Friedrich CP08E10 User Manual

Room Air Conditioner  
Service and Parts  
Manual  
0F  
Fan  
Speed  
hr  
Auto  
Swing  
Money Fan Cool  
Saver ® Only  
Temp  
Dry  
Timer  
0n/0ff  
Power  
Mode  
CP08E10 CP06E10  
CP06 CP08 SVC PARTS 2008(07/08)  
Safety Precautions  
Safety Precautions  
To prevent injury to the user or other people and property damage, the following instructions  
must be followed.  
Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness  
is classified by the following indications.  
This symbol indicates the possibility of death or serious injury.  
WARNING  
This symbol indicates the possibility of injury or damage to property only.  
CAUTION  
Meanings of symbols used in this manual are as shown below.  
Be sure not to do.  
Be sure to follow the instruction.  
WARNING  
Always install the expansion panel(s).  
Do not place the power cord near a heater.  
• Improper assembly or installation may cause  
incorrect operation, including injury, fire, and  
electric shock hazards.  
• It may cause fire and electric shock.  
Do not use the power cord near flammable  
gas or combustibles such as gasoline,  
benzene, thinner, etc.  
Do not disassemble or modify products.  
• It may cause explosion or fire.  
• It may cause failure and electric shock.  
Service Manual 3  
Safety Precautions  
Plug in the power plug  
properly.  
Do not operate or stop the  
unit by inserting or pulling  
out the power plug.  
Do not damage or use an  
unspecified power cord.  
• Otherwise, it will cause  
electric shock or fire.  
• It will cause electric shock or  
fire.  
• It will cause electric shock or  
fire.  
Do not modify power cord  
length.  
Use the air conditioner on a  
single outlet circuit.(see page 7.)  
Do not share the outlet with  
other appliances.  
Always plug into a  
grounded outlet.  
• It will cause electric shock or  
fire.  
It will cause electric shock or  
fire.  
• No grounding may cause  
electric shock.  
Ventilate before operating air Do not use the socket if it is  
Do not operate with wet  
hands or in damp  
environment.  
conditionerwhen gas goes  
out.  
loose or damaged.  
It may cause explosion, fire,  
and burn.  
• It may cause fire and electric  
shock.  
• It will cause electric shock.  
4 Room Air Conditioner  
Safety Precautions  
If water enters the product, turn off the the  
power switch of the main body of appliance.  
Contact service center after taking the power-  
plug out from the socket.  
Do not clean the air conditioner with water.  
• It will cause electric shock or failure of  
machine.  
• Water may enter the unit and degrade the  
insulation. It may cause an electric shock.  
CAUTION  
Never touch the metal parts of the unit  
when removing the filter.  
Do not block the inlet or outlet.  
• They are sharp and may cause injury.  
It may cause failure of appliance or  
performance deteriorate.  
Ensure that the outer caseis not damaged  
by age orwear.  
Be cautious not to touch the sharp edges  
when installing.  
• Leaving it damaged couldresult in the air  
conditioner falling out of the window, creating  
a safety hazard.  
It may cause injury.  
Sharp  
edges  
Service Manual 5  
Dimensions  
Dimensions  
Symbols Used in this Manual  
This symbol alerts you to the risk of electric shock.  
This symbol alerts you to hazards that could cause harm to the  
air conditioner.  
NOTICE  
This symbol indicates special notes.  
Outside Dimensions  
11  
1
525(20 /16")  
470(18 /2")  
6 Room Air Conditioner  
Specfications  
Product Specifications  
MODLES  
CP08E10  
CP06E10  
ITEMS  
POWER SUPPLY  
COOLING CAPACITY  
INPUT  
1Ø, 115, 60Hz  
(Btu/h)  
(W)  
7,800  
6,000  
560  
720  
6.8  
5.1  
RUNNING CURRENT  
E.E.R (BTU/W.h)  
(A)  
10.7  
10.8  
INDOOR ( C)  
OUTDOOR ( C)  
26.7(DB)* 19.4(WB)**  
35(DB)* 23.9(WB)**  
490g(17.3 oz) 285g(10.1 oz)  
OPERATING  
REFRIGERANT (R-22) CHARGE  
EVAPORATOR  
Ø7.0, 2ROW 14STACKS  
Ø5.0, 2ROW 16STACKS  
TURBO FAN  
CONDENSER  
FAN, INDOOR  
FAN, OUTDOOR  
PROPELLER TYPE FAN WITH SLINGER RING  
FAN SPEEDS, FAN/COOLING  
FAN MOTOR  
3/3  
6 POLES  
OPERATION CONTROL  
ROOM TEMP. CONTROL  
AIR DIRECTION CONTROL  
CONSTRUCTION  
REMOTE CONTROLLER  
THERMISTOR  
HORIZONTAL LOUVER (UP & DOWN), AUTOSWING LOUVER (RIGHT&LEFT)  
SLIDE IN-OUT CHASSIS  
COMPRESSOR  
FAN MOTOR  
OVERLOAD PROTECTOR  
PROTECTOR  
INTERNAL THERMAL PROTECTOR  
3 WIRE WITH GROUNDING  
POWER CORD  
ATTACHMENT PLUG (CORD-CONNECTED TYPE)  
DRAIN PIPE OR SPLASHED BY FAN SLINGER  
18 1/2 x 13 7/8 x 20 11/16  
DRAIN SYSTEM  
OUTSIDE DIMENSION  
(W x H x D)  
(inch)  
(mm)  
469 x 353 x 526  
* DB:Dry Bulb  
**WB:Wet Bulb  
Service Manual 7  
Operation  
Operation  
DESIGNED FOR COOLING ONLY  
POWERFUL AND INCREDIBLE COOLING  
TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE  
BUILT-IN ADJUSTABLE THERMOSTAT  
WASHABLE ONE-TOUCH FILTER  
COMPACT SIZE  
Location and Function of Controls  
Service Manual 8  
6
4
7
Power  
1
0F  
hr  
Temp  
Fan  
Speed  
2
Fan S peed  
4
Auto  
Swing  
Money Fan Cool  
Saver Only  
Mode  
Timer  
®
Temp  
5
6
3
Dry  
Auto  
Swing  
A
S wing  
Timer  
0n/0ff  
Power  
Mode  
3
2
1
5
6. AUTO SWING  
dry operation.  
This button can automatically control the air flow  
(dehumidify operation)  
direction(left+right).  
7
To receive the signal from remote controller.  
9 Room Air Conditioner  
Disassembly  
Disassembly  
Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.  
Mechanical Parts  
1. FRONT GRILLE  
1. Open the lnlet grille upward or downward.  
2. Remove the screw which fastens the front grille.  
3. Pull the front grille from the right side.  
4. Remove the front grille.  
5. Re-install the component by referring to the  
removal procedure, above.(See Figure 17)  
Figure 17  
2. CABINET  
1. After disassembling the FRONT GRILLE, remove  
the 2 screws which fasten the cabinet at both  
sides.  
2. Remove the 2 screws which fasten the cabinet at  
back.  
3. Pull the base pan forward. (See Figure 18)  
4. Remove the cabinet.  
5. Re-install the component by referring to the  
removal procedure, above.  
Figure 18  
3. CONTROL BOX  
1. Disconnect the unit from the power source.  
2. Remove the front grille.  
3. Remove the cabinet.  
4. Remove the screw which fastens the control box  
cover.  
5. Remove the housing which connects motor wire  
in the control box.  
6. Remove the 3 leads from the compressor.  
7.Discharge the capacitor by placing a 20,000  
ohmresistor across the capacitor terminals.  
8. Remove the 2 screws which fasten the control  
box.(See Figure 19)  
9. Pull the control box forward completely.  
10. Re-install the components by referring to the  
removal procedure, above. (See Figure 19)  
Figure 19  
Service Manual 10  
Disassembly  
Air Handling Parts  
1. AIR GUIDE AND BLOWER  
1. Remove the front grille.  
2. Remove the cabinet.  
3. Remove the control box.  
4. Remove the 3 screws which fasten the brace.  
5. Remove the brace.  
6. Remove the 2 screws which fasten the evaporator.  
7. Move the evaporator forward and pulling it upward  
slightly. (See Figure 20)  
8. Move the evaporator to the left carefully.  
9. Pull out the hook of orifice by pushing the tabs and  
remove it. (See Figure 21)  
Figure 20  
10. Remove the clamp with a hand plier which  
secures the blower.  
11. Remove the blower.  
12. Remove the 4 screws which fasten the air guide  
from the barrier.  
13. Move the air guide backward, pulling out from the  
base pan.  
14. Re-install the components by referring to the  
removal procedure, above.  
Figure 21  
2. FAN AND SHROUD  
1. Remove the cabinet.  
2. Remove the brace.  
3. Remove the 3 screws which fasten the condenser.  
4. Move the condenser to the left carefully.  
5. Remove the clamp which secures the fan.  
6. Remove the fan and then pull out the shroud.  
(See Figure 22)  
7. Re-install by referring to the removal procedure.  
Figure  
22  
11 Room Air Conditioner  
7—  
Disassembly  
3. MOTOR  
1. Remove the cabinet.  
2. Remove the evaporator.  
3. Remove the orifice.  
4. Remove the blower.  
5. Remove the fan.  
6. Remove the control box cover and housing of the  
motor in the control box.  
7. Remove the 2 screws which fasten the motor from  
the mount motor. (See Figure 23)  
8. Remove the motor.  
9. Re-install the components by referring to the  
removal procedure, above.(See Figure 23)  
Figure 23  
Electrical Parts  
1. OVERLOAD PROTECTOR  
1. Remove the cabinet.  
2. Remove the nut which fastens the terminal cover.  
3. Remove the terminal cover. (See Figure 24)  
4. Remove all the leads from the overload protector.  
5. Remove the overload protector.  
6. Re-install the component by referring to the  
removal procedure, above.  
Figure 24  
2. COMPRESSOR  
1. Remove the cabinet.  
2. Discharge the refrigerant system using a FreonTM  
Recovery System.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
the FreonTM. Leave the valve in place after  
servicing the system.  
3. Remove the overload protector.  
4. After purging the unit completely, unbraze the  
suction and discharge tubes at the compressor  
connections.  
5. Remove the 3 nuts and the 3 washers which  
fasten the compressor.  
6. Remove the compressor. (See Figure 25)  
7. Re-install the components by referring to the  
removal procedure, above.  
Figure 25  
Service Manual 12  
Disassembly  
3. CAPACITOR  
1. Remove the control box.  
2. Remove the screw which fasten control panel from  
control box.  
3. Remove the screw which located in the front.  
4. Open the bottom side of control box.  
5. Remove the screw and the clamp which fastens  
the capacitor.  
6. Disconnect all the leads of capacitor terminals.  
7. Re-install the components by referring to the  
removal procedure, above. (See Figure 26)  
Figure 26  
4. POWER CORD  
1. Remove the control box.  
2. Open the control box.  
3. Disconnect the grounding screw from the control  
box.  
4. Disconnect the 2 receptacles.  
5. Remove a screw which fastens the clip cord.  
(See Figure 27)  
6. Remove the power cord.  
7. Re-install the component by referring to the above  
removal procedure, above.  
(Use only one ground-marked hole  
connection.)  
for ground  
Figure 27  
8. If the supply cord of this appliance is damaged, it  
must be replaced by the special cord. (The  
special cord means the cord which has the same  
specification marked on the supply cord attached at  
the unit.)  
Refrigerating Cycle  
TM  
CAUTION: Discharge the refrigerant system using a Freon Recovery System. If there is no valve  
to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon . Leave  
TM  
the valve in place after servicing the system.  
1. CONDENSER  
1. Remove the cabinet.  
2. Remove the 3 screws which fasten the  
brace.  
3. Remove the 3 screws which fasten the condenser  
and shroud.  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the condenser  
connections.  
5. Remove the condenser carefully.  
6. Re-install the component by referring to notes.  
(See Figure 28)  
Figure 28  
Service Manual 13  
Disassembly  
2. EVAPORATOR  
1. Remove the cabinet.  
2. Remove the 2 screws which fasten the evaporator.  
3. Move the evaporator sideways carefully.  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the evaporator  
connections.  
5. Remove the evaporator carefully.  
6. Re-install the component by referring to notes.  
(See Figure 29)  
3. CAPILLARY TUBE  
1. Remove the cabinet.  
2. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the capillary  
tube.  
3. Remove the capillary tube.  
4. Re-install the component by referring to notes.  
Figure 29  
NOTICE  
remaining in the system. With valves A and B  
closed, stop the vacuum pump.  
4) Remove the hose from the vacuum pump and  
place it on the charging cylinder. See figure  
37B. Open valve C.  
Discharge the line at the manifold connection.  
5) The system is now ready for final charging.  
Replacement of the refrigeration cycle.  
1. When replacing the refrigeration cycle, be sure to  
TM  
Discharge the refrigerant system using a Freon  
recovery System.  
If there is no valve to attach the recovery system,  
install one (such as a WATCO A-1) before venting  
the Freon . Leave the valve in place after  
TM  
6. Recharge as follows :  
servicing the system.  
1) Refrigeration cycle systems are charged from  
the High-side. If the total charge cannot be put  
in the High-side, the balance will be put in the  
suction line through the access valve which you  
installed as the system was opened.  
2) Connect the charging cylinder as shown in figure  
30B.  
With valve C open, discharge the hose at the  
manifold connection.  
3) Open valve A and allow the proper charge to  
enter the system. Valve B is still closed.  
4) If more charge is required, the high-side will not  
take it. Close valve A.  
2. After discharging the unit completely, remove the  
desired component, and unbraze the pinch-off  
tubes.  
3. Solder service valves into the pinch-off tube ports,  
leaving the valves open.  
4. Solder the pinch-off tubes with Service valves.  
5. Evacuate as follows.  
1) Connect the vacuum pump, as illustrated figure  
30A.  
2) Start the vacuum pump, slowly open manifold  
valves A and B with two full turns counterclock-  
wise and leave the valves open.  
The vacuum pump is now pulling through valves  
A and B up to valve C by means of the manifold  
and entire system.  
5) With the unit running, open valve B and add the  
balance of the charge.  
a. Do not add the liquid refrigerant to the Low-side.  
b. Watch the Low-side gauge; allow pressure to  
rise to 30 lbs.  
c. Turn off valve B and allow pressure to drop.  
d. Repeat steps b. and c. until the balance of the  
charge is in the system.  
CAUTION: If high vacuum equip-  
ment is used, just crack valves A  
and B for a few minutes, then open  
slowly with the two full turns counter-  
clockwise. This will keep oil from foaming  
and being drawn into the vacuum pump.  
6) When satisfied the unit is operating correctly,  
use the pinch-off tool with the unit still running  
and clamp on to the pinch-off tube. Using a tube  
cutter, cut the pinch-off tube about 2 inches from  
the pinch-off tool. Use sil-fos braze and braze  
pinch-off tube closed. Turn off the unit, allow it to  
set for a while, and then test the leakage of the  
pinch-off connection.  
3) Operate the vacuum pump vaccum for 20 to 30  
minutes, until 600 microns of vaccum is  
obtained. Close valves A and B, and observe  
vacuum gauge for a few minutes. A rise in pres-  
sure would indicate a possible leak or moisture  
14 Room Air Conditioner  
Disassembly  
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable  
of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.  
COMPOUND GAUGE  
CONDENSER  
(HIGH PRESSURE SIDE)  
MANIFOLD  
GAUGE  
A
B
CAPILLARY TUBE  
SEE INSETS  
BELOW  
EVAPORATOR  
(LOW PRESSURE SIDE)  
COMPRESSOR  
HI  
LOW  
A
A
B
B
EXTERNAL  
VACUUM PUMP  
CHARGING  
CYLINDER  
C
Figure 30B-Charging  
Figure 30A-Pulling Vacuum  
Service Manual 15  
Schematic Diagram  
Circuit Diagram  
1
6
2
7
4
5
3
8
LOCATION  
Q'TY  
DESCRIPTION  
NO.  
1
PER SET  
POWER CORD ASSEMBLY  
FAN MOTOR  
1
1
1
1
1
1
1
1
2
3
COMPRESSOR  
4
DISPLAY P.W.B ASSEMBLY  
MAIN P.W.B ASSEMBLY  
THERMISTOR  
5
6
7
CAPACITOR  
8
OWERLOAD PROTECTOR  
Service Manual 16  
Schematic Diagram  
Electronic Control Device  
17 Room Air Conditioner  
Schematic Diagram  
Components Location(For Main P.W.B ASM)  
Service Manual 18  
Troubleshooting Guide  
Troubleshooting Guide  
Piping System  
CONDENSER COIL  
FAN  
CAPILLARY TUBE  
COMPRESSOR  
MOTOR  
BLOWER  
EVAPORATOR COIL  
Figure 38 is a brief description of the important components and their function in what is called the refrigeration  
system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.  
ROOM AIR CONITIONER  
CYCLE OF REFRIGERATION  
EVAPORATOR COILS  
CONDENSER COILS  
VAPOR INLET  
SUCTION LINE  
COOL LOW PRESSURE VAPOR  
HOT  
DISCHARGED  
AIR  
COMPLETE LIQUID  
BOIL OFF POINT  
COOLED  
AIR  
ROOM AIR HEAT LOAD  
OUTSIDE COOLING  
AIR FOR REFRIGERANT  
PASS THROUGH  
MOTOR  
COMPRESSOR  
OIL  
LIQUID  
PRESSURE  
DROP  
LIQUID OUTLET  
HIGH PRESSURE VAPOR  
(LIQUID REFRIGERANT)  
LIQUID REFRIGERANT  
LOW PRESSURE VAPOR  
CAPILLARY TUBE  
Figure 34  
19 Room Air Conditioner  
Troubleshooting Guide  
Troubleshooting Guide  
In general, possible trouble is classified in two kinds.  
The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air  
Conditioning caused by a defect in the refrigeration circuit and improper application.  
Unit runs but poor cooling.  
Ineffective Cooling  
Check cold air  
circulation for smooth  
flow.  
Check outdoor coil  
(heat exchanger) and  
fan operation.  
Check heat load  
increase.  
Clean condenser.  
Dirty indoor coil  
(heat exchanger)  
Check gas leakage.  
Repair gas leak.  
Not on separate circuit  
Malfunction of fan.  
Check inside gas  
pressure.  
Replacement of unit if  
the unit is beyond repair.  
Clogging of air filter.  
Obstruction at air outlet.  
Remove obstruction.  
Adjust refrigerant  
charge.  
Malfunction of  
compressor.  
Check clogging in refrigera-  
tion circuit.  
Replacement of  
compressor.  
Satisfactory operation  
with temperature  
Repair clogging in  
refrigeration circuit.  
difference of inlet & outlet  
air; 44~50°F (7~10°C)  
Service Manual 20  
Troubleshooting Guide  
Fails to Start  
Check of circuit breaker  
and fuse.  
Check of power source.  
Check of control panel  
setting.  
Check control panel.  
Compressor fails only to  
start.  
Fan only fails to start.  
Improper wiring.  
Improper thermistor  
setting  
Drop of power voltage.  
Defect of fan motor  
capacitor.  
Defect of compressor  
capacitor.  
Loose terminal  
connection  
Irregular motor  
resistance ()  
Irregular motor  
insulation ()  
Capacitor check.  
Replacement.  
Improper wiring  
Replacement of fan motor.  
Regular but fails to start.  
Irregular motor resistance ()  
Irregular motor insulation ()  
Replacement of compressor.  
(Locking of piston, metal.)  
Replacement of compressor  
(Motor damaged).  
21 Room Air Conditioner  
Troubleshooting Guide  
ELECTRIC PARTS TROUBLESHOOTING GUIDE:  
The unit does not operate.  
Possible Trouble 1  
NO  
Check the Fuse.  
Check the wiring diagram.  
Is the Trans input power  
AC 115V?  
YES  
NO  
NO  
Check the Main  
P.W.B pattern.  
Is the Trans output power  
about AC 14V?  
Is shorted the Trans. output?  
YES  
YES  
Exchange the Trans.  
Exchange D02D~D05D.  
NO  
NO  
Is output Voltage of IC01D  
DC 12V?  
Exchange IC01D.  
YES  
Exchange IC02D.  
Is output Voltage of IC02D  
DC 5V?  
YES  
NO  
NO  
NO  
Is the reset circuit all right?  
(The No.14 of Micom  
is 5V.)  
Exchange IC01A.  
YES  
Is the  
Connect connector  
exactly.  
connection between  
Main and Display  
all right?  
YES  
Check the P.W.B  
pattern.  
Is the voltage No.18 of Micom  
DC 5V?  
YES  
Exchange Main P.W.B Ass'y.  
Service Manual 22  
Troubleshooting Guide  
The compressor does not operate.  
Set the Temp. setting to lower Temp.  
Possible Trouble 2  
Is Temp.  
setting set lower than Room  
Temp.-0.5°C?  
NO  
NO  
YES  
NO  
NO  
Is the voltage No.10  
of IC01M 0V?  
Is the voltage N0.7 of  
Is the Unit for 3 minutes  
delay?  
IC01M DC 5V?  
YES  
YES  
YES  
Check the RY-COMP.  
Check the wiring  
Diagram.  
Exchange IC01M.  
Wait 3 Minutes  
Exchange MAIN  
P.W.B Ass'y.  
The compressor always operate.  
Possible Trouble 3  
Connect LEAD Wire to  
RY-COMP again.  
NO  
Is the wire connection of  
RY-COMP all right?  
YES  
Check the RY-COMP.  
Fan does not operate.  
Possible Trouble 4  
NO  
Is the voltage NO.1 or 4  
of IC01M DC 5V?  
Exchange IC01M.  
Exchange IC01M.  
YES  
NO  
Is the voltage NO.13 or 16  
of IC01M 0V?  
YES  
Check the RY-Hi or  
RY-Lo.  
Check the wiring diagram.  
23 Room Air Conditioner  
Troubleshooting Guide  
Romote controller does not operate.  
Possible Trouble 5  
NO  
NO  
Is the voltage of Battery  
about over 2.3V?  
Exchange the battery.  
YES  
Is the voltage No.16  
of CN-DISP1 on Main P.W.B  
Ass'y DC 5V?  
Check the P.W.B pattern.  
YES  
Connect connector to  
CN-DISP1 exactly.  
NO  
Is the connection of  
CN-DISP1 all right?  
YES  
Exchange Receiver Ass'y.  
It displays abnormally on Display P.W.B Ass'y.  
Possible Trouble 6  
NO  
NO  
NO  
Exchange IC01G.  
Is the IC01G all right?  
YES  
NO  
Connect connector  
to CN-DISP1 exactly.  
Is the connection of  
CN-DISP1 all right?  
YES  
Does the Q01G,  
Q02G, Q03G Q04G operate normally  
on main P.W.B Ass'y?  
Exchange Q01G,  
Q02G, Q03G, Q04G  
YES  
Exchange the display  
P.W.B Ass'y.  
Service Manual 24  
Troubleshooting Guide  
ROOM AIR CONDITIONER VOLTAGE LIMITS  
NAME PLATE RATING  
115V ± 10%  
MINIMUM  
103.5V  
MAXIMUM  
126.5V  
COMPLAINT  
CAUSE  
REMEDY  
Fan motor will not run.  
No power  
Check voltage at outlet. Correct if none.  
Power supply cord  
Rotary switch  
Check voltage to rotary switch. If none, check  
power supply cord. Replace cord if circuit is  
open.  
Check switch continuity. Refer to wiring diagram  
for terminal identification. Replace switch if  
defective.  
Wire disconnected or  
connection loose  
Connect wire. Refer to wiring diagram for  
terminal identification. Repair or replace loose  
terminal.  
Capacitor (Discharge  
Test capacitor.  
capacitor before testing.)  
Replace if not within ±10% of manufacturer's  
rating. Replace if shorted, open, or damaged.  
Will not rotate  
Fan blade hitting shroud or blower wheel hitting  
scroll. Re-align assembly.  
Units using slinger ring condenser fans must  
have 0.22~0.25 inch clearance to the base.  
If necessary, shim up the bottom of the fan motor  
with mounting screw(s).  
Check fan motor bearings; if motor shaft will not  
rotate, replace the motor.  
Fan motor runs.  
Revolves on overload  
Check voltage. See limits on this page.  
If not within limits, call an electrician.  
Test capacitor.  
Check bearings. Does the fan blade rotate  
freely?  
If not, replace fan motor.  
Pay attention to any change from high speed to  
low speed. If the speed does not change,  
replace the motor.  
25 Room Air Conditioner  
Troubleshooting Guide  
REMEDY  
COMPLAINT  
CAUSE  
Fan motor noise.  
Fan  
If cracked, out of balance, or partially missing,  
replace it.  
Blower  
If cracked, out of balance, or partially missing,  
replace it.  
Loose set screw  
Worn bearings  
Tighten it.  
If knocking sounds continue when running or  
loose, replace the motor. If the motor hums or  
noise appears to be internal while running,  
replace motor.  
Compressor will not run,  
fan motor runs.  
Voltage  
Wiring  
Check voltage. See the limits on the preceding  
page. If not within limits, call an electrician.  
Check the wire connections; if loose, repair or  
replace the terminal. If the wires are discon-  
nected, refer to wiring diagram for identification,  
and replace the wires. Check the wire connections;  
If not according to the wiring diagram, correct  
the connections.  
Thermistor  
Check the TEMP control. If not at the lowest  
number, set TEMP control to this setting and  
restart the unit.  
Check the continuity of the thermistor. Replace  
the thermistor if the circuit is open.  
Rotary  
Check for continuity, refer to the wiring diagram  
for terminal identification. Replace the switch if  
the circuit is open.  
Thermostat  
Check the position of knob. If not at the coldest  
setting, advance the knob to this setting and  
restart the unit.  
Check the continuity of the thermostat. Replace  
the thermostat if the circuit is open.  
Capacitor (discharge  
capacitor before  
servicing.)  
Check the capacitor.  
Replace if not within ±10% of manufacturers  
rating, replace if shorted, open, or damaged.  
Compressor  
Check the compressor for open circuit or  
ground. If open or grounded, replace the  
compressor.  
Overload  
Check the compressor overload if externally mounted.  
Replace if open. (If the compressor temperature is  
high, remove the overload, cool, and retest.)  
Service Manual 26  
Troubleshooting Guide  
COMPLAINT  
CAUSE  
REMEDY  
Compressor cycles on  
overload.  
Voltage  
Check the voltage. See the limits on the  
preceding page. If voltage is not within these limits,  
call an electrician.  
Overload  
Check overload, if externally mounted.  
Replace if open. (If the compressor temperature  
is high, remove the overload, cool, and retest.)  
Compressor cycles on  
overload.  
Fan motor  
If not running, determine the cause. Replace if  
required.  
Condenser air flow  
restriction  
Remove the cabinet, inspect the interior surface  
of the condenser. If restricted, clean carefully  
with a vacuum cleaner (do not damage fins) or  
brush. Clean the interior base before  
re-assembling.  
Condenser fins  
(damaged)  
If the condenser fins are closed over a large  
area on the coil surface, head pressures will  
increase, causing the compressor to cycle.  
Straighten the fins or replace the coil.  
Capacitor  
Test the capacitor.  
Wiring  
Check the terminals. If loose, repair or replace.  
Check the system for a restriction.  
If restricted, clean or replace.  
Refrigeration system  
Air filter  
Insufficient cooling  
Excessive noise  
Unit undersized  
Blower or fan  
Determine if the unit is properly sized for the  
area to be cooled.  
Check the set screw, or clamp. If loose or miss-  
ing, correct. If the blower or fan is hitting scroll  
or barrier, rearrange the air handling parts.  
Copper tubing  
Remove the cabinet and carefully rearrange the  
tubing not to contact the cabinet,  
compressor, shroud, and barrier.  
27 Room Air Conditioner  
Exploded View  
Exploded View  
554030  
130910  
731273  
148000  
559010  
346811  
352380  
W48602  
349600  
749740  
149980  
359012  
267110  
354210  
349001  
349480  
567502  
135314  
159830  
130410  
554160  
550140  
135312  
147581  
352115-1  
352115-2  
249950  
567480  
268711-1  
552102  
W0CZZ  
552113  
352113  
238310  
146812  
264110  
35211A  
237200  
268711-2  
135510  
Ser vice Man ual 28  
ReplacementParts list  
CP06E10  
LocNo  
130410  
349001  
130910  
135312  
135314  
135510  
147581  
147582  
149980  
159830  
238310  
567480  
264110  
267110  
249950  
237200  
268711-1  
268711-2  
146812  
349600  
346811  
349480  
352380  
552102  
550140  
559010  
CP08E10  
67302905  
67303502  
67303714  
67306017  
67306110  
67400148  
67306208  
67306264  
67303104  
67304309  
67500142  
67307806  
67300020  
67307704  
67305513  
67305512  
67307621  
67307622  
67300902  
67303604  
67303005  
67303412  
67302736  
67400190  
67301901  
67303203  
DESCRIPTION  
Base Assy Single  
Damper Assembly  
Cabinet Assy Single  
Grille Assy Front  
Grille Assy Inlet  
Cover  
REMARK  
67302912  
67303502  
67303714  
67306017  
67306110  
67400148  
67306208  
67306264  
67303108  
67304309  
67500142  
67307806  
67300020  
67307704  
67305511  
67305512  
67307621  
67307622  
67300902  
67303604  
67303013  
67303412  
67302736  
67400188  
67301900  
67303203  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Louver,Horizontal  
Louver,Vertical  
Shroud  
Filter (Mech)  
Escutcheon  
Thermistor  
Power Cord Assy  
Remote Controller  
Case Assembly,Control  
Panel,Control  
PWB(PCB) Assy Display  
PWB(PCB) Assy Main  
Swing Louver Motor  
Bracket,Motor  
Motor Assy Single  
Orifice  
Duct Assembly  
Tube Assy Capillary  
Isolator Comp  
Fan Assy Axial  
359012  
148000  
567502  
W0CZZ  
731273  
W48602  
749740  
67302609  
67303901  
67301405  
67300718  
67306312  
67302500  
67304002  
67302609  
67303901  
67301406  
67302726  
67306312  
67302500  
67304002  
Fan Turbo  
Supporter  
R
R
R
R
R
R
R
O.L.P. Overload Protect  
Capacitor  
installation Kit w/Curtain  
Clamp Spring  
Upper Guide Cabinet  
29 Room Air Conditioner  
Use Factory Certified Parts...  
FRIEDRICH AIR CONDITIONING CO.  
Post Office Box 1540 4200 N. Pan Am Expressway San Antonio, Texas 78295-1540  
(210) 357-4400 FAX (210) 357-4490  
CP06 CP08 SVC PARTS 2008(07/08)  

AllerAir 9900 User Manual
Brother MFC 3340C User Manual
Danby DBD5L User Manual
Danby DPAC9030 User Manual
Energizer Battery Charger CHVCM3 User Manual
Epson S70670 User Manual
Friedrich HAZARDGARD SH15 User Manual
Garmin STYLUS NX200 User Manual
Haier 0010557172 User Manual
HP Hewlett Packard LaserJet 3200m User Manual