Bryant R 22 User Manual

Application Guide and  
Service Manual  
AIR CONDITIONERS AND HEAT PUMPS  
USING R-22 REFRIGERANT  
Cancels: AP01-3, SM01,02-4  
SM01,02-5  
10-00  
NOTE: Read the entire instruction manual before starting the  
installation.  
Fan Motors..............................................................................21  
Service Alarm Control Board.................................................21  
Outdoor Thermostat(s)............................................................22  
Compressor Plug.....................................................................24  
Low-Voltage Terminals..........................................................25  
This symbol indicates a change since the last issue.  
TABLE OF CONTENTS  
RECIPROCATING COMPRESSOR ..........................................25  
Mechanical Failures................................................................25  
Electrical Failures ...................................................................26  
System Cleanup After Burnout ..............................................27  
Compressor Removal And Replacement ...............................27  
SAFETY CONSIDERATIONS.....................................................1  
INTRODUCTION..........................................................................2  
INSTALLATION GUIDELINE ....................................................2  
Residential New Construction..................................................2  
Add-On Replacement (Retrofit)...............................................2  
Seacoast (For Air Conditioners Only) .....................................2  
COPELAND SCROLL COMPRESSOR ....................................28  
Features ...................................................................................28  
Troubleshooting ......................................................................28  
Discharge Thermostat.............................................................28  
Discharge Solenoid Valve ......................................................28  
ACCESSORY DESCRIPTIONS...................................................2  
Compressor Crankcase Heater..................................................2  
Evaporator Freeze Thermostat..................................................2  
Winter Start Control .................................................................2  
Compressor Start Assist—PTC ................................................2  
Compressor Start Assist Capacitor/Relay ................................2  
Low-Ambient Controller ..........................................................2  
MotorMaster™ Control ............................................................2  
Low-Ambient Pressure Switch.................................................2  
Wind Baffle...............................................................................3  
Coastal Filter.............................................................................3  
Support Feet..............................................................................3  
Liquid-Line Solenoid Valve.....................................................3  
Thermostatic-Expansion Valve.................................................3  
Isolation Relay ..........................................................................3  
MILLENNIUM SCROLL COMPRESSOR................................29  
Features ...................................................................................29  
Compressor Protection............................................................29  
Troubleshooting ......................................................................29  
Scroll Compressor, 3–Phase Monitor.....................................29  
TWO-SPEED SYSTEM ..............................................................29  
Cautions and Warnings...........................................................29  
System Functions....................................................................29  
Factory Defaults......................................................................33  
Major Components..................................................................33  
LED Function/Malfunction Lights.........................................34  
Troubleshooting ......................................................................34  
LOW-AMBIENT GUIDELINE.....................................................3  
REFRIGERATION SYSTEM .....................................................35  
Refrigeration Cycle.................................................................35  
Leak Detection........................................................................35  
Brazing ....................................................................................37  
Service Valves ........................................................................38  
Check-Flo-Rater™ (Bypass-Type) Heat Pumps Only...........39  
Reversing Valve......................................................................39  
Thermostatic-Expansion Valves (TXV).................................40  
Thermostatic-Expansion Valve (Bi-Flow TXV)....................41  
Coil Removal ..........................................................................41  
Liquid-Line Strainer (Heat Pumps Only) ..............................41  
Accumulator............................................................................43  
Contaminant Removal ............................................................43  
System Charging.....................................................................43  
Checking Charge.....................................................................43  
LONG-LINE GUIDELINE............................................................3  
Approved Systems ....................................................................3  
Interconnecting Tubing Sizing .................................................3  
Metering Device Sizing............................................................6  
Liquid-Line Solenoid And Tubing Configuration...................7  
Charging Information................................................................8  
2–Speed Applications ...............................................................8  
UNIT IDENTIFICATION .............................................................8  
Product Number Stamped on Unit-Rating Plate......................8  
Serial Number Identification ....................................................9  
CABINET.....................................................................................10  
Remove Top Cover—Before 1/1/92 ......................................10  
Remove Fan-Motor Assembly—Before 1/1/92.....................10  
Information Plate—Reliant Products......................................10  
Control-Box Cover—Cube Products......................................10  
Remove Top Cover— After 1/1/92 .......................................10  
Remove Fan-Motor Assembly—After 1/1/92........................11  
CARE AND MAINTENANCE...................................................45  
SAFETY CONSIDERATIONS  
Service and repair of these units should be attempted only by  
trained service technicians familiar with Bryant standard service  
instructions and training manual.  
ELECTRICAL..............................................................................12  
Aluminum Wire ......................................................................12  
Contactors................................................................................13  
Capacitors................................................................................14  
Cycle Protector........................................................................15  
Crankcase Heater ....................................................................16  
Time-Delay Relay...................................................................16  
Pressure Switches....................................................................17  
Defrost Thermostats................................................................18  
Defrost-Control Board ............................................................18  
All equipment should be installed in accordance with accepted  
practices and unit Installation Instructions, and in compliance with  
all national and local codes.  
Power should be turned off when servicing or repairing electrical  
components. Extreme caution should be observed when trouble-  
shooting electrical components with power on. Observe all warn-  
ing notices posted on equipment.  
—1—  
TABLE 1REQUIRED FIELD-INSTALLED ACCESSORIES FOR AIR CONDITIONERS AND HEAT PUMPS  
REQUIRED FOR  
LOW-AMBIENT  
APPLICATIONS  
(BELOW 55°F)  
REQUIRED FOR  
LONG-LINE  
APPLICATIONS*  
(OVER 50 FT)  
REQUIRED FOR  
SEA COAST  
APPLICATIONS  
(WITHIN 2 MILES)  
ACCESSORY  
Crankcase Heater  
Evaporator Freeze Thermostat  
Winter Start Control  
Accumulator  
Yes  
Yes  
Yes†  
No  
Yes  
No  
No  
No  
No  
No  
No  
No  
Compressor Start Assist  
Capacitor and Relay  
Yes  
Yes  
No  
Low Ambient Controller,  
MotorMasterControl,  
or  
Yes  
No  
No  
Low-Ambient Pressure Switch  
Wind Baffle  
Coastal Filter  
Support Feet  
See Low-Ambient Instructions  
No  
No  
No  
No  
Yes  
No  
Recommended  
Recommended  
Liquid-Line Solenoid Valve  
See Long-Line  
Application  
Guideline  
or  
No  
No  
Hard-Shutoff TXV  
Ball-Bearing Fan Motor  
Isolation Relay  
Yes‡  
Yes**  
No  
No  
No  
No  
*For tubing line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline.  
†Only when low-pressure switch is used.  
‡Required for Low-Ambient Controller (full modulation feature) and MotorMaster™ control only.  
** Required on Heat Pumps only.  
IX. WIND BAFFLE  
LONG-LINE GUIDELINE  
A field-fabricated sheet-metal cover used to stop prevailing winds  
or where outdoor ambient temperature is less than 55°F during unit  
operation of cooling mode.  
This Long-Line Application Guideline applies to all Bryant  
residential air conditioner and heat pump split systems that have a  
nominal capacity of 18,000 to 60,000 Btuh. This guideline  
provides required system changes and accessories necessary for  
any residential product having piping requirements greater than 50  
ft or installations where indoor unit is located above outdoor unit.  
This guideline is intended to cover applications outside the  
standard Installation Instructions. This guideline is for standard,  
single-speed products. For applications involving 2-speed prod-  
ucts, refer to Section VI first.  
X. COASTAL FILTER  
A mesh screen inserted under top cover and inside base pan to  
protect condenser coil from salt damage without restricting air-  
flow.  
XI. SUPPORT FEET  
Four adhesive plastic feet which raise unit 4 in. above mounting  
pad. This allows sand, dirt, and other debris to be flushed from unit  
base; minimizes corrosion.  
NOTE: The presale literature for outdoor unit must be referred to  
in conjunction with this guideline.  
XII. LIQUID-LINE SOLENOID VALVE  
I. APPROVED SYSTEMS  
An electrically operated shutoff valve to be installed at outdoor or  
indoor unit (depending on tubing configuration) which stops and  
starts refrigerant liquid flow in response to compressor operation.  
Maintains a column of refrigerant liquid ready for action at next  
compressor-operation cycle and prevents liquid migration during  
the off cycle.  
Any residential indoor/outdoor unit combination listed in the  
outdoor unit presale literature is an approved system, EXCEPT the  
following:  
Indoor coils with capillary-metering devices  
All equipment less than nominal 18,000 Btuh  
All 1/4-in. and 5/16in. liquid-line applications  
XIII. THERMOSTATIC-EXPANSION VALVE  
Any indoor furnace coil/fan coil not listed in outdoor unit  
A modulating flow-control device which meters refrigerant flow  
rate into the evaporator in response to the superheat of the  
refrigerant gas leaving the evaporator. Only use factory-specified  
TXVs.  
presale literature  
Any application which has interconnecting tubing with an  
equivalent length greater than 175 ft  
XIV. ISOLATION RELAY  
II. INTERCONNECTING TUBING SIZING  
A DPDT relay which switches the low-ambient controller out of  
the outdoor fan-motor circuit when the heat pump switches to  
heating mode.  
Table 4 lists recommended interconnecting vapor-line diameters  
for equivalent total-line lengths. All residential split systems  
installed in long-line applications must use only 3/8-in. liquid  
lines. Equivalent line length equals the linear length (measured) of  
interconnecting vapor tubing plus losses due to elbows. (See Table  
5 and Fig. 3.) Liquid lines larger than 3/8-in. OD greatly increase  
charge quantity of the system. Excessive charge increases risk of  
migration and compressor damage. Table 4 provides the estimated  
percentage of nominal cooling-capacity losses based on the stan-  
dard, required vapor line size versus what is selected for the  
long-line application. Since the vapor line is the discharge line in  
heating mode, losses are minimal.  
LOW-AMBIENT GUIDELINE  
The minimum operating temperature for these units in cooling  
mode is 55°F outdoor ambient without additional accessories. This  
equipment may be operated in cooling mode at ambient tempera-  
tures below 55°F when the accessories listed in Table 1 are  
installed. Wind baffles are required when operating in cooling  
mode at ambients below 55°F. Refer to Fig. 1 or 2 and Table 2 or  
3 for wind baffle construction details.  
3—  
1
3
/ x / (5.56 x 9.53) SLOT  
4
8
4 REQ'D  
1
/ (3.45) DIA HOLE  
8
2 REQ'D  
H
3
/ ″  
8
5 5  
(151.5)  
/
16  
(9.6)  
1
/ (5.56) DIA HOLE 2 REQ'D  
4
J
G
1
/ ″  
2
(12.7)  
TYP  
SUPPORT  
MAT'L: 18 GA STEEL  
7
/
16  
C
(11.6)  
E
A
1/2″  
(12.7)  
1
/ (3.45) DIA HOLE  
8
1 REQ'D  
K
7
B
/
16  
(11.6)  
J
1
/ (5.56) DIA HOLE  
4
3 REQ'D  
1
3
/ ″  
6″  
(152.4)  
4
/ (9.6)  
8
(6.3)  
L
D
1
/ x 2″  
4
BAFFLE  
MAT'L: 20 GA STEEL  
(5.56 x 50.8) SLOT  
SCREW  
10 REQ'D  
F
SUPPORT  
4 REQ'D  
AA  
OUTDOOR  
UNIT  
BAFFLE  
2 REQ'D  
BAFFLE ASSEMBLY  
A95445  
Fig. 1Wind Baffle Construction for Reliant Units  
4—  
Calculate the linear length of vapor tube required, adding any  
losses for the total number of elbows for application. (See Table  
5.) Using this equivalent length, select desired vapor-line size from  
Table 4. Subtract the nominal percentage loss from outdoor-unit  
presale-literature Detailed Cooling Capacities data for the given  
indoor/outdoor combination. Reference all notes of Table 4.  
All standard accessory-tubing kits are supplied with 3/8-in. insu-  
lation on vapor line.  
For minimal capacity loss in long-line application, 1/2-in. insula-  
tion should be specified.  
NOTE: When specifying vapor-line insulation, be aware of the  
following standard practice:  
TABLE 2WIND BAFFLE DIMENSIONS FOR RELIANT UNITS WITH AEROQUIET-SYSTEM TOP (IN.)  
UNIT SIZE  
Small  
AA  
UNIT HEIGHT  
23-13/16  
27-13/16  
33-13/16  
27-13/16  
33-13/16  
39-13/16  
33-13/16  
39-13/16  
A
B
C
D
E
F
G
H
J
K
0
L
17-1/4 24-5/16 10-1/4 19-3/4 20-1/2 34-1/2 19-5/8 20-3/8 19-5/8  
17-1/4 24-5/16 10-1/4 23-3/4 24-1/2 34-1/2 23-5/8 24-3/8 23-5/8  
17-1/4 24-5/16 10-1/4 29-3/4 30-1/2 34-1/2 29-5/8 30-3/8 29-5/8  
0
26-3/16  
0
11-7/8  
14-7/8  
11-7/8  
14-7/8  
17-7/8  
0
21  
21  
21  
30-5/8 10-1/4 23-3/4 24-1/2  
30-5/8 10-1/4 29-3/4 30-1/2  
30-5/8 10-1/4 35-3/4 36-1/2  
42  
42  
42  
23-5/8 24-3/8 23-5/8  
29-5/8 30-3/8 29-5/8  
35-5/8 36-3/8 35-5/8  
17-1/8  
17-1/8  
17-1/8  
Medium  
Large  
33  
25-5/16 39-3/4 10-1/4 29-3/4 30-1/2 50-9/16 29-5/8 30-3/8 29-5/8 21-11/16 14-7/8  
25-5/16 39-3/4 10-1/4 35-3/4 36-1/2 50-9/16 35-5/8 36-3/8 35-5/8 21-11/16 17-7/8  
42-1/16  
3
1
7 7/ ″  
/
16  
/ (3.45) DIA  
8
8
(200.0)  
(4.6)  
2 REQ'D  
F
5 3  
(128.0)  
/
64  
E
C
C
1
/ ″  
2
E
1
/ ″  
4
(12.7)  
(6.4)  
5 3  
/
64  
(128.0)  
13  
/
64  
1
/ ″  
2
(5.4)  
TYP  
7 29  
/
(200.8)  
32  
B
7 7/ ″  
(199.9)  
8
(12.7)  
TYP  
BAFFLE - LEFT  
25  
/
(10.0)  
64  
1 21  
/
(42.1)  
MAT'L: 20 GA STEEL  
32  
BAFFLE - RIGHT  
MAT'L: 20 GA STEEL  
D
2 1/ ″  
(63.5)  
1
2
/ (5.56) DIA  
4
A
2 REQ'D  
2 1/ ″  
(63.5)  
1
3
A
2
/ x / (5.56 x 9.53) SLOT  
4
8
6 REQ'D  
D
1
/ (5.56) DIA  
4
4 REQ'D  
1 21  
/
(42.1)  
32  
G
(10.0)  
1
3
/ x / (5.56 x 9.53) SLOT  
4
8
25  
64  
6 REQ'D  
AA  
C
4 9  
/
(105.2)  
64  
23  
/
64  
LEFT  
SIDE  
RIGHT  
SIDE  
45°  
TYP  
(9.2)  
J
2 5  
(52.6)  
/
64  
SCREW  
14 REQ'D  
1
/ (5.56) DIA  
4
4 57  
64  
2 REQ'D  
(124.2) TYP  
SUPPORT  
3 REQ'D  
1
OUTDOOR  
UNIT  
/ (12.7)  
2
8 5  
/
(205.3)  
TYP  
64  
TYP  
1
23  
/ ″  
4
/
(9.2)  
64  
(6.4)  
SUPPORT  
MAT'L: 18 GA STEEL  
1
BAFFLE ASSEMBLY  
/ (3.45) DIA.  
J H  
8
4 REQ'D  
A95446  
Fig. 2Wind Baffle Construction for Cube Units  
5—  
TABLE 3WIND BAFFLE DIMENSIONS FOR CUBE UNITS (IN.)  
UNIT SIZE  
Small  
AA  
UNIT HEIGHT  
21-15/16  
23-15/16  
25-15/16  
27-15/16  
29-15/16  
31-15/16  
33-15/16  
21-15/16  
23-15/16  
25-15/16  
27-15/16  
29-15/16  
31-15/16  
33-15/16  
35-15/16  
37-15/16  
25-15/16  
27-15/16  
29-15/16  
31-15/16  
33-15/16  
35-15/16  
37-15/16  
39-15/16  
A
B
C
D
E
F
G
H
J
19-7/8  
21-7/8  
23-7/8  
25-7/8  
27-7/8  
29-7/8  
31-7/8  
19-7/8  
21-7/8  
23-7/8  
25-7/8  
27-7/8  
29-7/8  
31-7/8  
33-7/8  
35-7/8  
23-7/8  
25-7/8  
27-7/8  
29-7/8  
31-7/8  
33-7/8  
35-7/8  
37-7/8  
13-3/4  
13-3/4  
13-3/4  
13-3/4  
13-3/4  
13-3/4  
13-3/4  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
18-5/16  
25-3/4  
25-3/4  
25-3/4  
25-3/4  
25-3/4  
25-3/4  
25-3/4  
25-3/4  
28-1/8  
28-1/8  
28-1/8  
28-1/8  
28-1/8  
28-1/8  
28-1/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
32-5/8  
40-1/8  
40-1/8  
40-1/8  
40-1/8  
40-1/8  
40-1/8  
40-1/8  
40-1/8  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
10-11/16  
20-1/4  
20-1/4  
20-1/4  
20-1/4  
20-1/4  
20-1/4  
20-1/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
24-3/4  
32-1/4  
32-1/4  
32-1/4  
32-1/4  
32-1/4  
32-1/4  
32-1/4  
32-1/4  
11-11/16  
11-11/16  
11-11/16  
11-11/16  
11-11/16  
11-11/16  
11-11/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
16-3/16  
23-11/16  
23-11/16  
23-11/16  
23-11/16  
23-11/16  
23-11/16  
23-11/16  
23-11/16  
3-13/16  
3-13/16  
3-13/16  
3-13/16  
3-13/16  
3-13/16  
3-13/16  
8-1/4  
19-13/16  
21-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
31-13/16  
19-13/16  
21-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
31-13/16  
33-13/16  
35-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
31-13/16  
33-13/16  
35-13/16  
37-13/16  
17-13/16  
19-13/16  
21-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
17-13/16  
19-13/16  
21-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
31-13/16  
33-13/16  
21-13/16  
23-13/16  
25-13/16  
27-13/16  
29-13/16  
31-13/16  
33-13/16  
35-13/16  
18  
8-1/4  
8-1/4  
8-1/4  
Medium  
22-1/2  
8-1/4  
8-1/4  
8-1/4  
8-1/4  
8-1/4  
15-13/16  
15-13/16  
15-13/16  
15-13/16  
15-13/16  
15-13/16  
15-13/16  
15-13/16  
Large  
30  
TABLE 4ESTIMATED PERCENTAGE OF NOMINAL COOLING-CAPACITY LOSSES*  
UNIT  
NOMINAL  
LONG-LINE  
EQUIVALENT LINE LENGTH (FT)  
VAPOR-LINE  
SIZE  
(BTUH)  
DIAMETER  
50  
75  
100  
125  
150  
175  
(IN.)†  
5/8  
5
1
6
0
6
2
7
2
7
3
0
10  
4
0
7
1
7
3
9
4
12  
5
12  
5
14  
7
18,000  
24,000  
30,000  
36,000  
3/4  
5/8  
9
13  
1
16  
2
19  
3
22  
4
3/4  
1
5/8  
8
10  
4
13  
5
15  
6
17  
7
3/4  
3
3/4  
10  
4
14  
6
17  
8
21  
10  
20  
8
N/R  
11  
23  
10  
2
7/8  
3/4  
10  
4
13  
6
17  
7
42,000  
7/8  
1-1/8  
3/4  
0
1
1
2
14  
6
18  
7
22  
9
N/R  
11  
2
N/R  
13  
2
48,000  
60,000  
7/8  
1-1/8  
7/8  
0
1
1
9
11  
2
14  
3
16  
3
19  
4
1-1/8  
2
*The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling Capacities data specified in outdoor unit-presale literature for any given  
indoor/outdoor combination.  
Vapor-line diameter that may be selected for a long-line application. If smaller vapor lines are selected but not specified within the table, large capacity losses will occur  
and defrost capabilities will be reduced. If larger vapor lines are selected but not specified within the table, refrigerant oil return will be impaired due to velocity losses.  
N/RNot recommended due to excessive loss of capacity.  
For reference only, the close cell insulation material specified for  
accessory tubing kits is a compound of vinyl, neoprene, or nitrile  
blends of these polymers. Performance requirements include  
thermal range of 0° F to 200°F (-17.8° C to 93° C) and a maximum  
thermal conductivity of 0.28.  
lines and installed system design (indoor coil above or below  
outdoor unit.) The piston or TXV provides such flexibility.  
The piston should be changed for both indoor coil and outdoor heat  
pump unit, depending on system configuration and line length.  
Tables 6 and 7 provide necessary changes for a given application.  
NOTE: Special consideration must be given to isolating intercon-  
necting tubing from building structure. Isolate tubing so that  
vibration or noise is not transmitted into structure.  
Use Tables 6 and 7 when selecting correct piston size. Outdoor-  
unit presale literature must be consulted to determine metering  
devices specified for standard applications. After determining  
standard application piston size(s), refer to Tables 6 and 7 as they  
relate to system design (outdoor unit above or below indoor unit)  
per equivalent length of tubing.  
III. METERING DEVICE SIZING  
The metering device for a long-line application must be flexible  
enough to compensate for frictional losses due to long refrigerant  
6—  
EXAMPLE:  
An 042 size heat pump is 75 ft above an 042 size fan coil.  
The 042 size heat-pump presale literature specifies a size  
80 indoor piston and size 63 outdoor piston.  
To establish correct indoor piston size for a 75 ft vertical  
separation, refer to Table 6. For a 75 ft equivalent line  
length, the piston change is -5. Therefore subtract 5 from  
the original indoor piston size of 80:  
A
80 5 = 75  
Table 8 provides common piston sizes. In this instance, 75  
is not listed, therefore round DOWN to next piston size,  
which would be 74.  
90° STD  
To establish correct outdoor piston size for a 75 ft vertical  
separation, refer to Table 7. For a 75 ft equivalent line  
length, the piston change is +4. Therefore add 4 to the  
original outdoor piston size of 63:  
63 + 4 = 67  
Since 67 is listed in Table 8, that is the piston which should  
be used. If a 67 size piston were not listed, it would be  
necessary to round UP to next piston size.  
B
TXVs may be used instead of pistons for indoor-metering devices.  
Some fan coils are equipped with a hard-shutoff, bi-flow TXV  
standard, and no change is required. When sizing an accessory  
TXV for long-line applications, TXV should be the same nominal  
tonnage as outdoor unit. Refer to presale literature for kit part  
numbers.  
90° LONG RAD  
TABLE 6CALCULATION OF INDOOR PISTON NO.  
OUTDOOR UNIT ABOVE INDOOR  
FT  
PISTON CHANGE  
0-25  
0
-3  
26-50  
51-75  
-5  
76-100  
101-125  
126-150  
-7  
C
-9  
-10  
OUTDOOR UNIT BELOW INDOOR  
FT  
PISTON CHANGE  
0-25  
26-50  
0
A92498  
45° STD  
+4  
Fig. 3Tube Bend Losses  
TABLE 7CALCULATION OF OUTDOOR PISTON NO.  
TABLE 5FITTING LOSSES IN EQUIVALENT FT  
OUTDOOR UNIT ABOVE INDOOR  
REFERENCE DIAGRAM IN FIG. 1  
TUBE SIZE OD  
(IN.)  
FT  
PISTON CHANGE  
A
B
C
0-50  
0
5/8  
3/4  
1.6  
1.8  
2.0  
2.6  
1.0  
1.2  
1.4  
1.7  
0.8  
0.9  
1.0  
1.3  
51-75  
+4  
+6  
+8  
+10  
76-100  
101-125  
126-150  
7/8  
1-1/8  
OUTDOOR UNIT BELOW INDOOR  
FT  
PISTON CHANGE  
0
0-50  
NOTE: If total equivalent horizontal length is 100 ft or longer,  
both indoor and outdoor pistons must be increased 1 full piston  
size, in addition to changes required by Tables 6 and 7.  
IV. LIQUID-LINE SOLENOID AND TUBING CONFIGU-  
RATION  
After finding appropriate change in piston size, add or subtract the  
change from original piston number. If piston size is decreased,  
round new piston number down to nearest common piston number  
found in Table 8. If piston size is increased, round new piston  
number up to nearest common piston number found in Table 8.  
There are 2 types of liquid-line solenoids: 1 for single-flow  
applications and the other for bi-flow applications. The purpose of  
having 2 solenoids is to minimize the valve internal-pressure drop  
in accordance with refrigerant flow direction and liquid migration  
to the compressor. The bi-flow solenoid is designed to have  
minimal refrigerant-pressure drop in either flow direction, which  
makes it suitable for heat pump usage. Refer to Table 9 for  
liquid-line solenoid kit part numbers.  
7—  
TABLE 8COMMON PISTON SIZES  
EXAMPLE:  
To calculate additional charge required for a 25ft line set:  
25 ft 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge  
CHECK-FLO-  
RATER™  
CHECK-FLO-  
RATER™  
CHATLEFF  
CHATLEFF  
32  
33  
35  
36  
37  
38  
39  
40  
41  
42  
43  
45  
65  
67  
65  
67  
68  
70  
71  
73  
74  
76  
78  
80  
81  
82  
84  
86  
88  
89  
90  
92  
93  
96  
98  
101  
104  
The rating-plate charge of a given outdoor unit is for a standard  
application of 15 ft of interconnecting tubing. The rating-plate  
charge can be found on outdoor unit-rating plate or in outdoor  
unit-presale literature. Long-line applications do not require addi-  
tional oil charge.  
35  
70  
38  
73  
VI. 2SPEED APPLICATIONS  
40  
76  
78  
80  
Outdoor units may be connected to indoor section using accessory  
tubing package or field-supplied refrigerant grade tubing of correct  
size and condition. In longline applications, 2speed units are  
handled basically the same way as the single-speed units. There are  
2 major differences:  
42  
82  
84  
86  
88  
46  
1. For tubing up to 100 ft:  
47  
49  
51  
52  
53  
55  
57  
59  
61  
62  
63  
Liquid tube diameters and refrigerant connection diameters  
for all sizes are 3/8 in.  
Vapor tube diameter for the 036 and 048 is 7/8 in.; 060 is  
11/8 in.  
Vapor refrigerant connection diameter for all sizes is 7/8 in.  
DO NOT INSTALL EQUIVALENT INTERCONNECT-  
ING TUBING LENGTHS GREATER THAN 100 FT.  
49  
51  
52  
90  
55  
57  
59  
61  
93  
96  
98  
101  
104  
109  
2. Do not increase or decrease tubing sizes.  
For other applications see the previous sections under Long-Line  
Guidelines.  
63  
UNIT IDENTIFICATION  
I. PRODUCT NUMBER STAMPED ON UNIT-RATING  
PLATE  
NOTE: When installing a liquid-line solenoid, the system may  
require a minimum 60va low-voltage transformer.  
The unit product number has 16 positions containing groups of  
numbers and letters that indicate specific information about the  
unit. Listed below is the breakdown of the 16 positions.  
Positions 1, 2, and 3Product Series  
Example:  
A 500series number indicates a split-system condensing unit and  
a 600series number indicates a split-system heat pump.  
Position 4Model Letters  
Each type of solenoid has an indicator flow arrow stamped on the  
valve body. When solenoid is closed (not energized) and pressure  
is applied in direction of flow arrow, complete shutoff occurs. If  
pressure is applied against direction of flow arrow, leakage  
through valve occurs. When determining proper installation of  
valve within liquid line, 2 considerations must be made:  
1. Direction of flow arrow  
New models are introduced with the letter A, and subsequent  
model changes are identified by changing to the next letter, as B,  
then C, and so forth.  
Position 5Electrical Characteristics  
Example:  
2. Where solenoid is installed in system.  
TXVs can only be substituted for liquid-line solenoids in single-  
flow air conditioning systems. Bi-flow TXVs allow liquid migra-  
tion to coldest point during off cycles, which could allow liquid  
into compressor.  
J208230, 1 Phase, 60 Hertz  
Fig. 4 through 7 detail proper installation of liquid-line solenoid  
and provide applications where TXVs may be substituted. Refer-  
ence all notes of the appropriate figures.  
N208/230, 208/240, 1 Phase, 60 Hertz  
P208/230, 208/240, 3 Phase, 60 Hertz  
E460, 3 Phase, 60 Hertz  
Q220, 3 Phase, 50 Hertz  
S220/240, 1 Phase, 50 Hertz  
TABLE 9LIQUID-LINE SOLENOID KIT PART NUMBERS  
Z380/415, 3 Phase, 50 Hertz  
Position 6Fuel and Controls  
Not applicable on condensing units or heat pumps, so the letter X’  
is used to signify none.’  
TYPE OF VALVE  
Single Flow  
Bi-Flow  
PART NO.  
KAALS0101LLS  
KHALS0401LLS  
Positions 7, 8, and 9Nominal Cooling Capacity (in thousands  
Btuh)  
V. CHARGING INFORMATION  
Weigh in appropriate refrigerant charge, then use the standard  
practices of superheat-charging method for piston applications and  
subcooling-charging method for TXV applications to confirm  
correct charge. The standard charging methods can be found on  
outdoor unit-information plate, in unit Installation Instructions, or  
in the Service Manual. Since total system charge is increased for  
long-line applications, it may be necessary to calculate the  
additional refrigerant charge. Since long-line applications only  
involve 3/8-in. liquid lines, the additional refrigerant charge  
required is 0.6 oz of Refrigerant 22 (R-22) per ft of 3/8-in. liquid  
line over 15 ft.  
Example: 036 = 36,000 Btuh or 3ton capacity.  
Positions 10, 11, and 12Not applicable on condensing units or  
heat pumps, so the number zerois used to signify none.’  
Position 13Brand Name  
Example:  
ACommon unit U.S.A. Only  
Position 14Unit Series  
New units are introduced with the letter A, and subsequent major  
component variations, such as in compressor, fan motor, coil  
circuitor size, etc., are identified by changing to the next letter, as  
B, then C, and so forth.  
8—  
Positions 15 and 16Product Variations  
Example:  
AAStandard unit  
52Last week of a year  
Positions 3 and 4Year of Manufacture  
Example:  
Other lettersFor product variations from standard  
941994  
Position 5Manufacturing Site  
Example:  
AIndianapolis  
ECollierville  
Positions 6 through 10Serial Number  
II. SERIAL NUMBER IDENTIFICATION  
The unit serial number has 10 positions containing groups of  
numbers and a letter that indicate specific information about the  
unit. Listed below is the breakdown of the 10 positions.  
Positions 1 and 2Week of Manufacture  
Example:  
01First week of a year  
175' MAX.  
GROUND LEVEL  
BASEMENT  
A90074  
Fig. 4Application with Air Conditioner Installed in a Horizontal Configuration  
175' MAX.  
GROUND LEVEL  
BASEMENT  
A90075  
Fig. 5Application with Heat Pump Installed in a Horizontal Configuration  
9—  
TRAP  
50' MAX.  
HEAT PUMP ONLY  
GROUND LEVEL  
A90076  
Fig. 6Application with Air Conditioner or Heat Pump Installed with Indoor Unit Above Outdoor Unit  
CABINET  
III. INFORMATION PLATERELIANT PRODUCTS  
Certain maintenance routines and repairs require removal of  
cabinet panels. There are 4 basic cabinet designs for air condition-  
ers and heat pumps. (See Fig. 8.) The horizontal discharge unit will  
be discussed in a separate section of this manual. Note that  
separate sections apply according to date of manufacture.  
The information plate is secured to the front of the control box and  
provides a cover for it. (See Fig. 9.) This plate also provides a  
surface to attach the wiring schematic, superheat-charging tables  
with instructions, and warning labels. The plate has 2 tabs on the  
top edge that are bent down at slightly more than 90°. When the  
information plate is removed, these tabs can be inserted into 2  
mating slots in the bottom-front edge of the control box, and the  
plate will hang down, forming a lower front panel. (See Fig. 10.)  
This is convenient where access to the controls is required while  
the unit is operating. The information plate on the small size casing  
completely covers the opening below the control box. On larger  
models, the information plate may not cover the entire opening. In  
this instance, the top cover can be removed and placed on its side  
to cover the additional space.  
I. REMOVE TOP COVERBEFORE 1/1/92  
NOTE: This section applies to all Reliant products made prior to  
January 1, 1992.  
1. Turn off all power to outdoor and indoor units.  
2. Remove screws holding top cover to coil grille and corner  
posts.  
3. Remove access panel.  
IV. CONTROL-BOX COVERCUBE PRODUCTS  
4. Remove information plate.  
This panel contains much of the same information as the informa-  
tion plate mentioned previously, but is designed only to cover the  
control box.  
5. Disconnect fan motor wires, cut wire ties, and remove wire  
ties from control box. Refer to unit-wiring label.  
6. Lift top cover from unit.  
V. REMOVE TOP COVERAFTER 1/1/92  
7. Reverse sequence for reassembly.  
NOTE: The section applies to all Reliant Products made after  
II. REMOVE FAN-MOTOR ASSEMBLYBEFORE 1/1/92  
January 1, 1992.  
NOTE: This section applies to all Reliant products made prior to  
1. Turn off all power to outdoor and indoor units.  
January 1, 1992.  
2. Remove 5 screws holding top cover to coil grille and coil  
tube sheet.  
1. Perform items 1 through 6 above.  
3. Remove 2 screws holding control-box cover.  
4. Remove 2 screws holding information plate.  
2. Remove nuts holding fan-motor top cover.  
3. Remove motor and fan blade assembly.  
4. Reverse sequence for reassembly.  
5. Disconnect fan motor wires, cut any wire ties, and move  
wires out of control box and through tube clamp on back of  
control box.  
5. Prior to applying power, check that fan rotates freely.  
10—  
HEAT PUMP ONLY  
150' MAX.  
A90077  
Fig. 7Application with Air Conditioner or Heat Pump Installed Above Indoor Unit  
6. Lift top cover from unit.  
7. Reverse sequence for reassembly.  
VI. REMOVE FAN-MOTOR ASSEMBLYAFTER 1/1/92  
NOTE: This section applies to all Reliant products made after  
January 1, 1992  
1. Perform items 1, 3, 4, and 5 above. (Note item 2 is not  
required.)  
2. Remove 4 screws holding wire basket to top cover.  
3. Lift wire basket from unit.  
4. Remove nuts holding fan motor to wire basket.  
5. Remove motor and fan blade assembly.  
6. Pull wires through wire raceway to change motor.  
7. Reverse sequence for reassembly.  
8. Prior to applying power, check that fan rotates freely.  
11—  
A94003  
Fig. 8Basic Cabinet Designs  
ELECTRICAL  
I. ALUMINUM WIRE  
CAUTION: Aluminum wire may be used in the branch  
WARNING: Exercise extreme caution when working on  
any electrical components. Shut off all power to system  
prior to troubleshooting. Some troubleshooting tech-  
niques require power to remain on. In these instances,  
exercise extreme caution to avoid danger of electrical  
shock. ONLY TRAINED SERVICE PERSONNEL  
SHOULD PERFORM ELECTRICAL TROUBLE-  
SHOOTING.  
circuit (such as the circuit between the main and unit  
disconnect), but only copper wire may be used between  
the unit disconnect and the unit on Bryant systems.  
Whenever aluminum wire is used in the branch-circuit wiring with  
this unit, adhere to the following recommendations.  
Connections must be made in accordance with the National  
Electrical Code (NEC), using connectors approved for aluminum  
wire. The connectors must be UL-approved (marked Al/Cu with  
the UL symbol) for the application and wire size. The wire size  
selected must have a current capacity not less than that of the  
copper wire specified and must not create a voltage drop between  
the service panel and the unit in excess of 2 percent of the  
unit-rated voltage.  
Troubleshooting charts for air conditioning and heat pump units  
are provided in the back of this manual. They enable the service  
technician to use a systematic approach to locate the cause of a  
problem and correct system malfunctions.  
To prepare the wire before installing the connector, all aluminum  
wire must be brush scratchedand coated with a corrosion  
inhibiter such as Pentrox A. When it is suspected that the  
12—  
II. CONTACTORS  
NOTE: The section applies to single-speed models only.  
The contactor provides a means of applying power to unit using  
low voltage (24v) from transformer in order to power the contactor  
coil. (See Fig. 11.) Depending on unit model, you may encounter  
single-, double-, or triple-pole contactors to break power. One side  
of the line may be electrically energized, so exercise extreme  
caution when troubleshooting.  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ PAASFLDLKREW  
SEFL JOSDJ ATC  
SEFL JOSDJ UTUHD  
SEFL JOSDJC MD  
SEFL JOSDJHR ITYALK  
SEFL JOSDJ  
The contactor coil for residential air-conditioning units and heat  
pumps is powered by 24vac. If contactor does not operate:  
1. With power off, check whether contacts are free to move.  
Check for severe burning or arcing on contact points.  
2. With power off, use ohmmeter to check for continuity of  
coil. Disconnect leads before checking. A low-resistance  
reading is normal. Do not look for a specific value, as  
different part numbers have different resistance values.  
3. Reconnect leads and apply low-voltage power to contactor  
coil. This may be done by leaving high-voltage power to  
outdoor unit off, and turning thermostat to heat or cool.  
Check voltage at coil with voltmeter. Reading should be  
between 20v and 30v. Contactor should pull in if voltage is  
correct and coil is good. If contactor does not pull in,  
change contactor.  
A88411  
Fig. 9Information Plate  
connection will be exposed to moisture, it is very important to  
cover the entire connection completely to prevent an electrochemi-  
cal action that will cause the connection to fail very quickly. Do  
not reduce the effective size of wire, such as cutting off strands so  
that the wire will fit a connector. Proper size connectors should be  
used. Check all factory and field electrical connections for  
tightness. This should also be done after the unit has reached  
operating temperatures, especially if aluminum conductors are  
used.  
4. With high-voltage power off and contacts pulled in, check  
for continuity across contacts with ohmmeter. A very low or  
zero resistance should be read. Higher readings could  
indicate burned or pitted contacts which may cause future  
failures.  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ PAASFLDLKREW  
SEFL JOSDJ ATC  
SEFL JOSDJ UTUHD  
SEFL JOSDJC MD  
SEFL JOSDJHR ITYALK  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ  
SEFL JOSDJ PAASFLDLKREW  
SEFL JOSDJ ATC  
SEFL JOSDJ UTUHD  
SEFL JOSDJC MD  
SEFL JOSDJ  
SEFL JOSDJHR ITYALK  
SEFL JOSDJ  
A88412  
A88413  
Fig. 10Information Plate Removed/Installed Below Control Box  
13—  
A91455  
Fig. 12Capacitors  
A88350  
Use the following formula to calculate capacitance:  
Capacitance (mfd) = (2650 X amps) divided by (volts)  
Fig. 11Contactor  
III. CAPACITORS  
3. Remove any capacitor that shows signs of bulging, dents, or  
leaking. Do not apply power to a defective capacitor as it  
may explode.  
CAUTION: Capacitors can store electrical energy when  
power is off. Electrical shock can result if you touch the  
capacitor terminals and discharge the stored energy.  
Exercise extreme caution when working near capacitors.  
With power off, discharge stored energy by shorting  
across the capacitor terminals with a 15,000-ohm, 2-watt  
resistor.  
START CAPACITORS AND PTC DEVICES  
Sometimes under adverse conditions, a standard run capacitor in a  
system is inadequate to start compressor. In these instances, a  
start-assist device is used to provide an extra starting boost to  
compressor motor. The first device is called a positive-temperature  
coefficient (PTC) or thermistor. (See Fig. 13.) It is a resistor wired  
in parallel with the run capacitor. As current flows through the  
PTC at start-up, it heats up. As it heats up, its resistance increases  
greatly until it effectively lowers the current through it to an  
extremely low value. This, in effect, removes it from the circuit.  
NOTE: If bleed resistor is wired across start capacitor, it must be  
disconnected to avoid erroneous readings when ohmmeter is  
applied across capacitor. (See Fig. 12.)  
CAUTION: Always check capacitors with power off.  
Attempting to troubleshoot a capacitor with power on can  
be dangerous. Defective capacitors may explode when  
power is applied. Insulating fluid inside is combustible  
and may ignite, causing burns.  
12.5-22.5  
OHMS  
12.5 OHM  
(BEIGE COLOR)  
Capacitors are used as a phase-shifting device to aid in starting  
certain single-phase motors. Check capacitors as follows.  
25-45  
OHMS  
20-36  
OHMS  
1. After power is off, discharge capacitors as outlined above.  
Disconnect capacitor from circuit. Put ohmmeter on R X  
10k scale. Using ohmmeter, check each terminal to ground  
(use capacitor case). Discard any capacitor which measures  
1/2scale deflection or less. Place ohmmeter leads across  
capacitor and place on R X 10k scale. Meter should jump to  
a low-resistance value and slowly climb to higher value.  
Failure of meter to do this indicates an open capacitor. If  
resistance stays at zero or a low value, capacitor is inter-  
nally shorted.  
BLUE  
20 OHM  
(BLUE COLOR)  
25 OHM  
(BLUE COLOR)  
A88414  
Fig. 13PTC Devices  
After system shutdown, resistor cools and resistance value returns  
to normal until next time system starts. If indoor coil does not have  
a bleed-type expansion device, it may be necessary to remove start  
thermistor and replace with accessory start capacitor and relay.  
Consult pre-sale literature for application of start kits. Thermistor  
device is adequate for most conditions; however, in systems where  
off-cycle is short, device cannot cool fully and becomes less  
effective as a start device. It is an easy device to troubleshoot.  
2. Capacitance testers are available which read value of  
capacitor. If value is not within ± 10 percent value stated on  
capacitor, it should be changed. If capacitor is not open or  
shorted, the capacitance value is calculated by measuring  
voltage across capacitor and current it draws.  
WARNING: Exercise extreme caution when taking  
readings while power is on. Electrical shock can cause  
personal injury or death.  
1. Shut off all power to system.  
2. Check thermistor with ohmmeter as described below.  
3. Shut off all power to unit.  
14—  
4. Remove PTC from unit. Wait at least 10 minutes for PTC to  
cool to ambient temperature.  
CAUTION: Do not check winding at compressor termi-  
nals with pressure in the system. Check resistance by  
removing wires attached at the compressor contactor and  
run capacitor.  
5. Measure resistance of PTC with ohmmeter as shown in  
Fig.13.  
The cold resistance (RT) of any PTC device should be approxi-  
mately 100 180 percent of device ohm rating.  
12.5ohm PTC = 12.522.5 ohm resistance beige color  
25ohm PTC = 2545 ohm resistance blue color  
20ohm PTC = 2036 ohm resistance blue color  
3. Obtain  
a
start capacitor in the range of  
150180µF[@0330] volts rating. Connect 8gauge wires  
with insulated clips or terminals to the H and C terminals of  
the run capacitor.  
If PTC resistance is appreciably less than rating or more than 200  
percent higher than rating, device is defective.  
4. Turn power on to unit. If compressor starts, immediately  
remove start-capacitor wires from H and C terminals of run  
capacitor, using a pair of insulated, needle-nose pliers. DO  
NOT leave start capacitor attached to run capacitor for more  
than 3 seconds, even if compressor doesnt start.  
If thermistor is good and compressor does not start:  
1. Disconnect thermistor from starting circuit.  
2. Give compressor a temporary capacitance boost (see next  
section).  
5. Discharge start capacitor by using a pair of insulated,  
needle-nose pliers and shorting a 15,000 ohm, 2 watt  
resistor across terminals.  
3. Run compressor for 10 minutes, shut off, and allow system  
pressure to equalize.  
4. Reconnect start thermistor.  
NOTE: Some start capacitors already have a bleed resistor  
attached. If so, it will discharge itself over a short period of time.  
5. Try restarting compressor without boost capacitor. If after 2  
attempts compressor does not start, remove thermistor. Add  
an accessory start-capacitor relay package.  
6. Run compressor 10 minutes. Stop and allow unit to sit idle  
for 5 minutes.  
TEMPORARY CAPACITANCE BOOST  
7. Check system pressure equalization.  
WARNING: Do not under any circumstances attach a  
temporary boost capacitor directly to the compressor  
terminals. Serious personal injury can result. Exercise  
extreme caution with this procedure when high-voltage  
power is on.  
8. Attempt to restart without capacitance boost.  
If PTC thermistor device is inadequate as start device, a start  
capacitor and relay may be added to system to ensure positive start.  
Capacitor is wired in parallel with run capacitor through normally  
closed set of contacts on a device called start relay. The relay coil  
is wired across start and common terminals of compressor. The  
added capacitance gets the compressor started. As compressor  
comes up to speed, voltage across start and common terminals  
increases to a value high enough to cause start relay to energize.  
This opens normally closed contacts and removes start capacitor  
from circuit. In actual practice, this occurs in a fraction of a  
second.  
There are times when a temporary capacitance boost is needed to  
get compressor started. (See Fig. 14.) If compressor motor does not  
start, it may be due to low-line voltage, improper pressure  
equalization, weak run capacitor, or a seized compressor. Check  
each possibility and attempt capacitance boost before adding  
auxiliary start capacitor and relay.  
NOTE: If bleed resistor is wired across start capacitor, it must be  
disconnected to avoid erroneous readings when ohmmeter is  
applied across capacitor.  
220-V FROM UNIT  
CONTACTOR  
To check start relay and capacitor:  
1. Turn off all power to unit.  
2. Discharge start and run capacitors as outlined earlier.  
COMP. RUN  
CAPACITOR  
3. Most start capacitors will have a 15,000 ohm, 2 watt bleed  
resistor. Disconnect these devices from system.  
Start capacitor can be inspected visually. It is designed for short  
duration or intermittent duty. If left in circuit for prolonged period,  
start capacitor blows through a specially designed bleed hole. If it  
appears blown, check for welded contacts in start relay. Start  
capacitor can be checked by ohmmeter method discussed earlier.  
START (BOOST)  
CAPACITOR  
Start relay is checked with ohmmeter. Check for continuity across  
coil of relay. You should encounter a high resistance. Since relay  
contacts are normally closed, you should read low resistance  
across them. Both PTC device and capacitor-relay start system are  
standard equipment on some of these units. They are also available  
as accessories and may be field-installed.  
A88349  
Fig. 14Capacitance Boosting  
1. Turn off all power to unit. There may be more than one  
power source to condensing unit.  
NOTE: If a PTC is already installed, remove it from the system  
IV. CYCLE PROTECTOR  
Solid-state cycle-protector device protects unit compressor by  
preventing short cycling. After a system shutdown, cycle protector  
provides for a 5 ± 2-minute delay before compressor restarts. On  
normal start-up, a 5-minute delay occurs before thermostat closes.  
After thermostat closes, cycle protector device provides a 3-sec  
delay on HN67PA025, HN67ZA003, and HN67ZA008. (See Fig.  
15, 16, and 17.)  
by pulling PTC wires from H and C terminals on run capacitor.  
2. Check compressor for ground or open windings. If wind-  
ings resistance is within manufacturers recommendations,  
proceed. (See Reciprocating Compressor Section II-  
Electrical Failures for proper compressor-winding check.)  
15—  
T2  
T1  
T3  
T3  
T1  
T2  
HN67ZA002  
A91438  
HN67ZA008  
A94005  
T3 BLK  
T3 BLK  
T1 YEL T2 VIO  
T2  
T1  
T3  
HN67PA025  
HN67ZA003  
A91439  
A91440  
Fig. 15Cycle-Protector Device  
Cycle-protector device is simple to troubleshoot. Only a voltmeter  
capable of reading 24v is needed. Device is in control circuit;  
therefore, troubleshooting is safe with control power (24v) on and  
high-voltage power off.  
no circuit through the crankcase heater because both leads are  
connected to the same side of the line. This allows the heater to  
operate when the system is not calling for heating/cooling. The  
heater does not operate when the system is calling for  
heating/cooling. On units with 2 or 3 pole contactors, the crank-  
case heater is connected to the line side of the contactor and is not  
controlled by the contactor contacts.  
The crankcase heater is powered by high-voltage power of unit.  
Use extreme caution troubleshooting this device with power on.  
The easiest method of troubleshooting is to apply voltmeter across  
crankcase heater leads to see if heater has power. Do not touch  
heater. Carefully feel area around crankcase heater. If warm,  
crankcase heater is probably functioning. Do not rely on this  
method as absolute evidence heater is functioning. If compressor  
has been running, the area will still be warm.  
With power off and heater leads disconnected, check across leads  
with ohmmeter. Do not look for a specific resistance reading.  
Check for resistance or an open circuit. Change heater if an open  
circuit is detected. Some crankcase heaters in this series of units  
are equipped with a crankcase-heater switch. This energy-saving  
device shuts off power to heater when temperatures are high  
enough that heater is not needed. Be sure this switch is functioning  
normally before condemning crankcase heater.  
With high-voltage power off, attach voltmeter leads across T1 and  
T3 and set thermostat so that Y terminal is energized. Make sure  
all protective devices in series with Y terminal are closed.  
Voltmeter should read 24v across T1 and T3. With 24v still  
applied, move voltmeter lead from T1 terminal to T2 terminal  
across T2 and T3. After 5 ± 2 minutes, voltmeter should read 24v,  
indicating control is functioning normally. If no time delay is  
encountered or device never times out, change control.  
V. CRANKCASE HEATER  
Crankcase heater is a device for keeping compressor oil warm. By  
keeping oil warm, refrigerant does not migrate to and condense in  
compressor shell when the compressor is off. This prevents  
flooded starts which can damage compressor.  
Crankcase heaters come in 2 basic types: wraparound-(bellyband)  
type that is wrapped externally around compressor shell, and  
insertion-type that is inserted into compressor oil well in shell of  
compressor. Both types are used in outdoor units.  
On units that have a single-pole contactor, the crankcase heater is  
wired parallel with the contactor contacts and in series with the  
compressor. (See Fig. 18.) When the contacts are open, a circuit is  
completed from the line side of the contactor, through the  
crankcase heater, through the run windings of the compressor, and  
to the other side of the line. When the contacts are closed, there is  
VI. TIME-DELAY RELAY  
The time-delay relay (TDR) is a solid-state-controlled, recycle-  
delay timer which keeps the indoor blower operating for 90 sec  
after thermostat is satisfied. This delay enables the blower to  
remove residual cooling in the coil after compression shutdown,  
16—  
OPERATING  
TIME  
OPERATING  
TIME  
3
SEC  
5 MIN  
5 MIN  
T1  
_
T1  
_
T2  
T2  
BLK DENOTES CLOSED CONTACTS  
HN67ZA002  
BLK DENOTES CLOSED CONTACTS  
HN67PA025, HN67ZA003, HN67ZA008  
A91436  
A91437  
Fig. 16Cycle-Protector Sequence  
CUT YELLOW WIRE  
BETWEEN CONTACTOR AND  
LOW-PRESSURE SWITCH  
SAFETY  
CONTROL  
Y
YEL  
YEL  
YEL  
C
BRN  
C
YEL  
T1  
TERMINAL  
BOARD  
CONNECTION  
TERMINAL  
BOARD  
CONNECTION  
VIO  
LOGIC  
T3  
T2  
BLK  
A88415  
Fig. 17Cycle-Protector Wiring  
TDR is reset, and the fan relay remains energized. The TDR is a  
24v device that operates within a range of 15 to 30v and draws  
about 0.5 amps.  
DSV  
CH  
If the blower runs continuously instead of cycling off when the fan  
switch is set on AUTO, the TDR is probably defective and must be  
replaced.  
VII. PRESSURE SWITCHES  
Pressure switches are protective devices wired into control circuit  
(low voltage). They shut off compressor if abnormally high or low  
pressures are present in the refrigeration circuit. Depending on unit  
model, you may find a low- and/or high-pressure switch in system.  
11  
21  
LOW-PRESSURE SWITCH  
Located on suction line of condensing unit only, the low-pressure  
switch protects against low-suction pressures caused by such  
events as loss of charge, low airflow across indoor coil, dirty  
filters, etc. It opens on a pressure drop at about 27 psi. If system  
pressure is above this, switch should be closed. To check switch,  
turn off all power to unit, disconnect leads on switch, and apply  
ohmmeter leads across switch. You should have continuity on a  
good switch. Because these switches are attached to refrigeration  
system under pressure, it is not advisable to remove this device for  
troubleshooting unless you are reasonably certain that a problem  
exists. If switch must be removed, remove and recover all system  
charge so that pressure gages read 0 psi.  
A91426  
Fig. 18Wiring for Single-Pole Contactor  
thereby improving the efficiency of the system. The sequence of  
operation is that on closure of the wall thermostat and at the end of  
a fixed on-delay of 1 sec, the fan relay is energized. When the  
thermostat is satisfied, an off-delay is initiated. When the fixed  
delay of 90 ± 20 sec is completed, the fan relay is de-energized and  
fan motor stops. If the wall thermostat closes during this delay, the  
17—  
2. Remove control-box cover for access to electrical compo-  
nents and defrost-control board.  
CAUTION: Wear safety glasses and gloves when work-  
ing with refrigerants.  
3. Disconnect defrost-thermostat leads from control board and  
connect to ohmmeter. Thermostat leads are the black,  
insulated wires connected to DFT and R terminals on  
control board. Resistance reading may be zero (indicating  
closed defrost thermostat) or infinity (for open thermo-  
stat) depending on outdoor temperature.  
Apply heat with torch to solder joint and remove switch. Wear  
safety glasses when using torch. Have quenching cloth available.  
Oil vapor in line may ignite when switch is removed. Braze in  
1/4-in. flare fitting and screw on replacement pressure switch.  
HIGH-PRESSURE SWITCH  
4. Jumper between DFT and R terminals on control board as  
shown in Fig. 19.  
Located on discharge line, the high-pressure switch protects  
against high-discharge pressures caused by such events as over-  
charge, condenser-fan motor failure, system restriction, etc. It  
opens on pressure rise at about 435 psi. If system pressures go  
above this setting during abnormal conditions, the switch opens.  
Do not attempt to simulate these system abnormalities as high  
pressures pose a serious safety hazard. High-pressure switch is also  
checked with an ohmmeter similar to checking low-pressure  
switch. If system pressure is below 435 psi, the switch shows  
continuity. It is replaced in the same manner as low-pressure  
switch. Observe all safety precautions.  
5. Disconnect outdoor fan motor lead from OF2. Tape lead to  
prevent grounding.  
6. Turn on power to outdoor unit.  
7. Restart unit in heating, allowing frost to accumulate on  
outdoor coil.  
8. After a few minutes in heating, liquid-line temperature at  
defrost thermostat should drop below closing set point of  
defrost thermostat of approximately 30°F. Using ohmmeter,  
check resistance across defrost-thermostat leads. Resistance  
of zero indicates defrost thermostat is closed and operating  
properly.  
LIQUID-LINE PRESSURE SWITCH  
Located on liquid line of heat pump only, the liquid-line pressure  
switch functions similar to conventional low-pressure switch.  
Because heat pumps experience very low suction pressures during  
normal system operation, a conventional low-pressure switch  
cannot be installed on suction line. This switch is installed in liquid  
line instead and acts as loss-of-charge protector. The liquid line is  
the low side of the system in heating mode. It operates identically  
to low-pressure switch except it opens at 7 psi when the heating  
piston is in the liquid valve or 27 psi when the heating piston is in  
the liquid line. Troubleshooting and removing this switch is  
identical to procedures used on other switches. Observe same  
safety precautions.  
9. Remove protective cover from TP1 and TP2 speed-up  
terminals. Install jumper wire on speed-up terminals. This  
reduces the timing sequence to 1/60 of original time. (See  
Fig. 20.) Since Fig. 20 shows timing cycle set at 30 minutes,  
unit initiates defrost within approximately 30 sec; if setting  
is at 50 minutes, within 50 sec; 90 minutes, within 90 sec.  
When you hear the reversing valve change position, remove  
protective cover/jumper. Otherwise, control will terminate  
normal 10-minute defrost cycle in approximately 10 sec.  
CAUTION: Exercise extreme caution when shorting  
speed-up pins. If pins are accidentally grounded, damage  
to the control board will occur.  
VIII. DEFROST THERMOSTATS  
Defrost thermostat signals heat pump that conditions are right for  
defrost or that conditions have changed to terminate defrost. It is  
a thermally actuated switch clamped to outdoor coil to sense its  
temperature. Normal temperature range is closed at 30° ± 3°F and  
open at 80° ± 5°F.  
10. Unit is now operating in defrost mode. Using voltmeter,  
check between C and W2 as shown in Fig. 21. Reading on  
voltmeter should indicate 24v. This step ensures defrost  
relay contacts have closed, energizing supplemental heat  
(W2) and reversing valve solenoid (O).  
NOTE: The defrost thermostat must be located on the liquid side  
of the outdoor coil on the bottom circuit and as close to the coil as  
possible.  
IX. DEFROST-CONTROL BOARD  
11. Unit should remain in defrost no longer than 10 minutes.  
Actual time in defrost depends on how quickly speed-up  
jumper is removed. If it takes 3 sec to remove speed-up  
jumper after unit has switched to defrost, only 7 minutes of  
defrost cycle remains.  
Solid-state defrost boards used on heat pumps replace electrome-  
chanical timer and defrost relay found on older defrost systems.  
The defrost-control board can be field-set to check need for defrost  
every 30, 50, or 90 minutes of operating time by connecting the  
jumper (labeled W1 on the circuit board) to the terminal for the  
defrost time desired. The board is set at factory for 90 minutes. The  
defrost period is field-selectable, depending upon geographic areas  
and defrost demands. Two types of defrost boards are used, and  
functions are described in the sections to follow.  
12. After a few minutes in defrost (cooling) operation, liquid  
line should be warm enough to have caused defrost-  
thermostat contacts to open. Check resistance across defrost  
thermostat. Ohmmeter should read infinite resistance, indi-  
cating defrost thermostat has opened at approximately 80°F.  
Troubleshooting defrost control involves a series of simple steps  
that indicate whether or not board is defective.  
13. Shut off unit power and reconnect fan lead.  
NOTE: This procedure allows the service technician to check  
control board and defrost thermostat for defects. First troubleshoot  
to make sure unit operates properly in heating and cooling modes.  
This ensures operational problems are not attributed to the defrost-  
control board.  
14. Remove jumper wire from speed-up terminal and reinsert  
cover on speed-up terminals. Failure to remove jumper  
causes unit to speed up operating cycles continuously.  
15. Remove jumper between DFT and R terminals. Reconnect  
defrost thermostat leads.  
HK32FA003, 006 DEFROST CONTROL  
16. Replace control-box cover. Restore power to unit.  
This control board utilizes screw terminals for the low-voltage  
field wiring. The board has a feature that allows the heat pump to  
restart in defrost if room thermostat is satisfied during defrost. To  
troubleshoot the board, perform the following items.  
If defrost thermostat does not check out following above items or  
incorrect calibration is suspected, check for a defective thermostat  
as follows.  
1. Turn thermostat to OFF. Shut off all power to outdoor unit.  
1. Follow items 1-5 above.  
18—  
OF1  
OF2  
OF2  
G
E
OF1  
W2  
L
14  
C
C
G
R
W3  
R
O
R
T2  
Y
TI DFT  
C
TEST 30 50 90  
W1  
Y
R
Y
C
C
O
C
O
R
O
DFT  
W2  
Y
50  
30  
C
W1  
CES0110063,  
CES0130024  
A91442  
HK32FA003/HK32FA006  
A88402  
Fig. 19Jumper DFT and R Terminals  
2. Using thermocouple temperature-measuring device, route  
sensor or probe underneath coil (or other convenient loca-  
tion). Attach to liquid line near defrost thermostat. Insulate  
for more accurate reading.  
4. Jumper between DFT and R terminals on control board as  
shown in Fig. 21.  
5. Disconnect outdoor fan-motor lead from OF2. Tape lead to  
prevent grounding.  
6. Turn on power to outdoor unit.  
7. Restart unit in heating mode, allowing frost to accumulate  
on outdoor coil.  
3. Turn on power to outdoor unit.  
4. Restart unit in heating mode.  
5. Within a few minutes, liquid-line temperature drops within  
a range causing defrost thermostat contacts to close. Tem-  
perature range is from 33°F to 27°F. Notice temperature at  
which ohmmeter reading goes from to zero ohms.  
Thermostat contacts close at this point.  
8. After a few minutes in heating mode, liquid-line tempera-  
ture at defrost thermostat should drop below closing set  
point of defrost thermostat of approximately 30°F. Check  
resistance across defrost thermostat leads using ohmmeter.  
Resistance of zero indicates defrost thermostat is closed and  
operating properly.  
9. Short between the speed-up terminals using a thermostat  
screwdriver. This reduces the timing sequence to 1/256 of  
original time. (See Fig. 20 and Table 10.)  
6. Remove protective cover from TP1 and TP2 speed-up  
terminals, and install jumper wire on the speed-up termi-  
nals.  
7. Unit changes over to defrost within 90 sec (depending on  
timing cycle setting). Liquid-line temperature rises to range  
where defrost thermostat contacts open. Temperature range  
is from 75°F to 85°F. Resistance goes from zero to when  
contacts open.  
NOTE: Fig. 20 shows timing cycle set at 30 minutes; however,  
for the CES30110063 board the timing cycle will be set for 90 min  
and unit initiates defrost within approximately 21 sec. When you  
hear the reversing valve change position, remove screwdriver  
immediately. Otherwise, control will terminate normal 10-minute  
defrost cycle in approximately 2 sec.  
8. If either opening or closing temperature does not fall within  
above ranges or thermostat sticks in 1 position, replace  
thermostat to ensure proper defrost operation.  
CAUTION: Exercise extreme caution when shorting  
speed-up pins. If pins are accidentally shorted to other  
terminals, damage to the control board will occur.  
CES0110063 DEFROST CONTROL  
Some heat pumps built in 1991 and later incorporate a new defrost  
control. The screw terminals found on the previous control board  
have been replaced by a connector plug with stripped-wire leads.  
This control board also contains the feature that allows the heat  
pump to restart in defrost if the room thermostat is satisfied during  
defrost. The board also contains a 5-minute cycle protector that  
prevents the unit from short cycling after it cycles off or after a  
power interruption. To troubleshoot the board, perform the follow-  
ing items.  
10. Unit is now operating in defrost mode. Check between C  
and W2 using voltmeter as shown in Fig. 21. Reading on  
voltmeter should indicate 24v. This step ensures defrost-  
relay contacts have closed, energizing supplemental heat  
(W2) and reversing valve solenoid (O).  
11. Unit should remain in defrost no longer than 10 minutes.  
Actual time in defrost depends on how quickly speed-up  
jumper is removed. If it takes 2 sec. to remove speed-up  
jumper after unit has switched to defrost, the unit will  
switch back to heat mode.  
12. After a few minutes in defrost (cooling) operation, liquid  
line should be warm enough to have caused defrost-  
thermostat contacts to open. Check resistance across defrost  
thermostat. Ohmmeter should read infinite resistance, indi-  
cating defrost thermostat has opened at approximately 80°F.  
1. Turn thermostat to OFF. Shut off all power to outdoor unit.  
2. Remove control-box cover for access to electrical compo-  
nents and defrost-control board.  
3. Disconnect defrost-thermostat leads from control board,  
and connect to ohmmeter. Thermostat leads are the black,  
insulated wires connected to DFT and R terminals on  
control board. Resistance reading may be zero (indicating  
closed-defrost thermostat), or infinity (for open thermo-  
stat) depending on outdoor temperature.  
19—  
OF1 OF2  
OF2  
G
OF1  
E
W2  
L
14  
G
R
C
C
W3  
R
Y
R
Y
C
C
O
R
T2  
Y
TI DFT  
C
TEST 30 50 90  
W1  
O
C
DFT  
O
O
R
50 90  
W2  
Y
W1  
C
HK32FA003/HK32FA006  
CES0110063,  
CES0130024  
A88404  
A91444  
Fig. 20Inserting Jumper Wire  
OF2 OF1  
G
OF2  
OF1  
E
W2  
14  
L
W3  
G
R
C
C
R
Y
R
Y
C
C
O
O
R
T2  
Y
TI DFT  
C
TEST 30 50 90  
W1  
C
DFT  
O
30  
50  
W1  
O
R
HK32FA003/HK32FA006  
W2  
Y
A88403  
C
CES0110063,  
CES0130024  
A91443  
Fig. 21Checking Between C and W2  
13. Shut off unit power and reconnect fan lead.  
TABLE 10DEFROST CONTROL SPEED-UP TIMING SE-  
14. Remove jumper between DFT and R terminals. Reconnect  
defrost-thermostat leads. Failure to remove jumper causes  
unit to switch to defrost every 30, 50, or 90 minutes and  
remain in defrost for full 10 minutes.  
QUENCE FOR CES0110063/CES0130024  
SPEED-UP  
(NOMINAL)  
PARAMETER  
MINIMUM  
MAXIMUM  
30-minute cycle  
50-minute cycle  
90-minute cycle  
10-minute cycle  
5 minutes  
27  
45  
81  
9
33  
55  
99  
11  
5.5  
7 sec  
15. Replace control-box cover. Restore power to unit.  
12 sec  
21 sec  
2 sec  
If defrost thermostat does not check out following above items or  
incorrect calibration is suspected, check for a defective thermostat  
as follows.  
4.5  
1 sec  
1. Follow items 1-5 above.  
4. Restart unit in heating.  
2. Route sensor or probe underneath coil (or other convenient  
location) using thermocouple temperature-measuring de-  
vice. Attach to liquid line near defrost thermostat. Insulate  
for more accurate reading.  
5. Within a few minutes, liquid-line temperature drops within  
a range causing defrost-thermostat contacts to close. Tem-  
perature range is from 33°F to 27°F. Notice temperature at  
which ohmmeter reading goes from to zero ohms.  
Thermostat contacts close at this point.  
3. Turn on power to outdoor unit.  
20—  
6. Short between the speed-up terminals using a small, slotted  
screwdriver.  
3. Restart unit in heating mode, allowing frost to accumulate  
on outdoor coil.  
4. After a few minutes in heating mode, liquid-line tempera-  
ture should drop below closing point of defrost thermostat  
(approximately 30° F.  
7. Unit changes over to defrost within 21 sec (depending on  
timing-cycle setting). Liquid-line temperature rises to range  
where defrost-thermostat contacts open. Temperature range  
is from 75°F to 85°F. Resistance goes from zero to when  
contacts open.  
NOTE: Unit will remain in defrost until defrost thermostat  
reopens at approximately 80° F coil temperature at liquid line or  
remainder of defrost cycle time.  
8. If either opening or closing temperature does not fall within  
above ranges or thermostat sticks in 1 position, replace  
thermostat to ensure proper defrost operation.  
5. Turn off power to outdoor unit and reconnect fan-motor  
lead to OF2 on control board after above forced-defrost  
cycle.  
CES0130024 DEFROST CONTROL  
Compressor Shut Down  
Some heat pumps built in 1993 and later incorporated a new  
defrost control similar to the CES0110063 except the 5-minute  
cycle protector has been removed. This control is used on heat  
pump units with reciprocating compressors where short-cycle  
protection is not required.  
This control has the option of shutting down the compressor for 30  
seconds while going into and out of defrost modes. This is  
accomplished by turning DIP switch 3 to the ON position. See Fig.  
22 for switch position. Factory default is in the OFF position.  
Five-Minute Time Delay  
Troubleshooting this control will be the same as the CES0110063  
control except for the cycle-protector function. The CES0130024  
control is identical to the CES0110063 except the T2 terminal and  
cycle-protector logic have been removed.  
This control has a 5minute time delay on startup. The speedup  
terminals can be used to bypass this delay. Momentary shorting  
across the speedup terminals will, upon release, bypass 5minute  
time delay. Do not short out the speedup terminals for more than  
5 seconds, or defrost mode will be initiated.  
CES0130076 DEFROST CONTROL  
This defrost control is the same size as the CES0130063 control  
but is not backwards-compatible. (See Fig. 22.) To upgrade to the  
new control, you must have replacement-defrost thermostat and  
harness kit. See your replacement-component representative for kit  
part number.  
Troubleshooting  
Troubleshooting this control is done in the same manner as the  
CES0130063 control with the exceptions listed above.  
DEFROST THERMOSTAT LOCATION  
On most residential, outdoor heat-pump models, the defrost  
thermostat is located on the return-bend side of the coil. The 5/16  
OD feeder tube from the header will enter a 11/2 in. to 2in. long  
3/8 OD stub prior to entering the coil. There is only one stub tube  
per coil. All other feeder tubes enter the coil directly. The defrost  
thermostat attaches to this stub tube. (See Fig. 23.)  
Defrost Settings  
The defrost control is a time/temperature control which includes a  
field-selectable time period (DIP switch 1 and 2 on board, see  
Table 11) between defrost cycles of 30, 60, 90, and 120 minutes  
(factory-set at 90 minutes).  
X. FAN MOTORS  
TABLE 11DEFROST TIMER SETTINGS  
Fan motor rotates the fan blade that either draws or blows air  
through outdoor coil to perform heat exchange. Motors are totally  
enclosed to increase reliability. This also eliminates need for rain  
shield. For the correct position of the fan blade assembly, see Fig.  
24 and Table 12.  
SW1  
On  
SW2  
Off  
SW3  
30  
Off  
Off  
On  
On  
60  
Off  
90  
On  
120  
WARNING: Turn off all power to unit before servicing  
or replacing fan motor. Be sure unit main power switch is  
turned off. Failure to do so may result in electric shock,  
death, or injury from rotating fan blade.  
To initiate a forced defrost, two options are available, depending  
on the status of the defrost thermostat.  
If defrost thermostat is closed, speedup pins (J1) must be shorted  
by placing a Flathead screwdriver in between for 5 seconds and  
releasing, to observe a complete defrost cycle. When the Quiet  
Shift switch is selected, compressor will be turned off for two,  
30second intervals during this complete defrost cycle. When  
Quiet Shift switch is in factory-default OFF position, a normal and  
complete defrost cycle will be observed.  
The bearings are permanently lubricated; therefore, no oil ports are  
provided.  
For suspected electrical failures, check for loose or faulty electrical  
connections, or defective fan-motor capacitor. Fan motor is  
equipped with thermal overload device in motor windings which  
may open under adverse operating conditions. Allow time for  
motor to cool so device can reset. Further checking of motor can  
be done with an ohmmeter. Set scale on R X 1 position; check for  
continuity between 3 leads. Replace motors that show an open  
circuit in any of the windings. Place 1 lead of ohmmeter on each  
motor lead. At same time, place other ohmmeter lead on motor  
case (ground). Replace any motor that shows resistance to ground,  
signs of arcing, burning, or overheating.  
If defrost thermostat is in open position and speedup pins are  
shorted (with a Flathead screwdriver) for 5 seconds and released,  
a short defrost cycle will be observed (actual length is dependent  
upon the selected Quiet Shift position). When Quiet Shift switch is  
in ON position, the length of defrost is 1 minute (30 seconds  
compressor-off period followed by 30 seconds of defrost with  
compressor operation). On return to heat operation, compressor  
will again turn off for an additional 30 seconds and the fan for 40  
seconds. When the Quiet Shift is in OFF position, only a brief  
30second cycle will be observed.  
XI. SERVICE ALARM CONTROL BOARD  
NOTE: If the proper night-setback thermostat is not used, the  
service-alarm control will work, but there will be no light  
indication on thermostat.  
The service-alarm control provides immediate warning when  
outdoor heat pump requires servicing. It turns on indoor  
thermostat-malfunction light if compressor does not operate for  
If it is desirable to observe a complete defrost in warmer weather,  
the thermostat must be closed as follows.  
1. Turn off power to outdoor unit.  
2. Disconnect outdoor fan-motor lead from OF2 on control  
board. (See Fig. 22.) Tape to prevent grounding.  
21—  
CESO13007600  
Speedup  
Pins  
Quiet  
Shift  
Defrost interval  
DIP switches  
A99442  
Fig. 22Defrost Control  
either heating or cooling. This enables owner to obtain timely  
heat-pump service during heating season, reducing supplementary  
electric heat costs, and during cooling season, reducing period of  
heat discomfort.  
Service alarm requires 2 inputs.  
1. It must sense a 24v input from thermostat. As thermostat  
calls for heating or cooling, it supplies 24v to service-alarm  
device.  
2. A current transformer (or induction loop) similar to a  
clamp-on ammeter senses current draw in the compressor  
lead. Induction loop must sense a minimum current draw  
when thermostat is calling for heating or cooling.  
NOTE: On a single-phase compressor, induction loop senses  
current in common leg. On a 3-phase compressor, induction loop  
senses current in any 1 of the phases.  
The service alarm is an accessory device. Service alarm locks out  
compressor under certain adverse operating conditions. System is  
manually reset by shutting it off at thermostat subbase, then  
turning it back on. If adverse condition is corrected, system  
restarts.  
One example of an adverse condition would be a system located in  
a desert climate where high operating temperatures may cause  
system to shut down on the high-pressure switch or on the  
compressor internal overload.  
WARNING: If service alarm needs replacing, shut off  
all power to unit before attempting removal. Electrical  
shock can cause personal injury or death.  
Connect service alarm to outdoor-unit control-circuit-terminal  
board. (See Fig. 25 and wiring diagram on unit.)  
Connect all field line-power wires to unit in usual manner. Route  
1 field line-power supply wire through metallic loop on bottom of  
service alarm then to normal unit connection. Units with RLA of  
less than 14 amps will require 2 passes through the metallic loop.  
Troubleshooting service-alarm device is easy. With thermostat  
calling for heating or cooling and compressor running, indoor  
thermostat light should be off. If on, check for wiring errors or  
replace the service alarm.  
To check for correct operation, shut off circuit breaker or discon-  
nect switch to outdoor unit while it is running. Signal light on  
thermostat should light. If this does not occur, check for wiring  
errors or replace the service alarm.  
Refer to Fig. 25 or 26 for wiring connections for service alarm or  
service alarm with solid-state cycle-protector accessories, when  
used.  
NOTE: The wire from the X terminal on the service alarm to L on  
the outdoor terminal board, indoor terminal board, and thermostat  
subbase is field-supplied and wired when using defrost controls  
HK32FA003 or HK32FA006. When defrost control CES0110063  
or CES0130024 is used, field-supplied wire from X terminal on  
service alarm to L on indoor thermostat subbase is required.  
XII. OUTDOOR THERMOSTAT(S)  
The outdoor thermostat(s) is installed in the control box. The  
sensing bulb(s) remain in the control box. Outdoor thermostat  
brings on stages of electric heat as outdoor temperature and  
22—  
TABLE 12FAN POSITION  
AEROQUIET SYSTEM AND AEROMAX TOP  
Dimension A (In.)  
Fan Motor Part No.  
HC29GE208  
Fan Blade Part No.  
Brookside  
Revcor  
LA01EB023  
LA01EC019  
LA01EA026  
LA01RA015  
LA01EW049  
LA01RA015  
45/32  
51/8  
45/8  
HC31GE230/231  
47/8  
45/8  
HC33GE208  
HC33GE232  
HC34GE231  
HC34GE460  
HC35GE208  
51/4  
429/32  
417/32  
LA01RA015  
55/32  
425/32  
LA01EW048  
LA01EA025  
LA01RA024  
LA01RA026  
LA01EA025  
LA01EW046  
LA01EA031  
LA01EC018  
LA01RA026  
LA01EA036  
LA01EA024  
LA01EC018  
LA01EA036  
LA01EC018  
LA01RA026  
LA01EA024  
LA01EA024  
415/16  
57/8  
HC35GE232  
511/32  
59/16  
61/8  
53/32  
411/16  
61/8  
61/8  
HC37GE208  
HC37GE230  
HC38GE221  
65/32  
725/32  
511/16  
51/2  
HC39GE232  
HC39GE234  
HC39GE461  
43/4  
59/16  
53/32  
51/2  
427/32  
61/16  
61/4  
61/16  
59/32  
527/32  
57/32  
511/32  
519/32  
HC40GE230  
HC40GE461  
FEEDER TUBE  
STUB TUBE  
DEFROST  
THERMOSTAT  
A97517  
Fig. 23Defrost Thermostat Location  
A
BASKET TOP  
A91428  
Fig. 24Fan Position  
23—  
HIGH AND/OR LOW PRESSURE  
AND/OR DISCHARGE TEMPERATURE  
SWITCH (IF USED)  
DTS  
24-VOLT WIRING  
HPS  
LPS  
BRN  
C
C
Y
L
BLU  
BLU YEL  
YEL  
L
L
C
BLK  
ORN  
YEL RED  
THERMOSTAT  
SUBBASE  
INDOOR  
UNIT  
TERMINAL  
BOARD  
OUTDOOR  
UNIT  
TERMINAL  
BOARD  
1
2
3
X
SERVICE ALARM  
PASS SUPPLY WIRE THROUGH  
METALLIC LOOP TWICE ON  
UNITS WITH NAMEPLATE  
RLA OF 14 AMPS OR LESS.  
*METALLIC  
LOOP  
ONE FIELD  
LINE VOLTAGE  
SUPPLY WIRE  
A88340  
Fig. 25Service Alarm Wiring Connections  
FIELD LINE VOLTAGE SUPPLY WIRE  
CYCLE PROTECTOR  
T1 T2 T3  
SERVICE ALARM  
YEL  
X
3
2
1
HIGH AND/OR LOW PRESSURE  
AND/OR DISCHARGE TEMPERATURE  
SWITCH (IF USED)  
VIO BLK  
ORN  
Y
DTS  
C
L
L
L
C
C
C
YEL  
YEL  
BLU  
BLU  
BLK  
LPS  
HPS  
BLK  
BRN  
BRN  
A88339  
THERMOSTAT INDOOR OUTDOOR  
SUBBASE UNIT  
UNIT  
TERMINAL TERMINAL  
BOARD  
BOARD  
COMMON POTENTIAL  
FACTORY WIRING (FIELD CONNECTED)  
FIELD-SUPPLIED WIRING  
CONTACTOR  
C
A88339  
Fig. 26Wiring Connections for Service Alarm and Cycle Protector  
heat-pump output drops. Setting at which thermostat closes is  
variable, depending on design of system. It is set at time of  
installation and should not be changed without cause. Up to 2  
outdoor thermostats may be installed. Some systems may not have  
any thermostat. An outdoor thermostat can also be used to lock out  
compressor operation at low ambients in condensing unit not  
equipped with low-ambient control.  
XIII. COMPRESSOR PLUG  
The compressor electrical plug provides a quick-tight connection  
to the compressor terminals. The plug completely covers the  
compressor terminals, and the mating female terminals are com-  
pletely encapsulated in the plug. Therefore, the terminals are  
isolated from any moisture so corrosion and resultant pitted or  
discolored terminals are reduced. The plug is oriented to the relief  
slot in the terminal box so the cover cannot be secured if wires are  
not positioned in slot, assuring correct electrical connection at the  
compressor. The plug can be removed by simultaneously pulling  
while rockingthe plug. However, these plugs are specialized and  
vary in terminal orientation in the plug. Therefore, plugs can be  
used on only the specific compressor or group as shown in Fig. 27.  
Although these devices are installed in control circuit (24v), turn  
off all power to unit before attempting to troubleshoot thermostat.  
Use a standard ohmmeter to check for continuity through thermo-  
stat. If you suspect thermostat is out of calibration, use calibrated  
electronic thermometer to determine correct outdoor temperature.  
Turn thermostat dial knob until switch closes. Observe this using  
ohmmeter across switch. Read temperature setting when switch  
closes. It should be close to reading observed using electronic  
thermometer. Any setting within ± 5°F is acceptable.  
For the Carlyle and Bristol compressors in Fig. 27, the triangle  
formed by the fusite terminals points down, and the plug is  
likewise oriented. The fusite terminals and plug-terminal orienta-  
24—  
tion shown for the Tecumseh compressor is shown with the  
triangle formed by the terminals pointing toward the top. The  
configuration around the fusite terminals is the outline of the  
terminal covers used on the specific compressors. The slot through  
which the wires of the plug are routed is oriented on the bottom or  
slightly to the left or right. The correct plug can be connected  
easily to the compressor terminals and plug wires routed easily  
through the slot in the terminal cover. Therefore, if a Carlyle or  
Bristol compressor is substituted for a Tecumseh compressor, a  
new plug must be installed. If the plug is not changed, proper  
connection and routing of the plug wires through the terminal  
cover will be impossible.  
GEnergizes blower circuit from indoor thermostat.  
EEnergizes emergency-heat relay.  
W2Energizes first-stage supplemental heat through defrost relay  
(wht).  
LEnergizes light on thermostat with service alarm.  
W3Energizes second- or third-stage supplemental heat.  
REnergizes 24v power from transformer (red).  
YEnergizes contactor for first-stage cooling or first-stage heat-  
ing for heat pumps (yel).  
OEnergizes reversing valve on heat pumps (orn).  
CCommon side of transformer (blk).  
RECIPROCATING COMPRESSOR  
BRISTOL  
COPELAND  
CARLYLE  
LEAD 3  
BLUE  
The compressor is the heart of the refrigeration system. It pumps  
refrigerant through the system. If it malfunctions, system capacity  
and efficiency could be negatively affected.  
C
S
C
S
C
S
R
CAUTION: The compressor is an electrical (as well as  
mechanical) device. Exercise extreme caution when  
working near compressors. Power should be shut off, if  
possible, for most troubleshooting techniques. Refriger-  
ants in system present other safety hazards. Always wear  
safety glasses and gloves when handling refrigerants.  
R
R
LEAD 2  
YEL.  
LEAD 1  
BLK.  
TECUMSEH  
Compressor failures are classified in 2 broad failure categories:  
mechanical and electrical. Both types are discussed below.  
LEAD 1  
BLK.  
C
I. MECHANICAL FAILURES  
C
A compressor is a mechanical pump driven by an electric motor  
contained in a welded or hermetic shell. In a mechanical failure,  
motor or electrical circuit appears normal, but compressor does not  
function normally.  
S
R
S
R
LEAD 2  
YEL.  
LEAD 3  
BLUE  
CAUTION: Exercise extreme caution when reading  
compressor currents when high-voltage power is on.  
Correct any of the problems described below before  
installing and running a replacement compressor. Wear  
safety glasses and gloves when handling refrigerants.  
TECUMSEH  
LEAD 1  
BLK.  
LEAD 3  
BLUE  
C
C
LOCKED ROTOR  
S
S
In this type of failure, compressor motor and all starting compo-  
nents are normal. When compressor attempts to start, it draws  
locked-rotor current and cycles off on the internal protection.  
Locked-rotor current is measured by applying a clamp-on ammeter  
around common (blk) lead of the compressor on a single-phase  
compressor, or any 1 of the leads on a 3-phase compressor. Current  
drawn when it attempts to start is then measured. LRA (locked-  
rotor amp) value is stamped on compressor nameplate.  
R
R
LEAD 2  
YEL.  
MILLENNIUM  
If compressor draws locked-rotor amps and all other external  
sources of problems have been eliminated, compressor must be  
replaced. Because compressor is a sealed unit, it is impossible to  
determine exact mechanical failure. However, complete system  
should be checked for abnormalities such as incorrect refrigerant  
charge, restrictions, insufficient airflow across indoor or outdoor  
coil, and so forth, which could be contributing to the failure.  
LEAD 1  
BLK.  
C
C
R
S
S
R
LEAD 3  
BLUE  
RUNS, DOES NOT PUMP  
LEAD 2  
YEL.  
In this type of failure, compressor motor runs and turns compres-  
sor, but compressor does not pump the refrigerant. A clamp-on  
ammeter on common leg of a single-phase compressor, or any 1  
lead of a 3-phase compressor, shows a very low current draw,  
much lower than RLA (rated load amps) value stamped on  
compressor nameplate. Because no refrigerant is being pumped,  
there is no return gas to cool compressor motor. It eventually  
overheats and shuts off on its internal protection.  
A94002  
Fig. 27Compressor Plug  
XIV. LOW-VOLTAGE TERMINALS  
The low-voltage terminal designations, along with descriptions  
and/or functions, are used on all split-system condensers and heat  
pumps:  
RUNS, DOES NOT PUMP, HIGH-TO-LOW SIDE LEAK  
25—  
(EXAMPLE)  
?
?
?
TO DETERMINE INTERNAL CONNECTIONS OF SINGLE-  
PHASE MOTORS (C,S,R) EXCEPT SHADED-POLE  
DEDUCTION:  
POWER OFF!  
1
3
(GREATEST RESISTANCE)  
RUN WINDING (R)  
5.8(OHM)  
START WINDING (S)  
OHMMETER  
2
3
(SMALLEST RESISTANCE)  
2
IS COMMON (C)  
BY ELIMINATION  
0-10SCALE  
0.6Ω  
1
1
1
2
(REMAINING RESISTANCE)  
2
IS COMMON,  
THEREFORE,  
2
5.2Ω  
5.2Ω  
IS  
1
5.8Ω  
0.6Ω  
START WINDING (S)  
IS RUN WINDING (R)  
2
3
3
3
A88344  
Fig. 28Identifying Internal Connections  
In this type of failure, compressor motor runs and turns compres-  
sor, and compressor is pumping. Usually, an internal problem such  
as blown head gasket or broken internal-discharge line causes  
compressor to pump hot discharge gas back into its own shell  
rather than through system.  
2. Remove and recover all refrigerant from system so that  
gage pressures are 0 psi.  
3. Clean area around leak to bare metal.  
4. Apply flux and repair joint with silver solder. Do not use  
low-temperature solder such as 50-50.  
Using pressure gages on service valves shows high suction and  
low discharge pressure readings. Motor currents are lower than  
normal. Because hot gas is being discharged into shell, the shell  
becomes hot. The hot gas causes compressor motor to cycle off on  
its internal protection.  
5. Clean off excess flux, check for leaks, and apply paint over  
repaired area to prevent corrosion.  
Do not use this method to repair a compressor leak due to severe  
corrosion. Never attempt to repair a compressor leaking at electric  
terminals. This type of failure requires compressor replacement.  
RUNS AND PUMPS, LOW CAPACITY  
II. ELECTRICAL FAILURES  
This failure type is difficult to pinpoint because extent of damage  
varies. Compressor is a pump with internal valves that enable  
compressor to pump properly. The cylinder has a set of suction and  
discharge valves. Any of these parts may become damaged or  
broken, causing loss in pumping capacity. Severity of damage  
determines amount of capacity loss. Use pressure gages to find any  
abnormal system pressures if system charge and other conditions  
are normal.  
The compressor mechanical pump is driven by an electric motor  
within its hermetic shell. In electrical failures, compressor does not  
run although external electrical and mechanical systems appear  
normal. Compressor must be checked electrically for abnormali-  
ties.  
Before troubleshooting compressor motor, review this description  
of compressor motor-terminal identification.  
SINGLE-PHASE MOTORS  
An owner may complain that a unit is not handling the buildings  
heating or cooling load. The compressor current draw may be  
abnormally low or high. Although this type of failure does occur,  
all other possible causes of capacity loss must be eliminated before  
condemning compressor.  
To identify terminals C, S, and R:  
1. Turn off all unit power.  
2. Short the run and start capacitors to prevent shock.  
3. Remove all wires from motor terminals.  
NOISY COMPRESSOR  
4. Read resistance between all pairs of terminals using an  
ohmmeter on 0-10 ohm scale.  
Noise may be caused by a variety of internal problems such as  
loosened hardware, broken mounting springs, etc. System prob-  
lems such as overcharged compressor (especially at start-up) or too  
much oil in compressor may also cause excessive noise. Excess oil  
in compressor is normally encountered only after a replacement  
compressor has been added without purging oil from previous  
compressor. As new compressor pumps, excess oil in system  
returns and adds to volume already present, causing noise.  
5. Determine 2 terminals that provide greatest resistance  
reading.  
Through elimination, remaining terminal must be common (C).  
Greatest resistance between common (C) and another terminal  
indicates start winding because it has more turns. This terminal is  
start (S). Remaining terminal will be run winding (R). (See Fig.  
28.)  
COMPRESSOR LEAKS  
NOTE: If compressor is hot, allow time to cool and internal line  
break to reset. There is an internal line-break protector which must  
be closed.  
CAUTION: Use safety glasses and gloves when han-  
dling refrigerants.  
THREE-PHASE MOTORS  
Resistance readings between all 3 sets of windings should be the  
same.  
Sometimes a leak is detected at weld seam around girth of  
compressor or a fitting that joins compressor shell. Many of these  
leaks can be repaired and the compressor saved if correct proce-  
dure is followed.  
All compressors are equipped with internal motor protection. If  
motor becomes hot for any reason, protector opens. Compressor  
should always be allowed to cool and protector to close before  
troubleshooting. Always turn off all power to unit and disconnect  
leads at compressor terminals before taking readings.  
1. Turn off all power to unit.  
26—  
Most common motor failures are due to either an open, grounded,  
or short circuit. Directions below are specifically for single-phase  
units, however, they also apply to 3-phase compressors. When a  
single-phase compressor fails to start or run, 3 tests can help  
determine the problem. First, all possible external causes should be  
eliminated, such as overloads, improper voltage, pressure equal-  
ization, defective capacitor(s), relays, wiring, and so forth. Com-  
pressor has internal line-break overload, so be certain it is closed.  
4. Motor must be dry or free from direct contact with liquid  
refrigerant.  
MAKE THIS CRITICAL TEST  
(Not advisable unless above conditions are met.)  
1. Be sure all power is off.  
2. Discharge all capacitors.  
3. Remove wires from terminals C, S, and R.  
OPEN CIRCUIT  
4. Place instrument probes together and determine probe and  
lead wire resistance.  
To determine if any winding has a break in the internal wires and  
current is unable to pass through:  
5. Check resistance readings from C-R, C-S, and R-S.  
1. Be sure all power is off.  
6. Subtract instrument probe and lead resistance from each  
reading.  
2. Discharge all capacitors.  
3. Remove wires from terminals C, S and R.  
If any reading is within ± 20 percent of known resistance, motor is  
probably normal. Usually a considerable difference in reading is  
noted if a turn-to-turn short is present.  
4. Check resistance from C-R, C-S and R-S using an ohmme-  
ter on 0-1000 ohm scale.  
Because winding resistances are usually less than 10 ohms, each  
reading appears to be approximately 0 ohm. If resistance remains  
at 1000 ohms, an open or break exists, and compressor should be  
replaced.  
III. SYSTEM CLEANUP AFTER BURNOUT  
CAUTION: Turn off all power to unit before proceed-  
ing. Wear safety glasses and gloves when handling  
refrigerants. Acids formed as a result of motor burnout  
can cause burns.  
CAUTION: Be sure internal line-break overload is not  
temporarily open.  
NOTE: To analyze level of suspected contamination from com-  
pressor burnout, use Total Test. See your distributor/branch.  
GROUND CIRCUIT  
To determine if a wire has broken or come in direct contact with  
shell, causing a direct short to ground:  
Some compressor electrical failures can cause motor to overheat.  
When this occurs, by-products, which include sludge, carbon, and  
acids, can contaminate system. If burnout is severe enough, system  
must be cleaned before replacement compressor is installed. The 2  
types of motor burnout are classified as mild or severe.  
1. Be sure all power is off.  
2. Discharge all capacitors.  
3. Remove wires from terminals C, S, and R.  
In mild burnout, there is little or no detectable odor. Compressor  
oil is clear or slightly discolored. An acid test of compressor oil  
will be negative. This type of failure is treated the same as  
mechanical failure. Liquid-line strainer should be removed and  
liquid-line filter drier installed.  
4. On hermetic compressors, allow crankcase heaters to re-  
main on for several hours before checking motor to ensure  
windings are not saturated with refrigerant.  
5. Use an ohmmeter on R X 10,000 ohm scale. A megohm-  
meter may be used in place of ohmmeter. Follow manufac-  
turers instructions.  
In a severe burnout, there is a strong, pungent, rotten-egg odor.  
Compressor oil is very dark. Evidence of burning may be present  
in tubing connected to compressor. An acid test of compressor oil  
will be positive. Complete system must be reverse flushed with  
refrigerant. Check-Flo-Rateror TXV must be cleaned or re-  
placed. In a heat pump, accumulator and reversing valve are  
replaced. These components are also removed and bypassed during  
reverse-flushing procedure. Remove and discard liquid-line  
strainer. After system is reassembled, install liquid-line and  
suction-line filter driers. Run system for 2 hrs. Discard both driers  
and install new liquid-line drier only.  
6. Place 1 meter probe on ground or on compressor shell.  
Make a good metal-to-metal contact. Place other probe on  
terminals C, S, and R in sequence.  
7. Note meter scale.  
8. If reading of zero or low resistance is obtained, motor is  
grounded. Replace compressor.  
A 1 ton or less capacity compressor is probably grounded if  
resistance is below 1 million ohms. On larger-sized, single-phase  
compressors, resistance to ground should not be less than 1000  
ohms per volt of operating voltage.  
IV. COMPRESSOR REMOVAL AND REPLACEMENT  
Once it is determined that compressor has failed and the reason  
established, compressor must be replaced.  
Example:  
230 volts X 1000 ohms/volt = 230,000 ohms minimum.  
SHORT CIRCUIT  
CAUTION: Wear safety glasses and gloves when han-  
dling refrigerants and when using brazing torch.  
To determine if any wires within windings have broken through  
their insulation and made contact with other wires, thereby  
shorting all or part of the winding(s), be sure the following  
conditions are met:  
1. Shut off all power to unit.  
1. Correct motor-winding resistances must be known before  
testing, either from previous readings or from manufactur-  
ers specifications.  
2. Remove and recover all refrigerant from system until  
pressure gages read zero psi. Use all service ports.  
3. Disconnect electrical leads from compressor. Disconnect or  
remove crankcase heater and remove compressor-holddown  
bolts.  
2. Temperature of windings must be as specified, usually  
about 70°F.  
3. Resistance-measuring instrument must have an accuracy  
within ± 5 to 10 percent. This requires an accurate ohmme-  
ter, such as a Wheatstone bridge or null balance-type  
instrument.  
4. Cut compressor from system with tubing cutters. Do not use  
brazing torch for compressor removal. Oil vapor may ignite  
when compressor is disconnected.  
27—  
5. Scratch matching marks on stubs in old compressor. Make  
corresponding marks on replacement compressor.  
6. Use torch to remove stubs from old compressor and to  
reinstall them in replacement compressor.  
Scroll Gas Flow  
Compression in the scroll is  
created by the interaction of  
an orbiting spiral and a  
stationary spiral. Gas enters  
an outer opening as one of the  
spirals orbits.  
7. Use copper couplings to tie compressor back into system.  
8. Evacuate system, recharge, and check for normal system  
operation.  
1
9. Copeland CR-6 and scroll compressors have copper-plated,  
steel-suction ports. Excess heat during brazing will burn off  
copper plating. See Brazing section for additional informa-  
tion.  
COPELAND SCROLL COMPRESSOR  
I. FEATURES  
2
3
The scroll compressor pumps refrigerant through the system by the  
interaction of a stationary and an orbiting scroll. (See Fig. 29.) The  
scroll compressor has no dynamic suction or discharge valves, and  
it is more tolerant of stresses caused by debris, liquid slugging, and  
flooded starts. Due to the design of the scroll compressor, the  
internal compression components unload (equalize pressure) on  
shutdown. The white oil (Sontex 200LT) used in the scroll is  
compatible with 3GS oil, which can be used if additional oil is  
required. (See Table 13 for oil recharge requirements.)  
As the spiral continues to orbit,  
the gas is compressed into an  
increasingly smaller pocket.  
The open passage is sealed off  
as gas is drawn into the spiral.  
TABLE 13COMPRESSOR OIL RECHARGE  
4
5
By the time the gas arrives at  
the center port, discharge  
pressure has been reached.  
Actually, during operation, all  
six gas passages are in various  
stages of compression at all  
times, resulting in nearly con-  
tinuous suction and discharge.  
RECHARGE  
(FL. OZ.)  
COMPRESSOR MODEL  
OIL TYPE  
Carlyle/Scroll  
JType  
SC, SRD450AC  
SR  
44  
34  
52  
68  
70  
Suniso 3GS  
Zerol 150  
w/3 percent  
Syn-O-Ad  
A90198  
SRH482, SRY482  
SRH602, SRY602  
Fig. 29Scroll Compressor Refrigerant Flow  
vacuum. If a pumpdown procedure is used, the scroll compressor  
is capable of pumping into a vacuum very quickly, which could  
cause fusite arcing and compressor failure. See Step IV of  
Reciprocating Compressor section for removal and replacement.  
Copeland  
CRG3, CRH3, CRJ3, CRK3, CRL3  
CRN5, CRP5, CRT5, CTH1, CTL1  
CRC4, CRZ4  
51  
66  
36  
42  
19  
24  
30  
34  
56  
56  
56  
66  
III. DISCHARGE THERMOSTAT  
CR16K6 THROUGH CR42K6  
*ZR18K1  
Some scroll compressors have a discharge thermostat that recip-  
rocating compressors do not have. This thermostat is mounted in a  
well in the top of the compressor shell to sense if the discharge  
temperature reaches 290°F and shuts down the compressor to  
prevent damage to it. When the temperature of the thermostat  
reaches 140°F, power is restored to the compressor.  
To determine if the thermostat is operating properly, either attach  
the thermocouple of an electronic thermometer to the dome of the  
compressor near the thermostat, or remove the thermostat and  
place the thermocouple inside the well. The electronic thermom-  
eter must be capable of reading at least 300°F. Start the unit and let  
it run for at least 15 minutes to obtain normal operating conditions.  
Watch the thermometer to see if it is approaching 270°F. If the  
thermocouple is located on the dome near the discharge thermo-  
stat, there could be a 20° difference between well and dome  
temperatures. If the temperature approaches 270°F, repair system  
problem, such as low charge, blocked condenser coil, and so forth.  
If the temperature does not approach 270°F, replace discharge  
thermostat.  
*ZR23K1, ZR28K1  
*ZR34K1  
Suniso 3GS  
*ZR40K1  
*ZR49K1-PFV  
*ZR49K2-TF5, ZR49K2-TFD  
*ZR61K2-PFV  
*ZR61K2-TF5, ZR61K2-TFD  
Tecumseh  
AV55  
50  
30  
60  
AW55  
Suniso 3GS  
Suniso 3GS  
AG  
Bristol  
H23A  
52  
37  
47  
52  
62  
32  
H23B  
H24A3, H24A4  
H24A5  
H25A, H26A  
Replacing Discharge Thermostat  
H25B, H26B, H29B  
To replace the discharge thermostat, refer to the Installation  
Instructions packaged with the replacement discharge thermostat  
kit. (See Fig. 30.)  
*Copeland scrolls are charged initially with Sontex 200LT white oil. Since this  
oil is not commercially available, use 3GS.  
II. TROUBLESHOOTING  
IV. DISCHARGE SOLENOID VALVE  
Troubleshooting mechanical or electrical problems in a scroll  
compressor is the same as for a reciprocating compressor, except  
that a scroll compressor should never be allowed to pump into a  
Some larger units equipped with scroll compressors contain a  
solenoid valve that is piped between the discharge tube and suction  
tube of the compressor. The purpose of the solenoid valve is to  
28—  
The scroll compressor is capable of pumping into a vacuum very  
quickly, which could cause fusite arcing and compressor failure.  
See Step IV of Reciprocating Compressor section for removal and  
replacement.  
PLASTIC CAP  
IV. SCROLL COMPRESSOR, 3PHASE MONITOR  
CES0130075 PHASE MONITOR  
BLUE SEALANT  
PRONG  
This control is factory-installed on all 3phase, scroll compressor  
models. (See Fig. 31 and 32.) On start-up, the control will energize  
the pilot relay for 2 seconds. The monitor will check for correct  
compressor rotation. If rotation is correct, unit will continue to run.  
If rotation is incorrect, the control will break the 24vac power at  
the contactor and an LED light on the control will flash. If LED is  
flashing, turn off power, reverse L1 and L3 field-power leads, and  
restart unit. This control will check incoming power at every  
restart.  
GROMMET  
TWO-SPEED SYSTEM  
I. CAUTIONS AND WARNINGS  
CAUTION: For proper unit operation and reliability, the  
2-speed units must be installed with the factory-supplied  
balance port, hard shutoff TXV. Do not install with  
indoor coils having piston or capillary-tube metering  
devices.  
THERMOSTAT  
A90198  
THERMAL GREASE  
CAUTION: Do not install equivalent interconnecting  
tubing lengths greater than 100 ft. Do not decrease or  
increase interconnecting tubing diameters.  
Fig. 30Location of Discharge Thermostat  
cause a rapid pressure equalization around the compressor, thus  
reducing the normal shutdown sound created by reverse rotation of  
the scroll. The solenoid valve is normally closed and is wired  
across high-voltage line 1 to load terminals of the contactor. (See  
Fig. 18.) The solenoid-valve assembly also requires a check valve  
piped in the discharge tube between the solenoid-valve tee and the  
condenser coil, or reversing valve on heat pumps. The purpose of  
the check valve is to prevent refrigerant from bypassing through  
the solenoid valve into the suction tube when the unit cycles off.  
CAUTION: To avoid electrical shock, bleed resistor  
must be connected across run capacitor. Replace if  
missing or damaged.  
CAUTION: Contactor is mechanically interlocked. Do  
not disable mechanical interlock. Compressor damage  
may occur.  
MILLENNIUM SCROLL COMPRESSOR  
I. FEATURES  
The scroll compressor pumps refrigerant through the system by the  
interaction of a stationary and an orbiting scroll. (See Fig. 29.) The  
scroll compressor has no dynamic suction or discharge valves, and  
it is more tolerant of stresses caused by debris, liquid slugging, and  
flooded starts. The Millennium scroll varies from the Copeland  
scroll in that the Millennium has a shutdown flapper valve located  
between the scroll plates and the discharge head, whereas the  
Copeland has a check device at the discharge connection after the  
discharge head. The Copeland discharge head unloads when the  
compressor shuts down. The scroll plate actually runs backwards  
while it unloads. A 1 to 3 second unloading of refrigerant occurs.  
WARNING: Contactor control voltage is 240vac.  
WARNING: Do not attempt to operate this equipment  
below 55°F outdoor ambient temperature.  
NOTE: Sections that follow describe the 598A Series B and  
698A Series B products, which started production March, 1994.  
For 598A Series A and 698A Series A products, refer to the  
Split-System Service Manual dated 3194, Catalog No. BDP  
3356115.  
The Millennium flapper valve eliminates the refrigerant unloading  
by not allowing the discharge head to run backwards because of its  
location. The Millennium scroll compressor uses Zerol 150 oil  
with 3 percent Syn-O-Ad and is the only oil recommended for oil  
recharge. See Table 13 for recharge requirements.  
II. SYSTEM FUNCTIONS  
II. COMPRESSOR PROTECTION  
COOLING OPERATION  
Millennium scroll compressors are protected by an internal line-  
break mounted on the motor windings. Internal protectors respond  
to overcurrent and high temperature. These protectors are  
automatic-reset devices containing a snap-action, bi-metal switch.  
The 2-speed products utilize a 2-stage-cooling indoor thermostat.  
With a call for first-stage cooling (Y1), the outdoor fan and  
low-speed compressor are energized. If low speed cannot satisfy  
the cooling demand, high speed will be energized (Y1 and Y2) by  
the second stage of the indoor thermostat. The thermostat has a 2°  
differential between first and second stages. After second stage is  
satisfied, the unit returns to low-speed operation, until first stage is  
satisfied, or until second stage is again required.  
III. TROUBLESHOOTING  
Troubleshooting mechanical and electrical problems in a scroll  
compressor is similar to a reciprocating compressor, except that a  
scroll compressor should never be allowed to pump into a vacuum.  
29—  
A00010  
Fig. 31CES0130075 3Phase Monitor Board  
L1  
L2  
COMP  
CONT  
T2  
T1  
L3  
EQUIP  
GND  
11  
21  
T3  
*CH  
CONT  
CAP  
13  
23  
OFM  
L1  
L2  
L3  
LOGIC  
C
CESO130075  
Y
CONT  
CONT  
*LPS  
*HPS  
T2  
T3  
LOGIC  
T1  
*LLS  
CTD  
Y
G
IFR  
C
R
R
INDOOR  
THERMOSTAT  
EXTERNAL POWER SUPPLY 24 V  
A00011  
Fig. 32CESO130075 3Phase Monitor Wiring Diagram  
30—  
HEATING OPERATION (HEAT PUMP ONLY)  
LM1 LM2 DFT1 DFT2 T1 T2 S2 S1 PW2 PW1  
The 2-speed products utilize a 2-stage-heating indoor thermostat.  
The first stage of heating is heat-pump operation (Y1). Auxiliary  
backup heat is controlled by second stage (W2). There is a 2°  
differential between first and second stage. The control board  
determines the compressor speed based on ambient temperature.  
See Table 14 for ambient temperatures at which speed changes  
occur. When high-speed, heat-pump heating is required, the  
control provides a Y2 (24vac) signal back to the thermostat to  
energize high-speed-indicator LED.  
1
P1  
18  
K7  
FURN INT  
OFF  
ON  
50  
SPEED-UP  
TABLE 14AMBIENT TEMPERATURE FOR HIGH- AND  
LOW-SPEED OPERATION  
AMBIENT TEMPERATURE (°F)  
UNIT  
SIZE  
STAGE 2 DEFROST BALANCE  
LATCH TIME POINT  
High Speed  
30 or less  
33 or less  
40 or less  
Low Speed  
31 or greater  
34 or greater  
41 or greater  
036  
048  
060  
A93568  
Fig. 34Speedup Terminals  
CRANKCASE-HEATER OPERATION  
LED FUNCTION LIGHTS  
When using the factory-authorized indoor thermostats with the  
2-speed outdoor units, there are 2 locations where system-function  
LED-indicator lights are available. The indoor thermostat provides  
indicator lights for high- and low-speed operation, system mal-  
function, and auxiliary heat for heat pumps. The 2-speed control  
board has an LED which provides signals for several system  
operations. See Table 15 for LED functions, indicator locations,  
and definitions. Table 15 also provides the order of signal  
importance if more than 1 signal should occur. The signal to the  
indoor thermostat is supplied by the low-voltage Llead.  
The 2-speed control energizes the crankcase heater during the  
units off cycle when the outdoor ambient is below 75°F.  
OUTDOOR FAN-MOTOR OPERATION  
The 2-speed control energizes the outdoor fan any time the  
compressor is operating. The outdoor fan remains energized during  
the 1-minute, speed-change time delay and if a pressure switch or  
compressor PTC overload should trip.  
If the outdoor fan motor wont run, check the header-pin housing.  
(See Fig. 37.) There should be NO jumper wire between Terminals  
15 and 16.  
THREE-SECOND TIME DELAY  
Any time the control receives a 24v input, such as Y1 or Y2, there  
is a 3-sec time delay before the control function is initiated. This  
helps prevent nuisance trips and thermostat jiggling.″  
Heat Pumps  
After the termination of a defrost cycle, the outdoor fan delays  
come on for 20 sec. This allows the refrigeration system to recover  
the outdoor coil heat and minimize the steam cloudeffect.  
ONE-MINUTE SPEED-CHANGE TIME DELAY  
When the compressor changes speeds from high to low or low to  
high, there is a 1-minute time delay before the compressor restarts.  
The outdoor fan motor remains running.  
SECOND-STAGE LATCHING  
When low-speed cooling operation no longer satisfies the first  
stage of the indoor thermostat, the indoor temperature will increase  
by 2° until second stage is energized. After high-speed cooling  
satisfies second stage, it returns to low-speed cooling operation. If  
desired, the installer may select to have high-speed cooling by  
energizing Y1. High speed will stay energized until Y1 is satisfied.  
This eliminates the temperature drop between the first and second  
stages of indoor thermostat, holding room temperature closer to set  
point.  
FIVE-MINUTE TIME DELAY  
The 2-speed-control logic contains a 5-minute time delay that  
prevents the unit from short cycling after a thermostat-off cycle or  
power interruption. The unit can be forced to operate immediately  
by momentarily touching a jumper between the speed-up terminals  
of the control board. (See Fig. 33 and 34.) The speed-up feature  
will not bypass any other function or time delay.  
To utilize this function, the unit capacity should be plotted versus  
the heat gain of the structure, which provides the systems balance  
point when the structure requires high-speed capacity. (See Fig.  
35.)  
HIGH VOLTAGE  
LOW VOLTAGE  
L2  
LO  
HI  
CCH ODF  
LM1 LM2 DFT1 DFT2 T1 T2 S2 S1 PW2 PW1  
O
C
1
P1  
18  
Second-stage latching can be selected by rotating the potentiom-  
eter (POT) to the desired outdoor second-stage latching tempera-  
ture (See Fig. 34.) The temperatures that can be selected are 85°,  
90°, 95°, 100°, and 105°F. The POT is factory set at 105°F.  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
FURN INT  
OFF  
ON  
SPEED-UP  
ZONE SELECTION  
STAGE 2 DEFROST BALANCE  
LATCH  
TIME  
POINT  
If the stage2 latch POT is set to ZONE position, the compressor  
operating speed in either heat or cool mode is determined by the  
Y1 and/or Y2 inputs. The system operates in low speed with a Y1  
input and high speed with Y2 or Y1-and-Y2 input. This allows the  
multistage-zoning system to determine what speed is needed  
regardless of outdoor temperature or switchover point.  
LED 1  
A93569  
Fig. 33Two-Speed Control Board  
TWO-MINUTE LOW-SPEED MINIMUM  
DEFROST TIME SELECTION  
The defrost interval can be field selected, depending on local or  
geographic requirements. It is factory set at 90 minutes and can be  
changed to either 30 or 50 minutes by rotating the defrost-time  
POT. (See Fig. 34.)  
If the unit has not operated within the past 30 minutes, the unit  
operates for a minimum of 2 minutes in low speed upon the next  
thermostat high or low demand.  
31—  
TABLE 15FUNCTION LIGHT CODE AND DISPLAY LOCATION  
CODE  
TSTAT  
UNIT  
DEFINITION  
*
POSSIBLE CAUSE  
Constant flash  
No pause  
No demand  
Stand by  
X
9
1 flash  
w/pause  
X
X
X
X
X
Low-speed operation  
High-speed operation  
Ambient thermistor failure  
Coil thermistor failure  
8
7
6
5
2 flashes  
w/pause  
3 flashes  
w/pause  
4 flashes  
w/pause  
X
Thermistor drift, wrong location  
Incorrect wiring  
Incorrect refrigerant charge  
Dirty indoor/outdoor coil  
3 flashes  
pause  
4 flashes  
X
X
Thermistor out of range**  
4
Dirty outdoor coil  
Refrigerant overcharge  
Wrong indoor coil  
5 flashes  
w/pause  
Pressure switch trip  
(LM1/LM2)  
X‡  
X
X
X
X
3
2
1
Low refrigerant charge  
Compressor mechanical problem  
Dirty indoor/outdoor coil  
6 flashes  
w/pause†  
Compressor PTCs out of limit  
Board failure  
Constant light  
No pause  
Equipment or electrical service  
not grounded  
X
No flash  
*Function light signals order of importance; in case of multiple-signal request, 1 is most important.  
Signal at thermostat will occur after 3 consecutive attempted restarts and lockout has occurred.  
Will be energized if pressure switch remains open for 1 hr.  
**Check both thermistors to determine which is faulty.  
FIELD-INITIATED FORCED DEFROST  
By placing a jumper across the speedup terminals for a minimum  
of 5 sec and then removing it, the unit initiates a defrost cycle. (See  
Fig. 34.) The cycle occurs only if the outdoor ambient is less than  
50°F, regardless of outdoor coil temperature. The cycle terminates  
when the coil thermistor reaches 80°F ( ± 5) or the defrost period  
reaches a maximum of 10 minutes.  
70  
60  
50  
40  
30  
20  
10  
HIGH SPEED  
BALANCE POINT  
FURNACE INTERFACE  
This feature provides a heat-pump lockout upon a demand for  
auxiliary heat (W2) and must be used when interfacing a heat  
pump with a gas/oil furnace. Field selection of the furnace-  
interface option is done by connecting the factory-supplied jumper  
to the ON position of the 3 terminal connectors. (See Fig. 33.)  
When the option is selected, the heat pump will be locked out of  
operation any time there is a thermostat demand for W2 or the  
outdoor ambient is below the balance-point POT-setting selection.  
(See Fig. 34.) When the unit requires defrost, auxiliary heat (W2)  
energizes the furnace. After defrost is terminated, the heat pump  
shuts down and the furnace satisfies the thermostat. To utilize this  
function, the economic and/or thermal balance point must be  
determined. See the appropriate heat pump balance-point work-  
sheet available from your distributor or branch.  
STRUCTURE  
BALANCE POINT  
LOW SPEED  
BALANCE POINT  
50  
60  
70  
80  
90  
100  
110  
120  
TEMPERATURE (°F)  
A91282  
BALANCE POINT  
Fig. 35Typical Cooling Balance Points  
DEFROST  
This feature can be used in 2 different options: furnace interface or  
electric-heat staging. Refer to the Furnace Interface section for its  
application. If the heat pump is installed with a fan coil with  
multistages of electric heat, this option can be used to stage the  
banks of heat by outdoor ambient. This eliminates the need for  
accessory outdoor thermostats.  
When using this option to stage electric heat, first stage is  
energized by a W2 demand, and second stage is energized by a W3  
demand. Select the W3 desired temperature by rotating the  
balance-point POT. (See Fig. 34.) Temperatures that may be  
selected are 10°, 15°, 20°, 25°, 30°, 35°, 40°, and 45°F. The POT  
is factory set at 45°F.  
LOW-SPEED HEATING WITH AUXILIARY HEAT  
If the system is operating in low-speed heating and there is a  
demand for auxiliary heat (W2), the system changes to high-speed  
operation. W2 is energized unless the low-voltage control wiring is  
configured as described in Fig. 36.  
The 2-speed control logic for the defrost function is the standard  
time and temperature initiated, time or temperature terminated.  
Defrost occurs only at outdoor temperatures less than 50°F. The  
control initiates defrost when the outdoor coil thermistor is 30°F (±  
2) or less, and the selected defrost time (interval) has been  
accumulated during unit operation. Termination occurs when the  
coil thermistor reaches 80°F (± 5) or the defrost period reaches a  
maximum of 10 minutes.  
Defrost always occurs in high speed unless the stage2 latch POT  
is set at ZONE. During defrost the unit operates in high speed,  
energizes the reversing valve (O) and auxiliary heat (W2), and  
de-energizes the outdoor fan. Upon termination, there is a 20-sec  
delay in the outdoor fan being energized. If the stage2 latch POT  
is set to ZONE and the heat pump is in low speed, it defrosts in low  
speed.  
32—  
PRESSURE SWITCH PROTECTION  
TWO SPEED  
THERMOSTAT  
FAN  
COIL  
TWO SPEED  
HEAT PUMP  
The outdoor unit is equipped with high- and low-pressure  
switches, wired in series. If a pressure switch opens, the control  
provides a 5-minute time delay in outdoor unit operation with the  
outdoor fan running. A malfunction signal appears on the control  
when a pressure switch opens. If the switch remains open for 1 hr  
or longer, a malfunction signal is provided at the L terminal of the  
indoor thermostat.  
W2  
W2  
W2  
CONTROL  
LOGIC  
W3  
W3  
A93572  
III. FACTORY DEFAULTS  
Fig. 36Low-Voltage Control Wiring  
AUXILIARY HEAT (W2) LOCKOUT  
Factory defaults have been provided in the event of failure of the  
ambient thermistor, outdoor-coil thermistor, and/or furnace inter-  
face jumper. Refer to Table 17 for default and function.  
In some areas, it is necessary to disable the auxiliary heat, except  
for defrost, until the outdoor ambient is less than the structures  
balance point. This is accomplished by using the low-voltage  
wiring as shown in Fig. 36. Wire the 24vac W2 signal from the  
indoor thermostat to W3 of the control, and W2 of the control to  
W2 of the indoor unit. When the outdoor ambient is less than the  
setting of the balance-point POT, the 24vac signal energizes the  
auxiliary heat (W2) of the indoor unit.  
IV. MAJOR COMPONENTS  
TWO-SPEED CONTROL  
The 2-speed control board controls the following functions:  
High- and low-compressor contactor operation  
Outdoor fan-motor operation  
Crankcase-heater operation  
Compressor protection  
EMERGENCY HEAT  
If the 2-speed control receives a call for auxiliary heat (W2)  
without a heat-pump heating (Y1) call, the second auxiliary stage  
(W3) is energized. This ensures all available heat is energized if  
the indoor thermostat is switched to emergency heat.  
Pressure-switch monitoring  
Second-stage latching  
COMPRESSOR PTC-OVERLOAD PROTECTION  
Time delays  
The control senses the resistance of the compressor internal  
positive-temperature coefficient (PTC) overloads. If the resistance  
of the PTCs is out of range, the control shuts off the unit until the  
resistance range is acceptable. See Table 16 for compressor PTC  
ranges.  
5-minute time-delay speedup (bypass)  
Heat pumps:  
Time/temperature defrost  
Defrost-interval selection  
Furnace interface  
TABLE 16COMPRESSOR PTC RANGES  
Electric-heat staging  
COMPRESSOR INTERNAL-PTC RESISTANCE  
HEADER-PIN HOUSING  
Safe Range (77°F)  
To trip  
1.5k to 7.8k ohms  
26k to 34k ohms  
8.4k to 10k ohms  
The header-pin housing is the plastic assembly which holds the  
stripped-lead ends for field connections. The 2-speed control  
receives the 24vac low-voltage control-system inputs through the  
housing/pins. The housing also contains jumpers which the control  
uses for system configuration, such as heat pump versus air  
conditioner. See Fig. 37 for header-pin housing configurations.  
To reset  
When the control turns off the outdoor unit due to out-of-range  
PTCs, the unit remains off for 15 minutes with the outdoor fan  
running. After 15 minutes, the control checks the resistance every  
5 minutes until it reaches the reset range. During this time, a  
malfunction signal appears on the control board. If this happens,  
remove the wires on control board at S1 and S2 and measure the  
resistance across the leads. When the resistance reaches 8,400 to  
10,000 ohms, system operation may be resumed. If the resistance  
remains outside this range, a quick check of the leads at the  
compressor should be made. Loose connections can cause inaccu-  
rate readings. If a PTC trip occurs 3 times, the control will lock out  
the outdoor-unit operation and provide malfunction signals at both  
the control and indoor thermostat.  
TWO-SPEED COMPRESSOR  
The 2-speed compressor contains motor windings that provide  
low-speed, 4pole (1750 rpm) and high-speed, 2pole (3500 rpm)  
operation. Refer to Fig. 38 to determine which windings are  
energized at each speed. Refer to Compressor Winding-Check  
section under Troubleshooting and Table 18 for appropriate  
winding resistances.  
The 2-speed compressor is also protected by an internal-pressure  
relief (IPR), which relieves discharge gas into the compressor shell  
(low side) when the differential between suction and discharge  
TABLE 17FACTORY DEFAULTS  
FUNCTION  
FAILED COMPONENT  
DEFAULT  
Crankcase Heater  
Energized during any off cycle  
Does not function  
Second-Stage Latching  
Balance point does not function, but  
interface still energizes furnace and  
locks out heat pump with a call for W2  
Furnace Interface  
Ambient Thermistor  
Unit only runs in high-  
compressor speed  
Heating Switchover Speed Point  
Defrost Initiation  
Defrost is initiated based on coil  
temperature only  
Outdoor Thermostat for  
Auxiliary Heat  
Anytime there is a call for W2,  
W3 is also energized.  
Defrost occurs at each time interval,  
but terminates after 5 minutes  
Outdoor Coil Thermistor  
Furnace Interface Jumper  
Defrost Initiation and Termination  
Furnace Interface  
Does not function  
33—  
pressures exceeds 500 psi. The compressor is also protected by 3  
PTC devices attached to the motor windings. The PTCs resistance  
is sensed by the 2-speed control board. See Table 16 for resistance  
ranges.  
C - TRANSFORMER COMMON  
R - TRANSFORMER LINE  
1
2
3
MECHANICALLY INTERLOCKED CONTACTORS  
4
The 2-speed products are equipped with mechanically interlocked  
contactors. Each contactor has interconnecting linkage, providing  
independent interlocks.  
The 2-speed control provides the electrical interlock. The contac-  
tors are supplied with 240v coils, which reduce the va require-  
ments of the low-voltage (24vac) control system.  
W2 - FIRST STAGE AUXILIARY HEAT  
O - REVERSING VALVE  
5
6
Y2 - SECOND STAGE COOLING/HEAT PUMP  
Y1 - FIRST STAGE COOLING/HEAT PUMP  
W3 - SECOND STAGE AUXILIARY HEAT  
L - MALFUNCTION LIGHT  
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
TEMPERATURE THERMISTORS  
Thermistors are electronic devices which sense temperature. As  
the temperature increases, the resistance decreases. Two ther-  
mistors are used to sense temperature: one senses outdoor ambient,  
and the other senses coil temperature (heat pump only). Refer to  
Fig. 39 for resistance values versus temperature.  
If the outdoor ambient thermistor should fail, a malfunction signal  
appears on the indoor thermostat and 2-speed control. The control  
does not initiate second-stage latching, crankcase heater is turned  
on during all off-cycles, heating defaults to high speed, and defrost  
initiates on demand from coil thermistor. (See Table 17.)  
4 - TON  
IF NO JUMPER IS  
INSTALLED, DEFAULT  
IS 3 - TON  
5 - TON  
JUMPER FOR  
HEAT PUMP ONLY  
A93576  
THERMISTOR CURVE  
Fig. 37Header-Pin Housing  
T3 T8  
T7 T2  
T1  
90  
80  
70  
60  
50  
40  
30  
20  
EXTERNAL MAIN  
10  
0
0
20  
40  
60  
80  
100  
120  
MAIN WINDING  
4 POLE START  
2 POLE START  
TEMPERATURE (DEG. F)  
A91431  
Fig. 39Resistance Values Versus Temperature  
If the outdoor coil thermistor should fail, a malfunction signal  
appears on the indoor thermostat and 2-speed control. The control  
defrosts every 90 minutes of heating operation and terminates in 5  
minutes. (See Table 17.)  
V. LED FUNCTION/MALFUNCTION LIGHTS  
HIGH SPEED  
(L1) T1 + T7  
(L2) T2 + T3  
LOW SPEED  
(L1) T1  
(L2) T7 + T8  
The 2-speed control is equipped with an LED function/ malfunc-  
tion light.  
NOTE: Only malfunction signal appears at thermostat. Both  
function and malfunction signals appear at control board. (See Fig.  
33 for LED location.) Table 15 provides the function/malfunction  
code, location, and definition.  
A92015  
Fig. 38Energizing Windings  
VI. TROUBLESHOOTING  
NOTE: Troubleshooting charts for air conditioning and heat  
pump units are provided in the back of this manual see Fig. 52,  
53, and 54.  
TABLE 18TWO-SPEED COMPRESSOR  
(WINDING RESISTANCE AT 70°F ± 2°)  
WINDING  
T1-T2  
3 TON  
0.80  
4 TON  
0.70  
5 TON  
COMPRESSOR WINDING CHECK  
0.60  
1.80  
1.00  
2.00  
The 2-speed compressor is nothing more than 2 single-phase  
motors within 1 compressor shell. When the compressor fails to  
start or run, there are 3 tests that can be made: open, ground, or  
short. This compressor has no internal line-break overload; how-  
ever, it does have PTC motor protectors. See Compressor PTC-  
Overload Protection section for PTC overload information.  
T1-T3  
3.20  
2.20  
T1-T7  
1.30  
1.00  
T1-T8  
3.10  
2.20  
34—  
NOTE: To ensure accurate ohm measurements, place ohmmeter  
probes on flat surface of compressor-terminal tabs, not the brass  
mounting screw.  
24v power. If the fault clears, check to ensure the indoor and  
outdoor unit and electrical service are properly grounded. If the  
entire system is grounded, the control board should be replaced, as  
the control is not field reparable. If the control-board light is  
flashing, see LED and Table 15 for function/malfunction defini-  
tion. Cycling 24 vac to control board resets previous error  
messages and any lockouts which have occurred. See Table 19 for  
more information regarding control-board operation.  
Open  
To determine if a winding has an actual break in the internal wires  
and current is unable to pass through:  
1. Be sure all power is off.  
CONTROL-BOARD POWER INPUTS AND OUTPUTS  
See Fig. 33 and 37 for inputs and outputs.  
BLEED RESISTOR  
2. Discharge all capacitors.  
3. Remove wires from terminals T1, T2, T3, T7, and T8.  
4. Use an ohmmeter on 0-1000 ohm scale to check resistance.  
(See Fig. 38, 40, and 41 and Table 18.)  
The bleed resistor is a 150k, 2watt resistor across the compressor-  
run capacitor to protect service technician from injury by electrical  
shock. Capacitor will bleed-off approximately 1 minute after  
power to outdoor unit is turned off. If run capacitor is changed out,  
be sure to place bleed resistor on new capacitor. If bleed resistor is  
damaged, replace resistor.  
Because winding resistances are usually less than 10 ohm, each  
reading will appear to be approximately zero ohm. If during any  
check the resistance remains at 1000 ohm, an open or break exists,  
and the motor or compressor should be replaced.  
Ground  
START CAPACITOR AND RELAY  
To determine if any wire has broken and come in direct contact  
with the housing or shell, causing a direct short to ground:  
The 2-speed system has a second start relay in the control box. One  
start relay is for low-speed start, and the second is for high-speed  
start. Both start relays use a common-start capacitor. When  
servicing this equipment, be certain system starts in both low- and  
high-speed operation.  
1. Be sure all power is off.  
2. Discharge all capacitors.  
3. Remove wires from T1, T2, T3, T7, and T8.  
REFRIGERATION SYSTEM  
I. REFRIGERATION CYCLE  
4. Allow crankcase heater to remain on for several hrs before  
checking motor to ensure that windings are not saturated  
with refrigerant.  
In a refrigeration system, refrigerant moves heat from one place to  
another. It is useful to understand flow of refrigerant in a system.  
5. Using an ohmmeter on R X 10,000 ohm scale, place 1 meter  
probe on groundmotor or compressor frame. Make a  
good metal-to-metal contact. Place other probe on terminals  
T1, T2, T3, T7, and T8 in sequence. Note meter scale.  
In a straight cooling system, compressed hot gas leaves compres-  
sor and enters condensing coil. As gas passes through condenser  
coil, it rejects heat and condenses into liquid. The liquid leaves  
condensing unit through liquid line and enters metering device at  
indoor coil. As it passes through metering device, it becomes a  
gas-liquid mixture. As it passes through indoor coil, it absorbs heat  
and refrigerant and is again compressed to a hot gas. The cycle  
then repeats.  
If any reading of zero or low resistance is obtained, the motor is  
grounding. Replace the compressor.  
Short  
NOTE: This is an extremely critical test and is not advised unless  
the following conditions are met.  
In a heat pump, the basic cycle is the same. (See Fig. 42.)  
Reversing valve in system decides which coil, indoor or outdoor,  
becomes evaporator or condenser. It rejects heat into the home  
after heat is absorbed by outdoor evaporator coil, thus the home is  
heated.  
The correct motor-winding resistances must be known before  
testing. See Table 18 for cold-motor winding resistance.  
The temperature of the windings must be specified, 70°F ± 2°F.  
The resistance-measuring instrument must have an accurate ohm-  
meter (such as a Wheatstone bridge or null balance-type instru-  
ment).  
In cooling cycle, the indoor coil becomes the evaporator. It absorbs  
heat from the home and rejects it through the outdoor condenser  
coil, thus the home is cooled.  
The motor must be dry or free from direct contact with liquid  
refrigerant.  
A unique feature of the heat pump is that metering devices are  
designed to meter refrigerant in one direction of flow and allow  
refrigerant to pass unhindered in the other direction. If indoor-  
metering device is metering refrigerant, the outdoor device by-  
passes refrigerant and vice versa. This allows both coils to serve a  
dual function.  
To determine if any wires have broken through their insulation and  
come in direct contact with each other, thereby shortingall or  
part of the winding(s):  
1. Be sure all power is off.  
2. Discharge all capacitors.  
II. LEAK DETECTION  
3. Remove wires from terminals T1, T2, T3, T7, and T8.  
CAUTION: Always wear safety glasses and gloves  
4. Subtract instrument probe and lead resistance from each  
reading. If any reading is within ± 20 percent of the known  
resistance from Table 18, the motor probably does not have  
a short. Usually a considerable difference will be noted if a  
turn-to-turn short is present.  
when handling refrigerants.  
New installations should be checked for leaks prior to complete  
charging.  
CONTROL BOARD FAILURE  
If a system has lost all or most of its charge, system must be  
pressurized again, up to approximately 150 lb minimum. This can  
be done by adding refrigerant using normal charging procedures,  
or it may be pressurized with nitrogen (less expensive than  
refrigerant). Nitrogen also leaks faster than R-22 and is not  
absorbed by refrigeration oil. Nitrogen cannot, however, be  
detected by a leak detector. (See Fig. 43.)  
The control board continuously monitors its own operation and the  
operation of the system. The diagnostic feature allows easy  
troubleshooting of the control and system in the field. If a failure  
occurs, the LED light on the control will flash a failure code. If the  
failure is internal to the control board, the light will stay on  
continuously (no flash). Before replacing control board, reset the  
35—  
SCHEMATIC DIAGRAM  
(LADDER FORM)  
L1  
L2  
C2  
C1  
C2  
11  
17  
21  
27  
24  
14  
T7  
COMP  
MAIN  
T2  
T1  
EXT  
LOW  
START  
HIGH  
SC  
BR  
MAIN  
START  
T8  
T3  
C2  
EQUIP  
GND  
H
F
2
5
15  
16  
25  
HS  
SR  
C2  
C1  
C1  
C
1
26  
22  
23  
CAP  
2
1
5
12  
13  
LS  
SR  
A91446  
Fig. 40Low-Speed Windings  
SCHEMATIC DIAGRAM  
(LADDER FORM)  
L1  
L2  
C2  
C1  
C2  
11  
17  
21  
27  
24  
14  
T7  
COMP  
T2  
MAIN  
T1  
EXT  
MAIN  
LOW  
START  
HIGH  
START  
SC  
T8  
T3  
C2  
EQUIP  
GND  
H
2
5
15  
16  
25  
26  
BR  
HS  
SR  
C2  
C1  
C1  
C
1
CAP  
F
2
1
5
12  
13  
22  
23  
LS  
SR  
A91445  
Fig. 41High-Speed Windings  
36—  
In all instances, when a leak is found, system charge must be bled  
down and leak repaired before final charging and operation. After  
leak testing or leak is repaired, evacuate system, and recharge with  
correct refrigerant charge.  
COOLING CYCLE  
REVERSING VALVE  
(ENERGIZED)  
OUTDOOR FAN  
INDOOR  
FAN  
INDOOR COIL  
ACCUMULATOR  
SUCTION SERVICE  
PORT AT SERVICE  
VALVE (CLG CYCLE)  
COMP  
STRAINER  
OUTDOOR  
COIL  
STRAINER  
SUCTION  
SERVICE  
PORT  
LIQUID LINE  
PRESSURE SWITCH  
(METERING)  
(BYPASSING)  
HEAT PUMP  
ACCESSORY  
FILTER DRIER  
(DUAL FLOW)  
LIQUID LINE SERVICE PORT  
AT SERVICE VALVE (CLG CYCLE)  
A88400  
Fig. 42Heat Pump Refrigerant-Flow Diagrams  
CAUTION: Due to the high pressure of nitrogen, it  
should never be used without a pressure regulator on the  
tank.  
Leaks in a system pressurized with refrigerant can be spotted with  
a leak detector that detects extremely small refrigerant leaks. This  
discussion assumes that system is pressurized with either all  
refrigerant or a mixture of nitrogen and refrigerant.  
If system has been operating for some time, make first check for  
a leak visually. Since refrigerant carries a small quantity of oil,  
traces of oil at any joint or connection are an indication that  
refrigerant is leaking at that point.  
A simple and inexpensive method of testing for leaks is to use soap  
bubbles. Any solution of water and soap may be used. Soap  
solution is applied to all joints and connections in system. A small  
pinhole leak is located by tracing bubbles in soap solution around  
leak.  
Use electronic leak detector to check for leaks. This unquestion-  
ably is the most efficient and easiest method for checking leaks.  
There are various types of electronic leak detectors. Generally  
speaking, they are all portable, and most are lightweight, consist-  
ing of a box with several switches and a probe or sniffer. Detector  
is turned on and probe is passed around all fittings and connections  
in system. Leak is detected by either a movement of a pointer on  
detector dial, by a buzzing sound, or a light.  
A88401  
Fig. 43Leak Detector  
III. BRAZING  
When brazing is required in the refrigeration system, certain basics  
should be followed:  
1. Clean joints make the best joints. To clean:  
a. Remove all oxidation from surfaces to a shiny finish  
before brazing.  
TABLE 1924V PIN CONNECTION TROUBLESHOOTING  
MODE OF OPERATION  
18-PIN CONNECTOR  
TERMINAL  
DESIGNATION  
LOCATION ON  
CONTROL BOARD  
VOLTAGE  
PATH  
VOLTAGE  
REQUIRED  
POSSIBLE SOURCE  
OF PROBLEM  
All  
R-C  
Y1,0-C  
Y1, Y2, 0-C  
Y1-C  
2-1  
8,6-1  
8,7,6-1  
8-1  
Input  
Input  
Input  
Input  
Input  
24  
24  
24  
24  
24  
Check transformer (secondary)  
Check thermostat  
Low-speed Cooling  
High-speed Cooling  
Low-speed Heating  
Check thermostat  
Check thermostat  
Y1-C  
8-1  
Check thermostat  
High-speed Heating  
Defrost  
Outdoor temperature below  
speed; change temperature  
Y2-C  
Y1-C  
7-1  
8-1  
Output  
Input  
24  
24  
24  
Check thermostat  
Outdoor temperature below 50°F;  
Coil temperature less than 30°F  
Y2, W2, 0-C  
7,5,6-1  
Output  
Y1, W2-C  
W3, Y2-C  
7,5-1  
9,8-1  
Input  
24  
24  
Check thermostat  
Second Stage of  
Auxiliary Heat  
Output  
Check balance-point setting  
Cooling Second-  
stage Latching  
Ambient thermistor failure;  
Check second-stage POT  
Y1, Y2, 0-C  
8,7,6-1  
Input  
24  
37—  
SERVICE PORT  
W/SCHRADER  
CORE  
STEM  
FIELD  
SIDE  
STEM  
SERVICE PORT  
W/SCHRADER CORE  
FIELD  
SIDE  
SEAT  
SEAT  
BAR STOCK FRONT SEATING VALVE  
FORGED FRONT SEATING VALVE  
A91447  
A91448  
Fig. 44Service Valves  
b. Remove all flux residue with brush and water while  
material is still hot.  
pressurized. To pressurize the service port, this valve must be  
moved off the back-seating position. This valve does not contain a  
Schrader fitting. Both types of service valves are designed for  
sweat connection to the field tubing.  
2. Use sil-fosor phos-copperfor copper-to-copper only.  
No flux is required.  
The service valves in the outdoor unit come from the factory  
front-seated. This means that the refrigerant charge is isolated from  
the line-set connection ports. Some heat pumps are shipped with  
sweat-adapter tube. This tube must be installed on the liquid-  
service valve. After connecting the sweat adapter to the liquid-  
service valve of a heat pump, the valves are ready for brazing. The  
interconnecting tubing (line set) can be brazed to the service valves  
using either silver-bearing or non-silver-bearing brazing material.  
Consult local codes.  
Before brazing the line set to the valves, the belled ends of the  
sweat connections on the service valves must be cleaned so that no  
brass plating remains on either the inside or outside of the bell  
joint. To prevent damage to the valve and/or cap Oring, use a  
wet cloth or other acceptable heat-sinking material on the valve  
before brazing. To prevent damage to the unit, use a metal barrier  
between brazing area and unit.  
3. Silver solder is used on copper-to-brass, copper-to-steel, or  
copper-to-copper. Flux is required when using silver solder.  
4. Fluxes should be used carefully. Avoid excessive applica-  
tion and do not allow fluxes to enter into the system.  
5. Proper brazing temperature of copper is when it is heated to  
a dull red color.  
This section on brazing is not intended to teach a technician how  
to braze. There are books and classes that teach and refine brazing  
techniques. The basic points above are listed only as a reminder.  
IV. SERVICE VALVES  
WARNING: Never attempt to make repairs to existing  
service valves. Unit operates under high pressure. Dam-  
aged seats and o-rings should not be replaced. Replace-  
ment of entire service valve is required. Tampering with  
damaged valves can cause personal injury or death.  
Service valve must be replaced by properly trained  
service technician.  
After the brazing operation and the refrigerant tubing and evapo-  
rator coil have been evacuated, the valve stem can be turned  
counterclockwise until it opens or back-seats, which releases  
refrigerant into tubing and evaporator coil. The system can now be  
operated.  
Back-seating service valves must be back-seated (turned counter-  
clockwise until seated) before the service-port caps can be re-  
moved and hoses of gage manifold connected. In this position,  
refrigerant has access from and through outdoor and indoor unit.  
The service valve-stem cap is tightened to 20 ± 2 ft/lb torque and  
the service-port caps to 9 ± 2 ft/lb torque. The seating surface of  
the valve stem has a knife-set edge against which the caps are  
tightened to attain a metal-to-metal seal. If accessory pressure  
switches are used, the service valve must be cracked. Then, the  
knife-set stem cap becomes the primary seal.  
Service valves provide a means for holding original factory charge  
in outdoor unit prior to hookup to indoor coil. They also contain  
gage ports for measuring system pressures and provide shutoff  
convenience for certain types of repairs. (See Fig. 44.)  
Two types of service valves are used in outdoor residential  
equipment. The first type is a front-seating valve, which has a  
service port that contains a Schrader fitting. The service port is  
always pressurized after the valve is moved off the front-seat  
position.  
The service valve cannot be field-repaired; therefore, only a  
complete valve or valve stem and service-port caps are available  
for replacement.  
The second type is a combination front-seating/back-seating valve,  
which has a metal-to-metal seat in both the open and closed  
positions. When it is fully back-seated, the service port is not  
38—  
PISTON BODY  
FEEDER  
TUBES  
PISTON  
(ORIENT AS SHOWN)  
STRAINER  
BRASS  
HEX NUT  
PISTON  
PISTON RETAINER  
FLARE ADAPTER  
INTERNAL STRAINER  
TEFLON  
SEAL  
PISTON  
RETAINER  
BRASS  
HEX  
BODY  
PRODUCTION  
EXCEPT 1992  
A91138  
A94004  
Fig. 45Check-Flo-RaterComponents  
If the service valve is to be replaced, a metal barrier must be  
inserted between the valve and the unit to prevent damaging the  
unit exterior from the heat of the brazing operations.  
5. Slide piston out by inserting a small, soft wire with small  
kinks through metering hole. Do not damage metering hole,  
sealing surface around piston cones, or fluted portion of  
piston.  
CAUTION: Wear safety glasses and gloves when han-  
dling refrigerants.  
6. Clean piston refrigerant-metering hole.  
7. Install a new retainer O-ring or retainer assembly before  
reassembling bypass-type Check-Flo-Rater.  
RELIANT AND CUBE PRODUCTS PRODUCED IN 1992  
Pumpdown Procedure  
1. Shut off power to unit.  
Service valves provide a convenient shutoff valve useful for  
certain refrigeration-system repairs. System may be pumped down  
to make repairs on low side without losing complete refrigerant  
charge.  
2. Reclaim outdoor-unit refrigerant.  
3. Loosen brass hex nut and remove line from brass hex body.  
4. Slide piston out by inserting a small, soft wire with small  
kinks through metering hole. Do not damage metering hole,  
sealing surface around piston cones, or fluted portion of  
piston.  
1. Attach pressure gage to suction service-valve gage port.  
2. Front seat liquid-line valve.  
5. Clean piston refrigerant-metering hole.  
6. Always replace Teflon seal with new seal. Never try to  
reuse old seals.  
3. Start unit in cooling mode. Run until suction pressure  
reaches 5 psig (35kPa). Do not allow compressor to pump  
to a vacuum.  
7. Reassemble brass nut and brass hex body. Be sure orienta-  
tion is as shown in Fig. 45.  
4. Shut unit off. Front seat suction valve.  
NOTE: All outdoor unit coils will hold only factory-supplied  
amount of refrigerant. Excess refrigerant, such as in long-line  
applications, may cause unit to relieve pressure through internal  
pressure-relief valve (indicated by sudden rise of suction pressure)  
before suction pressure reaches 5 psig (35kPa). If this occurs, shut  
off unit immediately, front seat suction valve, and recover remain-  
ing pressure.  
VI. REVERSING VALVE  
In heat pumps, changeover between heating and cooling modes is  
accomplished with a valve that reverses flow of refrigerant in  
system. (See Fig. 46.) This reversing-valve device is easy to  
troubleshoot and replace. The reversing-valve solenoid can be  
checked with power off with an ohmmeter. Check for continuity  
and shorting to ground. With control-circuit (24v) power on, check  
for correct voltage at solenoid coil. Check for overheated solenoid.  
With unit operating, other items can be checked, such as frost or  
condensate water on refrigerant lines.  
The sound made by a reversing valve as it begins or ends defrost  
is a whooshingsound, as the valve reverses and pressures in  
system equalize. An experienced service technician detects this  
sound and uses it as a valuable troubleshooting tool.  
Using a remote measuring device, check inlet and outlet line  
temperatures. DO NOT touch lines. If reversing valve is operating  
normally, inlet and outlet temperatures on appropriate lines should  
be close. Any difference would be due to heat loss or gain across  
valve body. Temperatures are best checked with a remote-reading,  
electronic-type thermometer with multiple probes. Route thermo-  
couple leads to inside of coil area through service-valve mounting-  
plate area underneath coil. Fig. 47 and 48 show test points (TP) on  
reversing valve for recording temperatures. Insulate points for  
more accurate reading.  
V. CHECK-FLO-RATER™  
(BYPASS-TYPE)  
HEAT  
HOLE  
PUMPS ONLY REFRIGERANT-METERING  
THROUGH IT. THE RETAINER FORMS A STOP FOR  
PISTON IN REFRIGERANT-BYPASS MODE AND A SEAL-  
ING SURFACE FOR LIQUID-LINE FLARE CONNECTION.  
(SEE FIG. 45.) TO CHECK, CLEAN, OR REPLACE PIS-  
TON:  
RELIANT PRODUCTS EXCEPT 1992 PRODUCTION  
1. Shut off power to unit.  
2. Pump unit down using pumpdown procedure described in  
this service manual.  
3. Loosen nut and remove liquid-line flare connection from  
Check-Flo-Rater.  
4. Pull retainer out of body, being careful not to scratch  
flare-sealing surface. If retainer does not pull out easily,  
carefully use locking pliers to remove it.  
39—  
NEW SOLENOID COIL  
3 PORT DESIGN  
A91457  
4TH PORT  
4 PORT DESIGN  
A91456  
Fig. 46Reversing Valve  
If valve is defective:  
5. Use slip couplings to install new valve with stubs back into  
system. Even if stubs are long, wrap valve with a wet rag to  
prevent overheating.  
1. Shut off all power to unit and remove all charge from  
system.  
6. After valve is brazed in, check for leaks. Evacuate and  
charge system. Operate system in both modes several times  
to be sure valve functions properly.  
2. Check valve design. If valve is of the 3-port design and new  
replacement is of the 4-port design, replacement of the  
solenoid coil and wire leads is necessary. Valve bodies are  
interchangeable, but solenoid and wires are not. Three-port  
reversing valve and solenoid coil with leads must be used  
together. New solenoid coil cannot be used on a 3-port  
valve.  
FROM INDOOR COIL VIA  
SERVICE VALVE ON  
OUTDOOR COIL  
TO OUTDOOR  
COIL  
TO  
Four-port reversing valve uses solenoid with quick-connect  
terminals for leads connection. Old solenoid coil cannot be  
used on 4-port reversing valve. If for any reason a new wire  
cord is not available, cut the leads on the old solenoid coil  
as close to the coil as possible. Terminate the leads with 2  
female 1/4-in. quick-connects. Connect terminals to new  
solenoid and tape connection to insulate and provide  
moisture barrier. Replace these wires as soon as wire cord  
is available. See RCD (Replacement Component Catalog)  
for proper cord part number.  
ACCUMULATOR  
TP-4  
TP-3  
TP-2  
TP-1  
3. Remove solenoid coil from valve body. Remove valve by  
cutting it from system with tubing cutter. Repair person  
should cut in such a way that stubs can be easily rebrazed  
back into system. Do not use hacksaw. This introduces  
chips into system that cause failure. After defective valve is  
removed, wrap it in wet rag and carefully unbraze stubs.  
Save stubs for future use. Because defective valve is not  
overheated, it can be analyzed for cause of failure when it  
is returned.  
FROM COMPRESSOR  
DISCHARGE LINE  
A88342  
Fig. 47Reversing Valve (Cooling Mode or Defrost  
Mode, Solenoid Energized)  
VII. THERMOSTATIC-EXPANSION VALVES (TXV)  
The types of TXVs used in condensing-unit and heat-pump  
systems are as follows:  
4. Braze new valve onto used stubs. Keep stubs oriented  
correctly. Scratch corresponding matching marks on old  
valve and stubs and on new valve body to aid in lining up  
new valve properly. When brazing stubs into valve, protect  
valve body with wet rag to prevent overheating.  
Rapid-Pressure Balance (RPB)Has a special bleed port that  
allows rapid bleed-through of pressure after system shutdown until  
pressure equalization occurs within approximately 1 to 2 minutes.  
40—  
TABLE 20TXV SUPERHEAT SETTING AT OUTLET OF EVAPORATOR COIL  
INSTALLATION  
Field Accessory  
TXV TYPE  
RPB/HSO  
RPB/HSO  
HSO  
PRODUCT USAGE  
Air Conditioner Indoor Unit  
Heat Pump Indoor Unit  
Indoor Fan Coil Unit  
SUPERHEAT SETTING  
10°  
6°  
Field Accessory  
Field Accessory/Factory-Installed  
Factory-Installed  
6°  
HSO  
2-Speed Heat Pump Outdoor Unit  
2-Speed Indoor Unit  
4°  
Factory-Shipped/Field-Installed  
HSO  
4°  
increased leaving evaporator pressure, which is transferred  
via the equalizer tube to the underside of the diaphragm.  
This tends to cause the pin-Bryant spring pressure to close  
the valve. The refrigerant flow is effectively stabilized to  
the load demand with negligible change in superheat. The  
bi-flow TXV is used on split-system heat pumps. In the  
cooling mode, the TXV operates the same as the standard  
TXV previously explained. (See Fig. 49.)  
TO  
FROM  
TO INDOOR COIL  
VIA SERVICE VALVE  
ON OUTDOOR COIL  
ACCUMULATOR  
OUTDOOR  
COIL  
INSULATE  
FOR  
TP-2  
ACCURATE  
READING  
TP-4  
TP-3  
However, when the system is switched to the heating mode  
of operation, the refrigerant flow is reversed. The bi-flow  
TXV has an additional internal-check valve and external  
tubing. (See Fig. 50.) These additions allow the refrigerant  
to bypass the TXV when refrigerant flow is reversed with  
only a 1- to 2-psig pressure drop through the device. When  
the heat pump switches to the defrost mode, the refrigerant  
flows through a completely open (unthrottled) TXV, and  
the bulb senses the residual heat of the outlet tube of the coil  
that had been operating in the heating mode (about 85°F  
and 155 psig). This temporary, unthrottled valve decreases  
the indoor-pressure drop, which in turn increases the  
refrigerant-flow rate, decreases overall defrost time, and  
enhances defrost efficiency.  
INSULATE FOR  
ACCURATE  
READING  
TP-1  
FROM COMPRESSOR  
DISCHARGE LINE  
ELECTRONIC  
THERMOMETER  
A88341  
Fig. 48Reversing Valve (Heating Mode, Solenoid De-  
IX. COIL REMOVAL  
Energized)  
Coils on this family of units are easy to remove, if required for  
compressor removal or replacement coil.  
Hard Shutoff (HSO)Has no bleed port and allows no bleed-  
through after system shutdown. No pressure equalization occurs.  
Because of unequalized system pressures, a start capacitor and  
relay must be installed on single-phase reciprocating compressors  
to start the compressor.  
CAUTION: Wear safety glasses and gloves when han-  
dling refrigerants.  
See Table 20 for TXV superheat settings. These settings are  
factory set and are not field adjustable. Table 17 settings are for  
Bryant-approved accessories and factory-installed TXVs only.  
To remove or replace coil:  
1. Shut off all power to unit.  
VIII. THERMOSTATIC-EXPANSION VALVE (BI-FLOW  
TXV)  
2. Remove and recover refrigerant from system through ser-  
vice valves.  
The standard TXV is a metering device that is used in condensing  
and heat pump systems to adjust to changing load conditions by  
maintaining a preset superheat temperature at the outlet of the  
evaporator coil. The volume of refrigerant metered through the  
valve seat is dependent upon:  
3. Remove top cover. (See Remove Top Cover section.)  
4. Remove screws in base pan to coil grille.  
5. Remove coil grille from unit.  
6. Remove screws on corner-post (Reliant) service-valve  
panel (Cube unit) holding coil-tube sheet.  
1. Superheat temperature sensed by cap-tube sensing bulb on  
suction tube at outlet of evaporator coil. As long as this bulb  
and cap tube contains some liquid refrigerant, this tempera-  
ture is converted into suction pressure pushing downward  
on the diaphragm, which tends to open the valve via the  
pushrods.  
CAUTION: Cut tubes to reduce the possibility of fire  
and personal injury.  
2. The suction pressure at the outlet of the evaporator coil is  
transferred via the external equalizer tube to the underside  
of the diaphragm.  
7. Use midget-tubing cutter to cut liquid and vapor lines at  
both sides of coil. Cut in convenient location for easy  
reassembly with copper-slip couplings.  
3. The needle valve on the pin Bryant is spring-loaded, which  
also exerts pressure on the underside of the diaphragm via  
the pushrods, which tends to close the valve. Therefore,  
bulb pressure equals evaporator pressure (at outlet of coil)  
plus spring pressure. If the load increases, the temperature  
increases at the bulb, which increases the pressure on the  
topside of the diaphragm, which pushes the pin Bryant  
away from the seat, opening the valve and increasing the  
flow of refrigerant. The increased refrigerant flow causes  
8. Lift coil vertically from basepan. Place aside carefully.  
9. Reverse procedure to reinstall coil.  
X. LIQUID-LINE STRAINER (HEAT PUMPS ONLY)  
The liquid-line strainer is upstream of the heating piston. The  
strainer catches debris in the liquid line during heating mode. If it  
becomes plugged, system operation and pressure become abnor-  
mal, and the compressor may become hot and cycle off on the  
overloads or pressure relief.  
41—  
CAPILLARY TUBE  
DIAPHRAGM  
BYPASS TXV  
PUSHRODS  
FEEDER TUBES  
INLET  
COIL  
OUTLET  
NEEDLE  
VALVE  
SPRING  
DISTRIBUTOR  
BULB  
CHECK VALVE  
(CLOSED)  
EXTERNAL EQUALIZER TUBE  
BYPASS TUBE  
A88406  
Fig. 49TXV in Cooling Mode  
CAPILLARY TUBE  
DIAPHRAGM  
BYPASS TXV  
PUSHRODS  
FEEDER TUBES  
INLET  
COIL  
OUTLET  
NEEDLE  
VALVE  
SPRING  
DISTRIBUTOR  
BULB  
CHECK VALVE  
(OPEN)  
EXTERNAL EQUALIZER TUBE  
BYPASS TUBE  
A88405  
Fig. 50TXV in Heating Mode  
42—  
If the strainer must be replaced, shut off all power to the unit. See  
Fig. 49 for strainer location.  
XI. ACCUMULATOR  
The accumulator is a device always found in heat pumps and found  
in some condensing-unit models. Under some light-load condi-  
tions on indoor coils and on outdoor coil with heat pump in heating  
mode, some liquid refrigerant is present in suction gas returning to  
compressor. The accumulator stores liquid and allows it to boil off  
into a vapor so it can be safely returned to compressor. Since a  
compressor is designed to pump refrigerant in its gaseous state,  
introduction of liquid into it could cause severe damage or total  
failure of compressor.  
The accumulator is a passive device which seldom needs replac-  
ing. Occasionally, its internal oil-return orifice or bleed hole may  
become plugged. Some oil is contained in refrigerant returning to  
compressor. It cannot boil off in accumulator with liquid refriger-  
ant. The bleed hole allows a small amount of oil and refrigerant to  
enter the return line where velocity of refrigerant returns it to  
compressor. If bleed hole plugs, oil is trapped in accumulator, and  
compressor will eventually fail from lack of lubrication. If bleed  
hole is plugged, accumulator must be changed. Bleed hole is so  
tiny that cleaning efforts are usually not successful. The accumu-  
lator has a fusible element located in the bottom-end bell. (See Fig.  
51.) This fusible element melts at 430°F and vents the refrigerant,  
if this temperature is reached either internal or external to the  
system. If fuse melts, the accumulator must be replaced.  
430° FUSE  
ELEMENT  
A88410  
Fig. 51Accumulator  
1. Pump the system down to 28 in. of mercury vacuum and  
allow pump to continue to operate for additional 15  
minutes.  
2. Close service valves and shut off vacuum pump.  
To change accumulator:  
3. Connect a refrigerant cylinder to the system and open until  
system pressure is 2 psig.  
1. Shut off all power to unit.  
2. Remove and reclaim all refrigerant from system.  
NOTE: Coil may be removed for access to accumulator. Refer to  
appropriate sections of service manual for instructions.  
4. Close the service valve.  
5. Allow system to stand for 1 hr, during which time the dry  
refrigerant will be able to diffuse throughout the system,  
absorbing moisture.  
CAUTION: Wear safety glasses and gloves when work-  
ing on refrigerants and when using brazing torch.  
This procedure is repeated 3 times, after which the system will be  
free of any contaminants and water vapor.  
XIII. SYSTEM CHARGING  
3. When accumulator is exposed, remove it from system with  
tubing cutter.  
For all approved combinations, system must be charged correctly  
for normal system operation and reliable operation of components.  
4. Scratch matching marks on tubing stubs and old accumu-  
lator. Scratch matching marks on new accumulator. Un-  
braze stubs from old accumulator and braze into new  
accumulator.  
CAUTION: Always wear safety glasses and gloves  
when handling refrigerants.  
5. Thoroughly rinse any flux residue from joints and paint  
with corrosion-resistant coating such as zinc-rich paint.  
If system has lost all charge, weigh in charge using dial-a-charge  
or digital scale.  
6. Reinstall accumulator into system with copper-slip cou-  
plings.  
7. Evacuate and charge system.  
8. Pour and measure oil quantity (if any) from old accumula-  
tor. If more than 20 percent of oil charge is trapped in  
accumulator, add oil to compressor to make up for this loss.  
System charge should be fine-tuned by using the superheat or  
subcooling method, whichever is appropriate. These methods are  
covered in the Checking Charge section below.  
NOTE: Heat-pump check charts are for checking charge and  
performance and for adding a small amount of charge. During  
heating mode, correct method of charging is the weight method. In  
heating mode, check should be made approximately 15 minutes  
after a defrost with unit running with a clean coil. In cooling cycle,  
system should run at least 10 minutes for temperatures and  
pressures to stabilize. All charts assume there are no system  
abnormalities and indoor coil airflows are correct. If system  
abnormalities exist, correct them before checking system charge.  
XII. CONTAMINANT REMOVAL  
Proper evacuation of a unit removes non-condensibles and assures  
a tight, dry system before charging. The 2 methods used to  
evacuate a system are the deep-vacuum method and the triple-  
evacuation method.  
DEEP-VACUUM METHOD  
The deep-vacuum method requires a vacuum pump capable of  
pulling a vacuum of 1000 microns and a vacuum gage capable of  
accurately measuring this vacuum depth. The deep-vacuum  
method is the most positive way of assuring a system is free of air  
and liquid water.  
XIV. CHECKING CHARGE  
Superheat charging is the process of charging refrigerant into a  
system until the temperature (superheat) of the suction gas entering  
the compressor reaches a prescribed value. Small variations of  
charge affect suction-gas superheat temperatures greatly. There-  
fore, this method of charging is very accurate. This method can be  
used only on split-system condensing units and heat pumps  
(operating in the cooling mode) with fixed-restrictor-type metering  
devices such as Check-Flo-Rater, cap tube, etc. For units using  
TRIPLE-EVACUATION METHOD  
The triple-evacuation method can be used where the vacuum pump  
is capable of pumping down to only 28 in. of mercury vacuum, and  
the system does not contain any liquid water. The procedure is as  
follows.  
43—  
TABLE 21SUPERHEAT CHARGING TABLE  
INDOOR COIL ENTERING AIR TEMP (°F WET BULB)  
OUTDOOR TEMP (°F)  
50  
9
52  
12  
10  
6
54  
14  
12  
10  
7
56  
17  
15  
13  
10  
6
58  
20  
18  
16  
13  
9
60  
23  
21  
19  
16  
12  
8
62  
26  
24  
21  
19  
15  
12  
8
64  
29  
27  
24  
21  
18  
15  
11  
9
66  
32  
30  
27  
24  
21  
18  
15  
13  
10  
8
68  
35  
33  
30  
27  
24  
21  
19  
16  
14  
12  
9
70  
37  
35  
33  
30  
28  
25  
22  
20  
18  
15  
13  
11  
8
72  
40  
38  
36  
33  
31  
28  
26  
24  
22  
20  
17  
15  
14  
74  
42  
40  
38  
36  
34  
31  
30  
27  
25  
23  
22  
20  
18  
76  
45  
43  
41  
39  
37  
35  
33  
31  
29  
27  
26  
25  
23  
55  
60  
7
65  
70  
75  
80  
5
85  
90  
5
95  
6
100  
105  
110  
115  
5
6
Where a dash appears, do not attempt to charge system under these conditions or refrigerant slugging may occur.  
TABLE 22REQUIRED VAPOR TEMPERATURE (°F)  
VAPOR PRESSURE AT SERVICE PORT (PSIG)  
79.2  
SUPERHEAT TEMP  
(°F)  
61.5  
35  
37  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
64.2  
37  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
67.1  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
70.0  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
73.0  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
76.0  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
82.4  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
85.7  
0
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
91  
2
4
6
8
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
36  
38  
40  
a TXV, the subcooling method must be used. Heat pumps must be  
operating in the cooling mode. To charge by superheat, a service  
technician needs an accurate superheat thermocouple or  
thermistor-type thermometer, a sling psychrometer, and a gage  
manifold. Do not use mercury or small-dial-type thermometers as  
they are not adequate for this type of measurement. Then use 1 of  
the following procedures:  
5. Measure indoor-air (entering indoor coil), wet-bulb tem-  
perature with a sling psychrometer.  
6. Locate outdoor temperature and evaporator entering air  
wet-bulb temperature in Table 21. At this intersection note  
the superheat.  
7. Locate superheat temperature located in previous step and  
vapor pressure in Table 22. At this intersection note  
vapor-line temperature.  
SUPERHEAT CHARGING METHOD  
8. If unit has a higher vapor-line temperature than charted  
temperature, add refrigerant until charted temperature is  
reached.  
1. Operate a unit a minimum of 10 minutes before checking  
charge.  
2. Measure vapor pressure by attaching a gage to vapor  
valve-service port.  
9. If unit has a lower vapor-line temperature than charted  
temperature, bleed refrigerant until charted temperature is  
reached.  
3. Measure vapor-line temperature by attaching a service  
thermometer to unit vapor line near vapor valve. On a heat  
pump, attach to the suction tube between the accumulator  
and the compressor. Insulate thermometer for accurate  
readings.  
10. If outdoor-air temperature or pressure at vapor valve  
changes, charge to new vapor-line temperature indicated on  
chart.  
SUBCOOLING CHARGING METHOD  
1. Operate unit a minimum of 15 minutes before checking  
charge.  
4. Measure outdoor-air, dry-bulb temperature with a second  
thermometer.  
44—  
TABLE 23SUBCOOLING AT LIQUID-SERVICE VALVE FOR UNITS PRODUCED THROUGH DECEMBER, 1992  
RELIANT AIR CONDITIONERS  
598A 598A  
Model  
590A  
591A/592A  
593A/594A  
593B  
593C  
594C  
595A 596A 597A 597B  
High  
Low  
Series  
014  
018  
024  
030  
036  
038  
042  
048  
060  
A
B
C
A
B
C
D
A
6
7
8
6
B
6
7
8
6
C
D
A
B
A
B
9
A
B
A
A
8
A
A
A
A
9
14 14  
17 17  
13 13  
15 15  
13 12  
14 14 14  
14 14 14  
17 17 17  
11  
13  
9
11  
10  
12  
15  
11  
12  
13  
11  
14  
15  
11  
11  
12  
12  
12  
9
16 21 12  
15 15 14  
13 12 16  
13  
10  
14  
11  
10  
12  
9
9
10 10  
10 13 11  
16 16 16  
12 12  
5
9
13  
11  
10  
16  
11  
18  
11  
13  
17  
16  
21  
14  
19  
9
13 13 14 16 19 19 15 12 12  
15 14  
19 22  
18 14 18  
18 18 18  
14 14  
14 14  
9
RELIANT HEAT PUMPS  
698A  
Model  
690A  
691A/692A  
693A/694A  
693B  
693C  
694C  
697A  
697B  
Cooling  
Heating  
High  
A
Low  
A
High  
A
Low  
A
Series  
014  
018  
024  
030  
036  
042  
048  
060  
A
B
C
D
14  
A
B
A
B
A
A
9
A
7
A
9
A
7
7
7
16  
16  
20  
14  
18  
19  
13  
16  
16  
20  
14  
18  
14  
13  
11  
11  
10  
10  
15  
13  
14  
11  
11  
10  
10  
15  
13  
14  
10  
13  
11  
11  
12  
10  
11  
10  
10  
12  
11  
7
7
15  
18  
21  
18  
18  
13  
18  
13  
22  
23  
18  
18  
13  
18  
11  
17  
23  
18  
18  
13  
18  
11  
15  
23  
6
5
11  
9
10  
13  
10  
15  
15  
10  
12  
12  
12  
10  
9
12  
18  
11  
10  
12  
9
14  
14  
25  
22  
9
CUBE UNITAIR CONDITIONERS  
CUBE UNITHEAT PUMPS  
HORIZONTAL AIR CONDITIONERS  
MODEL  
561A/571A  
661A/671A  
566D  
566E  
A
Series  
014  
018  
024  
030  
036  
042  
048  
060  
A
B
A
11  
14  
9
B
14  
8
C
D
12  
15  
14  
12  
18  
18  
16  
11  
12  
16  
17  
17  
21  
10  
12  
17  
19  
10  
7
11  
7
12  
10  
2. Measure liquid service-valve pressure by attaching an  
accurate gage to the service port.  
cally on this equipment. The frequency with which maintenance is  
performed is dependent on such factors as hours of operation,  
geographic location, and local environmental conditions.  
3. Measure the liquid-line temperature by attaching an accu-  
rate thermistor-type or electronic thermometer to the liquid  
line near the outdoor coil.  
WARNING: Disconnect all electrical power to unit  
before performing any maintenance or service on outdoor  
unit. Remember to disconnect power supply to air handler  
as this unit supplies low-voltage power to the outdoor  
unit. Electric shock can cause personal injury or death.  
4. Refer to unit-rating plate to find required subcooling  
temperature for units produced during or after January  
1993. For units produced through December 1992, refer to  
Table 23. Find the point at which the required subcooling  
temperature intersects the measured liquid service-valve  
pressure on Table 24.  
The minimum maintenance that should be performed on this  
equipment is as follows.  
5. To obtain the required subcooling temperature at a specific  
liquid-line pressure, add refrigerant if liquid-line tempera-  
ture is higher than indicated or remove refrigerant if  
temperature is lower. Allow a tolerance of 3°F.  
1. Check outdoor coil for cleanliness each month during the  
heating (heat pump only) or cooling season and clean as  
necessary, but clean at least once each heating (heat pump  
only) and cooling season.  
CARE AND MAINTENANCE  
To assure high performance and minimize possible equipment  
malfunction, it is essential that maintenance be performed periodi-  
2. Check fan motor and blade for cleanliness each heating and  
cooling season and clean as necessary.  
45—  
TABLE 24REQUIRED LIQUID-LINE TEMPERATURE  
REQUIRED SUBCOOLING TEMPERATURE (°F)  
PRESSURE (PSIG)  
AT SERVICE FITTING  
0
5
10  
66  
15  
61  
20  
56  
25  
51  
134  
141  
148  
156  
163  
171  
179  
187  
196  
205  
214  
223  
233  
243  
253  
264  
274  
285  
297  
309  
321  
331  
346  
359  
76  
71  
79  
74  
69  
64  
59  
54  
82  
77  
72  
67  
62  
57  
85  
80  
75  
70  
65  
60  
88  
83  
78  
73  
68  
63  
91  
86  
81  
76  
71  
66  
94  
89  
84  
79  
74  
69  
97  
92  
87  
82  
77  
72  
100  
103  
106  
109  
112  
115  
118  
121  
124  
127  
130  
133  
136  
139  
142  
145  
95  
90  
85  
80  
75  
98  
93  
88  
83  
78  
101  
104  
107  
110  
113  
116  
119  
122  
125  
128  
131  
134  
137  
140  
96  
91  
86  
81  
99  
94  
89  
84  
102  
105  
108  
111  
114  
117  
120  
123  
126  
129  
132  
135  
97  
92  
87  
100  
103  
106  
109  
112  
115  
118  
121  
124  
127  
130  
95  
90  
98  
93  
101  
104  
107  
110  
113  
116  
119  
122  
125  
96  
99  
102  
105  
108  
111  
114  
117  
120  
3. Check electrical connections for tightness and controls for  
proper operation each heating (heat pump only) or cooling  
season and service as necessary.  
3. Check fan-blade setscrew for tightness.  
4. Reinstall fan motor and blade to top cover and check for  
alignment.  
5. Reinstall top cover and position blade as per Fig. 24.  
6. Reconnect electrical power and check for proper operation.  
CAUTION: Because of possible damage to the equip-  
ment or personal injury, maintenance should be per-  
formed by qualified personnel only.  
ELECTRICAL CONTROLS AND WIRING  
1. Disconnect power to both the outdoor and indoor units.  
COIL CLEANING  
2. Check all electrical connections for tightness. Tighten all  
screws on electrical connections. If any connections appear  
to be burned or smoky, disassemble the connection, clean  
all parts and stripped wires, and reassemble. Use a new  
connector if old one is burned or corroded and crimp  
tightly.  
1. Remove top cover. See Remove Top Cover section.  
CAUTION: Coil fin damage can result in higher oper-  
ating costs or compressor damage. Do not use flame,  
high-pressure water, steam, or volatile or corrosive clean-  
ers on fins or tubing.  
3. Reconnect electrical power to the indoor and outdoor units  
and observe unit through 1 complete operating cycle.  
2. Clean coil using vacuum cleaner and its crevice tool. Move  
crevice tool vertically, close to area being cleaned, making  
sure tool touches only the dirt on the fins and not the fins.  
To prevent fin damage, do not scrub fins with tool or move  
tool horizontally against fins.  
4. If there are any discrepancies in the operating cycle,  
troubleshoot to find the cause, and correct.  
REFRIGERANT CIRCUIT  
1. Check the refrigerant charge using the superheat or sub-  
cooling method, whichever is applicable. If low on charge,  
check unit for leaks using an electronic leak detector.  
3. If oil deposits are present, spray coil with ordinary house-  
hold detergent. Wait 10 minutes, and proceed to next step.  
4. Using garden hose, spray coil vertically downward with  
constant stream of water at moderate pressure. Keep nozzle  
at a 15° to 20° angle, about 3 in. from coil face and 18 in.  
from tube. Spray so debris is washed out of coil and  
basepan.  
2. If any leaks are found, recover or isolate charge (pump-  
down) if applicable and make necessary repairs.  
3. Evacuate, recharge, and operate unit through entire cycle.  
FINAL CHECKOUT  
After the unit has been operating, the following items should be  
checked:  
5. Restore power to unit.  
CLEANING OUTDOOR FAN MOTOR AND BLADE  
1. Check that unit operational noise is not excessive due to  
vibration of components, tubing, panels, etc. If present,  
isolate problem and correct.  
1. Remove fan motor and blade. Refer to Remove Fan-Motor  
Assembly section of this manual. Be careful not to bend or  
dent fan blade.  
2. Check to be sure caps are installed on service valves and  
that they are tight.  
2. Clean motor and blade with soft brush or cloth. Be careful  
not to disturb balance weights on fan blade.  
46—  
3. Check to be sure tools, loose parts, and debris are removed  
from the unit.  
3. Addition of coastal filter (see pre-sale literature for acces-  
sory listing).  
4. Check to be sure all panels and screws are in place and  
tight.  
Special maintenance requirements are as follows:  
1. Frequent inspection of coil and base pan, especially after  
storms and/or high winds.  
Desert and Seacoast Locations  
Special consideration must be given to the installation and main-  
tenance of condensing units and heat pumps installed in seacoast  
or desert locations. Salt and the alkali content of the sand adhere  
to the aluminum fins of the coil and can cause premature coil  
failure due to corrosion.  
2. Cleaning coil by flushing out sand from between coil fins  
and out of base pan as frequently as inspection determines  
necessary.  
3. Protecting the unit in off seasonwith cover that allows air  
to circulate through but prevents sand from sifting in (such  
as canvas material). Do not use plastic as plastic will hold  
moisture.  
Preventive measures can be taken during installations, such as:  
1. Locating the unit on side of structure opposite the prevailing  
winds.  
2. Elevating the unit to height where drifting sand cannot pile  
up against coil. Four-in.-high mounting feet or an 18-in.-  
high mounting rack are available as accessories and can be  
used to elevate the unit.  
47—  
AIR CONDITIONER  
TROUBLESHOOTING CHART  
NO COOLING OR  
INSUFFICIENT  
COOLING  
COMPRESSOR  
RUNS BUT  
COMPRESSOR  
RUNS BUT  
INSUFFICIENT  
COOLING  
COMPRESSOR  
WILL NOT RUN  
CYCLES ON  
INTERNAL  
OVERLOAD  
OUTDOOR FAN  
HIGH SUCTION  
LOW HEAD  
PRESSURE  
HIGH SUCTION  
LOW  
SUPERHEAT  
STOPPED OR  
CYCLING ON  
OVERLOAD  
CONTACTOR  
OPEN  
CONTACTOR  
CLOSED  
LOOSE LEAD  
AT FAN MOTOR  
LOW SUCTION  
PRESSURE  
OUTDOOR AIR  
RESTRICTED OR  
RECIRCULATING  
COMPRESSOR  
POWER SUPPLY  
OPEN  
DEFECTIVE  
COMPRESSOR  
VALVES  
MOTOR  
DEFECTIVE  
DIRTY AIR  
FILTERS  
UNIT  
OVERCHARGED  
POWER SUPPLY  
RESTRICTED  
DISCHARGE  
TUBE  
DEFECTIVE  
LOW-VOLTAGE  
TRANSFORMER  
INCORRECT  
OFM  
CAPACITOR  
INTERNAL  
PRESSURE  
RELIEF OPEN  
INCORRECT  
SIZE  
PISTON  
LOOSE LEADS AT  
COMPRESSOR  
DUCT  
RESTRICTED  
OVERCHARGE  
OR NON-  
CONDENSABLES  
IN SYSTEM  
OPEN  
THERMOSTAT  
FAULTY START  
GEAR (1-PH)  
DAMPERS  
PARTLY CLOSED  
OPEN SHORTED  
OR GROUNDED  
COMPRESSOR  
MOTOR  
LOW  
REFRIGERANT  
CHARGE  
OPEN CONTROL  
CIRCUIT  
INDOOR COIL  
FROSTED  
WINDINGS  
LINE VOLTAGE  
TOO HIGH OR  
LOW  
SLIGHTLY  
LOW ON  
REFRIGERANT  
LOSS OF  
CHARGE  
COMPRESSOR  
STUCK  
COMPRESSOR  
INTERNAL  
PROTECTION  
OPEN  
LIQUID LINE  
SLIGHTLY  
RESTRICTED  
CONTACTOR OR  
COIL DEFECTIVE  
DEFECTIVE RUN  
CAPACITOR  
LOOSE  
ELECTRICAL  
CONNECTION  
DEFECTIVE RUN  
CAPACITOR  
COMPRESSOR  
BEARINGS  
PISTON  
RESTRICTED  
INCORRECT  
SIZE  
PISTON  
HIGH  
SUPERHEAT  
INDOOR COIL  
STRAINER  
RESTRICTED  
INDOOR  
BLOWER MOTOR  
DEFECTIVE OR  
CYCLING ON OL  
A90208  
Fig. 52Air-Conditioner Troubleshooting Chart  
48—  
HEAT PUMP  
TROUBLESHOOTINGCOOLING CYCLE  
NO COOLING OR  
INSUFFICIENT  
COOLING  
COMPRESSOR  
RUNS BUT  
COMPRESSOR  
RUNS BUT  
INSUFFICIENT  
COOLING  
COMPRESSOR  
WILL NOT RUN  
CYCLES ON  
INTERNAL  
OVERLOAD  
OUTDOOR FAN  
HIGH SUCTION  
LOW HEAD  
PRESSURE  
HIGH SUCTION  
LOW  
SUPERHEAT  
STOPPED OR  
CYCLING ON  
OVERLOAD  
CONTACTOR  
OPEN  
CONTACTOR  
CLOSED  
LOOSE LEAD  
AT FAN MOTOR  
LOW SUCTION  
PRESSURE  
REVERSING  
VALVE HUNG UP  
OR INTERNAL  
LEAK  
OUTDOOR AIR  
RESTRICTED OR  
RECIRCULATING  
COMPRESSOR  
POWER SUPPLY  
OPEN  
DEFROST RELAY  
N.C. CONTACTS  
OPEN  
DIRTY AIR  
FILTERS  
UNIT  
OVERCHARGED  
POWER SUPPLY  
DAMAGED OR  
STUCK  
REVERSING  
VALVE  
DEFECTIVE  
LOW-VOLTAGE  
TRANSFORMER  
DEFECTIVE  
COMPRESSOR  
VALVES  
INCORRECT  
SIZE  
PISTON  
LOOSE LEADS AT  
COMPRESSOR  
MOTOR  
DEFECTIVE  
DUCT  
RESTRICTED  
RESTRICTED  
DISCHARGE  
TUBE  
INCORRECT  
OFM  
CAPACITOR  
INTERNAL  
PRESSURE  
RELIEF OPEN  
OPEN  
THERMOSTAT  
FAULTY START  
GEAR (1-PH)  
DAMPERS  
PARTLY CLOSED  
OPEN SHORTED  
OR GROUNDED  
COMPRESSOR  
MOTOR  
OVERCHARGE  
OR NON-  
CONDENSABLES  
IN SYSTEM  
DEFECTIVE  
DEFROST  
THERMOSTAT  
OPEN CONTROL  
CIRCUIT  
INDOOR COIL  
FROSTED  
WINDINGS  
LOW  
REFRIGERANT  
CHARGE  
SLIGHTLY  
LOW ON  
REFRIGERANT  
LOSS OF  
CHARGE  
COMPRESSOR  
STUCK  
COMPRESSOR  
INTERNAL  
PROTECTION  
OPEN  
LINE VOLTAGE  
TOO HIGH OR  
LOW  
LIQUID LINE  
SLIGHTLY  
RESTRICTED  
CONTACTOR OR  
COIL DEFECTIVE  
LOOSE  
ELECTRICAL  
CONNECTION  
PISTON  
RESTRICTED  
DEFECTIVE RUN  
CAPACITOR  
DEFECTIVE RUN  
CAPACITOR  
INCORRECT  
SIZE  
PISTON  
COMPRESSOR  
BEARINGS  
INDOOR COIL  
STRAINER  
RESTRICTED  
HIGH  
SUPERHEAT  
INDOOR  
BLOWER MOTOR  
DEFECTIVE OR  
CYCLING ON OL  
A90207  
Fig. 53Heat-Pump Troubleshooting Chart Cooling Cycle  
49—  
HEAT PUMP  
TROUBLESHOOTINGHEATING CYCLE  
NO HEATING OR  
INSUFFICIENT  
HEATING  
COMPRESSOR  
RUNS BUT  
COMPRESSOR  
RUNS  
INSUFFICIENT  
HEATING  
COMPRESSOR  
WILL NOT RUN  
CYCLES ON  
INTERNAL  
OVERLOAD  
DIRTY FILTERS  
OR INDOOR  
COIL  
CONTACT  
OPEN  
CONTACTOR  
CLOSED  
LOW SUCTION  
LOW HEAD  
STRIP HEATERS  
NOT OPERATING  
INDOOR FAN  
STOPPED OR  
CYCLING ON  
OVERLOAD  
DEFECTIVE LOW-  
VOLTAGE  
TRANSFORMER  
DEFECTIVE FAN  
MOTOR  
CAPACITOR  
OUTDOOR  
THERMOSTAT  
DEFECTIVE  
COMPRESSOR  
POWER SUPPLY  
OUTDOOR FAN  
STOPPED  
OUTDOOR FAN  
RUNNING  
REMOTE  
CONTROL  
CENTER  
DAMAGED  
REVERSING  
VALVE  
LOOSE LEADS  
AT  
FAN MOTOR  
LOOSE LEADS  
AT OUTDOOR  
FAN MOTOR  
LOOSE LEADS AT  
COMPRESSOR  
REVERSING  
VALVE STUCK  
ODT SETTING  
TOO LOW  
DEFECTIVE  
CAP TUBE  
PINCHED OR  
BULB NOT  
SENSING TRUE  
ODT  
CONTACTOR  
COIL OPEN OR  
SHORTED  
FAN MOTOR  
BURNED  
OUT  
INTERNAL FAN  
MOTOR KLIXON  
OPEN  
FAULTY START  
GEAR (1-PH)  
RESTRICTION IN  
DISCHARGE LINE  
RESTRICTED  
LIQUID LINE  
OVERCHARGE  
OR NON-  
CONDENSABLES  
IN SYSTEM  
STRIP HEATER  
RELAY OR  
CONTACTOR  
DEFECTIVE  
PISTON  
RESTRICTED OR  
IS CLOGGED  
OPEN INDOOR  
THERMOSTAT  
COMPRESSOR  
STUCK  
FAN MOTOR  
BURNED OUT  
OPENING IN  
POWER CIRCUIT  
TO HEATER  
COMPRESSOR  
INTERNAL  
OVERLOAD  
OPEN  
DEFROST RELAY  
N.C. CONTACTS  
OPEN ON  
LIQUID-LINE  
PRESSURE  
SWITCH OPEN  
LOW  
REFRIGERANT  
CHARGE  
UNDER-  
CHARGED  
ELEMENTS  
CIRCUIT BOARD  
OPEN SHORTED  
OR GROUNDED  
COMPRESSOR  
WINDINGS  
LINE VOLTAGE  
TOO HIGH OR  
LOW  
LOSS OF  
CHARGE  
OUTDOOR COIL  
DIRTY  
BROKEN FUSE  
LINK  
DEFECTIVE RUN  
CAPACITOR  
(1-PH)  
BROKEN  
HEATER  
ELEMENT  
OPEN CONTROL  
CIRCUIT  
DEFECTIVE RUN  
CAPACITOR  
STRAINER  
RESTRICTED  
OPEN (KLIXON)  
OVER  
TEMPERATURE  
THERMOSTAT  
OUTDOOR COIL  
HEAVILY  
FROSTED  
COMPRESSOR  
BEARINGS  
FAN MOTOR  
CONTACTS  
WELDED CLOSED  
IN DEFROST  
RELAY  
DEFECTIVE  
ROOM  
THERMOSTAT  
(2ND STAGE)  
DEFECTIVE  
DEFROST  
THERMOSTAT  
HIGH-LOAD  
CONDITION  
DEFROST  
THERMOSTAT IN  
POOR PHYSICAL  
CONTACT WITH  
TUBE  
REVERSING  
VALVE JAMMED  
IN MIDPOSITION  
REVERSING  
VALVE DID NOT  
SHIFT  
UNIT NOT  
PROPERLY  
CHARGED  
DEFECTIVE  
CIRCUIT BOARD  
HIGH  
SUPERHEAT  
BAD ELECTRICAL  
CONNECTION  
ANYWHERE IN  
DEFROST  
CIRCUIT  
A90206  
Fig. 54Heat-Pump Troubleshooting Chart Heating Cycle  
50—  
51—  
© 2000 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231  
Printed in U.S.A.  
sm01,025  
Catalog No. 5356-109  
52—  

Adrenaline Technologies TURBO CHARGE TC400 User Manual
Cisco Systems OL 23857 01 User Manual
Computer Expressions 40CG User Manual
Cornelius Ice Drink Dispenser Enduro 250 User Manual
Enerco HS170FAVT User Manual
Energizer CHFM User Manual
Epson All in One Printer PLQ 20 Series User Manual
Friedrich Air Conditioner CP15 User Manual
Friedrich CP10 User Manual
HP Hewlett Packard F300 User Manual