm User Manual
Viking Microwave Oven DMOR205 User Manual
Wagner SprayTech Paint Sprayer 867 User Manual
Weed Eater Tiller 010394 User Manual