Carrier Fan 13 50XP User Manual

PERFORMANCE™ 13 50XP  
SINGLE-PACKAGED ELECTRIC COOLING UNITS  
WITH PURON® (R-410A) REFRIGERANT  
2 to 5 Nominal Tons  
Product Data  
Single-Packaged Products with  
Energy-Saving Features and Puron®  
refrigerant.  
• Low Sound Levels  
• 13 SEER  
Variable Speed Blower-Standard  
• Factory Installed TXV  
Features/Benets  
One-piece cooling unit with optional  
electric heater, low installation cost,  
dependable performance and easy  
maintenance.  
Efcient operation  
High-efciency design with a SEER  
(Seasonal Energy Efciency Ratio)  
of 13.0.  
Puron® Environmentally Sound  
Refrigerant is Carrier’s unique  
refrigerant designed to help protect the  
environment. Puron is an HFC  
refrigerant which does not contain  
chlorine that can harm the ozone layer.  
The most important advantage of  
Puron refrigerant is that it has not been  
banned in future air conditioning  
systems as the traditional refrigerant  
R-22 has been. Puron refrigerant is in  
service in thousands of systems  
proving highly reliable,  
UNIT 50XP  
environmentally sound performance.  
IdealHumidity™ Technology  
featuring Thermidistat control and  
Variable Speed Blower motor that  
provides greater comfort, humidity  
control, and energy efciency. You can  
expect up to 30 times better  
dehumidication; economical constant  
fan for less than $50 a year, which  
provides improved indoor air quality  
and more even temperatures from room  
to room; and reduced indoor noise due  
to lower air velocity. In addition, you’ll  
realize improved installation exibility  
with 3 different airow choices for best  
overall comfort.  
Easy Installation  
Factory-assembled package is a  
compact, fully self-contained, electric  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model number nomenclature  
50XP  
024  
3
Options  
BT – AL evap, vinyl condens  
CC – AL evap, CU condens  
Model Number  
50XP – Single  
Packaged-Electric  
Cooling  
Options  
CU – CU evap & condens  
(None) – Wire Grille  
TP – Base unit with tin plated indoor coil  
AD – Louvered Grille  
hairpins  
TV – TP with vinyl coating on outdoor coil  
BT – Wire Grille and Vinyl-Coated Condenser  
Coil Fin  
TC – TP with AL indoor coil & CU/CU out-  
XT – Louvered Grille and Vinyl-Coated Con-  
door coil  
denser Coil Fin  
Nominal Cooling Capacity  
024 – 2 ton  
030 – 2.5 ton  
036 – 3 ton  
042 – 3.5 ton  
048 – 4 ton  
060 – 5 ton  
CC – Wire Grille, AL Evaporator and CU/CU  
Only used if ordering an option  
Condenser Coil  
AC – Louvered Grille, AL Evaporator and CU/  
CU con  
V-Ph-Hz  
3 – 208/230-1-60  
5 – 208/230-3-60  
AL — Aluminum  
CU — Copper  
ARI* capacities  
COOLING CAPACITIES AND EFFICIENCIES  
NET COOLING  
STANDARD  
CFM  
SOUND  
RATINGS‡  
(dB)  
UNIT  
50XP  
NOMINAL  
TONS  
CAPACITIES  
(Btuh)  
EER@A**  
SEER†  
024  
030  
036  
042  
048  
060  
2
2-1/2  
3
800  
24,000  
28,800  
36,000  
41,000  
45,000  
57,000  
11.0  
11.0  
11.0  
11.0  
11.0  
11.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
72  
72  
72  
72  
78  
78  
1000  
1100  
1400  
1450  
1710  
3-1/2  
4
5
LEGEND  
— Sound Levels (decibels)  
— Dry Bulb  
‡ Tested in accordance with ARI Standard 270-95 (not listed in ARI).  
NOTES:  
dB  
db  
1. Ratings are net values, reflecting the effects of circulating fan heat.  
Ratings are based on:  
SEER — Seasonal Energy Efficiency Ratio  
wb — Wet Bulb  
* Air Conditioning & Refrigeration Institute.  
** “A” Conditions- 80°F indoor db/67°F indoor wb & 95°F outdoor db.  
† Rated in accordance with U.S. Government DOE Department of  
Energy) test procedures and/or ARI Standard 210/240-94.  
Cooling Standard: 80°F db, 67°F wb indoor entering-air tempera-  
ture and 95°F db outdoor entering-air temperature.  
2. Before purchasing this appliance, read important energy cost and  
efficiency information available from your retailer.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
OUTDOOR SOUND: OCTAVE BAND DATA—DECIBELS (Lw(A))  
MODEL NO.  
50XP  
Frequency (Hz)  
024  
58.8  
63.5  
67.2  
66.9  
63.7  
58.3  
50.0  
030  
58.8  
63.5  
67.2  
66.9  
63.7  
58.3  
50.0  
036  
60.7  
63.3  
66.8  
66.5  
64.2  
60.3  
53.0  
042  
56.7  
62.8  
67.8  
67.4  
63.7  
57.7  
50.8  
048  
62.4  
69.9  
71.3  
73.4  
70.0  
66.3  
60.1  
060  
63.5  
67.6  
71.8  
75.5  
71.0  
68.1  
59.9  
125  
250  
500  
1000  
2000  
4000  
8000  
Physical data  
UNIT SIZE 50XP  
024  
2
030  
2-1/2  
343  
036  
3
042  
3-1/2  
433  
048  
4
060  
NOMINAL CAPACITY (ton)  
OPERATING WEIGHT (lb)  
COMPRESSOR  
5
343  
366  
Scroll  
456  
492  
REFRIGERANT (R-410A)  
Quantity (lb)  
7.3  
8.0  
9.5  
10.7  
TXV  
11.25  
TXV  
13.2  
TXV  
REFRIGERANT METERING DEVICE  
(Indoor)  
TXV  
TXV  
TXV  
CONDENSER COIL  
Rows—Fins/in.  
Face Area (sq ft)  
2—21  
11.95  
2—21  
12.0  
2—21  
13.6  
2—21  
15.4  
2—21  
17.4  
2—21  
19.3  
CONDENSER FAN  
Nominal Cfm  
Diameter (in.)  
2350  
22  
1/8 (825)  
2700  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2800  
22  
1/8 (825)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
Motor Hp (Rpm)  
EVAPORATOR COIL  
Rows—Fins/in.  
Face Area (sq ft)  
3—15  
3.7  
3—15  
3.7  
4—15  
3.7  
3—15  
4.7  
4—15  
4.7  
4—17  
5.7  
EVAPORATOR BLOWER  
Nominal Airow (Cfm)  
Size (in.)  
800  
10 x 10  
1/2  
1000  
10 x 10  
1/2  
1100  
11 x 10  
3/4  
1400  
11 x 10  
3/4  
1400  
11 x 10  
3/4  
1750  
11 x 10  
1.0  
Motor (Hp)  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
610 ± 15  
420 ± 25  
LOSS-OF-CHARGE/LOW-PRESSURE  
SWITCH  
(Liquid Line) (psig)  
Cutout  
Reset (Auto.)  
20 ± 5  
45 ± 10  
RETURN-AIR FILTERS (in.)*  
Throwaway  
20 x 20 x 1  
20 x 20 x 1  
20 x 24 x 1  
24 x 30 x 1  
24 x 30 x 1  
24 x 30 x 1  
* Required lter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated  
cooling airow or the heating airow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity  
type. Air lter pressure drop for non-standard lters must not exceed 0.08 in. wg.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options and accessories  
Factory-installed options  
Coil options include Tin-Plated* indoor hairpins, copper/  
copper and vinyl-coated construction for refrigerant coils.  
Units are shipped standard with copper tube/aluminum n  
construction. See model number nomenclature for coil  
options.  
*Tin-Plated indoor coils are built with special hairpins  
that are designed to resist both general pitting corrosion  
and excessive indoor corrosion (Formicary Corrosion).  
power supply for the entire unit, resulting in lower installed  
costs.  
Flat roof curbs in both 8 in. and 14 in. sizes are available  
for roof mounted applications.  
Square-to-round duct transition kit enables 024-048 size  
units to be tted to 14 in. round ductwork.  
Thermidistat Control coupled with the system’s variable  
speed indoor blower delivers Carrier’s patented  
IdealHumidity™ Technology that allows for even greater  
humidity control. Along with more precisely controlling  
temperature and humidity, the Thermidistat offers full  
seven-day programmability allowing you to further  
customize your comfort and energy savings.  
Field-installed accessories  
Economizer with Solid-State Controls and Barometric  
Relief Dampers  
Manual Air Damper (25% open)  
Electric Heaters  
Thermostats provide control for the system heating and  
cooling functions. Thermostat models are available in both  
programmable and non-programmable versions.  
Filter Rack  
Flat Roof Curbs (8-in. and 14-in.)  
Square-to-Round Duct Transition Kit  
Thermidistat™  
Lifting kit, including 4 metal brackets that are available to  
assist in lifting this product onto a roof application.  
Thermostats  
Crankcase Heater  
Crankcase heater provides anti-oodback protection for  
low-load cooling applications.  
Rigging Kit  
Low Ambient Kit (Motormaster® II Control)  
Solid-State Time Guard® II Device  
Lifting Kit  
Low-ambient kit (Motormaster II control) allows the  
use of mechanical cooling down to outdoor temperatures as  
low as 0°F.  
Compressor Hard Start Kit  
Solid-state Time Guard II device provides short-cycling  
protection for the compressor. Not required with corporate  
electronic thermostats.  
Economizer with solid-state controls and barometric  
relief dampers includes lter racks and provide outdoor air  
during cooling and reduce compressor operation.  
Manual outside air damper includes hood and lter rack  
with adjustable damper blade for up to 25% outdoor air.  
Electric heaters provide heat in the unit when required.  
Each package has a heater module that slides into the  
controls compartment. Heater sizes range from 5 to 20 kW.  
The electric heater design allows the use of a single-point  
Filter rack features easy installation, serviceability, and  
high-ltering performance for vertical or horizontal  
applications.  
Compressor Hard start kit assists compressor start-up by  
providing additional starting torque on single phase units  
and prolongs compressor motor life.  
ELECTRIC HEATERS  
USED WITH SIZES  
036 042  
ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)  
ODS CATALOG  
ORDERING NO.  
NOMINAL CAPACITY  
(kW)  
024  
030  
048  
060  
CPHEATER052A00  
CPHEATER069A00  
CPHEATER065A00  
CPHEATER051A00  
CPHEATER053A00  
5.0  
7.5  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0  
15.0  
20.0  
ELECTRIC HEATERS (208/230 — 3 PHASE — 60 Hz)  
CPHEATER055A00  
CPHEATER056A00  
CPHEATER057A00  
CPHEATER059A00  
5.0  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0  
15.0  
20.0  
LEGEND  
ODS — Order Distribution System  
NOTE: Electric heaters are rated at 240 v. Refer to Multiplication Factors table for other voltages.  
MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION  
UNIT  
024  
030  
036  
042  
048  
060  
1800  
AIRFLOW  
750  
750  
1250  
1205  
1500  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ECONOMIZER  
FILTER RACK  
MANUAL OUTSIDE AIR DAMPER  
REPLACEMENT  
PANEL  
MANUAL OUTSIDE  
AIR HOOD  
DAMPER  
BLADE  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions—50XP024-036  
CENTER OF GRAVITY  
in. [mm]  
UNIT HEIGHT  
in. [mm]  
“A”  
UNIT WEIGHT  
ELECTRICAL  
CHARACTERISTICS  
UNIT  
lb  
kg  
X
Y
Z
50XP024  
50XP030  
50XP036  
208/230-1-60  
208/230-1-60  
343  
343  
366  
156  
156  
166  
39.02 [991.1]  
39.02 [991.1]  
41.02 [1041.9]  
20 [508]  
20 [508]  
20 [508]  
19.3 [489]  
19.3 [489]  
14 [355.6]  
17.6 [447]  
17.6 [447]  
13 [330.2]  
208/230-1-60, 208/230-3-60  
50XP 024-036 Dimensions  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Base unit dimensions—50XP042-060  
CENTER OF GRAVITY  
in. [mm]  
UNIT HEIGHT  
in. [mm]  
“A”  
UNIT WEIGHT  
ELECTRICAL  
CHARACTERISTICS  
UNIT  
lb  
kg  
X
Y
Z
50XP042  
50XP048  
50XP060  
208/230-1-60, 208/230-3-60  
208/230-1-60, 208/230-3-60  
208/230-1-60, 208/230-3-60  
433  
456  
492  
197  
207  
223  
42.98 [1091.7]  
44.98 [1142.5]  
46.98 [1193.3]  
21 [533.4] 20.5 [520.2] 16.6 [421.6]  
19.5 [495.3] 17.6 [447.6] 18.0 [457.2]  
21 [533.4]  
20 [508]  
17.6 [447.0]  
50XP 042-060 Dimensions  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessory dimensions  
A
in. [mm]  
B
in. [mm]  
C
in. [mm]  
D
in. [mm]  
UNIT SIZE  
ODS CATALOG NUMBER  
CPRFCURB006A00  
CPRFCURB007A00  
CPRFCURB008A00  
CPRFCURB009A00  
8 [203]  
14 [356]  
8 [203]  
11 [279]  
16-1/2 [419]  
16-1/2 [419]  
17-3/8 [441]  
17-3/8 [441]  
28-3/4 [730]  
28-3/4 [730]  
40-1/4 [1022]  
40-1/4 [1022]  
50XP024-036  
11 [279]  
16-3/16 [411]  
16-3/16 [411]  
50XP042-060  
14 [356]  
NOTES:  
1. Roof curb must be set up for unit being installed.  
2. Seal strip must be applied, as required, to unit being installed.  
3. Dimensions in [ ] are in millimeters.  
4. Roof curb is made of 16-gage steel.  
5. Table lists only the dimensions, per part number, that have changed.  
6. Attach ductwork to curb (anges of duct rest on curb).  
7. Insulated panels: 1-in. thick berglass 1 lb density.  
8. Dimensions are in inches.  
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well.This bracket must also be used when required by code  
for hurricane or seismic conditions. This bracket is available through Micrometl.  
HVAC unit  
base  
HVAC unit  
base  
Gasketing  
inner flange*  
Screw  
(NOTE A)  
Screw  
(NOTE A)  
Gasketing  
inner flange*  
*Gasketing  
outer flange  
*Gasketing  
outer flange  
Wood nailer*  
Wood nailer*  
Flashing field  
supplied  
Flashing field  
supplied  
Roofcurb*  
Roofcurb*  
Insulation (field  
supplied)  
Insulation (field  
supplied)  
Roofing material  
field supplied  
Roofing material  
field supplied  
Duct work  
field supplied  
Duct work  
field supplied  
Cant strip  
field supplied  
Cant strip  
field supplied  
Roof  
Roof  
*Provided with roofcurb  
*Provided with roofcurb  
Roof Curb for Small Cabinet  
Roof Curb for Large Cabinet  
Note A: When unit mounting screw is used,  
retainer bracket must also be used.  
Note A: When unit mounting screw is used,  
retainer bracket must also be used.  
Supply opening  
(B x C)  
B Typ.  
D
C Typ.  
44 5/16"  
(1125.5mm)  
R/A  
S/A  
A
Short  
Support  
Insulated  
deck pan  
Long  
Support  
Return opening  
(B X C)  
C00076  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
50XP Corner weights (In Pounds)  
1
2
3
y
4
x
Small Base  
Large Base  
030  
69  
036  
74  
042  
87  
048  
92  
060  
99  
Model 50XP  
Corner Weight #1  
Corner Weight #2  
Corner Weight #3  
Corner Weight #4  
Total Weight  
024  
69  
53  
53  
57  
67  
71  
77  
83  
83  
88  
104  
174  
433  
110  
183  
456  
119  
198  
492  
138  
343  
138  
343  
147  
366  
Selection Procedure  
I Determine cooling and heating requirements at design  
conditions:  
Given:  
closely satisfies the heating required. To calculate kW at  
208v, multiply the heater kW by multiplication factor 0.75  
found in the Wattage Multiplication Factors table.  
5 kW x 0.75 = 3.75 kW  
Required Cooling Capacity (TC). . . . . . . . . . 34,500 Btuh  
Sensible Heat Capacity (SHC). . . . . . . . . . . . 26,000 Btuh  
Required Heating Capacity . . . . . . . . . . . . . . 15,000 Btuh  
Condenser Entering Air Temperature . . . . . . . . . . . . 95°F  
Indoor-Air Temperature. . . . . . . . . . . 80°F edb, 67°F ewb  
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 cfm  
External Static Pressure . . . . . . . . . . . . . . . . . . . 0.2 in. wg  
Electrical Characteristics . . . . . . . . . . . . . . . . . . .230-1-60  
3.75 kW x 3414 Btuh/kW = 12,802.50 Btuh  
IV Determine fan speed and power requirements at design  
conditions.  
Before entering the air delivery tables, calculate the total  
static pressure required. From the given, Filter Pressure  
Drop table, and the Accessory Electric Heat Pressure Drop  
table, find:  
II Select unit based on required cooling capacity.  
Enter Cooling Capacities table at condenser entering  
temperature of 95°F. The 036 unit at 1225 cfm and 67°F  
ewb (entering wet bulb) will provide a total capacity of  
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC  
correction, if required, using Note 4 under Cooling  
Capacities tables.  
Wet coil pressure drop  
External static pressure  
Filter  
0.032 in. wg  
0.200 in. wg  
0.130 in. wg  
Total static pressure  
0.362 in. wg  
Enter the table for Dry Coil Air Delivery — At 0.362 in. wg  
external static pressure and NOM speed pin selection, the  
motor delivers 1235 cfm.  
III Select electric heat.  
The required heating capacity is 15,000 Btuh (given).  
Determine the electric heat capacity in kW.  
15,000 Btuh  
V Select unit that corresponds to power source available.  
The Electrical Data table shows that the unit is designed to  
operate at 208/230-1-60.  
= 4.4 kW of heat required  
3414 Btuh/kW  
Enter the Electric Heater Packages table for 208/240,  
single-phase, 036 unit. The 5-kW heater at 240v most  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data-Standard ECM Indoor Motor  
COOLING CAPACITIES  
50XP024 COOLING PERFORMANCE TABLE  
Evaporator Air—CFM/BF  
Temp (F)  
800/0.026  
900/0.032  
1000/0.04  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
TC  
SHC  
24.0  
21.9  
1.7  
24.5  
21.3  
1.7  
26.5  
18.7  
1.8  
29.1  
15.4  
1.8  
24.6  
23.5  
1.8  
25.1  
22.8  
1.8  
27.1  
19.8  
1.8  
29.8  
16.1  
1.8  
25.1  
25.0  
1.8  
25.5  
24.2  
1.8  
27.4  
20.8  
1.8  
30.4  
16.7  
1.9  
75  
kW  
TC  
22.9  
21.4  
1.9  
23.3  
20.7  
1.9  
25.3  
18.1  
2.0  
27.9  
14.9  
2.0  
23.5  
22.9  
2.0  
23.9  
22.2  
2.0  
25.8  
19.2  
2.0  
28.5  
15.6  
2.0  
23.9  
24.3  
2.0  
24.3  
23.6  
2.0  
26.2  
20.3  
2.1  
28.9  
16.2  
2.1  
SHC  
85  
95  
kW  
TC  
21.8  
20.8  
2.2  
22.2  
20.2  
2.2  
24.0  
17.6  
2.2  
26.5  
14.3  
2.2  
22.3  
22.3  
2.2  
22.6  
21.6  
2.2  
24.5  
18.7  
2.2  
27.0  
15.0  
2.2  
22.7  
23.6  
2.2  
23.0  
22.9  
2.2  
24.8  
19.7  
2.3  
27.4  
15.6  
2.3  
SHC  
kW  
TC  
20.5  
20.2  
2.4  
20.9  
19.5  
2.4  
22.6  
16.9  
2.4  
25.0  
13.7  
2.4  
21.0  
21.6  
2.4  
21.3  
20.9  
2.4  
23.0  
18.0  
2.5  
25.4  
14.3  
2.5  
21.6  
22.5  
2.5  
21.7  
22.2  
2.5  
23.3  
19.0  
2.5  
25.7  
14.9  
2.5  
SHC  
105  
115  
125  
kW  
TC  
19.2  
19.4  
2.7  
19.5  
18.8  
2.7  
21.1  
16.3  
2.7  
23.3  
13.0  
2.7  
19.8  
20.6  
2.7  
19.9  
20.2  
2.7  
21.5  
17.3  
2.7  
23.7  
13.7  
2.7  
20.7  
21.5  
2.7  
20.4  
21.2  
2.7  
21.7  
18.3  
2.8  
23.6  
14.1  
2.8  
SHC  
kW  
TC  
17.8  
18.5  
2.9  
18.0  
18.1  
2.9  
19.4  
15.5  
3.0  
21.4  
12.3  
3.0  
18.5  
19.2  
3.0  
18.5  
19.2  
3.0  
19.5  
16.5  
3.0  
21.7  
12.9  
3.0  
19.0  
19.8  
3.0  
19.0  
19.7  
3.0  
19.9  
17.6  
3.1  
21.9  
13.5  
3.1  
SHC  
kW  
50XP030 COOLING PERFORMANCE TABLE  
Temp (F)  
Evaporator Air—CFM/BF  
1000/0.07  
875/0.06  
1125/0.08  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
TC  
SHC  
kW  
27.9  
24.1  
2.1  
28.6  
20.0  
2.1  
30.7  
20.6  
2.1  
33.6  
16.8  
2.1  
28.8  
26.0  
2.1  
29.4  
21.2  
2.1  
31.6  
22.1  
2.1  
34.5  
17.8  
2.2  
29.3  
27.0  
2.1  
30.0  
22.6  
2.1  
32.2  
23.5  
2.1  
35.2  
18.7  
2.2  
75  
85  
TC  
SHC  
kW  
26.9  
23.8  
2.3  
27.5  
19.5  
2.3  
29.5  
20.3  
2.4  
32.3  
16.4  
2.4  
27.6  
25.6  
2.3  
28.1  
20.8  
2.4  
30.2  
21.7  
2.4  
33.1  
17.4  
2.4  
28.3  
26.5  
2.4  
28.7  
22.1  
2.4  
30.8  
23.1  
2.4  
33.7  
18.3  
2.4  
TC  
SHC  
kW  
25.6  
23.1  
2.6  
26.2  
19.1  
2.6  
28.2  
19.9  
2.6  
30.8  
16.0  
2.6  
26.3  
24.7  
2.6  
26.8  
20.5  
2.6  
28.8  
21.3  
2.6  
31.5  
16.9  
2.6  
27.0  
26.2  
2.6  
27.3  
21.7  
2.6  
29.3  
22.6  
2.6  
32.0  
17.8  
2.6  
95  
TC  
SHC  
kW  
24.3  
22.4  
2.9  
24.7  
18.6  
2.9  
26.6  
19.3  
2.9  
29.2  
15.4  
2.9  
25.1  
23.8  
2.9  
25.3  
19.9  
2.9  
27.2  
20.8  
2.9  
29.7  
16.3  
2.9  
25.9  
24.4  
2.9  
25.7  
21.1  
2.9  
27.5  
22.1  
2.9  
30.1  
17.2  
2.9  
105  
TC  
SHC  
kW  
22.8  
21.7  
3.2  
23.2  
18.0  
3.2  
24.9  
18.8  
3.2  
27.3  
14.8  
3.2  
23.8  
22.3  
3.2  
23.6  
19.3  
3.2  
25.3  
20.2  
3.2  
27.7  
15.7  
3.2  
24.5  
23.7  
3.2  
24.0  
20.5  
3.2  
25.7  
21.5  
3.2  
28.1  
16.6  
3.2  
115  
125  
TC  
SHC  
kW  
21.4  
20.7  
3.5  
21.4  
17.3  
3.5  
24.9  
18.8  
3.2  
27.3  
14.8  
3.2  
23.8  
22.3  
3.2  
23.6  
19.3  
3.2  
25.3  
20.2  
3.2  
27.7  
15.7  
3.2  
24.5  
23.7  
3.2  
24.0  
20.5  
3.2  
25.7  
21.5  
3.2  
28.1  
16.6  
3.2  
See Legend and Notes on page 13.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)-Standard ECM Indoor Motor  
COOLING CAPACITIES  
50XP036 COOLING PERFORMANCE TABLE  
Evaporator Air—CFM/BF  
Temp (F)  
1100/0.06  
1225/0.07  
1400/0.08  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
36.2  
36.8  
39.7  
43.8  
36.9  
37.4  
40.3  
44.4  
37.9  
38.1  
41.0  
45.1  
TC  
SHC  
kW  
75  
85  
33.2  
2.7  
34.6  
32.4  
2.9  
33.0  
31.6  
3.2  
31.3  
30.6  
3.6  
29.6  
29.3  
4.0  
27.8  
27.5  
4.4  
26.7  
2.7  
35.1  
26.0  
2.9  
33.4  
25.3  
3.2  
31.5  
24.5  
3.6  
29.4  
23.7  
4.0  
27.2  
22.8  
4.3  
27.8  
2.7  
37.9  
27.1  
3.0  
36.0  
26.4  
3.3  
34.0  
25.6  
3.6  
31.8  
24.8  
4.0  
29.4  
23.9  
4.4  
22.3  
2.7  
41.8  
21.6  
3.0  
39.7  
20.9  
3.3  
37.5  
20.1  
3.6  
35.0  
19.3  
4.0  
32.4  
18.4  
4.4  
34.7  
2.7  
35.3  
34.0  
3.0  
33.7  
32.9  
3.3  
32.1  
31.5  
3.6  
30.4  
30.0  
4.0  
28.4  
28.2  
4.4  
27.9  
2.7  
35.6  
27.1  
3.0  
33.8  
26.4  
3.3  
31.9  
25.7  
3.6  
29.8  
24.8  
4.0  
27.5  
23.8  
4.4  
29.0  
2.7  
38.4  
28.3  
3.0  
36.5  
27.6  
3.3  
34.3  
26.8  
3.7  
32.1  
26.0  
4.0  
29.7  
25.0  
4.4  
23.1  
2.8  
42.4  
22.4  
3.0  
40.2  
21.7  
3.4  
37.9  
20.9  
3.7  
35.4  
20.0  
4.0  
32.7  
19.1  
4.4  
36.9  
2.8  
36.4  
35.6  
3.1  
34.8  
34.4  
3.4  
33.1  
32.8  
3.8  
31.3  
31.0  
4.1  
29.3  
29.0  
4.5  
29.6  
2.8  
36.3  
28.9  
3.1  
34.4  
28.1  
3.4  
32.4  
27.3  
3.7  
30.3  
26.4  
4.1  
28.0  
25.4  
4.5  
30.9  
2.8  
39.1  
30.2  
3.1  
37.0  
29.4  
3.4  
34.9  
28.6  
3.8  
32.6  
27.7  
4.1  
30.1  
26.7  
4.5  
24.2  
2.9  
43.1  
23.6  
3.2  
40.8  
22.8  
3.5  
38.4  
22.0  
3.8  
35.8  
21.1  
4.2  
33.0  
20.2  
4.5  
TC  
SHC  
kW  
TC  
SHC  
kW  
95  
TC  
SHC  
kW  
105  
TC  
SHC  
kW  
115  
125  
TC  
SHC  
kW  
50XP042 COOLING PERFORMANCE TABLE  
Temp (F)  
Evaporator Air—CFM/BF  
1225/0.07  
1100/0.06  
1400/0.08  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
TC  
SHC  
kW  
39.6  
33.5  
3.0  
40.4  
27.6  
3.0  
43.4  
28.6  
3.0  
47.6  
23.4  
3.1  
40.5  
35.4  
3.0  
41.2  
29.0  
3.0  
44.2  
30.0  
3.0  
48.4  
24.3  
3.1  
41.5  
37.9  
3.0  
42.1  
30.8  
3.0  
45.1  
31.9  
3.0  
49.4  
25.6  
3.1  
75  
85  
TC  
SHC  
kW  
37.9  
32.8  
3.3  
38.7  
26.9  
3.3  
41.5  
27.8  
3.4  
45.5  
22.7  
3.4  
38.7  
34.6  
3.3  
39.4  
28.2  
3.3  
42.3  
29.2  
3.4  
46.3  
23.6  
3.4  
39.7  
37.0  
3.3  
40.2  
30.0  
3.3  
43.2  
31.1  
3.4  
47.2  
24.8  
3.4  
TC  
SHC  
kW  
36.2  
32.0  
3.7  
36.8  
26.1  
3.7  
39.6  
27.0  
3.7  
43.4  
21.9  
3.8  
36.9  
33.8  
3.7  
37.5  
27.4  
3.7  
40.3  
28.4  
3.7  
44.1  
22.8  
3.8  
37.8  
35.9  
3.7  
38.2  
29.1  
3.7  
41.0  
30.3  
3.7  
44.9  
24.0  
3.8  
95  
TC  
SHC  
kW  
34.2  
31.0  
4.1  
34.8  
25.2  
4.1  
37.4  
26.2  
4.1  
41.0  
21.1  
4.1  
34.9  
32.7  
4.1  
35.4  
26.5  
4.1  
38.0  
27.6  
4.1  
41.6  
22.0  
4.1  
36.0  
34.3  
4.1  
36.0  
28.3  
4.1  
38.7  
29.4  
4.1  
42.3  
23.2  
4.1  
105  
TC  
SHC  
kW  
32.1  
30.0  
4.5  
32.6  
24.3  
4.5  
35.0  
25.2  
4.5  
38.4  
20.2  
4.5  
32.8  
31.4  
4.5  
33.1  
25.6  
4.5  
35.5  
26.6  
4.5  
38.9  
21.0  
4.6  
34.0  
32.8  
4.5  
33.7  
27.3  
4.5  
36.1  
28.5  
4.5  
39.5  
22.2  
4.6  
115  
125  
TC  
SHC  
kW  
29.8  
28.6  
4.9  
30.1  
23.2  
4.9  
32.3  
24.2  
4.9  
35.3  
19.1  
5.0  
30.6  
29.6  
4.9  
30.5  
24.5  
4.9  
32.7  
25.5  
4.9  
35.7  
20.0  
5.0  
31.7  
30.6  
4.9  
31.0  
26.1  
4.9  
33.2  
27.3  
4.9  
36.2  
21.1  
5.0  
See Legend and Notes on page 13.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)-Standard ECM Indoor Motor  
COOLING CAPACITIES  
50XP048 COOLING PERFORMANCE TABLE  
Evaporator Air—CFM/BF  
Temp (F)  
1260/0.06  
1400/0.06  
1600/0.08  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
45.0  
45.8  
49.6  
54.7  
46.7  
47.3  
51.2  
56.3  
48.1  
48.7  
52.5  
57.8  
TC  
SHC  
kW  
75  
85  
39.3  
3.4  
42.8  
38.2  
3.7  
40.6  
36.9  
4.1  
38.2  
35.7  
4.6  
35.7  
34.4  
5.0  
33.4  
32.1  
5.6  
32.0  
3.4  
43.6  
30.9  
3.7  
41.3  
29.8  
4.1  
38.9  
28.7  
4.6  
36.3  
27.5  
5.0  
33.4  
26.2  
5.6  
33.4  
3.4  
47.2  
32.3  
3.8  
44.7  
31.2  
4.2  
42.1  
30.1  
4.6  
39.3  
28.9  
5.1  
36.2  
27.6  
5.6  
27.2  
3.4  
52.1  
26.2  
3.8  
49.4  
25.2  
4.2  
46.4  
24.0  
4.6  
43.3  
22.9  
5.1  
39.4  
21.5  
5.7  
42.6  
3.4  
44.3  
41.3  
3.7  
41.8  
39.9  
4.1  
39.6  
38.3  
4.6  
38.2  
35.7  
5.1  
34.6  
33.8  
5.6  
34.3  
3.4  
44.9  
33.2  
3.7  
42.4  
32.0  
4.1  
39.8  
30.7  
4.6  
37.1  
29.5  
5.0  
34.1  
28.2  
5.6  
35.8  
3.4  
48.6  
34.7  
3.8  
46.0  
33.6  
4.2  
43.1  
32.3  
4.6  
40.1  
31.0  
5.1  
36.9  
29.7  
5.6  
28.9  
3.5  
53.5  
27.7  
3.8  
50.7  
26.7  
4.2  
47.6  
25.5  
4.7  
44.2  
24.3  
5.1  
40.5  
22.9  
5.6  
45.8  
3.4  
45.6  
44.3  
3.8  
44.2  
43.0  
4.2  
41.5  
40.0  
4.6  
38.7  
38.2  
5.1  
36.1  
35.6  
5.6  
36.8  
3.4  
46.1  
35.5  
3.8  
43.7  
34.6  
4.1  
40.8  
33.2  
4.6  
37.9  
31.8  
5.1  
34.8  
30.2  
5.6  
38.4  
3.4  
49.9  
37.3  
3.8  
47.0  
36.1  
4.2  
44.0  
34.8  
4.6  
40.8  
33.5  
5.1  
37.5  
31.9  
5.6  
30.6  
3.5  
54.8  
29.4  
3.8  
51.8  
28.3  
4.2  
48.5  
27.0  
4.7  
45.0  
25.8  
5.1  
41.2  
24.4  
5.6  
TC  
SHC  
kW  
TC  
SHC  
kW  
95  
TC  
SHC  
kW  
105  
TC  
SHC  
kW  
115  
125  
TC  
SHC  
kW  
50XP060 COOLING PERFORMANCE TABLE  
Temp (F)  
Evaporator Air—CFM/BF  
1750/0.007  
1500/0.004  
2000/0.01  
Outdoor Air  
Entering  
Condenser  
Evaporator Air — Ewb (F)  
62  
63*  
67  
72  
62  
63*  
67  
72  
62  
63*  
67  
72  
57.2  
58.2  
62.4  
68.1  
58.8  
59.7  
64.0  
69.8  
60.0  
60.8  
64.9  
70.8  
TC  
SHC  
kW  
75  
85  
49.4  
4.1  
54.7  
48.2  
4.5  
52.2  
47.0  
5.0  
49.4  
45.7  
5.5  
46.5  
44.3  
6.1  
43.3  
42.8  
6.7  
47.9  
4.1  
55.6  
46.7  
4.5  
53.0  
45.4  
5.0  
50.2  
44.1  
5.6  
47.2  
42.7  
6.2  
43.9  
41.2  
6.8  
41.6  
4.2  
59.7  
40.4  
4.6  
56.9  
39.2  
5.1  
53.8  
37.9  
5.6  
50.5  
36.4  
6.2  
46.7  
34.9  
6.8  
33.8  
4.2  
65.2  
32.6  
4.7  
62.0  
31.4  
5.2  
58.7  
30.1  
5.7  
55.0  
28.7  
6.3  
52.2  
27.8  
6.8  
53.6  
4.2  
56.2  
52.4  
4.7  
53.5  
51.1  
5.1  
50.7  
49.8  
5.7  
48.1  
48.1  
6.2  
45.2  
45.2  
6.8  
51.8  
4.3  
57.0  
50.5  
4.7  
54.3  
49.2  
5.2  
51.4  
47.9  
5.7  
48.3  
46.6  
6.3  
45.1  
45.1  
6.9  
44.5  
4.3  
61.1  
43.2  
4.8  
58.0  
41.9  
5.3  
54.8  
40.6  
5.8  
51.3  
39.2  
6.4  
47.4  
37.6  
7.0  
35.4  
4.4  
66.6  
34.2  
4.9  
63.2  
32.9  
5.3  
59.6  
31.6  
5.9  
56.8  
30.6  
6.4  
52.5  
28.9  
7.0  
57.6  
4.4  
57.4  
56.3  
4.8  
55.0  
55.0  
5.2  
52.5  
52.5  
5.8  
49.7  
49.7  
6.4  
46.4  
46.4  
7.0  
55.4  
4.4  
58.1  
54.2  
4.9  
55.3  
52.9  
5.3  
52.4  
51.6  
5.8  
49.7  
49.7  
6.4  
46.4  
46.4  
7.0  
47.1  
4.5  
61.9  
45.8  
5.0  
58.7  
44.5  
5.5  
55.4  
43.2  
6.0  
51.8  
41.8  
6.6  
47.9  
40.2  
7.2  
36.8  
4.6  
67.4  
35.6  
5.0  
64.1  
34.4  
5.5  
60.2  
33.0  
6.1  
57.0  
31.7  
6.6  
52.2  
29.7  
7.2  
TC  
SHC  
kW  
TC  
SHC  
kW  
95  
TC  
SHC  
kW  
105  
TC  
SHC  
kW  
115  
125  
TC  
SHC  
kW  
LEGEND  
Bypass Factor  
sensible capacity (Btuh)  
1.10 x cfm  
BF  
t
= t  
ldb  
edb  
Ewb  
kW  
SHC  
TC  
Entering Wet-Bulb  
Total Unit Power Input  
t
= Wet-bulb temperature corresponding to enthalpy of air leaving  
lwb  
Sensible Heat Capacity (1000 Btuh)  
Cooling Capacity (1000 Btuh)  
Electronic Computated Motor  
evaporator coil (h  
)
lwb  
total capacity (Btuh)  
4.5 x cfm  
ECM  
*
h
= h  
lwb  
ewb  
TVA Conditions (75°F Entering Dry Bulb)  
Where:  
h
= Enthalpy of air entering evaporator coil  
ewb  
NOTES:  
1. Ratings are net; they do account for the effects  
of the evaporator-fan motor power and heat.  
2. Direct interpolation is permissible. Do not extrapolate.  
3. The following formulas may be used:  
4. The SHC is based on 80°F Edb (Entering dry bulb) air temperature  
through Evaporator coil. Below 80°F Edb, subtract (Correction Factor x  
CFM) from SHC. Above 80°F Edb, add (Correction Factor x CFM) to  
SHC. Correction Factor = 1.10 x (1 – BF) x (Edb – 8)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)  
UNIT50XP  
024-036  
PRESSURE DROP  
0.20  
0.25  
042-060  
MULTIPLICATION FACTORS  
HEATER kW  
RATING  
VOLTAGE  
DISTRIBUTION  
MULTIPLICATION  
FACTOR  
200  
208  
230  
240  
.69  
.75  
.92  
1.00  
240  
Example: 15.0 kW (at 240v) heater on 208 v  
= 15.0 (.75 mult factor)  
= 11.25 capacity at 208 v  
FILTER PRESSURE DROP (In. wg)  
CFM  
FILTER SIZE  
500  
600  
700  
800  
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300  
20 X 20 X 1  
20 X 24 X 1  
24 X 30 X 1  
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15  
0.09 0.10 0.11 0.13 0.14 0.15 0.16  
0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18  
ELECTRIC HEAT PRESSURE DROP TABLES  
Small Cabinet: 024-036  
CFM  
STATIC  
500  
0.00  
0.00  
0.00  
0.00  
600  
0.00  
0.00  
0.00  
0.00  
700  
800  
0.00  
0.00  
0.00  
0.02  
900  
0.00  
0.00  
0.00  
0.04  
1000  
0.00  
0.00  
0.02  
0.06  
1100  
0.00  
0.02  
0.04  
0.08  
1200  
0.00  
0.03  
0.06  
0.10  
1300  
0.02  
0.05  
0.07  
0.12  
1400  
0.04  
0.07  
0.09  
0.14  
1500  
0.06  
0.08  
0.10  
0.16  
1600  
0.07  
0.09  
0.11  
0.18  
5 kW  
0.00  
0.00  
0.00  
0.00  
7.5 kW  
10 kW  
15 kW  
Large Cabinet: 042-060  
CFM  
STATIC  
1100  
0.00  
1200  
1300  
1400  
1500  
0.02  
0.03  
0.03  
0.05  
0.06  
1600  
0.03  
0.04  
0.04  
0.06  
0.07  
1700  
0.04  
0.05  
0.05  
0.07  
0.08  
1800  
0.05  
0.06  
0.06  
0.08  
0.09  
1900  
0.06  
0.07  
0.07  
0.09  
0.10  
2000  
0.07  
0.08  
0.08  
0.10  
0.11  
2100  
2200  
2300  
0.10  
0.11  
0.11  
0.13  
0.14  
2400  
2500  
0.12  
0.13  
0.13  
0.15  
0.16  
5 kW  
0.00  
0.00  
0.00  
0.02  
0.03  
0.00  
0.01  
0.01  
0.03  
0.04  
0.01  
0.02  
0.02  
0.04  
0.05  
0.08  
0.09  
0.09  
0.11  
0.12  
0.09  
0.10  
0.10  
0.12  
0.13  
0.11  
0.12  
0.12  
0.14  
0.15  
7.5 kW  
10 kW  
15 kW  
20 kW  
0.00  
0.00  
0.00  
0.02  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
50XP ECM DRY COIL AIRFLOW–SMALL CABINET  
CFM ADJUST  
PIN SELECT  
LO PIN  
NOM PIN  
HI PIN  
UNIT  
SIZE  
EXTERNAL STATIC  
PRESSURE RANGE  
0.0–0.39  
800  
0.4–0.69  
725  
0.7–1.0  
0.0–0.39  
885  
0.4–0.69  
805  
0.7–1.0  
0.0–0.39  
0.4–0.69  
0.7–1.0  
COOLING  
730  
645  
990  
795  
930  
775  
855  
745  
024  
030  
036  
COOLING  
DEHUMIDIFY  
715  
670  
715  
695  
COOLING  
1010  
890  
920  
825  
795  
970  
910  
1105  
890  
1030  
865  
930  
825  
1255  
1010  
1400  
1125  
1160  
980  
1050  
925  
COOLING  
DEHUMIDIFY  
845  
COOLING  
1115  
940  
1355  
1110  
1280  
1085  
1110  
990  
1025  
960  
1235  
990  
1175  
975  
COOLING  
DEHUMIDIFY  
50XP ECM DRY COIL AIRFLOW–LARGE CABINET  
CFM ADJUST  
PIN SELECT  
LO PIN  
NOM PIN  
HI PIN  
UNIT  
SIZE  
042  
048  
060  
EXTERNAL STATIC  
PRESSURE RANGE  
0.1–1.0  
1100  
980  
0.1–1.0  
1225  
980  
0.1–1.0  
1410  
1125  
1610  
1290  
2010  
1610  
COOLING  
COOLING  
DEHUMIDIFY  
COOLING  
1260  
1120  
1575  
1400  
1400  
1120  
1750  
1400  
COOLING  
DEHUMIDIFY  
COOLING  
COOLING  
DEHUMIDIFY  
50XP ECM WET COIL PRESSURE DROP  
STANDARD CFM  
UNIT  
SIZE  
600  
0.005  
700  
800  
900  
1000  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
024  
030  
036  
042  
048  
060  
0.007 0.010 0.012 0.015  
0.007 0.010 0.012 0.015 0.018 0.021 0.024  
0.019 0.023 0.027 0.032 0.037 0.042 0.047  
0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043  
0.027 0.032 0.036 0.041 0.046 0.052 0.057 0.063 0.068  
0.029 0.032 0.036 0.040 0.045 0.049 0.053  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical piping and wiring  
ROOF-MOUNTING  
CURB  
ROOF  
RETURN-AIR  
FLEXIBLE DUCT  
SUPPLY-AIR  
FLEXIBLE DUCT  
CEILING  
CONCENTRIC DIFFUSER BOX  
(FIELD-SUPPLIED)  
C00023  
INDOOR  
THERMOSTAT  
RETURN  
AIR  
FROM  
POWER  
SOURCE  
TOP COVER  
DISCONNECT  
PER NEC*  
*NEC - NATIONAL ELECTRICAL CODE  
C00063  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data  
Condensate trap — A 2-in. condensate trap must be eld  
supplied.  
openings. Remove the inserts similar to removing an  
electrical knock-out. Leave on duct covers to seal the  
horizontal discharge openings in the unit. Units installed in  
horizontal discharge orientation do not require duct covers.  
1” MIN.  
TRAP  
OUTLET  
Maximum cooling airow — To minimize the possibility  
of condensate blow-off from the evaporator, airow through  
the units should not exceed 450 cfm/ton.  
2” MIN.  
Minimum cooling airow — The minimum airow is 350  
cfm/ton for standard cooling modes. Airow can be lower in  
certain modes when humidity removal is an issue.  
Minimum cooling operating outdoor air temperature —  
All standard units have a minimum outdoor operating  
temperature of 55°F. With accessory low ambient temperature  
kit, units can operate at temperatures down to 0°F.  
Ductwork — Secure downow discharge ductwork to roof  
curb. For horizontal discharge applications, attach ductwork  
to unit with anges.  
To convert a unit to downow discharge — Units are  
equipped with factory-installed inserts in the downow  
Maximum cooling operating outdoor air temperature —  
Maximum outdoor operating air temperature is 125°F.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical data  
UNIT  
VOLTAGE  
RANGE  
OUTDOOR INDOOR  
FAN MOTOR FAN MOTOR  
COMPRESSOR  
ELECTRIC HEAT  
POWER SUPPLY  
MAX FUSE  
UNIT MCA or CKT. BKR.  
SIZE  
50XP  
V-PH-Hz  
Min  
Max  
RLA  
LRA  
FLA  
FLA  
Nominal kW*  
—/—  
3.8/5  
FLA  
—/—  
MOCP  
22.0/22.0  
27.9/31.4  
37.9/42.9  
50.5/57.5  
25.0/25.0  
27.9/31.4  
37.9/42.9  
50.5/57.5  
28.7/28.7  
31.1/34.5  
41.0/46.0  
53.6/60.6  
76.2/86.6  
22.9/22.9  
22.9/23.5  
34.6/38.6  
47.6/53.6  
35.6/35.6  
35.6/35.6  
41.0/46.0  
53.6/60.6  
76.2/86.6  
98.8/112.7  
26.9/26.9  
26.9/26.9  
34.6/38.6  
47.6/53.6  
60.5/68.5  
35.0/35.0  
35.0/35.0  
41.0/46.0  
53.6/60.6  
76.2/86.6  
98.8/112.7  
26.8/26.8  
26.8/26.8  
34.6/38.6  
47.6/53.6  
60.5/68.5  
44.5/44.5  
44.5/44.5  
44.5/48.9  
56.5/63.5  
79.1/89.5  
30/30  
30/35  
40/45  
60/60  
30/30  
30/35  
40/45  
60/60  
35/35  
35/40  
45/50  
18.1/20.8  
26/30  
024 208/230-1-60  
030 208/230-1-60  
187  
253  
13.5  
61.0  
0.8  
4.3  
5.4/7.2  
7.5/10  
—/—  
36.1/41.7  
—/—  
3.8/5  
18.1/20.8  
26/30  
187  
187  
187  
253  
253  
253  
15.9  
16.9  
12.2  
73.0  
83.0  
77.0  
0.8  
0.8  
0.8  
4.3  
6.8  
6.8  
5.4/7.2  
7.5/10  
—/—  
36.1/41.7  
—/—  
3.8/5  
18.1/20.8  
26/30  
208/230-1-60  
5.4/7.2  
7.5/10  
11.3/15  
—/—  
36.1/41.7  
54.2/62.5  
—/—  
60/70  
80/90  
036  
30/30  
30/30  
40/40  
50/60  
45/45  
45/45  
45/50  
5
10  
10.4/12  
20.8/24.1  
31.3/36.1  
—/—  
208/230-3-60  
15  
—/—  
3.8/5  
18.1/20.8  
26/30  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
—/—  
208/230-1-60  
187  
187  
187  
187  
187  
187  
253  
253  
253  
253  
253  
253  
22.4  
15.4  
21.3  
14.7  
27.0  
19.2  
105.0  
88.0  
0.8  
0.8  
1.6  
1.6  
1.6  
1.6  
6.8  
6.8  
6.8  
6.8  
9.1  
9.1  
36.1/41.7  
54.2/62.5  
72.2/83.3  
—/—  
60/70  
80/90  
100/125  
042  
35/35  
35/35  
40/40  
50/60  
45/45  
45/45  
45/50  
3.8/5  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
—/—  
208/230-3-60  
7.5/10  
11.3/15  
15/19.94  
—/—  
70/70  
3.8/5  
18.1/20.8  
26/30  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
—/—  
208/230-1-60  
109.0  
91.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
—/—  
60/70  
80/90  
100/125  
048  
35/35  
35/35  
40/40  
50/60  
60/60  
60/60  
60/60  
3.8/5  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
—/—  
208/230-3-60  
7.5/10  
11.3/15  
15/19.94  
—/—  
70/70  
3.8/5  
18.1/20.8  
26/30  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
—/—  
208/230-1-60  
145.0  
137.0  
36.1/41.7  
54.2/62.5  
60/70  
80/90  
100/125  
060  
72.2/83.3 101.6/115.5  
—/—  
34.7/34.7  
34.7/34.7  
37.4/41.4  
50.5/56.5  
63.3/71.3  
40/40  
40/40  
45/45  
60/60  
3.8/5  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
208/230-3-60  
7.5/10  
11.3/15  
15/19.94  
70/80  
See Legend and Notes on p. 19  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
LEGEND  
FLA  
LRA  
MCA  
— Full Load Amps  
— Locked Rotor Amps  
— Minimum Circuit Amps  
452 + 464 + 455  
®
Average Voltage =  
3
1371  
3
MOCP — Maximum Overcurrent Protection  
RLA  
— Rated Load Amps  
=
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.  
If power distribution voltage to unit varies from rated heater voltage,  
heater KW will vary accordingly.  
= 457  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
(AC) 457 455 = 2 v  
1. In compliance with NEC (National Electrical Code) requirements  
for multimotor and combination load equipment (refer to NEC  
Articles 430 and 440), the overcurrent protective device for the  
unit shall be Power Supply fuse. The CGA (Canadian Gas  
Association) units may be fuse or circuit breaker.  
2. Minimum wire size is based on 60 C copper wire. If other than  
60 C wire is used, or if length exceeds wire length in table,  
determine size from NEC.  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
457  
% Voltage Imbalance = 100 x  
= 1.53%  
3. Unbalanced 3-Phase Supply Voltage  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percentage of voltage imbalance.  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
% Voltage imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical wiring schematic— 208/230-1-60  
20  
C01037  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical wiring schematic— 208/230-3-60  
C03026  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Heating — If accessory electric heaters are installed, on a  
call for heat, circuit R-W is made through the thermostat  
contacts. Circuit R-G is made which energizes the IFM. If  
the heaters are staged, then the thermostat closes a second set  
of contacts (W2) when second stage is required. When  
thermostat is satised, contacts open, deenergizing the  
heater relay. After a preselected delay, the IFM shuts off. If  
the thermostat fan selector switch is in the “ON” position,  
the IFM will run continuously at speed selected on Easy  
Select™ Board.  
Operating sequence  
Cooling — When the system thermostat calls for cooling, 24  
V is supplied to the “Y” and “G” terminals of the thermostat.  
This completes the circuit to the contactor coil (C) and  
indoor (evaporator) fan time delay relay (TDR). The  
normally open contacts of C close and complete the circuit  
to compressor motor (COMP) and to outdoor (condenser)  
fan motor (OFM). Both motors start instantly. The IFM starts  
according to the selection pin set-up on the Easy Select™  
Board.  
On the loss of the thermostat call for cooling, 24 v is  
removed from both the “Y” and “G” terminals (provided the  
fan switch is in the “AUTO” position) deenergizing the  
compressor contactor and opening the contacts supplying  
power to compressor/OFM. After preselected delay, the IFM  
shuts off. If the thermostat fan selector switch is in the “ON”  
position, the IFM will run continuously at speed selected on  
Easy Select™ Board.  
NOTE: On units with a Time Guard® II device: once the  
compressor has started and then stopped, it cannot be  
restarted again until 5 minutes have elapsed.  
The indoor blower operation with a call for fan operation (G)  
in cooling mode will perform by the on/off delay prole  
selected at start up on the Easy Select™ Board.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications  
Packaged Electric Cooling Units  
Constant Volume Application  
5. Unit shall have a field-supplied condensate trap.  
C. Fans:  
1. The evaporator fan shall be direct-drive variable  
speed motor and control, as shown on equipment  
drawings.  
HVAC Guide Specifications  
Size Range: 2 to 5 Tons, Nominal Cooling  
Carrier Model Number: 50XP  
2. Fan wheel shall be made from steel, and shall be  
double-inlet type with forward curved blades with  
corrosion resistant finish. Fan wheel shall be dy-  
namically balanced.  
3. Condenser fan shall be direct drive propeller type  
with aluminum blades riveted to corrosion resistant  
steel spiders, be dynamically balanced, and dis-  
charge air vertically.  
Part 1—General  
SYSTEM DESCRIPTION  
Outdoor rooftop or ground mounted, electric cooling  
unit utilizing a hermetic compressor for cooling duty  
and optional electric heating. Unit shall discharge sup-  
ply air vertically or horizontally as shown on contract  
drawings. Condenser fan/coil section shall have a  
draw-thru design with vertical discharge for minimum  
sound levels.  
D. Compressor:  
1. Fully hermetic compressors with factory-installed  
vibration isolation.  
2. Scroll compressors shall be standard on all units.  
E. Coils:  
Evaporator and condenser coils shall have aluminum  
plate fins mechanically bonded to seamless copper  
tubes with all joints brazed. (Copper/copper and vinyl-  
coated construction available as option.) Tube sheet  
openings shall be belled to prevent tube wear.  
F. Refrigerant Metering Device:  
QUALITY ASSURANCE  
A. Unit shall be rated in accordance with ARI Standards  
210/240-94 and 270-95.  
B. Unit shall be designed in accordance with UL Standard  
1995.  
C. Unit shall be manufactured in a facility registered to  
ISO 9001 manufacturing quality standard.  
D. Unit shall be UL listed and c-UL certified as a total  
package for safety requirements.  
E. Roof curb shall be designed to conform to NRCA Stan-  
dards.  
Refrigerant metering device shall be of the TXV type.  
G. Filters:  
F. Insulation and adhesives shall meet NFPA 90A re-  
quirements for flame spread and smoke generation.  
G. Cabinet insulation shall meet ASHRAE Standard 62P.  
DELIVERY, STORAGE AND HANDLING  
Unit shall be stored and handled per manufacturer’s  
recommendations.  
Filter section shall consist of field-installed, throw-  
away, 1-in. thick fiberglass filters of commercially  
available sizes.  
H. Controls and Safeties:  
1. Unit controls shall be complete with a self-con-  
tained low voltage control circuit.  
2. Units shall incorporate an internal compressor pro-  
tector that provides reset capability.  
3. Unit shall provide High and Low/Loss-of-Charge  
Pressure Safety Protection.  
I. Operating Characteristics:  
Part 2 — Products  
EQUIPMENT  
A. General:  
Factory-assembled, single-piece, cooling unit. Con-  
tained within the enclosure shall be all factory wiring,  
piping, controls, refrigerant charge (R-410A), and spe-  
cial features required prior to field start-up.  
B. Unit Cabinet:  
1. Unit shall be capable of starting and running at  
125°F ambient outdoor temperature, exceeding  
maximum load criteria of ARI Standard 210.  
2. Compressor with standard controls shall be capable of  
operation down to 55° F ambient outdoor temperature.  
3. Indoor Fan on/off delay profile is selected (for cool-  
ing) on the Easy Select™ Board.  
1. Unit cabinet shall be constructed of phosphated,  
zinc-coated, pre-painted steel capable of withstand-  
ing 500 hours of salt spray.  
2. Normal service shall be through a single removable  
cabinet panel.  
3. The unit shall be constructed on a rust proof base-  
pan that has an externally trapped, integrated sloped  
drain pan.  
4. Evaporator fan compartment top surface shall be in-  
sulated with a minimum 1/2-in. thick, flexible fiber-  
glass insulation, coated on the air side and retained  
by adhesive and mechanical means. The evaporator  
wall sections will be insulated with a minimum  
semi-rigid foil-faced board capable of being wiped  
clean. Aluminum foil-faced fiberglass insulation  
shall be used in the entire indoor air cavity section.  
J. Electrical Requirements:  
All unit power wiring shall enter the unit cabinet at a  
single location.  
K. Motors:  
1. Compressor motors shall be of the refrigerant-  
cooled type with line-break thermal and current  
overload protection.  
2. All fan motors shall have permanently lubricated  
bearings, and inherent, automatic reset, thermal  
overload protection.  
3. Condenser fan motor shall be totally enclosed.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications (cont)  
L. Grille  
7. Filter Rack Kit:  
Shall provide filter mounting for downflow or hori-  
zontal applications.  
8. Square-To-Round Duct Transitions (024-048):  
Shall have the ability to convert the supply and re-  
turn openings from rectangular to round. (024-048  
only)  
9. Compressor Protection (Time Guard® II Kit)  
Solid-state control shall protect compressor by pre-  
venting “short cycling.”  
1. Louvered Grille:  
Louvered grille shall be standard on all units.  
M. Special Features Available  
1. Coil Options:  
Shall include factory-installed optional tin-plated  
indoor, copper/copper and vinyl-coated refriger-  
ant coils.  
2. Economizer:  
a. Economizer controls capable of providing free  
cooling using outside air.  
10. Crankcase Heater:  
b. Equipped with low leakage dampers not to ex-  
ceed 3% leakage, at 1.0 in. wg pressure differen-  
tial.  
Shall provide anti-floodback protection for low-  
load cooling applications.  
11. Electric heaters:  
c. Spring return motor shuts off outdoor damper on  
power failure.  
3. Flat Roof Curb:  
a. Electric heater shall be available as a field-  
installed option.  
b. Heater elements shall be open wire type, ade-  
quately supported and insulated with ceramic  
bushings.  
Curbs shall have seal strip and a wood nailer for  
flashing and shall be installed per manufacturer’s  
instructions.  
c. Electric heater packages must provide single  
point power connection capability.  
12. Compressor Hard start kit:  
4. Manual Outdoor Air Damper:  
Package shall consist of damper, birdscreen, and  
rainhood which can be preset to admit outdoor air  
for year-round ventilation.  
Shall be available to give a boost to the compressor  
motor at each start-up. (Single Phase only).  
5. Thermostat:  
To provide for one-stage heating and cooling in ad-  
dition manual or automatic changeover and indoor  
fan control.  
6. Low Ambient Package:  
Shall consist of a solid-state control and condenser  
coil temperature sensor for controlling condenser-  
fan motor operation, which shall allow unit to oper-  
ate down to 0° F outdoor ambient temperature.  
Copyright 2005 Carrier Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
Printed in U.S.A.  
edition date: 10/05  
Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations  
Catalog No: 50XP-4PD  
Replaces: 50XP-3PD  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Computer Accessories P35767ec User Manual
Bionaire Electric Heater BCH9208 User Manual
Blanco Indoor Furnishings 501 118 12 User Manual
Bodum Coffee Grinder 10903 User Manual
BodyCraft Home Gym F413 User Manual
Breville Coffeemaker BDC600XL User Manual
Briggs Stratton Tiller 5055 6 HP User Manual
Bush Hog Compact Excavator CBH60 User Manual
Carrier Heat Pump 25HCB3 User Manual
Chief Manufacturing Indoor Furnishings LCD2C User Manual