Maytag Water Heater HRN11240P User Manual

Series Twelve  
POWER VENT  
GAS WATER HEATER  
USER’S GUIDE  
FOR POTABLE WATER HEATING ONLY  
NOT SUITABLE FOR SPACE HEATING  
NOT FOR USE IN  
MANUFACTURED (MOBILE) HOMES  
Model Numbers  
HRN11240P  
HRP11250P  
HRP31250P  
HRN11275P  
HRN31275P  
HRP11275P  
HRP31275P  
HRN31240P  
HRP11240P  
HRP31240P  
HRN11250P  
HRN31250P  
For Your Safety  
AN ODORANT IS ADDED TO THE GAS USED  
BY THIS WATER HEATER.  
PRINTED IN THE U.S.A. 0505  
PART NO. 66001897  
184683-001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY PRECAUTIONS  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
SAFE INSTALLATION, USEAND SERVICE ....................................................................................................................................... 2  
SAFETY PRECAUTIONS ................................................................................................................................................................... 3  
TABLE OF CONTENTS ...................................................................................................................................................................... 4  
CUSTOMER RESPONSIBILITIES ..................................................................................................................................................... 5  
PRODUCT SPECIFICATIONS ........................................................................................................................................................... 5  
ACCESSORIES AND TOOLS NEEDED ............................................................................................................................................ 6  
Accessories ................................................................................................................................................................................ 6  
Tools............................................................................................................................................................................................ 6  
Additional Tools Needed When Sweat Soldering ...................................................................................................................... 6  
INSTRUCTIONS FOR INSTALLATION .............................................................................................................................................. 7  
Removing the Old Water Heater................................................................................................................................................. 7  
TYPICALINSTALLATION ................................................................................................................................................................ 8,9  
Get to Know Your Water Heater .................................................................................................................................................. 8  
LOCATING THE NEW HEATER ....................................................................................................................................................... 10  
Facts to Consider About the Location.................................................................................................................................. 10,11  
Combustion Air and Ventilation ........................................................................................................................................... 11-13  
Insulation Jackets ..................................................................................................................................................................... 13  
Combustion Air and Ventilation Appliances  
in Unconfined Spaces............................................................................................................................................................... 13  
Combustion Air and Ventilation Appliances  
in Confined Spaces ............................................................................................................................................................. 13,14  
Water Piping......................................................................................................................................................................... 14,15  
T & P Valve and Pipe Insulation ........................................................................................................................................ 15,16  
Temperature Pressure Relief Valve..................................................................................................................................... 16,17  
Filling the Water Heater ............................................................................................................................................................ 17  
Wiring ...................................................................................................................................................................................17,18  
Wiring Diagram ......................................................................................................................................................................... 18  
Venting..................................................................................................................................................................................19-25  
Gas Piping ................................................................................................................................................................................ 26  
Sediment Trap .......................................................................................................................................................................... 27  
OPERATING INSTRUCTIONS....................................................................................................................................................28-31  
Operating .................................................................................................................................................................................. 29  
Temperature Regulation ......................................................................................................................................................29-31  
Lighting & Operating Label ....................................................................................................................................................... 30  
SERVICEAND MAINTENANCE ..................................................................................................................................................32-34  
Tank (Sediment) Cleaning........................................................................................................................................................ 32  
Venting System Inspection ....................................................................................................................................................... 32  
Burner Inspection ..................................................................................................................................................................... 32  
Burner Cleaning........................................................................................................................................................................ 32  
L.P. Gas Control Valve & Burner Assembly Replacement Information .................................................................................... 33  
Housekeeping .......................................................................................................................................................................... 33  
Anode Rod Inspection .............................................................................................................................................................. 33  
Draining ............................................................................................................................................................................... 33,34  
Temperature-Pressure Relief Valve Operation ........................................................................................................................ 34  
Drain Valve Washer Replacement ........................................................................................................................................... 34  
Service....................................................................................................................................................................................... 34  
TROUBLESHOOTING ................................................................................................................................................................35-40  
Start Up Conditions ................................................................................................................................................................... 35  
Condensation ................................................................................................................................................................. 35  
Smoke / Odor .................................................................................................................................................................. 35  
Thermal Expansion ......................................................................................................................................................... 35  
Strange Sounds .............................................................................................................................................................. 35  
Operational Conditions ....................................................................................................................................................... 35,36  
Smelly Water .............................................................................................................................................................. 35,36  
“AIR” In Hot Water Faucets ............................................................................................................................................. 36  
High Temperature Shut Off System ................................................................................................................................ 36  
Venting Manual Reset Switch ......................................................................................................................................... 36  
Not Enough or No Hot Water .......................................................................................................................................... 36  
Water is To Hot ................................................................................................................................................................ 36  
Leakage Checkpoints............................................................................................................................................................... 37  
Thermostat and Gas Supply Check ......................................................................................................................................... 38  
System Check ........................................................................................................................................................................... 39  
Troubleshooting Guidelines..................................................................................................................................................... 40  
REPAIR PARTS LIST ..................................................................................................................................................................41-44  
NOTES ........................................................................................................................................................................................45-47  
WARRANTY ..................................................................................................................................................................................... 48  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
CUSTOMER RESPONSIBILITIES  
local codes, installations shall comply with the following:  
Thank You for purchasing a Maytag water heater. Properly  
installed and maintained, it should give you years of trouble  
free service. It is strongly suggested that this new water heater  
be professionally installed, contact Maytag Customer Service  
(1-800-788-8899) for recommended installers.  
In the United States: The National Fuel Gas Code ANSI  
Z223.1/NFPA 54. This publication is available from the  
Canadian Standards Association, 8501 East Pleasant Valley  
Rd., Cleveland Ohio 44131, or The National Fire Protection  
Association, 1 Batterymarch Park, Quincy, MA 02269.  
Abbreviations Found In This Instruction Manual:  
If after reading this manual you have any questions or do not  
understand any portion of the instructions, call Maytag  
Customer Service at 1-800-788-8899 for an authorized  
servicer.  
CSA - Canadian Standards Association  
ANSI - American National Standards Institute  
NFPA - National Fire Protection Association  
ASME - American Society of Mechanical Engineers  
GAMA - Gas Appliance Manufacturers Association  
Carefully plan the place where you are going to put the water  
heater. Correct combustion, vent action, and vent pipe  
installation are very important in preventing death from  
possible carbon monoxide poisoning and fires, see  
figure 1 and 2.  
This gas-fired water heater is design certified by CSA  
INTERNATIONAL under American National Standard/CSA  
Standard for Gas Water HeatersANSI Z21.10.1 • CSA4.1 (current  
edition). The installation must conform with this manual, local  
codes and with the current edition of the National Fuel Gas  
Code, ANSIZ223.1 NFPA 54.  
Examine the location to ensure the water heater complies  
with the Facts to Consider About the Location section in this  
manual.  
Read the “Safety Precautions” section, page 3 of this manual  
first and then the entire manual carefully. If you don’t follow  
the safety rules, the water heater will not operate properly. It  
could cause DEATH, SERIOUS BODILY INJURY AND/OR  
PROPERTY DAMAGE.  
For California installation this water heater must be braced,  
anchored, or strapped to avoid falling or moving during an  
earthquake. See instructions for correct installation  
procedures. Instructions may be obtained from your local  
dealer, wholesaler, public utilities or California Office of the  
State Architect, 400 P Street, Sacramento, CA 95814.  
This manual contains instructions for the installation,  
operation, and maintenance of the gas-fired water heater. It  
also contains warnings through out the manual that you must  
read and be aware of. All warnings and all instructions are  
essential to the proper operation of the water heater and  
your safety. Since we cannot put everything on the first few  
pages, READ THE ENTIRE MANUALBEFOREATTEMPTING  
TO INSTALLOR OPERATE THE WATER HEATER.  
Massachusetts Code requires this water heater to be  
installed in accordance with Massachusetts 248-CMR 2.00:  
State Plumbing Code and 248-CMR 5.00. In the  
Commonwealth of Massachusetts, this product must be  
installed by a licensed plumber or gasfitter.  
The installation must conform with these instructions and  
the local code authority having jurisdiction. In the absence of  
Complies with SCAQMD rule #1121 and districts having  
equivalent NOx requirements.  
PRODUCT SPECIFICATIONS  
TANK  
RECOVERY  
DIMENSIONS  
IN INCHES (mm)  
HEIGHT TOP OF  
DRAFTHOOD  
CAPACITY  
IN GALS  
(LITERS)  
TYPE  
OF  
GAS  
RATE GALS.  
PERHOUR  
@90°F RISE  
46.0  
VENTPIPE  
INCHES  
(mm)  
DIAMETER  
INCHES  
(mm)  
BTU  
RATE  
MODELNUMBER  
HRN11240P  
*HRN31240P  
HRP11240P  
*HRP31240P  
HRN11250P  
HRN31250P  
HRP11250P  
HRP31250P  
HRN11275P  
*HRN31275P  
HRP11275P  
*HRP31275P  
40 (151)  
40 (151)  
40 (151)  
40 (151)  
50 (189)  
50 (189)  
50 (189)  
50 (189)  
75 (284)  
75 (284)  
75 (284)  
75 (284)  
NATURAL  
NATURAL  
PROPANE  
PROPANE  
NATURAL  
NATURAL  
PROPANE  
PROPANE  
NATURAL  
NATURAL  
PROPANE  
PROPANE  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
75,000  
75,000  
70,000  
70,000  
3" (76)**  
3" (76)**  
3" (76)**  
3" (76)**  
3” (76) **  
3” (76) **  
3” (76)**  
3” (76)**  
3" (76)***  
3" (76)***  
3" (76)***  
3" (76)***  
20" (508)  
20" (508)  
20" (508)  
20" (508)  
22” (559)  
22” (559)  
22” (559)  
22” (559)  
26 1/2" (673)  
26 1/2" (673)  
26 1/2" (673)  
26 1/2" (673)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
71 1/2" (1,816)  
46.0  
46.0  
46.0  
46.0  
46.0  
46.0  
46.0  
77.0  
77.0  
72.0  
72.0  
* High altitude models have a B.T.U./Recovery Rate 10% less than shown.  
** Limited usage of 2” vent pipe - see pages 19 through 26.  
*** Limited usage of 4” vent pipe - see pages 19 through 26.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES AND TOOLS NEEDED  
Accessories  
To simplify the installation Maytag has available the installation parts shown below. You may or may not need all of these accessories  
depending on your type of installation. Call Maytag Customer Service at 1-800-788-8899 for an authorized installer.  
DRAIN PANS AVAILABLE IN 22” (559 mm) DIAMETER (PART NO.  
66001011) FOR WATER HEATERS HAVING A DIAMETER 20” (508  
mm) OR LESS, 24” (610mm) DIAMETER (PART NO. 66001105) FOR  
WATER HEATERS HAVINGA DIAMETER 22” (559 mm) OR LESSAND  
28” (711 mm) DIAMETER (PART NO. 66001012) FOR WATER HEATERS  
HAVING A DIAMETER 26” (660 mm) OR LESS.  
EXPANSION TANKS FOR THERMAL EXPANSION CONDITIONS  
AVAILABLE IN 2 GALLONS (7.6 LITERS), Part No. 66001013 AND 5  
GALLONS (18.9 LITERS), Part No. 66001014 CAPACITY.  
Tools  
Additional Tools Needed  
When Sweat Soldering  
You may or may not need all these tools, depending on your  
type of installation. These tools can be purchased at your local  
hardware store.  
• Tubing Cutters or Hacksaw  
• Propane Torch  
• Soft Solder  
• Solder Flux  
• Emery Cloth  
• Pipe Wrenches (2) 14” (356 mm)  
• Screwdriver  
• Tin Snips  
• 6’ (1.82 m) Tape or Folding Ruler  
• Garden Hose  
• Wire Brushes  
• Drill  
• Pipe Dope or Teflon Tape  
DRILL  
PROPANE  
TORCH  
SLOT-HEAD SCREWDRIVER  
TUBING CUTTER  
TIN SNIPS  
PHILLIPS SCREWDRIVER  
ROLL OF  
EMERY CLOTH  
PIPE DOPE  
(SQUEEZE TUBE)  
HACKSAW  
ROLL OF TEFLON  
TAPE (USE ONLYON  
USE FOR WATER AND GAS  
WATER HEATER  
CONNECTIONS  
CONNECTIONS)  
3/4” (19 mm) WIRE BRUSH  
1/2” (13 mm) WIRE BRUSH  
SOLDER  
FLUX  
ROLL OF LEAD-FREE  
SOFT SOLDER  
6 FOOT TAPE  
GARDEN HOSE  
PIPE WRENCH  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTRUCTIONS FOR INSTALLATION  
4. Attach a hose to the water heater  
Removing the Old Water Heater  
drain valve and put the other end  
in a floor drain or outdoors. Open  
the water heater drain valve. Open  
a nearby hot water faucet which will  
relieve pressure in the water  
heater and speed draining. The  
water passing out of the drain valve  
may be extremely hot. To avoid  
being scalded, make sure all  
connections are tight and that the  
water flow is directed away from  
any person, see Figures 1 and 4.  
FIGURE4.  
5. Disconnect the vent pipe from the draft hood where they  
connect to the water heater. In most installations the vent  
pipe can be lifted off after any screw or other attached devices  
are removed. Dispose of the draft hood. The new water  
heater has the draft hood which must be used for proper  
operation.  
6. If you have copper piping to the water heater, the two copper  
water pipes can be cut with a hacksaw approximately four  
inches away from where they connect to the water heater.  
This will avoid cutting off pipes too short. Additional cuts can  
be made later if necessary. Disconnect the temperature-  
pressure relief valve drain line. When the water heater is  
drained, disconnect the hose from the drain valve. Close the  
drain valve. The water heater is now completely disconnected  
and ready to be removed, see Figure 5.  
FIGURE1.  
1. Turn “OFF” the gas supply to the  
water heater.  
If the main gas line Shut-off valve  
serving all gas appliances is  
used, also shut “OFF” the gas at  
each appliance. Leave all gas  
appliances shut “OFF” until the  
water heater installation is  
completed, see Figures 1 and 2.  
FIGURE5.  
FIGURE2.  
FIGURE3.  
If you have galvanized pipe to the water heater, loosen the  
two galvanized pipes with a pipe wrench at the union in each  
line. Also disconnect the piping remaining to the water heater.  
These pieces should be saved since they may be needed  
when reconnecting the new water heater. Disconnect the  
temperature-pressure relief valve drain line. When the water  
heater is drained, disconnect the hose from the drain valve.  
Close the drain valve. The water heater is now completely  
disconnected and ready to be removed. Mineral buildup or  
sediment may have accumulated in the old water heater.  
This causes the water heater to be much heavier than normal  
and this residue, if spilled out, could cause staining, see  
Figure 6.  
2. Turn “OFF” the water supply to the  
water heater at the water shut off  
valve or water meter. Some  
installations require that the water  
be turned off to the entire house,  
see Figures 1 and 3.  
3. Check again to make sure the gas supply is “OFF” to the  
water heater. Then disconnect the gas supply connection  
from the gas control valve.  
FIGURE6.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
GET TO KNOW YOUR WATER HEATER - GAS MODELS  
A
B
C
D
E
F
Vent Pipe  
Blower  
Anode  
Hot Water Outlet  
Standard Pipe Fittings  
Gas Supply  
Manual Gas Shut-off Valve  
Ground Joint Union  
I
J
K
L
M
N
O
P
Drip Leg (Sediment Trap)  
Inner Door  
Outer door  
Q
R
S
T
U
V
Rating Plate  
Flue Baffle  
Thermostat  
Drain Valve  
Pilot and Main Burner  
Flue  
Union  
Inlet Water Shut-off Valve  
Cold Water Inlet  
Inlet Dip Tube  
G
H
W
Drain Pan  
Temperature-Pressure Relief Valve  
* INSTALL INACCORDANCE  
WITH LOCAL CODES.  
* DRIP LEG AS REQUIRED  
BY LOCAL CODES.  
(S) THERMOSTAT  
TO VENT TERMINATION  
ON ROOF  
(U) PILOT & MAIN BURNER  
*
ALL PIPING MATERIALS TO BE  
SUPPLIED BY CUSTOMERS.  
** CLOSED WATER SYSTEMSARE THOSE WITH BACK FLOW  
PREVENTION DEVICES INSTALLED IN THE INLET  
SERVICE LINE.  
FIGURE7.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
MIXING VALVE USAGE  
FIGURE8.  
This appliance has been design certified as complying with  
American National Standard/CSA Standard for water heaters  
and is considered suitable for:  
more likely to be permanently injured by hot water than others.  
These include the elderly, children, the infirm, or physically/  
mentally handicapped. If anyone using hot water in your home  
fits into one of these groups or if there is a local code or state  
law requiring a certain temperature water at the hot water tap,  
then you must take special precautions. In addition to using the  
lowest possible temperature setting that satisfies your hot water  
needs, a means such as a *Mixing Valve, shall be used at the  
hot water taps used by these people or at the water heater.  
Mixing valves are available at plumbing supply or hardware  
stores. See Figure 8. Valves for reducing point of use temperature  
by mixing cold and hot water are also available. Consult Maytag  
Customer Service (1-800-788-8899). Follow mixing valve  
manufacturer’s instructions for installation of the valves. Before  
changing the factory setting on the thermostat, read the  
Temperature Regulation” section in this manual, see Figure  
52 on page 31.  
Water (Potable) Heating: All models are considered suitable  
for water (potable) heating.  
This water heater shall not be connected to any heating  
system(s) or component(s) previously used with a non-potable  
water heating appliance.  
Toxic chemicals such as used for treatment of boilers or non-  
potable water heating appliances shall never be introduced  
into a potable water space heating system.  
HOTTER WATER CAN SCALD:  
Water heaters are intended to produce hot water. Water heated  
to a temperature which will satisfy space heating, clothes  
washing, dish washing, and other sanitizing needs can scald  
and permanently injure you upon contact. Some people are  
NOTE: To protect against untimely corrosion of hot and cold  
water fittings, it is strongly recommended that di-electric  
unions or couplings be installed on the water heater when  
connected to copper pipe.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATING THE NEW WATER HEATER  
Installation of the water heater must be accomplished in such a  
Facts to Consider About the Location  
manner that if the tank or any connections should leak, the flow  
will not cause damage to the structure. For this reason, it is not  
advisable to install the water heater in an attic or upper floor.  
When such locations cannot be avoided, a suitable drain pan  
should be installed under the water heater. Drain pans are  
available at your local hardware store. Such a drain pan must  
have a minimum length and width of at least 2 inches (51 mm)  
greater that the water heater dimensions and must be piped to  
an adequate drain. The pan must not restrict combustion air flow.  
Carefully choose an indoor location for the new water heater,  
because the placement is a very important consideration for  
the safety of the occupants in the building and for the most  
economical use of the appliance. This water heater is not for  
use in manufactured (mobile) homes or outdoor installation.  
Whether replacing an old water heater or putting the water heater  
in a new location, the following critical points must be observed:  
Water heater life depends upon water quality, water pressure  
and the environment in which the water heater is installed. Water  
heaters are sometimes installed in locations where leakage  
may result in property damage, even with the use of a drain pan  
piped to a drain. However, unanticipated damage can be reduced  
or prevented by a leak detector or water shut-off device used in  
conjunction with a piped drain pan. These devices are available  
from some plumbing supply wholesalers and retailers, and  
detect and react to leakage in various ways:  
The location selected should be indoors as close as practical  
to the vent termination point, and as centralized with the water  
piping system as possible. The water heater, as all water  
heaters, will eventually leak. Do not install without adequate  
drainage provisions where water flow will cause damage.  
40,000 BTU/HR INPUT MODELS - If vented through an outside  
wall or through the roof, the 3” vent piping cannot exceed a total  
of 115 feet (50 feet if optional 2” vent piping is used), including  
vertical and horizontal runs with one 90o elbow. If more elbows  
are required, the venting distance must be reduced 5 feet for  
every 90 elbow, see page 22 for vent chart.  
Sensors mounted in the drain pan that trigger an alarm or  
turn off the incoming water to the water heater when leakage  
is detected.  
70,000 and 75,000 BTU/HR INPUT MODELS -If vented through  
an outside wall or through the roof, the 3” vent piping cannot  
exceed a total of 70 feet (110 feet if optional 4” vent piping is  
used), including vertical and horizontal runs with one 90o elbow.  
If more elbows are required, the venting distance must be  
reduced 5 feet fro every 90 elbow, see page 22 for vent chart.  
Sensors mounted in the drain pan that turn off the water supply  
to the entire home when water is detected in the drain pan.  
Water supply shut-off devices that activate based on the  
water pressure differential between the cold water and hot  
water pipes connected to the water heater.  
Vent piping cannot slope downward and horizontal runs  
require 1/8” per five foot rise. All horizontal runs require  
adequate support at 3 1/2 foot intervals and vertical runs  
supported at 5 foot intervals.  
Devices that will turn off the gas supply to a gas water heater  
while at the same time shutting off its water supply.  
The water heater requires its own (separate) venting system.  
It cannot be connected to an existing vent pipe or chimney. It  
must terminate to the outdoors. Whenever possible terminate  
the vent on the leeward side of the building if vented through  
an outside wall. NOTE: Condensation may be created, at times,  
as the combustion gases exit the vent cap and discoloration  
of surfaces in proximity to the vent cap may occur.  
The power vent water heater requires its own (separate) venting  
system. It cannot be connected to an existing vent pipe or  
chimney. It must be terminated to the outdoors. Failure to properly  
install the venting system can result in asphyxiation, a fire or  
explosion and can cause DEATH, SERIOUS BODILY INJURY,  
OR PROPERTY DAMAGE.  
The water heater comes equipped with a 7 foot power cord  
which can be used to connect to a 110/120 volt power source  
if (1) local codes allow, and (2) there is a three prong receptacle  
available. This unit must have a grounded outlet to operate.  
Do not use an extension cord. If there is not a suitable  
receptacle and/or local codes prohibit use of a power cord,  
field wiring must be provided.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS  
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED  
(GARAGES, STORAGE AND UTILITY AREAS, ETC.):  
Flammable liquids (such as gasoline, solvents, propane [LP  
or butane, etc.] and other substances such as adhesives, etc.)  
emit flammable vapors which can be ignited by a gas water  
heater’s pilot light or main burner. The resulting flashback and  
fire can cause death or serious burns to anyone in the area, as  
well as property damage. If installation in such areas is your  
only option, then installation must be accomplished in a way  
that the pilot flame and main burner flame are elevated from  
the floor at least 18 inches. While this may reduce the chances  
of flammable vapors, from a floor spill being ignited, gasoline  
and other flammable substances should never be stored or  
used in the same room or area containing a gas water heater  
or other open flame or spark producing appliance. NOTE:  
Flammable vapors may be drawn by air currents from other  
areas of the structure to the appliance.  
FIGURE9.  
• Do not obstruct water heater air  
intake with insulating blanket.  
Also, the water heater must be located and/or protected so it is  
not subject to physical damage by a moving vehicle.  
• Gas and carbon monoxide  
detectors are available.  
Propellants of aerosol sprays and volatile compounds,  
(cleaners, chlorine based chemicals, refrigerants, etc.) in  
addition to being highly flammable in many cases, will also  
change to corrosive hydrochloric acid when exposed to the  
combustion products of the water heater. The results can be  
hazardous, and also cause product failure.  
• Install water heater in accordance  
with the instruction manual.  
A gas water heater cannot operate properly without the correct  
amount of air for combustion. Do not install in a confined area  
such as a closet, unless you provide air as shown in the  
Locating The New Water Heater section. Never obstruct the  
flow of ventilation air. If you have any doubts or questions at all,  
call your gas supplier. Failure to provide the proper amount of  
combustion air can result in a fire or explosion and cause  
death, serious bodily injury, or property damage.  
This water heater must not be installed directly on carpeting.  
Carpeting must be protected by metal or wood panel beneath  
the appliance extending beyond the full width and depth of the  
appliance by at least 3 inches (76.2 mm) in any direction, or if  
the appliance is installed in an alcove or closet, the entire floor  
must be covered by the panel. Failure to heed this warning  
may result in a fire hazard.  
FIGURE10.  
If this water heater will be used in beauty shops, barber shops,  
cleaning establishments, or self-service laundries with dry  
cleaning equipment, it is imperative that the water heater or  
water heaters be installed so that combustion and ventilation  
air be taken from outside these areas.  
Combustion Air and Ventilation  
When determining the installation location for a power vent  
water heater, snow accumulation and drifting should be  
considered in areas where applicable.  
Minimum clearances between the water heater and  
combustible construction are 0 inch at the sides and rear,  
6 inches (152 mm) at the front, and 0 inches from the vent pipe.  
Clearance from the top of the jacket is 14 inches (356 mm) on  
most models. Note that a lesser dimension may be allowed  
on some models, refer to the label attached adjacent to the  
gas control valve on the water heater, see Figure 9.  
VENTINGCLEARANCES  
0” clearance for 3” (and optional 2” and 4”) PVC, ABS or  
CPVC Schedule 40 vent piping from combustible surfaces.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24” minimum from any appliance inlet and/or outlet vents  
when directly below or 45o to either side of center line,  
see Figure 13.  
12” minimum from the ground, 9” ceiling overhangs, see  
Figure 11.  
18” minimum in all directions from any obstruction that may  
interfere, see Figure 14.  
FIGURE14.  
FIGURE11.  
The location selection must provide clearances for servicing  
and proper operation of the water heater, see Figure 15.  
The Power Vent outlet terminal shall terminate at least 36”  
above any forced air inlet into the building located within  
10 feet, see Figure 12.  
The Power Vent outlet terminal shall terminate at least  
4 feet below, 4 feet horizontally from or 1 foot above any door,  
window or gravity air inlet into the building, see Figure 12.  
FIGURE15.  
Vent termination must not be within 4 feet of any items such  
as gas meters, gas valves or other gas regulating  
equipment.  
The venting system must be installed in a manner which  
allows inspection of the installation of the venting pipes and  
joints as well as periodic inspection after installation as  
required by ANSI Standards.  
Vent termination must not be within 4 feet of any items such as  
gas meters, gas valves or other gas regulating equipment.  
FIGURE12.  
18” minimum from other natural draft (gravity) direct vent,  
power vent or power direct vent appliance inlet and/or outlet  
vent(s) when directly above or 135o to either side of the  
center line, see Figure 13.  
Failure to have required clearances between water heater and  
combustible material will result in a fire hazard.  
VENTING THROUGH ROOF - CLEARANCES  
0” clearances for 3” (or optional 2” and 4”) PVC, ABS, or  
CPVC Schedule 40 piping from combustible surfaces.  
The Power Vent outlet terminal shall terminate at least 18”  
above the roof surface, see Figure 16.  
The location selection must provide clearances for servicing  
and proper operation of the water heater, see Figure 15.  
The venting system must be installed in a manner which  
allows inspection of the installation of the venting pipes and  
joints as well as periodic inspection after the installation as  
required by ANSI Standards.  
FIGURE13.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Do inspect the insulation blanket frequently to make certain  
it does not sag, thereby obstructing combustion air flow.  
Combustion Air and Ventilation for  
Appliances Located in Unconfined Spaces  
UNCONFINED SPACE is space whose volume is not less than  
50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW) of the  
aggregate input rating of all appliances installed in that space.  
Rooms communicating directly with the space in which the  
appliances are installed, through openings not furnished with  
doors, are considered a part of the unconfined space.  
In unconfined spaces in buildings, infiltration may be adequate  
to provide air for combustion, ventilation and dilution of flue  
gases. However, in buildings of tight construction (for example,  
weather stripping, heavily insulated, caulked, vapor barrier, etc.),  
additional air may need to be provided using the methods  
described in Combustion Air and Ventilation for Appliances  
Located in Confined Spaces.  
FIGURE16.  
Insulation Blankets  
Combustion Air and Ventilation for  
Appliances Located in Confined Spaces  
Install water heater in accordance  
with the instruction manual and  
NFPA54.  
To avoid injury, combustion and  
ventilation air must be taken from  
outdoors.  
Do not place chemical vapor  
emitting products near water  
heater.  
CONFINED SPACE is a space whose volume is less than  
50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW) of the  
aggregate input rating of all appliances installed in that space.  
A. ALL AIR FROM INSIDE BUILDINGS:  
(See Figure 9 and 10 on page 11 and Figure 17 below)  
The confined space shall be provided with two permanent  
openings communicating directly with an additional room(s)  
of sufficient volume so that the combined volume of all spaces  
meets the criteria for an unconfined space. The total input of  
all gas utilization equipment installed in the combined space  
shall be considered in making this determination. Each  
opening shall have a minimum free area of one square inch  
per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all  
gas utilization equipment in the confined space, but not less  
than 100 square inches (645 cm2). One opening shall  
commence within 12 inches (30 cm) of the top and one  
commencing within 12 inches (30 cm) of the bottom of the  
enclosures.  
Insulation blankets available to the general public for external  
use on gas water heaters are not necessary with Maytag  
products. The purpose of an insulation blanket is to reduce the  
standby heat loss encountered with storage tank heaters. Your  
Maytag water heater meets or exceeds the National Appliance  
Energy Conservation Act standards with respect to insulation  
and standby loss requirements, making an insulation blanket  
unnecessary.  
Should you choose to apply an insulation blanket to this heater,  
you should follow these instructions (See Figure 7 for  
identification of components mentioned below). Failure to follow  
these instructions can restrict the air flow required for proper  
combustion, potentially resulting in fire, asphyxiation, serious  
personal injury or death.  
Do not apply insulation to the top of the water heater, as this  
will interfere with safe operation of the draft hood.  
Do not cover the outer door, thermostat or temperature &  
pressure relief valve.  
Do not allow insulation to come within 2” (50.8 mm) of the  
floor to prevent blockage of combustion air flow to the burner.  
Do not cover the instruction manual. Keep it on the side of  
the water heater or nearby for future reference.  
Do obtain new warning and instruction labels from Maytag  
for placement on the blanket directly over the existing labels.  
FIGURE17.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. ALL AIR FROM OUTDOORS: (See Figures 18, 19 and 20)  
they connect. The minimum short side dimension of  
rectangular air ducts shall not be less than 3 inches  
(76.2 mm), see Figure 20.  
The confined space shall be provided with two permanent  
openings, one commencing within 12 inches (30 cm) of the  
top and one commencing within 12 inches (30 cm) from the  
bottom of the enclosure. The openings shall communicate  
directly, or by ducts, with the outdoors or spaces (crawl or attic)  
that freely communicate with the outdoors.  
FIGURE20.  
Louvers and Grilles: In calculating free area, consideration  
shall be given to the blocking effect of louvers, grilles or  
screens protecting openings. Screens used shall not be  
smaller than 1/4 inch (6.4 mm) mesh. If the free area through  
a design of louver or grille is known, it should be used in  
calculating the size opening required to provide the free  
area specified. If the design and free area is not known, it  
may be assumed that wood louvers will be 20-25 percent  
free area and metal louvers and grilles will have 60-75  
percent free area. Louvers and grilles shall be fixed in the  
open position or interlocked with the equipment so that they  
are opened automatically during equipment operation.  
FIGURE18.  
When directly communicating with the outdoors, each opening  
shall have a minimum free area of 1 square inch per 4,000 Btu  
per hour (5.5 cm2/kW) of total input rating of all equipment in the  
enclosure, see Figure 18.  
Special Conditions Created by Mechanical Exhausting or  
Fireplaces: operation of exhaust fans, ventilation systems,  
clothes dryers or fireplaces may create conditions requiring  
special attention to avoid unsatisfactory operation of installed  
gas utilization equipment.  
When communicating with the outdoors through vertical  
ducts, each opening shall have a minimum free area of  
1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total  
input rating of all equipment in the enclosure, see  
Figure 19.  
Water Piping  
HOTTER WATER CAN SCALD:  
FIGURE19.  
Water heaters are intended to produce hot water. Water heated  
to a temperature which will satisfy space heating, clothes  
washing, dish washing, cleaning and other sanitizing needs  
can scald and permanently injure you upon contact. Some  
people are more likely to be permanently injured by hot water  
than others. These include the elderly, children, the infirm, or  
physically/mentally handicapped. If anyone using hot water in  
your home fits into one of these groups or if there is a local  
code or state law requiring a certain temperature water at the  
hot water tap, then you must take special precautions. In  
When communicating with the outdoors through horizontal  
ducts, each opening shall have a minimum free area of 1  
square inch per 2,000 BTU per hour (11 cm2/kW) of total  
input rating of all equipment in the enclosure, see  
Figure 20.  
When ducts are used, they shall be of the same cross-  
sectional area as the free area of the openings to which  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
addition to using the lowest possible temperature setting that  
satisfies your hot water needs, a means such as a *mixing  
valve, shall be used at the hot water taps used by these people  
or at the water heater. Mixing valves are available at plumbing  
supply or hardware stores, see Figure 8 on page 9 and Figure  
21 below. Valves for reducing point of use temperature by mixing  
cold and hot water are also available. Consult Maytag  
Customer Service (1-800-788-8899). Follow manufacturer’s  
instructions for installation of the valves. Before changing the  
factory setting on the thermostat, read the Temperature  
Regulation section in this manual.  
Figure 22 shows the typical attachment of the water piping to  
the water heater. The water heater is equipped with 3/4” NPT  
water connections for 40,000 Btuh models and 1 inch water  
connections for 70,000 and 75,000 Btuh models.  
NOTE: If using copper tubing, solder tubing to an adapter  
before attaching the adapter to the cold water inlet  
connection. Do not solder the cold water supply line directly  
to the cold water inlet. It will harm the dip tube and damage  
the tank.  
Look at the top cover of the water heater. The water outlet is  
marked “HOT”. Connect the hot water pipe to the hot water  
outlet on the water heater.  
See Figure 21 for mixing valve usage.  
Look at the top of the water heater. The cold water inlet is  
marked “COLD”. Connect the cold water pipe to the cold  
water inlet of the water heater.  
NOTE: This water heater is super insulated to minimize  
heat loss from the tank. Further reduction in heat loss  
can be accomplished by insulating the hot water lines  
from the water heater.  
FIGURE21.  
This water heater shall not be connected to any heating systems  
or component(s) used with a non-potable water heating  
appliance.  
If a water heater installed in a closed water supply system;  
such as one having a back-flow preventer, check valve, water  
meter with a check valve, etc. . . in the cold water supply; means  
shall be provided to control thermal expansion. Contact the  
local utility or call Maytag Customer Service Center at  
1-800-788-8899 for an authorized installer on how to control  
this situation.  
FIGURE22.  
T & P Valve and Pipe Insulation  
Remove insulation for T & P valve and pipe connections from  
carton.  
Fit pipe insulation over the incoming cold water line and the hot  
water line. Make sure that the insulation is against the top  
cover of the heater.  
NOTE: To protect against untimely corrosion of hot and cold  
water fittings, it is strongly recommended that di-electric  
unions or couplings be installed on this water heater when  
connected to copper pipe.  
Fit T & P valve insulation over valve. Make sure that the insulation  
does not interfere with the lever of the T & P valve.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Secure all insulation using tape.  
must not be blocked or reduced in size under any  
circumstances. Excessive length, over 30 feet (9.14 m), or use  
of more than four elbows can cause restriction and reduce the  
discharge capacity of the valve, see Figure 24.  
No valve or other obstruction is to be placed between the relief  
valve and the tank. Do not connect tubing directly to discharge  
drain unless a 6 inch air gap is provided. To prevent bodily  
injury, hazard to life, or property damage, the relief valve must  
be allowed to discharge water in quantities should  
circumstances demand. If the discharge pipe is not connected  
to a drain or other suitable means, the water flow may cause  
property damage.  
FIGURE 23.  
Temperature-Pressure Relief Valve  
Temperature-pressure relief valve  
must comply with ANSI Z21.22  
and ASME code.  
• Properly sized temperature-relief  
valve must be installed in opening  
provided.  
• Can result in overheating and  
excessive tank pressure.  
• Can cause serious injury or death.  
This heater is provided with a properly certified combination  
temperature - pressure relief valve by the manufacturer.  
FIGURE24.  
The valve is certified by a nationally recognized testing  
laboratory that maintains periodic inspection of production of  
listed equipment of materials as meeting the requirements for  
Relief Valves andAutomatic Gas Shut-off Devices for Hot Water  
Supply Systems, ANSI Z21.22 and the code requirements of  
ASME.  
If replaced, the valve must meet the requirements of local  
codes, but not less than a combination temperature and  
pressure relief valve certified as indicated in the above  
paragraph.  
The Discharge Pipe:  
The valve must be marked with a maximum set pressure not to  
exceed the marked hydrostatic working pressure of the water  
heater (150 psi = 1,035 kPa) and a discharge capacity not less  
than the water heater input rate as shown on the model rating  
plate.  
• Shall not be smaller in size than the outlet pipe size of the  
valve, or have any reducing couplings or other restrictions.  
• Shall not be plugged or blocked.  
• Shall be of material listed for hot water distribution.  
For safe operation of the water heater, the relief valve must not  
be removed from its designated opening nor plugged.  
• Shall be installed so as to allow complete drainage of both  
the temperature-pressure relief valve, and the discharge  
pipe.  
The temperature-pressure relief valve must be installed directly  
into the fitting of the water heater designed for the relief valve.  
Position the valve downward and provide tubing so that any  
discharge will exit only within 6 inches (153 mm) above, or at  
any distance below the structural floor. Be certain that no contact  
is made with any live electrical part. The discharge opening  
• Shall terminate at an adequate drain.  
• Shall not have any valve between the relief valve and tank.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
USEWITHPOWERCORD  
The water heater comes equipped with a 7 foot power cord  
which can be used to connect to a 110/120 volt power source if,  
(1) local codes allow, and (2) there is a three prong grounded  
receptacle available. This unit must have a grounded outlet to  
operate.  
The temperature-pressure relief valve must be manually  
operated at least once a year. Caution should be taken to  
ensure that (1) no one is in front of or around the outlet of the  
temperature-pressure relief valve discharge line, and (2) the  
water manually discharged will not cause any bodily injury or  
property damage because the water may be extremely hot.  
If after manually operating the valve, it fails to completely reset  
and continues to release water, immediately close the cold  
water inlet to the water heater, follow the draining instructions,  
and replace the temperature-pressure relief valve with a new  
one.  
FIGURE25.  
Filling the Water Heater  
You must provide all wiring, (1) to a receptacle or, (2) between  
the water heater and junction box when power cord is not used.  
Do not use an extension cord. If there is not a suitable  
receptacle and/or local codes prohibit use of a power cord,  
field wiring must be provided.  
If you are not familiar with electric codes and practices, or if you  
have any doubt in your ability to connect the wiring to this water  
heater, obtain the service of a competent electrician or contact  
your local electric utility.  
Never use this water heater unless it is completely full of water.  
To prevent damage to the tank, the tank must be filled with  
water. Water must flow from the hot water faucet before turning  
“ON” gas to the water heater.  
To fill the water heater with water:  
Close the water heater drain valve by turning the handle to  
the right (clockwise). The drain valve is on the lower front of  
the water heater.  
Open the cold water supply valve to the water heater.  
NOTE: The cold water supply valve must be left open when  
the water heater is in use.  
To insure complete filling of the tank, allow air to exit by  
opening the nearest hot water faucet. Allow water to run  
until a constant flow is obtained. This will let air out of the  
water heater and the piping.  
If wiring from the fuse box or circuit breaker box was aluminum  
for the old water heater, replace it with copper wire. If you wish  
to reuse the existing aluminum wire, have the connection at  
the water heater made by competent electrician. Contact a local  
electrical contractor and/or the local electric utility.  
Check all water piping and connections for leaks. Repair  
as needed.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
USE WITHOUT POWER CORD  
If power cord cannot be used, then follow these wiring  
instructions.  
Provide a way to easily shut off the electric power when  
working on the water heater. This could be with a circuit  
breaker or fuse block in the entrance box or a separate  
disconnect switch.  
Install and connect a circuit directly from the main fuse or  
circuit breaker box. This circuit must be the right size and  
have its own fuse or circuit breaker.  
A standard 1/2” conduit opening has been made in the water  
heater junction box for the conduit connection.  
Use wire nuts and connect the power supply wiring to the  
wires inside the water heater’s junction box.  
The water heater must be electrically “grounded” by the  
installer. The unit will not operate unless it is properly  
grounded. A green ground screw has been provided on the  
water heater’s junction box. Connect ground wire to this  
location. For complete grounding details and all allowable  
exceptions, refer to the current edition of the National  
Electrical Code, ANSI/NFPA 70.  
FIGURE26.  
Wiring Diagram  
NOTE: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING  
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS  
OPERATION. VERIFYPROPER OPERATIONAFTER SERVICING.  
FIGURE27.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Horizontal runs must be securely supported at 3 1/2” foot  
intervals and vertical runs supported at 5 foot intervals.  
Venting  
To insure proper venting of this gas-fired water heater, the  
correct vent pipe diameter must be utilized. Do not install other  
gas appliances on the same vent with this water heater as this  
will adversely affect the operation on the water heater.  
The combustion and ventilation air flow must not be obstructed.  
FIGURE29.  
VENTING THROUGHAN OUTSIDE WALL:  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY  
(See rating plate for BTU/HR rating)  
3” PVC, ABS or CPVC Schedule 40 vent piping:  
• A 3” PVC Schedule 40-45o vent cap with wire screen is  
supplied with the water heater.  
A 3” PVC, ABS or CPVC Schedule 40-90o street ell; used to  
connect the vent pipe to the water heater when the vent pipe  
is to be turned horizontally directly off the blower (supplied  
locally).  
The power vent water heater requires its own (separate) venting  
system. It cannot be connected to an existing vent pipe or  
chimney. It must be terminated to the outdoors. Failure to  
properly install the venting system can result in asphyxiation, a  
fire or explosion and cause DEATH, SERIOUS BODILY INJURY,  
OR PROPERTY DAMAGE.  
3” PVC, ABS or CPVC Schedule 40 pipe (must be supplied  
locally).  
The vent pipe from the water heater must slope upward 1/8”  
per five feet for any horizontal run.  
All vent gases must be completely vented to the outdoors of the  
structure (dwelling).  
FIGURE30.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY  
• The water heater requires its own (separate) venting  
system.  
FIGURE28.  
3” PVC, ABS or CPVC Schedule 40 piping and fittings are  
acceptable materials for the vent system on all 75 gallon  
70,000 and 75,000 BTU/HR models.  
Chemical vapor corrosion of the flue and vent system may  
occur. If air for combustion contains certain chemical vapors.  
Spray can propellants, cleaning solvents, refrigerator and air  
conditioner refrigerants, swimming pool chemicals, calcium  
and sodium chloride, waxes, bleach and process chemicals  
are typical compounds which are potentially corrosive.  
It cannot be connected to existing vent piping or chimney.  
It must terminate horizontally to the outdoors.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75 GALLON 70,000 AND 75,000 BTU/HR MODELS ONLY -  
OPTIONAL 4” VENT PIPING  
4” PVC, ABS or CPVC Schedule 40 vent piping:  
Awire screen to fit a 4” PCV,ABS or CPVC Schedule 40 - 45o  
vent cap is supplied with the water heater.  
A4” PVC,ABS or CPVC Schedule 40 - 45o vent cap (must be  
supplied locally).  
FIGURE32.  
A 3” PVC, ABS or CPVC Schedule 40 pipe, minimum length  
of 3” (must be supplied locally), to make vent connection at  
the blower outlet.  
The water heater requires its own (separate) venting  
system.  
3” PVC, ABS or CPVC Schedule 40 piping and fittings are  
acceptable materials for the vent system on all 40 and 50  
gallon 40,000 BTU/HR models.  
A 4” to 3” PVC, ABS or CPVC Schedule 40 reducer (must be  
supplied locally).  
A 4” PVC, ABS or CPVC Schedule 40 - 90o street ell; used to  
connect the vent pipe to the reducer when the vent pipe is to  
be turned horizontally off the blower (supplied locally).  
It cannot be connected to existing vent piping or chimney.  
It must terminate horizontally to the outdoors.  
4” PVC, ABS or CPVC Schedule 40 pipe (must be supplied  
locally).  
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS - OPTIONAL  
2” VENT PIPING  
2” PVC, ABS or CPVC Schedule 40 vent piping:  
Awire screen to fit a 2” PCV, ABS or CPVC Schedule 40 - 45o  
vent cap is supplied with the water heater.  
A 2” PVC, ABS or CPVC Schedule 40 - 45o vent cap (elbow)  
(must be supplied locally).  
A 3” PVC, ABS or CPVC Schedule 40 pipe, minimum length  
of 3” (must be supplied locally), to make vent connection at  
the blower outlet.  
FIGURE31.  
A 3” to 2” PVC, ABS or CPVC Schedule 40 reducer (must be  
supplied locally).  
• The water heater requires its own (separate) venting  
system.  
A 2” PVC, ABS or CPVC Schedule 40 - 90o street ell; used to  
connect the vent pipe to the reducer when the vent pipe is to  
be turned horizontally off the blower (supplied locally).  
4” and 3” PVC, ABS or CPVC Schedule 40 piping and fittings  
are acceptable materials for the vent system on all 75 gallon  
70,000 and 75,000 BTU/HR models.  
2” PVC, ABS or CPVC Schedule 40 pipe (must be supplied  
locally).  
It cannot be connected to existing vent piping or chimney.  
It must terminate horizontally to the outdoors.  
ALL 40AND 50 GALLON 40,000 BTU/HR MODELS ONLY  
3” PVC, ABS or CPVC Schedule 40 vent piping:  
A 3” PVC Schedule 40 - 45o vent cap with wire screen is  
supplied with the water heater.  
A 3” PVC, ABS or CPVC Schedule 40 - 90o street ell; used to  
connect the vent pipe to the water heater when the vent pipe  
is to be turned horizontally directly off the blower (supplied  
locally).  
3” PVC, ABS or CPVC Schedule 40 pipe (must be supplied  
locally).  
FIGURE33.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The water heater requires its own (separate) venting  
system.  
2” and 3” PVC, ABS or CPVC Schedule 40 piping and fittings  
are acceptable materials for the vent system on all 40 and  
50 gallon 40,000 BTU/HR models.  
It cannot be connected to existing vent piping or chimney.  
It must terminate horizontally to the outdoors.  
NOTE: See pages 24 and 25 for vertical venting through the  
roof.  
VENTING SYSTEM EXAMPLE INSTALLATIONS  
FOR ALL MODELS  
The vent piping cannot under any circumstances be run down  
hill.  
FIGURE36.  
FIGURE34.  
The vent piping may be installed as follows:  
Horizontal runs require a minimum 1/8” rise per five feet  
FIGURE37.  
75 GALLON 70,000 AND 75,000 BTU/HR MODELS  
See chart on following page for maximum length.  
FIGURE38.  
FIGURE35.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40 AND 50 GALLON 40,000 BTU/HR MODELS  
See Chart below for maximum length.  
FIGURE39.  
The total vertical and horizontal vent run cannot exceed the  
maximum length with the number of 90o elbows as specified  
in the following tables. If more are required the venting  
distance must be reduced 5 feet for every 90o elbow.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY  
3” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
FIGURE40.  
70  
65  
60  
55  
50  
45  
1
2
3
4
5
6
Minimum vent length for all 40,000 BTU/HR input models is  
4 feet and 16 inches for all other models.  
VENTING THROUGHAN OUTSIDE WALLWITH LOW GROUND  
CLEARANCE  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY -  
OPTIONAL 4” VENT PIPING  
When the venting piping cannot pass through an outside  
wall at a height greater than or equal to 12” above the ground  
(or above snow accumulation level), then the installation  
can be modified as shown below.  
4” DIA. VENT  
NUMBEROF  
MAX. LENGTH (FT.)  
90o ELBOWS*  
110  
105  
100  
95  
90  
85  
1
2
3
4
5
6
ALL 40AND 50 GALLON 40,000 BTH/HR MODELS ONLY  
3” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
115  
110  
105  
100  
95  
1
2
3
4
5
6
90  
ALL40 AND 50 GALLON 40,000 BTH/HR MODELS ONLY -  
OPTIONAL 2” VENT PIPING  
2” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
50  
45  
40  
35  
30  
25  
1
2
3
4
5
6
FIGURE41.  
Refer to the tables on page 23 for maximum vent lengths for  
low ground clearance installations. All installations assume  
the use of two additional 90 elbows and the standard 45o  
vent cap with screen outside of the exterior wall.  
* Two 45o elbows are equivalent to one 90o elbow.  
One 90o elbow equals 5 feet of equivalent vent length.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY  
Primer, cleaner and cements are extremely flammable. They  
are harmful or fatal if swallowed. The vapors are harmful They  
may irritate eyes and skin and can be absorbed through the  
skin.  
3” DIA. VENT  
NUMBEROF  
MAX. LENGTH (FT.)  
90 ELBOWS*(Inside bldg.)  
60  
55  
50  
45  
40  
35  
1
2
3
4
5
6
Always store primers, cleaners and cements in cool, dry, well  
ventilated places. Do not store them near heat, sparks or flames.  
Keep containers closed. Use them in well ventilated areas.  
Wear impervious clothing while handling. Do not smoke, eat  
or drink while handling. Wash thoroughly after handling and  
before eating. Wear eye protection when handling. If swallowed,  
drink water, do not induce vomiting, and call a physician or  
poison control center immediately. If inhaled, get fresh air and  
seek medical attention if ill feeling persists. In case of eye and  
skin contact, immediately flush with plenty of water for 15  
minutes and seek medical attention if irritation persists. KEEP  
OUT AND REACH OF CHILDREN.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY -  
OPTIONAL 4” VENT PIPING  
4” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*(Inside bldg.)  
100  
95  
90  
85  
80  
75  
1
2
3
4
5
6
All primers, cleaners and cements must meet all local codes  
and applicable standards of the American Society for Testing  
Materials Standards.  
Before using primers, cleaners and cements, stir or shake,  
making sure contents of liquid. Do not use if found to be lumpy  
or jelly-like.  
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS  
1. Cut pipe ends squarely removing all burrs and dirt.  
2. Dry fit pipe and fittings to be connected for proper fit.  
3. Clean pipe and fitting with a primer/cleaner.  
3” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*(Inside bldg.)  
105  
100  
95  
90  
85  
1
2
3
4
5
6
4. Apply a thin coat of cement to fitting, avoiding puddling inside.  
5. Apply a liberal coat of cement to pipe leaving no voids  
80  
6. QUICKLY assemble parts while cement is fluid! If you wait  
too long, re-coat pipes.  
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS -  
OPTIONAL 2” VENT PIPING  
7. Push pipe completely into socket of fitting, turning as it goes  
until it bottoms.  
2” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*(Inside bldg.)  
8. Hold pipe and fitting together for 30 seconds. Then carefully  
clean off excess with a cloth. Allow connections a sufficient  
time to cure before disturbing.  
40  
35  
30  
25  
20  
15  
1
2
3
4
5
6
9. Remember that vent pipes must be adequately and securely  
supported.  
APPROXIMATE SETTING TIME FOR  
2 1/2” TO 4” PIPE JOINTS  
* Two 45o elbows are equivalent to one 90o elbow.  
One 90o elbow equals 5 feet of equivalent vent length.  
MOVEMENT  
OF JOINTS  
3/4 HR.  
1 HR.  
1 1/3 HR.  
COMPLETE  
SET  
8 HRS.  
15 HRS.  
18 HRS.  
CEMENTING PVC, ABS OR CPVC PIPE AND FITTINGS  
90o F TO 150o F  
50o F TO 90o F  
0o F TO 50o F  
Read and observe all safety information printed on primer,  
cleaner and cement containers.  
CUTTING OPENING THROUGH AN OUTSIDE WALL AND  
COLLAR INSTALLATION  
After reading the manual and you have determined the location  
of the opening in the wall, (using the drawing below), cut a  
2 1/2” hole for 2” vent piping, 3 1/2” hole for 3” vent piping or a  
4 1/2” hole for 4” vent piping through an exterior wall.  
NOTE: When determining location of the opening in the  
outside wall allow for the 1/8” rise per five feet that has  
taken place in the horizontal run.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE44.  
If there is to be a vertical run of vent from blower, the 3” PVC,  
ABS or CPVC pipe must be attached to the blower using  
3 sheet metal screws.  
FIGURE42.  
FIGURE45.  
The 3” )or optional 2” or 4”) PVC, ABS or CPVC Schedule 40  
vent pipe can be run from the water heater through the wall or  
from the wall to the water heater, whichever is most convenient.  
The vent pipe must extend a minimum of 1 1/2” through the  
exterior wall. Extending the vent cap as far as possible from the  
surface of the exterior wall will help minimize discoloration of  
the wall in this area which may be caused by the flue gases.  
If the optional 2” vent piping is to be used (40,000 BTU/HR.  
models only), the 2” street elbow, 3” to 2” reducer and  
3” (minimum) section of 3” PVC, ABS or CPVC pipe must be  
supplied locally. The 3” (minimum) section of 3” PVC, ABS  
or CPVC pipe must be attached to the blower using 3 sheet  
metal screws,  
NOTE: that the inside collar must be slipped over the vent  
piping before locating the pipe through the wall. Before  
securing the inside and outside collars to the wall, use a  
silicone sealer between pipe and opening to insure a water  
and air tight seal.  
If the optional 4” vent piping is to be used (70,000 BTU/HR.  
and higher models only), the 4” street elbow, 4” to 3” reducer  
and 3” minimum section of 3” PVC, ABS or CPVC pipe must  
be supplied locally. The 3” (minimum) section of 3” PVC,  
ABS or CPVC pipe must be attached to the blower using  
3 sheet metal screws.  
INSTALLATION SHOWING USE OF PVC, ABS OR CPVC PIPE  
VENTING THROUGH A ROOF - ALL MODELS  
3” PVC, ABS or CPVC Schedule 40 vent piping:  
A 3” PVC Schedule 40 - 45o vent cap with wire screen is  
supplied with the water heater.  
3” PVC, ABS or CPVC Schedule 40 piping and fittings are  
acceptable materials for the vent system on all models and  
must be supplied locally.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY -  
OPTIONAL 4” VENT PIPING  
A wiring screen to fit a 4” PVC, ABS or CPVC Schedule  
40 - 45o vent cap is supplied with the water heater.  
FIGURE43.  
A 3” PVC, ABS or CPVC Schedule 40 pipe, minimum length  
of 3” (must be supplied locally), to make vent connection at  
the blower outlet.  
CONNECTING PVC, ABS OR CPVC PIPE VENT TO BLOWER  
If making an immediate horizontal run of vent off the blower,  
a 3” PVC, ABS or CPVC Schedule 40 (supplied locally) elbow  
is required. Place the elbow in the required direction on the  
blower and using 3 sheet metal screws, attach the elbow.  
A 4” to 3” PVC, ABS or CPVC Schedule 40 reducer (must be  
supplied locally).  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4” and 3” PVC, ABS or CPVC Schedule 40 piping and fittings  
are acceptable materials for vent system on all 75 gallon  
70,000 and 75,000 BTU/HR models and must be supplied  
locally.  
FIGURE46.  
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS -  
OPTIONAL 2” VENT PIPING  
2” PVC, ABS or CPVC Schedule 40 vent piping:  
A wire screen to fit 2” PVC, ABS or CPVC Schedule 40 - 45o  
vent cap is supplied with the water heater.  
A 3” PVC, ABS or CPVC Schedule 40 pipe, minimum length  
of 3” (must be supplied locally), to make vent connection at  
the blower outlet.  
FIGURE48.  
The total vertical and horizontal vent runs cannot exceed the  
maximum length with the number of 90o elbows as specified  
in the tables to follow. If more elbows are required, the venting  
distance must be reduced 5 feet for every 90o elbow.  
A 3” to 2” PVC, ABS or CPVC Schedule 40 reducer (must be  
supplied locally).  
2” and 3” PVC, ABS or CPVC Schedule 40 piping and fittings  
are acceptable materials for the vent system on all 40 and  
50 gallon 40,000 BTU/HR models and must be supplied  
locally.  
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY  
3” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
70  
65  
60  
55  
50  
45  
1
2
3
4
5
6
75 GALLON 70,000AND 75,000 BTU/HR MODELS ONLY -  
OPTIONAL 4” VENT PIPING  
4” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
110  
105  
100  
95  
90  
85  
1
2
3
4
5
6
FIGURE47.  
The water heater requires its own (separate) venting  
system.  
ALL40AND 50 GALLON 40,000 BTH/HR MODELS ONLY  
It cannot be connected to existing vent piping or chimney.  
It must terminate vertically to the outdoors.  
Typical installation(s) in next column.  
3” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
115  
110  
105  
100  
95  
1
2
3
4
5
6
Refer to “Cementing PVC, ABS or CPVC pipe and fittings”  
on page 23 and “Connecting Vent to Blower” on page 24.  
90  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALL40 AND 50 GALLON 40,000 BTH/HR MODELS ONLY -  
OPTIONAL 2” VENT PIPING  
The minimum inlet gas pressure shown on the rating plate is  
that which will permit firing at the rated input.  
2” DIA. VENT  
MAX. LENGTH (FT.)  
NUMBEROF  
90o ELBOWS*  
50  
45  
40  
35  
30  
25  
1
2
3
4
5
6
* Two 45o elbows are equivalent to one 90o elbow.  
One 90o elbow equals 5 feet of equivalent vent length.  
Gas Piping  
If a standard model is installed above 3,300 feet (1,006 m) or a  
high altitude model is installed above 5,500 feet (1,676 m) the  
input rating should be reduced at the rate of 4 percent for each  
1,000 feet (305 m ) above sea level which requires replacement  
of the burner orifice in accordance with National Fuel Gas Code  
ANSI Z223.1/NFPA 54. Contact Maytag Customer Service  
Center at 1-800-788-8899 or your local gas supplier or call  
for further information.  
Failure to replace the standard orifice with a high altitude orifice  
when installed at elevations above 3,300 feet (1,006 m) or  
above 5,500 feet (1,676 m) for high altitude model could result  
in improper and inefficient operation of the appliance, producing  
carbon monoxide gas in excess of safe limits, which could  
result in serious injury or death. Contact Maytag Customer  
Service at 1-800-788-8899 or your local gas supplier for any  
specific changes which may be required in your area.  
Make sure the gas supplied is the same type listed on the  
model rating plate. The inlet gas pressure must not exceed  
14 inch water column (2.6kPa) for natural and propane (L.P.)  
gas. The minimum inlet gas pressure listed on the rating  
plate is for the purpose of input adjustment. If the gas control  
valve is subjected to pressures exceeding 1/2 pound per square  
inch (3.5kPa), the damage to the gas control valve could result  
in a fire or explosion from leaking gas.  
If the main gas line Shut-off serving all gas appliances is used,  
also turn “OFF” the gas at each appliance. Leave all gas  
appliances shut “OFF” until the water heater installation is  
complete.  
A gas line of sufficient size must be run to the water heater.  
Consult the current edition of National Fuel Gas Code ANSI  
Z223.1/NFPA 54 and your gas supplier concerning pipe size.  
Use pipe joint compound or teflon tape marked as being  
resistant to the action of petroleum (Propane [L.P.]) gases.  
There must be:  
The appliance and its gas connection must be leak tested  
before placing the appliance in operation.  
A readily accessible manual shut off valve in the gas supply  
line serving the water heater, and  
The appliance and its individual Shut-off valve shall be  
disconnected from the gas supply piping system during any  
pressure testing of that system at test pressures in excess of  
1/2 pound per square inch (3.5kPa). It shall be isolated from  
the gas supply piping system by closing its individual manual  
Shut-off valve during any pressure testing of the gas supply  
piping system at test pressures equal to or less than 1/2 pound  
per square inch (3.5kPa).  
A drip leg (sediment trap) ahead of the gas control valve to  
help prevent dirt and foreign materials from entering the  
gas control valve.  
A flexible gas connector or a ground joint union between the  
shut off valve and control valve to permit servicing of the unit.  
Be sure to check all the gas piping for leaks before lighting the  
water heater. Use a soapy water solution, not a match or open  
flame. Rinse off soapy solution and wipe dry.  
Connecting the gas piping to the gas control valve of the water  
heater can be accomplished by either of the two methods,  
shown in Figures 49 and 50.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
of the gas control valve that may result in fire or explosion.  
Before attaching the gas line be sure that all gas pipe is clean  
on the inside. To trap any dirt or foreign material in the gas  
supply line, a drip leg (sometimes called a sediment trap)  
must be incorporated in the piping. The drip leg must be readily  
accessible. Install in accordance with the Gas Piping section.  
Refer to the current edition of the National Fuel Gas Code,  
ANSI Z223.1/NFPA54.  
Sediment Traps  
A sediment trap shall be installed as close to the inlet of the  
water heater as practical at the time of water heater installation.  
The sediment trap shall be either a tee fitting with a capped  
nipple in the bottom outlet or other device recognized as an  
effective sediment trap. If a tee fitting is used, it shall be installed  
in conformance with one of the methods of installation, shown  
in Figures 49 and 50.  
Contaminants in the gas lines may cause improper operation  
FIGURE 50. GAS PIPING WITH ALL  
BLACK IRON PIPE TO GAS CONTROL.  
FIGURE49. GASPIPINGWITHFLEXIBLECONNECTOR.  
CHECKFORLEAKS  
Be sure to check all your gas pipes for leaks before operating your water heater. Use a soapy water solution, not a match or open  
flame. Check the factory gas fittings after the main burner is turned “ON”. Use a soapy water solution for this, too.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
This water heater is equipped with an electronically operated  
3. The venting manual reset switch must be in the closed  
position. See “Venting Manual Reset Switch” in the  
“Troubleshooting” section.  
venting system and electronic control. For the burner to come  
on, the water heater thermostat must call for heat. Then the  
system will begin sequencing, each section proving itself before  
gas is allowed to flow to the burner.  
4. There is a non-resettable hi-limit switch in the thermostat,  
which must be good (closed) for the thermostat to be  
operated. See “High Temperature Limit Switch” in the  
“Troubleshooting” section.  
BEFORE THE WATER HEATER WILLOPERATE:  
1. The control system must be connected to a grounded 110/  
120 volt power supply. The control system has an overall  
rating of 2 amps. The water heater must be securely and  
adequately grounded in accordance with local codes and  
with the current edition of the National Electrical Code ANSI/  
NFPA70.  
OPERATION  
When the thermostat calls for heat, gas is allowed to flow to a  
(N/O) pressure switch closing it. An electrical circuit is then  
made to the blower, turning it on. When the blower has achieved  
sufficient venting, the air pressure switch will close. A 120 volt  
circuit will be completed through the venting manual reset switch  
and on the 120 volt gas valve. The 120 volt gas valve will open  
allowing gas to flow to the burner. The hot surface ignitor will  
establish a main burner flame.  
2. The ON/OFF rocker switch, located on the control box above  
the thermostat must be in the “ON” position for the electrical  
control system to operate allowing the gas portion to operate  
(ignite burner).  
OR  
FIGURE51.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Cycle is completed.  
Operating  
CONTROLSEQUENCE - HOT SURFACE DIRECT IGNITION  
Pre-purge  
5 sec.  
HSI Warm-Up  
20 sec.  
4 sec.  
1 sec.  
4 sec.  
5 sec.  
5 sec.  
2
Ignition Activation Period  
Flame Recognition Period  
Ignition Trial  
Interpurge  
Post-purge  
Retries  
Reset from lockout  
Flame Sensing (Nominal)  
HSI Off/Run Mode  
1 hr.  
4.0 µ VDC  
Propane gas is heavier than air. Should there be a leak in the  
system, the gas will settle near the ground. Basements, crawl  
spaces, skirted areas under manufactured (mobile) homes  
(even when ventilated), closets and areas below ground level  
will serve as pockets for the accumulated gas in the area.  
Search for odor of gas by sniffing at ground level in the vicinity  
of the appliance. If odor is detected, follow steps indicated at  
“For Your Safety” on the cover of this manual then leave the  
premises.  
Temperature Regulation  
Short repeated heating cycles caused by small hot water uses  
can cause temperatures at the point of use to exceed the  
thermostat by up to 30oF. If you experience this type of use you  
should consider using lower temperature settings to reduce  
scald hazards.  
Any water heater’s intended purpose is to heat water. Hot  
water is needed for cleansing, cleaning, and sanitizing (bodies,  
dishes, clothing). Untempered hot water can present a scald  
hazard. Depending on the time element, and the people  
involved (adults, children, elderly, infirm, etc.) scalding may occur  
at different temperatures.  
Operating instructions are located on front of the water heater,  
above or to the side of the gas control valve, see page 30.  
CHECKFORLEAKS  
Be sure to check all your gas pipes for leaks before operating  
your water heater. Use a soapy water solution, not a match or  
open flame. Check the factory gas fittings when the main burner  
is turned “ON”.  
WATERHEATINGIGNITIONSEQUENCE  
(Make sure gas and electric power are connected properly)  
1. The ignition control module is powered and monitors the  
system, waiting for a call for heat from the thermostat.  
2. The thermostat calls for heat by reading a resistance value  
within a given range directly proportional to water  
temperature.  
3. The control module:  
a. Checks the pressure switch for an open circuit.  
b. Energizes the blower.  
HOTTER WATER CAN SCALD: Water heaters are intended to  
produce hot water. Water heated to a temperature which will  
satisfy space heating, clothes washing, dish washing, and  
other sanitizing needs can scald and permanently injure you  
upon contact. Some people are more likely to be permanently  
injured by hot water than others. These include the elderly,  
children, the infirm, or physically/mentally handicapped. If  
anyone using hot water in your home fits into one of these  
groups or if there is a local code or state law requiring a certain  
temperature water at the hot water tap, then you must take  
special precautions. In addition to using the lowest possible  
temperature setting that satisfies your hot water needs, a  
means such as a mixing valve, shall be used at the hot water  
taps used by these people or at the water heater. Mixing valves  
are available at plumbing supply or hardware stores, see  
Figure 8 on page 9 and Figure 21 on page 15. Valves for  
reducing point of use temperature by mixing cold and hot water  
c. Checks the pressure switch for a closed circuit to prove  
draft.  
d. Sends line voltage to the hot surface igniter with a  
20-second warm up period.  
e. Opens the gas valve and checks the sensing rod for flame.  
4. The burner heats the water to the desired thermostat setting.  
a. The resistance in the thermostat rises to the value  
selected by the temperature control knob.  
b. The control module closes the gas valve and 5 seconds  
later, removes power from the blower.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b.To increase the temperature press and release the  
“HOTTER” button until the desired setting is reached.  
are also available. Consult Maytag Customer Service  
(1-800-788-8899). Follow manufacturer’s instructions for  
installation of the valves. Before changing the factory setting  
on the thermostat, read the Temperature Regulation section in  
this manual, see Figure 52.  
NOTE: Holding down the button will not continue to lower or  
raise the temperature setting. The button must be pressed  
and released for each temperature change desired.  
Never allow small children to use a hot water tap, or to draw  
their own bath water. Never leave a child or handicapped person  
unattended in a bathtub or shower.  
NOTE: Awater temperature range of 120°F-140°F (49°C-60°C)  
is recommended by most dishwasher manufacturers.  
The thermostat of this water heater has been factory set at its  
lowest position, to reduce the risk of scald injury. It is adjustable  
and must be reset to the desired temperature setting. The  
mark ( ) HOT indicative of approximately 120°F (49°C) is  
preferred starting point. Some states have a requirement for a  
lower setting. If you need hotter water, follow directions for  
temperature adjustment, but beware of the warnings in this  
section.  
Pressing the “COOLER”  
pressing the “HOTTER”  
button decreases temperature and  
button increases the temperatures.  
Should overheating occur or the gas supply fail to shut off, turn  
off the manual gas control valve to the appliance.  
Time to Produce  
Display  
2nd & 3rd Degree  
To avoid any unintentional changes in water temperature  
settings, the control has a tamper resistant feature for changing  
the temperature setting. To change the temperature setting  
follow these instructions:  
Temperature Setting  
A B C Burns on Adult Skin  
C = Flashing = approx. 160°F  
C = Approx. 150°F  
About 1/2 seconds  
About 1 1/2 seconds  
Less than 5 seconds  
About 30 seconds  
More than 5 minutes  
- - - - - - - - - - - - - -  
B = Approx. 140°F  
1. “Wake Up” the temperature indicators by holding down both  
“COOLER” and “HOTTER” temperature adjustment buttons  
at the same time for one second, see Figure 49. One or two  
of the temperature indicators will light up. These indicators  
will only remain on for 30 seconds if no further buttons are  
pressed. After 30 seconds the control will go back to “Sleep”  
mode.  
A = Approx. 130°F  
= Approx. 120°F  
WARM = Approx. 80°F  
FIGURE52.  
NOTE: Water temperature range of 120oF-140oF  
recommended by most dishwasher manufacturers.  
2. Release both temperature adjustment buttons.  
Should overheating occur or the gas supply fail to shut off,  
turn “OFF” the manual gas control valve to the appliance.  
a.To decrease the temperature press and release the  
“COOLER” button until the desired setting is reached.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal injury or loss of life.  
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATERANDAIR PURGED FROM ALL LINES.  
A. This appliance does not have a pilot. It is equipped with  
an ignition device which automatically lights the burner.  
Do NOT try to light the burner by hand.  
B. BEFORE LIGHTING smell all around the appliance area  
for gas. Be sure to smell next to the floor because some  
gas is heavier than air and will settle on the floor.  
WHAT TO DO IFYOU SMELL GAS:  
If you cannot reach your gas supplier, call the fire  
department.  
C. Use only your hand to push in or turn the gas control  
button. Never use tools. If the control button will not push  
in, don’t try to repair them, call a qualified service  
technician . Force or attempted repair may result in a fire  
or explosion.  
Do not try to light any appliance.  
Do not touch any electric switch; do not use any phone  
in your building.  
D. Do not use this appliance if any part has been under  
water. Immediately contact a qualified installer or service  
agnecy to replace a flooded water heater. Do not attempt  
to repair the unit! It must be replaced!  
Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas supplier’s instructions.  
LIGHTING INSTRUCTIONS  
5. The appliance is equipped with a device which automatically  
lights the burner.  
DONOTTRYTOLIGHTTHEBURNERBYHAND.  
6. Wait five (5) minutes to clear out any gas. If you then smell  
gas, STOP! Follow “B” in the safety information above  
on this label. If you don’t smell gas, go to next step.  
7. Turn on all electrical power to the appliance.  
8. Set the ON/OFF switch on the control box to the “ON”  
position.  
9. Set the thermostat to desired setting by first pressing the  
COOLER and HOTTER buttons together and holding  
for 1 second. Then press the HOTTER button.  
1.  
STOP! Read the safety information above on  
this label.  
10. WATERTEMPERATUREADJUSTMENT isapproximately  
120oF.  
2. Set the ON/OFF switch on the control box to the “ON”  
position.  
CAUTION: Hotter water increases the risk of  
scald injury. Consult the instructions manual  
before changing temperature.  
3. Set the thermostat to the lowest setting by first pressing  
theCOOLER andHOTTER buttonstogetherandholding  
for 1 second. Then press the COOLER button until the  
WARM indicator light appears.  
11. If the appliance will not operate, follow the instructions “TO  
TURN OFF GASTOAPPLIANCE” and call your technician or  
gas supplier.  
4. Set the ON/OFF switch on the control box to the “OFF”  
position.  
WARNING: TURN OFF ALL ELECTRIC POWER  
BEFORESERVICING.  
TO TURN OFF GAS TOAPPLIANCE  
2. Set the ON/OFF switch on the control box to the “OFF”  
position.  
1. Set thermostat to the lowest setting by first pressing  
the COOLER and HOTTER buttons together and  
holding for 1 second. Then press the COOLER button  
until the WARM indicator light appears.  
3. Turn off all electric power to the appliance if service is to  
be performed.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE AND MAINTENANCE  
Tank (Sediment) Cleaning  
Burner Inspection  
Sediment build-up on the tank bottom may create varying  
amount of noise, if left in the tank will cause permanent tank  
failure. In some water areas, sediment can be removed by  
draining off approximately one gallon of water each month.  
Flood damage to a water heater may not be readily visible or  
immediately detectable. However, over a period of time a  
flooded water heater will create dangerous conditions which  
can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY  
DAMAGE. Contact the Maytag dealer from whom the appliance  
was purchased or call Maytag Customer Service at  
1-800-788-8899 for an authorized servicer to replace a  
flooded water heater. Do not attempt to repair the unit! It  
must be replaced!  
Vent System Inspection  
At least once a year a visual inspection should be made of the  
main burner and pilot burner, see Figure 50.  
You should check for sooting. Soot is not normal and will impair  
proper combustion.  
Soot build-up indicates a problem that requires correction  
before further use. Turn “OFF” gas to water heater and  
leave off until repairs are made, because failure to correct the  
cause of the sooting can result in a fire causing death, serious  
injury, or property damage.  
If improper flame characteristics are not evident, check for  
accumulation of lint or other foreign material that restricts or  
blocks the air openings in the heater or burner. Also check  
Combustion Air and Ventilation Requirements.  
At least once a year a visual inspection should be made of the  
venting system. You should look for:  
Obstructions which could cause improper venting. The  
combustion and ventilation air flow must not be obstructed.  
Damage or deterioration which could cause improper  
venting or leakage of combustion products.  
FIGURE53.  
Rusted flakes around top of water heater.  
Burner Cleaning  
Be sure the vent piping is properly connected to prevent escape  
of dangerous flue gasses which could cause deadly  
asphyxiation.  
NOTE: Burner assembly must be handled carefully to avoid  
damaging the hot surface ignitor.  
Obstructions and deteriorated vent systems may present  
serious health risk or asphyxiation.  
In the event your burner needs cleaning, following these  
instructions:  
Chemical vapor corrosion of the flue and vent system may  
occur if air for combustion contains certain chemical vapors.  
Spray can propellants, cleaning solvents, refrigerator and air  
conditioner refrigerants, swimming pool chemicals, calcium  
and sodium chloride, waxes, bleach and process chemicals  
are typical compounds which are potentially corrosive.  
If inspection of the burner shows that cleaning is required, turn  
the “ON/OFF” rocker switch located on the control box to  
“OFF” position and allow the burner to cool.  
Loose deposits on or around the burner can be removed by  
carefully using the hose of a vacuum cleaner inserted through  
the access door of the water heater. If the burner needs to be  
removed for additional cleaning, call the local gas utility or  
qualified service agent to remove and clean the burner with a  
soft brush. Clean main burner orifice with a suitable soft  
material. Correct the problem that requires the burner to be  
cleaned.  
If after inspection of the vent system you found sooting or  
deterioration, something is wrong. Call Maytag Customer  
Service at 1-800-788-8899 for an authorized servicer or your  
local gas supplier to correct the problem and clean or replace  
the flue and venting before resuming operation of the water  
heater.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLED IN SUITABLEAREA: To insure sufficient ventilation  
and combustion air supply, proper clearances from the water  
heater must be maintained. See Facts to Consider About the  
Location section. Combustible materials such as clothing,  
cleaning materials, or flammable liquids, etc. must not be  
placed against or adjacent to the water heater which can cause  
a fire.  
L.P. Gas Control Valve & Burner Assembly  
Replacement Information  
For Propane (L.P.) Models Only  
Your water heater is equipped with a Propane (L.P.) gas control  
valve and a main burner assembly with left hand threads for  
the following fittings and their connections.  
Anode Rod Inspection  
The connection between the manifold and the gas control  
valve (A and B) are left hand threads.  
The connection between the main burner orifice and the  
manifold (C to D) are left hand threads.  
For ordering these replacement parts, please refer to the “Repair  
Parts List” section of this manual.  
The anode rod is used to protect the tank from corrosion. Most  
hot water tanks are equipped with an anode rod. The  
submerged rod sacrifices itself to protect the tank. Instead of  
corroding the tank, water ions attack and eat away the anode  
rod. This does not affect the water’s taste or color. The rod  
must be maintained to keep the tank in operating condition.  
Anode deterioration depends on water conductivity, not  
necessarily water condition. A corroded or pitted anode rod  
indicates high water conductivity and should be checked and/  
or replaced more often than an anode rod that appears to be  
intact. Replacement of a depleted anode rod can extend the  
life of your water heater. Inspection should be conducted by a  
qualified technician. At a minimum, the anode(s) should be  
checked annually after the warranty period.  
Draining  
The water heater should be drained if being shut down during  
freezing temperatures. Also periodic draining and cleaning of  
sediment from the tank may be necessary.  
FIGURE54.  
Housekeeping  
Vacuum around base of water heater for dust, dirt, and lint on a  
regular basis.  
Turn “OFF” gas supply to the water heater.  
CLOSE the cold water inlet valve to the water heater.  
OPEN a nearby hot water faucet and leave open to allow for  
draining.  
Connect a hose to the drain valve and terminate to an  
adequate drain.  
OPEN the water heater drain valve to allow for tank draining.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: If the water heater is going to be shut down and  
drained for an extended period, the drain valve should be  
left open with hose connected allowing water to terminate  
to an adequate drain.  
line or a water meter with a check valve. Consult Maytag  
Customer Service at 1-800-788-8899 for further information.  
Do not plug the temperature-pressure relief valve.  
Drain Valve Washer Replacement  
CLOSE the drain valve.  
(See Figure 56)  
Follow instructions in the Filling The Water heater section.  
NOTE: For ordering replacement washers, refer to the  
“Repair Parts List” section of this manual.  
Follow the lighting instructions in the Operation section to  
restart the water heater.  
Turn “OFF” gas supply to water heater.  
Follow “Draining” instructions.  
Temperature-Pressure Relief Valve Operation  
The temperature-pressure relief valve must be manually  
operated at least once a year.  
Turning counter clockwise (  
the screw handle.  
), remove the hex cap below  
Remove the washer and put the new one in place.  
Screw the handle and cap assembly back into the drain  
valve and retighten using a wrench. DO NOT OVER  
TIGHTEN.  
Follow instructions in the Filling The Water Heater section.  
Check for leaks.  
Follow the lighting instructions in the Instructions for  
Operation section to restart the water heater.  
When checking the temperature-pressure relief valve operation,  
make sure that (1) no one is in front of or around the outlet of  
the temperature-pressure relief valve discharge line, and (2)  
that the water discharge will not cause any property damage,  
as the water may be extremely hot, see Figure 55.  
FIGURE 56.  
Service  
FIGURE 55.  
Before calling for repair service, read the Start Up Conditions  
and Operational Conditions found in the Troubleshooting Guide  
of this manual.  
If after manually operating the valve, it fails to completely reset  
and continues to release water, immediately close the cold  
water inlet to the water heater, follow the draining instructions,  
and replace the temperature-pressure relief valve with a new  
one.  
If a condition persists or you are uncertain about the operation  
of the water heater, let the Maytag Customer Service Center  
check it out.  
If the temperature-pressure relief valve on the appliance weeps  
or discharges periodically, this may be due to thermal  
expansion. You may have a check valve installed in the water  
Call the Maytag Customer Service at 1-800-788-8899 for an  
authorized servicer.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Water supply system may, because of such events as high line  
Start Up Conditions  
Condensation  
pressure, frequent cut-offs, the effects of water hammer among  
others, have installed devices such as pressure reducing  
valves, check valves, back flow preventers, etc., to control these  
types of problems. When these devices are not equipped with  
an internal by-pass, and no other measures are taken, the  
devices cause the water system to be closed. As water is  
heated, it expands (thermal expansion) and closed systems  
do not allow for the expansion of heated water.  
Whenever the water heater is filled with cold water, some  
condensate will form while the burner is on. A water heater may  
appear to be leaking when in fact the water is condensation.  
This usually happens when:  
A new water heater is filled with cold water for the first time.  
The water within the water heater tank expands as it is heated  
and increases the pressure of the water system. If the relieving  
point of water heater’s temperature-pressure relief valve is  
reached, the valve will relief the excess pressure. The  
temperature-pressure relief valve is not intended for the  
constant relief of thermal expansion. This is an unacceptable  
condition and must be corrected.  
Burning gas produces water vapor In water heaters,  
particularly high efficiency models where flue temperatures  
are lower.  
Large amounts of hot water are used in a short time and the  
refill water in the tank is very cold.  
It is recommended that any devices installed which could create  
a closed system have a by-pass and/or the system have an  
expansion tank or device to relieve the pressure built by thermal  
expansion in the water system. Thermal expansion tanks are  
available for ordering through the Maytag Customer Service  
Center (1-800-788-8899). Contact the local plumbing inspector,  
water supplier and/or call Maytag Customer Service at  
1-800-788-8899 for assistance in controlling these situations.  
Moisture from the products of combustion condense on the  
cooler tank surfaces and form drops of water which may fall  
onto the burner or other hot surfaces to produce a “sizzling” or  
“frying” noise.  
Because of the suddenness and amount of water,  
condensation water may be diagnosed as a “tank leak”. After  
the water in the tank warms up (about 1-2 hours), the condition  
should disappear.  
Strange Sounds  
Do not assume the water heater is leaking until there has  
been enough time for the water in the tank to warm up.  
Possible noises due to expansion and contraction of some  
metal parts during periods of heat-up and cool-down do not  
represent harmful or dangerous conditions.  
An undersized water heater will cause more condensation.  
The water heater must be sized properly to meet the family’s  
demands for hot water including dishwashers, washing  
machines and shower heads.  
Condensation causes sizzling and popping within the burner  
area during heating and cooling periods and should be  
considered normal. See Condensation section.  
Excessive condensation may be noticed during the winter and  
early spring months when incoming water temperatures are at  
their lowest.  
Operational Conditions  
Smelly Water  
Good venting is essential for a gas fired water heater to operate  
properly as well as to carry away products of combustion and  
water vapor.  
In each water heater there is installed at least one anode rod  
(see parts section) for corrosion protection of the tank. Certain  
water conditions will cause a reaction between this rod and  
the water. The most common complaint associated with the  
anode rod is one of a “rotten egg smell”. This odor is derived  
from hydrogen sulfide gas dissolved in the water. The smell is  
the result of four factors which must all be present for the odor  
to develop:  
Smoke / Odor  
It is not uncommon to experience a small amount of smoke  
and odor during the initial start-up. This is due to burning off of  
oil from metal parts, and will disappear in a short while.  
Thermal Expansion  
a concentration of sulfate in the supply water.  
little or no dissolved oxygen in the water.  
a sulfate reducing bacteria within the water heater. (This  
harmless bacteria is non-toxic to humans.)  
an excess of active hydrogen in the tank. This is caused by  
the corrosion protective action of the anode.  
Smelly water may be eliminated or reduced in some water  
heater models by replacing the anode(s) with one of less active  
material, and then chlorinating the water heater tank and all  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
hot water lines. Contact Maytag Customer Service at  
1-800-788-8899 for further information concerning an Anode  
Replacement Kit and this Chlorination Treatment.  
If the smelly water persists after the anode replacement and  
chlorination treatment, we can only suggest that chlorination  
or aeration of the water supply be considered to eliminate the  
water problem.  
Do not remove the anode leaving the tank unprotected. By  
doing so, all warranty on the water heater tank is voided.  
“AIR” In Hot Water Faucets  
FIGURE 57.  
Not Enough or No Hot Water  
HYDROGEN GAS: Hydrogen gas can be produced in a hot  
water system that has not been used for a long period of time  
(generally two weeks or more). Hydrogen gas is extremely  
flammable and explosive. To prevent the possibility of injury  
under these conditions, we recommend the hot water faucet,  
located farthest away, be opened for several minutes before  
any electrical appliances which are connected to the hot water  
system are used (such as a dishwasher or washing machine).  
If hydrogen gas is present, there will probably be an unusual  
sound similar to air escaping through the pipe as the hot water  
faucet is opened. There must be no smoking or open flame  
near the faucet at the time it is open.  
1. Check the manual gas shut off valve to be sure it is open.  
2. The ON/OFF switch on the control box must be “ON”.  
3. The temperature button adjustment may be set too low. See  
the Temperature Regulation” section.  
4. The gas company can check the gas input to see if it is  
correct. An under-fired water heater will not heat water as  
quickly.  
5. Look for leaking or open hot water faucets. Make sure all  
are closed.  
High Temperature Limit Switch  
(Single-Use Type Energy Cut Off)  
6. The cold water inlet temperature may be colder during the  
winter months. It will take longer to heat the water and seem  
like less hot water.  
The thermostat has a built-in limit switch which will actuate in  
case of excessive water temperatures. The heater cannot be  
relit until the gas control valve is replaced. It is important that a  
serviceman be called to determine the reason for limit operation  
and thus avoid repeated thermostat replacement. Lower the  
temperature adjustment setting on new control. Call Maytag  
Customer Service at 1-800-788-8899 for an authorized  
servicer.  
7. If you cannot find what is wrong, call Maytag Customer  
Service 1-800-788-8899 for an authorized servicer.  
Water is Too Hot  
Should overheating occur or the gas supply fail to shut off,  
turn “OFF” the manual gas control valve to the appliance.  
1. The temperature adjustment dial may be set too high. See  
the “Temperature Adjustment” section.  
Venting Manual Reset Switch  
NOTE: A period of time is necessary after an adjustment has  
been made for the water temperature to reach the new  
temperature setting.  
There is a venting manual reset switch located on the draft  
hood. If the venting manual reset switch is activated, it will not  
reset itself. Before resetting this venting manual reset switch,  
check for flue blockage and propriety of the venting system. To  
reset the venting manual reset switch, press the red reset button.  
2. If lower temperature settings will not lower the water  
temperature, call Maytag Customer Service 1-800-788-8899  
for an authorized servicer.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Leakage from other appliances, water lines, or ground seepage  
should also be checked.  
Leakage Checkpoints  
*
To check where threaded portion enters tank, insert cotton  
swab between jacket opening and fitting. If cotton is wet,  
follow “Draining” instructions in the Periodic Maintenance  
section and then remove fitting. Put pipe dope or teflon tape  
on the threads and replace. Then follow Filling the Water  
Heater instructions in the Installation Instructions section.  
Read this manual first. Then before checking the water heater  
make sure the gas supply has been turned “OFF”, and never  
turn the gas “ON” before the tank is completely full of water.  
Never use this water heater unless it is completely filled with  
water. To prevent damage to the tank, the tank must be filled  
with water. Water must flow from the hot water faucet before  
turning “ON” gas to the water heater, see Figure 58.  
A. Water at the draft hood is water vapor which has condensed  
out of the combustion products. This is caused by a problem  
in the vent. Call Maytag Customer Service at  
1-800-788-8899 for an authorized servicer.  
B. *Condensation may be seen on pipes in humid weather or  
pipe connections may be leaking.  
C. *The primary anode rod fitting may be leaking.  
D. Small amounts of water from temperature-pressure relief  
valve may be due to thermal expansion or high water  
pressure in your area.  
E. *The temperature-pressure relief valve may be leaking at  
the tank fitting.  
F. Water from a drain valve may be due to the valve being  
slightly opened.  
G. *The drain valve may be leaking at the tank fitting.  
H. Combustion products contain water vapor which can  
condense on the cooler surfaces of the tank. Droplets form  
and drip onto the burner or run on the floor. This is common  
at the time of start-up after installation and when incoming  
water is cold.  
I. Water in the water heater bottom or on the floor may be from  
condensation, loose connections, or the relief valve.  
DO NOT replace the water heater until a full inspection of all  
possible water sources is made and necessary corrective  
steps taken.  
FIGURE 58.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING (Continued)  
This troubleshooting guide has been supplied for use by qualified service personnel who have a complete understanding of both  
electricity and gas.  
Label all wiring before disconnecting any wiring; to ensure correct reconnection. Failure to follow this instruction could cause  
improper and possible dangerous operation, resulting in DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.  
THERMOSTAT AND GAS SUPPLY CHECK  
Is gas being supplied to the  
thermostat?  
NO  
YES  
Turn “ON” gas supply.  
Is thermostat calling for heat?  
Run (HOT) water from heater and  
set adjustment button higher.  
Check using a manometer at  
thermostat pressure tap.  
YES  
Is there a minimum gas pressure  
4” W.C. for natural gas or 10” W.C.  
for propane (L.P.) gas?  
Call gas company to increase gas  
pressure.  
NO  
YES  
GO TO SYSTEM CHECK  
SECTION, PAGE 39.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM CHECK  
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.  
DO NOT BY-PASSANYCONTROLS TO MAKE HEATER OPERATE. OPERATE ONLYAS WIRED FROM FACTORY.  
LED STATUS  
An open earth ground circuit to the  
ignition system.  
1. Check that the earth ground connection is  
properly connected.  
A
B C  
2. Check that the ground conductor on the  
water heater is properly connected.  
Wiring error or a high resistance to  
earth ground.  
1. Check for proper connection of line  
neutral and hot wires.  
2. Check that the water heater is securely  
connected to earth ground.  
A
A
B C  
B C  
Pressure switch remained closed longer  
than 5 seconds after the call for  
heat began.  
1. Pressure switch wiring is incorrect.  
2. Replace pressure switch.  
Pressure switch remained open longer  
than 5 seconds after the combustion  
blower was energized.  
1. Pressure switch wiring is incorrect.  
2. Pressure switch tubing not connected  
correctly.  
A
A
B C  
B C  
3. Air intake or exhaust obstructed.  
Error in the hot surface ignitor circuit.  
System in lockout.  
1. Check that all wiring is correct and secure.  
2. Replace hot surface ignitor.  
1. Gas supply is off or too low to operate.  
2. Hot surface ignitor not positioned  
correctly.  
A
B C  
3. Low voltage to the water heater.  
4. Electric polarity to unit is incorrect - test  
and correct.  
Problem in the gas valve driver circuit.  
Problem with the internal circuit.  
Problem with the internal circuit.  
1. Turn power to the water heater off for  
10 seconds and then back on.  
2. Replace gas control valve.  
A
A
B C  
B C  
1. Turn power to the water heater off for  
10 seconds and then back on.  
2. Replace gas control valve.  
1. Turn power to the water heater off for  
10 seconds and then back on.  
2. Replace gas control valve.  
A
A
B C  
B C  
Flame signal sensed out of  
proper sequence.  
1. Replace gas control valve.  
A B C  
ECO activated.  
1. Replace gas control valve.  
A
A
B C  
B C  
One of the temperature adjust  
buttons stuck closed.  
1. Press and release each of the buttons once.  
2. Replace gas control valve.  
Water temperature sensor is  
either open or short circuited.  
1. Check that all wiring is correct and secure.  
2. Replace gas control valve.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING (Continued)  
These guidelines should be used by a qualified Maytag Customer Service CenterAgent. Call the  
Maytag Customer Service Center at 1-800-788-8899 for assistance.  
Problem  
Cause  
Solution  
Blower will not run.  
A) “ON/OFF” control switch turned off  
B) Blower unplugged.  
Turn switch to the “ON” position.  
Plug blower back into 115 VAC outlet.  
Repair service to outlet.  
Replace thermostat.  
C) No power at outlet.  
D) Thermostat defective.  
E) Control harness defective.  
F) High limit control circuit open.  
G) Blower motor defective.  
Thermostat problems.  
A) Thermostat set too low.  
B) Thermostat or ECO defective.  
Others.  
Replace control harness.  
Replace ECO.  
NOT ENOUGH  
HOT WATER  
Replace blower assembly.  
Set temperature control higher.  
Replace thermostat or ECO as required.  
A) Heater undersized.  
Reduce hot water use.  
B) Low gas pressure.  
Contact dealer.  
C) Incoming water is unusually cold.  
D) Leaking hot water pipes or fixtures.  
A) Not enough dilution air to mix with flue gases.  
Allow more time for heater to reheat.  
Have plumber check and repair leaks.  
Proper dilution air must be provided for dilution of flue  
temp. Refer to “Installation Instructions” section.  
Check for heat sources around and/or blockage of  
dilution air intake at draft hood. (see page 28).  
Install correct orifice.  
VENT PIPE TOO HOT  
(ABOVE 170OF  
B) Dilution air too hot for mixing with flue gases.  
C) Wrong burner assembly.  
A) Dirt in burner ports.  
Turn off heater and gas, clean burner head.  
Check dilution air intake, exhaust venting and air openings  
in bottom base pan for obstructions or blockage.  
Check dilution air intake for obstructions or blockage.  
See “Condensation” section.  
B) Combustion air path restricted.  
YELLOW FLAME  
CONDENSATION  
C) Not enough dilution air.  
A) Water on the floor under heater.  
B) Water dripping from the blower assembly.  
Provide drip “TEE” to catch condensation from horizontal  
section of exhaust vent close to blower assembly.  
Improperly sealed, hot or cold supply connections, Tighten threaded connections.  
relief valve, drain valve or thermostat threads.  
WATER LEAKS  
LEAKING T & P  
Leakage from other appliances or water lines.  
Condensation of flue products.  
Inspect other appliances near the water heater.  
See “Condensation” section.  
Thermal expansion in closed water system.  
Improperly seated valve.  
Install thermal expansion tank (DO NOT plug T & P valve).  
Check relief valve for proper operation (DO NOT plug  
T & P valve).  
HOT WATER ODORS  
High sulfate or mineral content in water supply.  
Bacteria in water supply.  
Drain and flush heater thoroughly then refill.  
Chlorinate water supply.  
(Refer to Smelly Water)  
WATER TOO HOT  
Thermostat set too high.  
Refer toTEMPERATURE REGULATION.  
See “Condensation” section.  
Condensation dripping on burner.  
Sediment at bottom of heater tank.  
WATER HEATER SOUNDS  
SIZZLING-RUMBLING  
Clean sediment from tank. Refer to “Draining” instruction  
in “Maintenance” section of manual.  
Refer to “Combustion Air and Ventilation” on pages 11-14.  
Test polarity and correct.  
SOOTING  
Improper combustion.  
Outlet polarity is reversed.  
HEATER LIGHTS BUT GOES  
OUT IN 4-5 SECONDS  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
MAYTAG GAS WATER HEATERS  
MODEL NO’S  
HRN11240P  
40 Gallon Natural Gas  
HRN31240P  
HRP11240P  
HRP31240P  
40 Gallon Natural Gas  
40 Gallon Propane Gas (L.P.)  
40 Gallon Propane Gas (L.P.)  
PCV, ABS OR CPVC ITEMS  
FOR ALL MODELS SUPPLIED  
LOCALLY  
Key  
Model Numbers  
No. Part Description  
HRN11240P  
HRN31240P  
HRP11240P  
HRP31240P  
1
2
3
Temperature-Pressure Relief Valve  
Primary Anode Rod  
Drain Valve  
66001700  
66001020  
66001015  
66001021  
66001881  
66001369  
66001372  
66001247  
66001538  
66001530  
66001027  
66001190  
66001029  
66001527  
- - - - - - - -  
66001617  
66001399  
66001895  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001881  
66001369  
66001372  
66001247  
66001538  
66001530  
66001027  
66001190  
66001029  
66001527  
- - - - - - - -  
66001617  
66001399  
66001895  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001881  
66001369  
66001372  
66001247  
66001538  
66001533  
66001027  
66001190  
66001029  
- - - - - - - -  
66001528  
66001617  
66001399  
66001895  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001881  
66001369  
66001372  
66001247  
66001538  
66001533  
66001027  
66001190  
66001029  
- - - - - - - -  
66001528  
66001617  
66001399  
66001895  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
*4 Drain Valve Washer (17/32” x 13/64” x 1/8” thick)  
5
6
7
8
9
Secondary Anode Rod w/Heat traps  
Pressure Switch  
Power Cord  
On/Off Switch  
Burner Orifice (Drill Size)  
10 Manifold  
11 Burner  
12 Outer Door  
13 Inner Door  
14 Gas Control Valve (Natural)  
14 Gas Control Valve (Propane{L.P.])  
15 Dip Tube  
16 Flue Baffle  
17 Junction Box Cover  
18 Inlet Nipple w/Heat Traps  
19 Pipe Insulation (2 ea.)  
20 Wiring Harness  
21 T & P Insulation  
22 Water Heater Stand  
23 Blower/ Draft Hood Ass’y  
24 Venting Switch  
25 3” or 2” Schedule 40 90o Elbow  
26 3” or 2” Schedule 40 Vent Pipe  
27 Wall Collar  
28 3” PVC Vent Terminal  
29 Hot Surface Ignition Ass’y  
30 Mounting Bracket  
*31 Manual  
* Not Shown.  
Now that you have purchased this gas water heater, should a need  
ever exist for repair parts or service, simply call Maytag Customer  
Service at 1-800-788-8899 for an authorized servicer. Be sure to  
provide all pertinent facts when you call or visit.  
When ordering repair parts, always give the following information:  
Model number  
Serial Number  
Part Description  
Part Number  
THIS IS AREPAIR PARTS LIST, NOTAPACKING LIST.  
The model number of this gas water heater will be found on the model  
rating plate located near the gas control valve.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
MAYTAG GAS WATER HEATERS  
MODEL NO’S  
HRN11250P  
HRN31250P  
HRP11250P  
HRP31250P  
50 Gallon Natural Gas  
50 Gallon Natural Gas  
50 Gallon Propane Gas (L.P.)  
50 Gallon Propane Gas (L.P.)  
PCV, ABS OR CPVC ITEMS  
FOR ALL MODELS SUPPLIED  
LOCALLY  
Key  
Model Numbers  
No. Part Description  
HRN11250P  
HRN31250P  
HRP11250P  
HRP31250P  
1
2
3
Temperature-Pressure Relief Valve  
Primary Anode Rod  
Drain Valve  
66001700  
66001020  
66001015  
66001021  
66001898  
66001368  
66001372  
66001247  
66001538  
66001659  
66001027  
66001190  
66001029  
66001527  
- - - - - - - -  
66001052  
66001399  
66001899  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001898  
66001368  
66001372  
66001247  
66001638  
66001659  
66001027  
66001190  
66001029  
66001527  
- - - - - - - -  
66001052  
66001399  
66001899  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001898  
66001368  
66001372  
66001247  
66001540  
66001659  
66001027  
66001190  
66001029  
- - - - - - - -  
66001528  
66001052  
66001399  
66001899  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
66001700  
66001020  
66001015  
66001021  
66001898  
66001368  
66001372  
66001247  
66001515  
66001659  
66001027  
66001190  
66001029  
- - - - - - - -  
66001528  
66001052  
66001399  
66001899  
66001707  
66001755  
66001526  
66001709  
66001243  
66001366  
66001367  
- - - - - - - -  
- - - - - - - -  
66001262  
66001255  
66001525  
66001896  
66001897  
*4 Drain Valve Washer (17/32” x 13/64” x 1/8” thick)  
5
6
7
8
9
Secondary Anode Rod w/Heat traps  
Pressure Switch  
Power Cord  
On/Off Switch  
Burner Orifice (Drill Size)  
10 Manifold  
11 Burner  
12 Outer Door  
13 Inner Door  
14 Gas Control Valve (Natural)  
14 Gas Control Valve (Propane{L.P.])  
15 Dip Tube  
16 Flue Baffle  
17 Junction Box Cover  
18 Inlet Nipple w/Heat Traps  
19 Pipe Insulation (2 ea.)  
20 Wiring Harness  
21 T & P Insulation  
22 Water Heater Stand  
23 Blower/ Draft Hood Ass’y  
24 Venting Switch  
25 3” or 2” Schedule 40 90o Elbow  
26 3” or 2” Schedule 40 Vent Pipe  
27 Wall Collar  
28 3” PVC Vent Terminal  
29 Hot Surface Ignition Ass’y  
30 Mounting Bracket  
*31 Manual  
* Not Shown.  
Now that you have purchased this gas water heater, should a need  
ever exist for repair parts or service, simply call Maytag Customer  
Service at 1-800-788-8899 for an authorized servicer. Be sure to  
provide all pertinent facts when you call or visit.  
When ordering repair parts, always give the following information:  
Model number  
Serial Number  
Part Description  
Part Number  
THIS IS AREPAIR PARTS LIST, NOTAPACKING LIST.  
The model number of this gas water heater will be found on the model  
rating plate located near the gas control valve.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
MAYTAG GAS WATER HEATERS  
MODEL NO’S  
HRN11275P  
HRN31275P  
HRP11275P  
HRP31275P  
75 Gallon Natural Gas  
75 Gallon Natural Gas  
75 Gallon Propane Gas (L.P.)  
75 Gallon Propane Gas (L.P.)  
PCV, ABS OR CPVC ITEMS  
FOR ALL MODELS SUPPLIED  
LOCALLY  
Key  
Model Numbers  
No. Part Description  
HRN11275P  
HRN31275P  
HRP11275P  
HRP31275P  
1
2
3
Temperature-Pressure Relief Valve  
Primary Anode Rod  
Drain Valve  
66001700  
66001020  
66001015  
66001021  
66001294  
66001372  
66001247  
66001900  
66001532  
66001221  
66001190  
66001146  
66001657  
- - - - - - - -  
66001030  
66001350  
66001895  
66001148  
66001526  
66001709  
66001243  
66001401  
66001291  
66001402  
66001262  
66001403  
66001342  
66001255  
- - - - - - - - -  
- - - - - - - -  
66001524  
66001896  
66001034  
66001897  
66001700  
66001020  
66001015  
66001021  
66001294  
66001372  
66001247  
66001901  
66001532  
66001221  
66001190  
66001146  
66001657  
- - - - - - - -  
66001030  
66001350  
66001895  
66001148  
66001526  
66001709  
66001243  
66001401  
66001291  
66001402  
66001262  
66001403  
66001342  
66001255  
- - - - - - - -  
- - - - - - - -  
66001524  
66001896  
66001034  
66001897  
66001700  
66001020  
66001015  
66001021  
66001294  
66001372  
66001247  
66001902  
66001532  
66001221  
66001190  
66001146  
- - - - - - - -  
66001658  
66001030  
66001350  
66001895  
66001148  
66001526  
66001709  
66001243  
66001401  
66001291  
66001402  
66001262  
66001403  
66001342  
66001255  
- - - - - - - -  
- - - - - - - -  
66001524  
66001896  
66001034  
66001897  
66001700  
66001020  
66001015  
66001021  
66001294  
66001372  
66001247  
66001903  
66001532  
66001221  
66001190  
66001146  
- - - - - - - -  
66001658  
66001030  
66001350  
66001895  
66001148  
66001526  
66001709  
66001243  
66001401  
66001291  
66001402  
66001262  
66001403  
66001342  
66001255  
- - - - - - - -  
- - - - - - - -  
66001524  
66001896  
66001034  
66001897  
*4 Drain Valve Washer (17/32” x 13/64” x 1/8” thick)  
5
6
7
8
9
Pressure Switch  
Power Cord  
On/Off Switch  
Burner Orifice (Drill Size)  
Manifold  
10 Burner  
11 Outer Door  
12 Inner Door  
13 Gas Control Valve (Natural)  
13 Gas Control Valve (Propane{L.P.])  
14 Dip Tube  
15 Flue Baffle  
16 PV Switch Cover  
17 Cold and Hot Water Nipples  
18 Wiring Harness  
19 T & P Insulation  
20 Water Heater Stand  
21 Draft Hood Ass’y  
22 Gasket Blower  
23 Blower  
24 Wall Collar  
25 Vent-Blower Adapter  
26 Venting Switch  
27 3” PVC Vent Terminal  
28 3” or 4” Schedule 40 Vent Pipe  
29 3” or 4” Schedule 40 90o Elbow  
30 Hot Surface Ignition Ass’y  
31 Mounting Bracket  
32 Pipe Insulation (2 ea.)  
*33 Manual  
* Not Shown.  
Now that you have purchased this gas water heater, should a need  
ever exist for repair parts or service, simply call Maytag Customer  
Service at 1-800-788-8899 for an authorized servicer. Be sure to  
provide all pertinent facts when you call or visit.  
When ordering repair parts, always give the following information:  
Model number  
Serial Number  
Part Description  
Part Number  
THIS IS AREPAIR PARTS LIST, NOTAPACKING LIST.  
The model number of this gas water heater will be found on the model  
rating plate located near the gas control valve.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
MAYTAG/STATE PART NUMBER CONVERSION KEY  
MAYTAG  
STATE  
MAYTAG  
66001372  
66001399  
66001400  
66001401  
66001402  
66001403  
66001404  
66001405  
66001515  
66001524  
66001525  
66001526  
66001527  
66001528  
66001530  
66001532  
66001533  
66001538  
66001540  
66001617  
66001638  
66001654  
66001657  
66001658  
66001659  
66001660  
66001700  
66001707  
66001708  
66001709  
66001755  
66001758  
66001818  
66001881  
66001895  
66001896  
66001897  
66001898  
66001899  
66001900  
66001901  
66001902  
66001903  
STATE  
9003095  
9003083  
9003156  
9003153  
9003152  
9003154  
9003157  
9000736  
9003453  
9003626  
9003627  
9003628  
9003629  
9003630  
9003685  
9003687  
9003688  
9003493  
9003495  
9003527  
9003443  
9003690  
9003693  
9003694  
9003697  
9003698  
9003917  
9003909  
9003717  
9003716  
9003971  
9003916  
9003930  
9004274  
9002113  
9004277  
184683-001  
9004268  
9002113  
9001671  
9002978  
9004278  
9004273  
66001010  
66001011  
66001012  
66001013  
66001014  
66001015  
66001020  
66001021  
66001025  
66001027  
66001029  
66001030  
66001034  
66001035  
66001041  
66001046  
66001047  
66001052  
66001068  
66001105  
66001146  
66001148  
66001168  
66001169  
66001172  
66001174  
66001177  
66001190  
66001221  
66001243  
66001247  
66001255  
66001259  
66001262  
66001291  
6001294  
9002404  
9001609  
9001608  
ETC2X  
ETC5X  
9002401  
9000734  
9001584  
0230120  
9002411  
9000281  
9002444  
9002445  
0230141  
0230224  
0230124  
0230123  
9002059  
9001453  
9002769  
9000369  
9002565  
0230209  
0230212  
0230225  
0230247  
0230260  
9000358  
9001271  
9001422  
9001773  
9001957  
9001976  
9001993  
9002508  
9002511  
9002512  
9002597  
9002678  
9002981  
9003081  
9003082  
9003089  
9003090  
66001295  
66001317  
66001342  
66001350  
66001366  
66001367  
66001368  
66001369  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
FULLONEYEAR WARRANTY  
For one year from the date of original retail purchase, any part which fails in normal home use will be repaired  
or replaced free of charge.  
If a leak occurs in the tank, a new water heater of the closest capacity and quality then available, will be  
replaced free of charge.  
The warranty of the replacement is the balance of the original water heater’s warranty.  
LIMITED PARTS WARRANTY  
After the first year and through the twelfth year from the date of original retail purchase, any parts which fail due  
to a defect in materials or workmanship, will be replaced or repaired free of charge for the part itself, with the  
owner paying all other costs, including labor, mileage and transportation.  
If the water heater is subjected to commercial, institutional, industrial or non-residential use, the above  
warranty coverage for parts that are proved to be defective in material or workmanship is effective for one year  
from the date of the original retail purchase.  
The warranty of the replacement is the balance of the original water heater’s warranty, or twelve months from  
the date of the part(s) purchase, whichever comes first.  
Blower fan and assembly are warranted for five years.  
This warranty is limited to the original owner of the water heater.  
LIMITED TANK WARRANTYAGAINST LEAKS  
After the first year and through the twelfth year from the date of original retail purchase, if a leak occurs in the  
tank, a new water heater of the closest capacity and quality then available, will be replaced free of charge for  
the water heater, with the owner paying all other costs, including labor, mileage and transportation.  
If the water heater is subjected to commercial, institutional, industrial or non-residential use, the above  
warranty coverage for the tanks that are proved to be defective in material or workmanship is effective for two  
years from the date of the original retail purchase.  
The warranty of the replacement is the balance of the original water heater’s warranty.  
Please note: The full and limited warranty applies only while this water heater is used in the United States of  
America.  
This warranty is limited to the original owner of the water heater.  
TO OBTAIN WARRANTYSERVICE  
To locate an authorized service company in your area contact the Maytag dealer from whom your appliance  
was purchased; or call Maytag Customer Service at the number listed below. Should you not receive satisfactory  
warranty service, please call or write:  
Maytag Customer Service  
P.O. Box 2370  
Cleveland, TN 37320-2370  
U.S.A. 1-800-788-8899  
When contacting Maytag Customer Service be sure to provide the model and serial number of your appliance,  
the name and address of the dealer from whom you purchased the appliance and the date of purchase.  
MAYTAG WATER HEATERS ARE MANUFACTURED AND THIS WARRANTY IS PROVIDED BYA.O. SMITH  
CORPORATION. MAYTAG® IS A TRADEMARK OF THE MAYTAG CORPORATION AND IS USED UNDER  
LICENSE TOA.O. SMITH CORPORATION.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lenoxx Electronics Handheld TV TV 504 User Manual
LG Electronics Clothes Dryer DLEX0001TM User Manual
LG Electronics Computer Monitor E2250V User Manual
Lightolier Indoor Furnishings 1102T Series User Manual
Line 6 Music Pedal POD X3 Family User Manual
Magnadyne Automobile Alarm 4900 Series User Manual
Makita Drill HP2050 User Manual
Makita Saw 5007NBA User Manual
McCulloch Trimmer Cabrio 433B User Manual
Metabo Welding System Welding Technology User Manual