		 Mounting in FACP Main Board Chassis   
					ANN-RLY Relay Module   
					Installation Instructions   
					ANN-RLY module standoffs   
					The ANN-RLY relay module provides 10 program-   
					mable Form-C relays when used with a compatible   
					FACP (Fire Alarm Control Panel). This document   
					is provided as a quick reference. For more detailed   
					information, refer to the appropriate FACP installa-   
					tion manual.   
					R1 R3 R5 (top)   
					R1 R3 R5   
					R7 R9   
					R7 R9   
					ground   
					wire   
					R2 R4 R6 (bottom) R8 R10   
					Note: Installation and wiring of this device must be   
					done in accordance with NFPA 72 and local   
					ordinances.   
					ANN-RLY module mounting hooks   
					1. Install the two supplied snap-in standoffs into the   
					backside of theANN-RLY circuit board in   
					locations indicated in illustration above.   
					Specifications   
					2. Using supplied hardware, attach the ground wire   
					using a screw and nut to location indicated in   
					illustration above. Be sure to position the ground   
					wire as shown to facilitateANN-RLYinstallation.   
					3. Position theANN-RLY module in the chassis so   
					that the two standoffs in the module are posi-   
					tioned over the wider portion of the mounting   
					holes in the chassis and the mounting hooks on   
					the module are sticking through the module   
					mounting slots in the bottom of the chassis.   
					4. Slide theANN-RLY module to the right to lock   
					the module into place.   
					Table 1: ANN-RLY Module Specifications   
					Operating Voltage   
					24 VDC   
					75 mA   
					15 mA   
					Max. Current @ Alarm   
					24 VDC   
					Standby   
					0o to 49o C   
					(32o to 120o F)   
					Operating Temperature   
					Max. Wiring Distance from   
					FACP (with 12 AWG wire)   
					1,250 ft.   
					(380 m)   
					Relay Contact Ratings   
					2 amps @ 30 VDC   
					(resistive)   
					5. Attach the ground wire installed in step 2 to the   
					chassis in the location indicated below.   
					0.5 amps @ 30 VAC   
					(resistive)   
					chassis   
					Indoor Use in Dry Location Only   
					Mounting   
					TheANN-RLY module may be mounted inside the   
					FACP main circuit board chassis or in the battery   
					area of the enclosure using mounting bracket P/N:   
					ANN-MBRLY. Refer to the following illustrations   
					for installation information.   
					ANN-RLY module   
					mounting holes   
					ANN-RLY module   
					ground   
					wire   
					mounting slots   
					Note:   
					1. ANN-RLY module can be installed without   
					removing the main circuit board or chassis.   
					2. ANN-MBRLY mounting bracket must be used   
					for the MS-9200UDLS.   
					1 
					ANN-RLY Module   
					Document # 53033 Rev. B 10/10/07   
					ECN 07-744   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Wiring ANN-RLY Module to FACP Setting DIP Switches   
					Refer to Table 2 and Figure 3 for wiring   
					connections.   
					Each ANN-BUS device requires a unique address.   
					ANN-RLY relay module DIP switch SW1 is used   
					to set the address for the annunciator.   
					ANN-RLY Terminals (TB1) FACP ANN-BUS Terminals   
					A maximum of 8 devices can be connected to the   
					FACPANN-BUS communication circuit. ANN-   
					BUS device addresses do not need to be sequential   
					and can be set to any number between 01 and 08.   
					Note that 00 is not a valid address. The following   
					illustrates the DIP switch settings for each address   
					(ID Number):   
					Terminal 4 (-)   
					Terminal 3 (+)   
					Terminal 2 (A)   
					Terminal 1 (B)   
					(-)   
					(+)   
					A (ANN-BUS)   
					B (ANN-BUS)   
					Table 2: Wiring ANN-RLY Module to FACP   
					ID Number   
					(Address)   
					DIP Switch SW1   
					C 
					NC   
					NO   
					(not valid) 00   
					C 
					NC   
					NO   
					01   
					02   
					03   
					04   
					05   
					06   
					07   
					08   
					ANN-RLY Relay Module   
					Figure 3: Wiring ANN-RLY Module to an FACP   
					Notes:   
					1. All connections/sources are to be power-limited   
					and supervised.   
					2. 12 - 18 AWG (0.75 - 3.25 mm2) wire for 24   
					VDC circuit is acceptable. Refer to the   
					appropriate FACP manual.   
					3. Power wire distance limitation is set by 1.2 volt   
					maximum line drop from source to end of   
					circuit.   
					4. Maximum distance from FACP to last ANN-   
					BUS device must not exceed 1,250 feet   
					(380 m). Refer to Wiring Distance Table in   
					appropriate FACP manual for wire gauge and   
					distance limitations.   
					5. Common, Normally Closed and Normally Open   
					terminals for each relay follow the same   
					pattern as illustrated above.   
					One Fire-Lite Place   
					Northford, CT 06472   
					USA TEL: (203) 484-7161   
					
					© 2006 Fire-Lite Alarms P/N: 53033   
					3 
					ANN-RLY Module   
					Document # 53033 Rev. B 10/10/07   
					ECN 07-744   