PRODUCT SPECIFICATIONS
PCB
COMMERCIAL SERIES
50 Hz
SELF-CONTAINED
PACKAGE AIR CONDITIONER
7½, 10, AND 15 TON
[26.4 kW to 52.8 kW]
COOLING CAPACITY:
90,000 TO 180,000 BTU/H
The PCB Commercial 50 Hz self-contained
packaged air conditioner is designed for
ground-level or rooftop application.
Standard Features
Cabinet Features
• Dual high-efficiency scroll compressors with
internal motor protection (2-stage cooling;
three compressors on 15-ton units)
• Compressor grommets for vibration isolation
• Time delay for compressor sequencing
• Fully charged systems
• Heavy-gauge, zinc-coated steel cabinet with
weather-resistant powder-paint finish
• Fully insulated with blankets of insulation
• Built-in filter rack
• Factory wiring conveniently arranged for
installation of accessories
• High- and low-pressure controls on all systems
• Mild ambient switch
• Control box and compressors easily accessible
from side access panels
• Two independent condenser coils for
2-stage operation
• Totally enclosed, permanently lubricated ball-
bearing outdoor fan motors
Accessory Heat Kit Features
• Control circuitry arranged to readily
permit staging
• Rust-resistant nickel chromium heating elements
• Primary and secondary limit protection
• Factory-installed one-time fuses on all models
• Enhanced copper tube/aluminum fin coils
• Expansion valve evaporator coil
• Vertical discharge with removable grilles
• Galvanized steel, powder-coated drain pan with
3/4” (19mm) NPT condensate connection
• Belt-driven, variable-pitch sheave permits multi-
speed adjustment
• Centrifugal fan for quiet and efficient operation
• Filters (2” [50.8mm] disposable) provided
with unit
Accessories
• Room thermostat; Low-ambient control
• Rooftop Lift Kit; Roof curb
• Economizers (horizontal and vertical)
• Manual/motorized fresh air damper
• Horizontal Duct Kit (Downflow to Horizontal
Conversion)
• Electric heat capacities 15 kW-30 kW @ 415V
50 Hz (field-installed accessory)
• Panel Louver Kit
• Operates up to 125°F ambient temperature
SS-PCB50
www.goodmanmfg.com
6/06
Supersedes 12/05
PRODUCT SPECIFICATIONS
DIMENSIONS
All dimensions in inches and millimeters. Drawings are not to scale.
FIGURE 1. VERTICAL DISCHARGE
See curb details for connection of duct work to
curb. Duct work is not intended to be connected
to unit.
FIGURE 2. HORIZONTAL DISCHARGE
Note: The Horizontal Conversion Kit is required to convert
a factory duct configuration (downflow) to a horizontal
duct configuration, as shown in Figure 2.
UNIT SIZE
090
A - HEIGHT
36” (914 mm)
52” (1321 mm)
B - SUPPLY AIR
C - RETURN AIR
12½” (318 mm) 179/16” (446 mm)
20¼” (514 mm) 2513/16” (656 mm)
120,180
SS-PCB50
3
PRODUCT SPECIFICATIONS
ELECTRICAL CONNECTIONS
MODEL
PCB090-5
PCB120-5
PCB180-5
B
7⅞” (200 mm)
23⅞” (606 mm)
23⅞” (606 mm)
1– Main power entrance location (with electric heat
installed)
2– Control wiring entrance location
3– Main power entrance location (without electric heat
installed)
Note: Single-point wiring is available at location #1
when heat kit is installed. See installation instructions
for heat kits.
FIGURE 3. ELECTRICAL HEAT UNITS
ELECTRIC HEAT
ELECTRIC HEAT AIR TEMPERATURE RISE @ NOMINAL VOLTAGE
Heater Model
No. Stages
HKCB20
2
HKCB30
2
HKCB40
2
Output MBH (W)
67.5 (19.8) 101.3 (29.7) 135.0 (39.6)
Notes:
2600 (1227) 24.2 (13.4) 36.2 (20.1)
2800 (1320) 22.5 (12.5) 33.6 (18.7)
3000 (1415) 21.0 (11.7) 31.4 (17.4)
-
-
-
1. Maximum air temperature rise of 40°F (22.2°C) must not be
exceeded.
2. See Electric Heater Availability table for various unit sizes.
3. Air temperature rise is for total heating capacity: Temperature rises
at other conditions may be calculated by using the formula:
3200 (1510) 19.7 (10.9) 29.4 (16.3) 39.3 (21.8)
3400 (1605) 18.5 (10.3) 27.7 (15.4) 37.0 (20.6)
Temperature Rise =
Output Capacity - BTU/h
1.08 x ft³/min. Airflow
3600 (1700)
3800 (1793)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2171)
4800 (2265)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
17.5 (9.7)
16.5 (9.2)
15.7 (8.7)
15.0 (8.3)
14.3 (7.9)
13.7 (7.6)
13.1 (7.3)
12.6 (7.0)
12.1 (6.7)
11.6 (6.4)
11.2 (6.2)
10.8 (6.0)
10.5 (5.8)
26.2 (14.6) 34.9 (19.4)
24.8 (13.8) 33.1 (18.4)
23.5 (13.1) 31.4 (17.4)
22.4 (12.4) 29.9 (16.6)
21.4 (11.9) 28.6 (15.9)
20.5 (11.4) 27.3 (15.2)
19.6 (10.9) 26.2 (14.6)
18.8 (10.4) 25.2 (14.0)
18.1 (10.1) 24.2 (13.4)
Note: Temperature rises must be calculated in other than nominal volt-
age conditions.
4. For altitudes over 2,000’, air temperature rise must be calculated
using the formula:
CFM
&
(L/S)
Temperature Rise =
Output Capacity - BTU/h
14.4 x ft³/Min. Airflow x Specific Weight of Air
5. Operation at less than nominal voltages must be de-rated by the
following factors: 415 volt-0.75; 380 volt-0.63.
17.4 (9.7)
16.8 (9.3)
16.2 (9.0)
15.7 (8.7)
23.3 (12.9)
22.5 (12.5)
21.7 (12.1)
21.0 (11.7)
ELECTRIC HEATER AVAILABILITY
NOMINAL VOLTAGE FOR HKCB
Unit Size
HKCB20
HKCB30
HKCB40
@ 480V
19.8 kW
29.7 kW
39.6 kW
@ 415V
@ 380V
7½
10
15
X
X
X
X
X
X
X
X
X
HKCB20-4
HKCB30-4
HKCB40-4
14.9 kW
22.3 kW
29.7 kW
12.5 kW
18.7 kW
25.0 kW
4
SS-PCB50
PRODUCT SPECIFICATIONS
FAN PERFORMANCE DATA
FIGURE 4. FAN CURVE - PCB 090
SUPPLY FAN PERFORMANCE - PCB090
EXTERNAL STATIC PRESSURE (INCHES W.C.) SEE NOTE (3)
0.6 0.8 1.0 1.2
RPM RPM RPM
CFM
0.2
0.4
1.4
RPM
1.6
RPM BHP
RPM
669
734
770
807
845
BHP
0.44
0.53
0.62
0.73
0.85
RPM
816
847
877
909
942
BHP
0.59
0.69
0.79
RPM
916
944
973
BHP
BHP
BHP
BHP
BHP
2600
2800
3000
3200
3400
0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67
0.85 1030 1.03 1109 1.21 1181 1.40 1249 1.60 1312 1.91
0.97 1053 1.15 1135 1.34 1206 1.54 1273 1.75 1336 1.96
0.91 1002 1.10 1086 1.29 1162 1.49 1232 1.70 1298 1.91 1360 2.12
1.04 1032 1.24 1114 1.44 1159 1.65 1259 1.87 1324 2.09 1384 2.31
Notes:
• Selections in ITALICS require a field drive change. See following table below for drive ranges.
• Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of
external static pressure drop.
• DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).
SUPPLY FAN DRIVE DATA - PCB090
MOTOR SHEAVE - ADJUSTABLE
FAN SHEAVE - FIXED
FACTORY SETTING
2 TURNS OPENS
MOTOR SHEAVE TURNS OPEN
FAN RPM 2.0 HP MOTOR
0
1
2
3
4
5
1209
1146
1082
1018
955
891
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.
Conversion Factor:
1 CFM = 0.472 L/S
1” W.C. = 2.5 M Bar
1 HP = 0.747 kW
SS-PCB50
5
PRODUCT SPECIFICATIONS
FAN PERFORMANCE DATA (CONT.)
FIGURE 5. FAN CURVE - PCB 120
SUPPLY FAN PERFORMANCE - PCB120
External Static Pressure (INCHES W.C.)
0.8 1.0
RPM
CFM
0.2
0.4
0.6
1.2
RPM
1.4
RPM
1.6
RPM
679
706
733
761
790
818
BHP
0.73
0.83
0.95
1.07
1.21
1.36
RPM
781
805
829
855
880
906
BHP
0.98
1.10
1.23
1.37
1.52
1.68
RPM
873
894
916
938
961
985
BHP
1.26
1.39
1.53
RPM
957
975
995
BHP
BHP
BHP
BHP
RPM
BHP
3400
3600
3800
4000
4200
4400
1.58 1034 1.91 1105 2.26 1171 2.26 1233 2.99
1.71 1051 2.05 1121 2.41 1188 2.78 1249 3.17
1.85 1069 2.20 1139 2.57 1204 2.95 1266 3.36
1.68 1016 2.01 1088 2.36 1156 2.74 1221 3.14 1282 3.55
1.84 1037 2.18 1108 2.54 1175 2.93 1239 3.33 1299 3.75
2.01 1059 2.36 1128 2.73 1194 3.13 1257 3.54 1316 3.97
Notes:
• Selections in ITALICS require a field drive change. See following table below for drive ranges.
• Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of
external static pressure drop.
SUPPLY FAN DRIVE DATA - PCB120
Motor Sheave - Adjustable
Factory Setting
Fan Sheave - Fixed
Two Turns Opens
Motor Sheave Turns Open
Fan RPM 3.0 HP Motor
0
1
2
3
4
5
1242
1186
1129
1073
1016
960
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.
Conversion Factor:
1 CFM = 0.472 L/S
1” W.C. = 2.5 M Bar
1 HP = 0.747 kW
6
SS-PCB50
PRODUCT SPECIFICATIONS
FAN PERFORMANCE DATA (CONT.)
FIGURE 6. FAN CURVE - PCB180
SUPPLY FAN PERFORMANCE - PCB180
External Static Pressure (Inches W.C.) See Last Note
0.6 0.8 1.0 1.2
BHP RPM BHP RPM BHP RPM BHP RPM
CFM
0.2
0.4
BHP RPM
1.4
BHP RPM
1.6
BHP RPM
RPM
784
814
844
874
904
932
966
997
BHP
4000
4200
4400
4600
4800
5000
5200
5400
1.14
1.29
1.45
1.63
1.82
876
903
930
957
986
1.44
1.60
959
983
1.76 1036 2.10 1108 2.47 1176 2.86 1239 3.26 1300 3.67
1.93 1058 2.28 1129 2.66 1195 3.05 1258 3.46 1318 3.89
1.78 1008 2.12 1081 2.48 1150 2.86 1215 3.26 1277 3.68 1337 4.12
1.97 1034 2.32 1105 2.69 1172 3.08 1236 3.49 1297 3.92 1356 4.37
2.17 1060 2.54 1129 2.92 1195 3.32 1258 3.74 1318 4.17 1375 4.63
2.02 1014 2.39 1086 2.77 1159 3.16 1218 3.57 1280 4.00 1338 4.44 1395 4.91
2.24 1043 2.62 1113 3.01 1179 3.42 1242 3.84 1302 4.27 1360 4.73 1416 5.20
2.48 1071 2.87 1141 3.28 1205 3.70 1267 4.12 1326 4.57 1382 5.03 1437 5.51
5600 1029 2.74 1101 3.14 1168 3.56 1231 3.99 1291 4.43 1394 4.88 1405 5.36 1458 5.85
Notes:
• Selections in ITALICS require a field drive change. See following table below for drive ranges.
• Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of
external static pressure drop.
• DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).
SUPPLY FAN DRIVE DATA - PCB180
Motor Sheave - Adjustable
Factory Setting
2 Turns Opens
2
Fan Sheave - Fixed
Motor Sheave Turns Open
Fan RPM 5.0 HP Motor
0
1400
1
1446
3
4
5
1273
1209
1146
1082
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.
Conversion Factor:
1 CFM = 0.472 L/S
1” W.C. = 2.5 M Bar
1 HP = 0.747 kW
SS-PCB50
7
PRODUCT SPECIFICATIONS
FAN PERFORMANCE DATA (CONT.)
COMPONENT PRESSURE DROPS
ECONO. RETURN AIR DAMP-
MODEL
090
CFM
WET COIL
ELEC. HEAT
MED. EFF. FILTERS
ER
2600
3000
3400
3600
4000
4400
5000
5400
5600
0.06
0.06
0.07
0.05
0.05
0.05
0.13
0.13
0.16
0.03
0.04
0.05
0.05
0.06
0.08
0.10
0.12
0.13
0.03
0.04
0.05
0.03
0.04
0.04
0.06
0.06
0.08
0.14
0.14
0.18
0.14
0.14
0.14
0.18
0.21
0.23
120
180
COOLING CAPACITY DATA
PCB090-5 (SI UNITS)
INDOOR
CONDENSER AIR TEMPERATURE
35.0°C
AIR
23.9°C
29.4°C
Sens
Cap.
40.6°C
Sens
Cap.
46.1°C
Sens
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Total
Cap.
L/S
WB
Kw
Kw
Kw
Kw
Kw
22.2 32.77
19.4 30.23
16.7 27.52
13.9 26.59
22.2 34.17
19.4 31.36
16.7 28.62
13.9 28.62
22.2 35.01
19.4 32.19
16.7 30.24
13.9 30.24
15.48
18.70
23.00
24.96
17.16
21.95
26.83
26.83
18.42
24.67
28.49
28.49
8.36
7.82
7.46
7.18
8.63
8.08
7.53
7.53
8.82
8.28
7.89
7.89
30.67
28.17
26.07
24.98
31.91
29.28
26.96
26.96
32.73
30.10
28.44
28.44
14.52
17.90
21.73
23.20
16.15
20.81
25.02
25.02
17.46
23.35
26.54
26.54
9.29
8.73
8.30
8.06
9.58
9.01
8.49
8.49
9.77
9.21
8.86
8.86
28.56
26.11
24.62
23.38
29.65
27.20
25.30
25.30
30.46
28.00
26.64
26.64
13.56
17.10
20.45
21.43
15.14
19.66
23.20
23.20
16.50
22.04
24.60
24.60
10.23
9.64
9.14
8.94
10.53
9.93
9.44
9.44
10.73
10.14
9.84
9.84
26.46
24.05
23.17
21.77
27.39
25.12
23.65
23.65
28.18
25.91
24.84
24.84
12.60
16.31
19.18
19.67
14.14
18.52
21.39
21.39
15.54
20.72
22.65
22.65
11.17
10.55
9.98
24.35
21.99
21.72
20.17
25.13
23.03
21.99
21.99
25.90
23.81
23.03
23.03
11.64
15.51
17.91
17.91
13.13
17.38
19.58
19.58
14.59
19.40
20.71
20.71
12.10
11.46
10.82
10.71
12.43
11.78
11.35
11.35
12.64
11.99
11.78
11.78
1203
1416
1628
9.83
11.48
10.86
10.40
10.40
11.69
11.07
10.81
10.81
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of
evaporator coil air per degree above 26.7°C.
PCB090-5 (ENGLISH UNITS)
CONDENSER AIR TEMPERATURE
95°F
INDOOR
AIR
75°F
Sens
Kbtuh Kbtuh
85°F
Sens
Kbtuh Kbtuh
105°F
Sens
115°F
Sens
Kbtuh Kbtuh
Total
Total
Total
Sens
Total
Total
SCFM WB
Kw
Kw
Kw
Kw
Kw
Kbtuh Kbtuh
Kbtuh Kbtuh
72
67
62
57
72
67
62
57
72
67
111.8
103.2
93.9
52.8
63.8
78.5
85.2
58.5
74.9
91.6
91.6
62.9
84.2
97.2
97.2
8.36
7.82
7.46
7.18
8.63
8.08
7.53
7.53
8.82
8.28
7.89
7.89
104.6
96.1
89.0
85.2
108.9
99.9
92.0
92.0
111.7
102.7
97.0
97.0
49.6
61.1
74.1
79.1
55.1
71.0
85.4
85.4
59.6
79.7
90.6
90.6
9.29
8.73
8.30
8.06
9.58
9.01
8.49
8.49
9.77
9.21
8.86
8.86
97.5
89.1
84.0
79.8
101.2
92.8
86.3
86.3
103.9
95.6
90.9
90.9
46.3
58.4
69.8
73.1
51.7
67.1
79.2
79.2
56.3
75.2
83.9
83.9
10.23
9.64
9.14
8.94
10.53
9.93
9.44
9.44
10.73
10.14
9.84
9.84
90.3
82.1
79.1
74.3
93.5
85.7
80.7
80.7
96.2
88.4
84.7
84.7
43.0
55.6
65.5
67.1
48.2
63.2
73.0
73.0
53.0
70.7
77.3
77.3
11.17
10.55
9.98
83.1
75.0
74.1
68.8
85.7
78.6
75.0
75.0
88.4
81.3
78.6
78.6
39.7
52.9
61.1
61.1
44.8
59.3
66.8
66.8
49.8
66.2
70.7
70.7
12.10
11.46
10.82
10.71
12.43
11.78
11.35
11.35
12.64
11.99
11.78
11.78
2550
90.7
9.83
116.6
107.0
97.6
11.48
10.86
10.40
10.40
11.69
11.07
10.81
10.81
3000
97.6
119.5
109.9
103.2
103.2
3450
62
57
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other
than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of
evaporator coil air per degree above 80°F.
8
SS-PCB50
PRODUCT SPECIFICATIONS
COOLING CAPACITY DATA (CONT.)
PCB120-5 (SI UNITS)
INDOOR
CONDENSER AIR TEMPERATURE
35.0°C
AIR
23.9°C
29.4°C
40.6°C
Sens
Cap.
46.1°C
Sens
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Total
Cap.
L/S
WB
Kw
Kw
Kw
Kw
Kw
22.2 43.67
19.4 40.29
16.7 36.65
13.9 35.42
22.2 45.54
19.4 41.79
16.7 38.12
13.9 38.12
22.2 46.65
19.4 42.90
16.7 40.29
13.9 40.29
21.02
25.44
31.24
33.85
23.30
29.83
36.41
36.41
25.03
33.53
38.65
38.65
9.95
9.31
8.89
8.54
10.28
9.62
8.95
8.95
10.50
9.86
9.39
9.39
41.04
37.70
34.88
33.43
42.71
39.18
36.07
36.07
43.81
40.28
38.05
38.05
19.52
24.09
29.22
31.17
21.72
27.99
33.63
33.63
23.49
31.41
35.67
35.67
11.27
10.59
10.07
9.78
11.62
10.92
10.29
10.29
11.85
11.17
10.75
10.75
38.41
35.11
33.11
31.44
39.87
36.57
34.03
34.03
40.96
37.66
35.82
35.82
18.03
22.74
27.19
28.49
20.13
26.14
30.85
30.85
21.94
29.29
32.70
32.70
12.59
11.86
11.25
11.01
12.96
12.22
11.62
11.62
13.20
12.48
12.11
12.11
35.78
32.52
31.34
29.45
37.04
33.97
31.98
31.98
38.11
35.04
33.59
33.59
16.54
21.38
25.17
25.82
18.55
24.29
28.07
28.07
20.39
27.18
29.72
29.72
13.91
13.14
12.43
12.24
14.30
13.52
12.95
12.95
14.55
13.78
13.46
13.46
33.15
29.93
29.57
27.45
34.20
31.36
29.93
29.93
35.26
32.41
31.36
31.36
15.04
20.03
23.14
23.14
16.96
22.45
25.29
25.29
18.84
25.06
26.75
26.75
15.23
14.41
13.61
13.47
15.64
14.82
14.29
14.29
15.90
15.09
14.82
14.82
1605
1888
2170
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of
evaporator coil air per degree above 26.7°C.
PCB120-5 (ENGLISH UNITS)
CONDENSER AIR TEMPERATURE
95°F
INDOOR
AIR
75°F
Sens
Kbtuh Kbtuh
85°F
Sens
Kbtuh Kbtuh
105°F
Sens
115°F
Sens
Kbtuh Kbtuh
Total
Total
Total
Sens
Total
Total
SCFM WB
Kw
Kw
Kw
Kw
Kw
Kbtuh Kbtuh
Kbtuh Kbtuh
72
67
62
57
72
67
62
57
72
67
149.0
137.5
125.1
120.9
155.4
142.6
130.1
130.1
159.2
146.4
137.5
137.5
71.7
86.8
106.6
115.5
79.5
101.8
124.2
124.2
85.4
114.4
131.9
131.9
9.95
9.31
8.89
8.54
10.28
9.62
8.95
8.95
10.50
9.86
9.39
9.39
140.0
128.6
119.0
114.1
145.7
133.7
123.1
123.1
149.5
137.5
129.9
129.9
66.6
82.2
99.7
106.4
74.1
95.5
114.7
114.7
80.1
107.2
121.7
121.7
11.27
10.59
10.07
9.78
11.62
10.92
10.29
10.29
11.85
11.17
10.75
10.75
131.1
119.8
113.0
107.3
136.1
124.8
116.1
116.1
139.8
128.5
122.2
122.2
61.5
77.6
92.8
97.2
68.7
12.59
11.86
11.25
11.01
12.96
12.22
11.62
11.62
13.20
12.48
12.11
12.11
122.1
111.0
106.9
100.5
126.4
115.9
109.1
109.1
130.0
119.6
114.6
114.6
56.4
73.0
85.9
88.1
63.3
82.9
95.8
95.8
69.6
92.7
101.4
101.4
13.91
13.14
12.43
12.24
14.30
13.52
12.95
12.95
14.55
13.78
13.46
13.46
113.1
102.1
100.9
93.7
116.7
107.0
102.1
102.1
120.3
110.6
107.0
107.0
51.3
68.4
79.0
79.0
57.9
76.6
86.3
86.3
64.3
85.5
91.3
91.3
15.23
14.41
13.61
13.47
15.64
14.82
14.29
14.29
15.90
15.09
14.82
14.82
3400
89.2
4000
105.3
105.3
74.9
100.0
111.6
111.6
4600
62
57
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other
than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of
evaporator coil air per degree above 80°F.
PCB180-5 (SI UNITS)
CONDENSER AIR TEMPERATURE
35.0°C
INDOOR
AIR
23.9°C
Sens
Cap.
29.4°C
Sens
Cap.
40.6°C
Sens
Cap.
46.1°C
Sens
Cap.
Total
Cap.
Total
Cap.
Total
Cap.
Sens
Cap.
Total
Cap.
Total
Cap.
L/S
WB
Kw
Kw
Kw
Kw
Kw
22.2 64.17
19.4 59.19
16.7 53.86
13.9 52.05
22.2 66.90
19.4 61.40
16.7 56.02
13.9 56.02
22.2 68.54
19.4 63.03
16.7 59.20
13.9 59.20
29.53
35.59
43.83
47.66
32.71
41.82
51.22
51.22
35.09
47.01
54.38
54.38
16.42
15.36
14.67
14.10
16.97
15.87
14.77
14.77
17.33
16.27
15.49
15.49
60.17
55.27
51.14
49.01
62.61
57.44
52.89
52.89
64.22
59.05
55.79
55.79
28.00
34.49
41.88
44.75
31.14
40.10
48.26
48.26
33.66
45.02
51.20
51.20
18.63
17.50
16.64
16.15
19.21
18.05
17.00
17.00
19.59
18.46
17.76
17.76
56.17
51.35
48.42
45.97
58.31
53.48
49.76
49.76
59.89
55.07
52.38
52.38
26.48
33.39
39.93
41.85
29.56
38.39
45.30
45.30
32.22
43.02
48.02
48.02
20.83
19.63
18.61
18.21
21.45
20.22
19.23
19.23
21.85
20.64
20.03
20.03
52.17
47.42
45.69
42.93
54.01
49.53
46.63
46.63
55.57
51.09
48.98
48.98
24.95
32.29
37.99
38.94
27.99
36.68
42.34
42.34
30.78
41.02
44.84
44.84
23.04
21.76
20.59
20.27
23.68
22.40
21.46
21.46
24.11
22.83
22.30
22.30
48.17
43.50
42.97
39.90
49.71
45.57
43.50
43.50
51.24
47.11
45.57
45.57
23.43
31.20
36.04
36.04
26.42
34.96
39.38
39.38
29.34
39.03
41.66
41.66
25.25
23.89
22.56
22.33
25.92
24.57
23.68
23.68
26.37
25.01
24.57
24.57
2246
2643
3039
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of
evaporator coil air per degree above 26.7°C.
SS-PCB50
9
PRODUCT SPECIFICATIONS
COOLING CAPACITY DATA (CONT.)
PCB180-5 (ENGLISH UNITS)
INDOOR
CONDENSER AIR TEMPERATURE
95°F
AIR
SCFM WB
72
75°F
Sens
Kbtuh Kbtuh
85°F
Sens
Kbtuh Kbtuh
105°F
Sens
115°F
Sens
Kbtuh Kbtuh
Total
Total
Total
Kbtuh Kbtuh
Sens
Total
Kbtuh Kbtuh
Total
Kw
Kw
Kw
Kw
Kw
219.0
202.0
183.8
177.6
228.3
209.5
191.1
191.1
233.9
215.1
202.0
202.0
100.8
121.4
149.6
162.6
111.6
142.7
174.8
174.8
119.7
160.4
185.6
185.6
16.42
15.36
14.67
14.10
16.97
15.87
14.77
14.77
17.33
16.27
15.49
15.49
205.3
188.6
174.5
167.2
213.6
196.0
180.5
180.5
219.1
201.5
190.4
190.4
95.6
18.63
17.50
16.64
16.15
19.21
18.05
17.00
17.00
19.59
18.46
17.76
17.76
191.7
175.2
165.2
156.9
199.0
182.5
169.8
169.8
204.4
187.9
178.8
178.8
90.4
20.83
19.63
18.61
18.21
21.45
20.22
19.23
19.23
21.85
20.64
20.03
20.03
178.0
161.8
155.9
146.5
184.3
169.0
159.1
159.1
189.6
174.3
167.1
167.1
85.1
110.2
129.6
132.9
95.5
125.2
144.5
144.5
105.0
140.0
153.0
153.0
23.04
21.76
20.59
20.27
23.68
22.40
21.46
21.46
24.11
22.83
22.30
22.30
164.4
148.4
146.6
136.1
169.6
155.5
148.4
148.4
174.9
160.7
155.5
155.5
79.9
106.5
123.0
123.0
90.1
119.3
134.4
134.4
100.1
133.2
142.1
142.1
25.25
23.89
22.56
22.33
25.92
24.46
23.68
23.68
26.37
25.01
24.57
24.57
67
62
57
72
67
62
57
72
67
62
117.7
142.9
152.7
106.3
136.9
164.7
164.7
114.8
153.6
174.7
174.7
113.9
136.3
142.8
100.9
131.0
154.6
154.6
109.9
146.8
163.9
163.9
4760
5600
6440
57
Sensible heat capacities shown are based on 80 °F DB entering air at the evaporator coil. For sensible heat capacities at other
than 80 °F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80 °F, or add 84 BTU/h per 100 CFM of
evaporator coil air per degree above 80 °F.
EVAPORATOR MOTOR HEAT
Horsepower/(kW)
2 (1.49)
BTU/h (KW)
4400 (1.29)
6200 (1.82)
10,500 (3.08)
3 (2.24)
5 (3.73)
10
SS-PCB50
PRODUCT SPECIFICATIONS
APPLICATION DETAILS AND ACCESSORIES
FACTORY SUPPLIED ACCESSORIES THERMOSTAT (CHT90-120)
Two-stage cool and two-stage heat thermostat with subbase, Manual changeover, Fan ON or AUTO. Note: A variety
of thermostat configurations can be used on this equipment based on the application needs. For example our
CHTS36-60 can be used if two-stage cooling and single-stage heat is desired. Our CHT18-60 can be used if single-
stage cooling and heating is desired. A single-stage cooling and two-stage heating thermostat can be used.
ROOFTOP LIFT KIT (RLK90-120)
Kit consists of four ½” (12.7mm) shackles that are used to lift the equipment into position on a roof, etc. The
shackles are to be attached to the mounting holes in the base rails. Wire or strap material along with field supplied
spreader bars are employed to complete the lifting assembly (See Rigging detail).
LOW AMBIENT CONTROL (LA-01)
Liquid temperature (or pressure) operated solid state control, which varies the speed of one of the condenser fans.
Low ambient control reduces fan motor RPM as liquid temperature (or pressure) decreases. Caution: If control is
used below 50 °F (10 °C) accumulators should be added to the equipment to avoid slugging of the compressors.
ROOF CURB (PGC-5)
Full perimeter curb for equipment in the down discharge application. Curb includes provisions for duct attachment
prior to setting unit. Curb is shipped knocked down with all necessary hardware and gasket material.
MANUAL AND MOTORIZED FRESH AIR DAMPERS (PGMD-5 & PGMDM-5)
Manual damper is fixed position type for 0 to 25% fresh air. Motorized damper is a field adjustable mechanical
damper for 0 to 25% fresh air, damper automatically closes when blower stops.
ECONOMIZERS (PGED 090/102-5 & PGED 120/180-5)
Fully modulating, enthalpy controlled economizers shipped with major components pre-assembled. Plug assembly
on equipment and economizer provides easy wiring.
HORIZONTAL DUCT KIT (PGHDK 090/102-5 & PGHDK 120/180-5)
The unit is shipped in the down flow (vertical) duct configuration. The horizontal duct kit must be installed in the
field for horizontal duct configuration.
PANEL LOUVER KIT (PLK090/102-5 & PLK120/180-5)
Louvered panels for condenser coil protection.
HEAT KIT ACCESSORY
Slide in heat kit from 15 to 30 kW @ 415V, 3Ph, 50 Hz are available. For 380/415V operation the -4 electrical
designation on HKCB heat kits must be used. The heating output is derated as shown by example on page 11 at
both 380V & 415V.
Bulletin illustrations cover the general appearance of Goodman Manufacturing Company, L.P., products at the
time of publication, and we reserve the right to make changes in design and construction at any time without
notice.
SS-PCB50
11
PRODUCT SPECIFICATIONS
QUALITY MAKES THE DIFFERENCE!
All of our systems are designed and manufactured with the same high-quality standards, regardless of size or efficiency. We have designed these units to significantly
reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit
is run-tested before it leaves the factory. That’s why we know...there’s no better quality.
Visit our website at
Goodman Products • Customer Services • Parts
Goodman Manufacturing Company, L.P.
2550 North Loop West, Suite 400
Houston, Texas 77092 USA
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations.
Copyright © 2003 Goodman Manufacturing Company, L.P. Houston, Texas Printed in the USA. Goodman products are made proudly in the USA.
•
•
•
12
SS-PCB50
|