40RU
Packaged Air---Handling Units
60 Hz
With PuronR (R---410A) Refrigerant
Sizes 25, 28, 30
Installation, Start---Up and
Service Instructions
Chilled Water Coil Freeze Protection . . . . . . . . . . . 26
TABLE OF CONTENTS
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . 26
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . 39-40
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 2
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . 2–22
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant and Chilled Water Piping Access . . . . . 13
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . 17
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . 18
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . 19
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . 21
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 21
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23–36
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fan Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Position Adjustment . . . . . . . . . . . . . . . . 24
Individual Fan Wheel Adjustment . . . . . . . . . . . . . . 25
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . 25
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . 25
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual
instructions package
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Table 1A — 40RUA Physical Data, English — Cooling Units
UNIT 40RUA*
25
28
30
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
20
25
30
730
225
1050
325
1062
325
FANS
Qty...Diam. (in.)
2...15
8000
2...18
10000
2...18
12000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
6000 – 10000
7500 – 12500
9000 – 15000
5.0
5.0
7.5
7.5
10.0
10.0
Motor Speed (rpm)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
1745
1745
1745
1755
1745
1755
REFRIGERANT
R---410A
Operating charge (lb)
3.5
4.5
5.0
{
(approx per circuit)
DIRECT---EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
650
19.88
2
24.86
29.83
2
No. of Splits
2
20
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/in.
18
24
Face...50/50
4...15
4...15
4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
1
3
3
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
2...1 /
2...1 /
5
2...1 /
8
8
2
8
2... /
1
8
1...2 /
1
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1... /
2
1...2
1...2
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Quantity...Size (in.)
Access Location
Either Side
}
STEAM COIL
Max Working Pressure (psig at 260° F)
Total Face Area (sq ft)
20
13.33
1...10
15.0
1...10
15.0
Rows...Fins/in.
1...10
}
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
150
15.0
13.33
15.0
2...8.5
2...12.5
2...12.5
Water Volume
(gal)
13.9
14.3
1.90
3
(ft )
LEGEND
DX — Direct Expansion
TXV— Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
Field installed accessory only.
}
3
Table 1B — 40RUA Physical Data, SI — Cooling Units
UNIT 40RUA*
25
28
30
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
70
87
105
331
102
477
148
482
148
FANS
Qty...Diam. (mm)
2...381
3775
2...457
4119
2...457
5663
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
2831 – 4719
3539 – 5899
4247 – 7079
3.73
3.73
5.60
5.60
7.46
7.46
Motor Speed (r/s)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
29.1
29.1
29.1
29.3
29.1
29.3
REFRIGERANT
R---410A
Operating charge (kg)
1.59
2.04
2.27
{
(approx per circuit)
DIRECT---EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
4481
1.85
2
2.30
2
2.77
2
No. of Splits
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/m
18
20
24
Face...50/50
4...591
4...591
4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
1
3
3
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
2...1 /
2...1 /
5
2...1 /
8
8
2
8
2... /
1
8
1...2 /
1
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1... /
2
1...2
1...2
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 610 x 51
4...508 x 635 x 51
Either Side
Quantity...Size (mm.)
Access Location
}
STEAM COIL
Max Working Pressure (kPag at 126° C)
Total Face Area (sq m)
138
1.39
1.24
1.39
Rows...Fins/m
1...394
1...394
1...394
}
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
1034
1.39
1.24
1.39
2...335
2...335
2...335
Water Volume
(L)
52.6
54.1
3
(m )
0.052
0.054
LEGEND
DX — Direct Expansion
TXV— Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
Field installed accessory only.
}
4
Table 1C — 40RUQ Physical Data, English — Heat Pump Units
UNIT 40RUQ*
25
NOMINAL CAPACITY (Tons)
20
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
720
140
FANS
Qty...Diam. (in.)
2...15
8000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
6000---10000
5.0
5.0
Motor Speed (rpm)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
1745
1745
REFRIGERANT
R---410A
3.5/3.5
Operating charge (lb)
(approx per circuit)
{
DIRECT---EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
650
19.9
No. of Splits
2
2
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/in.
Face....50/50
4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
1/
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
2...1
8
5/
2...
8
1/
1...2
1...1
2
2
1/
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...2
1...2
1/
1...1 ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.)
4...16 x 20 x 2
4...16 x 24 x 2
Access Location
Right or Left Side
}
STEAM COIL
Max Working Pressure (psig at 260° F)
Total Face Area (sq ft)
20
13.33
1...10
Rows...Fins/in.
}
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
150
13.33
2...8.5
Water Volume
(gal)
13.9
1.85
3
(ft )
LEGEND
DX — Direct Expansion
TXV— Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
Field installed accessory only.
}
5
Table 1D — 40RUA Physical Data, SI — Heat Pump Units
UNIT 40RUQ*
25
NOMINAL CAPACITY (kW)
70
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
326
44
FANS
Qty...Diam. (mm)
2...381
3775
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
2831---4719
3.73
3.73
Motor Speed (r/s)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
29.1
29.1
REFRIGERANT
R---410A
1.59/1.59
Operating charge (kg)
(approx per circuit)
{
DIRECT---EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
4482
1.85
No. of Splits
2
No. of Circuits per Split
Split Type...Percentage
Fins/m
2
Face...50/50
591
PIPING CONNECTIONS,
Quantity...Size (in.)
1/
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
2...1
8
5/
2...
8
1/
1...2
1...1
2
2
1/
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...2
1...2
1/
1...1 ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...406 x 610 x 51
4...406 x 508 x 51
Quantity...Size (mm)
Access Location
Right or Left Side
}
STEAM COIL
Max Working Pressure (kPag at 126° C)
Total Face Area (sq m)
138
1.24
Rows...Fins/m
1...394
}
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
1034
1.24
2...335
Water Volume
(L)
52.6
3
(m )
0.052
LEGEND
DX — Direct Expansion
TXV— Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
Field installed accessory only.
}
6
Table 1E — 40RUS Physical Data, English — Chilled Water Units
UNIT 40RUS*
25
28
30
NOMINAL CAPACITY (Tons)
20
25
30
OPERATING WEIGHT (lb)
Base Unit
683
225
1035
325
1042
325
Plenum
FANS
Qty...Diam. (in.)
2...15
8000
2...18
10000
2...18
12000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
6000 – 10000
7500 – 12500
9000 – 15000
5.0
5.0
7.5
7.5
10.0
10.0
Motor Speed (rpm)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
1745
1745
1745
1755
1745
1755
CHILLED WATER COIL
Max Working Pressure (psig)
Face Area (sq ft) – Upper
Face Area (sq ft) – Lower
Rows...Fins/in.
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
435
11.0
8.3
12.4
12.4
15.5
12.4
3...15
PIPING CONNECTIONS,
Quantity...Size (in.)
.
3
1
2...21/ ODM
8
Chilled Water — In
2...1 / ODM
8
2...2 / ODM
8
2...21/ ODM
8
2...21/ ODM
8
2...21/ ODM
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
8
1
1...2 /
2
2
1
1...1 /
1...2
1...2
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Quantity...Size (in.)
Access Location
Either Side
}
STEAM COIL
Max Working Pressure (psig at 260° F)
Total Face Area (sq ft)
20
13.33
1...10
15.0
1...10
15.0
Rows...Fins/in.
1...10
}
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
150
15.0
13.33
15.0
2...8.5
2...12.5
2...12.5
Water Volume
(gal)
13.9
1.1
14.3
1.90
3
(ft )
LEGEND
}
Field installed accessory only.
7
Table 1F — 40RUS Physical Data, SI — Chilled Water Units
UNIT 40RUS*
25
28
30
NOMINAL CAPACITY (kW)
70
87
105
OPERATING WEIGHT (kg)
Base Unit
Plenum
310
102
469
148
473
148
FANS
Qty...Diam. (mm)
2...381
3775
2831 – 4719
2...457
4719
3539 – 5899
2...457
5663
4247 – 7079
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
3.73
3.73
5.60
5.60
7.46
7.46
Motor Speed (r/s)
208/230---3---60 and 460---3---60
5 7 5 --- 3 --- 6 0
29.1
29.1
29.1
29.3
29.1
29.3
CHILLED WATER COIL
Max Working Pressure (kPag)
Face Area (sq m) – Upper
Face Area (sq m) – Lower
Rows...Fins/m
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
2999
1.02
0.77
1.15
1.15
1.44
1.15
3...591
3...591
3...591
PIPING CONNECTIONS,
Quantity...Size (in.)
3
1
1
Chilled Water — In
2...1 / ODM
8
2...2 / ODM
8
2...2 / ODM
8
3
1
1
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
2...1 / ODM
2...2 / ODM
8
2...2 / ODM
8
8
1
1...2 /
1...1 /
1...2
1...2
2
2
1
1
1...1 / ODM/1 IDF
4
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 610 x 51
4...508 x 635 x 51
Quantity...Size (mm.)
Access Location
Either Side
}
STEAM COIL
Max Working Pressure (kPag at 125° C)
Total Face Area (sq m)
138
1.39
1.24
1.39
Rows...Fins/m
1...394
1...394
1...394
}
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
1034
1.39
2..493
1.24
2...335
1.39
2...493
52.6
54.1
(m3)
0.052
0.054
LEGEND
}
Field installed accessory only.
8
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
UNIT WEIGHT
UNIT
lb (kg)
40RUA*25
40RUQ*25
40RUS*25
730 (331)
720 (326)
683 (310)
C10722
Fig. 1 - Dimensions – Size 25
9
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RUS may require alternate or additional
field favricated poping access holes
UNIT WEIGHT
UNIT
lb (kg)
40RUA*28
40RUA*30
40RUS*28
40RUS*30
1050 (477)
1062 (482)
1035 (469)
1042 (473)
C10723
Fig. 2 - Dimensions – Sizes 28 and 30
10
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18
4
0
R
U
A
A
2
5
A
1
A
6
–
0
A
0
A
0
_____________
____
Model Type
Brand / Packaging
40RU = Carrier Fan Coil
Puronr R–410ARefrigerant
0 = Standard
Not Used
A = Place Holder
Type of Coil
A = StandardDXCoil
Q = Heat Pump
Service Options
S = Chilled Water Coil
0 = Non-Painted Cabinet
1 = Painted Cabinet
Refrigerant Options
A = None
Not Used
A = Place Holder
Nominal Tonnage
25 = 20 Tons
28 = 25 Tons
30 = 30 Tons
Not Used
0 = Place Holder
Design Rev
Not Used
A = Place Holder
– = Catalog Model Number
1 = Design Revision (original)
Indoor Fan Options
Voltage
1 = Fan Drive and Motor - Low / Motor Efficiency - Standard
2 = Fan Drive and Motor - Med / Motor Efficiency - Standard
3 = Fan Drive and Motor - High / Motor Efficiency - Standard
1 = 575/3/60
5 = 208/230/3/60
6 = 460/3/60
Coil Options
A = Al/Cu
C!0724
Fig. 3 - Model Number Nomenclature
POSITION NUMBER
TYPICAL
1
2
2
6
3
1
4
0
5
G
6
1
7
2
8
3
9
4
10
5
POSITION
1−2
DESIGNATES
Week of manufacture (fiscal calendar)
3−4
Year of manufacture (“10” = 2010)
5
Manufacturing location (G = ETP, Texas, USA)
Sequential number
6−10
C!0725
Fig. 4 - Serial Number Nomenclature
TXV
COIL
horizontal arrangement with return air entering
horizontally and the supply air discharging horizontally.
When applying the unit in a horizontal arrangement,
ensure the condensate drain pan is located at the bottom
center of the unit for adequate condensate disposal. See
Fig. 6 for condensate connections for each unit position.
PLUG
PLUG
CONDENSATE
DRAIN
REMOVE FOAM BLOCK
LEGEND
LEGEND
TXV — Thermostatic Expansion Valve
Accessory Line
C10683
Alternate Air Intake and Discharge
Fig. 5 - Foam Block Location
Air Intake and Discharge
Note: Maintain recommended clearances
Unit Positioning - The unit can be mounted on the floor
for vertical application with return air entering the face of
the unit and supply air discharging vertically through the
top of the unit. The unit can also be applied in a
per Fig. 1 and Fig. 2
C10684
Fig. 6 - Typical Unit Positioning
11
Typical positioning and alternate return air locations are
shown in Fig. 6. Alternate return air locations can be used
by moving the unit panel from the alternate return air
location to the standard return air location. Refer to
overhead suspension accessory drawing (Fig. 7) for
preferred suspension technique. The unit needs support
underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain from
unit.
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZE 25
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZES 28, 30
NOTE: Dimensions in [ ] are millimeters
C10728
Fig. 7 - Preferred Suspension Technique
12
Unit Isolation - Where extremely quiet operation is
essential, install isolators between floor and base of unit,
or between ceiling and top section of unit.
The 40RU direct-expansion units have internal
factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-410A. See Table
2 for part numbers. Knockouts are provided in the unit
corner posts for 40RU refrigerant piping. See Fig. 8,
which also lists recommended knockouts and access holes
to use for each 40RU unit size. Recommended fittings are
listed in Table 3.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points
when leveling.
Refrigerant and Chilled Water Piping Access - The
40RU Series units come with standard knockouts for
refrigerant and chilled water piping. These knockouts are
located on both sides of the unit for installation flexibility.
The standard knockouts provide sufficient access to the
unit’s coils for all 40RUA*25, 28, and 30 units.
40RUQ*25 units, as well as 40RUS*25, 28, and 30 units
require additional holes which must be field-fabricated to
accommodate the piping. See Fig. 8 for the positions and
dimensions of the additional access holes required for
40RUQ and 40RUS units. Recommended access hole use
is also listed for all units. Note that Fig. 8 shows the
access holes on the control-box side of the unit; this is the
side of the unit with the coil headers, so it is used most
often for piping access.
The sensor bulb capillary tubes must be routed from the
TXVs inside the unit through one of the piping access
holes. Clamp the TXV sensor bulb on a vertical portion of
the suction line, outside the unit. See Fig. 9.
NOTE: Be sure to remove the styrofoam shipping pad
from the TXV. Verify that it has been removed. See Fig. 5.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 40RU Series evaporator coils have a face-split
design. Ensure that lower circuit of coil is first on/last off
when connected to the condensing unit and/or system
controls. See Fig. 10.
IMPORTANT: Do not bury refrigerant piping
underground.
External TXV equalizer connections are provided and
factory-brazed into the coil suction manifolds.
Refrigerant Piping - See Tables 1A–1F for refrigerant
pipe connection sizes. For ease in brazing, it is
recommended that all internal solder joints be made
before unit is placed in final position.
If suction line must be horizontal, clamp bulb to suction
line at least 45 degrees above bottom, at approximately
the 4 o’clock or 8 o’clock position. See Fig.11.
8
7
6
5
4
D
C
B
A
3
2
1
C10727
FIELD--FABRICATED HOLE DIAMATERS
in. (mm)
FIELD--FABRICATED HOLE POSITION DIMENSIONS
in. (mm)
USE HOLE
NUMBERS
UNIT
No. 5
No. 6
No. 7
No. 8
—
A
—
B
—
C
—
D
40RUA*25, 28, 30
40RUS*25
1,2, 3, 4
4, 5, 6, 7
—
—
—
—
—
3
3
3
1 / (44.5)
4
1 / (44.5)
4
1 / (44.5)
4
—
3.0 (76.2)
6.0 (152.5)
10.5 (266.7)
{
1
1
3
40RUQ*25
3 , 5, 6, 7
1 / (28.6)
8
1 / (28.6)
8
1 / (44.5)
4
—
3.25 (82.6) 6.125 (155.6) 10.38 (263.7)
6.0 (152.5) 9.625 (244.5) 13.38 (339.9) 17.0 (431.8)
1
1
1
1
40RUS*28, 30
5, 6, 7, 8
2 / (63.5)
2
2 / (63.5)
2 / (63.5)
2 / (63.5)
2
2
2
{
1
3
Must be enlarged from 1 / in. (28.6mm) to 1 / in. (44.5mm)
8
4
N OTE : A cce ss ho l e k no ck o ut s 1 --- 4 a re f a ct o ry --- sup p l i e d .
Fig. 8 - Refrigerant and Chilled Water Piping Access Holes
13
EQUALIZER LINE
TXV
UPPER
SPLIT
SENSING
BULB
SOLENOID
VALVE
SIGHT
GLASS
TXV
AIRFLOW
15 DIAMS
MIN
10
DIAMS
8 DIAMS
MIN
EQUALIZER
FILTER
DRIER
LINE
TXV
SENSING
BULB
LOWER
SPLIT
TXV
AIRFLOW
15 DIAMS
MIN
10
DIAMS
8 DIAMS
MIN
INDOOR
COIL
LEGEND:
TXV – Thermostatic Expansion Valve
NOTE: Component location arrangemetshown for field installation of
sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equilizer lines are factory installed.
C10726
Fig. 9 - Face-Split Coil Suction and Liquid Line Piping (Typical)
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.
FIRST ON/LAST OFF = B
VERTICAL INSTALLATION
C10689
Fig. 11 - TXV Sensing Bulb Location
FIRST ON/LAST OFF = A
HORIZONTAL INSTALLATION
C10688
Fig. 10 - Typical Evaporator Coil Connections (40RU)
14
Table 2 – Factory-Installed Nozzle and Distributor Data
FEEDER TUBES
PER DISTRIBUTOR{
Qty...Size (in.)
COIL TYPE
STD
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
NOZZLE
Qty...Part No.
UNIT
3
3
40RUA*25
40RUA*28
40RUA*30
40RUQ*25
4 Row
4 Row
4 Row
4 Row
2 . . . B B IZ E --- 8 --- G A
2 . . . B B IZ E --- 1 5 --- G A
2 . . . B B IZ E --- 1 5 --- G A
2 . . . B B IZ E --- 1 2 . 5 --- G A
2...D196---18--- /
2...1126
18... /
2...G6
2...C15
2...C17
2...G8
16
16
16
16
3
20... /
3
2...1126
3
24... /
3
2...113---12--- /
2 --- 1 2 . . . /
16
16
{
1
Feeder tube size is
/
in. (6.35 mm).
4
NOTE: Hot gas bypass applications require field---supplied auxiliary side connector.
Table 3 – Fitting Requirements
†
ACCESS
HOLE NO.
CONNECTION
FITTINGS REQUIRED
UNIT
CIRCUIT
}
TYPE
(in.)
1
1 / Street Elbow
8
1
5
1 / Nipple, 7 /
8
L
1
2
3
Suction
Lower
Lower
Upper
8
1
1 / Long Radius Elbow
8
5
/
/
/
/
/
/
Street Elbow
1
8
8
8
8
8
8
5
5
5
5
5
Nipple, 6 /
L
Liquid
Liquid
2
Long Radius Elbow
Street Elbow
1
40RUA*25
Nipple, 9 /
L
2
Long Radius Elbow
5
1
1 / Nipple, 5 /
8
L
8
1
1 / Long Radius Elbow
8
4
Suction
Upper
1
1 / Nipple, 11 L
8
1
1 / Long Radius Elbow
8
1
1 / Nipple, 3 L
8
3
5
Suction
Suction
Lower
Lower
11/ Long Radius Elbow
8
5
5
5
5
5
5
5
5
7
/
/
/
/
/
/
/
/
Nipple, 2 / L
8
8
8
8
8
8
8
8
8
45_ Elbow
5
Nipple, 1 / L
8
Long Radius Elbow
7
Nipple, 2 / L
8
40RUQ*25
45_ Elbow
6
7
Liquid
Upper
Upper
1
Nipple, 4 / L
4
Long Radius Elbow
1
1 / Nipple, 5 L
8
1
1 / 45_ Elbow
8
Suction
1
3
1 / Nipple, 8 /
8
L
4
1
1 / Long Radius Elbow
8
3
1 / Long Radius Elbow
8
3
3
1 / Nipple, 3 / L
8
4
4
5
6
7
Supply
Return
Return
Supply
Lower
Lower
Upper
Upper
3
1 / Long Radius Elbow
8
3
1 / Long Radius Elbow
8
3
3
1 / Nipple, 3 /
8
L
8
3
1 / Long Radius Elbow
8
40RUS*25
3
1 / Long Radius Elbow
8
3
1 / Nipple, 7 L
8
3
1 / Long Radius Elbow
8
3
1 / Long Radius Elbow
8
3
3
1 / Nipple, 11 /
L
8
4
11/ Long Radius Elbow
8
}
See Fig. 8 for access hole location by number.
Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
†
15
Table 3 — Fitting Requirement (cont)
†
ACCESS
HOLE NO.
CONNECTION
CIRCUIT
TYPE
FITTINGS REQUIRED
(in.)
UNIT
}
3
1 / Street Elbow
8
3
1 / Nipple, 11 L
8
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
3
1 / Long Radius Elbow
8
5
/
/
/
/
/
/
Street Elbow
1
8
8
8
8
8
8
5
5
5
5
5
Nipple, 1 /
L
2
Long Radius Elbow
Street Elbow
1
40RUA*28
Nipple, 19 /
L
2
Long Radius Elbow
3
3
1 / Nipple, 4 /
8
L
16
3
1 / Long Radius Elbow
8
4
Suction
Upper
3
1
1 / Nipple, 23 /
8
L
4
3
1 / Long Radius Elbow
8
1
2 / Long Radius Elbow
8
1
1
2 / Nipple, 3 / L
5
6
7
8
1
2
3
Supply
Return
Return
Supply
Suction
Liquid
Lower
Lower
Upper
Upper
Lower
Lower
Upper
8
2
1
2 / Long Radius Elbow
8
1
2 / Long Radius Elbow
8
1
2 / Nipple, 3 L
8
1
2 / Long Radius Elbow
8
40RUS*28, 30
1
2 / Long Radius Elbow
8
1
7
2 / Nipple, 6 /
8
L
8
1
2 / Long Radius Elbow
8
1
2 / Long Radius Elbow
8
1
7
2 / Nipple, 11 /
8
L
8
1
2 / Long Radius Elbow
8
3
1 / Street Elbow
8
3
1 / Nipple, 3 L
8
3
1 / Long Radius Elbow
8
5
/
/
/
/
/
/
Street Elbow
3
8
8
8
8
8
8
5
5
5
5
5
Nipple, 7 /
L
4
Long Radius Elbow
Street Elbow
1
40RUA*30
Nipple, 18 /
L
Liquid
2
Long Radius Elbow
3
3
1 / Nipple, 4 /
8
L
16
3
1 / Long Radius Elbow
8
4
Suction
Upper
3
1
1 / Nipple, 19 /
8
L
4
3
1 / Long Radius Elbow
8
}
See Fig. 8 for access hole location by number.
Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
†
16
Chilled Water Piping - See Tables 1E and 1F for chilled
water connection sizes. For ease in brazing, it it
recommended that all internal solder joints be made
before unit is placed in final position.
To size, design, and install chilled water piping, consult
the Carrier System Design manual. See Fig. 12 for an
example of a typical installation. Recommended fittings
are listed in Table 3.
Knockouts are provided in the unit corner posts for
40RUS refrigerant piping. Additional field-fabricated
access holes are required for 40RUS chilled water piping.
See Fig. 8, which lists recommended knockouts and
access holes to use for each 40RUS unit size.
To access 40RUS coil vents and drains, remove the unit
side panel over the coil header. Vent and drain plugs are
on the top and bottom of header, respectively. See the
Service section for information on preventing coil
freeze-up during winter.
C10690
Fig. 12 - Typical 40RUS Chilled Water Piping
17
Condensate Drain - Install a trapped condensate drain
line to unit connection as shown in Fig. 13. The unit drain
connection is a PVC stub. See Fig. 14. Some areas may
require an adapter to connect to either galvanized steel or
copper pipe. For these applications, install
a
field-supplied threaded PVC adapter.
3” MIN.
[76]
C10692
Fig. 14 - Drain Pan Slope Adjustment
As shipped, the unit’s condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be
changed to pitch towards the side of the unit with the
drain connection. See Fig. 14. Loosen the 2 screws next to
the drain outlet at both ends of the unit, push drain pan
down in the slots near the drain connection, and up in the
slots on the opposite end. Re-tighten screws. The pan
should have a pitch of at least 1/4 -in. over its length
toward the drain connection.
NOTE: Dimensions in [ ] are in millimeters
Fan Motors and Drives - Motor and drive packages are
factory installed in all units. The motor and drive
packages consist of the following items:
C10691
Fig. 13 - Condensate Drains
1 — fan motor
NOTE: A trap must be installed in the condensate drain
line to ensure that the static pressure of fans is balanced with
the water column in the drain line and that condensate can
drain completely from pan. Without a trap, air can be drawn
up drain line until water level in condensate pan becomes
equal to static pressure created by fans, preventing complete
drainage. Conditions will worsen as filters become dirty.
1 — adjustable motor pulley
1 — fan pulley
2 — matched fan belts
(40RUA*25-30, 40RUQ*25, 40RUS*25-30 units)
For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive
Adjustment in the Service section.
Install clean-out plugs in trap. Pitch drain line downward
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels.
Observe all local sanitary codes.
18
Power Supply and Wiring - Check the unit data plate to
ensure that available power supply matches electrical
characteristics of the unit. Provide a disconnect switch
with an integrated lock-out feature of size required to
provide adequate fan motor starting current. See Tables
4-6 for unit electrical data.
FAN SCROLL
FAN
CONTACTOR
BOX
MOTOR
AND DRIVE
WIRE
ACCESS
FAN DRIVE
PULLEY
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
!
WARNING
COIL
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
FILTER
ELEMENTS
TXV BULB
ACCESS
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
REFRIGERANT
PIPING ACCESS
FILTER
RETAINER
CLIP
CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)
LEGEND
TXV — Thermostatic Expansion Valve
C10693
Fig. 16 - Wiring and Service Access
(Side Panel Removed)
Fan motors are factory-installed on all units. Indoor-fan
contactors are located in the fan contactor box behind the
side access panel (see Fig. 16 and 17). Wire the thermostat
to the 24-v control circuit terminal block located in the
side of the fan contactor control box, according to Fig. 18
or the unit label diagram. If the air handler is part of a
split system, complete the wiring from the condensing
unit to the thermostat shown in Fig. 18.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and fan coil unit. Use only copper wire.
(See Fig. 15)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
W
ALUMINUM
WIRE
FAN
CONTACTOR
A93033
24V
TERMINAL
BLOCK
Fig. 15 - Disconnect Switch and Unit
POWER
Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 15-17 and the
unit label diagram. Connect power wiring with /4 - i n .
WIRING
KNOCKOUT
1
C10694
Fig. 17 - Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
ring terminal.
19
Table 4 – Electrical Data, Standard Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
{
UNIT
V --- P H --- H z
Minimum
LIMITS
Hp (kW)
FLA
MOCP
Circuit Amps
18.4/17.0
8.5
208/230---3---60
4 6 0 --- 3 --- 6 0
187---253
414---506
518---632
187---253
414---506
518---632
187---253
414---506
518---632
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
14.7/13.6
6.8
30/25
15
40RUA*25
40RUQ*25
40RUS*25
5 7 5 --- 3 --- 6 0
5.1
6.4
15
208/230---3---60
4 6 0 --- 3 --- 6 0
21.4/19.4
9.7
26.9/24.3
12.1
45/40
20
40RUA*28
40RUS*28
5 7 5 --- 3 --- 6 0
7.8
9.8
15
208/230---3---60
4 6 0 --- 3 --- 6 0
28.0/25.2
12.6
35.0/31.5
15.8
60/50
25
40RUA30
40RUS30
5 7 5 --- 3 --- 6 0
10.3
12.9
20
See Legend and Notes below.
Table 5 – Electrical Data, Alternate Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
{
UNIT
V --- P H --- H z
Minimum
LIMITS
Hp (kW)
FLA
MOCP
Circuit Amps
208/230---3---60
4 6 0 --- 3 --- 6 0
187---253
414---506
518---632
187---253
414---506
518---632
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
21.4/19.4
9.7
26.9/24.3
12.1
45/40
20
40RUA*25
40RUQ*25
40RUS*25
5 7 5 --- 3 --- 6 0
7.8
9.8
15
208/230---3---60
4 6 0 --- 3 --- 6 0
28.0/25.2
12.6
35.0/31.5
15.8
60/50
25
40RUA*28
40RUA*30
40RUS*28
40RUS*30
5 7 5 --- 3 --- 6 0
10.3
12.9
20
See Legend and Notes below.
Legend and Notes for Tables 4 and 5
LEGEND:
Example: Supply voltage is 230-3-60
F L A
--- Fu ll L o a d A m p s
max voltage deviation from average voltage
average voltage
MOCP --- Maximum Overcurrent Protection
% Voltage Imbalance = 100 x
{
Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits
shown in the Voltage Limits column.
AB = 393 v
BC = 403 v
AC = 396 v
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calcu-
lated in accordance with The NEC. Article 440.
(393 + 403 + 396)
1192
3
Average Voltage =
=
=
2. Motor FLA values are established in accordance with Under-
writers’ Laboratories (UL). Standard 1995.
3
397
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the formula in the example
(see column to the right) to determine the percentage of volt-
age imbalance.
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the
40RU indoor fan motor per NEC Article 430---28 (1) or (2)
(depends on length of conduit between heater enclosure and
40RU power entry location). Install wires in field---installed
conduit.
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
6
% Voltage Imbalance
= 100 x
= 1.5%
397
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
20
C10695
Fig. 18 - Unit Wiring
Table 6 – Fan Contactor Coil Data
installation. Using the existing screws, install the duct
flanges on the unit’s fan deck. Each fan discharge requires
2 flanges; each flange must be bent in the middle to
conform to the discharge opening. See Fig. 20. After
flanges are installed, connect them to the supply duct
using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to
prevent high air friction losses and air noise.
UNIT
40RU*
VOLTAGE
(vac)
MAXIMUM
HOLDING VA
25, 28, 30
24
10
Connecting Ductwork - Refer to the Carrier System
Design Manual for the recommended design and layout of
ductwork. Fig. 19 shows recommended duct connection to
units with 2 fans.
RETURN CONNECTIONS — When using return-air
ductwork, route return-air duct to the unit’s return air inlet
near the filter rack, using a canvas connection to prevent
transmission of unit vibration. If the duct blocks off the
unit’s access panel, provide a slip joint in the ductwork to
permit removal for servicing.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without ductwork or discharge
plenum unless fan speed has been adjusted for
external static pressure of zero in. wg. Failure to do so
may result in motor overload.
OUTDOOR-AIR INLET CONNECTIONS — Connect
outdoor-air inlet to field-installed accessory economizer.
Refer to Economizer Installation Instructions.
Return-Air Filters - Type and size of filters are shown
in Tables 1A – 1F and are factory-supplied and
factory-installed. In all units with 2 fans, a filter
replacement tool (hook) is shipped inside the unit for field
use when replacing filters. See the Service section for
instructions on filter element replacement.
DISCHARGE CONNECTIONS — Duct flanges are
factory-supplied; they are shipped inside the unit attached
to the hairpin end of the coil tube sheet for field
21
C10696
Fig. 19 - Typical Fan Discharge Connections for Multiple Fan Units
C10697
Fig. 20 - Duct Flange Installation
22
2. To increase superheat, turn the stem clockwise. To de-
crease the superheat, turn the stem counterclockwise.
Do not turn the stem more than one full turn.
3. Wait until suction pressure and superheat stabilize.
This may take more than 30 minutes.
START--UP
Before starting unit, check the following and correct as
necessary:
S Is unit solidly supported?
4. Continue adjustment until superheat reaches 10_F to
15_F (5.5_C to 8.3_C).
5. Replace the seal cap; tighten.
S Is fan adjusted for speed and pulley alignment?
S Are pulleys, motor, and bearings securely mounted?
S Are there any loose parts that will rattle or vibrate?
S Is condensate drain pan pitched for correct drainage?
INSTALLER / INSTALLATEUR
TXV superheat must be checked at initial
unit start-up and adjusted if necessary.
Superheat must be 10 - 15 deg F.
S Are coil baffle plates tight against coil to prevent air
bypass?
La surchauffe TXV doit être vérifiée au
moment de la mise en route initiale et
ajustée si nécessaire. La surchauffe doit
S Are all panels securely fastened?
S Are all electrical connections correct and tight?
être comprise entre 10 et 15 degrés F.
40RUA and 40RUQ ONLY —
40RU500073 2.0
S Is TXV bulb located on suction tube per Fig. 21?
C10828
Fig. 22 - Label, TXV Adjustment
S Is the capillary tube to the bulb free of kinks and not
subject to pinching?
SERVICE
S Is the bulb well secured to the suction tube with strap?
Inspection and maintenance should be performed at
regular intervals and should include the following:
Also refer to condensing unit or outdoor heat pump section
instructions before starting a split system. A split system
start-up checklist is provided at the end of these instructions.
S Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return-air
grille (if present).
40RU500072 2.0
IMPORTANT! / IMPORTANT
EQUALIZER LINE
S Inspection of panels and sealing of unit against air
leakage.
TXV
CONDUITE D'ÉQUILIBRAGE
SENSING
BULB
UPPER SPLIT
BLOC SUPÉRIEUR
SIGHT GLASS
HUBLOT
CAPTEUR TXV
S Adjustment of fan motor, belt, bearings, and wheels.
S Cleaning or replacement of filters.
AIR FLOW
CIRCULATION
D'AIR
TXV
15 DIAMS MIN
10 DIAMS
10 x DIA. MIN
15 x DIA. MIN
SOLENOID
VALVE
8 DIAMS MIN
8
x
DIA. MIN
VANNE
SOLÉNOÏDE
LOWER
SPLIT
S Testing for cooling/heating system leaks.
S Checking of all electrical connections.
FILTER
DRIER
FILTRE
BLOC
TXV SENSING
BULB
CAPTEUR TXV
INFÉRIEUR
DESSICCATEUR
TXV
AIR FLOW
CIRCULATION
D'AIR
!
EQUALIZER LINE
15 DIAMS MIN
15 x DIA. MIN 10 x DIA. MIN
WARNING
10 DIAMS
CONDUITE D'ÉQUILIBRAGE
8
8
DIAMS MIN
x
DIA. MIN
INDOOR COIL
ÉCHANGEUR INTÉRIEUR
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping
access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit.
See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.
Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur
de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale
de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise
en marche, et d'entretien. La surchauffe doit être ajustée sur place.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
C10827
Fig. 21 - Label, TXV Bulb Location
Adjusting TXV for Superheat
Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit’s orientation. When
service is completed, replace unit panels.
(40RUA and 40 RUQ only) —
The unit-mounted thermostatic expansion valve(s) is/are
factory set to provided superheat at the bulb location in
10_F to 15_F (5.5_C to 8.3_C) range. Actual system load
conditions may require adjustment of the factory setting.
To adjust the TXV superheat setting:
Panels - Panels are fastened to unit frame with sheet
metal screws. Fan and coil compartment must be sealed
tightly after service to prevent air from bypassing the
cooling coil.
1. Remove the seal cap from the bottom of the TXV
body.
23
Fan Motor Lubrication - Fan motor supplied with unit is
permanently lubricated and requires no further
lubrication.
Centering Fan Wheel - If fan and fan shaft assembly are
not properly centered, blades may scrape against the
blower side scroll plate or may create an objectionable
whistling noise. It may be necessary to adjust individual
fan wheels or move entire fan shaft. See the following two
sections.
Fan Shaft Bearings - Size 25-30 units have pillow-block
bearings (Fig. 23) that must be lubricated with suitable
bearing grease approximately every 3 months. See Table 7
for suitable lubricants.
Fan Shaft Position Adjustment - Loosen setscrew or
locking collar of each fan shaft bearing. Slide shaft into
correct position and replace locking collar (Fig. 24). To
replace locking collar, push collar up against inner face of
bearing. Turn collar in direction of fan rotation until tight,
and tighten setscrew. Tightening locking collar in
direction of fan rotation results in further tightening of
collar should setscrew work itself loose.
Table 7 – Lubricant Data
MANUFACTURER
Mobil
LUBRICANT
Mobilplex EP No. 2
Prestige 42
Sunoco
Texaco
Multifak 2
Texaco
R e g a l A F B --- 2 *
*Preferred lubricant, contains rust and oxidation inhibitors.
C10699
Fig. 24 - Fan Shaft Bearing
C10698
Fig. 23 - Fan Shaft, Bearings, and Fan Wheel (Typical)
C10700
Fig. 25 - Fan Motor Mounting
24
Individual Fan Wheel Adjustment - Loosen the 2
locking bolts holding fan wheel hub to shaft. See Fig. 23.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing
should be the same on both sides.
Fan Belts - Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal
adjustment. Adjust belt(s) for correct deflection by
loosening motor plate mounting bolts, moving motor/plate
assembly forward or back, and re-tightening bolts. Press
down on belt with one finger midway between fan and
motor pulleys to check deflection. The correct deflection
is 1/8 -in. (3.2 mm). See Fig. 25.
If complete belt replacement is required during servicing,
loosen the motor plate mounting bolts (Fig. 25), move
motor/plate assembly towards fan pulley, and pull belt(s)
off pulleys. Reverse the procedure with new bolts and
readjust deflection.
C10702
Fig. 27 - Fan Pulley Adjustments
Fan Rotation - Correct fan rotation with respect to fan
outlet is shown in Fig. 26.
4. If pulleys are not in correct alignment, loosen the mo-
tor holddown bolts and slide the motor axially until
the pulleys are aligned.
5. Tighten motor holddown bolts.
Pulley and Drive Adjustment - To obtain desired fan
speed, refer to the fan motor and drive data in Tables
8A-11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening
motor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the
fan speed and away from fixed flange to reduce
speed. Before tightening setscrew, make certain that
setscrew is over nearest flat surface of pulley hub
(Fig. 27).
C10701
Fig. 26 - Fan Rotation
To reverse the direction of rotation of a 3-phase fan
motor, reverse any 2 of the power leads. Refer to the
connection diagram on the inside of motor terminal box
cover for proper reversing procedure of single-phase
motor.
!
CAUTION
UNIT OPERATION HAZARD
Fan Pulley Alignment - Align as follows:
Failure to follow this caution could cause equipment
damage.
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan
pulley to lock it in place.
3. Use the methods shown in Fig. 27 to check proper
pulley alignment.
Increasing fan speed produces a greater load on motor.
Do not exceed rated capacity of motor.
Condensate Drains - Keep condensate drains free of dirt
and foreign matter.
Return-Air Filters - Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean
filters of the sizes listed in Tables 1A-1F.
25
Chilled Water Coil Freeze Protection - Shut off water
supply to unit. Remove side panel of unit and remove vent
and drain plugs in top and bottom of coil header. Drain
coil and blow out remaining water. Reinstall plugs and
side panel.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Alternative freeze protection methods follow:
Do not operate unit without air filters.
S Circulate hot water within the water coil’s supply main
or supplementary space heating.
S Close off supply lines to unit and open a union or
field-supplied drain valve in the return line.
IMPORTANT: Draining from return line will not
completely drain water from coils.
S After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.
FILTER
RETAINER
CLIP
SLIDE
S Add a sufficient quantity of non-corrosive antifreeze to
the entire system to prevent all water within the system
from freezing.
Coil Removal - Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil - Remove return-air filters.
Remove any heavy dirt that may have accumulated on
underside of coil. Coil can be cleaned more easily with a
stiff brush, vacuum cleaner, or compressed air when coil
is dry. If coil is wet or if water is to be used for cleaning,
guard against splashing water on electrical components or
damaging surrounding area. Clean coil baffles as
applicable and check for tight fit to be sure air does not
bypass coil.
C10703
Fig. 28 - Remove Filter Retainer Clip
Cleaning Insulation
-
The insulation contains an
immobilized antimicrobial agent that helps prevent the
growth of bacteria and fungi. Clean the inner surface of
the insulation according to the separate maintenance
instructions shipped with the unit.
Replacing Filters - Filters can be removed and installed
from either side of the unit. Install new filters in units that
have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 28).
3. Remove old filters by lifting and tilting them out of
the filter track. See Fig. 16 and 29. Use the factory-
supplied filter hook to slide filters within reach for re-
moval. The filter hook is shipped inside the unit in
the filter track
4. Reverse the procedure to install new filters.
C10704
Fig. 29 - Filter Removal/Replacement
26
Table 8A -- Fan Motor Data, Standard Motor — English
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
UNIT
208/230---3---60 and 460---3---60
Speed (rpm)
Hp
1745
5.0
1745
7.5
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
5 7 5 --- 3 --- 6 0
S184T
1
S213T
3
S215T
3
1 /
1 /
1 /
8
8
8
Speed (rpm)
Hp
1745
5.0
1755
7.5
1755
10.0
Frame (NEMA)
Shaft Dia (in.)
184T
1
S213T
3
D215T
3
1 /
1 /
1 /
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
Table 8B -- Fan Motor Data, Alternate Motor — English
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
UNIT
208/230---3---60 and 460---3---60
Speed (rpm)
Hp
1745
7.5
1745
10.0
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
5 7 5 --- 3 --- 6 0
S213T
3
S215T
3
S215T
3
1 /
1 /
1 /
8
8
8
Speed (rpm)
Hp
1755
7.5
1750
10.0
1750
10.0
Frame (NEMA)
Shaft Dia (in.)
S213T
3
D215T
3
D215T
3
1 /
1 /
1 /
8
8
8
LEGEND
NEMA — National Electrical Manufacturers Association
27
Table 8C -- Fan Motor Data, Standard Motor — SI
40RUA*25
40RUA*28
40RUA*30
40RUS*30
40RUQ*25
40RUS*25
UNIT
40RUS*28
208/230---3---60 and 460---3---60
Speed (r/s)
29.08
3.73
29.08
5.60
29.08
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
5 7 5 --- 3 --- 6 0
S184T
28.6
S213T
34.9
S215T
34.9
Speed (r/s)
29.08
3.73
29.25
5.60
29.25
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
184T
28.6
S213T
34.9
S215T
34.9
LEGEND
NEMA — National Electrical Manufacturers Association
Table 8D -- Fan Motor Data, Alternate Motor — SI
40RUA*25
40RUA*28
40RUA*30
40RUS*30
40RUQ*25
40RUS*25
UNIT
40RUS*28
208/230---3---60 and 460---3---60
Speed (r/s)
29.08
5.60
29.17
7.46
29.17
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
5 7 5 --- 3 --- 6 0
S213T
34.9
S215T
34.9
S215T
34.9
Speed (r/s)
29.25
5.60
29.17
7.46
29.17
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
S213T
34.9
D215T
34.9
D215T
34.9
LEGEND
NEMA — National Electrical Manufacturers Association
28
Table 9A -- Standard Drive Data, 60 Hz — English
40RUA*25
40RUA*28
40RUA*30
40RUS*30
40RUQ*25
40RUS*25
UNIT
40RUS*28
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
3.7---4.7
3.0
4.3---5.3
3.0
4.3---5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
9.4
7
11.0
15
11.0
15
1 /
1
/
1
/
16
16
16
2—B
41.8
2—B†
2—B†
(2) 42.8
(2) 43.8
(2) 42.8
(2) 43.8
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
771
679---863
1200
752
682---841
1100
752
674---831
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
15.3
13.1
13.1
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (in.)
9.12---10.99
6.67---9.43
6.67---9.43
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9B -- Medium--Static Drive Data, 60 Hz — English
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
4.3---5.3
3.0
4.3---5.3
3.0
4.3---5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
9.4
7
9.4
15
9.4
15
1 /
1
/
1
/
16
16
16
1—B
41.8
2—B†
2—B†
(2) 38.8
(2) 39.8
(2) 38.8
(2) 39.8
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
881
798---984
1200
881
798---984
1100
881
798---984
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
15.3
15.3
15.3
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (in.)
9.16---10.99
6.67---9.43
6.67---9.43
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
29
Table 9C -- High--Static Drive Data, 60 Hz — English
40RUA*25
40RUA*28
40RUA*30
40RUS*30
40RUQ*25
40RUS*25
UNIT
40RUS*28
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
4.3---5.3
3.0
4.3---5.3
3.0
4.3---5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
7.4
7
8.6
15
8.6
15
1 /
1
/
1
/
16
16
16
2—B
36.8
2—B
378
2—B
37.8
1118
1014---1200†
1200
1024
873---1075
1100
1024
873---1075
1100
Max Allowable Speed (rpm)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
19.4
16.7
16.7
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (in.)
8.16---10.02
6.67---9.43
6.67---9.43
†
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
Table 9D-- Standard Drive Data, 60 Hz — SI
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
94.0---119.4
3.0
109.2---134.6
3.0
109.2---134.6
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
239
36.5
2—B
279
49.2
279
49.2
2—B†
2—B†
(2) 1987
(2) 1113
(2) 1987
(2) 1113
Belt Pitch (mm)
1062
FAN SPEEDS (r/s)
Factory Setting
Range
12.9
11.3---14.4
20.0
12.5
11.4---14.0
18.3
12.5
11.2---13.9
18.3
Max Allowable Speed (r/s)
1
Change per / Turn of
2
Moveable Motor Pulley
Flange
0.255
0.218
0.218
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (mm)
232---279
169---240
169---240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
30
Table 9E -- Medium--Static Drive Data, 60 Hz — SI
40RUA*25
40RUA*28
40RUA*30
40RUS*30
40RUQ*25
40RUS*25
UNIT
40RUS*28
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
109.2---134.6
3.0
109.2---134.6
3.0
109.2---134.6
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
239
36.5
1—B
239
49.2
239
49.2
2—B†
2—B†
(2) 986
(2) 1011
(2) 986
(2) 1011
Belt Pitch (mm)
1062
FAN SPEEDS (r/s)
Factory Setting
Range
14.7
13.3---16.4
20.0
14.7
13.3---16.4
18.3
14.7
13.3---16.4
18.3
Max Allowable Speed (r/s)
1
Change per / Turn of
2
Moveable Motor Pulley
Flange
0.255
0.255
0.255
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (mm)
232---279
169---240
169---240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9F -- High--Static Drive Data, 60 Hz — SI
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
109.2---134.6
3.0
109.2---134.6
3.0
109.2---134.6
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
188
36.5
2—B
935
203†
49.2
2—B
935
203
49.2
2—B
960
18.6
16.9---20.0†
20.0
17.1
14.6---17.9
18.3
17.1
14.6---7.9
18.3
Max Allowable Speed (r/s)
1
Change per
/
2
Turn of
Moveable Motor Pulley
Flange
0.323
0.278
0.278
MAX FULL TURNS FROM
CLOSED POSITION
6
6
6
SHAFTS CENTER DISTANCE (mm)
207---255
169---240
169---240
†
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s
31
Table 10A -- 40RU Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
UNIT
Rpm
532
608
686
764
843
456
521
587
653
720
829
521
596
673
751
829
Bhp
1.25
1.93
2.83
3.97
5.38
1.29
1.98
2.88
4.03
5.46
8.84
1.99
3.16
4.63
6.51
8.84
Rpm
569
641
716
791
868
490
551
614
678
743
850
550
623
698
773
850
Bhp
1.39
2.09
3.01
4.18
5.62
1.47
2.18
3.11
4.29
5.75
9.19
2.25
3.40
4.90
6.82
9.19
Rpm
639
702
770
841
914
556
608
664
724
785
888
616
672
743
815
888
Bhp
1.69
2.42
3.38
4.59
6.09
1.85
2.61
3.59
4.82
6.33
9.88
2.77
3.89
5.45
7.44
9.88
Rpm
711
763
823
888
957
621
664
714
768
825
924
676
720
785
853
924
Bhp
2.06
2.08
3.77
5.02
6.55
2.25
3.07
4.09
5.37
6.93
10.57
3.23
4.40
6.02
8.06
10.57
Rpm
781
824
876
935
1000
678
720
763
812
865
958
731
767
826
890
958
Bhp
2.48
3.23
4.21
5.47
7.02
2.64
3.53
4.62
5.95
7.55
11.27
3.72
4.94
6.62
8.71
11.27
Rpm
846
885
930
982
1042
729
770
812
856
904
991
782
814
867
927
991
Bhp
2.93
3.71
4.70
5.96
7.53
3.06
3.99
5.15
6.54
8.20
11.99
4.20
5.50
7.23
9.38
11.99
Rpm
905
943
983
1030
1084
778
816
857
899
944
1024
829
859
908
963
1024
Bhp
3.60
4.23
5.24
6.51
8.08
3.60
4.45
5.68
7.14
8.86
12.73
4.70
6.05
7.87
10.07
12.73
6,000
7,000
40RUA*25
40RUQ*25
40RUS*25
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
15,000
9,000
40RUA*28
40RUS*28
10,500
12,000
13,500
15,000
40RUA*30
40RUS*30
See Legend and Notes on page 36.
Table 10A -- 40RU Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
1.4
1.6
1.8
2.0
2.2
2.4
UNIT
Rpm
Bhp
3.83
4.74
5.79
7.11
8.75
4.41
4.97
6.20
7.73
9.53
13.49
5.20
6.60
8.50
10.78
13.49
Rpm
1005
1040
1078
1120
1166
870
Bhp
4.27
5.24
6.38
7.72
9.37
5.10
5.59
6.74
8.32
10.19
14.28
5.85
7.14
9.14
11.49
14.28
Rpm
1052
1090
1130
1169
—
Bhp
4.72
5.80
7.00
8.37
—
Rpm
1098
1135
1173
—
Bhp
5.22
6.30
7.60
—
Rpm
Bhp
Rpm
Bhp
—
6,000
7,000
954
990
1142
1176
—
5.67
6.84
—
—
—
—
40RUA*25
40RUQ*25
40RUS*25
8,000
1028
1073
1126
831
—
—
9,000
—
—
—
—
10,000
7,500
—
—
—
—
—
—
913
5.90
6.42
7.33
8.90
10.84
—
950
980
1013
1052
1093
—
6.88
7.20
8.00
9.51
11.49
—
985
1020
1050
1088
—
7.70
8.10
8.82
10.16
—
—
—
8,750
859
901
944
—
—
10,000
11,250
12,500
15,000
9,000
900
939
976
—
—
40RUA*28
40RUS*28
941
980
1017
1058
—
—
—
984
1022
1090
899
—
—
1057
866
—
—
—
—
950
6.65
7.70
9.76
12.21
—
989
1016
1062
—
7.38
8.31
10.38
—
1029
1051
1095
—
8.32
8.99
11.01
—
1077
1085
—
9.74
9.77
—
10,500
12,000
13,500
15,000
902
942
980
40RUA*30
40RUS*30
949
988
1026
1073
—
1000
1057
1036
1090
—
—
—
—
—
—
—
—
See Legend and Notes on page 36.
32
Table 10B -- 40RU Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)
AIRFLOW
(L/s)
0
50
100
150
200
250
300
UNIT
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
2830
3300
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
8.86
0.94
1.44
2.11
2.96
4.01
0.96
1.47
2.15
3.01
4.07
1.48
2.35
3.45
4.85
6.59
9.48
1.04
1.56
2.25
3.12
4.19
1.09
1.62
2.32
3.20
4.29
1.68
2.53
3.66
5.08
6.85
10.65
11.70
12.84
14.02
15.23
9.27
1.26
1.81
2.52
3.43
4.54
1.38
1.94
2.67
3.59
4.72
2.07
2.90
4.07
5.54
7.36
11.84
12.71
13.71
14.81
15.96
10.34
11.07
11.89
12.80
13.75
11.27
11.99
13.08
14.22
15.40
1.53
2.08
2.81
3.74
4.88
1.68
2.29
3.05
4.00
5.17
2.41
3.28
4.49
6.01
7.88
13.01
13.73
14.60
15.59
16.66
11.30
11.99
12.72
13.53
14.41
12.19
12.78
13.76
14.83
15.97
1.85
2.41
3.14
4.08
5.24
1.97
2.63
3.45
4.43
5.63
2.77
3.68
4.93
6.49
8.40
14.10
14.74
15.49
16.37
17.36
12.15
12.84
13.53
14.27
15.07
13.03
13.56
14.45
15.44
16.52
2.19
2.77
3.51
4.45
5.62
2.28
2.97
3.84
4.88
6.11
3.13
4.10
5.39
6.99
8.94
15.08
15.71
16.39
17.17
18.07
12.97
13.60
14.29
14.99
15.74
13.81
14.32
15.14
16.05
17.06
2.53
3.15
3.91
4.85
6.03
2.68
3.32
4.23
5.33
6.61
3.50
4.51
5.87
7.51
9.49
10.14
11.43
12.74
14.05
7.60
10.69
11.93
13.19
14.47
8.16
40RUA*25
40RUQ*25
40RUS*25
8.68
9.18
10.13
11.07
12.06
13.09
10.27
11.21
12.38
13.58
14.81
40RUA*28
40RUS*28
9.78
10.23
11.30
12.38
9.17
10.89
12.00
8.68
9.93
10.38
11.63
12.89
14.17
40RUA*30
40RUS*30
11.21
12.51
13.82
See Legend and Notes on page 36.
Table 10B -- 40RU Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
450 500
AIRFLOW
350
400
550
600
UNIT
(L/s)
r/s
kW
2.86
3.53
4.32
5.30
6.52
3.29
3.71
4.62
5.77
7.10
3.88
4.92
6.34
8.04
10.06
r/s
kW
3.18
3.91
4.76
5.76
6.99
3.80
4.17
5.02
6.20
7.60
4.36
5.32
6.81
8.57
10.64
r/s
kW
3.52
4.32
5.22
6.24
—
r/s
kW
3.89
4.70
5.67
—
r/s
kW
r/s
—
kW
—
2830
15.90
16.50
17.13
17.88
18.77
13.85
14.31
14.99
15.68
16.39
14.43
15.04
15.81
16.66
17.61
16.75
17.33
17.97
18.67
19.43
14.50
15.01
15.65
16.34
17.03
14.98
15.71
16.47
17.27
18.16
17.53
18.17
18.83
19.48
—
18.30
18.92
19.55
—
19.03
19.60
—
4.23
5.10
—
3300
—
—
40RUA*25
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
—
—
40RUQ*25
40RUS*25
—
—
—
—
—
—
—
—
—
—
15.22
15.74
16.27
16.95
17.64
15.84
16.33
17.10
17.88
—
4.40
4.79
5.46
6.64
8.08
4.96
5.74
7.28
9.10
—
15.83
16.33
16.88
17.53
18.22
16.48
16.93
17.69
—
5.13
5.37
5.97
7.09
8.57
5.50
6.20
7.74
—
16.42
17.00
17.50
18.09
—
5.74
6.04
6.57
7.58
—
—
—
—
—
40RUA*28
40RUS*28
—
—
—
—
—
—
17.16
17.51
18.26
—
6.21
6.70
8.21
—
17.96
18.09
—
7.26
7.29
—
40RUA*30
40RUS*30
—
—
—
—
—
—
—
—
See Legend and Notes on page 36.
33
Table 10C -- 40RU High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
UNIT
Rpm
542
620
700
781
862
476
545
615
685
756
539
620
701
783
865
Bhp
1.29
1.99
2.92
4.10
5.56
1.39
2.14
3.12
4.37
5.92
2.18
3.37
4.94
6.95
9.45
Rpm
577
652
728
806
885
510
574
641
709
778
569
646
724
804
884
Bhp
1042
2.15
3.10
4.30
5.79
1.58
2.35
3.36
4.64
6.22
2.39
3.62
5.22
7.27
9.81
Rpm
646
711
781
854
929
579
633
692
754
819
626
695
769
844
921
Bhp
1.72
2.48
3.46
4.71
6.24
1.99
2.81
3.87
5.20
6.83
2.85
4.13
5.80
7.91
10.52
Rpm
716
771
833
900
971
644
691
743
800
860
683
744
811
883
956
Bhp
2.09
2.85
3.85
5.13
6.70
2.40
3.29
4.41
5.79
7.47
3.34
4.68
6.40
8.57
11.24
Rpm
785
831
885
946
1012
701
747
794
845
901
739
793
854
920
991
Bhp
2.51
3.28
4.29
5.58
7.18
2.81
3.77
4.96
6.40
8.14
3.83
5.25
7.04
9.26
11.98
Rpm
849
890
938
993
1054
752
797
843
891
942
791
842
897
958
1025
Bhp
2.95
3.76
4.78
6.08
7.69
3.29
4.25
5.51
7.02
8.83
4.32
5.83
7.69
9.97
12.75
Rpm
907
947
990
1039
1096
804
842
888
935
983
837
888
940
996
1059
Bhp
3.40
4.27
5.32
6.62
8.24
3.96
4.76
6.05
7.64
9.52
4.82
6.41
8.36
10.71
13.54
6,000
7,000
40RUA*25
40RUQ*25
40RUS*25
8,000
9,000
10,000
7,500
8,750
40RUA*28
40RUS*28
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000
40RUA*30
40RUS*30
See Legend and Notes on page 36.
Table 10C -- 40RU High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
1.8 2.0
AIRFLOW
(Cfm)
1.4
1.6
2.2
2.4
UNIT
Rpm
961
Bhp
3.86
4.79
5.88
7.21
8.83
5.33
5.36
6.60
8.25
10.20
5.37
6.97
9.02
11.45
14.35
Rpm
1011
1050
1090
1133
1180
897
Bhp
4.31
5.32
6.47
7.82
9.46
5.91
6.13
7.20
8.86
10.88
6.03
7.55
9.67
12.20
—
Rpm
1058
1097
1137
1178
—
Bhp
4.77
5.85
7.07
8.47
—
Rpm
1104
1142
1181
—
Bhp
5.24
6.38
7.67
—
Rpm
Bhp
Rpm
Bhp
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6,000
1147
1184
—
5.71
6.91
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7,000
1000
1041
1086
1138
874
40RUA*25
40RUQ*25
40RUS*25
8,000
9,000
—
—
10,000
7,500
—
—
—
—
940
6.80
7.32
7.89
9.49
11.56
6.89
8.17
10.32
—
990
1020
1045
1086
—
7.50
8.10
8.71
10.17
—
—
—
8,750
886
930
982
—
—
40RUA*28
40RUS*28
10,000
11,250
12,500
9,000
930
969
1007
1051
1097
967
—
—
976
1014
1061
923
—
—
1023
881
—
—
1020
1045
1094
—
8.25
8.86
10.97
—
—
—
10,500
12,000
13,500
15,000
930
970
1008
1058
—
—
—
40RUA*30
40RUS*30
981
1021
1072
—
—
—
1035
1093
—
—
—
—
—
—
—
—
See Legend and Notes on page 36.
34
Table 10D -- 40RU High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)
AIRFLOW
(L/s)
0
50
100
150
200
250
300
UNIT
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
1087
2.45
3.20
4.16
5.35
2.10
2.81
3.70
4.77
6.07
2.86
3.92
5.25
6.90
8.93
r/s
kW
r/s
kW
2.54
3.18
3.96
4.94
6.14
2.95
3.55
4.51
570
2830
3330
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
9.03
0.96
1.48
2.17
3.05
4.15
1.04
1.59
2.33
3.26
4.42
1.62
2.51
3.68
5.18
7.05
9.62
1.06
1.60
2.31
3.21
4.32
1.18
1.75
2.51
3.46
4.64
1.78
2.70
3.90
5.42
7.31
10.77
11.85
13.02
14.23
15.48
9.65
1.29
1.85
2.58
3.51
4.66
1.48
2.10
2.88
3.88
5.09
2.12
3.08
4.33
5.90
7.84
11.94
12.84
13.88
15.00
16.18
10.73
11.52
12.39
13.33
14.33
11.39
12.40
13.52
14.71
15.94
1.56
2.12
2.87
3.82
4.99
1.79
2.46
3.29
4.32
5.57
2.49
3.49
4.77
6.39
8.38
13.08
13.85
14.75
15.77
16.87
11.68
12.45
13.24
14.09
15.01
12.32
13.22
14.23
15.34
16.51
14.15
14.84
15.63
16.54
17.56
12.53
13.28
14.05
14.85
15.40
13.18
14.03
14.95
15.97
17.08
2.20
2.80
3.56
4.53
5.73
2.46
3.17
4.11
5.24
6.58
3.22
4.35
5.74
7.44
9.51
15.12
15.78
16.50
17.32
18.26
13.40
14.04
14.80
15.58
16.38
13.95
14.79
15.66
16.61
17.65
10.34
11.67
13.01
14.36
7.94
10.86
12.14
13.44
14.75
8.51
40RUA*25
40RUQ*25
40RUS*25
9.08
9.57
10.55
11.53
12.57
13.65
10.44
11.59
12.81
14.07
15.36
40RUA*28
40RUS*28
10.24
11.42
12.60
8.99
10.68
11.81
12.96
9.49
7.10
3.59
4.78
6.23
7.98
10.10
10.33
11.68
13.04
14.42
10.77
12.07
13.40
14.74
40RUA*30
40RUS*30
See Legend and Notes on page 36.
Table 10D -- 40RU High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
AIRFLOW
350
400
450
500
550
600
UNIT
(L/s)
r/s
kW
2.88
3.57
4.39
5.37
6.58
3.97
3.99
4.92
6.15
7.61
4.00
5.20
6.72
8.54
10.70
r/s
kW
3.22
3.96
4.82
5.83
7.05
4.41
4.57
5.37
6.61
8.11
4.49
5.63
7.21
9.10
—
r/s
kW
3.56
4.36
5.27
6.31
—
r/s
18.39
19.03
19.68
—
kW
3.91
4.75
5.72
—
r/s
kW
r/s
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
kW
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2830
16.01
16.67
17.35
18.11
18.96
14.57
14.76
15.49
16.26
17.04
14.68
15.51
16.35
17.24
18.22
16.85
17.50
18.17
18.88
19.67
14.95
15.51
16.15
16.91
17.68
15.38
16.17
17.01
17.87
—
17.64
18.28
18.95
19.63
—
19.12
19.73
—
4.26
5.15
—
3300
40RUA*25
3780
4250
4720
3540
4130
4720
5310
5900
4250
4960
5660
6370
7080
40RUQ*25
40RUS*25
—
—
—
—
—
—
15.67
16.36
16.78
17.51
18.28
16.12
16.80
17.64
—
5.07
5.46
5.88
7.08
8.62
5.14
6.09
7.69
—
16.50
17.00
17.42
18.10
—
5.59
6.04
6.50
7.58
—
—
—
—
—
40RUA*28
40RUS*28
—
—
—
—
—
—
17.00
17.41
18.23
—
6.15
6.61
8.18
—
—
—
—
—
40RUA*30
40RUS*30
—
—
—
—
—
—
—
—
—
—
See Legend and Notes on page 36.
35
Legend and Notes for Tables 10A and 10C
UNIT
LEGEND
Bhp --- Brake Horsepower Input to Fan
ESP --- External Static Pressure
NOTES:
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
1. Maximum allowable fan speed for size 25 units is 1200 rpm . Maximum
allowable fan speed for size 28 and 30 units is 1100 rpm.
2. Fan performance is based on deductions for wet coil, clean 2-in. filters,
and unit casing. See table at right for factory-supplied filter pressure drop.
6,000
8,000
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
40RUA*25
40RUQ*25
40RUS*25
3. Refer to fan motor and drive tables for additional data.
10,000
7,500
40RUA*28
40RUS*28
10,000
12,500
9,000
40RUA*30
40RUS*30
12,000
15,000
Legend and Notes for Tables 10B and 10D
FACTORY-SUPPLIED PRESSURE DROP — SI
LEGEND
ESP --- External Static Pressure
NOTES:
AIRFLOW
(L/s)
PRESSURE DROP
(Pa)
UNIT
1. Maximum allowable fan speed for size 25 units is 20 r/s. Maximum
allowable fan speed for size 28 and 30 units is 18.3 r/s.
2900
3800
4700
3500
4700
5900
4250
5650
7050
32
47
64
36
55
76
47
71
98
2. Fan performance is based on deductions for wet coil, clean 51---mm
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
40RUA*25
40RUQ*25
40RUS*25
3. Refer to fan motor and drive tables for additional data.
40RUA*28
40RUS*28
40RUA*30
40RUS*30
36
37
Catalog No: 40RU---07SI
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 40RU---05SI
38
START--UP CHECKLIST
(SPLIT SYSTEMS WITH 40RU UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO.
SERIAL NO.
INDOOR: MODEL NO.
SERIAL NO.
ADDITIONAL ACCESSORIES
II. PRE--START--UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)
CONTROLS
ARE THERMOSTAT(S) & INDOOR FAN CONTROL WIRING CONNECTIONS MADE & CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
PIPING
40RUA, 40RUQ
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N)
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (40RUA) OR OUTDOOR UINT
(40RUQ) COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED) (Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)
40RUS
HAS AIR BEEN BLED FROM SYSTEM? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, & INDOOR COILS? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
39
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:
(AB + AC + BC)/3 = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
AB
V
AC
V
BC
V
V
V
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START--UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1
COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY)
INTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY)
COMPRESSOR AMPS (L1/L2/L3)
____/____/____
____/____/____
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1/8 to 1/3 FULL? (Y/N)
NOTES:
Catalog No: 40RU---07SI
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date:01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 40RU---05SI
40
|