Heat Glo LifeStyle Indoor Fireplace 6000TR OAK IPI User Manual

Owner’s Manual  
Installation and Operation  
Models:  
6000TR-OAK  
6000TR-OAK-IPI  
Underwriters  
Laboratories Listed  
READ THIS MANUAL BEFORE INSTALLING OR  
OPERATING THISAPPLIANCE. THIS INSTALLERS  
GUIDE MUST BE LEFT WITH APPLIANCE FOR  
FUTURE REFERENCE.  
WARNING: IMPROPER INSTALLA-  
TION, ADJUSTMENT, ALTERATION,  
SERVICE OR MAINTENANCE CAN  
CAUSE INJURY OR PROPERTY DAM-  
AGE. REFER TO THIS MANUAL. FOR  
ASSISTANCE ORADDITIONAL INFOR-  
MATION CONSULT A QUALIFIED IN-  
STALLER, SERVICE AGENCY, OR THE  
GAS SUPPLIER.  
WARNING: IF THE INFORMATION  
IN THESE INSTRUCTIONS IS NOT  
FOLLOWED EXACTLY, A FIRE OR  
EXPLOSION MAY RESULT CAUS-  
ING PROPERTY DAMAGE, PER-  
SONAL INJURY, OR DEATH.  
1. This appliance may be installed in an af-  
termarket, permanently located, manufac-  
tured (mobile) home, where not prohibited  
by local codes.  
- Do not store or use gasoline or other  
flammable vapors and liquids in the vi-  
cinity of this or any other appliance.  
-
What to do if you smell gas  
• Do not try to light any appliance.  
• Do not touch any electrical switch.  
2. This appliance is only for use with the type  
of gas indicated on the rating plate. This  
appliance is not convertible for use with  
other gases, unless a certified kit is used.  
• Do not use any phone in your build-  
ing.  
• Immediately call your gas supplier from  
a neighbor's phone. Follow the gas  
supplier's instructions.  
Î
In the Commonwealth of Massachusetts:  
• If you cannot reach your gas supplier,  
call the fire department.  
• installation must be performed by a licensed  
plumber or gas fitter;  
- Installation and service must be  
performed by a qualified installer, service  
agency, or the gas supplier.  
See Table of Contents for location of additional  
Commonwealth of Massachusetts requirements.  
Printed in U.S.A. Copyright 2005  
Please contact your Heat & Glo dealer with any  
questions or concerns. For the number of your nearest  
Heat & Glo dealer, please call 1-888-427-3973.  
Heat & Glo, a brand of Hearth & Home Technologies Inc.  
20802 Kensington Boulevard, Lakeville, MN 55044  
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,  
5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165,  
6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802,  
6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250,  
780403, 1418504 or other U.S. and foreign patents pending.  
1
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Safety and Warning Information ................................................ 2  
Service Parts Lists ..................................................................... 4  
Section 1: Approvals and Codes ............................................... 8  
Appliance Certification................................................................... 8  
Installation Codes.......................................................................... 8  
HighAltitude Installations ............................................................... 8  
Requirements for the Commonwealth of Massachusetts ................ 9  
Î
Section 2: Getting Started ....................................................... 10  
Introducing the Heat & Glo Gas Fireplaces ................................. 10  
Pre-installation Preparation ......................................................... 10  
Section 3: Installing the Fireplace .......................................... 12  
Constructing the Fireplace Chase .............................................. 12  
Step 1  
Step 2  
Step 3  
Locating the Fireplace ................................................. 12  
Framing the Fireplace.................................................. 13  
Installing the Vent System............................................ 15  
A. Vent System Approvals........................................... 15  
B. Installing Vent Components.................................... 22  
C. Vent Termination .................................................... 25  
Positioning, Leveling, and  
Î
Step 4  
Securing the Fireplace................................................. 27  
Installing the Optional Heat-Zone-Gas Kit.................... 28  
The Gas Control Systems ........................................... 28  
The Gas Supply Line ................................................... 29  
Gas Pressure Requirements ...................................... 29  
Wiring the Fireplace .................................................... 30  
Step 5  
Step 6  
Step 7  
Step 8  
Step 9  
Step 10 Finishing ...................................................................... 32  
Step 11 Installing Trim, Logs, and Ember Material.................... 33  
Installing the Trim......................................................... 33  
Positioning the Logs .................................................... 33  
Shutter Settings ........................................................... 33  
Placing the Ember Material.......................................... 33  
Glass Specifications .................................................... 33  
Step 12 Before Lighting the Fireplace ....................................... 34  
Step 13 Lighting the Fireplace .................................................. 35  
After the Installation ..................................................................... 35  
Section 4: Maintaining and Servicing Your Fireplace......... 35  
Î = Contains updated information.  
3
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6000TR-OAK  
6000TR-OAK-IPI  
Service Parts  
Beginning Manufacturing Date: 4-01  
Ending Manufacturing Date: 6-06  
(NG, LP) Exploded Parts Diagram  
3
1
2
13  
4
5
12  
6 Log Set Assembly  
9
7
10  
11  
8
Part number list on following page.  
4
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Parts List  
6000TR-OAK, 6000TR-OAK-IPI  
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When order-  
ing, supply serial and model numbers to ensure correct service parts.  
ITEM  
COMMON PARTS  
SERIAL #  
PART NUMBER  
PRE 002324002 385-130  
POST 002324002 2026-108  
1
2
Surround  
Hood  
SRV60-143-BK  
3
Glass Door Assembly  
Burner NG, LP  
Log Grate  
GLA-6TROC  
PRE 002324002 SRV383-338A  
POST 002324002 SRV2025-007A  
4
5
383-360A  
6
Oak Log Set Assembly  
Log 1  
LOGS-6OAK  
SRV385-720  
SRV385-724  
SRV385-721  
SRV385-723  
SRV385-722  
385-401  
7
8
Log 2  
9
Log 3  
10  
11  
12  
Log 4  
Log 5  
Insulation Board  
Flue Restrictor  
Vent Gasket  
385-128  
PRE 002324002 385-411  
POST 002324002 2025-114  
Vermiculite Embers  
Touch-Up Paint  
Mystic-Embers  
TUP-GBK-12  
386-122A  
Glass Latch Sssembly  
Mineral Wool  
050-721  
STANDING PILOT IGNITION ONLY*  
Junction Box  
PRE 002324002 100-250A  
POST 002324002 4021-013  
13  
13  
INTERMITTENT PILOT IGNITION (IPI) *  
PRE 002324002 383-250A  
POST 002324002 4021-013  
Junction Box  
ACCESSORIES  
Fan Kit  
GFK-160A  
Wall Switch Kit, Off-white  
Wall Switch Kit, White  
WSK-21  
WSK-21-W  
Trim Door Mesh  
MESH-6000  
NGK-6TROC  
LPK-6TROC  
NGK-6TROC-IPI  
LPK-6TROC-IPI  
BRICK-6000-FB  
SRV2027-372  
SRV2027-371  
SRV2027-370  
NG Conversion  
LP Conversion  
NG Conversion - IPI  
LP Conversion - IPI  
Wall Refractory Kit (Firebrick, gray mortar lines)  
Wall Refractory Kit - Right Wall (BRICK-6000-FB Kit)  
Wall Refractory Kit - Left Wall (BRICK-6000-FB Kit)  
Wall Refractory Kit - Back Wall (BRICK-6000-FB Kit)  
*Also see pages 6 and 7 for additional IPI and Standing Pilot service part numbers.  
5
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6000TR-OAK-IPI  
Service Parts  
(NG, LP) Exploded Parts Diagram  
Beginning Manufacturing Date: 4-01  
Ending Manufacturing Date: 6-06  
3
Intermittent Pilot Ignition  
ValveAssembly  
13  
10  
12  
11  
9
1
2
6
8
7
4
5
ITEM  
DESCRIPTION  
SERIAL #  
PART NUMBER  
PRE 002324002  
POST 002324002  
550-169  
1
Valve Bracket  
2025-101  
302-320A  
2025-512  
060-521A  
750-500  
750-501  
2
3
4
5
5
Flex Ball Valve Assembly  
Ground Strap  
ON/OFF Rocker Switch  
Valve NG  
Valve LP  
6
Burner Orifice NG (#37C)  
582-837  
6
7
8
Burner Orifice LP (#52C)  
Module  
Wire Assembly  
582-852  
593-592  
593-590A  
477-301A  
383-302A  
385-510A  
4021-025  
385-511A  
4021-026  
N/A  
2026-017  
319-316A  
2026-130  
385-164  
PRE 002324002  
POST 002324002  
PRE 002324002  
POST 002324002  
PRE 002324002  
POST 002324002  
PRE 002324002  
POST 002324002  
PRE 002324002  
POST 002324002  
9
12" Flexible Gas Connector  
Pilot Assembly NG  
10  
10  
11  
Pilot Assembly LP  
Shutter Bracket Assembly  
Shutter Assembly  
12  
13  
Pilot Bracket  
Gasket Assembly  
Battery Pack  
3 Volt Transformer  
385-402A  
593-594A  
593-593A  
6
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6000TR-OAK  
Beginning Manufacturing Date: 4-01  
Ending Manufacturing Date: 6-06  
Service Parts  
(NG, LP) Exploded Parts Diagram  
Standing Pilot Ignition  
ValveAssembly  
6
5
7
12  
3
8
9
10  
4
11  
1
2
ITEM  
DESCRIPTION  
SERIAL #  
PART NUMBER  
1
2
2
ON/OFF Rocker Switch  
Valve NG  
060-521A  
060-522  
060-523  
Valve LP  
PRE 002324002  
POST 002324002  
477-301A  
383-302A  
3
Flexible Gas Connector  
4
5
5
6
Wire Assembly  
Pilot Assembly NG  
Pilot Assembly LP  
Pilot Bracket  
049-552A  
485-510A  
485-511A  
385-164  
PRE 002324002  
POST 002324002  
319-316A  
2026-130  
7
Shutter Assembly  
8
9
Valve Bracket  
2025-101  
302-320A  
291-513  
Flex Ball Valve Assembly  
Piezo Ignitor  
10  
11  
11  
Burner Orifice (NG) (#37C)  
Burner Orifice (LP) (#52C)  
582-837  
582-852  
PRE 002324002  
POST 002324002  
N/A  
2026-017  
12  
Shutter Bracket Assembly  
Gasket Assembly  
385-402A  
7
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Approvals and  
Codes  
1
High Altitude Installations  
Appliance Certification  
U.L. Listed gas appliances are tested and approved with-  
out requiring changes for elevations from 0 to 2,000 feet in  
the U. S. A. and in Canada.  
The Heat & Glo fireplace models discussed in this Installers  
Guide have been tested to certification standards and listed  
by the applicable laboratories.  
When installing this appliance at an elevation above 2,000  
feet, it may be necessary to decrease the input rating by  
changing the existing burner orifice to a smaller size. Input  
rate should be reduced by 4% for each 1000 feet above a  
2000 foot elevation in the U.S.A. or 10% for elevations  
between 2000 and 4500 feet in Canada. If the heating value  
of the gas has been reduced, these rules do not apply. To  
identify the proper orifice size, check with the local gas  
utility.  
Certification  
MODELS: 6000TR-OAK, 6000TR-OAK-IPI  
LABORATORY: Underwriters Laboratories  
TYPE: Direct Vent Gas Fireplace Heater  
STANDARD: ANSIZ21.88-2000•CSA2.33-M98•UL307B  
Installation Codes  
If installing this appliance at an elevation above 4,500 feet  
(in Canada), check with local authorities.  
The fireplace installation must conform to local codes. Before  
installing the fireplace, consult the local building code  
agency to ensure that you are in compliance with all  
applicable codes, including permits and inspections.  
In the absence of local codes, the fireplace installation must  
conform to the National Fuel Gas Code ANSI Z223.1 (in  
the United States) or the CAN/CGA-B149 Installation Codes  
(in Canada). The appliance must be electrically grounded  
in accordance with local codes or, in the absence of local  
codes with the National Electric Code ANSI/NFPA No. 70  
(in the United States), or to the CSAC22.1 Canadian Electric  
Code (in Canada).  
These models may be installed in a bedroom or bed-sitting  
room in the U.S.A. and Canada.  
Heat & Glo Quality Systems  
registered by SGS ICS  
8
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspection  
NOTE: The following requirements reference various  
Massachusetts and national codes not contained in  
this document.  
The state or local gas inspector of the side wall horizontally  
vented gas fueled equipment shall not approve the installa-  
tion unless, upon inspection, the inspector observes carbon  
monoxide detectors and signage installed in accordance with  
the provisions of 248 CMR 5.08(2)(a)1 through 4.  
Î
Requirements for the Commonwealth of  
Massachusetts  
Exemptions  
The following equipment is exempt from 248 CMR 5.08(2)(a)1  
through 4:  
For all side wall horizontally vented gas fueled equipment  
installed in every dwelling, building or structure used in  
whole or in part for residential purposes, including those  
owned or operated by the Commonwealth and where the  
side wall exhaust vent termination is less than seven (7)  
feet above finished grade in the area of the venting, includ-  
ing but not limited to decks and porches, the following re-  
quirements shall be satisfied:  
The equipment listed in Chapter 10 entitled “Equipment  
Not Required To Be Vented” in the most current edition  
of NFPA 54 as adopted by the Board; and  
Product Approved side wall horizontally vented gas fu-  
eled equipment installed in a room or structure sepa-  
rate from the dwelling, building or structure used in whole  
or in part for residential purposes.  
Installation of Carbon Monoxide Detectors  
At the time of installation of the side wall horizontal vented  
gas fueled equipment, the installing plumber or gasfitter  
shall observe that a hard wired carbon monoxide detector  
with an alarm and battery back-up is installed on the floor  
level where the gas equipment is to be installed. In addi-  
tion, the installing plumber or gasfitter shall observe that a  
battery operated or hard wired carbon monoxide detector  
with an alarm is installed on each additional level of the  
dwelling, building or structure served by the side wall hori-  
zontal vented gas fueled equipment. It shall be the respon-  
sibility of the property owner to secure the services of qual-  
ified licensed professionals for the installation of hard wired  
carbon monoxide detectors.  
MANUFACTURER REQUIREMENTS  
Gas Equipment Venting System Provided  
When the manufacturer of ProductApproved side wall hor-  
izontally vented gas equipment provides a venting system  
design or venting system components with the equipment,  
the instructions provided by the manufacturer for installa-  
tion of the equipment and the venting system shall include:  
Detailed instructions for the installation of the venting  
system design or the venting system components; and  
A complete parts list for the venting system design or  
venting system.  
In the event that the side wall horizontally vented gas fu-  
eled equipment is installed in a crawl space or an attic, the  
hard wired carbon monoxide detector with alarm and bat-  
tery back-up may be installed on the next adjacent floor  
level.  
In the event that the requirements of this subdivision can  
not be met at the time of completion of installation, the  
owner shall have a period of thirty (30) days to comply with  
the above requirements; provided, however, that during said  
thirty (30) day period, a battery operated carbon monoxide  
detector with an alarm shall be installed.  
Gas Equipment Venting System NOT Provided  
When the manufacturer of a Product Approved side wall  
horizontally vented gas fueled equipment does not provide  
the parts for venting the flue gases, but identifies “special  
venting systems”, the following requirements shall be sat-  
isfied by the manufacturer:  
The referenced “special venting system” instructions shall  
be included with the appliance or equipment installation  
instructions; and  
Approved Carbon Monoxide Detectors  
Each carbon monoxide detector as required in accordance  
with the above provisions shall comply with NFPA720 and  
be ANSI/UL 2034 listed and IAS certified.  
The “special venting systems” shall be ProductApproved  
by the Board, and the instructions for that system shall  
include a parts list and detailed installation instructions.  
A copy of all installation instructions for all Product Ap-  
proved side wall horizontally vented gas fueled equipment,  
all venting instructions, all parts lists for venting instruc-  
tions, and/or all venting design instructions shall remain  
with the appliance or equipment at the completion of the  
installation.  
Signage  
A metal or plastic identification plate shall be permanently  
mounted to the exterior of the building at a minimum height  
of eight (8) feet above grade directly in line with the ex-  
haust vent terminal for the horizontally vented gas fueled  
heating appliance or equipment. The sign shall read, in  
print size no less than one-half (1/2) inch in size, “GAS  
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-  
STRUCTIONS”.  
See Gas Connection section for additional Common-  
wealth of Massachusetts requirements.  
9
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
2
The Heat & Glo Warranty will be voided by, and Heat & Glo  
disclaims any responsibility for, the following actions:  
Introducing the Heat & Glo Gas Fireplaces  
Heat & Glo direct vent gas fireplaces are designed to oper-  
ate with all combustion air siphoned from outside of the  
building and all exhaust gases expelled to the outside.  
Installation of any damaged fireplace or vent system  
component.  
Modification of the fireplace or direct vent system.  
Installation other than as instructed by Heat & Glo.  
Improper positioning of the gas logs or the glass door.  
The information contained in this Installers Guide, unless  
noted otherwise, applies to all models and gas control  
systems. Gas fireplace diagrams, including the dimensions,  
are shown in this section.  
Installation and/or use of any component part not manu-  
factured and approved by Heat & Glo, not withstanding  
any independent testing laboratory or other party approval  
of such component part or accessory.  
Pre-install Preparation  
This gas fireplace and its components are tested and safe  
when installed in accordance with this Installers Guide.  
Report to your dealer any parts damaged in shipment,  
particularly the condition of the glass. Do not install any  
unit with damaged, incomplete, or substitute parts.  
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE  
HAZARD.  
When planning a fireplace installation, it’s necessary to  
determine:  
The vent system components and trim doors are shipped  
in separate packages. The gas logs may be packaged  
separately and must be field installed.  
Where the unit is to be installed.  
The vent system configuration to be used.  
Gas supply piping.  
Read all of the instructions before starting the  
installation. Follow these instructions carefully during  
the installation to ensure maximum safety and benefit.  
Failure to follow these instructions will void the  
owner’s warranty and may present a fire hazard.  
Electrical wiring.  
Framing and finishing details.  
Whether optional accessories—devices such as a fan,  
wall switch, or remote control—are desired.  
If the fireplace is to be installed on carpeting or tile, or on  
any combustible material other than wood flooring, the  
fireplace should be installed on a metal or wood panel that  
extends the full width and depth of the fireplace.  
10  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
28 1/2 [724mm]  
14 1/4  
[362mm]  
21 1/2 [548mm]  
8 [203mm]  
VENT COLLARS  
11 5/8 [297mm]  
8
ELECTRICAL  
ACCESS  
[203mm]  
VENT  
COLLARS  
GAS LINE  
ACCESS  
34 5/8  
[879mm]  
38  
[965mm]  
25 1/4  
[642mm]  
26 7/8  
[682mm]  
2 1/8  
[55mm]  
3 1/2  
[90mm]  
36 1/8  
[916mm]  
12 3/4  
[323mm]  
41  
6 7/8 [174mm]  
[1040mm]  
TOP STANDOFFS  
TOP VENT COLLARS  
REAR VENT COLLARS  
HOOD  
TRIM  
DOOR  
RATING PLATE  
AND LABELS  
GAS  
LINE  
ACCESS  
ELECTRICAL  
ACCESS  
GAS  
CONTROLS  
Figure 1. Diagram of the 6000TR-OAK, 6000TR-OAK-IPI  
11  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1” MIN. (25mm)  
B
A
Installing the Fireplace  
3
Constructing the Fireplace Chase  
A chase is a vertical box-like structure built to enclose the  
gas fireplace and/or its vent system. Vertical vents that run  
on the outside of a building may be, but are not required to  
be, installed inside a chase.  
D
E
C
CAUTION: TREATMENT OF FIRESTOP SPACERS AND  
CONSTRUCTION OF THE CHASE MAY VARY WITH THE  
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT  
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL  
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-  
ING CODES MUST BE CHECKED TO DETERMINE THE  
REQUIREMENTS FOR THESE STEPS.  
1/2” MIN. (13mm)  
A
42”  
Note* 42”  
B
22”  
22”  
C
36”  
40”  
D
E
51”  
57”  
72”  
80”  
*If venting with (2) 900 elbows off rear of unit  
the dimensions C, D, and E, will change.  
Figure 2. Fireplace Dimensions, Locations,  
and Space Requirements  
Factory-built fireplace chases should be constructed in the  
manner of all outside walls of the home to prevent cold air  
drafting problems. The chase should not break the outside  
building envelope in any manner.  
Minimum Clearances  
from the Fireplace to Combustible Materials  
Inches  
mm  
This means that the walls, ceiling, base plate and cantile-  
ver floor of the chase should be insulated. Vapor and air  
infiltration barriers should be installed in the chase as per  
regional codes for the rest of the home. Additionally, in re-  
gions where cold air infiltration may be an issue, the inside  
surfaces may be sheetrocked and taped for maximum air  
tightness.  
Glass Front........................ 36 .................... 914  
Floor ................................... 0 ....................... 0  
Rear ...................................1/2 ..................... 13  
Sides .................................1/2 ..................... 13  
Surround Sides*.................. 0 ....................... 0  
Top ................................... 3 1/2 ................... 89  
Ceiling** ............................. 31 .................... 787  
To further prevent drafts, the wall shield and ceiling firestops  
should be caulked with high temperature caulk to seal gaps.  
Gas line holes and other openings should be caulked with  
high temp caulk or stuffed with unfaced insulation. If the  
appliance is being installed on a cement slab, a layer of  
plywood may be placed underneath to prevent conducting  
cold up into the room.  
* See Figure 3.  
** The clearance to the ceiling is measured from the top  
of the unit, excluding the standoffs (see Figure 38).  
The distance from the unit to combustible construction  
is to be measured from the unit outer wrap surface to  
the combustible construction, NOT from the screw heads  
that secure the unit together.  
THE CHASE SHOULD BE CONSTRUCTED SO THATALL  
CLEARANCES TO THE FIREPLACE ARE MAINTAINED  
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.  
Minimum Clearances  
from the Vent Pipe to Combustible Materials  
Inches  
mm  
Step 1.  
Locating the Fireplace  
Vertical Sections. ............. 1 ................ 25  
The following diagram shows space and clearance require-  
ments for locating a fireplace within a room.  
Horizontal Sections  
Top ..................................... 3 ................ 75  
Bottom ............................... 1 ................ 25  
Sides ................................. 1 ................ 25  
Clearance Requirements  
The top, back, and sides of the fireplace are defined by  
stand-offs. The minimum clearance to a perpendicular wall  
extending past the face of the fireplace is one inch (25 mm).  
The back of the fireplace may be recessed 21 1/2 inches  
(546 mm) into combustible construction.  
At Wall Firestops  
Top .................................. 2 1/2 ............63.7  
Bottom .............................. 1/2 ............... 13  
Sides ................................. 1 ................ 25  
For minimum clearances, see the direct vent termination  
clearance diagrams on pages 24 and 25 in this manual.  
12  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2. Framing the Fireplace  
Fireplace framing can be built before or after the fireplace is  
set in place. Framing should be positioned to accommo-  
date wall coverings and fireplace facing material. The dia-  
gram below shows framing reference dimensions.  
CAUTION: MEASURE FIREPLACE DIMENSIONS AND  
VERIFY FRAMING METHODS AND WALL COVERING  
DETAILS BEFORE FRAMING.  
Framing should be  
constructed of 2 X 4  
lumber or heavier.  
Noncombustible zone is defined  
by 3” above the elbow for the  
entire width and depth (behind  
the front header) of the firebox.  
B
WALL  
STUD  
3”  
C
A. ............. 42”*  
B. .........38 1/2”  
C. ............... 22”  
D. .........42 3/4”  
E. .........27 7/8”  
A
3 1/2”  
1/2” CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE  
1/2” CLEARANCE  
FROM BOTH SIDES  
OF FIREPLACE  
E
D
TO COMBUSTIBLE  
FRAMING  
MEMBER  
Shows center of 10” x 12” vent framing  
holes for top and rear venting. The center  
of the hole is one (1) inch (25.4mm) above  
the center of the horizontal vent pipe.  
0” CLEARANCE TO  
FRAMING MEMBER  
0” CLEARANCE  
Figure 3. Framing Dimensions  
13  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
6
12  
DVP4  
DVP6  
DVP12  
14-1/4  
12-3/16  
MAX.  
2
MIN.  
24  
36  
DVP12A  
48  
9-7/8  
DVP24  
45.0O  
10-1/4  
DVP45  
DVP36  
11-1/4  
7-1/4  
1-1/4 TYP  
DVP48  
1/2 TYP  
8-9/16  
12-9/16  
DVP  
90ST  
NOTE: PIPES OVERLAP 1-1/4 INCHESAT EACH JOINT.  
Figure 4. DVP-Series Direct Vent Component Specifications (5-inch inner pipe / 8-inch outer pipe)  
14  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3. Installing the Vent System  
A. Vent System Approvals  
Identifying Vent Components  
The vent systems installed on this gas fireplace may in-  
clude one, two, or three 90° elbow assemblies. The rela-  
tionships of vertical rise to horizontal run in vent configura-  
tions using 90° elbows MUST BE strictly adhered to. The  
rise to run relationships are shown in the venting drawings  
and tables. Refer to the diagrams on the next several pages.  
These models are approved to use DVP-series direct vent  
pipe components and terminations (see Figures 4 and 5).  
Approved vent system components are labeled for identifi-  
cation. This pipe is tested and listed as an approved com-  
ponent of the fireplace. The pipe is tested to be run inside  
an enclosed wall. There is no requirement for inspection  
openings at each joint within the wall. There is no required  
pitch for horizontal vent runs. NO OTHER VENTING SYS-  
TEMS OR COMPONENTS MAY BE USED.  
NOTE: Two 45° elbows may be used in place of one  
90° elbow. Rise to run ratios in the vent system must  
be followed if 45° elbows are used.  
Detailed installation instructions are included with each vent  
termination kit and should be used in conjunction with this  
Installers Guide.  
This model has vent starting collars on both the top and the  
back of the unit. Depending upon the installation, decide  
which ONE set of starting collars will be used to attach the  
vent system. The starting collar sealing cap must remain  
on the starting collar NOT used.  
The flame and ember appearance may vary based on the type  
of fuel burned and the venting configuration used.  
STORM COLLAR  
ROOF FLASHING  
VERTICAL  
TERMINATION  
HORIZONTAL  
TERMINATION  
PIPE LENGTH  
Terminations Kits  
WALL FIRESTOP  
90 DEGREE  
ELBOW  
PVK-80  
(For use on IPI units only)  
CEILING  
FIRESTOP  
DVP-TRAP  
SERIES  
DVP-TB1  
(Required to have a minimum of 3  
feet of vertical in the vent system)  
DVP-TVHW  
Figure 5. Vent System Components and Termination Kits  
15  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flue Restrictor Instructions  
CAP  
1. Remove Exhaust Shield using a 1/4” nut driver by  
removing the four screws securing it in place (see  
Figure 7).  
STRAIGHT UP  
VERTICAL VENTING  
V (FT.)  
40' MAX. (12.4 M)  
V
EXHAUST  
SHIELD  
NOTE: On vertical venting  
configurations over 10 feet  
install the flue restrictor  
(385-128). See flue restric-  
tor installation instructions.  
FLUE  
RESTRICTOR  
Figure 7  
2. Break the Flue Restrictor into two pieces. Do this  
by bending the part back and forth until it breaks  
(see Figure 8).  
Figure 6.  
Straight Up Vertical Venting  
BREAK  
HERE  
Figure 8. Flue Restrictor  
16  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Match the amount of vertical you have in the sys-  
tem with the chart to find the appropriate position  
to set the Flue Restrictor (see Figure 9).  
HORIZONTALVENTING  
Kit No.  
H Max. Run  
DVP-TRAP  
24" (610 mm)  
- CHART -  
Top Vent  
NG  
Top Vent  
LP  
Rear Vent  
NG  
Rear Vent  
LP  
Vertical  
4'  
No  
Restrictor  
No  
Restrictor  
No  
Restrictor  
1-1  
2-2  
3-3  
3-4  
3-4  
4-4  
4-4  
5-4  
No  
Restrictor  
8'  
1-2  
3-2  
3-3  
3-3  
3-4  
3-4  
4-4  
1-1  
2-2  
3-3  
3-3  
3-4  
3-4  
4-4  
15'  
20'  
25'  
30'  
35'  
40'  
1-2  
2-3  
2-3  
3-3  
3-3  
3-4  
H
90-DEGREE  
ELBOWS  
45-DEGREE  
ELBOW  
Í
Figure 9.  
4. Center the Flue Restrictor on vent and secure in  
place by using two self-tapping screws (see Fig-  
ure 10).  
5. Reinstall the Exhaust Shield.  
1
2
3
4
5
NOTE: This model is tested and approved to  
use 45° elbows in corner installations. Howev-  
er, 90° elbows will result in better performance.  
SETTINGS  
Figure 11. Corner Installation  
1
2
3
4
5
Figure 10  
17  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH ONE (1) 90° ELBOW  
V
H
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6' MAX. (1.86m)  
8' MAX. (2.4m)  
V+H=40' MAX. (12.4m)  
H = 8' MAX. (2.4m)  
V
NOTE: On vertical venting configurations, where  
the vertical component is over 10 feet, install  
the flue restrictor included in the manual bag  
assembly to improve flame appearance.  
H
Figure 12. Venting with One 90° Elbow  
VENTING WITH ONE (1) 90° ELBOW  
V (FT.)  
H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
H
V
V+H= 40’ MAX. (12.4MM) H = 20' MAX. (6.2m)  
H
V
NOTE: For corner installations:A6-inch (152mm)  
section of straight pipe may need to be attached to  
the fireplace before a 90o elbow, to allow the vent  
pipe to clear the top standoffs.  
NOTE: If a 90o elbow is first attached to the unit,  
the maximum horizontal run is 3-feet (914mm).  
Figure 13. Venting with One 90° Elbow  
18  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH TWO (2)  
90° ELBOWS  
H
1
V
H
V
H
H + H1  
1´ MIN. (305 mm)  
2´ MIN. (610 mm)  
3´ MIN. (914 mm)  
4´ MIN. (1.22 m)  
2´ MAX. (610 mm)  
4´ MAX. (1.22 m)  
6´ MAX. (1.86 m)  
8´ MAX. (2.48 m)  
5´ MAX. (1.52m)  
10´ MAX. (3.1m)  
15´ MAX. (4.65m)  
20´ MAX. (6.2m)  
V+H+H1 = 40´ MAX. (12.4 m) H = 8´ MAX. (2.48 m) H+H1 = 20´ MAX. (6.2m)  
Figure 14. Venting with Two 90° Elbows  
VENTING WITH TWO (2) 90o ELBOWS  
V FT.  
H + H1 (FT.)  
5´ MAX. (1.52m)  
10´ MAX. (3.1m)  
15´ MAX. (4.65m)  
20´ MAX. (6.2m)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
V+H+H1= 40' MAX.(12.4m) H+H1 = 20´ MAX. (6.2m)  
V+V1+H= 40' MAX.(12.4m)  
V
1
V
H
Î
H1  
V
H
Figure 15. Venting with Two 90° Elbows  
19  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH THREE (3) 90° ELBOWS  
V
H
H + H1  
1´MIN. (305mm)  
2´MIN. (610mm)  
3´MIN. (914mm)  
4´MIN. (1.22m)  
2´MAX. (610mm)  
4´MAX. (1.22m)  
6´MAX. (1.86m)  
8´MAX. (2.48m)  
5´MAX. (1.52m)  
10´MAX. (3.1m)  
15´MAX. (4.65m)  
20´MAX. (6.2m)  
V1+V+H+H1 = 40´ MAX.(12.4 m) H = 8´MAX.(2.48 m) H+H1 = 20´MAX.(6.2 m)  
V
1
V
H
1
H
V
H
H + H1 + H2  
1´MIN. (305mm)  
2´MIN. (610mm)  
3´MIN. (914mm)  
4´MIN. (1.22m)  
2´MAX. (610mm)  
4´MAX. (1.22m)  
6´MAX. (1.86m)  
8´MAX. (2.48m)  
5´MAX. (1.52m)  
10´MAX. (3.1m)  
15´MAX. (4.65m)  
20´MAX. (6.2m)  
1
2
V+H+H +H = 40´ MAX. (12.4 m)  
H = 8´ MAX. (2.48 m)  
H+H1+H2 = 20´ MAX. (6.2 m)  
Î
V
H2  
H1  
H
Figure 16. Venting with three 90° elbows  
20  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH THREE (3) 90° ELBOWS  
H + H1 (FT.)  
Î
V (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
NOTE: H + H1 = 20' MAX. (6.2m)  
V + V1 + H + H1= 40' MAX. (12.4m)  
H
1
V
1
V
H
V
1
H
1
V
H
V + V1 (FT.)  
H + H1 (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
H +H1 = 20' MAX. (6.2m)  
NOTE: V+V1+H +H1 = 40' MAX. (12.4m)  
Figure 17. Venting with three 90° elbows  
21  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Installing Vent Components  
After determining which set of starting collars will be used  
(top or rear), follow venting instructions accordingly.  
1. Attach the First Vent Component to the  
Starting Collars  
To attach the first vent component to the starting collars of  
the fireplace:  
Venting Out the Rear Vent  
Remove the installed rear seal cap from the rear starting  
collars by cutting the strap at each end. (see Figure 18).  
Follow the vent configuration tables accordingly.  
• Make sure that the fiberglass gasket supplied in the  
manual bag seals between the first 8 inch (203mm)  
vent component and the outer fireplace wrap. Using 2  
self-tapping screws from the manual bag secure that  
gasket to the outer wrap (see Figure 19).  
Remove the insulation from the REAR five inch flue, pull  
the heat shield out from outside of the firebox.  
WARNING: THE TOP HEAT SHIELD (INSIDE  
THE FIREBOX) MUST REMAIN ATTACHED IF  
THE VENT SYSTEM IS ATTACHED TO THE  
REAR STARTING COLLARS. SEE FIGURE 18.  
!
OUTER  
WRAP  
FIRST VENT  
COMPONENT  
FIBERGLASS  
GASKET  
Venting Out the Top Vent  
Remove the two screws in the top vent collar seal cap and  
remove the top vent collar seal cap and two pieces of in-  
sulation inside the top two starting collars (See Figure 18).  
Remove the heat shield from inside the TOP five inch flue  
from outside of the firebox.  
The glass must be taken off again for positioning the logs  
when the unit is finally installed in place and finished around  
it. Re-install the glass door. Attach vent system to the top  
starting collars.  
Figure 19. Fiberglass Gasket  
WARNING: THE REAR VENT COLLAR SEAL  
CAP MUST REMAINATTACHED TO THE REAR  
!
DVP PIPE:  
VENT COLLARS IF THE VENT SYSTEM IS AT-  
TACHED TO THE TOP STARTING COLLARS.  
1. Attaching the Venting to the Fireplace  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
WARNING: FAILURE TO REMOVE INSULATION  
IN THE SET OF COLLARS YOU ARE USING  
!
COULD CAUSE A FIRE.  
2. Assembling Vent Sections  
WARNING:YOU MUST LEAVE THE INSULATION  
IN PLACE IN THE SET OF COLLARS YOU ARE  
NOT USING.  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
!
WARNING: ENSURE THAT THE FIBERGLASS  
GASKET SUPPLIED WITH THE FIREPLACE  
SEALS BETWEEN THE FIRST VENT COMPONENT  
AND THE OUTER FIREPLACE WRAP.  
!
Venting Out Top  
Venting Out Rear  
SEAL  
CAP  
SEAL  
CAP  
If the installation is for a termination cap attached directly  
to the fireplace, skip to the sections, Install Firestops and  
Vent Termination.  
HEAT  
SHIELD  
INSULATION  
DISCARD BOTH  
PIECES and  
HEAT SHIELD  
HEAT  
SHIELD  
DISCARD  
INSULATION  
and  
HEAT SHIELD  
CUT  
HERE  
Cut the seal cap  
strap and remove white  
gasket material.  
Figure 18  
22  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Continue Adding Vent Components  
• If the combustible materials are not in place at the time  
of install the elbow heat shield may be screwed to the  
exhaust pipe (see Figure 22). Cut the tabs as shown  
and bend down. Secure the heat shield to the pipe main-  
taining 3” to 4” between the pipe and shield.  
WARNING: INSTALLATION OF THIS FIREPLACE  
REQUIRES THE USE OF HEAT SHIELD 570-290  
ABOVE THE FIRST 900 ELBOW IN THE VENTING  
SYSTEM.  
SCREW  
To Install the Heat Shield:  
1. Determine if the heat shield is required. Do so by mea-  
suring the vertical distance between the top horizontal  
surface of the elbow to any combustible surface above.  
If the distance is more than 4 inches, the heat shield is  
NOT required. If it is 4 inches or less, the heat shield IS  
REQUIRED. Install per the following steps. See Figure 20.  
3”  
(76mm)  
COMBUSTIBLE  
SURFACE  
Figure 22  
3” MIN.  
(76mm)  
HEAT  
SHIELD  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
• Continue adding vent components, locking each succeed-  
ing component into place.  
• Ensure that each succeeding vent component is secure-  
ly fitted and locked into the preceding component in the  
vent system.  
• 90° elbows may be installed and rotated to any point  
around the preceding component’s vertical axis. If an el-  
bow does not end up in a locked position with the pre-  
ceding component, attach with a minimum of two (2)  
sheet metal screws.  
Figure 20  
4. Install Support Brackets  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
2. Fasten the shield in place using the four pilot holes pro-  
vided in the part. The shield should be oriented such that  
the 13 1/8 inch dimension (longest dimension) is run-  
ning in the same direction the elbow is pointing. The  
shield should be centered directly above the elbow, and  
positioned so that it creates a 1/2 inch airspace between  
the shield and the combustible surface. See Figure 21.  
CORRECT  
INCORRECT  
COMBUSTIBLE SURFACE  
DIRECTION  
UP  
HEAT SHIELD  
900ELBOW  
Figure 21  
23  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Vertical Runs - One ceiling firestop is REQUIRED at  
5. Install Firestops  
the hole in each ceiling through which the vent passes.  
For Horizontal Runs - Firestops are REQUIRED on both  
To install firestops for vertical runs that pass through ceilings:  
sides of a combustible wall through which the vent passes.  
NOTE: Model DVP-TRAP does not need an exterior  
firestop on an exterior combustible wall.  
• Position a plumb bob directly over the center of the verti-  
cal vent component.  
To install firestops for horizontal runs that pass through  
either interior or exterior walls:  
• Mark the ceiling to establish the centerpoint of the vent.  
• Drill a hole or drive a nail through this centerpoint.  
• Cut a 10-inch by 12-inch (254mm x 305mm) hole through  
the wall.  
• Check the floor above for any obstructions, such as wir-  
ing or plumbing runs.  
NOTE: The center of the hole is one (1) inch (25.4mm)  
above the center of the horizontal vent pipe.  
• Reposition the fireplace and vent system, if necessary,  
to accommodate the ceiling joists and/or obstructions.  
• Position the firestops on both sides of the hole previ-  
ously cut and secure the firestops with nails or screws.  
• Cut an 10-inch x 10-inch (254mm x 254mm) hole through  
the ceiling, using the centerpoint previously marked.  
• The heat shields of the firestops MUST BE placed to-  
wards the top of the hole.  
• Frame the hole with framing lumber the same size as the  
ceiling joists.  
• Continue the vent run through the firestops.  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
10" (254mm)  
10" (254mm)  
CHIMNEY  
HOLE  
10"  
INTERIOR  
WALL SHIELD  
EXISTING CEILING  
JOISTS  
NEW  
FRAMING  
MEMBERS  
CEILING  
12"  
Figure 25. 10" x 10" Hole & New Framing Members  
If the area above the ceiling is NOT an attic, position and  
secure the ceiling firestop on the ceiling side of the previously  
cut and framed hole.  
Figure 23. 10" x 12" Hole and Vent Pipe  
HEAT SHIELD  
TRIM HEAT  
SHIELD IF TOO  
LONG, ADD TO  
SHIELD IF TOO  
SHORT  
EXTERIOR  
FIRESTOP  
INTERIOR  
FIRESTOP  
Figure 24. Heat Shield, Interior & Exterior Firestops  
24  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Vent Termination  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
Horizontal Termination  
The termination kit should pass through the wall firestops  
from the exterior of the building.  
JOIST  
Adjust the termination cap to its final exterior position  
on the building and interlock the flue sections.  
WARNING: THE TERMINATION CAP MUST BE  
POSITIONED SO THAT THEARROW IS POINT-  
ING UP.  
!
CEILING  
WARNING: VENTING TERMINALS SHALL  
NOT BE RECESSED INTO A WALL OR SID-  
!
NAILS (4 REQUIRED)  
CEILING FIRESTOP  
ING. VENT TERMINATION CLEARANCES MUST  
BE FOLLOWED TO AVOID FIRE DANGER. SEE  
VENT TERMINATION MINIMUM CLEARANCES DI-  
AGRAM ON FOLLOWING PAGE.  
Figure 26. Ceiling Firestop (Ceiling Side)  
If the area above the ceiling IS an attic, position and secure  
the firestop on top of the previously framed hole.  
NOTE: Keep insulation away from the vent pipe at least  
1 inch (25mm).  
NAILS (4 REQUIRED)  
RAFTER  
7-1/4 in.  
(184mm)  
Figure 28. Trapezoid Termination Cap  
CEILING  
CEILING FIRESTOP  
Figure 27. Attic Firestop  
25  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M
N
P
G
R
v
A
H
D
Q
(See Note 2)  
v
V
B
L
U.S.  
(3 FT)  
B
T
v
v
v
B
v
S
S
Electrical  
Service  
V
V
F
v
M
I
D*  
V
v
X
A
J or K  
X
= VENT TERMINAL  
=AIR SUPPLY INLET  
= AREA WHERE TERMINAL IS NOT PERMITTED  
V
A
B
= 12" ....................... clearances above grade, veran-  
K
= 3 ft. (U.S.A.)  
(See Note 1)  
da, porch, deck or balcony  
6 ft. (Canada) ......... clearance to a mechanical  
air supply inlet  
= 12" ....................... clearances to window or door  
that may be opened, or to per-  
L** = 7 ft. ......................... clearance above paved  
(See Note 1)  
sidewalk or a paved driveway  
located on public property  
manently closed window.  
D*  
= 18" ....................... vertical clearance to unventilat-  
ed soffit or to ventilated soffit lo-  
M*** = 18" ......................... clearance under veranda,  
porch, deck, balcony or over-  
hang  
cated above the terminal  
*30” ...................... for vinyl clad soffits and below  
electrical service  
42” ......................... vinyl  
N
P
= 6” ........................... non-vinyl sidewalls  
12” ......................... vinyl sidewalls  
F
=
9" ........................ clearance to outside corner  
= 8 ft.  
G
H
= 6" ......................... clearance to inside corner  
= 3 ft. (Canada) ...... not to be installed above a gas  
meter/regulator assembly within  
______________________________Q___M_I_N___________________________________  
______1__c__a_p__________________3___f_e_e__t_________________2__x___Q___A_C_T_U_A_L____  
______2__c__a_p__s________________6___f_e_e__t_________________1__x___Q___A_C_T_U_A_L____  
______3__c__a_p__s_________________9__f_e_e__t_______________2_/_3__x___Q___A_C_T_U_A__L___  
4 caps 12 feet 1/2 x Q ACTUAL  
RMAX  
3 feet (90cm) horizontally from the  
center-line of the regulator  
I
= 3 ft. (U.S.A.)  
6 ft. (Canada) ...... clearance to gas service regu-  
lator vent outlet  
= 9" (U.S.A.)  
QMIN = # termination caps x 3  
RMAX = (2 / # termination caps) x QACTUAL  
J
12" (Canada) ........ clearance to non-mechanical air  
supply inlet to building or the  
combustion air inlet to any other  
appliance  
S = 6" .......................... clearance from sides of elec-  
(See Note 5)  
trical service  
T
= 12" ......................... clearance above electrical  
(See Note 5)  
service  
** a vent shall not terminate directly above a sidewalk or paved  
driveway which is located between two single family dwellings  
and serves both dwellings.  
NOTE 3: Local codes or regulations may require different  
clearances.  
NOTE 4: Termination caps may be hot. Consider their proximity to  
doors or other traffic areas.  
*** only permitted if veranda, porch, deck or balcony is fully open on  
a minimum of 2 sides beneath the floor, or meets Note 2.  
NOTE 5: Location of the vent termination must not interfere with  
access to the electrical service.  
NOTE 1: On private property where termination is less than 7 feet  
above a sidewalk, driveway, deck, porch, veranda or balcony, use of  
a listed cap shield is suggested.  
WARNING: In the U.S: Vent system termination is NOT permitted  
in screened porches. You must follow side wall, overhang and  
ground clearances as stated in the instructions.  
NOTE 2: Termination in an alcove space (spaces open only on one side  
and with an overhang) are permitted with the dimensions specified for  
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum  
between termination caps. 2. All mechanical air intakes within 10 feet  
of a termination cap must be a minimum of 3 feet below the termination  
cap. 3. All gravity air intakes within 3 feet of a termination cap must be  
a minimum of 1 foot below the termination cap.  
In Canada: Vent system termination is NOT permitted in screened  
porches. Vent system termination is permitted in porch areas  
with two or more sides open. You must follow all side walls,  
overhang and ground clearances as stated in the instructions.  
Heat & Glo assumes no responsibility for the improper perfor-  
mance of the fireplace when the venting system does not meet  
these requirements.  
Figure 29. Minimum Clearances for Terminations  
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE  
INSTALLED.  
26  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: MAJOR U.S. BUILDING CODES  
SPECIFY MINIMUM CHIMNEY AND/OR VENT  
HORIZONTAL  
OVERHANG  
!
HEIGHTABOVE THE ROOF TOP. THESE MINIMUM  
HEIGHTS ARE NECESSARY IN THE INTEREST OF  
SAFETY. SEE FIGURE 30 FOR MINIMUM HEIGHTS,  
PROVIDED THE TERMINATION CAP IS AT LEAST  
20 INCHES FROMA VERTICAL WALLAND 2-FEET  
BELOWA HORIZONTAL OVERHANG.  
2 FT.  
MIN.  
20 INCH MIN.  
VERTICAL  
WALL  
LOWEST  
DISCHARGE  
OPENING  
TERMINATION  
CAP  
X
NOTE: This also pertains to vertical vent systems in-  
stalled on the outside of the building.  
12  
ROOF PITCH  
IS X/ 12  
To seal the roof hole, and to divert rain and snow from the  
vent system:  
H (MIN.) - MINIMUM HEIGHT FROM ROOF  
TO LOWEST DISCHARGE OPENING  
• Attach a flashing to the roof using nails, and use a non-  
hardening mastic around the edges of the flashing base  
where it meets the roof.  
• Attach a storm collar over the flashing joint to form a  
water-tight seal. Place non-hardening mastic around the  
joint, between the storm collar and the vertical pipe.  
Roof Pitch  
H (min.) ft.  
flat to 6/12  
6/12 to 7/12  
over 7/12 to 8/12  
over 8/12 to 9/12  
over 9/12 to 10/12  
over 10/12 to 11/12  
over 11/12 to 12/12  
over 12/12 to 14/12  
over 14/12 to 16/12  
over 16/12 to 18/12  
over 18/12 to 20/12  
over 20/12 to 21/12  
1.0  
1.25  
• Slide the termination cap over the end of the vent pipe  
and snap into place.  
1.5  
2.0  
2.5  
3.25  
4.0  
5.0  
6.0  
7.0  
7.5  
8.0  
Step 4. Positioning, Leveling, and  
Securing the Fireplace  
The diagram below shows how to properly position, level,  
and secure the fireplace.  
Figure 30. Minimum Height from Roof to  
Lowest Discharge Opening  
For Vertical Terminations - To locate the vent and install  
the vent sections:  
• Locate and mark the vent centerpoint on the underside  
of the roof, and drive a nail through the centerpoint.  
• Make the outline of the roof hole around the centerpoint  
nail.  
NAILING TABS  
(BOTH SIDES)  
• The size of the roof hole framing dimensions depend on the  
pitch of the roof. There MUST BE a 1-inch (25.4mm) clear-  
ance from the vertical vent pipe to combustible materials.  
• Mark the roof hole accordingly.  
Figure 31. Proper Positioning,  
• Cover the opening of the installed vent pipes.  
• Cut and frame the roof hole.  
Leveling and Securing of a Fireplace  
• Place the fireplace into position.  
• Use framing lumber the same size as the roof rafters  
and install the frame securely. Flashing anchored to the  
frame must withstand heavy winds.  
• Level the fireplace from side to side and front to back.  
• Shim the fireplace with non-combustible material, such  
as sheet metal, as necessary.  
• Continue to install concentric vent sections up through  
the roof hole (for inside vent installations) or up past the  
roof line until you reach the appropriate distance above  
the roof (for outside terminations).  
• Secure the fireplace to the framing by nailing or screwing.  
27  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 6. The Gas Control Systems  
Step 5.  
Installing the Optional Heat-Zone-Gas Kit  
WARNING: THIS UNIT IS NOT FOR USE WITH  
SOLID FUEL.  
!
NOTE: There must be NO INSULATION or other com-  
bustibles inside the framed firestop opening.  
Two types of gas control systems are used with these models:  
Standing Pilot Ignition and Intermittent Pilot Ignition (IPI).  
Standing Pilot Ignition System  
This system includes millivolt control valve, standing pilot,  
thermopile/thermocouple flame sensor, and piezo ignitor.  
WARNING: 110-120 VAC MUST NEVER BE  
CONNECTED TO A CONTROL VALVE IN A  
MILLIVOLT SYSTEM.  
!
Intermittent Pilot Ignition (IPI) System  
This system includes a 3V control valve, electronic module  
and intermittent pilot.  
HEAT-ZONE-GAS  
ATTACHES  
HERE  
WARNING: CONTINUOUS 110-120 VAC SER-  
VICE MUST BE WIRED DIRECTLYTO THE FIRE-  
!
PLACE JUNCTION BOX.  
Figure 32.  
STANDING PILOT  
1. Remove the knockout from the fireplace and discard it  
(see Figure 32).  
3/8 in.  
(10mm)  
2. Center the duct collar around the exposed hole and at-  
tach it to the fireplace with 3 screws. NOTE: Do this BE-  
FORE final positioning of the fireplace.  
3. Determine the location for the air register/fan housing  
assembly.  
Reference the Heat-Zone-Gas kit instructions for the re-  
maining installation steps.  
INTERMITTENT PILOT IGNITION  
FLAME SENSOR  
ROD  
Figure 33. Gas Control Systems  
28  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 7. The Gas Supply Line  
NOTE: Have the gas supply line installed in accordance  
with local building codes by a qualified installer ap-  
proved and/or licensed as required by the locality. (In  
the Commonwealth of Massachusetts installation must  
be performed by a licensed plumber or gas fitter).  
Use a wrench on  
shut-off valve when  
tightening gas line.  
NOTE: Before the first firing of the fireplace, the gas  
supply line should be purged of any trapped air.  
MANUAL  
SHUT-OFF  
VALVE  
NOTE: Consult local building codes to properly size  
the gas supply line leading to the 1/2 inch (13mm)  
hook-up at the unit.  
GAS  
VALVE  
This gas fireplace is designed to accept a 1/2 inch  
(13 mm) gas supply line. To install the gas supply line:  
CONTROL  
VALVE  
• A listed (and Commonwealth of Massachusetts approved)  
1/2 inch (13mm) tee-handle manual shut-off valve and a  
listed flexible gas connector are connected to the 1/2  
inch (13mm) inlet of the control valve. NOTE: If substi-  
tuting for these components, please consult local codes  
for compliance.  
FLEX  
CONNECTOR  
GAS LINE  
ACCESS HOLE  
Figure 34. Gas Supply Line  
Step 8. Gas Pressure Requirements  
• Locate the gas line access hole in the outer casing of  
the fireplace.  
Pressure requirements for Heat & Glo gas fireplaces  
are shown in the table below.  
• The gas line may be run from either side of the fireplace  
provided the hole in the outer wrap does not exceed 2 1/2”  
in diameter and it does not penetrate the actual firebox.  
Pressure  
Natural Gas  
Propane  
Minimum  
Inlet Pressure  
5.0 inches  
w.c.  
11.0 inches  
w.c.  
• The gap between the supply piping and gas access hole  
can be plugged with non-combustible insulation to pre-  
vent cold air infiltration.  
Maximum Inlet  
Gas Pressure  
14.0 inches  
w.c.  
14.0 inches  
w.c.  
• Open the fireplace lower grille, insert the gas supply line  
through the gas line hole, and connect it to the shut-off valve.  
Manifold  
Pressure  
3.5 inches  
w.c.  
10.0 inches  
w.c.  
• When attaching the pipe, support the control so that the  
lines are not bent or torn.  
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is  
provided on the inlet and outlet side of the gas control for a  
test gauge connection to measure the manifold pressure.  
Use a small flat blade screwdriver to crack open the screw  
in the center of the tap. Position a rubber hose over the tap  
to obtain the pressure reading.  
• After the gas line installation is complete, all connec-  
tions must be tightened and checked for leaks with a  
commercially-available, non-corrosive leak check solu-  
tion. Be sure to rinse off all leak check solution following  
testing.  
WARNING: DO NOT USE AN OPEN FLAME TO  
CHECK FOR GAS LEAKS.  
The fireplace and its individual shut-off valve must be  
disconnected from the gas supply piping system during  
any pressure testing of the system at test pressures in  
excess of one-half (1/2) psig (3.5 kPa).  
!
• At the gas line access hole, use insulation to re-pack  
the space around the gas pipe.  
The fireplace must be isolated from the gas supply piping  
system by closing its individual shut-off valve during any  
pressure testing of the gas supply piping system at test  
pressures equal to or less than one-half (1/2) psig (3.5 kPa).  
• Insert insulation from the outside of the fireplace and  
pack the insulation tightly to totally seal between the  
pipe and the outer casing.  
29  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLACK S2  
REMOTE SWITCH  
PIGTAIL  
3/16” PIGGYBACK CONNECTOR  
ON  
OFF  
ON/OFF  
SWITCH  
WHITE T2  
GAS VALUE  
RED T1  
THERMOPILE  
THERMOCOUPLE  
OPTIONAL WALL SWITCH,  
THERMOSTAT OR REMOTE  
BLACK S1  
Figure 35. Standing Pilot Ignition Wiring Diagram  
Step 9. Wiring the Fireplace  
Optional Accessories  
Optional fan and remote control kits require that 110-120  
VAC be wired to the factory installed junction box before  
the fireplace is permanently installed.  
NOTE: Electrical wiring must be installed by a licensed  
electrician.  
CAUTION: DISCONNECT REMOTE CONTROLS IF AB-  
SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-  
VENTACCIDENTAL FIREPLACE OPERATION.  
Wall Switch  
Position the wall switch in the desired position on a wall.  
Run a maximum of 25 feet (7.8 m) or less length of 18  
A.W.G. minimum wire and connect it to the fireplace ON/  
OFF switch pigtails.  
For Standing Pilot Ignition Wiring  
Appliance Requirements  
This appliance DOES NOT require 110-120 VAC to operate.  
WARNING: DO NOT CONNECT 110-120 VAC  
!
TO THE WALL SWITCH OR THE CONTROL  
VALVE WILL BE DESTROYED.  
WARNING: DO NOT CONNECT 110-120 VAC  
TO THE GAS CONTROL VALVE OR THE AP-  
!
PLIANCE WILL MALFUNCTION AND THE  
VALVE WILL BE DESTROYED.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-  
TION WHEN SERVICING CONTROLS. WIRING ERRORS  
CAN CAUSE IMPROPERAND DANGEROUS OPERATION.  
VERIFY PROPER OPERATION AFTER SERVICING.  
VARIABLE SPEED CONTROL  
NOTE: IF ANY OF THE ORIGINAL WIRE  
AS SUPPLIED WITH THE APPLIANCE  
MUST BE REPLACED, IT MUST BE  
BLK  
BLK  
REPLACED WITH TYPE 105OC RATED WIRE.  
JUNCTION BOX  
BLOWER RECEPTACLE  
BLK  
BLK  
BLK  
BLK  
BLK  
WHT  
GROUND  
WHT  
BLK  
TEMPERATURE  
SENSOR SWITCH  
BLOWER  
GRN  
BLK  
WHT  
110-120 VAC  
SENSOR  
SWITCH  
BLOWER  
“FAN”  
RECEPTACLE  
SPEED  
CONTROL  
Figure 36. Fan Wiring Diagram  
30  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTERMITTENT  
PILOT  
I
IGNITION MODULE  
3 VAC  
PLUG-IN  
3V TRANSFORMER  
IGNITOR  
S
ON/OFF  
WALL  
SWITCH  
FLAME SPARKER/  
SENSOR  
IGNITION  
MODULE  
(3V)  
WHT  
ORG  
LOW VOLTAGE  
SEE NOTE 1  
VALVE  
GROUND TO  
FIREPLACE  
CHASSIS  
GROUND  
REMOTE  
CONTROL  
HOT  
NEUTRAL  
WHITE WIRE  
CAN BE  
PLUGGED  
INTO ANY  
OF #1-#5  
LOCATIONS  
ON THE  
BLACK WIRE CAN BE  
PLUGGED INTO ANY OF  
#1 - #5 LOCATIONS  
ON THE HOT SIDE  
PIGGYBACK  
ON/OFF SWITCH  
NEUTRAL SIDE  
TRANSFORMER  
3 VAC  
PLUG IN  
VALVE  
Figure 37. Intermittent Pilot Ignition (IPI) Wiring Diagram  
simply connect red and black wire leads to activate battery  
power (connect red to red, black to black). The fireplace  
can be used as necessary. Once power (110 VAC) is re-  
stored, disconnect red and black wire leads to extend bat-  
tery life.  
Intermittent Pilot Ignition (IPI) Wiring  
3 Volt Transformer  
Î
This appliance comes with a 3 volt transformer. The trans-  
former plugs into the junction box and the two leads plug  
into the green control module (see Figure 37).  
Optional Accessories  
Appliance Requirements  
Optional remote control kits require that 110-120 VAC be  
wired to the factory installed junction box before the fire-  
place is permanently installed.  
This appliance requires that 110-120 VAC be wired to the  
factory installed junction box. Maintain correct polarity when  
wiring the junction box.  
Wall Switch  
Position the wall switch in the desired position on a wall.  
Run a maximum of 25 feet (7.8 m) or less length of 18  
A.W.G. minimum wire and connect it to the fireplace ON/  
OFF switch pigtails.  
WARNING: DO NOT CONNECT 110-120 VAC  
TO THE GAS CONTROL VALVE OR THE AP-  
PLIANCE WILL MALFUNCTION AND THE  
VALVE WILL BE DESTROYED.  
!
Operation using Battery Power  
WARNING: DO NOT CONNECT 110-120 VAC  
TO THE WALL SWITCH OR THE CONTROL  
VALVE WILL BE DESTROYED.  
!
This fireplace has an optional battery operation. The sys-  
tem is fully functional with the use of two “D” size batteries  
without ordinary 110-120 VAC power.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-  
TION WHEN SERVICING CONTROLS. WIRING ERRORS  
CAN CAUSE IMPROPER AND DANGEROUS OPERA-  
TION. VERIFYPROPER OPERATIONAFTER SERVICING.  
Wiring to the battery pack should be left disconnected in  
order to conserve battery life. In the case of a loss of power,  
31  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS  
AND THE FIREPLACE SURROUND (TOP AND SIDES)  
ARE SEALED, A 300° F. MINIMUM SEALANT MATE-  
RIAL MUST BE USED. THESE JOINTS ARE NOT RE-  
QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE  
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF  
NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-  
PLACE SURROUND. SEE THE DIAGRAM BELOW.  
Step 10. Finishing  
Figure 38 shows the minimum vertical and corresponding  
maximum horizontal dimensions of fireplace mantels or other  
combustible projections above the top front edge of the  
fireplace. See Figures 2 and 3 for other fireplace clearances.  
Only non-combustible materials may be used to cover the  
black fireplace front.  
WARNING: WHEN FINISHING THE FIREPLACE,  
NEVER OBSTRUCT OR MODIFY THE AIR IN-  
!
FINISH WALL MATERIAL MAY BE  
COMBUSTIBLE - TOP AND SIDES  
LET/OUTLET GRILLES IN ANY MANNER.  
NON-COMBUSTIBLE  
BOARD  
0”  
12”  
11”  
10”  
31”  
9”  
TO CEILING  
8”  
7”  
18”  
6”  
17”  
5”  
16”  
4”  
15”  
3”  
14”  
13”  
12”  
11”  
0”  
2-1/2”  
10”  
0”  
9”  
HIGH TEMPERATURE (3000F / 1490C MIN.)  
TOP & SIDE SEAL JOINT  
4”  
1”  
1”  
TOP FRONT EDGE OF FIREPLACE  
Figure 39 Sealant Material  
Hearth Extensions  
Figure 38.  
A hearth extension may be desirable for aesthetic reasons.  
However,ANSI or CAN/CGAtesting standards do not require  
hearth extensions for gas fireplace appliances.  
Minimum Vertical and Maximum Horizontal  
Dimensions of Combustibles above Fireplace  
Note: There are 3 metal tabs holding the non-combustible  
board in place for shipping. These tabs are to be cut off or  
bent back before finishing around the fireplace front.  
32  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 11. Installing Trim, Logs,  
and Ember Material  
Installing the Trim  
Combustible materials may be brought up to the specified  
clearances on the side and top front edges of the fireplace,  
but MUST NEVER overlap onto the front face. The joints  
between the finished wall and the fireplace top and sides  
can only be sealed with a 300° F. (149° C) minimum sealant.  
LATCHES  
(BOTH BOTTOM  
AND TOP)  
GLASS  
WARNING: WHEN FINISHING THE FIREPLACE,  
NEVER OBSTRUCT OR MODIFY THE AIR INLET/  
OUTLET GRILLES IN ANY MANNER.  
Figure 41.ASSEMBLY  
Glass Assembly  
!
Install optional marble and brass trim surround kits as  
desired. Marble, brass, brick, tile, or other non-combustible  
materials can be used to cover up the gap between the  
sheet rock and the fireplace.  
• Embers CANNOT be placed directly over ports. Care  
should be taken not to cover the lighting trail of ports  
(from back to front).  
• When placing Glowing embers onto the burner care  
should be taken so that the ports are not covered. Place  
the embers along side the port trail, but not on or in  
between the ports (see Figure 42). Failure to follow this  
procedure will likely cause lighting and sooting problems.  
Do not obstruct or modify the air inlet/outlet grilles. When  
overlapping on both sides, leave enough space so that the  
bottom grille can be lowered and the trim door removed.  
• Place Mystic embers on areas of base refractory away  
from port holes. Use this material to give your fireplace a  
realistic ash bed.  
RETAINING  
SCREW  
(BOTH SIDES)  
• Save the remaining ember materials for use during fire-  
place servicing.  
BURNER  
• Replace the glass door and a front trim door on the unit.  
• Pull out and latch the glass clips into the groove on the  
glass frame.  
Figure 40.  
Burner Removal  
Shutter Settings  
NG  
LP  
___________________________________________  
EMBER MATERIAL  
Burner  
1/8”  
5/8”  
Positioning the Logs  
Figure 42. Placement of the Ember Material  
Glass Specifications:  
If the gas logs have been factory installed they should not  
need to be positioned. If the logs have been packaged  
separately, refer to the instructions that accompany the  
logs. Save the log instructions with this manual.  
6000TR-OAK:  
TEMPERED  
If sooting occurs, the logs might need to be repositioned  
slightly to avoid excessive flame impingement.  
6000TR-OAK-IPI: TEMPERED  
Heat & Glo fireplaces manufactured with tempered glass  
may be installed in hazardous locations such as bathtub  
enclosures as defined by the CPSC. The tempered glass  
has been tested and certified to the requirements of ANSI  
Z97.1-1984 and CPSC 16 CFR 1202. (Safety Glazing Certi-  
fication Council SGCC # 1595 and 1597. Architectural Test-  
ing, Inc. Reports 02-31919.01 and 02-31917.01.)  
Placing the Ember Material  
Ember material is shipped with this gas fireplace. To place  
the ember material:  
• Pull the four glass latches out of the groove on the glass  
frame. Remove glass door from the unit (see Figure 41).  
33  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The fireplace should be run 3 to 4 hours on the  
initial start-up. Turn it off and let it cool completely. Remove  
and clean the glass. Replace the glass and run the fireplace  
for an additional 8 hours. This will help to cure the products  
used in the paint and logs.  
This statement is in compliance with SPCS 16 CFR Sec-  
tion 1201.5 “Certification and labeling requirements” which  
refers to 15 USC 2063 stating “…Such certificate shall ac-  
company the product or shall otherwise be furnished to any  
distributor or retailer to whom the product is delivered.”  
Some local building codes require the use of tempered glass  
with permanent marking in such locations. Glass meeting  
this requirement is available from the factory. Please con-  
tact your dealer or distributor to order.  
During this break-in period it is recommended that some  
windows in the house be opened for air circulation. This will  
help avoid setting off smoke detectors, and help eliminate  
any odors associated with the fireplace’s initial burning.  
Step 12. Before Lighting the Fireplace  
Before lighting the fireplace, be sure to do the following:  
Remove all paperwork from underneath the fireplace.  
Review safety warnings and cautions  
Air Shutter Setting  
This fireplace has an adjustable air shutter (which controls  
the primary air) factory set for the minimum vertical vent run  
(see Figure 43). If your installation has more than the  
minimum required vertical vent length, adjustment of the air  
shutter may be necessary to obtain optimal flame  
appearance. This should be adjusted by a qualified  
installer at the time of installation.  
• Read the Safety and Warning Information section at  
the beginning of this Installers Guide.  
Double-check for gas leaks  
• Before lighting the fireplace, double-check the unit for  
possible gas leaks.  
By pushing the air shutter handle in, you will be closing the  
air shutter. To adjust loosen the wing nut. Care should be  
taken when adjusting the air shutter so as not to cause the  
fireplace to soot. If sooting occurs the air shutter will need  
to be opened by pulling the handle out. When finished tighten  
wing nut.  
Double-check vent terminations and front grilles for  
obstructions.  
• Before lighting the fireplace, double-check the unit for  
possible obstructions that could be blocking the vent ter-  
minations or the front grilles.  
Double-check for faulty components  
• Any component that is found to be faulty MUST BE re-  
placed with an approved component. Tampering with the  
fireplace components is DANGEROUS and voids all war-  
ranties.  
A small amount of air will be in the gas supply lines. When  
first lighting the fireplace, it will take a few minutes for the  
lines to purge themselves of this air. Once the purging is  
complete, the fireplace will light and will operate normally.  
Subsequent lightings of the fireplace will not require this  
purging of air from the gas supply lines, unless the gas  
valve has been turned to the OFF position, in which  
case the air would have to be purged.  
AIR SHUTTER  
WING NUT  
Figure 43.  
34  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 13. Lighting the Fireplace  
WARNING: PLEASE REFER TO THE USER’S  
MANUAL FORALL CAUTIONS, SAFETY, AND  
WARNING INFORMATION PERTAINING TO THE  
LIGHTING AND OPERATION OF THE FIREPLACE.  
!
You’ve reviewed all safety warnings, you’ve checked the  
fireplace for gas leaks, you know the vent system is  
unobstructed, and you’ve checked for faulty components.  
Now you’re ready to light the fireplace.  
After the Installation  
LEAVE THIS INSTALLATION MANUAL WITH  
THE APPLIANCE FOR FUTURE REFERENCE.  
!
Maintaining and Servicing Your Fireplace  
4
Fireplace Maintenance  
Although the frequency of your fireplace servicing and main-  
tenance will depend on use and the type of installation, you  
should have a qualified service technician perform an appli-  
ance check-up at the beginning of each heating season.  
See the table below for specific guidelines regarding each  
fireplace maintenance task.  
IMPORTANT: TURN OFF THE GAS BEFORE SERVICING  
YOUR FIREPLACE.  
Replacing old ember material  
Frequency: Once annually, during the checkup.  
By: Qualified service technician.  
MAKE SURE THE FLAMES  
ARE STEADY—NOT  
LIFTING OR FLOATING.  
Task: Brush away loose ember material near the burner.  
Replace old ember material with new dime-size and shape  
pieces. Save the remaining ember material and repeat this  
procedure at your next servicing. For more information, see  
Placing Ember Material.  
Figure 44.  
Burner Flame Patterns  
Cleaning Burner and Controls  
Frequency: Once annually.  
Checking Vent System  
Frequency: Before initial use and at least annually  
thereafter, more frequently if possible.  
By: Qualified service technician/Home owner.  
Task: Inspect the external vent cap on a regular basis to  
ensure that no debris is interfering with the flow of air. Inspect  
entire vent system for proper function.  
By: Qualified service technician.  
Task: Brush or vacuum the control compartment, fireplace  
logs and burner areas surrounding the logs.  
Cleaning Flame Sensor Rod (IPI Systems)  
Frequency: Annually.  
By: Qualified service technician.  
Cleaning Glass Door  
Frequency: After the first 3 to 4 hours of use. As neces-  
sary after initial cleaning.  
Task: Make a visual check of the straight flame sensor rod  
(see Figure 33). Use emery cloth to carefully remove any  
existing film or white deposits.  
By: Home owner.  
Task: Remove and clean glass after the first 3 to 4 hours of  
use. After the initial cleaning, clean as necessary, particu-  
larly after adding new ember (flame colorant) material. Film  
deposits on the inside of the glass door should be cleaned  
off using a household glass cleaner. NOTE: DO NOT handle  
or attempt to clean the door when it is hot and DO  
NOT use abrasive cleaners.  
Checking Flame Patterns, Flame Height  
Frequency: Periodically.  
By: Qualified service technician/Home owner.  
Task: Make a visual check of your fireplace’s flame patterns.  
Make sure the flames are steady - not lifting or floating.  
See Figure 44. The flame sensor (IPI) or thermopile/  
thermocouple (standing pilot) tips should be covered with  
flame. See Figure 33.  
35  
Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Inc Pressure Washer 1026 User Manual
Greenheck Fan Ventilation Hood CSP A700 User Manual
Grizzly Drill H6331 User Manual
Grizzly Impact Driver H8119 User Manual
Grundig CRT Television MFS 72 4610 8 TOP User Manual
Hach Scanner DR 5000 User Manual
Hamilton Beach Slow Cooker 840071200 User Manual
HANNspree Flat Panel Television k212 10a1 User Manual
Harbor Freight Tools Power Hammer ITEM 69451 User Manual
Honeywell Car Stereo System 63 1332 02 User Manual