Carrier 38AH044 084 User Manual

38AH044-134  
Air-Cooled Condensing Units  
50/60 Hz  
Installation, Start-Up and  
Service Instructions  
CONTENTS  
INSTALLATION  
Page  
Step 1 — Rig and Place Unit — All units are  
designed for overhead rigging, and it is important that this  
method be used. Lifting holes are provided in the frame base  
rails, which are marked for rigging (see rigging label on the  
unit and Tables 1, 2A, and 2B for rigging weights and center  
of gravity). It is recommended that field-supplied pipes, of  
sufficient length to extend at least 12-in. (305 mm) beyond  
the frame, be passed through the holes.  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . .  
1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-37  
Step 1 — Rig and Place Unit . . . . . . . . . . . . . . .  
• DOMESTIC UNITS  
1
• EXPORT UNITS  
• PLACING UNITS  
Step 2 — Check Compressor Mounting . . . . .  
• UNITS 38AH044-084  
3
• UNITS 38AH094-134  
Step 3 — Make Refrigerant Piping  
To maintain unit stability while lifting, use 4 cables,  
chains, or straps of equal length. Attach one end of  
each cable to one pipe end and the other end of each  
cable to the overhead rigging point.  
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
• UNITS 38AH044-084  
• UNITS 38AH094-134  
Step 4 — Make Electrical Connections . . . . . . 23  
• POWER SUPPLY  
Use spreader bars or frame to keep the cables, chains,  
and straps clear of the unit sides. Leave standard coil pro-  
tection packaging in place during rigging to provide protec-  
tion to coils. Remove and discard all coil protection after  
rigging cables are detached.  
• FIELD POWER CONNECTIONS  
• MAIN POWER  
• CONTROL CIRCUIT WIRING  
Step 5 — Install Accessories . . . . . . . . . . . . . . . 37  
• LOW-AMBIENT OPERATION  
• MISCELLANEOUS ACCESSORIES  
DOMESTIC UNITS — For units 38AH044-084, 124, and  
134; standard unit packaging consists of coil protection only.  
There is no standard packaging provided for units 38AH094  
and 104. Skids are not provided. If overhead rigging is not  
available at the jobsite, place the unit on a skid or pad before  
dragging or rolling. When rolling, use a minimum of  
3 rollers. When dragging, pull the pad or skid. Do not apply  
force to the unit. When in final position, raise from above to  
lift unit off the pad or skid.  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . 37,38  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-45  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-49  
CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-52  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 53,54  
START-UP CHECKLIST . . . . . . . . . . . . . . . CL-1, CL-2  
EXPORT UNITS — All export units are mounted on skids  
with vertical coil protection. Leave the unit on the skid until  
it is in final position. While on the skid, the unit can be rolled  
or skidded. Apply force to the skid, not to the unit. Use a  
minimum of 3 rollers when rolling. When in final position,  
raise from above to remove the skid.  
SAFETY CONSIDERATIONS  
Installing, starting up, and servicing this equipment can  
be hazardous due to system pressures, electrical compo-  
nents, and equipment location (roofs, elevated structures, etc.).  
Only trained, qualified installers and service mechanics  
should install, start up, and service this equipment.  
PLACING UNITS  
Units 38AH044-084 — Refer to Fig. 1 and 2 for airflow clear-  
ances. Recommended minimum clearances are 6 ft (1829 mm)  
for unrestricted airflow and service on sides of unit, 5 ft  
(1524 mm) on ends, and unrestricted clear air space above  
the unit. Provide ample space to connect liquid and suction  
lines to indoor unit. For multiple units, allow 8 ft (2440 mm)  
separation between units for airflow and service.  
Untrained personnel can perform basic maintenance func-  
tions, such as cleaning coils. All other operations should be  
performed by trained service personnel.  
When working on the equipment, observe precautions in  
the literature, and on tags, stickers, and labels attached to the  
equipment and any other safety precautions that may apply.  
• Follow all safety codes.  
• Wear safety glasses and work gloves.  
• Use care in handling, rigging, and setting bulky  
equipment.  
Do not forklift these units unless the unit is attached to  
a skid designed for forklifting.  
ELECTRIC SHOCK HAZARD.  
Open all remote disconnects before servicing  
this equipment.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 563-704  
Printed in U.S.A.  
Form 38AH-15SI  
Pg 1  
10-98  
Replaces: 38AH-14SI  
Tab 3a  
Remove sheet metal cover panels from return-bend end of  
Module 124B or 134B. Place Module 124B or 134B in  
position. The exposed return-bend ends of each module are  
now opposite each other and facing the service space. The  
compressors of each module are on opposite sides of the unit.  
Step 2 — Check Compressor Mounting  
UNITS 38AH044-084 — Compressors are mounted on pans  
and are held down by 4 bolts during shipment. After unit is  
installed, loosen each of these bolts until the snubber washer  
can be moved with finger pressure. See Fig. 10.  
IMPORTANT: Modules must be placed 24 in.  
(610 mm) apart and square relative to each other.  
UNITS 38AH094-134 — Units 38AH094 and 104 compres-  
sors are mounted on rails and held down by rail bolts during  
shipment. After unit is installed, loosen the rail bolts to al-  
low the rails and compressors to float freely on the springs  
located under the rails. See Fig. 10.  
Units 38AH124 and 134 compressors are mounted on pans  
and are held down by 4 bolts during shipment. After unit is  
installed, loosen each of these bolts until snubber washer can  
be moved with finger pressure. See Fig. 10.  
The modules are now in position for piping installa-  
tion and final assembly. See Fig. 8. For mounting units on  
vibration isolators, a perimeter support channel is required  
between the assembled unit and the support isolators. The  
perimeter support channel must be sized to support the fully  
assembled unit. Do not support modules on individual iso-  
lation supports. Support channel, hardware, and fasteners are  
field supplied.  
When unit is in proper location, level unit and bolt into  
position with field-supplied bolts.  
Table 2A — Operational Corner Weights with  
Refrigerant Charge (Approximate) — Lb  
Table 2B — Operational Corner Weights with  
Refrigerant Charge (Approximate) — Kg  
OPERATIONAL CORNER WEIGHT  
OPERATIONAL CORNER WEIGHT  
UNIT  
38AH  
TOTAL  
WEIGHT  
UNIT  
38AH  
TOTAL  
WEIGHT  
A
B
C
D
A
B
C
D
044  
3259  
3547  
3309  
3597  
3565  
3998  
3812  
4229  
4057  
4735  
5088  
5813  
5435  
6160  
939  
893  
695  
765  
697  
771  
765  
874  
777  
862  
827  
965  
1182  
1350  
1302  
1476  
732  
802  
742  
814  
771  
879  
903  
1035  
961  
1159  
601  
686  
755  
856  
044  
1478  
1609  
1501  
1632  
1617  
1813  
1729  
1918  
1840  
2148  
2308  
2637  
2465  
2794  
426  
460  
437  
469  
462  
510  
520  
577  
553  
646  
505  
577  
562  
637  
405  
438  
411  
444  
459  
508  
447  
481  
476  
538  
994  
1136  
970  
1099  
316  
347  
316  
350  
347  
397  
352  
391  
375  
438  
536  
612  
591  
670  
332  
364  
337  
369  
350  
399  
410  
470  
436  
526  
272  
311  
342  
388  
044C  
054  
1013  
964  
967  
044C  
054  
905  
054C  
064  
1034  
1018  
1125  
1146  
1272  
1220  
1425  
1114  
1273  
1240  
1405  
978  
054C  
064  
1011  
1117  
986  
064C  
074  
064C  
074  
074C  
084  
1059  
1049  
1186  
2192  
2504  
2138  
2423  
074C  
084  
084C  
094  
084C  
094  
094C  
104  
094C  
104  
104C  
104C  
MODULE  
38AH  
MODULE  
38AH  
124A  
3630  
4063  
3630  
4063  
3630  
4063  
3877  
4294  
1037  
1144  
1037  
1144  
1037  
1144  
1167  
1293  
1030  
1137  
1030  
1137  
1030  
1137  
997  
779  
889  
779  
889  
779  
889  
789  
874  
785  
894  
785  
894  
785  
894  
924  
1047  
124A  
1647  
1843  
1647  
1843  
1647  
1843  
1759  
1948  
470  
519  
470  
519  
470  
519  
529  
587  
467  
516  
467  
516  
467  
516  
452  
490  
353  
403  
353  
403  
353  
403  
358  
396  
356  
405  
356  
405  
356  
405  
419  
475  
124A-C  
124B  
124A-C  
124B  
124B-C  
134A  
124B-C  
134A  
134A-C  
134B  
134A-C  
134B  
134B-C  
1080  
134B-C  
LEGEND  
C — Copper Fin Coils  
LEGEND  
C — Copper Fin Coils  
NOTE: Total weight may differ from summation of corner weights due  
to rounding of numerals.  
NOTE: Total weight may differ from summation of corner weights due  
to rounding of numerals.  
TOP VIEW, TYPICAL  
3
DUAL CKT  
SINGLE CKT  
SUCTION  
CONNECTION(S)  
218Љ Dia [54 mm]  
258Љ Dia [67 mm]  
LIQUID  
CONNECTION(S)  
7
8Љ Dia [22 mm]  
118Љ Dia [29 mm]  
SUCTION C  
LIQUID D  
2Ј-1116Љ [627mm] 1Ј-10516Љ [567mm]  
1Ј-10116Љ [561mm] 1Ј-10516Љ [567mm]  
SUCTION (Ckt A) 1Ј-71316Љ [503mm] 2Ј-58  
SUCTION (Ckt B) 2Ј-58  
[626mm]  
Љ
[626mm]  
Љ
LIQUID (Ckt A)  
LIQUID (Ckt B)  
2Ј-534  
2Ј-1058  
Љ
[756mm] 2Ј-1058  
Љ
[879mm]  
Љ
[879mm]  
Chart 1, Field Power Supply Connections  
UNIT  
044  
VOLTAGE  
230  
Hz DIAMETER — in. [mm] QTY  
50  
60  
358 [92]  
358 [92]  
212 [63]  
212 [63]  
212 [63]  
358 [92]  
1
1
1
1
2
1
208/230  
044, 054  
346, 380/415 50  
044, 054, 064 460,575,380 60  
208/230 60  
346, 380/415 50  
064  
LEGEND  
C
MTG  
SAE  
Copper Fin Coils  
Mounting  
Society of Automotive Engineers  
NOTES:  
1. The approximate operating weight of the unit is:  
38AH-044---  
38AH-044--C  
38AH-054---  
38AH-054--C  
38AH-064---  
38AH-064--C  
3259 lb [1478 kg]  
3547 lb [1609 kg]  
3309 lb [1501 kg]  
3597 lb [1632 kg]  
3565 lb [1617 kg]  
3998 lb [1813 kg]  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting  
unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and  
the isolators is recommended.  
4. One 358Љ (92 mm) diameter hole is recommended for single-entry power on size 064 (208/230-v) units.  
5. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B for A-D corner weights.  
6. Circled numerals in Top View refer to condenser fans by position.  
Fig. 1 — Dimensions — Units 38AH044,054,064  
4
DUAL CKT  
SINGLE CKT  
SUCTION  
CONNECTION(S)  
218Љ Dia [54 mm]  
258Љ Dia [67 mm]  
LIQUID  
CONNECTION(S)  
7
8Љ Dia [22 mm]  
118Љ Dia [29 mm]  
SUCTION C  
LIQUID D  
2Ј-1116Љ [627mm] 1Ј-10516Љ [567mm]  
1Ј-10116Љ [561mm] 1Ј-10516Љ [567mm]  
SUCTION (Ckt A) 1Ј-71316Љ [503mm] 2Ј-58  
SUCTION (Ckt B) 2Ј-58  
[626mm]  
Љ
[626mm]  
Љ
LIQUID (Ckt A)  
LIQUID (Ckt B)  
2Ј-534  
2Ј-1058  
Љ
[756mm] 2Ј-1058  
Љ
[879mm]  
Љ
[879mm]  
Chart 1, Field Power Supply Connections  
UNIT  
074  
VOLTAGE  
208/230  
460  
Hz DIAMETER — in. [mm] QTY  
60  
60  
50  
60  
60  
60  
60  
212 [63]  
212 [63]  
358 [92]  
358 [92]  
212 [63]  
358 [92]  
358 [92]  
2
1
1
1
1
2
1
346, 380/415  
380  
074, 084  
084  
575  
208/230  
460  
LEGEND  
C
MTG  
SAE  
Copper Fin Coils  
Mounting  
Society of Automotive Engineers  
NOTES:  
1. The approximate operating weight of the unit is:  
38AH-074---  
38AH-074--C  
38AH-084---  
38AH-084--C  
3812 lb (1729 kg)  
4229 lb (1918 kg)  
4057 lb (1840 kg)  
4735 lb (2148 kg)  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit  
to spring isolators. If spring isolators are used, a perimeter support channel between the unit and the iso-  
lators is recommended.  
4. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B for A-D corner weights.  
5. Circled numerals in Top View refer to condenser fans by position.  
Fig. 2 — Dimensions — Units 38AH074,084  
5
Chart 1, Field Power Supply Connections  
LEGEND  
UNIT  
38AH  
VOLTAGE  
Hz DIAMETER — in. (mm) QUANTITY  
C
Copper Fin Coils  
MTG  
SAE  
Mounting  
208/230  
60  
60  
358 (92)  
358 (92)  
358 (92)  
2
1
1
Society of Automotive Engineers  
460, 575,  
380  
094  
NOTES:  
1. The approximate operating weight of the unit is:  
346, 380/415 50  
38AH-094---  
38AH-094--C  
5088 lb (2308 kg)  
5813 lb (2637 kg)  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
3. Mounting holes may be used to mount unit to concrete pad. They are not  
recommended for mounting unit to spring isolators.  
4. Two 358Љ (92-mm) dia holes are recommended for parallel conductors on  
208/230 v units.  
5. Circled numerals in Top View refer to condenser fans by position.  
6. If spring isolators are used, a perimeter support channel between the unit  
and the isolators is recommended.  
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A  
and 2B for A-D corner weights.  
Fig. 3 — Dimensions — Unit 38AH094  
6
LEGEND  
Chart 1, Field Power Supply Connections  
C
MTG  
SAE  
Copper Fin Coils  
Mounting  
UNIT  
38AH  
VOLTAGE  
Hz DIAMETER — in. (mm) QUANTITY  
Society of Automotive Engineers  
208/230  
60  
60  
358 (92)  
358 (92)  
358 (92)  
2
1
1
NOTES:  
1. The approximate operating weight of the unit is:  
460, 575,  
380  
104  
38AH-104---  
38AH-104--C  
5435 lb (2465 kg)  
6160 lb (2794 kg)  
346, 380/415 50  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
3. Mounting holes may be used to mount unit to concrete pad. They are not  
recommended for mounting unit to spring isolators.  
4. Two 358Љ (92-mm) dia holes are recommended for parallel conductors on  
208/230 v units.  
5. Circled numerals in Top View refer to condenser fans by position.  
6. If spring isolators are used, a perimeter support channel between the unit  
and the isolators is recommended.  
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A  
and 2B for A-D corner weights.  
Fig. 4 — Dimensions — Unit 38AH104  
7
Chart 1, Field Power Supply Connections  
NOTES:  
1. The approximate operating weight of the unit is:  
UNIT  
DIAMETER  
(in.)  
358 (92)  
212 (63)  
358 (92)  
38AH-124---  
38AH-124--C  
7260 lb (3293 kg)  
8126 lb (3686 kg)  
VOLTAGE  
Hz  
60  
60  
QUANTITY  
38AH  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
208/230  
1
1
1
124A  
124B  
460, 575,  
380  
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
3. Mounting holes may be used to mount unit to concrete pad. They are not rec-  
ommended for mounting unit to spring isolators.  
346, 380/415 50  
4. One 358Љ (92-mm) dia hole is recommended for single-entry power into each  
module (124A and 124B) of the 208/230-v units.  
LEGEND  
5. Circled numerals in Top View refer to condenser fans by position.  
6. If spring isolators are used, a perimeter support channel between the unit and  
the isolators is recommended. Do not support each module separately.  
7. Each module of the unit must be rigged into position separately. The unit must  
not be rigged after modules have been connected.  
C
MTG  
SAE  
Copper Fin Coils  
Mounting  
Society of Automotive Engineers  
8. Suction and liquid connections can exit on either side of the unit.  
9. Field power supply connections are required for each module.  
10. See Table 1 for rigging center of gravity (Dimensions K,L,X,Y). See Table 2A  
and 2B for A-D corner weights.  
Fig. 5 — Dimensions — Unit 38AH124  
8
NOTES:  
Chart 1, Field Power Supply Connections  
DIAMETER —  
1. The approximate operating weight of the unit is:  
38AH-134---  
38AH-134--C  
7507 lb (3405 kg)  
8357 lb (3791 kg)  
UNIT  
38AH  
VOLTAGE  
Hz  
QUANTITY  
in. (mm)  
358 (92)  
212 (63)  
358 (92)  
212 (63)  
212 (63)  
358 (92)  
358 (92)  
2. Unit must have clearances for airflow as follows:  
Top — Do not restrict in any way.  
208/230  
460, 575, 380  
346, 380/415  
208/230  
60  
60  
50  
60  
60  
60  
50  
1
1
1
2
1
1
1
Ends — 5 ft [1524 mm]  
Sides — 6 ft [1829 mm]  
134A  
3. Mounting holes may be used to mount unit to concrete pad. They are not  
recommended for mounting unit to spring isolators.  
4. One 358Љ (92-mm) dia hole is recommended for single-entry power into  
Module 134A and 208/230-v units. Single entry power into Module 134B is  
not recommended.  
460, 575  
134B  
380  
5. Circled numerals in Top View refer to condenser fans by position.  
6. If spring isolators are used, a perimeter support channel between the as-  
sembled unit and the isolators is recommended. Do not support each mod-  
ule separately.  
346, 380/415  
7. Each module of the unit must be rigged into position separately. The unit  
must not be rigged after modules have been connected.  
8. Suction and liquid connections can exit on either side of the unit.  
9. Field power supply connections are required for each module.  
10. See Table 1A or 1B for rigging center of gravity (Dimensions K,L,X,Y). See  
Table 2A and 2B for A-D corner weights.  
LEGEND  
C
MTG  
SAE  
Copper Fin Coils  
Mounting  
Society of Automotive Engineers  
Fig. 6 — Dimensions — Unit 38AH134  
9
Table 3A — Units 38AH044-084 Physical Data — 50/60 Hz (English)  
38AH  
044  
054  
064  
074  
084  
OPERATING WEIGHT WITH  
REFRIGERANT (Approx) — Lb  
Cu-Al  
Cu-Cu  
3259  
3547  
3309  
3597  
3565  
3998  
3812  
4229  
4057  
4735  
SHIP WEIGHT WITH COIL PROTECTION ONLY  
(Approx) — Lb  
Cu-Al  
Cu-Cu  
3250  
3538  
3290  
3578  
3530  
3963  
3780  
4197  
4000  
4678  
TYPICAL OPERATING REFRIGERANT  
Charge (Approx) — Lb  
Qty of Circuits  
R-22  
88  
2
62  
2
1
72  
2
1
104  
2
1
130  
2
1
Std  
Opt  
1
COMPRESSOR Type...Rpm  
(Qty Cylinder) Compressor*  
Model No. 06E  
Reciprocating Semi-Hermetic...1750 @ 60 Hz; 1458 @ 50 Hz  
Std  
Std  
Opt  
Opt  
Std  
Opt  
(4) A1  
(4) B1  
250  
(4) A1  
250  
(6) A1  
265  
17  
(6) B1  
265  
(6) A1  
265  
(6) A1  
275  
21  
(6) B1  
275  
(6) A1  
275  
(6) B1  
299  
(6) A1  
(6) B1  
299  
250  
(4) A1  
250  
17  
299  
(6) A1  
299  
19  
(Qty Cylinder) Compressor*  
Model No. 06E  
(4) A2  
250  
(4) A2  
250  
(6) A2  
265  
(6) A1  
299  
(6) A2  
275  
(6) A2  
299  
Oil Charge (Pt)  
17  
17  
21  
21  
21  
19  
19  
19  
17  
21  
17  
21  
21  
19  
21  
19  
Capacity Control Steps†  
4
CONDENSER FANS (6 Blade) — 60 Hz  
Qty...Dia (in.)  
4...30  
6...30  
Airflow (Cfm)  
35,000  
1140  
6.2  
52,000  
51,000  
Speed (Rpm)  
Total Power (kW)  
1140  
9.3  
CONDENSER FANS (6 Blade) — 50 Hz  
Qty...Dia (in.)  
4...30  
35,000  
950  
6...30  
Airflow (Cfm)  
52,000  
51,000  
Speed (Rpm)  
Total Power (kW)  
950  
9.3  
6.2  
CONDENSER COIL  
Enhanced Copper Tubes, Aluminum Lanced Fin  
Rows...Fins per in.  
2...17  
80.5  
35  
2...17  
80.5  
35  
3...17  
80.5  
55  
2...19  
116.7  
55  
3...17  
116.7  
80  
Face Area (sq ft)  
Storage Capacity (Lb per Circuit) at 120 F  
CONNECTIONS  
Suction, ODF (in.)**  
Liquid, ODF (in.)**  
Hot Gas Bypass, ODF (in.)  
218  
7
8
8
5
Table 3B — Units 38AH044-084 Physical Data — 50/60 Hz (SI)  
38AH  
044  
054  
064  
074  
084  
OPERATING WEIGHT WITH  
REFRIGERANT (Approx) — Kg  
Cu-Al  
Cu-Cu  
1478  
1609  
1501  
1632  
1617  
1813  
1729  
1918  
1840  
2148  
SHIP WEIGHT WITH COIL PROTECTION ONLY  
(Approx) — Kg  
Cu-Al  
Cu-Cu  
1474  
1605  
1492  
1623  
1601  
1798  
1715  
1904  
1814  
2122  
TYPICAL OPERATING REFRIGERANT  
CHARGE (Approx) — Kg  
Qty of Circuits  
R-22  
39.9  
2
28.1  
2
1
32.7  
2
1
47.2  
2
1
58.9  
2
1
Std  
Opt  
1
COMPRESSOR Type...R/s  
(Qty Cylinder) Compressor*  
Model No. 06E  
Reciprocating Semi-Hermetic...29.2 @ 60 Hz; 24.3 @ 50 Hz  
Std  
Std  
Opt  
Opt  
Std  
Opt  
(4) A1  
(4) B1  
250  
(4) A1  
250  
(6) B1  
265  
(6) A1  
265  
(6) B1  
275  
(6) A1  
275  
(6) B1  
299  
(6) A1  
(6) B1  
299  
250  
(4) A1  
250  
299  
(6) A1  
299  
(Qty) Cylinder) Compressor*  
Model No. 06E  
(4) A2  
250  
(6) A1  
265  
(4) A2  
250  
(6) A1  
275  
(6) A2  
265  
(6) A1  
299  
(6) A2  
275  
(6) A2  
299  
Oil Charge (L)  
8.0  
8.0  
8.0  
8.0  
8.0  
9.9  
9.9  
9.9  
9.9  
9.0  
9.0  
9.0  
9.0  
9.0  
9.9  
8.0  
9.9  
9.9  
9.0  
9.9  
Capacity Control Steps†  
4
CONDENSER FANS (6 Blade) — 50 Hz  
Qty...Dia (mm)  
4...762  
6...762  
Airflow (L/s)  
16,500  
15.8  
6.2  
24,500  
24,100  
Speed (R/s)  
Total Power (kW)  
15.8  
9.3  
CONDENSER FANS (6 Blade) — 60 Hz  
Qty...Dia (mm)  
4...762  
16,500  
19.0  
6...762  
Airflow (L/s)  
24,500  
24,100  
Speed (R/s)  
Total Power (kW)  
19.0  
9.3  
6.2  
CONDENSER COIL  
Enhanced Copper Tubes, Aluminum Lanced Fin  
Rows...Fins per m  
2...669  
7.48  
16  
2...669  
7.48  
16  
3...669  
7.48  
25  
2...782  
10.84  
25  
3...669  
10.84  
36  
Face Area (sq m)  
Storage Capacity (Kg per Circuit) at 48.9 C  
CONNECTIONS  
Suction, ODF (in.)**  
Liquid, ODF (in.)**  
Hot Gas Bypass, ODF (in.)  
218  
7
8
8
5
LEGEND  
**For single-circuit units, suction ODF is 258 in. (66.7 mm) and liquid ODF is  
118 in. (28.6 mm). Single circuits have a factory-installed manifold; no  
field modification is required.  
Cu-Al  
Cu-Cu  
ODF  
Opt  
Copper tubes with aluminum fins  
Copper tubes with copper fins  
Outside Diameter, Female  
Optional Single-Circuit Units  
Standard Dual-Circuit Units  
NOTES:  
1. Certified dimensional drawings available on request.  
2. Equivalent connection values in mm are as follows:  
Std  
in.  
mm  
*Compressor A1 is lead on standard and optional single-circuit units.  
†Capacity control steps listed are for constant-volume units with no accesso-  
ries. Refer to Table 19A or 19B, page 48, for additional system capacity  
information.  
5
8
8
15.9  
22.2  
54.0  
7
218  
10  
Table 4A — Units 38AH094-134 Physical Data — 50/60 Hz (English)  
124  
134  
38AH  
094  
104  
124A  
124B  
134A  
134B  
OPERATING WEIGHT WITH  
Cu-Al  
5088  
5813  
5435  
6160  
3630*  
4063*  
3630*  
4063*  
3630*  
4063*  
3877*  
4294*  
REFRIGERANT (Approx) — Lb Cu-Cu  
SHIP WEIGHT WITH  
Cu-Al  
5630  
6355  
5990  
6715  
3907*  
4340*  
3907*  
4340*  
3907*  
4340*  
4080*  
4497*  
COIL PROTECTION AND SKID Cu-Cu  
(Approx) — Lb  
TYPICAL OPERATING  
REFRIGERANT CHARGE  
(Approx) — Lb  
R-22  
148  
2
135  
2
88  
1
88  
1
88  
1
104  
1
Qty of Circuits  
COMPRESSOR Type...Rpm  
(Qty Cylinder) Compressor†  
Model No. 06E  
Reciprocating Semi-Hermetic...1750 @ 60 Hz; 1460 @ 50 Hz  
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2  
−275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275  
Oil Charge (Pt)  
21  
17  
5
19  
21  
17  
21  
21  
21  
21  
21  
21  
21  
21  
19  
21  
Capacity Control Steps**  
6
3
3
3
3
CONDENSER FANS (6 Blade) — 60 Hz  
Qty...Dia (in.)  
6...30  
52,000  
1140  
9.4  
6...30  
4...30  
4...30  
4...30  
6...30  
Airflow (Cfm)  
52,000  
1140  
9.5  
35,000  
1140  
6.4  
35,000  
1140  
6.4  
35,000  
1140  
6.4  
52,000  
1140  
9.2  
Speed (Rpm)  
Total Power (kW)  
CONDENSER FANS (6 Blade) — 50 Hz  
Qty...Dia (in.)  
6...30  
52,000  
950  
6...30  
52,000  
950  
4...30  
35,000  
950  
4...30  
35,000  
950  
4...30  
35,000  
950  
6...30  
52,000  
950  
Airflow (Cfm)  
Speed (Rpm)  
Total Power (kW)  
9.4  
9.5  
6.4  
6.4  
6.4  
9.2  
CONDENSER COIL  
Rows...Fins per in.  
Face Area (sq ft)  
Enhanced Copper Tubes, Aluminum Lanced Fin  
3...17  
128.3  
3...17  
128.3  
3...17  
80.5  
3...17  
80.5  
3...17  
80.5  
2...19  
116.7  
Storage Capacity  
178  
178  
110  
110  
110  
110  
(Lb per circuit) at 120 F  
CONNECTIONS  
Suction, ODF (in.)  
Liquid, ODF (in.)  
218  
7
218  
7
258  
258  
258  
258  
8
8
8
8
118  
5
118  
5
118  
5
118  
5
5
5
Hot Gas Bypass, ODF (in.)  
8  
8  
8
8
Table 4B — Units 38AH094-134 Physical Data — 50/60 Hz (SI)  
124  
134  
38AH  
094  
104  
124A  
124B  
134A  
134B  
OPERATING WEIGHT WITH  
Cu-Al  
2308  
2637  
2465  
2794  
1647*  
1843*  
1647*  
1843*  
1647*  
1843*  
1759*  
1948*  
REFRIGERANT (Approx) — Kg Cu-Cu  
SHIP WEIGHT WITH  
Cu-Al  
2554  
2883  
2717  
3046  
1860*  
1968*  
1860*  
1968*  
1860*  
1968*  
1851*  
1968*  
COIL PROTECTION AND SKID Cu-Cu  
(Approx) — Kg  
TYPICAL OPERATING  
REFRIGERANT CHARGE  
(Approx) — Kg  
R-22  
67.1  
2
61.2  
2
39.9  
1
39.9  
1
39.9  
1
47.2  
1
Qty of Circuits  
COMPRESSOR Type...R/s  
(Qty Cyliner) Compressor†  
Model No. 06E  
Reciprocating Semi-Hermetic...29.2 @ 60 Hz; 24.3 @ 50 Hz  
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2  
−275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275  
Oil Charge (L)  
10  
8
5
9
10  
8
10  
10  
10  
10  
10  
10  
10  
10  
9
10  
Capacity Control Steps**  
6
3
3
3
3
CONDENSER FANS (6 Blade) — 60 Hz  
Qty...Dia (mm)  
6...762  
24,544  
19  
6...762  
24,544  
19  
4...762  
16,520  
19  
4...762  
16,520  
19  
4...762  
16,520  
19  
6...762  
24,544  
19  
Airflow (L/s)  
Speed (R/s)  
Total Power (kW)  
9.4  
9.5  
6.4  
6.4  
6.4  
9.2  
CONDENSER FANS (6 Blade) — 50 Hz  
Qty...Dia (mm)  
6...762  
24,544  
15.8  
6...762  
24,544  
15.8  
4...762  
16,520  
15.8  
4...762  
16,520  
15.8  
4...762  
16,520  
15.8  
6...762  
24,544  
15.8  
Airflow (L/s)  
Speed (R/s)  
Total Power (kW)  
9.4  
9.5  
6.4  
6.4  
6.4  
9.2  
CONDENSER COIL  
Rows...Fins per m  
Face Area (sq m)  
Storage Capacity  
(Kg per circuit) at 49 C  
Enhanced Copper Tubes, Aluminum Lanced Fin  
3...669.3  
11.9  
3...669.3  
11.9  
3...669.3  
7.5  
3...669.3  
7.5  
3...669.3  
7.5  
2...781.6  
10.8  
81  
81  
50  
50  
50  
50  
CONNECTIONS  
Suction, ODF (in.)  
Liquid, ODF (in.)  
218  
7
218  
7
258  
258  
258  
258  
8
8
8
8
118  
5
118  
5
118  
5
118  
5
5
5
Hot Gas Bypass, ODF (in.)  
8  
8  
8
8
LEGEND  
NOTES:  
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit  
38AH134 consists of one 134A module and one 134B module.  
2. Certified dimensional drawings available on request.  
Cu-Al  
Cu-Cu  
ODF  
Copper Tubes with Aluminum Fins  
Copper Tubes with Copper Fins  
Outside Diameter, Female  
3. Equivalent connection values in mm are as follows:  
*Includes piping and trim kit.  
†Compressors are shipped with minimum oil charge.  
**Capacity control steps listed are for constant volume units with no accesso-  
ries. Refer to Table 20, page 48, for additional system capacity information.  
in.  
mm  
5
8
8
15.9  
22.2  
28.6  
54.0  
66.7  
7
118  
218  
258  
11  
Fig. 7 — Modules 38AH124A or 134A — Shipping Locations of Piping  
and Sheet Metal Trim Kit  
CONTROL  
BOX  
SHEET METAL COVER  
PANEL (REMOVED)  
RIG  
HERE  
RIG  
HERE  
RIG  
HERE  
24-in. (610-mm)  
SERVICE SPACE  
RIG  
HERE  
Fig. 8 — Correct Placement of Modules Without Piping  
and Sheet Metal Trim (Unit 38AH134 Shown)  
12  
Fig. 9B — Field-Installed Suction Line Loop  
FACTORY-  
INSTALLED  
SUCTION  
LINE LOOP  
Fig. 9A — Typical Module with Cover  
Panels Removed  
38AH044-084,124,134  
MOUNTING SPRINGS  
SHIPMENT BOLTS  
SHIPMENT BOLTS  
38AH094,104  
MOUNTING  
BOLTS  
MOUNTING  
BOLTS  
RAIL BOLT (3) (2 SHOWN)  
RAIL BOLT (3) (2 SHOWN)  
Fig. 10 — Outer View, Compressor Mounting  
13  
38AH044-084 optional single-circuit units) shows required  
location of solenoid valves and recommended locations for  
the filter driers and sight glasses. Complete the refrigerant  
piping from the evaporator to the condenser before opening  
the liquid and suction lines at the condenser.  
Step 3 — Make Refrigerant Piping  
Connections  
The field-supplied liquid line solenoid valve must be  
installed at the evaporator to avoid possible compressor  
damage during unit operation. See Fig. 11 (for 38AH044-  
084 dual-circuit and 38AH094-134 units), or Fig. 12 (for  
38AH044-084 optional single-circuit units).  
Table 5 — Liquid Lift  
MAXIMUM LIQUID LIFT  
UNIT  
60 Hz  
50 Hz  
38AH  
Ft  
69  
75  
75  
45  
75  
55  
50  
75  
45  
M
Ft  
M
044  
054  
064  
074  
084  
094  
104  
124  
134  
21.0  
23.0  
23.0  
13.7  
23.0  
16.7  
15.2  
23.0  
13.7  
57.5  
75.0  
65.0  
37.5  
75.0  
46.0  
42.0  
65.0  
37.5  
17.5  
23.0  
19.8  
11.4  
23.0  
14.0  
12.8  
19.8  
11.4  
The units have large suction lines to minimize friction losses.  
The units also have the ability to operate at low capacity.  
Because of these capabilities, use special care with suction  
piping and suction risers to ensure proper compressor oil  
return under all operating conditions. Maximum allowable  
vertical separation between the condensing unit and the evapo-  
rator is shown in Table 5. Size suction lines in accordance  
with Tables 6A or 6B through 9A or 9B and Fig. 13. Mount  
liquid line solenoid valve just ahead of the TXVs (thermo-  
static expansion valves) which will be mounted at the  
evaporator. See Fig. 11 (for 38AH044-084 dual-circuit and  
38AH094-134 units) or Fig. 12 (for 38AH044-084 optional  
single-circuit units).  
To achieve good mixing of the refrigerant leaving the evapo-  
rator suction header for proper sensing by the TXV bulb:  
1. Install a minimum of two 90-degree elbows upstream of  
the TXV bulb location. See Fig. 14 (for 38AH044-084  
dual-circuit and 38AH094-134 units) or Fig. 15 (for  
38AH044-084 optional single-circuit units).  
UNITS 38AH044-084 — Relieve the pressure caused by the  
holding charge into a refrigerant recovery system. Uncap  
the suction line and cut the run-around tube at the liquid line  
as close to the loop elbow as possible. This will leave  
approximately 2 in. (50 mm) of straight tube for liquid line  
connection.  
IMPORTANT: Protect the liquid valves from the heat  
of brazing.  
2. Locate the TXV bulb on a vertical riser, where possible.  
If a horizontal location is necessary, secure the bulb at  
approximately the 4 o’clock position.  
Leak test the entire system by using soap bubbles and  
nitrogen or R-22 with an electronic leak detector.  
3. Size the suction line from the evaporator to the common  
suction line to achieve high refrigerant velocity. See  
Tables 6A or 6B through 9A or 9B and Fig. 13.  
Purge nitrogen or reclaim R-22 from system after com-  
pletion of leak-checking procedure. Repair leak if one is  
found. When finished, evacuate and dehydrate system using  
the methods described in Carrier GTAC II (General Training  
Air Conditioning II), Module 4, System Dehydration.  
If an oil return connection at the bottom of the suction  
header is supplied with an evaporator, tee-in this connection  
ahead of first mixing elbow. See Fig. 14 (for 38AH044-084  
dual-circuit and 38AH094-134 units) or Fig. 15 (for 38AH044-  
084 optional single-circuit units). When the compressor is  
below the evaporator, the riser at the evaporator should ex-  
tend to the top of the evaporator section. After the riser is  
installed, the suction line can elbow down immediately.  
Install a field-supplied filter drier and sight glasses in each  
refrigerant system. Select the filter drier for maximum unit  
capacity and minimum pressure drop. Figure 11 (for 38AH044-  
084 dual-circuit and 38AH094-134 units) or Fig. 12 (for  
UNITS 38AH094-134 — Relieve the R-22 holding charge  
of each circuit into a refrigerant recovery system. Remove  
the liquid line to factory-installed suction line loop by cut-  
ting the loop at the liquid valve. (See Fig. 9A and 9B.) Cut  
as close to the 90-degree bend in the loop as possible. The  
remaining tube piece in the valve will be used for brazing  
the liquid line. Unbraze and remove the cap from the liquid  
line. For 38AH094 and 104 units, sweat-connect the liquid  
and suction lines from the evaporator. For 38AH124 and 134  
units, see Piping Kit Connections on page 21.  
LEGEND  
LLS  
TXV  
Liquid Line Solenoid  
Thermostatic Expansion Valve  
*Field-Supplied.  
Fig. 11 — Required Location of Solenoid Valves and Recommended Filter Drier and  
Sight Glass Locations for 38AH044-084 Dual-Circuit and 38AH094-134 Units  
14  
*Field-Supplied.  
Fig. 12 — Required Location of Solenoid Valves and Recommended Filter Drier and  
Sight Glass Locations for 38AH044-084 Optional Single-Circuit Units  
LEGEND  
PIPE D DIAMETER  
A
Pipe A, Suction Riser, without Trap  
Pipe B, Suction Riser with Trap  
Suction Line to Condensing Unit  
Pipe D, Suction Riser Short Lift  
Reducer  
Dual Circuit*  
UNIT  
38AH  
B
Single Circuit*  
A
B
C
D
RED.  
STR  
in.  
mm  
in.  
mm  
in.  
mm  
044  
158  
158  
158  
218  
218  
218  
258  
41  
41  
41  
54  
54  
54  
67  
158  
158  
218  
218  
218  
218  
258  
41  
41  
54  
54  
54  
54  
67  
218  
218  
218  
218  
54  
54  
54  
54  
67†  
Street  
054  
NOTES:  
064  
1. Short riser, pipe D, is used when routing suction line to condens-  
ing unit connection. See table at right.  
074  
084  
258  
2. See Tables 6A-9B for values of A, B, and C.  
094, 104  
124, 134  
*Maximum length of riser is 3 ft (914 mm).  
†Double suction riser required if accessory unloader is field  
installed.  
Fig. 13 — Double Suction Riser Construction  
15  
Table 6A — Refrigerant Piping Requirements — 38AH044-104 Dual-Circuit Units — 60 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
15-25  
(4.6-7.6)  
25-50  
(7.6-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
L
S
S
S
S
S
S
5
Ckt A  
8
8
158  
158  
218  
218  
218  
218  
044  
054  
064  
074  
084  
094  
104  
5
Ckt B  
158  
158  
218  
218  
218  
218  
5
7
7
7
7
7
7
7
Ckt A  
Ckt B  
8
8
158  
158  
8
8
158  
218  
8
8
218  
218  
8
218  
218  
8
218  
218  
8
218  
258  
7
118  
118  
118  
7
7
7
7
7
7
Ckt A  
Ckt B  
8
8
158  
8
8
218  
8
8
218  
8
218  
118  
218  
118  
7
218  
218  
218  
118  
218  
118  
258  
118  
7
7
7
Ckt A  
Ckt B  
8
8
218  
218  
8
218  
218  
8
218  
218  
118  
218  
258  
118  
138  
258  
118  
138  
7
118  
118  
118  
258  
7
Ckt A  
Ckt B  
8
8
218  
118  
218  
118  
218  
118  
118  
258  
138  
258  
258  
138  
7
218  
118  
218  
118  
218  
258  
138  
138  
7
Ckt A  
Ckt B  
8
8
218  
218  
118  
218  
218  
118  
118  
258  
118  
258  
138  
118  
258  
138  
138  
7
7
8
218  
118  
258  
258  
7
Ckt A  
Ckt B  
8
8
218  
118  
218  
118  
258  
258  
118  
118  
258  
138  
258  
138  
7
218  
118  
218  
118  
258  
138  
318**  
138  
LEGEND  
5. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop  
design criteria may allow selection of smaller pipe sizes, but at a  
penalty of decreased system capacity and efficiency.  
6. Double suction risers may be required if condensing unit is  
elevated above the evaporator. See footnotes and double suction  
riser table below.  
7. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
8. All pipe sizes are OD inches. Equivalent sizes in millimeters  
follow:  
L
S
Liquid Line  
Suction Line  
*Double suction riser required on units with field installed unloader  
on circuit B compressor if condensing unit is elevated above  
evaporator.  
†Double suction riser required on units with field installed unloader  
on circuit B compressor if condensing unit is elevated above  
evaporator.  
**Double suction riser required on all unit configurations if condens-  
ing unit is elevated above evaporator.  
NOTES:  
in.  
mm  
1. Addition of  
2
unloaders to circuit  
B
compressor is not  
5
8
15.9  
22.2  
28.6  
34.9  
41.3  
54.0  
66.7  
79.4  
recommended.  
7
8
2. 38AH094 and 38AH104 piping sizes apply only to factory sup-  
plied unit configurations. They do NOT take into account any field  
installed unloaders.  
118  
138  
158  
218  
258  
318  
3. Piping sizes are based on unit operation above 40 F (4.4 C) satu-  
rated suction temperature (SST). When operating below 40 F  
(4.4 C), refer to Carrier System Design Manual, E20-IIpiping de-  
sign program, or ASHRAE Handbook to select proper line sizes.  
4. Pipe sizes are based on the total linear length shown for each  
column, plus a 50% allowance for fittings.  
Table 6B — Refrigerant Piping Requirements for Double Suction Risers,  
38AH054-104 Dual-Circuit Units — 60 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
A
B
C
A
B
C
A
B
C
A
B
C
Ckt A  
054  
064  
074  
084  
094  
104  
Ckt B  
158  
218  
258  
Ckt A  
Ckt B  
158  
158  
158  
218  
218  
218  
258  
258  
258  
158  
158  
158  
158  
218  
218  
218  
258  
258  
258  
258  
318  
Ckt A  
Ckt B  
158  
158  
138  
218  
218  
218  
258  
258  
258  
Ckt A  
Ckt B  
158  
138  
218  
218  
258  
258  
Ckt A  
Ckt B  
Ckt A  
Ckt B  
138  
138  
218  
258  
258  
318  
158  
258  
318  
158  
258  
318  
LEGEND  
3. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher design pressure  
drop criteria may allow selection of smaller pipe sizes but at a pen-  
alty of decreased system capacity and efficiency.  
4. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
Not Required  
Pipe A  
Pipe B  
Pipe C  
Suction Riser Without Trap  
Suction Riser With Trap  
Suction Line to Condensing Unit  
NOTES:  
1. See Refrigerant Piping Requirements table at top of page to  
determine need for double suction risers.  
2. Pipe sizes are based on the total linear length, shown for each  
column, plus a 50% allowance for fittings.  
5. All pipe sizes are OD inches. See Table 6A notes for metric  
equivalents.  
6. Refer to Fig. 13 for double suction riser construction.  
16  
Table 7A — Refrigerant Piping Requirements, 38AH044-104 Dual-Circuit Units — 50 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
15-25  
(4.6-7.6)  
25-50  
(7.6-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
L
S
S
S
S
S
S
5
Ckt A  
8
8
138  
158  
158  
218  
218  
218  
044  
054  
064  
074  
084  
094  
104  
5
Ckt B  
138  
158  
158  
218  
218  
218  
5
7
7
7
7
7
7
7
Ckt A  
Ckt B  
8
8
138  
158  
8
8
158  
158  
8
8
158  
218  
8
8
218  
218  
8
218  
8
218  
7
7
118  
218  
118  
258*†  
7
7
7
7
7
7
Ckt A  
Ckt B  
8
8
158  
8
8
158  
8
8
218  
8
8
218  
118  
218  
*
118  
258**  
7
7
158  
218  
218  
218  
118  
258  
118  
258  
258  
*
7
7
7
7
7
Ckt A  
Ckt B  
8
8
158  
218  
8
8
218  
218  
8
218  
218  
8
218  
258  
118  
118  
258  
118  
118  
7
118  
118  
258  
258  
7
7
7
Ckt A  
Ckt B  
8
8
218  
8
8
218  
118  
218  
118  
258  
118  
258  
258  
118  
258  
7
218  
218  
118  
218  
118  
258  
118  
118  
258  
7
Ckt A  
Ckt B  
8
8
218  
218  
118  
218  
218  
118  
118  
258**  
218  
118  
118  
258**  
258*†  
118  
118  
258**  
138  
118  
318**  
258*†  
7
7
8
258*†  
7
7
Ckt A  
Ckt B  
8
8
218  
8
218  
118  
218  
118  
258**  
118  
258**  
258  
138  
318**  
7
218  
118  
218  
118  
258  
118  
258  
138  
138  
318**  
LEGEND  
5. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop  
design criteria may allow selection of smaller pipe sizes, but at a  
penalty of decreased system capacity and efficiency.  
6. Double suction risers may be required if condensing unit is  
elevated above the evaporator. See footnotes and double suction  
riser table below.  
7. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
8. All pipe sizes are OD inches. Equivalent sizes in millimeters  
follow:  
L
S
Liquid Line  
Suction Line  
*Double suction riser required on units with field installed unloader  
on circuit B compressor if condensing unit is elevated above  
evaporator.  
†Double suction riser required on units with field installed unloader  
on circuit B compressor if condensing unit is elevated above  
evaporator.  
**Double suction riser required on all unit configurations if condens-  
ing unit is elevated above evaporator.  
NOTES:  
in.  
mm  
1. Addition of  
2
unloaders to circuit  
B
compressor is not  
5
8
15.9  
22.2  
28.6  
34.9  
41.3  
54.0  
66.7  
79.4  
recommended.  
7
8
2. 38AH094 and 38AH104 piping sizes apply only to factory sup-  
plied unit configurations. They do NOT take into account any field  
installed unloaders.  
118  
138  
158  
218  
258  
318  
3. Piping sizes are based on unit operation above 40 F (4.4 C) satu-  
rated suction temperature (SST). When operating below 40 F  
(4.4 C), refer to Carrier System Design Manual, E20-IIpiping de-  
sign program, or ASHRAE Handbook to select proper line sizes.  
4. Pipe sizes are based on the total linear length shown for each  
column, plus a 50% allowance for fittings.  
Table 7B— Refrigerant Piping Requirements for Double Suction Risers,  
38AH054-104 Dual-Circuit Units — 50 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
A
B
C
A
B
C
A
B
C
A
B
C
Ckt A  
138  
158  
218  
138  
158  
218  
054  
064  
074  
084  
094  
104  
Ckt B  
158  
218  
258  
Ckt A  
Ckt B  
158  
158  
218  
158  
218  
258  
158  
218  
258  
158  
218  
258  
Ckt A  
Ckt B  
158  
138  
138  
138  
218  
218  
218  
218  
258  
258  
258  
258  
158  
158  
158  
158  
158  
218  
218  
218  
218  
218  
258  
258  
258  
258  
258  
158  
158  
158  
158  
218  
218  
258  
218  
258  
258  
318  
258  
Ckt A  
Ckt B  
138  
218  
258  
Ckt A  
Ckt B  
Ckt A  
Ckt B  
158  
258  
318  
158  
258  
318  
LEGEND  
3. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher design pressure  
drop criteria may allow selection of smaller pipe sizes but at a pen-  
alty of decreased system capacity and efficiency.  
4. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
Not Required  
Pipe A  
Pipe B  
Pipe C  
Suction Riser Without Trap  
Suction Riser With Trap  
Suction Line to Condensing Unit  
NOTES:  
1. See Refrigerant Piping Requirements table at top of page to  
determine need for double suction risers.  
2. Pipe sizes are based on the total linear length, shown for each  
column, plus a 50% allowance for fittings.  
5. All pipe sizes are OD inches. See Table 7A notes for metric  
equivalents.  
6. Refer to Fig. 13 for double suction riser construction.  
17  
Table 8A — Refrigerant Piping Requirements for 38AH044-084  
Optional Single-Circuit Units and 38AH124,134  
Modular Units (Dual-Circuit) — 60 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
15-20  
(4.6-6.1)  
20-50  
(6.1-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
L
S
218  
218  
S
218  
258  
L
118  
118  
S
218  
258  
L
118  
118  
S
258  
258  
L
138  
138  
S
258  
318  
L
138  
138  
S
318  
318  
7
044  
054  
8
*
*
*
*
*
7
8
064;  
Modules 124A,  
124B,134A  
118  
218  
118  
258  
118  
258  
138  
318  
*
138  
318  
*
138  
318  
*
074;  
118  
118  
218  
258  
118  
118  
258  
258  
138  
138  
318  
318  
138  
138  
318  
318  
138  
158  
318  
358  
158  
158  
358  
358  
*
Module 134B  
084  
*
LEGEND  
design criteria may allow selection of smaller pipe sizes, but at a  
penalty of decreased system capacity and efficiency.  
5. Double suction risers may be required if condensing unit is  
elevated above the evaporator. See footnotes and double suction  
riser table below.  
6. Refer to Carrier System Design Manual, E20-II design program,  
or ASHRAE Handbook for further information on selecting pipe  
sizes for split systems.  
7. All pipe sizes are OD inches. Equivalent sizes in millimeters  
follow:  
CV  
L
Constant Volume  
Liquid Line  
S
Suction Line  
VAV  
Variable Air Volume  
*Double suction riser required on all units configurations if condens-  
ing unit is elevated above evaporator.  
†Double suction riser required on units with factory installed VAV op-  
tion or CV units with additional field installed unloader on circuit A1  
(lead) compressor if condensing unit is elevated above evaporator.  
in.  
mm  
NOTES:  
7
1. Addition of field-installed unloaders on A2 (lag) compressor is not  
recommended.  
8
22.2  
28.6  
34.9  
41.3  
54.0  
66.7  
79.4  
92.1  
118  
138  
158  
218  
258  
318  
358  
2. Piping sizes are based on unit operation above 40 F (4.4 C) satu-  
rated suction temperature (SST). When operating below 40 F  
(4.4 C), refer to Carrier System Design Manual, E20-IIpiping  
design program, or ASHRAE Handbook to select proper line sizes.  
3. Pipe sizes are based on the total linear length shown for each  
column, plus a 50% allowance for fittings.  
4. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop  
Table 8B — Refrigerant Piping Requirements for Double Suction Risers,  
38AH044-084 Optional Single-Circuit Units and 38AH124,134  
Modular Units (Dual-Circuit) — 60 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT  
UNIT  
38AH  
15-50  
(4.6-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
A
B
C
A
B
C
A
158  
B
218  
C
258  
A
158  
158  
B
218  
258  
C
258  
318  
A
158  
158  
B
258  
258  
C
318  
318  
044  
054  
064  
Modules 124A,  
124B,134A  
158  
218  
258  
158  
218  
258  
158  
258  
318  
158  
258  
318  
158  
258  
318  
074;  
158  
158  
218  
218  
258  
258  
158  
158  
258  
258  
318  
318  
158  
158  
258  
258  
318  
318  
158  
218  
258  
318  
318  
358  
218  
218  
318  
318  
358  
358  
Module 134B  
084  
LEGEND  
3. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher design pressure  
drop criteria may allow selection of smaller pipe sizes but at a pen-  
alty of decreased system capacity and efficiency.  
4. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
Not Required  
Pipe A  
Pipe B  
Pipe C  
Suction Riser Without Trap  
Suction Riser With Trap  
Suction Line to Condensing Unit  
NOTES:  
1. See Refrigerant Piping Requirements table at top of page to de-  
termine need for double suction risers.  
2. Pipe sizes are based on the total linear length, shown for each  
column, plus a 50% allowance for fittings.  
5. All pipe sizes are OD inches. See Table 8A notes for metric  
equivalents.  
6. Refer to Fig. 13 for double suction riser construction.  
18  
Table 9A — Refrigerant Piping Requirements for 38AH044-084  
Optional Single-Circuit Units and 38AH124,134  
Modular Units (Dual Circuit) — 50 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
15-20  
(4.6-6.1)  
20-50  
(6.1-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
L
S
218  
218  
S
218  
218  
L
118  
118  
S
218  
258  
L
118  
118  
S
258  
258  
L
118  
118  
S
258  
258  
L
138  
138  
S
258  
318  
7
044  
054  
8
*
*
*
*
*
*
7
8
*
064;  
7
Modules 124A,  
124B, 134A  
8
8
218  
118  
258  
118  
258  
118  
258  
138  
318  
*
138  
318  
*
074;  
Module 134B  
7
218  
218  
118  
118  
258  
258  
118  
138  
258  
318  
138  
138  
318  
318  
*
138  
138  
318  
318  
*
138  
158  
318  
358  
*
084  
118  
*
*
*
*
LEGEND  
design criteria may allow selection of smaller pipe sizes, but at a  
penalty of decreased system capacity and efficiency.  
5. Double suction risers may be required if condensing unit is  
elevated above the evaporator. See footnotes and double suction  
riser table below.  
6. Refer to Carrier System Design Manual, E20-II design program,  
or ASHRAE Handbook for further information on selecting pipe  
sizes for split systems.  
7. All pipe sizes are OD inches. Equivalent sizes in millimeters  
follow:  
CV  
L
Constant Volume  
Liquid Line  
S
Suction Line  
VAV  
Variable Air Volume  
*Double suction riser required on all units configurations if condens-  
ing unit is elevated above evaporator.  
†Double suction riser required on units with factory installed VAV op-  
tion or CV units with additional field installed unloader on circuit A1  
(lead) compressor if condensing unit is elevated above evaporator.  
in.  
mm  
NOTES:  
7
1. Addition of field-installed unloaders on A2 (lag) compressor is not  
recommended.  
8
22.2  
28.6  
34.9  
41.3  
54.0  
66.7  
79.4  
92.1  
118  
138  
158  
218  
258  
318  
358  
2. Piping sizes are based on unit operation above 40 F (4.4 C) satu-  
rated suction temperature (SST). When operating below 40 F  
(4.4 C), refer to Carrier System Design Manual, E20-IIpiping  
design program, or ASHRAE Handbook to select proper line sizes.  
3. Pipe sizes are based on the total linear length shown for each  
column, plus a 50% allowance for fittings.  
4. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop  
Table 9B — Refrigerant Piping Requirements for Double Suction Risers,  
38AH044-084 Optional Single-Circuit Units and 38AH124,134  
Modular Units (Dual Circuit) — 50 Hz  
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)  
UNIT  
38AH  
15-20  
(4.6-6.1)  
20-50  
(6.1-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
100-150  
(30.5-45.7)  
150-200  
(45.7-61.0)  
A
B
C
A
B
C
A
158  
B
218  
C
258  
A
158  
158  
B
218  
218  
C
258  
258  
A
158  
158  
B
258  
218  
C
258  
258  
A
158  
158  
B
258  
258  
C
258  
318  
044  
054  
064;  
Modules 124A,  
124B, 134A  
158  
218  
258  
158  
218  
258  
158  
218  
258  
158  
258  
318  
158  
258  
318  
074;  
158  
158  
218  
218  
258  
258  
158  
158  
218  
258  
258  
318  
158  
158  
258  
258  
318  
318  
158  
158  
258  
258  
318  
318  
158  
158  
318  
318  
358  
358  
Module 134B  
084  
LEGEND  
Not Required  
3. Suction and liquid line sizing is based on pressure drop equivalent  
to 2 F (1.1 C) at nominal rating conditions. Higher design pressure  
drop criteria may allow selection of smaller pipe sizes but at a pen-  
alty of decreased system capacity and efficiency.  
4. Refer to Carrier System Design Manual or to E20-II design  
programs for further information on selecting pipe sizes for split  
systems.  
Pipe A  
Pipe B  
Pipe C  
Suction Riser Without Trap  
Suction Riser With Trap  
Suction Line to Condensing Unit  
NOTES:  
1. See Refrigerant Piping Requirements table at top of page to  
determine need for double suction risers.  
2. Pipe sizes are based on the total linear length, shown for each  
column, plus a 50% allowance for fittings.  
5. All pipe sizes are OD inches. See Table 9A notes for metric  
equivalents.  
6. Refer to Fig. 13 for double suction riser construction.  
19  
LEGEND  
TXV  
TYP  
Thermostatic Expansion Valve  
Typical  
NOTE: Lower split first on, last off.  
Fig. 14 — Typical Piping Connections for Face Split Coils for 38AH044-084 Dual-Circuit  
and 38AH094-134 Units  
LEGEND  
TXV  
TYP  
Thermostatic Expansion Valve  
Typical  
NOTE: Lower split first on, last off.  
Fig. 15 — Typical Piping Connections for Face Split Coils for 38AH044-084  
Optional Single-Circuit Units  
20  
Units 38AH124 and 134 Piping Kit Connections — The  
38AH124 and 134 units are delivered with a factory-  
supplied suction and liquid piping kit for installation in the  
24-in. (610-mm) service space between the 2 unit modules.  
The piping kit allows for a common unit side piping con-  
nection from the indoor unit to each of the condensing unit  
refrigeration circuits. Fittings are provided and shipped in  
the control box.  
align holes and reinsert screws B. Place horizontal cover on  
top of Module 134A end cover with opposite side resting on  
the horizontal flange of the installed Module B vertical top  
cover piece. Align holes on flange and top cover. Reinsert  
screws A through the top cover holes into the end cover. From  
within the service space, insert supplied screws up through  
the flange and horizontal cover to make a secure connection  
between the horizontal and vertical cover pieces.  
Insert supplied screws into each of the 2 holes in the ver-  
tical side flange of the top cover at each end of the service  
space.  
Remove the copper tubes from Module 124A or 134A com-  
pressor rails. Save the pipe clamps for later use. Cut the  
258-in. (67-mm) suction tube into 2 pieces: 28 in. (711 mm)  
and 67 in. (1702 mm). Connect the 2 formed 118-in.  
(29-mm) tubes to the liquid line connection at the liquid valve.  
See Fig. 16.  
Attach Side Panels — Insert side panels at the ends of the  
service space and hook side panel flange over the 2 screws  
previously inserted in the top cover flange. Fasten panels to  
the corner posts with supplied self-drilling screws, 3 per side.  
See Fig. 19.  
NOTE: Piping kit is designed to allow air handler connec-  
tions to project from either side of the service space.  
To prepare condensing unit modules for piping connec-  
tion, refer to beginning paragraphs of Step 3 — Make  
Refrigeration Piping Connections, page 14.  
Connect Tubing from Evaporator to Unit  
Two 258-in. (67-mm) and one 118-in. (29-mm) elbows are  
supplied for piping connections. Fit tubing to ensure proper  
installation. All tubes should have equal lengths projecting  
beyond unit corner posts. See Fig. 16. Ensure suction tube  
is level for oil return requirements.  
Protect liquid valves from the heat of brazing.  
Braze the liquid and suction lines from the evaporator to  
the condensing unit liquid and suction lines. Leak test the  
entire system by the pressure method described in the  
Carrier Standard Service Techniques Manual, Chapter 1,  
Section 1-6. Use R-22 at approximately 25 psig (172 kPa)  
backed up with an inert gas to a total pressure not to exceed  
245 psig (1689 kPa). If a leak is detected, evacuate and de-  
hydrate the system. Follow methods described in the Carrier  
Service Manual, Chapter 1, Section 1-7.  
Protect liquid valves from the heat of brazing.  
Braze the piping connections.  
Level the tubes and clamp to the corner posts with factory-  
supplied self-drilling screws and pipe clamps removed from  
Module 124A or 134A during piping kit removal.  
Units 38AH124 and 134 Sheet Metal Trim Kit Installation  
— After the units are in place and the piping kit is installed,  
install the sheet metal trim kit.  
NOTE: Install sheet metal trim kit before connection to air  
handler tubing in case the modules must be repositioned to  
accommodate the sheet metal installation.  
Remove two 43-in. (1092 mm) base rail trim pieces from  
Module 124A or 134A base rail. Remove the 3 corner post  
bolts from the bottom of each corner post at the service space.  
Align the base rail trim piece holes over the bolt holes in the  
corner rails. See Fig. 17. Reinsert corner post bolts through  
the trim piece into the corner posts.  
Attach Top Cover — To attach top cover, proceed as  
follows:  
For Unit 38AH124, remove screws A from top of each of  
4 corner posts at service space. See Fig. 18. Place cover on  
top of service space and align top cover slots with corner  
post screw holes. Reinsert screws A.  
NOTES:  
For Unit 38AH134, remove screws A from top of each cor-  
ner post on Module 134A and screws B from top of each  
corner post on Module 134B. See Fig. 18. Top cover is in  
2 pieces: one vertical piece and one horizontal piece. Slide  
vertical top cover partly under Module 134B end cover flange;  
1. Ensure suction tube is level for oil return requirements.  
2. Protect liquid valves from heat of brazing.  
Fig. 16 — Units 38AH124 and 134 with Installed  
Piping Kit  
21  
CORNER  
SCREWS (2) CORNER  
TOP  
MODULE  
124B  
OR 134B  
MODULE  
124A  
POST (4 PER FOR  
POST  
COVER  
MODULE)  
MOUNTING (4 PER  
FLANGE OR 134A  
SIDE PANEL MODULE)  
BASE RAIL  
BOLTS (6)  
CORNER  
POST  
CORNER POST  
FACTORY-SUPPLIED  
SELF-DRILLING  
SCREWS (4 PER  
CORNER POST)  
Fig. 17 — Units 38AH124 and 134 with Installed Trim  
Kit Rails  
24-in. (610-mm)  
SERVICE WAY  
Fig. 19 — Fully Assembled Piping and Trim Kit  
(Unit 38AH134 Shown)  
SCREWS A  
TOP COVER,  
HORIZONTAL  
PIECE  
TOP COVER,  
VERTICAL  
PIECE  
SCREWS B  
VERTICAL  
END COVER  
FLANGES  
TOP COVER  
FLANGE  
END COVER  
(HIDDEN)  
24-in. (610-mm)  
SERVICE WAY  
CORNER MODULE 124B  
CORNER MODULE 124A  
POST OR 134A  
POST  
OR 134B  
Fig. 18 — Units 38AH124 and 134 with Installed Top  
Cover (Unit 38AH134 Shown)  
22  
MAIN POWER — Units 38AH044-104 have single-point  
power connection to simplify field-power wiring (all power  
enters at one end). Units 38AH124 and 134 require 2 con-  
nection points, one for each module. Units may use copper,  
copper-clad aluminum, or aluminum conductors at all volt-  
ages. The maximum wire size units can accept per terminal  
block is 500 kcmil.  
Step 4 — Make Electrical Connections  
POWER SUPPLY — Electrical characteristics of available  
power supply must agree with unit nameplate rating. Supply  
voltage must be within the limits shown in Tables 10A or  
10B, 11 and 12. See Table 13 for control circuit data and  
Table 14 for fan motor electrical data.  
Power must be supplied as shown in Table 15.  
IMPORTANT: Operation of unit on improper supply  
voltage or with excessive phase imbalance constitutes  
abuse and can affect any Carrier warranty.  
CONTROL CIRCUIT WIRING — Control circuit wiring is  
accomplished with a step-down transformer on voltage des-  
ignations 500, 600, and 100 in table below where the pri-  
mary voltage is field voltage. For 208/230-v, 3-ph, 60-Hz  
units, ensure that the transformer primary is wired properly  
for the voltage which will be applied. All control wiring must  
comply with applicable local and national codes. The safety  
circuits are 24 v on all units. The safety circuit voltage is  
created with a step-down transformer where main control  
voltage is the transformer primary voltage.  
FIELD POWER CONNECTIONS — All power wiring must  
comply with applicable local and national codes. Install field-  
supplied, branch circuit safety disconnect(s) of a type that  
can be locked off/open. Disconnects must be located within  
sight of, and readily accessible from, the unit in compliance  
with NEC (National Electrical Code) (U.S.A. Standard)  
Article 440-14.  
See Table 13 for control circuit information.  
All field power enters the unit through a hole in the con-  
trol box shelf. Refer to Fig. 20-28 for field wiring details.  
Table 10A — Electrical Data — 50/60 Hz (38AH044-084 Dual-Circuit Units)  
STANDARD UNIT  
COMPRESSOR*  
A1 B1  
Compressor  
A1/B1  
Supply Voltage†  
Voltage  
Nameplate  
V-Ph-Hz  
38AH  
044  
MCA  
MOCP  
ICF  
Designation  
Min  
Max  
RLA  
LRA  
RLA  
LRA  
Model No.  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
198  
342  
325  
254  
508  
632  
418  
254  
440  
367  
179.4  
91.3  
225  
100  
100  
125  
225  
100  
125  
434.7  
218.6  
162.4  
241.2  
296.7  
219.6  
165.9  
67.9  
34.6  
28.8  
34.6  
67.9  
34.6  
33.3  
345  
173  
120  
191  
207  
173  
115  
67.9  
34.6  
28.8  
34.6  
67.9  
34.6  
33.3  
345  
173  
120  
191  
207  
173  
115  
600  
100  
575-3-60  
78.4  
200  
06E4250/250  
380-3-60  
230-3-50  
380/415-3-50  
346-3-50  
93.5  
800 (PW)  
900  
180.2  
91.5  
300 (PW)  
100.0  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
206.6  
102.4  
88.0  
107.1  
102.7  
107.0  
250  
125  
125  
150  
125  
150  
535.7  
268.6  
206.4  
297.2  
269.6  
198.9  
67.9  
34.6  
28.8  
34.6  
34.6  
33.3  
345  
173  
120  
191  
173  
115  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
446  
223  
164  
247  
223  
148  
600  
100  
575-3-60  
054  
064  
074  
084  
06E4250/265  
06E8265/275  
06E8275/299  
06E8299/299  
200  
380-3-60  
380/415-3-50  
346-3-50  
900  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
249.3  
115.5  
100.6  
126.9  
114.1  
129.8  
350  
150  
125  
175  
150  
175  
617.5  
307.6  
226.1  
341.1  
335.6  
230.5  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
446  
223  
164  
247  
223  
148  
106.4  
46.8  
40.4  
52.6  
46.8  
53.8  
506  
253  
176  
280  
280  
168  
600  
100  
575-3-60  
380-3-60  
200  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
330.5  
148.6  
132.2  
174.5  
143.0  
170.8  
450  
200  
175  
250  
200  
250  
829.0  
408.2  
336.8  
458.0  
403.8  
300.4  
106.4  
46.8  
40.4  
52.6  
46.8  
53.8  
506  
253  
176  
280  
280  
168  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
600  
100  
575-3-60  
380-3-60  
200  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
371.5  
167.2  
148.9  
200.7  
167.6  
205.3  
500  
225  
200  
250  
225  
250  
870.0  
426.8  
353.5  
484.2  
428.4  
334.9  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
600  
100  
575-3-60  
380-3-60  
200  
900  
380/415-3-50  
346-3-50  
300 (PW)  
See page 24 for Legend and Notes.  
23  
Table 10B — Electrical Data — 50/60 Hz (38AH044-084 Optional Single-Circuit Units)  
OPTIONAL SINGLE-CIRCUIT UNIT  
COMPRESSOR*  
A1 A2  
Compressor  
Supply Voltage  
Voltage  
Nameplate  
V-Ph-Hz  
38AH  
044  
A1/A2  
Model No.  
MCA  
MOCP  
ICF  
Designation  
Min  
Max  
RLA  
LRA  
RLA  
LRA  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
198  
342  
325  
254  
508  
632  
418  
254  
440  
367  
179.4  
91.3  
225  
100  
100  
125  
225  
100  
125  
434.7  
218.6  
162.4  
241.2  
296.7  
219.6  
165.9  
67.9  
34.6  
28.8  
34.6  
67.9  
34.6  
33.3  
345  
173  
120  
191  
207  
173  
115  
67.9  
34.6  
28.8  
34.6  
67.9  
34.6  
33.3  
345  
173  
120  
191  
207  
173  
115  
600  
100  
575-3-60  
78.4  
200  
06E4250/250  
380-3-60  
230-3-50  
380/415-3-50  
346-3-50  
93.5  
800 (PW)  
900  
180.2  
91.5  
300 (PW)  
100.0  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
206.6  
102.4  
88.0  
107.1  
102.7  
107.0  
250  
125  
125  
150  
125  
150  
535.7  
268.6  
206.4  
297.2  
269.6  
198.9  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
446  
223  
164  
247  
223  
148  
67.9  
34.6  
28.8  
34.6  
34.6  
33.3  
345  
173  
120  
191  
173  
115  
600  
100  
575-3-60  
054  
064  
074  
084  
06E4265/250  
06E8275/265  
06E8299/275  
200  
380-3-60  
380/415-3-50  
346-3-50  
900  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
249.3  
115.5  
100.6  
126.9  
115.7  
129.8  
350  
150  
125  
175  
150  
175  
617.5  
307.6  
226.1  
341.1  
335.6  
230.5  
106.4  
46.8  
40.4  
52.6  
46.8  
53.8  
506  
253  
176  
280  
280  
168  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
446  
223  
164  
247  
223  
148  
600  
100  
575-3-60  
380-3-60  
200  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
330.5  
148.6  
132.2  
174.5  
143.0  
170.8  
450  
200  
175  
250  
200  
250  
829.0  
408.2  
336.8  
458.0  
403.8  
300.4  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
106.4  
46.8  
40.4  
52.6  
46.8  
53.8  
506  
253  
176  
280  
280  
168  
600  
100  
575-3-60  
380-3-60  
200  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
187  
414  
518  
342  
342  
325  
254  
508  
632  
418  
440  
367  
371.5  
167.2  
148.9  
200.7  
167.6  
205.3  
500  
225  
200  
250  
225  
250  
870.0  
426.8  
353.5  
484.2  
428.4  
334.9  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
147.4  
65.4  
57.1  
78.8  
65.4  
79.5  
690  
345  
276  
382  
345  
229  
600  
100  
575-3-60  
06E8299/299  
LEGEND  
200  
380-3-60  
380/415-3-50  
346-3-50  
900  
300 (PW)  
*All compressors are across-the-line start only except 38AH044  
230 v, 3-phase, 50 Hz; and all 346 v, 3-phase, 50 Hz.  
FLA  
ICF  
Full Load Amps  
†Units are suitable for use on electrical systems where voltage sup-  
plied to unit terminals is within listed minimum to maximum limits.  
Maximum Instantaneous Current Flow During Starting.  
(The point in the starting sequence where the sum of  
the LRA for the starting compressors, plus the total RLA  
for all running compressors, plus the FLA for all running  
fan motors is maximum.)  
NOTES:  
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.  
2. Maximum incoming wire size for terminal block is 500 kcmil.  
kcmil  
LRA  
Max  
Thousand Circular Mils  
Locked Rotor Amps  
Maximum  
MCA  
Minimum Circuit Amps (used for sizing; complies with  
National Electrical Code [NEC] [U.S.A. Standard],  
section 430-24).  
Min  
MOCP  
Minimum  
Maximum Overcurrent Protection (used for sizing dis-  
connect; complies with NEC Article 440, Section 22).  
Rated Load Amps  
RLA  
PW  
Part Wind Only  
24  
Table 11 — Electrical Data — 50/60 Hz (Units 38AH094,104)  
COMPRESSOR†  
A2 B1  
RLA LRA RLA LRA RLA LRA RLA LRA  
SUPPLY  
UNIT  
VOLTAGE  
NAMEPLATE  
V-Ph-Hz  
VOLTAGE*  
MCA MOCP ICF  
A1  
B2  
38AH DESIGNATION  
Min  
187  
414  
518  
342  
342  
325  
187  
414  
518  
342  
342  
325  
Max  
253  
506  
633  
418  
440  
380  
253  
506  
633  
418  
440  
380  
500  
600  
208/230-3-60  
460-3-60  
398.5  
183.1  
160.9  
209.1  
183.6  
212.9  
399.4  
196.3  
168.0  
205.9  
196.7  
205.6  
500  
225  
200  
250  
225  
250  
450  
225  
200  
250  
225  
250  
897 106.4 506  
67.9  
34.6  
28.8  
34.6  
34.6  
33.3  
67.9  
34.6  
28.8  
34.6  
34.6  
33.3  
345 147.7 690  
443  
366  
493  
444  
343  
722  
361  
286  
396  
363  
298  
46.8 253  
40.4 176  
52.6 280  
46.8 280  
53.8 168  
89.7 446  
43.6 223  
36.5 164  
45.5 247  
43.6 223  
44.9 148  
173  
120  
191  
173  
115  
345  
173  
120  
191  
173  
229  
65.4  
57.1  
78.8  
65.4  
79.5  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
345  
276  
382  
345  
229  
446  
223  
164  
247  
223  
148  
100  
575-3-60  
094  
200  
380-3-60  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
89.7  
43.6  
36.5  
45.5  
43.6  
49.9  
446  
223  
164  
247  
223  
148  
600  
100  
575-3-60  
104  
200  
380-3-60  
900  
380/415-3-50  
346-3-50  
300 (PW)  
LEGEND  
*Units are suitable for use on electrical systems where voltage sup-  
plied to unit terminals is within listed minimum to maximum limits.  
†All compressors are across-the-line start only except 346-V, 3-ph,  
50-Hz units.  
FLA  
ICF  
Not Applicable  
Full Load Amps  
Maximum Instantaneous Current Flow During Starting.  
(The point in the starting sequence where the sum of  
the LRA for the starting compressors, plus the total RLA  
for all running compressors, plus the FLA for all running  
fan motors is maximum.)  
Thousand Circular Mils  
Locked Rotor Amps  
NOTES:  
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.  
2. Maximum incoming wire size for terminal block is 500 kcmil.  
3. For units 38AH094 and 104 compressor model numbers, see table  
below:  
kcmil  
LRA  
MCA  
Minimum Circuit Amps (used for sizing; complies with  
National Electrical Code [NEC] [U.S.A. Standard],  
section 430-24).  
UNIT  
094  
A2  
104  
38AH  
MOCP  
RLA  
Maximum Overcurrent Protection (used for sizing  
disconnect; complies with NEC [U.S.A. Standard],  
section 440-22).  
CKT  
A1  
B1  
A1  
A2  
B1  
B2  
MODEL  
NO. 06E  
−275 −250 −299 −265 −250 −265 −265  
Rated Load Amps  
25  
Table 12 — Electrical Data — 50/60 Hz (Units 38AH124, 134)  
COMPRESSOR†  
A1 A2  
SUPPLY  
UNIT  
38AH  
COMPRESSOR  
A1/A2  
VOLTAGE  
NAMEPLATE  
V-Ph-Hz  
VOLTAGE*  
MCA  
MOCP  
ICF  
DESIGNATION  
MODULE  
MODEL NO.  
Min  
187  
414  
518  
342  
342  
325  
187  
414  
518  
342  
342  
325  
Max  
254  
508  
632  
418  
440  
367  
254  
508  
632  
418  
440  
367  
RLA  
617.5 106.4  
LRA  
506  
253  
176  
280  
280  
168  
690  
345  
276  
382  
345  
229  
RLA  
LRA  
446  
223  
164  
247  
223  
148  
506  
253  
176  
280  
280  
168  
500  
208/230-3-60  
460-3-60  
249.3  
115.5  
100.6  
126.9  
115.7  
129.8  
330.5  
148.6  
132.2  
174.5  
149.0  
170.8  
350  
150  
125  
175  
150  
175  
450  
200  
175  
250  
200  
250  
89.7  
43.6  
36.5  
45.5  
43.6  
44.9  
106.4  
46.8  
40.4  
52.6  
46.8  
53.8  
600  
307.6  
226.1  
341.1  
335.6  
230.5  
46.8  
40.4  
52.6  
46.8  
53.8  
124A  
124B  
134A  
100  
575-3-60  
06E8275/  
265  
200  
380-3-60  
900  
380/415-3-50  
346-3-50  
300 (PW)  
500  
208/230-3-60  
460-3-60  
829.0 147.4  
600  
408.2  
336.8  
458.0  
403.8  
300.4  
65.4  
57.1  
78.8  
65.4  
79.5  
100  
575-3-60  
06E8299/  
275  
134B  
200  
380-3-60  
900  
380/415-3-50  
346-3-50  
300 (PW)  
LEGEND  
*Units are suitable for use on electrical systems where voltage sup-  
plied to unit terminals is within listed minimum to maximum limits.  
†All compressors are across-the-line start only except 346-v, 3-ph,  
50 Hz unit.  
FLA  
ICF  
Full Load Amps  
Maximum Instantaneous Current Flow During Starting.  
(The point in the starting sequence where the sum of  
the LRA for the starting compressors, plus the total RLA  
for all running compressors, plus the FLA for all running  
fan motors is maximum.)  
Thousand Circular Mils  
Locked Rotor Amps  
NOTES:  
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.  
2. Maximum incoming wire size for terminal block is 500 kcmil.  
kcmil  
LRA  
MCA  
Minimum Circuit Amps (used for sizing; complies with  
National Electrical Code [NEC] [U.S.A. Standard],  
section 430-24).  
Maximum Overcurrent Protection (used for sizing  
disconnect; complies with NEC [U.S.A. Standard],  
section 440- 22).  
Part Wind  
Rated Load Amps  
MOCP  
PW  
RLA  
Table 13 — Control Circuit Electrical Data — 50/60 Hz  
UNIT POWER  
V-Ph-Hz  
CONTROL POWER  
UNIT  
DESIGNATION  
AMPS  
V-Ph-Hz  
Min  
Max  
−500  
−600  
−100  
−200  
−800  
−900  
−300  
208/230-3-60  
460-3-60  
115-1-60  
115-1-60  
115-1-60  
230-1-60  
230-1-50  
230-1-50  
200-1-50  
103  
103  
103  
207  
207  
207  
180  
127  
127  
127  
253  
253  
253  
220  
4.1  
4.1  
4.1  
2.0  
2.0  
2.0  
2.4  
575-3-60  
380-3-60  
230-3-50  
380/415-3-50  
346-3-50  
NOTE: Units 38AH124 and 134 have 2 control boxes per unit, one in each module.  
26  
Table 14 — Fan Motor Electrical Data  
CONDENSER FAN  
UNIT  
38AH  
Nameplate  
V-Ph-Hz  
Hp  
(kW)  
Total  
kW  
Qty  
(No.*) FLA Each  
(No.*) LRA Each  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3,4) 6.6  
(1,2) 2.8 (3,4) 3.3  
(1-4) 3.4  
(1,2) 30.0 (3,4) 31.6  
(1,2) 30.0 (3,4) 31.6  
(1-4) 30.0  
575-3-60  
1
044  
380-3-60  
4
6.2  
(1-4) 3.9  
(1-4) 20.9  
(0.746)  
230-3-50  
(1,2) 5.5 (3,4) 6.8  
(1-4) 3.4  
(1,2) 30.0 (3,4) 31.6  
(1-4) 30.0  
380/415-3-50  
346-3-50  
(1-4) 4.4  
(1-4) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3,4) 6.6  
(1,2) 2.8 (3,4) 3.3  
(1-4) 3.4  
(1,2) 30.0 (3,4) 31.6  
(1,2) 30.0 (3,4) 31.6  
(1-4) 30.0  
575-3-60  
1
054  
064  
074  
084  
094  
104  
4
4
6
6
6
6
6.2  
6.2  
9.3  
9.3  
9.4  
9.5  
(0.746)  
380-3-60  
(1-4) 3.9  
(1-4) 20.9  
380/415-3-50  
346-3-50  
(1-4) 3.4  
(1-4) 30.0  
(1-4) 4.4  
(1-4) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3,4) 6.6  
(1,2) 2.8 (3,4) 3.3  
(1-4) 3.4  
(1,2) 30.0 (3,4) 31.6  
(1,2) 30.0 (3,4) 31.6  
(1-4) 30.0  
575-3-60  
1
(0.746)  
380-3-60  
(1-4) 3.9  
(1-4) 20.9  
380/415-3-50  
346-3-50  
(1-4) 3.4  
(1-4) 30.0  
(1-4) 4.4  
(1-4) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3-6) 6.6  
(1,2) 2.8 (3-6) 3.3  
(1-6) 3.4  
(1,2) 30.0 (3-6) 31.6  
(1,2) 30.0 (3-6) 31.6  
(1-6) 30.0  
575-3-60  
1
(0.746)  
380-3-60  
(1-6) 3.9  
(1-6) 20.9  
380/415-3-50  
346-3-50  
(1-6) 3.4  
(1-6) 30.0  
(1-6) 4.4  
(1-6) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3-6) 6.6  
(1,2) 2.8 (3-6) 3.3  
(1-6) 3.4  
(1,2) 30.0 (3-6) 31.6  
(1,2) 30.0 (3-6) 31.6  
(1-6) 30.0  
575-3-60  
1
(0.746)  
380-3-60  
(1-6) 3.9  
(1-6) 20.9  
380/415-3-50  
346-3-50  
(1-6) 3.4  
(1-6) 30.0  
(1-6) 4.4  
(1-6) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3-6) 6.6  
(1-2) 2.8 (3-6) 3.3  
(1-6) 3.4  
(1,2) 30.0 (3-6) 31.6  
(1,2) 30.0 (3-6) 31.6  
(1-6) 30.0  
575-3-60  
1
(0.746)  
380-3-60  
(1-6) 3.9  
(1-6) 20.9  
380/415-3-50  
346-3-50  
(1-6) 3.4  
(1-6) 30.0  
(1-6) 4.4  
(1-6) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3-6) 6.6  
(1,2) 2.8 (3-6) 3.3  
(1-6) 3.4  
(1,2) 30.0 (3-6) 31.6  
(1,2) 30.0 (3-6) 31.6  
(1-6) 30.0  
575-3-60  
1
(0.746)  
380-3-60  
(1-6) 3.9  
(1-6) 20.9  
380/415-3-50  
346-3-50  
(1-6) 3.4  
(1-6) 30.0  
(1-6) 4.4  
(1-6) 20.9  
UNIT 38AH  
MODULE  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3,4) 6.6  
(1,2) 2.8 (3,4) 3.3  
(1-4) 3.4  
(1,2) 30.0 (3,4) 31.6  
(1,2) 30.0 (3,4) 31.6  
(1-4) 30.0  
124A  
124B  
134A  
575-3-60  
1
4
6
6.4  
9.2  
(0.746)  
380-3-60  
(1-4) 3.9  
(1-4) 20.9  
380/415-3-50  
346-3-50  
(1-4) 3.4  
(1-4) 30.0  
(1-4) 4.4  
(1-4) 20.9  
208/230-3-60  
460-3-60  
(1,2) 5.5 (3-6) 6.6  
(1,2) 2.8 (3-6) 3.3  
(1-6) 3.4  
(1,2) 30.0 (3-6) 31.6  
(1,2) 30.0 (3-6) 31.6  
(1-6) 30.0  
575-3-60  
1
134B  
(0.746)  
380-3-60  
(1-6) 3.9  
(1-6) 20.9  
380/415-3-50  
346-3-50  
(1-6) 3.4  
(1-6) 30.0  
(1-6) 4.4  
(1-6) 20.9  
LEGEND  
*Refers to condenser fans by position: See circled numbers on top  
views of units in Fig. 1-6.  
FLA  
LRA  
Full Load Amps  
Locked Rotor Amps  
NOTE: All fans are protected by a single circuit breaker.  
27  
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.  
*To control heating device and provide automatic indoor-  
fan operation on heating.  
†Jumper removed only when separate 24-v trans-  
former power source is used to power the 33CSUCE-06  
relay pack.  
**Field-supplied.  
NOTES:  
0.13 amp at 230 vac). Thermostats must have a  
LEGEND  
1. Liquid line solenoid valve LLS-A is used for so-  
lenoid drop on circuitA. Liquid line solenoid valve  
LLS-B is used for solenoid drop for circuit B.  
2. Solenoid drop is a safety feature which pre-  
vents refrigerant migration to the compressor dur-  
ing the OFF cycle. It is recommended on all  
systems and required on systems where piping  
exceeds 75 ft (22.9 m) in length.  
minimum pilot duty rating of 300 va (2.5 amps at  
120 vac and 1.3 amps at 230 vac).  
AWG  
CR  
American Wire Gage  
Control Relay  
8. Replacement of factory wires must be with type  
105 C wire or its equivalent.  
HD  
Heating Device  
IFC  
IFR  
kcmil  
LLS  
NEC  
Indoor-Fan Contactor  
Indoor-Fan Relay  
9. Field-supplied liquid line solenoid valves installed  
at the evaporator are required on all units.  
10. Units have 175 va of power available for field-  
installed accessories.  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
3. The 33CSUCE-06 relay pack requires 10 va.  
4. Factory wiring is in accordance with NEC; field  
modifications or additions must be in compli-  
ance with all applicable codes.  
5. Wiring for field power supply must be rated  
75 C minimum. Use copper, copper-clad alumi-  
num, or aluminum conductors. Maximum in-  
coming wire size for each terminal block is  
500 kcmil.  
11. To minimize voltage drop, the following wire sizes  
are recommended:  
R
Heating Relay (field-  
supplied 24-v sealed coil,  
10 va maximum rating)  
Reversing Valve  
Terminal Block  
Factory Wiring  
LENGTH —  
Ft (M)  
INSULATED WIRE — AWG  
(35 C Minimum)  
RV  
TB  
Up to 50  
(15.2)  
50-75  
(15.2-22.9)  
More Than 75  
(22.9)  
No. 18  
No. 16  
No. 14  
Field Wiring  
6. Terminal blocks TB3 and TB4 are for external  
field control connections. Control connections  
are to be Class 1 wiring.  
7. Field-supplied components (IFC, LLS-A, and  
LLS-B) must have a maximum sealed coil rat-  
ing of 30 va each (0.25 amp at 120 vac and  
Fig. 20 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Dual-Circuit Units  
28  
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.  
*To control heating device and provide automatic indoor-  
fan operation on heating.  
†Jumper removed only when separate 24-v trans-  
former power source is used to power the 33CSUCE-06  
relay pack.  
**Field-supplied.  
NOTES:  
LEGEND  
at 230 vac). Thermostats must have a minimum pilot  
duty rating of 300 va (2.5 amps at 120 vac and  
1.3 amps at 230 vac).  
1. Liquid line solenoid valves LLS-A1 and A2 are used  
for solenoid drops.  
AWG  
CR  
American Wire Gage  
Control Relay  
2. Solenoid drop is a safety feature which prevents  
refrigerant migration to the compressor during  
the OFF cycle. It is recommended on all systems  
and required on systems where piping exceeds  
75 ft (22.9 m) in length.  
3. The 33CSUCE-01 relay pack requires 10 va.  
4. Factory wiring is in accordance with NEC; field modi-  
fications or additions must be in compliance with  
all applicable codes.  
5. Wiring for field power supply must be rated 75 C  
minimum. Use copper, copper-clad aluminum, or  
aluminum conductors. Maximum incoming wire size  
for each terminal block is 500 kcmil.  
6. Terminal blocks are for external field control con-  
nections. Control connections are to be Class 1  
wiring.  
8. Replacement of factory wires must be with type  
105 C wire or its equivalent.  
HD  
Heating Device  
IFC  
IFR  
kcmil  
LLS  
NEC  
Indoor-Fan Contactor  
Indoor-Fan Relay  
9. Field-supplied liquid line solenoid valves installed at  
the evaporator are required on all units.  
10. Units have 175 va of power available for field-  
installed accessories.  
11. To minimize voltage drop, the following wire sizes are  
recommended:  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
R
Heating Relay (field-  
supplied 24-v sealed coil,  
10 va maximum rating)  
Reversing Valve  
Terminal Block  
Factory Wiring  
LENGTH —  
Ft (M)  
INSULATED WIRE — AWG  
(35 C Minimum)  
RV  
TB  
Up to 50  
(15.2)  
50-75  
(15.2-22.9)  
More Than 75  
(22.9)  
No. 18  
No. 16  
No. 14  
Field Wiring  
7. Field-supplied components (IFC, LLS-A1, and  
LLS-A2) must have a maximum sealed coil rating  
of 30 va each (0.25 amp at 120 vac and 0.13 amp  
Fig. 21 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Optional Single-Circuit Units  
29  
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.  
*To control heating device and provide automatic indoor-  
fan operation on heating.  
†Jumper removed only when separate 24-v trans-  
former power source is used to power the 33CSUCE-06  
relay pack.  
**Field-supplied.  
NOTES:  
1. Liquid line solenoid valve LLS-A1 is used for solenoid drop  
on circuit A. Liquid line solenoid valve LLS-B1 is used for  
solenoid drop for circuit B.  
2. Solenoid drop is a safety feature which prevents refrigerant  
migration to the compressor during the OFF cycle. It is rec-  
ommended on all systems and required on systems where  
piping exceeds 75 ft (22.9 m) in length.  
3. The 33CSUCE-06 relay pack requires 10 va.  
4. Factory wiring is in accordance with NEC; field modifications  
or additions must be in compliance with all applicable codes.  
5. Wiring for field power supply must be rated 75 C mini-  
mum. Use copper, copper-clad aluminum, or aluminum con-  
ductors. Maximum incoming wire size for each terminal block  
is 500 kcmil.  
6. Terminal blocks are for external field control connections. Con-  
trol connections must be Class 1 wiring.  
7. Field-supplied components (IFC, LLS-A1, and LLS-B1) must  
have a maximum sealed coil rating of 30 va each (0.25 amp  
at 120 vac and 0.13 amp at 230 vac). Thermostats must have  
a minimum pilot duty rating as follows:  
8. Replacement of factory wires must be with  
LEGEND  
type 105 C wire or its equivalent.  
9. Field-supplied liquid line solenoid valves in-  
stalled at the evaporator are required on all  
units.  
AWG  
CR  
American Wire Gage  
Control Relay  
HD  
Heating Device  
IFC  
IFR  
kcmil  
LLS  
NEC  
Indoor-Fan Contactor  
Indoor-Fan Relay  
10. Units 38AH094 has 140 va and unit 38AH104  
has 130 va of power available for field-  
installed accessories.  
11. To minimize voltage drop, the following wire  
sizes are recommended:  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
R
Heating Relay (field-  
supplied 24-v sealed coil,  
10 va maximum rating)  
Reversing Valve  
Terminal Block  
Factory Wiring  
INSULATED WIRE —  
LENGTH —  
AWG  
RV  
TB  
Ft (M)  
(35 C Minimum)  
Up to 50  
No. 18  
(15.2)  
Field Wiring  
50-75  
(15.2-22.9)  
No. 16  
VA  
More Than 75  
(22.9)  
38AH  
094  
AMPS  
VAC  
No. 14  
(Ea Stage)  
2.29  
1.15  
2.70  
1.35  
120  
240  
120  
240  
275  
104  
325  
Fig. 22 — Field Wiring, One 2-Stage Thermostat — Units 38AH094 and 104  
30  
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.  
*Jumper removed only when separate 24-v trans-  
former power source is used to power the 33CSUCE-06  
relay pack.  
†Field-supplied.  
NOTES:  
1. Liquid line solenoid valves LLS-A1 and A2 are used  
for solenoid drop on Module 124A or 134A on cir-  
cuit A. Liquid line solenoid valves LLS-B1 and B2  
are used for solenoid drop for Module 124B or 134B.  
Solenoid drop is a safety feature which prevents  
refrigerant migration to the compressor during  
the OFF cycle. It is recommended on all systems  
and required on systems where piping exceeds  
75 ft (22.9 m) in length.  
2. Disconnect black wire from CR2 terminal 6; cap loose  
end and secure. Connect new field-supplied wire  
from CR2 terminal 6 to TB3 terminal 1 on module  
124B or 134B.  
3. The 33CSUCE-06 relay pack requires 10 va.  
4. Factory wiring is in accordance with NEC; field modi-  
fications or additions must be in compliance with  
all applicable codes.  
5. Wiring for field power supply must be rated 75 C  
minimum. Use copper, copper-clad aluminum, or  
aluminum conductors. Maximum incoming wire size  
for each terminal block is 500 kcmil.  
7. Field-supplied components (IFC, LLS-A1,A2, and  
LEGEND  
LLS-B1,B2) must have a maximum sealed coil  
rating of 30 va each (0.25 amp at 120 vac and  
0.13 amp at 230 vac). Thermostats must have a  
minimum pilot duty rating of 300 va (2.5 amps at  
120 vac).  
AWG  
C
American Wire Gage  
Compressor Contactor  
Capacity Control Pressure  
Switch  
Control Relay  
Heating Device  
Indoor-Fan Contactor  
Indoor-Fan Relay  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
Heating Relay (field-  
supplied 24-v sealed coil,  
10 va maximum rating)  
Reversing Valve  
CCPS  
CR  
8. Replacement of factory wires must be with type  
HD  
IFC  
105 C wire or its equivalent.  
IFR  
9. Field-supplied liquid line solenoid valves installed  
at the evaporator are required on all units.  
10. Units have 175 va of power available for field-  
installed accessories.  
kcmil  
LLS  
NEC  
11. To minimize voltage drop, the following wire sizes  
R
are recommended:  
LENGTH —  
Ft (M)  
INSULATED WIRE — AWG  
(35 C Minimum)  
RV  
SDR  
TB  
Solenoid Drop Relay  
Terminal Block  
Timer Relay  
Factory Wiring  
Field Wiring  
Up to 50  
(15.2)  
50-75  
(15.2-22.9)  
More Than 75  
(22.9)  
No. 18  
No. 16  
No. 14  
TR  
6. Terminal blocks (TB3) are for external field control  
connections. Control connections must be Class 1  
wiring.  
Fig. 23 — Field Wiring, One 2-Stage Thermostat — Units 38AH124 and 134  
31  
*Field-supplied.  
NOTES:  
1. Factory wiring is in accordance with NEC; field modifications or addi-  
tions must be in compliance with all applicable codes.  
2. Wiring for field power supply must be rated 75 C minimum. Use cop-  
per, copper-clad aluminum, or aluminum conductors. Maximum  
incoming wire size for each terminal block is 500 kcmil.  
3. Terminal blocks TB3 and TB4 are for external field control connec-  
tions. Control connections are to be Class 1 wiring.  
4. Field-supplied components (IFC, LLS-A, and LLS-B) must have a maxi-  
mum sealed coil rating of 30 va each (.25 amp at 120 vac, .13 amp at  
230 vac). AHMS IFC-AUX must have a minimum pilot duty rating of  
200 va (1.7 amps at 120 vac, 0.9 amps at 230 vac) each.  
5. Replacement of factory wires must be with type 105 C wire or its  
equivalent.  
LEGEND  
AHMS  
Air Handler Motor  
Starter  
SDR  
TB  
Solenoid Drop Relay  
Terminal Block  
TBX  
Terminal Block for Variable  
Air Volume Units  
Timer Motor  
AUX  
C
Auxiliary  
Compressor Contactor  
Fuse  
FU  
TM  
GND  
IFC  
Equipment Ground  
Indoor Fan Control  
TR  
Timer Relay  
TRAN  
Transformer  
kcmil  
LLS  
NEC  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
U
Unloader Solenoid  
6. Field-supplied liquid line solenoid valves installed at the evaporator are  
required on all units.  
7. Units have 175 va of power available for field-installed accessories.  
Factory Wiring  
Field Wiring  
Fig. 24 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Dual-Circuit Units  
*Field-supplied.  
NOTES:  
1. Factory wiring is in accordance with NEC; field modifications or addi-  
tions must be in compliance with all applicable codes.  
2. Wiring for field power supply must be rated 75 C minimum. Use cop-  
per, copper-clad aluminum, or aluminum conductors. Maximum in com-  
ing wire size for each terminal block is 500 kcmil.  
LEGEND  
3. Terminal blocks TB3, TBX1, and TBX2 are for external field control con-  
nections. Control connections are to be Class 1 wiring.  
4. Field-supplied components (IFC, LLS-A1, and LLS-A2) must have a  
maximum sealed coil rating of 30 va each (0.25 amp at 120 vac,  
13 amp at 230 vac). AHMS IFC-AUX must have minimum pilot duty  
rating of 400 va each (3.4 amps at 120 vac, 1.8 amps at 230 vac) each.  
5. Replacement of factory wires must be with type 105 C wire or its  
equivalent.  
AHMS  
Air Handler Motor  
Starter  
SDR  
Solenoid Drop Relay  
Terminal Block  
Terminal Block for  
Variable Air Volume  
Units  
TB  
TBX  
AUX  
C
Auxiliary  
Compressor Contactor  
Fuse  
FU  
GND  
IFC  
Equipment Ground  
Indoor Fan Control  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
TM  
TR  
TRAN  
U
Timer Motor  
Timer Relay  
kcmil  
LLS  
NEC  
Transformer  
Unloader Solenoid  
6. Field-supplied liquid line solenoid valves installed at the evaporator are  
required on all units.  
Factory Wiring  
Field Wiring  
7. Control has 175 va of power available for field-installed accessories.  
Fig. 25 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Optional Single-Circuit Units  
*Field-supplied.  
NOTES:  
1. Factory wiring is in accordance with NEC. Field modifications  
or additions must be in compliance with all applicable codes.  
2. Wiring for field power supply must be rated 75 C minimum. Use  
copper, copper-clad aluminum, or aluminum conductors. Maxi-  
mum incoming wire size for each terminal block is 500 kcmil.  
3. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external  
field control connections. Control connections are to be  
Class 1 wiring.  
LEGEND  
4. Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must  
have a maximum sealed coil rating of 30 va each (0.25 amp at  
120 vac, 0.13 amp at 230 vac). AHMS IFC-AUX contact must  
have minimum pilot duty rating of 325 va each (2.7 amps at  
120 vac, 1.4 amps at 230 vac).  
AHMS  
AUX  
C
Air Handler Motor Starter  
SDR  
Solenoid Drop Relay  
Terminal Block  
Auxiliary  
TB  
Compressor Contactor  
Fuse  
TBX  
Terminal Block for Variable  
Air Volume Units  
Timer Motor  
FU  
GND  
IFC  
kcmil  
LLS  
NEC  
Equipment Ground  
Indoor Fan Control  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
TM  
TR  
TRAN  
U
5. Replacement of factory wires must be with type 105 C wire or  
its equivalent.  
Timer Relay  
Transformer  
Unloader Solenoid  
6. Field-supplied liquid line solenoid valves installed at the evapo-  
rator are required on all units.  
Factory Wiring  
Field Wiring  
7. Control has 25 va of power available for field-installed  
accessories.  
Fig. 26 — Field Wiring, Single ModuPanel™ Control, Unit 38AH094  
34  
*Field-supplied.  
NOTES:  
1. Factory wiring is in accordance with NEC. Field modifications or  
additions must be in compliance with all applicable codes.  
2. Wiring for field power supply must be rated 75 C minimum. Use  
copper, copper-clad aluminum, or aluminum conductors. Maxi-  
mum incoming wire size for each terminal block is 500 kcmil.  
3. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field  
control connections. Control connections are to be Class 1 wiring.  
4. Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must  
have a maximum sealed coil rating of 30 va each (0.25 amp at  
120 vac, 0.13 amp at 230 vac). AHMS IFC-AUX contact must have  
minimum pilot duty rating of 375 va each (3.1 amps at 120 vac,  
1.6 amps at 230 vac).  
LEGEND  
AHMS  
AUX  
C
Air Handler Motor Starter  
TB  
TBX  
Terminal Block  
Terminal Block for  
Variable Air Volume  
Units  
Auxiliary  
Compressor Contactor  
Fuse  
FU  
GND  
IFC  
kcmil  
LLS  
NEC  
Equipment Ground  
Indoor Fan Control  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
Solenoid Drop Relay  
TM  
TR  
TRAN  
U
Timer Motor  
Timer Relay  
Transformer  
Unloader Solenoid  
Factory Wiring  
5. Replacement of factory wires must be with type 105 C wire or its  
equivalent.  
Field Wiring  
SDR  
6. Field-supplied liquid line solenoid valves installed at the evapora-  
tor are required on all units.  
7. Control has 35 va of power available for field-installed accessories.  
Fig. 27 — Field Wiring, Single ModuPanel™ Control, Unit 38AH104  
35  
*Field-supplied.  
NOTES:  
1. Factory wiring is in accordance with NEC. Field modifications or  
additions must be in compliance with all applicable codes.  
2. Wiring for field power supply must be rated 75 C minimum. Use  
copper, copper-clad aluminum, or aluminum conductors. Maxi-  
mum incoming wire size for each terminal block is 500 kcmil.  
3. Terminal blocks TB3 and TBX1 are for external field control con-  
nections. Control connections are to be Class 1 wiring.  
4. Field-supplied components (IFC, LLS-A1 and A2) must have a maxi-  
mum sealed coil rating of 30 va each (0.25 amp at 120 vac,  
0.13 amp at 230 vac). AHMS IFC-AUX contact must have mini-  
mum pilot duty rating of 400 va each (3.4 amps at 120 vac,  
1.8 amps at 230 vac).  
LEGEND  
AHMS  
AUX  
C
Air Handler Motor Starter  
SDR  
TB  
TBX  
Solenoid Drop Relay  
Terminal Block  
Auxilliary  
Compressor Contactor  
Fuse  
Terminal Block for Variable  
Air Volume Units  
Timer Motor  
FU  
GND  
IFC  
kcmil  
LLS  
NEC  
Equipment Ground  
Indoor Fan Control  
Thousand Circular Mils  
Liquid Line Solenoid  
National Electrical Code  
(U.S.A. Standard)  
TM  
TR  
TRAN  
U
5. Replacement of factory wires must be with type 105 C wire or its  
equivalent.  
Timer Relay  
Transformer  
6. Field-supplied liquid line solenoid valves installed at the evapora-  
tor are required on all units.  
7. Units have 175 va of power available for field-installed  
accessories.  
Unloader Solenoid  
Factory Wiring  
Field Wiring  
Fig. 28 — Field Wiring, Single ModuPanel™ Control, Units 38AH124 and 134  
36  
Table 15 — Main Power Connection and Control Circuit Wiring  
MAIN POWER CONNECTION  
CONTROL CIRCUIT  
Electrical  
Characteristics  
(V-Ph-Hz)  
Qty  
Terminal  
Blocks  
Qty  
Max Wire  
Size  
(kcmil)  
Control Power  
(V)  
Safety Circuit  
(V)  
Parallel  
Conductors*  
208/230-3-60  
1
1
1
1
1
6
3
6
3
3
500  
500  
500  
500  
500  
115†  
115†  
230  
24  
24  
24  
24  
24  
460-3-60  
575-3-60  
230-3-50  
380-3-60  
380/415-3-50  
230  
346-3-50  
200  
LEGEND  
kcmil  
*Conductors are from the safety disconnect.  
†Control power is accomplished with a step-down transformer where primary voltage is field voltage.  
Thousand Circular Mils  
2. Backseat (open) compressor suction and discharge shut-  
off valves. Close valves one turn to allow refrigerant pres-  
sure to reach the test gages.  
Step 5 — Install Accessories  
LOW-AMBIENT OPERATION  
Units 38AH044-084, 124, and 134 — If operating tempera-  
tures below 55 F (13 C) are expected, MotormasterIII fan  
motor control is recommended. Refer to separate installa-  
tion instructions for low-ambient operation guidelines.  
3. Open liquid line service valves.  
4. Check tightness of all electrical connections.  
5. Oil should be visible in the compressor sight glasses.  
See Fig. 29. An acceptable oil level in the compressor  
1
1
Units 38AH094 and 104 — If operating temperatures below  
45 F (7 C) are expected, Motormaster III fan motor control  
is recommended. Refer to separate installation instructions  
for low-ambient operation guidelines.  
is from 8 to ⁄3 of sight glass. Adjust the oil level as  
required. No oil should be removed unless the crank-  
case heater has been energized for at least 24 hours. See  
Preliminary Oil Charge section on page 38, for Carrier-  
approved oils.  
MISCELLANEOUS ACCESSORIES — For applications  
requiring special accessories, the following packages are  
available: condenser coil hail guard package, gage panel,  
unloader package, unloader conversion kits, sound reduc-  
tion package, condenser coil protective grilles, compressor  
security grilles, ModuPanel™ control, and thermostat trans-  
former relay package.  
6. Electrical power source must agree with unit  
nameplate.  
Crankcase heaters on all units are wired into the  
control circuit, so they are always operable as long  
as the main power supply disconnect is on (closed),  
even if any safety device is open. Compressor heat-  
ers must be on for 24 hours prior to the start-up of  
any compressor.  
PRE-START-UP  
IMPORTANT: Before beginning Pre-Start-Up or Start-  
Up, review Start-Up Checklist at the back of this pub-  
lication. The Checklist assures proper start-up of a unit  
and provides a record of unit condition, application re-  
quirements, system information, and operation at ini-  
tial start-up.  
7. Crankcase heaters must be firmly locked into compres-  
sors, and must be on for 24 hours prior to start-up.  
8. Fan motors are 3-phase. Check rotation of fans during  
first start-up check. Fan rotation is clockwise as viewed  
from top of unit. If fan is not turning clockwise, reverse  
2 of the power wires.  
9. Check compressor suspension. On units 38AH044-084,  
124, and 134, snubber washers (for noise suppression)  
can be moved with finger pressure. On units 38AH094  
and 104, rails allow compressors to float freely on com-  
pressor rail springs.  
10. On 38AH074,084 single-circuit units and Module  
38AH134B, ensure that the packaging block located be-  
tween the oil equalization tube and the compressor cross-  
brace has been removed.  
Do not attempt to start the air-conditioning system until  
following checks have been completed.  
System Check  
1. Check all system components, including the air-  
handling equipment. Consult manufacturer’s instruc-  
tions. If the unit has field-installed accessories, be sure  
all are properly installed and wired correctly. Refer to  
unit wiring diagrams.  
37  
DISCHARGE  
GAS THERMOSTAT  
HIGH-  
FAN CYCLING  
DISCHARGE GAS  
CYLINDER  
HEADS  
OIL PRESSURE SWITCH AND  
CAPACITY CONTROL  
PRESSURE SWITCH CAPILLARIES  
PRESSURE PRESSURE SWITCH THERMOSTAT  
SWITCH  
MUFFLER  
SIGHT  
GLASS  
OIL  
EQUALIZER  
LINE  
LOW-  
PRESSURE  
SWITCH  
RAIL  
CRANKCASE  
HEATER  
SIGHT  
GLASS  
MOUNTING  
SPRING  
(HIDDEN)  
PRESSURE RELIEF  
VALVE  
NOTE: Units 38AH044-084 and 38AH124, 134 compressors are pan  
mounted. Units 38AH094 and 104 compressors are mounted on rails.  
Fig. 29 — 06E Compressors, Typical  
8. If any leaks are detected, evacuate and dehydrate as pre-  
viously outlined in Step 3 — Make Refrigerant Piping  
Connections, page 14.  
START-UP  
Compressor crankcase heaters must be on for 24 hours  
before start-up. To energize the crankcase heaters, set the  
space thermostat above the ambient so there will be no de-  
mand for cooling. Close the field disconnect and turn on the  
fan circuit breakers. Leave the compressor circuit breakers  
off/open. The crankcase heaters are now energized.  
Preliminary Oil Charge — Each compressor is fac-  
tory charged with oil (see Table 3A, 3B, 4A, or 4B). When  
oil is checked at start-up, it may be necessary to add or re-  
move oil to bring it to the proper level. One recommended  
oil level adjustment method is as follows:  
Preliminary Checks  
ADD OIL — Close suction shutoff valve and pump down  
crankcase to 2 psig (14 kPa). (Low-pressure cutout must be  
jumped.) Wait a few minutes and repeat until pressure re-  
mains steady at 2 psig (14 kPa). Remove oil fill plug above  
the oil level sight glass, add oil through plug hole, and re-  
place plug. Run compressor for 20 minutes and check oil  
level.  
1. Ensure that compressor service valves are backseated.  
2. Verify that each compressor on units 38AH044-084, 124,  
and 134 floats freely on its mounting springs. Verify that  
each compressor on units 38AH094 and 104 floats freely  
on its rails.  
3. Check that electric power supply agrees with unit name-  
plate data.  
4. Verify that compressor crankcase heaters are securely in  
place.  
5. Check that compressor crankcase heaters have been on at  
least 24 hours.  
IMPORTANT: For units with 2 compressors per re-  
frigeration circuit, both compressors must be running  
to adjust the oil level. Two oil level equalizer lines  
between compressors distribute the oil to each  
compressor.  
6. Note that compressor oil level is visible in the sight glass.  
7. Recheck for leaks using same procedure as previously out-  
lined in Step 3 — Make Refrigerant Piping Connections,  
page 14.  
38  
NOTE: Use only Carrier approved compressor oil. Ap-  
proved sources are: Petroleum Specialties Inc. (Cryol 150A),  
Texaco, Inc. (Capella WF-32-150), and Witco Chemical Co.  
(Suniso 3GS). Do not reuse oil that has been drained out, or  
oil that has been exposed to atmosphere.  
compressor B1. Start-up of compressor B1 is delayed from  
12 seconds to 512 minutes. (Circuit B of unit 38AH094 has  
only one compressor.)  
Each circuit’s lead compressor start-up is controlled by  
the unit control timer. The circuit’s lag compressor start-up  
is controlled by the D-D2 timer contacts and capacity  
control pressure switches (CCPSs) which monitor compres-  
sor suction pressure. The circuit’s lag compressor will start  
approximately 212 minutes after a call for cooling if com-  
pressor pressure is above CCPS set point.  
REMOVE OIL — Pump down compressor to 2 psig  
(14 kPag). Loosen the 14-in. (6.4-mm) pipe plug at the com-  
pressor base and allow the oil to seep out past the threads of  
the plug.  
NOTE: The crankcase will be slightly pressurized. Do not  
remove the plug, or the entire oil charge will be lost.  
38AH124,134 UNITS — Start-up of the lead circuit  
(Module 124A or 134A) lead compressor A1 (Table 16) is  
delayed from 12 seconds to 512 minutes from the time the  
call for cooling is initiated by TC1. Lag compressor A2 is  
controlled by D-D2 timer contacts and capacity control pres-  
sure switches (CCPSs) which monitor compressor suction  
pressure. The lag compressor starts approximately 212 min-  
utes after the lead compressor starts if the suction pressure  
is above the CCPS set point.  
After the lead circuit (Module 124A or 134A) lead com-  
pressor A1 (Table 16) starts, close the TC2 thermostat to start  
the lag circuit (Module 124B or 134B) lead compressor (A1).  
Lag circuit compressor A1 start-up is delayed from 12 sec-  
onds to 512 minutes from the time the call for cooling is  
initiated by TC2. Lag compressor A2 is controlled by D-D2  
timer contacts and CCPSs which monitor compressor suc-  
tion pressure. Lag compressor A2 starts approximately 212  
minutes after lead compressor A1 starts if the suction pres-  
sure is above the CCPS set point.  
Small amounts of oil can be removed through the oil pump  
discharge connection while the compressor is running.  
Preliminary Charge — Refer to GTAC II (General Train-  
ing Air Conditioning), Module 5, Charging, Recovery,  
Recycling, and Reclamation for charging procedures. Using  
the liquid charging method and charging by weight proce-  
dure, charge each circuit with the amount of R-22 listed in  
Table 3A, 3B, 4A, or 4B.  
Never charge liquid into the low-pressure side of sys-  
tem. Do not overcharge. During charging or removal of  
refrigerant, be sure indoor-fan system is operating.  
Start Unit — The field disconnect is closed, the fan cir-  
cuit breaker is closed, and the space thermostats are set above  
ambient so that there is no demand for cooling. Only the  
crankcase heaters are energized.  
Adjust Refrigerant Charge  
Close the compressor circuit breakers and then reset both  
space thermostats below ambient so that a call for stage one  
cooling is ensured. Lead refrigeration circuit ther-  
mostat TC1 must be set to call for cooling at a lower tem-  
perature than lag refrigeration circuit thermostat TC2.  
See Table 16 for lead/lag circuits on all units. Now set TC2  
for cooling.  
Never charge liquid into the low-pressure side of sys-  
tem. Do not overcharge. During charging or removal of  
refrigerant, be sure indoor-fan system is operating.  
With all fans operating, and all compressors on the cir-  
cuit being serviced operating at full capacity, adjust the  
refrigerant charge in accordance with the unit charging charts  
located on the inside of the control box doors and in  
Fig. 30-43. Charge vapor into compressor low-side service  
port located above oil pump crankshaft housing. Measure  
pressure at the liquid line service valve, making sure a Schrader  
depressor is used if required. Also, measure liquid line tem-  
perature as close to the liquid service valve as possible. Add  
charge until the pressure and temperature conditions of the  
charging chart curve are met. If liquid pressure and tempera-  
ture point fall above curve, add charge. If liquid pressure  
and temperature point fall below curve, reduce the charge  
until the conditions match the curve.  
If the sight glass at location A (Fig. 11 and 12) is cloudy,  
check refrigerant charge again. Ensure all fans and com-  
pressors on the circuit being serviced are operating. Also  
ensure maximum allowable liquid lift has not been  
exceeded.  
If the sight glass at location A is clear and the sight  
glass at location B is cloudy, a restriction exists in the  
line between the 2 sight glasses. Check for a plugged filter  
drier or partially open solenoid valve. Replace or repair, as  
needed.  
NOTE: Do not use circuit breakers to start and stop the com-  
pressor except in an emergency.  
38AH044-084 DUAL-CIRCUIT UNITS — Start-up of lead  
compressor A1 (Table 16) will be delayed from 12 seconds  
to 512 minutes from the time the call for cooling is initiated  
by TC1. After the lead compressor starts, close the TC2 ther-  
mostat to start lag circuit compressor B1. Compressor B1  
will start a minimum of 60 seconds after thermostat TC2 is  
closed.  
38AH044-084 OPTIONAL SINGLE CIRCUIT UNITS —  
Start-up of lead compressor A1 (Table 16) is delayed from  
12 seconds to 512 minutes from the time the call for cooling  
is initiated by TC1. Closure of TC2 will actuate LLS-A2.  
Lag compressor A2 is controlled by D-D2 timer contacts and  
capacity control pressure switches (CCPSs) which monitor  
compressor suction pressure. The lag compressor starts ap-  
proximately 212 minutes after the lead compressor starts if  
the suction pressure is above the CCPS set point.  
38AH094,104 UNITS — Start-up of lead circuit A,  
compressor A1 (Table 16) is delayed from 12 seconds to  
512 minutes from the time the call for cooling is initiated.  
After lead circuit A, compressor A1 starts, close refrig-  
eration circuit thermostat TC2 to start lag circuit B, lead  
39  
Table 16 — Index of Lead/Lag Circuits and Compressors  
UNIT  
38AH  
044-084  
STD  
044-084  
OPT  
094  
104  
124  
134  
Module  
124A  
A1  
Module  
134A  
A1  
LEAD CIRCUIT  
A
A
A
A
Compressor, Lead  
Compressor; Lag  
A1  
*
A1  
A2  
A1  
A2  
A1  
A2  
A2  
A2  
Module  
124B  
A1  
Module  
134B  
A1  
LAG CIRCUIT  
B
B
B
Compressor, Lead  
Compressor; Lag  
B1  
*
B1  
*
B1  
B2  
A2  
A2  
LEGEND  
OPT  
STD  
Optional Single-Circuit Units  
Standard Dual-Circuit Units  
*Circuit has only one compressor.  
†Units have only one circuit.  
electrically actuated unloaders are installed, energize the so-  
lenoid to unload the compressor. Recheck the compressor  
oil level as described in Check Compressor Oil Level above.  
Return unloader to original setting after checks are  
complete.  
Check Compressor Oil Level — After adjusting the  
refrigerant charge, allow each circuit to run fully loaded for  
1
1
20 minutes. Running oil level should be 8 to ⁄3 up on the  
sight glass. Stop the compressors at the field power supply  
disconnect and check the crankcase oil level. Add oil only if  
necessary to bring the oil into view in the sight glass. If oil  
is added, run the circuit for an additional 10 minutes, then  
stop and check oil level. If the level remains low, check the  
piping system for proper design for oil return; also, check  
the system for leaks.  
UNITS 38AH094,104 — For this minimum load check, the  
lead compressor (A1, B1) of each refrigeration circuit is un-  
loaded. See Table 16. The lag compressor (A2, B2 [38AH104  
only]) of each refrigeration circuit must not be operating.  
Unload the compressor(s) by turning the control set point  
adjustment nut counterclockwise until the adjustment nut stops.  
The unloader is now at 0 psig (0 kPag) set point. If electri-  
cally actuated unloaders are installed, energize the solenoid  
to unload the compressor.  
Return unloader to original setting after checks are  
complete.  
If the initial check shows too much oil (too high in the  
sight glass) remove oil to proper level. See Preliminary Oil  
Charge for proper procedure for adding and removing oil.  
When the above checks are complete, repeat the proce-  
dure with the unit operating at minimum load conditions.  
UNITS 38AH044-084,124, AND 134 — For this minimum  
load check, run the lead compressor of each refrigeration cir-  
cuit fully unloaded with the lag compressor not operating.  
Unload the compressor(s) by turning the control set point  
adjustment nut counterclockwise until the adjustment nut  
stops. The unloader is now at 0 psig (0 kPag) set point. If  
Final Checks — Ensure all safety controls are operat-  
ing, control panel covers are on, and the service panels are  
in place.  
40  
Fig. 30 — Charging Chart — Unit 38AH044; 50/60 Hz — Dual Circuit  
Fig. 31 — Charging Chart — Unit 38AH054; 50/60 Hz — Dual Circuit  
41  
Fig. 32 — Charging Chart — Unit 38AH064; 50/60 Hz — Dual Circuit  
Fig. 33 — Charging Chart — Unit 38AH074; 50/60 Hz — Dual Circuit  
42  
Fig. 34 — Charging Chart — Unit 38AH084; 50/60 Hz — Dual Circuit  
Fig. 36 — Charging Chart — Unit 38AH054;  
50/60 Hz — Optional Single Circuit  
Fig. 35 — Charging Chart — Unit 38AH044;  
50/60 Hz — Optional Single Circuit  
43  
Fig. 37 — Charging Chart — Unit 38AH064;  
50/60 Hz — Optional Single Circuit  
Fig. 38 — Charging Chart — Unit 38AH074;  
50/60 Hz — Optional Single Circuit  
Fig. 39 — Charging Chart — Unit 38AH084;  
50/60 Hz — Optional Single Circuit  
44  
Fig. 40 — Charging Chart — Unit 38AH094; 50/60 Hz  
Fig. 41 — Charging Chart — Unit 38AH104; 50/60 Hz  
Fig. 42 — Charging Chart — Modules 124A, 124B,  
and 134A; 50/60 Hz  
Fig. 43 — Charging Chart — Module 134B;  
50/60 Hz  
45  
The heater is held in place by a clip and bracket and must be  
tightly connected since exposure to the air causes the heater  
to burn out. Each heater is wired into the compressor control  
circuit through a relay which energizes only when the com-  
pressor is off. The heater keeps the oil at a temperature that  
prevents excessive absorption of refrigerant during shut-  
down periods.  
SERVICE  
ELECTRIC SHOCK HAZARD  
Turn off all power to unit before servicing.  
The ON-OFF switch on control panel  
does not shut off control power; use field  
disconnect.  
Energize the crankcase heaters when the unit is not run-  
ning except during prolonged shutdown or servicing. Ener-  
gize the heaters at least 24 hours before restarting the unit  
after prolonged shutdown.  
Coil Cleaning — Clean the coils with a vacuum cleaner,  
compressed air, water, or a non-wire bristle brush.  
Refrigerant Circuit  
TIME GUARDFUNCTION — This function prevents com-  
pressors from short-cycling.  
LEAK TESTING — Units are shipped with a holding charge  
of R-22 (see Table 3A, 3B, 4A, or 4B) and should be under  
sufficient pressure to conduct a leak test. If there is no pres-  
sure in the system, introduce enough nitrogen to search  
for the leak. Repair the leak using good refrigeration prac-  
tices. After leaks are repaired, system must be evacuated and  
dehydrated using methods described in GTAC II , Module 4,  
System Dehydration.  
Fan Motor Protection — Fan motors are protected  
by a single circuit breaker for all motors.  
Head Pressure Control — Head pressure control re-  
duces condenser capacity under low-ambient conditions. This  
is achieved by fan cycling control (standard, all units) and  
MotormasterIII control accessory (field installed).  
REFRIGERANT CHARGE (Refer to Table 3A, 3B, 4A, or  
4B) — At the liquid line connection point on each circuit is  
a factory-installed liquid line service valve. On each  
FAN CYCLING — All condensing units have standard pro-  
vision for fully automatic intermediate season head pressure  
control through fan cycling (see Table 17).  
1
valve is a 4-in. Schrader connection for charging liquid  
38AH044-084 Dual-Circuit Units — Fans no. 3 and 4 are  
cycled by pressure control on all units. On 38AH074 and  
084, fans no. 5 and 6 are also cycled by pressure control.  
38AH044-084 Optional Single Circuit Units — Fans no. 3  
and 4 are cycled by pressure control on all units. On 38AH074  
and 084, fans no. 5 and 6 are cycled by an air-temperature  
switch located in the bottom shelf of the control box.  
Units 38AH094,104 — Fans no. 3 through 6 are cycled by  
pressure control.  
Units 38AH124,134 — Fans no. 3 and 4 on each unit mod-  
ule are cycled by pressure control. On module 134B only,  
fans no. 5 and 6 are cycled by an air-temperature switch lo-  
cated in the bottom shelf of the control box.  
Pressure control is achieved via a fan cycling pressure switch  
located on the cylinder head of the unit or circuit lead com-  
pressor (see Fig. 29).  
The air-temperature switch used to control fans no. 5 and  
6 on 38AH074,084 optional single-circuit units and on mod-  
ule 134B is closed and cycles the fans on when the ambient-  
air temperature is above 70 F (21 C).  
refrigerant.  
Charging with Unit Off and Evacuated — Close liquid  
line service valve before charging. Weigh in charge shown  
in Table 3A, 3B, 4A, or 4B. Open liquid line service valve;  
start unit and allow it to run several minutes fully loaded.  
Check for a clear sight glass. Be sure clear condition is liq-  
uid and not vapor. Complete charging the unit in accordance  
with Start-Up, Adjust Refrigerant Charge, page 39.  
Charging with Unit Running — If charge is to be added while  
unit is operating, it is necessary to have all condenser fans  
and compressors operating. It may be necessary to block con-  
denser coils at low-ambient temperatures to raise condens-  
ing pressure to approximately 280 psig (1931 kPag) to turn  
all condenser fans on. Do not totally block a coil to do this.  
Partially block all coils in uniform pattern. Charge  
vapor into compressor low-side service port located above  
oil pump crankshaft housing. Charge each circuit until sight  
glass shows clear liquid.  
Troubleshooting — Refer to Troubleshooting chart lo-  
cated at back of book.  
Oil Pressure Safety Switch (OPS) — An oil pres-  
sure safety switch for each of the independent refrigerant  
circuits shuts off the compressor in that circuit if oil pressure  
is not established at start-up or maintained during operation.  
If the OPS stops the unit, determine and correct the cause  
before restarting the unit. Failure to do so constitutes equip-  
ment abuse and could affect the warranty.  
Table 17 — Fan Cycling Control — Psig (kPag)  
Control by Pressure*  
Switch Opens  
Switch Closes  
± 10 (69)  
160 (1103)  
255 (1758)  
*On all units, fans no. 3 and 4; also on unit 38AH074, 084 (dual-  
circuit units only) and 38AH094,104, fans no. 5 and 6.  
NOTE: Fans no. 1 and 2 are noncycling. Units 38AH074,084 optional  
Compressor Motor Protection  
single-circuit units and module 134B fans no.  
5
and  
6
are  
CIRCUIT BREAKER — A manual reset, calibrated trip cir-  
cuit breaker for each compressor protects against overcur-  
rent. Do not bypass connections or increase size of circuit  
breaker for any reason. If trouble occurs, determine the cause  
and correct it before resetting the breaker.  
cycled by an air-temperature switch which operates above 70 F  
(21 C) ambient-air temperature.  
DISCHARGE GAS THERMOSTAT — A sensor in the  
cylinder head of each compressor (Fig. 29) shuts down the  
compressor if excessively high discharge gas temperature is  
sensed. If the discharge gas thermostat shuts the unit down,  
it may be reset by the thermostat or power disconnect switch.  
38AH044-064,  
Modules 124A, 124B,  
134A  
38AH074-104,  
Module 134B  
CRANKCASE HEATER (See Fig. 29) — Each compressor  
has an electric crankcase heater located in the bottom cover.  
46  
Winter Start Control — A212-minute low-pressure switch  
(LPS) bypass function in the timer prevents nuisance LPS  
trips during start-up in low-ambient conditions.  
38AH094,104 — Capacity control is achieved by a pressure-  
actuated cylinder bank unloader on the lead compressor  
(A1, B1) on each of the 2 refrigeration circuits. As the cool-  
ing load decreases and the suction pressure drops, the un-  
loader actuates at the pre-set suction pressure and unloads  
the cylinder bank. (See Fig. 44 and Table 20.) The unloading  
of the compressor cylinder bank has no effect on the opera-  
tion of the circuit lag compressor (A2, B2 [except 38AH094,  
circuit B]) which is controlled by fixed setting capacity con-  
trol pressure switches (CCPSs) as follows:  
High-Pressure Switch — This switch has nonadjust-  
able settings. Figure 29 shows connection on a cylinder head.  
See Table 18 for pressure switch settings.  
NOTE: High-pressure switch must be removed from cylin-  
der head before removing compressor from the unit.  
TO CHECK — Slowly close the discharge shutoff valve un-  
til the compressor shuts down. This should be at approxi-  
mately 426 psig (2935 kPag). Slowly open the valve. When  
the pressure drops to approximately 320 psig (2205 kPag),  
the pressure switch resets. To reenergize the control circuit,  
manually switch the fan circuit breaker off and then on. The  
compressor starts again under Time Guardcontrols.  
CUT-IN —  
Psi (kPa)  
CUTOUT —  
Psi (kPa)  
CCPS 1  
CCPS 2  
83 (572)  
80 (551)  
63 (531)  
53 (365)  
CCPS  
Capacity Control Pressure Switch  
Low-Pressure Switch — The low-pressure switch (LPS)  
has fixed nonadjustable settings. It is located at the pump  
end of the compressor above the bearing head. See Table 18  
for pressure switch settings.  
Pressure Relief — High-side pressure relief is pro-  
vided by a fusible plug in the liquid line at the service valve.  
For low-side pressure relief, a fusible plug is inserted in the  
side of the accumulator (all units except 38AH044-084 dual-  
circuit, constant-volume units). See Fig. 45. The 38AH044-  
084 dual-circuit, constant-volume units have a fusible plug  
in the suction tubing. A pressure relief valve installed on the  
compressor relieves at 450 psig (3102 kPag) (see Fig. 1-6).  
TO CHECK — Slowly close the suction cut-off valve and  
allow the compressor to shut down. This should occur at  
approximately 27 psig (186 kPag). Slowly open the valve.  
The compressor restarts under Time Guard control when the  
pressure builds to approximately 67 psig (462 kPag).  
Table 18 — Pressure Switch Settings,  
Psig (kPag)  
SWITCH  
High  
CUTOUT  
CUT-IN  
426 ±  
7
320 ± 20  
(2205 ± 138)  
(2935 ± 48)  
27 ±  
4
67 ±  
7
Low  
(186 ± 28)  
(462 ± 48)  
Capacity Control  
38AH044-084 DUAL-CIRCUIT UNITS — Capacity con-  
trol is achieved by a pressure-actuated cylinder bank un-  
loader on lead compressor A1. As the cooling load decreases  
and the suction pressure drops, the unloader actuates at the  
pre-set suction pressure and unloads the cylinder bank. (See  
Fig. 44 and Table 19A.) The unloading of the compressor  
cylinder bank has no effect on the operation of lag compres-  
sor B2, which is controlled by TC2.  
38AH044-084 SINGLE-CIRCUIT UNITS AND MOD-  
ULES 124A, 124B, 134A, AND 134B — Capacity control  
is achieved by a pressure-actuated cylinder bank unloader  
on lead compressor A1. See Table 16. As the cooling load  
decreases and the suction pressure drops, the unloader  
actuates at the pre-set suction pressure and unloads the cyl-  
inder bank. (See Fig. 44 and Table 19B and 20.) Lag com-  
pressorA2 is controlled by fixed setting capacity control pressure  
switches (CCPSs) as follows:  
CUT-IN —  
Psi (kPa)  
CUTOUT —  
Psi (kPa)  
Unloader Settings  
CCPS 1  
CCPS 2  
83 (572)  
80 (551)  
63 (531)  
53 (365)  
Unload, psig (kPag)  
Load, psig (kPag)  
56 (386)  
76 (524)  
CCPS  
Capacity Control Pressure Switch  
*Unloader location.  
Fig. 44 — Unloader Location and Settings  
If suction pressure continues to drop after lead compres-  
sor A1 unloads and lag compressor A2 is operating, A2 will  
stop operating when the suction pressure drops to the CCPS  
cutout point.  
47  
Table 19A — One 2-Stage Thermostat Capacity  
Control for 38AH044-084 Dual-Circuit Units  
Table 20 — One 2-Stage Thermostat Capacity  
Control for 38AH094-134 Units  
QUANTITY OF LOADED  
SYSTEM  
QUANTITY OF LOADED  
SYSTEM  
CAPACITY  
(%)  
UNIT  
38AH  
COMPRESSOR CYLINDERS  
COMPRESSOR CYLINDERS  
UNIT  
38AH  
CAPACITY  
(%)  
Circuit  
A
Circuit  
B
Ckt A  
Ckt B  
Total  
Total  
10  
10  
10  
10  
8
6
4
2
0
0
0
0
16  
14  
12  
10  
8
100  
85  
4
2
4
2
4
4
0
0
8
6
4
2
100  
75  
70*  
55  
044  
054  
50  
25  
094  
104  
44  
6
4
6
4
33  
4
2
2
4
2
6
6
4
0
0
10  
8
100  
79  
59  
42  
21  
22  
6*  
4
10  
8
12  
12  
10  
6
22  
20  
18  
16  
12  
10  
6
100  
91  
82  
73  
55  
45  
27  
18  
18  
9†  
2
8
10  
6
6
4
2
6
4
2
6
6
6
0
0
0
12  
10  
8*  
6
100  
84  
68  
48  
32  
16  
6
6
4
064  
074  
084  
0
6
4
0
4
4
0
4
4
2*  
2†  
0
2
6
4
2
6
4
2
6
6
6
0
0
0
12  
10  
8*  
6
100  
86  
72  
43  
29  
15  
12  
10  
10  
12  
12  
10  
10  
10  
8*  
6
24  
22  
20  
18  
16  
14  
12  
10  
6
100  
92  
83  
75*  
67  
58*  
50  
42  
25  
17  
8*  
8*  
4
6
6
2*  
124  
6
4
2
6
4
2
6
6
6
0
0
0
12  
10  
8*  
6
100  
83  
66  
50  
33  
17  
6
4
6
6
0
4
0
4
2
4
2*  
0
2*  
12  
12  
12  
10  
10  
10  
8*  
6
24  
22  
20  
18  
16  
14  
12  
10  
6
100  
92  
83  
75*  
67  
58*  
50  
42  
25  
17  
8*  
10  
10  
*Requires units with VAV (variable air volume) factory-supplied  
option.  
8*  
NOTE: Units have 2 independent refrigeration circuits. Circuit A is lead  
circuit.  
6
6
134  
6
4
6
6
0
Table 19B — One 2-Stage Thermostat Capacity  
Control for 38AH044-084 Optional Single-Circuit Units  
4
0
4
2
2*  
0
*Requires VAV (variable air volume) unit or accessory unloader(s) field  
installed on circuit lead compressor. Lead compressor is identified in  
Table 16, page 40.  
SYSTEM  
UNIT  
38AH  
QUANTITY OF  
CAPACITY  
(%)  
LOADED CYLINDERS  
†Requires field-installed accessory unloader on circuit lead compres-  
sor. Lead compressor is identified in Table 16, page 40.  
8
6
4
2
100  
75  
50  
25  
044  
054  
NOTES:  
1. Temperatures calculated with the minimum number of fans oper-  
ating per circuit.  
10  
8
100  
81  
2. See Table 16, page 40, for information on lead and lag circuits.  
6
60  
6
56  
4
37  
2*  
19*  
CONTROL SET POINT — Control set point (cylinder load  
point) is adjustable from 0 to 85 psig (0 to 586 kPag).  
To adjust the set point, turn the control set point adjust-  
ment nut clockwise to bottom stop. (See Fig. 46.) In this  
position, load-up set point is 85 psig (586 kPag). Turn  
adjustment counterclockwise to desired control set point.  
Every full turn clockwise decreases the load-up set point by  
7.5 psig (52 kPag).  
12  
10  
8
100  
82  
64  
56  
36  
18  
064  
074  
084  
6
4
2†  
12  
10  
8
100  
81  
62  
57  
38  
19  
6
4
PRESSURE DIFFERENTIAL — Pressure differential  
(difference between cylinder load and unload points) is  
adjustable from 6 to 22 psig (41 to 152 kPag). To adjust,  
turn pressure differential adjustment screw counterclock-  
wise to back stop position. The differential pressure is now  
adjusted to 6 psig (41 kPag). Turn the adjustment screw clock-  
wise to adjust the differential pressure. Every full clockwise  
turn increases the differential by 1.5 psig (10 kPag).  
2†  
12  
10  
8
100  
83  
66  
50  
33  
17  
6
4
2†  
*Requires accessory unloader on lead 06E-265 compressor (A1).  
†Requires VAV (variable air volume) factory-installed option or ac-  
cessory unloader.  
48  
CONDENSER  
COIL  
FUSIBLE  
PLUG  
SUCTION  
LINE  
ACCUMULATOR  
DISCHARGE  
LINE  
COMPRESSOR RAIL  
Fig. 45 — Accumulator and Fusible Plug  
Timer Functions — (See Timer Cycle, Fig. 47.) Each  
refrigeration circuit is controlled by an independent timer  
which allows for the independent operation of each refrig-  
eration circuit.  
Fig. 46 — Pressure-Actuated Capacity Control Valve  
CONTROL  
NOTE: Unit 38AH044-084 optional single-circuit units have  
one timer which controls the lead compressor. Lag compres-  
sor is controlled by CCPS (capacity control pressure switch).  
Sequence of Operation — Units are controlled with  
electromechanical components. Each refrigeration circuit  
(except 38AH044-084 optional single-circuit units) is oper-  
ated by an independent timer which controls the operation  
sequence of each circuit.  
SWITCH A — The timer is energized through contacts A-A1  
or A-A2. This establishes the Time Guardfunction which  
prevents compressor short-cycling. Start of compressor is  
delayed approximately 5.5 minutes after shutdown.  
On a call for cooling, first stage cooling thermostat TC1  
closes. Condenser fans and timer (TM) are energized. After  
approximately 7 seconds, timer contacts E-E1 close.  
Approximately 12 seconds after TC1 closes, normally-open  
timer contacts B-B1 close for 1 second. This energizes  
compressor A1 contacts CA1 and starts the compressor. At  
the same time, solenoid drop relays (SDRs) and liquid line  
solenoid valve no. 1 (LLS-A for 38AH044-084 dual-circuit  
units; LLS-A1 for all other units) open, and timer relay  
no. 1 (TR2) is energized. Normally open TR2 contacts close,  
completing a circuit around B-B1 and through compressor  
A1 contactors to maintain compressor operation when B-B1  
contacts open. Contacts E-E1 remain closed for approxi-  
mately 40 seconds to bypass the oil pressure switch (OPS).  
If oil pressure is insufficient when contacts E-E1 open, the  
compressor stops, the timer cycles off, and the control cir-  
cuit locks out. At start-up, timer contacts D-D1 are closed,  
bypassing low-pressure relay contacts LPR-A for 212 min-  
utes. This provides a winter start-up feature.  
SWITCH B — The compressor is initially energized through  
contacts B-B1.  
SWITCH D — Contacts D-D1 provide a 212-minute bypass  
of the low-pressure switch at start-up for winter-start con-  
trol. On 38AH044-084 optional single-circuit units, contacts  
D-D2 control start-up of compressor A2.  
SWITCH E — Contacts E-E1 provide a 40-second bypass  
of the oil pressure switch at start-up. If oil pressure does not  
build to the required minimum pressure in 40 seconds, the  
compressor shuts down and the control circuit locks out.  
On 38AH044-084 dual-circuit and 38AH094,104 units, lag  
circuit B start-up is delayed 60 seconds after a call for cool-  
ing is made to the circuit. This prevents compressor(s) in  
both lead and lag circuits from starting at the same time.  
Control Circuit Reset — The control circuit locks out  
if the unit shuts down because of low oil pressure, high  
discharge gas temperature (DGT), or excessive high-side pres-  
sure. To reset the control circuit, open and close the fan  
circuit breaker (FCB). This resets the timer, and the unit  
restarts under Time Guard control. At start-up, if the low-  
pressure switch (LPS) does not close after 212 minutes, the  
unit shuts down. When the pressure builds enough for the  
LPS to cut in, the control circuit is energized automatically  
and start-up proceeds under Time Guard control.  
Approximately 212 minutes after TC1 closes, timer con-  
tacts D-D1 open and D-D2 close. If pressure is insufficient  
to close the low-pressure switch, the low-pressure switch  
relay is open, the compressor shuts down, and the Time Guard  
control is initiated. (Time Guard control prevents compres-  
sor from restarting for 5 minutes after the demand for cool-  
ing is satisfied.)  
49  
38AH044-084 DUAL-CIRCUIT UNITS; 38AH094,104 —  
If circuit A operation is insufficient for the cooling require-  
ments, the thermostat second stage TC2 closes to bring cir-  
cuit B on-line for cooling. This circuit follows the same se-  
quence of operation as the lead circuit, except a  
60-second time delay relay (TDR) delays compressor start-up  
for 60 seconds after the call for cooling.  
38AH044-084 OPTIONAL SINGLE-CIRCUIT UNITS: MOD-  
ULES 124A, 124B, 134A, AND 134B  
NOTE: This sequence of operation assumes that 2 thermo-  
stats control units 38AH124 or 134 with one thermostat con-  
trolling each module.  
If compressor A1 is insufficient for the cooling require-  
ments, the thermostat second stage closes, which opens the  
liquid line solenoid valve LLS-A2. Compressor A2 starts only  
after D-D2 contacts in the timer close and the suction pres-  
sure is sufficient to close the capacity control switches.  
NOTE: Black denotes closed contacts.  
Fig. 47 — Timer Cycle  
Unit Control Box — (See Fig. 48.) Viewed facing com-  
pressors, the control box is at left end of the unit. All in-  
coming power enters through the control box. The control  
box contains power components and electronic controls. Outer  
panels are hinged and latched for easy opening. Remove screws  
to remove inner panels. Outer panels can be held open for  
service and inspection by using door retainer on each panel.  
Remove bottom pin from door retainer assembly, swing re-  
tainer out horizontally, and engage pin in one of the retainer  
ears and the hinge assembly.  
ALL UNITS — When the fan switch is set for automatic  
(AUTO) operation, the indoor-fan contactor (IFC) is cycled  
with the lead compressor. If the fan switch is set for con-  
tinuous (CONT), the IFC is energized as long as the unit  
power is on.  
Restart After Stoppage by Safety Control — The  
high-pressure switch, compressor discharge gas thermostats,  
and the oil pressure switch must be reset manually by break-  
ing the control power supply at any of the following points:  
control circuit fuse, fan motor circuit breaker, or the ther-  
mostat. Restart follows the Time Guardcontrol delay.  
Stoppage by low-pressure switch results in Time Guard  
control delay, then unit attempts normal restart.  
The compressor motor overcurrent protectors are manual-  
reset circuit breakers. Reset of control circuit may also be  
necessary.  
Condenser Fans — Each fan is supported by a formed  
wire mount bolted to fan deck and covered with a wire guard.  
The exposed end of fan motor shaft is protected from weather  
by grease. If fan motor must be removed for service or re-  
placement, be sure to regrease fan shaft, and reinstall fan  
7
guard. For proper performance, fan should be  
8  
in.  
(22 mm) below top of venturi on the fan deck to top of  
the fan hub for 60-Hz units, and 2 in. (13 mm) for 50-Hz  
1
Independent Refrigerant Circuit Controls — Each  
refrigeration circuit is controlled by independent circuitry.  
Therefore, it is possible to maintain partial cooling capabil-  
ity even if one compressor is inoperable.  
units. (See Fig. 49.) Tighten set screws to 15 ± 1 ft-lbs  
(20 ± 1.3 N-m). Figure 49 shows proper position of mounted  
fan.  
IMPORTANT: Check for proper fan rotation (clock-  
wise viewed from above). If necessary to reverse, switch  
leads.  
NOTE: The 38AH044-084 optional single-circuit units do  
not have independent control circuitry.  
50  
TRANSFORMERS  
FAN CONTACTORS  
TIMERS  
TIME-DELAY  
RELAY  
COMPRESSOR  
CIRCUIT  
BREAKERS  
FAN CIRCUIT  
BREAKER  
TERMINAL  
BLOCKS  
OIL PRESSURE  
SWITCHES  
FUSE  
HOLDERS  
TERMINAL  
BLOCKS  
COMPRESSOR  
CONTACTORS  
Fig. 48 — Unit Control Box  
Required Compressor Modification for 38AH044-  
084 Optional Single-Circuit Units, When Com-  
pressor A1 is Out — To maintain unit operation, com-  
pressor no.1 must be operable. If it is not operable, the following  
temporary modifications must be made to keep the unit  
running:  
1. Change the oil pressure switch connections from com-  
pressor A1 to compressor A2.  
2. Connect compressor A2 into the Time Guardcircuit as  
compressor A1 was originally.  
3. Open compressor A1 circuit breaker.  
NOTE: Make sure the crankcase heaters are energized when  
compressors are off.  
NOTE: Fan rotation is clockwise when viewed from top of unit.  
Fig. 49 — Condenser Fan Adjustment  
51  
Compressor Removal — Access to the pump end  
of the compressor is from the compressor side of the unit.  
Access to the motor end of the compressor is from the inside  
of the unit. All compressors can be removed from the com-  
pressor side of the unit.  
Compressor Replacement — Perform the following:  
1. Reverse procedure in Compressor Removal section to end  
of Step 4.  
2. Reinstall service valves and safety switches, and tighten  
to torques as listed:  
IMPORTANT: All compressor mounting hardware and  
support brackets removed during servicing must be re-  
installed prior to start-up.  
Torque  
Compressor(s)  
Tighten discharge valves to —  
20-25 ft-lbs ( 27- 34 N-m)  
80-90 ft-lbs (109-122 N-m)  
Tighten suction valves to —  
80- 90 ft-lbs (109-122 N-m)  
90-120 ft-lbs (122-163 N-m)  
06E-250  
06E-265,275,299  
1. Disconnect power to unit; lockout power to compressor.  
2. Close suction and discharge service valves.  
3. Relieve refrigerant pressure into a refrigerant recovery  
system.  
06E-250  
06E-265,275,299  
Tighten the following fittings as specified —  
60 ft-lbs (81 N-m)  
120 in.-lbs (13.5 N-m)  
4. Remove:  
Discharge Gas Thermostat  
High-Pressure Switch, Fan-  
Cycling Pressure Switch  
a. Fan-cycling pressure switch (FCPS)  
b. High-pressure switch  
c. Low-pressure switch  
120 in.-lbs (13.5 N-m)  
Low-Pressure Switch  
d. Oil-pressure switch  
e. Discharge gas temperature switch.  
5. Disconnect power wires at terminal box and disconnect  
conduit.  
6. Disconnect wires from crankcase heater.  
7. Disconnect service valves from compressor.  
3. Leak-check and evacuate system, reclaim refrigerant.  
4. Recharge system per pre-start-up and start-up sequences.  
Recheck oil levels.  
5. Energize crankcase heater for 24 hours prior to restart of  
system.  
OIL CHARGE — (Refer to Table 3A, 3B, 4A, or 4B.) All  
units are factory charged with oil. Acceptable oil level for  
each compressor is from 18 to 13 of sight glass (see Fig. 29,  
page 38).  
When additional oil or a complete charge is required, use  
only Carrier-approved compressor oil.  
NOTE: On 38AH044-084 optional single-circuit units and  
units with 2 compressors per circuit, disconnect both oil  
equalizer lines located on the motor barrel and on the oil  
pump sump.  
8. Units 38AH044-084, 124, and 134:  
a. Remove 4 large screws securing compressor mount-  
ing pan to unit base rail.  
b. Slide compressor (on mounting pan) to outside of unit  
frame; support and/or lower to ground.  
Approved oils are:  
Petroleum Specialties, Inc. — Cryol 150A (factory oil charge)  
Texaco, Inc.  
Witco Chemical Co.  
— Capella WF-32-150  
— Suniso 3GS  
c. Unbolt compressor from mounting pan and remove.  
9. Units 38AH094, 104:  
OIL REQUIRED  
Pts  
COMPRESSOR  
L
a. Remove 4 large screws securing compressor to the com-  
pressor rails.  
b. Lift compressor off mounting bolts and remove.  
06E-250  
06E-265  
06E-275  
06E-299  
17  
21  
21  
19  
8.0  
9.9  
9.9  
9.0  
Do not reuse drained oil, and do not use any oil that has  
been exposed to atmosphere.  
Adjust oil level in accordance with Start-Up, Preliminary  
Oil Charge, page 38.  
52  
TROUBLESHOOTING  
PROBLEM  
COMPRESSOR DOES NOT RUN  
Contactor Open  
SOLUTION  
1. Power off.  
1. Restore power.  
2. Fuses blown in field power circuit.  
2. After finding cause and correcting, replace with correct  
size fuse.  
3. No control power.  
3. Check secondary fuse(s); replace with correct type and  
size. Replace transformer if primary windings receiving  
power.  
4. Thermostat circuit open.  
4. Check thermostat setting.  
5. Multi-function timer not operating.  
6. Compressor circuit breaker tripped.  
5. Check timer for proper operation; replace if defective.  
6. Check for excessive compressor current draw. Reset  
breaker; replace if defective.  
7. Safety device lockout circuit active.  
8. Low-pressure switch open.  
7. Reset lockout circuit at thermostat or circuit breaker.  
8. Check for refrigerant undercharge, obstruction of indoor  
airflow, or whether compressor suction shutoff valve is  
fully open. Make sure liquid line solenoid valve(s) is  
open.  
9. High-pressure switch open.  
9. Check for refrigerant overcharge, obstruction of outdoor  
airflow, air in system or whether compressor discharge  
valve is fully open. Be sure outdoor fans are operating  
correctly.  
10. Discharge gas temperature switch open.  
10. Check for open condition. Allow for reset. Replace if  
defective.  
11. Loose electrical connections.  
12. Compressor stuck.  
11. Tighten all connections.  
12. See 06E compressor service literature.  
Contactor Closed  
1. Compressor leads loose.  
2. Motor windings open.  
3. Single phasing.  
1. Check connections.  
2. See 06E compressor service literature.  
3. Check for blown fuse. Check for loose connection at  
compressor terminal.  
COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH  
Outdoor Fan On  
1. High-pressure switch faulty.  
2. Airflow restricted.  
1. Replace switch.  
2. Remove obstruction.  
3. Air recirculating.  
3. Clear airflow area.  
4. Noncondensables in system.  
5. Refrigerant overcharge.  
6. Line voltage incorrect.  
7. Refrigerant system restrictions.  
4. Purge and recharge as required.  
5. Purge as required.  
6. Consult power company.  
7. Check or replace filter drier, expansion valve, etc. Check  
that compressor discharge valve is fully open.  
Outdoor Fan Off  
1. Fan slips on shaft.  
2. Motor not running.  
3. Motor bearings stuck.  
4. Motor overload open.  
5. Motor burned out.  
1. Tighten fan hub setscrews.  
2. Check power and capacitor.  
3. Replace bearings.  
4. Check overload rating. Check for fan blade obstruction.  
5. Replace motor.  
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH  
Indoor-Air Fan Running  
1. Filter drier plugged.  
1. Replace filter drier.  
2. Expansion valve power head defective.  
3. Low refrigerant charge.  
2. Replace power head.  
3. Add charge. Check low-pressure switch setting.  
Airflow Restricted  
1. Coil iced up.  
2. Coil dirty.  
1. Check refrigerant charge.  
2. Clean coil fins.  
3. Air filters dirty.  
4. Dampers closed.  
3. Clean or replace filters.  
4. Check damper operation and position.  
Indoor-Air Fan Stopped  
1. Electrical connections loose.  
2. Fan relay defective.  
1. Tighten all connections.  
2. Replace relay.  
3. Motor overload open.  
4. Motor defective.  
3. Power supply.  
4. Replace motor.  
5. Fan belt broken or slipping.  
5. Replace or tighten belt.  
53  
TROUBLESHOOTING (cont)  
PROBLEM  
SOLUTION  
COMPRESSOR STOPS ON OIL PRESSURE SWITCH  
1. Oil level too low or too high.  
1. Check oil level requirements; adjust oil level until sight  
1
1
glass is filled  
2. Check for  
8
to  
3
when running.  
2. Compressor is short cycling.  
a) Thermostat location and operation.  
b) Safety device lockout circuit operation.  
c) End-of-cycle control and timer operation.  
d) Low-pressure switch and relay operation.  
3. Check relay operation; replace crankcase heater(s), if  
defective.  
3. Crankcase heater off.  
4. Low refrigerant charge.  
4. Adjust charge as required.  
5. Refrigerant floodback.  
5. Adjust TXV superheat.  
6. Evaporator coil is blocked or iced.  
7. Evaporator fan not operating.  
8. Distributor and/or TXV too large.  
6. Check and correct as required.  
7. Check and correct as required.  
8. Check sizing at design conditions; change if incorrect  
for current application.  
9. Suction riser too large.  
9. Check line sizing at minimum design condition; change  
piping if incorrect.  
10. Defective oil pressure switch.  
10. Check switch for proper operation; check capillary lines  
for plugged lines.  
11. Plugged oil pump inlet screen.  
12. Faulty oil pump drive segment.  
13. Worn oil pump.  
11. Clean oil pump screen.  
12. Replace drive segment.  
13. Replace bearing head assembly.  
14. Replace compressor; see 06E service instructions.  
14. Worn compressor bearings.  
COMPRESSOR RUNNING BUT COOLING INSUFFICIENT  
Suction Pressure Low  
1. Refrigerant charge low.  
2. Head pressure low.  
1. Add refrigerant.  
2. Check refrigerant charge.  
Check outdoor-air fan thermostat settings.  
3. Clean or replace filters.  
4. Replace power head.  
5. Check low-pressure setting.  
6. Remove obstruction.  
3. Air filters dirty.  
4. Expansion valve power head defective.  
5. Indoor coil partially iced.  
6. Indoor airflow restricted.  
Suction Pressure High  
1. Unloaders not functioning.  
1. Check unloader adjustments.  
Check unloader setting.  
2. Compressor valve defective.  
3. Heat load excessive.  
2. See 06E compressor service literature.  
3. Check for open doors or windows in vicinity of fan coil.  
UNIT OPERATES TOO LONG OR CONTINUOUSLY  
1. Low refrigerant charge.  
1. Add refrigerant.  
2. Control contacts fused.  
2. Replace control.  
3. Air in system.  
4. Partially plugged expansion valve or filter drier.  
3. Purge and evacuate system.  
4. Clean or replace.  
SYSTEM IS NOISY  
1. Piping vibration.  
1. Support piping as required.  
2. Compressor noisy.  
2. Check valve plates for valve noise. Replace compressor  
if bearings are worn.  
COMPRESSOR LOSES OIL  
1. Leak in system.  
1. Repair leak.  
2. Crankcase heaters not energized during shutdown.  
2. Check wiring and relays. Check heater and replace if  
defective.  
3. Improper interconnecting piping design.  
FROSTED SUCTION LINE  
3. Check piping for oil return. Replace if necessary.  
1. Expansion valve admitting excess refrigerant.  
HOT LIQUID LINE  
1. Adjust expansion valve.  
1. Shortage of refrigerant due to leak.  
2. Expansion valve opens too wide.  
1. Repair leak and recharge.  
2. Adjust expansion valve.  
FROSTED LIQUID LINE  
1. Restricted filter drier.  
1. Remove restriction or replace.  
COMPRESSOR WILL NOT UNLOAD  
1. Defective unloader.  
1. Replace unloader.  
2. Replace valve.  
3. Rewire correctly.  
4. Replace spring.  
2. Defective capacity control solenoid valve (if used).  
3. Miswired capacity control liquid line solenoid (if used).  
4. Weak, broken, or wrong valve body spring.  
COMPRESSOR WILL NOT LOAD  
1. Miswired capacity control liquid line solenoid (if used).  
2. Defective capacity control solenoid valve (if used).  
3. Plugged strainer (high side).  
1. Rewire correctly.  
2. Replace valve.  
3. Clean or replace strainer.  
4. Clean or replace the necessary parts.  
4. Stuck or damaged unloader piston or piston ring(s).  
Copyright 1998 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 563-704  
Printed in U.S.A.  
Form 38AH-15SI  
54  
10-98  
Replaces: 38AH-14SI  
Tab 3a  
START-UP CHECKLIST  
A. Preliminary Information  
OUTDOOR: MODEL NO.  
SERIAL NO.  
SERIAL NO.  
INDOOR: AIR HANDLER MANUFACTURER  
MODEL NO.  
ADDITIONAL ACCESSORIES  
B. Pre-Start-Up  
OUTDOOR UNIT  
IS THERE ANY SHIPPING DAMAGE?  
IF SO, WHERE:  
(Y/N)  
WILL THIS DAMAGE PREVENT UNIT START-UP?  
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?  
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)  
(Y/N)  
(Y/N)  
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?  
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?  
(Y/N)  
(Y/N)  
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED?  
(Y/N)  
CONTROLS  
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING  
CONNECTIONS MADE AND CHECKED?  
(Y/N)  
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?  
HAVE CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS?  
(Y/N)  
(Y/N)  
INDOOR UNIT  
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?  
ARE PROPER AIR FILTERS IN PLACE? (Y/N)  
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?  
(Y/N)  
(Y/N)  
DO THE FAN BELTS HAVE PROPER TENSION?  
(Y/N)  
PIPING  
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED?  
(Y/N)  
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, EVAPORATORS,  
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS  
WITH A LEAK DETECTOR?  
(Y/N)  
LOCATE, REPAIR, AND REPORT ANY LEAKS.  
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)?  
(Y/N)  
1
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING ABOUT 2 FULL?  
(Y/N)  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
AB  
V
AC  
V
BC  
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =  
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
CL-1  
C. Start-Up  
CHECK EVAPORATOR FAN SPEED AND RECORD.  
CHECK CONDENSER FAN SPEED AND RECORD.  
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
COMP A1  
COMP A2  
COMP B1  
COMP B2  
OIL PRESSURE  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER AIR TEMP  
LEAVING CONDENSER AIR TEMP  
EVAP ENTERING AIR DB TEMP  
EVAP ENTERING AIR WB TEMP  
EVAP LEAVING AIR DB TEMP  
EVAP LEAVING AIR WB TEMP  
COMPRESSOR AMPS (L1)  
COMPRESSOR AMPS (L2)  
COMPRESSOR AMPS (L3)  
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING  
1
1
OIL LEVEL AT  
8  
TO  
3
FULL?  
(Y/N)  
NOTES:  
Copyright 1998 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 563-704  
Printed in U.S.A.  
Form 38AH-15SI  
CL-2  
10-98  
Replaces: 38AH-14SI  
Tab 3a  

Brother MFC 8880DN User Manual
Bryant DURAPAC PLUS 551B User Manual
Carrier 38AH024 034 User Manual
Carrier KC_233P User Manual
Casio CELVIANO AP 31V User Manual
EMI DWPH365 WHP36 SHC36 User Manual
GE General Electric Air Conditioner 3828A User Manual
GE General Electric Air Conditioner AS_18 User Manual
Graco UltraClear 2755B User Manual
Haier AD282AMERA User Manual