HomeSeer Technologies Single Package Air Conditioner 13 SEER User Manual

USER’S MANUAL AND INSTALLATION  
INSTRUCTIONS  
13 SEER  
Single Package Air Conditioner  
Single Package Air Conditioner  
IMPORTANT  
Read this owner information to become familiar with the capabilities and use  
of your appliance. Keep this with literature on other appliances where you  
have easy access to it in the future. If a problem occurs, check the instructions  
and follow recommendations given. If these suggestions don’t eliminate your  
problem, call your installing contractor or distributor in your area.  
INTRODUCTION  
Mostanyairconditionerwillkeepyoucool.Ourairconditionerwasdesignedtodo  
it efficiently. Efficiency means less cost to you while keeping you comfortable.  
WHYYOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY  
1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by  
this same coil.  
2. Air is then delivered through the main duct, via registers, into your home.  
3. Return air is drawn through the return register.  
4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidi-  
fied. Then the cycle begins again.  
is any question concerning the power supply,  
contact the local power company.  
SECTION 2.  
INSTALLER INFORMATION  
Inspecting Equipment: All units are securely  
packedatthetimeofshipmentand,uponarrival,  
shouldbecarefullyinspectedfordamage.Claims  
for damage (apparent or concealed) should be  
filed immediately with the carrier.  
GENERAL  
Read the following instructions completely  
before performing the installation.  
These instructions are for the use of qualified  
personnel specially trained and experienced  
in the installation of this type of equipment  
and related system components. Some states  
require installation and service personnel to  
be licensed. Unqualified individuals should not  
attempt to interpret these instructions or install  
this equipment.  
INSTALLATION  
1. SELECTTHE BEST LOCATION FORTHE  
AIR CONDITIONING UNIT  
IMPORTANT: DO NOT PLACE UNIT UNDER  
THE HOME.  
The single packaged air conditioners are de-  
signed for outdoor installation only and can be  
readilyconnectedintothehighstaticductsystem  
of a home. The only connections needed for  
installation are the supply and return ducts, the  
line voltage, and thermostat wiring.A complete  
air conditioning system typically consists of:  
• Select a solid, level position, preferably on a  
concrete slab, slightly above the grade level,  
and parallel to the home.  
• The hot condenser air must be discharged  
up and away from the home, and if possible,  
in a direction with the prevailing wind.  
• Do not place the unit in a confined space.  
• If practical, place the air conditioner where it  
and the ducts will be shaded from the after-  
noon sun when the heat load is greatest.  
Try to select a site for the unit that is as close  
as possible to the proposed return grille loca-  
tion.  
• Single Package Air Conditioner  
• Home Fittings Kit  
• Unit Fittings Kit  
• Thermostat  
Thesinglepackageairconditioneriscompletely  
assembled,factorywired,andfactoryruntested.  
The units are ready for easy and immediate  
installation.  
• Keep in mind that the length of the supply and  
returnductsshouldbekepttoaminimumwith  
no sharp radiused bends.  
2. UNPACK THE UNIT  
It is recommended that the unit be unpacked  
at the installation site to minimize damage due  
to handling.  
PRE-INSTALLATION CHECK  
Before any installation is attempted, the cool-  
ing load of the area to be conditioned must be  
calculated and a system of the proper capacity  
selected. It is recommended that the area to  
be conditioned be completely insulated and  
vapor sealed.  
CAUTION:  
Do not tip the unit on its side. Oil  
may enter the compressor cylinders  
and cause starting trouble. If unit has  
been set on its side,restore to upright  
position and do not run for several  
hours.Thenrununitforafewseconds.  
Do this three or four times with five  
minutes between runs.  
The installer should comply with all local codes  
and regulations which govern the installation  
of this type of equipment. Local codes and  
regulations take precedence over any recom-  
mendations contained in these instructions.  
Consult local building codes and the National  
ElectricalCode(ANSICI)forspecialinstallation  
requirements.  
The electrical supply should be checked to de-  
termine if adequate power is available. If there  
a. Remove the bands from around the unit.  
b. Unfold the top and bottom cap flanges.  
c. Carefully remove the top cap and tube.  
3
RETURN DUCT  
6 ft.  
Align the 14” return duct slots with the holes in  
the collar and install two screws. Position the  
collarovertheopeningandalignthefournotches  
in the collar with the four dimples in the panel.  
Using self-drilling screws (10-16x.5) attach the  
collar to the rear panel.  
24"  
4. LOCATING AND INSTALLING THE RE-  
TURN AIR ASSEMBLY  
To avoid complications, locate and install the  
return air assembly first. The return air box  
with grille and filter (Figure 4) should not be  
located in heavy traffic areas like hallways or  
center of rooms. A good spot is in a corner or  
under a table, if a minimum two inch clearance  
is available. If desired, the return opening can  
be located inside a closet with louvered doors  
that have an open area equal to or greater than  
the 12x 20grille furnished.The return air grille  
can be placed in the wall of a closet and the air  
ductedintothelterboxthroughaboxed-inarea  
at the closet floor level. Make sure the filter is  
readily accessible.  
12"  
12"  
Figure 2. Minimum Unit Clearances  
3. INSTALLTHERETURNANDSUPPLYAIR  
FITTINGS ON THE UNIT  
The supply and return fittings are included with  
select models. If supplied, the duct fittings are  
shippedinthesupplyduct.Theyattachtotheunit  
openings with a flange and bead arrangement,  
secured with two sheet metal screws. Note: For  
ease of access, install fitting before positioning  
unit in final location.  
After determining the location of the return air  
opening, start the installation from under the  
home by cutting a small hole in the fiber under-  
board to determine how the floor joist location  
willaffectcuttingtheopeningneededforthebox.  
Floorjoistsgenerallyarelocatedon16centers,  
leaving 14-3/8” between joists. After measuring  
the return air box (approximately 12-1/4” x 14-  
1/4”), cut the hole through the floor so that the  
box will fit between the floor joists. Care should  
betakenwhencuttingthroughcarpetingtoavoid  
snags.Inmostinstallationsitwillbenecessaryto  
cut a similar hole in the fiberboard directly under  
the hole in the floor.However, if the floor is more  
SUPPLY DUCT  
Positionthesupplyductcollar, ifsupplied, sothe  
edge of the unit opening fits between the flange  
andthebead.Overlapthecollarendskeepingthe  
smallscrewholesunderneath.Aligntheholesin  
the crimped area and install one screw.  
Note: It may be necessary to loosen the four  
screws that hold the transition duct in order to  
install the supply fitting. Re-tighten when instal-  
lation is complete.  
Tap collar as necessary to ensure engagement  
with unit opening and install second screw.  
Tighten first screw. Rotate collar clockwise so  
joint is near three o’clock position.  
Transition Duct Screws  
14” Duct Dimples  
Supply Air  
Return Air  
Figure 3. Return and Supply Air Fittings  
Figure 4. Return Air Box  
4
than ten inches deep, it will only be necessary  
to cut a hole for the collar on the return air box  
or for the insulated duct.  
Set the box into the opening and fasten with  
screws or nails. Put the filter and return air  
grille in place.  
5. LOCATING AND INSTALLING THE  
SUPPLY DAMPER(S)  
Figure 5. Supply Damper  
over all tabs flat on the inside of the heat duct.  
Seal the opening between the fiberboard and  
damper or flexible duct.  
CAUTION:  
When a home is not equipped with a  
make-ready kit means must be pro-  
vided to prevent simultaneous opera-  
tion of the heating and cooling units.  
Aheat/coolthermostatisavailablefor  
this purpose.  
DUCTING SYSTEM  
DUCT REQUIREMENTS  
The supply duct system, including the number  
and type of registers, will have much more ef-  
fect on the performance of an air conditioning  
system than any other factor.The duct must be  
sufficientlylargetoconductanadequateamount  
of air to each register.  
When installing this air conditioning  
system in conjunction with a furnace,  
a damper must be installed in the fur-  
nace base assembly to prevent cold  
air being discharged around the heat  
exchanger. Damage to the heat ex-  
changer and asphyxiation may occur  
if a damper is not installed.if the damp  
THE AIR CONDITIONING OUTPUT OF THE  
SYSTEMWILL NOT COOLTHE HOME IFTHE  
AIR IS LOST TO THE OUTSIDE THROUGH  
LEAKSINTHEDUCTSYSTEM.ALSO,DUCTS  
WHICH ARE COLLAPSED OR RESTRICTED  
BY FOREIGN OBJECTS WILL PREVENT  
ADEQUATE AIR FLOW.  
Check with the furnace manufacturer  
for damper requirements. Failure to  
install the required furnace damper  
mayinvalidatecodeagencylistingand  
limited warranty on the furnace.  
Note:For highly resistive duct systems it may be  
necessarytoaddanadditionalreturnairductand  
orsupplytoachievemaximumperformanceand  
prevent coil icing and refrigerant flood back.  
CONNECTING THE RETURN AND SUPPLY  
AIR FLEXIBLE DUCTS  
When locating the supply damper(s), carefully  
check floor joists and frame members that could  
interfere with the installation of the damper or  
flexible duct. Ideally, the damper should be  
located in the bottom of the main duct, forward  
of center of the home, at least three feet from  
the nearest register.The round supply opening  
in the slanted side of the damper should face  
the side of the home where the air conditioner  
is located.To locate the center of the heat duct,  
first cut a small hole in the fiberboard below the  
duct at the desired location. After locating the  
duct center, cut a hole approximately 3/4larger  
than the damper opening in the fiberboard. Cut  
a 9-1/8” x 13-1/8” hole in the duct and bend  
over all tabs flat on the inside of the heat duct.  
After inserting the damper into the duct, bend  
a. The supply duct for all units is twelve inches  
in diameter.The return duct is 14” diameter  
for all air conditioning units.  
b. The flexible ducts can be connected to the  
corresponding fittings with the clamps pro-  
vided with the ducts. Note: All connections  
should be leak tight or a loss in cooling  
capacity will result.  
c. Theexibleductsmaybecuttotherequired  
length, see instructions packed with duct.  
Keep all ducts as short and straight as pos-  
sible. Avoid sharp bends.  
d. Ducts may be spliced with sheet metal  
sleeves and clamps. (See Ducting Instal-  
lation Accessories below.)  
5
TYPICAL APPLICATIONS  
4
4
6
4
3
2
3
2
6
6
7
1
1
5
5
SINGLE DUCT APPLICATION  
MULTIPLE DUCT APPLICATION  
Ref. No.  
Description  
12” x 20” Return Air  
16” x 20” Air Filter  
12” x 20” Grille  
1
2
3
4
5
6
7
Supply Damper  
14” Diameter Flex Return Duct  
12” Diameter Flex Supply Duct  
12” x 12” x 12” “Y” Fitting  
Figure 6. Typical Applications  
e. Once the inner duct is connected to the  
proper fitting, the insulation and plastic  
sleeveshouldbepulledovertheconnection  
and clamped.  
f. For homes with multiple supply ducts or for  
special applications, aY tting is available  
to divide the supply air so it can be ducted  
to different areas of the home for more  
efficient cooling. Note:TheY tting should  
be insulated for maximum performance.  
If Standard Motor:  
1. Disconnect all electrical power to the  
unit and remove the service panel.  
2. Remove the motor lead from terminal #4 of  
the blower relay. Cut the wire tie holding the  
motor lead bundle. The motor leads are  
color coded as shown in Figure 7.  
3. Ifthedesiredheatingblowerspeedisdifferent  
than the cooling speed, remove and discard  
the jumper wire between terminals #6 and  
#4. on the blower relay. Place the desired  
heating blower speed lead on terminal #6  
and the desired cooling blower speed  
lead on terminal #4 of the blower relay. Use  
another wire tie (field supplied) to bundle the  
remaining motor leads.  
Blower Speed — For optimum system  
performance and comfort, it may be necessary  
to change the factory set speed. See table 1 for  
factory settings. To change the blower speed:  
6
If Fixed Torque Motor:  
1. Disconnect all electrical power to the unit  
and remove the blower panel.  
Check all factory wiring per the unit wiring  
diagram and inspect the factory wiring connec-  
tions to be sure none loosened during shipping  
or installation.  
2. Locate the orange and red wires terminated  
totheblowermotor. Theorangewirecontrols  
coolingoperationwhiletheredwirecontrols  
heating operation.  
3. Verify the required speed from the airflow  
datafoundingure7.Placeappropriatewire  
on the appropriate motor speed tap for the  
required airflow point.  
CAUTION:  
To avoid personal injury or property  
damage, make certain that the motor  
leads cannot come into contact with  
any uninsulated metal components  
of the unit.  
Note:If the same speed is required for both  
heating and cooling, remove either the red  
or orange wire from the blower motor. Next,  
obtainthejumperwirefromthehomeowners  
packet and connect it to the blower relays  
at the coils on the blue wire and red wire  
side.  
Check all factory wiring per the unit wiring  
diagram and inspect the factory wiring connec-  
tions to be sure none loosened during shipping  
or installation.  
Model  
Wire Color /  
Speed Tap  
Motor  
Speed  
Air Flow  
(0.3 In. WC)  
P3RD  
CONDENSATE DRAIN  
Red  
Black  
Red  
Low  
High  
760  
2 Ton  
A 3/4condensate fitting extends out of the side  
oftheunit.Thedraintrap,shippedintheelectrical  
compartment,mustbeinstalledtopreventwater  
from collecting inside the unit.Thread the elbow  
provided with the unit into the drain connection  
until hand tight.Install the trap into the fitting and  
seal the joint. Make sure it is level. Route the  
condensatefromthetraptoasuitabledrain.Any  
connecting tubing or hose must have the outlet  
below the trap level for proper drainage.  
1000  
760  
Low  
2.5 Ton  
3 Ton  
Black  
Red  
High  
1000  
760  
Low  
Black  
T1  
High  
1000  
750  
Low  
T2  
Med/Low  
Medium  
Med/High  
High  
1,000  
1,140  
1,300  
1,350  
1,340  
1,450  
1,650  
1,750  
1,965  
1,340  
1,450  
1,650  
1,750  
1,965  
3.5 Ton  
4 Ton  
Orange / T3  
Red / T4  
T5  
T1  
Low  
Orange / T2  
Red / T3  
T4  
Med/Low  
Medium  
Med/High  
High  
WARNING:  
T5  
Turnoffelectricalpowerbeforeservic-  
ing controls. Severe electrical shock  
may result unless power is turned off.  
Unit must be installed in compliance  
withtheNationalElectricalCode(NEC)  
and local codes.  
T1  
Low  
T2  
Med/Low  
Medium  
Med/High  
High  
5 Ton  
Orange / T3  
Red / T4  
T5  
Figure 7. Standard Motor Lead Connection  
Elbow  
High Voltage  
Low Voltage  
P-Trap  
Figure 8. Drain Trap  
Figure 9. Power Entry  
7
Y terminals respectively on the thermostat  
subbase. Connect the green wire to the  
yellow wire at the unit. See the instruction  
sheetpackedwiththethermostatfordetailed  
methods of mounting.  
ELECTRICAL CONNECTIONS  
1. ELECTRICAL SERVICE  
High Voltage  
a. Install a branch circuit disconnect of ad-  
equatesizeperNEC.Locatethedisconnect  
within sight of the unit.  
b. Extend leads through power wiring hole  
provided.Connect L1 and L2 directly to the  
contactor. (See Figure 9).  
Note:The cooling-only thermostat must be  
connected to an interlock switch to prevent  
simultaneous operation of the furnace and  
the air conditioner. (See Figure 1, Page  
2.)  
c. Ground the air conditioning unit using the  
green grounding screw provided in the  
control panel.  
b. Connect the Heat-CoolThermostat: The  
heat-cool thermostat is equipped with a  
systemHEAT-COOLswitch,whichprovides  
a positive means of preventing simultane-  
ous operation of the heating and cooling  
units.The thermostat is also equipped with  
an ON-AUTO fan switch which allows the  
home owner to operate the indoor blower  
when air circulation is desired.  
Low Voltage  
a. Route24vcontrolwiresthroughthesealing  
grommet near the power entrance.  
b. Connect the control wires to the leads in  
the low voltage area. (See Figure 10).  
2. OVERCURRENT PROTECTION  
Connect the red, yellow, green and brown  
low voltage wires to the R or RC, Y, G and  
W terminals respectively on the thermostat  
base.The black wire is the 24 volt common  
required on some thermostats. See ther-  
mostat instruction sheet for more detailed  
information.  
In general, the best fuse or breaker for any air  
conditioner is the smallest size that will permit  
the equipment to run under normal use and  
service without nuisance trips. Such a device,  
sized properly, gives maximum equipment  
protection. The principal reason for specifying  
a time delay type is to prevent nuisance trips  
when the unit starts.  
Refer to furnace installation instructions  
for required connections and proper heat  
anticipator setting when installing unit with  
an external furnace.  
In the event that a fuse does blow or a breaker  
trips, always determine the reason. Do not arbi-  
trarily put in a larger fuse or breaker and do not,  
in any case, exceed the maximum size listed on  
the data label of the unit.  
c. If two stage heating is desired, an  
optional outdoor thermostat may be  
installed: Connect the thermostat to the  
orange low voltage wire and theW terminal  
on the indoor thermostat base (See Figure  
10). See the thermostat instructions for  
details on setting the outdoor thermostat.  
3. LOCATING THE THERMOSTAT  
Locate the thermostat away from drafts and  
slammingdoorsandplaceitwherethereisafree  
flowofair.Mountonaninsidewallapproximately  
five feet from the floor.  
4. ELECTRIC HEAT PACKAGE (OP-  
TIONAL)  
Do not locate near a lamp, kitchen range, direct  
sunlight, or in line with air flow from supply  
registers.  
The air conditioner is shipped without an auxil-  
iary electric heat kit installed. If electric heat is  
desired, an accessory Heater Kit must be field  
installed.See Specifications Sheet for available  
kits and their applications.  
a. ConnectCoolingThermostat:Thecooling  
thermostatavailableforusewiththissystem  
is equipped with a selector switch. To shut  
down the air conditioner, set the selector  
switch to the OFF position.Connect the red  
and yellow wires from the unit to the R and  
Select the correct size heat package for the  
installation.  
8
4 Wire Heat/Cool Thermostat  
2 Wire Cooling Thermostat  
Control Wire Legend  
Green - Blower Relay  
Single Stage Electric Heat  
Red - Transformer  
24V  
RED  
R
RED  
R
Yellow - Cooling 1st  
Stage  
YELLOW  
GREEN  
Y
YELLOW  
GREEN  
Y
Brown - Heating 1st  
Stage  
G
W
Orange - Heating 2nd  
Stage  
BROWN  
BROWN  
ORANGE  
Two Stage Electric Heat  
RED  
R
Y
YELLOW  
GREEN  
G
W
BROWN  
ORANGE  
Optional  
Outdoor Thermostat  
(Field Supplied)  
Figure 10. Low Voltage Connections  
Follow installation instructions provided  
with each heater kit.  
Installation is most easily accomplished  
before making duct or electrical connec-  
tions.  
Is the thermostat wired correctly? Is it  
installed in a proper location?  
2. START-UP PROCEDURE  
The blower must be set to high speed for  
electric heat operation.  
a. Set the system switch to the OFF posi-  
tion.  
b. Dial thermostat setting as high as it will  
go.  
c. Turn on power supply at the disconnect  
switch.  
d. Set the system switch to ON or COOL.  
Set the temperature setting to below room  
temperature. Verify that the indoor blower,  
outdoorfan, andcompressorareenergized  
and the cooling function starts.  
e. Verify that the discharge air grilles are  
adjusted and the system is balanced.  
f. Verify that there are no air leaks in the duct  
work.  
SYSTEM OPERATION  
1. PRE-START CHECK LIST  
The following check list should be observed  
prior to starting the unit.  
Is the unit level? It should be level or  
slightly slanted toward the drain for proper  
condensate drainage.  
Is the unit installed with the proper clear-  
ances (See Figure 2)?  
g. Verify that the condensate drain is properly  
installed and that it functions correctly.  
h. Dial the thermostat higher than room tem-  
perature. The unit should stop.  
Isthewiringcorrectaccordingtothewiring  
diagram and electrical codes?  
i. Ifusingacombinationheating-coolingther-  
mostat, set to the HEAT position. Proceed  
to check for correct furnace operation.  
j. Verify that the furnace controls and burners  
or heating elements operate correctly.  
k. Instruct the owner on unit operation, filter  
servicing, and proper thermostat opera-  
tion.  
Areallthewiringconnectionstight?Check  
the condenser fan to make sure it turns  
freely.  
Is the overcurrent protection properly  
sized?  
9
13 SEER - Charging Charts  
OUTDOOR TEMPERATURE (°F)  
85 90  
2
TON  
Suct. Dis.  
70  
75  
80  
95  
100  
Dis. Dis.  
105  
Dis. Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
75  
77  
79  
81  
83  
85  
87  
89  
91  
93  
95  
97  
99  
101  
142  
144  
147  
150  
153  
133  
138  
144  
147  
149  
157  
159  
161  
164  
168  
136  
141  
146  
149  
152  
171  
173  
176  
179  
182  
138  
143  
148  
152  
155  
186  
188  
190  
193  
197  
200  
141  
146  
150  
154  
158  
161  
200  
202  
205  
208  
211  
215  
144  
148  
152  
156  
160  
164  
215  
217  
219  
222  
226  
229  
146  
150  
155  
159  
163  
167  
229  
231  
233  
237  
240  
244  
149  
153  
157  
161  
165  
170  
244  
246  
248  
251  
255  
258  
151  
155  
159  
163  
168  
172  
OUTDOOR TEMPERATURE (°F)  
85 90  
2-1/2  
TON  
Suct. Dis.  
70  
75  
80  
95  
100  
Dis.  
105  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
75  
77  
79  
81  
83  
85  
87  
89  
91  
93  
95  
97  
99  
101  
143  
145  
148  
149  
153  
126  
131  
137  
143  
146  
158  
161  
163  
165  
168  
130  
135  
140  
146  
149  
174  
176  
178  
180  
184  
134  
139  
144  
148  
152  
189  
191  
193  
196  
199  
203  
138  
143  
147  
151  
155  
159  
204  
206  
208  
211  
215  
218  
142  
146  
151  
155  
158  
162  
219  
221  
223  
227  
230  
234  
145  
150  
154  
158  
162  
166  
234  
236  
238  
242  
246  
249  
149  
153  
157  
161  
166  
170  
250  
252  
254  
258  
261  
265  
152  
156  
160  
165  
169  
174  
Refrigerant Charging Chart Legend for Cooling Mode of Operation  
* Note: All pressures are listed in psig. and all temperatures in °F.  
- Shaded Boxes indicate  
flooded conditions  
- Rated Design Values. Suction Pressure will be lower than design value if indoor air  
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.  
- Discharge temperatures greater than charted  
values indicate an undercharged system.  
10  
13 SEER - Charging Charts - Continued  
OUTDOOR TEMPERATURE (°F)  
3
TON  
70  
75  
80  
85  
90  
95  
Dis.  
100  
Dis.  
105  
Dis.  
Suct. Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
91  
93  
95  
147  
149  
152  
152  
156  
140  
145  
150  
159  
161  
163  
166  
168  
169  
173  
144  
149  
154  
160  
163  
180  
182  
184  
186  
189  
147  
152  
157  
162  
166  
196  
198  
200  
203  
206  
210  
151  
155  
160  
165  
168  
172  
212  
215  
217  
219  
223  
226  
154  
159  
163  
167  
171  
175  
229  
231  
233  
236  
240  
243  
157  
161  
166  
170  
174  
178  
245  
247  
249  
253  
256  
260  
160  
164  
168  
172  
177  
181  
261  
263  
265  
270  
273  
276  
163  
167  
170  
175  
180  
184  
OUTDOOR TEMPERATURE (°F)  
3-1/2  
TON  
70  
75  
80  
85  
90  
95  
Dis.  
100  
Dis.  
105  
Dis.  
Suct. Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
98  
162  
164  
167  
167  
170  
127  
133  
138  
148  
150  
179  
182  
184  
184  
188  
135  
140  
145  
152  
155  
196  
199  
201  
202  
206  
141  
146  
151  
157  
160  
213  
216  
218  
220  
223  
227  
148  
153  
157  
162  
166  
169  
230  
232  
235  
237  
241  
244  
154  
159  
163  
167  
171  
175  
247  
249  
251  
255  
258  
262  
161  
165  
169  
173  
177  
181  
264  
266  
268  
272  
276  
279  
167  
171  
175  
179  
183  
188  
281  
283  
285  
290  
293  
297  
172  
176  
180  
185  
189  
194  
Refrigerant Charging Chart Legend for Cooling Mode of Operation  
* Note: All pressures are listed in psig. and all temperatures in °F.  
- Shaded Boxes indicate  
flooded conditions  
- Rated Design Values. Suction Pressure will be lower than design value if indoor air  
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.  
- Discharge temperatures greater than charted  
values indicate an undercharged system.  
11  
13 SEER - Charging Charts - Continued  
OUTDOOR TEMPERATURE (°F)  
4
TON  
70  
75  
80  
85  
90  
95  
Dis.  
100  
Dis.  
105  
Dis.  
Suct. Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
91  
93  
95  
97  
151  
153  
156  
157  
160  
147  
152  
157  
164  
167  
169  
171  
173  
175  
179  
151  
156  
161  
167  
170  
187  
189  
191  
193  
197  
156  
161  
165  
170  
174  
204  
206  
209  
211  
215  
218  
160  
165  
169  
174  
177  
181  
222  
224  
226  
229  
233  
236  
164  
169  
173  
177  
181  
185  
240  
242  
244  
247  
251  
254  
169  
173  
177  
181  
185  
189  
257  
259  
261  
265  
269  
272  
172  
176  
180  
185  
189  
193  
275  
277  
279  
283  
287  
290  
176  
180  
184  
189  
193  
198  
OUTDOOR TEMPERATURE (°F)  
5
TON  
70  
75  
80  
85  
90  
95  
Dis.  
100  
Dis.  
105  
Dis.  
Suct. Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Dis.  
Press. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.  
68  
70  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
151  
154  
156  
157  
161  
151  
156  
162  
168  
171  
168  
170  
172  
174  
178  
155  
160  
165  
171  
174  
184  
186  
189  
191  
194  
159  
164  
169  
173  
177  
201  
203  
205  
208  
211  
215  
163  
168  
172  
176  
180  
184  
217  
219  
221  
224  
228  
231  
167  
171  
175  
179  
183  
187  
234  
236  
238  
241  
244  
248  
170  
174  
179  
183  
187  
191  
250  
252  
254  
258  
261  
265  
173  
177  
182  
186  
190  
194  
266  
268  
270  
274  
278  
281  
177  
181  
184  
189  
194  
198  
Refrigerant Charging Chart Legend for Cooling Mode of Operation  
* Note: All pressures are listed in psig. and all temperatures in °F.  
- Shaded Boxes indicate  
flooded conditions  
- Rated Design Values. Suction Pressure will be lower than design value if indoor air  
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.  
- Discharge temperatures greater than charted  
values indicate an undercharged system.  
12  
710554  
Figure 11. Wiring Diagram  
13  
K C B L A  
710589A  
Figure 12. Wiring Diagram  
14  
15  
INSTALLER  
PLEASE LEAVE THESE  
INSTALLATION INSTRUCTIONS  
WITH THE HOMEOWNER.  
708548A (Replaces 7085480)  
Specifications and illustrations subject  
to change without notice and without  
incurring obligations.  
¢708548L¤  
O'Fallon, MO  
Printed in U.S.A. (06/06)  
708548A  

Brother P2500 User Manual
Epson Stylus CX3810 User Manual
Ford MILAN 2010 User Manual
Friedrich Air Conditioner P012A User Manual
GE ASQ14AK User Manual
Heat Controller Inc Air Conditioner A MMC36FA 1 User Manual
Hitachi UC 18YG User Manual
Honeywell 11280S User Manual
Honeywell C7150B User Manual
HP Hewlett Packard OFFICEJET 7300 User Manual