Friedrich CP05N10A User Manual

Room Air Conditioner  
Service and Parts  
Manual  
CP05N10A  
115 Volts  
CP05 Svc Parts 2010 (05/10)  
1. PREFACE  
This service manual provides various service information, including the mechanical and electrical parts, etc.  
This room air conditioner was manufactured and assembled under a strict quality control system.  
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.  
1.1 FEATURES  
DESIGNED FOR COOLING ONLY  
BUILT-IN ADJUSTABLE THERMOSTAT  
WASHABLE ONE-TOUCH FILTER  
COMPACT SIZE  
1.2 SPECIFICATIONS  
1.2-2 SPECIFICATIONS  
MODELS  
CP05N10A  
ITEMS  
COOLING CAPACITY (BTU/h)  
POWER SUPPLY (Phase, V, Hz)  
INPUT (W)  
5,450  
1ø, 115V, 60HZ  
510  
OPERATING CURRENT (AMP.)  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE (R410A)  
INSIDE FAN  
4.8  
CAPILLARY TUBE  
280g (9.9 oz)  
TURBO FAN  
OUTSIDE FAN  
PROPELLER FAN WITH SLINGER RING  
2-WAY (RIGHT AND LEFT)  
TOP-DOWN  
AIR DISCHARGE  
CHASSIS  
‡ꢀOVERLOAD PROTECTOR FOR COMPRESSOR  
‡ꢀ,17(51$/ꢀ3ROTECTOR FOR FAN MOTOR  
PROTECTOR  
TEMPERATURE CONTROL  
FAN MOTOR  
THERMISTOR  
4 POLES,21W  
—2—  
1.3 LOCATIONS OF CONTROLS  
1
TEMPERATURE SETTING  
• These buttons control the temperature of the room.  
The temperature can be set within a range of 60°F to 86°F, in increments of 1°F.  
2
MONEY SAVER  
The fan stops when the compressor stops cooling.  
• Approximately every 3 minutes the fan will turn on and sample the room air to determine if  
more cooling is needed.  
3
4
OPERATION MODE SELECTOR  
• Everytime you push this button, it will rotate between the COOL, FAN and DRY modes.  
ON/OFF TIMER  
ON–When the air conditioner is off, it can be set to automatically  
come on in 1 to 12 hours from its previous setting. Each touch will increase the timer by 1  
hour.  
OFF–When the air conditioner is on, it can be set to automatically  
turn off in 1 to 12 hours. Each touch will increase the timer by 1 hour. After the timer has been  
on for 30 minutes, the temperature will automatically rise 2°F, and after another 30 minutes, it  
will automatically rise 2°F again. The temperature will then stay the same until the timer goes  
OFF.  
To cancel the timer, press the TIMER pad until the display time disappears.  
5
6
POWER  
• To turn the unit ON, push the button. To turn the unit OFF, push the button again.  
• This button takes priority over any other buttons.  
• When you first turn it on, the unit is on the High cool mode and the temp. at 72°F  
FAN SPEED  
• Everytime you push this button it will rotate between the following fan speeds:  
High (F3) Low(F1) Medium (F2) High (F3)  
—3—  
2. DISASSEMBLY INSTRUCTIONS  
2.1 MECHANICAL PARTS  
2.1.1 FRONT GRILLE  
1. Pull the inlet grille forward.  
Figure 1  
2. Remove the screw securing the Front Grille. (Fig. 3)  
3. Push the grille up from the bottom and pull the top of  
the grille away from the case to lift the top tabs out of  
their slots. (Fig. 4)  
4. Carefully position the grille, bottom first, and snap back  
into place.  
5. Reposition the screw that secures the front grille  
Figure 2  
2.1.2 CABINET  
1. Disconnect the unit from the power source.  
2. Remove the front grille. (Refer to section 2.1.1)  
3. Remove 9 screws that secure the cabinet to the  
base pan and condenser. (See Figure 3)  
4. Lift the cabinet from the unit.  
5. Re-install by referring to the procedures above.  
Figure 3  
2.1.3 CONTROL PANEL  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove 1 screws that secure the control board to  
base pan and air guide. (See Figure 4)  
5. Pull the control panel toward yourself.  
NOTE : Controls, wires, and capacitor are now  
accessible for servicing. Discharge the  
capacitor before servicing. See step  
2.3.3 on page 8 for procedures.  
Figure 4  
the fan motor and compressor. (See Figure 5)  
7. Re-install components by referring to procedures  
above. (Refer to wiring diagram on page 23 in this  
manual or inside control board.)  
Figure 5  
—4—  
Figure 6  
2.2 AIR HANDLING PARTS  
2.2.1 AIR GUIDE UPPER  
1. Disconnect the unit from the power source.  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove the control panel.  
(Refer to Section 2.1.3)  
5. Remove 2 screws that secure the upper air guide  
to air guide lower. (See Figure 6)  
6. Lift upper air guide upward.  
7. Re-install by referring to the procedures above.  
Figure 7  
2.2.2 ORIFICE, TURBO FAN AND FAN  
1. Disconnect the unit from the power source.  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove the control board.  
(Refer to Section 2.1.3)  
5. Remove the air guide upper.  
(Refer to Section 2.2.1)  
6. Remove 2 screws that secure the base pan to  
condenser. (See Figure 7)  
7. Remove screw that secures the shroud to  
channel of condenser.  
Figure 8  
8. Press the snap area of shroud with your thumbs.  
This allows you to remove it from the condenser.  
9. Lift the compressor upward with the evaporator  
and condenser. (See Figure 7)  
10. Remove the orfice by pushing the snap area of  
the air guide blower. (See Figure 8)  
11. Remove the clamp springs which are clamped to  
the shaft of fan and turbo fan by hand plier. (See  
Figure 9)  
12. Pull the fan and turbo fan outward.  
13. Remove the shroud.  
14. Re-install by referring to the procedures above.  
Figure 9  
—5—  
2.2.3 MOTOR  
Figure 10  
1. Disconnect the unit from the power source.  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove the control panel.  
(Refer to Section 2.1.3)  
5. Remove the upper air guide.  
(Refer to Section 2.2.1)  
6. Remove the compressor, turbo fan, fan and  
shroud. (Refer to Section 2.2.2)  
7. Remove 2 screws that secure the motor to the  
motor mount . (See Figure 10)  
8. Remove the motor.  
9. Re-install by referring to the procedures above.  
Figure 11  
2.2.4 AIR GUIDE  
1. Disconnect the unit from the power source.  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove the control panel.  
(Refer to Section 2.1.3)  
5. Remove the upper air guide .  
(Refer to Section 2.2.1)  
6. Remove the compressor, turbo fan, fan and  
shroud. (Refer to Section 2.2.2)  
7. Remove the motor. (Refer to Section 2.2.3)  
8. Remove 2 screws that secure the air guide to the  
base pan. (See Figure 11)  
9. Push the air guide backward and lift it upward.  
(See Figure 11)  
10. Re-install by referring to the procedures above.  
Figure 13  
Figure 12  
2.3 ELECTRICAL PARTS  
2.3.1 OVERLOAD PROTECTOR  
1. Remove the front grille and cabinet.  
(Refer to Section 2.1)  
2. Remove the nut which fastens the terminal cover.  
3. Remove the terminal cover.  
4. Remove all the leads from the overload protector.  
5. Remove the overload protector.  
6. Re-install the components by referring to the  
removal procedure above.  
(See Figure 12 and 13)  
—6—  
2.3.2 COMPRESSOR  
1. Remove the front grille and cabinet.  
Figure 14  
(Refer to Section 2.1)  
2. Discharge the refrigerant by using a refrigerant  
recovery system.  
3. Remove the overload protector.  
(Refer to Section 2.3.1)  
4. After discharging the unit completely, unbrace the  
suction and discharge pipes at the compressor  
connections.  
5. Remove 3 nuts which fasten the compressor.  
6. Remove the compressor.  
7. Re-install by referring to the removal procedure  
above. (See Figure 14)  
2.3.3 CAPACITOR  
1. Remove the cabinet. (Refer to Section 2.1.2)  
2. Remove the control panel.  
Figure 15  
(Refer to Section 2.1.3)  
3. Discharge the capacitor by placing a 20 KΩ  
resistor across the capacitor terminals.  
4. Remove the screw which fastens the capacitor  
clamp.  
5. Remove all the leads of capacitor terminals.  
6. Re-install the components by referring to the  
removal procedure above. (See Figure 15)  
2.3.4 THERMISTOR  
1. Remove the cabinet. (Refer to Section 2.1.2)  
2. Remove the control panel.  
Figure 16  
(Refer to Section 2.1.3)  
3. Disconnect the thermistor terminals from main  
P.W.B assembly.  
4. Remove the thermistor.  
5. Re-install the components by referring to the  
removal procedure above. (See Figure 16)  
Figure 17  
2.3.5 CONTROL BOARD  
1. Remove the cabinet. (Refer to Section 2.1.2)  
2. Remove the control panel.  
(Refer to Section 2.1.3)  
3. Pull the control board forward and pull out it.  
4. Remove 2 lead wire terminals.  
5. Re-install the components by referring to the  
removal procedure above. (See Figure 17)  
—7—  
Figure 18  
2.3.6 POWER CORD  
1. Disconnect the unit from source of power.  
2. Remove the front grille. (Refer to Section 2.1.1)  
3. Remove the cabinet. (Refer to Section 2.1.2)  
4. Remove a screw that secures control panel to  
base pan. (Refer to Section 2.1.3)  
5. Pulls the control board toward you.  
6. Disconnect the 2 receptacles and remove the  
grounding screw.  
7. Remove a screw securing the clip with cord to the  
control panel.  
8. Pull the power cord.  
9. Re-install by referring to procedures above.  
Figure19  
2.4 REFRIGERANT CYCLE  
2.4.1 CONDENSER  
1. Remove the cabinet. (Refer to Section 2.1.2)  
2. Discharge the refrigerant by using a refrigerant  
recovery system.  
3. Remove the air guide. (Refer to Section 2.2.1)  
4. Remove 2 screws which fasten the condenser.  
5. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the  
condenser connections.  
6. Remove the condenser.  
7. Re-install by referring to the procedures above.  
—8—  
wise. This will keep oil from foaming and being  
drawn into the vacuum pump.  
2.4.2 EVAPORATOR  
1. Remove the cabinet.  
2. Discharge the refrigerant by using a refrigerant  
recovery system.  
3. Remove the upper air guide . (Refer to Section  
2.2.1)  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube at the condenser  
connections.  
6-3. Operate the vacuum pump for 20 to 30 min-  
utes, until 600 micron vacuum is obtained.  
Close valves A and B and observe vacuum  
gauge for a few minutes.  
A rise in pressure would indicate a possible  
leak or moisture remaining in the system.  
With valves A and B closed, stop the vacuum  
pump.  
5. Remove the evaporator.  
6. Re-install by referring to the procedures above.  
6-4. Remove the hose from the vacuum pump and  
place it on the charging cylinder. See figure  
20B. Open valve C.  
2.4.3 CAPILLARY TUBE  
1. Remove the cabinet.  
Discharge the line at the manifold connection.  
6-5. The system is now ready for final charging.  
7. Recharge as follows:  
2. Discharge the refrigerant by using a refrigerant  
recovery system.  
3. Remove the upper air guide. (Refer to Section  
2.2.1)  
4. After discharging the refrigerant completely,  
unbraze the interconnecting tube of the capillary  
tube.  
5. Remove the capillary tube.  
6. Re-install by referring to the procedures above.  
7-1. Rotary compressor systems are charged from  
the high-side. If the total charge cannot be put  
in the high-side, the balance will be put in the  
suction line through the access valve which is  
installed as the system is opened.  
7-2. Connect the charging cylinder as shown in fig-  
ure20B. With valve C open, discharge the  
hose at the manifold connection.  
NOTES  
7-3. Open valve A and allow the proper charge to  
enter the system. Valve B is still closed.  
7-4. If more charge is required, the high-side will  
not take it. Close valve A.  
7-5. With the unit running, open valve B and add  
the balance of the charge.  
Replacement of the refrigeration cycle.  
1. When replacing the refrigerating cycle, be sure to  
discharge the refrigerant by using a refrigerant  
recovery system.  
2. After discharging the unit completely, remove the  
desired components, and unbraze the pinch-off  
tubes.  
3. Solder service valves into the pinch-off tube ports,  
leaving the valves open.  
4. Solder the pinch-off tubes with service valves.  
5. After completing the above procedures, the valve  
must be removed .  
a. Do not add the liquid refrigerant to the low-  
side.  
b. Watch the low-side gauge, allow pressure to  
rise to 39 lbs.  
c. Turn off valve B and allow the pressure to  
drop.  
d. Repeat steps B and C until the balance of  
the charge is in the system.  
7-6. When the unit is operating correctly, use the  
pinch-off tool with the unit still running and the  
clamp on the pinch-off tube. Using a tube cut-  
ter, cut the pinch-off tube about 2 inches from  
the pinch-off tool. Use sil-fos solder and solder  
the pinch-off tube closed. Turn off the unit,  
allow setting for a while and then test the leak-  
age of the pinch-off connection.  
6. Evacuate as follows:  
6-1. Connect the vacuum pump, as illustrated in  
figure 20A.  
6-2. Start the vacuum pump. Slowly open manifold  
valves A and B with two full turns counter-  
clockwise and leave the valves closed.  
The vacuum pump is now pulling through  
valves A and B up to valve C by means of  
manifold and the entire system.  
CAUTION : If high vacuum equipment is used,  
just crack valves A and B for a few minutes, then  
open slowly with the two full turns counter-clock-  
—9—  
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable  
of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.  
COMPOUND GAUGE  
MANIFOLD  
GAUGE  
B
A
CONDENSER  
(HIGH PRESSURE SIDE)  
SEE INSETS  
BELOW  
COMPRESSOR  
EVAPORATOR  
(LOW PRESSURE SIDE)  
CAPILLARY TUBE  
LO  
HI CHARGING CYLINDER  
A
A
B
B
EXTERNAL VACUUM PUMP  
C
Figure 20A-Pulling Vacuum  
Figure 20B-Charging  
—10—  
2.4.4 ELECTRICAL DATA  
Line Cord Plug  
Use Wall Receptacle  
Power Supply  
Do not under any  
circumstances cut  
or remove the  
grounding prong  
from the plug.  
Use 15 AMP, time  
delay fuse, or circuit  
breaker.  
Power supply cord with  
3-prong grounding plug  
Standard 125V, 3-wire grounding  
receptacle rated 15A, 125V AC  
USE OF EXTENSION CORDS  
Because of potential safety hazards, we strongly discourage the use of an extension cord. However, if you wish to use an extension  
cord, use a CSA certified/UL-listed 3-wire (grounding) extension cord, rated 15A, 125V.  
3. TROUBLESHOOTING GUIDE  
3.1 OUTSIDE DIMENSIONS (unit: mm [in])  
21  
9
21  
42 (1 /32")  
370 (14 /16")  
472 (18 9/16")  
42 (1 /32")  
3
120 (4 /4")  
3
27.5 (1 /32")  
22.5(0.8 3/32")  
155(6 3/32")  
9
370 (14 /16")  
9
472 (18 /16")  
—11—  
3.2 PIPING SYSTEM  
CONDENSER COILS  
FAN  
MOTOR  
CAPILLARY  
TUBE  
TURBO FAN  
EVAPORATOR  
COILS  
Following is a brief description of the important components and their function in what is called the refrigeration  
system. Reference should be made to Figure 21 to follow the refrigerating cycle and the flow of the refrigerant in  
the cooling cycle.  
ROOM AIR CONDITIONER  
CYCLE OF REFRIGERATION  
EVAPORATOR COILS  
CONDENSER COILS  
VAPOR INLET  
SUCTION LINE  
COOL LOW PRESSURE VAPOR  
HOT  
DISCHARGED  
AIR  
COMPLETE LIQUID  
BOIL OFF POINT  
COOLED  
AIR  
ROOM AIR HEAT LOAD  
OUTSIDE COOLING  
AIR FOR REFRIGERANT  
PASS THROUGH  
MOTOR  
DISCHARGE  
LINE  
NOT HIGH PRESSURE  
VAPOR  
COMPRESSOR  
OIL  
LIQUID  
PRESSURE  
DROP  
LIQUID OUTLET  
(LIQUID REFRIGERANT)  
HIGH PRESSURE VAPOR  
LIQUID REFRIGERANT  
LOW PRESSURE VAPOR  
CAPILLARY TUBE  
Figure 21  
—12—  
3.3 TROUBLESHOOTING GUIDE  
In general, possible trouble is classified in two kinds.  
The one is called Starting Failure which is caused by an electrical defect. The other is Ineffective Air Con-  
ditioning caused by a defect in the refrigeration circuit and improper application.  
Unit is running but cooling is ineffective.  
Ineffective Cooling  
Check cold air  
circulation for smooth  
flow.  
Check outdoor coil  
(heat exchanger) and  
fan operation.  
Check heat load  
increase.  
Clean condenser.  
Dirty indoor coil  
(heat exchanger)  
Check for gas leakage.  
Repair gas leak.  
Not on dedicated circuit.  
Malfunction of fan.  
Clogging air filter.  
Check inside gas  
pressure.  
Replacement of unit if  
the unit is beyond repair.  
Adjust refrigerant  
charge.  
Obstruction at air outlet.  
Remove obstruction.  
Malfunction of  
compressor.  
Check for restriction in refri -  
geration circuit.  
Replacement of  
compressor.  
Satisfactory operation  
with temperature  
Remove restriction in  
refrigeration circuit.  
difference of inlet & outlet  
air; 18~26°F.  
—13—  
Fails to Start  
Check of circuit breaker  
and fuse.  
Check voltage power source.  
Check control switch  
setting.  
Gas leakage of feeler  
bulb of thermostat.  
Check control switch.  
Compressor fails to  
start.  
Fan fails to start.  
Improper wiring.  
Improper thermostat  
setting  
Drop of power voltage.  
Defect of fan motor or  
capacitor.  
Defect of compressor or  
capacitor.  
Loose terminal  
connection  
Irregular motor  
resistance (Ω)  
Irregular motor  
insulation (Ω)  
Capacitor check.  
Replacement.  
Improper wiring  
Replacement of fan motor.  
Irregular motor resistance (Ω)  
Irregular motor insulation (Ω)  
Regular but fails to start.  
Replacement of compressor.  
Replacement of compressor  
(Motor damaged).  
—14—  
ROOM AIR CONDITIONER VOLTAGE LIMITS  
NAME PLATE RATING  
115V ± 10%  
MINIMUM  
103.5V  
MAXIMUM  
126.5V  
COMPLAINT  
CAUSE  
REMEDY  
Fan motor will not run.  
No power  
Check voltage at outlet. Correct if none.  
Power supply cord  
Check voltage to electronic control board. If none,  
check power supply cord. Replace cord if circuit is  
open.  
Wire disconnected or  
connection loose  
Connect wire. Refer to wiring diagram for  
terminal identification. Repair or replace loose  
terminal.  
Capacitor (Discharge  
Test capacitor.  
capacitor before testing.)  
Replace if not within ±10% of manufacturer's  
rating. Replace if shorted, open, or damaged.  
Will not rotate  
Fan blade hitting shroud or blower wheel hitting  
scroll. Re-align assembly.  
Units using slinger ring condenser fans must  
have 1/4" inch clearance to the base.  
If necessary, shim up the bottom of the fan motor  
with mounting screw(s).  
Check fan motor bearings; if motor shaft will not  
rotate, replace the motor.  
Fan motor runs.  
Revolves on overload  
Check voltage. See limits on this page.  
If not within limits, call an electrician.  
Test capacitor.  
Check bearings. Does the fan blade rotate  
freely?  
If not, replace fan motor.  
Pay attention to any change from high speed to  
low speed. If the speed does not change,  
replace the motor.  
—15—  
&203/$,17ꢀ  
&$86(ꢀ  
)DQꢀꢀEODGH  
5(0('<ꢀ  
)DQꢀPRWRUꢀQRLVHꢁ  
,IꢀFUDFNHGꢂꢀRXWꢀRIꢀEDODQFHꢂꢀRUꢀSDUWLDOO\ꢀPLVVLQJꢂꢀ  
UHSODFHꢀLWꢁꢀ  
%ORZHU wheel  
,IꢀFUDFNHGꢂꢀRXWꢀRIꢀEDODQFHꢂꢀRUꢀSDUWLDOO\ꢀPLVVLQJꢂꢀ  
UHSODFHꢀLWꢁꢀ  
/RRVHꢀVHWꢀVFUHZꢀ  
:RUQꢀEHDULQJVꢀ  
7LJKWHQꢀLWꢁꢀ  
,IꢀNQRFNLQJꢀVRXQGVꢀFRQWLQXHꢀZKHQꢀUXQQLQJꢀ  
ꢀUHSODFHꢀWKHꢀPRWRUꢁꢀ,IꢀWKHꢀPRWRUꢀKXPVꢀRUꢀ  
QRLVHꢀDSSHDUVꢀWRꢀEHꢀLQWHUQDOꢀZKLOHꢀUXQQLQJꢂꢀ  
UHSODFHꢀPRWRUꢁꢀ  
&RPSUHVVRUꢀZLOOꢀQRWꢀUXQꢂ  
IDQꢀPRWRUꢀUXQVꢁꢀ  
9ROWDJHꢀ  
:LULQJꢀ  
&KHFNꢀYROWDJHꢁꢀ6HHꢀWKHꢀOLPLWVꢀRQꢀWKHꢀSUHFHGLQJꢀ  
SDJHꢁꢀ,IꢀQRWꢀZLWKLQꢀOLPLWVꢂꢀFDOOꢀDQꢀHOHFWULFLDQꢁꢀ  
&KHFNꢀWKHꢀZLUHꢀFRQQHFWLRQVꢃꢀLIꢀORRVHꢂꢀUHSDLUꢀRUꢀ  
UHSODFHꢀWKHꢀWHUPLQDOꢁꢀ,IꢀWKHꢀZLUHVꢀDUHꢀGLVFRQꢄ  
QHFWHGꢂꢀUHIHUꢀWRꢀZLULQJꢀGLDJUDPꢀIRUꢀLGHQWLILFDWLRQꢂꢀ  
DQGꢀUHSODFHꢀWKHꢀZLUHVꢁꢀ&KHFNꢀWKHꢀZLUHꢀFRQQHFWLRQVꢃꢀ  
,IꢀQRWꢀDFFRUGLQJꢀWRꢀWKHꢀZLULQJꢀGLDJUDPꢂꢀFRUUHFWꢀ  
WKHꢀFRQQHFWLRQVꢁꢀ  
7KHUPLVWRU  
&KHFNꢀWKHꢀ7(03ꢀFRQWUROꢁꢀ,IꢀQRWꢀDWꢀWKHꢀORZHVWꢀ  
QXPEHUꢂꢀVHWꢀ7(03ꢀFRQWUROꢀWRꢀWKLVꢀVHWWLQJ.ꢀ  
&KHFNꢀWKHꢀFRQWLQXLW\ꢀRIꢀWKHꢀWKHUPLVWRUꢁꢀ5HSODFHꢀ  
WKHꢀcontrol boardꢀLIꢀWKHꢀFLUFXLWꢀLVꢀRSHQꢁ  
&DSDFLWRUꢀꢅGLVFKDUJHꢀ  
FDSDFLWRUꢀEHIRUHꢀ  
VHUYLFLQJꢁꢉꢀ  
&KHFNꢀWKHꢀFDSDFLWRUꢁꢀ  
5HSODFHꢀLIꢀQRWꢀZLWKLQꢀ“ꢆꢇꢈꢀRIꢀPDQXIDFWXUHU¶V  
UDWLQJꢂꢀUHSODFHꢀLIꢀVKRUWHGꢂꢀRSHQꢂꢀRUꢀGDPDJHGꢁꢀ  
&RPSUHVVRUꢀ  
2YHUORDGꢀ  
9ROWDJHꢀ  
&KHFNꢀWKHꢀFRPSUHVVRUꢀIRUꢀRSHQꢀFLUFXLWꢀRUꢀ  
JURXQGꢁꢀ,IꢀRSHQꢀRUꢀJURXQGHGꢂꢀUHSODFHꢀWKHꢀ  
FRPSUHVVRUꢁꢀ  
&KHFNꢀWKHꢀFRPSUHVVRUꢀRYHUORDGꢀLIꢀH[WHUQDOO\ꢀPRXQWHGꢁ  
5HSODFHꢀLIꢀRSHQꢁꢀꢅ,IꢀWKHꢀFRPSUHVVRUꢀWHPSHUDWXUHꢀLVꢀ  
KLJKꢂꢀUHPRYHꢀWKHꢀRYHUORDGꢂꢀFRROꢂꢀDQGꢀUHWHVWꢁꢉꢀ  
&RPSUHVVRUꢀF\FOHVꢀRQꢀ  
RYHUORDGꢁꢀ  
&KHFNꢀWKHꢀYROWDJHꢁꢀ6HHꢀWKHꢀOLPLWVꢀRQꢀWKHꢀ  
SUHFHGLQJꢀSDJHꢁꢀ,IꢀYROWDJHꢀLVꢀQRWꢀZLWKLQꢀWKHVHꢀOLPLWVꢂ  
FDOOꢀDQꢀHOHFWULFLDQꢁ  
2YHUORDGꢀ  
&KHFNꢀRYHUORDGꢂꢀLIꢀH[WHUQDOO\ꢀPRXQWHGꢁꢀ  
5HSODFHꢀLIꢀRSHQꢁꢀꢅ,IꢀWKHꢀFRPSUHVVRUꢀWHPSHUDWXUHꢀ  
LVꢀKLJKꢂꢀUHPRYHꢀWKHꢀRYHUORDGꢂꢀFRROꢂꢀDQGꢀUHWHVWꢁꢉꢀ  
—16—  
COMPLAINT  
CAUSE  
Fan motor  
REMEDY  
Compressor cycles on  
overload.  
If not running, determine the cause. Replace if  
required.  
Condenser air flow  
restriction  
Remove the cabinet, inspect the interior surface  
of the condenser. If restricted, clean carefully  
with a vacuum cleaner (do not damage fins) or  
brush. Clean the interior base before  
re-assembling.  
Condenser fins  
(damaged)  
If the condenser fins are closed over a large  
area on the coil surface, head pressures will  
increase, causing the compressor to cycle.  
Straighten the fins or replace the coil.  
Capacitor  
Test the capacitor.  
Wiring  
Check the terminals. If loose, repair or replace.  
Check the system for a restriction.  
If restricted, clean or replace.  
Refrigeration system  
Air filter  
Insufficient cooling  
Excessive noise  
Unit undersized  
Blower or fan  
Determine if the unit is properly sized for the  
area to be cooled.  
Check the set screw, or clamp. If loose or miss-  
ing, correct. If the blower or fan is hitting scroll  
or barrier, rearrange the air handling parts.  
Copper tubing  
Remove the cabinet and carefully rearrange the  
tubing not to contact the cabinet,  
compressor, shroud, and barrier.  
—17—  
4. CIRCUIT DIAGRAM  
WH  
(BL)  
(SMPS)  
250V/T2A  
(250V/T3.15A)  
MEZ62420702  
LOCATION  
PART NO  
CP05N10A PER SET  
67300020  
67400116  
Q'TY  
DESCRIPTION  
NO.  
1
POWER CORD ASSY  
FAN MOTOR  
1
1
1
1
1
2
3
COMPRESSOR  
CAPACITOR  
-
-
4
5
OVERLOAD PROTECTOR  
67301425  
—18—  
ꢁꢂꢀ(;3/2'('ꢀ9,(:  
ꢑꢋꢍꢑꢋꢇ  
ꢆꢊꢇꢍꢆꢇ  
ꢌꢌꢍꢇꢆꢆ  
:ꢋꢏꢐꢇꢎ  
ꢆꢋꢍꢍꢏꢇ  
ꢎꢐꢑꢆꢆꢇ  
ꢊꢋꢍꢋꢏꢇ  
ꢆꢊꢎꢆꢇꢇꢄꢆ  
ꢆꢊꢎꢆꢇꢇꢄꢎ  
ꢆꢊꢌꢊꢆꢎ  
ꢆꢋꢑꢌꢏꢎꢄ2  
ꢊꢌꢎꢊꢍꢇꢄꢆ  
ꢆꢋꢑꢌꢏꢎꢄꢆ  
145200  
ꢊꢌꢍꢇꢆꢎ  
ꢊꢋꢐꢏꢆꢆ  
:ꢋꢏꢐꢇꢎ  
ꢆꢌꢎꢊꢇꢎ  
352390-2  
ꢆꢊꢇꢋꢆꢇ  
ꢆꢊꢌꢊ0ꢊ  
:ꢇ&==  
ꢎꢐꢋꢆꢆꢇ  
ꢌꢐꢑꢌꢇꢎ  
ꢎꢊꢑꢎꢇꢇ  
ꢎꢐꢏꢑꢆꢆꢄꢎ  
567480  
ꢊꢌꢎꢆꢆ$  
ꢌꢌꢇꢆꢋꢇ  
ꢎꢊꢏꢊꢆꢇ ꢎꢐꢏꢑꢆꢆꢄꢆ  
ꢎꢋꢍꢍꢌꢇ  
²19²  
LocNo  
130410  
130910  
135312  
135303  
145200  
149980  
152302  
237200  
238310  
249950  
264110  
267110  
346811  
349480  
359012  
550140  
559011  
567480  
567502  
749740  
132100-1  
132100-2  
147582-1  
147582-2  
268711-1  
268711-2  
35211A  
352390-1  
352390-2  
W0CZZ  
W48602  
DESCRIPTION  
Base Assembly,Weld  
Cabinet  
CP05N10A  
67302931  
67303719  
67306008  
67306107  
67304600  
67305531  
67400167  
67305507  
67500149  
67305532  
67300020  
67302240  
67400116  
67303414  
67302617  
67301900  
67302613  
67307806  
67301425  
67304010  
67303800  
67303801  
67304500  
67304501  
67307611  
67307650  
67307651  
67302742  
67302743  
67300730  
67302500  
Grille Assembly,Front  
Grille,Inlet  
Link  
Shroud  
Filter,Air  
Panel,Control  
Escutcheon  
Case Assembly,Control  
Power Cord Assembly  
Remote Controller Assembly  
Motor Assembly,AC,Single  
Orifice  
Fan,Turbo  
Damper,Compressor  
Fan Assembly,Axial  
Thermistor,NTC  
Overload Protect  
Guide  
Frame Assembly  
Frame Assembly  
Louver,Vertical  
Louver,Vertical  
PCB Assembly,Display  
PCB Assembly,Main  
Tube Assembly,Suction  
Guide Assembly,Air  
Guide Assembly,Air  
Capacitor,Film,Box  
Clamp,Spring  
—20—  
Use Factory Certified Parts...  
FRIEDRICH AIR CONDITIONING CO.  
Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540  
• (210) 357-4400 • FAX (210) 357-4490  
CP05 Svc Parts 2010 (05/10)  
P/NO:MFL38735502  

Briggs Stratton 54000 User Manual
Briggs Stratton THE POWER WITHIN 650 SERIES User Manual
Bryant 538MNC User Manual
Canon Wireless Photo All In One 8335B026 User Manual
Cornelius QUANTUM SERIES User Manual
Friedrich Air Conditioner SH20L30 A User Manual
Friedrich Air Conditioner SS14 User Manual
Fujitsu Air Conditioner Halcyon Air Conditioner User Manual
Honeywell 50150 User Manual
HP Hewlett Packard LaserJet 1100A User Manual