Thru-the-Wall Series
Service and Parts
Manual
Thru-the-Wall Series
115 Volts US08B10A:Starting with serial number LFMK00001
US10B10A:Starting with serial number LGBK00003
US12B10A:Starting with serial number LGBK00001
230 Volts US10B30A
US14B30A
Starting with serial number LGBK00001
US12B30B:
Unifit. Cool (03/07)
CONTENTS
2.4 REFRIGERATION CYCLE.................................10
1. PREFACE
2.4.1 CONDENSER ......................................10
2.4.2 EVAPORATOR ....................................10
2.4.3 CAPILLARY TUBE...............................10
1.1 SAFETY PRECAUTIONS ...............................2
1.2 INSULATION RESISTANCE TEST.................2
1.3 SPECIFICATIONS ..........................................3
1.4 FEATURES.....................................................5
1.5 CONTROL LOCATIONS.................................5
3. TROUBLESHOOTING GUIDE
3.1 OUTSIDE DIMENSIONS...............................13
3.2 PIPING SYSTEM ..........................................13
3.3 TROUBLESHOOTING GUIDE......................14
2. DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS....................................6
2.1.1 FRONT GRILLE.....................................6
2.1.2 CABINET................................................6
2.1.3 CONTROL BOX.....................................6
2.2 AIR HANDLING PARTS..................................7
2.2.1 ORIFICE, HEATER ASSY AND TURBO FAN .........7
2.2.2 FAN........................................................7
2.2.3 SHROUD................................................8
2.3 ELECTRICAL PARTS.....................................8
2.3.1 MOTOR..................................................8
2.3.2 COMPRESSOR .....................................8
2.3.3 CAPACITOR ..........................................8
2.3.4 POWER CORD......................................9
2.3.5 THERMISTOR .......................................9
4. SCHEMATIC DIAGRAM
4.1 CIRCUIT DIAGRAM......................................19
5. EXPLODED VIEW..................................20
6. REPLACEMENT PARTS LIST .......21
1. PREFACE
This SERVICE MANUAL provides various service information, including the mechanical and electrical
parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
1. When servicing the unit, turn off the air conditioner
and unplug the power cord.
1.2 INSULATION RESISTANCE TEST
1. Unplug the power cord and connect a jumper
between 2 pins (black and white).
2. Observe the original lead dress.
2. The grounding conductor (green or green & yellow)
is to be open.
3. Measure the resistance value with an ohm meter
between the jumpered lead and each exposed
metallic part on the equipment.
If a short circuit is found, replace all parts which
have been overheated or damaged by the short
circuit.
3. After servicing the unit, make an insulation
resistance test to protect the customer from being
exposed to shock hazards.
4. The value should be over 1MΩ.
—2—
1.3 SPECIFICATIONS
1.3.1 FOR US08B10A/US10B10A/US12B10A
MODELS
REMARK
US08B10A
US10B10A
US12B10A
ITEMS
POWER SUPPLY
1Ø, 115V, 60Hz
9,800
COOLING CAPACITY (Btu/h)
INPUT (W)
RUNNING CURRENT (A)
8,000
11,500
1,310
830
7.5
1,110
10.2
12.0
E.E.R
(Btu/w.h)
9.6
8.8
8.8
REFRIGERANT (R-22) CHARGE(g)
545g(19.2OZ)
470g(16.6OZ)
26.7(DB) 19.4(WB)
35(DB) 23.9(WB)
500g(17.6OZ)
OPERATING
INDOOR (°C)
TEMPERATURE
EVAPORATOR
CONDENSER
FAN, INDOOR
FAN, OUTDOOR
OUTDOOR (°C)
2 ROW 12STACKS
3 ROW 12STACKS
2ROW 17STACKS, L-BENDING TYPE
LOUVERED-FIN TYPE
TURBO FAN
PROPELLER TYPE FAN WITH SLINGER-RING
3/3
FAN SPEEDS, FAN/COOLING
FAN MOTOR
6 POLES
4POLES
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
ELECTRIC
THERMISTOR
VERTICAL LOUVER(RIGHT & LEFT)
HORIZONTAL LOUVER(UP & DOWN)
TOP-DOWN
CONSTRUCTION
PROTECTOR
COMPRESSOR
FAN MOTOR
EXTERNAL OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
2.3m (3WIRES WITH GROUNDING)
ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)
SPLASHED BY FAN SLINGER
POWER CORD
DRAIN SYSTEM
NET WEIGHT
(lbs/kg)
73/33
78/35
24 x 1413/32 x 20 3/32
610 x 366 x 499
25 7/8 x 15 17/32 x 16 23/32
656 x 394 x 425
20 1/2
80/36
DIMENSION
(inch)
(W x H x D)
(mm)
(inch)
(mm)
(inch)
(mm)
SLEEVE DIMESION
(W x H x D)
OPTIONAL
PART
SLEEVE DEPTH
WITH FRONT GRILLE
521
—3—
1.3.2 FOR US10B30A/US12B30B/US14B30A
MODELS
US10B30A
US12B30B
US14B30A
REMAR
ITEMS
1Ø, 230/208V, 60Hz
11,500/11,200
1,310/1,270
POWER SUPPLY
10,000/9,800
1,060/1,040
4.7/5.2
13,200/12,800
1,550/1,500
7.1/7.6
COOLING CAPACITY
INPUT
(Btu/h)
(W)
6.0/6.4
RUNNING CURRENT
E.E.R.
(A)
9.4/9.4
8.8/8.8
8.5/8.5
(Btu/W.h)
480g(16.9OZ)
485g(17.1OZ)
26.7(DB) 19.4(WB)
35(DB) 23.9(WB)
545g(19.2OZ)
INDOOR (°C)
OUTDOOR (°C)
OPERATING
TEMPERA-TURE
REFRIGERANT (R-22) CHARGE(g)
EVAPORATOR
3 ROW 12STACKS 3 ROW 12STACKS 3 ROW 12STACKS
2ROW 17STACKS, L-BENDING TYPE
LOUVERED-FIN TYPE
CONDENSER
TURBO FAN
FAN, INDOOR
PROPELLER TYPE FAN WITH SLINGER-RING
3/3
FAN, OUTDOOR
FAN SPEEDS (FAN/COOLING/HEATING)
FAN MOTOR
6 POLES
4POLES
ELECTRIC
4POLES
OPERATION CONTROL
ROOM TEMP. CONTROL
THERMISTOR
VERTICAL LOUVER(RIGHT & LEFT)
HORIZONTAL LOUVER(UP & DOWN)
TOP-DOWN
AIR DIRECTION CONTROL
CONSTRUCTION
EXTERNAL OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
1.4m (3WIRES WITH GROUNDING)
ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)
SPLASHED BY FAN SLINGER
COMPRESSOR
PROTECTOR
FAN MOTOR
POWER CORD
DRAIN SYSTEM
78/35
80/36
24 x 14 13/32 x 20 3/32
610 x 366 x 499
25 7/8 x 15 17/32 x 16 23/32
656 x 394 x 425
20 1/2
87/40
NET WEIGHT
(lbs/kg)
(inch)
(mm)
(inch)
(mm)
(inch)
(mm)
DIMENSION
(W x H x D)
SLEEVE DIMESION
(W x H x D)
OPTIONAL
PART
SLEEVE DEPTH
WITH FRONT GRILLE
521
—4—
1.4 FEATURES
• Designed for cooling only.
• Built in adjustable THERMOSTAT.
• Washable one-touch filter.
• Compact size.
• Powerful and quiet.
• Slide out chassis for the simple installation and service.
1.5 CONTROL LOCATIONS
1.5.1 COOLING ONLY MODEL
• OPERATION
REMOTE CONTROL SIGNAL RECEIVER
TEMPERATURE SETTING
• Use this button to automatically control the temperature of the room.
The temperature can be set within a range of 60°F to 86°F by
increments of 1°F.
• The setting appears in the display.
POWER
• To turn the air conditioner ON, push this button.
To turn the air conditioner OFF, push the button again.
• This button takes priority over any other button.
• When you first turn it on, the unit is in cool mode, at High fan
speed, and set at a temperature setting of 72°F.
TIMER
- SHUT-OFF TIME
• You will usually use shut-off time while you sleep.
• If unit is running, use Timer to set number of
hours until shut-off.
• For your sleeping comfort, once Timer is set, the
Temperature setting will raise 2°F after 30 min.,
and once again after another 30 min.
FAN SPEED
• Every time you push this button, it advances the setting as follows:
{High ꢀ Low ꢀ Med ꢀ High}
....
• Push Timer button to advance setting from 1 Hour
ꢀ
2 Hours ꢀꢀ
ꢀ
12 Hours maximum.
- START TIME
• If unit is off, use Timer to set number of hours before unit starts.
ꢀ.....
• Push Timer button to advance setting from 1 Hour
ꢀ
2 Hours
ꢀ
ꢀ
12 Hours maximum.
MODE
-
Push this button to shift mode of operation from COOL ꢀꢀ MONEY SAVER ꢀ FAN.
- COOL :
• Fan runs continuously for normal cooling operation.
- MONEY SAVER:
• The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check
the room air to determine if cooling is needed.
- FAN :
• Fan-only operation.
• VENTILATION
Push the lever to the "CLOSE" position to cool, heat or recirculate room air only.
Pull the lever to the "OPEN" position to exhaust smoke or stale air from the room.
This feature is best used in conjunction with the FAN ONLY position.
CAUTION
When the air conditioner has been operating in the
cooling and is turned off or set to the fan only position,
wait at least 3 minutes before resetting to the cooling
operation again.
PULL OPEN / PUSH CLOSE
—5—
2. DISASSEMBLY INSTRUCTIONS
— Prior to disassembling the unit, make sure that the POWER is off and the power cord is unplugged from the
wall receptacle.
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Open the inlet grille downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille. (See Fig. 1)
5. Re-install the component by referring to the
removal procedure.
Figure 1
2.1.2 CABINET
1. After disassembling the FRONT GRILLE, remove
the 6 screws which fasten the cabinet at the both
sides and the top. (See Fig. 2)
Keep these for later use.
Figure 2
2.1.3 CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the screw which fasten the control
box. (See Fig. 3)
3. Pull the control box from the barrier.(See Fig.3)
4. Discharge the capacitor by placing a 20,000 ohm
resistor across the capacitor terminals.
5. Disconnect two wire housings in the control box.
6. Pull the control box forward completely.
7. Re-install the components by referring to the
removal procedure. (See Fig. 3)
Figure 3
(Refer to the circuit diagram found on page 19 in
this manual and on the control box.)
—6—
2.2 AIR HANDLING PARTS
2.2.1 ORIFICE, AND TURBO FAN
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the 2 screws which fasten the
evaporator at the left side and the right side.
(See Fig. 4)
4. Move the evaporator to the side carefully.
Figure 4
5. Remove the orifice. (See Fig. 5)
Figure 5
8. Using handheld pliers, remove the clamp which
secures the turbo fan. (See Fig. 6)
Figure 6
9. Remove the turbo fan with pliers or your hand,
without touching blades. (See Fig. 7)
10. Re-install the components by referring to the
removal procedures, above.
Figure 7
2.2.2 FAN
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace.
(Refer to section 2.2.1)
3. Remove the 7 screws which fasten the condenser.
4. Move the condenser to the side carefully.
5. Using handheld pliers, remove the clamp which
secures the fan.
6. Remove the fan. (See Fig. 8)
7. Re-install the components by referring to the
removal procedures, above.
Figure 8
—7—
2.2.3 SHROUD
1. Remove the fan. (Refer to section 2.2.2)
2. Remove the shroud. (See Fig. 9)
3. Re-install the components by referring to the
removal procedures, above.
2.3 ELECTRICAL PARTS
2.3.1 MOTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the clamp cord and disconnect the wire
housing in control box. (Refer to section 2.1.3)
3. Remove the turbo fan. (Refer to section 2.2.2)
4. Remove the fan. (Refer to section 2.2.2)
5. Remove the 4 or 2 screws which fasten the motor.
(See Fig. 10)
Figure 9
6. Remove the motor.
7. Re-install the components by referring to the
removal procedures, above.
2.3.2 COMPRESSOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant system using a FreonTM
Recovery System.
Figure 10
Install a valve for recovery before venting the
Freon. Remove the valve when finished.
3. Disconnect the 3 leads from the compressor.
4. After purging the unit completely, unbraze the
suction and discharge tubes at the compressor
connections.
5. Remove the 3 nuts and the 3 washers which
fasten the compressor. (See Fig. 11)
6. Remove the compressor.
7. Re-install the components by referring to the
removal procedures, above.
2.3.3 CAPACITOR
1. Remove the control box. (Refer to section 2.1.3)
Figure 11
2. Remove the 1 screw
3. Open the control box
4. Disconnect all the leads on the capacitor terminals.
5. Re-install the components by referring to the
removal procedures, above.
Figure 12
—8—
2.3.4 POWER CORD
1. Remove the control box. (Refer to section 2.1.3)
2. Unfold the control box. (Refer to section 2.3.3)
3. Disconnect the grounding screw from the Base
pan.
4. Disconnect 2 receptacles.
5. Remove a screw which fastens the clip cord.
6. Pull the power cord. (See Fig. 13)
7. Re-install the components by referring to the
removal procedure, above.
(Use only one ground-marked hole, , for ground
connection.)
8. If the supply cord of this appliance is damaged, it
must be replaced with the factory-authorized and
specified cord.
Figure 13
2.3.5 ELECTRONIC CONTROL BOARD
1. Remove the control box. (Refer to section 2.1.3)
2. Unfold the control box. (Refer to section 2.3.3)
3. Disconnect all the leads of Electronic control board
terminals.
4. Remove the Electronic control board. (See Fig. 14)
5. Re-install the components by referring to the
removal procedures, above.
Figure 14
—9—
2.4 REFRIGERATION CYCLE
CAUTION
TM
Discharge the refrigerant system using a Freon
Recovery System.
Install a valve for the recovery, before venting
the Freon, remove the valve when finished.
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace.
(Refer to section 2.2.1)
3. Remove the 7 screws which fasten the condenser.
4. After discharging the refrigerant completely into a
FreonTM Recovery System, unbraze the
interconnecting tube at the condenser
connections.
5. Remove the condenser.
6. Re-install the components by referring to the notes
– on pages 11-13. (See Fig. 15)
Figure 15
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant completely – into a
FreonTM Recovery System.
3. Remove the 2 screws which fasten the evaporator
at the left side and the right side.
4. Move the evaporator to the side carefully and then
unbraze the interconnecting tube at the evaporator
connectors.
5. Remove the evaporator.
6. Re-install the components by referring to the notes
– on pages 11-13. (See Fig. 16)
Figure 16
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2.1.2)
2. After discharging the refrigerant completely – into
a FreonTM Recovery System, unbraze the
interconnecting tube at the capillary tube.
3. Remove the capillary tube.
4. Re-install the components by referring to the notes
– on page 11-13.
—10—
NOTES
— Replacement of the refrigeration cycle.
1. When replacing refrigeration components, be sure
to discharge the refrigerant system using a FreonTM
recovery System.
Install a valve for the recovery, before venting the
Freon, remove the valve when finished.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the
High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in Fig. 17B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, and the high-side will
not
1) Connect the vacuum pump, as illustrated Fig.
17A.
take it. Close valve A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
5) With the unit running, open valve B and add the
balance of the charge.
counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the
charge is in the system.
CAUTION
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test for leakage add the
pinch-off connection.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum is obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See Fig. 17B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
—11—
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool
capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service
valve.
COMPOUND GAUGE
CONDENSER
(HIGH PRESSURE SIDE)
MANIFOLD
GAUGE
A
B
CAPILLARY TUBE
SEE INSETS
BELOW
EVAPORATOR
(LOW PRESSURE SIDE)
COMPRESSOR
HI
LOW
A
B
A
B
EXTERNAL
VACUUM PUMP
CHARGING
CYLINDER
C
Figure 17A-Pulling Vacuum
Figure 17B-Charging
—12—
3. TROUBLESHOOTING GUIDE
3.1 OUTSIDE DIMENSIONS
20-3/32"
24"
(610mm)
(499mm)
3.2 PIPING SYSTEM
CONDENSER COILS
FAN
CAPILLARY TUBE
COMPRESSOR
MOTOR
TURBO FAN
EVAPORATOR COILS
: REFRIGERANT FLOW
Following is a brief description of the important components and their functions in the refrigeration system.
Refer to Fig. 18 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
ROOM AIR CONDITIONER
CYCLE OF REFRIGERATION
EVAPORATOR COILS
CONDENSER COILS
VAPOR INLET
SUCTION LINE
COOL LOW PRESSURE VAPOR
HOT
DISCHARGED
AIR
COMPLETE LIQUID
BOIL OFF POINT
COOLED
AIR
ROOM AIR HEAT LOAD
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
MOTOR
COMPRESSOR
OIL
LIQUID
PRESSURE
DROP
LIQUID OUTLET
HIGH PRESSURE VAPOR
(LIQUID REFRIGERANT)
LIQUID REFRIGERANT
LOW PRESSURE VAPOR
CAPILLARY TUBE
Figure 18
—13—
3.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
One is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning
caused by a defect in the refrigeration circuit and/or improper application.
Unit is running but cooling is ineffective
Ineffective Cooling
Check cold air circulation
for smooth flow.
Check outdoor coil
(heat exchanger) & the fan
operation.
Check heat load increase.
Unexpected residue
Overloaded Circuit
Dirty indoor coil
(Heat exchanger)
Check gas leakage.
Repair gas leak.
Malfunction of fan
Clogged air filter
Check inside gas pressure.
Replacement of unit if the
unit is beyond repair.
Obstruction at air outlet
Adjusting of refrigerant
charge
Correct above troubles
Malfunction of compressor
Check for a clog in
refrigeration circuit.
Replacement of
compressor
Satisfactory operation with
temperature difference of
inlet & outlet air ; 18-26°F
Repair for a clog in
refrigeration circuit.
—14—
Fails to Start
Check power source.
Check circuit breaker
and fuse.
Check control switch
setting.
Check control board
Only compressor fails to
start.
Only fan fails to start.
Improper wiring.
Drop in power voltage.
Improper thermostat setting
Defect of fan motor
capacitor.
Defective compressor
capacitor.
Loose terminal connection.
Improper wiring
Irregular motor resistance
(
).
Irregular motor insulation
).
Check capacitor.
Replacement.
(
Replacement of fan motor
Regular but fails to start
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor
(locking of rotor, metal)
Replacement of compressor
(Motor damaged)
—15—
COMPLAINT
CAUSE
REMEDY
Fan motor will not run.
No power
Check voltage at outlet. Correct if none.
Power supply cord
Rotary switch
Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open.
Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if
defective.
Wire disconnected or
connection loose
Connect wire. Refer to wiring diagram for terminal
identification. Repair or replace loose terminal.
Capacitor (Discharge
Test capacitor.
capacitor before testing.)
Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Will not rotate
Fan blade hitting shroud or blower wheel hitting
scroll. Realign assembly.
Units using slinger ring condenser fans must
have 1/4 to 5/16 inch clearance to the base. If it is
hitting the base, shim up the bottom of the fan
motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not
rotate, replace the motor.
Fan motor runs
intermittently
Cycles on overload.
Check voltage. See limits on page 17. If not within
limits, call an electrician.
Test capacitor.
Check bearings. Does the fan blade rotate freely?
If not, replace fan motor.
Pay attention to any change from high speed to
low speed. If the speed does not change, replace
the motor.
Fan motor noise.
Grommets
Fan
Check grommets; if worn or missing, replace them.
If cracked, out of balance, or partially missing,
replace it.
Turbo fan
If cracked, out of balance, or partially missing,
replace it.
Loose set screw
Worn bearings
Tighten it.
If knocking sounds continue when running or
loose, replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
—16—
COMPLAINT
CAUSE
REMEDY
Compressor will not run,
but fan motor runs.
Voltage
Wiring
Check voltage. See the limits on the preceding.
page. If not within limits, call an electrician.
Check the wire connections, if loose, repair or
replace the terminal. If wires are off, refer to wiring
diagram for identification, and replace. Check wire
locations. If not per wiring diagram, correct.
Rotary
Check for continuity, refer to the wiring diagram
for terminal identification. Replace the switch if
circuit is open.
Capacitor (Discharge
capacitor before
servicing.)
Check the capacitor.
Replace if not within ±10% of manufacturers
rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Compressor
Overload
Check the compressor overload, if externally
mounted. Replace if open. (If the compressor
temperature is high, remove the overload, cool it,
and retest.)
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING
MINIMUM
MAXIMUM
126.5V
253V
115V
103.5V
187V
208/230V
—17—
REMEDY
COMPLAINT
CAUSE
Compressor cycles
on overload.
Voltage
Check the voltage. See the limits on the preced-
ing page. If not within limits, call an electrician.
Overload
Check overload, if externally mounted.
Replace if open. (If the compressor temperature
is high, remove the overload, cool, and retest.)
Fan motor
If not running, determine the cause. Replace if
required.
Condenser air flow
restriction
Remove the cabinet. Inspect the interior surface
of the condenser; if restricted, clean carefully
(do not damage fins). Clean the interior base before
reassembling.
Condenser fins
(damaged)
If condenser fins are closed over a large area
on the coil surface, head pressures will increase,
causing the compressor to cycle. Straighten the
fins or replace the coil.
Capacitor
Test capacitor.
Wiring
Refrigerating system
Air filter
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean or replace.
Insufficient cooling or
heating
Exhaust damper door
Unit undersized
Close if open.
Determine if the unit is properly sized for the area to
be cooled.
Excessive noise.
Blower or fan
Copper tubing
Check the set screw or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.
Remove the cabinet and carefully rearrange tubing
not to contact cabinet, compressor, shroud, and
barrier.
—18—
4. SCHEMATIC DIAGRAM
4.1 CIRCUIT DIAGRAM
• MODEL : US08B10A, US10B10A, US12B10A, US10B30A, US12B30B,US14B30A
—19—
5. EXPLODED VIEW
• MODEL: US08B10A, US10B10A, US12B10A, US10B30A, US12B30B,US14B30A
749180
E
152302
147581
147582-1
135303
147582-2
130900
149980
135312
346811
W48602
559010
435301
359012
W48602
435301
435300
352380
349600
731273
147900
130410
A
264110
W6631
268714
263230
B
C
567502
268712
C
o
o
l
E
n
e
v
r
e
g
S
y
a
r
F
a
n
F
1
L
F
O
W
2
M
H
F
E
3
D
H
I
G
T
i
m
e
'
F
r
M
O
D
E
T
N
E
M
P
W0CZZ
T
I
M
E
R
F
A
S
P
E
E
D
P
O
W
E
R
550140
238310
237200
267110
—20—
6. REPLACEMENT PARTS LIST
• MODEL: US08B10A
US08B10A(TXC121BPMK0.AWYBFRD)
LocNo
W0CZZ
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
147900
149980
550140
15302
FRD P/NO
67300726
67302925
67303712
67306311
67308102
67306106
67306012
67500114
67302500
67303021
67306205
67306256
67306257
67306802
67500112
67305000
67500113
67302725
67302607
67303202
67307804
67300027
67307701
67301406
67307620
67307619
67304801
67305510
Description
CAPACITOR,DRAWING
BASE ASSEMBLY,SINGLE
CABINET
REMARK
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
BARRIER,SINGLE
SHROUD
ISOLATOR,COMP
Filter,Air
352380
359012
559010
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—21—
• MODEL: US10B10A
US10B10A(TXC101BPMK0.AWYBFRD)
LocNo
W0CZZ
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
346900
149980
550140
15302
FRD P/NO
Description
CAPACITOR,DRAWING
BASE ASSEMBLY,SINGLE
CABINET
REMARK
67300724
67302926
67303712
67306311
67308102
67306106
67306012
67500114
67302500
67303023
67306205
67306250
67306256
67303606
67500112
67305000
67500113
67302724
67302607
67303202
67307804
67300027
67307701
67301409
67307620
67307619
67304801
67305510
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
MOUNT, MOTOR
SHROUD
ISOLATOR,COMP
Filter,Air
352380
359012
559010
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—22—
• MODEL: US12B10A
US12B10A(TXC081BPMK0.AWYBFRD)
LocNo
W0CZZ
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
346900
550140
149980
15302
FRD P/NO
Description
CAPACITOR,DRAWING
BASE ASSEMBLY,SINGLE
CABINET
REMARK
67300724
67302926
67303712
67306311
67308102
67306106
67306012
67500114
67302500
67303023
67306205
67306256
67306257
67303606
67305000
67500112
67500113
67302724
67302607
67303202
67307804
67300025
67307701
67301407
67307620
67307619
67304801
67305510
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
MOUNT MOTOR
ISOLATOR,COMP
SHROUD
Filter,Air
352380
359012
559010
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—23—
• MODEL: US10B30A
US10B30A(TXC103BPMK0.AWYBFRD)
DESCRIPTION
LocNo
W0CZZ
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
149980
550140
15302
FRD P/NO
67300723
REMARK
CAPACITOR,DRAWING
BASE ASSEMBLY,SINGLE
CABINET
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
67302924
67303712
67306311
67308102
67306106
67306012
67500114
67302500
67303024
67306205
67306256
67306257
67500112
67305000
67500113
67302725
67302607
67303202
67307804
67300026
67307701
67301416
67307618
67307619
67304801
67305510
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
SHROUD
ISOLATOR,COMP
Filter,Air
352380
359012
559010
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—24—
• MODEL: US12B30B
US12B30B(TXC123BPMK0.AWYBFRD)
DESCRIPTION
LocNo
W0CZZ
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
346900
149980
550140
15302
FRD P/NO
67300723
REMARK
CAPACITOR,DRAWING
BASE ASSEMBLY,SINGLE
CABINET
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
67302926
67303712
67306311
673008102
67306106
67306012
67500114
67302500
67303037
67306205
67306256
67306257
67303606
67500112
67305000
67500113
67302724
67302608
67303202
67307804
67300026
67307701
67500056
67307618
67307619
67304801
67305510
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
MOUNT MOTOR
SHROUD
ISOLATOR,COMP
Filter,Air
352380
359012
559010
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—25—
• MODEL: US14B30A
US14B30A(TXC143BPMK0.AWYBFRD)
DESCRIPTION
LocNo
130410
130900
731273
749180
135303
135312
238310
W48602
346811
147581
147582-1
147582-2
346900
149980
550140
15302
FRD P/NO
67302926
REMARK
BASE ASSEMBLY,SINGLE
CABINET
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
67303712
67306311
67308102
67306106
67306012
67500114
67302500
67303037
67306205
67306256
67306257
67303606
67500112
67305000
67500113
67302724
67302607
67303202
67300727
67307804
67300026
67307701
67301406
67307618
67307619
67304801
67305510
INSTALL PART ASSEMBLY. SINGLE
FRAME
GRILLE,INLET
GRILLE ASSEMBLY,FRONT(SINGLE)
ESCUTCHEON
CLAMP,SPRING
MOTOR ASSEMBLY,SINGLE
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
MOUNT MOTOR
SHROUD
ISOLATOR,COMP
Filter,Air
352380
359012
559010
W0CZZ
263230
264110
267110
567502
268714
268712
435301
237200
AIR GUIDE
FAN,TURBO
FAN ASSEMBLY,AXIAL
CAPACITOR,DRAWING
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
O.L.P
PWB(PCB) ASSEMBLY,MAIN
PWB(PCB) ASSEMBLY,DISPLAY
GRILLE,REAR
PANEL,CONTROL
—26—
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540
• (210) 357-4400 • FAX (210) 357-4480
P/NO.:3828A20294U
Printed in the U.S.A
UNi-fit. Cool (03/07)
|