Carrier Air Conditioner 19XRV User Manual

19XRV  
with PIC III Controls  
Rockwell PowerFlex 755 VFD Option  
Start-Up and Service Instructions  
SAFETY CONSIDERATIONS  
Centrifugal liquid chillers are designed to provide safe and  
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS  
INTERRUPTED, confirm that all circuits are deenergized before resuming  
work.  
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.  
USE SAFETY GOGGLES. Wash any spills from the skin with soap and  
water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES  
with water and consult a physician.  
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is  
under pressure or while chiller is running. Be sure pressure is at 0 psig (0  
kPa) before breaking any refrigerant connection.  
reliable service when operated within design specifica-  
tions. When operating this equipment, use good judgment  
and safety precautions to avoid damage to equipment and  
property or injury to personnel.  
Be sure you understand and follow the procedures and  
safety precautions contained in the chiller instructions as  
well as those listed in this guide.  
DANGER  
ONLY QUALIFIED Electrical Personnel familiar with the construction  
and operation of this equipment and the hazards involved should install,  
adjust, operate, or service this equipment.  
READ AND UNDERSTAND this manual and other applicable manuals in  
their entirety before proceeding. Failure to observe this precaution could  
result in severe bodily injury or loss of life.  
DO NOT install modification kits with power applied to the drive. Discon-  
nect and lock out incoming power before attempting such installation or  
removal. Failure to observe this precaution could result in severe bodily  
injury or loss of life  
UNUSED WIRES in conduit must be grounded at both ends to avoid a  
possible shock hazard caused by induced voltages. Also, if a drive sharing  
a conduit is being serviced or installed; all drives using this conduit should  
be disabled to eliminate the possible shock hazard from cross-coupled  
motor leads. Failure to observe these precautions could result in bodily  
injury.  
DO NOT VENT refrigerant relief valves within a building. Outlet from  
rupture disc or relief valve must be vented outdoors in accordance with the  
latest edition of ANSI/ASHRAE 15 (American National Standards Insti-  
tute/American Society of Heating, Refrigerating, and Air Conditioning  
Engineers). The accumulation of refrigerant in an enclosed space can dis-  
place oxygen and cause asphyxiation.  
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15,  
especially for enclosed and low overhead spaces. Inhalation of high con-  
centrations of vapor is harmful and may cause heart irregularities, uncon-  
sciousness, or death. Misuse can be fatal. Vapor is heavier than air and  
reduces the amount of oxygen available for breathing. Product causes eye  
and skin irritation. Decomposition products are hazardous.  
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any  
purpose. Oxygen gas reacts violently with oil, grease, and other common  
substances.  
CAUTION  
TO AVOID an electric shock hazard, verify that the voltage on the bus  
capacitors has discharged completely before servicing. Check the DC bus  
voltage at the Power Terminal Block by measuring between the +DC and -  
DC terminals, between the +DC terminal and the chassis, and between the  
-DC terminal and the chassis. The voltage must be zero for all three mea-  
surements.  
THE USER is responsible to conform with all applicable local, national,  
and international codes. Failure to observe this precaution could result in  
damage to, or destruction of, the equipment.  
THIS DRIVE contains ESD (Electrostatic Discharge) sensitive parts and  
assemblies. Static control precautions are required when installing, testing,  
servicing or repairing this assembly. Component damage may result if  
ESD control procedures are not followed. For static control procedures,  
reference Rockwell publication Guarding Against Electrostatic Damage, or  
any other applicable ESD protection handbook.  
DO NOT alter the setting of any jumper. Failure to observe this precaution  
could result in damage to, or destruction of, the equipment.  
USE OF power correction capacitors on the output of the drive can result  
in erratic operation of the motor, nuisance tripping, and/or permanent dam-  
age to the drive. Remove power correction capacitors before proceeding.  
Failure to observe this precaution could result in damage to, or destruction  
of, the equipment.  
MOST CODES require that upstream branch circuit protection be pro-  
vided to protect input power wiring. If fuses are chosen as the protection  
method, refer to the PowerFlex 750 user manual. Failure to observe this  
precaution could result in damage to, or destruction of, the equipment.  
DO NOT route signal and control wiring with power wiring in the same  
conduit. This can cause interference with drive operation. Failure to  
observe this precaution could result in damage to, or destruction of, the  
equipment.  
DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rat-  
ing of the drive. Failure to observe this precaution could result in damage  
to, or destruction of, the equipment.  
DO NOT STEP on refrigerant lines. Broken lines can whip about and  
release refrigerant, causing personal injury.  
NEVER EXCEED specified test pressures, VERIFY the allowable test  
pressure by checking the instruction literature and the design pressures on  
the equipment nameplate.  
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.  
DO NOT VALVE OFF any safety device.  
BE SURE that all pressure relief devices are properly installed and func-  
tioning before operating any chiller.  
THERE IS A RISK OF INJURY OR DEATH by electrocution. High volt-  
age may be present on the motor leads even though the motor is not run-  
ning. Open the power supply disconnect before touching motor leads or  
terminals.  
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow  
safe practices when using ladders.  
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move  
inspection covers or other heavy components. Even if components are  
light, use mechanical equipment when there is a risk of slipping or losing  
your balance.  
BE AWARE that certain automatic start arrangements CAN ENGAGE  
THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the  
VFD, tower fans, or pumps.  
WARNING  
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all  
refrigerant (liquid and vapor) has been removed from chiller. Traces of  
vapor should be displaced with dry air or nitrogen and the work area  
should be well ventilated. Refrigerant in contact with an open flame pro-  
duces toxic gases.  
DO NOT work on high-voltage equipment unless you are a qualified elec-  
trician.  
USE only repair or replacement parts that meet the code requirements of  
the original equipment.  
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion,  
rust, leaks, or damage.  
DO NOT WORK ON electrical components, including control panels,  
switches, VFD, or oil heater until you are sure ALL POWER IS OFF and  
no residual voltage can leak from capacitors or solid-state components.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53190012-01 Printed in U.S.A. Form 19XRV-3SS Pg 1 711 3-11 Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Opening the VFD Access Door  
WARNING  
Before removing the drive enclosure, open access door and  
verify that the DC bus voltage has dropped to zero by  
checking the terminals behind the access door. Failure to  
observe this precaution could result in severe bodily injury  
or loss of life.  
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat  
or T20 star, open access door. See Fig. 2.  
2. Check to be sure that the voltage between DC+ and DC-  
and from each DC terminal to the chassis is zero before  
proceeding. See Fig. 3.  
Drive Assembly Catalog Number — See Fig. 4 for  
an example Catalog Number.  
Components and Physical Data — The Allen-  
Bradley PF755 Frame 6 drive is used for the 230-amp rated ap-  
plication (carrier Part No. 19XRV0230...). See Fig. 5.  
The Allen-Bradley PF755 Frame 7 drive is used for the  
335-amp and 445-amp rated application (Carrier Part No.  
19XVR0335... and 19XVR0445... respectively). See Fig. 6.  
Fig. 2 — Opening Access Door  
A19-1831  
L1 L2 L3  
I
1
See Fig. 7 for the dimensions of Frames 6 and 7.  
LOCKOUT/TAGOUT  
O
2
0V  
DC+ DC–  
DC BUS TEST  
TERMINALS  
LOCATED INSIDE  
ACCESS DOOR  
MULTIMETER  
0V  
Fig. 3 — Check DC Bus Terminals  
A19-1814  
A19-1842  
21P 1 0248 3 - 3 - 0 - 0 - C  
21P PF755 VFD  
Customer  
C – Carrier  
Voltage Rating  
1– 460 to 480 v, 60 Hz  
2380 to 415 v, 50 Hz  
3380 to 400 v, 60 Hz  
4– 401 to 439 v, 60 Hz  
Meter Package  
0 – No Meter Package  
1 – Analog Meter Package  
Input Reactor  
PF755 Full Load Amp Rating  
(Maximum Continuous Amps)*  
0248 – 248  
0 – No Input Reactor  
1 3% Input Line Reactor  
0361 361  
0477 – 477  
Disconnect/Breaker Options  
3 – 65 KAIC Capacity Breaker  
4 – 100 KAIC Capacity Breaker  
Drive Assembly  
3 – Unit Mount NEMA 1 Liquid Cooled  
* For Carrier applications, maximum continuous amp  
ratings are 230, 335, and 445.  
Fig. 4 — Drive Assembly Catalog Number Nomenclature  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
A19-  
1832  
LEGEND  
NO.  
1
NAME  
Power Terminals  
PE Grounding Studs  
DESCRIPTION  
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3  
Terminating point to chassis ground  
for incoming motor shield  
2
3
DC Bus and Brake  
Terminals  
+DC, -DC, BR1, BR2  
4
5
PE-A and PE-B  
DC+ and DC-  
MOV and CMC Jumper Wires  
Bus Voltage Test Points  
A19-1833  
LEGEND  
Fig. 5 — Frame 6 Drive Components  
NO.  
1
NAME  
Power Terminals  
PE Grounding Studs  
DESCRIPTION  
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3  
Terminating point to chassis ground  
for incoming motor shield  
2
3
DC Bus and Brake  
Terminals  
+DC, -DC, BR1, BR2  
4
5
PE-A and PE-B  
DC+ and DC-  
MOV and CMC Jumper Wires  
Bus Voltage Test Points  
Fig. 6 — Frame 7 Drive Components  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
If other than refrigerant cooling is used, before connecting  
the drive to the incoming power, make sure that the coolant  
is circulating and has no leaks.  
CAUTION  
When working with the Drive Explorer, never use the  
Rotate function as the motor will immediately start and  
severe compressor damage could result.  
Alternate Wire Lugs — In the case where the incoming  
power wire size does not fit the standard lug, alternate lugs may  
be used. See Table 1. Note that lugs rated for a higher current  
than the circuit breaker may be used.  
Table 1 — Wire Lugs  
STANDARD  
LUG CABLE  
RANGE  
ALTERNATE  
LUG CABLE  
RANGE  
CIRCUIT  
BREAKER  
STANDARD  
ABB LUG  
ALTERNATE  
ABB LUG  
65 KAIC  
(Standard)  
100 KAIC  
(Optional)  
(3) 2/0 - 400  
MCM  
(2) 250 - 500  
MCM  
K6TJ  
K6TH  
Verify Installation Record the following job  
information:  
1. Job Name  
2. Job Number  
A19-1834  
Fig. 7 — Enclosure Dimensions - Frames 6 and 7  
3. City  
4. State  
5. Zip Code  
Record the following nameplate information:  
START-UP  
DANGER  
1. From the Allen-Bradley nameplate (Fig. 1) located inside  
the VFD enclosure:  
Internal components and circuit boards of the drive are live  
when the drive is connected to incoming power. Coming  
into contact with this voltage is extremely dangerous and  
will result in severe personal injury or death.  
The motor terminals U, V, W and the DC-link/brake resis-  
tor terminals B+/R+, R- are live when the drive is con-  
nected to incoming power, even if the motor is not running.  
Do not make any connections when the drive is connected  
to the incoming power.  
After having disconnected the drive, wait until the indica-  
tors on the keypad go out (if no keypad is attached see the  
indicator through the keypad base). Wait 5 more minutes  
before doing any work on drive connections. Do not even  
open the cover before this time has expired..  
a. Allen-Bradley ID or CAT NO.  
b. Allen-Bradley Serial Number  
c. Carrier Part Number  
2. From the machine nameplete (Fig. 8) located inside the  
VFD enclosure:  
a. Chiller Serial Number  
b. Chiller Model  
c. Motor rated load amps  
d. Motor nameplate rpm  
e. Motor nameplate kW  
f. Motor nameplate voltage  
g. IPWM (pulse width modulation) frequency  
h. Voltage  
Before connecting the drive to the incoming power, make  
sure that the switchgear enclosure door is closed.  
3. From the drive module label (Fig. 9) located on the drive  
module:  
WARNING  
a. Model or Cat. Number  
b. Serial Number  
4. From the ICVC control panel screen:  
a. Carrier Part Number and Revision  
b. ICVC Software Number  
Rockwell PowerFlex 750 drive start-up must be registered  
on the Rockwell website. Rockwell Registration site URL:  
The control I/O-terminals are isolated from the mains  
potential. However, the relay outputs and other I/O termi-  
nals may have a dangerous control voltage present even  
when the drive is disconnected from incoming power.  
Coming into contact with this voltage could result in severe  
personal injury.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configure the VFD — All configurations required by  
the VFD are supplied by the ICVC through the VFD Gateway.  
Any configuration changes necessary and possible are made on  
the ICVC screens. A complete set of configurations is transmit-  
ted to the VFD each time the controls are powered up.  
a19-  
1846  
The following is from the 19XRV PIC III ICVC screen. Pa-  
rameters in italics are to be entered or confirmed at start-up. Pa-  
rameters in bold are to be changed only after consulting with  
Carrier service engineering. See Table 2.  
A United Technologies Company  
Table 2 VFD Configurations  
MODEL NUMBER  
SERIAL NUMBER  
PARAMETER  
Motor Nameplate Voltage  
Compressor 100% Speed  
Line Freq=60 Hz? (No=50)  
Rated Line Voltage*  
DEFAULT VALUE  
MACHINE NAMEPLATE SUPPLY DATA  
460  
VOLTS/PHASE/HERTZ  
LOCKED ROTOR AMPS  
OVERLOAD TRIP AMPS  
Yes  
460  
200  
100  
100  
200  
100  
3456  
100  
MAX FUSE/CIRCUIT BREAKER SIZE  
MIN SUPPLY CIRCUIT AMPACITY  
Rated Line Amps*  
MACHINE ELECTRICAL DATA  
MOTOR NAMEPLATE VOLTAGE  
Rated Line Kilowatts *  
Motor Rated Load kW*  
Motor Rated Load Amps*  
Motor Nameplate Amps  
Motor Nameplate RPM  
Motor Nameplate KW  
Inverter PWM Frequency (0 = 4 kHz, 1 =  
2 kHz)  
Skip Frequency 1 (Hz)  
Skip Frequency 2 (Hz)  
Skip Frequency 3 (Hz)  
Skip Frequency Band Line (Hz)  
Voltage % Imbalance  
COMPRESSOR 100% SPEED  
RATED LINE VOLTAGE  
RATED LINE AMPS  
RATED LINE KILOWATTS  
MOTOR RATED LOAD KW  
MOTOR RATED LOAD AMPS  
MOTOR NAMEPLATE AMPS  
MOTOR NAMEPLATE RPM  
MOTOR NAMEPLATE KW  
INTERTER PWM FREQUENCY  
1
102.0  
102.0  
102.0  
0.0  
10  
Line Volt Imbalance Time (sec)  
Line Current % Imbalance  
Line Current Imbal Time (sec)  
Motor Current % Imbalance  
Motor Current Imbal Time  
Increase Ramp Time (sec)  
Decrease Ramp Time (sec)  
Single Cycle Dropout (DSABLE/ENABLE)  
10  
40  
10  
40  
10  
30  
30  
SAFETY CODE CERTIFICATION  
THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE  
IN ACCORDANCEWITH CARRIER SPECIFICATION Z-420.  
19XV05008701 REV. 3  
DSABLE  
Fig. 8 — Machine Nameplate  
* Parameters marked with an * are not downloadable to the VFD but are used  
in other calculations and algorithms in the ICVC.  
NOTES:  
1. Parameters in italics are to be entered or confirmed at start-up.  
2. Parameters in bold are to be changed only after consultation with ser-  
vice engineering.  
Commissioning the Unit — The commission proce-  
dure is as follows:  
1. If the chiller has been stored outdoors, allow at least 24  
hours room temperature stabilization prior to commis-  
sioning. Ensure any condensation that occurs as a result  
of the ambient temperature is allowed to evaporate.  
2. Enter parameters in the VFD_CONF screen.  
3. Install surge suppression devices if required.  
4. Review the power wiring and grounding to ensure that it  
has been properly connected.  
5. Visually examine the inside of the drive enclosure to:  
a. Look for signs of corrosion or moisture residue.  
b. Remove any dirt or debris.  
a19-  
1924  
c. Make sure all vents are clear.  
6. Apply power to the drive and take thermal measurements  
of the capacitor bank and power connections. Do this  
again before start-up.  
7. Measure and record the incoming line voltage. Line-to-  
line voltages should be balanced within 3% as calculated  
by Rockwell’s procedure below:  
Fig. 9 — Drive Module Label  
Measure voltages phase-to-phase and phase-to-ground.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vmax = Maximum measured phase-to-phase voltage  
(A to B, B to C, C to A)  
Vmin = Minimum measured phase-to-phase voltage  
Imbalance Calculation Formula  
b. Check motor and wiring insulation.  
c. Check parameter settings on VFD_CONF screen  
in the ICVC.  
Check Internal Jumpers — On the Main VFD Con-  
trol board there are two jumpers labeled J1 HARDWARE EN-  
ABLE and J2 SAFETY ENABLE. J1 should be removed and  
J2 should be in place. See Fig. 10.  
There are two jumper wires that connect a particular termi-  
nal to chassis ground. The MOV and AC EMI jumper should  
be connected to the PE-A terminal. The COMMON MODE  
CAPACITORS to GROUND jumper should be connected to a  
standoff rather than the PE-B terminal.  
Use the recommended tools as follows when connecting  
jumper wires in Frame 6 and in Frame 7:  
• Recommended torque (screws and nuts) = 1.36 N·m  
(120.0 lb·in)  
(VAB + VBC + VCA)  
Vavg  
=
=
3
(Vmax – Vmin) x 100  
Vavg  
Imbalance %  
8. Take a final thermal measurement of the capacitor bank  
and power after finalizing the installation to ensure all  
connections are good.  
9. If a ground fault occurs, then do the following:  
a. Check for a ground in the motor or motor wiring.  
b. Check for damage to wiring insulation and that  
wiring is dry.  
c. Verify the motor wiring is separated from ground  
and there is no connection between phases.  
d. Check for failed IGBTs.  
• Recommended hex socket = 7 mm  
• Recommended screwdriver = T20 star type  
See Fig. 11A and Fig. 11B for the correct positions of the  
jumpers.  
10. If an Overcurrent fault occurs, then do the following:  
a. Check for excessive load and verify load limit set-  
tings on the ICVC.  
LEGEND  
NO.  
1
NAME  
HIM Connector  
Fan Connector  
DESCRIPTION  
DPI Port 1 (HIM Cradle) connection.  
Power supply for internal cooling fan  
(Frames 2 & 3).  
2
Battery  
Receptacle  
User installed CR1220 lithium coin cell  
battery provides power to the Real Time  
Clock (Optional, not supplied).  
3
DPI Port 2  
Cable connection for handheld and  
remote HIM options.  
4
5
Embedded EtherNet/ Rotary switches for setting lowest octet  
IP Address Selectors of EtherNet address (forces address to  
192.168.1.xxx).  
Embedded EtherNet/ Network cable connection.  
IP Connector  
6
7
Jumper J2 SAFETY Safety enable jumper. Removed when  
safety option is installed.  
Jumper J1 ENABLE Hardware enable jumper. Removed  
when a hardware enable configuration is  
utilized.  
8
9
TB1  
I/O terminal block.  
a19-1921  
TB1 I/O Terminal Designations  
NAME  
FIXED I/O  
TERMINAL  
DESCRIPTION  
Digital Input 120V AC  
Digital Input Common  
Digital Input 24V DC  
+24 Volt Power  
Connections for AC power supply.  
Digital input common  
Di 0ac  
Di C  
Di 0dc  
+24V  
Di 0ac  
Di C  
Connections for DC power supply.  
Connections for drive supplied 24V power.  
Di 0dc  
+24V  
24VC  
24 Volt Common  
24VC  
IMPORTANT: Wiring to pluggable terminal block connectors  
should be supported by wire ties or other means to help pre-  
vent unintentional disconnection  
Fig. 10 — PF755 Main Control Board  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting the Drive — The drive can display  
two kinds of error codes on the ICVC called the Alert and  
Alarm codes. These codes signal a problem detected during  
self tuning or drive operation. Alert and Alarm codes are locat-  
ed in the 19XRV Start-Up, Operation and Maintenance Instruc-  
tions. Note the following differences between Carrier and  
Allen-Bradley terminology:  
• A warning message on the ICVC is an ALERT.  
• The same warning viewed with Rockwell Drive Explorer  
is a VFD ALARM.  
• A failure resulting in a shutdown is seen as an ALARM  
on the ICVC and as a VFD FAULT when viewed with  
Drive Explorer.  
CONDITION CODES  
ICVC ALERT  
ICVC ALARM  
=
=
VFD ALARM  
VFD FAULT  
See Tables 3-6 and Fig. 12.  
A19-1835  
ICVC ALERT CODES — An alert condition is indicated by  
a message at the top of the ICVC default screen. In addition, an  
exclamation point (!) will appear next to any affected point on  
an ICVC display screen. The drive will continue to operate  
during the alert condition. Investigate the cause of the alert to  
ensure it does not lead to a fault condition. The alert code will  
automatically be cleared from the ICVC when the condition  
causing the alert no longer exists. See Table 4.  
Fig. 11A — Jumper Wire Locations — Frame 6  
ICVC ALARM CODES — An alarm condition is also indi-  
cated by a message at the top of the ICVC default screen. If an  
alarm occurs, the drive coasts to stop. The STS (status) light on  
the drive will turn from Green to Red or Yellow (see Table 3).  
The detected fault message is maintained on the display until it  
is cleared by pressing the RESET softkey. See Table 5.  
TEST EQUIPMENT NEEDED TO TROUBLESHOOT —  
An isolated multimeter adequately rated for the DC bus volt-  
age will be needed to measure DC bus voltage and to make  
resistance checks. Note that dedicated troubleshooting test  
points are not provided.  
Allen-Bradley  
A19-1836  
8
7
9
4
5
2
6
Fig. 11B — Jumper Wire Locations — Frame 7  
1
3
SERVICE  
WARNING  
DC bus capacitors retain hazardous voltages after input  
power has been disconnected. After disconnecting input  
power, wait five (5) minutes for the DC bus capacitors to  
discharge and then check the voltage with a voltmeter to  
ensure the DC bus capacitors are discharged before touch-  
ing any internal components. Failure to observe this pre-  
caution could result in severe bodily injury or loss of life.  
A1  
9-  
1815  
Fig. 12 — Drive Status Indicator  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 Drive Status Indicator Descriptions  
NAME  
COLOR  
Green  
STATE  
Flashing  
Steady  
DESCRIPTION  
Drive ready but not running, and no faults are present.  
Drive running, no faults are present.  
Yellow  
Flashing  
Drive is not running. A type 2 (non-configurable) alarm condition exists and the  
drive cannot be started.  
Steady  
Drive is not running, a type 1 alarm condition exists. The drive can be started.  
Red  
Flashing  
A major fault has occurred. Drive cannot be started until fault condition is  
cleared.  
STS (Status)  
Steady  
A non-resettable fault has occurred.  
Red/Yellow  
Flashing Alternately  
A minor fault has occurred. When running, the drive continues to run. System is  
brought to a stop under system control. Fault must be cleared to continue. Use  
parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major  
fault.  
Green/Red  
None (Unlit)  
Flashing Alternately  
Off  
Drive is flash updating.  
Adapter and/or network is not powered, adapter is not properly connected to  
the network, or adapter needs an IP address.  
Red  
Flashing  
Steady  
Flashing Alternately  
Flashing  
An EtherNet/IP connection has timed out.  
Adapter failed the duplicate IP address detection test.  
Adapter is performing a self-test.  
Adapter is properly connected but is not communicating with any devices on  
the network.  
ENET  
Red/Green  
Green  
Steady  
Off  
Flashing  
Steady  
Adapter is properly connected and communicating on the network.  
Adapter is not powered or is not transmitting on the network.  
Adapter is properly connected and transmitting data packets on the network.  
Adapter is properly connected but is not transmitting on the network.  
None (Unlit)  
Green  
LINK  
NOTES:  
2. A Type 2 alarm indicates that a configuration error exists and  
the drive cannot be started. Type 2 alarms are not configurable.  
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms  
are user configurable.  
VERIFYING THAT DC BUS CAPACITORS ARE DIS-  
CHARGED — The drive’s DC bus capacitors retain hazard-  
ous voltages after input power has been disconnected. Perform  
the following steps before touching any internal components:  
1. Turn off and lock out input power. Wait five minutes.  
2. Verify that there is no voltage at the drive’s input power  
terminals.  
3. Measure the DC bus potential with a voltmeter while  
standing on a non-conductive surface and wearing insu-  
lated gloves (1000 V). Measure the DC bus potential. See  
Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and  
477-amp drives. The voltage between DC+ and DC-, and  
from each DC terminal to the chassis must be zero before  
proceeding.  
SWING UP KEY PAD  
MOUNT TO ACCESS  
CONTROL BOARDS  
4. Once the drive has been serviced, reapply input power.  
HIGH TEMPERATURE ALARMS  
Coolant flow  
through the cold plate is controlled by an orifice in the refriger-  
ant line leaving the cold plate. The orifice looks like one of the  
O-ring face seal connectors and in fact is used as one of the  
connections on the coolant tubing. The difference is that the  
passage through the fitting is 0.375 in. (9.5 mm). If the orifice  
is present and condenser liquid flow is present, the liquid will  
flash to cooler temperature at the orifice. This temperature dif-  
ference is great enough to be easily felt.  
MAIN CONTROL BOARD (MCB) COMPONENTS —  
Figure 13 shows the drive module with the cover removed. To  
access the control boards, loosen the screw on the face of the  
keypad mount and swing the keypad mount upward.  
The components on the main control board (MCB) are  
shown in Fig. 14. Note the location of the terminals labeled  
MCB I/O. The high pressure switch is wired to these terminals  
as shown in Fig. 15. In the event of a high condenser pressure  
alarm, the connections at these terminals should be checked  
and tightened if necessary.  
a19-1843  
Fig. 13 — Drive Module with Cover Removed  
A typical wiring schematic is shown in Appendix A.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DPI PORT 02 (COMPUTER PORT)  
DIGITAL INPUT TERMINAL BLOCKS  
(SLOTS 04 & 05)  
ETHERNET/IP ADDRESS SWITCHES  
DIGITAL OUTPUT TERMINAL BLOCKS  
(SLOTS 04 & 05)  
EMBEDDED ETHERNET/IP PORT  
MCB I/O TERMINALS  
(AUX FAULT /  
HIGH PRESSURE FAULT /  
ENABLE INPUT)  
Fig. 14 — MCB (Main Control Board) Components  
a19-1844  
*Located outside of starter; connected by field wiring.  
Fig. 15 — High Pressure Switch Wiring  
a19-1925  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — ICVC Alert Codes  
PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is  
necessary.  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
100  
PRESTART  
ALERT  
STARTS LIMIT  
EXCEEDED  
100Excessive compressor starts  
(8 in 12 hours).  
Depress the RESET softkey if additional start  
is required. Reassess start-up requirements.  
101  
PRESTART  
ALERT  
HIGH BEARING  
TEMPERATURE  
101Comp Thrust Brg Temp [VALUE] Check oil heater for proper operation.  
exceeded limit of [LIMIT]*.  
Check for low oil level, partially closed oil sup-  
ply valves, clogged oil filters.  
Check the sensor wiring and accuracy.  
Check Comp Thrust Brg Alert setting in  
SETUP1 screen.  
102  
PRESTART  
ALERT  
HIGH MOTOR  
TEMPERATURE  
102Comp Motor Winding Temp  
[VALUE] exceeded limit of [LIMIT]*.  
Check motor sensors for wiring and accuracy.  
Check motor cooling line for proper operation,  
or restrictions.  
Check for excessive starts within a short time  
span.  
Check Comp Motor Temperature Override  
setting in SETUP1 screen.  
103  
104  
PRESTART  
ALERT  
HIGH  
103Comp Discharge Temp [VALUE] Allow discharge sensor to cool.  
DISCHARGE  
TEMP  
exceeded limit of [LIMIT]*.  
Check sensor wiring and accuracy.  
Check for excessive starts.  
Check Comp Discharge Alert setting in  
SETUP1 screen.  
PRESTART  
ALERT  
LOW  
REFRIGERANT  
TEMP  
104Evaporator Refrig Temp [VALUE] Check transducer wiring and accuracy.  
exceeded limit of [LIMIT]*.  
Check for low chilled fluid supply  
temperatures.  
Check refrigerant charge.  
Check Refrig Override Delta T in SETUP1  
screen.  
105  
106  
PRESTART  
ALERT  
PRESTART  
ALERT  
LOW OIL  
105Oil Sump Temp [VALUE]  
Check oil heater contactor/relay and power.  
Check oil level and oil pump operation.  
TEMPERATURE  
exceeded limit of [LIMIT]*.  
HIGH  
CONDENSER  
PRESSURE  
106Condenser Pressure [VALUE]  
exceeded limit of [LIMIT]*.  
Check transducer wiring and accuracy.  
Check for high condenser water  
temperatures.  
Check high condenser pressure switch wiring.  
107  
108  
109  
PRESTART  
ALERT  
LOW LINE  
VOLTAGE  
107Percent Line Voltage [VALUE]  
Check voltage supply.  
exceeded limit of [LIMIT]*.  
Check voltage transformers and switch gear.  
Consult power utility if voltage is low.  
PRESTART  
ALERT  
HIGH LINE  
VOLTAGE  
108Percent Line Voltage [VALUE]  
exceeded limit of [LIMIT]*.  
Check voltage supply.  
Check power transformers.  
Consult power utility if voltage is high.  
Press STOP button on ICVC and perform  
Guide Vane Calibration in Controls Test  
screen.  
Check guide vane actuator feedback  
potentiometer.  
PRESTART  
ALERT  
GUIDE VANE  
CALIBRATION  
109Actual Guide Vane Pos  
Calibration Required Before Startup.  
110  
111  
PRESTART  
ALERT  
HIGH  
110Rectifier Temperature [VALUE]  
Check that VFD refrigerant isolation valves  
are open.  
RECTIFIER  
TEMP  
exceeded limit of [LIMIT]*.  
Check VFD refrigerant cooling solenoid and  
refrigerant strainer.  
Check for proper VFD cooling fan operation  
and blockage.  
PRESTART  
ALERT  
HIGH  
INVERTER  
TEMP  
111Inverter Temperature [VALUE]  
exceeded limit of [LIMIT]*.  
Check that VFD refrigerant isolation valves  
are open.  
Check VFD refrigerant cooling solenoid and  
refrigerant strainer.  
Check for proper VFD cooling fan operation  
and blockage.  
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is  
the actual pressure, temperature, voltage, etc., at which the control tripped.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — ICVC Alert Codes (cont)  
NORMAL RUN WITH OVERRIDES  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
120  
121  
122  
RUN CAPACITY  
LIMITED  
HIGH CONDENSER  
PRESSURE  
120Condenser Pressure  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check condenser water pump operation.  
Check for high condenser water temperatures or  
low flow rate. Verify that isolation valves are  
open.  
Check Cond Press Override setting in SETUP1.  
RUN CAPACITY  
LIMITED  
HIGH MOTOR  
TEMPERATURE  
121Comp Motor Winding Check for closed valves or restriction in motor  
Temp [VALUE] exceeded  
limit of [LIMIT]*.  
cooling lines.  
Check for closed refrigerant isolation valves.  
Check Comp Motor Temp Override setting in  
SETUP1.  
RUN CAPACITY  
LIMITED  
LOW EVAP REFRIG  
TEMP  
122Evaporator Refrig  
Temp [VALUE] exceeded  
limit of [LIMIT]*.  
Check refrigerant charge.  
Check that optional cooler liquid line isolation  
valve is fully open.  
Check for excessive condenser flow or low  
chilled water flow.  
Check for low entering cooler temperature.  
Check that condenser inlet and outlet water  
nozzles are piped correctly.  
Check for waterbox division plate gasket bypass.  
123  
RUN CAPACITY  
LIMITED  
HIGH COMPRESSOR  
LIFT  
123Surge Prevention  
Override: Lift Too High For  
Compressor  
Check for high condenser water temperature or  
low suction temperature.  
Check for high Evaporator or Condenser  
approaches.  
Check surge prevention parameters in  
OPTIONS screen.  
124  
125  
126  
RUN CAPACITY  
LIMITED  
MANUAL GUIDE VANE  
TARGET  
124Run Capacity Limited: Target Guide Vane Position has been forced in  
Manual Guide Vane Target. the COMPRESS screen. Select and RELEASE  
force to return to normal (automatic) operation.  
RUN CAPACITY  
LIMITED  
LOW DISCHARGE  
SUPERHEAT  
No Alert message.  
Check for oil loss or excess refrigerant charge.  
Verify that the valves in the oil reclaim lines are  
open.  
RUN CAPACITY  
LIMITED  
HIGH RECTIFIER TEMP 126Rectifier Temperature Check Rectifier Temp Override in SETUP1  
[VALUE] exceeded limit of  
[LIMIT]*.  
screen.  
Check that VFD refrigerant isolation valves are  
open.  
Check VFD refrigerant cooling solenoid.  
Check for proper VFD cooling fan operation and  
blockage.  
127  
RUN CAPACITY  
LIMITED  
MANUAL SPEED  
CONTROL  
No Alert message.  
Chiller is not in automatic temperature control.  
128  
RUN CAPACITY  
LIMITED  
HIGH INVERTER TEMP 128Inverter Temperature  
[VALUE] exceeded limit of  
Check Inverter Temp Override in SETUP1  
screen.  
Check that VFD refrigerant isolation valves are  
open.  
[LIMIT]*.  
Check VFD refrigerant cooling solenoid.  
Check for proper VFD cooling fan operation and  
blockage.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — ICVC Alert Codes (cont)  
CHILLER ALERTS  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
140  
141  
142  
SENSOR ALERT  
LEAVING COND WATER  
TEMP  
ENTERING COND WATER 141Sensor Fault: Check  
TEMP  
140Sensor Fault: Check  
Check sensor resistance or voltage drop.  
Leaving Cond Water Sensor. Check for proper wiring.  
SENSOR ALERT  
Check sensor resistance or voltage drop.  
Entering Cond Water Sensor. Check for proper wiring.  
142Low Oil Pressure Alert. Check for partially or closed shut-off valves.  
Check Oil Filter.  
LOW OIL  
PRESSURE ALERT  
CHECK OIL FILTER  
Check oil filter.  
Check oil pump and power supply.  
Check oil level.  
Check for foaming oil at start-up.  
Check transducer wiring and accuracy.  
143  
144  
AUTORESTART  
PENDING  
LINE CURRENT  
IMBALANCE  
143Line Current Imbal-  
ance: Check VFD Fault His-  
tory for Values.  
144Single Cycle Line  
Voltage Dropout.  
Power loss has been detected in any phase.  
Chiller automatically restarting.  
AUTORESTART  
PENDING  
LINE VOLTAGE  
DROP OUT  
A drop in line voltage has been detected within  
2 voltage cycles.  
Chiller automatically restarting if Auto Restart is  
enabled in OPTIONS screen.  
145  
146  
147  
AUTORESTART  
PENDING  
AUTORESTART  
PENDING  
AUTORESTART  
PENDING  
HIGH LINE VOLTAGE  
LOW LINE VOLTAGE  
VFD MODULE RESET  
145High Percent Line  
Check phase to phase and phase to ground line  
power.  
Check phase to phase and phase to ground line  
power.  
Voltage [VALUE].  
146Low Percent Line  
Voltage [VALUE].  
147->VFD Module Power-On VFD Module has detected a hardware fault due  
Reset When Running.  
to electrical noise, power loss or software and  
has reset. Chiller automatically restarting.  
Check for power loss and sources of electro-  
magnetic interference.  
148  
AUTORESTART  
PENDING  
POWER LOSS  
148Control Power-Loss  
When Running.  
Check 24 vac control power supply to ICVC.  
149  
SENSOR ALERT  
HIGH DISCHARGE TEMP 149Comp Discharge Temp Check sensor resistance or voltage drop.  
[VALUE] Exceeded Limit of  
[LIMIT]*.  
Check for proper wiring.  
Check for proper inlet guide vane and optional  
diffuser actuator operation.  
Check for proper condenser flow and  
temperature.  
Check for high lift or low load.  
Check for fouled tubes or noncondensables in  
the chiller.  
150  
151  
152  
SENSOR ALERT  
CONDENSER  
HIGH BEARING  
TEMPERATURE  
150Comp Thrust Brg Temp Check sensor resistance or voltage drop.  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check for proper wiring.  
Check for partially closed service valves.  
Check oil cooler TXV.  
Check oil level and oil temperature.  
PUMP RELAY  
PRESSURE ALERT ENERGIZED  
151High Condenser Pres- Check sensor wiring and accuracy.  
sure [VALUE]: Pump Ener-  
gized to Reduce Pressure.  
Check condenser flow and water temperature.  
Check for fouled tubes.  
This alarm is not caused by the High Pressure  
Switch.  
RECYCLE ALERT  
EXCESSIVE RECYCLE  
STARTS  
152Excessive recycle  
starts.  
Chiller load is too low to keep compressor on  
line and there has been more than 5 starts in  
4 hours.  
Increase chiller load, adjust hot gas bypass,  
increase RECYCLE RESTART DELTA T from  
SETUP1 Screen.  
153  
154  
no message:  
ALERT  
no message; ALERT only 153Lead/Lag Disabled-  
Config: Duplicate Chiller  
Illegal chiller address configuration in Lead/Lag  
screen. Both chillers require a different address.  
only  
Address.  
POTENTIAL  
FREEZE-UP  
COND PRESS/TEMP  
TOO LOW  
154Condenser freeze up  
prevention.  
The condenser pressure transducer is reading a  
pressure that could freeze the condenser tubes.  
Check for condenser refrigerant leaks.  
Check fluid temperature.  
Check sensor wiring and accuracy.  
Place the chiller in PUMPDOWN mode if the  
vessel is evacuated.  
155  
156  
157  
158  
OPTION SENSOR  
FAULT  
REMOTE RESET  
SENSOR  
155Sensor Fault/Option  
Disabled: Remote Reset  
Sensor.  
156Sensor Fault/Option  
Disabled: Auto Chilled Water Check for proper wiring to CCM connector J5.  
Reset.  
157Sensor Fault/Option  
Disabled: Auto Demand Limit Check for proper wiring to CCM connector J5.  
Input.  
158Spare Temperature 1  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check sensor resistance or voltage drop.  
Check for proper wiring to CCM connector J4.  
OPTION SENSOR  
FAULT  
AUTO CHILLED WATER  
RESET  
Check sensor resistance or voltage drop.  
OPTION SENSOR  
FAULT  
AUTO DEMAND LIMIT  
INPUT  
Check sensor resistance or voltage drop.  
SENSOR ALERT  
SPARE TEMPERATURE  
#1  
Check sensor resistance or voltage drop.  
Check for proper wiring to CCM connector J4.  
Check Spare Temp #1 Limit in SETUP1 screen.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — ICVC Alert Codes (cont)  
CHILLER ALERTS (cont)  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
159  
SENSOR ALERT  
SPARE TEMPERATURE  
#2  
159Spare Temperature 2  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check sensor resistance or voltage drop.  
Check for proper wiring to CCM connector J4.  
Check Spare Temp #2 Limit in SETUP1 screen.  
161  
LOSS OF  
COMMUNICATION  
WITH WSM  
161WSM Cool Source —  
Loss of Communication.  
Check settings in WSMDEFME screen.  
Check CCN communications link with WSM  
(Water System Manager) Module.  
Check Supervisory Part of WSM.  
162  
163  
SENSOR ALERT  
SENSOR ALERT  
EVAPORATOR  
APPROACH  
162Evaporator Approach  
[VALUE] Exceeded Limit of  
[LIMIT]*.  
Check that refrigerant charge level is adequate,  
waterbox division plate gaskets are sealing,  
evaporator tubes are not fouled and that oil  
reclaim system is working.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check Evap Approach Alert setting in SETUP1  
screen.  
CONDENSER APPROACH 163Condenser Approach  
[VALUE] Exceeded Limit of  
Check sensors resistance or voltage drop.  
Check for proper wiring.  
[LIMIT]*.  
Check Cond Approach Alert setting in SETUP1  
screen.  
Check for noncondensable gas in the  
condenser.  
Check that the condenser tubes are not fouled.  
164  
165  
166  
167  
VFD SPEED ALERT LOW VFD SPEED  
164Actual VFD Speed  
Actual VFD Speed on COMPRESS screen must  
exceeded limit of Target VFD be at least 90% of Target VFD Speed.  
Speed –10%.  
AUTORESTART  
PENDING  
LOW DC BUS VOLTAGE  
165Low DC Bus Voltage:  
[VALUE] Exceeded Limit of  
[LIMIT]*.  
166High DC Bus Voltage:  
[VALUE] Exceeded Limit of  
[LIMIT]*.  
Verify phase to phase and phase to ground line  
voltage.  
AUTORESTART  
PENDING  
HIGH DC BUS VOLTAGE  
Verify phase to phase and phase to ground line  
voltage. Monitor AC line for high transient volt-  
age conditions.  
SYSTEM ALERT  
HIGH DISCHARGE TEMP 167Comp Discharge Temp Check sensor resistance or voltage drop.  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check for proper wiring.  
Check for excessive starts.  
Check Comp Discharge Alert setting in SETUP1  
screen.  
168  
SENSOR ALERT  
HUMIDITY SENSOR  
INPUT  
168Sensor Fault: Check  
Check humidity sensor wiring on CCM connec-  
Humidity Sensor Input Sensor. tors J3 and J5. CCM switch SW2-1 must be in  
“OFF” position.  
Check Humidity Sensor Input in Controls Test.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — ICVC Alarm Codes  
CHILLER PROTECTIVE LIMIT FAULTS  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
200  
201  
202  
PROTECTIVE LIMIT RECTIFIER POWER  
200Rectifier Power Fault:  
Malfunction within VFD Power Module.  
Call Carrier Service.  
Malfunction within VFD Power Module.  
Call Carrier Service.  
Check main circuit breaker for trip. Increase  
Current % Imbalance in VFD_CONF screen.  
FAULT  
Check VFD Status.  
PROTECTIVE LIMIT INVERTER POWER FAULT 201Inverter Power Fault:  
Check VFD Status.  
PROTECTIVE LIMIT MOTOR AMPS NOT  
202Motor Amps Not  
Sensed — Average Load  
Current [VALUE].  
SENSED  
203  
FAILURE TO START MOTOR ACCELERATION 203Motor Acceleration Fault Check that inlet guide vanes are fully closed at  
FAULT  
— Average Load Current  
[VALUE].  
start-up.  
Check Motor Rated Load Amps in VFD_CONF  
screen. Reduce unit pressure if possible.  
204  
205  
FAILURE TO STOP VFD SHUTDOWN FAULT 204VFD Shutdown Fault:  
VFD Circuit Board malfunction.  
Call Carrier Service.  
Verify phase to phase and phase to ground line  
voltage. Monitor AC line for high transient volt-  
age conditions. VFD Circuit Board malfunction.  
Call Carrier Service.  
Check Inverter Power Unit.  
PROTECTIVE LIMIT HIGH DC BUS VOLTAGE  
205High DC Bus Voltage:  
[VALUE] exceeded limit of  
[LIMIT]*.  
206  
207  
PROTECTIVE LIMIT VFD FAULT  
206VFD Fault Code:  
[VALUE]; Check VFD Fault  
Code List.  
See VFD Fault Code description and corrective  
action.  
PROTECTIVE LIMIT HIGH CONDENSER  
207High Cond Pressure  
Check Compressor Discharge High Pressure  
PRESSURE  
trip. [VALUE] exceeded Switch switch wiring and accuracy.  
Trippoint.  
Check for high condenser water temperatures,  
low water flow, fouled tubes.  
Check for division plate/gasket bypass.  
Check for noncondensables in refrigerant.  
208  
PROTECTIVE LIMIT EXCESSIVE MOTOR  
208Percent Load Current  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check Motor Rated Load Amps in VFD_CONF  
screen. Percent Load Current > 110%.  
Check Motor Rated Load Amps setting.  
AMPS  
209  
PROTECTIVE LIMIT LINE CURRENT  
209Line Current Imbal-  
ance: Check VFD Fault His-  
tory for Values.  
Check phase to phase and phase to ground  
power distribution bus voltage.  
Check Line Current % Imbalance in VFD_CONF  
screen. Consult power company.  
IMBALANCE  
210  
211  
212  
213  
PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210Single Cycle Line Volt- Temporary loss of voltage. Disable Single Cycle  
age Dropout. Dropout in VFD_CONF screen.  
PROTECTIVE LIMIT HIGH LINE VOLTAGE  
PROTECTIVE LIMIT LOW LINE VOLTAGE  
PROTECTIVE LIMIT VFD MODULE RESET  
211High Percent Line Volt- Check phase to phase and phase to ground dis-  
age [VALUE]. tribution bus voltage. Consult power company.  
212Low Percent Line Volt- Check phase to phase and phase to ground dis-  
age [VALUE]. tribution bus voltage. Consult power company.  
213VFD Module Power-On Temporary loss of VFD control voltage. Check  
Reset When Running.  
VFD control power breaker, transformer and  
fuses.  
214  
PROTECTIVE LIMIT POWER LOSS  
214Control Power Loss  
When Running.  
Check phase to phase and phase to ground dis-  
tribution bus voltage.  
Check VFD fuses.  
Check 24 vac power supply to ICVC.  
Consult power company.  
215  
216  
217  
PROTECTIVE LIMIT LOW DC BUS VOLTAGE  
215Low DC Bus Voltage:  
[VALUE] exceeded limit of  
[LIMIT]*.  
216Line Voltage Imbal-  
ance. Check VFD Fault His-  
tory for Values.  
Verify phase-to-phase and phase-to-ground line  
voltage. VFD Circuit Board malfunction.  
Call Carrier Service.  
Check phase-to-phase and phase-to-ground  
distribution bus voltage. Increase Line Voltage  
% Imbalance in VFD_CONF screen.  
Any phase current > 106% Rated Load Amps.  
Can result from significant load side current  
imbalance when running at full load.  
Check entering condenser water temperature  
and water flow rate.  
Check Motor Rated Load Amps in VFD_CONF  
screen.  
PROTECTIVE LIMIT LINE VOLTAGE  
IMBALANCE  
PROTECTIVE LIMIT MOTOR OVERLOAD TRIP 217Motor Overload Trip;  
Check VFD configurations.  
218  
PROTECTIVE LIMIT VFD RECTIFIER  
218VFD Rectifier Temp  
Check that VFD refrigerant isolation valves are  
OVERTEMP  
Exceeded: Check Cooling and open.  
VFD Config.  
Check VFD refrigerant cooling solenoid and  
refrigerant strainer.  
Check for proper VFD cooling fan operation and  
blockage.  
219  
PROTECTIVE LIMIT VFD INVERTER  
219VFD Inverter Temp  
Check that VFD refrigerant isolation valves are  
OVERTEMP  
Exceeded: Check Cooling and open.  
VFD Config.  
Check VFD refrigerant cooling solenoid and  
refrigerant strainer.  
Check for proper VFD cooling fan operation and  
blockage.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
NOTE: ICVC Alarms 212-226 are declared as a result of VFD Faults.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — ICVC Alarm Codes (cont)  
CHILLER PROTECTIVE LIMIT FAULTS (cont)  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
220  
PROTECTIVE LIMIT GROUND FAULT  
220Ground Fault Trip;  
Check Motor and Current  
Sensors.  
Check for condensation on motor terminals.  
Check motor power leads for phase to phase or  
phase to ground shorts. Disconnect motor from  
VFD and megger motor.  
Call Carrier Service.  
221  
222  
PROTECTIVE LIMIT UNUSED  
PROTECTIVE LIMIT LINE FREQUENCY TRIP 222Line Frequency —  
221UNUSED  
If operating from a generator, check generator  
size and speed.  
[VALUE] exceeded limit of  
[LIMIT]; Check Power Supply. Check utility power supply.  
223  
224  
LOSS OF  
WITH VFD GATEWAY  
223Loss of SIO Comm with Check VFD communication wiring and  
COMMUNICATION MODULE  
VFD Gateway: Check VFG  
Module and Power.  
connectors on VFD Gateway and DPI board.  
Check for compatibility between ICVC and  
Gateway software.  
PROTECTIVE LIMIT VFD COMMUNICATIONS 224Loss of DPI Comm with Check VFD communication wiring and  
FAULT  
VFD Gateway: Check VFG to connectors.  
VFD Comm.  
Check status lights on DPI Communications  
Interface Board.  
Call Carrier Service.  
225  
PROTECTIVE LIMIT MOTOR CURRENT  
225Motor Current Imbal-  
ance: Check VFD Fault  
History for Values.  
Check Motor Current % Imbalance in  
VFD_CONF screen.  
IMBALANCE  
226  
227  
PROTECTIVE LIMIT LINE PHASE REVERSAL 226Line Phase Reversal:  
Reverse connections of any two line conductors  
to circuit breaker.  
Check Line Phases.  
PROTECTIVE LIMIT OIL PRESS SENSOR  
227Oil Pressure Delta P  
[VALUE] (Pump Off): Check  
Pump/Transducers.  
Check transducer wiring and accuracy.  
Check power supply to pump.  
Check pump operation.  
FAULT  
Check transducer calibration.  
228  
PROTECTIVE LIMIT LOW OIL PRESSURE  
228Low Operating Oil  
Check transducer wiring and accuracy.  
Pressure [VALUE]: Check Oil Check power supply to pump.  
Pump and Filter.  
Check pump operation.  
Check oil level.  
Check for partially closed service valves.  
Check oil filters.  
Check for foaming oil at start-up.  
Check transducer calibration.  
229  
PROTECTIVE LIMIT LOW CHILLED WATER  
229Low Chilled Water Flow; Perform pump control test.  
FLOW  
Check Switch/Delta P Config Check optional transducer calibration and  
& Calibration.  
wiring.  
Check Evaporator Refrigerant Temperature  
sensor.  
Check chilled water valves.  
Check for evaporator saturation temperature  
< 34 F if not in Pumpdown Lockout mode. Place  
unit in Pumpdown mode before removing  
charge.  
230  
231  
PROTECTIVE LIMIT LOW CONDENSER  
230Low Condenser Water Perform pump control test.  
WATER FLOW  
Flow; Check Switch/Delta P  
Config & Calibration.  
Check optional transducer calibration and  
wiring.  
Check condenser water valves.  
Check for COND PRESS OVERRIDE + 5 psig.  
PROTECTIVE LIMIT HIGH DISCHARGE TEMP 231Comp Discharge Temp Check for closed compressor discharge isola-  
[VALUE] Exceeded Limit of  
[LIMIT]*.  
tion valve.  
Check if chiller was operating in surge.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check for proper condenser flow and  
temperature.  
Check compressor discharge isolation valve.  
Check for proper inlet guide vane and optional  
diffuser actuator operation.  
232  
PROTECTIVE LIMIT LOW REFRIGERANT  
232Evaporator Refrig Temp Check for proper refrigerant charge.  
TEMP  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check float valve operation.  
Check for closed condenser liquid line isolation  
valve. If problem occurs at high load, check for  
low condenser pressure which causes inade-  
quate flasc orifice differential pressure.  
Check for proper water flow and temperature.  
Confirm that condenser water enters bottom row  
of condenser tubes first.  
Check Evaporator Refrigerant Temperature  
sensor.  
Check for division plate gasket bypass.  
Check for fouled tubes.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — ICVC Alarm Codes (cont)  
CHILLER PROTECTIVE LIMIT FAULTS (cont)  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
233  
PROTECTIVE LIMIT HIGH MOTOR  
233Comp Motor Winding Check motor sensors wiring and accuracy.  
TEMPERATURE  
Temp [VALUE] exceeded  
limit of [LIMIT]*.  
Check motor cooling line and spray nozzle for  
proper operation, or restrictions.  
Check for excessive starts within a short time  
span.  
234  
PROTECTIVE LIMIT HIGH BEARING  
234Comp Thrust Brg Temp Check oil heater for proper operation.  
TEMPERATURE  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check for low oil level, partially closed oil supply  
valves, or clogged oil filter.  
Check oil cooler refrigerant thermal expansion  
valves.  
Confirm that TXV (thermostatic expansion valve)  
bulb is secured in place and insulated.  
Check for sensor wiring and accuracy.  
This fault can result from extended operation at low  
load with low water flow to the evaporator or  
condenser.  
235  
236  
PROTECTIVE LIMIT HIGH CONDENSER  
235Condenser Pressure  
[VALUE] exceeded limit of  
[LIMIT]*.  
Check for high condenser water temperatures, low  
water flow, fouled tubes.  
PRESSURE  
Check for division plate/gasket bypass.  
Check for noncondensables.  
Check transducer wiring and accuracy.  
Check for high condenser water temperatures, low  
PROTECTIVE LIMIT COMPRESS SURGE/  
236Compressor Surge:  
LOW SPEED  
Check condenser water temp water flow, fouled tubes.  
and flow.  
Check for division plate/gasket bypass.  
Check for noncondensables.  
Check surge prevention parameters in OPTIONS  
screen. Increase VFD Increase Step in SETUP2.  
Check VFD Minimum Speed in SETUP2 screen.  
237  
PROTECTIVE LIMIT SPARE SAFETY  
237Spare Safety Device.  
238Compressor Surge:  
Spare safety input has tripped or factory installed  
jumper is not present on Terminal Block 4 terminals  
17 and 20 in the VFD enclosure.  
DEVICE  
238  
PROTECTIVE LIMIT EXCESSIVE COMPR  
Check for high condenser water temperatures, low  
SURGE  
Check condenser water temp water flow, fouled tubes.  
and flow.  
Check for division plate/gasket bypass.  
Check for noncondensables.  
Check surge prevention parameters in OPTIONS  
screen.  
Check cooling tower control settings and perfor-  
mance to design/selection temperatures across the  
entire operating range of the chiller.  
Check cooler approach and water flow.  
239  
240  
PROTECTIVE LIMIT TRANSDUCER  
239Transducer Voltage Ref Check that CCM transducer voltage reference is  
VOLTAGE FAULT  
[VALUE] exceeded limit of  
[LIMIT]*.  
between 4.5 v and 5.5 v.  
Check that pressure transducers are not shorted to  
ground. This fault is normally declared the first time  
an ICVC is powered up if it was downloaded with  
software when it was not connected to a CCM.  
Call Carrier Service.  
PROTECTIVE LIMIT LOW DISCHARGE  
240Check for Oil in Or  
Overcharge of Refrigerant.  
Check for oil loss or excessive refrigerant. If oil level  
is low, refrigerant charge may be too low resulting in  
ineffective oil reclaim. Excessive refrigerant charge  
may cause liquid carryover into compressor.  
Check calibration of evaporator pressure and con-  
denser pressure sensors.  
SUPERHEAT  
Check calibration of compressor discharge temper-  
ature sensor.  
241  
242  
PROTECTIVE LIMIT RECTIFIER  
241Rectifier Overcurrent  
Check for high water temperatures or changes in  
water flow rates.  
Check wiring and control power to CCM.  
Confirm that all CCM SW1 switches are in the  
“OFF” position.  
OVERCURRENT  
Fault: Check VFD Status.  
LOSS OF  
WITH CCM MODULE  
242Loss of Communica-  
tion With CCM, Check  
Comm. Connectors.  
COMMUNICATION  
243  
POTENTIAL  
FREEZE-UP  
EVAP PRESS/TEMP  
TOO LOW  
243Evaporator Refrig  
Temp [VALUE] exceeded  
limit of [LIMIT]*.  
Check for proper refrigerant charge.  
Check float valve operation.  
Check for proper fluid flow and temperature.  
Confirm that condenser water enters bottom row  
of condenser tubes first.  
Check Evaporator Refrigerant Temperature  
sensor.  
Check for division plate gasket bypass.  
Check for fouled tubes.  
244  
POTENTIAL  
FREEZE-UP  
COND PRESS/TEMP  
TOO LOW  
244Condenser Refrig  
Temp [VALUE] exceeded  
limit of [LIMIT]*.  
Condenser water too cold or chiller shut down with  
brine below 32 F in cooler so equalization tempera-  
ture in chiller approached 32 F.  
Check condenser pressure transducer.  
Check refrigerant charge.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — ICVC Alarm Codes (cont)  
CHILLER PROTECTIVE LIMIT FAULTS (cont)  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
245  
246  
247  
PROTECTIVE LIMIT HIGH VFD SPEED  
245Actual VFD Speed  
Actual VFD Speed on COMPRESS screen must  
exceeded limit of Target VFD not exceed Target VFD Speed by more than  
Speed + 10%.  
10%.  
PROTECTIVE LIMIT INVALID DIFFUSER  
246Diffuser Control Invalid Check 25%, 50%, and 75% Guide Vane and Dif-  
Configuration: Check SETUP2 fuser Load Point entries in SETUP2 screen.  
Entries.  
247Diffuser Position Fault: Confirm that Diffuser Option in SETUP 2 screen  
Check Guide Vane/Diffuser  
Actuator.  
CONFIG.  
PROTECTIVE LIMIT DIFFUSER POSITION  
FAULT  
has not been Enabled if compressor does not  
have a split ring diffuser. May indicate rotating  
stall condition.  
Check rotating stall transducer wiring accuracy  
and sealing.  
Check diffuser schedule and guide vane sched-  
ule in SETUP2 screen.  
Check for proper operation of diffuser and inlet  
guide vane actuators including inlet guide vane  
calibration.  
Check diffuser actuator coupling for rotational  
slip.  
Check RC snubber on CCM J4-23 and J4-24.  
Check 4.3k ohm resistor between CCM termi-  
nals J3-7 and J3-8.  
Check for electrical noise in CCM Diffuser Pres-  
sure wiring. Do not continue to operate com-  
pressor except for diagnostic purposes.  
248  
PROTECTIVE LIMIT SPARE TEMPERATURE  
248Spare Temperature #1 Check Spare Temperature Enable and Spare  
#1  
[VALUE] exceeded limit of  
[LIMIT]*.  
Temperature Limit in SETUP1 Screen.  
249  
PROTECTIVE LIMIT SPARE TEMPERATURE  
249Spare Temperature #2 Check Spare Temperature Enable and Spare  
#2  
[VALUE] exceeded limit of  
[LIMIT]*.  
Temperature Limit in SETUP1 Screen.  
250  
251  
UNUSED  
UNUSED  
250Unused State.  
PROTECTIVE LIMIT VFD CONFIG CONFLICT 251VFD Config Conflict  
The VFD_CONF table in the Gateway does not  
match that which is in the ICVC. This is a normal  
fault if an ICVC has been uploaded with soft-  
ware when it was not attached to the CCM.  
Enter VFD_CONF screen and then exit  
(VFD Uploaded): Verify to  
Reset Alarm.  
VFD_CONF screen by pressing EXIT then  
CANCEL. Re-enter the VFD_CONF screen,  
press EXIT then SAVE. Parameters stored in  
the Gateway will be uploaded into the ICVC.  
Confirm valid settings in VFD_CONF screen.  
252  
253  
PROTECTIVE LIMIT VFD CONFIG CONFLICT 252VFD Config Conflict  
The VFD_CONF table in the Gateway does not  
(VFD Downloaded): Verify to match that which is in the ICVC.  
Reset Alarm.  
PROTECTIVE LIMIT GUIDE VANE  
253Guide Vane Fault  
[VALUE]. Check Calibration.  
Enter CONTROL TEST and execute Guide  
Vane Calibration.  
Check CCM guide vane feedback terminals J4-9  
and J4-10.  
CALIBRATION  
Check guide vane feedback potentiometer.  
Alarm before start indicates guide vane opening  
is not less than 4%. Alarm running indicates  
guide vane position is < -1% or > 103%, or feed-  
back voltage is < .045 or > 3.15 VDC.  
254  
255  
PROTECTIVE LIMIT VFD CHECKSUM ERROR 254Checksum Error:  
Actual VFD checksum does not match calcu-  
lated value.  
Press Reset to Restore  
Configuration  
PROTECTIVE LIMIT VFD DEW PREVENTION 255Dew Prevention - Cool- VFD COLDPLATE TEMP is too close to dew  
ant Too Cold. Check Solenoid point based on VFD ENCLOSURE TEMP and  
& Cond T.  
RELATIVE HUMIDITY in POWER screen.  
Check for moisture in VFD enclosure.  
Check Humidity Sensor in CONTROLS TEST.  
Check for contamination on CCM J3-7 and J3-9  
Humidity Sensor.  
Check that VFD refrigerant cooling modulating  
valve is closing.  
256  
257  
PROTECTIVE LIMIT INDUCTOR OVERTEMP  
PROTECTIVE LIMIT VFD START INHIBIT  
256Inductor Overtemp Trip - Check for cooling fan air flow obstructions.  
Check Temp Switch and Cool-  
ing Fans.  
257VFD Start Inhibit: Check The VFD Start Inhibit is derived from the Alarm  
VFD Diagnostic Parameters  
212/214.  
bit being set in the VFD. The conditions causing  
the alarm must be corrected in the VFD to  
enable subsequent starts and operation. See  
VFD parameters 212/214.  
258  
UNUSED STATE  
UNUSED  
258Unused.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — ICVC Alarm Codes (cont)  
CHILLER PROTECTIVE LIMIT FAULTS (cont)  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
259  
PROTECTIVE LIMIT CCN OVERRIDE STOP  
259CCN Emergency/  
Override Stop.  
CCN has signaled the chiller to stop.This fault  
must be manually reset from the default screen  
of the ICVC.  
282  
PROTECTIVE LIMIT INVALID VFD CONFIG  
282Line Frequency  
LINE FREQUENCY in POWER screen must be  
[VALUE] Exceeded Configura- maintained between 45-52 Hz if LINE  
tion Range.  
FREQ=60Hz? is set to NO(50 Hz). LINE FRE-  
QUENCY must be maintained between  
55-62 Hz if LINE FREQ=60Hz? is set to YES  
(60 Hz).  
Check high pressure switch and connections to  
TB4-24 and TB4-25.  
283  
PROTECTIVE LIMIT INVALID VFD CONFIG  
283Compressor 100%  
COMPRESSOR 100% SPEED in VFD_CONF  
Speed Config Ranges: 50=Hz screen must be set between 45-52 Hz if LINE  
45-52; 60 Hz=55-62.  
FREQ=60Hz? is set to NO(50 Hz). COMPRES-  
SOR 100% SPEED must be set between  
55-62 Hz if LINE FREQ=60Hz? is set to YES  
(60 Hz).  
284  
285  
286  
VFD GATEWAY  
VFD GATEWAY  
COMPATIBILITY  
CONFLICT  
284VFD Gateway Compati- VFD Gateway and VFD software versions are  
bility Conflict: Check VFG/  
VFD Versions.  
not compatible.  
Call Carrier Service.  
COMPATIBILITY  
CONFLICT  
285VFD Gateway Compati- VFD Gateway and ICVC software versions are  
bility Conflict: Check VFG/  
ICVC Versions.  
not compatible.  
Call Carrier Service.  
PROTECTIVE LIMIT INVERTER  
OVERCURRENT  
286Inverter Overcurrent  
Fault: Check VFD Status.  
Check for high entering water temperature or  
low condenser water flow.  
Check current settings in VFD_CONF screen.  
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or  
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.  
OUT-OF-RANGE SENSOR  
ICVC FAULT  
STATE  
PRIMARY  
MESSAGE  
SECONDARY  
MESSAGE  
PRIMARY CAUSE  
ADDITIONAL CAUSE/REMEDY  
260  
261  
262  
SENSOR FAULT LEAVING CHILLED WATER 260Sensor Fault: Check  
Check sensor resistance or voltage drop.  
Leaving Chilled Water Sensor. Check for proper wiring.  
Check for disconnected or shorted wiring.  
SENSOR FAULT ENTERING CHILLED  
261Sensor Fault: Check  
Entering Chilled Water  
Sensor.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check for disconnected or shorted wiring.  
WATER  
SENSOR FAULT CONDENSER PRESSURE 262Sensor Fault: Check  
Check sensor wiring.  
Condenser Pressure Sensor.  
Check for disconnected or shorted wiring.  
Check for condensation in transducer  
connector.  
263  
SENSOR FAULT EVAPORATOR  
263Sensor Fault: Check  
Evaporator Pressure Sensor.  
Check sensor wiring.  
PRESSURE  
Check for disconnected or shorted wiring.  
Check for condensation in transducer  
connector.  
264  
265  
266  
267  
268  
269  
SENSOR FAULT COMPRESSOR BEARING 264Sensor Fault: Check  
Check sensor resistance or voltage drop.  
TEMP  
Comp Thrust Brg Temp Sensor. Check for proper wiring.  
Check for disconnected or shorted wiring.  
SENSOR FAULT COMPRESSOR MOTOR  
265Sensor Fault: Check  
Comp Motor Winding Temp  
Sensor.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check for disconnected or shorted wiring.  
TEMP  
SENSOR FAULT COMP DISCHARGE TEMP 266Sensor Fault: Check  
Check sensor resistance or voltage drop.  
Comp Discharge Temp Sensor. Check for proper wiring.  
Check for disconnected or shorted wiring.  
SENSOR FAULT OIL SUMP TEMP  
267Sensor Fault: Check Oil  
Sump Temp Sensor.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check for disconnected or shorted wiring.  
Check sensor resistance or voltage drop.  
Check for proper wiring.  
Check for disconnected or shorted wiring.  
SENSOR FAULT COMP OIL PRESS DIFF  
SENSOR FAULT CHILLED WATER FLOW  
268Sensor Fault: Check Oil  
Pump Delta P Sensor.  
269Sensor Fault: Check  
Chilled Water Delta P Sensor.  
Check sensor wiring and accuracy.  
Check for disconnected or shorted wiring.  
If pressure transducers are not installed,  
check for presence of resistors and jumpers  
on lower CCM terminal block J3.  
270  
271  
SENSOR FAULT COND WATER FLOW  
270Sensor Fault: Check  
Check sensor wiring and accuracy.  
Cond Water Delta P Sensor.  
Check for disconnected or shorted wiring.  
If pressure transducers are not installed,  
check for presence of resistors and jumpers  
on lower CCM terminal block J3.  
SENSOR FAULT EVAP SATURATION TEMP 271Sensor Fault: Check  
Check sensor resistance or voltage drop.  
Evap Saturation Temp Sensor. Check for proper wiring.  
Check for disconnected or shorted wiring.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 Powerflex 755 Fault Code Descriptions and Corrective Actions  
VFD  
FAULT  
CODE  
ICVC  
FAULT  
STATE  
FAULT TYPE  
DESCRIPTION  
CORRECTIVE ACTION  
ON VFD  
HIST  
SCREEN  
NONE  
0
206  
Processor memory fault  
Consult VFD manual to resolve generic fault.  
No Entry  
Check Compressor Discharge High Pressure  
switch wiring and accuracy.  
Check for high condenser water temperatures,  
low water flow, fouled tubes.  
Check for division plate/gasket bypass. Check for  
noncondensables in refrigerant.  
2
207  
Auxiliary Input  
Input is open.  
Temporary loss of voltage. Disable Single Cycle  
Dropout in VFD_CONF sceen.  
Verify phase-to-phase and phase-to-ground line  
voltage. VFD Circuit Board malfunction.  
Call Carrier Service.  
3
4
210  
215  
Power Loss  
Line voltage dropout  
Low DC bus voltage  
Undervoltage  
Verify phase to phase and phase to ground line  
voltage. Monitor AC line for high transient voltage  
conditions.  
5
7
166  
217  
Overvoltage  
High DC bus voltage  
Any phase current > 106% RLA. Can result from  
significant load side current imbalance when  
running at full load.  
Motor Overload  
An internal electronic overload trip has occurred. Check entering condenser water temperature  
and water flow rate.  
Check Motor Rated Load Amps in VFD_CONF  
screen.  
Check that VFD refrigerant isolation valves are  
open.  
Heat Sink Over-  
temp  
Heat sink temperature has exceeded the maxi-  
mum operating temperature  
Check VFD refrigerant cooling orifice and refrig-  
erant strainer.  
8
219  
Check for proper VFD cooling fan operation and  
air flow blockage.  
Check that VFD refrigerant isolation valves are  
open.  
Transistor Over-  
temp  
The output transistors have exceeded the maxi-  
mum operating temperature  
Check VFD refrigerant cooling orifice and refrig-  
erant strainer.  
9
219  
Check for proper VFD cooling fan operation and  
air flow blockage.  
Check for high entering water temperature or low  
condenser water flow. Check current settings in  
VFD_CONF screen.  
The drive output current has exceeded the hard-  
ware current limit.  
12  
286  
HW Overcurrent  
Check the motor, motor terminals, and external  
wiring to the drive output terminals for a  
grounded condition.  
A current path to earth ground greater than 25%  
13  
14  
220  
206  
Ground Fault  
of drive rating has occurred.  
The ground current has exceeded the level set in  
P467  
Ground Warning  
To reset the processor, cycle power to chiller,  
If this fault appears, there may be a problem with check ICVC VFD_CONF settings and save set-  
15  
206  
Load Loss  
software configuration.  
Line Voltage imbalance  
tings when exiting VFD_CONF screen.  
Check VFD parameters with Drive Explorer.  
The DC bus ripple  
has exceeded a  
preset level.  
Check phase-to-phase and phase-to-ground dis-  
tribution bus voltage. Increase Line Voltage %  
Imbalance in VFD_CONF screen.  
17  
216  
20  
21  
206  
225  
TorqPrv Spd Band See VFD Fault Code 15  
See VFD Fault Code 15  
The current in one or more phases has been lost Check Motor Current % Imbalance in  
Output PhaseLoss  
or remains below a preset level.  
VFD_CONF screen.  
Verify input voltage is within drive specified limits.  
Verify system ground impedance follows proper  
grounding techniques.  
Disable bus regulation P186 and/or add dynamic  
brake resistor and/or extend deceleration time  
P537 and P538.  
The drive is not following a commanded decelera-  
tion because it is attempting to limit the bus volt-  
age.  
24  
204  
Decel Inhibit  
33  
36  
206  
AuRsts Exhausted See VFD Fault Code 15  
See VFD Fault Code 15  
The drive output current has exceeded the 1 ms Check for excess load, improper DC boost set-  
current rating. ting, DC brake volts set too high.  
286  
SW Overcurrent  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 Powerflex 755 Fault Code Descriptions and Corrective Actions (cont)  
VFD  
FAULT  
CODE  
ICVC  
FAULT  
STATE  
FAULT TYPE  
DESCRIPTION  
CORRECTIVE ACTION  
ON VFD  
HIST  
SCREEN  
38  
39  
40  
41  
42  
43  
Phase U to Gnd  
Phase V to Gnd  
Phase W to Gnd  
Phase UV Short  
Phase VW Short  
Phase WU Short  
Phase UNot  
Check the wiring between the drive and the  
motor.  
220  
246  
GROUND FAULT  
GROUND FAULT  
Check motor for grounded phase.  
Check Motor terminals. d. Replace drive.  
Check the wiring between the drive and the  
motor.  
Check Motor terminals.  
Replace drive.  
44  
45  
46  
206  
206  
206  
Check the wiring between the drive and the  
motor.  
Check Motor terminals.  
Replace drive.  
Phase VNot ToGnd  
Phase WNot  
GROUND FAULT (no LF2 equivalent)  
The temperature sensor on the main control  
board detected excessive heat.  
Check that VFD refrigerant isolation valves are  
open.Check VFD refrigerant strainer  
55  
NONE Inverter Overtemp  
61  
62  
206  
206  
Shear Pin 1  
Shear Pin 2  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
Check for high entering water temperature or low  
condenser water flow. Check current settings in  
VFD_CONF screen.  
64  
206  
Drive Overload  
Drive is overloaded  
65  
77  
206  
206  
OW TrqLvlTimeout See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
IR Volts Range  
See VFD Fault Code 15  
FluxAmpsRef  
Rang  
78  
206  
See VFD Fault Code 15  
See VFD Fault Code 15  
Check that guide vanes are closed completely.  
Check for high entering water temperature or low  
condenser flow.  
Motor did not come up to speed in the allotted  
time  
79  
206  
Excessive Load  
Repeat Autotune  
80  
87  
206  
206  
AutoTune Aborted See VFD Fault Code 15  
See VFD Fault Code 15  
Ixo voltae calculated from motor nameplate data Re-enter motor nameplate data in VFD_CONF  
IXo VoltageRange  
Pri VelFdbk Loss  
is too high.  
screen.  
91  
93  
94  
95  
96  
97  
206  
206  
206  
206  
206  
206  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
HW Enable Check See VFD Fault Code 15  
Alt VelFdbk Loss See VFD Fault Code 15  
Aux VelFdbk Loss See VFD Fault Code 15  
PositionFdbkLoss See VFD Fault Code 15  
Auto Tach Switch  
See VFD Fault Code 15  
Press ICVC reset.  
Check VFD_CONF parameters.  
Cycle power to the drive.  
The checksum read from the board does not  
match the checksum calculated.  
100  
206  
Parameter Chksum  
Press ICVC reset.  
The main control board was moved to a different  
power structure. Data set to default values.  
107  
113  
NONE Replaced MCB-PB  
Check VFD_CONF parameters.  
Cycle power to the drive.  
Press ICVC reset.  
Cycle power to the drive  
206  
Tracking DataErr  
Internal data error.  
124  
141  
142  
143  
144  
145  
206  
206  
206  
206  
206  
206  
App ID Changed  
Autn Enc Angle  
Autn Spd Rstrct  
Autotune CurReg  
Autotune Inertia  
Autotune Travel  
Application firmware changed.  
P78 [Encdrlss AngComp] is out of range  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
Verify application version.  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 Powerflex 755 Fault Code Descriptions and Corrective Actions (cont)  
VFD  
FAULT  
CODE  
ICVC  
FAULT  
STATE  
FAULT TYPE  
DESCRIPTION  
CORRECTIVE ACTION  
ON VFD  
HIST  
SCREEN  
Heatsink temperature sensor is reporting a value  
below -18.7 C (-1.66 F) or the sensor feedback  
circuit is open.  
HeatSinkUnder-  
Tmp  
Check heat sink temperature sensor. Check heat  
sink temperature.  
168  
206  
206  
HW En Jumper  
Out  
210  
See VFD Fault Code 15  
See VFD Fault Code 15  
211  
213  
291  
292  
293  
294  
295  
296  
315  
316  
206  
206  
206  
206  
206  
206  
206  
206  
206  
206  
Safety Brd Fault  
Safety Jumper In  
HSFan Lifwe  
InFan Life  
MtrBrg Life  
MtrBrg Lube  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
See VFD Fault Code 15  
MachBrg life  
MachBrg Lube  
Excess Psn Error  
Node Fault Error  
Table 7 Diode Checks  
METER LEAD  
METER READING  
(-)  
Checking Power Modules and Motor Input  
with Input Power Off — Use the following procedure  
to check the drive’s power module circuitry with power off:  
1. Turn off and lock out input power. Wait five minutes.  
2. Verify there is no voltage at the drive’s input power termi-  
nals.  
3. Using a voltmeter, check the DC bus potential as de-  
scribed above to ensure the DC bus capacitors are dis-  
charged.  
4. Disconnect the motor from the drive.  
5. Check all AC line and DC bus fuses.  
6. Use a multimeter to check the input diodes and output  
IGBTs if a fuse is open.  
7. Check motor impedance.  
(+)  
R
S
T
R
S
T
U
V
W
U
V
W
DC+  
DC+  
DC+  
DC-  
DC-  
DC-  
DC+  
DC+  
DC+  
DC-  
DC-  
DC-  
DC+  
DC+  
DC+  
DC-  
DC-  
DC-  
DC+  
DC+  
DC+  
DC-  
DC-  
DC-  
R
S
T
R
S
T
U
V
W
0.5 V  
0.5 V  
0.5 V  
infinite (OL)  
Infinite (OL)  
Infinite (OL)  
0.5 V  
0.5 V  
0.5 V  
infinite (OL)  
Infinite (OL)  
Infinite (OL)  
Infinite (OL)  
Infinite (OL)  
Infinite (OL)  
0.5 V  
0.5 V  
0.5 V  
Infinite (OL)  
Infinite (OL)  
Infinite (OL)  
0.5 V  
8. Reconnect the motor to the drive.  
9. Reapply input power. See Tables 7 and 8.  
WARNING  
Confirm that the DC bus has discharged before performing  
diode checks.  
U
V
W
0.5 V  
0.5 V  
NOTE: Digital meters require a special diode check function  
because the current sourced by the meter during a normal resis-  
tance (Ohms) test is too low to accurately test a diode. Make sure  
the meter is set to the diode test function. Voltage readings may not  
be exact as shown in above tables, but look for consistency during  
each of the 4 tests. When performing a test that should return infinity  
(OL) as shown in above tables, you may see a value slowly climbing  
toward infinity. This is a result of the meter charging a capacitor and  
is normal.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Servicing the Drive  
L1 L2 L3  
I
1
2
WARNING  
LOCKOUT/TAGOUT  
To guard against possible personal injury and/or equipment  
damage:  
1. Inspect all lifting hardware for proper attachment be-  
fore lifting drive.  
2. Do not allow any part of the drive or lifting mecha-  
nism to make contact with electrically charged con-  
ductors or components.  
3. Do not subject the drive to high rates of acceleration  
or deceleration while transporting to the mounting lo-  
cation or when lifting.  
O
0V  
DC+ DC–  
DC BUS TEST  
TERMINALS  
MULTIMETER  
0V  
LOCATED INSIDE  
ACCESS DOOR  
Do not allow personnel or their limbs directly underneath  
the drive when it is being lifted and mounted.  
Fig. 17 — Check DC Bus Terminals  
A19-1814  
WARNING  
DC bus capacitors retain hazardous voltages after input  
power has been disconnected. After disconnecting input  
power, wait five (5) minutes for the DC bus capacitors to  
discharge and then check the voltage with a voltmeter to  
ensure the DC bus capacitors are discharged before touch-  
ing any internal components. Failure to observe this pre-  
caution could result in severe bodily injury or loss of life.  
SLIDE  
ENCLOSURE  
FORWARD  
LOOSEN  
ENCLOSURE  
FASTENERS  
1. Using recommended screwdriver = 6.4 mm (0.25 in.) flat  
or T20 star, open access door. See Fig. 16.  
2. Check to be sure that the voltage between DC+ and DC-  
and from each DC terminal to the chassis is zero before  
proceeding. See Fig. 17.  
90°  
A19-1816  
Fig. 18 — Removing Enclosure  
When replacing the drive, reverse the procedures and tight-  
en to the torques for the Frames 6 and 7 Power Terminal Block  
referred to in Table 8.  
3. Remove the enclosure. See Fig. 18.  
REMOVING THE DRIVE — The dimensions and weights  
specified must be taken into consideration when removing the  
drive. All lifting equipment and lifting components (hooks,  
bolts, lifts, slings, chains, etc.) must be properly sized and rated  
to safely lift and hold the weight of the drive while removing it.  
See Fig. 19. The drive weights are as follows:  
Table 8 Frames 6 and 7 Power Terminal Block  
MAXIMUM LUG  
WIDTH  
RECOMMENDED  
TORQUE  
TERMINAL  
BOLT SIZE  
FRAME  
6
7
34.6 mm (1.36 in.) 11.3 N·m (100 in.-lb)  
43.5 mm (1.71 in.) 11.3 N·m (100 in.-lb)  
M8 x 1.25  
M8 x 1.25  
• Drive weight for Frame 6: 85 lb.  
• Drive weight for Frame 7: 160 - 249 lb.  
RIGGING THE ENCLOSURE — Where overhead room  
and/or clearance in front of the drive enclosure is insufficient to  
allow the drive to be safely removed from the enclosure, the  
entire enclosure may have to be removed from the chiller.  
The dimensions and weights specified must be taken into  
consideration when removing the enclosure. The total weight  
for Frames 6 and 7, including drive weight and enclosure, is  
720 lb. All lifting equipment and lifting components (hooks,  
bolts, lifts, slings, chains, etc.) must be properly sized and rated  
to safely lift and hold the weight of the enclosure and drive  
while removing. See Fig. 20A and Fig. 20B.  
Fig. 16 — Open Access Door  
A19-1831  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DRIVE RIGGING ACCESS  
DRIVE WIDTH + 4 IN.  
<45°  
1
/
>
2 A  
A
Fig. 20A — Rigging the Enclosure, Frame 6  
A19-1837  
<45°  
1
/
>
2 A  
A
FRONT VIEW  
Fig. 20B — Rigging the Enclosure, Frame 7  
2 IN.  
DRIVE RIGGING  
2 IN.  
A19-1838  
ACCESS  
REPLACING THE GATEWAY (A-B20-750-20COMM  
OPTION CARD) — The following are the steps for remov-  
ing and replacing the existing gateway.  
1. Disconnect power to the drive. Before removing the en-  
closure, open the access door on the front of the drive.  
See Fig. 16.  
DRIVE POSITIONED FOR  
VERTICAL LIFT  
2. Check to be sure that the voltage between DC+ and DC-  
and from each DC terminal to the chassis is zero before  
proceeding. See Fig. 17.  
3. Remove the enclosure. See Fig. 18.  
4. Remove the 2 screws securing the mounting plate and re-  
move the mounting plate and COMM card. See Fig. 21.  
5. Mount the new COMM card and mounting plate and at-  
tach with the 2 screws removed in Step 4. See Fig. 22.  
DRIVE EXTENDS  
BEHIND MAIN  
ENCLOSURE  
6. Use the shorter ribbon cable to connect the plug on the  
COMM card to the connector on the mounting plate. See  
Fig. 21.  
SUPPORT FROM  
BELOW  
7. Install the enclosure. See Fig. 18.  
SIDE VIEW  
Fig. 19 — Enclosure Access for Removing Drive  
a19-1817  
A19-1818  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHILL PLATE FAN AND INTERNAL FAN REPLACE-  
MENT — The following are the steps to replace the chill plate  
fan and internal fan in Frames 6 and 7.  
Frame 6:  
1. Disconnect power to the drive. Before removing the en-  
closure, open the access door on the front of the drive.  
See Fig. 16.  
GATEWAY  
MOUNTING PLATE  
2. Check to be sure that the voltage between DC+ and DC-  
and from each DC terminal to the chassis is zero before  
proceeding. See Fig. 17.  
0.45-0.67 N-m  
(4.0-6.0 lb.-in.)  
3 PLACES  
3. Remove the enclosure. See Fig. 18.  
4. Remove and replace the chill plate fan. See Fig. 23.  
5. Remove and replace the internal fan. See Fig. 24.  
6. Install the enclosure. See Fig. 18.  
RIBBON CABLE  
CHILL PLATE  
FAN POWER  
CONNECTION  
A19-1819  
Fig. 21 — COMM Card  
CHILL PLATE FAN  
MOUNTING PLATE  
GATEWAY  
T20  
2.6 N•m (23 lb•in.)  
Fig. 23 — Chill Plate Fan, Frame 6  
A19-1839  
2.6 N•m  
(23 lb•in.)  
T20  
INTERNAL FAN  
Fig. 22 — Mount COMM Card Plate to Drive  
A19-1820  
T20  
2.6 N•m  
(23 lb•in.)  
A19-1840  
Fig. 24 — Internal Fan, Frame 6  
711  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Frame 7:  
1. Disconnect power to the drive. Before removing the en-  
closure, open the access door on the front of the drive.  
See Fig. 16.  
5.20 N•m  
(46 lb•in.)  
T15  
INTERNAL FANS  
2. Check to be sure that the voltage between DC+ and DC-  
and from each DC terminal to the chassis is zero before  
proceeding. See Fig. 17.  
T15  
2.6 N•m (23 lb•in.)  
3. Remove the enclosure. See Fig. 18.  
4. Remove and replace the Heat Sink and Internal and fans.  
See Fig. 25.  
Install the enclosure. See Fig. 18.  
Part Identification and Location — See Fig. 26-28  
X 2  
for parts descriptions and locations.  
T20  
CHILL PLATE FANS  
2.6 N•m (23 lb•in.)  
Fig. 25 — Chill Plate and Internal Fans, Removal  
and Replacement, Frame 7  
A19-1841  
CR1  
EA1  
6
CR2  
CR3  
CR4  
CR5  
CR6  
CR1  
CR1  
CR2  
CR3  
CR4  
CR5  
CR6  
LINE-  
PE  
CB1  
CR6  
1
TB4  
1
TB4  
2
CABLE  
ACCESS  
CUTOUT  
DIST.  
SIDE  
FU2  
FU1 FU3  
TB1 TB2  
CB2  
1
1
1
TB1,TB2,  
FU1-FU3  
3P  
KTK/FNQ-R  
TB4  
30A  
2
2
2
PT1  
PT1  
SECONDARY  
SIDE  
TOWARD  
DOOR  
3
5
4
SECONDARY SIDE  
LEFT SIDEWALL  
VIEW FROM INSIDE  
FRONT VIEW  
DOOR REMOVED  
80  
LEGEND  
1
2
3
4
5
6
Power Module  
Input Circuit Breaker  
15 Amp Control Circuit Breaker  
Control Transformer  
Control Fuses  
Control Relays (CR1 - CR5)  
a19-1847  
Fig. 26 — Assembly Parts  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
1
2
3
4
5
6
7
PF750 Series, Precharge Kit  
PF750 Series, Gate Interface  
PF750 Series, Power Interface  
PowerFlex 750 Series, Flange Gasket  
PF755 Main Control Board  
PF750 Series, Backplane Interface  
PF750 Series, Type 4X/12 Chill Plate  
(Heatsink) Fan Kit  
a19-1848  
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked  
“J1 ENABLE” must be removed and the jumper marked “J1 SAFETY” must be  
left in place.  
8
Chill Plate Fan  
Fig. 27 — Frame 6 Parts  
LEGEND  
1 — Slot for Gateway (Gateway Not Shown)  
2 — PF750 Series, Backplane Interface  
3 — PF750 Series, Type 4X/12 Heatsink Fan Kit  
4 — PF750 Series, Power Interface  
5 — PF750 Series, Bus Cap Assembly  
6 — PF750 Series, Power Interface Cable  
7 — PF750 Series, Current Transducer Kit  
8 PF750 Series, Precharge Kit  
9 — Slot for 24V I/O Module (24V I/O Module Not Shown)  
10 — PF755 Main Control Board  
NOTE: When replacing the Main Control Board (Item No. 1) the jumper marked “J1 ENABLE” must be  
removed and the jumper marked “J1 SAFETY” must be left in place.  
a19-1849  
Fig. 28 — Frame 7 Parts  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WIRING SCHEMATICS  
CHILLER CONTROL SCHEMATIC  
(SHIELD)  
EXT  
4-20mA  
(1-5vdc)  
(RED)  
AUTO DEMAND LIMIT  
(OPTIONAL)  
(BLK)  
EXT  
4-20mA  
(1-5vdc)  
(CLR)  
AUTO CHILLED WATER  
RESET (OPTIONAL)  
(CLR)  
(BLK)  
(SHIELD)  
4-20mAkw  
6
OUTPUT  
+
-
+
-
+
-
+
-
-
+
-
+
3
2
1
4
3
2
1
6
5
4
3
2
2
1
J5  
J6  
J7  
J8  
(RED)  
1
EVAP ENT  
WATER TEMP  
(BLK)  
(RED)  
2
3
SWITCH POSITION  
O
N
1
3
SW "ON" = EXT 4-20mA  
SW "OFF" = EXT 1-5Vdc  
EVAP LVG  
WATER TEMP  
(BLK)  
(WHT)  
(BLK)  
4
SW2  
(RED)  
1 "OFF"  
2 "ON"  
3 "ON"  
(BLU)  
(ORN)  
5
COND ENT  
WATER TEMP  
(BLK)  
6
(RED)  
7
COND LVG  
WATER TEMP  
(BLK)  
(YEL)  
8
L1  
4
7
(CLR)  
9
G.V. POSITION  
FEEDBACK  
L2  
8
(BLK)  
10  
DIFFUSER ACTUATOR  
10K  
(SHIELD)  
(BLK)  
(WHT)  
(RED)  
(BLK)  
11  
12  
EVAP REFRIG  
LIQUID TEMP  
(SHIELD)  
COMMON  
(CLR)  
(RED)  
(BLK)  
X
3
REMOTE TEMP  
RESET  
(OPTIONAL)  
G.V. INCREASE  
3
(WHT)  
(BLK)  
13  
14  
2
1
G.V. DECREASE  
2
L1  
L2  
15  
16  
17  
18  
19  
20  
GUIDE VANE ACTUATOR  
(RED)  
(BLK)  
(CLR)  
(BLK)  
(SPARE)  
(RED)  
(BLK)  
COMP'R  
DISCH TEMP  
(RED)  
(BLK)  
(CLR)  
(BLK)  
(BRN)  
1
2
3
COMP'R THRUST  
BRG TEMP  
(YEL)  
CB2  
(BLK)  
(BRN)  
(BLU)  
(BLK)  
(WHT)  
(ORN)  
(BLK)  
6
5
4
3
2
1
VFD COOLANT  
SOLENOID  
21  
22  
COMP'R OIL  
SUMP TEMP  
*
(BLK)  
(CLR)  
3
1
3C  
(BRN)  
HGBP (OPTIONAL)  
(WHT)  
1
2
3
(CLR)  
(BLK)  
23  
24  
COMP'R  
MOTOR TEMP  
(BRN)  
C2  
C1  
(SPARE)  
NOISE  
SUPPRESSOR  
2C  
COMP'R OIL PUMP  
(WHT)  
(RED)  
(GRY)  
C2  
C1  
1C  
(BRN)  
(BRN)  
COMP'R OIL HEATER  
(WHT)  
(BLK)  
(WHT)  
(BLK)  
25  
26  
27  
28  
SPARE TEMP #1  
(OPTIONAL)  
(WHT)  
SPARE TEMP #2  
(OPTIONAL)  
(BLK)  
(CLR)  
(RED)  
(BLK)  
(CLR)  
CCM  
1
2
3
4
5
6
7
8
9
-
OIL SUMP  
PRESS  
+
+
100»f  
-
+
OIL PUMP  
DISCH PRESS  
+
NOTE: GND SHIELDS AT THIS END ONLY  
100»f  
(RED)  
(BLK)  
(SHIELD)  
(SHIELD)  
LOAD RESISTOR  
(RED)  
(CLR)  
(BLK)  
+
G
(RED)  
(WHT)  
(BLK)  
-
4.3K  
RELATIVE  
HUMIDITY  
S
RMS  
(RED)  
+
CCN  
(WHT)  
-
10  
11  
12  
SP  
1
ALL SWITCHES SET  
TO "OFF" POSITION  
LOAD RESISTOR  
(RED)  
(GRY)  
10K  
2
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
LOAD RESISTOR  
4.3K  
JUMPER  
J7  
J1  
ALARM  
R
6
LOAD RESISTOR  
JUMPER  
(RED)  
(GRY)  
(GRY)  
(RED)  
(GRY)  
(BLK)  
(CLR)  
(RED)  
5
4
3
2
1
2
1
24VAC  
ICVC  
CB1  
4.3K  
(GRY)  
-
G
+
STOP  
J8  
SERVICE  
(BLK)  
(CLR)  
(RED)  
(BLK)  
(CLR)  
(RED)  
1
2
3
4
5
6
-
+
EVAP PRESS  
COND PRESS  
-
+
a19-1946  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WIRING SCHEMATICS (cont)  
CHILLER CONTROL SCHEMATIC (cont)  
(GRN)  
1
2
3
TO TB-G **  
230V  
COM  
COMP'R OIL HEATER  
11  
OPEN  
21  
22  
23  
11  
12  
13  
4 CLOSE  
5
(BLK)  
(BLK)  
1C  
1C  
1C  
1C  
1C  
1C  
(BLK)  
(WHT)  
(WHT)  
(WHT)  
6
12  
13  
(BLK)  
(WHT)  
(BLK)  
(WHT)  
115V  
HGBP  
ACTUATOR  
(RED)  
COM  
(WHT)  
(BLK)  
3C  
3C  
6
5
(BLK)  
2
(WHT)  
230V WIRING MODIFICATION  
COMP'R OIL HEATER  
(BLK)  
(BLU)  
(BLU)  
4
HOT GAS BYPASS  
(WHT)  
(BLK)  
(WHT)  
(BLK)  
(RED)  
(FR #7 & 8 HT EXCH)  
115V CONTROL ONLY  
(BLK)  
(BLK)  
(BLK)  
(BLK)  
(YEL)  
(RED)  
(ORN)  
(BRN)  
(BLK)  
(CLR)  
(BLK)  
(RED)  
(WHT)  
(WHT)  
(RED)  
(WHT)  
(RED)  
(WHT)  
(RED)  
(WHT)  
51  
50  
43  
17  
C
T3  
24VAC  
T1  
24VAC  
T2  
24VAC  
(BLK)  
(BLK)  
(GRN)  
TO VFD  
(BRN)  
(BRN)  
(BRN)  
(BRN)  
(BRN)  
(BRN)  
(BLU)  
(RED)  
COMP'R DISCH  
HIGH PRESS  
(BLU)  
B
(RED)  
HGBP  
SOLENOID  
(YEL)  
(BLK)  
A
(SHIELD)  
(BLK)  
(BLK)  
(RED)  
(GRY)  
(BLK)  
(RED)  
(GRY)  
(YEL)  
4
2
(RED)  
(BLK)  
3C  
SHOWN WIRED FOR 115V  
(CLR)  
(BLK)  
(BRN)  
23  
21  
2
1
(GRN)  
WHT  
WHT  
UPC  
(WHT)  
(WHT)  
(BLU)  
(RED)  
COMP'R OIL PUMP MOTOR  
(BLU)  
(RED)  
(YEL)  
(BLK)  
WINDING HIGH TEMPERATURE  
HGBP  
SOLENOID  
(WHT)  
(RED)  
(GRY)  
(BLK)  
(YEL)  
(BLK)  
4
2
3C  
230V WIRING MODIFICATION  
HOT GAS BYPASS  
(FR #1 - 6 HT EXCH)  
a19-1947  
YEL  
21  
22  
23  
11  
12  
13  
(YEL)  
2C  
2C  
2C  
VOLTAGE  
PER JOB  
REQM'T  
BLK  
(1-1/2 HP)  
COMP'R OIL  
PUMP MOTOR  
(BLK)  
(RED)  
M
RED  
LEGEND  
CB  
Circuit Breater  
Denotes Control Panel Terminal  
Denotes Oil Pump Terminal  
Denotes Power Panel Terminal  
CCM  
HGBP  
ICVC  
RHS  
UPC  
VFD  
Chiller Control Module  
Hot Gas Bypass  
International Chiller Visual Controller  
Relative Humidity Sensor  
Universal Protocol Controller  
Variable Frequency Drive  
Denotes Motor Starter Panel Conn  
Denotes Component Terminal  
Wire Splice  
**  
Denotes Conductor male/Female Connector  
Option Wiring  
* Standard on LF2 drive; optional on machines equipped with  
other VFDs.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WIRING SCHEMATICS (cont)  
ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical)  
a19-1966  
CONTINUED ON  
FACING PAGE  
NOT  
USED  
611  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WIRING SCHEMATICS (cont)  
ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont)  
DETAIL A  
34  
TB4  
TB4  
33  
CARRIER  
FACTORY  
WIRING  
SEE  
DETAIL  
A
a19-1967  
SEE  
DETAIL  
B
DETAIL B  
POWER  
PANEL  
TB4  
43  
35  
TB4  
19  
36  
POWER  
PANEL  
CARRIER  
FACTORY  
WIRING  
LEGEND  
CAP  
CB  
Capacitor  
Circuit Breaker  
Common  
COM  
COMM  
COND  
CR  
Communication  
Condenser  
Control Relay  
DPI/SI  
EA  
Internal Communication Protocols Connections  
Electrical Assembly  
Electro-Magnetic Interference  
Evaporator  
EMI  
EVAP  
FU  
Fuse  
GND  
JMPR  
M
Ground  
Jumper  
Motor  
NC  
Normally Closed  
Normally Open  
Potential Earth (Ground)  
I/O Card Mounting Slot Board  
Remote  
NO  
PE  
POD  
REM  
ROC  
SHLD  
TB  
Relay Output Common  
Shield  
Terminal Block  
* Located outside of starter; connected by field wiring.  
31  
611  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING  
Optional BACnet* Communications Wiring —  
0
The following section is used to configure the UPC Open con-  
troller which is used when the BACnet communications option  
is selected. The UPC Open controller is mounted in a separate  
enclosure below the main control box.  
1
9
2
8
7
3
10's  
1's  
5 4  
a48-8578  
6
0
1
9
TO ADDRESS THE UPC OPEN CONTROLLER — The  
user must give the UPC Open controller an address that is  
unique on the BACnet network. Perform the following proce-  
dure to assign an address:  
1. If the UPC Open controller is powered, pull the screw ter-  
minal connector from the controller's power terminals la-  
beled Gnd and HOT. The controller reads the address  
each time power is applied to it.  
2. Using the rotary switches (see Fig. A and B), set the con-  
troller's address. Set the Tens (10's) switch to the tens dig-  
it of the address, and set the Ones (1's) switch to the ones  
digit.  
As an example in Fig. B, if the controller’s address is 25,  
point the arrow on the Tens (10's) switch to 2 and the arrow on  
the Ones (1's) switch to 5.  
2
8
7
3
5 4  
6
Fig. B — Address Rotary Switches  
BACNET DEVICE INSTANCE ADDRESS — The UPC  
Open controller also has a BACnet Device Instance address.  
This Device Instance MUST be unique for the complete BAC-  
net system in which the UPC Open controller is installed. The  
Device Instance is auto generated by default and is derived by  
adding the MAC address to the end of the Network Number.  
The Network Number of a new UPC Open controller is 16101,  
but it can be changed using i-Vu® Tools or BACView device.  
By default, a MAC address of 20 will result in a Device In-  
stance of 16101 + 20 which would be a Device Instance of  
1610120.  
BT485  
TERMINATOR  
BACNET  
CONNECTION  
(BAS PORT)  
POWER LED  
Tx1 LED  
Rx1 LED  
Tx2 LED  
Rx2 LED  
BACNET  
BAUD RATE  
DIP SWITCHES  
EIA-485  
JUMPERS  
ADDRESS  
ROTARY  
SWITCHES  
RUN LED  
ERROR LED  
Fig. A — UPC Open Controller  
a48-8579  
* Sponsored by ASHRAE (American Society of Heating, Refrigerat-  
ing and Air Conditioning Engineers).  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
CONFIGURING THE BAS PORT FOR BACNET MS/  
TP — Use the same baud rate and communication settings for  
all controllers on the network segment. The UPC Open con-  
troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this  
protocol's communications.  
If the UPC Open controller has been wired for power, pull  
the screw terminal connector from the controller's power termi-  
nals labeled Gnd and HOT. The controller reads the DIP  
Switches and jumpers each time power is applied to it.  
a48-  
8580  
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS  
Port DIP switch DS4 to “EIA-485.” Set the BMS Protocol DIP  
switches DS8 through DS5 to “MSTP.” See Table A.  
Fig. C — DIP Switches  
Table A — SW3 Protocol Switch Settings  
for MS/TP  
Wire the controllers on an MS/TP network segment in a dai-  
sy-chain configuration. Wire specifications for the cable are  
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,  
twisted, stranded, shielded copper wire. The maximum length  
is 2000 ft.  
Install a BT485 terminator on the first and last controller on  
a network segment to add bias and prevent signal distortions  
due to echoing. See Fig. B, D, and E.  
DS8  
DS7  
DS6  
DS5  
DS4  
DS3  
Off  
Off  
Off  
Off  
On  
Off  
Verify that the EIA-485 jumpers below the CCN Port are set  
to EIA-485 and 2W.  
The example in Fig. C shows the BAS Port DIP Switches  
set for 76.8k (Carrier default) and MS/TP.  
Set the BAS Port DIP Switches DS2 and DS1 for the appro-  
priate communications speed of the MS/TP network (9600,  
19.2k, 38.4k, or 76.8k bps). See Fig. C and Table B.  
To wire the UPC Open controller to the BAS network:  
1. Pull the screw terminal connector from the controller's  
BAS Port.  
Table B — Baud Selection Table  
2. Check the communications wiring for shorts and  
grounds.  
3. Connect the communications wiring to the BAS port’s  
screw terminals labeled Net +, Net -, and Shield.  
NOTE: Use the same polarity throughout the network  
segment.  
4. Insert the power screw terminal connector into the UPC  
Open controller's power terminals if they are not current-  
ly connected.  
5. Verify communication with the network by viewing a  
module status report. To perform a module status report  
using the BACview keypad/display unit, press and hold  
the “FN” key then press the “.” Key.  
BAUD RATE  
9,600  
DS2  
Off  
On  
Off  
On  
DS1  
Off  
Off  
On  
On  
19,200  
38,400  
76,800  
WIRING THE UPC OPEN CONTROLLER TO THE MS/  
TP NETWORK — The UPC Open controller communicates  
using BACnet on an MS/TP network segment communications  
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.  
a48-8581  
Fig. D — Network Wiring  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
a48-8582  
Fig. E — BT485 Terminator Installation  
To install a BT485 terminator, push the BT485 terminator  
on to the BT485 connector located near the BACnet connector.  
NOTE: The BT485 terminator has no polarity associated with  
it.  
To order a BT485 terminator, consult Commercial Products  
i-Vu Open Control System Master Prices.  
MS/TP WIRING RECOMMENDATIONS — Recommen-  
dations are shown in Tables C and D. The wire jacket and UL  
temperature rating specifications list two acceptable alterna-  
tives. The Halar specification has a higher temperature rating  
and a tougher outer jacket than the SmokeGard specification,  
and it is appropriate for use in applications where the user is  
concerned about abrasion. The Halar jacket is also less likely to  
crack in extremely low temperatures.  
NOTE: Use the specified type of wire and cable for maximum  
signal integrity.  
Table C — MS/TP Wiring Recommendations  
SPECIFICATION  
Cable  
Conductor  
Insulation  
Color Code  
Twist Lay  
RECOMMMENDATION  
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable  
22 or 24 AWG stranded copper (tin plated)  
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.  
Black/White  
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal  
Aluminum/Mylar shield with 24 AWG TC drain wire  
Shielding  
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.  
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.  
Jacket  
DC Resistance  
Capacitance  
Characteristic Impedance  
Weight  
15.2 Ohms/1000 feet (50 Ohms/km) nominal  
12.5 pF/ft (41 pF/meter) nominal conductor to conductor  
100 Ohms nominal  
12 lb/1000 feet (17.9 kg/km)  
SmokeGard 167°F (75°C)  
Halar -40 to 302°F (-40 to 150°C)  
UL Temperature Rating  
Voltage  
Listing  
300 Vac, power limited  
UL: NEC CL2P, or better  
LEGEND  
AWG  
CL2P  
DC  
American Wire Gage  
Class 2 Plenum Cable  
Direct Current  
FEP  
NEC  
O.D.  
TC  
Fluorinated Ethylene Polymer  
National Electrical Code  
Outside Diameter  
Tinned Copper  
Underwriters Laboratories  
UL  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table D — Open System Wiring Specifications and Recommended Vendors  
WIRING SPECIFICATIONS  
Description  
RECOMMENDED VENDORS AND PART NUMBERS  
Connect Air  
International  
Contractors  
Wire and Cable  
Wire Type  
Belden RMCORP  
22 AWG, single twisted shielded pair, low capacitance, CL2P,  
TC foam FEP, plenum rated. See MS/TP Installation Guide for  
specifications.  
24 AWG, single twisted shielded pair, low capacitance, CL2P,  
TC foam FEP, plenum rated. See MS/TP Installation Guide  
for specifications.  
W221P-22227  
W241P-2000F  
25160PV  
CLP0520LC  
MS/TP  
Network (RS-485)  
82841 25120-OR  
21450  
Rnet  
4 conductor, unshielded, CMP, 18 AWG, plenum rated.  
W184C-2099BLB 6302UE  
CLP0442  
LEGEND  
American Wire Gage  
Class 2 Plenum Cable  
Communications Plenum Rated  
Fluorinated Ethylene Polymer  
Tinned Copper  
AWG  
CL2P  
CMP  
FEP  
TC  
LOCAL ACCESS TO THE UPC OPEN CONTROL-  
LER — The user can use a BACview6 handheld keypad dis-  
play unit or the Virtual BACview software as a local user inter-  
face to an Open controller. These items let the user access the  
controller network information. These are accessory items and  
do not come with the UPC Open controller.  
The BACview6 unit connects to the local access port on the  
UPC Open controller. See Fig. F. The BACview software must  
be running on a laptop computer that is connected to the local  
access port on the UPC Open controller. The laptop will re-  
quire an additional USB link cable for connection.  
If modifications to the default Element and Bus number are  
required, both the ComfortLink and UPC Open configurations  
must be changed.  
The following configurations are used to set the CCN Ad-  
dress and Bus number in the ComfortLink control. These con-  
figurations can be changed using the scrolling marquee display  
or accessory Navigator handheld device.  
ConfigurationCCNCCN.A (CCN Address)  
ConfigurationCCNCCN.B (CCN Bus Number)  
The following configurations are used to set the CCN Ad-  
dress and Bus Number in the UPC Open controller. These con-  
figurations can be changed using the accessory BACview6 dis-  
play.  
See the BACview Installation and User Guide for instruc-  
tions on connecting and using the BACview6 device.  
To order a BACview6 Handheld (BV6H), consult Commer-  
Navigation: BACviewCCN  
Home: Element Comm Stat  
Element: 1  
cial Products i-Vu® Open Control System Master Prices.  
CONFIGURING THE UPC OPEN CONTROLLER'S  
PROPERTIES — The UPC Open device and ComfortLink™  
controls must be set to the same CCN Address (Element) num-  
ber and CCN Bus number. The factory default settings for  
CCN Element and CCN Bus number are 1 and 0 respectively.  
Bus: 0  
TROUBLESHOOTING — If there are problems wiring or  
addressing the UPC Open controller, contact Carrier Technical  
Support.  
Fig. F — BACview6 Device Connection  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
COMMUNICATION LEDS — The LEDs indicate if the  
controller is communicating with the devices on the network.  
See Tables E and F. The LEDs should reflect communication  
traffic based on the baud rate set. The higher the baud rate the  
more solid the LEDs become. See Fig. B for location of LEDs  
on UPC Open module.  
REPLACING THE UPC OPEN BATTERY — The UPC  
Open controller's 10-year lithium CR2032 battery provides a  
minimum of 10,000 hours of data retention during power  
outages.  
IMPORTANT: Power must be ON to the UPC Open when  
replacing the battery, or the date, time, and trend data will  
be lost.  
Remove the battery from the controller, making note of the  
battery's polarity. Insert the new battery, matching the battery's  
polarity with the polarity indicated on the UPC Open  
controller.  
NETWORK POINTS LIST — The points list for the control-  
ler is shown in Table G.  
Table E — LED Status Indicators  
LED  
STATUS  
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on  
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition  
that caused the fault returns to normal.  
Power  
Rx  
Tx  
Run  
Error  
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.  
Lights when the controller transmits data to the network segment; there is a Tx LED for Ports 1 and 2.  
Lights based on controller status. See Table F.  
Lights based on controller status. See Table F.  
Table F — Run and Error LEDs Controller and Network Status Indication  
RUN LED  
ERROR LED  
STATUS  
2 flashes per second  
2 flashes per second  
2 flashes per second  
2 flashes per second  
2 flashes per second  
5 flashes per second  
5 flashes per second  
7 flashes per second  
Off  
Normal  
2 flashes, alternating with Run LED  
3 flashes, then off  
1 flash per second  
On  
On  
Off  
Five minute auto-restart delay after system error  
Controller has just been formatted  
Controller is alone on the network  
Exec halted after frequent system errors or control programs halted  
Exec start-up aborted, Boot is running  
Firmware transfer in progress, Boot is running  
Ten second recovery period after brownout  
7 flashes per second, alternating with Run LED  
14 flashes per second 14 flashes per second, alternating with Run LED Brownout  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table G — Network Points List  
CCN  
READ/  
DEFAULT  
VALUE  
BACNET  
OBJECT ID  
BACNET  
OBJECT NAME  
POINT DESCRIPTION  
UNITS  
RANGE  
POINT NAME WRITE  
1st Current Alarm State  
Active Demand Limit  
Actual Guide Vane Position  
Actual VFD Speed  
Calc Evap Sat Temp  
Chilled Water Deadband  
Chilled Water Delta P  
Chilled Water Delta T  
Chilled Water Pump  
Chilled Water Temp  
Chiller Start/Stop  
ALARM_01  
DEM_LIM  
GV_POS  
VFD_ACT  
EAT  
R
R/W  
R
R
R
R
R
R
R
R
R/W  
R
R
R
R
R
R
R
N/A  
N/A  
N/A  
N/A  
N/A  
1.0  
N/A  
N/A  
OFF  
N/A  
STOP  
N/A  
N/A  
N/A  
NO  
OFF  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
0-270  
40 to 100  
0 to 100  
AV:4  
AV:6  
AV:7  
AV:11  
AV:13  
AV:14  
AV:15  
AV:16  
BV:4  
AV:17  
BV:5  
AV:18  
AV:19  
AV:20  
BV:6  
alarm_01_1  
dem_lim_1  
gv_pos_1  
vfd_act_1  
ert_1  
%
%
%
°F  
^F  
^F  
^F  
N/A  
°F  
N/A  
°F  
0 to 110  
-40 to 245  
0.5 to 2.0  
-6.7 to 420  
-40 to 245  
OFF/ON  
-40 to 245  
STOP/START  
-40 to 245  
-40 to 245  
-40 to 245  
NO/YES  
CWDB  
cwdb_1  
chwpd_1  
CHWPD  
CHW_DT  
CHLP  
CHW_TMP  
CHIL_S_S  
CMPD  
MTRW  
MTRB  
CDW_FLOW  
CDP  
CRP  
CRT  
CDWPD  
LCW_STPT  
CHWSTPT  
N/A  
chw_dt_1  
chlp_1  
chw_tmp_1  
chil_s_s_1  
cmpd_1  
mtrw_1  
mtrb_1  
cdw_flow_1  
cdp_1  
Comp Discharge Temp  
Comp Motor Winding Temp  
Comp Thrust Brg Temp  
Cond Water Flow  
°F  
°F  
N/A  
N/A  
PSI  
°F  
PSI  
°F  
°F  
%
%
%
Cond Water Pump  
OFF/ON  
BV:7  
Condenser Pressure  
Condenser Refrig Temp  
Condenser Water Delta P  
Control Point  
Current CHW Setpoint  
Demand Level 1  
Demand Level 2  
Demand Level 3  
Element Comm Status  
-6.7 to 420  
-40 to 245  
-6.7 to 420  
10 to 120  
0.00 to 99.9  
0 to 100  
AV:21  
AV:22  
AV:23  
AV:24  
AV:25  
AV:1  
AV:2  
AV:3  
BV:2999  
crp_1  
crt_1  
cdwpd_1  
R
R/W  
R
R
R
lcw_stpt_1  
chwstpt_1  
dmv_lvl_1_perct_1  
dmv_lvl_2_perct_1  
dmv_lvl_3_perct_1  
element_stat_1  
N/A  
N/A  
N/A  
0 to 100  
0 to 100  
No Comm/Normal  
R
R
N/A  
Element Communications  
Alarm  
N/A  
R
R
N/A  
N/A  
N/A  
Inactive/Active  
BV:20  
comm_lost_alm_1  
emstop_1  
ENABLE/  
EMSTOP  
Emergency Stop  
EMSTOP  
ENABLE  
BV:8  
Entering Chilled Water  
Entering Condenser Water  
ECW  
ECDW  
R
R
°F  
°F  
N/A  
N/A  
-40 to 245  
-40 to 245  
AV:26  
AV:27  
ecw_1  
ecdw_1  
Comm Normal  
Comm Lost  
Equipment Alarm  
N/A  
R
N/A  
N/A  
BV:1  
element_alarm_1  
Evaporator Pressure  
Evaporator Refrigerant Temp  
ERP  
ERT  
R
R
PSI  
°F  
N/A  
N/A  
-6.7 to 420  
-40 to 245  
AV:28  
AV:13  
erp_1  
ert_1  
Leaving Chilled Water -  
Prime Variable  
LCW  
R
°F  
N/A  
-40 to 245  
AV:31  
lcw_1  
Leaving Condenser Water  
Line Active Current  
Line Active Voltage  
Line Frequency  
Line Power Factor  
Local Schedule  
Occupied?  
Oil Sump Temperature  
Remote Start Contact  
LCDW  
AMPS_ACT  
VOLT_ACT  
LINEFREQ  
LINE_PF  
N/A  
OCC  
OILT  
REM_CON  
R
R
R
R
R
R
R
R
R/W  
°F  
A
V
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
NO  
N/A  
OPEN  
-40 to 245  
0.0 to 99999.0  
0.0 to 99999.0  
0 to 99  
0.00 to 2.00  
No Comm/Normal  
NO/YES  
AV:32  
AV:8  
AV:9  
AV:30  
AV:34  
BV:2  
BV:10  
AV:33  
BV:11  
lcdw_1  
amps_act_1  
volt_act_1  
linefreq_1  
line_pf_1  
schedule_1  
occ_1  
Hz  
N/A  
N/A  
°F  
-40 to 245  
OPEN/CLOSE  
oilt_1  
rem_con_1  
N/A  
0=Timeout,  
1=Ready,  
2=Recyle,  
3=Startup,  
4=Running,  
5=Demand,  
6=Ramping,  
7=Autorest,  
8=Override,  
9=Tripout,  
Run Status  
STATUS  
R
N/A  
N/A  
AV:35  
status_1  
10=Control Test,  
11=Lockout,  
12=Pumpdown,  
13=Prestart  
Service Ontime  
Surge Line Delta T  
S_HRS  
DELTA_TX  
R/W  
R
hr  
°F  
N/A  
N/A  
0 to 32767  
0 to 200  
AV:36  
AV:38  
s_hrs_1  
delta_tx_1  
1=Normal,  
2=Alert, 3=Alarm  
System Alert/Alarm  
SYS_ALM  
R
N/A  
N/A  
AV:40  
sys_alm_1  
611  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table G — Network Points List (cont)  
CCN  
READ/  
DEFAULT  
VALUE  
BACNET  
OBJECT ID  
BACNET  
OBJECT NAME  
POINT DESCRIPTION  
UNITS  
RANGE  
POINT NAME WRITE  
System Cooling Demand  
Level  
N/A  
R
N/A  
N/A  
N/A  
AV:9006  
cool_demand_level_1  
System Demand Limiting  
Target Guide Vane Position  
Target VFD Speed  
N/A  
GV_TRG  
VFD_OUT  
TFR_HIGH  
TFR_LOW  
N/A  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
N/A  
%
%
N/A  
N/A  
N/A  
OFF  
OFF  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
OFF/ON  
0 to 100  
0 to 100  
OFF/ON  
OFF/ON  
N/A  
N/A  
N/A  
N/A  
N/A  
BV:3  
AV:41  
AV:42  
BV:13  
dem_lmt_act_1  
gv_trg_1  
vfd_out_1  
tfr_high_1  
tfr_low_1  
user_analog_1_1  
user_analog_2_1  
user_analog_3_1  
user_analog_4_1  
user_analog_5_1  
user_binary_1_1  
user_binary_2_1  
user_binary_3_1  
user_binary_4_1  
user_binary_5_1  
Tower Fan Relay High  
Tower Fan Relay Low  
User Defined Analog 1  
User Defined Analog 2  
User Defined Analog 3  
User Defined Analog 4  
User Defined Analog 5  
User Defined Binary 1  
User Defined Binary 2  
User Defined Binary 3  
User Defined Binary 4  
User Defined Binary 5  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
BV:14  
AV:2901  
AV:2902  
AV:2903  
AV:2904  
AV:2905  
BV:2911  
BV:2912  
BV:2913  
BV:2914  
BV:2915  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
LEGEND  
CHW  
R
VFD  
W
Chilled Water  
Read  
Variable Frequency Drive  
Write  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2011 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53190012-01  
Printed in U.S.A.  
Form 19XRV-3SS  
Pg 40  
711  
3-11  
Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Iron F980 User Manual
Black Decker Power Hammer BPHR223K User Manual
Briggs Stratton Portable Generator 01653 4 User Manual
Cadco Food Warmer CML User Manual
Canon Digital Camera 0581C002 User Manual
Canon Scanner M11058 User Manual
Carrier Heat Pump 50YX User Manual
Cary Audio Design Stereo Amplifier CAD 211 FE User Manual
C Crane Portable Radio CCRadio plus User Manual
Chicago Electric Mixer 65760 User Manual