Part # 461006
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
MODEL PVF
INDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITS
Installation, Operation and Maintenance Manual
R
Refer to Part Number 460945 for any unit information other than that pertaining to the Indirect Fired Furnace.
WARNING!!!
Improper installation, adjustment, alteration, service or maintenance can cause injury or death.
Read the installation, operating and maintenance instructions thoroughly before installing or
servicing this equipment.
CAUTION!!!
Units are designed for outdoor installation only. DO NOT locate units indoors.
Indirect Fired Gas Unit Installations
Units are listed for installation in the United States and Canada
• Installation of gas fired duct furnaces must conform with local building codes. In the absence of local
codes, installation must conform to the National Fuel Gas code, ANSI Z223.1 or in Canada,
CAN/CGA-B149 installation codes.
• All electrical wiring must be in accordance with the regulation of the National Electric Code,
ANSI/NFPA No. 70.
• Unit is approved for installation downstream from refrigeration units. In these conditions, condensate
could form in the duct furnace and provision must be made to dispose of the condensate.
Shipping
Check the unit for shipping damage. If any shipping damage is found, it should be reported to the last carrier
and your local Greenheck representative.
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Connections
WARNING!!!
•
•
•
Disconnect power supply before making wiring connections to prevent electrical shock and
equipment damage.
All appliances must be wired strictly in accordance with wiring diagram furnished with the unit. Any
wiring different from the diagram could result in a hazard to persons and property.
Any original factory wiring that requires replacement must be replaced with wiring material having a
temperature rating of at least 105°C.
1. Installation of wiring must conform with local building codes. In the absence of local codes, installation
must conform to the National Electric Code ANSI/NFPA 70-Latest Edition. Unit must be electrically
grounded in conformance with this code. In Canada, wiring must comply with CSA C22.1, Canadian
Electrical Code.
2. All furnaces are provided with a wiring diagram located on the inside of the access panel. Refer to this
wiring diagram for all wiring connections.
3. The combustion blower motor will not run unless the furnace is turned on and the gas controls are calling
for heat.
Control Center Layout
1. Two-stage temperature controls - Controls the
9
1
furnace stages based on the unit discharge
temperature.
2. Combustion blower - Exhausts the products of
combustion from the furnace tubes.
3. Ignition controller - Continually monitors,
analyzes, and controls the proper operation of
the gas burner.
2
3
4. Manifold pressure test port - Used for checking
the manifold gas pressure.
5. Time Delay relay - Allows burner to stay at high
fire for 10 seconds upon being lit.
4
6. Air pressure switch - Tests to ensure the
combustion blower is operating.
7. Two-stage gas valve - Contains main pressure
regulator, safety shut-off valves, and manual
shut off knob. It controls the furnace to 50% or
100% fire.
5
6
8. Ignitor - Provides spark for burner ignition.
9. Flame Sensor - Ensures that each burner has
7
ignited.
8
Figure 2: Furnace Control Center
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up Procedure
1. Turn off power to the unit at the disconnect switch.
Close all manual gas valves.
2. Check that all gas and electrical connections are
weatherized.
3. Make sure that the combustion air inlet and the
combustion blower discharge are free from
obstructions.
4. Inspect the unit to make sure that no damage has
occurred during installation.
5. With the furnace control center access panel
removed, connect a “U” tube manometer to the
manifold pressure test port as shown in Figure 2.
This will be used for checking the manifold gas
pressure.
7. Open all manual gas valves including the
combination gas valve and turn power on.
8. Call for heat with the thermostat or discharge
temperature controls and allow the burner to light.
Greenheck duct furnaces are equipped with an
automatic spark ignition system which
automatically lights the burner. DO NOT attempt to
light the burners manually.
9. After the burner is lit, check to make sure that the
supply blower is operating.
10.Verify that the gas controls sequence properly (see
Sequence of Operation below).
11.Check the manifold gas pressure (see Burner
Adjustments on pages 5 and 6).
6. Set the thermostat or discharge temperature
controls to lowest setting.
Sequence of Operation
Power-up/Standby
5a. Two-stage control: The burner will light at 100%
fire and remain there for 10 seconds. The
After power is supplied to the unit:
thermostat will then operate the burners at high or
low fire, depending on the demand for heat.
1. The ignition control will reset and perform a self-
check routine.
5b. Electronic Modulation - The burner will light at
100% fire and remain there for 10 seconds. The
main burner gas valve will then modulate from
100% down to 50% as needed. If the burner
remains on low fire for an extended period of time,
the burner will shut off and re-light as necessary.
2. The diagnostic LED will flash for up to four
seconds.
3. The ignition control will begin scanning the
thermostats.
6. The ignition control constantly monitors the
thermostat, pressure switch, and burner flame to
assure proper operation.
Heat Mode
When the thermostat or discharge temperature
controls call for heat:
7. When the thermostat or discharge temperature
controls are satisfied, the main valve is de-
energized and the combustion blower shuts off
following a 30-second post-purge period.
1. The ignition control will check that the pressure
switch for the combustion blower is open.
2. The combustion blower will be energized and the
15-second pre-purge begins.
3. The gas valve is energized and the igniter will spark
for up to 10 seconds.
Recovery from Lockout
The ignition control will automatically reset after 1 hour
if the thermostat is still calling for heat. Prior to 1 hour,
a manual reset (cycle power to unit) is required. The
thermostat may be reset or the power interrupted for a
period of 5 seconds. See page 7 for Ignition Control
Diagnostics.
Natural Gas - If a flame is not sensed during the
trial for ignition, two additional trials will be
attempted before going into lockout for one hour.
LP Gas - If a flame is not sensed during the trial for
ignition, the control will go into lockout for one
hour.
4. When a flame is sensed, sparking stops
immediately. The gas valve and combustion blower
remain energized.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Air Temperature Rise Through Unit (°F)
Model
Input Output 20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100
Number (MBH) (MBH)
CFM
PVF 100
PVF 150
PVF 200
PVF 250
PVF 300
PVF 350
PVF 400
100
150
200
250
300
350
400
80
3704 2963 2469 2116 1852 1646 1481 1347 1235 1140 1058 988 926 871 823 780 741
120 5556 4444 3704 3175 2778 2469 2222 2020 1852 1709 1587 1481 1389 1307 1235 1170 1111
160 7407 5926 4938 4233 3704 3292 2963 2694 2469 2279 2116 1975 1852 1743 1646 1559 1481
200 9259 7407 6173 5291 4630 4115 3704 3367 3086 2849 2646 2469 2315 2179 2058 1949 1852
240 11111 8889 7407 6349 5556 4938 4444 4040 3704 3419 3175 2963 2778 2614 2469 2339 2222
280 12963 10370 8642 7407 6481 5761 5185 4714 4321 3989 3704 3457 3241 3050 2881 2729 2593
320 14815 11852 9877 8466 7407 6584 5926 5387 4938 4558 4233 3951 3704 3486 3292 3119 2963
Ratings shown are for elevations up to 2000 ft. For higher elevations, the input should be reduced by 4% per 1000 ft. of
elevation above sea level. In Canada, from 2000 to 4500 ft in elevation, the unit must be derated to 90% of the input listed
above. The unit shall also be used in accordance with standard CGA 2.17.
Furnace Controls
Staged Temperature Controls
For Energy Recovery Units without Temperature Control Package
The furnace stage controls are located in the furnace control center. One control is
provided for each stage of heating. The discharge temperature setting is located on
the control furthest to the left. The offset and differential settings for each stage are
preset at the factory; however, field-adjustments may be made to get the best control
for your application. See the literature provided with the controls for further
information.
For Energy Recovery Units with Temperature Control Package
If two-stage control is ordered with a Temperature Control Package, the controller in
the unit’s main control center will control the stages of heating. The temperature set
point may be adjusted on the controller (See Temperature Controller IOM).
Figure 3: Staged Controls
Staged Burner Adjustments
Setting Manifold Pressure for Two Stage Gas Control
1. Set the unit to high fire by setting the
Solenoid
discharge temperature control or
High Fire Adjustment
thermostat to its maximum setting. If the
Low Fire Adjustment
ambient temperature is warm, the unit
may not stay at high fire.
High Fire
Terminal
2. Measure the burner manifold pressure at
the manifold pressure test port (see
Control Center Layout on page 3) using a
“U” tube manometer. The pressure on
high fire should be 3.5 in. wg for natural
gas and 10 in. wg for LP gas. To change
the pressure, adjust the regulator
adjustment screw on the combination gas
valve.
3. Set the unit to low fire by removing the
wire from the high fire terminal on the
combination gas valve.
4. The manifold pressure on low fire for natural gas
should be 0.88 in. wg and 2.5 in. wg for LP gas. To
change the pressure, use the low fire adjustment
screw on the combination gas valve.
Figure 4: Combination Gas Valve
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Electronic Modulation Temperature Controls
For Energy Recovery Units without Temperature
Control Package
For Energy Recovery Units with Temperature Control
Package
A Discharge Temperature Dial is used for temperature
The Temperature Controller in the unit’s main control
control for electronic modulation. The temperature dial center will provide the electronic modulation control.
will be located in the furnace control center.
High and Low Fire Settings for Electronic Modulation
Check the high and low gas pressures on initial start up per the instructions below. These settings are pre-set at
the factory, but should be adjusted in the field if necessary. Set the high fire first and the low fire second. The low
fire must always be checked if the high fire is changed.
Modulating Valve
Low fire adjustment
B
Combination Gas Valve
High fire adjustment
Figure 5: Electronic Modulation Valves
A
1. Set the unit to high fire by placing a jumper between terminals 7 and 8 on the Maxitrol amplifier.
2. Measure the burner manifold pressure at each furnace at the pressure test port (see Figure 2) using a high
quality manometer that can measure low gas pressures. The pressure at high fire should be 3.5 in. wg for
natural gas and 10.0 in. wg for LP Gas. To change the pressure, adjust the high fire screw on the combination
gas valve.
3. To get the unit to low fire: Remove the wire from terminal 3 on the amplifier and isolate it from touching
anything. Set the discharge temperature selector to the highest setting. If there is a room override thermostat,
turn the dial to the highest setting.
4. Measure the manifold pressure on low fire, it should be 0.88 in. wg for natural gas and 2.5 in. wg for LP gas.
5. To adjust the low fire, remove the bypass cap (A) and turn screw (B) as shown in diagram. Adjust the screw
indicated in Figure 5 on the modulating valve.
6. Reconnect wire to terminal 3.
7. Remove jumper and place all wires back to where they were and plug the manifold pressure port.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Ignition Control Diagnostic LED
During normal operation, the LED is shut off. The LED
will be on or flashing during a fault condition. If a fault
condition is occurring, turn the unit off and on again. If
the LED is still flashing, refer to the following
troubleshooting section.
LED Indication
Steady on
1 flash
2 flashes
3 flashes
Error Mode
Internal control failure
Air flow fault
Flame with no call for heat
Ignition lockout
Airflow Fault (1 Flash)
An airflow fault may occur for the following reasons:
• An airflow switch continually monitors the combustion airflow during an ignition sequence. During the initial
call for heat, if the pressure switch contacts are in the closed position for 30 seconds without an output to
the combustion blower, an airflow fault will be declared. The control will remain in this mode with the
combustion blower off.
• After the combustion blower output (L1 and IND) is energized and the airflow switch remains open for more
than 30 seconds, an airflow fault will be declared. The control will stay in this mode with the combustion
blower on, waiting for the airflow switch to close.
• If the airflow signal is lost while the burner is firing, the control will immediately de-energize the gas valve
and the combustion blower will remain on. If the call for heat remains, the control will wait for proper airflow
to return. If proper airflow is not detected after 30 seconds, an airflow fault will be declared. If proper airflow
is detected at any time, a normal ignition sequence will begin.
Once proper airflow is detected, the normal Sequence Of Operation for ignition will follow (see page 4).
Flame Fault (2 Flashes)
If the main valve fails to close completely and maintains a flame, the full-time flame sense circuit will detect it and
energize the combustion blower. Should the main valve later close completely and remove the flame signal, the
combustion blower will be de-energized.
Ignition Lockout (3 Flashes)
Possible Cause
Manual gas valve not open
Solution
Open manual valve
Air in the gas line
Bleed gas line
Supply gas pressure too high or too low Check that supply pressure is between 6 in. wg and 14 in. wg for
natural gas and 11 in. wg and 14 in. wg for LP.
Loose wire connections
No spark:
Check for tight wire connections.
a. Transformer failure
a. Check primary and secondary voltages of transformer. Replace
if necessary.
1
b. Spark electrode
b. Ensure spark gap is ⁄8 in. and ceramic insulator is not cracked.
Replace if necessary. Electrode is NOT field-adjustable.
c. Spark cable shorted to ground
d. Ignition controller not grounded
c. Replace spark cable
d. Check that the ignition controller is grounded to the furnace
control center.
High limit control tripped
Check unit airflow and manifold pressure.
Faulty combination gas valve
If 24 volts is measured between terminals MV and common, but
valve remains closed, replace valve.
Faulty ignition control
Check diagnostic LED for steady on and for voltage between V1
and V2. If no voltage is present, replace ignition control.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Routine Maintenance
CAUTION!!!
Turn off all gas and electrical power to the unit before performing any maintenance or
service operations to this unit.
• Before reinstalling the burner assembly, look
Combustion Blower Motor
down the heat exchanger tubes to make sure
they are clear of any debris.
Motor maintenance is generally limited to cleaning.
Cleaning should be limited to exterior surfaces only.
Removing dust and grease build-up on the motor
housing assures proper motor cooling. Use caution
and do not allow water or solvents to enter the motor
or bearings. Under no circumstances should motors or
bearings be sprayed with steam, water or solvents.
The motor bearings are pre-lubricated and sealed,
requiring no further lubrication.
• Reinstall manifold and burner assembly,
reconnect wire leads, and gas supply piping.
• Turn on the electrical power and gas supply.
• Follow the start-up procedure to light the
burners and verify proper operation.
Heat Exchanger
The heat exchanger should be checked annually for
cracks and discoloration of the tubes. If a crack is
detected, the heat exchanger should be replaced
before the unit is put back into operation. If the tubes
are dark gray, airflow across the heat exchanger
should be checked to make sure the blower is
operating properly.
Burners and Orifices
Before each heating season, examine the burners and
gas orifices to make sure they are clear of any debris
such as spider webs, etc. Clean burner as follows:
• Turn off both electrical and gas supplies to the
unit.
• Disconnect union between manifold and gas
valve.
Flue Collector Box
The flue passageway and flue collector box should be
inspected prior to each heating season and cleared of
any debris.
• Remove manifold and burner assembly.
• Inspect and clean orifices and burners as
necessary. Avoid using any hard or sharp
instruments which could cause damage to the
orifices or burners.
Electrical Wiring
The electrical wiring should be checked annually for
loose connections or wiring deterioration.
- Remove any soot deposits from the burner
with a wire brush.
Replacement Parts
- Clean the ports with an aerosol degreaser
or compressed air.
- Wipe the inside of the burner clean.
Cleaning the burner with a degreaser will
slow the future buildup of dirt.
When ordering replacement parts, include the
complete unit model number and serial number listed
on the unit rating plate.
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which prove to be defective during the warranty period will
be repaired or replaced at our option.
The motor is warranted by the motor manufacturer for a period of one year. Should the motor prove
defective during this period, it should be returned to an authorized motor service station.
Greenheck will not be responsible for any installation or removal costs.
ERCH - PVF IOM FS