HP Hewlett Packard Water Pump 8 UB 1 User Manual

®
Pump Division  
Type: 8-UB-1  
CENTRIFUGAL PUMP  
USER INSTRUCTIONS:  
INSTALLATION, OPERATION, MAINTENANCE  
PCN=71569247 07-04(E)  
(supercedes 6176/6511)  
These instructions must be read prior to installing,  
operating, using and maintaining this equipment.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
INDEX  
PAGE  
PAGE  
Additional sources (10.3)......................................... 31  
Alignment of shafting (4.2, 4.4 and 4.6)  
Pre-commissioning (5.1) ..........................................16  
Priming and auxiliary supplies (5.5) .........................17  
Protection systems (4.8) ..........................................16  
Reassembly (6.10, Assembly) .................................24  
Receipt and unpacking (2.1) ....................................10  
Recommended grease lubricants (5.2.1).................17  
Recommended spares (6.4).....................................22  
Recycling (2.5) .........................................................10  
Renewal clearances (6.7).........................................23  
Replacement parts (6.3 and 6.4)..............................22  
Running the pump (5.7)............................................18  
Safety action (1.6.3) ...................................................5  
Safety markings (1.6.1) ..............................................5  
Safety, protection systems (1.6 and 4.8)  
Sectional drawings (8)..............................................29  
Sound pressure level (1.9, Noise level) .....................9  
Sources, additional information (10.3) .....................31  
Spare parts (6.3) ......................................................22  
Specific machine performance (1.8) ..........................8  
Starting the pump (5.6).............................................18  
Stop/start frequency (5.7.6)......................................19  
Stopping and shutdown (5.8) ...................................19  
Storage, pump (2.4) .................................................10  
Storage, spare parts (6.3.2) .....................................22  
Supplementary manuals or information sources......31  
Supplementary User Instructions (10.1)...................31  
Tools required (6.5)..................................................23  
Torques for fasteners (6.6).......................................23  
Trouble-shooting (see 7) ..........................................27  
Vibration (5.7.5)........................................................19  
Warning labels (1.7.2) ................................................8  
Assembly (6.10)....................................................... 24  
ATEX marking (1.6.4.2) ............................................. 7  
CE marking and approvals (1.2)................................ 4  
Certification (9) ........................................................ 31  
Change notes (10.2)................................................ 31  
Clearances (6.7, Renewal clearances).................... 23  
Commissioning and operation (5)............................ 16  
Compliance, ATEX (1.6.4.1)...................................... 6  
Configurations (3.1) ................................................. 11  
Consumable items (6.4) .......................................... 22  
Copyright (1.4)........................................................... 4  
Design of major parts (3.3)...................................... 11  
Direction of rotation (5.3) ......................................... 17  
Disassembly (6.8).................................................... 23  
Disclaimer (1.3).......................................................... 4  
Dismantling (6.8, Disassembly)............................... 23  
Drawings (8) ............................................................ 29  
Duty conditions (1.5).................................................. 4  
Electrical connections (4.7) ..................................... 16  
End of product life (2.5) ........................................... 10  
Examination of parts (6.9)........................................ 24  
Fastener torques (6.6) ............................................. 23  
Faults; causes and remedies (7) ............................. 27  
Forces and moments (4.5.3) ................................... 15  
Foundation (4.2) ...................................................... 12  
General arrangement drawing (8.2) ........................ 30  
General assembly drawings (8)............................... 29  
Grouting (4.3)........................................................... 12  
Guarding (5.4).......................................................... 17  
Handling (2.2) .......................................................... 10  
Hydraulic, mechanical and electrical duty (5.9)....... 19  
Inspection (6.2.1 and 6.2.2)..................................... 21  
Installation (4) .......................................................... 12  
Lifting (2.3)............................................................... 10  
Location (4.1)........................................................... 12  
Lubrication (5.2 and 6.2.3)  
Lubrication schedule (5.2.2) .................................... 17  
Maintenance (6)....................................................... 20  
Maintenance schedule (6.2) .................................... 20  
Name nomenclature (3.2)........................................ 11  
Nameplate (1.7.1)...................................................... 8  
Operating limits (3.4.1) ............................................ 11  
Options (8.1.2)......................................................... 30  
Ordering spare parts (6.3.1) .................................... 22  
Parts lists (8)............................................................ 29  
Performance (3.4).................................................... 11  
Piping (4.5) .............................................................. 13  
Page 3 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
and Approvals. To confirm the Approvals applying  
and if the product is CE marked, check the serial  
number plate markings and the Certification. (See  
section 9, Certification.)  
1 INTRODUCTION AND SAFETY  
1.1 General  
These Instructions must always be kept  
close to the product's operating location or  
directly with the product.  
1.3 Disclaimer  
Information in these User Instructions is believed to  
be reliable. In spite of all the efforts of Flowserve  
Pump Division to provide sound and all necessary  
information the content of this manual may appear  
insufficient and is not guaranteed by Flowserve as  
to its completeness or accuracy.  
Flowserve products are designed, developed and  
manufactured with state-of-the-art technologies in  
modern facilities. The unit is produced with great  
care and commitment to continuous quality control,  
utilising sophisticated quality techniques, and safety  
requirements.  
Flowserve manufactures products to exacting  
International Quality Management System Standards as  
certified and audited by external Quality Assurance  
organisations. Genuine parts and accessories have  
been designed, tested and incorporated into the  
products to help ensure their continued product quality  
and performance in use. As Flowserve cannot test  
parts and accessories sourced from other vendors the  
incorrect incorporation of such parts and accessories  
may adversely affect the performance and safety  
features of the products. The failure to properly select,  
install or use authorised Flowserve parts and  
accessories is considered to be misuse. Damage or  
failure caused by misuse is not covered by the  
Flowserve warranty. In addition, any modification of  
Flowserve products or removal of original components  
may impair the safety of these products in their use.  
Flowserve is committed to continuous quality  
improvement and being at service for any further  
information about the product in its installation and  
operation or about its support products, repair and  
diagnostic services.  
These instructions are intended to facilitate  
familiarization with the product and its permitted use.  
Operating the product in compliance with these  
instructions is important to help ensure reliability in  
service and avoid risks. The instructions may not  
take into account local regulations; ensure such  
regulations are observed by all, including those  
installing the product. Always coordinate repair  
activity with operations personnel, and follow all plant  
safety requirements and applicable safety and health  
laws and regulations.  
1.4 Copyright  
These instructions should be read prior to  
installing, operating, using and maintaining the  
equipment in any region worldwide. The  
equipment must not be put into service until all  
the conditions relating to safety, noted in the  
instructions, have been met.  
All rights reserved. No part of these instructions may  
be reproduced, stored in a retrieval system or  
transmitted in any form or by any means without prior  
permission of Flowserve Pump Division.  
1.5 Duty conditions  
This product has been selected to meet the  
specifications of your purchaser order. The  
acknowledgement of these conditions has been sent  
separately to the Purchaser. A copy should be kept  
with these instructions.  
1.2 CE marking and approvals  
It is a legal requirement that machinery and  
equipment put into service within certain regions of  
the world shall conform with the applicable CE  
Marking Directives covering Machinery and, where  
applicable, Low Voltage Equipment, Electromagnetic  
Compatibility (EMC), Pressure Equipment Directive  
(PED) and Equipment for Potentially Explosive  
Atmospheres (ATEX).  
The product must not be operated beyond  
the parameters specified for the application. If  
there is any doubt as to the suitability of the  
product for the application intended, contact  
Flowserve for advice, quoting the serial number.  
Where applicable, the Directives and any additional  
Approvals, cover important safety aspects relating to  
machinery and equipment and the satisfactory  
provision of technical documents and safety  
instructions. Where applicable this document  
incorporates information relevant to these Directives  
If the conditions of service on your purchase order are  
going to be changed (for example liquid pumped,  
temperature or duty) it is requested that the user seeks  
the written agreement of Flowserve before start up.  
Page 4 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
1.6 Safety  
NEVER DO MAINTENANCE WORK  
WHEN THE UNIT IS CONNECTED TO POWER  
1.6.1 Summary of safety markings  
These User Instructions contain specific safety  
markings where non-observance of an instruction would  
cause hazards. The specific safety markings are:  
GUARDS MUST NOT BE REMOVED WHILE  
THE PUMP IS OPERATIONAL  
DRAIN THE PUMP AND ISOLATE PIPEWORK  
BEFORE DISMANTLING THE PUMP  
The appropriate safety precautions should be taken  
where the pumped liquids are hazardous.  
This symbol indicates electrical safety  
instructions where non-compliance will involve a high  
risk to personal safety or the loss of life.  
This symbol indicates safety instructions where  
non-compliance would affect personal safety and  
could result in loss of life.  
FLUORO-ELASTOMERS (When fitted.)  
When a pump has experienced temperatures over  
250 ºC (482 ºF), partial decomposition of fluoro-  
elastomers (example: Viton) will occur. In this  
condition these are extremely dangerous and skin  
contact must be avoided.  
This symbol indicates “hazardous and toxic fluid”  
safety instructions where non-compliance would affect  
personal safety and could result in loss of life.  
HANDLING COMPONENTS  
This symbol indicates safety  
instructions where non-compliance will involve some  
risk to safe operation and personal safety and would  
damage the equipment or property.  
Many precision parts have sharp corners and the  
wearing of appropriate safety gloves and equipment  
is required when handling these components. To lift  
heavy pieces above 25 kg (55 lb) use a crane  
appropriate for the mass and in accordance with  
current local regulations.  
This symbol indicates explosive atmosphere  
zone marking according to ATEX. It is used in safety  
instructions where non-compliance in the hazardous  
area would cause the risk of an explosion.  
THERMAL SHOCK  
Rapid changes in the temperature of the liquid within  
the pump can cause thermal shock, which can result  
in damage or breakage of components and should be  
avoided.  
This sign is not a safety symbol but indicates  
an important instruction in the assembly process.  
1.6.2 Personnel qualification and training  
All personnel involved in the operation, installation,  
inspection and maintenance of the unit must be  
qualified to carry out the work involved. If the  
personnel in question do not already possess the  
necessary knowledge and skill, appropriate training  
and instruction must be provided. If required the  
operator may commission the manufacturer/supplier  
to provide applicable training.  
APPLYING HEAT TO REMOVE IMPELLER  
There may be occasions when the impeller has either  
been shrunk fit on to the pump shaft or has become  
difficult to remove due to products of corrosion.  
If you elect to use heat to remove the impeller, it must  
be applied quickly to the impeller boss. TAKE  
GREAT CARE!  
Before applying heat ensure any residual hazardous  
liquid trapped between the impeller and pump shaft is  
thoroughly drained out through the impeller keyway to  
prevent an explosion or emission of toxic vapour.  
This must be carried out with the shaft in the vertical  
position. On some pump sizes a cavity exists in the  
impeller bore so on occasions a significant volume of  
liquid may drain out.  
Always coordinate repair activity with operations and  
health and safety personnel, and follow all plant  
safety requirements and applicable safety and health  
laws and regulations.  
1.6.3 Safety action  
This is a summary of conditions and actions to  
help prevent injury to personnel and damage to  
the environment and to equipment. For products  
used in potentially explosive atmospheres  
section 1.6.4 also applies.  
Page 5 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
HOT (and cold) PARTS  
DO NOT RUN THE PUMP AT  
ABNORMALLY HIGH OR LOW FLOW RATES  
Operating at a flow rate higher than normal or at a flow  
rate with no back pressure on the pump may overload  
the motor and cause cavitation. Low flow rates may  
cause a reduction in pump/bearing life, overheating of  
the pump, instability and cavitation/vibration.  
If hot or freezing components or auxiliary heating  
supplies can present a danger to operators and  
persons entering the immediate area action must be  
taken to avoid accidental contact. If complete  
protection is not possible, the machine access must  
be limited to maintenance staff only, with clear visual  
warnings and indicators to those entering the  
immediate area. Note: bearing housings must not be  
insulated and drive motors and bearings may be hot.  
1.6.4 Products used in potentially explosive  
atmospheres  
Measures are required to:  
Avoid excess temperature  
Prevent build up of explosive mixtures  
Prevent the generation of sparks  
Prevent leakages  
If the temperature is greater than 68 ºC (175 ºF) or  
below 5 ºC (20 ºF) in a restricted zone, or exceeds  
local regulations, action as above shall be taken.  
HAZARDOUS LIQUIDS  
When the pump is handling hazardous liquids care must  
be taken to avoid exposure to the liquid by appropriate  
siting of the pump, limiting personnel access and by  
operator training. If the liquid is flammable and/or  
explosive, strict safety procedures must be applied.  
Maintain the pump to avoid hazard  
The following instructions for pumps and pump units  
when installed in potentially explosive atmospheres  
must be followed to help ensure explosion protection.  
Both electrical and non-electrical equipment must  
meet the requirements of European Directive  
94/9/EC.  
Gland packing must not be used when pumping  
hazardous liquids.  
PREVENT EXCESSIVE EXTERNAL  
PIPE LOAD  
1.6.4.1 Scope of compliance  
Do not use pump as a support for piping. Do not  
mount expansion joints, unless allowed by Flowserve  
in writing, so that their force, due to internal pressure,  
acts on the pump flange.  
Use equipment only in the zone for which it is  
appropriate. Always check that the driver, drive  
coupling assembly, seal and pump equipment are  
suitably rated and/or certified for the classification of  
the specific atmosphere in which they are to be  
installed.  
ENSURE CORRECT LUBRICATION  
(See section 5, Commissioning, startup, operation  
and shutdown.)  
Where Flowserve has supplied only the bare shaft  
pump, the Ex rating applies only to the pump. The  
party responsible for assembling the pump set shall  
select the coupling, driver and any additional  
equipment, with the necessary CE Certificate/  
Declaration of Conformity establishing it is suitable for  
the area in which it is to be installed.  
START THE PUMP WITH OUTLET  
VALVE PARTLY OPENED  
(Unless otherwise instructed at a specific point in the  
User Instructions.)  
This is recommended to minimize the risk of  
overloading and damaging the pump motor at full or  
zero flow. Pumps may be started with the valve  
further open only on installations where this situation  
cannot occur. The pump outlet control valve may  
need to be adjusted to comply with the duty following  
the run-up process. (See section 5, Commissioning  
start-up, operation and shutdown.)  
The output from a variable frequency drive (VFD) can  
cause additional heating affects in the motor and so,  
for pumps sets with a VFD, the ATEX Certification for  
the motor must state that it is covers the situation  
where electrical supply is from the VFD. This  
particular requirement still applies even if the VFD is  
in a safe area.  
NEVER RUN THE PUMP DRY  
INLET VALVES TO BE FULLY OPEN  
WHEN PUMP IS RUNNING  
Running the pump at zero flow or below the  
recommended minimum flow continuously will cause  
damage to the pump and mechanical seal.  
Page 6 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
1.6.4.2 Marking  
Temperature classification “Tx” is used when the  
liquid temperature varies and the pump could be  
installed in different hazarous atmospheres. In this  
case the user is responsible for ensuring that the  
pump surface temperature does not exceed that  
permitted in the particular hazardous atmosphere.  
An example of ATEX equipment marking is shown  
below. The actual classification of the pump will be  
engraved on the nameplate.  
II 2 GD c 135 ºC (T4)  
If an explosive atmosphere exists during the  
Equipment Group  
I = Mining  
II = Non-mining  
installation, do not attempt to check the direction of  
rotation by starting the pump unfilled. Even a short  
run time may give a high temperature resulting from  
contact between rotating and stationary components.  
Category  
2 or M2 = High level protection  
3 = normal level of protection  
Where there is any risk of the pump being run against  
a closed valve generating high liquid and casing  
external surface temperatures it is recommended that  
users fit an external surface temperature protection  
device.  
Gas and/or Dust  
G = Gas; D= Dust  
c = Constructional safety  
(in accordance with prEn13463-5)  
Avoid mechanical, hydraulic or electrical overload by  
using motor overload trips, temperature monitor or a  
power monitor and make routine vibration monitoring  
checks.  
Maximum surface temperature (Temperature Class).  
(See section 1.6.4.3.)  
1.6.4.3 Avoiding excessive surface temperatures  
In dirty or dusty environments, regular checks must  
be made and dirt removed from areas around close  
clearances, bearing housings and motors.  
ENSURE THE EQUIPMENT TEMPERATURE  
CLASS IS SUITABLE FOR THE HAZARD ZONE  
Pumps have a temperature class as stated in the  
ATEX Ex rating on the nameplate. These are based  
on a maximum ambient of 40 ºC (104 ºF); refer to  
Flowserve for higher ambient temperatures.  
1.6.4.4 Preventing the build up of explosive  
mixtures  
ENSURE THE PUMP IS PROPERLY FILLED  
AND VENTED AND DOES NOT RUN DRY  
Ensure the pump and relevant suction and discharge  
pipeline system is totally filled with liquid at all times  
during the pump operation, so that an explosive  
atmosphere is prevented. In addition it is essential to  
make sure that seal chambers, auxiliary shaft seal  
systems and any heating and cooling systems are  
properly filled.  
The surface temperature on the pump is influenced  
by the temperature of the liquid handled. The  
maximum permissible liquid temperature depends on  
the temperature class and must not exceed the  
values in the table that follows.  
The temperature rise at the seals and bearings and  
due to the minimum permitted flow rate is taken into  
account in the temperatures stated.  
If the operation of the system cannot avoid this  
condition the fitting of an appropriate dry run  
protection device is recommended (for example liquid  
detection or a power monitor).  
Maximum  
surface  
temperature  
permitted  
Temperature limit of liquid  
handled (* depending on  
material and construction  
variant - check which is lower)  
Temperature  
class to  
prEN 13463-1  
To avoid potential hazards from fugitive emissions of  
vapour or gas to atmosphere the surrounding area  
must be well ventilated.  
T6  
T5  
T4  
T3  
T2  
T1  
85 °C (185 °F)  
100 °C (212 °F)  
135 °C (275 °F)  
200 °C (392 °F)  
300 °C (572 °F)  
450 °C (842 °F)  
Consult Flowserve  
Consult Flowserve  
115 °C (239 °F) *  
180 °C (356 °F) *  
275 °C (527 °F) *  
400 °C (752 °F) *  
1.6.4.5 Preventing sparks  
To prevent a potential hazard from mechanical  
contact, the coupling guard must be non-sparking  
and anti-static for Category 2.  
The responsibility for compliance with the  
specified maximum liquid temperature is with the  
plant operator.  
Page 7 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
To avoid the potential hazard from random induced  
current generating a spark, the earth contact on the  
baseplate must be used.  
1.7 Warning labels summary  
1.7.1 Nameplate  
For details of nameplate, see the Declaration of  
Conformity, or separate documentation included with  
these User Instructions.  
Avoid electrostatic charge: do not rub non-metallic  
surfaces with a dry cloth; ensure cloth is damp.  
The coupling must be selected to comply with 94/9/EC  
and correct alignment must be maintained.  
1.7.2 Warning labels  
1.6.4.6 Preventing leakage  
The pump must only be used to handle liquids  
for which it has been approved to have the correct  
corrosion resistance.  
Avoid entrapment of liquid in the pump and associated  
piping due to closing of suction and discharge valves,  
which could cause dangerous excessive pressures to  
occur if there is heat input to the liquid. This can occur if  
the pump is stationary or running.  
Bursting of liquid containing parts due to freezing  
must be avoided by draining or protecting the pump  
and ancillary systems.  
Where there is the potential hazard of a loss of a seal  
barrier fluid or external flush, the fluid must be  
monitored.  
Oil lubricated units only:  
If leakage of liquid to atmosphere can result in a  
hazard, the installation of a liquid detection device is  
recommended.  
1.6.4.7 Maintenance to avoid the hazard  
CORRECT MAINTENANCE IS REQUIRED TO  
AVOID POTENTIAL HAZARDS WHICH GIVE A  
RISK OF EXPLOSION  
1.8 Specific machine performance  
For performance parameters see section 1.5, Duty  
conditions. When the contract requirement specifies  
these to be incorporated into User Instructions these  
are included here. Where performance data has  
been supplied separately to the purchaser these  
should be obtained and retained with these User  
Instructions if required.  
The responsibility for compliance with  
maintenance instructions is with the plant  
operator.  
To avoid potential explosion hazards during  
maintenance, the tools, cleaning and painting  
materials used must not give rise to sparking or  
adversely affect the ambient conditions. Where there  
is a risk from such tools or materials, maintenance  
must be conducted in a safe area.  
It is recommended that a maintenance plan and  
schedule is adopted. (See section 6, Maintenance.)  
Page 8 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
The figures are indicative only, they are subject to a  
+3 dB tolerance, and cannot be guaranteed.  
1.9 Noise level  
When pump noise level exceeds 85 dB(A) attention  
must be given to prevailing Health and Safety  
Legislation, to limit the exposure of plant operating  
personnel to the noise. The usual approach is to  
control exposure time to the noise or to enclose the  
machine to reduce emitted sound. You may have  
already specified a limiting noise level when the  
equipment was ordered, however if no noise  
requirements were defined then machines above a  
certain power level will exceed 85 dB(A). In such  
situations consideration must be given to the fitting of  
an acoustic enclosure to meet local regulations.  
The values are based on the noisiest ungeared  
electric motors that are likely to be encountered.  
They represent sound pressure levels at 1 m (3.3 ft)  
from the directly driven pump, for "free field over a  
reflecting plane".  
If a pump unit only has been purchased, for fitting  
with your own driver, then the "pump only" noise  
levels from the table should be combined with the  
level for the driver obtained from the supplier. If the  
motor is driven by an inverter it may show an  
increase in noise level at some speeds. Consult a  
Noise Specialist for the combined calculation.  
Pump noise level is dependent on a number of  
factors - the type of motor fitted, the operating  
capacity, pipework design and acoustic  
characteristics of the building. Typical sound  
pressure levels measured in dB, and A-weighted are  
shown in the table below.  
For units driven by equipment other than electric  
motors or units contained within enclosures, see the  
accompanying information sheets and manuals.  
Typical sound pressure level, dBA, LpA at 1 m reference 20 µPa (LwA sound power 1 pW where LpA > 85 dBA)  
Motor size  
and speed  
3550 r/min  
2900 r/min  
1750 r/min  
1450 r/min  
Pump and  
motor  
Pump  
only  
Pump and  
motor  
Pump  
only  
Pump and  
motor  
Pump  
only  
Pump and  
motor  
Pump  
only  
kW (hp)  
dBA  
dBA  
dBA  
dBA  
dBA  
dBA  
dBA  
dBA  
<0.55 (<0.75)  
0.75 (1)  
1.1 (1.5)  
1.5 (2)  
71 (88)  
74 (91)  
66 (83)  
66 (83)  
68 (85)  
70 (87)  
72 (89)  
74 (91)  
75 (92)  
77 (94)  
78 (95)  
80 (97)  
83 (100)  
83 (100)  
83 (100)  
85 (102)  
86 (103)  
87 (104)  
88 (105)  
90 (107)  
90 (107)  
91 (108)  
92 (109)  
x
64 (81)  
67 (84)  
67 (84)  
70 (87)  
71 (88)  
74 (91)  
75 (92)  
83 (100)  
83 (100)  
84 (101)  
85 (102)  
85 (102)  
85 (102)  
93 (110)  
93 (110)  
93 (110)  
95 (112)  
95 (112)  
95 (112)  
95 (112)  
96 (113)  
x
62 (79)  
62 (79)  
64 (81)  
66 (83)  
68 (85)  
70 (87)  
71 (88)  
73 (90)  
74 (91)  
76 (93)  
79 (96)  
79 (96)  
79 (96)  
81 (98)  
82 (99)  
83 (100)  
84 (101)  
86 (103)  
86 (103)  
87 (104)  
88 (105)  
x
64 (81)  
67 (84)  
67 (84)  
70 (87)  
71 (88)  
74 (91)  
75 (92)  
76 (93)  
77 (94)  
78 (95)  
80 (97)  
80 (97)  
81 (98)  
84 (101)  
84 (101)  
84 (101)  
86 (103)  
88 (105)  
90 (107)  
91 (108)  
91 (108)  
x
62 (79)  
62 (79)  
64 (81)  
66 (83)  
68 (85)  
70 (87)  
71 (88)  
73 (90)  
74 (91)  
76 (93)  
79 (96)  
79 (96)  
79 (96)  
80 (97)  
80 (97)  
80 (97)  
81 (98)  
81 (98)  
81 (98)  
83 (100)  
83 (100)  
83 (100)  
84 (101)  
85 (102)  
86 (103)  
90 (107)  
63 (80)  
63 (80)  
65 (82)  
66 (83)  
68 (85)  
70 (87)  
71 (88)  
72 (89)  
73 (90)  
74 (91)  
76 (93)  
76 (93)  
77 (94)  
80 (97)  
80 (97)  
80 (97)  
82 (99)  
83 (100)  
85 (102)  
86 (103)  
86 (103)  
x
62 (79)  
62 (79)  
64 (81)  
66 (83)  
68 (85)  
70 (87)  
71 (88)  
71 (88)  
72 (89)  
73 (90)  
75 (92)  
75 (92)  
75 (92)  
76 (93)  
76 (93)  
76 (93)  
77 (94)  
78 (95)  
78 (95)  
79 (96)  
79 (96)  
80 (97)  
81 (98)  
83 (100)  
86 (103)  
88 (105)  
74 (91)  
77 (94)  
2.2 (3)  
78 (95)  
3 (4)  
81 (98)  
4 (5)  
82 (99)  
5.5 (7.5)  
7.5 (10)  
11 (15)  
90 (107)  
90 (107)  
91 (108)  
92 (109)  
92 (109)  
92 (109)  
100 (117)  
100 (117)  
100 (117)  
100 (117)  
100 (117)  
100 (117)  
100 (117)  
101 (118)  
x
15 (20)  
18.5 (25)  
22 (30)  
30 (40)  
37 (50)  
45 (60)  
55 (75)  
75 (100)  
90 (120)  
110 (150)  
150 (200)  
200 (270)  
300 (400)  
500 (670)  
1000 (1300)  
1500 (2000)  
x
x
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
x
x
x
x
x
x
x Motors in this range are generally job specific and noise levels should be calculated based on actual equipment installed.  
For 960 r/min reduce 1450 r/min values by 5 dBA.  
Page 9 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
2 TRANSPORT AND STORAGE  
2.1 Consignment receipt and unpacking  
Immediately after receipt of the equipment it must be  
checked against the delivery and shipping documents  
for its completeness and that there has been no  
damage in transportation.  
Any shortage and or damage must be reported  
immediately to Flowserve Pump Division and  
received in writing within one month of receipt of the  
equipment. Later claims cannot be accepted.  
When there are no specific lifting points on the baseplate  
A crane must be used for all pump sets in  
excess of 25 kg (55 lb.). Fully trained personnel must  
carry out lifting, in accordance with local regulations.  
Check any crates, boxes and wrappings for any  
accessories or spare parts that may be packed  
separately with the equipment or attached to side  
walls of the box or equipment.  
The driver weight is recorded on its nameplate or  
massplate.  
2.4 Storage  
Each product has a unique serial number. Check  
that this number corresponds with that advised and  
always quote this number in correspondence as well  
as when ordering spare parts or further accessories.  
Store the pump in a clean, dry  
location away from vibration. Leave piping  
connection covers in place to keep dirt and other  
foreign material out of pump casing. Turn pump at  
intervals to prevent brinelling of the bearings and the  
seal faces, if fitted, from sticking.  
2.2 Handling  
Boxes, crates, pallets or cartons may be unloaded  
using fork lift vehicles or slings dependent on their  
size and construction.  
The pump may be stored as above for up to 6  
months. Consult Flowserve for preservative actions  
when a longer storage period is needed.  
2.3 Lifting  
To avoid distortion, the pump unit  
should be lifted as shown.  
2.5 Recycling and end of product life  
At the end of the service life of the product or its  
parts, the relevant materials and parts should be  
recycled or disposed of using an environmentally  
acceptable method and local regulations. If the  
product contains substances that are harmful to the  
environment, these should be removed and disposed  
of in accordance with current regulations. This also  
includes the liquids and or gases that may be used in  
the "seal system" or other utilities.  
Make sure that hazardous substances are  
disposed of safely and that the correct personal  
protective equipment is used. The safety  
specifications must be in accordance with the current  
regulations at all times.  
Page 10 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
3.3.5 Bearing housing  
Two grease nipples enable grease lubricated bearings  
to be replenished between major service intervals.  
3 PUMP DESCRIPTION  
3.1 Configurations  
The 8-UB-1pump is a horizontal split casing two stage  
volute type centrifugal pump designed for water works,  
drainage, general service and circulating applications. It  
can be used with motor, steam turbine and gasoline or  
diesel engine drive.  
3.3.6 Seal housing  
The design enables one of a number of sealing  
options to be fitted.  
3.3.7 Shaft seal  
The mechanical seal(s), attached to the pump shaft, seals  
the pumped liquid from the environment. Gland packing  
may be fitted as an option.  
It has the following horizontal configuration:  
3.3.8 Driver  
The driver is normally an electric motor. Different drive  
configurations may be fitted such as internal combustion  
engines, turbines, hydraulic motors etc driving via  
couplings, belts, gearboxes, drive shafts etc.  
3.3.9 Accessories  
Accessories may be fitted when specified by the  
customer.  
3.2 Name nomenclature  
The pump size will be engraved on the nameplate  
typically as below:  
3.4 Performance and operating limits  
This product has been selected to meet the  
specifications of your purchase order, see section 1.5.  
8-UB- 1  
Nominal discharge branch size  
The following data is included as additional information to  
help with your installation. It is typical, and factors such  
as temperature, materials, and seal type may influence  
this data. If required, a definitive statement for your  
particular application can be obtained from Flowserve.  
Configuration – see 3.1 above  
The typical nomenclature above is the general guide  
to the UB configuration description. Identify the  
actual pump size and serial number from the pump  
nameplate. Check that this agrees with the  
applicable certification provided.  
3.4.1 Operating limits  
- 20 to + 120 ºC  
Pumped liquid temperature limits*  
(- 4 to + 250 ºF)  
- 20 to + 40 ºC  
(- 4 to +104 ºF)  
Maximum ambient temperature*  
3.3 Design of major parts  
up to 3 % by volume  
(refer for size limits)  
refer to the nameplate  
Maximum soft solids in suspension*  
3.3.1 Pump casing  
Maximum pump speed  
The pump has its main casing gasket axial to the  
shaft allowing maintenance to the rotating element by  
removing the top half casing. Suction and discharge  
branches are in the bottom half and therefore remain  
undisturbed.  
*Subject to written agreement from Flowserve.  
3.4.2 Pump and impeller data  
Impeller  
minimum  
passage  
size  
Nominal  
Mean  
wear  
radial  
Pump  
size  
ring  
diameter  
mm (in.)  
wear ring  
clearance  
mm (in.) *  
3.3.2 Impellers  
The impellers are fully shrouded and may be fitted  
with optional hub rings.  
mm (in.)  
8-UB-1  
17.5 (0.69)  
266.7 (10.5)  
0.19 (0.0075)  
*May be up to 0.13 mm (0.005 in.) larger if casing ring and impeller  
have a tendency to gaul.  
3.3.3 Shaft  
Nominal diaphragm  
bush diameter  
mm (in.)  
Mean radial  
bush clearance  
mm (in.)  
The large diameter stiff shaft, mounted on bearings,  
has a keyed drive end.  
Pump  
size  
8-UB-1  
127 (5)  
0.11 (0.0045)  
3.3.4 Pump bearings and lubrication  
Ball bearings are fitted as standard and may be either  
oil or grease lubricated.  
Page 11 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
4 INSTALLATION  
e) If the pump is driven via a universal joint drive  
shaft there may be a requirement to offset the  
pump shaft with respect to the driver to optimize  
the universal joint drive shaft bearing life. This  
offset will typically be in the range 0 to 4 degrees  
depending on shaft design. Please consult the  
separate User Instructions before installation.  
f) Any support for the universal joint drive shaft  
plummer blocks must not exhibit resonant  
frequencies in the range 0.8 to 1.2 N where  
N = pump running speed.  
Equipment operated in hazardous locations  
must comply with the relevant explosion protection  
regulations. See section 1.6.4, Products used in  
potentially explosive atmospheres.  
4.1 Location  
The pump should be located to allow room for  
access, ventilation, maintenance and inspection with  
ample headroom for lifting and should be as close as  
practicable to the supply of liquid to be pumped.  
g) If not supplied, guarding shall be fitted as  
necessary to meet the requirements of EN292  
and EN953 and or any applicable local safety  
regulations.  
Refer to the general arrangement drawing for the  
pump set.  
4.2 Foundation  
4.3 Grouting  
Where applicable, grout in the foundation bolts.  
There are many methods of installing  
pump units to their foundations. The correct method  
depends on the size of the pump unit, its location and  
noise vibration limitations. Non-compliance with the  
provision of correct foundation and installation may  
lead to failure of the pump and, as such, would be  
outside the terms of the warranty. Ensure the  
following are met.  
a) The baseplate should be mounted onto a firm  
foundation, either an appropriate thickness of  
quality concrete or sturdy steel framework. (It  
should NOT be distorted or pulled down onto the  
surface of the foundation, but should be  
After adding pipework connections and rechecking  
the coupling alignment, the baseplate should then be  
grouted in accordance with good engineering  
practice. Fabricated steel, cast iron and epoxy  
baseplates can be filled with grout. Folded steel  
baseplates should be grouted to locate their packing  
pieces. If in any doubt, please contact your nearest  
service centre for advice.  
Grouting provides solid contact between the pump  
unit and foundation, prevents lateral movement of  
running equipment and dampens resonant vibrations.  
supported to maintain the original alignment.)  
b) Install the baseplate onto packing pieces evenly  
spaced and adjacent to foundation bolts.  
Foundation bolts should only be fully tightened when  
the grout has cured.  
4.4 Initial alignment  
4.4.1 Thermal expansion  
The pump and motor will normally  
have to be aligned at ambient temperature and  
should be corrected to allow for thermal expansion at  
operating temperature. In pump installations  
involving high liquid temperatures, the unit should be  
run at the actual operating temperature, shut down  
and the alignment checked immediately.  
c) Level with shims between baseplate and packing  
pieces.  
d) The pump and driver have been aligned before  
dispatch however the alignment of pump and motor  
half coupling must be checked. If this is incorrect, it  
indicates that the baseplate has become twisted  
and should be corrected by re-shimming.  
Page 12 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
4.4.2 Alignment methods  
Pumps with thick flanged non-spacer couplings can  
be aligned by using a straight-edge across the  
outside diameters of the coupling hubs and  
measuring the gap between the machined faces  
using feeler gauges, measuring wedge or callipers.  
Ensure pump and driver are isolated  
electrically and the half couplings are disconnected.  
The alignment MUST be checked.  
When the electric motor has sleeve bearings it is  
necessary to ensure that the motor is aligned to run  
on its magnetic centreline.  
Although the pump will have been aligned at the  
factory it is most likely that this alignment will have  
been disturbed during transportation or handling. If  
necessary, align the motor to the pump, not the pump  
to the motor.  
Refer to the motor manual for details.  
A button (screwed into one of the shaft ends) is  
normally fitted between the motor and pump shaft  
ends to fix the axial position.  
Alignment is achieved by adding or removing shims  
under the motor feet and also moving the motor  
horizontally as required. In some cases where the  
alignment cannot be achieved it will be necessary to  
move the pump before recommencing the above  
procedure.  
If the motor does not run in its  
magnetic centre the resultant additional axial force  
may overload the pump thrust bearing.  
For couplings with narrow flanges use a dial indicator  
as shown below to check both parallel and angular  
alignment.  
Complete piping as below and see sections 4.6,  
Final shaft alignment check up to and including  
section 5, Commissioning, startup, operation and  
shutdown before connecting driver and checking  
actual rotation.  
Parallel  
4.5 Piping  
Protective covers are fitted to the pipe  
connections to prevent foreign bodies entering during  
transportation and installation. Ensure that these  
covers are removed from the pump before connecting  
any pipes.  
Angular  
Maximum permissible misalignment at working  
temperature:  
4.5.1 Suction and discharge pipework  
In order to minimize friction losses and hydraulic  
noise in the pipework it is good practice to choose  
pipework that is one or two sizes larger than the  
pump suction and discharge. Typically main  
pipework velocities should not exceed 2 m/s (6 ft/sec)  
suction and 3 m/s (9 ft/sec) on the discharge.  
Parallel 0.2 mm (0.008 in.) TIR  
Angular 0.1 mm (0.004 in.) TIR  
When checking parallel alignment, the total indicator  
read-out (TIR) shown is twice the value of the actual  
shaft displacement.  
Take into account the available NPSH, which must be  
higher than the required NPSH of the pump.  
Align in the vertical plane first, then horizontally by  
moving motor. When performing final alignment, check  
for soft-foot under the driver. A TIR indicator placed on  
the coupling, reading in the vertical direction, should not  
indicate more than 0.05 mm (0.002 in.) movement when  
any driver foot fastener is loosened.  
Never use the pump as a support for  
piping.  
Maximum forces and moments allowed on the pump  
flanges vary with the pump size and type. To minimize  
these forces and moments that may, if excessive,  
cause misalignment, hot bearings, worn couplings,  
vibration and the possible failure of the pump casing,  
the following points should be strictly followed:  
While the pump is capable of operating with the  
maximum misalignment shown above, maximum pump  
reliability is obtained by near perfect alignment of 0.05  
to 0.10 mm (0.002 to 0.004 in.) TIR parallel and 0.05  
mm (0.002 in.) per 100 mm (4 in.) of coupling flange  
diameter as TIR angular misalignment. This covers the  
full series of couplings available.  
Page 13 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
Typical design – flooded suction  
®
Prevent excessive external pipe load  
Never draw piping into place by applying force to  
pump flange connections  
Do not mount expansion joints so that their force,  
due to internal pressure, acts on the pump flange  
Concentric  
conical  
reducer  
Eccentric  
conical  
reducer  
Suction  
isolating  
valve  
Discharge  
isolating  
valve  
Non  
return  
valve  
>5D  
The table in 4.5.3 summarizes the maximum forces  
and moments allowed on horizontal shaft pump  
casings.  
Slope up from  
pump suction  
Ensure piping and fittings are flushed  
before use.  
Note:  
Ideally reducers should be limited to one pipe diameter change,  
ie 150 mm (6 in.) to 200 mm (8 in.). Must have a maximum total  
angle of divergence of 15 degrees.  
Ensure piping for hazardous liquids is arranged  
to allow pump flushing before removal of the pump.  
Typical design – suction lift  
4.5.2 Suction piping  
Discharge  
isolating  
valve  
Concentric  
conical  
reducer  
Eccentric  
conical  
reducer  
Non  
return  
valve  
a) The inlet pipe should be one or two sizes larger  
than the pump inlet bore and pipe bends should  
be as large a radius as possible.  
Slope down  
from pump  
suction  
>5D  
b) Pipework reducers should be conical and have a  
maximum total angle of divergence of 15 degrees.  
c) On suction lift the piping should be inclined up  
towards the pump inlet with eccentric reducers  
incorporated to prevent air locks.  
Long  
radius  
bend  
d) On positive suction, the inlet piping must have a  
constant fall towards the pump.  
e) Flow should enter the pump suction with uniform  
flow, to minimize noise and wear. This is  
particularly important on large or high-speed  
pumps, which should have a minimum of five  
diameters of straight pipe on the pump suction  
between the elbow and inlet flange. See section  
10.3, Reference 1, for more detail.  
Notes:  
1. S = Minimum submergence >3E.  
2. Ideally reducers to be limited to one pipe diameter change,  
ie 150 mm (6 in.) to 200 mm (8 in.). Must have a maximum  
total angle of divergence of 15 degrees.  
f) Inlet strainers, when used, should have a net `free  
area' of at least three times the inlet pipe area.  
g) Do not install elbows at an angle other than  
perpendicular to the shaft axis. Elbows parallel  
to the shaft axis will cause uneven flow.  
h) Except in unusual circumstances strainers are  
not recommended in inlet piping. If considerable  
foreign matter is expected a screen installed at  
the entrance to the wet well is preferable.  
i) Fitting an isolation valve will allow easier  
maintenance.  
j) Never throttle pump on suction side and never  
place a valve directly on the pump inlet nozzle.  
Page 14 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
4.5.3 Maximum forces and moments allowed on the pump suction and discharge flanges of horizontal  
shaft pumps  
Maximum forces (F) in kN (lbf) and maximum moments (M) in kNm (lbf·ft)  
Type and size  
Suction  
Discharge  
Fx  
7.35  
(1653)  
Fy  
5.78  
(1299)  
Fz  
4.20  
(944)  
Mx  
4.25  
(3134)  
My  
2.25  
(1659)  
Mz  
3.00  
(2212)  
Fx  
3.84  
(863)  
Fy  
4.40  
(989)  
Fz  
3.20  
(719)  
Mx  
2.20  
(1622)  
My  
1.20  
(885)  
Mz  
1.60  
(1180)  
8-UB-1  
Notes:  
1) F = External force (tension or compression).  
M = External moment, clockwise or counter-clockwise.  
4.5.5 Auxiliary piping  
2) Forces and moments may be applied simultaneously in any  
direction.  
3) Values apply to all materials.  
4) Higher loads may be applicable, if direction and magnitude of  
individual loads are known, but these need written approval  
from Flowserve Pumps.  
4.5.5.1 Drains  
Pipe pump casing drains and gland leakage to a  
convenient disposal point.  
4.5.5.2 Pumps fitted with packed gland  
5) Pumps must be on rigid foundations and baseplates must be  
fully grouted  
When suction pressure is below ambient pressure it  
is necessary to feed the gland packing with liquid to  
provide lubrication and prevent the ingress of air.  
This is normally achieved with a supply from the  
pump discharge volute to the stuffing box.  
6) Pump/baseplate should not be used as pipe anchor. Suction  
and discharge piping should be anchored as close as possible  
to the pump flanges to reduce vibration and prevent strain on  
the pump casing. Expansion joints are recommended. They  
must be properly tied and located on the side of the pipe anchor  
away from the pump.  
7) The pump mounting bolt torques specified must be used to  
prevent relative movement between the pump casing and  
baseplate. (See section 6.6, Fastener torques.) The bolt  
material must have a minimum yield strength of 600 N/mm2  
(87 000 lb/in.2).  
If the pumped liquid is dirty and cannot be used for  
sealing, a separate clean compatible liquid supply to  
the gland at 1 bar (15 psi) above suction pressure is  
recommended.  
4.5.4 Discharge piping  
See section 4.5.2 for typical pipework design.  
4.5.5.3 Pumps fitted with mechanical seals  
Single seals requiring re-circulation will normally be  
provided with the auxiliary piping from pump casing  
already fitted.  
A non-return valve should be located in the discharge  
pipework to protect the pump from excessive back  
pressure and hence reverse rotation when the unit is  
stopped.  
If the seal requires an auxiliary quench then a  
connection must be made to a suitable source of  
liquid flow, low pressure steam or static pressure from  
a header tank. Recommended pressure is 0.35 bar  
(5 psi) or less. Check General arrangement drawing.  
Pipework reducers should have a maximum total  
angle of divergence of 9 degrees.  
Fitting an isolation valve will allow easier maintenance.  
Page 15 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
Special seals may require different auxiliary piping to  
that described above. Consult separate User  
Instructions and or Flowserve if unsure of correct  
method or arrangement.  
If not supplied pre-wired to the pump unit, the  
controller/starter electrical details will also be supplied  
within the controller/starter.  
For electrical details on pump sets with controllers  
see the separate wiring diagram.  
For pumping hot liquids, to avoid seal damage, it is  
recommended that any external flush/cooling supply  
be continued after stopping the pump.  
See section 5.3, Direction of rotation  
before connecting the motor to the electrical supply.  
4.5.6 Final checks  
Check the tightness of all bolts in the suction and  
discharge pipework. Check also the tightness of all  
foundation bolts.  
4.8 Protection systems  
The following protection systems are  
recommended particularly if the pump is installed in a  
potentially explosive area or is handling a hazardous  
liquid. If in doubt consult Flowserve.  
4.6 Final shaft alignment check  
After connecting piping to the pump, rotate the shaft  
several times by hand to ensure there is no binding  
and all parts are free.  
If there is any possibility of the system allowing the  
pump to run against a closed valve or below  
minimum continuous safe flow a protection device  
should be installed to ensure the temperature of the  
liquid does not rise to an unsafe level.  
Recheck the coupling alignment, as previously  
described, to ensure no pipe strain. If pipe strain  
exists, correct piping.  
If there are any circumstances in which the system  
can allow the pump to run dry, or start up empty, a  
power monitor should be fitted to stop the pump or  
prevent it from being started. This is particularly  
relevant if the pump is handling a flammable liquid.  
4.7 Electrical connections  
Electrical connections must be made  
by a qualified Electrician in accordance with relevant  
local, national and international regulations.  
If leakage of product from the pump or its associated  
sealing system can cause a hazard it is  
recommended that an appropriate leakage detection  
system is installed.  
It is important to be aware of the EUROPEAN  
DIRECTIVE on potentially explosive areas where  
compliance with IEC60079-14 is an additional  
requirement for making electrical connections.  
To prevent excessive surface temperatures at  
bearings it is recommended that temperature or  
vibration monitoring are carried out. See sections  
5.7.4 and 5.7.5.  
It is important to be aware of the EUROPEAN  
DIRECTIVE on electromagnetic compatibility when  
wiring up and installing equipment on site. Attention  
must be paid to ensure that the techniques used during  
wiring/installation do not increase electromagnetic  
emissions or decrease the electromagnetic immunity of  
the equipment, wiring or any connected devices. If in  
any doubt contact Flowserve for advice.  
5 COMMISSIONING, START-UP,  
OPERATION AND SHUTDOWN  
These operations must be carried  
out by fully qualified personnel.  
The motor must be wired up in  
accordance with the motor manufacturer's instructions  
(normally supplied within the terminal box) including  
any temperature, earth leakage, current and other  
protective devices as appropriate. The identification  
nameplate should be checked to ensure the power  
supply is appropriate.  
5.1 Pre-commissioning procedure  
Pumps and electric motors are supplied pre-greased.  
Other drivers and gearboxes, if appropriate, should  
be lubricated in accordance with their manuals.  
A device to provide emergency stopping must  
be fitted.  
Page 16 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
5.2 Pump lubricants  
5.3 Direction of rotation  
Ensure the pump is given the same  
rotation as the pump direction arrow cast on the  
pump casing.  
5.2.1 Recommended grease lubricants  
Grease nipples  
Grease  
NLGI 2 *  
NLGI 3 **  
Temp. range ºC  
(ºF)  
-20 to +100  
(-4 to +212)  
-20 to +100  
(-4 to +212)  
To avoid dry running the pump must either be filled  
with liquid or have the flexible coupling disconnected  
before driver is switched on.  
Designation  
according to DIN  
K2K-20  
K2K 30  
BP  
DEA  
Elf  
Energrease LS2  
Glissando 20  
Elfmulti 2  
Energrease LS3  
Glissando 30  
Elfmulti 3  
If maintenance work has been carried  
out to the site's electricity supply, the direction of  
rotation should be re-checked as above in case the  
supply phasing has been altered.  
Esso  
Mobil  
Q8  
Beacon 2  
Beacon 3  
Mobilux 2  
Mobilux 3  
5.4 Guarding  
Rembrandt 2  
Rembrandt 3  
Alvania Fett G2  
Alvania Fett R2  
Guarding is supplied fitted to the pump set.  
If this has been removed or disturbed ensure that all  
the protective guards around the pump coupling and  
exposed parts of the shaft are securely fixed.  
Shell  
Alvania R3  
Multilak 20  
Multilak EP2  
Multilak 30  
Multilak EP3  
Texaco  
Wintershall  
(BASF Group)  
Wiolub LFK 2  
-
5.5 Priming and auxiliary supplies  
SKF  
LGMT 2  
G55/T  
LGMT 3  
G56/T  
Silkolene  
Ensure all electrical, hydraulic,  
pneumatic, sealant and lubrication systems (as  
applicable) are connected and operational.  
* NLGI 2 is an alternative grease and is not to be mixed with other  
grades.  
** Factory packed bearings for the temperature range with grease  
nipples.  
Ensure the inlet pipe and pump casing  
are completely full of liquid before starting continuous  
duty operation.  
5.2.2  
Lubrication schedule  
When grease nipples are fitted, one charge between  
grease changes is advisable for most operating  
conditions, ie 2 000 hours interval.  
5.5.1 Suction pressure above atmospheric  
pressure  
Horizontal pumps: open vent connection (1) on top of  
the pump upper casing to allow the trapped air to  
escape. Let liquid run out until free from air bubbles.  
Normal intervals between grease changes are 4 000  
hours or at least every 6 months.  
(1) Possible  
priming  
The characteristics of the installation and severity of  
service will determine the frequency of lubrication.  
Lubricant and bearing temperature analysis can be  
useful in optimising lubricant change intervals.  
points  
The bearing temperature may be allowed to rise to  
55 °C (131 °F) above ambient but should not exceed  
95 °C (204 °F). For most operating conditions a quality  
grease having a lithium soap base and NLGI  
consistency of No 2 or No 3 is recommended. The  
drop point should exceed 175 °C (350 °F).  
Never mix greases containing different  
bases, thickeners or additives.  
Page 17 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
5.5.2 Suction lift with foot valve fitted  
Fill suction pipe and casing with liquid at a pressure  
of 1 to 2 bar from an external source. Vent as  
described in section 5.5.1.  
5.7.2 Pumps fitted with packed gland  
If the pump has a packed gland there must be some  
leakage from the gland. Gland nuts should initially be  
finger-tight only. Leakage should take place soon  
after the stuffing box is pressurised.  
5.5.3 Suction lift without foot valve  
The gland must be adjusted evenly to give  
visible leakage and concentric alignment of the gland  
to avoid excess temperature. If no leakage takes  
place the packing will begin to overheat. If  
overheating takes place the pump should be stopped  
and allowed to cool before being re-started. When  
the pump is re-started, check to ensure leakage is  
taking place at the packed gland.  
Pump casing vents on the suction volute must be  
connected to an external vacuum pump priming  
system. If in doubt please consult Flowserve.  
Possible  
priming  
points  
To vacuum  
pump  
If hot liquids are being pumped it may be necessary  
to slacken the gland nuts to achieve leakage.  
The pump should be run for 30 minutes with steady  
leakage and the gland nuts tightened by 10 degrees  
at a time until leakage is reduced to an acceptable  
level, normally a minimum of 120 drops per minute is  
required. Bedding in of the packing may take another  
30 minutes.  
5.6 Starting the pump  
Care must be taken when adjusting the gland  
on an operating pump. Safety gloves are essential.  
Loose clothing must not be worn to avoid being  
caught up by the pump shaft. Shaft guards must be  
replaced after the gland adjustment is complete.  
a)  
Ensure flushing and/or cooling/  
heating liquid supplies are turned ON before  
starting the pump.  
b) CLOSE the outlet valve.  
c) OPEN all inlet valves.  
d) Prime the pump.  
Never run gland packing dry, even for  
a short time.  
e)  
Ensure all vent connections are closed  
before starting.  
5.7.3 Pumps fitted with mechanical seal  
Mechanical seals require no adjustment. Any slight  
initial leakage will stop when the seal is run in.  
f) Start motor and check outlet pressure.  
g) If the pressure is satisfactory, slowly OPEN outlet  
control valve.  
Before pumping dirty liquids it is advisable, if  
possible, to run in the pump mechanical seal using  
clean liquid to safeguard the seal face.  
h)  
Do not run the pump with the  
outlet valve closed for a period longer than 30  
seconds.  
i) If NO pressure, or LOW pressure, STOP the  
pump. Refer to section 7, Faults; causes and  
remedies, for fault diagnosis.  
External flush or quench should be  
started before the pump is run and allowed to flow for  
a period after the pump has stopped.  
5.7 Running the pump  
Never run a mechanical seal dry,  
even for a short time.  
5.7.1 Venting the pump  
5.7.4 Bearings  
Vent the pump to enable all trapped air to  
escape taking due care with hot or hazardous liquids.  
If the pumps are working in a potentially  
explosive atmosphere, temperature or vibration  
monitoring at the pump bearings is recommended.  
Under normal operating conditions, after the pump  
has been fully primed and vented, it should be  
unnecessary to re-vent the pump.  
Page 18 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
If bearing temperatures are to be monitored it is  
essential that a benchmark temperature is recorded  
at the commissioning stage and after the bearing  
temperature has stabilized.  
5.8 Stopping and shutdown  
a)  
Close the outlet valve, but ensure  
that the pump runs in this condition for no more  
than a few seconds.  
Record the bearing temperature (t) adjacent to  
the bearing and the ambient temperature (ta)  
Estimate the likely maximum ambient  
temperature (tb)  
Set the alarm at (t+tb-ta+5) °C [(t+tb-ta+10) °F]  
and the trip at 100 °C (212 °F) for oil lubrication  
and 105 °C (220 °F) for grease lubrication  
b) Stop the pump.  
c) Switch off flushing and/or cooling/heating liquid  
supplies at a time appropriate to the process.  
d)  
For prolonged shut-downs and  
especially when ambient temperatures are likely  
to drop below freezing point, the pump and any  
cooling and flushing arrangements must be  
drained or otherwise protected.  
It is important, particularly with grease lubrication, to  
keep a check on bearing temperatures. After start up  
the temperature rise should be gradual, reaching a  
maximum after approximately 1.5 to 2 hours. This  
temperature rise should then remain constant or  
marginally reduce with time. (Refer to section 6.2.3.1  
for further information.)  
5.9 Hydraulic, mechanical and electrical  
duty  
This product has been supplied to meet the  
performance specifications of your purchase order,  
however it is understood that during the life of the  
product these may change. The following notes may  
help the user decide how to evaluate the implications  
of any change. If in doubt contact your nearest  
Flowserve office.  
5.7.5 Normal vibration levels, alarm and trip  
For guidance, pumps generally fall under a  
classification for rigid support machines within the  
International rotating machinery standards and the  
recommended maximum levels below are based on  
those standards.  
5.9.1 Specific gravity (SG)  
Pump capacity and total head in metres (feet) do not  
change with SG, however pressure displayed on a  
pressure gauge is directly proportional to SG. Power  
absorbed is also directly proportional to SG. It is  
therefore important to check that any change in SG  
will not overload the pump driver or over-pressurize  
the pump.  
Alarm and trip values for installed  
pumps should be based on the actual measurements  
(N) taken on the pump in the fully commissioned as  
new condition. Measuring vibration adjacent to the  
pump bearings at regular intervals will then show any  
deterioration in pump or system operating conditions.  
Vibration velocity – unfiltered  
Horizontal  
pumps  
Vertical  
pumps  
5.9.2 Viscosity  
mm/s (in./s) r.m.s.  
For a given flow rate the total head reduces with  
increased viscosity and increases with reduced  
viscosity. Also for a given flow rate the power  
absorbed increases with increased viscosity, and  
reduces with reduced viscosity. It is important that  
checks are made with your nearest Flowserve office if  
changes in viscosity are planned.  
Normal  
Alarm  
N
5.6 (0.22)  
7.1 (0.28)  
11.2 (0.44) 14.2 (0.56)  
7.1 (0.28)  
9.0 (0.35)  
N x 1.25  
Shutdown trip N x 2.0  
5.7.6 Stop/start frequency  
Pump sets are normally suitable for the number of  
equally spaced stop/starts per hour shown in the  
table below. Check actual capability of the driver and  
control/starting system before commissioning.  
5.9.3 Pump speed  
Changing pump speed effects flow, total head, power  
absorbed, NPSHR, noise and vibration. Flow varies  
in direct proportion to pump speed, head varies as  
speed ratio squared and power varies as speed ratio  
cubed. The new duty, however, will also be  
dependent on the system curve. If increasing the  
speed, it is important therefore to ensure the  
maximum pump working pressure is not exceeded,  
the driver is not overloaded, NPSHA > NPSHR, and  
that noise and vibration are within local requirements  
and regulations.  
Maximum stop/starts  
Motor rating kW (hp)  
per hour  
Up to 15 (20)  
Between 15 (20) and 90 (120)  
Above 90 (120)  
15  
10  
6
Where duty and standby pumps are installed it is  
recommended that they are run alternately every  
week.  
Page 19 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
5.9.4 Net positive suction head (NPSHA)  
NPSH available (NPSHA) is a measure of the head  
available in the pumped liquid, above its vapour  
pressure, at the pump suction branch.  
The positioning of these accessories must not limit  
access or hinder the lifting of the part to be serviced.  
When air or compressed inert gas is used in the  
maintenance process, the operator and anyone in the  
vicinity must be careful and have the appropriate  
protection.  
NPSH required (NPSHR) is a measure of the head  
required in the pumped liquid, above its vapour  
pressure, to prevent the pump from cavitating. It is  
important that NPSHA > NPSHR. The margin between  
NPSHA > NPSHR should be as large as possible.  
Do not spray air or compressed inert gas on skin.  
Do not direct an air or gas jet towards other people.  
Never use air or compressed inert gas to clean clothes.  
If any change in NPSHA is proposed, ensure these  
margins are not significantly eroded. Refer to the  
pump performance curve to determine exact  
requirements particularly if flow has changed. If in  
doubt please consult your nearest Flowserve office  
for advice and details of the minimum allowable  
margin for your application.  
Before working on the pump, take measures to  
prevent an uncontrolled start. Put a warning board  
on the starting device with the words:  
"Machine under repair: do not start".  
5.9.5 Pumped flow  
With electric drive equipment, lock the main switch  
open and withdraw any fuses. Put a warning board  
on the fuse box or main switch with the words:  
"Machine under repair: do not connect".  
Flow must not fall outside the minimum and  
maximum continuous safe flow shown on the pump  
performance curve and or data sheet.  
Never clean equipment with inflammable solvents or  
carbon tetrachloride. Protect yourself against toxic  
fumes when using cleaning agents.  
6 MAINTENANCE  
6.1 General  
6.2 Maintenance schedule  
It is the plant operator's responsibility to ensure  
that all maintenance, inspection and assembly work  
is carried out by authorized and qualified personnel  
who have adequately familiarized themselves with  
the subject matter by studying this manual in detail.  
(See also section 1.6.2.)  
It is recommended that a maintenance plan and  
schedule is adopted, in line with these User  
Instructions. It should include the following:  
a) Any auxiliary systems installed must be monitored,  
if necessary, to ensure they function correctly.  
b) Gland packings must be adjusted correctly to  
give visible leakage and concentric alignment of  
the gland follower to prevent excessive  
Any work on the machine must be performed when it  
is at a standstill. It is imperative that the procedure  
for shutting down the machine is followed, as  
described in section 5.8.  
temperature of the packing or follower.  
c) Check for any leaks from gaskets and seals. The  
correct functioning of the shaft seal must be  
checked regularly.  
On completion of work all guards and safety devices  
must be re-installed and made operative again.  
d) Check bearing lubricant level, and if the hours  
run show a lubricant change is required.  
e) Check that the duty condition is in the safe  
operating range for the pump.  
f) Check vibration, noise level and surface  
temperature at the bearings to confirm  
Before restarting the machine, the relevant  
instructions listed in section 5, Commissioning, start  
up, operation and shut down must be observed.  
Oil and grease leaks may make the ground  
slippery. Machine maintenance must always  
begin and finish by cleaning the ground and the  
exterior of the machine.  
satisfactory operation.  
g) Check dirt and dust is removed from areas around  
close clearances, bearing housings and motors.  
h) Check coupling alignment and re-align if necessary.  
If platforms, stairs and guard rails are required for  
maintenance, they must be placed for easy access to  
areas where maintenance and inspection are to be  
carried out.  
Page 20 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
Our specialist service personnel can help with  
preventative maintenance records and provide  
condition monitoring for temperature and vibration to  
identify the onset of potential problems.  
Regrease - via grease nipples every 2 000 hours or  
sooner depending on the severity of the application.  
a) It is important not to under or over grease the  
bearings as this will lead to over heating and  
premature failure. Grease lubricated bearing  
housings have grease nipples fitted in the  
bearing brackets.  
If any problems are found the following sequence of  
actions should take place:  
a) Refer to section 7, Faults; causes and remedies,  
for fault diagnosis.  
b) Ensure equipment complies with the  
recommendations in this manual.  
b) The maximum allowable operating temperatures  
for anti friction bearings will vary from unit to unit,  
depending on ambient and fluid temperature.  
The rise above ambient should not normally  
exceed 55 °C (131 °F) or a combined maximum  
of 95 °C (204 °F).  
c) Contact Flowserve if the problem persists.  
6.2.1 Routine inspection (daily/weekly)  
c) A continuously rising temperature or an abrupt  
temperature rise indicates a problem. If these  
symptoms occur, stop the pump immediately and  
investigate the cause.  
The following checks should be made  
and the appropriate action taken to remedy any  
deviations:  
a) Check operating behaviour. Ensure noise,  
vibration and bearing temperatures are normal.  
b) Check that there are no abnormal fluid or  
lubricant leaks (static and dynamic seals) and  
that any sealant systems (if fitted) are full and  
operating normally.  
c) Check that shaft seal leaks are within acceptable  
limits.  
d) Check the level and condition of oil lubricant. On  
grease lubricated pumps, check running hours  
since last recharge of grease or complete grease  
change.  
TIME  
Grease change - every 4 000 hours or sooner  
depending on the severity of the application.  
a) Remove the bearing bracket from the rotor  
assembly.  
b) Brush the bearing bracket with hot kerosene (100 to  
115 °C/212 to 240 °F) or other non-toxic solvent.  
c) Clean and flush out the housing with a light  
mineral oil.  
e) Check any auxiliary supplies eg. heating/cooling,  
if fitted, are functioning correctly.  
Refer to the manuals of any associated  
equipment for routine checks needed.  
6.2.2 Periodic inspection (six monthly)  
a)  
Check foundation bolts for  
security of attachment and corrosion.  
b) Check pump running records for hourly usage to  
determine if bearing lubricant requires changing.  
c) The coupling should be checked for correct  
alignment and worn driving elements.  
d) Do not use waste oil to clean the housing.  
To clean the bearings:  
a) Wipe off as much grease as possible with a clean  
lint-free cloth.  
Refer to the manuals of any associated  
equipment for periodic checks needed.  
b) Brush bearings with hot kerosene (80 to 90 °C/  
175 to 195 °F) while gently spinning the outer  
bearing ring.  
6.2.3 Re-lubrication  
Lubricant and bearing temperature analysis can be  
useful in optimizing lubricant change intervals. In  
general however, the following is recommended.  
c) Spin each ball to ensure that it is clean.  
See section 5.2.1 for grease  
recommendations.  
Page 21 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
6.3 Spare parts  
6.3.1 Ordering of spares  
Flowserve keeps records of all pumps that have been  
supplied. When ordering spares the following  
information should be quoted.  
1) Pump serial number.  
2) Pump size.  
3) Part name – taken from section 8.  
4) Part number – taken from section 8.  
5) Number of parts required.  
To remove badly oxidized grease that refuses to  
come off:  
The pump size and serial number are shown on the  
pump nameplate.  
a) Support the rotor in a vertical position and  
immerse the bearing in hot kerosene or a mixture  
of alcohol and light mineral solvent.  
b) Gently spin the bearing outer ring.  
To ensure continued satisfactory operation,  
replacement parts to the original design specification  
should be obtained from Flowserve. Any change to  
the original design specification (modification or use  
of a non-standard part) will invalidate the pump’s  
safety certification.  
6.3.2 Storage of spares  
Spares should be stored in a clean dry area away  
from vibration. Inspection and re-treatment of  
metallic surfaces (if necessary) with preservative is  
recommended at 6 monthly intervals.  
c) Dry and reflush the bearing with clean light oil.  
d) It is important not to under or over grease the  
bearings as this will lead to over heating and  
premature failure. It is recommended that the  
bearings be filled with grease using a suitable  
spatula. In addition the housings should be no  
more than half filled.  
6.4 Recommended spares and  
consumable items  
For start up purposes:  
6.2.4 Mechanical seals  
No adjustment is possible. When leakage reaches  
an unacceptable level the seal will need replacement.  
1 - complete set of gland packing  
2 - shaft sleeves  
1 - set of gaskets and seals  
(optional: 2 - mechanical seals)  
6.2.5 Gland packing  
The stuffing box gland can be backed off for  
re-packing or to enable the addition of extra rings of  
packing.  
For 2 years operation:  
1 - set of bearings (line and thrust)  
2 - sets of gland packing  
2 - shaft sleeves  
The stuffing box is normally supplied with a lantern  
ring to enable a clean or pressurised flush to the  
centre of the packing. If not required, this can be  
replaced by an extra 2 rings of packing.  
2 - sets of gaskets and seals  
2 - lantern rings  
2 - casing wear rings  
1 – diaphragm bush  
(optional: 2 - mechanical seals  
2 - impeller wear rings)  
There must always be a small leakage, normally a  
minimum of 120 drops per minute to atmosphere to  
lubricate and cool the packing is required.  
For 4 years operation:  
1 - set of bearings (line and thrust)  
2 - sets of gland packing  
2 - shaft sleeves  
2 - sets of gaskets and seals  
2 - lantern rings  
2 - casing wear rings  
Page 22 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
1 – impeller  
To dismantle the pump consult the sectional  
1 – diaphragm bush  
drawings. See section 8, Parts lists and drawings.  
(optional: 2 - mechanical seals  
2 - impeller wear rings)  
a) Isolate motor and lock off electrical supply in  
accordance with local regulations.  
b) Isolate suction and discharge valves.  
c) Remove coupling guards and disconnect the  
coupling halves.  
d) Drain pump casing. Remove any auxiliary piping  
if applicable.  
6.5 Tools required  
A typical range of tools that will be required to  
maintain these pumps is listed below.  
Readily available in standard tool kits, and dependent  
on pump size:  
e) Release the copper lockwasher securing the  
coupling nut and remove the pump half coupling.  
f) Unbolt the glands/seal covers from the casing.  
If glands are split type, remove completely.  
g) With a suitable punch, drive out the two locating  
dowels which are used on the horizontal split  
flange to align the upper and lower half casings.  
h) Remove the bolts, which hold the upper and lower  
half of the casing together, and remove the upper  
half. Tapped holes are provided in the joint flange  
to enable the use of forcing bolts to loosen the joint.  
i) Lift the casing upper half using the two eye bolts  
provided.  
Open ended spanners (wrenches) to suit up to  
M 24 (7/8 in.) screws/nuts  
Socket spanners (wrenches), up to M 24 (7/8 in.)  
screws  
Allen keys, up to 6 mm (¼ in.) A/F  
Range of screwdrivers  
Soft mallet  
More specialized equipment:  
Bearing pullers  
Bearing induction heater  
Dial test indicator  
C-spanner (wrench) - for removing shaft nut.  
(If difficulties in sourcing are encountered, consult  
Flowserve.)  
Do NOT use this method to lift the bottom  
half or complete pump casing.  
j) Remove the 6 – screws securing each bearing  
bracket to the bottom half casing.  
k) Lift out rotor assembly. Use care in slinging,  
handling and supporting of the rotor for  
subsequent dismantling. Place rotor securely on  
two support blocks.  
l) When removing the rotor assembly, the casing rings  
and diaphragm plate will be loosely attached to the  
rotor.  
6.6 Fastener torques  
Torque Nm (lbf·ft)  
Bolt size  
Pump feet  
All other  
fasteners  
fasteners  
M8 (5/16 in.)  
M10 (in.)  
M12 (½ in.)  
M16 (in.)  
M20 (¾ in.)  
M24 (in.)  
-
-
10 (7)  
20 (15)  
63 (46)  
170 (125)  
340 (250)  
590 (435)  
34 (25)  
84 (62)  
165 (120)  
285 (210)  
m) Remove bearing covers and slide bearing housings  
off bearings.  
n) Release the copper lockwasher securing the  
bearing locknut at the non-drive end and remove the  
locknut. Pull off both ball bearings using a suitable  
puller; ensuring force is applied to inner race only.  
Retain the bearing distance pieces and coupling  
distance piece for future use. Remove the bearing  
covers.  
6.7 Renewal clearances  
As wear takes place between the impeller, casing ring  
and diaphragm bush the overall efficiency of the pump  
set will decrease. To maintain optimum efficiency it is  
recommended that rings and bush are replaced and the  
impeller renovated when the radial clearance detailed in  
section 3.4.2 has doubled.  
o) Depending on configuration remove glands/seal  
covers, packing and lantern ring/mechanical seal.  
6.8 Disassembly  
Refer to any special instructions supplied  
with the mechanical seal.  
Refer to section 1.6, Safety, before dismantling  
the pump.  
p) Remove the two socket head screws securing  
each shaft sleeve nut. Using C-spanner remove  
shaft nuts. Slide off shaft sleeves.  
Before dismantling the pump for  
overhaul, ensure genuine Flowserve replacement  
parts are available.  
Page 23 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
q) Remove impellers, casing rings, diaphragm plate  
complete with its bush together with the impeller  
key.  
d) Bearing seals are not totally leak free devices.  
Oil from these may cause staining adjacent to the  
bearings.  
If impellers prove difficult to remove, the  
use of heat is permissible. Refer to Section 1.6,  
Safety, APPLYING HEAT TO REMOVE  
6.10 Assembly  
To assemble the pump consult the sectional  
drawings, see section 8, Parts list and drawings.  
IMPELLER, for more details.  
r) If it is required to remove the diaphragm plate  
bush then remove the 4 countersunk screws and  
push out the bush.  
s) If impeller rings are also fitted, they are shrunk  
onto the impeller and fixed with locking screws  
between their diametric mating surfaces.  
t) To remove the impeller rings, remove the locking  
screws and heat up the ring until it slides off easily.  
Ensure threads, gasket and O-ring mating faces are  
clean. Apply thread sealant to non-face sealing pipe  
thread fittings. Coat the outside diameter of the dowel  
bushings with pipe compound prior to installation.  
6.10.1 Impeller wear rings  
a) Impeller rings (when fitted) should be heated up  
to approximately 100 ºC (212 ºF) using a hotplate  
or hot oil bath and then slipped onto the impeller  
and pressed down to the shoulder. (Do NOT use  
a steel hammer to knock them into position.)  
b) Drill and tap 3 holes approximately 120 degrees  
apart into the diametral mating faces of the ring  
and impeller and insert socket head screws.  
(The existing half tapped holes from the removed  
impeller ring cannot be re-used.)  
6.9 Examination of parts  
Used parts must be inspected before  
assembly to ensure the pump will subsequently run  
properly.  
In particular, fault diagnosis is essential to enhance  
pump and plant reliability.  
46  
6.9.1 Casing, seal housing and impeller  
a) Inspect for excessive wear, pitting, corrosion,  
erosion or damage and any sealing surface  
irregularities.  
45  
b) Replace as necessary.  
6.9.2 Shaft and sleeve (if fitted)  
Replace if grooved, pitted or worn.  
6.10.2 Pre-assembly of casing gasket  
a) Fit casing gasket to the bottom half horizontal  
flange using a small amount of contact adhesive  
to prevent movement when the top half is fitted.  
Do not apply adhesive to the top surface of the  
gasket.  
b) It is important that the external corner of the  
casing gasket face and the stuffing box face is as  
sharp as possible.  
6.9.3 Gaskets and O-rings  
After dismantling, discard and replace.  
6.9.4 Bearings  
It is recommended that bearings are not re-used after  
any removal from the shaft.  
6.9.5 Bearing isolators, labyrinths or lip seals  
(if fitted)  
a) The lubricant, bearings and bearing housing  
seals are to be inspected for contamination and  
damage.  
b) If bearing damage is not due to normal wear and  
the lubricant contains adverse contaminants, the  
cause should be corrected before the pump is  
returned to service.  
c) Labyrinth seals and bearing isolators should be  
inspected for damage but are normally non-  
wearing parts and can be re-used.  
Do not chamfer with a file.  
c) If necessary trim gasket to match volute profile.  
Do not trim to stuffing box face at this stage.  
6.10.3 Rotating element and bearing bracket  
a) Ensure all gaskets and O-rings are renewed and  
replaced in the correct position during assembly.  
b) Assemble the impellers on the shaft. It is  
important to mount the impellers so that the vane  
tips point away from the apparent flow direction.  
Page 24 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
The bearings must be heated up to 100 ºC (212 ºF)  
using a hot plate, oil bath or induction heater and  
slid onto the shaft. Ensure bearing is fully seated  
against the bearing distance piece and the distance  
piece is located up to the shaft shoulder.  
j) Fill both sides of bearing with grease.  
k) Fit the bearing lockwasher and tighten the  
bearing shaft nut.  
l) Peen a segment of the copper lockwasher over a  
flat on the bearing locknut.  
m) Slip casing rings, loosely over the impeller hubs.  
n) Slide the bearing housings over the bearings.  
Ensure bearings are located square in the  
bracket bore.  
o) One third fill the space between bearing cover  
and bearing with grease. Secure bearing cover,  
complete with gasket.  
p) Fit the coupling distance piece and pump half  
coupling. Fit copper lockwasher and secure  
coupling nut. Peen a segment of the copper  
lockwasher over a flat on the coupling nut.  
The rotor always rotates towards the expanding  
section of the volute  
c) The diaphragm plate complete with its bush must  
be fitted on to the shaft between the two impellers.  
d) Fit the two shaft sleeves, O-rings (when fitted)  
and shaft nuts and lightly secure the impellers on  
the shaft. Take care to protect the sleeve O-rings  
(when fitted) from damage on the shaft threads.  
The sleeves and nuts define the impeller position  
on the pump shaft and hence in the pump casing.  
Initially position the impellers centrally on its  
keyway. This position may be adjusted slightly  
later on in the assembly process.  
e) It is recommended that gasket sealing compound  
Loctite 574 or equivalent is used between sleeve  
and impeller mating faces to protect the shaft  
from the liquid pumped.  
f) When mechanical seals are fitted the rotating  
parts can be slid onto the sleeves before the  
sleeves are fitted onto the shaft. The seal locking  
collars should be left loose.  
6.10.4 Casing lower half  
a) If required, drive in two new locating dowels on  
the horizontal flange.  
b) Coat the faces of the bearing housing brackets  
with liquid sealant to protect against corrosion.  
c) Place the complete rotating assembly into the  
casing ensuring that impeller rings and diaphragm  
plate are in the correct position to allow the anti-  
rotation tongues to locate correctly in the anti-  
rotation grooves in the casing bores.  
Refer to any special instructions supplied  
The anti-rotation grooves in the bottom  
half casing are bigger in diameter than those in  
the top.  
with the mechanical seal.  
g) If gland packing is used fit the glands.  
h) Fit seal covers complete with seal seat, water  
throwers and bearing covers complete with  
gaskets.  
i) Fit the bearings onto the shaft. The main thrust  
bearing is at the non-drive end.  
d) Locate the bearing housings in the machined  
spigots in the casing and torque up the fixing  
screws.  
e) Check rotor for free rotation.  
f) Centralize the impellers within the casing  
waterway by adjusting the shaft nut, if necessary.  
Using a C-spanner fully tighten the shaft nuts and  
lock with the two radial socket head screws.  
g) Set the seals, if fitted, to the correct working  
length and tighten the seal collar screws.  
Where double row bearings are fitted  
these must be assembled 'back to back' as below:  
Refer to any special instructions supplied  
with the mechanical seal.  
h) Check for free rotation.  
Page 25 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
6.10.5 Casing upper half  
a) Assemble the casing upper half over the lower  
half. Take care to ensure the renewable rings and  
diaphragm plate are correctly located in the upper  
half bores and that dowel holes pick up the  
locating dowels in the lower half.  
b) Tap horizontal flange over locating dowels to  
accurately position the top half casing and torque  
up all horizontal flange bolts.  
c) Check for free rotation.  
d) Using a sharp flexible-bladed knife, cut off the  
exposed casing gasket in the stuffing box area  
flush with the stuffing box face.  
e) If mechanical seals are fitted apply a small amount  
of silicon rubber sealant along the horizontal joint  
line on the stuffing box face and fit seal cover  
complete with gasket or O-ring. Take care not to  
damage O-ring, if fitted, and locate cover squarely  
on stuffing box face.  
f) Torque up seal cover bolts and check shaft/sleeve  
does not rub on seal cover or stationary seal seat  
bore. Ensure any spare holes in mechanical seal  
cover, particularly on cartridge seals, have sealing  
plugs fitted.  
g) If gland packing is fitted pack the gland, ensuring  
that the cut ends in each ring are staggered by  
120 degrees. The glands are packed as shown on  
the relevant drawings in Sections 8.1 to 8.3.  
Finger tighten the gland nuts.  
h) Check coupling alignment, fit coupling drive  
element(s) and fit guards.  
i) Pipe up any external auxiliary connections.  
j) Check for free rotation.  
Page 26 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
7 FAULTS; CAUSES AND REMEDIES  
FAULT SYMPTOM  
Pump overheats and seizes  
Bearings have short life  
Pump vibrates or is noisy  
Mechanical seal has short life  
Mechanical seal leaks excessively  
Pump requires excessive power  
Pump loses prime after starting  
Insufficient pressure developed  
Insufficient capacity delivered  
Pump does not deliver liquid  
PROBABLE CAUSES  
POSSIBLE REMEDIES  
A. SYSTEM TROUBLES  
z
z
z
z
Pump not primed.  
Check complete filling.  
Pump or suction pipe not completely filled with  
liquid.  
z
z
z
z
z
z
Check and complete filling.  
Check NPSHA>NPSHR, proper submergence,  
losses at strainers and fittings.  
z
z
Suction lift too high or level too low.  
z
z
z
z
z
z
z
Excessive amount of air or gas in liquid.  
Air or vapour pocket in suction line.  
Air leaks into suction line.  
Check and purge from pipes.  
Check suction line design for pockets.  
Check airtight pipe then joints and gaskets.  
Air leaks into pump through mechanical seal,  
sleeve joints, casing joint or pipe lugs.  
z
z
Check airtight assembly then joints and gaskets.  
z
z
z
z
z
z
Foot valve too small.  
Investigate replacing the foot valve.  
Clean foot valve.  
Foot valve partially clogged.  
z
z
z
Inlet of suction pipe insufficiently submerged.  
Check cut out system design.  
Check discharge head and head losses in  
discharge pipe at the valve settings. Check back  
pressure is not too high.  
z
z
z
z
Total head of system higher than differential head  
of pump.  
Total head of system lower than pump design  
head.  
Throttle at discharge valve or ask Flowserve if the  
impeller can be trimmed.  
z
z
z
Specific gravity of liquid different from design.  
Viscosity of liquid differs from design.  
Operation at very low capacity.  
Consult Flowserve.  
Consult Flowserve.  
z
z
z
z
Measure value and check minimum permitted.  
Measure value and check maximum permitted.  
z
z
z
z
Operation at high capacity.  
B. MECHANICAL TROUBLES  
Check the flange connections and eliminate  
strains using elastic couplings or a method  
permitted.  
z
z
z
Misalignment due to pipe strain.  
Check setting of baseplate: tighten, adjust, grout  
base as required.  
z
z
z
z
Improperly designed foundation.  
Shaft bent.  
z
z
z
z
z
z
z
z
z
Check shaft runouts within acceptable values.  
Check for signs of this and consult Flowserve if  
necessary.  
z
z
Rotating part rubbing on stationary part internally.  
z
z
Bearings worn  
Replace bearings.  
z
z
Wearing ring surfaces worn.  
Replace worn wear ring/surfaces.  
Page 27 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
FAULT SYMPTOM  
Pump overheats and seizes  
Bearings have short life  
Pump vibrates or is noisy  
Mechanical seal has short life  
Mechanical seal leaks excessively  
Pump requires excessive power  
Pump loses prime after starting  
Insufficient pressure developed  
Insufficient capacity delivered  
Pump does not deliver liquid  
PROBABLE CAUSES  
POSSIBLE REMEDIES  
z
z
z
Impeller damaged or eroded.  
Replace impeller and check reason.  
Replace joint and check for damage.  
z
z
Leakage under sleeve due to joint failure.  
Check alignment of faces or damaged parts and  
assembly method used.  
z
z
z
z
z
z
Mechanical seal improperly installed.  
Incorrect type of mechanical seal for operating  
conditions.  
z
z
Consult Flowserve  
Check misalignment and correct if necessary.  
If alignment satisfactory check bearings for  
excessive wear.  
z
z
z
z
z
Shaft running off centre because of worn  
bearings or misalignment.  
z
z
z
z
Impeller out of balance resulting in vibration.  
Abrasive solids in liquid pumped.  
Check and consult Flowserve.  
Check and consult Flowserve.  
z
z
Check mechanical seal condition and source of  
dry running and repair.  
z
z
z
z
Mechanical seal was run dry.  
Internal misalignment due to improper repairs  
causing impeller to rub.  
Check method of assembly, possible damage or  
state of cleanliness during assembly.  
z
z
z
z
Excessive thrust caused by a mechanical failure  
inside the pump.  
Check wear condition of impeller, its clearances  
and liquid passages.  
z
z
z
z
z
z
Excessive grease in ball bearings.  
Lack of lubrication for bearings.  
Check method of regreasing.  
Check hours run since last change of lubricant,  
the schedule and its basis.  
Check method of assembly, possible damage or  
state of cleanliness during assembly and type of  
bearing used.  
z
z
z
z
Improper installation of bearings.  
Check contamination source and replace  
damaged bearings.  
Damaged bearings due to contamination.  
C. ELECTRICAL TROUBLES  
z
z
z
z
z
z
z
Wrong direction of rotation.  
Motor running too slow.  
Reverse 2 phases on motor terminal box.  
Check motor terminal box connections.  
Page 28 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
8 PARTS LISTS AND DRAWINGS  
8.1 Sectional drawings – 8-UB-1 grease lubricated, gland packed  
3
4
5
6
7
8
17  
15  
13  
15A  
9
12  
16  
18  
21  
29  
25  
26  
27  
28  
32  
31  
14  
1
2
20A  
10  
11  
19  
20  
22  
23  
24  
30  
Taken from A767/112  
8.1.1 Parts list  
12  
13  
14  
15  
15A  
16  
17  
18  
19  
20  
Casing wear ring  
Diaphragm plate  
Diaphragm bush  
Impeller – first stage  
Impeller – second stage  
Key – impeller  
Seal pipe assembly  
Shaft sleeve  
Shaft nut  
22  
Water shield  
Bearing cover  
Gasket – bearing cover  
Ball bearing – line  
Grease nipple  
Shaft  
Key – coupling  
Bearing distance piece  
Coupling distance piece  
Coupling nut  
Ref. no. Description  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
1
2
Nameplate  
Bearing locknut  
3
4
5
Lockwasher – bearing locknut  
Ball bearing - thrust  
Shaft collar  
6
Gland  
7
Lantern ring  
8
Gland packing  
Bearing bracket – Drive end  
Bearing bracket – Non-drive end  
Socket head screw for 19 & 38  
9
10  
11  
Casing – upper half  
Casing – lower half  
Gasket – horizontal split  
20A  
21  
Lockwasher – for coupling nut  
Page 29 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
8.1.2 Options  
8.1.3 Options parts list  
Ref. no. Description  
46  
34  
35  
36  
37  
38  
39  
40  
45  
46  
Mechanical seal  
Mechanical seal cover  
Gasket – mechanical seal cover  
Socket head screw for 38 (a)  
Seal abutment ring (a)  
Cartridge seal assembly  
Impeller nut  
45  
Impeller wear ring  
Socket head screw for 45  
View on ‘Z’ impeller ring  
a) When fitted, depends on type of mechanical seal.  
37  
34  
36  
35  
8.2 General arrangement drawing  
The typical general arrangement drawing and any  
specific drawings required by the contract will be sent to  
the Purchaser separately unless the contract specifically  
calls for these to be included into the User Instructions.  
If required, copies of other drawings sent separately to  
the Purchaser should be obtained from the Purchaser  
and retained with these User Instructions.  
38  
Component mechanical seal  
40  
21  
39  
Cartridge mechanical seal  
Page 30 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
9 CERTIFICATION  
Certificates determined from the Contract requirements  
are provided with these Instructions where applicable.  
Examples are certificates for CE marking, ATEX  
marking etc. If required, copies of other certificates sent  
separately to the Purchaser should be obtained from  
the Purchaser for retention with these User Instructions.  
10 OTHER RELEVANT  
DOCUMENTATION AND MANUALS  
10.1 Supplementary User Instructions  
Supplementary instructions such as for a driver,  
instrumentation, controller, seals, sealant system etc  
are provided as separate documents in their original  
format. If further copies of these are required they  
should be obtained from the supplier for retention  
with these User Instructions.  
10.2 Change notes  
If any changes, agreed with Flowserve Pump Division,  
are made to the product after its supply, a record of the  
details should be maintained with these User Instructions.  
10.3 Additional sources of information  
Reference 1:  
NPSH for Rotordynamic Pumps: a reference guide,  
Europump Guide No. 1, Europump & World Pumps,  
Elsevier Science, United Kingdom, 1999.  
Reference 2:  
Pumping Manual, 9th edition, T.C. Dickenson,  
Elsevier Advanced Technology, United Kingdom, 1995.  
Reference 3:  
Pump Handbook, 2nd edition, Igor J. Karassik et al,  
McGraw-Hill Inc., New York, 1993.  
Reference 4:  
ANSI/HI 1.1-1.5  
Centrifugal Pumps - Nomenclature, Definitions,  
Application and Operation.  
Reference 5:  
ANSI B31.3 - Process Piping.  
Page 31 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UB USER INSTRUCTIONS ENGLISH 71569247 07-04  
®
FLOWSERVE  
REGIONAL SALES OFFICES:  
USA and Canada  
Latin America and Caribbean  
Flowserve Corporation (Pump Division)  
5215 North O’Connor Blvd. Suite 2300  
Irving, Texas 75039, USA  
Flowserve Corporation (Pump Division)  
6840 Wynnwood Lane  
Houston, Texas 77008, USA  
Tel +1 972 443 6500  
Toll free 800 728 PUMP (7867)  
Fax +1 972 443 6800  
Tel +1 713 803 4434  
Fax +1 713 803 4497  
Europe, Middle East and Africa  
Flowserve Limited (Pump Division)  
Harley House, 94 Hare Lane  
Claygate, Esher, Surrey KT10 0RB  
United Kingdom  
Asia Pacific  
Flowserve Pte Ltd (Pump Division)  
200 Pandan Loop, 06-03/04  
Pantech 21, Singapore 128388  
Tel +65 775 3003  
Fax +65 779 4607  
Tel +44 (0)1372 463 700  
Fax +44 (0)1372 460 190  
Visit our web site at: www.flowserve.com  
Your Flowserve factory contact:  
Your local Flowserve representative:  
Flowserve Pumps Limited  
PO Box 17, Newark  
Notts NG24 3EN  
United Kingdom  
Telephone (24 hours) +44 (0)1636 494 600  
Sales & Admin Fax +44 (0)1636 705 991  
Repair & Service Fax +44 (0)1636 494 833  
To find your local Flowserve representative, please  
use the Sales Support Locator System found at  
Page 32 of 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  

GPX Stereo System HT119B User Manual
Hasselblad Camcorder H4D200MS User Manual
Havis Shields Laptop Docking Station DS DELL 101 User Manual
Hotpoint Cooktop BG51 B P User Manual
HP Hewlett Packard Server 5187 2725 User Manual
Husqvarna Chainsaw SMB 70 SMB 70 E User Manual
Hypertec Mouse KYBAC210 PS2HY User Manual
IBM Credit Card Machine OS User Manual
IKEA Indoor Furnishings AA 171181 1 User Manual
Impex Home Gym AB 4000 User Manual