Bryant 538J 18 1 User Manual

installation, start-up and  
service instructions  
LIGHT COMMERCIAL  
CONDENSING UNITS  
538J  
Sizes 018-060  
Cancels: New  
II 538J -18-1  
1/15/02  
CONTENTS  
I. COMPLETE PRE-INSTALLATION CHECKS  
A. Unpack Unit  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Move unit to final location. Remove unit packaging being  
careful not to damage service valves or grilles.  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-7  
I. Complete Pre-Installation Checks . . . . . . . . . . . . . . 1  
II. Rig and Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
III. Complete Refrigerant Piping Connections . . . . . . . 3  
IV. Make Electrical Connections . . . . . . . . . . . . . . . . 4  
V. Accessory Installation. . . . . . . . . . . . . . . . . . . . . . . . 4  
B. Inspect Shipment  
File claim with shipping company if shipment is damaged or  
incomplete. Check unit nameplate to ensure unit matches  
job requirements.  
C. Consider System Requirements  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9  
Consult local building codes and NEC for special installation  
requirements.  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
I. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
II. Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
III. Cleaning Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Allow sufficient space for airflow clearance, wiring, refriger-  
ant piping, and servicing unit. See Fig. 1 and 2. Unit can be  
mounted on a level pad directly on base legs or mounted on  
raised pads at support points. See Fig. 2 for center of gravity.  
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
SAFETY CONSIDERATIONS  
Installing and servicing air-conditioning equipment can be  
hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install or service air-conditioning equipment.  
Untrained personnel may perform basic maintenance such  
as cleaning and replacing filters. All other operations should  
be performed by trained service personnel. When working on  
air-conditioning equipment, observe safety precautions in  
literature, and on tags and labels attached to unit.  
C
O
O
LIN  
G
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for brazing operations. Have a fire extin-  
guisher available. Read these instructions thoroughly. Con-  
sult local building codes and National Electrical Code (NEC,  
U.S.A. Standard) for special installation requirements.  
INSTALLATION  
WARNING: Before installing or servicing system,  
always turn off main power to system. There may be  
more than one disconnect switch. Turn off accessory  
heater power if applicable. Electrical shock can cause  
personal injury.  
Fig. 1 — Typical Condensing Unit  
II. RIG AND MOUNT UNIT  
A. Mounting on Ground  
Mount unit on a solid, level concrete pad. Position unit so  
water or ice from roof does not fall directly into unit. Field-  
fabricated stacking kits can be used when units are to be  
stacked. If conditions or local codes require unit to be fas-  
tened to a pad, 6 field-supplied tiedown bolts should be used  
and fastened through slots provided in unit mounting feet.  
B. Mounting on Roof  
Mount unit on level platform or frame at least 6 in. above  
roof surface. Isolate unit and tubing from structure.  
C. Rigging  
CAUTION: Be sure unit panels are securely in  
place prior to rigging.  
Fig. 3 — Lifting Unit with Sling  
Keep unit upright. Lift unit using sling. Use cardboard or  
padding under sling, and spreader bars to prevent sling  
damage to unit. See Fig. 3. See Fig. 2 for center of gravity ref-  
erence. Install unit so coil does not face into prevailing  
winds. If this is not possible and constant winds above  
25 mph are expected, use field-fabricated wind baffle.  
A. Check AccuRater® Control  
The AccuRater refrigerant control is required for cooling sys-  
tem capacity optimization. An AccuRater device with field-  
replaceable piston should be supplied with the indoor unit.  
Refer to AccuRater metering device table in separate indoor  
unit installation instructions to determine the correct Accu-  
Rater piston size required for the condenser/evaporator sys-  
tem being installed.  
NOTE: Accessory wind baffles should be used on all units  
with accessory low-ambient control.  
Field-fabricated snow stand may be used to raise unit when  
operation will be required during the winter. Units may also  
be wall mounted using the accessory wall mounting kit.  
Note that one of 2 types of the AccuRater devices can be  
used. Use Type A only if Type B is unavailable. See Fig. 4. Do  
not interchange components between AccuRater device  
types. Matching of outdoor unit with indoor unit may require  
field replacement of piston. Replace piston, if required,  
before connecting refrigerant lines. Piston replacement  
instructions are included in the indoor unit installation  
instructions. After system installation is complete, see  
Refrigerant Charging section on page 8 to check and/or  
adjust refrigerant charge.  
III. COMPLETE REFRIGERATION PIPING CONNECTIONS  
Outdoor units may be connected to indoor units using field-  
supplied tubing of refrigerant grade and condition. See  
Tables 1A and 1B for correct line sizes. Do not use less than  
10 ft (3 m) of interconnecting tubing.  
CAUTION: DO NOT BURY MORE THAN 36 IN.  
(922 mm) OF REFRIGERANT PIPE IN THE  
GROUND. If any section of pipe is buried, there must  
be a 6 in. (154 m) vertical rise to the valve connections  
on the outdoor unit. If more than the recommended  
length is buried, refrigerant may migrate to the cooler,  
buried section during extended periods of system shut-  
down. This causes refrigerant slugging and could dam-  
age compressor at start-up.  
The 538J series units may also be installed with units using  
a thermostatic expansion valve (TXV). If a TXV is used, be  
sure to remove the piston from the indoor coil. See installa-  
tion instructions shipped with the TXV for proper position-  
ing and adjustment.  
When more than 50 ft (15.2 m) of interconnecting tubing and  
more than 30 ft (9.1 m) of vertical lift is used, refer to Part 3  
of the System Design Manual for design details, or contact  
your local distributor.  
If either refrigerant tubing or indoor coil is exposed to atmo-  
spheric conditions for longer than 5 minutes, it must be evac-  
uated to 1000 microns to eliminate contamination and  
moisture in the system.  
TYPE A (FIELD-INSTALLED BYPASS TYPE)  
Run refrigerant tubes as directly as possible, avoiding  
unnecessary turns and bends. Suspend refrigerant tubes so  
they do not damage insulation on vapor tube and do not  
transmit vibration to the structure. Also, when passing  
refrigerant tubes through the wall, seal opening so that  
vibration is not transmitted to structure. Leave some slack  
in refrigerant tubes between structure and outdoor unit to  
absorb vibration. Refer to separate indoor unit installation  
instructions for additional information.  
TYPE B (RECOMMENDED)  
NOTE: Arrow on AccuRater body points in free-flow direction, away  
from the indoor coil.  
Fig. 4 — AccuRater Metering Device Components  
3—  
B. Make Piping Sweat Connections  
switch, fuses, and field wiring must be in compliance with  
NEC (U.S.A. Standard) and applicable local codes. Use mini-  
mum 60 C wire for field power connection.  
Remove plastic caps from liquid and suction service valves.  
Use refrigerant grade tubing. Service valves are closed from  
the factory and ready for brazing. After wrapping the service  
valve with a wet cloth, the tubing set can be brazed to the  
service valve using either silver bearing or non-silver bear-  
ing brazing material. Consult local code requirements.  
Refrigerant tubing and indoor coil are ready for leak testing.  
Route power wires through opening in the unit side panel  
and connect in unit control box as shown on unit label dia-  
gram and Fig. 5 and 6. Unit must be grounded.  
B. Control Circuit Wiring  
Control voltage is 24 v. See Fig. 5 and unit label diagram for  
field-supplied wiring details. Route control wire through  
opening in the unit side panel to connection in unit control  
box.  
NOTE: Unit is shipped with a full factory charge of R-22  
refrigerant as indicated on nameplate.  
Pass nitrogen or other inert gas through piping while braz-  
ing to prevent formation of copper oxide.  
NOTE: For wire runs up to 50 ft (15 m), use no. 18 AWG  
(American Wire Gage) insulated wire (35 C minimum). For  
50 to 75 ft (15 to 23 m), use no. 16 AWG insulated wire. For  
more than 75 ft (23 m), use no. 14 AWG insulated wire. See  
Table 2 for conversion to European wire sizes.  
CAUTION: To avoid damage while brazing, service  
valves should be wrapped in a heat-sinking material  
such as a wet cloth.  
NOTE: Operation of unit on improper line voltage constitutes  
abuse and could affect any applicable warranty. See Table 3.  
Do not install unit in system where voltage may fluctuate  
above or below permissible limits.  
CAUTION: When brazing tubing sets to the ser-  
vice valves, a brazing shield must be used to prevent  
damage to the painted unit surface.  
See Table 3 for recommended fuse sizes. When making elec-  
trical connections, provide clearance at unit for refrigerant  
piping connections.  
C. Provide Safety Relief  
A fusible plug is located in unit suction line; do not cap this  
plug. If local code requires additional safety devices, install  
as directed.  
Use indoor unit transformer as 24-v (40-va minimum) supply  
for system as shown in Fig. 5 or use accessory transformer.  
IV. MAKE ELECTRIAL CONNECTIONS  
WARNING: Before performing service or mainte-  
nance, be sure the indoor unit main power switch is off  
and indoor blower has completely stopped. Failure to  
do so may result in electrical shock or injury from  
rotating fan blades.  
WARNING: Unit cabinet must have an uninter-  
rupted, unbroken electrical ground to minimize the  
possibility of personal injury if an electrical fault  
should occur. This ground may consist of electrical wire  
connected to the unit ground lug in control compart-  
ment, or conduit approved for electrical ground when  
installed in accordance with NEC, ANSI/NFPA (Ameri-  
can National Standards Institute/National Fire Protec-  
tion Association) 70, and local electrical codes. Failure  
to follow this warning could result in the installer  
being liable for personal injury to others.  
C. Connections to Duct-Free Fan Coil Units  
The 538J units are designed for easy match-up to 619C,  
619F, 619ENX018 and 619ENX024 duct-free fan coils. These  
units provide 24-v power for the outdoor unit from the fan  
coil. Connect the Y and C terminals of the indoor unit to the  
blue and brown wires of the outdoor unit with 20 gage (mini-  
mum) thermostat wire.  
CAUTION: Unit failure as a result of operation on  
improper line voltage or excessive phase imbalance  
constitutes abuse and may cause damage to electrical  
components. Such operation will invalidate any appli-  
cable warranty.  
V. ACCESSORY INSTALLATION  
Install all unit accessories per accessory installation instruc-  
tions prior to start-up.  
Do not use accessory Time Guard® II device when combining  
a 538J unit with 619E indoor units.  
A. Power Wiring  
When ambient temperature will fall below 55 F (13 C), acces-  
sory low ambient controller (part no. 53DS900060) is  
required. When accessory low ambient kit is used, unit  
should also be equipped with accessory winter start kit and  
field-fabricated wind baffles.  
Unit is factory-wired for voltage shown on nameplate. Pro-  
vide adequate, fused disconnect switch within sight of unit,  
readily accessible but out of reach of children. Provision for  
locking the switch open (off) is advisable to prevent power  
from being turned on while unit is being serviced. Disconnect  
4—  
Table 1A — Physical Data (English)  
UNIT 538J  
NOMINAL CAPACITY (Btuh)  
UNIT OPERATING WEIGHT (lb)  
018  
18,000  
130  
024  
24,000  
136  
030  
30,000  
161  
036  
36,000  
185  
048  
48,000  
222  
060  
60,000  
249  
COMPRESSOR  
Type  
Hermetic  
Copeland  
Scroll  
ZR18KC-PFV  
25/21  
Copeland  
Scroll  
ZR24KC-PFV  
25/21  
Copeland  
Scroll  
Copeland  
Scroll  
Copeland  
Scroll  
ZR47KC-PFV  
42/38  
Copeland  
Scroll  
ZR57KC-PFV  
56/52  
Model  
Oil (oz) Initial/Recharge  
ZR28KC-PFV  
38/34  
ZR34KC-PFV  
42/38  
OUTDOOR FAN  
Rpm  
Propeller Type, Direct Drive, Horizontal  
850  
850  
850  
850  
850  
850  
Diameter (in.)...No. of Blades  
Fan Pitch (Deg)  
Motor Hp  
18...3  
18...3  
18...3  
18...3  
24...3  
24...3  
25  
27  
27  
31  
24  
24  
1
1
1
1
1
1
/
/
/
/
/
/
4
8
8
8
8
4
Nominal Airflow (Cfm)  
1720  
1720  
1720  
1720  
3900  
3900  
OUTDOOR COIL  
Face Area (sq ft)...No. of Rows  
Fins per in.  
Copper Tube, Aluminum Plate Fin  
6.1...1  
20  
6.1...1.5  
20  
6.1...2  
20  
6.1...2  
20  
12.3...1.5  
20  
12.3...1.75  
20  
CONTROLS PRESSURESTAT SETTINGS  
Low Pressure  
Cutout (psig)  
7
3
5
Cut-In (psig)  
Fusible Plug  
22  
210 F  
NOTE: Line sizes are for runs up to 25 feet.  
Table 1B — Physical Data (SI)  
UNIT 538J  
NOMINAL CAPACITY (kW)  
UNIT OPERATING WEIGHT (kg)  
018  
5.3  
58.9  
024  
7.0  
61.6  
030  
8.8  
73.0  
036  
10.5  
83.9  
048  
14.1  
100.6  
060  
17.6  
112.9  
COMPRESSOR  
Type  
Hermetic  
Copeland  
Scroll  
ZR18KC-PFV  
.74/.62  
Copeland  
Scroll  
ZR24KC-PFV  
.74/.62  
Copeland  
Scroll  
Copeland  
Scroll  
Copeland  
Scroll  
ZR47KC-PFV  
1.25/1.13  
Copeland  
Scroll  
ZR57KC-PFV  
1.66/1.54  
Model  
Oil (L) Initial/Recharge  
ZR28KC-PFV  
1.13/1.00  
ZR34KC-PFV  
1.25/1.13  
OUTDOOR FAN  
R/s  
Propeller Type, Direct Drive, Horizontal  
14.2  
457...3  
25  
14.2  
457...3  
27  
14.2  
457...3  
27  
14.2  
457...3  
31  
14.2  
610...3  
24  
14.2  
610...3  
24  
Diameter (mm)...No. of Blades  
Fan Pitch (Deg)  
Motor kW  
.13  
.09  
.09  
812  
.09  
.19  
.19  
Nominal Airflow (L/s)  
812  
812  
812  
1840  
1840  
OUTDOOR COIL  
Copper Tube, Aluminum Plate Fin  
2
Face Area (m )...No. of Rows  
.57...1  
.8  
.57...1.5  
.8  
.57...2  
.8  
.57...2  
.8  
1.14...1.5  
.8  
1.14...1.75  
.8  
Fins per mm  
CONTROLS PRESSURESTAT SETTINGS  
Low Pressure  
Cutout (kPa)  
48 21  
152 34  
99 C  
Cut-In (kPa)  
Fusible Plug  
NOTE: Line sizes are for runs up to 7.6 m.  
5—  
LEGEND  
*The IFR and IFM are located in indoor unit on heating-cooling applications. If accessory  
IFR is required for cooling-only applications, locate (IFR) in fan coil.  
NOTES:  
1. Refer to unit wiring label for wire colors: BRN to BLU and C to Y connections.  
2. Arrangement A, B and C are for use with residential fan coils.  
C
Contactor (12-va)  
Heating Control  
Indoor-Fan Motor  
Indoor-Fan Relay  
HC  
IFM  
IFR  
TRANS — Transformer  
Field Wiring  
Factory Wiring  
Fig. 5 — Typical Control Circuit Connections  
LEGEND  
NEC — National Electrical Code  
(U.S.A. Standard)  
Terminal Board  
Transformer  
TB  
Field Wiring  
Factory Wiring  
Fig. 6 — Line Power Connections  
6—  
Table 2 — American/European Wire Conversions  
SERVICE  
AMERICAN  
EUROPEAN  
WARNING: Before performing recommended main-  
tenance, be sure unit main power switch is off. Failure to  
do so may result in electrical shock or injury from rotat-  
ing fan blade.  
Industry  
Standard Size  
American Conversion  
Industry Standard  
2
(mm)  
Size (mm )  
18 AWG  
16 AWG  
14 AWG  
12 AWG  
10 AWG  
8 AWG  
0.82  
1.30  
1.0  
1.5  
2.08  
2.5  
3.30  
4.0  
5.25  
6.0  
I. OUTDOOR FAN  
6.36  
10.0  
16.0  
25.0  
A reinforced wire mount holds the outdoor fan assembly in  
place. See Fig. 7 for proper mounting positions.  
6 AWG  
13.29  
21.14  
26.65  
33.61  
42.39  
53.49  
67.42  
85.00  
107.19  
4 AWG  
3 AWG  
2 AWG  
35.0  
50.0  
70.0  
95.0  
120.0  
1 AWG  
1/0 AWG  
2/0 AWG  
3/0 AWG  
4/0 AWG  
250 kcmil  
300 kcmil  
350 kcmil  
400 kcmil  
500 kcmil  
600 kcmil  
126.64  
151.97  
177.90  
202.63  
253.29  
303.95  
150.0  
185.0  
240.0  
300.0  
LEGEND  
UNIT 538J DIMENSIONS — in. (mm)  
AWG — American Wire Gage  
kcmil — Thousand Circular Mils  
018  
0.433 (11)  
024-036  
0.709 (18)  
048-060  
0.16 (4)  
START-UP  
I. PRELIMINARY CHECKS  
Fig. 7 — Condenser Fan Mounting Positions  
II. HIGH-PRESSURE RELIEF VALVE  
1. Check that all internal wiring connections are tight  
and that barriers, covers, and panels are in place.  
Valve is located in compressor. Relief valve opens at a  
pressure differential of approximately 450 ± 50 psig (3100 ±  
345 kPa) between suction (low side) and discharge (high  
side) to allow pressure equalization.  
2. Make certain field electrical power source agrees  
with unit nameplate rating.  
3. Open all service valves.  
III. INTERNAL CURRENT AND TEMPERATURE SENSITIVE  
OVERLOAD  
II. LEAK TEST  
Field piping and fan coil must be leak tested by the pressure  
method. Use R-22 at approximately 25 psig (172 kPa) backed  
up with an inert gas to a total pressure not to exceed  
245 psig (1690 kPa).  
Control resets automatically when internal compressor  
motor temperature drops to a safe level (overloads may  
require up to 45 minutes to reset). When an internal over-  
load is suspected of being open, check by using an ohmmeter  
or continuity tester.  
III. EVACUATE AND DEHYDRATE  
Field piping and fan coil must be evacuated and dehydrated.  
IV. PUMPDOWN PROCEDURE  
The system may be pumped down in order to make repairs  
on low side without losing complete refrigerant charge.  
IV. CHARGE SYSTEM  
Release factory charge into system by opening (backseating)  
liquid and suction line service valves. Add charge amount as  
required for the total system. Refer to separate indoor unit  
installation instructions for the required total system charge  
when connected to the indoor unit.  
To pump down:  
1. Attach pressure gage to suction service valve gage  
port.  
2. Frontseat the liquid line valve.  
V. TO START UNIT  
CAUTION: The 538J unit coils hold only the  
factory-designated amount of refrigerant. Additional  
refrigerant may cause units to relieve pressure  
through compressor internal pressure relief valve  
(indicated by sudden rise of suction pressure) before  
suction pressure reaches 5 psig (34 kPa). If this occurs,  
shut off unit immediately, then frontseat the suction  
valve and remove and reclaim excess refrigerant fol-  
lowing accepted practice.  
NOTE: When using 538J unit in conjunction with 619 series  
fan coils, refer to start-up instructions included with fan coil  
for correct start-up procedures.  
Be sure that field disconnect is closed. Set room thermostat  
below ambient temperature. Operate unit for 15 minutes,  
then check system refrigerant charge. See Refrigerant  
Charging section on page 8.  
Unit compressor starts after a 5-minute delay if equipped  
with accessory Time Guard® II device.  
3. Start unit and run until suction pressure reaches  
5 psig (34 kPa).  
4. Shut unit off and frontseat suction valve.  
5. Depressurize low side of unit and recover refrigerant  
following accepted practice.  
7—  
Table 3 — Electrical Data  
OPERATIONAL  
VOLTAGE*  
COMPRESSOR  
POWER SUPPLY  
538J  
V-PH-Hz  
Max Fuse† or HACR-Type  
Min  
Max  
RLA  
LRA  
Fan FLA  
MCA  
Ckt Bkr Amps  
018  
024  
030  
036  
048  
060  
10.7  
13.2  
15.7  
15.7  
24.3  
28.6  
47.0  
59.0  
.70  
.70  
.70  
.70  
.45  
.45  
14.1  
17.2  
20.3  
20.3  
31.8  
37.2  
25  
30  
35  
35  
50  
65  
73.0  
93.0  
208/230-1-60  
187  
254  
131.0  
170.0  
LEGEND  
Full Load Amps  
2. All motors and compressors contain internal overload protection.  
3. In compliance with NEC (U.S.A. Standard) requirements for multimotor  
and combination load equipment (refer to NEC Articles 430 and 440), the  
overcurrent protective device for the unit shall be fuse or HACR breaker.  
4. Motor RLA values are established in accordance with UL (Underwriters’  
Laboratories) Standard 465 (U.S.A. Standard).  
FLA  
HACR — Heating, Air Conditioning, Refrigeration  
LRA  
MCA  
NEC  
RLA  
Locked Rotor Amps  
Minimum Circuit Amps per NEC Section 430-24  
National Electrical Code (U.S.A. Standard)  
Rated Load Amps (Compressor)  
*Permissible limits of the voltage range at which unit will operate  
satisfactorily.  
†Time-delay fuse.  
NOTES:  
1. Control circuit is 24 v on all units and requires an external power source.  
V. LOW PRESSURE SWITCH  
hole, sealing surface around piston cones, and fluted  
portion of piston are not damaged.  
6. Clean piston refrigerant metering hole.  
7. Replace retainer O-ring before reassembling Accu-  
Rater device (O-ring part no. 99CC501052).  
This switch, mounted on the suction line, has fixed non-  
adjustable settings. To check pressure switch, attach pres-  
sure gage to suction service valve gage port. Slowly close  
liquid shutoff valve and allow compressor to pump down. Do  
not allow compressor to pump down below 2 psig (14 kPa).  
Compressor should shut down when suction pressure drops  
to cutout pressure in Tables 1A and 1B, and should restart  
when pressure builds up to cut-in pressure shown after  
accessory CLO (compressor lockout) switch has been reset  
and accessory Time Guard® II device has completed its tim-  
ing cycle.  
VIII. REFRIGERANT CHARGING  
WARNING: To prevent personal injury, wear  
safety glasses and gloves when handling refrigerant.  
Do not overcharge system — this can cause compressor  
flooding.  
NOTE: Do not vent or depressurize unit refrigerant to atmo-  
sphere. Remove and recover refrigerant following practice.  
VI. SERVICE VALVES  
The service valves in the outdoor unit come from the factory  
frontseated. This means the refrigerant charge is isolated  
from the line-set connection ports. To prevent damage to the  
valve, use a wet cloth or other acceptable heat sink material  
on the valve before brazing.  
A. Superheat Method (Cooling, Non-TXV)  
To check and adjust charge during cooling season, use  
Tables 4A-5B and the following procedure:  
1. Operate unit a minimum of 15 minutes before check-  
ing charge.  
2. Measure suction pressure by attaching a gage to suc-  
tion valve service port.  
3. Measure suction line temperature by attaching a ser-  
vice thermometer to unit suction line near suction  
valve. Insulate thermometer for accurate readings.  
4. Measure outdoor coil inlet-air dry bulb temperature  
with a second thermometer.  
5. Measure indoor coil inlet-air wet bulb temperature  
with a sling psychrometer.  
6. Refer to Tables 4A and 4B. Find air temperature enter-  
ing outdoor coil and wet-bulb temperature entering  
indoor coil. At this intersection, note the superheat  
temperature.  
7. Refer to Tables 5A and 5B. Find superheat tempera-  
ture and suction pressure and note suction line  
temperature.  
8. If unit has higher suction line temperature than  
charted temperature, add refrigerant until charted  
temperature is reached.  
The service valves must be backseated (turned counterclock-  
wise until seated) before the service port caps can be  
removed and the hoses of the gage manifold connected. In  
this position, refrigerant has access from the through out-  
door and indoor unit. The service valve cannot be field  
repaired; only a complete valve or valve stem seal and  
service port caps are available for replacement.  
VII. ACCURATER® (BYPASS TYPE) DEVICE  
See Fig. 4 for bypass type AccuRater device components. The  
piston has a refrigerant metering hole through it. The  
retainer forms a stop for the piston in the refrigerant bypass  
mode and a sealing surface for liquid line flare connection.  
To check, clean or replace piston:  
1. Shut off power to unit.  
2. Pump down using Pumpdown Procedure section on  
page 7.  
3. Remove liquid line flare connection from AccuRater  
device.  
4. Pull retainer out of body, being careful not to scratch  
flare sealing surface. If retainer does not pull out  
easily, carefully use locking pliers to remove retainer.  
5. Slide piston out by inserting a small soft wire, with  
small kinks, through metering hole. Ensure metering  
9. If unit has lower suction line temperature than  
charted temperature, remove and recover refrigerant  
until charted temperature is reached.  
8—  
10. If air temperature entering outdoor coil or pressure  
at suction valve changes, charge to new suction line  
temperature indicated on chart.  
Table 5A — Required Suction-Tube Temperature (F)  
— English (Entering Suction Service Valve)  
SUCTION PRESSURE AT SERVICE PORT (psig)  
61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7  
SUPERHEAT  
TEMP (F)  
NOTE: The above procedure is independent of indoor air  
quantity.  
0
2
4
6
8
35  
37  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
36  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
91  
B. Subcooling Method (Cooling, TXV)  
To check and adjust charge during cooling season, use  
Tables 6A and 6B and the following procedure:  
1. Operate unit a minimum of 15 minutes before check-  
ing charge.  
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
36  
38  
40  
2. Measure liquid line temperature near liquid line ser-  
vice valve, and measure liquid pressure at liquid line  
service valve. Use a digital thermometer for all tem-  
perature measurements. DO NOT use mercury or  
dial-type thermometers.  
3. Refer to Tables 6A and 6B. Find temperature point at  
which the required subcooling temperature intersects  
the measured liquid line pressure.  
4. If the measured liquid line temperature does not  
agree with the required liquid line temperature, ADD  
refrigerant to lower the temperature, or REMOVE  
refrigerant to raise the temperature (allow a toler-  
ance of ± 3 F).  
Table 4A — Superheat Charging Table — English  
(Superheat Entering Suction Service Valve)  
Table 5B — Required Suction-Tube Temperature (C)  
— SI (Entering Suction Service Valve)  
INDOOR COIL ENTERING AIR (F) WB  
50 52 54 56 58 60 62 64 66 68 70 72 74 76  
OUTDOOR  
TEMP (F)  
SUCTION PRESSURE AT SERVICE PORT (kPa)  
424 443 463 483 503 524 546 568 591  
SUPERHEAT  
TEMP (C)  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
105  
110  
115  
9
7
*
*
*
*
*
*
*
*
*
*
*
12 14 17 20 23 26 29 32 35 37 40 42 45  
10 12 15 18 21 24 27 30 33 35 38 40 43  
0
1
2
3
4
6
7
8
9
10  
11  
12  
13  
14  
16  
17  
18  
19  
20  
21  
22  
2
3
4
5
6
7
8
9
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
3
4
5
6
7
4
5
6
7
8
5
6
7
8
9
6
7
8
7
8
9
8
9
9
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
27  
28  
29  
31  
32  
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
27  
28  
29  
31  
32  
33  
6
*
10 13 16 19 21 24 27 30 33 36 38 41  
10 13 16 19 21 24 27 30 33 36 39  
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
27  
28  
29  
31  
7
9
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
26  
26  
27  
28  
29  
*
*
*
*
*
*
*
*
*
*
6
*
9
5
*
*
*
*
*
*
*
12 15 18 21 24 28 31 34 37  
12 15 18 21 25 28 31 35  
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
27  
28  
*
*
*
*
*
*
*
*
8
8
9
9
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
27  
*
*
*
*
*
*
*
*
8
5
11 15 19 22 26 30 33  
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
26  
*
*
*
*
*
*
9
6
13 16 20 24 27 31  
10 14 18 22 25 29  
11  
12  
13  
14  
15  
16  
17  
18  
19  
21  
22  
23  
24  
25  
*
*
*
*
*
*
8
5
*
12 15 20 23 27  
*
*
*
9
6
13 17 22 26  
11 15 20 25  
*
*
8
14 18 23  
LEGEND  
WB — Wet Bulb  
*Do not attempt to charge system under these conditions or refrigerant slug-  
ging may occur.  
Table 4B — Superheat Charging Table — SI  
(Superheat Entering Suction Service Valve)  
INDOOR COIL ENTERING AIR (C) WB  
10 11 12 13 14 16 17 18 19 20 21 22 23 24  
OUTDOOR  
TEMP (C)  
13  
16  
18  
21  
24  
27  
29  
32  
35  
38  
41  
43  
46  
5
4
*
*
*
*
*
*
*
*
*
*
*
7
6
3
*
*
*
*
*
*
*
*
*
*
8
7
6
4
*
*
*
*
*
*
*
*
*
9
8
7
6
3
*
*
*
*
*
11 13 14 16 18 19 21 22 23 25  
10 12 13 15 17 18 19 21 22 24  
9
7
5
3
11 12 13 15 17 18 20 21 23  
9
7
4
11 12 13 15 17 18 20 22  
8
7
4
3
10 12 13 16 17 19 21  
8
6
5
3
10 12 14 16 17 19  
*
*
8
7
6
4
3
11 12 14 17 18  
*
*
*
*
*
*
*
*
*
*
*
*
9
8
7
5
3
11 13 15 17  
10 12 14 16  
*
*
*
*
*
*
8
7
6
4
11 13 15  
*
*
*
*
*
*
9
8
8
12 14  
11 14  
10 13  
*
*
*
LEGEND  
WB — Wet Bulb  
*Do not attempt to charge system under these conditions or refrigerant slug-  
ging may occur.  
9—  
MAINTENANCE  
Clean coil annually or as required by location and outdoor  
air conditions. Inspect coil monthly and clean as required.  
Fins are NOT continuous through coil sections. Dirt and  
debris may pass through the first section, become trapped  
between the rows of fins, and restrict condenser airflow. Use  
a flashlight to determine if dirt or debris has collected  
between coil sections. Clean coil as follows:  
WARNING: Before performing recommended main-  
tenance, be sure unit main power is off. Failure to do so  
may result in electrical shock or injury from rotating fan  
blades.  
1. Turn off unit power.  
I. LUBRICATION  
2. Use a garden hose or other suitable equipment to  
flush coil from the outside to remove dirt. Be sure to  
flush all dirt and debris from drain holes in the base  
of unit. Fan motors are waterproof.  
The outdoor fan motor is factory lubricated and requires no  
oil.  
II. COMPRESSOR  
The compressor contains factory oil charges; replace oil when  
lost. See Tables 1A and 1B for oil recharge. Recommended oil  
is Sontex 200LT for all units.  
III. CLEANING COILS  
Coil should be washed out with water or blown out with com-  
pressed air. Note that the blow-thru design causes dirt and  
debris to build up on the inside of the coils.  
Table 6A — Required Liquid Line Temperature (F) — English (At Service Valve)  
REQUIRED  
SUBCOOLING  
(F)  
LIQUID PRESSURE AT SERVICE VALVE (PSIG)  
134 141 148 156 163 171 179 187 196 205 214 223 233 243 253 264 274 285 297 309 321 331 346 359  
0
5
76  
71  
66  
61  
56  
51  
79  
74  
69  
64  
59  
54  
82  
77  
72  
67  
62  
57  
85  
80  
75  
70  
65  
60  
88  
83  
78  
73  
68  
63  
91  
86  
81  
76  
71  
66  
94  
89  
84  
79  
74  
69  
97 100 103 106 109 112 115 118 121 124 127 130 133 136 139 142 145  
92  
87  
82  
77  
72  
95  
90  
85  
80  
75  
98 101 104 107 110 113 116 119 122 125 128 131 134 137 140  
10  
15  
20  
25  
93  
88  
83  
78  
96  
91  
86  
81  
99 102 105 108 111 117 120 123 126 129 129 132 135  
94  
89  
84  
97 100 103 106 109 112 115 118 121 124 127 130  
92  
87  
95  
90  
98 101 104 107 110 113 116 119 122 125  
93 96 99 102 105 108 111 114 117 120  
Table 6B — Required Liquid Line Temperature (C) — SI (At Service Valve)  
REQUIRED  
SUBCOOLING  
(C)  
LIQUID PRESSURE AT SERVICE VALVE (PSIG)  
911 969 1030 1061 1121 1186 1219 1286 1360 1397 1471 1547 1588 1671 1755 1800 1885 1976 2026 2125 2222 2264 2379 2475  
0
2
4
24  
22  
20  
18  
16  
14  
12  
10  
26  
24  
22  
20  
18  
16  
14  
12  
28  
26  
24  
22  
20  
18  
16  
14  
29  
27  
25  
23  
21  
19  
17  
15  
31  
29  
27  
25  
23  
21  
19  
17  
33  
31  
29  
27  
25  
23  
21  
19  
34  
32  
30  
28  
26  
24  
22  
20  
36  
34  
32  
30  
28  
26  
24  
22  
38  
36  
34  
32  
30  
28  
26  
24  
39  
37  
35  
33  
31  
29  
27  
25  
41  
39  
37  
35  
33  
31  
29  
27  
43  
41  
39  
37  
35  
33  
31  
29  
44  
42  
40  
38  
36  
34  
32  
30  
46  
44  
42  
40  
38  
36  
34  
32  
48  
46  
44  
42  
40  
38  
36  
34  
49  
47  
45  
43  
41  
39  
37  
35  
51  
49  
47  
45  
43  
41  
39  
37  
53  
51  
49  
47  
45  
43  
41  
39  
54  
52  
50  
48  
46  
44  
42  
40  
56  
54  
52  
50  
48  
46  
44  
42  
58  
56  
54  
52  
50  
48  
46  
44  
59  
57  
55  
53  
51  
49  
47  
45  
61  
59  
57  
55  
53  
51  
49  
47  
63  
61  
59  
57  
55  
53  
51  
49  
6
8
10  
12  
14  
10—  
TROUBLESHOOTING  
11—  
Copyright 2002 Bryant Heating & Cooling Systems  
Printed in Mexico  
CATALOG NO. 5353-802  

Brother MFC4450 User Manual
Brother MFC 8840D User Manual
Chromalox UB 2502A User Manual
Continental Electric CE11185 User Manual
Dakota Digital LED Tail Lights for 1956 Chevy Car LAT NR200 User Manual
Dakota Digital LED Tail Lights for 1973 74 Nova LAT NR380 User Manual
Friedrich MR18DC3E User Manual
Friedrich YS12M33 User Manual
Fujitsu Air Conditioner Heat Cool Model Reverse Cycle Room Air Conditioner Multi Split Type 2 Rooms User Manual
Haier Commercial Cool CPN10XCJ User Manual