Greenheck Fan Ventilation Hood PN 471755 User Manual

PN 471755  
®
Sidewall Propeller Fans  
Belt Drive, Direct Drive and Reversible  
Exhaust, Supply and Filtered Supply  
Installation, Operation and Maintenance Manual  
Please read and save these instructions for future reference. Read carefully before attempting  
to assemble, install, operate, or maintain the product described. Protect yourself and others by  
observing all safety information. Failure to comply with instructions could result in personal injury  
and/or property damage!  
Sidewall Propeller Fans  
Greenheck’s sidewall propeller fan line is the ideal choice for factory and  
warehouse applications where high volumes of air and low pressures are  
required. From general ventilation to industrial duty, the range of construction  
and performance capabilities offered represent the most comprehensive sidewall  
propeller fan line in the industry.  
Performance spans the range between 300 to 87,000 cfm (510 to 147,814 m3/hr)  
with static pressures to 1.25 in. wg (249 Pa). Fan sizes range from 8 to 54 inches  
(203 to 1372 mm) for direct drive and 20 to 72 inches (508 to 1829 mm) for belt  
drive. Regardless of fan size, performance or duty level, all Greenheck sidewall  
propeller fans are built to perform with the same high standards of reliability and  
durability. All models are available in exhaust or supply arrangements.  
Models SE1, SS1, SE2, SS2, SCE3, SCS3, SCR3, SBE-1, SBS-1, SBE-2, SBS-2, SBE-3, SBS-3, SBCE, SBCS, and SBCR.  
Filtered Supply  
Filtered supply wall housings are available in seven sizes for fans ranging  
from size 24 to 54 inches (610 to 1372 mm). They are designed with  
the draw-thru concept to achieve the highest filter and fan efficiencies.  
Permanent 2 inch (51 mm) washable filters are accessed through a bolted  
panel and can be easily removed for cleaning.  
General Safety Information  
Only qualified personnel should install this fan.  
Personnel should have a clear understanding of  
these instructions and should be aware of general  
safety precautions. Improper installation can result  
in electric shock, possible injury due to coming in  
contact with moving parts, as well as other potential  
hazards. Other considerations may be required  
if high winds or seismic activity are present. If  
more information is needed, contact a licensed  
professional engineer before moving forward.  
the National Fire Protection Agency (NFPA),  
where applicable. Follow the Canadian Electric  
Code (CEC) in Canada.  
2. The rotation of the propeller is critical. It must  
be free to rotate without striking or rubbing any  
stationary objects.  
3. Motor must be securely and adequately  
grounded.  
4. Do not spin fan propeller faster than max  
cataloged fan RPM. Adjustments to fan speed  
significantly effects motor load. If the fan RPM is  
changed, the motor current should be checked  
to make sure it is not exceeding the motor  
nameplate amps.  
DANGER  
Always disconnect, lock and tag power source before  
installing or servicing. Failure to disconnect power source  
can result in fire, shock or serious injury.  
5. Do not allow the power cable to kink or come  
in contact with oil, grease, hot surfaces,  
or chemicals. Replace cord immediately if  
damaged.  
CAUTION  
When servicing the fan, motor may be hot enough to  
cause pain or injury. Allow motor to cool before servicing.  
CAUTION  
Precaution should be taken in explosive atmospheres.  
6. Verify that the power source is compatible with  
the equipment.  
7. Never open access doors to a duct while the fan  
is running.  
1. Follow all local electrical and safety codes, as  
well as the National Electrical Code (NEC) and  
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
Fans mounted to the wall require a different wall  
opening (W.O.) size than those mounted in collars or  
wall housings. Propeller-to-damper distance (M) is  
important to reduce turbulence and damper flutter  
which may lead to premature damper failure.  
Pre-Installation Checks  
Check chart below for correct wall opening  
dimensions.  
Check motor voltage and amperage rating for  
compatibility with electrical supply. Supply wiring  
must be properly fused and conform to local and  
national codes.  
Figure 1 and 2 show the wall opening (W.O.) required  
for installations with either a wall housing or collar.  
Figure 3 shows the recommended wall opening  
(W.O.) and the minimum distance (M) suggested  
between the fan and damper for direct to wall  
installations.  
Figure 4 shows the dimensions and wall opening  
(W.O.) required for installations with a filtered supply  
wall housing.  
Motor load amperage must be checked and  
compared to nameplate rating to avoid serious  
damage to motor when speed is increased.  
Wall Opening Requirements  
Wall opening size and propeller-to-damper distance  
are two important dimensions for fan installation.  
W.O.  
W.O.  
Figure 1 - Wall Housing Installation  
Figure 2 - Wall Collar Installation  
Wall  
Filter  
Housing  
Section  
INTERIOR  
EXTERIOR  
Optional 90º  
Weatherhood  
Filters  
Filters  
Airflow  
A
W.O.  
M
24 in.  
15 in.  
Optional  
Damper  
C
B
Figure 3 - Direct to Wall Installation  
Figure 4 - Filtered Supply Wall Housing Installation  
Recommended Wall Opening (W.O.)  
Damper  
Filtered Supply Wall Housing Only  
Square  
Fan  
Size  
M
Size  
Square  
Minimum  
Figures 1  
and 2  
Figure 3  
Figure 4  
A
B
C
Filter Quantity & Size  
8
10 (254) 141 (362)  
10½ (267)  
12½ (318)  
14½ (368)  
16½ (419)  
18½ (470)  
20½ (521)  
22½ (572)  
26½ (673)  
-
-
-
-
-
-
-
6 (152)  
6 (152)  
7 (178)  
8 (203)  
9 (229)  
10 (254)  
12 (305)  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10 12 (305) 161 (413)  
12 14 (356) 191 (489)  
14 16 (406) 211 (540)  
16 18 (457) 231 (591)  
18 20 (508) 251 (641)  
20 22 (559) 271 (692)  
24 26 (660) 333 (857)  
3334 (857) 13 (330) 3214 (819)  
63 (1600)  
65 (1651)  
24 (610)  
26 (660)  
4
4
6
6
12  
2314 x 1614 (591 x 413)  
2458 x 1914 (625 x 489)  
2314 x 2218 (591 x 562)  
2418 x 2518 (613 x 638)  
2314 x 1834 (591 x 476)  
2314 x 2034 (591 x 527)  
-
30 32 (813) 393 (1010) 32½ (826) 3934 (1010) 13 (330) 3814 (972)  
36 38 (965) 453 (1162) 38½ (978) 4534 (1162) 14 (356) 4414 (1124) 6714 (1708) 281 (718)  
42 44 (1118) 513 (1314) 44½ (1130) 5134 (1314) 15 (381) 5018 (1273) 7278 (1851)  
48 50 (1270) 573 (1467) 50½ (1283) 5734 (1467) 16 (406) 5618 (1426) 7278 (1851)  
34 (864)  
34 (864)  
54 56 (1422) 633 (1619) 56½ (1435) 6334 (1619) 17 (432) 6238 (1584) 791116 (2024) 401116 (1033) 12  
60 62 (1575) 693 (1772) 62½ (1588)  
72 74 (1880) 843 (2153) 74½ (1892)  
-
-
19 (483)  
19 (483)  
-
-
-
-
-
-
-
All dimensions given in inches (millimeters). Filters are 2 inch (51 mm) nominal thickness. Above filter sizes are actual dimensions.  
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
3
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Choose method of support. Attach support to end  
of unit (above or below housing) with rods, cable,  
angle, etc. (supplied by others) as shown.  
Vertical braces must carry a minimum load of 500  
pounds per support, and angled (45°) braces a  
minimum of 750 pounds per support based on two  
supports.  
WARNING  
Always disconnect, lock and tag power source before  
installing or servicing. Failure to disconnect power  
source can result in fire, shock or serious injury.  
Typical Installation  
Move fan to the desired location and determine the  
method by which the fan is to be mounted as shown  
in Figures 1-4 shown on page 3. Optional wall mount  
housings (Figure 1) and wall mount collars (Figure  
2) provide a convenient means of mounting sidewall  
propeller fans while maintaining the proper distance  
between propeller and damper.  
Step 3 Install Weatherhood  
Optional 90º  
Weatherhood  
Attach the fan by inserting a suitable fastener  
through each of the prepunched mounting holes in  
the fan panel. Care should be taken not to bend or  
distort the fan panel or drive components during  
installation.  
Support Braces  
Wall Housing sizes 42 and larger with heavy motors  
and all Filtered Supply Wall Housings need additional  
bracing.  
Position weatherhood over end of wall housing  
and fasten through mounting holes with self-  
tapping screws. Caulk, flash and complete  
electrical hook-up to finish installation.  
Filtered Supply Wall Housing Installation  
Step 1 Install Housing  
Pre-Starting Checks  
Check all fasteners and setscrews for tightness. This  
is especially important for bearing setscrews.  
INTERIOR  
EXTERIOR  
The propeller should rotate freely and not rub on the  
fan panel venturi. Rotation direction of the propeller  
should be checked by momentarily turning the unit  
on. Propeller blade should cup and throw the air  
when rotating in the correct rotation as shown in  
the figure below. Rotation should be in the same  
direction as the rotation decal affixed to the unit.  
Airflow  
Mounting  
Angles  
Temporary  
Brace  
Install housing through wall opening from outside.  
Temporarily brace end of unit until permanent  
support braces are installed.  
Secure through prepunched holes in angles with  
suitable fasteners.  
Step 2 Install Support Braces  
500 lb. load  
per support  
750 lb. load  
per support  
45º  
For 3-phase installations, fan rotation can be  
reversed by simply interchanging any two of the  
three electrical leads. For single-phase installations  
follow the wiring diagram located on the motor.  
For Belt Drive Fans: The adjustable motor pulley is  
preset at the factory for the specified fan RPM. Fan  
speed can be increased by closing or decreased by  
opening the adjustable pulley. Two or three groove  
variable pitch pulleys must be adjusted an equal  
45º  
750 lb. load  
500 lb. load  
per support  
per support  
4
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
number of turns open. Any increase in fan speed  
represents a substantial increase in horsepower  
required from the motor. Always check motor load  
amperage and compare to nameplate rating when  
changing fan speed.  
Bearings (For belt drive fans only)  
Bearings are the most critical moving part of the  
fan and should be inspected at periodic intervals.  
Locking collars and setscrews, in addition to  
fasteners attaching the bearings to the bearing  
plate, must be checked for tightness. In a clean  
environment and temperatures above 32ºF (0ºC)  
and below 200ºF (93ºC), fan shaft bearings with  
grease fittings should be lubricated semi-annually  
using a high-quality lithium based grease. If unusual  
environmental conditions exist, temperatures below  
32ºF (0ºC) and above 200ºF (93ºC), moisture or  
contaminants, more frequent lubrication is required.  
Routine Maintenance  
Once the fan has been put into operation, a periodic  
maintenance program should be set up to preserve  
the reliability and performance of the fan. Items to  
be included in this program are: Belts, Bearings,  
Fasteners and Setscrews, Lubrication, and Removal  
of Dust and Dirt.  
WARNING  
With the unit running, add grease very slowly with  
a manual grease gun until a slight bead of grease  
forms at the seal. Be careful not to unseat the seal  
by over lubricating or using excessive pressure.  
Bearings without grease fittings are lubricated for  
life.  
Always disconnect, lock and tag power source before  
installing or servicing. Failure to disconnect power  
source can result in fire, shock or serious injury.  
Belts  
Fasteners and Setscrews  
Any fan vibration has a tendency to loosen  
Premature belt failures are frequently caused by  
improper belt tension (either too tight or too loose) or  
misaligned pulleys. The proper tension for operating  
a V-belt is the lowest tension at which the belts will  
not slip at peak load conditions. For initial tensioning,  
the proper belt deflection halfway between pulley  
centers is 1/64 inch (0.4 mm) for each inch of belt  
span. For example, if the belt span is 64 inches  
(1626 mm), the belt deflection should be one inch  
(25 mm) using moderate thumb pressure at midpoint  
of the drive. See figure shown below.  
mechanical fasteners. A periodic inspection should  
include checking all fasteners and setscrews for  
tightness. Particular attention should be paid to  
setscrews or taper-lock bushings attaching the  
propeller to the motor shaft and the motor shaft to  
the bearings. Loose bearing setscrews will lead to  
premature failure of the fan shaft. In addition, check  
all fasteners attaching the motor to the motor plate.  
Lubrication  
Refer to the paragraph on bearings for bearing  
lubrication. Many fractional horsepower motors  
installed on the smaller fans are lubricated for life  
and require no further attention. Motors equipped  
with oil holes should be oiled in accordance with the  
manufacturer’s instructions printed on the motor.  
Use a high grade SAE 20 machine oil and use caution  
not to over lubricate. Motors supplied with grease  
fittings should be greased according to directions  
printed on the motor.  
Slack  
Side  
Check belt tension two times during the first 24  
hours of operation and periodically thereafter. To  
adjust belt tension, simply loosen four fasteners  
(two on each side of the motor plate) and slide the  
motor plate away from the fan shaft until proper  
belt tension is attained. On some fans, fasteners  
attaching the motor to the motor plate must be  
loosened in order to adjust the belt.  
Removal of Dust and Dirt  
Dirt clogs cooling openings on the motor housing,  
contaminates bearing lubricant and collects on  
propeller blades causing severe imbalance if left  
unchecked. The exterior surface of the motor, fan  
panel and entire propeller should be thoroughly  
cleaned periodically. Use caution and do not allow  
water or solvents to enter the motor or bearings.  
Motors or bearings must not be sprayed with steam  
or water.  
It is very important  
that the drive pulleys  
remain in proper  
alignment after  
adjustments are  
The filters also require periodic cleaning. The 2 inch  
(51 mm) washable aluminum filters are accessed  
through the bolted access panel.  
made. Misalignment  
of pulleys will result  
in premature belt  
wear noise, vibration  
and power loss.  
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
®
Troubleshooting  
WARNING: Before taking any corrective action, make certain unit is not capable of operation during repairs.  
PROBLEM  
CAUSE  
CORRECTIVE ACTION  
Resistance lower than designed Decrease fan speed.  
Too Much Airflow  
Check backdraft dampers for proper operation. Remove  
obstructions in ductwork. Clean dirty filters. Check for adequate  
supply air for exhaust fans or exhaust air for supply fans.  
System resistance too high  
Fan too close to damper  
Fan speed too low  
Increase distance between fan and damper.  
Increase fan speed.  
Reduced Airflow  
Excessive dirt buildup on  
propeller  
Clean propeller.  
Tighten collars and fasteners. Lubricate bearings. Replace  
defective bearings.  
Bearings  
Tighten pulleys on motor and fan shaft. Adjust belt tension. Align  
pulleys properly. Replace worn belts or pulleys. See Maintenance.  
V-Belt drive  
Clean dirt buildup from propeller. Check all setscrews and  
fasteners for tightness. Check for worn bearing. Correct propeller  
imbalance. Check for loose dampers, guards or ductwork.  
Excessive vibration  
Defective motor  
Excessive Noise  
Replace motor.  
Check VFD for drive setting, some controllers are able to be adjust  
Variable Frequency Drive (VFD) to lower the harmonic noises sometimes heard during operation by  
adjusting a simple setting on the controller.  
Debris  
Remove all debris from the fan.  
Check fuses/circuit breakers. Check for switches turned off or  
disconnected. Check for correct supply voltage.  
Electrical Supply  
Drive  
Fan Does Not  
Operate  
Check for broken or worn belts. Tighten loose pulleys.  
Assure motor is correct horsepower and not tripping overload  
protector.  
Motor  
Maintenance Documentation  
Job Information  
Job Name:___________________________________ Service Organization: _________________________________  
Address: ____________________________________ Address:_____________________________________________  
City: ________________________________________ City:_________________________________________________  
State: _______________ Zip:__________________ State: _______________ Zip:__________________________  
Phone: ______________________________________ Phone: ______________________________________________  
Contact Person:______________________________ Work Done By: _______________________________________  
Nameplate Information  
Field Start-Up Documentation  
Model: ______________________________________  
Volts: ________ Hertz:________ Phase:______ Actual Voltage: _______ Hertz:______ Phase:_________  
Amps:_______________ Mark: ________________ Actual Amperage: ____________________________________  
Supply hp:___________ Exhaust hp: __________ Blower Rotation: _____________________________________  
Serial Number:_______________________________ Air Volume: Design cfm: _____________________________  
Model Voltage:_______________________________  
Actual cfm:______________________________  
Motor Amperage: ____________________________ Level of fan (L or H): __________________________________  
Fan RPM: ___________________________________ Fan RPM Range (min.) ___________ (max.) _____________  
6
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
Parts List  
NOTE  
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information will  
assist the local Greenheck representative and the factory in providing service and replacement parts. Before taking any  
corrective action, make certain unit is not capable of operation during repairs.  
CAUTION  
A fan manufactured with an explosion resistant motor does not certify the entire unit to be explosion proof.  
Parts List - Belt Drive  
SBE-1, SBS-1, SBE-2 and SBS-2 (L and H propellers)  
1. Fan Panel  
2. Propeller  
1
3. Drive Frame Channel (2)  
4. Motor /Bearing Plate  
5. Motor  
2
8
9
6. Motor Pulley  
7. Shaft Pulley  
8. Fan Shaft  
9. Bearings (2)  
10. Belt  
4
10  
Exhaust  
Supply  
Airflow  
Airflow  
3
5
6
7
SBE-3, SBS-3, SBCE, SBCS, and SBCR (L and H propellers)  
3
1. Fan Panel  
2. Propeller  
1
3. Drive Frame Channel (2)  
4. Motor Plate  
5. Motor  
6. Motor Pulley  
7. Shaft Pulley  
8. Fan Shaft  
11  
4
9
8
7
2
10  
6
9. Bearings (2)  
10. Belt  
11. Bearing Plate  
5
Exhaust  
Airflow  
Supply  
Airflow  
Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
®
Parts List - Direct Drive  
SE1 and SS1 (Sizes 8 thru 12 - D, G and E motor speeds)  
1. Fan Panel  
2. Propeller  
3. Drive Frame/Motor Support  
4. Motor  
6
2
5. Riser Blocks (4) - supply fan only  
6. Shaft Extension- supply fan only  
4
Exhaust  
Supply  
Airflow  
Airflow  
1
3
5
SE1 and SS1 (Sizes 12 thru 24 - A, B and C motor speeds)  
SE2 and SS2  
SCE3, SCS3 and SCR3  
1. Fan Panel  
2. Propeller  
1
2
3. Drive Frame Channels (2)  
4. Motor Plate  
5. Motor  
Exhaust  
Supply  
Airflow  
Airflow  
3
4
5
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year  
from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at  
our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer  
for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should  
be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or  
installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications  
without notice.  
Greenheck Catalog Sidewall Propeller Fans provides additional  
information describing the equipment, fan performance,  
available accessories, and specification data.  
AMCA Publication 410-96, Safety Practices for  
Users and Installers of Industrial and Commercial  
Fans, provides additional safety information. This  
publication can be obtained from AMCA International,  
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected]Website: www.greenheck.com  
471755 • Sidewall Propeller Fans IOM • Rev. 2, October 2008 Copyright 2008 © Greenheck Fan Corp  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Marine Sanitation System 295616 User Manual
Greenway Home Products Indoor Fireplace MEF2822CWG User Manual
Grizzly Automobile Parts H8092 User Manual
Haier Handheld TV LCD258 User Manual
Hamilton Beach Rice Cooker 840106800 User Manual
Honeywell Heating System 96 6127 2 User Manual
Hotpoint Refrigerator CTX18GICAA User Manual
HP Hewlett Packard Power Supply 6472C User Manual
Husqvarna Snow Blower 1130SB XLSB User Manual
Ice O Matic Ice Maker FD550 User Manual