Baldor Portable Generator PG 6000 User Manual

PG 6000 Generator  
Installation & Operating Manual  
8/06  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section 1  
Product Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1  
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1  
Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1  
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2  
Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6  
Section 2  
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1  
Section 3  
Receiving & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1  
Receiving & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1  
Lifting the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1  
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1  
Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
Frame Ground Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3  
Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
Recommended Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
Use of Electric Motor Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
Optional Wheel Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
Section 4  
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1  
Operator Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1  
PreStart Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1  
StartUp Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2  
Stopping Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2  
Section 5  
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1  
Problems and Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2  
Appendix A  
PG6000 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1  
Appendix B  
Special Information for California . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1  
MN2418  
Table of Contents i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ii Table of Contents  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
Product Safety Information  
Safety Notice  
Be sure that you are completely familiar with the safe operation of this equipment. This  
equipment may be connected to other machines that have rotating parts or parts that are  
controlled by this equipment. Improper use can cause serious or fatal injury. Always  
disconnect all electrical loads before starting the generator.  
Installation and repair procedures require specialized skills with electrical generating equipment.  
Any person that installs or repairs this generator must have these specialized skills to ensure that  
this generating unit is safe to operate. Seek expert advise for repairs or any questions you may  
have about the safe installation and operation of this system.  
The precaution statements are general guidelines for the safe use and operation of this  
generator. It is not practical to list all unsafe conditions. Therefore, if you use a procedure that is  
not recommended in this manual you must determine if it is safe for the operator and all  
personnel in the proximity to the generator and connected loads. If there is any question of the  
safety of a procedure please seek expert advise before starting the generator.  
This equipment contains high voltages. Electrical shock can cause serious or fatal injury. Only  
qualified personnel should attempt the startup procedure or troubleshoot this equipment.  
This equipment may be connected to other machines that have rotating parts or parts that are  
driven by this equipment. Improper use can cause serious or fatal injury. Only qualified  
personnel should attempt the startup procedure or troubleshoot this equipment.  
System documentation must be available to anyone that operates this equipment at all  
times.  
Keep non-qualified personnel at a safe distance from this equipment.  
Only qualified personnel familiar with the safe installation, operation and maintenance  
of this device should attempt start-up or operating procedures.  
Always stop engine before making or removing any connections.  
Always stop engine and allow it to cool before refueling.  
Responsibility  
When your generator is delivered, it becomes the responsibility of the owner/operator of the  
generator set to prevent unsafe conditions and operation of the equipment. Some  
responsibilities include (but are not limited to) the following:  
1. It is the responsibility of the owner/operator of this generator to ensure that this  
equipment is correctly and safely installed.  
2. It is the responsibility of the owner/operator of this generator to ensure that this  
equipment, when installed fully complies with all federal, state and local codes.  
3. It is the responsibility of the owner/operator of this generator to ensure that any person  
operating this equipment has been properly trained.  
4. It is the responsibility of the owner/operator of this generator to ensure that any person  
operating this equipment has access to all manuals and information required for the  
safe use and operation of this equipment.  
5. It is the responsibility of the owner/operator of this generator to ensure that it is properly  
maintained and safety inspected at regular scheduled intervals.  
6. It is the responsibility of the owner/operator of this generator to ensure that any person  
who has not been trained on the safe use of this equipment does not have access to  
this equipment.  
Read This Manual Thoroughly  
If you do not understand any concept, any procedure, any safety warning statement, any safety  
caution statement or any portion of this manual, seek expert advise. We are happy to make sure  
you understand the information in this manual so that you can safely enjoy the full use of this  
generator.  
MN2418  
Product Safety Information 1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Precaution Statements Used In This Manual  
There are three classifications of precautionary statements used in this manual. The most critical  
is a WARNING statement, then the Caution statement and the least critical is the Note  
statement. The usage of each statement is as follows:  
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in injury or  
death.  
Caution: Indicates a potentially hazardous situation which, if not avoided, could result in damage to  
property.  
Note:  
Additional information that is not critical to the installation or operation.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS This manual contains important instructions for the generator that should  
be followed during installation, operation and maintenance of the generator.  
For ease of reading, the Warning statements are divided into four categories: Operation, Burn, Installation,  
and Maintenance.  
Operation  
WARNING: Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death. For  
storage or refueling handle fuel with care and only in clean, approved, properly marked safety  
fuel containers.  
WARNING: Do not overfill the fuel tank. Only fill the tank to within 1/2, of the top of the tank to allow  
space for fuel expansion. Overfilling of tank may cause fuel to spill out onto engine and  
cause fire or explosion.  
WARNING: Clean up fuel spills by wiping completely dry before starting engine. Gasoline and diesel fuel  
are flammable and can cause fire, explosions, injury or death.  
WARNING: Make sure the fuel cap is completely and securely closed after refueling to prevent spillage.  
Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death.  
WARNING: Never operate this generator in a manner other than as described in this manual. Operation  
in any manner not described in this manual should be considered unsafe and should not be  
attempted. Never start the engine unless you have first verified that the installation and  
operation of the generator are as described in this manual.  
WARNING: Be sure that you are completely familiar with the safe operation of this equipment. This  
equipment may be connected to other machines that have rotating parts or parts that are  
controlled by this equipment. Improper use can cause serious or fatal injury.  
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never  
breath exhaust fumes produced by a running engine. Only run the engine outdoors where  
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and  
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon  
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or  
incoherence. If you or anyone else experiences these symptoms, get out into fresh air  
immediately. Stop the engine and do not restart the engine until it has been inspected and if  
necessary repaired or reinstalled in a well ventilated area.  
WARNING: Hot exhaust gasses must never be directed toward anything that may catch fire or explode.  
WARNING: This generator must not be used on or near any forest covered, brush covered, or grass  
covered land unless the engine’s exhaust system is equipped with a spark arrestor. The  
spark arrestor must be maintained in effective working order by the operator.  
WARNING: Some parts of this generator rotate during operation. Rotating parts can present extreme  
danger if clothing or body extremities are caught by the rotating part and can cause serious  
or fatal injury. Never touch a part of the generator until the engine has been stopped and all  
rotating parts are completely stopped. Also, disconnect the spark plug wires and battery  
connection to prevent accidental engine rotation during servicing.  
WARNING: Never move a generator set that is running. Loads should be connected and position secure  
before starting the engine. Hazards are caused by moving a generator set that is running.  
Continued on next page.  
1-2 Product Safety Information  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation Warning Statements Continued  
WARNING: Be sure that you understand how to stop the engine quickly in case of an emergency situation.  
Become familiar with the controls and safety systems provided with this generator set.  
WARNING: Always wear safety glasses with side shields and hearing protection when working near the  
generator.  
WARNING: Improper operation may cause violent motion of connected equipment. Be certain that  
unexpected movement will not cause injury to personnel or damage to equipment.  
WARNING: Never operate the generator set indoors or in a poorly ventilated area such as a tunnel or  
cave. Exhaust fumes are extremely dangerous to all personnel that are in or in contact with  
that area.  
WARNING: Never permit anyone to operate the generator without proper instructions. Be sure to keep a  
copy of this manual with the generator so that all users can be properly informed of its safe  
operation.  
WARNING: Never allow children or pets to be in the area where the generator is running. The generator  
and the equipment being powered by the generator may cause injury or death.  
WARNING: Never operate the generator unless all guards, covers, shields and other safety items are  
properly installed.  
WARNING: Do not put hands, feet, tools clothing or other objects near rotating parts such as drive shaft,  
pulley, belt etc. Rotating parts cause extremely dangerous situations because they can catch  
loose clothing or extremities and cause serious or fatal injury.  
WARNING: When operating this generator remain alert at all times. Never operate machinery when  
physically or mentally fatigued, or while under the influence of alcohol, drugs or medication.  
WARNING: Never operate the engine when the air cleaner is removed. An engine backfire can cause  
serious burns.  
WARNING: High voltage is present whenever engine is running. Electrical shock can cause serious or  
fatal injury. Never operate electrical equipment while standing in water, on wet ground or with  
wet hands, feet or shoes or while barefoot.  
WARNING: High voltage is present whenever the engine is running. Electrical shock can cause serious  
or fatal injury. Always stop engine before connecting or disconnecting power cords or  
external devices.  
WARNING: Do not smoke near generator during operation or while refueling. Gasoline and diesel fuel are  
flammable and can cause fire, explosions, injury or death.  
WARNING: Stop engine and allow engine to cool before refueling. Gasoline and diesel fuel are flammable  
and can cause fire, explosions, injury or death.  
WARNING: Never store the generator with fuel in the tank. Never store the generator indoors or in an  
enclosed area or in a poorly ventilated enclosure where fumes may reach an open flame,  
electrical spark or pilot light as on a furnace, water heater, clothes dryer, etc. Gasoline and  
diesel fuel are flammable and can cause fire, explosions, injury or death.  
WARNING: Allow generator to cool before transporting it or storing it. Always drain fuel from tank after  
generator has cooled.  
WARNING: When transporting the generator (especially over rough roads) always drain the fuel tank to  
prevent leakage or spillage of fuel. Gasoline and diesel fuel are flammable and can cause fire,  
explosions, injury or death.  
WARNING: Operate the generator only on a level surface. If the generator is tilted during operation, fuel  
spillage may result. Gasoline and diesel fuel are flammable and can cause fire, explosions,  
injury or death.  
WARNING: Keep generator at least three feet away from buildings and other structures.  
WARNING: Keep generator away from flammable or hazardous materials (trash, rags, lubricants,  
explosives, paints etc.) and grass or leaf build up.  
WARNING: Keep a fire extinguisher near the generator while generator is in use. An extinguisher rated  
“ABC” by the National Fire Protection Association is appropriate.  
Continued on next page.  
MN2418  
Product Safety Information 1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning Statements Continued  
Burn  
WARNING: Parts of this generator are extremely hot during and after operation. To prevent severe burns,  
do not touch any part of the generator until you have first determined if the part is hot. Wear  
protective clothing and after use allow sufficient time for parts to cool before touching any  
part of the generator.  
WARNING: Do not touch the hot exhaust parts or the high voltage spark plug or coil terminals of the  
engine. Although spark plug voltages are not normally lethal, a sudden involuntary jerk of the  
hand or body part caused by contact with high voltage or a hot surface can result in injury to  
yourself or others.  
Installation  
WARNING: Installation and repair procedures requires specialized skills with electrical generating  
equipment and small engine systems. Any person that installs or performs repairs must have  
these specialized skills to ensure that the generator set is safe to operate.  
WARNING: Be sure all wiring complies with the National Electrical Code (NEC) and all regional and local  
codes or CE Compliance. Improper wiring may cause a hazardous condition and exposure to  
electrical hazards can cause serious injury or death.  
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power  
before you ensure that grounds are connected. Electrical shock can cause serious or fatal  
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be  
connected to an approved earth ground. Local codes may also require proper grounding of  
generator systems.  
WARNING: Place protective covers over all rotating parts such as drive shaft, pulley, belt etc. Rotating  
parts cause extremely dangerous situations because they can catch loose clothing or  
extremities and cause serious or fatal injury.  
WARNING: Unauthorized modification of a generator set may make the unit unsafe for operation or may  
impair the operation of the unit. Never start a generator set that has been modified or  
tampered with. Be sure that all covers and guards are properly installed and that the unit is  
safe before starting the engine. If you are unsure, seek expert advise before starting the  
engine.  
WARNING: When moving the generator, use reasonable caution. Be careful where you place fingers and  
toes to prevent injury “Pinch Points”. Never try to lift a generator without a hoist or lift means  
because they are heavy and bodily injury may result.  
WARNING: When transporting a generator (especially if it has wheel option installed) secure the unit to  
prevent movement during transport.  
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician  
has installed an approved transfer switch. The National Electrical Code (NEC) requires that  
connection of a generator to any electrical circuit normally powered by means of an electric  
utility must be connected by means of approved transfer switch equipment so as to isolate  
the electrical circuit from the utility distribution system when the generator is operating.  
Failure to isolate the electrical circuits by such means may result in injury or death to utility  
power workers due to backfeed of electrical energy onto the utility lines.  
WARNING: Circuit overload protection must be provided in accordance with the National Electrical Code  
and local regulations.  
WARNING: Have electrical circuits and wiring installed and checked by licensed electrician or qualified  
technician. Electrical shock can cause serious or fatal injury.  
WARNING: Incorrect installation of this generator set could result in property damage, injury or death.  
Connection of the generator to its fuel source must be done by a qualified professional  
technician or contractor.  
Continued on next page.  
1-4 Product Safety Information  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning Statements Continued  
Maintenance  
WARNING: Before servicing the generator set, be sure to disconnect the spark plug(s) to prevent  
accidental engine starting.  
WARNING: Before cleaning, inspecting, repairing, refueling or performing any maintenance to the  
generator set, always be sure the engine has stopped and that all rotating parts have also  
stopped. After stopping, certain components are still extremely hot so be careful not to get  
burned. Before servicing the generator set, be sure to disconnect the spark plug wires and  
the battery terminals to prevent accidental engine rotation or starting.  
WARNING: Inspect all wiring frequently and replace any damaged, broken or frayed wiring or wires with  
damaged insulation immediately. Electrical shock can cause serious or fatal injury.  
WARNING: Disconnect all electrical wires and load devices from generator power outlets before servicing  
the generator. Electrical shock can cause serious or fatal injury. Always treat electrical  
circuits as if they are energized.  
WARNING: Check fuel tank, fuel lines and their connections monthly for fuel leaks. Gasoline and diesel  
fuel are flammable and can cause fire, explosions, injury or death. If a leak is found, replace  
only with approved components.  
WARNING: The capacitor used in this generator can store and discharge a high voltage charge. Before  
working with or in the area of the capacitor, discharge the capacitor with a screwdriver with  
an insulated handle or insulated jumper wire. Seek expert advise before performing any  
maintenance.  
WARNING: Be extremely careful when flashing the generator. When the alternator cover is removed  
rotating parts and high voltage are present. Electrical shock can cause serious or fatal injury.  
Rotating parts can present extreme danger if clothing or body extremities are caught by the  
rotating part and can cause serious or fatal injury. Seek expert advise before performing any  
maintenance.  
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area  
where gasoline fumes could reach an ignition source and cause an explosion.  
Caution Statements  
Caution: The brass connecting tab on some 120VAC duplex receptacles have been removed. Each  
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect  
the brass tab that normally links both receptacles. If it is removed, be sure to remove the  
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will  
cause a direct short to the generator windings and cause possible generator damage.  
Caution: Avoid installing the generator set beside heat generating equipment, or directly below water  
or steam pipes or in the vicinity of corrosive substances or vapors, metal particles and dust.  
Heat can cause engine problems to develop and unwanted substances can cause rust or  
generator failure over time.  
Caution: Do not apply high voltage to windings in a moisturesaturated condition. Moisture can cause  
insulation breakdown, making it necessary to return the generator to the factory for repair,  
and consequent expense and loss of time.  
Caution: Use only original equipment or authorized replacement parts. Using the correct parts will  
assure continued safe operation as designed.  
Caution: Do not support the generator from the top of the wrap frame.  
Caution: Do not tamper with or change the engine speed. Engine speed is factory set to produce the  
correct voltage and output frequency.  
Caution: Never operate the engine without a muffler. The engine is designed to have the correct  
exhaust components installed and operating without these components can present a fire  
hazard, cause excessive exhaust gases and cause damage to engine. Inspect muffler  
periodically and replace if necessary.  
Caution: Operate the generator only on a level surface. Operation of the generator on an incline or  
slope may degrade engine lubrication and result in engine failure.  
Caution: Always fill fuel tank with clean fresh fuel before use. Never leave fuel in tank for long storage  
periods. Old fuel becomes stale and can damage the fuel system causing the engine not to  
start. Always drain the fuel tank after use before storage.  
MN2418  
Product Safety Information 1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-6 Product Safety Information  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
General Information  
Thank you for purchasing your Baldor Generator Set. This manual contains information you need to safely and efficiently  
install and operate your generator set. During the preparation of this manual every effort was made to ensure the  
accuracy of its contents. This manual describes only very basic engine information. A separate owner’s manual for the  
engine is supplied with this unit for your use. Please refer to the engine manual for information relative to engine  
operation, maintenance, recommendations and additional safety warnings.  
Copyright Baldor E 2006. All rights reserved.  
This manual is copyrighted and all rights are reserved. This document may not, in whole or in part, be copied or  
reproduced in any form without the prior written consent of Baldor Electric Company, Inc.  
Baldor Generators have earned the reputation of being high quality and dependable. We take pride in this fact and  
continue to keep our quality standards high on our list of priorities. We are also constantly researching new technological  
ideas to determine if they could be used to make our generator sets even better.  
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied  
warranties of fitness for any particular purpose. The information in this document is subject to change without notice.  
Baldor assumes no responsibility for any errors that may appear in this document.  
Limited Warranty  
Baldor will replace or repair free of charge any part or parts of the generator of their manufacture that are defective in  
workmanship and materials for a period of time as set forth in the Warranty Period chart below. All Baldor products  
requiring warranty service shall be transported or shipped freight prepaid to a Baldor Generator repair facility.  
Notification of the defect or problem, a description of the manner in which the Baldor generator is used, and the name,  
address and telephone number of the customer requiring warranty service must be included. Baldor is not responsible for  
removal and shipment of the Baldor product to the service center or for the reinstallation of the Baldor product upon its  
return to the customer, or any incidental or consequential damages resulting from the defect, removal, reinstallation,  
shipment or otherwise. Problems with Baldor products can be due to improper maintenance, faulty installation,  
nonBaldor additions or modifications, or other problems not due to defects in Baldor workmanship or materials. If a  
Baldor Generator repair facility determines that the problem with a Baldor product is not due to defects in Baldor  
workmanship or materials, then the customer will be responsible for the cost of any necessary repairs. Genset engines  
are covered under the engine manufacturers warranty. Proper engine maintenance is required. Any request for engine  
warranty or repair should be made directly with the engine manufacturers warranty center. See engine manufacturers  
data for applicable engine warranty periods and location of repair centers. This Limited Warranty and Service Policy  
represents Baldor’s sole and exclusive warranty obligation with respect to Baldor products. Baldor’s liability to a customer  
or any other person shall not exceed Baldor’s sales price of the applicable Baldor product. BALDOR DISCLAIMS ALL  
OTHER EXPRESSED AND IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A  
PARTICULAR PURPOSE AND MERCHANTABILITY.  
Warranty Period  
Generator Series  
Labor*  
1 Year  
Parts  
3 Years  
Portable Products (Premier, Powerchief,  
DG Series)  
Towable Products (TS)  
POW’R LITE Light Towers  
1 Year or 3,000 Hours  
1 Year or 3,000 Hours  
3 Years or 3,000 Hours  
3 Years or 3,000 Hours  
Light Fixture, Lamps and Ballasts are excluded  
from any warranty coverage  
3600 RPM Standby Systems  
(Some AE Models)  
1800 RPM Standby Systems  
(Some AE Models, DLC, GLC)  
1 Year or 1,000 Hours  
1 Year or 3,000 Hours  
3 Years or 1,000 Hours  
3 Years or 3,000 Hours  
Industrial Standby Systems  
Industrial Prime Power Systems  
International  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
2 Years or 1,000 Hours  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
*For products covered under labor coverage, travel expenses will be allowed up to 7 hours straight labor or 300 miles,  
whichever occurs first, and only applies to permanently wired and mounted products (AE, DLC, GLC, IDLC).  
You must save the purchase receipt. Proof of purchase, date, serial number and model number will be required for all  
portable and Towable products to qualify for any warranty consideration.  
A startup inspection form/warranty registration must be completed in its entirety and submitted to Baldor Generators  
within 30 days of startup to qualify for any warranty consideration, excluding: Portables, Towables and Light Towers.  
MN2418  
General Information 2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-2 General Information  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Receiving & Installation  
Receiving & Inspection When you receive your generator, there are several things you should do immediately.  
1. Observe the condition of the shipping container and report any damage immediately to  
the commercial carrier that delivered your system.  
2. Verify that the part number of the system you received is the same as the part number  
listed on your purchase order.  
3. If the system is to be stored for several weeks before use, be sure that it is stored in a  
location that conforms to published storage temperature and humidity specifications.  
Lifting the Generator  
When lift or hoist equipment is used to lift the generator and move it to position, be careful not to  
contact overhead wires or other obstacles. The generator weighs between 170 and 200 lbs.  
Use proper lift equipment and methods to avoid injury. Lift only by the tubular metal frame.  
Figure 3-1 PG6000 Generator  
Storage  
If you will not be using the generator set for a significant amount of time (3 months or longer) you  
should store the generator to prevent any problems that could arise from sitting idle. Please fully  
read the following guidelines prior to storing the unit.  
1. Remove all fuel from the engine’s fuel tank.  
2. Start the generator set and allow it to run out of fuel.  
3. Close all the fuel valves.  
Note: An alternative to draining the fuel from a gasoline engine is adding a fuel stabilizer, to  
minimize the formation of fuel gum deposits during storage (Follow the manufacturer’s  
directions). After the fuel stabilizer is added, run the generator set for 5 minutes to get the  
stabilizer into the carburetor. After shutting the engine off, be sure to close all the fuel  
valves.  
4. Drain the used oil from the engine’s crankcase and refill it with clean oil.  
5. Remove the spark plugs and pour1 oz. of clean engine oil into each cylinder. Put a rag  
over each spark plug port and pull the starting cord approximately 5 times to distribute  
the oil in the cylinder.  
6. Replace the spark plug(s) but do not connect the plug wires. This will help prevent  
accidental or unauthorized starting.  
7. Provide maintenance to the engine and generator set as described in the engine and  
generator maintenance sections of this manual.  
8. Cover any bare metal spots with paint or another type of rust preventative.  
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area  
where gasoline fumes could reach an ignition source and cause an explosion.  
MN2418  
Receiving & Installation 3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Physical Location  
The mounting location of the system is important. It should be installed in an area that is  
protected from direct harmful gases or liquids, dust, metallic particles, shock and vibration. It can  
only be installed in an outdoor location so the exhaust fumes are vented to the atmosphere. This  
system must never be installed inside an enclosed building, home, shop or garage etc.  
Several other factors should be carefully evaluated when selecting a location for installation:  
1. For effective cooling and maintenance, the generator should be mounted on a flat, smooth,  
non-flammable level surface. A concrete pad is ideal and provides a secure installation.  
2. The location for the generator must be dry. Never operate a generator in an area that  
has standing water or puddles.  
3. Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. It  
is important that the unit be operated in a reasonably clean environment.  
4
All engines give off considerable heat when running. The engine in your generator set  
uses air to keep it cool so it is important that the ambient temperature is cool and does  
not exceed 100°F (even while it is running). Where natural ventilation is inadequate a  
fan to boost circulation should be used.  
5. Exhaust gases from internal combustion engines are extremely poisonous. Never  
operate an engine indoors.  
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never  
breath exhaust fumes produced by a running engine. Only run the engine outdoors where  
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and  
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon  
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or  
incoherence. If you or anyone else experiences these symptoms, get out into fresh air  
immediately. Stop the engine and do not restart the engine until it has been inspected and if  
necessary repaired or reinstalled in a well ventilated area.  
6. All electrical equipment should be protected from excessive moisture. Failure to do so  
will result in deterioration of the insulation and may result in short circuits and a  
possible electrocution hazard.  
Installation  
The generator is completely assembled, tested and adjusted at the factory before it is shipped to  
you. External connections required at the time of installation are:  
1. Electrical Connections.  
2. Ground Connection.  
Note: The generator is shipped dry. This means no oil is in the engine crankcase and no battery  
is installed. You must refer to the engine manual and obtain the correct type and quantity  
of engine motor oil and the correct battery (if equipped for electric start).  
After installation, the post installation checks must be performed prior to starting the engine.  
After these checks have been performed and the system operation is verified to be good, refer to  
Section 5 Troubleshooting and Maintenance for periodic checks that must be performed at  
scheduled intervals to ensure continued operation with minimal problems.  
3-2 Receiving & Installation  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Connections All load connections are made at the panel using electrical cords with the proper  
mating plug for the receptacle being used. More than one receptacle can be used as long as the  
total load does not exceed the continuous rating of the generator.  
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician  
has installed an approved transfer switch. The National Electrical Code (NEC) requires that  
connection of a generator to any electrical circuit normally powered by means of an electric  
utility must be connected by means of approved transfer switch equipment so as to isolate  
the electrical circuit from the utility distribution system when the generator is operating.  
Failure to isolate the electrical circuits by such means may result in injury or death to utility  
power workers due to backfeed of electrical energy onto the utility lines.  
Use correct size insulated wire to connect the generator to the load. The gauge of the wire will  
depend on the distance to the load, the permissible voltage drop at the load, and the current  
required by the load. If you are not sure of the gauge wire needed for your application, consult a  
competent electrician. Using wire that is too small can result in fire hazard. Also, be sure the  
wire has the appropriate ratings for insulation and environment conditions.  
The correct mating connector must be used to fit the connectors provided on the operator panel  
Table 3-1 Single Phase Power Receptacle Description  
Electrical Connection Information (Receptacle Provided at Panel)  
Model  
Straight 120VAC  
(20Amp)  
Twist Lock 120/240VAC  
(30Amp)  
Rated Watts/  
(Full load Amps 120/240)  
PG6000  
2− 520R 120VAC  
1− L1430R 120/240VAC  
5700 / (44.2/22.1)  
Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.  
Figure 3-2 Receptacle Connections  
(GOLD)  
X
Ground  
120VAC  
G
NEMA  
L14−30R  
125/250V  
30A  
Y
(GOLD)  
W
(SILVER)  
NEMA 520R  
125V 20A  
120VAC  
Neutral  
MN2418  
Receiving & Installation 3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Frame Ground Connection  
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power  
before you ensure that grounds are connected. Electrical shock can cause serious or fatal  
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be  
connected to an approved earth ground. Local codes may also require proper grounding of  
generator systems.  
The NEC requires that the frame and exposed metal surfaces be at local ground reference  
potential to avoid electrical shock hazard. A local ground reference may require a driven earth  
ground conductor at the generator installation site. Make the ground connection as shown in  
earth at least 8 feet or as necessary to reach the water table.  
Figure 3-3 Frame Ground Connection  
Nut  
Washer  
Ground Wire Lug  
Washer  
Stud  
Frame  
Engine Oil  
Refer to the engine manual that was provided with your generator. Determine the correct type of  
engine oil and the amount specified by the engine manufacturer. Add the required amount of oil  
to bring the oil level to full.  
SUMMER  
OIL  
WINTER  
OIL  
OIL  
CAPACITY  
2.0 PTS  
MODEL  
PG6000  
SAE. 30  
5W/30  
Use of Electric Motor Loads  
Electric motors require much more current (amperes) to start them than to keep them running.  
Some motors, particularly splitphase motors are very difficult to start and require 5 to 7 times  
more current to start them. Repulsioninduction type motors are the easiest to start and normally  
only require 2 to 3 times as much current to start them.  
Most fractional horsepower motors take about the same amount of current to start them and  
keep them running. This is true whether they are the repulsioninduction type motor, capacitor  
type motor, or the splitphase type motor.  
Other factors that influence the amount of current needed to start a motor are:  
1. The type of load connected to the motor. If the electric motor is connected to a hard  
starting load such as an air compressor it will require more starting current. If the same  
electric motor is connected to a light load such as a heater or power saw it will require  
less starting current.  
2. The brand or design of the electric motor. The expected starting current for a  
particular size motor will vary depending on the brand of the electric motor as well as  
the type of electric motor (Split Phase, capacitor, Repulsioninduction type, etc.)  
3. The condition of the electric motor. A clean motor with free turning bearings will  
require less starting currents than a similar type motor that is dirty and the bearings are  
not as free turning as they used to be.  
Optional Wheel Kit PDG2 2 Wheel Dolly Kit; and PDG4 4 Wheel Dolly Kit  
An optional 2 or 4 wheel dolly kit is available for portable generators. If you have purchased one  
of these kits, refer to MN2409 for the installation instructions.  
3-4 Receiving & Installation  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Section 4  
Operation  
Operator Control Panel  
Figure 4-1 Operator Panels  
AC Circuit Breakers  
120VAC 120VAC  
20A 20A  
240VAC  
22A  
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician  
has installed an approved transfer switch. The National Electrical Code (NEC) requires that  
connection of a generator to any electrical circuit normally powered by means of an electric  
utility must be connected by means of approved transfer switch equipment so as to isolate  
the electrical circuit from the utility distribution system when the generator is operating.  
Failure to isolate the electrical circuits by such means may result in injury or death to utility  
power workers due to backfeed of electrical energy onto the utility lines.  
AC Circuit Breakers Provide overcurrent protection for the generator output. When tripped, the plunger (in  
center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger into  
the breaker to reset the breaker. Correct any overloads then restore the loads.  
Receptacles Receptacles are provided to allow easy connection of electrical loads. Never connect this  
generator to any buildings electrical system unless a licensed electrician has installed an  
approved transfer switch. Multiple receptacles may be used at the same time provided the total  
electrical load does not exceed the generators rated output.  
120Volts PG6000 has 2 outlets each rated 125VAC at 20 Amperes.  
(NEMA 520R Duplex receptacle125VAC at 20 Amperes).  
240 Volts Twist lock NEMA L1430R receptacle rated 250Volts at 30 Amperes.  
Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.  
PreStart Checks Before the engine is started, several things must first be checked.  
1. Place the generator set in an open, dry, well ventilated and reasonably level location.  
2. If grounding is required for your application, check to make sure your unit is grounded  
properly (see Section3).  
3. Check the engine’s oil level and add oil if necessary to bring it to the level  
recommended by the engine manufacturer.  
4. Check the fuel level and add fuel to within 1/2 inch of the fill tube if necessary.  
5. Open the fuel valve on the fuel tank (and on the engine if installed).  
6. Check the fuel system for fuel leaks and repair them prior to starting the engine. Wipe  
up any fuel spills before starting the engine.  
7. Disconnect or “turn off” all external loads.  
8. Make sure all circuit breakers are set (pushed in).  
9. Tighten any bolts or nuts that may have loosened due to vibration.  
10. Be sure all extension cords are in good condition before starting the generator.  
Use only U.L. listed extension cords and connectors.  
MN2418  
Operation 4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
StartUp Procedure  
Recoil Start  
1. Move the engine’s choke lever to the “Choke/Start” position. If the engine is warm or if  
the ambient air temperature is high; try starting the engine without choking it.  
2. Move the Control Panel Engine “ON/OFF” switch to “ON” (if equipped).  
3. Pull lightly on the recoil grip until you feel significant resistance, then pull sharply. Allow  
the recoil to gently rewind into the recoil housing. See your engine manual for  
instructions specific to your unit. Do not allow the recoil rope to “snap back” into the  
recoil housing.  
Note: If the engine does not start after several attempts, smell for fuel near the air cleaner. If  
there is a significant gasoline smell coming from the air cleaner, turn the choke lever off  
and attempt to start the engine with the choke off.  
4. When the engine starts, turn the engine’s choke lever to the “OFF” position.  
5. Power is now present at the receptacles.  
Connect or “turn on” the loads you wish to operate.  
Stopping Procedure  
1. Disconnect or “Turn Off” all loads connected to the generator set.  
2. Move the Control Panel Engine “ON/OFF” switch to “OFF” (if equipped).  
3. Push the engine stop switch if so equipped.  
OR  
Turn the engine key switch to the “OFF” position.  
4. Turn all fuel valves off.  
4-2 Operation  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5  
Troubleshooting and Maintenance  
Maintenance  
This manual contains only very minimal engine maintenance instructions. Refer to the engine  
manufacturer’s owner’s manual for specific engine maintenance instructions for your generator  
set. Any maintenance instructions or recommendations in the engine owner’s manual take  
precedence over any of the following general recommendations.  
General:  
1. Inspect the fuel system for leaks. Replace all defective components immediately.  
2. Inspect and replace any fuel line that shows signs of deterioration.  
3. Inspect all fuel clamps to ensure they are tight.  
4. Make sure the fuel cap fits snugly on the fuel tank and that the fuel tank does not leak.  
5. Inspect the external wire cables and connectors used with the generator set for cuts,  
frayed insulation, or loose connections. Repair or replace damaged parts before use.  
6. The engine should be checked for proper speed setting(s).  
Prior to adjusting the engine speed, turn the auto idler switch to “OFF” (if present).  
Make sure that the auto idler magnet does not touch the throttle lever of the engine  
when running.  
a. Disconnect all electrical loads and start the engine.  
b. Adjust the engine speed to 3720 RPM (62 Hz) with no load speed.  
Engine:  
1. Clean and/or replace any fuel, oil, and/or air filters per the engine manufacturers’  
guidelines.  
2. Check oil level regularly; at least every 5 to 8 operating hours. Maintain the proper oil  
level.  
3. Change the oil as is recommended in the engine manufacturer’s owner’s manual.  
4. Replace the spark plug(s) as is recommended by the engine manufacturer.  
5. Clean the cooling fins on the engine to keep the engine’s heat dissipation potential at  
it’s maximum.  
6. Inspect and clean all governor and carburetor linkages so they operate properly.  
7. Inspect the recoil starting rope for any damage and replace it if necessary (if  
applicable).  
8. Clean the trash screen around the recoil starter or other cooling air intake.  
Alternator: ( also called Generator End)  
This generator set must be run at its proper speed to obtain the correct electrical power at its  
output. All engines have a tendency to slow down when a load is applied to it. The engine  
governor is designed to hold the operating speed as nearly constant as possible. When the  
electrical load is increased, the engine is more heavily loaded and engine speed drops slightly.  
This slight decrease in engine speed results in a slight decrease in generator voltage and  
frequency output. This voltage and frequency variation has no appreciable effect in the operation  
of motors, lights, and most appliances and tools. However, timing devices and clocks will not  
keep perfect time when used on this generator.  
1. Clean the generator set and remove any and all dust, dirt, or other foreign material.  
2. Inspect and clean the cooling air intake and exhaust louvers of the generator end.  
Make sure they are clean. Remove dirt or any buildup that may restrict the cooling air  
flow.  
3. Clean the generator set and its components with a damp cloth or sponge.  
Never use a water hose or pressure washer as this may damage electrical  
components.  
4. Inspect and replace any control panel components that are broken or not working  
properly (receptacles, circuit breakers, switches, etc.)  
MN2418  
Troubleshooting and Maintenance 5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problems and Solutions  
Some of the more common problems are listed in Table 5-1. This information is intended to be a  
for all types of problems. Procedures that require in depth knowledge or skills (like flashing the  
field) should be referred to generator service facility.  
Table 5-1 Troubleshooting Guide  
Problem  
Possible Cause  
Remedy  
Engine will not start  
No fuel.  
Restricted air flow.  
No spark.  
Check that fuel valves are ON. Check fuel level in fuel tank.  
Check/replace air filter.  
Check/replace spark plug(s). Check that engine switch is in Start  
position.  
Engine starts but will not run smoothly  
Engine overheats  
Fuel or ignition problem  
Refer to engine manual.  
Excessive load  
Debris or dirt buildup on engine  
Remove one or more electrical loads.  
Remove debris. Clean engine surfaces to allow cooling.  
No output voltage  
Ciruit Breaker tripped or defective.  
Loss of residual magnetism in exciter  
field poles.  
Reset circuit breaker or replace if required.  
Flash field.  
Open in stator windings  
Defective exciter circuit.  
Check for continuity in windings. Return to factory for repair if open.  
Check/replace diode and capacitor and flash the field.  
Output voltage varies  
Irregular speed (fixed speed mode)  
Fluctuating speed (fixed speed mode)  
Check engine for malfunction or load for fluctuation  
Stabilize load. The addition of a lamp load (resistance load) may  
compensate partially for load changes caused by intermittent motor  
operation. Do not overload.  
Loose terminal or load connections  
Defective bearing (uneven air gap)  
Verify all connections are proper and check tighness torque of  
terminals.  
Replace worn bearing  
Low output voltage  
Low engine speed  
Excessive load  
Check that the Auto Idle switch is in OFF position (if installed).  
Check engine for malfunction or system for overload. Reduce load.  
Verify all connections are proper and check tighness torque of  
terminals.  
Test field coils for possible short by checking resistance with an  
ohmmeter or resistancebridge. Return rotor assembly to service  
center for repair if alternator field coils are shorted.  
High resistance connections −  
connections will be warm or hot  
Shorted field  
Reduce inductive (motor) load. Some AC motors use about the  
same current regardless of load. Do not use motors of greater  
horsepower rating than is necessary to move the mechanical load.  
Low power factor  
High output voltage  
Excessive speed (fixed speed mode)  
Check engine for malfunction  
Electrical shock when frame is touched  
Static charge.  
Grounded armature or field coil.  
Ground generator frame at local reference ground (see Section 3).  
Return to service center for repair  
Mechanical noise  
Defective bearing  
Rotor rubbing on stator  
Replace bearing  
Bad bearing − replace.  
Bent shaft − return to service center.  
Loose end bell − tighten;  
Loose drive Discs − tighten  
Loose or misaligned coupling  
Tighten; align coupling and alternator shaft to engine shaft.  
Service  
Parts  
Service for your generator can be obtained from a generator service center. Please have the  
following information available:  
The model number and serial number of the generator set.  
A complete and accurate description of the problem.  
Parts for your generator can be obtained from a generator service center. Please have the  
following information available:  
The model number and serial number of the generator set.  
A complete and accurate description of the part (part number if known).  
Note: Engine parts can usually be obtained by using the information in the engine  
manufacturer’s owner’s manual.  
5-2 Troubleshooting and Maintenance  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix A  
PG6000 Connections  
Caution: The brass connecting tab on some 120VAC duplex receptacles has been removed. Each  
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect  
the brass tab that normally links both receptacles. If it is removed, be sure to remove the  
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will  
cause a direct short to the generator windings and cause possible generator damage.  
Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.  
MN2418  
PowerchiefR Series A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure A-2 PG6000 Wiring Diagram  
A-2 PowerchiefR Series  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B  
Special Information for California  
Information in this Appendix applies only to products operated in the state of California.  
LIMITED WARRANTY ON EVAPORATIVE EMISSION CONTROL SYSTEMS CALIFORNIA ONLY  
The California Air Resources Board (CARB) and Baldor Generators (herein ”Baldor”) are pleased to explain the Evaporative Emission  
Control System (EECS) warranty on your model year 2006 and later generator. In California, new generators must be designed, built  
and equipped to meet the State’s stringent antismog standards. Baldor must warrant the EECS on your generator for the period of  
time listed below provided there has been no abuse, neglect or improper maintenance of your generator. Your EECS may include parts  
such as the carburetor, fuelinjection system, ignition system, catalytic converter, fuel tanks, fuel lines, fuel caps, valves, canisters,  
filters, vapor hoses, camps, connectors, and other associated emissionrelated components. Where a warrantable condition exists,  
Baldor will repair your generator at no cost to you including diagnosis, parts and labor for the time period set forth below.  
BALDOR EVAPORATIVE EMISSION CONTROL SYSTEM DEFECTS WARRANTY COVERAGE  
This evaporative emission control system is warranted for a period of two (2) years, subject to the provisions set forth below. If any  
covered evaporative emissionrelated part on your equipment is defective, the part will be repaired or replaced by Baldor.  
OWNER’S WARRANTY RESPONSIBILITIES  
As the generator owner, you are responsible for performance of all the required maintenance listed in your owner’s manual. Baldor  
recommends that you retain all receipts covering maintenance on your generator, but Baldor cannot deny EECS warranty claims solely  
for the lack of receipts. As the generator owner, you should however be aware that Baldor may deny you warranty coverage if your  
generator or a part has failed due to abuse, neglect, or improper maintenance or unapproved modifications. You are responsible for  
presenting your generator to an authorized Baldor service center as soon as the problem exists. The warranty repairs should be  
completed in a reasonable amount of time, not to exceed 30 days from the date of delivery to the authorized Baldor service center.  
If you have a question regarding your warranty coverage, you should contact Baldor Generator Technical Support at  
14796464711.  
CONDITIONS AND RESTRICTIONS EVAPORATIVE EMISSIONS CONTROL SYSTEM WARRANTY COVERAGE  
Baldor warrants to the ultimate purchaser and each subsequent purchaser that the generator is: (1) designed, built and equipped so  
as to conform with all applicable CARB EECS regulations; (2) free from defects in materials and workmanship that cause the failure  
of a warranted part to be identical in all material respects to that part as described in Baldor’s application of certification to CARB; (3)  
the warranty period begins on the date the generator is delivered to an ultimate purchaser or first placed into service. The warranty  
period is two years.  
Subject to certain conditions and exclusions as stated below, the warranty on EVAP emissionrelated parts is as follows: Any warranted  
part that is not scheduled for replacement as required maintenance in the written instructions supplied, is warranted for the warranty  
period. If the part fails during the period of warranty coverage, the part will be repaired or replaced by Baldor at an authorized Baldor  
service center at no charge to the owner. Any such part repaired or replaced under warranty will be warranted for the remainder of the  
EECS warranty period. Any warranted part that is scheduled only for regular inspection in the written instructions supplied is warranted  
for the EECS warranty period. Any such part repaired or replaced under warranty will be warranted for the remaining EECS warranty  
period. Any warranted part that is scheduled for replacement as required maintenance in the written instructions supplied is warranted  
for the period of time before the first scheduled replacement date for that part. If the part fails before the first schedule replacement,  
the part will be repaired or replaced by Baldor. Any such part repaired or replaced under warranty will be warranted for the remainder  
of the period prior to the first scheduled replacement point for the part. Notwithstanding the provisions herein, EECS warranty services  
or repairs will be provided at designated service facilities to service the subject equipment. The generator owner will not be charged  
for diagnostic labor that leads to the determination that an EECS warranted part is defective, if the work is performed at an authorized  
Baldor service center. Baldor is liable for damages to other Baldor generator equipment components proximately caused by a failure  
under warranty of any EECS warranted part. Throughout the EECS warranty period, Baldor will maintain a supply of EECS warranted  
parts sufficient to meet the expected demands for such parts. Any replacement part may be used in the performance of any EECS  
warranty maintenance or repairs and must be provided without charge to the owner. Such use will not reduce the warranty obligations  
of Baldor. Addon or modified parts that are not exempted by the California Air Resources Board may not be used. The use of any  
nonexempted addon or modified parts by the ultimate purchaser will be grounds for disallowing warranty claims. Baldor will not be  
liable to warrant failures of warranted parts caused by the use of a nonexempted addon or modified part. This limited warranty does  
not cover any part which malfunctions, fails or is damaged due to failure to follow the maintenance and operating instructions provided  
with the generator.  
EVAPORATIVE EMISSIONS CONTROL SYSTEM WARRANTED PARTS: The repair or replacement of any warranted part otherwise  
eligible for warranty coverage may be excluded from such warranty coverage if Baldor demonstrates that the generator has been  
abused, neglected, or improperly maintained, and that such abuse, neglect, or improper maintenance was the direct cause of the need  
for repair or replacement of the part. That notwithstanding, any adjustment of a component that has a factory installed, and properly  
operating, adjustmentlimiting device is still eligible for warranty coverage. Parts covered under the California Evaporative Emissions  
Warranty are (1) low permeation fuel lines and fittings.  
MN2418  
Special Information for California B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Engine exhaust from this product contains chemicals known  
to the state of California to cause cancer, birth defects and  
other reproductive harm.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Battery posts, terminals and related accessories are known to  
the state of California to cause cancer, birth defects and other  
reproductive harm.  
B-2 Special Information for California  
MN2418  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Baldor District Offices  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Engine exhaust from this product contains chemicals known  
to the state of California to cause cancer, birth defects and  
other reproductive harm.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Battery posts, terminals and related accessories are known to  
the state of California to cause cancer, birth defects and other  
reproductive harm.  
BALDOR ELECTRIC COMPANY  
P.O. Box 2400  
Ft. Smith, AR 72901--2400  
(479) 646--4711  
Fax (479) 648--5792  
© Baldor Electric Company  
MN2418  
Printed in USA  
8/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Adaptec Microscope Magnifier 2120S User Manual
ADC Network Router 1900 PCS User Manual
ADC TV Converter Box ADDC1 User Manual
Addonics Technologies Blu ray Player DDU7SAS User Manual
AEG Convection Oven BP5003021 User Manual
AEG Washer 76730 User Manual
Amana Dishwasher W10261420A User Manual
Atlona Switch AT SDI81 User Manual
Atmel Stereo Amplifier ATR7040 User Manual
Avocent Speaker System EMS1000P User Manual