Dimplex Heat Pump LA16ASR User Manual

CE  
MOUNTING and OPERATING MANUAL  
Reversible Air-to-Water Heat Pump  
for Outdoor Installation  
LA 16ASR  
Order No.: 452158.66.21  
FD 8507  
Download from Www.Somanuals.com. All Manuals Search And Download.  
READ IMMEDIATELY  
1.2 Legal Provisions and Guidelines  
READ IMMEDIATELY  
This heat pump was designed and built in  
compliance with all relevant EU directives, DIN and  
VDE regulations (see CE Declaration of Conformity).  
1
1.1 Important Information  
The electrical connection of the heat pump must be  
performed according to and conforming with all  
relevant VDE, EN and IEC standards. Beyond that,  
all technical connection requirements of the local  
electrical utility company have to be observed.  
CAUTION!  
Prior to opening the unit it must be  
ensured that all electrical circuits are disconnected  
from the power source.  
On connecting the heating and cooling system,  
CAUTION!  
all relevant regulations have to be complied wit.  
During transport, the heat pump must  
not be tilted more than 45° (in either direction).  
1.3 Energy-Efficient Use of the Heat  
Pump  
CAUTION!  
Heat pump and transport pallet are  
only connected by the packaging film.  
By purchasing this heat pump you contribute to the  
protection of the environment. A prerequisite for  
energy-efficient operation is the proper design of the  
heat source system and the heat utilization/cooling  
system.  
CAUTION!  
The intake and outlet duct openings  
must not be restricted nor obstructed.  
One of the most important factors of heat pump  
efficiency is keeping the temperature difference  
between the heating water and the heat source as  
small as possible. It is therefore strongly  
recommended that the design of both the heat  
source system and the heat distribution system be  
carried out with great care. A 1 Kelvin (1°C) higher  
temperature difference corresponds to an  
increase in power consumption of approx. 2.5%.  
When designing the heating system care must be  
taken that special applications such as domestic  
water heating are taken into consideration and  
dimensioned for low temperature operation. Heat  
pumps are optimally suited for underfloor heating  
(surface/radiant heating) applications due to the  
low supply temperatures (30 °C to 40 °C).  
CAUTION!  
Clockwise phase sequence to be  
observed: Damage to the compressor may be  
incurred if it is operated in the wrong sense of  
rotation.  
CAUTION!  
Do not use any cleaning agents  
containing sand, soda, acid or chloride as these may  
attack the surface.  
CAUTION!  
To prevent consequential damage it  
is imperative that the water circuit be neutralized  
after cleaning using appropriate agents.  
During operation it is essential that the heat  
exchanger is not contaminated as this would  
increase the temperature difference resulting in an  
inferior coefficient of performance.  
CAUTION!  
The unit is not suitable for operation  
A considerable contribution to the economical  
operation is made by the heat pump controller  
provided it is set correctly. For more detailed  
information refer to the operating manual of the heat  
pump controller.  
with a frequency converter.  
CAUTION!  
Work on the refrigeration circuit may  
be performed by qualified persons only.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PURPOSE OF HEAT PUMP  
SCOPE OF DELIVERY  
valve as well as the low-noise compressor, a  
desuperheater, a condenser and the electric control  
unit.  
PURPOSE OF HEAT  
2 PUMP  
In the case of low ambient temperatures, air humidity  
may accumulate on the evaporator in the form of  
frost impairing the heat transfer. The evaporator is  
automatically defrosted by the heat pump, if required.  
2.1 Application  
The air-to-water heat pump is designed for use in  
existing or newly built heating systems.  
Cooling  
In the "cooling" mode, the operating process of  
The heat pump is designed exclusively for the  
evaporator and condenser is reversed..  
heating and cooling of heating water!  
The heating water transfers the heat to the refrigerant  
via the condenser that is now working as the  
evaporator. In the compressor the temperature of  
the refrigerant is raised, and the heat is rejected to  
the ambient air via the condenser (in the heating  
mode the evaporator).  
In the heating mode, the heat pump is suitable both  
for mono-energetic and bivalent operation at outdoor  
o
air temperatures down to -20 C.  
In the continuous mode of operation, a heating water  
return temperature of more than 18 °C must be  
maintained in order to ensure proper defrosting of  
the evaporator.  
Via the additional heat exchanger, the waste heat  
can also be used for hot water consumers such as  
domestic hot water, swimming pool or bathroom  
heating applications.  
The heat pump is not designed for any increased  
heat demand during the drying phase of new  
buildings; the additional heat demand must be met  
by special appliances to be supplied on site. For the  
structural drying of new buildings in the autumn or  
winter it is recommended that an additional electric  
heating element (available as accessory) be  
installed.  
SCOPE OF DELIVERY  
3
3.1 Baseline Unit  
In the cooling mode, the heat pump is suited for air  
temperatures ranging from +15 °C ... +40 °C.  
The heat pump is delivered as a compact unit  
containing the components listed below.  
It can be used for passive and dynamic cooling  
applications alike. The minimum water temperature  
is +7 °C.  
The refrigerant used is R404A.  
1
2
CAUTION!  
The unit is not suited for operation  
with a frequency converter.  
2.2 Principle of Operation  
Heating  
Ambient air is drawn in by the fan and passed over  
the evaporator (heat exchanger). The evaporator  
cools the air, i.e. it extracts the heat it contains. In  
the evaporator, the heat removed is transferred to  
the working fluid (refrigerant).  
With the aid of an electrically driven compressor, the  
absorbed heat is "pumped" to a higher temperature  
level through pressure increase and given off to the  
heating water via the condenser (heat exchanger).  
The desuperheater, mounted upstream, enables  
domestic hot water to be produced simultaneously  
or separately.  
In so doing, electrical energy is used to raise the  
heat of the environment to a higher temperature level.  
Due to the fact that the energy extracted from the air  
is transferred to the heating water, this type of  
appliance is referred to a air-to-water heat pump.  
6
5
4
3
1) Evaporator  
(heating mode)  
2) Fan  
4) Pressostats  
5) Condenser  
(heating mode)  
6) Compressor  
The air-to-water heat pump consists of the following  
main components: evaporator, fan and expansion  
3) Control box  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SCOPE OF DELIVERY  
TRANSPORT  
3.2 Control Box  
TRANSPORT  
The control box is integrated in the heat pump. It can  
be folded downward after removing the lower front  
panel and loosening the fastening screws located  
at the top on the right.  
4
CAUTION!  
During transport, the heat pump  
The control box houses the mains terminals as well  
must not be tilted more than 45° (in either direction).  
as the power contactors and the soft start unit.  
The plug connector for the control lead is located at  
the bottom of the unit in the immediate vicinity of the  
line feed-through through the bottom of the unit.  
The unit should be transported to the final installation  
site on a wooden pallet. The baseline unit can be  
transported either by means of a lift truck, a sack  
trolley, or the like, or using 3/4" pipes to be put through  
the openings provided in the base plate or the frame.  
3.3 Heat Pump Controller  
For the operation of your reversible air-to-water  
heat pump, the reversible heat pump controller  
included in the scope of delivery is to be used.  
he heat pump controller is a comfortable electronic  
regulating and control unit. It controls and monitors  
the entire heating/cooling system as a function of  
the outdoor air temperature, the hot water  
preparation and the safety devices.  
The external temperature sensor, to be mounted by  
the customer, incl. fastening hardware is shipped  
with the controller.  
Method of functioning and operation of the heat pump  
controller are described in the enclosed operating  
manual.  
CAUTION!  
The heat pump and transport pallet  
are only connected by the packaging film.  
It is necessary to remove the lower cover panel to be  
able to access the transport openings in the frame.  
For this purpose, loosen two screws each in the base,  
retract the panels and disengage them at the  
1.  
3.  
1.  
3.  
2.  
1.  
2.  
1.  
1.  
2.  
Opening the cover  
Closing the cover  
top. When reinstalling the panels, they should be  
pushed upward by exerting slight pressure.  
When slipping the carrying pipes through the frame,  
care must be taken that no components are damaged.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
MOUNTING  
INSTALLATION  
MOUNTING  
5
6
5.1 General  
6.1 General  
The unit should always be installed on a permanently  
level, smooth and horizontal floor. The entire base  
frame surface should thereby make close contact with  
the floor in order to ensure adequate sound insulation  
and to prevent water-carrying parts from cooling out.  
If this is not the case, additional insulation measures  
may become necessary. It must be possible to carry  
out servicing work without any problems. This is  
ensured if a clearance of 1.2 m to solid walls is  
maintained.  
The following connections need to be established  
on the heat pump:  
- supply/return flow of heating system  
- supply/return flow of hot water circuit  
- condensate drain  
- control lead to the heat pump controller  
- power supply  
6.2 Heating and Hot Water Connection  
The connections on the heating side of the heat  
pump are provided with 1"external thread. The hoses  
to be connected exit the unit through its bottom. When  
carrying out the connections, use a wrench to  
counterhold at the transitions.  
1,2 m  
Before completing the heat pump connections on  
the heating water side, the heating installation must  
be flushed in order to remove any impurities that  
may be present and to ensure trouble-free operation  
of the heat pump. On systems equipped with heating  
water flow shut-off devices such as radiator or  
thermostat valves, an overflow valve to be provided  
by the customer needs to be installed behind the  
heating pump in a heating system bypass. This  
guarantees a minimum heating water flow through  
the heat pump and prevents any malfunctions from  
occurring.  
1,2 m  
1,2 m  
1,2 m  
Once the installation on the heating side has been  
completed, the heating system must be filled, de-  
aerated and pressure-tested.  
CAUTION!  
The intake and discharge openings  
must not be restricted nor obstructed.  
Frost Protection  
As a precaution against frost, manual drain valves  
should be provided. If the heat pump is placed out of  
service or in the event of a power failure, the system  
has to be drained at three points (see figure) and  
blown out. In heat pump installations where a power  
failure cannot be readily detected (holiday house),  
the heating circuit must contain a suitable antifreeze  
product.  
5.2 Condensate Line  
The condensation water that may collect during  
operation must be drained in a place protected from  
frost. The heat pump must be positioned horizontally  
so that proper discharge can be ensured. The  
condensation water pipe must have a minimum  
diameter of 50 mm and should be discharged to the  
sewer drain in a frost-proof location.  
Wärmepumpe  
Heat pump  
3
1
2
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING  
COMMISSIONING  
6.3 Electrical Connection  
via a commercially available 4-core cable.  
COMMISSIONING  
The power connection of the heat pump is effected  
7
7.1 General  
The cable has to be supplied by the client and the  
wire cross-section to be selected according to the  
power consumption of the heat pump (see Equip-  
ment Data in the appendix) as well as the relevant  
VDE (EN) and VNB regulations.  
To ensure proper commissioning it should be  
carried out by an after-sales service authorized by  
the manufacturer. Only then can an extended  
warranty period of 3 years in total be granted (cf.  
Warranty service).  
The power supply of the heat pump must be  
equipped with an all-pole disconnecting device with  
a contact gap of at least 3 mm (e.g. utility company  
shut-off contactor, power contactor) as well as a 3-  
pole circuit breaker with simultaneous tripping of all  
external conductors (tripping current as stated on  
the device data plate).  
7.2 Preparatory Steps  
Prior to commissioning, the following items need to  
be checked:  
- All connections of the heat pump must have been  
made as described in Chapter 6.  
When making the electrical connection, the  
clockwise phase sequence of the power supply must  
be ensured.  
- In the heating circuit all valves that could impair  
the proper heating water flow must be open.  
- The air intake/discharge path must be  
unobstructed.  
Phase sequence: L1, L2, L3.  
- The sense of rotation of the fan must correspond  
to the direction of the arrow.  
CAUTION!  
Clockwise phase sequence to be  
observed: Damage to the compressor may be  
incurred if it is operated in the wrong sense of  
rotation.  
- The settings of the heat pump controller must be  
adapted to the heating installation in accordance  
with the instructions contained in its instruction  
manual.  
The control voltage is supplied via the heat pump  
- Proper condensate drainage must be ensured.  
controller.  
The 230V AC-50 Hz power supply of the heat pump  
controller is effected as described in its instruction  
manual (fusing 16 A).  
7.3 Procedure During Heating Season  
The start-up of the heat pump is effected via the heat  
pump controller. The settings must be made in  
accordance with its instruction manual.  
The control lead (not included in the scope of  
delivery) is connected to the heat pump controller  
via a multi-pole plug connector. In the heat pump,  
the plug connector located at the bottom of the unit  
in the immediate vicinity of the line feed-through  
through the base of the unit. More detailed  
instructions are contained in the instruction manual  
of the heat pump controller.  
Malfunctions during operation are displayed on the  
heat pump controller and may be corrected as  
described in the heat pump controller's instruction  
manual.  
n the case of outdoor temperatures below 10 °C  
and heating water temperatures below 16 °C, the  
buffer tank has to be heated to at least  
30 °C using the second heat generator.  
For more detailed information refer to the wiring  
diagrams in the appendix.  
The following procedure has to be observed so that  
the commissioning activities can be carried out  
without any problems:  
a) Close all heating circuits.  
b) Open the overflow valve all the way.  
c) Select the automatic mode on the controller.  
d) Wait until the buffer tank has reached a  
temperature of 25-30 °C.  
e) Subsequently, slowly reopen the valves of the  
heating circuits, one after the other, in such a  
way that the heating water flow rate is  
continually increased by slightly opening the  
related heating circuit valve. When so doing, the  
heating water temperature in the buffer tank  
must not fall below 25 °C so that the heat pump  
can be defrosted at any time.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMISSIONING  
CLEANING / MAINTENANCE  
f)  
Once all heating circuit are fully open and a  
heating water temperature of approx. 25 °C is  
maintained in the buffer tank, the minimum flow  
rate must be set on the overflow valve and the  
heating circulating pump.  
CLEANING /  
8 MAINTENANCE  
8.1 Maintenance  
g) New buildings have an increased heat demand  
due to the energy required for structural drying.  
This increased heat demand may result in  
insufficiently dimensioned heating installations  
not attaining the desired room temperature at  
all times. In this case it is therefore  
recommended that the second heat generator  
be kept ready for operation in the first heating  
season. The limit temperature on the heat pump  
controller should therefore be raised to 15°C.  
To protect the paint finish, avoid placing objects  
against or on the unit. The external parts of the heat  
pump can be wiped with a damp cloth and  
commercially available cleaning agents.  
CAUTION!  
Do not use any cleaning agents  
containing sand, soda, acid or chloride as these may  
damage the surface.  
To prevent malfunctions in the heat exchanger of the  
heat pump caused by dirt deposits, care must be  
taken that the heat exchanger cannot become  
contaminated in the heating installation. In the event  
that operating malfunctions due to contamination  
occur nevertheless, the system should be cleaned  
as described below.  
7.4 Procedure During Cooling Season  
In this case, all heating circuits can be fully opened.  
The setting described in 7.3 f) must be carried out  
during the heating season.  
8.2 Cleaning of Heating Side  
The ingress of oxygen into the heating water may  
result in the formation of oxidation products. An ad-  
ditional contamination of the heating water caused  
by residues of lubricating and sealing agents occurs  
in many cases.  
Both of the above causes may lead to a reduction in  
the performance of the heat pump condenser. In  
these cases the installer needs to clean the  
condenser. Based on information known to date we  
recommend cleaning with a 5% phosphoric acid  
solution or, in the case that cleaning needs to be  
performed more frequently, with a 5% formic acid  
solution. In both cases the  
cleaning fluid should be at room temperature.  
Thorough flushing is necessary to ensure that all  
cleaning agent residues are removed from the  
system. It is recommended that the heat exchanger  
is cleaned in the direction opposite to the normal  
flow direction. Owing to their acid content flushing  
agents must be used with caution. To prevent acidic  
flushing agents from entering the heating installation  
when cleaning the condenser, we recommend that  
the flushing device should be mounted directly to  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
CLEANING / MAINTENANCE  
MALFUNCTIONS / TROUBLESHOOTING  
DECOMMISSIONING  
the supply and return line of the heat pump. The  
regulations of the trade associations must be  
adhered to. If in doubt, contact the manufacturers of  
the chemicals!  
MALFUNCTIONS /  
9 TROUBLESHOOTING  
This heat pump is a quality product and is designed  
for troublefree and maintenance-free operation. In  
the event that a malfunction occurs nevertheless,  
you will be able to correct the problem easily  
yourself. Simply consult the Malfunctions and  
Troubleshooting table in the operating manual of  
the controller. Malfunctions can be interrogated at  
the heat pump controller. If the problem cannot be  
corrected by the user, please contact the after-sales  
service in charge (see Warranty Card).  
CAUTION!  
To prevent consequential damage it  
is imperative that the water circuit be neutralized  
after cleaning using appropriate agents.  
Caution - Heating Engineers  
Depending on the water quality and quantity, in  
particular in the case of mixed installations and  
plastic pipes, mineral deposits (rust sludge, lime)  
may form impairing the proper functioning of the  
heating installation. A cause of this is the water  
hardness as well as oxygen dissolved in the filling  
water as well as additional oxygen from the air which  
may penetrate via valves, fittings and plastic pipes  
(oxygen diffusion). As a preventive measure it is  
recommended that a physical water conditioner such  
as ELYSATOR be used.  
CAUTION!  
Any work on the heat pump may only  
be performed by an authorized and qualified after-  
sales service.  
DECOMMISSIONING  
10  
10.1 Placing Out of Service in Summer  
8.3 Cleaning of Air Side  
Placing the heat pump out of service in summer can  
be effected by switching the heat pump controller to  
the "Summer" operating mode.  
Evaporator, fan and condensate drain should be  
cleaned of debris (leaves, branches, etc.) from time  
to time. To this end, the front panel of the heat pump  
should be opened first at the bottom and then at the  
top.  
10.2 End-of-Life Decommissioning /  
Disposal  
Prior to opening the unit it must be  
CAUTION!  
ensured that all electrical circuits are disconnected  
from the power source.  
Before removing the heat pump, disconnect the  
machine from the power supply and close all valves.  
Environment-relevant requirements regarding the  
recovery, recycling and disposal of service fuels and  
components in accordance with all relevant  
standards must be adhered to. In this context,  
particular attention must be paid to the proper  
disposal of refrigerants and refrigeration oils.  
The removal and reinstallation of the panel  
assemblies to be performed as described in  
Chapter 4.  
When cleaning do not use any sharp or hard objects  
so as to prevent any damage to the evaporator and  
the condensate pan.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX  
APPENDIX  
11  
11.1  
11.2  
11.3  
DIMENSION DRAWING  
11  
12  
EQUIPMENT DATA  
SCHEMATICS  
11.3.1  
Heating Mode  
13  
14  
11.3.2  
Cooling Mode  
11.4  
WIRING DIAGRAMS  
11.4.1  
11.4.2  
11.4.3  
11.4.4  
Control  
15  
16  
17  
18  
Load  
Terminal Diagram  
Legend  
11.5  
11.6  
11.7  
HYDRAULIC BLOCK  
DIAGRAM  
19  
20  
21  
EC DECLARATION OF  
CONFORMITY  
WARRANTY CERTIFICATE  
AFTER-SALES SERVICE  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.1 DIMENSION DRAWING  
Dimension Drawing  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.2 EQUIPMENT DATA  
Equipment Data  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.3 SCHEMATICS  
11.3.1 Heating Mode  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.3 SCHEMATICS  
11.3.2 Cooling Mode  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.4 WIRING DIAGRAMS  
11.4.1 Control  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.4 WIRING DIAGRAMS  
11.4.2 Load  
y e / g n  
y e / g n  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.4 WIRING DIAGRAMS  
11.4.3 Terminal Diagram  
Terminal connection diagram and connector assignment  
in the reversible air-to-water outdoor unit  
Wire () and pin numbers  
Mains  
Wire () and pin numbers  
Heat pump controller  
Heat pump controller  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.4 WIRING DIAGRAMS  
11.4.4 Legend  
E1  
E2  
E3  
E4  
Crankcase heater, compressor  
Fan for nozzle ring heater  
Defrost end pressostat  
Condensing pressure pressostat  
F2  
High-pressure pressostat  
Low-pressure pressostat  
Thermostat HG  
F3  
F5  
F23  
Winding shield, fan  
K1  
Compressor contactor  
K2  
Fan contactor  
M1  
M2  
Compressor  
Fan  
N1  
Heat pump controller  
N3  
Soft start control  
R9  
Frost protection sensor for heating water  
Heating water return flow sensor  
Coding resistor (5k6)  
R10  
R11  
X1  
X2  
X3  
X4  
X5  
X6  
X7  
Terminal strip: load terminal  
Terminal strip: internal wiring  
Terminal strip: heaters  
Plug connector, heat pump controller  
Plug connector, control lead  
Plug connector, control lead  
Plug connector, heat pump  
Y1  
4-way reversing valve  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM  
Hydraulic Block Diagram  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: 11.6 EC DECLARATION OF CONFORMITY  
EC Declaration of Conformity  
Declaration of Conformity  
The undersigned  
KKW Kulmbacher Klimageräte-Werk GmbH,  
Geschäftsbereich Dimplex  
Am Goldenen Feld 18  
D-95326 Kulmbach  
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed  
on the market by us, conform to the relevant requirements of the applicable EC directives.  
This declaration becomes invalidated if any modifications are made to the product(s) without our  
prior authorization.  
Designation of the product(s):  
EC Directives:  
Air-to-water heat pumps  
for outdoor installation,  
containing R404A  
EC Directive for Low Voltage  
(73/23/EEC)  
EC Directive for Electromagnetic Compatibility (EMC)  
(89/336/EEC)  
Pressure Equipment Directive  
(97/23/EEC)  
Type(s):  
LA 16ASR  
Harmonized EN Standards:  
Requirements of category II  
Order No.:  
342 070  
National Standard/Directives:  
Kulmbach, 25.07.2003  
General Manager  
Technical Director  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
KKW Kulmbacher Klimageräte-Werk GmbH  
Geschäftsbereich Dimplex  
Am Goldenen Feld 18  
Technical data subject to change without notice  
Fax +49 (0) 92 21 709-589  
D-95326 Kulmbach  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Cobra Electronics Marine Radio 37 ST User Manual
Craftsman Portable Generator 919679580 User Manual
Curtis Flat Panel Television LCDVD198 User Manual
Cypress Computer Hardware CY7C1231H User Manual
Dyson Vacuum Cleaner DC01 User Manual
Electro Voice Microphone PL84 User Manual
Everpure Water System CES 2900E 136 DP User Manual
Fundex Games Games 4 Great Games User Manual
GE Answering Machine 2 9892 User Manual
Glen Dimplex Home Appliances Ltd Cooktop 321R User Manual