Henny Penny 6 User Manual

Installation  
Refer to the following pages for important information regarding the  
installation of LCS and LCG ClimaPlus Combis. It is recommended  
that installation be accomplished by a certified and properly trained  
technician.  
NOTE: When installing a ClimaPlus combi, humidity calibration must  
be performed. This process takes approximately 45-60 minutes. (page 62)  
Site, leveling  
Minimum clearance sides and back:  
2 in. (50 mm)  
Service clearance, left side:  
20 in. (500 mm)  
Clearance for door opening:  
Model 6 & 10: 2012 in. (521 mm)  
Model 1020:  
Model 20:  
Model 40:  
2912 in. (749 mm)  
2834 in. (730 mm)  
3034 in. (781 mm)  
1) Check for any transport damages. Should there be any signs of transport  
damage immediately inform your dealer/freight forwarder.  
2) Check installation site. Check entrance clearance.  
Fig. 1  
Minimum entrance space needed without pallet:  
Model 6 & 10:  
Model 1020:  
Model 20:  
351  
495⁄  
397⁄  
521⁄  
2
in. (902 mm)  
in. (1262 mm)  
in. (1012 mm)  
in. (1332 mm)  
8
8
Model 40:  
2
I Floor at installation site must be level.  
I Cold water line in place. (page 63)  
I 2 in. (50 mm) drain connection installed.  
I Max. drain height for floor units: 4 in. (100mm)  
Fig. 2  
I Electrical power supply/protective measures installed and sized correctly.  
(page 60-61)  
3) Remove all cartons, packing materials, documents etc. from the interior cabinet.  
4) Remove grid shelves/trolley from cabinet.  
5) Take unit off the pallet.  
I Moving unit without pallet: Sizes 6, 10, 1020 (Fig. 1)  
59  
I Moving unit without pallet: Sizes 20, 40 (Fig. 2)  
INSTALLATION  
Electrical requirements of gas units:  
Model  
Voltage Phase Cycle/Hz  
KW  
1
LCG-6  
LCG-10  
120  
120  
1
1
1
1
3
60  
60  
60  
60  
60  
1
LCG-1020 208/240  
1.5  
1.6  
3.5  
Fig. 8  
LCG-20  
LCG-40  
208/240  
208/240  
N
L
3
L
2
L
1
Choose conductor size according above tables and your local regulations.  
IMPORTANT  
Gas units are voltage specific. Supply voltage must match voltage rated on data plate.  
I Gas units are supplied with grounded power cord and plug.  
Fig. 9  
I Electric units are NOT supplied with power cord.  
To connect power supply for electric units, models 6, 10:  
Cable  
Inlet  
I Open the operator panel. (Fig. 8)  
I Insert power cord through cable inlet under left side of unit to desired  
length and secure the cable connection tight. (Fig. 9)  
I The circuit diagram is located behind the control panel.  
To connect power supply for electric units, models 1020, 20, 40:  
Fig. 10  
I Access power connection terminals by removing left side panel.  
240 volt tap  
I Insert power supply cable through cable inlet under left side of unit to desired  
length and secure the cable connection tight. (Fig. 9)  
I Connect supply wires as follows:  
Gray terminals:  
L1, L2, L3, phase sequence  
does not need to be observed  
Blue terminal:  
Neutral (if applicable)  
Common tap  
208 volt tap  
Fig. 11  
Yellow/Green terminal: Ground  
IMPORTANT  
In some areas Henny Penny Electric Combis are shipped set up for 240 volts, but  
can be converted to 208 volt operation. If conversion is necessary the unit must be  
reset and calibrated.  
Jumper  
wire  
Convert from 240 volt to 208 volt operation  
I Disconnect unit from power supply source.  
Terminal  
location  
I Open service door (Fig. 8) by loosening fastener at top of the unit over the  
control panel using a 5 mm Allen wrench. A rubber grommet must first be  
removed to access the bolt.  
I Move transformer primary lead from the 240v tap to the 208v tap (Fig. 10).  
I Open left side panel and locate relay K3.1 (Fig. 11).  
I Remove the jumper wire from the appropriate terminal positions. The  
terminals on K3.1 relay socket are numbered. Use the chart below to  
determine from which terminals to disconnect jumpers.  
K3.1 relay  
61  
Model  
Terminal Positions  
5 and 6  
LCG-6  
LCG-10  
LCG-1020  
LCG-20  
LCG-40  
5 and 6  
5 and 6  
6 and 7  
5 and 6  
I Once conversion has been completed, a total resetof the CPU-PCB must be  
done.  
Record all end-user (custom) programs before undertaking a Total Reset.  
I Secure all panels and covers.  
Total reset  
I Turn on unit.  
I Press and hold IQT Sensor key, IQT key, and PROG/START  
simultaneously and turn unit off.  
I Release all keys. Wait at least 4 seconds and turn unit on.  
NOTE: With total reset procedure all custom programs are deleted. After a total  
reset, 12:00 or 13:00 will be indicated on the timer display. Real time must be  
reset. To set clock to actual time, see page 50.  
Humidity calibration  
I The interior cabinet must be clean. If it is not, wipe clean.  
I The interior cabinet temperature must be below 122°F (50°C) and the  
cabinet must be dry.  
I Turn on unit.  
I Open cabinet door.  
I Select any cooking mode.  
I Access diagnostic program by pressing TEMPERATURE key, IQT  
Sensor key, and IQT key simultaneously until the word VERSION”  
appears next to the IQT key.  
I Use Central Dial to select CALIBRATE.  
I Close cabinet door.  
I To start calibration press PROG/START and TEMPERATURE key  
simultaneously.  
I Calibration starts automatically and lasts 45-60 minutes.  
I After calibration, unit must be switched off for 5 seconds before using again.  
I During calibration, several values will be shown on the display.  
I Once calibration begins, do not interrupt the process.  
I Do not open door until calibration is complete.  
After calibration, very hot steamaround 392°F (200°C)remains in the cabinet.  
When opening the cabinet door hot steam will escape, and burns could result.  
62  
INSTALLATION  
Water supply  
9) Drain Connection (WA)  
Fig. 12  
I For drain connection (Fig. 12) use only steam temperature resistant pipe,  
diameter 2 in. (50 mm) and constant slope 5%. No hose should be used.  
I Direct drain connection is possible, ventilated gap is an integrated part of the  
WA  
appliance (Fig. 13).  
I Drain pipe should be supported to the wall/floor.  
I Max. water discharge rate during Auto Flush:11 gal./min. (0.7 liter/sec.)  
I Average drain water temperature: 150°F (65°C).  
Fig. 13  
10) Water Connection (WZ)  
I Observe all local plumbing codes.  
I Flush water line before connecting the water supply to the unit.  
I Connect to cold, potable water only.  
WA  
I Operational water pressure: MIN: 30 psi (200kPa) MAX: 88 psi (600kPa).  
RECOMMENDED: 44 psi (300kPa). Water flow must be at least 3 gal/min  
(12 l/min).  
I Water connection supplied by customer: 1⁄  
fitting.  
2
in. pressure hose with R 3⁄  
in. tapered  
4
Fig. 14  
I Customer fitted shut-off valve for each appliance.  
WZ  
I Water conductivity: 50-2000 µS, lower conductivity on request.  
C
B
A
I Maximum chloride concentration (Cl-): below 150 ppm (150 mgr/liter)  
at any time.  
I For conductivity above 2000 µS or higher chloride concentration use  
hydrogen-ion exchanger (A in Fig. 15) in the supply water line.  
Fig. 15  
I Water Redox-Potential must be below 300mV at any time.  
WZ2  
I For higher Redox Potential use Active Carbon Filter (B in Fig. 14). Observe  
WZ1  
maintenance period of active carbon filter.  
I Use a 3 micron (0.08mm) particle filter (C in Fig. 14) to prevent excessive  
soiling of the supply water.  
I Recommended test instruments: Cl2 Tester (swimming pool accessories),  
conductivity tester, redox meter.  
Optional Treated Water Connection  
I To connect a dual water supplytreated soft water or warm water below  
I 140°F (60°C)disconnect T-water connection at the two water inlets (Fig. 15).  
Connect treated water to water inlet marked WZ2 and standard water to inlet  
marked WZ1. Treated water must comply with the above-mentioned water  
specifications.  
NOTE: If using external filter to treat hard water: Contact your Henny Penny  
distributor for average water consumption when using CleanJet. Increases in  
average water consumption may exceed specifications of external filters and may  
affect the frequency of filter maintenance. (See page 57)  
63  
INSTALLATION  
General  
11) Technical Data  
Working place specific noise level: <70dB  
Average water consumption during operation:  
Model 6:  
3.17 gal/hr (0.2 l/min.)  
6.7 gal/hr (0.42 l/min.)  
10.9 gal/hr (.069 l/min.)  
13.2 gal/hr (0.83 l/min.)  
15.8 gal/hr (1.0 l/min.)  
Model 10:  
Model 1020:  
Model 20:  
Model 40:  
Heat emission:  
Model  
Latent  
.64 W (2.30 kJ)/hr  
Sensible  
LCS/G-6  
LCS-G-10  
84 W (2.93 kJ)/hr  
1.05 W (8.50 kJ)/hr 1.4 W (5.00 kJ)/hr  
LCS/G-1020 1.67 W (6.00 kJ)/hr 2.4 W (8.50 kJ)/hr  
LCS-G-20  
LCS/G-40  
2.13 W (7.67 kJ)/hr 2.67 W (9.60 kJ)/hr  
3.7 W (13.35 kJ)/hr 4.26 W (15.34 kJ)/hr  
Ventilation  
Contact your local regulatory agency for ventilation requirements. If a ventilation  
hood is installed, observe the following:  
I The standards of the local authority.  
I The hood should protrude 12-20 in. (300-500 mm) over the front of the  
appliance.  
I The integrated grease filter should be in the protruding part of the hood.  
Specifications and technical descriptions in this applications manual are subject to  
change without prior notice.  
Gas supply  
12) Gas supply (for LCG units only)  
The ClimaPlus gas model is available for either natural or propane gas. Check  
the data plate on the left corner of the unit to determine the proper gas supply  
requirement.  
Model  
Gas Line  
Connection  
3
1
LCG-6  
4
in.  
in.  
2
in.  
in.  
in.  
in.  
3
3
LCG-10  
LCG-1020  
LCG-20  
LCG-40  
4
4
3
1 in.  
4
3
1 in.  
114 in.  
4
1 in.  
64  
INSTALLATION  
continued  
DO NOT attempt to use any type of gas other than that specified on the data  
plate. Incorrect gas supply could result in fire or explosion resulting in severe  
injuries and/or property damage.  
To avoid possible serious personal injury, the installation must conform with local  
codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI  
Z223.1-1988 or latest edition. In Canada, CAN/CGA-B 149.1 Natural Gas  
Installation Code CAN/CGA-B 149.2 Propane Installation Code.  
I All Henny Penny Combi-Steamers are equipped with two heat exchanger  
systems. One is responsible for steam production, the second for dry heat. Each  
individual heat exchanger is heated with a separate burner assembly.  
I Separate gas valves for the steam burner and dry heat burner are responsible for  
the gas supply to the individual burners. All LCG models have manual shut-off  
valves that can be accessed from the left without tools. To operate the valves,  
unscrew the two knurled screws and remove the service cover. Open or close  
manual valves as desired.  
Gas Leak Test  
I After piping and fittings have been installed, check for gas leaks. A simple  
checking method is to turn on the gas and brush all connections with a soap  
solution. The appearance of bubbles indicates escaping gas. In this event, the  
piping connection must be redone until no bubbles occur.  
Never use a lighted match or open flame to test for gas leaks. Escaping gas could  
result in fire or explosion resulting in severe injuries and/or property damage.  
Gas pressure  
I The gas pressure should be measured when all other gas appliances in the  
kitchen are on high flame. The minimum and maximum incoming line flow  
pressures should be as follows:  
Natural: 7-10 in. water column (18-25 mb)  
Propane: 12-14 in. water column (30-35 mb)  
65  
INSTALLATION  
During pressure testing note the following:  
continued  
1. The unit and its individual shut-off valves must be disconnected from the gas  
supply piping system during any pressure testing of that system when test  
pressures exceed 1⁄  
gas supply line.  
2
psig (3.45kPa). Turn OFF main gas shut-off valve or main  
2. The unit must be isolated from the gas supply piping system by closing its  
individual manual shut-off valves during any pressure testing of the gas supply  
piping system at test pressure equal to or less than 1⁄  
psig (3.45kPa).  
2
3. If incoming pressure is over 14 in. water column (35 mb) a separate regulator  
must be installed ahead of the manual gas shut-off valve.  
To prevent damage to the control valve regulator, the first time the gas valve knob is  
turned to the ON position, it is very important to turn the knob very slowly.  
NOTE  
After turning on the gas, the manual shut-off valve must remain open, except  
during pressure testing as outlined above, or when necessary during service  
maintenance.  
I Incoming pressure reading can be taken by installing a gas pressure gauge on  
the front of the units main gas valves test port. This should be done with all  
gas appliances in operation on the same gas supply line. Should the manifold  
pressure drop below the desired level, consult your local gas utility service.  
Gas Hook-up  
RIGHT  
WRONG  
A minimum pull of appliance  
away from wall is acceptable in  
order to disconnect hook-up.  
Maximum pull prior to disconnect  
will result in kinked ends and reduce  
hose and connector life.  
66  
INSTALLATION  
Utilize elbows when necessary to avoid sharp kinks or excessive bending. For ease of  
movement, install with a lazyloop. Gas appliance must be disconnected prior to  
maximum movement. (Minimum movement is permissible to disconnect gas line.  
continued  
Couplings and hose should be installed in the  
same plane as shown at left. DO NOT OFFSET  
COUPLINGS. This results in twisting and undue  
torsion causing premature failure.  
Correct way to install metal hose for vertical traverse.  
Note single, natural loop. Allowing a sharp bend,  
shown at right, strains and twists the metal hose to  
a point of early failure at the coupling.  
Maintain the minimum or larger bending diameter  
between couplings for the longest life. Couplings too  
close together, as shown at right, create double bends  
causing work fatigue failure of fittings.  
In all installations where self-draining is not necessary,  
connect metal hose in a vertical loop. DO NOT  
CONNECT METAL HOSE HORIZONTALLY  
unless self-draining is necessary. Then use support on  
lower plane as show at left.  
Cable Restraint  
Please refer to the illustration at left when installing cable restraint on all moveable  
gas appliances  
Eye-bolt is to be secured to the building using acceptable building practices.  
Dry wall construction  
Secure eye-bolt to a framing stud. DO NOT attach to dry wall only. Locate eye-bolt  
at the same height as the gas service approximately 6 in. (150 mm) to either side of  
service. Cable restraint must be at least 6 in. (150 mm) shorter than flexible gas line.  
67  

GE 26939 User Manual
Fisher VMC 8614F User Manual
Epson S1C88650 User Manual
Electrolux EW36IC60I S User Manual
Electrolux ELCO 900 User Manual
Electrolux 922046 User Manual
Dell POWERVAULT MD3600F User Manual
Asus Computer Monitor VH192 User Manual
Acer TravelMate 4060 User Manual
25942GE1 User Manual