Hearth and Home Technologies Electric Heater SL 550TRSI AUE User Manual

INSTALLATION AND OPERATION  
INSTRUCTIONS  
MODEL: SL-550TRSI-AUE  
AUSTRALIAN GAS ASSOCIATION APPROVED  
Approval Number 5666  
THIS MANUAL MUST BE USED FOR INSTALLATION AND RETAINED  
BY HOMEOWNER FOR OPERATION AND MAINTENANCE.  
HEAT & GLO, a brand of Hearth & Home Technologies Inc.  
20802 Kensington Boulevard, Lakeville, MN 55044 USA • 1-888-427-3973  
THIS PRODUCT MAY BE COVERED BY ONE OR MORE OF THE FOLLOWING PATENTS:  
(United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407,  
5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474,  
6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, D320652, D445174, D462436; (Canada) 1297749,  
2195264, 2225408; (Australia) 543790;586383; (Mexico) 97-0457; (New Zealand) 200265; or other U.S. and foreign patents pending.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1.0 Installation Instructions......................................................................................... 5  
1.1 Introduction ................................................................................................... 6  
1.2 Flue SystemApprovals and Installation ......................................................... 8  
1.3 Connecting the Gas Supply ........................................................................ 22  
1.4 Ignition System Wiring ................................................................................ 23  
1.5 Blower Fan................................................................................................. 24  
1.6 Finishing .................................................................................................... 25  
1.7 Installer Testing ........................................................................................... 26  
1.8 Log Placement ........................................................................................... 27  
2.0 Operating Instructions ....................................................................................... 30  
2.1 Safety and Lighting Information................................................................... 31  
2.2 Fan Operation ............................................................................................ 32  
3.0 Servicing and Maintenance............................................................................... 32  
3.1 Removal of Covers for Servicing ................................................................ 33  
3.2 Removal of Components for Service .......................................................... 33  
3.3 Parts Replacement..................................................................................... 33  
3.4 Adjustments and Replacement Parts .......................................................... 33  
3.5 Maintenance Tasks..................................................................................... 34  
3.6 Troubleshooting .......................................................................................... 35  
4.0 Replacement Parts ........................................................................................... 37  
Limited Warranty............................................................................................... 39  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
25-3/4 in.  
(653mm)  
12-7/8 in.  
(327mm)  
16-3/8 in.  
(414mm)  
15-7/8 in.  
(402mm)  
8-3/4 in.  
(223mm)  
Ø 6-1/2 in.  
(165mm)  
Ø 82 in.  
(203mm)  
36 in.  
(913mm)  
32 in.  
(813mm)  
36-3/8 in.  
(924mm)  
32-5/8 in.  
(828mm)  
16-1/8 in.  
(408mm)  
2-1/8 in.  
(55mm)  
3-1/2 in.  
(90mm)  
23-3/8 in.  
(593mm)  
GAS LINE  
ACCESS  
26-3/8 in.  
(671mm)  
ELECTRICAL  
ACCESS  
6-7/8 in.  
(175mm)  
31-1/8 in.  
(790mm)  
6 in.  
(153mm)  
TOP STANDOFFS  
FLUE COLLAR  
COVER PLATE  
HOOD  
DATA BADGE  
& LABELS  
DRESS  
GUARD  
ACCESS  
DOOR  
GAS  
CONTROLS  
ELECTRICAL  
ACCESS  
GAS LINE  
ACCESS  
Figure 1. Diagram of SL-550TRSI-AUE  
4
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The heater can be mounted on any of the following sur-  
face:  
Top Flue  
1” MIN. (25mm)  
1. A flat surface (minimum 6mm base).  
2. Four (4) corner supports.  
B
(Example: Four (4) concrete masonry blocks). These  
supports must be positioned so they contact all four (4)  
perimeter edges on the bottom of the unit.  
A
Heater framing can be built before or after the heater is  
set in place. Framing should be positioned to accom-  
modate wall covering and heater facing material. The  
heater framing should be constructed of 2 inch X 4 inch  
(51 x 102mm) lumber or heavier. The framing headers  
may rest on the heater standoffs. Refer to Figure 2 and  
Figure 3 for heater and framing reference dimensions.  
E
D
C
1/2” MIN. (12.5mm)  
D
Minimum Clearances  
from the Fireplace to Combustible Materials  
A
B
C
E
59  
Inches  
37  
16-1/4  
413  
29-1/2  
749  
41-3/4  
1060  
Millimeters  
940  
1499  
Inches  
mm  
Glass Front...................................... 36 ........ 914  
Floor .................................................0........... 0  
Rear ................................................ 1/2 ........ 13  
Sides .............................................. 1/2 ........ 13  
Top ................................................ 1 1/2 ....... 38  
Ceiling* ............................................ 31 ........ 787  
Rear Flue  
1” MIN. (25mm)  
B
A
*The clearance to ceiling is measured from the top  
of the unit, excluding the standoffs (see Figure 30).  
E
D
Minimum Clearances  
from the Vent Pipe to Combustible Materials  
C
Inches  
mm  
3” (76mm)  
Vertical Sections. ............. 1 ................ 25  
A
B
C
D
E
Horizontal Sections  
Inches  
Millimeters  
37  
16-3/8  
413  
33  
46-11/16  
1186  
66  
940  
838  
1676  
Top ..................................... 3 ................ 75  
Bottom ............................... 1 ................ 25  
Sides ................................. 1 ................ 25  
Figure 2. Fireplace Dimensions, Locations, and  
Space Requirements  
At Wall Firestops  
Top ..................................... 3 ................ 75  
Bottom ............................... 1 ................ 25  
Sides ................................. 1 ................ 25  
1.0 INSTALLATION INSTRUCTIONS  
NOTE: Not intended for fireplace insert.  
In planning the installation for the heater it is neces-  
sary to determine where the unit is to be installed, the  
type of flue system to be used (straight out, corner, or  
elevated), and whether optional accessories (wall  
switch or remote control) are desired. Gas supply pip-  
ing should also be planned. Refer to the appliance data  
plate on the base pan of the heater for all gas pres-  
sures and input rate information.  
For minimum clearances, see the direct vent termina-  
tion clearance in Figures 23 and 28.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Framing should be constructed  
of 2 X 4 lumber or heavier.  
The framing headers  
may rest on the  
fireplace stand-offs.  
B
C
A
76mm  
D
FLUE  
WALL STUD  
38mm  
FRAMING  
HOLE  
E
NON-COMBUSTIBLE ZONE  
IS DEFINED BY 76MM ABOVE THE  
ELBOW FOR THE ENTIRE  
WIDTH AND DEPTH (BEHIND THE  
FRONT HEADER) OF THE FIREBOX.  
A
B
C
D*  
E*  
37 in.  
(940mm)  
33-1/4 in.  
(845mm)  
16-1/2 in.  
(420mm)  
43-3/4 in.  
(1111mm)  
23-3/8 in.  
(594mm)  
*NOTE: The center of the framing hole is one inch  
(254mm) above the center of the horizontal flue pipe.  
Figure 3. Framing Dimensions  
CAUTION: Measure heater dimensions, and  
verify framing methods and wall covering details be-  
fore framing construction begins.  
The control system for this model is an electronic igni-  
tion type. It consists of a gas control valve/variable regu-  
lator, a pilot/sensor/electrode and an ON/OFF switch.  
The controls are located behind the access door. Ro-  
tate the door down to open. See Figure 1.  
1.1 INTRODUCTION  
Minimum inlet gas supply pressure for purpose of input  
adjustment is 4.5 inches w.c. (1.13kPa) for natural gas  
and 11 inches w.c. (2.75kPa) for propane. Manifold (out-  
let) pressures should be set at 3.5 inches w.c. (.8kPa)  
for natural gas models and 9.5 inches w.c. (2.36kPa) for  
propane models.  
This model is designed to operate with all com-  
bustion air being siphoned from the outside of the  
building and all exhaust gases expelled to the  
outside of the building.  
WARNING: THIS UNIT IS NOT FOR USE WITH  
SOLID FUEL.  
These units MUST use the flue termination described  
in the flueing section of the manual.  
6
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T = Flue terminal  
= Mechanical air inlet  
M = Gas meter  
P = Electricity meter or fuse box  
Shading indicates prohibited  
areas for flue terminals  
I
a
-
Below eaves, balconies or other projections:  
MIN. CLEARANCE (mm)  
Appliances to 50 MJ/h input ................................................................................................ 300  
Appliances over 50 MJ/h input ............................................................................................ 500  
From the ground or above a balcony ...................................................................................... 300  
From a return wall or external corner ..................................................................................... 500  
From a gas meter (M) ........................................................................................................... 1000  
From an electricity meter or fuse box (P) ............................................................................... 500  
From a drain or soil pipe......................................................................................................... 150  
Horizontally from any building structure (unless appliance approved  
b
c
d
e
f
-
-
-
-
-
-
g
for closer installation) or obstruction facing a terminal ......................................................... 500  
From any other flue terminal, cowl, or combustion air intake ............................................... 500  
Horizontally from an openable window, door, non-mechanical air  
h
j
-
-
inlet, or any other opening into a building, with the exception of  
sub-floor ventilation:  
Appliances up to 150 MJ/h input ......................................................................................... 500  
Appliances over 150 MJ/h input ........................................................................................ 1500  
From a mechanical air inlet, including a spa blower ......................................................... 1500  
Vertically below an openable window, non-mechanical air  
k
n
-
-
inlet or any other opening into a building, with the exception of ................................. See table  
sub-floor ventilation ............................................................................................................. below  
CLEARANCES 'n' (mm)  
Space heaters  
Up to 50 MJ/h  
All other appliances  
UP to 50 MJ/h  
input  
Over 50 MJ/h &  
up  
Over 150 MJ/h  
input  
input  
to 150 MJ/h  
150  
500  
1000  
1500  
NOTES: 1. All distances are measured vertically or horizontally along the wall to a point  
in line with the nearest part of the terminal.  
2. Prohibited area below electricity meter or fuse box extends to ground level.  
3. See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.  
4. See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue  
terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.  
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS  
OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES  
Figure 4  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 1  
FLUE TERMINATION APPROVALS  
DVP-TRAP2 & SLK-01TRD HORIZONTALTERMINATION CAP  
DVP-TVHW & SLK-991DA VERTICALTERMINATION CAP  
MODEL  
SL-550TRSI-AUE  
1.2 FLUE SYSTEM APPROVALS  
These models have flue starting collars on both the top  
and the back of the unit. Depending upon the installa-  
tion, decide which ONE set of starting collars will be  
used to attach the flue system. Thestartingcollarsealing  
cap must remain on the starting collar NOT used.  
configurations using 90° elbows MUST BE strictly  
adhered to. The rise to run relationships are shown in  
the flueing drawings and tables on the next few pages.  
WARNING:THIS GASAPPLIANCEAND FLUEAS-  
SEMBLY MUST FLUE DIRECTLY TO THE OUTSIDE  
AND MUST NEVER BE ATTACHED TO A CHIMNEY  
SERVING ASEPARATE SOLID FUEL BURNING AP-  
PLIANCE. EACH GAS APPLIANCE MUST USE A  
SEPARATE FLUE SYSTEM-COMMON FLUE SYS-  
TEMS ARE PROHIBITED.  
These models use SL-D-series direct flue components  
when using the TOP flue collars and DVP-series direct  
flue components when using the REAR flue collars.  
WARNING: YOU MUST NOT MIX DVP-SERIES  
AND SL D-SERIES COMPONENTS IN ANY FLUE  
SYSTEM CONFIGURATION.  
CAUTION: UNDER NO CONDITION SHOULD  
COMBUSTIBLE MATERIAL BE CLOSER THAN 3  
INCHES (2 1/2 INCHES (64MM) AT WALL FIRE-  
STOPS) FROM THE TOP OF THE PIPE OR 1-INCH  
TO THE SIDESAND THE BOTTOM FOR HORIZONTAL  
SECTIONS OF THIS FLUE SYSTEM. VERTICAL  
SECTIONS OF THIS SYSTEM REQUIRE A MINI-  
MUM OF 1-INCH (25MM) CLEARANCE TO COM-  
BUSTIBLE MATERIALS ALL AROUND THE PIPE.  
Approved flue system components are labeled for  
identification. NO OTHER FLUEING SYSTEMS OR  
COMPONENTS MAY BE USED. Detailed installation  
instructions are included with each flue termination kit  
and should be used in conjunction with this manual. Figure  
5 below shows flue system components and terminations.  
Identifying Flue Components  
For alternative installations, other than depicted, con-  
tact your dealer for further information.  
The flue systems installed on this gas fireplace may  
include one, two, or three 90°elbow assemblies. The  
relationships of vertical rise to horizontal run in flue  
Refer to Figure 4 for required clearances to flue terminals.  
Flue system components  
STORM  
VERTICAL  
COLLAR  
TERMINATION  
ROOF FLASHING  
HORZONTAL  
TERMINATION  
HORIZONTAL PIPE  
SUPPORT  
PIPE LENGTH  
WALL  
FIRESTOP  
90 DEGREE  
ELBOW  
WALL BRACKET  
CEILING  
FIRESTOP  
Flue system termination kits  
SL D-SERIES  
DVP-SERIES  
SLK-01TRD  
SLK-991DA  
DVP-TRAP2  
DVP-TVHW  
Figure 5. Flue Components and Terminations  
8
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
102mm  
152mm  
305mm  
DVP4  
DVP6  
DVP12  
362mm  
310mm  
MAX.  
51mm  
MIN.  
610mm  
914mm  
DVP12A  
1219mm  
251mm  
DVP24  
45.0O  
260mm  
DVP45  
DVP36  
286mm  
184mm  
32mm TYP  
DVP48  
13mm TYP  
217mm  
319mm  
DVP  
90ST  
NOTE: PIPES OVERLAP 32mmAT EACH JOINT.  
Figure 6. DVP-Series Balanced Flue Component Specifications  
(127mm inner pipe / 203mm outer pipe)  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 3/8  
(162mm)  
6 ½  
(165mm)  
9 5/8  
(244mm)  
6 3/8  
(162mm)  
6 5/8  
(168mm)  
9 5/8  
(244mm)  
SL-90D  
6 ½  
(165mm)  
17-24  
(432-610mm)  
5 ¾  
(146mm)  
11 ¾  
(298mm)  
6 5/8  
(168mm)  
SL-06D  
SL-12D  
SL-17/24D  
47 ¾  
(1213mm)  
35 ¾  
(908mm)  
23 ¾  
(603mm)  
12-17  
(305-432mm)  
8 ¾  
(222mm)  
SL-09D  
SL-24D  
SL-36D  
SL-48D  
SL-12/17D  
NOTE: PIPES OVERLAP 1 3/8 INCHES (35mm) AT EACH JOINT.  
Figure 7. SL D-Series Balanced Flue Component Specifications  
(4-inch (102mm) inner pipe / 6 5/8-inch (168mm) outer pipe)  
10  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vertical Flue Restrictor  
If the heater installation requires a vertical flue ex-  
ceeding 4.5m above the unit with no horizontal  
flue or elbows, a vertical flue restrictor must be  
installed (see Figure 8).  
CAP  
VERTICAL FLUEING  
V
FT. (M)  
V
36' MAXIMUM (10.97M)  
RESTRICTOR  
PLATE  
USE SL D-SERIES  
COMPONENTS ONLY.  
Figure 8.  
Figure 9.  
STRAIGHT OUT HORIZONTAL  
FLUEING  
H
Max. Run  
24" (610mm)  
H
USE DVP-SERIES COMPONENTS ONLY.  
Figure 10.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
NOTE: A146mm section of vertical  
pipe must be attached to the heater  
before a 900 elbow.  
H
V
USE SL D-SERIES  
COMPONENTS  
ONLY.  
FLUEING WITH ONE (1) 90° ELBOW  
V
H
FT. (M)  
FT. (M)  
1' MIN.(0.30M)  
2' MIN.(0.61M)  
3' MIN.(0.91M)  
4' MIN.(1.22M)  
V + H = 30' (9.14M)  
2' MAX.(0.61M)  
4' MAX.(1.22M)  
8' MAX.(2.44M)  
10' MAX.(3.05M)  
Figure 11.  
FLUEING WITH ONE (1) 90o ELBOW  
V (FT.)  
H (FT.)  
1' MIN. (0.30M)  
2' MIN. (0.61M)  
3' MIN. (0.91M)  
4' MIN. (1.22M)  
3' MAX. (0.91M)  
6' MAX. (1.83M)  
9' MAX. (2.74M)  
12' MAX. (3.66M)  
V+H =36' MAX. (10.97M) H= 12' MAX. (3.66M)  
V
USE DVP-SERIES  
COMPONENTS  
ONLY.  
H
Figure 12.  
12  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLUEING WITH TWO (2) 90° ELBOWS  
V
H + H1  
FT. (M)  
FT. (M)  
1' MIN.(0.30M)  
2' MIN.(0.61M)  
3' MIN.(0.91M)  
4' MIN.(1.22M)  
5' MIN.(1.52M)  
2' MAX.(0.61M)  
4' MAX.(1.22M)  
6' MAX.(1.83M)  
8' MAX.(2.44M)  
10' MAX. (3.05M)  
30' MAX.(9.14M)  
10' MAX. (3.05M)  
H1  
V
USE SL D-SERIES COMPONENTS ONLY.  
H
H
V1  
V
FLUEING WITH TWO (2) 90° ELBOWS  
V
H
FT. (M)  
FT. (M)  
1' MIN.(0.30M)  
2' MIN.(0.61M)  
3' MIN.(0.91M)  
4' MIN.(1.22M)  
5' MIN.(1.52M)  
2' MAX.(0.61M)  
4' MAX. (1.22M)  
6' MAX. (1.83M)  
8' MAX. (2.44M)  
12' MAX. (3.66M)  
12' MAX.(3.66M)  
NOTE: V + V1 MAX 33' (10.06M)  
Figure 13.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLUEING WITH TWO (2) 90° ELBOWS  
V
H
H + H1  
1´ MIN. (0.30M)  
2´ MIN. (0.61M)  
3´ MIN. (0.91M)  
4´ MIN. (1.22M)  
1´ MAX. (0.30M)  
2´ MAX. (0.61M)  
3´ MAX. (0.91M)  
4´ MAX. (1.22M)  
2´ MAX. (0.61M)  
4´ MAX. (1.22M)  
8´ MAX. (2.44M)  
10´ MAX. (3.05M)  
H = 8´ MAX.(2.44M) H+H1= 10´MAX. (3.05M)  
V + H + H1 = 30’ (9.14M) MAX.  
H1  
V
USE DVP-SERIES  
COMPONENTS ONLY.  
H
V (FT)  
H + H1 (FT)  
1' MIN. (0.30 M)  
2' MIN. (0.61 M)  
3' MAX. (0.91M)  
5' MAX. (1.52M)  
3' MIN. (0.91 M)  
4' MIN. (1.22 M)  
8' MAX. (2.44M)  
12' MAX. (3.66M)  
V
H + H1= 12' MAX. (3.66M)  
V + H + H1= 33' (10.06m) MAX.  
H
1
H
Figure 14.  
14  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLUEING WITH THREE (3) 90° ELBOWS  
V
H
H + H1  
FT. (M)  
FT. (M)  
FT. (M)  
H
2' MIN.(0.61M)  
3' MIN.(0.91M)  
4' MIN.(1.22M)  
2' MAX.(0.61M)  
3' MAX.(0.91M)  
4' MAX.(1.22M)  
4' MAX.(1.22M)  
6' MAX (1.83M)  
8' MAX.(2.44M)  
V+V1 = 30' MAX (9.14M) 6' MAX (1.83M) 8' MAX.(2.44M)  
H
1
V1  
V
USE SL D-SERIES COMPONENTS ONLY.  
V1  
V
H
H1  
FLUEING WITH THREE (3) 90° ELBOWS  
V
H + H1  
FT. (M)  
FT. (M)  
1'MIN.(0.30M)  
2'MIN.(0.61M)  
3'MIN.(0.91M)  
4'MIN.(1.22M)  
5'MIN.(1.52M)  
2' MAX.(0.61M)  
4' MAX.(1.22M)  
6' MAX.(1.83M)  
8' MAX.(2.44M)  
12' MAX.(3.66M)  
12' MAX.(3.66M)  
NOTE: V + V1 MAX. 33' (10.06M)  
Figure 15.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
FLUEING WITH THREE (3) 90° ELBOWS  
V (FT.)  
H (FT.)  
H + H1 (FT.)  
1´ MIN. (0.30M)  
2´ MIN. (0.61M)  
3´ MIN. (0.91M)  
4´ MIN. (1.22M)  
1´ MAX. (0.30M)  
2´ MAX. (0.61M)  
4´ MAX. (1.22M)  
6´ MAX. (1.83M)  
3´ MAX. (0.91M)  
5´ MAX. (1.52M)  
8´ MAX. (2.44M)  
12´ MAX. (3.66M)  
H = 6´ MAX. (1.83M) H+H1 = 12´ MAX. (3.66M)  
NOTE: V + V, + H + H1 = 33’ (10.06M) MAX.  
V
1
V
H
H1  
USE DVP-SERIES  
COMPONENTS ONLY.  
H2  
V
H1  
FLUEING WITH THREE (3) 90° ELBOWS  
V (FT.)  
H (FT.)  
H + H1 + H2 (FT.)  
1´ MIN. (0.30M)  
2´ MIN. (0.61M)  
3´ MIN. (0.91M)  
4´ MIN. (1.22M)  
1´ MAX. (0.30M)  
2´ MAX. (0.61M)  
3´ MAX. (0.91M)  
4´ MAX. (1.22M))  
2´ MAX. (0.61M)  
4´ MAX. (1.22M)  
8´ MAX. (2.44M)  
10´ MAX. (3.05M)  
H
V+H+H1+H2 = 30´MAX.(9.14M) H=4´MAX.(1.22M) H+H1+H2 =10´MAX.(3.05M)  
Figure 16.  
16  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Flue Components  
WARNING: THE REAR FLUE COL-  
LAR SEAL CAP MUST REMAIN AT-  
TACHED TO THE REAR FLUE COL-  
LARS IF THE FLUE SYSTEM IS AT-  
TACHED TO THE TOP STARTING  
COLLARS. SEE FIGURE 17.  
!
!
After determining which set of starting collars will be  
used (top or rear), follow flueing instructions  
accordingly.  
Flueing Out the Rear Flue  
Remove the rear collar seal cap by cutting the  
strap at each end (see Figure 17).  
Next, remove the insulation from the rear flue, pull  
the heat shield out from outside of the heater.  
WARNING: FAILURE TO REMOVE  
INSULATION IN THE SET OF COL-  
LARS YOU ARE USING COULD  
CAUSE A FIRE.  
WARNING: THE TOP FLUE COLLAR  
SEAL CAP MUST REMAIN ATTACHED  
!
TO THE TOP FLUE COLLAR IF THE FLUE  
SYSTEM IS ATTACHED TO THE REAR  
STARTING COLLARS. SEE FIGURE 17.  
WARNING: YOU MUST LEAVE  
THE INSULATION IN PLACE IN  
THE SET OF COLLARS YOU ARE  
NOT USING.  
!
Flueing Out the Top Flue  
Remove the top collar cover plate. Remove the  
seal cap and both pieces of insulation in the top  
collars (see Figure 17). Remove the heat shield  
inside the top collars from the outside of the  
heater.  
FLUEING OUT REAR  
FLUEING OUT TOP  
Insert screwdriver  
or similar object  
here to remove cap.  
SEAL  
CAP  
INSULATION,  
DISCARD  
BOTH  
SEAL  
CAP  
PIECES and  
HEAT SHIELD  
HEAT  
SHIELD  
HEAT  
SHIELD  
DISCARD  
INSULATION  
and  
HEAT SHIELD  
CUT  
HERE  
Figure 17.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Flue Components  
WARNING  
A. On the REAR of the heater  
Fire Risk  
1. Attaching the First Flue Component to the Start-  
ing Collars:  
Exhaust Fumes Risk  
Impaired Performance of Appliance  
Overlap pipe slip sections at least  
38 mm.  
To attach the first flue component to the starting collars  
on the rear of the heater:  
Screws must not exceed one inch long.  
Make sure that the flue gasket supplied with the  
heater seals between the first flue component and  
the outer heater wrap.  
Pipe may separate if not properly  
joined.  
Slide the male end of the inner flue of the pipe sec-  
tion over the inner collar on the heater. At the same  
time, slide the outer flue over the outer collar on the  
heater. Push the flue section into the appliance col-  
lar until all the lances (see Figure 18) have snapped  
in place. Tug slightly on the flue to confirm that it  
has completely locked into place.  
2. Assembling Flue Components  
Insert the inner flue of sectionAinto the flared inner flue  
of section B.  
Start the outer flue of section A over the outer flue of  
section B (see Figure 19). Note: The end of the pipe  
sections with the lances/tabs on it will face towards  
the appliance.  
Once both inner and outer flues are started, press sec-  
tionAonto section B firmly until all lances have snapped  
into place. Check to make sure they have snapped  
together (see Figure 20) and the seams are not aligned  
(see Figure 21). Tug slightly on section A to confirm it  
has completely locked into place.  
A
B
Figure 18.  
Any 90° elbow installed directly on the back of a  
rear flueing heater MUST BE in a vertical position.  
WARNING: ENSURE THAT THE HEATER  
GASKET SUPPLIED WITH THE HEATER  
SEALS BETWEEN THE FIRST FLUE COMPO-  
!
NENTAND THE OUTER HEATER WRAP.  
Figure 19.  
Figure 20.  
18  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. On the TOP of the heater  
1. Attaching the First Flue Component to the Start-  
ing Collars:  
To attach the first flue component to the starting collars  
on the top of the heater:  
Lock the flue components into place by sliding the  
concentric pipe sections with four (4) equally spaced  
interior beads into the heater collar or previously in-  
stalled component end with four (4) equally spaced  
indented sections.  
CORRECT  
Figure 22. Adding Venting Components  
When the internal beads of each outer pipe line up,  
rotate the pipe section clockwise about one quarter  
(1/4) turn. The flue pipe is now locked together.  
Slide the ceramic fiber pad over the first flue section  
and place it flush to the fireplace. Continue to add  
vent components.  
WARNING: ENSURE THAT THE HEATER  
GASKET SUPPLIED WITH THE HEATER  
SEALS BETWEEN THE FIRST FLUE COMPO-  
NENTAND THE OUTER HEATER WRAP.  
INCORRECT  
!
Note: Make sure that the seams are not aligned to  
prevent unintentional disconnection.  
Figure 21. Seams  
2. Continue Adding Flue Components  
NOTE: Make sure that seams are NOT aligned to prevent  
To continue adding flue components in accordance with  
the pre-planned flue system configuration:  
unintentional disconnection.  
For elbows that are changing the flue direction, two  
screws minimum should be put in the outer flue at the  
joint to prevent the elbow from rotating.  
Ensure that each succeeding flue component is se-  
curely fitted and locked into the preceding compo-  
nent in the flue system.  
PROCEED TO STEP 3  
(Install Support Brackets)  
For elbows that are changing the flue direction, two  
screws minimum should be put in the outer flue at the  
joint to prevent the elbow from rotating.  
3. Install Support Brackets  
For Horizontal Runs - The flue system must be  
supported every five (5) feet (1.5m) of horizontal run by  
a horizontal pipe support.  
To install support brackets for horizontal runs:  
Place the pipe supports around the flue pipe.  
• Nail the pipe supports to the framing members.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
For Vertical Runs  
The flue system must be supported every eight (8) feet  
(2.4 M) above the heater flue outlet by wall brackets.  
10" (254mm)  
INTERIOR  
WALL SHIELD  
To install support brackets for vertical runs:  
Attach wall brackets to the flue pipe and secure the  
wall bracket to the framing members with nails or  
screws.  
12" (305mm)  
WALL BRACKET  
WALL STUD  
Figure 24. Flue Pipe & Firestop  
For Vertical Runs - One firestop is REQUIRED at the  
hole in each ceiling through which the flue passes.  
To install firestops for vertical runs that pass through  
ceilings:  
Position a plumb bob directly over the center of the  
vertical flue component.  
8 FT.  
(2.4m)  
Mark the ceiling to establish the centerpoint of the  
flue.  
FLUE  
OUTLET  
Drill a hole or drive a nail through this center point.  
Check the floor above for any obstructions, such as  
wiring or plumbing runs.  
Reposition the heater and flue system, if neces-  
sary, to accommodate the ceiling joists and/or ob-  
structions.  
1 INCH MIN.  
(25mm)  
Cut a 10-inch X 10-inch (254mm X 305mm) hole  
through the ceiling, using the firestop pipe opening  
as a guide.  
Figure 23. Installing Support Brackets  
Frame the hole with framing lumber the same size  
as the ceiling joists.  
4. Install Firestops  
For Horizontal Runs - Firestops are REQUIRED on  
both sides of a combustible wall through which the flue  
passes.  
10" (254mm)  
10” (254mm)  
To install firestops (heat shield) for horizontal runs that  
pass through either interior or exterior walls:  
CHIMNEY  
HOLE  
Cut a 10-inch by 12-inch (254 mm X 305 mm) hole  
through the wall.  
EXISTING CEILING  
JOISTS  
NEW  
FRAMING  
Position the firestops on both sides of the hole pre-  
viously cut and secure the firestops with nails or  
screws.  
MEMBERS  
CEILING  
Figure 25. Hole and New Framing Members  
The pipe opening of the firestops MUST BE placed  
towards the bottom of the firestop.  
Continue the flue run through the firestop.  
20  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the area above the ceiling is NOT an attic, position  
and secure the ceiling firestop on the ceiling side of  
the previously cut and framed hole.  
The heat shield sections will overlap to match the  
wall thickness (depth).  
If the wall thickness does not allow the required 1-1/  
2 inch heat shield overlap, an extended heat shield  
must be used. The extended heat shield will need  
to be cut to the thickness of the wall and be at-  
tached to the wall shield.  
JOIST  
The small leg in the shield rests on top of the flue to  
properly space it from the pipe section (see Figure  
28).  
CEILING  
Interior  
Wall Shield  
Rear Vent  
Heat Shield  
NAILS (4 REQUIRED)  
CEILING FIRESTOP  
38mm min.  
overlap  
Figure 26. Ceiling Firestop (Ceiling Side)  
If the area above the ceiling IS an attic, position and  
secure the firestop on top of the previously framed hole.  
NAILS (4 REQUIRED)  
Outer Flue  
Inner Flue  
38mm min.  
Overlap  
RAFTER  
INTERIOR  
EXTERIOR  
Figure 28. Venting through the Wall  
CEILING  
The termination kit should pass through the wall  
firestops from the exterior of the building.  
CEILING FIRESTOP  
Figure 27. Attic Firestop  
Adjust the termination cap to its final exterior posi-  
tion on the building and interlock the flue sections.  
C. Flue Termination  
WARNING: THE TERMINATION CAP  
MUST BE POSITIONED SO THAT THE  
For Horizontal Terminations using the DVP-TRAP  
!
ARROW IS POINTING UP.  
To attach and secure the termination to the last section  
of horizontal flue:  
Use a high-temperature sealant gasket to seal be-  
tween the pipe and exterior firestop.  
The rear flue heat shield MUST be placed one inch  
above the top of the flue between the wall shield and  
the base of the termination cap.  
One section of the heat shield is attached to the  
wall shield. The other is attached to the termination  
cap in the same manner (see Figure 28).  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Vertical Terminations - To locate the flue and  
install the flue sections:  
Locate and mark the flue centerpoint on the under-  
side of the roof, and drive a nail through the  
centerpoint.  
Make the outline of the roof hole around the  
centerpoint nail.  
The size of the roof hole framing dimensions depend  
on the pitch of the roof. There MUST BE a 1-inch  
(25mm) clearance from the vertical flue pipe to com-  
bustible materials.  
GAS ACCESS  
Mark the roof hole accordingly.  
Cover the opening of the installed flue pipes.  
Cut and frame the roof hole.  
Figure 29. Gas Supply Line  
Use framing lumber the same size as the roof rafters  
and install the frame securely. Flashing anchored to  
the frame must withstand heavy winds.  
1.3 CONNECTING THE GAS SUPPLY  
The gas is introduced to the appliance on the left hand  
side. See Figure 29. After the gas pipe installation is  
complete, check carefully all gas connections for leaks  
with a commercially-available, non-corrosive leak check  
solution. Be sure to rinse off all leak check solution  
following testing. DO NOT USE AN OPEN FLAME.  
Continue to install concentric flue sections up through  
the roof hole and up past the roof line until you reach  
the appropriate distance above the roof.  
CAUTION: FOLLOW THE REQUIREMENTS OF THE  
AGA GAS INSTALLATION CODE FOR MINIMUM  
HEIGHT REQUIREMENTSABOVE THE ROOF.  
NOTE: THE GAS SUPPLYLINE SHOULD BE PURGED  
OF ANY TRAPPED AIR PRIOR TO THE FIRST FIR-  
ING OF THE UNIT.  
To seal the roof hole, and to divert rain and snow from  
the flue system:  
Attach a flashing to the roof using nails, and use a  
non-hardening mastic around the edges of the flash-  
ing base where it meets the roof.  
Attach a storm collar over the flashing joint to form a  
water-tight seal. Place non-hardening mastic around  
the joint, between the storm collar and the vertical  
pipe.  
Slide the termination cap over the end of the flue  
pipe and rotate the pipe clockwise 1/4 turn.  
22  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLAME SPARKER/  
SENSOR  
VALVE  
REMOTE  
CONTROL  
ANT.  
ON/OFF  
WALL SWITCH  
PILOT  
IGNITION  
MODULE  
(6V)  
IGNITION MODULE  
6VDC  
GROUND  
NEUTRAL  
HOT  
BATTERY PORT  
PLUG IN  
THERMOCOUPLE  
BLOCK  
(CONNECTED TO  
ON/OFF  
SWITCH  
BACK OF VALVE)  
VALVE  
GAS LINE  
CONNECTED TO  
BACK OF VALVE  
Figure 30.  
1.4 IGNITION SYSTEM WIRING  
CAUTION  
This gas fireplace is equipped with an electronic igni-  
Label all wires prior to disconnection when servic-  
ing controls. Wiring errors can cause improper  
and dangerous operation. Verify proper operation  
after servicing.  
tion system which operates on a 6 volt system.  
This appliance requires 240 VAC to be wired to the  
factory installed junction box. Check factory installed  
power cord for damage before using .  
WARNING  
Shock Risk  
Replace damaged wire with type  
105O C rated wire.  
Wire must have high temperature  
insulation.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
NOTE: IF ANY OF THE ORIGINAL  
WIRE AS SUPPLIED WITH THE  
APPLIANCE MUST BE RE-  
PLACED, IT MUST BE REPLACED  
WITH TYPE 105C RATED WIRE.  
BLACK  
BLACK  
VARIABLE  
SPEED  
CONTROL  
BROWN  
BLUE  
BROWN  
BLUE  
BLACK  
TEMPERATURE  
SENSOR SWITCH  
GREEN/YELLOW  
STRIPE  
BLOWER  
240VAC JUNCTION BOX  
BLUE  
BROWN  
GREEN/YELLOW  
Figure 31.  
1.5 BLOWER FAN  
These heaters have a factory installed Fan, Elec-  
trical Junction Box, Variable Speed Rheostat  
Control Switch and Temperature Sensor Switch  
for the fan. These components are located be-  
hind the lower door.  
BLACK  
BROWN  
BLACK  
BLUE  
(HOT) BROWN  
BROWN  
Use of the fan requires that the Junction Box  
(factory installed) be connected to 240 VAC  
service before permanently enclosing the heater.  
The access hole for connecting the service wires  
is found on the right exterior side of the unit.  
See Figure 32 for wire connection detail.  
(NEUTRAL) BLUE  
BLUE  
Figure 32.  
24  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IF JOINTS BETWEEN THE FINISHED WALLS AND  
THE FIREPLACE SURROUND (TOP AND SIDES)  
ARE SEALED, A 300° F (149°C). MINIMUM SEAL-  
ANT MATERIAL MUST BE USED. THESE JOINTS  
ARE NOT REQUIRED TO BE SEALED. ONLY NON-  
COMBUSTIBLE MATERIAL (USING 300° F. (149°C)  
MINIMUM ADHESIVE, IF NEEDED) CAN BE AP-  
PLIED AS FACING TO THE FIREPLACE SUR-  
ROUND. SEE FIGURE 33.  
1.6 FINISHING  
The minimum clearance to combustibles are 0 from  
the sides, floor, back and top (these clearances are  
defined by the standoffs). The minimum distance to the  
perpendicular side wall extending past the appliance  
front is 2-inches (51mm). Clearance to a mantelpiece  
is shown in Figure 33.  
CEILING  
31”  
(787mm)  
12” (305mm)  
11” (279mm)  
10” (254mm)  
9” (229mm)  
8” (203mm)  
7” (178mm)  
6” (152mm)  
5” (127mm)  
9”  
(229mm)  
10”  
(254mm)  
6”  
4” (102mm)  
3” (76mm)  
2” (51mm)  
(152mm)  
7”  
(178mm)  
11”  
(279mm)  
5”  
(127mm)  
4”  
12”  
(305mm)  
8”  
(203mm)  
(102mm)  
3”  
(76mm)  
2”  
(51mm)  
TOP FRONT EDGE  
OF FIREPLACE  
NON-COMBUSTIBLE  
BOARD  
FINISH MATERIAL  
MAY BE COMBUSTIBLE  
- TOP AND SIDES  
OF UNIT  
TOP SEAL  
JOINT  
SIDE SEAL  
JOINT  
0”  
1/2”  
(13mm)  
Figure 33.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Trim  
Follow the Safety Information and Lighting Instructions  
pages of this manual to light the appliance.  
Combustible materials may be brought up to the  
specified clearances on the side and top front edges of  
the fireplace, but MUST NEVER overlap onto the front  
face. The joints between the finished wall and the  
fireplace top and sides can only be sealed with a 300°  
F. (149° C) minimum sealant.  
To obtain proper operation, it is imperative that the pi-  
lot and main burner flame characteristics are steady,  
not lifting or floating. Typically, the top 3/8-inch (10mm)  
of the thermocouple should be engulfed in the pilot flame  
(see Figure 34).  
WARNING: WHEN FINISHING THE FIRE-  
!
PLACE, NEVER OBSTRUCT OR MODIFY  
THE AIR INLET/OUTLET GRILLES IN ANY  
MANNER.  
Burner flame patterns are shown in Figure 35.  
Proper gas log positioning is shown in Section 1.8.  
Follow Section 3.5 TROUBLESHOOTING for adjusting  
the appliance to operate properly.  
Install optional marble and brass trim surround kits as  
desired. Marble, brass, brick, tile, or other non-  
combustible materials can be used to cover up the gap  
between the sheet rock and the fireplace.  
Pilot Assembly  
Do not obstruct or modify the air inlet/outlet grilles. When  
overlapping on both sides, leave enough space so that  
the bottom grille can be opened and the trim door  
removed.  
1.7  
INSTALLER TESTING  
The space heater must be tested and be operating ac-  
cording to manufacturer's specifications prior to the in-  
staller leaving the site. Note: the tips of the flames  
should never hit the top of the firebox after the unit has  
warmed up. Please contact your dealer or a qualified  
service person to replace injector or adjust valve.  
Upon completing the gas line connection, a small  
amount of air will be in the lines. When first lighting the  
pilot light, it will take a few minutes for the lines to  
purge themselves of this air. Once the purging is com-  
plete, the pilot and burner will light and operate as indi-  
cated in the Lighting Instructions.  
Figure 34.  
Subsequent lightings of the appliance will not require  
such purging.  
MAKE SURE THE FLAMES  
ARE STEADY—NOT  
LIFTING OR FLOATING.  
Figure 35.  
26  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.8  
LOG PLACEMENT INSTRUCTIONS  
Log Set Assembly: LOGS-550TRSI-AUE  
TABS  
1 2 3 4 5 6 7 8  
CAUTION: Logs are fragile! Carefully remove the logs from the packaging.  
1
1
LOG #1 (SRV550-715): Place log #1 onto the log grate so that the notches in the bottom of the log  
fit on the right three grate bars. Push log #1 towards the rear locating tabs.  
2
2
LOG #2 (SRV347-703): Place log #2 so that its left edge sits against the left front grate corner and  
its right edge rests against the tab on the second grate bar.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
3
LOG #3 (SRV349-704): Position log #3 so that its right edge sits on log #1 as shown and it's left edge  
sits on the first grate bar behind log #2.  
4
4
LOG #4 (SRV278-705): Position log #4 between log #1 and the locating tab on the fourth grate bar.  
Push its left hand side back to the locating tab as the grate bar.  
5
5
LOG #5 (SRV540-704): Put the forked end of log #5 on the base in front of the grate, towards the  
center of the second bar grate.  
28  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
6
LOG #6 (SRV550-718): Place log #6 on the base on front of the grate as shown.  
7
7
LOG #7 (SRV484-703): Place log #7 on the groove in log #2 with its rear top on log #1 and front top  
resting on log #5.  
8
8
LOG #8 (SRV347-701): Hook log #8 on the right hand corner grate bar and rest its rear on log  
#1 as shown.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.0 OPERATING INSTRUCTIONS  
THE DRESS GUARD IS FITTED TO THIS APPLI-  
ANCE TO REDUCE THE RISK OF FIRE OR INJURY  
FROM BURNSAND NO PART OF IT SHOULD BE  
PERMANENTLY REMOVED. FOR PROTECTION  
OF YOUNG CHILDREN OR THE INFIRM, A SEC-  
ONDARY GUARD IS REQUIRED.  
This appliance is a balanced flue heater and is designed  
to operate with all combustion air being siphoned from  
the outside of the building and all exhaust gases ex-  
pelled to the outside of the building.  
WARNING: THIS UNIT IS NOT FOR USE  
THE GLASS DOOR ASSEMBLY MUST BE IN  
PLACE AND SEALED AND THE FIXED MESH  
DRESS GUARD MUST BE IN PLACE ON THE  
FIREPLACE BEFORE THE UNIT CAN BE PLACED  
INTO SAFE OPERATION.  
!
WITH SOLID FUEL.  
The control system for this model includes a pilot, elec-  
tronic module, spark ignitor and thermocouple. It con-  
sists of a 6V gas control valve/variable regulator and  
an remote control. The controls are located in the lower  
compartment behind the lower door, and access is  
gained by lifting the door up. See Figure 1.  
DO NOT USE THIS APPLIANCE IF ANY PART  
HAS BEEN UNDER WATER. IMMEDIATELYCALL  
A QUALIFIED SERVICE TECHNICIAN TO INSPECT  
THE UNITAND TO REPLACEANY PART OF THE  
CONTROL SYSTEM AND ANY GAS CONTROL  
WHICH HAS BEEN UNDERWATER.  
WARNING:DO NOT CONNECT 240 VAC  
TO THE GAS CONTROL VALVE OR CON-  
TROL WIRING SYSTEM OF THIS UNIT.  
!
When lit for the first time, the appliance will emit a slight  
odor for an hour or two, due to paint and lubricants used  
in the manufacturing process. For the first few minutes  
after each lighting, vapor may condense and fog the  
glass and the flames may be blue. After a few minutes  
this moisture will disappear and within 15-30 minutes  
the flames should become yellow.  
DO NOT OPERATE THISAPPLIANCE WITH THE  
GLASS DOOR REMOVED, CRACKED, OR BRO-  
KEN. REPLACEMENT OF THE GLASS DOOR  
SHOULD BE DONE BY A LICENSED OR QUALI-  
FIED PERSON. DO NOT STRIKE OR SLAM THE  
GLASS DOOR.  
THE GLASS DOORASSEMBLY SHALL ONLY BE  
REPLACED AS A COMPLETE UNIT AS SUPPLIED  
BY THE GAS FIREPLACE MANUFACTURER. NO  
SUBSTITUTE MATERIALS MAY BE USED.  
The heater may produce a noise, caused from metal  
expansion and contraction as it heats up and cools down.  
This noise is similar to one that a furnace or heat duct  
may produce and does not affect the operation or lon-  
gevity of the heater.  
OPERATING  
CAUTIONS  
FLAME SPARKER/  
SENSOR  
VALVE  
THIS APPLIANCE  
MAY EXHIBIT A  
SLIGHT CARBON  
DEPOSITION.  
REMOTE  
CONTROL  
ANT.  
ON/OFF  
WALL SWITCH  
PILOT  
DO NOT PLACE  
ARTICLES ON OR  
AGAINST THIS  
APPLIANCE.  
IGNITION  
MODULE  
(6V)  
IGNITION MODULE  
6VDC  
GROUND  
NEUTRAL  
HOT  
DO NOT USE OR  
STORE FLAM-  
MABLE MATERI-  
ALS NEAR THIS  
APPLIANCE.  
BATTERY PORT  
PLUG IN  
DO NOT SPRAY  
AEROSOLS IN  
THE VICINITY OF  
THIS APPLIANCE  
WHILE IT IS IN  
OPERATION.  
THERMOCOUPLE  
BLOCK  
(CONNECTED TO  
ON/OFF  
SWITCH  
BACK OF VALVE)  
VALVE  
GAS LINE  
CONNECTED TO  
BACK OF VALVE  
Figure 36.  
30  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.1 SAFETY & LIGHTING INFORMATION  
tact your dealer or a qualified service person to replace  
the injector or adjust the valve.  
Follow SAFETY INFORMATION and LIGHTING IN-  
STRUCTIONS to light the appliance.  
NOTE: THE TIPS OF THE FLAMES SHOULD NEVER  
HIT THE TOP OF THE FIREBOX.  
By design, the flame pattern will not be identical from  
unit to unit. Additionally, flame pattern may vary depend-  
ing on installation type and weather conditions.  
These gas models have remote control valve which al-  
low you to increase or decrease the height of the main  
burner flames. Push the button to increase the flame  
height and the button to decrease the flame height.  
After the unit has warmed up (i.e. approximately 15 min-  
utes) flame height should be slightly (about 2" (51mm)  
below the top of the mesh trim assembly. If the flame  
height is higher than this, adjustments must be made to  
prevent overheating the gasket and glass. Please con-  
FOR YOUR SAFETY  
READ BEFORE LIGHTING  
LIGHTING  
INSTRUCTIONS  
WARNING: If you do not follow these instructions  
exactly, a fire or explosion may result causing prop-  
erty damage, personal injury or loss of life.  
1. This gas fireplace is equipped with an  
ignition device which automatically  
lights the burner. Do not try to light the  
burner by hand.  
A. This appliance is equipped with  
an electronic ignition device  
which automatically lights the  
burner. Do not try to light the  
burner by hand.  
Do not touch any electric switch;  
do not use any phone in your build-  
ing.  
Immediately call your gas supplier  
from a neighbor's phone. Follow  
the gas supplier's instructions.  
GAS  
VALVE  
B. BEFORE LIGHTING, smell all  
around the appliance area for  
gas. Be sure to smell next to the  
floor because some gas is  
heavier than air and will settle on  
the floor.  
If you cannot reach your gas sup-  
plier, call the fire department.  
C. Do not use this appliance if any  
part has been under water. Imme-  
diately call a qualified service tech-  
nician to inspect the appliance and  
to replace any part of the control  
system and any gas control which  
has been under water.  
2. Wait five (5) minutes to clear out any  
gas. Then smell for gas, including near  
the floor. If you smell gas, STOP! Fol-  
low "B" in the Safety Information located  
on the left side of this label. If you don't  
smell gas, go to next step.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
3. To light the burner, simultaneously  
WARNING: CAUTION:  
press the star  
and up  
arrow but-  
tons on the remote control until a short  
acoustic signal confirms the start se-  
quence has begun.  
DO NOT CONNECT 220/240  
VAC TO THE CONTROL VALVE.  
Hot while in operation. Do not  
touch. Keep children, clothing, fur-  
niture, gasoline and other liquids  
having flammable vapors away.  
Improper installation, adjustment,  
alteration, service or maintenance  
can cause injury or property dam-  
age. Refer to the owner's informa-  
tion manual provided with this ap-  
pliance.  
4. If the gas fireplace will not operate,  
check the batteries then follow the  
instructions “To Turn Off Gas to Ap-  
pliance” and call your service techni-  
cian or gas supplier.  
Do not operate the appliance with  
panel(s) removed, cracked or bro-  
ken. Replacement of the panel(s)  
should be done by a licensed or  
qualified service person.  
This appliance needs fresh air for  
safe operation and must be in-  
stalled so there are provisions for  
adequate combustion and ventila-  
tion air.  
NOT FOR USE  
WITH SOLID FUEL  
TO TURN OFF  
GAS TOAPPLIANCE  
If not installed, operated, and main-  
tained in accordance with the  
manufacturer's instructions, this  
product could expose you to sub-  
stances in fuel or fuel combustion.  
For use with natural, propane and  
butane gases.  
1. Push the "OFF" button on remote.  
2. Remove power from receiver.  
Keep burner and control compart-  
ment clean. See installation and  
operating instructions accompany-  
ing appliance.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
When the appliance is put back in service check burner  
flame patterns with Figure 37.  
2.2  
FAN OPERATION  
The accessory fan is wired in series with a speed con-  
trol switch and a temperature sensor switch. Set the  
speed control to an "ON" position and light the heater.  
The temperature sensor switch will automatically start  
the fan when the switch warms up—and stop the fan  
when it cools down. You can manually stop the fan by  
turning the speed control switch to "OFF". See Figure  
31 for fan wiring diagram.  
To obtain proper operation, it is imperative that the pi-  
lot and main burner flame characteristics are steady,  
not lifting or floating. Typically, the top 3/8-inch (10m)  
of the thermocouple should be engulfed in the pilot flame  
(Figure 38).  
3.0  
SERVICING AND MAINTENANCE  
A. HEATER SERVICING: Frequency of heater servic-  
ing will depend upon use and type of installation.  
B. IMPORTANT: TURN OFF GASAND ELECTRICAL  
POWER BEFORE SERVICINGAPPLIANCE. IT IS  
RECOMMENDED THATACOMPETENT SERVICE  
TECHNICIAN PERFORM SERVICE CHECK-UPSAT  
THE BEGINNING OF EACH HEATING SEASON.  
C. The appliance and flue system should be inspected  
before initial use and at least annually by a qualified  
field service person.  
MAKE SURE THE FLAMES  
ARE STEADY—NOT  
LIFTING OR FLOATING.  
Figure 37.  
D. Inspect the external flue cap on a regular basis to  
make sure that no debris is interfering with the air  
flow.  
E. Keep the control compartment, logs, and burner area  
surround the logs clean by vacuuming or brushing at  
least twice a year.  
Pilot Assembly  
CAUTION: THE LOGS GET VERY HOT - HANDLE  
ONLY WHEN COOL.  
WARNING: DO NOT USE ABRASIVE  
CLEANERS ON THE GLASS DOOR AS-  
!
SEMBLY. DO NOT ATTEMPT TO CLEAN THE  
GLASS DOOR WHEN IT IS HOT.  
F. The glass door should be cleaned using a house-  
hold glass cleaner. DO NOT handle or attempt to  
clean the glass when it is HOT.  
G. Visually inspect the flexible power supply cord; if  
damaged, contact the service agent for a special  
replacement cord assembly.  
Figure 38.  
H. In order to properly clean the burner and pilot as-  
sembly, turn off the gas to the unit and remove the  
logs exposing the burner and pilot assembly. Clean  
all foreign materials from top of burner. Check to  
make sure that the burner orifice is clean.  
Visually inspect the pilot periodically. Brush or blow  
away any dust or linen accumulations. If the pilot ori-  
fice is plugged, disassembly may be required to re-  
move any foreign materials from the orifice or tubing.  
32  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. PILOTASSEMBLY/IGNITION SYSTEM  
3.1  
REMOVAL OF COVERS FOR  
SERVICING  
Remove the log set, log grate, metal base pan and  
burner.  
A. Control Compartment Door  
Rotate the lower door down to access the gas controls.  
B. Dress Guard and Glass Door  
Disconnect the gas supply tube from the back of  
the gas valve and the thermocouple from the  
interruptor block.  
Lift the front dress guard up and out away from the  
appliance side surrounds. Replace the dress guard  
when servicing is complete.  
Disconnect and remove the pilot assembly from the  
bracket.  
NOTE: When removing the pilot assembly, carefully  
pull the electrode wire up through the grommeted hole  
in the base pan.  
Release the four glass clips around the glass door.  
Carefully lift the glass up and out away from the ap-  
pliance (see Figure 39).  
3.3 PARTS REPLACEMENT  
1. FAN/SWITCHES  
Disconnect the fan wires from the junction box wires  
by pulling the male and female connectors apart and  
slide the fan out the front of the lower controls com-  
partment.  
LATCHES  
(BOTH TOP  
AND BOTTOM)  
Disconnect the wires from the fan speed control  
switch, pull off the knob, and remove the nut holding  
the speed control to the bracket.  
GLASS  
ASSEMBLY  
Figure 39. Glass Assembly  
Disconnect the wires from the fan temperature sen-  
sor switch and remove the nut holding the switch  
bracket onto the side of the firebox.  
3.2 REMOVAL OF COMPONENTS  
FOR SERVICE  
2. GLASS PANEL  
1. BURNER  
To replace the glass door, place the bottom edge on  
top of the bottom mounting brackets. Push glass  
against unit and latch the two fasteners at the top of  
the glass door and the two fasteners at the bottom  
(see Figure 39).  
Carefully remove the log set. Remove the rear screws  
holding the log grate. Remove log grate and metal  
base pan.  
Unscrew the brackets at both ends of the burner and  
the retaining screws at the pilot bracket (see Figure  
40). Slide the burner towards the right away from the  
burner orifice.  
3.4 ADJUSTMENTS AND  
REPLACEMENT PARTS  
PILOT BRACKET  
RETAINING SCREWS  
Adjustments and replacement parts for this appliance  
should only be done by a qualified service person. A  
wiring diagram for the appliance is shown in SECTION  
2.0 OPERATING INSTRUCTIONS. Areplacement part  
table is shown in SECTION 4.0 of this manual.  
Figure 40.  
CAUTION: ALL SCREWS WHICH WERE  
REMOVED MUST BE REPLACED.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
3.5  
MAINTENANCE TASKS  
Inspect  
Maintenance Tasks  
Doors  
1. Inspect for scratches, dents or other damage and repair as necessary.  
2. Verify no obstructions to airflow .  
3. Verify maintenance of proper clearance to combustible household objects.  
Gasket Seal, Glass  
Assembly and Glass  
1. Inspect gasket seal and its condition.  
2. Inspect glass panels for scratches and nicks that can lead to breakage when exposed to  
heat.  
3. Confirm there is no damage to glass or glass frame. Replace as necessary.  
4. Verify that latches engage properly, clip studs are not stripped, and glass attachment  
components are intact and operating properly. Replace as necessary.  
5. Clean glass. Replace glass assembly if severely coated with silicate deposits that cannot  
be removed.  
Valve Compartment  
and Firebox Top  
1. Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these  
areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.  
2. Remove any foreign objects.  
3. Verify unobstructed air circulation.  
Logs  
1. Inspect for broken, damaged, or missing logs. Replace as necessary.  
2. Verify correct log placement and no flame impingement causing sooting. Correct as  
necessary.  
Firebox  
1. Inspect for paint condition, warpage, corrosion or perforation. Sand and repaint as  
necessary.  
2. Replace gas fireplace if firebox has been perforated.  
Burner Ignition and  
Operation  
1. Verify burner is properly secured and aligned with pilot or igniter.  
2. Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if  
necessary.  
3. Replace ember materials with new dime-size and shape pieces. Do not block ports or  
obstruct lighting paths.  
4. Check for smooth lighting and ignition carryover to all ports. Verify there is no ignition delay.  
5. Inspect for lifting or other flame problems.  
6. Inspect orifice for soot, dirt or corrosion.  
7. Verify manifold and inlet pressures. Adjust regulator as required.  
8. Inspect pilot flame strength. Clean or replace orifice as necessary.  
9. Inspect thermocouple for soot, corrosion and deterioration. Clean with emery cloth or  
replace as required.  
Flueing  
1. Inspect venting for blockage or obstruction such as bird nests, leaves, etc.  
2. Confirm that termination cap remains clear and unobstructed by plants, etc.  
3. Verify that termination cap clearance to subsequent construction (building additions, decks,  
fences or sheds) has been maintained.  
4. Inspect for corrosion or separation.  
5. Verify weather stripping, sealing and flashing remains intact.  
1. Verify operation of remote.  
Remote controls  
2. Replace batteries in remote transmitters and battery-powered receivers.  
34  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.6 TROUBLESHOOTING  
With proper installation and maintenance, your new Gas Heater should provide years of trouble-free service. If you do  
experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in  
the diagnosis of problems and the corrective action to be taken.  
Electronic Ignition System  
Symptom  
Possible Causes  
Corrective Actions  
1. No transmission, motor does a. Receiver must learn new  
Press and hold the receiver’s reset button until you hear 2  
acoustic signals. After the second longer acoustic signal,  
release the reset button and within the subsequent 20  
seconds, press the down arrow on the remote handset until  
you hear an additional long acoustic signal confirming the  
new code is set.  
not turn.  
code.  
2. No ignition. No tone.  
a. Receiver  
Replace receiver and reprogram code.  
3. No ignition; one 5 seconds  
continuous tone (7 shorts  
beeps might be heard prior to  
the 5 seconds tone).  
a. ON/OFF switch is in OFF Push switch to ON position.  
position.  
b. Loose wire.  
c. Receiver.  
Secure wire.  
Replace receiver and reprogram.  
Straighten pins on 8 wire connector.  
d. Bent pins on 8 wire  
connector.  
e. Valve.  
Replace valve.  
4. No pilot flame and control  
a. Air in the pilot supply line.  
Purge the line or start ignition several times.  
continues to spark.  
b. Thermocouple circuit wired Check polarity of the thermocouple wires.  
incorrectly.  
c. No spark at pilot burner  
Check spark gap, check wiring connection. Check for spark  
in location along cable.  
d. Valve.  
Replace valve. Do not over tighten.  
Replace valve and thermocouple interrupter.  
e. Over tightened  
thermocouple interrupter.  
f. Receiver.  
a. Receiver.  
Replace receiver and reprogram code.  
Replace receiver and reprogram code.  
5. Pilot is lit and control  
continues to spark. Valve shuts  
off after 10 to30 seconds.  
Valve operates manually.  
6. Pilot is lit, sparking stops if  
a flame is present. Valve shuts  
off after 10 to 60 seconds.  
a. Thermocouple.  
Replace thermocouple.  
b. Low inlet pressure to valve. Confirm sufficient inlet pressure to the valve. Adjust or  
replace inlet regulator if necessary.  
Valve does not work manually.  
c. Valve.  
Replace valve and the thermocouple interrupter.  
7. 3 short beeps while the  
motor turns.  
a. Batteries are low.  
Replace batteries - quality alkaline recommended.  
WARNING: Creating an electrical short between the  
batteries/battery box and metal parts of the appliance may  
render the receiver inoperable.  
8. Pilot flame lights but there is a. Manual override know (if  
Turn Manual override know to ON position.  
no main gas flow.  
equipped) is in MAN  
position.  
b. Valve turned don to pilot  
flow.  
Turn flame to high fire by pressing up button on remote  
handset.  
c. Low inlet pressure to valve. Confirm sufficient inlet pressure to the valve. Adjust or  
replace inlet regulator if necessary.  
9. Pilot sparks, but pilot will not a. Correct gas supply.  
light.  
Verify that incoming gas line ball valve is “open”. Verify that  
inlet pressure reading is within acceptable limits, inlet  
pressure must not exceed 50 mbar.  
b. Ignitor gap is too large.  
c. Module is not grounded.  
Verify that spark gap from ignitor to pilot hood is .43 cm.  
Verify module is securely grounded to metal chassis of  
fireplace.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Electronic Ignition System - (continued)  
Symptom  
Possible Causes  
Corrective Actions  
10. Glass soots.  
a. Flame impingement on Adjust the log set so that the flame does not impinge on it.  
logs.  
b. Improper venturi setting. Adjust the air shutter at the base of the burner.  
c. Debris around venturi.  
Inspect the opening at the base of the burner. It is imperative that NO  
material be placed in this opening.  
11. Flame burns blue a. Insufficient oxygen  
and lifts off burner. being supplied.  
1. Check to make sure flue cap is installed properly and free of debris.  
Make sure that flue system points are tight and have no leaks.  
2. Check to make sure that no material has been placed in the opening at  
the burner base or in the area of the air holes in the center of the base  
pan beneath the burne.  
3. Be sure glass is tighened properly on unit, particularly on top corners.  
36  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SL-550TRSI-AUE  
Service Parts  
Beginning Manufacturing Date: 6/06  
Ending Manufacturing Date: ______  
(NG, LP) Exploded Parts Diagram  
16  
32  
31  
20  
33  
5
38  
34  
17  
2
40  
37  
35  
3
39  
36  
1
19  
7
12  
4
6
18  
13  
14  
15  
11  
22 Log set assembly  
21  
9
23  
30  
25  
8
29  
26  
28  
10  
24  
27  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
SL-550TRSI-AUE Service Parts List  
IMPORTANT: When ordering, supply serial and model numbers to ensure correct service parts.  
ITEM  
PARTS  
PART NUMBER  
Valve NG  
Valve LP  
Orifice NG  
2098-130  
1
2098-131  
582-840  
2
3
4
Orifice LP  
582-057  
Flexible Gas Connector  
Burner Assembly NG  
Burner Assembly LP  
Ignition Cable  
530-302A  
2079-010  
2079-012  
2098-147  
SRV550-175  
GLA-550TRS  
2079-040  
550-251A  
2079-041  
2021-007  
550-117  
100-505A  
2078-025  
546-251A  
2098-050  
2098-051  
2098-145  
2079-109  
2078-022  
491-510A  
046-530  
LOGS-550TRSAUD  
SRV550-715  
SRV347-703  
SRV349-704  
SRV278-705  
SRV540-704  
SRV550-718  
SRV484-703  
SRV347-701  
530-431  
2079-104  
2089-120  
2098-143  
2098-142  
2098-144  
2045-407  
100-512  
5
6
7
8
9
10  
11  
12  
13  
14  
15  
Hood  
Glass Door Assembly  
Dress Guard  
Top Louver  
Lower Door  
Grate  
Base Refractory  
Blower Assembly 240V  
Junction Box  
Power Cord  
Pilot Assembly NG  
Pilot Assembly LP  
Switch Assembly  
Interior Top Heat Shield  
Gas Shutoff Assembly  
Rheostat  
Switch Sensor  
Log Set Assembly  
Log #1  
Log #2  
Log #3  
Log #4  
Log #5  
Log #6  
Log #7  
Log #8  
Valve Plate Gasket  
Pilot Bracket  
Valve Bracket  
Control Cable  
Module, Maxitrol  
240V Adaptor  
Burner Neck Gasket  
Rheostat Knob  
Thermocouple Block  
Block Control Wire  
Glass Latch Assembly  
Mineral Wool  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
2098-146  
2098-148  
386-122A  
050-721  
Mesh Assembly  
Exhaust Resistor  
Accesssories  
Wall Switch Kit, Off White  
Wall Switch Kit, White  
Conversion Kit NG  
Conversion Kit LP  
561-330A  
347-299  
WSK-21  
WSK-21W  
NGK-550I-AUE  
LPK-550I-AUE  
38  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED 10 YEAR WARRANTY  
HEAT & GLO, a brand of Hearth & Home Technologies Inc.  
InordertopresumptivelyestablishthedatestowhichyourHEAT&GLOLimited10YearWarrantyruns,youmust  
mailthecompletedwarrantycardtoHEAT&GLO,abrandofHearth&HomeTechnologiesInc.,20802Kensington  
Boulevard, Lakeville, MN 55044, within 60 days of the date of fireplace installation. If you fail to do so, you may be  
required to prove the date of installation before warranty work can be performed.  
The warranty exclusions and limitations of liability are effective upon installation of the fireplace.  
Subject to the conditions set forth herein, HEAT & GLO, a brand of Hearth & Home Technologies Inc. ("HEAT &  
GLO")extendsthefollowingwarrantywithrespecttoHEAT&GLO, abrandofHearth&HomeTechnologiesInc..  
If HEAT & GLO is reasonably satisfied that any part or portion of the fireplace covered by this Limited Warranty is  
defective in material or workmanship under normal use and service as described in the Operating Instructions,  
HEAT & GLO will take the following actions:  
1. If the defect is reported during the first year from the date of installation (stainless steel burners and fiber logs  
are coveredfor 3years), HEAT & GLO will replaceor repairthedefectivecomponentsat itssoleexpense. The  
decisionwhethertoreplaceacomponentshallbemadeatHEAT&GLO's solediscretion.ThisLimitedWarranty  
does not cover components broken during shipping, misuse or careless handling. HEAT & GLO shall be not  
responsibleforanyindirect,incidental,orconsequentialdamagesorforanycostsotherthanthoseincurredby  
HEAT&GLOtorepairorreplacethedefectivecomponent. Ifcomponents(includingventing)otherthanfactory  
approvedcomponentsareused,allwarrantyandliabilityonthefireplaceisvoided. Defectsreportedafterthe  
first year will not be covered by warranty unless they fall within the purview of paragraph 2 or 3 below.  
2. Ifthefollowingdefectsarereportedduringthesecondyearafterthedateofinstallation,HEAT&GLOwillsupply  
replacement parts at the current wholesale price: defective electrical or manual components, optional  
components or accessories, and glass panels (not including glass panels broken during misuse or careless  
handling). HEAT & GLO shall not be responsible for any labor, transportation or other costs. Furthermore, it  
shall not be liable for any indirect, incidental or consequential damages.  
3. HEAT & GLO will replace or repair a defective firebox or heat exchanger, at any time during the 10 years from  
thedateofinstallation.ThedecisionwhethertoreplacethedefectivecomponentshallbemadeatHEAT&GLO's  
sole discretion. HEAT & GLO shall not be responsible for any indirect, incidental or consequential damages or  
for any costs other than those incurred by HEAT & GLO to repair or replace the defective component.  
ThisLimitedWarrantyistheexclusiveremedyavailabletoyou.IfHEAT&GLOcannoteffectivelyresolveawarranty  
probleminanexpedientandcost-effectivemanner,itcandischargeitsentirewarrantyliabilitybyrefundingtheprice  
of the product to you.  
Productsmadebyothermanufacturers,whethersoldwiththefireplaceoraddedthereafter,areNOTcoveredbythis  
Limited Warranty. The use of other unauthorized components will make this warranty null and void. This Limited  
Warranty will also be void if the appliance is not installed by a qualified installer in accordance with the Installation  
Instructions. Furthermore, theLimitedWarrantywillbe voidifthefireplaceisnotoperated, atalltimes, according  
totheOperatingInstructionsfurnishedwiththefireplace.Anyserviceworkmustbeperformedbyauthorizedservice  
representatives.  
EXCEPT TO THE EXTENT PROVIDED BY LAW, NO OTHER EXPRESS OR IMPLIED WARRANTIES,  
INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL  
APPLY TO THE FIREPLACE PRODUCT. In States that do not allow limitations on how long an implied warranty  
lasts,ordonotallowexclusionofindirectdamages,thoselimitationsorexclusionsmaynotapplytoyou. Youmay  
also have additional rights not covered in this Limited Warranty.  
HEAT & GLO reserves the right to make changes at any time, without notice, in design, material, specifications  
and prices. It also reserves the right to discontinue styles and products.  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Service or Replacement Parts Contact:  
Melbourne  
Jetmaster  
444 Swan Street  
Richmond 3121  
(03) 9429-5573  
Perth  
Fireplace Corner  
277 Lord Street  
East Perth 6000  
(08) 9228-2600  
Sydney  
Jetmaster  
10 MartinAvenue  
Arncliff 2205  
(02) 9597-7222  
40  
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Marine Sanitation System 206405 User Manual
Groupe SEB USA T FAL Iron GV6500 User Manual
Harman Stereo Amplifier 518S User Manual
Hasbro Motorized Toy Car 80285 Asst User Manual
Honeywell TV Cables 7845gsmr User Manual
Hotpoint Cooktop HL500G User Manual
Hotpoint Refrigerator RFR51V User Manual
Hotpoint Washer WMYL 661 User Manual
HP Hewlett Packard Personal Computer 520 5 XX User Manual
iHome Speaker System iDM8 User Manual