Honeywell Clock Radio MRP 2001 User Manual

PN: 53040:A  
ECN 07-072  
Deluge • Preaction Control  
MRP-2001 & MRP-2001E  
Installation, Operation and Programming Manual  
Document  
4/16/07  
#53040  
A
Revision:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adherence to the following will aid in problem-free  
installation with long-term reliability:  
Installation Precautions  
WARNING - Several different sources of power can be  
connected to the fire alarm control panel. Disconnect all  
sources of power before servicing. Control unit and asso-  
ciated equipment may be damaged by removing and/or  
inserting cards, modules, or interconnecting cables while  
the unit is energized. Do not attempt to install, service, or  
operate this unit until this manual is read and understood.  
Like all solid state electronic devices, this system may  
operate erratically or can be damaged when subjected to  
lightning-induced transients. Although no system is  
completely immune from lightning transients and  
interferences, proper grounding will reduce susceptibility.  
Overhead or outside aerial wiring is not recommended, due  
to an increased susceptibility to nearby lightning strikes.  
Consult with the Technical Services Department if any  
problems are anticipated or encountered.  
CAUTION - System Reacceptance Test after Software  
Changes. To ensure proper system operation, this product  
must be tested in accordance with NFPA 72 after any  
Disconnect AC power and batteries prior to removing or  
programming operation or change in site-specific software. inserting circuit boards. Failure to do so can damage  
Reacceptance testing is required after any change,  
addition or deletion of system components, or after any  
modification, repair or adjustment to system hardware or  
wiring.  
circuits.  
Remove all electronic assemblies prior to any drilling,  
filing, reaming, or punching of the enclosure. When  
possible, make all cable entries from the sides or rear.  
Before making modifications, verify that they will not  
interfere with battery, transformer, and printed circuit board  
location.  
All components, circuits, system operations, or software  
functions known to be affected by a change must be 100%  
tested. In addition, to ensure that other operations are not  
inadvertently affected, at least 10% of initiating devices that  
are not directly affected by the change, up to a maximum of  
50 devices, must also be tested and proper system  
operation verified.  
Do not tighten screw terminals more than 9 in-lbs.  
Over-tightening may damage threads, resulting in reduced  
terminal contact pressure and difficulty with screw terminal  
removal.  
This system meets NFPA requirements for indoor dry  
operation at 0-49° C/32-120° F and at a relative humidity of  
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.  
However, the useful life of the system's standby batteries  
and the electronic components may be adversely affected  
by extreme temperature ranges and humidity. Therefore, it  
is recommended that this system and all peripherals be  
installed in an environment with a nominal room tempera-  
ture of 15-27° C/60-80° F.  
This system contains static-sensitive components.  
Always ground yourself with a proper wrist strap before  
handling any circuits so that static charges are removed  
from the body. Use static-suppressive packaging to  
protect electronic assemblies removed from the unit.  
Follow the instructions in the installation, operating, and  
programming manuals. These instructions must be  
followed to avoid damage to the control panel and  
associated equipment. FACP operation and reliability  
depend upon proper installation by authorized personnel.  
Verify that wire sizes are adequate for all initiating and  
indicating device loops. Refer to manual Specifications  
section for maximum allowable I.R. drop from the specified  
device voltage.  
FCC Warning  
WARNING: This equipment generates, uses, and can  
radiate radio frequency energy and if not installed and  
used in accordance with the instruction manual, may  
cause interference to radio communications. It has  
been tested and found to comply with the limits for class  
A computing device pursuant to Subpart B of Part 15 of  
FCC Rules, which is designed to provide reasonable  
protection against such interference when operated in a  
commercial environment. Operation of this equipment  
in a residential area is likely to cause interference, in  
which case the user will be required to correct the  
interference at their own expense.  
Canadian Requirements  
This digital apparatus does not exceed the Class A  
limits for radiation noise emissions from digital  
apparatus set out in the Radio Interference Regulations  
of the Canadian Department of Communications.  
Le present appareil numerique n'emet pas de bruits  
radioelectriques depassant les limites applicables aux  
appareils numeriques de la classe A prescrites dans le  
Reglement sur le brouillage radioelectrique edicte par  
le ministere des Communications du Canada.  
PrecauLarge.PMD  
02/26/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Table of Contents  
SECTION 1: Product Description .........................................................................................................................11  
1.1: Product Features ..........................................................................................................................................11  
1.2: Specifications ..............................................................................................................................................13  
1.3: Controls and Indicators................................................................................................................................14  
1.4: Components.................................................................................................................................................15  
1.5: Optional Modules and Accessories .............................................................................................................16  
SECTION 2: Installation ........................................................................................................................................17  
2.1: Backbox Mounting ......................................................................................................................................17  
2.2: Operating Power..........................................................................................................................................20  
2.3: Input Circuits...............................................................................................................................................21  
2.4: Output Circuits ............................................................................................................................................23  
2.4.1: Outputs/Notification Appliance/Releasing Circuits..........................................................................23  
2.4.2: Special Application DC Power Output Connections ........................................................................24  
2.4.3: Relays - Programmable .....................................................................................................................24  
2.5: Power-limited Wiring Requirements...........................................................................................................25  
2.6: Installation of Optional Modules.................................................................................................................26  
2.6.1: CAC-5X Class A Converter Module ................................................................................................26  
2.6.1.1 Installation ...............................................................................................................................26  
2.6.1.2 Wiring NACs and IDCs for Class A .......................................................................................27  
2.6.2: 4XTMF Municipal Box Transmitter Option Module........................................................................28  
2.6.2.1 4XTMF Transmitter Module Installation ...............................................................................29  
2.7: ANN-BUS Devices .....................................................................................................................................30  
2.7.1: ANN-BUS Wiring.............................................................................................................................30  
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................30  
2.7.1.2 Wiring Configuration ..............................................................................................................32  
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................33  
2.7.2: ANN-BUS Device Addressing..........................................................................................................33  
2.7.3: ANN-80 Remote LCD Annunciator .................................................................................................34  
2.7.4: Specifications ....................................................................................................................................34  
2.7.5: Installation.........................................................................................................................................34  
2.7.5.1 Mounting .................................................................................................................................34  
2.7.5.2 Opening/Closing Annunciator ................................................................................................34  
2.7.5.3 Wiring ANN-80 to FACP .......................................................................................................35  
2.7.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................37  
2.7.6.1 Specifications ..........................................................................................................................37  
2.7.6.2 PRN-6 Printer Installation .......................................................................................................37  
2.7.6.2.1 Connecting PRN-6 Printer ...................................................................................................38  
2.7.6.2.2 Setting Printer Options .........................................................................................................38  
2.7.7: ANN-I/O LED Driver Module..........................................................................................................39  
2.7.7.1 ANN-I/O Board Layout ..........................................................................................................39  
2.7.7.2 Specifications ..........................................................................................................................39  
2.7.7.3 ANN-I/O Connection to FACP ...............................................................................................40  
2.7.7.4 ANN-I/O Module LED Wiring ...............................................................................................41  
2.7.8: ANN-LED Annunciator Module.......................................................................................................41  
2.7.8.1 ANN-LED Board Layout ........................................................................................................42  
2.7.8.2 Specifications ..........................................................................................................................42  
2.7.8.3 Mounting/Installation ..............................................................................................................42  
2.7.8.4 ANN-LED Connection to FACP ............................................................................................43  
2.7.9: ANN-RLY Relay Module..................................................................................................................44  
2.7.9.1 ANN-RLY Board Layout ........................................................................................................44  
2.7.9.2 Specifications ..........................................................................................................................44  
2.7.9.3 Mounting/Installation ..............................................................................................................44  
2.7.9.4 ANN-RLY Connection to FACP ............................................................................................45  
SECTION 3: Programming ..................................................................................................................................46  
3.1: User Programming.......................................................................................................................................46  
4
MRP-2001 & MRP-2001E P/N: 53040:A 4/16/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
3.2: Initial Power-up...........................................................................................................................................47  
3.3: Programming Screens Description..............................................................................................................47  
3.4: Programming and Passwords ......................................................................................................................48  
3.5: Master Programming Level.........................................................................................................................49  
3.5.1: FACP CONFIG (Application Templates) .........................................................................................50  
3.5.2: Input Zones........................................................................................................................................50  
3.5.3: Output Circuits..................................................................................................................................57  
3.5.3.1 Enabled ....................................................................................................................................58  
3.5.3.2 Type ........................................................................................................................................58  
3.5.3.2.1 Release Circuit 1 or Release Circuit 2 .................................................................................58  
3.5.3.2.2 Release Stage NAC ..............................................................................................................59  
3.5.3.3 Silence .....................................................................................................................................59  
3.5.3.4 Auto Silence ............................................................................................................................60  
3.5.3.5 Silence Inhibited .....................................................................................................................60  
3.5.3.6 Coding .....................................................................................................................................61  
3.5.3.6.1 Synchronized NAC Operation .............................................................................................62  
3.5.4: Cross Input Zones .............................................................................................................................63  
3.5.5: On-Board Relays...............................................................................................................................64  
3.5.6: System Setup.....................................................................................................................................64  
3.5.6.1 Timers ....................................................................................................................................65  
3.5.6.1.1 Soak 1 or Soak 2 ..................................................................................................................66  
3.5.6.1.2 Waterflow Delay ..................................................................................................................66  
3.5.6.1.3 AC Loss Delay .....................................................................................................................67  
3.5.6.2 Banner .....................................................................................................................................67  
3.5.6.3 Time-Date ...............................................................................................................................68  
3.5.6.3.1 Time .....................................................................................................................................69  
3.5.6.3.2 Date ......................................................................................................................................69  
3.5.6.3.3 Clock Format ........................................................................................................................69  
3.5.6.3.4 Daylight Savings Time .........................................................................................................70  
3.5.6.4 Trouble Reminder ...................................................................................................................70  
3.5.6.5 Charger Disable .......................................................................................................................70  
3.5.7: ANN-BUS.........................................................................................................................................71  
3.5.7.1 ANN-BUS Enabled .................................................................................................................71  
3.5.7.2 ANN-BUS Modules ................................................................................................................72  
3.5.7.3 Auto-Configure .......................................................................................................................73  
3.5.7.4 ANN-S/PG Options .................................................................................................................73  
3.5.7.5 ANN-I/O LED Zone Assignments ..........................................................................................75  
3.5.7.6 ANN-80 Options .....................................................................................................................76  
3.5.7.7 ANN-RLY Options .................................................................................................................77  
3.5.8: History...............................................................................................................................................78  
3.5.8.1 View Events ............................................................................................................................78  
3.5.8.2 Erase History ...........................................................................................................................78  
3.5.9: Walktest.............................................................................................................................................79  
3.5.10: Clear Program .................................................................................................................................80  
3.5.11: Password Change ............................................................................................................................80  
3.6: Maintenance Programming Level ...............................................................................................................81  
3.6.1: Input Zones - Enable/Disable............................................................................................................82  
3.6.2: History...............................................................................................................................................82  
3.6.3: Walktest.............................................................................................................................................83  
3.6.4: Time-Date..........................................................................................................................................84  
SECTION 4: Operating Instructions ....................................................................................................................85  
4.1: Panel Control Buttons .................................................................................................................................85  
4.1.1: Acknowledge/Step ............................................................................................................................85  
4.1.2: Alarm Silenced..................................................................................................................................85  
4.1.3: Drill/Hold 2 Sec ................................................................................................................................85  
MRP-2001 & MRP-2001E P/N: 53040:A 4/16/07  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
4.1.4: Reset..................................................................................................................................................85  
4.2: Indicators .....................................................................................................................................................86  
4.3: Normal Operation........................................................................................................................................86  
4.4: Trouble Operation........................................................................................................................................87  
4.5: Alarm Operation..........................................................................................................................................88  
4.6: Supervisory Operation.................................................................................................................................89  
4.7: Disable/Enable Operation............................................................................................................................89  
4.8: Waterflow Circuits Operation......................................................................................................................89  
4.9: 2nd-Shot Water Switch................................................................................................................................90  
4.10: Detector Functions.....................................................................................................................................90  
4.11: Time Functions: Real-Time Clock.............................................................................................................90  
4.12: Coded NAC Operation ..............................................................................................................................90  
4.13: Release Stages ...........................................................................................................................................91  
4.14: Special System Timers ..............................................................................................................................91  
4.14.1: Silence Inhibit Timer.......................................................................................................................91  
4.14.2: Autosilence Timer ...........................................................................................................................91  
4.14.3: Trouble Reminder............................................................................................................................91  
4.14.4: Soak Timers.....................................................................................................................................91  
4.14.5: Waterflow Delay Timer...................................................................................................................91  
4.15: Walktest .....................................................................................................................................................91  
4.16: Read Status ................................................................................................................................................92  
4.16.1: FACP Configuration........................................................................................................................93  
4.16.2: Input Zones......................................................................................................................................93  
4.16.3: Output Circuits ................................................................................................................................94  
4.16.4: Cross Input Zones............................................................................................................................94  
4.16.5: On-Board Relays.............................................................................................................................95  
4.16.6: System Settings ...............................................................................................................................95  
4.16.7: Timers..............................................................................................................................................96  
4.16.8: Daylight Savings .............................................................................................................................96  
4.16.9: History.............................................................................................................................................97  
4.16.10: ANN-S/PG ....................................................................................................................................97  
4.16.11: ANN-BUS .....................................................................................................................................98  
SECTION 5: Power Supply Calculations .............................................................................................................99  
5.1: Overview .....................................................................................................................................................99  
5.2: Calculating the AC Branch Circuit..............................................................................................................99  
5.3: Calculating the System Current Draw.........................................................................................................100  
5.3.1: Overview ...........................................................................................................................................100  
5.3.2: How to Use Table 5-3 on page 101 to Calculate System Current Draw...........................................100  
5.4: Calculating the Battery Size ........................................................................................................................102  
5.4.1: NFPA Battery Requirements.............................................................................................................102  
5.4.2: Selecting and Locating Batteries.......................................................................................................102  
APPENDIX A: Circuit Mapping and Cross-Zoning ..........................................................................................103  
A.1: Input-to-Output Circuit Mapping and Cross-Zone Operation ...................................................................103  
A.1.1: Mapping Input Zones to Output Circuits for Direct Activation ......................................................104  
A.1.2: Mapping Input Zones to Release Circuits for Cross Zone  
Activation ........................................................................................................................................105  
A.1.3: Complex Examples of Cross Zoning and I/O Mapping for  
Release Circuits ..............................................................................................................................107  
APPENDIX B: FACP Configuration Templates ................................................................................................108  
B.1: Template 7: Single Hazard - 3 Zone .........................................................................................................109  
B.2: Template 8: Single Hazard - Cross-Zone With Manual Release ..............................................................110  
B.3: Template 9: Dual Hazard - Combined Release ........................................................................................111  
B.4: Template 10: Dual Hazard - Split Release ................................................................................................112  
B.5: Template 11: Single Hazard - 3 Zones and Low Pressure ........................................................................113  
6
MRP-2001 & MRP-2001E P/N: 53040:A 4/16/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
B.6: Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active ....................................................114  
B.7: Template 13: Single Hazard - Dual Zone .................................................................................................115  
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................116  
C.1: NFPA 72 Auxiliary Fire Alarm System ....................................................................................................119  
C.2: Central Station/Remote Station Transmitter:  
Connection to FACP Dry Contacts ...........................................................................................................122  
APPENDIX D: FACP with Keltron .....................................................................................................................123  
APPENDIX E: Testing & Maintenance ..............................................................................................................124  
E.1: Testing .......................................................................................................................................................124  
E.1.1: Inspection .........................................................................................................................................124  
E.1.2: Alarm Test .......................................................................................................................................124  
5.4.3: Detector Testing ................................................................................................................................124  
E.2: Maintenance ...............................................................................................................................................125  
MRP-2001 & MRP-2001E P/N: 53040:A 4/16/07  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
8
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction  
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:  
Underwriters Laboratories Standards  
NFPA 72 National Fire Alarm Code  
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems  
Before proceeding, the installer should be familiar with the following documents.  
NFPA Standards  
This Fire Alarm Control Panel complies with the following NFPA Standards:  
NFPA 13 Installation of Sprinkler Systems  
NFPA 15 Water Spray Fixed Systems  
NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray Systems  
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote  
Station Fire Alarm Systems (requires an optional Remote Station Output Module)  
Underwriters Laboratories Documents for Reference:  
UL 38 Manually Actuated Signaling Boxes  
UL 217 Smoke Detectors, Single and Multiple Station  
UL 228 Door Closers–Holders for Fire Protective Signaling Systems  
UL 268 Smoke Detectors for Fire Protective Signaling Systems  
UL 268A Smoke Detectors for Duct Applications  
UL 346 Waterflow Indicators for Fire Protective Signaling Systems  
UL 464 Audible Signaling Appliances  
UL 521 Heat Detectors for Fire Protective Signaling Systems  
UL 864 Standard for Control Units for Fire Protective Signaling Systems  
UL 1481 Power Supplies for Fire Protective Signaling Systems  
UL 1638 Visual Signaling Appliances  
UL 1971 Signaling Devices for Hearing Impaired  
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems  
Other:  
NEC Article 250 Grounding  
NEC Article 300 Wiring Methods  
NEC Article 760 Fire Protective Signaling Systems  
Applicable Local and State Building Codes  
Requirements of the Local Authority Having Jurisdiction (LAHJ)  
Fire•Lite Documents  
Fire•Lite Device Compatibility Document  
411UD Manual  
411UDAC Manual  
Document #15384  
Document #50759  
Document #51073  
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire  
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not  
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Main Circuit Board  
D B T P O F T M X 4  
10  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Features  
Product Description  
SECTION 1  
Product Description  
The MRP-2001 is a six zone FACP for single and dual hazard deluge and preaction applications.  
The FACP provides reliable fire detection, signaling and protection for commercial, industrial and  
institutional buildings requiring water-based releasing. The FACP is compatible with System  
Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance  
trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when  
the ambient temperature falls below the detector rating of approximately 45o F (refer to System  
Sensor for i3 Installation and Maintenance Instructions). In addition, the control panel is  
compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke  
detectors, pull stations, waterflow devices, tamper switches and other normally-open contact  
devices. Refer to Device Compatibility Document for a complete listing of compatible devices.  
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids.  
Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory)  
and 24 VDC special application resettable and nonresettable power outputs are also included on the  
main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.  
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will  
activate audible and visual signaling devices, illuminate an indicator, display alarm information on  
the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate  
an optional module used to notify a remote station or initiate an auxiliary control function.  
The MRP-2001E offers the same features as the MRP-2001 but allows connection to 220/240 VAC.  
Unless otherwise specified, the information in this manual applies to both the 110/120 VAC and  
220/240 VAC versions of the panels.  
1.1 Product Features  
Six programmable Style B (Class B) IDCs (Initiating  
Device Circuit)  
Four programmable Style Y (Class B) output circuits  
- (special application power)  
Three programmable Form-C relays  
7.0 amps total 24 VDC output current  
Resettable and non-resettable output power  
Built-in Programmer  
ANN-BUS for connection to optional:  
ANN-80 Remote LCD Annunciator  
ANN-I/O LED Driver  
ANN-S/PG Printer Module  
ANN-RLY Relay Module  
ANN-LED Annunciator Module  
80-character LCD display (backlit)  
Real-time clock/calendar with daylight savings time control  
History log with 256 event storage  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Product Description  
Product Features  
Control Buttons  
ACK (Acknowledge)  
Alarm Silence  
System Reset/Lamp Test  
Drill  
Indicators  
Fire Alarm  
Supervisory  
Trouble  
AC Power  
Alarm Silence  
Discharge  
Piezo sounder for alarm, trouble and supervisory  
24 volt operation  
Low AC voltage sense  
Outputs Programmable for:  
Releasing Solenoids  
NACs programmable for:  
Silence Inhibit  
Auto-Silence  
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)  
Selective Silence (horn-strobe mute)  
Temporal or Steady Signal  
Silenceable or Nonsilenceable  
Release Stage Sounder  
Designed for sprinkler standards NFPA 13, 15 and 16  
Disable/Enable control per input zone and output zone  
Extensive transient protection  
Dual hazard operation  
Adjustable waterflow discharge timer and two soak timers  
Cross-zone (double-interlock) capability  
Pre-programmed and custom application templates  
Automatic battery charger with charger supervision  
Silent or audible walktest capabilities  
Optional Dress Panel DP-51050 (red)  
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet  
Optional CAC-5X Class A Converter Module for Outputs and IDCs  
Optional 4XTMF Municipal Box Transmitter Module  
Optional Digital Alarm Communicators (411, 411UD, 411UDAC)  
12  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Product Description  
1.2 Specifications  
AC Power  
MRP-2001: 120 VAC, 60 Hz, 3.66 amps  
MRP-2001E: 240 VAC, 50 Hz, 2.085 amps  
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation  
Supervised, nonpower-limited  
Battery (sealed lead acid only) - J12  
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp  
Supervised, nonpower-limited  
Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed  
in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or BB-55)  
Minimum Battery Size: 7 Amp Hour  
Initiating Device Circuits - TB4 and TB6  
Alarm Zones 1 - 5 on TB 4  
Alarm Zone 6 on TB6  
Supervised and power-limited circuitry  
Operation: All zones Style B (Class B)  
Normal Operating Voltage: Nominal 20 VDC  
Alarm Current: 15 mA minimum  
Short Circuit Current: 40 mA max.  
Maximum Loop Resistance: 100 ohms  
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)  
Standby Current: 2 mA  
Refer to the Device Compatibility Document for listed compatible devices  
1
Notification Appliance and Releasing Circuit(s) - TB5 and TB7  
Four Output Circuits  
Operation: Style Y (Class B)  
Special Application power  
Supervised and power-limited circuitry  
Normal Operating Voltage: Nominal 24 VDC  
Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC)  
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)  
Max. Wiring Voltage Drop: 1.5 VDC  
Refer to the Device Compatibility Document for compatible listed devices  
Form-C Relays - Programmable - TB8  
Relay 1 (factory default programmed as Alarm Relay)  
Relay 2 (factory default programmed as fail-safe Trouble Relay)  
Relay 3 (factory default programmed as Supervisory Relay)  
Relay Contact Ratings: 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive)  
Auxiliary Trouble Input  
The Auxiliary Trouble Input is an open collector, unsupervised circuit which can be used to  
monitor external devices for trouble conditions. It can be connected to the trouble bus of a  
peripheral, such as a power supply, which is compatible with open collector circuits.  
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.  
Special Application Resettable Power - TB9  
Operating Voltage: Nominal 24 VDC  
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see  
note 1)  
Power-limited Circuitry  
Refer to the Device Compatibility Document for compatible listed devices  
1. Total current for resettable power, nonresettable power and Output Circuits must not exceed  
7.0 amps.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
Product Description  
Special Application Resettable or Nonresettable Power - TB9  
Controls and Indicators  
Operating Voltage: Nominal 24 VDC  
Maximum Available Current: 500 mA (see note 1)  
Power-limited Circuitry  
Jumper selectable by JP31 for resettable or nonresettable power:  
Jumper pins 1 & 2 on JP31 for nonresettable power  
Jumper pins 2 & 3 on JP31 for resettable power  
Refer to the Device Compatibility Document for compatible listed devices  
1.3 Controls and Indicators  
LCD Display  
The FACP uses an 80-character  
(4 lines X 20 characters) high viewing angle  
LCD display. The display includes a long life  
LED backlight that remains illuminated. If AC  
power is lost and the system is not in alarm, the  
LED backlight will turn off to conserve batteries.  
SYSTEM ALL NORMAL  
10:00A 012106  
Key Panel  
Mounted on the main circuit board, the key panel includes a window for the LCD display and  
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25  
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.  
Function keys:  
Acknowledge/Step  
Alarm Silence  
Drill  
System Reset (lamp test)  
Service/program keys:  
Keys labeled 1 to 9  
* key  
# key  
Figure 1.1 Membrane/Display Panel  
0 (recall) key  
1st Event key  
Clear key  
Escape key  
Mode key  
Four cursor keys (up, down, left and right)  
Enter key  
14  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Components  
Product Description  
Local Piezo Sounder  
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory  
conditions.  
Indicators  
Indicators are provided to annunciate the following conditions:  
Fire Alarm - red indicator  
Supervisory - yellow indicator  
AC Power - green indicator  
System Trouble - yellow indicator  
Alarm Silence - yellow indicator  
Discharge - red indicator  
Local Piezo Sounder  
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and  
supervisory conditions as follows:  
Alarm - on steady  
Trouble - pulse 1 second on and 1 second off  
Maintenance - pulse ½ second on and ½ second off  
Supervisory - pulse ½ second on and ½ second off  
1.4 Components  
Main Circuit Board  
The main circuit board contains the system’s CPU and other primary components and wiring  
interface connectors. Optional modules plug in and are mounted to the main circuit board.  
Power Supply  
One FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.  
Cabinet  
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides  
space for two batteries (up to 18 Amp Hours). Also available is an optional dress panel (DP-51050  
[red] and supplied standard with Canadian versions only, DP-51050LED for mounting ANN-LED  
annunciator modules) which mounts inside the cabinet and trim-ring (TR-CE [red]).  
Batteries  
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL  
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Product Description  
Optional Modules and Accessories  
1.5 Optional Modules and Accessories  
CAC-5X Class A Converter Module  
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to  
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect  
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required  
to convert all six Output Circuits and four Initiating Device Circuits.  
4XTMF Transmitter Module  
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and  
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper  
option allows the reverse polarity circuit to open with a system trouble condition if no alarm  
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.  
ANN-80 LCD Annunciator  
The ANN-80 is a remote LCD annunciator that mimics the information displayed on the FACP  
LCD display.  
ANN-LED Annunciator Module  
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and  
Supervisory.  
ANN-RLY Relay Module  
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.  
ANN-S/PG Serial/Parallel Printer Gateway  
The ANN-S/PG module provides a connection for a serial or parallel printer.  
ANN-I/O LED Driver Module  
The ANN-I/O module provides connections to a user supplied graphic annunciator.  
Dress Panel  
A dress panel DP-51050 (red) is available as an option. The dress panel restricts access to the  
system wiring while allowing access to the membrane switch panel.  
DP-51050LED Dress Panel  
A DP-51050LED dress panel is provided standard only with Canadian versions of the FACP. The  
dress panel restricts access to the system wiring while allowing access to the membrane switch  
panel. It also allows the installation of an optional ANN-LED annunciator module.  
TR-CE Trim-ring  
A trim-ring TR-CE (red) is available as an option. The trim-ring allows semi-flush mounting of the  
cabinet.  
Battery Box  
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour.  
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.  
16  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Backbox Mounting  
Installation  
SECTION 2  
Installation  
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the  
installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots  
at the top of the backbox and two additional securing holes located at the bottom.  
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,  
vibration-free area where extreme temperatures or levels of humidity are not encountered. The area  
should be readily accessible with sufficient room to easily install and maintain the panel. Locate  
the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the  
left. Determine the number of conductors required for the devices to be installed. Sufficient  
knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the  
conductors into the box. All wiring should be in accordance with the National and/or Local codes  
for fire alarm systems.  
2.1 Backbox Mounting  
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist  
strap before handling any boards so that static charges are removed from the body. Use static  
suppressive packaging to protect electronic assemblies.  
!
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main  
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top  
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis  
assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.  
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the  
dimensions illustrated in Figure 2.2 on page 18  
See Page  
Install center top fastener in the wall with the screw head protruding  
Place backbox over the top screw, level and secure  
Mark and drill the left and right upper and lower mounting holes  
Note: outer holes (closest to sidewall) are used for 16” on-center stud mounting  
Install remaining fasteners and tighten  
Board on Chassis  
mounting holes  
mounting slots  
mounting studs  
mounting tabs  
grounding stud:  
attach solid earth  
ground wire (refer to  
Figure 2.4 on page 20)  
mounting slots  
Backbox  
Figure 2.1 Chassis Mounting in Backbox  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Installation  
Backbox Mounting  
Semi-Flush Mounting  
Do not recess box more  
than 3.875” into wall to  
avoid covering venting  
holes on top of box.  
Hinge Slot for  
optional Dress Panel  
Mounting  
slots for  
optional  
Trim Ring  
Semi-Flush  
mounting hole  
Hinge Slot for optional  
Dress Panel  
Figure 2.2 Cabinet Dimensions  
18  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Backbox Mounting  
Installation  
Figure 2.3 Backbox  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Operating Power  
2.2 Operating Power  
WARNING: Several different sources of power can be connected to this panel. Disconnect all  
sources of power before servicing. The panel and associated equipment may be damaged by  
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.  
Primary Power Source (AC) and Earth Ground Connections  
AC power connections are made inside the control panel cabinet. The primary power source for the  
panel is 120 VAC, 60 Hz, 3.66 amps for the MRP-2001 or 240 VAC, 50 HZ, 2.085 amps for the  
MRP-2001E. Run a pair of wires (with ground conductor) from the protected premises main  
breaker box to the AC terminal block TB1 on the main power supply. As per the National  
Electrical Code, use 14 AWG (2.00 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V  
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be  
provided with overcurrent protection and may not contain any power disconnect devices. A  
separate Earth Ground connection must be made to ensure proper panel operation and lightning and  
transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm2)] to the  
grounding stud in the backbox. Do not use conduit for the Earth Ground connection since this does  
not provide reliable protection.  
Secondary Power Source (Batteries)  
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit  
board using the plug-in connector and cable provided. The battery charger is current-limited and  
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.  
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and  
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with  
water for 15 minutes and seek immediate medical attention.  
!
120 VAC Power  
Hot (L1)  
Ground  
Neutral (L2)  
Ground Wire  
-
+
J12  
Batteries  
Figure 2.4 Operating Power Connections  
20  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Circuits  
Installation  
2.3 Input Circuits  
The MRP-2001 has six programmable IDCs (Initiating Device Circuits). Each circuit is compatible  
with System Sensor’s i3 smoke detectors which generate a maintenance signal when the detector  
becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the  
detector rating of approximately 45oF. The maximum loop resistance limit for each IDC is 100  
ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is  
supervised for opens, shorts and ground faults. All conditions are visually and audibly  
annunciated.  
Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any  
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.  
Refer to the Device Compatibility Document for a list of compatible devices.  
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A  
Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.  
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252  
UL listed Power Supervision Relay  
(refer to Device Compatibility Document for list of compatible relays)  
UL listed compatible 4-wire smoke detector  
Input IDC  
Waterflow Circuit  
Normally Open  
Waterflow  
Devices or  
Pressure Switches  
manual pull stations  
Resettable 24 VDC  
4-wire smoke  
detector power  
manual  
release  
heat detectors  
(500 mA maximum)  
Dummy load all unused  
circuits - 4.7 KΩ, ½ watt  
resistor (P/N: 71245)  
Figure 2.5 IDC Connections  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
Installation  
Input Circuits  
Combination Waterflow/Supervisory Zone  
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm  
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any  
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of  
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.  
Class B Initiating Device Circuits (supervised and power-limited)  
4.7 KΩ, ½ watt resistor P/N:71252  
Supervisory Switch  
(tamper)  
In-Line-Resistor  
1.2 KΩ, ½ watt resistor P/N: 75579  
Alarm Switch  
(waterflow)  
Dummy load all unused  
circuits - 4.7 KΩ, ½ watt  
resistor (P/N: 71245)  
Figure 2.6 Style B Combination Circuit on Zone 2  
Requirements for the Combination Waterflow/Supervisory circuit are as follows:  
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before  
the In-Line Resistor as shown in Figure 2.6  
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-  
Line Resistor as shown in Figure 2.6  
Program the FACP Initiating Device Circuit as a Combination circuit as described in  
"Input Zones" on page 50. Note that since a Waterflow Supervisory Switch is included in  
a Combination circuit, the waterflow delay must be taken into consideration. Refer to  
"Waterflow Delay" on page 66.  
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm  
condition is cleared and the FACP is reset  
Supervisory Switch activation causes the panel to latch the supervisory condition if the  
Combo type code is selected or track (the panel will clear when the supervisory condition  
is cleared) if the Combo Autoresettable Supervisory type code is selected  
22  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output Circuits  
Installation  
2.4 Output Circuits  
2.4.1 Outputs/Notification Appliance/Releasing Circuits  
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0  
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed  
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and  
provides special application power. Refer to the Device Compatibility Document for a listing of  
compatible notification appliances.  
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter  
module. Refer to "CAC-5X Class A Converter Module" on page 26.  
Class B Notification Appliance Circuits (supervised and power-limited)  
4.7 KΩ, ½ watt resistor P/N:71252  
Polarized Bell  
Polarized Bell  
Polarized Strobe  
Polarized Horn  
Polarized Strobe  
Polarized Horn  
Releasing Solenoid  
Dummy load any unused  
circuits (P/N: 71245)  
Notification Appliance Circuits  
polarity shown in alarm condition  
Ferrite Beads  
P/N 29150  
Ferrite Bead  
P/N 29150  
+
- +  
-
+
- +  
-
Note: Short Circuit Supervision must be enabled when using the  
REL-4.7K for Canadian Applications. Refer to the section titled  
"Release Circuit 1 or Release Circuit 2" on page 58 for information  
on enabling short circuit supervision.  
Ferrite Bead (P/N 29150)  
Large gauge wire  
should be looped  
through bead at least  
once as illustrated.  
Smaller gauge wire can  
be looped more often.  
Ferrite Bead in open position  
Ferrite Bead in closed position  
Figure 2.7 NAC/Output Connections  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
Installation  
Output Circuits  
2.4.2 Special Application DC Power Output Connections  
Special Application Resettable and Nonresettable 24 VDC power is available on the MRP-2001  
control panel.  
Special Application  
4-Wire Smoke Detector Power (500 mA)  
24 VDC filtered, resettable power for 4-wire smoke detectors  
can be obtained from these terminals (power-limited)  
-
4
3
2
1
+
-
Special Application  
Resettable or Nonresettable Power (500 mA)  
24 VDC filtered, resettable or nonresettable power can be  
obtained from these terminals (power-limited)  
+
Jumper JP31 pins 1 & 2 for nonresettable power (as  
illustrated in figure to right)  
Jumper JP31 pins 2 & 3 for resettable power  
Figure 2.8 Special Application Auxiliary Power  
2.4.3 Relays - Programmable  
The MRP-2001control panel provides a factory default programmed alarm relay, fail-safe trouble  
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer  
to "On-Board Relays" on page 64). Each Form-C relay is rated for 2 amps @ 30VDC (resistive)  
and 0.5 amps @ 30 VAC (resistive).  
Note that relay connections must be power-limited.  
Note: Relay contacts are shown with  
power applied to the panel and no active  
troubles, alarms or supervisories.  
The Trouble Relay is a fail-safe relay  
which will transfer on any trouble or  
total power failure.  
Figure 2.9 Relay Terminals  
24  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power-limited Wiring Requirements  
Installation  
2.5 Power-limited Wiring Requirements  
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All  
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-  
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must  
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is  
illustrated below.  
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent  
to a releasing circuit (nonpower-limited without supervision kit REL-4.7K)  
Nonpower-limited Circuits*  
Power-limited Circuits  
(Class 2)  
Power-limited Circuits (Class 2)  
Power-limited  
Circuits  
(Class 2)  
CAC-5X  
CAC-5X  
AC Power  
120 VAC  
Hot (L1)  
Ground  
Neutral (L2)  
4XTMF  
Nonpower-  
limited  
Circuit  
earth  
ground  
Nonpower-  
limited  
Circuit  
Power-limited  
Circuit  
(Class 2)  
Deluge - Preaction Control FACP  
Figure 2.10 Typical UL Power-limited Wiring Requirements  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
Installation  
Installation of Optional Modules  
2.6 Installation of Optional Modules  
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.  
2.6.1 CAC-5X Class A Converter Module  
2.6.1.1 Installation  
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to  
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z  
(Class A). Two CAC-5X Modules are required to convert all Output Circuits and/or Initiating  
Device Circuits to Class A. The modules plug into connector J2 which is located at the top left  
of the main circuit board and J7 which is located at the top center of the main circuit board.  
To install the CAC-5X, remove the two main circuit board mounting screws referenced in the  
following illustration and replace with the two supplied male/female standoffs in the locations  
indicated in the following figure. Carefully align the connector on the CAC-5X with J2 on the  
FACP main circuit board and press the module securely into place. Make certain the pins are  
properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to  
the standoffs with the screws that were just removed.  
To install the second CAC-5X on J7, remove the main circuit board mounting screw referenced  
in the following illustration and replace with the supplied male/female standoff. Insert the  
supplied plastic standoff in the location indicated in the following illustration. Carefully align  
the connector on the CAC-5X with J7 and press the module securely into place. Make certain  
the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the  
CAC-5X to the metal standoff with the screw that was just removed.  
Installation on J7 Connector  
Installation on J2 Connector  
CAC-5X Module  
CAC-5X Module  
Metal  
Standoff  
Metal  
Standoff  
Metal  
Standoff  
Plastic  
Standoff  
Main Circuit Board  
Figure 2.11 CAC-5X Module Installation  
26  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of Optional Modules  
Installation  
2.6.1.2 Wiring NACs and IDCs for Class A  
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit  
board and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits  
using TB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will  
be identical when using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity  
when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed  
and return for the positive side of a device and the B- and A- terminals must comprise the feed  
and return for the negative side of a device. To configure any of the zones for Class B when the  
CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the  
End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+  
and A- terminals on the CAC-5X module.  
Class B (Style B) IDC - 4.7 KΩ  
½ watt ELR resistor  
P/N:71252 (supervised and power-limited)  
Class A (Style D) IDC  
(supervised and power-limited)  
Smoke  
Smoke  
Class A (Style Z) NAC  
(supervised and power-limited)  
Polarized  
Bell  
Pull Station  
Pull Station  
Polarized  
Strobe  
Heat  
Heat  
Polarized  
Horn  
Ferrite Bead  
P/N 29150  
Dummy load all unused  
circuits - 4.7 KΩ  
½ watt ELR resistor  
Circuit polarities  
shown in alarm  
condition  
B+ B- B+ B- B+ B- B+ B- B+ B-  
(P/N: 71245)  
B+ B-  
B+ B-  
FACP Main  
Circuit Board  
A+ A-  
A+ A-  
A+ A- A+ A- A+ A- A+ A- A+ A-  
CAC-5X Class A Converter Module  
Large gauge wire should be looped through  
bead at least once as illustrated. Smaller  
gauge wire can be looped more often.  
Ferrite Bead in open position  
Ferrite Bead in closed position  
Figure 2.12 Wiring NACs and IDCs for Class A Operation  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
Installation  
Installation of Optional Modules  
2.6.2 4XTMF Municipal Box Transmitter Option Module  
The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board.  
The following steps must be followed when installing the 4XTMF module:  
1. Remove all power (AC and DC) from the FACP before installing the modules  
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the  
placement of the 4XTMF option module  
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide  
the required earth ground protection  
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP  
main circuit board, being careful not to bend any pins  
5. Secure the option module to the standoff on the main circuit board with the supplied screws  
6. When the installation has been completed, connect the wiring to the modules as indicated in  
the following sections  
7. Test system for proper operation  
Standoffs  
J4  
J5  
Figure 2.13 4XTMF Option Module Connection  
28  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of Optional Modules  
Installation  
2.6.2.1 4XTMF Transmitter Module Installation  
The 4XTMF provides a supervised output for a local energy municipal box transmitter in  
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity  
circuit to open with a system trouble condition if no alarm condition exists. A disable switch  
allows disabling of the transmitter output during testing to prevent accidental calling of the  
monitoring service.  
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):  
Supervisory Current: 5.0 mA  
Trip Current: 350 mA (subtracted from notification appliance power)  
Coil Voltage: 3.65 VDC  
Maximum Coil Resistance: 14.6 ohms  
Maximum allowable wire resistance between panel and trip coil: 3 ohms  
Municipal Box wiring can leave the building  
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for  
connection to a polarity reversal circuit or a Remote Station receiving unit having  
compatible ratings:  
Maximum load for each circuit: 10 mA  
Reverse polarity output voltage: 24 VDC  
Remote Alarm and Remote Trouble wiring can leave the building  
Before installing the module, place the disconnect switch to the down (disconnect) position to  
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate  
after the module is installed in the FACP. In addition, the System Trouble indicator will turn on  
to indicate the Disconnect condition.  
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity  
supervisory signal. For an application using reverse polarity of a supervisory signal,  
refer to the Appendix titled "FACP with Keltron" on page 123.  
Polarities are shown for module activation  
TB1  
1+  
2-  
3+  
4-  
}Remote Alarm (power-limited)*  
}Remote Trouble (power-limited)*  
5
No connection  
6+  
7-  
}Municipal Box (nonpower-limited)*  
* Wiring from these terminals can  
exit the protected premises.  
TBL Jumper  
TBL  
J1  
J2  
Dummy load terminals 6 and 7  
(4.7kΩ, ¼ watt resistor) if  
Municipal Box is not connected.  
Disconnect  
Switch  
shown in  
disconnect  
position  
Disconnect LED  
Connect to FACP Connectors J4 & J5  
Figure 2.14 4XTMF Transmitter Module  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
Installation  
ANN-BUS Devices  
2.7 ANN-BUS Devices  
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any  
modules or wiring.  
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.  
Compatible devices include:  
ANN-80 LCD Annunciator  
ANN-S/PG Serial/Parallel Printer Interface Module  
ANN-I/O LED Driver Module  
ANN-LED Annunciator Module (annunciates alarms, troubles and supervisories)  
ANN-RLED Annunciator Module (annunciates alarms only)  
ANN-RLY Relay Module  
2.7.1 ANN-BUS Wiring  
This section contains information on calculating ANN-BUS wire distances and the types of wiring  
configurations (Class B).  
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules  
The following instructions will guide the installer in determining the type of wire and the  
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.  
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is  
necessary to calculate the total worst case current draw for all modules on a single 4-conductor  
bus. The total worst case current draw is calculated by adding the individual worst case  
currents for each module. The individual worst case values are shown in the following table:  
Model Number  
ANN-80 LCD Annunciator  
Worst Case Current Draw  
0.040 amps  
ANN-S/PG Serial/Parallel Printer Interface Module  
ANN-I/O LED Driver Module  
0.040 amps  
0.200 amps  
ANN-(R)LED Annunciator Module  
ANN-RLY Relay Module  
0.068 amps  
0.075 amps  
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.  
30  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance  
the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of  
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire  
gauges, capacitance is the limiting factor.  
These cases are marked in the chart with an asterisk (*). Maximum length can never be more  
than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is  
shown in the note below.  
Wiring Distance: ANN-BUS Modules to FACP  
Total Worst Case Current  
22 Gauge  
18 Gauge  
16 Gauge  
14 Gauge  
Draw (amps)  
0.100  
1,852 ft.  
926 ft.  
617 ft.  
463 ft.  
370 ft.  
4,688 ft.  
2,344 ft.  
1,563 ft.  
1,172 ft.  
938 ft.  
* 6,000 ft.  
3,731 ft.  
2,488 ft.  
1,866 ft.  
1,493 ft.  
*6,000 ft.  
5,906 ft.  
3,937 ft.  
2,953 ft.  
2,362 ft.  
0.200  
0.300  
0.400  
0.500  
Table 2.1 Wiring Distances  
Note: The following formulas were used to generate the wire distance chart:  
Maximum Resistance (Ohms)  
=
=
6.0 Volts  
Total Worst Case Current Draw (amps)  
Maximum Wire Length (feet)  
(6,000 feet maximum)  
Maximum Resistance (Ohms)  
Rpu  
*500  
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)  
Wire Gauge  
Ohms per 1,000 feet (Rpu)  
22  
18  
16  
14  
16.2  
6.4  
4.02  
2.54  
Exception: When using the ANN-RLY module, the installer must ensure that the maximum  
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring  
limitations:  
Wire Gauge  
Maximum Wire Length  
312 feet  
18  
16  
14  
12  
497 feet  
787 feet  
1,250 feet  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
ANN-BUS Devices  
Wiring Distance Calculation Example:  
Suppose a system is configured with the following ANN-BUS modules:  
2 ANN-80 Remote LCD Annunciators  
1 ANN-S/PG Serial/Parallel Printer Interface Module  
1 ANN-I/O LED Driver Module  
The total worst case current is calculated as follows:  
ANN-80 Current Draw  
ANN-S/PG Current Draw  
ANN-I/O Current Draw  
= 2 X 0.040 amps  
= 1 X.0.040 amps  
= 1 X.0.200 amps  
= 0.080 amps  
= 0.040 amps  
= 0.200 amps  
= 0.320 amps  
Total Worst Case Current Draw  
Using this value and referring to the Wiring Distance Table 2.1 on page 31, it can be found that  
the available options are:  
463 feet maximum using 22 Gauge wire  
1,172 feet maximum using 18 Gauge wire  
1,866 feet maximum using 16 Gauge wire  
2,953 feet maximum using 14 Gauge wire  
2.7.1.2 Wiring Configuration  
Figure 2.15 illustrates the wiring between the FACP and ANN-BUS devices.  
FACP  
TB3  
ANN-BUS and power wiring are  
supervised and power-limited  
ANN-80  
Figure 2.15 FACP wiring to ANN-BUS Device  
32  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply  
Figure 2.16 illustrates the powering of ANN-BUS devices from an auxiliary power supply such  
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-  
BUS power requirements.  
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)  
TB3  
FACP  
ANN-BUS  
-24 VDC  
ANN-80  
+24 VDC  
ANN-BUS and power wiring are  
supervised and power-limited  
FCPS-24FS6/8  
Figure 2.16 Powering ANN-BUS Devices from FCPS-24FS6/8  
2.7.2 ANN-BUS Device Addressing  
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the  
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these  
devices must also be programmed at the FACP for the specific device (refer to the programming  
section titled "ANN-BUS" on page 71).  
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device  
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that  
00 is not a valid address. The following table shows the DIP switch setting for each address.  
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.  
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and  
above must be set to OFF.  
Address  
Switch 5  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
Switch 4  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
Switch 3  
OFF  
OFF  
OFF  
OFF  
ON  
Switch 2  
OFF  
OFF  
ON  
Switch 1  
OFF  
ON  
not valid  
01  
02  
03  
04  
05  
06  
07  
08  
OFF  
ON  
ON  
OFF  
OFF  
ON  
OFF  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
OFF  
OFF  
OFF  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
Installation  
ANN-BUS Devices  
2.7.3 ANN-80 Remote LCD Annunciator  
The ANN-80 LCD Annunciator is a compact, 80 character, backlit LCD remote fire annunciator  
which mimics the FACP display. It also provides system status indicators for AC Power, Alarm,  
Trouble, Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and  
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication  
format. The devices are powered, via two additional wires, from either the host FACP or remote  
UL-listed, filtered, power supply.  
2.7.4 Specifications  
Operating Voltage Range: 18 VDC to 28 VDC  
Current Consumption @ 24 VDC nominal (filtered and nonresettable):  
Normal/Standby (no activity): 37.0 mA  
Trouble: 39.0 mA  
Alarm: 40.0 mA  
AC Fail (not backlit): 15.0 mA  
For use indoors in a dry location  
2.7.5 Installation  
Ensure that all power (AC and DC) has been removed from the FACP before installing the  
annunciator.  
2.7.5.1 Mounting  
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical  
box. Select and remove the appropriate knockout(s), pull the necessary wires through the  
knockouts and mount the annunciator in or on the wall depending on the type of installation  
desired.  
The ANN-80 cover must be attached to the annunciator backplate before mounting the  
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the  
annunciator has been mounted.  
2.7.5.2 Opening/Closing Annunciator  
The following procedure details the steps used to open the annunciator in order to access the  
terminal block and DIP switches (refer to figure below):  
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise  
2. Push in the snap latch located on the right side of the unit while pulling the cover open  
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the  
cover closed, snapping it shut  
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key  
Annunciator cover with LCD display  
Annunciator backplate  
Press in latch and pull  
annunciator cover open  
Key switch shown in ON position  
34  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.5.3 Wiring ANN-80 to FACP  
The following steps can be used as a guide to wire the annunciator. Make certain all power has  
been removed from the FACP prior to annunciator installation.  
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal  
block TB1  
wiring channel  
wires  
TB1  
2. Remove appropriate amount of wire insulation  
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).  
Make certain to connect A to A and B to B  
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1  
terminals 3 & 4. Make certain to connect A to A and B to B  
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2  
(+). Make certain to observe proper polarity  
6. If appropriate, connect the power wiring going to the next device to terminals  
1 (-) & 2 (+). Make certain to observe proper polarity  
7. After all connections are made, remove extra wire from inside of annunciator by dressing it  
neatly through wire channel, with any excess wire pushed back through hole into electrical  
box  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Installation  
ANN-BUS Devices  
FACP  
TB3  
4 3 2 1  
ANN-BUS and power wiring are  
supervised and power-limited  
ANN-80  
Figure 2.17 ANN-80 Wiring to FACP  
The following table shows the ANN-80 connections to the FACP.  
FACP (TB3)  
ANN-80 (TB1)  
Terminal 4 GND (-)  
Terminal 1 (-)  
Terminal 2 (+)  
Terminal 3 (A)  
Terminal 4 (B)  
Terminal 3 PWR (+)  
Terminal 2 A (ANN-BUS)  
Terminal 1 B (ANN-BUS)  
Programming  
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator  
must be added to the system via FACP programming. Refer to the programming section titled  
"ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD  
option for programming.  
36  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.6 ANN-S/PG Serial/Parallel Printer Interface Installation  
The ANN-S/PG Serial/Parallel Interface module allows the ancillary connection of a serial or  
parallel printer to the FACP for a real-time log of system events, detector status reports and event  
history. Note that either a serial or parallel printer may be installed, not both. Proceed with the  
installation as described in the following:  
1. Ensure that all power (AC and DC) has been removed from the FACP.  
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.18  
TB3  
FACP  
ANN-S/PG Module  
Parallel  
Cable  
ANN-BUS and power wiring are  
supervised and power-limited  
Connectors for  
connection to  
printer  
Serial  
Figure 2.18 ANN-S/PG Connection to FACP  
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number  
(address) to the module  
4. Select the address and configuration options for the ANN-S/PG module as described in the  
Programming section of this manual (refer to "ANN-BUS" on page 71)  
Note that the Auto-configure feature allows the programmer to quickly bring all installed  
ANN-BUS modules online (refer to "Auto-Configure" on page 73)  
5. Connect a printer to the ANN-S/PG Parallel or Serial connector (refer to Figure 2.18 on page  
37)  
2.7.6.1 Specifications  
Operating Voltage: 24 VDC  
Current (Alarm and Standby): 45 mA  
Ambient Temperature: 32oF to 120oF (0oC to 49oC)  
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)  
Mounting: Surface  
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)  
For indoor use in a dry location only  
2.7.6.2 PRN-6 Printer Installation  
When connected to the FACP via the ANN-S/PG module, the PRN-6 prints the status changes  
within the control panel and time-stamps the printout with the time of day and date that the  
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This  
section contains information on connecting a printer to the control panel and setting the printer  
options.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
Installation  
ANN-BUS Devices  
2.7.6.2.1 Connecting PRN-6 Printer  
Remote printers require a primary AC power source. If required for the fire alarm system  
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a  
secondary power source (battery backup). Since a secondary power source is not provided as a  
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.  
The building emergency power supply may be used, as long as it meets the power continuity  
requirements of NFPA 72. Refer to NFPA 72 for further details.  
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25  
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the  
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-  
9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a  
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the  
same time.  
2.7.6.2.2 Setting Printer Options  
Refer to the documentation supplied with the PRN printer for instructions on using the printer  
menu controls. Set the printer options (under the menu area) as shown in the following table:  
Table 2.2 PRN-6 Setup Options  
Option  
Font  
LPI  
Setting  
HS Draft  
6 LPI  
Option  
CPI  
Skip  
Setting  
10CPI  
0.5  
ESC Character  
Bidirectional Copy  
CG-TAB  
Country  
Auto CR  
Color Option  
Formien  
ESC  
ON  
Graphic  
E-US ASCII  
OFF  
Emulate  
I/O  
Buffer  
Serial  
Baud  
Format  
Protocol  
Character Set  
SI.Zero  
Auto LF  
PAPER  
BIN 1  
Epson FX-850  
40K  
9600 or 2400  
7 Bit, Even, 1 Stop  
XON/XOFF  
Standard  
Not Installed  
Lines  
Standard  
6LPI=60  
Exec 10.5  
On  
On  
12/72”  
12/72”  
12/72”  
12/72”  
12/72”  
12/72”  
BIN 2  
SINGLE  
PUSH TRA  
PULL TRA  
PAP ROLL  
38  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.7 ANN-I/O LED Driver Module  
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including  
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40  
LEDs. The following sections describe hardware installation. Refer to the section titled "ANN-  
BUS" on page 71 for programming information.  
2.7.7.1 ANN-I/O Board Layout  
Figure 2.19 illustrates the ANN-I/O board showing locations of screw terminals for connection  
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-  
BUS ID number.  
Terminals not used (future)  
ANN-BUS (ID#)  
Address DIP  
switch  
ANN-BUS Connector  
Figure 2.19 ANN-I/O Board Layout  
2.7.7.2 Specifications  
Max. ANN-BUS Voltage: 28 VDC  
Max. Current:  
Alarm: 200 mA  
Standby: 35 mA  
Each LED: 10 mA  
Operating Temperature: 32oF to 120oF (0oC to 49oC)  
For indoor use in a dry location only  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
Installation  
ANN-BUS Devices  
2.7.7.3 ANN-I/O Connection to FACP  
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.20. After the  
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.  
TB3  
ANN-I/O Module  
FACP  
ANN-BUS and power wiring are  
supervised and power-limited  
Figure 2.20 ANN-I/O Connection to FACP  
40  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.7.4 ANN-I/O Module LED Wiring  
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10  
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized  
so that there is approximately 10 mA of current for each LED. No series resistors are required.  
LED outputs are mapped to output circuits. Refer to the section titled "ANN-I/O LED Zone  
Assignments" on page 75 of this manual.  
The LEDs are wired as illustrated in Figure 2.21. Note that the illustration depicts only  
connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).  
Figure 2.21 ANN-I/O Board Layout  
2.7.8 ANN-LED Annunciator Module  
The ANN-LED annunciator modules provide LED annunciation of general system faults and input  
zones when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble  
(yellow) and supervisory (yellow) indication for up to ten input zones.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
41  
Installation  
ANN-BUS Devices  
2.7.8.1 ANN-LED Board Layout  
Figure 2.22 illustrates the ANN-LED board showing locations of screw terminals for  
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.  
ANN-BUS (ID#)  
Address DIP switch  
ANN-BUS Connector  
Figure 2.22 ANN-LED Board Layout  
2.7.8.2 Specifications  
Max. ANN-BUS Voltage: 24 VDC  
Max. Current:  
Alarm: 68 mA  
Standby: 28 mA  
o
o
o
o
Operating Temperature: 32 F to 120 F (0 C to 49 C)  
For indoor use in a dry location only  
2.7.8.3 Mounting/Installation  
Install the ANN-LED Module as described in the documentation supplied with the annunciator.  
42  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.8.4 ANN-LED Connection to FACP  
Figure 2.23 illustrates the ANN-LED board showing locations of screw terminals for  
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.  
FACP  
ANN-LED  
-24 VDC  
+24 VDC  
ANN-BUS  
Figure 2.23 ANN-LED Connection to FACP  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
43  
Installation  
ANN-BUS Devices  
2.7.9 ANN-RLY Relay Module  
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a  
compatible FACP.  
2.7.9.1 ANN-RLY Board Layout  
Figure 2.22 illustrates the ANN-RLY board showing locations of screw terminals for  
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.  
ANN-BUS (ID#)  
Address DIP switch  
ANN-BUS Connector  
Figure 2.24 ANN-RLY Board Layout  
2.7.9.2 Specifications  
Operating Voltage: 24 VDC  
Max. Current:  
Alarm: 75 mA  
Standby: 15 mA  
Relay Contact Ratings:  
2.0 amps @ 30 VDC (resistive)  
0.5 amps @ 30 VAC (resistive)  
o
o
o
o
Operating Temperature: 32 F to 120 F (0 C to 49 C)  
For indoor use in a dry location only  
2.7.9.3 Mounting/Installation  
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.  
44  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANN-BUS Devices  
Installation  
2.7.9.4 ANN-RLY Connection to FACP  
Figure 2.23 illustrates the ANN-RLY board showing locations of screw terminals for  
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.  
FACP  
ANN-RLY  
-24 VDC  
+24 VDC  
ANN-BUS  
Figure 2.25 ANN-RLY Connection to FACP  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
45  
Programming  
User Programming  
SECTION 3  
Programming  
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES  
This product incorporates field-programmable software. In order for the product to comply with the requirements in the  
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited  
to specific values or not used at all as indicated below.  
Program feature or option  
Permitted in UL 864? (Y/N)  
Possible settings  
Settings permitted in UL 864  
ANN-80 Lock Enable  
Y
Lock Enable Yes  
Lock Enable No  
Lock Enable Yes  
Refer to Lock Enable in  
"ANN-80 Options" on page 76  
3.1 User Programming  
The FACP is completely field programmable using the panel keypad and requires no special  
software skills. While programming the FACP, the fire protection capabilities of the control panel  
are enabled.  
!
Program Templates have been provided to allow the panel to be quickly programmed with typical  
job-site configurations. Refer to "Circuit Mapping and Cross-Zoning" on page 103 for an  
explanation of mapping and cross-zoning and "FACP Configuration Templates" on page 108 for a  
detailed description of each template.  
Site-specific programming may be accomplished:  
by Manual programming or editing, using the FACP keypad  
The System All Normal screen will be displayed in a programmed system with no active alarms,  
troubles or supervisories, as illustrated below:  
SYSTEM ALL NORMAL  
10:00A 092105  
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or  
supervisory event exists at the panel, the event must be cleared before entering Programming mode.  
The exception to this is the programmer/operator can access Programming mode if the supervisory  
is due to the Disable Release event. Refer to Table 3.1 on page 52.  
To access any of the programming or read status features, the Enter or Mode key must be pressed,  
which will cause the LCD to display the following:  
WATER RELEASE PANEL  
1=READ STATUS MODE  
2=PROGRAMMING MODE  
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read  
Status Mode which allows the user to view the programmed features and status of the control panel  
The Read Status feature is not password protected. Refer to "Read Status" on page 92 for a  
detailed description of this feature.  
See Page  
46  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initial Power-up  
Programming  
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized  
person. After pressing 2, a screen will prompt for a password. After entering the correct password,  
the user may select from a list of programming options.  
Exit Programming and Read Status Mode  
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the  
display reads System All Normal. Note that the data which is entered during Programming mode  
is automatically saved by the panel as soon as the data is entered. If the Reset key is pressed or  
power is lost before exiting Programming mode, all data just entered will not be lost.  
User Programming Levels  
There are two user programming levels:  
User Master Program Level 1 is used for programming panel specific data relating to device  
types, zoning, messages, control panel functions, etc.  
User Maintenance Program Level 2 is used by a qualified operator to access features such as  
Disable/Enable, View and Clear History, Walktest and System Time Change.  
3.2 Initial Power-up  
The following sections describe the initial programming procedures for a new system. The same  
procedures are used to modify programming in an existing system.  
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has  
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition  
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an  
example of a possible trouble message that may be displayed.  
OPEN PULL STATION  
ZONE 1 OPEN FAULT  
09:03A 012106  
3.3 Programming Screens Description  
Two options are available when the Enter key is pressed: Read Status and Programming Mode.  
The Read Status and Programming options have multiple functions or features which may be  
chosen. To view all of the choices, it is necessary that the programmer scroll through a number of  
additional subscreens. These selections are displayed on multiple screens to make them more  
readable for the programmer. Refer to "Master Programming Level" on page 49, for additional  
information on the various screens.  
See Page  
The title of the main option screen will always be displayed at the top of the subscreens for the  
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed  
in the upper right corner of the screen being viewed. The programmer can then press the keypad  
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the  
programmer presses the keypad numerical key corresponding to the desired choice.  
Note that subscreens may also have multiple options which require viewing more than one screen.  
The same process, as detailed in the previous paragraphs, is followed to view all option choices.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
47  
Programming  
Programming and Passwords  
3.4 Programming and Passwords  
There are two factory set programming passwords which will access the Programming screens as  
indicated in the following examples. From either of the screens, access to specific system and  
device features or programming may be obtained. All user programming entries are stored in  
nonvolatile memory. The factory set passwords can be changed by the user as described in  
"Password Change" on page 80. If an invalid password is entered, the blinking cursor will return to  
the first password character position. To exit Programming or Read Status mode at any time, press  
the ESC (Escape) key repeatedly. Note that as soon as program data is entered, the data is  
automatically saved by the panel. If the Reset key is pressed or power is lost before exiting  
Programming mode, the data just entered will not be lost.  
See Page  
To access user Programming mode, press the Enter or Mode key. The LCD will display the  
following:  
1=READ STATUS MODE  
2=PROGRAMMING MODE  
To enter the user Programming mode, press 2. The display will read as follows:  
PROGRAMMING  
ENTER PASSWORD  
*****  
Entering the Master level password (default 00000) will cause the following screen to appear:  
PROGRAMMING  
1=FACP CONFIG  
T5  
2=INPUT ZONES  
3=OUTPUT CIRCUITS  
Programming Screen #1  
If the Maintenance level password (default 11111) is entered, the following screen will appear:  
PROGRAMMING  
1=INPUT ZONES  
2=HISTORY  
3=WALKTEST  
Note that in the two preceding screens, an arrow appears to inform the programmer that additional  
options can be viewed by pressing the keypad down arrow key.  
48  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5 Master Programming Level  
When the Master Program Level password is entered, the control panel will enter user  
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and  
the system Trouble indicator flashes until Programming mode is exited. The following display will  
appear:  
PROGRAMMING  
1=FACP CONFIG  
T6  
2=INPUT ZONES  
3=OUTPUT CIRCUITS  
Programming Screen #1  
The down arrow which appears in the display indicates that additional programming choices can be  
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the  
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as  
illustrated below while pressing the ‘up’ arrow key will display the previous screen.  
PROGRAMMING  
1=CROSS INPUT ZONES  
2=ON-BOARD RELAYS  
3=SYSTEM SETUP  
Programming Screen #2  
PROGRAMMING  
1=ANN-BUS  
2=HISTORY 256 EVENTS  
3=WALKTEST  
Programming Screen #3  
PROGRAMMING  
1=CLEAR PROGRAM  
2=PASSWORD CHANGE  
Programming Screen #4  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
49  
Programming  
Master Programming Level  
3.5.1 FACP CONFIG (Application Templates)  
For a detailed description of each Template, refer to "FACP Configuration Templates" on page  
108. The FACP Configuration option allows the user to program the FACP with one of seven  
factory preprogrammed templates or one custom template which can be programmed by the user.  
The templates have been provided to allow the user to quickly program the panel with typical job-  
site configurations. The user may choose to select one of the templates or bypass this option,  
proceeding to the next sections which detail customized programming of the FACP.  
PROGRAMMING  
A factory template may be chosen and later changed to better fit a site requirement. The changed  
template can be saved as the one custom template.  
1=FACP CONFIG USER  
2=INPUT ZONES  
3=OUTPUT CIRCUITS  
Pressing 1, while viewing Programming Screen #1, will select the FACP Config option and display  
Programming Screen #1  
the following screen:  
FACP CONFIG  
1=N/A  
2=N/A  
3=N/A  
FACP Config Screen #1  
Pressing the down arrow key will display screens for additional Templates and the Custom  
Template. During initialization of the panel following power-up or reset, the selected Template will  
be displayed by the LCD.  
Note: Only Templates 7 through 13 are available for the MRP-2001/E Pre-Action/Deluge Control  
Panel.  
To select a pre-programmed templates, press the number key corresponding to the desired template.  
Note that the factory templates may pre-set most programmable features of the FACP.  
3.5.2 Input Zones  
The Input Zones option allows the user to initially program or change the programming for the six  
input zones (circuits). Pressing 2, while viewing Programming Screen #1, will select the Input  
Zones option and display a screen similar to the following:  
INPUT ZONES  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
Input Zone Screen #1  
Pressing the down arrow key will display additional screens for Input Zones 4 through 6. To  
program a specific zone, press the number key corresponding to the desired zone while viewing one  
of the Input Zone screens.  
To program Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following  
screens will be displayed:  
INPUT ZONE 1  
Normal PULL STATION  
PRESS TO EDIT  
Edit Input Zone Screen #1  
50  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to  
view the Edit Zone screens.  
The following examples show the editing of Input Zone 1:  
INPUT ZONE 1  
1=ENABLED  
YES  
2=TYPE PULL STATION  
3=OUTPUT CIRCUIT MAP  
Edit Input Zone Screen #2  
INPUT ZONE 1  
1=NOUN/ADJECTIVE  
2=DESCRIPTION  
********************  
Edit Input Zone Screen #3  
Enable/Disable Zone  
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2.  
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled  
No is selected, the zone will be disabled by the control panel, preventing the circuit from  
reporting alarms and troubles to the panel. The control panel LCD will display the zone which  
has been disabled and FACP will turn on the Trouble indicator.  
Type  
INPUT ZONE  
1=ENABLED  
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone  
Screen #2. This will cause the control panel to display the following Zone Type Screen:  
2=TYPE  
3=OUTPUT CIRCUIT MAP  
Edit Input Zone Screen #2  
ZONE 1 TYPE  
1=PULL STATION  
2=N/A  
3=MANUAL RELEASE  
Zone Type Screen #1  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
51  
Programming  
Master Programming Level  
Pressing the down arrow key displays additional zone types as indicated in the following table.  
Table 3.1 Zone Types  
Zone Type  
Action When Activated  
Fire Alarm  
Pull-Station  
Manual Release1  
Fire Alarm  
Normally Open Contact  
Fire  
N/A  
N/A  
Waterflow  
Fire  
Waterflow NS (nonsilenceable)  
Combo  
Fire, nonsilenceable  
Fire/Supervisory  
Combo w/AutoResettable Superv2  
Fire/Supervisory, nonlatching  
2-Wire Smoke  
2-Wire Heat  
Linear Heat  
N/A  
Fire Alarm  
Fire Alarm  
Fire Alarm  
N/A  
Fire  
Fire Alarm  
Low Pressure  
Supervisory, latching  
Supervisory, nonlatching  
Low Pressure AutoResettable2  
High Pressure  
Supervisory  
High Pressure AutoResettable2  
Supervisory, nonlatching  
Disable Release3  
Supervisory  
Supervisory, nonlatching (disables Release Circuits)  
Supervisory, latching  
Supervisory AutoResettable2  
N/A  
Supervisory, nonlatching  
2nd-Shot Water Switch4  
Fire Alarm, nonlatching  
Table Footnote  
1. Activation of a Manual Release Switch will override Predischarge Delay,  
resulting in an immediate water release.  
2. AutoResettable means that a device with this type code, when activated, will  
automatically reset when the corresponding condition is cleared.  
3. Disable Release allows the installer to disable the releasing solenoids during  
system testing. Disable Release will only work when the system is not in alarm.  
4. The 2nd-Shot Water Switch provides the option of performing another immediate  
water release manually. Refer to "2nd-Shot Water Switch" on page 90.  
While viewing any Zone Type screen, select the type of zone being programmed by pressing the  
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and  
indicate the selection next to the Type option.  
52  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
Output Circuit MAP  
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits  
that will be activated when a particular Input Zone or cross-zoned releasing group goes active.  
Pressing 3 for Output Circuit Map while viewing Edit Input Zone Screen #2 will display  
screens which show the Output Circuits programmed to activate when the selected Input Zone  
(or cross-zoned releasing group) is activated. Output Map Screen #1 displays the Output Type  
Codes and programming for Output Circuits 1 through 3 and Output Map Screen #2 displays  
the Output Type Code and programming for Output Circuit 4.  
INPUT ZONE #  
1=ENABLED  
As an example, if Template 6 has been selected as the FACP Configuration [refer to "FACP  
CONFIG (Application Templates)" on page 50], selecting the Output Circuit Map for Input  
Zone 1 will display the following screens:  
2=TYPE  
3=OUTPUT CIRCUIT MAP  
Edit Input Zone Screen #2  
OUTPUT MAP ZONE 1  
1=ALARM NAC  
2=WATERFLOW NAC NO  
3=RELEASE 1 YES  
YES  
Output Map Screen#1  
OUTPUT MAP ZONE 1  
4=SUPV BELL NAC N/A  
Output Zone Screen#2  
The screens indicate that when Input Zone 1 is activated:  
Output Circuit #1 default programmed as Alarm NAC will activate (Yes)  
Output Circuit #2 default programmed as Waterflow NAC will not activate (No)  
Output Circuit #3 default programmed as Release 1 will activate (Yes)  
Output Circuit #4 default programmed as Supv Bell NAC is not mapped (N/A)  
Note that the MAP may indicate that an Input Zone is programmed to a particular Output  
Circuit but, if it is cross-zoned with one or more other Input Zones, all must be active in order to  
activate the Output Circuit. Refer to the examples in "Circuit Mapping and Cross-Zoning" on  
page 103.  
The Output Circuit Map can be customized by selecting or deselecting any of the four output  
circuits for activation. Pressing the number key corresponding to the selected output will toggle  
the display between Yes for activation by the Input Zone to No for no activation. The new  
customized programming is automatically saved by the panel as soon as it is entered.  
INPUT ZONE #  
1=NOUN/ADJECTIVE  
2=DESCRIPTION  
Noun/Adjective  
The Noun/Adjective selection allows the programmer to enter specific descriptors about the  
detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #3 will  
cause the following screen to be displayed:  
*****************  
Edit Input Zone Screen #3  
1=STANDARD ADJECTIVE  
2=STANDARD NOUN  
Noun/Adjective Screen  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
53  
Programming  
Master Programming Level  
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be  
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective  
screens. Press the number corresponding to the adjective that is to be used as a descriptor for  
the location of the detector currently being programmed. When an adjective has been selected,  
it will appear at the top of the display as indicated by the asterisks.  
**********************  
**********************  
1=3RD  
2=4TH  
3=5TH  
1=NORTH  
2=SOUTH  
3=EAST  
Adjective Screen #5  
Adjective Screen #1  
**********************  
1=FLOOR1  
2=FLOOR2  
**********************  
1=WEST  
2=FRONT  
3=FLOOR3  
3=CENTER  
Adjective Screen #6  
Adjective Screen #2  
**********************  
1=REAR  
2=UPPER  
**********************  
1=FLOOR4  
2=FLOOR5  
3=LOWER  
3=ROOM  
Adjective Screen #3  
Adjective Screen #7  
*********************  
1=MAIN  
2=FIRST  
3=2ND  
Adjective Screen #4  
54  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be  
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.  
Press the number corresponding to the noun that is to be used as a descriptor for the location of  
the detector currently being programmed. When a noun has been selected, it will appear at the  
top of the display as indicated by the asterisks.  
**********************  
1=HVAC RM  
2=ISLAND  
**********************  
1=BASEMENT  
2=BOILER RM  
3=KITCHEN  
3=CLASSROOM  
Noun Screen #4  
Noun Screen #1  
**********************  
1=COMPUTER RM  
2=CONTROL RM  
**********************  
1=ROOM  
2=STOREROOM  
3=DATA ROOM  
3=TELCO ROOM  
Noun Screen #2  
Noun Screen #5  
**********************  
1=UPS ROOM  
2=VAULT  
**********************  
1=DOCUMENT RM  
2=ELECTRIC RM  
3=GARAGE  
Noun Screen #6  
Noun Screen #3  
Description  
INPUT ZONE #  
1=NOUN/ADJECTIVE  
2=DESCRIPTION  
The Description selection allows the programmer to enter additional information about the  
detector currently being programmed. This information will be displayed as part of the device  
label on the display. Pressing 2 while viewing Edit Input Zone Screen #3 will cause the  
following screen to be displayed:  
Edit Input Zone Screen #3  
ZONE # DESCRIPTION  
PRESS ENTER IF DONE  
********************  
Adjective/Noun Screen  
A flashing cursor will appear at the first asterisk to the left. The programmer can enter  
additional descriptive information about the device being programmed. This information will  
appear on the display along with the standard device label information.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
55  
Programming  
Master Programming Level  
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric  
characters from the keypad, repeatedly press the appropriate key until the desired character is  
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three  
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor  
one position to the right and repeat the process to enter the next character. To enter a space,  
press the * (QZ) key four times until a blank appears in the desired position. When all  
characters have been entered, press the Enter key to store the information. The display will  
return to the Edit Detector Screen #5, displaying the new information at the bottom of the  
screen.  
Recall/Increment Function  
In addition, the user may use the Recall/Increment function at any time when the cursor is on  
the first letter of the Description, Adjective or Noun field as follows:  
If the zero key is pressed, a 0 is placed in the first letter position  
If the zero key is then pressed a second time with no intervening key actions, the entire field  
is replaced with the field entered for the previous device programmed, and the cursor moves  
to the last character of the field (Recall function). The Recalled Adjective or Noun field may  
now be changed letter-by-letter  
If the zero key is pressed again with no other intervening key actions and the last character in  
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it  
changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last  
character are also numbers, they are also incremented (overflow)  
The above increment function may be repeated with each press of the zero key  
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:  
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display  
FLR_3  
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the  
display ROOM_304. The cursor automatically jumps from the first to the last letter of the  
Noun field  
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the  
room number to 305  
4. Press the Enter key to store the information  
56  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.3 Output Circuits  
The options for the Output Circuits on the control panel main circuit board can be configured by  
pressing 2 while viewing Programming Screen #2. The following screens will be displayed:  
OUTPUT CIRCUITS  
1=OUTPUT 1  
2=OUTPUT 2  
3=OUTPUT 3  
PROGRAMMING  
1=FACP CONFIG  
2=INPUT ZONES  
3=OUTPUT CIRCUITS  
NAC Selection Screen  
OUTPUT CIRCUITS  
1=OUTPUT 4  
Programming Screen #1  
NAC Selection Screen  
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3  
for Output 3 or 4 for Output 4.  
To program an Output circuit, press the number corresponding to the Output to be programmed.  
The following screens will be displayed for each selection:  
OUTPUT #  
1=ENABLED  
2=TYPE  
YES  
ALARM NAC  
Output Screen #1  
OUTPUT #  
1=SILENCE  
2=AUTO SILENCE  
3=SIL INHIBIT  
NON-SIL  
NO  
NO  
Output Screen #2  
OUTPUT #  
1=CODING  
STEADY  
Output Screen #3  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
57  
Programming  
Master Programming Level  
3.5.3.1 Enabled  
Pressing 1 while viewing Output Screen #1 will cause the display to change to Enabled No.  
This will prevent the selected main circuit board NAC from activating its devices. Each press  
of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.  
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is  
enabled. The exception is when a Release Circuit is disabled, a supervisory will be logged on  
the FACP until the circuit is enabled.  
NAC #  
3.5.3.2 Type  
1=ENABLED  
2=TYPE  
Pressing 2 while viewing Output Screen #1 will cause the following screen to be displayed:  
ALARM NAC  
NAC Screen #1  
EDIT OUTPUT # TYPE  
1=RELEASE CIRCUIT 1  
2=RELEASE CIRCUIT 2  
3=ALARM NAC  
Edit Output # Type Screen  
Pressing the down arrow key while viewing the Edit Output Type Screen will display additional  
screens with the types shown in the following table:  
Release Circuit 1  
Release Circuit 2  
Alarm NAC  
Waterflow NAC  
Release Stage NAC  
Horn NAC  
Strobe NAC  
Supv Bell NAC  
Trouble Bell NAC  
Press the number key corresponding to the desired Output Type to program the selected Output.  
3.5.3.2.1 Release Circuit 1 or Release Circuit 2  
If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen  
will be displayed:  
EDIT RELEASE CIR #  
1=UNSUPV SHORTS  
2=SUPV SHORTS  
This screen allows the programmer to select whether or not to supervise the Releasing Circuit  
Output for shorts.  
When a normally-closed releasing solenoid is connected to the output circuit, pressing 1 will  
prevent the FACP from supervising the output circuit for shorts.  
When a normally-open releasing solenoid is connected to the output circuit, pressing 2 will  
allow the FACP to supervise the output circuit for shorts.  
Note: Release circuits may be directly activated by a single input zone or may be activated using  
cross-zoned inputs. Refer to "Circuit Mapping and Cross-Zoning" on page 103 for a description of  
cross-zoning and input to output circuit mapping.  
58  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.3.2.2 Release Stage NAC  
If Release Stage NAC is selected as the Output Type, the following subscreen will be displayed:  
RELEASE STAGES  
1=RELEASE 1 ONLY  
2=RELEASE 2 ONLY  
An NAC can be used to signal the two stages of a release operation. This screen allows the  
programmer to select the NAC output that will indicate the release stages for Release Circuit 1  
or Release Circuit 2. For a description of this feature, refer to "Release Stages" on page 91.  
OUTPUT #  
3.5.3.3 Silence  
1=SILENCE NON-SIL  
2=AUTO SILENCE NO  
3=SIL INHIBITED NO  
Pressing 1 while viewing Output Screen #2 will cause the following screen to be displayed:  
Output Screen #2  
SILENCEABLE  
1=SILENCEABLE  
2=NON SILENCEABLE  
3=SYNC MUTE  
Silenceable Screen  
Pressing 1 while viewing the Silenceable Screen will program the selected Output as a  
silenceable circuit. This will allow the Output to be silenced by pressing the Alarm Silence key  
or by the Auto Silence feature.  
Pressing 2 while viewing the Silenceable Screen will program the selected Output as a  
nonsilenceable circuit. This will prevent the selected main circuit board Output from being  
silenced by pressing the Alarm Silence key or by the Auto Silence feature.  
Pressing 3 while viewing the Silenceable Screen will program the selected Output as a  
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 62 for a  
description of synchronization.  
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Silenceable  
Option will not be available and the display will indicate N/A next to it.  
Important: When an Output Circuit with a mix of audible and visual devices is programmed for  
Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the  
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
59  
Programming  
Master Programming Level  
3.5.3.4 Auto Silence  
The Auto Silence feature, when enabled, automatically silences all main circuit board  
silenceable notification appliances after a programmed length of time. To enable this feature  
and program the time delay before Auto Silence activation, press 2 while viewing Output  
Screen #2. The following screens will be displayed:  
AUTO SILENCE  
1=NO  
2=5 MINUTES  
3=10 MINUTES  
Auto Silence Screen #1  
AUTO SILENCE  
1=15 MINUTES  
2=20 MINUTES  
3=25 MINUTES  
Auto Silence Screen #2  
AUTO SILENCE  
1=30 MINUTES  
Auto Silence Screen #3  
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To  
enable the Auto Silence feature, press the number corresponding to the time delay which will  
elapse before Auto Silence activates. This information will be stored in memory and the  
display will return to NAC Screen #1.  
OUTPUT #  
1=SILENCEABLE YES  
2=AUTO SILENCE NO  
3=SIL INHIBITED NO  
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence  
Option will not be available and the display will indicate N/A next to it.  
Output Screen #2  
3.5.3.5 Silence Inhibited  
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit  
board Output for a period of one minute. Resetting the FACP will also be prevented for one  
minute while the Output programmed for silence inhibit is activated. Pressing 3 while viewing  
Output Screen #2 will cause a screen to be displayed with the options 1=No Silence Inhibit and  
2=1 Min. Silence Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2  
will enable a 1 minute Silence Inhibit for the selected Output.  
60  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.3.6 Coding  
The Coding feature allows the programmer to select the type of output that the main circuit  
board outputs will generate when activated. Pressing 1 while viewing Output Screen #3 will  
cause the following displays to appear:  
CODING  
1=STEADY  
OUTPUT #  
1=CODING  
2=MARCH TIME  
3=CALIFORNIA  
Coding Screen #1  
Output Screen #3  
CODING  
1=TEMPORAL  
2=FUTURE USE  
3=FUTURE USE  
Coding Screen #2  
CODING  
1=CROSS ZONE  
2=SYNC SYSTEM SENSOR  
3=SYNC WHEELOCK  
Coding Screen #3  
CODING  
1=SYNC GENTEX  
2=SYNC FARADAY  
3=SYNC AMSECO  
Coding Screen #4  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61  
Programming  
Master Programming Level  
The programmer can select the notification appliance output coding by pressing the number  
corresponding to the desired output. The coding selections are:  
Steady - a continuous output with no coding  
March Time - 120 ppm (pulse-per-minute) output  
California - 10 seconds on and 5 seconds off  
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second  
off  
Cross-Zone:  
1st zone of a cross-zoned group in alarm causes programmed NAC output to pulse 1  
second on and 1 second off  
2nd zone of a cross-zoned group in alarm causes programmed NAC output to pulse ½  
second on and ½ second off - Note: if more than three zones are cross-zoned, the  
programmed NAC output will continue to pulse ½ second on and ½ second off for each  
subsequent zone in alarm, until the final zone in the cross-zoned group goes into alarm  
All zones of a cross-zoned group in alarm causes the output programmed as a Releasing  
Circuit to perform a release and the programmed NAC output to turn on steady  
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to  
"Synchronized NAC Operation" on page 62 for additional information.  
Selection of one of the above options will cause the control panel to store the information in  
memory and return the display to Output Screen #1, which will display the new coding choice.  
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Coding Option  
will not be available and the display will indicate N/A next to it.  
3.5.3.6.1 Synchronized NAC Operation  
Synchronization is a panel feature that controls the activation of notification appliances in such  
a way that all devices will turn on and off at exactly the same time. This is particularly critical  
when activating strobes which must be synchronized to avoid random activation and a potential  
hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s  
devices.  
Notes:  
1. The NAC1 output can be used to synchronize notification appliances connected to external  
panels such as remote power supplies.  
2. For Dual Hazard applications, NAC circuits are not synchronized.  
3.5.3.6.1.1 Maximum Number of Strobes for Synchronization  
The maximum current draw for a Notification Appliance Circuit cannot exceed 3.0 amps.  
Refer to the manufacturer’s documentation supplied with the Strobes to determine the  
maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.  
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that  
can be attached to each circuit. Following is a list of the strobes that have been tested with this  
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC  
maximum current is not exceeded:  
System Sensor: 46 Strobes  
Wheelock: 50 Strobes  
Gentex: 39 Strobes  
Faraday: 33 Strobes  
Amseco: 34 Strobes  
62  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.4 Cross Input Zones  
An application may require that two or more input zones become active at the same time before a  
particular releasing output activates. This is referred to as cross-zoning. For example, an installer  
may want four particular zones to become active at the same time before a releasing circuit is  
activated. By using the Cross Input Zone feature, the programmer can designate the input zones  
that must become active and the output circuits that will be affected.  
The Cross Input Zone option allows the user to view and program the groups of input zones that  
will be used to activate one of the releasing output circuits. Pressing 1 while viewing Programming  
Screen #2 will display a screen similar to the following:  
PROGRAMMING  
1=CROSS INPUT ZONES  
2=ON-BOARD RELAYS  
3=SYSTEM SETUP  
CROSS INPUT ZONES  
1=RELEASE 1 GROUPS  
2=RELEASE 2 GROUPS  
Programming Screen #2  
This screen allows the programmer to view the cross-zoned grouping for Release Circuit 1 or  
Release Circuit 2. In the following example, Template 7 has been chosen as the FACP  
Configuration [refer to "FACP CONFIG (Application Templates)" on page 50]. Pressing 1 for  
Release 1 Groups will display the following screen:  
REL 1 CROSS GROUPS  
1=  
2=  
3=  
X 1 2  
NONE  
NONE  
The display indicates that Input Zone 1 is cross-zoned with Input Zone 2. Input Zone 3 is not cross-  
zoned.  
The user can alter the cross-zoning by pressing the number key corresponding to the Zone to be  
reprogrammed. Screens similar to the following will be displayed:  
REL 1 CROSS GROUP 1  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
YES  
YES  
NO  
Select Cross Zone Screen #1  
REL 1 CROSS GROUP 1  
1=ZONE 4  
2=ZONE 5  
NO  
NO  
3=ZONE 6  
N/A  
Select Cross Zone Screen #2  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
63  
Programming  
Master Programming Level  
In this example, since the cross-zoning for Release Circuit 1 (Zone 1) is being displayed, Yes is  
shown for Zone 1 which is cross-zoned with Zone 2. Zone 2 displays Yes since it is cross-zoned  
with Zone 1. The remaining zones display NO or N/A for no cross-zoning to Zone 1. By pressing  
the number key corresponding to the desired zone, the display for that zone will toggle between Yes  
and No indicating cross-zoning to Zone 1 or no cross-zoning to Zone 1.  
3.5.5 On-Board Relays  
Pressing 2 while viewing Programming Screen #2 will allow the programmer to configure the three  
main circuit board Form-C relays. The following screen will be displayed:  
ON-BOARD RELAYS  
1=RELAY 1  
2=RELAY 2  
3=RELAY 3 SUPERVSRY  
ALARM  
TROUBLE  
Relays Selection Screen  
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following  
screens will appear for each relay to be programmed:  
RELAY TYPE  
1=ALARM  
2=TROUBLE  
RELAY TYPE  
1=FUTURE USE  
2=DISCHARGE  
3=AC LOSS  
3=SUPERVISORY  
Relay Screen #1  
Relay Screen #2  
While viewing the selected screen, press the number corresponding to the desired relay type to  
program the main circuit board relay. The choice will be stored in memory and the display will  
return to the Relay Type Screen which will show the programmed type choice. Press the Escape  
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining  
relays.  
3.5.6 System Setup  
System Setup allows the programmer to configure the following control panel features:  
Abort Type: Future Use  
Timers: This option allows the programmer to set the Soak 1, Soak 2, Waterflow and AC  
Loss time delays.  
Banner: This option allows the user to change the top two lines of the LCD display from the  
factory default readout to a user defined readout when the control panel is in Normal  
condition.  
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12  
hr), date and daylight savings time feature into the FACP memory  
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or  
trouble still exists on the FACP after the control panel has been silenced. The control panel  
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes  
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The  
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If  
the Trouble Reminder feature is not enabled and a trouble condition is not cleared within 24  
hours, the panel will reactivate the trouble sounder an send an Abnormal 24 hour Test  
message via the optional communicator.  
Charger Disable: This option allows the programmer to disable the onboard battery charger  
in the event an external battery charger is being used.  
64  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following  
screens to be displayed:  
SYSTEM SETUP  
1=FUTURE USE  
2=TIMERS  
3=BANNER  
PROGRAMMING  
1=CROSS INPUT ZONES  
2=ON-BOARD RELAYS  
3=SYSTEM SETUP  
System Setup Screen #1  
Programming Screen #2  
SYSTEM SETUP  
1=TIME-DATE  
2=TROUBLE REMIND NO  
3=CHARGR DISABLE NO  
System Setup Screen #2  
SYSTEM SETUP  
1=ABORT TYPE  
2=TIMERS  
3.5.6.1 Timers  
Timers for Soak, Waterflow Delay and AC Loss Delay can be programmed by pressing 2 while  
viewing System Setup Screen #1. The following screen will be displayed:  
3=BANNER  
System Setup Screen #1  
TIMERS  
1=SOAK 1  
2=SOAK 2  
3=WATERFLOW DELAY 60S  
1 MIN  
2 MIN  
Timer Screen #1  
TIMERS  
1=AC LOSS DELAY 2 HR  
Timer Screen #2  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
65  
Programming  
Master Programming Level  
3.5.6.1.1 Soak 1 or Soak 2  
The factory default setting for Soak Time is 10 minutes. To select a Soak Time delay of 10 to  
30 minutes, press 1 for Soak 1 (Release Circuit 1) or 2 for Soak 2 (Release Circuit 2) while  
viewing Timer Screen #1. The following display will appear:  
SOAK # TIME  
1=ALWAYS ON  
2=ENTER MINUTES  
Soak Time Setup Screen  
Pressing 1 while viewing the Soak Time Setup Screen will program the corresponding releasing  
circuit to remain on during alarm activation until the alarm is cleared and the panel is reset.  
Pressing 2 while viewing the Soak Time Setup Screen will display the following screen:  
SOAK # TIME  
RANGE 10-30 MINUTES  
Soak Time Screen  
This screen allows the user to program a specific length of time for the releasing circuit to  
remain active after an input initiating a release has cleared. A flashing cursor is positioned in  
the lower left corner of the display. Enter a soak time consisting of two digits, such as 10 for ten  
minutes. Upon entering the second digit, the time delay will be stored in the control panel  
memory and the display will return to the Delay Screen which will indicate the new soak time.  
In this example, when the input circuit which initiated a release has cleared, the soak timer will  
start, allowing the releasing circuit to continue releasing water for a total of ten minutes and  
then deactivate.  
TIMER  
3.5.6.1.2 Waterflow Delay  
1=SOAK 1  
2=SOAK 2  
1 MIN  
2 MIN  
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any  
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 00  
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for  
Waterflow delay, press 3 while viewing Timer Screen #1 to display the following screen:  
3=WATERFLOW DELAY 0 S  
Timer Screen #1  
WATERFLOW DELAY  
RANGE 00-90 SECONDS  
Waterflow Delay Screen  
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time  
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the  
time delay will be stored in the control panel memory and the display will return to the Delay  
Screen which will indicate the new delay time.  
66  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.6.1.3 AC Loss Delay  
The reporting of a loss of AC power can be delayed by programming the length of the desired  
delay. Press 1 while viewing Timer Screen #2 to display the following:  
AC LOSS DELAY  
RANGE 00-24 HOURS  
TIMER  
1=AC LOSS DLAY 2 HR  
AC Loss Delay Screen #1  
A flashing cursor will appear in the lower left corner of the display. The factory default setting  
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When  
the second digit is entered, the display will return to AC Loss Delay Screen #1.  
Timer Screen #2  
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will  
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC  
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC  
Loss Delay setting.  
SYSTEM SETUP  
1=ABORT TYPE  
2=TIMERS  
3=BANNER  
3.5.6.2 Banner  
System Setup Screen #1  
The top line of the display, which appears when the control panel is in normal mode, can be  
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will  
cause the following to be displayed:  
SELECT BANNER  
1=FACTORY BANNER  
2=USER BANNER  
Select Banner Screen  
Pressing 1 while viewing the Select Banner Screen will display the following screen:  
FACTORY BANNER  
PRESS ENTER IF OK  
User Defined Banner Screen #1  
This screen allows the user to select the factory default Banner which will be displayed when  
the system is in Normal Mode of operation. Press the Enter key to accept this as the default  
display. Press the Escape key to cancel and return to the Select Banner Screen.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
67  
Programming  
Master Programming Level  
Pressing 2 while viewing the Select Banner Screen will display the following screen:  
USER BANNER-LINE 1  
PRESS ENTER IF OK  
User Defined Banner Screen  
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in  
the bottom left corner of the display. A maximum of 20 characters (including spaces) can be  
entered into the screen. After entering up to 20 characters in the screen, press Enter to store the  
entry. To quickly clear the current banner, press the CLR key.  
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until  
the desired character is displayed in the first position. For example, to enter the letter B, press  
the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow  
key to move the cursor one position to the right and repeat the process to enter the next  
character. To enter a space, press the * (QZ) key four times to place a blank in the desired  
position. When all characters have been entered, press the Enter key to store the information.  
The display will return to the Select Banner Screen.  
3.5.6.3 Time-Date  
The control panel time and date can be changed by pressing 1 while viewing the System Setup  
Screen #2. The following screen will be displayed:  
TIME AND DATE  
1=TIME 10:00A  
2=DATE 04072006  
3=CLOCK FORMAT 12HR  
SYSTEM SETUP  
1=TIME-DATE  
2=TROUBLE REMIND  
3=CHARGR DISABLE  
System Setup Screen #2  
Time-Date Screen #1  
TIME AND DATE  
1=DAYLIGHT SAVINGS  
Time-Date Screen #2  
68  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.6.3.1 Time  
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be  
displayed:  
ENTER TIME AS 12HRS  
:
10:00  
1=AM  
2=PM  
Time Screen  
A flashing cursor is located toward the top left of the display. Below the cursor is the current  
time. To change the time, enter the two-digit hours followed by the two-digit minutes. The  
cursor will move one position to the right each time a digit is entered. After the last minutes  
digit is entered, the cursor will again move one position to the right. At this point enter 1 for  
AM or 2 for PM. The display will then return to the Time-Date Screen which will show the  
new time entry. If an error is made while entering a digit, press the CLR key to delete the entire  
entry and beginning again.  
3.5.6.3.2 Date  
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be  
displayed:  
ENTER DATE  
**-**-****  
MONTH DAY YEAR  
04-07-2006  
Date Screen  
A flashing cursor is located toward the top left of the display. Below the cursor is the current  
date. To change the date, enter the two-digit month followed by the two-digit day and then the  
two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right  
each time a digit is entered. After the last year digit is entered, the display will return to the  
Time-Date Screen which will show the new date entry. If an error is made while entering a  
digit, press the CLR key to delete the entire entry and beginning again.  
3.5.6.3.3 Clock Format  
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time.  
Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR  
and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.  
Note: If the clock is changed to 24 hour (military) format, the date will change to the European  
standard of Day-Month-Year (for display purposes only).  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
69  
Programming  
Master Programming Level  
3.5.6.3.4 Daylight Savings Time  
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:  
DAYLIGHT SAVINGS  
1=ENABLED  
2=START MONTH MAR  
3=START WEEK WK 2  
YES  
TIME AND DATE  
1=DAYLIGHT SAVINGS  
Daylight Savings Screen #1  
Time & Date Screen #2  
DAYLIGHT SAVINGS  
1=END MONTH  
2=END WEEK  
NOV  
WK 1  
Daylight Savings Screen #2  
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between  
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight  
savings time when Enabled Yes is selected.  
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows  
the programmer to select the month that daylight savings time will begin. In this sub-screen,  
pressing 1 will select March, 2 will select April and 3 will select May.  
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow  
the programmer to select the week of the month that daylight savings time will begin. In the  
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will  
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and  
2 will select the last week of the selected month.  
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows  
the programmer to select the month that daylight savings time will end. In this sub-screen,  
pressing 1 will select September, 2 will select October and 3 will select November.  
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow  
the programmer to select the week of the month that daylight savings time will end. In the first  
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select  
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will  
select the last week of the selected month.  
SYSTEM SETUP  
1=TIME-DATE  
3.5.6.4 Trouble Reminder  
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for  
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 64, for  
a detailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will  
cause the display to toggle to Trouble Remind Yes, which enables this feature. Each press of the  
2 key will cause the display to toggle between Trouble Remind Yes and Trouble Remind No.  
2=TROUBLE REMIND  
3=CHARGR DISABLE  
System Setup Screen #2  
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for  
more than 24 hours will cause the FACP to resound the trouble sounder.  
3.5.6.5 Charger Disable  
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or  
disable the onboard battery charger. If an external battery charger is being used, the onboard  
battery charger must be disabled. Each press of the 3 key will toggle between Chargr Disable  
No and Chargr Disable Yes.  
70  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.7 ANN-BUS  
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and  
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing  
Programming Screen #3 will cause the control panel to display the following screens.  
PROGRAMMING  
1=ANN-BUS  
ANN-BUS  
2=HISTORY  
1=BUS ENABLED  
2=BUS MODULES  
3=AUTO CONFIGURE  
NO  
3=WALKTEST  
Programming Screen #3  
ANN-BUS Screen #1  
ANN-BUS  
1=ANN-S/PG OPTIONS  
2=ANN-I/O OPTIONS  
3=ANN-80 OPTIONS  
ANN-BUS Screen #2  
ANN-BUS  
1=ANN-RLY OPTIONS  
2=ANN-LED OPTIONS  
ANN-BUS Screen #3  
An ANN-S/PG Printer module, ANN-I/O module, ANN-80 LCD annunciator module, ANN-  
RLY relay module and ANN-LED module can be installed in the FACP. These devices  
communicate with the FACP over the ANN-BUS terminals on the control panel.  
3.5.7.1 ANN-BUS Enabled  
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To  
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads  
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-  
BUS Enabled Yes and ANN-BUS Enabled No.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
71  
Programming  
Master Programming Level  
3.5.7.2 ANN-BUS Modules  
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select  
ANN-BUS addresses for the module(s). The following screen will be displayed.  
ANN-BUS MODULES  
1=ADDR. 1 NONE  
2=ADDR. 2 NONE  
3=ADDR. 3 NONE  
On Board DACT Screen #1  
Pressing the down arrow key will allow the programmer to view additional screens displaying  
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen  
with technical information about the selected module.  
In the technical information screen, pressing 1 for Type will display the following screens:  
ANN-BUS MODULE TYPE  
1=NONE  
2=ANN-80  
3=ANN-I/O  
Module Type Screen #1  
ANN-BUS MODULE TYPE  
1=ANN-S/PG  
2=ANN-RLY  
3=ANN-LED  
Module Type Screen #2  
Press the number corresponding to the module type, if any, that is installed with the selected  
address. This will enable the module.  
72  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.7.3 Auto-Configure  
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed  
ANN-BUS modules online. The software will search for all ANN-BUS modules and  
automatically program the device type and address into the system. Pressing 3 while viewing  
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to  
be displayed:  
ANN-BUS  
AUTO-CONGFIGURE  
IN PROGRESS  
PLEASE WAIT  
Auto-Configure Screen  
PROGRAMMING  
3.5.7.4 ANN-S/PG Options  
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing  
the ANN-BUS Screen #2 will display the following screens:  
1=ANN-S/PG OPTIONS  
2=ANN-I/O OPTIONS  
3=ANN-80 OPTIONS  
ANN-BUS Screen #2  
ANN-S/PG OPTIONS  
1=PORT PARALLEL  
2=PRINTER SUPV NO  
3=OFFLINE TIMER  
60  
Printer Options Screen #1  
ANN-S/PG OPTIONS  
1=BAUD RATE  
2=DATA BITS  
3=PARITY  
N/A  
N/A  
N/A  
Printer Options Screen #2  
ANN-S/PG OPTIONS  
1=STOP BITS N/A  
Printer Options Screen #3  
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select  
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the  
display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that  
the interface selected determines which options are available to the user.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
73  
Programming  
Master Programming Level  
If the Parallel Port option is selected, the user has the option to supervise the printer and select  
an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print  
Options screen #1. Each press of the 2 key will cause the display to toggle between Printer  
Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option  
is not selectable if the Serial Port option has been selected.  
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by  
pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer  
to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer  
supervision is reported as a trouble.  
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be  
available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the  
Serial Port option has been selected.  
Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear  
which allow the user to select a Baud Rate of 19200, 9600 or 2400.  
Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear  
which allow the user to select 5, 6, 7 or 8 Data Bits.  
Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear  
which allows the user to select between No Parity, Even Parity or Odd Parity.  
Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear  
which allows the user to select between 0.5, 1.0 or 2.0 Stop Bits.  
74  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.7.5 ANN-I/O LED Zone Assignments  
The information displayed by LEDs on every ANN-I/O module is not programmable and will  
therefore be as indicated in the following table.  
LED  
1
Zone (any address)  
AC Fault  
2
3
4
5
General Alarm  
General Supervisory  
General Trouble  
Alarm Silenced  
Earth Fault  
6
7
8
9
Battery Fault  
Charger Fault  
Disable  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
Maintenance  
Zone 1 Alarm  
Zone 2 Alarm  
Zone 3 Alarm  
Zone 4 Alarm  
Zone 5 Alarm  
Zone 6 Alarm  
Not Used  
Not Used  
Not Used  
Not Used  
Zone 1 Trouble  
Zone 2 Trouble  
Zone 3 Trouble  
Zone 4 Trouble  
Zone 5 Trouble  
Zone 6 Trouble  
Not Used  
Not Used  
Not Used  
Not Used  
Zone 1 Supervisory  
Zone 2 Supervisory  
Zone 3 Supervisory  
Zone 4 Supervisory  
Zone 5 Supervisory  
Zone 6 Supervisory  
Not Used  
Not Used  
Not Used  
Not Used  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75  
Programming  
Master Programming Level  
3.5.7.6 ANN-80 Options  
Pressing 2 while ANN-BUS screen #2 will display the following screen:  
ANN-80 OPTIONS  
1=PIEZO ENABLE  
2=LOCK ENABLE  
3=ACK BTN ENABLE  
ANN-80 Options Screen #1  
ANN-80 OPTIONS  
1=SIL BTN ENABLE  
2=RST BTN ENABLE  
3=DRL BTN ENABLE  
ANN-80 Options Screen #2  
The Piezo Enable option allows the programmer to select whether the piezo sounder on any  
installed ANN-80 annunciator will ever sound. Pressing 1 while viewing the ANN-80 Options  
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.  
The Lock Enable option allows the programmer to select whether or not the ANN-80 LCD  
annunciator must be unlocked by its key before any annunciator key presses will function.  
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between  
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock  
position is ignored).  
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select  
whether the Ack/Step button on any installed ANN-80 LCD annunciator will function normally  
or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the  
display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack  
Btn Enable No (Ack/Step button never functions).  
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether  
the Silence button on any installed ANN-80 LCD annunciator will function normally or always  
be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to  
toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No  
(Silence button never functions).  
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether  
the Reset button on any installed ANN-80 LCD annunciator will function normally or always  
be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to  
toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No  
(Reset button never functions).  
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether  
the Drill button on any installed ANN-80 LCD annunciator will function normally or always be  
ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle  
between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill  
button never functions).  
76  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.7.7 ANN-RLY Options  
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following  
screen to be displayed:  
ANN-RLY OPTIONS  
1=RELAY 1 IN ZONE 1  
2=RELAY 2 IN ZONE 2  
3=RELAY 3 IN ZONE 3  
PROGRAMMING  
1=ANN-RLY OPTIONS  
2=ANN-LED OPTIONS  
ANN-BUS Screen #3  
ANN-RLY Options Screen  
The ANN-RLY module provides ten Form-C relays which can be programmed for various  
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will  
display the remaining relays for this module.  
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option  
screen, press the number key corresponding to the relay to be programmed. Following is a list  
of the available programming options for each relay:  
General Alarm  
General Trouble  
General Supervisory  
Future Use  
Future Use  
Future Use  
General Discharge  
Discharge Release 1  
Discharge Release 2  
AC Loss  
Waterflow Delay  
Future Use  
Future Use  
Future Use  
General 2nd Shot Release  
2nd Shot Release 1  
2nd Shot Release 2  
Input Zone 1  
Input Zone 2  
Input Zone 3  
Input Zone 4  
Input Zone 5  
Input Zone 6  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
77  
Programming  
Master Programming Level  
3.5.8 History  
The History option allows an authorized user to view or erase events which have occurred in the  
control panel. Pressing 2 while viewing Programming Screen #3 will display the History options  
as shown in the following display:  
HISTORY  
1=VIEW EVENTS  
2=ERASE HISTORY  
PROGRAMMING  
1=ANN-BUS  
2=HISTORY  
3=WALKTEST  
Programming Screen #3  
History Screen  
3.5.8.1 View Events  
Pressing 1 while viewing the History Screen will allow the user to select the events to be  
viewed as illustrated in the following:  
HISTORY  
1=VIEW ALL  
2=VIEW ALARMS  
3=VIEW OTHER EVENTS  
View Events Screen  
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3  
to view other events. Use the up and down arrow keys to scroll through all of the displayed  
events.  
3.5.8.2 Erase History  
The Erase History option allows a user to erase all events from the history file. This will  
provide a clean slate in order to use the history file to track future events. Pressing 2 while  
viewing the History Screen will display the following screen:  
ERASE HISTORY  
PROCEED ?  
1=YES  
2=NO  
Erase History Screen  
Pressing 1 while viewing the Erase History Screen will erase all events from the History file.  
During this process, the display will read as follows:  
ERASING HISTORY  
PLEASE WAIT  
Erase History Wait Screen  
After the History file has been erased, the display will return to the History Screen.  
78  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Programming Level  
Programming  
3.5.9 Walktest  
Walktest allows an individual to test the fire alarm system without the necessity to reset the control  
panel after each device activation. Pressing 3 while viewing the Programming Screen #3 will cause  
the following Walktest options to be displayed:  
WALKTEST  
1=SILENT  
2=AUDIBLE  
PROGRAMMING  
1=ANN-BUS  
2=HISTORY  
3=VIEW EVENTS  
3=WALKTEST  
Programming Screen #3  
Walktest Screen  
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest  
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the  
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the  
following screen will be displayed:  
UNIT IN WALKTEST  
Walktest Active Screen  
The user can now perform a one-person walktest by activating devices throughout the system. As  
each device is activated, the screen will display the information about the activated device as shown  
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the  
walktest screen from an actual alarm screen.  
ALARM ZONE 1  
<ADJ> <NOUN>  
Z01  
10*00A 010805  
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to  
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing  
the Walktest Screen. The following screen will be displayed:  
WALKTEST EVENTS  
Use the up and down arrow keys to view all of the walktest results which will be displayed as  
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC  
and DC) is removed from the FACP, the Walktest log information will be lost. This information is  
also overwritten when subsequent walktests are performed.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
79  
Programming  
Master Programming Level  
3.5.10 Clear Program  
Pressing 1 while viewing Programming Screen #4, will select the Clear Program option. The  
control panel will provide a warning to the user by prompting with the following display:  
WARNING!  
SYSTEM CHANGE  
PROCEED?  
PROGRAMMING  
1=CLEAR PROGRAM  
1=YES  
2=NO  
2=PASSWORD CHANGE  
Programming Screen #4  
Pressing 1 for Yes will cause the control panel to carry out the selected clear option. Pressing 2 for  
No will prevent programming from being cleared.  
3.5.11 Password Change  
The factory set passwords, which have been programmed into the control panel, can be changed by  
selecting the Password Change option. Pressing 2 while viewing Programming Screen #4 will  
cause the following screen to be displayed:  
PASSWORD CHANGE  
1=MASTER  
2=MAINTENANCE  
Password Change Screen  
Press 1 to change the Master Programming Level password or 2 to change the Maintenance Level  
password. Note that the passwords will not be displayed on annunciators.  
The following screen will appear when either change option is selected:  
ENTER NEW FIVE DIGIT  
PASSWORD  
Enter Password Screen  
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as  
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:  
VERIFY NEW  
PASSWORD  
Password Change Screen  
The new five digit password must be re-entered to accept the change. The display will then return  
to the initial Password Change Screen.  
80  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Programming Level  
Programming  
3.6 Maintenance Programming Level  
To access Maintenance Programming mode, press the Enter key. The LCD will display the  
following:  
1=READ STATUS  
2=PROGRAMMING  
To enter the Maintenance Programming mode, press 2. The display will read as follows:  
PROGRAMMING  
ENTER PASSWORD  
When the Maintenance level password (default 11111) is entered, the following screen will appear:  
PROGRAMMING  
1=INPUT ZONES  
2=HISTORY  
3=WALKTEST  
Note that in the preceding screens, an arrow appears to inform the programmer that additional  
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.  
PROGRAMMING  
1=TIME-DATE  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
81  
Programming  
Maintenance Programming Level  
3.6.1 Input Zones - Enable/Disable  
The Input Zones option allows the user to enable or disable desired zones. Pressing 1 for Input  
Zones, while viewing Maintenance Screen #1 will cause the following screens to be displayed:  
POINT PROGRAM  
1=ZONE 1  
2=ZONE 2  
PROGRAMMING  
3=ZONE 3  
1=INPUT ZONES  
2=HISTORY  
3=WALKTEST  
Zone Select Screen  
Maintenance Screen #1  
Pressing the down arrow key will display additional Zones 4 - 6. Select the number corresponding  
to the desired zone. A screen will appear which will allow enabling or disabling of the selected  
zone, as illustrated in the following example:  
INPUT ZONE 1  
1=ENABLED YES  
TYPE PULL STATION  
Enable/Disable Select Screen  
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.  
3.6.2 History  
Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:  
HISTORY  
1=VIEW EVENTS  
2=ERASE HISTORY  
History Screen  
The History feature allows the operator to view control panel events which have been stored in a  
history file in memory and erase the contents of the history file  
82  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Programming Level  
Programming  
Pressing 1 while viewing the History screen will cause the following screen to be displayed:  
HISTORY  
1=VIEW ALL  
2=VIEW ALARMS  
3=VIEW OTHER EVENTS  
To view all the events which have occurred in the control panel since the history file was last  
erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2  
while viewing the Events screen. To view events other than alarms, press 3. The most recent event  
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys  
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS  
IN HISTORY.  
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:  
ERASE HISTORY  
PROCEED ?  
1=YES  
2=NO  
Erase History Screen  
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY,  
PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will  
cause the display to return to the History Screen without erasing the History file.  
3.6.3 Walktest  
PROGRAMMING  
1=INPUT ZONES  
2=HISTORY  
To perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be  
displayed:  
3=WALKTEST  
Maintenance Screen #1  
WALKTEST  
1=SILENT  
2=AUDIBLE  
3=VIEW EVENTS  
Walktest Screen  
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The  
display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.  
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the  
walktest.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
83  
Programming  
Maintenance Programming Level  
3.6.4 Time-Date  
To program the time and date into the control panel, press 1 while viewing Maintenance Screen #2.  
The following display will appear:  
TIME AND DATE  
1=TIME  
2=DATE  
3=CLOCK FORMAT 12HRS  
01:00A  
01012006  
PROGRAMMING  
1=TIME-DATE  
Maintenance Screen #2  
Time and Date Screen  
To change the time, press 1 to display the following screen:  
ENTER TIME AS 12HRS  
:
01:00  
1=AM  
2=PM  
Time Screen  
A flashing cursor will appear on the left side of the display. Enter the four digit number  
corresponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one  
position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will  
return to the Time and Date Screen displaying the new time.  
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be  
displayed:  
ENTER DATE  
**-**-****  
MONTH DAY YEAR  
01-01-2006  
Date Screen  
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit  
day and four digit year. The cursor will move one position to the right after each entry. When the  
fourth digit of the year has been entered, the display will return to the Time and Date Screen which  
will show the new date.  
To change between 12 hour and 24 hour format, press 3 for Clock Format while viewing the Time  
and Date screen. Each press of the 3 key will toggle the display between 12 HR and 24 HR format.  
84  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Panel Control Buttons  
Operating Instructions  
SECTION 4  
Operating Instructions  
Factory programmed Templates have been provided to facilitate the installation and configuration  
of the Fire Alarm Control Panel. The factory default programming for this panel is Template #7.  
Refer to "FACP Configuration Templates" on page 108 for a detailed description of the FACP  
operation for Template #7.  
4.1 Panel Control Buttons  
4.1.1 Acknowledge/Step  
The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to  
steady and also changes the status field on the LCD display from capital letters to small letters  
(TROUBL to troubl). When the piezo is silenced, an acknowledge message is sent to the printer and  
the history file. Acknowledge also sends a silence piezo command to the optional annunciators  
connected to the FACP. The Acknowledge key will have no effect on the Notification Appliance  
Circuits.  
When more than one event exists, the first press of the Acknowledge/Step key functions as  
described in the preceding paragraph. Subsequent pressing of the key steps through each active  
event.  
4.1.2 Alarm Silenced  
The Alarm Silenced key performs the same functions as Acknowledge/Step, except it will not step  
through each event when multiple events are present at the panel. In addition, if an alarm exists, it  
turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm Silenced  
indicator to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and  
optional annunciators. A subsequent new alarm will resound the system NACs. The Alarm  
Silenced indicator is turned off by pressing the Reset key, the Drill key or subsequent activation of  
the NACs.  
Note:  
1. If Silence Inhibit has been enabled, NACs cannot be silenced for one minute following  
initiation of an alarm.  
2. When the system is configured for dual hazard operation, an alarm in one hazard area may  
reactivate notification appliance circuits programmed for that area only.  
4.1.3 Drill/Hold 2 Sec  
When the Drill key is held for a minimum of two seconds (time required to prevent accidental  
activations), the FACP turns on all NAC outputs and turns off the Alarm Silenced indicator if it was  
previously on. The EVAC IN SYSTEM message is shown on the LCD display. The same message  
is sent to the printer and history file. The Alarm Silence key can be used to turn off all silenceable  
NAC outputs following activation by the Drill key.  
4.1.4 Reset  
Pressing and releasing the Reset key turns off all NACs, temporarily turns off resettable power to 4-  
wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the  
same message to the printer and history file. It also performs a lamp test by turning on all LEDs,  
piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that  
exists after a reset will resound the system.  
Note that if Silence Inhibit has been enabled, the FACP cannot be reset for one minute following  
initiation of an alarm.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
85  
Operating Instructions  
Indicators  
4.2 Indicators  
The eight indicators, which are located on the front panel, operate as follows:  
AC Power  
This is a green indicator which illuminates if AC power is applied to the FACP. A loss of AC  
power will turn off this indicator.  
Fire Alarm  
This red indicator flashes when one or more alarms occur. It illuminates steady when the  
Acknowledge/Step or Alarm Silence key is pressed. The Fire Alarm indicator turns off when the  
Reset key is pressed. The indicator will remain off if all alarms have been cleared.  
Supervisory  
This is a yellow indicator that flashes when one or more supervisory conditions occur, such as a  
sprinkler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm  
Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory  
alarms have been cleared.  
Trouble  
This is a yellow indicator that flashes when one or more trouble conditions occur. It stays on steady  
when the Acknowledge/Step or Alarm Silence key is pressed. The indicator turns off when all  
trouble conditions are cleared. This indicator will also illuminate if the microprocessor watchdog  
circuit is activated.  
Alarm Silenced  
This is a yellow indicator that illuminates after the Alarm Silence key is pressed while an alarm  
condition exists. It turns off when the Drill or Reset key is pressed.  
Discharge  
This is a red indicator that illuminates steadily when the water releasing circuit is activated.  
4.3 Normal Operation  
With no alarms or troubles in the system, the display message is System All Normal along with the  
current time and date as shown below. To set the time and date, refer to the appropriate section in  
this manual.  
SYSTEM ALL NORMAL  
10:00A 031106  
The FACP performs the following functions at regular intervals in Normal mode:  
Monitors AC input voltage and battery voltage  
Monitors and reports status option cards and control panel  
Refreshes LCD display and updates time  
Scans control panel keypad for key presses  
Tests memory  
Updates and reads all communications busses (EIA-485, etc.)  
i3 smoke detectors will be polled for maintenance and freeze conditions (temperature of  
o
45 F or less) on initial entry into Normal mode. Thereafter, each device will be polled  
every hour for freeze and every four hours for maintenance conditions  
86  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Operation  
Operating Instructions  
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five  
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or  
maintenance condition, the panel will continue to monitor for freeze conditions every hour and  
maintenance conditions every four hours.  
4.4 Trouble Operation  
With no alarms in the system, the detection of a trouble will cause the following:  
The piezo to pulse 1 second On and 1 second Off  
The system Trouble indicator to flash one second On and one second Off  
The output circuits programmed as Trouble Bell NAC to activate  
The trouble relay to activate  
TROUBL with device type, noun/adjective, address and trouble description will appear on  
the LCD display  
The same message, along with the time and date, is sent to the optional printer and the history  
buffer.  
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn  
off the AC Power indicator, etc.  
Input Zone  
For Input Zones, the following is a typical message that could appear on the LCD display for a  
device trouble:  
TROUBL PULL STATION  
<ADJ> <NOUN>  
ZONE 1 OPEN FAULT  
10:00A 030806  
The information displayed in the above example provides the following information:  
First line in display:  
The type of event; in this example OPEN indicating a circuit trouble  
Device type identifier; in this example, PULL STATION indicates a manual device. Other  
device type identifiers which can be displayed include 2-WIRE SMOKE for Smoke  
Detector, 2-WIRE HEAT for Heat Detector, etc.  
Second line in display:  
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the  
control panel or custom entry via PC.  
<NOUN>; refers to the user programmed noun descriptor from library list resident in the  
control panel or custom entry via PC.  
Third line in display indicates Zone and the fault condition. Other possible troubles include:  
U OPEN - indicating an open circuit  
U DIRTY - maintenance alert indicating that a detector is near but below the allowed  
alarm limit and is in need of maintenance before the performance is compromised  
Fourth line in display:  
Time; the current time in this example is 10:00A which represents 10:00 AM  
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day  
of the month and 06 for the year 2006  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
87  
Operating Instructions  
Alarm Operation  
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the  
system Trouble indicator to change from flashing to on steady. This block acknowledgment occurs  
regardless of the number of troubles, alarms and supervisory events active in the system. When the  
Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the  
‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or  
after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and  
history file.  
If all troubles clear and there are no supervisory or fire conditions active in the system, the system  
returns to normal mode operation and the System All Normal message is shown on the LCD display  
and sent to the history and printer files. The auto-restore feature will restore cleared troubles even  
if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only  
troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except  
the Alarm Silenced indicator will light.  
4.5 Alarm Operation  
For a detailed description of the alarm operation for each preprogrammed Template, refer to  
"FACP Configuration Templates" on page 108 and "Circuit Mapping and Cross-Zoning" on page  
103. Alarm operation is similar to trouble operation with the following differences:  
The piezo sounder produces a steady output as opposed to a pulsed output  
The Fire Alarm indicator flashes 1 second On and 1 second Off  
The LCD displays Alarm along with the device name, type, adjective/noun, associated zones  
and time/date  
Alarms latch and are not allowed to clear automatically  
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started  
Soak and Waterflow Delay Timers are started (if enabled) for appropriate circuits  
Alarms activate the general alarm relay  
Silenced alarms are resounded  
Release Solenoid circuits are activated to produce a water release  
The trouble relay is not activated  
Store event in history buffer  
A typical alarm display would be as illustrated below:  
ALARM PULL STATION  
<ADJ> <NOUN>  
ZONE 1  
10:00A 030806  
Note that the device type, which in this example is PULL STATION, can be any other  
programmable alarm type.  
The information displayed in the above example provides the following information:  
First line in display:  
The type of event; in this example ALARM indicating an alarm condition  
Device type identifier; in this example, PULL STATION indicates a manual pull box.  
Other device type identifiers which can be displayed include 2-WIRE SMOKE for Smoke  
Detector, 2-WIRE HEAT for Heat Detector, etc.  
Second line in display:  
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the  
control panel or custom entry via PC.  
<NOUN>; refers to the user programmed noun descriptor from library list resident in the  
control panel or custom entry via PC.  
Third line in display: Zone 1 indicates the zone programmed to this device which, in this  
example, is Input Zone 1.  
88  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supervisory Operation  
Operating Instructions  
Fourth line in display:  
Time; the current time in this example is 10:00A which represents 10:00 AM  
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day  
of the month and 06 for the year 2006  
4.6 Supervisory Operation  
Supervisory operation is similar to alarm operation but with the following differences:  
The piezo sounder pulses ½ second On and ½ second Off  
The Supervisory indicator flashes ½ second On and ½ second Off  
The LCD displays the status label Active Supervisory along with the device name, type,  
adjective/noun, associated zones and time/date  
The output circuits programmed as Supervisory NAC are activated  
The supervisory relay is activated  
The alarm relay is not activated  
Silenced alarms are not resounded  
Timers are not started  
Store event in history buffer  
A typical Supervisory event would be displayed as illustrated in the following:  
FREEZE SUPERVISORY  
<ADJ> <NOUN>  
ZONE 05 FROZEN SUPRV  
10:00A 030806  
In the preceding example:  
U FROZEN SUPRV - indicates zone detector is below approximately 45oF  
Note that, like alarms, supervisory signals latch (except when programmed for supervisory  
autoresettable). Supervisory alarms do not cause resound as do other alarm conditions. Open  
circuits in supervisory wiring are processed by the control panel the same way as other trouble  
conditions. Refer to "Alarm Operation" on page 88, for a description of the information displayed  
on the control panel LCD.  
4.7 Disable/Enable Operation  
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are  
held in the off state. Disabled zones/NACs are treated as if they were in trouble, with the exception  
being the LCD status label that will be displayed is DISABL.  
Note that disabled Releasing Circuits are treated as supervisory events.  
4.8 Waterflow Circuits Operation  
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will  
not function.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
89  
Operating Instructions  
2nd-Shot Water Switch  
4.9 2nd-Shot Water Switch  
Following an initial waterflow release, an input circuit with the nonlatching Type Code of 2nd-Shot  
Water Switch, when activated, will cause another waterflow release to occur immediately. If a  
manual switch is connected to the circuit, an operator has the option to perform any number of  
additional waterflow releases following an initial release.  
4.10 Detector Functions  
Maintenance Alert  
i3 smoke detectors will be polled for maintenance and freeze conditions (temperature less than  
o
45 F) on initial entry into Normal mode. Thereafter, each device will be polled every hour for  
freeze and every four hours for maintenance conditions All alarm and system trouble conditions  
are annunciated on the control panel’s LCD.  
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five  
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or  
maintenance condition, the panel will continue to monitor for freeze conditions every hour and  
maintenance conditions every four hours.  
Important! In order to avoid false alarms, input zones must be disabled prior to any service work  
being done. After service is completed, the input zones must be re-enabled.  
4.11 Time Functions: Real-Time Clock  
The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is  
displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time  
change-over is programmable and automatic. If both AC and battery are lost, the time must be  
reprogrammed.  
4.12 Coded NAC Operation  
The NAC circuits resident on the control panel main circuit board can be programmed for coded  
operation. The available options which can be programmed for coded operation are as follows:  
Steady - Steady output with no pulsing  
March Time - Pulses at 120 ppm (pulses per minute)  
California Code - 10 seconds On, 5 seconds Off  
Temporal Code - Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½  
second On, 1½ second Off  
Cross-Zone:  
1st zone of a cross-zoned group in alarm causes programmed NAC output to pulse 1  
second on and 1 second off  
2nd zone of a cross-zoned group in alarm causes programmed NAC output to pulse ½  
second on and ½ second off - Note: if more than three zones are cross-zoned, the  
programmed NAC output will continue to pulse ½ second on and ½ second off for each  
subsequent zone in alarm, until the final zone in the cross-zoned group goes into alarm  
all zones of a cross-zoned group in alarm causes the output programmed as a Releasing  
Circuit to perform a water release and the programmed NAC output to turn on steady  
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to  
"Synchronized NAC Operation" on page 62 for additional information.  
90  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Release Stages  
Operating Instructions  
4.13 Release Stages  
Outputs programmed as Release Stage NACs indicate the two stages of a release operation:  
the activation of an output programmed as a Releasing Circuit will cause the programmed  
indicating NAC output to turn on steady  
upon completion of the release, the programmed indicating NAC output will pulse at a 20  
pulse-per-minute rate  
4.14 Special System Timers  
4.14.1 Silence Inhibit Timer  
This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following  
an alarm. A new alarm during the initial 60 second period will not cause the timer to restart with a  
new 60 seconds. Silence Inhibit operation requires the approval of the local AHJ.  
4.14.2 Autosilence Timer  
If Autosilence is selected, the notification appliances, programmed as silenceable, will  
automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the  
Drill key will restart the timer. Autosilence operation requires the approval of the local AHJ.  
4.14.3 Trouble Reminder  
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the  
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the  
Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder  
will occur until the alarm or fault is cleared.  
Note that if Trouble Reminder feature is not selected and the trouble is not cleared within 24 hours,  
the piezo will resound, indicating that the trouble condition still exists.  
4.14.4 Soak Timers  
Two Soak Timers allow the user to program a time between 10 and 30 minutes for each water  
releasing circuit to remain active. Soak Timer 1 is used for Releasing Solenoid Circuit 1 and Soak  
Timer 2 is used for Releasing Solenoid Circuit 2. Following an alarm condition in which the  
releasing circuit is activated, the water release will stop when the corresponding Soak Timer  
reaches zero.  
4.14.5 Waterflow Delay Timer  
If selected, this option will delay the activation of a waterflow type alarm for a programmable time  
duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow  
device. This feature requires the approval of the local AHJ.  
4.15 Walktest  
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest  
will momentarily sound the Notification Appliance Circuits in the building and store the walktest  
information in a file at the panel. A silent walktest will not sound the NACs but will store the  
walktest information in a file which can be viewed at the panel. Disabled NAC devices will not  
activate during walktest. In addition, i3 smoke detectors will enter their own test mode causing  
their LEDs to flash twice every five seconds (refer to i3 specification document).  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
91  
Operating Instructions  
Alarm/Shorted Condition  
Read Status  
When in audible Walktest, the panel responds to each new alarm and activates its programmed  
control outputs for four seconds, if those outputs have been programmed for silenceable activation.  
It also stores each alarm in the walktest history file which can be sent to an optional printer. The  
stored display will be the same as if the device actually activated except the colon (:) in the time  
stamp is replaced with an asterisk (*).  
Open Condition  
Addressable devices as well as all main circuit board NACs are monitored for fault conditions  
during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs  
programmed for Walktest, then shut them off after eight seconds.  
While in Walktest, the trouble relay is activated and the system Trouble indicator flashes (as in all  
of the Program and status change operations). The alarm relay is not activated.  
4.16 Read Status  
Read Status functions do not require a password. The control panel will continue to provide fire  
protection while in Read Status mode. This mode can be entered while the control panel is in alarm  
or trouble. If a new alarm occurs during these functions, the Read Status is exited to prevent  
confusion.  
Read Status Entry  
When the operator presses the control panel Enter key, the LCD will display the following:  
1=READ STATUS MODE  
2=PROGRAMMING MODE  
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read  
Status mode which allows the user to view and print the programmed features and status of the  
control panel.  
The following screens will be displayed:  
READ STATUS  
1=TIMERS  
2=DAYLIGHT SAVINGS  
3=HISTORY  
READ STATUS  
1=FACP CONFIG  
2=INPUT ZONES  
3=OUTPUT CIRCUITS  
Read Status Screen #1  
Read Status Screen #3  
READ STATUS  
READ STATUS  
1=PRINT  
2=ANN-BUS  
1=CROSS INPUT ZONES  
2=ON-BOARD RELAYS  
3=SYSTEM SETTINGS  
Read Status Screen #2  
Read Status Screen #4  
92  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read Status  
Operating Instructions  
4.16.1 FACP Configuration  
Pressing 1 while viewing Read Status Screen #1 will display the type of configuration programmed  
into the FACP (refer to "FACP CONFIG (Application Templates)" on page 50). As an example, if  
Template 7 was programmed as the FACP configuration, the following screen will be displayed:  
READ FACP CONFIG  
TEMPLATE 7  
SINGLE HAZARD  
X-ZONE MAN REL SW  
4.16.2 Input Zones  
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:  
READ INPUT ZONES  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
Pressing the down arrow key will allow the selection of Zones 4-6.  
The operator selects the zone which is to be viewed by pressing the number corresponding to the  
desired zone in each screen. For example, if 1 is pressed in the first screen, the display will change  
to a screen similar to the following:  
READ INPUT ZONE 1  
PULL STATION  
Normal  
PRESS TO VIEW  
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to  
view additional programming information about the selected device, such as:  
Enable/Disable Status  
Device Type  
Output Circuit MAP  
Adjective/Noun descriptor  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
93  
Operating Instructions  
Read Status  
4.16.3 Output Circuits  
Pressing 3 while viewing Read Status Screen #1 will display the following screens:  
READ OUTPUTS  
1=OUTPUT 1  
2=OUTPUT 2  
3=OUTPUT 3  
READ STATUS  
1=FACP CONFIG  
2=INPUT ZONES  
Read Outputs Screen #1  
3=OUTPUT CIRCUITS  
Read Status Screen #1  
READ OUTPUTS  
1=OUTPUT 4  
Read Outputs Screen #2  
The operator can press 1 to view the programmed options for Output 1, 2 to view the programmed  
options for Output 2, 3 to view the programmed options for Output 3 or 4 to view the programmed  
options for Output 4.  
The resulting screens will display the following information:  
Enable/Disable Status  
Circuit Type  
Silenceable/Nonsilenceable  
Auto Silence Enable/Disable and time delay (in minutes)  
Silence Inhibit Enabled/Disabled  
Coding Selection (Temporal, Steady, etc.)  
4.16.4 Cross Input Zones  
READ STATUS  
Pressing 1 while viewing Read Status Screen #2 will display the following screens:  
1=CROSS INPUT ZONES  
2=ON-BOARD RELAYS  
3=SYSTEM SETTINGS  
CROSS INPUT ZONES  
1=RELEASE 1  
2=RELEASE 2  
Read Status Screen #2  
Cross Input Zone Screen  
Pressing 1 for Release 1 or 2 for Release 2 will display the cross-zoning, if any, for the selected  
Releasing Circuit as illustrated in the following screen:  
CROSS ZONE REL 1  
X 1 4  
NONE  
NONE  
Cross Input Zone Screen  
The Cross Zone Release screen displays the zones that have been cross-zoned. In this example,  
Zone 1 is cross-zoned with Zone 4.  
94  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read Status  
Operating Instructions  
4.16.5 On-Board Relays  
Pressing 2 while viewing Read Status Screen #2 will display the following screen:  
ON-BOARD RELAYS  
RELAY 1  
RELAY 2  
RELAY 3  
ALARM  
TROUBLE  
SUPERVSRY  
This screen allows the operator to view the programmed option for each relay.  
4.16.6 System Settings  
Pressing 3 while viewing Read Status Screen #2 will display the following screens:  
SYSTEM SETTINGS  
FUTURE USE  
TROUBLE REMIND  
NO  
CHARGER DISABLE NO  
SYSTEM SETTINGS  
FACTORY BANNER  
The operator can view the system settings options that have been programmed into the FACP.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
95  
Operating Instructions  
Read Status  
4.16.7 Timers  
Pressing 1 while Read Status Screen #3 will display the following screens:  
TIMERS  
SOAK 1 10 MIN  
SOAK 2 10 MIN  
WATERFLOW DELAY 0 S  
READ STATUS  
1=TIMERS  
2=DAYLIGHT SAVINGS  
3=HISTORY  
Read Status Screen #3  
TIMERS  
AC LOSS DELAY 2 HR  
These screens allow the operator to view the various timer settings.  
4.16.8 Daylight Savings  
Pressing 2 while Read Status Screen #3 will cause the following screens to be displayed:  
DAYLIGHT SAVINGS  
ENABLED  
START MONTH  
START WEEK  
YES  
MAR  
WK 2  
DAYLIGHT SAVINGS  
END MONTH  
END WEEK  
NOV  
WK 1  
These screens allow the operator to view settings that have been programmed for Daylight Savings  
Time.  
96  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read Status  
Operating Instructions  
4.16.9 History  
Pressing 3 while viewing Read Status Screen #3 will display the following screens:  
HISTORY  
1=VIEW ALL  
2=VIEW ALARMS  
3=VIEW OTHER EVENTS  
The operator can view all events which have been stored in the history file, only alarms or other  
events, such as troubles or supervisories, by pressing the corresponding number key.  
4.16.10 PRINT  
READ STATUS  
To print control panel data, press 1 while viewing Read Status Screen #4. This allows printing to  
1=PRINT  
the printer connected to the ANN-S/PG module. The following screens will be displayed:  
2=ANN-BUS  
Read Status Screen #4  
PRINT  
1=HISTORY  
2=WALKTEST LOG  
3=EXIT PRINTING  
Pressing 1 allows the user to print the History file which will detail all of the system activities since  
the file was last cleared from memory.  
Pressing 2 allows the user to print the Walktest log which will detail all of the system activations  
during walktest since the log was last cleared. Refer to "Walktest" on page 79 for additional  
information on the display.  
Pressing 3 will exit the Print operation.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
97  
Operating Instructions  
Read Status  
4.16.11 ANN-BUS  
Pressing 2 while viewing Read Status Screen #4 will display the settings for the ANN-BUS options  
as shown in the following screens:  
ANN-BUS  
BUS ENABLED  
NO  
1=BUS MODULES  
2=ANN-S/PG OPTIONS  
ANN-BUS Screen #1  
ANN-BUS  
1=ANN-80 OPTION  
2=ANN-RLY OPTIONS  
ANN-BUS Screen #2  
ANN-BUS Screen #1 indicates whether the ANN-BUS is enabled (Yes/No).  
Pressing 1 while viewing ANN-BUS Screen #1 will display BUS Module addresses 1-8 and the  
devices, if any, located at those addresses.  
Pressing 2 while viewing ANN-BUS Screen #1 will display the programmed options for the ANN-  
S/PG Module devices connected to the ANN-BUS.  
Pressing 1 while viewing ANN-BUS Screen #2 will display the programmed options for the ANN-  
80 LCD annunciators connected to the ANN-BUS.  
Pressing 2 while viewing ANN-BUS Screen #2 will display the programmed options for the ANN-  
RLY devices connected to the ANN-BUS.  
98  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Overview  
Power Supply Calculations  
SECTION 5  
Power Supply Calculations  
5.1 Overview  
This section contains instructions and tables for calculating power supply currents in alarm and  
standby conditions. This is a four-step process, consisting of the following:  
1. Calculating the total amount of AC branch circuit current required to operate the system  
2. Calculating the power supply load current for non-fire and fire alarm conditions and calcu-  
lating the secondary (battery) load  
3. Calculating the size of batteries required to support the system if an AC power loss occurs  
4. Selecting the proper batteries for your system  
5.2 Calculating the AC Branch Circuit  
The control panel requires connection to a separate, dedicated AC branch circuit, which must be  
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed  
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm  
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,  
from the power source to the control panel. Overcurrent protection for this circuit must comply  
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2)  
wire with 600 volt insulation for this branch circuit.  
Use Table 5-1 , to determine the total amount of current, in AC amperes (A), that must be supplied  
to the system.  
TABLE 5-1:120 VAC Branch Circuit Requirements  
Number of  
Devices  
Current Draw  
(AC amps)  
Total Current per  
Device  
Device Type  
MRP-2001  
or  
3.66  
1
X
=
2.085  
MRP-2001E  
[
[
]
]
X
X
=
=
=
[
]
Sum Column for AC Branch Current Required  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Supply Calculations  
Calculating the System Current Draw  
5.3 Calculating the System Current Draw  
5.3.1 Overview  
The control panel must be able to power all internal and external devices continuously during the  
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when  
primary power is applied, use Calculation Column 1 in Table 5-3 on page 101. The control panel  
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on  
the power supply, use Calculation Column 2 in Table 5-3 on page 101. The secondary power  
source (batteries) must be able to power the system during a primary power loss. To calculate the  
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 5-3 on page  
101.  
When calculating current draw and the battery size, note the following:  
• ‘Primary’ refers to the main power source for the control panel  
• ‘Secondary’ refers to the control panel’s backup batteries  
• All currents are given in amperes (A). Table 5-2 shows how to convert milliamperes and  
microamperes to full amperes.  
TABLE 5-2:Converting to Full Amperes  
To convert...  
Multiply  
Example  
Milliamperes (mA) to  
amperes (A)  
mA x 0.001  
3 mA x 0.001 = 0.003A  
Microamperes (µA) to  
amperes (A)  
µA x 0.000001  
300 µA x 0.000001 = 0.0003 A  
5.3.2 How to Use Table 5-3 on page 101 to Calculate System Current Draw  
Use Table 5-3 on page 101 to calculate current draws as follows:  
1. Enter the quantity of devices in all three columns  
2. Enter the current draw where required. Refer to the Device Compatibility Document for  
compatible devices and their current draw  
3. Calculate the current draws for each in all columns  
4. Sum the total current for each column  
5. Copy the totals from Column 2 and Column 3 to Table 5-4 on page 102  
Following are the types of current that can be entered into Table 5-3 on page 101:  
Calculation Column 1 - The primary supply current load that the control panel must  
support during a non-fire alarm condition, with AC power applied.  
Calculation Column 2 - The primary supply current load that the control panel must  
support during a fire alarm condition, with AC power applied.  
Calculation Column 3 - The standby current drawn from the batteries in a non-fire  
alarm condition during a loss of AC power.  
100  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Calculating the System Current Draw  
Power Supply Calculations  
Table 5-3 contains three columns for calculating current draws. For each column, calculate the  
current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Cal-  
culation Column 2 and Calculation Column 3 to Table 5-4 on page 102.  
TABLE 5-3:System Current Draw Calculations  
Calculation Column 1  
Primary, Non-Fire Alarm Current  
(amps)  
Calculation Column 2  
Primary, Fire Alarm Current  
(amps)  
Calculation Column 3  
Secondary, Non-Fire Alarm Current  
(amps)  
Device Type  
Qty  
X[current draw]=  
X[0.122]=  
Total  
Qty  
X [current draw] =  
Total  
Qty  
X[current draw]=  
X[0.122]=  
Total  
1
Main Circuit Board  
CAC-5X  
1
0.122  
1
0.185  
1
0.122  
X[0.185] =  
[
[
[
[
[
]
]
]
]
]
X[0.001]=  
[
[
[
[
[
]
]
]
]
]
X[0.001]=  
[
[
[
[
[
]
]
]
]
]
X[0.001]=  
1
4XTMF  
X[0.005]=  
X[0.005]=  
X[0.011] =  
ANN-80  
X[0.037]=  
2
X[0.040]=  
X[0.037]=  
2-wire Detector Heads  
4-wire Detector Heads  
Power Supervision  
X[  
X[  
]=  
]=  
X[  
X[  
]=  
]=  
X[  
] =  
2
X[  
] =  
[
]
X[0.025]=  
[
]
X[0.025]=  
[
]
X[0.025]=  
3
Relays  
4
[
[
]
]
X[  
X[  
]=  
]=  
NAC #1  
NAC #2  
NAC #3  
NAC #4  
Current Draw from  
[
]=  
[
]=  
[
]=  
5
TB9 (nonalarm )  
6
Sum each column  
for totals  
Primary Non-Alarm =  
Primary Alarm =  
Secondary Non-Alarm =  
Table Footnote  
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005  
amps.  
2. Refer to the Device Compatibility Document for standby current.  
3. Must use compatible listed Power Supervision Relay.  
4. Current limitation of Terminal TB5 circuits is 3.0 amps per NAC  
5. The total standby current must include both the resettable (TB9 Terminals 3 & 4) and nonresettable/resettable (TB9 Terminals 1  
& 2) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum rat-  
ings specified. Current limitations of TB9, Terminals 1 & 2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mVRMS  
,
nonresettable power and TB9, Terminals 3 & 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mVRMS, resettable  
power.  
6. Total current draw listed above cannot exceed 7.0 amps  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
101  
Power Supply Calculations  
Calculating the Battery Size  
5.4 Calculating the Battery Size  
Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load  
determines the battery size (in AH), required to support the control panel under the loss of AC  
power. Complete Table 5-4 as follows:  
1. Enter the totals from Table 5-3 on page 101, Calculation Columns 2 and 3 where shown  
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)  
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm  
ampere hours  
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)  
5. Write the ampere hour requirements on the Protected Premises label located inside the cabi-  
net door  
TABLE 5-4:Total Secondary Power Requirements at 24 VDC  
Secondary Standby Load  
(total from Table 5-3 Calculation  
Column 3)  
Required Standby Time  
(24 hours)  
[
]
X[  
]
=
AH  
Primary Alarm Load  
(total from Table 5-3 Calculation  
Column 2)  
Required Alarm Time  
(for 5 min., enter 0.084,  
for 10 min., enter 0.168)  
=
=
AH  
AH  
[
]
X[  
]
Sum of Standby and Alarm Ampere Hours  
Multiply by the Derating Factor  
X 1.2  
Battery Size, Total Ampere Hours Required  
=
AH  
5.4.1 NFPA Battery Requirements  
NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power  
followed by 5 minutes in alarm  
5.4.2 Selecting and Locating Batteries  
Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The control  
panel can charge batteries in the 7 AH to 26 AH range. The control panel cabinet is capable of  
housing batteries up to 18 AH. Batteries larger than 18 AH require the BB-26, BB-55 or other UL  
listed external battery cabinet.  
102  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
Circuit Mapping and Cross-Zoning  
APPENDIX A  
Circuit Mapping and Cross-Zoning  
A.1 Input-to-Output Circuit Mapping and Cross-Zone Operation  
The flexible cross-zoning and input-to-output (I/O) mapping capability of this fire panel provides a  
powerful toolset to accommodate many site-specific configurations. To simplify initial setup,  
preconfigured application templates that employ cross-zoning and I/O mapping are included from  
the factory. Refer to "FACP Configuration Templates" on page 108 for a description of each  
supplied template.  
The following sections provide some examples of setting up your own cross-zoned or I/O mapped  
system.  
The Installer is responsible for completely testing the proper operation of the fire panel as set  
!
up by programming.  
Notes:  
1. Any general system trouble, such as a battery fault, will activate any output circuit  
programmed as TROUBLE NAC in the OUTPUT CIRCUITS menu. Circuit mapping does  
not apply.  
2. Any input zone programmed for supervisory operation or as a DISABLE RELEASE switch in  
the INPUT CIRCUITS menus will activate any output circuit programmed as SUPV BELL  
NAC in the OUTPUT CIRCUITS menus. Circuit mapping does not apply.  
3. The programming menus will prevent you from mapping any incompatible input zone and  
output circuit types together, such as mapping a supervisory input zone to a releasing output  
circuit.  
4. Timers and/or delays are not represented in these examples.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
103  
Circuit Mapping and Cross-Zoning  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
A.1.1 Mapping Input Zones to Output Circuits for Direct Activation  
Using the INPUT ZONES menus, you can assign any input zone to directly activate (without cross-  
zoning) any of the four output circuits provided they are assigned matching operational types (see  
the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).  
Example 1: A waterflow input zone assigned to directly activate an alarm output circuit by setting  
the OUTPUT CIRCUIT MAP assignment to YES.  
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.  
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.  
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus.  
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.  
Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.  
Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output  
Circuits 2, 3 or 4.  
ZONE 1 TYPE  
1=N/A  
2=WATERFLOW  
3=WATERFLOW NS  
OUTPUT MAP ZONE 1  
1=ALARM NAC  
2=RELEASE 1  
3=RELEASE 2  
YES  
NO  
NO  
OUTPUT MAP ZONE 1  
1=SUPV BELL NAC  
N/A  
Example 2: A single hazard application where a smoke detector input zone will directly activate  
both an alarm NAC circuit and a releasing output circuit.  
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.  
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.  
Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.  
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.  
Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.  
Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release  
1) but not output circuits 3 or 4.  
ZONE 1 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
OUTPUT MAP ZONE 1  
1=ALARM NAC  
2=RELEASE 1  
3=WATERFLOW NAC  
YES  
YES  
NO  
OUTPUT MAP ZONE 1  
1=SUPV BELL NAC  
N/A  
104  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
Circuit Mapping and Cross-Zoning  
A.1.2 Mapping Input Zones to Release Circuits for Cross Zone  
Activation  
Using the OUTPUT CIRCUITS menus, this fire panel will allow you to assign a release circuit type  
of operation to any two of the four output circuits. Up to two releasing circuits (or hazards), called  
RELEASE 1 and RELEASE 2, may be created. Input zones may be assigned in various ways to  
activate either one or both of the release circuits. The fire panel treats RELEASE 1 and RELEASE  
2 functions independently from each other, although they may share input circuits for activation.  
Cross-zoning is set up in the CROSS INPUT ZONES menus, where you can create up to three  
groups of input zones for each release circuit. When cross zone groups have been set up, the  
OUTPUT CIRCUIT MAP associated with the input zones will automatically show YES for release  
output circuits. This extremely flexible cross-zone with grouping capability is used in the  
following examples.  
Example 3: A single hazard, cross-zoned application using two smoke detector input zones and  
one releasing output circuit. Input Zones 1 and 2 are cross-zoned to activate output circuit 2, which  
is programmed as a RELEASE 1.  
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.  
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.  
Output Circuit 3 is programmed as alarm NAC using the OUTPUT CIRCUITS menus  
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.  
Either of smoke detector Input Zones 1 or 2 will directly activate Output Circuit 1 (Alarm  
NAC).  
Smoke detector Input Zone 2 will also directly activate Output Circuit 3 (Alarm NAC) but  
not Output Circuits 2 or 4.  
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate  
Output Circuit 2 (Release 1) but not Output Circuit 4.  
ZONE 1 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
ZONE 2 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
OUTPUT MAP ZONE 1  
OUTPUT MAP ZONE 2  
1=ALARM NAC  
2=RELEASE 1  
3=ALARM NAC  
YES  
YES  
NO  
1=ALARM NAC  
YES  
YES  
YES  
2=RELEASE 1  
3=ALARM NAC  
OUTPUT MAP ZONE 1  
OUTPUT MAP ZONE 2  
1=SUPV BELL NAC  
N/A  
1=SUPV BELL NAC  
N/A  
REL 1 CROSS GROUP 1  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
YES  
YES  
NO  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Circuit Mapping and Cross-Zoning  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output  
circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as  
RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is  
programmed as a RELEASE 2.  
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.  
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.  
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus  
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.  
Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm  
NAC) but not Output Circuits 2, 3 or 4.  
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate  
Output Circuit 2 (Release 1) but not Output Circuits 3 or 4.  
Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate  
Output Circuit 3 (Release 2) but not Output Circuits 2 or 4.  
ZONE 1 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
ZONE 3 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
3=2-WIRE SMOKE  
ZONE 2 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
ZONE 4 TYPE  
1=COMBO  
2=COMBO W/AR. SUPERV  
3=2-WIRE SMOKE  
OUTPUT MAP ZONE 1  
OUTPUT MAP ZONE 2  
1=ALARM NAC  
2=RELEASE 1  
3=RELEASE 2  
YES  
YES  
NO  
1=ALARM NAC  
2=RELEASE 1  
3=RELEASE 2  
YES  
YES  
NO  
OUTPUT MAP ZONE 1  
OUTPUT MAP ZONE 2  
1=SUPV BELL NAC  
N/A  
1=SUPV BELL NAC  
N/A  
OUTPUT MAP ZONE 4  
OUTPUT MAP ZONE 3  
1=ALARM NAC  
2=RELEASE 1  
3=RELEASE 2  
YES  
NO  
YES  
1=ALARM NAC  
2=RELEASE 1  
3=RELEASE 2  
YES  
NO  
YES  
OUTPUT MAP ZONE 3  
OUTPUT MAP ZONE 4  
1=SUPV BELL NAC  
N/A  
1=SUPV BELL NAC  
N/A  
REL 1 CROSS GROUP 1  
REL 2 CROSS GROUP 1  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
YES  
YES  
NO  
1=ZONE 1  
2=ZONE 2  
3=ZONE 3  
NO  
NO  
YES  
REL 2 CROSS GROUP 1  
1=ZONE 4  
2=ZONE 5  
3=ZONE 6  
YES  
NO  
NO  
106  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
Circuit Mapping and Cross-Zoning  
A.1.3 Complex Examples of Cross Zoning and I/O Mapping for  
Release Circuits  
Following are some complex examples of cross-zoning for more demanding applications that are  
possible with this fire panel. Input zone entries in a single cross-zone group are effectively  
AND’ed together while the cross-zone groups are effectively OR’ed together. For the purpose of  
describing this, the following language is used:  
R1  
R2  
=
=
=
=
=
=
=
=
=
=
RELEASE 1  
RELEASE 2  
Z1  
INPUT ZONE 1  
Z2  
INPUT ZONE 2  
Z3  
INPUT ZONE 3  
Z4  
INPUT ZONE 4  
Z5  
INPUT ZONE 5  
Z6  
INPUT ZONE 6  
OR  
AND  
any input zone may cause a release  
all input zones must be active for a release  
Example 5: Release Circuit 1 activates if either Input Zone 1 or 2 are active in addition to Input  
Zone 3 being active.  
R1 = (Z1 AND Z3) OR (Z2 AND Z3)  
Set Zones 1 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT  
ZONES menus.  
Set Zones 2 and 3 to YES in Cross Zoning Group 2 for RELEASE 1 in the CROSS INPUT  
ZONES menus.  
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS  
INPUT ZONES menus.  
Example 6: Release Circuit 1 activates if Input Zones 1 and 2 and 3 are all active.  
R1 = Z1 AND Z2 AND Z3  
Set Zones 1, 2 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT  
ZONES menus.  
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS  
INPUT ZONES menus.  
Example 7: Release Circuit 1 activates if Input Zones 1 and 2 and 3 are all active. Release Circuit  
2 activates if Input Zones 2 and 3 and 4 are all active.  
R1 = Z1 AND Z2 AND Z3  
R2 = Z2 AND Z3 AND Z4  
Set Zones 1, 2 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT  
ZONES menus.  
Set Zones 2, 3 and 4 to YES in Cross Zoning Group 1 for RELEASE 2 in the CROSS INPUT  
ZONES menus.  
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS  
INPUT ZONES menus.  
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 2 in the CROSS  
INPUT ZONES menus.  
Example 8: Release Circuit 1 activates if Input Zone 1 activates followed in time by Input Zone 2  
activating.  
This kind of sequential reaction is not possible at this time.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
107  
FACP Configuration Templates  
Input-to-Output Circuit Mapping and Cross-Zone Operation  
APPENDIX B  
FACP Configuration Templates  
The MRP-2001/E has been provided with preprogrammed templates which allow the user to  
quickly configure the FACP [refer to "FACP CONFIG (Application Templates)" on page 50]. The  
user also has the option to reprogram selected portions of the template for customized applications.  
The following pages of this appendix describe the programming for each of the templates.  
Note: MRP-2001/E Pre-Action/Deluge Control Panel can be configured using preprogrammed  
Templates 7 through 13 only. Template 7 is the factory default template for the FACP.  
(Templates 1 through 6 are not available for this panel.)  
Important! Each Template has been programmed with specific Input Zone Types and Output  
Circuit Types. If the FACP is configured with one of the preprogrammed Templates, the user must  
ensure that the devices connected to each Input Zone and Output Circuit are compatible with the  
programmed types. (The user can reprogram the circuit types if desired).  
108  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Template 7: Single Hazard - 3 Zone  
FACP Configuration Templates  
B.1 Template 7: Single Hazard - 3 Zone  
TEMPLATE 7: SINGLE HAZARD - 3 ZONE  
INPUT ZONES  
3
WATERFLOW  
1
2
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
MANUAL  
RELEASE  
X
SUPV.  
#1 ALARM NAC  
X
X
X
X
#2 WATERFLOW NAC  
#3 RELEASE SOLENOID 1  
#4 SUPV. BELL NAC  
X
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on  
corresponding output circuit).  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - no waterflow delay since Waterflow Delay Timer is set to 0  
Zone 4 = Manual Release  
Zone 5 = Pull Station  
Zone 6 = Supervisory  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Waterflow NAC - no waterflow delay since Waterflow Delay Timer is set to 0  
Output 3 = Release Solenoid 1 (unsupervised for shorts)  
Output 4 = Supervisory Bell NAC  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 0 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or  
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output  
#3. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak  
Timer 1  
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is  
no FACP initiated delay in activation since the Waterflow Delay Timer is set to 0 seconds  
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
109  
FACP Configuration Templates  
Template 8: Single Hazard - Cross-Zone With Manual Release  
B.2 Template 8: Single Hazard - Cross-Zone With Manual Release  
TEMPLATE 8: CROSS-ZONE WITH MANUAL RELEASE SWITCH  
INPUT ZONES  
1
2
3
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
WATERFLOW  
MANUAL  
RELEASE  
X
SUPV.  
#1 ALARM NAC  
X
X
#2 WATERFLOW NAC  
#3 RELEASE SOLENOID 1  
#4 SUPV. BELL NAC  
X
C1  
C1  
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding  
output circuit).  
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid  
number must be active at the same time to turn on the corresponding solenoid output circuit  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - activation delayed for 60 seconds (Waterflow Delay set to 60 secs.)  
Zone 4 = Manual Release  
Zone 5 = Pull Station  
Zone 6 = Supervisory  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Waterflow NAC - activation delayed for 60 seconds (Waterflow Delay set to 60 sec)  
Output 3 = Release Solenoid 1 (unsupervised for shorts)  
Output 4 = Supervisory Bell NAC  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 60 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone  
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #3.  
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer  
1. Activation of any one of these zones will operate Alarm NAC Output #1  
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is  
a 60 second FACP initiated delay in activation since Waterflow Delay Timer is set to 60  
seconds  
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay  
110  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Template 9: Dual Hazard - Combined Release  
FACP Configuration Templates  
B.3 Template 9: Dual Hazard - Combined Release  
TEMPLATE 9: DUAL HAZARD - COMBINED RELEASE  
INPUT ZONES  
1
2
3
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
WATERFLOW  
MANUAL  
RELEASE  
X
SUPV.  
#1 ALARM NAC  
X
X
X
#2 SUPV BELL NAC  
X
#3 RELEASE SOLENOID 1  
#4 RELEASE SOLENOID 2  
X
X
X
X
X
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding  
output circuit).  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Zone 4 = Manual Release  
Zone 5 = Pull Station  
Zone 6 = Supervisory  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Supervisory Bell NAC  
Output 3 = Release Solenoid 1 (unsupervised for shorts)  
Output 4 = Release Solenoid 2 (unsupervised for shorts)  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 10 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or  
Zone 5 (Pull Station) will operate the Alarm NAC Output #1, Release Solenoid 1 Output #3  
and Release Solenoid 2 Output #4. Release Solenoid 1 will turn off water release following  
time-out of the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release  
following time-out of the 10 minute Soak Timer 2  
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a  
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10  
seconds  
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #2  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
111  
FACP Configuration Templates  
Template 10: Dual Hazard - Split Release  
B.4 Template 10: Dual Hazard - Split Release  
TEMPLATE 10: DUAL HAZARD - SPLIT RELEASE  
INPUT ZONES  
1
2
3
4
5
6
PULL  
STATION  
X
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
WATERFLOW  
SUPV.  
MANUAL  
RELEASE  
X
#1 ALARM NAC  
#2 SUPV BELL NAC  
#3 RELEASE SOLENOID 1  
#4 RELEASE SOLENOID 2  
X
X
X
X
X
X
X
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding  
output circuit).  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to secs.)  
Zone 4 = Supervisory  
Zone 5 = Manual Release  
Zone 6 = Pull Station  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Supervisory Bell NAC  
Output 3 = Release Solenoid 1 (unsupervised for shorts)  
Output 4 = Release Solenoid 2 (unsupervised for shorts)  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 10 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and  
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2  
Output #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release) or Input 6  
(Manual Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and  
Alarm NAC Output #1. Release Solenoid 1 will turn off water release following time-out of  
the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release following  
time-out of the 10 minute Soak Timer 2  
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a  
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10  
seconds  
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 5 (Manual Release) or Zone 6 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 4 (Supervisory) will operate the Supervisory Relay  
112  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Template 11: Single Hazard - 3 Zones and Low Pressure  
FACP Configuration Templates  
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure  
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE  
INPUT ZONES  
1
2
3
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
WATERFLOW  
MANUAL  
RELEASE  
X
LOW  
PRESS.  
#1 ALARM NAC  
X
X
X
X
#2 WATERFLOW NAC  
#3 SUPV. BELL NAC  
#4 RELEASE SOLENOID 1  
X
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding  
output circuit).  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Zone 4 = Manual Release  
Zone 5 = Pull Station  
Zone 6 = Low Pressure  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)  
Output 3 = Supervisory Bell NAC  
Output 4 = Release Solenoid 1 (unsupervised for shorts)  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 10 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or  
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output  
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak  
Timer 1  
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is  
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10  
seconds  
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
113  
FACP Configuration Templates  
Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active  
B.6 Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active  
TEMPLATE 12: SINGLE HAZARD - 2 ZONES CROSS-ZONES WITH ALL ACTIVE  
INPUT ZONES  
1
2
3
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
WATERFLOW  
MANUAL  
RELEASE  
X
LOW  
PRESS.  
#1 ALARM NAC  
X
X
#2 WATERFLOW NAC  
#3 SUPV. BELL NAC  
#4 RELEASE SOLENOID 1  
X
X
C1  
C1  
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding  
output circuit).  
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid  
number must be active at the same time to turn on the corresponding solenoid output circuit  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Zone 4 = Manual Release  
Zone 5 = Pull Station  
Zone 6 = Low Pressure  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Output 3 = Supervisory Bell NAC  
Output 4 = Release Solenoid 1 (unsupervised for shorts)  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 10 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone  
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #4.  
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer  
1. Activation of any one of these zones will operate Alarm NAC Output #1  
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is  
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10  
seconds  
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay  
114  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Template 13: Single Hazard - Dual Zone  
FACP Configuration Templates  
B.7 Template 13: Single Hazard - Dual Zone  
TEMPLATE 13: SINGLE HAZARD - DUAL ZONE  
INPUT ZONES  
1
2
3
4
5
PULL  
STATION  
X
6
OUTPUT CIRCUITS  
2-WIRE SMOKE  
FIRE  
LOW  
PRESS.  
WATERFLOW  
MANUAL  
RELEASE  
X
#1 ALARM NAC  
X
X
X
X
X
X
#2 WATERFLOW NAC  
#3 RELEASE SOLENOID 1  
#4 WATERFLOW NAC  
X
X
X
Table Legend:  
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on  
corresponding output circuit).  
Input Zone Types:  
Zone 1 = 2-wire smoke  
Zone 2 = Fire  
Zone 3 = Low Pressure  
Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Zone 5 = Pull Station  
Zone 6 = Manual Release  
Output Circuit Types:  
Output 1 = Alarm NAC  
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Output 3 = Release Solenoid 1 (unsupervised for shorts)  
Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)  
Timers  
Soak Timer 1 - set for 10 minutes  
Soak Timer 2 - set for 10 minutes  
Waterflow Delay Timer - set for 10 seconds  
AC Loss Delay Timer - set for 2 hours  
Operation  
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 5 (Pull Station) or  
Zone 6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1  
Output #3. Release Solenoid will turn off water release following time-out of the 10 minute  
Soak Timer 1  
Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow  
NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay  
in activation of these outputs since the Waterflow Delay Timer is set to 10 seconds  
Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)  
FACP Relay Operation  
The following description of FACP relay operations are in addition to normal system operation.  
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3  
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull  
Station) will operate Alarm Relay  
Trouble Relay - any system trouble will activate the Trouble Relay  
Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
115  
NFPA Standard-Specific Requirements  
Template 13: Single Hazard - Dual Zone  
APPENDIX C  
NFPA Standard-Specific Requirements  
This panel has been designed for use in commercial, industrial and institutional applications and  
meets the requirements for service under the National Fire Protection Association (NFPA)  
Standards outlined in this Appendix. The minimum system components required for compliance  
with the appropriate NFPA standard are listed below:  
MRP-2001/E Control Panel  
Contains the main control board, cabinet (backbox and door), main power supply transformer and  
power supply.  
Batteries  
Refer to "Power Supply Calculations" on page 99, for Standby Power Requirements.  
Initiating Devices  
Connected to one of the control panel's Initiating Device Circuits.  
Notification Appliances  
Connected to one of the control panel's Output Circuits.  
Releasing Devices  
Connected to one of the control panel's Output Circuits.  
The following additional equipment is needed for compliance with the NFPA 72 standards listed  
below:  
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service  
411UD may be installed as illustrated in Figure C.1, “FACP Connection to 411UD,”  
on page 117  
OR  
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver.  
See Figure C.3 on page 120, for installation instructions for this unit  
NFPA 72 Auxiliary Fire Alarm System  
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.  
This unit must be installed as illustrated in the section titled "4XTMF Municipal Box Transmitter  
Option Module" on page 28 and as outlined in Figure C.2, “Municipal Box Connected to 4XTMF  
Transmitter Module,” on page 119.  
NFPA 72 Proprietary Fire Alarm System  
FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.4,  
“Proprietary Protective Signaling System,” on page 121, for installation instructions for this unit.  
The relay contacts of this control panel may be used to trip any dialer that is UL-listed for Central  
Station/Remote Station services. The illustrations in this appendix provide examples of possible  
system configurations.  
116  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Template 13: Single Hazard - Dual Zone  
NFPA Standard-Specific Requirements  
The following figure illustrates an example of Central Station/Remote Station Reporting using a  
411UD. The relay contacts from the MRP-2001/E may be used to trip any dialer UL-listed for  
Central Station/Remote Station Reporting Services.  
411UD  
1
Channel1  
2
3
Channel 2  
4
5
Channel 3  
6
7
Channel 4 (2.2K ELR)  
8
1
2
3
4
5
6
7
8
9
Jumper -VDC to Trouble Relay contact  
+ 24 VDC nonresettable power  
- 24 VDC nonresettable power  
J4 Not Installed  
Relay Output (DACT Trouble) from 411UD  
FACP Supervisory Relay  
FACP Trouble Relay  
FACP Alarm Relay  
2.2K ELRs P/N 27070  
1 2 3 4 5 6 7 8 9  
FACP  
Trouble Input  
(nonsupervised,  
power-limited)  
Figure C.1 FACP Connection to 411UD  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
117  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA Standard-Specific Requirements  
Template 13: Single Hazard - Dual Zone  
411UD  
FACP  
Alarm  
TB2-1  
TB2-2  
TB2-3  
TB2-4  
TB2-5  
TB2-6  
TB8-1  
TB8-3  
TB8-4  
TB8-6  
TB8-7  
TB8-9  
Trouble  
Supervisory  
Table C.1 411-UD Connections to FACP  
Notes:  
1. Reference the 411UD Manual for additional information  
2. All connections between the control panel and the 411UD must be in conduit, less than 20 ft.  
(610 cm) in length in the same room.  
3. Any zone of the 411UD can be wired to function as alarm, trouble or supervisory; the 411UD  
must be programmed accordingly. In this example, Channel/Zone 1 is wired to the control  
panel’s alarm relay, Channel 2/Zone 2 is wired to the control panel’s trouble relay and  
Channel 3/Zone 3 is wired to the control panel’s supervisory relay.  
4. Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for  
nonresettable power on the FACP. Jumper J4 on the 411UD must be removed for 24 VDC  
power.  
5. End-of-Line resistors must terminate all 411UD circuits, including unused circuits.  
6. Program the 411UD for slave operation.  
7. The MRP-2001/E must be programmed for AC Loss Reporting Delay This prevents the  
immediate transmission of a trouble on the loss of AC power.  
8. A (-)VDC from the 411UD Trouble Contacts will activate the Trouble Input J6 on the FACP.  
118  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA 72 Auxiliary Fire Alarm System  
NFPA Standard-Specific Requirements  
C.1 NFPA 72 Auxiliary Fire Alarm System  
All connections are power-limited and supervised. This application is not suitable for separate  
transmission of sprinkler supervisory or trouble conditions.  
Notes:  
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.  
2. Cut JP30 on the MRP-2001/E main circuit board to supervise placement of 4XTMF module  
and circuit.  
3. Cut JP24 on the MRP-2001/E main circuit board to enable FACP Supervisory relay.  
4. Refer to "4XTMF Municipal Box Transmitter Option Module" on page 28 for detailed  
information.  
Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module  
FIRE  
+
Municipal Box  
-
Circuit  
Gamewell Model M34-56  
Local Energy Municipal Box  
Polarities shown in alarm condition  
Nonpower-limited  
+
-
4XTMF  
Figure A.2 Municipal Box Connected to 4XTMF Transmitter Module  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
119  
NFPA Standard-Specific Requirements  
NFPA 72 Auxiliary Fire Alarm System  
NFPA 72 Remote Station Protective Signaling System  
Notes:  
1. Cut Jumper JP30 on the MRP-2001/E main circuit board to supervise placement of the  
4XTMF module.  
2. Refer to "4XTMF Transmitter Module Installation" on page 29 for detailed information.  
RS82 Remote Station Receiver UL listed.  
Refer to Instruction Manual for Remote Station Receiver  
Model RS82.  
Polarity Shown is  
Normal Standby  
+
-
+
Power-limited  
-
(Dummy load with a 4.7KΩ, ¼ watt  
resistor when no connection is made)  
Cutting TBL Jumper allows the  
reverse polarity circuit to open  
with a system trouble condition  
if no alarm condition exists.  
4XTMF Transmitter Module  
Figure C.3 Remote Station Connection Using 4XTMF Module  
120  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA 72 Auxiliary Fire Alarm System  
NFPA Standard-Specific Requirements  
NFPA 72 Proprietary Protective Signaling Systems  
Fire Alarm Control Panel  
FACP Main Circuit Board  
Form-C Alarm contact programmed to  
activate on General Alarm.  
Form-C Trouble contact which will  
automatically activate on any Trouble  
condition.  
Form-C relay contact programmed to  
activate on Supervisory condition.  
Notes:  
1. Connection between the FACP and the  
transmitter are supervised by the transmitter.  
2. This FACP/Transmitter arrangement can be  
employed for NFPA 72 Proprietary  
Protective Signaling System.  
Figure C.4 Proprietary Protective Signaling System  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
121  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA Standard-Specific Requirements  
Central Station/Remote Station Transmitter: Connection to FACP Dry  
C.2 Central Station/Remote Station Transmitter:  
Connection to FACP Dry Contacts  
The dry contacts of the MRP-2001/E programmable relays can be used to trip a UL-864 Listed  
Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central  
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value  
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote  
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter  
manufacturer’s manual for details.  
Typical Central Station/Remote Station Transmitter Module  
Typical Input Zone Triggers  
*Note: The Trouble Relay is a  
fail-safe relay. With power  
applied to the FACP and no  
troubles in the panel, the wiring  
should be connected to the NO  
and C contacts as indicated in the  
illustration.  
Fire Alarm Control Panel  
Figure C.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter  
122  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts  
FACP with Keltron  
APPENDIX D  
FACP with Keltron  
The following figure illustrates the connections between the FACP and Keltron Reveiver/  
Transmitter.  
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are  
not shown in actual order. Follow Keltron manual and module markings for exact terminal  
locations to prevent severe module damage!  
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20  
feet and enclosed within conduit or equivalently protected against mechanical injury.  
Keltron 95M3158 TTM-RPS  
1. Terminals 7 and 8: Remote station alarm/trouble inputs.  
2. Terminals 9 and 10: Sprinkler supervisory input.  
*Note: For more information,  
refer to Keltron manual.  
Sprinkler Supervisory Signal  
Alarm/Trouble Signal  
4XTMF Module  
Note: Cut TBL jumper on 4XTMF module to send  
alarm/trouble signal from the same pair or terminals.  
Fire Alarm Control Panel  
(terminal blocks are not shown in  
their actual positions in order to  
clarify wiring connections)  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
123  
Testing & Maintenance  
APPENDIX E  
E.1 Testing  
Testing  
Testing & Maintenance  
E.1.1 Inspection  
Once installation has been completed, a careful visual inspection should be made before applying  
power to the system. Check the actual wiring hookup with the wiring diagrams. Insure that no  
pieces of wire have fallen into the circuitry. Check for missing or damaged parts.  
E.1.2 Alarm Test  
An initial alarm test should be conducted following installation to determine that all parts of the  
system are functioning properly. The panels should remain powered for 24 to 36 hours prior to  
connecting the releasing solenoids. This precaution will avoid false activation of the suppression  
system in case of faulty or improperly placed detectors.  
To perform an alarm test on the control panel, proceed with the following steps:  
1. Disconnect AC power and battery power  
2. Disconnect the installed solenoid valve circuit leads and connect spare solenoid valves or  
connect an End-of-Line device to serve as a dummy load  
3. Reconnect AC and battery power  
4. Initiate a first zone alarm condition by introducing smoke into one of the Zone 1 detectors.  
This should cause the first zone alarm condition  
The red Fire Alarm indicator will illuminate  
The LCD display will indicate an alarm condition for zone 1  
The control panel piezo will sound  
The Alarm relay will energize  
The devices connected to the Indicating Circuit(s) programmed to activate on Zone 1  
alarm will turn on  
5. Repeat step 4 for each input zone  
6. When testing has been completed, remove AC and battery power, reconnect the solenoid  
valve circuits removed in step 2, reconnect AC and battery power and ensure that the control  
panel is in normal standby condition  
5.4.3 Detector Testing  
Detectors must be tested after installation and following maintenance.  
Important: Before testing, notify the proper authorities that maintenance is being performed and  
the system will be temporarily out of service. Disable the zone or system undergoing maintenance  
to prevent any unwanted alarms. Disconnect the installed solenoid valve circuit leads and connect  
spare solenoid valves or connect an End-of-Line device to serve as a dummy load to prevent  
unwanted water release.  
Ensure proper wiring and power is applied. After power-up, allow 80 seconds for the detectors to  
stabilize before testing. Refer to System Sensor’s i3 Installation and Maintenance Instructions  
document I56-1800-00 for device specifications and testing procedures.  
124  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Testing & Maintenance  
Test i3 Series detectors as follows:  
Test Switch  
1. An opening for the recessed test switch is located on the detector housing.  
2. Insert a small screwdriver or allen wrench (0.18” max.) into the test switch opening; push  
and hold.  
3. If the detector is within the listed sensitivity limits, the detector’s red LED should light  
within five seconds.  
Smoke Entry Test  
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke  
through the detector until it alarms.  
Note: For the above tests, the detector will reset only after the power source has been momentarily  
interrupted.  
If a detector fails any of the above test methods, its wiring should be checked and it should be  
cleaned as outlined in the Maintenance section of the System Sensor Document. If the detector still  
fails, it should be replaced.  
Notify the proper authorities when the system is back in service.  
E.2 Maintenance  
A regular schedule of inspection, testing and maintenance is vital to ensure proper and reliable  
operation of the control panel. The procedures should be performed as required by the local  
authority having jurisdiction. Refer to NFPA documentation for further details.  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
125  
Testing & Maintenance  
Maintenance  
126  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Numerics  
2nd-Shot Water Switch 52  
4XTMF 120  
BB-55  
see also battery box 16  
buttons  
see also control buttons 12  
A
ABB-BUS  
C
wiring distance 30  
AC Loss Delay 65, 67  
AC power 20  
AC power rating 13  
AC power requirements 99  
accessories 16  
cabinet  
mounting 17  
cabinet dimensions 18  
cabinet mounting 19  
CAC-5X 21  
California 62  
ACK  
charger capacity 13  
Charger Disable 64  
charger disable 70  
circuits 11  
Class A 16, 21, 27  
Class A Converter Module 16  
installation 26  
Class B 11, 13, 21  
clear programming 80  
Clock Format 69  
Coded Operation 90  
Coding  
see also Acknowledge 12  
Acknowledge 12  
Acknowledge/Step 14, 85  
Adjective  
list 54  
multiple entries 56  
Alarm 88  
alarm  
piezo pulse rate 15  
alarm relay 11, 24  
contact rating 13  
Alarm Silence 12, 14, 85  
ANN-BUS 98  
NAC 61  
combination circuit 22  
combination waterflow/supervisory 22  
requirements 22  
wiring 22  
compatibility  
see also device compatibility 11  
configuration  
programming 50  
Control Buttons 85  
control buttons 12  
controls 14  
auto-configure 73  
aux. power 33  
device addressing 33  
wiring configuration 32  
wiring distance chart 31  
ANN-BUS Devices 30  
ANN-BUS devices 11  
ANN-BUS modules 72  
ANN-BUS wiring 30  
ANN-I/O  
LED zone assignments 75  
ANN-LED 43, 45  
ANN-LED Annunciator Module 41  
ANN-S/PG module 97  
auto-configure  
cross input zones 63, 94  
Cross-Zone 62  
cross-zoning 63  
current  
nonresettable power 24  
resettable power 24  
total output 23  
ANN-BUS 73  
Autosilence  
NAC 60  
current requirements for system 100, 101  
D
Date setting 69  
Daylight Savings 96  
Daylight Savings Time 70  
Description  
Autosilence Timer 91  
auxiliary power 24  
Auxiliary Trouble Input 13  
B
backbox  
dimensions 15  
mounting 17  
detector label 55  
description 11  
Banner 64  
Detector  
setting 67  
battery 15, 20  
precautions 20  
rating 13  
battery box 16  
adding description 53  
enable/disable 51  
detector functions 90  
device compatibility 11  
dimensions  
battery calculations 102  
backbox 15  
MRP-2001 & MRP-2001E PN 53040:A 4/16/07  
127  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Disable Release 46, 52  
Disable/Enable 89  
DP-51050LED Dress Panel 16  
dress panel 12, 16  
Drill 12, 14, 85  
E
discharge 86  
Fire Alarm 86  
Supervisory 86  
Trouble 86  
Indicators 15  
indicators 12, 14  
Initiating Device Circuit 11, 13, 21  
Class A 27  
earth ground 20  
edit  
detector screens 51  
Enable/Disable 82  
zone 51  
End-of-Line resistor  
IDC 13, 21, 22  
NAC 13, 23  
In-Line resistor  
IDC combination circuit 22  
input zone types 52  
Input Zones 50, 93  
installation 17  
4XTM 29  
Enter key 48  
Erase History 78  
exiting  
programming 47, 48  
Read Status 47, 48  
F
FACP configuration 50  
fail-safe  
class A converter module 26  
option modules 26  
transmitter module 28  
J
J4 and J5  
option module connectors 28  
JP30 jumper  
placement supervision 28  
K
Key Panel 14  
trouble relay 24  
features 11  
Form-C  
see also relay 11  
freeze 21, 89  
function keys 14  
service/program keys 14  
L
freeze signal  
lamp test 14  
see also smoke detector monitoring 11  
H
History 78, 97  
erase 78  
LCD display 11, 14  
LED annunciator module 16  
LED driver module 16, 39  
connections 40  
Maintenance Level 82  
view events 78  
history log 11  
specifications 39  
wiring LEDs 41  
LED option module  
LED zone assignments 75  
M
I
I3 detectors 21  
IDC 11, 13, 21  
alarm current 13  
compatibility 21  
End-of_Line resistor 22  
End-of-Line resistor 13, 21  
maximum loop resistance 13, 21  
short circuit current 13  
standby current 13  
wiring 21  
Main 10  
maintenance 21  
piezo pulse rate 15  
Maintenance Alert 90  
Maintenance Program Level 2 47, 81  
maintenance signal  
see also smoke detector monitoring 11  
Manual programming 46  
Map 53  
Indicator  
March Time 62  
AC Power 12, 15  
Alarm Silence 12, 15  
discharge 12, 15  
Fire Alarm 12, 15  
Supervisory 12, 15  
System Trouble 15  
Trouble 12  
Master Program Level 1 47, 49  
Mode key 48  
Mounting  
main circuit board 17  
mounting  
cabinet 17  
municipal box 29  
municipal box transmitter  
see also 4XTM 16  
indicator  
AC Power 86  
Alarm Silenced 86  
128  
MRP-2001 & MRP-2001E PN 53040:A 4/16/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
N
Piezo  
see also sounder 15  
piezo 15  
alarm 15  
NAC 11, 13  
Auto Silence 60  
coded 90  
current 23  
maintenance 15  
see also sounder 12  
supervisory 15  
trouble 15  
End-of-Line resistor 13, 23  
maximum current 13  
programmable 12  
synchronized 62  
wiring 23  
NFPA 72 Auxiliary Fire Alarm System 116, 119  
NFPA 72 Central Station Service (Protected Premises  
polarity reversal circuit  
see also transmitter module 29  
power 13, 20, 24  
primary 20  
Unit) or Remote Station Service 116  
secondary  
NFPA 72 Proprietary Fire Alarm System 116  
NFPA 72 Proprietary Protective Signaling Systems 121  
NFPA 72 Remote Station Protective Signaling System  
120  
see also battery 20  
power supply calculations 99  
power-limited wiring 25  
Power-up  
NFPA Standard 116  
nonpower-limited wiring 25  
nonresettable power 11, 14, 24  
current 24  
first time 47  
printer connection 38  
printer module 16, 37  
installation 37  
maximum current 14  
Normal 86  
normal display 46  
Notification Appliance Circuit 11, 13, 23  
Class A 27  
specifications 37  
printer options 38, 73  
Program  
clear 80  
program keys  
Noun  
see also Key Panel 14  
Programming 46  
autoprogramming 46  
exiting 47  
list 55  
multiple entries 56  
Noun/Adjective 53, 55  
O
Level 1 47  
Operating Instructions 85  
Operation  
Level 2 47  
manual 46  
alarm 88  
disable/enable 89  
normal 86  
Master Level 1 49  
Programming Levels 47  
Programming Screens 47  
R
supervisory 89  
trouble 87  
waterflow 89  
Read Status 46, 92  
ANN-BUS 98  
Option Modules 71  
option modules 16  
installation 26, 28  
Output  
Configuration 93  
Cross Input Zones 94  
exiting 47  
history 97  
coding 61  
silence inhibit 60  
silenceable 59  
Input Zones 93  
input zones 93  
NAC 94  
output circuit MAP 53  
Output Circuits 57  
output circuits 23  
Output enable/disable 58  
output types 58  
outputs 12  
Output Circuits 94  
Print 97  
relay 95  
Real-Time Clock 90  
Recall/Increment Function 56  
Relay  
P
Form-C 64  
Password 48  
programming 64  
relay 11, 24  
change 80  
Maintenance Level 2 48, 81  
Master Level 1 48  
contact rating 13, 24  
relay module 16  
MRP-2001 & MRP-2001E PN 53040:A 4/16/07  
129  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Relays 64, 95  
Release Circuit 58  
Release Stage 91  
System Settings 95  
System Setup 64  
T
Release Stage NAC 59  
releasing circuit 13  
releasing solenoid 12  
releasing solenoids 11  
remote LCD annunciator  
installation 34  
Temporal 62  
Time setting 69  
Time-Date  
Maintenance Level 84  
Time-Date setting 64, 68  
Timers 64, 96  
timers 65  
Transmitter Module 16  
transmitter module 29  
installation 28, 29  
operation 29  
specifications 29  
transmitter option module  
placement supervision 28  
trim ring 16  
programming 36, 76  
specifications 34  
wiring 35  
remote station service 29  
Remote Station Transmitter Connection to FACP Dry  
Contacts 122  
Reset 12, 14, 85  
resettable power 11, 13, 24  
current 24  
maximum current 13  
reverse polarity circuit  
see also 4XTM 16  
S
Trouble 87  
trouble  
piezo pulse rate 15  
Trouble Input  
Silence Inhibit 60  
Silence Inhibit Timer 91  
Silenceable  
Auxiliary 13  
trouble relay 11, 24  
contact rating 13  
fail-safe 24  
Output 59  
silenceable circuits  
synchronized signals 59  
soak timer 65, 66  
Soak Timers 91  
Trouble Reminder 64, 70, 91  
Type  
zone 51  
type  
sounder 12, 15  
zone 51  
sprinkler standards  
NFPA 12  
types  
outputs 58  
Steady 62  
U
strobes 12, 62  
UL  
maximum 62  
Style B 13, 21  
wiring requirements 25  
V
see also Class B 11  
Style D 16, 21, 27  
Style Y 13  
see also Class B 11  
Style Z 16, 27  
View Events 78  
W
Walktest 79, 91  
audible 79  
Maintenance Level 83  
operation 91  
subscreen 47  
supervision  
silent 79  
transmitter option module placement 28  
Supervisory 11, 89  
supervisory  
piezo pulse rate 15  
supervisory relay 24  
contact rating 13  
Synchronization 62  
synchronization 62  
Synchronized 62  
synchronized 62  
Waterflow Delay timer 65, 66  
Waterflow DelayTimer 91  
waterflow/supervisory circuit 22  
wiring  
ANN-BUS 30  
class A converter module 27  
Class A IDC 27  
Class A NAC 27  
combination waterflow/supervisory 22  
IDC 21  
synchronized signals 62  
and silenceable circuits 59  
system current calculations 100  
NAC 23  
nonpower-limited 25  
power-limited 25  
130  
MRP-2001 & MRP-2001E PN 53040:A 4/16/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
UL requirements 25  
Z
Zone  
type 51  
Zone Setup  
Maintenance Level 82  
zone type  
inputs 52  
MRP-2001 & MRP-2001E PN 53040:A 4/16/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
131  
Testing & Maintenance  
Maintenance  
132  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Testing & Maintenance  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
133  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Testing & Maintenance  
Maintenance  
134  
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
Honeywell International Inc. warrants products manufactured by it  
to be free from defects in materials and workmanship for eighteen  
(18) months from the date of manufacture, under normal use and  
service. Products are date stamped at time of manufacture. The sole  
and exclusive obligation of Honeywell International Inc. is to repair  
or replace, at its option, free of charge for parts and labor, any part  
that is defective in materials or workmanship under normal use and  
service. All returns for credit are subject to inspection and testing at  
the factory before actual determination is made to allow credit.  
Honeywell International Inc. does not warrant products not  
manufactured by it, but assigns to the purchaser any warranty  
extended by the manufacturer of such products. This warranty is void  
if the product is altered or repaired by anyone other than Honeywell  
International Inc. or as expressly authorized by Honeywell  
International Inc. in writing, or is serviced by anyone other than  
Honeywell International Inc. or its authorized distributors. This  
warranty is also void if there is a failure to maintain the products and  
systems in which they operate in a proper and workable manner. In  
case of defect, secure a Return Material Authorization form from our  
Return Authorization Department.  
This writing constitutes the only warranty made by Honeywell  
International Inc., with respect to its products.  
Honeywell  
International Inc., does not represent that its products will prevent  
any loss by fire or otherwise, or that its products will in all cases  
provide the protection for which they are installed or intended. Buyer  
acknowledges that Honeywell International Inc., is not an insurer  
and assumes no risk for loss or damages or the cost of any  
inconvenience, transportation damage, misuse, abuse, accident or  
similar incident.  
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,  
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR  
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS  
BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO  
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.  
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,  
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF  
THE USE OF, OR INABILITY TO USE HONEYWELL  
INTERNATIONAL INC.’S PRODUCTS.  
FURTHERMORE,  
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR  
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE  
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL  
OR INDUSTRIAL USE OF ITS PRODUCTS.  
This warranty replaces all previous warranties and is the only  
warranty made by Honeywell International Inc. No increase or  
alteration, written or verbal, of the obligation of this warranty is  
authorized.  
Warn-HL-05-2007.fm  
Download from Www.Somanuals.com. All Manuals Search And Download.  
World Headquarters  
1 Firelite Place  
Northford, CT 06472-1653 USA  
203-484-7161  
fax 203-484-7118  
www.firelite.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Stroller 6213 851 6 02 User Manual
Grizzly Nail Gun H8235 User Manual
Grundig Flat Panel Television GLCD1906HDVW User Manual
Havis Shields Automobile Accessories C TTB CV User Manual
Honeywell Air Cleaner HFD 120 User Manual
HP Hewlett Packard All in One Printer 6300AF User Manual
Husqvarna Blower 125BVX User Manual
Iluv Portable DVD Player i1155 User Manual
Impex Fitness Equipment MWB 715N User Manual
Impex Home Gym MD 3400 User Manual