State Industries Water Heater STC 080 User Manual

SERVICE HANDBOOK  
FOR  
STANDARD RESIDENTIAL  
GAS WATER HEATERS  
(NON POWER VENTED MODELS)  
Printed in the USA 0604  
$15.00  
Part Number STC-080  
This service handbook addresses service issues associated with Standard Residential Gas  
Water Heaters. Includes C-3 Flammable Vapor Technology.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Tools Required:  
Phillips head screw driver  
3/8, 7/16, ¾ inch open end wrenches  
3/16 inch Allen wrench  
11/16 inch – 6 point – socket – for anode removal  
set of marked drill bits  
electrical multimeter  
gas pressure gauge or monometer  
water pressure gauge  
thermometer  
tubing cutter if pilot tube is to be replaced  
hose – to drain tank  
container – to measure gallons per minute flow  
MISCELLANEOUS INFORMATION  
Draw efficiency is the quantity of hot water available to the consumer before the outlet water  
temperature decreases 25 degrees F. A 40 gallon water heater will typically provide 70% (28  
gallons) of this “usable” hot water. The burner is allowed to operate during this test. Incoming,  
cold water mixes the remaining stored water below this 25 degree limitation.  
Energy Factor is an indicator of the combined thermal efficiency and standby efficiency of a  
water heater. The higher the energy factor, the more efficient the water heater will be.  
Recovery rate is the amount of water that is heated to a set temperature, per hour. An  
example might be that a water heater has a recovery rate of 30 gallons of water per hour at 80  
degree F. (Fahrenheit) temperature rise.  
“R” Value is a measure of the resistance of a substance to heat flow.  
Thermal efficiency is approximately the amount of generated BTU (British Thermal Units),  
which enters the water. A percentage of the total BTU passes out through the vent piping.  
Temperature rise is the increase in the temperature from its coldest “inlet” water temperature  
to the desired hot (outlet) setting. Typically this is assumed to be 40 degrees entering water;  
120 degrees desired stored water or 80 degrees “temperature rise.”  
Standby efficiency – the water heater’s ability to contain heat in the tank. A minimum of tank  
water heat loss per hour is desired.  
Sample: temperature change = Btu/h loss/ square foot of tank surface  
“R” value  
Water cannot (for all practical purposes) be compressed.  
Water expands when it is heated.  
2
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Water Hammer – is a concussion of moving water against the sides of a containing pipe or  
vessel on a sudden stoppage of flow.  
EX: 1/2 “copper pipe, 5GPM flow (7.2ft/sec.) – stop. Pressure rise of approximately 412 PSI.  
3/4” copper pipe, 5GPM flow (3.3ft/sec) – stop. Pressure rise of approximately 188 PSI  
Minerals and gases will separate from water as temperature increases.  
Formulas:  
Btu (British Thermal Unit) is the heat required to raise 1 pound of water 1°F  
1 BTU = 252 cal = 0.252 kcal  
1 cal = 4.187 Joules  
BTU X 1.055 = Kilo Joules  
BTU divided by 3,413 = Kilowatts  
To convert from Fahrenheit to Centigrade: (° F – 32) times 5/9, or .556, equals degrees C.  
One gallon of (120° F, 49°C) water weighs approximately 8.25 pounds.  
Pounds X .45359 = Kilogram  
Gallons X 3.7854 = Liters  
% of Hot = (Mixed Temp. – Cold) divided by (Hot Temp. – Cold)  
% Thermal Efficiency = (GPH X 8.25 X Temp. Rise X 1.0) divided by BTU/H Input  
Btu Output = GPH X 8.25 X Temp. Rise X 1.0  
GPH = (BTU/H Input X % Eff.) divided by (Temp. Rise X 8.25)  
One cubic foot of Natural Gas contains about 1000 BTU of heat.  
One “thermis equal to 100,000 BTU  
One cubic foot of Propane Gas contains about 2500 BTU of heat.  
One gallon of Propane gas contains about 91,250 BTU of heat.  
One pound of Propane gas contains about 21,600 BTU of heat.  
One pound of gas pressure is equal to 27.7 inches water column pressure  
Inches of Water Column X .036091 = PSI  
Inches of Water Column X .073483 = Inches of Mercury (Hg.)  
3
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Centimeters = Inches X 2.54  
MM (millimeters) = Inches X 25.4  
Meters = Inches X .0254  
Doubling the diameter of a pipe will increase its flow capacity (approximately) 5.3 times.  
CONSTRUCTION:  
Tank is constructed of steel.  
The inside of the tank is constructed of a glass lining bonded to the steel. This prevents  
water to metal contact and rusting of the tank.  
An anode rod will be installed within the tank. The hex-head plug end of the anode is visible  
on the top of the water heater. This metal rod offers secondary protection of the tank against  
corrosion where the application of glass is not possible (threaded tank openings). These areas  
will have small areas of water to metal contact.  
All water heaters will contain at least one thermostat (to operate the heater) and one high  
limit (to prevent water temperatures approaching the “steam” level).  
4
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
INSTALLATION OF RESIDENTIAL GAS WATER HEATER  
Water  
Exhaust Vent to  
Shut Off  
Outside of Building  
Valve  
Union  
Union  
Expansion Tank  
Pressurize to Equal  
Supply Water  
Pressure  
See Manual and  
Labels For Installation  
Clearances  
Temperature And  
Pressure Relief  
Valve – Do Not  
Reuse Old Valve.  
Typical Model  
and Rating  
Plate Location  
Temperature and  
pressure relief valve  
tube piped to within 6”  
of drain.  
Maximum Gas Supply  
13.8” W.C. or ½ PSI  
Minimum  
Thermostat –  
4.5” W.C. –Natural Gas  
11.0” W.C. Propane Gas  
recommended starting  
point - 120°F.  
Safety Pan – Piped to  
Drain  
Drain  
Air Is Drawn In For  
Combustion. Keep  
area clean and free  
from flammables and  
flammable vapors  
Inner and  
Outer Doors –  
Reinstall After  
Lighting Pilot.  
Installation Must Follow Local Codes and Instruction Manual Guidelines  
5
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
RESIDENTAL GAS WATER HEATER SERVICE  
This portion of this manual applies to the Operations and Servicing of Residential Gas, Tank  
Type, Water Heaters, which are vented atmospherically and use a thermocouple as their  
electrical source.  
Control: There is one control on this style of water heater. The control has a main gas  
regulator, pilot gas regulator, on-off-pilot knob, controls water temperature, has a temperature  
adjustment knob, and a high water temperature limit safety.  
σ(delta)  
Note: The word “Hot”  
may or may not be  
present on the control  
knob  
6
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas – continued  
Burner: The burner assembly consists of the main burner, main burner orifice, main burner  
gas supply tube, pilot burner, pilot burner orifice, pilot burner gas supply tube and thermocouple.  
The pilot burner remains on once it is manually lit. When incoming cold water activates the  
thermostat, gas flows to the main burner. The pilot flame ignites this gas. The main flame  
burns until the tank reaches set temperature then the thermostat interrupts this main gas flow.  
AFTER HAVING CONFIRMED THAT THE WATER HEATER HAS BEEN INSTALLED  
PER THE INSTALLATION MANUAL INSTRUCTIONS:  
Normal Operation  
Electrical: The Pilot Flame heats the end of a thermocouple. As the thermocouple is heated,  
it generates a small (cannot be detected without an electrical meter) electrical current to the  
bottom of the control valve. This current powers the electromagnet and holds open the safety  
valve as long as the pilot flame is heating the thermocouple. DANGER! If the pilot is  
extinguished, it can take up to 180 seconds for the thermocouple to cool sufficiently to close the  
safety valve.  
See also C3 technology product information beginning on page 15 .  
7
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas – continued  
Temperature: Two metal probes mounted  
onto the back of the control are immersed  
inside the tank water. One probe (the  
shorter) acts as a temperature high limit. If  
water gets excessively hot, a sensor within  
the probe opens, interrupts the small  
electrical current to the gas valve, and gas  
flow through the control is interrupted. If this  
safety sensor opens, the entire control must  
be replaced.  
The longer probe contains a metal rod that  
expands and contracts as water temperature  
around the probe cools and heats. As the  
rod expands, it pushes against a lever  
actuated gas valve. If the regulator is  
pushed sufficiently, gas flow is interrupted to  
the main burner. Adjusting the temperature  
dial changes the distance the rod must  
expand or contract to open or close the gas  
valve.  
Gas: When you prepare to light the pilot,  
you are instructed to turn the top  
knob to the pilot position and depress  
the knob. When the knob is  
depressed gas will flow to the pilot  
burner only. You then have to  
(manually) ignite this pilot gas. When  
the pilot is lit, the flame must heat the  
thermocouple until it generates  
sufficient electricity to the gas valve  
to allow you to release the knob while  
gas continues to flow to the pilot.  
When the top knob is turned to the  
“ON” position, gas is also available to  
the main burner if the thermostat calls  
for heat.  
8
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas - continued  
Water Flow: When a hot water faucet is opened, water pressure from the well tank or street  
main forces cold water into the water heater. This pushes hot water out of the tank.  
Operation: A residential water heater is not a precise operating appliance. Because the water  
heater relies on the expansion and contraction of a metal rod, when the thermostat dial is set at  
an indicated setting (“” is recommended as a starting setting. This is approximately 120  
degrees F.) The heater may shut off at 110 to 130° F. The heater will consistently shut off at  
this same temperature. For this same reason, water temperature may drop 15 - 25° F, around  
the temperature probe, before the main burner is activated. Keep in mind that hot water in the  
upper part of the tank will probably be very near the “shut off” temperature of the control while  
incoming cold water drops the water temperature around the thermostat probe. Also, short  
repeating heating cycles caused by small hot water uses can cause temperatures at the point of  
use to exceed the thermostat setting by up to 30° F.  
Setting Approximate Temperature (°F) Time To Produce 2nd & 3rd  
Degree Burns on Adult Skin  
120° ± 10°  
130° ± 10°  
140° ± 10°  
150° ± 10°  
160° ± 10°  
5 Minutes  
30 Seconds  
5 Seconds  
Hot ()  
A
B
C
1.5 Seconds  
Under 1 Second  
Very Hot  
9
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas - continued  
Service:  
Air: A gas burning appliance requires the oxygen contained in 12.5 cubic feet of air (at sea  
level) for every 1000 BTU of heat that is generated. If your water heater has a BTU per hour  
input of 40,000 BTU then a minimum of 500 (40 times 12.5) cubic feet of clean air must be  
available. This oxygen will mix with the gas for a clean, blue flame in the burner chamber and  
provide dilution air for flue products.  
(Enters  
Here)  
12.5  
Cubic  
Feet of  
Air  
1,000  
BTU  
Fuel  
+
=
(Enters Here)  
Do not forget that your gas (or oil) furnace and gas clothes dryer also require a like amount of  
air.  
When calculating air supply provisions, also consider the presence of whole house exhaust fans  
or other exhaust fans competing for the same air supply.  
Air must be allowed to enter the heater chamber from the base of the heater and also enter the  
flue vent from below the draft hood. Do not block these areas with insulation blankets or  
obstructions lying around the base of the heater.  
Lack of Oxygen: If a sufficient supply of oxygen (air) is not available for combustion and  
dilution, the result will be:  
Pilot outage  
Yellow burner flame  
Sooting water heater  
10  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Possible carbon monoxide  
Smell of burnt gas in the room  
Residential Gas – continued  
The instruction manual gives guidelines under “Air Requirements” and “Unconfined “ or  
“Confined Space” sections. If you want to test for a lack of air:  
1. Turn on every appliance and fan that exhausts air from the utility room and/or house.  
Make sure all windows and doors are closed, as well as chimney dampers.  
2. Open a hot water faucet so that the main burner will ignite  
3. Remove the outer door of the water heater – not the inner door  
4. Monitor the flame characteristics for several minutes  
If the flame begins to “yellow” open a door or window, to the outdoors, to see if additional air  
corrects this back to blue. If it does, the room needs more air supply. Perform draft test at draft  
hood of water heater with match or smoke source to verify.  
Testing with  
Gas  
Pressure  
Gauge  
Pilot Gas  
Pressure  
Test  
Manifold  
Gas Pressure  
Test  
Gas pressure checks are done with flowing gas.  
Supply gas pressure checks are taken ahead of the gas control and as close to the heater  
as possible.  
Pilot gas pressure checks are taken by using fitting adapters to tap into the pilot gas tubing.  
Manifold (main burner) gas pressure is measured using the Allen wrench tap on the  
bottom of the control valve.  
Desired gas pressures will be noted on the gas valve label.  
If …  
… then  
supply gas pressure is under desired pressure  
setting  
increase supply gas pressure regulator  
setting and,  
increase supply gas piping size.  
add gas pressure regulator.  
reduce setting on existing regulator.  
supply gas pressure is over desired pressure  
pilot gas pressure is more than +/- .3 inch  
W.C. from desired  
replace the control valve.  
manifold gas pressure is more than +/- .3 inch replace the control valve.  
W.C. from desired  
Additional considerations when pilot or main burner flames are too large or too small:  
Incorrect orifice  
Dirt in orifice or gas supply tubing  
11  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas - continued  
Sooting causes:  
If …  
… then  
the burner is clean but the chamber and/or flue check for lack of supply air.  
are sooted  
the main burner, chamber and flue are sooted check the following:  
incorrect orifice  
excessive gas pressure  
loose main burner  
cross threaded orifice  
gas control valve gas seepage  
loose gas connection in burner assembly.  
Electrical Testing  
This type of water heater has its own electrical  
generating system.  
When two dissimilar metals are joined together  
and this joint is heated, a small, electrical current  
will be produced. A thermocouple uses this  
science.  
TO GROUND  
Thermocouple output test  
Procedures/Conditions:  
Meter set for DC millivolt testing  
Test from lower ECO (emergency cut off or energy cut off) solder joint to ground.  
Note: If pilot will not stay lit, manually hold the top knob down in the pilot position. This allows  
gas to flow to the pilot. Light the pilot and continue to hold this knob down while conducting the  
test.  
If …  
… then  
reading test of at least 13 mV is not present  
check that flame contacts end of  
thermocouple  
replace thermocouple.  
reading test of at least 13 mV is present  
continue to next test.  
12  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas - continued  
Electrical Testing– continued  
Millivolt dropout test through copper magnet winding and ECO (Emergency Cut Off)  
Procedure: Move meter probe to upper ECO solder joint and ground  
If …  
… then  
replace the control valve.  
replace the control valve.  
reading of at least 10 mV is not present  
reading of more than 10 mV is present but,  
gas to the pilot shuts off each time knob is  
released  
Safety drop out test –  
The safety gas shutoff should interrupt gas through  
the valve when mV current drops to 1-3 mV.  
Procedures:  
Meter still connected to upper ECO solder joint and  
ground.  
Turn Top Knob to “off” position  
Millivolt output will decrease as thermocouple cools  
TO GROUND  
If…  
… then  
replace the control valve.  
internal safety does not activate between 1  
and 3 mV (you will hear a “click” inside the  
valve)  
*internal safety does activate between 1 and valve is within tolerance and will interrupt gas  
3 mV flow if pilot looses heat or ECO opens.  
*Note: A “click” sound should be heard from the valve as the main gas interrupter snaps up to  
the “closed” position.  
Condensation  
Flue gas products contain moisture. If these flue gas products are cooled to their “dew point”,  
they become visible moisture – condensation.  
Flue gas may become cooled by:  
Cold supply air temperatures  
Cool surfaces – generally, if tank water temperatures drop below 110°F, the flue pipe  
surface and/or bottom tank head will be cool enough to cause condensation.  
Increased combustion efficiency – higher thermal efficiency means that an increased  
amount of heat is transferring from the flue gas into the water. If you transfer  
(approximately) 87.5%, or more, the moisture in the flue gas will condense.  
13  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas – continued  
Condensation is a mild acid – it will corrode steel  
Condensation is usually noted when:  
water dripping is heard (only) while the main burner is on,  
there is “water” around the heater just after the heater has been operating,  
there are small, black or red granules on the main burner or top of the heater or  
corroded jacket or vent piping is noted.  
If …  
… then  
any of the above conditions exist  
raise the supply air temperature or  
increase stored water temperature or  
increase the size of the tank  
You would not wish to lower combustion  
efficiency – this would waste gas. Use  
materials (stainless steel, PVC etc.) that  
will not be affected by the condensation  
Suggested Multiple Heater Water Piping Required For  
Proper Operation of Top Connect Models  
Installed in accordance with local codes.  
TEMPERATURE/PRESSURE RELIEF VALVES  
14  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
Residential Gas – continued  
Exhaust Venting Notes  
Follow current National Fuel Gas Code requirements for proper installation.  
“D” – Typically, same or larger diameter as Draft  
Hood outlet  
“L” – Horizontal piping slopes upward ¼” per foot  
from heater to chimney or vertical vent  
Length of horizontal not more than 75% of “H”  
“H” – Not less than 5 feet  
Maximize vertical distance to first elbow  
FLAMMABLE VAPOR IGNITION RESISTANT (FVIR) DESIGN  
This section will address the changes brought about by the introduction of FVIR compliant  
products. Other than items mentioned here, the construction, installation, and service will  
remain the same as discussed in the primary handbook.  
The FVIR acronym stands for "Flammable Vapor Ignition Resistant." The State products are  
based on "Corderite Combustion Containment" known as “C3 Technology™” . The C3  
Technology design features a sealed (from non designated air intake openings) combustion  
chamber and a "flame arrestor" component.  
This class of residential gas water heaters meet the new ANSI standards and testing protocols  
(ANSI Z21.10.1) established to deal with the accidental or unintended ignition of flammable  
vapors, such as those emitted by gasoline. Virtually all gas-fired, atmospherically vented,  
residential water heaters manufactured in the United States with BTU ratings of 75,000 or less  
are required to meet this new ANSI standard effective July 1,2003. The current implementation  
schedule for C3 TECHNOLOGY compliant residential gas-fired products is shown in the  
following table. These dates are subject to change.  
15  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
IMPLEMENTATION ANTICIPATED  
CLASS OF PRODUCTS  
CATEGORY  
INTRODUCTION  
INCLUDED IN THIS CATEGORY  
July 1, 2003  
30, 40, and 50 gallon atmospheric vented.  
Phase I  
(July 1, 2004* Can.) (Manufactured housing models are excluded.)  
30, 40, and 50 gallon power-vented models.  
January 1, 2005*  
Phase II  
Phase III  
(Manufactured housing models are excluded.)  
All other gas-fired models with inputs of 75,000 BTU  
July 1, 2005*  
or less.  
* Subject to change. This supplement addresses the July1, 2003 compliant products.  
In addition to the standard water heater design discussed in the main service handbook, the C3  
Technology design also includes:  
A LDO (Lint Dust and Oil) screen over the combustion air intake  
A Flame Arrestor  
A combustion chamber Thermal Cut Off (TCO) limit  
An additional tool for these products might be a vacuum cleaner with both blowing and  
vacuuming capabilities. Also include the long, narrow crevice accessory.  
LDO SCREEN (LINT, DUST, OIL) SCREEN(S)  
An easy to clean screen designed to minimize lint, dust and oil based contaminants from being  
drawn into the “Flame Arrestor” along with make up – combustion - air. There may be one or  
two of these screens. The LDO screen must be installed with the arrows on the right and left  
side facing up to function properly. (The arrows are located on two mounting tabs on each side  
of the screen).  
Service:  
Inspect the LDO screen(s) regularly. Clean or wash as necessary.  
Pulling the tab located in the middle of the screen will remove the screen. Reinstall the clean  
screen by inserting the end tabs into the jack with the arrows pointing up.  
Possible Service issues associated with a blocked screen:  
Poor combustion – yellow flame, possible sooting  
Pilot outage resulting from a lack of oxygen  
Pilot outage resulting from to increased combustion chamber temperature below the  
main burner. This may open the automatic reset, thermal cut off switch (TCO).  
16  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
FLAME ARRESTOR  
Made from Corderite, a fireproof ceramic material, the flame arrestor is built into the base of  
the water heater. Combustion air is drawn in through the LDO screen (s). After entering the  
bottom area of the water heater, this air passes up through the small ports of the flame  
arrestor and into the combustion chamber.  
In the event flammable vapors are introduced accidentally into the combustion chamber, the  
flame arrestor is designed so any flames burn off the top surface of the arrestor and cannot  
escape down through the arrestor. The arrestor works somewhat like a check valve.  
Service:  
Inspect the bottom ports of the flame arrestor by removing the LDO screen (s) and using  
a mirror and flashlight. Clean the ports if necessary by vacuuming the bottom of the  
arrestor.  
Inspect the top of the flame arrestor by removing the inner door and burner assembly.  
Lift the heat shield located on the bottom of the chamber. Inspect with the mirror and  
flashlight. Vacuum or blow down any blocking material. If you blow down through the  
ports, be certain to also vacuum below the arrestor.  
17  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
If there has been a flammable vapor ignition, a qualified service agent needs to inspect  
the arrestor for cracks. The arrestor is not a replaceable part – the heater would need to  
be replaced.  
Possible service issues associated with the flame arrestor.  
Poor combustion – yellow flame, sooting, possible carbon monoxide production.  
Pilot outage due to lack of oxygen. Continued pilot outage or finding that the LDO  
screen(s) is heavily blocked would warrant inspection of the flame arrestor.  
Pilot outage due to increased combustion chamber temperatures below the main burner.  
This may open the automatic reset, thermal cut off switch (TCO).  
The flame arrestor having contained a flammable vapor ignition. The TCO will open and  
the chamber and arrestor should be inspected by a qualified service agent.  
COMBUSTION CHAMBER TEMPERATURE SENSOR  
The C3 Technology water heaters will come equipped with a thermal cutoff (TCO)  
device that is integral with the thermocouple. Temperature cutoff points range from  
160°C to 200°C depending on model. The TCO is an automatic reset thermal switch.  
When activated it will open the thermocouple circuit and shut off the main and pilot  
burner gas flow. The pilot would have to be relit after the TCO has had sufficient time to  
cool down (sensor is below 120 degrees F).  
In addition to printing the temperature setting on the TCO, a label located near the gas  
valve attachment end of the thermocouple notes the temperature setting of the TCO.  
The TCO performs two primary functions:  
In the event of flammable vapor ignition inside the combustion chamber, it  
senses the corresponding increase in temperature and shuts off gas flow to the  
main and pilot burners.  
If excessive temperatures inside the combustion chamber indicate poor  
combustion due to a clogged LDO screen or inadequate air for combustion, the  
TCO will shut off gas flow to the main and pilot burners.  
18  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
SERVICE:  
There is no routine service associated with the TCO. The standard thermocouple millivolt output  
checks described in this service handbook still apply. Millivolt readings indicate that the TCO is  
closed. An open TCO (within a cool chamber) would indicate that the assembly must be  
replaced.  
The TCO is an integral part of the thermocouple and not replaceable as a separate item. A pilot  
burner assembly must be reinstalled. On repeated calls of no hot water or pilot outage, a  
clogged/dirty LDO screen might be the cause and should be checked. Keep in mind this TCO  
will shut off the pilot and main burner when activated.  
With the different cutoff temperature set-points of TCO devices for different model water  
heaters, it is important that the correct part is used when replacement of the pilot burner  
assembly is necessary.  
Possible service issues associated with the Thermal Cut Off switch being opened:  
Pilot outage due to increased combustion chamber temperatures below the main burner.  
This may open the automatic reset, thermal cut off switch (TCO).  
The flame arrestor having contained a flammable vapor ignition. The TCO will open and  
the chamber and arrestor should be inspected by a qualified service agent.  
ONE PIECE PILOT BURNER ASSEMBLY  
C3 Technology models feature a "one piece" pilot burner assembly. There are five main  
components that make up this pilot assembly:  
1. Thermocouple with integral Thermal Cut Off switch (TCO).  
2. Pilot burner w/orifice and tubing  
3. Piezo igniter cable  
4. Pilot assembly seal/grommet (orange).  
5. An inner door gasket (white) will also be included.  
19  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
To replace a pilot assembly:  
Turn off the gas supply  
Disconnect the piezo cable from the piezo button (connection near gas control  
valve).  
1.  
2.  
3.  
Disconnect the pilot tubing, thermocouple and main burner tube from the bottom of  
the gas control valve.  
4.  
5.  
6.  
7.  
8.  
Remove (2) 3/8 inch nuts securing the inner door.  
Remove the entire burner assembly.  
Remove screw securing pilot burner assembly to pilot mounting bracket.  
Remove pilot assembly - with orange gasket – from the back side of the inner door.  
Reinsert new pilot assembly into back side of inner door. Wetting the orange gasket  
may help in securing the gasket into place.  
9.  
Reattach the new pilot assembly to the pilot mounting bracket.  
10.  
Inspect/replace the white, inner door gasket before making the connections to the  
bottom of the gas control valve.  
11.  
12.  
13.  
14.  
Reattach the piezo cable to the piezo button.  
Remount the inner door.  
Follow the pilot lighting instructions including gas and gasket leak checks.  
Install the outer door.  
SEALED COMBUSTION CHAMBER  
The combustion chamber is factory sealed around the flame arrestor and the upper and lower  
perimeter of the chamber. Access for service is provided through an inner door as with current  
product. However, this inner door is now sealed with; a door gasket, a pilot assembly grommet  
type seal, and a main burner tube boot/sleeve type seal.  
20  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
The three seals on the inner door should be checked every time any service is performed. The  
sight glass should be checked to insure it is not damaged or missing. The pilot tube and  
thermocouple routing should be straight (not bent at an angle close to the surface of the seal) as  
it passes through the pilot assembly seal.  
A "five point inner door seal inspection" is outlined below:  
Five point inner door seal inspection:  
1. Inner door gasket condition and fit.  
2. Main burner tube seal condition and fit.  
3. Pilot assembly seal condition and fit.  
4. Sight glass, condition; present, not broken or cracked.  
5. Straight routing of the thermocouple and pilot burner tube through the pilot assembly  
seal.  
These are all critical to maintaining the C3 TECHNOLOGY integrity of the combustion  
chamber.  
21  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
PIEZO IGNITER  
C3 TECHNOLOGY models will feature a Piezo igniter to light the pilot burner. The push button  
switch will be located on the top of the gas control valve. There will be a plug connector  
between the push button and the igniter wire which is part of the pilot burner assembly.  
Important Service Reminder  
Any time service is performed on C3 TECHNOLOGY product the Five Point Inner Door Seal  
Inspection outlined in the Sealed Combustion Chamber section should be performed and the  
LDO Screen (s) should be inspected for proper installation (arrows up) and cleaned before  
leaving.  
Other features  
All C3 TECHNOLOGY models will feature Green Choice by having a low NOx (nitrous oxide)  
burner which meets SCAQMD rule 1121. All C3 TECHNOLOGY models will have a brass drain  
valve standard.  
See the “Technical Bulletins Section “ of this manual for explanations of:  
Water Hammer  
Mineral Buildup  
Aluminum Hydroxide  
Condensation  
Discolored Water  
Smelly Water  
Chlorination Process  
Lack of hot water  
Thermal Expansion  
Temperature and Pressure Relief Valve Operation  
Parts Replacement – The parts on these models may change due to improvements/changes  
in the products. To order the current, correct replacement part for your model gas water heater,  
you must know the model number and (complete) serial number of your water heater. This  
information will be located on a black and white label, on the front of your water heater. This  
label will also display a star within a circle (the CSA symbol).  
To order parts, contact your local State Water Heater Contractor or Distributor,  
phone State parts at 800-821-2018 or contact State on Web site  
“www.statewaterheaters.com”  
22  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
WHY WATER HEATER TANKS LEAK  
WHAT  
Water  
Pressure  
WHY  
PREVENTION  
A Temperature and Pressure Relief  
Valve limits pressure to a  
maximum.  
Adding a Thermal Expansion Tank  
limits pressure to near supply water  
pressure.  
Water expands when it is heated  
(Thermal Expansion). Water  
cannot be compressed.  
Excessive Pressure in the tank  
causes failure of joints, welds or  
gaskets.  
Condensation) Products of combustion contain  
moisture. As the combustion  
products cool the moisture  
becomes liquid – carbonic acid.  
The acid attacks the metal.  
Higher efficiency water heaters  
have cooler gases.  
Install a water heater with capacity  
to minimize significant stored water  
temperature drop during usage.  
Store water at a higher temperature  
– install a mixing valve to reduce  
danger of scalding.  
Recommended water storage  
temperatures create cooler  
surfaces.  
Contaminated Bleaches, floor waxes,  
Supply the heater with clean air.  
“Direct Vent” water heaters use air  
from outside of the building for  
Air  
detergents, salt and many other  
household products contain  
chemicals which, when drawn into combustion.  
contact with a flame (a gas water  
heater uses 12 cubic feet of air for  
each 1000 BTU of heat  
generated). When these  
chemical vapors or dusts come  
into contact with a flame or  
electrical contact, various acids  
form. These acids attack the  
metal.  
Soft Water  
Soft water minimizes mineral  
buildup within the tank. Minimal  
minerals maintain the water  
heater at high efficiency but may  
also expose interior surfaces to  
corrosion. Mineral buildup in  
some heaters prevents them  
leaking while greatly reducing  
efficiency.  
A metal “Anode” rod within the tank  
helps to prevent internal corrosion.  
Maintain the self sacrificing “anode”  
rod by inspecting the rod annually  
and replacing when large “gouges”  
appear in its surface.  
23  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
WHY WATER HEATER TANKS LEAK -  
WATER CONDITIONS  
Continued  
WHAT  
WHY  
PREVENTION  
“Hard” Water  
“Hard” water contains minerals.  
As water is heated the minerals  
separate from the water and  
attach to hot surfaces within the  
tank. In gas water heaters, these  
minerals “insulate” the heat  
transfer surfaces conducting heat  
from the burner through to the  
water. These surfaces become  
hotter than if they were clean.  
Hotter surfaces mean more  
expansion and contraction of the  
metal as the burner cycles on and  
off. The metal or weld joints  
crack.  
“Flush” the sand from the tank every 6  
months.  
Delime the tank interior yearly.  
Install a water softener in hard water  
areas. These should be adjusted  
according to manufacturer’s  
recommendations, typically for 5 grains  
hardness.  
Water  
Temperature  
Begin with a water heater setting of  
120°F (49°C) and increase only as  
necessary.  
Purchasing a proper sized tank will  
minimize burner or element operation  
when only small quantities of hot water  
are used.  
Water stored at 160°F (72 °C)  
may be twice as corrosive as  
water stored at 140°F (60°C)  
Each time the burner or elements  
cycle on and off, a small amount  
of metal expansion and  
contraction take place. As  
bending a piece of wire back and  
forth will break the wire, this  
expansion and contraction will  
eventually crack tank joints or  
welds.  
Usage  
24  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 11  
WATER HAMMER  
Water hammer is the destructive forces, pounding noises and vibration in a piping  
GENERAL  
system when water flowing through a pipeline is stopped abruptly. When water  
hammer occurs, a high intensity pressure wave travels back through the piping  
system until it reaches a point of some relief. The shock wave will then surge back  
and forth between the point of relief and the point of stoppage until the destructive  
energy is dissipated in the piping system. The violent action accounts for “banging”,  
“thumping”, and/or intense vibration in the pipe line. Although noise is generally  
associated with the occurrence of water hammer, it can occur without audible sound  
or noise. Quick closure always causes some degree of shock with or without noise.  
The common cause of water hammer is single lever faucets (sinks/lavatories) or  
automatic solenoid valves (dishwashers, washing machines, etc.). The speed of the  
valve closure time is directly related to the intensity of the surge pressure.  
The damage from water hammer can manifest itself in a number of ways. The most  
common are:  
EFFECTS  
Expanded Tank Shell - This can be demonstrated by measuring the circumference at  
various locations along the shell. Pressures in excess of the maximum design working  
pressure can cause permanent deformation of the shell.  
Collapsed Flue Tube - This will choke off the ability to vent the products of combustion  
causing the flame and/or combustion to spill out from the combustion chamber. Often  
this will occur where thinning of the flue tube walls has occurred due to contamination  
of the combustion air or because of excessive condensation.  
Inverted or Deformed Tank Heads - Often this accompanies collapsed flues, but one  
or both heads can be deformed.  
The only effective means of control is to install water hammer arrestors. These  
devices have diaphragms, which separate an air chamber from the water in the piping  
system. As the shock wave reaches this device, the air chamber absorbs the shock.  
Arrestors should be located as close as possible to the source of the shock wave.  
THE FIX  
NOTES  
Since water hammer exposes the equipment to pressures in excess of its design  
limits, failures caused by water hammer are not eligible for warranty consideration.  
25  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 13  
MINERAL BUILD-UP  
Rumbling  
Crackling  
Popping  
SYMPTOMS  
CAUSE  
With the advent of high input and larger storage tanks in both commercial and  
residential heaters, deliming has become a necessity of modern maintenance.  
Lime (CaCO3), is the most notable factor when discussing water hardness.  
Lime is present in every water system to some degree across the entire  
United States. Since lime is inversely soluble [the more you heat, the more  
lime comes out], higher usage, excessive hardness, and increased heating  
surface can lead to a high incidence of “limed-up” heaters.  
Symptoms often include a popping of water trapped under lime deposits or  
the sizzling of water trapped next to elements, boiling it to steam.  
Treatment of a “limed-up“ heater is relatively simple. Since CaCO3 is a base,  
the easiest way to dissolve it so it can be flushed from the heater is with an  
acid. The most commonly used is phosphoric acid at a food-grade level.  
THE FIX  
Two common treatments available from State are Mag-Erad® and Un-Lime®.  
Any well-stocked plumbing supply house should have a deliming solution  
available.  
The directions on the product should be followed explicitly.  
For additional information and instructions in deliming water heaters and  
boilers, please refer to the following pamphlets available from State:  
NOTES  
Why? When & How: To Remove Water Scale from Tank Type Water  
Heaters  
The Mag-Erad® Method of Cleaning Gas Fired Water Heaters  
Up-N-DownTransfer Kit  
All About Deliming Coil Type Water Heaters  
26  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 14  
ALUMINUM HYDROXIDE  
“Crackling”, “gurgling”, or “popping” noises from new water heaters (installed less than  
six months).  
SYMPTOMS  
In a few isolated parts of the United States where the water supply has a relatively high pH (8+),  
CAUSE  
water conditions will react with the aluminum anode to form excessive amounts of aluminum  
hydroxide on the anode and in the bottom of the tank. Aluminum hydroxide looks like “jelly  
beads” or a green, blue or gray gel like substance in the heater drain or at faucet aerators.  
This procedure should only be performed by someone with abilities equal to a licensed  
tradesman. Aluminum hydroxide can be removed by using one of the methods outlined.  
THE FIX  
If tank is new with no lime build-up to any degree:  
1
2
3
4
Turn off the heater.  
Remove the anode.  
Flush the tank thoroughly with water.  
Replace the aluminum anode (identifiable by smooth surface on plug) with magnesium  
anode (identifiable by weld bead on plug).  
If the tank is new with lime build-up to any degree:  
1
2
3
4
Turn off the heater.  
Drain the heater.  
Remove the anode.  
Add UN-LIME to the tank.  
20-40 gallon models (use 3 gallons of UN-LIME)  
41-65 gallon models (use 5 gallons of UN-LIME)  
66-100 gallon models (use 7 gallons of UN-LIME)  
(On electric models, be certain the lower element is immersed in solution.)  
5
Heat the UN-LIME to a temperature between 140°F to 160°F.  
GAS - Heat for 7 to 10 minutes.  
6
7
8
9
Shut off the water heater.  
Allow the heated UN-LIME to stand for up to 12 minutes.  
Drain and flush the tank. Caution: UN-LIME will still be hot.  
Replace the original aluminum anode with a magnesium anode.  
10 Fill the system with water.  
11 Turn heater fuel “ON”.  
NOTE  
Since aluminum hydroxide is a product of a chemical reaction dependent on the water condition,  
any treatment is not considered warranty related.  
27  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 21  
DISCOLORED WATER  
Rusty, brown, black, or yellow water appearing in the hot water.  
SYMPTOMS  
Complaints of discolored water are commonly blamed on water heaters and  
CAUSE  
storage tanks, but in fact, it is a rare occurrence for today’s high quality glass  
lined tanks to have a lining failure significant enough to allow water to contact  
enough bare metal to discolor the contents of even a small tank.  
The most common cause of “rusty” water is a non-toxic iron reducing bacteria,  
scientifically termed Crenothrix, Leptothrix, and Gallionella. Iron bacteria is  
commonly found in soil, water wells, water treatment plants and water  
distribution piping systems where soluble iron exceeds 0.2 ppm, higher levels  
make conditions even more favorable. Soluble iron in the water provides food  
for the bacteria. Rusty discolored water is the end result of the bacteria feeding  
process. Water heaters and storage tanks usually require new anode rods as  
presence of iron bacteria contributes to premature anode failure.  
The requirements for the bacteria to thrive are:  
Elevated level of iron and manganese in the water  
Water with little or no dissolved oxygen  
Temperatures below 138°F  
Items that can increase the potential for this bacteria are:  
Water softeners  
Well water  
Long periods of no water movement  
The simplest treatment available is shock-chlorination of the system. This is a  
surface treatment, and often requires repeated trials in heavily infected  
systems. The chlorination of a system requires that you follow each step  
explicitly to avoid an un-treated portion of the piping system from reinfecting  
another part. See Bulletin 23 for the chlorination procedure.  
TREATMENT  
Since rusty water is caused by a bacteria presence and is not caused by the  
water heater, any treatment would not be considered warranty related.  
NOTE  
28  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 22  
SMELLY WATER  
The most common cause of “smelly water” is a non-toxic sulfate reducing  
CAUSE  
bacteria, scientifically termed Divibrio Sulfurcans. This bacterium often enters  
the water system through construction or a break in ground piping. The  
bacteria create the energy it needs to survive by converting sulfate (SO4) to  
hydrogen sulfide (H2S) gas you smell in the water.  
Hydrogen sulfide gas is distinctive because of its rotten egg-like stench. Its  
presence can severely affect the taste as well as the odor of the water.  
Occasionally these bacteria can be accompanied by black deposits, the result  
of pipe and fitting corrosion. In extremely high concentrations, hydrogen  
sulfide gas can be toxic though the gas is detectable long before harmful  
levels are reached.  
The requirements for the bacteria to thrive are: a) an elevated level of sulfur in  
the water, b) activated hydrogen from cathodic reactions within the tank, c)  
water with little or no dissolved oxygen, d) and temperatures below 138°F.  
Items that can increase the potential for these bacteria are: a) water  
softeners, b) well water, c) and long periods of no water movement.  
Other factors that may contribute to smelly water:  
Chlorides of Magnesium and Calcium leave a bitter taste.  
Chloride of Sodium produces a salty taste.  
Sulfates (50 ppm) give a medicinal taste.  
Carbon Dioxide in low pH water gives fizzy water.  
Iron and tannic waters also give a bad taste and odor.  
The simplest treatment available is the shock-chlorination of the system. This  
is a surface treatment, and often requires repeated trials in heavily infected  
systems. The chlorination of a system requires that you follow each step  
explicitly to avoid an un-treated portion of the piping system from reinfecting  
another part. See Bulletin 23 for the chlorination procedure. Longer lasting  
solutions include chlorination or aeration of the water supply.  
TREATMENT  
Since smelly water is caused by a bacteria presence and is not caused by the  
water heater, any treatment would not be considered warranty related.  
NOTE  
29  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 23  
CHLORINATION PROCEDURE  
The chlorination procedure is used to eliminate various bacteria that  
accumulate and grow in water heaters. These bacteria often cause odorous  
or discolored water conditions.  
CAUSE  
PROCEDURE  
Please read the steps of the chlorination procedure prior to beginning. If you  
feel uncomfortable performing any of these steps, contact a service person to  
perform this procedure for you.  
STEP 1  
STEP 2  
STEP 3  
STEP 4  
STEP 5  
STEP 6  
Turn off the gas supply to the tank.  
Turn off the cold water supply valve to the tank.  
Open a nearby hot water faucet to relieve the vacuum.  
Drain all the water from the tank (a water-hose may be needed).  
Remove the anode rod(s), and close the drain valve.  
Using a funnel in the anode opening add one gallon of household chlorine  
bleach (e.g. Clorox or Purex) for every 25 gallons of tank capacity.  
Reinstall anode rod(s) after inspecting and replacing as needed.  
Open cold water supply valve and refill the system. Then draw the water to  
every hot water fixture, until the smell of chlorine is detected. Operate dish  
and clothes washers until a noticeable amount of the chlorine is detected as  
well. All hot water lines must receive treatment.  
STEP 7  
STEP 8  
STEP 9  
STEP 10  
Leave the chlorine solution undisturbed for one hour or more.  
After the contact time has elapsed, drain the tank according to steps #2, #3, &  
#4.  
STEP 11  
Close the drain valve and refill the tank. Allow the tank to sit for 15 minutes.  
Repeat steps #2, #3, and #4. Continue to flush the tank if the water is  
discolored or contains a chlorine odor.  
STEP 12  
STEP 13  
Close the drain valve and refill the tank. Flush all chlorine from the piping by  
opening every hot water outlet/ appliance.  
Return hot water heating system to service by following the recommended  
start-up procedure posted on the unit or in the manual.  
30  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 35  
NOT ENOUGH HOT WATER - GAS  
Not enough hot water complaints are becoming more frequent in the water heater  
CAUSE  
industry. This increase was triggered when changes required by our regulatory  
agencies were implemented. For example, heaters are now factory preset at a  
lower temperature and inlet tubes have been shortened. While lower temperatures  
settings reduce the burn rate, and shorter dip tubes guard against stacking, both  
affect the amount of hot water a water heater can supply. The following test will  
help determine if a water heater is supplying the intended amount of hot water and  
will help pinpoint any problems that exist.  
Please read all the steps of the test prior to beginning. If you feel uncomfortable  
performing any of these steps, contact a service person to conduct this test for you.  
TEST  
STEP 1  
At the faucet nearest to the water heater, time (in seconds) how long it takes to fill a  
1 gallon bucket (flow rate).  
Gallon per minute (gpm) = 60 seconds / seconds to fill a 1 gallon bucket  
If the bucket fills in: 10 sec = 6 gpm  
12 sec = 5 gpm  
15 sec = 4 gpm  
20 sec = 3 gpm  
24 sec = 2.5 gpm  
STEP 2  
STEP 3  
STEP 4  
STEP 5  
STEP 6  
STEP 7  
Turn thermostat dial on the water heater so the arrow points to “A” position.  
Run about 15 gallons of hot water from the nearest faucet. Shut water off.  
Water heater should complete heating 15 gallons in approximately 20-35 minutes.  
At a nearby faucet using a candy thermometer, measure the hot water temperature.  
The temperature should fall between 120°F to 140°F.  
Continue running the hot water until 60% of the tank capacity is depleted:  
CAPACITY  
30 gallons  
40 gallons  
50 gallons  
75 gallons  
100 gallons  
DEPLETE  
18 gallons  
24 gallons  
30 gallons  
45 gallons  
60 gallons  
STEP 8  
STEP 9  
At the same faucet using a candy thermometer, measure the water temperature.  
The temperature should be about 30°F below the temperature in step 6.  
Step 6 - if the temperature was not within range, check the thermostat.  
Step 9 - if more than 30 °F was lost, check the dip tube.  
THE FIX  
31  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 45  
THERMAL EXPANSION  
Effects are only noticeable after hot water use followed by periods of no water use.  
Relief valve drips during any recovery cycle when no hot or cold water is used.  
Hot water pipes creak while heater is recovering and all valves are closed.  
Tanks or other components of the water supply system fail prematurely.  
A metallic creaking noise might actually be heard in the location of the heater as the  
pressure is relieved and the stretched tank returns to a natural shape.  
Faucets drips during any recovery cycle when no hot or cold water is used.  
SYMPTOMS  
Water surges when a valve is first open and then pressure drops.  
The water in a water heating system expands when it is heated and has a greater  
volume. Since water will not compress (like air), system designers must include  
provisions for thermal expansion. (Water in a closed tank at 50 psi, when heated just  
10 degrees, will reach a pressure of 250 psi).  
CAUSE  
Many water supply systems have check valves at the water meter to prevent any  
possible contamination of the public water supply by the accidental back-flow of  
contaminated water into the supply mains. These check valves are often required by  
code, and some cities are even installing the check valves. They serve a useful  
purpose. Do not remove them!  
The use of pressure reducing valves (PRV) is another cause. PRVs are designed to  
conserve water and prolong fixture life. Many PRVs also act as very effective check  
valves. Again, do not remove them!  
Water softeners in the system may also act as back-flow preventers.  
Follow these easy steps to diagnose thermal expansion:  
Turn the heater thermostat all the way down, and install a water pressure gauge  
with dead hand (part #4798) on the drain valve. Open the drain valve, so the gauge  
reads system pressure.  
TEST  
Open a hot water tap and allow 15% to 20% of the tanks volume to run out. Shut  
off the drain valve and make sure that no other fixture in the system, hot or cold, is  
open. Make sure that outside fixtures, if they are on the same system, are turned  
off too. Any water leaks or use will make the test meaningless.  
Check the water pressure gauge, and turn the pointer so it lines up with the  
pressure indicating needle. Turn the thermostat back up to its normal position, so  
the heater cycles on. Watch the pressure gauge.  
If the system is closed, the pressure will start to climb steadily and rapidly. A small  
amount of thermal expansion control may be built into the system because of  
trapped air pockets or a water hammer arrestor. In that case the pressure will  
increase slightly, hold steady for a short time and then rapidly increase. The  
temperature and pressure relief valve (T&P) or PRV should open and release water  
once the pressure reaches the maximum setting on the valve. The valve will close  
once the pressure falls below the pressure setting of the valve.  
32  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
The ideal fix involves the use of a pressure reducing valve if supply pressures are  
THE FIX  
above 60 to 70 psi, and a properly sized expansion tank. The PRV reduces supply  
pressures to 40 to 60 psi allowing an economically priced and sized expansion tank to  
be used. The PRV also offers the benefit of saving water and prolonging the life of  
water flow valves. The PRV is not required if the system already has one or if high  
supply pressures are desired.  
The PRV is installed between the check valve and the water heating system. The  
expansion tank is installed between the PRV and the water heating system. Follow the  
manufacturers’ instructions for installing the expansion tank.  
Run the thermal expansion check again. The pressure should increase only slightly  
then hold steady throughout the recovery cycle. The expanded water is flowing back  
from the heater and into the pressurized storage bladder of the expansion tank. Air  
pressure will force this water out of the expansion tank into the supply once usage  
resumes.  
DO NOT DEPEND ON THE T&P VALVE TO HANDLE THERMAL EXPANSION! The  
T&P valve, according to the makers of those valves, was designed as an emergency  
relief device only. The T&P could be subject to reduced effectiveness or failure.  
FIGURE  
Thermal expansion of water, if not compensated for in system design, will lead to the  
early failure of components. These failures are not covered by the manufacturer’s  
warranty, so it is extremely important that everyone be aware of the causes, symptoms  
and solutions to thermal expansion in a closed water heating system.  
WARNING  
33  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER  
SERVICE HANDBOOK  
TECHNICAL BULLETIN - 52  
LEAKING TEMPERATURE AND PRESSURE RELIEF VALVE  
Water seeping around the relief valve tank connection  
SYMPTOMS  
GENERAL  
Leakage at the threaded portion of the relief valve connection  
Intermittent weeping and/or dribbling from the relief valve  
Large volume of hot water sporadically discharged from the relief valve  
The temperature and pressure relief valve (T & P) is a safety device limiting temperature and  
pressure levels in a water heater. Each T & P has both a temperature and pressure rating.  
Normally, the temperature and pressure relief valve will have a temperature rating for 210°F. A  
probe (part of the relief valve) extends into the tank measuring the stored water temperature.  
This probe must be within the top six inches of the water heater. However, if the water heater’s  
thermostat malfunctions, higher than normal water temperatures could be produced. Once the  
probe senses a temperature exceeding its temperature rating, the relief valve will open to full  
capacity releasing “very hot” water until the temperature is below its reset temperature.  
The pressure rating on the relief valve should be the same or less than the certified working  
pressure of the tank (generally 150 psi) and be below the lowest pressure rating of any system  
components. It is not acceptable to install a relief valve that exceeds the maximum working  
pressure of the water heater. Once the pressure in the tank reaches the valve’s pressure rating,  
it will slightly open relieving the pressure. Relieving of pressure can be noted as “dribbling” or  
“weeping” water from the relief valve.  
If an incorrectly sized temperature and pressure relief valve is installed, the warranty will be  
void.  
Seeping at the spud of the water heater - Spuds are welded to the tank and are not  
repairable. The heater should be replaced.  
Leakage at the threaded relief valve connection - Remove relief valve and reseal  
connection.  
Intermittent weeping and/or dribbling at the relief valve - The relief valve relieves water  
slowly when actuating on pressure. A closed system can cause pressure to increase in the  
system. This condition is called thermal expansion. For additional information regarding  
thermal expansion please see Bulletin 45.  
THE FIX  
Large volume of hot water sporadically discharged from the relief valve - The relief valve  
relieves water quickly when actuating on temperature. The only cause of this problem is a  
malfunctioning thermostat.  
34  
State Water Heater  
© 2004  
Technical Training Department  
Ashland city, TN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To order additional copies of this Service Handbook and to view  
other service and presentation literature and CDs that are  
available from State Water Heaters:  
Telephone 1-800-821-2017, Fax number 800-644-9306 or visit our  
For additional information or assistance in servicing you’re  
State water heater, visit our web site or telephone the Technical  
Information Department at 1-800-365-0024  
This Service Handbook was prepared by the Technical Training Department,  
Ashland City, TN.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Servis Rhino Compact Loader 5211 User Manual
Shop Vac Vacuum Cleaner 14rt400a User Manual
Shure Microphone BETA 91A User Manual
SonicWALL Camera Accessories SRA 1200 4200 User Manual
Sony Projection Television KDF 37H1000 User Manual
Spirit Home Gym 350 User Manual
Sprint Nextel IP Phone 597E User Manual
Stamina Products Baby Gym 55 5686B User Manual
StarTechcom Switch SV221DD User Manual
State Industries Water Heater SSED 5 User Manual