48EZ(N)---A
Comfortt 13 SEER Single---Packaged HYBRID HEAT®
Dual Fuel System with Puronr (R---410A) Refrigerant
Single And Three Phase
2 --- 5 N o m i n a l To n s ( S i z e s 2 4 --- 6 0 )
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
NOTE: Installer: Make sure the Owner’s Manual and Service
Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1--2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
RECEIVING AND INSTALLATION . . . . . . . . . . . . . . . . . 2--13
Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Identify Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connect Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Install Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configuring Units for Downflow (Vertical)
A09034
Fig. 1 -- Unit 48EZ--A
Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Check Defrost Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
PuronR Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Install Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . 13
High--Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . 13
Special Procedures for 208--V Operation . . . . . . . . . . . . . . 13
Control Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . 13
Balance Point Setting Thermidistat or Hybrid Heat
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15--18
Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 15
Unit Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 15
Start--Up Heating and Make Adjustments . . . . . . . . . . . . . . . 15
Checking Heating Control . . . . . . . . . . . . . . . . . . . . . . . . . 16
Check Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Adjust Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Start--Up Cooling and Make Adjustments . . . . . . . . . . . . . . . 18
Checking Cooling Control Operation . . . . . . . . . . . . . . . . 18
Checking and Adjusting Refrigerant . . . . . . . . . . . . . . . . . 18
Indoor Airflow and Airflow Adjustments . . . . . . . . . . . . . 18
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28--34
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Indoor Blower and Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Flue Gas Passageways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Limit Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Outdoor Coil, Indoor Coil, & Condensate Drain Pan . . . . . . 29
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and
qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on this
equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes, the current editions of the National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code
(NEC) NFPA 70.
In Canada refer to the current editions of the National Standards of
Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane
Installation codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol
.
When you see this symbol on the unit and in instructions or manu-
als, be alert to the potential for personal injury. Understand these
signal words: DANGER, WARNING, and CAUTION. These
1
A09450
Fig. 2 -- 48EZ--A24--36 Unit Dimensions
3
A09451
Fig. 3 -- 48EZ--A42--60 Unit Dimensions
4
B
HVAC unit
basepan
C
HVAC unit
base rails
Sealing
Gasket
Roofcurb
H
F
A
Anchor screw
Wood nailer*
Roofcurb*
Flashing field
supplied
Insulation
(field supplied)
Roofing material
field supplied
E
D
Cant strip
field supplied
SMALL CURB
A09418
*Provided with roofcurb
A09090
ROOF CURB DETAIL
B
C
G
H
A
F
E
D
LARGE CURB
A09415
A09419
CATALOG
NUMBER
CPRFCURB010A00
CPRFCURB011A00
CPRFCURB012A00
CPRFCURB013A00
A
B
C
D
E
F
G
H
UNIT SIZE
Small
IN. (mm)
IN. (mm)*
IN. (mm)
IN. (mm)
IN. (mm)
IN. (mm)
IN. (mm)
IN. (mm)
11 (279)
14 (356)
11 (279)
14 (356)
10 (254)
32.4 (822)
30.6 (778)
47.8
(1214)
16 (406)
2.7 (69)
46.1 (1170)
43.9
(1116)
Large
14 (356)
42.2 (1072)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
IMPORTANT: Do not install large base pan HYBRID HEAT
units onto the small base pan (common curb). The center of gravity
on a large base pan HYBRID HEAT unit could overhang the curb
causing an unsafe condition. Before installing any large base pan
unit onto the common curb, check the “Y” distance in the product
literature dimensional drawing to ensure that “Y” is greater than 14
in. (356 mm). Do not install any large base pan unit onto the
common curb with a “Y” dimension (center of gravity) less than 14
in. (356 mm).
Fig. 4 -- Roof Curb Dimensions
5
CAUTION - NOTICE TO RIGGERS
PRUDENCE - AVIS AUX MANIPULATEUR
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
DUCTS
MINIMUM HEIGHT: 36" (914.4 mm)
HAUTEUR MINIMUM
BANDE SCELLANT DOIT ÊTRE
EN PLACE AVANT DE PLACER
L'UNITÉ SUR LA BASE DE TOIT
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
UNIT HEIGHT
HAUTEUR D'UNITÉ
DETAIL A
VOIR DÉTAIL A
SEE DETAIL A
VOIR DÉTAIL A
50CY502286 2.0
A09051
RIGGING WEIGHTS (SMALL CABINET)
RIGGING WEIGHTS (LARGE CABINET)
42 48
24
30
36
60
Unit
Unit
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
230
Rigging
Weight
Rigging
Weight
359
163
373
169
379
172
461
209
482
219
507
*For 460 Volt units add 14 lb (6.35 kg) to the rigging weight.
NOTE: See dimensional drawing for corner weights.
Fig. 5 -- 48EZ--A Suggested Rigging
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
Step 5 — Rig and Place Unit
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.
See unit rating plate for any required clearances around ductwork.
Cabinet return--air static shall not exceed --.25 IN. W.C.
!
WARNING
PERSONAL INJURY OR PROPERTY DAMAGE
HAZARD
Step 4 — Provide Clearances
The required minimum operating and service clearances are shown
in Fig. 2 and 3.
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Failure to follow this warning could result in personal
injury, death or property damage.
When installing the unit on a rooftop, be sure the roof will
support the additional weight.
Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated
structures, etc.).
The condenser fan pulls air through the condenser coil and
discharges it through the top grille. Be sure that the fan discharge
does not recirculate to the condenser coil. Do not locate the unit in
either a corner or under an overhead obstruction. The minimum
clearance under a partial overhang (such as a normal house
overhang) is 48--in. (1219 mm) above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48--in.
(1219 mm).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. The unit may be installed
on Class A, B, or C roof covering materials. Slab mounted units
should be at least 4--in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
6
TRAP
OUTLET
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles,
clevis pins, and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
hooking points and load support areas. Materials showing any kind
of wear in these areas must not be used and should be discarded.
1-in. (25 mm) min.
2-in. (51 mm) min.
!
WARNING
A09052
UNIT FALLING HAZARD
Fig. 6 -- Condensate Trap
Failure to follow this warning could result in personal
injury or death.
Step 7 — Install Flue Hood
The flue assembly is secured and shipped in the return air duct.
Remove duct cover to locate the assembly (See Fig. 8 and 9).
Never stand beneath rigged units or lift over people.
NOTE:
Dedicated low NOx models MUST be installed in
!
WARNING
California Air Quality Management Districts where a Low NOx
rule exists.
PROPERTY DAMAGE HAZARD
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms/joule or less as
shipped from the factory.
NOTE: Low NOx requirements apply only to natural gas
installations.
Failure to follow this warning could result in personal
injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36
in. (914 mm) above the unit top cover.
Rigging/Lifting of Unit (See Fig. 5)
Lifting holes are provided in base rails as shown in Fig. 2 and 3.
!
WARNING
1. Leave top shipping skid on the unit for use as a spreader bar
to prevent the rigging straps from damaging the unit. If the
skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
2. Attach shackles, clevis pins, and straps to the base rails of
the unit. Be sure materials are rated to hold the weight of the
unit (See Fig. 5).
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
The venting system is designed to ensure proper venting.
The flue hood assembly must be installed as indicted in this
section of the unit installation instructions.
Install the flue hood as follows:
After the unit is placed on the roof curb or mounting pad, remove
the top skid.
1. This installation must conform with local building codes
and with the National Fuel Gas Code (NFGC) NFPA 54 /
ANSI Z223.1, (in Canada, CAN/CGA B149.1, and
B149.2) latest revision. Refer to Provincial and local
plumbing or wastewater codes and other applicable local
codes.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 48EZ--A disposes of condensate water through a 3/4 in.
NPT fitting which exits through the compressor access panel (See
Fig. 2 and 3 for location).
2. Remove flue hood from shipping location (inside the return
section of the blower compartment--see Fig. 8 & 9). Re-
move the return duct cover to locate the flue hood. Place
flue hood assembly over flue panel. Orient screw holes in
flue hood with holes in the flue panel.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied condensate trap at end
of condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the
drain--pan condensate connection to prevent the pan from
overflowing (See Fig. 6). Prime the trap with water. When using a
gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away
from the unit, install a 2--in. (51 mm) trap at the condensate
connection to ensure proper drainage (See Fig. 6). Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the
drain--pan condensate connection. This prevents the pan from
overflowing.
3. Secure flue hood to flue panel by inserting a single screw on
the top flange and the bottom flange of the hood.
Step 8 — Install Gas Piping
The gas supply pipe enters the unit through the access hole
provided. The gas connection to the unit is made to the 1/2--in.
(12.7 mm) FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to
Table 2 and the NFGC for gas pipe sizing. Do not use cast--iron
pipe. It is recommended that a black iron pipe is used. Check the
local utility for recommendations concerning existing lines. Size
gas supply piping for 0.5 IN. W.C. maximum pressure drop. Never
use pipe smaller than the 1/2--in. (12.7 mm) FPT gas inlet on the
unit gas valve.
For natural gas applications, the gas pressure at unit gas connection
must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C.
while the unit is operating. For propane applications, the gas
pressure must not be less than 11.0 IN. W.C. or greater than 13 IN.
W.C. at the unit connection.
Prime the trap with water. Connect a drain tube -- using a minimum
of 3/4--in. PVC or 3/4--in. copper pipe (all field--supplied) -- at the
outlet end of the 2--in. (51 mm) trap. Do not undersize the tube.
Pitch the drain tube downward at a slope of at least 1--in. (25 mm)
for every 10 ft (3 m) of horizontal run. Be sure to check the drain
tube for leaks.
7
A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas
supply connection to the gas valve.
!
WARNING
When installing the gas supply line, observe local codes pertaining
to gas pipe installations. Refer to the NFGC NFPA 54/ANSI
Z223.1 latest edition (in Canada, CAN/CGA B149.1).
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
NOTE: In the state of Massachusetts:
--Connect gas pipe to unit using a backup wrench to avoid
damaging gas controls.
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
--Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections.
2. When flexible connectors are used, the maximum length
shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
--Use proper length of pipe to avoid stress on gas control
manifold.
In the absence of local building codes, adhere to the following
pertinent recommendations:
--If a flexible connector is required or allowed by authority
having jurisdiction, black iron pipe shall be installed at
furnace gas valve and extend a minimum of 2 in. (51 mm)
outside furnace casing.
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.
(6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.
Grade all horizontal runs downward to risers. Use risers to
connect to heating section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft (1.8
m). For pipe sizes larger than 1/2 in., (12.7 mm) follow
recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
--If codes allow a flexible connector, always use a new
connector. Do not use a connector which has previously
serviced another gas appliance.
8. Check for gas leaks at the field--installed and
factory--installed gas lines after all piping connections have
been completed. Use a commercially available soap solution
made specifically for the detection of leaks (or method
specified by local codes and/or regulations).
IN
4. Install sediment trap in riser leading to heating section (See
Fig. 7). This drip leg functions as a trap for dirt and
condensate.
5. Install an accessible, external, manual main shutoff valve in
gas supply pipe within 6 ft (1.8 m) of heating section.
6. Install ground--joint union close to heating section between
unit manual shutoff and external manual main shut--off
valve.
7. Pressure test all gas piping in accordance with local and
national plumbing and gas codes before connecting piping
to unit.
TEE
NOTE: Pressure test the gas supply system after the gas supply
piping is connected to the gas valve. The supply piping must be
disconnected from the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig. Pressure test the
gas supply piping system at pressures equal to or less than 0.5 psig.
The unit heating section must be isolated from the gas piping
system by closing the external main manual shutoff valve and
slightly opening the ground--joint union.
OUT
NIPPLE
CAP
C99020
Fig. 7 -- Sediment Trap
8
Table 1 – Physical Data -- Unit 48EZ--A
UNIT SIZE 48EZ ---A
NOMINAL CAPACITY ---ton
SHIPPING WEIGHT ---lb.
(kg)
24040
2
24060
2
30040
2 --- 1/2
373
30060
2 --- 1/2
373
36060
3
36090
3
42060
3 --- 1/2
461
42090
3 --- 1/2
461
359
163
359
163
379
172
379
172
169
169
209
209
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R---410A)
Quantity ---lb
8.3
3.8
8.3
3.8
10.2
4.6
10.2
4.6
7.9
3.6
7.9
3.6
10.0
4.5
10.0
4.5
(kg)
REFRIGERANT METERING
DEVICE
In door --- T X V, Ou tdoor --- Accu r ater
OUTDOOR ORIFICE
0.038 (Left)
0.040(Right)
.97/1.02
in. (qty)
(mm)
0.032 (2)
.81
0.035 (2)
.89
0.037 (2)
.94
OUTDOOR COIL
Rows...Fins/in.
2...21
11.9
2...21
11.9
2...21
2...21
11.9
2...21
11.9
2...21
11.9
2...21
2...21
13.6
11.9
13.6
Fa c e A r e a --- s q f t
OUTDOOR FAN
2000
24
610
2000
24
610
2700
24
610
2700
24
610
2700
24
610
2700
24
610
3100
26
660
3100
26
660
Nominal Cfm
Diameter---in.
(mm)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
Motor Hp (Rpm)
INDOOR COIL
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
Rows...Fins/in.
Fa c e A r e a --- s q f t
INDOOR BLOWER
Nominal Cooling Airflow---(CFM)
S i z e --- i n .
800
10x10
254x254
1/2
800
10x10
254x254
1/2
1000
10x10
254x254
1/2
1000
10x10
254x254
1/2
1200
11x10
279x254
3/4
1200
11x10
279x254
3/4
1400
11x10
279x254
3/4
1400
11x10
279x254
3/4
(mm)
M o t o r --- h p
FURNACE SECTION*
Burner Orifice
Natural Gas Qty...Drill Size (Factory Installed)
Propane GasQty...Drill Size
HIGH---PRESSURE SWITCH
( p s i g ) C u t --- o u t
2...44
2...55
2...38
2...53
2...44
2...55
2...38
2...53
2...38
2...53
3...38
3...53
2...38
2...53
3...38
3...53
650 +/---15
420 +/---25
Reset (Auto)
L O S S --- O F --- C H A R G E /
LOW---PRESSURE SWITCH
(Liquid Line) (psig)
C u t --- o u t
20 +/ --- 5
45 +/---10
Reset (auto)
RETURN---AIR FILTERS † }
Throwaway (in.)
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
*Based on altitude of 0 to 2000 ft (0---610 m).
{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
9
Table 1 -- Physical Data -- Unit 48EZ--A (Cont’d)
UNIT SIZE 48EZ ---A
NOMINAL CAPACITY ---ton
OPERATING WEIGHT---lb
48090
4
482
219
48115
4
48130
4
482
219
60090
5
507
230
60115
5
60130
5
507
230
482
219
507
230
(kg)
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R---410A)
Quantity ---lb
9.6
4.4
12.3
5.6
(kg )
REFRIGERANT METERING DEVICE
OUTDOOR ORIFICE---in. (qty)
(mm)
TXV
0.046 (2)
1.2
0.052 (2)
1.3
OUTDOOR COIL
Rows...Fins---in.
2...21
13.6
2...21
13.6
2...21
13.6
2...21
17.5
2...21
17.5
2...21
17.5
Fa c e A r e a --- s q f t
OUTDOOR FAN
3100
26
660
3100
26
660
3100
26
660
3500
26
660
3500
26
660
3500
26
660
Nominal Cfm
Diameter---in.
(mm)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
1/5 (810)
M o t o r H p --- R p m
INDOOR COIL
3...17
4.7
3...17
4.7
3...17
4.7
3...17
5.7
3...17
5.7
3...17
5.7
Rows...Fins---in.
Fa c e A r e a --- s q f t
INDOOR BLOWER
Nominal Cooling Airflow---(CFM)
S i z e --- i n .
1600
11x10
279x254
1.0
1600
11x10
279x254
1.0
1600
11x10
279x254
1.0
1850
11x10
279x254
1.0
1850
11x10
279x254
1.0
1850
11x10
279x254
1.0
(mm)
M o t o r --- h p
FURNACE SECTION*
Burner Orifice
3...38
3...53
3...33
3...51
3...31
3...49
3...38
3...53
3...33
3...51
3...31
3...49
Natural Gas Qty...Drill Size (Factory Installed)
Propane GasQty...Drill Size
HIGH---PRESSURE SWITCH (psig) Cut---out
Reset (Auto)
650 +/---15
420 +/---25
L O S S --- O F --- C H A R G E /
LOW---PRESSURE SWITCH
(Liquid Line) (psig)
C u t --- o u t
20 +/ --- 5
45 +/---10
Reset (auto)
RETURN---AIR FILTERS †
Throwaway (in.)
(mm)
24x36x1
(610x914x25)
*Based on altitude of 0 to 2000 ft (0---610 m).
{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
Table 2 – Maximum Gas Flow Capacity*
NOMINAL
IRON
PIPE,
SIZE (IN.)
1/2
LENGTH OF PIPE, FT† (m)
INTERNAL
DIAMETER
(IN.)
10
20
30
40
50
60
70
(21.3)
80
(24.4)
90
(27.4)
100
125
150
175
200
(3.1)
(6.1)
(9.1)
(12.2)
(15.2)
(18.3)
(30.5)
(38.1)
(46.0)
(53.3)
(61.0)
.622
.824
1.049
1.380
1.610
175
360
120
250
97
200
375
770
1180
82
73
66
61
57
53
50
44
93
175
360
550
40
84
160
325
500
—
77
145
300
460
—
72
135
280
430
3/4
170
320
600
990
151
285
580
900
138
260
530
810
125
240
490
750
118
220
460
690
110
205
430
650
103
195
400
620
1
680
465
1 --- 1 / 4
1400
950
1 --- 1 / 2
2100
1460
* Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2
and National Fire Protection Association NFPA 54/ANSI Z223.1.
† This length includes an ordinary number of fittings.
Table 3 – Heating Inputs
GAS SUPPLY PRESSURE (IN. W.C.)
Natural{ Propane*{
MANIFOLD PRESSURE
(IN. W.C.)
HEATING INPUT
(BTUH)
NUMBER OF
ORIFICES
Min
4.0
4.0
4.0
4.0
4.0
Max
13.0
13.0
13.0
13.0
13.0
Min
11.0
11.0
11.0
11.0
11.0
Max
13.0
13.0
13.0
13.0
13.0
Natural{
3.2∼3.8
3.2∼3.8
3.2∼3.8
3.2∼3.8
3.2∼3.8
Propane*†
10.0∼11.0
10.0∼11.0
10.0∼11.0
10.0∼11.0
10.0∼11.0
40,000
60,000
90,000
115,000
130,000
2
2
3
3
3
*When a unit is converted to propane, different size orifices must be used. See separate, natural---to---propane conversion kit instructions.
{Based on altitudes from sea level to 2000 ft (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
10
Step 9 — Install Duct Connections
!
CAUTION
The unit has duct flanges on the supply-- and return--air openings
on the side and bottom of the unit. For downshot applications, the
ductwork connects to the roof curb (See Fig. 2 and 3 for
connection sizes and locations).
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Configuring Units for Downflow (Vertical) Discharge
Collect ALL screws that were removed. Do not leave screws
on rooftop as permanent damage to the roof may occur.
!
WARNING
6. Using a suitable saw cut along “V” groove and remove duct
panels.
7. Tip unit back onto its base and replace duct covers.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
8. After completing unit conversion, perform all safety checks
and power up unit.
Before installing or servicing system, always turn off main
power to system and install lockout tag. There may be more
than one disconnect switch.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
1. Open all electrical disconnects before starting any service
work.
2. Remove horizontal (metal) duct covers to access vertical
(downflow) discharge duct knockouts in unit basepan. (See
Fig. 8.)
3. Using Fig. 9 as a guide, proceed to cut out the downflow
duct panels.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
1. Units are shipped for horizontal duct installation (by
removing duct covers).
2. Select and size ductwork, supply--air registers, and
return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)
recommendations.
4. Drill 1/2 in. (13 mm) diameter or larger holes in all four
corners of duct panels.
NOTE: On large chassis units remove sheet metal shields on
panels by using a screw driver to shear off retainers and discard.
3. Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather tight and airtight seal.
5. On left and side supply duct opening side with keyhole or
single bladed hacksaw cut out panel along “V” groove.
6. On right side, with keyhole or single blade hacksaw, with
teeth facing up and starting from the front and moving to
the rear, cut along “V” groove.
4. All units must have field--supplied filters or accessory filter
rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
7. Now with three sides cut, flex panel up and down to re-
move.
5. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.
8. Replace side access panel and duct cover.
9. After completing unit conversion, perform all safety checks
and power up unit.
6. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) and Air Conditioning Contractors
of America (ACCA) minimum installation standards for
heating and air conditioning systems. Secure all ducts to
building structure.
Alternate Method
1. Open all electrical disconnects and install lockout tag before
starting any service work.
2. Remove horizontal (metal) ductcovers to access vertical
(downflow) discharge duct knockouts in unit basepan. (See
Fig. 8.)
3. Leave top shipping crate on unit during this method.
7. Flash, weatherproof, and vibration--isolate all openings in
building structure in accordance with local codes and good
building practices.
4. Tip unit over on the front side (access panels) so the bottom
of the base pan is accessible.
5. Drill two holes diagonally opposed, of suitable size to ac-
commodate jigsaw or reciprocating saw. (See Fig. 9.)
NOTE: On large chassis units remove sheet metal shields on
panels by using a screw driver to shear off retainers and discard.
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
When cutting duct panels, do not contact or damage any
internal components (heat exchanger, electric heat). Do not
use a saw blade that protrudes more than 1 in. (25 mm) into
unit.
11
Return Duct Panels
Horizontal Duct Covers
A09061
Basepan
Downflow
(Vertical)
Supply
Basepan
Downflow
(Vertical)
Return
Knockout
Supply Duct Panels
Knockout
A09060
Fig. 8 -- Supply and Return Duct Opening
Return & Supply Duct Panels from
Underside of Base (Alternate Method)
A09420
Fig. 9 -- Vertical (Downflow) Discharge Duct Knockouts
12
Single phase units:
Step 10 — Install Electrical Connections
1. Run the high--voltage (L1, L2) and ground lead into the
control box.
!
WARNING
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
The unit cabinet must have an uninterrupted, unbroken
electrical ground. This ground may consist of an electrical
wire connected to the unit ground screw in the control
compartment, or conduit approved for electrical ground when
installed in accordance with NEC, NFPA 70 National Fire
Protection Association (latest edition) (in Canada, Canadian
Electrical Code CSA C22.1) and local electrical codes.
5. Connect field wire L2 to yellow wire on connection 23 of
the compressor contactor.
Three--phase units:
1. Run the high--voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
5. Connect field wire L3 to yellow wire on connection 13 of
the compressor contactor.
Failure to follow this caution may result in damage to the unit
being installed.
6. Connect field wire L2 to blue wire from compressor.
1. Make all electrical connections in accordance with NEC
NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
Special Procedures for 208-V Operation
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
3. Be sure that high--voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
Makesurethepower supplyto theunit isswitched OFFbefore
making any wiring changes. Tag the disconnect switch with a
suitable warning label. With disconnect switch open, move
black wire from transformer (3/16 in.) terminal marked 230 to
terminal marked 200. This retaps transformer to primary
voltage of 208 vac.
4. Insulate low--voltage wires for highest voltage contained
within conduit when low--voltage control wires are in
same conduit as high--voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
!
WARNING
ELECTRICAL SHOCK AND EXPLOSION HAZARD
High-Voltage Connections
Failure to follow this warning could result in personal injury
or death.
When routing power leads into unit, use only copper wire between
disconnect and unit. The high voltage leads should be in a conduit
until they enter the duct panel; conduit termination at the duct
panel must be watertight.
Beforemakingany wiringchanges, makesurethe gassupply
is switched off first. Then switch off the power supply to the
unit and install lockout tag.
The unit must have
a
separate electrical service with
a
field--supplied, waterproof disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field--supplied disconnect switch box may be mounted on the
unit over the high--voltage inlet hole when the standard power and
low--voltage entry points are used (See Fig. 2 and 3 for acceptable
location).
Control Voltage Connections
Do not use any type of power--stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35_C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the
control voltage wires), use no. 16 AWG color--coded, insulated
(35_C minimum) wires.
See unit wiring label (Fig. 15 and 16) and Fig. 10 for reference
when making high voltage connections. Proceed as follows to
complete the high--voltage connections to the unit.
Locate the seven (eight on 3--phase) low voltage thermostat leads
in 24 volt splice box. See Fig. 10 for connection diagram. Run the
low--voltage leads from the thermostat, through the control wiring
inlet hole grommet (Fig. 2 and 3), and into the low--voltage splice
box. Provide a drip loop before running wires through panel.
Secure and strain relief all wires so that they do not interfere with
operation of unit. A gray wire is standard on 3--phase unit for
connection to an economizer.
13
PRE--START--UP
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
POWER
SUPPLY
!
WARNING
FIRE,EXPLOSION,ELECTRICAL SHOCKHAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
EQUIP GR
FIELD-SUPPLIED
FUSED DISCONNECT
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power
to unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all
electrical sources are disconnected and tagged.
4. Relieve and recover all refrigerant from system before
touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor
terminals.
CONTROL BOX
WHT(W1)
W
YEL(Y)
Y
GRN(G)
G
RED(R)
THERMOSTAT
(TYPICAL)
R
LOW-VOLTAGE
BRN(C)
C
POWER LEADS
(SEE UNIT
ORN(O)
WIRING LABEL)
O
BLU (DH)
DH
GRA (Y2)
3-Phase
Only
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
SPLICE BOX
A09067
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective goggles and
proceed as follows:
Fig. 10 -- High and Control--Voltage Connections
Balance Point Setting-Thermidistat or Hybrid
Thermostat
BALANCE POINT TEMPERATURE--The “balance point”
temperature is a setting which affects the operation of the heating
mode. This is a field--selected input temperature (range 5 to 55_F)
(--15 to 12_C) where the Thermidistat or dual fuel thermostat will
monitor outdoor air temperature and decide whether to enable or
disable the heat pump. If the outdoor temperature is above the
“balance point”, the heat pump will energize first to try to satisfy
the indoor temperature demand. If the heat pump does not make a
sufficient improvement within a reasonable time period (i.e. 15
minutes), then the gas furnace will come on to satisfy the indoor
temperature demand. If the outdoor temperature is below the
“balance point”, the heat pump will not be allowed to operate (i.e.
locked out), and the gas furnace will be used to satisfy the indoor
temperature. There are three separate concepts which are related to
selecting the final “balance point” temperature. Read each of the
following carefully to determine the best “balance point” in a
hybrid installation:
a. Shut off electrical power to unit and install lockout
tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
Proceed as follows to inspect and prepare the unit for initial
start--up:
1. Remove access panels (see Fig. 19).
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
1. Capacity Balance Temperature: This is a point where the
heat pump cannot provide sufficient capacity to keep up
with the indoor temperature demand because of declining
outdoor temperature. At or below this point, the furnace is
needed to maintain proper indoor temperature.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a
refrigerant leak.
2. Economic Balance Temperature: Above this point, the heat
pump is the most cost efficient to operate, and below this
point the furnace is the most cost efficient to operate. This
can be somewhat complicated to determine and it involves
knowing the cost of gas and electricity, as well as the
efficiency of the furnace and heat pump. For the most
economical operation, the heat pump should operate above
this temperature (assuming it has sufficient capacity) and the
furnace should operate below this temperature.
3. Comfort Balance Temperature: When the heat pump is
operating below this point, the indoor supply air feels
uncomfortable (i.e. too cool). This is purely subjective and
will depend on the homeowner’s idea of comfort. Below
this temperature the gas furnace should operate in order to
satisfy the desire for indoor comfort.
c. Leak test all refrigerant tubing connections using
electronic leak detector, halide torch, or liquid--soap
solution. If a refrigerant leak is detected, see the Check
for Refrigerant Leaks section.
d. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
e. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
f. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Transformer Protection
The transformer is of the energy--limiting type. It is set to withstand
a 30--sec. overload or shorted secondary condition. If an overload
or short is present, correct overload condition and check for blown
fuse on gas control board or Interface Fan Board. Replace fuse as
required with correct size and rating.
Do not purge gas supply into the combustion chamber. Do not
use a match or other open flame to check for gas leaks. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections.
14
4. Verify the following conditions:
de--energized. The evaporator motor is de--ener-
gized after a 90 sec. delay.
d. GAS HEATING MODE
a. Make sure gas line is free of air. Before lighting the unit
for the first time, perform the following with the gas
valve in the “OFF” position:
Outdoor temperature below balance point setpoint of
thermostat.
NOTE: If the gas supply pipe was not purged before connecting
the unit, it will be full of air. It is recommended that the ground
joint union be loosened, and the supply line be allowed to purge
until the odor of gas is detected. Never purge gas lines into a
combustion chamber. Immediately upon detection of gas odor,
retighten the union. Allow 5 minutes to elapse, then light unit.
Heating Sequence of Operation
(See Fig. 15 and 16 and unit wiring label.)
On a call for heating, terminal W of the thermostat is energized,
starting the induced--draft motor. When the pressure switch senses
that the induced--draft motor is moving sufficient combustion air,
the burner sequence begins. This function is performed by the
integrated gas unit controller (IGC). The indoor (evaporator)--fan
motor is energized 45 sec after flame is established. When the
thermostat is satisfied and W is de--energized, the burners stop
firing and the indoor (evaporator) fan motor shuts off after a
45--sec time--off delay. Please note that the IGC has the capability
to automatically reduce the indoor fan motor on delay and increase
the indoor fan motor off delay in the event of high duct static
and/or partially--clogged filter.
b. Make sure that condenser--fan blade is correctly
positioned in fan orifice. Leading edge of condenser--fan
blade should be 1/2 in. (12 mm) maximum from fan
orifice.
c. Make sure that air filter(s) is in place.
d. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
e. Make sure that all tools and miscellaneous loose parts
have been removed.
NOTE: An LED (light--emitting diode) indicator is provided on
the control board to monitor operation. The control board is
located by removing the burner access panel (see Fig. 19). During
normal operation, the LED is continuously on.
START--UP
Step 1 — Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:
Step 3 — Start--up Heating and Make Adjust-
ments
1. Locate leak and make sure that refrigerant system pressure
has been relieved and reclaimed from both high-- and
low--pressure ports.
!
CAUTION
2. Repair leak following Refrigerant Service procedures.
NOTE: Install a bi--flow filter drier whenever the system has been
opened for repair.
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit
being installed.
3. Add a small charge of R--410A refrigerant vapor to system
and leak--test unit.
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety
devices when operating the unit.
4. Recover refrigerant from refrigerant system and evacuate to
500 microns if no additional leaks are not found.
5. Charge unit with Puron (R--410A) refrigerant, using an
electronic scale. Refer to unit rating plate for required
charge.
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Make sure that burner orifices are
properly aligned. Unstable operation my occur when the burner
orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation
label (located on the inside of the control access panel) to start the
heating section.
Step 2 — Unit Sequence of Operation
48EZ-A Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the
blower motor for continuous fan.
b. COOLING MODE
NOTE: Make sure that gas supply has been purged, and that all
gas piping has been checked for leaks.
(1.) If indoor temperature is above temperature set
point thermostat closes circuits R to G, R to Y and
R to O--The unit delivers cooling airflow.
c. HEAT PUMP HEATING MODE
Outdoor temperature above balance point setpoint of
thermostat.
(1.) On a call for heating, terminals “Y” and “G“ of the
Hybrid thermostat are energized. The “Y“ signal is
sent to the Defrost Board (DB) terminal “Y”. The
DB has a built in five minute anti--short cycle timer
which will not allow the compressor to restart
before the time delay has expired.
(2.) “T2” energizes the compressor contactor via the
High Pressure Switch (HPS) and Low Pressure
Switch (LPS). The compressor and outdoor fan
start. Thermostat “G” energizes the Interface Fan
Board terminal “G”. The blower motor is energized
through contacts of the IFB.
Pipe Plug
Manifold
A07679
(3.) When the thermostat removes the “Y” and “G”
calls, the compressor contactor and outdoor fan are
Fig. 11 -- Burner Assembly
15
Table 4 – Altitude Derate Multiplier for U.S.A.*
BURNER FLAME
DERATE MULTIPLIER
ALTITUDE FT (M)
PERCENT OF DERATE
FACTOR{
0---2000
(0---610)
0
1.00
BURNER
2001---3000*
(610---914)
8 --- 1 2
0.90
0.86
0.82
0.78
0.74
0.70
0.66
0.62
3001---4000
(315---1219)
12---16
16---20
20---24
24---28
28---32
32---36
36---40
4001---5000
(1220---1524)
MANIFOLD
5001---6000
(1524---1829)
6001---7000
(1829---2134)
7001---8000
(2134---2438)
C99021
8001---9000
(2439---2743)
Fig. 12 -- Monoport Burner
9001---10,000
(2744---3048)
Check Heating Control
*In Canada see Canadian Altitude Adjustment.
{Derate multiplier factors are based on midpoint altitude for altitude range.
IN CANADA:
The input rating for altitudes from 2,000 to 4,500 ft (610 m to
1372 m) above sea level must be derated 10% by an authorized
Gas Conversion Station or Dealer.
Start and check the unit for proper heating control operation as
follows (see furnace lighting instructions located on the inside of
the control access panel):
1. Place room thermostat SYSTEM switch in the HEAT
position and the fan switch is placed in AUTO position.
2. Set the heating temperature control of the thermostat above
room temperature.
EXAMPLE:
90,000 Btu/hr Input Furnace Installed at 4300 ft (1311 m).
3. The induced--draft motor will start.
Furnace Input Rate at
Sea Level
X
Derate Multiplier
Factor
= Furnace Input Rate at
Installation Altitude
4. On a call for heating, the main burner should light within 5
sec. of the spark being energized. If the burners do not light,
there is a 22--sec. delay before another 5--sec. try. If the
burners still do not light, this sequence is repeated. If the
burners do not light within 15 minutes from the initial call
for heat, there is a lockout. To reset the control, break the
24--v power to W.
90,000
X
0.90
=
81,000
When the gas supply being used has a different heating value or
specific gravity, refer to national and local codes, or contact your
distributor to determine the required orifice size.
5. The evaporator fan will turn on 45 sec. after the flame has
been established. The evaporator fan will turn off 45 sec.
after the thermostat has been satisfied. Please note that the
integrated gas unit controller (IGC) has the capability to
automatically reduce the evaporator “ON” delay and in-
crease the evaporator “OFF” delay in the event of high duct
static and/or partially--clogged filter.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit
and/or component life.
Do Not redrill an orifice. Improper drilling (burrs,
out--of--round holes, etc.) can cause excessive burner noise
and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check
orifice hole with a numbered drill bit of correct size.
Check Gas Input
Check gas input and manifold pressure after unit start--up (See
Table 3). If adjustment is required proceed as follows:
S The rated gas inputs shown in Table 3 are for altitudes from sea
Adjust Gas Input
level to 2000 ft (610 m) above sea level. These inputs are based
3
The gas input to the unit is determined by measuring the gas flow
at the meter or by measuring the manifold pressure. Measuring the
gas flow at the meter is recommended for natural gas units. The
manifold pressure must be measured to determine the input of
propane gas units.
on natural gas with a heating value of 1025 Btu/ft at 0.60
specific gravity, or propane gas with a heating value of 2500
3
Btu/ft at 1.5 specific gravity.
IN THE U.S.A.:
The input rating for altitudes above 2,000 ft (610 m) must be
reduced by 4% for each 1,000 ft (305 m) above sea level.
For installations below 2,000 ft (610 m), refer to the unit rating
plate.
Measure Gas Flow (Natural Gas Units)
Minor adjustment to the gas flow can be made by changing the
manifold pressure. The manifold pressure must be maintained
between 3.2 and 3.8 IN. W.C.
For installations above 2,000 ft (610 m) multiply the input by on
the rating plate by the derate multiplier in Table 4 for correct input
rate.
If larger adjustments are required, change main burner orifices
following the recommendations of national and local codes.
NOTE: All other appliances that use the same meter must be
turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (See Fig. 11) and connect
manometer. Turn on gas supply to unit.
3. Record number of seconds for gas meter test dial to make
one revolution.
16
4. Divide number of seconds in Step 3 into 3600 (number of
seconds in one hr).
5. Multiply result of Step 4 by the number of cubic feet (cu ft)
shown for one revolution of test dial to obtain cubic feet (cu
ft) of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to
obtain total measured input in Btuh. Compare this value
with heating input shown in Table 3 (Consult the local gas
supplier if the heating value of gas is not known).
the same for each burner. Propane will have blue flame (See Fig.
12). Refer to the Maintenance section for information on burner
removal.
Normal Operation
An LED (light--emitting diode) indicator is provided on the
integrated gas unit controller (IGC) to monitor operation. The IGC
is located by removing the control access panel (see Fig. 19).
During normal operation, the LED is continuously on (See Table 5
for error codes).
EXAMPLE: Assume that the size of test dial is 1 cu ft, one
revolution takes 32 sec, and the heating value of the gas is 1050
Btu/ft . Proceed as follows:
Airflow and Temperature Rise
The heating section for each size unit is designed and approved for
heating operation within the temperature--rise range stamped on the
unit rating plate.
3
1. 32 sec. to complete one revolution.
2. 3600 ÷ 32 = 112.5.
Table 10 shows the approved temperature rise range for each
heating input, and the air delivery cfm at various temperature rises
for a given external static pressure. The heating operation airflow
must produce a temperature rise that falls within the approved
range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust
heating airflow when required.
3
3. 112.5 x 1 =112.5 ft of gas flow/hr.
4. 112.5 x 1050 = 118,125 Btuh input.
If the desired gas input is 115,000 Btuh, only a minor change in the
manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas
input:
Limit Switches
1. Remove regulator cover screw over plastic adjustment
screw on gas valve (See Fig. 13).
Normally closed limit switch (LS) completes the control circuit.
Should the leaving--air temperature rise above the maximum
allowable temperature, the limit switch opens and the control
circuit “breaks.” Any interruption in the control circuit instantly
closes the gas valve and stops gas flow to the burners. The blower
motor continues to run until LS resets.
2. Turn plastic adjustment screw clockwise to increase gas
input, or turn plastic adjustment screw counterclockwise to
decrease input (See Fig. 13). Manifold pressure must be
between 3.2 and 3.8 IN. W.C.
REGULATOR
COVER SCREW
When the air temperature at the limit switch drops to the
low--temperature setting of the limit switch, the switch closes and
completes the control circuit. The direct--spark ignition system
cycles and the unit returns to normal heating operation.
Table 5 – LED Indications
PLASTIC
ADJUSTMENT
SCREW
ON/OFF SWITCH
REGULATOR SPRING
(PROPANE - WHITE)
NATURAL - SILVER)
(
STATUS CODE
Normal Operation
LED INDICATION
GAS PRESSURE
REGULATOR
ADJUSTMENT
2
On
INLET
PRESSURE TAP
No Power or Hardware Failure
Limit Switch Fault
Off
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
Flame Sense Fault
MANIFOLD
PRESSURE TAP
Four Consecutive Limit Switch Faults
Ignition Lockout Fault
Pressure Switch Fault
A07751
Fig. 13 -- Single--Stage Gas Valve
Rollout Switch Fault
Internal Control Fault
Temporary 1 hr auto reset
!
1
WARNING
NOTES:
FIRE AND UNIT DAMAGE HAZARD
1.This code indicates an internal processor fault that will reset itself in one
hr. Fault can be caused by stray RF signals in the structure or nearby. This
is a UL requirement.
2. LED indicates acceptable operation. Do not change ignition control
board.
3. When W is energized the burners will remain on for a minimum of 60 sec.
4. If more than one error mode exists they will be displayed on the LED in
sequence.
Failure to follow this warning could result in personal
injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure
is outside this range.
Rollout Switch
3. Replace regulator cover screw on gas valve (See Fig. 13).
The function of the rollout switch is to close the main gas valve in
the event of flame rollout. The switch is located above the main
burners. When the temperature at the rollout switch reaches the
maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor
(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE
7.
4. Turn off gas supply to unit. Remove manometer from
pressure tap and replace pipe plug on gas valve. (See Fig.
11.) Turn on gas to unit and check for leaks.
Measure Manifold Pressure (Propane Units)
Refer to propane kit installation instructions for properly checking
gas input.
NOTE: For installations below 2,000 ft (610 m), refer to the unit
rating plate for proper propane conversion kit. For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.
Check Burner Flame
With control access panel (see Fig. 19) removed, observe the unit
heating operation. Watch the burner flames to see if they are light
blue and soft in appearance, and that the flames are approximately
17
Proceed as follows:
Step 4 — Start--up Cooling and Make Adjust-
ments
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40°F (4.4°C) (unless accessory
low--ambient kit is installed). Do not rapid--cycle the compressor.
Allow 5 minutes between on cycles to prevent compressor damage.
1. Remove caps from low-- and high--pressure service fittings.
2. Using hoses with valve core depressors, attach low-- and
high--pressure gauge hoses to low-- and high--pressure
service fittings, respectively.
3. Start unit in Cooling Mode and let unit run until system
pressures stabilize.
4. Measure and record the following:
Checking Cooling Control Operation
Start and check the unit for proper cooling control operation as
follows:
a. Outdoor ambient--air temperature (°F [°C] db).
b. Liquid line temperature (°F [°C]).
c. Discharge (high--side) pressure (psig).
d. Suction (low--side) pressure (psig) (for reference only).
5. Using “Cooling Charging Charts,” compare outdoor--air
temperature(°F [°C] db) with the discharge line pressure
(psig) to determine desired system operating liquid line
temperature (See Fig. 17).
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 90 sec.
6. Compare actual liquid line temperature with desired liquid
line temperature. Using a tolerance of ± 2°F (±1.1°C), add
refrigerant if actual temperature is more than 2°F (1.1°C)
higher than proper liquid line temperature, or remove
refrigerant if actual temperature is more than 2°F (1.1°C)
lower than required liquid line temperature.
IMPORTANT:
Three--phase, scroll compressors units are
direction oriented. Unit must be checked to ensure proper
compressor 3--phase power lead orientation. If not corrected within
5 minutes, the internal protector will shut off the compressor. The
3--phase power leads to the unit must be reversed to correct
rotation. When turning backwards, the difference between
compressor suction and discharge pressures will be near zero.
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to the Check for Refrigerant Leaks section.
Indoor Airflow and Airflow Adjustments
!
CAUTION
Checking and Adjusting Refrigerant Charge
UNIT OPERATION HAZARD
The refrigerant system is fully charged with PuronR (R--410A)
refrigerant and is tested and factory sealed. Allow system to operate
a minimum of 15 minutes before checking or adjusting charge.
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to
450 cfm for each 12,000 Btuh of rated cooling capacity. For
heating operation, the airflow must produce a temperature
rise that falls within the range stamped on the unit rating
plate.
NOTE: Adjustment of the refrigerant charge is not required unless
the unit is suspected of not having the proper PuronR (R--410A)
charge.
The charging label and the tables shown refer to system
temperatures and pressures in cooling mode only. A refrigerant
charging label is attached to the inside of the compressor access
panel (see Fig. 19). The chart includes the required liquid line
temperature at given discharge line pressures and outdoor ambient
temperatures.
An accurate thermocouple-- or thermistor--type thermometer, and a
gauge manifold are required when using the subcooling charging
method for evaluating the unit charge. Do not use mercury or small
dial--type thermometers because they are not adequate for this type
of measurement.
NOTE: Be sure that all supply--and return--air grilles are open,
free from obstructions, and adjusted properly.
!
WARNING
ELECTRICAL SHOCK AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before making any indoor wiring adjustments, shut off gas
supply. Then disconnect electrical power to the unit and
install lockout tag before changing blower speed.
!
CAUTION
This unit has independent fan speeds for gas heating and cooling.
In addition, this unit has the field-selectable capability to run two
different cooling fan speeds: A normal cooling fan speed (350~400
CFM/Ton) and an enhanced dehumidification fan speed (As low as
320 CFM/Ton) for use with either a dehumidistat or a thermostat
that supports dehumidification.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
When evaluating the refrigerant charge, an indicated
adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an
abnormal condition exists somewhere in the cooling system,
such as insufficient airflow across either coil or both coils.
This unit is factory-set up for use with a single cooling fan speed.
The cooling speed is marked “LOW” on the interface fan board
(IFB) (See Fig. 14) . The factory-shipped settings are noted in
Table 10. There are 3 additional speed tap wires available for use
in either gas heating or cooling (For color coding on the indoor fan
motor leads, see Table 6). The additional 3 speed tap wires are
shipped loose with vinyl caps and are located in the control box,
near the interface fan board (IFB) (See Fig. 14).
18
5. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding) for the dehumidification
cooling fan speed and place desired speed tap wire on the
“LOW” connection on the interface board (IFB). Verify
that static pressure is in the acceptable range for the speed
tap to be used for dehumidification cooling.
Gas Heating Fan Speed Set-up
To change the gas heating speed:
1. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding). Table 10 shows the
temperature rise associated with each fan speed for a given
static pressure. Make sure that the speed chosen delivers a
temperature rise within the rise range listed on the unit
rating plate.
6. Use any spare vinyl plugs to cap any unused speed tap
wires.
Continuous Fan Operation
2. Remove the current speed tap wire from the “GAS HEAT”
terminal on the interface fan board (IFB) (Fig.14) and place
vinyl cap over the connector on the wire.
When the DEHUM feature is not used, the continuous fan speed
will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed
when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized (see Fig. 14).
3. Connect the desired speed tap wire to the “GAS HEAT”
terminal on the interface fan board (IFB).
Single Cooling Fan Speed Set-up (Dehumidification
feature not used)
To change cooling speed:
NOTE: For heat pump operation, the recommended airflow is 350
to 450 CFM for each 12,000 Btuh of rated cooling capacity.
Table 6 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
1. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding). Add the wet coil
pressure drop in Table 8 to the system static to determine the
correct cooling airflow speed in Table 10 that will deliver
the nominal cooling airflow as listed in Table 1 for each
size.
Orange = Med---High Speed
Red = Med Speed
Pin k = Med --- L ow Speed
Blue = Low Speed
GAS
HEAT
2. Remove the current speed tap wire from the “LOW”
terminal on the interface fan board (IFB) (See Fig. 14) and
place vinyl cap over the connector on the wire.
3. Connect the desired speed tap wire to the “LOW” terminal
on the interface fan board (IFB).
HIGH
QC7
LOW
QC4
COM
QC3
QC6
K2
K1
D2
DCR
QCR
QC1
Two Cooling Fan Speeds Set-up (Dehumidification
feature used)
C
RL3 C8 R1L
Q1
RI0
JM6
Q3
RI2
IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
C9
C4
RI DL
JM5
G1
G2
Use of the dehumidification cooling fan speed requires use of
either a 24 VAC dehumidistat or a thermostat which includes
control of a 24 VAC dehumidistat connection. In either case, the
dehumidification control must open the control circuit on humidity
rise above the dehumidification set point. Dehumidification
controls are available with the reverse logic; these must not be
used.
OILL C2 D6 D4
A7
R9 AB A15
F1
C0
U1
R4
RL4
C3
D5 D3
C7
JW3
1. Remove fan speed tap wire from the “LOW” terminal on
the interface fan board (IFB) (See Fig. 14).
R3 R5
P2R6
R2
QCB
JW7
2. Determine correct normal cooling fan speed for unit and
application. Add the wet coil pressure drop in Table 8 to
the system static to determine the correct cooling airflow
speed in Table 10 that will deliver the nominal cooling
airflow as listed in Table 1 for each size.
JW2
JW4
Y
Y
R
U
C
24VAC
JW1
P1
SSTZ-8
Y2/
DH
Y1/
3. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding) for the normal cooling
fan speed and place desired speed tap wire on “HIGH” on
the interface board.
W2
G
Y
C
R
A09058
Fig. 14 -- Interface Fan Board (IFB)
4. Refer to airflow tables (Table 10) to determine allowable
speeds for the dehumidification cooling fan speed. In Table
10, speeds that are not allowed for dehumidification cooling
are shaded.
19
Table 7 – Filter Pressure Drop Table (IN. W.C.)
CFM
FILTER SIZE
in. (mm)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20X20X1
(508X508X25)
20X24X1
(508X610x25 )
24X30X1
(610X762x25)
24X36X1
(610X914X25)
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.09 0.10 0.11 0.13 0.14 0.15 0.16
0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.10
—
—
—
—
0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14
Table 8 – 48EZ--A Wet Coil Pressure Drop (IN. W.C.)
Standard CFM (S.C.F.M)
Unit Size
500
600
0.06
700
0.07
800
0.08
0.12
900
0.09
0.15
1000
0.10
0.19
0.07
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
24
30
36
42
48
60
0.23
0.11
0.27
0.18
0.04
0.26
0.07
0.35
0.10
0.11
0.15
0.14
0.21
0.17
0.10
0.22
0.17
0.28
0.23
0.31
0.36
Table 9 – Wet Coil Air Delivery (CFM) -- Downflow -- High Speed with 1--in. (25 mm) Filter and Economizer
EXTERNAL STATIC PRESSURE (in. W.C.)
UNIT SIZE
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
36
42
48
60
1333
1612
2166
2298
1289
1569
2085
2239
1256
1527
2002
2180
1214
1481
1919
2110
1152
1451
1798
2044
1118
1393
1709
1951
1076
1351
1582
1862
1035
1317
1467
1777
997
950
1242
988
1278
1270
1697
1591
Table 10 – Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
EXTERNAL STATIC PRESSURE (in. W.C.)
HEATING
MOTOR
WIRE
UNIT
RISE RANGE
SPEED
COLOR
0.1
0.2
0.3
538
0.4
429
0.5
--- ---
0.6
--- ---
0.7
--- ---
0.8
0.9
CFM
754
650
--- ---
--- ---
Heating
40
46
56
NA
NA
NA
NA
NA
NA
o
Rise ( F)
Low
Blue
Pink
Heating
22
851
36
26
777
39
31
675
45
NA
591
51
NA
475
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Heating
20
941
32
22
851
36
25
774
39
28
684
44
NA
576
52
NA
479
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
30 --- 60 F
o
2
Rise ( F)
48EZ(---,N)A24040
Medium
Red
o
(17 --- 33 C)
Heating
18
1009
30
20
917
33
22
840
36
25
759
40
29
667
45
NA
577
52
NA
447
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
Blue
1
High
Heating
17
1241
NA
18
1167
NA
20
1111
NA
22
1036
NA
25
969
31
29
881
34
NA
818
37
NA
731
41
NA
640
47
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Low
Heating
NA
754
NA
NA
650
NA
NA
538
NA
NA
429
NA
17
--- ---
NA
19
--- ---
NA
21
--- ---
NA
23
--- ---
NA
26
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
851
52
NA
777
NA
NA
675
NA
NA
591
NA
NA
475
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
29
941
47
NA
851
52
NA
774
NA
NA
684
NA
NA
576
NA
NA
479
NA
NA
--- ---
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
25 --- 55 F
o
2
Rise ( F)
48EZ(---,N)A24060
Medium
Red
o
(14 --- 31 C)
Heating
26
1009
44
29
917
48
NA
840
53
NA
759
NA
NA
667
NA
NA
577
NA
NA
447
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- High
Orange
Black
Heating
24
1241
36
27
1167
38
29
1111
40
NA
1036
43
NA
969
46
NA
881
50
NA
818
54
NA
731
NA
NA
640
NA
o
Rise ( C)
CFM
Heating
o
1
Rise ( F)
High
Heating
20
21
22
24
25
28
30
NA
NA
o
Rise ( C)
20
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
EXTERNAL STATIC PRESSURE (in. W.C.)
HEATING
MOTOR
WIRE
UNIT
RISE RANGE
SPEED
COLOR
0.1
0.2
0.3
547
0.4
415
0.5
--- ---
0.6
--- ---
0.7
--- ---
0.8
0.9
CFM
741
638
--- ---
--- ---
Heating
41
47
55
NA
NA
NA
NA
NA
NA
o
Rise ( F)
Low
Blue
Pink
Heating
23
973
31
26
887
34
31
823
37
NA
733
41
NA
665
45
NA
538
56
NA
451
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
1
Low
Heating
17
1088
NA
19
1023
30
20
954
32
23
881
34
25
800
38
31
723
42
NA
658
46
NA
563
54
NA
461
NA
o
Rise ( C)
CFM
Heating
o
30 --- 60 F
o
Rise ( F)
48EZ(---,N)A30040
Medium
Red
o
(17 --- 33 C)
Heating
NA
1140
NA
16
1064
NA
18
996
30
19
915
33
21
840
36
23
758
40
26
687
44
30
564
54
NA
480
NA
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
Blue
2
High
Heating
NA
1202
NA
NA
1140
NA
17
1082
NA
18
1015
30
20
961
31
22
881
34
24
810
37
30
732
41
NA
631
48
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Low
Heating
NA
741
NA
NA
638
NA
NA
547
NA
17
415
NA
17
--- ---
NA
19
--- ---
NA
21
--- ---
NA
23
--- ---
NA
27
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
973
46
NA
887
50
NA
823
54
NA
733
NA
NA
665
NA
NA
538
NA
NA
451
NA
NA
--- ---
NA
NA
--- ---
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
25
1088
41
28
1023
43
30
954
47
NA
881
50
NA
800
NA
NA
723
NA
NA
658
NA
NA
563
NA
NA
461
NA
o
Rise ( C)
CFM
Heating
o
25 --- 55 F
o
Rise ( F)
48EZ(---,N)A30060
Medium
Med ---
Red
o
(14 --- 31 C)
Heating
23
1140
39
24
1064
42
26
996
45
28
915
49
NA
840
53
NA
758
NA
NA
687
NA
NA
564
NA
NA
480
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Orange
Black
Blue
2
High
Heating
22
1202
37
23
1140
39
25
1082
41
27
1015
44
29
961
46
NA
881
50
NA
810
55
NA
732
NA
NA
631
NA
o
Rise ( C)
CFM
Heating
o
1
Rise ( F)
High
Heating
21
1234
36
22
1168
38
23
1093
41
24
1021
44
26
961
46
28
894
50
30
825
54
NA
759
NA
NA
687
NA
o
Rise ( C)
CFM
Heating
o
1
Rise ( F)
Low
Heating
20
1290
34
21
1223
36
23
1154
39
24
1090
41
26
1027
43
28
977
45
30
894
50
NA
828
54
NA
762
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
19
1354
33
20
1290
34
21
1226
36
23
1158
38
24
1102
40
25
1046
42
28
981
45
30
918
48
NA
843
53
o
Rise ( C)
CFM
Heating
o
25 --- 55 F
o
2
Rise ( F)
48EZ(---,N)A36060
Medium
Red
o
(14 --- 31 C)
Heating
18
1606
28
19
1546
29
20
1489
30
21
1430
31
22
1371
32
24
1316
34
25
1258
35
27
1208
37
29
1140
39
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- High
High
Orange
Black
Heating
15
1630
27
16
1580
28
17
1517
29
17
1463
30
18
1407
32
19
1339
33
20
1277
35
20
1210
37
22
1131
39
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
15
16
16
17
18
18
19
20
22
o
Rise ( C)
21
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
EXTERNAL STATIC PRESSURE (in. W.C.)
HEATING
MOTOR
WIRE
UNIT
RISE RANGE
SPEED
COLOR
0.1
0.2
0.3
1093
0.4
1021
0.5
961
0.6
894
0.7
825
0.8
0.9
CFM
1234
1168
759
687
Heating
55
58
62
NA
NA
NA
NA
NA
NA
o
Rise ( F)
Low
Blue
Pink
Heating
31
1290
53
32
1223
56
35
1154
59
NA
1090
62
NA
1027
NA
NA
977
NA
NA
894
NA
NA
828
NA
NA
762
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Heating
29
1354
50
31
1290
53
33
1226
55
35
1158
59
NA
1102
62
NA
1046
65
NA
981
NA
NA
918
NA
NA
843
NA
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
2
Rise ( F)
48EZ(---,N)A36090
Medium
Red
o
(19 --- 36 C)
Heating
28
1606
42
29
1546
44
31
1489
46
33
1430
48
34
1371
50
36
1316
52
NA
1258
54
NA
1208
56
NA
1140
60
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- High
Orange
Black
Blue
Heating
24
1630
42
24
1580
43
25
1517
45
26
1463
46
28
1407
48
29
1339
51
30
1277
53
31
1210
56
33
1131
60
o
Rise ( C)
CFM
Heating
o
1
Rise ( F)
High
Heating
23
1295
34
24
1234
36
25
1182
38
26
1126
39
27
1075
41
28
1016
44
30
955
47
31
898
49
33
857
52
o
Rise ( C)
CFM
Heating
o
1
Rise ( F)
Low
Heating
19
1345
33
20
1282
35
21
1235
36
22
1194
37
23
1140
39
24
1095
41
26
1027
43
27
974
46
29
921
48
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
18
1505
30
19
1452
31
20
1413
31
21
1358
33
22
1323
34
23
1282
35
24
1234
36
25
1169
38
27
1130
39
o
Rise ( C)
CFM
Heating
o
25 --- 55 F
o
Rise ( F)
48EZ(---,N)A42060
Medium
Med ---
Red
o
(14 --- 31 C)
Heating
16
1545
29
17
1492
30
17
1449
31
18
1411
31
19
1362
33
19
1313
34
20
1278
35
21
1231
36
22
1188
37
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Orange
Black
Blue
2
High
Heating
16
1705
26
17
1643
27
17
1607
28
17
1568
28
18
1518
29
19
1483
30
19
1448
31
20
1404
32
21
1360
33
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Low
Heating
14
1295
53
15
1234
55
15
1182
58
16
1126
60
16
1075
63
17
1016
NA
17
955
NA
18
898
NA
18
857
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
29
1345
51
31
1282
53
32
1235
55
34
1194
57
35
1140
60
NA
1095
62
NA
1027
NA
NA
974
NA
NA
921
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
28
1505
45
29
1452
47
31
1413
48
32
1358
50
33
1323
51
35
1282
53
NA
1234
55
NA
1169
58
NA
1130
60
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
1
Rise ( F)
48EZ(---,N)A42090
Medium
Red
o
(19 --- 36 C)
Heating
25
1545
44
26
1492
46
27
1449
47
28
1411
48
29
1362
50
29
1313
52
31
1278
53
32
1231
55
33
1188
57
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
2
High
Heating
24
1705
40
25
1643
41
26
1607
42
27
1568
43
28
1518
45
29
1483
46
30
1448
47
31
1404
48
32
1360
50
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Heating
22
23
24
24
25
25
26
27
28
o
Rise ( C)
22
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
EXTERNAL STATIC PRESSURE (in. W.C.)
HEATING
MOTOR
WIRE
UNIT
RISE RANGE
SPEED
COLOR
0.1
0.2
0.3
1311
0.4
1263
0.5
1224
0.6
1172
0.7
1136
0.8
0.9
CFM
1402
1351
1080
1041
Heating
49
50
52
54
56
58
60
63
65
o
1
Rise ( F)
Low
Blue
Pink
Heating
27
1457
47
28
1404
48
29
1367
50
30
1318
52
31
1284
53
32
1233
55
33
1197
57
35
1144
59
36
1104
62
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Heating
26
1736
39
27
1695
40
28
1642
41
29
1601
42
29
1553
44
31
1512
45
32
1465
46
33
1427
48
34
1381
49
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
2
Rise ( F)
48EZ(---,N)A48090
Medium
Red
o
(19 --- 36 C)
Heating
22
2149
NA
22
2111
NA
23
2062
NA
24
2026
NA
24
1980
NA
25
1945
35
26
1905
36
26
1864
36
27
1793
38
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- High
High
Orange
Black
Blue
Heating
NA
2344
NA
NA
2306
NA
NA
2259
NA
NA
2203
NA
NA
2141
NA
19
2070
NA
20
1991
NA
20
1902
36
21
1803
38
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
1402
NA
NA
1351
NA
NA
1311
NA
NA
1263
NA
NA
1224
NA
NA
1172
NA
NA
1136
NA
20
1080
NA
21
1041
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Low
Heating
NA
1457
60
NA
1404
NA
NA
1367
NA
NA
1318
NA
NA
1284
NA
NA
1233
NA
NA
1197
NA
NA
1144
NA
NA
1104
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
33
1736
50
NA
1695
51
NA
1642
53
NA
1601
54
NA
1553
56
NA
1512
57
NA
1465
59
NA
1427
NA
NA
1381
NA
o
Rise ( C)
CFM
Heating
o
30 --- 60 F
o
2
Rise ( F)
48EZ(---,N)A48115
Medium
Red
o
(17 --- 33 C)
Heating
28
2149
40
28
2111
41
29
2062
42
30
2026
43
31
1980
44
32
1945
45
33
1905
46
NA
1864
47
NA
1793
48
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
Blue
1
High
Heating
22
2344
37
23
2306
38
23
2259
38
24
2203
39
24
2141
41
25
2070
42
25
1991
44
26
1902
46
27
1803
48
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Low
Heating
21
1402
NA
21
1351
NA
21
1311
NA
22
1263
NA
23
1224
NA
23
1172
NA
24
1136
NA
25
1080
NA
27
1041
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
1457
NA
NA
1404
NA
NA
1367
NA
NA
1318
NA
NA
1284
NA
NA
1233
NA
NA
1197
NA
NA
1144
NA
NA
1104
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
NA
1736
55
NA
1695
57
NA
1642
59
NA
1601
60
NA
1553
62
NA
1512
64
NA
1465
NA
NA
1427
NA
NA
1381
NA
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
2
Rise ( F)
48EZ(---,N)A48130
Medium
Red
o
(19 --- 36 C)
Heating
31
2149
45
32
2111
46
33
2062
47
33
2026
48
34
1980
49
35
1945
50
NA
1905
51
NA
1864
52
NA
1793
54
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
1
High
Heating
25
2344
41
25
2306
42
26
2259
43
26
2203
44
27
2141
45
28
2070
47
28
1991
48
29
1902
51
30
1803
53
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Heating
23
23
24
24
25
26
27
28
30
o
Rise ( C)
23
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48EZ--A24--60
EXTERNAL STATIC PRESSURE (in. W.C.)
HEATING
MOTOR
WIRE
UNIT
RISE RANGE
SPEED
COLOR
0.1
0.2
0.3
1341
0.4
1281
0.5
1236
0.6
1189
0.7
1139
0.8
0.9
CFM
1445
1389
1072
1027
Heating
47
49
51
53
55
57
60
63
NA
o
1
Rise ( F)
Low
Blue
Pink
Heating
26
1678
41
27
1635
42
28
1602
42
29
1558
44
31
1513
45
32
1474
46
33
1438
47
35
1404
48
NA
1349
50
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Heating
23
1927
35
23
1893
36
24
1858
37
24
1824
37
25
1791
38
26
1759
39
26
1720
40
27
1689
40
28
1640
41
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
2
Rise ( F)
48EZ(---,N)A60090
Medium
Red
o
(19 --- 36 C)
Heating
20
2131
NA
20
2088
NA
20
2065
NA
21
2013
NA
21
1982
NA
21
1941
35
22
1888
36
22
1860
37
23
1785
38
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- High
High
Orange
Black
Blue
Heating
NA
2461
NA
NA
2409
NA
NA
2339
NA
NA
2286
NA
NA
2192
NA
19
2140
NA
20
2062
NA
20
1968
35
21
1874
36
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
1445
60
NA
1389
NA
NA
1341
NA
NA
1281
NA
NA
1236
NA
NA
1189
NA
NA
1139
NA
19
1072
NA
20
1027
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Low
Heating
33
1678
52
NA
1635
53
NA
1602
54
NA
1558
56
NA
1513
57
NA
1474
59
NA
1438
60
NA
1404
NA
NA
1349
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
29
1927
45
30
1893
46
30
1858
47
31
1824
48
32
1791
49
33
1759
49
34
1720
51
NA
1689
51
NA
1640
53
o
Rise ( C)
CFM
Heating
o
30 --- 60 F
o
2
Rise ( F)
48EZ(---,N)A60115
Medium
Red
o
(17 --- 33 C)
Heating
25
2131
41
26
2088
42
26
2065
42
26
2013
43
27
1982
44
27
1941
45
28
1888
46
29
1860
47
29
1785
49
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
Blue
1
High
Heating
23
2461
35
23
2409
36
23
2339
37
24
2286
38
24
2192
40
25
2140
41
26
2062
42
26
1968
44
27
1874
46
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Low
Heating
20
1445
NA
20
1389
NA
21
1341
NA
21
1281
NA
22
1236
NA
23
1189
NA
23
1139
NA
25
1072
NA
26
1027
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Heating
NA
1678
57
NA
1635
59
NA
1602
60
NA
1558
62
NA
1513
64
NA
1474
65
NA
1438
NA
NA
1404
NA
NA
1349
NA
o
Rise ( C)
CFM
Heating
o
Rise ( F)
Med --- L ow
Pink
Heating
32
1927
50
33
1893
51
33
1858
52
34
1824
53
35
1791
54
36
1759
55
NA
1720
56
NA
1689
57
NA
1640
59
o
Rise ( C)
CFM
Heating
o
35 --- 65 F
o
2
Rise ( F)
48EZ(---,N)A60130
Medium
Red
o
(19 --- 36 C)
Heating
28
2131
45
28
2088
46
29
2065
47
29
2013
48
30
1982
49
30
1941
50
31
1888
51
32
1860
52
33
1785
54
o
Rise ( C)
CFM
Heating
Med ---
o
Rise ( F)
Orange
Black
1
High
Heating
25
2461
39
26
2409
40
26
2339
41
27
2286
42
27
2192
44
28
2140
45
28
2062
47
29
1968
49
30
1874
51
o
Rise ( C)
CFM
Heating
o
Rise ( F)
High
Heating
22
22
23
23
24
25
26
27
29
o
Rise ( C)
* Air delivery values are without air filter and are for dry coil (See Table 8 --- 48EZ---A Wet Coil Pressure Drop table).
1
Factory---shipped gas heating speed
Factory---shipped heat pump speed
2
NA --- Not allowed for heating speed
Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
24
A09068
Fig. 15 -- 208/230--1--60 Wiring Diagram, Unit 48EZ--A
25
A09209
Fig. 16 -- 208/230--3--60 Wiring Diagram, Unit 48EZ--A
26
A08019
Fig. 17 -- Cooling Charging Table--Subcooling
27
3. Inspect blower motor and wheel for cleanliness at the
beginning of each heating and cooling season. Clean when
necessary. For first heating and cooling season, inspect
blower wheel bi--monthly to determine proper cleaning
frequency.
4. Check electrical connections for tightness and controls for
proper operation each heating and cooling season. Service
when necessary. Ensure electrical wiring is not in contact
with refrigerant tubing or sharp metal edges.
MAINTENANCE
To ensure continuing high performance and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This combination
heating/cooling unit should be inspected at least once each year by
a qualified service person. To troubleshoot cooling or heating of
units, refer to Tables 10, 11 and 12.
NOTE: Consult your local dealer about the availability of a
maintenance contract.
5. Check and inspect heating section before each heating
season. Clean and adjust when necessary.
!
WARNING
6. Check flue hood and remove any obstructions, if necessary.
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Air Filter
Failure to follow this warning could result in personal injury
or death and unit component damage.
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. (See Table 1
for recommended filter sizes.)
The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills, tools
and equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment, other than those
procedures recommended in the Owner’s Manual.
Inspect air filter(s) at least once each month and replace
(throwaway--type) or clean (cleanable--type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and/or lint.
Indoor Blower and Motor
NOTE: All motors are prelubricated. Do not attempt to lubricate
these motors.
!
WARNING
ELECTRICAL SHOCK AND EXPLOSION HAZARD
Failure to follow these warnings could result in personal
injury or death:
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
1. Turn off electrical power to the unit and install a lockout
tag before performing any maintenance or service on this
unit.
!
WARNING
2. Use extreme caution when removing panels and parts.
ELECTRICAL SHOCK HAZARD
3. Never place anything combustible either on or in contact
with the unit.
4. Should overheating occur or the gas supply fail to shut
off, turn off external main manual gas valve to the unit.
Then shut off electrical supply.
Failure to follow this warning could result in personal injury
or death.
Disconnect and tag electrical powerto theunit beforecleaning
and lubricating the blower motor and wheel.
Cleaning the Blower Motor and Wheel
1. Remove and disassemble blower assembly as follows:
a. Remove blower access panel (see Fig. 19).
b. Disconnect 5 pin plug and 4 pin plug from indoor
blower motor. Remove capacitor if required.
c. On all units, remove blower assembly from unit.
Remove screws securing blower to blower partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 19) or performing
maintenance functions inside your unit, be aware of sharp
sheet metal parts and screws. Although special care is taken
to reduce sharp edges to a minimum, be extremely careful
when handling parts or reaching into the unit.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft.
Remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of
housing.
!
CAUTION
2. Remove and clean blower wheel as follows:
UNIT OPERATION HAZARD
a. Ensure proper reassembly by marking wheel orientation.
Failure to follow this caution may result in improper
operation.
b. Lift wheel from housing. When handling and/or
cleaning blower wheel, be sure not to disturb balance
weights (clips) on blower wheel vanes.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to
disconnecting when servicing.
c. Remove caked--on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from
wheel and housing with vacuum cleaner, using soft
brush attachment. Remove grease and oil with mild
solvent.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary. Certain geographical locations may require more
frequent inspections.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of
shaft. Reinstall blower into unit. Reinstall capacitor.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate
drain each cooling season for cleanliness. Clean when
necessary.
28
f. Connect 5 pin plug and 4 pin plug to indoor blower
motor.
1. Remove the induced draft blower assembly according to
directions in the Induced Draft Blower Assembly section.
g. Reinstall blower access panel (see Fig. 19).
2. Remove the 11 screws holding the flue collector box cover
(See Fig. 18) to the heat exchanger assembly. Inspect the
heat exchangers.
3. Restore electrical power to unit. Start unit and check for
proper blower rotation and motor speeds during heating and
cooling cycles.
3. Clean all surfaces, as required, using a wire brush.
Limit Switch
Integrated
Gas Unit
Controller
(IGC)
Remove blower access panel (see Fig. 19). Limit switch is located
on the fan partition.
Auto Transformer
fuses used on 460
volt units only.
(Hidden)
Burner Ignition
Unit is equipped with a direct spark ignition 100 percent lockout
system. Ignition module (IGC) is located in the control box (See
Interface Fan
Board (IFB)
Fig. 18). Module contains
a
self--diagnostic LED. During
servicing, refer to label diagram or Table 5 in these instructions for
LED interpretation.
Induced Draft
Motor
If lockout occurs, unit may be reset by either momentarily
interrupting power supply to unit or by turning selector switch to
OFF position at the thermostat.
Fan Partition
Flue
Rollout
Switch
Mounting
Bracket
Collector
Box
Inducer
Blower
Housing
Burner
Rack
Mounting
Screw
Main Burners
A09193
At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.
Fig. 18 -- Blower Housing and Flue Collector Box
Removal of Gas Train
To remove the gas train for servicing:
1. Shut off main gas valve.
2. Shut off power to unit and install lockout tag.
3. Remove control access panel (See Fig. 19).
4. Disconnect gas piping at unit gas valve.
5. Remove fan partition mounting bracket (2 screws located
on the left side of the control compartment on the fan parti-
tion panel). Slide bracket forward, bottom first, to remove
(See Fig. 18).
6. Remove wires connected to gas valve. Mark each wire.
7. Remove the mounting screw that attaches the burner rack to
the unit base (See Fig. 18).
CONTROL
ACCESS
PANEL
BLOWER
8. Partially slide the burner rack out of the unit (see Fig. 18
and 21). Remove ignitor and sensor wires at the burner as-
sembly. Remove rollout switch wires.
ACCESS
COMPRESSOR
PANEL
ACCESS PANEL
A09207
9. Slide the burner rack out of the unit (See Fig. 18 and 21).
10. To reinstall, reverse the procedure outlined above.
Fig. 19 -- Unit Access Panels
Induced Draft (combustion air) Blower Assembly
The induced--draft blower assembly consists of the inducer motor,
the blower housing, and the induced--draft blower wheel.
Clean periodically to assure proper airflow and heating efficiency.
Inspect blower wheel every fall and periodically during the heating
season. For the first heating season, inspect blower wheel
bimonthly to determine proper cleaning frequency.
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the outdoor coil, indoor coil, and condensate drain pan at
least once each year. The coils are easily cleaned when dry;
therefore, inspect and clean the coils either before or after each
cooling season. Remove all obstructions, including weeds and
shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent--and--water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray outdoor coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
To inspect blower wheel, remove draft hood assembly. Shine a
flashlight into opening to inspect wheel. If cleaning is required,
remove induced--draft blower assembly as follows:
1. Remove control access panel (See Fig. 19).
2. Remove the 5 screws that attach induced--draft blower as-
sembly to the flue collector box cover.
3. Slide the assembly out of the unit. (See 20). Clean the
blower wheel. If additional cleaning is required, continue
with Steps 4 and 5.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain tube is restricted, clear it with a “plumbers
snake” or similar probe device. Ensure that the auxiliary drain port
above the drain tube is also clear.
4. To remove blower wheel, remove 2 setscrews.
5. To remove inducer motor, remove screws that hold the
inducer motor to the blower housing.
6. To reinstall, reverse the procedure outlined above.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat
exchanger:
29
BLOWER
HOUSING
2 SETSCREWS
(HIDDEN)
A07680
Fig. 23 -- Burner Rack Removed
Outdoor Fan
!
CAUTION
UNIT OPERATION HAZARD
C99085
Failure to follow this caution may result in damage to unit
components.
Fig. 20 -- Removal of Motor and Blower Wheel
Keep the outdoor fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
5. When replacing fan blade, position blade back to the same
position as before.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
A07680
Fig. 21 -- Burner Rack Removed
7. Replace grille.
Electrical Controls and Wiring
FEEDER TUBE
STUB TUBE
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the gas supply, and then the electrical power to the
unit.
Remove access panels (see Fig. 19) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any discolored or burned
connections are noticed, disassemble the connection, clean all the
parts, re--strip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace the
access panels (see Fig. 19). Start the unit, and observe at least one
complete heating cycle and one complete cooling cycle to ensure
proper operation. If discrepancies are observed in any operating
cycle, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.
DEFROST
THERMOSTAT
C99029
Fig. 22 -- Defrost Thermostat Location
NOTE: Refer to the heating and/or cooling sequence of operation
in this publication as an aid in determining proper control
operation.
Refrigerant Circuit
Annually inspect all refrigerant tubing connections and the unit
base for oil accumulations. Detecting oil generally indicates a
refrigerant leak.
30
Speedup
Pins
Quiet
Shift
Defrost interval
DIP switches
A08020
Fig. 24 -- Defrost Control
the Indoor Airflow and Airflow Adjustments section to check the
system airflow.
!
WARNING
Check Defrost Thermostat
EXPLOSION,
ENVIRONMENTAL HAZARD
PERSONAL
INJURY
AND
The defrost thermostat is usually located on the lowest liquid
leaving circuit of the left condenser coil (see Fig. 22). The
thermostat closes at 32_F (0_C) and opens at 65_F (18_C).
Failure to follow this warning could result in personal injury,
death or property damage.
Puron Items
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal. Use all
service ports and open all flow--control devices, including
solenoid valves.
Metering Device (Thermostatic Expansion Valve &
Piston)
This unit uses both a hard shutoff, balance port TXV in the indoor
coil and a piston in each side of the outdoor coil. The TXV
maintains a constant superheat at the evaporator coil exit (cooling
mode) resulting in higher overall system efficiency.
If oil is detected or if low cooling performance is suspected,
leak--test all refrigerant tubing using an electronic leak--detector,
halide torch, or liquid--soap solution. If a refrigerant leak is
detected, refer to the Check for Refrigerant Leaks section.
Pressure Switches
Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. These pressure
switches are specifically designed to operate with Puron (R--410A)
systems. R--22 pressure switches must not be used as replacements
for the Puron (R--410A) system.
If no refrigerant leaks are found and low cooling performance is
suspected, refer to the Checking and Adjusting Refrigerant Charge
section.
Gas Input
The gas input does not require checking unless improper heating
performance is suspected. If a problem exists, refer to the Start--Up
section.
Loss of Charge Switch
This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch
should be closed. To check switch:
Indoor Airflow
The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem exists, be
sure that all supply-- and return--air grilles are open and free from
obstructions, and that the air filter is clean. When necessary, refer to
1. Turn off all power to unit.
31
C99097
Fig. 25 -- Refrigerant Circuit
2. Disconnect leads on switch.
The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power
should be shut off, if possible, for most troubleshooting techniques.
Refrigerants present additional safety hazards.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
NOTE: Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in personal injury
or death and/or property damage.
High--Pressure Switch
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
The high--pressure switch is located in the discharge line and
protects against excessive condenser coil pressure. It opens at 650
psig.
High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation. To check switch:
The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an internal
pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port
has an operating range between 550 and 625 psig differential
pressure.
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to
operate with Puron (R--410A) refrigerant and cannot be
interchanged.
32
INDOOR COIL
OUTDOOR COIL
TXV in Metering
Position
LCS
HPS
Bypass
Position
LEGEND
HPS – High Pressure Switch
LCS – Loss of Charge Switch
®
Accurater Metering Device
Arrow indicates direction of flow
C03011
Fig. 26 -- Typical Heat Pump Operation, Cooling Mode
INDOOR COIL
OUTDOOR COIL
TXV in Bypass
Position
LCS
HPS
Metering
Position
LEGEND
HPS – High Pressure Switch
LCS – Loss of Charge Switch
®
Accurater Metering Device
Arrow indicates direction of flow
C03012
Fig. 27 -- Typical Heat Pump Operation, Heating Mode
Refrigerant System
!
WARNING
This information covers the refrigerant system of the 48EZ--A,
including the compressor oil needed, servicing systems on roofs
containing synthetic materials, the filter drier and refrigerant
charging.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury
or equipment damage.
Compressor Oil
If additional oil is needed use Uniqema RL32--3MAF. If this oil is
not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC.
This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
This system uses Puron (R--410A) refrigerant which has
higher operating pressures than R--22 and other refrigerants.
No other refrigerant may be used in this system. Gauge set,
hoses,andrecoverysystemmustbe designedto handlePuron.
If you are unsure, consult the equipment manufacturer.
33
Servicing Systems on Roofs and with Synthetic materials
Liquid Line Filter Drier
POE (polyolester) compressor lubricants are known to cause long
term damage to some synthetic roofing materials.
This filter drier is specifically designed to operate with Puron. Use
only factory--authorized components. Filter drier must be replaced
whenever the refrigerant system is opened. When removing a filter
drier, use a tubing cutter to cut the drier from the system. Do not
unsweat a filter drier from the system. Heat from unsweating will
release moisture and contaminants from drier into system.
Exposure, even if immediately cleaned up, may cause
embrittlement (leading to cracking) to occur in one year or more.
When performing any service that may risk exposure of
compressor oil to the roof, take appropriate precautions to protect
roofing. Procedures which risk oil leakage include, but are not
limited to, compressor replacement, repairing refrigerant leaks,
replacing refrigerant components such as filter drier, pressure
switch, metering device, coil, accumulator, or reversing valve.
Puron (R--410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some R--410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to
flow from cylinder in upright position. For cylinders equipped
with a dip tube, charge Puron units with cylinder in upright
position and a commercial metering device in manifold hose.
Charge refrigerant into suction--line.
Synthetic Roof Precautionary Procedure
1. Cover extended roof working area with an impermeable
polyethylene (plastic) drip cloth or tarp. Cover an
approximate 10x10 ft (3x3 m) area.
2. Cover area in front of the unit service panel with a terry
cloth shop towel to absorb lubricant spills and prevent
run--offs, and protect drop cloth from tears caused by tools
or components.
TROUBLESHOOTING
Use the Troubleshooting Guides (See Tables 10--12) if problems
occur with these units.
START--UP CHECKLIST
Use Start--Up checklist to ensure proper start--up procedures are
followed.
3. Place terry cloth shop towel inside unit immediately under
component(s) to be serviced and prevent lubricant run--offs
through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil contaminated material per
local codes.
PURONR (R--410A) QUICK REFERENCE GUIDE
S
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S
S
S
Puron refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard.
Use hoses with minimum 700 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquid--line filter driers with rated working pressures less than 600 psig.
Do not leave Puron suction line filter driers in line longer than 72 hrs.
Do not install a suction--line filter drier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter driers and service valves with wet cloth when brazing.
A factory approved liquid--line filter drier is required on every unit.
Do NOT use an R--22 TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S
S
S
Do not vent Puron into the atmosphere.
Observe all warnings, cautions, and bold text.
All indoor coils must be installed with a hard shutoff Puron TXV metering device.
34
Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode
SYMPTOM
CAUSE
REMEDY
Power Failure
Call power company.
Replace fuse or reset circuit breaker.
Fuse blown or circuit breaker tripped
Defective thermostat, contactor, transformer, or control
relay
Compressor and Outdoor fan will not
start.
Replace component.
Insufficient line voltage
Determine cause and correct.
Incorrect or faulty wiring
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Thermostat setting too high
Faulty wiring or loose connections in compressor circuit
Compressor motor burned out, seized, or internal over-
load open
Determine cause Replace compressor.
Compressor will not start but Outdoor
fan runs.
Defective run/start capacitor, overload, start relay
Determine cause and replace.
Replace fuse or reset circuit breaker. Determine
cause.
One leg of 3---phase power dead
Three---phase scroll compressor makes
excessive noise, and there may
be a low pressure differential.
Correct the direction of rotation by reversing the
3---phase power leads to the unit.
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and recharge
to capacities shown on nameplate.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Defective compressor
Insufficient line voltage
Compressor cycles (other than normally
satisfying thermostat).
Blocked Outdoor
Defective run/start capacitor, overload or start relay
Defective thermostat
Faulty Outdoor---fan motor or capacitor
Damaged reversing valve
Restriction in refrigerant system
Dirty air filter
Replace.
Determine cause and correct
Locate restriction and remove.
Replace filter.
Unit undersized for load
Thermostat set too low
Low refrigerant charge
Mechanical damage in compressor.
Air in system
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Check defrost time settings, Reset as necessary
Check defrost temperature switch, Replace as nec-
essary
Compressor operates continuously.
Excessive head pressure.
Frosted coil with incorrect defrost operation
Outdoor coil dirty or restricted
Dirty air filter
Dirty Indoor or Outdoor coil
Refrigerant overcharged
Air in system
Indoor or Outdoor air restricted or air short---cycling
Low refrigerant charge
Compressor IPR leaking
Restriction in liquid tube
High heat load
Compressor IPR leaking
Refrigerant overcharged
Reversing valve hung up or leaking internally
Dirty air filter
Low refrigerant charge
Metering device or low side restricted
Clean coil or remove restriction .
Replace filter.
Clean coil.
Recover excess refrigerant.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks, repair, and recharge.
Replace compressor.
Head pressure too low.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Excessive suction pressure.
Recover excess refrigerant.
Replace valve
Replace Filter.
Check for leaks, repair, and recharge.
Remove source of restriction.
Increase air quantity. Check filter — replace if neces-
sary.
Insufficient Indoor airflow
Suction pressure too low.
Temperature too low in conditioned area
Outdoor ambient below 55°F (12.8°C)
Field---installed filter---drier restricted
Reset thermostat.
Install low---ambient kit.
Replace.
Move timer on control board to 30 minutes between
defrost cycles
(Heat) Outdoor coil frosted
Compressor runs but outdoor fan does
not
Check condition of relay on board Replace if neces-
sary
NC (normally closed) contacts on defrost board open
35
Table 12 – Troubleshooting Guide–Heating
SYMPTOM
CAUSE
REMEDY
Water in gas line
Drain. Install drip leg.
No power to furnace
Check power supply fuses, wiring or circuit breaker.
Check transformer.
NOTE: Some transformers have internal over--current protection
that requires a cool--down period to reset.
No 24--v power supply to control circuit
Burners will not ignite
Mis--wired or loose connections
Misaligned spark electrodes
Check all wiring and wire nut connections
Check flame ignition and sense electrode positioning.
Adjust as necessary.
1. Check gas line for air. Purge as necessary. NOTE: After purging
gas line of air, wait at least 5 minutes for any gas to dissipate be-
fore attempting to light unit.
No gas at main burners
2. Check gas valve.
Dirty air filter
Clean or replace filter as necessary
Gas input to furnace too low
Unit undersized for application
Restricted airflow
Check gas pressure at manifold match with that on unit nameplate
Replace with proper unit or add additional unit
Clean or replace filter. Remove any restriction.
Inadequate heating
Check rotation of blower, temperature rise of unit. Adjust as neces-
sary.
Limit switch cycles main burners
1. Tighten all screws around burner compartment
2. Cracked heat exchanger. Replace.
3. Unit over--fired. Reduce input (change orifices or adjust gas line
or manifold pressure).
4. Check burner alignment.
Incomplete combustion results in: Aldehyde odors,
carbon monoxide, sooting flame, floating flame
Poor flame characteristics
5. Inspect heat exchanger for blockage. Clean as necessary.
Table 13 – Troubleshooting Guide–LED Error Codes
SYMPTOM
CAUSE
REMEDY
Check 5--amp fuse son IGC*, power to unit, 24--v circuit breaker,
and transformer. Units without a 24--v circuit breaker have an
internal overload in the 24--v transformer. If the overload trips,
allow 10 minutes for automatic reset.
No Power or Hardware fail-
ure
(LED OFF)
Loss of power to control module (IGC)*.
Check the operation of the indoor (evaporator) fan motor. Ensure
that the supply--air temperature rise is in accordance with the
range on the unit nameplate. Clean or replace filters.
Limit switch faults
(LED 2 flashes)
High temperature limit switch is open.
The IGC* sensed flame that should not be present.
Inadequate airflow to unit.
Flame sense fault
(LED 3 flashes)
Reset unit. If problem persists, replace control board.
4 consecutive limit switch
faults
(LED 4 flashes)
Check the operation of the indoor (evaporator) fan motor and that
supply--air temperature rise agrees with range on unit nameplate
information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that fame sense and ignition wires are properly terminated.
Verify that unit is obtaining proper amount of gas.
Verify wiring connections to pressure switch and inducer motor.
Verify pressure switch hose is tightly connected to both inducer
housing and pressure switch. Verify inducer wheel is properly
attached to inducer motor shaft. Verify inducer motor shaft is turn-
ing.
Ignition lockout
(LED 5 flashes)
Unit unsuccessfully attempted ignition for 15 minutes.
Open pressure switch.
Pressure Switch Fault
(LED 6 flashes)
Rollout switch will automatically reset, but IGC* will continue to
lockout unit. Check gas valve operation. Ensure that induced--draft
blower wheel is properly secured to motor shaft. Inspect heat
exchanger. Reset unit at unit disconnect.
Rollout switch fault
(LED 7 flashes)
Rollout switch has opened.
Internal control fault
(LED 8 flashes)
Microprocessor has sensed an error in the software
or hardware.
If error code is not cleared by resetting unit power, replace the
IGC*.
Temporary 1 hr auto reset
(LED 9 flashes)
Reset 24--v. to control board or turn thermostat off, then on again.
Fault will automatically reset itself in one (1) hour.
Electrical interference impeding IGC software
*WARNING
: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control
board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to Table 11---Troubleshooting Guide---Heating for additional troubleshooting analysis.
LEGEND
IGC—Integrated Gas Unit Controller
LED—Light---Emitting Diode
36
START--UP CHECKLIST
(Remove and Store in Job Files)
I. PRELIMINARY INFORMATION
MODEL NO.:
SERIAL NO.:
DATE:
TECHNICIAN:
II. PRESTART--UP (Insert check mark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
III. START--UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS
INDOOR (EVAPORATOR) FAN AMPS
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE
RETURN--AIR TEMPERATURE
DB
DB
WB
COOLING SUPPLY AIR
DB
WB
HEAT PUMP SUPPLY AIR__________________
GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE
IN. W.C.
GAS MANIFOLD PRESSURE
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
IN. W.C.
PSIG, SUCTION LINE TEMP*
PSIG, LIQUID TEMP{
( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GAS HEAT TEMPERATURE RISE
TEMPERATURE RISE (See Literature) RANGE
MEASURED TEMPERATURE RISE
* Measured at suction inlet to compressor
{
Measured at liquid line leaving condenser.
37
Catalog No: 48EZ---06SI
Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 08/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 48EZ---05SI
38
|