®
Merchandisers
Service Merchandisers
Fresh Meat, Delicatessen, and Seafood Merchandisers
(Includes Wedge Installation)
NSF® Certified
Installation &
Operation Manual
Shipped with Technical Data Sheets
P/N 0420057_B
Impact Series
July 2008
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
iii
CONTENTS
INSTALLATION
Merchandiser Electrical Data . . . . . . . . . . . 2-4
Electrical Connections . . . . . . . . . . . . . . . . . 2-4
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Identification of Wiring . . . . . . . . . . . . . . . . 2-4
Wiring Color Code . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
NSF Certification . . . . . . . . . . . . . . . . . . . . . 1-1
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Front Glass Caution . . . . . . . . . . . . . . . . 1-1
Shipping Damage . . . . . . . . . . . . . . . . . . . . 1-2
Apparent Loss or Damage . . . . . . . . . . . . . . . . . . . . 1-2
Concealed Loss or Damage . . . . . . . . . . . . . . . . . . . 1-2
Exterior Loading . . . . . . . . . . . . . . . . . . . . . 1-2
Merchandisers Shipped with End Installed . 1-2
Shipping Braces . . . . . . . . . . . . . . . . . . . . . . 1-2
Shipping Rider . . . . . . . . . . . . . . . . . . . . . . . 1-2
Case Leveling . . . . . . . . . . . . . . . . . . . . . . . 1-3
Preparation . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Leveler Adjustment . . . . . . . . . . . . . . . . . 1-4
Glass Positioning . . . . . . . . . . . . . . . . . . . . . 1-5
Adjustment Bolt . . . . . . . . . . . . . . . . . . . . . 1-6
Joining Instructions . . . . . . . . . . . . . . . . . . . 1-8
Installing Coil Cover and Drip Tray . . . . . . 1-8
Removing Protective Film from Bumper . . 1-9
Installing Optional Wrap Board . . . . . . . . . 1-9
Installing Optional Scale Stand . . . . . . . . . 1-11
DRIP PIPING AND SPLASHGUARDS
Waste Outlet and Water Seal . . . . . . . . . . . . 3-1
Installing Drip Piping . . . . . . . . . . . . . . . . . 3-1
Installing Splashguards and
Lower Front Panels . . . . . . . . . . . . . . . . . 3-2
Assembly Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Installing Bottom Rear Panel . . . . . . . . . . . 3-4
START UP / OPERATION
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Stocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Load Limits . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Load Limit Profiles . . . . . . . . . . . . . . . . . . . 4-2
Installing
FDA / NSF Required Thermometer . . . . . 4-2
REFRIGERATION / ELECTRICAL
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . 2-1
Connection Location . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Multiplexing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Line Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Line Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Oil Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Suction Line . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Liquid Line . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Control Settings . . . . . . . . . . . . . . . . . . . . . . 2-2
Refrigeration Thermostat . . . . . . . . . . . . . . 2-3
Defrost Termination Thermostat . . . . . . . . . 2-3
MAINTENANCE
Care and Cleaning . . . . . . . . . . . . . . . . . . . . 5-1
Exterior Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Interior Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Do NOT USE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
DO Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Interior Cleaning Steps . . . . . . . . . . . . . . . . 5-2
Removable Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Fan Plenum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Drip Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Removing Scratches from Bumper . . . . . . . 5-6
CONTINUED ON PAGE IV.
IMPORTANT
KEEP IN STORE FOR FUTURE REFERENCE
Quality that sets industry standards.
®
This merchandiser is NSF certified.
®
12999 St. Charles Rock Road • Bridgeton, MO 63044 U.S.A. • (314) 291-2000 • FAX (314) 298-4767
Download from Www.Somanuals.com. All Manuals Search And Download.
iv
CONTENTS
CONTENTS (CONTINUED)
SERVICE
Replacing Fan Motors and Blades . . . . . . . 6-1
Removing Polycarbonate Lamp Covers . . . 6-2
Electrical Service Receptacles . . . . . . . . . . 6-3
Replacing Fluorescent Lamps . . . . . . . . . . . 6-3
Replacing Lamp Holders and End Caps . . . 6-3
Replacing Electronic Ballast . . . . . . . . . . . . 6-4
Replacing Cylinders —Single Pane Glass . 6-5
Replacing Single Pane Front Glass . . . . . . . 6-6
Replacing Glass Hand Grip . . . . . . . . . . . . . 6-7
Hinge Hardware . . . . . . . . . . . . . . . . . . . . . 6-7
Repairing Aluminum Coils . . . . . . . . . . . . . 6-8
Refrigerant Warning . . . . . . . . . . . . . . . . . . . . . . . . 6-8
WARRANTY
REVISION HISTORY
Revision B
1. Updated image, pages 1-1, 2-1, 2-3, 3-4, and 4-2.
2. Updated flexible wiper gasket information, page 1-6.
3. Added section for removing protective film from
bumper, page 1-10.
* * * * * * * * * * * * * * * * * * * * * * * * * *
ANSI Z535.5 DEFINITIONS
4. Added NSF Thermometer, pages 4-4 and 4-5.
5. Updated acceptable water temperature, pages 5-1 and
5-5.
• DANGER – Indicate[s] a hazardous
situation which, if not avoided, will
result in death or serious injury.
!
6. Added information on cleaning anti-reflective glass,
page 5-6.
• WARNING – Indicate[s] a hazardous
7. Updated WARNING, CAUTION, and NOTICE boxes through-
out.
situation which, if not avoided, could
result in death or serious injury.
!
8. Added Optional Wrapping Board, page 1-9.
9. Added Optional Scale Stand, page 1-11.
10. Added Call Center telephone numbers to bottom of
each page.
• CAUTION – Indicate[s] a hazardous
situation which, if not avoided, could
result in minor or moderate injury.
!
• NOTICE – Not related to personal injury –
Indicates[s] situations, which if not avoided,
could result in damage to equipment.
Revision A
1. Added leveling detail beginning on page 1-3.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
v
SAFETY
There are two main hazard areas that service
technicians may encounter on a day-to-day
basis. They are: working within close proximi-
ty to the public, and personal safety. Before
starting work, review these hazards by com-
pleting the following checklist:
ELECTRICAL HAZARDS
Are all live electrical hazards protected
from public access; i.e., de-energized/locked
out or cordoned off? Is proper signage in
place?
Do light bulbs need to be replaced: If yes,
will high work be conducted from a ladder or
a scissor lift? Make sure the work area is cor-
doned off as shown below.
WORKING NEAR THE PUBLIC
KEEPING THE PUBLIC OUT:
The following techniques reduce the risk of
injury to third parties (shoppers, store
employees, etc.):
Cordon off all work areas with cones, cau-
tion tape, warning signs and/or barricades.
Maintain a work area of at least five feet
from the public.
Is a second person required to prevent the
public from entering the work area when the
work area cannot be adequately cordoned
off?
HAZARDOUS MATERIALS
Can the public be exposed to any chemi-
cals, refrigerants or fumes? If yes, can steps be
taken to eliminate or reduce the risk of expo-
sure? to guard against accidental release of
refrigerants, make sure the work area is ade-
quately cordoned off (instead of posting a
WET FLOOR sign, use CAUTION tape to prevent
the public from entering the area).
Are wet floors going to create a slip haz-
ard for pedestrians? If yes, be sure to post
WET FLOOR signs and establish a schedule for
clean up as soon as the work is complete.
CAUTION
!
Fluorescent lamps contain mercury vapor.
Mercury exposure at high levels can harm
the brain, heart, kidneys, lungs, and immune
system of people of all ages. Do not break or
puncture fluorescent lamps. Dispose of, or
store, all fluorescent lamps in accordance
with Federal (40 CFR 273), State, and local
hazardous waste requirements. Refer to
©2008 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-522-1900 • WWW.HUSSMANN.COM
Service Merchandisers
Download from Www.Somanuals.com. All Manuals Search And Download.
vi
CONTENTS
PERSONAL SAFETY
ELECTRICAL / LOTO
Over 90% of accidents are due to human
error or from complacency about the job. This
checklist is provided to remind you of the
potentially hazardous conditions at the job-
site.
Does the project require you to work with
live electricity? If yes, have you received
appropriate training?
Do you have appropriate locks and tags to
de-energize or isolate the electrical supply?
WORKING AT HEIGHT
REMOTE AND LIMITED USE LOCATIONS
Is there the potential to contact poisonous
plants (ivy, oak or sumac)? If yes, make sure
you wear proper PPE (gloves, long pants and
long sleeves).
Check for snakes, vermin and bees / wasps.
If stung or bitten, do you have reactions
that require medical treatment, such as
Epinephrine EpiPen? If yes, inform the client
prior to starting work.
Will you be working more than six feet off
the ground? If yes, have you received appro-
priate training (i.e., ladder, scissor lifts and
personal fall-arrest systems)?
Do you have the appropriate personal
protective equipment (PPE) for working at
height (safety harness/lanyard)?
Will you be working on roofs with unpro-
tected edges? If yes, make sure actions are
taken to prevent a fall (i.e., identification of
adequate anchor points for safety harnesses).
* * * * * * * * * * * * * * * * * * * * * * * * * *
ANSI Z535.5 DEFINITIONS
CONFINED SPACE WORK
Will you be working in any confined
spaces? If yes, have you received appropriate
training? A confined space has limited means
of entry/egress, is not designed for human
occupancy, and is large enough for bodily
entry.
• DANGER – Indicate[s] a hazardous
situation which, if not avoided, will
result in death or serious injury.
!
• WARNING – Indicate[s] a haz-
ardous situation which, if not avoided,
could result in death or serious injury.
Is permit-required confined space entry
required? If yes, have appropriate steps been
taken for safe entry, such as permit issuance.
If in doubt, DO NOT ENTER and inform the
client.
!
• CAUTION – Indicate[s] a hazardous
situation which, if not avoided, could
result in minor or moderate injury.
!
• NOTICE – Not related to personal injury –
Indicates[s] situations, which if not avoided,
could result in damage to equipment.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-1
INSTALLATION
NSF CERTIFICATION
CAUTION
Read before raising front glass to prevent
injury from broken or falling glass.
!
These merchandisers are manufactured to meet
ANSI / National Sanitation Foundation (NSF®)
Standard #7 requirements. Proper installation is
required to maintain certification. Near the serial
plate, each case carries a label identifying the
type of application for which the case was certi-
fied.
The top cylinders, which allow the raising and
lowering of this glass, have been carefully
installed and tested for the proper tension before
shipment. However, during shipment and stor-
age, the lubricant inside the cylinders may have
settled. This settling can cause excessive or
uneven tension on the glass to the point of
breakage.
ANSI/NSF-7 Type I – Display Refrigerator / Freezer
Intended for 75°F / 55%RH Ambient Application
ANSI/NSF-7 Type II – Display Refrigerator / Freezer
Intended for 80°F / 55%RH Ambient Application
To avoid any damage, please do the follow-
ing before completely raising the front
glass.
ANSI/NSF-7 – Display Refrigerator
Intended for Bulk Produce
1. Slowly raise and lower each glass section
6 times to a height of 6 in. (152 mm).
LOCATION
These merchandisers are designed for displaying
products in air conditioned stores where tempera-
ture is maintained at or below the ANSI/NSF-7
specified level and relative humidity is main-
tained at or below 55%.
2. Increase the height to about 12 in. (305
mm) and raise and lower the glass 6 times.
3. Then raise the glass to the full extension
and lower.
Placing refrigerated merchandisers in direct sun-
light, near hot tables or near other heat sources
could impair their efficiency.
This should release any settled lubricant in the
cylinders and prevent any stress on the front
glass.
Like other merchandisers, these are sensitive to
air disturbances. Air currents passing around
merchandisers will seriously impair their opera-
tion. Do NOT allow air conditioning, electric
fans, open doors or windows, etc. to create air
currents around the merchandisers.
Leveling and adjustment
procedures begin on
Page 1-3.
6 in.
6 in.
Product should always be maintained at proper
temperature. This means that from the time the
product is received, through storage, preparation
and display, the temperature of the product
must be controlled to maximize the life of the
product.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-2
INSTALLATION
MERCHANDISERS SHIPPED
WITH END INSTALLED
NOTICE
If the case was shipped with the end installed,
two long bolts were used to hold the shipping
brace to the end. If the shipping bolts are re-
inserted after removing the brace, they will
extend into the product area. Therefore, be sure
to replace these bolts with the shorter bolts
provided. Refer to the detailed information
provided in the separate End Kit Instruction
shipped with each end.
Do NOT remove shipping braces until
the merchandisers are positioned for
installation. Frames may be damaged.
SHIPPING DAMAGE
All equipment should be thoroughly examined
for shipping damage before and during unload-
ing. This equipment has been carefully inspected
at our factory. Any claim for loss or damage
must be made to the carrier. The carrier will
provide any necessary inspection reports and/or
claim forms.
Note: Be careful not to damage the factory
installed end while moving the case. Make sure
that tools are positioned past the end and beneath
the merchandiser’s support bar.
Apparent Loss or Damage
If there is an obvious loss or damage, it must be
noted on the freight bill or express receipt and
signed by the carrier’s agent; otherwise, carrier
may refuse claim.
SHIPPING BRACES
Move the fixture as close as possible to its per-
manent location and then remove all packaging
and shipping braces. Check for damage before
discarding packaging. Remove all separately
packed accessories such as kits, and shelves.
Concealed Loss or Damage
When loss or damage is not apparent until after
equipment is uncrated, retain all packing materi-
als and submit a written request to the carrier for
inspection, within 15 days.
Remove all nut retainers used with shipping
braces. NSF certification requires the use of
ANSI Standard nuts and bolts with not more than
two (2) threads showing after installation.
WARNING
Do not stand or walk on top of case
because falling off could
!
SHIPPING RIDER
cause serious personal injury.
Each case is shipped on a rider to protect
factory-installed legs, and to make positioning
the case easier. Remove the rider after the case
has been positioned.
EXTERIOR LOADING
Do NOT walk on top of merchandisers or
damage to the merchandisers and serious person-
al injury could occur. Merchandisers ARE NOT
STRUCTURALLY DESIGNED TO SUPPORT EXCESSIVE
EXTERNAL LOADING such as the weight of a
person. Do not place heavy objects on the case.
Note: Once the rider is removed, the case must
be lifted –NOT PUSHED– to reposition.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-3
Cross-Members
Sides
Screws
(each leg)
Screws
(two each end
of each
Shipping Rider
for 8 ft Case
cross-member)
Leg
To remove the rider, remove screws attaching
each leg to rider. Remove screws holding rider
cross-members, then slide cross-members out
from between sides. Once cross-members are
out, slide the sides out.
2. Snap a chalk line for the front and rear
positions of the base legs.
3. Mark the location of each joint from front
to back lines.
4. FLOORS ARE NOT LEVEL!!! When
working with two or more cases to be joined,
the whole lineup must be leveled on the
same plane, left to right and front to back.
This means that the entire lineup must be
brought up to the level of the highest case in
the lineup.
CASE LEVELING
Merchandisers must be installed level to ensure
proper operation of the refrigeration system and
to ensure proper drainage of defrost water.
During all steps of setting, joining and leveling
cases, close attention to glass position and
operation must be maintained. Please review
all steps and photos before making any adjust-
ments. DO NOT make any glass adjustments
until individual case is set and level.
Along the lines previously marked, find the
highest point of the floor by:
• Walking the floor and noticing any dips
or mounds;
• Using a string level; and
• Using a transit.
Preparation
1. Using store blueprints, measure off and mark
on floor the exact dimensions/locations of
the case footprint.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-4
INSTALLATION
U
Leveler Adjustment
Position the first case at the highest point.
Set a long level (4 ft [1220 mm] or more)
on the upper front panel of the case. Use an
open-end wrench to turn leg levelers until
the case is level from end to end and from
front to back. Check all 6 legs on 8 ft (2438
mm) cases, or 8 legs on 12 ft (3658 mm)
cases.
Level on
Upper Front
Panel
Note: To avoid removing concrete flooring,
begin lineup leveling from the highest point
of the store floor.
MINIMUM
HEIGHT
MAXIMUM
HEIGHT
Adjustable
Leg Leveler
Attention to glass position is critical
during the leveling process.
Lower
Raise
Adjusting leg levelers will affect the
position of the glass. Make certain that the
glass is square with the case, avoiding
interference with other glass and case ends.
NOTICE
Do not adjust glass until case is level.
In many instances, proper leveling will align
glass without further adjustment.
If the glass is still out of alignment, refer to
the following Glass Positioning instructions.
Glass
Glass
Movement
CAUTION
!
To prevent injury from falling
glass during adjustment, one
person must support glass
while a second person makes
adjustments.
Leg
Leveler
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-5
GLASS POSITIONING
Check the following to improve opening or clos-
ing of the case front glass.
1. Has the case been leveled according to
preceding paragraphs?
2. Is the glass handle installed correctly?
Verify the glass is bottomed out the length of the
handle. A bowed handle indicates the glass may
not be bottomed out at the center of the handle.
The handle must be removed before it can be
repositioned. The handle is held in place with
silicone which must be completely removed
from the handle and the glass. Remove the
handle by pulling it away from the glass (do not
use tools to pry this loose). A damaged or bent
handle must be replaced. Apply new silicone
into the handle and firmly press onto the glass.
A. Remove the glass and clamp hardware from
the case by opening the glass and loosening
set screws in hinge, (Metric 3 millimeter set
screws).
B. Slide the glass and clamp hardware to the
side out of the hinges and lay them on an
appropriate work surface.
3. Is the glass seated in the clamp hardware
correctly?
Note: adjacent glass must be closed.
C. Loosen the 8 set screws on the underside of
the clamp hardware.
Verify glass is bottomed out in clamp hardware.
D. Push the clamp hardware onto the glass until
bottomed out.
E. The clamp hardware must overhang the glass
by an equal amount on each side.
F. Tighten set-screws and re-install on case.
If the glass is not bottomed out in the clamp
hardware it can be re-positioned as follows:
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-6
INSTALLATION
4. Is the glass hitting the end or adjacent glass?
Slowly open and close the glass to inspect.
ADJUSTMENT BOLT
If the glass still does not open or close correctly,
adjustment of the top frame may be necessary.
If the glass is hitting the end or adjacent glass it
may not be positioned correctly from left to
right. This can be adjusted as follows:
This case is equipped with an adjustment bolt at
the top rear of the case to raise or lower the
glass. This allows for improvements in the glass
operation and sealing. The following outlines
how to access the adjustment bolt. The top must
be free to move as the adjustment bolt is turned.
1. Loosen joining or end bolts at top of case,
(2 at each end of case).
• Loosen the 2 screws holding the hinge to the
clamp hardware (Metric 3 millimeter screws).
• Slide the clamp hardware to either side as
needed.
• Tighten the screws and check glass for proper
operation.
5. Is the glass still hitting adjacent glass?
Slowly open and close the glass to inspect.
Optional Flexible Wiper Gasket
There may be an optional flexible wiper gasket
that is attached to each side. These are designed
to overlap each other, sealing the gap between
the glass and allowing side-to-side glass adjust-
ment. After all glass has been adjusted as
defined in Step 4, the flexible portion of one
gasket at a joint may be trimmed with a razor
knife. Be sure that the remaining wiper gasket
seals the gap. Verify proper operation.
2. If caulk or silicone has been applied between
case joints or ends in the top area it must be
removed.
3. Remove rear doors.
Optional Flexible Wiper Gasket
Glass
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-7
4. Remove screws at top of rear door frame.
The bottom screws do not need to be
removed.
9. The set screw and adjusting bolt are now
accessible.
5. Pull back the top of the door frame approxi-
mately 2 inches. This will allow clearance
for removal of the stainless steel top liner
and trim pieces.
• The set screw must be backed out before turn-
ing the adjusting bolt, (1/8 inch set screw). The
set screw serves as a positive stop.
• The adjusting bolt should be turned no more
than a half-turn before inspecting glass posi-
tion and operation.
• Turning the adjusting bolt clockwise will raise
the front glass.
• Turning the adjusting bolt counter-clockwise
will lower the front glass.
• Once the glass position is set, tighten the set
screw (positive stop).
6. Some models have a Phillips truss head
screw holding the stainless steel liner to the
trim. These screws are visible from the rear
of the case to the side of the door frame.
These must be removed.
7. Remove stainless steel top liner by grabbing
the rear flange and pulling back. Note: It is
possible to access the adjusting bolt by using
a small swivel socket without removing the
stainless top liner. To do this, the stainless
steel trim and foam noted in Step 8 must be
removed.
10. Once glass is positioned and operating
correctly, re-install components and hard-
ware removed.
Note: the door frame is designed to have a tight
fit. A putty knife between the top of the frame
and the insulated panel will help guide it into
position.
8. Remove stainless steel trim pieces and foam
insulation on each side of the door frame.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-8
INSTALLATION
11. Re-apply caulk or silicone as required.
12. Verify glass is positioned and operating cor-
rectly.
Pivot Support
Adjusting Bolt
Set Screw
Positive Stop
JOINING INSTRUCTIONS
Sectional construction means that two or more
merchandisers may be joined in line yielding
one long continuous display requiring only one
pair of ends.
Check the drip tray for obvious damage before
installation. Damaged or leaking drip trays must
be replaced. Remove any loose debris and clean
the drip tray before installing.
All joints must be air-tight to prevent formation
of ice or condensation.
Coil cover hooks and drip tray hooks are factory
installed at the front and back in each gravity
coil. Hanging holes are formed in the cover and
drip tray.
Refer to the detailed information provided in the
separate Joining Instruction shipped with each
case.
Coil Cover
INSTALLING COIL COVER AND
DRIP TRAY
Each gravity coil in these service merchandisers
has a 4 ft (1219 mm) stainless steel coil cover
and molded plastic drip tray. A condensate drip
tube is factory installed.
Drip Tube
Connection
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-9
From the back of the case, hang the coil cover
from the top hooks, then position the drip tray in
the case with the drip tube connection to your
right. Hang drip tray on two back hooks and two
front hooks.
REMOVING PROTECTIVE FILM FROM BUMPER
Remove protective film from bumper once
installation is complete.
Front
Back
Coil
Cover
Hooks
Coil
Cover
Coil
Drip Tray Hooks
Drip Tray Hooks
Drip Tray
Installing Optional Wrap Board
MOA 0470438
1. Turn off power to case.
Connect installed copper drip tube to drip tray
using flexible connector supplied.
2. Determine location by positioning the wrap
board on the rear of the case between door
frames.
Ensure condensate flows freely from drip tray
through drip tube. Check the drip tube connec-
tion for leaks before stocking.
Rear View of Case - Location of Backups
Backup
2.668
TYP
Drip Tray
19.327
TYP
Connector
7.562
7.874
7.874
7.562
12-Ft
8-Ft
6-Ft
4-Ft
36.717
36.668
40.193
36.717
36.668
24.656
33.125
24.656
Notes:
1. All dimensions given in inches.
2. For location of Backups on cases with add-on wedge, start measuring from
the square end of the case opposite the wedge end. Use corresponding case
size dimensions.
3. For location of Backups on 7-Ft cases (facing rear of case)
use 6-Ft case dimensions on the left and 8-Ft case dimensions on the right.
Drip Tube
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-10
INSTALLATION
8.969 for 36-in. Board
8.656 for 48-in. Board
REF
3. Align the assembly on the back of the case
as shown below.
8.969 for 36-in. Board
8.656 for 48-in. Board
REF
0.812
0.812
3.25
REF
0.125-in.
Diameter
Drill 6 additional holes 0.5-in. deep
if not already existing in wrapping board.
Bottom View of Wrap Board Panel
Wrap Board Panel
Screw - #8 x1/2
PHIL AB SMS
(3 required for
each bracket)
Screw - 1/4-20 x 0.75-in.
Flange Thread Cutting
(3 required for each bracket)
Bracket - Adj
(2 required)
Bracket Spacer
(2 required)
Screw - 1/4-20 x 0.5-in.
Hex Head Zinc Plate
(2 required for each bracket)
Mounting Holes
Wrapping Board Assembly for Mounting to Left Hand Side of Case
(Facing Front of Case)
Wrap Board Panel
Screw - #8 x1/2
PHIL AB SMS
(3 required for
each bracket)
Screw - 1/4-20 x 0.75-in.
Flange Thread Cutting
(3 required for each bracket)
Bracket - Adj
(2 required)
Bracket Spacer
(2 required)
Screw - 1/4-20 x 0.5-in.
Hex Head Zinc Plate
(2 required for each bracket)
Mounting Holes
Wrapping Board Assembly for Mounting to Right Hand Side of Case
(Facing Front of Case)
4. Using holes in wrapping board bracket as a
template, mark hole locations on rear of case.
Wrap Board Panel
Screw - #8 x1/2
PHIL AB SMS
(3 required for
each bracket)
5. Remove wireway cover; make sure there
are no wires behind hole locations.
Screw - 1/4-20 x 0.75-in.
Flange Thread Cutting
(3 required for each bracket)
6. Drill 3/8-inch (0.1875) diameter holes for
three 1/4-20 thread cutting screws through stain-
less steel and structural members.
Bracket - Adj
(2 required)
Bracket Spacer
(2 required)
Screw - 1/4-20 x 0.5-in.
Hex Head Zinc Plate
(2 required for each bracket)
Mounting Holes
Wrapping Board Assembly for Mounting to Center of 12-Ft Case
or Mounting in Positions Other Than Left, Right or Center of Case
(Facing Front of Case)
7. Securely fasten brackets to case.
8. Adjust wrapping board as needed. The attach
points for hinging brackets on wrapping board is
determined by which position the assembly is to
be mounted. Refer to figures for LH, RH or
Center mounting positions.
9. Replace wireway cover.
10. Restore power.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
1-11
Installing Optional Scale Stand
MOA 0458960
1. Turn off power to case.
2. Determine location by positioning the scale
stand on the rear of the case between door
frames.
Screw - SM #8-18 x 3/8
Truss Head
3. Using holes in scale stand bracket as a
template, mark hole locations on rear and top of
case.
Case Wireway
4. Remove scale stand. Drill 1/8-inch diameter
pilot holes through metal liners at the marked
locations.
1
NOTE: METAL LINERS ARE LESS THAN /8-INCH
THICK-- DO NOT DRILL BEYOND METAL LINERS.
5. Move top panel away from back of case.
Remove center rear door trim and remove LH
Upright wireway cover to allow routing of
receptacle harness.
Insulation in this area to be notched
as needed for wire harness routing.
Screw - SM #8-18 x 3/8
Truss Head
(3 required)
Connect after routing wiring through case.
Install strain relief connector where
Communication Cable exits scale
stand assembly. Use plug button if
Communication Cable i not required.
Isolated Ground Sticker
(If required)
3/4 Bushing
Convenience Outlet
LH Upright
Wireway
Harness -
Receptacle
Communication Cable
Route cable with 12-in.
outside the strain relief
connector in the scale stand
Scale Stand Upright Cover
Screw - SM #8-18 x 3/8 Hex Head
(2 required)
Rear Door Center Trim
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
1-12
INSTALLATION
Case
Wireway
Receptacle
Harness
Mount Junction Box at this
location when scale stand
is mounted at Center Mullion.
Route Communication
Cable to Junction Box
as shown. Coil excess
cable in Junction Box.
Communication Cable
6. NOTE: RECEPTACLE HARNESS WIRING MUST HAVE
INSULATION SLEEVE INSTALLED PRIOR TO ROUTING.
Leaving about 12 inches of harness hang out of
case, route receptacle harness wiring from the
3/4-in. bushing, down the LH upright wireway
through hole and into case wireway.
Some stores specify an isolated ground for scale
stand convenience outlets. If required, apply the
following:
• Isolated ground sticker to scale stand.
• Isolated ground tag to ground wire in case
wireway.
NOTE: COMMUNICATION CABLE WIRING CAN BE
ROUTED SIMILARLY.
7. Install the rear door center trim with 3/4-in.
bushing by routing wire harness through 3/4-in.
bushing and attach with #8 truss head screws.
8. Reposition top over rear door center trim and
attach using #8 truss head screws.
9. Reposition scale stand and attach using #8
truss head screws.
10. Install scale stand upright cover with #8
blunt tip sheet metal screws.
11. Connect wiring to power in wireway.
12. Restore power. Check for proper operation.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
2-1
REFRIGERATION / ELECTRICAL
REFRIGERANT
REFRIGERANT PIPING
The correct type of refrigerant will be stamped
on each serial plate. The case refrigeration
piping is factory sealed, pressurized and leak
tested. Before making refrigeration hookups,
depress universal line valve to ensure that coils
have maintained pressure during shipment.
Connection Location
The refrigerant line connections are at the right-
hand end of the merchandiser (as viewed from
the front) beneath the display pans. A sticker
marks the location of the connection “pod.”
The installer must saw a hole through the pod
to exit the case.
After connections have been made, seal this
outlet thoroughly. Seal both the inside and the
outside. We recommend using an expanding
polyurethane foam insulation.
WARNING
!
Refrigerant vapor is hazardous to your health
and can cause death.
Multiplexing
Avoid breathing refrigerant and lubrication
vapor or mist. Exposure may irritate eyes,
nose and throat. If accidental system dis-
charge occurs,ventilate work area before
resuming service.
Piping of cases operating on the same refrigera-
tion system may be run from case to case. DO
NOT RUN REFRIGERANT LINES THROUGH CASES
THAT ARE NOT ON THE SAME REFRIGERATION
SYSTEM BRANCH as this may result in poor
refrigeration control and compressor failure.
Always wear safety goggles and protective
gloves when working with refrigerants.
Contact with refrigerant may cause injury.
Disconnect hoses with extreme caution! All
hoses may contain liquid refrigerant under
pressure.
Interconnecting piping inside the merchandiser
must be located as shown below to allow room
for lifting the hinged fan plenums and for clear-
ance beneath the display pans. The intercon-
necting piping may be run outside the case.
Be sure that any room where you are working
is thoroughly ventilated, especially if a leak
is suspected.
Read all safety information regarding the safe
handling of refrigerant and refrigerant oil,
including the Material Safety Data Sheet.
MSDS sheets can be obtained from your
refrigerant supplier.
Display Pan
Coil
Fan
Refrigeration lines are under pressure
and should be depressurized before
attempting to make any connections.
Piping Location
When brazing pipes, be sure to use the
insulation blanket shipped with the
merchandiser to prevent fire or damage
to the plastic case bottom.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
2-2
REFRIGERATION / ELECTRICAL
Line Sizing
LIQUID LINE
Refrigerant lines should be sized as shown on
the refrigeration legend that is furnished for the
store or according to ASHRAE guidelines.
Refer to the information on the next page for
branch line piping of Hussmann Equipment.
•
May be reduced by one size after one half
the case run load. Do not reduce below the
case liquid line connection size.
•
Take-offs to case liquid lines should exit the
bottom of the branch liquid line. Provide an
expansion loop for each evaporator take-off.
(Minimum 3 in. [76 mm] loop.)
Oil Traps
P-traps (oil traps) must be installed at the base
of all suction line vertical risers.
Pressure Drop
Pressure drop can rob the system of capacity.
To keep the pressure drop to a minimum, keep
the refrigerant line run as short as possible
using a minimum number of elbows. Where
elbows are required, USE LONG RADIUS ELBOWS
ONLY.
Minimum Loop
3-in. (76 mm)
Liquid Line Take Off
INSULATION
CONTROL SETTINGS
The suction and liquid lines should be clamped
or taped together and insulated for a minimum
of 30 ft (9144 mm) from the merchandiser.
Additional insulation for the balance of the
liquid and suction lines is recommended wher-
ever condensation drippage is objectionable or
lines are exposed to ambient conditions.
Merchandiser Technical Data Sheets (TDS) are
shipped with this manual. The TDS provide
case control settings and defrost data.
An evaporator pressure regulator or EPR
(primary control) and a 3 – 5ºF (1.7 – 2.7ºC)
differential thermostat (secondary control) must
control refrigeration temperature. The EPR
must be set to maintain the proper saturated
evaporator temperature as listed in the data
sheets. The thermostat must be set a couple
degrees colder than the discharge air tempera-
ture specified in the data sheets. The thermostat
will prevent product freezing should the EPR
temperature drift downward during reduced
load periods (lights off, lower ambient). The
thermostat will be wired to control the com-
pressor motor contactor (single compressor) or
a liquid line solenoid valve (parallel compressor
systems).
SUCTION LINE
•
•
Pitch in direction of flow.
May be reduced by one size at one third of
case run load and again after the second
third. Do not reduce below the case suction
line size.
•
Case suction lines should enter at the top of
the branch line.
Defrost is Off Time. Defrost control settings are
listed in the data sheets. When these merchan-
disers are connected to parallel compressor
systems, a suction stop valve must be used to
isolate the evaporator during defrost periods.
Suction Line Return
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
2-3
Offtime Defrost
8 Ft Case
(2438 mm)
12 Ft Case
(3658 mm)
8 Ft Case
(2438 mm)
12 Ft Case
(3658 mm)
Liquid Line
Suction Line
REFRIGERATION THERMOSTAT
The optional refrigeration thermostat bulb is
located in the discharge air of the evaporator.
The optional refrigeration thermostat is located
behind the exterior rear panel.
DEFROST TERMINATION
THERMOSTAT
The standard disc type defrost termination
thermostat is not adjustable. This thermostat
is clamped to the inlet of the coil on the
left-hand (facing front) end of the case.
Standard Defrost
Termination
Thermostat
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
2-4
REFRIGERATION / ELECTRICAL
MERCHANDISER ELECTRICAL DATA
FIELD WIRING
Merchandiser data sheets are shipped with this
manual. The data sheets provide case electrical
data, electrical schematics, parts lists and
performance data. Refer to the merchandiser
data sheets and case serial plate for electrical
information.
Field wiring must be sized for component
amperes stamped on the serial plate. Actual
ampere draw may be less than specified. Field
wiring from the refrigeration control panel to
the merchandisers is required for defrost termi-
nation thermostats and for optional refrigeration
thermostats. When multiple merchandisers are
on the same defrost circuit, the defrost termina-
tion
ELECTRICAL CONNECTIONS
thermostats are wired in series. ALWAYS
CHECK THE SERIAL PLATE FOR COMPONENT
AMPERES.
All wiring must be in compliance with NEC
and local codes. All electrical connections are
to be made in the electrical raceway or Handy
Box.
IDENTIFICATION OF WIRING
Leads for all electrical circuits are identified by
colored plastic bands. These bands correspond
to the color code sticker (shown below) located
inside the merchandiser’s raceway.
WIRING COLOR CODE
Leads for all electrical circuits are identified by a colored plastic band: neutral
wire for each circuit has either White insulation or a White plastic sleeve in
addition to the color band.
PINK ............REFRIG. THERMOSTAT LOW TEMP.
LIGHT BLUE..REFRIG. THERMOSTAT NORM TEMP.
DARK BLUE ..DEFROST TERM. THERMOSTAT
PURPLE........CONDENSATE HEATERS
ORANGE OR
TAN ..........LIGHTS
MAROON...RECEPTACLES
YELLOW....DEFROST HEATERS 120V
RED ........DEFROST HEATERS 208V
BROWN ........FAN MOTORS
GREEN* .......GROUND
*EITHER COLORED SLEEVE OR COLORED INSULATION
ELECTRICIAN NOTE: Use copper conductor wire only.
CASE MUST BE GROUNDED
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
3-1
DRIP PIPING AND SPLASHGUARDS
WASTE OUTLET AND WATER SEAL
The waste outlet is located in front of the fan
plenum 6 ft (1829 mm) from the left-hand of the
merchandiser (facing case front) allowing drip
piping to be run under the fixture lengthwise.
A 11/2 in. (38 mm) water seal is supplied with
each fixture. The water seal must be installed to
prevent air leakage and insect entrance into the
fixture. A tee, adapter, ell, and plug have been
shipped to allow field installation to determine
direction of drain.
4. Avoid long runs of drip piping. Long runs
make it impossible to provide the pitch
necessary for good drainage.
5. Provide a suitable air break between
flood rim of the floor drain and outlet
of drip pipe. To meet code on low base
merchandisers, it may be necessary
to install a field-supplied drip pipe
reducer. An alternative is to cut the
last section of drip pipe at an angle.
NOTES:
Water seal outlet must clear front skid rail.
PVC–DWV solvent cement is recommended.
Follow the manufacturer’s instructions.
6. Prevent drip pipes from freezing:
A. Do NOT install drip pipes in contact with
uninsulated suction lines. Suction lines should
be insulated with a non-absorbent insulation
material.
INSTALLING DRIP PIPING
Poorly or improperly installed drip pipes can
seriously interfere with the operation of these
merchandisers, and result in costly maintenance
and product losses. Please follow the recommen-
dations listed below when installing drip pipes to
ensure proper installation.
B. Where drip pipes are located in dead air
spaces, such as between merchandisers or
between a merchandiser and a store wall,
provide means to prevent freezing.
Note: To prevent condensation problems, the
water seal should be insulated.
1. Never use drip piping smaller than the
nominal diameter of the pipe or water seal
supplied with the merchandiser.
2. When connecting drip piping, the water seal
must be used as part of the drip piping to
prevent air leakage or insect entrance. Never
use two water seals in series in any one drip
pipe. Double water seals in series will cause
an air lock and prevent draining.
3. Pitch the drip piping in the direction of flow.
There should be a minimum pitch of 1/8 in.
per foot (3 mm per 300 mm).
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
3-2
DRIP PIPING AND SPLASHGUARDS
INSTALLING SPLASHGUARD AND
LOWER FRONT PANEL
Make certain that the end assemblies, end
splashguards and end panels have been
installed according to the End Kit instruction.
3. Push the lower edge of the splashguard toward
the bottom of the bracket until it snaps into
place.
The splashguard and lower front panel are
shipped inside each case. After merchandisers
have been leveled and joined, and all drip
piping, electrical and refrigeration work has
been completed, install the splashguard and
lower front panel.
To Install Lower Front Panel
1. Position the lower front panel with the top
angled as shown in the illustration. Tabs
extending from the upper front assembly are
designed to fit into the slots on the top of the
lower front panel.
1. At front of merchandiser, attach a splashguard
retainer/bracket to each leg with sheet metal
screws.
2. Once the top is positioned, lift the panel up
and drop it into the groove at the top of the
splashguard.
2. Position top of splashguard over the top edge
of the retainer/bracket as shown below.
Do not use additional fasteners or sealant to hold
splashguards or panels in place. To meet NSF
cleanability requirements, splashguards and
panels must be removable without tools.
Leg of
Case
1
1
Tab
Retainer/
Bracket
Lower
Leg of
Front
Case
Panel
2
Leg of
Case
Splashguard
Lower Front Panel
2
Leg of
Case
Leg of
Case
3
Splashguard
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
3-3
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
3-4
DRIP PIPING AND SPLASHGUARDS
INSTALLING BOTTOM REAR PANEL
For fixed installation:
1. Align slots in bottom rear panel with center
of legs.
2. Drive a hex head sheetmetal screw through
each slot into each leg.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
4-1
START UP / OPERATION
START UP
STOCKING
See the specific merchandiser's Data Sheet Set
for refrigerant settings and defrost requirements.
Bring merchandisers down to the operating
temperatures listed on the data sheet.
Product should NOT be placed in merchandisers
until case is at proper operating temperature.
Proper rotation of product during stocking is
necessary to prevent product loss.
Each 4 ft (1219 mm) section has its own evapo-
rator coil and pre-set non-adjustable thermostatic
expansion valve (TEV). No adjustment is
required. DO NOT REMOVE THE CAP ON THE
TEVS. This cap is to be removed only for valve
disassembly.
AIR DISCHARGE AND RETURN FLUES MUST REMAIN
OPEN AND FREE OF OBSTRUCTION AT ALL TIMES to
provide proper refrigeration and air curtain
performance. Do not allow product, packages,
signs, etc. to block these grilles. Do not use
non-approved shelving, baskets, display racks,
or any accessory that could hamper air curtain
performance.
CAUTION
!
Removal of the TEV cap will result in
refrigerant loss unless the system is first
isolated and the refrigerant recovered.
LOAD LIMITS
Each merchandiser has a load limit decal.
The TEV has been factory set to provide the
recommended performance settings as specified
on the merchandiser data sheets.
LOAD LIMIT
Recommended load limit profiles are shown on
the next page.
Shelf life of perishables will be short if load
limit is violated. Overstocking will adversely
affect product temperature and merchandiser
efficiency.
DO NOT BLOCK AIR GRILLE.
CAUTION
!
At no time should merchandisers be
stocked beyond the load limits indicated.
Improper stocking can cause poor
NOTICE
Do not put heavy objects on case
because it could lead to structural damage.
performace that results in spoiled food.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
4-2
START UP / OPERATION
LOAD LIMIT PROFILES
Load Limit
Load Limit
Load Limit
SMB
SMBT
SMGT
SSGT
SMBV
SMGV
SSGV
Load Limit
Load Limit
Load Limit
SMG
Load Limit
Load Limit
Load Limit
SSG
INSTALLING FDA/NSF REQUIRED
THERMOMETER
This requirement does not apply to display
refrigerators intended for bulk produce (refer
to page 1-1).
The following pages provide the same informa-
tion that ships with the thermometer.
Please note that the tape cannot be exposed after
installation.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
4-3
Suggested Mounting Locations
in Single Deck Glass Front
Impact Merchandisers
This is an NSF-7 &
US FDA Food Code
Required
Package Guard,
Facing Out
Thermometer
Thermometer — Hussmann Part TM.4911251
Hussmann Corporation • 12999 St. Charles Rock Road • Bridgeton, MO 63044-2483
© 2007 Hussmann Corporation
Double Stick Tape
End Panel
Price Tag
Molding
Flexible Plastic
Fits in Price Tag
Moldings
Suggested Mounting Locations
in Multi-deck Merchandisers
Hussmann P/N 0429971_C
10/2007
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
4-4
START UP / OPERATION
Important – Please read!
This thermometer is provided in response to United States
and
Each installation will be different
The thermometer may need to be
moved several times to find the
warmest location. Mounting options
include flexible plastic for price tag
molding application, magnet
depending on how the unit is
stocked, shopping patterns in the
department and ambient conditions
of the store. The suggested loca-
tions provided herein are possible
locations. It is the responsibility of
the purchaser / user to determine
the location within the food storage
area of the unit that best meets the
code requirements above.
applied to back of flexible plastic for
steel end wall, and double stick
tape. Tape must not be exposed
after installation.
Questions about either code should
be addressed to local agencies or
other appropriate officials.
Keep with merchandiser
or give to store manager.
DO NOT DESTROY.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
5-1
MAINTENANCE
CARE AND CLEANING
WARNING
ALWAYS SHUT POWER OFF
!
Long life and satisfactory performance of any
equipment is dependent upon the care it
receives. To ensure long life, proper sanitation
and minimum maintenance costs, these mer-
chandisers should be thoroughly cleaned, all
debris removed and the interiors washed down,
at least weekly.
Prevent injury.
during cleaning process.
Do Not Use:
•
•
•
Abrasive cleansers and scouring pads, as
these will mar the finish.
Exterior Surfaces
The exterior surfaces must be cleaned with a
mild domestic detergent and warm water to
protect and maintain their attractive finish.
NEVER USE ABRASIVE CLEANERS OR SCOURING
PADS. DO NOT USE AMMONIA BASED CLEANERS
ON ACRYLIC PARTS.
A hose on lighted shelves or submerge the
shelves in water.
Solvent, oil or acidic based cleaners on any
interior surfaces.
Do:
Interior Surfaces
•
Remove the product and all loose debris to
The interior surfaces may be cleaned with most
domestic detergents, ammonia based cleaners
and sanitizing solutions with no harm to the
surface. Removable parts are labeled REMOVE
FOR CLEANING.
avoid clogging the waste outlet.
•
Store product in a refrigerated area such as a
cooler. Remove only as much product as can
be taken to the cooler in a timely manner.
Turn off refrigeration, then disconnect
electrical power.
Thoroughly clean all surfaces with mild
detergent and water (105 to 140°F / 40 to
60°C). DO NOT USE STEAM OR HIGH WATER
PRESSURE HOSES TO WASH THE INTERIOR.
THESE WILL DESTROY THE MERCHANDISER’S
LINER AND SEALS CAUSING LEAKS AND POOR
PERFORMANCE.
Lift or remove fan plenum for cleaning.
Hook chain in rear panel to secure plenum
during cleaning. Be sure to reposition the fan
plenum after cleaning merchandiser.
Take care to minimize direct contact between
fan motors and cleaning or rinse water.
Rinse with water, but do NOT flood. NEVER
INTRODUCE WATER FASTER THAN THE WASTE
OUTLET CAN REMOVE IT.
•
•
Removable stainless steel parts may be cleaned
and sanitized in dishwasher.
See next page for detailed direction.
NOTICE
Product will be degraded
and may spoil if allowed to sit
in a non-refrigerated area.
•
•
•
CAUTION
!
Do NOT use HOT water on COLD glass
surfaces. This can cause the glass to
shatter and could result in personal
injury. Allow glass fronts, ends, and
service doors to warm before applying
hot water.
•
•
Allow merchandisers to dry before resuming
operation.
After cleaning is completed, turn on power
to the merchandiser.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
5-2
MAINTENANCE
INTERIOR CLEANING STEPS
WARNING
!
NOTICE
— LOCK OUT / TAG OUT —
Product will be degraded
and may spoil if allowed to sit
in a non-refrigerated area .
To avoid serious injury or death from electri-
cal shock, always disconnect the electrical
power at the main disconnect when servicing
or replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
STEP 1 – Remove product to cooler.
STEP 4 – Unplug shelves and close receptacle
caps, then
41°F
(5°C)
STEP 2 – Turn off refrigeration.
remove shelves.
STEP 3 – Shut power off.
Note that refrigeration controls
and power controls are not in
the merchandiser. Consult the
store legend or facility manager.
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
5-3
STEP 5 – Remove display pans.
STEP 8 – Lift out interior back panel.
STEP 6 – Lift out display pan support.
STEP 9 – Lift out upper shelf supports.
STEP 7 – Lift out discharge air grille.
STEP 10 – Lift out lower shelf supports.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
5-4
MAINTENANCE
STEP 11 – Lift out return air grille (from
front).
OR
Unplug fan harness.
STEP 12 – Rotate fan plenum up and back;
hook chain at rear of liner.
Lift fan plenum up and back to remove.
(view is from the back)
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
5-5
STEP 13 – Remove drip trays.
STEP 14 – Clean inside the merchandiser.
Separate lower end of flexible connector from
drip tube (see page 1-4). Lift and rotate tray as
necessary to clear front and back hooks.
Once interior parts have been removed, collect
loose debris for removal. Do not clog waste
outlet.
STEP 15 – Clean and sanitize according to
Health Code requirements.
Hand wash drip trays. Sanitize drip trays and
drip tubes. Use paper toweling to dry inside and
outside of trays before reinstalling.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
5-6
MAINTENANCE
STEP 16 – Reassemble in reverse order.
REMOVING SCRATCHES FROM
BUMPER
Turn on power, then
refrigeration. Make
certain merchandiser
has cooled to operating
temperature before
restocking.
Most scratches and dings can be removed using
the following procedure.
1. Use steel wool to smooth out the surface
area of the bumper.
2. Clean area.
3. Apply vinyl or car wax and polish surface
for a smooth glossy finish.
CLEANING ANTI-REFLECTIVE GLASS
Anti-Reflective Glass
While the anti-reflective coatings are durable,
they are susceptible to scratching if abrasive
materials are used for cleaning. Once the glass
surfaces are scratched, it is impossible to restore
the original finish. Special care must be taken to
prevent damage when cleaning the glass.
Anti-reflective glass can be cleaned with clear
water or any non-alkaline detergent.
However, it is very important to use a soft
cloth, a micro-fiber cleaning cloth or a wet
sponge.
Never use the following types of materials
to clean glass with anti-reflective coatings:
• Coarse Paper Towels
• Scouring Pads or Powders
• Steel Wool or Steel Fiber Materials
• Blades
• Acidic or highly Alkaline detergents
• Fluorine based detergents
P/N 0420057_B
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
6-1
SERVICE
REPLACING FAN MOTORS AND BLADES
See cross section for location of evaporator fans.
Should it ever be necessary to service or replace
the fan motors or blades be certain that the fan
blades are re-installed correctly. THE BLADES
MUST BE INSTALLED WITH RAISED EMBOSSING
(PART NUMBER ON PLASTIC BLADES) POSITIONED
AS INDICATED ON THE PARTS LIST. (Refer to the
case data sheet for each model.)
WARNING
!
— LOCK OUT / TAG OUT —
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
For access to evaporator fans:
1. Turn off power
3
2. Remove bottom display pans.
3. Disconnect fan from wiring harness.
4. Lift fan plenum out of case. Place on stable
work surface.
5. Remove screws holding fan basket to plenum.
Fan blade may be removed after fan assembly
is removed from plenum.
4
6. Remove screws holding bottom of motor to
fan basket.
7. Replace fan motor and blade in fan basket.
8. Reinstall fan basket in plenum and reinstall
plenum in case.
9. Reconnect fan to wiring harness. Turn power
on.
5
10. Verify that motor is working and blade is
turning in the correct direction.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
6-2
SERVICE
For access to ambient fans:
REMOVING POLYCARBONATE LAMP
COVERS
1. Turn off power.
The canopy and rail covers are removed without
tools. Apply pressure as shown in the photos until
the cover clears the retainer, then pivot out of the
retainer. Reinstall in reverse order.
2. Remove lower front panel.
3. Disconnect fan from wiring harness.
4. Remove screws holding motor and grille.
5. Replace fan motor and grille.
Canopy Fixture
From the front of the case, grasp the cover with
both hands. Pull forward until the back of the
cover clears the retainer, then rotate down and
out.
6. Reconnect fan to wiring harness. Turn power
on.
7. Verify that motor is working and blade is
turning in the correct direction.
8. Replace lower front panel.
Rail Fixture
From the front of the case, grasp the cover with
both hands. Pull forward and up until the back of
the cover clears the retainer.
Screws
P/N 0420057_B
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
6-3
ELECTRICAL SERVICE RECEPTACLES
REPLACING LAMP HOLDERS AND
END CAPS
The receptacles located on the exterior back of the
merchandisers are intended for scales and other
light duty appliances that are found in meat and
delicatessen departments. The receptacles are not
intended for large motors.
The Hussmann Impact lamp holder is designed to
snap into the sheet metal of the case. The lamp
holder has a locking ‘nub’ which fits inside the
groove of specially designed end caps.
REPLACING FLUORESCENT LAMPS
Hussmann
Impact
End-Cap
Groove
Fluorescent lamps are furnished with moisture
resistant lamp holders and end caps. Lamps on
lighted shelves have plastic shields. Whenever a
fluorescent lamp is replaced, be certain to re-
install the plastic shields and end caps.
Plastic Shield
Fluorescent
Lamp
Nub
End Cap
Hussmann
Impact
Lamp Holder
CAUTION
!
IMPORTANT!
Always replace lamp holders and end caps with
Hussmann lamp holders and end caps.
Fluorescent lamps contain mercury vapor.
Mercury exposure at high levels can harm
the brain, heart, kidneys, lungs, and immune
system of people of all ages. Do not break or
puncture fluorescent lamps. Dispose of, or
store, all fluorescent lamps in accordance
with Federal (40 CFR 273), State, and local
hazardous waste requirements. Refer to
Use of non-Hussmann parts may result in poor
electrical contact and short lamp life.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
6-4
SERVICE
REPLACING ELECTRONIC BALLAST
Lamp Ballast
WARNING
!
The lamp ballast are located in the raceway,
behind the back lower panel at the left-hand end
of the merchandiser (facing rear of case). NOTE:
The switch for the lamp is located in this panel.
— LOCK OUT / TAG OUT —
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
To gain access:
1. Disconnect the electrical power to the mer-
chandiser.
2. Remove the left lower rear panel.
3. Service or replace ballast as required.
Reassemble items as they were originally
installed.
4. Reconnect the electrical power.
Remove Screws Holding Panel in Place
Ballast Located
Behind This Panel
Light Switch Below
P/N 0420057_B
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
6-5
REPLACING CYLINDERS —
SINGLE PANE GLASS
1. Raise the front glass to open completely.
2. Use special hand tool, shown in photo, to
compress and remove cylinder.
WARNING
!
Check each glass section monthly to
determine if support cylinders are worn
and need to be replaced. If the glass
does not stay in a raised position, have
the cylinders replaced.
Note: Cylinders cannot be removed without
special hand tool.
Each front curved glass section weighs
about 40 lb (18 kg). To prevent glass
from falling during installation, use or
maintenance and causing injury to
customers or personnel, Hussmann
recommends one person hold the glass
in a raised position while the other
person performs cylinder replacement.
Support the front glass at all times until
cylinder is replaced or the glass is low-
ered.
Cylinder
Removal
Tool
P/N 0425326
NOTICE
Cylinders are a wear item.
They are designed:
• to support the glass when fully open.
• to allow the glass to come down
(or close) slowly.
Have your Service Contractor replace the
cylinders when required.
When cylinders need to be replaced, the lifting
force of the cylinder must be known. The lifting
force can be determined by the data printed on the
cylinder being replaced. The following shows the
part number for the 300N and 400N cylinders.
Removing a Cylinder
300N Cylinder – P/N 0412539
400N Cylinder – P/N 0406925
CAUTION
!
Cylinder rods must point down so
oil will lubricate the rod and seals. Failure to
lubricate will severely shorten cylinder life.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
6-6
SERVICE
REPLACING SINGLE PANE FRONT
GLASS (Requires more than one person.)
!
WARNING
Once set screws are loose, the glass and
glass clamp have NO support or retain-
ers. Support the front glass at all times
until the top glass clamp and set screws
are secured, or glass is removed.
1. Raise the front glass to open completely.
2. Loosen all set screws along the inside bottom
of the glass clamp.
Note: All cylinders do not have to be removed to
remove the glass
IMPORTANT
When reinstalling glass, be certain that:
1. Gasket is on glass evenly.
Fully Engage Glass
in Clamp
2. Glass bottom is fully in retainer.
Gasket
3. When set screws are tightened, glass is firmly
held in place by the glass clamps.
Set Screw Locations
P/N 0420057_B
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 0420057_B
6-7
REPLACING GLASS HAND GRIP
Type: Two cylinders and three fastening points.
P/N 0407352
The hand grip is fastened to the curved glass as
shown below. A 2 inch (51 mm) bead of silicone
needs to be placed 3 inches (76 mm) from each
end and in the center of the hand grip. The duct
tape is placed on the glass to provide a tight fit.
Used on: 30° outside wedge.
3/8 in. (10 mm) of
Duct Tape on Each
Side of Bottom
Edge of Glass
Duct Tape
Type: Three cylinders and four fastening points.
P/N 0412538
Used on 90° inside wedge, 45° outside and inside
wedge, 30° inside wedge.
Note: This hinge assembly, when used on the 90°
and 45° inside wedge, uses only two cylinders.
Glass
3/8 in. (10 mm)
Start 2 in. (51 mm)
Silicone Bead
3 in. (76 mm)
3 in.
From Each End
(76 mm)
Glass Grip
HINGE HARDWARE
Type: Four cylinders and five fastening points.
P/N 0413170
Type: Two cylinders and one fastening point.
P/N 0401884
Used On: 90° outside wedge.
Used on: 8 ft and 12 ft (2438 mm and 3658 mm)
parent cases and as a joining bracket.
Service Merchandisers
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
6-8
SERVICE
REPAIRING ALUMINUM COIL
WARNING
The aluminum coils used in Hussmann merchan-
disers may be easily repaired in the field.
Materials are available from local refrigeration
wholesalers.
!
Refrigerant vapor is hazardous to your health
and can cause death.
Hussmann recommends the following solders and
technique:
Avoid breathing refrigerant and lubrication
vapor or mist. Exposure may irritate eyes,
nose and throat. If accidental system dis-
charge occurs,ventilate work area before
resuming service
Solders
Aladdin Welding Products Inc.
P.O. Box 7188
1300 Burton St.
Grand Rapids, MI 49507
Phone: 1-800-645-3413
Always wear safety goggles and protective
gloves when working with refrigerants.
Contact with refrigerant may cause injury.
Disconnect hoses with extreme caution! All
hoses may contain liquid refrigerant under
pressure.
Fax:
1-800-645-3414
X-Ergon
1570 E. Northgate
P.O. Box 2102
Irving, TX 75062
Phone: 1-800-527-9916
Be sure that any room where you are working
is thoroughly ventilated, especially if a leak
is suspected.
NOTE:
Hussmann Aluminum melts at 1125°F (607°C)
Read all safety information regarding the safe
handling of refrigerant and refrigerant oil,
includingthe Material Safety Data Sheet.
MSDS sheets can be obtained from your
refrigerant supplier.
Aladdin 3-in-1 rod at
X-Ergon Acid core at
732°F (389°C)
455°F (235°C)
Technique:
1. Locate Leak.
2. REMOVE ALL PRESSURE.
3. Brush area UNDER HEAT.
4. Use PRESTOLITE TORCH ONLY.
Number 6 tip.
Refrigeration lines are under pressure
and should be depressurized before
attempting to make any connections.
When brazing pipes, be sure to use the
insulation blanket shipped with the
merchandiser to prevent fire or damage
to the plastic case bottom.
5. Maintain separate set of stainless steel
brushes and USE ONLY ON ALUMINUM.
6. Tin surface around area.
7. Brush tinned surface UNDER HEAT,
thoroughly filling the open pores around leak.
8. Repair leak. Let aluminum melt solder, NOT
the torch.
9. Don't repair for looks. Go for thickness.
10. Perform a leak check.
11. Wash with water.
12. Cover with a good flexible sealant.
P/N 0420057_B
Download from Www.Somanuals.com. All Manuals Search And Download.
®
To obtain warranty information
or other support, contact your
Hussmann representative.
Please include the model and
serial number of the product.
Hussmann Corporation, Corporate Headquarters: Bridgeton, Missouri, U.S.A. 63044-2483
01 July 2005
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|