GenTran Power Supply R1020 User Manual

POWER CENTER  
For Models R2060, R3060, R5010, R2020, R3020, R5020,  
R6010, R6020, R1020, R1220  
All models are suitable as service entrance equipment.  
INSTALLATION AND OPERATING INSTRUCTIONS  
Warning: Gen/Tran transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working  
with generators. Gen/Tran accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. These transfer switches are  
intended for surface mounting outdoors or indoors.  
Caution: If using the generator and transfer switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges and small air  
conditioners, check the labels on the appliances to be sure they do NOT exceed the rating of the generator. No appliance should have an amperage rating that  
exceeds the “GENERATOR MAIN” rating in the transfer switch.  
Thank you for purchasing the finest manual transfer switch available today. Gen/Tran’s Power Centers are designed to safely connect generators to load centers  
in homes and light commercial buildings (single phase only) for standby power applications. Features include:  
Generator Main and Utility Main mechanically interlocked preventing utility or generator power back feed  
Full branch circuit protection with Siemens® circuit breakers  
Optional GFCI, Arc Fault or Surge Protection circuit breakers to further protect your home and electronic equipment (Available from Gen/Tran)  
High Corrosion-resistant aluminum cabinet  
Items Needed for Installation:  
¼” and 11/32 nut drivers  
Straight blade and Phillips screwdriver  
Large Allen Wrench Set  
Electric drill  
Wire cutter/stripper  
Anchors and screws to mount switch to wall  
Power Cord to connect generator to switch.  
Typical Power Center Installation:  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
For “Hard-wired” Generator Connection: (Models R6010, R6020, R1020, R1220)  
1. Follow steps 1 - 6 as described above.  
2. Installer to determine size of conduit for bringing power from generator to the Power Center. KOs on bottom of Power Center should be  
used, although alternate entry is adequate when necessary. Watertight hubs should be used above live breaker terminals. NOTE: If a 2” KO  
is cut in the side of the Power Center enclosure, the dead front panel may need to be “notched” to clear the 2” fittings. The back of the KO  
must be 3/8” from the rear of the enclosure.  
3. Terminate wires from generator to “Generator Main” circuit breaker lugs on the Right side of the bus assembly. Terminate neutral and  
ground wires into the appropriate bars provided.  
4. Proceed with steps 7, 8 and 9 as described above.  
TABLE 1 - SPECIFICATIONS:  
MODEL #  
R2060  
60 Amp  
20 Amp  
As marked  
20 Amp  
5000  
5000  
16  
8
L14-20  
12/4 wire  
R3060  
60 Amp  
30 Amp  
As marked  
30 Amp  
7500  
7500  
16  
8
L14-30  
10/4 wire  
R5010  
100 Amp  
50 Amp  
As marked  
50 Amp  
12,500  
12,500  
16  
R2020  
200 Amp  
20 Amp  
As marked  
20 Amp  
5000  
5000  
12  
6
L14-20  
12/4 wire  
R3020  
200 Amp  
30 Amp  
As marked  
30 Amp  
7500  
7500  
12  
6
L14-30  
10/4 wire  
R5020  
200 Amp  
50 Amp  
As marked  
50 Amp  
12,500  
12,500  
12  
UTILITY MAIN breaker, Included  
GEN MAIN breaker, included  
Max Load per Circuit  
Max Load on Generator  
Max Watts @ 250 Volt  
Max Watts @ 125 Volt  
Max 1-pole Circuits *  
Max 2-pole Circuits *  
NEMA Config. of Inlet  
Min. gauge Cord Size  
8
6
CS6365  
6/4 wire  
CS6365  
6/4 wire  
TABLE 1A – SPECIFICATIONS:  
MODEL #  
R6010  
R6020  
200 Amp  
60 Amp  
As marked  
60 Amp  
15,000  
15,000  
12  
R1020  
200 Amp  
100 Amp  
As marked  
100 Amp  
25,000  
25,000  
12  
R1220  
UTILITY MAIN breaker, Included  
GEN MAIN breaker, included  
Max Load per Circuit  
Max Load on Generator  
Max Watts @ 250 Volt  
Max Watts @ 125 Volt  
Max 1-pole Circuits *  
Max 2-pole Circuits *  
NEMA Config. of Inlet  
Min. gauge Cord Size  
100 Amp  
60 Amp  
As marked  
60 Amp  
15,000  
15,000  
16  
200 Amp  
125 Amp  
As marked  
125 Amp  
30,000  
30,000  
12  
6
N/A  
Hardwired  
8
N/A  
6
N/A  
Hardwired  
6
N/A  
Hardwired  
Hardwired  
NOTE: if Ground Fault Circuit Interrupting (GFCI) breakers, Arc-Fault breaker or surge protecting circuit breakers are used in the Power Center,  
they will reduce the maximum number of circuits from the number shown in the table above. Also if circuit breakers larger than 50 amps are used  
as sub-feed breakers, the maximum number of circuit breakers will also be reduced. Contact Gen/Tran at 1-888-GEN-TRAN for more information  
on GFCI, Arc-Fault and Surge Protecting circuit breakers.  
Operating Your Power Center Transfer Switch:  
Transferring from Utility Power to Generator Power:  
1. Move generator outdoors. WARNING: Operating a generator indoors or in a garage could result in injury or death.  
2. Insert the male plug of the Power Cord into the correct outlet on the generator.  
3. Plug in the female connector of the Power Cord to the inlet (if provided) located on the bottom of the Power Center.  
4. Turn OFF all circuit breakers in the Power Center and Main load center.  
5. Start the generator outdoors, following the procedures described in the generator’s owner’s manual furnished by the manufacturer.  
6. Turn ON the GENERATOR MAIN circuit breaker in the Power Center.  
7. Turn ON individual circuit breakers in the Power Center and the Main load center up to the continuous wattage rating of your generator. If the Generator  
Main breaker trips, you have overloaded the generator. Some circuit breakers must be turned OFF to avoid damage to the generator or to the loads being  
connected.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transferring from Generator Power to Utility Power:  
1. On the Power Center, turn OFF Generator MAIN breaker and turn ON Utility MAIN breaker. On 200 amps Main breaker models, this will require sliding the  
interlock mechanism up with the left hand while turning ON the 200 amp circuit breaker.  
2. Turn ON any branch circuit breakers in the Power Center and Main Load center that are OFF.  
3. Shut down the generator, following the procedures in the generator Owner’s Manual.  
4. Unplug the power cord from the Power Center and then the generator.  
5. Let the generator cool down before storing in a dry, secured location.  
6. To ensure that your generator will work properly when you need it, it is important to start and run your generator under load regularly and keep the tank  
filled with fresh fuel. Perform the above steps at least ONCE A MONTH to keep the generator properly “exercised.”  
TABLE 2 - Wire Connector Usage Chart:  
WIRE SIZE  
12  
Red  
Red  
NA  
NA  
NA  
10  
NA  
Red  
Red  
NA  
NA  
8
NA  
NA  
NA  
Blue  
Blue  
6
NA  
NA  
NA  
Blue  
Blue  
14  
12  
10  
8
6
TABLE 3 – Compatible Circuit Breaker Types:  
Compatible GFCI, Arc-Fault/ Surge Protection Circuit Breakers:  
Siemens QP, QT, QPH, HQP, QPF, QPHF, QFP, QE, QEH  
Cutler Hammer/Westinghouse Series BD, BR, BQ, GFC  
Challenger Type A, C, HAGF  
Square D Series HOM  
GE Series THQL  
Siemens: QPF (GFCI), QAF (Arc Fault), QP (Surge Protector)  
WIRING DIAGRAMS:  
Gen/Tran Corporation  
P.O. Box 1001, Alpharetta, GA 30009-1001  
Toll Free: 1-888-GEN-TRAN Fax: 770-552-7756  
© 2003 Gen-Tran Corporation. All Rights Reserved. PowerStay is a trademark of Gen-Tran Corporation  
4
PN XXXXX Rev A 6-12-03  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Ei Electronics Smoke Alarm Ei 176 User Manual
Electro Voice Microphone 600EH User Manual
Exido Blender 246 017 User Manual
Exido Scale 246 022 User Manual
Fitness Quest Home Gym 80e User Manual
FujiFilm Camera Lens 2030526 User Manual
Fujitsu Battery Charger LT C 500 User Manual
Genesis Advanced Technologies Speaker System Monitor 2 User Manual
Gianni Industries Door GL 1800S User Manual
Global Machinery Company Drill DP21 User Manual