Franklin Air Conditioner SS PCB50 User Manual

PRODUCT SPECIFICATIONS  
PCB  
COMMERCIAL SERIES  
50 Hz  
SELF-CONTAINED  
PACKAGE AIR CONDITIONER  
7½, 10, AND 15 TON  
[26.4 kW to 52.8 kW]  
COOLING CAPACITY:  
90,000 TO 180,000 BTU/H  
The PCB Commercial 50 Hz self-contained  
packaged air conditioner is designed for  
ground-level or rooftop application.  
Standard Features  
Cabinet Features  
• Dual high-efciency scroll compressors with  
internal motor protection (2-stage cooling;  
three compressors on 15-ton units)  
• Compressor grommets for vibration isolation  
• Time delay for compressor sequencing  
• Fully charged systems  
• Heavy-gauge, zinc-coated steel cabinet with  
weather-resistant powder-paint nish  
• Fully insulated with blankets of insulation  
• Built-in lter rack  
• Factory wiring conveniently arranged for  
installation of accessories  
• High- and low-pressure controls on all systems  
• Mild ambient switch  
• Control box and compressors easily accessible  
from side access panels  
Two independent condenser coils for  
2-stage operation  
Totally enclosed, permanently lubricated ball-  
bearing outdoor fan motors  
Accessory Heat Kit Features  
• Control circuitry arranged to readily  
permit staging  
• Rust-resistant nickel chromium heating elements  
• Primary and secondary limit protection  
• Factory-installed one-time fuses on all models  
• Enhanced copper tube/aluminum n coils  
• Expansion valve evaporator coil  
• Vertical discharge with removable grilles  
• Galvanized steel, powder-coated drain pan with  
3/4” (19mm) NPT condensate connection  
• Belt-driven, variable-pitch sheave permits multi-  
speed adjustment  
• Centrifugal fan for quiet and efcient operation  
• Filters (2” [50.8mm] disposable) provided  
with unit  
Accessories  
• Room thermostat; Low-ambient control  
• Rooftop Lift Kit; Roof curb  
• Economizers (horizontal and vertical)  
• Manual/motorized fresh air damper  
• Horizontal Duct Kit (Downow to Horizontal  
Conversion)  
• Electric heat capacities 15 kW-30 kW @ 415V  
50 Hz (eld-installed accessory)  
• Panel Louver Kit  
• Operates up to 125°F ambient temperature  
SS-PCB50  
www.goodmanmfg.com  
6/06  
Supersedes 12/05  
PRODUCT SPECIFICATIONS  
DIMENSIONS  
All dimensions in inches and millimeters. Drawings are not to scale.  
FIGURE 1. VERTICAL DISCHARGE  
See curb details for connection of duct work to  
curb. Duct work is not intended to be connected  
to unit.  
FIGURE 2. HORIZONTAL DISCHARGE  
Note: The Horizontal Conversion Kit is required to convert  
a factory duct conguration (downow) to a horizontal  
duct conguration, as shown in Figure 2.  
UNIT SIZE  
090  
A - HEIGHT  
36” (914 mm)  
52” (1321 mm)  
B - SUPPLY AIR  
C - RETURN AIR  
12½” (318 mm) 179/16” (446 mm)  
20¼” (514 mm) 2513/16” (656 mm)  
120,180  
SS-PCB50  
3
PRODUCT SPECIFICATIONS  
ELECTRICAL CONNECTIONS  
MODEL  
PCB090-5  
PCB120-5  
PCB180-5  
B
7” (200 mm)  
23” (606 mm)  
23” (606 mm)  
1– Main power entrance location (with electric heat  
installed)  
2– Control wiring entrance location  
3– Main power entrance location (without electric heat  
installed)  
Note: Single-point wiring is available at location #1  
when heat kit is installed. See installation instructions  
for heat kits.  
FIGURE 3. ELECTRICAL HEAT UNITS  
ELECTRIC HEAT  
ELECTRIC HEAT AIR TEMPERATURE RISE @ NOMINAL VOLTAGE  
Heater Model  
No. Stages  
HKCB20  
2
HKCB30  
2
HKCB40  
2
Output MBH (W)  
67.5 (19.8) 101.3 (29.7) 135.0 (39.6)  
Notes:  
2600 (1227) 24.2 (13.4) 36.2 (20.1)  
2800 (1320) 22.5 (12.5) 33.6 (18.7)  
3000 (1415) 21.0 (11.7) 31.4 (17.4)  
-
-
-
1. Maximum air temperature rise of 40°F (22.2°C) must not be  
exceeded.  
2. See Electric Heater Availability table for various unit sizes.  
3. Air temperature rise is for total heating capacity: Temperature rises  
at other conditions may be calculated by using the formula:  
3200 (1510) 19.7 (10.9) 29.4 (16.3) 39.3 (21.8)  
3400 (1605) 18.5 (10.3) 27.7 (15.4) 37.0 (20.6)  
Temperature Rise =  
Output Capacity - BTU/h  
1.08 x ft³/min. Airow  
3600 (1700)  
3800 (1793)  
4000 (1888)  
4200 (1982)  
4400 (2076)  
4600 (2171)  
4800 (2265)  
5000 (2360)  
5200 (2454)  
5400 (2548)  
5600 (2643)  
5800 (2737)  
6000 (2832)  
17.5 (9.7)  
16.5 (9.2)  
15.7 (8.7)  
15.0 (8.3)  
14.3 (7.9)  
13.7 (7.6)  
13.1 (7.3)  
12.6 (7.0)  
12.1 (6.7)  
11.6 (6.4)  
11.2 (6.2)  
10.8 (6.0)  
10.5 (5.8)  
26.2 (14.6) 34.9 (19.4)  
24.8 (13.8) 33.1 (18.4)  
23.5 (13.1) 31.4 (17.4)  
22.4 (12.4) 29.9 (16.6)  
21.4 (11.9) 28.6 (15.9)  
20.5 (11.4) 27.3 (15.2)  
19.6 (10.9) 26.2 (14.6)  
18.8 (10.4) 25.2 (14.0)  
18.1 (10.1) 24.2 (13.4)  
Note: Temperature rises must be calculated in other than nominal volt-  
age conditions.  
4. For altitudes over 2,000’, air temperature rise must be calculated  
using the formula:  
CFM  
&
(L/S)  
Temperature Rise =  
Output Capacity - BTU/h  
14.4 x ft³/Min. Airow x Specic Weight of Air  
5. Operation at less than nominal voltages must be de-rated by the  
following factors: 415 volt-0.75; 380 volt-0.63.  
17.4 (9.7)  
16.8 (9.3)  
16.2 (9.0)  
15.7 (8.7)  
23.3 (12.9)  
22.5 (12.5)  
21.7 (12.1)  
21.0 (11.7)  
ELECTRIC HEATER AVAILABILITY  
NOMINAL VOLTAGE FOR HKCB  
Unit Size  
HKCB20  
HKCB30  
HKCB40  
@ 480V  
19.8 kW  
29.7 kW  
39.6 kW  
@ 415V  
@ 380V  
7½  
10  
15  
X
X
X
X
X
X
X
X
X
HKCB20-4  
HKCB30-4  
HKCB40-4  
14.9 kW  
22.3 kW  
29.7 kW  
12.5 kW  
18.7 kW  
25.0 kW  
4
SS-PCB50  
PRODUCT SPECIFICATIONS  
FAN PERFORMANCE DATA  
FIGURE 4. FAN CURVE - PCB 090  
SUPPLY FAN PERFORMANCE - PCB090  
EXTERNAL STATIC PRESSURE (INCHES W.C.) SEE NOTE (3)  
0.6 0.8 1.0 1.2  
RPM RPM RPM  
CFM  
0.2  
0.4  
1.4  
RPM  
1.6  
RPM BHP  
RPM  
669  
734  
770  
807  
845  
BHP  
0.44  
0.53  
0.62  
0.73  
0.85  
RPM  
816  
847  
877  
909  
942  
BHP  
0.59  
0.69  
0.79  
RPM  
916  
944  
973  
BHP  
BHP  
BHP  
BHP  
BHP  
2600  
2800  
3000  
3200  
3400  
0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67  
0.85 1030 1.03 1109 1.21 1181 1.40 1249 1.60 1312 1.91  
0.97 1053 1.15 1135 1.34 1206 1.54 1273 1.75 1336 1.96  
0.91 1002 1.10 1086 1.29 1162 1.49 1232 1.70 1298 1.91 1360 2.12  
1.04 1032 1.24 1114 1.44 1159 1.65 1259 1.87 1324 2.09 1384 2.31  
Notes:  
• Selections in ITALICS require a eld drive change. See following table below for drive ranges.  
Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of  
external static pressure drop.  
• DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).  
SUPPLY FAN DRIVE DATA - PCB090  
MOTOR SHEAVE - ADJUSTABLE  
FAN SHEAVE - FIXED  
FACTORY SETTING  
2 TURNS OPENS  
MOTOR SHEAVE TURNS OPEN  
FAN RPM 2.0 HP MOTOR  
0
1
2
3
4
5
1209  
1146  
1082  
1018  
955  
891  
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.  
Conversion Factor:  
1 CFM = 0.472 L/S  
1” W.C. = 2.5 M Bar  
1 HP = 0.747 kW  
SS-PCB50  
5
PRODUCT SPECIFICATIONS  
FAN PERFORMANCE DATA (CONT.)  
FIGURE 5. FAN CURVE - PCB 120  
SUPPLY FAN PERFORMANCE - PCB120  
External Static Pressure (INCHES W.C.)  
0.8 1.0  
RPM  
CFM  
0.2  
0.4  
0.6  
1.2  
RPM  
1.4  
RPM  
1.6  
RPM  
679  
706  
733  
761  
790  
818  
BHP  
0.73  
0.83  
0.95  
1.07  
1.21  
1.36  
RPM  
781  
805  
829  
855  
880  
906  
BHP  
0.98  
1.10  
1.23  
1.37  
1.52  
1.68  
RPM  
873  
894  
916  
938  
961  
985  
BHP  
1.26  
1.39  
1.53  
RPM  
957  
975  
995  
BHP  
BHP  
BHP  
BHP  
RPM  
BHP  
3400  
3600  
3800  
4000  
4200  
4400  
1.58 1034 1.91 1105 2.26 1171 2.26 1233 2.99  
1.71 1051 2.05 1121 2.41 1188 2.78 1249 3.17  
1.85 1069 2.20 1139 2.57 1204 2.95 1266 3.36  
1.68 1016 2.01 1088 2.36 1156 2.74 1221 3.14 1282 3.55  
1.84 1037 2.18 1108 2.54 1175 2.93 1239 3.33 1299 3.75  
2.01 1059 2.36 1128 2.73 1194 3.13 1257 3.54 1316 3.97  
Notes:  
• Selections in ITALICS require a eld drive change. See following table below for drive ranges.  
Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of  
external static pressure drop.  
SUPPLY FAN DRIVE DATA - PCB120  
Motor Sheave - Adjustable  
Factory Setting  
Fan Sheave - Fixed  
Two Turns Opens  
Motor Sheave Turns Open  
Fan RPM 3.0 HP Motor  
0
1
2
3
4
5
1242  
1186  
1129  
1073  
1016  
960  
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.  
Conversion Factor:  
1 CFM = 0.472 L/S  
1” W.C. = 2.5 M Bar  
1 HP = 0.747 kW  
6
SS-PCB50  
PRODUCT SPECIFICATIONS  
FAN PERFORMANCE DATA (CONT.)  
FIGURE 6. FAN CURVE - PCB180  
SUPPLY FAN PERFORMANCE - PCB180  
External Static Pressure (Inches W.C.) See Last Note  
0.6 0.8 1.0 1.2  
BHP RPM BHP RPM BHP RPM BHP RPM  
CFM  
0.2  
0.4  
BHP RPM  
1.4  
BHP RPM  
1.6  
BHP RPM  
RPM  
784  
814  
844  
874  
904  
932  
966  
997  
BHP  
4000  
4200  
4400  
4600  
4800  
5000  
5200  
5400  
1.14  
1.29  
1.45  
1.63  
1.82  
876  
903  
930  
957  
986  
1.44  
1.60  
959  
983  
1.76 1036 2.10 1108 2.47 1176 2.86 1239 3.26 1300 3.67  
1.93 1058 2.28 1129 2.66 1195 3.05 1258 3.46 1318 3.89  
1.78 1008 2.12 1081 2.48 1150 2.86 1215 3.26 1277 3.68 1337 4.12  
1.97 1034 2.32 1105 2.69 1172 3.08 1236 3.49 1297 3.92 1356 4.37  
2.17 1060 2.54 1129 2.92 1195 3.32 1258 3.74 1318 4.17 1375 4.63  
2.02 1014 2.39 1086 2.77 1159 3.16 1218 3.57 1280 4.00 1338 4.44 1395 4.91  
2.24 1043 2.62 1113 3.01 1179 3.42 1242 3.84 1302 4.27 1360 4.73 1416 5.20  
2.48 1071 2.87 1141 3.28 1205 3.70 1267 4.12 1326 4.57 1382 5.03 1437 5.51  
5600 1029 2.74 1101 3.14 1168 3.56 1231 3.99 1291 4.43 1394 4.88 1405 5.36 1458 5.85  
Notes:  
• Selections in ITALICS require a eld drive change. See following table below for drive ranges.  
Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of  
external static pressure drop.  
• DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).  
SUPPLY FAN DRIVE DATA - PCB180  
Motor Sheave - Adjustable  
Factory Setting  
2 Turns Opens  
2
Fan Sheave - Fixed  
Motor Sheave Turns Open  
Fan RPM 5.0 HP Motor  
0
1400  
1
1446  
3
4
5
1273  
1209  
1146  
1082  
Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.  
Conversion Factor:  
1 CFM = 0.472 L/S  
1” W.C. = 2.5 M Bar  
1 HP = 0.747 kW  
SS-PCB50  
7
PRODUCT SPECIFICATIONS  
FAN PERFORMANCE DATA (CONT.)  
COMPONENT PRESSURE DROPS  
ECONO. RETURN AIR DAMP-  
MODEL  
090  
CFM  
WET COIL  
ELEC. HEAT  
MED. EFF. FILTERS  
ER  
2600  
3000  
3400  
3600  
4000  
4400  
5000  
5400  
5600  
0.06  
0.06  
0.07  
0.05  
0.05  
0.05  
0.13  
0.13  
0.16  
0.03  
0.04  
0.05  
0.05  
0.06  
0.08  
0.10  
0.12  
0.13  
0.03  
0.04  
0.05  
0.03  
0.04  
0.04  
0.06  
0.06  
0.08  
0.14  
0.14  
0.18  
0.14  
0.14  
0.14  
0.18  
0.21  
0.23  
120  
180  
COOLING CAPACITY DATA  
PCB090-5 (SI UNITS)  
INDOOR  
CONDENSER AIR TEMPERATURE  
35.0°C  
AIR  
23.9°C  
29.4°C  
Sens  
Cap.  
40.6°C  
Sens  
Cap.  
46.1°C  
Sens  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Total  
Cap.  
L/S  
WB  
Kw  
Kw  
Kw  
Kw  
Kw  
22.2 32.77  
19.4 30.23  
16.7 27.52  
13.9 26.59  
22.2 34.17  
19.4 31.36  
16.7 28.62  
13.9 28.62  
22.2 35.01  
19.4 32.19  
16.7 30.24  
13.9 30.24  
15.48  
18.70  
23.00  
24.96  
17.16  
21.95  
26.83  
26.83  
18.42  
24.67  
28.49  
28.49  
8.36  
7.82  
7.46  
7.18  
8.63  
8.08  
7.53  
7.53  
8.82  
8.28  
7.89  
7.89  
30.67  
28.17  
26.07  
24.98  
31.91  
29.28  
26.96  
26.96  
32.73  
30.10  
28.44  
28.44  
14.52  
17.90  
21.73  
23.20  
16.15  
20.81  
25.02  
25.02  
17.46  
23.35  
26.54  
26.54  
9.29  
8.73  
8.30  
8.06  
9.58  
9.01  
8.49  
8.49  
9.77  
9.21  
8.86  
8.86  
28.56  
26.11  
24.62  
23.38  
29.65  
27.20  
25.30  
25.30  
30.46  
28.00  
26.64  
26.64  
13.56  
17.10  
20.45  
21.43  
15.14  
19.66  
23.20  
23.20  
16.50  
22.04  
24.60  
24.60  
10.23  
9.64  
9.14  
8.94  
10.53  
9.93  
9.44  
9.44  
10.73  
10.14  
9.84  
9.84  
26.46  
24.05  
23.17  
21.77  
27.39  
25.12  
23.65  
23.65  
28.18  
25.91  
24.84  
24.84  
12.60  
16.31  
19.18  
19.67  
14.14  
18.52  
21.39  
21.39  
15.54  
20.72  
22.65  
22.65  
11.17  
10.55  
9.98  
24.35  
21.99  
21.72  
20.17  
25.13  
23.03  
21.99  
21.99  
25.90  
23.81  
23.03  
23.03  
11.64  
15.51  
17.91  
17.91  
13.13  
17.38  
19.58  
19.58  
14.59  
19.40  
20.71  
20.71  
12.10  
11.46  
10.82  
10.71  
12.43  
11.78  
11.35  
11.35  
12.64  
11.99  
11.78  
11.78  
1203  
1416  
1628  
9.83  
11.48  
10.86  
10.40  
10.40  
11.69  
11.07  
10.81  
10.81  
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other  
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of  
evaporator coil air per degree above 26.7°C.  
PCB090-5 (ENGLISH UNITS)  
CONDENSER AIR TEMPERATURE  
95°F  
INDOOR  
AIR  
75°F  
Sens  
Kbtuh Kbtuh  
85°F  
Sens  
Kbtuh Kbtuh  
105°F  
Sens  
115°F  
Sens  
Kbtuh Kbtuh  
Total  
Total  
Total  
Sens  
Total  
Total  
SCFM WB  
Kw  
Kw  
Kw  
Kw  
Kw  
Kbtuh Kbtuh  
Kbtuh Kbtuh  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
111.8  
103.2  
93.9  
52.8  
63.8  
78.5  
85.2  
58.5  
74.9  
91.6  
91.6  
62.9  
84.2  
97.2  
97.2  
8.36  
7.82  
7.46  
7.18  
8.63  
8.08  
7.53  
7.53  
8.82  
8.28  
7.89  
7.89  
104.6  
96.1  
89.0  
85.2  
108.9  
99.9  
92.0  
92.0  
111.7  
102.7  
97.0  
97.0  
49.6  
61.1  
74.1  
79.1  
55.1  
71.0  
85.4  
85.4  
59.6  
79.7  
90.6  
90.6  
9.29  
8.73  
8.30  
8.06  
9.58  
9.01  
8.49  
8.49  
9.77  
9.21  
8.86  
8.86  
97.5  
89.1  
84.0  
79.8  
101.2  
92.8  
86.3  
86.3  
103.9  
95.6  
90.9  
90.9  
46.3  
58.4  
69.8  
73.1  
51.7  
67.1  
79.2  
79.2  
56.3  
75.2  
83.9  
83.9  
10.23  
9.64  
9.14  
8.94  
10.53  
9.93  
9.44  
9.44  
10.73  
10.14  
9.84  
9.84  
90.3  
82.1  
79.1  
74.3  
93.5  
85.7  
80.7  
80.7  
96.2  
88.4  
84.7  
84.7  
43.0  
55.6  
65.5  
67.1  
48.2  
63.2  
73.0  
73.0  
53.0  
70.7  
77.3  
77.3  
11.17  
10.55  
9.98  
83.1  
75.0  
74.1  
68.8  
85.7  
78.6  
75.0  
75.0  
88.4  
81.3  
78.6  
78.6  
39.7  
52.9  
61.1  
61.1  
44.8  
59.3  
66.8  
66.8  
49.8  
66.2  
70.7  
70.7  
12.10  
11.46  
10.82  
10.71  
12.43  
11.78  
11.35  
11.35  
12.64  
11.99  
11.78  
11.78  
2550  
90.7  
9.83  
116.6  
107.0  
97.6  
11.48  
10.86  
10.40  
10.40  
11.69  
11.07  
10.81  
10.81  
3000  
97.6  
119.5  
109.9  
103.2  
103.2  
3450  
62  
57  
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other  
than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of  
evaporator coil air per degree above 80°F.  
8
SS-PCB50  
PRODUCT SPECIFICATIONS  
COOLING CAPACITY DATA (CONT.)  
PCB120-5 (SI UNITS)  
INDOOR  
CONDENSER AIR TEMPERATURE  
35.0°C  
AIR  
23.9°C  
29.4°C  
40.6°C  
Sens  
Cap.  
46.1°C  
Sens  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Total  
Cap.  
L/S  
WB  
Kw  
Kw  
Kw  
Kw  
Kw  
22.2 43.67  
19.4 40.29  
16.7 36.65  
13.9 35.42  
22.2 45.54  
19.4 41.79  
16.7 38.12  
13.9 38.12  
22.2 46.65  
19.4 42.90  
16.7 40.29  
13.9 40.29  
21.02  
25.44  
31.24  
33.85  
23.30  
29.83  
36.41  
36.41  
25.03  
33.53  
38.65  
38.65  
9.95  
9.31  
8.89  
8.54  
10.28  
9.62  
8.95  
8.95  
10.50  
9.86  
9.39  
9.39  
41.04  
37.70  
34.88  
33.43  
42.71  
39.18  
36.07  
36.07  
43.81  
40.28  
38.05  
38.05  
19.52  
24.09  
29.22  
31.17  
21.72  
27.99  
33.63  
33.63  
23.49  
31.41  
35.67  
35.67  
11.27  
10.59  
10.07  
9.78  
11.62  
10.92  
10.29  
10.29  
11.85  
11.17  
10.75  
10.75  
38.41  
35.11  
33.11  
31.44  
39.87  
36.57  
34.03  
34.03  
40.96  
37.66  
35.82  
35.82  
18.03  
22.74  
27.19  
28.49  
20.13  
26.14  
30.85  
30.85  
21.94  
29.29  
32.70  
32.70  
12.59  
11.86  
11.25  
11.01  
12.96  
12.22  
11.62  
11.62  
13.20  
12.48  
12.11  
12.11  
35.78  
32.52  
31.34  
29.45  
37.04  
33.97  
31.98  
31.98  
38.11  
35.04  
33.59  
33.59  
16.54  
21.38  
25.17  
25.82  
18.55  
24.29  
28.07  
28.07  
20.39  
27.18  
29.72  
29.72  
13.91  
13.14  
12.43  
12.24  
14.30  
13.52  
12.95  
12.95  
14.55  
13.78  
13.46  
13.46  
33.15  
29.93  
29.57  
27.45  
34.20  
31.36  
29.93  
29.93  
35.26  
32.41  
31.36  
31.36  
15.04  
20.03  
23.14  
23.14  
16.96  
22.45  
25.29  
25.29  
18.84  
25.06  
26.75  
26.75  
15.23  
14.41  
13.61  
13.47  
15.64  
14.82  
14.29  
14.29  
15.90  
15.09  
14.82  
14.82  
1605  
1888  
2170  
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other  
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of  
evaporator coil air per degree above 26.7°C.  
PCB120-5 (ENGLISH UNITS)  
CONDENSER AIR TEMPERATURE  
95°F  
INDOOR  
AIR  
75°F  
Sens  
Kbtuh Kbtuh  
85°F  
Sens  
Kbtuh Kbtuh  
105°F  
Sens  
115°F  
Sens  
Kbtuh Kbtuh  
Total  
Total  
Total  
Sens  
Total  
Total  
SCFM WB  
Kw  
Kw  
Kw  
Kw  
Kw  
Kbtuh Kbtuh  
Kbtuh Kbtuh  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
149.0  
137.5  
125.1  
120.9  
155.4  
142.6  
130.1  
130.1  
159.2  
146.4  
137.5  
137.5  
71.7  
86.8  
106.6  
115.5  
79.5  
101.8  
124.2  
124.2  
85.4  
114.4  
131.9  
131.9  
9.95  
9.31  
8.89  
8.54  
10.28  
9.62  
8.95  
8.95  
10.50  
9.86  
9.39  
9.39  
140.0  
128.6  
119.0  
114.1  
145.7  
133.7  
123.1  
123.1  
149.5  
137.5  
129.9  
129.9  
66.6  
82.2  
99.7  
106.4  
74.1  
95.5  
114.7  
114.7  
80.1  
107.2  
121.7  
121.7  
11.27  
10.59  
10.07  
9.78  
11.62  
10.92  
10.29  
10.29  
11.85  
11.17  
10.75  
10.75  
131.1  
119.8  
113.0  
107.3  
136.1  
124.8  
116.1  
116.1  
139.8  
128.5  
122.2  
122.2  
61.5  
77.6  
92.8  
97.2  
68.7  
12.59  
11.86  
11.25  
11.01  
12.96  
12.22  
11.62  
11.62  
13.20  
12.48  
12.11  
12.11  
122.1  
111.0  
106.9  
100.5  
126.4  
115.9  
109.1  
109.1  
130.0  
119.6  
114.6  
114.6  
56.4  
73.0  
85.9  
88.1  
63.3  
82.9  
95.8  
95.8  
69.6  
92.7  
101.4  
101.4  
13.91  
13.14  
12.43  
12.24  
14.30  
13.52  
12.95  
12.95  
14.55  
13.78  
13.46  
13.46  
113.1  
102.1  
100.9  
93.7  
116.7  
107.0  
102.1  
102.1  
120.3  
110.6  
107.0  
107.0  
51.3  
68.4  
79.0  
79.0  
57.9  
76.6  
86.3  
86.3  
64.3  
85.5  
91.3  
91.3  
15.23  
14.41  
13.61  
13.47  
15.64  
14.82  
14.29  
14.29  
15.90  
15.09  
14.82  
14.82  
3400  
89.2  
4000  
105.3  
105.3  
74.9  
100.0  
111.6  
111.6  
4600  
62  
57  
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other  
than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of  
evaporator coil air per degree above 80°F.  
PCB180-5 (SI UNITS)  
CONDENSER AIR TEMPERATURE  
35.0°C  
INDOOR  
AIR  
23.9°C  
Sens  
Cap.  
29.4°C  
Sens  
Cap.  
40.6°C  
Sens  
Cap.  
46.1°C  
Sens  
Cap.  
Total  
Cap.  
Total  
Cap.  
Total  
Cap.  
Sens  
Cap.  
Total  
Cap.  
Total  
Cap.  
L/S  
WB  
Kw  
Kw  
Kw  
Kw  
Kw  
22.2 64.17  
19.4 59.19  
16.7 53.86  
13.9 52.05  
22.2 66.90  
19.4 61.40  
16.7 56.02  
13.9 56.02  
22.2 68.54  
19.4 63.03  
16.7 59.20  
13.9 59.20  
29.53  
35.59  
43.83  
47.66  
32.71  
41.82  
51.22  
51.22  
35.09  
47.01  
54.38  
54.38  
16.42  
15.36  
14.67  
14.10  
16.97  
15.87  
14.77  
14.77  
17.33  
16.27  
15.49  
15.49  
60.17  
55.27  
51.14  
49.01  
62.61  
57.44  
52.89  
52.89  
64.22  
59.05  
55.79  
55.79  
28.00  
34.49  
41.88  
44.75  
31.14  
40.10  
48.26  
48.26  
33.66  
45.02  
51.20  
51.20  
18.63  
17.50  
16.64  
16.15  
19.21  
18.05  
17.00  
17.00  
19.59  
18.46  
17.76  
17.76  
56.17  
51.35  
48.42  
45.97  
58.31  
53.48  
49.76  
49.76  
59.89  
55.07  
52.38  
52.38  
26.48  
33.39  
39.93  
41.85  
29.56  
38.39  
45.30  
45.30  
32.22  
43.02  
48.02  
48.02  
20.83  
19.63  
18.61  
18.21  
21.45  
20.22  
19.23  
19.23  
21.85  
20.64  
20.03  
20.03  
52.17  
47.42  
45.69  
42.93  
54.01  
49.53  
46.63  
46.63  
55.57  
51.09  
48.98  
48.98  
24.95  
32.29  
37.99  
38.94  
27.99  
36.68  
42.34  
42.34  
30.78  
41.02  
44.84  
44.84  
23.04  
21.76  
20.59  
20.27  
23.68  
22.40  
21.46  
21.46  
24.11  
22.83  
22.30  
22.30  
48.17  
43.50  
42.97  
39.90  
49.71  
45.57  
43.50  
43.50  
51.24  
47.11  
45.57  
45.57  
23.43  
31.20  
36.04  
36.04  
26.42  
34.96  
39.38  
39.38  
29.34  
39.03  
41.66  
41.66  
25.25  
23.89  
22.56  
22.33  
25.92  
24.57  
23.68  
23.68  
26.37  
25.01  
24.57  
24.57  
2246  
2643  
3039  
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other  
than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of  
evaporator coil air per degree above 26.7°C.  
SS-PCB50  
9
PRODUCT SPECIFICATIONS  
COOLING CAPACITY DATA (CONT.)  
PCB180-5 (ENGLISH UNITS)  
INDOOR  
CONDENSER AIR TEMPERATURE  
95°F  
AIR  
SCFM WB  
72  
75°F  
Sens  
Kbtuh Kbtuh  
85°F  
Sens  
Kbtuh Kbtuh  
105°F  
Sens  
115°F  
Sens  
Kbtuh Kbtuh  
Total  
Total  
Total  
Kbtuh Kbtuh  
Sens  
Total  
Kbtuh Kbtuh  
Total  
Kw  
Kw  
Kw  
Kw  
Kw  
219.0  
202.0  
183.8  
177.6  
228.3  
209.5  
191.1  
191.1  
233.9  
215.1  
202.0  
202.0  
100.8  
121.4  
149.6  
162.6  
111.6  
142.7  
174.8  
174.8  
119.7  
160.4  
185.6  
185.6  
16.42  
15.36  
14.67  
14.10  
16.97  
15.87  
14.77  
14.77  
17.33  
16.27  
15.49  
15.49  
205.3  
188.6  
174.5  
167.2  
213.6  
196.0  
180.5  
180.5  
219.1  
201.5  
190.4  
190.4  
95.6  
18.63  
17.50  
16.64  
16.15  
19.21  
18.05  
17.00  
17.00  
19.59  
18.46  
17.76  
17.76  
191.7  
175.2  
165.2  
156.9  
199.0  
182.5  
169.8  
169.8  
204.4  
187.9  
178.8  
178.8  
90.4  
20.83  
19.63  
18.61  
18.21  
21.45  
20.22  
19.23  
19.23  
21.85  
20.64  
20.03  
20.03  
178.0  
161.8  
155.9  
146.5  
184.3  
169.0  
159.1  
159.1  
189.6  
174.3  
167.1  
167.1  
85.1  
110.2  
129.6  
132.9  
95.5  
125.2  
144.5  
144.5  
105.0  
140.0  
153.0  
153.0  
23.04  
21.76  
20.59  
20.27  
23.68  
22.40  
21.46  
21.46  
24.11  
22.83  
22.30  
22.30  
164.4  
148.4  
146.6  
136.1  
169.6  
155.5  
148.4  
148.4  
174.9  
160.7  
155.5  
155.5  
79.9  
106.5  
123.0  
123.0  
90.1  
119.3  
134.4  
134.4  
100.1  
133.2  
142.1  
142.1  
25.25  
23.89  
22.56  
22.33  
25.92  
24.46  
23.68  
23.68  
26.37  
25.01  
24.57  
24.57  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
117.7  
142.9  
152.7  
106.3  
136.9  
164.7  
164.7  
114.8  
153.6  
174.7  
174.7  
113.9  
136.3  
142.8  
100.9  
131.0  
154.6  
154.6  
109.9  
146.8  
163.9  
163.9  
4760  
5600  
6440  
57  
Sensible heat capacities shown are based on 80 °F DB entering air at the evaporator coil. For sensible heat capacities at other  
than 80 °F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80 °F, or add 84 BTU/h per 100 CFM of  
evaporator coil air per degree above 80 °F.  
EVAPORATOR MOTOR HEAT  
Horsepower/(kW)  
2 (1.49)  
BTU/h (KW)  
4400 (1.29)  
6200 (1.82)  
10,500 (3.08)  
3 (2.24)  
5 (3.73)  
10  
SS-PCB50  
PRODUCT SPECIFICATIONS  
APPLICATION DETAILS AND ACCESSORIES  
FACTORY SUPPLIED ACCESSORIES THERMOSTAT (CHT90-120)  
Two-stage cool and two-stage heat thermostat with subbase, Manual changeover, Fan ON or AUTO. Note: A variety  
of thermostat congurations can be used on this equipment based on the application needs. For example our  
CHTS36-60 can be used if two-stage cooling and single-stage heat is desired. Our CHT18-60 can be used if single-  
stage cooling and heating is desired. A single-stage cooling and two-stage heating thermostat can be used.  
ROOFTOP LIFT KIT (RLK90-120)  
Kit consists of four ½” (12.7mm) shackles that are used to lift the equipment into position on a roof, etc. The  
shackles are to be attached to the mounting holes in the base rails. Wire or strap material along with eld supplied  
spreader bars are employed to complete the lifting assembly (See Rigging detail).  
LOW AMBIENT CONTROL (LA-01)  
Liquid temperature (or pressure) operated solid state control, which varies the speed of one of the condenser fans.  
Low ambient control reduces fan motor RPM as liquid temperature (or pressure) decreases. Caution: If control is  
used below 50 °F (10 °C) accumulators should be added to the equipment to avoid slugging of the compressors.  
ROOF CURB (PGC-5)  
Full perimeter curb for equipment in the down discharge application. Curb includes provisions for duct attachment  
prior to setting unit. Curb is shipped knocked down with all necessary hardware and gasket material.  
MANUAL AND MOTORIZED FRESH AIR DAMPERS (PGMD-5 & PGMDM-5)  
Manual damper is xed position type for 0 to 25% fresh air. Motorized damper is a eld adjustable mechanical  
damper for 0 to 25% fresh air, damper automatically closes when blower stops.  
ECONOMIZERS (PGED 090/102-5 & PGED 120/180-5)  
Fully modulating, enthalpy controlled economizers shipped with major components pre-assembled. Plug assembly  
on equipment and economizer provides easy wiring.  
HORIZONTAL DUCT KIT (PGHDK 090/102-5 & PGHDK 120/180-5)  
The unit is shipped in the down ow (vertical) duct conguration. The horizontal duct kit must be installed in the  
eld for horizontal duct conguration.  
PANEL LOUVER KIT (PLK090/102-5 & PLK120/180-5)  
Louvered panels for condenser coil protection.  
HEAT KIT ACCESSORY  
Slide in heat kit from 15 to 30 kW @ 415V, 3Ph, 50 Hz are available. For 380/415V operation the -4 electrical  
designation on HKCB heat kits must be used. The heating output is derated as shown by example on page 11 at  
both 380V & 415V.  
Bulletin illustrations cover the general appearance of Goodman Manufacturing Company, L.P., products at the  
time of publication, and we reserve the right to make changes in design and construction at any time without  
notice.  
SS-PCB50  
11  
PRODUCT SPECIFICATIONS  
QUALITY MAKES THE DIFFERENCE!  
All of our systems are designed and manufactured with the same high-quality standards, regardless of size or efciency. We have designed these units to signicantly  
reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit  
is run-tested before it leaves the factory. That’s why we know...there’s no better quality.  
Visit our website at  
Goodman Products • Customer Services • Parts  
Goodman Manufacturing Company, L.P.  
2550 North Loop West, Suite 400  
Houston, Texas 77092 USA  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specications or designs without notice or without incurring obligations.  
Copyright © 2003 Goodman Manufacturing Company, L.P. Houston, Texas Printed in the USA. Goodman products are made proudly in the USA.  
12  
SS-PCB50  

Briggs Stratton 19 User Manual
Briggs Stratton Automobile Parts 200000 User Manual
Briggs Stratton Automobile Parts 400000 User Manual
Dakota Digital LED Tail Lights for 1968 Chevelle LAT NR180 User Manual
Epson All in One Printer 845 User Manual
Field Controls CC 2000 User Manual
Friedrich 18 User Manual
Friedrich Air Conditioner XQ08 User Manual
Haier HSU 0912RF03 User Manual
HP Hewlett Packard Hewlett Packard All in One Printer X476DN User Manual