Powerware Power Supply 8 10 kVA User Manual

User’s Guide  
UPS 8 – 10 kVA,  
230V 50/60 Hz output  
(1-phase input)  
&
UPS 8 – 15 kVA,  
230V 50/60 Hz output  
(3-phase input)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS 8 – 10 kVA, 230V 50/60 Hz output (1-phase input)  
UPS 8 – 15 kVA, 230V 50/60 Hz output (3-phase input)  
User’s Guide 1022403 revision B1  
Contents  
1. Safety instructions ................................................................................................................ 4  
Audience ..................................................................................................................................................... 4  
CE marking ................................................................................................................................................ 4  
User precautions ......................................................................................................................................... 4  
Environment............................................................................................................................................... 5  
Inquiries ..................................................................................................................................................... 5  
2. Mechanical installation ......................................................................................................... 6  
Delivery check ............................................................................................................................................ 6  
Unpacking and visual inspection................................................................................................................ 6  
3. Planning before installation .................................................................................................. 8  
4. Cabinet installation............................................................................................................... 9  
Mechanical bypass switch ........................................................................................................................... 9  
Transformer option ................................................................................................................................... 11  
External battery cabinet option ................................................................................................................ 12  
Battery racks ............................................................................................................................................. 12  
5. Electrical installation .......................................................................................................... 13  
Power cables and protective fuses ............................................................................................................ 14  
Wiring procedure...................................................................................................................................... 15  
External battery cabinet (EBC) installation procedure ............................................................................. 21  
SPM tie cabinet ......................................................................................................................................... 23  
6. Software and connectivity ................................................................................................... 26  
Communication cables ............................................................................................................................. 26  
Connection to the standard RS-232 port (X53) ....................................................................................... 26  
LanSafe software ................................................................................................................................... 27  
External control connections ................................................................................................................... 27  
Emergency Power Off (EPO) ................................................................................................................ 28  
Relay outputs ........................................................................................................................................ 29  
Programmable signal inputs ................................................................................................................. 29  
X-slot communication (option)................................................................................................................ 30  
SNMP/Web Module (optional) ............................................................................................................. 30  
AS400 Relay Module (optional) ........................................................................................................... 31  
Single Serial Port Module (optional) .................................................................................................... 31  
Modus/Jbus Module (optional) ............................................................................................................ 31  
7. User operations ................................................................................................................... 32  
Display functions ...................................................................................................................................... 32  
User Settings ............................................................................................................................................. 33  
Configuring user settings...................................................................................................................... 34  
Changing language ............................................................................................................................... 34  
Changing charging current ................................................................................................................... 34  
Using relay outputs ............................................................................................................................... 34  
Normal start-up ........................................................................................................................................ 35  
Battery start-up ......................................................................................................................................... 35  
Shutdown ................................................................................................................................................. 35  
8. Maintenance ........................................................................................................................ 36  
Scrapping .............................................................................................................................................. 36  
Regular service/intervals ........................................................................................................................... 36  
Batteries ................................................................................................................................................ 36  
Cooling fan ........................................................................................................................................... 37  
LED Indicators ......................................................................................................................................... 37  
Maintenance bypass switch (MBS) operation ........................................................................................... 37  
Turn UPS from normal mode to mechanical bypass ............................................................................. 38  
Turn UPS from mechanical bypass to normal mode ............................................................................. 39  
9. Dimensional drawings ........................................................................................................ 41  
10. Technical data .................................................................................................................... 43  
Standards .................................................................................................................................................. 43  
Environment............................................................................................................................................. 43  
Mechanical configuration ......................................................................................................................... 43  
Characteristics .......................................................................................................................................... 43  
AC input ................................................................................................................................................... 44  
DC circuit ................................................................................................................................................ 44  
AC output ................................................................................................................................................. 44  
11. Warranty ............................................................................................................................. 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Safety instructions  
The UPS operates with mains, battery or bypass power. It contains components that carry high  
currents and voltages. The properly installed enclosure is earthed and IP20 rated against  
electrical shock and foreign objects. However, only qualified personal is allowed to install and  
service the UPS.  
Warning!  
Operations inside the UPS must be performed by a service engineer from the  
manufacturer or from an agent authorised by the manufacturer.  
Do not ever service inside the UPS when mains power is applied or the UPS is in battery mode.  
Use the optional mechanical bypass if installed to the system. Remember to open battery  
breaker. Always ensure by measuring with a multi-meter that no dangerous voltages are  
present.  
Audience  
The intended audiences of this manual are people who plan the installation, install,  
commission, and use or service the UPS. The manual provides guidelines to check delivery,  
installing and commissioning of the UPS.  
The reader is expected to know the fundamentals of electricity, wiring, electrical components  
and electrical schematic symbols. This manual is written for a global reader.  
Note!  
Read the manual before operating or working on the UPS.  
CE marking  
The product has the CE marking in compliance with the following European directives:  
LV Directive (Safety)  
EMC Directive  
72/23/CEE and 93/68/CEE  
89/336/EEC and 93/68/EEC  
Declaration of conformity with UPS harmonised standards and directives EN 62040-1-1  
User precautions  
The only user operations permitted are:  
Start up and shut down of the UPS, excluding the commissioning start-up.  
Use of the LCD control panel and Maintenance Bypass Switch (MBS)  
Use of optional connectivity modules and their software  
The user must follow the precautions and only perform the described operations. Any deviations  
from the instructions could be dangerous to the user or cause accidental load loss.  
4
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning!  
The user is not permitted to open of any screws excluding connectivity plates and the  
MBS locking plate. Failure to recognise the electrical hazards could prove fatal.  
Environment  
The UPS must be installed according to the recommendations in this manual. Under no  
circumstances the UPS should be installed in an airtight room, in the presence of flammable  
gases, or in an environment exceeding the specification.  
Excessive amount of dust in the operating environment of UPS may cause damage or lead to  
malfunction. The UPS should be always protected from the outside weather and sunshine. The  
recommended operating temperature is from +15 to +25 Celsius degrees.  
Inquiries  
Address any inquiries about the UPS and battery cabinet to the local office or agent authorised  
by the manufacturer. Please quote the type code and the serial number of the equipment.  
1022403  
5
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Mechanical installation  
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with  
a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the  
equipment. Do not either stack the pallets because of high-energy batteries involved and the  
heavy weight  
Delivery check  
The UPS is delivered with the following items:  
Plastic bag containing:  
Quick Installation Guide, paper format, multilingual (coming later)  
Users Guide, paper format, multilingual  
Users Guide, CD-ROM format, multilingual (coming later)  
Residual voltage warning stickers  
Software Suite, CD-ROM format, English language  
RS-232 serial cable for the Software Suite  
Delivery documents  
Unpacking and visual inspection  
Check that there are no signs of shipping damages. The outside ’Tip&Tel’ indicator should be  
intact if the equipment has been transported in the upright position.  
Note!  
A claim for shipping damage must be filed immediately and the carrier must be  
informed within 7 days of receipt of the equipment. The packing materials should be  
stored for further investigation.  
Unpack the equipment by removing the packing and shipping materials. Make a visual  
inspection and check that the inside ‘Drop&Tell’ indicator is intact. Make sure that the floor  
surface is solid and suitable for the wheeling and heavy weight, twist the levelling feets of the  
unit to up position and remove the equipment from the pallet.  
Figure1. Instructions for removing the equipment from the pallet.  
6
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check the information on the type designation label of the equipment to verify that the unit is  
of the correct type. The type designation label includes ratings, a CE marking, a type code, a  
part number and a serial number. The serial number is important when making inquiries. It  
allows individual recognition of the equipment.  
Figure 2. Type designation label.  
1022403  
7
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Planning before installation  
The equipment must be installed in upright position. The equipment requires space to front  
and back to enable cooling airflow, service and maintenance. All cooling air enters at front and  
exits at unit rear. The required min. clearance from unit rear to an obstruction is 150 mm.  
Figure 3. Ventilation space around the equipment.  
It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed  
to keep the max. room temperature rise at desired level:  
Temperature rise of max. +5°C requires the airflow of 600 m3 per 1 kW of losses.  
Temperature rise of max. +10°C requires the airflow of 300 m3 per 1 kW of losses.  
An ambient temperature of 15 to 25 Celsius degrees is recommended to achieve a long life of  
the UPS and batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high  
ambient temperature, moisture and humidity.  
The floor material should be non-flammable and strong enough to support the heavy load. The  
UPS has (4) leveling feet that should be used when finalising the installation. The diameter of a  
single leveling foot is 1 inch (25.4 mm).  
Equipment  
UPS+1BAT  
UPS+2BAT  
UPS  
Weight  
155 kg  
265 kg  
50 kg  
Point  
Distributed  
738 kg/m2  
1262 kg/m2  
238 kg/m2  
310 kg/m2  
382 kg/m2  
929 kg/m2  
1476 kg/m2  
Note  
7.75 kg/cm2  
13.25 kg/cm2  
2.50 kg/cm2  
3.25 kg/cm2  
3.95 kg/cm2  
9.75 kg/cm2  
15.50 kg/cm2  
Batteries installed.  
Batteries installed.  
No Batteries.  
UPS+1BAT  
UPS+2BAT  
2BAT  
65 kg  
No Batteries installed.  
No Batteries installed.  
Batteries installed.  
Batteries installed.  
80 kg  
195 kg  
310 kg  
3BAT  
Table 4. The floor surface must tolerate these loading.  
8
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Cabinet installation  
The required distance for UPS units next to each other is ten millimetres. The same applies to  
the optional battery cabinets that should be installed next to the UPS cabinet.  
Figure 5. UPS and external battery cabinets.  
The UPS family has several alternative battery cabinets and configurations depending on the  
selected back-up time and quality of batteries.  
Mechanical bypass switch  
The mechanical bypass switch (MBS) shall be mounted in back of the UPS battery  
compartment. It can be ordered factory installed.  
Figure 6. Instructions for locating the mechanical bypass switch.  
Please fix the mechanical bypass switch (MBS) to the wall (din rail) or to the back of the UPS  
as shown below.  
1022403  
9
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 7. The mechanical bypass switch (MBS) when installed in the backside.  
Figure 8. 9155 MBS assembly  
10  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transformer option  
The galvanic isolation transformer can be ordered as factory installed. The transformer is an  
integral part of the UPS unit. Alternatively, the isolation transformer can be purchased as a  
separate item to upgrade your existing system.  
Figure 9. Transformer option can be ordered factory installed (integral) or separately.  
The overtemperature sensor cable is connected to the control input (X45 or X44) of the UPS,  
see the next drawing. In the factory installed systems this cable is ready-made for use.  
Figure 10. Wiring diagram of the UPS and the external transformer option.  
1022403  
11  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External battery cabinet option  
It’s recommended to install external battery cabinets next to the UPS unit. The external battery  
can be placed on either side of the UPS unit. Check before the installation that the battery  
voltage values in the type plate of the UPS and external battery cabinets are the same. The  
cables are delivered with the external battery cabinet. See External Battery Cabinet (EBC)  
installation procedure.  
Warning!  
The UPS contains high DC voltages. A qualified person must do the connections between  
the UPS and the external battery cabinet(s). The battery cabinet is connected electrically  
in parallel with the internal batteries of the UPS.  
Figure11. UPS and external battery cabinets.  
Battery racks  
External battery racks shall be sized to take the voltage drop in the cable into account. To  
obtain support and help contact the local office or agent authorised by the manufacturer.  
12  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Electrical installation  
The customer has to supply the wiring to connect the UPS to the local power source. The  
electrical installation procedure is described in the following text. The installation inspection  
and initial start up of the UPS and extra battery cabinet shall be carried out by a qualified  
engineer with UPS installation experience.  
Warning!  
Physical injury or death may follow, or damage may occur to the UPS, or the load  
equipment if these instructions are ignored.  
Figure 12. Location of the power terminals.  
1022403  
13  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The UPS unit has the following power connections:  
Three-phase (L1, L2, L3) and protective earth (PE) connection for the rectifier input  
or  
Single-phase (L1), Neutral (N) isolated connection point (bypass N is used in the rectifier)  
and protective earth (PE) connection for the rectifier input.  
Single-phase (L1), Neutral (N) and protective earth (PE) connection for the bypass input  
Single-phase (L1), Neutral (N) and protective earth (PE) connection for the load output  
Plus (+), minus (-) and protective earth (PE) connection for the external batteries  
Note!  
The rectifier requires a Neutral to operate. It’s connected internally from the bypass  
terminal to the rectifier, see wiring diagram.  
Figure 13. Power terminals found in UPS units.  
Power cables and protective fuses  
Always use copper cable types to fit terminals with approximately 1.5 Nm torque for different load  
currents. The Cu cable sizing is based on multi-core cables laid in conduits/trunkings on the wall or  
on the floor (installation procedure C), ambient temperature 25°C, PVC insulation, surface  
temperature up to 70°C. Cables of several UPS can be installed in parallel to each other.  
Standards SFS 6000-5-52 (2002) and IEC 60364-5-52 (2001-08) “Electrical installations of  
buildings” are used as a sizing guide. For any other conditions, size the cables according to the  
local safety regulations regarding installation environment, appropriate voltage and currents of  
the UPS.  
Fuses are sized according to local safety regulations, appropriate input voltage and the rated  
current of the UPS. Therefore, protect the input and bypass cables with gG (gL) fuses or B-C-D  
type of circuit breakers against overload and short-circuit.  
14  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contact the manufacturers authorised agent or the local office for assistance at fuse and cable  
sizing. Refer to the recommended cable and fuse ratings in the below table.  
Input  
Fusing  
3x16 A  
50 A  
Bypass  
Fusing  
3x2.5 mm² 50 A  
10 mm² 50 A  
Load  
PE  
Battery  
Cable  
UPS rating  
Cable  
Cable  
Cable  
I nom  
34.8 A  
34.8 A  
43.5 A  
43.5 A  
43.5 A  
52.2 A  
65.2 A  
65.2 A  
Cable  
8 kVA  
3-phase  
1-phase  
3-phase  
3-phase  
1-phase  
3-phase  
3-phase  
3-phase  
10 mm² 10 mm²  
10 mm² 10 mm²  
10 mm² 10 mm²  
10 mm² 10 mm²  
10 mm² 10 mm²  
16 mm² 16 mm²  
25 mm² 25 mm²  
25 mm² 25 mm²  
35 mm² 35 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
16 mm²  
16 mm²  
16 mm²  
35 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
10 mm²  
16 mm²  
10 kVA  
3x16 A* 3x2.5 mm² 50 A  
3x20 A  
63 A  
3x25 A  
3x25 A* 3x6 mm²  
3x4 mm²  
16 mm²  
3x6 mm²  
50 A  
50 A  
63 A  
80 A  
80 A  
80 A  
12 kVA  
15 kVA  
3x32 A  
3x63 A  
3x10 mm²  
3x16 mm²  
Maximum 3-phase  
Table 14. Cable and fuse ratings for the different UPS ratings  
(*With optional limited charging feature at low input and high kW load, see User Settings)  
Wiring procedure  
The power cable terminals are located in the back of the UPS unit. The service personnel is  
responsible for the correct electrical installation. They must be authorised by the manufacturer.  
The installation procedure:  
1.  
Remove the cover(s) of the terminal box of the power cables with a screwdriver.  
Refer to the dimensional drawing for the correct location at the back of the unit.  
2.  
3.  
Slide the cables through the grommets of the connection box.  
Connect the conductors of the rectifier and bypass input cables to the proper terminals.  
With single phase unit it is recommended to use the same phases for rectifier and bypass  
inputs.  
4.  
5.  
Connect the conductors of the load cable to the proper terminals.  
Connect the conductors of an external battery cabinet cable to the external battery +, -  
and PE terminals. Check for the correct polarity.  
See External Battery Cabinet (EBC) installation procedure.  
Warning!  
If available, the internal battery has to be disconnected first because the external battery  
terminals are hazardous due to the parallel battery string.  
6.  
7.  
Secure the cables with the grommets in the connection box.  
Fasten the cover of the terminal box with a screwdriver.  
The IEC/EN 62040-1 safety instructions require the fitting by the user of a warning label on all  
primary power isolators installed remote from the UPS area. The warning label for electrical  
maintenance personnel shall carry the following wording or equivalent:  
“ISOLATE UNINTERRUBTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT.”  
A readily accessible disconnect device shall be incorporated in the building installation wiring  
as shown in diagrams.  
1022403  
Revision B1  
15  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 15. Wiring diagram of UPS N-model (3-ph rectifier) with integral MBS.  
Figure 16. Wiring diagram of UPS N-model (3-ph rectifier).  
16  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 17. Wiring diagram of UPS NT-model (3-ph rectifier)  
1022403  
17  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 18. Wiring diagram of UPS S-model (1-ph rectifier) with integral MBS.  
Figure 19. Wiring diagram of UPS S-model (1-ph rectifier).  
18  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 20. Wiring diagram of UPS ST-model (1-ph rectifier).  
1022403  
19  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note!  
Site wiring fault must be  
disabled from LCD  
User Settings menu.  
Figure 21. Wiring diagram of UPS S-model (1-ph rectifier) with integral MBS, (Norway)  
Note!  
Site wiring fault must be  
disabled from LCD  
User Settings menu.  
Figure 22. Wiring diagram of UPS S-model (1-ph rectifier), (Norway)  
20  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note!  
Site wiring fault must be  
disabled from LCD  
User Settings menu.  
Figure 23. Wiring diagram of UPS ST-model (1-ph rectifier), (Norway)  
External Battery Cabinet (EBC) installation procedure  
The installation procedure is as follows:  
1.  
The EBC is recommended to place next to the UPS unit.  
Note!  
Do not place EBC on the UPS unit.  
2.  
The required minimum distance for UPS unit and EBC is ten millimeters, which is also  
required distance between two EBCs.  
3.  
4.  
Turn F1 battery breaker from the UPS unit in OFF position.  
Check that the circuit breaker F3 of the EBC is in the OFF position. To minimise safety risk  
remove one of the cable (+ or -) from battery string to break a battery circuit.  
Battery cables can be accessed by removing a plastic front cover and a metal hatch behind  
the plastic cover. Do not remove the safety wire of the circuit breaker before all the wires  
are connected and the installation of the whole system is ready. Remove plate A on the  
rear side of the EBC to connect cables to EBCs terminal block X6. Bring cables outside  
from the EBC by removing the cover plate B. Place the plate A back to the original position  
and connect the cable clamp to the place of the cover plate B.  
1022403  
Revision B1  
21  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning!  
If there is already connected battery string to terminal block there is a danger of a lethal  
electric shock. Thus it is recommended break a battery circuit by disconnecting one of the  
cables from battery string before connecting new cables to terminal circuit.  
5.  
If the system consists two or more EBC connect first the EBCs parallel as follows:  
a) Connect the cables to second EBC in the same way as guided in point four (4)  
of this installation procedure.  
b) Remove the cover plate C of the first EBC and connect cables to terminal block X6.  
Connect the cable clamp to the place of the cover plate C.  
6.  
When all the EBCs are connected parallel, disconnect one of the cables (+ or -) from UPS  
cabinets internal battery string in the same way as guided with EBC in point four (4) of  
this installation procedure before connecting cables to terminal block X3 of the UPS unit.  
Otherwise the terminal block X3 is live.  
7.  
8.  
After installation connect disconnected battery cables to strings, check that the removed  
plates on right positions remove safety wires from circuit breakers and turn breakers of  
EBCs and the UPS on.  
Finally change the Number of 32 pcs. battery strings from User Settings. SETTINGS ->  
USER SETTINGS -> NUMBER OF BATTERY STRINGS.  
Figure 24. Connection of UPS and External Battery Cabinets  
22  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 25. To minimise safety risk remove + or - cable from battery string before connecting  
UPS and EBCs.  
SPM tie cabinet  
The System Parallel Module (SPM), provided by UPS manufacturer, has input connections up  
to three parallel UPS modules. It is also possible to use two parallel UPS modules and one  
bypass connection. This bypass option can be used for service or test purposes.  
Note!  
It is not allowed to feed the load simultaneously from mains (bypass) and inverter(s) of  
the UPS unit(s). While turning the switch, where the bypass is connected, ON/OFF, UPS  
should be on static bypass mode or shut down.  
Note!  
The maximum load supported by the system is limited to size of one UPS if there are  
two UPSs and bypass connected to SPM.  
Terminals of the SPM have two-wire connection (L1 and N) and ground terminals. The upper  
ground terminal is for a load cable and the lower ground terminal is for UPSs. The wiring shall  
be done according to the following wiring diagrams. The terminals and cable routing is shown  
in Figure Cable routing of the SPM. See also Table 14 for cable and fuse ratings for the different  
UPS ratings.  
1022403  
Revision B1  
23  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 26. Dimensions of the SPM  
Figure 27. Cable routing of the SPM  
24  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 28. SPM9155 wiring diagram with three UPSs connected  
Figure 29. SPM9155 wiring diagram with two UPSs and bypass connected  
1022403  
25  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Software and connectivity  
The software Suite CD-ROM that is bundled with the UPS contains software distributions and  
documentation in CD format. Furthermore, the comprehensive connectivity option portfolio  
includes Web/SNMP adapters for networked environments, Modem card for 24/7 remote  
monitoring, ModBus/Jbus card for building management system integration, relay interface  
cards for industrial and facilities use and RS-232 cards for serial communication to one or  
multiple computers.  
Communication cables  
It is recommended that the control cables and power cables be installed on separate trays.  
Where control cables will cross power cables make sure they are arranged at an angle as near to  
90 degrees as possible.  
All control cables shall preferably be shielded. If the shield is grounded, this shall take place on  
only one end of the cable.  
The procedure for connecting the control cables is the following:  
1.  
Remove the front cover by lifting the cover from the bottom outwards by releasing the  
retaining clip. It’s located in the bottom part of the bezel.  
2.  
Locate the control terminal or X-slot module where you want to install the  
communications cable.  
Figure 30. Location of control cable terminals.  
Connection to the standard RS-232 port (X53)  
The standard RS-232 interface uses 9-pin female D-sub connector. It shall be used with the  
delivered cable for a computer or external modem connection. The data is transmitted with  
XCP protocol that includes status and meters information about the UPS. The RS-232 port has  
the following format:  
Data bits  
Parity  
8
None  
1
Stop bits  
Handshake  
None  
26  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 31. Identification of the interface port pins.  
LanSafe software  
The LanSafe software shuts down computers and whole networks in case of an extended power  
failure. It provides basic monitoring, data logging, notification and event actions for a single  
UPS solution. The software is bundled free of charge in Software Suite CD.  
The connection procedure for the RS-232 interface port is following:  
1. Connect the RS-232 communication cable to the computer.  
2. Connect the RS-232 communication cable to the serial interface on the UPS.  
3. Run the UPS software installation disk (Software Suite CD) on the computer.  
Note!  
If communication does not work choose the correct baud rate from the LCD display  
Please refer to the optional software manuals for appropriate baud rate settings.  
External control connections  
The UPS has an input/output interface for direct communication with your computer system. It  
is located behind the front bezel of the UPS unit. The cables connected to these terminals  
should be connected to cable clips.  
Input and output terminals have a functional isolation from terminal to terminal. They are  
connected to the chassis through individual 1 Mresistors.  
1022403  
Revision B1  
27  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 32. External control cable connections to the UPS.  
Note!  
Pay attention to proper polarity if one is using a semiconductor switch type. A relay or  
other mechanical control is a preferred method.  
Emergency Power Off (EPO)  
This input is used to shut down the UPS from a distance. This feature can be used for  
emergency power down. There are two modes of operation, normally closed at X52 and  
normally open at X12. Remote shut down terminal X52 pins 1 and 2 are as factory default  
linked (X12 is open). When the loop on X52 is opened, the logic circuitry will immediately  
shut down the UPS output.  
Note!  
EPO does not necessarily disconnect supply to load when unit is on internal or external  
bypass. Quaranteed disconnection of bypass supply has to be through a separate  
disconnect switch located in the supplying switchgear cabinet.  
In order to have the UPS running again pins 1 and 2 of connector X52 have to be reconnected  
and the UPS started manually. The pins must be shorted in order to keep the UPS running.  
Maximum resistance is 10 ohm. The EPO shall not be galvanically connected to any mains  
connected circuits. Reinforced insulation to the mains is required.  
If the use of normally open EPO operation is desired, the loop on X52 has to be retained and  
the normally open EPO switch connected to X12. Operation is as above.  
28  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay outputs  
The UPS incorporates a programmable relay output with potential free contacts at X57 for remote  
alarm indications. It is rated for max. 30 VAC 1 A or 60 VDC 0,2 A nominal values. Additional  
(4) relay outputs can be obtained with the X-slot compatible AS/400 Relay Module (optional).  
Warning!  
The relay contacts must not be directly connected to mains related circuits. Reinforced  
insulation to the mains is required.  
Programmable signal inputs  
The UPS incorporates two programmable inputs (X44, X45). Use of a non-polar (relay) control  
input is recommended. The pins must be shorted with maximum resistance of 10 ohm in order  
to activate the specific input.  
Note!  
Please note the polarity of the inputs as indicated in the external control connections if  
used with a polarity control.  
The default and programmable settings for the signal inputs are  
a)  
Disable Bypass Operation  
If active the automatic transfer to the static bypass is prevented.  
b)  
Charger off  
If active the batteries charging is disabled. In case of mains power outage the discharge of  
batteries is supported.  
c)  
Remote ON/OFF  
If active the UPS output turns off regardless of mode of operation. Auxiliary power, fan,  
communications and rectifier/battery charger shall remain functional. Restart initiated  
immediately when inactive.  
d)  
e)  
f)  
Request Bypass  
If active the UPS transfers to bypass if bypass voltage, frequency and synchronisation are ok.  
Request Normal  
If active the UPS transfers to inverter operation if not prohibited by EPO or alarm condition.  
Force Bypass  
If active the UPS is forced to static bypass operation regardless of the bypass status.  
g)  
h)  
External Battery Breaker Status  
If active the UPS knows that the batteries are disconnected.  
Building alarm 1-6  
These can be activated separately or at the same time with other building alarms.  
i)  
j)  
Not in use (default)  
Shutdown  
If active the UPS will shutdown immediately.  
k)  
l)  
Delayed Shutdown  
If active the UPS will shutdown after user configurable delay time. Restart initiated  
immediately when inactive.  
Normal/Bypass  
If active the UPS transfers to bypass if ok. If inactive the UPS transfers to inverter when  
possible.  
1022403  
Revision B1  
29  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
X-slot communication (option)  
X-Slot modules allow the UPS to communicate in a variety of networking environments and with  
different types of devices. The UPS incorporates two (2) empty X-slot communication bays.  
Figure 33. Location of empty X-slot bays.  
The UPS supports two serial communication devices according to the table below.  
Independent  
Multiplexed  
Std. RS-232 port  
Configuration  
Default #1  
Default #2  
Default #3  
X-slot #1  
X-slot #2  
Any X-slot Module  
Any X-slot Module  
Any X-slot Module  
Any X-slot Module  
Relay Module  
Not in use  
Not in use  
Available  
Available  
Table 34. Typical X-slot configurations for UPS communication.  
SNMP/Web Module (optional)  
The module supports SNMP and HTTP compliant remote monitoring and shutdown for the  
protected computer systems. It can be connected to a twisted-pair Ethernet network (10/  
100BaseT) using an RJ45 connector.  
The SNMP/Web module has a build-in switching hub that allows three (3) additional network  
devices to be connected to the network without the requirement of additional network drops.  
In addition, an Environmental Monitoring Probe can be requested from the UPS manufacturer  
to obtain humidity, temperature, smoke alarm and security information. It is connected to the  
communication port of the SNMP/Web module as option.  
Figure 35. ConnectUPS-X SNMP/Web Module and Environmental Monitoring Probe.  
30  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS400 Relay Module (optional)  
The Relay Module provides potential free relay interface for AS/400 connected computers and  
industrial applications. The relay interface supports both 15-pin D-sub connector and terminal  
block connections up to four (4) potential free relays.  
The relay contacts are rated for 1 A, 30 Vac or 200 mA, 60 Vdc, and they have a galvanic  
isolation from the other circuits of the UPS unit.  
Figure 36. AS400 Relay Module.  
Single Serial Port Module (optional)  
To establish communication between the UPS and a computer, connect your computer to the  
UPS communication port using the supplied communication cable.  
When the communication cable is installed, power management software can exchange data  
with the UPS. The software polls the UPS for detailed information on the status of the power  
environment. If a power emergency occurs, the software initiates the saving of all data and an  
orderly shutdown of the equipment.  
Modus/Jbus Module (optional)  
The Modbus module provides monitoring and integration to the Building Management  
Software (BMS) such as Wonderware. It features continuous and reliable communication  
through isolated DB9 ports (RS485/RS232) or a terminal strip (RS485).  
Figure 37. Modus/Jbus Module.  
1022403  
Revision B1  
31  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. User operations  
The UPS has a four-button graphical LCD with backlight. It provides useful information about  
the unit itself, load status, events, measurements, and settings.  
The LCD backlight is switched on by pressing any button. It has a timeout that automatically  
switches off after 15 minutes of inactivity.  
Display functions  
As default and after 15 minutes of inactivity the UPS is showing the selectable start screen:  
1.  
2.  
Logo screen  
Mimic screen (See User Settings on LCD screen)  
The screen backlit has automatic shutdown after long period of inactivity. It will light up once a  
button is pushed. The right side button will initiate the text to the screen. The scrolling  
through the menu structure is done with buttons indicated by the ↑ ↓images of the LCD  
screen. The menu structure is shown in the table below.  
Main Menu  
Submenu  
Menu functions  
I
UPS off / System normal / UPS supporting load / UPS on battery /  
UPS on bypass / +active alarms and notices / +battery status  
(resting, charging, floating, not connected, dischargin)  
UPS STATUS  
->  
->  
I
EVENT LOG  
I
Notice / Alarm  
MEASUREMENTS OUTPUT  
Voltage / Current / Frequency / Power  
Voltage / Current / Runtime  
Voltage / Current / Frequency  
Voltage / Frequency  
BATTERY  
INPUT  
BYPASS  
I
CONTROL  
->  
Goto bypass / Battery test / Display test  
Date / LCD contrast / Change language / Relay config / Signal  
inputs / Serial port config / Start screen / User password / Audible  
alarms / Battery charging method / +list of std. settings  
USER  
SETTINGS  
SETTINGS  
SERVICE  
SETTINGS  
Adjust parameters / Adjust events / Reset custom / Clear history /  
+ modem call settings  
I
IDENTIFICATI-  
ON  
->  
->  
UPS Type / Part nro. / Serial nro / Revisions  
-
I
TURN UPS  
ON/OFF  
Table 38. Menu map for display functions.  
32  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
User Settings  
The UPS has the following typical settings that are user configurable. Note that some of the  
settings become effective at the next start-up of the UPS.  
Description  
Available settings  
Default setting  
General:  
Display contrast adjustment  
+ / -  
Moderate  
[English], [Spanish], [French],  
[German]  
Display language  
English (British)  
Date & time  
[xxxx-xx-xx]  
0001-01-01  
Normal  
Audible alarms  
[Normal], [Disabled]  
[logo], [mimic]  
Normal screen in display  
user settings password  
Nominal values:  
Powerware logo  
Not required  
[Not required], [Set]  
Nominal output voltage  
Nominal output frequency  
Rectifier phase current limit  
Communication and connectivity:  
Disable control commands  
Communication speed  
[220], [230], [240]  
[50 Hz], [60 Hz]  
Step: 1 A  
230 Volts  
50 Hz  
32 Amps (3~)  
[Enabled], [Disabled]  
Disabled  
[1200], [2400], [9600], [19200]  
19200 bps.  
[UPS ON/OK], [Custom], [Battery low], UPS ON/OK  
[System on bypass], [System on battery]  
Std. relay output function  
Signal input #1-2 function  
[Nothing], [see Signal inputs]  
Nothing  
120 sec  
Hardware remote off delay for hardware Remote off  
with restart function.  
Step: 1 sec.  
X-slot defaults:  
#1: on battery  
#2: battery low  
#3: UPS on/ok  
#4: on bypass  
X-slot relay output 1-4 function  
[Nothing], [see Signal inputs]  
Step: 1 sec.  
X-slot input signal (long break via Rx)  
Nothing  
X-slot shutdown signal activation delay before the  
signal is accepted.  
5 sec  
Bypass and syncronisation:  
Usage of bypass  
[Enabled], [Disabled]  
[Required], [Not Required]  
[Immediately], [after delay]  
[Enabled], [Disabled]  
+1% ... +20%, step: 1%  
-1% ... -20%, step: 1%  
0.5 ... 3.0 Hz, step: 0.1 Hz  
Step: 0.1 Hz/s  
Enabled  
Not required  
Immediately  
Enabled  
+10%  
Require synch at transfer on bypass  
Transfer on bypass on overload  
Synchronization enable  
Bypass voltage deviation high limit  
Bypass voltage deviation low limit  
Synchronization window  
-15%  
2.0 Hz  
Frequency slew rate  
0.2 Hz/s  
Battery information and settings:  
ABM charging cycling disable  
Charging temp compensation  
Battery size setting  
[Enabled], [Disabled]  
[Enabled], [Disabled]  
Step: 1 Watts/cell  
Enabled  
Enabled  
24 Watts/cell  
1 string  
Number of 32 pcs. battery strings  
Battery low alarm level  
0 (no batteries), 1, 2, 3, 4...  
Step: 0.01 V/cell  
1.88 V/cell  
Enabled  
Automatic battery support test  
Maximum charging current  
[Enabled], [Disabled]  
Step: 0.1 A [max. 20 Amps]  
3 Amps  
Output on, automatic delay time before turning  
the output on  
[Disabled], [Set delay, step: 1 sec]  
[Disabled], [Set delay, step: 1 sec]  
0 sec.  
Output off, automatic delay time on battery after  
which output is turned off  
Disabled  
User preferences:  
Operation priority while rectifier input break  
Site wiring fault w/ wrong Neurtal connection  
[On battery], [On bypass]  
[Enabled], [Disabled]  
On bypass  
Enabled  
Table 39. User setting in the LCD menu screen.  
1022403  
Revision B1  
33  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring user settings  
User settings can be configured via front panel. Select Settings from main menu and then select  
User Settings.  
Changing language  
Pressing and holding down the first button on the left for about 5 seconds selects the language  
menu. This action is possible from any LCD menu screen.  
The default firmware has four main languages: English, Spanish, French and German. Other  
local language packages including Chinese, Greek and Russian can be requested from the local  
service representative.  
Changing charging current  
Maximum charging current setting should be checked when needed back-up time needs more  
than 3 Amps charging current.  
Load (kVA)  
p.f. 0.7  
10  
10  
10  
Load (kVA)  
p.f. 0.7  
15  
15  
15  
Back-up time  
Min current  
Back-up time  
Min current  
1 h  
3 h  
5 h  
10 h  
1.8 A  
4 A  
6.5 A  
13 A  
1 h  
3 h  
5 h  
10 h  
2.5 A  
6.5 A  
9 A  
10  
15  
18 A  
Table 40. Required battery charge currents.  
Select Maximum charging current from User Settings menu. Default setting is 3.0 Amps and it  
is changeable up to 20 Amps. Minimum step is 0.1 A.  
Note!  
Maximum charging current is dependent on output load and power rate of the UPS. If the  
UPS is supporting maximum output load the highest level of Maximum charging current is  
3.0 A, which is also the default setting. As a thumb rule, 1 kW decrease in the load provides  
extra 2.0 A charging capacity. For example, the charging capacity is 5 Amps at 8 kW load,  
and 7 A at 7 kW load.  
Using relay outputs  
Relay outputs can be used for remote alarm indications.  
Each relay has four standard pre-programmed settings for alarms:  
on bypass, UPS ok, battery low, on battery  
One of the standard relay settings is “custom” that can be customised by the user.  
The procedure to select customised alarms:  
1.  
2.  
Push any key of the control panel to enable the functions on the LCD screen.  
First select “SETTINGS”, then “USER SETTINGS” and finally “RELAY CONFIG” from  
the LCD menu.  
3.  
4.  
5.  
6.  
7.  
Select the relay what is needed to be configured (ALARM-1 is fixed relay output X57).  
Select “empty” to clear old settings.  
Select “custom” and activate needed alarms with the button on the right.  
After the selection press “OK” button  
Finally test that UPS alarms correctly  
34  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Normal start-up  
Check the mechanical and electrical installation of the UPS before start-up. Go through the  
checklist below together with another person.  
Check  
Read the attached safety manual before you work on the unit.  
The unit is fixed according to mechanical installation  
The ambient conditions are within specification.  
The cooling air will flow freely.  
The UPS is grounded properly.  
The input and bypass voltages match the UPS nominal voltage.  
The input, bypass, battery and output terminal connections are OK  
Appropriate input and bypass fuses and disconnectors are installed.  
Appropriate backfeed warning sign for disconnectors are installed.  
Appropriate cables sizes are used.  
The external control connections inside the UPS are OK.  
There are no tools, foreign objects or dust inside the UPS from the installation.  
Covers are in place.  
Optional MBS is placed to UPS position as default.  
You are then ready to proceed with the starting up the UPS:  
1. Turn the battery and input circuit breakers to ON position.  
2. UPS will enter a stand-by mode and starts to charge batteries with a cooling fan  
operational. Output is without the voltage in the stand-by mode.  
3. Push any key of the control panel to enable the functions of the LCD screen  
4. Select “TURN UPS ON” from the LCD menu (see: Display Functions)  
5. Press and hold button for 2 sec. There shall be no sound during the hold.  
The UPS shall check its internal functions, synchronise to bypass and start to supply the load.  
The green LED is blinking if there occurs an active notice. In normal operation the green LED is  
constantly lit if no new active notice such as ‘unsyncronised’ or similar notices present.  
The output voltage shall be verified from the output measurements screen of the LCD. If there  
is voltage in the output then UPS is supplying the load.  
Battery start-up  
UPS will start on battery if mains is not available. Note that the UPS behavior may be slightly  
different from the normal start-ups.  
Shutdown  
The procedure to shutdown from LCD is following:  
1. Push any key of the control panel to enable the functions of the LCD screen  
2. Select “TURN UPS OFF” from the LCD menu (see: Display Functions)  
3. Press and hold button for 5 sec. There shall be an indication sound during the hold.  
4. UPS shall do a shutdown routine.  
5. Turn the battery and input circuit breakers to OFF position to finalise the shutdown procedure.  
Note!  
The behaviour is different if UPS is turned off from the programmable input or through  
communication cards. If battery and input circuit breakers are left ON, UPS will enter a  
stand-by mode and starts to charge batteries with a cooling fan operational. Output is  
without the voltage in the stand-by mode.  
1022403  
Revision B1  
35  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Maintenance  
All operations inside the unit must be performed only by a service engineer from the  
manufacturer or from an agent, authorised by the manufacturer.  
The troubleshooting procedure gives simple remedial if a malfunction occurs in the UPS. The  
operator should start the trouble shooting if there is an active alarm indicated on the LCD  
screen. Service should be contacted if the active alarm is abnormal and displayed as a service  
code.  
Call service if you are not able to solve the problem.  
LCD display  
Description  
Action  
Shut down the least important load  
that is connected to the UPS. The UPS  
should switch back to normal  
operation once the load level is  
acceptable.  
The connected load needs more  
power than the UPS is rated to  
provide. The inverter or static bypass  
is supplying the excessive load level.  
Overload  
Batteries should be replaced and you  
need to contact the local office or  
representative of the UPS manufacturer.  
Your batteries are detected to be  
faulty.  
Battery test failed  
Battery low  
The UPS is operating in stored energy Make controlled shutdown of the  
mode. It will shut down soon due to  
low battery voltage.  
protected load immediately to prevent  
loss of data.  
Save your data and perform a  
controlled shutdown of your server  
load.  
The UPS is operating in stored energy  
mode.  
On battery  
Check that fans are operational and  
ventilation holes are not blocked. Make  
sure the ambient temperature is not  
excessive  
Overtemperature  
High UPS temperature is detected.  
Table 41. Typical alarms displayed in the LCD screen of the UPS unit.  
Scrapping  
Before scrapping UPS or its battery cabinet, the battery bank must be removed. Local  
requirements must be followed in battery recycling or discard. The removal of batteries is  
allowed only by authorised service personnel due to high energy and voltage.  
Regular service/intervals  
The UPS requires very little maintenance if installed in an appropriate environment.  
Maintentenance  
Interval  
Batteries change  
Batteries test  
Cooling fan change  
~ 3-5 years / service  
~ 18 months / service  
~ 5 years / service  
Table 42. Routine maintenance intervals recommended by the manufacturer.  
Batteries  
The condition of the batteries is crucial for operation. The UPS will indicate by audible and  
visual alarms if the capacity of the battery bank has decreased. The UPS units are provided with  
the automatic battery test and ABM management function to continuously monitor the  
condition of the battery bank.  
36  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Servicing of batteries should be performed or supervised by personnel knowledgeable about  
batteries and required precautions. When replacing batteries, replace with the same type and  
number of batteries.  
Note!  
Do not dispose of batteries in a fire. The batteries may explode.  
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It  
may be toxic.  
Cooling fan  
The cooling fan lifespan of the UPS unit is about 60 000 operating hours. The actual lifespan  
depends on the environment and ambient temperature.  
Fan failure can be predicted by increasing noise from the fan bearings. The fan replacement is  
recommended once this symptom starts appearing.  
Do not use other than manufacturers specified spare parts.  
LED Indicators  
The UPS unit has (4) LEDs to indicate the status.  
Graphical sign  
LED  
Description  
Note  
Blinking when a new notice message  
is active.  
Green  
UPS status is ok.  
Yellow 1  
Yellow 2  
Red  
UPS is in battery mode  
UPS is in bypass mode  
UPS has an active alarm  
Blinking when new alarm is not reset  
and still active.  
Table 43. Description of the LED indicators.  
Maintenance bypass switch (MBS) operation  
The maintenance bypass switch may be as standard or as optional in your system depending on  
the ordered configuration. The operation of the MBS is allowed for a trained person only who is  
familiar with the UPS behaviour and functions. The full UPS wiring diagram with a MBS switch  
is presented in the installation part of the manual.  
Note!  
The MBS consist of three switches and failure to understand the correct sequence may  
drop the critical load.  
1022403  
Revision B1  
37  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 41. The normal positions of the three MBS switches.  
Turn UPS from normal mode to mechanical bypass  
The procedure to turn the UPS to mechanical bypass switch is described below.  
Figure 42. The normal (UPS supplying the load) positions of the three MBS switches.  
No break transfer from normal mode to Service Bypass:  
1.  
2.  
The normal start position should be following:  
OFF  
ON  
ON  
Use LCD to turn the UPS on internal static bypass mode. Remember to verify the transfer  
before proceeding the next step.  
3.  
4.  
Remove the locking plate of the S1-3 switches.  
Turn ON the S1 switch to bypass UPS:  
ON  
ON  
ON  
5.  
Turn OFF the S3 switch to disconnect UPS output:  
ON  
OFF  
ON  
6.  
7.  
Use LCD to turn UPS OFF.  
Turn F1 battery breakers and F2 input to OFF position.  
38  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.  
9.  
Turn OFF the S2 switch to disconnect UPS bypass input:  
ON  
OFF  
OFF  
Remount the locking plate of the S1-3 switches to the position to prevent the use of them.  
10. UPS is now in the mechanical bypass mode, see below:  
Turn UPS from mechanical bypass to normal mode  
The procedure to turn the UPS back to normal mode is described below.  
Figure 46. The service (bypass supplying the load) positions of the three MBS switches.  
No break transfer from Mechanical Bypass to normal mode:  
1.  
The normal start position should be following:  
ON  
OFF  
OFF  
2.  
3.  
Remove the locking plate of the S1-3 switches.  
Turn ON S2 switch to connect bypass input to UPS:  
ON  
OFF  
ON  
4.  
5.  
Turn the F1 battery and F2 input breakers to ON position.  
Use LCD to “Turn UPS on” and wait until fully started.  
- Make sure the UPS is not displaying alarms or notices alarm with the green LED lit.  
- You may verify the output voltage from the meters screen of the LCD.  
6.  
Use LCD to transfer the UPS to internal static bypass. Remember to verify the transfer  
before proceeding the next step.  
1022403  
Revision B1  
39  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.  
8.  
9.  
Turn ON S3 switch to connect UPS output to load:  
ON  
ON  
ON  
Turn OFF S1 switch to disconnect bypass output:  
OFF  
ON  
ON  
Use LCD to transfer the UPS to normal mode.  
10. Remount the locking plate of the S1-3 swiches to the position to prevent the use of them.  
11. UPS is now in Normal mode, see below:  
40  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Dimensional drawings  
Figure 47. UPS models with no battery sections.  
Figure 48. UPS models with (1) and (2) battery bottom sections.  
Figure 49. UPS models with (1) and (2) battery bottom sections plus integrated MBS.  
1022403  
41  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 50. External battery cabinet models with (2) and (3) sections.  
Figure 51. UPS models with middle battery and bottom transformer sections.  
42  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.Technical data  
Standards  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Safety  
EMC  
IEC 62040-1-1, EN 62040-1-1 and EN 60950  
EN 50091-2  
Product  
IEC 62040-3 and EN 62040-3  
Environment  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Amb. temperature  
Relative humidity  
Altitude  
0 to +40°C (electronics), 15 to +25°C (batteries)  
0 to 95%, no condensation allowed  
<1000 m above sea level at +40°C  
Vibration  
IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal  
Mechanical configuration  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Dimensions  
- Width  
- Depth  
305 mm  
702 mm  
- Height  
817 mm (32 bat) or 1214 mm (2x32 bat)  
Weight  
- no battery  
- 32 battery  
- 64 battery  
- 32 battery and transformer  
- MBS  
65 kg  
155 kg  
265 kg  
270 kg  
70 kg  
160 kg  
270 kg  
275 kg  
+15 kg  
Colour  
RAL 9005 black  
Characteristics  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Efficiency  
- nominal load  
Heat losses  
Up to 92%  
<580 W  
Up to 93%  
<720 W  
Up to 93%  
<1050 W  
Up to 92%  
<870 W  
10 min (32 bat 7 Ah) 6 min (32 bat 7 Ah)  
15 min (32 bat 9 Ah) 10 min (32 bat 9 Ah) 8 min (32 bat 9 Ah)  
28 min (64 bat 7 Ah) 20 min (64 bat 7 Ah) 15 min (64 bat 7 Ah) 10 min (64 bat 7 Ah)  
33 min (64 bat 9 Ah) 25 min (64 bat 9 Ah) 20 min (64 bat 9 Ah) 15 min (64 bat 9 Ah)  
50 - 53 dB(A) depending on the load  
Backup time  
- load pf 0.7  
(+25°C amb.)  
5 min (32 bat 9 Ah)  
Noise (ISO 7779)  
1022403  
Revision B1  
43  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC input  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Rectifier input  
- S/SC model  
- N/NC model  
Bypass input  
1-phase  
3-phases  
-
-
3-phases  
3-phases  
1 phase  
Voltage (L.-N)  
Frequency  
Power factor  
Input distortion  
Rated input current  
- 3-phases  
192 to 253 Volts without using battery  
45 to 65 Hz  
0.99  
< 5% THD(I)  
11,6 A  
34,8 A  
14,5 A  
43,5 A  
17,4 A  
-
21,8 A  
-
- 1-phase  
DC circuit  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Management  
Nominal voltage  
Battery qty  
Advanced Battery Management  
384 Volts  
32 pcs.  
Float voltage  
Battery type  
Cut off voltage  
Battery charging  
2.30 VPC  
VRLA 12 Volts  
1.75 VPC  
3 amps, user selectable  
AC output  
UPS  
8 kVA  
10 kVA  
12 kVA  
15 kVA  
Active power  
Nro. of phases  
Frequency  
Voltage  
7,2 kW  
9 kW  
10,8 kW  
13.5 kW  
1-phase  
50 Hz or 60 Hz, user selectable  
220, 230 or 240 Volts, user selectable  
Short circuit  
capability  
100 A, < 300 ms  
144 A, < 300 ms  
10 min >100-110% load  
1 min > 110-125% load  
5 sec >125-150% load  
300 ms >150% load  
Overload capability  
44  
1022403  
Revision B1  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Warranty  
The product is warranted against defects in design, materials and workmanship for a period of  
twelve (12) months from its original date of purchase. The local office or distributor may grant  
a warranty period different to the above and refer to local terms of liability as defined in the  
supply contract.  
The UPS manufacturer is not responsible for  
Any costs resulting from a failure if the installation, commissioning, repair, alternation, or  
ambient conditions of the equipment do not fulfil the requirements specified in the  
documentation delivered with the unit and other relevant documentation.  
Equipment subjected to misuse, negligence or accident  
Equipment comprised of materials provided or designs stipulated by the purchaser.  
Under no circumstances shall the manufacturer, its suppliers or subcontractors be liable for  
special, indirect, incidental or consequential damages, losses or penalties.  
The technical data, information and specifications are valid at the time of printing. The UPS  
manufacturer reserves the right to modifications without prior notice.  
1022403  
45  
UPS 8 – 15 kVA, 230V 50/60 Hz output  
Revision B1  
Users Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Philips CRT Television 14PT1686S User Manual
Philips Iron GC148 User Manual
Philips Projector Garbo User Manual
Philips VCR SVB106 User Manual
Pioneer Music Mixer Sound Vision MIxer User Manual
Planar Projector PR5022 User Manual
Planar Projector PR9030 User Manual
Plantronics Stereo System mda200 User Manual
Polycom Server KWS1500 User Manual
Premier Mounts Projector Accessories PCS 5000 User Manual