Carrier Fan 19XR User Manual

19XR  
50/60 Hz  
Hermetic Centrifugal Liquid Chillers  
with HFC-134a  
Installation Instructions  
SAFETY CONSIDERATIONS  
NEVER APPLY an open flame or live steam to a refrigerant cylinder.  
Centrifugal liquid chillers are designed to provide safe  
and reliable service when operated within design speci-  
fications. When operating this equipment, use good judg-  
ment and safety precautions to avoid damage to equip-  
ment and property or injury to personnel.  
Be sure you understand and follow the procedures and  
safety precautions contained in the machine instruc-  
tions, as well as those listed in this guide.  
Dangerous over pressure can result. When it is necessary to heat re-  
frigerant, use only warm (110 F [43 C]) water.  
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to  
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emp-  
tied, evacuate remaining gas pressure, loosen the collar, and unscrew  
and discard the valve stem. DO NOT INCINERATE.  
CHECK THE REFRIGERANT TYPE before adding refrigerant to the  
machine. The introduction of the wrong refrigerant can cause  
machine damage or malfunction.  
Operation of this equipment with refrigerants other than those cited  
herein should comply with ANSI/ASHRAE15 (latest edition). Contact  
Carrier for further information on use of this machine with other  
refrigerants.  
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while  
machine is under pressure or while machine is running. Be sure pres-  
sure is at 0 psig (0 kPa) before breaking any refrigerant connection.  
CAREFULLY INSPECT all relief valves, rupture discs, and other  
relief devices AT LEAST ONCE A YEAR. If machine operates  
in a corrosive atmosphere, inspect the devices at more frequent  
intervals.  
DO NOT ATTEMPT TO REPAIR OR RECONDITION any  
relief valve when corrosion or build-up of foreign material (rust, dirt,  
scale, etc.) is found within the valve body or mechanism. Replace the  
valve.  
DO NOT VENT refrigerant relief devices within a building. Outlet from  
rupture disc or relief valve must be vented outdoors in accordance with  
the latest edition of ANSI/ASHRAE 15 (American National Standards  
Institute/American Society of Heating, Refrigeration and Air-Conditioning  
Engineers) (Safety Code for Mechanical Refrigeration). The accumu-  
lation of refrigerant in an enclosed space can displace oxygen and cause  
asphyxiation.  
PROVIDE adequate ventilation in accordance with ANSI/  
ASHRAE 15, especially for enclosed and low overhead spaces. Inha-  
lation of high concentrations of vapor is harmful and may cause heart  
irregularities, unconsciousness, or death. Intentional misuse can be fa-  
tal. Vapor is heavier than air and reduces the amount of oxygen avail-  
able for breathing. Product causes eye and skin irritation. Decompo-  
sition products are hazardous.  
DO NOT USE OXYGEN to purge lines or to pressurize a machine for  
any purpose. Oxygen gas reacts violently with oil, grease, and other  
common substances.  
DO NOT install relief devices in series or backwards.  
USE CARE when working near or in line with a compressed spring.  
Sudden release of the spring can cause it and objects in its path to act  
as projectiles.  
DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.  
NEVER EXCEED specified test pressures. VERIFY the allowable test  
pressure by checking the instruction literature and the design pressures  
on the equipment nameplate.  
DO NOT VALVE OFF any safety device.  
BE SURE that all pressure relief devices are properly installed and func-  
tioning before operating any machine.  
RISK OF INJURY OR DEATH by electrocution. High voltage is present  
on motor leads even though the motor is not running when a solid state  
or inside-delta mechanical starter is used. Open the power supply dis-  
connect before touching motor leads or terminals.  
DO NOT STEP on refrigerant lines. Broken lines can whip about and  
release refrigerant, causing personal injury.  
DO NOT climb over a machine. Use platform, catwalk, or staging. Fol-  
low safe practices when using ladders.  
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move  
inspection covers or other heavy components. Even if components are  
light, use mechanical equipment when there is a risk of slipping or  
losing your balance.  
BE AWARE that certain automatic start arrangements CAN ENGAGE  
THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead  
of the starter, tower fan, and pumps. Shut off the machine or pump  
before servicing equipment.  
USE only repaired or replacement parts that meet the code require-  
ments of the original equipment.  
DO NOT VENT OR DRAIN waterboxes containing industrial brines,  
liquid, gases, or semisolids without the permission of your process con-  
trol group.  
DO NOT LOOSEN waterbox cover bolts until the waterbox has been  
completely drained.  
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until  
all refrigerant (liquid and vapor) has been removed from chiller. Traces  
of vapor should be displaced with dry air or nitrogen and the work area  
should be well ventilated. Refrigerant in contact with an open flame  
produces toxic gases.  
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the  
entire assembly.  
DO NOT work on high-voltage equipment unless you are a qualified  
electrician.  
DO NOT WORK ON electrical components, including control  
panels, switches, starters, or oil heater until you are sure ALL POWER  
IS OFF and no residual voltage can leak from capacitors or solid-state  
components.  
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other  
items have been removed before rotating any shafts.  
DO NOT LOOSEN a packing gland nut before checking that the nut  
has a positive thread engagement.  
PERIODICALLY INSPECT all valves, fittings, and piping for corro-  
sion, rust, leaks, or damage.  
PROVIDE A DRAIN connection in the vent line near each pressure  
relief device to prevent a build-up of condensate or rain water.  
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK  
IS INTERRUPTED, confirm that all circuits are deenergized before  
resuming work.  
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.  
USE SAFETY GOGGLES. Wash any spills from the skin with soap  
and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH  
EYES with water and consult a physician.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 211  
Catalog No. 531-940  
Printed in U.S.A.  
Form 19XR-2SI  
Pg 1  
10-97  
Replaces: 19XR-1SI  
Tab 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 1 — Model Number Identification  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
FRONT TOP VIEW  
1
2
Oil Level Sight Glass  
Diffuser Actuator (Hidden/19XR5 Only)  
Discharge Isolation Valve  
Condenser Pumpout Connection  
Condenser Safety Relief Valves  
Three-Way Condenser Relief Valve  
Hot Gas Bypass Line  
3
4
5
6
7
8
Condenser Waterbox Nozzles  
Cooler Waterbox Nozzles  
Cooler Safety Relief Valves  
Cooler Pumpout Connection  
Machine Identification Nameplate  
Control Panel  
Refrigerant Charging Valve  
Guide Vane Actuator  
Compressor/Transmission  
Oil Drain/Charging Valve  
Oil Pump  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Auxillary Power Panel  
Oil Filter Isolation Valve  
Oil Filter  
Motor  
BOTTOM REAR VIEW  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
Waterbox Vents  
Oil Reclaim Filter  
Float Chamber  
Unit Mounted Starter  
Refrigerant Filter/Drier Isolation Valves  
Sight Glass/Moisture Indicator  
Refrigerant Filter/Drier  
Cooler Liquid Line Isolation Valve  
Hot Gas Bypass Valve (Option)  
Hot Gas Bypass Isolation Valve (Option)  
Oil Reclaim Filter Isolation Valve  
Waterbox Vents  
Fig. 2 — Typical 19XR Installation  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAIN LENGTH  
COMPRESSOR  
FRAME SIZE*  
COOLER  
SIZE  
MAXIMUM  
WEIGHT (lb)  
VESSEL  
LENGTH  
DIM. ‘‘A’’  
DIM. ‘‘E’’  
DIM. ‘‘F’’  
‘‘B’’  
‘‘C’’  
‘‘D’’  
10-12  
15-17  
20-22  
30-32  
35-37  
40-42  
45-47  
50-52  
55-57  
50-52  
55-57  
60-62  
65-67  
18,500  
19,000  
19,500  
21,000  
22,500  
29,700  
31,800  
32,200  
33,200  
32,530  
34,230  
39,950  
36,950  
10Ј  
12Ј  
10Ј  
12Ј  
14Ј  
12Ј  
14Ј  
12Ј  
14Ј  
12Ј  
14Ј  
12Ј  
14Ј  
4Ј- 7Љ  
5Ј- 9Љ  
4Ј- 7Љ  
5Ј- 9Љ  
7Ј- 4Љ  
5Ј- 9Љ  
6Ј-10Љ  
5Ј- 9Љ  
6Ј-10Љ  
5Ј- 9Љ  
6Ј- 2Љ  
5Ј- 9Љ  
6Ј- 2Љ  
12Ј-7Љ  
13Ј-6Љ  
12Ј-7Љ  
13Ј-6Љ  
14Ј-2Љ  
12Ј-8Љ  
13Ј-1Љ  
12Ј-7Љ  
13Ј-1Љ  
13Ј-1Љ  
13Ј-7Љ  
13Ј-1Љ  
13Ј-7Љ  
13Ј-0Љ  
13Ј-2Љ  
13Ј-0Љ  
13Ј-2Љ  
13Ј-4Љ  
12Ј-8Љ  
13Ј-2Љ  
12Ј-9Љ  
18Ј-3Љ  
12Ј-9Љ  
13Ј-1Љ  
12Ј-9Љ  
13Ј-1Љ  
13Ј-0Љ  
13Ј-3Љ  
13Ј-0Љ  
13Ј-3Љ  
13Ј-4Љ  
13Ј-4Љ  
13Ј-8Љ  
13Ј-5Љ  
15Ј-9Љ  
13Ј-4Љ  
14Ј-4Љ  
13Ј-4Љ  
14Ј-4Љ  
2Ј-3Љ  
3Ј-1Љ  
3Ј-6Љ  
2Ј-6Љ  
2Ј-4Љ  
2Ј-6Љ  
2
2 or 3  
3
4
3Ј-2Љ  
3Ј-4Љ  
2Ј-7Љ  
2Ј-8Љ  
*The first digit of the 3-digit compressor code indicates the frame size of the compressor.  
MACHINE RIGGING GUIDE  
NOTES:  
1. Each cable must be capable of supporting the entire weight of the  
machine. See chart for maximum weights.  
2. Chain lengths shown are typical for 15Ј lifting height. Some minor  
adjustments may be required.  
Fig. 3 — Machine Rigging Guide (Cooler Size 10 Through 67)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAIN LENGTH  
COMPRESSOR COOLER  
MAXIMUM  
VESSEL  
DIM. ‘‘A’’ DIM. ‘‘B’’ DIM. ‘‘C’’  
FRAME SIZE*  
SIZE  
WEIGHT (lb) LENGTH  
‘‘D’’  
‘‘E’’  
‘‘F’’  
70-72  
75-77  
70-72  
75-77  
80-82  
85-87  
40,410  
44,210  
45,600  
49,400  
54,900  
58,300  
14Ј  
16Ј  
14Ј  
16Ј  
14Ј  
16Ј  
6Ј- 6Љ  
7Ј- 5Љ  
6Ј- 2Љ  
6Ј-11Љ  
6Ј- 2Љ  
6Ј-11Љ  
3Ј-4Љ  
3Ј-5Љ  
3Ј-6Љ  
3Ј-6Љ  
3Ј-6Љ  
3Ј-6Љ  
3Ј-5Љ  
3Ј-5Љ  
3Ј-7Љ  
3Ј-6Љ  
3Ј-7Љ  
3Ј-6Љ  
11Ј-6Љ 12Ј-5Љ 12Ј-9Љ  
12Ј-0Љ 13Ј-3Љ 13Ј-6Љ  
11Ј-6Љ 12Ј-5Љ 12Ј-9Љ  
12Ј-0Љ 13Ј-3Љ 13Ј-6Љ  
11Ј-6Љ 12Ј-5Љ 12Ј-9Љ  
12Ј-0Љ 13Ј-3Љ 13Ј-6Љ  
4
5
*The first digit of the 3-digit compressor code indicates the frame size of the compressor.  
CG  
Center of Gravity  
MACHINE RIGGING GUIDE  
NOTES:  
1. Each chain must be capable of supporting the entire weight of the  
machine. See chart for maximum weights.  
2. Chain lengths shown are typical for 15Ј lifting height. Some minor  
adjustments may be required.  
3. Dimensions ‘‘A’’ and ‘‘B’’ define distance from machine center of  
gravity to tube sheet outermost surfaces. Dimension ‘‘C’’ defines  
distance from machine center of gravity to floor.  
Fig. 4 — Machine Rigging Guide (Cooler Size 70 Through 87)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TUBE REMOVAL  
SPACE FOR  
EITHER END  
10'-0" (3048 mm)  
(SIZES 10-12, 20-22)  
12'-3 1/2" (3747 mm)  
(SIZES 15-17)  
MOTOR SERVICE  
CLEARANCE  
4'0"- (1219 mm)  
3'0" (915 mm)  
RECOMMENDED OVERHEAD  
SERVICE CLEARANCE  
12'-3 1/2" (3747 mm)  
(SIZES 30-32, 40-42,  
50-52, 60-62)  
14'-3" (4343 mm)  
(SIZES 35-37, 45-47,  
55-57, 65-67)  
14'-0" (4267 mm)  
(SIZES 70-72,  
80-82)  
16'-0" (4877 mm)  
(SIZES 75-77,  
85-87)  
C
2'-61/8" MIN  
(362 mm)  
A
B
2' MIN  
(610 mm)  
SERVICE AREA  
Fig. 5 — 19XR Dimensions (Refer to Tables 1 Through 3)  
Table 1 — 19XR Dimensions (Nozzle-In-Head Waterbox)  
A (Length, with Nozzle-in-Head Waterbox)  
B (Width)  
C (Height)  
HEAT EXCHANGER  
SIZE  
2-Pass*  
1 or 3 Pass†  
ft-in.  
mm  
ft-in.  
mm  
ft-in.  
4-1134  
4-1134  
5- 534  
5- 534  
5- 534  
6- 2  
mm  
ft-in.  
mm  
10 to 12  
15 to 17  
20 to 22  
30 to 32  
35 to 37  
40 to 42  
45 to 47  
50 to 52  
55 to 57  
60 to 62  
65 to 67  
70 to 72  
75 to 77  
80 to 82  
85 to 87  
11- 378  
13- 738  
11- 518  
13- 814  
15- 434  
13-11  
15- 712  
13-1114  
15- 734  
13-1134  
15- 814  
16- 4  
3451  
4150  
3483  
4172  
4693  
4242  
4763  
4248  
4769  
4261  
4782  
4978  
5588  
4997  
5607  
11-1034  
14- 214  
12- 012  
14- 314  
15-1134  
14- 614  
16- 234  
14- 634  
16- 314  
14- 714  
16- 334  
17- 012  
19- 012  
17- 112  
19- 112  
3626  
4324  
3670  
4350  
4870  
4426  
4947  
4439  
4959  
4451  
4972  
5194  
5804  
5220  
5829  
1518  
1518  
1670  
1670  
1670  
1880  
1880  
1994  
1994  
2096  
2096  
2426  
2426  
2711  
2711  
6- 114  
6- 114  
6- 314  
6- 958  
6- 958  
7- 034  
7- 034  
7- 278  
7- 278  
7- 478  
7- 478  
9- 912  
9- 912  
9-1114  
9-1114  
1861  
1861  
1911  
2073  
2073  
2153  
2153  
2207  
2207  
2257  
2257  
2985  
2985  
3029  
3029  
6- 2  
6- 612  
6- 612  
6-1012  
6-1012  
7-1112  
7-1112  
8-1034  
8-1034  
18- 4  
16- 434  
18- 434  
*Assumes both cooler and condenser nozzles on same end of chiller.  
†1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design.  
NOTES:  
1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition,  
National Fire Protection Association (NFPA) 70, and local safety code.  
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging.  
3. Certified drawings available upon request.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — 19XR Dimensions (Marine Waterbox)  
A (Length, Marine Waterbox —  
not shown)  
HEAT EXCHANGER  
SIZE  
2-Pass*  
1 or 3 Pass†  
ft-in.  
NA  
mm  
NA  
ft-in.  
NA  
mm  
NA  
10 to 12  
15 to 17  
20 to 22  
30 to 32  
35 to 37  
40 to 42  
45 to 47  
50 to 52  
55 to 57  
60 to 62  
65 to 67  
70 to 72  
75 to 77  
80 to 82  
85 to 87  
NA  
12- 658  
NA  
NA  
NA  
3826  
4496  
5017  
4591  
5099  
4591  
5099  
4591  
5112  
5385  
5994  
5398  
6007  
14- 3  
4343  
4997  
5518  
5099  
5620  
5099  
5620  
5111  
5632  
6058  
6668  
6121  
6731  
14- 9  
16- 434  
18- 114  
16- 834  
18- 514  
16- 834  
18- 514  
16- 914  
18- 534  
19-1012  
21-1012  
20- 1  
16- 512  
15- 014  
16- 834  
15- 014  
16- 834  
15- 034  
16- 914  
17- 8  
19- 8  
17- 812  
19- 812  
22- 1  
*Assumes both cooler and condenser nozzles on same end of chiller.  
†1 or 3 pass length applies if cooler is a 1 or 3 pass design.  
NOTES:  
1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition,  
National Fire Protection Association (NFPA) 70, and local safety code.  
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging.  
3. Certified drawings available upon request.  
Table 3 — 19XR Nozzle Size  
NOZZLE SIZE (in.)  
(Nominal Pipe Size)  
FRAME  
SIZE  
Cooler  
Condenser  
1-Pass  
8
2-Pass  
3-Pass  
1-Pass  
8
2-Pass  
3-Pass  
1
2
3
4
5
6
7
8
6
8
6
6
6
8
6
6
10  
10  
10  
8
6
10  
8
6
10  
8
6
10  
8
6
10  
8
6
10  
10  
10  
12  
14  
8
10  
10  
12  
14  
8
10  
8
14  
10  
12  
14  
12  
12  
14  
14  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — 19XR Compressor Weights  
ENGLISH  
SI  
MOTOR  
CODE  
Total Compressor Weight*  
(lb)  
Total Compressor Weight*  
(kg)  
60 Hz  
50 Hz  
3,755  
3,805  
3,870  
3,950  
3,950  
4,756  
4,771  
4,842  
4,868  
4,883  
4,898  
4,898  
6,158  
6,224  
6,262  
6,351  
6,412  
6,466  
6,868  
6,977  
11,135  
11,265  
11,282  
11,435  
11,435  
11,635  
11,605  
60 Hz  
50 Hz  
BD  
BE  
BF  
BG  
BH  
CD  
CE  
CL  
CM  
CN  
CP  
CQ  
DB  
DC  
DD  
DE  
DF  
DG  
DH  
DJ  
3,755  
3,805  
3,870  
3,950  
3,950  
4,659  
4,685  
4,710  
4,737  
4,751  
4,806  
4,874  
6,112  
6,138  
6,216  
6,224  
6,274  
6,364  
6,412  
6,466  
8,025  
11,085  
11,160  
11,181  
11,271  
11,335  
11,434  
1703  
1726  
1755  
1792  
1792  
2134  
2155  
2137  
2149  
2156  
2181  
2211  
2772  
2822  
2819  
2823  
2846  
2886  
2908  
2933  
3640  
5028  
5062  
5072  
5113  
5142  
5186  
1703  
1726  
1755  
1792  
1792  
2153  
2165  
2167  
2209  
2215  
2212  
2212  
2793  
2823  
2840  
2881  
2908  
2933  
3115  
3165  
5051  
5110  
5118  
5187  
5187  
5278  
5264  
EH  
EJ  
EK  
EL  
EM  
EN  
EP  
*Compressor weight is comprised of compressor, stator, rotor, end bell, suction elbow, and dis-  
charge elbow.  
NOTE: For medium voltage motors (over 600 v), add 490 lb (222 kg).  
Table 5 — 19XR Component Weights  
FRAME 2  
COMPRESSOR  
FRAME 3  
COMPRESSOR  
FRAME 4  
COMPRESSOR  
FRAME 5  
COMPRESSOR  
COMPONENT  
Suction Elbow  
lb  
50  
kg  
23  
lb  
54  
kg  
24  
lb  
kg  
79  
lb  
kg  
95  
175  
157  
30  
210  
140  
30  
Discharge Elbow  
60  
27  
46  
21  
71  
63  
Control Cabinet*  
30  
14  
30  
14  
14  
14  
Optional Unit-Mounted Starter†  
Optional Isolation Valves  
800  
115  
363  
52  
800  
115  
363  
52  
800  
115  
363  
52  
800  
115  
363  
52  
*Included in total cooler weight.  
†Weight of optional factory-mounted starter is not included and must be added to the heat  
exchanger weight.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — 19XR Heat Exchanger Data  
ENGLISH  
Machine Charge  
SI  
Dry Rigging Weight  
(lb)  
Dry Rigging Weight  
Machine Charge  
(kg)  
CODE  
Refrigerant  
Weight  
Water Volume  
(gal)  
Refrigerant  
Weight  
Water  
Cooler Condenser  
Cooler Condenser  
Volume  
Only  
Only  
Only  
Only  
Cooler Condenser Cooler Condenser  
Cooler Condenser Cooler Condenser  
10  
11  
12  
15  
16  
17  
20  
21  
22  
30  
31  
32  
35  
36  
37  
40  
41  
42  
45  
46  
47  
50  
51  
52  
55  
56  
57  
60  
61  
62  
65  
66  
67  
70  
71  
72  
75  
76  
77  
80  
81  
82  
85  
86  
87  
2,742  
2,812  
2,883  
3,003  
3,089  
3,176  
3,442  
3,590  
3,746  
4,137  
4,319  
4,511  
4,409  
4,617  
4,835  
5,898  
6,080  
6,244  
6,353  
6,561  
6,748  
7,015  
7,262  
7,417  
7,559  
7,839  
8,016  
8,270  
8,462  
8,617  
8,943  
9,161  
9,338  
12,395  
12,821  
13,153  
13,293  
13,780  
14,159  
16,156  
16,530  
16,919  
17,296  
17,723  
18,169  
2,704  
2,772  
2,857  
2,984  
3,068  
3,173  
3,523  
3,690  
3,854  
3,694  
3,899  
4,100  
4,606  
4,840  
5,069  
6,054  
6,259  
6,465  
6,617  
6,851  
7,085  
7,285  
7,490  
7,683  
7,990  
8,214  
8,434  
8,286  
8,483  
8,676  
9,204  
9,428  
9,648  
13,139  
13,568  
13,969  
14,211  
14,702  
15,160  
15,746  
16,176  
16,606  
17,001  
17,492  
17,984  
290  
310  
200  
200  
200  
250  
250  
250  
225  
225  
225  
260  
260  
260  
310  
310  
310  
280  
280  
280  
330  
330  
330  
400  
400  
400  
490  
490  
490  
420  
420  
420  
510  
510  
510  
780  
780  
780  
925  
925  
925  
720  
720  
720  
860  
860  
860  
34  
37  
42  
45  
1244  
1276  
1308  
1362  
1401  
1441  
1561  
1628  
1699  
1877  
1959  
2046  
2000  
2094  
2193  
2675  
2757  
2832  
2881  
2976  
3060  
3181  
3293  
3364  
3428  
3555  
3635  
3751  
3838  
3908  
4056  
4155  
4235  
5622  
5816  
5966  
6030  
6251  
6423  
7328  
7498  
7674  
7845  
8039  
8241  
1227  
1257  
1296  
1354  
1392  
1439  
1598  
1674  
1748  
1676  
1769  
1860  
2089  
2195  
2299  
2746  
2839  
2933  
3001  
3108  
3214  
3304  
3397  
3484  
3624  
3725  
3825  
3758  
3847  
3935  
4174  
4276  
4376  
5960  
6154  
6336  
6446  
6669  
6877  
7142  
7337  
7532  
7712  
7934  
8158  
132  
141  
150  
145  
154  
168  
156  
175  
197  
159  
190  
222  
181  
218  
249  
254  
286  
313  
290  
327  
358  
340  
381  
408  
395  
426  
445  
426  
445  
463  
463  
481  
494  
553  
608  
653  
619  
683  
737  
680  
735  
785  
767  
826  
880  
91  
91  
129  
140  
152  
149  
163  
178  
183  
207  
234  
208  
242  
271  
232  
266  
301  
338  
368  
396  
372  
407  
438  
435  
477  
502  
481  
527  
557  
546  
578  
604  
605  
641  
671  
848  
919  
974  
927  
1009  
1072  
1080  
1143  
1208  
1183  
1254  
1329  
158  
170  
185  
183  
198  
216  
181  
210  
239  
210  
246  
282  
233  
273  
314  
365  
400  
433  
403  
442  
481  
483  
518  
552  
536  
575  
613  
601  
636  
669  
668  
707  
745  
791  
867  
937  
885  
971  
1052  
1000  
1075  
1150  
1118  
1205  
1291  
330  
40  
49  
91  
320  
39  
48  
113  
113  
113  
102  
102  
102  
118  
118  
118  
141  
141  
141  
127  
127  
127  
150  
150  
150  
181  
181  
181  
222  
222  
222  
190  
190  
190  
231  
231  
231  
354  
354  
354  
420  
420  
420  
327  
327  
327  
390  
390  
390  
340  
43  
52  
370  
47  
57  
345  
48  
48  
385  
55  
55  
435  
62  
63  
350  
55  
55  
420  
64  
65  
490  
72  
74  
400  
61  
62  
480  
70  
72  
550  
80  
83  
560  
89  
96  
630  
97  
106  
114  
106  
117  
127  
128  
137  
136  
142  
152  
162  
159  
168  
177  
176  
187  
197  
209  
229  
248  
234  
257  
278  
264  
284  
304  
295  
318  
341  
690  
105  
98  
640  
720  
108  
116  
115  
126  
133  
127  
139  
147  
144  
153  
160  
160  
169  
177  
224  
243  
257  
245  
266  
283  
285  
302  
319  
313  
331  
351  
790  
750  
840  
900  
870  
940  
980  
940  
980  
1020  
1020  
1060  
1090  
1220  
1340  
1440  
1365  
1505  
1625  
1500  
1620  
1730  
1690  
1820  
1940  
*Rigging weights are for standard tubes of standard wall thickness (Turbo-B3 and Spikefin 2,  
0.025-in. [0.635 mm] wall).  
NOTES:  
1
1. Cooler includes the control panel (LID), suction elbow, and 2 the distribution piping weight.  
1
2. Condenser includes float valve and sump, discharge elbow, and  
weight.  
3. For special tubes refer to the 19XR Computer Selection Program.  
4. All weights for standard 2 pass NIH (nozzle-in-head) design.  
2
the distribution piping  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — 19XR Additional Data for Marine Waterboxes*  
ENGLISH  
SI  
HEAT EXCHANGER  
FRAME, PASS  
Rigging Weight  
(lb)  
Water Volume  
(gal)  
Rigging Weight  
(kg)  
Water Volume  
(L)  
Psig  
kPa  
FRAME 2, 1 AND 2 PASS  
FRAME 2, 2 PASS  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
300  
300  
300  
300  
300  
300  
300  
300  
300  
300  
300  
300  
300  
300  
730  
365  
84  
42  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
1034  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
2068  
331  
166  
331  
166  
481  
240  
562  
281  
680  
340  
912  
336  
841  
265  
390  
195  
390  
195  
549  
272  
626  
313  
748  
374  
1406  
1041  
1245  
739  
318  
159  
317  
159  
465  
231  
526  
263  
612  
306  
1234  
617  
1537  
768  
318  
159  
317  
159  
465  
231  
526  
263  
612  
306  
1234  
617  
1533  
768  
FRAME 3, 1 AND 2 PASS  
FRAME 3, 2 PASS  
730  
84  
365  
42  
FRAME 4, 1 AND 3 PASS  
FRAME 4, 2 PASS  
1060  
530  
123  
61  
FRAME 5, 1 AND 3 PASS  
FRAME 5, 2 PASS  
1240  
620  
139  
69  
FRAME 6, 1 AND 3 PASS  
FRAME 6, 2 PASS  
1500  
750  
162  
81  
FRAME 7, 1 AND 3 PASS  
FRAME 7, 2 PASS  
2010  
740  
326  
163  
406  
203  
84  
FRAME 8, 1 AND 3 PASS  
FRAME 8, 2 PASS  
1855  
585  
FRAME 2, 1 AND 3 PASS  
FRAME 2, 2 PASS  
860  
430  
42  
FRAME 3, 1 AND 3 PASS  
FRAME 3, 2 PASS  
860  
84  
430  
42  
FRAME 4, 1 AND 3 PASS  
FRAME 4, 2 PASS  
1210  
600  
123  
61  
FRAME 5, 1 AND 3 PASS  
FRAME 5, 2 PASS  
1380  
690  
139  
69  
FRAME 6, 1 AND 3 PASS  
FRAME 6, 2 PASS  
1650  
825  
162  
81  
FRAME 7, 1 AND 3 PASS  
FRAME 7, 2 PASS  
3100  
2295  
2745  
1630  
326  
163  
405  
203  
FRAME 8, 1 AND 3 PASS  
FRAME 8, 2 PASS  
*Add to heat exchanger data for total weights or volumes.  
NOTES:  
1. Weight adder shown is the same for cooler and condenser of equal frame size.  
2. For the total weight of a vessel with a marine waterbox, add these values to the heat  
exchanger weights (or volumes).  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8A — 19XR Waterbox Cover Weights  
ENGLISH (lb)  
FRAME 1  
FRAME 2  
FRAME 3  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Standard  
Nozzles  
Standard  
Flanged  
Flanged  
Flanged  
Nozzles  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
177  
204  
218  
196  
136  
301  
324  
288  
175  
320  
320  
300  
300  
411  
411  
433  
400  
350  
350  
340  
300  
486  
518  
468  
400  
320  
350  
350  
340  
300  
486  
518  
468  
400  
185  
320  
180  
300  
136  
300  
COOLER/  
CONDENSER  
248  
411  
255  
411  
253  
433  
175  
400  
FRAME 4  
FRAME 5  
FRAME 6  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Nozzles  
Standard  
Nozzles  
Standard  
Nozzles  
Flanged  
Flanged  
Flanged  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
485  
487  
504  
379  
593  
594  
621  
569  
521  
540  
520  
379  
668  
700  
656  
569  
616  
590  
629  
428  
764  
761  
795  
713  
652  
663  
655  
428  
655  
839  
838  
713  
802  
770  
817  
583  
880  
844  
901  
833  
838  
843  
843  
583  
956  
995  
952  
833  
COOLER/  
CONDENSER  
FRAME 7 COOLER  
FRAME 7 CONDENSER  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Flanged  
Nozzles  
Standard  
Flanged  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
1392  
1345  
1434  
1022  
1985  
1934  
2009  
1567  
1469  
1461  
1471  
1022  
2150  
2174  
2090  
1567  
1205  
1163  
1222  
920  
1282  
1279  
1280  
920  
COOLER/  
CONDENSER  
1690  
1628  
1714  
1923  
1851  
1862  
1831  
1923  
FRAME 8 COOLER  
FRAME 8 CONDENSER  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Flanged  
Nozzles  
Standard  
Flanged  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
1831  
1739  
1851  
1480  
2690  
2595  
2698  
1440  
1909  
1893  
1909  
1480  
2854  
2924  
2861  
1440  
1682  
1589  
1702  
1228  
2394  
2269  
2417  
1767  
1760  
1744  
1761  
1228  
2549  
2578  
2529  
1767  
COOLER/  
CONDENSER  
LEGEND  
NIH  
MWB  
Nozzle-in-Head  
Marine Waterbox  
NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.  
RIG MACHINE COMPONENTS — Refer to instructions  
below, Fig. 6-9, and Carrier Certified Prints for machine com-  
ponent disassembly.  
Do not attempt to disconnect flanges while the machine  
is under pressure. Failure to relieve pressure can result  
in personal injury or damage to the unit.  
IMPORTANT: Only a qualified service technician should  
perform this operation.  
Before rigging the compressor, disconnect all wires en-  
tering the power panel.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8B — 19XR Waterbox Cover Weights  
SI (kg)  
FRAME 1  
FRAME 2  
FRAME 3  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Standard  
Nozzles  
Standard  
Flanged  
Flanged  
Flanged  
Nozzles  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
80  
93  
99  
145  
145  
136  
136  
186  
186  
196  
181  
159  
159  
154  
136  
220  
235  
212  
181  
145  
159  
159  
154  
136  
220  
235  
212  
181  
84  
145  
82  
89  
140  
62  
62  
136  
COOLER/  
CONDENSER  
112  
116  
115  
79  
137  
147  
131  
79  
186  
186  
196  
181  
FRAME 4  
FRAME 5  
FRAME 6  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Nozzles  
Standard  
Nozzles  
Standard  
Nozzles  
Flanged  
Flanged  
Flanged  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
220  
221  
229  
172  
269  
269  
282  
258  
236  
245  
236  
172  
303  
318  
298  
258  
279  
268  
285  
194  
347  
345  
361  
323  
296  
301  
297  
194  
381  
398  
380  
323  
364  
349  
371  
265  
399  
383  
409  
378  
380  
382  
381  
265  
434  
451  
432  
378  
COOLER/  
CONDENSER  
FRAME 7 COOLER  
FRAME 7 CONDENSER  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Flanged  
Nozzles  
Standard  
Flanged  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
631  
610  
650  
464  
900  
877  
911  
711  
666  
663  
667  
464  
975  
986  
948  
711  
547  
528  
554  
417  
767  
738  
777  
872  
582  
580  
581  
417  
840  
845  
831  
872  
COOLER/  
CONDENSER  
FRAME 8 COOLER  
FRAME 8 CONDENSER  
HEAT  
EXCHANGER  
WATERBOX  
DESCRIPTION  
Standard  
Flanged  
Nozzles  
Standard  
Flanged  
Nozzles  
NIH, 1 Pass Cover, 150 psig  
NIH, 2 Pass Cover, 150 psig  
NIH, 3 Pass Cover, 150 psig  
NIH/MWB End Cover, 150 psig  
NIH, 1 Pass Cover, 300 psig  
NIH, 2 Pass Cover, 300 psig  
NIH, 3 Pass Cover, 300 psig  
NIH/MWB End Cover, 300 psig  
831  
789  
866  
859  
763  
721  
798  
791  
840  
866  
772  
799  
671  
671  
557  
557  
COOLER/  
CONDENSER  
1220  
1177  
1224  
653  
1295  
1326  
1298  
653  
1086  
1029  
1096  
802  
1156  
1169  
1147  
802  
LEGEND  
NIH  
MWB  
Nozzle-in-Head  
Marine Waterbox  
NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.  
NOTE: If the cooler and condenser vessels must be sepa-  
rated, the heat exchangers should be kept level by placing a  
support plate under the tube sheets. The support plate will  
also help to keep the vessels level and aligned when the ves-  
sels are bolted back together.  
Remove all transducer and sensor wires at the sensor. Clip  
all wire ties necessary to pull heat exchangers apart.  
To Separate Cooler and Condenser:  
1. Place a support plate under each tube sheet to keep each  
vessel level (Fig. 6, Item 6).  
2. Cut the refrigerant motor cooling line at the location shown  
(Fig. 6, Item 7).  
NOTE: Wiring must also be disconnected. Label each wire  
before removal (see Carrier Certified Prints). In order to dis-  
connect the starter from the machine, remove wiring for the  
oil pump, oil heater, control wiring at the power panel, and  
the main motor leads at the starter lugs.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Disconnect the compressor discharge elbow at the com-  
pressor (Fig. 7, Item 3).  
3. Disconnect the motor refrigerant return line (Fig. 6,  
Item 8).  
4. Cut the hot gas bypass line at the location shown (Fig. 6,  
Item 1).  
5. Unbolt the cooler liquid feed line at the location shown  
(Fig. 6, Item 10).  
6. Cover all openings.  
7. Disconnect all wires and cables that cross from the cooler  
side of the machine to the condenser side, including:  
4. Disconnect the following:  
a. compressor oil sump temperature sensor cable  
(Fig. 8, Item 4)  
b. bearing temperature sensor cable (Fig. 8, Item 2).  
c. motor temperature sensor cable (Fig. 8, Item 1)  
d. wires and cable housings that cross from the power  
panel to the starter and control panel (Fig. 7, Item 2)  
e. discharge temperature sensor cable (Fig. 8, Item 6)  
f. compressor oil sump pressure cable (Fig. 8, Item 3)  
g. compressor oil discharge pressure cable (Fig. 8,  
Item 5)  
h. guide vane actuator cable (Fig. 7, Item 1).  
i. diffuser actuator cable (Frame 5 compressor only —  
not shown)  
a. temperature sensor cable at the waterbox (Fig. 9,  
Item 1)  
b. condenser transducer cable at the transducer (Fig. 7,  
Item 4)  
c. motor power wires at the starter (Fig. 6, Item 4)  
d. wires and cable housings at the power panel that cross  
from the starter to the power panel (Fig. 7, Item 2).  
8. Disconnect the rabbet-fit connectors on the tube sheets  
(Fig. 6, Item 5).  
9. Rig the vessels apart.  
5. Disconnect the flared fitting for the oil reclaim line  
(Fig. 6, Item 3).  
6. Unbolt the compressor discharge elbow (Fig. 7, Item 3).  
7. Cover all openings.  
To Separate the Compressor from the Cooler:  
1. Unbolt the compressor suction elbow at the cooler flange  
(Fig. 6, Item 2).  
8. Disconnect motor power cables at the starter lugs  
(Fig. 6, Item 4).  
2. Cut the refrigerant motor cooling line at the location shown  
(Fig. 6, Item 7).  
9. Unbolt the compressor mounting from the cooler  
(Fig. 6, Item 9).  
10. Rig the compressor.  
1
2
3
4
5
Optional Hot Gas Bypass (Cut)  
Compressor Suction Elbow (Unbolt)  
Oil Reclaim Line (Unbolt)  
6
7
Tube Sheet  
Refrigerant Motor Cooling Line (Cut)  
Motor Drain (Unbolt)  
8
Starter Connector (Unbolt)  
9
10  
Compressor Mounting (Unbolt)  
Cooler Liquid Feed Line (Unbolt)  
Vessel Connectors (Unbolt)  
Fig. 6 — Cooler, Side View  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
Guide Vane Actuator Cable  
Power Panel to Starter Cables (Oil Pump Power,  
Control Power, and Communication)  
3
4
Compressor Discharge Elbow Joints  
Condenser Transducer Cable  
Fig. 7 — 19XR Chiller Top View  
1
2
Motor Temperature Sensor Cable  
Bearing Temperature Sensor Cable  
Connection (Inside Box)  
4
Compressor Oil Sump Temperature  
Sensor Cable  
Compressor Oil Discharge Pressure Cable  
Discharge Temperature Sensor Cable  
5
6
3
Compressor Oil Sump Pressure Cable  
Fig. 8 — Compressor Detail  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
Guide Vane Actuator  
Diffuser Actuator  
Water Temperature Sensor Cables  
Fig. 9 — Chiller End View  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Rig Compressor  
NOTE: The motor end of the 19XR compressor is heavy  
and will tip backwards unless these directions are followed:  
1. Cut two 4 in. × 6 in. wooden beams to the same length  
as the compressor.  
2. Drill holes into the beams and bolt them to the base of  
the compressor.  
Additional Notes  
1. Use silicon grease on new O-rings when refitting.  
2. Use gasket sealant on new gaskets when refitting.  
INSTALL ACCESSORY ISOLATION (if required) — Un-  
even floors or other considerations may dictate the use of  
accessory soleplates (supplied by Carrier for field installa-  
tion) and leveling pads. Refer to Fig. 10 and 12.  
Level machine by using jacking screws in isolation sole-  
plates. Use a level at least 24-in. (600 mm) long.  
For adequate and long lasting machine support, proper grout  
selection and placement is essential. Carrier recommends that  
only pre-mixed, epoxy type, non-shrinking grout be used for  
machine installation. Follow manufacturer’s instructions in  
applying grout.  
1. Check machine location prints for required grout  
thickness.  
3. Cooler and condenser vessels may be rigged vertically.  
Rigging should be fixed to all 4 corners of the tube sheet.  
2. Carefully wax jacking screws for easy removal from grout.  
3. Grout must extend above the base of the soleplate and  
there must be no voids in grout beneath the plates.  
4. Allow grout to set and harden, per manufacturer’s in-  
structions, before starting machine.  
Install Machine Supports  
INSTALL STANDARD ISOLATION — Figures 10 and 11  
show the position of support plates and shear flex pads, which  
together form the standard machine support system.  
5. Remove jacking screws from leveling pads after grout has  
hardened.  
DIMENSIONS (ft-in.)  
HEAT EXCHANGER  
SIZE  
A
B
10-12  
15-17  
20-22  
30-32  
35-37  
40-42  
45-57  
50-52  
55-57  
60-62  
65-67  
70-72  
75-77  
80-82  
85-87  
10- 714  
12-1034  
10- 714  
12-1034  
14- 714  
12-1034  
14- 714  
12-1034  
14- 714  
12-1034  
14- 714  
15- 178  
17- 178  
15- 178  
17- 178  
4-1114  
4-1114  
5- 514  
5- 414  
5- 414  
6- 0  
6- 0  
6- 512  
6- 512  
6- 912  
6- 912  
7-1012  
7-1012  
8- 934  
8- 934  
Fig. 10 — 19XR Machine Footprint  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL SPRING ISOLATION — Spring isolation may  
be purchased as an accessory from Carrier for field instal-  
lation. It may also be field supplied and installed. Spring iso-  
lators may be placed directly under machine support plates  
or located under machine soleplates. See Fig. 13. Consult  
job data for specific arrangement. Low profile spring isola-  
tion assemblies can be field supplied to keep the machine at  
a convenient working height.  
Obtain specific details on spring mounting and machine  
weight distribution from job data. Also, check job data for  
methods to support and isolate pipes that are attached to spring  
isolated machines.  
NOTES:  
VIEW Y-Y  
1. Dimensions in ( ) are in millimeters.  
2. Isolation package includes 4 shear flex pads.  
Fig. 11 — Standard Isolation  
ACCESSORY SOLEPLATE DETAIL  
VIEW X-X  
LEGEND  
HRS  
Hot Rolled Steel  
NOTES:  
3. Jacking screws to be removed after grout has set.  
4. Thickness of grout will vary, depending on the amount necessary  
to level chiller. Use only pre-mixed non-shrinking grout, Ceilcote  
648CP 0Ј-112Љ (38.1) to 0Ј-214Љ (57) thick.  
1. Dimensions in ( ) are in millimeters.  
2. Accessory (Carrier supplied, field installed) soleplate package  
includes 4 soleplates, 16 jacking screws and leveling pads.  
Fig. 12 — Accessory Isolation  
NOTE: The accessory spring isolators are supplied by Carrier for installation in the field.  
Fig. 13 — 19XR Accessory Spring Isolation  
(Shown with Accessory Soleplates)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Provide openings in water piping for required pressure  
gages and thermometers. For thorough mixing and tem-  
perature stabilization, wells in the leaving water pipe should  
extend inside pipe at least 2 in. (50 mm).  
3. Install air vents at all high points in piping to remove air  
and prevent water hammer.  
Connect Piping  
INSTALL WATER PIPING TO HEAT EXCHANGERS —  
Install piping using job data, piping drawings, and proce-  
dures outlined below. A typical piping installation is shown  
in Fig. 14.  
4. Install pipe hangers where needed. Make sure no weight  
or stress is placed on waterbox nozzles or flanges.  
5. Water flow direction must be as specified in Fig. 15-18.  
Factory-supplied insulation is not flammable but can be  
damaged by welding sparks and open flame. Protect in-  
sulation with a wet canvas cover.  
NOTE: Entering water is always the lower of the 2 nozzles.  
Leaving water is always the upper nozzle for cooler or  
condenser.  
6. Water flow switches must be of vapor-tight construction  
and must be installed on top of pipe in a horizontal run  
and at least 5 pipe diameters from any bend.  
Remove chilled and condenser water sensors before  
welding connecting piping to water nozzles. Refer to  
Fig. 9. Replace sensors after welding is complete.  
7. Install waterbox vent and drain piping in accordance with  
3
individual job data. All connections are 4-in. FPT.  
1. Offset pipe flanges to permit removal of waterbox cover  
for maintenance and to provide clearance for pipe clean-  
ing. No flanges are necessary with marine waterbox  
option; however, water piping should not cross in front  
of the waterbox or access will be blocked.  
8. Install waterbox drain plugs in the unused waterbox drains  
and vent openings.  
9. Install optional pumpout system or pumpout system and  
storage tank as shown in Fig. 19-22.  
*
*
LEGEND  
COM  
N.O.  
Common  
Normally Open  
*Do not tap connections after shutoff valve.  
Fig. 14 — Typical Nozzle Piping  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOZZLE-IN HEAD WATERBOXES  
FRAMES 1, 2, AND 3  
FRAMES 4, 5, AND 6  
NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES  
CONDENSER WATERBOXES  
COOLER WATERBOXES  
PASS  
Arrangement  
Code*  
PASS  
Arrangement  
In  
Out  
In  
Out  
Code*  
11  
2
10  
1
10  
1
2
11  
12  
3
3
12  
P
Q
R
S
T
1
2
3
8
5
7
4
7
4
5
8
9
6
6
9
A
B
C
D
E
F
1
2
3
U
*Refer to certified drawings.  
Fig. 15 — Piping Flow Data (NIH, Frames 1 Through 6)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOZZLE-IN-HEAD WATERBOXES  
FRAMES 7 AND 8  
NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES  
COOLER WATERBOXES  
CONDENSER WATERBOXES  
PASS  
PASS  
Arrangement  
Arrangement  
Code*  
In  
Out  
In  
Out  
Code*  
8
5
7
4
7
4
5
8
9
6
6
9
A
B
C
D
E
F
11  
2
2
11  
12  
3
P
Q
R
S
T
1
2
3
1
2
3
10  
1
10  
1
3
12  
U
*Refer to certified drawings.  
Fig. 16 — Piping Flow Data (NIH, Frames 7 and 8)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MARINE WATERBOXES  
FRAMES 2 AND 3*  
*There is no Frame 1 marine waterbox.  
NOZZLE ARRANGEMENT CODES  
COOLER WATERBOXES  
CONDENSER WATERBOXES  
PASS  
In  
Arrangement  
Code  
Arrangement  
Code  
Out  
In  
Out  
8
5
8
9
6
6
9
A
B
C
D
E
F
10  
1
12  
3
R
1
5
7
2
4
S
7
3
4
Fig. 17 — Piping Flow Data (MWB, Frames 2 and 3)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MARINE WATERBOXES (cont)  
FRAMES 4, 5, AND 6  
NOZZLE ARRANGEMENT CODES  
COOLER WATERBOXES  
CONDENSER WATERBOXES  
PASS  
Arrangement  
Code  
Arrangement  
Code  
In  
Out  
In  
Out  
9
6
7
4
7
4
6
9
9
6
6
9
A
B
C
D
E
F
10  
1
12  
3
R
1
2
3
S
FRAMES 7 AND 8  
NOZZLE ARRANGEMENT CODES  
COOLER WATERBOXES CONDENSER WATERBOXES  
PASS  
Arrangement  
Arrangement  
In  
Out  
In  
Out  
Code  
Code  
8
5
7
4
7
4
5
8
9
6
6
9
A
B
C
D
E
F
10  
1
12  
3
1
2
3
R
S
Fig. 18 — Piping Flow Data (MWB, Frames 4 Through 8)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — 19XR Waterbox Nozzle Sizes  
NOMINAL PIPE SIZE (in.)  
PASS  
ACTUAL PIPE ID (in.)  
Cooler Condenser  
FRAME  
SIZE  
PRESSURE  
psig (kPa)  
Cooler  
Condenser  
1
2
3
8
6
6
8
6
6
7.981  
6.065  
6.065  
7.981  
6.065  
6.065  
150/300  
1
2
3
4
5
6
(1034/2068)  
1
2
3
10  
8
6
10  
8
6
10.020  
7.981  
6.065  
10.020  
7.981  
6.065  
150/300  
(1034/2068)  
1
2
3
10  
8
6
10  
8
6
10.020  
7.981  
6.065  
10.020  
7.981  
6.065  
150/300  
(1034/2068)  
1
2
3
10  
8
6
10  
8
6
10.020  
7.981  
6.065  
10.020  
7.981  
6.065  
150/300  
(1034/2068)  
1
2
3
10  
8
6
10  
10  
8
10.020  
7.981  
6.065  
10.020  
10.020  
7.981  
150/300  
(1034/2068)  
1
2
3
10  
10  
8
10  
10  
8
10.020  
10.020  
7.981  
10.020  
10.020  
7.981  
150/300  
(1034/2068)  
1
2
3
14  
12  
10  
14  
12  
12  
13.250  
12.000  
10.020  
13.250  
12.000  
12.000  
150  
(1034)  
7
8
1
2
3
14  
12  
10  
14  
12  
12  
12.500  
11.376  
9.750  
12.500  
11.750  
11.750  
300  
(2068)  
1
2
3
14  
14  
12  
14  
14  
12  
13.250  
13.250  
12.000  
13.250  
13.250  
12.000  
150  
(1034)  
1
2
3
14  
14  
12  
14  
14  
12  
12.500  
12.500  
11.376  
12.500  
12.500  
11.376  
300  
(2068)  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS  
ENGLISH (ft-in.)  
TANK  
SIZE  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
0428 10- 5  
9-10  
4-9  
2-434 1-238 3-1316 4-11  
3-818 3- 8  
2-9716 3-2  
0-312 4-834 1-778 1-7516 3-734 5-014  
0452 14-1114 14- 412 5-078 2-812 1-414 3-4716 7- 214 4-0  
3-1178 3-1516 3-578 0-338 7-112 1-834 1-7916 3-8  
5-012  
SI (mm)  
TANK  
SIZE  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
0428  
0452  
3175  
4553  
2997  
4382  
1448  
1546  
730  
826  
365  
413  
945  
1499  
2191  
1121  
1219  
1118  
1216  
849  
948  
965  
89  
86  
1442  
2172  
505  
528  
491  
497  
1111  
1118  
1530  
1537  
1027  
1064  
NOTES:  
1.  
Denotes center of gravity.  
2. Dimensions in ( ) are in millimeters.  
3. The weights and center of gravity values given are for an empty storage tank.  
4. For additional information on the pumpout unit, see certified drawings.  
5. The available conduit knockout sizes are:  
QTY  
TRADE SIZE  
LOCATION  
1
1
1
1
1
2
Љ
top  
3
4Љ  
bottom  
middle  
middle  
1Љ  
114  
Љ
Fig. 19 — Optional Pumpout Unit and Storage Tank  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RATED DRY WEIGHT AND REFRIGERANT CAPACITY  
ENGLISH (lb)  
DRY  
WEIGHT*  
(lb)  
MAXIMUM REFRIGERANT CAPACITY (lb)  
TANK  
SIZE  
TANK OD  
(in.)  
ANSI/ASHRAE 15  
UL 1963  
0428  
0452  
24.00  
27.25  
2380  
3460  
1860  
3563  
1716  
3286  
SI (kg)  
DRY  
WEIGHT*  
(kg)  
MAXIMUM REFRIGERANT CAPACITY (kg)  
TANK  
SIZE  
TANK OD  
(mm)  
ANSI/ASHRAE 15  
UL 1963  
0428  
0452  
610  
592  
1080  
1569  
844  
778  
1616  
1491  
LEGEND  
ASHRAE  
American Society of Heating, Refrigeration,  
and Air Conditioning Engineers  
Outside Diameter  
OD  
UL  
Underwriters’ Laboratories  
*The above dry weight includes the pumpout condensing unit weight of 210 lbs (95 kg).  
Fig. 19 — Optional Pumpout Unit and Storage Tank (cont)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 20 — Optional Pumpout System Piping Schematic with Storage Tank  
Fig. 21 — Optional Pumpout System Piping Schematic without Storage Tank  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OIL  
tubing or piping near the device is essential on spring-  
isolated machines.  
RETURN LINE  
CONNECTION  
4. Cover the outdoor vent with a rain cap and place a con-  
densation drain at the low point in the vent piping to pre-  
vent water build-up on the atmospheric side of the relief  
device.  
Table 10 — Relief Device Locations  
QUANTITY  
Frame 5  
RELIEF VALVE  
OUTLET SIZE  
LOCATION  
Compressor With  
Frame 7 or 8  
All  
Others  
SERVICE  
VALVES  
Heat Exchanger  
1-in. NPT FEMALE  
CONNECTOR  
Cooler  
4
4
2
2
2
2
1-in.NPT FEMALE  
CONNECTOR  
Condenser  
1-in. NPT FEMALE  
CONNECTOR  
Optional  
Storage Tank  
COMPRESSOR  
MOUNTING  
SPRINGS  
NOTE: All valves relieve at 185 psi (1275 kPa).  
CONDENSER  
WATER CONNECTIONS  
REFRIGERANT  
INLET VALVE  
Make Electrical Connections — Field wiring must  
be installed in accordance with job wiring diagrams and all  
applicable electrical codes.  
Fig. 22 — Pumpout Unit  
INSTALL VENT PIPING TO RELIEF VALVES — The  
19XR chiller is factory equipped with relief devices on the  
cooler and condenser shells. Refer to Fig. 23 and Table 10  
for size and location of relief devices. Vent relief devices to  
the outdoors in accordance with ANSI/ASHRAE 15 (latest  
edition) Safety Code for Mechanical Refrigeration and all  
other applicable codes.  
Do not run 120-v wiring into the control cabinet. The  
control cabinet should only be used for additional extra-  
low voltage wiring (50 v maximum).  
Wiring diagrams in this publication (Fig. 24-31) are for  
reference only and are not intended for use during actual in-  
stallation; follow job specific wiring diagrams.  
Refrigerant discharged into confined spaces can dis-  
place oxygen and cause asphyxiation.  
Do not attempt to start compressor or oil pump (even  
for a rotation check) or apply test voltage of any kind  
while machine is under dehydration vacuum. Motor in-  
sulation breakdown and serious damage may result.  
1. If relief devices are manifolded, the cross-sectional area  
of the relief pipe must at least equal the sum of the areas  
required for individual relief pipes.  
CONNECT CONTROL INPUTS — Connect the control in-  
put wiring from the chilled and condenser water flow switches  
to the starter terminal strip. Wiring may also be specified for  
a spare safety switch, and a remote start/stop contact can be  
wired to the starter terminal strip. Additional spare sensors  
and Carrier Comfort Network modules may be specified as  
well. These are wired to the machine control panel as indi-  
cated in Fig. 24 and 25.  
2. Provide a pipe plug near outlet side of each relief device  
for leak testing. Provide pipe fittings that allow vent pip-  
ing to be disconnected periodically for inspection of valve  
mechanism.  
3. Piping to relief devices must not apply stress to the  
device. Adequately support piping. A length of flexible  
Fig. 23 — Relief Valve Locations  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 24 — Carrier Comfort Network Communication Bus Wiring  
LEGEND  
Factory Wiring  
Field Wiring  
*Field supplied terminal strip must be located in control panel.  
Fig. 25 — COMM1 CCN Communication Wiring For Multiple Chillers (Typical)  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECT CONTROL OUTPUTS — Connect auxiliary  
equipment, chilled and condenser water pumps, and spare  
alarms as required and indicated on job wiring drawings.  
740 amps. The top hat is shipped in the knocked-down po-  
sition and must be assembled and installed on top of the starter  
cabinet, over the line side circuit breaker. During assembly,  
remove the access plate and use it as the cover piece of the  
top hat. The top hat provides additional wire bending space  
to attach line side power leads to the circuit breaker within  
the starter.  
CONNECT STARTER — The 19XR is available with either  
a unit-mounted, factory-installed starter or a free-standing,  
field-installed starter (Fig. 28 and 29).  
Unit Mounted, Factory-Installed Starter— Attach power leads  
by connecting them from inside the starter cabinet to the line  
side circuit breaker terminals. See Fig. 26 and 28. Machines  
with electro-mechanical starters (wye-delta) will have a top  
hat shipped with the machine if the RLA (rated load amps)  
is greater than 935 amps. If the machine is equipped with a  
solid-state starter, a top hat is provided if the RLA exceeds  
IMPORTANT: Be sure to ground the power circuit in  
accordance with the National Electrical Code (NEC),  
applicable local codes, and job wiring diagrams. Also,  
make sure correct phasing is observed for proper  
rotation.  
3
8
7
Piping  
Control Wiring  
Power Wiring  
LEGEND  
IMPORTANT: Wiring and piping shown are for general point-  
of-connection only and are not intended to show details for a  
specific installation. Certified field wiring and dimensional dia-  
grams are available on request.  
1
2
Disconnect  
Unit Mounted Starter  
Control Cabinet  
3
4
Power Panel  
5
Vents  
NOTES:  
6
Pressure Gages  
1. All wiring must comply with applicable codes.  
2. Refer to Carrier System Design Manual for details regarding pip-  
ing techniques.  
7
Chilled Water Pump  
Condenser Water Pump  
Chilled Water Pump Starter  
Condensing Water Pump Starter  
Cooling Tower Fan Starter  
8
9
3. Wiring not shown for optional devices such as:  
• remote start-stop  
10  
11  
• remote alarm  
• optional safety device  
• 4 to 20 mA resets  
• optional remote sensors  
Fig. 26 — 19XR with Optional Unit-Mounted Starter  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Insulate each terminal by wrapping with one layer of in-  
sulation putty.  
2. Overwrap putty with 4 layers of vinyl tape.  
Free-Standing, Field-Installed Starter — Assemble and in-  
stall compressor terminal box in desired orientation, and cut  
necessary conduit openings in conduit support plates. See  
Fig. 27 and 29. Attach power leads to compressor terminals  
in accordance with job wiring drawings, observing caution  
label in terminal box. Use only copper conductors. The mo-  
tor must be grounded in accordance with NEC (National Elec-  
trical Code), applicable local codes, and job wiring diagrams.  
Installer is responsible for any damage caused by improper  
wiring between starter and compressor motor.  
High Voltage Units — High-voltage units require special ter-  
minal preparation. Follow local electrical codes for high-  
voltage installation. Vinyl tape is not acceptable; a high voltage  
terminal method must be used.  
Connect Power Wires to Oil Pump Starter — See Fig. 30.  
Connect power wires to oil pump starter mounted in ma-  
chine power panel. Use separate fused disconnect or circuit  
breaker as shown on job wiring diagrams and Fig. 30. Check  
that power supply voltage agrees with oil pump voltage. Fol-  
low correct phasing for proper motor rotation.  
IMPORTANT: Do not insulate terminals until wiring  
arrangement has been checked and approved by  
Carrier start-up personnel. Also, make sure correct phas-  
ing is followed for proper motor rotation.  
Insulate Motor Terminals and Lead Wire Ends — Insulate  
compressor motor terminals, lead wire ends, and electrical  
wires to prevent moisture condensation and electrical arc-  
ing. For low-voltage units (up to 600 v), obtain insulation  
material from machine shipping package consisting of 3 rolls  
of insulation putty and one roll of vinyl tape.  
Do not punch holes or drill into the top surface of the  
power panel. Knockouts are provided in the bottom of  
the power panel for wiring connections.  
Piping  
IMPORTANT: Wiring and piping shown are for general point-  
of-connection only and are not intended to show details for a  
specific installation. Certified field wiring and dimensional dia-  
grams are available on request.  
Control Wiring  
Power Wiring  
LEGEND  
NOTES:  
1
2
Disconnect  
1. All wiring must comply with applicable codes.  
2. Refer to Carrier System Design Manual for details regarding pip-  
ing techniques.  
Free-Standing Compressor Motor Starter  
Compressor Motor Terminal Box  
Chiller Power Panel  
3
4
3. Wiring not shown for optional devices such as:  
• remote start-stop  
5
Control Cabinet  
6
Vents  
• remote alarm  
7
Pressure Gages  
• optional safety device  
8
Chilled Water Pump  
• 4 to 20 mA resets  
9
Condenser Water Pump  
Chilled Water Pump Starter  
Condensing Water Pump Starter  
Cooling Tower Fan Starter  
Disconnect  
• optional remote sensors  
10  
11  
12  
13  
14  
4. Oil pump disconnect may be located within the enclosure of Item  
2 — Free-Standing Compressor Motor Starter.  
Oil Pump Disconnect (see Note 4)  
Fig. 27 — 19XR with Free-Standing Starter  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT: Wiring shown is typical and not intended to show  
detail for a specific installation. Refer to certified field wiring  
diagrams.  
LEGEND  
AWG  
N.C.  
N.O.  
PR  
American Wire Gage  
Normally Closed  
Normally Open  
Pilot Relay  
RLA  
ST  
Rated Load Amps  
Shunt Trip  
TB  
Terminal Block  
Required Power Wiring  
Required Control Wiring  
Options Wiring  
NOTES:  
fan motors must be provided to assure machine protection. If primary pump  
and tower fan motor are controlled by other means, also provide a parallel  
means for control by Carrier. Do not use starter control transformer as the  
power source for pilot relay loads.  
I. GENERAL  
1.0 Starters shall be designed and manufactured in accordance with  
Carrier Engineering Requirement Z-375.  
1.1 All field-supplied conductors, devices, field-installation wiring, and ter-  
mination of conductors and devices must be in compliance with all ap-  
plicable codes and job specifications.  
1.2 The routing of field-installed conduit and conductors and the location  
of field-installed devices must not interfere with equipment access or  
the reading, adjusting, or servicing of any component.  
3.4 Do not route control wiring carrying 30 v or less within a conduit which has  
wires carrying 50 v or higher or alongside wires carrying 50 v or higher.  
3.5 Voltage selector switch in machine power panel is factory set for 115 v  
control power source. When 230 v control power source is used, set switch  
to 230 v position.  
3.6 Control wiring cables between starter and power panel must be shielded  
with minimum rating of 600 v, 80 C. Ground shield at starter.  
3.7 If optional oil pump circuit breaker is not supplied within the starter enclo-  
sure as shown, it must be located within sight of the machine with wiring  
routed to suit.  
1.3 Equipment, installation, and all starting and control devices must com-  
ply with details in equipment submittal drawings and literature.  
1.4 Contacts and switches are shown in the position they would assume  
with the circuit deenergized and the chiller shut down.  
1.5 WARNING — Do not use aluminum conductors.  
1.6 Installer is responsible for any damage caused by improper wiring be-  
tween starter and machine.  
IV. POWER WIRING BETWEEN STARTER AND COMPRESSOR MOTOR  
4.0 Low voltage (600 v or less) compressor motors have (6) 3  
in. terminal  
4  
studs (lead connectors not supplied by Carrier). Either 3 or 6 leads  
must be run between compressor motor and starter, depending on type  
of motor starter employed. If only 3 leads are required, jumper motor  
terminals as follows: 1 to 6, 2 to 4, 3 to 5. Center to center distance  
between terminals is 21516 inches. Compressor motor starter must have  
nameplate stamped as conforming with Carrier requirement Z-375.  
4.1 When more than one conduit is used to run conductors from starter to  
compressor motor terminal box, one conductor from each phase must  
be in each conduit to prevent excessive heating. (e.g., conductors to  
motor terminals 1, 2 & 3 in one conduit, and those to 4, 5 & 6 in  
another.)  
4.2 Compressor motor power connections can be made through top, top  
rear, or sides of compressor motor terminal box using holes cut by con-  
tractor to suit conduit. Flexible conduit should be used for the last few  
feet to the terminal box for unit vibration isolation. Use of stress cones  
or 12 conductors larger than 500 MCM may require an oversize (spe-  
cial) motor terminal box (not supplied by Carrier). Lead connections  
between 3-phase motors and their starters must not be insulated until  
Carrier personnel have checked compressor and oil pump rotations.  
4.3 Compressor motor frame to be grounded in accordance with the Na-  
tional Electrical Code (NFPA-70) and applicable codes. Means for ground-  
ing compressor motor is a pressure connector for No. 4 to 500 MCM  
wire, supplied and located in the back lower left side corner of the com-  
pressor motor terminal box.  
II. POWER WIRING TO STARTER  
2.0 Power conductor rating must meet minimum unit nameplate voltage  
and compressor motor RLA.  
When (3) conductors are used:  
Minimum ampacity per conductor = 1.25 x compressor RLA  
When (6) conductors are used:  
Minimum ampacity per conductor = 0.721 x compressor RLA  
2.1 Lug adapters may be required if installation conditions dictate that con-  
ductors be sized beyond the minimum ampacity required. Contact starter  
supplier for lug information.  
2.2 Compressor motor and controls must be grounded by using equip-  
ment grounding lugs provided inside starter enclosure.  
III. CONTROL WIRING  
3.0 Field supplied control conductors to be at least 18 AWG or larger.  
3.1 Chilled water and condenser water flow switch contacts, optional re-  
mote start device contacts, and optional spare safety device contacts  
must have 24 vdc rating. Max current is 60 mA; nominal current is  
10 mA. Switches with gold plated bifurcated contacts are  
recommended.  
3.2 Remove jumper wire between 12A and 12B before connecting auxil-  
iary safeties between these terminals.  
3.3 Pilot relays can control cooler and condenser pump and tower fan mo-  
tor contactor coil loads rated 10 amps at 115 vac up to 3 amps at  
600 vac. Control wiring required for Carrier to start pumps and tower  
4.4 Do not allow motor terminals to support weight of wire cables. Use cable  
supports and strain reliefs as required.  
4.5 Use backup wrench when tightening lead connectors to motor terminal  
studs. Torque to 45 lb-ft max.  
Fig. 28 — 19XR Typical Field Wiring with Optional Unit-Mounted Starter  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
AWG  
N.C.  
N.O.  
PR  
American Wire Gage  
Normally Closed  
Normally Open  
Pilot Relay  
SMM  
Starter Management  
Module  
TB  
Terminal Block  
Required Power Wiring  
Required Control Wiring  
Options Wiring  
RLA  
Rated Load Amps  
IMPORTANT: Wiring shown is typical and not intended to show detail  
for a specific installation. Refer to certified field wiring diagrams.  
NOTES:  
3.4 Do not route control wiring carrying 30 v or less within a conduit which  
has wires carrying 50 v or higher or alongside wires carrying 50 v or  
higher.  
3.5 Voltage selector switch in machine power panel is factory set for  
115 v control power source. When 230 v control power source is used,  
set switch to 230 v position.  
3.6 Control wiring cables between starter and power panel must be shielded  
with minimum rating of 600 v, 80 C. Ground shield at starter.  
3.7 If optional oil pump circuit breaker is not supplied within the starter en-  
closure as shown, it must be located within sight of the machine with  
wiring routed to suit.  
3.8 For 19XR chillers with free-standing starts, voltage to terminals LL1  
and LL2 comes from a control transformer in a starter built to Carrier  
specifications. Do not connect an outside source of control power to  
the compressor motor starter terminals (LL1 and LL2). An outside power  
source will produce dangerous voltage at the line side of the starter,  
because supplying voltage at the transformer secondary terminals pro-  
duces input level voltage at the transformer primary terminals.  
I. GENERAL  
1.0 Starters shall be designed and manufactured in accordance with  
Carrier Engineering Requirement Z-375.  
1.1 All field-supplied conductors, devices, field-installation wiring, and ter-  
mination of conductors and devices must be in compliance with all ap-  
plicable codes and job specifications.  
1.2 The routing of field-installed conduit and conductors and the location  
of field-installed devices must not interfere with equipment access or  
the reading, adjusting, or servicing of any component.  
1.3 Equipment, installation, and all starting and control devices must com-  
ply with details in equipment submittal drawings and literature.  
1.4 Contacts and switches are shown in the position they would assume  
with the circuit deenergized and the chiller shut down.  
1.5 WARNING — Do not use aluminum conductors.  
1.6 Installer is responsible for any damage caused by improper wiring be-  
tween starter and machine.  
II. POWER WIRING TO STARTER  
IV. POWER WIRING BETWEEN STARTER AND COMPRESSOR MOTOR  
4.0 Low voltage (600 v or less) compressor motors have (6) 3  
in. terminal  
2.0 Power conductor rating must meet minimum unit nameplate voltage  
and compressor motor RLA.  
4  
studs (lead connectors not supplied by Carrier). Either 3 or 6 leads  
must be run between compressor motor and starter, depending on type  
of motor starter employed. If only 3 leads are required, jumper motor  
terminals as follows: 1 to 6, 2 to 4, 3 to 5. Center to center distance  
between terminals is 21516 inches. Compressor motor starter must have  
nameplate stamped as conforming with Carrier requirement Z-375.  
4.1 When more than one conduit is used to run conductors from starter to  
compressor motor terminal box, one conductor from each phase must  
be in each conduit to prevent excessive heating. (e.g., conductors to  
motor terminals 1, 2 & 3 in one conduit, and those to 4, 5 & 6 in  
another.)  
4.2 Compressor motor power connections can be made through top, top  
rear, or sides of compressor motor terminal box using holes cut by con-  
tractor to suit conduit. Flexible conduit should be used for the last few  
feet to the terminal box for unit vibration isolation. Use of stress cones  
or 12 conductors larger than 500 MCM may require an oversize (spe-  
cial) motor terminal box (not supplied by Carrier). Lead connections  
between 3-phase motors and their starters must not be insulated until  
Carrier personnel have checked compressor and oil pump rotations.  
4.3 Compressor motor frame to be grounded in accordance with the Na-  
tional Electrical Code (NFPA-70) and applicable codes. Means for ground-  
ing compressor motor is a pressure connector for No. 4 to 500 MCM  
wire, supplied and located in the back lower left side corner of the com-  
pressor motor terminal box.  
When (3) conductors are used:  
Minimum ampacity per conductor = 1.25 x compressor RLA  
When (6) conductors are used:  
Minimum ampacity per conductor = 0.721 x compressor RLA  
2.1 Lug adapters may be required if installation conditions dictate that con-  
ductors be sized beyond the minimum ampacity required. Contact starter  
supplier for lug information.  
2.2 Compressor motor and controls must be grounded by using equip-  
ment grounding lugs provided inside starter enclosure.  
III. CONTROL WIRING  
3.0 Field supplied control conductors to be at least 18 AWG or larger.  
3.1 Chilled water and condenser water flow switch contacts, optional re-  
mote start device contacts, and optional spare safety device contacts  
must have 24 vdc rating. Max current is 60 mA; nominal current is  
10 mA. Switches with gold plated bifurcated contacts are  
recommended.  
3.2 Remove jumper wire between 12A and 12B before connecting auxil-  
iary safeties between these terminals.  
3.3 Pilot relays can control cooler and condenser pump and tower fan mo-  
tor contactor coil loads rated 10 amps at 115 vac up to 3 amps at  
600 vac. Control wiring required for Carrier to start pumps and tower-  
fan motors must be provided to assure machine protection. If primary  
pump and tower fan motor are controlled by other means, also provide  
a parallel means for control by Carrier. Do not use starter control trans-  
former as the power source for pilot relay loads.  
4.4 Do not allow motor terminals to support weight of wire cables. Use cable  
supports and strain reliefs as required.  
4.5 Use backup wrench when tightening lead connectors to motor terminal  
studs. Torque to 45 lb-ft max.  
Fig. 29 — 19XR Typical Field Wiring with Free-Standing Starter  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Power Wires to Oil Heater Contactor — Connect  
control power wiring between the oil heater contactor ter-  
minals and terminals LL1 and LL2 on the field wiring strip  
in the compressor motor starter. Refer to Fig. 31 and wiring  
label on the machine power panel.  
The negative pins must be wired to the negative pins. The  
signal ground pins must be wired to the signal ground pins.  
See Fig. 24 for location of the CCN network connector  
(COMM1) on the processor module.  
NOTE: Conductors and drain wire must be 20 AWG  
(American Wire Gage) minimum stranded, tinned copper. In-  
dividual conductors must be insulated with PVC, PVC/  
nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester  
100% foil shield and an outer jacket of PVC, PVC/nylon,  
chrome vinyl, or Teflon with a minimum operating tempera-  
ture range of −4 F to 140 F (−20 C to 60 C) is required. See  
table below for cables that meet the requirements.  
Voltage to terminals LL1 and LL2 comes from a con-  
trol transformer in a starter built to Carrier specifica-  
tions. Do not connect an outside source of control power  
to the compressor motor starter (terminals LL1 and LL2).  
An outside power source will produce dangerous volt-  
age at the line side of the starter, because supplying volt-  
age at the transfomer secondary terminals produces in-  
put level voltage at the transformer primary terminals.  
MANUFACTURER  
Alpha  
CABLE NO.  
2413 or 5463  
A22503  
American  
Belden  
Connect Wiring from Starter to Power Panel — Connect con-  
trol wiring from main motor starter to the machine power  
panel. All control wiring must use shielded cable. Also, con-  
nect the communications cable. Refer to the job wiring dia-  
grams for cable type and cable number. Make sure the con-  
trol circuit is grounded in accordance with applicable electrical  
codes and instructions on machine control wiring label.  
8772  
Columbia  
02525  
When connecting the CCN communication bus to a sys-  
tem element, a color code system for the entire network is  
recommended to simplify installation and checkout. The fol-  
lowing color code is recommended:  
CCN BUS CONDUCTOR  
INSULATION COLOR  
COMM1 PLUG  
PIN NO.  
SIGNAL TYPE  
+
Ground  
Red  
White  
Black  
1
2
3
If a cable with a different color scheme is selected, a simi-  
lar color code should be adopted for the entire network.  
LEGEND  
Factory Wiring  
Field Wiring  
At each system element, the shields of its communication  
bus cables must be tied together. If the communication bus  
is entirely within one building, the resulting continuous shield  
must be connected to ground at only one single point. See  
Fig. 25. If the communication bus cable exits from one build-  
ing and enters another, the shields must be connected to ground  
at the lightening suppressor in each building where the cable  
enters or exits the building (one point only).  
Oil Pump Terminal  
Power Panel Component Terminal  
Fig. 30 — Oil Pump Wiring  
To connect the 19XR chiller to the network, proceed as  
follows (Fig. 24 and 25):  
1. Cut power to the PIC control panel.  
2. Remove the COMM1 plug from the processor module.  
3. Cut a CCN wire and strip the ends of the RED, WHITE,  
and BLACK conductors.  
4. Using a wirenut, connect the drain wires together.  
5. Insert and secure the RED wire to Terminal 1 of the  
COMM1 plug.  
6. Insert and secure the WHITE wire to Terminal 2 of the  
COMM1 plug.  
LEGEND  
Field Wiring  
7. Insert and secure the BLACK wire to Terminal 3 of the  
COMM1 plug.  
8. Mount a terminal strip in a convenient location.  
9. Connect the opposite ends of each conductor to separate  
terminals on the terminal strip.  
Power Panel Component Terminal  
NOTE: The voltage selector switch in the machine power panel is  
factory set for 115 v control power source. When a 230 v control power  
source is used, set the voltage selector switch at 230 v.  
Fig. 31 — Oil Heater and Control Power Wiring  
10. Cut another CCN wire and strip the ends of the  
conductors.  
11. Connect the RED wire to the matching location on the  
terminal strip.  
12. Connect the WHITE wire to the matching location on  
the terminal strip.  
13. Connect the BLACK wire to the matching location on  
the terminal strip.  
CARRIER COMFORT NETWORK INTERFACE — The  
Carrier Comfort Network (CCN) communication bus wiring  
is supplied and installed by the electrical contractor. It con-  
sists of shielded, 3-conductor cable with drain wire.  
The system elements are connected to the communication  
bus in a daisy chain arrangement. The positive pin of each  
system element communication connector must be wired to  
the positive pins of the system element on either side of it.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• cooler tube sheets  
Install Field Insulation  
• suction piping  
• motor cooling drain  
• oil reclaim piping  
• oil cooler refrigerant side tubing  
• refrigerant liquid line to cooler  
NOTE: Insulation of the waterbox covers is applied only at  
the jobsite by the contractor. When insulating the covers, make  
sure there is access for removal of waterbox covers for ser-  
vicing (Fig. 32).  
Protect insulation from weld heat damage and weld  
splatter. Cover with wet canvas cover during water  
piping installation.  
When installing insulation at the jobsite, insulate the fol-  
lowing components:  
• compressor motor  
• cooler shell  
Fig. 32 — 19XR Insulation Area  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 1997 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 211  
Catalog No. 531-940  
Printed in U.S.A.  
Form 19XR-2SI  
Pg 38  
10-97  
Replaces: 19XR-1SI  
Tab 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION START-UP REQUEST CHECKLIST  
Machine Model Number: 19XR  
To:  
Serial Number:  
Date  
Project Name  
Attn:  
Carrier Job Number  
The following information provides the status of the chiller installation.  
YES/NO  
(N/A)  
DATE TO BE  
COMPLETED  
1. The machine is level.  
2. The machine components are installed and connected in  
accordance with the installation instructions.  
3. The isolation package and grouting (if necessary)  
are installed.  
4. The relief valves are piped to the atmosphere.  
5. All piping is installed and supported. Direction of flow  
is indicated in accordance with the installation instructions  
and job prints.  
a. Chilled water piping  
b. Condenser water piping  
c. Waterbox drain piping  
d. Pumpout unit condenser piping (if installed)  
e. Other  
6. Gages are installed as called for on the job prints required  
to establish design flow for the cooler and condenser.  
a. Water pressure gages IN and OUT  
b. Water temperature gages IN and OUT  
7. The machine’s starter wiring is complete. The wiring is  
installed per installation instructions and certified prints.  
a. Power wiring to compressor motor. (Motor leads will  
not be taped until the Carrier technician megger tests  
the motor.)  
b. Oil pump wiring  
c. Oil heater/control wiring  
d. Other  
8. The motor starter has not been supplied by Carrier. It  
has been installed according to the manufacturer’s  
instructions.  
9. The motor starter has not been supplied by Carrier and it  
has been checked for proper operation.  
COMMENTS:  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DATE TO BE  
COMPLETED  
TESTING  
YES/NO  
1. The cooling tower fan has been checked for blade pitch and  
proper operation.  
2. The chilled water and condenser water lines have been:  
a. Filled  
b. Tested  
c. Flushed  
d. Vented  
e. Strainers cleaned  
3. The chilled water and condenser water pumps have been  
checked for proper rotation and flow.  
4. The following cooling load will be available for start-up:  
a. 25%  
b. 50%  
c. 75%  
d. 100%  
5. The refrigerant charge is at the machine.  
6. Services such as electrical power and control air will be avail-  
able at start-up.  
7. The electrical and mechanical representatives will be available  
to assist in commissioning the machine.  
8. The customer’s operators will be available to receive instruc-  
tions for proper operation of the chiller after start-up.  
Concerns about the installation/request for additional assistance:  
I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the machine and  
the options and accessories used with it.  
Your contact at the jobsite will be  
Phone number  
Beeper number  
Fax number  
In accordance with our contract, we hereby request the services of your technician to render start-up services per contract terms  
for this job on  
(Date). I understand that the technician’s time will be charged as extra services due to correcting items  
in this checklist that are incomplete.  
Signature of Purchaser  
Signature of Jobsite Supervisor  
Copyright 1997 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 211  
Catalog No. 531-940  
Printed in U.S.A.  
Form 19XR-2SI  
Pg CL-2  
10-97  
Replaces: 19XR-1SI  
Tab 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Iron AS390 User Manual
Black Decker Saw 633526 00 User Manual
Bosch Appliances Home Care Product F01U252722 User Manual
Bose Speaker System Cinemate Digital Home Theater Speaker System User Manual
Braun Electric Toothbrush Toothbrush User Manual
Braun Iron PV1505 User Manual
Breville Blender BSB400 User Manual
Bush Hog Lawn Mower 2426QT User Manual
Canon Camcorder 2685B001 User Manual
CDA Ventilation Hood EVM9 User Manual