Hoshizaki Ice Maker M029 897 User Manual

Hoshizaki America, Inc.  
Hoshizaki  
Stackable Square Cuber  
Model  
IM-500SAA  
SERVICE MANUAL  
“A Superior Degree  
of Reliability”  
Number: M029-897  
Issued: 2-8-2013  
Revised: 5-19-2014  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
This manual should be read carefully before the appliance is serviced. Read  
the warnings and guidelines contained in this manual carefully as they provide  
essential information for the continued safe use, service, and maintenance of the  
appliance. Retain this manual for any further reference that may be necessary.  
CONTENTS  
Important Safety Information ................................................................................................. 4  
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 6  
A. Construction.................................................................................................................. 6  
B. Water/Refrigeration Circuit Diagram.............................................................................. 7  
II. Sequence of Operation and Service Diagnosis................................................................. 8  
A. Sequence of Operation Flow Chart............................................................................... 8  
B. Sequence of Operation ................................................................................................. 9  
1. Startup Cycle............................................................................................................ 9  
2. Harvest Cycle .......................................................................................................... 9  
3. Freeze Cycle............................................................................................................ 9  
4. Shutdown............................................................................................................... 10  
C. Service Diagnosis Table...............................................................................................11  
D. Bin Control Check and Cleaning ................................................................................. 14  
1. Bin Control Check .................................................................................................. 14  
2. Bin Control Cleaning.............................................................................................. 15  
E. Evaporator Thermistor Check...................................................................................... 16  
III. Controls and Adjustments............................................................................................... 17  
A. Control Switch............................................................................................................. 17  
B. Control Board .............................................................................................................. 17  
1. Control Board Layout ............................................................................................. 18  
C. Control Buttons............................................................................................................ 19  
D. Control Board Settings ................................................................................................ 20  
E. Control Board Information Display .............................................................................. 23  
F. Control Board Model Code Setting .............................................................................. 25  
1. Control Board Replacement................................................................................... 25  
2. Checking or Changing the Control Board Model Code.......................................... 25  
G. Error Codes ................................................................................................................ 27  
H. Quick Adjustments ...................................................................................................... 28  
1. Dimple Diameter .................................................................................................... 28  
2. Ice Clarity .............................................................................................................. 29  
IV. Refrigeration Circuit and Component Service Information.............................................. 30  
A. Refrigeration Circuit Service Information .................................................................... 30  
B. Component Service Information.................................................................................. 32  
V. Maintenance .................................................................................................................... 34  
VI. Preparing the Icemaker for Periods of Non-Use............................................................. 35  
VII. Disposal......................................................................................................................... 36  
VIII. Technical Information.................................................................................................... 37  
A. Specification Data ....................................................................................................... 37  
B. Performance Data ....................................................................................................... 38  
C. Wiring Diagram ........................................................................................................... 39  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Information  
Throughout this manual, notices appear to bring your attention to situations which could  
result in death, serious injury, damage to the appliance, or damage to property.  
WARNING  
NOTICE  
IMPORTANT  
Indicates a hazardous situation which could result in death or  
serious injury.  
Indicates a situation which could result in damage to the  
appliance or property.  
Indicates important information about the use and care of the  
appliance.  
WARNING  
The appliance should be destined only to the use for which it has been expressly  
conceived. Any other use should be considered improper and therefore dangerous.  
The manufacturer cannot be held responsible for injury or damage resulting from  
improper, incorrect, and unreasonable use. Failure to service and maintain the  
appliance in accordance with this manual will adversely affect safety, performance,  
component life, and warranty coverage and may result in costly water damage.  
To reduce the risk of death, electric shock, serious injury, or fire, follow basic  
precautions including the following:  
• Only qualified service technicians should install and service this appliance.  
• The appliance must be installed in accordance with applicable national, state, and  
local codes and regulations. Failure to meet these code requirements could result in  
death, electric shock, serious injury, re, or damage to the appliance.  
• Electrical connection must be hard-wired and must meet national, state, and local  
electrical code requirements. Failure to meet these code requirements could result  
in death, electric shock, serious injury, re, or damage.  
• The icemaker requires an independent power supply of proper capacity. See the  
nameplate for electrical specifications. Failure to use an independent power supply  
of proper capacity can result in a tripped breaker, blown fuse, damage to existing  
wiring, or component failure. This could lead to heat generation or fire.  
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker  
could result in death or serious injury.  
To reduce the risk of electric shock, do not touch the control switch with damp  
hands.  
• Move the control switch to the "OFF" position and turn off the power supply before  
servicing. Lockout/Tagout to prevent the power supply from being turned back on  
inadvertently.  
• Do not make any alterations to the appliance. Alterations could result in electric  
shock, serious injury, re, or damage.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING, continued  
• The appliance is not intended for use by persons (including children) with reduced  
physical, sensory, or mental capabilities, or lack of experience and knowledge,  
unless they have been given supervision or instruction concerning use of the  
appliance by a person responsible for their safety.  
• Children should be properly supervised around the appliance.  
• Do not climb, stand, or hang on the appliance or allow children or animals to do so.  
Serious injury could occur or the appliance could be damaged.  
• Do not use combustible spray or place volatile or flammable substances near the  
appliance. They might catch fire.  
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance  
could cause harm to individuals or damage to the appliance.  
NOTICE  
• Follow the instructions in this manual carefully to reduce the risk of costly water  
damage.  
• In areas where water damage is a concern, install in a contained area with a floor  
drain.  
• Install the appliance in a location that stays above freezing. Normal operating  
ambient temperature must be within 45°F to 100°F (7°C to 38°C).  
• Do not leave the appliance on during extended periods of non-use, extended  
absences, or in sub-freezing temperatures. To properly prepare the appliance for  
these occasions, follow the instructions in "VI. Preparing the Icemaker for Periods of  
Non-Use."  
• Do not place objects on top of the appliance.  
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in  
the dispenser unit/ice storage bin.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
I. Construction and Water/Refrigeration Circuit Diagram  
A. Construction  
1. Air-Cooled Model (SAA)  
Evaporator  
Water Plate  
Thermostatic Expansion Valve  
Hot Gas Valve  
Inlet Water Valve  
High-Pressure  
Switch  
Condenser  
Pump Motor  
Actuator Motor  
Fan Motor  
Drain Pan  
Control Board Thermistor  
Drier  
Control Box  
Compressor  
Evaporator Thermistor  
Fuse Holder  
Control  
Switch  
Water Tank  
Bin Control  
Model Shown: IM-500SAA  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Water/Refrigeration Circuit Diagram  
1. Air-Cooled Model (SAA)  
Inlet  
Water  
Valve  
Thermostatic Expansion Valve  
Evaporator  
Evaporator Thermistor  
Water Tank  
Water  
Pump  
Condenser  
Heat Exchanger  
Hot Gas  
Valve  
Fan Motor  
Strainer  
Compressor  
Drier  
Water Circuit  
Refrigerant Circuit  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. Sequence of Operation and Service Diagnosis  
A. Sequence of Operation Flow Chart  
"IM" Control Board  
1. 30-Sec.  
Startup  
Cycle  
3. Freeze Cycle  
• Max. freeze time: 45 min. (CB Setting 6)  
2. Harvest Cycle  
Cycle  
Steps  
• HGV: If CBT≤81°F (27°C) (CB Setting  
74), HGV repeatedly energizes 40 sec./  
de-energizes 40 sec.  
• FM: If CBT≥118°F (48°C) (CB Setting 34),  
FM operates continuously in harvest cycle  
• Max. harvest time: 30 min.  
ET≤-1.3°F (-18.5°C)  
(CB Setting 2)  
WV Delay  
*1  
ET≥41°F (5°C)  
(CB Setting 1)  
PM Delay  
Time varies based on  
*4  
control board calculation  
Startup  
Water Tank Closed  
(Actuator Motor PS)  
PM energized If CBT>81°F (27°C) (CB  
WV energized *2  
HGV energized  
Setting 74) and CBT≤111°F  
(44°C) (CB Setting 70), HGV  
energizes 5 sec./de-energizes  
25 sec./energizes 5 sec. (CB  
Setting 71, 72)  
HGV continues Comp continues  
AMD energized AMU energized  
Comp energized FM energized  
WV energized *3  
Comp continues  
FM continues  
WV energized *4+*5  
HGV de-energized  
Shutdown and Restart Sequence Flow Chart  
1. Bin Full  
2. Icemaker Off  
3. Ice Level Lowered  
Shutdown  
and Restart  
Icemaker restarts at  
1. 30-Sec. Startup Cycle.  
BC Operation  
BC open 10 sec. or more All components  
BC closed 80 sec. or more  
(BC actuator paddle  
disengaged).  
(BC actuator paddle  
engaged). Shutdown  
occurs at end of harvest  
cycle.  
de-energized.  
Initial Harvest and  
Initial Freeze after  
Power On  
Initial Harvest and Initial Freeze after  
Bin Control Initiated Restart  
Normal Harvest and Freeze  
CB  
Note  
Setting  
All WT  
20 sec.  
*2 10, 11 95 sec.  
WT>48°F (9°C)  
0 sec.  
10 sec. (CB Setting NA) 95 sec.  
WT≤48°F (9°C) WT>48°F (9°C) WT≤48°F (9°C)  
*1 NA  
0 sec.  
20 sec.  
30 sec.  
0 sec.  
20 sec.  
95 sec.  
10 sec.  
30 sec.  
22 sec.  
60 sec.  
44 sec.  
*3 NA  
PD*4 12  
PD*5 15  
FD*4 12  
FD*5 15  
10 sec.  
0 sec.  
10 sec.  
30 sec. × 2  
22 sec. × 2  
60 sec.  
30 sec. × 2  
22 sec. × 2  
60 sec.  
30 sec. × 2  
22 sec. × 2  
60 sec.  
30 sec.  
22 sec.  
60 sec.  
44 sec.  
44 sec.  
44 sec.  
44 sec.  
Legend:  
FM–fan motor  
HGV–hot gas valve  
PD–partial drain (CB Setting 14)  
PM–pump motor  
PS–position sensor  
AMD–actuator motor down  
AMU–actuator motor up  
BC–bin control  
CBT–control board thermistor  
Comp–compressor  
WT–water temperature  
WV–inlet water valve  
ET–evaporator thermistor  
FD–full drain (CB Setting 14)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Sequence of Operation  
1. Startup Cycle  
When power supply is turned on, "on" appears on CB display and HGV energizes.  
30 sec. later, harvest cycle starts.  
• If the "RESET" button is pressed during 30-sec. startup cycle time, startup cycle ends  
immediately and harvest cycle starts.  
2. Harvest Cycle  
HGV continues. Comp and AMD energize. WV energizes as listed in table below.  
Initial Harvest Initial Harvest after Bin Control  
Normal Harvest  
CB  
Setting  
after Power On  
Initiated Restart  
Note  
All WT  
WT>48°F (9°C) WT≤48°F (9°C) WT>48°F (9°C) WT≤48°F (9°C)  
WV Delay  
WV Time after 10, 11 95 sec.  
WV Delay  
NA  
20 sec.  
0 sec.  
10 sec.  
(CB Setting NA)  
0 sec.  
95 sec.  
20 sec.  
30 sec.  
20 sec.  
95 sec.  
WV Time  
when  
NA  
10 sec.  
0 sec.  
10 sec.  
0 sec.  
10 sec.  
ET≥41°F  
(5°C)  
(CB Setting 1)  
Note: ET temperature is recorded 30 seconds after PM energizes in the preceding  
freeze cycle. Water temperature correction value (CB Setting 13) is added to ET  
temperature and this is used as WT value.  
If CBT≤81°F (27°C) (CB Setting 74) at beginning of harvest cycle, HGV repeatedly  
energizes 40 sec./de-energizes 40 sec. If CBT≥118°F (48°C) (CB Setting 34) at  
beginning of harvest cycle, FM operates continuously in harvest cycle.  
When ET reaches harvest cycle termination temperature (CB Setting 1) of 41°F (5°C) ,  
HGV de-energizes, FM and AMU energize. Comp continues. WV energizes as listed in  
table above. Harvest cycle is complete when actuator motor PS indicates water tank is  
fully closed.  
3. Freeze Cycle  
Comp and FM continue. WV energizes for total time of WV Time 1 and WV Time 2 listed  
in table below. PM energizes after PM delay listed in table below.  
Initial Freeze Initial Freeze after Bin Control  
Normal Freeze  
CB  
Setting  
after Power On  
Initiated Restart  
Note  
All WT  
All WT  
All WT  
PD  
WV Time 1  
and PM Delay  
PD  
12  
30 sec. × 2  
30 sec. × 2  
30 sec.  
15  
12  
22 sec. × 2  
60 sec.  
22 sec. × 2  
60 sec.  
22 sec.  
60 sec.  
WV Time 2  
FD  
WV Time 1  
and PM Delay  
FD  
15  
44 sec.  
44 sec.  
44 sec.  
WV Time 2  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
ET temperature is recorded 30 seconds after PM energizes. Water temperature  
correction value (CB Setting 13) is added to ET temperature and this is used as WT  
value in following harvest cycle.  
If CBT>81°F (27°C) (CB Setting 74) and CBT≤111°F (44°C) (CB Setting 70), when  
ET≤-1.3°F (-18.5°C) (CB Setting 2), HGV energizes 5 sec., de-energizes 25 sec.,  
energizes 5 sec. (CB Settings 71 and 72) to reduce bonding of the water tank to the  
evaporator.  
CB monitors time after ET temperature≤32°F (0°C). CB terminates freeze cycle when the  
following equation is satisfied:  
temp. (absolute value) × time (min.) = (absolute value of CB Setting 2) × (CB Setting 3)  
Using default settings, freeze cycle is terminated when:  
temp. (absolute value) × time (min.) = 185  
This formula helps maintain consistent dimple size regardless of differences in seasonal  
ambient and water temperatures.  
4. Shutdown  
When BC is engaged (open) for more than 10 seconds, the icemaker shuts down after  
harvest cycle.  
When BC is disengaged (closed) for more than 80 seconds, icemaker restarts at startup  
cycle.  
If BC is engaged (open) while the water tank is opening after the power supply is turned  
on (or after the "RESET" button is pressed), shutdown does not start: Shutdown occurs  
10 seconds after actuator motor's internal position sensor indicates water tank is fully  
open.  
Legend: AMD–actuator motor down; AMU–actuator motor up; BC–bin control; CB–control  
board; CBT–control board thermistor; Comp–compressor; ET–evaporator  
thermistor; FD–full drain (CB Setting 14); FM–fan motor; HGV–hot gas valve;  
PM–pump motor; PD–partial drain (CB Setting 14); PS–position sensor; WT–water  
temperature; WV–inlet water valve  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Service Diagnosis Table  
First see "III.G. Error Codes." If there are no recorded errors, refer to the table below.  
No Ice Production - Possible Cause  
1. Power Supply  
a) Off, blown fuse, or tripped breaker.  
b) Not within specifications.  
a) Blown.  
2. Fuse (Control Box)  
3. Control Switch  
a) In "OFF" or "WASH" position.  
b) Bad contacts.  
4. High-Pressure Switch  
a) Dirty condenser or air filter.  
b) Fan motor not operating.  
c) Refrigerant overcharged.  
d) Bad contacts.  
e) Refrigerant lines or components restricted.  
a) Coil winding open or shorted.  
5. Control Transformer  
(115VAC/10.5VAC)  
6. Control Board  
a) Error. See "III.G. Error Codes."  
b) Defective.  
7. Bin Control  
See "II.D. Bin Control Check and  
Cleaning"  
a) Tripped with bin filled with ice.  
b) Actuator does not move freely.  
c) Defective.  
8. Water Supply  
9. Inlet Water Valve  
10. Compressor  
a) Water supply off or improper water pressure.  
b) External water filters restricted.  
a) Screen or orifice restricted.  
b) Coil winding open.  
a) Compressor relay/magnetic contactor contacts bad or coil winding  
open.  
b) Start capacitor or run capacitor defective (single phase).  
c) Internal protector open.  
d) Start relay contacts bad or coil winding open (single phase).  
e) Defective.  
11. Hot Gas Valve  
a) Defective.  
12. Evaporator (Cube Control)  
Thermistor  
a) Loose, disconnected, or defective.  
See "II.E. Evaporator Thermistor  
Check"  
13. Pump Motor  
a) Mechanical seal worn out.  
b) Defective.  
c) Defective capacitor.  
a) Bulb loose.  
14. Thermostatic Expansion Valve  
15. Fan Motor  
b) Defective.  
a) Defective.  
b) Defective capacitor.  
a) Water leaks.  
16. Water System  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Low Ice Production - Possible Cause  
Long Harvest Cycle  
a) Scaled up.  
a) Low.  
1. Evaporator  
2. Refrigerant Charge  
3. Control Board  
a) Thermistor connection loose (K3).  
b) Defective.  
4. Evaporator (Cube Control)  
Thermistor  
a) Loose, disconnected, or defective.  
See "II.E. Evaporator Thermistor  
Check"  
5. Hot Gas Valve  
a) Erratic or closed.  
a) Inefficient or off.  
a) Defective.  
6. Compressor  
7. Thermostatic Expansion Valve  
Long Freeze Cycle  
a) Scaled up, dirty.  
a) Defective.  
1. Evaporator  
2. Hot Gas Valve  
3. Condenser  
a) Restricted.  
4. Control Board  
a) Defective.  
5. Refrigerant Charge  
6. Thermostatic Expansion Valve  
a) Low.  
a) Bulb loose.  
b) Defective.  
7. Compressor  
a) Inefficient or off.  
Slab Does Not Break Into Separate Cubes - Possible Cause  
1. Spring  
a) Over-extended.  
2. Water Plate  
a) Obstacle caught between evaporator and water plate.  
Cubes Drop Separately - Possible Cause  
1. Refrigerant Charge  
2. Cam Arm  
a) Low - Long harvest cycle.  
a) Worn out.  
Imperfect Ice Production - Possible Cause  
1. Water Supply  
a) Improper water pressure.  
b) External water filters restricted.  
c) Water leaks from water tank or water plate due to broken tank or  
plate or icemaker out of level.  
2. Inlet Water Valve  
3. Water Plate  
a) Water leaks from valve body or water supply pipe joint.  
a) Spray holes restricted.  
4. Pump Motor  
a) Defective.  
Large-Hole Cubes - Possible Cause (Also see III.H.1. Dimple Diameter")  
1. Refrigerant Charge  
2. Condenser  
a) Low.  
a) Dirty condenser or air filter.  
a) Defective.  
3. Fan Motor  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Large-Hole Cubes - Possible Cause (Also see III.H.1. Dimple Diameter")  
4. Icemaker Location  
a) Insufficient clearance.  
b) Ambient temperature too high.  
a) Water leaks.  
5. Water Supply  
b) Improper water pressure.  
Cloudy Cubes - Possible Cause  
1. Water Quality  
a) High hardness. See "III.H.2. Ice Clarity."  
2. Slush Ice  
a) Use Anti-Slush Control (Control Board Settings 50 and 51).  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Bin Control Check and Cleaning  
1. Bin Control Check  
This appliance uses a lever-actuated proximity switch to control the ice level in the  
storage bin. No adjustment is required.  
To check, follow the steps below.  
1) Turn off the power supply.  
2) Remove the front panel, then move the control switch to the "OFF" position.  
3) Remove the control box cover. Clear any ice away from BC.  
4) Check BC wire harness connections.  
5) Disconnect BC wire harness connector from CB CN11 connector.  
6) Check for continuity across the wires of BC wire harness connector. When the actuator  
paddle is not engaged, BC switch is closed. If open, check that the wire harness  
connector is properly connected and that the actuator paddle is not sticking. Clean if  
necessary. See "II.D.2. Bin Control Cleaning." If BC switch still reads open, replace BC.  
7) Press and hold the actuator paddle; check for continuity across the wires of BC wire  
harness connector. When the actuator paddle is engaged, BC switch is open. If closed,  
check that the actuator paddle is not restricted. Clean if necessary. See "II.D.2. Bin  
Control Cleaning." If BC switch still reads closed, replace BC.  
8) Reconnect BC wire harness connector to CB CN11 connector, then move the control  
switch to the "ICE" position. Turn on the power supply.  
9) Allow the icemaker to cycle on. Press and hold the actuator paddle for at least  
10 seconds. The icemaker should shut down. If it does not, replace CB.  
Note: If BC is engaged (open) while the water tank is opening after the power supply  
is turned on (or after the "RESET" button is pressed), shutdown does not start:  
Shutdown occurs 10 seconds after actuator motor's internal position sensor  
indicates water tank is fully open.  
Legend: BC–bin control; CB–control board  
Bin Control Bracket  
Thumbscrew  
Bin Control Cable Connector  
Bin Control  
Fig. 1  
Switch Mount  
Actuator Paddle  
Magnet  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Bin Control Cleaning  
Scale may build up on BC. Scale can cause the actuator paddle and magnet to stick. In  
this case, BC should be cleaned.  
WARNING  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after the icemaker is serviced. Make sure that none have fallen  
into the dispense unit/ice storage bin.  
1) Turn off the power supply.  
2) Remove the front panel, then move the control switch to the "OFF" position.  
3) Clear any ice away from BC.  
4) Carefully remove the BC cable from the cable ties in the evaporator case, then remove  
the BC from the bin control bracket and move to the front of the icemaker for cleaning.  
5) Remove the actuator paddle from the switch mount. See Fig. 1.  
6) Wipe down BC with a mixture of 1 part of Hoshizaki "Scale Away" and 25 parts of warm  
water. Rinse the parts thoroughly with clean water.  
7) Reassemble BC and replace it in its correct position.  
Note: If the magnet was removed for cleaning, be sure to replace it in its correct  
position.  
8) Replace the BC cable into the cable ties in the evaporator case, then move the control  
switch to the "ICE" position.  
9) Confirm CB wire harness connections are secure, then replace the control box cover in  
its correct position.  
10) Turn on the power supply to start the automatic icemaking process.  
11) Replace the front panel in its correct position.  
Legend: BC–bin control; CB–control board  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E. Evaporator Thermistor Check  
To check thermistor resistance, follow the steps below.  
1) Turn off the power supply.  
2) Remove the front panel. Move the control switch to the "OFF" position.  
3) Remove the control box cover.  
4) Remove the thermistor from the evaporator.  
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.  
6) Disconnect the thermistor connector from CB CN13 connector and check the resistance  
between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range,  
replace the thermistor. See "IV.B. Component Service Information." If within the normal  
range, continue to the next step.  
7) Replace the thermistor in its correct position. See "IV.B. Component Service  
Information."  
8) Reconnect the thermistor connector to CB CN13 connector.  
9) Replace the control box cover in its correct position.  
10) Move the control switch to the "ICE" position.  
11) Replace the front panel in its correct position.  
12) Turn on the power supply.  
Legend: CB–control board; Comp–compressor  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Controls and Adjustments  
A. Control Switch  
The control switch has three positions: OFF for power off, ICE for icemaking, and WASH  
to energize the water pump when cleaning and sanitizing.  
B. Control Board  
• A Hoshizaki exclusive control board is employed in IM series appliances.  
• All models are pretested and factory adjusted.  
NOTICE  
• Fragile, handle very carefully.  
• The control board contains integrated circuits, which are susceptible to failure  
due to static discharge. It is especially important to touch the metal part of the  
icemaker when handling or replacing the control board.  
• Do not touch the electronic devices on the control board or the back of the control  
board.  
• Do not change wiring and connections.  
• Do not short out power supply to test for voltage.  
• Always replace the whole control board assembly if it goes bad.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Control Board Layout  
• CN16 Connector  
Actuator Motor Position Sensor (Hall IC) Input  
• CN11 Connector  
Bin Control Input  
• CN13 Connector  
Evaporator (Cube Control) Thermistor Input  
• CN10 Connector  
• CN9 Connector  
Compressor Start DC Relay Drive Output  
• CN4 Connector  
Display Output  
Data Input/Output  
• RESET Button  
• CN1 Connector  
Control Transformer (10.5VAC) Input  
• SERVICE 1 Button  
• SERVICE 2 Button  
• CN2 Connector  
115VAC Input  
• CN5 Connector  
Actuator Motor Output  
• F1 Fuse  
6.3A, 250VAC  
• CN3 Connector  
115VAC Output: Pump Motor; Hot Gas Valve;  
Fan Motor; Inlet Water Valve; Compressor Relay  
"IM" Control Board  
Part Number P01873-01 Version 1.3A or Later  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Control Buttons  
The control board features RESET, SERVICE 1, and SERVICE 2 Buttons  
1. RESET Button  
• Press briefly to go to initial harvest cycle.  
• Press and hold for 3 seconds to enter control board setting mode. For details about  
control board settings, see "III.D. Control Board Setting Mode and Control Board  
Settings."  
2. SERVICE 1 and SERVICE 2 Buttons  
• Press the "SERVICE 1" or "SERVICE 2" button briefly to display the current freeze  
cycle termination temperature (Control Board Setting 2). This setting controls dimple  
diameter. For details about adjusting the dimple diameter, see "III.H.1. Dimple  
Diameter." NOTICE! Do not decrease dimple size below 3/16" (5 mm).  
• Press and hold the "SERVICE 1" button for 3 seconds to enter information display and  
model code setting mode. For details about information display and model code setting,  
see "III.F. Model Code Setting Mode."  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Control Board Settings  
NOTICE  
Failure to maintain factory settings may adversely affect performance and warranty  
coverage. For more information, contact your Hoshizaki Service Center.  
1) With "on" in display, press and hold the "RESET" button for 3 seconds. Display changes  
to "1".  
2) Use the "SERVICE 1" and "SERVICE 2" buttons to choose a control board setting.  
3) Press the "RESET" button to view the setting’s value. Current value flashes in display.  
4) Use the "SERVICE 1" and "SERVICE 2" buttons to change value.  
5) Press the "RESET" button to select value. Display returns to control board setting  
number.  
6) Once display returns to "on" (20 seconds), the new setting is saved.  
Control Board (CB) Setting Menu  
IM-500SAA  
Category  
No. Item  
Range  
Default  
Basic  
1
Harvest Cycle Termination Temperature  
2 to 20°C  
5
Temperature to complete harvest cycle.  
(1°C increments)  
2
Freeze Cycle Termination Temperature  
-5 to -40°C  
-18.5  
Integrated with freeze cycle termination time (CB  
Setting 3) to control length of freeze cycle after  
evaporator (cube control) thermistor temperature  
drops to 32°F (0°C). To use this setting for dimple  
size adjustment, see "III.H.1. Dimple Diameter."  
(0.5°C increments. The  
"." in the lower, right  
corner of the display  
indicates .5°C.)  
3
Freeze Cycle Termination Time  
5 to 90 min.  
10  
Integrated with freeze cycle termination temperature (1 min. increments)  
(CB Setting 2) to control length of freeze cycle after  
evaporator (cube control) thermistor temperature  
drops to 32°F (0°C).  
4
5
6
Ambient Temperature Correction Value for Freeze  
Cycle Termination  
DO NOT ADJUST  
10 to 50°C  
(1°C increments)  
10  
100  
45  
Ambient Temperature Correction Rate for Freeze  
Cycle Termination  
DO NOT ADJUST  
10 to 100% (00 = 100)  
(1% increments)  
Freeze Cycle Backup Timer  
45 to 90 min.  
Maximum allowed freeze time to prevent possible  
freeze-up issues.  
(5 min. increments)  
Water  
Supply  
10 Harvest Cycle Water Supply Time: Water  
Temperature 48°F (9°C) or Lower  
1 to 99 sec,  
99 = continuous  
(1 sec. increments)  
95  
When set to "99", inlet water valve energized until  
harvest cycle termination temperature (CB Setting 1)  
is reached.  
11 Harvest Cycle Water Supply Time: Water  
Temperature Higher Than 48°F (9°C)  
When set to "99", inlet water valve energized until  
harvest cycle termination temperature (CB Setting 1)  
is reached.  
1 to 99 sec,  
99 = continuous  
(1 sec. increments)  
30  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Board (CB) Setting Menu  
IM-500SAA  
Default  
Category  
No. Item  
Range  
Water  
Supply,  
continued  
12 Freeze Cycle Water Supply Time 1: Partial Drain (CB 0 to 90 sec.  
30  
60  
11  
Setting 14)  
(1 sec. increments)  
Freeze Cycle Water Supply Time 1: Full Drain (CB  
Setting 14)  
13 Water Temperature Correction Value  
+0 to +20°C  
Value added to correct the difference between  
the temperature at the evaporator (cube control)  
thermistor and actual water supply temperature.  
(1°C increments)  
14 Partial/Full Drain Selection  
Partial=1; Full=0  
1
Controls timing for inlet water valve and pump motor  
in the freeze cycle.  
Partial Drain: Pump motor energizes after freeze  
cycle water supply time 1 (CB Setting 12) timer  
terminates. During the first freeze cycle after startup  
or following a bin control initiated shutdown and  
restart, freeze cycle water supply times 1 and 2 (CB  
Settings 12 and 15) are doubled.  
Full Drain: Pump motor energizes after freeze cycle  
water supply time 1 (CB Setting 12) timer terminates.  
If full drain is selected, change freeze cycle making  
water supply times 1 and 2 (CB Settings 12 and 15)  
to the full drain times listed in this table and move  
the water tank drain pipe to the drain position. For  
details, see "III.H.2. Ice Clarity."  
15 Freeze Cycle Water Supply Time 2: Partial Drain (CB 0 to 90 sec.  
22  
44  
1
Setting 14)  
(1 sec. increments)  
Freeze Cycle Water Supply Time 2: Full Drain (CB  
Setting 14)  
Other  
Model  
21 Stackable Bin Control  
Allows for stacked units to be controlled through one  
bin control.  
Yes=1; No=0  
DO NOT ADJUST  
22 Refrigeration Circuit Cycling when Bin Full  
On=1; Off=0  
0 to 3  
0
3
DO NOT ADJUST  
30 Type  
0: WC, PS, No CondTherm, Ignore CB Setting 34  
1: AC, No PS, No CondTherm, Use CB Setting 34  
2: AC, No PS, CondTherm, Use CB Setting 34  
3: AC, PS, No CondTherm, Use CB Setting 34  
DO NOT ADJUST  
Harvest  
34  
40 to 70°C  
(1°C increments)  
48  
Harvest Cycle High Temperature Control  
Cycle High  
Temperature  
Control  
Active if type setting (CB Setting 30) is set to 1, 2,  
or 3. If control board thermistor temperature at the  
beginning of harvest cycle is equal to or greater than  
the harvest cycle high temperature control setting,  
fan motor operates continuously in harvest cycle.  
Water  
Regulating  
Valve  
36 Water Regulating Valve Error Detection Temperature 0 to 50°C  
DO NOT ADJUST 0=ignore, air-cooled  
0
model  
(1°C increments)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Board (CB) Setting Menu  
Category No. Item  
IM-500SAA  
Default  
Range  
Compressor 37 Compressor Output Selection  
0: X8 (DC Relay) On  
1: X1 (AC Relay) On  
1
DO NOT ADJUST  
Anti-Slush  
Control  
50 Pump De-Energized Time  
0 to 90 sec.  
0=ignore, no anti-slush  
(1 sec. increments)  
0
When temperature at evaporator (cube control)  
thermistor drops to 37°F (3°C) in the freeze cycle,  
pump de-energizes for the length of time set.  
51 Anti-Slush Control Water Supply Time  
Time inlet water valve is energized while pump is  
de-energized if pump de-energized time (CB Setting  
50) is greater than 0.  
0 to 5 sec.  
(1 sec. increments)  
0
Hard Water 60 Integrated Value  
Control If hard water control water supply time (CB Setting  
10 to 100%  
(00=100)  
10  
61) is greater than 0: After evaporator (cube control) (1% increments)  
thermistor indicates temperature of 32°F (0°C) in  
freeze cycle, inlet water valve energized starting  
when percentage of freeze cycle termination  
temperature and freeze cycle time integrated value  
has been achieved.  
DO NOT ADJUST  
61 Hard Water Control Water Supply Time  
Time inlet water valve is energized after integrated  
value (CB Setting 60) conditions are met.  
Before using this setting, follow the instructions to  
improve ice clarity; see "III.H.2. Ice Clarity."  
0 to 90 sec.  
(1 sec. increments)  
0
Water Tank 70 If control board thermistor temperature is above  
Ice Control 71 the water tank ice control lower temperature setting  
72 (CB Setting 74) and equal to or less than the  
74 water tank ice control upper temperature setting  
(CB Setting 70) when freeze cycle termination  
See Ranges Below  
See  
Defaults  
Below  
temperature (CB Setting 2) is met, the hot gas valve  
energizes/de-energizes/energizes for the times set  
by the hot gas valve energized/de-energized times  
(CB Settings 71 and 72) to reduce bonding of the  
water tank to the evaporator.  
Water Tank 70 Water Tank Ice Control Upper Temperature  
10 to 60°C  
44  
Ice Control  
& Ice Bridge  
Control  
See CB Setting 70, 71, 72, 74 description above.  
Ice Bridge Control Temperature  
See CB Setting 73 description below.  
(1°C increments)  
Water Tank 71 Water Tank Ice Control Hot Gas Valve Energized  
0 to 20 sec.  
(1 sec. increments)  
5
25  
0
Ice Control  
Time  
See CB Setting 70, 71, 72, 74 description above.  
72 Water Tank Ice Control Hot Gas Valve De-Energized 10 to 60 sec.  
Time  
(1 sec. increments)  
See CB Setting 70, 71, 72, 74 description above.  
Ice Bridge  
Control  
73 Ice Bridge Control Hot Gas Valve De-Energized Time 0 to 30 sec.  
Time hot gas valve is de-energized after 20 sec. in  
harvest cycle if control board thermistor temperature  
is above the ice bridge control temperature  
(CB Setting 70) when freeze cycle termination  
temperature (CB Setting 2) is met.  
(1 sec. increments)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Board (CB) Setting Menu  
IM-500SAA  
Default  
Category  
No. Item  
Range  
Water Tank 74 Water Tank Ice Control Lower Temperature  
0 to 40°C  
27  
Ice Control  
& Harvest  
Cycle Low  
Temperature  
Control  
See CB Setting 70, 71, 72, 74 description above.  
Harvest Cycle Low Temperature Control  
(1°C increments)  
If control board thermistor temperature at the  
beginning of harvest cycle is equal to or less than  
the harvest cycle low temperature control setting, hot  
gas valve repeatedly energizes for 40 seconds then  
de-energizes for 40 seconds to promote a balanced  
harvest across the evaporator plate.  
E. Control Board Information Display  
1. With unit on, press and hold the "SERVICE 1" button for 3 seconds. Display changes to  
"n1".  
2. Use the "SERVICE 1" and "SERVICE 2" buttons to move through the list.  
3. Press the "RESET" button to view the item’s value.  
4. Press the "RESET" button to return to list.  
5. Display returns to normal if no buttons are touched for 20 seconds.  
Control Board Information Display  
History Cleared by  
Pressing and Holding  
SERVICE 1 and  
SERVICE 2 Buttons  
Simultaneously for  
5 Sec. when Item Value  
No. Item  
Description  
is Displayed?  
n1 Freeze Cycle Time  
0 to 99 min.  
No  
During Freeze Cycle: Time since freeze cycle  
started.  
After Freeze Cycle: Time of previous freeze cycle.  
n2 Freeze Cycle Completion Rate  
During Freeze Cycle: Percent of freeze cycle  
completed.  
0 to 100%  
00 = 100%  
No  
After Freeze Cycle: Percent of previous freeze  
cycle completed.  
n3 Current Evaporator (Cube Control) Thermistor  
Temperature  
°C  
°C  
No  
No  
n4 Current Control Board Thermistor Temperature  
n5 Water Temperature  
"H" if Higher than 48°F No  
Temperature at evaporator (cube control)  
thermistor 30 seconds after pump motor  
energized in freeze cycle plus the water  
temperature correction value (Control Board  
Setting 13).  
(9°C)  
"L" if 48°F (9°C) or  
Lower  
n6 Current Condenser Thermistor Temperature  
Not Applicable to IM-500SAA  
°C  
No  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Board Information Display  
History Cleared by  
Pressing and Holding  
SERVICE 1 and  
SERVICE 2 Buttons  
Simultaneously for  
5 Sec. when Item Value  
is Displayed?  
No. Item  
Description  
h1 Last Completed Freeze Cycle Time  
Freeze cycles interrupted by bin control shutdown  
or the "RESET" button are not recorded.  
0 to 99 min.  
Yes  
h2 Number of Completed Freeze Cycles Since Last Displays up to 999,999 Yes  
Counter Reset cycles. Displays two  
Counter updates every 10 freeze cycles. Freeze digits at a time. For  
cycles interrupted by bin control shutdown or the example, 655,350 cycles  
"RESET" button are not recorded.  
display as follows:  
65>off>53>off>50>off>- -  
(repeat)  
h3 Total Number of Completed Freeze Cycles  
Counter updates every 10 freeze cycles. Freeze  
cycles interrupted by bin control shutdown or the  
"RESET" button are not recorded.  
No  
h4 Error Log  
For example, E5 (most Yes  
Displays up to 5 errors with the most recent error recent), E4, E3, E2,  
first. For error details, see "III.G. Error Codes."  
E1 (least recent of up  
to 5 errors) displays as  
follows:  
E5>off>E4>off>E3>off>E  
2>off>E1>off>- - (repeat)  
h5 Firmware Version  
For example, version  
1.0A, displays as follows:  
01.>off>0A>off>- -  
(repeat)  
No  
Displays control board's firmware version.  
h6 Model Code  
Displays two-character No  
model code.  
"00" to "FF"  
The model code puts all settings for a given  
model to the correct default settings. The model  
code setting mode should only be used when the  
control board has been changed, the model code  
is incorrect, or to reset all settings to the default.  
For details about the model code setting mode,  
see "III.F. Model Code Setting Mode."  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. Control Board Model Code Setting  
1. Control Board Replacement  
WARNING  
• This appliance should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
• Move the control switch to the "OFF" position and turn off the power supply. Place  
the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply  
from being turned back on inadvertently.  
1) Move the control switch to the "OFF" position and turn off the power supply. Place the  
disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from  
being turned back on inadvertently.  
2) Remove the front cover and control box cover.  
3) Disconnect all the connectors from the control board.  
4) Remove the old control board and install the new control board (P01873-01 Version 1.3A  
or Later).  
5) Connect the connectors to the new control board.  
6) Replace the control box cover in its correct position.  
7) Turn on the power supply, then move the control switch to the "ICE" position.  
8) "00" appears in the display of the new control board.  
9) Press the "SERVICE 1" button to increase the first digit in the display and the  
"SERVICE 2" button to increase the second digit. Digits appear in the following order:  
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F. When a valid model code is displayed, the dot  
in the bottom right of the display turns on. For IM-500SAA, set model code to "08".  
10) When the desired model code is displayed, press the "RESET" button to save the  
setting. "on" appears in the display.  
11) Replace the front panel in its correct position.  
2. Checking or Changing the Control Board Model Code  
1) With unit on, press and hold the "SERVICE 1" button for 3 seconds. Display changes to  
"n1".  
2) Use the "SERVICE 1" and "SERVICE 2" buttons to move through the list until "h6" is  
displayed.  
3) Press the "RESET" button to view the current model code. To change the model code,  
continue through the remaining steps; otherwise, the display returns to normal if no  
buttons are touched for 20 sec.  
4) Press and hold the "SERVICE 1" and "SERVICE 2" buttons simultaneously for 15 sec.  
"00" appears in display.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5) Press the "SERVICE 1" button to increase the first digit in the display and the  
"SERVICE 2" button to increase the second digit. Digits appear in the following order:  
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F. When a valid model code is displayed, the dot  
in the bottom right of the display turns on. For IM-500SAA, set model code to "08".  
6) When the desired model code is displayed, press the "RESET" button to save the  
setting. "on" appears in the display.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G. Error Codes  
When the control board detects an error, the display shows one of the following error  
codes in the display mode. Error codes other than E1 and E2 are displayed as "EE" at  
the time of occurrence. To see the actual error code, see the error log.  
1. With the unit on, press and hold the "SERVICE 1" button for 3 seconds. Display changes  
to "n1".  
2. Use the "SERVICE 1" and "SERVICE 2" buttons to move through the list until "h4" is  
displayed.  
3. Press the "RESET" button to view the error log. Displays up to 5 errors with the most  
recent error first.  
4. Press the "RESET" button to return to list. To clear error log history, press and hold the  
"SERVICE 1" and "SERVICE 2" buttons simultaneously for 5 sec.  
5. Display returns to normal if no buttons are touched for 20 sec.  
Error Codes  
Error Problem  
Code  
Corrective Action/Reset Details  
E1  
E2  
EE  
Freeze Cycle Backup Timer  
Freeze cycle backup timer (Control Board Setting leaking by, pump motor not pumping, thermostatic  
6) has terminated.  
45 min. after water tank starts to close in  
preceding harvest cycle, unit stops if the  
evaporator temperature is above 32°F (0°C).  
Check for inlet water valve leaking by, hot gas valve  
expansion valve not feeding properly, low charge, or  
inefficient compressor.  
Press the "RESET" button to reset.  
Harvest Cycle Backup Timer  
Check for open thermistor, HGV not opening, TXV  
leaking by, low charge, or inefficient compressor.  
Harvest cycle backup timer has terminated.  
30 min. after water tank starts to open in harvest  
cycle, unit stops if harvest cycle termination  
temperature (Control Board Setting 1) has not  
been reached.  
Press the "RESET" button to reset.  
Water Tank Opening Backup Timer  
Check actuator motor and control board.  
Press the "RESET" button to reset.  
(E3) 3-minute opening backup timer starts when water  
tank starts to open.  
If actuator motor's internal position sensor  
does not indicate water tank is fully open within  
3 minutes, display shows "EE" and unit stops for  
60 minutes.  
If error recurs after unit resumes operation,  
display shows "EE" and unit shuts down.  
EE  
Water Tank Closing Backup Timer  
Check actuator motor and control board.  
Press the "RESET" button to reset.  
(E4) 3-minute closing backup timer starts when water  
tank starts to close.  
If actuator motor's internal position sensor does  
not indicate water tank is fully closed within  
3 minutes, display shows "EE" and unit stops for  
60 minutes.  
If error recurs after unit resumes operation,  
display shows "EE" and unit shuts down.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Error Codes  
Error Problem  
Code  
Corrective Action/Reset Details  
EE  
High Evaporator Temperature  
Check for harvest problem (stuck HGV or control  
(E5) If evaporator temperature 140°F (60°C) or higher board relay), hot water entering unit, or shorted  
for 5 sec., unit stops.  
thermistor.  
Press the "RESET" button to reset.  
Replace condenser thermistor.  
EE  
Condenser Thermistor Error  
(E9) If condenser thermistor is open or shorted for  
2 sec., unit stops.  
Note: IM-500SAA does not utilize a condenser  
thermistor, therefore E9 error will not occur.  
EE  
(EA) If model data IC is defective, unit stops.  
EE Evaporator (Cube Control) Thermistor Error  
Control Board Error  
Replace control board.  
Replace evaporator thermistor.  
(EC) If evaporator thermistor is open or shorted for  
2 sec., unit stops.  
EE  
Water Regulating Valve Error  
Check water regulating valve.  
(Ed) If water regulating valve thermistor detects a  
temperature below the water regulating valve  
error detection temperature (Control Board  
Setting 36), error is displayed but unit continues  
to operate.  
Press the "RESET" button to reset.  
Note: IM-500SAA does not utilize a water  
regulating valve, therefore Ed error will not occur.  
H. Quick Adjustments  
1. Dimple Diameter  
The factory set dimple diameter is 3/16" (5 mm). NOTICE! Do not decrease the dimple  
diameter below 3/16" (5 mm).  
a) To increase dimple diameter:  
1) Remove front panel.  
2) Press the "SERVICE 1" button to view the current freeze cycle termination temperature  
setting.  
3) Press the "SERVICE 1" button to raise freeze cycle termination temperature setting  
(Control Board Setting 2). Temperature setting rises in .5°C increments. The "." in the  
lower, right corner of the display indicates .5°C. Default is -18.5°C. For reference, raising  
freeze cycle termination temperature setting to -13°C will result in a dimple diameter of  
approximately 3/8" (10 mm).  
4) Once the display returns to "on" (20 seconds), the new setting is saved.  
b) To decrease dimple diameter:  
1) Remove front panel.  
2) Press the "SERVICE 2" button to view the current freeze cycle termination temperature  
setting.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3) Press the "SERVICE 2" button to lower freeze cycle termination temperature setting  
(Control Board Setting 2). Temperature setting lowers in .5°C increments. The "." in the  
lower, right corner of the display indicates .5°C. Default is -18.5°C. NOTICE! Do not  
decrease dimple size below 3/16" (5 mm).  
4) Once the display returns to "on" (20 seconds), the new setting is saved.  
2. Ice Clarity  
In hard water conditions, white ice may be produced. In such cases, install a water filter  
and/or water softener, then follow the instructions below.  
1) Move the control switch to the "OFF" position, then turn off the power supply.  
2) Remove the front panel.  
3) Remove the screw, then move the water tank drain pipe to the drain position. See Fig. 2.  
Use the screw to secure the water tank drain pipe in the drain position.  
4) Turn on the power supply, then move the control switch to the "ICE" position.  
5) Press and hold the "RESET" button for 3 seconds. "1" appears in the display.  
6) Press the "SERVICE 1" button until "12" appears in the display. Press the "RESET"  
button. The current icemaking water supply time value flashes in the display. Press the  
"SERVICE 1" or "SERVICE 2" buttons to change the setting to "60".  
7) Press the "RESET" button to save the setting and return to the menu.  
8) Using the same procedure as above, change the full/partial drain setting (Control Board  
Setting 14) from "1" (partial drain) to "0" (full drain).  
9) Using the same procedure as above, change the additional icemaking water supply time  
setting (Control Board Setting 15) to "44".  
10) Once the display returns to "on" (20 seconds), the new setting is saved.  
11) Replace the front panel in its correct position.  
Note: If white ice continues to be an issue, set hard water setting water supply time  
(Control Board Setting 61) to "15". This results in the inlet water valve energizing  
for 15 seconds part way through the freeze cycle and diluting the water in the  
water tank. Do not increase this setting beyond 15 seconds; otherwise, freeze  
cycle times may become long and bridging may occur in the ice storage bin.  
Normal Position  
Drain Position  
Screw  
Fig. 2  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. Refrigeration Circuit and Component Service Information  
WARNING  
• This appliance should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
• Move the control switch to the "OFF" position and turn off the power supply. Place  
the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply  
from being turned back on inadvertently.  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after the icemaker is serviced. Make sure that none have fallen  
into the dispenser unit/ice storage bin.  
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are  
clean after service.  
A. Refrigeration Circuit Service Information  
WARNING  
• Repairs requiring the refrigeration circuit to be opened must be performed by  
properly trained and EPA-certified service personnel.  
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with  
pressurized air for leak testing.  
NOTICE  
• Always recover the refrigerant and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
• Do not leave the system open for longer than 15 min. when replacing or servicing  
parts. The Polyol Ester (POE) oils used in R-404A applications can absorb  
moisture quickly. Therefore it is important to prevent moisture from entering the  
system when replacing or servicing parts.  
• Always install a new drier every time the sealed refrigeration system is opened.  
Do not replace the drier until after all other repair or replacement has been made.  
Install the new drier with the arrow on the drier in the direction of the refrigerant  
flow.  
• When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
1. Refrigerant Recovery  
The icemaker is provided with refrigerant access valves. Using proper refrigerant practices,  
recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the  
refrigerant into the atmosphere.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Brazing  
WARNING  
• R-404A itself is not flammable at atmospheric pressure and temperatures up to  
176°F (80°C).  
• R-404A itself is not explosive or poisonous. However, when exposed to high  
temperatures (open flames), R-404A can be decomposed to form hydrofluoric  
acid and carbonyl fluoride both of which are hazardous.  
• Do not use silver alloy or copper alloy containing arsenic.  
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,  
it is important to make connections outside the evaporator case when possible. If  
it is necessary to braze inside the evaporator case, use sandpaper to remove the  
coating from the brazing connections before unbrazing the components.  
NOTICE  
• Always install a new drier every time the sealed refrigeration system is opened.  
• Do not replace the drier until after all other repair or replacement has been made.  
Install the new drier with the arrow on the drier in the direction of the refrigerant  
flow.  
• When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with  
pressurized air for leak testing.  
3. Evacuation and Recharge (R-404A)  
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both  
high and low-side refrigerant access valves.  
IMPORTANT  
The vacuum level and vacuum pump may be the same as those for current  
refrigerants. However, the rubber hose and gauge manifold to be used for  
evacuation and refrigerant charge should be exclusively for POE oils.  
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the  
vacuum pump to flow backwards.  
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends  
on pump capacity.  
4) Close the low-side valve and high-side valve on the gauge manifold.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a  
refrigerant service cylinder. Remember to loosen the connection and purge the air  
from the hose. For the required refrigerant charge, see the nameplate. Hoshizaki  
recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard  
700 (latest edition) be used.  
6) A liquid charge is required when charging an R-404A system (to prevent fractionation).  
Place the service cylinder on the scales; if the service cylinder is not equipped with  
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side  
valve on the gauge manifold.  
7) Allow the system to charge with liquid until the proper charge weight is met.  
8) If necessary, add any remaining charge to the system through the low-side.  
NOTICE! To prevent compressor damage, use a throttling valve or liquid  
dispensing device to add the remaining liquid charge through the low-side  
refrigerant access valve with the icemaker running.  
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold  
hoses.  
10) Cap the refrigerant access valves to prevent a possible leak.  
B. Component Service Information  
NOTICE  
When replacing a component listed below, see the notes to help ensure proper  
operation.  
Component  
Compressor  
Notes  
Install a new start capacitor, run capacitor, and start relay.  
Thermostatic  
Expansion Valve  
• Attach the thermostatic expansion valve bulb to the suction line in the same location  
as the previous bulb.  
• The bulb should be between the 10 and 2 o'clock positions on the tube.  
• Secure the bulb with the clamp and holder, then insulate it.  
• Replace the strainer if applicable.  
Hot Gas Valve  
• Use copper tube of the same diameter and length when replacing valve lines.  
Fan Motor  
Install a new capacitor.  
Install a new capacitor.  
Install a new capacitor.  
Pump Motor  
Actuator Motor  
Evaporator  
(Cube Control)  
Thermistor  
• Attach the new thermistor to the same location on the evaporator as the previous  
thermistor.  
• Smoothly fill the recessed area of the thermistor holder with high thermal conductive  
type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink  
Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured  
by ShinEtsu Silicones), or equivalent are recommended.  
• Attach the new thermistor in position on the evaporator and press down the  
thermistor holder over the thermistor.  
• Be very careful to prevent damage to the leads.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water Pan  
Assembly  
Refer to illustration for assembly.  
1. Water Tank  
2. Water Plate Bracket  
3. Bracket  
4. Spring Hook Screw  
5. Pump Tubing (Suction)  
6. Pump Tubing (Discharge)  
7. Pump Motor Bracket  
8. Water Plate  
9. Overflow Pipe  
10. Screw (for Overflow Pipe)  
11. Nylon Tie  
12. O-ring  
J. Pump Motor Assembly  
S1-4. Tapping Screw  
S5. Machine Screw  
Icemaking  
Assembly and  
Cam Mechanism  
Refer to illustration for assembly.  
G. Water Pan Assembly  
1. Evaporator  
2. Bolt  
3. Collar (Spacer)  
4. Bearing  
5. Actuator Motor  
7. Shaft  
9. Actuator Motor Bracket  
10. Cam Shaft Bearing  
11. Spring Pin  
13. Cam Arm (B)  
14. Cam Shaft  
15. Snap Pin  
16. Split Pin  
17. Spring  
18. Washer (A)  
19. Washer (B)  
20. Washer (C)  
21. Thermistor Holder  
22. Label (for Overflow Pipe)  
23. Thermistor (Cube Control)  
26. Frame  
27. Frame  
28. Wire Saddle  
29. Washer  
30. Cam Arm (A)  
31. Change Lever  
S1-5. Machine Screw  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V. Maintenance  
The maintenance schedule below is a guideline. More frequent maintenance may be  
required depending on water quality, the appliance's environment, and local sanitation  
regulations  
WARNING  
• Only qualified service technicians should service the appliance.  
To reduce the risk of electric shock, do not touch the control switch or service  
switch with damp hands  
• Before servicing: Move the control switch to the "OFF" position and turn off the  
power supply. Place the disconnect in the "OFF" position.  
Lockout/Tagout to prevent the power supply from being turned back on  
inadvertently.  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after any maintenance is done to the icemaker. Make sure that  
none have fallen into the dispenser unit/ice storage bin.  
Maintenance Schedule  
Frequency Area  
Daily Scoop  
Task  
Clean the ice scoop using a neutral cleaner. Rinse thoroughly after  
cleaning.  
Bi-Weekly Air Filters  
Inspect. Wash with warm water and neutral cleaner if dirty.  
Check for proper pressure and change if necessary.  
Monthly  
External Water  
Filters  
Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a  
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining  
(rust colored spots) using a non-abrasive cleanser.  
Yearly  
Icemaker and  
Clean and sanitize per the cleaning and sanitizing instructions provided  
Dispenser Unit/Ice in the instruction manual or maintenance label on the icemaker.  
Storage Bin Liner  
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water  
system. Clean the water supply inlet screen.  
Condenser  
Inspect. Clean if necessary by using a brush or vacuum cleaner. More  
frequent cleaning may be required depending on location.  
Water Hoses  
Inspect the water hoses and clean/replace if necessary.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. Preparing the Icemaker for Periods of Non-Use  
NOTICE  
• When storing the appliance for an extended time or in sub-freezing temperatures,  
follow the instructions below to prevent damage.  
To prevent damage to the water pump, do not operate the appliance with the  
control switch in the "WASH" position when the water tank is empty.  
When the appliance is not used for two or three days under normal conditions, it is  
sufficient to move the control switch to the "OFF" position. When storing the appliance for  
an extended time or in sub-freezing temperatures, follow the instructions below.  
1. Remove the water from the icemaker water supply line:  
1) Turn off the power supply.  
2) Move the control switch to the "OFF" position.  
3) Close the icemaker water supply line shut-off valve and open the icemaker water supply  
line drain valve.  
4) Allow the icemaker water supply line to drain by gravity.  
5) Attach compressed air or carbon dioxide supply to the icemaker water supply line drain  
valve.  
6) Move the control switch to the "ICE" position and turn on the power supply.  
7) Blow the icemaker water supply line out using compressed air or carbon dioxide.  
2. Drain the water tank:  
1) Turn off the power supply.  
2) Remove the front panel.  
3) Remove the screw, and move the tank drain pipe to the drain position.  
4) Close the icemaker water supply line.  
5) Turn on the power supply.  
6) Press the the "RESET" button. The water tank will start to open.  
Note: This procedure is necessary to protect the icemaker from freezing up at  
subfreezing temperatures.  
7) Turn off the power supply when the water tank has fully opened.  
8) Move the tank drain pipe to the normal position, and secure it with the screw.  
9) Replace the front panel.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VII. Disposal  
The appliance contains refrigerant and must be disposed of in accordance with  
applicable national, state, and local codes and regulations. Refrigerant must be  
recovered by properly certified service personnel.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIII.Technical Information  
We reserve the right to make changes in specifications and design without prior notice.  
A. Specification Data  
1. IM-500SAA  
115/60/1  
AC SUPPLY VOLTAGE  
AMPERAGE  
11.5 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
Temp.(°F)  
70  
WATER TEMP. (°F)  
70  
50  
90  
lbs./day ( kg/day )  
Reference without *marks  
*500 (227)  
485 (220)  
481 (218)  
471 (214)  
481 (218)  
456 (207)  
*435 (197)  
426 (193)  
447 (203)  
417 (189)  
397 (180)  
*363 (165)  
80  
90  
100  
Cube Ice  
SHAPE OF ICE  
6.9.lbs. (3.15kg) 140 pcs.  
N/A  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
90/70°F  
990(5.45)  
86(19.8)  
1
70/50°F  
920(4.40)  
105(21.0)  
ENERGY STAR  
YES  
44" x 27.6" x 21.7" (1118 x 700 x 550 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 196 lbs. (89 kg), Shipping 220 lbs. (100 kg)  
Permanent-Connection  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
Inlet  
1/2" FPT  
3/4" FPT  
- DRAIN  
Outlet  
Thermistor and Timer  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
Hot Gas, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Mechanical Level Switch with Delay  
Hermetic, Model NT6222GKV  
Air-Cooled, Fin and tube type  
Cell type, Copper and Tin dipping  
Thermostatic Expansion Valve  
R-404A 1lb, 10.5oz (750g)  
High 350PSIG, Low 220PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
N/A  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin  
104 - 127 V  
45 -100° F  
OPERATING CONDITIONS  
VOLTAGE RANGE  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Performance Data  
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold  
should be used for reference only.  
1. IM-500SAA  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
500  
485  
227  
220  
481  
456  
218  
207  
447  
417  
203  
189  
90/32  
100/38  
481  
471  
218  
214  
435  
426  
197  
193  
397  
363  
180  
165  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
920  
936  
941  
945  
941  
968  
990  
996  
967  
993  
1016  
1040  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
105  
101  
99  
0.40  
0.38  
0.38  
99  
92  
86  
0.38  
0.35  
0.33  
92  
84  
78  
0.35  
0.32  
0.30  
80/27  
90/32  
gal./day m3/day  
100/38  
91  
0.34  
84  
0.32  
71  
0.27  
FREEZING CYCLE TIME  
70/21  
80/27  
17  
18  
18  
20  
20  
23  
90/32  
100/38  
70/21  
18  
19  
22  
23  
24  
27  
min.  
HARVEST CYCLE TIME  
3.6  
3.0  
2.0  
80/27  
90/32  
3.2  
3.0  
2.2  
1.6  
2.0  
1.5  
min.  
100/38  
70/21  
80/27  
90/32  
2.4  
1.6  
1.4  
HEAD PRESSURE  
210  
226  
231  
14.8  
15.9  
16.3  
231  
260  
283  
16.3  
18.2  
19.9  
255  
281  
306  
18.0  
19.7  
21.5  
PSIG kg/cm2G  
100/38  
70/21  
80/27  
90/32  
100/38  
234  
42  
16.5  
3.0  
3.1  
3.1  
3.2  
288  
45  
48  
51  
20.3  
3.1  
3.4  
3.6  
3.6  
327  
48  
52  
55  
58  
23.0  
3.4  
3.6  
3.8  
4.1  
SUCTION PRESSURE  
44  
45  
45  
PSIG kg/cm2G  
52  
TOTAL HEAT OF REJECTION FROM CONDENSER  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
4,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
1,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Wiring Diagram  
1. IM-500SAA  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Stroller ISPS005AA User Manual
Guardian Technologies Portable Generator 05324 User Manual
Hamilton Beach Gas Grill 25285 User Manual
Harbor Freight Tools Air Cleaner 1118 User Manual
Hasbro Motorized Toy Car 08625 User Manual
Havis Shields Window WGI D23 1 6 User Manual
Hoshizaki Ice Maker DCM 270BAH OS User Manual
Hotpoint Refrigerator FF40P User Manual
HP Hewlett Packard Plumbing Product J9020A User Manual
HTC Cell Phone 91H0XXXX XXM User Manual