Honeywell Water Dispenser F76S User Manual

F76S Water Filters and  
MV876B Automatic-Backwash Controls  
PRODUCT DATA  
FEATURES  
F76  
Built-in backwash impeller provides efficient cleaning  
with supply pressures as low as 22 psi.  
Increased flow capacity on 1/2 in. to 1-1/4 in. models  
provides lower pressure drop.  
Robust backwash mechanism.  
MV876B1018  
(Bayonet fitting  
for F76S)  
No shut-off or disassembly is required for cleaning.  
During backwash, the F76S continues to supply  
filtered water without interruption through a secondary  
screen.  
Memory ring indicates when the next manual  
backwash is due.  
MV876  
MV876B1018 bayonet fitting simplifies upgrade to  
automatic backwash.  
16 field-selectable backwash intervals (from every four  
minutes to once every three months) on the MV876B  
eliminate need for external timer.  
Connections for external control on the MV876B  
provide for use in automated systems and differential  
pressure control.  
MV876B1000  
(for F76A,G)  
MV876B can be turned manually to initiate backwash.  
F76S  
Battery (AA) backup to insure completion of backwash  
cycle in spite of power loss.  
APPLICATION  
The F76S is a high flow capacity water filter used at point-of-  
entry (POE) to remove sediment and debris from residential or  
commercial water systems. Used as a prefilter, the F76S  
protects elements of the water system, including specialized  
treatment devices such as taste/odor or reverse osmosis  
(R/O) or other common fixtures and appliances. The flow,  
filtering capacity, and ease of cleaning make the F76S the  
ideal filter for the most demanding applications.  
Contents  
The MV876 Automatic-Backwash Control is available as an  
accessory. This control is fitted to the drain valve and is  
programmed by the user to automatically perform the back-  
wash function according to the desired interval.  
® U.S. Registered Trademark  
Copyright © 1999 Honeywell Inc. • All Rights Reserved  
62- 3015- 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
Accessories (continued):  
AF11S-112C Screen insert (50 microns) for 1-1/2 to 2 in. F76S.  
AF11S-1D Screen insert (200 microns) for 1/2 to 1-1/4 in. F76S.  
AF11S-112D Screen insert (200 microns) for 1-1/2 to 2 in. F76S.  
KF11S-1A Clear Plastic Filter Sump Kit for 1/2 to 1-1/4 in. F76S.  
KF11S-112A Clear Plastic Filter Sump Kit for 1-1/2 to 2 in. F76S.  
FT09RS-1A Bronze Filter Sump Kit for 1/2 to 1-1/4 in. F76S.  
FT09RS-112A Bronze Filter Sump Kit for 1-1/2 to 2 in. F76S.  
KH11S-1A Ball Valve Assembly for 1/2 to 2 in. F76S.  
M76K-200 Pressure Gauge, 200 psi maximum.  
M76K-400 Pressure Gauge, 400 psi maximum.  
U76S5007 Sweat Tailpiece for any 1/2 in. F76.  
U76S5015 Sweat Tailpiece for any 3/4 in. F76.  
U76S5023 Sweat Tailpiece for any 1 in. F76.  
U76S5031 Sweat Tailpiece for any 1-1/4 in. F76.  
U76S5039 Sweat Tailpiece for any 1-1/2 in. F76.  
U76S5047 Sweat Tailpiece for any 2 in. F76.  
U76T1004 Threaded Tailpiece for any 1/2 in. F76.  
U76T1014 Threaded Tailpiece for any 3/4 in. F76.  
U76T1022 Threaded Tailpiece for any 1 in. F76.  
U76T1030 Threaded Tailpiece for any 1-1/4 in. F76.  
U76T1038 Threaded Tailpiece for any 1-1/2 in. F76.  
U76T1046 Threaded Tailpiece for any 2 in. F76.  
ZR10K-1 Sump Wrench for any 1 in. or 1-1/4 in. F76.  
ZR10K-112 Sump Wrench for any 1-1/2 in. or 2 in. F76.  
ZR10K-12 Sump Wrench for 1/2 in. and 3/4 in. F76A,G.  
ZR10K-34 Sump Wrench for 1/2 in. and 3/4 in. F76S.  
100  
150  
200  
50  
0
Honeywell  
Braukmann  
1
1
1
1
1
2
l
SIZE  
L
D
H
h
WEIGHT  
6.4 (2.9)  
6.4 (2.9)  
6.8 (3.1)  
7.3 (3.3)  
8.8 (4.0)  
10.6 (4.8)  
1/2 INCH  
3/4 INCH  
1 INCH  
6-11/16 (170)  
7 (178)  
4-5/16 (110)  
4-5/16 (110)  
5-1/8 (130)  
3-13/16 (97)  
3-13/16 (97)  
3-13/16 (97)  
3-13/16 (97)  
4-3/4 (119)  
4-3/4 (119)  
17-11/16 (449)  
17-11/16 (449)  
17-7/8 (453)  
13-13/16 (350)  
13-13/16 (350)  
13-13/16 (350)  
13-13/16 (350)  
16-7/16 (417)  
16-7/16 (417)  
H
8-1/4 (209)  
8-3/4 (222)  
9-11/16 (246)  
10-1/2 (267)  
1-1/4 INCH  
1-1/2 INCH  
2 IINCH  
5-1/8 (130)  
17-7/8 (453)  
h
5-15/16 (150)  
5-15/16 (150)  
20-15/16 (532)  
20-15/16 (532)  
1
2
DIMENSIONS IN INCHES AND (MILLIMETERS).  
WEIGHT IN POUNDS AND (KILOGRAMS).  
D
l
M18084  
L
Fig. 1. F76S Dimensions.  
Table 2. MV876B Timer Selections.  
Program Value Backwash Interval  
Table 1. Capacity in Gallons Per Minute (gpm).  
Pipe Size (in.)  
Pressure Drop  
1
4 minutes  
8 minutes  
16 minutes  
32 minutes  
1 hour  
(psi) Across Filter 1/2 3/4  
1
18  
25  
31  
36  
40  
70  
1-1/4 1-1/2  
2
30  
42  
51  
59  
66  
114  
2
1
8
11  
16  
19  
22  
25  
43  
20  
28  
35  
40  
45  
78  
26  
36  
44  
51  
57  
99  
3
2
12  
14  
16  
18  
32  
4
3
5
4
6
2 hours  
5
7
4 hours  
15  
8
8 hours  
Flow Volume for 15 sec backwash at 60 psi inlet  
3.2 3.2 4.0 4.0  
9
17 hours  
34 hours  
3 days  
4.7  
4.7  
10  
11  
12  
13  
14  
15  
16  
NOTE: C is equal to capacity at 1 psi pressure drop.  
v
6 days  
11 days  
23 days  
45 days  
3 months  
3
62-3015—4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
An increased pressure drop across the filter results when  
PLANNING THE INSTALLATION  
higher velocities are maintained to increase the capacity  
through any given size filter. Severe pressure drops will be  
encountered as capacity approaches that of the pipe size. To  
ensure the backwash cycle operates properly and cleaning  
action is not reduced, follow all recommendations in Fig. 2.  
Refer to Fig. 2a for an ideal installation.  
The F76S should be sized based on the required flow rate and  
the resulting pressure drop across the filter. As a guideline for  
most applications, the F76S should be sized to avoid pressure  
drops exceeding 3 psi.  
EXAMPLE:What size F76S is required to provide a flow  
rate of 30 gpm? Reading across Table 1 at  
NOTE: All filter installations are different. The size, type, and  
amount of dirt and debris and the flow rate must  
3 psi pressure drop, a 1 in. filter can provide 31  
gpm without exceeding 3 psi pressure drop.  
always be considered when choosing a screen and  
deciding to install multiple F76 Water Filters in parallel.  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
100  
150  
50  
200  
0
Honeywell  
Brau  
nn  
kma  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
M16488  
M16490  
M16489  
Fig. 2a. Ideal F76S installation. A funnel  
mounted directly under the backwash downsized. Do not use 1/4 or 3/8 inch  
Fig. 2b. Ensure the inlet pipe is not  
Fig. 2c. Ensure the backwash outlet  
pipe is not downsized, long, or  
port is the best installation layout.  
tubing on 1/2 or 3/4 inch models.  
crimped. Instead, install a short  
oversized pipe on the backwash outlet.  
Do not use a low capacity solenoid  
valve to automate the backwash cycle.  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
M16492  
M16478  
M16491  
Fig. 2d. Ensure the backwash outlet is Fig. 2e. Ensure the F76S is not used  
Fig. 2f. Ensure the F76S is not  
not raised above the F76S. If the  
backwash outlet must be raised above  
the F76S, increase inlet pressure 5 psi  
for every 10 feet that it is raised.  
with an undersized pump. An  
undersized pump may not provide  
proper pressure or flow.  
installed in a bypass across a pump.  
Fig. 2. Installation recommendations.  
62-30154  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
3.  
Install pressure gauge in the F76S center port (see Fig. 4).  
Commercial and Industrial Installations  
(1-1/2 and 2 in. models)  
IMPORTANT  
When using an MV876, stop here and install the MV876.  
Commercial and industrial installations have high flow  
requirements. For proper operation, limit flow across the F76S  
screen. For example, a two-inch pipe may have a 120 gpm flow  
at 12 fps linear velocity across a clean screen. High linear  
velocity impacts dirt deeply into the screen, making it difficult to  
backwash and causing the screen to plug up quickly. In these  
situations, install multiple F76 filters in parallel. See Fig. 3.  
4.  
5.  
6.  
Ensure the F76S air vent is open.  
Slowly open the water supply valve.  
Once the F76S sump fills with water, close the air vent  
and fully open the water supply valve.  
1
100  
150  
100  
150  
50  
200  
0
Honeywell  
Braukmann  
50  
1
200  
0
Honeywell  
Braukmann  
1
100  
150  
50  
200  
0
Honeywell  
Braukmann  
1
100  
150  
INLET  
PIPE  
50  
200  
0
Honeywell  
Braukmann  
1
ISOLATION VALVE.  
M17360  
Fig. 3. Parallel installation of three F76S Water Filters.  
Advantages of parallel installation:  
Increased cleaning capacity. Backwash interval is reduced.  
Elimination of system downtime. Can backwash one F76S  
while the others maintain required flow.  
Another consideration in commercial and industrial  
installations is the backwash interval. Because of the high flow  
requirements, screens need cleaning on a regular basis. An  
MV876 Automatic-Backwash Control can be installed to back-  
wash the F76S automatically.  
M16480  
Fig. 4. Installing the F76S.  
INSTALLATION  
MV876  
When adding an MV876 to an existing F76, the procedure can  
vary depending on the F76 model.  
CAUTION  
Equipment Damage Hazard.  
Excessive pressure or temperature can damage  
the device.  
Installation on an F76S  
1.  
2.  
3.  
Open the backwash outlet ball valve.  
Remove the backwash outlet handle.  
Install the MV876. See Fig. 5 and 6.  
Ensure water temperature and pressure are below  
maximum ratings specified.  
NOTE: When you rotate the MV876, it closes the  
backwash outlet ball valve.  
CAUTION  
Equipment Damage Hazard.  
Excessive heating can damage internal parts.  
Before sweating, separate the tailpieces and nuts from  
the filter body.  
4.  
5.  
6.  
Ensure the F76S air vent is open.  
Slowly open the water supply valve.  
Once the F76S sump fills with water, close the air vent  
and fully open the water supply valve.  
Program the desired backwash interval by pushing the  
program button until the desired interval number  
appears in the display.  
7.  
F76S  
When installing an F76S, use the following procedure:  
1.  
2.  
Shut off water supply by closing the water supply valve.  
Install the F76S in the water line with the arrow pointing  
in the direction of water flow.  
5
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
M V 8 7 6 B  
M16481  
Fig. 5. Installing the MV876.  
MV876B  
M16483  
Fig. 6. Final position of MV876 and F76S components.  
Installation on an F76A  
1.  
2.  
Close the water supply valve to shut off water supply.  
Drain all water from the F76A by opening both a fixture  
downstream, and the backwash outlet; loosen the air  
vent on top of the F76A.  
M17357  
3.  
4.  
Remove the backwash outlet (see Fig. 7):  
a. Grip the F76A fixture with a wrench.  
b. Using another wrench, turn the outlet  
Fig. 7. Installing the MV876B on the F76A.  
counterclockwise  
(viewed from the bottom).  
Connect the MV876 to the F76A (see Fig. 7):  
a. Ensure a plastic washer is placed between the filter  
sump and the backwash outlet.  
b. Connect the externally threaded portion of the  
MV876 backwash outlet to the internally threaded  
F76A connection.  
Set Pressure Gauge Needles  
The black needle on the pressure gauge measures the F76S  
outlet pressure. When the F76S is running with clean screens,  
there is a small pressure drop across the F76S (3 psi at  
maximum recommended flow).  
5.  
Connect the hose fitting to the MV876 backwash outlet  
The red needle is a stationary needle that helps monitor back-  
wash interval.  
NOTE: The following assumes a constant inlet pressure. If  
inlet pressure is variable, another gauge on the inlet  
piping, or the air vent will provide more information  
regarding actual pressure differential.  
1.  
2.  
Backwash F76S once to ensure the screens are clean.  
With the F76S in operation, rotate the clear gauge cover  
to set the red needle to match the black needle.  
62-30154  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
4.  
5.  
6.  
7.  
As the F76S operates, screens become plugged. Backwash  
the F76S when the black needle measures about five psi  
lower than the red needle. However, each installation is  
different. Residential applications can require backwash only  
once a week, or once every few weeks. Industrial applications  
can require backwash several times a day. To determine the  
backwash interval, see Determining Backwash Interval in the  
Operation section.  
Insert a new 800 mA fuse (see Fig. 10).  
Replace the cover.  
Replace and tighten the four housing screws.  
Reconnect the power supply.  
NOTE: For residential applications, backwash the F76S  
once a week regardless of need is an excellent  
guideline to follow to ensure F76S peak operating  
efficiency.  
Fitting Batteries and Fuses  
The batteries (not included) provide power to the MV876 in  
the event of a power loss. This is desirable especially when  
power loss occurs during the reverse rinsing cycle. To provide  
this, the MV876 requires four AA alkaline batteries. Install  
these batteries in the cover of the MV876:  
MV876B  
CAUTION  
Electrical Shock or Equipment Damage Hazard.  
Can shock individuals or short equipment  
circuitry.  
M17352  
Disconnect power supply before installation.  
Fig. 8. Removing the MV876 cover.  
1.  
Unscrew the four housing screws and set them aside.  
IMPORTANT  
Ensure that the connecting cable is protected from  
damage while the MV876 cover is loose.  
2.  
3.  
4.  
5.  
Remove the MV876 cover (see Fig. 8).  
Insert four AA alkaline batteries (see Fig. 9).  
Replace the cover.  
MV876B  
Replace and tighten the four housing screws.  
NOTES:  
1.  
To avoid unnecessary battery drainage, connect  
the MV876 to power as soon as possible after  
inserting new batteries.  
M17353  
2.  
To ensure the availability of battery power, replace  
the batteries after a power loss.  
Fig. 9. Installing batteries in the MV876.  
If the 800 mA fuse blows, replace it:  
CAUTION  
Electrical Shock or Equipment Damage Hazard.  
Can shock individuals or short equipment circuitry.  
Disconnect power supply before installation.  
1.  
Unscrew the four housing screws and set them aside.  
IMPORTANT  
Ensure that the connecting cable is protected from  
damage while the MV876 cover is loose.  
M17351  
2.  
3.  
Remove the MV876 cover (see Fig. 8).  
Remove and discard the old fuse (see Fig. 10).  
Fig. 10. Replacing the MV876 fuse.  
7
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
While the upper screen filters the water. Some of the water  
WIRING  
passing through the upper screen is directed through the  
impeller to backwash the lower screen (from inside to out-  
side). Remaining filtered water meets the needs downstream.  
CAUTION  
Water jets from the rapidly spinning impeller enhance the  
reversed water flow. The reverse flow removes trapped  
sediment and debris from the lower filter. This sediment drains  
out the backwash outlet. Cleaning the lower screen requires  
approximately 20 seconds. See Fig. 12b.  
Electrical Shock or Equipment Damage Hazard.  
Can shock individuals or short equipment circuitry.  
Disconnect power supply before installation.  
IMPORTANT  
All wiring must comply with applicable codes and  
ordinances.  
The F76S requires no maintenance if backwashed at the  
proper interval.  
MV876  
Determining Backwash Interval  
1.  
Mount the AT140A1034 Transformer and wire as shown  
in Fig. 11.  
All F76S applications are different and require backwashing at  
different intervals. Backwash interval is directly proportional to:  
The level and type of sediment in the local water supply.  
Water usage.  
2.  
3.  
4.  
Ensure the F76 air vent is open.  
Slowly open the water supply valve.  
Once the F76 sump fills with water, close the air vent  
EXAMPLE:In northern states, water usage is higher in  
summer months than in winter months due to  
lawn watering in the summer. Therefore, the  
F76S should be backwashed more often in  
and fully open the supply valve.  
5.  
Reconnect power to the system. When the system is  
powered, the MV876 will run through one backwash  
cycle (approximately 20 seconds).  
summer months than in winter months.  
By accurately determining a proper backwash interval, the  
F76S will operate at a higher efficiency.  
6.  
7.  
Set MV876 backwash interval to the desired setting.  
See the Operation section.  
Check MV876 operation by interrupting primary power  
to the transformer. When power is switched back on, the  
MV876 will backwash the F76 once.  
To determine the F76S backwash interval:  
1.  
Backwash the system once to ensure the lower screen  
is clean.  
MV876  
2.  
The black pressure gauge needle measures outlet pressure.  
With clean screens, inlet pressure equals outlet pressure  
because of negligible pressure drop across the F76S.  
Rotate the clear gauge cover to set the red needle to  
match the black needle.  
Record the date and time.  
Monitor the F76S closely. Over time, the screens  
become obstructed and outlet pressure drops.  
3.  
4.  
5.  
1
L1  
(HOT)  
L2  
NOTE: The F76S requires a backwash when the black  
needle measures about five psi lower than the  
red needle. Installations do vary and can  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
M16484  
require a backwash at different times.  
Fig. 11. Wiring diagram for F76 with MV876.  
6.  
7.  
Record date and time again. Residential applications  
can require an F76S backwash only once every few  
weeks to once per week. Industrial applications can  
require an F76S backwash several times a day.  
Backwash the F76S regularly at the determined interval.  
A backwash can be done manually or automatically.  
a. Manual Backwash: Open the backwash outlet for  
approximately 30 seconds.  
OPERATION  
The F76S Water Filter removes sediment and debris from the  
water using an upper and lower screen. During normal  
operation, no water passes through the upper screen. Water  
is filtered as it flows through the lower screen. (See Fig. 12a.)  
With continued operation, the lower screen becomes  
obstructed, reducing efficiency and creating a pressure drop  
across the F76S. Backwash the F76S periodically. Suggested  
interval is either once per week (residential applications) or  
when the black needle measures about five psi lower than the  
red needle.  
NOTE: The amount of time required varies among  
installations. However, 30 seconds is the  
standard guideline to clean the lower screen.  
b. Automatic Backwash: Install an MV876 Automatic-  
Backwash Valve and select the backwash interval.  
See the Operation section.  
To backwash the F76S manually, open the backwash outlet  
on the F76S bottom. This forces the entire filter insert down-  
wards. Water flow to the lower screen outer side is blocked.  
The upper filter removes sediment and debris from the water.  
62-30154  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
a. F76S DURING NORMAL FLOW  
b. F76S DURING BACKWASH CYCLE  
SCREEN  
BACKWASH  
IMPELLER  
ENLARGED  
ENLARGED  
CROSS SECTION  
CROSS SECTION  
DEBRIS AND  
SEDIMENT  
M17362  
Fig. 12. Water flow through the F76S.  
9
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
F76S REPLACEMENT PARTS LIST (SEE FIG. 13)  
PARTS AND ACCESSORIES FOR NEW STYLE F76S FILTERS:  
Description  
(A) Pressure Gauge (new style F76S only)  
Standard Pressure (230 psi)  
High Pressure (400 psi)  
(B) Tailpieces (same for new and old style)  
Sweat  
1/2 inch  
3/4 inch  
1 inch  
1-1/4 inch  
1-1/2 inch  
2 inch  
M76K-200 M76K-200 M76K-200 M76K-200 M76K-200  
M76K-400 M76K-400 M76K-400 M76K-400 M76K-400  
M76K-200  
M76K-400  
U76S5007 U76S5015 U76S5023 U76S5031 U76S5039  
U76T1004 U76T1014 U76T1022 U76T1030 U76T1038  
U76S5047  
U76T1046  
N/A  
Threaded (shown)  
(C) Union Nuts  
N/A  
N/A  
N/A  
N/A  
N/A  
(D) Tailpiece Gaskets (sold in packs of 10) 0901444  
0901444  
N/A  
0901445  
N/A  
0901446  
N/A  
0901447  
N/A  
0901448  
N/A  
(E) Guide Barrel  
N/A  
Screen Insert Complete (new style only)  
20 Micron  
50 Micron  
100 Micron  
200 Micron  
AF11S-1B AF11S-1B AF11S-1B AF11S-1B AF11S-112B  
AF11S-1C AF11S-1C AF11S-1C AF11S-1C AF11S-112C  
AF11S-1A AF11S-1A AF11S-1A AF11S-1A AF11S-112A  
AF11S-1D AF11S-1D AF11S-1D AF11S-1D AF11S-112D  
AF11S-112B  
AF11S-112C  
AF11S-112A  
AF11S-112D  
Includes:  
(F) Barrel O Ring  
(G) Impeller and Screen Assembly  
(J) Chamber O Ring  
(H) Base Spring  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
(J) Chamber O Ring (sold in packs of 10) 0900747  
Filter Sump Kits (new style only)  
0900747  
0900747  
0900747  
0900748  
0900748  
Clear Plastic  
Bronze  
KF11S-1A KF11S-1A KF11S-1A KF11S-1A KF11S-112A  
KF11S-112A  
FT09RS-1A FT09RS-1A FT09RS-1A FT09RS-1A FT09RS-112A FT09RS-112A  
Includes:  
(J) Chamber O-Ring  
(K) Sump  
(L) Ball Valve O-Ring  
(M) Integrated Ball Valve  
(N) Memory Ring  
(P) Ball Valve Bowl  
(Q) Ball Valve Knob  
(R) Joint Ring Seal  
(S) Drain Connector  
Ball Valve Assembly (new style only)  
Includes:  
KH11S-1A KH11S-1A KH11S-1A KH11S-1A KH11S-1A  
KH11S-1A  
ZR10K-112  
(M) Ball Valve  
(L) Ball Valve O-Ring  
Sump Wrench  
ZR10K-34 ZR10K-34 ZR10K-1  
ZR10K-1  
ZR10K-112  
N/A = Part number not available at time of printing.  
a
Sold in packs of ten.  
62-30154  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
A
100  
150  
50  
C
B
200  
0
Honeywell  
Braukmann  
B
C
D
K
D
E
F
L
M
G
N
P
H
R
J
Q
OR  
T
S
M18073  
Fig. 13. F76S exploded view. Parts are keyed to F76S Replacement Parts List.  
11  
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
F76A,G REPLACEMENT PARTS LIST (SEE FIG. 14)  
Description  
(A) Pressure Gauge  
1/2 inch  
3/4 inch  
1 inch  
1-1/4 inch  
1-1/2 inch  
2 inch  
F76A & F76B  
F76G & F76H  
0901537  
5267400  
0901537  
5267400  
0901537  
5267400  
0901537  
5267400  
0901537  
5267400  
0901537  
5267400  
(B) Tailpieces (for new and old style)  
Sweat  
U76S5007  
U76T1004  
N/A  
U76S5015  
U76T1014  
N/A  
U76S5023  
U76T1022  
N/A  
U76S5031  
U76T1030  
N/A  
U76S5039  
U76T1038  
N/A  
U76S5047  
U76T1046  
N/A  
Threaded (shown)  
(C) Union Nuts  
a
0901444  
0901444  
0901445  
0901446  
0901447  
0901448  
(D) Tailpiece Gaskets  
(E) Ring (plastic)  
Screen Kit  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
20 Micron  
QF76Q2007 QF76Q2007 QF76Q2015 QF76Q2015 QF76Q2023 QF76Q2023  
QF76R2030 QF76R2030 QF76R2038 QF76R2038 QF76R2046 QF76R2046  
QF76S2051 QF76S2051 QF76S2059 QF76S2059 QF76S2067 QF76S2067  
QF76T2074 QF76T2074 QF76T2082 QF76T2082 QF76T2090 QF76T2090  
50 Micron  
100 Micron  
200 Micron  
Includes:  
(F) Upper Screen  
(H) Barrel O Ring  
(L) Lower Screen  
Internal Seal Kit  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Includes: (H) Barrel O Ring  
(K) Screen Seal  
(Q) Chamber O Ring  
(S) Joint Ring Seal  
Filter Insert Kit  
QF76G2053 QF76G2053 QF76G2061 QF76G2061 QF76G2069 QF76G2069  
(F) Upper Screen  
(G) Upper Guide Barrel  
(H) Barrel O Ring  
(J) Lower Guide Barrel  
(K) Screen Seal  
(L) Lower Screen  
(M) Impeller  
(N) Lower Screen Support  
(P) Conical Base Spring  
(Q) Chamber O Ring  
Filter Sump Kits  
Clear Plastic  
b
b
PF76C1007 PF76C1007 PF76C1015 PF76C1015  
PF76C1023 PF76C1023  
Bronze  
202913  
202913  
202914  
202914  
202915  
202915  
Includes:  
(Q) Chamber O-Ring  
(R) Sump  
(S) Joint Ring Seal  
(T) Drain Tap (Backwash Outlet)  
(U) Red Handle and Screw  
b
b
(U) Red Handle and Screw  
Sump Wrench  
251550  
251550  
251550  
251550  
251550  
251550  
ZR10K-12  
ZR10K-12  
ZR10K-1  
ZR10K-1  
ZR10K-112  
ZR10K-112  
N/A = Part number not available at time of printing.  
a
Sold in packs of ten.  
b
PF76C1023 does not include drain tap and red handle and screw.  
62-30154  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS  
A
100  
150  
50  
C
B
200  
0
Honeywell  
Braukmann  
B
C
N
D
E
F
D
G
P
Q
H
J
K
R
L
S
M
U
T
M746  
Fig. 14. F76A,G exploded view. Parts are keyed to F76A,G Replacement Parts List.  
13  
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
62-30154  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
62-30154  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
P.O. Box 524  
Minneapolis, MN 55408-0524  
M2H 3N7  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
62-30154 B.B. Rev. 10-99  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Swing PD162286B User Manual
Graco Car Seat PD214124A User Manual
Harbor Freight Tools Grinder 94186 User Manual
Harbor Freight Tools Scale 98059 User Manual
Heath Zenith Door 598 1109 05 User Manual
HP Hewlett Packard Photo Printer 470 series User Manual
HP Hewlett Packard Printer 175X User Manual
HP Hewlett Packard Printer WP36 50 User Manual
HP Hewlett Packard Switch 1410 16G User Manual
Husqvarna Chainsaw 136 User Manual