Greenheck Fan Furnace PVF User Manual

Part # 461006  
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE  
MODEL PVF  
INDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITS  
Installation, Operation and Maintenance Manual  
R
Refer to Part Number 460945 for any unit information other than that pertaining to the Indirect Fired Furnace.  
WARNING!!!  
Improper installation, adjustment, alteration, service or maintenance can cause injury or death.  
Read the installation, operating and maintenance instructions thoroughly before installing or  
servicing this equipment.  
CAUTION!!!  
Units are designed for outdoor installation only. DO NOT locate units indoors.  
Indirect Fired Gas Unit Installations  
Units are listed for installation in the United States and Canada  
• Installation of gas fired duct furnaces must conform with local building codes. In the absence of local  
codes, installation must conform to the National Fuel Gas code, ANSI Z223.1 or in Canada,  
CAN/CGA-B149 installation codes.  
• All electrical wiring must be in accordance with the regulation of the National Electric Code,  
ANSI/NFPA No. 70.  
• Unit is approved for installation downstream from refrigeration units. In these conditions, condensate  
could form in the duct furnace and provision must be made to dispose of the condensate.  
Shipping  
Check the unit for shipping damage. If any shipping damage is found, it should be reported to the last carrier  
and your local Greenheck representative.  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Connections  
WARNING!!!  
Disconnect power supply before making wiring connections to prevent electrical shock and  
equipment damage.  
All appliances must be wired strictly in accordance with wiring diagram furnished with the unit. Any  
wiring different from the diagram could result in a hazard to persons and property.  
Any original factory wiring that requires replacement must be replaced with wiring material having a  
temperature rating of at least 105°C.  
1. Installation of wiring must conform with local building codes. In the absence of local codes, installation  
must conform to the National Electric Code ANSI/NFPA 70-Latest Edition. Unit must be electrically  
grounded in conformance with this code. In Canada, wiring must comply with CSA C22.1, Canadian  
Electrical Code.  
2. All furnaces are provided with a wiring diagram located on the inside of the access panel. Refer to this  
wiring diagram for all wiring connections.  
3. The combustion blower motor will not run unless the furnace is turned on and the gas controls are calling  
for heat.  
Control Center Layout  
1. Two-stage temperature controls - Controls the  
9
1
furnace stages based on the unit discharge  
temperature.  
2. Combustion blower - Exhausts the products of  
combustion from the furnace tubes.  
3. Ignition controller - Continually monitors,  
analyzes, and controls the proper operation of  
the gas burner.  
2
3
4. Manifold pressure test port - Used for checking  
the manifold gas pressure.  
5. Time Delay relay - Allows burner to stay at high  
fire for 10 seconds upon being lit.  
4
6. Air pressure switch - Tests to ensure the  
combustion blower is operating.  
7. Two-stage gas valve - Contains main pressure  
regulator, safety shut-off valves, and manual  
shut off knob. It controls the furnace to 50% or  
100% fire.  
5
6
8. Ignitor - Provides spark for burner ignition.  
9. Flame Sensor - Ensures that each burner has  
7
ignited.  
8
Figure 2: Furnace Control Center  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up Procedure  
1. Turn off power to the unit at the disconnect switch.  
Close all manual gas valves.  
2. Check that all gas and electrical connections are  
weatherized.  
3. Make sure that the combustion air inlet and the  
combustion blower discharge are free from  
obstructions.  
4. Inspect the unit to make sure that no damage has  
occurred during installation.  
5. With the furnace control center access panel  
removed, connect a “U” tube manometer to the  
manifold pressure test port as shown in Figure 2.  
This will be used for checking the manifold gas  
pressure.  
7. Open all manual gas valves including the  
combination gas valve and turn power on.  
8. Call for heat with the thermostat or discharge  
temperature controls and allow the burner to light.  
Greenheck duct furnaces are equipped with an  
automatic spark ignition system which  
automatically lights the burner. DO NOT attempt to  
light the burners manually.  
9. After the burner is lit, check to make sure that the  
supply blower is operating.  
10.Verify that the gas controls sequence properly (see  
Sequence of Operation below).  
11.Check the manifold gas pressure (see Burner  
Adjustments on pages 5 and 6).  
6. Set the thermostat or discharge temperature  
controls to lowest setting.  
Sequence of Operation  
Power-up/Standby  
5a. Two-stage control: The burner will light at 100%  
fire and remain there for 10 seconds. The  
After power is supplied to the unit:  
thermostat will then operate the burners at high or  
low fire, depending on the demand for heat.  
1. The ignition control will reset and perform a self-  
check routine.  
5b. Electronic Modulation - The burner will light at  
100% fire and remain there for 10 seconds. The  
main burner gas valve will then modulate from  
100% down to 50% as needed. If the burner  
remains on low fire for an extended period of time,  
the burner will shut off and re-light as necessary.  
2. The diagnostic LED will flash for up to four  
seconds.  
3. The ignition control will begin scanning the  
thermostats.  
6. The ignition control constantly monitors the  
thermostat, pressure switch, and burner flame to  
assure proper operation.  
Heat Mode  
When the thermostat or discharge temperature  
controls call for heat:  
7. When the thermostat or discharge temperature  
controls are satisfied, the main valve is de-  
energized and the combustion blower shuts off  
following a 30-second post-purge period.  
1. The ignition control will check that the pressure  
switch for the combustion blower is open.  
2. The combustion blower will be energized and the  
15-second pre-purge begins.  
3. The gas valve is energized and the igniter will spark  
for up to 10 seconds.  
Recovery from Lockout  
The ignition control will automatically reset after 1 hour  
if the thermostat is still calling for heat. Prior to 1 hour,  
a manual reset (cycle power to unit) is required. The  
thermostat may be reset or the power interrupted for a  
period of 5 seconds. See page 7 for Ignition Control  
Diagnostics.  
Natural Gas - If a flame is not sensed during the  
trial for ignition, two additional trials will be  
attempted before going into lockout for one hour.  
LP Gas - If a flame is not sensed during the trial for  
ignition, the control will go into lockout for one  
hour.  
4. When a flame is sensed, sparking stops  
immediately. The gas valve and combustion blower  
remain energized.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data  
Air Temperature Rise Through Unit (°F)  
Model  
Input Output 20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95 100  
Number (MBH) (MBH)  
CFM  
PVF 100  
PVF 150  
PVF 200  
PVF 250  
PVF 300  
PVF 350  
PVF 400  
100  
150  
200  
250  
300  
350  
400  
80  
3704 2963 2469 2116 1852 1646 1481 1347 1235 1140 1058 988 926 871 823 780 741  
120 5556 4444 3704 3175 2778 2469 2222 2020 1852 1709 1587 1481 1389 1307 1235 1170 1111  
160 7407 5926 4938 4233 3704 3292 2963 2694 2469 2279 2116 1975 1852 1743 1646 1559 1481  
200 9259 7407 6173 5291 4630 4115 3704 3367 3086 2849 2646 2469 2315 2179 2058 1949 1852  
240 11111 8889 7407 6349 5556 4938 4444 4040 3704 3419 3175 2963 2778 2614 2469 2339 2222  
280 12963 10370 8642 7407 6481 5761 5185 4714 4321 3989 3704 3457 3241 3050 2881 2729 2593  
320 14815 11852 9877 8466 7407 6584 5926 5387 4938 4558 4233 3951 3704 3486 3292 3119 2963  
Ratings shown are for elevations up to 2000 ft. For higher elevations, the input should be reduced by 4% per 1000 ft. of  
elevation above sea level. In Canada, from 2000 to 4500 ft in elevation, the unit must be derated to 90% of the input listed  
above. The unit shall also be used in accordance with standard CGA 2.17.  
Furnace Controls  
Staged Temperature Controls  
For Energy Recovery Units without Temperature Control Package  
The furnace stage controls are located in the furnace control center. One control is  
provided for each stage of heating. The discharge temperature setting is located on  
the control furthest to the left. The offset and differential settings for each stage are  
preset at the factory; however, field-adjustments may be made to get the best control  
for your application. See the literature provided with the controls for further  
information.  
For Energy Recovery Units with Temperature Control Package  
If two-stage control is ordered with a Temperature Control Package, the controller in  
the unit’s main control center will control the stages of heating. The temperature set  
point may be adjusted on the controller (See Temperature Controller IOM).  
Figure 3: Staged Controls  
Staged Burner Adjustments  
Setting Manifold Pressure for Two Stage Gas Control  
1. Set the unit to high fire by setting the  
Solenoid  
discharge temperature control or  
High Fire Adjustment  
thermostat to its maximum setting. If the  
Low Fire Adjustment  
ambient temperature is warm, the unit  
may not stay at high fire.  
High Fire  
Terminal  
2. Measure the burner manifold pressure at  
the manifold pressure test port (see  
Control Center Layout on page 3) using a  
“U” tube manometer. The pressure on  
high fire should be 3.5 in. wg for natural  
gas and 10 in. wg for LP gas. To change  
the pressure, adjust the regulator  
adjustment screw on the combination gas  
valve.  
3. Set the unit to low fire by removing the  
wire from the high fire terminal on the  
combination gas valve.  
4. The manifold pressure on low fire for natural gas  
should be 0.88 in. wg and 2.5 in. wg for LP gas. To  
change the pressure, use the low fire adjustment  
screw on the combination gas valve.  
Figure 4: Combination Gas Valve  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electronic Modulation Temperature Controls  
For Energy Recovery Units without Temperature  
Control Package  
For Energy Recovery Units with Temperature Control  
Package  
A Discharge Temperature Dial is used for temperature  
The Temperature Controller in the unit’s main control  
control for electronic modulation. The temperature dial center will provide the electronic modulation control.  
will be located in the furnace control center.  
High and Low Fire Settings for Electronic Modulation  
Check the high and low gas pressures on initial start up per the instructions below. These settings are pre-set at  
the factory, but should be adjusted in the field if necessary. Set the high fire first and the low fire second. The low  
fire must always be checked if the high fire is changed.  
Modulating Valve  
Low fire adjustment  
B
Combination Gas Valve  
High fire adjustment  
Figure 5: Electronic Modulation Valves  
A
1. Set the unit to high fire by placing a jumper between terminals 7 and 8 on the Maxitrol amplifier.  
2. Measure the burner manifold pressure at each furnace at the pressure test port (see Figure 2) using a high  
quality manometer that can measure low gas pressures. The pressure at high fire should be 3.5 in. wg for  
natural gas and 10.0 in. wg for LP Gas. To change the pressure, adjust the high fire screw on the combination  
gas valve.  
3. To get the unit to low fire: Remove the wire from terminal 3 on the amplifier and isolate it from touching  
anything. Set the discharge temperature selector to the highest setting. If there is a room override thermostat,  
turn the dial to the highest setting.  
4. Measure the manifold pressure on low fire, it should be 0.88 in. wg for natural gas and 2.5 in. wg for LP gas.  
5. To adjust the low fire, remove the bypass cap (A) and turn screw (B) as shown in diagram. Adjust the screw  
indicated in Figure 5 on the modulating valve.  
6. Reconnect wire to terminal 3.  
7. Remove jumper and place all wires back to where they were and plug the manifold pressure port.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Ignition Control Diagnostic LED  
During normal operation, the LED is shut off. The LED  
will be on or flashing during a fault condition. If a fault  
condition is occurring, turn the unit off and on again. If  
the LED is still flashing, refer to the following  
troubleshooting section.  
LED Indication  
Steady on  
1 flash  
2 flashes  
3 flashes  
Error Mode  
Internal control failure  
Air flow fault  
Flame with no call for heat  
Ignition lockout  
Airflow Fault (1 Flash)  
An airflow fault may occur for the following reasons:  
• An airflow switch continually monitors the combustion airflow during an ignition sequence. During the initial  
call for heat, if the pressure switch contacts are in the closed position for 30 seconds without an output to  
the combustion blower, an airflow fault will be declared. The control will remain in this mode with the  
combustion blower off.  
• After the combustion blower output (L1 and IND) is energized and the airflow switch remains open for more  
than 30 seconds, an airflow fault will be declared. The control will stay in this mode with the combustion  
blower on, waiting for the airflow switch to close.  
• If the airflow signal is lost while the burner is firing, the control will immediately de-energize the gas valve  
and the combustion blower will remain on. If the call for heat remains, the control will wait for proper airflow  
to return. If proper airflow is not detected after 30 seconds, an airflow fault will be declared. If proper airflow  
is detected at any time, a normal ignition sequence will begin.  
Once proper airflow is detected, the normal Sequence Of Operation for ignition will follow (see page 4).  
Flame Fault (2 Flashes)  
If the main valve fails to close completely and maintains a flame, the full-time flame sense circuit will detect it and  
energize the combustion blower. Should the main valve later close completely and remove the flame signal, the  
combustion blower will be de-energized.  
Ignition Lockout (3 Flashes)  
Possible Cause  
Manual gas valve not open  
Solution  
Open manual valve  
Air in the gas line  
Bleed gas line  
Supply gas pressure too high or too low Check that supply pressure is between 6 in. wg and 14 in. wg for  
natural gas and 11 in. wg and 14 in. wg for LP.  
Loose wire connections  
No spark:  
Check for tight wire connections.  
a. Transformer failure  
a. Check primary and secondary voltages of transformer. Replace  
if necessary.  
1
b. Spark electrode  
b. Ensure spark gap is 8 in. and ceramic insulator is not cracked.  
Replace if necessary. Electrode is NOT field-adjustable.  
c. Spark cable shorted to ground  
d. Ignition controller not grounded  
c. Replace spark cable  
d. Check that the ignition controller is grounded to the furnace  
control center.  
High limit control tripped  
Check unit airflow and manifold pressure.  
Faulty combination gas valve  
If 24 volts is measured between terminals MV and common, but  
valve remains closed, replace valve.  
Faulty ignition control  
Check diagnostic LED for steady on and for voltage between V1  
and V2. If no voltage is present, replace ignition control.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Routine Maintenance  
CAUTION!!!  
Turn off all gas and electrical power to the unit before performing any maintenance or  
service operations to this unit.  
• Before reinstalling the burner assembly, look  
Combustion Blower Motor  
down the heat exchanger tubes to make sure  
they are clear of any debris.  
Motor maintenance is generally limited to cleaning.  
Cleaning should be limited to exterior surfaces only.  
Removing dust and grease build-up on the motor  
housing assures proper motor cooling. Use caution  
and do not allow water or solvents to enter the motor  
or bearings. Under no circumstances should motors or  
bearings be sprayed with steam, water or solvents.  
The motor bearings are pre-lubricated and sealed,  
requiring no further lubrication.  
• Reinstall manifold and burner assembly,  
reconnect wire leads, and gas supply piping.  
• Turn on the electrical power and gas supply.  
• Follow the start-up procedure to light the  
burners and verify proper operation.  
Heat Exchanger  
The heat exchanger should be checked annually for  
cracks and discoloration of the tubes. If a crack is  
detected, the heat exchanger should be replaced  
before the unit is put back into operation. If the tubes  
are dark gray, airflow across the heat exchanger  
should be checked to make sure the blower is  
operating properly.  
Burners and Orifices  
Before each heating season, examine the burners and  
gas orifices to make sure they are clear of any debris  
such as spider webs, etc. Clean burner as follows:  
• Turn off both electrical and gas supplies to the  
unit.  
• Disconnect union between manifold and gas  
valve.  
Flue Collector Box  
The flue passageway and flue collector box should be  
inspected prior to each heating season and cleared of  
any debris.  
• Remove manifold and burner assembly.  
• Inspect and clean orifices and burners as  
necessary. Avoid using any hard or sharp  
instruments which could cause damage to the  
orifices or burners.  
Electrical Wiring  
The electrical wiring should be checked annually for  
loose connections or wiring deterioration.  
- Remove any soot deposits from the burner  
with a wire brush.  
Replacement Parts  
- Clean the ports with an aerosol degreaser  
or compressed air.  
- Wipe the inside of the burner clean.  
Cleaning the burner with a degreaser will  
slow the future buildup of dirt.  
When ordering replacement parts, include the  
complete unit model number and serial number listed  
on the unit rating plate.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one  
year from the purchase date. Any units or parts which prove to be defective during the warranty period will  
be repaired or replaced at our option.  
The motor is warranted by the motor manufacturer for a period of one year. Should the motor prove  
defective during this period, it should be returned to an authorized motor service station.  
Greenheck will not be responsible for any installation or removal costs.  
ERCH - PVF IOM FS  
Rev1 July 2001  
Copyright © 2001 Greenheck Fan Corp.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Stroller PD108602A User Manual
Harman Kardon Stereo Receiver AVR 700 User Manual
Honeywell Clock PC04 User Manual
Honeywell Clock TE219ELW User Manual
Hotpoint Washer Dryer WMT01 User Manual
HP Hewlett Packard Computer Hardware B110I User Manual
HP Hewlett Packard Personal Computer BrioBA410 User Manual
HP Hewlett Packard Power Supply 6621A User Manual
I Data Personal Computer POLARIS Panel PC 191 User Manual
Iiyama Computer Monitor B1780SD B1 User Manual