Bryant Air Cooled Condensing Units 569C User Manual

installation, start-up and  
service instructions  
COMMERCIAL AIR-COOLED  
CONDENSING UNITS  
569C  
576B  
Cancels: II 569C-72-3  
II 569C-72-4  
5/1/99  
IMPORTANT —READ BEFORE INSTALLING  
1. Read and become familiar with these installation  
instructions before installing this unit (Fig. 1).  
2. Be sure the installation conforms to all applicable local  
and national codes.  
3. These instructions contain important information for the  
proper maintenance and repair of this equipment. Re-  
tain these instructions for future use.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . .  
1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9  
I. Locate the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
II. Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . .  
III. Compressor Mounting . . . . . . . . . . . . . . . . . . . . . .  
IV. Unit Refrigerant Piping Connections . . . . . . . . . .  
V. Electrical Connections . . . . . . . . . . . . . . . . . . . . . .  
VI. Accessory Installation . . . . . . . . . . . . . . . . . . . . . .  
2
2
2
2
6
9
Fig. 1 — Typical Unit (569C072 Shown)  
Understand the signal words — DANGER, WARNING, and  
CAUTION. These words are used with the safety-alert sym-  
bol. Danger identifies the most serious hazards which will  
result in severe personal injury or death. Warning indicates  
a condition that could result in personal injury. Caution is  
used to identify unsafe practices which would result in minor  
personal injury or product and property damage.  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
I. Start-Up and Adjustments . . . . . . . . . . . . . . . . . . 10  
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . 10  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-13  
I. Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
II. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
III. Condenser-Fan Adjustment . . . . . . . . . . . . . . . . 11  
IV. Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
V. Compressor Removal . . . . . . . . . . . . . . . . . . . . . 12  
VI. Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . 12  
VII. Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . 12  
VIII. Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . 12  
WARNING: Before performing service or mainte-  
nance operations on unit, turn off main power switch  
to unit. Electrical shock could cause personal injury.  
1. The power supply (volts, hertz, and phase) must corre-  
spond to that specified on unit rating plate.  
2. The electrical supply provided by the utility must be suf-  
ficient to handle load imposed by this unit.  
3. Refer to the Locate the Unit section on page 2 and  
Fig. 2 and 3 for locations of electrical inlets, required  
clearances, and weight distribution based on recom-  
mended support points before setting unit in place.  
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . 14,15  
4. This installation must conform with local building codes.  
Refer to local plumbing or wastewater codes and other  
applicable local codes.  
SAFETY CONSIDERATIONS  
WARNING: Improper installation, adjustment, alter-  
ation, service, maintenance, or use can cause explo-  
sion, fire, electric shock, or other occurrences which may  
injure you or damage your property. Consult a quali-  
fied installer or service agency for information or assis-  
tance. The qualified installer or agency must use only  
factory-authorized kits or accessories when repairing this  
product.  
INSTALLATION  
NOTE: When installing any accessory item, see the manu-  
facturer s installation instructions packaged with the acces-  
sory. A qualified agency must use factory-authorized kits or  
accessories when modifying this unit.  
The 569C072,090, and 120 units use hermetic compressors.  
The 576B090,102, and 120 units use semi-hermetic compres-  
sors. Refer to Tables 1A and 1B.  
Recognize safety information. This is the safety-alert sym-  
bol. (  
) When you see this symbol on the unit and in  
instructions or manuals, be alert to the potential for per-  
sonal injury.  
Table 1A — Specifications (English)  
UNIT  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
NOMINAL CAPACITY (Tons)  
6
712  
10  
712  
812  
10  
OPERATING WEIGHT (lb)  
Aluminum Coils (Standard)  
Copper Coils (Optional)  
340  
386  
370  
438  
395  
472  
510  
578  
564  
632  
564  
632  
RIGGING WEIGHT (lb)  
Aluminum Coils (Standard)  
Copper Coils (Optional)  
390  
436  
420  
488  
445  
522  
560  
628  
614  
682  
614  
682  
REFRIGERANT*  
COMPRESSOR  
Quantity...Type  
R-22  
Bristol, Reciprocating Copeland, Scroll Copeland, Scroll  
Reciprocating, Semi-Hermetic  
1...06DH824  
(See Note)  
1...H26A72Q  
1...ZR94KC  
1...ZR125KC  
1...06DA818 1...06DA824  
4
Quantity Cylinders  
Speed (Rpm)  
Oil Charge (oz) (ea)  
2
3500  
65  
3500  
85  
3500  
110  
6
1750  
88  
1750  
128  
CONDENSER FAN  
Quantity...Rpm  
Propeller; Direct Drive  
1...850  
1...1100  
26  
Diameter (in.)  
26  
1
3
Motor Hp (NEMA)  
Nominal Airflow (cfm)  
3
4
3800  
6500  
7000  
6500  
6500  
6500  
CONDENSER COIL  
Face Area (sq ft)  
Storage Capacity (lb)†  
Enhanced Copper Tubes, Aluminum Lanced Fins  
12.24  
11.26  
15.75  
14.88  
20.5  
18.0  
18.0  
16.56  
18.0  
16.56  
18.87  
16.56  
CONNECTIONS (sweat)  
Suction (in.)  
Liquid (in.)  
118  
118  
118  
118  
118  
118  
1
1
5
1
5
5
2
2
8
2
8
8
CONTROLS  
Pressurestat Settings (psig)  
High Cutout  
Cut-in  
426 Ϯ  
7
320 Ϯ 20  
Low Cutout  
Cut-in  
7 Ϯ  
22 Ϯ  
3
5
LEGEND  
NOTE: Unit 576B120 has one step of unloading. Full load is 100% ca-  
pacity, and one step of unloading is 67% capacity. Unit 576B120 has  
the following unloader settings: load is 70 Ϯ 1 psig and unload is  
60 Ϯ 2 psig.  
NEMA  
National Electrical Manufacturing Association  
*Unit is factory supplied with holding charge only.  
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at  
124 F.  
—3—  
Table 1B — Specifications (SI)  
UNIT  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
NOMINAL CAPACITY (kW)  
21  
26  
35  
26  
29.9  
35  
OPERATING WEIGHT (kg)  
Aluminum Coils (Standard)  
Copper Coils (Optional)  
154  
175  
168  
199  
179  
214  
231  
262  
256  
287  
256  
287  
RIGGING WEIGHT (kg)  
Aluminum Coils (Standard)  
Copper Coils (Optional)  
176  
198  
191  
221  
202  
237  
254  
285  
279  
309  
279  
309  
REFRIGERANT*  
COMPRESSOR  
Quantity...Type  
R-22  
Bristol, Reciprocating Copeland, Scroll Copeland, Scroll  
Reciprocating, Semi-Hermetic  
1...06DH824  
(See Note 1)  
1...H26A72Q  
1...ZR94KC  
1...ZR125KC  
1...06DA818 1...06DA824  
4
Quantity Cylinders  
Speed (R/s)  
Oil Charge (L) (ea)  
2
58.4  
1.92  
58.4  
2.51  
58.4  
3.25  
6
29.2  
2.60  
29.2  
3.78  
CONDENSER FAN  
Quantity...R/s  
Propeller; Direct Drive  
1...14.2  
1...18.3  
660  
Diameter (mm)  
660  
1
3
Motor Hp (NEMA)  
Nominal Airflow (L/s)  
3
4
1800  
3050  
3300  
3050  
3050  
3050  
CONDENSER COIL  
Face Area (sq m)  
Storage Capacity (kg)†  
Enhanced Copper Tubes, Aluminum Lanced Fins  
1.14  
5.1  
1.46  
6.75  
1.90  
8.6  
1.67  
7.5  
1.67  
7.5  
1.67  
7.5  
CONNECTIONS (sweat)  
Suction (in.)  
Liquid (in.)  
118  
118  
118  
118  
118  
118  
1
1
5
1
5
5
2
2
8
2
8
8
CONTROLS  
Pressurestat Settings (kPa)  
High Cutout  
Cut-in  
2937 Ϯ 48  
2206 Ϯ 138  
48 Ϯ 20  
Low Cutout  
Cut-in  
152 Ϯ 34  
LEGEND  
NOTES:  
1. Unit 576B120 has one step of unloading. Full load is 100% capacity,  
and one step of unloading is 67% capacity. Unit 576B120 has the  
following unloader settings: load is 483 Ϯ 6.9 kPa and unload is  
414 Ϯ 13.8 kPa.  
NEMA  
National Electrical Manufacturing Association  
*Unit is factory supplied with holding charge only.  
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at  
51 C.  
2. Equivalent mm values for connectors are as follows:  
in.  
mm  
1
2
8
12.7  
15.9  
28.6  
5
118  
—4—  
ELECTRICAL CONNECTIONS  
UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F  
WEIGHT CHART*  
1Ј-612  
Љ
1Ј-234  
[470.0] [375.0]  
1Ј-8Љ 1Ј-612  
[508.0] [470.0]  
1Ј-9Љ 1Ј-8Љ  
Љ
1Ј-214  
Љ
1Ј-4516Љ 2Ј-9516Љ  
UNIT Std Unit Corner W Corner X Corner Y Corner Z  
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg  
CONNECTION SIZES  
138Љ DIA [35] FIELD POWER SUPPLY HOLE  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
[362]  
[415] [846.5]  
AA  
BB  
CC  
DD  
Љ
1Ј-3Љ 2Ј-516Љ 3Ј-5716Љ  
[381] [613] [1052.5]  
1Ј-3Љ 2Ј-516Љ 3Ј-5716Љ  
[613] [1052.5]  
569C072 340 154 86 39 53 24  
569C090 370 168 86 39 78 35  
77 35 124 56  
99 45 107 49  
2Љ DIA [51] POWER SUPPLY KNOCK-OUT  
212Љ DIA [64] POWER SUPPLY KNOCK-OUT  
2Ј-0Љ  
[533.4] [508.0] [609.6] [381]  
7
569C120 395 179 89 40 92 42 109 49 105 48  
576B090 510 231 115 52 89 40 133 60 173 87  
576B102 564 256 133 60 97 44 141 64 193 88  
576B120 564 256 133 60 97 44 141 64 193 88  
*Weights are for aluminum coils.  
8Љ DIA [22] FIELD CONTROL WIRING HOLE  
1Ј-6Љ 1Ј-434  
[457.2] [425.5] [858.8] [381]  
1Ј-7Љ  
1Ј-5Љ 2Ј-91316Љ 1Ј-3Љ 2Ј-516Љ 3Ј-5716Љ  
[482.6] [431.8] [858.8] [381] [613] [1052.5]  
1Ј-7Љ  
1Ј-5Љ 2Ј-91316Љ 1Ј-3Љ 2Ј-516Љ 3Ј-5716Љ  
[482.6] [431.8] [858.8] [381] [613] [1052.5]  
Љ
2Ј-91316Љ 1Ј-3Љ 2Ј-516Љ 3Ј-5716Љ  
[613] [1052.5]  
SERVICE VALVE CONNECTIONS — 60 Hz  
UNIT  
SUCTION  
118Љ [28.6]  
118Љ [28.6]  
118Љ [28.6]  
118Љ [28.6]  
118Љ [28.6]  
118Љ [28.6]  
LIQUID  
1
1
5
1
5
5
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
2Љ [12.7]  
2Љ [12.7]  
8Љ [15.9]  
2Љ [12.7]  
8Љ [15.9]  
8Љ [15.9]  
c. Between units, control box side, 42 in. [1067]  
per NEC (National Electrical Code) (U.S.A.  
Standard).  
d. Between unit and ungrounded surfaces, con-  
trol box side, 36 in. [914] per NEC.  
e. Between unit and block or concrete walls and  
other grounded surfaces, control box side,  
42 in. [1067] per NEC.  
5. With the exception of the clearance for the con-  
denser coil as stated in note 4b, a removable  
fence or barricade requires no clearance.  
6. Units may be installed on combustible floors made  
from wood or Class A, B, or C roof covering  
material.  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2.  
3.  
Center of Gravity. See chart for dimensions.  
Direction of Airflow.  
4. Minimum clearance (local codes or jurisdiction may prevail):  
a. Condenser coil, for proper airflow, 36 in. [914] one side, 12 in. [305]  
the other. The left or rear side getting the greater clearance is optional.  
b. Overhead, 60 in. [1524] to assure proper condenser fan operation.  
Fig. 3 — Base Unit Dimensions  
RIGGING WEIGHT*  
UNIT  
A
B
C
in.  
lb  
kg  
in.  
mm  
1143  
1143  
1143  
1143  
1143  
1143  
in.  
mm  
978  
978  
978  
978  
978  
978  
mm  
904  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
390  
420  
445  
560  
614  
614  
176  
191  
202  
254  
279  
279  
45.0  
45.0  
45.0  
45.0  
45.0  
45.0  
38.5  
38.5  
38.5  
38.5  
38.5  
38.5  
35.5  
43.5  
43.5  
43.5  
43.5  
43.5  
1105  
1105  
1105  
1105  
1105  
*Weights are for aluminum coils.  
Fig. 4 — Rigging Label  
—5—  
Table 3 — Liquid Line Data  
LIQUID LINE  
MAX  
ALLOWABLE  
LIQUID LIFT  
Max Allowable  
Pressure Drop  
Max Allowable  
Temp Loss  
UNIT  
Ft  
86  
60  
70  
60  
65  
65  
M
psi  
7
kPa  
48.3  
48.3  
48.3  
48.3  
48.3  
48.3  
F
2
2
2
2
2
2
C
1
1
1
1
1
1
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
26.2  
18.3  
21.3  
18.3  
19.8  
19.8  
7
7
7
7
7
Fig. 5 — Typical Compressor Mounting (576B Units)  
B. Filter Drier and Moisture Indicator  
NOTE: Values shown are for units operating at 45 F (7.2 C) saturated  
suction and 95 F (35 C) entering air.  
V. ELECTRICAL CONNECTIONS  
The filter drier is factory installed. Moisture indicator is a  
field-installed accessory and should be installed just after liq-  
uid line shutoff valve. Do not use a receiver. A receiver is not  
supplied with the unit and should not be used.  
WARNING: The unit cabinet must have an uninter-  
rupted, unbroken electrical ground to minimize the pos-  
sibility of personal injury if an electrical fault should  
occur. This ground may consist of electrical wire con-  
nected to the unit ground lug in the control compart-  
ment or conduit approved for electrical ground when  
installed in accordance with the NEC and local electri-  
cal codes. Failure to adhere to this warning could re-  
sult in personal injury.  
NOTE: Unit is shipped with R-22 holding charge. System pres-  
sure must be relieved before removing caps. Recover refrig-  
erant prior to brazing.  
Pass nitrogen or other inert gas through piping while braz-  
ing to prevent formation of copper oxide.  
Install field-supplied thermostatic expansion valve(s) in evapo-  
rator section. It is r ecom m en d ed that a field supplied liq-  
uid line solenoid be positioned in the main liquid line (near  
the evaporator coil). It should be wired to close when com-  
pressor stops to minimize refrigerant migration during the  
‘‘OFFcycle.  
CAUTION: Failure to follow these precautions could  
result in damage to the unit being installed:  
A. Field Power Supply (Fig. 6-8)  
1. Make all electrical connections in accordance with NEC  
ANSI/NFPA (American National Standards Institute/  
National Fire Protection Association) 70, latest edition,  
and local electrical codes governing such wiring. Refer  
to unit wiring diagram.  
Table 2 — Refrigerant Piping Sizes  
LINEAR LENGTH OF PIPING — FT (M)  
0-25  
(0-7.6)  
25-50  
(7.6-15.2)  
50-75  
(15.2-22.9)  
75-100  
(22.9-30.5)  
2. Use only copper or copper-clad conductor fan connec-  
tions between field-supplied electrical disconnect switch  
and unit. DO NOT USE ALUMINUM WIRE. Maximum  
wire size is no. 2 AWG (American Wire Gage).  
UNIT  
Line Size (in. OD)  
L
S
L
S
L
S
L
S
1
1
5
1
5
5
1
1
1
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
2
2
8
2
8
8
118  
118  
118  
118  
118  
118  
2
2
8
2
8
8
118  
118  
138  
118  
118  
118  
2
8
8
8
8
8
118  
118  
138  
118  
138  
138  
2
8
8
8
8
8
118  
138  
138  
138  
138  
138  
1
5
1
5
5
5
5
5
5
5
5
5
5
5
5
3. Voltage to compressor terminals during operation must  
be within voltage range indicated on unit nameplate (also  
see Table 4). On 3-phase units, voltages between phases  
must be balanced within 2% and the current within 10%.  
Use the formula shown in Table 4, Note 2, to determine  
the percent voltage imbalance. Operation on improper  
line voltage or excessive phase imbalance constitutes abuse  
and may cause damage to electrical components. Such  
operation would invalidate any applicable warranty.  
LEGEND  
S
L
Liquid Line  
Suction Line  
NOTES:  
1. Pipe sizes are based on a 2° F (1° C) loss for liquid and suction  
lines.  
4. Insulate low-voltage wires for highest voltage con-  
tained within conduit when low-voltage control wires are  
run in same conduit as high-voltage wires.  
2. Pipe sizes are based on the maximum linear length shown for each  
column, plus a 50% allowance for fittings.  
3. Charge units with R-22 in accordance with unit installation instructions.  
4. Line size conversion to mm is:  
5. Do not damage internal components when drilling through  
any panel to mount electrical hardware, conduit, etc.  
in.  
mm  
1
2
8
12.7  
15.9  
28.6  
34.9  
5
118  
138  
—6—  
All units except 208/230-v units are factory wired for the volt-  
age shown on the nameplate. If the 208/230-v unit is to be  
connected to a 208-v power supply, the transformer must be  
rewired by moving the black wire from the 230-v orange wire  
on the transformer and connecting it to the 200-v red wire  
from the transformer. The end of the orange wire must then  
be insulated.  
Refer to unit label diagram for additional information. Pig-  
tails are provided for field wire connections. Use factory-  
supplied splices or UL (Underwriters’ Laboratories) approved  
copper/aluminum connector.  
B. Control Voltage Connections  
Install an accessory thermostat assembly according to instal-  
lation instructions included with the accessory. Locate ther-  
mostat assembly on a solid wall in the conditioned space to  
sense average temperature in accordance with thermostat  
installation instructions.  
Route thermostat cable or equivalent single leads of colored  
wire from subbase terminals to low-voltage connections on  
unit (shown in Fig. 7) as described in Steps 1 through 4  
below.  
NOTE: Refer to Table 5 for wire conversion information.  
When installing units, provide a disconnect per NEC.  
NOTE: For wire runs up to 50 ft (15.2 m), use no. 18 AWG  
(0.82 mm) insulated wire (35 C minimum). For 50 to 75 ft  
(15.2 to 22.9 m), use no. 16 AWG (1.30 mm) insulated wire  
(35 C minimum). For over 75 ft (22.9 m), use no. 14 AWG  
(2.08 mm) insulated wire (35 C minimum). All wire larger  
than no. 18 AWG (0.82 mm) cannot be directly connected to  
the thermostat and will require a junction box and splice at  
the thermostat.  
All field wiring must comply with NEC and local  
requirements.  
Install field wiring as follows:  
1. Install conduit through side panel openings.  
2. Install power lines to terminal connections as shown in  
Fig. 6.  
1. Connect thermostat wires to screw terminals of low volt-  
age connection board.  
2. Pass the control wires through the hole provided in the  
corner post. See Fig. 8.  
3. Feed wire through raceway built into the corner post  
and into the 24-v thermostat connection board. The 24-v  
thermostat connection is located on the left side of the  
low voltage connection compartment. The raceway pro-  
vides the UL required clearance between the high- and  
low-voltage wiring.  
4. Total combined amperage draw of the field-installed liq-  
uid line solenoid valve and indoor fan contactor must  
not exceed 22 va. If the specified va must be exceeded,  
use a remote relay to switch the load.  
LEGEND  
C
NEC  
Contactor  
National Electrical Code (U.S.A. Standard)  
Field Wiring  
Factory Wiring  
Splice Connection (Factory Supplied)  
Fig. 6 — Power Wiring Connections  
LEGEND  
AHA  
Adjustable Heat Anticipator  
Contactor, Compressor  
Circuit Breaker  
LLSV  
LPS  
TB  
Liquid Line Solenoid Valve  
Low-Pressure Switch  
Terminal Block  
Thermostat-Cooling  
Time-Delay Relay  
Thermostat-Heating  
Transformer  
Terminal (Marked)  
Splice  
Factory Wiring  
Field Control Wiring  
To Indicate Common Potential Only,  
Not To Represent Wiring  
C
CB  
CC  
CLO  
HPS  
IFC  
Cooling Compensator  
Compressor Lockout  
TC  
TDR  
TH  
TRAN  
High-Pressure Switch  
Indoor (Evaporator) Fan Contactor  
Fig. 7 — Typical Control Wiring Connections (569C Shown)  
—7—  
Table 4 — Electrical Data  
VOLTAGE RANGE  
COMPRESSOR  
RLA LRA  
OFM  
FLA  
POWER SUPPLY  
NOMINAL VOLTAGE  
(V-Ph-Hz)  
UNIT  
Min  
Max  
MCA  
MOCP  
208/230-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
414  
518  
198  
360  
254  
508  
632  
242  
440  
21.8  
9.6  
142  
72  
1.9  
1.0  
1.9  
1.0  
1.0  
25.6  
12.9  
11.4  
25.6  
12.9  
35  
15  
15  
35  
15  
569C072  
7.6  
58  
19.0  
9.5  
142  
72  
208/230-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
414  
518  
198  
360  
254  
508  
632  
242  
440  
28.8  
14.7  
10.8  
28.8  
14.7  
195  
95  
3.8  
1.9  
1.9  
1.5  
1.5  
39.8  
20.3  
15.4  
37.5  
19.9  
45  
20  
15  
45  
20  
569C090  
569C120  
80  
195  
90  
208/230-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
414  
518  
198  
360  
254  
508  
632  
242  
440  
37.8  
17.2  
12.3  
37.8  
17.2  
239  
125  
80  
239  
114  
3.1  
1.4  
1.4  
1.4  
1.4  
46.2  
22.7  
19.3  
46.2  
22.7  
60  
30  
25  
60  
30  
208/230-3-60  
380-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
342  
414  
518  
198  
342  
254  
418  
508  
632  
253  
460  
31.5  
19.0  
15.7  
12.6  
31.5  
15.7  
160  
75  
3.1  
2.2  
1.4  
1.4  
1.4  
1.4  
42.5  
26.0  
21.0  
17.2  
42.5  
21.0  
50  
35  
25  
20  
50  
25  
80  
576B090  
576B102  
576B120  
64  
160  
80  
208/230-3-60  
380-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
342  
414  
518  
198  
342  
254  
418  
508  
632  
253  
460  
39.7  
24.0  
19.9  
15.9  
39.7  
19.9  
198  
93  
3.1  
2.2  
1.4  
1.4  
1.4  
1.4  
52.7  
32.2  
26.3  
21.3  
52.7  
26.3  
70  
40  
35  
25  
70  
35  
99  
79  
198  
99  
208/230-3-60  
380-3-60  
460-3-60  
575-3-60  
220-3-50  
400-3-50  
187  
342  
414  
518  
198  
342  
254  
418  
508  
632  
253  
460  
39.7  
24.0  
19.9  
15.9  
39.7  
19.9  
198  
93  
3.1  
2.2  
1.4  
1.4  
1.4  
1.4  
52.7  
32.2  
26.3  
21.3  
52.7  
26.3  
70  
40  
35  
25  
70  
35  
99  
79  
198  
99  
LEGEND  
Example: Supply voltage is 460-3-60.  
CSA  
FLA  
Canadian Standards Association  
Full Load Amps  
AB = 452 v  
BC = 464 v  
AC = 455 v  
HACR  
LRA  
MCA  
MOCP  
NEC  
OFM  
RLA  
UL  
Heating, Air Conditioning and Refrigeration  
Locked Rotor Amps  
452 + 464 + 455  
Minimum Circuit Amps  
Average Voltage =  
=
3
Maximum Overcurrent Protection  
National Electrical Code (U.S.A. Standard)  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
1371  
3
= 457  
Underwriters’ Laboratories  
(AB) 457 - 452 = 5 v  
(BC) 464 - 457 = 7 v  
(AC) 457 - 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent voltage imbalance  
7
% Voltage Imbalance = 100 x  
457  
= 1.53%  
NOTES:  
1. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
2. Unbalanced 3-Phase Supply Voltage  
This amount of phase imbalance is satisfactory as it is below the maxi-  
mum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
Never operate a motor where a phase imbalance in supply voltage is  
greater than 2%. Use the following formula to determine the percent  
voltage imbalance.  
3. The 575-v units are CSA only.  
4. The 380-v units are not UL or CSA listed.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
—8—  
PRE-START-UP  
WARNING: Failure to observe the following warn-  
ings could result in serious personal injury:  
1. Follow recognized safety practices and wear pro-  
tective goggles when checking or servicing refrig-  
erant system.  
2. Do not operate compressor or provide any electric  
power to unit unless compressor terminal cover is  
in place and secured.  
3. Do not remove compressor terminal cover until all  
electrical sources have been disconnected.  
4. If refrigerant leak is suspected around compres-  
sor terminals, recover refrigerant whenever pos-  
sible and relieve all pressure from system before  
touching or disturbing anything inside terminal box.  
5. Never attempt to repair soldered connection while  
refrigerant system is under pressure.  
6. Do not use torch to remove any component. Sys-  
tem contains oil and refrigerant under pressure.  
To remove a component, wear protective goggles  
and proceed as follows:  
Fig. 8 — Field Control Wiring Raceway  
(576B Unit Shown)  
a. Shut off electrical power to unit.  
b. Recover refrigerant. Relieve all pressure from  
system.  
Table 5 — American/European Wire Conversions  
c. Cut component-connecting tubing with tubing  
cutter and remove component from unit.  
AMERICAN  
EUROPEAN  
American  
Conversion  
(mm2)  
Industry  
Standard  
Size (mm2)  
Industry  
d. Carefully unsweat remaining tubing stubs when  
necessary. Oil can ignite when exposed to torch  
flame.  
Standard Size  
18 AWG  
16 AWG  
14 AWG  
12 AWG  
10 AWG  
8 AWG  
0.82  
1.30  
1.0  
1.5  
2.08  
2.5  
Proceed as follows to inspect and prepare the unit for initial  
start-up:  
3.30  
4.0  
5.25  
6.0  
6.36  
10.0  
16.0  
25.0  
1. Field electrical power source must agree with unit name-  
plate rating.  
6 AWG  
13.29  
21.14  
26.65  
33.61  
42.39  
53.49  
67.42  
85.00  
107.19  
4 AWG  
3 AWG  
2. Check voltage imbalance as shown in Table 4, Note 2.  
2 AWG  
35.0  
50.0  
70.0  
95.0  
120.0  
1 AWG  
3. Check that all internal wiring connections are tight and  
that all barriers, covers, and panels are in place.  
1/0 AWG  
2/0 AWG  
3/0 AWG  
4/0 AWG  
4. Ensure all service valves are open. On 576B units, be  
sure all compressor service valves are backseated.  
250 kcmil  
300 kcmil  
350 kcmil  
400 kcmil  
500 kcmil  
600 kcmil  
126.64  
151.97  
177.90  
202.63  
253.29  
303.95  
150.0  
185.0  
240.0  
300.0  
5. Verify that compressor holddown bolts have been loos-  
ened and that flat/snubber washers can be rotated by  
applying finger pressure (snug, but not tight).  
6. On 569C and 576B units, verify compressor crankcase  
heater is securely in place. Crankcase heater must op-  
erate for a least 24 hours before start-up.  
LEGEND  
AWG  
kcmil  
American Wire Gage  
Thousand Circular Mils  
7. Note that compressor oil level is visible in the sight  
glass (576B units only).  
VI. ACCESSORY INSTALLATION  
8. Check for leaks in refrigerant system by using soap  
bubbles and/or electronic leak detector.  
At this time any required accessories should be installed on  
the unit. Refer to Table 6 for available accessories. Control  
wiring information is provided in the unit wiring book.  
9. Check that liquid line solenoid valve is located at evapo-  
rator coil as shown in Filter Drier and Moisture Indi-  
cator section, page 6.  
Table 6 — Accessory List  
ACCESSORY  
10. Check that both outdoor and indoor units are properly  
mounted in accordance with installation instructions  
and applicable codes.  
Gage Panel  
Winter-Start Relay Package  
Weatherprobe™ II Low Ambient Kit  
Hail Guard Package (072)  
Hail Guard Package (090,102,120)  
Thermostats  
Subbase  
—9—  
START-UP  
Terminals G and C) will also open, allowing the system to  
function in cooling. As cooling demand is satisfied, the ther-  
mostat contacts break, deenergizing the contactor causing the  
system to shut off. The liquid line solenoid (LLS) valve closes,  
minimizing the potential for refrigerant migration at this time.  
The compressor does not restart until the thermostat again  
calls for cooling. If a demand for cooling occurs within 5 min-  
utes after the thermostat is satisfied, the system will not re-  
start due to the feature of Time Guard II device. After the  
5-minute time period, the system will restart as normal upon  
thermostat demand.  
I. START-UP AND ADJUSTMENTS  
CAUTION: Complete the required procedures given  
in the Pre-Start-Up section before starting the unit.  
Do not jumper any safety devices when operating the  
unit.  
Do not operate the compressor when the outdoor tem-  
perature is below 25 F (Ϫ4 C) (unless accessory low am-  
bient kit is installed).  
A. Checking Cooling Control Operation  
The system is protected with a Cycle-LOC device so that the  
compressor will not start if a high-pressure or low-pressure  
fault occurs. To reset the Cycle-LOC device, set the thermo-  
stat to eliminate the cooling demand then return to the origi-  
nal set point. This should be done only once, and if system  
shuts down due to the same fault, determine the problem be-  
fore attempting to reset the Cycle-LOC device.  
Start and check the unit for proper cooling control operation  
as follows:  
1. Place room thermostat SYSTEM switch in OFF posi-  
tion. Observe that blower motor starts when FAN switch  
is placed in ON position and shuts down when FAN switch  
is placed in AUTO. position.  
The crankcase heaters must be energized for a minimum of  
24 hours before starting a 569C and 576B unit.  
2. Place SYSTEM switch in COOL position and FAN switch  
in AUTO. position. Set cooling control below room tem-  
perature. Observe that compressor and condenser- and  
evaporator-fan motors start. Observe that cooling cycle  
shuts down when control setting is satisfied.  
D. Oil Charge  
576B Units  
Allow unit to run for about 20 minutes. Stop unit and check  
compressor oil level. Add oil only if necessary to bring oil into  
view in sight glass. Use only approved compressor oil.  
B. Unit Controls  
All units have the following internal-protection controls:  
Compressor Overload  
Approved oils are:  
This overload interrupts power to the compressor when  
either the current or internal motor winding temperature be-  
come excessive, and automatically resets when the internal  
temperature drops to a safe level. This overload may require  
up to 60 minutes (or longer) to reset. If the internal overload  
is suspected of being open, disconnect the electrical power to  
the unit and check the circuit through the overload with an  
ohmmeter or continuity tester.  
Suniso 3GS  
WF32-150  
If oil is added, run unit for an additional 10 minutes. Stop  
unit and check oil level. If level is still low, add oil only after  
determining that piping system is designed for proper oil re-  
turn and that system is not leaking oil.  
569C Units  
The 569C units do not have a sight glass and are factory charged  
with the correct amount of oil.  
Time GuardII Device  
The unit is equipped with accessory Time Guard II recycle  
timer. The device will cause a 5-minute delay between com-  
pressor starts.  
All Units  
Do not reuse drained oil or use any oil that has been exposed  
to the atmosphere. Procedures for adding or removing oil are  
given in the Standard Service Techniques Manual, Chapter 1,  
Refrigerants.  
Cycle-LOC™ Device  
When high-pressure or low-pressure fault occurs, the Cycle-  
LOC device will protect the system by not allowing the com-  
pressor to start.  
Low-Pressure/ Loss of Charge Switch (LPS)  
When the liquid line pressure drops below 7 psig (48 kPa),  
the LPS opens 24-v power to the compressor contactor and  
stops the compressor. When the pressure reaches 22 psig  
(152 kPa), the switch resets and the compressor is allowed to  
restart.  
CARE AND MAINTENANCE  
To ensure continuing high performance and to minimize the  
possibility of premature equipment failure, periodic mainte-  
nance must be performed on this equipment. This cooling unit  
should be inspected at least once each year by a qualified serv-  
ice person.  
High-Pressure Switch (HPS)  
When the refrigerant high-side pressure reaches 426 psig  
(2937 kPa), the HPS opens 24-v power to the compressor con-  
tactor and stops the compressor. When the pressure drops to  
320 psig (2206 kPa), the switch resets and the compressor is  
allowed to restart.  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
WARNING: The ability to properly perform mainte-  
nance on this equipment requires certain expertise,  
mechanical skills, tools, and equipment. If you do not  
possess these, do not attempt to perform any mainte-  
nance on this equipment other than those procedures  
recommended in the Users Manual. FAILURE TO HEED  
THIS WARNING COULD RESULT IN SERIOUS PER-  
SONAL INJ URY AND POSSIBLE DAMAGE TO THIS  
EQUIPMENT.  
C. Sequence of Operation  
At start-up, the thermostat calls for cooling. When all safety  
devices are satisfied, the compressor contactor (fan con-  
tactor) will energize causing the compressor and outdoor (con-  
denser) fan motor to operate. Terminal ЉGЉ at the thermostat  
is also energized, allowing the field-supplied and -installed  
(24v) indoor (evaporator) fan contactor to function. A field-  
supplied and -installed liquid line valve (connected between  
—10—  
SERVICE  
WARNING: When servicing unit, shut off all electri-  
cal power to unit to avoid shock hazard or injury from  
rotating parts.  
I. CLEANING  
Inspect unit interior at the beginning of each cooling season  
and as operating conditions require.  
A. Condenser Coil  
Inspect coil monthly. Clean condenser coil annually, and as  
required by location and outdoor-air conditions.  
Clean coil as follows:  
1. Turn off unit power.  
Fig. 10 — Propping Up Top Panel  
2. Remove and save top panel screws on condensing unit.  
3. Remove condenser coil corner post. See Fig. 9. To hold  
top panel open, place coil corner post between top panel  
and side panel. See Fig. 10.  
4. Remove bracket holding coil sections together at return  
end of condenser coil. Carefully separate the outer coil  
section 3 to 4 in. (75 to 100 mm) from the inner coil sec-  
tion. See Fig. 11.  
5. Use a water hose or other suitable equipment to flush  
down between the 2 coil sections to remove dirt and  
debris. Clean the outer surfaces with a stiff brush in the  
normal manner.  
6. Reposition the outer coil section, attach the bracket re-  
moved in Step 4, and remove the coil corner post from  
between the top panel and side panel. Secure the sec-  
tions together. Install the coil corner post and replace  
all screws (removed in Step 2).  
II. LUBRICATION  
A. Compressors  
Fig. 11 — Separating Coil Sections  
Each compressor is charged with the correct amount of oil at  
the factory. Refer to the Oil Charge section on page 10 for ad-  
ditional information.  
III. CONDENSER-FAN ADJUSTMENT (Fig. 12)  
1. Shut off unit power supply.  
2. Remove condenser-fan assembly (grille, motor, motor cover,  
and fan).  
B. Fan Motor Bearings  
Fan motor bearings are of the permanently-lubricated type.  
No further lubrication is required.  
3. Loosen fan hub setscrews.  
4. Adjust fan height as shown in Fig. 12.  
5. Tighten set screws.  
6. Replace condenser-fan assembly.  
NOTE: Fan height adjustments are as follows:  
Fig. 9 — Cleaning Condenser Coil  
UNIT  
in.  
mm  
569C072  
4.50  
114  
All Units  
(except 569C072)  
6.42  
163  
Fig. 12 — Outdoor (Condenser) Fan Adjustment  
—11—  
IV. CAPACITY CONTROL (576B120 Only)  
8. Clean system. Add new liquid line filter drier.  
9. Install new compressor in unit.  
A suction pressure-actuated unloader controls 2 cylinders and  
provides capacity control. Unloaders are factory set (see  
Table 1A or 1B), but may be field adjusted:  
10. Connect suction and discharge lines to compressor. En-  
sure that compressor holddown bolts are in place.  
11. Connect wiring.  
12. Install crankcase heater.  
13. Evacuate and recharge unit, per Step VII.  
14. Restore unit power.  
A. Control Set Point  
The control set point (cylinder load point) is adjustable from  
0 to 85 psig (586 kPa). To adjust, turn control set point ad-  
justment nut (Fig. 13) clockwise to its bottom stop. In this  
position, set point is 85 psig (586 kPa). Then, turn adjust-  
ment counterclockwise to desired control set point. Every full  
turn counterclockwise decreases set point by 7.5 psig (51.7 kPa).  
VI. CRANKCASE HEATER (Except 569C072)  
The crankcase heater prevents refrigerant migration and com-  
pressor oil dilution during shutdown when compressor is not  
operating.  
B. Pressure Differential  
The pressure differential (difference between cylinder load and  
unload points) is adjustable from 6 to 22 psig (41.4 to 152 kPa).  
To adjust, turn pressure differential adjustment screw (Fig. 13)  
counterclockwise to its back stop position. In this position,  
differential is 6 psig (41.4 kPa). Then, turn adjustment screw  
clockwise to desired pressure differential. Every full turn clock-  
wise increases differential by 1.5 psig (10.3 kPa).  
Close both compressor service valves if applicable when crank-  
case heater is deenergized for more than 6 hours.  
VII. REFRIGERANT CHARGE  
Unit panels must be in place when unit is operating during  
charging procedure. Unit is shipped with a holding charge  
only. Weigh in 7 lbs (3 kg) of R-22 to start unit. Refer to GTAC II,  
Module 5, Charging, Recovery, Recycling, and Reclamation  
for additional information.  
See Troubleshooting Guide on page 14 for additional  
information.  
A. Low Charge Cooling  
Using Cooling Charging Charts, Fig. 14 and 15, vary refrig-  
erant until the conditions of the appropriate chart are met.  
Note the charging charts are different from type normally used.  
The charts are based on charging the units to the correct sub-  
cooling for the various operating conditions. Accurate pres-  
sure gage and temperature sensing device are required. Con-  
nect the pressure gage to the service port on the liquid line  
service valve. Mount the temperature sensing device on the  
liquid line, close the liquid line service valve, and insulate it  
so that outdoor ambient temperature does not affect the read-  
ing. Indoor-air cfm must be within the normal operating range  
of the unit.  
Operate unit a minimum of 15 minutes. Ensure that tem-  
perature and pressure have stabilized. Plot liquid pressure  
and temperature on chart and add or reduce charge as re-  
quired. Do not vent refrigerant to the atmosphere. Recover  
any excess charge. Operate the unit until the system stabi-  
lizes. Adjust charge to conform with charging chart, using liq-  
uid pressure and temperature to read chart.  
Fig. 13 — Compressor Capacity Control Unloader  
B. Refrigerant Leaks  
V. COMPRESSOR REMOVAL  
Proceed as follows to repair a refrigerant leak and to charge  
the unit:  
1. Locate the leak and ensure that refrigerant system pres-  
sure has been relieved.  
See Tables 1A and 1B for compressor information.  
Follow safety codes and wear safety glasses and work gloves.  
1. Shut off power to unit. Remove unit access panel (front  
of unit).  
2. Repair leak following accepted practices.  
2. Remove refrigerant from system using refrigerant re-  
moval methods described in GTAC II, Module 5, Charg-  
ing, Recovery, Recycling, and Reclamation.  
3. Disconnect compressor wiring at compressor terminal  
box.  
NOTE: Install a new filter drier in the liquid line whenever  
the system has been opened for repair.  
3. Add a small charge of R-22 refrigerant vapor to system  
and leak-test unit.  
4. Evacuate refrigerant system if additional leaks are not  
found.  
4. Remove bolts from suction flange and discharge serv-  
ice valve (576B Units).  
5. Charge unit with R-22 refrigerant.  
CAUTION: Excessive movement of copper lines at  
compressor may cause higher levels of vibration when  
unit is restored to service.  
NOTE: Do not vent refrigerant to the atmosphere. Recover  
any excess charge.  
5. Remove crankcase heater from compressor base (576B  
units only).  
VIII. REFRIGERANT SERVICE PORTS  
Each unit has 3 service ports: one on the suction line, one on  
the liquid line, and one on the compressor discharge line. Be  
sure caps on the ports are tight.  
6. Remove compressor holddown bolts.  
7. Remove compressor from unit.  
—12—  
Fig. 15 — Cooling Charging Chart — 569C090,120  
and 576B090,102,120  
Fig. 14 — Cooling Charging Chart — 569C072  
—13—  
TROUBLESHOOTING GUIDE  
CAUSE  
SYMPTOM  
REMEDY  
Compressor does not run —  
Contactor open  
Power off.  
Restore power.  
Fuses blown.  
Replace with correct fuses after finding cause  
and correcting.  
Transformer open/shorted.  
Replace transformer if primary windings are  
receiving power and no output.  
Thermostat circuit open.  
Check thermostat setting.  
Low-pressure switch open.  
Check for refrigerant undercharge or system  
leak.  
High-pressure switch open.  
Check for refrigerant over charge or  
obstruction of outdoor airflow.  
Connections loose.  
Tighten all connections.  
Compressor motor thermostat open.  
Compressor leads loose, broken.  
Single phasing.  
Check for excessive motor temperature.  
Check connections with power off.  
Replace blown fuse.  
Compressor does not run —  
Contactor closed  
Compressor internal overload open.  
Allow compressor motor windings to cool down to reset  
overload. Determine cause for overload opening.  
Compressor cycles on high-  
pressure switch —  
Condenser fan on  
High-pressure switch faulty.  
Airflow restricted. Dirty coil.  
Air recirculating.  
Replace switch.  
Remove obstruction, clean condenser coil.  
Clear airflow area.  
Noncondensables in system.  
Recover, evacuate and recharge as required. Refer to  
Carrier GTAC-II, Module 5, Charging, Recovery,  
Recycling, and Reclamation.  
Refrigerant overcharge.  
Recover as required.  
Refrigerant system restrictions.  
Check or replace filter drier, expansion  
valve, etc.  
Compressor cycles on high-  
pressure switch —  
Condenser fan off  
Fan slips on shaft.  
Motor not running.  
Tighten fan hub screws.  
1
3
Check power and capacitor  
Replace motor.  
3
and  
4  
hp motor.  
Motor bearings seized.  
Motor overload open.  
Check overload rating. Check for  
fan blade obstruction.  
Motor burned out, windings open.  
Filter drier plugged.  
Replace motor.  
Compressor cycles on low-  
pressure switch —  
Evaporator fan running  
Replace filter drier.  
Replace power head.  
Expansion valve power head  
defective.  
Low refrigerant charge.  
Expansion valve restricted/plugged.  
Evaporator coil iced up.  
Evaporator coil dirty.  
Find leak, repair, evacuate system, and recharge.  
Remove and replace expansion valve.  
Check refrigerant charge.  
Clean coil fins.  
Airflow restricted —  
Low suction pressure  
Indoor-air filter dirty.  
Clean or replace filters.  
Check damper operation and position.  
Tighten all connections.  
Replace relay.  
Indoor-air dampers closed.  
Electrical connections loose.  
Fan relay defective.  
Indoor (evaporator) fan stopped —  
Low suction pressure  
Motor overload open.  
Motor defective.  
Check power supply.  
Replace motor.  
Fan belt broken or slipping.  
Refrigerant charge low.  
Head pressure low.  
Replace or tighten belt.  
Add charge.  
Compressor runs but  
cooling insufficient —  
Suction pressure low  
Check refrigerant charge.  
Clean or replace filters.  
Replace power head.  
Indoor-air filters dirty.  
Expansion valve power head  
defective.  
Expansion valve restricted/plugged.  
Evaporator coil partially iced.  
Evaporator airflow restricted.  
Heat load excessive.  
Remove and replace expansion valve.  
Check low-pressure setting.  
Remove obstruction.  
Compressor runs but  
cooling insufficient —  
Suction pressure high  
Check for open doors or windows.  
NOTE: See Fig. 16 and 17 for component arrangements.  
—14—  
LEGEND FOR FIG. 16 AND 17  
C
Contactor, Compressor  
Capacitor  
LPS  
NEC  
OFC  
OFM  
OL  
QT  
TB  
TDR  
TRAN  
Low-Pressure Switch  
National Electrical Code  
Outdoor (Condenser) Fan Contactor  
Outdoor (Condenser) Fan Motor  
Overload Relay  
Quadruple Terminal  
Terminal Block  
Time-Delay Relay  
Terminal (Marked)  
CAP  
CB  
Terminal (Unmarked)  
Circuit Breaker  
CH  
Crankcase Heater  
Compressor Lockout  
Compressor Motor  
Compressor Temperature Protection  
Equipment  
Ground  
High-Pressure Switch  
Terminal Block  
CLO  
COMP  
COTP  
EQUIP  
GND  
HPS  
Factory Wiring  
Field Power Wiring  
Transformer  
Fig. 16 — Typical 569C Wiring Schematic and Component Arrangement  
Fig. 17 — Typical 576B Wiring Schematic and Component Arrangement  
—15—  
Copyright 1999 Bryant Heating & Cooling Systems  
CATALOG NO. 5356-902  
START-UP CHECKLIST  
I. PRELIMINARY INFORMATION  
OUTDOOR: MODEL NO.  
SERIAL NO.  
INDOOR: AIR HANDLER MANUFACTURER  
MODEL NO.  
SERIAL NO.  
ADDITIONAL ACCESSORIES  
II. PRE-START-UP  
OUTDOOR UNIT  
IS THERE ANY SHIPPING DAMAGE?  
IF SO, WHERE:  
(Y/N)  
WILL THIS DAMAGE PREVENT UNIT START-UP?  
(Y/N)  
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?  
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)  
(Y/N)  
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?  
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?  
(Y/N)  
(Y/N)  
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?  
(Y/N)  
CONTROLS  
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING  
CONNECTIONS MADE AND CHECKED?  
(Y/N)  
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?  
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?  
(Y/N)  
(Y/N)  
INDOOR UNIT  
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?  
ARE PROPER AIR FILTERS IN PLACE? (Y/N)  
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?  
(Y/N)  
(Y/N)  
DO THE FAN BELTS HAVE PROPER TENSION?  
(Y/N)  
HAS CORRECT FAN ROTATION BEEN CONFIRMED?  
(Y/N)  
PIPING  
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE EVAPORATOR COIL AS REQUIRED?  
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR,  
(Y/N)  
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS  
WITH A LEAK DETECTOR? (Y/N)  
LOCATE, REPAIR, AND REPORT ANY LEAKS.  
ARE ALL 576B COMPRESSOR SERVICE VALVES FULLY OPENED (BACKSEATED)?  
(Y/N)  
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED?  
(Y/N)  
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE ON 576B UNIT IN VIEW IN THE COMPRESSOR SIGHT GLASS?  
(Y/N)  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
AB  
V
AC  
V
BC  
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =  
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
—CL-1—  
III. START-UP  
CHECK EVAPORATOR-FAN SPEED AND RECORD.  
CHECK CONDENSER-FAN SPEED AND RECORD.  
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
OIL PRESSURE (576B only)  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER-AIR TEMP  
LEAVING CONDENSER-AIR TEMP  
EVAP ENTERING-AIR DB (dry bulb) TEMP  
EVAP ENTERING-AIR WB (wet bulb) TEMP  
EVAP LEAVING-AIR DB TEMP  
EVAP LEAVING-AIR WB TEMP  
COMPRESSOR AMPS (L1/L2/L3)  
/
/
HAS REFRIGERANT CHARGE BEEN ADJUSTED PER UNIT CHARGING CHART?  
NOTES:  
Copyright 1999 Bryant Heating & Cooling Systems  
CATALOG NO. 5356-902  
—CL-2—  

Carrier 38BRC User Manual
Dacor Beverage Dispenser DYWS4 User Manual
Daewoo DOC 091R User Manual
Danby Products Air Conditioner SHCC6026 User Manual
Exide FLOODED FLAT PLATE FAST CHARGE MOTIVE POWER BATTERIES GB4145 2011 10 User Manual
Field Controls UV 18X User Manual
Garmin STYLUS PRO PRO WT7900 User Manual
GE VERTICAL ZONELINE 2010 User Manual
GE ZONELINE 2800 User Manual
HP Hewlett Packard LaserJet 4345mfp User Manual