installation, start-up,
355MAV
Series D
and operating instructions
DELUXE 4-WAY MULTIPOISE
VARIABLE-CAPACITY DIRECT-VENT
CONDENSING GAS FURNACE
Cancels: II 355M-40-4
II 355M-40-5
7-97
CANADIAN GAS ASSOCIATION
ama
®
A PPROVED
R
A93040
NOTE: Read the entire instruction manual before starting the
installation.
As an ENERGY STARSM
Partner, Bryant Heating &
Cooling Systems Com-
pany has determined that
this product meets the EN-
ERGY STAR guidelines
for energy efficiency.
This symbol → indicates a change since the last issue.
CERTIFICATION OF MANUFACTURING SITE
Index
Page
DIMENSIONAL DRAWING........................................................2
SAFETY CONSIDERATIONS.....................................................3
Clearances to Combustibles......................................................3
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS ....3-4
INTRODUCTION..........................................................................4
APPLICATIONS ......................................................................4-11
General ......................................................................................4
Upflow Applications..............................................................4-6
Downflow Applications.........................................................7-8
Horizontal Left (Supply-Air Discharge) Applications .........8-9
Horizontal Right (Supply-Air Discharge) Applications.....9-11
LOCATION ............................................................................11-13
General...............................................................................11-12
Low-Fire Only Installation.....................................................12
Furnace Location Relative to Cooling Equipment ................12
Hazardous Locations...............................................................13
INSTALLATION....................................................................13-17
Leveling Legs (If Desired).....................................................13
Installation In Upflow or Downflow Applications ..........13-15
Installation In Horizontal Applications..................................15
Filter Arrangement..................................................................16
Bottom Closure Panel.............................................................16
Gas Piping...............................................................................17
ELECTRICAL CONNECTIONS...........................................17-21
115-v Wiring......................................................................17-18
24-v Wiring........................................................................18-20
Accessories ........................................................................20-21
DIRECT VENTING ...............................................................21-29
Removal of Existing Furnaces from
AIRFLOW
UPFLOW
HORIZONTAL
LEFT
HORIZONTAL
RIGHT
DOWNFLOW
AIRFLOW
AIRFLOW
AIRFLOW
A93041
Fig. 1—Multipoise Orientations
Heating Mode—Two Stage....................................................32
Emergency Heat Mode...........................................................32
Cooling Mode .........................................................................32
Heat Pump Mode...............................................................32-33
Continuous Fan Mode ............................................................33
Component Test......................................................................34
Bypass Humidifier Mode........................................................34
Dehumidification Mode..........................................................34
Zone Mode..............................................................................34
START-UP PROCEDURES ..................................................34-42
General ....................................................................................34
Select Setup Switch Positions...........................................34-35
Prime Condensate Trap With Water.................................35-36
Purge Gas Lines......................................................................37
Adjustments .......................................................................37-42
Set Gas Input Rate ............................................................37-41
Set Temperature Rise ........................................................41-42
Set Thermostat Heat Anticipator............................................42
CHECK SAFETY CONTROLS ............................................42-43
Check Primary Limit Control.................................................42
Check Pressure Switch......................................................42-43
CHECKLIST...........................................................................43-44
Common Vent Systems.....................................................21
Combustion-Air and Vent Piping .....................................21-26
Concentric Vent and Combustion-Air Termination
Kit Installation..............................................................26-29
Multiventing and Vent Terminations.....................................29
CONDENSATE DRAIN..............................................................29
General ....................................................................................29
Application..............................................................................29
Condensate Drain Protection..................................................29
SEQUENCE OF OPERATION..............................................31-34
Self-Test Mode........................................................................31
Heating Mode ....................................................................31-32
—1—
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY CONSIDERATIONS
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified person-
nel should install, repair, or service heating equipment. Untrained
personnel can perform basic maintenance functions such as clean-
ing and replacing air filters. All other operations must be per-
formed by trained service personnel. When working on heating
equipment, observe precautions in literature, on tags, and on labels
attached to or shipped with unit and other safety precautions that
may apply.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation
and servicing to protect the furnace electronic control.
Precautions will prevent electrostatic discharges from
personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing
the control to electrostatic discharge by putting the
furnace, the control, and the person at the same electro-
static potential.
→ Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA No.
54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm
Air Heating and Air Conditioning Systems (NFPA 90B)
ANSI/NFPA 90B. In Canada, refer to the current edition of the
National Standard of Canada CAN/CGA-B149.1- and .2-M95
Natural Gas and Propane Installation Codes (NSCNGPIC). Wear
safety glasses and work gloves. Have fire extinguisher available
during start-up and adjustment procedures and service calls.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on unit or in instructions and manuals,
be alert to potential for personal injury.
.
2. Firmly touch a clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily
discharged.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size
Furnaces are only approved for altitudes 0 - 7,000 ft. (0 - 2,135m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for
some natural gas applications.
This furnace is for indoor installation in a building constructed on site. This furnace may be installed in a manufactured
(mobile) home when stated on rating plate and using factory authorized kit.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible
material.
This appliance requires a special venting system. Refer to the installation instructions for parts list and method of
installation. This furnace is for use with schedule-40 PVC, PVC-DWV, or ABS-DWV pipe, and must not be vented in
common with other gas-fired appliances. Construction through which vent/air intake pipes may be installed is maximum
24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).
MINIMUM INCHES CLEARANCE
Clearance arrows
do not change with
furnace orientation.
TO COMBUSTIBLE CONSTRUCTION
ALL POSITIONS:
Mimimum front clearance for service 30
inches (762mm).
140 size furnaces require 1 inch back
clearance to combustible materials.
*
††
1"
DOWNFLOW POSITIONS:
For installation on combustible floors only
†
††
§
when installed on special base No.
KGASB0201ALL, Coil Assembly, Part No.
CD5 or CK5, or Coil Casing, Part No.
KCAKC.
0"B A
0"
A
R
C
E
R
K
R
I
E
HORIZONTAL POSITIONS:
S
Clearance shown is for air inlet and air
outlet end.
Line contact is permissible only between
lines formed by intersections of top and two
sides of furnace jacket, and building joists,
studs, or framing.
E
L
È
R
E
§
N
V
T
I
I
T
R
C
E
F
R
O
E
A
*
MIN
N
N
V
30
T
A
N
0"
T
3"
§
120 and 140 size Furnaces require 1 inch
bottom clearance to combustible materials.
Ø
0"
†
Ø
Vent clearance to
combustibles 0".
323857-101 REV. B (LIT)
Clearance in inches
A97378
→ Fig. 3—Clearances to Combustibles
—3—
Download from Www.Somanuals.com. All Manuals Search And Download.
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch un-
grounded objects, etc.).
Installations must comply with regulations of serving gas supplier
and local building, heating, plumbing, or other codes in effect in
area in which installation is made. In absence of local codes,
installation must conform with NFGC.
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touch-
ing control or wires.
Canadian installations must be made in accordance with NSCNG-
PIC and all authorities having jurisdiction.
5. Use this procedure for installed and uninstalled (un-
grounded) furnaces.
These instructions cover minimum requirements for a safe instal-
lation and conform to existing national standards and safety codes.
In some instances, these instructions exceed certain local codes
and ordinances, especially those that may not have kept pace with
changing residential construction practices. We require these
instructions as a minimum for a safe installation.
6. Before removing a new control from its container, dis-
charge your body’s electrostatic charge to ground to protect
the control from damage. If the control is to be installed in
a furnace, follow items 1 through 5 before bringing the
control or yourself into contact with the furnace. Put all
used AND new controls into containers before touching
ungrounded objects.
CAUTION: Application of this furnace should be in-
doors with special attention given to vent sizing and
material, gas input rate, air temperature rise, unit leveling,
and unit sizing. Improper installation or misapplication of
furnace can require excessive servicing or cause prema-
ture component failure.
7. An ESD service kit (available from commercial sources)
may also be used to prevent ESD damage.
INTRODUCTION
The 355MAV Multipoise Condensing Gas-Fired Furnaces are
A.G.A./C.G.A. certified for natural and propane gases and for
installation in alcoves, attics, basements, closets, utility rooms,
crawlspaces, and garages. The furnace is factory-shipped for use
with natural gas. An A.G.A./C.G.A. listed gas conversion kit is
required to convert furnace for use with propane gas.
These furnaces SHALL NOT be installed directly on carpeting,
tile, or any other combustible material other than wood flooring. In
downflow installations, accessory floor base MUST be used when
installed on combustible materials and wood flooring. Special base
is not required when this furnace is installed on manufacturer’s
Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No.
KCAKC is used. The design of this furnace line is not
A.G.A./C.G.A. certified for installation in mobile homes, recre-
ation vehicles, or outdoors. These furnaces are suitable for
installation in a residence built on site or a manufactured residence
completed at final site.
These furnaces are shipped with the drain and pressure tubes
connected for UPFLOW applications. Minor modifications are
required when used in DOWNFLOW, HORIZONTAL RIGHT, or
HORIZONTAL LEFT (supply-air discharge direction) applica-
tions as shown in Fig. 1. See details in Applications section.
These furnaces are shipped with the following materials to assist in
proper furnace installation. These materials are shipped in the main
blower compartment.
WARNING: Improper installation, adjustment, alter-
ation, service, maintenance, or use can cause carbon
monoxide poisoning, explosion, fire, electrical shock, or
other conditions which may cause personal injury or
property damage. Consult a qualified installer, service
agency, local gas supplier, or your distributor or branch
for information or assistance. The qualified installer or
agency must use only factory-authorized and listed kits or
accessories when modifying this product. Failure to
follow this warning could result in electrical shock, fire,
personal injury, or death.
For accessory installation details, refer to applicable installation
literature.
APPLICATIONS
I. GENERAL
Some assembly and modifications are required for furnaces
installed in any of the 4 applications shown in Fig. 1. All drain and
pressure tubes are connected as shown in Fig. 5. See appropriate
application instructions for these procedures.
Installer Packet includes:
II. UPFLOW APPLICATIONS
Installation, Start-Up, and Operating Instructions
An upflow furnace application is where furnace blower is located
below combustion and controls section of furnace, and conditioned
air is discharged upwards.
Service and Maintenance Procedures
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes:
Quantity
A. Condensate Trap Location (Factory-Shipped
Orientation)
Pressure tube extension
Collector box or condensate trap extension tube
Inducer housing drain tube
1/2-in. CPVC street elbow
Drain tube coupling
Drain tube coupling grommet
Vent and combustion-air pipe support
Combustion-air pipe perforated disk assembly
1
1
1
2
1
1
2
1
The condensate trap is factory installed in the blower shelf and
factory connected for UPFLOW applications. A factory-supplied
tube is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factory-Shipped Orientation) section for drain tube
extension details.
→ Before installing the furnace in the United States, refer to the
current edition of the NFGC and the NFPA 90B. For further
information, the NFGC and the NFPA 90B are available from
National Fire Protection Association Inc., Batterymarch Park,
Quincy, MA 02269; American Gas Association, 1515 Wilson
Boulevard, Arlington, VA 22209; or from Literature Distribution.
Before installing the furnace in Canada, refer to the current edition
of the NSCNGPIC. Contact Standards Department of Canadian
Gas Association, 55 Scarsdale Road, Don Mills, Ontario, Canada
M3B 2R3.
B. Condensate Trap Tubing (Factory-Shipped
Orientation)
NOTE: See Fig. 5 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port,
and Pressure Switch Tubes
These tubes should be factory attached to condensate trap
and pressure switch ready for use in UPFLOW applications.
These tubes can be identified by their connection location
—4—
Download from Www.Somanuals.com. All Manuals Search And Download.
FURNACE
DOOR
BLOWER SHELF
CONDENSATE
TRAP
FURNACE
DOOR
CONDENSATE
TRAP (INSIDE)
FURNACE
SIDE
FURNACE
SIDE
7
4
8
4
3
4
3
5
1
4
5
4
4
26
3
4
1
1
FIELD
DRAIN
CONN
FIELD
DRAIN
CONN
26
4
1
2
ALTERNATE DRAIN
TUBE LOCATION
SIDE VIEW
FRONT VIEW
END VIEW
FRONT VIEW
CONDENSATE TRAP
DRAIN TUBE LOCATION
HORIZONTAL
APPLICATIONS
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
UPFLOW APPLICATIONS
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
1⁄4 OD
COLLECTOR BOX TO
TRAP RELIEF PORT
1
1
2
1⁄2 OD
INDUCER HOUSING
DRAIN CONNECTION
3
4
5⁄8 OD
COLLECTOR BOX
DRAIN CONNECTION
1
7
8
8
SCREW HOLE FOR
UPFLOW OR DOWN-
FLOW APPLICATIONS
(OPTIONAL)
3
1
4
7
WIRE TIE
GUIDES
(WHEN USED)
1
1⁄2-IN. PVC OR CPVC
2
4
FRONT VIEW
SIDE VIEW
A93026
Fig. 4—Condensate Trap
and also by a color label on each tube. These tubes are
identified as follows: collector box drain tube (blue label),
inducer housing drain tube (violet label or molded), relief
port tube (green label), and pressure switch tube (pink
label).
f. Connect larger diameter drain tube and clamp (factory-
supplied in loose parts bag) to condensate trap and clamp
securely.
g. Route tube to coupling and cut to appropriate length.
h. Attach tube to coupling and clamp securely.
2. Condensate Trap Drain Tube
C. Condensate Trap Location (Alternate Upflow
Orientation)
The condensate trap drain connection must be extended for
field attachment by doing the following:
An alternate location for the condensate trap is the left-hand side
of casing. (See Fig. 2 and 6.)
a. Determine location of field drain connection. (See Fig. 2
or 5.)
NOTE: If the alternate left-hand side of casing location is used,
the factory-connected drain and relief port tubes must be discon-
nected and modified for attachment. See Condensate Trap Tubing
(Alternate Upflow Orientation) section for tubing attachment.
NOTE: If internal filter is used, drain tube should be located to
opposite side of casing of return duct attachment to assist in filter
removal.
b. Remove and discard casing drain hole plug button from
desired side.
To relocate condensate trap to the left-hand side, perform the
following:
c. Install drain tube coupling grommet (factory-supplied in
loose parts bag) in selected casing hole.
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
d. Slide drain tube coupling (factory-supplied in loose parts
bag) through grommet so long end of coupling faces
blower.
3. Remove casing hole filler cap from casing hole. (See Fig. 2
or 6.)
e. Cement 2 factory-supplied 1/2-in. street CPVC elbows to
rigid drain tube connection on condensate trap. (See Fig.
5.) These elbows must be cemented together and ce-
mented to condensate trap drain connection.
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
5. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
—5—
Download from Www.Somanuals.com. All Manuals Search And Download.
PLUG
CAP
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (GREEN)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
CONDENSATE
TRAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
COLLECTOR BOX
TUBE (GREEN)
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FIELD-INSTALLED
FACTORY-SUPPLIED
1⁄2 -IN. CPVC STREET
ELBOWS (2) FOR
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (RIGHT
DRAIN OPTION)
LEFT DRAIN OPTION
A94213
A94214
Fig. 5—Factory-Shipped Upflow Tube Configuration
(Shown With Blower Access Panel Removed)
Fig. 6—Alternate Upflow Tube Configuration and
Trap Location
D. Condensate Trap Tubing (Alternate Upflow
Orientation)
c. Determine appropriate length, cut, and connect tube.
E. Condensate Trap Field Drain Attachment
NOTE: See Fig. 6 or tube routing label on main furnace door to
confirm location of these tubes.
Refer to Condensate Drain section for recommendations and
procedures.
1. Collector Box Drain Tube
F. Pressure Switch Tubing
Connect collector box drain tube (blue label) to condensate
trap.
The LOWER collector box pressure tube (pink label) is factory
connected to the pressure switch and should not require any
modification.
NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between
corrugated sections to prevent kinks.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door
to check for proper connections.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to conden-
sate trap.
G. Upper Collector Box and Inducer Housing (Unused)
Drain Connections
UPPER COLLECTOR BOX DRAIN CONNECTION
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to conden-
sate trap.
Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white striped
label). This tube is plugged to prevent condensate leakage in this
application. Ensure this tube is plugged.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door
to check for proper connections.
3. Relief Port Tube
UPPER INDUCER HOUSING DRAIN CONNECTION
a. Connect relief port tube (green label) to condensate trap.
Attached to the UPPER (unused) inducer housing drain connection
is a cap and clamp. This cap is used to prevent condensate leakage
in this application. Ensure this connection is capped.
b. Extend this tube (if required) by splicing to small
diameter tube (factory-supplied in loose parts bag).
—6—
Download from Www.Somanuals.com. All Manuals Search And Download.
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
COLLECTOR BOX
TUBE (GREEN)
PLUG
PLUG
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
EXTENSION TUBE
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
CONDENSATE
TRAP
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
INDUCER HOUSING
DRAIN TUBE (VIOLET)
DRAIN TUBE
COUPLING
A94215
A94216
Fig. 7—Downflow Tube Configuration
(Left-Hand Trap Installation)
Fig. 8—Downflow Tube Configuration
(Right-Hand Trap Installation)
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door
to check for proper connections.
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to
condensate trap.
H. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
c. Connect LOWER collector box drain connection to
condensate trap.
III. DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located
above combustion and controls section of furnace, and conditioned
air is discharged downwards.
(1.) Condensate Trap Located on Left Side of Casing
(a.) Connect LOWER collector box drain tube
(blue and white striped label) to condensate
trap. Tube does not need to be cut.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 7, or 8.
(b.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
To relocate condensate trap from the blower shelf to desired
location, perform the following:
(a.) Install drain tube coupling (factory-supplied in
loose parts bag) into collector box drain tube
(blue and white striped label) which was pre-
viously plugged.
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
(b.) Connect larger diameter drain tube (factory-
supplied in loose parts bag) to drain tube
coupling, extending collector box drain tube
for connection to condensate trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2,
7, or 8.)
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
→
(c.) Route extended collector box drain tube di-
rectly from collector box drain to condensate
trap as shown in Fig. 8.
5. Install condensate trap into desired casing hole by inserting
tube connection stubs through casing hole and rotating until
tabs snap into locking position.
(d.) Determine appropriate length and cut.
(e.) Connect to condensate trap.
B. Condensate Trap Tubing
(f.) Clamp tube to prevent any condensate leakage.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door
to check for proper connections.
2. Inducer Housing Drain Tube
a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
1. Collector Box Drain Tube
—7—
Download from Www.Somanuals.com. All Manuals Search And Download.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to conden-
sate trap.
IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE)
APPLICATIONS
A horizontal left furnace application is where furnace blower is
located to the right of combustion and controls section of furnace,
and conditioned air is discharged to the left.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and factory-
supplied in loose parts bag) to connect LOWER inducer
housing drain connection to the condensate trap.
CAUTION: Local codes may require a drain pan under
entire furnace and condensate trap when a condensing
furnace is used in an attic application or over a finished
ceiling.
e. Connect inducer housing drain connection to condensate
trap.
(1.) Condensate Trap Located on Left Side of Casing
(a.) Determine appropriate length and cut.
(b.) Connect tube to condensate trap.
NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box (J-box) MUST be relocated to
opposite side of furnace casing. (See Fig. 9.) See Electrical
Connection section for J-box relocation.
(c.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
A. Condensate Trap Location
→
(a.) Route inducer housing drain tube (violet label)
directly from inducer housing drain to conden-
sate trap as shown in Fig. 8.
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 9.
(b.) Determine appropriate length and cut.
(c.) Connect tube to condensate trap.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
(d.) Clamp tube to prevent any condensate leakage.
1. Remove 3 tubes connected to condensate trap.
3. Relief Port Tube
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
Refer to Pressure Switch Tubing section for connection
procedure.
3. Remove casing hole filler cap from casing hole. (See Fig. 2
or 9.)
C. Condensate Trap Field Drain Attachment
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
Refer to Condensate Drain section for recommendations and
procedures.
5. Install condensate trap into casing hole by inserting tube
connection stubs through casing hole and rotating until tabs
snap into locking position.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This tube MUST be dis-
connected and used for the condensate trap relief port tube. The
other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be
connected to the pressure switch in DOWNFLOW or HORIZON-
TAL RIGHT applications.
B. Condensate Trap Tubing
NOTE: See Fig. 9 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Install drain tube coupling (factory-supplied in loose
parts bag) into collector box drain tube (blue label)
which was previously connected to condensate trap.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door
to check for proper connections.
b. Connect large diameter drain tube and clamp (factory-
supplied in loose parts bag) to drain tube coupling,
extending collector box drain tube.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached
to pressure switch.
c. Route extended tube (blue label) to condensate trap and
cut to appropriate length.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connec-
tion by splicing to small diameter tube (factory-supplied in
loose parts bag).
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
3. Connect collector box pressure tube (green label) to pres-
sure switch connection labeled COLLECTOR BOX.
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to conden-
sate trap.
4. Extend collector box pressure tube (pink label) which was
previously connected to pressure switch by splicing to
remaining small diameter tube (factory-supplied in loose
parts bag).
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to conden-
sate trap.
5. Route this extended tube (pink label) to condensate trap
relief port connection.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
3. Relief Port Tube
E. Condensate Trap Freeze Protection
a. Extend collector box tube (green label) which was
previously connected to condensate trap by splicing to
small diameter tube (factory-supplied in loose parts bag).
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
—8—
Download from Www.Somanuals.com. All Manuals Search And Download.
b. Route extended collector box pressure tube to relief port
connection on condensate trap.
V. HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE)
APPLICATIONS
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
C. Condensate Trap Field Drain Attachment
A horizontal right furnace application is where furnace blower is
located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.
Refer to Condensate Drain section for recommendations and
procedures.
D. Pressure Switch Tubing
CAUTION: Local codes may require a drain pan under
entire furnace and condensate trap when a condensing
furnace is used in attic application or over a finished
ceiling.
The LOWER collector box pressure tube (pink label) is factory
connected to the pressure switch and should not require any
modification.
NOTE: See Fig. 9 or tube routing label on main furnace door to
check for proper connections.
NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC Installation Codes and/or local codes.
E. Condensate Trap Freeze Protection
A. Condensate Trap Location
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
F. Construct a Working Platform
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 11.
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 10.)
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
CAUTION: The condensate trap MUST be installed
below furnace. See Fig. 4 for dimensions. The drain
connection to condensate trap must also be properly
sloped to an open drain.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2
or 11.)
NOTE: Combustion-air and vent pipes are restricted to a mini-
mum length of 5 ft. (See Table 6.)
NOTE: A 12-in. minimum offset pipe section is recommended
with short (5 to 8 ft) vent systems. This recommendation is to
reduce excessive condensate droplets from exiting the vent pipe.
(See Fig. 10 or 29.)
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
5. Install condensate trap into casing hole by inserting tube
connection stubs through casing hole and rotating until tabs
snap into locking position.
PLUG
CAP
COLLECTOR BOX
AUXILIARY "J" BOX
RELOCATED HERE
DRAIN TUBE
(BLUE AND WHITE STRIPED)
CONDENSATE
TRAP
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
COLLECTOR BOX
EXTENSION TUBE
DRAIN TUBE (VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR
BOX EXTENSION
DRAIN TUBE
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
040, 060, AND 080 HEATING INPUT FURNACES
A93353
Fig. 9—Horizontal Left Tube Configuration
—9—
Download from Www.Somanuals.com. All Manuals Search And Download.
COMBUSTION – AIR
INTAKE
VENT
A 12-IN. MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT) VENT SYSTEMS
TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
30″ MIN
WORK AREA
3
5 ⁄ ″
4
MANUAL
SHUTOFF
GAS VALVE
ACCESS OPENING
FOR TRAP
DRAIN
SEDIMENT
TRAP
CONDENSATE
TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
A93031
Fig. 10—Attic Location and Working Platform
B. Condensate Trap Tubing
3. Relief Port Tube
NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
Refer to Pressure Switch Tubing section for connection
procedure.
1. Collector Box Drain Tube
C. Condensate Trap Field Drain Attachment
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
Refer to Condensate Drain section for recommendations and
procedures.
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously con-
nected to condensate trap.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This tube MUST be dis-
connected and used for the condensate trap relief port tube. The
other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be
connected to the pressure switch in DOWNFLOW or HORIZON-
TAL RIGHT applications.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not
need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to conden-
sate trap.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached
to pressure switch.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
2. Extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connec-
tion by splicing to small diameter tube (factory-supplied in
loose parts bag).
d. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to conden-
sate trap.
3. Connect collector box pressure tube (green label) to pres-
sure switch connection labeled COLLECTOR BOX.
e. Determine appropriate length, cut, and connect tube to
condensate trap.
4. Use remaining small diameter tube (factory-supplied in
loose parts bag) to extend collector box pressure tube (pink
label) which was previously connected to pressure switch.
f. Clamp tube to prevent any condensate leakage.
—10—
Download from Www.Somanuals.com. All Manuals Search And Download.
COLLECTOR BOX DRAIN TUBE (BLUE)
CAP
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
PLUG
CONDENSATE
TRAP
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
A93354
Fig. 11—Horizontal Right Tube Configuration
5. Route this extended tube (pink label) to condensate trap
relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
LEVEL (0″)
FRONT
TO
FRONT
LEVEL (0″)
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
1⁄2″ MAX
TO
1⁄2″ MAX
F. Construct a Working Platform
UPFLOW OR DOWNFLOW
HORIZONTAL
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 10.)
A93025
NOTE: For proper furnace operation, install furnace so that it is
level or pitched forward within 1/2 in. to ensure proper condensate
drainage from secondary heat exchangers.
CAUTION: The condensate trap MUST be installed
below furnace. See Fig. 4 for dimensions. The drain
connection to condensate trap must also be properly
sloped to an open drain.
Locate furnace as close to center of air distribution system as
possible.
Locate furnace so combustion-air pipe lengths are not exceeded.
Refer to Table 6.
NOTE: Combustion-air and vent pipes are restricted to a mini-
mum length of 5 ft. (See Table 6.)
CAUTION: If these furnaces are used during construc-
tion when adhesives, sealers, and/or new carpets are
being installed, make sure all combustion and circulating
air requirements are followed. If operation of furnace is
required during construction, use clean outside air for
combustion and ventilation. Compounds of chlorine and
fluorine, when burned with combustion air, form acids
which will cause corrosion of heat exchangers. Some of
these compounds are found in paneling, dry wall adhe-
sives, paints, thinners, masonry cleaning materials, and
many other solvents commonly used in the construction
process.
NOTE: A 12-in. minimum offset pipe section is recommended
with short (5 to 8 ft) vent systems. This recommendation is to
reduce excessive condensate droplets from exiting the vent pipe.
(See Fig. 10 or 29.)
LOCATION
I. GENERAL
When a furnace is installed so that supply ducts carry air to areas
outside the space containing the furnace, return air must also be
handled by ducts sealed to furnace casing. The ducts terminate
outside the space containing the furnace to ensure there will not be
a negative pressure condition within equipment room or space.
Furnace may be located in a confined space without special
provisions for dilution or ventilation air. This furnace must be
installed so electrical components are protected from water.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
—11—
Download from Www.Somanuals.com. All Manuals Search And Download.
FRONT
°F
°F
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
RETURN
AIR
MAX 85°F MIN 55°F
A93042
NOTE: These furnaces are designed for a minimum continuous
return-air temperature of 60°F or intermittent operation down to 55°F
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F. Failure to follow
these return-air temperature limits may affect reliability of heat
exchangers, motors, and controls.
A93058
CAUTION: If these furnaces are installed in an uncon-
ditioned space where ambient temperatures may be 32°F
or lower, freeze protection measures must be taken.
II. LOW-FIRE ONLY INSTALLATION
Provide ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown on unit’s clear-
ance to combustibles label. (See Fig. 3.) Locate furnace where
available electric power and gas supplies meet specifications on
furnace rating plate.
This 355MAV furnace can be installed to operate in the low-fire
only heating mode when sized using the low-fire heating capacity.
This is accomplished by placing setup switch SW-2 in the ON
position to provide only low-fire-heat operation. See Fig. 25 and
Table 10. With this setup, high-fire operation will not occur.
When the model no. on the furnace rating plate is followed by an
asterisk (*), the furnace has an alternate low-fire only efficiency
rating as listed in the GAMA and CEC directories. This alternate
rating will be listed as the furnace model number followed by an
(-L) suffix.
FRONT
CAUTION: The furnace can operate in the high-fire
mode when certain fault conditions occur. The following
precautions should be taken:
1. Size gas piping based on the high-fire input.
2. Check the high-fire input and adjust it per the main
literature instructions.
B
A
C
K
BACK
NEVER assume the high-fire input rate is not important
for low-fire-only installation.
III. FURNACE LOCATION RELATIVE TO COOLING
EQUIPMENT
FRONT
A93043
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air must prevent chilled air from entering furnace.
If dampers are manually operated, they must be equipped with a
means to prevent operation of either unit unless damper is in
full-heat or full-cool position.
WARNING: Do not install furnace on its back. Safety
control operation will be adversely affected. Never con-
nect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.
—12—
Download from Www.Somanuals.com. All Manuals Search And Download.
IV. HAZARDOUS LOCATIONS
5⁄16″
5⁄16″
1 3⁄4″
1 3⁄4″
5⁄16″
18-IN. MINIMUM
TO BURNERS
A93044
5⁄16″
1 3⁄4″
1 3⁄4″
WARNING: When furnace is installed in a residential
garage, it must be installed so that burners and ignition
sources are located a minimum of 18 in. above floor. The
furnace must be located or protected to avoid physical
damage by vehicles. When furnace is installed in a public
garage, airplane hangar, or other building having a
hazardous atmosphere, unit must be installed in accor-
dance with requirements of National Fire Protection
Association, Inc.
A89014
Fig. 12—Leveling Legs
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1
and Fig. 13.
INSTALLATION
I. LEVELING LEGS (IF DESIRED)
3. Construct plenum to dimensions specified in Table 1 and
Fig. 13.
When furnace is used in upflow position with side inlet(s), leveling
legs may be desired. (See Fig. 12.) Install field-supplied,
corrosion-resistant 5/16-in. machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16-in.
diameter hole in each bottom corner of furnace. (See Fig.
12.) Holes in bottom closure panel may be used as guide
locations.
4. If downflow subbase (KGASB) is used, install as shown in
Fig. 14.
If coil assembly CD5 or CK5 or Coil Box KCAKC is used,
install as shown in Fig. 15.
NOTE: Remove furnace perforated, discharge duct flanges when
they interfere with mating flanges on coil on downflow subbase.
To remove furnace perforated, discharge duct flange, use wide
duct pliers or duct flange tool to bend flange back and forth until
it breaks off. Be careful of sharp edges. (See Fig. 16.)
2. For each hole, install nut on bolt and then install bolt and
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten
inside nut to secure arrangement.
WARNING: Do not bend duct flanges inward as shown
in Fig. 16. This will affect airflow across heat exchangers
and may cause limit cycling or premature heat exchanger
failure. Remove duct flange completely or bend it inward
a minimum of 210° as shown in Fig. 16.
NOTE: Bottom closure must be used when leveling legs are used.
See Bottom Closure Panel section.
II. INSTALLATION IN UPFLOW OR DOWNFLOW
APPLICATIONS
NOTE: This furnace is approved for use on combustible flooring
when special base (available from manufacturer) Part No.
KGASB0201ALL is used. Special base in not required when this
furnace is installed on manufacturer’s Coil Assembly Part No.
CD5 or CK5, or Coil Box Part No. KCAKC is used.
—13—
Download from Www.Somanuals.com. All Manuals Search And Download.
A
PLENUM
OPENING
B
D
FLOOR
OPENING
C
A96283
Fig. 13—Floor and Plenum Opening Dimensions
FURNACE
FURNACE
(OR COIL CASING
WHEN USED)
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
SHEET METAL
PLENUM
FLOOR
OPENING
FLOOR
OPENING
A96284
A96285
Fig. 15—Furnace, Plenum, and Coil
Assembly or Coil Box Installed
on a Combustible Floor
Fig. 14—Furnace, Plenum, and Subbase
Installed on a Combustible Floor
TABLE 1—OPENING DIMENSIONS (IN.)
FURNACE
CASING
WIDTH
PLENUM OPENING
FLOOR OPENING
APPLICATION
A
B
C
D
Upflow Applications
16
24-1/8
19
16-5/8
16-1/2
24-3/4
19-5/8
Downflow Applications on Non-Combustible Flooring
15-7/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
17-1/2
15-1/8
15-1/2
19
19
16-3/4
16-1/2
20-3/8
20
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications
19-1/2
19-3/8
24-1/8
19
20-1/8
20
24-3/4
19-5/8
Downflow Applications on Non-Combustible Flooring
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
21
18-5/8
19
19
19
20-1/4
20
20-3/8
20
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications
23
24-1/8
19
23-5/8
23-1/2
24-3/4
19-5/8
Downflow Applications on Non-Combustible Flooring
22-7/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
24-1/2
22-1/8
22-1/2
19
19
23-3/4
23-1/2
20-3/8
20
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
—14—
Download from Www.Somanuals.com. All Manuals Search And Download.
III. INSTALLATION IN HORIZONTAL APPLICATIONS
PERFORATED
DISCHARGE DUCT
FLANGE
These furnaces can be installed horizontally in either horizontal
left or right discharge position. In a crawlspace, furnace can either
be hung from floor joist or installed on suitable blocks or pad.
Furnace can be suspended from each corner by hanger bolts and
angle iron supports. (See Fig. 17.) Cut hanger bolts (4 each 3/8-in.
all-thread rod) to desired length. Use 1 X 3/8-in. flat washers,
3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in
Fig. 17. Dimples are provided for hole locations. (See Fig. 2.)
NO
YES
CAUTION: The entire length of furnace MUST be
supported when furnace is used in a horizontal position to
ensure proper draining. When suspended, bottom brace
supports sides and center blower shelf. When unit is
supported from the ground, blocks or pad should support
sides and center blower shelf area.
210°
MIN
YES
A93029
Fig. 16—Duct Flanges
3⁄8-IN. ROD
ANGLE
3
5 ⁄ ″
IRON OR
4
EQUIVALENT
ALTERNATE SUPPORT
LOCATION 4-IN. MIN
8-IN. MAX
(B)
(A)
DRAIN
(B)
(A)
(B)
(A) ROD LOCATION
USING DIMPLE
LOCATORS
13/16-IN. MAX
ALTERNATE SUPPORT
LOCATION FROM BACK
3/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
(A)
(B)
(SEE DIMENSIONAL
DWG FOR
LOCATIONS)
NOTES: 1. A 1 In. clearance minimum between top of
(A) PREFERRED ROD LOCATION
(B) ALTERNATE ROD LOCATION
furnace and combustible material.
2. The entire length of furnace must be
supported when furnace is used in horizontal
position to ensure proper drainage.
A93304
Fig. 17—Crawlspace Horizontal Application
—15—
Download from Www.Somanuals.com. All Manuals Search And Download.
IV. FILTER ARRANGEMENT
CAUTION: Never operate unit without a filter or with
blower access panel removed.
241⁄2-IN. WIDE
171⁄2-IN. WIDE
Factory-supplied washable framed filters are shipped in blower
compartment. Determine location for filter and relocate filter
retaining wire if necessary. See Table 2 to determine correct filter
size for desired filter location. Table 2 indicates filter size,
location, and quantity shipped with this furnace. See Fig. 2 for
location and size of bottom and side return-air openings.
CASINGS ONLY:
CUT AND FOLD
CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.
FACTORY-PROVIDED
FILTERS AS SHOWN
TO DESIRED SIZE.
3″
TABLE 2—FILTER INFORMATION
1
24 / ″
2
FURNACE
CASING
WIDTH (IN.)
FILTER SIZE (IN.)*
Side Return Bottom Return
FILTER TYPE
FRAMED
1″
17-1/2
21
(1) 16 X 25 X 1† (1) 16 X 25 X 1
(1) 16 X 25 X 1 (1) 20 X 25 X 1†
(2) 16 X 25 X 1† (1) 24 X 25 X 1
Cleanable
Cleanable
Cleanable
24-1/2
* Filters can be field modified by cutting frame as marked and folding to desired
size. Alternate sizes can be ordered from your distributor or dealer.
† Factory-provided with furnace.
CAUTION: Air delivery above 1800 CFM requires that
both sides, a combination of 1 side and bottom, or bottom
only of furnace be used for return air.
NOTE: Side return-air openings can ONLY be used in UPFLOW
configurations. Install filter(s) as shown in Fig. 18.
For bottom return-air applications, filter may need to be cut to fit
some furnace widths. Install filter as shown in Fig. 19.
NOTE: Remove and discard bottom closure panel when bottom
inlet is used.
WASHABLE
FILTER
V. BOTTOM CLOSURE PANEL
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when side
return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front
filler panel. (See Fig. 20.)
FILTER
RETAINER
FILTER
SUPPORT
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
A96030
4. Reinstall front filler panel and screws.
→ Fig. 19—Bottom Filter Arrangement
WASHABLE
FILTER
FILTER
RETAINER
BOTTOM
CLOSURE
PANEL
FRONT FILLER
PANEL
A93045
A93047
Fig. 18—Filter Installed for Side Inlet
Fig. 20—Removing Bottom Closure Panel
—16—
Download from Www.Somanuals.com. All Manuals Search And Download.
VI. GAS PIPING
GAS
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC. Canadian installations
must be made in accordance with NSCNGPIC and all authorities
having jurisdiction. Gas supply line should be a separate line
running directly from meter to furnace, if possible. Refer to Table
3 for recommended gas pipe sizing. Risers must be used to connect
to furnace and to meter. Support all gas piping with appropriate
straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint
compound (pipe dope) should be applied sparingly and only to
male threads of joints. Pipe dope must be resistant to propane gas.
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
TABLE 3—MAXIMUM CAPACITY OF PIPE*
NOMINAL
LENGTH OF PIPE (FT)
IRON
PIPE
SIZE
(IN.)
INTERNAL
DIAMETER
(IN.)
10
20
30
40
82
50
73
1/2
3/4
0.622
0.824
1.049
1.380
1.610
175
360
120
250
465
950
97
A93324
200
375
770
170 151
320 285
660 580
Fig. 21—Typical Gas Pipe Arrangement
1
680
1-1/4
1-1/2
1400
→ NOTE: The gas valve inlet press tap connection is suitable to use
as test gage connection providing test pressure DOES NOT exceed
maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 48.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before furnace has been attached.
In Canada, refer to current edition of NSCNGPIC. If pressure
exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected
from furnace and capped before pressure test. If test pressure is
equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff
switch located on gas valve before test. It is recommended that
ground joint union be loosened before pressure testing. After all
connections have been made, purge lines and check for leakage.
2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54-1996.
CAUTION: Connect gas pipe to furnace using a backup
wrench to avoid damaging gas controls.
→
WARNING: Gas valve shutoff switch MUST be facing
forward or tilted upward. Failure to follow this warning
could result in property damage or death.
ELECTRICAL CONNECTIONS
See Fig. 22 for field wiring diagram showing typical field 115-v
and 24-v wiring. Check all factory and field electrical connections
for tightness.
WARNING: Never purge a gas line into a combustion
chamber. Never use matches, candles, flame, or other
sources of ignition for purpose of checking leakage. Use
a soap-and-water solution to check for leakage. A failure
to follow this warning could result in fire, explosion,
personal injury, or death.
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Do not bypass or close switch with panel
removed. Failure to follow this warning could result in
personal injury or death.
WARNING: Use proper length of pipe to avoid stress on
gas control manifold. Failure to follow this warning could
result in a gas leak resulting in fire, explosion, personal
injury, or death.
CAUTION: Furnace control must be grounded for
proper operation or control will lock out. Control is
grounded through green wire routed to gas valve and
burner box screw.
Install a sediment trap in riser leading to furnace. Trap can be
installed by connecting a tee to riser leading to furnace so
straight-through section of tee is vertical. Then connect a capped
nipple into lower end of tee. Capped nipple should extend below
level of gas controls. Place a ground joint union between gas
control manifold and manual gas shutoff valve. (See Fig. 21.)
I. 115-V WIRING
Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility
is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 4 for equipment electrical specifications.
CAUTION: If a flexible connector is required or al-
lowed by authority having jurisdiction, black iron pipe
shall be installed at gas valve and extend a minimum of
2 in. outside furnace casing.
→ Make all electrical connections in accordance with NEC
ANSI/NFPA 70-1996 and any local codes or ordinances that might
apply. For Canadian installations, all electrical connections must
be made in accordance with Canadian Electrical Code CSA C22.1
or subauthorities having jurisdiction.
An accessible manual shutoff valve MUST be installed upstream
of furnace gas controls and within 6 ft of furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, MUST be
installed immediately upstream of gas supply connection to
furnace and downstream of manual shutoff valve.
Use a separate, fused branch electrical circuit containing a properly
sized fuse or circuit breaker for this furnace. See Table 4 for wire
size and fuse specifications. A disconnecting means must be
located within sight from and readily accessible to furnace.
—17—
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-, 208/230-, 460-VOLT WIRING
NOTE 5
THERMOSTAT
TERMINALS
W
C
R
G
Y
FIVE
WIRE
FIELD-SUPPLIED
FUSED DISCONNECT
THREE-WIRE
HEATING
ONLY
208/230- OR
460-VOLT
THREE
PHASE
W/W1
GND
GND
GND
115-VOLT
SINGLE
PHASE
NOTE
3
W2
R
208/230-
VOLT
SINGLE
PHASE
G
C
115-VOLT
FUSED
AUXILIARY
J-BOX
GND
NOTE 1
DISCONNECT
SWITCH
CONDENSING
UNIT
Y/Y2
(WHEN REQUIRED)
TWO WIRE
NOTES:
24-VOLT
TERMINAL
BLOCK
FURNACE
CONTROL
CENTER
1. Connect Y or Y/Y2 terminal as shown for proper cooling operation.
2. Proper polarity must be maintained for 115-volt wiring.
3. Use W2 with 2-stage thermostat when zoning.
4. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
5. Some thermostats require a "C" terminal connection as shown.
A96338
→ Fig. 22—Heating and Cooling Application Wiring Diagram
ELECTRIC
DISCONNECT
SWITCH
FACTORY
INSTALLED
LOCATION
ALTERNATE
FIELD
COPPER
LOCATION
WIRE ONLY
ALUMINUM
WIRE
A93033
CAUTION: Do not connect aluminum wire between
disconnect switch and furnace. Use only copper wire.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control center fault code indicator light will
flash rapidly and furnace will NOT operate.
A93051
Fig. 23—Relocating J-Box
→
WARNING: The cabinet MUST have an uninterrupted
or unbroken ground according to NEC ANSI/NFPA
70-1996 and Canadian Electrical Code CSA C22.1 or
local codes to minimize personal injury if an electrical
fault should occur. This may consist of electrical wire or
conduit approved for electrical ground when installed in
accordance with existing electrical codes. Do not use gas
piping as an electrical ground. Failure to follow this
warning could result in electric shock, fire, or death.
CAUTION: If manual disconnect switch is to be
mounted on furnace, select a location where a drill or
fastener will not contact electrical or gas components.
II. 24-V WIRING
Make field 24-v thermostat connections at 24-v terminal block on
control center. Y wire from thermostat MUST be connected to Y
terminal on control center, as shown in Fig. 22, for proper cooling
operation. The 24-v terminal board is marked for easy connection
of field wiring. (See Fig. 24.) The 24-v circuit contains a 3-amp,
automotive-type fuse located on control center. (See Fig. 25.) Any
electrical shorts of 24-v wiring during installation, service, or
maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp).
J-BOX RELOCATION
1. Remove 2 screws holding auxiliary J-box. (See Fig. 23.)
2. Rotate J-box 180° and attach box to right side, using holes
provided.
—18—
Download from Www.Somanuals.com. All Manuals Search And Download.
)
S E U D H E W ( N
P S L G
N
O R
L
Y E
Y A
F F O - D E L
E R W B L O
B L K
W H
S T . T E P M C O
M Z
A T . H E R E M
T
T
H
B P
E A H T W L O
F L T
L
Y E
W H
B L K
T
W H
B L K
R E
B R
D
N
D
T
R E
D
R E
B L K
W H
N
G R
N
N
L
B R
O R
Y E
T
W H
B L K
B L K
W H
G R
Y E
B R
O R
5 B L U
4 Y E
3 V I
R N 2 O
E D 1 R
T
N
L
N
N
B L U
L
O
C 2 E A
C 1 E A
T
W H
R E D
R E D
O R N O R N
V I O
Y E
V I O
Y E
B L
L
L
U
N
G R
U
B L
W H T
B L
W H T
B L
# 7 T E N O
N I D .
K
K
L
Y E
D
R E
—19—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 4—ELECTRICAL DATA
OPERATING
VOLTAGE RANGE
VOLTS—
HERTZ—
PHASE
MAXIMUM
UNIT
AMPS
MINIMUM
WIRE
SIZE
UNIT
SIZE
UNIT
AMPACITY†
MAXIMUM WIRE
LENGTH (FT)‡
MAXIMUM FUSE OR
CKT BKR AMPS**
Maximum*
127
Minimum*
104
042040
042060
042080
060080
060100
060120
115—60—1
115—60—1
115—60—1
115—60—1
115—60—1
115—60—1
8.9
8.9
12.0
12.0
12.0
17.9
18.1
15.3
14
14
14
12
12
12
31
31
31
32
32
37
15
15
15
20
20
20
127
104
127
104
8.9
127
104
13.8
13.8
11.6
127
104
127
104
* Permissible limits of voltage range at which unit will operate satisfactorily.
† Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time-delay fuse is recommended.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. For wire lengths over 100 ft, use AWG No.
16 wire.
NOTE: For 2-speed applications, refer to Sequence of Operation
section.
(4.) Insert stripped end into factory-supplied white
leads’s butt connector and crimp to secure.
NOTE: If desired, cut butt connectors off factory leads and strip
insulation approximately 1/4 in and use field-supplied wire nuts to
connect.
III. ACCESSORIES
b. An alternate method to attach EAC lead to control center
is the following procedure:
1. Electronic Air Cleaner (EAC)
The control center EAC terminals are energized with 115v
(1.5-amp maximum) during blower operation.
a. Two extension leads are connected to the control center
EAC terminals to assist field installation of an EAC. (See
Fig. 25.) To use these leads, proceed with the following:
(1.) Remove 2 screws securing the control box to
furnace blower shelf.
(2.) Remove and discard 2 factory-supplied leads from
control center EAC terminals.
(1.) Strip EAC power lead insulation approximately 1/4
in.
(3.) Strip EAC power leads insulation approximately
1/8 in.
(2.) Insert stripped end into factory-supplied black
lead’s butt connector and crimp to secure.
NOTE: The control center EAC terminals are sized for 12 gage
maximum, solid or stranded wire.
(3.) Strip EAC neutral lead insulation approximately 1/4
in.
(4.) Route EAC leads through right-hand wire grommet.
HOT SURFACE
IGNITOR CONNECTOR
EAC-ELECTRONIC AIR
CLEANER TERMINALS
(115-VAC 1 AMP MAX)
115-V
CONNECTORS
PRESSURE SWITCH
CONNECTOR
HUM-HUMIDIFIER
TERMINAL
(24-VAC 0.5 AMP MAX)
MAIN BLOWER
CONTROL WIRE
CONNECTOR
24-V THERMOSTAT
TERMINALS
TRANSFORMER
24-V CONNECTORS
DEHUMIDIFIER (DH)
CONNECTOR
3-AMP FUSE
STATUS AND DIAGNOSTIC
LED LIGHTS
AIR CONDITIONING
(A/C) SETUP SWITCH
SETUP SWITCHES
(SW) AND BLOWER
OFF DELAY SETUP
SWITCHES
CONTINUOUS
FAN (CF) SETUP
SWITCHES
MODEL PLUG
COMMUNICATION
CONNECTOR
A93062
Fig. 25—Control Center
—20—
Download from Www.Somanuals.com. All Manuals Search And Download.
connected to the venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they shall
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance shall
operate continuously.
EAC1
5. Test for draft hood equipped appliance spillage at the draft
hood relief opening after 5 minutes of main burner opera-
tion. Use the flame of a match or candle.
6. After it has been determined that each appliance connected
to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace damp-
ers, and any other gas-burning appliance to their previous
conditions of use.
EAC2
Fig. 26—EAC Terminals on Control Center
A93053
7. If improper venting is observed during any of above tests,
the venting system must be corrected.
(5.) Insert EAC stripped leads into control center EAC
terminals by depressing terminal’s arm with a
screwdriver or finger. (See Fig. 26.)
Vent system or vent connectors may need to be resized. For any
other appliances when resizing vent systems or vent connectors,
system or connector must be sized to approach minimum size as
determined using appropriate table found in the NFGC or NSC-
NGPIC.
(6.) Reinstall control box to furnace blower shelf using
2 screws removed earlier.
2. Humidifier (HUM)
II. COMBUSTION-AIR AND VENT PIPING
A. General
Screw terminals (HUM and COM) are provided for 24-v
humidifier connection. (See Fig. 24.) HUM terminal is
energized with 24v (0.5-amp maximum) after inducer
motor prepurge period.
Combustion-air and vent pipe fittings must conform to American
National Standards Institute (ANSI) standards and American
Society for Testing and Materials (ASTM) standards D1785
(schedule-40 PVC), D2665 (PVC-DWV), D2241 (SDR-21 and
SDR-26 PVC), D2661 (ABS-DWV), F628 (schedule-40 ABS), or
F891 (PVC-DWV cellular core). Pipe cement and primer must
conform to ASTM standards D2564 (PVC) or D2235 (ABS). See
Table 6 for maximum pipe lengths and Fig. 31, 32, 33, 34, and 35
for exterior piping arrangements.
NOTE: A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
3. Dehumidification (DH)
A 1/4-in. male quick-connect terminal is provided on
control center to attach a normally open (N/O) humidistat
contact when dehumidification is desired. (See Fig. 25.)
Connect humidistat to thermostat R terminal and DH
terminal on control center. A 15 percent reduction of
cooling airflow or constant fan airflow will occur when DH
terminal is energized and a single- or 2-speed "call for
cooling" is received.
In Canada, construct all combustion-air and vent pipes for this unit
of CSA or ULC certified schedule-40 PVC, PVC-DWV or
ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in
Canada.
NOTE: Furnace combustion-air and vent pipe connections are
sized for 2-in. pipe. Any pipe size change should be made outside
furnace casing in vertical pipe. (See Fig. 27.) This allows proper
drainage of vent condensate.
DIRECT VENTING
The 355MAV Furnaces require a dedicated (one 355MAV furnace
only) direct-vent system. In a direct-vent system, all air for
combustion is taken directly from outside atmosphere, and all flue
products are discharged to outside atmosphere.
Combustion-air and vent pipes must terminate together in same
atmosphere pressure zone, either through roof or sidewall (roof
termination preferred), using accessory termination kit. See Table
5 for required clearances.
I. REMOVAL OF EXISTING FURNACES FROM
COMMON VENT SYSTEMS
Furnace combustion-air and vent pipe connections must be at-
tached as shown in Fig. 28. Combustion-air intake plug fitting and
inducer housing alternate vent cap may need to be relocated in
some applications.
If furnace being replaced was connected to a common vent system
with other appliances, the following steps shall be followed with
each appliance connected to the venting system placed in opera-
tion, while any other appliances connected to the venting system
are not in operation:
CAUTION: When combustion-air pipe is installed
above a suspended ceiling, pipe must be insulated with
3/8-in. thick Armaflex-type insulation. Combustion-air
pipe should also be insulated when it passes through a
warm, humid space.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch as required in the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CGA B149 Installation Codes and these
instructions. Determine that there is no blockage or restric-
tion, leakage, corrosion, and other deficiencies which could
cause an unsafe condition.
CAUTION: When vent pipe is exposed to temperatures
below freezing, such as when it passes through an
unheated space or when a chimney is used as a raceway,
pipe must be insulated as shown in Table 7 with
Armaflex-type insulation.
3. If practical, close all building doors and windows and all
doors between the space in which the appliance(s) con-
nected to the venting system are located and other spaces of
the building. Turn on clothes dryers and any appliance not
—21—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 5—COMBUSTION-AIR AND VENT PIPE
TERMINATION CLEARANCES
NOTE: Select 1 vent pipe connection and NOTE: Select 1 vent pipe connection and
1 combustion-air pipe connection.
1 combustion-air pipe connection.
AIR
FLOW
CLEARANCE (FT)
LOCATION
COMBUSTION-
AIR
COMBUSTION-
AIR
U.S.A.
Canada
VENT
Above grade level or above antici-
pated snow depth
1
1†
VENT
VENT
Dryer vent
3
3
1
3
3
6
VENT
From plumbing vent stack
From any mechanical fresh air intake
For furnaces with an input capacity
less than 100,000 Btuh—from any
non-mechanical air supply (windows
or doors which can be opened) or
combustion-air opening
COMBUSTION-
AIR
COMBUSTION-
AIR
1
1
1
3
AIR
FLOW
UPFLOW
DOWNFLOW
For furnaces with an input capacity
greater than 100,000 Btuh—from any
non-mechanical air supply (windows
or doors which can be opened) or
combustion-air opening
COMBUSTION-
AIR
COMBUSTION-
AIR
VENT
VENT
From service regulator vent, electric
and gas meters, and relief equipment
4*
7
6‡
7
Above grade when adjacent to public
walkway
AIR
FLOW
AIR
FLOW
* Horizontal distance.
† 18 in. above roof surface in Canada.
‡ 36 in. to electric meter in Canada only.
NOTES:
1. If installing 2 adjacent 355MAV Furnaces, refer to Multiventing and Vent
Terminations section for proper vent configurations.
2. When locating combustion-air and vent terminations, consideration must be
given to prevailing winds, location, and other conditions which may cause
recirculation of the appliance’s own flue products or the flue products of
adjacent vents. Recirculation can cause poor combustion, inlet condensate
problems, and accelerated corrosion of heat exchangers.
HORIZONTAL-LEFT DISCHARGE
HORIZONTAL-RIGHT DISCHARGE
A96187
Fig. 28—Combustion-Air and Vent Pipe Connections
WARNING: Solvent cements are combustible. Keep
away from heat, sparks, and open flame. Use only in well
ventilated areas. Avoid breathing in vapor or allowing
contact with skin or eyes. Failure to follow this warning
could result in fire, property damage, personal injury, or
death.
FURNACE
NOT IN
HORIZONTAL
SECTION
PIPE DIAMETER
TRANSITION IN
WARNING: All combustion-air and vent pipes must be
airtight and watertight. Pipes must also terminate exactly
as shown in Fig. 31, 32, 33, 34, or 35. Failure to follow
this warning could result in property damage, personal
injury, or death.
VERTICAL SECTION
A93034
Fig. 27—Combustion-Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
NOTE: The minimum combustion-air and vent pipe length (each)
for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge
water droplets. These droplets may be undesirable, and a 12-in.
minimum offset pipe section is recommended, as shown in Fig. 29,
to reduce excessive droplets from exiting vent pipe outlet.
CAUTION: Combustion air must not be taken from
inside structure because that air is frequently contami-
nated by halogens, which include fluorides, chlorides,
bromides, and iodides. These elements are found in
aerosols, detergents, bleaches, cleaning solvents, salts, air
fresheners, adhesives, paint, and other household prod-
ucts. Locate combustion-air inlet as far as possible from
swimming pool and swimming pool pump house.
B. Combustion-Air and Vent Pipe Diameter
Determine combustion-air and vent pipe diameter.
1. Using Table 6, individually determine the combustion-air
and vent pipe diameters. Pick the larger of these 2 pipe
diameters and use this diameter for both combustion-air and
vent pipes.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
2. When installing vent systems of short pipe length, use the
smallest allowable pipe diameter. Do not use pipe size
greater than required or incomplete combustion, flame
disturbance, or flame sense lockout may occur.
NOTE: Do not count elbows or pipe sections in terminations or
within furnace. See shaded areas in Fig. 31, 32, 33, 34, and 35.
—22—
Download from Www.Somanuals.com. All Manuals Search And Download.
b. Reposition combustion-air intake housing plug fitting in
appropriate unused intake housing connection.
EXAMPLE:
An 042080 size furnace located in Indianapolis, elevation
650 ft above sea level, could be installed in an application
requiring 3 elbows and 17 ft of vent pipe, along with 5
elbows and 16 ft of combustion-air pipe. Table 6 indicates
this application would allow a 1-1/2-in. diameter vent pipe,
but require a 2-in. diameter combustion air pipe (1-1/2-in.
pipe is good for 20 ft with 3 elbows, but only 10 ft with 5
elbows). Therefore, 2-in. diameter pipe must be used for
both vent and combustion-air pipes since larger required
diameter must always be used for both pipes. If same
installation were in Albuquerque, elevation 5250 ft above
sea level, installation would require 2-in. vent pipe and
combustion-air pipe. At 5001- to 6000-ft elevation, 1-1/2-
in. pipe is not allowed with 5 elbows, but 2-in. pipe is good
for 68 ft with 5 elbows.
c. Insert perforated disk assembly (factory supplied) in
intake housing where combustion-air intake pipe will be
connected.
d. Install pipe support (factory-supplied in loose parts bag)
into selected furnace casing combustion-air pipe hole.
Pipe support should be positioned to bottom of casing
hole.
e. Insert 2-in. diameter pipe into intake housing.
NOTE: A 2-in. diameter pipe must be used within the furnace
casing. Make all pipe diameter transitions outside furnace casing.
f. Drill a 1/8-in. hole in 2-in. combustion-air pipe using
hole in intake housing as a guide.
g. Install a field-supplied No. 6 or No. 8 sheet metal screw
into combustion-air pipe.
C. Combustion-Air and Vent Pipe Attachment
NOTE: All pipe joints must be watertight except attachment of
combustion-air pipe to inlet housing connection since it may be
necessary to remove pipe for servicing.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage to intake
housing or fitting may cause air leakage to occur.
NOTE: Do not attach combustion-air intake pipe permanently to
combustion-air intake housing since it may be necessary to remove
pipe for service of ignitor or flame sensor.
1. Attach combustion-air pipe as follows:
a. Determine location of combustion-air intake pipe con-
nection to combustion-air intake housing as shown in
Fig. 28 for application.
12″ MIN
12″ MIN
VENT PIPE
VENT PIPE
COMBUSTION-AIR PIPE
COMBUSTION-AIR PIPE
HORIZONTAL TO ROOF
HORIZONTAL TO SIDEWALL
COMBUSTION-AIR PIPE
VENT PIPE
COMBUSTION-AIR PIPE
12″ MIN
12″ MIN
VENT PIPE
VERTICAL TO ROOF
VERTICAL TO SIDEWALL
NOTE: A 12 In. minimum offset pipe section is recommended with
short (5 to 8 ft) vent systems. This recommendation is to reduce
excessive condensate droplets from exiting the vent pipe.
A96230
Fig. 29—Short Vent (5 to 8 Ft) System
—23—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 6—MAXIMUM ALLOWABLE PIPE LENGTH (FT)
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
6
1-1/2
2
50
70
50
70
30
70
45
70
10
35
70
45
70
45
70
25
70
40
70
NA
30
70
40
70
40
70
20
70
35
70
NA
15
70
35
70
35
70
15
70
30
70
NA
NA
70
30
70
30
70
10
70
25
70
NA
NA
70
25
70
25
70
5
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
0 to 2000
70
20
70
NA
NA
70
2
2 Pipe or 2-In.
Concentric
060100
2-1/2
2-1/2
3
2 Pipe or 3-In.
Concentric
060120
3†
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
25
70
25
70
6
6
1-1/2
2
45
70
45
70
26
70
40
70
31
63
40
70
40
70
21
70
35
70
26
62
35
70
35
70
16
70
30
70
12
62
30
70
30
70
11
70
25
70
NA
61
20
70
20
70
NA
70
15
70
NA
61
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
2001 to 3000
70
20
70
NA
61
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
3
2 Pipe or 3-In.
Concentric
3†
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
22
70
22
70
5
6
1-1/2
2
42
70
42
70
25
70
38
70
29
59
37
70
37
70
20
70
33
70
24
59
32
70
32
70
15
70
28
70
10
58
27
70
27
70
10
70
23
70
NA
57
17
70
17
70
NA
70
13
70
NA
56
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
3001 to 4000
70
18
70
NA
57
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
3
2 Pipe or 3-In.
Concentric
3†
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
6
1-1/2
2
40
70
40
70
23
70
36
70
35
70
35
70
18
70
31
70
30
70
30
70
13
70
26
70
25
70
25
70
8
20
70
20
70
NA
70
16
70
15
70
15
70
NA
68
11
70
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
4001 to 5000‡
70
21
70
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
2 Pipe or 3-In.
Concentric
3†
56
55
54
53
52
52
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
6
12
70
12
70
NA
63
8
1-1/2
2
37
70
37
70
22
70
33
70
32
70
32
70
17
70
28
70
27
70
27
70
12
70
23
70
22
70
22
70
7
17
70
17
70
NA
68
13
70
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
5001 to 6000‡
70
18
70
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
70
2 Pipe or 3-In.
Concentric
3†
53
52
50
49
48
47
See notes on next page.
—24—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 6—MAXIMUM ALLOWABLE PIPE LENGTH (FT) Continued
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
6
10
64
10
64
NA
57
6
1-1/2
2
35
70
35
70
20
70
31
70
30
70
30
70
15
70
26
70
25
68
25
68
10
68
21
68
20
67
20
67
5
15
66
15
66
NA
62
11
66
2 Pipe or 2-In.
Concentric
042040
042060
1-1/2
2
2 Pipe or 2-In.
Concentric
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
6001 to 7000‡
67
16
67
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
64
2 Pipe or 3-In.
Concentric
3†
49
48
47
45
44
43
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
12
60
12
60
NA
57
9
6
7
1-1/2
2
32
66
32
66
18
66
29
66
27
65
27
65
13
65
24
65
22
63
22
63
8
17
62
17
62
NA
62
14
62
2 Pipe or 2-In.
Concentric
042040
042060
59
7
1-1/2
2
2 Pipe or 2-In.
Concentric
59
NA
52
NA
59
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
7001 to 8000‡
63
19
63
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
60
2 Pipe or 3-In.
Concentric
3†
46
44
43
41
40
38
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
5
10
55
10
55
NA
51
7
6
5
1-1/2
2
30
62
30
62
17
62
27
62
25
60
25
60
12
60
22
60
20
58
20
58
7
15
56
15
56
NA
56
12
56
2 Pipe or 2-In.
Concentric
042040
042060
53
5
1-1/2
2
2 Pipe or 2-In.
Concentric
53
NA
46
NA
53
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
8001 to 9000‡
58
17
58
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
55
2 Pipe or 3-In.
Concentric
3†
43
41
39
37
35
34
NUMBER OF 90° ELBOWS
UNIT
SIZE
TERMINATION
TYPE
PIPE DIAMETER
(IN.)*
ALTITUDE
1
2
3
4
12
51
12
51
NA
51
9
5
7
6
1-1/2
2
27
57
27
57
15
57
24
57
22
55
22
55
10
55
19
55
17
53
17
53
5
NA
47
NA
47
NA
41
NA
47
2 Pipe or 2-In.
Concentric
042040
042060
49
7
1-1/2
2
2 Pipe or 2-In.
Concentric
49
NA
46
NA
49
1-1/2
2
042080
060080
2 Pipe or 2-In.
Concentric
9001 to 10000‡
53
14
53
2
2 Pipe or 2-In.
Concentric
060100
060120
2-1/2
51
2 Pipe or 3-In.
Concentric
3†
39
37
35
33
31
29
* Disk usage—Unless otherwise stated, use perforated disk assembly (factory-supplied in loose parts bag).
† Wide radius elbow.
‡ Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA—Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
—25—
Download from Www.Somanuals.com. All Manuals Search And Download.
COMBUSTION-AIR INTAKE HOUSING PLUG
FITTING
WARNING: Vent pipe must be installed and fully
seated against inducer housing. Clamp must be tightened
to prevent any condensate leakage. Failure to follow this
warning could result in electrical shock, fire, personal
injury, or death.
The combustion-air intake plug fitting must be installed in
unused combustion-air intake housing. This fitting must be
attached by using RTV sealant, or by drilling a 1/8-in. hole
in fitting, using hole in intake housing as a guide. Install a
field-supplied No. 6 or No. 8 sheet metal screw.
NOTE: A 2-in. diameter pipe must be used within the furnace
casing. Make all pipe diameter transitions outside furnace casing.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage to intake
housing or fitting may cause air leakage to occur.
3. Working from furnace to outside, cut pipe to required
length(s).
A plugged drain connection has been provided on this
fitting for use when moisture is found in combustion-air
intake pipe and combustion box.
4. Deburr inside and outside of pipe.
5. Chamfer outside edge of pipe for better distribution of
primer and cement.
NOTE: Moisture in combustion-air intake may be result of
improper termination. Ensure combustion-air intake pipe is similar
to that shown in Fig. 31, 32, 33, 34, or 35 so it will not be
susceptible to areas where light snow or other sources of moisture
could be pulled in.
6. Clean and dry all surfaces to be joined.
7. Check dry fit of pipe and mark insertion depth on pipe.
NOTE: It is recommended that all pipes be cut, prepared, and
preassembled before permanently cementing any joint.
If use of this drain connection is desired, drill out fitting’s
tap plug with a 3/16-in. drill and connect a field-supplied
3/8-in. tube. This tube should be routed to open condensate
drain for furnace and A/C (if used), and should be trapped.
(See Fig. 30.)
8. After pipes have been cut and preassembled, apply gener-
ous layer of cement primer to pipe fitting socket and end of
pipe to insertion mark. Quickly apply approved cement to
end of pipe and fitting socket (over primer). Apply cement
in a light, uniform coat on inside of socket to prevent
buildup of excess cement. Apply second coat.
COMBUSTION – AIR
INTAKE HOUSING
9. While cement is still wet, twist pipe into socket with 1/4
turn. Be sure pipe is fully inserted into fitting socket.
3/8" ID TUBE
BURNER
BOX
10. Wipe excess cement from joint. A continuous bead of
cement will be visible around perimeter of a properly made
joint.
11. Handle pipe joints carefully until cement sets.
3/16"
12. Support combustion-air and vent piping a minimum of
every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated
metal hanging strap.
DRILL
COMBUSTION –
AIR PIPE
4″
MIN
13. Slope combustion-air and vent pipes toward furnace a
minimum of 1/4 in. per linear ft with no sags between
hangers.
TRAP
TO OPEN
DRAIN
14. Use appropriate methods to seal openings where vent and
combustion-air pipes pass through roof or sidewall.
A93035
Fig. 30—Intake Housing Plug Fitting Drain
III. CONCENTRIC VENT AND COMBUSTION-AIR
TERMINATION KIT INSTALLATION
NOTE: If these instructions differ from those packaged with
termination kit, follow kit instructions.
2. Attach vent pipe as follows:
a. Determine location of vent pipe connection to inducer
housing as shown in Fig. 28 for application.
Combustion-air and vent pipes must terminate outside structure. A
factory accessory termination kit must be installed in 1 of the
installations shown in Fig. 31, 32, 33, 34, or 35. Four termination
kits are available.
b. Reposition neoprene inducer housing outlet cap and
clamp to appropriate unused inducer housing connec-
tion. Tighten clamp.
1. The 2-in. termination bracket kit is for 1-in., 1-1/2 in., and
2-in. diameter 2-pipe termination systems.
WARNING: Inducer housing outlet cap must be in-
stalled and fully seated against inducer housing. Clamp
must be tightened to prevent any condensate leakage.
Failure to follow this warning could result in electrical
shock, fire, personal injury, or death.
2. The 3-in. termination bracket kit is for 2-1/2 in. and 3-in.
diameter 2-pipe termination systems.
3. The 2-in. concentric vent/air termination kit is for 1-in.,
1-1/2 in., 2-in., and 2-1/2 in. diameter pipe systems when
single penetration of wall or roof is desired.
4. The 3-in. concentric vent/air termination kit is for 2-1/2 in.
and 3-in. diameter pipe systems when single penetration of
wall or roof is desired.
c. Install pipe support (factory-supplied in loose parts bag)
into selected furnace casing vent pipe hole. Pipe support
should be positioned to bottom of casing hole.
NOTE: Shaded parts in Fig. 31, 32, 33, 34, and 35 are considered
to be terminations. These components should NOT be counted
when determining pipe diameter. Roof termination is preferred
since it is less susceptible to damage, has reduced chances to intake
d. Insert 2-in. diameter pipe into inducer housing through
neoprene coupling and clamp in inducer housing.
Tighten clamp.
—26—
Download from Www.Somanuals.com. All Manuals Search And Download.
ROOF
18″ MAXIMUM
BRACKET
COUPLING
COMBUSTION
AIR
VERTICAL SEPARATION
BETWEEN COMBUSTION
AIR AND VENT
3
VENT
8
6
/ ″ FOR 3″ KIT
4
3
/ ″ FOR 2″ KIT
4
MAINTAIN 12 IN. MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24 IN. ABOVE ROOF.
A87224
Fig. 31—Roof Termination (Preferred)
OVERHANG OR ROOF
12″ MINIMUM
1″ MAXIMUM
VENT
COMBUSTION-AIR
VENT
COMBUSTION
AIR
MAINTAIN 12 IN.
MAINTAIN 12 IN.
CLEARANCE
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
A93055
A93054
Fig. 33—Concentric Vent and Combustion-Air Side
Termination
Fig. 32—Concentric Vent and Combustion-Air Roof
Termination (Preferred)
OVERHANG OR ROOF
OVERHANG OR ROOF
12″ MINIMUM
12″ MINIMUM
VENT
VENT
90°
90°
BRACKET
BRACKET
COUPLING
12 IN. SEPARATION
12 IN. SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT
MAINTAIN 12 IN.
CLEARANCE
MAINTAIN 12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
COMBUSTION-AIR
(ELBOW PARALLEL
TO WALL)
COMBUSTION-AIR
WHICHEVER IS
GREATER.
A87225
A87226
Fig. 34—Sidewall Termination of 12 in. or More
Fig. 35—Sidewall Termination of Less than 12 in.
—27—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 7—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN WINTER DESIGN
TEMPERATURE AMBIENT*
WINTER DESIGN
TEMPERATURE
(°F)
MAXIMUM PIPE
DIAMETER
(IN.)
INSULATION THICKNESS (IN.)†
UNIT
SIZE
0
3/8
1/2
3/4
1
20
0
2
21
10
5
37
22
14
55
33
23
65
39
27
70
42
28
70
51
35
42
25
17
61
38
26
70
45
31
70
48
33
70
58
40
50
30
21
70
46
33
70
55
39
70
59
41
70
70
50
57
35
25
70
53
38
70
63
45
70
68
49
70
70
59
042040
042060
2
-20
20
0
2
2
30
16
9
2
-20
20
0
2
2
2
37
20
11
41
21
11
49
26
15
042080
060080
-20
20
0
2
2-1/2
2-1/2
2-1/2
3
060100
060120
-20
20
0
3
-20
3
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as
specified in Table 6.
† Insulation thickness based on R value of 3.5 per in.
contaminants, and has less visible vent vapors. (See Fig. 31 or 32.)
Sidewall termination may require sealing or shielding of building
surfaces with a corrosive resistance material due to corrosive
combustion products of vent system.
Roof terminations—Loosely install pipe coupling on prop-
erly cut vent pipe. Coupling must be positioned so bracket
will mount as shown in Fig. 31.
For applications using combustion-air pipe option indicated
by dashed lines in Fig. 31, install 90° street elbow into 90°
elbow, making U-fitting. A 180° U-fitting may be used.
A. Extended Exposed Sidewall Pipes
Sidewall combustion-air and vent pipe terminations may be
extended beyond area shown in Fig. 34 or 35 in outside ambient by
insulating pipes as indicated in Table 7.
Sidewall terminations—Install bracket as shown in Fig. 34
or 35.
1. Determine combustion-air and vent pipe diameters, as
stated above, using total pipe length and number of elbows.
For applications using vent pipe option indicated by dashed
lines in Fig. 34, rotate vent elbow 90° from position shown
in Fig. 34.
2. Using winter design temperature (used in load calculations),
find appropriate temperature for your application and fur-
nace model.
4. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
3. Determine required insulation thickness for exposed pipe
lengths.
5. Check required dimensions as shown in Fig. 31, 34, or 35.
C. Concentric Vent/Air Termination Kit
1. Determine location for termination.
NOTE: Pipe length (ft) specified for maximum pipe lengths
located in unconditioned spaces cannot exceed total allowable pipe
length as specified in Table 6.
Consideration of the following should be made when
determining an appropriate location for termination kit.
B. Two-Pipe Termination Kit
1. Determine location for termination.
a. Comply with all clearance requirements as stated in
Table 5.
Consideration of the following should be made when
determining an appropriate location for termination kit.
b. Termination kit should be positioned where vent vapors
will not damage plants/shrubs or air conditioning equip-
ment.
a. Comply with all clearance requirements as stated in
Table 5.
b. Termination kit should be positioned where vent vapors
will not damage plants/shrubs or air conditioning equip-
ment.
c. Termination kit should be positioned so it will not be
affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.
c. Termination kit should be positioned so it will not be
affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.
d. Termination kit should be positioned where it will not be
damaged by or subjected to foreign objects, such as
stones, balls, etc.
d. Termination kit should be positioned where it will not be
damaged by or subjected to foreign objects, such as
stones, balls, etc.
e. Termination kit should be positioned where vent vapors
are not objectionable.
2. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in.
diameter hole for 3-in. kit.
e. Termination kit should be positioned where vent vapors
are not objectionable.
3. Loosely assemble concentric vent/air termination compo-
nents together using instructions in kit.
2. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size
being used.
3. Loosely install elbow in bracket and place assembly on
combustion-air pipe.
4. Slide assembled kit with rain shield REMOVED through
hole.
—28—
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
Roof terminations—Locate assembly through roof to ap-
propriate height as shown in Fig. 32.
Sidewall terminations—Locate assembly through sidewall
with rain shield positioned no more than 1-in. from wall as
shown in Fig. 33.
5. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
6. Check required dimensions as shown in Fig. 32 or 33.
IV. MULTIVENTING AND VENT TERMINATIONS
When 2 or more 355MAV Furnaces are vented near each other,
each furnace must be individually vented. NEVER common vent
or breach vent 355MAV furnaces. When 2 or more 355MAV
furnaces are vented near each other, 2 vent terminations may be
installed as shown in Fig. 36, 37, 38, 39, or 40, but next vent
termination must be at least 36 in. away from first 2 terminations.
It is important that vent terminations be made as shown to avoid
recirculation of flue gases. Dimension "A" in Fig. 36, 37, 38, 39,
and 40 represents distance between pipes or rain shields, as
touching or 2-in. maximum separation.
A93058
CAUTION: Unit must not be installed, operated, and
then turned and left off in an unoccupied structure during
cold weather when temperature drops to 32°F or below
unless drain trap and drain line have adequate freeze
protection. See Service and Maintenance Procedures for
winterizing procedure.
CONDENSATE DRAIN
I. GENERAL
Condensate trap is shipped installed in the blower shelf and factory
connected for UPFLOW applications. Condensate trap must be
RELOCATED for use in DOWNFLOW and HORIZONTAL
applications.
Outdoor draining of the furnace is permissible if allowed by local
codes. Caution should be taken when freezing ambient may freeze
drain pipe and prohibit draining.
Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain to
this condensate trap.
WARNING: Caution should be taken to prevent drain-
ing where slippery conditions may cause personal inju-
ries. Excessive condensate draining may cause saturated
soil conditions which may result in damage to plants.
The field drain connection (condensate trap or drain tube coupling)
is sized for 1/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube
connection.
Drain pipe and fittings must conform to ANSI standards and
ASTM D1785 or D2846. CPVC or PVC cement and primer must
conform to ASTM D2564 or F493. In Canada, use CSA or ULC
certified schedule 40 CPVC or PVC drain pipe, fittings, and
cement.
III. CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may
cause cracks, and possible water damage may occur. If freeze
protection is required, use condensate freeze protection accessory
or equivalent 3 to 6 watt per ft at 120v and 40°F self-regulating,
shielded, and waterproof heat tape. See Installation Instructions
supplied with accessory or heat tape manufacturer’s recommenda-
tions.
When a condensate pump is required, select a pump which is
approved for condensing furnace applications. To avoid conden-
sate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a condensate
pH neutralizing filter may be desired. Check with local authorities
to determine if a pH neutralizer is required.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back.
(See Fig. 42.)
II. APPLICATION
3. Use wire ties to secure heat tape in place. Wire ties can be
positioned in notches of condensate trap sides. (See Fig.
42.)
The furnace, A/C, and humidifier drains may be combined and
drained together. The A/C drain must have an external, field-
supplied trap prior to the furnace drain connection. All drain
connections (furnace, A/C, or humidifier) must be terminated into
an open or vented drain as close to the respective equipment as
possible to prevent siphoning of the equipment’s drain.
4. Wrap field drain pipe with remaining heat tape, approxi-
mately 1 wrap per ft.
5. When using field-supplied heat tape, follow heat tape
manufacturer’s instructions for all other installation guide-
lines.
See Fig. 41 for example of possible field drain attachment using
1/2-in. CPVC or PVC tee for vent and A/C or humidifier drain
connection.
—29—
Download from Www.Somanuals.com. All Manuals Search And Download.
A
A96128
Fig. 36—Rooftop Termination (Dimension "A" is Touching or 2-In. Maximum Separation)
1″ MAXIMUM
(TYP)
VENT
VENT
A
COMBUSTION AIR
VENT
COMBUSTION
AIR
A
VENT
A93056
A93057
Fig. 37—Concentric Vent and Combustion-Air Roof
Termination (Dimension "A" is Touching or
2-In. Maximum Separation)
Fig. 38—Concentric Vent and Combustion-Air Side
Termination (Dimension "A" is Touching or
2-In. Maximum Separation)
VENT
VENT
COMBUSTION AIR
COMBUSTION AIR
COMBUSTION AIR
COMBUSTION AIR
A
A
A96129
A96130
Fig. 39—Sidewall Termination of 12 in. or Less
(Dimension "A" is Touching or 2-In.
Maximum Separation)
Fig. 40—Sidewall Termination of More Than 12 in.
(Dimension "A" is Touching or 2-In.
Maximum Separation)
—30—
Download from Www.Somanuals.com. All Manuals Search And Download.
I. SELF-TEST MODE
The control center goes through a brief self-test whenever 115-v or
24-v power is interrupted. The self-test takes approximately 2 sec
to complete. After power is restored, red (microprocessor) LED
briefly comes on. Then green LED comes on for 1 sec, followed by
1 sec where both yellow and green LEDs are on. During this time,
the microprocessor is checking itself.
II. HEATING MODE
When thermostat calls for heat, R-W/W1 circuit closes.
OPEN STAND
PIPE FOR
A/C OR
1. Prepurge period—The inducer motor is turned on and
slowly comes up to speed. When low-pressure switch
closes, inducer motor RPM is noted by microprocessor, and
a 25 sec prepurge period begins. The RPM is used to
evaluate vent system resistance. This evaluation is then
used to determine required RPM necessary to operate
inducer in low-heat mode.
HUMIDIFIER
DRAIN
TEE
NOTE: The heat cycle can start in either high or low heat. If a
high-heat cycle is initiated, the inducer continues increasing its
speed after low-pressure switch closes. When high-pressure switch
closes, inducer motor RPM is noted by microprocessor before the
25 sec prepurge period begins. The RPM is used to evaluate vent
system resistance. This evaluation is then used to determine
required RPM necessary to operate inducer in high-heat mode.
TO OPEN
DRAIN
2. Humidifier (HUM)—The HUM terminal is energized after
the inducer prepurge period is completed.
A94054
3. Ignitor warm up—At end of prepurge period, the hot
surface ignitor (HSI) is energized for a 17-sec HSI warm-up
period.
Fig. 41—Example of Field Drain Attachment
4. Ignition sequence—After HSI ignitor warm-up period is
completed, the gas valve opens, permitting gas flow to
burners where it is ignited. After 5 sec, the HSI is
de-energized, and a 2-sec flame-sensing period begins.
CONDENSATE TRAP
NOTE: The initial heat mode after 115-v or 24-v power interrup-
tion will be LOW HEAT. Low heat remains energized for 16
minutes before high heat is initiated, providing thermostat is still
calling for heat.
After initial cycle, the microprocessor evaluates the length of low-
and high-heat operating times and calculates optimum length of
low and high heat for next heat cycle. This accommodates the heat
load requirement seen as a result of thermostat operating time.
WIRE TIE(S)
5. Flame sensing—When burner flame is sensed, the control
center holds gas valve open and begins blower on delay
period.
HEAT TAPE
(3 WRAPS MINIMUM)
NOTE: Ignition sequence repeats 3 additional times before a
lockout occurs. Lockout automatically resets after 3 hr, or can be
manually reset by turning 115-v or 24-v power off (not at
thermostat) for 3 sec minimum, then turning on again.
6. Inducer speed operation—If cycle starts in low heat,
inducer speed reduces slightly after flame sense. If cycle
starts in high heat, inducer speed increases 15 sec after
flame sense. The reduction in speed in low heat is to
optimize combustion for maximum efficiency.
A93036
Fig. 42—Condensate Trap Heat Tape
SEQUENCE OF OPERATION
7. Blower on delay—The blower starts 60 sec after flame
sense if cycle started in low heat or 35 sec after flame sense
if cycle started in high heat.
CAUTION: Furnace control must be grounded for
proper operation, or control will lock out. Control is
grounded through green wire routed to gas valve and
burner box screw.
NOTE: The blower starts at approximately 400-500 RPM. After
20 sec, the motor is turned off for 1/10 of a sec where a coast down
calibration is done to evaluate resistance of the conditioned air
duct system. The microprocessor then determines blower RPM
required to provide proper airflow for heating mode.
Using schematic diagram (see Fig. 24), follow sequence of
operation through different modes. This furnace has a new control
system. Read and follow wiring diagram carefully.
8. Electronic Air Cleaner—The EAC-1 terminal is energized
whenever the blower operates.
NOTE: If 115-v power supply to furnace or blower access panel
switch is interrupted during a call for heat, blower operates at
low-heat speed for 60 sec when power is restored before heating
cycle is resumed.
9. Blower off delay—When thermostat is satisfied, the
R-W/W1 signal is terminated, de-energizing gas valve
(stopping gas flow to burners), and HUM terminal is
de-energized.
—31—
Download from Www.Somanuals.com. All Manuals Search And Download.
The blower reduces its speed to low-heat RPM. The blower
and EAC remain operating 90, 135, 180, or 225 sec
(depending on blower off time selection). The furnace is
factory set for a 90-sec blower off delay.
NOTE: Ignition sequence repeats 3 additional times before lock-
out occurs. Lockout automatically resets after 3 hr, or can be
manually reset by turning 115-v or 24-v power off (not at
thermostat) for 3 sec minimum, then turning on again. Fault codes
will not flash in emergency heat mode.
10. Post purge—The inducer continues operating for 15 sec
after gas valve is de-energized.
8. Blower off delay—When thermostat is satisfied, the
R-W/W1 signal is terminated, de-energizing gas valve
(stopping gas flow to burners), and HUM terminal is
de-energized. The blower stops immediately.
III. HEATING MODE—TWO STAGE
The control center provides 2-stage heating using a single-stage
thermostat. The control center maximizes comfort while optimiz-
ing efficiency to meet the demands of conditioned area when a
thermostat R-W/W1 signal is received.
9. Post purge—Post purge does NOT occur. The inducer
stops immediately.
If thermostat control over furnace staging is desired, a 2-stage
thermostat can be used. When control center receives a thermostat
R-W/W1 and R-W2 signal, high heat is energized and when a
R-W/W1 signal alone is received, low heat is energized. This
method overrides microprocessor control of high or low heat.
V. COOLING MODE
A. Single-Speed Applications
When thermostat calls for cooling, the R-G and R-Y/Y2 circuits
close.
NOTE: When using 2-stage thermostat operation with R-W/W1
and R-W2 signals, setup switch SW-2 MUST be in ON position.
1. Cooling unit—The cooling unit starts when thermostat
R-Y signal is received.
The heat cycle operates as stated in Heating Mode section.
2. Blower on—The control center starts blower immediately
when it receives an R-Y/Y2 and R-G signal. The blower
starts at approximately 400-500 RPM. After 20 sec, the
blower is turned off for 1/10 of a sec where a coast down
calibration is done to evaluate resistance of the conditioned
air duct system. The microprocessor then determines
blower RPM required to provide selected cooling airflow.
To allow for greater comfort, 2-stage thermostat control is recom-
mended when zone systems are used.
IV. EMERGENCY HEAT MODE
NOTE: The furnace should not be operated in emergency heat
mode for extended periods of time. Operation is only recom-
mended to provide heat until replacement components can be
obtained or fault resolved.
NOTE: In cooling mode, the microprocessor adjusts blower RPM
to operate at 400 CFM per ton as selected on A/C setup switches.
See Air Conditioning Setup Switches section. There is also a chart
on wiring diagram. (See Fig. 24.)
In this mode, the microprocessor is bypassed and motors operate at
full speed with high-heat operation. The heat exchangers, motors,
and electronics can be overstressed and may reduce the life of
components if operated for an extended period.
NOTE: If Y/Y2 thermostat lead is not connected to furnace
control center, blower motor operates in continuous fan speed and
indoor coil freeze-up may occur.
NOTE: No safeties are bypassed when using emergency heat
mode.
3. Electronic Air Cleaner—The EAC-1 terminal is energized
Emergency heat mode can be selected using setup switch SW-4.
SW-4 should be used when a fault condition exists or difficult to
resolve problems occur. This allows heating until fault can be
corrected.
whenever blower operates.
4. Cooling unit—The cooling unit stops when thermostat R-Y
signal is terminated.
In emergency heat mode, the normal heat mode outlined in
Heating Mode section is not followed. The following sequence
will occur:
5. Blower off delay—When thermostat is satisfied, the
R-Y/Y2 and R-G signals are terminated, and blower re-
mains operating for 90 sec.
When thermostat calls for heat, the R-W/W-1 circuits close.
B. Two-Speed Applications
1. Prepurge period—The inducer motor is turned on IMME-
DIATELY operating at maximum speed, closing low- and
high-pressure switches. Prepurge begins 25 sec after high-
pressure switch closes.
For details on 2-speed cooling applications, refer to Fig. 43.
VI. HEAT PUMP MODE
A. Single-Speed Applications
2. Blower on—The blower motor is turned on IMMEDI-
ATELY and slowly increases to maximum speed as soon as
a call for heat is received. No blower calibration occurs.
When furnace is operating in heat pump heating mode, R-Y/Y2
and R-G circuits are closed energizing heat pump, and blower
operates at cooling speed. When heat pump defrost is required,
R-W/W1 circuits close starting gas heat cycle, and blower adjusts
to low-heat speed.
3. Electronic Air Cleaner—The EAC-1 terminal does not
operate in emergency heat mode.
4. Humidifier—The HUM terminal is energized IMMEDI-
1. Prepurge period—The inducer motor is turned on and
slowly comes up to speed. When low-pressure switch
closes, inducer motor RPM is noted by microprocessor, and
a 25 sec prepurge period begins. The RPM is used to
evaluate vent system resistance. This evaluation is then
used to determine required RPM necessary to operate
inducer in low-heat mode.
ATELY.
5. Ignitor warm up—The HSI is energized for a 17 sec
warm-up period after prepurge period is completed.
6. Ignition sequence—After HSI warm-up period has com-
pleted, the gas valve is energized, permitting gas flow to
burners where it is ignited. After 5 sec, the HSI is
de-energized, and a 2-sec flame-sensing period begins.
NOTE: The heat cycle can start in either high or low heat. If a
high-heat cycle is initiated, inducer continues increasing its speed
after low-pressure switch closes. When high-pressure switch
closes, inducer motor RPM is noted by microprocessor before the
25 sec prepurge period begins. The RPM is used to evaluate vent
system resistance. This evaluation is used to determine required
RPM necessary to operate inducer in high-heat mode.
NOTE: Emergency heat mode only operates in high heat.
7. Flame sensing—When burner flame is sensed, control
center holds gas valve open. If burner flame is not sensed,
control center de-energizes gas valve and ignition sequence
is repeated.
—32—
Download from Www.Somanuals.com. All Manuals Search And Download.
b. R-W/W1 with R-Y/Y2 and R-G signals terminated—
The blower continues to operate completing a normal
blower off delay.
VARIABLE
SPEED
THERMOSTAT
2-SPEED
THERMOSTAT
2-SPEED AIR
CONDITIONER
11. Post purge—The inducer continues operating for 15 sec
after gas valve is de-energized.
R
R
R
C
B. Two-Speed Applications
For details on 2-speed heat pump applications, refer to Fig. 44.
C
G
C
G
VARIABLE
SPEED
2-SPEED
2-SPEED
THERMOSTAT
HEAT PUMP
THERMOSTAT
W2
W/W1
W2
Y2
W3
L
R
R
R
C
Y2
E
Y/Y2
C
G
C
G
L
W2
W/W1
W2
Y2
Y1
Y1
Y2
E
Y/Y2
W3
A94302
Fig. 43—Wiring Schematic for 2-Speed
Cooling Applications
L
L
2. Humidifier—The HUM terminal is energized after inducer
O
O
prepurge period is completed.
3. Ignitor warm up—After prepurge period, HSI is energized
Y1
Y1
for 17 sec.
4. Ignition sequence—After HSI warm-up period is com-
pleted, the gas valve is energized, permitting gas flow to the
burners where it is ignited. After 5 sec, the HSI is
de-energized, and a 2-sec flame-sensing period begins.
A94303
Fig. 44—Wiring Schematic for 2-Speed
Heat Pump Applications
VII. CONTINUOUS FAN MODE
5. Flame sensing—When burner flame is sensed, control
center holds gas valve open.
1. Operating with continuous fan only—
If burner flame is not sensed, control center de-energizes
gas valve, and ignition sequence is repeated.
a. Call for continuous fan—The thermostat closes R-G
circuit.
6. Blower off period—Ten sec after gas valve is energized,
the blower stops for 25 sec to allow heat exchangers to
warm up.
b. Blower on—The blower starts immediately.
NOTE: The blower starts at approximately 400-500 RPM. After
20 sec, the motor is turned off for 1/10 of a sec where a coast down
calibration is done to evaluate resistance of the conditioned air
duct system. The microprocessor then determines blower RPM
required to provide proper airflow for heating mode.
7. Blower on delay—After blower off period, blower starts.
NOTE: The blower starts at approximately 400-500 RPM. After
20 sec, the motor is turned off for 1/10 of a sec where a coast down
calibration is done to evaluate resistance of the conditioned air
duct system. The microprocessor then determines blower RPM
required to provide proper airflow for heating mode.
NOTE: The continuous fan speed is the same as low-heat speed
unless it is field adjusted to another desired airflow. See Continu-
ous Fan Setup Switches section. There is also a chart on wiring
diagram. (See Fig. 24.)
8. Electronic Air Cleaner—The EAC-1 terminal is energized
c. Electronic Air Cleaner—The EAC-1 terminal is ener-
gized whenever blower operates, regardless of operating
mode.
whenever blower operates.
9. Inducer speed operation—If cycle starts in low heat,
inducer speed reduces slightly after the flame sense. If cycle
starts in high heat, inducer speed increases 15 sec after
flame sense. The reduction in speed in low heat is to
optimize combustion for maximum efficiency.
2. Operating with continuous fan (R-G) and call for heat
(R-W/W1) is received—Same as heat pump mode except
blower on delay is 10 sec less than heat mode. After call for
heat (R-W/W1) is terminated, the blower remains operating
at low-heat speed for selected blower off delay before
resuming continuous fan speed.
10. Call for heat terminated—When the call for heat is
satisfied, the R-W/W1 signal is terminated, de-energizing
gas valve (stopping gas flow to burners), and HUM terminal
is de-energized.
3. Operating with continuous fan (R-G) and call for cool-
ing (R-Y/Y2) is received—See Cooling Mode section.
After call for cooling (R-Y/Y2) is terminated, the blower
remains operating at cooling speed for 90 sec before
resuming continuous fan speed.
a. R-W/W1 signal terminated with R-Y/Y2 and R-G
still present—The blower changes its speed to cooling
RPM.
—33—
Download from Www.Somanuals.com. All Manuals Search And Download.
VIII. COMPONENT TEST
XI. ZONE MODE
All components are functionally operated except gas valve with
component test feature.
When setup switch SW-5 MZ is in ON position, blower motor
control is the same as above except with the following exceptions:
This feature helps diagnose a system problem in case of a
component failure.
1. While blower is operating in either low heat or continuous
fan, the coast down calibration is performed once a minute
to update blower RPM for zone damper position changes
during a given cycle unless the blower pulse width to
blower motor is greater than 60 percent. This prevents
nuisance faults from occurring when a high continuous fan
CFM has been selected.
NOTE: Setup switch SW-1 MUST be in OFF position or Fault
Code 22 (setup error) will occur.
NOTE: NO thermostat signal may be present at control center,
and all blower time delay off periods must be completed.
To initiate component test feature, proceed with the following:
1. Leave 115-v power to furnace turned on.
2. Remove main furnace door.
2. While blower is operating in either high heat or cooling,
blower pulse width to blower motor is frozen when blower
RPM is within 10 percent of calculated blower RPM for 5
sec.
3. Remove blower access panel.
START-UP PROCEDURES
I. GENERAL
4. Turn setup switch SW-6 to ON position.
5. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
1. Furnace must have a 115-v power supply properly con-
nected and grounded.
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Caution must be taken when manually closing
this switch for service purposes. Failure to follow this
warning could result in personal injury or death.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control center fault indicator light flashes
rapidly and furnace does not operate.
2. Thermostat wire connections at terminals R, W/W1, G, and
Y/Y2 must be made at 24-v terminal block on control
center.
When items 1-5 have been completed, the following will occur:
3. Natural gas service pressure must not exceed 0.5 psig
(14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
1. The control center goes through a brief self-test. This
self-test takes approximately 2 sec to complete. After door
switch is closed, red (microprocessor) LED briefly comes
on. Then green LED comes on for 1 sec, followed by 1 sec
where both green and yellow LEDs are on. During this time,
the microprocessor is checking itself.
4. Blower access panel must be in place to complete 24-v
electrical circuit to furnace.
CAUTION: These furnaces are equipped with a manual
reset limit switch in burner box. This switch opens if an
overheat condition (rollout) occurs in burner enclosure.
Correct inadequate combustion-air supply or improper
venting condition and reset switch. DO NOT jumper this
switch.
2. Inducer motor operates for 20 sec at low speed, operates for
20 sec at high speed, then turns off.
3. Hot surface ignitor is energized for 15 sec, then de-
energized.
4. Main blower motor operates for 20 sec at low speed,
operates for 20 sec at high speed, then turns off.
Before operating furnace, check each manual reset switch for
continuity. If necessary, press button to reset switch.
5. After component operation test is completed, 1 or more
fault codes (11, 22, 41, or 42) will flash. See service label
on back of main furnace door for explanation of fault codes.
II. SELECT SETUP SWITCH POSITIONS
A. Air Conditioning (A/C) Setup Switches
NOTE: To repeat component test, turn setup switch SW-6 to OFF
and then back to ON.
The air conditioning setup switches are used to match furnace
airflow to cooling unit used. This furnace will provide 400 CFM
per selected air conditioning tonnage.
After component test, perform the following:
1. Release blower panel access door switch and turn setup
switch SW-6 to OFF position.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate A/C setup switches on control center. (See Fig. 25.)
3. Determine air conditioning tonnage used.
2. If applicable, replace blower access panel and check LED
status by removing plug in blower access panel.
3. Reinstall main furnace door if all LEDs are off, indicating
furnace is ready to operate when a signal from thermostat is
received.
4. Use Table 8 or wiring schematic to determine proper setup
position of A/C switches. (See Fig. 24 and 45.)
NOTE: Excessive airflow caused by improper A/C switch setup
may cause condensate blow off in cooling mode.
IX. BYPASS HUMIDIFIER MODE
When setup switch SW-3 BPH is in ON position, RPM calculated
for low heat is multiplied by 1.15 for all furnace model sizes. This
compensates for increased return-air temperature caused by by-
passed air supply.
5. Replace main furnace door and blower access panel.
NOTE: EAC-1 terminal is energized whenever blower operates.
HUM terminal is only energized when gas valve is energized.
X. DEHUMIDIFICATION MODE
B. Continuous Fan (CF) Setup Switches
If dehumidification input is energized with a 24-vac input, RPM
calculated for cooling and continuous fan is multiplied by 0.85 for
all furnace model sizes. This compensates for high humidity
conditions during cooling operation.
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode. This setup feature allows
continuous fan airflow to be adjusted. To set desired continuous
fan airflow:
—34—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 8—AIR CONDITIONING (A/C) AIRFLOW SETUP SWITCH POSITION
A/C SETUP
SWITCH POSITION
AIR
ALLOWABLE FURNACE MODEL SETUP
CONDITIONER CFM AIRFLOW
(TONS)
A/C-1 A/C-2 A/C-3
042040
3 Tons
042060
3 Tons
042080
3 Tons
060080
5 Tons
060100
5 Tons
060120
5 Tons
1200 or
2000
Default
OFF
OFF
OFF
1200 CFM 1200 CFM 1200 CFM 2000 CFM 2000 CFM 2000 CFM
1-1/2
600
800
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
X
X
X
X
X
X
—
X
X
X
X
X
X
—
X
X
X
X
X
X
—
X
X
X
X
X
X
2
2-1/2
3
1000
1200
1400
1600
2000
ON
X
X
X
OFF
ON
OFF
OFF
ON
X
X
X
3-1/2
4
ON
X
X
X
OFF
ON
ON
—
—
—
—
—
—
5
ON
ON
X—Indicates allowable selection.
TABLE 9—CONTINUOUS FAN (CF) AIRFLOW SETUP SWITCH POSITION
CF SETUP
ALLOWABLE FURNACE MODEL SETUP
SWITCH POSITION
CONTINUOUS
FAN (CFM)
CF-1
CF-2
OFF
OFF
ON
CF-3
OFF
OFF
OFF
OFF
ON
042040
042060
042080
060080
060100
060120
Default
600
OFF
ON
565*
X
515*
X
690*
X
690*
—
X
860*
—
X
1035*
—
X
X
X
X
X
X
800
OFF
ON
X
X
X
1000
1200
1400
1600
2000
ON
X
X
X
X
X
OFF
ON
OFF
OFF
ON
X
X
X
X
X
ON
X
X
X
X
X
OFF
ON
ON
—
—
—
—
—
—
X
X
ON
ON
X
X
* Add 15% additional CFM when Bypass Humidifier switch SW-3 on control board is used.
X—Indicates allowable selection.
3. See Table 10 for setup switch description. (See Fig. 24 and
45.)
1
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW-3 (BPH)
should be in ON position. This prevents nuisance limit trips caused
by the increased temperature in return air resulting from bypass.
NOTE: If modulating dampers are used, setup switch SW-5 (MZ)
should be in ON position. This allows furnace control center to
compensate for modulating dampers. The control re-calibrates for
new system static conditions once every minute while operating in
low-heat or continuous fan modes.
OFF
III. PRIME CONDENSATE TRAP WITH WATER
A95198
Fig. 45—Example of Setup Switch in OFF Position
CAUTION: Condensate trap must be PRIMED or
proper draining may not occur. The condensate trap has 2
internal chambers which can ONLY be primed by pour-
ing water into the inducer drain side of condensate trap.
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on control center. (See Fig. 25.)
3. Determine desired continuous fan airflow.
4. Use Table 9 or wiring schematic to determine proper setup
position of CF switches. (See Fig. 24 and 45.)
1. Remove upper inducer housing drain connection cap. (See
Fig. 46.)
NOTE: The CF switches are factory set to provide continuous fan
airflow equal to low-heat mode.
2. Connect field-supplied 1/2-in. ID tube to upper inducer
housing drain connection.
5. Replace main furnace door and blower access panel.
3. Insert field-supplied funnel into tube.
C. Setup Switches (SW)
4. Pour 1 quart of water into funnel/tube. Water should run
through inducer housing, overfill condensate trap, and flow
into open field drain. (See Fig. 47.)
The control center has 8 setup switches that may be set to meet the
application requirements. Position these setup switches for the
appropriate requirement.
5. Remove funnel and tube from inducer housing and replace
drain connection cap and clamp.
1. Remove main furnace door and blower access panel.
2. Locate setup switches on control center. (See Fig. 25.)
—35—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 10—SETUP SWITCH DESCRIPTION
SETUP
SWITCH NO.
NORMAL
POSITION
DESCRIPTION OF USE
SW-1
(FLT)
Turn switch to ON for fault history display. No thermostat signal can be
present for fault history display.
OFF
SW-2
(LOW)
OFF
OFF
Turn switch to ON to lock furnace in low-heat mode only.
Turn switch to ON when a bypass humidifier is used. This compensates
for higher return-air temperature and provides 5 percent more airflow in
low-heat mode only.
SW-3
(BPH)
Turn switch to ON to bypass microprocessor control. Furnace will oper-
ate at high heat only with main blower and inducer motor operating at
maximum RPM. NO safeties are bypassed.
SW-4
(EMER HEAT)
OFF
OFF
Turn switch to ON when modulating dampers are used. In this mode,
main blower speed is recalculated once every minute while furnace is in
low-heat or continuous fan mode.
SW-5
(MZ)
Turn switch to ON to initiate component test. Furnace will operate in-
ducer motor for 20 sec at low speed, operate inducer motor for 20 sec at
high speed, energize HSI for 15 sec, operate blower for 20 sec at low
speed, and operate blower for 20 sec at high speed. SW-1 must be in
OFF position. No thermostat signal can be present for component test to
be initiated.
SW-6
(COMP TEST)
OFF
SW-7 and -8
(Blower Off Delay)
Adjust switches to provide desired heating mode blower off delay time,
90, 135, 180, or 225 sec.
See Table 11
TABLE 11—BLOWER OFF DELAY SETUP SWITCH
POSITION
DESIRED HEATING
MODE BLOWER
OFF DELAY (SEC)
SETUP SWITCH (SW-7 AND -8) POSITION
SW-7
SW-8
90
OFF
ON
OFF
OFF
ON
135
180
225
OFF
ON
ON
A94208
A94209
Fig. 46—Inducer Housing Drain Tube
Fig. 47—Filling Condensate Trap
—36—
Download from Www.Somanuals.com. All Manuals Search And Download.
IV. PURGE GAS LINES
e. Turn low-heat adjusting screw (5/64 hex Allen wrench)
counterclockwise (out) to decrease input rate or clock-
wise (in) to increase input rate.
If not previously done, purge the lines after all connections have
been made and check for leaks.
LOW-FIRE
ON/OFF
SWITCH
WARNING: Never purge a gas line into a combustion
chamber. Never use matches, candles, flame, or other
sources of ignition for the purpose of checking leakage.
Use a soap-and-water solution to check for leakage.
Failure to follow this warning could result in fire,
explosion, personal injury, or death.
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
HIGH-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
INLET
PRESSURE
TAP
O
F
F
ON
V. ADJUSTMENTS
A. Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft.
In the U.S.A., the input rating for altitudes above 2000 ft must be
reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft to 4500 ft above sea level.
Furnace input rate must be within ±2 percent of input on furnace
rating plate.
BURNER
1. Determine natural gas orifice size and manifold pressure for
correct input.
ENCLOSURE
REFERENCE
a. Obtain yearly heat value average (at installed altitude)
from local gas supplier.
PRESSURE TAP
MANIFOLD
PRESSURE
TAP
b. Obtain yearly specific gravity average from local gas
supplier.
A97386
→
Fig. 48—Redundant Automatic Gas Valve
c. Verify furnace model. Table 12 can only be used for
model 355MAV Furnaces.
NOTE: DO NOT set low-heat manifold pressure less than 1.3-in.
wc or more than 1.7-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.
d. Find installation altitude in Table 12.
NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A.
altitudes of 2001 to 3000 ft in Table 12.
e. Find closest natural gas heat value and specific gravity in
Table 12.
CAUTION: DO NOT bottom out gas valve regulator
adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low- and high-heat
manifold pressure settings for proper operation.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
EXAMPLE: (0—2000 ft altitude)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45
f. Turn setup switch SW-2 to OFF position after complet-
ing low-heat adjustment.
Manifold pressure: 3.6-in. wc for high heat
1.5-in. wc for low heat
* Furnace is shipped with No. 45 orifices. In this example,
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.
g. Jumper R and W2 thermostat connections on control
center. (See Fig. 25.) This keeps furnace locked in
high-heat operation.
h. Turn high-heat adjusting screw (5/64 hex Allen wrench)
counterclockwise (out) to decrease input rate or clock-
wise (in) to increase rate.
g. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE; ALWAYS CHECK AND
VERIFY.
NOTE: DO NOT set high-heat manifold pressure less than 3.2-in.
wc or more than 3.8-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.
2. Adjust manifold pressure to obtain input rate.
a. Remove burner enclosure front.
i. When correct input is obtained, replace caps that conceal
gas valve regulator adjustment screws. Main burner
flame should be clear blue, almost transparent. (See Fig.
49.)
NOTE: Manifold pressure MUST always be measured with the
burner box cover REMOVED.
b. Remove caps that conceal adjustment screws for low-
and high-heat gas valve regulators. (See Fig. 48.)
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent
pipes, and burner enclosure front are in place when checking input
by clocking gas meter.
c. Turn setup switch SW-2 on control center to ON
position. (See Fig. 25.) This keeps furnace locked in
low-heat operation.
a. Calculate high-altitude adjustment (if required).
UNITED STATES
d. Jumper R and W/W1 thermostat connections on control
center to start furnace.
—37—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 12—MODEL 355MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT
(TABULATED DATA BASED ON 20,000 BTUH HIGH HEAT/13,000 BTUH LOW HEAT PER BURNER
DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
0.58
Manifold
0.60
Manifold
0.62
Manifold
0.64
Manifold
Pressure
High/Low
0.66
Manifold
Pressure
High/Low
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
Pressure
High/Low
Pressure
High/Low
850
875
43
43
44
44
44
44
45
45
45
45
47
3.7/1.5
3.5/1.5
3.7/1.6
3.5/1.5
3.4/1.4
3.2/1.3
3.7/1.6
3.5/1.5
3.3/1.4
3.2/1.3
3.6/1.5
43
43
43
44
44
44
45
45
45
45
47
3.8/1.6
3.6/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.5
3.3/1.4
3.7/1.6
42
43
43
44
44
44
44
45
45
45
45
3.2/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.6
3.6/1.5
3.4/1.4
3.2/1.4
42
43
43
43
44
44
44
44
45
45
45
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.4/1.4
3.2/1.3
3.7/1.6
3.5/1.5
3.4/1.4
42
42
43
43
44
44
44
44
45
45
45
3.4/1.4
3.2/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.5/1.5
900
0
to
925
950
975
1000
1025
1050
1075
1100
2000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
U.S.A.
Altitudes
2001
775
800
825
850
875
900
925
950
975
1000
1025
43
43
44
44
44
44
45
45
45
47
47
3.8/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.5
3.5/1.5
3.3/1.4
3.7/1.6
3.6/1.5
42
43
43
44
44
44
45
45
45
45
47
3.2/1.4
3.7/1.5
3.4/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.6
42
43
43
44
44
44
44
45
45
45
45
3.3/1.4
3.8/1.6
3.6/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.6
3.5/1.5
3.4/1.4
3.2/1.3
42
42
43
43
44
44
44
45
45
45
45
3.4/1.4
3.2/1.4
3.7/1.5
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.5/1.5
3.3/1.4
42
42
43
43
43
44
44
44
45
45
45
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
to
3000
or
Canada
Altitudes
2000
to
4500
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
750
775
800
825
850
875
900
925
950
975
1000
43
43
44
44
44
45
45
45
45
47
47
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.6/1.5
3.5/1.5
43
43
43
44
44
44
45
45
45
45
47
3.8/1.6
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.2/1.3
3.6/1.5
42
43
43
44
44
44
45
45
45
45
47
3.3/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.5
3.3/1.4
3.7/1.6
42
43
43
43
44
44
44
45
45
45
45
3.4/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.7/1.5
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.4/1.4
3.2/1.4
42
42
43
43
44
44
44
44
45
45
45
3.5/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
3.7/1.5
3.5/1.5
3.3/1.4
3001
to
4000
—38—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 12—MODEL 355MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued
(TABULATED DATA BASED ON 20,000 BTUH HIGH HEAT/13,000 BTUH LOW HEAT PER BURNER
DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
0.58
Manifold
0.60
Manifold
0.62
Manifold
0.64
Manifold
Pressure
High/Low
0.66
Manifold
Pressure
High/Low
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
Pressure
High/Low
Pressure
High/Low
725
750
775
800
825
850
875
900
925
950
43
43
44
44
44
45
45
45
47
47
3.7/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
43
43
44
44
44
45
45
45
45
47
3.8/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.4
3.6/1.5
42
43
43
44
44
44
45
45
45
45
3.2/1.4
3.7/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.2/1.3
42
43
43
44
44
44
44
45
45
45
3.3/1.4
3.8/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
3.6/1.5
3.4/1.5
3.3/1.4
42
42
43
43
44
44
44
45
45
45
3.4/1.4
3.2/1.4
3.7/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
4001
to
5000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
700
725
750
775
800
825
850
875
900
925
950
975
1000
43
43
44
44
44
45
45
45
47
47
48
48
48
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.2/1.3
3.6/1.5
3.4/1.4
3.2/1.4
3.6/1.5
3.4/1.4
3.7/1.6
3.5/1.5
3.3/1.4
43
43
44
44
44
45
45
45
47
47
48
48
48
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.8/1.6
3.6/1.5
3.5/1.5
42
43
43
44
44
44
45
45
45
47
47
48
48
3.2/1.3
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.2/1.4
3.6/1.5
3.4/1.5
3.3/1.4
3.7/1.5
3.5/1.5
3.8/1.6
3.6/1.5
42
43
43
44
44
44
45
45
45
45
47
47
48
3.3/1.4
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
3.6/1.5
3.4/1.4
3.7/1.6
42
43
43
43
44
44
44
45
45
45
47
47
48
3.4/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.2/1.4
3.7/1.5
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.8/1.6
5001
to
6000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
650
675
700
725
750
775
800
825
850
875
42
43
44
44
44
45
45
45
47
47
3.2/1.3
3.6/1.5
3.8/1.6
3.6/1.5
3.3/1.4
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
42
43
43
44
44
44
45
45
45
47
3.3/1.4
3.7/1.6
3.4/1.5
3.7/1.6
3.4/1.5
3.2/1.4
3.7/1.5
3.4/1.5
3.2/1.4
3.6/1.5
42
43
43
44
44
44
45
45
45
45
3.4/1.4
3.8/1.6
3.6/1.5
3.8/1.6
3.6/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
42
42
43
43
44
44
44
45
45
45
3.5/1.5
3.2/1.4
3.7/1.6
3.4/1.4
3.7/1.6
3.4/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.3/1.4
42
42
43
43
44
44
44
45
45
45
3.6/1.5
3.3/1.4
3.8/1.6
3.5/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.4
6001
to
7000
—39—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 12—MODEL 355MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued
(TABULATED DATA BASED ON 20,000 BTUH HIGH HEAT/13,000 BTUH LOW HEAT PER BURNER
DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
0.58
Manifold
0.60
Manifold
0.62
Manifold
0.64
Manifold
Pressure
High/Low
0.66
Manifold
Pressure
High/Low
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
Pressure
High/Low
Pressure
High/Low
625
650
675
700
725
750
775
800
825
850
43
43
44
44
44
45
45
45
47
47
3.8/1.6
3.5/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.6/1.5
3.4/1.4
42
43
43
44
44
45
45
45
45
47
3.3/1.4
3.7/1.6
3.4/1.4
3.6/1.5
3.4/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
3.5/1.5
42
43
43
44
44
44
45
45
45
47
3.4/1.4
3.8/1.6
3.5/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.5
42
42
43
43
44
44
45
45
45
45
3.5/1.5
3.2/1.4
3.6/1.5
3.4/1.4
3.6/1.5
3.4/1.4
3.8/1.6
3.6/1.5
3.4/1.4
3.2/1.3
42
42
43
43
44
44
44
45
45
45
3.6/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.5/1.5
3.3/1.4
7001
to
8000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
600
625
650
675
700
725
750
775
800
43
43
44
44
44
45
45
45
47
3.8/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.2/1.4
3.6/1.5
3.4/1.4
3.2/1.3
3.6/1.5
42
43
43
44
44
45
45
45
47
3.3/1.4
3.6/1.5
3.4/1.4
3.6/1.5
3.3/1.4
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
42
43
43
44
44
44
45
45
45
3.4/1.4
3.8/1.6
3.5/1.5
3.7/1.6
3.4/1.5
3.2/1.4
3.6/1.5
3.4/1.4
3.2/1.3
42
42
43
44
44
44
45
45
45
3.5/1.5
3.2/1.4
3.6/1.5
3.8/1.6
3.6/1.5
3.3/1.4
3.8/1.6
3.5/1.5
3.3/1.4
42
42
43
43
44
44
44
45
45
3.6/1.5
3.3/1.4
3.7/1.6
3.4/1.5
3.7/1.6
3.4/1.4
3.2/1.4
3.6/1.5
3.4/1.4
8001
to
9000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62 0.64
Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.66
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Manifold
Pressure
High/Low
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Pressure
High/Low
575
600
625
650
675
700
725
750
775
43
43
44
44
45
45
45
47
47
3.8/1.6
3.5/1.5
3.7/1.6
3.4/1.4
3.8/1.6
3.6/1.5
3.3/1.4
3.7/1.6
3.5/1.5
42
43
44
44
44
45
45
45
47
3.2/1.4
3.6/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.4/1.5
3.2/1.4
3.6/1.5
42
43
43
44
44
45
45
45
47
3.3/1.4
3.7/1.6
3.5/1.5
3.7/1.5
3.4/1.4
3.8/1.6
3.6/1.5
3.3/1.4
3.7/1.6
42
42
43
44
44
44
45
45
45
3.5/1.5
3.2/1.3
3.6/1.5
3.8/1.6
3.5/1.5
3.3/1.4
3.7/1.6
3.4/1.5
3.2/1.4
42
42
43
43
44
44
45
45
45
3.6/1.5
3.3/1.4
3.7/1.6
3.4/1.4
3.6/1.5
3.4/1.4
3.8/1.6
3.5/1.5
3.3/1.4
9001
to
10,000
—40—
Download from Www.Somanuals.com. All Manuals Search And Download.
EXAMPLE:
100,000 Btuh input furnace installed at 4300 ft.
Furnace Input
Rate at
Sea Level
Derate
X Multiplier =
Factor
Furnace Input Rate
at Installation
Altitude
100,000
X
0.91
=
91,000
CANADA
At installation altitudes from 2000 to 4500 ft, this
furnace must be derated 5 percent by an authorized Gas
Conversion Station or Dealer. To determine correct input
rate for altitude, see example above and use 0.95 as
derate multiplier factor.
BURNER
ORIFICE
b. Reinstall burner box cover.
A93059
NOTE: Clocking gas input rate MUST always be performed with
the burner box cover INSTALLED.
CAUTION: DO NOT redrill orifices. Improper drilling
(burrs, out-of-round holes, etc.) can cause excessive
burner noise and misdirection of burner flames. This can
result in flame impingement of burners and heat exchang-
ers, causing failures.
c. Check that gas valve adjustment caps are in place for
proper input to be clocked.
d. Obtain yearly heat value average for local gas supply.
NOTE: Be sure heating value of gas used for calculations is
correct for your altitude. Consult local gas utility for altitude
adjustment of gas heating value.
BURNER FLAME
BURNER
e. Check and verify orifice size in furnace. NEVER AS-
SUME THE ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
f. Turn off all other gas appliances and pilots.
g. Turn setup switch SW-2 to ON position. (See Fig. 25.)
This keeps furnace locked in low-heat operation.
h. Let furnace run for 3 minutes in low-heat operation.
i. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
j. Refer to Table 14 for cubic ft of gas per hr.
k. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
MANIFOLD
l. Turn setup switch SW-2 to OFF position and jumper R
and W2 thermostat connections. (See Fig. 25.) This keeps
furnace locked in high-heat operation. Repeat items h
through k for high-heat operation.
A89020
Fig. 49—Burner Flame
At altitudes above 2000 ft, this furnace has been ap-
proved for a 2 percent derate for each 1000 ft above sea
level. See Table 13 for derate multiplier factor and
example.
EXAMPLE: (High-heat operation at 0—2000 ft altitude)
Furnace input from rating plate is 100,000 Btuh
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 975 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 14)
Btu heating input = 103 X 975 = 100,425 Btuh In this
example, the orifice size and manifold pressure adjustment
is within ±2 percent of the furnace input rate.
TABLE 13—ALTITUDE DERATE MULTIPLIER FOR U.S.A.
ALTITUDE
(FT)
% OF
DERATE
DERATE MULTIPLIER
FACTOR FOR U.S.A.*
0—2000
2001—3000
3001—4000
4001—5000
5001—6000
6001—7000
7001—8000
8001—9000
9001—10,000
0
1.00
0.95
0.93
0.91
0.89
0.87
0.85
0.83
0.81
NOTE: Measured gas inputs (high heat and low heat) must be
within ±2 percent of that stated on furnace rating plate when
installed at sea level or derated per that stated above when installed
at higher altitudes.
4—6
6—8
8—10
10—12
12—14
14—16
16—18
18—20
m. Remove jumper across R, W/W1, and W2 thermostat
connections to terminate call for heat.
* Derate multiplier factor is based on midpoint altitude for altitude range.
—41—
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 14—GAS RATE CU FT/HR
d. Ensure bypass humidifier switch (BPH) setup switch
SW-3 on control center is in ON position when a bypass
humidifier is used. (See Fig. 25 for switch location.)
SECONDS SIZE OF TEST DIAL SECONDS SIZE OF TEST DIAL
FOR 1
1
2
5
FOR 1
1
2
5
REVOLUTION cu ft cu ft cu ft REVOLUTION cu ft cu ft cu ft
e. Check Troubleshooting Guide for Variable-Speed
2-Stage Electronic Condensing Furnaces.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
360
327
300
277
257
240
225
212
200
189
180
171
164
157
150
144
138
133
129
124
120
116
113
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
73
720 1800
655 1636
600 1500
555 1385
514 1286
480 1200
450 1125
424 1059
400 1000
50
51
52
53
54
55
56
57
58
59
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
72
71
69
68
67
65
64
63
62
61
60
58
56
54
53
51
50
48
47
46
45
44
43
42
41
40
39
38
38
37
36
35
35
34
33
144
141
138
136
133
131
129
126
124
122
120
116
112
109
106
103
100
97
95
92
90
88
86
84
82
80
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
C. Set Thermostat Heat Anticipator
The thermostat heat anticipator must be set to match the amp draw
of components in the R-W/W1 circuit. Accurate amp draw
measurements can be obtained at the thermostat subbase terminals
R and W.
379
360
343
327
313
300
288
277
267
257
248
240
232
225
218
212
206
200
195
189
185
180
176
172
167
164
160
157
153
150
147
947
900
857
818
783
750
720
692
667
643
621
600
581
563
545
529
514
500
486
474
462
450
439
429
419
409
400
391
383
375
367
Fig. 50 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after blower
motor has started and furnace is operating in low heat.
1. To operate furnace in low heat, turn setup switch SW-2 to
ON position (See Fig. 25) and connect ammeter leads
across thermostat subbase R-W.
2. See thermostat manufacturer’s instructions for adjusting the
heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3
cycles per hr.
3. Return setup switch SW-2 to OFF position and replace
thermostat on subbase.
78
76
75
74
72
71
69
68
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
67
HOOK-AROUND
AMMETER
110
112
116
120
33
32
31
30
65
64
62
60
164
161
155
150
R
Y
W
G
B. Set Temperature Rise
CAUTION: Temperature rise must be within limits
specified on unit rating plate. Recommended operation is
at midpoint of rise or above. Failure to follow this caution
may result in condensing or overheating the heat ex-
changers.
10 TURNS
Furnace must operate within range of temperature rise specified on
the unit rating plate. Determine air temperature rise as follows:
FROM UNIT 24-V
CONTROL TERMINALS
1. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
0.5 AMPS FOR THERMOSTAT
5.0 AMPS ON AMMETER
=
EXAMPLE:
ANTICIPATOR SETTING
10 TURNS AROUND JAWS
A96316
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
Fig. 50—Amp Draw Check with Ammeter
CHECK SAFETY CONTROLS
I. CHECK PRIMARY LIMIT CONTROL
NOTE: Temperature rise can be determined for low-fire opera-
tion by placing setup switch SW-2 on control center in ON
position. For high-heat operation, place setup switch SW-2 in OFF
position and jumper R-W2 on control center. DO NOT forget to
return setup switch to OFF position and remove R-W2 jumper
upon completion of testing. (See Fig. 25 for switch and terminal
location.)
This control shuts off the combustion control system and energizes
the air-circulating blower motor if furnace overheats.
1. The recommended method of checking this limit control is
to gradually block off return air after furnace has been
operating for a period of at least 5 minutes.
2. As soon as limit control has shut off burners, a 33 fault code
will appear on control center.
3. This furnace is capable of automatically providing proper
airflow to maintain the temperature rise within the range
specified on unit rating plate. If temperature rise is outside
this range, proceed as follows:
3. The return-air opening should be unblocked to permit
normal air circulation.
By using this method to check the limit control, it can be
established that the limit is functioning properly and the furnace
will operate safely if there is a restricted return-air supply or motor
failure. If the limit control does not function during this test, the
cause must be determined and corrected.
a. Check gas input for low- and high-heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive restric-
tions causing static pressure greater than 0.5-in. wc.
—42—
Download from Www.Somanuals.com. All Manuals Search And Download.
II. CHECK PRESSURE SWITCHES
7. Turn on 115-v power to furnace.
This control proves operation of the draft inducer. Check switch
operation as follows:
8. Reset thermostat to desired temperature.
1. Turn off 115-v power to furnace.
CHECKLIST
2. Remove control access door and disconnect inducer motor
12-pin wire harness at inducer motor.
1. Put away tools and instruments. Clean up debris.
2. Verify manual reset switch has continuity.
3. Turn on 115-v power to furnace.
4. Set thermostat to call for heat. When pressure switches are
functioning properly, fault code 42 will flash on control
center approximately 10 sec after thermostat switch is
closed. If either a fault code 31 or 32 is flashed when ICM
inducer motor is disconnected, the furnace will shut itself
down immediately. Determine the reason pressure switches
did not function properly and correct the condition.
3. Verify that blower and control access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc-
tions.
6. Review User’s Manual with owner.
7. Leave literature packet near furnace.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace
access door.
—43—
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKLIST—INSTALLATION
LOAD CALCULATION
Heating Load (Btuh)
Condensate Drain
____________
____________
____________
________
Unit Level or Pitched Forward
Cooling Load (Btuh)
Internal Tubing Connections Free of Kinks
and Traps
________
________
Furnace Model Selection
External Drain Connection Leak Tight and
Sloped
COMBUSTION AND VENT PIPING
Termination Location
________
________
Condensate Trap Primed before Start-Up
Heat Tape Installed if Required
CHECKLIST—START-UP
________
________
________
________
________
________
________
________
Roof or Sidewall
Termination Kit — 2 Pipe or Concentric
Combustion-Air Pipe Length
Combustion-Air Pipe Elbow Quantity
Vent Pipe Length
Gas Input Rate
(Set Within 2 percent of Rating Plate)
________
________
Temperature Rise Adjusted
Thermostat Anticipator
Vent Pipe Elbow Quantity
Pipe Diameter Determined from Sizing Table
Pipe Sloped To Furnace
________
________
Anticipator Setting Adjusted or
Cycle Rate (3 Cycles per Hr) Selected
Safety Controls Check Operation
Primary Limit
Pipe Insulation
________
________
________
________
Over Ceilings
Pressure Switches
Low-Ambient Exposed Pipes
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training
[ ] Classroom Service Training
A94328
© 1997 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
Printed in U.S.A.
355m405
Catalog No. BDP-5335-500
—44—
Download from Www.Somanuals.com. All Manuals Search And Download.
|