Safety Guidelines for Hazardous Voltages  
If hazardous voltages are connected to the module, take the  
following precautions. A hazardous voltage is a voltage greater  
than 42.4 Vpk or 60 VDC to earth ground.  
Caution Ensure that hazardous voltage wiring is  
performed only by qualified personnel adhering to  
local electrical standards.  
Caution Do not mix hazardous voltage circuits and  
human-accessible circuits on the same module.  
Caution Make sure that devices and circuits connected to  
the module are properly insulated from human contact.  
Caution When module terminals are hazardous voltage  
LIVE (>42.4 Vpk/60 VDC), you must ensure that devices  
and circuits connected to the module are properly  
insulated from human contact.  
Safety Guidelines for Hazardous Locations  
The NI 9426 is suitable for use in Class I, Division 2, Groups A, B,  
C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4, and  
© National Instruments Corp.  
3
NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ex nA IIC T4 hazardous locations; and nonhazardous locations  
only. Follow these guidelines if you are installing the NI 9426 in a  
potentially explosive environment. Not following these guidelines  
may result in serious injury or death.  
Caution Do not disconnect I/O-side wires or connectors  
unless power has been switched off or the area is known  
to be nonhazardous.  
Caution Do not remove modules unless power has been  
switched off or the area is known to be nonhazardous.  
Caution Substitution of components may impair  
suitability for Class I, Division 2.  
Caution For Zone 2 applications, install the system  
in an enclosure rated to at least IP 54 as defined by  
IEC 60529 and EN 60529.  
Caution For Zone 2 applications, install a protection  
device that prevents the Vsup voltage from exceeding  
42 V if there is a transient overvoltage condition.  
NI 9426 Operating Instructions and Specifications  
4
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Special Conditions for Hazardous Locations Use in Europe  
This equipment has been evaluated as Ex nA IIC T4 equipment  
under DEMKO Certificate No. 07 ATEX 0626664X. Each module  
is marked  
II 3G and is suitable for use in Zone 2 hazardous  
locations. If you are using the NI 9426 in Gas Group IIC hazardous  
locations or in ambient temperatures of –40 °C Ta 70 °C, you  
must use the device in an NI chassis that has been evaluated as  
EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.  
Special Conditions for Marine Applications  
Some modules are Lloyd’s Register (LR) Type Approved for  
marine applications. To verify Lloyd’s Register certification, visit  
ni.com/certification and search for the LR certificate, or  
look for the Lloyd’s Register mark on the module.  
Caution To meet radio frequency emission requirements  
for marine applications, use shielded cables and install  
the system in a metal enclosure. Suppression ferrites  
must be installed on power supply inputs near power  
entries to modules and controllers. Power supply and  
module cables must be separated on opposite sides of the  
enclosure and must enter and exit through opposing  
enclosure walls.  
© National Instruments Corp.  
5
NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the NI 9426  
The NI 9426 has a 37-pin DSUB connector that provides  
connections for 32 simultaneously-sampled digital input channels.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
DI0  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
DI7  
DI16  
DI17  
DI18  
DI19  
DI20  
DI21  
DI22  
DI23  
Vsup  
Vsup  
DI24  
DI25  
DI26  
DI27  
DI28  
DI29  
DI30  
DI31  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
Vsup  
Vsup  
DI8  
DI9  
DI10  
DI11  
DI12  
DI13  
DI14  
DI15  
NC  
Figure 1. NI 9426 Pin Assignments  
NI 9426 Operating Instructions and Specifications  
6
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Each channel has a DI pin to which you can connect a digital input  
signal. The NI 9426 has four supply pins, Vsup, that are internally  
connected to the isolated reference of the module.  
The NI 9426 has sourcing inputs, meaning the DI pin sources  
current from Vsup to the sinking output device. The NI 9426  
internally limits current signals connected to DI. For more  
information about input current levels, refer to the Specifications  
section.  
You can connect 2-, 3-, and 4-wire sinking-output devices to  
the NI 9426. A sinking-output device provides a path from the  
DI pin to a voltage below Vsup. An example of a sinking-output  
device is an open collector NPN.  
Connect the sinking-output device to the DI pin of the NI 9426.  
Connect the positive power supply lead of the external device to the  
Vsup pin. Refer to Figure 2 for an illustration of connecting a device  
to the NI 9426.  
© National Instruments Corp.  
7
NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vsup  
DI  
External  
Power  
Supply  
+
_
Sinking-Output  
Device  
NI 9426  
Figure 2. Connecting a Device to the NI 9426 (Three-Wire Device Shown)  
The NI 9426 channel registers as ON when the sinking-output  
device drives the input below Vsup and meets the input ON range.  
The channel registers as OFF when the device does not drive the  
input low and is in the input OFF range. If no device is connected  
to the DI pin, the channel registers as OFF. Refer to the  
Specifications section for more information about the ON and  
OFF states.  
NI 9426 Operating Instructions and Specifications  
8
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Sleep Mode  
This module supports a low-power sleep mode. Support for sleep  
mode at the system level depends on the chassis that the module is  
plugged into. Refer to the chassis manual for information about  
support for sleep mode. If the chassis supports sleep mode, refer to  
the software help for information about enabling sleep mode. Visit  
ni.com/info and enter cseriesdoc for information about  
C Series documentation.  
Typically, when a system is in sleep mode, you cannot  
communicate with the modules. In sleep mode, the system  
consumes minimal power and may dissipate less heat than it does  
in normal mode. Refer to the Specifications section for more  
information about power consumption and thermal dissipation.  
Specifications  
The following specifications are typical for the range –40 to 70 °C  
unless otherwise noted. All voltages are relative to Vsup unless  
otherwise noted.  
Input Characteristics  
Number of channels..........................32 digital input channels  
© National Instruments Corp.  
9
NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Input type..........................................Sourcing  
Digital logic levels  
OFF state  
Input voltage1.......................(Vsup – 5 V)  
Input current.........................150 μA from DI pin  
ON state  
Input voltage1.......................(Vsup – 10 V)  
Input current.........................330 μA from DI pin  
Hysteresis  
Input voltage ........................1.9 V min  
Input current.........................65 μA min  
Input impedance................................30 kΩ 5%  
I/O protection (Vsup-to-channel)  
Input voltage...............................30 V max  
Reverse-biased voltage...............30 V max  
1
Vsup is the external power supply voltage.  
NI 9426 Operating Instructions and Specifications  
10  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hold time1.........................................0 s min  
Setup time2........................................1 μs min  
Update/transfer time3........................7 μs max  
MTBF ...............................................955,723 hours at 25 °C;  
Bellcore Issue 2, Method 1,  
Case 3, Limited Part Stress  
Method  
Note Contact NI for Bellcore MTBF specifications  
at other temperatures or for MIL-HDBK-217F  
specifications.  
1
Hold time is the amount of time input signals must be stable after initiating a read  
from the module.  
2 Setup time is the amount of time input signals must be stable before reading from the  
module.  
3 The update/transfer time is valid when the module is used in a CompactRIO system.  
When used in other systems, driver software and system latencies impact this time.  
© National Instruments Corp.  
11 NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Requirements  
Power consumption from chassis  
Active mode ...............................615 mW max  
Sleep mode1................................5 mW max  
Thermal dissipation (at 70 °C)  
Active mode ...............................1.35 W max  
Sleep mode .................................1.16 W max  
Physical Characteristics  
If you need to clean the module, wipe it with a dry towel.  
Weight...............................................147 g (5.2 oz)  
Safety  
Safety Voltages  
Connect only voltages that are within the following limits.  
Vsup-to-channel .................................30 VDC max  
1
The external power supply may power the module during sleep mode.  
NI 9426 Operating Instructions and Specifications  
12  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Isolation  
Channel-to-channel ....................None  
Channel-to-earth ground  
Continuous...........................60 VDC,  
Measurement Category I  
Withstand .............................1,000 Vrms, verified by a 5 s  
dielectric withstand test  
Measurement Category I is for measurements performed on  
circuits not directly connected to the electrical distribution system  
referred to as MAINS voltage. MAINS is a hazardous live electrical  
supply system that powers equipment. This category is for  
measurements of voltages from specially protected secondary  
circuits. Such voltage measurements include signal levels, special  
equipment, limited-energy parts of equipment, circuits powered by  
regulated low-voltage sources, and electronics.  
Caution Do not connect the NI 9426 to signals or use for  
measurements within Measurement Categories II,  
III, or IV.  
© National Instruments Corp.  
13 NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Standards  
This product is designed to meet the requirements of the following  
standards of safety for electrical equipment for measurement,  
control, and laboratory use:  
IEC 61010-1, EN 61010-1  
UL 61010-1, CSA 61010-1  
Note For UL and other safety certifications, refer to the  
product label or visit ni.com/certification, search  
by module number or product line, and click the  
appropriate link in the Certification column.  
Hazardous Locations  
U.S. (UL) ..........................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2,  
AEx nA IIC T4  
Canada (C-UL) .................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2,  
Ex nA IIC T4  
Europe (DEMKO).............................Ex nA IIC T4  
NI 9426 Operating Instructions and Specifications  
14  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Environmental  
National Instruments C Series modules are intended for indoor use  
only but may be used outdoors if installed in a suitable enclosure.  
Refer to the manual for the chassis you are using for more  
information about meeting these specifications.  
Operating temperature  
(IEC 60068-2-1, IEC 60068-2-2) .....40 to 70 °C  
Storage temperature  
(IEC 60068-2-1, IEC 60068-2-2) .....40 to 85 °C  
Ingress protection..............................IP 40  
Operating humidity  
(IEC 60068-2-56)..............................10 to 90% RH,  
noncondensing  
Storage humidity  
(IEC 60068-2-56)..............................5 to 95% RH,  
noncondensing  
Maximum altitude.............................2,000 m  
Pollution Degree (IEC 60664)..........2  
© National Instruments Corp.  
15 NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shock and Vibration  
To meet these specifications, you must panel mount the system.  
Operating vibration  
Random (IEC 60068-2-64).........5 grms, 10 to 500 Hz  
Sinusoidal (IEC 60068-2-6) .......5 g, 10 to 500 Hz  
Operating shock  
(IEC 60068-2-27)..............................30 g, 11 ms half sine,  
50 g, 3 ms half sine,  
18 shocks at 6 orientations  
Electromagnetic Compatibility  
This product is designed to meet the requirements of the following  
standards of EMC for electrical equipment for measurement,  
control, and laboratory use:  
EN 61326 EMC requirements; Industrial Immunity  
EN 55011 Emissions; Group 1, Class A  
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A  
Note For EMC compliance, operate this device with  
shielded cabling.  
NI 9426 Operating Instructions and Specifications  
16  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CE Compliance  
This product meets the essential requirements of applicable  
European directives, as amended for CE markings, as follows:  
2006/95/EC; Low-Voltage Directive (safety)  
2004/108/EC; Electromagnetic Compatibility Directive  
(EMC)  
Note Refer to the Declaration of Conformity (DoC) for  
this product for any additional regulatory compliance  
information. To obtain the DoC for this product, visit  
ni.com/certification, search by module number  
or product line, and click the appropriate link in the  
Certification column.  
Environmental Management  
National Instruments is committed to designing and manufacturing  
products in an environmentally responsible manner. NI recognizes  
that eliminating certain hazardous substances from our products is  
beneficial not only to the environment but also to NI customers.  
© National Instruments Corp.  
17 NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For additional environmental information, refer to the NI and the  
Environment Web page at ni.com/environment. This page  
contains the environmental regulations and directives with which  
NI complies, as well as other environmental information not  
included in this document.  
Waste Electrical and Electronic Equipment (WEEE)  
EU Customers At the end of their life cycle, all products  
must be sent to a WEEE recycling center. For more  
information about WEEE recycling centers and National  
Instruments WEEE initiatives, visit ni.com/  
environment/weee.htm.  
⬉ᄤֵᙃѻક∵ᶧ᥻
ㅵ⧚
⊩ ˄Ё೑  
˅
RoHS  
ヺড়Ё೑⬉ᄤֵᙃ  
Ё೑ᅶ᠋  
National Instruments  
ѻકЁ䰤
Փ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ  
DŽ݇Ѣ  
(RoHS)  
Ё೑  
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ  
RoHS  
National Instruments  
ni.com/environment/rohs_chinaDŽ  
about China RoHS compliance, go to  
environment/rohs_china  
(For information  
ni.com/  
.)  
NI 9426 Operating Instructions and Specifications  
18  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where to Go for Support  
The National Instruments Web site is your complete resource for  
technical support. At ni.com/support you have access to  
everything from troubleshooting and application development  
self-help resources to email and phone assistance from  
NI Application Engineers.  
National Instruments corporate headquarters is located at  
11500 North Mopac Expressway, Austin, Texas, 78759-3504.  
National Instruments also has offices located around the world to  
help address your support needs. For telephone support in the  
United States, create your service request at ni.com/support  
and follow the calling instructions or dial 512 795 8248. For  
telephone support outside the United States, contact your local  
branch office:  
Australia 1800 300 800, Austria 43 662 457990-0,  
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,  
Canada 800 433 3488, China 86 21 5050 9800,  
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,  
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,  
Germany 49 89 7413130, India 91 80 41190000,  
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,  
© National Instruments Corp.  
19 NI 9426 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,  
Malaysia 1800 887710, Mexico 01 800 010 0793,  
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,  
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,  
Portugal 351 210 311 210, Russia 7 495 783 6851,  
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,  
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,  
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,  
Taiwan 886 02 2377 2222, Thailand 662 278 6777,  
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545  
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the  
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other  
product and company names mentioned herein are trademarks or trade names of their respective companies.  
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,  
the patents.txt file on your media, or ni.com/patents.  
© 2007–2008 National Instruments Corp. All rights reserved.  
374712D-01  
May08  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Vacuum Cleaner S 8900 User Manual
Milwaukee Power Screwdriver 2101 20 User Manual
Murphy Remote Starter AS730 User Manual
NETGEAR Computer Drive Pioneer Edition User Manual
Network Technologies Switch MAN027 User Manual
Nikon Digital Camera 1544 User Manual
Olympus Camcorder 227500 User Manual
Onkyo Home Theater System SKB 540 User Manual
Onkyo Stereo Receiver PR SC886 User Manual
Oster Fryer 3222 User Manual