Honeywell Smoke Alarm IFS 2600 User Manual

IFS-2600  
Fire Indicator Panel  
TECHNICAL, PROGRAMMING  
& INSTALLATION MANUAL  
8/05/08  
P/N 10069  
Rev:
3.01  
ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Precautions  
Adherence to the following will aid in  
problem-free installation with long-term  
reliability:  
Remove all electronic assemblies prior to any  
drilling, filing, reaming, or punching of the  
enclosure. When possible, make all cable entries  
from the sides or rear. Before making  
modifications, verify that they will not interfere with  
battery, transformer, or printed circuit board  
location.  
WARNING - Several different sources of power  
can be connected to the fire alarm control  
panel. Disconnect all sources of power before  
servicing. Control unit and associated equipment  
may be damaged by removing and/or inserting  
cards, modules, or interconnecting cables while the  
unit is energized. Do not attempt to install, service,  
or operate this unit until manuals are read and  
understood.  
Do not over tighten screw terminals. Over  
tightening may damage threads, resulting in  
reduced terminal contact pressure and difficulty  
with screw terminal removal.  
This system contains static-sensitive  
components. Always ground yourself with a  
proper wrist strap before handling any circuits so  
that static charges are removed from the body.  
Use static suppressive packaging to protect  
electronic assemblies removed from the unit.  
Verify that wire sizes are adequate for all  
initiating and indicating device loops. Most devices  
cannot tolerate more than a 10% I.R. drop from the  
specified device voltage.  
Follow the instructions in the installation,  
operating, and programming manuals. These  
instructions must be followed to avoid damage to  
the control panel and associated equipment.  
FACP operation and reliability depend upon proper  
installation.  
Like all solid state electronic devices, this  
system may operate erratically or can be damaged  
when subjected to lightning induced transients.  
Although no system is completely immune from  
lightning transients and interference, proper  
grounding will reduce susceptibility. Overhead or  
outside aerial wiring is not recommended, due to  
an increased susceptibility to nearby lightning  
strikes. Consult with the Technical Services  
Department if any problems are anticipated or  
encountered.  
This equipment must be correctly programmed  
and installed to suit the specific application.  
Please ensure correct operational parameters are  
set prior to commissioning. If further details on  
programming options are required, please consult  
the programming manual or contact our helpful  
technical support personnel.  
Disconnect AC power and batteries prior to  
removing or inserting circuit boards. Failure to do  
so can damage circuits.  
EMC WARNING:  
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if  
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio  
communications. It has been tested and found to comply with the Class A radiated and conducted EMI  
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility  
requirements of Clause C3.5 in AS4428.0:1997.  
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices  
and systems.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Documentation Feedback  
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about  
our printed manuals you can email us.  
Please include the following information:  
Product name and version number (if applicable)  
Manual part number and revision (found on the front cover)  
Page number  
Brief description of the content you think should be improved or corrected  
Your suggestion for how to correct/improve documentation  
Send email messages to:  
Please note this email address is for documentation feedback only. If you have any technical issues, please contact  
you nearest branch for technical support.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 1  
TABLE OF CONTENTS  
COMPATIBLE DETECTORS................................................................................................5  
OVERVIEW...........................................................................................................................6  
CAUTION ........................................................................................................................................................................... 6  
SPECIFICATION...................................................................................................................7  
APPROVALS...................................................................................................................................................................... 7  
ENVIRONMENTAL LIMITS........................................................................................................................................... 7  
POWER SUPPLY RATINGS AND SETTINGS ............................................................................................................. 9  
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY .......................................................................................... 9  
INTERNAL 27.3V DC 1.5A BATTERY CHARGER..................................................................................................... 9  
Internal 5VDC 2A Power Supply ..................................................................................................................................... 9  
EXTERNAL 27VDC POWER SUPPLY ....................................................................................................................... 10  
BATTERY TYPE AND CAPACITIES .......................................................................................................................... 10  
TECHNICAL DESCRIPTION ..............................................................................................11  
GENERAL ........................................................................................................................................................................ 11  
TRANSIENT SUPPRESSION......................................................................................................................................... 11  
CURRENT CONSUMPTION ......................................................................................................................................... 11  
AZF DESCRIPTION........................................................................................................................................................ 12  
AZF SUPERVISORY CURRENT .................................................................................................................................. 12  
OVERLOAD PROTECTION.......................................................................................................................................... 12  
ZONE OVERLOAD SELF RESET ................................................................................................................................ 12  
PRINTER OUTPUT......................................................................................................................................................... 13  
CABLE CONNECTION.................................................................................................................................................. 13  
PROGRAMMING BY COMPUTER ............................................................................................................................. 13  
ALIGNMENT AND ADJUSTMENT .....................................................................................14  
PCB2006 POWER SUPPLY BOARD ............................................................................................................................ 14  
INTERNAL 24VDC (nom) POWER SUPPLY.............................................................................................................. 14  
INTERNAL 27.3 VDC BATTERY CHARGER............................................................................................................ 14  
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted) ............................................................................................. 14  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 2  
IFS-2600 Installation & Programming Manual  
PCB2005 TERMINATION BOARD............................................................................................................................... 14  
INTERNAL 5VDC POWER SUPPLY TP8................................................................................................................... 14  
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10 .........................................................................14  
NON ADJUSTABLE TEST POINTS.............................................................................................................................. 14  
ALARM THRESHOLD COMPARATOR TP7.............................................................................................................15  
FAULT THRESHOLD COMPARATOR TP6 ..............................................................................................................15  
CONFIGURATION JUMPERS......................................................................................................................................16  
IFS2004 - JP3 DEFAULT .............................................................................................................................................16  
IFS2004 - JP4 PROGRAM DISABLE .......................................................................................................................... 16  
IFS2004 - JP5 CPU RESET...........................................................................................................................................16  
IFS2005 – JP2 DOOR HOLDER BYPASS................................................................................................................... 16  
IFS2006 – JP1 EXTERNAL PS MONITORING..........................................................................................................16  
IFS804 - JP1-7 ZONE BOARD ADDRESSING...........................................................................................................16  
PLACING INTO OPERATION ............................................................................................ 17  
EQUIPMENT AS FITTED ..............................................................................................................................................17  
INITIAL CHECKLIST .................................................................................................................................................... 17  
POWER UP CHECKLIST............................................................................................................................................... 18  
FUNCTIONAL TESTING ............................................................................................................................................... 18  
FAULT RECORD............................................................................................................................................................. 19  
INSTRUCTIONS TO OPERATORS.................................................................................... 20  
INDICATORS...................................................................................................................................................................20  
SUGGESTED ALARM PROCEDURE .......................................................................................................................... 21  
OPERATOR INSTRUCTIONS.......................................................................................................................................21  
FIREFIGHTER FUNCTIONS........................................................................................................................................21  
GLOBAL FUNCTIONS................................................................................................................................................. 22  
ZONE FUNCTIONS....................................................................................................................................................... 24  
PROGRAMMING................................................................................................................ 27  
GLOBAL OPTIONS......................................................................................................................................................... 27  
ZONE OPTIONS .............................................................................................................................................................. 27  
OUTPUT RELAY OPTIONS ..........................................................................................................................................28  
DEFAULT SETTINGS..................................................................................................................................................... 28  
PROGRAM MODE.......................................................................................................................................................... 29  
PROGRAMMING MODE..............................................................................................................................................29  
PROGRAMMING HIERARCHY ..................................................................................................................................29  
ZONES............................................................................................................................................................................29  
RELAYS.........................................................................................................................................................................30  
GLOBAL ........................................................................................................................................................................30  
PRINT.............................................................................................................................................................................30  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 3  
MAIN MENU.................................................................................................................................................................... 30  
EXIT PROGRAMMING MODE ................................................................................................................................... 31  
ZONE PROGRAMMING................................................................................................................................................ 31  
SELECT ZONE #........................................................................................................................................................... 31  
ZONE SELECTED......................................................................................................................................................... 31  
ZONE TYPE .................................................................................................................................................................. 31  
ZONE OUTPUT CONFIGURATION ........................................................................................................................... 32  
RELAY PROGRAMMING MODE................................................................................................................................ 32  
SELECT RELAY # ........................................................................................................................................................ 32  
RELAY SELECTED...................................................................................................................................................... 32  
RELAY TYPE................................................................................................................................................................ 33  
RELAY MAPPING........................................................................................................................................................ 33  
GLOBAL PROGRAMMING.......................................................................................................................................... 33  
ACF OUTPUT................................................................................................................................................................ 34  
AVF ................................................................................................................................................................................ 34  
RELAY (GLOBAL RELAY UNITY MAP) .................................................................................................................. 34  
PRINT PROGRAMMING DATA .................................................................................................................................. 35  
TIME (DATE & TIME)................................................................................................................................................... 35  
APPENDIX A ......................................................................................................................36  
DESCRIPTION OF ALARM ZONE TYPES ................................................................................................................ 36  
LATCHING TYPE......................................................................................................................................................... 36  
NON LATCHING TYPE ............................................................................................................................................... 36  
TIME DELAY AZF........................................................................................................................................................ 37  
APPENDIX B ......................................................................................................................38  
ZONE OUTPUT CONFIGURATIONS.......................................................................................................................... 38  
APPENDIX C ......................................................................................................................39  
ALARM VERIFICATION FACILITY (AVF) .............................................................................................................. 39  
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 39  
APPENDIX D ......................................................................................................................40  
ANCILLARY TRIP (ACF).............................................................................................................................................. 40  
GLOBAL PROGRAMMABLE OPTIONS.................................................................................................................... 40  
APPENDIX E.......................................................................................................................41  
RELAY OUTPUT MAPPING......................................................................................................................................... 41  
AND MAPPING ............................................................................................................................................................... 41  
OR MAPPING.................................................................................................................................................................. 41  
FAULT MAPPING........................................................................................................................................................... 41  
FAULT/ISOLATE MAPPING........................................................................................................................................ 42  
ISOLATE MAPPING ...................................................................................................................................................... 42  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
IFS-2600 Installation & Programming Manual  
APPENDIX F ...................................................................................................................... 43  
GLOSSARY OF TERMS................................................................................................................................................. 43  
APPENDIX G...................................................................................................................... 44  
SUMMARY OF TERMINATIONS AND CAUTIONS.................................................................................................44  
MCP LOOP.....................................................................................................................................................................44  
DETECTION ZONES .................................................................................................................................................... 44  
RELAY OUTPUTS ........................................................................................................................................................ 44  
BELL OUTPUTS ........................................................................................................................................................... 44  
ACF OUTPUTS.............................................................................................................................................................. 44  
WARNING SYSTEM..................................................................................................................................................... 44  
DOOR HOLDER OUTPUTS .........................................................................................................................................44  
AUXILIARY POWER & MIMIC POWER ................................................................................................................... 44  
MAF ISOL & TRANSPONDER 0V .............................................................................................................................. 44  
MIMIC DATA & CLOCK..............................................................................................................................................44  
AC INPUT ......................................................................................................................................................................44  
BATTERY......................................................................................................................................................................45  
DOOR HOLDER AC INPUT.........................................................................................................................................45  
OUTPUT RELAYS ........................................................................................................................................................ 45  
APPENDIX H ...................................................................................................................... 46  
IFS-2600 PROGRAMMED OPTIONS........................................................................................................................... 46  
APPENDIX I........................................................................................................................ 53  
TECHNICAL DRAWINGS .............................................................................................................................................53  
MAIN KEYPAD AND DISPLAY..................................................................................................................................53  
EXPANSION DISPLAY ................................................................................................................................................ 53  
Block Connection Diagram.............................................................................................................................................54  
System Sensor Conventional Detector Connection Diagram .......................................................................................... 54  
System Sensor Conventional Detector Connection Diagram .......................................................................................... 55  
Hochiki Conventional Detector Connection Diagram.....................................................................................................55  
Hochiki Conventional Detector Connection Diagram.....................................................................................................56  
Ancillary Connection Diagram........................................................................................................................................57  
ASE Connection Diagram............................................................................................................................................... 58  
Auto Changeover Dual Sounder Connection Diagram....................................................................................................59  
Auto Change Over Dual Sounder Connection Diagram..................................................................................................60  
MIMIC Connection Diagram..........................................................................................................................................61  
Single Fan Connection Diagram .....................................................................................................................................62  
Dual Fan Connection Diagram........................................................................................................................................63  
Exhaust Fan Connection Diagram...................................................................................................................................64  
Supply Fan Connection Diagram ....................................................................................................................................65  
Smoke Spill Fan Connection Diagram............................................................................................................................ 66  
10W EVAC Connection Diagram...................................................................................................................................67  
10W EVAC Slave Connection Diagram......................................................................................................................... 68  
30W EVAC Connection Diagram...................................................................................................................................69  
30W EVAC Slave Connection Diagram......................................................................................................................... 70  
50W EVAC Connection Diagram...................................................................................................................................71  
50W EVAC Slave Connection Diagram......................................................................................................................... 72  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 5  
COMPATIBLE DETECTORS  
Make  
Model  
Type  
Model Number  
5451 AUS  
51A51  
4451 AUS  
51B51  
51B51S  
51C51  
51D51  
2151 AUS  
2151B AUS  
1151 AUS  
51D51  
BEAM1224  
DHP-100  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
System Sensor  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Smoke  
Smoke  
Smoke  
Thermal  
Smoke  
Smoke  
Type A  
Type A  
Type B  
Type B  
Type B Sealed  
Type C  
Type D  
Photo-Optical  
Photo-Optical  
Ionisation  
Type D  
Beam  
Duct  
Apollo  
Apollo  
Apollo  
Apollo  
Apollo  
Apollo  
Thermal  
Thermal  
Thermal  
Thermal  
Smoke  
Type A  
Type B  
Type C  
Type D  
Ionisation  
Photo Optical  
Series 60  
Series 60  
Series 60  
Series 60  
Series 60  
Series 60  
Smoke  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Hochiki  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal  
Thermal Cool Room  
Smoke  
Type A  
Type A  
Type A  
Type B  
Type B  
Type C  
Type C  
Type C  
DCA-B-60R MkV  
DCC-A  
DCD-A  
DFE-60B  
DFJ-60B  
DCA-B-90R Mk1  
DCC-C  
DCD-C  
Type D  
Type D  
DFE-90D  
FDJ-90D  
DFG-60BLKJ  
SIH-AM  
SIJ-ASN  
SLK-A  
Type B sealed  
Ionisation  
Ionisation  
Photo Optical  
Photo Optical  
Smoke  
Smoke  
Smoke  
SLR-AS  
Olsen  
Olsen  
Olsen  
Olsen  
Olsen  
Olsen  
Thermal  
Thermal  
Thermal  
Thermal  
Smoke  
Type A  
Type B  
Type C  
Type D  
Ionisation  
Photo Optical  
T56B-T6A  
T56B-T6B  
T56B-T6C  
T56B-T6D  
C24B  
Smoke  
P24B  
Panelect  
Panelect  
Panelect  
Panelect  
Panelect  
Panelect  
Panelect  
Panelect  
Thermal  
Thermal  
Thermal  
Thermal  
Smoke  
Smoke  
Smoke  
Smoke  
Type A  
Type B  
Type C  
Type D  
Ionisation  
Ionisation  
Photo Optical  
Photo Optical  
PFS-A  
PFS-B  
PFS-C  
PFS-D  
PFS-I  
PFS-I , MkII  
PFS-P  
PFS-P, MkII  
IEI  
VESDA E700, E70D  
CONTACT DEVICE  
Please contact NOTIFIER INERTIA for any additional detectors.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 6  
IFS-2600 Installation & Programming Manual  
OVERVIEW  
IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal  
display and conventional LED displays for fast and accurate display of system status and changing events.  
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast,  
efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of the  
many user configurable options of this FIP. The FIP can be configured on-site without the need of expensive  
programmers or components.  
A serial printer can also be connected if required. The printer can be used to output programming information for ease of  
modification, for safekeeping and to assist in the commissioning of the installation.  
IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.  
A door holder power supply (using optional transformer) is incorporated into the system for the release of smoke and fire  
doors on alarm.  
IFS-2600 is available in a standard 8-zone configuration and can be expandable to its fully expanded state as required.  
The IFS-2600 in its fully expanded state can;  
Monitor 64 detection zones  
Control 64 optional "mapped" relay outputs  
Output to a serial printer  
Output serially to a mimic panel  
Control to door holders  
Interface as required to any Australian Fire Brigade  
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly interface.  
CAUTION  
IFS-2600 FIP has been tested and approved to AS4428.1 and meets the requirements of AS1670 and AS1668 Parts 1 &  
2.  
However, the equipment must be correctly programmed and installed to suit the specific application. Please ensure  
correct operational parameters are set prior to commissioning. If further details on programming options are required,  
please consult the programming manual or contact our helpful technical support personnel.  
WARNING:  
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if  
not installed and operated in accordance with the manufacturers instructions, may cause interference to radio  
communications. It has been tested and found to comply with the Class A radiated and conducted EMI  
requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility  
requirements of Clause C3.5 in AS4428.0:1997  
CAUTION: Radio communication devices should not be used in the vicinity of fire panels or associated  
ancillary devices and systems  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 7  
SPECIFICATION  
Cabinet  
Zinc Sealed Steel 1.6mm  
Powder Coated  
Hinged Inner Door  
Hinged Outer Door  
Outside Dimensions  
2608 (8 zones)  
2624 (24 zones)  
394mm H x 390mm W x 180mm D*  
750mm H x 390mm W x 180mm D*  
2600 (32 to 64 zones) 18U, 28U & 40U Cabinets  
Battery Box  
*Note: the depth quoted is including the door and break glass.  
The internal cabinet depth not including he door and break glass  
is 140mm.  
AC Operational Voltage  
Internal Power Supplies  
240 VAC 50Hz  
+ 10%  
Battery Charger  
Panel Supply  
Logic Supply  
80C52  
27.3 VDC  
1.5AMP  
24 VDC(nom) 3.0AMP  
5 VDC 2.0AMP  
Microprocessor  
Memory Type  
Liquid Crystal Display  
Fuses  
Non-volatile E2ROM  
2 Lines x 16 Characters LED Backlit  
F1: Panel Supply  
M205 5A  
M205 3A  
F2: Battery Charger  
F3: Battery Protection Polyfuse 3A  
F4: External Supply  
F5: Door Holder  
M205 7A  
M205 3A  
F6: Aux Power Output M205 1A Slow Blow  
F7: Bell  
F8: Warning System  
F9: ACF  
M205 1A  
M205 1A  
M205 1A  
E.O.L Resistor On AZFs, monitored  
outputs, Bells, Warning system, ACF  
4K7 Ohms  
APPROVALS  
Australian Standard AS4428.1 1998  
SSL Approval No AFP-1553  
C-Tick Approval No. N1336  
ENVIRONMENTAL LIMITS  
-10 Deg. C to +55 Deg. C Dry heat.  
+40 Deg. C @ 93% Relative Humidity.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 8  
IFS-2600 Installation & Programming Manual  
SYSTEM EXPANSION  
Zones  
8
Qty  
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
3
2
1
1
1
4
2
1
1
1
5
3
1
1
1
6
3
1
1
1
7
4
Hardware Required  
Main Control Board  
Product Code  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
PCB-2004  
PCB-2005  
PCB-2006  
PCB-804G3  
PCB-816  
Main Termination board  
Power Supply board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
Main Control board  
Main Termination board  
Power Supply board  
8 Zone Expansion board  
16 Zone Indicator board  
16  
24  
32  
40  
48  
56  
64  
Additional relay outputs:  
Relays  
8
16  
24  
32  
40  
48  
56  
64  
Qty  
1
2
3
4
5
6
7
8
Hardware Required  
Product Code  
IFS-717  
IFS-717  
IFS-717  
IFS-717  
IFS-717  
IFS-717  
IFS-717  
IFS-717  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
Relay board containing 8 relays 24VDC 1A  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 9  
POWER SUPPLY RATINGS AND SETTINGS  
INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY  
This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection  
circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.  
AC Input  
30 VAC +10% - 15%  
3.0 AMPS  
26.5 VDC  
3.0 AMPS  
50 mV  
Output Current  
Output Voltage  
Current Limit  
Output Ripple  
INTERNAL 27.3V DC 1.5A BATTERY CHARGER  
Its primary function is to charge the batteries. This supply meets the requirements of AS4428.5.  
AC Input  
30 VAC +10% -15%  
1.5 AMPS  
27.3 VDC  
1.5 AMPS  
200 mV  
Output Current  
Output Voltage  
Current Limit  
Output Ripple  
Important Note:  
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately  
20V +/- 2V.  
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure  
that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.  
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it  
externally. The battery should be thoroughly tested before returning it to service.  
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30  
ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode  
(Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from  
pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to  
bring it up to the minimum level.  
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important  
that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24  
hours and then fully tested to ensure that no damage has occurred due to the deep discharge.  
Internal 5VDC 2A Power Supply  
This supply's primary function is to power all internal operations of the FIP, i.e.: Microprocessor, liquid crystal  
display, LED's keypad etc.  
AC Input  
30 VAC +15% or 27.6VDC+15%  
Output Current  
Output Voltage  
Current Limit  
Output Ripple  
2.0 AMPS  
5.0 VDC  
2.0 AMPS  
150 mV  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 10  
IFS-2600 Installation & Programming Manual  
EXTERNAL 27VDC POWER SUPPLY  
This supply is used in addition to the internal power supply for large systems. Its primary function is to power  
any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5  
Important Notes:  
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.  
If this supply is used to power a NI-2008 gas module, the following additional components are required to  
ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.  
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the  
external +27V output of the IFS-2600 termination board.  
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the  
+27V and 0V of the ancillary device.  
IFS-2600 TERMINATION BOARD  
AC  
INPUT  
REMOTE  
OUTPUT  
REMOTE  
INPUT  
BATT  
INPUT  
+
-
24V 0V 24V 0V  
6A4  
POWER IN  
+
3300uF  
NI-2008 GAS  
SUPPRESSION  
MODULE  
24V  
0V  
OUTPUT  
EXTERNAL  
POWER  
0V  
24V  
SUPPLY  
BATTERY TYPE AND CAPACITIES  
In general, any Sealed Lead Acid Battery, or Wet Lead Acid Battery designed for stationary use is compatible  
with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium  
batteries is not recommended.  
Manufacturer  
Best and Best  
Best and Best  
Best and Best  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Olympic Batteries  
Type  
Number  
BP17-12  
BP24-12  
BP40-12  
CJ12-7  
CJ12-12  
CJ12-18  
CJ12-26  
CJ12-33  
CJ12-40  
CJ12-88  
CJ12-100  
Voltage  
12  
Capacity (Ah)  
Qty Required  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
Sealed LA  
17  
24  
40  
7
12  
18  
26  
33  
40  
88  
100  
2
2
2
2
2
2
2
2
2
2
2
12  
12  
12  
12  
12  
12  
12  
12  
12  
12  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 11  
TECHNICAL DESCRIPTION  
GENERAL  
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination  
board and the power supply board.  
The main control board contains the Microprocessor, EPROM, RAM and E2ROM. The main control board also  
has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this  
board. The main control board complete with the inner door is easily removed during installation to avoid  
damage and allow greater access to the field terminals.  
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply  
and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All  
charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains  
two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.  
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These  
boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a  
jumper that selects which group of eight zones the board refers to.  
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone  
expansion boards fitted.  
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at  
1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest  
output to the main board.  
NOTE This product utilises state of the art components and materials and therefore boards must be returned  
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not  
recommended and would void all warranties on the product.  
TRANSIENT SUPPRESSION  
The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on  
incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all self-  
resetting.  
CURRENT CONSUMPTION  
Zones Fitted  
Quiescent Current  
150 mA  
250 mA  
Quiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF  
8
2.23 AMPS  
2.33 AMPS  
2.43 AMPS  
2.53 AMPS  
2.63 AMPS  
2.73 AMPS  
2.83 AMPS  
2.93 AMPS  
16  
24  
32  
40  
48  
56  
64  
350 mA  
450 mA  
550 mA  
650 mA  
750 mA  
850 mA  
Note:  
1:  
Each installation would require individual battery calculations to be performed for load capacity and  
power supply capacity.  
2:  
Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 12  
IFS-2600 Installation & Programming Manual  
AZF DESCRIPTION  
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's  
significantly reduce the possibility of false alarms and improve product efficiency and reliability.  
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel  
connected detector loads.  
AZF SUPERVISORY CURRENT  
The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line  
resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable,  
are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit  
across the + and - terminals of the detector base. The maximum number of detectors that can be installed on  
each AZF is dependant on the type of detector and is listed in the IFS-2600 ActivFire® listing.  
In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current to  
flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm  
state) or the interruption of the supervisory current will produce a fault signal in the AZF.  
As described above, the level of current is used to define the status of the alarm zone: -  
I = 3.5 mA and below  
FAULT  
I = 4.0 - 5.0mA at 24V  
I = 16 mA to 40 mA (current limited)  
QUIESCENT  
ALARM  
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is  
then transferred to the microprocessor for processing.  
OVERLOAD PROTECTION  
Panel Supply  
Battery Charger  
Battery Protection  
External Supply  
Door Holder  
Aux Power Output  
Bell  
Warning System  
ACF  
AZF Circuits  
Fuse F1  
Fuse F2  
Fuse F3  
Fuse F4  
Fuse F5  
Fuse F6  
Fuse F7  
Fuse F8  
Fuse F9  
Current Limited  
M205 5A  
M205 3A  
Polyfuse 3A  
M205 7A  
M205 3A  
M205 1A Slow Blow  
M205 1A  
M205 1A  
M205 1A  
40mA  
ZONE OVERLOAD SELF RESET  
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down  
and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and  
once the overload is removed, restore power and the fault will clear.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 13  
PRINTER OUTPUT  
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will  
report alarms and faults together with the date and time of the event. The printer can also be used during  
“walk test” mode to produce a history of the test and can also be used to print current programming  
configuration.  
A DB9 plug male is provided at the top of the main termination board. This communication port will  
communicate with an IBM compatible serial printer (ASCII printer) with the following settings.  
Baud Rate  
Data Bits  
Stop Bits  
Parity  
1200 bps  
8
1
None  
DTR  
Handshaking  
CABLE CONNECTION  
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9  
socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a  
male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions  
IFS-2600 END  
DB9 FEMALE  
PRINTER END  
DB25 MALE  
DB9 MALE  
2
3
5
7
8
RX (only for programming)  
TX  
GND  
RTS ( do not use)  
CTS ( only for printer)  
2
3
7
(5)  
4
3
2
5
(8)  
7
PROGRAMMING BY COMPUTER  
Programming of the zones, relays, global functions and time can by set with the DOS based program  
“2600/SW” using the printer port. (Cannot be used with Windows XP)  
After the cable is installed, the program can be run and the menu will prompt for the available functions.  
2600  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 14  
IFS-2600 Installation & Programming Manual  
ALIGNMENT AND ADJUSTMENT  
PCB2006 POWER SUPPLY BOARD  
INTERNAL 24VDC (nom) POWER SUPPLY  
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test  
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until  
voltage is 26.5V 0.05V (26.45V – 26.55V).  
Current limiting is fixed and field adjustment is not possible.  
INTERNAL 27.3 VDC BATTERY CHARGER  
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test  
points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until  
voltage is 27.3V 0.05V (27.25V – 27.35V).  
Current limiting is factory preset and field adjustment is not required.  
EXTERNAL 24VDC (nom) POWER SUPPLY (if fitted)  
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals  
on PCB2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V  
(26.0V – 27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the  
voltage must not go outside the limits as specified for the field ancillaries that it powers.  
PCB2005 TERMINATION BOARD  
INTERNAL 5VDC POWER SUPPLY TP8  
All parameters are fixed and field adjustment is not possible.  
POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10  
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multi-  
turn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V)  
NON ADJUSTABLE TEST POINTS  
TP8 = 5.0 VDC 5%  
5VDC POWER SUPPLY  
TP5 = 12.0 VDC 5% 12VDC POWER SUPPLY  
(If these test point voltages are not correct, please return the main termination board to the factory for  
repair.)  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 15  
ALARM THRESHOLD COMPARATOR TP7  
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER  
SUPPLY as above.  
Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until  
the voltage is as per the following table.  
Rail Voltage  
20.6  
3.3V Setting  
2.833  
2.888  
2.956  
3.025  
3.094  
3.163  
3.231  
3.300  
3.369  
3.438  
3.506  
3.575  
3.644  
3.713  
3.781  
3.795  
3.850  
Range  
2.80 to 2.86  
2.86 to 2.92  
2.93 to 2.99  
2.99 to 3.06  
3.06 to 3.12  
3.13 to 3.19  
3.20 to 3.26  
3.27 to 3.33  
3.34 to 3.40  
3.40 to 3.47  
3.47 to 3.54  
3.54 to 3.61  
3.61 to 3.68  
3.68 to 3.75  
3.74 to 3.82  
3.76 to 3.83  
3.81 to 3.89  
21.0  
21.5  
22.0  
22.5  
23.0  
23.5  
24.0  
24.5  
25.0  
25.5  
26.0  
26.5  
27.0  
27.5  
27.6  
28.0  
FAULT THRESHOLD COMPARATOR TP6  
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER  
SUPPLY as above.  
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust  
until the voltage is as per the following table.  
Rail Voltage  
20.6  
0.6V Setting  
0.600  
0.612  
0.626  
0.641  
0.655  
0.670  
0.684  
0.699  
0.714  
0.728  
0.743  
0.757  
0.772  
0.786  
0.801  
0.804  
0.816  
Range  
0.59 to 0.61  
0.61 to 0.62  
0.62 to 0.63  
0.63 to 0.65  
0.65 to 0.66  
0.66 to 0.68  
0.68 to 0.69  
0.69 to 0.71  
0.71 to 0.72  
0.72 to 0.74  
0.74 to 0.75  
0.75 to 0.76  
0.76 to 0.78  
0.78 to 0.79  
0.79 to 0.81  
0.80 to 0.81  
0.81 to 0.82  
21.0  
21.5  
22.0  
22.5  
23.0  
23.5  
24.0  
24.5  
25.0  
25.5  
26.0  
26.5  
27.0  
27.5  
27.6  
28.0  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 16  
IFS-2600 Installation & Programming Manual  
CONFIGURATION JUMPERS  
IFS2004 - JP3 DEFAULT  
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard  
factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.  
IFS2004 - JP4 PROGRAM DISABLE  
When fitted, jumper between these pins to inhibit program changes.  
IFS2004 - JP5 CPU RESET  
With panel operating, a momentary short across these pins will cause a CPU restart.  
IFS2005 – JP2 DOOR HOLDER BYPASS  
If zoned door holder outputs are required and is to be done external to the main termination board,  
then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB  
does this.  
Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be  
linked on PCB2004 CPU board prior to Version 6 Firmware.  
IFS2006 – JP1 EXTERNAL PS MONITORING  
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU  
monitoring.  
IFS804 - JP1-7 ZONE BOARD ADDRESSING  
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones.  
Place jumper in link position for the appropriate 8 zones to which the expansion board applies.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 17  
PLACING INTO OPERATION  
Suitably qualified technicians must install the panel. The following check procedures are recommended after  
every installation and prior to initial power-up.  
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal  
filings, loose circuit boards, loose cabling, damage in transit etc.  
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to  
the equipment.  
EQUIPMENT AS FITTED  
QTY  
Description  
Code  
1
1
1
MAIN CONTROL BOARD  
IFS -2004  
IFS -2005  
IFS -2006  
IFS -804  
IFS -816  
IFS-717  
MAIN TERMINATION BOARD  
MAIN POWER SUPPLY  
8 ZONE EXPANSION BOARD  
16 ZONE INDICATOR BOARD  
ADD ON, 8 WAY RELAY BOARD  
EXTERNAL POWER SUPPLY BOOSTER  
PS244, PS249, NPS-3,  
NPS-5, NPS-11  
3A DOOR HOLDER P/SUPPLY TRANSFORMER  
2600/DHTX  
INITIAL CHECKLIST  
System general appearance good  
Cabinet colour and condition good  
Cabinet keyed 003  
All circuit boards firmly fastened  
Manual call point fitted & functional  
Viewing window clear and firmly secured  
Cable entries adequately sealed  
240VAC mains cabling is correctly terminated  
All earthing secured  
Transformer securely mounted  
Transformer correctly wired  
All ribbon cables firmly secured  
All operational zones adequately identified  
All fuses correct value and fitted properly  
All other modules securely fitted  
Manufacturing label affixed  
You are now ready to power up the IFS-2600 Fire Indicator Panel.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 18  
IFS-2600 Installation & Programming Manual  
POWER UP CHECKLIST  
Ensure batteries are disconnected.  
Turn mains switch to "on"  
The "mains on" led should light.  
Allow 15 seconds for the panel to perform its start up tests.  
Connect batteries  
FUNCTIONAL TESTING  
Primary ac supply voltage: 200 or 220 or 240vac +10% as required  
Charger output voltage without batteries: 27.3v dc  
Keypad functional  
Perform auto test  
Led’s all functional  
LCD backlighting functional  
Liquid crystal display functional  
Zone fault detection  
Zone alarm detection  
Internal sounder operating  
MCP loop wired to zone number ______ (if applicable)  
Test auxiliary power output  
Test bell output  
Test warning system output  
Test ACF output  
Test door holder output (optional)  
Test bell output supervision  
Test warning system output supervision  
Test ACF output supervision  
Test brigade alarm relay #1  
Test brigade alarm relay #2  
Test standby relay (normally energised)  
Test fault relay (normally energised)  
Test mains fail relay  
Test isolate relay  
Test general alarm relays (2)  
Test relay boards (if fitted)  
Test open collector output boards (if fitted)  
Press "battery test" once  
If batteries are flat, allow 24hrs to charge and then re-test.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 19  
FAULT RECORD  
FAULT  
CORRECTION  
DATE  
TESTS SATISFACTORILY COMPLETED.  
TESTED BY _______________________________  
SIGNATURE _______________________________  
DATE OF TEST ____________________________  
If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now  
ready for operation.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 20  
IFS-2600 Installation & Programming Manual  
INSTRUCTIONS TO OPERATORS  
INDICATORS  
Qty  
1
Descriptor  
Colour  
Green  
Function  
Buzzer  
Yes  
MAINS ON  
Illuminates when there is 200/220/240 VAC supply to  
the panel.  
1
BATTERY  
FAULT  
Yellow Illuminates if the battery fails a battery test.  
Illuminates if batteries are disconnected >30  
seconds.  
Illuminates if batteries are short circuit >30 seconds.  
Yellow Illuminates if the power supply is outside the  
manufacturers range.  
Yellow Illuminates if the battery charger is outside the  
recommended float charge voltage.  
Yellow Illuminates if;  
1
1
1
PSU FAULT  
Yes  
Yes  
Yes  
CHARGER  
LOW  
COMMON  
FAULT  
Any un-isolated zone goes into fault.  
ACF output is open or short circuit  
Bell output is open or short circuit  
Warning System output is open or short circuit  
Battery Fault  
Charger Fault  
Power Supply Fault  
MAF Isolate Input is Open Circuit  
Configuration Fault  
1
1
ACF ACT  
ACF FLT  
Red  
Illuminates if the ACF output has been activated.  
Yellow Illuminates if the ancillary circuit is open or short  
circuit. The LED will extinguish when the load is  
restored.  
Yellow Illuminates if the ancillary output has been manually  
isolated.  
Yes  
Yes  
1
ACF ISO  
1
1
Bell ACT  
Bell FLT  
Red  
Illuminates when the bell output has been energised.  
Yellow Illuminates if the bell circuit is open or short circuit.  
The LED will extinguish when the load is restored.  
Yellow Illuminates if the bell output has been manually  
isolated.  
1
1
1
Bell ISO  
Warning  
System ACT  
Warning  
Red  
Illuminates if the Warning System output has been  
energised.  
Yellow Illuminates if the Warning System circuit is open or  
short circuit. The LED will extinguish if the load is  
restored.  
Yellow Illuminates if the Warning System has been manually  
isolated.  
Yes  
Yes  
System FLT  
1
8
Warning  
System ISO  
ALARM LEDS  
Red  
This LED will flash if it's corresponding zone goes  
into alarm. It will remain flashing until it is  
Acknowledged at which time it will go steady and  
remain on until the alarm is reset. If the zone is  
programmed as a time delay type, a steady LED  
indicates the “pre-alarm” condition. If the zone is  
isolated and in alarm it will also be steady.  
8
8
FAULT LEDS  
Yellow This LED illuminates if it's corresponding zone goes  
into fault. It will remain on until the fault is removed.  
Yellow This LED illuminates if its corresponding zone is  
isolated. It will remain on until the zone is de-  
isolated.  
Yes  
ISOLATE LEDS  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 21  
SUGGESTED ALARM PROCEDURE  
The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire  
indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel  
not be operated in an emergency situation by anyone other than suitably qualified fire fighters.  
Do not open fire indicator panel door or press any buttons until fire officers arrives.  
Determine location of the fire by inspecting the label beside any lit red zone alarm LEDs on the panel.  
Visually inspect area at a safe distance for actual fire or false alarm.  
Notify fire-monitoring station of either result.  
Perform evacuation and extinguishing operations as required.  
IF a FIRE, direct fire fighters to the fire indicator panel and cause of alarm as they arrive.  
IF a FALSE ALARM, advise maintenance technicians to determine and rectify cause.  
Record all events in logbook.  
NOTE A suitably qualified fire officer should perform the above procedure. These are suggested procedures  
only, and if specific fire procedures are available or issued, they MUST prevail.  
OPERATOR INSTRUCTIONS  
The functions of the IFS-2600 are divided into three (3) categories  
Fire Fighter Functions  
Global Functions  
Zone Functions  
FIREFIGHTER FUNCTIONS  
Fire Fighter Functions are those specifically used by the Fire Brigade on attendance. Following is an  
explanation of their operation and the keystrokes required to perform the function required. These keys are  
located at the top of the keypad marked FIREFIGHTER’S FACILITY and bordered in red.  
ACKNOWLEDGE  
ACK  
The purpose of the internal buzzer is to alert persons of a new event on the panel, and a new potential fire  
danger. Once the fire's location has been determined, the fire-fighter may wish to silence the internal buzzer  
without having to totally reset the alarm.  
When the buzzer is operating, pressing the "ACK" key once will silence it, however the External Alarm Bell will  
continue to sound. If a subsequent alarm arises, the buzzer will be reactivated and a second ACK operation  
will be required to silence it.  
When an alarm is acknowledged, the Alarm LED will stop flashing and light continuously.  
RESET  
RESET  
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) that have  
been acknowledged. This returns the zone back to its "normal" state. The reset key only operates on zones  
with acknowledged alarms.  
ISOLATE  
ISOLATE  
The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility.  
The isolate key only operates on zones with acknowledged alarms.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 22  
IFS-2600 Installation & Programming Manual  
EXT BELL  
ISOL  
BELL ISOLATE  
Depressing the "EXT BELL ISOLATE" key will isolate the bells. The "Ext Bells Isolate" LED will illuminate and  
the bells will not sound until the bells are de-isolated. Pressing "EXT BELL ISOLATE" a second time will de-  
isolate the bell.  
WARN SYS  
ISOL  
WARN SYS ISOLATE  
Depressing the "WARN SYS ISOLATE" key will isolate the warning system. The "Warn Sys Isolate" LED will  
illuminate and the warning system will not operate in the event of an alarm. Pressing "WARN SYS ISOLATE"  
a second time will de-isolate the warning system.  
GLOBAL FUNCTIONS  
Global functions are those relating to the overall system and are not specific to particular zones. Following is  
an explanation of their operation and the keystrokes required to perform the function.  
BATTERY TEST  
BATT  
TEST  
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a  
battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and apply  
load on the batteries for 15 seconds.  
The result of the test will be displayed on the LED's. If the "Battery Fault" LED is on, only a successful battery  
test will turn the LED off. The pressing of any key during the test period will abort the battery test and return  
the system back to normal mode.  
Battery test function is disabled when the panel is in alarm condition.  
AUTO  
TEST  
AUTO TEST MODE  
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any  
zone(s) is in alarm. Auto test will perform the following test functions;  
Turn on ALL LEDs for 0.5 seconds  
Test LCD backlighting  
Test panel memory (E ROM & RAM)  
2
Test LCD  
Isolate all alarm zones  
Fault test all alarm zones  
Alarm test all alarm zones  
Test buzzer  
The pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal mode  
once the current test is complete.  
Note  
During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 second  
delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously  
configured types.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 23  
WALK TEST MODE  
WALK  
TEST  
This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of  
detector zones. This mode cannot be selected if any zone(s) is in alarm. Entry to walk test mode will be  
acknowledged by three beeps and the LCD will display "WALK TEST MODE".  
For the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells  
only) and all zones are set to type #1 (standard latching, 2 second).  
If the bells are not required to ring during walk test, simply press the "EXT BELL ISOLATE" key once. The EXT  
BELL ISOLATE LED will illuminate to verify that the bells have been isolated.  
Any alarm signal from detectors etc. will be received by the panel on its appropriate zone. The panel will beep  
to acknowledge receipt of the alarm and indicate the alarm by illuminating the appropriate alarm LED for 4  
seconds (the bells will also ring for a 3 second period unless previously isolated).  
The zone and detector will then be automatically reset for 15 seconds  
If the optional printer is connected, the alarm will be printed out as it is received. This can eliminate the need  
for a second serviceman to record zone numbers during walk test and the printout can be retained for  
verification at a later date.  
Pressing any key will terminate the walk test mode and return the panel back to normal operation, restoring all  
zone types and output configurations also ensuring that bell and ancillary outputs are de-isolated. The bells will  
give three pulses of 1 second each to warn any testers still in the building that walk test mode has been  
terminated.  
Failure to receive any alarms or keystrokes within a 15 minutes period will result in the panel automatically  
exiting walk test mode and returning back to normal as follows:  
Bell outputs to be de-isolated.  
Ancillary outputs to be de-isolated.  
Bell will sound 3 times, each of 1-second duration.  
Exit from walk test mode.  
Zone types and output configurations restored  
ACF ISOLATE  
ACF  
ISOL  
Depressing the "ACF ISOLATE" key will isolate the ACF (Ancillary output) and the Door Holder Output. The  
ACF isolated LED will illuminate and the output will not operate until de-isolated. Pressing "ACF ISOLATE" for  
a second time will de-isolate the output.  
If the ancillary output has already been tripped and is programmed as latching, isolating the ACF will not affect  
the existing ancillary output. If the ACF is isolated prior to the alarm, it will prevent the ancillary output from  
tripping. This does not apply to the Door Holder output.  
ACF RESET  
ACF  
RESET  
Resetting of the ancillary output (ACF) is only required if the ancillary output was programmed as latching.  
The ancillary alarm will remain latched until manually reset. Pressing the "ACF RESET" button will extinguish  
the 'ACF Activated' LED and de-energise the ancillary output. Pressing "ACF RESET" when the ACF is not  
tripped will have no effect.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 24  
IFS-2600 Installation & Programming Manual  
ZONE FUNCTIONS  
Zone functions are those relating specifically to the detection zones. Following is an explanation of their  
operation and the keystrokes required to perform the function required.  
ALARM TEST  
ALARM TEST  
#
ENT  
The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a  
detector going into alarm, therefore testing the zone(s) alarm detection capability.  
A resistive load equal to worst case alarm condition is placed on the zone for a period of 120 seconds and  
then removed, if the zone being tested is not a latching type, the alarm will reset automatically once the load is  
removed. Acknowledging and resetting the alarm will terminate an alarm test.  
Once the zone has alarmed, all outputs are initiated (as programmed) similar to a real alarm.  
The zone may be isolated prior to an alarm test if desired; this will prevent any outputs from operating.  
‘#’ in the above key sequence is the zone number.  
If only one zone is to be tested, use the appropriate number. Alternatively the "ALL" button can be used to  
simultaneously test all zones.  
To perform an alarm test:  
1. Press the "ALARM TEST" button once; the buzzer will give 2 short beeps to indicate that alarm test mode  
has been entered.  
2. The LCD display will read "ALARM TEST MODE, ENTER ZONE No.".  
3. Now enter the zone number ("#") 1-64 or “all”  
4. Press "ENT"  
If a correct entry is made, alarm testing on the zone commences immediately. However remember there is a 2  
second transient delay on all zones. It will therefore take approximately 2 seconds before the zone registers an  
alarm (this could be longer, depending on zone type).  
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ALARM TEST"  
button will need to be depressed again to re-enter alarm test mode.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 25  
FAULT TEST  
FAULT TEST  
#
ENTER  
The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst-case  
condition for fault.  
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is  
returned back to its normal condition.  
If several zones are being tested consecutively and are being entered at a rate faster than the 5-second fault  
timer, the fault timeout will occur 5 seconds after the last entry was completed.  
Once the zone has registered a fault, all outputs relating to that zone are initiated similar to a real fault.  
The zone may be isolated prior to a fault test if desired. This will prevent any outputs from operating.  
‘#’ in the above key sequence is the zone number.  
If only one zone is to be tested, use the appropriate zone number. Alternatively the "ALL" button can be used  
to simultaneously test all zones.  
To perform a fault test on a particular zone or on all zones:  
1.  
Press the "FAULT TEST" button once.  
The buzzer will give 2 short beeps to indicate that fault test mode has been entered.  
2.  
3.  
4.  
The LCD display will read "FAULT TEST MODE, ENTER ZONE No.".  
Enter the zone number ("#") 1-64 or “all”.  
Press "ENTER".  
A long beep will signify an incorrect entry and the panel will revert back to normal operating mode. The  
"FAULT TEST" button will need to be pressed again to re-enter fault test mode.  
If a correct entry is made, fault testing on the zone commences and the fault LED will illuminate.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 26  
IFS-2600 Installation & Programming Manual  
ISOLATE  
ISOLATE  
#
ENTER  
The isolate function prevents the transmission of alarms or faults from the zones, to the master alarm facility.  
‘#’ in the above key sequence is the zone number.  
If only one zone is to be isolated, use the appropriate zone number. Alternatively the "ALL" button can be used  
to simultaneously isolate all zones.  
To isolate a particular zone or all zones:  
1.  
Press the "ISOLATE" button.  
The buzzer will give 2 short beeps to indicate that isolate mode has been entered.  
2.  
3.  
4.  
The LCD display will read "ALARM ISOL. MODE, ENTER ZONE No.".  
Enter the zone number ("#")1-64 or “all”.  
Press "ENTER".  
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ISOLATE"  
button will need to be depressed again to re-enter isolate mode.  
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm  
outputs are isolated and indicators remain visible.  
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the  
"ALL" function for a second time will de-isolate all zones.  
RESET  
RESET  
#
ENTER  
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being  
reset. This returns the zone back to its "normal" state.  
‘#’ in the above key sequence is the zone number.  
If only one zone is to be reset, type in the zone number. Alternatively the "ALL" button can be used to  
simultaneously reset all zones.  
To perform a reset on a particular zone or on all zones:  
1.  
Press the "RESET" button.  
The buzzer will give 2 short beeps to indicate that reset mode has been entered.  
2.  
3.  
4.  
The LCD display will read "ALARM RESET MODE, ENTER ZONE NO".  
Enter the zone number ("#") 1-64 or “all”.  
Press "ENTER".  
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "RESET" button  
will need to be depressed again to re-enter reset mode.  
If a correct entry is made, resetting of the zone begins immediately. Any alarm indication will be removed  
immediately; also resetting the zone(s) programmed outputs.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 27  
PROGRAMMING  
GLOBAL OPTIONS  
ANCILLARY TRIP  
1
2
3
4
LATCHING  
NON-LATCHING  
LATCHING  
NORMALLY DE-ENERGISED  
NORMALLY DE-ENERGISED  
NORMALLY ENERGISED  
NORMALLY ENERGISED  
NON-LATCHING  
ALARM VERIFICATION  
1
2
3
4
5
DISABLED  
2 MINUTES  
3 MINUTES  
4 MINUTES  
5 MINUTES  
TIME  
(DD) / (MM) / (YY)  
(HH) : (MM)  
ZONE OPTIONS  
DESCRIPTION  
INPUT DELAY  
1
2
3
4
5
6
7
8
9
10  
Standard Latching  
Standard Latching  
Non Latching  
Non Latching  
Time Delay  
Time Delay  
Time Delay  
Time Delay  
Time Delay  
2 seconds  
2 seconds with AVF  
2 seconds  
20 seconds  
10 seconds  
20 seconds  
30 seconds  
40 seconds  
50 seconds  
60 seconds  
Time Delay  
Type  
Output Description  
1
2
3
4
5
6
7
Indicate Only  
Indicate, Bell  
Indicate, Bell, General Alarm  
Indicate, Bell, General Alarm, Ancillary  
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1  
Indicate, Bell, General Alarm, Ancillary Brigade Relay #2  
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 28  
IFS-2600 Installation & Programming Manual  
OUTPUT RELAY OPTIONS  
Optional Relays can be programmed to simulate: -  
Isolate Relay  
ACF Output  
Brigade Relay #1  
Brigade Relay #2  
Fault Relay  
Mains Fail Relay  
General Alarm Relay  
Bell Output  
Door Holder Relay  
Door Switch  
Reset  
Or Can Be Used To:  
"MAP AND"  
"MAP OR"  
“MAP FAULT”  
“MAP ISOLATE”  
“MAP ISO/FAULT”  
Up to 5 Zones in Alarm  
Up to 5 Zones in Alarm  
Up to 5 Zones in Fault  
Up to 5 Zones in Isolate  
Up to 5 Zones in Isolate/Fault  
DEFAULT SETTINGS  
ACF OUTPUT  
NON-LATCHING, NORMALLY DE-ENERGISED  
ALARM VERIFICATION (AVF)  
TIME  
3 MINUTES  
1/1/11 11:11  
ZONE TYPES  
STANDARD LATCH 2S  
ZONE OUTPUT CONFIG  
RELAY MAPPING  
I-B-G-A-BR1 & BR2  
MAP -OR-, MAPPING = 1 TO 1  
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............  
The 2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number  
of relay boards.  
Zone expansion boards fitted must have the correct jumper selected.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 29  
PROGRAM MODE  
Press the following buttons in order shown to enter programming mode.  
PREVIOUS NEXT SELECT EXIT ENTER  
PROGRAMMING MODE  
The liquid crystal display will display all messages and prompts required to program the 2600.  
ONLY the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All  
other keys will give an error beep and are ignored.  
Alarm detection is not affected during the programming function but you must exit programming mode if any  
other panel functions are to be performed including acknowledge and reset of alarms.  
Note:  
Refer to appendices for detailed explanation of functions  
PROGRAMMING HIERARCHY  
EXIT  
SAVE CHANGES  
YES  
NO  
ZONES  
GLOBAL  
RELAY  
PRINT  
ZONES  
TYPE  
OUTPUT  
INDICATE  
I BELL  
STD LATCHING  
STANDARD LATCHING AVF  
NON LATCH  
IB GENERAL  
NON LATCH 20S  
TIME DELAY 10S  
TIME DELAY 20S  
TIME DELAY 30S  
TIME DELAY 40S  
TIME DELAY 50S  
TIME DELAY 60S  
IBG ACF OUT  
IBGA BRIGADE 1  
IBGA BRIGADE 2  
IBGA BRIGADE 1 & 2  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 30  
IFS-2600 Installation & Programming Manual  
RELAYS  
TYPE  
MAPPING  
ISOLATE RELAY  
ANCILLARY OUTPUT (ACF)  
BRIGADE RELAY #1  
BRIGADE RELAY #2  
FAULT RELAY  
MAINS FAIL RELAY  
GENERAL ALARM RELAY  
BELL OUTPUT  
DOOR HOLDER RELAY  
MAP - AND  
MAP - OR  
(00)(00)(00)(00)(00)  
(00)(00)(00)(00)(00)  
(00)(00)(00)(00)(00)  
(00)(00)(00)(00)(00)  
(00)(00)(00)(00)(00)  
MAP - FAULT  
MAP – ISOLATE  
MAP – ISOLATE / FAULT  
DOOR SWITCH  
RESET  
GLOBAL  
ACF  
NON-LATCHING ND  
LATCHING ND  
NON-LATCHING NE  
LATCHING NE  
AVF  
RELAY  
MAP RELAY (XX) >>>  
FROM ZONE XX  
TIME  
(DD) / (MM) / (YY)  
(HH) : (MM)  
DISABLED  
2 MINUTES  
3 MINUTES  
4 MINUTES  
5 MINUTES  
ND: = NORMALLY DE-ENERGISED  
NE: = NORMALLY ENERGISED  
PRINT  
PRINT  
PRINTS OUT CURRENT CONFIGURATION  
MAIN MENU  
(ZONES)  
GLOBAL  
RELAYS  
PRINT  
Use the "NEXT" & "PREVIOUS" keys to scroll through "ZONES" "RELAYS" "GLOBAL" "PRINT" and wrap  
around. Once the desired option has been highlighted, pressing the "SELECT" button will select it.  
Pressing "EXIT" at this stage will exit programming mode.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 31  
EXIT PROGRAMMING MODE  
SAVE CHANGES  
YES (NO)  
Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been  
highlighted, pressing the "SELECT" button will select it.  
Highlighting "YES" and pressing "SELECT" will write all changes made to the system memory (E2ROM) and  
the panel will then restart.  
WARNING!! The above action cause the panel to drop any door holders / air-conditioning if connected.  
Highlighting "NO" and pressing "SELECT" will ignore any changes made to the programming and exit back to  
normal panel operation without restarting.  
Note: This does not apply to saving changes to the time. Changes to time are saved immediately the  
select key is pressed when in the time adjustment menu.  
ZONE PROGRAMMING  
SELECT ZONE #  
SELECT ZONE #  
(ALL)  
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3"  
Up to the maximum number of zones fitted and then wrap around. Once the desired zone number has been  
highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to main menu.  
ZONE SELECTED  
ZONE # ALL  
(TYPE) OUTPUT  
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "OUTPUT". Once the desired option has  
been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return  
"SELECT ZONE #".  
ZONE TYPE  
ZONE # ALL TYPE  
STD LATCHING  
Use the "NEXT" & "PREVIOUS" keys to scroll through  
STD LATCHING  
STD LATCHING AVF  
NON LATCH  
NON LATCH 20S  
TIME DELAY 10S  
TIME DELAY 20S  
TIME DELAY 30S  
TIME DELAY 40S  
TIME DELAY 50S  
TIME DELAY 60S  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 32  
IFS-2600 Installation & Programming Manual  
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection  
or pressing "EXIT" will return to zone selected.  
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously  
set options will not be displayed if "ALL" is selected.  
A function of “BELL” also operates the WARNING SYSTEM.  
ZONE OUTPUT CONFIGURATION  
ZONE #ALL OUTPUT  
IBGA BRIG 1&2  
Use the "NEXT" & "PREVIOUS" keys to scroll through:  
INDICATE  
I BELL  
IB GENERAL  
IBG ACF OUT  
IBGA BRIGADE 1  
IBGA BRIGADE 2  
IBGA BRIG 1&2  
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at  
this stage will return to "Zone Selected".  
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously  
set options will not be displayed if "ALL" is selected.  
A function of “BELL” also operates the WARNING SYSTEM.  
RELAY PROGRAMMING MODE  
SELECT RELAY #  
SELECT  
RELAY#  
(ALL)  
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3". Up to 64 and then wrap around.  
Once the desired relay number has been selected, pressing the "SELECT" button will select it. Pressing  
"EXIT" at this stage will return to main menu.  
RELAY SELECTED  
RELAY #ALL  
(TYPE) MAPPING  
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "MAPPING". Once the desired option has  
been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to  
"Select Relay #".  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 33  
RELAY TYPE  
RELAY #ALL TYPE  
(GENERAL)  
Use the "NEXT" & "PREVIOUS" keys to scroll through:  
ISOLATE  
ANCILLARY  
BRIGADE 1  
BRIGADE 2  
FAULT  
MAINS FAIL  
GENERAL  
BELL  
DOOR HOLDER  
MAP -AND-  
MAP -OR-  
MAP –FAULT-  
MAP –ISOLATE-  
MAP -ISOLATE/FLT-  
DOOR SWITCH  
RESET  
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection  
or pressing "EXIT" will return to "Relay Selected".  
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously  
set options will not be displayed if "ALL" is selected.  
RELAY MAPPING  
RELAY #1 MAP  
(00) 00 00 00 00  
** Relay mapping can only be selected if the relay is set as a MAP type.  
These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated from.  
Use the "NEXT" and "PREVIOUS" keys to increment/decrement the zone number within the brackets.  
Use the "ENTER" key to move to the next field. Fields may be changed as required and set by pressing  
"SELECT".  
Any fields left as (00) will be ignored.  
Pressing "EXIT" at this stage will return to "RELAY # ".  
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously  
set options will not be displayed if "ALL" is selected.  
GLOBAL PROGRAMMING  
(ACF)  
AVF  
RELAY  
TIME  
Use the "NEXT","PREVIOUS" & "SELECT" keys to select.  
Pressing "EXIT" will return to "Main Menu".  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 34  
IFS-2600 Installation & Programming Manual  
ACF OUTPUT  
ACF OUTPUT  
(NON-LATCH ND)  
Use the "NEXT" & "PREVIOUS" keys to scroll through:  
LATCHING ND  
NON-LATCH NE  
LATCHING NE  
Note: The option previously set is displayed in brackets and is the first to be displayed.  
ND = Normally De-energised i.e.: Output is not energised until an alarm occurs.  
NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs.  
AVF  
AVF TIMEOUT  
(3 MINUTES)  
Use the "NEXT" & "PREVIOUS" keys to scroll through:  
DISABLED  
2 MINUTES  
3 MINUTES  
4 MINUTES  
5 MINUTES  
Note: The option previously set is displayed in brackets and  
is the first to be displayed.  
RELAY (GLOBAL RELAY UNITY MAP)  
MAP RELAY (XX) >>  
FROM ZONE (XX)  
Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone.  
Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity  
map.  
This function will start programming relays starting from the relay number specified in a 1 to 1 configuration  
with zones starting from the first zone number specified.  
Example 1: if the above table was to look like this:  
MAP RELAY (10) >>  
FROM ZONE (01)  
Then relay #10 would be set as MAP OR with its mapping as (01) 00 00 00 00, relay #11 would be set as MAP  
OR with it’s mapping set as (02) 00 00 00 00 and so on all the way up to relay #64. Relays number 1-through  
9 remains unaffected by this function.  
Example 2: if the above table was to look like this:  
MAP RELAY (01) >>  
FROM ZONE (09)  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 35  
Then relay #1 would be set as MAP OR with its mapping as (09) 00 00 00 00, relay #2 would be set as MAP  
OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64.  
Note: In example 2, zone number 64 is reached and there are still more relays to go. (I.e. we are only at  
relay #56) the programming stops at this point and any relays not yet programmed will be left in their  
previous programmed mode and are unaffected by this function.  
PRINT PROGRAMMING DATA  
Prints the programming data currently stored in RAM, including all changes made (they may have not yet been  
written to the E2ROM).  
Output is printed directly onto the serial printer if fitted.  
TIME (DATE & TIME)  
The current DATE & TIME will be displayed as DD/MM/YY (in 24h format)  
Use the PREVIOUS” & NEXT” keys to increment or decrement the number highlighted by brackets.  
The ENTER key will move to the next field.  
When finished, the SELECT key must be pushed to store the date/time.  
Note:  
The Date/Time data is saved when the Select key is pushed.  
DO NOT select “Save Changes “Y” as this will restart (and drop any door holders / air-  
conditioning if connected).  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 36  
IFS-2600 Installation & Programming Manual  
APPENDIX A  
DESCRIPTION OF ALARM ZONE TYPES  
Different zone types can be selected using the programming mode. Each zone can be selected as any one of  
the following:  
Type  
1
2
3
4
5
6
7
Description  
Standard Latching  
Standard Latching  
Non Latching  
Non Latching  
Time Delay  
Time Delay  
Time Delay  
Time Delay  
Time Delay  
Input Delay  
2 seconds  
2 seconds with AVF  
2 seconds  
20 seconds  
10 seconds  
20 seconds  
30 seconds  
40 seconds  
50 seconds  
60 seconds  
8
9
10  
Time Delay  
LATCHING TYPE  
Once an alarm condition is received from the detector, the alarm zone will start a timer, if after 2 seconds the  
detector is still activated the alarm zone will register an alarm condition. Indicators will illuminate and alarm  
functions are initiated immediately, unless zone is set as AVF - refer Appendix C. The alarm zone will remain  
in alarm until manually reset.  
A reset is performed by interrupting the power to the detector for 0.5 seconds and returning the alarm zone  
back to its quiescent state. If an alarm is still present in the detector area, the detector will re-activate and the  
2-second timer will be re-initiated.  
NON LATCHING TYPE  
A temporary actuation device (e.g. Flow Switch) is usually connected to this type of alarm zone. Once a  
signal has been received CONTINUOUSLY for 2 seconds or 20 seconds (dependant on programming) an  
alarm will be registered causing the alarm LED to flash and alarm functions will be performed as programmed.  
The alarm group will remain in alarm until the actuating device no longer reports a signal. When actuating  
device signal is clear, the alarm is cleared, causing the zone to power down for 0.5 seconds and return back to  
normal state.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 37  
TIME DELAY AZF  
The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is  
used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991.  
Example:  
Timer #1 = 60 seconds  
Once the first alarm is received, the alarm LED is turned on steady; this indicates "PARTIAL ALARM"  
condition.  
The detector is then reset (by removing its power for 0.5 seconds) and a timer is also started for 60 seconds  
(TIMER#1). Another timer of 10 seconds (TIMER#2) is also started. The zone must respond again within this  
10 seconds (TIMER#2) to register another alarm.  
Failure to receive another alarm within this 10-second period will return the zone back to its normal state  
immediately and extinguish the alarm LED.  
If an alarm is received, the detector is reset again and TIMER#2 is also reset.  
This monitoring continues until the 60-second timer (TIMER#1) has elapsed and then the NEXT alarm signal  
will trip the zone into "FULL ALARM". This is the stage at which all mapped relays, bells etc. will operate.  
When "FULL ALARM" condition is reached, a third timer (TIMER#3) of 70 seconds is started. This timer is  
used to prevent "hunting" of air conditioning fans as specified in AS1668  
TIMER#2 is kept operating and alarm signals are still to be received as per previous. Alarm signals are  
required continually to keep the zone in "FULL ALARM". Each time another alarm is received Timer#3 is  
restarted (i.e. 70 seconds)  
Failure to comply with TIMER#2 will result in the zone being returned back to its NORMAL state once  
TIMER#3 has elapsed.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 38  
IFS-2600 Installation & Programming Manual  
APPENDIX B  
ZONE OUTPUT CONFIGURATIONS  
Once a zone has alarmed, its output functions as programmed to one of the following output types.  
Type Output Description  
1
Indicate Only  
2
3
4
5
6
7
Indicate, Bell  
Indicate, Bell, General Alarm  
Indicate, Bell, General Alarm, Ancillary  
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1  
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #2  
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2  
NOTE: A function of “BELL” also operated the WARNING SYSTEM.  
Refer to technical specification for descriptions of output types.  
The zone can also be programmed to operate one (1) or more relay contacts through the use of the relay  
mapping output feature.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 39  
APPENDIX C  
ALARM VERIFICATION FACILITY (AVF)  
Alarm verification (AVF) is a facility used to minimise false alarms.  
AVF only applies to the zones programmed for the AVF function.  
GLOBAL PROGRAMMABLE OPTIONS  
AVF TIMEOUT  
Disabled  
2 Minutes  
3 Minutes  
4 Minutes  
5 Minutes  
Operation is as follows:  
If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first  
AVF zone in alarm.  
This zone and all other zones programmed as AVF zones are reset by shutting down power to their detectors  
for 12 seconds, the power is then restored and the zones are re- enabled.  
The alarm verification zones are now in "alert" mode. Any AVF zone going into alarm within the pre-selected  
timeout period (2,3,4,5 minutes) will then cause an immediate alarm condition with all the programmed output  
functions being initiated.  
If no alarm is received within this period, the AVF zones are removed from the "alert" mode and returned to  
normal. A further alarm will re-initiate the reset sequence etc.  
Other zones are unaffected by the actions of AVF zones. They will all function as normal, regardless of AVF  
zone status.  
If the timeout period is disabled, the alarm will transmit instantly thus making the AVF non-functional.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 40  
IFS-2600 Installation & Programming Manual  
APPENDIX D  
ANCILLARY TRIP (ACF)  
The ancillary trip is used for the shutting down of air conditioning systems etc. in the event of a fire.  
GLOBAL PROGRAMMABLE OPTIONS  
ANCILLARY TRIP (ACF)  
NON-LATCHING ND  
LATCHING  
NON-LATCHING  
LATCHING  
ND  
NE  
NE  
The ancillary trip can be programmed as latching or non- latching depending on the application.  
It call also be programmed as normally energised or normally de-energised.  
If a zone is programmed to operate the ancillary trip, an alarm condition will energise the ancillary trip until the  
alarm is removed (if non-latching), or until the alarm is removed and the ACF is manually reset via the keypad  
(latching).  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 41  
APPENDIX E  
RELAY OUTPUT MAPPING  
A total of 64 expansion relays can be fitted to the IFS-2600. Each relay can be individually programmed to  
mimic any of the following;  
STANDARD OUTPUTS WHICH MAY BE MIMICED  
ANCILLARY OUTPUT (ACF)  
BRIGADE ALARM RELAY #1  
BRIGADE ALARM RELAY #2  
*
*
FAULT RELAY (NORMALLY ENERGISED)  
MAINS FAIL RELAY (NV) (NORMALLY ENERGISED)  
ISOLATE RELAY  
GENERAL ALARM RELAYS  
BELL OUTPUT  
DOOR SWITCH  
RESET  
DOOR HOLDER RELAY  
FAULT/ISOLATE  
When mapping to a normally energised relay, take care to ensure that connections take into account the  
normally energised state of the relay.  
Alternatively, the expansion relay(s) can be mapped to provide customised  
logic to suit specific installations:  
AND MAPPING  
AND MAPPING allows the relay output to be programmed for a combination of up to 5 zones, and only  
after they all go into alarm, will the relay operate.  
AND MAPPING is useful for applications which have special shutdowns, multiple risk Gas Facilities  
etc.  
OR MAPPING  
OR MAPPING works similarly. This function will cause the relay to operate if any one of up to five (5)  
zones go into alarm, the relay will operate.  
If the relay map options are set as "01" "02" "03" "00" "00", zones 1 or 2 or 3 in alarm will cause the  
relay to operate.  
OR MAPPING is useful for applications which have special shutdowns, zoned mimic outputs etc.  
FAULT MAPPING  
FAULT MAPPING works the same as OR mapping of alarm except it relates to the fault flag on each  
zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5)  
zones go into fault.  
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault, will  
cause the relay to operate.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 42  
IFS-2600 Installation & Programming Manual  
FAULT/ISOLATE MAPPING  
FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the  
fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if  
any one of up to five (5) zones go into fault/put in isolate.  
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault/(or  
are manually put in isolate) will cause the relay to operate.  
ISOLATE MAPPING  
ISOLATE MAPPING works the same as or mapping of alarm except it relates to the isolate flag on  
each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to  
five zones is put in isolate.  
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3, if put in isolate will  
cause the relay to operate.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 43  
APPENDIX F  
GLOSSARY OF TERMS  
AS-4428.1  
AS-4428.1  
AS-1670  
Australian standard for; -  
Automatic Fire Detection and Alarm Systems Control and Indicating Equipment.  
Australian standard for; -  
Automatic Fire Detection and Alarm Systems Power Supply Units.  
Australian standard for; -  
Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning.  
AS-1668.1  
Australian standard for; -  
SAA Mechanical Ventilation and Air Conditioning Fire Precautions in Buildings with Air-  
handling Systems.  
AZF  
MAF  
ACF  
AVF  
ISOL  
FLT  
ZONE  
DET  
LED  
LCD  
A/C  
AC  
Alarm Zone Facility (zone)  
Master Alarm Facility  
Ancillary Control Facility  
Alarm Verification Facility  
Isolate  
Fault  
Alarm Zone Facility  
Detector  
Light Emitting Diode  
Liquid Crystal Display  
Air Conditioning  
Alternating Current  
Direct Current  
Voltage  
DC  
V
A
Amps  
FIP  
N/L  
Fire Indicator Panel  
Non Latching  
TD  
Time Delay  
STD  
SBY  
BR1  
BR2  
NV  
Standard  
Standby  
Brigade Relay 1  
Brigade Relay 2  
AC Fail Relay  
Isolate  
IS  
GEN  
D/H  
RLY  
General Alarm Contacts  
Door Holder  
Relay  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 44  
IFS-2600 Installation & Programming Manual  
APPENDIX G  
SUMMARY OF TERMINATIONS AND CAUTIONS  
MCP LOOP  
Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by  
wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector.  
The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.  
DETECTION ZONES  
Refer to list of compatible actuation devices for detectors which may be used. Any other hard contact device  
may be used on these detection zones. An end of line resistor (E.O.L) of 4K7 ohms is required.  
RELAY OUTPUTS  
Relay outputs are voltage free change over contacts rated at 24VDC 1Amp (resistive). DO NOT attempt to  
switch 240VAC with these relay contacts.  
Note: Relay Contacts Shown At Terminals (NC, C, NO) Are For The Relay In a De-energised State.  
BELL OUTPUTS  
This output is fused at 1 Amp and can drive up to 10 NIFS bells as specified. Output is also monitored and if  
no bells are connected an EOL resistor (4K7 ohms) is required across the output terminals.  
ACF OUTPUTS  
This output is fused at 1 Amp. Output is also monitored and if no ancillary devices are connected, an EOL  
resistor (4K7 ohms) is required across the output terminals.  
WARNING SYSTEM  
Connection for warning systems such as Occupant Warning System or electronic sounders.  
DOOR HOLDER OUTPUTS  
When a door holder transformer is fitted to the panel, this output becomes functional. Output is rated at 3  
Amps maximum and can power up to 30 NIFS style door holders continuously. (Nom. 80mA each). Output is  
separately fused at 3A (FS-1). Jumper JP3 if fitted will disable this output, i.e. 24V DC output all the time. The  
Door Holder Output can be isolated using the ACF Isolate function.  
AUXILIARY POWER & MIMIC POWER  
A total auxiliary power draw of 500mA is available from the auxiliary power and mimic power terminals. This  
output is fused at 1 Amp (FS-3) and is battery backed.  
MAF ISOL & TRANSPONDER 0V  
A 0V signal is switched back from the transponder test switch and is used for indication purposes at the FIP.  
This will indicate as MAF ISOLATED and initiate a common fault. It can also used for an external device to  
indicate a fault.  
MIMIC DATA & CLOCK  
These outputs together with the mimic power terminals are used to serially communicate with the mimic  
panels when fitted. EOL resistor is not required on these lines.  
NOTE: Firmware must be Version 6 or above for mimic operation  
AC INPUT  
Mains step down transformer output (30VAC) is connected at these terminals. DO NOT connect 240VAC to  
these terminals.  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 45  
BATTERY  
The 24V batteries are connected at these terminals. Reverse polarity will cause serious and permanent  
damage to the equipment.  
DOOR HOLDER AC INPUT  
Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at  
this point. DO NOT connect 240VAC at this point.  
OUTPUT RELAYS  
STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below specified  
voltage.  
BRIGADE1  
BRIGADE2  
FAULT (N)  
AC-FAIL (N)  
ISOLATE  
Brigade 1, defaults as energising on any alarm zone, programmable.  
Brigade 2, defaults as energising on any alarm zone, programmable.  
Normally energised, drops out on any fault unless that function is isolated.  
Normally energised, drops out if the mains power is lost.  
Energised if any zone is isolated.  
GENERAL1  
GENERAL2  
Energised if any zone goes into alarm  
Energised if any zone goes into alarm  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 46  
IFS-2600 Installation & Programming Manual  
APPENDIX H  
IFS-2600 PROGRAMMED OPTIONS  
Global System Parameters  
Date:  
/
/
Latch ND  
Non-Latch ND Latch NE Non-Latch NE  
ACF Output  
Disabled 2 min  
3 min  
4 min  
5 min  
Alarm Verification  
(AVF)  
Notes:  
Programmed by  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 47  
ZONE TYPE PROGRAMMING  
Date:  
/
/
1
2
3
4
5
6
7
8
9
10  
AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D  
2S AVF 2S 20S 10S 20S 30S 40S 50S 60S  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 48  
IFS-2600 Installation & Programming Manual  
1
2
3
4
5
6
7
8
9
10  
AZF No. STD STD N/L N/L T/D T/D T/D T/D T/D T/D  
2S AVF 2S 20S 10S 20S 30S 40S 50S 60S  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 49  
ZONE OUTPUT PROGRAMMING  
Date:  
/
/
INDICATE  
I-  
IB-  
GENERAL  
IBG-  
ACF  
IBGA-  
BR1  
IBGA- BR2  
IBGA-  
BR1&BR2  
AZF No.  
BELL  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 50  
IFS-2600 Installation & Programming Manual  
INDICATE  
I-  
IB-  
GENERAL  
IBG-  
ACF  
IBGA-  
BR1  
IBGA-  
BR2  
IBGA-  
BR1&BR2  
AZF No.  
BELL  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 51  
RELAY OUTPUT MAPPING  
Date:  
/
/
MAPPING  
FLT  
RLY  
ISO  
ACF  
BR1  
BR2  
FLT  
MAINS  
FAIL  
GEN BELL  
D/H  
AND  
OR  
ISO  
ISO/  
FLT  
DO-  
OR  
RE-  
SET  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Place an "X" in the appropriate box  
= Default  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 52  
IFS-2600 Installation & Programming Manual  
MAPPING  
RLY  
ISO  
ACF  
BR1  
BR2  
FLT  
MAINS  
FAIL  
GEN BELL  
D/H  
AND  
OR  
FLT  
ISO  
ISO/  
FLT  
DO-  
OR  
RE-  
SET  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 53  
APPENDIX I  
TECHNICAL DRAWINGS  
MAIN KEYPAD AND DISPLAY  
EXPANSION DISPLAY  
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 54  
IFS-2600 Installation & Programming Manual  
Block Connection Diagram  
1
2
3
4
4 CORE CABLE  
TX, CTS, GND  
DB-9 FEMALE  
SERIAL PRINTER  
A
A
B
C
D
OUTPUTS  
PCB1125  
MAIN TERMINATION BOARD  
IFS PCB2005  
MAIN PROCESSOR BOARD  
CABLE C32  
ZONE  
IFS PCB2004  
BELL/ACF  
POWER  
SUPPLY  
BOARD  
ZONE DISPLAYS 1-8  
INPUTS  
1-8  
PCB2006  
MAX 120M  
LAPTOP  
3 CORE CABLE  
RX, TX, GND  
OUT  
IN  
RELAY  
BOARD  
IFS803  
CABLE C3  
CABLE C5  
CABLE C1  
P/N 130  
16 ZONE  
DISP  
ZONE  
EXP  
ZONE  
INPUTS  
9-16  
OUT  
4 CORE CABLE  
PCB816  
8 RELAY  
PCB804  
B
C
D
OUTPUTS  
1-8  
MIMIC PANEL  
CABLE C8  
ZONE  
EXP  
ZONE  
INPUTS  
32-40  
IFS 810 MIMIC DRV  
IFS 811B IND BRD  
CABLE C3  
MAINS SUPPLY  
240 V AC  
PCB804  
8 ZONE  
DISP  
IN  
OUT  
IFS 812 DISPLAY BRD  
(1 FOR EACH 8 ZONES)  
RELAY  
BOARD  
IFS803  
8 RELAY  
PCB816  
OUTPUTS  
9-16  
240V  
ISOL  
S/W  
CABLE C3  
240V/30V AC  
100 VA  
TRANSFORMER  
PANEL  
LAST DISPLAY CAN BE 8/16  
OTHERS MUST BE 16 ZONE  
POWER  
IN  
RELAY  
OUT  
8 RELAY  
OUTPUTS  
32-40  
2600/DHTX  
100 VA  
TRANSFORMER  
D/HOLDER  
POWER  
BOARD  
IFS803  
OPTION  
CABLE C9  
-
-
+
+
MAX 8 PCB803  
12V BATTERY  
12V BATTERY  
Title  
Size  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
IFS2600  
Drawn/  
Traced  
Engineer  
Design  
BLOCK CONNECTION DIAGRAM  
Notifier Inertia Fire Systems  
14/08/03  
I.P.  
C
O
D
C
B
Removed Part Numbers  
Revised Printer Connection  
REVISED PART NUMBERS  
IP  
IP  
IP  
IP  
21/12/05  
18/8/05  
Unauthorised use of this  
document in any way is  
prohibited.  
Approved  
Rev  
Drg.  
Drawing File No.  
G.W. G.W. 9/3/04  
This Drawing must not be used for Construction  
unless signed as approved  
L2600-1  
A4  
=DocumentFullPathAndName  
No.  
D
Revision - revise on CAD. Do not amend by hand Eng. App.  
Date  
No.  
1
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 55  
System Sensor Conventional Detector Connection Diagram  
1
2
3
4
DET A  
5
DET B  
5
DET B  
5
A
B
C
D
A
B
C
D
+
4
4
RIP  
RIP  
4
+R  
+D  
-D  
+R  
+D  
-D  
1
1
1
TO PANEL  
3
3
3
4K7  
EOL  
2
2
2
-
BASE B401  
BASE B401  
CONVENTIONAL DETECTOR CONNECTION DIAGRAM  
470R  
+R  
+D  
-D  
Current limited 10 mA  
+R  
Not current limited (3-24 V)  
Common Return  
+D  
-D  
REMOTE INDICATOR  
Title  
Size  
7 Columbia Court,  
Copyright  
SYSTEM SENSOR  
CONVENTIONAL DETECTOR  
CONNECTION DIAGRAM  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
Drawn/  
Traced  
Engineer  
Design  
I PERRY  
I PERRY  
C
O
I PERRY  
Approved  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
SS-DET  
A4  
=DocumentFullPathAndName  
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 56  
IFS-2600 Installation & Programming Manual  
Hochiki Conventional Detector Connection Diagram  
1
2
3
4
DET A  
DET B  
DET C  
3
3
3
A
B
C
D
RIP  
RIP  
A
B
C
D
+
-
2
2
2
4
4
4
+R  
+D  
-D  
+R  
+D  
4K7  
1
1
1
5
5
5
EOL  
-D  
TO PANEL  
7
6
7
6
7
6
CONNECTION FOR STANDARD DETECTORS AND BASES  
DET A  
DET B  
DET C  
+
RIP  
RIP  
BLUE  
C
+R  
+D  
-D  
+R  
+D  
4K7  
L
S
L
S
C
L
S
C
EOL  
-D  
RED WHITE  
TO PANEL  
-
CONNECTION FOR DFG-60BLKJ SEALED DETECTOR  
470R  
+R  
Current limited 10 mA  
+R  
+D  
Not current limited (3-24 V)  
+D  
-D  
Common Return  
-D  
REMOTE INDICATOR  
Title  
7 Columbia Court,  
Copyright  
HOCHIKI  
CONVENTIONAL DETECTOR  
CONNECTION DIAGRAM  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
remain the property of  
Engineer  
Design  
I PERRY  
I PERRY  
Notifier Inertia Fire Systems  
C
O
Unauthorised use of this  
document in any way is  
prohibited.  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
HOC-DET  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 57  
Ancillary Connection Diagram  
1
2
3
4
1
2
3
4
NOTE:  
2220  
PCB1125 may be omitted if the  
ancillary device is high  
impedance or contains an inbuilt  
reverse protection diode.  
+
-
+
-
SOUNDER  
LOAD  
IN  
1ST SOUNDER  
D2  
D1  
R1  
A
A
B
C
D
+
OUT  
In this case a 4K7 EOL must be  
fitted to the last device on the  
circuit.  
-
PCB1125C  
REMOVE RESISTOR R1  
EXCEPT ON LAST PCB  
IFS2600  
TERMINATION  
1
2
3
4
2220  
SOUNDER  
PCB2004  
N/C  
COM  
N/O  
+
-
+
LOAD  
IN  
-
LAST SOUNDER  
D2  
D1  
R1  
+
OUT  
+24  
0V  
-
PCB1125C  
+24  
0V  
1.5 OHM 5W  
R1 TO BE FITTED ON  
LAST PCB ONLY  
B
C
D
+24  
0V  
+
-
+
24VDC  
BELL  
LOAD  
IN  
-
+24  
0V  
D2  
D1  
R1  
FITTED WHEN  
STROBE USED  
+
OUT  
-
TP 0V  
PCB1125C  
MAF ISO  
REMOVE RESISTOR R1  
EXCEPT ON LAST PCB  
CLK  
DATA  
+
-
+
LOAD  
IN  
-
-
D2  
D1  
R1  
+
+
STROBE  
OUT  
-
PCB1125C  
R1 TO BE FITTED ON  
LAST PCB ONLY  
2600/DHTX  
DOOR HOLDER TRANSFORMER  
+
-
A
+
-
+
LOAD  
IN  
DOOR HOLDERS  
-
D2  
D1  
R1  
+
N
E
OUT  
-
RELAY  
240V/24V  
TRANSFORMER  
FAN  
PCB1125C  
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
IFS2600 TYPICAL  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
remain the property of  
Engineer  
Design  
23/8/05  
I PERRY  
ANCILLARY CONNECTION  
Notifier Inertia Fire Systems  
C
O
Unauthorised use of this  
document in any way is  
prohibited.  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
26-ANC-CON  
A4  
No.  
=DocumentFullPathAndName  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 58  
IFS-2600 Installation & Programming Manual  
ASE Connection Diagram  
1
2
3
4
A
B
C
D
A
B
C
D
N/C  
COM  
N/O  
N
N/C  
COM  
N/O  
ASE  
BR1  
N/C  
COM  
N/O  
AC FAIL  
FAULT  
ISOLATE  
N
N/C  
COM  
N/O  
N
IFS2600  
TERMINATION  
PCB2004  
N
N
ASE  
BRACKET  
N/C  
COM  
N/O  
CODE RED #10115  
ROMTEK 10117  
TYCO #10116  
N/C  
COM  
N/O  
POWER  
+24  
0V  
Title  
Size  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
2600  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
remain the property of  
Engineer  
Design  
22/8/05  
I.P.  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
ASE CONNECTION  
C
O
Approved  
Rev  
Drg.  
prohibited.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
26-ASE  
A4  
=DocumentFullPathAndName  
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 59  
Auto Changeover Dual Sounder Connection Diagram  
1
2
3
4
A
B
C
D
A
B
C
D
NOTE:  
NOTE:  
Maximum capacity is 10 sounders  
or 4 strobes  
INSTALL LINK JP1 FOR AUTO  
CHANGEOVER FROM ALERT TO EVAC  
MONITORED DRIVER BOARD  
IFS 993  
IFS2600  
TERMINATION  
PCB2004  
IFS958 RELAY BOARD  
ALERT STROBE  
(AMBER)  
EVAC STROBE  
(RED)  
N/O  
+24  
0V  
+24V  
RED  
0V  
BLACK  
+24V  
RED  
0V  
BLACK  
+24  
0V  
WARN SYS EOL  
4K7  
1K8  
EOL  
+24  
0V  
+24  
0V  
4
3
2
1
4
3
2
1
DUAL TONE AS2220  
SOUNDER  
DUAL TONE AS2220  
SOUNDER  
Title  
Size  
7 Columbia Court,  
Copyright  
IFS2600 MONITORED  
DUAL SOUNDER  
AUTO CHANGEOVER  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
remain the property of  
Engineer  
Design  
23/8/05  
I PERRY  
Notifier Inertia Fire Systems  
C
O
Unauthorised use of this  
document in any way is  
prohibited.  
G.W. G.W.23/1/04  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Rev  
Drg.  
Drawing File No.  
=DocumentFullPathAndName  
2600-DUAL  
B
No.  
ADDED RELAY  
Revision - revise on CAD. Do not amend by hand Eng. App.  
This Drawing must not be used for Construction  
unless signed as approved  
A4  
No. AUTO-SNDR  
A
Date  
1
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 60  
IFS-2600 Installation & Programming Manual  
Auto Change Over Dual Sounder Connection Diagram  
1
2
3
4
A
B
C
D
A
B
C
D
NOTE:  
NOTE:  
Maximum capacity is 10 sounders  
or 4 strobes  
REMOVE LINK JP1 FOR MANUAL  
CHANGEOVER FROM ALERT TO EVAC  
IFS2600  
TERMINATION  
PCB2004  
MONITORED DRIVER BOARD  
IFS 993  
N/O  
+24  
0V  
IFS958 RELAY BOARD  
ALERT ACTIVATION  
ALERT STROBE  
(AMBER)  
EVAC STROBE  
(RED)  
+24  
0V  
+24  
0V  
+24V  
RED  
0V  
BLACK  
+24V  
RED  
0V  
BLACK  
+24  
0V  
WARN SYS EOL  
4K7  
1K8  
EOL  
4
3
2
1
4
3
2
1
NC  
COM  
NO  
IFS803  
RELAY  
BOARD  
EVAC ACTIVATION  
DUAL TONE AS2220  
SOUNDER  
DUAL TONE AS2220  
SOUNDER  
Title  
Size  
7 Columbia Court,  
Copyright  
IFS2600 MONITORED  
DUAL SOUNDER  
MANUAL CHANGEOVER  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
remain the property of  
Engineer  
Design  
23/8/05  
I PERRY  
Notifier Inertia Fire Systems  
C
O
Unauthorised use of this  
document in any way is  
prohibited.  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Rev  
Drg.  
Drawing File No.  
=DocumentFullPathAndName  
2600-DUAL  
This Drawing must not be used for Construction  
unless signed as approved  
A4  
A
No.  
MANUAL-SNDR  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 61  
MIMIC Connection Diagram  
1
2
3
4
PCB812  
PCB812  
PCB812  
A
A
B
C
D
ZONES 1-8  
ZONES 9-16  
ZONES 17-24  
IFS2600  
PCB810  
TERMINATION  
BOARD  
FITTED WITH  
IFS2600 MIMIC  
DRIVER  
N/O  
+24  
B
C
D
0V  
+24  
0V  
33-40  
41-48  
49-56  
57-64  
1-8  
9-16  
17-24  
25-32  
+24  
0V  
+24  
0V  
TP 0V  
Max 120 Meters  
MAF ISO  
4/0.75mm cable  
CLK  
POWER AND SIGNAL RETURN  
SERIAL BUS  
MIMIC  
DATA  
-
MIM/EXT/26  
MIM/EXT/26  
+
FOR EXTRA ZONES  
MIM/26/KIT  
FOR 8 ZONES  
STANDARD SIZES 8, 24 AND 64 ZONES  
PCB811  
Title  
7 Columbia Court,  
Copyright  
Sheet: 1 Of: 1  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
Drawn/ 2/2/04  
G.W.  
remain the property of  
Engineer  
Design  
MIM/26/KIT  
Notifier Inertia Fire Systems  
C
O
Traced  
Unauthorised use of this  
document in any way is  
prohibited.  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
Email: [email protected] unless signed as approved  
26-MIM-CON  
4
A4  
=DocumentFullPathAndName  
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 62  
IFS-2600 Installation & Programming Manual  
Single Fan Connection Diagram  
1
2
3
4
FIRE PANEL  
FIELD WIRING  
A
A
B
C
D
FAN TERMINATION BOARD  
AUX POWER  
AUX +24  
+24  
+24  
START  
STOP  
RUN  
COMMON +VE  
CONTROL  
START  
STOP  
AUX 0V  
0V  
START1  
STOP1  
FAN START RELAY  
FAN RUNNING  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
B
FAN STOP RELAY  
PCB1128  
FAN 1  
C
RUN  
STOP  
FAULT  
* NOTE  
AUTO  
OFF  
ON  
THE MECHANICAL SERVICES BOARD  
MUST BE CONFIGURED TO HAVE  
THE STOP RELAY TO TAKE  
PRECEDENCE OVER THE START RELAY  
FRONT PANEL CONTROL  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
SINGLE FAN (GENERAL)  
CONTROL  
Drawn/  
Traced  
Engineer  
Design  
19/8/05  
I PERRY  
Notifier Inertia Fire Systems  
C
O
Unauthorised use of this  
document in any way is  
prohibited.  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
A4  
=DocumentFullPathAndName  
2600-DUAL FAN  
4
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 63  
Dual Fan Connection Diagram  
1
2
3
4
FIRE PANEL  
FIELD WIRING  
A
A
B
C
D
FAN TERMINATION BOARD  
AUX POWER  
AUX +24  
+24  
+24  
START  
STOP  
RUN  
COMMON +VE  
CONTROL  
START  
STOP  
AUX 0V  
0V  
START1  
STOP1  
START2  
STOP2  
FAN 1  
FAN 1 START RELAY  
FAN RUNNING  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
B
FAN 1 STOP RELAY  
+24  
COMMON +VE  
CONTROL  
START  
STOP  
RUN  
START  
STOP  
FAN 2 START RELAY  
FAN 2 STOP RELAY  
FAN 2  
FAN RUNNING  
PCB1102  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
FAN 1  
FAN 2  
C
RUN  
RUN  
STOP  
STOP  
FAULT  
FAULT  
* NOTE  
AUTO  
AUTO  
OFF  
ON  
OFF  
ON  
THE MECHANICAL SERVICES BOARD  
MUST BE CONFIGURED TO HAVE  
THE STOP RELAY TO TAKE  
*NOTE  
FOR SINGLE CONTROL  
REMOVE SW2  
FRONT PANEL CONTROL  
PRECEDENCE OVER THE START RELAY  
LINK SW1 A & B TO SW2 A, B  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
DUAL FAN (GENERAL)  
CONTROL  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
Drawn/  
Traced  
Engineer  
Design  
19/8/05  
I PERRY  
C
O
Approved  
Size  
Rev  
Drg.  
prohibited.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
A4  
=DocumentFullPathAndName  
2600-DUAL FAN  
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 64  
IFS-2600 Installation & Programming Manual  
Exhaust Fan Connection Diagram  
1
2
3
4
FIRE PANEL  
FIELD WIRING  
FAN TERMINATION BOARD  
A
A
B
C
D
AUX POWER  
AUX +24  
AUX 0V  
+24  
+24  
START  
STOP  
RUN  
COMMON +VE  
CONTROL  
START  
STOP  
0V  
START1  
STOP1  
FAN STOP RELAY  
(MAPPED TO ACF FOR  
GENERAL OR ZONED)  
FAN RUNNING  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
B
PCB1128  
* NOTE  
EITHER THE MAPPING ABOVE MAY  
BE USED TO STOP THE EXHAUST FAN  
OR THE GENERAL ACF TRIP BELOW,  
BUT NOT BOTH.  
* NOTE  
FAN 1  
THE MECHANICAL SERVICES BOARD  
MUST BE CONFIGURED TO HAVE  
THE STOP RELAY TO TAKE  
PRECEDENCE OVER THE START RELAY  
RUN  
USE OF THE FIRE TRIP RELAY BELOW  
REQUIRES THAT THE MSSB  
STOP  
STOPS THE FAN.  
FAULT  
C
AUTO  
OFF  
ON  
FRONT PANEL CONTROL  
FROM FIP  
+24  
+
-
+
-
ACF  
LOAD  
IN  
0v  
+
D1  
R1  
OUT  
FIRE TRIP  
RELAY  
-
PCB1125  
D
Title  
Size  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
EXHAUST FAN (TYPICAL)  
CONTROL  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Drawn/  
Traced  
Engineer  
19/8/05  
I PERRY  
Design  
C
O
Approved  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-EXH  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 65  
Supply Fan Connection Diagram  
1
2
3
4
FIRE PANEL  
FIELD WIRING  
FAN TERMINATION BOARD  
A
A
B
C
D
AUX POWER  
AUX +24  
AUX 0V  
+24  
+24  
START  
STOP  
RUN  
COMMON +VE  
CONTROL  
START  
STOP  
0V  
START1  
STOP1  
FAN START RELAY  
(MAPPED TO ACF FOR  
GENERAL OR ZONED)  
FAN RUNNING  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
FAN STOP RELAY  
(MAPPED TO AIR INTAKE  
SMOKE DETECTOR)  
B
PCB1128  
* NOTE  
EITHER THE MAPPING ABOVE MAY  
BE USED TO START THE SAF  
OR THE GENERAL ACF TRIP BELOW,  
BUT NOT BOTH.  
* NOTE  
FAN 1  
THE MECHANICAL SERVICES BOARD  
MUST BE CONFIGURED TO HAVE  
THE STOP RELAY TO TAKE  
RUN  
USE OF THE FIRE TRIP RELAY BELOW  
REQUIRES THAT THE MSSB  
PRECEDENCE OVER THE START RELAY  
STOP  
STARTS THE FAN.  
FAULT  
C
AUTO  
OFF  
ON  
FRONT PANEL CONTROL  
FROM FIP  
+24  
+
-
+
-
ACF  
LOAD  
IN  
0v  
+
D1  
R1  
OUT  
FIRE TRIP  
RELAY  
-
PCB1125  
D
Title  
Size  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
SUPPLY AIR FAN (TYPICAL)  
CONTROL  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Drawn/  
Traced  
Engineer  
19/8/05  
I PERRY  
Design  
C
O
Approved  
This Drawing must not be used for Construction  
Rev  
Drg.  
Drawing File No.  
2600-SAF  
A4  
=DocumentFullPathAndName  
A
No.  
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
Email: [email protected] unless signed as approved  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 66  
IFS-2600 Installation & Programming Manual  
Smoke Spill Fan Connection Diagram  
1
2
3
4
FIRE PANEL  
FIELD WIRING  
FAN TERMINATION BOARD  
A
B
C
D
A
B
C
D
AUX POWER  
AUX +24  
+24  
+24  
START  
STOP  
RUN  
COMMON +VE  
CONTROL  
START  
STOP  
AUX 0V  
0V  
START1  
STOP1  
FAN START RELAY  
(MAPPED TO ACF FOR  
GENERAL OR ZONED)  
FAN RUNNING  
STOP  
FLT  
INDICATION  
FAN STOPPED AND POWER AVAILABLE  
FAN FAULT OR NO POWER AVAILABLE  
* NOTE  
EITHER THE MAPPING ABOVE MAY  
BE USED TO START THE SSF  
OR THE GENERAL ACF TRIP BELOW,  
BUT NOT BOTH.  
PCB1128  
USE OF THE FIRE TRIP RELAY BELOW  
REQUIRES THAT THE MSSB  
STARTS THE FAN.  
* NOTE  
FAN 1  
THE MECHANICAL SERVICES BOARD  
MUST BE CONFIGURED TO HAVE  
THE STOP RELAY TO TAKE  
PRECEDENCE OVER THE START RELAY  
RUN  
STOP  
FAULT  
AUTO  
OFF  
ON  
FRONT PANEL CONTROL  
FROM FIP  
+24  
+
-
+
-
ACF  
LOAD  
IN  
0v  
+
D1  
R1  
OUT  
FIRE TRIP  
RELAY  
-
PCB1125  
Title  
Size  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
SMOKE SPILL FAN (TYPICAL)  
CONTROL  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Drawn/  
Traced  
Engineer  
19/8/05  
I PERRY  
Design  
C
O
Approved  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-SSF  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 67  
10W EVAC Connection Diagram  
1
2
3
4
10W EVAC  
PCB 908  
FRONT  
PANEL  
EVAC  
CONTROL  
A
A
B
C
D
+24  
IFS2600  
0V  
TERMINATION  
BOARD  
+24  
0V  
B
4K7 5%  
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
AND ISOLATION CAPACITORS  
LINK JP1  
WHITE  
RED  
BLACK/SHIELD  
BLUE  
MICROPHONE  
WITH PTT  
SHIELDED  
NOTE:  
C
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
THE MICROPHONE AND BGM  
MUST ONLY BE CONNECTED TO  
THE MASTER AMPLIFIER.  
SHIELDED  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
BGM INPUT  
1V P-P  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
IFS-2600  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
Drawn/  
Traced  
Engineer  
Design  
I PERRY  
I PERRY  
10 WATT  
C
O
CONNECTION DIAGRAM  
I PERRY  
Approved  
Size  
Rev  
Drg.  
prohibited.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-10W  
A4  
No.  
=DocumentFullPathAndName  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 68  
IFS-2600 Installation & Programming Manual  
10W EVAC Slave Connection Diagram  
1
2
3
4
10W EVAC  
PCB 908  
FRONT  
PANEL  
EVAC  
CONTROL  
A
A
B
C
D
+24  
IFS2600  
0V  
TERMINATION  
BOARD  
+24  
0V  
B
4K7 5%  
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
AND ISOLATION CAPACITORS  
LINK JP1  
CONNECT TO  
FAULT OUT  
FROM SLAVE  
WHITE  
RED  
BLACK/SHIELD  
BLUE  
MICROPHONE  
WITH PTT  
SHIELDED  
NOTE:  
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
THE MICROPHONE AND BGM  
MUST ONLY BE CONNECTED TO  
THE MASTER AMPLIFIER.  
C
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
CONNECT FAULT OUTPUTS  
TOGETHER AND MOVE THE  
LAST WRE ON I/O PCB TO THE  
FAULT TERMINAL ON THE  
MASTER AMPLIFIER.  
SHIELDED  
BGM INPUT  
1V P-P  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
IFS-2600  
10 WATT SLAVE  
CONNECTION DIAGRAM  
Drawn/  
Traced  
Engineer  
Design  
I PERRY  
I PERRY  
C
O
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
Email: [email protected] unless signed as approved  
2600-10W SLAVE  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 69  
30W EVAC Connection Diagram  
1
2
3
4
30W EVAC  
PCB 908  
FRONT  
PANEL  
EVAC  
CONTROL  
A
A
B
C
D
IFS2600  
TERMINATION  
BOARD  
+24  
0V  
+24  
0V  
B
4K7 5%  
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
AND ISOLATION CAPACITORS  
LINK JP1  
WHITE  
RED  
BLACK/SHIELD  
BLUE  
MICROPHONE  
WITH PTT  
SHIELDED  
NOTE:  
C
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
A
AC1  
AC2  
+24V  
0V  
IFS1100  
POWER SUPPLY  
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
THE MICROPHONE AND BGM  
MUST ONLY BE CONNECTED TO  
THE MASTER AMPLIFIER.  
N
E
SHIELDED  
240V/20V  
TRANSFORMER  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
BGM INPUT  
1V P-P  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
IFS-2600  
Drawn/  
Traced  
Engineer  
Design  
25/8/05  
I PERRY  
30 WATT  
C
O
CONNECTION DIAGRAM  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
I PERRY  
Approved  
Size  
Rev  
Drg.  
prohibited.  
Drawing File No.  
This Drawing must not be used for Construction  
Email: [email protected] unless signed as approved  
2600-30W  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 70  
IFS-2600 Installation & Programming Manual  
30W EVAC Slave Connection Diagram  
1
2
3
4
30W EVAC  
PCB 908  
FRONT  
PANEL  
EVAC  
CONTROL  
A
A
B
C
D
IFS2600  
TERMINATION  
BOARD  
+24  
0V  
+24  
0V  
B
4K7 5%  
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
LINK JP1  
CONNECT TO  
FAULT OUT  
FROM SLAVE  
AND ISOLATION CAPACITORS  
WHITE  
RED  
NOTE:  
BLACK/SHIELD  
BLUE  
MICROPHONE  
WITH PTT  
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
THE MICROPHONE AND BGM  
MUST ONLY BE CONNECTED TO  
THE MASTER AMPLIFIER.  
SHIELDED  
C
CONNECT FAULT OUTPUTS  
TOGETHER AND MOVE THE  
LAST WRE ON I/O PCB TO THE  
FAULT TERMINAL ON THE  
MASTER AMPLIFIER.  
A
AC1  
AC2  
+24V  
0V  
IFS1100  
POWER SUPPLY  
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
N
E
SHIELDED  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
240V/20V  
TRANSFORMER  
BGM INPUT  
1V P-P  
D
Title  
7 Columbia Court,  
Copyright  
1
1
Sheet:  
Of:  
This document is & shall  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Norwest Business Park  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
IFS-2600  
Drawn/  
Traced  
Engineer  
Design  
25/8/05  
I PERRY  
30 WATT SLAVE  
C
O
CONNECTION DIAGRAM  
I PERRY  
Approved  
Size  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-30W-SLAVE  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IFS-2600 Installation & Programming Manual  
Page 71  
50W EVAC Connection Diagram  
1
2
3
4
0
60  
30  
20  
10  
0
AUDIO TRANSFORMER  
2
4
6
8
A
A
B
C
D
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
AND ISOLATION CAPACITORS  
AMP  
50W EVAC  
PCB 905E  
GND  
LINE +  
LINE -  
LINE +  
LINE -  
+24  
IFS2600  
TERMINATION  
0V  
BOARD  
NOTE:  
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
THE MICROPHONE AND BGM  
MUST ONLY BE CONNECTED TO  
THE MASTER AMPLIFIER.  
+24  
0V  
B
LINK JP1  
CONNECT JP3 MASTER TO JP4  
SLAVE FOR FAN CONTROL  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
FRONT  
PANEL  
EVAC  
CONTROL  
4K7 5%  
C
WHITE  
RED  
+24V  
BAT CHG  
0V  
BLACK/SHIELD  
BLUE  
MAINS_ON  
MF_N/C  
MICROPHONE  
WITH PTT  
SHIELDED  
240V/30V  
N
N
MF_N/O  
MF_COM  
LOW_N/C  
LOW_N/O  
A
N
E
LOW_COM  
TRANSFORMER  
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
SHIELDED  
BGM INPUT  
1V P-P  
D
Title  
Size  
7 Columbia Court,  
Norwest Business Park  
Copyright  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
IFS-2600  
remain the property of  
Notifier Inertia Fire Systems  
Unauthorised use of this  
document in any way is  
prohibited.  
Engineer  
Design  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
25/8/05  
I PERRY  
50 WATT  
C
O
CONNECTION DIAGRAM  
I PERRY  
Approved  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-50W  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 72  
IFS-2600 Installation & Programming Manual  
50W EVAC Slave Connection Diagram  
1
2
3
4
0
60  
30  
20  
10  
0
AUDIO TRANSFORMER  
2
4
6
8
A
B
C
D
A
B
C
D
EOL  
47K 5%  
SPEAKERS WITH  
100V LINE TRANSFORMERS  
AND ISOLATION CAPACITORS  
AMP  
50W EVAC  
PCB 905E  
GND  
LINE +  
LINE -  
LINE +  
LINE -  
+24  
0V  
IFS2600  
NOTE:  
TERMINATION  
BOARD  
TO SLAVE TWO AMPLIFIERS  
TOGETHER, REMOVE THE IFS903  
BOARD FROM THE SLAVE  
AMPLIFIER AND CONNECT JP1  
ON THE MASTER TO JP2 ON THE  
SLAVE.  
THE MICROPHONE AND BGM  
SHOULD ONLY BE CONNECTED  
TO THE MASTER AMPLIFIER.  
+24  
0V  
CONNECT JP3 MASTER TO JP4  
SLAVE FOR FAN CONTROL  
CONNECT FAULT OUTPUTS  
TOGETHER AND MOVE THE  
LAST WRE ON I/O PCB TO THE  
FAULT TERMINAL ON THE  
MASTER AMPLIFIER.  
LINK JP1  
FRONT  
PANEL  
EVAC  
CONNECT PIN 4, P12 ON MASTER  
TO PIN4 P12 ON SLAVE.  
CONTROL  
4K7 5%  
WHITE  
RED  
+24V  
0V  
BAT CHG  
CONNECT TO  
FAULT OUT  
FROM SLAVE  
BLACK/SHIELD  
BLUE  
MAINS_ON  
MF_N/C  
MICROPHONE  
WITH PTT  
SHIELDED  
240V/30V  
N
N
MF_N/O  
A
MF_COM  
LOW_N/C  
LOW_N/O  
N
E
LOW_COM  
TRANSFORMER  
BGM ENABLE  
( ENABLED ON  
CLOSURE )  
SHIELDED  
BGM INPUT  
1V P-P  
Title  
Size  
7 Columbia Court,  
Norwest Business Park  
Copyright  
1
1
Sheet:  
Drawn/  
Traced  
Of:  
This document is & shall  
remain the property of  
IFS-2600  
Engineer  
Design  
Baulkham Hills NSW 2153  
AUSTRALIA  
Tel 61 2 9894 1444  
Fax 61 2 9899 4156  
25/8/05  
I PERRY  
50 WATT SLAVE  
Notifier Inertia Fire Systems  
C
O
CONNECTION DIAGRAM  
Unauthorised use of this  
document in any way is  
prohibited.  
I PERRY  
Approved  
Rev  
Drg.  
Drawing File No.  
This Drawing must not be used for Construction  
unless signed as approved  
2600-50W-SLAVE  
A4  
=DocumentFullPathAndName  
No.  
A
Revision - revise on CAD. Do not amend by hand Eng. App.  
1
Date  
No.  
2
3
4
P/N 10069 ECN08-0066  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
New South Wales  
(Head Office)  
7 Columbia Court  
Baulkham Hills NSW 2153  
Queensland  
24 Potts Street  
East Brisbane, QLD 4169  
Victoria  
32 Lambert Street  
Richmond, VIC 3121  
ph +61 (0)7 3391 5777  
fax +61 (0)7 3391 5800  
ph +61 (0)3 9421 5552  
fax +61 (0)3 9421 5553  
ph +61 (02 9899-4155  
fax +61 (0)2 9899-4156  
Western Australia  
New Zealand  
Unit 4, 283 Camboon Road  
Malaga WA 6090  
264 Mt Eden Road  
Auckland  
ph +61 (0)8 9270 6555  
fax +61 (0)8 9270 6556  
ph +64 (0)9 623 5275  
fax +64 (0)9 623 5060  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Car Seat PD205009A User Manual
Graco Crib ISPP008AA User Manual
Graco Inc Automobile Parts 308287 User Manual
Greenheck Fan Ventilation Hood SSWDR 53 User Manual
Grindmaster Beverage Dispenser 3341 User Manual
Grizzly Automobile Parts H6287 H6289 User Manual
Hans Grohe Indoor Furnishings 31020XX1 User Manual
Hearth and Home Technologies Outdoor Fireplace CASTLEWOOD 42 User Manual
HP Hewlett Packard Printer 2000CP 2500 User Manual
IBM Laptop T400S User Manual