PG 6000 Generator
Installation & Operating Manual
8/06
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Section 1
Product Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Section 2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Section 3
Receiving & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Receiving & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Lifting the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Frame Ground Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Recommended Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Use of Electric Motor Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Optional Wheel Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Section 4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Operator Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Pre−Start Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Start−Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Stopping Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Section 5
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Problems and Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Appendix A
PG6000 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Appendix B
Special Information for California . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
MN2418
Table of Contents i
Download from Www.Somanuals.com. All Manuals Search And Download.
ii Table of Contents
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1
Product Safety Information
Safety Notice
Be sure that you are completely familiar with the safe operation of this equipment. This
equipment may be connected to other machines that have rotating parts or parts that are
controlled by this equipment. Improper use can cause serious or fatal injury. Always
disconnect all electrical loads before starting the generator.
Installation and repair procedures require specialized skills with electrical generating equipment.
Any person that installs or repairs this generator must have these specialized skills to ensure that
this generating unit is safe to operate. Seek expert advise for repairs or any questions you may
have about the safe installation and operation of this system.
The precaution statements are general guidelines for the safe use and operation of this
generator. It is not practical to list all unsafe conditions. Therefore, if you use a procedure that is
not recommended in this manual you must determine if it is safe for the operator and all
personnel in the proximity to the generator and connected loads. If there is any question of the
safety of a procedure please seek expert advise before starting the generator.
This equipment contains high voltages. Electrical shock can cause serious or fatal injury. Only
qualified personnel should attempt the start−up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are
driven by this equipment. Improper use can cause serious or fatal injury. Only qualified
personnel should attempt the start−up procedure or troubleshoot this equipment.
−
System documentation must be available to anyone that operates this equipment at all
times.
−
−
Keep non-qualified personnel at a safe distance from this equipment.
Only qualified personnel familiar with the safe installation, operation and maintenance
of this device should attempt start-up or operating procedures.
−
−
Always stop engine before making or removing any connections.
Always stop engine and allow it to cool before refueling.
Responsibility
When your generator is delivered, it becomes the responsibility of the owner/operator of the
generator set to prevent unsafe conditions and operation of the equipment. Some
responsibilities include (but are not limited to) the following:
1. It is the responsibility of the owner/operator of this generator to ensure that this
equipment is correctly and safely installed.
2. It is the responsibility of the owner/operator of this generator to ensure that this
equipment, when installed fully complies with all federal, state and local codes.
3. It is the responsibility of the owner/operator of this generator to ensure that any person
operating this equipment has been properly trained.
4. It is the responsibility of the owner/operator of this generator to ensure that any person
operating this equipment has access to all manuals and information required for the
safe use and operation of this equipment.
5. It is the responsibility of the owner/operator of this generator to ensure that it is properly
maintained and safety inspected at regular scheduled intervals.
6. It is the responsibility of the owner/operator of this generator to ensure that any person
who has not been trained on the safe use of this equipment does not have access to
this equipment.
Read This Manual Thoroughly
If you do not understand any concept, any procedure, any safety warning statement, any safety
caution statement or any portion of this manual, seek expert advise. We are happy to make sure
you understand the information in this manual so that you can safely enjoy the full use of this
generator.
MN2418
Product Safety Information 1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Precaution Statements Used In This Manual
There are three classifications of precautionary statements used in this manual. The most critical
is a WARNING statement, then the Caution statement and the least critical is the Note
statement. The usage of each statement is as follows:
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in injury or
death.
Caution: Indicates a potentially hazardous situation which, if not avoided, could result in damage to
property.
Note:
Additional information that is not critical to the installation or operation.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS − This manual contains important instructions for the generator that should
be followed during installation, operation and maintenance of the generator.
For ease of reading, the Warning statements are divided into four categories: Operation, Burn, Installation,
and Maintenance.
Operation
WARNING: Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death. For
storage or refueling handle fuel with care and only in clean, approved, properly marked safety
fuel containers.
WARNING: Do not overfill the fuel tank. Only fill the tank to within 1/2, of the top of the tank to allow
space for fuel expansion. Overfilling of tank may cause fuel to spill out onto engine and
cause fire or explosion.
WARNING: Clean up fuel spills by wiping completely dry before starting engine. Gasoline and diesel fuel
are flammable and can cause fire, explosions, injury or death.
WARNING: Make sure the fuel cap is completely and securely closed after refueling to prevent spillage.
Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death.
WARNING: Never operate this generator in a manner other than as described in this manual. Operation
in any manner not described in this manual should be considered unsafe and should not be
attempted. Never start the engine unless you have first verified that the installation and
operation of the generator are as described in this manual.
WARNING: Be sure that you are completely familiar with the safe operation of this equipment. This
equipment may be connected to other machines that have rotating parts or parts that are
controlled by this equipment. Improper use can cause serious or fatal injury.
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never
breath exhaust fumes produced by a running engine. Only run the engine outdoors where
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or
incoherence. If you or anyone else experiences these symptoms, get out into fresh air
immediately. Stop the engine and do not restart the engine until it has been inspected and if
necessary repaired or reinstalled in a well ventilated area.
WARNING: Hot exhaust gasses must never be directed toward anything that may catch fire or explode.
WARNING: This generator must not be used on or near any forest covered, brush covered, or grass
covered land unless the engine’s exhaust system is equipped with a spark arrestor. The
spark arrestor must be maintained in effective working order by the operator.
WARNING: Some parts of this generator rotate during operation. Rotating parts can present extreme
danger if clothing or body extremities are caught by the rotating part and can cause serious
or fatal injury. Never touch a part of the generator until the engine has been stopped and all
rotating parts are completely stopped. Also, disconnect the spark plug wires and battery
connection to prevent accidental engine rotation during servicing.
WARNING: Never move a generator set that is running. Loads should be connected and position secure
before starting the engine. Hazards are caused by moving a generator set that is running.
Continued on next page.
1-2 Product Safety Information
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Warning Statements Continued
WARNING: Be sure that you understand how to stop the engine quickly in case of an emergency situation.
Become familiar with the controls and safety systems provided with this generator set.
WARNING: Always wear safety glasses with side shields and hearing protection when working near the
generator.
WARNING: Improper operation may cause violent motion of connected equipment. Be certain that
unexpected movement will not cause injury to personnel or damage to equipment.
WARNING: Never operate the generator set indoors or in a poorly ventilated area such as a tunnel or
cave. Exhaust fumes are extremely dangerous to all personnel that are in or in contact with
that area.
WARNING: Never permit anyone to operate the generator without proper instructions. Be sure to keep a
copy of this manual with the generator so that all users can be properly informed of its safe
operation.
WARNING: Never allow children or pets to be in the area where the generator is running. The generator
and the equipment being powered by the generator may cause injury or death.
WARNING: Never operate the generator unless all guards, covers, shields and other safety items are
properly installed.
WARNING: Do not put hands, feet, tools clothing or other objects near rotating parts such as drive shaft,
pulley, belt etc. Rotating parts cause extremely dangerous situations because they can catch
loose clothing or extremities and cause serious or fatal injury.
WARNING: When operating this generator remain alert at all times. Never operate machinery when
physically or mentally fatigued, or while under the influence of alcohol, drugs or medication.
WARNING: Never operate the engine when the air cleaner is removed. An engine backfire can cause
serious burns.
WARNING: High voltage is present whenever engine is running. Electrical shock can cause serious or
fatal injury. Never operate electrical equipment while standing in water, on wet ground or with
wet hands, feet or shoes or while barefoot.
WARNING: High voltage is present whenever the engine is running. Electrical shock can cause serious
or fatal injury. Always stop engine before connecting or disconnecting power cords or
external devices.
WARNING: Do not smoke near generator during operation or while refueling. Gasoline and diesel fuel are
flammable and can cause fire, explosions, injury or death.
WARNING: Stop engine and allow engine to cool before refueling. Gasoline and diesel fuel are flammable
and can cause fire, explosions, injury or death.
WARNING: Never store the generator with fuel in the tank. Never store the generator indoors or in an
enclosed area or in a poorly ventilated enclosure where fumes may reach an open flame,
electrical spark or pilot light as on a furnace, water heater, clothes dryer, etc. Gasoline and
diesel fuel are flammable and can cause fire, explosions, injury or death.
WARNING: Allow generator to cool before transporting it or storing it. Always drain fuel from tank after
generator has cooled.
WARNING: When transporting the generator (especially over rough roads) always drain the fuel tank to
prevent leakage or spillage of fuel. Gasoline and diesel fuel are flammable and can cause fire,
explosions, injury or death.
WARNING: Operate the generator only on a level surface. If the generator is tilted during operation, fuel
spillage may result. Gasoline and diesel fuel are flammable and can cause fire, explosions,
injury or death.
WARNING: Keep generator at least three feet away from buildings and other structures.
WARNING: Keep generator away from flammable or hazardous materials (trash, rags, lubricants,
explosives, paints etc.) and grass or leaf build up.
WARNING: Keep a fire extinguisher near the generator while generator is in use. An extinguisher rated
“ABC” by the National Fire Protection Association is appropriate.
Continued on next page.
MN2418
Product Safety Information 1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Warning Statements Continued
Burn
WARNING: Parts of this generator are extremely hot during and after operation. To prevent severe burns,
do not touch any part of the generator until you have first determined if the part is hot. Wear
protective clothing and after use allow sufficient time for parts to cool before touching any
part of the generator.
WARNING: Do not touch the hot exhaust parts or the high voltage spark plug or coil terminals of the
engine. Although spark plug voltages are not normally lethal, a sudden involuntary jerk of the
hand or body part caused by contact with high voltage or a hot surface can result in injury to
yourself or others.
Installation
WARNING: Installation and repair procedures requires specialized skills with electrical generating
equipment and small engine systems. Any person that installs or performs repairs must have
these specialized skills to ensure that the generator set is safe to operate.
WARNING: Be sure all wiring complies with the National Electrical Code (NEC) and all regional and local
codes or CE Compliance. Improper wiring may cause a hazardous condition and exposure to
electrical hazards can cause serious injury or death.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power
before you ensure that grounds are connected. Electrical shock can cause serious or fatal
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be
connected to an approved earth ground. Local codes may also require proper grounding of
generator systems.
WARNING: Place protective covers over all rotating parts such as drive shaft, pulley, belt etc. Rotating
parts cause extremely dangerous situations because they can catch loose clothing or
extremities and cause serious or fatal injury.
WARNING: Unauthorized modification of a generator set may make the unit unsafe for operation or may
impair the operation of the unit. Never start a generator set that has been modified or
tampered with. Be sure that all covers and guards are properly installed and that the unit is
safe before starting the engine. If you are unsure, seek expert advise before starting the
engine.
WARNING: When moving the generator, use reasonable caution. Be careful where you place fingers and
toes to prevent injury “Pinch Points”. Never try to lift a generator without a hoist or lift means
because they are heavy and bodily injury may result.
WARNING: When transporting a generator (especially if it has wheel option installed) secure the unit to
prevent movement during transport.
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
WARNING: Circuit overload protection must be provided in accordance with the National Electrical Code
and local regulations.
WARNING: Have electrical circuits and wiring installed and checked by licensed electrician or qualified
technician. Electrical shock can cause serious or fatal injury.
WARNING: Incorrect installation of this generator set could result in property damage, injury or death.
Connection of the generator to its fuel source must be done by a qualified professional
technician or contractor.
Continued on next page.
1-4 Product Safety Information
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Warning Statements Continued
Maintenance
WARNING: Before servicing the generator set, be sure to disconnect the spark plug(s) to prevent
accidental engine starting.
WARNING: Before cleaning, inspecting, repairing, refueling or performing any maintenance to the
generator set, always be sure the engine has stopped and that all rotating parts have also
stopped. After stopping, certain components are still extremely hot so be careful not to get
burned. Before servicing the generator set, be sure to disconnect the spark plug wires and
the battery terminals to prevent accidental engine rotation or starting.
WARNING: Inspect all wiring frequently and replace any damaged, broken or frayed wiring or wires with
damaged insulation immediately. Electrical shock can cause serious or fatal injury.
WARNING: Disconnect all electrical wires and load devices from generator power outlets before servicing
the generator. Electrical shock can cause serious or fatal injury. Always treat electrical
circuits as if they are energized.
WARNING: Check fuel tank, fuel lines and their connections monthly for fuel leaks. Gasoline and diesel
fuel are flammable and can cause fire, explosions, injury or death. If a leak is found, replace
only with approved components.
WARNING: The capacitor used in this generator can store and discharge a high voltage charge. Before
working with or in the area of the capacitor, discharge the capacitor with a screwdriver with
an insulated handle or insulated jumper wire. Seek expert advise before performing any
maintenance.
WARNING: Be extremely careful when flashing the generator. When the alternator cover is removed
rotating parts and high voltage are present. Electrical shock can cause serious or fatal injury.
Rotating parts can present extreme danger if clothing or body extremities are caught by the
rotating part and can cause serious or fatal injury. Seek expert advise before performing any
maintenance.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion.
Caution Statements
Caution: The brass connecting tab on some 120VAC duplex receptacles have been removed. Each
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect
the brass tab that normally links both receptacles. If it is removed, be sure to remove the
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will
cause a direct short to the generator windings and cause possible generator damage.
Caution: Avoid installing the generator set beside heat generating equipment, or directly below water
or steam pipes or in the vicinity of corrosive substances or vapors, metal particles and dust.
Heat can cause engine problems to develop and unwanted substances can cause rust or
generator failure over time.
Caution: Do not apply high voltage to windings in a moisture−saturated condition. Moisture can cause
insulation breakdown, making it necessary to return the generator to the factory for repair,
and consequent expense and loss of time.
Caution: Use only original equipment or authorized replacement parts. Using the correct parts will
assure continued safe operation as designed.
Caution: Do not support the generator from the top of the wrap frame.
Caution: Do not tamper with or change the engine speed. Engine speed is factory set to produce the
correct voltage and output frequency.
Caution: Never operate the engine without a muffler. The engine is designed to have the correct
exhaust components installed and operating without these components can present a fire
hazard, cause excessive exhaust gases and cause damage to engine. Inspect muffler
periodically and replace if necessary.
Caution: Operate the generator only on a level surface. Operation of the generator on an incline or
slope may degrade engine lubrication and result in engine failure.
Caution: Always fill fuel tank with clean fresh fuel before use. Never leave fuel in tank for long storage
periods. Old fuel becomes stale and can damage the fuel system causing the engine not to
start. Always drain the fuel tank after use before storage.
MN2418
Product Safety Information 1-5
Download from Www.Somanuals.com. All Manuals Search And Download.
1-6 Product Safety Information
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2
General Information
Thank you for purchasing your Baldor Generator Set. This manual contains information you need to safely and efficiently
install and operate your generator set. During the preparation of this manual every effort was made to ensure the
accuracy of its contents. This manual describes only very basic engine information. A separate owner’s manual for the
engine is supplied with this unit for your use. Please refer to the engine manual for information relative to engine
operation, maintenance, recommendations and additional safety warnings.
Copyright Baldor E 2006. All rights reserved.
This manual is copyrighted and all rights are reserved. This document may not, in whole or in part, be copied or
reproduced in any form without the prior written consent of Baldor Electric Company, Inc.
Baldor Generators have earned the reputation of being high quality and dependable. We take pride in this fact and
continue to keep our quality standards high on our list of priorities. We are also constantly researching new technological
ideas to determine if they could be used to make our generator sets even better.
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied
warranties of fitness for any particular purpose. The information in this document is subject to change without notice.
Baldor assumes no responsibility for any errors that may appear in this document.
Limited Warranty
Baldor will replace or repair free of charge any part or parts of the generator of their manufacture that are defective in
workmanship and materials for a period of time as set forth in the Warranty Period chart below. All Baldor products
requiring warranty service shall be transported or shipped freight pre−paid to a Baldor Generator repair facility.
Notification of the defect or problem, a description of the manner in which the Baldor generator is used, and the name,
address and telephone number of the customer requiring warranty service must be included. Baldor is not responsible for
removal and shipment of the Baldor product to the service center or for the reinstallation of the Baldor product upon its
return to the customer, or any incidental or consequential damages resulting from the defect, removal, reinstallation,
shipment or otherwise. Problems with Baldor products can be due to improper maintenance, faulty installation,
non−Baldor additions or modifications, or other problems not due to defects in Baldor workmanship or materials. If a
Baldor Generator repair facility determines that the problem with a Baldor product is not due to defects in Baldor
workmanship or materials, then the customer will be responsible for the cost of any necessary repairs. Genset engines
are covered under the engine manufacturers warranty. Proper engine maintenance is required. Any request for engine
warranty or repair should be made directly with the engine manufacturers warranty center. See engine manufacturers
data for applicable engine warranty periods and location of repair centers. This Limited Warranty and Service Policy
represents Baldor’s sole and exclusive warranty obligation with respect to Baldor products. Baldor’s liability to a customer
or any other person shall not exceed Baldor’s sales price of the applicable Baldor product. BALDOR DISCLAIMS ALL
OTHER EXPRESSED AND IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE AND MERCHANTABILITY.
Warranty Period
Generator Series
Labor*
1 Year
Parts
3 Years
Portable Products (Premier, Powerchief,
DG Series)
Towable Products (TS)
POW’R LITE Light Towers
1 Year or 3,000 Hours
1 Year or 3,000 Hours
3 Years or 3,000 Hours
3 Years or 3,000 Hours
Light Fixture, Lamps and Ballasts are excluded
from any warranty coverage
3600 RPM Standby Systems
(Some AE Models)
1800 RPM Standby Systems
(Some AE Models, DLC, GLC)
1 Year or 1,000 Hours
1 Year or 3,000 Hours
3 Years or 1,000 Hours
3 Years or 3,000 Hours
Industrial Standby Systems
Industrial Prime Power Systems
International
1 Year or 1,000 Hours
1 Year or 1,000 Hours
1 Year or 1,000 Hours
2 Years or 1,000 Hours
1 Year or 1,000 Hours
1 Year or 1,000 Hours
*For products covered under labor coverage, travel expenses will be allowed up to 7 hours straight labor or 300 miles,
whichever occurs first, and only applies to permanently wired and mounted products (AE, DLC, GLC, IDLC).
You must save the purchase receipt. Proof of purchase, date, serial number and model number will be required for all
portable and Towable products to qualify for any warranty consideration.
A start−up inspection form/warranty registration must be completed in its entirety and submitted to Baldor Generators
within 30 days of start−up to qualify for any warranty consideration, excluding: Portables, Towables and Light Towers.
MN2418
General Information 2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
2-2 General Information
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3
Receiving & Installation
Receiving & Inspection When you receive your generator, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to
the commercial carrier that delivered your system.
2. Verify that the part number of the system you received is the same as the part number
listed on your purchase order.
3. If the system is to be stored for several weeks before use, be sure that it is stored in a
location that conforms to published storage temperature and humidity specifications.
Lifting the Generator
When lift or hoist equipment is used to lift the generator and move it to position, be careful not to
contact overhead wires or other obstacles. The generator weighs between 170 and 200 lbs.
Use proper lift equipment and methods to avoid injury. Lift only by the tubular metal frame.
Figure 3-1 PG6000 Generator
Storage
If you will not be using the generator set for a significant amount of time (3 months or longer) you
should store the generator to prevent any problems that could arise from sitting idle. Please fully
read the following guidelines prior to storing the unit.
1. Remove all fuel from the engine’s fuel tank.
2. Start the generator set and allow it to run out of fuel.
3. Close all the fuel valves.
Note: An alternative to draining the fuel from a gasoline engine is adding a fuel stabilizer, to
minimize the formation of fuel gum deposits during storage (Follow the manufacturer’s
directions). After the fuel stabilizer is added, run the generator set for 5 minutes to get the
stabilizer into the carburetor. After shutting the engine off, be sure to close all the fuel
valves.
4. Drain the used oil from the engine’s crankcase and refill it with clean oil.
5. Remove the spark plugs and pour1 oz. of clean engine oil into each cylinder. Put a rag
over each spark plug port and pull the starting cord approximately 5 times to distribute
the oil in the cylinder.
6. Replace the spark plug(s) but do not connect the plug wires. This will help prevent
accidental or unauthorized starting.
7. Provide maintenance to the engine and generator set as described in the engine and
generator maintenance sections of this manual.
8. Cover any bare metal spots with paint or another type of rust preventative.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion.
MN2418
Receiving & Installation 3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Physical Location
The mounting location of the system is important. It should be installed in an area that is
protected from direct harmful gases or liquids, dust, metallic particles, shock and vibration. It can
only be installed in an outdoor location so the exhaust fumes are vented to the atmosphere. This
system must never be installed inside an enclosed building, home, shop or garage etc.
Several other factors should be carefully evaluated when selecting a location for installation:
1. For effective cooling and maintenance, the generator should be mounted on a flat, smooth,
non-flammable level surface. A concrete pad is ideal and provides a secure installation.
2. The location for the generator must be dry. Never operate a generator in an area that
has standing water or puddles.
3. Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. It
is important that the unit be operated in a reasonably clean environment.
4
All engines give off considerable heat when running. The engine in your generator set
uses air to keep it cool so it is important that the ambient temperature is cool and does
not exceed 100°F (even while it is running). Where natural ventilation is inadequate a
fan to boost circulation should be used.
5. Exhaust gases from internal combustion engines are extremely poisonous. Never
operate an engine indoors.
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never
breath exhaust fumes produced by a running engine. Only run the engine outdoors where
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or
incoherence. If you or anyone else experiences these symptoms, get out into fresh air
immediately. Stop the engine and do not restart the engine until it has been inspected and if
necessary repaired or reinstalled in a well ventilated area.
6. All electrical equipment should be protected from excessive moisture. Failure to do so
will result in deterioration of the insulation and may result in short circuits and a
possible electrocution hazard.
Installation
The generator is completely assembled, tested and adjusted at the factory before it is shipped to
you. External connections required at the time of installation are:
1. Electrical Connections.
2. Ground Connection.
Note: The generator is shipped dry. This means no oil is in the engine crankcase and no battery
is installed. You must refer to the engine manual and obtain the correct type and quantity
of engine motor oil and the correct battery (if equipped for electric start).
After installation, the post installation checks must be performed prior to starting the engine.
After these checks have been performed and the system operation is verified to be good, refer to
Section 5 Troubleshooting and Maintenance for periodic checks that must be performed at
scheduled intervals to ensure continued operation with minimal problems.
3-2 Receiving & Installation
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Connections All load connections are made at the panel using electrical cords with the proper
mating plug for the receptacle being used. More than one receptacle can be used as long as the
total load does not exceed the continuous rating of the generator.
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
Use correct size insulated wire to connect the generator to the load. The gauge of the wire will
depend on the distance to the load, the permissible voltage drop at the load, and the current
required by the load. If you are not sure of the gauge wire needed for your application, consult a
competent electrician. Using wire that is too small can result in fire hazard. Also, be sure the
wire has the appropriate ratings for insulation and environment conditions.
The correct mating connector must be used to fit the connectors provided on the operator panel
Table 3-1 Single Phase Power Receptacle Description
Electrical Connection Information (Receptacle Provided at Panel)
Model
Straight 120VAC
(20Amp)
Twist Lock 120/240VAC
(30Amp)
Rated Watts/
(Full load Amps 120/240)
PG6000
2− 520R 120VAC
1− L1430R 120/240VAC
5700 / (44.2/22.1)
Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.
Figure 3-2 Receptacle Connections
(GOLD)
X
Ground
120VAC
G
NEMA
L14−30R
125/250V
30A
Y
(GOLD)
W
(SILVER)
NEMA 520R
125V 20A
120VAC
Neutral
MN2418
Receiving & Installation 3-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power
before you ensure that grounds are connected. Electrical shock can cause serious or fatal
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be
connected to an approved earth ground. Local codes may also require proper grounding of
generator systems.
The NEC requires that the frame and exposed metal surfaces be at local ground reference
potential to avoid electrical shock hazard. A local ground reference may require a driven earth
ground conductor at the generator installation site. Make the ground connection as shown in
earth at least 8 feet or as necessary to reach the water table.
Figure 3-3 Frame Ground Connection
Nut
Washer
Ground Wire Lug
Washer
Stud
Frame
Engine Oil
Refer to the engine manual that was provided with your generator. Determine the correct type of
engine oil and the amount specified by the engine manufacturer. Add the required amount of oil
to bring the oil level to full.
SUMMER
OIL
WINTER
OIL
OIL
CAPACITY
2.0 PTS
MODEL
PG6000
SAE. 30
5W/30
Use of Electric Motor Loads
Electric motors require much more current (amperes) to start them than to keep them running.
Some motors, particularly split−phase motors are very difficult to start and require 5 to 7 times
more current to start them. Repulsion−induction type motors are the easiest to start and normally
only require 2 to 3 times as much current to start them.
Most fractional horsepower motors take about the same amount of current to start them and
keep them running. This is true whether they are the repulsion−induction type motor, capacitor
type motor, or the split−phase type motor.
Other factors that influence the amount of current needed to start a motor are:
1. The type of load connected to the motor. If the electric motor is connected to a hard
starting load such as an air compressor it will require more starting current. If the same
electric motor is connected to a light load such as a heater or power saw it will require
less starting current.
2. The brand or design of the electric motor. The expected starting current for a
particular size motor will vary depending on the brand of the electric motor as well as
the type of electric motor (Split Phase, capacitor, Repulsion−induction type, etc.)
3. The condition of the electric motor. A clean motor with free turning bearings will
require less starting currents than a similar type motor that is dirty and the bearings are
not as free turning as they used to be.
Optional Wheel Kit PDG2 − 2 Wheel Dolly Kit; and PDG4 − 4 Wheel Dolly Kit
An optional 2 or 4 wheel dolly kit is available for portable generators. If you have purchased one
of these kits, refer to MN2409 for the installation instructions.
3-4 Receiving & Installation
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4
Operation
Operator Control Panel
Figure 4-1 Operator Panels
AC Circuit Breakers
120VAC 120VAC
20A 20A
240VAC
22A
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
AC Circuit Breakers Provide overcurrent protection for the generator output. When tripped, the plunger (in
center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger into
the breaker to reset the breaker. Correct any overloads then restore the loads.
Receptacles − Receptacles are provided to allow easy connection of electrical loads. Never connect this
generator to any buildings electrical system unless a licensed electrician has installed an
approved transfer switch. Multiple receptacles may be used at the same time provided the total
electrical load does not exceed the generators rated output.
120Volts − PG6000 has 2 outlets each rated 125VAC at 20 Amperes.
(NEMA 520R Duplex receptacle125VAC at 20 Amperes).
240 Volts − Twist lock NEMA L1430R receptacle rated 250Volts at 30 Amperes.
Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.
Pre−Start Checks Before the engine is started, several things must first be checked.
1. Place the generator set in an open, dry, well ventilated and reasonably level location.
2. If grounding is required for your application, check to make sure your unit is grounded
properly (see Section3).
3. Check the engine’s oil level and add oil if necessary to bring it to the level
recommended by the engine manufacturer.
4. Check the fuel level and add fuel to within 1/2 inch of the fill tube if necessary.
5. Open the fuel valve on the fuel tank (and on the engine if installed).
6. Check the fuel system for fuel leaks and repair them prior to starting the engine. Wipe
up any fuel spills before starting the engine.
7. Disconnect or “turn off” all external loads.
8. Make sure all circuit breakers are set (pushed in).
9. Tighten any bolts or nuts that may have loosened due to vibration.
10. Be sure all extension cords are in good condition before starting the generator.
Use only U.L. listed extension cords and connectors.
MN2418
Operation 4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Start−Up Procedure
Recoil Start
1. Move the engine’s choke lever to the “Choke/Start” position. If the engine is warm or if
the ambient air temperature is high; try starting the engine without choking it.
2. Move the Control Panel Engine “ON/OFF” switch to “ON” (if equipped).
3. Pull lightly on the recoil grip until you feel significant resistance, then pull sharply. Allow
the recoil to gently rewind into the recoil housing. See your engine manual for
instructions specific to your unit. Do not allow the recoil rope to “snap back” into the
recoil housing.
Note: If the engine does not start after several attempts, smell for fuel near the air cleaner. If
there is a significant gasoline smell coming from the air cleaner, turn the choke lever off
and attempt to start the engine with the choke off.
4. When the engine starts, turn the engine’s choke lever to the “OFF” position.
5. Power is now present at the receptacles.
Connect or “turn on” the loads you wish to operate.
Stopping Procedure
1. Disconnect or “Turn Off” all loads connected to the generator set.
2. Move the Control Panel Engine “ON/OFF” switch to “OFF” (if equipped).
3. Push the engine stop switch if so equipped.
OR
Turn the engine key switch to the “OFF” position.
4. Turn all fuel valves off.
4-2 Operation
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5
Troubleshooting and Maintenance
Maintenance
This manual contains only very minimal engine maintenance instructions. Refer to the engine
manufacturer’s owner’s manual for specific engine maintenance instructions for your generator
set. Any maintenance instructions or recommendations in the engine owner’s manual take
precedence over any of the following general recommendations.
General:
1. Inspect the fuel system for leaks. Replace all defective components immediately.
2. Inspect and replace any fuel line that shows signs of deterioration.
3. Inspect all fuel clamps to ensure they are tight.
4. Make sure the fuel cap fits snugly on the fuel tank and that the fuel tank does not leak.
5. Inspect the external wire cables and connectors used with the generator set for cuts,
frayed insulation, or loose connections. Repair or replace damaged parts before use.
6. The engine should be checked for proper speed setting(s).
Prior to adjusting the engine speed, turn the auto idler switch to “OFF” (if present).
Make sure that the auto idler magnet does not touch the throttle lever of the engine
when running.
a. Disconnect all electrical loads and start the engine.
b. Adjust the engine speed to 3720 RPM (62 Hz) with no load speed.
Engine:
1. Clean and/or replace any fuel, oil, and/or air filters per the engine manufacturers’
guidelines.
2. Check oil level regularly; at least every 5 to 8 operating hours. Maintain the proper oil
level.
3. Change the oil as is recommended in the engine manufacturer’s owner’s manual.
4. Replace the spark plug(s) as is recommended by the engine manufacturer.
5. Clean the cooling fins on the engine to keep the engine’s heat dissipation potential at
it’s maximum.
6. Inspect and clean all governor and carburetor linkages so they operate properly.
7. Inspect the recoil starting rope for any damage and replace it if necessary (if
applicable).
8. Clean the trash screen around the recoil starter or other cooling air intake.
Alternator: ( also called Generator End)
This generator set must be run at its proper speed to obtain the correct electrical power at its
output. All engines have a tendency to slow down when a load is applied to it. The engine
governor is designed to hold the operating speed as nearly constant as possible. When the
electrical load is increased, the engine is more heavily loaded and engine speed drops slightly.
This slight decrease in engine speed results in a slight decrease in generator voltage and
frequency output. This voltage and frequency variation has no appreciable effect in the operation
of motors, lights, and most appliances and tools. However, timing devices and clocks will not
keep perfect time when used on this generator.
1. Clean the generator set and remove any and all dust, dirt, or other foreign material.
2. Inspect and clean the cooling air intake and exhaust louvers of the generator end.
Make sure they are clean. Remove dirt or any buildup that may restrict the cooling air
flow.
3. Clean the generator set and its components with a damp cloth or sponge.
Never use a water hose or pressure washer as this may damage electrical
components.
4. Inspect and replace any control panel components that are broken or not working
properly (receptacles, circuit breakers, switches, etc.)
MN2418
Troubleshooting and Maintenance 5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Problems and Solutions
for all types of problems. Procedures that require in depth knowledge or skills (like flashing the
field) should be referred to generator service facility.
Table 5-1 Troubleshooting Guide
Problem
Possible Cause
Remedy
Engine will not start
No fuel.
Restricted air flow.
No spark.
Check that fuel valves are ON. Check fuel level in fuel tank.
Check/replace air filter.
Check/replace spark plug(s). Check that engine switch is in Start
position.
Engine starts but will not run smoothly
Engine overheats
Fuel or ignition problem
Refer to engine manual.
Excessive load
Debris or dirt buildup on engine
Remove one or more electrical loads.
Remove debris. Clean engine surfaces to allow cooling.
No output voltage
Ciruit Breaker tripped or defective.
Loss of residual magnetism in exciter
field poles.
Reset circuit breaker or replace if required.
Flash field.
Open in stator windings
Defective exciter circuit.
Check for continuity in windings. Return to factory for repair if open.
Check/replace diode and capacitor and flash the field.
Output voltage varies
Irregular speed (fixed speed mode)
Fluctuating speed (fixed speed mode)
Check engine for malfunction or load for fluctuation
Stabilize load. The addition of a lamp load (resistance load) may
compensate partially for load changes caused by intermittent motor
operation. Do not overload.
Loose terminal or load connections
Defective bearing (uneven air gap)
Verify all connections are proper and check tighness torque of
terminals.
Replace worn bearing
Low output voltage
Low engine speed
Excessive load
Check that the Auto Idle switch is in OFF position (if installed).
Check engine for malfunction or system for overload. Reduce load.
Verify all connections are proper and check tighness torque of
terminals.
Test field coils for possible short by checking resistance with an
ohmmeter or resistancebridge. Return rotor assembly to service
center for repair if alternator field coils are shorted.
High resistance connections −
connections will be warm or hot
Shorted field
Reduce inductive (motor) load. Some AC motors use about the
same current regardless of load. Do not use motors of greater
horsepower rating than is necessary to move the mechanical load.
Low power factor
High output voltage
Excessive speed (fixed speed mode)
Check engine for malfunction
Electrical shock when frame is touched
Static charge.
Grounded armature or field coil.
Ground generator frame at local reference ground (see Section 3).
Return to service center for repair
Mechanical noise
Defective bearing
Rotor rubbing on stator
Replace bearing
Bad bearing − replace.
Bent shaft − return to service center.
Loose end bell − tighten;
Loose drive Discs − tighten
Loose or misaligned coupling
Tighten; align coupling and alternator shaft to engine shaft.
Service
Parts
Service for your generator can be obtained from a generator service center. Please have the
following information available:
The model number and serial number of the generator set.
A complete and accurate description of the problem.
Parts for your generator can be obtained from a generator service center. Please have the
following information available:
The model number and serial number of the generator set.
A complete and accurate description of the part (part number if known).
Note: Engine parts can usually be obtained by using the information in the engine
manufacturer’s owner’s manual.
5-2 Troubleshooting and Maintenance
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A
PG6000 Connections
Caution: The brass connecting tab on some 120VAC duplex receptacles has been removed. Each
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect
the brass tab that normally links both receptacles. If it is removed, be sure to remove the
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will
cause a direct short to the generator windings and cause possible generator damage.
Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.
MN2418
PowerchiefR Series A-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure A-2 PG6000 Wiring Diagram
A-2 PowerchiefR Series
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B
Special Information for California
Information in this Appendix applies only to products operated in the state of California.
LIMITED WARRANTY ON EVAPORATIVE EMISSION CONTROL SYSTEMS − CALIFORNIA ONLY
The California Air Resources Board (CARB) and Baldor Generators (herein ”Baldor”) are pleased to explain the Evaporative Emission
Control System (EECS) warranty on your model year 2006 and later generator. In California, new generators must be designed, built
and equipped to meet the State’s stringent anti−smog standards. Baldor must warrant the EECS on your generator for the period of
time listed below provided there has been no abuse, neglect or improper maintenance of your generator. Your EECS may include parts
such as the carburetor, fuel−injection system, ignition system, catalytic converter, fuel tanks, fuel lines, fuel caps, valves, canisters,
filters, vapor hoses, camps, connectors, and other associated emission−related components. Where a warrantable condition exists,
Baldor will repair your generator at no cost to you including diagnosis, parts and labor for the time period set forth below.
BALDOR EVAPORATIVE EMISSION CONTROL SYSTEM DEFECTS WARRANTY COVERAGE
This evaporative emission control system is warranted for a period of two (2) years, subject to the provisions set forth below. If any
covered evaporative emission−related part on your equipment is defective, the part will be repaired or replaced by Baldor.
OWNER’S WARRANTY RESPONSIBILITIES
As the generator owner, you are responsible for performance of all the required maintenance listed in your owner’s manual. Baldor
recommends that you retain all receipts covering maintenance on your generator, but Baldor cannot deny EECS warranty claims solely
for the lack of receipts. As the generator owner, you should however be aware that Baldor may deny you warranty coverage if your
generator or a part has failed due to abuse, neglect, or improper maintenance or unapproved modifications. You are responsible for
presenting your generator to an authorized Baldor service center as soon as the problem exists. The warranty repairs should be
completed in a reasonable amount of time, not to exceed 30 days from the date of delivery to the authorized Baldor service center.
If you have a question regarding your warranty coverage, you should contact Baldor − Generator Technical Support at
1−479−646−4711.
CONDITIONS AND RESTRICTIONS EVAPORATIVE EMISSIONS CONTROL SYSTEM WARRANTY COVERAGE
Baldor warrants to the ultimate purchaser and each subsequent purchaser that the generator is: (1) designed, built and equipped so
as to conform with all applicable CARB EECS regulations; (2) free from defects in materials and workmanship that cause the failure
of a warranted part to be identical in all material respects to that part as described in Baldor’s application of certification to CARB; (3)
the warranty period begins on the date the generator is delivered to an ultimate purchaser or first placed into service. The warranty
period is two years.
Subject to certain conditions and exclusions as stated below, the warranty on EVAP emission−related parts is as follows: Any warranted
part that is not scheduled for replacement as required maintenance in the written instructions supplied, is warranted for the warranty
period. If the part fails during the period of warranty coverage, the part will be repaired or replaced by Baldor at an authorized Baldor
service center at no charge to the owner. Any such part repaired or replaced under warranty will be warranted for the remainder of the
EECS warranty period. Any warranted part that is scheduled only for regular inspection in the written instructions supplied is warranted
for the EECS warranty period. Any such part repaired or replaced under warranty will be warranted for the remaining EECS warranty
period. Any warranted part that is scheduled for replacement as required maintenance in the written instructions supplied is warranted
for the period of time before the first scheduled replacement date for that part. If the part fails before the first schedule replacement,
the part will be repaired or replaced by Baldor. Any such part repaired or replaced under warranty will be warranted for the remainder
of the period prior to the first scheduled replacement point for the part. Notwithstanding the provisions herein, EECS warranty services
or repairs will be provided at designated service facilities to service the subject equipment. The generator owner will not be charged
for diagnostic labor that leads to the determination that an EECS warranted part is defective, if the work is performed at an authorized
Baldor service center. Baldor is liable for damages to other Baldor generator equipment components proximately caused by a failure
under warranty of any EECS warranted part. Throughout the EECS warranty period, Baldor will maintain a supply of EECS warranted
parts sufficient to meet the expected demands for such parts. Any replacement part may be used in the performance of any EECS
warranty maintenance or repairs and must be provided without charge to the owner. Such use will not reduce the warranty obligations
of Baldor. Add−on or modified parts that are not exempted by the California Air Resources Board may not be used. The use of any
non−exempted add−on or modified parts by the ultimate purchaser will be grounds for disallowing warranty claims. Baldor will not be
liable to warrant failures of warranted parts caused by the use of a non−exempted add−on or modified part. This limited warranty does
not cover any part which malfunctions, fails or is damaged due to failure to follow the maintenance and operating instructions provided
with the generator.
EVAPORATIVE EMISSIONS CONTROL SYSTEM WARRANTED PARTS: The repair or replacement of any warranted part otherwise
eligible for warranty coverage may be excluded from such warranty coverage if Baldor demonstrates that the generator has been
abused, neglected, or improperly maintained, and that such abuse, neglect, or improper maintenance was the direct cause of the need
for repair or replacement of the part. That notwithstanding, any adjustment of a component that has a factory installed, and properly
operating, adjustment−limiting device is still eligible for warranty coverage. Parts covered under the California Evaporative Emissions
Warranty are (1) low permeation fuel lines and fittings.
MN2418
Special Information for California B-1
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Engine exhaust from this product contains chemicals known
to the state of California to cause cancer, birth defects and
other reproductive harm.
WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Battery posts, terminals and related accessories are known to
the state of California to cause cancer, birth defects and other
reproductive harm.
B-2 Special Information for California
MN2418
Download from Www.Somanuals.com. All Manuals Search And Download.
Baldor District Offices
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Engine exhaust from this product contains chemicals known
to the state of California to cause cancer, birth defects and
other reproductive harm.
WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Battery posts, terminals and related accessories are known to
the state of California to cause cancer, birth defects and other
reproductive harm.
BALDOR ELECTRIC COMPANY
P.O. Box 2400
Ft. Smith, AR 72901--2400
(479) 646--4711
Fax (479) 648--5792
© Baldor Electric Company
MN2418
Printed in USA
8/06
Download from Www.Somanuals.com. All Manuals Search And Download.
|