AIRSTREAM™  
42BHC,BVC  
System Fan Coils  
Product  
Data  
600 to 4000 Cfm  
Carrier’s versatile belted fan coil units  
satisfy design requirements:  
• A selection of 8 sizes covers  
capacities from 600 to 4000 cfm  
• Choice of motors, from 1/4 to 5 hp,  
eliminates oversizing  
• Wide range of coil options for 2-pipe  
or 4-pipe systems  
• Optional DX coils with expansion  
valve and distributor  
• Single and three-phase electric  
heat (1.0 to 40 kW)  
Features/Benefits  
The 42BHC, BVC belt drive  
fan coil units provide year-  
round comfort air  
conditioning with central  
station operating economy.  
42BHC UNIT  
A variety of coil options  
reduces first cost  
Four, 6 or 8-row cooling coils combine  
needed capacities with the most effi-  
cient heat transfer surface. For  
4-pipe systems, select either of two  
split-coil options. Coils consist of alu-  
minum fins securely bonded to 1/2-in.  
OD seamless copper tubes. Each fin’s  
aluminum collar ensures accurate con-  
trol of the fin spacing, while complete-  
ly covering the tubes to lengthen coil  
life. All coils also feature manual air  
vents, with automatic air vent available  
as an option.  
42BVC UNIT  
Copyright 2005 Carrier Corporation  
Form 42B-1PD  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model number nomenclature  
42BH  
C
08  
L
42BH Vertical Belt Drive Fan Coil Unit  
42BV Vertical Belt Drive Fan Coil Unit  
Coil — Rows  
B 4, 2-Pipe  
6, 2-Pipe  
L —  
H 4/1, Same End Conn.  
K 4/2, Same End Conn.  
N 6/1, Same End Conn.  
Q 6/2, Same End Conn.  
R 8, 2-Pipe  
1 4 With Electric Heat  
2 6 With Electric Heat  
3 8 With Electric Heat  
C Design  
Size Nominal  
Cfm  
06 —  
600  
08  
10  
800  
1000  
12 1200  
16 1600  
20 2000  
30 3000  
40 4000  
NOTE: Refer to current 42 Series Master Prices for  
complete model definition, including motor, cfm and  
total static pressure.  
Physical data  
UNIT SIZE 42BHC, BVC  
NOMINAL CFM  
06  
600  
08  
800  
10  
1000  
12  
1200  
16  
1600  
20  
2000  
30  
3000  
40  
4000  
42BHC SHIPPING WT (lb)  
(no heat/ with heat)  
42BVC SHIPPING WT (lb)  
(no heat/ with heat)  
203/234  
200/231  
205/236  
202/233  
253/287  
256/290  
247/281  
312/346  
289/323  
344/380  
351/387  
437/474  
436/473  
553/590  
522/559  
243/277  
FILTERS (2 in. pleated)  
Number...Size (in.)  
Face Area (sq ft)  
1...161/2 x 24 1...161/2 x 24 1...181/4 x 33 1...181/4 x 33 2...181/4 x 211/2 2...203/4 x 22 2...29 x 22 2...29 x 29  
2.8  
2.8  
4.2  
4.2  
5.5  
6.3  
8.9  
11.7  
COILS  
Size (in.)  
15 x 20  
2.1  
15 x 20  
2.1  
15 x 29  
3.0  
15 x 29  
3.0  
15 x 39  
4.1  
18 x 40  
4.9  
27 x 40  
7.7  
27 x 54  
10.3  
Face Area (sq ft)  
Fins per inch  
10  
Coil Water Weight (approx. lb per  
0.240  
0.240  
0.324  
0.324  
0.420  
0.492  
0.768  
1.020  
row of coil)  
FANS  
Number...Size (in.)  
1...9 x 4  
1...9 x 6  
1...10 x 4  
1...10 x 7  
1...11 x 10  
1...12 x 9  
1...12 x 12 1...15 x 12  
11/2 OD  
COPPER COIL CONN. 8 ROW  
(in.) (Cooling)  
1 OD  
COPPER COIL CONN. 4 AND 6 ROW  
(in.) (Cooling)  
3
/4 OD  
1 OD  
11/2 OD  
COPPER COIL CONN. 1 AND 2 ROW  
(in.) (Heating)  
1
/
2 OD  
3
DRAIN CONN. SIZES (in.)  
/4 MPT  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options and accessories  
42BHC, BVC OPTIONS AND ACCESSORIES  
electric heater data table for availability per unit) with  
single-stage or multiple-stage, single power source.  
Voltages:  
• 115 v, 208 v, 230 v and 277 v single-phase 60 Hz  
• 208 v, 230 v and 480 v three-phase 60 Hz  
Electric heat is available with the following staging options  
(3-phase staging is balanced).  
• 1 to 12 kW 1 stage only — single phase  
• 3 to 12 kW 1 or 2 stage only — single phase  
• 1 to 40 kW 1 stage only — 3 phase  
• 4 to 40 kW 1 or 2 stage only — 3 phase  
• 12 to 40 kW 1, 2, or 3 stage — 3 phase  
ITEM  
Automatic Air Vents  
Controls  
Electric Heat  
Filters  
OPTION*  
ACCESSORY†  
X
X
X
X
X
X
Heating/Cooling Coils  
Insulation  
Mixing Boxes  
Motors  
X
X
Thermostats  
Valve Packages  
X
X
*Factory-installed option.  
†Field-installed accessory.  
Heater coils are constructed of high-grade resistance  
wire that is supported by ceramic insulators on plated steel  
brackets. These heat elements are suspended directly in  
front of the outlet after the blower and the coil. High limit  
thermal cutouts protect the heater in the event of air  
failure.  
Filters — Two in. pleated filters are standard. One-in.  
pleated, two 1-in. throwaway, or 2-in. MERV (minimum  
efficiency reporting value) 11 filters with 2-in. pleated  
pre-filter are available. The 2-in. MERV 11 filters with 2-in.  
pleated pre-filter include a filter rack.  
The 42BHC and 42BVC fan coil units are designed to  
offer maximum flexibility in an application, accessibility for  
service, quiet operation and durability.  
Factory-installed options  
Automatic air vents — Automatic air vents have fiber-  
washers, which allow air in the pipes to pass through,  
automatically bleeding the system. The fiber washers elimi-  
nate the need to manually remove air from the system.  
When wet, washers swell and seal the system.  
Insulation — Tuf-Skin™ II (1-in. thick) insulation is  
standard. Units are available with ¾-in. closed cell, 1-in.  
Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.  
Coils — Coils are available in a choice of two-pipe system  
with 4-row cooling/heating or four-pipe system with 4, 6  
or 8-row cooling and 1 or 2 row heating.  
Motors — A wide selection of standard motors provides  
efficient operation in ducted applications with excellent  
performance with up to 2 inches of total static pressure.  
Reheat operation is standard. Preheat is available as an  
option.  
Controls  
• Interlocking disconnect switch  
• Heater power fusing  
Available motor options:  
• 115 v, 208 v, 230 v and 277 v single-phase 60 Hz  
• 208 v, 230 v and 460 v three-phase 60 Hz  
• Open drip-proof motors  
• 24 v Class 2 transformer (40 va)  
• 8-pole control terminal strip  
• Auto reset temperature limit switch  
• Airflow safety switch  
• External junction box  
Field-installed accessories  
• Motor power fusing  
Mixing boxes Mixing boxes can be used when outside  
air is required for ventilation. Preassembled at the factory  
and shipped separately with base rails for field installation,  
mixing boxes include a linkage kit consisting of two crank  
arms, 2 swivels and either a 25 in. long (for sizes 06-16) or  
a 84 in. long (for sizes 20-40) rod for field installation of an  
actuator.  
• Motor control contactor  
• 24 v condensate overflow switch  
Electric heat — Total electric heat eliminates the require-  
ment for a boiler. Heating and/or cooling may be available  
on an individual basis throughout the year. Resistance  
electric heat is available from 1.0 kW to 40.0 kW (refer to  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Thermostats — Three thermostats are available for field  
installation:  
• programmable operating range, dead band, digital dis-  
play, temperature set-back  
Honeywell T834C manual changeover, single-stage heat  
thermostat features:  
• off-cool-heat system switch  
• on-auto fan mode switch  
• single-stage electric heat  
• outside air signal  
Honeywell T8500 digital, automatic/manual changeover,  
2-stage heat thermostat features:  
• digital display of temperatures and all functions  
• off-cool-heat-auto system mode buttons  
• single speed fan operation  
• on-auto fan mode button  
• single or two stage electric heat signal  
• outside air signal  
• remote temperature sensor available  
Sunne T170 single-stage heat, 2-pipe heat/cool auto  
changeover thermostat features:  
• digital display of ambient temperature and operating  
mode  
THERMOSTAT FUNCTIONS  
THERMOSTATS  
SYSTEM  
FUNCTION  
CHANGEOVER  
Honeywell Honeywell Sunne  
T834C  
T8500  
X
T170  
X
2 Pipe  
2 Pipe  
HW-Heat Only  
ACO  
ACO  
MCO  
ACO  
MCO  
CW-Cool Only  
X
X
X
CW/HW  
Heat/Cool  
2 Pipe  
X
CW/HW  
Heat/Cool with  
Aux. Electric Heat  
X
2 Pipe  
ACO  
X
MCO  
ACO  
MCO  
ACO  
X
X
X
X
X
X
X
X
X
X
CW-Cooling with  
2 Pipe  
4 Pipe  
Total Electric Heat  
CW/HW  
Heat/Cool  
LEGEND  
ACO  
Aux  
CW  
Automatic Changeover  
Auxiliary  
Chilled Water  
HW — Hot Water  
MCO — Manual Changeover  
Valve packages — Valve packages are factory assembled  
for field installation. Motorized valves (24 v) can be operat-  
ed with power on with spring return or power off/power  
on.  
It is recommended that basic motor controls are ordered  
when valve packages are ordered.  
• single fan speed operation, power and operating mode  
buttons  
• continuous fan operation, cycling water control valve  
• 4-pipe ACO/MCO (automatic changeover/manual  
changeover) with “on-auto” fan mode button  
• one or 2 stage electric heat signal available  
• purge cycle and temperature sensor for 2-pipe cold  
water/hot water systems  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions  
42BHC FAN COIL BASE UNIT (NO CONTROLS)  
DIMENSIONS (in.)  
Supply Duct  
UNIT  
42BHC  
Return Duct  
Mounting Holes  
Fan Size  
Depth  
Width  
Height  
A
B
C
D
E
F
J
K
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
11 x 10  
12 x  
12 x 12  
15 x 12  
4
6
4
7
363/16  
363/16  
373/4  
373/4  
2811  
2811  
/
/
181/2  
181/2  
201/4  
201/4  
201/4  
223/4  
31  
137/8  
137/8  
137/8  
137/8  
11/8  
11/8  
11/8  
11/8  
11/8  
11/8  
61/8  
51/8  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
273/16  
273/16  
363/16  
363/16  
463/16  
473/16  
473/16  
613/16  
16  
16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
16  
16  
3715  
/
1613  
/
16  
16  
9
403/8  
403/8  
439/16  
173/4  
161/16  
2213  
31  
/
16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BHC FAN COIL WITH MOTOR CONTROL OPTION  
DIMENSIONS (in.)  
UNIT  
42BHC  
Supply Duct  
Return Duct  
Mounting Holes  
Fan Size  
Depth  
Width  
Height  
A
B
C
D
E
F
J
K
351/4  
351/4  
3613  
3613  
37  
397/16  
397/16  
425/8  
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
11 x 10  
12 x  
12 x 12  
15 x 12  
4
6
4
7
363/16  
363/16  
373/4  
373/4  
2811  
2811  
/
/
181/2  
181/2  
201/4  
201/4  
201/4  
223/4  
31  
137/8  
137/8  
137/8  
137/8  
11/8  
11/8  
11/8  
11/8  
11/8  
11/8  
61/8  
51/8  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
167/16  
167/16  
183/16  
183/16  
183/16  
2011  
2815  
2815  
273/16  
273/16  
363/16  
363/16  
463/16  
473/16  
473/16  
613/16  
16  
16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
/
/
16  
16  
3715  
/
1613  
/
16  
16  
9
403/8  
403/8  
439/16  
173/4  
161/16  
2213  
/
/
/
16  
16  
16  
31  
/
16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions (cont)  
42BHC FAN COIL WITH ELECTRIC HEAT OPTION  
DIMENSIONS (in.)  
Supply Duct  
UNIT  
42BHC  
Return Duct  
Mounting Holes  
Fan Size  
Depth  
Width  
Height  
A
B
C
D
E
F
J
K
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
11 x 10  
12 x  
12 x 12  
15 x 12  
4
6
4
7
363/16  
363/16  
373/4  
373/4  
2811  
2811  
/
/
181/2  
181/2  
201/4  
201/4  
201/4  
223/4  
31  
11/8  
11/8  
11/8  
11/8  
11/8  
11/8  
61/8  
51/8  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
273/16  
273/16  
363/16  
363/16  
463/16  
473/16  
473/16  
613/16  
16  
16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
16  
16  
3715  
/
16  
16  
9
403/8  
403/8  
439/16  
31  
16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BVC FAN COIL BASE UNIT (NO CONTROLS)  
DIMENSIONS (in.)  
Supply Duct  
UNIT  
42BVC  
Return Duct  
Fan Size  
Depth  
Width  
Height  
A
B
C
E
F
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
11 x 10  
12 x  
12 x 12  
15 x 12  
4
6
4
7
20  
20  
22  
22  
22  
24  
28  
28  
281/16  
281/16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
361/2  
361/2  
393/8  
393/8  
393/8  
451/8  
543/16  
575/8  
71/8  
89/16  
71/2  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
915  
/
16  
135/16  
121/2  
157/8  
167/16  
9
16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions (cont)  
42BVC FAN COIL WITH MOTOR CONTROL OPTION  
DIMENSIONS (in.)  
UNIT  
42BVC  
Supply Duct  
B
Return Duct  
Fan Size  
Depth  
Width  
Height  
A
C
E
F
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
11 x 10  
12 x  
12 x 12  
15 x 12  
4
6
4
7
20  
20  
22  
22  
22  
24  
28  
28  
281/16  
281/16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
361/2  
361/2  
393/8  
393/8  
393/8  
451/8  
543/16  
575/8  
71/8  
89/16  
71/2  
109/16  
109/16  
33/4  
33/4  
51/2  
51/2  
167/8  
1713  
161/8  
227/8  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
167/16  
167/16  
183/16  
183/16  
183/16  
1111  
1111  
1211  
/
/
/
16  
16  
16  
915  
/
16  
135/16  
121/2  
157/8  
167/16  
9
133/4  
133/4  
161/16  
/
2011  
2815  
2815  
/
16  
/
16  
/
16  
16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BVC FAN COIL WITH ELECTRIC HEAT OPTION  
DIMENSIONS (in.)  
Supply Duct  
UNIT  
Return Duct  
42BVC  
Fan Size  
Depth  
Width  
Height  
A
B
109/16  
109/16  
C
33/4  
33/4  
51/2  
51/2  
167/8  
E
F
06  
08  
10  
12  
16  
20  
30  
40  
9 x  
9 x  
10 x  
10 x  
4
6
4
7
20  
20  
22  
22  
22  
24  
28  
28  
281/16  
281/16  
371/16  
371/16  
471/16  
481/16  
481/16  
621/16  
361/2  
361/2  
393/8  
393/8  
393/8  
451/8  
543/16  
575/8  
71/8  
89/16  
71/2  
241/16  
241/16  
331/16  
331/16  
431/16  
441/16  
441/16  
581/16  
167/16  
167/16  
183/16  
183/16  
183/16  
1111  
1111  
1211  
133/4  
133/4  
/
/
/
16  
16  
16  
915  
/
16  
11 x 10  
12 x  
135/16  
121/2  
157/8  
167/16  
9
1713  
/
2011  
2815  
2815  
/
16  
/
16  
/
16  
16  
12 x 12  
15 x 12  
161/8  
227/8  
161/16  
NOTES:  
1. All dimensions are in inches ( 1/4 in.).  
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to  
change without notice.  
3. Right hand shown, left hand opposite.  
4. Hanger rods, which are field-supplied, are shown for reference only.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions (cont)  
42BHC UNIT CORNER WEIGHTS (lb)  
1
2
2
4
1
3
3
4
RIGHT HAND UNIT  
LEFT HAND UNIT  
LEFT-HAND UNITS  
RIGHT-HAND UNITS  
UNIT  
42BHC  
TOTAL  
CONFIGURATION  
WEIGHT  
1
2
3
4
1
2
3
4
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
No Heat  
With Heat  
50  
55  
47  
51  
55  
50  
51  
47  
203  
234  
205  
236  
253  
287  
256  
290  
312  
346  
344  
380  
437  
474  
553  
590  
06  
08  
10  
12  
16  
20  
30  
40  
50  
51  
50  
63  
62  
64  
63  
80  
79  
90  
58  
55  
59  
71  
76  
72  
76  
87  
91  
98  
59  
47  
59  
55  
68  
56  
68  
69  
82  
74  
67  
52  
68  
63  
81  
64  
82  
76  
95  
82  
58  
55  
59  
71  
76  
72  
76  
87  
91  
98  
50  
51  
50  
63  
62  
64  
63  
80  
79  
90  
67  
52  
68  
63  
81  
64  
82  
76  
95  
82  
59  
47  
59  
55  
68  
56  
68  
69  
82  
74  
88  
92  
90 102  
118 127  
88 100 102  
92 100 127 118 100  
90 100  
118 131 106 119 131 118 119 106  
155 162 114 122 162 155 122 114  
155 166 129 140 166 155 140 129  
NOTE: Unit weights (shown in pounds) 10%, are based on the 8-row coil and 1 Hp motor.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BVC UNIT CORNER WEIGHTS (lb)  
2
1
2
1
3
4
3
4
1
2
2
1
4
3
3
LEFT HAND UNIT  
4
RIGHT HAND UNIT  
RIGHT-HAND UNITS  
LEFT-HAND UNITS  
UNIT  
TOTAL  
WEIGHT  
CONFIGURATION  
42BVC  
1
2
3
4
1
2
3
4
No Heat  
With Heat  
52  
54  
51  
43  
47  
43  
47  
50  
54  
51  
55  
58  
61  
68  
71  
81  
83  
94  
95  
54  
52  
43  
47  
43  
47  
50  
54  
51  
55  
58  
61  
68  
71  
81  
83  
94  
94  
51  
200  
231  
202  
233  
243  
277  
247  
281  
289  
323  
351  
387  
436  
473  
522  
559  
06  
58  
65  
61  
65  
58  
61  
No Heat  
With Heat  
No Heat  
53  
55  
51  
55  
53  
51  
08  
58  
66  
62  
66  
58  
62  
63  
69  
61  
69  
63  
31  
10  
With Heat  
No Heat  
With Heat  
69  
81  
72  
81  
69  
72  
64  
70  
62  
70  
64  
62  
12  
70  
82  
73  
82  
70  
73  
No Heat  
With Heat  
No Heat  
74  
85  
72  
85  
74  
72  
16  
80  
98  
84  
98  
80  
84  
90  
108  
123  
139  
155  
172  
190  
86  
108  
123  
139  
155  
172  
190  
90  
86  
20  
With Heat  
No Heat  
With Heat  
95  
99  
95  
99  
110  
115  
131  
135  
106  
120  
125  
140  
110  
115  
131  
135  
106  
120  
125  
140  
30  
No Heat  
With Heat  
40  
NOTE: Unit weights (shown in pounds) 10% are based on the 8-row coil and 1 Hp motor.  
TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)  
Corner weights on pages 12 and 13 are for 8-row water filled coils. For a different number of rows, total unit weight  
can be determined by the following procedure:  
• Identify the number of rows and the size of the unit.  
• Determine the total weight of the unit from the Corner Weight tables.  
• From the table below, identify the correction factor (for size of unit and number of rows) and subtract this from the  
total weight.  
4 ROWS  
5 ROWS  
Correction Factors (lb)  
6 ROWS  
7 ROWS  
UNITS  
42BHC,BVC  
06  
08  
10  
12  
16  
20  
30  
40  
21  
21  
28  
28  
39  
46  
74  
98  
16  
16  
21  
21  
29  
35  
55  
74  
11  
11  
14  
14  
20  
23  
37  
49  
5
5
7
7
10  
12  
18  
25  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessory dimensions  
MIXING BOX  
B
B
W
W
2
2
TOP VIEWS  
4
A
1
2.4  
3
A
2.4  
H
H
2.4  
A
3
2.4  
1
A
4
C
C
BOTTOM/REAR INLET  
TOP/REAR INLET  
RIGHT HAND SIDE VIEWS  
NOTE: All dimensions in inches.  
DIMENSIONS (in.)  
42BHC,BVC  
UNIT SIZE  
H
18.5  
18.5  
20.25  
20.25  
20.25  
22.75  
31.0  
W
28  
28  
37  
37  
47  
48  
48  
48  
A
6
6
8
8
8
8
10  
10  
B
C
06  
08  
10  
12  
16  
20  
30  
40  
24  
24  
33  
33  
43  
44  
44  
44  
11  
11  
13  
13  
13  
13  
15  
15  
31.0  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MIXING BOX RAILS  
A
1
3
1
W
D
FRONT VIEW  
SIDE VIEW  
NOTE: All dimensions in inches.  
DIMENSIONS (in.)  
DIMENSIONS (in.)  
UNIT  
UNIT  
W
28  
28  
37  
37  
47  
48  
48  
62  
D
A
W
28  
28  
37  
37  
47  
48  
48  
62  
D
A
42BHC06  
42BHC08  
42BHC10  
42BHC12  
42BHC16  
42BHC20  
42BHC30  
42BHC40  
51.6  
51.6  
55.2  
55.2  
55.4  
57.8  
59.8  
63.0  
16.1  
16.1  
18.1  
18.1  
18.1  
18.1  
20.1  
20.1  
42BVC06  
42BVC08  
42BVC10  
42BVC12  
42BVC16  
42BVC20  
42BVC30  
42BVC40  
35.5  
35.5  
39.5  
39.5  
39.5  
41.5  
47.5  
47.5  
16.1  
16.1  
18.1  
18.1  
18.1  
18.1  
20.1  
20.1  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessory dimensions (cont)  
VALVE PACKAGES  
Basic — Basic valve package includes 2 or 3-way  
valves with balancing valves and 2 ball valvs.  
Deluxe — Deluxe valve package includes a circuit  
setter and a strainer in addition to the components  
listed under basic valve package.  
F
B
A
E
D
D
C
C
A
E
B
F
NOTE: All dimensions in inches.  
PIPING  
PACKAGE  
CLOSE  
OFF  
CONTROL VALVE  
SIZE  
A
B
C
D
E
F
Cv  
1/2 in.  
3/4 in.  
1 in.  
1/2 in.  
3/4 in.  
1 in.  
1/2 in.  
3/4 in.  
1 in.  
1/2 in.  
3/4 in.  
1 in.  
12.45  
12.71  
14.88  
12.99  
12.84  
14.72  
13.29  
13.59  
14.97  
13.41  
13.03  
14.77  
2.285  
3.156  
3.38  
1.823  
2.318  
2.774  
2.031  
2.219  
2.731  
5.805  
7.411  
8.247  
6.014  
7.313  
8.248  
15.25  
17.71  
20.81  
16.29  
17.34  
20.65  
16.09  
18.59  
20.90  
16.71  
17.53  
20.70  
7.41  
7.936  
9.6  
19.32  
21.02  
25.19  
7.41  
7.936  
9.6  
20.16  
21.4  
3.5  
5
8
4
5
25 psig  
20 psig  
17 psig  
25 psig  
20 psig  
17 psig  
60 psig  
60 psig  
60 psig  
60 psig  
60 psig  
60 psig  
2-way  
Normal Close Off  
Spring Return  
14.7  
3-way  
2-way  
3-way  
16.24  
19.38  
2.285  
3.156  
3.38  
15.54  
16.62  
19.47  
8
3.5  
4.6  
6.6  
3.8  
5.9  
9
High Close Off  
Power On/  
Power Off  
25.28  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING CONNECTION LOCATION DIAGRAM*  
CWR  
HWR  
D
C
CWS  
HWS  
B
A
Drain  
2(51)  
1-5/8(41)  
0
RH Tell-Tale  
LH Tell-Tale  
Use the table on the next page to determine the location of the piping  
connections. For example, on a size 20 unit with 4 rows and a right  
hand connection, the location of the chilled water supply line is deter-  
mined by G (6 in.) and B (74/5 in.).  
LEGEND  
CWR — Cold Water Return  
CWS — Cold Water Supply  
HWR — Hot Water Return  
HWS — Hot Water Supply  
Left Hand  
RH — Right Hand  
SO — Stub Out  
LH  
*Right-hand unit with re-heat coil shown.  
HEAD STUB OUT SIZES (in.)  
8 Row Coil SO 6 Row Coil SO 4 Row Coil SO Heating 1 or 2 SO  
42BHC,BVC  
UNIT SIZE  
Nominal  
Nominal  
0.75  
0.75  
0.75  
0.75  
1
Nominal  
0.75  
0.75  
0.75  
0.75  
1
Row Coil Nominal  
06  
08  
10  
12  
16  
20  
30  
40  
1
1
1
1
1
1
1.5  
1.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
1
1
1.5  
1.5  
1.5  
1.5  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessory dimensions (cont)  
COIL ROWS  
DIMENSIONS (in.)  
42BHC,BVC  
UNIT SIZE  
HEAT OPTIONS  
Cool  
Heat  
A
B
C
D
151/2  
E
7
F
7
G
H
0
1
2
0
1
2
0
0
1
2
0
1
2
0
0
4
31/2  
515  
/
16  
313  
/
1513  
/
79/16  
79/16  
16  
16  
06/08  
31/2  
61/8  
123/4  
6
8
4
151/2  
1513  
93/16  
93/4  
93/16  
93/4  
81/8  
313  
/
/
16  
16  
101/4  
7
79/16  
7
79/16  
51/8  
57/16  
171/8  
177/16  
515/  
16  
10/12  
73/4  
143/8  
6
8
51/8  
171/8  
177/16  
93/16  
93/4  
93/16  
93/4  
81/8  
527  
/
61  
101/4  
7
7
79/16  
LH 105/8  
RH 133/8  
57/16  
95/8  
95/8  
79/16  
4
1
12  
515/  
16  
2
0
177/16  
16  
73/4  
155/8  
LH 105/8  
RH 133/8  
57/16  
1113  
1113  
/
/
93/16  
93/16  
93/4  
16  
6
8
4
1
12  
81/8  
Re-heat  
211/  
16  
16  
2
0
0
177/16  
93/4  
101/4  
7
7
79/16  
LH 1115  
/
/
95/8  
95/8  
79/16  
16  
1
135/16  
515/  
16  
RH 1411  
51/2  
16  
2
0
201/16  
20  
713  
/
183/16  
16  
LH 1115  
RH 1411  
51/2  
/
/
1113  
1113  
/
/
93/16  
93/16  
93/4  
16  
16  
6
8
4
1
135/16  
81/8  
16  
16  
2
0
0
201/16  
93/4  
95/8  
95/8  
79/16  
101/4  
8
8
79/16  
LH 141/16  
RH 1813  
35/8  
1
167/16  
515/  
16  
/
16  
2
0
281/8  
30/40  
515  
/
265/16  
16  
LH 141/16  
1113  
1113  
/
/
103/16  
103/16  
93/4  
16  
6
1
167/16  
81/8  
RH 1813  
35/8  
/
16  
16  
2
0
0
1
2
0
1
2
0
0
1
2
0
1
2
0
0
1
2
0
1
2
0
0
1
2
0
1
2
0
0
1
2
0
1
2
0
281/8  
93/4  
8
4
101/4  
31/2  
61/8  
63/4  
61/8  
61/8  
63/4  
61/8  
61/8  
73/4  
83/8  
73/4  
73/4  
83/8  
73/4  
73/4  
73/4  
83/8  
73/4  
73/4  
83/8  
73/4  
73/4  
713  
87/16  
713  
713  
87/16  
713  
713  
515  
69/16  
515  
515  
69/16  
515  
515  
123/4  
133/8  
123/4  
123/4  
133/8  
123/4  
123/4  
143/8  
15  
515  
/
16  
211/  
16  
33/4  
47/8  
151/2  
211  
/
211  
/
7
81/8  
81/8 211/  
93/16  
101/4  
101/4 211  
16  
31/4  
16  
31/4  
313  
/
1513  
/
16  
16  
06/08  
10/12  
16  
31/2  
16  
6
8
4
151/2  
1513  
211  
/
211  
/
33/4  
47/8  
16  
31/4  
16  
31/4  
313  
/
/
16  
16  
/
16  
515  
/
16  
211/  
16  
51/8  
57/16  
51/8  
57/16  
171/8  
177/16  
171/8  
177/16  
211  
/
211  
/
7
81/8  
81/8 211  
93/16  
101/4  
33/4  
47/8  
/
16  
33/4  
47/8  
16  
31/4  
16  
31/4  
143/8  
143/8  
15  
6
8
4
211  
/
211  
/
16  
31/4  
16  
31/4  
143/8  
143/8  
155/8  
161/4  
155/8  
155/8  
161/4  
155/8  
155/8  
183/16  
101/4 211  
/
/
16  
515  
/
16  
211  
16  
51/8  
57/16  
171/8  
177/16  
211  
/
211/  
7
81/8  
81/8 211  
33/4  
47/8  
16  
16  
31/4  
31/4  
Pre-heat*  
/
16  
6
8
4
51/8  
57/16  
171/8  
177/16  
211  
/
211/  
93/16  
101/4  
33/4  
47/8  
16  
16  
31/4  
31/4  
101/4 211  
/
/
16  
/
515  
/
16  
211  
16  
16  
53/16  
51/2  
53/16  
51/2  
1813  
/
193/4  
201/16  
193/4  
201/16  
211  
/
211/  
7
81/8  
81/8 211/  
93/16  
101/4  
101/4 211  
33/4  
47/8  
16  
16  
31/4  
16  
/
/
183/16  
183/16  
31/4  
16  
20  
16  
16  
6
8
4
1813  
/
211  
/
211/  
33/4  
47/8  
16  
16  
31/4  
16  
/
/
/
183/16  
183/16  
265/16  
31/4  
16  
16  
16  
/
16  
515  
/
16  
211/  
16  
35/16  
35/8  
2615  
/
2713  
/
7
81/8  
81/8 211/  
93/16  
101/4  
33/4  
47/8  
16  
16  
/
/
265/16  
265/16  
281/8  
211  
/
211/  
16  
16  
16  
30/40  
31/4  
31/4  
211/  
16  
31/4  
16  
16  
6
8
35/16  
35/8  
2615  
/
2713  
/
33/4  
47/8  
16  
16  
/
/
265/16  
265/16  
281/8  
211  
/
16  
16  
31/4  
101/4 211/  
16  
16  
*Factory-installed option.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data  
Basic definitions  
UNIT HAND  
Unit hand — When facing the supply air outlet from the  
front of the unit (air blowing in your face), your right hand  
will be the right hand side of the unit and your left hand the  
left hand side of the unit.  
PIPING COMPONENTS  
CV FACTOR  
RATING*  
PSI  
SYMBOL/SKETCH  
DESCRIPTION  
1
3
/
/
4
F
2
MANUAL AIR VENT: Threaded brass needle valve  
with screwdriver slot for adjustment.  
Application — Body brazed into high point of heat-  
ing and cooling coils for bleeding air from coil. Stan-  
dard item on all hydronic coils (not used on steam  
or DX coils). Should not be used in lieu of main sys-  
tem air vents.  
N/A  
N/A  
400  
100  
AUTOMATIC AIR VENT: Nickel plated brass valve,  
fiber-disc type, with positive shut-off ballcheck and  
quick vent feature via knurled vent screw.  
Application — Optional replacement for manual air  
vent. Automatically passes minute quantities of air  
through the fiber discs which expand upon contact  
with water, completely sealing the valve. As air  
accumulates, the fiber discs dry and shrink, repeat-  
ing the cycle. Not recommended for removing large  
quantities of air encountered during initial start-up  
or subsequent draining and refilling. Should not be  
used in lieu of main system air vents.  
N/A  
N/A  
125  
240  
SWAGE: Copper tube end expanded to accept a  
copper tube of the same size for factory or field  
brazing.  
Application — Used where possible for all tubing  
joints for best joint integrity.  
N/A  
N/A  
300  
300  
200  
250  
CIRCUIT SETTER: Variable water flow balancing  
valve with manual adjustment knob, pointer, per-  
cent-open scale, memory stop and integral pres-  
sure read-out ports.  
2.12  
3.9  
Application — Used for close tolerance water flow  
balancing. Positive shut-off ball valve feature allows  
usage as combination balancing and shut-off valve.  
LEGEND  
Cv — Coefficient of Velocity  
DXDirect Expansion  
*Check all system component pressure ratings (coils, values, pumps,  
etc.) with manufacturer and any applicable local or national piping  
codes prior to specifying system pressure rating.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data (cont)  
PIPING COMPONENTS (cont)  
CV FACTOR  
RATING*  
PSI  
SYMBOL/SKETCH  
DESCRIPTION  
1
3
/
/
4
F
2
BALANCE VALVE: Variable water flow manual bal-  
ancing valve with screwdriver slot adjustment  
screw.  
Application — Often used in conjunction with test  
port fittings for water flow balancing. Balance by  
temperature differential or coil pressure drop  
(check specifications for service fittings required if  
balancing by pressure drop). May be used in 3-way  
valve bypass line to permit equal flow balancing.  
3.0  
8.9  
150  
200  
STRAINER: Y-type body with 50 mesh stainless  
steel screen.  
Application — Used for removal of small particles  
from system water during normal system operation.  
Should not be used in lieu of main system strain-  
ers. Strainer screen may have to be removed dur-  
ing initial high pressure system flushing during  
start-up. Screen should be removed and cleaned  
per normal maintenance schedule (provisions for  
strainer blow-down not provided).  
9.0  
19.0  
400  
400  
250  
200  
Clean  
Clean  
BALL VALVE: Manual balance and shut-off valve.  
Application — Used for unit isolation and water flow  
balancing. Without memory stop feature water bal-  
ance point must be marked by installer (if neces-  
sary). Check specifications for service fittings  
required when used for water balancing.  
4.0  
7.5  
LEGEND  
Cv — Coefficient of Velocity  
DXDirect Expansion  
*Check all system component pressure ratings (coils, values, pumps,  
etc.) with manufacturer and any applicable local or national piping  
codes prior to specifying system pressure rating.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING COMPONENTS (cont)  
RATING  
PSI  
CV FACTOR  
SYMBOL/SKETCH  
DESCRIPTION  
1
3
/
/
1
F
2
4
2-WAY MOTORIZED VALVE: Electric  
2-position flow control valve (open/closed).  
Normally closed body with manual override  
lever. Installed in supply line to unit.  
3.5  
3.5  
4.0  
3.8  
5.0  
SPRING RETURN  
4.6  
8.0  
Application — All standard control and valve  
packages are based upon normally closed  
valves (valve electrically powered open and  
closed by spring return when electric power  
removed). Manual override lever allows valve  
to be placed in the open position for second-  
ary (unit) flushing, constant water flow prior to  
start-up, etc. Manual override is automatically  
disengaged when valve is electrically acti-  
vated. Consult factory for normally open  
valve applications.  
300  
200  
6.6  
8.0  
9.0  
POWER ON/OFF  
5.0  
3-WAY MOTORIZED VALVE: Electric  
2-position flow control valve (closed to coil/  
open to bypass or open to coil/closed to  
bypass). Normally closed with manual over-  
ride lever. Installed in supply line to unit.  
Application — Same comments as 2-way  
motorized valve except with manual override  
lever engaged the valve is open to both ports  
and water flow will take the path of least resis-  
tance through the valve package (not neces-  
sarily 100% through the coil).  
SPRING RETURN  
5.9  
300  
200  
POWER ON/OFF  
LEGEND  
Cv — Coefficient of Velocity  
DXDirect Expansion  
NOTES:  
1. Motorized spring return 2-way valves have a maximum close-off differential of 25 psi.  
2. Motorized spring return 3-way valves have a maximum close-off differential of 25 psi.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection procedure  
This selection procedure provides a guide to determine  
unit performance of the 42BHC, BVC units. Capacity  
tables (in Performance Data) are based on nominal cfm.  
Correction factors are provided for other operating condi-  
tions as explained in the following selection example.  
For applications outside the range provided in this  
catalog, please consult the factory.  
FORMULAS:  
TC = TCb x Ct x Et  
SC = SCb x Cs x Es  
Where:  
Cs = Sensible Airflow Correction Factor  
Ct = Total Airflow Correction Factor  
Es = Sensible Elevation Correction Factor  
Et = Total Elevation Correction Factor  
SC = Sensible Capacity  
SC = SCb x Cs x Es  
= 34.2 x .96 x 1.00  
= 32.83 MBtuh  
a) Calculate water pressure drop (or refer to the Water  
Pressure Drop for Cv Factor and Water Flow Rate  
table on page 33). From the Cv Factor by Coil and  
Unit Size table on page 32, find the Cv value for  
unit size 16 with four rows.  
Cv = 7.2  
P = [GPM/(0.658 x Cv)]2  
= [7.0/(0.658 x 7.2)]2  
= 2.18 feet of H2O  
b) For selections other than those listed here, please  
contact the factory.  
IV Determine motor.  
To determine motor and drive selection requirements  
and obtain the cfm for a specific application, the  
total static pressure (TSP) for that application must be  
determined.  
The TSP is the sum of the internal static pressure  
(ISP) and the external static pressure (ESP) measured in  
inches of water column. Internal static pressure is the  
sum of the static resistance of the unit’s components  
— the cabinet, coil and filter. The ESP is the static  
resistance of the unit’s external components, including,  
but not limited to, ductwork, grilles and additional  
filtration. For non-ducted applications, the ESP is  
0 in. wg.  
After the TSP has been calculated (see the following  
example), use the motor horsepower table on pages 30  
and 31 to determine actual horsepower (hp) for the belt  
drive unit. Horsepower offerings are limited to 1/4, 1/3,  
1/2, 3/4, 1, 11/2, 2, 3 and 5.  
The standard selection is the nearest offering above  
the actual hp shown in the table.  
SCb = Base Sensible Capacity from Base Cooling Capaci-  
ties by gpm charts  
TC = Total Capacity  
TCb = Base Total Capacity from Base Cooling Capacities  
by gpm charts  
EXAMPLE:  
I Rate unit performance.  
To rate the performance at sea level for a 42BHC16  
unit with a four-row coil at 80 F/67 F EAT, 45 F EWT,  
7 gpm water flow, and 1500 cfm:  
a) Enter the Base Cooling Capacities by Gpm, 4-Row  
Capacity Units table at 80 F/67 F EAT and  
45 F EWT.  
b) Locate the appropriate row for unit size 16 and  
7 gpm.  
Record the tabulated base performance.  
TCb = 42.0 MBtuh  
SCb = 34.2 MBtuh  
Using the TSP of the table, match the unit size with  
the cfm row to determine the correct motor for the  
specific application. Drive sheaves and the required  
belt assembly will be provided to meet specific design  
requirements. Drive sheaves are set at the factory.  
Calculate the hp and drive selection required to deliv-  
er 1500 cfm on a 42BHC16 unit equipped with a  
4-row hydronic cooling coil and a 2-in. pleated filter in  
a ducted application at .38 in. ESP, including duct and  
grille losses.  
T = 12.0 F  
c) Divide CFM Actual by CFM Nominal to determine  
Cfm Ratio.  
Cfm Ratio = 1500/1600 =.9375  
II Select CFM correction factors.  
Select the Cfm correction factors, Ct and Cs, from the  
Airflow Correction Factors table. (Interpolation may be  
required.)  
Ct = .9625  
Cs = .96  
Select the elevation correction factors, Et and Es, from  
the Elevation Correction Factors table. (No correction  
necessary in this example, unit is at sea level.)  
Et = 1.00  
Es = 1.00  
Using the Component Static Resistance table on  
page 32, the ISP is calculated as follows:  
Cabinet  
4-row Wet Coil  
2-in. Pleated Filter  
ISP  
ESP  
TSP  
.09-in. wg  
.30-in. wg  
.12-in. wg  
.51-in. wg  
.38-in. wg  
.89-in. wg  
III Calculate actual performance.  
TC = TCb x Ct x Et  
= 42.0 x .9625 x 1.00  
= 40.42 MBtuh  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data  
42BHC,BVC AIRFLOW CORRECTION FACTORS  
DIRECT EXPANSION (DX) CORRECTION FACTORS  
CFM RATIO  
CORRECTION FACTOR  
% OF  
TOTAL (Ct)  
SENSIBLE (Cs)  
(Actual/Base)  
1.40  
1.35  
1.30  
1.25  
1.20  
1.15  
1.10  
1.05  
1.00  
0.95  
0.90  
0.85  
0.80  
0.75  
0.70  
0.65  
0.60  
0.55  
0.50  
0.45  
0.40  
0.35  
0.30  
0.25  
NOMINAL CFM  
Total  
Sensible  
0.93  
0.96  
1.00  
1.04  
1.25  
1.22  
1.19  
1.16  
1.13  
1.10  
1.07  
1.04  
1.00  
0.97  
0.94  
0.90  
0.86  
0.82  
0.78  
0.74  
0.70  
0.66  
0.62  
0.58  
0.53  
0.48  
0.43  
0.38  
1.26  
1.23  
1.20  
1.17  
1.14  
1.11  
1.08  
1.04  
1.00  
0.97  
0.93  
0.89  
0.85  
0.81  
0.77  
0.72  
0.67  
0.62  
0.57  
0.52  
0.47  
0.42  
0.38  
0.33  
80  
90  
100  
110  
120  
0.95  
0.97  
1.00  
1.02  
1.05  
1.08  
Consult factory for values outside of table.  
DX Total Capacity (MBtuh) = Base Et x Total Correction Factor  
DX Sensible Capacity (MBtuh) = Base Es x Sensible Correction Factor  
% of Nominal Cfm = Actual Cfm (from Fan Performance table)  
÷ Nominal Cfm  
ALTITUDE COOLING CORRECTION FACTORS  
ELEVATION (ft)  
TOTAL HEAT (Et)  
SENSIBLE HEAT (Es)  
1000  
2000  
3000  
4000  
5000  
6000  
0.99  
0.98  
0.97  
0.96  
0.94  
0.93  
0.96  
0.93  
0.89  
0.86  
0.83  
0.80  
7000  
8000  
9000  
0.92  
0.91  
0.90  
0.77  
0.75  
0.73  
NOTE: Use Sensible Heat correction factors when calculating heating  
capacity.  
42BHC,BVC HOT WATER CAPACITY CORRECTION FACTORS  
ENTERING WATER TEMPERATURE (F)  
ENTERING AIR  
TEMPERATURE (F)  
100  
110  
120  
130  
140  
150  
160  
170  
180  
190  
200  
50  
55  
60  
65  
70  
75  
80  
0.455  
0.409  
0.363  
0.318  
0.272  
0.227  
0.182  
0.545  
0.500  
0.455  
0.409  
0.363  
0.318  
0.272  
0.636  
0.591  
0.545  
0.500  
0.455  
0.409  
0.363  
0.727  
0.682  
0.636  
0.591  
0.545  
0.500  
0.455  
0.818  
0.773  
0.727  
0.682  
0.636  
0.591  
0.545  
0.909  
0.864  
0.818  
0.773  
0.727  
0.682  
0.636  
1.000  
0.955  
0.909  
0.864  
0.818  
0.773  
0.727  
1.091  
1.045  
1.000  
0.955  
0.909  
0.864  
0.818  
1.182  
1.136  
1.091  
1.045  
1.000  
0.955  
0.909  
1.273  
1.227  
1.182  
1.136  
1.091  
1.045  
1.000  
1.364  
1.318  
1.273  
1.227  
1.182  
1.136  
1.091  
NOTES:  
1. Leaving air temperature not to exceed 104 F with standard motor.  
2. Base capacity ratings based on 180 F entering water temperature  
and 70 F entering air temperature.  
3. Hot Water Heating Capacity (MBtuh) = Rated Heating Capacity x  
Hot Water Capacity Correction Factor x Sensible Airflow Correc-  
tion Factor.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
42BHC, BVC NOMINAL COOLING CAPACITIES  
42BHC,BVC NOMINAL HEATING CAPACITIES  
UNIT SIZE  
HEATING CAPACITY  
(MBtuh)  
COOLING*  
NOMINAL CFM  
ROWS  
42BHC,BVC  
UNIT SIZE  
42BHC,BVC  
NOMINAL  
CFM  
COIL  
ROWS  
EWT  
(F)  
Total  
Capacity  
(MBtuh)  
Sensible  
Capacity  
(MBtuh)  
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
27.0  
46.9  
27.0  
46.9  
27.0  
46.9  
38.5  
68.5  
48.0  
87.7  
58.7  
104.9  
78.0  
149.2  
92.3  
182.4  
06  
600  
40  
45  
50  
40  
45  
50  
23.3  
17.9  
12.8  
16.0  
13.8  
12.0  
08  
10  
12  
16  
20  
30  
40  
800  
1000  
1200  
1600  
2000  
3000  
4000  
4
6
31.0  
24.5  
18.0  
19.8  
17.0  
14.5  
06  
08  
10  
600  
800  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
33.8  
26.7  
19.4  
21.2  
18.1  
15.2  
8
4
28.4  
21.9  
15.3  
20.0  
17.5  
15.3  
38.4  
30.3  
22.5  
25.1  
21.7  
18.6  
6
42.6  
33.7  
24.7  
27.2  
23.3  
19.8  
8
4
NOTES:  
40.5  
31.6  
23.4  
27.3  
23.7  
20.6  
1. Ratings are based on 180 F Entering Water Temperature (EWT) and 70 F  
Entering Air Temperature (EAT).  
2. Leaving-air temperature is not to exceed 104 F with the standard motor.  
Consult the factory for higher temperature motor applications.  
3. For information on four and six-row heating coil capacities and applications,  
consult the factory.  
52.2  
41.7  
31.2  
33.3  
28.7  
24.5  
1000  
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4. For all application ratings, use the quick-selection ratings provided in this  
catalog, or contact the factory.  
57.7  
46.4  
34.6  
36.0  
31.0  
26.2  
45.4  
35.5  
26.5  
31.2  
27.2  
23.8  
59.6  
47.4  
35.5  
38.4  
33.2  
28.5  
12  
1200  
1600  
2000  
3000  
4000  
66.6  
53.3  
39.9  
42.0  
36.1  
30.7  
59.7  
46.4  
34.4  
41.2  
35.9  
31.4  
78.7  
62.6  
46.8  
50.9  
44.1  
37.8  
16  
89.0  
71.3  
53.3  
56.0  
48.3  
41.0  
75.2  
59.0  
44.1  
51.6  
45.1  
39.5  
99.0  
78.7  
59.0  
63.8  
55.2  
47.4  
20  
30  
40  
111.8  
89.9  
67.6  
70.3  
60.6  
51.6  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
112.5  
87.6  
65.0  
77.6  
67.6  
59.1  
148.5  
117.8  
88.1  
95.8  
82.8  
71.1  
168.0  
135.0  
101.2  
105.5  
91.0  
77.4  
157.7  
123.6  
92.6  
106.7  
92.9  
81.1  
204.0  
162.6  
122.3  
130.5  
112.7  
96.7  
230.1  
185.6  
140.2  
143.5  
123.8  
105.2  
LEGEND  
Entering Water Temperature  
MBtuh — Capacity (Btuh in thousands)  
EWT  
*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10  
degrees F.  
NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning &  
Refrigeration Institute).  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BHC,BVC 4-ROW COOLING CAPACITY (by Gpm)  
75 F DB/ 63 F WB  
45 F EWT  
TCb SCb T TCb SCb T TCb SCb T  
80 F DB/67 F WB  
45 F EWT  
85 F DB/71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
GPM  
40 F EWT  
50 F EWT  
40 F EWT  
TCb  
50 F EWT  
TCb SCb T  
40 F EWT  
TCb  
50 F EWT  
SCb T TCb SCb  
T  
SCb T  
TCb SCb T  
SCb T  
TCb  
3
4
5
10.9 16.3 13.2 9.0 13.5 12.1 7.2 10.7 10.7 13.0 19.5 14.5 11.1 16.6 13.4 9.1 13.7 12.3 15.3 22.9 15.7 13.3 19.9 14.6 11.2 16.9 13.5  
9.1 18.3 14.0 7.5 15.0 12.7 5.7 11.5 11.5 11.0 22.0 15.5 9.3 18.6 14.1 7.6 15.2 12.8 13.1 26.2 16.9 11.3 22.6 15.5 9.5 18.9 14.2  
06  
08  
7.9 19.7 14.6 6.4 16.1 13.1 5.0 12.5 11.6 9.6  
23.9 16.3 8.0 20.1 14.7 6.5 16.2 13.2 11.4 28.5 17.8 9.8  
24.5 16.3 8.2 20.4 14.8  
3
4
5
6
12.2 18.3 16.0 10.0 15.0 15.0 8.4 12.7 12.7 14.5 21.7 17.4 12.4 18.7 16.3 10.2 15.2 15.2 16.9 25.4 18.8 14.8 22.2 17.7 12.6 19.0 16.6  
10.4 20.8 17.0 8.6 17.2 15.6 6.9 13.8 13.8 12.4 24.9 18.6 10.6 21.1 17.2 8.7 17.4 15.8 14.6 29.2 20.2 12.7 25.4 18.8 10.7 21.4 17.4  
9.0 22.6 17.7 7.4 18.6 16.1 5.8 14.5 14.5 10.8 27.1 19.5 9.2 22.9 17.9 7.5 18.7 16.3 12.9 32.1 21.3 11.1 27.7 19.6 9.3 23.2 18.0  
8.0 23.9 18.3 6.5 19.5 16.5 5.0 14.9 14.9 9.6 28.9 20.3 8.1 24.3 18.4 6.6 19.7 16.7 11.5 34.4 22.1 9.8  
29.5 20.3 8.2 24.6 18.5  
3
4
5
6
15.4 23.1 20.2 12.7 19.0 19.0 10.6 16.0 16.0 18.2 27.2 22.0 15.6 23.4 20.6 12.8 19.2 19.2 21.1 31.7 23.7 18.5 27.8 22.3 15.8 23.8 21.0  
13.2 26.4 21.6 11.0 21.9 19.8 8.8 17.5 17.5 15.7 31.5 23.6 13.4 26.8 21.8 11.1 22.1 20.1 18.4 36.9 25.5 16.0 32.0 23.8 13.6 27.1 22.1  
11.5 28.8 22.6 9.5 23.7 20.5 7.4 18.5 18.5 13.8 34.6 24.9 11.7 29.2 22.8 9.6 23.9 20.8 16.3 40.7 27.0 14.1 35.2 24.9 11.8 29.6 22.9  
10.2 30.6 23.4 8.4 25.1 21.1 6.4 19.1 19.1 12.3 36.9 25.8 10.4 31.1 23.5 8.4 25.3 21.3 14.6 43.8 28.2 12.6 37.7 25.8 10.5 31.5 23.6  
10  
12  
16  
20  
3
4
5
6
16.4 24.6 22.8 13.8 20.7 20.7 11.6 17.4 17.4 19.3 28.9 24.7 16.7 25.0 23.3 14.0 20.9 20.9 22.3 33.5 26.5 19.6 29.5 25.1 16.9 25.4 23.8  
14.2 28.4 24.3 11.9 23.7 22.4 9.7 19.3 19.3 16.8 33.6 26.5 14.4 28.8 24.6 11.6 23.2 23.2 19.6 39.2 28.5 17.1 34.2 26.7 14.5 29.1 25.0  
12.4 31.1 25.4 10.3 25.8 23.2 8.2 20.5 20.5 14.8 37.1 27.8 12.6 31.5 25.7 10.4 26.0 23.6 17.4 43.6 30.1 15.1 37.8 28.0 12.7 31.9 25.9  
11.1 33.2 26.3 9.1 27.3 23.9 7.1 21.4 21.4 13.3 39.8 28.9 11.2 33.7 26.5 9.2 27.5 24.2 15.6 46.9 31.4 13.5 40.5 29.0 11.3 34.0 26.7  
5
7
14.2 35.4 31.4 11.7 29.3 29.3 9.9 24.7 24.7 16.8 41.9 34.2 14.4 36.1 32.0 11.9 29.7 29.7 19.5 48.8 36.8 17.1 42.8 34.7 14.7 36.6 32.6  
11.8 41.3 33.8 9.8 34.3 31.0 7.8 27.4 27.4 14.1 49.4 37.1 12.0 42.0 34.2 9.9 34.6 31.5 16.6 58.0 40.1 14.4 50.3 37.3 12.1 42.5 34.6  
10.1 45.3 35.5 8.3 37.2 32.2 6.4 28.9 28.9 12.1 54.4 39.1 10.2 46.0 35.8 8.3 37.5 32.6 14.3 64.4 42.5 12.3 55.5 39.2 10.3 46.5 36.0  
8.7 48.1 36.7 7.1 39.3 33.0 5.4 29.9 29.9 10.6 58.3 40.7 8.9 48.8 36.9 7.2 39.5 33.3 12.6 69.3 44.4 10.8 59.4 40.6 9.0 49.5 37.0  
9
11  
5
7
9
16.5 41.3 37.9 13.8 34.6 34.6 11.6 29.1 29.1 19.4 48.6 41.2 16.8 42.0 38.7 14.0 35.0 35.0 22.5 56.3 44.2 19.8 49.5 41.8 17.0 42.6 39.5  
13.9 48.5 40.8 11.6 40.5 37.6 9.3 32.7 32.7 16.5 57.6 44.6 14.0 49.2 41.4 11.7 40.8 38.3 19.2 67.4 48.1 16.7 58.6 45.0 14.2 49.7 41.9  
11.9 53.5 42.9 9.8 44.1 39.1 7.7 34.8 34.8 14.2 64.0 47.1 12.0 54.1 43.3 9.9 44.4 39.6 16.7 75.2 51.0 14.5 65.0 47.3 12.2 54.7 43.6  
11 10.4 57.1 44.4 8.5 46.8 40.1 6.6 36.1 36.1 12.5 68.6 48.9 10.5 57.8 44.7 8.5 47.0 40.6 14.8 81.3 53.3 12.7 69.9 49.0 10.6 58.4 44.9  
7
9
15.9 55.6 55.6 13.9 48.5 48.5 11.7 41.0 41.0 19.0 66.5 59.7 16.2 56.8 56.8 14.1 49.4 49.4 22.0 77.0 64.0 19.5 68.2 61.0 16.5 57.9 57.9  
14.6 65.5 58.6 12.1 54.4 54.4 10.2 45.8 45.8 17.2 77.4 63.7 14.8 66.8 59.8 12.2 55.1 55.1 20.0 90.1 68.5 17.6 79.0 64.7 15.1 67.8 60.9  
30  
40  
11 13.1 72.3 61.3 11.0 60.5 56.6 8.9 49.1 49.1 15.6 85.9 67.0 13.4 73.5 62.2 11.1 61.1 57.7 18.3 100.5 72.2 15.9 87.6 67.6 13.5 74.5 63.1  
14 11.4 79.9 64.5 9.4 66.1 58.8 7.5 52.3 52.3 13.7 95.6 70.7 11.6 81.1 65.1 9.5 66.6 59.7 16.1 112.5 76.6 13.9 97.4 71.1 11.7 82.1 65.7  
17 11.4 85.5 66.8 8.3 70.2 60.5 6.4 54.5 54.5 12.1 102.8 73.6 10.2 86.8 67.3 8.3 70.7 61.2 14.3 121.8 80.1 12.3 104.9 73.8 10.3 87.9 67.7  
11 16.4 90.5 79.5 13.5 74.4 74.4 11.4 62.5 62.5 19.4 106.8 86.4 16.7 91.8 80.8 13.7 75.1 75.1 22.6 124.1 92.8 19.7 108.5 87.4 16.9 92.8 82.1  
14 14.4 100.9 83.7 12.0 84.0 76.8 9.6 67.4 67.4 17.1 119.9 91.4 14.6 102.1 84.6 12.1 84.6 78.2 20.0 140.2 98.6 17.4 121.8 92.0 14.7 103.2 85.6  
17 12.8 108.7 87.0 10.6 89.7 79.2 8.3 70.6 70.6 15.3 129.9 95.4 12.9 110.0 87.6 10.6 90.2 80.2 18.0 152.6 103.2 15.5 132.0 95.7 13.1 111.1 88.3  
21 11.1 116.5 90.2 9.1 95.5 81.5 7.0 73.6 73.6 13.3 140.0 99.4 11.2 118.0 90.7 9.1 95.9 82.3 15.8 165.5 108.1 13.6 142.4 99.4 11.3 119.2 91.1  
25  
9.8 122.3 92.7 8.0 99.8 83.2 6.0 75.6 75.6 11.8 147.9 102.7 9.9 124.0 93.0 8.0 100.3 84.0 14.1 175.8 112.1 12.0 150.4 102.4 10.0 125.5 93.3  
LEGEND  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
DB  
Dry Bulb Temperature  
EWT — Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb  
TCb  
WB  
T  
Base Sensible Capacity at Nominal Cfm  
Base Total Capacity at Nominal Cfm  
Wet Bulb Temperature  
Change in Water Temperature (F)  
42BHC,BVC 6-ROW COOLING CAPACITY (by Gpm)  
75 F DB/63 F WB  
45 F EWT  
80 F DB/67 F WB  
45 F EWT  
85 F DB/71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
GPM  
T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb  
3
4
5
13.5 20.2 15.4 11.1 16.7 13.9 8.8 13.2 12.5 16.1 24.2 16.9 13.7 20.6 15.5 11.2 16.8 14.0 19.0 28.4 18.3 16.5 24.7 16.9 13.9 20.8 15.5  
11.3 22.6 16.4 9.2 18.5 14.6 7.2 14.4 12.9 13.6 27.2 18.2 11.5 23.0 16.4 9.3 18.6 14.7 16.1 32.2 19.8 13.9 27.9 18.1 11.7 23.4 16.4  
9.7 24.2 17.1 7.9 19.7 15.1 6.1 15.1 13.3 11.7 29.2 19.1 9.9 24.6 17.1 7.9 19.9 15.2 13.9 34.8 20.9 12.0 30.0 19.0 10.0 25.1 17.1  
06  
3
4
5
6
15.3 22.9 18.7 12.8 19.2 17.2 10.2 15.3 15.3 18.1 27.2 20.4 15.5 23.3 18.9 12.9 19.3 17.4 21.2 31.8 22.0 18.5 27.7 20.5 15.7 23.6 19.1  
13.0 26.0 20.0 10.7 21.4 18.1 8.3 16.5 16.5 15.5 31.1 22.0 13.2 26.4 20.1 10.8 21.6 18.3 18.3 36.5 23.8 15.8 31.7 22.0 13.4 26.7 20.2  
11.3 28.1 20.9 9.2 23.1 18.7 7.2 18.0 16.7 13.5 33.8 23.1 11.4 28.6 21.0 9.3 23.2 18.9 16.0 40.0 25.2 13.8 34.6 23.1 11.6 29.0 21.0  
9.9 29.7 21.6 8.1 24.3 19.2 6.3 18.8 17.0 12.0 35.9 24.0 10.1 30.2 21.6 8.2 24.5 19.3 14.2 42.6 26.2 12.2 36.7 23.9 10.2 30.7 21.6  
08  
4
5
6
8
16.2 32.3 25.0 13.4 26.8 22.7 10.4 20.8 20.8 19.2 38.5 27.4 16.4 32.7 25.1 13.5 26.9 22.9 22.5 45.0 29.6 19.5 39.1 27.4 16.5 33.1 25.2  
14.1 35.3 26.3 11.6 29.0 23.6 9.1 22.8 21.1 16.9 42.3 29.0 14.3 35.8 26.3 11.7 29.2 23.8 19.9 49.8 31.5 17.2 43.0 28.9 14.5 36.2 26.3  
12.5 37.5 27.2 10.2 30.6 24.3 7.9 23.8 21.5 15.0 45.1 30.2 12.7 38.1 27.2 10.3 30.8 24.4 17.8 53.3 32.9 15.4 46.1 30.0 12.9 38.6 27.2  
10.1 40.5 28.6 8.2 32.9 25.3 6.3 25.3 22.1 12.3 49.1 31.9 10.3 41.3 28.5 8.3 33.2 25.3 14.6 58.5 35.0 12.6 50.3 31.7 10.5 41.9 28.4  
10  
12  
16  
6
8
10  
13.7 41.0 30.8 11.2 33.6 27.7 8.8 26.5 24.8 16.4 49.1 33.9 13.8 41.5 30.9 11.3 33.8 27.9 19.3 57.8 36.8 16.6 49.9 33.8 14.0 41.9 30.9  
11.2 44.7 32.4 9.1 36.4 28.9 7.1 28.2 25.5 13.5 53.9 35.9 11.3 45.4 32.4 9.2 36.7 29.0 16.0 63.9 39.3 13.8 55.0 35.8 11.5 46.0 32.4  
9.4 47.1 33.5 7.7 38.3 29.7 5.9 29.4 26.0 11.5 57.3 37.4 9.6 48.0 33.5 7.7 38.6 29.7 13.6 68.2 41.1 11.7 58.6 37.2 9.8 48.8 33.4  
7
9
14.6 51.2 39.6 12.1 42.3 35.9 9.4 32.8 32.8 17.5 61.1 43.5 14.8 51.9 39.8 12.2 42.6 36.3 20.5 71.7 47.0 17.8 62.1 43.5 15.0 52.4 40.0  
12.5 56.1 41.7 10.2 46.0 37.4 8.0 36.0 33.3 15.0 67.4 46.0 12.6 56.9 41.8 10.3 46.2 37.6 17.7 79.5 50.1 15.3 68.7 45.9 12.8 57.6 41.8  
11 10.8 59.5 43.2 8.8 48.5 38.5 6.8 37.6 34.0 13.1 71.8 47.9 11.0 60.5 43.2 8.9 48.9 38.6 15.5 85.2 52.4 13.3 73.4 47.7 11.1 61.3 43.2  
13  
9.5 62.0 44.4 7.8 50.5 39.3 6.0 38.8 34.5 11.6 75.3 49.4 9.7 63.2 44.3 7.8 50.9 39.4 13.8 89.6 54.2 11.8 76.9 49.1 9.9 64.2 44.2  
7
9
17.0 59.6 47.6 14.2 49.5 43.4 11.2 39.2 39.2 20.2 70.7 52.0 17.2 60.3 47.9 14.2 49.8 44.0 23.6 82.5 56.0 20.5 71.7 52.1 17.4 60.8 48.2  
14.6 65.9 50.2 12.0 54.2 45.3 9.2 41.5 41.5 17.5 78.7 55.2 14.8 66.6 50.4 12.1 54.5 45.7 20.5 92.4 59.8 17.8 79.9 55.1 14.9 67.3 50.5  
20  
11 12.8 70.4 52.2 10.5 57.6 46.7 8.2 45.0 41.6 15.4 84.6 57.6 13.0 71.3 52.2 10.5 57.9 47.0 18.1 99.8 62.7 15.6 86.1 57.4 13.1 72.1 52.2  
13 11.4 73.8 53.7 9.3 60.2 47.8 7.2 46.6 42.3 13.7 89.0 59.5 11.5 74.9 53.6 9.3 60.5 48.0 16.2 105.3 64.9 14.0 90.8 59.2 11.7 75.9 53.6  
15 10.2 76.5 54.9 8.3 62.2 48.7 6.4 47.9 42.8 12.3 92.6 61.0 10.4 77.8 54.8 8.4 62.6 48.8 14.7 110.2 67.0 12.6 94.6 60.7 10.5 78.9 54.7  
11 16.3 89.4 71.5 13.5 74.4 65.3 10.7 59.0 59.0 19.3 106.2 78.1 16.5 90.6 72.1 13.6 75.0 66.2 22.5 124.0 84.3 19.6 107.9 78.4 16.7 91.6 72.7  
14 14.1 98.9 75.5 11.6 81.5 68.2 8.9 62.5 62.5 16.9 118.2 83.0 14.3 100.2 75.8 11.7 82.0 68.8 19.8 138.9 90.0 17.2 120.3 82.9 14.5 101.3 76.0  
17 12.4 105.8 78.5 10.2 86.7 70.3 8.0 67.8 62.7 15.0 127.2 86.7 12.6 107.3 78.6 10.3 87.2 70.8 17.6 150.0 94.3 15.2 129.6 86.4 12.8 108.6 78.7  
21 10.7 112.5 81.5 8.7 91.7 72.4 6.8 71.0 63.9 12.9 135.8 90.4 10.9 114.3 81.4 8.8 92.3 72.7 15.4 161.2 98.8 13.2 138.8 89.9 11.0 115.9 81.3  
30  
40  
17 15.6 132.8 101.1 12.9 109.4 91.3 10.2 86.6 82.1 18.7 158.6 111.1 15.8 134.3 101.4 12.9 109.9 92.0 21.9 185.9 120.3 18.9 160.8 110.8 15.9 135.4 101.6  
21 13.6 142.7 105.4 11.1 116.8 94.3 8.7 91.3 83.9 16.3 171.3 116.4 13.8 144.5 105.4 11.2 117.3 94.8 19.2 201.8 126.5 16.6 174.2 115.8 13.9 145.9 105.3  
25 12.0 150.0 108.6 9.8 122.3 96.6 7.6 94.8 85.3 14.5 180.8 120.4 12.2 152.2 108.5 9.8 123.0 97.0 17.1 213.8 131.4 14.7 184.4 119.7 12.3 154.1 108.3  
LEGEND  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
DB  
Dry Bulb Temperature  
EWT  
Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb  
TCb  
WB  
T  
Base Sensible Capacity at Nominal Cfm  
Base Total Capacity at Nominal Cfm  
Wet Bulb Temperature  
Change in Water Temperature (F)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
42BHC,BVC 8-ROW COOLING CAPACITY (by Gpm)  
75 F DB / 63 F WB  
45 F EWT  
80 F DB / 67 F WB  
45 F EWT  
85 F DB / 71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
GPM  
T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb T TCb SCb  
4
5
6
7
11.8 23.6 17.0 9.7 19.4 15.2 7.6 15.1 13.4 14.2 28.4 18.9 12.1 24.1 17.1 9.8 19.6 15.3 16.8 33.6 20.6 14.6 29.2 18.8 12.3 24.6 17.1  
10.2 25.6 17.9 8.4 20.9 15.8 6.4 16.1 13.8 12.4 30.9 20.0 10.5 26.2 17.9 8.5 21.2 15.9 14.7 36.7 21.9 12.7 31.9 19.9 10.7 26.7 17.9  
9.0 27.0 18.6 7.3 22.0 16.3 5.6 16.8 14.1 10.9 32.7 20.8 9.2 27.6 18.5 7.4 22.3 16.3 13.0 39.0 22.9 11.3 33.8 20.6 9.4 28.3 18.5  
8.0 28.0 19.0 6.5 22.8 16.7 5.0 17.3 14.3 9.7 34.1 21.4 8.2 28.7 19.0 6.6 23.1 16.7 11.6 40.7 23.6 10.1 35.2 21.2 8.4 29.4 18.9  
06  
08  
4
5
6
7
8
13.6 27.2 20.8 11.3 22.5 18.8 9.0 18.0 17.0 16.2 32.5 22.8 13.8 27.7 20.9 11.4 22.8 19.0 19.0 38.1 24.7 16.6 33.2 22.9 14.1 28.1 21.0  
11.9 29.9 21.9 9.8 24.6 19.7 7.7 19.3 17.5 14.4 35.9 24.2 12.2 30.4 22.0 9.9 24.8 19.8 16.9 42.3 26.4 14.7 36.7 24.2 12.4 30.9 22.0  
10.6 31.9 22.8 8.7 26.1 20.3 6.7 20.2 17.9 12.8 38.4 25.3 10.8 32.5 22.8 8.8 26.4 20.4 15.2 45.5 27.7 13.1 39.4 25.2 11.0 33.1 22.8  
9.5 33.4 23.5 7.8 27.2 20.8 6.0 21.0 18.2 11.5 40.4 26.2 9.7 34.1 23.5 7.9 27.6 20.9 13.7 47.9 28.7 11.9 41.5 26.1 9.9 34.8 23.5  
8.6 34.6 24.1 7.0 28.2 21.2 5.4 21.6 18.4 10.5 41.9 26.9 8.8 35.4 24.0 7.1 28.5 21.2 12.5 50.0 29.6 10.8 43.2 26.7 9.0 36.1 24.0  
6
7
8
9
13.3 40.0 28.6 10.9 32.8 25.5 8.5 25.5 22.5 16.0 48.1 31.7 13.6 40.7 28.6 11.0 33.1 25.6 18.9 56.8 34.6 16.4 49.2 31.6 13.8 41.3 28.6  
12.0 42.1 29.6 9.8 34.4 26.2 7.6 26.5 22.9 14.5 50.8 32.9 12.3 42.9 29.5 9.9 34.7 26.2 17.2 60.2 36.0 14.9 52.1 32.7 12.5 43.6 29.4  
10.9 43.7 30.3 8.9 35.6 26.7 6.8 27.3 23.2 13.2 52.9 33.8 11.2 44.6 30.3 9.0 36.0 26.7 15.7 62.8 37.2 13.6 54.4 33.6 11.4 45.5 30.1  
10.0 45.0 31.0 8.1 36.6 27.2 6.2 28.0 23.5 12.1 54.6 34.6 10.2 46.0 30.8 8.2 37.1 27.2 14.5 65.1 38.1 12.5 56.2 34.4 10.4 47.0 30.7  
10  
12  
16  
20  
7
9
11  
13  
13.2 46.4 33.6 10.9 38.0 30.0 8.5 29.7 26.5 15.9 55.7 37.1 13.5 47.1 33.6 10.9 38.3 30.1 18.8 65.7 40.5 16.3 56.9 37.0 13.6 47.8 33.5  
11.1 50.1 35.3 9.1 40.8 31.2 7.0 31.5 27.3 13.5 60.5 39.2 11.3 51.0 35.2 9.2 41.2 31.2 15.9 71.7 43.0 13.8 62.0 39.0 11.5 51.9 35.1  
9.6 52.6 36.4 7.8 42.8 32.0 5.9 32.7 27.8 11.6 63.8 40.7 9.8 53.7 36.3 7.9 43.2 32.0 13.8 76.1 44.8 11.9 65.5 40.4 10.0 54.8 36.1  
8.4 54.4 37.2 6.8 44.2 32.6 5.2 33.6 28.1 10.2 66.3 41.8 8.6 55.6 37.1 6.9 44.7 32.6 12.2 79.1 46.2 10.5 68.2 41.5 8.7 56.9 37.0  
9
13.6 61.0 44.5 11.1 50.1 39.7 8.7 39.2 35.3 16.3 73.3 49.1 13.8 62.1 44.5 11.2 50.6 39.9 19.2 86.4 53.5 16.6 74.9 48.9 14.0 63.0 44.4  
11 11.9 65.3 46.4 9.7 53.3 41.1 7.5 41.2 36.1 14.3 78.8 51.5 12.1 66.5 46.3 9.8 53.8 41.2 16.9 93.2 56.3 14.7 80.6 51.2 12.3 67.5 46.1  
13 10.5 68.3 47.7 8.6 55.7 42.1 6.6 42.7 36.7 12.7 82.7 53.2 10.7 69.7 47.6 8.6 56.2 42.1 15.1 98.2 58.4 13.1 84.9 52.9 10.9 70.9 47.4  
15 9.4 70.6 48.8 7.7 57.4 42.9 5.8 43.9 37.1 11.4 85.8 54.6 9.6 72.2 48.6 7.7 58.0 42.9 13.6 102.3 60.1 11.7 88.1 54.2 9.8 73.6 48.4  
10 14.9 74.6 54.8 12.3 61.3 49.1 9.6 48.1 43.7 17.9 89.4 60.4 15.1 75.7 54.8 12.3 61.7 49.3 21.0 105.1 65.6 18.2 91.0 60.1 15.3 76.5 54.7  
12 13.2 79.4 56.9 10.8 64.9 50.6 8.4 50.4 44.6 15.9 95.6 63.0 13.4 80.6 56.8 10.9 65.4 50.7 18.8 112.8 68.8 16.3 97.5 62.6 13.6 81.7 56.6  
14 11.9 83.0 58.6 9.7 67.7 51.8 7.4 52.2 45.3 14.3 100.3 65.1 12.1 84.5 58.4 9.7 68.2 51.8 17.0 118.7 71.2 14.6 102.6 64.6 12.2 85.7 58.1  
16 10.7 85.8 59.8 8.7 69.8 52.7 6.7 53.5 45.8 13.0 103.9 66.7 10.9 87.5 59.6 8.8 70.4 52.7 15.4 123.5 73.3 13.3 106.5 66.2 11.1 89.0 59.3  
13 16.1 104.3 78.9 13.3 86.4 71.3 10.6 68.7 64.2 19.2 124.5 86.7 16.3 105.9 79.2 13.4 87.1 72.0 22.4 145.9 93.8 19.5 126.8 86.6 16.5 107.2 79.5  
16 14.2 113.6 83.0 11.7 93.3 74.2 9.1 73.1 65.9 17.0 136.3 91.6 14.4 115.4 83.0 11.8 94.0 74.6 20.1 160.5 99.6 17.4 139.0 91.2 14.6 116.9 82.9  
19 12.7 120.5 86.1 10.4 98.5 76.4 8.0 76.4 67.3 15.3 145.2 95.4 12.9 122.6 85.9 10.5 99.4 76.6 18.1 171.6 104.2 15.6 148.4 94.8 13.1 124.4 85.7  
22 11.4 125.8 88.5 9.3 102.6 78.2 7.2 79.0 68.3 13.8 152.0 98.4 11.6 128.1 88.2 9.4 103.5 78.2 16.4 180.2 107.8 14.2 155.7 97.7 11.8 130.2 87.9  
25 10.4 129.9 90.3 8.5 105.7 79.5 6.5 81.0 69.1 12.6 157.4 100.8 10.6 132.5 90.0 8.5 106.7 79.5 15.0 187.2 110.8 12.9 161.5 100.0 10.8 134.9 89.6  
30  
40  
19 15.9 151.5 110.7 13.1 124.5 99.0 10.3 97.7 88.0 19.1 181.4 122.0 16.1 153.4 110.5 13.2 125.2 99.4 22.4 213.0 132.5 19.4 184.3 121.2 16.3 155.0 110.3  
22 14.5 159.4 114.3 11.9 130.4 101.5 9.2 101.4 89.5 17.4 191.6 126.4 14.7 161.7 113.8 11.9 131.2 101.7 20.5 225.8 137.7 17.7 195.1 125.4 14.9 163.6 113.4  
25 13.3 165.7 117.1 10.8 135.2 103.6 8.4 104.4 90.7 16.0 199.7 129.9 13.5 168.3 116.6 10.9 136.1 103.6 18.9 236.1 142.0 16.3 203.9 128.8 13.6 170.6 116.0  
28 12.2 170.8 119.3 9.9 139.0 105.2 7.6 106.9 91.7 14.7 206.4 132.8 12.4 173.8 118.8 10.0 140.1 105.2 17.5 244.4 145.5 15.1 211.1 131.7 12.6 176.4 118.2  
LEGEND  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
DB  
Dry Bulb Temperature  
EWT  
Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb  
TCb  
WB  
T  
Base Sensible Capacity at Nominal Cfm  
Base Total Capacity at Nominal Cfm  
Wet Bulb Temperature  
Change in Water Temperature (F)  
42BHC,BVC 4-ROW COOLING CAPACITY (by T)  
75 F DB/ 63 F WB  
45 F EWT  
80 F DB/67 F WB  
45 F EWT  
85 F DB/71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
T  
GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb  
SCb GPM TCb SCb GPM TCb SCb  
10 3.5 17.3 13.6 2.5 12.5 11.7 3.5 17.3 13.6 4.7 23.3 16.0 3.6 17.9 13.8 2.6 12.8 12.0 6.0 30.0 18.5 4.8 24.2 16.2 3.7 18.3 14.0  
12 2.5 14.9 12.6  
2.5 14.9 12.6 3.5 20.8 15.0 2.6 15.5 12.9  
4.6 27.7 17.5 3.6 21.7 15.2 2.7 16.0 13.2  
06  
14  
16  
2.6 18.1 13.9  
3.5 24.8 16.4 2.7 19.0 14.2  
2.7 21.8 15.3  
10 4.3 21.3 17.2 3.0 15.1 15.1 4.3 21.3 17.2 5.7 28.4 20.0 4.4 21.9 17.5 3.1 15.3 15.3 7.3 36.4 22.9 5.8 29.2 20.2 4.5 22.3 17.7  
12 3.1 18.6 16.1 2.2 13.3 13.3 3.1 18.6 16.1 4.2 25.5 18.9 3.2 19.3 16.5 2.3 13.7 13.7 5.6 33.5 21.8 4.4 26.4 19.1 3.3 19.8 16.8  
08  
10  
12  
16  
20  
14 2.3 15.8 15.0  
2.3 15.8 15.0 3.2 22.5 17.7 2.4 16.5 15.5  
4.3 30.2 20.6 3.3 23.4 18.1 2.5 17.2 16.0  
16  
18  
2.4 19.3 16.5  
3.4 27.0 19.3 2.5 20.3 17.0  
2.6 23.4 18.1  
10 6.2 30.9 23.5 4.6 23.1 20.3 6.2 30.9 23.5 8.1 40.5 27.3 6.3 31.6 23.7 4.7 23.4 20.6 10.2 51.2 31.1 8.4 41.8 27.4 6.4 32.2 23.9  
12 4.7 28.1 22.3 3.4 20.7 19.3 4.7 28.1 22.3 6.2 37.3 26.0 4.8 28.8 22.6 3.5 21.0 19.7 8.0 47.9 29.8 6.4 38.5 26.1 4.9 29.4 22.9  
14 3.6 25.2 21.1 2.5 17.6 17.6 3.6 25.2 21.1 4.9 34.3 24.8 3.7 25.9 21.5 2.6 18.1 18.1 6.4 44.7 28.5 5.0 35.4 25.0 3.8 26.5 21.9  
16 2.8 22.0 19.8  
18  
2.8 22.0 19.8 3.9 31.0 23.5 2.9 22.9 20.4  
3.1 27.5 22.1  
5.2 41.2 27.2 4.0 32.1 23.8 2.9 23.5 20.9  
4.2 37.7 25.8 3.2 28.6 22.6 2.2 19.5 19.5  
10 7.0 34.8 27.0 5.2 26.2 23.4 7.0 34.8 27.0 9.1 45.4 31.2 7.1 35.5 27.2 5.3 26.5 23.8 11.5 57.5 35.5 9.3 46.8 31.3 7.2 36.1 27.4  
12 5.3 31.8 25.7 3.9 23.6 22.4 5.3 31.8 25.7 7.0 41.9 29.8 5.4 32.5 26.0 3.8 22.9 22.9 9.0 53.8 34.0 7.2 43.1 29.9 5.5 33.0 26.3  
14 4.1 28.6 24.4 2.9 20.4 20.4 4.1 28.6 24.4 5.5 38.6 28.4 4.2 29.4 24.9 3.0 20.9 20.9 7.2 50.1 32.6 5.7 39.7 28.7 4.3 29.9 25.3  
16 3.2 25.3 23.0 2.2 17.8 17.8 3.2 25.3 23.0 4.4 35.1 27.0 3.3 26.1 23.7 2.3 18.5 18.5 5.8 46.3 31.1 4.5 36.1 27.4 3.4 26.8 24.2  
18 2.3 21.0 21.0  
2.3 21.0 21.0 3.5 31.4 25.6 2.4 21.9 21.9  
4.7 42.4 29.7 3.6 32.5 26.2 2.5 22.6 22.6  
10 9.1 45.4 35.6 6.8 33.9 30.8 9.1 45.4 35.6 11.9 59.7 41.2 9.3 46.4 35.9 6.9 34.4 31.4 15.2 75.8 47.0 12.3 61.4 41.4 9.5 47.3 36.3  
12 6.8 40.9 33.7 4.8 28.9 28.9 6.8 40.9 33.7 9.1 54.7 39.2 7.0 41.9 34.2 4.9 29.5 29.5 11.8 70.6 44.9 9.4 56.3 39.5 7.1 42.8 34.7  
14 5.1 35.9 31.6 3.6 25.2 25.2 5.1 35.9 31.6 7.1 49.6 37.2 5.3 37.2 32.4 3.7 26.2 26.2 9.3 65.3 42.9 7.3 51.3 37.7 5.5 38.2 33.2  
16 3.6 28.9 28.9  
18  
3.6 28.9 28.9 5.5 44.1 35.1 3.8 30.3 30.3  
4.2 38.0 32.8  
7.4 59.6 40.7 5.7 45.9 35.8 4.2 33.4 31.6  
6.0 53.7 38.5 4.5 40.1 33.8  
10 11.6 57.9 44.8 8.7 43.7 38.9 11.6 57.9 44.8 15.0 75.2 51.6 11.8 59.0 45.1 8.8 44.1 39.5 19.1 95.4 58.8 15.5 77.6 51.9 12.0 60.0 45.5  
12 8.9 53.2 42.8 6.6 39.5 37.2 8.9 53.2 42.8 11.6 69.9 49.4 9.0 54.2 43.3 6.7 40.1 38.0 14.9 89.6 56.5 12.0 71.7 49.7 9.2 55.1 43.8  
14 6.9 48.1 40.7 4.9 34.2 34.2 6.9 48.1 40.7 9.2 64.6 47.3 7.0 49.3 41.4 5.0 35.0 35.0 11.9 83.4 54.1 9.5 66.3 47.7 7.2 50.2 42.1  
16 5.3 42.8 38.5 3.8 30.0 30.0 5.3 42.8 38.5 7.4 59.0 45.1 5.5 44.1 39.5 3.9 31.2 31.2 9.7 77.4 51.8 7.6 60.7 45.7 5.6 45.2 40.4  
18 3.9 35.4 35.4  
3.9 35.4 35.4 5.9 53.1 42.8 4.1 36.9 36.9  
7.9 71.3 49.5 6.1 54.8 43.7 4.2 38.0 38.0  
10 17.2 85.8 66.9 12.8 64.1 58.0 17.2 85.8 66.9 22.5 112.5 77.6 17.5 87.6 67.6 13.0 65.0 59.1 28.6 142.8 88.4 23.1 115.8 77.8 17.8 89.2 68.2  
12 12.9 77.4 63.4 9.1 54.7 54.7 12.9 77.4 63.4 17.2 103.3 73.8 13.2 79.4 64.5 9.3 55.8 55.8 22.1 132.7 84.4 17.7 106.4 74.4 13.5 81.0 65.3  
14 9.8 68.3 59.7 6.8 47.9 47.9 9.8 68.3 59.7 13.4 94.0 70.1 10.1 70.6 61.2 7.1 49.8 49.8 17.6 123.3 80.7 13.9 97.0 71.0 10.4 72.5 62.5  
30  
40  
16 6.9 55.2 55.2  
18  
6.9 55.2 55.2 10.5 84.0 66.2 7.6 61.1 57.7  
8.1 72.8 62.0  
14.1 112.9 76.8 10.9 87.2 67.5 7.9 63.5 59.5  
11.3 102.0 72.8 8.5 76.6 63.9  
14 14.7 102.9 84.5 10.4 72.8 72.8 14.7 102.9 84.5 19.5 136.6 98.0 15.0 105.0 85.7 10.6 74.1 74.1 25.1 175.5 112.0 20.0 140.1 98.6 15.2 106.7 86.8  
16 11.6 92.9 80.4 8.2 65.3 65.3 11.6 92.9 80.4 15.8 126.1 93.9 11.9 95.2 82.1 8.4 67.2 67.2 20.5 163.8 107.5 16.2 129.4 94.7 12.1 97.1 83.5  
18 9.1 81.9 76.0 6.1 55.2 55.2 9.1 81.9 76.0 12.8 115.0 89.5 9.4 84.8 78.3 6.5 58.5 58.5 16.9 152.4 103.1 13.1 118.4 90.8 9.7 87.2 80.2  
LEGEND  
Dry Bulb Temperature  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
DB  
EWT — Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb  
TCb  
WB  
T  
Base Sensible Capacity at Nominal Cfm  
Base Total Capacity at Nominal Cfm  
Wet Bulb Temperature  
Change in Water Temperature (F)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BHC, BVC 6-ROW COOLING CAPACITY (by T)  
75 F DB/63 F WB  
45 F EWT  
80 F DB/67 F WB  
85 F DB/71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
40 F EWT  
50 F EWT  
40 F EWT  
45 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
T  
GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb  
10 4.8 23.8 17.0 3.5 17.7 14.3 2.4 12.0 12.0 6.2 31.0 19.8 4.9 24.5 17.0 3.6 18.0 14.5 7.8 38.8 22.7 6.4 32.2 19.9 5.0 25.1 17.1  
12 3.6 21.8 16.1 2.6 15.8 13.5  
4.8 28.9 18.9 3.7 22.4 16.2 2.7 16.1 13.8 6.2 37.0 21.9 5.0 30.0 19.0 3.8 23.0 16.3  
06  
08  
10  
12  
16  
20  
30  
40  
14 2.8 19.6 15.1  
3.8 26.7 18.0 2.9 20.2 15.3  
3.0 24.3 17.0 2.2 17.8 14.4  
5.0 34.7 20.9 4.0 27.8 18.1 3.0 20.7 15.5  
4.0 32.3 19.9 3.2 25.3 17.1 2.3 18.4 14.7  
16  
18  
2.4 21.7 15.9  
3.3 29.8 18.9 2.5 22.7 16.2  
10 5.9 29.6 21.6 4.4 22.2 18.4 3.1 15.5 15.5 7.7 38.4 25.1 6.1 30.3 21.7 4.5 22.5 18.6 9.7 48.3 28.6 8.0 39.8 25.1 6.2 31.0 21.7  
12 4.5 27.2 20.5 3.3 20.0 17.5 2.3 14.0 14.0 6.0 35.8 23.9 4.6 27.9 20.7 3.4 20.3 17.8 7.6 45.6 27.5 6.2 37.1 24.0 4.7 28.5 20.8  
14 3.5 24.7 19.4 2.5 17.7 16.6  
4.7 33.2 22.8 3.6 25.3 19.7 2.6 18.1 17.0 6.1 42.9 26.3 4.9 34.3 23.0 3.7 25.8 19.9  
16 2.7 21.9 18.3  
18  
3.8 30.4 21.7 2.8 22.6 18.7  
3.0 27.4 20.5 2.2 19.9 17.6  
5.0 40.0 25.2 3.9 31.4 21.9 2.9 23.2 19.0  
4.1 37.0 24.0 3.2 28.4 20.8 2.3 20.5 18.1  
10 8.1 40.6 28.7 6.2 30.9 24.4 4.4 22.0 20.7 10.4 52.2 33.3 8.3 41.7 28.7 6.2 31.2 24.5 13.0 65.1 37.9 10.8 54.2 33.3 8.5 42.6 28.7  
12 6.4 38.1 27.5 4.7 28.5 23.4 3.3 19.7 19.7 8.3 49.5 32.1 6.5 39.0 27.6 4.8 28.8 23.6 10.4 62.4 36.7 8.5 51.1 32.0 6.6 39.8 27.7  
14 5.1 35.4 26.3 3.7 26.0 22.4 2.6 17.9 17.9 6.7 46.7 30.8 5.2 36.2 26.5 3.8 26.3 22.7 8.5 59.4 35.4 6.9 48.1  
30.8 5.3 36.9 26.6  
5.5 43.7 29.6 4.2 33.3 25.3 3.0 23.7 21.7 7.0 56.2 34.1 5.6 45.0 29.6 4.2 33.9 25.5  
4.5 40.6 28.2 3.4 30.2 24.1 2.3 20.4 20.4 5.9 53.0 32.7 4.6 41.7 28.4 3.4 30.8 24.5  
16 4.1 32.5 25.1 2.9 23.3 21.3  
18 3.3 29.5 23.8 2.2 19.9 19.9  
10 9.3 46.3 33.2 7.0 35.2 28.4 4.9 24.4 24.4 11.9 59.6 38.4 9.5 47.4 33.2 7.1 35.5 28.5 14.9 74.3 43.7 12.3 61.7 38.4 9.7 48.4 33.2  
12 7.2 43.5 31.9 5.4 32.6 27.3 3.8 22.8 22.8 9.4 56.3 37.0 7.4 44.3 32.0 5.5 32.8 27.5 11.8 71.1 42.3 9.7 58.0 36.9 7.5 45.1 32.1  
14 5.8 40.4 30.6 4.3 29.8 26.1 3.0 20.9 20.9 7.6 53.0 35.6 5.9 41.2 30.7 4.3 30.1 26.5 9.7 67.6 40.8 7.8 54.6 35.6 6.0 41.9 30.9  
16 4.7 37.2 29.2 3.4 27.0 25.0 2.3 18.4 18.4 6.2 49.7 34.2 4.7 38.0 29.5 3.4 27.4 25.5 8.0 63.7 39.2 6.4 51.1 34.3 4.8 38.6 29.7  
18 3.8 33.9 27.8 2.6 23.3 23.3  
5.1 46.2 32.7 3.8 34.6 28.2 2.6 23.8 23.8 6.7 60.1 37.8 5.3 47.4 32.9 3.9 35.2 28.6  
10 12.2 61.2 44.0 9.3 46.4 37.6 6.4 32.1 32.1 15.7 78.7 50.9 12.5 62.6 44.1 9.4 46.8 37.8 19.7 98.5 58.0 16.3 81.5 50.9 12.8 63.9 44.1  
12 9.5 57.0 42.1 7.1 42.5 36.0 4.9 29.7 29.7 12.4 74.2 48.9 9.7 58.3 42.3 7.2 42.9 36.4 15.6 93.9 56.0 12.8 76.5 48.9 9.9 59.4 42.5  
14 7.5 52.6 40.2 5.5 38.4 34.3 3.8 26.6 26.6 10.0 69.7 47.0 7.7 53.8 40.5 5.6 39.0 34.9 12.7 89.1 54.0 10.3 71.8 47.1 7.8 54.8 40.8  
16 6.0 47.8 38.2 4.1 32.6 32.6  
18 4.7 42.7 36.0  
8.1 64.8 45.0 6.1 49.0 38.7 4.2 33.4 33.4 10.5 83.7 51.8 8.3 66.8 45.2 6.3 50.0 39.2  
6.6 59.6 42.9 4.9 44.0 36.8 3.3 29.8 29.8 8.7 78.6 49.7 6.8 61.5 43.2 5.0 45.1 37.5  
10 15.4 76.9 55.1 11.7 58.6 47.1 8.1 40.6 40.6 19.8 99.0 63.8 15.7 78.7 55.2 11.8 59.0 47.4 24.7 123.3 72.5 20.4 102.1 63.6 16.1 80.3 55.2  
12 12.0 72.3 53.0 9.1 54.3 45.4 6.3 38.1 38.1 15.6 93.6 61.5 12.3 73.7 53.2 9.1 54.7 45.8 19.7 117.9 70.2 16.0 96.3 61.3 12.5 75.0 53.3  
14 9.6 67.4 50.9 7.1 49.9 43.6 5.0 35.0 35.0 12.6 88.2 59.2 9.8 68.7 51.2 7.2 50.4 44.2 16.0 112.0 67.7 13.0 90.7 59.2 10.0 69.7 51.4  
16 7.8 62.3 48.7 5.7 45.3 41.7 3.9 31.0 31.0 10.4 82.9 56.9 7.9 63.5 49.1 5.7 45.9 42.6 13.3 106.1 65.3 10.6 85.1 57.0 8.1 64.4 49.5  
18 6.3 56.9 46.4 4.3 39.1 39.1  
8.6 77.3 54.6 6.5 58.1 47.1 4.4 40.0 40.0 11.1 100.2 62.9 8.8 79.2 54.8 6.6 59.1 47.6  
10 23.0 115.1 82.6 17.5 87.3 70.6 12.1 60.5 60.5 29.7 148.5 95.8 23.6 117.8 82.8 17.6 88.1 71.1 37.0 185.2 109.0 30.6 153.2 95.6 24.1 120.3 82.9  
12 17.9 107.5 79.3 13.4 80.2 67.6 9.3 56.0 56.0 23.3 139.8 92.1 18.3 109.9 79.6 13.5 81.0 68.4 29.3 176.0 105.0 24.0 144.1 92.0 18.6 111.9 79.8  
14 14.2 99.3 75.7 10.4 72.6 64.6 7.2 50.3 50.3 18.8 131.3 88.4 14.5 101.5 76.3 10.5 73.7 65.7 23.9 167.6 101.5 19.3 135.3 88.6 14.8 103.3 76.8  
16 11.3 90.6 72.0 7.7 61.8 61.8  
18 9.0 81.1 68.0 6.1 54.6 54.6  
15.3 122.4 84.7 11.6 92.8  
12.5 112.9 80.8 9.3 83.5  
72.9 7.9 63.2 63.2 19.7 157.8 97.5 15.7 126.0 85.0 11.8 94.5 73.7  
69.4 6.3 56.7 56.7 16.5 148.3 93.6 12.9 116.2 81.4 9.5 85.5 70.6  
42.2 210.9 130.2 33.2 166.2 112.7  
10 31.8 158.9 112.7 24.3 121.4 96.3 17.4 87.2 82.3 40.8 204.0 130.5 32.5 162.6 112.7 24.5 122.3 96.7  
12 25.0 150.0 108.6 18.9 113.1 92.8 13.1 78.8 78.8 32.3 193.6 125.9 25.5 153.0 108.8 19.0 113.9 93.5 40.6 243.4 143.8 33.3 199.6 125.7 26.0 155.7 108.9  
14 20.1 140.7 104.6 14.9 104.6 89.3 10.4 73.1 73.1 26.2 183.1 121.4 20.5 143.3 104.9 15.1 105.4 90.4 33.2 232.4 139.1 26.9 188.5 121.3 20.8 145.4 105.1  
16 16.4 131.0 100.3 12.0 95.7 85.7 8.2 66.0 66.0 21.6 172.9 117.0 16.7 133.2 100.9 12.1 96.8 87.2 27.6 220.5 134.1 22.2 177.4 117.0 16.9 135.1 101.5  
18 13.4 120.7 96.0 9.6 86.3 82.0 6.3 56.3 56.3 18.0 162.2 112.6 13.7 122.9 96.9 9.3 84.1 84.1 23.2 208.8 129.3 18.5 166.1 112.7 13.8 124.6 97.8  
LEGEND  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
DB  
Dry Bulb Temperature  
TCb Base Total Capacity at Nominal Cfm  
EWT — Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb Base Sensible Capacity at Nominal Cfm  
WB — Wet Bulb Temperature  
T — Change in Water Temperature (F)  
42BHC, BVC 8-ROW COOLING CAPACITY (by T)  
75 F DB/63 F WB  
45 F EWT  
80 F DB/67 F WB  
85 F DB/71 F WB  
45 F EWT  
UNIT  
SIZE  
42BHC,BVC  
40 F EWT  
50 F EWT  
40 F EWT  
45 F EWT  
50 F EWT  
40 F EWT  
50 F EWT  
T  
GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb  
10 5.2 25.8 18.0 3.8 19.0 15.0  
6.8 33.8 21.2 5.3 26.7 18.1 3.9 19.4 15.2 8.5 42.4 24.4 7.1 35.3 21.3 5.5 27.6 18.2  
12 3.9 23.3 16.9  
5.2 31.4 20.2 4.0 24.2 17.1  
6.7 40.2 23.4 5.5 32.8 20.3 4.2 25.0 17.2  
14  
16  
18  
4.1 28.7 19.0  
5.4 37.6 22.3 4.3 30.1 19.2  
4.4 34.8 21.1 3.4 26.9 17.9  
06  
08  
3.5 31.6 19.8  
10 6.5 32.7 23.2 4.9 24.3 19.6 3.3 16.5 16.5 8.5 42.6 27.2 6.7 33.7 23.3 4.9 24.7 19.8 10.7 53.4 31.1 8.9 44.3 27.2 6.9 34.7 23.4  
12 5.0 29.8 21.9 3.6 21.4 18.4  
6.6 39.7 25.9 5.1 30.7 22.1 3.3 19.9 19.9 8.4 50.7 29.9 6.9 41.3 26.0 5.3 31.5 22.3  
14 3.8 26.4 20.5  
5.2 36.5 24.5 3.9 27.4 20.8  
6.8 47.5 28.5 5.4 38.0 24.7 4.0 28.2 21.1  
16  
18  
4.1 32.9 23.0  
5.5 44.0 27.1 4.3 34.3 23.3  
4.5 40.3 25.6 3.4 30.3 21.8  
10 9.0 45.0 31.0 6.8 34.1 26.1 4.5 22.5 22.5 11.5 57.7 36.0 9.3 46.4 31.0 6.9 34.6 26.2 14.3 71.4 41.0 12.0 60.1 36.0 9.5 47.6 31.0  
12 7.0 42.1 29.6 5.2 31.1 24.8 3.5 20.9 20.9 9.1 54.8 34.7 7.2 43.3 29.7 5.3 31.6 25.0 11.5 68.9 39.9 9.5 56.9 34.7 7.4 44.4 29.7  
10  
14 5.5 38.8 28.1 4.0 27.9 23.5  
7.4 51.7 33.3 5.7 39.9 28.3 3.6 25.5 25.5 9.4 65.8 38.5 7.7 53.7 33.3 5.8 40.9 28.4  
16 4.4 35.1 26.5  
18 3.4 31.0 24.7  
6.0 48.2 31.8 4.5 36.2 26.8  
4.9 44.3 30.1 3.6 32.2 25.2  
7.8 62.3 36.9 6.2 50.0 31.9 4.6 37.2 27.1  
6.5 58.7 35.4 5.1 46.0 30.3 3.7 33.2 25.7  
10 10.4 51.9 36.1 7.9 39.4 30.6 5.3 26.4 26.4 13.3 66.6 42.0 10.7 53.3 36.1 8.0 39.9 30.7 16.5 82.5 47.7 13.8 69.1 41.9 10.9 54.7 36.1  
12 8.1 48.6 34.6 6.0 36.1 29.2 4.1 24.6 24.6 10.5 63.1 40.4 8.3 49.9 34.7 6.1 36.5 29.4 13.2 79.3 46.2 10.9 65.4 40.3 8.5 51.0 34.7  
14 6.4 44.9 32.9 4.6 32.5 27.7  
16 5.1 40.9 31.2 3.6 28.8 26.2  
8.5 59.5 38.8 6.6 46.1 33.1 4.7 33.1 28.1 10.8 75.6 44.6 8.8 61.6 38.8 6.7 47.1 33.3  
6.9 55.6 37.1 5.2 42.0 31.5 3.5 27.8 27.8 9.0 71.6 42.9 7.2 57.5 37.2 5.4 42.9 31.8  
12  
16  
20  
30  
40  
18 4.0 36.4 29.3  
5.7 51.2 35.2 4.2 37.6 29.8  
7.5 67.5 41.2 5.9 53.0 35.5 4.3 38.6 30.3  
10 13.9 69.4 48.2 10.5 52.6 40.8 7.0 35.2 35.2 17.8 89.0 56.0 14.3 71.3 48.3 10.7 53.3 41.0 22.1 110.6 63.9 18.5 92.5 56.0 14.6 73.1 48.3  
12 10.8 64.9 46.2 8.0 48.1 38.9 5.4 32.6 32.6 14.1 84.4 54.0 11.1 66.7 46.3 8.1 48.8 39.3 17.7 106.0 61.8 14.6 87.5 53.9 11.4 68.2 46.4  
14 8.6 59.9 43.9 6.2 43.2 36.9  
16 6.8 54.2 41.5 4.7 37.7 34.6  
11.4 79.6 51.8 8.8 61.5 44.2 6.3 44.0 37.5 14.5 101.2 59.7 11.8 82.4 51.9 9.0 62.9 44.4  
9.3 74.2 49.5 7.0 55.9 42.0 4.6 36.7 36.7 12.0 95.8 57.4 9.6 76.8 49.7 7.2 57.2 42.4  
18 5.3 47.8 38.8  
7.6 68.2 47.0 5.5 49.7 39.6  
10.0 90.2 55.0 7.8 70.6 47.3 5.7 51.2 40.3  
10 17.5 87.6 60.6 13.4 66.9 51.4 9.5 47.4 43.4 22.4 111.8 70.3 18.0 89.9 60.6 13.5 67.6 51.6 27.7 138.7 80.0 23.2 116.2 70.2 18.4 92.1 60.5  
12 13.8 82.7 58.4 10.3 62.0 49.3 7.0 42.1 42.1 17.8 106.6 67.9 14.1 84.7 58.4 10.4 62.6 49.6 22.2 133.4 77.6 18.4 110.3 67.7 14.4 86.5 58.4  
14 11.0 77.3 56.0 8.1 56.7 47.2 5.5 38.8 38.8 14.5 101.2 65.5 11.3 79.0 56.1 8.2 57.4 47.7 18.3 127.8 75.1 14.9 104.5 65.4 11.5 80.6 56.2  
16 8.9 71.4 53.4 6.4 51.2 44.9  
18 7.2 65.0 50.6 5.0 45.1 42.5  
11.9 95.4 63.0 9.1 73.0 53.7 6.5 52.1 45.7 15.2 121.6 72.5 12.3 98.4 62.9 9.3 74.3 53.9  
9.9 89.0 60.2 7.4 66.6 51.2 5.2 46.4 43.6 12.8 115.5 69.9 10.2 91.7 60.4 7.5 67.9 51.7  
10 26.3 131.4 91.0 20.0 100.0 77.1 13.4 66.8 66.8 33.6 168.0 105.5 27.0 135.0 91.0 20.2 101.2 77.4 41.7 208.7 120.4 34.9 174.6 105.4 27.7 138.4 90.9  
12 20.6 123.5 87.4 15.3 91.9 73.6 10.4 62.3 62.3 26.6 159.8 101.9 21.1 126.6 87.6 15.5 93.1 74.2 33.4 200.5 116.6 27.6 165.6 101.7 21.6 129.5 87.6  
14 16.4 114.5 83.4 11.9 83.2 70.0 8.0 56.4 56.4 21.6 151.2 98.1 16.8 117.4 83.8 12.1 84.5 71.0 27.4 191.7 112.7 22.4 156.5 98.0 17.1 120.0 84.1  
16 13.1 104.6 79.0 9.2 73.7 66.2  
18 10.4 93.6 74.3  
17.7 141.7 93.9 13.4 107.5 79.8 8.8 70.6 70.6 22.7 182.0 108.5 18.3 146.5 94.1 13.7 109.8 80.4  
14.6 131.1 89.4 10.7 96.7 75.6 19.1 171.9 104.3 15.1 135.5 89.9 11.0 99.1 76.6  
10 36.1 180.6 123.9 27.7 138.7 105.1 19.7 98.7 88.4 46.0 230.1 143.5 37.1 185.6 123.8 28.0 140.2 105.2 56.9 284.6 163.3 47.8 238.9 143.1 38.1 190.4 123.5  
12 28.6 171.7 119.8 21.6 129.7 101.2 14.6 87.5 87.5 36.7 220.3 139.2 29.3 175.8 119.7 21.8 130.8 101.6 45.7 274.2 158.6 38.0 228.2 138.7 29.9 179.6 119.4  
14 23.1 161.9 115.4 17.1 120.1 97.2 11.7 81.8 81.8 30.0 210.2 134.5 23.6 165.5 115.4 17.3 121.1 97.9 37.7 264.2 154.1 31.0 217.1 134.1 24.1 168.5 115.3  
16 18.9 151.2 110.5 13.7 109.8 92.9 9.3 74.3 74.3 24.9 199.6 129.9 19.3 154.3 110.8 13.9 111.1 94.1 31.6 253.0 149.2 25.7 205.7 129.6 19.6 156.9 111.0  
18 15.5 139.5 105.4 11.0 98.8 88.5  
20.9 188.0 124.9 15.8 142.4 106.1 11.2 100.6 90.2 26.8 241.3 144.2 21.5 193.4 124.7 16.1 144.8 106.6  
LEGEND  
DB  
Dry Bulb Temperature  
TCb Base Total Capacity at Nominal Cfm  
WB — Wet Bulb Temperature  
T — Change in Water Temperature (F)  
EWT — Entering Water Temperature  
MBtuh — Btuh in Thousands  
SCb Base Sensible Capacity at Nominal Cfm  
NOTE: All capacities are given in thousands of Btuh (MBtuh).  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) — 4-ROW COIL  
ENTERING-AIR TEMPERATURE (F)—DRY BULB/WET BULB  
80/63 75/67 80/67 80/71  
TH TH  
CONNECTION  
SIZE(in.)  
UNIT  
SIZE  
42BHC,BVC  
R-22  
SUCTION  
TEMP(F)  
CFM  
75/63  
TH  
85/71  
Liquid  
Suction  
SH  
TH  
SH  
SH  
TH  
SH  
SH  
TH  
SH  
40  
45  
50  
40  
45  
50  
8.6  
7.8  
5.4  
2.3  
12.0  
9.0  
5.0  
9.9  
9.9  
13.5  
7.2  
7.8  
5.5  
2.3  
11.5  
8.5  
5.0  
13.5  
8.4  
9.8  
18.7  
13.5  
6.6  
26.9  
19.4  
11.0  
9.8  
7.8  
5.5  
14.2  
11.4  
8.6  
18.8  
13.6  
7.8  
26.6  
19.7  
13.0  
11.7  
9.8  
400  
600  
5.4  
2.3  
7.8  
5.4  
7.8  
5.4  
7.9  
5.4  
2.3  
5.4  
7.8  
13.3  
9.0  
5.0  
15.4  
12.3  
8.9  
15.4  
12.3  
8.9  
19.5  
11.5  
5.0  
19.5  
13.2  
8.9  
14.5  
12.1  
8.9  
17.1  
14.5  
12.2  
3
3
1
1
5
5
5
06  
08  
10  
12  
16  
20  
/
/
/
/
/
/
/
8
8
2
2
8
8
8
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
15.3  
10.4  
6.1  
13.3  
9.0  
5.0  
17.0  
11.8  
7.1  
18.4  
12.9  
7.9  
24.7  
17.2  
11.9  
29.1  
20.8  
14.8  
31.0  
22.3  
16.0  
29.1  
20.8  
14.8  
32.8  
23.7  
17.1  
34.4  
24.0  
18.1  
38.2  
26.0  
18.9  
41.9  
28.9  
21.1  
45.1  
31.4  
23.0  
48.8  
33.4  
24.5  
52.2  
36.2  
26.6  
55.3  
38.6  
28.5  
72.3  
49.0  
35.9  
76.1  
52.1  
38.2  
79.7  
54.9  
40.4  
83.0  
57.6  
42.4  
110.1  
82.1  
58.8  
113.6  
85.1  
61.3  
13.8  
10.4  
6.1  
12.0  
9.0  
5.0  
15.4  
11.8  
7.1  
16.9  
12.9  
7.9  
18.9  
15.8  
11.9  
22.7  
19.3  
14.8  
24.5  
20.9  
16.0  
22.7  
19.3  
14.8  
26.1  
22.4  
17.1  
27.6  
24.0  
18.1  
30.7  
26.0  
18.9  
34.1  
28.9  
21.1  
37.1  
31.4  
23.0  
39.2  
33.4  
24.5  
42.4  
36.2  
26.6  
45.3  
38.6  
28.5  
57.6  
49.0  
35.9  
61.1  
52.1  
38.2  
64.4  
54.9  
40.4  
67.5  
57.6  
42.4  
84.0  
72.3  
58.8  
87.3  
75.4  
61.3  
17.7  
14.2  
10.4  
15.4  
12.3  
8.9  
19.8  
15.9  
11.7  
21.5  
17.3  
12.9  
23.9  
20.0  
16.0  
29.1  
24.4  
19.7  
31.4  
26.4  
21.2  
29.1  
24.4  
19.7  
33.5  
28.1  
22.7  
35.3  
29.7  
24.0  
39.4  
32.8  
25.9  
43.7  
36.4  
28.9  
47.3  
39.5  
31.4  
50.3  
41.9  
33.4  
54.3  
45.3  
36.1  
57.8  
48.3  
38.5  
73.9  
61.6  
49.0  
78.4  
65.4  
52.0  
82.5  
68.9  
54.9  
86.3  
72.1  
57.5  
107.6  
91.7  
75.4  
112.1  
95.5  
78.5  
116.2  
99.0  
81.5  
120.1  
102.4  
84.3  
17.7  
14.2  
10.4  
15.4  
12.3  
8.9  
19.8  
15.9  
11.7  
21.5  
17.3  
12.9  
23.9  
20.0  
16.0  
29.1  
24.4  
19.7  
31.4  
26.4  
21.2  
29.1  
24.4  
19.7  
33.5  
28.1  
22.7  
35.3  
29.7  
24.0  
39.4  
32.8  
25.9  
43.7  
36.4  
28.9  
47.3  
39.5  
31.4  
50.3  
41.9  
33.4  
54.3  
45.3  
36.1  
57.8  
48.3  
38.5  
73.9  
61.6  
49.0  
78.4  
65.4  
52.0  
82.5  
68.9  
54.9  
86.3  
72.1  
57.5  
107.6  
91.7  
75.4  
112.1  
95.5  
78.5  
116.2  
99.0  
81.5  
120.1  
102.4  
84.3  
21.9  
13.3  
6.1  
19.5  
11.5  
5.0  
24.3  
14.9  
7.1  
26.3  
16.2  
7.9  
33.2  
24.9  
15.1  
38.8  
29.2  
18.1  
41.2  
31.1  
19.4  
38.8  
29.2  
18.1  
43.4  
32.7  
20.6  
45.4  
34.3  
21.8  
52.0  
37.9  
21.8  
56.7  
41.5  
24.2  
60.8  
44.6  
26.3  
65.9  
48.5  
28.8  
70.3  
51.9  
31.0  
74.2  
54.9  
33.0  
98.0  
72.0  
42.3  
102.8  
75.8  
44.8  
107.4  
79.2  
47.2  
111.6  
82.4  
49.2  
141.6  
111.1  
76.7  
145.9  
114.6  
79.2  
150.0  
117.8  
81.7  
153.8  
120.9  
83.9  
13.1  
9.9  
22.0  
15.1  
10.4  
19.5  
13.2  
8.9  
24.2  
16.8  
11.7  
26.2  
18.3  
12.9  
32.9  
24.9  
17.0  
38.6  
29.3  
19.7  
40.8  
31.2  
21.2  
38.6  
29.3  
19.7  
42.8  
32.9  
22.7  
45.1  
34.5  
24.0  
51.8  
38.3  
25.9  
56.0  
42.0  
28.9  
60.1  
45.1  
31.4  
65.4  
48.9  
33.4  
69.7  
52.4  
36.1  
73.6  
55.4  
38.5  
96.5  
72.6  
49.0  
102.0  
76.4  
52.0  
106.0  
79.9  
54.9  
110.9  
83.2  
57.5  
141.1  
110.8  
81.4  
144.1  
114.5  
84.4  
148.7  
117.8  
87.1  
153.0  
121.0  
89.8  
16.5  
13.9  
10.4  
14.5  
12.1  
8.9  
18.4  
15.6  
11.7  
20.1  
17.1  
12.9  
22.2  
18.9  
15.9  
26.5  
22.8  
19.7  
28.4  
24.6  
21.2  
26.5  
22.8  
19.7  
30.1  
26.2  
22.7  
31.9  
27.7  
24.0  
36.2  
30.8  
25.9  
39.7  
34.2  
28.9  
43.1  
37.3  
31.4  
45.8  
39.3  
33.4  
49.4  
42.6  
36.1  
52.6  
45.5  
38.5  
67.3  
57.8  
49.0  
71.5  
61.3  
52.0  
74.9  
64.7  
54.9  
78.7  
67.8  
57.5  
96.2  
84.0  
72.8  
99.3  
87.4  
76.0  
103.0  
90.6  
79.1  
106.5  
93.7  
82.0  
30.1  
21.9  
12.7  
26.9  
19.4  
11.0  
33.0  
24.1  
14.2  
35.5  
26.4  
15.6  
42.0  
33.9  
24.6  
48.8  
39.5  
29.0  
51.7  
41.9  
30.8  
48.8  
39.5  
29.0  
54.3  
44.0  
32.5  
56.7  
45.9  
34.0  
66.5  
53.0  
37.2  
72.3  
57.6  
40.5  
77.3  
61.6  
44.0  
83.7  
67.0  
47.5  
89.1  
71.3  
51.2  
93.9  
75.1  
54.1  
124.8  
99.7  
71.0  
130.8  
104.6  
74.0  
136.3  
109.0  
77.7  
141.5  
113.2  
81.3  
173.7  
143.8  
110.8  
178.8  
148.0  
114.2  
183.5  
151.9  
117.3  
187.9  
155.6  
120.2  
16.1  
13.0  
9.9  
14.2  
11.4  
8.6  
17.7  
14.5  
11.2  
19.2  
15.9  
12.3  
21.5  
18.2  
14.8  
25.3  
21.6  
17.8  
26.9  
23.1  
19.2  
25.3  
21.6  
17.8  
28.5  
24.5  
20.4  
29.9  
25.8  
21.5  
34.6  
29.4  
23.7  
37.9  
32.3  
26.3  
40.8  
34.9  
28.7  
43.7  
37.2  
30.3  
46.8  
40.0  
32.9  
49.6  
42.5  
35.1  
64.8  
55.1  
44.8  
68.2  
58.1  
47.2  
71.4  
60.9  
49.8  
74.4  
63.6  
52.4  
90.0  
78.3  
66.3  
93.0  
81.1  
68.8  
95.9  
83.7  
71.2  
98.6  
86.2  
73.5  
29.8  
22.2  
15.0  
26.6  
19.7  
13.0  
32.4  
24.4  
16.7  
35.3  
26.3  
17.3  
41.4  
33.6  
24.9  
48.4  
39.1  
29.3  
51.0  
41.6  
31.2  
48.4  
39.1  
29.3  
54.2  
43.5  
32.9  
56.6  
45.6  
34.4  
65.9  
52.6  
38.3  
71.8  
57.2  
41.8  
77.0  
61.2  
44.9  
83.2  
66.5  
48.8  
88.5  
70.6  
52.2  
93.2  
74.3  
55.2  
122.5  
98.6  
72.5  
129.8  
103.8  
76.2  
134.3  
107.7  
79.7  
141.0  
112.3  
83.0  
173.3  
143.3  
111.1  
178.3  
146.2  
114.7  
183.0  
150.5  
118.0  
187.4  
154.5  
121.1  
19.4  
16.6  
14.1  
17.1  
14.5  
12.2  
21.4  
18.4  
15.8  
23.4  
20.1  
17.3  
25.2  
22.1  
18.9  
30.0  
26.4  
22.8  
32.0  
28.4  
24.6  
30.0  
26.4  
22.8  
34.2  
30.1  
26.3  
36.0  
31.8  
27.8  
41.2  
36.1  
31.0  
45.4  
39.8  
34.4  
49.2  
43.2  
37.5  
52.2  
45.8  
39.5  
56.1  
49.3  
42.8  
59.6  
52.5  
45.8  
76.6  
67.3  
58.0  
81.4  
71.4  
61.6  
85.0  
74.9  
64.9  
89.4  
78.5  
68.1  
107.4  
95.7  
84.0  
111.3  
98.8  
87.4  
115.0  
102.4  
90.7  
118.5  
105.9  
93.8  
700  
6.1  
11.5  
8.5  
5.0  
14.6  
11.1  
7.1  
15.9  
12.1  
7.9  
18.3  
14.9  
11.3  
21.7  
17.9  
13.8  
23.2  
19.2  
14.9  
21.7  
17.9  
13.8  
24.6  
20.4  
16.0  
25.9  
21.5  
16.9  
29.4  
23.8  
18.0  
32.3  
26.4  
20.1  
34.9  
28.6  
22.0  
37.3  
30.5  
23.3  
40.1  
32.9  
25.3  
42.6  
35.1  
27.2  
55.2  
44.9  
34.1  
58.2  
47.5  
36.3  
61.1  
50.0  
38.4  
63.7  
52.3  
40.3  
78.8  
66.5  
53.6  
81.6  
69.0  
55.8  
84.3  
71.4  
57.9  
86.8  
73.6  
59.9  
600  
5
/
800  
8
900  
800  
7
/
1000  
1100  
1000  
1200  
1300  
1400  
1600  
1800  
1800  
2000  
2200  
2600  
2800  
3000  
3200  
3600  
3800  
4000  
4200  
8
7
/
8
7
/
8
7
/
8
5
30  
/
8
11/8  
7
40  
/
8
11/8  
117.1  
87.9  
63.7  
120.4  
90.5  
66.0  
90.5  
78.4  
63.7  
93.6  
81.3  
66.0  
LEGEND  
*Capacity based on R-22 refrigerant at 105 F liquid temperature and 10 F  
superheat.  
MBtuh — Capacity (Btuh in thousands)  
SH  
TH  
Sensible Heat  
Total Heat  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) — 6-ROW COIL  
ENTERING AIR TEMPERATURE (F) — DRY BULB/WET BULB  
80/63 75/67 80/67 80/71  
CONNECTION  
SIZE (in.)  
Liquid Suction  
UNIT  
SIZE  
42BHC,BVC  
R-22  
CFM SUCTION  
TEMP (F)  
75/63  
85/71  
TH  
SH  
TH  
SH  
TH  
SH  
TH  
SH  
TH  
SH  
TH  
SH  
40  
15.4  
9.1  
11.1  
9.1  
13.6  
11.4  
9.1  
20.6  
17.3  
14.0  
13.6  
11.4  
9.1  
20.6  
17.3  
14.0  
20.8  
15.6  
9.3  
29.3  
22.3  
14.0  
11.1  
8.9  
20.8  
15.6  
10.2  
29.4  
22.4  
15.4  
13.2  
11.0  
8.9  
19.1  
16.2  
13.5  
26.4  
21.3  
15.7  
37.2  
30.2  
22.3  
13.2  
11.0  
8.9  
18.7  
15.8  
12.9  
26.3  
21.3  
15.7  
37.0  
30.2  
22.6  
15.3  
13.1  
11.0  
21.9  
19.0  
16.2  
400  
600  
45  
50  
6.7  
6.7  
6.5  
40  
45  
50  
22.1  
14.0  
10.5  
16.2  
14.0  
10.5  
15.9  
12.9  
9.8  
3
3
1
1
5
5
5
5
7
7
7
7
06  
08  
10  
12  
16  
20  
/
/
/
/
/
/
/
/
/
/
/
/
8
8
2
2
8
8
8
8
8
8
8
8
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
40  
45  
50  
25.1  
17.8  
12.1  
22.1  
14.0  
10.5  
27.7  
19.8  
13.7  
30.0  
21.6  
15.0  
33.3  
25.1  
16.6  
39.1  
29.8  
20.3  
41.6  
31.9  
22.0  
39.1  
29.8  
20.3  
43.9  
33.7  
23.6  
46.0  
35.4  
25.1  
53.9  
40.4  
27.5  
59.0  
44.4  
30.7  
63.5  
48.0  
33.6  
68.0  
51.3  
35.3  
72.7  
55.1  
38.4  
77.0  
58.5  
41.2  
100.8  
75.9  
51.6  
106.1  
80.1  
54.9  
111.0  
84.0  
58.1  
115.6  
87.6  
61.1  
137.6  
107.9  
78.5  
141.9  
111.6  
78.8  
145.9  
115.1  
81.9  
149.7  
118.3  
84.9  
18.6  
15.5  
12.1  
16.2  
14.0  
10.5  
20.7  
17.4  
13.7  
22.7  
19.2  
15.0  
23.3  
19.7  
16.6  
28.0  
23.9  
20.3  
30.1  
25.9  
22.0  
28.0  
23.9  
20.3  
32.1  
27.7  
23.6  
34.0  
29.5  
25.1  
38.8  
32.9  
27.5  
43.0  
36.8  
30.7  
46.9  
40.3  
33.6  
49.2  
42.0  
35.3  
53.2  
45.7  
38.4  
57.0  
49.1  
41.2  
72.3  
61.5  
51.6  
76.7  
65.5  
54.9  
80.8  
69.2  
58.1  
84.7  
72.8  
61.1  
99.2  
86.4  
74.4  
103.1  
90.0  
78.8  
106.9  
93.6  
81.9  
110.5  
97.1  
84.9  
23.7  
20.0  
16.1  
20.6  
17.3  
14.0  
26.6  
22.4  
18.1  
29.1  
24.6  
19.9  
29.3  
25.1  
20.9  
35.7  
30.7  
25.5  
38.7  
33.2  
27.6  
35.7  
30.7  
25.5  
41.4  
35.5  
29.6  
43.8  
37.7  
31.4  
49.4  
42.2  
34.9  
55.1  
47.1  
39.0  
60.2  
51.5  
42.6  
62.9  
53.8  
44.6  
68.3  
58.5  
48.5  
73.2  
62.7  
52.0  
92.2  
78.9  
65.3  
98.0  
83.9  
69.5  
103.6  
88.7  
73.5  
108.8  
93.1  
77.2  
128.3  
110.9  
93.2  
133.7  
115.6  
97.2  
138.9  
120.1  
101.0  
143.8  
124.4  
104.7  
23.7  
20.0  
16.1  
20.6  
17.3  
14.0  
26.6  
22.4  
18.1  
29.1  
24.6  
19.9  
29.3  
25.1  
20.9  
35.7  
30.7  
25.5  
38.7  
33.2  
27.6  
35.7  
30.7  
25.5  
41.4  
35.5  
29.6  
43.8  
37.7  
31.4  
49.4  
42.2  
34.9  
55.1  
47.1  
39.0  
60.2  
51.5  
42.6  
62.9  
53.8  
44.6  
68.3  
58.5  
48.5  
73.2  
62.7  
52.0  
92.2  
78.9  
65.3  
98.0  
83.9  
69.5  
103.6  
88.7  
73.5  
108.8  
93.1  
77.2  
128.3  
110.9  
93.2  
133.7  
115.6  
97.2  
138.9  
120.1  
101.0  
143.8  
124.4  
104.7  
33.0  
25.1  
15.9  
29.3  
22.3  
14.0  
36.5  
27.5  
17.7  
39.5  
30.0  
19.3  
42.4  
34.0  
24.5  
49.4  
39.6  
28.7  
52.3  
42.0  
30.4  
49.4  
39.6  
28.7  
54.9  
44.1  
32.0  
57.3  
46.0  
33.5  
69.0  
54.6  
38.6  
75.1  
59.6  
42.1  
80.4  
63.8  
45.3  
86.5  
68.8  
48.8  
92.1  
73.3  
52.2  
97.1  
77.4  
55.2  
128.7  
102.3  
72.7  
135.0  
107.4  
76.4  
140.9  
112.1  
79.7  
146.3  
116.5  
82.9  
168.6  
137.6  
103.5  
173.1  
141.4  
106.5  
177.3  
144.9  
109.4  
181.1  
148.1  
112.1  
18.0  
14.7  
11.3  
15.9  
12.9  
9.8  
20.0  
16.3  
12.6  
21.8  
17.9  
13.9  
22.6  
19.0  
15.2  
26.7  
22.5  
18.2  
28.4  
24.1  
19.6  
26.7  
22.5  
18.2  
30.1  
25.6  
20.9  
31.6  
26.9  
22.1  
37.3  
31.2  
24.9  
40.9  
34.4  
27.7  
44.1  
37.3  
30.2  
46.9  
39.5  
31.7  
50.3  
42.5  
34.4  
53.4  
45.3  
36.8  
69.5  
58.3  
46.7  
73.2  
61.6  
49.5  
76.7  
64.7  
52.2  
80.0  
67.6  
54.7  
92.0  
79.1  
65.7  
95.0  
81.8  
68.3  
97.8  
84.4  
70.7  
100.4  
86.9  
73.1  
33.0  
25.3  
17.6  
29.4  
22.4  
15.4  
36.3  
27.9  
19.6  
39.3  
30.3  
21.4  
42.2  
33.8  
25.1  
49.0  
39.6  
29.7  
52.0  
42.1  
31.7  
49.0  
39.6  
29.7  
54.7  
44.3  
33.5  
57.1  
46.3  
35.2  
68.6  
54.6  
40.2  
74.5  
59.7  
44.2  
80.0  
64.1  
47.7  
85.9  
68.8  
51.1  
91.8  
73.5  
54.8  
96.4  
77.7  
58.1  
127.6  
102.2  
75.5  
134.1  
107.4  
79.7  
140.2  
112.3  
83.5  
145.8  
116.8  
87.1  
168.3  
138.7  
107.5  
173.2  
142.9  
111.0  
177.7  
146.8  
114.4  
181.9  
150.4  
117.5  
21.7  
18.5  
15.6  
19.1  
16.2  
13.5  
24.1  
20.7  
17.5  
26.4  
22.7  
19.4  
26.9  
23.2  
19.7  
31.8  
27.9  
24.0  
34.2  
30.0  
25.9  
31.8  
27.9  
24.0  
36.3  
32.0  
27.8  
38.3  
33.9  
29.6  
44.6  
38.6  
33.0  
49.1  
42.9  
36.9  
53.3  
46.8  
40.5  
56.2  
49.0  
42.1  
60.7  
53.1  
45.8  
64.5  
56.9  
49.3  
82.8  
72.1  
61.6  
87.6  
76.4  
65.6  
92.2  
80.6  
69.4  
96.6  
84.5  
73.0  
111.0  
98.6  
86.3  
115.1  
102.5  
90.1  
119.1  
106.3  
93.7  
122.8  
110.0  
97.2  
41.8  
33.6  
25.1  
37.2  
30.2  
22.3  
45.8  
37.0  
27.7  
49.4  
40.2  
29.8  
51.8  
43.5  
34.0  
59.9  
50.3  
39.5  
63.3  
53.1  
41.9  
59.9  
50.3  
39.5  
66.3  
55.6  
44.0  
68.9  
57.9  
45.8  
84.6  
70.6  
54.7  
91.8  
76.5  
59.4  
97.9  
81.7  
63.4  
105.6  
88.2  
68.7  
112.2  
93.7  
72.9  
117.9  
98.5  
77.2  
157.6  
131.6  
102.8  
165.0  
137.7  
107.2  
171.8  
143.4  
112.2  
178.0  
148.6  
115.8  
200.7  
170.2  
137.1  
205.7  
174.4  
140.6  
210.2  
178.3  
143.8  
214.3  
181.8  
146.6  
21.1  
17.8  
14.6  
18.7  
15.8  
12.9  
23.3  
19.7  
16.3  
25.3  
21.6  
17.8  
25.9  
22.4  
18.7  
30.3  
26.3  
22.2  
32.2  
28.1  
23.8  
30.3  
26.3  
22.2  
33.9  
29.7  
25.3  
35.5  
31.2  
26.7  
42.7  
36.9  
30.9  
46.7  
40.5  
34.0  
50.2  
43.7  
36.9  
53.6  
46.4  
39.0  
57.2  
49.8  
42.0  
60.6  
52.8  
45.0  
79.5  
68.8  
57.8  
83.6  
72.4  
60.9  
87.4  
75.9  
64.1  
90.9  
79.1  
66.9  
102.8  
90.5  
78.1  
105.9  
93.4  
80.8  
108.8  
96.2  
83.4  
111.5  
98.9  
85.9  
41.5  
33.8  
25.5  
37.0  
30.2  
22.6  
45.5  
37.1  
28.1  
49.0  
40.0  
30.4  
51.5  
43.1  
34.3  
59.6  
49.9  
39.9  
62.6  
52.9  
42.3  
59.6  
49.9  
39.9  
65.8  
55.5  
44.5  
68.8  
57.8  
46.4  
83.7  
70.1  
55.2  
91.5  
76.1  
60.1  
97.5  
81.2  
64.3  
105.3  
87.9  
69.4  
111.5  
93.4  
73.9  
116.8  
98.1  
77.9  
156.4  
131.1  
103.2  
164.4  
137.3  
108.3  
170.2  
143.0  
113.0  
177.2  
148.1  
117.4  
200.3  
170.6  
139.1  
205.3  
175.2  
143.2  
210.2  
179.5  
146.9  
214.7  
183.5  
150.4  
24.8  
21.6  
18.5  
21.9  
19.0  
16.2  
27.4  
24.0  
20.7  
29.8  
26.2  
22.7  
30.1  
26.5  
23.1  
35.5  
31.5  
27.7  
37.8  
33.8  
29.8  
35.5  
31.5  
27.7  
40.1  
36.0  
31.8  
42.3  
37.9  
33.7  
49.8  
44.2  
38.5  
55.0  
48.8  
42.7  
59.4  
52.9  
46.6  
63.0  
55.9  
48.8  
67.5  
60.2  
52.9  
71.6  
64.1  
56.7  
92.9  
82.5  
71.8  
98.2  
87.1  
76.1  
102.6  
91.5  
80.2  
107.4  
95.7  
84.2  
121.7  
109.8  
97.9  
125.9  
113.9  
101.9  
129.9  
117.8  
105.7  
133.8  
121.6  
109.3  
700  
600  
800  
900  
800  
1000  
1100  
1000  
1200  
1300  
1400  
1600  
1800  
1800  
2000  
2200  
2600  
2800  
3000  
3200  
3600  
3800  
4000  
4200  
5
30  
/
8
11/8  
7
40  
/
8
11/8  
LEGEND  
*Capacity based on R-22 refrigerant at 105 F liquid temperature and 10 F  
superheat.  
MBtuh — Capacity (Btuh in thousands)  
SH  
TH  
Sensible Heat  
Total Heat  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
UNIT HORSEPOWER DATA TABLE  
TOTAL STATIC PRESSURE (in. wg)  
0.6 0.7 0.8  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
UNIT  
SIZE  
42BHC,BVC  
BLOWER  
CFM  
0.3  
0.4  
0.5  
0.9  
1.0  
1.1  
400 677 0.05 770 0.07 857 0.09 937 0.11 1009 0.13 1077 0.14 1140 0.16 1200 0.18 1257 0.20  
500 729 0.07 798 0.09 873 0.33 947 0.13 1019 0.16 1086 0.18 1150 0.20 1210 0.23 1267 0.25  
600 809 0.11 856 0.12 909 0.14 968 0.16 1031 0.18 1093 0.21 1154 0.24 1214 0.26 1271 0.29  
700 906 0.15 939 0.17 977 0.18 1020 0.20 1067 0.22 1118 0.25 1171 0.28 1225 0.31 1278 0.34  
800 1012 0.22 1038 0.23 1068 0.25 1100 0.27 1135 0.29 1174 0.31 1215 0.33 1259 0.36 1305 0.39  
9 in. x 4 in.  
06  
08  
10  
12  
16  
600 670 0.07 745 0.09 815 0.11 880 0.12 942 0.14 1000 0.16 1055 0.18 1108 0.20 1159 0.22  
700 706 0.10 776 0.11 842 0.13 903 0.15 962 0.17 1018 0.19 1071 0.21 1123 0.24 1172 0.26  
800 748 0.12 812 0.14 874 0.17 932 0.19 988 0.21 1041 0.23 1092 0.25 1142 0.28 1190 0.30  
900 794 0.16 853 0.18 910 0.20 965 0.23 1018 0.25 1069 0.28 1118 0.30 1165 0.33 1211 0.35  
9 in. x 6 in.  
10 in. x 4 in.  
10 in. x 7 in.  
11 in. x 10 in.  
1000  
1103 0.34 1149 0.36 1193 0.39 1236 0.41  
800 817 0.17 854 0.19 896 0.21 943 0.23 992 0.25 1042 0.28 1091 0.31 1139 0.34 1185 0.36  
900 897 0.23 926 0.25 959 0.27 996 0.29 1036 0.31 1079 0.34 1123 0.37 1168 0.40 1212 0.43  
1000 982 0.31 1006 0.33 1033 0.35 1062 0.37 1095 0.39 1130 0.41 1167 0.44 1206 0.47 1246 0.50  
1100 1068 0.41 1088 0.42 1111 0.44 1135 0.46 1161 0.48 1190 0.50 1221 0.53 1254 0.56 1288 0.59  
1200 1143 0.51 1172 0.53 1192 0.55 1212 0.57 1234 0.59 1258 0.62 1284 0.64 1311 0.67 1340 0.70  
1000 629 0.13 688 0.15 744 0.18 789 0.20 849 0.22 898 0.24 946 0.26 991 0.29 1035 0.31  
1100 656 0.16 712 0.19 765 0.21 816 0.23 865 0.26 912 0.28 958 0.30 1002 0.33 1044 0.35  
1200 686 0.20 738 0.22 789 0.25 837 0.27 884 0.30 929 0.32 973 0.35 1015 0.38 1056 0.40  
1300 717 0.24 767 0.27 814 0.29 861 0.32 905 0.35 948 0.37 990 0.40 1031 0.43 1071 0.46  
1400  
1400  
968 0.43 1008 0.46 1048 0.49 1086 0.52  
648 0.20 699 0.23 747 0.26 792 0.29 834 0.31 875 0.34 913 0.37 949 0.40  
1500 611 0.20 664 0.23 714 0.26 761 0.29 805 0.32 847 0.35 887 0.38 925 0.41 961 0.44  
1600 631 0.24 682 0.27 730 0.30 776 0.33 819 0.36 860 0.39 899 0.42 937 0.45 973 0.48  
1700 651 0.27 700 0.30 747 0.34 791 0.37 834 0.40 874 0.43 913 0.47 950 0.50 986 0.53  
1800  
1800  
890 0.49 928 0.52 965 0.56 1000 0.60  
629 0.32 672 0.36 712 0.39 751 0.43 788 0.46 824 0.50 860 0.54 894 0.57  
1900 603 0.32 646 0.36 686 0.40 726 0.43 763 0.47 800 0.51 835 0.55 869 0.59 903 0.62  
2000 621 0.36 662 0.40 702 0.44 740 0.48 777 0.52 812 0.56 846 0.60 880 0.64 913 0.68  
2100 639 0.41 679 0.45 718 0.49 755 0.53 790 0.57 825 0.61 859 0.66 891 0.70 923 0.74  
2200 658 0.46 697 0.50 734 0.54 770 0.59 805 0.63 839 0.67 871 0.71 903 0.76 935 0.80  
12 in. x 9 in.  
20  
2300  
2400  
887 0.78 918 0.83 947 0.87  
932 0.90 961 0.95  
2400 604 0.43 647 0.47 688 0.52 728 0.57 766 0.62 803 0.66 840 0.71 875 0.76 909 0.82  
2600 633 0.52 674 0.57 713 0.62 750 0.67 787 0.72 823 0.77 857 0.82 891 0.88 924 0.93  
2800 660 0.62 701 0.67 739 0.73 775 0.78 810 0.84 844 0.89 877 0.95 909 1.01 941 1.06  
3000 694 0.74 730 0.79 766 0.85 800 0.91 834 0.97 866 1.03 898 1.09 929 1.15 960 1.21  
3200 726 0.87 760 0.93 794 0.99 827 1.05 859 1.12 890 1.18 921 1.24 951 1.30 980 1.37  
12 in. x 12 in.  
15 in. x 12 in.  
30  
40  
3400  
944 1.42 972 1.48 1000 1.55  
3400  
3600  
3800  
609 0.79 639 0.85 668 0.91 697 0.97 724 1.04 752 1.10 778 1.16  
627 0.90 656 0.96 684 1.03 712 1.09 738 1.16 765 1.22 791 1.29  
616 0.95 646 1.02 674 1.09 701 1.16 727 1.22 753 1.29 779 1.36 804 1.43  
4000 607 1.01 637 1.08 665 1.15 692 1.22 718 1.29 744 1.37 769 1.44 794 1.51 818 1.58  
4200 629 1.14 657 1.22 684 1.30 711 1.37 736 1.45 761 1.52 786 1.59 809 1.67 833 1.74  
4400  
806 1.79 829 1.87 852 1.95  
LEGEND  
Application not available  
Bhp — Horsepower  
NOTES:  
1. Contact factory if higher horsepower selection is required for a  
given cfm and total static pressure.  
2. The variable pitch motor sheave provided will allow + 15% rpm  
3
adjustment. Unit sizes 06, 08, 10 and 12 have  
/
in. bore fan  
4
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.  
3. Consult factory for motor selections when outlet air temperature  
exceeds 104 F on hot water coil applications.  
4. Single-phase motors are only available to 2 hp. Three-phase  
motors are available from 1/2 to 3 hp.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT HORSEPOWER DATA TABLE (cont)  
TOTAL STATIC PRESSURE (in. wg)  
1.5 1.6 1.7  
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp  
UNIT  
SIZE  
42BHC,BVC  
BLOWER  
CFM  
1.2  
1.3  
1.4  
1.8  
1.9  
2.0  
400  
500 1321 0.27 1374 0.30  
06  
08  
10  
12  
16  
9 in. x 4 in.  
600 1326 0.32 1378 0.35 1429 0.38 1478 0.40  
700 1331 0.37 1383 0.40 1433 0.43 1482 0.46 1529 0.50 1575 0.53 1619 0.56 1662 0.59 1705 0.63  
800 1352 0.42 1399 0.46 1446 0.49 1492 0.52 1538 0.56 1583 0.60 1627 0.63 1670 0.67 1712 0.71  
600 1208 0.24  
700 1220 0.28 1266 0.30 1310 0.33 1353 0.35 1395 0.37  
9 in. x 6 in.  
10 in. x 4 in.  
10 in. x 7 in.  
11 in. x 10 in.  
800 1236 0.33 1280 0.35 1324 0.38 1366 0.40 1407 0.43 1447 0.45 1486 0.48 1524 0.51 1562 0.53  
900 1256 0.38 1299 0.40 1341 0.43 1382 0.46 1423 0.49 1462 0.52 1500 0.54 1537 0.57 1574 0.60  
1000 1278 0.44 1319 0.47 1359 0.49 1398 0.52 1436 0.55 1474 0.57 1510 0.60 1546 0.63 1582 0.65  
800 1229 0.39 1271 0.42 1311 0.44 1350 0.47 1388 0.50 1425 0.52 1461 0.55 1496 0.58 1530 0.60  
900 1254 0.46 1296 0.49 1336 0.52 1375 0.55 1413 0.58 1450 0.61 1486 0.64 1520 0.67 1554 0.70  
1000 1286 0.53 1326 0.57 1365 0.60 1403 0.64 1441 0.67 1477 0.70 1513 0.74 1547 0.77 1581 0.81  
1100 1324 0.62 1360 0.66 1396 0.69 1433 0.73 1469 0.77 1504 0.80 1539 0.84 1573 0.88 1606 0.92  
1200 1370 0.73 1402 0.76 1434 0.80 1467 0.84 1501 0.87 1534 0.91 1567 0.95 1600 0.99 1633 1.03  
1000 1078 0.33 1120 0.36 1160 0.38 1200 0.40 1239 0.43 1276 0.45 1313 0.47 1349 0.50 1385 0.52  
1100 1086 0.38 1126 0.40 1166 0.43 1222 0.48 1242 0.48 1279 0.51 1315 0.53 1350 0.56 1396 0.61  
1200 1097 0.43 1136 0.46 1174 0.48 1211 0.51 1248 0.54 1284 0.57 1319 0.59 1353 0.62 1387 0.65  
1300 1110 0.49 1148 0.51 1185 0.54 1221 0.57 1257 0.60 1292 0.63 1326 0.66 1359 0.69 1392 0.72  
1400 1124 0.55 1162 0.58 1198 0.61 1234 0.64 1269 0.67 1304 0.70 1338 0.73 1371 0.77 1404 0.80  
1400 985 0.42 1018 0.45 1051 0.48 1083 0.51 1113 0.54 1143 0.57 1172 0.59 1200 0.62 1227 0.65  
1500 996 0.47 1030 0.50 1062 0.53 1094 0.56 1124 0.59 1154 0.62 1182 0.65 1210 0.68 1238 0.71  
1600 1008 0.52 1041 0.55 1074 0.58 1105 0.61 1135 0.64 1165 0.67 1193 0.71 1221 0.74 1248 0.77  
1700 1020 0.57 1053 0.60 1085 0.63 1116 0.67 1146 0.70 1176 0.73 1204 0.77 1232 0.80 1259 0.84  
1800 1033 0.63 1065 0.66 1097 0.70 1128 0.73 1157 0.77 1186 0.80 1215 0.84 1242 0.87 1268 0.90  
1800 927 0.61 959 0.65 991 0.69 1022 0.73 1052 0.77  
1900 935 0.66 967 0.70 998 0.74 1028 0.78 1058 0.83 1087 0.87 1115 0.91  
2000 944 0.72 975 0.76 1006 0.80 1035 0.85 1065 0.89 1093 0.93 1121 0.97 1149 1.02 1176 1.06  
2100 954 0.78 985 0.82 1014 0.87 1043 0.91 1072 0.96 1100 1.00 1128 1.04 1155 1.09 1181 1.14  
2200 965 0.85 995 0.89 1024 0.94 1052 0.98 1080 1.03 1108 1.07 1135 1.12 1162 1.17 1188 1.21  
2300 976 0.92 1004 0.96 1032 1.01 1060 1.05 1087 1.10 1114 1.14 1141 1.19 1167 1.24 1193 1.28  
2400 989 0.99 1016 1.04 1044 1.09 1071 1.13 1097 1.18 1124 1.23 1150 1.28 1175 1.32 1200 1.37  
2400 943 0.87 976 0.92 1008 0.97 1039 1.03 1070 1.08 1101 1.14 1130 1.20 1160 1.26 1189 1.32  
2600 956 0.99 988 1.04 1019 1.10 1049 1.16 1079 1.21 1108 1.27 1137 1.33 1166 1.39 1194 1.45  
2800 972 1.12 1002 1.18 1032 1.24 1062 1.30 1090 1.36 1119 1.42 1147 1.48 1174 1.54 1201 1.61  
3000 990 1.27 1019 1.33 1048 1.39 1076 1.45 1104 1.52 1131 1.58 1158 1.65 1185 1.71 1211 1.78  
3200 1009 1.43 1037 1.50 1065 1.56 1093 1.63 1120 1.69 1146 1.76 1172 1.83 1198 1.90 1224 1.97  
3400 1027 1.61 1055 1.68 1082 1.75 1108 1.82 1135 1.89 1161 1.96 1186 2.03 1212 2.10 1237 2.17  
3400 805 1.23 830 1.30 856 1.36 881 1.43 905 1.51 930 1.58 954 1.65 978 1.73 1001 1.81  
3600 816 1.36 841 1.43 865 1.50 889 1.57 913 1.64 937 1.72 960 1.79 983 1.87 1006 1.95  
3800 828 1.50 852 1.57 876 1.64 899 1.72 923 1.79 945 1.87 968 1.95 990 2.02 1012 2.10  
4000 842 1.65 865 1.73 888 1.80 911 1.88 933 1.95 955 2.03 977 2.11 999 2.19 1020 2.27  
4200 856 1.82 879 1.90 901 1.97 923 2.05 945 2.13 966 2.21 987 2.29 1008 2.37 1029 2.46  
4400 874 2.03 896 2.11 917 2.19 938 2.27 959 2.35 980 2.43 1000 2.51 1020 2.60 1040 2.68  
20  
12 in. x 9 in.  
12 in. x 12 in.  
30  
40  
15 in. x 12 in.  
LEGEND  
Application not available  
Bhp — Horsepower  
NOTES:  
1. Contact factory if higher horsepower selection is required for a  
given cfm and total static pressure.  
2. The variable pitch motor sheave provided will allow + 15% rpm  
3
adjustment. Unit sizes 06, 08, 10 and 12 have  
/
in. bore fan  
4
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.  
3. Consult factory for motor selections when outlet air temperature  
exceeds 104 F on hot water coil applications.  
4. Single-phase motors are only available to 2 hp. Three-phase  
motors are available from 1/2 to 3 hp.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
42BHC,BVC COMPONENT STATIC RESISTANCE (in. wg)  
WET COIL  
6
DRY COIL  
4
TWO-INCH  
PLEATED  
MERV 11  
FILTER  
ONE-INCH TWO-INCH TWO-INCH  
PLEATED THROWAWAY PLEATED  
UNIT  
SIZE 42BHC,BVC  
NOMINAL  
CFM  
CABINET  
4
8
1
2
6
8
FILTER  
FILTER  
FILTER  
Row Row Row Row Row Row Row Row  
400  
500  
600  
700  
800  
0.02  
0.03  
0.04  
0.06  
0.08  
0.04  
0.06  
0.08  
0.10  
0.12  
0.04  
0.05  
0.06  
0.08  
0.09  
0.06  
0.08  
0.09  
0.11  
0.13  
0.08 0.12 0.16 0.01 0.02 0.04 0.06 0.08  
0.13 0.19 0.25 0.01 0.03 0.06 0.09 0.12  
0.18 0.27 0.36 0.02 0.04 0.08 0.13 0.17  
0.25 0.37 0.50 0.03 0.06 0.12 0.17 0.23  
0.32 0.49 0.65 0.04 0.08 0.15 0.23 0.30  
0.18 0.27 0.36 0.02 0.04 0.08 0.13 0.17  
0.25 0.37 0.50 0.03 0.06 0.12 0.17 0.23  
0.32 0.49 0.65 0.04 0.08 0.15 0.23 0.30  
0.41 0.61 0.82 0.05 0.10 0.19 0.29 0.38  
0.51 0.76 1.01 0.06 0.12 0.24 0.35 0.47  
0.15 0.23 0.31 0.02 0.04 0.07 0.11 0.14  
0.19 0.29 0.39 0.02 0.05 0.09 0.14 0.18  
0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22  
0.29 0.44 0.58 0.03 0.07 0.14 0.20 0.27  
0.35 0.52 0.69 0.04 0.08 0.16 0.24 0.32  
0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22  
0.29 0.44 0.58 0.03 0.07 0.14 0.20 0.27  
0.35 0.52 0.69 0.04 0.08 0.16 0.24 0.32  
0.41 0.61 0.81 0.05 0.09 0.19 0.28 0.38  
0.47 0.71 0.94 0.05 0.11 0.22 0.33 0.44  
0.03  
0.05  
0.08  
0.10  
0.14  
0.08  
0.10  
0.14  
0.17  
0.21  
0.07  
0.09  
0.11  
0.14  
0.16  
0.11  
0.14  
0.16  
0.19  
0.22  
0.02  
0.03  
0.04  
0.06  
0.08  
0.04  
0.06  
0.08  
0.10  
0.12  
0.04  
0.05  
0.06  
0.08  
0.09  
0.06  
0.08  
0.09  
0.11  
0.13  
0.03  
0.04  
0.06  
0.08  
0.11  
0.06  
0.08  
0.11  
0.14  
0.17  
0.06  
0.07  
0.09  
0.11  
0.13  
0.09  
0.11  
0.13  
0.15  
0.17  
0.06  
0.09  
0.12  
0.17  
0.22  
0.12  
0.17  
0.22  
0.28  
0.34  
0.12  
0.15  
0.18  
0.22  
0.26  
0.18  
0.22  
0.26  
0.31  
0.36  
06  
08  
10  
12  
16  
600  
700  
800  
900  
1000  
800  
900  
1000  
1100  
1200  
1000  
1100  
1200  
1300  
1400  
1400  
1500  
1600  
1700  
1800  
0.07  
0.09  
0.10  
0.11  
0.12  
0.26 0.39 0.52 0.03 0.06 0.12 0.18 0.24  
0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28  
0.34 0.51 0.68 0.04 0.08 0.16 0.24 0.32  
0.38 0.58 0.77 0.04 0.09 0.18 0.27 0.36  
0.43 0.65 0.86 0.05 0.10 0.20 0.30 0.40  
0.13  
0.15  
0.17  
0.19  
0.21  
0.07  
0.09  
0.10  
0.11  
0.12  
0.10  
0.12  
0.13  
0.15  
0.17  
0.21  
0.24  
0.27  
0.31  
0.35  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
0.12  
0.13  
0.14  
0.16  
0.17  
0.19  
0.21  
0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28  
0.34 0.50 0.67 0.04 0.08 0.16 0.23 0.31  
0.37 0.56 0.74 0.04 0.09 0.17 0.26 0.35  
0.41 0.61 0.82 0.05 0.10 0.19 0.29 0.38  
0.45 0.67 0.90 0.05 0.10 0.21 0.31 0.42  
0.49 0.74 0.98 0.06 0.11 0.23 0.34 0.46  
0.54 0.80 1.07 0.06 0.12 0.25 0.37 0.50  
0.13  
0.14  
0.16  
0.18  
0.19  
0.21  
0.23  
0.08  
0.08  
0.09  
0.10  
0.11  
0.12  
0.13  
0.10  
0.12  
0.13  
0.14  
0.16  
0.17  
0.19  
0.21  
0.24  
0.26  
0.29  
0.32  
0.35  
0.38  
20  
2400  
2600  
2800  
3000  
3200  
3400  
3400  
3600  
3800  
4000  
4200  
4400  
0.11  
0.13  
0.15  
0.18  
0.20  
0.23  
0.13  
0.15  
0.16  
0.18  
0.20  
0.22  
0.22 0.33 0.43 0.03 0.05 0.10 0.15 0.20  
0.25 0.38 0.51 0.03 0.06 0.12 0.18 0.24  
0.29 0.44 0.59 0.03 0.07 0.14 0.21 0.27  
0.34 0.51 0.68 0.04 0.08 0.16 0.24 0.31  
0.39 0.58 0.77 0.04 0.09 0.18 0.27 0.36  
0.43 0.65 0.87 0.05 0.10 0.20 0.30 0.40  
0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22  
0.27 0.40 0.54 0.03 0.06 0.12 0.19 0.25  
0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28  
0.33 0.50 0.66 0.04 0.08 0.15 0.23 0.31  
0.36 0.55 0.73 0.04 0.08 0.17 0.25 0.34  
0.40 0.60 0.80 0.05 0.09 0.19 0.28 0.37  
0.13  
0.15  
0.17  
0.20  
0.23  
0.25  
0.15  
0.16  
0.18  
0.20  
0.22  
0.25  
0.07  
0.09  
0.10  
0.12  
0.13  
0.15  
0.09  
0.10  
0.11  
0.12  
0.13  
0.14  
0.10  
0.12  
0.14  
0.16  
0.18  
0.20  
0.12  
0.13  
0.15  
0.16  
0.18  
0.20  
0.21  
0.24  
0.28  
0.32  
0.37  
0.42  
0.24  
0.27  
0.30  
0.33  
0.37  
0.40  
30  
40  
Hydronic coil pressure drop — All of the factory’s hy-  
dronic coils have a coefficient of velocity (Cv) resistance  
factor assigned to assist in a more accurate determination  
of water pressure drop (see Cv Factor by Coil and Unit Size  
table below).  
Coil pressure drop (ft wg):  
P = (GPM2/Cv2 ) x 2.31  
or  
P = [GPM/(0.658 x Cv)]2  
or  
Calculating pressure drop:  
Refer to the Water Pressure Drop for Cv Factor and  
Water Flow Rate table. See example on page 22.  
The Cv factor is equal to the flow rate of water in gpm  
through a piping component when the pressure drop  
through the component is 1.0 pounds per square inch  
(psi), or 2.31 ft wg.  
P (ft wg) = P (psi) x 2.31  
Use the Cv factor from the Cv Factor by Coil and Unit  
Size table to determine the water coil pressure drop.  
Cv FACTOR BY COIL AND UNIT SIZE  
42BHC,BVC UNIT SIZE  
COIL TYPE  
06 08 10 12 16 20  
1.4 1.4 1.3 1.3 1.2 1.2  
2.4 2.4 2.2 2.2 2.0 1.9  
4.7 4.7 4.4 4.4 7.2 6.8 13.2 12.4  
4.0 4.0 3.7 3.7 6.1 5.8 11.4 10.5  
30  
0.8  
1.6  
40  
0.7  
1.4  
1 Row Heat Only  
2 Row Heat Only  
4 Row Heat/Cool  
6 Row Heat/Cool  
8 Row Heat/Cool  
3.6 3.6 3.3 3.3 5.3 5.1  
9.8  
9.0  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42BHC,BVC WATER PRESSURE DROP (ft. wg) FOR CV FACTOR AND WATER FLOW RATE (GPM)  
WATER FLOW RATE (GPM)  
Cv  
FACTORS  
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 10.5 11.0 11.5 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0  
0.8  
0.9  
1.0  
1.1  
1.2  
0.9 3.6 8.1 14.4 22.5 32.4  
0.7 2.8 6.4 11.4 17.8 25.6 34.9  
0.5 2.3 5.2 9.2 14.4 20.7 28.2 36.9  
0.4 1.9 4.2 7.6 11.9 17.1 23.3 30.5  
1.6 3.6 6.4 10.0 14.4 19.6 25.6 32.4  
1.3  
1.4  
1.5  
1.6  
1.7  
1.3 3.0 5.4 8.5 12.3 16.7 21.8 27.6 34.1  
1.1 2.6 4.7 7.3 10.6 14.4 18.8 23.8 29.4  
1.0 2.3 4.1 6.4 9.2 12.5 16.4 20.7 25.6 31.0  
0.9 2.0 3.6 5.6 8.1 11.0 14.4 18.2 22.5 27.2 32.4  
0.8 1.8 3.2 4.9 7.1 9.7 12.7 16.1 19.9 24.1 28.7 33.7  
1.8  
1.9  
2.0  
2.1  
2.2  
0.7 1.6 2.8 4.4 6.4 8.7 11.4 14.4 17.8 21.5 25.6 30.1  
0.6 1.4 2.5 4.0 5.7 7.8 10.2 12.9 15.9 19.3 23.0 27.0 31.3  
0.5 1.3 2.3 3.6 5.2 7.0 9.2 11.6 14.4 17.4 20.7 24.4 28.2 32.4  
0.5 1.1 2.0 3.2 4.7 6.4 8.3 10.6 13.0 15.8 18.8 22.1 25.6 29.4 33.5  
0.4 1.0 1.9 2.9 4.2 5.8 7.6 9.6 11.9 14.4 17.1 20.1 23.3 26.8 30.5  
2.3  
2.4  
2.5  
2.6  
2.7  
0.9 1.7 2.7 3.9 5.3 6.9 8.8 10.9 13.2 15.7 18.4 21.3 24.5 27.9 31.5  
0.9 1.6 2.5 3.6 4.9 6.4 8.1 10.0 12.1 14.4 16.9 19.6 22.5 25.6 28.9 32.4  
0.8 1.4 2.3 3.3 4.5 5.9 7.4 9.2 11.1 13.3 15.6 18.1 20.7 23.6 26.7 29.9 33.3  
0.7 1.3 2.1 3.0 4.1 5.4 6.9 8.5 10.3 12.3 14.4 16.7 19.2 21.8 24.6 27.6 30.8  
0.7 1.2 1.9 2.8 3.8 5.0 6.4 7.9 9.5 11.4 13.3 15.5 17.8 20.2 22.8 25.6 28.5 31.6  
2.8  
2.9  
3.0  
3.2  
3.4  
0.6 1.1 1.8 2.6 3.6 4.7 5.9 7.3 8.9 10.6 12.4 14.4 16.5 18.8 21.2 23.8 26.5 29.4 32.4  
0.6 1.1 1.7 2.4 3.3 4.3 5.5 6.8 8.3 9.8 11.6 13.4 15.4 17.5 19.8 22.2 24.7 27.4 30.2  
0.5 1.0 1.6 2.3 3.1 4.1 5.2 6.4 7.7 9.2 10.8 12.5 14.4 16.4 18.5 20.7 23.1 25.6 28.2 31.0  
0.5 0.9 1.4 2.0 2.7 3.6 4.5 5.6 6.8 8.1 9.5 11.0 12.6 14.4 16.3 18.2 20.3 22.5 24.8 27.2 29.8  
0.8 1.2 1.8 2.4 3.2 4.0 4.9 6.0 7.1 8.4 9.7 11.2 12.7 14.4 16.1 18.0 19.9 22.0 24.1 26.4 28.7  
3.6  
3.8  
4.0  
4.2  
4.4  
0.7 1.1 1.6 2.1 2.8 3.6 4.4 5.3 6.4 7.5 8.7 10.0 11.4 12.8 14.4 16.0 17.8 19.6 21.5 23.5 25.6 30.1  
0.6 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.7 6.7 7.8 9.0 10.2 11.5 12.9 14.4 15.9 17.6 19.3 21.1 23.0 27.0 31.3  
0.5 0.9 1.3 1.7 2.3 2.9 3.6 4.3 5.2 6.1 7.0 8.1 9.2 10.4 11.6 13.0 14.4 15.9 17.4 19.0 20.7 24.4 28.2  
0.5 0.8 1.1 1.6 2.0 2.6 3.2 3.9 4.7 5.5 6.4 7.3 8.3 9.4 10.6 11.8 13.0 14.4 15.8 17.3 18.8 22.1 25.6 29.4  
0.4 0.7 1.0 1.4 1.9 2.4 2.9 3.6 4.2 5.0 5.8 6.7 7.6 8.6 9.6 10.7 11.9 13.1 14.4 15.7 17.1 20.1 23.3 26.8 30.5  
4.6  
4.8  
5.0  
5.3  
5.6  
0.6 0.9 1.3 1.7 2.2 2.7 3.3 3.9 4.6 5.3 6.1 6.9 7.8 8.8 9.8 10.9 12.0 13.2 14.4 15.7 18.4 21.3 24.5 27.9 31.5  
0.6 0.9 1.2 1.6 2.0 2.5 3.0 3.6 4.2 4.9 5.6 6.4 7.2 8.1 9.0 10.0 11.0 12.1 13.2 14.4 16.9 19.6 22.5 25.6 28.9  
0.5 0.8 1.1 1.4 1.8 2.3 2.7 3.3 3.9 4.5 5.2 5.9 6.6 7.4 8.3 9.2 10.1 11.1 12.2 13.3 15.6 18.1 20.7 23.6 26.7 29.9  
0.5 0.7 1.0 1.3 1.6 2.0 2.4 2.9 3.4 4.0 4.6 5.2 5.9 6.6 7.4 8.2 9.0 9.9 10.8 11.8 13.9 16.1 18.5 21.0 23.7 26.6 29.6  
0.4 0.6 0.9 1.1 1.4 1.8 2.2 2.6 3.1 3.6 4.1 4.7 5.3 5.9 6.6 7.3 8.1 8.9 9.7 10.6 12.4 14.4 16.5 18.8 21.2 23.8 26.5 29.4  
5.9  
6.2  
6.5  
6.8  
7.1  
0.6 0.8 1.0 1.3 1.6 2.0 2.3 2.8 3.2 3.7 4.2 4.7 5.3 5.9 6.6 7.3 8.0 8.7 9.5 11.2 13.0 14.9 16.9 19.1 21.5 23.9 26.5  
0.5 0.7 0.9 1.2 1.5 1.8 2.1 2.5 2.9 3.3 3.8 4.3 4.8 5.4 6.0 6.6 7.2 7.9 8.6 10.1 11.7 13.5 15.3 17.3 19.4 21.6 24.0  
0.4 0.6 0.8 1.1 1.3 1.6 1.9 2.3 2.6 3.0 3.5 3.9 4.4 4.9 5.4 6.0 6.6 7.2 7.8 9.2 10.7 12.3 13.9 15.8 17.7 19.7 21.8  
0.6 0.8 1.0 1.2 1.5 1.8 2.1 2.4 2.8 3.2 3.6 4.0 4.5 4.9 5.5 6.0 6.6 7.1 8.4 9.7 11.2 12.7 14.4 16.1 18.0 19.9  
0.5 0.7 0.9 1.1 1.3 1.6 1.9 2.2 2.5 2.9 3.3 3.7 4.1 4.5 5.0 5.5 6.0 6.6 7.7 8.9 10.3 11.7 13.2 14.8 16.5 18.3  
7.5  
8.0  
8.5  
9.0  
9.5  
0.5 0.6 0.8 1.0 1.2 1.4 1.7 2.0 2.3 2.6 2.9 3.3 3.7 4.1 4.5 4.9 5.4 5.9 6.9 8.0 9.2 10.5 11.8 13.3 14.8 16.4  
0.5 0.7 0.9 1.0 1.3 1.5 1.7 2.0 2.3 2.6 2.9 3.2 3.6 3.9 4.3 4.7 5.2 6.1 7.0 8.1 9.2 10.4 11.6 13.0 14.4  
0.5 0.6 0.8 0.9 1.1 1.3 1.5 1.8 2.0 2.3 2.5 2.8 3.2 3.5 3.8 4.2 4.6 5.4 6.2 7.1 8.1 9.2 10.3 11.5 12.7  
0.4 0.5 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8 3.1 3.4 3.7 4.1 4.8 5.5 6.4 7.3 8.2 9.2 10.2 11.4  
0.5 0.6 0.7 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8 3.1 3.3 3.6 4.3 5.0 5.7 6.5 7.4 8.2 9.2 10.2  
10.0  
10.5  
11.0  
11.5  
12.0  
0.4 0.5 0.7 0.8 0.9 1.1 1.3 1.4 1.6 1.8 2.0 2.3 2.5 2.7 3.0 3.3 3.9 4.5 5.2 5.9 6.6 7.4 8.3 9.2  
0.5 0.6 0.7 0.8 1.0 1.1 1.3 1.5 1.7 1.8 2.0 2.3 2.5 2.7 3.0 3.5 4.1 4.7 5.3 6.0 6.7 7.5 8.3  
0.4 0.5 0.6 0.8 0.9 1.0 1.2 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 3.2 3.7 4.2 4.8 5.5 6.1 6.8 7.6  
0.5 0.6 0.7 0.8 0.9 1.1 1.2 1.4 1.5 1.7 1.9 2.1 2.3 2.5 2.9 3.4 3.9 4.4 5.0 5.6 6.3 6.9  
0.4 0.5 0.6 0.7 0.9 1.0 1.1 1.3 1.4 1.6 1.7 1.9 2.1 2.3 2.7 3.1 3.6 4.1 4.6 5.2 5.7 6.4  
13.0  
14.0  
15.0  
16.0  
17.0  
0.4 0.5 0.6 0.7 0.8 0.9 1.1 1.2 1.3 1.5 1.6 1.8 1.9 2.3 2.6 3.0 3.5 3.9 4.4 4.9 5.4  
0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.3 1.4 1.5 1.7 1.9 2.3 2.6 3.0 3.4 3.8 4.2 4.7  
0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.7 2.0 2.3 2.6 2.9 3.3 3.7 4.1  
0.5 0.5 0.6 0.7 0.8 0.9 0.9 1.0 1.1 1.3 1.5 1.7 2.0 2.3 2.6 2.9 3.2 3.6  
0.5 0.5 0.6 0.7 0.8 0.8 0.9 1.0 1.1 1.3 1.5 1.8 2.0 2.3 2.5 2.8 3.2  
18.0  
19.0  
20.0  
0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8  
0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5  
0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.1 1.3 1.4 1.6 1.8 2.0 2.3  
NOTE: Table interpolation is permissible, and extrapolation is not rec-  
ommended.  
SOUND POWER DATA  
DISCHARGE SOUND RATINGS — A-WEIGHTED SOUND POWER LEVEL RATINGS* (dB)  
CENTER FREQUENCY (Hz)  
42BHC,BVC UNIT SIZE  
NOMINAL CFM  
125  
60  
60  
68  
68  
69  
67  
70  
78  
250  
57  
57  
65  
65  
66  
64  
67  
75  
500  
57  
57  
65  
65  
66  
64  
67  
75  
1000  
58  
58  
66  
66  
67  
65  
68  
76  
2000  
54  
54  
62  
62  
63  
61  
64  
72  
4000  
49  
8000  
42  
06  
08  
10  
12  
16  
20  
30  
40  
600  
800  
49  
42  
1000  
1200  
1600  
2000  
3000  
4000  
57  
50  
57  
50  
58  
51  
56  
49  
59  
52  
67  
60  
*These noise ratings are calculated values, not actual test values, and  
apply only to the discharge of the unit, not the radiated sound levels.  
Sound power is in decibels re 10e-12 w.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical wiring schematics  
BASE UNIT, SINGLE-PHASE POWER  
MOTOR CONTROL/DISCONNECT OPTION SINGLE-PHASE POWER  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BASE UNIT, THREE-PHASE POWER  
MOTOR CONTROL/DISCONNECT OPTION THREE-PHASE POWER  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical wiring schematics (cont)  
2-PIPE COOLING ONLY WITH SINGLE-SPEED FAN OPERATION AND HONEYWELL THERMOSTAT  
NOTES:  
1. Optional valves are field wired.  
2. No HW valve with electric heat.  
2-PIPE OR 4-PIPE HEATING/COOLING WITH SINGLE-SPEED  
FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT  
NOTES:  
1. Optional valves are field wired.  
2. No HW valve with electric heat.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical data  
42BHC,BVC ELECTRIC HEATER DATA AVAILABILITY  
42BHC,BVC ELECTRIC HEATER DATA  
42BHC UNIT SIZE  
kW  
FULL LOAD AMPS  
Single-Phase  
kW  
06  
08  
10  
12  
16  
20  
30  
40  
Three-Phase  
1
1.5  
2
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
120 V 208 V 240 V 277 V 208 V 240 V 480 V  
1
1.5  
2
8.3  
12.5  
16.7  
20.8  
25.0  
29.2  
33.3  
37.5  
41.7  
4.8  
7.2  
9.6  
12.0  
14.4  
16.8  
19.2  
21.6  
24.0  
28.8  
23.7  
38.5  
47.6  
4.2  
6.3  
3.6  
5.4  
2.8  
4.2  
2.4  
2.4  
1.2  
1.2  
2.5  
3
8.3  
7.2  
5.6  
4.8  
2.4  
2.5  
3
10.4  
12.5  
14.6  
16.7  
18.8  
20.8  
25.0  
29.2  
33.3  
41.3  
9.0  
6.9  
6.0  
3.0  
3.5  
4
10.8  
12.6  
14.4  
16.2  
18.1  
21.7  
25.3  
28.9  
35.7  
43.3  
8.3  
7.2  
3.6  
3.5  
4
9.7  
8.4  
4.2  
4.5  
5
11.1  
12.5  
13.9  
16.7  
19.4  
22.2  
27.5  
33.3  
41.6  
44.4  
9.6  
4.8  
4.5  
5
10.8  
12.0  
14.4  
16.8  
19.2  
23.8  
28.9  
36.1  
38.5  
47.9  
5.4  
6
G
G
G
G
6.0  
7
6
7.2  
8
7
8.4  
10  
12  
15  
16  
20  
25  
30  
35  
40  
8
9.6  
G
10  
12  
15  
16  
20  
25  
30  
35  
40  
11.9  
14.4  
18.0  
19.2  
23.9  
30.1  
36.1  
42.1  
48.0  
G
G
G
G
LEGEND  
GStandard Offering  
NOTES:  
1. Stages available:  
Single phase: 1-12 kW, 1 stage only  
3-12 kW, 1 stage or 2 stage  
Three phase: 1-40 kW, 1 stage only  
4-40 kW, 1 or 2 stage  
12-40 kW, 1, 2 or 3 stage  
2. Electric Heating Capacities (Btuh) = Heater kW x 3413  
3. Electric Heater Amperage for Single-phase Power  
= (Heater kW x 1000)/Applied Voltage Electric Heater Amp. for 3-phase Power  
= (Heater kW x 1000)/(Applied Voltage x 1.73).  
Service Switches:  
MOTOR PERFORMANCE DATA (AMPS)  
The service switch is an On/Off switch on incoming power  
supply to unit. Proper amperage load must be determined  
before switch can be selected. The range of the fused or  
non-fused service switch is 0 to 40 amps.  
Amp Load = [Motor amps + Heater amps (if required)]*  
1.20.  
Nominal HP  
VOLTAGE  
V-Ph-Hz  
1
1
1
3
/
4
/
/
/
4
1
11/2  
2
3
5
3
2
115-1-60  
208-1-60  
230-1-60  
277-1-60  
208-3-60  
230-3-60  
460-3-60  
5.2 6.0 8.6 13.3 14.4  
3.0 3.6 4.8  
2.5 3.0 4.2  
2.1 2.5 3.6  
6.5 7.4 9.4 11.0  
6.6 6.0 9.0 10.9  
5.1 5.4 8.5  
3.6 3.8 6.0  
3.0 3.2 4.8  
1.5 1.9 2.8  
8.0  
6.5 8.2  
6.2 8.0 14.0  
3.1 4.0 7.0  
2.4  
2.2  
1.1  
The UL listing signifies that Carrier’s fan coil units have been examined  
by UL and comply with the organization’s applicable standards of U.S.  
and Canadian national product safety standard, UL 1995/CSA C22.2  
No. 236.  
NOTES:  
1. Motor Full Load Amps refer to National Electric Code (NEC)  
Amps; actual motor nameplate amps may vary.  
2. NEC data extrapolated for 277 v.  
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm  
rated at continuous duty, 140 F ambient with reversible rotation.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
• 8-pole control terminal strip  
• Auto reset temperature limit switch  
• Manual reset backup temperature limit switch  
• 80/20 heater element wire  
Standard control features  
• 4 in. x 4 in. junction box  
NOTE: Motor leads are wired to the 4 in. x 4 in. junction  
box, mounted on the external panel. Field verification of  
the motor rotation is required on 3-phase applications.  
• Motor power fusing*  
• Motor control contactor**  
• Agency listed for 0-in. clearance  
Electric heat options:  
• Single-phase, 1 or 2 stage heat  
• Three-phase, 1, 2 or 3 stage heat  
Motor control options  
• Interlocking disconnect switch*  
• 24-v class 2 transformer (40 va)†  
• 8-pole control terminal strip  
• Motor power fusing*  
• Motor control contactor**  
*Complies with NEC’s requirement, Article 430 for dis-  
connect, branch circuit protection motor controller and  
motor overload protection.  
Motor and electric heat control options  
NOTE: Electric heat option requires same voltage as motor  
and must include the control option. These control features  
are standard with electric heat options and control option.  
• Interlocking disconnect switch*  
• Heater power fusing*  
• 24-v class 2 transformer (40 va)†  
†No control fusing necessary.  
**Complies with NEC’s requirement for a motor starter  
with internal heating elements when used with the  
factory’s standard motors with integral thermal overload  
protection.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications  
male MPT stainless secondary drain connection  
(capped when not required). The outside surface of  
System Fan Coil Unit  
HVAC Guide Specifications — 42B  
Size Range: 600 to 4000 Nominal Cfm  
Carrier Model Number:  
1
the drain pan shall be insulated with /8-in. closed  
cell insulation.  
C. Fans:  
42BHC (Horizontal Fan Coil Unit)  
42BVC (Vertical Fan Coil Unit)  
Part 1 — General  
Belt-driven, double-width fan wheels shall have  
forward-curved blades and be statically and dynami-  
cally balanced. Fan drive shall consist of variable-  
pitch motor pulley, fixed-pitch fan pulley and V-belt.  
Fans and scrolls shall be of galvanized steel.  
1.01 SYSTEM DESCRIPTION  
Horizontal and vertical, 2-pipe or 4-pipe, belt-  
driven, galvanized casing model fan coil unit for  
ducted installation above the ceiling or within  
floor mounted cabinet, with full access to internal  
components.  
D. Coils:  
Standard unit shall be equipped with a 4-row coil for  
installation in a 2-pipe system and additional rows of  
coil shall be provided for installation in a 4-pipe sys-  
tem as described in the Options and Accessories  
section. Coils shall have 1/2-in. copper tubes, alumi-  
num fins bonded to the tubes by mechanical expan-  
sion and have a working pressure of 250 psig at  
200 F. Each coil shall have a manual air vent and  
sweat connections for copper tubes.  
1.02 QUALITY ASSURANCE  
A. Unit performance shall be rated in accordance with  
ARI Standard 440-2005.  
B. Unit construction shall comply with ASHRAE (latest  
edition) Safety Code and NEC.  
C. Unit shall be constructed in accordance with ETL  
and ETL, Canada standards. Factory-installed  
motors and electric heaters shall be UL approved.  
D. Each coil shall be factory tested for leakage  
at 350-psig air pressure with coil submerged  
in water. Insulation and adhesive shall meet  
NFPA-90A requirements for flame spread and  
smoke generation.  
E. Operating Characteristics:  
A single-circuit coil unit installed in a 2-pipe system  
shall be capable of providing heating or cooling as  
determined by the operating mode of the central  
water supply system. A double-circuit coil unit  
installed in a 4-pipe system shall be capable of pro-  
viding sequenced heating and cooling.  
F. Motor(s):  
E. Each coil shall be factory tested for leakage at  
350 psig air pressure with coil submerged in water.  
Insulation and adhesive shall meet NFPA-90A  
requirements for flame spread and smoke genera-  
tion. Factory-installed motors shall be UL approved.  
Fan motors shall be open, drip-proof, single-speed,  
60 Hz, 1750 rpm 1 or 3 phase, suitable for contin-  
uous duty at 104 F (40 C). Single phase motors are  
capacitor start, include automatic reset thermal  
overload protection and are available in 115, 208,  
230, or 277 volts (60 Hz). Three-phase motors are  
available in 208, 230, or 460 volts (60 Hz). Motors  
are resilient base mounted (except 3 and 5 hp  
motors, which are rigid base mounted).  
1.03 DELIVERY, STORAGE AND HANDLING  
Unit shall be handled and stored in accordance with  
the manufacturer’s instructions.  
Part 2 — Products  
2.01 EQUIPMENT  
A. General:  
G. Options and Accessories:  
1. Factory-Installed Options:  
a. Coils:  
Factory-assembled, horizontal and vertical, draw-  
thru type fan coil unit for ducted installation above  
the ceiling or floor mounting. Unit shall be complete  
with water coils, fan(s), motor, belt drive, drain pan,  
and filter.  
1) Unit coil(s) shall be equipped with auto-  
matic air vent(s).  
2) Unit shall be equipped with a high-  
capacity 6-row or 8-row coil for installa-  
tion in a 2-pipe system.  
3) For installation in a 4-pipe system, unit  
shall be equipped with either a 4-row  
cooling/1-row hot water heating split-  
circuit coil, or a 4/2, 6/1, or 6/2 split-  
circuit coil as required.  
4) Unit shall be equipped with either a 4-  
row DX (direct expansion) cooling coil  
or a 6-row DX cooling coil as required.  
5) Unit coil(s) shall be copper fin, copper  
tube with stainless steel tube and sheets.  
B. Casing:  
Construction shall be heavy-gage galvanized steel,  
lined with one-in. thick fiberglass Tuf-Skin™ II  
thermal/acoustical insulation. Knockouts shall be  
provided for hanging the horizontal unit, that will  
3
accept /8-in. threaded rod at the top, and bottom  
of all unit corners. Supply and return duct connec-  
tion shall be 1 in. long. Removable side panels shall  
be provided for access to the fan/motor assembly. A  
double-sloped drain pan shall be constructed of  
stainless steel, extending under the full length and  
width of the coil(s) with a 3/4-in. male nominal pipe  
b. Filters:  
1) A two-in. pleated filter shall be installed  
in the unit (standard).  
1
thread stainless steel drain connection and /2-in.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications (cont)  
2) One-in. pleated, (2) 1-in. throwaway or  
2-in pleated MERV 11 filters with 2-in.  
pre-filter shall be installed as indicated  
on the equipment schedule.  
2) Mixing boxes shall include  
a linkage kit, which consists of two  
crank arms, 2 swivels and a rod, 25 in.  
long (for unit sizes 06-16) or 84 in.  
long (for unit sizes 20-40), for the field  
installation of the actuator.  
c. Insulation:  
1) Units shall be equipped with 1-in. thick  
Tuf-Skin™ II insulation (standard).  
b. Thermostats:  
2) Units are available with ¾-in. closed  
cell, 1-in. Tuf-Skin Rx™ edge sealed,  
or 1-in. foil-faced insulation.  
Three thermostats shall be available for  
field installation:  
1) The single stage heat thermostat shall  
feature manual changeover, off-cool-  
heat system switch, on-auto fan mode  
switch, single-stage electric heat, and  
outside air signal.  
d. Controls:  
1) Unit shall be equipped with 24-v trans-  
former, motor contactor and terminal  
strip for connection to field or factory  
provided controller.  
2) Unit shall be equipped with interlock-  
ing door-disconnect switch, touch-type  
fusing, 24-v transformer, motor con-  
tactor and terminal strip for connec-  
tion to field provided controller.  
3) Unit shall be equipped with interlock-  
ing door-disconnect switch, separate  
motor and electric heater touch-type  
fusing, 24-v transformer, motor con-  
tactor and terminal strip for connec-  
tion to field-provided or factory-  
provided controller.  
2) The 2-stage heat thermostat shall fea-  
ture automatic/manual changeover,  
digital display of temperatures and all  
functions, off-cool-heat-auto system  
mode buttons, single speed fan opera-  
tion, on-auto fan mode button, single  
or two stage electric heat signal, out-  
side air signal and optional remote  
temperature sensor.  
3) The single-stage heat, 2-pipe heat/  
cool thermostat shall feature digital  
display of ambient temperature and  
operating mode, single fan speed oper-  
ation, power and operating mode but-  
tons, continuous fan operation, cycling  
water control valve, 4-pipe automatic  
changeover/manual changeover with  
“on-auto” fan mode button, optional  
one or 2-stage electric heat signal, and  
purge cycle, temperature sensor for  
2-pipe cold water/hot water systems,  
and programmable operating range,  
dead band, digital display, tempera-  
ture set-back.  
e. Motor(s):  
Single-phase motors are capacitor start and  
shall include automatic reset thermal over-  
load protection and shall be available in  
115, 208, 230, or 277 volts (60 Hz).  
Three-phase motors shall be available in  
208, 230, or 460 volts (60 Hz).  
f. Electric Heat:  
1) Electric heaters shall be constructed of  
high-grade resistance wire supported  
by ceramic insulators on plated steel  
brackets. The heat elements shall be  
suspended in front of the outlet, after  
the blower and coil. High-limit thermal  
cutouts shall protect the heat elements  
in the event of an air failure.  
2) Single-phase heaters shall be available  
in 115, 208, 230, or 277 volts (60  
Hz). Three-phase electric heat shall be  
available in 208, 230, or 460 volts (60  
Hz).  
c. Valve Packages:  
1) Valve packages shall be factory-  
assembled for field installation.  
2) Basic valve packages shall include  
2-way or 3-way valves with balancing  
valves and 2 ball valves.  
3) Deluxe valve packages shall include a  
circuit setting and a strainer in addition  
to the features included in the basic  
valve package.  
2. Field-Installed Accessories:  
a. Mixing Boxes:  
1) Mixing boxes shall be preassembled at  
the factory and shipped separately with  
base rails.  
Carrier Corporation • Syracuse, New York 13221  
9-05A  
9-05  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 3  
New Book 4  
Pg 40  
Catalog No. 524-236  
Printed in U.S.A.  
Form 42B-1PD  
Replaces: 42BHC-1PD  
Tab 7a  
Tab 4FC4  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Box Network Cables BLACK BOXNETWORK SERVICES User Manual
Bosch Power Tools Laser Level GPL2 User Manual
Briggs Stratton Portable Generator 40275 User Manual
Briggs Stratton Pressure Washer 20319 User Manual
Cadet Electric Heater CGH562 User Manual
Canon Camera Flash 420 EZ User Manual
Canon Camera Lens EF100 400mm f 45 56L IS USM User Manual
Canon Digital Camera 115 HS User Manual
Celestron Telescope 21052 User Manual
Channel Vision Switch P 1205 User Manual