Honeywell Universal Remote W7761A User Manual

Excel 10 W7761A Remote Input/Output  
Device  
CONTENTS  
Table of Contents  
Introduction  
...........................................................................................................................  
Description of Devices .......................................................................................  
Control Application.............................................................................................  
Control Provided.................................................................................................  
Products Covered...............................................................................................  
Organization of Manual ......................................................................................  
Applicable Literature ..........................................................................................  
Product Names ..................................................................................................  
Agency Listings..................................................................................................  
Abbreviations and Definitions.............................................................................  
Construction.......................................................................................................  
Controllers .....................................................................................................  
4
5
5
6
6
6
6
7
7
9
9
Performance Specifications...................................................................... 12  
Wall Modules................................................................................................. 15  
Configurations.................................................................................................... 16  
Mixed-Output-Type Control ........................................................................... 17  
Occupancy Sensor ........................................................................................ 17  
Window Open/Closed Digital Input................................................................ 17  
Wall Module Options ..................................................................................... 17  
Dirty Filter Monitor ......................................................................................... 17  
Indoor Air Quality (IAQ) Override................................................................... 17  
Application Steps  
...........................................................................................................................  
Overview ............................................................................................................ 18  
Step 1. Plan The System.................................................................................... 18  
Step 2. Determine Other Bus Devices Required................................................ 19  
Step 3. Lay Out Communications and Power Wiring......................................... 19  
E-Bus Layout................................................................................................. 19  
Power Wiring................................................................................................. 21  
Power Budget Calculation Example:......................................................... 21  
Line Loss: ................................................................................................. 22  
Step 4. Prepare Wiring Diagrams ...................................................................... 24  
General Considerations................................................................................. 24  
W7761A Devices........................................................................................... 24  
E-Bus Termination Module............................................................................ 30  
Step 5. Order Equipment.................................................................................... 33  
Step 6. Configure Devices.................................................................................. 36  
Step 7. Troubleshooting..................................................................................... 36  
Troubleshooting Excel 10 Controllers and Wall Modules.............................. 36  
Temperature Sensor and Setpoint Potentiometer Resistance Ranges......... 36  
Alarms ........................................................................................................... 36  
Broadcasting the Service Message............................................................... 37  
W7761A Controller Status LEDs................................................................... 37  
T7780 DDWM Bypass Pushbutton................................................................ 38  
List of Figures  
...........................................................................................................................  
Fig. 1. Typical system overview. ........................................................................  
Fig. 2. Typical W7761A control application........................................................  
2
4
5
Fig. 3. Excel 10 W7761A Remote I/O Device. ................................................... 10  
Fig. 4. W7761A construction.............................................................................. 11  
74-2699  
U.S. Registered Trademark  
Copyright 1998 Honeywell Inc. All Rights Reserved  
LonWorks LonMark and LonMark logo are Registered  
Trademarks of Echelon Corporation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
INTRODUCTION  
Description of Devices  
The W7761A, Excel 10 Remote Input/Output device, provides auxiliary inputs and outputs for use with an Excel 10 Zone  
®
®
Manager and Excel 10 controllers over the Echelon LonWorks E-Bus. These I/O points are configured with the E-Vision  
®
®
tool. The W7761A device uses Echelon LonWorks communication technology and a new free topology twisted pair  
transceiver (FTT) for greater network installation flexibility. The Excel 10 RIO device can be combined with the Excel 10 Zone  
Manager (FTT), other Excel Controllers, and the Excel Building Supervisor, to provide a complete and low cost control solution  
for small to large commercial buildings.  
The Q7750A Excel 10 Zone Manager is a communications interface that allows devices on the E-Bus network to communicate  
with devices on the standard EXCEL 5000® System C-Bus. Fig. 1 shows an overview of a typical system layout. The Q7750A  
also provides some control and monitoring functions.  
Q7752A  
FTT E-BUS  
SERIAL  
C-BUS COMMUNICATION NETWORK  
ADAPTER  
EXCEL 10  
Q7750A  
PERSONAL COMPUTER TOOLS  
E-VISION  
CARE  
FTT ZONE  
MANAGER  
EXCEL 500  
EXCEL BUILDING SUPERVISOR  
C-BUS TO E-BUS  
INTERFACE DEVICE  
Q7740A  
2-WAY  
REPEATER  
FTT E-BUS COMMUNICATIONS NETWORK  
FTT E-BUS COMMUNICATIONS NETWORK  
EXCEL 10  
W7750B  
CVAHU  
CONTROLLER  
Q7751A  
FTT  
E-BUS  
ROUTER  
FTT E-BUS  
COMMUNICATIONS  
NETWORK  
EXCEL 10  
T7780  
31  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
EXCEL 10 W7751F  
DIGITAL  
DISPLAY  
WALL  
18  
17  
16  
PANEL PLENUM  
MOUNT VERSION  
VARIABLE AIR  
VOLUME  
MODULE  
CONTROLLER  
EXCEL 10  
T7770E  
WALL  
MODULE  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
J3  
EXCEL 10  
REMOTE  
INPUT/  
OUTPUT  
DEVICE  
31  
31  
30  
30  
29  
29  
28  
28  
27  
27  
26  
26  
25  
24  
25  
24  
24  
24  
23  
23  
22  
22  
21  
21  
20  
20  
24  
19  
DI-4  
24  
19  
DI-4  
18  
18  
GND  
GND  
17  
17  
DI-3  
DI-3  
DI-2  
DI-2  
GND  
VAC  
COM  
1
OUT  
2
OUT  
16  
8
OUT  
GND  
VAC  
COM  
1
OUT  
2
OUT  
16  
8
OUT  
DI-1  
3
OUT  
DI-1  
3
OUT  
VA  
4
OUT  
VA  
4
OUT  
C
5
OUT  
C
5
OUT  
6
OUT  
6
OUT  
7
OUT  
7
OUT  
EXCEL 10 W7752 FTT FAN  
COIL UNIT CONTROLLER  
70  
75  
80  
85  
65  
60  
55  
auto  
0
1
E
GND  
E
GND  
LED  
2
LED  
2
BYP  
BYP  
ASS  
ASS  
SNSR GND  
SNSR GND  
SET  
6
SET  
6
PT AI-1  
OHM  
PT AI-1  
OHM  
GND  
8
GND  
8
A1-2  
A1-2  
AI-3  
AI-3  
GND  
11  
GND  
11  
AI-4  
V/mA  
AI-4  
V/mA  
22VDC  
OUT  
22VDC  
OUT  
1
OHM  
E-B  
14  
1
OHM  
E-B  
14  
V/mA  
U
S
V/mA  
U
S
E
-
B
E
-
B
3
US  
CK  
3
US  
CK  
4
5
4
5
7
7
JA  
JA  
9
9
10  
10  
12  
12  
13  
13  
15  
15  
J3  
J3  
EXCEL 10 W7753A UNIT  
VENTILATOR CONTROLLER  
EXCEL 10 T7770  
WALL MODULE  
M12884  
Fig. 1. Typical system overview.  
3
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Control Application  
The W7761A, Excel 10 Remote Input/Output device, provides auxiliary inputs and outputs for use with an Excel 10 Zone  
®
®
Manager and Excel 10 controllers over the Echelon LonWorks E-Bus. The W7761A Remote Input/Output Device can be  
connected to outdoor air temperature and humidity sensors that can be used by other Excel 10 controllers on the E-Bus or  
Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the controllers to use their physical  
inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control. The W7761A can be used to  
average many space temperature sensors that are located in a zone that is controlled by the W7750 Constant Volume AHU  
Controller. The W7761A device has 8 Digital Outputs which may be Discrete, Modulating or Floating. For example, this allows  
the control of lighting zones, miscellaneous exhaust or ventilation fans, miscellaneous pumps, and can enable freeze  
protection. See Fig. 2.  
OA  
HUMIDITY  
MISC.  
FANS  
PUMPS  
EXCEL 10  
W7761A  
REMOTE  
INPUT/OUTPUT  
OA  
TEMPERATURE  
LIGHTING  
CONTROL  
OCCUPANCY  
SENSOR  
EXCEL 10 T7770  
WALL MODULE  
M12885  
WINDOW CONTACT  
Fig. 2. Typical W7761A control application.  
Control Provided  
The W7761A was not intended to control staged or modulating heating/cooling coils, mixed air economizer dampers, or system  
fan/heat pump units. The W7761A contains inputs and outputs, but no control software. All control that would be associated  
with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable  
for VAV control, temperature control, or any control function that would require less than a 30 second update rate.  
Products Covered  
This System Engineering Guide describes how to apply the W7761A Excel 10 Remote Input/Output Device and related  
accessories to typical applications. The specific devices covered include:  
W7761A Remote I/O device.  
T7770 A through D Wall Modules.  
Q7750A Excel 10 Zone Manager.  
Q7751A Router (FTT to FTT only).  
Q7752A Serial Interface Adapter.  
Q7740A,B Repeaters (2-way and 4-way).  
209541B FTT Termination Module.  
Organization of Manual  
This manual is divided into three basic parts: the Introduction, the Application Steps, and the Appendices that provide  
supporting information. The Introduction and Application Steps 1 through 5 provide the information needed to make accurate  
material ordering decisions. Application Step 6 and the Appendices include configuration engineering that can be started using  
Excel E-Vision PC Software after the devices and accessories are ordered. Application Step 7 is troubleshooting.  
The organization of the manual assumes a project is being engineered from start to finish. If an operator is adding to, or is  
changing an existing system, the Table of Contents can provide the relevant information.  
Applicable Literature  
The following list of documents contains information related to the Excel 10 W7761 Remote I/O Device and the EXCEL 5000®  
System in general.  
Form No.  
Title  
4
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
74-2698  
74-2956  
74-2697  
74-2955  
74-2950  
74-2952  
74-2954  
74-2858  
Excel 10 W7761A Device Specification Data  
Excel 10 W7750A,B Controller Specification Data  
T7770A through G Wall Module Specification Data  
T7780 Digital Display Wall Module Specification Data  
Excel 10 Q7750A, Zone Manager Specification Data  
Excel 10 Q7751A Router Specification Data  
Excel 10 Q7752A Serial Interface Specification Data  
Excel 10 Q7740A,B FTT Repeaters Specification Data  
95-7539  
95-7521  
95-7538  
95-7558  
95-7509  
95-7510  
95-7511  
95-7516  
95-7555  
95-7554  
Excel 10 W7761A Device Installation Instructions  
Excel 10 W7750A,B Controller Installation Instructions  
T7770 Wall Module Installation Instructions  
T7780 Digital Display Wall Module Installation Instructions  
Excel 10 Q7750A Zone Manager Installation Instructions  
Excel 10 Q7751A Router Installation Instructions  
Excel 10 Q7752A Serial Interface Installation Instructions  
Excel 10 SLTA Connector Cable Installation Instructions  
Excel 10 Q7740A,B FTT Repeaters Installation Instructions  
Excel 10 209541B FTT Termination Module Installation Instructions  
74-2588  
74-5587  
74-5577  
74-2039  
74-5018  
Excel E-Vision User’s Guide  
CARE User’s Manual  
CARE Icon Guide  
XBS User’s Manual  
XBS Application Guide  
Product Names  
The W7761A Remote I/O Device is available in one model:  
W7761A Remote Input/Output Device.  
The T7770 Wall Module is available in five models:  
T7770A1xxx Wall Module with temperature sensor only - not applicable to the RIO device (jumper switches the sensor from  
20Kohm NTC to a linearized version of a 20 Kohm NTC used with the W7751A,C,E,G).  
T7770A2xxx Wall Module with temperature sensor and E-Bus network connection.  
T7770B Wall Module with temperature sensor—(current feature that can be used with the RIO Device), setpoint, and E-Bus  
network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).  
T7770C Wall Module with temperature sensor—(current feature that can be used with the RIO Device), setpoint, Bypass  
button and LED, and E-Bus network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).  
T7770D Wall Module with temperature sensor—(current feature that can be used with the RIO Device), Bypass button and  
LED, and E-Bus network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).  
NOTE: The T7770B,C Models are available with a relative scale plate adjustable in E-Vision °F (± 5°C).  
Only one PT3000 sensor is supported with the W7761A device.  
The T7780 Digital Display Wall Module (DDWM) is available in one model:  
T7780 DDWM displays and provides space temperature, setpoint, Occ/Unocc override, Application Mode, and Fan  
mode/speed selection for all Excel 10 controllers (except W7751 A,C,E,G).  
Other products:  
Q7750A Excel 10 Zone Manager.  
Q7751A Bus Router.  
Q7752A Serial Adapter.  
Q7740A,B FTT Repeaters.  
209541B FTT Termination Module.  
ML6161 Series 60 Damper Actuator.  
M6410A Series 60 Valve Actuator (use with V5812 or V5813 Valves).  
ML684A Series 60 Versadrive Valve Actuator (use with V5011 and V5013 Valves).  
MMC325-010 Transducer, Series 60 to pneumatic 0 to 10 psi.  
MMC325-020 Transducer, Series 60 to pneumatic 0 to 20 psi.  
ML6464A Direct Coupled Damper Actuator, 66 lb-in. torque, Series 60.  
ML6474 Direct Coupled Damper Actuator, 132 lb-in. torque, Series 60.  
ML6185A Direct Coupled Damper Actuator, Spring Return, Series 60.  
ML7984B Direct Coupled Valve Actuator, PWM (use with V5011 or V5013F,G Valves).  
EL7680A1008 Wall Module Infrared Occupancy Sensor.  
EL7628A1007 Ceiling Mounted Infrared Occupancy Sensor.  
EL7611A1003 Ultrasonic Occupancy Sensor.  
EL7612A1001 Ultrasonic Occupancy Sensor.  
Refer to Table 8 in Application Step 5. Order Equipment for a complete listing of all available part numbers.  
NOTE: The Q7750A Zone Manager is referred to as (E-Link) in internal software and CARE.  
5
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Agency Listings  
Table 1 provides information on agency listings for Excel 10 products.  
Table 1. Agency Listings.  
Device  
Agency  
UL  
Comments  
W7761A Input/Output Device  
Tested and listed under UL916 (file number E87741).  
Listed (E87741).  
cUL  
CE  
General Immunity per European Consortium Standards EN50081-1 (CISPR  
22, Class B) and EN 50082-1:1992 (based on Residential, Commercial, and  
Light Industrial).  
EN 61000-4-2: IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.  
EN 50140,  
EN 50204:  
IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.  
EN 61000-4-4: IEC 1000-4-4 (IEC 801-4) Electrical Fast Transient (Burst).  
Radiated Emissions and Conducted Emissions:  
EN 55022:  
CISPR-22:  
1987 Class B.  
1985.  
FCC  
Complies with requirements in FCC Part 15 rules for a Class B Computing  
Device. Operation in a residential area can cause interference to radio or TV  
reception and require the operator to take steps necessary to correct the  
interference.  
T7770A through D Wall Modules  
T7780 DDWM  
UL  
(Not applicable.)  
CSA  
FCC  
CE  
(Not applicable.)  
(Not applicable.)  
Emissions; EN50081-1, En55022 (CISPR Class B), Immunity 50082-1  
UL &cUL Tested and listed under UL916, S8L9 Energy Management Equipment.  
FCC  
Complies with requirements in FCC Part 15 rules for a Class B Computing  
Device.  
Q7750A Excel 10 Zone Manager  
UL  
Tested and listed under UL916, file number S4804 (QVAX, PAZY).  
Listing pending.  
CSA  
FCC  
Complies with requirements in FCC Part 15 rules for a Class A Computing  
Device. Operation in a residential area can cause interference to radio or TV  
reception and require the operator to take steps necessary to correct the  
interference.  
Q7751A,B Router,  
UL  
UL1784.  
Q7752A Serial Adapter  
Q7740A,B FTT Repeaters  
CSA  
FCC  
Listed.  
Complies with requirements in FCC Part 15 rules for a Class B Computing  
Device.  
Abbreviations and Definitions  
AHU - Air Handling Unit; the central fan system that includes the blower, heating equipment, cooling equipment, ventilation  
air equipment, and other related equipment.  
CO - Carbon Monoxide. Occasionally used as a measure of indoor air quality.  
CO2 - Carbon Dioxide. Often used as a measure of indoor air quality.  
CARE - Computer Aided Regulation Engineering; the PC based tool used to configure C-Bus and E-Bus devices.  
C-Bus -Honeywell proprietary Control Bus for communications between EXCEL 5000® System controllers and components.  
CPU - Central Processing Unit; an EXCEL 5000® System controller module.  
cUL - Underwriters Laboratories Canada.  
CVAHU -Constant Volume AHU; refers to a type of air handler with a single-speed fan that provides a constant amount of  
supply air to the space it serves.  
6
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
DDF - Delta Degrees Fahrenheit.  
D/X - Direct Expansion; refers to a type of mechanical cooling where refrigerant is (expanded) to its cold state, within a  
heat-exchanging coil that is mounted in the air stream supplied to the conditioned space.  
E-Bus - Honeywell implementation of Echelon® LonWorks® network for communication among Excel 10 Controllers.  
E-Bus Segment - An E-Bus section containing no more than 60 Excel 10s. Two segments can be joined together using a  
router.  
Echelon® - The company that developed the LON® bus and the Neuron® chips used to communicate on the E-Bus.  
Economizer - Refers to the mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor  
conditions, fresh air can be used to supplement the mechanical cooling equipment. Because this action saves energy,  
the dampers are often referred to as economizer dampers.  
EMI - Electromagnetic Interference; electrical noise that can cause problems with communications signals.  
E-Link - Refers to the Q7750A Zone Manager. This name is used in internal software and in CARE software.  
EMS - Energy Management System; refers to the controllers and algorithms responsible for calculating optimum operational  
parameters for maximum energy savings in the building.  
EEPROM - Electrically Erasable Programmable Read Only Memory; the variable storage area for saving user setpoint values  
and factory calibration information.  
EPROM - Erasable Programmable Read Only Memory; the firmware that contains the control algorithms for the Excel 10  
Controller.  
Excel 10 Zone Manager - A controller that is used to interface between the C-Bus and the E-Bus. The Excel 10 Zone Manager  
also has the functionality of an Excel 100 Controller, but has no physical I/O points.  
NOTE: The Q7750A Zone Manager can be referred to as E-Link in the internal software, CARE.  
FCU - Fan Coil Unit.  
Firmware - Software stored in a nonvolatile memory medium such as an EPROM.  
Floating Control - Refers to Series 60 Modulating Control of a valve or damper. Floating Control utilizes one digital output to  
pulse the actuator open, and another digital output to pulse it closed.  
FTT - Free Topology Transceiver.  
IAQ - Indoor Air Quality. Refers to the quality of the air in the conditioned space, as it relates to occupant health and  
comfort.  
I/O - Input/Output; the physical sensors and actuators connected to a controller.  
I x R - I times R or current times resistance; refers to Ohm’s Law: V = I x R.  
K - Degrees Kelvin.  
Level IV - Refers to a classification of digital communication wire. Formerly known as UL Level IV, but not equivalent to  
Category IV cable. If there is any question about wire compatibility, use Honeywell-approved cables (see Step 5 Order  
Equipment section).  
NEC - National Electrical Code; the body of standards for safe field-wiring practices.  
NEMA - National Electrical Manufacturers Association; the standards developed by an organization of companies for safe field  
wiring practices.  
Node - A Communications Connection on a network; an Excel 10 Controller is one node on the E-Bus network.  
NV - Network Variable; an Excel 10 parameter that can be viewed or modified over the E-Bus network.  
PC - An IBM compatible Personal Computer with 386 or higher processor and capable of running Microsoft® Windows™  
Version 3.1.  
Pot - Potentiometer. A variable resistance electronic component located on the T7770B,C Wall Module; used to allow user-  
adjusted setpoints to be input into the Excel 10 Controller.  
7
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
PWM - Pulse Width Modulated output; allows analog modulating control of equipment using a digital output on the controller.  
RTD - Resistance Temperature Detector; refers to a type of temperature sensor whose resistance output changes according  
to the temperature change of the sensing element.  
RIO - Remote Input/Output Device. Provides auxiliary inputs and outputs for use with an Excel 10 Zone Manager and Excel  
10 controllers.  
Subnet - An E-Bus segment that is separated by a router from its Q7750A Zone Manager.  
TOD - Time-Of-Day; the scheduling of Occupied and Unoccupied times of operation.  
TPT - Twisted Pair Transceiver.  
UV - Unit Ventilator Controller.  
VA - Volt Amperes; a measure of electrical power output or consumption as applies to an ac device.  
Vac - Voltage alternating current; ac voltage rather than dc voltage.  
VAV - Variable Air Volume; Refers to either a type of air distribution system, or to the W7751 Excel 10 VAV Box Controller  
that controls a single zone in a variable air volume delivery system.  
VOC - Volatile Organic Compound; refers to a class of common pollutants sometimes found in buildings. Sources include  
out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is  
occasionally used as a measure of indoor air quality.  
W7750 - The model number of the Excel 10 CVAHU Controllers (also see CVAHU).  
W7751 - The model number of the Excel 10 VAV Box Controllers (also see VAV).  
W7752 - The model number of the Excel 10 FCU Controllers (also see FCU).  
W7753 - The model number of the Excel 10 UV Controllers (also see UV).  
W7761 - The model number of the Excel 10 RIO Device (also see RIO).  
Wall Module - The Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the T7770 or  
T7780 Wall Modules. See Application Step 5. Order Equipment for details on the various models of Wall Modules.  
XBS - Excel Building Supervisor; a PC based tool for monitoring and changing parameters in C-Bus devices.  
Construction  
Controllers  
The Excel 10 W7761A RIO Device is available in one model. It contains 4 resistive inputs that can be configured for either  
20Kohm NTC or PT3000 sensors, 2 voltage or current inputs, 4 digital inputs and 8 Digital Outputs (Triacs) which may be  
Discrete (maintained or momentary), Modulating (PWM) or Floating.  
The W7761A consists of a single circuit board that is mounted in a sheet metal subbase and protected by a factory snap-on  
cover. The device mounts with two screws (see Fig. 3 or 4). Using DIN rail adapters (see Fig. 5) they can also be snapped onto  
standard EN 50 022 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) DIN rail. DIN rail is available through local suppliers. If using DIN  
rail also purchase from Augat Inc. part number 2TK2D DIN rail (adapter) two each for every device (see Fig. 5). Wires are  
attached to the screw terminal blocks on both sides of the device. Connection for operator access to the E-Bus is provided by  
plugging the SLTA connector cable into the communications jack.  
A channel in the cover allows the device status LED to be visible when the cover is in place. There are no field-serviceable  
parts on the circuit board and, therefore, it is intended that the cover never be removed.  
The W7761A can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat  
dissipation regardless of the mounting orientation. See Fig. 3 and 4.  
8
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
W7761A  
3
1
3
0
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
D
I -  
1
9
4
1
G
8
N
D
1
7
D
I
1
-3  
6
D
I-  
2
V
AC 24  
C O M  
G
N
D
D
I
-1  
V
AC 24  
O
U
T
1
O
U
T
2
O
U
T
3
O
U
T
4
O
U
T
5
O
U
T
6
O
U
T
7
O
UT  
8
E G N D  
N O T  
U S E D  
N O T  
U S E D  
AI-1  
O H M  
G N D  
AI-2  
AI-3  
O H M  
O H M  
G N D  
AI-4  
O H M  
AI-5  
V / m A  
G N D  
AI-6  
V / m A  
22  
O
V
U
D
T
C
E
B
U S  
1
2
E
JA  
B
C
U
S
K
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
J
3
M 10118  
Fig. 3. Excel 10 W7761A Remote I/O Device.  
9
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
2-1/8  
(54)  
31 30 29 28 27 26 25 24 23 22  
21 20 19 18 17 16  
5-5/8  
(143)  
VA  
C
C
O
24  
M
VA  
C
24  
OU  
T
1
OU  
T
2
O
U
T
3
O
U
T
4
O
U
T
5
O
U
T
6
OU  
T
7
O
U
T
8
G N D  
G N D  
D
I-  
4
D
I-  
3
D
I-2  
D
I-  
1
NOT  
USED  
NOT  
USED  
AI-1  
O H M  
AI-2  
O H M  
AI-3  
O H M  
AI-4  
O H M  
AI-5  
V / m A  
AI-6  
V / m A  
2
2
O
V
U
D
T
C
E
BU  
S
EB  
J AC  
U
S
K
E G N D  
G N D  
G N D  
G N D  
3-1/16  
(77)  
1
2
3
4
5
6
7
8
9
10  
11 12 13 14 15  
J3  
5-3/16 (132)  
6 (152)  
M 6856  
Fig. 4. W7761A construction in in. (mm).  
10  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
2
3
1
M6857  
Fig. 5. DIN rail adapters.  
The input/output points are summarized in Table 2.  
Table 2. List Of Available Points.  
W7761A  
8 Triac Outputs  
4
Digital Outputs  
Digital Inputs  
Analog Inputs  
6
(4 Resistive and 2  
Voltage/Current Inputs)  
DC Power  
20 Vdc available to  
power optional sensors  
(50 mA max.)  
Floating (Series 60) Heating or Cooling  
Control  
PWM Control  
Heating or Cooling  
Performance Specifications  
Power:  
24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at either 50 or 60 Hz. The W7761A power consumption is 6 VA  
maximum at 50 or 60 Hz. The W7761A is a NEC Class 2 rated device. This listing imposes limits on the amount of power the  
product can consume or directly control to a total of 100 VA (U.S. only).  
The individual Triac outputs incorporate an internal common connection with the input power transformer. The Triacs provide a  
switched path from the hot side (R) of the transformer through the load to the common of the transformer. The W7761A Device  
design must use the same power transformer for any loads connected to that device; see Fig. 19.  
Each individual Triac is rated 500mA at 30 Vac maximum. Under all operating conditions, the maximum load/source power  
budget for the W7761A Device is 100 VA.  
11  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
CPU:  
Motorola or Toshiba 3150 Neuron processor, containing three eight-bit CPU’s. Each Neuron has a unique 48-bit network  
identification number.  
Memory Capacity:  
64K ROM/PROM (6K reserved for network operations, 58K usable for control algorithm code).  
512 bytes EEPROM.  
2K RAM.  
Specified Space Temperature Sensing Range:  
45 to 99°F (7 to 37°C) with an allowable control setpoint range from 50 to 90°F (10 to 32°C) when initiated from the network  
and 55 to 85°F (13 to 29°C) when configured and connected to T7770 Wall Modules or T7780 DDWM.  
Communications:  
The W7761A Device uses a transformer-coupled communications port with differential Manchester-encoded data at 78 kilobits  
per second (kbs). The transformer-coupled communications interface offers a much higher degree of common-mode noise  
rejection while ensuring dc isolation.  
Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated  
2
unshielded, twisted pair, solid conductor wire. For non-plenum areas, use Level IV 22 AWG (0.34 mm ) such as U.S. part  
2
AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm ) such as  
U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). (See Tables 6 and 8 for part numbers.) Contact Echelon Corp.  
Technical Support for the recommended vendors of Echelon approved cables.  
The Free Topology Transceiver (FTT) supports polarity insensitive free topology wiring. This frees the system installer from the  
need to wire using a bus topology. Star, bus, mixed, and loop wiring are all supported by this architecture. The maximum E-Bus  
length when using a combination of star, loop, and bus wiring (singly terminated) is 1640 ft (500m) with the maximum node-to-  
node length of 1312 ft (400m). In the event that the total wire length is exceeded, then a Q7740A 2-Way Repeater or a Q7740B  
4-Way Repeater can be used to allow the number of devices to be spread out as well as increasing the length of wire over  
which they communicate. The maximum number of repeaters per segment is one (on either side of the router). A Q7751A E-  
Bus Router can also be used to effectively double the maximum E-Bus length. The advantage of using the router is that it will  
segregate traffic to a segment while when using the repeater, all traffic is repeated on each segment. When utilizing a doubly  
terminated E-Bus structure, use a continuous daisy-chain with no stubs or taps from the main backbone, The maximum E-Bus  
length is 4593 ft (1400m) with the maximum node-to-node length of 3773 ft (1150m).  
FTT networks are very flexible and convenient to install and maintain, but it is imperative to carefully plan the network layout  
and create and maintain accurate documentation. Unknown or inaccurate wire run lengths, node-to-node distances, node  
counts, total wire length, and misplaced or missing terminators can cause poor network performance. Refer to E-Bus Wiring  
Guidelines form, 74-2865 for complete description of network topology rules.  
LonMark Functional Profile  
W7761A Device supports the LonMark Preliminary Functional Profile for a Remote Input/Output Device.  
Environmental:  
Operating Temperature:  
-40° to 150°F (-40° to 65.5°C).  
Shipping Temperature:  
-40° to 150°F (-40° to 65.5°C).  
Relative Humidity:  
5% to 95% noncondensing.  
Vibration:  
Rated V2 level compliant.  
Inputs/Outputs:  
The W7761A Unit supports the following hardware features:  
Four 20KNTC (1000 through 150,000 ohm) or PT3000 (250 through 12,000 ohm) resistive analog inputs.  
Two 0.2 to 10 VDC or 2 to 20 mA (user selectable) analog inputs.  
Four dry contact digital inputs.  
Eight 24 Vac Triac digital outputs (500 mA MAX).  
One 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.  
Analog Inputs:  
Space Temperature:  
Type: RTD.  
12  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Supported Sensors: T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and T7780  
DDWM.  
Discharge Air Temperature:  
Type: RTD.  
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,  
C7031K1017.  
Outdoor Air Temperature:  
Type: RTD.  
Supported Sensors: C7170A1002.  
Return Air Temperature:  
Type: RTD.  
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,  
C7031K1017.  
Mixed Air Temperature:  
Type: RTD.  
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,  
C7031K1017.  
*The PT3000 sensor is not recommended for floating control (real time - discharge or return configured as space sensor).  
The PT3000 sensor is intended for monitoring or differential (staged) control.  
Outdoor Air Humidity:  
Type: Voltage/Current.  
Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).  
Return Air Humidity:  
Type: Voltage/Current.  
Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).  
Outdoor Air Enthalpy:  
Type: Current.  
Supported Sensors: C7400A1004 (4 to 20mA).  
Return Air Enthalpy:  
Type: Current.  
Supported Sensors: C7400A1004 (4 to 20mA).  
Air Filter Differential Pressure:  
Type: Voltage.  
Supported Sensors: Third party 2 to 10V, 0 to 5 inw ( 0 to 1.25 kPa) differential pressure sensors.  
Space CO2 Sensor:  
Type: Voltage.  
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO2 sensors.  
Outdoor Air CO2 Sensor:  
Type: Voltage.  
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO2 sensors.  
Outdoor Air CO Sensor:  
Type: Current.  
Supported Sensors: Third party 4 to 20mA, 0 to 300 ppm CO sensor.  
Monitor Sensor for network use:  
Type: Voltage.  
Supported Sensors: Third party 2 to 10V, 2 to 10 volts displayed.  
Digital Inputs:  
Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts detection circuit. It is very important that the device used contains  
high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as  
gold or silver) or pimpled or sealed contacts to assure consistent, long-term operation.  
Triac Outputs:  
Triac Outputs on the RIO:  
Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA MAX current for any voltage.  
13  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
CAUTION  
When any device is energized by a Triac, the device must be able to sink a minimum of 25 mA.  
NOTE: Triacs sink current to the 24 Vac common (COM terminal on the W7761A); see Fig. 19 for wiring example.  
IMPORTANT:  
If non-Honeywell motors, actuators, or transducers are to be used with Excel 10 Controllers, Triac compatibility must  
be verified (see previous NOTE).  
Wall Modules  
The T7770A,B,C,D Wall Module sensor—(current feature that can be used with the Excel 10 W7761A RIO Device). See Fig. 6.  
KNOCKOUTS FOR EUROPEAN  
APPLICATIONS  
KNOCKOUTS FOR EUROPEAN  
APPLICATIONS  
70  
75  
65  
60  
5-1/16  
(128)  
5-1/16  
(128)  
80  
85  
55  
29/32  
(23)  
1-1/4  
(32)  
3-5/32 (80)  
2-3/8 (60)  
3-5/32 (80)  
2-3/8 (60)  
2-3/8  
(60)  
2-3/8  
(60)  
9
8
7
6
5
4
3
2
1
STANDARD  
UTILITY  
STANDARD  
UTILITY  
CONDUIT  
BOX (2 X 4)  
MOUNTING  
HOLES  
CONDUIT  
BOX (2 X 4)  
MOUNTING  
HOLES  
M15119  
Fig. 6. T7770A,B,C,D (T7770A,C shown) construction in in. (mm), sensor—(current feature that can be used with RIO  
Device).  
14  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
The T7780 DDWM for the Excel 10 Controllers (see Product Names section) is shown in Fig. 7.  
KNOCKOUTS FOR EUROPEAN  
APPLICATIONS  
5-1/16  
(128)  
1
(25)  
3-5/32 (80)  
2-3/8 (60)  
2-3/8  
(60)  
STANDARD  
UTILITY  
CONDUIT  
BOX (2 X 4)  
MOUNTING  
HOLES  
M11391  
Fig. 7. T7780 construction, subbase dimensions in in. (mm).  
Configurations  
Each W7761A device can control or monitor a variety of different types of mechanical equipment. The W7761A was not  
intended to control staged or modulating heating/cooling coils, mixed air economizer dampers, or system fan/heat pump units.  
The W7761A contains inputs and outputs, but no control software. All control that would be associated with the inputs and  
outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control,  
temperature control, or any control function that would require less than a 30 second update rate.  
It would be suitable to control miscellaneous exhaust or ventilation fans, lighting zones that are spread out through a building  
which need to be linked to a start/stop time program through the Zone Manager or to enable freeze protection. The W7761A  
device can be connected to outdoor air temperature and humidity sensors that can be used by other Excel 10 controllers on  
the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. The W7761A can be used to monitor  
Occupancy, Window, Dirty filter, Indoor air quality, and Smoke control sensors. This allows the controllers to use their physical  
inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control. The W7761A can be used to  
15  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
average many space temperature sensors that are located in a zone that is controlled by the W7750 Constant Volume AHU  
Controller.  
Mixed-Output-Type Control  
The W7761A Device can control mixed-output-types of applications such as PWM and staged control occurring simultaneously  
with Series 60 Floating Control.  
Occupancy Sensor  
Excel 10 W7761A device can be connected to an occupancy sensor through a digital input. This is a device, such as a passive  
infrared motion detector, that contains a dry contact (see following NOTE) closure to indicate whether or not people are present  
in the space. The Excel 10 W7761A Device expects a contact closure to indicate the space is Occupied. See Fig. 18 in  
Application Step 4, Prepare Wiring Diagrams, for details on wiring connections. This occupancy sensor can then be bound to  
other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This  
would allow the other Excel 10 controllers to use their physical inputs for monitoring other elements such as return humidity,  
IAQ, etc. to achieve better control.  
NOTE: The Excel 10 Controllers (W7750 CVAHU and W7761A RIO) have limited power available (only 9 mA at 4.8 volts) for  
checking the digital inputs for contact closures. It is very important that the device used contains high quality,  
noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as  
gold or silver), pimpled or sealed contacts to assure consistent, long-term operation.  
The recommended devices for use with the Excel 10 W7750 Controller and W7761A Device are the EL7628A1007 Ceiling  
Mounted Infrared or the EL7680A1008 Wall Mounted Wide View Infrared Occupancy Sensors. If ultrasonic sensors are  
required, the EL7611A1003 and the EL7612A1001 Occupancy Sensors are recommended. An EL76XX Power Supply/Control  
Unit is required for use with these occupancy sensors. The EL7630A1003 can power up to four sensors, and is multi-tapped for  
several line voltages. The EL7621A1002 can power three sensors and it connects to 120 Vac line voltage. The EL7621A1010  
can also power three sensors but it connects to 277 Vac line voltage.  
Window Open/Closed Digital Input  
Excel 10 W7761A device can be connected to a window sensor to indicate whether a window in the space was opened. The  
Excel 10 W7761A device can be connected to a dry contact (see the NOTE for the Occupancy Sensor and Fig. 18 in  
Application Step 4. Prepare Wiring Diagrams, for details) or a set of contacts wired in series (for monitoring multiple windows)  
to verify that the window(s) are closed. This window(s) sensor can then be bound to other Excel 10 controllers on the E-Bus or  
Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. The algorithm in the other Excel 10 controllers  
expects a contact closure to indicate the window is closed. If an open window is detected, the algorithm in the other Excel 10  
controllers changes the mode of operation to FREEZE_PROTECT, which shuts down the control functions, and watches for  
low space temperature conditions. The freeze protection setpoint is 46.4°F (8°C), and the frost alarm occurs at 42.8°F (6°C).  
Wall Module Options  
As previously discussed, there are five basic varieties of the T7770. There is one variety of the PT3000 sensor and the T7780  
DDWM (see the Product Names and the Construction sections). The T7770A,B,C,D 20Kohm NTC sensor—(current feature  
that can be used with the RIO Device) and one PT3000 sensor can be configured on any of the four resistive inputs. The  
T7780 is an E-Bus node and would not be directly connected to the RIO Device.  
Dirty Filter Monitor  
The air filter in the air handler can be monitored by the W7761A RIO device and an alarm issued by the Zone Manager when  
the filter media needs replacement. The two methods of monitoring the filter are:  
1. Connecting a differential pressure switch to a digital input on the W7761A.  
2. Wiring a 2-to-10V differential pressure sensor to a voltage input on the W7761A. If the analog input sensor is used, its  
measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint. The comparison is done in the  
Zone Manager —valid range: 0 to 5 inw (0 to 1.25 kPa), and the Dirty Filter alarm is issued when the pressure drop  
across the filter exceeds the setpoint.  
Indoor Air Quality (IAQ)  
The Excel 10 W7761A device can monitor IAQ using one of two different methods of detecting poor air quality. The first is with  
an IAQ switch device connected to a digital input on the W7761A, where a contact closure indicates poor air quality, and an  
alarm can be issued by the Zone Manager. The device can detect poor air quality using any desired measure such as CO2,  
VOC, CO, etc. The second method, is through an analog input that connects to a CO2 sensor (0 to 10V). The measured value  
of CO2 from this sensor (0 to 2000 ppm) is compared to a user-selectable setpoint (the comparison is done in the Zone  
Manager —valid range: 0 to 2000 ppm), and an IAQ alarm can be issued when the CO2 level exceeds the setpoint. The IAQ  
sensor that is connected to the W7750 RIO, can be bound to other W7750 CVAHU Excel 10 controllers on the E-Bus.  
16  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
APPLICATION STEPS  
Overview  
The seven application steps shown in Table 3 are planning considerations for engineering an Excel 10 W7761 Remote  
Input/Output Device. These steps are guidelines intended to aid understanding of the product I/O options, bus arrangement  
choices and the Excel 10 W7761A Devices role in the overall EXCEL 5000® System architecture.  
Table 3 . Application Steps.  
Step No.  
Description  
Plan The System  
1
2
3
4
5
6
7
Determine Other Bus Devices Required  
Lay Out Communication and Power Wiring  
Prepare Wiring Diagrams  
Order Equipment  
Configure Devices  
Troubleshooting  
Step 1. Plan The System  
Plan the use of the W7761A Devices according to the job requirements. Determine the location, functionality and sensor or  
actuator usage. Verify the sales estimate of the number of W7761A Devices and the number and type of output actuators and  
other required accessories.  
When planning the system layout, consider potential expansion possibilities to allow for future growth. Planning is very  
important to be prepared for adding HVAC systems and controllers in future projects.  
T7770A,B,C,D Wall Modules (sensor—current feature that can be used with the RIO Device)can be installed as either  
hardwired I/O-only devices or additional wiring can be run to them (for the E-Bus network ) to allow a CARE/E-Vision operator  
terminal to have access to the E-Bus. The application engineer needs to determine how many wall modules or other input  
sensors are required. This information is required during installation to ensure that the proper number and type of wires are  
pulled to the wall modules, and the building operators are informed about where they can plug in to the E-Bus network with a  
portable operator terminal (see Fig. 8 through 10).  
Fig. 8. Connecting the portable operator terminal to the E-Bus.  
The FTT communication loop, (E-Bus) between controllers is a free topology wiring scheme that supports star, loop, and/or bus  
wiring. Refer to the E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules. See Application  
Step 3. Lay Out Communications and Power Wiring, for more information on bus wiring layout, and see Fig. 16 through 19 in  
Application Step 4. Prepare Wiring Diagrams, for wiring details.  
The application engineer must review the Direct Digital Control (DDC) job requirements. This includes the Sequences of  
Operation for the Excel 10 controllers, and for the system as a whole. Usually there are variables that must be passed between  
the W7750 (CVAHU), Q7750A Zone Manager, W7761 (RIO), and other Excel 10 controller(s), or central plant controller(s) that  
are required for optimum system-wide operation. Typical examples are the TOD Occ/Unocc signal, the outdoor air  
temperature, demand limit control signal, and smoke control mode signal.  
17  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
It is important to understand these interrelationships early in the job engineering process to ensure implementing when  
configuring the controllers. (See Application Step 6. Configure Devices, for information on the various Excel 10 parameters and  
on Excel 10 point mapping.)  
Step 2. Determine Other Bus Devices Required  
A maximum of 62 nodes can communicate on a single E-Bus segment. Each W7761A (RIO), W7750 (CVAHU), W7751 (VAV)  
Controller or T7780 Wall Module constitutes one node. If more nodes are required, a Q7751A Router is necessary. Using a  
router allows up to 125 nodes, divided between two E-Bus segments. The router accounts for two of these nodes (one node on  
each side of the router); a Q7750A Excel 10 Zone Manager takes one node and two nodes are available for operator terminal  
nodes, leaving 120 nodes available for Excel 10 Controllers and T7780 Wall Modules. All 120 controllers and T7780 Wall  
Modules are able to talk to each other through the router. A Q7750A Excel 10 Zone Manager is required to connect the E-Bus  
to the standard EXCEL 5000® System C-Bus. Each Excel 10 Zone Manager can support no more than 120 Excel 10  
Controllers and T7780 Wall Modules. This limit is set in the Excel 10 Zone Manager database as an absolute maximum.  
Each E-Bus segment is set up with two unused nodes to allow for a CARE/E-Vision or Hand Held Tool (HHT) to be connected  
to the E-Bus. Multiple CARE/E-Vision or HHT terminals can be connected to the bus at the same time. Table 4 summarizes the  
E-Bus segment configuration rules.  
Table 4 . E-Bus Configuration Rules And Device Node Numbers.  
One E-Bus Segment Example  
One Q7750A Excel 10 Zone Manager 1 node  
Port for operator terminal access (CARE/E-Vision or HHT) 1 node  
Maximum Number of Nodes Equals 62  
Maximum number of Excel 10s and T7780s 60 nodes (Only T7780 Wall Modules are E-Bus nodes)  
Total 62 nodes  
Two E-Bus Segments Example Maximum Number of Nodes Equals 125  
One Q7750A Excel 10 Zone Manager 1 node  
One Q7751A Router 2 nodes (1 in each Bus Segment)  
Ports for operator terminal access (two CARE/E-Vision or HHT 2 nodes (1 in each Bus Segment)  
terminals)  
Maximum number of Excel 10s and T7780s in segment number 60 nodes (Only T7780 Wall Modules are E-Bus nodes)  
one  
Maximum number of Excel 10s and T7780s in segment number 60 nodes (Only T7780 Wall Modules are E-Bus nodes)  
two  
Total 125 nodes  
Refer to the E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules and the maximum wire  
length limitations. If longer runs are required, a Q7740A 2-way or Q7740B 4-way repeater can be added to extend the length of  
the E-Bus. A Q7751A Router can be added to partition the system into two segments and effectively double the length of the  
E-Bus. Only one router is allowed with each Excel 10 Zone Manager and each network segment can have a maximum of 1  
repeater. In addition, all E-Bus segments require the installation of a Bus Termination Module for a singly terminated E-Bus or  
two Bus Termination Modules for a doubly terminated E-Bus. For more details on E-Bus termination, refer to the E-Bus Wiring  
Guidelines form, 74-2865, or see Application Step 3. Lay Out Communications and Power Wiring, and the E-Bus Termination  
Module subsection in Application Step 4.  
Step 3. Lay Out Communications and Power Wiring  
E-Bus Layout  
The communications bus, E-Bus, is a 78-kilobit serial link that uses transformer isolation and differential Manchester encoding.  
Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated  
2
unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.34 mm ), such as U.S. part  
2
AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm ) such as  
U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 10 for part numbers. Contact Echelon Corp.  
Technical Support for the recommended vendors of Echelon approved cables. The FTT communications bus, E-Bus,  
supports a polarity insensitive, free topology wiring scheme that supports star, loop, and/or bus wiring.  
E-Bus networks can be configured in a variety of ways, so refer to the E-Bus Wiring Guidelines form, 74-2865 for a complete  
description of network topology rules and Table 4. Fig. 9 and 10 depict two typical E-Bus network topologies; one as a singly  
terminated bus segment that has 60 nodes or less, and one showing a doubly terminated segment. The bus configuration is  
set up using the Network Manager tool from within CARE (see the CARE User’s Manual form, 74-5587 or Excel E-Vision  
User’s Guide form, 74-2588).  
18  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
NOTE: For wiring details see the E-Bus Termination Module subsection in Step 4. For wall module wiring, US part AK3782  
(non-plenum) or US part AK3792 (plenum) can be used. These cables contain two twisted pairs (one for the run down  
to the wall module, and one for the run back up to the controller) for ease of installation.  
Fig. 9. Bus wiring layout for doubly terminated daisy-chain E-Bus segment.  
19  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Fig. 10. Bus wiring layout for two singly terminated E-Bus segments.  
NOTE: See the E-Bus Termination Module section for wiring details.  
IMPORTANT  
Notes on communications wiring:  
All field wiring must conform to local codes and ordinances.  
Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum  
2
rated unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.34 mm ), such  
as U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22  
2
AWG (0.34 mm ) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 10 for part  
numbers. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved  
cables.  
Unswitched 24 Vac power wiring can be run in the same conduit as the E-Bus cable.  
Do not use different wire types or gauges on the same E-Bus segment. The step change in line impedance  
characteristics causes unpredictable reflections on the bus. When using different types is unavoidable, use a  
Q7751A Router at the junction.  
In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, or lines containing lighting  
dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the E-Bus cable.  
Make sure that neither of the E-Bus wires is grounded.  
Power Wiring  
A power budget must be calculated for each Excel 10 W7761 Device to determine the required transformer size for proper  
operation. A power budget is simply the summing of the maximum power draw ratings (in VA) of all the devices to be controlled  
by an Excel 10 W7761 Device. This includes the device itself, the equipment actuators (ML6161, or other motors) and various  
contactors and transducers, as appropriate, for the Excel 10 configuration.  
Power Budget Calculation Example  
The following is an example power budget calculation for a typical W7761A Excel 10 Device.  
Device  
Excel 10 W7761  
Device  
VA  
6.0 VA  
Information Obtained from the  
W7761  
Specification Data  
20  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
ML6161  
Damper Actuator  
2.2 VA  
21.0 VA  
0.7 VA  
TRADELINE®  
Catalog  
R8242A  
Contactor for fan  
TRADELINE®  
Catalog in-rush rating  
M6410A Steam  
TRADELINE®  
Heating Coil Valve  
Catalog, 0.32A at 24 Vac  
TOTAL: 29.9 VA  
The Excel 10 System example requires 29.9 VA of peak power; therefore, a 40 VA AT72D Transformer is able to provide  
ample power for this device and its accessories. Alternatively, a 75 VA AT88A Transformer could be used to power two Excel  
10 Systems of this type, or a 100 VA AT92A Transformer could be used to power three of these controllers and meet NEC  
Class 2 restrictions (no greater than 100 VA). See Fig. 12 through 14 for illustrations of power wiring details. See Table 5 for  
VA ratings of various devices.  
Table 5 . VA Ratings For Transformer Sizing.  
Device  
W7761A  
Description  
Excel 10 W7761 Device  
Damper Actuator, 35 lb-in.  
Contactor  
VA  
6.0  
2.2  
ML6161A/B  
R8242A  
R6410A  
MMC325  
ML684  
21.0  
0.7  
Valve Actuator  
Pneumatic Transducer  
Versadrive Valve Actuator  
Damper Actuator, 66 lb-in.  
Damper Actuator, 132 lb-in.  
5.0  
12.0  
3.0  
ML6464  
ML6474  
ML6185  
3.0  
Damper Actuator SR 50 lb-in. 12.0  
For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power  
budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized  
outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined  
when sizing the transformer.  
Line Loss  
Excel 10 Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a  
voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total  
power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft (61m)  
run from the transformer to a W7761 Device drawing 37 VA using 18 AWG (1.0 mm2) wire.  
The formula is:  
Loss = [length of round-trip wire run (ft)] x [resistance in wire (ohms per ft)] x [current in wire (amperes)]  
From specification data:  
18 AWG twisted pair wire has 6.52 ohms per 1000 feet.  
Loss = [(200 ft) x (2 - round-trip) x (6.52/1000 ohms per ft)] x [(37 VA)/(24V)] = 4.02 volts  
This means that four volts are going to be lost between the transformer and the device; therefore, to assure the device receives  
at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the  
size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 11 shows this  
voltage load dependence.  
In the preceding I x R loss example, even though the device load is only 37 VA, a standard 40 VA transformer is not sufficient  
due to the line loss. From Fig. 11, a 40 VA transformer is just under 100 percent loaded (for the 37 VA device) and, therefore,  
has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 11 that represents the worst case  
conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the device, which is not enough voltage for  
proper operation.  
In this situation, the engineer basically has three alternatives:  
1. Use a larger transformer; for example, if an 80 VA model is used, see Fig. 11, an output of 24.4 volts minus the four volt  
line loss supplies 20.4V to the device. Although acceptable, the four-volt line-loss in this example is higher than  
recommended. See the following IMPORTANT.  
2. Use heavier gauge wire for the power run. 14 AWG (2.0 mm2) wire has a resistance of 2.57 ohms per 1000 ft which,  
using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA  
transformer to be used. 14 AWG (2.0 mm2) wire is the recommended wire size for 24 Vac wiring.  
3. Locate the transformer closer to the device, thereby reducing the length of the wire run, and the line loss.  
The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula  
and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary,  
use heavier gauge wire, a bigger transformer, or install the transformer closer to the device.  
IMPORTANT  
21  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
No installation should be designed where the line loss is greater than two volts to allow for nominal operation if the  
primary voltage drops to 102 Vac (120 Vac minus 15 percent).  
To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits.  
The chart in Fig. 11 shows the required limits at various loads.  
With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a  
purchased transformer meets the NEMA standard DC20-1986, the transformer voltage-regulating ability can be considered  
reliable. Compliance with the NEMA standard is voluntary.  
The following Honeywell transformers meet this NEMA standard:  
Transformer Type  
AT20A  
VA Rating  
20  
40  
AT40A  
AT72D  
AT87A  
40  
50  
AK3310 Assembly  
100  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
200  
0
50  
100  
150  
% OF LOAD  
M993  
Fig. 11. NEMA class 2 transformer voltage output limits.  
Attach earth ground to W7761 Device terminal 1. See Fig. 12, 13 and 14, 16 through 20.  
TRIAC`  
COMMON  
TRIAC LINES`  
TRANSFORMER  
TO ACTUATORS`  
AND CONTACTORS  
W7761A  
CONNECT POWER TO `  
TERMINALS 24 AND 25  
2524 22 20  
1
EARTH`  
M10089  
GROUND  
Fig. 12. Power wiring details for one Excel 10 per transformer.  
22  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
TRANSFORMER  
24 VAC  
120/240 VAC  
W7761A  
W7761A  
W7761A  
2524  
25 24  
25 24  
1
1
1
EARTH`  
EARTH`  
EARTH`  
M10090  
GROUND  
GROUND  
GROUND  
Fig. 13. Power wiring details for two or more Excel 10s per transformer.  
IMPORTANT  
If the W7761A Device is used on Heating and Cooling Equipment (UL 1995 US only) devices and the transformer  
primary power is more than 150 volts, connect the transformer secondary to earth ground, see Fig. 14.  
LINE VOLTAGE`  
GREATER`  
THAN 150 VAC  
24 VAC  
W7761A  
TRANSFORMER  
1
EARTH`  
GROUND  
1
EARTH`  
GROUND  
1` IF THE W7761 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND `  
THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE `  
SIDE OF TRANSFORMER SECONDARY.  
M10088  
Fig. 14. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only).  
IMPORTANT  
Notes on power wiring:  
All field wiring must conform to local codes and ordinances.  
To maintain NEC Class 2 and UL ratings, the installation must use transformers of 100 VA or less capacity.  
For multiple controllers operating from a single transformer, the same side of the transformer secondary must be  
connected to the same input terminal in each device and the ground terminals (1 on the W7761A) must be  
connected to a verified earth ground for each device in the group. See Fig. 13. (Device configurations are not  
necessarily limited to three devices per transformer.)  
For the W7761A Device (which has Triac outputs), all output devices must be powered from the same transformer  
as the one powering the Excel 10 W7761A Device.  
Use the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2) for all  
power and earth ground connections.  
To minimize EMI noise, do not run Triac output wires in the same conduit as the input wires or the E-Bus  
communications loop.  
Unswitched 24 Vac power wiring can be run in the same conduit as the E-Bus cable.  
23  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Make earth ground connections with the shortest possible wire run using 14 AWG (2.0 mm2) wire. A good earth  
ground is essential for W7761A operation. Ideally, connect the earth ground to the ground bus at a motor control  
center or circuit breaker panel. However, if the nearest ideal earth ground is inaccessible, consider an alternate  
source for earth ground. Metal water pipe is generally a good ground, but do not use sprinkler pipe if prohibited by  
local codes. Attention must be given when duct work, conduit, or rebar are to be considered as ground sources. It  
is the responsibility of the installer to assure that these structures are tied back to a known earth ground.  
Step 4. Prepare Wiring Diagrams  
General Considerations  
The purpose of this step is to assist the application engineer in developing job drawings to meet job specifications. Wiring  
details are included for the W7761A device the T7770A,B,C,D wall module (sensor—current feature that can be used with the  
RIO Device) and the T7780 DDWM. The drawings detail I/O, power, and communication bus wiring connections.  
NOTE: For field wiring, when two or more wires are to be attached to the same connector block terminal, be sure to twist  
them together. Deviation from this rule can result in improper electrical contact. See Fig. 15.  
The connector block terminals on the W7761A and on the T7770 accept 14 through 22 AWG (2.0 to 0.34 mm2) wire. Table 6  
lists wiring types, sizes, and length restrictions for Excel 10 products.  
Table 6 . Field Wiring Reference Table.  
Recommended  
Minimum Wire  
Specification  
or  
Requirement  
Wire  
Maximum Length  
ft (m)  
Function Size AWG (mm2)  
Construction  
Vendor Wire Type  
E-Bus  
22 AWG  
Twisted pair solid conductor, Level IV 140°F Honeywell  
Refer to E-Bus  
(Plenum) (0.34 mm2)  
nonshielded or Echelon  
approved shielded cable.  
(60°C) rating  
AK3791 (one twisted pair) Wiring Guidelines  
AK3792 (two twisted pairs) for maximum  
length  
E-Bus  
(Non-  
Plenum)  
22 AWG  
Twisted pair solid conductor, Level IV 140°F Honeywell  
Refer to E-Bus  
(0.34 mm2)  
nonshielded or Echelon  
approved shielded cable.  
(60°C) rating  
AK3781 (one twisted pair) Wiring Guidelines  
AK3782 (two twisted pairs) for maximum  
length  
Input  
Wiring  
Sensors  
Contacts  
18 to 22 AWG  
Multiconductor (usually five- 140°F (60°C) Standard thermostat wire 1000 ft (305m)  
(1.0 to 0.34 mm2) wire cable bundle). For runs rating  
>200 ft (61m) in noisy EMI  
for 18 AWG  
200 ft (61m)  
for 22 AWG  
areas, use shielded cable.  
Output  
Wiring  
Actuators (18 AWG (1.0  
14 AWG (2.0  
mm2)  
Any pair nonshielded (use  
heavier wire for longer  
runs).  
NEC Class 2  
140°F (60°C) AK3702 (18 AWG)  
rating  
Honeywell  
Limited by line-loss  
effects on power  
consumption.  
(See Line Loss  
subsection.)  
AK3712 (16 AWG)  
AK3754 (14 AWG)  
or equivalent  
Relays  
mm2) acceptable  
for short runs)  
Power  
Wiring  
14 AWG  
Any pair nonshielded (use  
heavier wire for longer  
runs).  
NEC Class 2  
140°F (60°C) AK3754 (14 AWG)  
rating twisted pair  
Honeywell  
Limited by line-loss  
effects on power  
consumption.  
(2.0 mm2)  
AK3909 (14 AWG) single (See Line Loss  
conductor or equivalent subsection.)  
W7761A Devices  
Fig. 16 through 20 illustrate W7761A Device wiring for various configurations. Connections to the wall module terminals (4  
through 6) and the communications terminals (14 and 15) are made at terminal blocks. Connection for access to the E-Bus is  
provided by plugging the connector into the communications jack.  
NOTE: If an Excel 10 W7761A Device or Zone Manager is not connected to a good earth ground, the device internal transient  
protection circuitry is compromised and the function of protecting the device from noise and power line spikes cannot  
be fulfilled. This can result in a damaged circuit board and require replacing the device.  
24  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
TWO 14 AWG`  
(2.0 MM2) WIRES  
3/8`  
(10)  
1. STRIP 3/8 IN. (10 MM) FROM WIRES `  
TO BE ATTACHED AT ONE TERMINAL.  
2. TWIST WIRES TOGETHER `  
WITH PLIERS (A MINIMUM `  
OF THREE TURNS).  
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) `  
BEFORE INSERTING INTO TERMINAL AND TIGHTENING`  
SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS`  
TO CHECK FOR GOOD MECHANICAL CONNECTION.  
M10086  
Fig. 15. Attaching two or more wires at terminal blocks.  
See Table 7 for a description of the W7761A terminals.  
Table 7 . W7761A I/O Description.  
Description  
Terminal  
Number  
Terminal  
OUT 8  
16  
Digital Output 8  
Digital Output 7  
Digital Output 6  
Digital Output 5  
Digital Output 4  
Digital Output 3  
Digital Output 2  
Digital Output 1  
OUT 7  
OUT 6  
OUT 5  
OUT 4  
OUT 3  
OUT 2  
OUT 1  
17  
18  
19  
20  
21  
22  
23  
+24Vac (H) 25  
Power for the device  
COM (N)  
E-Bus  
E-Bus  
DI -4  
24  
15  
14  
31  
30  
29  
28  
27  
26  
Return for power to device  
Echelon® communications screw terminals  
Echelon® communications screw terminals  
Digital Input 4  
DGND  
DI -3  
Digital Ground  
Digital Input 3  
DI -2  
Digital Input 2  
DGND  
DI -1  
Digital Ground  
Digital Input 1  
22 VDC out 13  
22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.  
AI-6  
12  
11  
10  
9
Analog Input 6 voltage or current  
Analog ground  
AGND  
AI-5  
Analog Input 5 voltage or current  
Analog Input 4 resistance  
Analog ground  
AI-4  
AGND  
AI -3  
AI-2  
8
7
Analog Input 3 resistance  
Analog Input 2 resistance  
25  
6
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
GROUND  
AI-1  
5
4
3
2
1
Analog ground  
Analog Input 1 resistance  
Not Used  
Not Used  
EGND  
Earth Ground  
See Fig. 20 to wire a pneumatic transducer to a W7761A.  
C7770A AIR  
TEMPERATURE SENSOR  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
TRIAC EQUIVALENT CIRCUIT  
W7761A  
REMOTE I/O  
DEVICE  
E-BUS  
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
E-BUS  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
E-BUS  
NETWORK  
ACCESS  
T7770A  
WALL  
MODULE  
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
M15276  
Fig. 16. Typical T7770A and C7770A wiring diagram. (For note 2, refer to Fig. 15.)  
26  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
+
24 VAC  
-
30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
31  
TRIAC EQUIVALENT CIRCUIT  
W7 761 A  
RE M O TE I/O  
DE VIC E  
NOT  
USED  
E-BUS  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
1
2
E-B  
+
+
C7400A  
C7600C  
S
S
Humidity  
(4 to 20mA)  
Enthalpy  
(4 to 20mA)  
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIR E AVAILABLE, UP TO 14 AWG (2.O MM2 )  
WITH A MINIMUM OF 18 AWG (1.O MM2 ), F OR EAR TH GROUND WIRE.  
1
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
2
Fig. 17. Typical Humidity and Enthalpy (4 to 20mA) sensor wiring diagram. (For note 2, refer to Fig. 15.)  
27  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
WINDOW  
CONTACT  
(CONTACT  
CLOSED =  
WINDOW  
CLOSED)  
OCCUPANCY  
SENSOR  
(CONTACT  
CLOSED =  
OCCUPIED)  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
TRIAC EQUIVALENT CIRCUIT  
W7761A  
REMOTE I/O  
DEVICE  
E-BUS  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
1
E-BUS  
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
M15277  
Fig. 18. Typical Window and Occupancy sensor wiring diagram. (For note 2, refer to Fig. 15.)  
28  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
PWM  
VALVE ACTUATOR  
ML7984B  
LINE POWER  
T6 T5  
C
B
W
R
+
FAN  
24 VAC  
-
CONTACTOR (24 VAC)  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
TRIAC EQUIVALENT CIRCUIT  
W7761A  
REMOTE I/O  
DEVICE  
E-BUS  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
1
E-BUS  
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
M15279  
Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to W7761A. (For note 2, refer to Fig. 15.)  
29  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
MMC325 PNEUMATIC  
TRANSDUCER  
M
M
B
4
1
2
3
PNEUMATIC  
VALVE  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
TRIAC EQUIVALENT CIRCUIT  
W7761A  
REMOTE I/O  
DEVICE  
E-BUS  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
5
REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION  
(DIRECT/REVERSE).  
1
2
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN:  
REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.  
3
4
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.  
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE  
6 FT. (1.8M) OR LONGER.  
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
5
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
M15278  
Fig. 20. Typical Pneumatic transducer (Series 60 - Floating) to W7761A.  
E-Bus Termination Module  
One E-Bus Termination Module, part number 209541B is required for a single terminated E-Bus or two E-Bus Termination  
Module, part number 209541B for a double terminated E-Bus (see Fig. 21). Refer to the E-Bus Wiring Guidelines form, 74-  
2865 for termination module placement rules.  
30  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
W7753A  
W7753A  
W7753A  
1415  
1415  
1415  
ORANGE  
BROWN  
BROWN  
PART NO. 209541B  
ORANGE  
PART NO. 209541B  
TERMINATION  
MODULE  
TERMINATION  
MODULE  
M12690  
Fig. 21. Typical E-Bus termination module wiring diagrams (place a wire nut on each remaining wire that is not  
connected to a controller or device).  
See Fig. 22 for E-Bus termination wiring options.  
31  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Fig. 22. E-Bus termination wiring options.  
32  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Step 5. Order Equipment  
After compiling a bill of materials through completion of the previous application steps, refer to Table 8 for ordering information.  
Contact Honeywell for information about Controllers and Wall Modules with no logo.  
Table 8. Excel 10 W7761A Device Ordering Information.  
Part Number  
Product Description  
Excel 10 W7761A  
Comments  
W7761A2002  
Remote Input/Output Device  
Excel 10 W7750 Controllers:  
Constant Volume AHU Controller (W7750A)  
Constant Volume AHU Controller (W7750B)  
T7770 Wall Modules:  
W7750A1007  
W7750B1005  
T7770A1006  
T7770A1014  
T7770A2004  
T7770A2012  
T7770B1004  
Sensor with Honeywell Logo (Not used with RIO)  
Sensor with No Logo (Not used with RIO)  
Sensor with Network Jack and Honeywell Logo  
Sensor with Network Jack and No Logo  
Used with Excel 5000 and Excel 10 Controllers  
Used with Excel 5000 and Excel 10 Controllers  
Used with Excel 5000 and Excel 10 Controllers  
Used with Excel 5000 and Excel 10 Controllers  
Sensor with Setpoint and Network Jack, Honeywell Degrees F Absolute. Sensor—(current feature  
Logo that can be used with the RIO Device).  
T7770B1046  
T7770B1012  
T7770B1020  
T7770B1053  
T7770B1038  
T7770C1002  
T7770C1044  
T7770C1010  
T7770C1028  
T7770C1051  
T7770C1036  
T7770D1000  
T7770D1018  
T7780A1004  
T7780A1012  
Sensor with Setpoint and Network Jack, Honeywell Relative Setpoint. Sensor—(current feature  
Logo that can be used with the RIO Device).  
Sensor with Setpoint and Network Jack, No Logo Degrees F Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint and Network Jack, Honeywell Degrees C Absolute. Sensor—(current feature  
Logo  
that can be used with the RIO Device).  
Sensor with Setpoint and Network Jack, No Logo Relative Setpoint. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint and Network Jack, No Logo Degrees C Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, Honeywell Logo  
Degrees F Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, Honeywell Logo  
Relative Setpoint. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, No Logo  
Degrees F Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, Honeywell Logo  
Degrees C Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, No Logo  
Relative Setpoint. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Setpoint, Bypass/LED and Network  
Jack, No Logo  
Degrees C Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Bypass/LED and Network Jack,  
Honeywell Logo  
Degrees F Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor with Bypass/LED and Network Jack, No  
Logo  
Degrees C Absolute. Sensor—(current feature  
that can be used with the RIO Device).  
Sensor, Digital Display Wall Module with Network Degrees F Absolute (default)  
Jack, Honeywell Logo  
Sensor, Digital Display Wall Module with Network Degrees F Absolute (default)  
Jack, No Logo  
Sensors:  
C7770A1006  
Air Temperature Sensor. 20 Kohm NTC  
nonlinearized  
Duct-mounted sensor that functions as a  
primary and/or secondary sensor.  
(continued)  
33  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table 8. Excel 10 W7761A Device Ordering Information (Continued).  
Part Number  
Product Description  
Comments  
Sensors (Continued):  
C7031J1050  
Averaging Discharge/Return Air Temperature  
Sensor. 20 Kohm NTC  
Duct element cord length 12 ft. (3.7m)  
Use 112622AA Immersion Well  
C7031B1033  
Discharge Air or Hot Water Temperature Sensor.  
20 Kohm NTC  
C7031C1031  
C7031D1062  
Duct Discharge/Return Air Sensor. 20 Kohm  
18 in. (457mm) insertion length.  
Hot or chilled Water Temperature Sensor. 20 Kohm  
NTC  
C7031K1017  
C7100A1015  
C7170A1002  
Hot or chilled Water Temperature Sensor. 20 Kohm Strap-on  
NTC  
Averaging Discharge/Return Air Temperature  
Sensor. PT3000  
13 in. (330mm) insertion length.  
Outdoor Air Temperature Sensor. PT3000  
Echelon® Based Components and Parts:  
Excel 10 Zone Manager  
Q7750A1003  
Q7751A2002  
Q7752A2001  
Q7740A1008  
Free Topology Tranceiver (FTT)  
Router  
(FTT)  
(FTT)  
Serial Interface  
Excel 10 2-Way Repeater  
Used to extend the length of the E-Bus.  
Contains built in termination modules.  
Q7740B1006  
Excel 10 4-Way Repeater  
Used to extend the length of the E-Bus.  
Contains built in termination modules.  
XD 505A  
XD 508  
Standard C-Bus Communications Submodule  
C-Bus Communications Submodule (1 megabit baud  
rate)  
209541B  
205979  
Termination Module  
One or two required per E-Bus segment  
Serial interface to wall module or controller  
Operator Terminal Cable for E-Bus  
Accessories:  
EL7680A1008  
EL7628A1007  
Wall Mounted Wide View Infrared Occupancy  
Sensor  
Ceiling Mounted Infrared Occupancy Sensor  
Ultrasonic Occupancy Sensors  
EL7611A1003,  
EL7612A1001  
EL7630A1003,  
EL7621A1002,  
EL7621A1010  
Power Supply/Control Units for Occupancy sensors  
C7400A1004  
C7600B1000  
C7600C1008  
C7600C1018  
Solid State Enthalpy Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
Solid State Humidity Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
For outdoor and return air enthalpy  
For outdoor and return air humidity  
For outdoor and return air humidity  
For outdoor and return air humidity  
Use to control Pneumatic reheat valves  
MMC325-010,  
MMC325-020  
Pneumatic Retrofit Transducers.  
Select pressure range: (010) 0 to 10 psi (68.97 kPa)  
or (020) 0 to 20 psi (137.93 kPa).  
MMCA530  
DIN rail adapter for MMC325 Transducers  
Metal enclosure for MMC325 Transducers  
Valve Actuator Pulse Width Modulation (PWM)  
Damper Actuator Series 60  
MMCA540  
ML7984B3000  
ML6161B1000  
M6410A  
Use with V5011 or V5013 F and G Valves  
Use with V5812/V5813 Valves  
Use with V5011 and V5013 Valves  
Valve Actuator Series 60  
ML684A1025  
ML6464A1009  
Versadrive Valve Actuator with linkage, Series 60  
Direct Coupled Actuator, 66 lb-in., Series 60  
(continued)  
34  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table 8. Excel 10 W7761A Device Ordering Information (Continued).  
Part Number  
Product Description  
Comments  
Accessories (Continued):  
ML6474A1008  
Direct Coupled Actuator, 132 lb-in. torque, Series 60  
Direct Coupled Actuator, 50 lb-in. spring return  
Wall Mounted Wide View Infrared Occupancy Sensor  
Ceiling Mounted Infrared Occupancy Sensor  
Ultrasonic Occupancy Sensors  
ML6185A1000  
EL7680A1008  
EL7628A1007  
Series 60  
EL7611A1003,  
EL7612A1001  
EL7630A1003,  
EL7621A1002,  
EL7621A1010  
Power Supply/Control Units for Occupancy sensors  
C7400A1004  
C7600B1000  
C7600C1008  
C7600C1018  
Solid State Enthalpy Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
Solid State Humidity Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
For outdoor and return air enthalpy  
For outdoor and return air humidity  
For outdoor and return air humidity  
For outdoor and return air humidity  
Use to control Pneumatic reheat valves  
MMC325-010,  
MMC325-020  
Pneumatic Retrofit Transducers.  
Select pressure range: (010) 0 to 10 psi (68.97 kPa)  
or (020) 0 to 20 psi (137.93 kPa).  
MMCA530  
DIN rail adapter for MMC325 Transducers  
Metal enclosure for MMC325 Transducers  
Valve Actuator Pulse Width Modulation (PWM)  
Damper Actuator Series 60  
MMCA540  
ML7984B3000  
ML6161B1000  
M6410A  
Use with V5011 or V5013 F and G Valves  
Valve Actuator Series 60  
Use with V5812/V5813 Valves  
ML684A1025  
ML6464A1009  
ML6474A1008  
ML6185A1000  
V5812A  
Versadrive Valve Actuator with linkage, Series 60  
Direct Coupled Actuator, 66 lb-in., Series 60  
Direct Coupled Actuator, 132 lb-in. torque, Series 60  
Direct Coupled Actuator, 50 lb-in. spring return  
Two-way terminal unit water valve; 0.19, 0.29, 0.47,  
Use with V5011 and V5013 Valves  
Series 60  
Use with M6410 Valve Actuator. Close-off  
0.74, 1.2, and 1.9 C 1/2 in. npt (13 mm) or  
rating for 0.19 to 1.9 C is 65 psi; for 2.9  
v
v
2.9 and 4.9 C 3/4 in. npt (19 mm)  
and 4.9, C is 45 psi. (Coefficient of  
v
v
volume or capacity index C = gallons per  
minute divided by the square root of the  
pressure drop across the valve.)  
v
V5813A  
R8242A  
Three-way mixing terminal unit hot water valve; 0.19, Use with M6410 Valve Actuator. Close-off  
0.29, 0.47, 0.74, 1.2, and 1.9 C 1/2 in. npt (13 mm) rating 0.19 to 0.74 C is 55 psi; 1.2, and  
v
v
or 2.9 and 4.9 C 3/4 in. npt (19 mm)  
1.9 C is 22 psi; 2.9 and 4.9 C is 26 psi.  
v
v
v
Contactor, 24 Vac coil, DPDT  
AT72D, AT88A, AK3310, etc. Transformers  
EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)  
Obtain locally: A controller requires 5 in.  
Augat Inc. part number 2TK2D DIN rail (adapter)  
Purchase from Augat Inc. two DIN rail  
adapters for each controller  
Serial Interface Cable, male DB-9 to female DB-9 or  
female DB-25.  
Obtain locally from any computer  
hardware vendor.  
Cabling  
Honeywell AK3791 (one  
twisted pair) AK3792 (two  
twisted pairs)  
E-Bus (plenum): 22 AWG (0.34 mm2) twisted pair  
solid conductor, nonshielded or Echelon approved  
cable.  
Level IV 140°F (60°C) rating  
Honeywell AK3781 (one  
twisted pair) AK3782 (two  
twisted pairs)  
E-Bus (nonplenum): 22 AWG (0.34 mm2) twisted pair Level IV 140°F (60°C) rating  
solid conductor, nonshielded or Echelon approved  
cable.  
Honeywell AK3725  
Inputs: 18 AWG (1.0 mm2) five wire cable bundle  
Standard thermostat wire  
(continued)  
74-2699  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table 8. Excel 10 W7761A Device Ordering Information (Continued).  
Part Number  
Product Description  
Comments  
Cabling (Continued):  
Honeywell AK3752  
(typical or equivalent)  
Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2)  
NEC Class 2 140°F (60°C) rating  
Non-plenum  
Honeywell AK3702  
(typical or equivalent)  
18 AWG (1.0 mm2) twisted pair  
16 AWG (1.3 mm2) twisted pair  
14 AWG (2.0 mm2) two conductor  
Honeywell AK3712  
(typical or equivalent)  
Non-plenum  
Honeywell AK3754  
Non-plenum  
(typical or equivalent)  
Step 6. Configure Devices  
Excel E-Vision PC Software is used to configure W7761A Devices to match their intended application. The E-Vision User  
Guide form, 74-2588 provides details for operating the PC software.  
Step 7. Troubleshooting  
Troubleshooting Excel 10 Controllers and Wall Modules  
In addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product.  
See the Applicable Literature section for form numbers.  
Temperature Sensor and Setpoint Potentiometer Resistance Ranges  
The T7770 Wall Module or the C7770A Air Temperature Sensor has the following specified calibration points, which are plotted  
in Fig. 23:  
Temperature (°F)  
Resistance Value (ohms)  
99  
85  
70  
55  
45  
11,520  
16,301  
24,039  
36,280  
48,000  
80K  
70K  
60K  
50K  
40K  
30K  
20K  
20K OHM AT  
77oF (25oC)  
10K  
80  
30  
0
40  
50  
10  
TEMPERATURE (DEGREES)  
60  
70  
90  
100  
110 oF  
oC  
20  
40  
30  
M5874A  
Fig. 23. Temperature sensor resistance plots.  
Alarms  
When an Excel 10 has an alarm condition, it reports it to the central node on the E-Bus (typically, the Excel 10 Zone Manager).  
See Table 9. Information contained in an alarm message is:  
Subnet Number:  
E-Bus subnet that contains the Excel 10 node that has the alarm condition. Subnet 1 is on the Zone Manager side of the  
router; Subnet 2 is on the other side.  
Node Number:  
Excel 10 node that has the alarm condition (see Network Status).  
Alarm Type:  
Specific alarm being issued. An Excel 10 can provide the alarm types listed in Table 9.  
36  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table 9. Excel 10 Alarms.  
Alarm type  
Name of alarm or error bit  
number  
Meaning of alarm code or error bit  
RETURN_TO_NORMAL  
128U  
Return to no alarm after being in an alarm condition. This code is added  
numerically to another alarm code to indicate that the alarm condition has  
returned to normal.  
ALARM_NOTIFY_DISABLED 255U  
The alarm reporting has been turned off by the DestManMode. No more  
alarms are reported via nvoAlarm until DestManMode turns on alarm repor  
or upon application restart.  
NO_ALARM  
0
1
No alarms presently detected.  
INPUT_NV_FAILURE  
One or more NV inputs have failed in receiving an update within their spec  
FAILURE_DETECT_TIME.  
NODE_DISABLED  
2
The control algorithm has stopped because the RIO device is in  
DISABLED_MODE, MANUAL, or FACTORY_TEST mode. No more alarms  
reported when the device is in the DISABLED_MODE. Alarms continue to  
reported if the device is in the MANUAL or FACTORY_TEST mode. The  
control is shut down and disabled until power is cycled or the node is reset  
See note 1 below.  
SENSOR_FAILURE  
3
One or more sensors have failed.  
NOTE: The node can be reset by switching the node to MANUAL and then to the normal operating mode.  
Also, the Excel 10 variables, AlarmLogX where X is 1 through 5, that store the last five alarms to occur in the device, are  
available. These points can be viewed through XBS or E-Vision.  
Broadcasting the Service Message  
The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the device ID  
number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building.  
There are two methods of broadcasting the Service Message from an Excel 10 W7761A Device. One uses a hardware service  
pin button on the side of the device (see Fig. 24). The other involves using the PC Configuration tool, as follows.  
The commissioning tool is used to perform the ID Assignment task (see the E-Vision User’s Guide form, 74-2588).  
SERVICE  
PIN  
BUTTON  
M10094  
Fig. 24. Location of the Service Pin Button.  
W7761A Device Status LED  
The LED on the front and center of a W7761A Device provides a visual indication of the status of the device. See Fig. 25.  
When the W7761A receives power, the LED should appear in one of the following allowable states (see Table 10):  
37  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table 10. LED States.  
Hardware or  
Software Failure  
Service LED Blink Rate  
(Cycles per second)  
Alarm Condition  
None  
None  
1
Any alarm condition None  
Don't Care Failed  
2
steady ON or OFF  
1. Off—no power to the processor.  
2. Continuously On—processor is in initialized state.  
3. Slow Blink—controlling, normal state.  
4. Fast Blink—when the Excel 10 has an alarm condition.  
W7750  
STATUS`  
LED  
M10095  
Fig. 25. LED location on W7761A.  
T7780 DDWM Bypass Pushbutton  
See Fig. 26 for the T7780 DDWM bypass pushbutton location (occupied or unoccupied). The T7780 DDWM has two methods  
for generating its neuron ID, shorting two pads or winking.  
1. Pressing the bypass pushbutton whenever a Carat () on the bottom of the LCD display is flashing (Menu Selection  
Mode).  
2. Pressing the bypass pushbutton when the T7780A DDWM is in wink mode (LCD display shows WINK when E-Vision  
sends a Service Message out on the E-Bus).  
When the space covered by the T7780 DDWM is in Occupied mode, the sun symbol is shown on the left side of the LCD  
display. When the space is in Standby mode, the half-sun symbol is shown. When the space is in Unoccupied mode, the moon  
symbol is shown.  
38  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
T7780A  
BYPASS  
PUSHBUTTON  
M11616  
Fig. 26. Bypass pushbutton location on T7780 DDWM.  
APPENDICES  
Appendix A. Using E-Vision to Commission a W7761 Device.  
CARE/E-Vision must be used to configure the W7761 device. The inputs and outputs will be configured through the application  
selection menu (see E-Vision user guide form, 74-2588). The RIO does not contain control loops for directly controlling the  
digital outputs, therefore the Zone Manager or some other device has to be bound to the outputs to perform the control  
function. Refer to the CARE User’s Manual form, 74-5587 to add Control Strategy, Switching Logic, or Time Programs for  
control of the RIO digital outputs. Refer to the E-Vision user guide (form, 74-2588 for the RIO commissioning procedure and  
updating/downloading of the Zone Manager files.  
NOTE: The RIO device does not synchronize the floating digital outputs. This function (position is synchronized whenever an  
endpoint is reached (full open or full close).and when the elapsed time since the last synchronization is 24 hours)  
must be done by the controlling device (such as the Zone Manager).  
SENSOR CALIBRATION  
The resistive temperature sensors and voltage/current inputs can all be calibrated. The wall module setpoint potentiometer is  
not supported on the W7761A. Perform the sensor calibration by adding an offset value (either positive or negative) to the  
sensed value using E-Vision menus (see E-Vision user guide form, 74-2588).  
When calibrating voltage/current sensors on the W7761A, the offset amount entered by the user is in volts, regardless of the  
inputs actual engineering units. See Appendix E for information on how to derive the proper voltage value to enter as an offset  
during calibration.  
CUSTOM MAPPING  
The RIO default CARE plant contains all available points that are supported on the RIO device. If the RIO plant was  
customized by deleting unused points, then the Custom mapping feature will have to be used to add points back into the plant  
so that they can be used or monitored by other devices. The following procedures will describe the Custom mapping process  
for adding analog/digital inputs and digital outputs.  
ADDING ANALOG INPUTS - ENTHALPY (4 to 20 mA)  
To add an enthalpy (outdoor or return air) sensor to an RIO plant, the user must add a software point (pseudo analog) that can  
be mapped to the actual hardware input through the Custom Mapping function of E-Vision. The following procedure will instruct  
the user on adding the pseudo analog and using the Custom Mapping function. This allows the enthalpy input to be used with  
other Excel 10 controllers (referenced) on the E-Bus, used in Zone Manager control strategy or switching logic, or be used with  
Excel 5000 controllers on the C-Bus.  
1. With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the  
pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to  
add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point.  
39  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into  
switching logic. Select the Software Points menu item and then Pseudo Analog. The Create/Select Software Point <Va>  
dialog box will be displayed. Type in a New point name for the enthalpy sensor (such as OaEnthaply) and click on the OK  
button. The new point that was just created will be added to the screen as the header point for switching logic table and  
also added to the Point List . Select the Cancel button to exit the Create/Select Software Point <Va> dialog box. Exit  
switching logic by selecting the File menu item and Exit. CARE will display the Delete Unused Software Points list box.  
Click the Cancel button to continue.  
2. Go into the Data Point Editor (Controller/Edit/Data Point Editor) and under Point select the pseudo analog point that was  
just created and click the OK button. Select the drop down list for the Engineering Unit and scroll through the list until the  
mA (mA matches the engineering unit of the RIO input) engineering units are displayed. Select the mA engineering unit  
that is shown with one decimal place (number 66) and click the OK button to save the selection. Cancel the User  
Address list box and select File/Exit to exit out of the Data Point Editor.  
3. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the Project and Export to E-  
Vision menu items. Type in the name of the Zone Manager Export file when the Export Zone Manager dialog box is  
displayed. Select the project and the Zone manager within that project that is being exported and click the Export button.  
Exit CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created above. Once  
the project is open, select the RIO device that the enthalpy sensor is connected to and go into the Application Selection  
screen (offline) by selecting the Controller, then the Application Selection menu items. From the Inputs tab of the  
Application Selection dialog box, add Oa_Enthalpy to either analog input 5 or 6 and select the OK button to save the  
selection.  
4. Select the Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo  
analog point. If this function has already been performed before, the user will be prompted with the message CARE  
Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the  
import is finished, E-Vision displays the message CARE Export File has been imported. Select OK to continue.  
5. Select the Network menu item and then Map C-Bus Points. Select RIO1 as the Controller Type from the Map C-Bus  
Points dialog box. Under Unmapped CARE, select the name of the RIO device that the enthalpy sensor was added to in  
CARE. Under Unmapped Excel 10, select the name of the RIO device that the actual enthalpy sensor was added to  
(both names should be the same). Next, select the Custom button and the Custom Mapping CARE Points dialog box will  
be displayed. Select the OaEnthalpy point under CARE Points and CurrentAI under Excel 10. CurrentAI is the user  
address in the RIO device that contains the actual sensor value for the OaEnthalpy (C7400A1004, 4 to 20 mA device).  
Select the Map button to add the OaEnthalpy point to the list of Mapped Points. Click on the Close button to exit the  
Custom Mapping CARE Points dialog box. Click on the Close button to exit the Map C-Bus Points dialog box.  
6. To use the OaEnthalpy custom mapped point with other Excel 10 controllers on the E-Bus, select the Network menu item  
and Refer Excel 10 Points. Select the RIO device name as the Source Excel 10 and then scroll down the list of Excel 10  
Points: until you reach CurrentAI and select it. Select an Excel 10 controller from the Destination Excel 10 list. For  
example if the user had selected a CVAHU controller from the Destination Excel 10 list, the user would select from the  
Excel 10 Points list as the destination point and then click on the Add button to add the point association (Binding)  
between the RIO and CVAHU controllers. If DestOaEnth is already being used in an association, then the message At  
Least one of the output network variables is in an existing connection and E-Vision will not allow this association to be  
added. In order to add this association, the user has to remove any other associations with the DestOaEnth point. Select  
the Close button to exit out of the Refer Excel 10 Points dialog box. Any controllers involved in the new association or  
change in an existing association will require commissioning.  
7. Select the Controller menu item and the Update Zone Manager Files. E-Vision will add the custom mapping information  
to the Zone Manager files. When the Update Zone Manager Files function is done, commission any controllers that need  
to be commissioned, then close the E-Vision project and exit out of E-Vision.  
8. Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and  
start XI584 by selecting the Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities and File  
Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select  
Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE  
Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set  
by the XI581 Emulation function (Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and  
select Download. The Download dialog box will be displayed. Check the All selection and click the Controller button.  
When the Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is high  
lighted and select the OK button. Click the Download button and click Yes to the message Replace updated application  
part in controller (CPU address or Controller name). When the download is complete, exit out of the Download dialog  
box. From the XI584 main menu, select the Data, Access by User Address menu items. Type OaEnthalpy in the Search  
For User Address and click the Search button. When the OaEnthalpy point displays in the User Addresses list, click on  
the point and select the Attributes button. XI584 will now display the value of the enthalpy sensor connected to the RIO  
device. This point can now be used in the Zone Manager control strategy or switching logic. This point can be used in  
other Excel 5000 (C-Bus) controllers by assigning a global analog point in the destination controller with the user address  
name of OaEnthalpy. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points in Excel  
5000 controllers.  
ADDING OTHER VOLTAGE/CURRENT SENSORS  
See Table A-1 for the supported Voltage/Current analog input sensors that can be connected to the RIO Device. The user  
must add a software point (pseudo analog - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant)  
through the Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA)  
sensor should be followed and instructs the user on adding the pseudo analog point in the RIO CARE Plant and using the  
40  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in  
the Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.  
Table A-1. Supported Voltage And Current Input Sensors.  
E-Vision Enumerated Name in the Input  
Application Selection Tab  
RIO Network Variable that contains the  
Hardware Input Value  
RA_Hum_C7600C  
OA_Hum_C7600C  
Filter_Diff_Pres  
RA_Hum_C7600B  
OA_Hum_C7600B  
RA_Enthalpy  
Humidity1 or Humidity2  
Humidity1 or Humidity2  
Pressure1 or Pressure2  
Humidity1 or Humidity2  
Humidity1 or Humidity2  
CurrentAI  
OA_Enthalpy  
CurrentAI  
Space_CO2  
CO2Level  
Voltage_Monitor  
VoltageAI  
ADDING DIGITAL INPUTS  
See Table A-2 for the supported Digital input types that can be connected to the RIO Device. The user must add a software  
point (pseudo digital nstate - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the  
Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should  
be followed. The user will add a Pseudo Digital nstate point (<Vd>) in step one instead of the Pseudo Analog to the RIO CARE  
Plant and then use the Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the  
E-Bus, that are used in Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.  
Table A-2. Supported Digital Input Types.  
E-Vision Enumerated Name in the Input  
Application Selection Tab  
RIO Network Variable that contains the  
Hardware Input Value  
Digital Input 1:  
Active_Short / Active_Open  
SrcDigIn1Sts  
SrcDigIn2Sts  
SrcDigIn3Sts  
SrcDigIn4Sts  
Digital Input 2:  
Active_Short / Active_Open  
Digital Input 3:  
Active_Short / Active_Open  
Digital Input 4:  
Active_Short / Active_Open  
ADDING DIGITAL OUTPUTS  
See Table A-3 for the supported digital output types that can be connected to the RIO Device.  
The user must add a software point (pseudo analog) that can be mapped to the actual hardware output through the Custom  
Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom  
Mapping function so that the Digital Output can be used in the Zone Manager control strategy or switching logic, or be used  
with Excel 5000 controllers on the C-Bus.  
1. With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the  
pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to  
add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point.  
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into  
switching logic. Select the Software Points menu item and then Pseudo Analog. The Create/Select Software Point <Va>  
dialog box will be displayed. Type in a New point name for the Digital Output (such as MiscExhFan) and click on the OK  
button. The new point that was just created will be added to the screen as the header point for switching logic table and  
also added to the Point list. Select the Cancel button to exit the Create/Select Software Point <Va> dialog box. Exit  
switching logic by selecting the File menu item and Exit. CARE will display the Delete Unused Software Points list box.  
Click the Cancel button to continue.  
2. Go into the Data Point Editor (Controller/Edit/Data Point Editor) and under Point select the pseudo analog point that was  
just created and the OK button. Select the drop down list for the Engineering Unit and scroll through the list until the Pct  
engineering units are displayed. Select the Pct engineering unit that is shown with one decimal place (number 55) and  
the OK button to save the selection. Cancel the User Address list box and select File/Exit to exit out of the Data Point  
Editor.  
3. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the Project and Export to E-  
Vision menu items. Type in the name of the Zone Manager Export file when the Export Zone Manager dialog box is  
41  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
displayed. Select the project and the Zone manager within that project that is being exported and the Export button. Exit  
CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created previously. Once  
the project is open, select the RIO device that the Digital Output is connected to and go into the Application Selection  
screen (offline) by selecting the Controller, Application Selection menu items. From the Outputs tab of the Application  
Selection dialog box, select the first Unused_DigOutput and scroll up until Discrete1 is displayed and select it. Select the  
OK button to save the selection.  
4. Select the Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo  
analog point. If this function has already been performed before, the user will be prompted with the message CARE  
Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the  
import is finished, E-Vision displays the message CARE Export File has been imported. Select OK to continue.  
5. Select the Network menu item and then Map C-Bus Points. Select RIO1 as the Controller Type from the Map C-Bus  
Points dialog box. Under Unmapped CARE, select the name of the RIO device that the Digital Output was added to in  
CARE. Under Unmapped Excel 10, select the name of the RIO device that the actual Digital Output was added to (both  
names should be the same). Next, select the Custom button and the Custom Mapping CARE Points dialog box will be  
displayed. Select the MiscExhFan point under CARE Points and DigOut1Cmd under Excel 10. Select the Map button to  
add the MiscExhFan point to the list of Mapped Points. Click on the Close button to exit the Custom Mapping CARE  
Points dialog box. Click on the Close button to exit the Map C-Bus Points dialog box.  
6. Re-commission the RIO device that had the custom mapping done.  
7. Select the Controller menu item and the Update Zone Manager Files. E-Vision will add the custom mapping information  
to the Zone Manager files. When the Update Zone Manager Files function is done, close the E-Vision project and exit out  
of E-Vision.  
8. Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and  
start XI584 by selecting the Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities, File  
Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select  
Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE  
Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set  
by the XI581 Emulation function (Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and  
select Download. The Download dialog box will be displayed. Check the All selection and click the Controller button.  
When the Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is  
highlighted and select the OK button. Click the Download button and Yes to the message Replace updated application  
part in controller (CPU address or Controller name). When the download is complete, exit out of the Download dialog  
box. From the XI584 main menu, select the Data, Access by User Address menu items. Type MiscExhFan in the Search  
For User Address and click on the Search button. When the MiscExhFan point displays in the User Addresses list, click  
on the point and select the Attributes button. XI584 will now display the value of the Digital Output connected to the RIO  
device. To command the MiscExhFan to the On mode, put the point in the Manual mode and enter a value of 1.0 or  
greater. To command the MiscExhFan to the Off mode, put the point in the Manual mode and enter a value of 0.0. This  
point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be  
used in other Excel 5000 controllers (C-Bus) by assigning a global analog point in the destination controller with the user  
address name of MiscExhFan. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points  
in Excel 5000 controllers.  
Table A-3. Supported Digital Output Types.  
E-Vision Enumerated Name in the Output  
Application Selection Tab  
RIO Network Variable that contains the  
Hardware Output Value  
Float1_Open through Float8_Open (Series 60 - DigOut1Cmd through DigOut8Cmd  
requires two outputs assigned. Float1_Open  
must be assigned before Float1_Close)  
Float1_Close through Float8_Close (Series 60  
- requires two outputs assigned. Float1_Open  
must be assigned before Float1_Close)  
DigOut1Cmd through DigOut8Cmd  
Discrete1 through Discrete8 (Maintained On/Off DigOut1Cmd through DigOut8Cmd  
outputs)  
Modulate1 through Modulate8 (PWM outputs)  
DigOut1Cmd through DigOut8Cmd  
Appendix B. Sequences of Operation.  
Common Operations  
The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with  
the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for  
VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and  
digital sensors could be shared or bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus  
through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring  
other elements such as return humidity, IAQ, etc. to achieve better control.  
Room Temperature Sensor (RmTemp)  
42  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
The T7770A,B,C,D wall module is the room space temperature sensor—(current feature that can be used with the RIO  
Device). When it is configured, it provides the temperature input that can be shared with the W7750 or W7751 controllers. If  
there are multiple space sensors in a area controlled by one W7750 CVAHU, then the space temperatures can be wired into  
the W7761A controller and mapped to the Zone Manager. The Zone Manager can average all of the space temperatures and  
then have that value can be bound to the W7750 controlling that area.  
Window Sensor (StatusWndw)  
The digital input for a window contact can be wired into the W7761A device and then bound to a W7750 CVAHU to disable its  
temperature control algorithm if someone has opened a window or door in the room or area that the W7750 is serving. When a  
window is detected to be Open (digital input contacts Open equals window open), the normal temperature control is disabled,  
and the W7750 Controller enters the Freeze Protect mode. Freeze Protect mode sets the space setpoint to 50 °F (10°C) and  
brings on the fan and heat if the space temperature falls below this setpoint. Normal temperature control resumes on window  
closure.  
Dirty Filter Monitor  
The air filter in the air handler can be monitored by a digital input in the W7761A and an alarm issued by the Zone Manager  
when the filter media needs replacement. The two methods of monitoring the filter are:  
1. A differential pressure switch whose contacts are connected to a digital input on the W7761A and;  
2. A 2 to 10V differential pressure sensor wired to a voltage input on the W7761A. If the analog input sensor is used, its  
measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint in the Zone Manager, the  
comparison is done in the Zone Manager - valid range: 0 to 5 inw (0 to 1.25 kPa), and the Dirty Filter alarm is issued by  
the Zone Manager when the pressure drop across the filter exceeds the setpoint.  
Series 60 Modulating Control  
Series 60 Control is also commonly referred to as Floating Control. The Excel 10 W7761A Device can drive Series 60 type  
actuators to control a modulating damper or valve actuator. The W7761A device contains no control software, so these outputs  
would have to be bound to either the Zone Manager or other Excel 10 controllers. When floating control is used, the full-stroke  
motor drive time of the actuator must be entered into the configuration parameter DO1FlSpeed (for output 1), DO2FlSpeed (for  
output 2). When Floating control is configured, two digital outputs are required, so the user has to change the configuration  
parameter for the appropriate digital outputs.  
Pulse Width Modulating (PWM) Control  
The Excel 10 W7761A device can drive a PWM-type actuator to control a modulating actuator. The W7761A device contains  
no control software, so these outputs would have to be bound to either the Zone Manager or other Excel 10 controllers. PWM  
control positions the actuator based on the length, in seconds, of the pulse from the digital output. The controller outputs a  
pulse whose length consists of two parts, a minimum and a maximum. The minimum pulse time represents the analog value of  
zero percent (also indicates a signal presence) and the maximum pulse length that represents an analog value of 100 percent.  
If the analog value is greater than zero percent, an additional time is added to the minimum pulse time. The length of time  
added is directly proportional to the magnitude of the analog value. If PWM control is used, the configuration parameters for  
the PWM operation must be specified. These parameters are DO1PWMPeriod and PWMZeroScale, and PWMFullScale.  
Example: To find the pulse width of a valve actuator (for example stroke mid position - 50 percent) with the PWMZeroScale =  
0.1 seconds, PWMFullScale = 25.5 seconds, and the PWMPeriod = 25.6 seconds. There are 256 increments available, so the  
number of increments required for 50 percent would be (0.5 X 256) or 128. The time for each increment for this industry  
standard pulse time is 0.1 seconds. The pulse width is the minimum time (0.1 second) + the number of increments (128 times  
the seconds added 0.1) = 12.9 seconds. The W7750B Controller would command the valve output on for 12.9 seconds every  
25.6 seconds to maintain the valve position at 50 percent.  
Indoor Air Quality (IAQ) Override  
The Excel 10 W7761A Device can monitor an IAQ sensor and that input can be bound to a W7750 CVAHU Controller that  
supports an IAQ override feature, that upon detection of poor air quality in the space, allows the economizer dampers to be  
opened above the standard minimum position setting to a value set in EconIAQPos (parameter located in W7750). Two  
different methods of detecting poor air quality are supported, The first is by using an IAQ switch device connected to a digital  
input on the W7761A Device, where a contact closure indicates poor air quality. This digital input would then be bound to the  
W7750 Controller that is serving the area being monitored and would initiate the IAQ override mode. The second is through an  
analog input that connects to a CO2 Sensor (0 to 10V). The measured value of CO2 from this sensor (0 to 2000 ppm) is  
mapped into the Zone Manager where it is compared to a setpoint (parameter located in the Zone Manager). When the CO2  
level is higher than the setpoint, the Zone Manager can initiate an IAQ alarm. A pseudo digital point in the Zone Manager can  
be bound to the W7750 CVAHU Controller which can initiate the IAQ override mode.  
43  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User Addresses.  
C1. Input/Output Points.  
C2. Control Parameters.  
C3. Status Points.  
C4. Configuration Parameters.  
C5. Direct Access And Special Points.  
Table C0 lists the applicable Engineering Units for the analog points found in the W7761A.  
Table C0. Engineering Units For Analog Points.  
English Units (Inch-Pound)  
Standard International Units (SI)  
Measured Item  
Temperature  
Description  
Degrees Fahrenheit  
Abbreviation  
Description  
Degrees Celsius  
Abbreviation  
F
C
Relative  
Delta Degrees Fahrenheit  
DDF  
Degrees Kelvin  
K
Temperature  
Relative Humidity  
Air Flow  
Percent  
%
Percent  
%
Cubic Feet per Minute  
CFM  
PPM  
Meters cubed per hour  
Parts Per Million  
kiloJoules/kilogram  
m3h  
PPM  
kJ/kg  
CO2 Concentration Parts Per Million  
Enthalpy  
British Thermal Units per Pound btu/lb  
of Air  
Differential  
Pressure  
Inches of Water Column  
inw  
kiloPascal  
kPa  
Tables C1 through C5 list all network variables associated with the W7761A Controller and the default User Address names.  
Table C1 lists the Network Variable Inputs and Outputs, which are stored in RAM memory. Table C2 lists the Control  
Parameters, which are the values stored in the controllers EEPROM memory.  
NOTE: Table C2. User Addresses For W7761A Control Parameters. (Control Parameters are stored in EEPROM - limited to  
10,000 writes. Do NOT use as outputs from Control Strategies, Time Programs, or Switching Tables. If these points  
are changed more than 10,000 times, irreversible hardware failure results).  
Tables provides point attributes as follows:  
Engineering  
Units—  
This field indicates the point valid range and displayed Engineering Unit. For digital points, the valid states  
and the corresponding enumerated values are shown.  
Default—  
The value or state of the point on controller start-up.  
Shareable— The point can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel  
10 Points as either a data source or a destination.  
Mappable— The point can be converted into a C-Bus point used by C-Bus devices. A mappable point has a one-to-one  
relationship with a C-Bus User Address.  
Direct  
Access—  
E-Vision  
Monitor—  
The point is accessible through the Subsystem Points mechanism in XBS.  
These points are viewable within the E-Vision Controller Monitoring on-line screen. PAR refers to control  
parameters that are set in the Application Selection dialog boxes in E-Vision.  
Hardware  
Config—  
These are points that involve controller I/O configuration. Any change to HW Config. points causes the  
W7761A to perform an application reset; therefore, these points can only be modified off-line.  
These points are used to set the controller outputs when in manual mode. The W7761A is placed in manual  
mode through a menu selection in the E-Vision Controller Monitor screen.  
Manual—  
Fixable—  
These input points can be set to a constant value in the E-Vision Controller Monitor screen.  
NOTES:  
1. Mapped points can be viewed and changed, if applicable, on C-Bus devices such as an XI581, XI582 and  
XI584 and on an XBS central and E-Vision.  
2. All Excel 10 points, mappable, calibration, configuration and internal data sharing points, can be viewed and  
changed, as allowed, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.  
3. E-Vision - These points are displayed to the user and polled during the E-Vision monitor function. Monitor (M)  
indicates the point appears in the Software list box. Schematic (S) indicates the point is to be displayed on the  
schematic air handler diagram directly. Calibrate (C) - These points are calibratible and the calibration dialog  
(either the temperature or air flow dialog) is displayed. These points are displayed in a listbox by selection of the  
menu item Controller, Calibration. When the user double clicks on these points the calibration dialog is  
displayed. Parameter (P) - This information is displayed to the user in the Application Selection screens. These  
fields are read/write when offline and read only when online.  
4. Manual - These points can be placed in the manual mode. When the user double clicks on these points the  
manual dialog is displayed, this contains radio buttons; one for Auto and one for Manual.  
44  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Left).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
AI1RType  
NvName  
Field Name  
ResistiveIn0  
Default  
ncirioIoSelect  
DA_Temp_PT3000  
0
Unused_Res_AI  
OA_Temp_PT3000  
RA_Temp_PT3000  
Custom_PT3000  
1
2
3
DA_Temp_20KNTC  
RA_Temp_20KNTC  
Space_Temp_T7770  
Custom_20KNTC  
Unused_Res_AI  
4
5
6
7
255  
AI2RType  
AI3RType  
AI4RType  
AI5VType  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
ResistiveIn1  
ResistiveIn2  
ResistiveIn3  
VoltageIn0  
See AI1RType Eng. Units/States  
column for selections  
Unused_Res_AI  
Unused_Res_AI  
Unused_Res_AI  
Unused_Volt_AI  
See AI1RType Eng. Units/States  
column for selections  
See AI1RType Eng. Units/States  
column for selections  
RA_Hum_C7600C  
OA_Hum_C7600C  
Filter_Diff_Pres  
RA_Hum_C7600B  
OA_Hum_C7600B  
RA_Enthalpy  
0
1
2
3
4
5
OA_Enthalpy  
6
Space_CO2  
7
Voltage_Monitor  
Unused_Volt_AI  
8
255  
AI6VType  
ncirioIoSelect  
VoltageIn1  
See AI5VType Eng. Units/States  
column for selections  
Unused_Volt_AI  
(continued)  
45  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Right).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
AI1RType specifies which logical sensor is assigned to which physical analog input  
sensor channel according to the enumerated list shown in the Eng. Units/States  
column.  
X
X
X
X
X
X
X
X
AI2RType: Refer to the description for AI1RType.  
AI3RType: Refer to the description for AI1RType.  
AI4RType: Refer to the description for AI1RType.  
AI5VType specifies which logical voltage or current sensor is assigned to which  
physical analog input sensor channel according to the enumerated list that is  
shown in the Eng. Units/States column.  
X
X
AI6VType: Refer to the description for AI5VType.  
(continued)  
46  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
DestOut1Cmd  
NvName  
Field Name  
Default  
nviRemoteCmd(0)  
percent  
0
-163 to 163  
DestOut2Cmd  
DestOut3Cmd  
DestOut4Cmd  
DestOut5Cmd  
DestOut6Cmd  
DestOut7Cmd  
DestOut8Cmd  
DI1Sel1Type  
nviRemoteCmd(1)  
nviRemoteCmd(2)  
nviRemoteCmd(3)  
nviRemoteCmd(4)  
nviRemoteCmd(5)  
nviRemoteCmd(6)  
nviRemoteCmd(7)  
ncirioIoSelect  
percent -163 to 163  
percent -163 to 163  
percent -163 to 163  
percent -163 to 163  
percent -163 to 163  
percent -163 to 163  
percent -163 to 163  
0
0
0
0
0
0
0
DigitalIn0S1  
Active_Short  
0
Unused_DigInput  
Active_Open  
1
Unused_DigInput  
255  
DI2Sel1Type  
ncirioIoSelect  
DigitalIn1S1  
See DI1Sel1Type Eng.  
Units/States column for  
selections.  
Unused_DigInput  
(continued)  
47  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
X
M
DestOut1Cmd: DestOut1Cmd through DestOut8Cmd corresponds to DO1 through  
DO8. Refer to the Eng. Units/States column for DO1Type for the enumerated  
values that can be assigned to any output channels.  
Note that a selection of FLOAT means that the two DO channels are used for  
output. RIO assumes that the tool makes the proper assignment of enumerated  
values to DO1 through DO8 and also takes the responsibility to avoid assignment  
of multiple or overlapping commands on the same output channels. An example of  
the relationship between nviRemoteCmd and ncirioIoSelect is discribed below:  
RIO is receiving a command to DestOut4Cmd. This can be mapped as one of the  
three output types (Discrete, Modulate, Float_Open, or Float_Close) by DO3Type.  
If the user selects an enumerated value of Discrete2 for DO3Type, this value would  
be stored in (DO2). Then the DestOut4Cmd will command DO2.  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
M
M
M
M
M
M
M
DestOut2Cmd: Refer to the description for DestOut1Cmd.  
DestOut3Cmd: Refer to the description for DestOut1Cmd.  
DestOut4Cmd: Refer to the description for DestOut1Cmd.  
DestOut5Cmd: Refer to the description for DestOut1Cmd.  
DestOut6Cmd: Refer to the description for DestOut1Cmd.  
DestOut7Cmd: Refer to the description for DestOut1Cmd.  
DestOut8Cmd: Refer to the description for DestOut1Cmd.  
X
DI1Sel1Type specifies the sensor type and function connected to DigitalIn0S1  
through DigitalIn3S1. The valid enumerated list of logical digital states for  
DigitalIn0S1 is listed in the Eng. Units/States column.  
X
X
DI2Sel1Type: Refer to the description for DI1Sel1Type.  
(continued)  
48  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
Default  
DI3Sel1Type  
ncirioIoSelect DigitalIn2S1  
ncirioIoSelect DigitalIn3S1  
ncirioIoSelect DigitalIn0S2  
See DI1Sel1Type Eng. Units/States  
column for selections.  
Unused_DigInput  
DI4Sel1Type  
DI1Sel2Type  
See DI1Sel1Type Eng. Units/States  
column for selections.  
Unused_DigInput  
Maintained  
Momentary  
0
Maintained  
1
Unused_DigInput  
255  
DI2Sel2Type  
DI3Sel2Type  
DI4Sel2Type  
DO1Type  
ncirioIoSelect DigitalIn1S2  
ncirioIoSelect DigitalIn2S2  
ncirioIoSelect DigitalIn3S2  
ncirioIoSelect DigitalOut0  
See DI1Sel2Type Eng. Units/States  
column for selections.  
Maintained  
See DI1Sel2Type Eng. Units/States  
column for selections.  
Maintained  
See DI1Sel2Type Eng. Units/States  
column for selections.  
Maintained  
Discrete1  
0
Unused_DigOutput  
Discrete2  
1
Discrete3  
2
Discrete4  
3
Discrete5  
4
Discrete6  
5
Discrete7  
6
Discrete8  
7
Modulate1  
8
Modulate2  
9
Modulate3  
Modulate4  
Modulate5  
Modulate6  
Modulate7  
Modulate8  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
255  
Float1_Open  
Float2_Open  
Float3_Open  
Float4_Open  
Float5_Open  
Float6_Open  
Float7_Open  
Float8_Open  
Float1_Close  
Float2_Close  
Float3_Close  
Float4_Close  
Float5_Close  
Float6_Close  
Float7_Close  
Float8_Close  
Unused_DigOutput  
49  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
DI3Sel1Type: Refer to the description for DI1Sel1Type.  
X
X
X
X
DI4Sel1Type: Refer to the description for DI1Sel1Type.  
DI1Sel2Type specifies the sensor type and function connected to DigitalIn0S2  
through DigitalIn3S2. The valid enumerated list of logical digital states for  
DI1Sel2Type is listed in the Eng. Units/States column.  
X
X
X
X
X
X
X
X
DI2Sel2Type: Refer to the description for DI1Sel2Type.  
DI3Sel2Type: Refer to the description for DI1Sel2Type.  
DI4Sel2Type: Refer to the description for DI1Sel2Type.  
DO1Type specifies which logical digital output function is assigned to the digital  
physical output according to the enumerated list that is shown in the Eng.  
Units/States column.  
50  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
Default  
DO2Type  
ncirioIoSelect  
DigitalOut1  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Unused_DigOutput  
DO3Type  
DO4Type  
DO5Type  
DO6Type  
DO7Type  
DO8Type  
FiftySixtyHz  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
ncirioIoSelect  
nciIoSelect  
DigitalOut2  
DigitalOut3  
DigitalOut4  
DigitalOut5  
DigitalOut6  
DigitalOut7  
FiftySixtyHz  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Unused_DigOutput  
Unused_DigOutput  
Unused_DigOutput  
Unused_DigOutput  
Unused_DigOutput  
Unused_DigOutput  
Sixty  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Refer to the Eng. Units/States  
column for DO1Type for selections  
available.  
Sixty  
Fifty  
0
1
SrcCO2Level  
SrcCurrentAI  
SrcDigIn1Sts  
nvoRemoteCO2  
PPM  
0 to 65535  
0
nvoRemoteCurrent  
nvoRemoteDigIn(0)  
nvoRemoteDigIn(0)  
milliamps  
-20.0 to 200.0  
0
DI1Value  
DI1State  
0 to 255  
0
ST_OFF  
ST_LOW  
ST_MED  
ST_HIGH  
ST_ON  
0
1
2
3
ST_NUL  
4
ST_NUL  
255  
(continued)  
51  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
DO2Type:  
Refer to the description for DO1Type.  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
DO3Type:  
Refer to the description for DO1Type.  
DO4Type:  
Refer to the description for DO1Type.  
DO5Type:  
Refer to the description for DO1Type.  
DO6Type:  
Refer to the description for DO1Type.  
DO7Type:  
Refer to the description for DO1Type.  
DO8Type:  
Refer to the description for DO1Type.  
FiftySixtyHz specifies the power supply frequency. Correctly selecting FiftySixtyHz  
decreases the noise picked up by analog sensor wiring from the power supply.  
When FiftySixtyHz is 1, the power supply frequency is Fifty Hz and when  
FiftySixtyHz is 0, the power supply frequency is Sixty Hz.  
X
X
X
X
X
M
SrcCO2Level is an output network variable corresponding to the voltage or current  
input channel (AI5 or AI6) if the selection for a CO2 sensor was made via  
ncirioIoSelect.  
X
M
SrcCurrentAI is an output network variable corresponding to the voltage or current  
input channel (AI5 or AI6) if the selection for a current sensor was made via  
ncirioIoSelect.  
SrcDigIn1Sts: There are four digital input channels (DI1 through DI4). If any of the  
four channels are configured, the corresponding output network variable will be  
updated with the value whose data type is SNVT_switch.  
X
X
X
M
DI1State: There are four digital input channels (DI1 through DI4). If any of the four  
channels are configured, the corresponding output network variable will be updated  
with the value whose data type is SNVT_switch. Refer to the enumerated list that is  
shown in the Eng. Units/States column.  
(continued)  
52  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
DI2Value  
DI2State  
Default  
SrcDigIn2Sts  
nvoRemoteDigIn(1)  
nvoRemoteDigIn(1)  
0 to 255  
0
Refer to the DI1State enumerated list  
shown in the Eng. Units/States column.  
ST_NUL  
SrcDigIn3Sts  
SrcDigIn4Sts  
nvoRemoteDigIn(2)  
nvoRemoteDigIn(2)  
DI3Value  
DI3State  
0 to 255  
0
Refer to the DI1State enumerated list  
shown in the Eng. Units/States column.  
ST_NUL  
nvoRemoteDigIn(3)  
nvoRemoteDigIn(3)  
DI4Value  
DI4State  
0 to 255  
0
Refer to the DI1State enumerated list  
shown in the Eng. Units/States column.  
ST_NUL  
SrcHumidAI5  
SrcHumidAI6  
SrcPressAI5  
SrcPressAI6  
SrcTempAI1  
SrcTempAI2  
SrcTempAI3  
SrcTempAI4  
SrcVoltageAI  
nvoRemoteHum(0)  
nvoRemoteHum(1)  
nvoRemotePres(0)  
nvoRemotePres(1)  
nvoRemoteTemp(0)  
nvoRemoteTemp(1)  
nvoRemoteTemp(2)  
nvoRemoteTemp(3)  
nvoRemoteVolt  
percent  
-163 to 163  
0
0
0
0
0
0
0
0
0
percent  
-163 to 163  
inw -131.5 to 131.5  
kPa (-32.768 to 32.767)  
inw -131.5 to 131.5  
kPa (-32.768 to 32.767)  
degrees F -40 to 240  
degrees C (-40 to 116)  
degrees F -40 to 240  
degrees C (-40 to 116)  
degrees F -40 to 240  
degrees C (-40 to 116)  
degrees F -40 to 240  
degrees C (-40 to 116)  
Volts  
0.0 to 10.5  
)
53  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C1. Input/Output Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.  
X
X
X
M
DI2State:  
Refer to the description for DI1State.  
SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.  
X
X
X
M
DI3State:  
Refer to the description for DI1State.  
SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.  
X
X
X
X
X
X
M
M
DI4State:  
Refer to the description for DI1State.  
SrcHumidAI5 is an output network variable corresponding to the voltage or current  
input channel (AI5) if the selection for humidity sensor was made via ncirioIoSelect  
for AI5.  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
M
M
M
M
M
M
M
M
SrcHumidAI6 is an output network variable corresponding to the voltage or current  
input channel (AI6) if the selection for humidity sensor was made via ncirioIoSelect  
for AI6.  
SrcPressAI5 is an output network variable corresponding to the voltage or current  
input channel (AI5) if the selection for a pressure sensor was made via  
ncirioIoSelect for AI5.  
SrcPressAI6 is an output network variable corresponding to the voltage or current  
input channel (AI6) if the selection for a pressure sensor was made via  
ncirioIoSelect for AI6.  
SrcTempAI1 is an output network variable corresponding to the analog input  
channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1  
applied to it.  
SrcTempAI2 is an output network variable corresponding to the analog input  
channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2  
applied to it.  
SrcTempAI3 is an output network variable corresponding to the analog input  
channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3  
applied to it.  
SrcTempAI4 is an output network variable corresponding to the analog input  
channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4  
applied to it.  
SrcVoltageAI is an output network variable corresponding to the voltage or current  
input channel (AI5 or AI6) if the selection for a voltage sensor was made via  
ncirioIoSelect.  
54  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C2. Control Parameters (Left).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
nviInUse  
Field Name  
InUseNumber  
Default  
0 to 65534  
0xFFFF  
55  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C2. Control Parameters (Right).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
nviInUse is used by a management node to indicate to all other management  
nodes that it is logged on, to the Excel 10 node and that they should not try to  
interact with any of the Excel 10s network variables. Before the management node  
reads or writes any network variables, the management node checks nviInUse for  
a zero value meaning no other management nodes are already logged on and that  
a management node may log on, to the node. Then the management node writes a  
number, 1 through 65534, to nviInUse and periodically writes the same value to  
indicate that the management node is still logged on. If there are no writes made to  
nviInUse for approximately 60 seconds, then the Excel 10 resets nviInUse to zero  
to automatically log off the management node. Before interacting with any network  
variables, the management node verifies that the nviInUse has not changed. The  
management node logs off by writing 0 to nviInUse.  
During power up, an application restart, or return to on-line from off-line, the Excel  
10 sets nviInUse to 65535 to indicate to the management node that it has returned  
to on-line.  
56  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Left).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
Default  
AlarmNode  
nvoAlarm  
node  
0 to 127  
0
0
AlarmSubnet  
AlarmType  
nvoAlarm  
nvoAlarm  
subnet  
1 to 255  
type  
NO_ALARM  
0
NO_ALARM  
0 to 255  
INPUT_NV_FAILURE  
NODE_DISABLED  
SENSOR_FAILURE  
rINPUT_NV_FAILURE  
rNODE_DISABLED  
rSENSOR_FAILURE  
ALARM_NOTIFY_DISABLED  
1
2
3
129  
130  
131  
255  
AlarmTypeLog0  
nvoAlarmLog  
type0  
Refer to the AlarmType  
NO_ALARM  
enumerated list shown in the  
Eng. Units/States column.  
AlarmTypeLog1  
AlarmTypeLog2  
AlarmTypeLog3  
AlarmTypeLog4  
Errorbyte1  
nvoAlarmLog  
nvoAlarmLog  
nvoAlarmLog  
nvoAlarmLog  
nvoError  
type1  
type2  
type3  
type4  
Refer to the AlarmType  
enumerated list shown in the  
Eng. Units/States column.  
NO_ALARM  
NO_ALARM  
NO_ALARM  
NO_ALARM  
FALSE  
Refer to the AlarmType  
enumerated list shown in the  
Eng. Units/States column.  
Refer to the AlarmType  
enumerated list shown in the  
Eng. Units/States column.  
Refer to the AlarmType  
enumerated list shown in the  
Eng. Units/States column.  
error_bit(0)  
Byte Offset = 0  
Bit Offset = 0  
FALSE  
TRUE  
0
1
ResSensor1Error(AI1)  
(continued)  
57  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Right).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
AlarmNode: is the LonWorks node number (in domain entry 1 of the nodes domain  
table) assigned to the node.  
AlarmSubnet: is the LonWorks subnet number (in domain entry 1 of the nodes  
domain table) to which the node is assigned.  
AlarmType: is the alarm type being issued. When an alarm condition is no longer  
TRUE, type is set to the sum of the alarm conditions numeric value and the  
RETURN_TO_NORMAL numeric value. The type also is recorded in  
AlarmTypeLog0 through AlarmTypeLog4. When a new alarm is detected, just the  
corresponding numeric value for the alarm is reported. Refer to table 9 (Excel 10  
Alarms) in the System Engineering Guide for all the error conditions that may be  
reported.  
X
M
AlarmTypeLog0 (0, 1, 2, 3, 129, 130, 131, 255)  
A supervisory node may poll the AlarmTypeLog output for a short alarm history. The  
last five alarm reports sent via nvoAlarm are reported via AlarmTypeLog. When  
ALARM_NOTIFY_DISABLED is entered into the log, further alarms or return to  
normals are not entered into the log, until alarm reporting is again enabled. If  
nvoAlarm is bound and not being acknowledged, the last alarm report entered into  
the AlarmTypeLog is the one that was not acknowledged.  
See nvoAlarm and for related subjects.  
type ( n ) specifies the alarm that was issued via nvoAlarm. See nvoAlarm for the  
alarm types used in AlarmTypeLog. The newest alarm is reported in type( 0 ) and  
the oldest is reported in type( 4 ). When a new entry is made to the log, the oldest  
entry is lost.  
X
X
X
X
X
M
M
M
M
M
AlarmTypeLog1:  
Refer to the description for AlarmTypeLog0.  
AlarmTypeLog2:  
Refer to the description for AlarmTypeLog0.  
AlarmTypeLog3:  
Refer to the description for AlarmTypeLog0.  
AlarmTypeLog4:  
Refer to the description for AlarmTypeLog0.  
ResSensor1Error(AI1): The nvoError is a polled output containing a list of the current  
errors detected by the node. A search for error conditions in the node is made  
periodically. A diagnostic tool may poll nvoError for all of the current errors. nvoError  
uses one bit for each possible error condition. nvoError contains all the detected  
current errors even though they may be suppressed for reporting by nvoAlarm.  
There is a correspondence between the error conditions and alarm types. nvoError  
includes sensor failure errors and input network variable failure detect errors. Any  
sensor failure errors result in a SENSOR_FAILURE alarm. Failure to receive any  
bound network variable periodically results in an INPUT_NV_FAILURE alarm.  
nvoError tells which sensor(s) or network variable(s) have failed. See nvoAlarm,  
AlarmTypeLog for related subjects.  
(continued)  
58  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
Errorbyte2  
NvName  
nvoError  
Field Name  
error_bit(0)  
Byte Offset = 0  
Bit Offset = 1  
Default  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
ResSensor2Error(AI2)  
Errorbyte3  
Errorbyte4  
BugFixVer  
nvoError  
nvoError  
error_bit(0)  
Byte Offset = 0  
Bit Offset = 2  
FALSE  
TRUE  
0
1
ResSensor3Error(AI3)  
error_bit(0)  
Byte Offset = 0  
Bit Offset = 3  
FALSE  
TRUE  
0
1
ResSensor4Error(AI4)  
nroPgmVer  
nroPgmVer  
nroPgmVer  
nroPgmVer  
nroPgmVer  
BugVer  
3
NodeType  
MajorVer  
MinorVer  
NodeType  
RIO1  
MajorVer  
MinorVer  
2
1
6
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
CommFailure  
disabled  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
TRUE  
0
1
ElectricalFault  
FailSelfTest  
FeedbackFailure  
InAlarm  
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
InvalidId  
FALSE  
TRUE  
0
1
InvalidRequest  
FALSE  
TRUE  
0
1
(continued)  
59  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
M
ResSensor2Error(AI2): Refer to the description of ResSensor1Error(AI1).  
X
X
X
M
M
ResSensor3Error(AI3): Refer to the description of ResSensor1Error(AI1).  
ResSensor4Error(AI4): Refer to the description of ResSensor1Error(AI1).  
Software version.  
A four byte ASCII string indicating the type of node (model).  
Software version.  
X
X
Software version.  
The NodeType is a numeric identifier that is stored in EPROM that identifies the  
Excel 10 node type. Whenever a new software version or upgrade is issued, this is  
reflected in nroPgmVer which typically is read by a network management node to  
identify the node type. The contents of nroPgmVer contain compatible model type  
information and is fixed at the time when the node software is compiled.  
CommFailure:  
This field is not supported and is set to 0 (FALSE).  
disabled: disabled reports 1 if nvoIO mode is set to DISABLED_MODE or  
FACTORY_TEST mode. Otherwise disabled is set to 0.  
ElectricalFault:  
This field is not supported and is set to 0 (FALSE).  
FailSelfTest:  
This field is not supported and is set to 0 (FALSE).  
FeedbackFailure:  
This field is not supported and is set to 0 (FALSE).  
InAlarm: If there are currently any active alarms reported by InAlarm, or InAlarm is  
set to AlarmNotifyDisabled, then InAlarm is set to True, if not InAlarm is set to False.  
InvalidId: If object_id is not a valid object, invalid_id is set to 1 (TRUE) otherwise it is  
set to 0 (FALSE).  
InvalidRequest: If object_request is not a valid request for the object addressed,  
InvalidRequest is set to 1 (TRUE) otherwise it is set to 0 (FALSE).  
(continued)  
60  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
nvoStatus  
Field Name  
Default  
InOverride  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
nvoStatus  
nvoStatus  
nvoStatus  
LockedOut  
FALSE  
TRUE  
0
1
ManualControl  
FALSE  
TRUE  
0
1
MechanicalFault  
FALSE  
TRUE  
0
1
nvoStatus  
nvoStatus  
ObjectId  
0 TO 65535  
0
OpenCircuit  
FALSE  
TRUE  
0
1
FALSE  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
nvoStatus  
OutOfLlimits  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
OutOfService  
OverRange  
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
SelfTestInProgress  
UnableToMeasure  
UnderRange  
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
FALSE  
TRUE  
0
1
61  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C3. Status Points (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
InOverride:  
This field is not supported and is set to 0 (FALSE).  
LockedOut:  
This field is not supported and is set to 0 (FALSE).  
ManualControl:  
This field is not supported and is set to 0 (FALSE).  
MechanicalFault:  
This field is not supported and is set to 0 (FALSE).  
ObjectId: is set to the current value of nviRequest.object_id  
OpenCircuit:  
This field is not supported and is set to 0 (FALSE).  
OutOfLlimits:  
This field is not supported and is set to 0 (FALSE).  
OutOfService:  
This field is not supported and is set to 0 (FALSE).  
OverRange:  
This field is not supported and is set to 0 (FALSE).  
SelfTestInProgress:  
This field is not supported and is set to 0 (FALSE).  
UnableToMeasure:  
This field is not supported and is set to 0 (FALSE).  
UnderRange:  
This field is not supported and is set to 0 (FALSE).  
62  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Left).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
nciApplVer  
Field Name  
ApplicationType  
Default  
0 to 255  
0
nciDeviceName  
DeviceName  
ASCII Blanks  
nciApplVer  
Time1Jan70  
seconds  
0 to 255  
0
nciApplVer  
VersionNumber  
LowerLimitS7  
0
0
AILowLimit  
nciEUConvrtRes  
degrees F -40 to 240  
degrees C (-40 to 116)  
AIOutputRHigh  
AIOutputRLow  
AIResHigh  
nciEUConvrtRes  
nciEUConvrtRes  
nciEUConvrtRes  
OutputResHighS7  
OutputResLowS7  
ResHigh  
degrees F -40 to 240  
degrees C (-40 to 116)  
0
0
0
degrees F -40 to 240  
degrees C (-40 to 116)  
Ohms  
10 to 150000  
AIResLow  
nciEUConvrtRes  
ResLow  
Ohms  
0
10 to 150000  
(continued)  
63  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Right).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
ApplicationType identifies the current application number of the Excel 10.  
nciDeviceName is an 18 character field used to identify the node uniquely as one  
object at the site or project. The contents of the nciDeviceName is maintained by a  
management node. If nciDeviceName is all ASCII blanks, it is considered  
unconfigured.  
The time stamp of the last change to the Excel 10 application configuration. Time  
meets the ANSI C time stamp requirement specifying the number of seconds  
elapsed since midnight (0:00:00), January 1, 1970. It is represented in the Intel  
Format.  
VersionNumber identifies the version number of the Excel 10 application.  
X
M
X
AILowLimit: This is the low limit value or the lowest value that will be displayed for  
this sensor. This value must be between the AIOutputRLow and AIOutputRHigh and  
lower than the value specified for AIUpperLimit.  
X
X
X
M
M
M
X
X
X
AIOutputRHigh: This is the equivalent temperature degrees F (degrees C) value for  
the resistance entered for AIResHigh. Using the resistance example for AIResHigh  
of 48,000 ohms, you would enter the equivalent temperature of 45.0 degrees F (7.2  
degrees C) for the AIOutputRHigh value.  
AIOutputRLow: This is the equivalent temperature degrees F (degrees C) value for  
the resistance entered for AIResLow. Using the resistance example for AIResLow of  
11,520 ohms, you would enter the equivalent temperature of 99.0 degrees F (37.2  
degrees C) for the AIOutputRLow value.  
AIResHigh: This is the highest resistance value of the user specified range for a  
custom resistive input as selected through E-Vision in the input Tab of the  
Application selection screen. The user can select between a PT3000  
(Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) sensor. This value is  
specified in ohms with LSB in 10 Ohms. This means that if your high resistance  
value for a 20 Kohm NTC sensor was 48,000 ohms, 45.0 degrees F (7.2 degrees C),  
the value that would be entered for AIResHigh would be 4800 (the resistance value  
divided by ten).  
X
M
X
AIResLow: This is the lowest resistance value of the user specified range for a  
custom resistive input as selected through E-Vision in the input Tab of the  
Application selection screen. The user can select between a PT3000  
(Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) sensor. This value is  
specified in ohms with LSB in 10 Ohms. This means that if the low resistance value  
for a 20 Kohm NTC sensor was 11,520 ohms, 99.0 degrees F (37.2 degrees C), the  
value that would be entered for AIResLow would be 1152 (the resistance value  
divided by ten).  
(continued)  
64  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
AIUpperLimit  
NvName  
Field Name  
UpperLimitS7  
Default  
nciEUConvrtRes  
degrees F -40 to 240  
degrees C (-40 to 116)  
0
0
DeltaC  
nciDelta  
deltacurrent  
mA  
0 to 256  
DeltaCO2  
DeltaH  
nciDelta  
nciDelta  
nciDelta  
deltaCO2  
deltahum  
deltapres  
PPM 0 to 2000  
percent 0 to 163  
0
0
0
DeltaP  
inw 0 to 32  
kPa (0 to 7.97)  
DeltaT1  
DeltaT2  
DeltaT3  
DeltaT4  
nciDelta  
nciDelta  
nciDelta  
nciDelta  
deltatemp(0)  
deltatemp(1)  
deltatemp(2)  
deltatemp(3)  
degrees F 0 to 256  
degrees C (0 to 124)  
0
0
0
0
degrees F 0 to 256  
degrees C (0 to 124)  
degrees F 0 to 256  
degrees C (0 to 124)  
degrees F 0 to 256  
degrees C (0 to 124)  
DeltaV  
nciDelta  
deltaVolt  
DO0  
0 to 10.5 volts  
0
DO1FlSpeed  
nciFloatConfig  
seconds  
0 to 900  
90  
DO2FlSpeed  
DO3FlSpeed  
DO4FlSpeed  
nciFloatConfig  
nciFloatConfig  
nciFloatConfig  
DO1  
DO2  
DO3  
seconds  
0 to 900  
90  
90  
90  
seconds  
0 to 900  
seconds  
0 to 900  
(continued)  
65  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
M
X
AIUpperLimit: This is the high limit value or the highest value that will be displayed  
for this sensor. This value must be between the AIOutputRLow and AIOutputRHigh  
and higher than the value specified for AILowLimit.  
X
M P  
X
DeltaC: The default value of delta for all RIO sensor types is set to zero. With this  
default value, the RIO will send the sensor values at the fastest rate of 2 seconds  
update rate. However, if the user desires to reduce the network traffic or not receive  
the noisy sensor values, a delta value can be specified. This value will force the RIO  
to transmit the sensor value when the current value exceeds the last sent value by  
the delta amount. RIO will also send the sensor value whenever the time of update  
exceeds nciRioSendT. RIO will send the sensor value at the rate of nciRioSendT  
regardless of delta change.  
X
X
X
M P  
M P  
M P  
X
X
X
DeltaCO2: Refer to the description for DeltaC.  
DeltaH: Refer to the description for DeltaC.  
DeltaP: Refer to the description for DeltaC.  
X
X
X
X
M P  
M P  
M P  
M P  
M P  
X
X
X
X
DeltaT1: Refer to the description for DeltaC.  
DeltaT2: Refer to the description for DeltaC.  
DeltaT3: Refer to the description for DeltaC.  
DeltaT4: Refer to the description for DeltaC.  
DeltaV: Refer to the description for DeltaC.  
X
X
X
X
DO1FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO1Type were configured to  
either Float_Open or Float_Close.  
X
X
X
X
X
X
DO2FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO2Type were configured to  
either Float_Open or Float_Close.  
DO3FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO3Type were configured to  
either Float_Open or Float_Close.  
DO4FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO4Type were configured to  
either Float_Open or Float_Close.  
(continued)  
66  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
Default  
DO5FlSpeed  
nciFloatConfig  
DO4  
DO5  
DO6  
DO7  
seconds  
0 to 900  
90  
DO6FlSpeed  
DO7FlSpeed  
DO8FlSpeed  
DO1PWMPeriod  
nciFloatConfig  
nciFloatConfig  
nciFloatConfig  
nciPWMConfig1  
seconds  
0 to 900  
90  
seconds  
0 to 900  
90  
seconds  
0 to 900  
90  
DO0.si_period_pwm  
seconds  
25.6  
0.0 to 3000  
DO1PWMZero  
DO1PWMFull  
DO2PWMPeriod  
DO2PWMZero  
DO2PWMFull  
DO3PWMPeriod  
DO3PWMZero  
DO3PWMFull  
DO4PWMPeriod  
DO4PWMZero  
DO4PWMFull  
DO5PWMPeriod  
DO5PWMZero  
DO5PWMFull  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig1  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
DO0.si_pnct_time  
DO0.si_delta_time  
DO1.si_period_pwm  
DO1.si_pnct_time  
DO1.si_delta_time  
DO2.si_period_pwm  
DO2.si_pnct_time  
DO2.si_delta_time  
DO3.si_period_pwm  
DO3.si_pnct_time  
DO3.si_delta_time  
DO4.si_period_pwm  
DO4.si_pnct_time  
DO4.si_delta_time  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
0.1  
25.5  
25.6  
0.1  
25.5  
25.6  
0.1  
25.5  
25.6  
0.1  
25.5  
25.6  
0.1  
25.5  
(continued)  
67  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
DO5FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO5Type were configured to  
either Float_Open or Float_Close.  
X
X
X
X
X
X
X
X
DO6FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO6Type were configured to  
either Float_Open or Float_Close.  
DO7FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO7Type were configured to  
either Float_Open or Float_Close.  
DO8FlSpeed is how long it takes for the actuator motor to move one cycle of travel  
from closed to open. This value would be required if DO8Type were configured to  
either Float_Open or Float_Close.  
M
DO1PWMPeriod is a intermittent voltage pulse whose width varies in proportion to  
the desired actuator position. The PWM signal has three parameters that have to be  
configured in order for the output to function correctly. The period, is the overall pulse  
lenegth in seconds. The percent_time (signal presence) is the zero percent position  
of the actuator output. The actuator requires this signal (pulse width) sent once every  
period, so that it knows that it is still connected to the controller and where the zero  
position starts. The variable width (delta_time) portion is incremented in proportion to  
the signal percentage. There are 255 increments available (for example 0.1 second).  
Thus, the pulse width will be the minimum width (percent_time) plus the number of  
increments (delta_time/ 255). The smallest time that can be used with the RIO  
controller is 0.1 second. An example stroke at mid position is: 0.1 second  
(percent_time) + 128 x 0.1 (255/0.5 - 50 percent position) = 12.9 seconds. The period  
would equal the percent_time plus the delta_time (for example 0.1 seconds) + 255 x  
0.1 seconds = 25.6 seconds.  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
M
M
M
M
M
M
M
M
M
M
M
M
M
M
X
X
X
X
X
X
X
X
X
X
X
X
X
X
DO1PWMZero: Refer to the description for DO1PWMPeriod.  
DO1PWMFull: Refer to the description for DO1PWMPeriod.  
DO2PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO2PWMZero: Refer to the description for DO1PWMPeriod.  
DO2PWMFull: Refer to the description for DO1PWMPeriod.  
DO3PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO3PWMZero: Refer to the description for DO1PWMPeriod.  
DO3PWMFull: Refer to the description for DO1PWMPeriod.  
DO4PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO4PWMZero: Refer to the description for DO1PWMPeriod.  
DO4PWMFull: Refer to the description for DO1PWMPeriod.  
DO5PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO5PWMZero: Refer to the description for DO1PWMPeriod.  
DO5PWMFull: Refer to the description for DO1PWMPeriod.  
(continued)  
68  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C4. Configuration Parameters (Left Continued).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
DO6PWMPeriod  
DO6PWMZero  
DO6PWMFull  
DO7PWMPeriod  
DO7PWMZero  
DO7PWMFull  
DO8PWMPeriod  
DO8PWMZero  
DO8PWMFull  
NvName  
Field Name  
DO5.si_period_pwm  
DO5.si_pnct_time  
DO5.si_delta_time  
DO6.si_period_pwm  
DO6.si_pnct_time  
DO6.si_delta_time  
DO7.si_period_pwm  
DO7.si_pnct_time  
DO7.si_delta_time  
Default  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
nciPWMConfig2  
seconds 0.0 to 3000  
25.6  
0.1  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
seconds 0.0 to 3000  
25.6  
25.6  
0.1  
25.5  
25.6  
0.1  
25.5  
Table C4. Configuration Parameters (Right Continued).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
M
X
DO6PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO6PWMZero: Refer to the description for DO1PWMPeriod.  
DO6PWMFull: Refer to the description for DO1PWMPeriod.  
DO7PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO7PWMZero: Refer to the description for DO1PWMPeriod.  
DO7PWMFull: Refer to the description for DO1PWMPeriod.  
DO8PWMPeriod: Refer to the description for DO1PWMPeriod.  
DO8PWMZero: Refer to the description for DO1PWMPeriod.  
DO8PWMFull: Refer to the description for DO1PWMPeriod.  
X
X
X
X
X
X
X
X
M
M
M
M
M
M
M
M
X
X
X
X
X
X
X
X
69  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table C5. Direct Access And Special Points (Left).  
Digital  
State  
or  
Engineering Units:  
English (Metric) or  
States plus Range  
Value  
of  
State  
User Address  
NvName  
Field Name  
Default  
DestManMode  
nviManualMode  
MODE_ENABLE  
MODE_DISABLE  
MODE_MANUAL  
SUPPRESS_ALARMS  
UNSUPPRESS_ALARMS  
0
1
2
3
4
MODE_ENABLE  
Table C5. Direct Access And Special Points (Right).  
Share (SH), Map (MA), Direct Access (DA)  
E-Vision (EV): Calibrate (C), Monitor (M),  
Parameter (P), Schematic (S)  
Hardware Configuration (HW),  
Manual Point (MN), Test (TS)  
SH  
MA  
DA  
EV  
HW  
MN  
TS  
Comments  
X
X
M P  
DestManMode: is an input which is used to manually set the physical outputs.  
DestManMode remains unchanged until another mode has been commanded or an  
application restart has been performed. The valid enumerated values are:  
MODE_ENABLE enables the node so that the RIO controls the physical outputs as  
the normal mode. MODE_ENABLE is the default state after power is restored or an  
application restart occurs. If the mode was MANUAL and DestManMode is set to  
MODE_ENABLE, the node then goes through application restart.  
MODE_DISABLED sets the node into the DISABLED mode. The alarm  
NODE_DISABLED is initiated, and the physical outputs are turned off. The physical  
inputs, network variable inputs, and network variable outputs are still functioning  
when the node is in the DISABLED mode.  
MODE_MANUAL sets the node into the MANUAL mode. The alarm  
NODE_DISABLED is initiated, and the physical outputs are controlled manually as  
commanded by DestManMode. The nodes configuration variables and  
DestManMode are used to set valves, dampers, and/or digital output to the desired  
manual positions or state(s). The physical inputs, network variable inputs, and  
network variable outputs are still functioning when the node is in the MANUAL mode.  
SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED,  
and AlarmTypeLog to no longer record alarms. If alarms are suppressed,  
UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to  
reporting alarms. See nvoAlarm for more details. All unspecified values are the same  
as MODE_ENABLE.  
70  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Appendix D. Q7750A Excel 10  
Zone Manager Point Estimating Guide.  
Memory size approximation is shown below: (all sizes in bytes)  
When memory size is less than 110,000 bytes, the size is OK.  
When memory size is between 110,000 and 128,000 bytes, the application may be too large. The user must expect to reduce  
the application complexity, reduce the number of attached Excel 10s or distribute the Excel 10s over more than one Zone  
Manager.  
When memory size is greater than 128,000, the size is too large. The application size must be reduced as described above.  
Approximate Memory Size Estimating Procedure.  
1. Determine the number of points per controller required at the Central (for example, XBS).  
NOTE: All remaining points that are not mapped can be accessed through the Direct Access feature.  
2. Calculate the number of Excel 10 Zone Manager program points that are used in control logic and in the switching table.  
3. Estimate the program complexity of the Zone Manager (one of three levels).  
a. No time programs, control logic, or switching tables.  
b. 10K of control logic (one time program, five switching tables, and five control loops).  
c. 20K of control logic (multiple time programs, ten switching tables, and ten control loops).  
Use Fig. D-1 to determine the number of Excel 10s that can be connected to the Zone Manager.  
NOTE: More than 60 Excel 10s requires a Router.  
4. Repeat for each Q7750A Excel 10 Zone Manager in a project.  
(A) NO TIME PROGRAM,  
NO CONTROL LOOPS,  
NO SWITCHING TABLES.  
920  
900  
900  
895  
(B) 10K CONTROL PROGRAM  
(I.E., 1 TIME PROGRAM,  
5 CONTROL LOOPS,  
800  
800  
5 SWITCHING TABLES.)  
765  
NUMBER OF  
C-BUS POINTS  
(EXCEL 10  
MAPPED  
NUMBER OF  
C-BUS POINTS  
(EXCEL 10  
MAPPED  
740  
700  
700  
POINTS  
POINTS  
PLUS ZONE  
MANAGER  
POINTS)  
PLUS ZONE  
MANAGER  
POINTS)  
(C) 20K CONTROL PROGRAM  
(I.E., MULTIPLE TIME PROGRAMS,  
10 CONTROL LOOPS,  
10 SWITCHING TABLES.)  
610  
600  
600  
585  
20  
(OR LESS)  
60  
(ADD ROUTER)  
120  
M8729  
NUMBER OF EXCEL 10s  
Fig. D-1. Point capacity estimate for Zone Manager.  
The exact equation for calculating memory size follows:  
Memory size = 21,780  
+ 4096 (in case of a time program).  
+ CARE Control Program.  
+ 14 x time points x Excel 10 units.  
+ 50 x Excel 10 units.  
+ map complexity x Excel 10 units x mapped points.  
+ 57 x C-Bus points.  
+ 7488 x Excel 10 types.  
Where:  
Time points = number of switch points in time program per Excel 10.  
Excel 10 units = number of attached Excel 10s.  
C-Bus points = including mapped points and others; for example, remote points.  
Mapped points = number of mapped points per Excel 10,  
including One-to-Many and Many-to-One  
mechanism.  
Excel 10 types = number of different Excel 10 types (currently three)  
Map complexity =  
20 = using One-to-Many and not using  
points with read/write.  
30 = average.  
45 = many points with read/write ability.  
71  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Appendix E. Sensor Data for Calibration.  
Resistance Sensors.  
Sensor Type:  
C7100A1015, (and C7170A1002).  
Sensor Use:  
Discharge air, Outdoor air.  
Table E-1 lists the points for Sensor Resistance versus Temperature. Fig. E-1 shows the graph of these points.  
Table E-1. Sensor Resistance Versus Temperature.  
°F (°C)  
Resistance Ohms  
2916.08  
2964.68  
3013.28  
3061.88  
3110.48  
3159.08  
3207.68  
3256.28  
3304.88  
3353.48  
3402.08  
3450.68  
3499.28  
3547.88  
3596.48  
3645.08  
3693.68  
-40 (-40)  
-30 (-34.5)  
-20 (-28.9)  
-10 (-23.3)  
0 (-17.8)  
10 (-12.2)  
20 (-6.7)  
30 (-1.1)  
40 (4.4)  
50 (10)  
60 (15.6)  
70 (21.1)  
80 (26.7)  
90 (32.2)  
100 (37.8)  
110 (43.4)  
120 (49)  
SENSOR RESISTANCE VERSUS TEMPERATURE  
3750  
3700  
3650  
3600  
3550  
3500  
3450  
3400  
3350  
3300  
3250  
3200  
3150  
3100  
3050  
3000  
2950  
2900  
°F  
-30 -20 -10  
0
10 20 30 40 50 60 70 80 90 100 110 120  
-12.2  
-1.1 10 21.1 32.2 43.4  
-40  
-40  
-34.5  
-23.3  
°C  
-28.9  
-17.8  
-6.7 37.8  
4.4  
15.6  
26.7  
49  
M11959  
Fig. E-1. Graph of Sensor Resistance versus Temperature.  
Sensor Type:  
C7031B1033, C7031C1031, C7031D1062, C7031F1018, C7031J1050, C7031K1017.  
Sensor Use:  
Return Air, Discharge Air Temperature.  
72  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Table E-2 lists the points for Sensor Resistance versus Temperature. Fig. E-2 shows the graph of these points.  
Table E-2. Sensor Resistance Versus Temperature.  
°F (°C)  
30 (-1.1)  
35 (1.7)  
Resistance Ohms  
1956.79  
1935.79  
1914.79  
1893.79  
1872.79  
1851.79  
1830.79  
1809.79  
1788.79  
1767.79  
1746.79  
1725.79  
1704.78  
1683.78  
1662.78  
1641.78  
1620.78  
1599.78  
1578.78  
40 (4.4)  
45 (7.2)  
50 (10)  
55 (12.8)  
60 (15.6)  
65 (18.3)  
70 (21.1)  
75 (23.9)  
80 (26.7)  
85 (29.4)  
90 (32.2)  
95 (35)  
100 (37.8)  
105 (40.6)  
110 (43.3)  
115 (46.1)  
120 (48.9)  
SENSOR RESISTANCE VERSUS TEMPERATURE  
2000  
1950  
1900  
1850  
1800  
1750  
1700  
1650  
1600  
1550  
1500  
30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105110 115120  
°F  
1.7  
7.2  
12.8  
18.3  
21.1  
23.9  
26.7  
29.4  
32.2  
35  
40.6  
43.3  
37.8  
46.1  
48.9  
M11960  
°C  
-1.1  
4.4  
10  
15.6  
Fig. E-2. Graph of Sensor Resistance versus Temperature.  
Sensor Type:  
T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and C7770A.  
Sensor Use:  
Space Temperature and Discharge/Return Air Temperature.  
Table E-3 lists the points for Sensor Resistance versus Temperature. Fig. E-3 shows the graph of these points.  
Table E-3 Sensor Resistance Versus Temperature.  
°F (°C)  
40 (4.4)  
45 (7.2)  
50 (10)  
Resistance Ohms  
9961.09  
9700.90  
9440.72  
55 (12.8)  
60 (15.6)  
9180.53  
8920.35  
73  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
65 (18.3)  
70 (21.1)  
75 (23.9)  
80 (26.7)  
85 (29.4)  
90 (32.2)  
95 (35)  
8660.16  
8399.98  
8139.79  
7879.61  
7619.42  
7359.24  
7099.06  
6838.87  
100 (37.8)  
80K  
70K  
60K  
50K  
40K  
30K  
20K  
20K OHM AT  
77oF (25oC)  
10K  
80  
30  
0
40  
50  
10  
TEMPERATURE (DEGREES)  
60  
70  
90  
100  
110 oF  
oC  
20  
40  
30  
M5874A  
Fig. E-3. Graph of Sensor Resistance versus Temperature.  
Voltage/Current Sensors.  
Sensor Type:  
C7600B1000 (Decorative Wall Mount) and C7600C1018 2 to 10V.  
Sensor Use:  
Humidity.  
Table E-4 lists the points for Sensor Voltage versus Humidity. Fig. E-4 shows the graph of these points.  
Table E-4. Sensor Voltage Versus Humidity.  
Humidity Percentage  
Sensor Voltage  
2.67  
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
3.08  
3.48  
3.88  
4.28  
4.68  
5.08  
5.48  
5.88  
6.28  
6.69  
7.09  
7.49  
7.89  
8.29  
74  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
85  
90  
8.69  
9.09  
SENSOR VOLTAGE VERSUS HUMIDITY PERCENTAGE  
10.00  
9.50  
9.00  
8.50  
8.00  
7.50  
7.00  
6.50  
6.00  
5.50  
5.00  
4.50  
4.00  
3.50  
3.00  
2.50  
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90  
M11610  
PERCENTAGE  
Fig. E-4. Graph of Sensor Voltage versus Humidity.  
Sensor Type:  
C7600C1008 (4 to 20 mA).  
Sensor Use:  
Humidity.  
Table E-5 lists the points for Sensor Current versus Humidity. Fig. E-5 shows the graph of these points.  
Table E-5. Sensor Current Versus Humidity.  
Humidity Percentage  
Sensor Current  
5.6  
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
6.4  
7.2  
8.0  
8.8  
9.6  
10.4  
11.2  
12.0  
12.8  
13.6  
14.4  
15.2  
16.0  
16.8  
17.6  
18.4  
75  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
20  
18  
16  
14  
12  
10  
RH (%) I (mA)  
10  
20  
30  
40  
50  
60  
70  
80  
90  
5.6  
7.2  
8.8  
10.4  
12.0  
13.6  
15.2  
16.8  
18.4  
8
6
4
0
10 20 30 40 50 60 70 80 90 100  
HUMIDITY IN PERCENT RELATIVE HUMIDITY  
M3131B  
Fig. 5. C7600C output current vs. humidity.  
Sensor Type:  
C7400A1004.  
Sensor Use:  
Enthalpy.  
Table E-6 lists the points for Sensor Current versus Enthalpy (volts). Fig. E-6 shows the graph of these points.  
Table E-6. Sensor Current Versus Enthalpy (Volts).  
Enthalpy (volts)  
Sensor Current (mA)  
4
5
1
1.25  
1.49  
1.74  
1.99  
2.24  
2.49  
2.74  
2.99  
3.24  
3.49  
3.74  
3.98  
4.23  
4.48  
4.73  
4.98  
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SENSOR CURRENT VERSUS ENTHALPY (VOLTS)  
5.00  
4.75  
4.50  
4.25  
4.00  
3.75  
3.50  
3.25  
3.00  
2.75  
2.50  
2.25  
2.00  
1.75  
1.50  
1.25  
1.00  
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20  
M11607  
(MA)  
76  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Fig. E-6. Graph of Sensor Current versus Enthalpy (volts).  
See Fig. E-7 for a partial psychometric chart for the a C7400A Solid State Enthalpy Sensor.  
85  
90  
95 100 105 110  
(29) (32) (35) (38) (41) (43)  
CONTROL CONTROL POINT  
CURVE  
APPROX. °F (°C)  
80  
(27)  
AT 50% RH  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
75  
(24)  
70  
(21)  
65  
(18)  
60  
60  
(16)  
A
55  
(13)  
B
50  
(10)  
C
20  
45  
(7)  
D
40  
(4)  
35  
(2)  
1
A
B
C
D
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95 100 105 110  
(2)  
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)  
APPROXIMATE DRY BULB TEMPERATURE—°F (°C)  
HIGH LIMIT CURVE FOR W6210D,W7210D.  
M11160  
1
Fig. E-7. Partial psychometric chart for a C7400A Solid State Enthalpy Sensor.  
See Fig. E-8 for a C7400A Solid State Enthalpy Sensor output current versus relative humidity.  
C7400A OUTPUT CURRENT  
100  
90  
80  
70  
14 mA 12 mA  
18 mA  
60  
50  
40  
D = 17 MA  
C = 15.5 MA  
B = 13.5 MA  
A = 11 MA  
30  
20  
10  
B
70  
(21)  
A
D
C
40  
(4)  
50  
(10)  
60  
(16)  
80  
(27)  
90  
(32)  
100  
(38)  
TEMPERATURE °F (°C)  
M11605  
Fig. E-8. C7400A Solid State Enthalpy Sensor output current vs. relative humidity.  
77  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Sensor Type:  
T7242 or equivalent.  
Sensor Use:  
CO2 concentration.  
Table E-9 lists the points for Sensor Voltage versus CO2 concentration. Fig. E-9 shows the graph of these points.  
Table E-9. Sensor Voltage Versus CO2 Concentration.  
CO2 Concentration PPM  
Sensor Voltage  
0.00  
0
100  
0.50  
200  
1.00  
300  
1.50  
400  
2.00  
500  
2.50  
600  
3.00  
700  
3.50  
800  
4.00  
900  
4.50  
1000  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
5.00  
5.50  
6.00  
6.50  
7.00  
7.50  
8.00  
8.50  
9.00  
9.50  
10.00  
SENSOR VOLTAGE VERSUS CO2 CONCENTRATION  
10  
9
8
7
6
5
4
3
2
1
0
100  
200  
300  
400  
500  
600  
700 900 1100 1300 1500 1700 1900  
800 1000 1200 1400 1600 1800 2000  
M11611  
PPM  
Fig. E-9. Graph of Sensor Voltage versus CO2 concentration.  
Sensor Type:  
Third party (2 to 20V).  
Sensor Use:  
Monitor voltage.  
Table E-10 lists the points for Sensor Voltage versus input Voltage to A/D. Fig. E-10 shows the graph of these points.  
Table E-10. Sensor Voltage Versus Input Voltage To A/D.  
78  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7761A INPUT/OUTPUT DEVICE  
Voltage to A/D  
0.00  
Sensor Voltage  
0.00  
0.50  
0.25  
1.00  
0.50  
1.50  
0.75  
2.00  
1.00  
2.50  
1.25  
3.00  
1.50  
3.50  
1.75  
4.00  
2.00  
4.50  
2.25  
5.00  
2.50  
5.50  
2.75  
6.00  
3.00  
6.50  
3.25  
7.00  
3.50  
7.50  
3.75  
8.00  
4.00  
8.50  
4.25  
9.00  
4.50  
9.50  
4.75  
10.00  
5.00  
SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D  
5.00  
4.50  
4.00  
3.50  
3.00  
2.50  
2.00  
1.50  
1.00  
0.50  
0
600  
800  
0
100  
200  
300  
400  
500  
VOLTS  
700  
900 1000  
M11612  
Fig. E-10. Graph of Sensor Voltage versus input Voltage to A/D.  
Sensor Type:  
Third party.  
Sensor Use:  
Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5 inw (0 to 1.25 kPa).  
Table E-11 lists the points for Sensor Voltage (Vdc) versus Pressure (Inw). Fig. E-11 shows the graph of these points.  
Table E-11. Sensor Voltage (Vdc) Versus Pressure (Inw).  
Pressure Inw (kPa)  
0.00 (0.00)  
Sensor Voltage (Vdc)  
2.00  
2.80  
3.60  
4.40  
5.20  
6.00  
0.50.(0.13)  
1.00 (0.25)  
1.50 (0.37)  
2.00 (0.5)  
2.50 (0.62)  
79  
74-2699  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.00 (0.75)  
3.50 (0.87)  
4.00 (1.00)  
4.50 (1.12)  
5.00 (1.25)  
6.80  
7.60  
8.40  
9.20  
10.00  
SENSOR VOLTAGE VERSUS PRESSURE  
10.00  
9.00  
8.00  
7.00  
6.00  
5.00  
4.00  
3.00  
2.00  
Inw  
kPa  
0
0
0.50  
0.13  
1.00  
0.25  
1.50 2.00  
0.37 0.5  
2.50  
0.62  
3.00  
0.75  
3.50  
0.87  
4.00  
1.0  
4.50  
1.12  
5.00  
1.25  
M11963  
Fig. E-11. Graph of Sensor Voltage (Vdc) versus Pressure (Inw).  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
74-2699 J.D. 6-98  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grandstream Networks Network Card HandyTone 496 User Manual
Grizzly Saw G8994z User Manual
Guardian Technologies Kitchen Grill PTDCM SA12020 User Manual
Harbor Freight Tools Battery Charger 92775 User Manual
Harman Kardon Stereo Receiver AVR 700 User Manual
Heatmaster Fan HMDGII User Manual
Hoshizaki Ice Maker DCM 270BAH OS User Manual
HP Hewlett Packard Fax Machine HP FAX 700 User Manual
Hypertec Network Card PCI 10 100 TX User Manual
Ikelite Camcorder Accessories HDR SR7 User Manual