| 	
		 2 0 11   
					Room Air Conditioners   
					T 
					e 
					m 
					p 
					e 
					r 
					a 
					t 
					u 
					r 
					e 
					C 
					o 
					o 
					le   
					r 
					W 
					a 
					rm   
					e 
					r 
					C 
					o 
					o 
					l 
					P 
					o 
					w 
					e 
					r 
					F 
					a 
					n 
					F 
					a 
					n 
					M 
					O 
					o 
					n 
					n 
					ly   
					e 
					y 
					S 
					p 
					e 
					e 
					d 
					T 
					im   
					e 
					r 
					S 
					a 
					O 
					v 
					p 
					e 
					® 
					e 
					r 
					r 
					a 
					O 
					tio   
					n 
					/ 
					n 
					S 
					ta   
					rt   
					S 
					to   
					p 
					S 
					e 
					t 
					H 
					r.   
					R-410A Models   
					Cool Only   
					115-Volt: XQ05M10 , XQ06M10 , XQ08M10 , XQ10M10   
					* * * *   
					Cool with Electric Heat   
					115-Volt: EQ08M11   
					* 
					X-Star-ServMan (1-11)   
					Last character may vary.   
					* 
				IMPORTANT SAFETY INFORMATION   
					The information contained in this manual is intended for use by a qualified service technician who is familiar   
					with the safety procedures required for installation and repair, and who is equipped with the proper tools and   
					test instruments required to service this product.   
					Installation or repairs made by unqualified persons can result in subjecting the unqualified person making   
					such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical   
					shock which can be serious or even fatal.   
					Safety warnings have been placed throughout this manual to alert you to potential hazards that may be   
					encountered. If you install or perform service on equipment, it is your responsibility to read and obey these   
					warnings to guard against any bodily injury or property damage which may result to you or others.   
					Your safety and the safety of others are very important.   
					We have provided many important safety messages in this manual and on your appliance. Always read   
					and obey all safety messages.   
					This is a Safety Alert symbol.   
					This symbol alerts you to potential hazards that can kill or hurt you and others.   
					All safety messages will follow the safety alert symbol with the word “WARNING”   
					or “CAUTION”. These words mean:   
					You can be killed or seriously injured if you do not follow instructions.   
					WARNING   
					You can receive minor or moderate injury if you do not follow instructions.   
					CAUTION   
					All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury,   
					and tell you what will happen if the instructions are not followed.   
					A message to alert you of potential property damage will have the   
					word “NOTICE”. Potential property damage can occur if instructions   
					are not followed.   
					NOTICE   
					PERSONAL INJURY OR DEATH HAZARDS   
					ELECTRICAL HAZARDS:   
					• 
					Unplug and/or disconnect all electrical power to the unit before performing inspections,   
					maintenance, or service.   
					• 
					• 
					• 
					Make sure to follow proper lockout/tag out procedures.   
					Always work in the company of a qualified assistant if possible.   
					Capacitors, even when disconnected from the electrical power source, retain an electrical charge   
					potential capable of causing electric shock or electrocution.   
					• 
					• 
					Handle, discharge, and test capacitors according to safe, established, standards, and approved   
					procedures.   
					Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary   
					to test or troubleshoot equipment with the power on to the unit.   
					2 
				• 
					• 
					Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel,   
					and sleeve on the room side of the air conditioning unit while cleaning.   
					Electrical component malfunction caused by water could result in electric shock or other electrically   
					unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Never operate the A/C unit with wet hands.   
					Use air conditioner on a single dedicated circuit within the specified amperage rating.   
					Use on a properly grounded outlet only.   
					Do not remove ground prong of plug.   
					Do not cut or modify the power supply cord.   
					Do not use extension cords with the unit.   
					Follow all safety precautions and use proper and adequate protective safety aids such as: gloves,   
					goggles, clothing, adequately insulated tools, and testing equipment etc.   
					• 
					Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   
					REFRIGERATION SYSTEM HAZARDS:   
					• 
					• 
					• 
					Use approved standard refrigerant recovering procedures and equipment to relieve pressure before   
					opening system for repair.   
					Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor   
					to moderate injury.   
					Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s flame or hot   
					surfaces can cause serious burns.   
					• 
					• 
					• 
					Make sure to protect personal and surrounding property with fire proof materials.   
					Have a fire extinguisher at hand while using a torch.   
					Provide adequate ventilation to vent off toxic fumes, and work with a qualified assistant whenever   
					possible.   
					• 
					• 
					• 
					Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for   
					leaks, flushing etc.   
					Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves,   
					safety glasses, clothing etc.   
					Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   
					MECHANICAL HAZARDS:   
					• 
					Extreme care, proper judgment and all safety procedures must be followed when testing,   
					troubleshooting, handling, or working around unit with moving and/or rotating parts.   
					• 
					Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and   
					other unit components especially the sharp fins of the indoor and outdoor coils.   
					• 
					• 
					Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc.   
					Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   
					3 
				PROPERTY DAMAGE HAZARDS   
					FIRE DAMAGE HAZARDS:   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Read the Installation/Operation Manual for this air conditioning unit prior to operating.   
					Use air conditioner on a single dedicated circuit within the specified amperage rating.   
					Connect to a properly grounded outlet only.   
					Do not remove ground prong of plug.   
					Do not cut or modify the power supply cord.   
					Do not use extension cords with the unit.   
					Failure to follow these instructions can result in fire and minor to serious property damage.   
					WATER DAMAGE HAZARDS:   
					• 
					Improper installation maintenance, or servicing of the air conditioner unit, or not following the above   
					Safety Warnings can result in water damage to personal items or property.   
					• 
					• 
					• 
					Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit.   
					Do not drill holes in the bottom of the drain pan or the underside of the unit.   
					Failure to follow these instructions can result in result in damage to the unit and/or minor to serious   
					property damage.   
					INTRODUCTION   
					This service manual is designed to be used in conjunction with the operation and installation manual provided   
					with each unit.   
					This service manual was written to assist the professional HVAC service technician to quickly and accurately   
					diagnose and repair any malfunctions of this product.   
					This manual, therefore, will deal with all subjects in a general nature. (i.e. All text will pertain to all models).   
					IMPORTANT:   
					It will be necessary for you to accurately identify the unit you are   
					servicing, so you can be certain of a proper diagnosis and repair.   
					(See Unit Identification.)   
					Compressor   
					Condenser Coil   
					Discharge Air   
					Outdoor Grille   
					Front Cover   
					System Controls   
					Evaporator Coil   
					Sleeve   
					Return Air Grille/Filter   
					Blower Wheel   
					Condenser Fan Blade   
					Blower Motor   
					Basepan   
					4 
				UNIT IDENTIFICATION   
					Model Number Code   
					X Q 08 M 1 0 A - A   
					9th Digit – Engineering Suffix   
					Indicates Modification   
					(Subject to change)   
					1st Digit – Function   
					E = Electric Heat   
					X = Straight Cool   
					8th Digit – Marketing Suffix   
					Indicates Modification   
					(Subject to change)   
					7th Digit – Options   
					0 = Straight Cool   
					1 = 1 KW Heat Strip, Nominal   
					2nd Digit   
					Q = Chassis Size   
					6th Digit – Voltage   
					1 = 115 Volts   
					5th Digit - Model Series / Year Introduced   
					3rd and 4th Digit - Approximate   
					BTU/HR in 1000s (Cooling)   
					M=2010   
					Heating BTU/Hr capacity listed in the   
					Specification/Performance Data Section   
					RAC Serial Number Identification Guide   
					Serial Number   
					Decade Manufactured   
					A 
					A 
					A 
					Y 
					00001   
					Production Run Number   
					L=0   
					A=1   
					B=2   
					C=3   
					D=4   
					E=5   
					F=6   
					G=7   
					H=8   
					J=9   
					Year Manufactured   
					Product Line   
					X-Start   
					A=1   
					B=2   
					C=3   
					D=4   
					E=5   
					F=6   
					G=7   
					H=8   
					J=9   
					K=0   
					Month Manufactured   
					A=Jan D=Apr G=Jul K=Oct   
					B=Feb E=May H=Aug L=Nov   
					C=Mar F=Jun J=Sept M=Dec   
					5 
				PERFORMANCE DATA   
					* 
					R-410A   
					REF.   
					EVAP. AIR TEMP. DEG. F   
					OPERATING PRESSURES   
					ELECTRICAL RATINGS   
					BREAKER FUSE   
					60 Hertz Amps   
					COOLING   
					PERFORMANCE DATA**   
					CONDENSER   
					TEMPERATURE DEG. F   
					Discharge Temp Suction Temp Super Heat Sub-Cooling   
					Voltage   
					Temp.   
					Locked Rotor Charge in   
					Discharge Air   
					Suction   
					Discharge   
					Amps Cool Amps Heat   
					Drop F.   
					Amps   
					OZ.   
					XQ05M10   
					57   
					54   
					51   
					47   
					49   
					23   
					26   
					29   
					33   
					31   
					117   
					120   
					119   
					131   
					120   
					133   
					152   
					160   
					176   
					162   
					60   
					63   
					63   
					59   
					60   
					5 
					19   
					18   
					25   
					32   
					27   
					157   
					150   
					138   
					132   
					133   
					410   
					410   
					420   
					490   
					420   
					4.5   
					4.9   
					6.3   
					9.8   
					24.0   
					25.0   
					32.0   
					57.0   
					32.0   
					27.0   
					21.0   
					25.5   
					24.0   
					25.5   
					115   
					115   
					115   
					115   
					115   
					15   
					15   
					15   
					15   
					15   
					* 
					XQ06M10   
					12   
					13   
					12   
					14   
					* 
					XQ08M10   
					* 
					XQ10M10   
					* 
					EQ08M11   
					7.0   
					7.6   
					* 
					Due to continuing research in new energy-saving technology, performance data and 8th and 9th character are subject to change without notice.   
					** Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R410A.   
					* 
					Energy   
					Estimated   
					Yearly   
					Operating Removal Circulation   
					Room Side   
					Air   
					Moisture   
					Net   
					Weight   
					Cooling Heating   
					Capacity Btu Capacity Btu   
					Volts   
					Rated   
					Cooling   
					Amps   
					Cooling   
					Watts   
					Heating   
					Amps   
					Heating   
					Watts   
					Ratio   
					EER   
					Model   
					COP   
					Cost   
					Pints/HR   
					CFM   
					Sleeve Lbs   
					XStar   
					® 
					XQ05M10   
					XQ06M10   
					XQ08M10   
					XQ10M10   
					5500   
					6000   
					7500   
					9500   
					— 
					— 
					— 
					— 
					115   
					115   
					115   
					115   
					4.5   
					4.9   
					6.9   
					9.0   
					491   
					500   
					701   
					970   
					— 
					— 
					— 
					— 
					— 
					— 
					— 
					— 
					11.2   
					12.0   
					10.7   
					9.8   
					$39   
					† 
					1.0   
					1.0   
					1.7   
					2.5   
					170   
					175   
					175   
					180   
					Q 
					Q 
					Q 
					Q 
					72   
					72   
					71   
					71   
					* 
					* 
					* 
					$56   
					$56   
					* 
					XStar   
					® 
					Electric Heat   
					EQ08M11 7500   
					* 
					4000   
					115   
					6.3   
					701   
					11.2   
					1290   
					2.8   
					10.7   
					$56   
					1.9   
					175   
					Q 
					72   
					As an ENERGY STAR® partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR® (#) models   
					meet the ENERGY STAR®   
					Estimated yearly operating cost based on a 2007 national average electricity cost of 10.65 cents per kWh.   
					† The estimated yearly operating cost of this model was not available at the time the range was published.   
					Installation Information / Sleeve Dimensions   
					Thru-the-wall Installation   
					Finished Hole   
					Depth Shell Depth to   
					with Front   
					Window Width   
					Minimum** Maximum Height   
					Minimum   
					Extension   
					Into Room*   
					Minimum   
					Extension   
					Outside*   
					Louvers   
					Sleeve   
					Height   
					Width   
					19   
					Width   
					Max. Depth   
					3 
					Q 
					14"   
					21 /8"   
					22"   
					42"   
					14 ¼"   
					20"   
					8 ½”   
					¾ 
					" 
					8 
					½"   
					5 
					½"   
					10 ¾"   
					* Minimum extensions when mounted in a window.   
					** Minimum widths achieved using one side curtain assembly as opposed to both in a standard installation.   
					Circuit Rating/ Breaker   
					Circuit Rating   
					Breaker or   
					T-D Fuse   
					Plug   
					Face   
					Wall Outlet   
					Appearance   
					Power Cord   
					Length (ft.)   
					Model   
					(NEMA#)   
					XQ05M10 , XQ06M10   
					, 
					7 
					* 
					* 
					XQ08M10 , XQ10M10   
					* 
					EQ08M11   
					* 
					* 
					125V - 15A   
					5 - 15P   
					6 
					Front   
					SIDE VIEW   
					( 
					Window Mounting Kits   
					Heat/Cool Models   
					Kit No.   
					EQ08M11   
					WIKQ   
					* 
					Friedrich heat/cool models include accessories for   
					thru-the-wall installation only. Window mounting requires   
					use of optional accessory kit as listed above.   
					6 
				ELECTRICAL DATA   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before service or   
					installation.   
					All electrical connections and wiring MUST be   
					installedbyaqualifiedelectricianandconformto   
					the National Electrical Code and all local codes   
					which have jurisdiction.   
					Failure to do so can result in personal injury or   
					death.   
					NOTICE   
					FIRE HAZARD   
					Not following the above WARNING could result in fire or   
					electically unsafe conditions which could cause moderate   
					or serious property damage.   
					Read, understand and follow the above warning.   
					Wire Size   
					Use ONLY wiring size recommended for single outlet branch circuit.   
					Fuse/Circuit Breaker   
					Use ONLY the correct HACR type and size fuse/circuit breaker. Read electrical ratings on unit’s   
					rating plate. Proper circuit protection is the responsibiity of the homeowner.   
					Grounding   
					Receptacle   
					Unit MUST be grounded from branch circuit through service cord to unit, or through separate   
					ground wire provided on permanently connected units. Be sure that branch circuit or general   
					purpose outlet is grounded.   
					The field supplied outlet must match plug on service cord and be within reach of service cord.   
					Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above   
					for proper receptacle and fuse type.   
					The consumer - through the AHAM Room Air Conditioner Certification Program - can   
					be certain that the AHAM Certification Seal accurately states the unit’s cooling and   
					heating capacity rating, the amperes and the energy efficiency ratio.   
					*HACR: Heating Air Conditioning and Refrigeration   
					7 
				WARNING   
					ELECTRICAL SHOCK HAZARD   
					Make sure your electrical receptacle has the same   
					configuration as your air conditioner’s plug. If   
					different, consult a Licensed Electrician.   
					Do not use plug adapters.   
					Do not use an extension cord.   
					Do not remove ground prong.   
					Always plug into a grounded 3 prong outlet.   
					Failure to follow these instructions can result in   
					electrical shock, serious injury or death.   
					8 
				How to operate the Friedrich room air conditioner (XQ models)   
					To start unit   
					Figure 3   
					8 
					9 
					2 
					3 
					4 
					1 
					If your air conditioner is installed and plugged into a proper receptacle, it is   
					readytogo. Thefirsttimetheunitisstarted, thecompressorwilldelayforthree   
					minutes. See Automatic Component Protection on the following page.   
					PM   
					X Star   
					Touch the Power button once. The unit will automatically be in Cool   
					mode with the temperature set at 75°F (24°C) and the fan speed at   
					F1, the sleep setting.   
					1 
					Power   
					To set mode of operation   
					Cool   
					When you rst turn the unit on, it will be in the Cool mode (light on), with   
					Fan   
					Speed   
					MoneySaver®   
					Mode   
					constant fan.   
					Fan Only   
					Clock   
					Touch the Mode button once to activate the MoneySaver® (light on).   
					2 
					Timer   
					On/Off   
					Set   
					Hour   
					Start Time   
					MoneySaver® is a feature that cycles the fan with the compressor   
					so that the fan does not run all the time. This saves energy and   
					improves dehumidi cation. Or you may prefer constant fan for more   
					air movement (to return to constant fan, touch the Mode button two   
					more times).   
					Stop Time   
					Temp/Hour   
					6 
					5 
					13   
					10 11 12   
					7 
					In order to run the fan by itself, do the following:   
					To set the hour clock   
					ContinuingfromMoneySaver® mode(lighton), touchtheModebutton   
					once to activate the FAN ONLY feature (light on).   
					3 
					Touch the Set Hour button to see the current setting (clock light   
					10   
					comes on). The number that is displayed is the approximate time   
					The FAN ONLY setting will circulate air in the room without the com-   
					(hour only). Use the and   
					buttons to change the settings. BE   
					pressor coming on.   
					SURE TO SET A.M. AND P.M. ACCORDINGLY. (P.M. is indicated   
					by a red light in the upper left corner of the display).   
					To adjust temperature   
					Use the Mode button to select either the COOL or MoneySaver®   
					function   
					To set the timer   
					NOTE: Set the HOUR CLOCK before attempting to set timer functions.   
					4 
					You can set the START and STOP times a minimum of one hour apart, and   
					a maximum of twenty-three hours apart.   
					COOLER – Touch the   
					button to lower the room air temperature.   
					button to raise the room air temperature.   
					and buttons at the same time to switch the   
					5 
					6 
					7 
					WARMER – Touch the   
					After setting the time, press the Set Hour button once (Start light   
					11   
					12   
					comes on). Use the   
					and   
					buttons to select the time that the   
					Press both the   
					temperature readout from Fahrenheit (°F) to Celsius (°C).   
					unit will START.   
					Repeat step 7 to switch from °C back to °F.   
					After selecting theSTARTtime, press theSetHourbutton once more   
					(Stop light comes on). Use the and buttons to select the time   
					To adjust fan speed   
					that the unit will STOP. After selecting the stopping time, press the   
					Set Hour button once.   
					Touch the FanSpeedbutton to see the current setting. Touch it again   
					to change speed. F1 is the lowest setting (SLEEP SETTING / LOW),   
					F2 is MEDIUM, and F3 is HIGH.   
					8 
					Press the Timer On/Off button (light turns on) to activate the timer   
					function. To deactivate this function, press theTimer On/Off button   
					once again (light turns off). Once the on and off times have been   
					selected, they will remain in memory and cycle daily until changed.   
					13   
					To activate Smart Fan   
					NOTE: If the unit is unplugged or the power is interrupted, the HOUR   
					must be reset or the Timer On/Off will not function when desired.   
					There is a fourth option, SF, when selecting the fan speed. This is   
					the SMART FAN function. SMART FAN DOES NOT OPERATE IN   
					CONJUCTION WITH THE FAN ONLY MODE.   
					9 
					Automatic component protection   
					Smart Fan will adjust the fan speed automatically to maintain the   
					desired comfort level. For example, if the outside doors in your home   
					are opened for an extended period of time, or more people enter a   
					room, Smart Fan may adjust to a higher fan speed to compensate   
					for the increased heat load. This keeps you from having to adjust the   
					fan speed on your own.   
					Your unit is equipped with Automatic Component Protection. To protect the   
					compressor of the unit, there is a three minute start delay if you turn the unit   
					off or if power is interrupted. The fan operation will not be affected. Also, if you   
					switch from Cool mode to Fan Only, and switch back to Cool mode, there   
					is a three minute delay before the compressor comes back on.   
					9 
				How to use the remote control (XQ models)   
					To start unit   
					To set the timer   
					NOTE: You can set the START and STOP times a minimum of one hour   
					POWER - Press the Power button once. The unit will automatically   
					start in the mode and fan speed it was last left on.   
					1 
					apart, and a maximum of 23 hours apart.   
					TIMER START - Press Start to view the current start time for cooling.   
					Continue pressing the Start button until you arrive at the start time   
					you desire. The start time for cooling will then be set.   
					9 
					To set mode of operation   
					COOL - Press the Cool button to automatically switch the operating   
					2 
					3 
					4 
					TIMER STOP - Press the Stop button. Continue pressing the Stop   
					button until you arrive at the stop time you desire. The stop time for   
					cooling will then be set.   
					10   
					11   
					mode to COOL.   
					FAN ONLY - Press the Fan Only button if you want to run the fan   
					only.   
					TIMER ON / OFF - Press the On/Off button to activate (light on) or   
					deactivate (light off) the timer. Once the on and off times have been   
					selected, they will remain in memory and cycle daily until changed.   
					MoneySaver® - Press the MoneySaver® button to activate the   
					MoneySaver® feature. This feature cycles the fan with the compres-   
					sor so that the fan does not run all the time.   
					NOTE: If the unit is unplugged or the power is interrupted, the Set Hr.   
					function must be reset or the On/Off function will not work.   
					To adjust temperature setting   
					WARMER - Press the Warmer button to raise the temperature   
					setting.   
					5 
					COOLER - Press the Cooler button to lower the temperature   
					setting.   
					6 
					Temperature   
					Cooler   
					Warmer   
					Power   
					6 
					5 
					To adjust fan speed   
					Cool   
					2 
					3 
					1 
					4 
					7 
					8 
					FAN SPEED - Press the Fan Speed button to see the current set-   
					ting. Press again to change the fan speed. F1 is the lowest setting   
					(SLEEP / LOW), F2 is MEDIUM, F3 is HIGH, and SF is the SMART   
					FAN setting.   
					7 
					Fan   
					Fan   
					Money   
					Saver®   
					Only   
					Speed   
					Timer Operation   
					On/O! Start   
					Stop Set Hr.   
					11   
					9 
					10   
					To set the hour clock   
					SET HOUR CLOCK - Press Set Hr. once to see the current clock   
					setting. Continue pressing the button until you arrive at the current   
					time (Hour only). Minutes are not shown on the display. Make sure   
					that the A.M. / P.M. setting is correct.   
					8 
					Additional RC1 wireless remote controls can be purchased from your Friedrich dealer.   
					How To Operate The EQ08   
					Function Control Knob   
					The left knob is a six position control that allows you to   
					select heat or cool in either low speed or high speed. Plus   
					you can select fan only if you wish.   
					Thermostat Knob   
					The right hand knob is the thermostat - turn it clockwise for   
					cooler, counter-clockwise for warmer.   
					10   
				ELECTRONIC CONTROL SEQUENCE OF OPERATION   
					MODE CONTROL   
					FAN ONLY MODE   
					The mode control pad(s) allow the selection of the operating   
					modes of the unit.   
					When in the FAN ONLY mode, the compressor will not   
					operate. The fan will run continuously at the user-selected   
					speed (see “Fan Speed Set” below). Smart Fan is not   
					available in FAN ONLY Mode.   
					There is a two second delay before the mode activates its   
					appropriate relay.   
					FAN SPEED SET   
					OPERATING SEQUENCE / CHARACTERISTICS   
					AND FEATURES   
					Compressor Operation   
					The run state of the compressor is determined by the   
					difference between the indoor ambient temperature and   
					the set temperature. See specific mode of operation for   
					details.   
					XQ fan speed is changed by pressing FAN SPEED button   
					and scrolling through F1, F2, F3 and SF (Smart Fan) in the   
					digital display.   
					Therewillbea2seconddelaybeforethefanspeedchanges   
					to prevent unnecessary switching of the relays during fan   
					speed selection.   
					Compressor Time Delay: 180 seconds   
					This feature is initiated every time the compressor is de-   
					energized, either due to:   
					(1) satisfying the temperature set point   
					(2) changing mode to fan only   
					SMART FAN   
					On the XQ model, smart fan is activated by pressing the   
					FAN SPEED button and scrolling through speeds until   
					“SF” appears in the digital display. Using the remote   
					control, Smart Fan is selected by the fourth push of Fan   
					Speed button.   
					(3) a power interruption or   
					(4) turning the unit off   
					Smart fan changes fan speeds based on the temperature   
					differential between the ambient and set temperatures.   
					The compressor is also time delayed for 3 minutes when the   
					control is first plugged in or power is restored after failure.   
					When the compressor cycles off as a result of satisfying the   
					“load”, the time delay is typically timed out during the off   
					cycle. Compressor time delay is bypassed by “Test Mode”.   
					CHECKING ROOM TEMPERATURE   
					Check the room temperature at the electronic control   
					pad by pressing the “FAN SPEED” button and the   
					“TEMP ” button at the same time on XQ models.   
					Return Air Temperature Sensor   
					The control range is 60°F to 90°F +/- 2.0°F.   
					The indoor temperature will display for 10 seconds. Indoor   
					temperature can be viewed in all modes, including the   
					TEST mode. The display can be changed back to SET   
					temperature by pressing any key, except the ON/OFF   
					button, or after 10 seconds has elapsed.   
					Frost Protection Sensor   
					Temperature settings:   
					Disable the compressor when sensing 30° +/- 3°F for 2   
					minutes continuously.   
					Enable compressor @ 55° +/- 5°F.   
					KEEP ALIVE   
					The fan should not be affected by the Frost Protection. It   
					should continue to function normally if freeze protection is   
					called for.   
					The electronic control has a memory to retain all functions   
					and status as set up by the user in the event of a power   
					failure. Once power is restored to the unit there is a two   
					second delay before the fan comes on and approximately   
					three minutes delay before the compressor is activated,   
					providing that the mode was set for cooling and the set   
					point temperature has not been met in the room.   
					COOL MODE FOR XQ MODELS   
					When in the COOL mode, the control will turn on the   
					compressor when the indoor temperature is 1.5°F above the   
					set point and turn off the compressor when the ambient gets   
					below the set point by 1.5°F. The fan will run continuously.   
					REBOOT/RESET THE CONTROL BOARD   
					With unit on, press “MODE” and “TEMP/HOUR ” buttons   
					simultaneously for 10 seconds. If the panel will reboot, you   
					will hear the fan come on and the temperature window   
					will read 60°F. If this happens, turn the unit off for about   
					10 seconds and then turn it back on to finish the reboot   
					cycle. If the panel does not reboot, you possibly need to   
					replace it.   
					MONEY SAVER MODE   
					When in MONEY SAVER mode, the system will be turned   
					on when the indoor temperature gets above the set point by   
					0.75°F and turns off when the indoor temperature gets below   
					the set point by 0.75°F. The fan will turn on 5 seconds before   
					the compressor and turn off 5 seconds after the compressor   
					stops. If the compressor is delayed the fan will continue to   
					run while the compressor restarts. If the thermostat remains   
					satisfied for more than approximately 9 minutes, the fan will   
					turn on for a period of 90 seconds for air sampling. Operation   
					in MONEY SAVER mode will light both the MONEY SAVER   
					and COOL indicators.   
					11   
				FUNCTIONAL COMPONENT DEFINITIONS   
					MECHANICAL COMPONENTS   
					Plenum assembly Diffuser with directional louvers used   
					to direct the conditioned airflow.   
					Blower wheel Attaches to the indoor side of the fan motor   
					shaft and is used for distributing unconditioned, room side   
					air though the heat exchanger and delivering conditioned   
					air into the room.   
					Slinger fan blade Attaches to the outdoor side of the fan   
					motor shaft and is used to move outside air through the   
					condenser coil, while slinging condensate water out of the   
					base pan and onto the condenser coil, thus lowering the   
					temperature and pressures within the coil.   
					ELECTRICAL COMPONENTS   
					Thermostat Used to maintain the specified room side   
					comfort level   
					System switch Used to regulate the operation of the fan   
					motor, thecompressorortoturntheunitoff. Fortroubleshoot-   
					ing, refer to the wiring diagrams and schematics in the back   
					of this service manual.   
					Capacitor Reduces line current and steadies the voltage   
					supply, while greatly improving the torque characteristics of   
					the fan motor and compressor motor.   
					Smart Fan   
					Automatically adjusts the fan speed to main-   
					tain the desired room temp.   
					MoneySaver® switch When engaged, it sends the power   
					supply to the fan motor through the thermostat, which allows   
					for a cycle-fan operation.   
					Fan Motor Dual-shafted fan motor operates the indoor   
					blower wheel and the condenser fan blade simultaneously.   
					Heatingelement Electricresistanceheater, availablein   
					EQ08 model.   
					Heat anticipator Used to provide better thermostat and   
					room air temperature control.   
					HERMETIC COMPONENTS   
					Compressor Motorizeddeviceusedtocompressrefrigerant   
					through the sealed system.   
					Capillarytube Acylindricalmeterdeviceusedtoevenlydis-   
					tribute the flow of refrigerant to the heat exchangers (coils.)   
					12   
				COMPONENTS TESTING   
					TESTING THE ELECTRONIC CONTROL   
					BOARDS FOR XQ MODELS   
					ERROR CODE LISTINGS   
					E1 SHORT CYCLE SITUATION: Defined as (compressor   
					powered on before the three minute time delay ten times in   
					one hour. Investigate and correct short cycling problem.   
					X Star   
					PM   
					E2 KEYBOARD STUCK ERROR: If key button(s) are   
					pressed continuously for twenty seconds or more. If MODE   
					key is stuck, unit will default to cool. Exit Error Code   
					Mode to see if error “E2” is no longer displayed and unit is   
					functioning. Replace board if “E2” still displays after exiting   
					Error Code Mode.   
					Power   
					Cool   
					Fan   
					Speed   
					MoneySaver®   
					Fan Only   
					Mode   
					Clock   
					Timer   
					On/Off   
					Set   
					Hour   
					Start Time   
					Stop Time   
					E3 FROST PROBE OPEN: Normal operation is allowed.   
					Ohm frost probe. Replace probe if ohm value not read. If   
					ohm value is present replace board.   
					Temp/Hour   
					E4 FROST PROBE SHORT: Normal operation allowed.   
					Replace probe.   
					Activating Test Mode:   
					Activate test mode by pressing at the same time the   
					“MODE” button and the “TEMP ” button on XQ   
					models. LEDs for Hour, Start, and Stop will blink 1 bps   
					while Test Mode is active.   
					E5 INDOOR PROBE OPEN: Control assumes indoor   
					ambient temperature is 90 degree F and unit will operate.   
					Ohm indoor probe. Replace probe if ohm value not read.   
					Test Mode has duration of 90 minutes. Test Mode can   
					be activated under any conditions, including Off. Test   
					Mode is cancelled by pressing the On/Off button,   
					unplugging the unit, or when the 90 minutes is timed   
					out. All settings revert to the factory default settings of   
					Cool, 75 degrees F, Timer and Set Hour features are   
					nonfunctional.   
					E6 INDOOR PROBE SHORT: Control assumes ambient   
					temperature is 90 degree F and unit will operate. Replace   
					probe.   
					NOTE: All Error Code displays for Frost & Indoor Probe   
					will allow unit to operate. Unit may or will ice up if faulty   
					components not replaced.   
					Test Mode overrides the three-minute lockout, all   
					delays for compressor and fan motor start / speed   
					change, and no delay when switching modes.   
					FROST PROBE SENSOR: disables compressor at 35   
					degrees F.   
					INDOOR PROBE SENSOR: Control range is 60°F to 90°F   
					+/- 2°F.   
					During Test Mode, the default settings are; Unit ON,   
					Money Saver ON, 60°F, and High fan speed.   
					Indoor temperature will be displayed by pressing:   
					(XQ units) The Fan Speed button and the “TEMP   
					button.   
					” 
					Activating Error Code Mode: (Submode of Test Mode)   
					Unit must be in Test Mode to enter Error Code Mode   
					The indoor temperature will be displayed for 10 seconds.   
					The display will change back to the Set Point temperature   
					by pressing any key button except for the On/Off button.   
					The indoor temperature can be viewed in all modes,   
					including test mode.   
					1. Activate Error Code Mode by pressing the “TIMER ON/   
					OFF” button on XQ models. LED for the “TIMER ON/OFF”   
					will flash 1 bps while Error Code Mode is active. Pressing   
					the “TEMP/HR   
					” button will display 00. Consecutive   
					presses will scroll through all error codes logged. Press   
					the “TEMP/HR ” button to see the reverse order of all   
					error codes logged. When the end of logged error codes is   
					reached the temperature set point will appear.   
					IMPORTANT: Error Codes are cleared from the   
					log by exiting from Error Code Mode. To exit on XQ   
					models, press Timer On/Off button. Or unplug unit to   
					exit Error Code Mode. Plug unit in after 5 seconds to   
					resume normal operation of unit.   
					13   
				COMPONENTS TESTING (Continued)   
					EQ08 SYSTEM CONTROL SWITCH - TEST   
					4. Turn thermostat knob counterclockwise to its warmest   
					position.   
					“EQ08” SYSTEM CONTROL SWITCH – TEST   
					5. Test for continuity - contacts should be open.   
					Turn knob to phase of switch to be tested. There must be   
					continuity as follows:   
					NOTE: The thermostat must be within the temperature   
					range listed to open and close.   
					1. “Fan Only” Position – between terminals “MS” and “H”   
					To maintain the comfort level desired, a cross ambient type   
					thermostat is used. The thermostat has a range from 60°   
					±2°F to 92° ±3°F. The thermostat bulb is positioned in front   
					of the evaporator coil to sense the return air temperature.   
					Thermostat malfunction or erratic operation is covered in   
					the troubleshooting section of this manual.   
					2. “Hi Cool” Position – between terminals “L1” and “C” and   
					“MS” and “H”   
					3. “Low Cool” Position – between terminals “L1” and “C”   
					and “MS” and “LO”   
					4. “Low Heat” Position – between terminals “L2” and “2”   
					and “MS” and “LO”   
					TEST:   
					Cooling/Heating Models: Remove wires from thermostat   
					and check continuity between terminal “2” (common) and   
					“3” for cooling. Check between terminals “2” (common)   
					and “1” for heating. Also check that contacts in thermostat   
					open after placing in either position. NOTE: Temperature   
					must be within range listed to check thermostat. Refer to   
					the troubleshooting section in this manual for additional   
					information on thermostat testing.   
					5. “Hi Heat” Position – between terminals “L2” and “2” and   
					“MS” and “H”   
					L1   
					System Control Switch   
					B1   
					(EQ Models)   
					L2   
					MS   
					THERMOSTAT ADJUSTMENT   
					No attempt should be made to adjust thermostat. Due   
					to the sensitivity of the internal mechanism and the   
					sophisticated equipment required to check the calibration,   
					it is suggested that the thermostat be replaced rather than   
					calibrated. Thermostat bulb must be straight to insure   
					proper performance.   
					C 
					H 
					2 
					LO   
					THERMOSTAT (“EQ08” Models)  
					This thermostat is single pole-double throw, cross ambient   
					with a range of 60° to 92°F and a differential of ±2°F. Terminal   
					“2” is common.   
					Thermostat   
					Thermostat   
					(EQ Model)   
					THERMOSTAT BULB LOCATION   
					The position of the bulb is important in order for the   
					thermostat to function properly. The bulb of the thermostat   
					should be located approximately 45° to a maximum of 60°   
					from horizontal. Also, do not allow the thermostat bulb to   
					touch the evaporator coil.  
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Disconnect power to the unit before   
					servicing. Failure to follow this warning   
					could result in serious injury or death.   
					Thermostat Bulb Location   
					(EQ Model)   
					TEST:   
					Thermostat sensor holder 020   
					to be positioned between the   
					4th and 5th and 6th and 7th   
					rows of tubes from the bottom   
					of the coil at dimension shown   
					1. Remove leads from thermostat.   
					2. Turn thermostat knob clockwise to its coldest   
					position.   
					3. Test for continuity between the two terminals. Contacts   
					should be closed.   
					14   
				COMPONENTS TESTING (Continued)   
					FAN MOTOR   
					Asinglephasepermanentsplitcapacitormotorisusedtodrive   
					the evaporator blower and condenser fan. A self-resetting   
					overload is located inside the motor to protect against high   
					temperature and high amperage conditions.  
					Many motor capacitors are internally fused. Shorting the   
					terminals will blow the fuse, ruining the capacitor. A 20,000   
					ohm 2 watt resistor can be used to discharge capacitors   
					safely. Remove wires from capacitor and place resistor   
					across terminals. When checking a dual capacitor with   
					a capacitor analyzer or ohmmeter, both sides must be   
					tested.   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Capacitor Check with Capacitor Analyzer   
					Disconnect power to the unit before   
					servicing. Failure to follow this warning   
					could result in serious injury or death.   
					The capacitor analyzer will show whether the capacitor is   
					“open” or “shorted.” It will tell whether the capacitor is within   
					its micro farads rating and it will show whether the capacitor   
					is operating at the proper power-factor percentage. The   
					instrument will automatically discharge the capacitor when   
					the test switch is released.   
					BLOWER/FAN MOTOR - TEST   
					1. Determine that capacitor is serviceable.   
					2. Disconnect fan motor wires from fan speed switch or   
					system switch.   
					Capacitor Connections   
					The starting winding of a motor can be damaged by a   
					shorted and grounded running capacitor. This damage   
					usually can be avoided by proper connection of the running   
					capacitor terminals.   
					3. Apply“live”testcordprobesonblackwireandcommon   
					terminal of capacitor. Motor should run at high speed.   
					4. Apply “live” test cord probes on red wire and common   
					terminal of capacitor. Motor should run at low speed.   
					From the supply line on a typical 230 volt circuit, a 115 volt   
					potential exists from the “R” terminal to ground through a   
					possible short in the capacitor. However, from the “S” or   
					start terminal, a much higher potential, possibly as high as   
					400 volts, exists because of the counter EMF generated   
					in the start winding. Therefore, the possibility of capacitor   
					failure is much greater when the identified terminal is   
					connected to the “S” or start terminal. The identified   
					terminal should always be connected to the supply line, or   
					“R” terminal, never to the “S” terminal.   
					5. Apply “live” test cord probes on each of the remaining   
					wires from the speed switch or system switch to test   
					intermediatespeeds.Ifthecontrolisinthe“MoneySaver”   
					mode and the thermostat calls for cooling, the fan will   
					start -thenstopafterapproximately 2minutes; thenthe   
					fan and compressor will start together approximately 2   
					minutes later.   
					Blower/Fan Motor   
					When connected properly, a shorted or grounded running   
					capacitor will result in a direct short to ground from the “R”   
					terminal and will blow the line fuse. The motor protector   
					will protect the main winding from excessive temperature.   
					Dual Rated Run Capacitor Hook-up   
					CAPACITORS   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before servicing.   
					Discharge capacitor with a 20,000 Ohm 2 Watt   
					resistor before handling.   
					Failure to do so may result in personal injury,   
					or death.   
					15   
				COMPONENTS TESTING (Continued)   
					HEATING ELEMENT  
					DRAIN PAN VALVE   
					All electric heat models are equipped with a heating element.   
					The EQ08 has a 1.15 KW element.   
					During the cooling mode of operation, condensate which   
					collects in the drain pan is picked up by the condenser fan   
					blade and sprayed onto the condenser coil. This assists   
					in cooling the refrigerant plus evaporating the water.   
					Heating Element   
					During the heating mode of operation, it is necessary that   
					water be removed to prevent it from freezing during cold   
					outside temperatures. This could cause the condenser   
					fan blade to freeze in the accumulated water and prevent   
					it from turning.   
					To provide a means of draining this water, a bellows type   
					drain valve is installed over a drain opening in the base   
					pan.   
					The heating element contains a fuse link and a heater limit   
					switch. The fuse link is in series with the power supply and   
					will open and interrupt the power when the temperature   
					reaches 199°F or a short circuit occurs in the heating   
					element. Once the fuse link separates, a new fuse link   
					must be installed.   
					This valve is temperature sensitive and will open when   
					the outside temperature reaches 40°F. The valve will   
					close gradually as the temperature rises above 40°F to   
					fully close at 60°F.   
					NOTE: Always replace with the exact replacement.   
					The heater element has a high limit control. This control   
					is a bimetal thermostat mounted in the top of the heating   
					element.   
					Bellows Assembly   
					Drain Pan Valve   
					Should the fan motor fail or filter become clogged, the high   
					limit control will open and interrupt power to the heater   
					before reaching an unsafe temperature condition.   
					The control is designed to open at 110°F ±6°F. Test   
					continuity below 110°F and for open above 110°F.   
					TESTING THE HEATING ELEMENT   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Disconnect power to the unit before   
					servicing. Failure to follow this warning   
					could result in serious injury or death.   
					Testing of the elements can be made with an ohmmeter   
					across the terminals after the connecting wires have been   
					removed. A cold resistance reading of approximately 10.11   
					ohms for the 1.15 KW heater should be registered.   
					16   
				REFRIGERATION SEQUENCE OF OPERATION   
					A good understanding of the basic operation of the   
					refrigeration system is essential for the service technician.   
					Without this understanding, accurate troubleshooting of   
					refrigeration system problems will be more difficult and time   
					consuming, if not (in some cases) entirely impossible. The   
					refrigeration system uses four basic principles (laws) in its   
					operation they are as follows:   
					The refrigerant leaves the condenser Coil through the liquid   
					line as a warm high pressure liquid. It next will pass through   
					the refrigerant drier (if so equipped). It is the function of the   
					driertotrapanymoisturepresentinthesystem,contaminants,   
					and large particulate matter.   
					The liquid refrigerant next enters the metering device. The   
					metering device is a capillary tube. The purpose of the   
					metering device is to “meter” (i.e. control or measure) the   
					quantity of refrigerant entering the evaporator coil.   
					1. “Heat always flows from a warmer body to a cooler   
					body.”   
					2. “Heat must be added to or removed from a substance   
					before a change in state can occur”   
					In the case of the capillary tube this is accomplished (by   
					design) through size (and length) of device, and the pressure   
					difference present across the device.   
					3. “Flow is always from a higher pressure area to a lower   
					pressure area.”   
					Since the evaporator coil is under a lower pressure (due to   
					the suction created by the compressor) than the liquid line,   
					the liquid refrigerant leaves the metering device entering the   
					evaporator coil. As it enters the evaporator coil, the larger   
					area and lower pressure allows the refrigerant to expand   
					and lower its temperature (heat intensity). This expansion is   
					often referred to as “boiling”. Since the unit’s blower is moving   
					indoor air across the finned surface of the evaporator coil,   
					the expanding refrigerant absorbs some of that heat. This   
					results in a lowering of the indoor air temperature, hence the   
					“cooling” effect.   
					4. “The temperature at which a liquid or gas changes state   
					is dependent upon the pressure.”   
					The refrigeration cycle begins at the compressor. Starting   
					the compressor creates a low pressure in the suction line   
					which draws refrigerant gas (vapor) into the compressor.   
					The compressor then “compresses” this refrigerant, raising   
					its pressure and its (heat intensity) temperature.   
					The refrigerant leaves the compressor through the discharge   
					Line as a hot High pressure gas (vapor). The refrigerant   
					enters the condenser coil where it gives up some of its   
					heat. The condenser fan moving air across the coil’s finned   
					surface facilitates the transfer of heat from the refrigerant to   
					the relatively cooler outdoor air.   
					The expansion and absorbing of heat cause the liquid   
					refrigerant to evaporate (i.e. change to a gas). Once the   
					refrigerant has been evaporated (changed to a gas), it is   
					heated even further by the air that continues to flow across   
					the evaporator coil.   
					When a sufficient quantity of heat has been removed from   
					the refrigerant gas (vapor), the refrigerant will “condense”   
					(i.e. change to a liquid). Once the refrigerant has been   
					condensed (changed) to a liquid it is cooled even further by   
					the air that continues to flow across the condenser coil.   
					The particular system design determines at exactly what   
					point (in the evaporator) the change of state (i.e. liquid to a   
					gas) takes place. In all cases, however, the refrigerant must   
					be totally evaporated (changed) to a gas before leaving the   
					evaporator coil.   
					The RAC design determines at exactly what point (in the   
					condenser) the change of state (i.e. gas to a liquid) takes   
					place. In all cases, however, the refrigerant must be   
					totally condensed (changed) to a Liquid before leaving the   
					condenser coil.   
					The low pressure (suction) created by the compressor   
					causes the refrigerant to leave the evaporator through the   
					suction line as a cool low pressure vapor. The refrigerant then   
					returns to the compressor, where the cycle is repeated.   
					Suction   
					Line   
					Discharge   
					Line   
					Condenser   
					Coil   
					Evaporator   
					Coil   
					Compressor   
					Metering   
					Device   
					Refrigerant Drier   
					Liquid   
					Line   
					Refrigerant   
					Strainer   
					17   
				R-410A SEALED SYSTEM REPAIR CONSIDERATIONS   
					WARNING   
					Refrigeration system under high pressure   
					Do not puncture, heat, expose to flame or incinerate.   
					Only certified refrigeration technicians should   
					service this equipment.   
					R410Asystems operate at higher pressures than   
					R22 equipment.Appropriate safe service and   
					handling practicces must be used.   
					Only use gauge sets designed for use with R410A.   
					Do not use standard R22 gauge sets.   
					The following is a list of important considerations when working with R-410A equipment   
					• 
					• 
					• 
					R-410A pressure is approximately 60% higher than R-22 pressure.   
					R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.   
					R-410A must never be pressurized with a mixture of air, it may become   
					flammable.   
					• 
					• 
					Servicing equipment and components must be specifically designed for use with R-410A and   
					dedicated to prevent contamination.   
					Manifold sets must be equipped with gauges capable of reading 750 psig (high side) and 200   
					psig (low side), with a 500-psig low-side retard.   
					• 
					• 
					Gauge hoses must have a minimum 750-psig service pressure rating   
					Recovery cylinders must have a minimum service pressure rating of 400 psig, (DOT 4BA400   
					and DOT BW400 approved cylinders).   
					• 
					• 
					POE (Polyol-Ester) lubricants must be used with R-410A equipment.   
					To prevent moisture absorption and lubricant contamination, do not leave the refrigeration   
					system open to the atmosphere longer than 1 hour.   
					• 
					• 
					• 
					• 
					Weigh-in the refrigerant charge into the high side of the system.   
					Introduce liquid refrigerant charge into the high side of the system.   
					For low side pressure charging of R-410A, use a charging adaptor.   
					Use Friedrich approved R-410A filter dryers only.   
					18   
				R-410A SEALED REFRIGERATION SYSTEM REPAIRS   
					IMPORTANT   
					SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.   
					EQUIPMENT REQUIRED:   
					9. High Pressure Gauge - (0 to 750 lbs.)   
					10. Low Pressure Gauge - (-30 to 200 lbs.)   
					11. Vacuum Gauge - (0 - 1000 microns)   
					1. Voltmeter   
					2. Ammeter   
					3. Ohmmeter   
					12. Facilities for flowing nitrogen through refrigeration tubing   
					during all brazing processes.   
					4. E.P.A. Approved Refrigerant Recovery System   
					5. Vacuum Pump (capable of 200 microns or less   
					vacuum.)   
					EQUIPMENT MUST BE CAPABLE OF:   
					6. Acetylene Welder   
					1. Recovering refrigerant to EPA required levels.   
					7. Electronic Halogen Leak Detector capable of   
					detecting HFC (Hydrofluorocarbon) refrigerants.   
					2. Evacuation from both the high side and low side of the   
					system simultaneously.   
					8. Accurate refrigerant charge measuring device such   
					as:   
					3. Introducing refrigerant charge into high side of the   
					system.   
					a. Balance Scales - 1/2 oz. accuracy   
					b. Charging Board - 1/2 oz. accuracy   
					4. Accurately weighing the refrigerant charge introduced   
					into the system.   
					Proper refrigerant charge is essential to proper unit operation.   
					Operating a unit with an improper refrigerant charge will   
					result in reduced performance (capacity) and/or efficiency.   
					Accordingly, the use of proper charging methods during   
					servicing will insure that the unit is functioning as designed   
					and that its compressor will not be damaged.   
					WARNING   
					RISK OF ELECTRIC SHOCK   
					Unplug and/or disconnect all electrical power   
					to the unit before performing inspections,   
					maintenances or service.   
					Failure to do so could result in electric shock,   
					serious injury or death.   
					Too much refrigerant (overcharge) in the system is just as bad   
					(if not worse) than not enough refrigerant (undercharge). They   
					both can be the source of certain compressor failures if they   
					remain uncorrected for any period of time. Quite often, other   
					problems (such as low air flow across evaporator, etc.) are   
					misdiagnosed as refrigerant charge problems. The refrigerant   
					circuit diagnosis chart will assist you in properly diagnosing   
					these systems.   
					WARNING   
					HIGH PRESSURE HAZARD   
					SealedRefrigerationSystemcontainsrefrigerant   
					and oil under high pressure.   
					An overcharged unit will at times return liquid refrigerant   
					(slugging) back to the suction side of the compressor eventually   
					causing a mechanical failure within the compressor. This   
					mechanical failure can manifest itself as valve failure, bearing   
					failure, and/or other mechanical failure. The specific type of   
					failure will be influenced by the amount of liquid being returned,   
					and the length of time the slugging continues.   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with refrigerants.   
					Failure to follow these procedures could   
					result in serious injury or death.   
					Refrigerant Charging   
					Not enough refrigerant (undercharge) on the other hand, will   
					cause the temperature of the suction gas to increase to the point   
					where it does not provide sufficient cooling for the compressor   
					motor. When this occurs, the motor winding temperature will   
					increase causing the motor to overheat and possibly cycle open   
					the compressor overload protector. Continued overheating of   
					the motor windings and/or cycling of the overload will eventually   
					lead to compressor motor or overload failure.   
					NOTE: Because the XStar system is a sealed system,   
					service process tubes will have to be installed. First install a   
					line tap and remove refrigerant from system. Make necessary   
					sealed system repairs and vacuum system. Crimp process   
					tube line and solder end shut. Do not leave a service valve in   
					the sealed system.   
					19   
				Method Of Charging / Repairs   
					The acceptable method for charging the RAC system is the   
					Weighed in Charge Method. The weighed in charge method is   
					applicable to all units. It is the preferred method to use, as it is   
					the most accurate.   
					The weighed in method should always be used whenever   
					a charge is removed from a unit such as for a leak repair,   
					compressor replacement, or when there is no refrigerant   
					charge left in the unit. To charge by this method, requires the   
					following steps:   
					1. Install a piercing valve to remove refrigerant from the   
					sealedsystem. (Piercing valve must be removed from the   
					system before recharging.)   
					2. Recover Refrigerant in accordance with EPA regulations.   
					WARNING   
					BURN HAZARD   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with a torch.   
					Failure to follow these procedures could   
					result in moderate or serious injury.   
					3. Install a process tube to sealed system.   
					CAUTION   
					FREEZE HAZARD   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with liquid refrigerant.   
					Failure to follow these procedures could   
					result in minor to moderate injury.   
					4. Make necessary repairs to system.   
					5. Evacuate system to 200 microns or less.   
					6. Weigh in refrigerant with the property quantity of R410-A   
					refrigerant.   
					7. Start unit, and verify performance.   
					WARNING   
					BURN HAZARD   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with a torch.   
					Failure to follow these procedures could   
					result in moderate or serious injury.   
					8. Crimp the process tube and solder the end shut.   
					20   
				WARNING   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before service or   
					installation.   
					HIGH PRESSURE HAZARD   
					SealedRefrigerationSystemcontainsrefrigerant   
					and oil under high pressure.   
					Extreme care must be used, if it becomes   
					necessary to work on equipment with power   
					applied.   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with refrigerants.   
					Failure to do so could result in serious injury or   
					death.   
					Failure to follow these procedures could   
					result in serious injury or death.   
					Undercharged Refrigerant Systems   
					An undercharged system will result in poor performance   
					(low pressures, etc.) in both the heating and cooling   
					cycle.   
					A check of the amperage drawn by the compressor   
					motor should show a lower reading. (Check the Unit   
					Specification.) After the unit has run 10 to 15 minutes,   
					check the gauge pressures. Gauges connected to system   
					with an undercharge will have low head pressures and   
					substantially low suction pressures.   
					Whenever you service a unit with an undercharge of   
					refrigerant, always suspect a leak. The leak must be   
					repaired before charging the unit.   
					To check for an undercharged system, turn the unit on,   
					allow the compressor to run long enough to establish   
					working pressures in the system (15 to 20 minutes).   
					During the cooling cycle you can listen carefully at the exit   
					of the metering device into the evaporator; an intermittent   
					hissing and gurgling sound indicates a low refrigerant   
					charge. Intermittent frosting and thawing of the evaporator   
					is another indication of a low charge, however, frosting   
					and thawing can also be caused by insufficient air over   
					the evaporator.   
					Checks for an undercharged system can be made at   
					the compressor. If the compressor seems quieter than   
					normal, it is an indication of a low refrigerant charge.   
					of the evaporator will not be encountered because the   
					refrigerant will boil later if at all. Gauges connected to   
					system will usually have higher head pressure (depending   
					upon amount of over charge). Suction pressure should be   
					slightly higher.   
					Overcharged Refrigerant Systems   
					Compressor amps will be near normal or higher.   
					Noncondensables can also cause these symptoms. To   
					confirm, remove some of the charge, if conditions improve,   
					system may be overcharged. If conditions don’t improve,   
					Noncondensables are indicated.   
					Whenever an overcharged system is indicated, always   
					make sure that the problem is not caused by air flow   
					problems. Improper air flow over the evaporator coil may   
					indicate some of the same symptoms as an over charged   
					system.   
					An overcharge can cause the compressor to fail, since it   
					would be “slugged” with liquid refrigerant.   
					Thechargeforanysystemiscritical. Whenthecompressor   
					is noisy, suspect an overcharge, when you are sure that   
					the air quantity over the evaporator coil is correct. Icing   
					21   
				Restricted Refrigerant System   
					Troubleshooting a restricted refrigerant system can be   
					difficult. The following procedures are the more common   
					problems and solutions to these problems. There are two   
					types of refrigerant restrictions: Partial restrictions and   
					complete restrictions.   
					at the metering device entrance to the evaporator. The   
					evaporator in a partial restriction could be partially frosted   
					or have an ice ball close to the entrance of the metering   
					device. Frost may continue on the suction line back to the   
					compressor.   
					A partial restriction allows some of the refrigerant to   
					circulate through the system.   
					Often a partial restriction of any type can be found by feel,   
					as there is a temperature difference from one side of the   
					restriction to the other.   
					With a complete restriction there is no circulation of   
					refrigerant in the system.   
					With a complete restriction, there will be no sound at the   
					metering device entrance. An amperage check of the   
					compressor with a partial restriction may show normal   
					current when compared to the unit specifi cation. With a   
					complete restriction the current drawn may be considerably   
					less than normal, as the compressor is running in a deep   
					vacuum (no load.) Much of the area of the condenser will   
					be relatively cool since most or all of the liquid refrigerant   
					will be stored there.   
					Restricted refrigerant systems display the same symptoms   
					as a “low-charge condition.”   
					When the unit is shut off, the gauges may equalize very   
					slowly.   
					Gauges connected to a completely restricted system will   
					run in a deep vacuum. When the unit is shut off, the gauges   
					will not equalize at all.   
					The following conditions are based primarily on a system   
					in the cooling mode.   
					A quick check for either condition begins at the evaporator.   
					With a partial restriction, there may be gurgling sounds   
					22   
				COMPRESSOR CHECKS   
					External Overload   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					The compressor is equipped with an external overload   
					which senses both motor amperage and winding tem-   
					perature. High motor temperature or amperage heats the   
					overload causing it to open, breaking the common circuit   
					within the compressor.   
					Turn off electric power before service or   
					installation. Extreme care must be used, if it   
					becomes necessary to work on equipment with   
					power applied.   
					Heat generated within the compressor shell, usually due   
					to recycling of the motor, is slow to dissipate. It may take   
					anywhere from a few minutes to several hours for the   
					overload to reset.   
					Failure to do so could result in serious injury or   
					death.   
					Locked Rotor Voltage (L.R.V.) Test   
					Locked rotor voltage (L.R.V.) is the actual voltage available   
					at the compressor under a stalled condition.   
					Checking the External Overload   
					Single Phase Connections   
					WARNING   
					Disconnect power from unit. Using a voltmeter, attach one   
					lead of the meter to the run “R” terminal on the compressor   
					and the other lead to the common “C” terminal of the com-   
					pressor. Restore power to unit.   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before service or   
					installation. Extreme care must be used, if it   
					becomes necessary to work on equipment   
					with power applied.   
					Failure to do so could result in serious injury or   
					death.   
					Determine L.R.V.   
					Start the compressor with the volt meter attached; then stop   
					the unit. Attempt to restart the compressor within a couple   
					of seconds and immediately read the voltage on the meter.   
					The compressor under these conditions will not start and will   
					usually kick out on overload within a few seconds since the   
					pressures in the system will not have had time to equalize.   
					Voltage should be at or above minimum voltage of 197 VAC,   
					as specified on the rating plate. If less than minimum, check   
					for cause of inadequate power supply; i.e., incorrect wire   
					size, loose electrical connections, etc.   
					WARNING   
					BURN HAZARD   
					Certain unit components operate at   
					temperatures hot enough to cause burns.   
					Proper safety procedures must be followed,   
					and proper protective clothing must be   
					worn.   
					Amperage (L.R.A.) Test   
					Failure to follow this warning could result   
					in moderate to serious injury.   
					The running amperage of the compressor is the most impor-   
					tant of these readings. A running amperage higher than that   
					indicated in the performance data indicates that a problem   
					exists mechanically or electrically.   
					With power off, remove the leads from compressor termi-   
					nals. If the compressor is hot, allow the overload to cool   
					before starting check. Using an ohmmeter, test continu-   
					ity across the terminals of the external overload. If you   
					do not have continuity; this indicates that the overload is   
					open and must be replaced.   
					Single Phase Running and L.R.A. Test   
					NOTE: Consult the specification and performance section   
					for running amperage. The L.R.A. can also be found on the   
					rating plate.   
					Select the proper amperage scale and clamp the meter   
					probe around the wire to the “C” terminal of the compres-   
					sor. Turn on the unit and read the running amperage on   
					the meter. If the compressor does not start, the reading   
					will indicate the locked rotor amperage (L.R.A.).   
					23   
				Single Phase Resistance Test   
					Remove the leads from the compressor terminals and set   
					the ohmmeter on the lowest scale (R x 1).   
					Many compressor failures are caused by the following   
					conditions:   
					1. Improper air flow over the evaporator.   
					Touch the leads of the ohmmeter from terminals common   
					to start (“C” to “S”). Next, touch the leads of the ohmmeter   
					from terminals common to run (“C” to “R”).   
					2. Overcharged refrigerant system causing liquid to be   
					returned to the compressor.   
					Add values “C” to “S” and “C” to “R” together and   
					check resistance from start to run terminals (“S” to “R”).   
					Resistance “S” to “R” should equal the total of “C” to “S”   
					and “C” to “R.”   
					3. Restricted refrigerant system.   
					4. Lack of lubrication.   
					5. Liquid refrigerant returning to compressor causing oil   
					to be washed out of bearings.   
					In a single phase PSC compressor motor, the highest   
					value will be from the start to the run connections (“S” to   
					“R”). The next highest resistance is from the start to the   
					common connections (“S” to “C”). The lowest resistance   
					is from the run to common. (“C” to “R”) Before replacing a   
					compressor, check to be sure it is defective.   
					6.   
					Noncondensables such as air and moisture in   
					the system. Moisture is extremely destructive to a   
					refrigerant system.   
					7. Defective capacitors.   
					GROUND TEST   
					Use an ohmmeter set on its highest scale. Touch one   
					lead to the compressor body (clean point of contact as   
					a good connection is a must) and the other probe in turn   
					to each compressor terminal. If a reading is obtained the   
					compressor is grounded and must be replaced.   
					Check the complete electrical system to the compressor   
					and compressor internal electrical system, check to be   
					certain that compressor is not out on internal overload.   
					Complete evaluation of the system must be made   
					whenever you suspect the compressor is defective. If   
					the compressor has been operating for sometime, a   
					careful examination must be made to determine why the   
					compressor failed.   
					24   
				COMPRESSOR REPLACEMENT   
					Recommendedprocedureforcompressor   
					replacement   
					3. After all refrigerant has been recovered, disconnect   
					suction and discharge lines from the compressor and   
					remove compressor. Be certain to have both suction   
					and discharge process tubes open to atmosphere.   
					WARNING   
					4. Carefully pour a small amount of oil from the suction   
					RISK OF ELECTRIC SHOCK   
					Unplug and/or disconnect all electrical power   
					to the unit before performing inspections,   
					maintenances or service.   
					stub of the defective compressor into a clean   
					container.   
					5. Using an acid test kit (one shot or conventional kit), test   
					the oil for acid content according to the instructions   
					with the kit.   
					Failure to do so could result in electric shock,   
					serious injury or death.   
					6. If any evidence of a burnout is found, no matter how   
					slight, the system will need to be cleaned up following   
					proper procedures.   
					1. Be certain to perform all necessary electrical and   
					refrigeration tests to be sure the compressor is   
					actually defective before replacing.   
					7. Install the replacement compressor.   
					WARNING   
					WARNING   
					HIGH PRESSURE HAZARD   
					SealedRefrigerationSystemcontainsrefrigerant   
					and oil under high pressure.   
					EXPLOSION HAZARD   
					The use of nitrogen requires a pressure   
					regulator. Follow all safety procedures and   
					wear protective safety clothing etc.   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with refrigerants.   
					Failure to follow proper safety procedures   
					result in serious injury or death.   
					Failure to follow these procedures could   
					result in serious injury or death.   
					8. Pressurize with a combination of R410-A and nitrogen   
					and leak test all connections with an electronic or   
					Halide leak detector. Recover refrigerant and repair   
					any leaks found.   
					2. Recover all refrigerant from the system though   
					the process tubes. PROPER HANDLING OF   
					RECOVERED REFRIGERANT ACCORDING TO   
					EPA REGULATIONS IS REQUIRED. Do not use   
					gauge manifold for this purpose if there has been   
					a burnout. You will contaminate your manifold and   
					hoses. Use a Schrader valve adapter and copper   
					tubing for burnout failures.   
					Repeat Step 8 to insure no more leaks are present.   
					9. Evacuate the system with a good vacuum pump capable   
					of a final vacuum of 200 microns or less. The system   
					should be evacuated through both liquid line and suction   
					line gauge ports. While the unit is being evacuated, seal   
					all openings on the defective compressor. Compressor   
					manufacturers will void warranties on units received not   
					properly sealed. Do not distort the manufacturers tube   
					connections.   
					WARNING   
					HIGH TEMPERATURES   
					Extreme care, proper judgment and all safety   
					procedures must be followed when testing,   
					troubleshooting, handling or working around   
					unit while in operation with high temperature   
					components. Wear protective safety aids   
					such as: gloves, clothing etc.   
					CAUTION   
					FREEZE HAZARD   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with liquid refrigerant.   
					Failure to do so could result in serious burn   
					injury.   
					Failure to follow these procedures could   
					result in minor to moderate injury.   
					NOTICE   
					FIRE HAZARD   
					10. Recharge the system with the correct amount of   
					refrigerant. The proper refrigerant charge will be   
					found on the unit rating plate. The use of an accurate   
					measuring device, such as a charging cylinder,   
					The use of a torch requires extreme care and proper   
					judgment. Follow all safety recommended precautions   
					and protect surrounding areas with fire proof materials.   
					Have a fire extinguisher readily available. Failure to follow   
					this notice could result in moderate to serious property   
					damage.   
					electronic scales or similar device is necessary.   
					25   
				SPECIAL PROCEDURE IN THE CASE OF MOTOR   
					COMPRESSOR BURNOUT   
					WARNING   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before service or   
					installation.   
					Failure to do so may result in personal injury,   
					or death.   
					WARNING   
					HIGH PRESSURE HAZARD   
					SealedRefrigerationSystemcontainsrefrigerant   
					and oil under high pressure.   
					Proper safety procedures must be followed,   
					and proper protective clothing must be worn   
					when working with refrigerants.   
					Failure to follow these procedures could   
					result in serious injury or death.   
					WARNING   
					EXPLOSION HAZARD   
					The use of nitrogen requires a pressure   
					regulator. Follow all safety procedures and   
					wear protective safety clothing etc.   
					Failure to follow proper safety procedures   
					result in serious injury or death.   
					1.   
					2.   
					Recover all refrigerant and oil from the system.   
					Remove compressor, capillary tube and filter drier   
					from the system.   
					3.   
					Flush evaporator condenser and all connecting   
					tubing with dry nitrogen or equivalent. Use approved   
					flushing agent to remove all contamination from   
					system. Inspect suction and discharge line for   
					carbon deposits. Remove and clean if necessary.   
					Ensure all acid is neutralized.   
					4. Reassemble the system, including new drier strainer   
					and capillary tube.   
					5. Proceed with step 8-10 on previous page.   
					ROTARY COMPRESSOR SPECIAL TROUBLESHOOTING   
					AND SERVICE   
					Basically, troubleshooting and servicing rotary compres-   
					sors is the same as on the reciprocating compressor with   
					only one main exception:   
					NEVER, under any circumstances, liquid charge a rotary   
					compressor through the LOW side. Doing so would cause   
					permanent damage to the new compressor.   
					26   
				ROUTINE MAINTENANCE   
					AIR FILTER   
					WARNING   
					Clean the unit air intake filter at least every 300 to 350 hours   
					of operation. Clean the filters with a mild detergent in warm   
					water and allow to dry thoroughly before reinstalling.   
					ELECTRIC SHOCK HAZARD   
					Turn off electric power before inspections,   
					maintenances, or service.   
					COILS AND BASE PAN   
					Extreme care must be used, if it becomes   
					necessary to work on equipment with power   
					applied.   
					The indoor coil (evaporator coil), the outdoor coil (condenser   
					coil) and base pan should be inspected periodically   
					(yearly or bi-yearly) and cleaned of all debris (lint, dirt,   
					leaves, paper, etc.). Clean the coils and base pan with a soft   
					brush and compressed air or vacuum. If using a pressure   
					washer, be careful not to bend the aluminium fin pack. Use   
					a sweeping up and down motion in the direction of the verti-   
					cal aluminum fin pack when pressure cleaning coils. Cover   
					all electrical components to protect them from water or spray.   
					Allow the unit to dry thoroughly before reinstalling it in the   
					sleeve.   
					Failure to do so could result in serious injury   
					or death.   
					WARNING   
					EXCESSIVE WEIGHT HAZARD   
					Use two people to lift or carry the unit, and wear   
					proper protective clothing.   
					BLOWER WHEEL / HOUSING / CONDENSER FAN /   
					SHROUD   
					Failure to do so may result in personal injury.   
					Inspect the indoor blower housing, evaporator blade, con-   
					denser fan blade and condenser shroud periodically (yearly   
					or bi-yearly) and clean of all debris (lint, dirt, mold, fungus,   
					etc.). Clean the blower housing area and blower wheel with   
					an antibacterial / antifungal cleaner. Use a biodegradable   
					cleaning agent and degreaser on condenser fan and con-   
					denser shroud. Use warm or cold water when rinsing these   
					items. Allow all items to dry thoroughly before reinstalling   
					them.   
					WARNING   
					CUT/SEVER HAZARD   
					Be careful with the sharp edges and corners.   
					Wear protective clothing and gloves, etc.   
					Failure to do so could result in serious injury.   
					ELECTRONIC / ELECTRICAL / MECHANICAL   
					NOTICE   
					Units are to be inspected and serviced by qualified service   
					personnel only. Use proper protection on surrounding   
					property. Failure to follow this notice could result in   
					moderate or serious property damage.   
					Periodically (at least yearly or bi-yearly): inspect all control   
					components: electronic, electrical and mechanical, as well as   
					the power supply. Use proper testing instruments (voltmeter,   
					ohmmeter, ammeter, wattmeter, etc.) to perform electrical   
					tests. Use an air conditioning or refrigeration thermometer   
					to check room, outdoor and coil operating temperatures.   
					Use an electronic tester to measure wet bulb temperatures   
					indoors and outdoors.   
					NOTICE   
					Do not use a caustic coil cleaning agent on coils or base   
					pan. Use a biodegradable cleaning agent and degreaser,   
					to prevent damage to the coil and/or base pan.   
					27   
				ROUTINE MAINTENANCE (Continued)   
					NOTICE   
					Do not drill holes in the bottom of the drain pan or the   
					underside of the unit. Not following this notice could   
					result in damage to the unit or condensate water leaking   
					inappropriately which could cause water damage to   
					surrounding property.   
					SLEEVE / DRAIN   
					Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and   
					debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and   
					ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as   
					needed.   
					FRONT COVER   
					Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry   
					thoroughly before reinstalling it in the chassis.   
					CLEARANCES   
					Inspect the surrounding area (inside and outside) to ensure that the unit’s clearances have not been compromised or   
					altered.   
					Compressor   
					Condenser Coil   
					Discharge Air   
					Front Cover   
					System Controls   
					Evaporator Coil   
					Outdoor Grille   
					Sleeve   
					Return Air Grille/Filter   
					Blower Wheel   
					Condenser Fan Blade   
					Blower Motor   
					Basepan   
					28   
				ROOM AIR CONDITIONER UNIT   
					PERFORMANCE TEST DATA SHEET   
					DATE: _______________ MODEL:_______________ SERIAL:________________   
					YES   
					____   
					____   
					____   
					NO   
					IS THERE A FRIEDRICH SLEEVE INSTALLED?   
					IS THERE A CHASSIS SEAL GASKET INSTALLED?   
					IS MAINTENANCE BEING PERFORMED?   
					____   
					____   
					____   
					If NO is checked use back of sheet for explanation   
					ELECTRICAL:   
					LINE VOLTAGE (STATIC)   
					START UP VOLTAGE   
					--------- VOLTS   
					--------- VOLTS   
					AMPERAGE DRAW   
					AMPERAGE DRAW   
					--------- AMPS (COOL)   
					--------- AMPS (HEAT)   
					COMPRESSOR   
					LOCKED ROTOR AMPS   
					RUNNING AMPS   
					LOCKED ROTOR VOLTAGE   
					INDOOR TEMPERATURES:   
					INDOOR AMBIENT TEMPERATURE   
					RELATIVE HUMIDITY (RH) INDOOR   
					--------- AMPS   
					--------- AMPS   
					--------- VOLTS   
					-------- F   
					-------- %   
					COOL   
					HEAT   
					DISCHARGE AIR TEMPERATURE (INDOOR)   
					RETURN AIR TEMPERATURE (INDOOR)   
					DIFFERENTIAL   
					---------- F --------- F   
					---------- F --------- F   
					---------- F --------- F   
					OUTDOOR TEMPERATURE:   
					OUTDOOR AMBIENT TEMPERATURE   
					RH OUTDOOR   
					--------- F   
					--------- %   
					CONDENSER:   
					DISCHARGE AIR TEMPERATURE (OUTDOOR)   
					INTAKE AIR TEMPERATURE (OUTDOOR   
					DIFFERENTIAL   
					--------- F ---------- F   
					--------- F ---------- F   
					--------- F ---------- F   
					APPLICATION USE ------------------------- ROOM (RESIDENTIAL OR COMMERCIAL)   
					This is a general guide.   
					Please consult manual J or M for exact load calculations.   
					1. If heavily shaded, reduce capacity 10%.   
					2. If very sunny, add 10%.   
					3. Add 500 BTU/H per person over 2 people.   
					4. Add 4,000 BTU/H if area is a kitchen.   
					Due to variations in room design, climate zone and occupancy, larger areas   
					may require the use of multiple units to provide the optimal cooling solution.   
					29   
					29   
				GENERAL TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Possible Solution   
					Turn the unit to the on position and raise or   
					lower temperature setting (as appropriate) to   
					call for operation.   
					The unit is turned to the off position,   
					Plug into a properly grounded 3 prong   
					receptacle. See “Electrical Rating Tables” on   
					pg. 6 for the proper receptacle type for your   
					unit.   
					The LCDI power cord is unplugged.   
					Press and release RESET (listen for click;   
					Reset button latches and remains in) to resume   
					operation.   
					Unit does not operate.   
					The LCDI power cord has tripped   
					(Reset button has popped out).   
					Reset the circuit breaker, or replace the fuse as   
					applicable. If the problem continues, contact a   
					licensed electrician.   
					The circuit breaker has tripped or   
					the supply circuit fuse has blown.   
					There has been a local power   
					failure.   
					The unit will resume normal operation once   
					power has been restored.   
					Other appliances are being used on   
					the same circuit.   
					The unit requires a dedicated outlet circuit, not   
					shared with other appliances.   
					Do NOT use an extension cord with this or any   
					other air conditioner.   
					An extension cord is being used.   
					Unit Trips Circuit Breaker or   
					Blows Fuses.   
					Replace with a circuit breaker or time-delay   
					fuse of the proper rating. See “Electrical   
					Rating Tables” on pg. 6 for the proper circuit   
					breaker/fuse rating for your unit. If the problem   
					continues, contact a licensed electrician.   
					The circuit breaker or time-delay   
					fuse is not of the proper rating.   
					The LCDI power cord can trip   
					(Reset button pops out) due to   
					disturbances on your power supply   
					line.   
					Press and release RESET (listen for click;   
					Reset button latches and remains in) to resume   
					normal operation.   
					LCDI Power Cord Trips (Reset   
					Button Pops Out).   
					Electrical overload, overheating, or   
					cord pinching can trip (Reset button   
					pops out) the LCDI power cord.   
					Once the problem has been determined and   
					corrected, press and release RESET (listen for   
					click; Reset button latches and remains in) to   
					resume normal operation.   
					NOTE: A damaged power supply cord must be replaced with a new power supply cord   
					obtained from the product manufacturer and must not be repaired.   
					Ensure that the return and/or discharge air   
					The return/discharge air grille is   
					paths are not blocked by curtains, blinds,   
					blocked.   
					furniture, etc.   
					Windows or doors to the outside are   
					Ensure that all windows and doors are closed.   
					open.   
					The temperature is not set at a cool   
					enough/warm enough setting.   
					Adjust the Temperature control to a cooler or   
					warmer setting as necessary.   
					Unit Does Not Cool/Heat   
					On And Off Too Frequently.   
					remove obstruction.   
					The indoor coil or outdoor coil is   
					dirty or obstructed.   
					Clean the coils, (See Routine Maintenance), or   
					remove obstruction.   
					Be sure to use exhaust vent fans while cooking   
					or bathing and, if possible, try not to use heat   
					producing appliances during the hottest part of   
					the day.   
					There is excessive heat or moisture   
					(cooking, showers, etc.) in the room.   
					The temperature of the room you   
					are trying to cool is extremely hot.   
					Allow additional time for the air conditioner to   
					cool off a very hot room.   
					30   
				GENERAL TROUBLESHOOTING TIPS (CONTINUED)   
					Problem   
					Possible Cause   
					Possible Solution   
					Do not try to operate your air conditioner in the   
					cooling mode when the outside temperature   
					is below 60° F (16° C). The unit will not cool   
					properly, and the unit may be damaged.   
					The outside temperature is below   
					60° F (16° C).   
					Since the fan does not circulate the room   
					air continuously at this setting, the room air   
					does not mix as well and hot (or cold) spots   
					may result. Using the continuous fan setting   
					is recommended to obtain optimum comfort   
					levels.   
					The digital control is set to fan   
					cycling mode.   
					Unit Does Not Cool/Heat   
					On And Off Too Frequently   
					(continued).   
					Check the cooling capacity of your unit to   
					ensure it is properly sized for the room in which   
					it is installed. Room air conditioners are not   
					designed to cool multiple rooms.   
					cooling capacity to match the heat   
					gain of the room.   
					Check the heating capacity of your unit. Air   
					conditioners are sized to meet the cooling load,   
					and heater size is then selected to meet the   
					heating load. In extreme northern climates,   
					room air conditioners may not be able to be   
					used as a primary source of heat.   
					heating capacity to match the heat   
					loss of the room.   
					If there are heat producing appliances in use   
					in the room, or if the room is heavily occupied,   
					the unit will need to run longer to remove the   
					additional heat.   
					This may be due to an excessive   
					heat load in the room.   
					Be sure to use exhaust vent fans while cooking   
					or bathing and, if possible, try not to use heat   
					producing appliances during the hottest part of   
					the day.   
					It may also be due to an improperly   
					sized unit.   
					your new air conditioner may result in the   
					unit running longer than you feel it should.   
					This may be more apparent, if it replaced an   
					This may be normal for higher   
					Unit Runs Too Much.   
					compared to older models.   
					You may notice that the discharge   
					air temperature of your new air   
					conditioner may not seem as cold   
					as you may be accustomed to from   
					older units. This does not, however,   
					indicate a reduction in the cooling   
					capacity of the unit.   
					capacity rating (Btu/h) listed on the unit’s rating   
					31   
				COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Low voltage   
					Action   
					Check voltage at compressor. 115V & 230V   
					units will operate at 10% voltage variance   
					T-stat not set cold enough or   
					inoperative or electronic control   
					board is bad   
					Set t-stat to coldest position. Test t-stat &   
					replace if inoperative   
					Compressor hums but cuts off on   
					overload   
					Hard start compressor. Direct test compressor.   
					If compressor starts, add starting components   
					Compressor   
					does not run   
					Open or shorted compressor   
					windings   
					Check for continuity & resistance   
					Open overload   
					Test overload protector & replace if inoperative   
					Test capacitor & replace if inoperative   
					Test for continuity in all positions. Replace if   
					inoperative switch or electronic board.   
					Refer to appropriate wiring diagrams to check   
					wiring   
					Open capacitor   
					Inoperative system switch,   
					thermistor or electronic board   
					Broken, loose or incorrect wiring   
					Problem   
					Possible Cause   
					Inoperative system switch   
					Broken, loose or incorrect wiring   
					Open capacitor   
					Action   
					Test switch & replace if inoperative   
					Refer to applicable wiring diagram   
					Test capacitor & replace if inoperative   
					Test switch & replace if inoperative   
					Test fan motor & replace if inoperative (be sure   
					internal overload has had time to reset)   
					Fan motor   
					does not run   
					Fan speed switch open   
					Inoperative fan motor   
					Problem   
					Possible Cause   
					Action   
					Undersized unit   
					Refer to industry standard sizing chart   
					Thermistor or electronic board is bad,   
					T-stat open or inoperative   
					Set to coldest position. Test t-stat or electronic   
					control board & replace if necessary.   
					Dirty filter   
					Clean as recommended in Owner’s Manual   
					Use pressure wash or biodegradable cleaning   
					agent to clean   
					Dirty or restricted condenser or   
					evaporator coil   
					Does not cool or   
					only cools slightly   
					Poor air circulation   
					Adjust discharge louvers. Use high fan speed   
					Close doors. Instruct customer on use of this   
					feature   
					Fresh air or exhaust air door open   
					on applicable models   
					Low capacity - undercharge   
					Check for leak & make repair   
					Check amperage draw against nameplate. If   
					not conclusive, make pressure test   
					Compressor not pumping properly   
					32   
				COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Action   
					Replace fuse, reset breaker. If repeats, check   
					fuse or breaker size. Check for shorts in unit   
					wiring & components   
					Fuse blown or circuit tripped   
					Power cord not plugged in   
					Plug it in   
					System switch in “OFF” position   
					Set switch correctly   
					Unit does not run   
					Inoperative system switch or open   
					electronic control board   
					Test for continuity   
					Loose or disconnected wiring at   
					Check wiring & connections. Reconnect per   
					wiring diagram   
					switch, control board or other com-   
					ponents   
					Problem   
					Possible Cause   
					Action   
					Dirty filter   
					Clean as recommended in Owner’s Manual   
					Check for dirty or obstructed coil. Use   
					pressure wash or biodegradable cleaning   
					agent to clean   
					Restricted airflow   
					Inoperative t-stat or thermistors   
					Short of refrigerant   
					Test for continuity   
					Evaporator coil   
					freezes up   
					De-ice coil & check for leak   
					Inoperative fan motor   
					Test fan motor & replace if inoperative   
					De-ice coil. Check temp. differential (delta T)   
					across coil. Touch test coil return bends for   
					same temp. Test for low running current   
					Partially restricted capillary tube   
					Problem   
					Possible Cause   
					Action   
					Unit undersized. Test cooling performance &   
					replace with larger unit if needed   
					Check for partially iced coil & check   
					temperature split across coil   
					Excessive heat load   
					Restriction in line   
					Refrigerant leak   
					Check for oil at silver soldered connections.   
					Check for partially iced coil. Check split across   
					coil. Check for low running amperage   
					Check operation of t-stat. Replace if contacts   
					remain closed.   
					Compressor runs   
					continually & does   
					not cycle off   
					T-stat contacts stuck   
					T-stat incorrectly wired   
					Thermistor shorted   
					Refer to appropriate wiring diagram   
					Replace thermistor or electronic control board   
					Problem   
					Possible Cause   
					Action   
					Disconnect power to unit. Remove cover   
					of t-stat & check if contacts are stuck. If so,   
					replace t-stat   
					T-stat contacts stuck   
					Turn to higher temp. setting to see if unit   
					cycles off   
					T-stat set at coldest point   
					Incorrect wiring   
					T-stat does not   
					turn unit off   
					Refer to appropriate wiring diagrams   
					Refer to industry standard sizing chart   
					Replace thermistor or electronic control board   
					Unit undersized for area to be   
					cooled   
					Defective thermistor   
					33   
				COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Overload inoperative. Opens too   
					soon   
					Action   
					Check operation of unit. Replace overload if   
					system operation is satisfactory   
					Allow a minimum of 2 minutes to allow   
					pressures to equalize before attempting to   
					restart. Instruct customer of waiting period   
					Check voltage with unit operating. Check for   
					other appliances on circuit. Air conditioner   
					should be in separate circuit for proper voltage   
					& fused separately   
					Compressor restarted before   
					system pressures equalized   
					Compressor runs   
					for short periods   
					only. Cycles on   
					overload   
					Low or Àuctuating voltage   
					Incorrect wiring   
					Refer to appropriate wiring diagram   
					Check by substituting a known good capacitor   
					of correct rating or test cap   
					Shorted or incorrect capacitor   
					Restricted or low air Àow through   
					Check for proper fan speed or blocked   
					coils   
					condenser coil or evaporator coil   
					Check for kinked discharge line or restricted   
					condenser. Check amperage   
					Compressor running abnormally   
					hot   
					Problem   
					Possible Cause   
					Action   
					Place jumper across t-stat terminals to check if   
					unit operates. If unit operates, replace t-stat.   
					Check as above   
					Loss of charge in t-stat bulb   
					(EQ08M11)   
					T-stat does not   
					turn unit on   
					Loose or broken parts in t-stat   
					Incorrect wiring   
					Refer to appropriate wiring diagram   
					Replace thermistor or electronic control board   
					Defective thermistor   
					Problem   
					Possible Cause   
					Poorly installed   
					Action   
					Refer to Installation Manual for proper   
					installation   
					Fan blade striking chassis   
					Reposition - adjust motor mount   
					Check that compressor grommets have not   
					deteriorated. Check that compressor mounting   
					parts are not missing   
					Noisy operation   
					Compressor vibrating   
					Improperly mounted or loose   
					cabinet parts refrigerant tubes   
					Check assembly & parts for looseness,   
					rubbing & rattling. Correct as needed   
					Problem   
					Possible Cause   
					Action   
					Evaporator drain pan overÀowing   
					Clean obstructed drain trough   
					Evaporator drain pan broken or cracked.   
					Reseal or replace. No chassis gasket installed.   
					Install chassis gasket   
					Condensation forming underneath   
					base pan   
					Poor installation resulting in rain   
					entering the room   
					Check installation instructions. Reseal as   
					required   
					Water leaks into   
					the room   
					Dirty evaporator coil. Use pressure wash   
					or biodegradable cleaning agent to clean.   
					Environmental phenomena: point supply   
					louvers upward   
					Condensation on discharge grille   
					louvers   
					Chassis gasket not installed   
					Downward slope of unit is too   
					steep inward   
					Install gasket, per Installation manual   
					Refer to installation manual for proper   
					installation   
					34   
				COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Sublimation:   
					Action   
					Ensure that foam gaskets are installed in   
					between window panes & in between the   
					unit & the sleeve. Also, ensure that fresh   
					air/exhaust vents (on applicable models) are in   
					the closed position & are in tact   
					When unconditioned saturated,   
					outside air mixes with conditioned   
					air, condensation forms on the   
					cooler surfaces   
					Water “spitting”   
					into room   
					Follow installation instructions to ensure that   
					downward pitch of installed unit is no less than   
					1/4” & no more than 3/8”   
					Downward pitch of installation is   
					too steep towards back of unit   
					Clean & advise customer of periodic cleaning   
					& maintenance needs of entire unit   
					Restricted coil or dirty filter   
					Problem   
					Possible Cause   
					Insufficient air circulation thru area   
					to be air conditioned   
					Action   
					Adjust louvers for best possible air circulation   
					Operate in “MoneySaver” position   
					Advise customer   
					Excessive   
					moisture   
					Oversized unit   
					Inadequate vapor barrier in building   
					structure, particularly floors   
					Problem   
					Possible Cause   
					Defective thermistor   
					Action   
					Replace thermistor or electronic control board   
					Replace t-stat   
					T-stat differential too narrow   
					Plenum gasket not sealing,   
					allowing discharge air to short   
					cycle t-stat   
					T-stat or   
					thermistor   
					short cycles   
					Check gasket. Reposition or replace as   
					needed   
					Clean & advise customer of periodic cleaning   
					& maintenance needs of entire unit   
					Restricted coil or dirty filter   
					Problem   
					Possible Cause   
					Heat anticipator (resistor) wire   
					disconnected at t-stat or system   
					switch   
					Action   
					Refer to appropriate wiring diagram   
					Disconnect plus from outlet. Remove resistor   
					from bracket. Insert plug & depress “COOL”   
					& “FAN AUTOMATIC” buttons. Place t-stat to   
					warmest setting. Feel resistor for temperature.   
					If no heat, replace resistor   
					Prolonged off   
					cycles (automatic   
					operation)   
					Heat anticipator (resistor) shorted or   
					open   
					Partial loss of charge in t-stat bulb   
					causing a wide differential   
					Replace t-stat   
					Defective thermistor   
					Replace thermistor or electronic control board   
					Problem   
					Possible Cause   
					Evaporator drain pan cracked or   
					obstructed   
					Action   
					Repair, clean or replace as required   
					Detach shroud from pan & coil. Clean &   
					remove old sealer. Reseal, reinstall & check   
					Use pressure wash or biodegradable cleaning   
					agent to clean   
					Water in compressor area   
					Obstructed condenser coil   
					Outside water   
					leaks   
					Fan blade/slinger ring improperly   
					positioned   
					Adjust fan blade to 1/2” of condenser coil fin   
					pack   
					35   
				HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS   
					Problem   
					Possible Cause   
					Action   
					Disconnect power to unit. Remove resistor from   
					t-stat bulb block. Plug in unit & allow to operate.   
					Feel resistor for heat. If not heat, replace resistor   
					Heat anticipator (resistor) shorted (on applicable   
					models)   
					Room temperature   
					uneven   
					(Heating cycle)   
					Wide differential - partial loss of t-stat bulb charge Replace t-stat   
					Refer to appropriate wiring diagram. Resistor is   
					Incorrect wiring   
					energized during "ON" cycle of compressor or   
					fan.   
					Problem   
					Possible Cause   
					Action   
					Close doors or windows.   
					Opened doors or windows   
					Dirty filter   
					Clean as recommended in Owner's Manual   
					Check heat rise across coil. If unit operates   
					efficiently, check if insulation can be added   
					to attic or walls. If insulation is adequate,   
					recommend additional unit or larger one   
					Unit undersized   
					Does not heat   
					adequately   
					* 
					Check for adequate fan air across heater. Check   
					control for open at 110°F & close at 100°F   
					Heater hi-limit control cycling on & off   
					Shorted or opened heater   
					Incorrect wiring   
					Ohmmeter/continuity check   
					Check applicable wiring diagram   
					* NOTE: Heater size on the EQ08M11 is: 1.15 KW.   
					36   
				ELECTRONIC CONTROL   
					COOL ONLY MODELS:   
					XQ05M10   
					XQ06M10   
					XQ08M10   
					XQ10M10   
					* * * *   
					Last character may vary.   
					* 
					37   
				ELECTROMECHANICAL CONTROL   
					COOL WITH ELECTRIC HEAT MODEL:   
					EQ08M11   
					* 
					Last character may vary.   
					* 
					38   
				INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE   
					FORM FOR ROOM AIR CONDITIONERS   
					(AHAM PUB. NO. RAC-1)   
					A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations   
					which do not require specific conditions of inside temperature and humidity.   
					B. The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas   
					in the continental United States having other outside design temperatures by applying a correction factor for the   
					particular locality as determined from the map.   
					C. The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as   
					living rooms, offices, etc.)   
					D. The numbers of the following paragraphs refer to the corresponding numbered item on the form:   
					1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the   
					area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian   
					blinds, use the factor for “Inside Shades.” For windows shaded by outside awnings or by both outside aw-   
					nings and inside shades (or venetian blinds), use the factor for “Outside Awnings.” “Single Glass” includes   
					all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows,   
					and glass block. Only one number should be entered in the right hand column for Item 1, and this number   
					should represent only the exposure with the largest load.   
					2. Multiply the total square feet of all windows in the room by the applicable factor.   
					3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should   
					be considered as being part of the wall. Outside walls facing due north should be calculated separately from   
					outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be   
					considered “North Exposure.” Do not consider trees and shrubbery as providing permanent shading. An   
					uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.” An   
					insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.”   
					3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any uncondi-   
					tioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.   
					4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly   
					describing the particular application (use one line only.)   
					5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the   
					ground or over a basement.   
					6. Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use   
					a minimum of 2 people.   
					7. Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that   
					will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.   
					8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned   
					space by the applicable factor.   
					NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated   
					value. In such cases, both adjoining rooms should be considered as a single large room, and the room air   
					conditioner unit or units should be selected according to a calculation made on this new basis.   
					9. Total the loads estimated for the foregoing 8 items.   
					10. Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular   
					locality. The result is the total estimated design cooling load in BTU per hour.   
					E. For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance   
					with the NEMAStandards Publication for RoomAir Conditioners, CN 1-1960) as close as possible to the estimated   
					load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less   
					satisfactory than one which is slightly undersized and which would operate more nearly continuously.   
					F. Intermittent loads such as kitchen and laundry equipment are not included in this form.   
					39   
				COOLING LOAD ESTIMATE FORM   
					FACTORS   
					BTU/Hr.   
					(Quantity x Factor)   
					HEAT GAIN FROM   
					QUANTITY   
					DAY   
					No   
					Shades*   
					60   
					Outside (Area   
					Awnings* X Factor)   
					Inside   
					Shades*   
					1.   
					WINDOWS: Heat gain from the sun.   
					Northeast   
					East   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					20 ____   
					25 ____   
					20 ____   
					20 ____   
					30 ____   
					45 ____   
					35 ____   
					0 ____   
					Use   
					only   
					the   
					____   
					____   
					____   
					25   
					40   
					30   
					35   
					45   
					65   
					50   
					0 
					* These factors are for single glass   
					only. For glass block, multiply the   
					above factors by 0.5; for double   
					glass or storm windows, multiply the   
					above factors by 0.8.   
					80   
					75   
					Southeast   
					South   
					75   
					largest ____   
					load. ____   
					Southwest   
					West   
					110   
					150   
					120   
					0 
					Use   
					only   
					one.   
					____   
					____   
					____   
					Northwest   
					North   
					2.   
					3.   
					WINDOWS: Heat by conduction   
					(Total of all windows.)   
					Single glass   
					_____   
					_____   
					14   
					7 
					____sq. ft.   
					____sq. ft.   
					Double glass or glass block   
					WALLS: (Based on linear feet of wall)   
					a. Outside walls   
					North Exposure   
					Light Construction   
					Heavy Construction   
					_____   
					_____   
					30   
					60   
					____ ft.   
					____ ft.   
					20   
					30   
					Other than North exposure   
					b. Inside Walls (between conditioned and   
					unconditioned spaces only.)   
					_____   
					30   
					____sq. ft.   
					4.   
					ROOF OR CEILING: (Use one only)   
					a. Roof, uninsulated   
					_____   
					_____   
					_____   
					_____   
					_____   
					19   
					8 
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					____sq. ft.   
					b. Roof, 1 inch or more insulation   
					c. Ceiling, occupied space above   
					d. Ceiling, insulated, with attic space above   
					e. Ceiling, uninsulated, with attic space above   
					3 
					5 
					12   
					_____   
					5.   
					Floor: (Disregard if floor is directly on ground or   
					over a basement.   
					3 
					____sq. ft.   
					_____   
					_____   
					6.   
					7.   
					8.   
					NUMBER OF PEOPLE   
					600   
					3 
					____   
					LIGHTS AND ELECTRICAL EQUIPMENT IN USE   
					____watts   
					DOORS AND ARCHES CONTINUOUSLY   
					OPENED TO UNCONDITIONED SPACE: (TOTAL   
					LINEAR FEET OF WIDTH.)   
					_____   
					_____   
					300   
					____ft.   
					*****   
					9.   
					SUBTOTAL   
					*****   
					10. TOTAL COOLING LOAD (BTU per hour to be used   
					for selection of room air conditioner(s).)   
					____ Total in Item 9 X ____ (Factor from Map) =   
					____   
					40   
				HEAT LOAD FORM   
					The heat load form on the following page may be used by   
					Following is an example using the heat load form:   
					servicingpersonneltodeterminetheheatlossofaconditioned   
					space and the ambient winter design temperatures in which   
					the unit will heat the calculated space.   
					A space to be conditioned is part of a house geographically   
					located in an area where the lowest outdoor ambient winter   
					temperature is 40°F. The calculated heat loss is 184 BTU/   
					Hr./°F.   
					The upper half of the form is for computing the heat loss of   
					the space to be conditioned. It is necessary only to insert   
					the proper measurements on the lines provided and multiply   
					by the given factors, then add this result for the total heat   
					loss in BTU/Hr./°F.   
					Subtract 40°F (lowest outdoor ambient temperature for the   
					geographical location) from 70°F(insidedesigntemperature   
					of the unit) for a difference of 30°F. Multiply 184 by 30 for a   
					5500 BTU/Hr. total heat loss for the calculated space.   
					The BTU/Hr. per °F temperature difference is the 70°F   
					insidewinterdesignedtemperatureminusthelowestoutdoor   
					ambient winter temperature of the area where the unit is   
					installed. Thistemperaturedifferenceisusedasthemultiplier   
					when calculating the heat loss.   
					On the graph, plot the base point (70°) and a point on the   
					40°F line where it intersects with the 5500 BTU/Hr. line on   
					the left scale. Draw a straight line from the base point 70   
					through the point plotted at 40°F. This is the total heat loss   
					line.   
					The graph shows the following:   
					Knowing that we have a 5500 BTU/Hr. heat loss, and   
					we expect that our heat pump will maintain a 70°F inside   
					temperature at 40°F outdoor ambient, we plot the selected   
					unit capacity BTU/Hr. of the unit between 35° and 60° on the   
					graph and draw a straight line between these points. Where   
					the total heat loss line and the unit capacity line intersect,   
					read down to the outdoor ambient temperature scale and   
					find that this unit will deliver the required BTU/Hr. capacity   
					to approximately 30°F.   
					Left Hand Scale   
					Unit capacity BTU/Hr. or heat loss   
					BTU/Hr.   
					Bottom Scale   
					Outdoor ambient temperature, base   
					point.   
					Heat Pump Model   
					Balance Point   
					BTU/Hr. capacity heat pump will   
					deliver at outdoor temperatures.   
					Maximum BTU/Hr. heat pump   
					will deliver at indicated ambient   
					temperature.   
					41   
				HEATING LOAD FORM   
					FRIEDRICH ROOM UNIT HEAT PUMPS   
					BTU/HR PER   
					WALLS: (Linear Feet)   
					2” Insulation   
					Average   
					°F TEMP. DIFFERENCE   
					Lin. Ft. x 1.6   
					Lin. Ft. x 2.6   
					WINDOWS & DOORS (Area, sq. ft.)   
					Single Glass:   
					Double Glass:   
					Sq. Ft. x 1.13   
					Sq. Ft. x 0.61   
					INFILTRATION - WINDOWS & DOORS: AVG.   
					Lin. Ft. x 1.0   
					Lin. Ft. x 2.0   
					Loose   
					CEILING: (Area, Sq. Ft.)   
					Insulated (6”)   
					Insulated (2”)   
					Sq. Ft. x 0.07   
					Sq. Ft. x 0.10   
					Sq. Ft. x 0.10   
					Sq. Ft. x 0.20   
					Sq. Ft. x 0.33   
					Built-up Roof (2” insulated   
					Built-up Roof (1/2” insulated)   
					No Insulation   
					FLOOR: (Area, Sq. Ft.)   
					Above Vented Crawl space   
					Insulated (1:)   
					Sq. Ft. x 0.20   
					Sq. Ft. x 0.50   
					Lin. Ft. x 1.70   
					Uninsulated   
					* Slab on Ground   
					1” Perimeter insulation   
					* Based on Linear Feet of outside wall   
					Lin. Ft. x 1.00   
					TOTAL HEAT LOSS PER °F BTU/HR/°F   
					Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from   
					the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the   
					unit capacity line represents the winter design heating load.   
					42   
				Friedrich Air Conditioning Company   
					10001 Reunion Place, Suite 500   
					San Antonio, TX 78216   
					1-800-541-6645   
					
					ROOM AIR CONDITIONERS   
					LIMITED WARRANTY   
					FIRST YEAR   
					ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original   
					purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor   
					cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the   
					responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.   
					SECOND THROUGH FIFTH YEAR   
					SEALED REFRIGERANT SYSTEM:   
					because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts   
					necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight   
					charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the   
					Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy   
					within sixty months from the date of the original purchase.   
					APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia,   
					and Canada. This warranty is not applicable to:   
					1.   
					A 
					2. Products on which the model and serial numbers have been removed.   
					3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or   
					installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes,   
					material shortages beyond the control of FRIEDRICH, or acts of God.   
					OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your   
					area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service   
					Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540.   
					LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY   
					IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION   
					OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL   
					OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.   
					Performance of Friedrich’s Warranty obligation is limited to one of the following methods:   
					1. Repair of the unit   
					2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.   
					3. Providing a replacement unit of equal value   
					NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not allow the limitation or exclusion of consequential or   
					incidental damages, so the foregoing exclusions and limitations may not apply to you.   
					OTHER:   
					PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services.   
					All service calls for explaining the operation of this product will be the sole responsibility of the consumer.   
					All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.   
					(10-08)   
					43   
				TECHNICAL SUPPORT   
					CONTACT INFORMATION   
					FRIEDRICH AIR CONDITIONING CO.   
					10001 Reunion Place, Ste. 500, San Antonio, TX 78216   
					(210) 546-0500 877-599-5665 x 261   
					Email: [email protected]   
					
					FAX (210) 546-0731   
					Printed in the U.S.A.   
					44   
				FRIEDRICH AIR CONDITIONING CO.   
					10001 Reunion Place, Ste. 500, San Antonio, TX 78216   
					P 210-546-0500 | F 210-546-0731   
					
					Printed in the U.S.A.   
					X-Star-ServMan (1-11)   
				 |