Energy Tech Laboratories DSH User Manual

Model DSH  
Ceiling Mounted Ducted R-410A  
Air Conditioning Units  
Form 145.32-IOM1 (908)  
New Release  
CEILING MOUNTED DUCTED R-410A  
AIR CONDITIONING UNITS  
INSTALLATION INSTRUCTIONS  
FORM 145.32-IOM1 (908)  
CHANGEABILITY OF THIS DOCUMENT  
In complying with Johnson Controls policy for continu-  
ous product improvement, the information contained  
in this document is subject to change without notice.  
While Johnson Controls makes no commitment to up-  
date or provide current information automatically to the  
manual owner, that information, if applicable, can be  
obtained by contacting the nearest Johnson Controls  
service office.  
It is the responsibility of operating/service personnel as  
to the applicability of these documents to the equipment  
in question. If there is any question in the mind of oper-  
ating/service personnel as to the applicability of these  
documents, then, prior to working on the equipment, they  
should verify with the owner whether the equipment has  
been modified and if current literature is available.  
TABLE OF CONTENTS  
SAFETY SYMBOLS.......................................................................................................................2  
CHANGEABILITY OF THIS DOCUMENT.....................................................................................3  
TABLE OF CONTENTS.................................................................................................................3  
GENERAL INFORMATION ...........................................................................................................4  
PRE-INSTALLATION INSPECTION OF EQUIPMENT .................................................................6  
RIGGING.................................................................................................................................................6  
INSTALLATION .............................................................................................................................6  
UNIT MOUNTING ...................................................................................................................................7  
SEPARATION OF UNITS .......................................................................................................................8  
INTERCONNECTING REFRIGERANT TUBING - SPLIT INSTALLATION ...........................................8  
DUCTWORK ...............................................................................................................................11  
LOUVER SIZING GUIDELINES ...........................................................................................................11  
ELECTRICAL WIRING ................................................................................................................12  
PACKAGED UNIT .......................................................................................................................12  
SPLIT SYSTEM ...........................................................................................................................12  
MOTOR AND PULLEY DATA...............................................................................................................14  
BLOWER SPEED ADJUSTMENT .......................................................................................................14  
START-UP AND OPERATION ....................................................................................................15  
REFRIGERANT CHARGES..................................................................................................................15  
PRESSURE SWITCH SETTINGS.........................................................................................................15  
MAINTENANCE / SERVICE .......................................................................................................17  
FILTERS................................................................................................................................................17  
EVAPORATOR AND CONDENSER COILS.........................................................................................17  
BLOWERS ............................................................................................................................................17  
DRIVE BELTS.......................................................................................................................................17  
REFRIGERANT CIRCUIT(S) ................................................................................................................17  
COMFORT ALERT™ DIAGNOSTICS ........................................................................................18  
LED DESCRIPTION..............................................................................................................................18  
INTERPRETING THE DIAGNOSTIC LEDS .........................................................................................18  
INSTALLATION VERIFICATION .................................................................................................21  
3
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
GENERAL INFORMATION  
Our units are designed to meet the ever-changing  
(unique) installation requirements of today’s market. The  
horizontal configuration is unitized for single package  
or split installation. Low profile design allows the unit to  
be installed on the floor or suspended from the ceiling.  
All unit components are securely mounted inside the  
heavy gauge “Galvalume” sheet metal cabinet. All units  
are lined with a 1/2 in. thick – 21lb density acoustical  
insulation to ensure the quietest operation. All models  
are shipped with medium-efficiency 2-in. thick throw-  
away filters. Multi-position filter rack is external to the  
cabinet.  
Service access doors are equipped with handles and  
are located on all sides of the unit to allow easy servic-  
ing of all components. Service access doors are factory  
shipped with knock-outs allowing gauge lines to be  
installed and pressure readings to be taken while the  
machine is operating. In addition there is a removable  
panel on the access door so visual observation of the  
sight glass is possible without removing the access door.  
All units are equipped with centrifugal blowers combined  
with variable pitch adjustable pulleys. Forward curved  
double width and inlet centrifugal blowers are used for  
condenser & evaporator air movement. All models em-  
ploy a draw-through air flow system. All blower wheels  
are galvanized steel, with solid steel shafts and are  
equipped with permanently lubricated ball bearings. V-  
belt driven blowers are used in all models; RPM can be  
adjusted through the variable pitch motor sheave.  
Unit can be turned on its side for short periods of time,  
which allows passage through standard door sizes.  
Removal of the cross supports on the top and sides will  
convert packaged unit into a split system, allowing the  
condensing section to be installed remotely from the  
evaporator section.  
ONLYQUALIFIEDPERSONNELSHOULD  
PERFORM INSTALLATION AND SER-  
VICE OF THIS EQUIPMENT.  
Horizontal units 2, 3, 4 & 5 ton models have a single  
refrigerant circuit configuration.All models are equipped  
with an adjustable thermal expansion valve (with exter-  
nal equalizer), one valve per circuit. Each refrigerant  
circuit is also equipped with a liquid line filter drier, sight  
glass/moisture indicator and easy access service gauge  
ports.All 2-5 ton models are shipped as factory-charged  
unitized packages. The 2-5 ton units include refrigerant  
line shut-off valves to allow the units to be field split.  
High efficiency scroll compressors are used in all mod-  
els, mounted on durable rubber isolator pads reducing  
vibration and noise while operating. Large evaporator  
and condenser coil face areas reduce noise levels, air  
pressure drops and minimize potential for condensate  
blow off. All models are equipped with copper tube and  
rippled aluminum plate fin coils.  
Installation time is minimized with all models. When plan-  
ning an installation consider power supply, thermostat,  
condensate drain line, duct run, servicing allowances,  
and load points. A remote thermostat control device is  
field supplied and installed to control the units operation.  
Each refrigerant circuit is equipped with auto-reset high  
pressure and low pressure switches. Each circuit is con-  
stantly monitored by ComfortAlert module. By monitoring  
and analyzing data from the Copeland Scroll compressor  
and the thermostat demand, the module can accurately  
detect the cause of electrical and system related failures  
and protect the compressor. A flashing LED indicator  
communicates the ALERT code and guides the service  
technician more quickly and accurately to the root cause  
of a problem. Control circuit is 24-volt operation with  
oversized transformer. Optional anti-short circuit timers  
can be field/factory installed.  
Units will operate reliably at an outdoor ambient down  
to 60 deg F.  
4
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
TYPICAL INSTALLATION DRAWING  
5
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
PRE-INSTALLATION INSPECTION OF EQUIPMENT  
INSTALLATION  
Lock all electrical power supply switch-  
es in the off position before installing  
the unit. Failure to disconnect power  
supply may result in electrical shock or  
even death.  
All units are factory tested to ensure safe operation  
and quality assembly. Units are packaged and sealed  
on shipping skids and shipped in first class condition.  
Torn and broken packaging, scratched or dented panels  
should be reported to carrier immediately. An internal  
inspection of each unit should be performed prior to  
installation. Remove all access doors and check for  
visual defects that can occur during transport.Any prob-  
lems found internally should be reported to carrier and  
manufacturer immediately. Refrigerant circuit should be  
checked to ensure no leaks have occurred during ship-  
ment. Install gauge set on high and low pressure ports  
to confirm pressure has been maintained and no leaks  
have occurred during shipment. Repair any damage  
prior to installation to ensure safe operation.  
Location - To ensure unit operates at maximum efficien-  
cies, choose a dry indoor area where the temperature  
is controlled between 50 deg F and 115 deg F. Con-  
sideration of surrounding areas should be taken when  
choosing a location to install the unit. Common vibration  
and sound levels associated with commercial equipment  
may be objectionable to people or equipment.  
Failure to allow adequate space between  
units may result in poor unit perfor-  
mance and possible unit failure.  
Record any unit damage on the Bill of  
Lading and report to carrier and factory  
immediately. Shipping and handling  
damages are not warranty items.  
Refer to typical installation diagram (Page #5).  
RIGGING  
Install thermostats, air supplies and returns so that each  
unit will operate only on individual unit control. To assure  
fast drainage of condensate run-off, unit can be slightly  
pitched in the same direction as drain pan outlet.  
Prior to mounting unit, check individual  
unit weights (pages 7-8) and verify lifting  
capacity of lifting equipment exceeds  
weight of units by safe margins. Failure  
to do so may result in unit damage, per-  
sonal injury or even death.  
To ensure safe installation of the unit when ceiling mount  
application is specified, estimate the approximate center  
of gravity of the unit. The configuration of internal com-  
ponents for each unit is different and weight is unevenly  
distributed.  
Determine the actual center of gravity of  
the unit by performing a test lift. Lifting  
an unbalanced unit can cause personal  
injury or even death.  
6
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
UNIT MOUNTING  
Aminimum of 4-in. clearance is required under the unit to  
allow for trapping of the evaporator condensate drain.  
The 2 through 5 ton unit consist of an evaporator and  
condenser module. These two modules are rigidly at-  
tached by a joining strip across the top of the two cabinet,  
and two long side cross-member angles which bridge the  
mounting channels on the bottom of the unit. These units  
may be field split to allow for passage through doors,  
elevators, hallways, etc. Alternatively, the units may be  
installed as a split system after separation.  
Floor mounted units should be secured on a solid, level  
pad. The use of isolating vibro-pads at several points  
under the bottom mounting channels is recommended.  
Ensure that provision is made for clearance to install a  
trap on the condensate drain outlet.  
Units may be either hung, or floor mounted. If unit is to  
be hung, use all mounting points indicated - regardless  
if unit is installed as a package or split system (See unit  
dimension drawings). Use of 1/2in. dia hanger rods is  
recommended. Ensure the attachment point of the rods  
to the building structure is sufficient to support the unit  
weight. In order to ensure efficient condensate drain-  
age, the unit may be pitched towards the evaporator  
end of the unit.  
7
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
SEPARATION OF UNITS  
INTERCONNECTING REFRIGERANT TUBING  
- SPLIT INSTALLATION  
The 2 through 5 ton units are provided with refrigerant  
shut-off valves to allow the evaporator and condenser  
sections to be field split - without the necessity of re-  
claiming the entire unit refrigerant charge.  
After the evaporator and condenser sections have been  
mounted, the interconnecting refrigerant tubing can be  
fabricated. Line sizing recommendations shown in the  
accompanying table are suitable for most applications.  
Consult sales office for applications outside the speci-  
fied guidelines.  
The evaporator and condenser sections may be sepa-  
rated by performing the following procedure:  
Route refrigerant tubing for minimum linear length, and  
minimum number of bends and fittings. Use long radius  
elbows for all 90-degree bends, except oil traps. Traps  
should be constructed from short radius street elbows,  
in order to keep the trap as small as possible.All brazing  
should be done using a 2 to 8 psig dry nitrogen purge  
flowing through the pipe being brazed.  
1.Close all refrigerant shut-off valves, on both suction  
and liquid lines. There are four valves in a single  
compressor model, and a total of eight valves in the  
dual compressor models. Valves are not a back-  
seating design. Caps are wrench tight. Remove  
caps and turn stem clockwise to seat in the closed  
position.  
Once the brazing operation of refrigeration lines is com-  
pleted, the field-brazed connections must be checked for  
leaks. Pressurize the system through the shut-off valve  
ports with dry nitrogen to a minimum of 400 psig. Use  
soap bubbles or alternate methods of leak-checking all  
field brazed joints. After completion of the leak check,  
evacuate the interconnecting lines to hold a 350-micron  
vacuum. If gauge pressure rises above 500 microns in  
one minute, then evacuation is incomplete or the system  
has a leak.  
2.Use the valve access ports to reclaim the refrigerant  
trapped in the lines between the pairs of shut-off  
valves.  
3.Cut the refrigerant line sections between the pairs of  
shut-off valves. It is recommended to make this out  
where accessibility is greatest - in the condensing  
section of the unit. This will allow best access for  
reconnection, or attachment of an extended line  
set in the case of a split system.  
Additional refrigerant (R-410A) must be added to the  
system due to the extended refrigerant lines. Calculate  
the amount of additional refrigerant required as fol-  
lows:  
4.Remove the interconnecting wiring between the  
evaporator and condenser electrical panel. Dis-  
connect the wire terminations in the condenser  
electrical panel, and pull the excess wire into the  
evaporator panel.  
1.5/16 in OD liquid line - add 0.40 oz per linear foot  
2.3/8 in OD liquid line - add 0.60 oz per linear foot  
3.1/2 in OD liquid line - add 1.20 oz per linear foot  
4.5/8 in OD liquid line - add 1.80 oz per linear foot  
5.Remove the threaded wire bushing connecting the  
two electrical panels.  
6.Remove the unit top-joining strip; take care to re-  
move only those screws which attaches the joining  
strip to the evaporator and condenser cabinets.  
7.Remove the two side cross-member angles.  
8.Carefully pull the evaporator section away from the  
condenser section. Take care not to damage the  
short lengths of refrigerant tubing extending into  
the condenser section.  
The separated evaporator and condenser modules may  
now be individually moved to the proposed installation  
site for re-assembly, or separately located for split ap-  
plications.  
8
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
DIMENSIONAL DATA  
9
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
DIMENSIONAL DATA (Cont.)  
10  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
DUCTWORK  
The use of louvers with higher velocities than above may  
be employed, at the discretion of the engineer/installer,  
provided that the total air pressure drop does not exceed  
the capability of the condenser fan and motor. The use  
of low restriction louvers with shallow blade angles can  
allow higher face velocities without excessive static  
pressure loss.  
When installing ductwork, adhere to local Codes and  
sensible practice. Minimize duct runs and avoid abrupt  
changes in direction where possible.Allow ample access  
space for servicing of the coils and changing of filters.  
Perform regular maintenance on ducts to increase unit  
life, maintain efficient operation, and reduce accumu-  
lation of explosive dust. Refer to blower performance  
charts, and engineer duct runs and accessory pres-  
sure drop so as not to exceed maximum external static  
values.  
Exceeding the static pressure capability of the con-  
denser fan will result in insufficient condenser air volume.  
This will cause a loss in system capacity, and may cause  
compressor shutdown during high ambient periods. (In-  
stallation of an oversize condenser motor/drive, where  
applicable, may be considered in such cases.)  
LOUVER SIZING GUIDELINES  
One of the key issues in obtaining optimum performance  
from indoor air-conditioners is the proper selection of the  
condenser intake and discharge louvers. Unlike outdoor  
air cooled units, which intake and discharge their cooling  
virtually unrestricted, indoor units must overcome the  
resistance of grilles or louvers at the outside wall - plus  
the restriction of any interconnecting ductwork.  
(As a general rule, these velocities will require an intake  
louver sized approximately 1.25 to 1.5 times the dimen-  
sions of the duct connection on the unit, and a discharge  
louver sized approximately 1.5 to 2 times the duct con-  
nection dimensions.)  
Use only louver sections that provide different deflection  
angles for air discharge and air intake, to ensure the  
unit does not short circuit. Protect the unit from weather  
conditions (rain, snow) entering through the condenser  
air intake. All outdoor air ducts should pitch away from  
the unit, toward the outside wall. Connect all ducts to unit  
with canvas section duct connectors or choose another  
suitable noise and vibration absorbing device.  
Our indoor air cooled air-conditioners are designed to ac-  
commodate the external static pressure loss associated  
with properly sized louvers of the “storm proof” type. This  
type of louver typically has a free area approximately  
40-45% of the actual louver size. To determine the free  
area required for any given unit, adhere to the following  
guidelines:  
- Size condenser air intakes for 500-750 feet/minute  
nominal velocity  
The Manufacturer will not accept any  
liability resulting from incorrect instal-  
lation of this equipment. Follow instal-  
lation instructions carefully.  
(Maximum recommended 800 feet/minute)  
- Size condenser air discharge for 1,200-1,500 feet/  
minute nominal velocity  
(Maximum recommended 1,700 feet/minute)  
11  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
ELECTRICAL WIRING  
PACKAGED UNIT  
If unit is to be installed as a complete integral unit, the  
thermostat (low voltage) wiring is to be brought through  
connection “A”, while power wiring will be brought  
through connection “C”). Make sure you check the unit  
data plate for full specifications as previously mentioned  
(i.e. minimum circuit ampacity and fuse size).  
Follow local electrical codes when making electrical  
connections.Unitsarecompletelyfactorywiredfornormal  
supply voltages (ie.208-230, 460, 575/3phase/60Hz)  
Confirm unit specifications by checking unit data plate.  
The factory wiring terminates in two boxes, one in each  
section of the unit. The electrical control boxes are  
located behind outer access panels. Each electrical  
compartment has its own control cover.  
SPLIT SYSTEM  
If the unit is a split system application (condenser sec-  
tion remote from evaporator section), the following wir-  
ing instructions are applicable. The thermostat wiring  
is brought through connection “A” on the evaporator  
section, and is then interconnected via connection “B”  
on the condenser section. The power wiring is brought  
through “C” on the condenser section. The power feed  
to the evaporator is run through “D” on the evaporator  
section.  
Provide individual power disconnects for each unit, or  
each section in the case of split applications. Install a  
secure ground to both evaporator and condenser. If  
canvas joiners are used on ductwork, install a ground  
wire to the ductwork as well. Unit requires installer to  
provide a 24volt thermostat with appropriate heating  
and cooling stages as needed. The condenser section  
electrical cover is installed with wiring diagrams on the  
inner access door, which must be opened to read the  
diagrams.  
IMPORTANT: All wiring must comply  
with applicable local and national codes  
(NEC). Type and location of disconnect  
switches must comply with all applicable  
codes.  
Disconnect and lock out power when  
servicing unit. Unit may start automati-  
cally if power is not disconnected. Fail-  
ure to do so may result in personal injury  
or death due to electrical shock.  
For low voltage wiring, 18 gauge wire may be used for  
up to 50 feet lengths. Low voltage runs up to 125 feet  
require 16-gauge wire.  
12  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
STANDARD MOTORS  
MODEL  
VOLTAGE  
COMPRESSOR  
RLA  
EVAPORATOR FAN  
CONDENSER FAN  
MIN. CCT.  
"MOP"  
Max Overcurrent  
Prot.  
#
QTY  
1
1
LRA  
HP  
FLA  
HP  
FLA  
AMPACITY  
23.98  
14.35  
DSH  
24H12 208-230/1/60  
DSH  
24H32 208-230/3/60  
@
@
13.5  
8.6  
58.3  
55.0  
0.25  
0.25  
2.6  
1.4  
0.50  
0.50  
4.5  
2.2  
35  
20  
DSH  
36H12 208-230/1/60  
DSH  
36H32 208-230/3/60  
1
1
1
1
@
@
@
@
14.1  
9.0  
5.6  
3.8  
77.0  
71.0  
38.0  
36.5  
0.33  
0.33  
0.33  
0.50  
3.3  
1.6  
0.8  
0.9  
0.75  
0.75  
0.75  
0.75  
5.5  
2.6  
1.3  
1.0  
26.43  
15.45  
9.10  
40  
20  
15  
15  
DSH  
36H34  
36H35  
DSH  
460/3/60  
575/3/60  
6.63  
D
S
H
48H12 208-230/1/60  
1
1
1
1
@
@
@
@
19.9  
13.1  
6.1  
109.0  
83.1  
41.0  
34.0  
0.75  
0.75  
0.75  
0.75  
5.5  
2.6  
1.3  
1.0  
1.00  
1.00  
1.00  
1.00  
6.3  
3.3  
1.5  
1.1  
36.68  
22.28  
10.43  
8.35  
50  
35  
15  
15  
48H32 208-230/3/60  
DSH  
48H34  
DSH  
D
S
H  
460/3/60  
575/3/60  
48H35  
5.0  
60H32 208-230/3/60  
DSH  
1
1
1
@
@
@
16.0  
7.8  
5.7  
110.0  
52.0  
38.9  
1.00  
1.00  
1.00  
3.3  
1.5  
1.1  
1.50  
1.50  
1.50  
4.6  
2.1  
1.7  
27.90  
13.35  
9.93  
40  
20  
15  
DSH  
60H34  
460/3/60  
575/3/60  
DSH  
60H35  
Notes:  
Data shown for packaged unit installation, with single point power supply.  
For split installation with separate evaporator motor power supply, calculate MCA and MFS as follows -  
Min. Circuit Ampacity ( MCA ) = 1.25 X Largest motor amps (FLA or RLA) + sum of the remaining motor amps  
Max Fuse / Cct. Bkr Size ( MFS ) = 2.25 X Largest motor amps + sum of the remaining motor amps  
Select next smallest NEC listed fuse size from calculated value  
FAN PERFORMANCE DATA  
SUPPLY AIR BLOWER PERFORMANCE  
EXTERNAL STATIC PRESSURE - Inches W.C.  
0.8 1.0 1.2  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
MODEL  
SUPPLY  
CFM  
0.2  
0.4  
0.6  
1.4  
1.6  
1.8  
700  
800  
900  
593 0.06 755 0.10 915 0.13 1048 0.17 1175 0.23  
629 0.08 777 0.12 914 0.16 1169 0.20 1178 0.25  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2 TON  
668 0.11 804 0.15 930 0.19 1170 0.24  
-
-
1000  
1200  
1400  
598 0.11 722 0.16 835 0.19 930 0.25 1141 0.32  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 TON  
4 TON  
727 0.20 831 0.25 929 0.31 972 0.33  
747 0.26 844 0.32  
-
-
-
-
-
-
-
-
1450  
1600  
1800  
595 0.22 661 0.27 745 0.31 836 0.38 909 0.45 982 0.52 1046 0.61  
601 0.26 691 0.33 773 0.39 847 0.44 921 0.51 987 0.61 1056 0.67  
-
-
-
-
-
-
-
-
-
-
-
-
652 0.35 735 0.42 812 0.5 883 0.57 948 0.64 1018 0.72  
-
-
1800  
2000  
2200  
583 0.30 674 0.37 755 0.44 830 0.52 900 0.59 966 0.69 1037 0.75  
688 0.45 767 0.53 839 0.61 907 0.69 971 0.77 1029 0.85 1086 0.92  
-
-
-
-
-
-
-
-
-
-
-
-
5 TON  
677 0.5 754 0.59 826 0.68 894 0.77 957 0.86 1018 0.95  
-
-
NOTE:  
1. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary.  
2. Values include pressure drop from wet coil and clean filters.  
3. Shaded areas indicate oversize motors  
4. Adjustment limits of standard factory-installed drives are indicated by bold borders. (See pulley data on Pg. 17)  
14)  
CONDENSER AIR BLOWER PERFORMANCE  
EXTERNAL STATIC PRESSURE - Inches W.C.  
MODEL OUTDOOR  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2 TON  
3 TON  
4 TON  
5 TON  
1600  
1950  
2500  
2900  
750 0.29 852 0.35 948 0.42 996 0.46  
864 0.47 949 0.55 1032 0.63 1112 0.72  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
645 0.53 749 0.63 812 0.74 872 0.86 945 0.98  
723 0.79 800 0.84 871 1.07 935 1.20 996 1.55 1057 1.42  
13  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
MOTOR AND PULLEY DATA  
EVAPORATOR  
- STANDARD BLOWER MOTOR AND DRIVE DATA  
Adjustable  
Motor Pulley  
Fixed  
Blower Pulley  
Motor  
Belts  
Drive Range  
Model  
(RPM)  
Pitch Dia.(in)  
Browning #  
Pitch Dia.(in) Browning#  
Rating / Size  
HP  
Frame Eff.(%)  
Qty  
2 TON  
3 TON  
4 TON  
5 TON  
845-1170  
675-1010  
675-1010  
745-1120  
1/4  
1/3  
3/4  
1
56  
56  
56  
66.0  
75.0  
75.0  
75.0  
2.6-3.6  
2.0-3.0  
2.0-3.0  
2.0-3.0  
1VP40 X 5/8  
1VP34 X 5/8  
1VP34 X 5/8  
1VP34 X 7/8  
5.4  
5.2  
5.2  
4.7  
AK56H  
AK54H  
AK54H  
AK49H  
4L370  
4L370  
4L400  
4L390  
1
1
1
1
143  
CONDENSER  
- STANDARD BLOWER MOTOR AND DRIVE DATA  
Adjustable  
Motor Pulley  
Fixed  
Blower Pulley  
Motor  
Belts  
Drive Range  
Model  
(RPM)  
Pitch Dia.(in)  
Browning #  
Pitch Dia.(in) Browning#  
Rating / Size  
HP  
Frame Eff.(%)  
Qty  
2 TON  
3 TON  
4 TON  
5 TON  
770-1070  
745-1071  
615-920  
1/2  
3/4  
1
56  
56  
143  
145  
75.0  
82.5  
82.5  
84.0  
2.6-3.6  
2.0-3.0  
2.0-3.0  
2.6-3.6  
1VP40 X 5/8  
1VP34 X 5/8  
1VP34 X 7/8  
1VP40 X 7/8  
5.9  
4.7  
5.7  
5.9  
AK61H  
AK49H  
AK59H  
AK61H  
4L500  
4L390  
4L490  
4L500  
1
1
1
1
770-1070  
1.5  
BLOWER SPEED ADJUSTMENT  
3.Blower speed will increase when moveable flange is  
adjusted towards the fixed flange (closed). Blower  
speed will decrease when the moveable flange  
is adjusted away from the fixed flange (opened).  
Pulleys are adjustable only in half-turn increments.  
Do not open pulley more than five full turns for “4L”  
and “A” belts, or six full turns for “B” belts.  
The RPM of the supply air and condenser air blow-  
ers will depend on the required CFM, and the static  
resistance of both the supply/discharge and the return/  
intake duct systems. With this information, the RPM  
for the blowers can be determined from the blower  
performance tables. Adjustment of blower speed is  
accomplished as follows:  
1.Loosen belt tension by moving motor towards the  
blower shaft via the adjustable mounting base.  
4.Once the pulley has been opened/closed the ap-  
propriate number of turns, replace the external key  
and tighten the adjustment set screw. Proper torque  
is 110 - 130 in-lbs.  
2.Loosen the setscrew in the adjustable motor pul-  
ley flange. Remove external key on pulleys 4-in.  
dia and larger.  
5.Install drive belt and adjust motor mount to tension  
belt.  
14  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
START-UP AND OPERATION  
Prior to starting unit for the first time,  
If opposite rotation is needed, disconnect and reverse  
any two leads of the three phase supply. Reconnect  
power and observe for correct rotation.  
turn the thermostat system switch to  
oFF - or raise the cooling setpoint to  
the highest temperature, to prevent the  
unit from starting. Close the electrical  
disconnect switch. This will energize the  
compressor crankcase heater(s). WAIT  
A MINIMUM OF FOUR HOURS BEFORE  
STARTING THE SYSTEM. This period will  
allow the crankcase heater to vaporize  
any liquid refrigerant in the compressor  
crankcase.  
Observe unit operation and check for unusual noise or  
vibration.  
REFRIGERANT CHARGES  
Ref. Charge  
No. of Circuits  
Per Circuit (lb)  
2 TON  
1
3 TON  
1
4 TON  
1
5 TON  
1
7.625  
8.125  
11.188  
10.938  
Start unit and check rotation of fans and compressors.  
The Air Conditioning section of this  
equipment is charged with R-410A; a hi-  
pressure refrigerant. Only qualified techni-  
cians, using appropriately pressure-rated  
test instruments, should perform trouble-  
shooting or service on this equipment.  
Scroll compressors will only compress in one rotational  
direction. Three phase compressors will rotate in either  
direction depending upon phasing of the power. Since  
there is a 50-50 chance of connecting power in such a  
way as to cause rotation in the reverse direction, it is  
important to ensure proper rotation direction is achieved  
when the system is installed and operated.  
PRESSURE SWITCH SETTINGS  
Verification of proper direction is made by observing  
that suction pressure drops and discharge pressure  
rises when the compressor is energized. Reverse rota-  
tion also results in an elevated sound level as well as  
substantially reduced current draw.  
ALL MODELS  
High  
600  
Low  
55  
Cut Out (PSIG)  
Cut In (PSIG)  
450  
75  
There is no negative impacts on durability caused by  
operating three phase Scroll compressors in the re-  
versed direction for a short period of time (less than one  
hour). However, after several minutes of operation the  
compressors internal protector will trip.  
RECCOMENEDED REFRIGERANT LINE SIZES  
LESS THAN 60 LINEAR FEET  
60 - 150 LINEAR FEET  
UNIT SIZE  
LIQUID LINE  
SUCTION LINE  
5/8  
LIQUID LINE  
SUCTION LINE  
3/4  
2 TON  
3 TON  
4 TON  
5 TON  
8 TON  
10 TON  
12 TON  
15 TON  
5/16  
3/8  
3/8  
3/8  
3/4  
7/8  
3/8  
7/8  
1/2  
1-1/8  
3/8  
1-1/8  
1/2  
1-1/8  
2 X 3/8  
2 X 3/8  
2 X 1/2  
2 X 1/2  
2 X 7/8  
2 X 1-1/8  
2 X 1-1/8  
2 X 1-1/8  
2 X 3/8  
2 X 1/2  
2 X 1/2  
2 X 5/8  
2 X 1-1/8  
2 X 1-1/8  
2 X 1-3/8  
2 X 1-3/8  
NOTES: - Maximum Suction Lift 60 FT  
- Maximum Liquid Line Rise 40 FT (measured from condensing unit level).  
- Liquid Line Solenoid Valve required on systems over 100 linear feet.  
- Suction Accumulator(s) required on systems over 125 linear feet.  
15  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
TYPICAL SCHEMATIC  
16  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
MAINTENANCE / SERVICE  
Disconnect And Lock Out Power When  
DRIVE BELTS  
Examine belts periodically for wear. Glazed areas on the  
drive surfaces indicate overheating due to belt slippage.  
Ideal tension is the lowest tension at which the belt will  
not slip under peak load conditions. Over-tensioning  
shortens belt and bearing life.  
Servicing Unit. Failure To Do So May  
Result In Personal Injury Or Death Due  
To Electrical Shock.  
The tension on the belt should be adjusted for a deflec-  
tion of 1164 of an inch per inch of belt span, with the ap-  
propriate force applied at the midpoint of the span. Ten-  
sion “New” belts at the maximum value indicated. Used  
belts should be maintained at the minimum value.  
Exercise care when working around  
the sharp metal edges of door panels  
or door frames, etc. These edges can  
cause injury.  
FILTERS  
Inspect filters monthly and replace as necessary. Use UL  
Class 2 rated filters. Factory supplied filters are medium  
efficiency, extended surface pleated type. Replacements  
should be of the same type, to maintain optimum airflow  
performance. Filter sizes are as follows:  
FILTERS  
QTY / SIZE  
FILTERS  
2 TON  
2 / 20 x 14 x 2  
4 TON  
3 TON  
2 / 20 x 14 x 2  
5 TON  
QTY / SIZE  
2 / 25 x 16 x 2  
2 / 25 x 16 x 2  
POUNDS FORCE  
EVAPORATOR AND CONDENSER COILS  
Belt Cross Section  
Min.  
1-1/2  
3-1/2  
5-1/2  
8
Max.  
2-1/2  
6-1/2  
8
Inspect the evaporator coil at filter change intervals.  
Inspect the condenser coil at least semi-annually. A  
dirty condenser coil will result in elevated condensing  
pressures and poor unit performance. Dirty or clogged  
evaporator coils cause low suction pressure and lost  
capacity. If the coils appear dirty, clean them using mild  
detergent or a commercial coil cleaning agent.  
4L  
A
B
BX  
11  
BLOWERS  
REFRIGERANT CIRCUIT(S)  
Inspect both the evaporator and condenser blowers at  
each regular service interval. Clean blower wheels as  
needed. Bearings are permanently sealed ball type, and  
do not require lubrication. Check bearings for any signs  
of wear (movement between inner and outer races). En-  
sure bearing locking collars are secure to the shaft, and  
that collar locking screw is properly set. Check that the  
blower wheel is tight on the shaft, and that the setscrews  
in the blower hub are properly torqued.  
With the unit operating, check and record the compres-  
sor discharge and suction pressures. The compressor  
running current should also be recorded.Amaintenance  
log of these readings can indicate if the unit is operating  
within its normal limits. Abnormal readings should be  
investigated, and the cause corrected.  
17  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
COMFORT ALERT™ DIAGNOSTICS  
The ComfortAlert diagnostics module is a breakthrough  
innovation for troubleshooting and protecting three  
phase Copeland Scroll® compressors. The module  
installs easily in the electrical box of the condensing  
unit near the compressor contactor. By monitoring and  
analyzing data from the Copeland Scroll compressor  
and the thermostat demand, the module can accurately  
detect the cause of electrical and system related failures  
and protect the compressor. A flashing LED indicator  
communicates the ALERT code and guides the service  
technician more quickly and accurately to the root cause  
of a problem.  
This module provides compressor  
protection and will shut down the com-  
pressor when compressor damaging  
conditions are detected.  
INTERPRETING THE DIAGNOSTIC LEDS  
When an abnormal system condition occurs, the Comfort  
Alert module displays the appropriate ALERT and/or  
TRIP LED. The yellowALERT LED will flash a number of  
times consecutively, pause and then repeat the process.  
To identify a Flash Code number, count the number of  
consecutive flashes. Every time the module powers up,  
the last ALERT Flash Code that occurred prior to shut  
down is displayed for one minute. If the yellow ALERT  
LED is on solid more than 2 amps are conducted through  
the PROT terminal. The contactor coil may be shorted  
or the PROT terminal miswired.  
LED DESCRIPTION  
POWER LED (Green): indicates voltage is present at  
the power connection of the module.  
ALERT LED (Yellow): communicates an abnormal sys-  
tem condition through a unique flash code. The ALERT  
LED will flash a number of times consecutively, pause  
and then repeat the process. The number of consecu-  
tive flashes, defined as the Flash Code, correlates to a  
particular abnormal condition. Detailed descriptions of  
specific ALERT Flash Codes are shown in two tables  
attached to this manual.  
Some ALERT codes indicate a compressor damaging  
condition and the Comfort Alert module will shut down  
and lock out the compressor. Refer to the tables below  
TRIP LED (Red): indicates there is a demand signal  
from the thermostat but no current to the compressor  
is detected by the module. The TRIP LED typically indi-  
cates the compressor protector is open or may indicate  
missing supply power to the compressor. A flashing  
TRIP LED indicates the anti-short cycle timer is active,  
preventing compressor from starting.  
to identify ALERT codes that result in a lock out.  
18  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
Status LED  
Green “POWER”  
Status LED Description  
Status LED Troubleshooting Information  
Supply voltage is present at module terminals  
Module has power  
Red “TRIP” LED Thermostat demand signal Y 1. Compressor protector is open  
On Solid  
is present, but the  
compressor is not running  
2. Condensing unit power disconnect is open  
3. Compressor circuit breaker or fuse(s) is open  
4. Broken supply wires or connector is not making contact  
5. Compressor power wires not routed  
through Comfort Alert  
6. Compressor contactor has failed open  
Red “TRIP” LED  
Flashing  
The anti-short cycle timer (3 minutes), in module is preventing compressor restart.  
Module locks out compressor when compressor damaging ALERT codes appear.  
Lockout ALERT codes are noted in the Status LED Description.  
During a compressor lock out, 24VAC power must be removed from module to manually reset  
Yellow "ALERT" A short circuit or over current 1. Compressor contactor coil shorted.  
LED On Solid  
condition exists on PROT  
terminal.  
2. Electrical load too high for PROT circuit  
(maximum 1 Amp)  
3. 24 VAC wired directly to PROT terminal  
Yellow “ALERT”  
Flash Code 2  
System Pressure Trip  
Discharge pressure out of  
limits or compressor over-  
loaded (if no high pressure  
switch in system)  
1. High head pressure  
2. Condenser coil poor air circulation (dirty,  
blocked, damaged)  
3. Condenser fan is not running  
LOCKOUT  
4. If low pressure switch is open:  
Refer to Code 3 for troubleshooting  
Yellow “ALERT”  
Flash Code 3  
Short Cycling  
1. If low pressure switch is open:  
a. Low refrigerant charge  
Compressor is running only  
briefly  
LOCKOUT  
b. Evaporator blower is not running  
c. Evaporator coil is frozen  
d. Faulty metering device  
e. Condenser coil is dirty  
(filter drier  
f. Liquid line restriction
blocked if present)  
2. If high pressure switch is open, go to  
Flash Code 2 information  
3. Intermittent thermostat demand signal  
4. System or control board defective  
19  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
Status LED  
Status LED Description  
Status LED Troubleshooting Information  
1. Low line voltage to compressor  
Yellow “ALERT”  
Flash Code 4  
Locked Rotor  
LOCKOUT  
2. Excessive liquid refrigerant in compressor  
3. Compressor bearings are seized  
Yellow “ALERT”  
Flash Code 5  
Open Circuit  
1. Condensing unit power disconnect is open  
2. Compressor circuit breaker or fuses are open  
3. Compressor contactor has failed open  
4. High pressure switch is open and requires manual reset  
5. Broken supply wires or connector is not making contact  
6. Unusually long compressor protector reset time due to  
extreme ambient temperature  
7. Compressor windings are damaged  
Yellow “ALERT”  
Flash Code 6  
Missing Phase  
LOCKOUT  
1. Compressor fuse is open on one phase  
2. Broken wire or connector on one phase  
3. Compressor motor winding is damaged  
4. Utility supply has dropped one phase  
Yellow “ALERT”  
Flash Code 7  
Reverse Phase  
LOCKOUT  
1. Compressor running backward due to  
supply phase reversal  
Yellow “ALERT”  
Flash Code 8  
Welded Contactor  
Compressor always runs  
1. Compressor contactor has failed closed  
2. Thermostat demand signal not connected to module  
1. Control circuit transformer is overloaded  
Yellow “ALERT”  
Flash Code 9  
Low Voltage  
Control circuit < 18VAC  
2. Low line voltage to compressor  
Resetting Alert Codes  
Flash code number corresponds to a number of LED  
Alert codes can be reset manually and automatically.  
The manual method to reset anAlert code is to cycle the  
power to Comfort Alert off and on. For automatic reset,  
Comfort Alert continues to monitor the compressor and  
system after an Alert is detected. If conditions return to  
normal, theAlert code is turned off automatically.ALERT  
codes that result in a compressor lock out can only be  
reset manually. ALERT codes that result in a lockout  
can only be reset manually.  
flashes, followed by a pause and then repeated.  
TRIP and ALERT LED’s flashing at the same time  
means control circuit voltage is too low for opera-  
tion.  
20  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
Miswiring the Comfort Alert module will cause false LED codes. Table 1 describes LED opera-  
tion when the module is miswired and what troubleshooting action is required to correct the  
problem.  
TABLE 1 - COMFORT ALERT MODULE TROUBLESHOOTING  
Installation Verification  
To verify the installation of Comfort Alert is correct, a functional test can be performed. Force a call for cooling and  
when the compressor starts to run, monitor the yellowALERT LED. The LED should remain off during test. Disconnect  
power to the compressor while the call for cooling is still active. The red TRIP LED will flash indicating the anti-short  
cycle timer is active. If the red LED does not function as described, refer to Table 1 to verify the wiring.  
21  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
LIMITED WARRANTY  
ONE YEAR LIMITED WARRANTY  
Johnson Controls warrants this product to be free from defects in workmanship or material for a period of one year from date of original  
installation or 18 months from date of shipment, whichever comes first.  
Johnson Controls obligation under this Warranty is LIMITED to repairing or replacing at our sole option, at our factory, any part thereof  
which shall be returned to our factory, transportation charges prepaid and which on examination proves to have been thus defective  
under normal domestic use not exceeding the fuel rating. The defective part should be returned through a qualified servicing dealer.  
Upon warranty determination, the replacement part will be shipped freight collect and assumes the unexpired portion of this Limited  
Warranty.  
When a defective part can be repaired or replaced, Johnson Controls shall not be obligated to repair the entire unit or any part thereof  
other than the defective part.  
This warranty applies only to the original homeowner, and is subject to the terms and conditions hereof.  
COMPRESSOR – FIVE YEAR LIMITED WARRANTY  
In addition to the One Year Limited Warranty, Johnson Controls warrants the compressor to be free from defects in workmanship or  
material for a period of five (5) years from the date of original installation. If a compressor fails during this five year period, a new com-  
pressor will be supplied. The customer will be responsible for freight costs from our factory for delivery of the replacement compres-  
sor and also for the return of the defective compressor which may be required under the terms of the Warranty. Labor and any other  
expense involved in replacing the compressor is not covered by this Warranty.  
LABOR AND COST NOT COVERED  
This Warranty provides only replacement parts or credits, and does not provide for or cover any labor, shipping, handling or other costs  
for service travel, servicing, removing, or installing any parts.  
EXCLUSIONS  
This Warranty shall be void if:  
1. The unit is not installed by a licensed or otherwise qualified or contractor and in compliance with the Installation Manual, applicable  
installation and good trade practices.  
2. The defect or damage is caused by accident, abuse, negligence of any person or company, misuse, riot, flood, fire or Acts of  
God.  
3. The unit is not operated and regularly serviced and maintained as called for in the Users’ Manual.  
4. Damages are caused by operating the unit in a commercial or corrosive atmosphere containing any damaging or dangerous  
chemicals.  
5. The unit is modified or services in a manner not in accordance with the Installation Manual and Users’ Manual.  
6. Components, replacement parts, or other accessories not compatible with the unit or not approved by Johnson Controls have  
been used with or attached to the unit.  
7. The defect or damage is not caused by Johnson Controls, or it arises from circumstances beyond the control of Johnson Controls.  
8. The unit is installed outside the United States or Canada, or has been removed from the place where it was originally installed.  
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, OBLIGATIONS OR LIABILITIES, EXPRESSED OR IMPLIED BY  
EMPLOYEES OR REPRESENTATIVES OF JOHNSON CONTROLS. ALL STATUTORY, EXPRESSED OR IMPLIED WARRANTIES,  
INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY  
NEGATED AND EXCLUDED. ANY CLAIMS FOR INCIDENTAL AND CONSEQUENTIAL DAMAGES, OR ANY OTHER DAMAGES  
OR EXPENSES BEYOND THE TERMS OF THIS LIMITED WARRANTY ARE HEREBY EXPRESSLY NEGATED AND EXCLUDED.  
22  
JOHNSON CONTROLS  
FORM 145.32-IOM1 (908)  
R-410A QUICK REFERENCE GUIDE  
Refer to Installation Instructions for specific installation requirements.  
• R-410A Refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing  
equipment and replacement components are designed to operate with R-410A.  
• R-410A Refrigerant cylinders are rose colored.  
• Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.  
• Recovery equipment must be rated for R-410A.  
Do not use R-410Aservice equipment on R-22 systems. All hoses, gages, recovery cylinders, charging  
cylinders and recovery equipment must be dedicated for use on R-410A systems only.  
• Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard.  
• All hoses must have a service pressure rating of 800 psig.  
• Leak detectors, must be designed to detect HFC refrigerants.  
• Systems must be charged with refrigerant. Use a commercial type metering device in the manifold  
hose.  
• R-410A can only be used with POE type oils.  
• POE type oils rapidly absorb moisture from the atmosphere.  
• Vacuum pumps will not remove moisture from POE type oils.  
Do not use liquid line driers with a rated working pressure rating less than 600 psig.  
Do not install suction line drivers in the liquid line.  
• A liquid line drier is required on every unit.  
Do not use an R-22 TXV. If a TXV is to be used, it must be an R-410A TXV.  
• Never open system to atmosphere when under vacuum.  
• If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and  
replace filter driers.  
23  
JOHNSON CONTROLS  
Subject to change without notice. Printed in U.S.A.  
Copyright© 2008 by Unitary Products Group. All rights reserved.  
Form 145.32-IOM1 (908)  
New Release  
Engineered Systems  
Products  
P.O. Box 1592  
York, PA  
York  
PA  
Group  
17405  
17405  

Brother MFC J6710DW User Manual
Code Alarm CR3 User Manual
Danby DAC5210M User Manual
Danby DPAC 12099 User Manual
Electro Voice Constant Directivity Horn HP940 User Manual
Epson Stylus SX200 User Manual
Havis Shields Impala C SM 830 User Manual
Hitachi RAS 14KH2 User Manual
Honda Automobiles Tonneau Cover 4D16070S User Manual
Honeywell M847D User Manual