Hoshizaki Ice Maker KM 1301SAH 3 User Manual

Hoshizaki America, Inc.  
Hoshizaki  
Stackable Crescent Cuber  
Models  
KM-1301SAH/3  
KM-1301SWH/3  
KM-1301SRH/3  
SERVICE MANUAL  
“A Superior Degree  
of Reliability”  
Number: 73169  
Issued:1-21-2009  
Revised: 8-6-2009  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
This manual should be read carefully before the icemaker is serviced or  
maintenance operations are performed. Only qualified service technicians  
should install, service, and maintain the icemaker. Read the warnings  
contained in this booklet carefully as they give important information regarding  
safety. Please retain this booklet for any further reference that may be  
necessary.  
CONTENTS  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Information  
Throughout this manual, notices appear to bring your attention to situations which could  
result in death, serious injury, or damage to the unit.  
WARNING  
Indicates a hazardous situation which could result in death or  
serious injury.  
CAUTION  
IMPORTANT  
Indicates a situation which could result in damage to the unit.  
Indicates important information about the use and care of the  
unit.  
WARNING  
This icemaker should be destined only to the use for which it has been  
expressly conceived. Any other use should be considered improper and  
therefore dangerous. The manufacturer cannot be held responsible for  
eventual damage caused by improper, incorrect, and unreasonable use.  
To reduce the risk of death, electric shock, serious injury, or fire, follow  
basic precautions including the following:  
• Electrical connection must be hard-wired and must meet national, state, and  
local electrical code requirements. Failure to meet these code requirements  
could result in death, electric shock, serious injury, fire, or severe damage to  
equipment.  
• This unit requires an independent power supply. See the nameplate for  
proper voltage and breaker/fuse size. Failure to use a proper breaker or fuse  
can result in a tripped breaker, blown fuse, or damage to existing wiring. This  
could lead to heat generation or fire.  
THIS UNIT MUST BE GROUNDED. Failure to properly ground this unit  
could result in death or serious injury.  
• This unit should be disassembled or repaired only by qualified service  
personnel to reduce the risk of electric shock, injury, or fire.  
• Do not make any alterations to the unit. Alterations could result in electric  
shock, injury, fire, or damage to the unit.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
I. Specifications  
A. Icemaker  
1. KM-1301SAH (air-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/1 (3 wire with neutral for 115V)  
12.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
70  
Temp.(°F)  
50  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1329 (603)  
1292 (586)  
1281 (581)  
1253 (568)  
1281 (581)  
1217 (552)  
*1164 (528)  
1140 (517)  
1188 (539)  
1109 (503)  
1060 (481)  
965 (438)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
29.8 lbs. (13.5 kg) 1440pcs.  
N/A  
90/70°F  
2180(4.5)  
183(15.7)  
3
70/50°F  
2160(3.9)  
605(45.5)  
ENERGY STAR  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 275 lbs. (125 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS14K6E-PFV-237  
Air-Cooled , Fin and tube type  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
R404A, 3 lb. 15.5 oz. (1800g)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin  
OPERATING CONDITIONS  
VOLTAGE RANGE  
AMBIENT TEMP.  
187 - 253 V  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. KM-1301SAH3 (air-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/3  
9.5 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1298 (589)  
1267 (575)  
1257 (570)  
1225 (556)  
1257 (570)  
1204 (546)  
*1159 (526)  
1133 (514)  
1162 (527)  
1086 (493)  
1049 (476)  
947 (430)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
30.4 lbs. (13.8 kg) 1440pcs.  
N/A  
90/70°F  
2220(4.6)  
181(15.6)  
3
70/50°F  
2090(3.9)  
511(39.4)  
ENERGY STAR  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 275 lbs. (125 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS14K6E-TF5-237  
Air-Cooled, Fin and tube type  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
R404A, 3 lb. 15.5 oz. (1800g)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin  
OPERATING CONDITIONS  
VOLTAGE RANGE  
AMBIENT TEMP.  
187 - 253 V  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. KM-1301SWH (water-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/1 (3 wire with neutral for 115V)  
8.2 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1318 (598)  
1319 (598)  
1319 (599)  
1281 (581)  
1319 (599)  
1321 (599)  
*1323 (600)  
1301 (590)  
1249 (567)  
1211 (549)  
1228 (557)  
1141 (518)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
WATER COOLED CONDENSER  
gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
31 lbs. (14.1 kg) 1440pcs.  
N/A  
90/70°F  
1760(3.2)  
257(19.4)  
1561(118)  
70/50°F  
1740(3.2)  
546(41.4)  
861(65)  
3
ENERGY STAR  
N/A  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 265 lbs. (120 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
Cond. Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
Cond. Outlet 3/8" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
Water Regulator  
Thermostat  
Hermetic, Model CS12K6E-PFV-237  
Water-cooled, Tube in tube type  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
R404A, 2 lb. 8.2 oz. (1140g)  
High 427PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin  
OPERATING CONDITIONS  
VOLTAGE RANGE  
AMBIENT TEMP.  
187 - 253 V  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4. KM-1301SWH3 (water-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/3  
6.1 A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1333 (605)  
1326 (601)  
1323 (600)  
1286 (584)  
1323 (600)  
1311 (594)  
*1300 (590)  
1277 (579)  
1246 (565)  
1198 (544)  
1201 (545)  
1110 (503)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
WATER COOLED CONDENSER  
gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
32.2 lbs. (14.6 kg) 1440pcs.  
N/A  
90/70°F  
1840(3.4)  
248(19.1)  
1547(119)  
70/50°F  
1770(3.2)  
557(41.8)  
857(64)  
3
ENERGY STAR  
N/A  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 265 lbs. (120 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
Cond. Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
Cond. Outlet 3/8" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
Water Regulator  
Thermostat  
Hermetic, Model CS12K6E-TF5-237  
Water-cooled, Tube in tube type  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
R404A, 2 lb. 8.2 oz. (1140g)  
High 427PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin  
OPERATING CONDITIONS  
VOLTAGE RANGE  
AMBIENT TEMP.  
187 - 253 V  
45 -100° F  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45 - 90° F  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5. KM-1301SRH (remote air-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/1 (3 wire with neutral for 115V)  
13.5A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
20 A  
20 A  
APPROXIMATE ICE PRODUCTION  
Ambient  
WATER TEMP. (°F)  
PER 24 HR.  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1353 (614)  
1324 (600)  
1315 (596)  
1281 (581)  
1315 (596)  
1264 (573)  
*1222 (554)  
1196 (542)  
1219 (553)  
1144 (519)  
1110 (504)  
1008 (457)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
ENERGY STAR  
31.1 lbs. (14.1 kg) 1440pcs.  
N/A  
90/70°F  
2090(4.1)  
203(16.6)  
3
70/50°F  
2010(3.6)  
479(35.4)  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 255 lbs. (116 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS12K6E-PFV-279  
Air-Cooled Remote, Condenser Unit URC-14F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-14F  
R404A, 10 lbs. 5.8 oz. (4700g)  
(Icemaker 5 lbs. 15.2 oz. Cond. Unit 4 lbs. 6.5 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin, Remote Condenser Unit  
VOLTAGE RANGE  
OPERATING CONDITIONS  
187 - 253 V  
45 -100° F  
45 - 90° F  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6. KM-1301SRH3 (remote air-cooled)  
AC SUPPLY VOLTAGE  
AMPERAGE  
208-230/60/3  
10.7A ( 5 Min. Freeze AT 104°F / WT 80°F)  
MINIMUM CIRCUIT AMPACITY  
MAXIMUM FUSE SIZE  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
Ambient  
WATER TEMP. (°F)  
Temp.(°F)  
50  
70  
90  
lbs./day ( kg/day )  
Reference without *marks  
70  
80  
90  
100  
*1339 (607)  
1307 (593)  
1297 (589)  
1266 (574)  
1297 (589)  
1243 (564)  
*1197 (543)  
1171 (531)  
1203 (546)  
1127 (511)  
1088 (494)  
988 (448)  
SHAPE OF ICE  
Crescent Cube  
ICE PRODUCTION PER CYCLE  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
WATER gal./24HR (gal./100 lbs.)  
CEC/CEE TIER LEVEL  
ENERGY STAR  
30.7 lbs. (13.9 kg) 1440pcs.  
N/A  
90/70°F  
2140(4.3)  
192(16.0)  
3
70/50°F  
2090(3.8)  
463(34.6)  
YES  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
48" x 27-3/8" x 27-3/8" (1219 x 695 x 695 mm)  
Stainless Steel, Galvanized Steel (Rear)  
Net 255 lbs. (116 kg), Shipping 315 lbs. (143 kg)  
Permanent - Connection  
Inlet  
1/2" FPT  
- DRAIN  
Outlet  
3/4" FPT  
- CONDENSATE DRAIN  
CUBE CONTROL SYSTEM  
HARVESTING CONTROL SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
3/8" OD Tube  
Float Switch  
Hot Gas and Water, Thermistor and Timer  
Timer Controlled. Overflow Pipe  
N/A  
Thermostat  
Hermetic, Model CS12K6E-TF5-279  
Air-Cooled Remote, Condenser Unit URC-14F  
Vertical type, Stainless Steel and Copper  
Thermostatic Expansion Valve  
Condensing Pressure Regulator on URC-14F  
R404A, 10 lbs. 5.8 oz. (4700g)  
(Icemaker 5 lbs. 15.2 oz. Cond. Unit 4 lbs. 6.5 oz.)  
High 467PSIG, Low 230PSIG  
High Voltage Cut-out ( Internal )  
Auto-reset Overload Protector ( Internal )  
Auto-reset High Pressure Control Switch  
Float Switch  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES -SUPPLIED  
-REQUIRED  
N/A  
Ice Storage Bin, Remote Condenser Unit  
VOLTAGE RANGE  
OPERATING CONDITIONS  
187 - 253 V  
45 -100° F  
45 - 90° F  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
10 - 113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
1ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
B. Condenser Unit  
1. URC-14F  
Unit: inches (mm)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPECIFICATIONS  
MODEL: URC-14F  
AC SUPPLY VOLTAGE  
FAN MOTOR  
115/60/1 (Connection to Icemaker)  
115 V Total 2.6FLA  
130W  
EXTERIOR DIMENSIONS (WxDxH)  
DIMENSIONS INCLUDING LEGS (WxDxH)  
EXTERIOR FINISH  
35-11/16" x 15-11/16" x 21-15/16" (907.2 x 398 x 557.8 mm)  
37-13/16" x 18-1/8" x 36-15/16" (960 x 460 x 937.8 mm)  
Galvanized Steel  
WEIGHT  
Net 80 lbs. ( 36 kg )  
Shipping 87 lbs. ( 39 kg )  
CONNECTIONS - ELECTRIC  
- REFRIGERANT  
Permanent - Connection  
Discharge Line 1-1/16"-12 UNF Fitting (#10 AEROQUIP)  
Liquid Line 5/8"-18 UNF Fitting (#6 AEROQUIP)  
CONDENSER  
Air-cooled, Fin and tube type  
Thermal Protection  
FAN MOTOR PROTECTION  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
Condensing Pressure Regulator  
R-404A  
4 lb. 7 oz.  
(2000g)  
High 467 PSIG  
VOLTAGE RANGE  
AMBIENT TEMP.  
Leg  
OPERATING CONDITIONS  
104 ~ 127 V  
-20 ~ 122 °F  
ACCESSORIES -SUPPLIED  
2 pcs  
8 pcs  
8 pcs  
Hex. Head Bolt w/Washer 8 x 16  
Hex. Nut  
8
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. General Information  
A. Construction  
1. KM-1301SAH, KM-1301SAH3 (air-cooled)  
Spray Tubes  
Low-Side Service Valve  
High-Side Service Valve  
Inlet Water Valve  
Evaporator Assembly  
Expansion Valves  
Water Supply Inlet  
Junction Box  
Hot Gas Valve  
Check Valves  
Cleaning Valve  
Air-Cooled  
Condenser  
Control Box  
Fan Blade  
Check Valve  
(water)  
Water Pump  
Fan Motor  
Float Switch  
Compressor  
Drier  
Liquid Line Valve  
Bin Control Thermostat  
Transformer Box  
(KM-1301SAH3)  
Control Switch  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. KM-1301SWH, KM-1301SWH3 (water-cooled)  
Spray Tubes  
Low-Side Service Valve  
Inlet Water Valve  
Evaporator Assembly  
High-Side Service Valve  
Expansion Valves  
Water Supply Inlet  
Junction Box  
Hot Gas Valve  
Check Valves  
Water-Cooled  
Condenser  
Cleaning Valve  
Check Valve  
(water)  
Water Pump  
Water Regulating  
Valve  
Float Switch  
Compressor  
Bin Control Thermostat  
Drier  
Control Box  
Liquid Line Valve  
Control Switch  
Transformer Box  
(KM-1301SWH3)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. KM-1301SRH, KM-1301SRH3 (remote air-cooled)  
Low-Side Service Valve  
Spray Tubes  
Inlet Water Valve  
High-Side Service Valve  
High-Side Liquid Service Valve  
Evaporator Assembly  
Water Supply Inlet  
Hot Gas Valve  
Junction Boxes  
Check Valves  
Cleaning Valve  
Expansion Valves  
Receiver Tank  
Check Valve  
(water)  
Water Pump  
Float Switch  
Compressor  
Control Box  
Access Valve  
Bin Control Thermostat  
Control Switch  
Drier  
Transformer Box  
(KM-1301SRH3)  
Liquid Line Valve  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
B. Sequence of Operation  
IMPORTANT  
This unit utilizes a thermostatic bin control. For operation, the K4 jumper  
(4A4883G01) must be in place on the control board RED K4 connector.  
1. Sequence Cycles and Shutdown  
The steps in the sequence are as outlined below. When power is supplied, CB red  
"POWER OK" LED and green "BC CLOSED" LED come on. The green "BC CLOSED"  
LED is on continuously when the K4 jumper is in place. If CB yellow "BC OPEN" LED is  
on, check that CB has the K4 jumper in place on CB RED K4 connector. This unit will not  
operate unless the K4 jumper is in place. There is a 5-second delay before startup. Note  
that the order of the component LEDs from the outer edge of CB is 1, 4, 3, ꢀ.  
a) 1-Minute Fill Cycle  
LED 4 is on. WV and Xꢀ relay (auxiliary code T-0 and U-0), X11 relay (auxiliary code  
U-1 and later) energize and the 1-minute fill cycle begins. After 1 minute, CB checks for  
a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV remains energized  
through additional 1-minute fill cycles until water fills the tank and closes F/S. This  
serves as a low water safety to protect PM.  
b) Initial Harvest Cycle  
LEDs 1, 4, and ꢀ are on. WV and Xꢀ relay (auxiliary code T-0, U-0), X11 relay (auxiliary  
code U-1 and later) remain energized, HGV, X1 relay (auxiliary code T-0, U-0),  
X10 relay (auxiliary code U-1 and later), Comp, and FMR energize. CB monitors the  
warming of the evaporator via the thermistor located on the suction line. When the  
thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal from the thermistor and turns  
harvest termination over to the harvest timer (S4 dip switch 1 & ꢀ). The harvest timer  
has settings of 60, 90, 1ꢀ0, and 180 seconds. For details, see "II.C.3.b) Harvest Timer  
(S4 dip switch 1 & ꢀ)." WV is energized during harvest for a maximum of 6 minutes or  
the length of harvest minus 0 or 50 seconds (harvest pump timer (S4 dip switch 7)),  
whichever is shorter. CAUTION! Do not adjust S4 dip switch 7 out of the factory  
default position on this model. Adjustment outside of the factory default position  
may result in damage to the icemaker. For details, see "II.C.3.e) Harvest Pump Timer  
(S4 dip switch 7)." LED 4 goes off when WV and Xꢀ relay (auxiliary code T-0, U-0),  
X11 relay (auxiliary code U-1 and later) de-energize. LED 3 comes on and PM energizes  
and runs for the last 0 or 50 seconds of harvest depending on S4 dip switch 7 setting.  
This circulates water over the evaporator for the last 0 or 50 seconds of harvest. PM  
is energized through the #5 pin (DBu wire) on the CB K1 ten-pin connector and the  
X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later). When the  
harvest timer expires, the harvest cycle is complete. CB checks the position of F/S and  
proceeds to the freeze cycle if it is closed or calls for a 1-minute fill cycle if it is open. The  
minimum total time allowed by CB for a complete harvest cycle is ꢀ minutes.  
c) Freeze Cycle  
LED 1 is on. Comp and FMR remain energized, PM energizes or remains energized  
depending on harvest pump timer (S4 dip switch 7) setting. FM and LLV energize.  
HGV and X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
de-energize. For the first 5 minutes, CB will not accept a signal from F/S. This minimum  
5-minute freeze time is short cycle protection for Comp. At the end of 5 minutes, F/S  
assumes control. As ice builds on the evaporator, the water level in the tank lowers. The  
freeze cycle continues until F/S opens and terminates the cycle. There is a 15 second  
delay before CB acknowledges an open F/S.  
d) Pump-Out Cycle  
LEDs 1, 3, and ꢀ are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on.  
CAUTION! Do not adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this  
position on this model prevents the unit from operating correctly and may cause  
damage. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." Comp and  
FMR remain energized, HGV energizes, WV energizes if S4 dip switch 3 off and 4 on.  
LLV and FM de-energize. PM stops for ꢀ seconds then reverses, taking water from the  
bottom of the tank and forcing pressure against the check valve seat allowing water to  
go through the check valve and down the drain. At the same time, water flows through  
the small tube to power flush F/S. When the pump-out timer expires, the pump-out is  
complete.  
The first pump-out occurs after the 11th freeze cycle, then every 10th cycle thereafter.  
The pump-out frequency control is factory set, and generally no adjustment is required.  
However, where water quality is bad and the icemaker needs a pump-out more often, the  
pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 &  
6) can be set to have a pump-out occur every cycle, or every ꢀ, 5, or 10 cycles. Timing of  
the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below. For  
details, see "II.C.3.d) Pump-Out Frequency Control (S4 dip switch 5 & 6)."  
S4 Dip Switch Setting  
Pump-Out  
Frequency  
1st Pump-Out  
No. 5  
OFF  
ON  
No. 6  
OFF  
OFF  
ON  
Every cycle  
Every ꢀ cycles  
Every 5 cycles  
Every 10 cycles  
After ꢀnd freeze cycle  
After 3rd freeze cycle  
After 6th freeze cycle  
After 11th freeze cycle  
OFF  
ON  
ON  
e) Harvest Cycle  
Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."  
Note: Unit continues to cycle until BC is satisfied or power is turned off. The unit always  
restarts at the 1-minute fill cycle.  
f) Shutdown  
When ice contacts the thermostatic bulb (BC switch open), BC shuts down the unit within  
10 seconds. The bin control is factory set, and generally no adjustment is required.  
However, adjustment may be needed in some conditions, particularly at higher altitude  
locations.  
Legend: BC–bin control; CB–control board; Comp–compressor; FMR–fan motor-remote;  
FM–fan motor; F/S–float switch; HGV–hot gas valve; LLV–liquid line valve;  
PM–pump motor; WV–inlet water valve  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. Sequence Flow Chart  
ꢀ0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
C. Control Board  
• A Hoshizaki exclusive solid-state control board is employed in KM-1301SAH/3,  
KM-1301SWH/3, and KM-1301SRH/3, Stackable Crescent Cubers.  
• All models are pretested and factory set.  
CAUTION  
1. The control board is fragile; handle very carefully.  
ꢀ. The control board contains integrated circuits, which are susceptible to  
failure due to static discharge. It is especially important to touch the metal  
part of the unit before handling or replacing the control board.  
3. Do not touch the electronic devices on the control board or the back of the  
control board.  
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,  
because the same connector is used for the thermistor, K4 jumper, and float  
switch. The control board RED K4 connector must have the K4 jumper in  
place for proper operation.  
5. Always replace the whole control board assembly if it goes bad.  
6. Do not short out power supply to test for voltage.  
ꢀ1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Control Board Layout  
"G" Control Board  
Bin Control Switch  
Closed LED (green)  
(on continuously  
S4 Dip  
Switch  
"OUTPUT TEST" Button  
(used to test relays on control board)  
"ALARM RESET" Button  
in thermostatic bin  
control application)  
WHITE K3 Connector  
Harvest Control  
(thermistor)  
Bin Control Switch  
Open LED (yellow)  
(mechanical bin control  
application only)  
RED K4 Connector  
K4 Jumper (4A4883G01  
thermostatic bin control  
application) or Mechanical  
Bin Control  
Part Number  
Alarm Buzzer  
S5 Dip Switch  
Power LED (red)  
(lights when  
power is supplied to  
the control board)  
BLACK K5 Connector  
Float Switch  
Label  
(control board revision  
level indicated on label  
on side of relay)  
Relay LEDs (4)  
(indicate which  
relays are energized  
as listed below)  
K1 Ten-Pin Connector  
Pins #1 through #10  
#1, 9 Magnetic Contactor  
#ꢀ Hot Gas Valve (HGV)  
#3 Liquid Line Valve (LLV),  
Fan Motor (FM)  
LED ꢀ (Xꢀ Relay)  
Hot Gas Valve (HGV)  
Fan Motor (FM)  
(FM off when LED on)  
#4 Pump Motor (icemaking)  
#5 Pump Motor (pump-out,  
harvest (if applicable))  
#6 Inlet Water Valve (WV)  
#7, 10 Component Power  
Supply  
LED 3 (X3 Relay)  
Pump Motor (PM)  
(on at pump-out,  
harvest (if applicable))  
LED 4 (X4 Relay)  
Inlet Water Valve (WV)  
#8 Open  
Switch for "C" control board  
and "ALPINE" control board  
(service control board only)  
LED 1 (X1 Relay)  
Compressor (Comp),  
Fan Motor-Remote  
(FMR)  
Kꢀ Connector  
Transformer  
Control Board  
Part Number ꢀA379ꢀ-01  
ꢀꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. Features  
a) Maximum Water Supply Period - 6 minutes  
The inlet water valve will be open during harvest for 6 minutes or the length of harvest  
minus 0 or 50 seconds (harvest pump timer (S4 dip switch 7)), whichever is shorter. For  
details, see "II.C.3.e) Harvest Pump Timer (S4 dip switch 7)."  
b) Harvest Backup Timer and Freeze Timer  
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest  
cycle takes more than ꢀ0 minutes to complete. The control board will signal this problem  
using ꢀ beeps every 3 seconds.  
The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle  
takes longer than the time specified to complete. The control board will signal this  
problem using 3 beeps every 3 seconds. The freeze timer is factory set using S4 dip  
switch 9 & 10. For details, see "II.C.3.g) Freeze Timer (S4 dip switch 9 & 10).  
The "ALARM RESET" button on the control board must be pressed with power on to  
reset either of these safeties.  
c) High Temperature Safety  
The temperature of the suction line in the refrigeration circuit is limited by the high  
temperature safety. This protects the unit from excessively high temperatures. If the  
evaporator temperature reaches 1ꢀ7°F±7°F (53°C±4°C), the control board reads a .8 kΩ  
signal from the thermistor and shuts down the icemaker.  
The control board will signal this problem using 1 beep every 3 seconds. The "ALARM  
RESET" button on the control board must be pressed with power on to reset the safety.  
d) Low Water Safety  
The control board checks the position of the float switch at the end of the initial 1-minute  
fill cycle and at the end of each harvest cycle. If the float switch is in the up position  
(electrical circuit closed), the control board changes to the next cycle. If the float switch  
is in the down position (electrical circuit open), the control board changes to additional  
1-minute fill cycles until water enters the tank and closes the float switch. When the float  
switch closes, the control board changes to the next cycle. The unit will not start without  
adequate water in the tank. This serves as a low water safety to protect the water pump.  
For water-cooled model, if the condenser water supply is shut off, the unit is protected by  
the high-pressure switch.  
e) High Voltage and Low Voltage Cut-outs  
The maximum and minimum allowable supply voltages of this icemaker are limited by  
the high voltage and low voltage cut-outs. If miswiring (especially on single phase 3 wire  
models) causes excessive voltage (147Vac±5% or more), the high voltage cut-out shuts  
down the circuit in 3 seconds and the icemaker automatically stops. The control board  
will signal this problem using 7 beeps every 3 seconds.  
The icemaker also automatically stops in cases of insufficient voltage (9ꢀVac±5% or  
less). The control board will signal this problem using 6 beeps every 3 seconds.  
When the proper supply voltage is resumed, the icemaker automatically starts running  
again.  
ꢀ3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
f) LED Lights and Audible Alarm Safeties  
At startup, a 5-second delay occurs while the control board conducts an internal timer  
check. A beep occurs when the control switch is moved to the "ICE" position.  
The red LED indicates proper control voltage and will remain on unless a control voltage  
problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup  
as listed in the table below. Note that the order of the LEDs from the outer edge of the  
control board is 1, 4, 3, ꢀ. For details, see "II.B. Sequence of Operation."  
Time LEDs are On  
Max.  
Energized  
Components  
Sequence Step  
LED  
Min.  
Avg.  
1-Minute Fill Cycle  
Harvest Cycle  
4
WV  
1 minute  
ꢀ0 minutes 3 to 5 minutes  
1, 4, ꢀ  
Comp, FMR, WV,  
HGV  
Comp, FMR, PM,  
HGV  
Comp, FM/FMR,  
PM, LLV  
ꢀ minutes  
0 seconds  
5 minutes  
Harvest Pump Timer 1, 3, ꢀ  
50 seconds harvest pump timer  
setting  
freeze timer 30 to 35 minutes  
setting  
Freeze Cycle  
1
Pump-Out Cycle  
1, 4*, 3, ꢀ Comp, FMR, WV*, 10 seconds ꢀ0 seconds *pump-out timer  
PM, HGV setting  
The built-in safeties shut down the unit and have alarms as listed below.  
No. of Beeps  
(every 3 sec.)  
Type of Alarm  
Notes  
1
High Evaporator Temp.  
(temperature > 1ꢀ7°F)  
(53°C)  
Check for harvest problem (stuck HGV or relay), hot  
water entering unit, stuck HM, or shorted thermistor.  
3
Harvest Backup Timer  
(harvest > ꢀ0 min. for two cycles LLV leaking by, low charge, or inefficient Comp.  
in a row)  
Check for open thermistor, HGV not opening, TXV or  
Freeze Timer  
(freeze > specified setting for  
two cycles in a row)  
Check for F/S stuck closed (up), WV leaking by, HGV  
leaking by, PM not pumping, TXV not feeding properly,  
LLV not opening, low charge, HM not bypassing, or  
Timer is factory set using S4 dip inefficient Comp.  
switch 9 & 10  
To reset the above safeties, press the "ALARM RESET" button with the power supply on.  
6
Low Voltage  
(9ꢀVac±5% or less)  
Red LED will turn off if voltage protection operates.  
The control voltage safeties automatically reset when  
voltage is corrected.  
7
High Voltage  
(147Vac±5% or more)  
Legend: Comp–compressor; FM–fan motor; FMR–fan motor-remote; F/S–float switch;  
HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump  
motor; TXV–thermostatic expansion valve; WV–inlet water valve  
ꢀ4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Controls and Adjustments  
CAUTION  
Dip switches are factory set. Failure to maintain factory settings may adversely  
affect performance and warranty coverage. For more information, contact  
Hoshizaki Technical Support at 1-800-ꢀ33-1940.  
a) Default Dip Switch Settings  
The dip switches are factory set to the following positions:  
S4 Dip Switch  
S4 Dip Switch No.  
KM-1301SAH/3  
KM-1301SWH/3  
KM-1301SRH/3  
1
2
3
4
5
6
7
8
9
10  
OFF OFF ON ON ON ON ON OFF OFF OFF  
OFF OFF ON ON ON ON ON OFF OFF OFF  
OFF OFF ON ON ON ON ON OFF ON OFF  
S5 Dip Switch (Do Not Adjust)  
1
2
3
4
5
S5 Dip Switch No.  
KM-1301SAH/3  
OFF OFF OFF OFF OFF  
KM-1301SWH/3 OFF OFF OFF OFF OFF  
KM-1301SRH/3 OFF OFF OFF OFF OFF  
Freeze Timer (9 & 10)  
Factory Use (8)  
Harvest Pump Timer (7)  
(Do not adjust)  
Pump-Out Frequency Control (5 & 6)  
Pump-Out Timer (3 & 4)  
(Do not adjust to 3 off and 4 on)  
Harvest Timer (1 & ꢀ)  
b) Harvest Timer (S4 dip switch 1 & 2)  
The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet  
and the control board reads the thermistor's 3.9 KΩ signal. The harvest timer is factory  
set, and generally no adjustment is required. However, a setting longer than the factory  
setting may be advised in cases where the flush provided at harvest needs to be  
prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical  
Support at 1-800-ꢀ33-1940 for recommendations. Keep in mind that setting the harvest  
timer to a longer setting decreases ꢀ4-hour production.  
S4 Dip Switch Setting  
Time  
(seconds)  
No. 1  
OFF  
ON  
No. 2  
OFF  
OFF  
ON  
60  
90  
OFF  
ON  
1ꢀ0  
180  
ON  
ꢀ5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
c) Pump-Out Timer (S4 dip switch 3 & 4)  
CAUTION  
Do not adjust S4 dip switch 3 off and S4 dip switch 4 on for this model.  
Otherwise, pump motor does not rotate in the pump-out direction.  
When a pump-out is called for, the pump motor stops after the preceding freeze cycle.  
The pump motor restarts ꢀ seconds later in the reverse direction, taking water from the  
bottom of the tank and forcing pressure against the check valve seat allowing water to  
go through the check valve and down the drain. At the same time, water flows through  
the small tube to power flush the float switch. The pump motor drains the water tank  
for the time determined by the pump-out timer. The pump-out timer also acts in place  
of the harvest timer during cycles with a pump-out. The pump-out timer is factory set,  
and generally no adjustment is required. However, where water quality is bad and the  
icemaker needs a longer pump-out time, the pump-out timer can be adjusted. The  
pump-out timer control can be set to pump-out for 10 or ꢀ0 seconds.  
Inlet  
Water  
S4 Dip Switch Setting Time (seconds)  
T1  
10  
10  
10  
ꢀ0  
Valve  
closed  
closed  
open  
No. 3  
OFF  
ON  
No. 4  
OFF  
OFF  
ON  
T2  
150  
180  
1ꢀ0  
180  
OFF  
ON  
ON  
closed  
T1: Time to drain the water tank  
Tꢀ: Harvest timer at pump-out  
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)  
The pump-out frequency control is factory set to drain the water tank every 10 cycles,  
and generally no adjustment is required. However, where water quality is bad and the  
icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The  
pump-out frequency control can be set to have a pump-out occur every cycle, or every  
ꢀ, 5, or 10 cycles.  
Timing of the first pump-out is dependent on S4 dip switch 5 & 6 settings. The first  
pump-out is factory set to occur after the 11th freeze cycle. See the table below.  
S4 Dip Switch Setting  
Pump-Out  
Frequency  
1st Pump-Out  
No. 5  
OFF  
ON  
No. 6  
OFF  
OFF  
ON  
Every cycle  
Every ꢀ cycles  
Every 5 cycles  
Every 10 cycles  
After ꢀnd freeze cycle  
After 3rd freeze cycle  
After 6th freeze cycle  
After 11th freeze cycle  
OFF  
ON  
ON  
ꢀ6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
e) Harvest Pump Timer (S4 dip switch 7)  
CAUTION  
Factory set for proper operation. Do not adjust. Adjustment outside of the  
factory default setting may result in damage to the icemaker.  
Depending on the harvest pump timer setting, the pump motor energizes and runs  
the last 0 or 50 seconds of harvest. When the pump is on, water circulates over the  
evaporator. The water valve is open during harvest for a maximum of 6 minutes or the  
length of harvest minus 0 or 50 seconds (determined by the harvest pump timer setting),  
whichever is shorter.  
When S4 dip switch 7 is on, the pump motor is energized through the #5 pin (DBu wire)  
on the control board K1 ten-pin connector and the X1 relay (auxiliary code T-0, U-0), X10  
relay (auxiliary code U-1 and later). The #5 pin (DBu wire) is used in most applications  
to reverse the pump motor or energize the drain valve in pump-out cycles. In this  
application, it is used for the pump-out cycle (reverse rotation) as well as the harvest  
pump timer (freeze rotation). Therefore, the harvest pump timer relays are needed to  
control the pump motor direction during the pump-out and harvest cycles. See "III.B.  
Wiring Diagrams."  
S4 Dip Switch Setting  
Pump Motor  
Time (seconds)  
No. 7  
ON  
50  
0
OFF  
f) Factory Use (S4 dip switch 8)  
Factory set for proper operation. Do not adjust. This must be left in the factory default  
position.  
g) Freeze Timer (S4 dip switch 9 & 10)  
CAUTION  
Adjust to proper specification, or the unit may not operate correctly.  
The freeze timer setting determines the maximum allowed freeze time to prevent  
possible freeze-up issues. Upon termination of the freeze timer, the control board  
initiates the harvest cycle. After ꢀ consecutive freeze timer terminations, the control  
board shuts down the icemaker. In this case, see "IV.F.3. Low Ice Production" for  
possible solutions. The freeze timer is factory set, and generally no adjustment  
is required. Before changing this setting, contact Hoshizaki Technical Support at  
1-800-ꢀ33-1940 for recommendations.  
Time  
S4 Dip Switch Setting  
(minutes)  
No. 9  
OFF  
OFF  
ON  
No. 10  
OFF  
ON  
60  
50  
70  
60  
OFF  
ON  
ON  
ꢀ7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
h) Float Switch Control (S5 dip switch 1)  
CAUTION  
Do not adjust. This must be left in the factory default position or the unit will not  
operate correctly.  
Factory set. S5 dip switch 1 allows for single or double float switch applications. The  
KM-1301SAH/3, KM1301SWH/3, and KM-1301SRH/3 use a single float switch.  
i) Refill Counter (S5 dip switch 2 through 5)  
CAUTION  
Do not adjust. These must be left in the factory default position or the unit will  
not operate correctly.  
Factory set. S5 dip switch ꢀ through 5 allows for refills during the freeze cycle.  
The KM-1301SAH/3, KM1301SWH/3, and KM-1301SRH/3 do not refill.  
ꢀ8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
D. Bin Control  
CAUTION  
When the ambient temperature is below 45°F (7°C), the thermostatic bin  
control switch opens and shuts down the icemaker even if the ice storage bin  
is empty. When the thermostat is set in the prohibited range, the icemaker  
operates continuously even if the ice storage bin is filled with ice. Setting in the  
prohibited range may result in severe damage to the icemaker.  
The thermostatic bin control switch is a temperature controlled switch used to control  
the level of ice in the bin. It is in line with the power supply to the control switch.  
The thermostatic bin control switch shuts down the unit within 10 seconds when ice  
contacts the thermostatic bulb, regardless of the cycle at activation. The bin control  
is factory set, and generally no adjustment is required. However, adjustment may be  
needed in some conditions, particularly at higher altitude locations. For further details,  
see "IV.C. Bin Control Check."  
E. Float Switch  
The float switch is used to determine that there is sufficient water in the tank after the  
1-minute fill cycle and after each harvest cycle. The float switch is also used to determine  
that the appropriate volume of water has been converted into ice before switching out of  
the freeze cycle. No adjustment is required.  
F. Thermistor  
The thermistor is used as a harvest control sensor. The thermistor's resistance varies  
depending on the suction line temperature. The control board monitors the resistance to  
start the harvest timer. No adjustment is required.  
G. Control Switch  
The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and  
"WASH" to activate the water pump when cleaning and sanitizing.  
ꢀ9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
III. Technical Information  
A. Water Circuit and Refrigeration Circuit  
1. KM-1301SAH, KM-1301SAH3 (air-cooled)  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. KM-1301SWH, KM-1301SWH3 (water-cooled)  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. KM-1301SRH, KM-1301SRH3 (remote air-cooled)  
3ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
B. Wiring Diagrams  
1. Auxiliary Code T-0, U-0  
a) KM-1301SAH (air-cooled)  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
b) KM-1301SWH (water-cooled)  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
c) KM-1301SRH (remote air-cooled)  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
d) KM-1301SAH3 (air-cooled) and KM-1301SWH3 (water-cooled)  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
e) KM-1301SRH3 (remote air-cooled)  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. Auxiliary Code U-1 and Later  
a) KM-1301SAH (air-cooled)  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
b) KM-1301SWH (water-cooled)  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
c) KM-1301SRH (remote air-cooled)  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
d) KM-1301SAH3 (air-cooled) and KM-1301SWH3 (water-cooled)  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
e) KM-1301SRH3 (remote air-cooled)  
4ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
C. Performance Data  
1. KM-1301SAH (air-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
70/21  
80/27  
90/32  
100/38  
70/21  
80/27  
90/32  
50/10  
90/32  
1329  
1292  
1281  
1253  
603  
586  
581  
568  
1281  
1217  
1164  
1140  
581  
552  
528  
517  
1188  
1109  
1060  
965  
539  
503  
481  
438  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
2160  
2164  
2166  
2193  
2166  
2174  
2180  
2197  
2222  
2257  
2253  
2320  
watts  
100/38  
70/21  
80/27  
90/32  
100/38  
70/21  
80/27  
90/32  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
605  
510  
481  
345  
2.29  
1.93  
1.82  
1.30  
481  
318  
183  
179  
1.82  
1.21  
0.69  
0.68  
429  
331  
167  
152  
1.62  
1.25  
0.63  
0.58  
gal./day m3/day  
FREEZING CYCLE TIME  
31  
32  
32  
33  
4.7  
32  
34  
35  
36  
3.9  
35  
37  
38  
41  
3.7  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
100/38  
4.1  
3.9  
3.1  
2.9  
2.1  
2.1  
3.1  
2.1  
2.1  
min.  
HEAD PRESSURE  
70/21  
80/27  
90/32  
255  
269  
273  
17.9  
18.9  
19.2  
273  
297  
317  
19.2  
20.9  
22.3  
298  
321  
342  
20.9  
22.6  
24.0  
PSIG kg/cm2G  
100/38  
278  
19.5  
323  
22.7  
365  
25.7  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
50  
50  
50  
3.5  
3.5  
3.5  
50  
50  
50  
3.5  
3.5  
3.5  
53  
55  
55  
3.8  
3.9  
3.8  
PSIG kg/cm2G  
100/38  
52  
3.6  
51  
3.6  
59  
4.1  
TOTAL HEAT OF REJECTION FROM CONDENSER  
20,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. KM-1301SAH3 (air-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
70/21  
80/27  
50/10  
90/32  
1298  
589  
575  
1257  
1204  
570  
546  
1162  
1086  
527  
493  
1267  
90/32  
100/38  
70/21  
80/27  
90/32  
1257  
1225  
570  
556  
1159  
526  
514  
1049  
947  
476  
430  
lbs./day kg./day  
1133  
APPROXIMATE ELECTRIC  
CONSUMPTION  
2090  
2119  
2128  
2123  
2128  
2178  
2220  
2224  
2152  
2187  
2236  
2250  
watts  
100/38  
70/21  
80/27  
90/32  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
511  
438  
415  
305  
1.94  
1.66  
1.57  
1.15  
415  
287  
181  
176  
1.57  
1.09  
0.68  
0.67  
367  
286  
159  
139  
1.39  
1.08  
0.60  
0.53  
gal./day m3/day  
100/38  
70/21  
80/27  
90/32  
100/38  
70/21  
FREEZING CYCLE TIME  
32  
33  
33  
34  
4.2  
33  
35  
36  
37  
3.6  
36  
39  
40  
43  
3.4  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
100/38  
3.8  
3.6  
2.9  
2.8  
2.1  
2.1  
2.9  
2.1  
2.1  
min.  
HEAD PRESSURE  
70/21  
80/27  
90/32  
254  
268  
272  
17.9  
18.8  
19.1  
272  
295  
315  
19.1  
20.8  
22.1  
296  
319  
339  
20.8  
22.4  
23.8  
PSIG kg/cm2G  
100/38  
276  
19.4  
321  
22.5  
361  
25.4  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
48  
49  
49  
3.4  
3.4  
3.4  
49  
50  
51  
3.4  
3.5  
3.6  
52  
54  
55  
3.6  
3.8  
3.8  
PSIG kg/cm2G  
100/38  
50  
3.5  
52  
3.6  
58  
4.1  
TOTAL HEAT OF REJECTION FROM CONDENSER  
20,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. KM-1301SWH (water-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1318  
1319  
598  
598  
1319  
1321  
599  
599  
1249  
1211  
567  
549  
90/32  
100/38  
1319  
1281  
599  
581  
1323  
1301  
600  
590  
1228  
1141  
557  
518  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
1740  
1744  
1746  
1746  
1754  
1760  
1767  
1782  
1786  
watts  
100/38  
70/21  
1755  
1766  
1810  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
1407  
1499  
1527  
1861  
5.33  
5.67  
5.78  
7.04  
1527  
1686  
1818  
1969  
5.78  
6.38  
6.88  
7.46  
2049  
2406  
2465  
3060  
7.76  
9.11  
80/27  
90/32  
9.33  
gal./day m3/day  
100/38  
11.58  
FREEZING CYCLE TIME  
70/21  
80/27  
31  
31  
32  
33  
34  
31  
90/32  
100/38  
70/21  
31  
32  
4.5  
32  
33  
3.9  
34  
36  
3.5  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
4.0  
3.9  
3.1  
2.4  
3.0  
2.2  
min.  
100/38  
3.2  
2.4  
2.1  
HEAD PRESSURE  
70/21  
80/27  
90/32  
235  
236  
236  
16.5  
16.6  
16.6  
236  
237  
238  
16.6  
16.7  
16.7  
246  
253  
252  
17.3  
17.8  
17.7  
PSIG kg/cm2G  
100/38  
241  
16.9  
241  
17.0  
264  
18.6  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
50  
50  
50  
3.5  
3.5  
3.5  
50  
49  
49  
3.5  
3.5  
3.4  
52  
52  
52  
3.6  
3.7  
3.6  
PSIG kg/cm2G  
100/38  
51  
3.6  
50  
3.5  
54  
3.8  
TOTAL HEAT OF REJECTION FROM CONDENSER  
17,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
WATER FLOW FOR CONDENSER  
2,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
120 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]  
PRESSURE DROP OF COOLING WATER LINE  
less than 10 PSIG  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4. KM-1301SWH3 (water-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1333  
1326  
605  
601  
1323  
1311  
600  
594  
1246  
1198  
565  
544  
90/32  
100/38  
1323  
1286  
600  
584  
1300  
1277  
590  
579  
1201  
1110  
545  
503  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
1770  
1786  
1791  
1791  
1818  
1840  
1805  
1824  
1850  
watts  
100/38  
70/21  
1789  
1842  
1860  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
1414  
1499  
1526  
1846  
5.35  
5.68  
5.78  
6.99  
1526  
1673  
1795  
1944  
5.78  
6.33  
6.80  
7.36  
2036  
2382  
2431  
3015  
7.71  
9.02  
80/27  
90/32  
9.20  
gal./day m3/day  
100/38  
11.41  
FREEZING CYCLE TIME  
70/21  
80/27  
30  
31  
32  
32  
33  
31  
90/32  
100/38  
70/21  
31  
31  
4.5  
32  
33  
3.8  
34  
35  
3.5  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
4.0  
3.8  
3.0  
2.4  
3.0  
2.2  
min.  
100/38  
3.1  
2.3  
2.1  
HEAD PRESSURE  
70/21  
80/27  
90/32  
237  
238  
238  
16.7  
16.7  
16.7  
238  
239  
240  
16.7  
16.8  
16.9  
249  
256  
255  
17.5  
18.0  
17.9  
PSIG kg/cm2G  
100/38  
244  
17.1  
244  
17.1  
269  
18.9  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
50  
50  
50  
3.5  
3.5  
3.5  
50  
49  
49  
3.5  
3.5  
3.4  
52  
53  
52  
3.7  
3.7  
3.7  
PSIG kg/cm2G  
100/38  
51  
3.6  
50  
3.5  
55  
3.9  
TOTAL HEAT OF REJECTION FROM CONDENSER  
17,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
WATER FLOW FOR CONDENSER  
2,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
119 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]  
PRESSURE DROP OF COOLING WATER LINE  
less than 10 PSIG  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5. KM-1301SRH (remote air-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1353  
1324  
614  
600  
1315  
1264  
596  
573  
1219  
1144  
553  
519  
90/32  
100/38  
1315  
1281  
596  
581  
1222  
1196  
554  
542  
1110  
1008  
504  
457  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2010  
2028  
2033  
2052  
2033  
2064  
2090  
2105  
2088  
2131  
2153  
2210  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
479  
417  
398  
1.81  
1.58  
1.51  
398  
292  
203  
1.51  
1.10  
0.77  
350  
278  
173  
1.32  
1.05  
0.66  
80/27  
90/32  
gal./day m3/day  
100/38  
70/21  
80/27  
303  
1.15  
196  
0.74  
146  
0.55  
FREEZING CYCLE TIME  
31  
32  
33  
34  
36  
32  
90/32  
100/38  
70/21  
32  
33  
4.1  
35  
35  
3.6  
37  
40  
3.3  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
3.7  
3.6  
2.9  
2.3  
2.9  
2.2  
min.  
100/38  
3.0  
2.3  
2.1  
HEAD PRESSURE  
70/21  
80/27  
90/32  
211  
222  
226  
14.8  
15.6  
15.9  
226  
246  
262  
15.9  
17.3  
18.4  
246  
265  
282  
17.3  
18.7  
19.9  
PSIG kg/cm2G  
100/38  
230  
16.2  
267  
18.8  
301  
21.2  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
50  
50  
51  
3.5  
3.5  
3.6  
51  
51  
52  
3.6  
3.6  
3.7  
53  
55  
56  
3.8  
3.9  
3.9  
PSIG kg/cm2G  
100/38  
52  
3.6  
53  
3.7  
59  
4.1  
TOTAL HEAT OF REJECTION FROM CONDENSER  
17,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
2,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
133 CU. IN (URC-14F)  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6. KM-1301SRH3 (remote air-cooled)  
APPROXIMATE ICE  
PRODUCTION PER 24 HR.  
WATER TEMP. (ºF/ºC)  
70/21  
AMBIENT TEMP.  
(ºF/ºC)  
50/10  
90/32  
70/21  
80/27  
1339  
1307  
607  
593  
1297  
1243  
589  
564  
1203  
1127  
546  
511  
90/32  
100/38  
1297  
1266  
589  
574  
1197  
1171  
543  
531  
1088  
988  
494  
448  
lbs./day kg./day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
70/21  
80/27  
90/32  
2090  
2101  
2105  
2128  
2105  
2124  
2140  
2156  
2160  
2199  
2208  
2270  
watts  
100/38  
70/21  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
463  
403  
384  
1.75  
1.52  
1.45  
384  
279  
192  
1.45  
1.06  
0.72  
338  
269  
165  
1.28  
1.02  
0.63  
80/27  
90/32  
gal./day m3/day  
100/38  
70/21  
80/27  
291  
1.10  
185  
0.70  
141  
0.53  
FREEZING CYCLE TIME  
31  
32  
34  
35  
37  
32  
90/32  
100/38  
70/21  
32  
33  
3.9  
35  
36  
3.4  
39  
42  
3.2  
min.  
HARVEST CYCLE TIME  
80/27  
90/32  
3.5  
3.4  
2.8  
2.2  
2.8  
2.1  
min.  
100/38  
2.9  
2.2  
2.1  
HEAD PRESSURE  
70/21  
80/27  
90/32  
214  
224  
228  
15.0  
15.8  
16.0  
228  
246  
261  
16.0  
17.3  
18.4  
252  
273  
287  
17.7  
19.2  
20.2  
PSIG kg/cm2G  
100/38  
234  
16.5  
267  
18.8  
311  
21.9  
SUCTION PRESSURE  
70/21  
80/27  
90/32  
50  
50  
51  
3.5  
3.5  
3.6  
51  
51  
52  
3.6  
3.6  
3.7  
54  
56  
56  
3.8  
3.9  
3.9  
PSIG kg/cm2G  
100/38  
52  
3.7  
53  
3.7  
60  
4.2  
TOTAL HEAT OF REJECTION FROM CONDENSER  
17,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
TOTAL HEAT OF REJECTION FROM COMPRESSOR  
CONDENSER VOLUME  
2,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]  
133 CU. IN (URC-14F)  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
ꢀ. We reserve the right to make changes in specifications and design without prior  
notice.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IV. Service Diagnosis  
WARNING  
1. This unit should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
ꢀ. Risk of electric shock. Use extreme caution and exercise safe electrical  
practices.  
3. Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.  
4. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews  
are securely in place after the unit is serviced. Make sure that none have  
fallen into the storage bin.  
5. Make sure all food zones in the icemaker and storage bin are clean after  
the unit is serviced. For cleaning procedures, see "VI. Cleaning and  
Maintenance."  
A. Diagnostic Procedure  
The diagnostic procedure is basically a sequence check which can be used at unit  
startup or for system diagnosis. This procedure allows you to diagnose electrical system  
and component failures in normal operating conditions of 70°F (ꢀ1°C) or warmer air and  
50°F (10°C) or warmer water temperatures. Before conducting the diagnostic procedure,  
check for correct installation, proper voltage per unit nameplate, and adequate water  
supply. Check CB using the steps in "IV.B. Control Board Check." Check the dip switch  
settings to assure that S4 dip switch 3, 4, 7, 8, 9, & 10 and S5 dip switch 1 through 5 are  
in the factory default position. S4 dip switch 1, ꢀ, 5, & 6 are cleaning adjustments and  
the settings are flexible. For factory default settings, see "II.C.3.a) Default Dip Switch  
Settings." As you go through the procedure, check to assure the components energize  
and de-energize correctly. If not, those components and controls are suspect.  
1) Turn off the power supply, then access the control box. Clear any ice from BC.  
ꢀ) Turn on the power supply, then move the control switch to the "ICE" position. A  
5-second delay occurs. The red "POWER OK" LED and the green "BC CLOSED" LED  
on the CB come on. If the yellow "BC OPEN" LED is on (indicating a full bin), confirm  
that the CB K4 jumper is in place. If missing, the unit cannot operate.  
WARNING  
1. Risk of electric shock. Use extreme caution and exercise safe electrical  
practices.  
ꢀ. Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3) 1-Minute Fill Cycle – LED 4 is on. WV and Xꢀ relay (auxiliary code T-0, U-0),  
X11 relay (auxiliary code U-1 and later) energize and the 1-minute fill cycle begins.  
After 1 minute, CB checks for a closed F/S. If F/S is closed, the harvest cycle begins. If  
closed, continue to step 4. If open, WV remains energized through additional 1-minute  
fill cycles until water fills the tank and closes F/S (low water safety). Diagnosis: If WV  
does not open, check the supply voltage at WV terminals, check continuity on the  
coil, confirm the screen or external filter isn't plugged (no water flow). If unit fails to  
start harvest, check for open F/S or bad 1-minute timer in CB. See "IV.D. Float Switch  
Check and Cleaning" and "IV.B. Control Board Check."  
4) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and Xꢀ relay (auxiliary code  
T-0, U-0), X11 relay (auxiliary code U-1 and later) remain energized, HGV, X1 relay  
(auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later), Comp, and FMR  
energize. CB monitors the warming of the evaporator via the thermistor located on the  
suction line. When the thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal from  
the thermistor and turns harvest termination over to the harvest timer (S4 dip switch  
1 & ꢀ). The harvest timer has settings of 60, 90, 1ꢀ0, and 180 seconds. For details,  
see "II.C.3.b) Harvest Timer (S4 dip switch 1 & ꢀ)." When the harvest timer expires,  
the harvest cycle is complete. CB checks the position of F/S and proceeds to the next  
cycle if it is closed, or calls for a 1-minute fill cycle if it is open. The minimum total time  
allowed by CB for a complete harvest cycle is ꢀ minutes.  
WV is energized during harvest for a maximum of 6 minutes or the length of harvest  
minus 0 or 50 seconds (harvest pump timer (S4 dip switch 7)), whichever is shorter.  
LED 4 goes off when WV and Xꢀ relay (auxiliary code T-0, U-0), X11 relay (auxiliary  
code U-1 and later) de-energize. LED 3 comes on and PM energizes and runs for the  
last 0 or 50 seconds of harvest depending on S4 dip switch 7 setting. CAUTION! Do  
not adjust S4 dip switch 7 out of the factory default position on this model.  
Adjustment outside of the factory default position may result in damage to the  
icemaker. For details, see "II.C.3.e) Harvest Pump Timer (S4 dip switch 7)."  
PM is energized through the #5 pin (DBu wire) on the CB K1 ten-pin connector and  
the X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later). When  
the harvest timer expires, the harvest cycle is complete. CB checks the position of  
F/S and proceeds to the next cycle if it is closed or calls for a 1-minute fill cycle if it is  
open. The minimum total time allowed by CB for a complete harvest cycle is ꢀ minutes.  
Diagnosis: Check if Comp is running, HGV and WV still energized. Average harvest  
cycle at factory setting is ꢀ to 3 minutes. How long does initial harvest last? 1.5 minutes  
after initial harvest begins, touch Comp discharge line. Is it hot? If not, check refrigerant  
pressures and Comp operation. If it is hot, touch the inlet line to the evaporator. Is it  
hot? If it is hot and the freeze cycle is not starting, check the harvest timer adjustment  
(S4 dip switch 1 & ꢀ), the thermistor for open circuit, the discharge line temperature,  
Comp efficiency, and if HGV is fully open. For a thermistor check, see "IV.E. Thermistor  
Check." Check that PM circulates water over evaporator for the last 50 seconds of  
harvest. If not, check X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code  
U-1 and later) and S4 dip switch 3 & 4. If 1-minute fill cycle starts, see "IV.D. Float  
Switch Check and Cleaning."  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5) Freeze Cycle – LED 1 is on. Comp and FMR remain energized, PM energizes  
or remains energized depending on harvest pump timer (S4 dip switch 7) setting.  
FM and LLV energize. HGV, and X1 relay (auxiliary code T-0, U-0), X10 relay  
(auxiliary code U-1 and later) de-energize. The unit is held in freeze by a 5-minute  
short cycle protection timer (CB will not accept a signal from F/S). After the 5-minute  
short cycle protection timer expires, CB turns freeze termination over to F/S. During  
the first 5 minutes of freeze, confirm that the evaporator temperature drops. After  
5 minutes in freeze, disconnect black F/S connector from CB BLACK K5 connector.  
After a 15 second delay, the unit should switch out of the freeze cycle. Diagnosis: If  
the evaporator is not cold, check to see if HGV is still open or if TXV is not opening  
properly, if WV is continuing to fill the reservoir, if there are improper unit pressures,  
an inoperative Comp, or an inoperative HM. If the unit switches out of freeze with F/S  
connector removed, but would previously not switch out of freeze with F/S connected  
(long freeze - 3 beep alarm), F/S may be sticking. To check and clean F/S, see "IV.  
D. Float Switch Check and Cleaning." If the unit remains in freeze longer than 15  
seconds after disconnecting black F/S connector, replace CB. See "V.P. Removal and  
Replacement of Control Board."  
Note: Normal freeze cycle will last ꢀ0 to 40 minutes depending on model and  
conditions. Cycle times and pressures should follow performance data provided  
in this manual. See "III.C. Performance Data."  
6) Pump-Out Cycle – (10/20 second pump-out) – LEDs 1, 3, and 2 are on. LED 4 is on  
when S4 dip switch 3 & 4 are set to 3 off and 4 on. CAUTION! Do not adjust S4 dip  
switch 3 & 4 to 3 off and 4 on. Adjustment to this position on this model prevents  
the unit from operating correctly and may cause damage. For details, see "II.  
C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." Comp and FMR remain energized, HGV  
energizes. WV energizes if S4 dip switch 3 off and 4 on. LLV and FM de-energize.  
PM stops for ꢀ seconds, then reverses for 10/ꢀ0 seconds depending on pump-out  
timer S4 dip switch 3 & 4 setting. When the pump-out timer expires, the pump-out  
is complete. The pump-out frequency control is factory set for every 10th cycle, and  
generally no adjustment is required. However, where water quality is bad and the  
icemaker needs a pump-out more often, the pump-out frequency can be adjusted.  
The pump-out frequency control (S4 dip switch 5 & 6) can be set to have a pump-out  
occur every cycle, or every ꢀ, 5, or 10 cycles. For details, see "II.C.3.d) Pump-Out  
Frequency Control (S4 dip switch 5 & 6)."  
Timing of the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table  
below  
S4 Dip Switch Setting  
Pump-Out  
Frequency  
1st Pump-Out  
No. 5  
OFF  
ON  
No. 6  
OFF  
OFF  
ON  
Every cycle  
Every ꢀ cycles  
Every 5 cycles  
Every 10 cycles  
After ꢀnd freeze cycle  
After 3rd freeze cycle  
After 6th freeze cycle  
After 11th freeze cycle  
OFF  
ON  
ON  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnosis: If PM does not reverse, check to see if CB S4 and S5 dip switch settings  
are in the factory default position. If S4 dip switch 3 and 4 are adjusted to 3 off and  
4 on, WV and harvest pump timer relays energize. Once these relays energize, the  
pump motor rotates in the freeze cycle rotation. See "III.B. Wiring Diagrams." Check  
PM circuit and capacitor, check #5 pin (DBu wire) on CB K1 ten-pin connector for  
voltage, harvest pump timer X1 and Xꢀ relays (auxiliary code T-0 and U-0), X10 and  
X11 relays (auxiliary code U-1 and later). If water does not pump out, check and clean  
the check valve assembly and tubing.  
7) Normal Harvest Cycle – same as the initial harvest cycle – Return to "IV.A.4) Initial  
Harvest Cycle."  
8) Shutdown  
When the unit is running hold ice in contact with the thermostatic bulb, the thermostatic  
BC switch opens within 10 seconds, shutting down the unit. The bin control is factory  
set, and generally no adjustment is required. However, adjustment may be needed in  
some conditions, particularly at higher altitude locations. Diagnosis: See "IV.C. Bin  
Control Check."  
Legend: BC–bin control; CB–control board; Comp–compressor; FM–fan motor;  
FMR–fan motor-remote; F/S–float switch; HGV–hot gas valve; HM–headmaster  
(C.P.R.); LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion  
valve; WV–inlet water valve  
5ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Control Board Check  
Before replacing a control board that does not show a visible defect and that you  
suspect is bad, always conduct the following check procedure. This procedure will help  
you verify your diagnosis.  
Alarm Reset: If the control board is in alarm (beeping), press the "ALARM RESET"  
button on the control board with power on. Once reset, the unit starts at  
the 1-minute fill cycle. For audible alarm information, see "II.C.ꢀ.f) LED  
Lights and Audible Alarm Safeties."  
1) Check the dip switch settings to assure that S4 dip switch #3, 4, 7, 8, 9, & 10 and  
S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, ꢀ, 5, & 6  
are cleaning adjustments and the settings are flexible. For factory default settings, see  
"II.C.3.a) Default Dip Switch Settings."  
ꢀ) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, the  
control voltage is good. If the "POWER OK" LED is off, check the control transformer  
secondary circuit. The control transformer secondary circuit includes the cleaning valve  
interlock switch. Make sure the interlock switch is closed; otherwise, no control voltage  
is supplied to the Kꢀ connector. Transformer output is 10.5V at 115V primary input. If  
the secondary circuit has proper voltage and the red LED is off, the control board is  
bad and should be replaced. See "V.P. Removal and Replacement of Control Board."  
If the secondary circuit does not have proper voltage, check the control transformer  
primary circuit. Check for 115V at the control board K1 ten-pin connector. Check the  
#10 pin (BR wire) to a white neutral wire for 115V. (Always choose a white neutral wire  
to establish a good neutral connection when checking voltages.) For additional checks,  
see "IV.F.1.[1] The icemaker will not start."  
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control  
switch is in the "ICE" position, then press the "OUTPUT TEST" button. The correct  
lighting sequence is 1, 4, 3, ꢀ. Note that the order of the LEDs from the outer edge  
of the control board is 1, 4, 3, ꢀ. Components (e.g., compressor) will cycle during the  
test. Following the test, the icemaker resumes operation. If the LEDs do not light as  
described above, the control board is bad and should be replaced. See "V.P. Removal  
and Replacement of Control Board."  
4) To verify voltage output from the control board to the components, slide the control  
board K1 ten-pin connector out far enough to allow multimeter lead contact. With the  
unit in the cycle to be tested, check output voltage from the corresponding pin on the  
control board K1 ten-pin connector to ground. If output voltage is not found and the  
appropriate LED is on, the control board is bad and should be replaced. See "V.P.  
Removal and Replacement of Control Board."  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
C. Bin Control Check  
To check the thermostatic bin control, follow the steps below.  
CAUTION  
When the ambient temperature is below 45°F (7°C), the thermostatic bin  
control switch opens and shuts down the icemaker even if the ice storage bin  
is empty. When the thermostat is set in the prohibited range, the icemaker  
operates continuously even if the ice storage bin is filled with ice. Setting in the  
prohibited range may result in severe damage to the icemaker.  
The bin control is factory set, and generally no adjustment is required. However,  
adjustment may be needed in some conditions, particularly at higher altitude locations.  
1) Turn off the power supply.  
ꢀ) Remove the front panel, then remove the control box cover.  
3) Disconnect the thermostatic bin control wires from the thermostatic bin control switch.  
4) Clear any ice away from the thermostatic bulb, then hold your hand around the  
thermostatic bulb to warm it up.  
5) Check for continuity across the thermostatic bin control switch. If closed, continue to  
step 6. If open, adjust or replace the thermostatic bin control.  
6) With the multimeter test leads still in place, hold ice on the thermostatic bulb to lower  
the temperature. Within 10 seconds, the thermostatic bin control switch should open  
(no continuity). If it remains closed, adjust or replace the thermostatic bin control.  
D. Float Switch Check and Cleaning  
The float switch is used to determine that there is sufficient water in the tank after the  
1-minute fill cycle and after each harvest cycle. The float switch is also used to determine  
that the appropriate volume of water has been converted into ice before switching out of  
the freeze cycle. No adjustment is required.  
1. Float Switch Check  
To check the float switch, follow the steps below.  
1) Turn off the power supply.  
ꢀ) Remove the front panel and move the control switch to the "OFF" position.  
3) Remove the insulation panel, then remove the cap located on the front bottom part of  
the ice dropping hole. Drain the water tank.  
4) Replace the cap in its correct position. Be careful not to cross thread it.  
5) Remove the control box cover.  
6) Disconnect the black float switch connector from the control board BLACK  
K5 connector.  
7) Check for continuity across the float switch leads. With the water tank empty, the float  
switch should be open. If open, continue to step 8. If closed, follow the steps in "IV.  
D.ꢀ. Float Switch Cleaning." After cleaning the float switch, check it again. Replace if  
necessary.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8) Reconnect the black float switch connector to the control board BLACK K5 connector,  
then replace the control box cover in its correct position.  
9) Move the control switch to the "ICE" position. Replace the insulation panel and the  
front panel in their correct positions, then turn on the power supply. After 1 minute, the  
1-minute fill cycle should end and the initial harvest cycle should begin. If the initial  
harvest cycle begins, the float switch is good and the check is complete. If the initial  
harvest cycle does not begin, continue to step 10.  
10) Turn off the power supply.  
11) Remove the front panel.  
1ꢀ) Move the control switch to the "OFF" position.  
13) Remove the control box cover.  
14) Disconnect the black float switch connector from the control board BLACK  
K5 connector.  
15) Check for continuity across the float switch leads. With the water tank full, the float  
switch should be closed. If the float switch is closed and the icemaker will not switch  
from the 1-minute fill cycle to the initial harvest cycle, replace the control board.  
If open, confirm that the water tank is full. If the tank is not full, check the water supply,  
water filters, and inlet water valve. If the tank is full, follow the steps in "IV.D.ꢀ. Float  
Switch Cleaning." After cleaning the float switch, check it again. Replace if necessary.  
2. Float Switch Cleaning  
Depending on local water conditions, scale may build up on the float switch. Scale on the  
switch can cause the float to stick. In this case, the float switch should be cleaned.  
1) Turn off the power supply.  
ꢀ) Remove the front panel and move the control switch to the "OFF" position.  
3) Remove the insulation panel, then remove the cap located on the front bottom part of  
the ice dropping hole. Drain the water tank.  
Vent  
4) Replace the cap in its correct position. Be  
careful not to cross thread it.  
Flush  
5) Disconnect the vent tube and the flush  
tube from the top of the float switch, then  
remove the float switch assembly from the  
mounting bracket and remove the rubber  
boot from the bottom of the float switch  
assembly. See Fig. 1.  
Shaft  
Float Switch  
Housing  
6) Remove the retainer rod from the bottom of  
the float switch assembly, then remove the  
float. Be careful not to bend the retainer  
rod excessively when removing it.  
Float  
Retainer Rod  
Rubber Boot  
and Hose  
Fig. 1  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7) Wipe down the float switch assembly's housing, shaft, float, and retainer rod with a  
mixture of 1 part of recommended cleaner Hoshizaki "Scale Away" or "LIME-A-WAY"  
(Economics Laboratory, Inc.) and ꢀ5 parts of warm water. Clean the inside of the  
rubber boot and hose with the cleaning solution. Rinse the parts thoroughly with clean  
water.  
8) Reassemble the float switch assembly and replace it and the rubber boot in their  
correct positions. Reconnect the vent tube and the flush tube.  
9) Move the control switch to the "ICE" position.  
10) Replace the insulation panel and front panel in their correct positions.  
E. Thermistor Check  
To check thermistor resistance, follow the steps below.  
1) Turn off the power supply.  
ꢀ) Remove the front panel, then move the control switch to the "OFF" position.  
3) Remove the control box cover.  
4) Remove the thermistor. See "V.L. Removal and Replacement of Thermistor."  
5) Immerse the thermistor sensor portion in a glass containing ice and water for ꢀ or  
3 minutes.  
6) Remove the white thermistor connector from the control board WHITE K3 connector  
and check the resistance between thermistor leads. Normal reading is within 4.7 to  
6.ꢀ kΩ. If outside the normal reading, replace the thermistor. If inside the normal  
reading, continue to the next step.  
7) Replace the thermistor in its correct position. See "V.L. Removal Replacement of  
Thermistor."  
8) Reconnect the white thermistor connector to the control board WHITE K3 connector.  
9) Replace the control box cover in its correct position, then turn on the power supply.  
10) Move the control switch to the "ICE" position.  
11) Once the harvest cycle starts, begin timing the harvest cycle.  
1ꢀ) The harvest timer should expire and terminate the harvest cycle within ꢀ to 3 minutes.  
If the harvest timer does not expire and terminate the harvest cycle, the harvest timer is  
bad and the control board should be replaced. See "V.P. Removal and Replacement of  
Control Board."  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F. Diagnostic Charts  
1. No Ice Production  
Problem  
Possible Cause  
Remedy  
[1] The icemaker will not a) Power Supply  
start.  
1. Off, blown fuse, or  
tripped breaker.  
1. Turn on, replace, or reset.  
ꢀ. Loose connection.  
3. Bad contacts.  
ꢀ. Tighten.  
3. Check for continuity and  
replace.  
4. Not within  
4. Refer to nameplate and  
correct.  
specifications.  
b) Transformer (115V  
primary) (3 phase only)  
1. Voltage tap switch  
does not match  
1. Verify incoming voltage,  
move switch to proper  
setting.  
incoming voltage.  
ꢀ. Coil winding open or ꢀ. Replace.  
shorted.  
c) Water Supply  
1. Water supply off or  
pressure too low.  
1. Check and get  
recommended pressure.  
d) Thermostatic Bin  
Control  
1. Tripped with bin filled 1. Remove ice.  
with ice.  
ꢀ. Ambient temperature ꢀ. Increase ambient  
too cool.  
temperature.  
3. Set too warm.  
3. See "IV.C. Bin Control  
Check."  
4. Bulb out of position.  
5. Bad contacts.  
4. Place in position.  
5. Check for continuity and  
replace.  
e) Fuse (Control Box)  
f) Control Switch  
1. Blown.  
1. Check for short circuit and  
replace.  
1. "OFF" or "WASH"  
position.  
1. Move to "ICE" position.  
ꢀ. Bad contacts.  
ꢀ. Check for continuity and  
replace.  
g) High Pressure Control 1. Bad contacts.  
1. Check for continuity and  
replace.  
ꢀ. Dirty air filter or  
condenser.  
ꢀ. Clean.  
3. Ambient or condenser 3. Reduce temperature.  
water temperature too  
warm.  
4. Refrigerant  
overcharged.  
4. Recover, evacuate, and  
recharge.  
5. Fan not operating  
(except water-cooled  
model).  
5. See chart 1.[7].  
6. Refrigerant lines or  
components plugged.  
6. Clean and replace drier.  
7. Condenser water  
pressure too low or off  
(water-cooled model).  
7. Check and get  
recommended pressure.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Problem  
Possible Cause  
Remedy  
[1] The icemaker will not h) Transformer  
start. (continued)  
1. Coil winding open or 1. Replace.  
shorted.  
i) Wiring to Control Board 1. Loose connections or 1. Check for continuity and  
open.  
replace.  
j) Interlock Switch  
(Cleaning Valve)  
1. Open position.  
ꢀ. Bad contacts.  
1. Move to closed position.  
ꢀ. Check for continuity and  
replace.  
k) Thermistor  
1. Leads shorted or open 1. See "IV.E. Thermistor  
and high temperature  
or harvest backup  
timer safety operates  
(1 beep or ꢀ beep  
alarm).  
Check."  
l) Hot Gas Valve  
1. Continues to open  
in freeze cycle and  
freeze timer safety  
operates (3 beep  
alarm).  
1. Check for hot gas valve  
stuck open and replace.  
m)Control board green  
"BC CLOSED" LED  
off and/or yellow "BC  
OPEN" LED on  
1. K4 jumper missing or 1. Confirm jumper is in place.  
open.  
Check for continuity.  
n) Inlet Water Valve  
1. Mesh filter or orifice  
gets clogged and  
water supply cycle  
does not finish.  
1. Clean.  
ꢀ. Coil winding open.  
ꢀ. Replace.  
3. Wiring to inlet water  
valve.  
3. Check for loose connection  
or open, and replace.  
o) Float Switch  
1. Bad contacts.  
1. Check for continuity and  
replace.  
ꢀ. Float does not move ꢀ. Clean or replace. See "IV.  
freely.  
D. Float Switch Check and  
Cleaning."  
p) Control Board  
a) Water Supply  
b) Float Switch  
1. Defective or in alarm. 1. See "IV.B. Control Board  
Check."  
[ꢀ] Fill cycle will not  
terminate.  
1. Water supply off or  
pressure too low.  
1. Check and get  
recommended pressure.  
1. Connector  
disconnected.  
1. Reconnect.  
ꢀ. Defective switch.  
ꢀ. Clean or replace. See "IV.  
D. Float Switch Check and  
Cleaning."  
3. Float does not move ꢀ. Clean or replace. See "IV.  
freely or switch  
defective.  
D. Float Switch Check and  
Cleaning."  
c) Control Board  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[3] Compressor will  
not start or stops  
operating.  
a) Magnetic Contactor  
1. Bad contacts.  
1. Check for continuity and  
replace.  
ꢀ. Coil winding open.  
ꢀ. Replace.  
1. Replace.  
b) Start Capacitor or Run 1. Defective.  
Capacitor  
c) Internal Overload  
Protector Open (check  
1 through 3 to the right  
and d through f below)  
1. Loose terminal.  
1. Tighten or replace.  
ꢀ. Check and correct.  
3. Clean.  
ꢀ. Voltage.  
3. Dirty condenser.  
d) Starter  
1. Bad contacts.  
1. Check and replace.  
ꢀ. Replace.  
ꢀ. Coil winding open.  
e) Compressor  
1. Power supply not  
within specifications.  
1. Refer to nameplate and  
correct.  
ꢀ. Wiring to compressor. ꢀ. Check for loose connection  
or open, and replace.  
3. Defective.  
3. Replace.  
4. Protector tripped.  
4. Reduce temperature.  
f) Control Board  
1. No power to contactor. 1. See "IV.B. Control Board  
Check."  
[4] Water continues to  
be supplied in freeze  
cycle.  
a) Water Pressure  
b) Inlet Water Valve  
1. Too high.  
1. Reduce.  
1. Diaphragm does not 1. Check for water leaks with  
close.  
icemaker off.  
c) Control Board  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
[5] Water pump will not a) Pump Motor  
start.  
1. Motor winding open. 1. Replace.  
ꢀ. Bearing worn out. ꢀ. Replace.  
3. Wiring to pump motor. 3. Check for loose connection  
or open, and replace.  
4. Defective capacitor.  
4. Replace.  
5. Defective or bound  
impeller.  
5. Replace and clean.  
6. Mechanical seal worn 6. Check and replace.  
out.  
b) Control Board  
c) Control Switch  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
1. Bad contacts.  
1. Replace.  
[6] Freeze cycle time is a) Pump-Out Check Valve 1. Leaking by.  
too short.  
1. Clean or replace.  
b) Float Switch  
1. Dirty or erratic  
operation.  
1. Clean or replace. See "IV.  
D. Float Switch Check and  
Cleaning."  
c) Control Board  
d) Water System  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
1. Water leaks.  
1. Check connections for  
water leaks, and replace.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[7] Fan motor will  
not start, or is not  
operating (except  
water-cooled model).  
a) Fan Motor  
1. Motor winding open. 1. Replace.  
ꢀ. Bearing worn out.  
ꢀ. Replace.  
3. Wiring to fan motor.  
3. Check for loose connection  
or open, and replace.  
4. Defective capacitor.  
5. Fan blade bound.  
1. Defective.  
4. Replace.  
5. Check and replace.  
b) Control Board  
a) Refrigerant  
1. See "IV.B. Control Board  
Check."  
[8] All components  
run, but no ice is  
produced.  
1. Low charge.  
1. Check for leaks. Recover,  
repair, evacuate, and  
recharge.  
ꢀ. Air or moisture  
trapped.  
ꢀ. Replace drier, evacuate,  
and recharge.  
b) Compressor  
1. Defective.  
1. Replace.  
c) Hot Gas Valve  
1. Continues to open in 1. Check and replace.  
freeze cycle.  
d) Liquid Line Valve  
(if applicable)  
1. Continues to close in 1. Check and replace.  
freeze cycle.  
e) Inlet Water Valve  
1. Inlet water valve is  
wide open during  
freeze.  
1. Check for water leaks with  
icemaker off.  
f) Expansion Valve  
1. Bulb loose.  
1. Secure bulb.  
ꢀ. Operating erratically. ꢀ. Check and replace.  
g) Headmaster (C.P.R.)  
(remote condenser  
unit)  
1. Not operating properly 1. Replace headmaster.  
and liquid line  
temperature too warm.  
h) Water Supply Line  
(water-cooled model)  
1. Condenser water  
pressure too low or  
off and high pressure  
control opens and  
closes frequently.  
1. Check and get  
recommended pressure.  
i) Water Regulating Valve 1. Set too high.  
(water-cooled model)  
1. Adjust or replace. See  
"V.J. Adjustment of Water  
Regulating Valve."  
2. Evaporator is Frozen Up  
Problem  
Possible Cause  
Remedy  
[1]Freeze cycle time is a) Inlet Water Valve  
too long.  
1. Diaphragm does not 1. Check for water leaks with  
close.  
icemaker off.  
b) Float Switch  
1. Float does not move 1. Clean or replace. See "IV.  
freely or defective  
switch.  
D. Float Switch Check and  
Cleaning."  
c) Evaporator  
d) Spray Tubes  
e) Water Pump  
1. Scaled up.  
ꢀ. Damaged.  
1. Dirty.  
1. Clean.  
ꢀ. Replace.  
1. Clean.  
ꢀ. Out of position.  
1. RPM too slow.  
ꢀ. Place in position.  
1. See chart 1.[5].  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[1]Freeze cycle time is f) Thermistor  
too long. (continued)  
1. Loose or  
1. Reattach or connect. See  
"IV.E. Thermistor Check."  
disconnected.  
g) Refrigerant Charge  
1. Low charge.  
1. Check for leaks. Recover,  
repair, evacuate, and  
recharge.  
h) Expansion Valve  
1. Bulb loose.  
1. Secure bulb.  
ꢀ. Operating erratically. ꢀ. Check and replace.  
i) Control Board  
a) Evaporator  
1. Defective.  
1. See "IV.B. Control Board  
Check."  
[ꢀ]All ice formed on  
evaporator does not  
fall into bin in harvest  
cycle.  
1. Scaled up.  
ꢀ. Damaged.  
1. Clean.  
ꢀ. Replace.  
b) Ambient and/or Water 1. Too cool.  
Temperature  
1. Increase temperature.  
c) Water Supply Line  
1. Water pressure too  
1. Check and get  
low.  
recommended pressure.  
d) Water System  
1. Water supply line  
too small; requires  
1/ꢀ" OD line dedicated  
per machine.  
1. Increase water line size.  
ꢀ. Water filter clogged or ꢀ. Replace filter or install a  
flow rate too small.  
higher flow rate filter.  
e) Inlet Water Valve  
f) Spray Tubes  
1. Dirty mesh filter or  
orifice.  
1. Clean.  
ꢀ. Diaphragm does not ꢀ. Check for water leaks with  
close.  
icemaker off.  
1. Dirty.  
1. Clean.  
ꢀ. Out of position.  
ꢀ. Place in position.  
g) Thermistor  
1. Loose or  
1. Reattach or connect. See  
"IV.E. Thermistor Check."  
disconnected.  
h) Hot Gas Valve  
1. Coil winding open.  
1. Replace.  
ꢀ. Replace.  
ꢀ. Plunger does not  
move.  
3. Wiring to hot gas  
valve.  
3. Check for loose  
connection or open, and  
replace.  
i) Expansion Valve  
1. Open.  
1. Check and replace.  
j) Liquid Line Valve  
(if applicable)  
1. Continues to open in 1. Check operation in harvest  
harvest cycle.  
cycle and replace.  
k) Control Board  
1. Harvest timer is set  
too short.  
1. Adjust longer, referring to  
"II.C.3.b) Harvest Timer  
(S4 dip switch 1 & ꢀ)."  
ꢀ. Defective.  
ꢀ. See "IV.B. Control Board  
Check."  
l) Refrigerant Charge  
1. Low Charge  
1. Check for leaks. Recover,  
repair, evacuate, and  
recharge.  
m)Water Regulating Valve 1. Leaking by in harvest. 1. Check and replace.  
(water-cooled model)  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[3]Other.  
a) Ice Cube Guide  
1. Out of position.  
1. Bulb out of position.  
ꢀ. Bad contacts.  
1. Place in position.  
1. Place in position.  
b) Thermostatic Bin  
Control  
ꢀ. See "IV.C. Bin Control  
Check."  
3. Low Ice Production  
Problem  
Possible Cause  
Remedy  
[1] Freeze cycle time is a) Inlet Water Valve  
long.  
1. Diaphragm does not 1. Check for water leaks with  
close.  
icemaker off.  
b) Float Switch  
1. Float switch does  
not move freely or  
defective switch.  
1. Clean or replace. See "IV.  
D. Float Switch Check and  
Cleaning."  
c) Evaporator  
d) Spray Tubes  
e) Water Pump  
1. Scaled up.  
ꢀ. Damaged.  
1. Dirty.  
1. Clean.  
ꢀ. Replace.  
1. Clean.  
ꢀ. Out of position.  
1. RPM too slow.  
ꢀ. Place in position.  
1. See chart 1.[5].  
f) Condenser (except  
water-cooled model)  
1. Air filter or condenser 1. Clean.  
clogged.  
g) Refrigerant Charge  
1. Low charge.  
1. Check for leaks. Recover,  
repair, evacuate, and  
recharge.  
h) Hot Gas Valve  
1. Open.  
1. Check and replace.  
1. Secure bulb.  
i) Expansion Valve  
1. Bulb loose.  
ꢀ. Operating erratically. ꢀ. Check and replace.  
1. Erratic or off. 1. See chart 1.[3].  
1. Water regulating valve 1. Adjust or replace. See  
j) Compressor  
k) Condenser Water  
(water-cooled model)  
set too high.  
"V.J. Adjustment of Water  
Regulating Valve."  
ꢀ. Condenser water  
pressure too low.  
ꢀ. Check and get  
recommended pressure.  
3. Water temperature out 3. Correct to specification.  
of specification.  
l) Liquid Line Valve  
1. Erratic, sticking.  
1. Bypassing.  
1. Check and replace.  
1. Replace.  
m)Headmaster (C.P.R.)  
(remote condenser  
unit)  
n) Control Board  
1. Float switch  
1. Check and reconnect.  
connection loose (K5).  
ꢀ. Defective.  
ꢀ. See "IV.B. Control Board  
Check."  
6ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[ꢀ] Harvest cycle time is a) Water Supply  
long.  
1. Water temperature too 1. Increase temperature.  
cold.  
b) Thermistor  
1. Out of position or  
defective.  
1. Reattach and secure.  
See "V.L. Removal  
and Replacement of  
Thermistor" and "IV.E.  
Thermistor Check."  
c) Control Board  
1. Not reading  
thermistor.  
1. Check and replace. See  
"IV.E. Thermistor Check."  
ꢀ. Sending voltage to  
liquid line valve (if  
ꢀ. Check and replace. See  
"IV.B. Control Board  
Check."  
applicable) in harvest.  
d) Inlet Water Valve  
e) Evaporator  
1. Clogged.  
1. Clean or replace.  
1. Clean.  
1. Scaled up.  
f) Hot Gas Valve  
1. Does not open, or  
opens partially.  
1. Check and replace.  
g) Expansion Valve  
1. Wide open in harvest. 1. Check and replace.  
h) Water Regulating Valve 1. Open during harvest. 1. Adjust or replace. See  
(water-cooled model)  
"V.J. Adjustment of Water  
Regulating Valve ."  
i) Liquid Line Valve (if  
applicable)  
1. Open during harvest 1. Check and replace.  
cycle.  
4. Abnormal Ice  
Problem  
Possible Cause  
Remedy  
[1] Small cubes.  
a)Pump-Out Check Valve 1. Dirty or worn and  
leaking by.  
1. Clean or replace.  
b)Ice Cube Guide  
1. Out of position.  
Circulated water falls  
into bin.  
1. Place in position.  
c) Water System  
1. Water supply line  
too small; requires  
1/ꢀ" OD line dedicated  
per machine.  
1. Increase water line size.  
ꢀ. Water filter clogged or ꢀ. Replace filter or install a  
flow rate too small.  
higher flow rate filter.  
d)Inlet Water Valve  
1. Dirty mesh filter or  
orifice.  
1. Clean.  
e)Pump Motor  
1. RPM too slow.  
1. Defective.  
1. See chart 1.[5].  
f) Control Board  
1. See "IV.B. Control Board  
Check."  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem  
Possible Cause  
Remedy  
[ꢀ] Cloudy or irregular  
cubes.  
a)Evaporator  
1. Frozen up.  
ꢀ. Scaled up.  
3. Damaged.  
1. See chart ꢀ.  
ꢀ. Clean  
3. Replace.  
b)Water System  
1. Water supply line  
too small; requires  
1/ꢀ" OD line dedicated  
per machine.  
1. Increase water line size.  
ꢀ. Water filter clogged or ꢀ. Replace filter or install a  
flow rate too small.  
higher flow rate filter.  
3. High hardness or  
contains impurities.  
3. Install a water softener or  
filter.  
c) Spray Guide  
1. Dirty.  
1. Clean.  
5. Other  
Problem  
Possible Cause  
Remedy  
[1]Icemaker will not stop a)Thermostatic Bin  
1. Set too cold.  
ꢀ. Defective.  
1. See "IV.C. Bin Control  
Check."  
when bin is filled with  
ice.  
Control  
ꢀ. Replace.  
[ꢀ] Abnormal noise.  
a)Pump Motor  
1. Bearings worn out.  
1. Bearings worn out.  
1. Replace.  
1. Replace.  
b)Fan Motor (except  
water-cooled model)  
ꢀ. Fan blade deformed. ꢀ. Replace.  
3. Fan blade does not  
move freely.  
3. Replace.  
c) Compressor  
1. Bearings worn out or 1. Replace.  
cylinder valve broken.  
ꢀ. Mounting pad out of  
position.  
ꢀ. Reinstall.  
d)Refrigerant Lines  
1. Rub or touch other  
lines or surfaces.  
1. Reposition.  
[3]Ice in storage bin  
often melts.  
a)Drain Line(s)  
1. Plugged.  
1. Clean.  
b)Icemaker and Bin  
1. Drains not run  
separately.  
1. Separate the drain lines.  
c) Ice Cube Guide  
1. Out of position.  
Circulated water falls  
into bin.  
1. Place in position.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V. Removal and Replacement of Components  
WARNING  
1. This unit should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
ꢀ. Move the control switch to the "OFF" position and turn off the power supply  
before servicing.  
3. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews  
are securely in place after the unit is serviced. Make sure that none have  
fallen into the storage bin.  
4. Make sure all food zones in the icemaker and storage bin are clean after  
the unit is serviced. For cleaning procedures, see "VI. Cleaning and  
Maintenance."  
A. Service for Refrigerant Lines  
WARNING  
1. Repairs requiring the refrigeration circuit to be opened must be performed by  
properly trained and EPA-certified service personnel.  
ꢀ. Always recover the refrigerant and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a  
trace of refrigerant to the system (if using an electronic leak detector), and  
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A  
as a mixture with pressurized air for leak testing.  
CAUTION  
1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture  
quickly. Therefore it is important to prevent moisture from entering the  
system when replacing or servicing parts.  
ꢀ. Always install a new drier every time the sealed refrigeration system is  
opened.  
3. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
4. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
5. Do not leave the system open for longer than 15 minutes when replacing or  
servicing parts.  
1. Refrigerant Recovery  
The icemaker is provided with refrigerant service valves. Using proper refrigerant practices,  
recover the refrigerant from the service valves and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. Brazing  
WARNING  
1. R-404A itself is not flammable at atmospheric pressure and temperatures up  
to 176°F (80°C).  
ꢀ. R-404A itself is not explosive or poisonous. However, when exposed to  
high temperatures (open flames), R-404A can be decomposed to form  
hydrofluoric acid and carbonyl fluoride both of which are hazardous.  
3. Do not use silver alloy or copper alloy containing arsenic.  
4. Use an electronic leak detector or soap bubbles to check for leaks. Add a  
trace of refrigerant to the system (if using an electronic leak detector), and  
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A  
as a mixture with pressurized air for leak testing.  
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,  
it is important to make connections outside the evaporator case when possible. If  
it is necessary to braze inside the evaporator case, use sandpaper to remove the  
coating from the brazing connections before unbrazing the components.  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
ꢀ) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
3. Evacuation and Recharge (R-404A)  
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both  
high and low-side service valves.  
IMPORTANT  
The vacuum level and vacuum pump may be the same as those for current  
refrigerants. However, the rubber hose and gauge manifold to be used for  
evacuation and refrigerant charge should be exclusively for POE oils.  
ꢀ) Turn on the vacuum pump. Open the gauge manifold valves. Then, open the high and  
low-side service valves. Never allow the oil in the vacuum pump to flow backwards.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3) Allow the vacuum pump to pull down to a ꢀ9.9" Hg vacuum. Evacuating period depends  
on pump capacity.  
4) Close the low-side valve and high-side valve on the gauge manifold.  
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a  
refrigerant service cylinder. Remember to loosen the connection and purge the air  
from the hose. For air-cooled and water-cooled models, see the nameplate for the  
required refrigerant charge. For remote air-cooled model, see the rating label inside the  
icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which  
meets ARI Standard 700 (latest edition) be used.  
6) A liquid charge is recommended for charging an R-404A system. Invert the service  
cylinder and place it on scales. Open the high-side valve on the gauge manifold.  
7) Allow the system to charge with liquid until the proper charge weight is met.  
8) If necessary, add any remaining charge to the system through the low-side. Use a  
throttling valve or liquid dispensing device to add the remaining liquid charge through  
the low-side service valve with the unit running.  
9) Close the high and low-side service valves. Then, close the high and low-side gauge  
manifold valves and disconnect the gauge manifold hoses.  
10) Cap the service valves to prevent a possible leak.  
B. Removal and Replacement of Compressor  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
Note: When replacing a compressor with a defective winding, be sure to install the  
new start capacitor and start relay supplied with the replacement compressor.  
Due to the ability of the POE oil in the compressor to absorb moisture quickly,  
the compressor must not be opened more than 15 minutes for replacement or  
service. Do not mix lubricants of different compressors even if both are charged  
with R-404A, except when they use the same lubricant.  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Recover the refrigerant and store it in an approved container.  
4) Remove the terminal cover on the compressor and disconnect the compressor wiring.  
On remote air-cooled models, disconnect the crankcase heater.  
5) Remove the discharge, suction, and process pipes.  
6) Remove the hold-down bolts, washers, and rubber grommets.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7) Remove the compressor. Unpack the new compressor package.  
8) Attach the rubber grommets of the prior compressor to the new compressor.  
9) Place the compressor in position and secure it using the bolts and washers.  
10) Remove the drier, then place the new drier in position.  
11) Remove the plugs from the suction, discharge, and process pipes.  
1ꢀ) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
13) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
14) Evacuate the system and charge it with refrigerant. For air-cooled and water-cooled  
models, see the nameplate for the required refrigerant charge. For remote air-cooled  
models, see the rating label inside the icemaker.  
15) Connect the terminals and replace the terminal cover in its correct position. On remote  
air-cooled models, connect the crankcase heater.  
16) Replace the panels in their correct positions.  
17) Turn on the power supply.  
C. Removal and Replacement of Expansion Valve  
Moisture in the refrigeration circuit may exceed drier capacity and freeze up at the  
expansion valve.  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the valve body and drier by using wet cloths to  
prevent the valve body and drier from overheating. Do not allow the valve  
body or drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Recover the refrigerant and store it in an approved container.  
4) Remove the insulation and the expansion valve bulb on the suction line.  
5) Remove the expansion valve cover and disconnect the expansion valve. Place the new  
expansion valve in position.  
6) Remove the drier, then place the new drier in position.  
7) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
9) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled  
models, see the nameplate for the required refrigerant charge. For remote air-cooled  
models, see the rating label inside the icemaker.  
10) Attach the expansion valve bulb to the suction line in the same location as the previous  
bulb. The bulb should be at the 10 or ꢀ o'clock position on the tube. Be sure to secure  
the bulb with the clamp and holder and to insulate it.  
11) Place the expansion valve cover in position.  
1ꢀ) Replace the panels in their correct positions.  
13) Turn on the power supply.  
D. Removal and Replacement of Hot Gas Valve or Liquid Line Valve  
IMPORTANT  
1. Always use a copper tube of the same diameter and length when replacing  
the valve lines; otherwise, performance may be affected.  
ꢀ. Always replace the strainer when replacing the hot gas valve.  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the valve body and drier by using wet cloths to  
prevent the valve body and drier from overheating. Do not allow the valve  
body or drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Recover the refrigerant and store it in an approved container.  
4) Remove the bolt and the solenoid.  
5) Disconnect the valve. If replacing the hot gas valve, also remove the strainer.  
6) Place the new valve and strainer (if applicable) in position.  
7) Remove the drier, then place the new drier in position.  
8) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
10) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled  
models, see the nameplate for the required refrigerant charge. For remote air-cooled  
models, see the rating label inside the icemaker.  
11) Cut the leads of the solenoid allowing enough lead length to reconnect using closed  
end connectors.  
1ꢀ) Connect the new solenoid leads.  
13) Attach the solenoid to the valve body and secure it with the bolt.  
14) Replace the panels in their correct positions.  
15) Turn on the power supply.  
E. Removal and Replacement of Evaporator  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels and the front and top insulation.  
3) Recover the refrigerant and store it in an approved container.  
4) Remove the spray tubes. Remove the insulation at the "U" shaped notch where the  
refrigeration tubing passes through the molded chassis.  
5) Disconnect the evaporator tubing.  
6) Remove the pop rivets securing the evaporator, then lift out the evaporator.  
7) Install the new evaporator.  
8) Remove the drier, then place the new drier in position.  
9) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
10) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
11) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled  
models, see the nameplate for the required refrigerant charge. For remote air-cooled  
models, see the rating label inside the icemaker.  
1ꢀ) Replace the removed parts in the reverse order of which they were removed.  
13) Replace the top insulation and the panels in their correct positions.  
14) Turn on the power supply.  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F. Removal and Replacement of Air-Cooled Condenser  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Recover the refrigerant and store it in an approved container.  
4) Disconnect the condenser inlet and outlet piping.  
5) Remove the side frame, then remove the condenser assembly.  
6) Remove the shroud from the old condenser and attach it to the new condenser.  
7) Install the new condenser assembly, then attach the side frame in its correct position.  
8) Remove the drier, then place the new drier in position.  
9) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
10) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
11) Evacuate the system, and charge it with refrigerant. See the nameplate for the required  
refrigerant charge.  
1ꢀ) Replace the panels in their correct positions.  
13) Turn on the power supply.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
G. Removal and Replacement of Water-Cooled Condenser  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Close the condenser water supply line shut-off valve. If connected to a closed loop  
water supply, also close the condenser return outlet shut-off valve.  
4) Open the condenser water supply line drain valve. If connected to a closed loop water  
supply, also open the condenser return outlet drain valve.  
5) Attach a compressed air or carbon dioxide supply to the condenser water supply line  
drain valve.  
6) Open the water regulating valve by using a screwdriver to pry up on the spring retainer  
underneath the spring. While holding the valve open, blow out the condenser using the  
compressed air or carbon dioxide supply until water stops coming out.  
7) Recover the refrigerant and store it in an approved container.  
8) Disconnect the condenser water inlet and outlet piping and the refrigeration inlet and  
outlet piping at the condenser.  
9) Remove the old condenser and install the new condenser.  
10) Remove the drier, then place the new drier in position.  
11) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
1ꢀ) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
13) Evacuate the system, and charge it with refrigerant. See the nameplate for the required  
refrigerant charge.  
14) Close the drain valve(s). Open the condenser water supply line shut-off valve. If  
connected to a closed loop water supply, also open the condenser return outlet shut-off  
valve.  
15) Check for water leaks.  
16) Replace the panels in their correct positions.  
17) Turn on the power supply.  
7ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
H. Removal and Replacement of Remote Air-Cooled Condenser  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the icemaker panels.  
3) Recover the refrigerant and store it in an approved container.  
4) Remove the condenser unit panels.  
5) Disconnect the condenser inlet and outlet piping.  
6) Remove the screws securing the condenser to the base of the unit, then remove the  
condenser.  
7) Remove the shroud from the condenser and attach to the new condenser.  
8) Install the new condenser.  
9) Remove the drier (located in the icemaker), then place the new drier in position.  
10) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
11) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
1ꢀ) Evacuate the system, and charge it with refrigerant. See the rating label inside the  
icemaker for the required refrigerant charge.  
13) Replace the panels in their correct positions.  
14) Turn on the power supply.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
I. Removal and Replacement of Water Regulating Valve  
(water-cooled model)  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Close the condenser water supply line shut-off valve. If connected to a closed loop  
water supply, also close the condenser return outlet shut-off valve.  
4) Open the condenser water supply line drain valve. If connected to a closed loop water  
supply, also open the condenser return outlet drain valve.  
5) Attach a compressed air or carbon dioxide supply to the condenser water supply line  
drain valve.  
6) Open the water regulating valve by using a screwdriver to pry up on the spring retainer  
underneath the spring. While holding the valve open, blow out the condenser using the  
compressed air or carbon dioxide supply until water stops coming out.  
7) Recover the refrigerant and store it in an approved container.  
8) Disconnect the capillary tube at the condenser outlet.  
9) Disconnect the flare-connections of the valve.  
10) Remove the screws and the valve from the bracket.  
11) Install the new valve.  
1ꢀ) Remove the drier, then place the new drier in position.  
13) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
14) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
15) Evacuate the system, and charge it with refrigerant. See the nameplate for the required  
refrigerant charge.  
16) Connect the flare-connections.  
17) Close the drain valve(s). Open the condenser water supply line shut-off valve. If  
connected to a closed loop water supply, also open the condenser return outlet shut-off  
valve.  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
18) Check for water leaks.  
19) Replace the panels in their correct positions.  
ꢀ0) Turn on the power supply.  
J. Adjustment of Water Regulating Valve (water-cooled model)  
The water regulating valve (also called "water regulator") is factory set, and generally no  
adjustment is required. However, when necessary, adjust the water regulator using the  
following procedures.  
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure  
gauge to the high-side line of the system.  
Adjustment Screw  
ꢀ) Five minutes after a freeze cycle starts,  
confirm that the thermometer reads 104°F  
to 115°F (40°C to 46°C). If it does not,  
rotate the adjustment screw by using a flat  
blade screwdriver until the temperature  
is in the proper range. See Fig. ꢀ. Next,  
check that the reference pressure is in the  
range indicated in the Head Pressure table  
in the Performance Data section. If it is not  
in the proper range, verify the refrigerant  
charge.  
CW – Higher  
CCW – Lower  
Top View  
Fig. 2  
3) Check that the condenser drain temperature is stable.  
K. Removal and Replacement of Headmaster (Condensing Pressure  
Regulator - C.P.R.) (remote air-cooled model)  
CAUTION  
1. Always install a new drier every time the sealed refrigeration system is  
opened.  
ꢀ. Do not replace the drier until after all other repair or replacement has been  
made. Install the new drier with the arrow on the drier in the direction of the  
refrigerant flow.  
3. When brazing, protect the headmaster and drier by using wet cloths to  
prevent the headmaster and drier from overheating. Do not allow the  
headmaster or drier to exceed ꢀ50°F (1ꢀ1°C).  
1) Turn off the power supply.  
ꢀ) Remove the panels from the remote condenser unit.  
3) Recover the refrigerant and store it in an approved container.  
4) Before heating, break off the stub on the dome to release the dome charge.  
5) Disconnect the headmaster.  
6) Place the new headmaster in position.  
7) Remove the drier, then place the new drier in position.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8) Braze all fittings with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
10) Evacuate the system and charge it with refrigerant. See the rating label inside the  
icemaker for the required refrigerant charge.  
11) Replace the panels in their correct positions.  
1ꢀ) Turn on the power supply.  
L. Removal and Replacement of Thermistor  
This section covers removal and replacement of the thermistor. For a thermistor check  
procedure, see "IV.E. Thermistor Check."  
IMPORTANT  
1. Fragile; handle very carefully.  
ꢀ. Always use the recommended sealant (high thermal conductive type),  
Model KE4560RTV manufactured by SHINETSU SILICONE, Part Code  
60Y000-11, or Part Code 4A0683-01 equivalent.  
3. Always use the recommended foam insulation (non-absorbent type) or  
equivalent.  
4. Do not shorten or cut the thermistor leads.  
1) Turn off the power supply.  
Thermistor Lead  
Cable Tie  
ꢀ) Remove the panels.  
3) Remove the control box cover.  
4) Disconnect the white thermistor connector  
from the control board WHITE K3  
connector.  
5) Remove the plastic cable ties, foam  
insulation, thermistor holder, and  
thermistor. See Fig. 3.  
Foam Insulation  
Thermistor Holder  
6) Scrape away the old sealant on the  
thermistor holder and the suction pipe.  
Fig. 3  
7) Wipe off moisture or condensation on the  
suction pipe.  
8) Smoothly apply recommended sealant (KE4560RTV, Part Code 60Y000-11 or  
4A0683-01) to the thermistor holder concave.  
9) Attach the new thermistor to the suction pipe in the same position as the previous  
thermistor. Be very careful to prevent damage to the leads. Secure it using the  
thermistor holder and recommended foam insulation.  
10) Secure the insulation using the plastic cable ties.  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
11) Connect the white thermistor connector through the bushing of the control box to the  
control board WHITE K3 connector.  
CAUTION  
Do not cut the leads of the thermistor.  
1ꢀ) Replace the control box cover and the panels in their correct positions.  
13) Turn on the power supply.  
M. Removal and Replacement of Fan Motor (air-cooled and  
remote air-cooled models)  
Note: When replacing a fan motor with defective winding, it is recommended that a new  
capacitor be installed.  
1) Turn off the power supply.  
ꢀ) Remove the panels.  
3) Remove the junction box cover from the remote condenser unit (remote air-cooled  
model).  
4) Disconnect the fan motor wires.  
5) Remove the fan motor bracket and fan motor.  
6) Install the new fan motor, connect the fan motor wires, and replace the removed parts  
in the reverse order of which they were removed.  
7) Replace the panels in their correct positions.  
8) Replace the junction box cover in its correct position (remote air-cooled models).  
9) Turn on the power supply.  
N. Removal and Replacement of Inlet Water Valve  
1) Turn off the power supply.  
ꢀ) Close the icemaker water supply line shut-off valve. Open the icemaker water supply  
line drain valve.  
3) Remove the front panel.  
4) Disconnect the valve outlet tubing by releasing the clamp.  
5) Loosen the fitting nut. Be careful not to lose the washer.  
6) Disconnect the terminals from the inlet water valve.  
7) Remove the bracket and valve from the unit.  
8) Install the new valve. Replace the removed parts in the reverse order of which they  
were removed. Make sure the washer is in place in the fitting nut.  
9) Close the icemaker water supply line drain valve. Open the icemaker water supply line  
shut-off valve.  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
10) Turn on the power supply.  
11) Check for leaks.  
1ꢀ) Replace the front panel in its correct position.  
13) Turn on the power supply.  
Cube Guide  
Separator  
O. Removal and Replacement of Pump Motor  
1) Turn off the power supply.  
ꢀ) Remove the front panel and the insulation panel.  
Front  
Inside of Ice  
Dropping Hole  
3) Drain the water tank by removing the cap  
located on the front bottom part of the ice  
dropping hole. See Fig. 4.  
Fig. 4  
4) Replace the cap in its correct position. Be  
careful not to cross thread the cap.  
Cap  
5) Disconnect the pump suction and discharge hoses.  
6) Remove the closed end connectors from  
the pump motor leads. Remove the ground  
wire.  
7) Remove the two screws and the pump motor bracket.  
8) Remove the pump housing and check the impeller.  
9) If the impeller is defective, install a new impeller.  
10) Install the new motor or new parts, and replace the removed parts in the reverse order  
of which they were removed. Be sure to reconnect the pump motor ground wire.  
11) Turn on the power supply and check for leaks.  
1ꢀ) Replace the insulation panel and the front panel in their correct positions.  
13) Turn on the power supply.  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
P. Removal and Replacement of Control Board  
When replacing a control board follow the precautions below.  
CAUTION  
1. The control board is fragile; handle very carefully.  
ꢀ. The control board contains integrated circuits, which are susceptible to  
failure due to static discharge. It is especially important to touch the metal  
part of the unit before handling or replacing the control board.  
3. Do not touch the electronic devices on the control board or the back of the  
control board.  
4. Do not change wiring and connections. Do not misconnect K3, K4, and K5,  
because the same connector is used for the thermistor and float switch. K4  
must have the K4 jumper in place for proper operation.  
5. Always replace the whole control board assembly if it goes bad.  
6. Do not short out power supply to test for voltage.  
1) Turn off the power supply.  
ꢀ) Remove the front panel and the control box cover.  
3) Disconnect the control board connectors from the control board.  
4) Remove the control board.  
5) Adjust the dip switches on the new control board to the factory default settings. See "II.  
C.3.a) Default Dip Switch Settings." CAUTION! Do not adjust S4 dip switch 7 out  
of the factory default position on this model. Adjustment outside of the factory  
default position may result in damage to the icemaker.  
6) Install the new control board taking care not to damage it.  
7) Connect the control board connectors to the new control board.  
8) Replace the control box cover and front panel in their correct positions.  
9) Turn on the power supply.  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VI. Cleaning and Maintenance  
IMPORTANT  
Ensure all components, fasteners, and thumbscrews are securely in place after  
any cleaning or maintenance is done to the equipment.  
A. Cleaning and Sanitizing Instructions  
Hoshizaki recommends cleaning this icemaker at least once a year. More frequent  
cleaning, however, may be required in some existing water conditions.  
WARNING  
1. To prevent injury to individuals and damage to the icemaker, do not use  
ammonia type cleaners.  
ꢀ. Always wear liquid-proof gloves to prevent the cleaning and sanitizing  
solutions from coming into contact with skin.  
3. Carefully follow any instructions provided with the bottles of cleaning and  
sanitizing solution.  
4. Never run the icemaker when the water tank is empty.  
IMPORTANT  
1. The cleaning valve is used to allow solution flow to the inside of the  
evaporator during the cleaning and sanitizing operation. It should be closed  
for all icemaking operation. The compressor will not operate unless this  
valve is completely closed.  
ꢀ. To open the cleaning valve, the valve handle should be parallel to the valve  
body. To close the valve, the valve handle should be at a right angle to the  
valve body.  
CLOSED POSITION  
OPEN POSITION  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Cleaning Procedure  
1) Dilute ꢀ7 fl. oz. (800 ml) of recommended cleaner Hoshizaki "Scale Away" or  
"LIME-A-WAY" (Economics Laboratory, Inc.) with 5 gal. (19 l) of warm water.  
ꢀ) Remove all ice from the evaporator and the storage bin.  
Note: To remove cubes on the evaporator, turn off the power supply and turn it on  
after 3 minutes. The harvest cycle starts and the cubes will be removed from the  
evaporator.  
Cube Guide  
Separator  
3) Turn off the power supply.  
4) Remove the front panel, and then remove  
the insulation panel by first removing the  
thumbscrew, lifting up the panel slightly  
and pulling it towards you.  
Front  
Inside of Ice  
Dropping Hole  
5) Remove the cap located on the front  
bottom part of the ice dropping hole. Drain  
the water tank. See Fig. 5.  
6) Replace the cap in its correct position. Be  
careful not to cross thread it.  
Fig. 5  
Cap  
7) In bad or severe water conditions, clean the float switch assembly as described below.  
Otherwise, continue to step 8.  
a. Disconnect the vent tube and the flush tube from the top of the float switch, then  
remove the float switch assembly from the mounting bracket and remove the  
rubber boot from the bottom of the assembly.  
b. Remove the retainer rod from the bottom of the float switch assembly, then remove  
the float. Be careful not to bend the retainer rod excessively when removing it.  
c. Wipe down the float switch assembly's housing, shaft, float, and retainer rod with  
cleaning solution. Clean the inside of the rubber boot and hose with cleaning  
solution. Rinse the parts thoroughly with clean water.  
d. Reassemble the float switch assembly and replace it and the rubber boot in their  
correct positions. Reconnect the vent tube and the flush tube.  
8) Pour the cleaning solution into the water tank.  
9) Fully open the cleaning valve on the left side wall of the machine compartment.  
10) Move the control switch on the control box to the "WASH" position.  
11) Replace the insulation panel and the front panel in their correct positions.  
1ꢀ) Turn on the power supply to start the washing process.  
13) Turn off the power supply after 30 minutes.  
14) Remove the front panel and the insulation panel.  
15) Remove the cap located on the front bottom part of the ice dropping hole. Drain the  
water tank. Replace the cap and the insulation panel in their correct positions.  
16) Move the control switch to the "ICE" position.  
17) Close the cleaning valve.  
Note: The icemaker will not operate unless the cleaning valve is completely closed.  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
18) Replace the front panel in its correct position.  
19) Turn on the power supply to fill the water tank with water.  
ꢀ0) Turn off the power supply after 3 minutes.  
ꢀ1) Remove the front panel and fully open the cleaning valve.  
ꢀꢀ) Move the control switch to the "WASH" position.  
ꢀ3) Replace the front panel in its correct position.  
ꢀ4) Turn on the power supply to rinse off the cleaning solution.  
ꢀ5) Turn off the power supply after 5 minutes.  
ꢀ6) Remove the front panel and the insulation panel.  
ꢀ7) Remove the cap located on the front bottom part of the ice dropping hole. Drain the  
water tank. Replace the cap and the insulation panel in their correct positions.  
Note: Do not replace the insulation panel when you proceed to "ꢀ. Sanitizing  
Procedure."  
ꢀ8) Repeat steps 16 through ꢀ7 three more times to rinse thoroughly.  
Note: If you do not sanitize the icemaker, go to step 9 in "ꢀ. Sanitizing Procedure."  
2. Sanitizing Procedure - Following Cleaning Procedure  
1) Dilute ꢀ.5 fl. oz. (74 ml or 5 tbs) of a 5.ꢀ5% sodium hypochlorite solution (chlorine  
bleach) with 5 gal. (19 l) of warm water.  
ꢀ) Pour the sanitizing solution into the water tank.  
3) Replace the insulation panel and the front panel in their correct positions.  
Note: Make sure that the control switch is in the "WASH" position and the cleaning  
valve is open.  
4) Turn on the power supply to start the sanitizing process.  
5) Turn off the power supply after 15 minutes.  
6) Remove the front panel and the insulation panel.  
7) Remove the cap located on the front bottom part of the ice dropping hole. Drain the  
water tank. Replace the cap and the insulation panel in their correct positions.  
8) Repeat steps 16 through ꢀ7 in "1. Cleaning Procedure" two times to rinse thoroughly.  
9) Close the cleaning valve.  
10) Move the control switch to the "ICE" position.  
11) Replace the front panel in its correct position.  
1ꢀ) Clean the storage bin using a neutral cleaner. Rinse thoroughly after cleaning.  
13) Turn on the power supply to start the automatic icemaking process.  
8ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
B. Maintenance Instructions  
IMPORTANT  
This icemaker must be maintained individually, referring to the instruction  
manual and labels provided with the icemaker.  
1. Stainless Steel Exterior  
To prevent corrosion, wipe the exterior occasionally with a clean, soft cloth. Use a damp  
cloth containing a neutral cleaner to wipe off oil or dirt build up.  
2. Storage Bin and Scoop  
• Wash your hands before removing ice. Use the plastic scoop provided (bin accessory).  
• The storage bin is for ice use only. Do not store anything else in the storage bin.  
• Clean the scoop and the storage bin liner using a neutral cleaner. Rinse thoroughly  
after cleaning.  
3. Air Filters (self-contained air-cooled models)  
Plastic mesh air filters remove dirt and dust from the air, and keep the condenser from  
getting clogged. As the filters get clogged, the icemaker's performance will be reduced.  
Check the filters at least twice a month. When clogged, use warm water and a neutral  
cleaner to wash the filters.  
4. Condenser (self-contained and remote air-cooled models)  
Check the condenser once a year, and clean the coil if required by using a brush or  
vacuum cleaner. More frequent cleaning may be required depending on location.  
C. Preparing the Icemaker for Long Storage  
IMPORTANT  
When shutting off the icemaker for an extended time, drain out all water from  
the water tank and remove the ice from the storage bin. The storage bin should  
be cleaned and dried. Drain the icemaker to prevent damage to the water  
supply line at sub-freezing temperatures, using air or carbon dioxide. Shut off  
the icemaker until the proper ambient temperature is resumed.  
When the icemaker is not used for two or three days, it is sufficient to only move the control  
switch to the "OFF" position, unless the icemaker will be at sub-freezing temperatures.  
1. On water-cooled models only, first remove the water from the water-cooled  
condenser:  
1) Turn off the power supply and remove the front panel and right side panel.  
ꢀ) Close the condenser water supply line shut-off valve. If connected to a closed loop  
water supply, also close the condenser return outlet shut-off valve.  
3) Open the condenser water supply line drain valve. If connected to a closed loop water  
supply, also open the condenser return outlet drain valve.  
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line  
drain valve.  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer  
underneath the spring. While holding the valve open, blow out the condenser using the  
compressed air or carbon dioxide supply until water stops coming out.  
6) Close the drain valve(s) and replace the right side panel in its correct position.  
2. Remove the water from the icemaker water supply line:  
1) If you have not already done so, turn off the power supply and remove the front panel.  
ꢀ) Close the icemaker water supply line shut-off valve and open the icemaker water  
supply line drain valve.  
3) Allow the line to drain by gravity.  
4) Attach a compressed air or carbon dioxide supply to the icemaker water supply line  
drain valve.  
5) Make sure at least 3 minutes have elapsed since you turned off the power supply.  
Make sure the control switch is in the "ICE" position. Replace the front panel in its  
correct position and turn on the power supply.  
6) Blow the icemaker water supply line out using the compressed air or carbon dioxide  
supply.  
7) Close the icemaker water supply line drain valve.  
3. Drain the water tank:  
1) Turn off the power supply and remove the front panel. Move the control switch to the  
"OFF" position.  
ꢀ) Remove the insulation panel. Remove the cap located on the front bottom part of the  
ice dropping hole. Drain the water tank. See Fig. 6.  
3) Replace the cap and the insulation panel in their correct positions. Be careful not to  
cross thread the cap.  
4) Remove all ice from the storage bin. Clean the storage bin using a neutral cleaner.  
Rinse thoroughly after cleaning.  
5) Replace the insulation panel and the front panel in their correct positions.  
Cube Guide  
Separator  
Front  
Inside of Ice  
Dropping Hole  
Fig. 6  
Cap  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Stroller PD108195A User Manual
Grizzly Impact Driver H0582 User Manual
Grizzly Treadmill G0695 User Manual
HannsG Computer Monitor HW216 User Manual
Harbor Freight Tools Sander 69474 User Manual
Hasbro Games 20574 20570 User Manual
HP Hewlett Packard Mouse CQ45 323TX User Manual
HP Hewlett Packard Switch J3250M User Manual
Hunter Fan Fan 23970 User Manual
Husqvarna Trimmer 325R User Manual