| GS110IOM-2   GS110W   NATURAL OR PROPANE GAS BOILERS   INSTALLATION & OPERATION MANUAL   MEA#117-96-E   DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE   VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE   OF 50 PSI WATER.   TO INSTALLER   NOTE: READ THESE INSTRUCTIONS CAREFULLY. THEY   WILL SAVE YOU TIME IN ASSEMBLING BOILER PROPERLY.   WARNING: If the information in this manual is not followed exactly, a fire   or explosion may result causing property damage, personal injury or loss of life.   Do not store or use gasoline or other flammable vapors and liquids in the vicinity of   this or any other appliance.   WHAT TO DO IF YOU SMELL GAS:   • Do not try to light any appliance.   • Do not touch any electrical switch. Do not use any phone in your building.   • Immediately call your gas supplier from a neighbor’s phone. Follow the gas   supplier’s instructions.   • If you cannot reach your gas supplier, call the fire department.   INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.   CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.   NOTE: Installation and service must be performed by a qualified installer, service   agency or the gas supplier.   260 NORTH ELM STREET WESTFIELD, MA 01085   TEL. (413) 562-9631 FAX: (413) 562-3799   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 3   The installation must conform to the requirements of the   2. An optimum site will be level, central to the hot water   authority having jurisdiction or, in the absence of such   requirements, to the National Fuel Gas Code, ANSI   Z223.1-latest revision. In Canada, the installation must   be in accordance with the requirements of CSA B149.1   or B149.2 Installation Code for Gas Burning Appliances   and Equipment.   piping system, close to an outside wall and have   adequate fresh air for combustion.   3. Ensure that the floor is structurally sound and will   support the weight of the boiler.   NOTE: This boiler is designed for direct placement   on a combustible floor. Never install this boiler on   carpeting!   BOILER RATINGS & CAPACITIES   Before undertaking the installation of the GS110 check   the boiler rating plate to ensure that the boiler is the   proper size for the job. The "Net I=B=R Ratings" specify   the equivalent amount of direct cast iron radiation that   the boiler can handle under normal conditions.   4. DO NOT install this boiler in a location that would   subject any of the gas ignition components to direct   contact with water or excessive moisture during   operation or servicing.   Also ensure that the boiler has been set up for the type   of gas available at the installation site. Other important   considerations are the availability of an adequate   electrical supply, fresh air for combustion and proximity   a suitable outside wall.   5. NEVER store objects on or around the boiler.   WARNING: Never store combustible materials,   gasoline or any product containing flammable   vapors or liquids in the vicinity of the boiler.   Failure to comply with this warning can result   in extensive property damage, severe personal   injury or death!   BOILER LOCATION   WARNING: The clearances to combustible   construction show in Figure 1 must be main-   tained. Failure to comply with this warning can   result in extensive property damage, severe   personal injury or death!   Figure 2 - Moving Boiler   CAUTION: Do not lift the boiler by the jacket. Use a   hand truck under the base frame as shown in Figure 2.   1. Locate the boiler in an area that provides good   access to the unit. Keep in mind that servicing may   require the removal of jacket panels. Accessibility   clearances must take precedence over fire   protection clearances.   Figure 1 - Clearances to Combustible Construction   Page 4   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   All Combustion Air From Inside The Building   COMBUSTION AIR & VENTILATION   Older houses often have enough “leakage” to provide   an adequate amount of combustion air provided that the   demand for combustion air is not too great, Figure 3.   Homes that are relatively new or “tight” will most likely   require that the combustion be ducted to the boiler from   outside the building. Any home utilizing other gas   burning appliances, a fireplace, wood stove or any type   of exhaust fan must be checked for adequate   combustion air when all of these devices are in   operation at one time.   WARNING: This boiler must be supplied with   combustion air in accordance with Section 5.3,   Air for Combustion & Ventilation, of the latest   revision of the National Fuel Gas Code, ANSI   Z223.1/NFPA 54 and all applicable local building   codes. Canadian installations must comply with   CSA B149.1 or .2 Installation Code for Gas   Burning Appliances and Equipment, or   applicable provisions of the local building   codes. Failure to provide adequate combustion   air for this boiler/water heater can result in   excessive levels of carbon monoxide which can   result in severe personal injury or death!   If the boiler is to be located in an alcove, closet or other   confined space the distances from the boiler and it's   vent system to all-combustible construction must be   equal to or greater than the minimum clearances in   Figure 1. When installed in a closet or confined space   two permanent openings of equal area adjoining another   room or rooms having sufficient volume to meet the   requirements of an unconfined space must be provided,   Figures 4 & 5. Each opening must have a minimum free   area of one square inch per 1000 Btu/hr (2200 mm2/   kW) based on the total input rating of all gas utilization   equipment in the confined area. Each opening must be   no less than 100 square inches (64516 mm2) in size.   The upper opening must be within 12 inches (305 mm)   of, but not less than 3 inches (76 mm) from, the top of   the enclosure. The bottom opening must be within 12   inches (305 mm) of, but not less than 3 inches (76 mm)   from, the bottom of the enclosure.   To operate properly and safely this boiler requires a   continuous supply of air for combustion. NEVER store   objects on or around the boiler!   CAUTION: Combustion air contaminated with   fluorocarbons or other halogenated compounds   such as cleaning solvents and refrigerants will   result in the formation of acids in the combustion   chamber. These acids will cause premature failure   of the boiler voiding the warranty!   CAUTION: If the boiler is operated while the building   is under construction it MUST be protected from   wood, concrete, sheet rock and other types of dust.   Failure to properly protect the unit from   construction dust will damage the unit voiding the   warranty!   All Combustion Air From Outside The Building   When installed in a confined space without the intake   air option two permanent openings communicating   directly with, or by ducts to, the outdoors or spaces that   freely communicate with the outdoors must be present.   The upper opening must be within 12 inches (305 mm)   of, but not less than 3 inches (76 mm) from, the top of   the enclosure. The bottom opening must be within 12   inches (305 mm) of, but not less than 3 inches (76 mm)   from, the bottom of the enclosure.   Buildings may require the installation of a fresh air duct   or other means of providing make-up air if the intake   air option isn't used. Any building utilizing other gas   burning appliances, a fireplace, wood stove or any type   of exhaust fan must be checked for adequate   combustion air when all of these devices are in   operation at one time. Sizing of an outside air duct must   be done to meet the requirements of all such devices.   Where directly communicating with the outdoors or   communicating with the outdoors through vertical ducts,   each opening shall have a minimum free area of 1 in2/   4000 Btu/hr (550 mm2/kW) of the total input rating of   all of the equipment in the enclosure.   WARNING: Never operate this boiler in an   environment subjected to a negative pressure   unless the air intake is connected to the   outdoors. Failure to comply with this warning   can result in excessive levels of carbon   monoxide causing severe personal injury or   death!   Where communicating with the outdoors through hori-   zontal ducts, each opening shall have a minimum free   area of 1 in2/2000 Btu/hr (1100 mm2/kW) of the total   input rating of all of the equipment in the enclosure.   When ducts are used, they must have the same cross-   sectional area as the free area of the opening to which   they connect. Sizing of an outside air duct must be   based on the total input rating of all gas utilization   equipment in the confined space.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 5   When calculating the free area necessary to meet the   Table 1 - Combustion Air Duct Sizing   make-up air requirements of the enclosure,   consideration must be given to the blockage effects of   louvers, grills and screens.   Input Btuh   1/4”Wire   Screen Mesh   Input Btuh   Metal   Louvers   Input Btuh   Wooden   Louvers   FreshAir   Duct Size   3” x 12”   144,000   256,000   384,000   512,000   108,000   192,000   288,000   384,000   36,000   64,000   96,000   128,000   8” x 8”   Screens must have a minimum mesh size of 1/4"   (6.4mm). If the free area through a louver or grill is not   known ducts should be sized per Table 1.   8” x 12”   8-1/2” x 16”   Figure 3 - Horizontal Positive Pressure Venting Using Inside Combustion Air (Cat. III)   Figure 4 - Vertical Negative Pressure Masonry Chimney System Using Inside Combustion Air (Cat. I)   Page 6   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Figure 5 - Vertical Negative Pressure Metal Chimney System and Inside Combustion Air (Cat. I)   Intake Air Option - General Guidelines   Table 2 - Combustion Air System Sizing   This configuration provides combustion air directly to the   boiler using a dedicated pipe. Combustion air can be   drawn in horizontally through an outside wall or vertically   through the roof, see Figures 6, 7, 8, 9 & 10.   Equivalent Intake   Length (see note)   3” Diameter   Equivalent Intake   Length (see note)   4” Diameter   Boiler   Model   Number   GS110-3   GS110-4   GS110-5   GS110-6   GS110-7   45 feet (13.7 m)   45 feet (13.7 m)   45 feet (13.7 m)   n/a   65 feet (19.8 m)   65 feet (19.8 m)   65 feet (19.8 m)   * 40 feet (12.2 m)   * 40 feet (12.2 m)   WARNING: Each boiler must have it's own intake   air system. Common intake air systems are not   to be used! Improper installation can result in   excessive levels of carbon monoxide which can   cause severe personal injury or death!   n/a   * 4" to 3" reducer required.   Note: Subtract 5 feet (1.5 m) for each 90° elbow.   Single wall galvanized smoke pipe, single wall aluminum   pipe, flexible aluminum pipe, PVC or CPVC pipe can be   used for the intake air pipe. Maximum intake lengths   must not be exceeded per Table 2, larger diameters may   be used on 3,4,and 5 section boilers.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 7   All joints in metal intake air systems must be secured   Intake Air Optional - Horizontal Guidelines   using corrosion resistant fasteners and sealed using a   suitable Silicone caulk. If PVC or CPVC is used, the   joints must be cleaned with a suitable solvent and   connected using a solvent based PVC cement. The   intake air system MUST be supported by the building   structure not the boiler/water heater.   The maximum equivalent length for the horizontal intake   air pipe is listed in Table 2. The intake air system must   be pitched down, toward the terminal, 1/4" per foot   (21 mm per meter).   If horizontal runs exceed 5 feet (1.5 m) they must be   supported at 3 foot (0.98 m) intervals with overhead   hangers. Figures 7 through 10 show the four horizontal   air intake options. The intake terminations certified for   use the GS110 are listed in Table 5.   Intake Air Option - Vertical Guidelines   A listed, nonrestrictive intake air cap must be used. The   intake air cap must terminate as shown in Figure 6. The   penetration point in the roof must be properly flashed   and sealed.   Figure 6 - Vertical Positive Pressure Venting with Outdoor Combustion Air (Cat. III)   Page 8   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Figure 7 - Horizontal Positive Pressure Venting with Outdoor Combustion Air   Figure 8 - Horizontal Positive Pressure Venting with Outdoor Combustion Air   Smith   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 9   Figure 9 - Vertical Negative Pressure Masonry Chimney System using Outside Combustion Air (Cat. I)   Figure 10 - Vertical Positive Pressure Venting using Outside Combustion Air (Cat. III)   Page 10   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Certified vent systems are manufactured by the following   companies:   GENERAL VENTING GUIDELINES   Heat-fab, Inc.   WARNING: The vent installation must be in   130 Industrial Blvd., Turners Falls, MA 01376   (800) 772-0739.   accordance with Part 7, Venting of Equipment,   of the National Fuel Gas Code, ANSI Z223.1/   NFPA 54-latest revision or applicable provisions   of the local building codes. Canadian   installations must comply with CSA B149.1 or   .2 Installation Code. Improper venting can result   in excessive levels of carbon monoxide which   can result in severe personal injury or death!   Z-Flex U.S., Inc.   20 Commerce Park North, Bedford, NH 03110-6911   (800) 654-5600.   Protech Systems Inc.   26 Gansevoort Street, Albany, NY 12202   (518) 463-7284   WARNING: Thimbles and fire-stops must be   used where required. A minimum clearance of   6" must be maintained between single wall   metal vents and combustible construction or a   fire resulting in severe personal injury or death   may occur!   GENERAL DIRECT VENT INFO   In this configuration the boiler blower is used to push the   flue products to the outdoors while drawing combustion   air from the outdoors. The instructions under the   COMBUSTION AIR & VENTILATION SECTION must be   followed! The vent system must be sized per Table 3.   WARNING : Each boiler/water heater must have   it's own vent system. Common positive   pressure vent systems are not to be used!   Improper installation can result in excessive   levels of carbon monoxide which can cause   severe personal injury or death!   Table 3 - Positive Pressure Vent System Sizing   Equivalent Vent   Length (see note)   3” Diameter   Equivalent Vent   Length (see note)   4” Diameter   Boiler   Model   Number   GS110-3   GS110-4   GS110-5   GS110-6   GS110-7   45 feet (13.7 m)   45 feet (13.7 m)   45 feet (13.7 m)   n/a   *65 feet (19.8 m)   *65 feet (19.8 m)   *65 feet (19.8 m)   40 feet (12.2 m)   40 feet (12.2 m)   All vent systems must be fully supported by the building   structure and not by the boiler/water heater.   n/a   * 4" to 3" reducer required   Note: Subtract 5 feet (1.5 m) for each 90° elbow.   VENT SYSTEM OPTIONS   The GS110 may be vented the following ways:   1) Direct Vent (Positive Pressure), uses a vent system   certified to UL 1738 for installations in the United States,   ULS636 for installations in Canada. Combustion air is   piped from the outdoors to the blower inlet.   HORIZONTAL DIRECT VENT   SYSTEMS   See figures 7 & 8. The vent materials used in horizontal   positive pressure vent systems must be certified to UL   1738 for installations in the United States, ULS636 for   installations in Canada.   2) Horizontal Vent (Positive Pressure), uses a vent   system certified to UL 1738 for installations in the United   States, ULS636 for installations in Canada. Combustion   air is obtained from the space in which the unit is installed.   Each 90° elbow is equal to 5 linear feet (1.5 m) of pipe.   To maximize the performance of single wall sheet metal   vent systems locate 90° elbows as far from the boiler as   possible and from one another. For best results, horizontal   vent systems should be as short and straight as possible.   The vent system must be both gas tight and watertight.   All seams and joints in metal pipes must be joined and   sealed in accordance with the vent system manufacturer’s   instructions.   3) Vertical Vent (Positive Pressure), uses a vent system   certified to UL 1738 for installations in the United States,   ULS636 for installations in Canada. Combustion air is   piped from the outdoors to the blower inlet or is obtained   from the space in which the unit is installed.   4) Vertical/Chimney Vent (Negative Pressure), uses an   approved metal chimney system or masonry chimney.   Combustion air is obtained from the space in which the   unit is installed or is piped from the outdoors to the blower   inlet.   When horizontal vent runs exceed 5 feet (1.5m) they must   be supported at 3 foot (0.98 m) intervals with overhead   hangers. The vent system must be pitched down, toward   the vent terminal, 1/4" per foot (21mm per meter). If any   part of a single wall metal vent system passes through   an unheated space it must be insulated with insulation   rated for 400°F. Structural penetrations must be made   using approved thimbles.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 11   Horizontal vent systems shall terminate at least 4 feet   HORIZONTAL VENT   (1.3 m) below, 4 feet (1.3 m) horizontally from or 1 foot   (0.23 m) above any door, window or gravity air inlet into   any building. It must not terminate less than 4 feet (1.3   m) horizontally from, and in no case above or below,   unless a 4 feet (1.3 m) horizontal distance is maintained,   from electric meters, gas meters, regulators and relief   equipment and not less than 7 feet (2.3 m) from any   adjacent public walkway. The bottom of the vent   terminal(s) shall be located at least 5 feet (1.5 m) above   the air intake terminal(s). Avoid terminal locations likely   to be affected by winds, snowdrifts, people and pets.   POSITIVE PRESSURE SYSTEMS   See Figure 3. The vent materials used in horizontal   positive pressure vent systems must be certified to UL   1738 for installations in the United States, ULS636 for   installations in Canada.   The maximum vent lengths are listed in Table 3.   Each 90° elbow is equal to 5 linear feet (1.5 m) of pipe.   To maximize the performance of single wall sheet metal   vent systems locate 90° elbows as far from the boiler   as possible and from one another. Horizontal vent   systems should be as short and straight as possible.   Table 4 - Certified Vent & Intake Terminals   Company   Protech   Part No.   300311   Description   Tee   Dia. (in.)   3 4 3 4 3 4 3 4 3 4 3 4 When horizontal vent runs exceed 5 feet (1.5 m) they   must be supported at 3 foot (0.98 m) intervals with   overhead hangers. The vent system must be pitched   down, toward the vent terminal, 1/4" per foot (21 mm   per meter). If any part of a single wall metal vent system   passes through an unheated space it must be insulated   with insulation rated for 400°F. Structural penetrations   must be made using approved thimbles.   Protech   300312   Tee   Protech   300186   Bird Screen   Bird Screen   45° Elbow   45° Elbow   90° Elbow   90° Elbow   Mitered   Mitered   Tee   Protech   300187   Protech   300130   Protech   300131   Protech   300160   Protech   300161   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   7390GC   7490GC   7390TEE   7490TEE   7392GC   7492GC   7314TERM   7414TERM   The vent system must be both gas tight and watertight.   All seams and joints in metal pipes must be joined and   sealed in accordance with the vent system   manufacturer's instructions.   Tee   Screen   Screen   90° Elbow   90° Elbow   3 4 Horizontal vent systems shall terminate at least 4 feet   (1.3 m) below, 4 feet (1.3 m) horizontally from or 1 foot   (0.23 m) above any door, window or gravity air inlet into   any building. It must not terminate less than 4 feet (1.3   m) horizontally from, and in no case above or below,   unless a 4 feet (1.3 m) horizontal distance is maintained,   from electric meters, gas meters, regulators and relief   equipment and not less than 7 feet (2.3 m) from any   adjacent public walkway. The bottom of the vent   terminal(s) shall be located at least 5 feet (1.5 m) above   the air intake terminal(s). Avoid terminal locations likely   to be affected by winds, snowdrifts, people and pets.   Protect building materials and vegetation from   degradation caused by flue gasses.   VERTICAL DIRECT VENT SYSTEMS   See Figures 6 & 10. The vent materials used in vertical   positive pressure vent systems must be certified to UL   1738 for installations in the United States, ULS636 for   installations in Canada.   The maximum length for the vertical vent system is   listed in Table 4. Each 90° elbow is equal to 5 linear   feet (1.5 m) of pipe. To maximize the performance of   single wall sheet metal vent systems locate 90° elbows   as far from the boiler as possible and from one another.   If any part of a single wall metal vent system passes   through an unheated space it must be insulated with   insulation rated for 400°F. Structural penetrations must   be made using approved fire-stops.   Table 5- Certified Vent Terminals   Company   Protech   Part No.   300311   Description   Tee   Dia. (in.)   3 4 3 4 3 4 3 4 3 4 The vent system must be both gas tight and watertight.   All seams and joints in metal pipes must be joined and   sealed in accordance with the vent system   manufacturer’s instructions.   Protech   300312   Tee   Protech   300130   45° Elbow   45° Elbow   90° Elbow   90° Elbow   Tee   Protech   300131   Protech   300160   Protech   300161   Vertical vent systems must be terminated with an   approved terminal cap as shown in Figures 6 & 10.   Heat-Fab   Heat-Fab   Heat-Fab   Heat-Fab   7390TEE   7490TEE   7314TERM   7414TERM   Tee   90° Elbow   90° Elbow   Page 12   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   VERTICAL VENT   WARNING: If an appliance using any type of a   mechanical draft system operating under   positive pressure is connected to a chimney   flue, never connect any other appliances to this   flue. Doing so can result in excessive levels of   carbon monoxide which can cause severe   personal injury or death!   POSITIVE PRESSURE SYSTEMS   See Figure 11. The vent materials used in vertical   positive pressure vent systems must be certified to UL   1738 for installations in the United States, ULS636 for   installations in Canada.   The maximum vent lengths are listed in Table 3.   Chimney Inspection & Sizing   A thorough inspection of the masonry chimney must be   performed to ensure that the chimney is clean, properly   constructed and properly sized. Exterior masonry   chimneys should not be used unless properly lined to   prevent condensation and draft problems. Table 6 lists   the equivalent breeching and flue sizes required for the   boiler/water heater. When more than one appliance is   connected to the same chimney flue the flue must be   large enough to safely vent the combined output of all   of the appliances.   Each 90° elbow is equal to 5 linear feet (1.5 m) of pipe.   To maximize the performance of single wall sheet metal   vent systems locate 90° elbows as far from the boiler   as possible and from one another. If any part of a single   wall metal vent system passes through an unheated   space it must be insulated with insulation rated for 400   °F. Structural penetrations must be made using   approved fire-stops.   The vent system must be both gas-tight and watertight.   All seams and joints in metal pipes must be joined and   sealed in accordance with the vent system   manufacturer's instructions. Vertical vent systems must   terminate as shown in Figures 6 & 11. An approved   terminal cap must be used.   Table 6 - Equivalent Breeching & Chimney Size   Boiler   Model   Vent & Chimney Diameter   inches (mm)   Intake Diameter   inches (mm)   GS110-3   GS110-4   GS110-5   GS110-6   GS110-7   3 (7.6)   4 (10.2)   4 (10.2)   5 (12.7)   5 (12.7)   3 (7.6)   3 (7.6)   3 (7.6)   4 (10.2)   4 (10.2)   VERTICAL VENT   NEGATIVE PRESSURE SYSTEMS   See Figures 4, 5 & 9. The GS110 is listed as a Category   I appliance when vented vertically into a metal chimney   system or masonry chimney sized as listed in Table 6.   Note: These sizes are based on a 20 foot (6.1m)   chimney height.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 13   The vent connector should be sloped up toward the   Always provide a minimum clearance of 6 inches   chimney 1/4" per foot. Ensure that the vent connector   is properly supported and each connection securely   fastened with at least 3 corrosion resistant sheet metal   screws. The termination of the vent pipe must be flush   with the inside of the chimney flue.   between single wall metal vent pipe and any   combustible materials. Type B1 vent may be used,   clearance between it and any combustible material must   be as listed.   WARNING: Failure to maintain minimum   clearances between vent connectors and   combustible materials can result in a fire   causing extensive property damage, severe   personal injury or death!   CAUTION: The vent connector length must never   exceed 3/4 of the height of the chimney or venting   problems will occur!   Figure 11 - Vertical Positive Pressure Venting (Cat. III)   Page 14   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Dans la mesure du possible, fermer toutes les   COMMON VENT SYSTEMS   portes et les fenêtres du bâtiment et toutes les   portes entre l'espace où les appareils toujours   raccordés du système d'évacuation sont installés et   les autres espaces du bâtiment. Mettre en marche   les sécheuses, tous les appareils non raccordés au   système d'évacuation commun et tous les   ventilateurs d'extraction comme les hottes de   cuisinère et les ventilateurs des salles de bain.   S'assurer que ces ventilateurs fonctionnent à la   vitesse maximale. Ne pas faire fonctionner les   ventilateurs d'été. Fermer les registres des   cheminées.   WARNING: DO NOT connect this boiler or any   other appliance using a positive pressure   common vent system or a mechanical draft   system! Failure to comply with this WARNING   could result in the accumulation of carbon   monoxide gas which can cause severe personal   injury or death!   If an existing boiler/water heater is removed from a   common venting system, the common venting system   may then be too large for the proper venting of the   remaining appliances connected to it. At the time of   removal of an existing boiler/water heater, the following   steps shall be followed with each appliance remaining   connected to the common venting system placed in   operation, while the other appliances remaining   connected to the common venting system are not in   operation.   d) Place in operation the appliance being inspected.   Follow the lighting instructions. Adjust thermostat so   appliance will operate continuously.   Mettre l'appareil inspecté en marche. Suivre les   instructions d'allumage. Régler le thermostat de   façon que l'appareil fonctionne de façon continue.   Au moment du retrait d'une chaudière existante, les   mesures suivantes doivent être prises pour chaque   appareil toujours raccordé au système d'évacuation   commun et qui fonctionne alors que d'autres appareils   toujours raccordés au système d'évacuation ne fonction-   nent pas: système d'évacuation   e) Test for spillage at the draft hood relief opening after   5 minutes of main burner operation. Use the flame   of a match or candle, or smoke from a cigarette,   cigar or pipe.   Faire fonctionner le brûleur principal pendant 5 min   ensuite, déterminer si le coupe-tirage déborde à   l'ouverture de décharge. Utiliser la flamme d'une   allunette ou d'une chandelle ou la fumée d'une   cigarette, d'un cigare ou d'une pipe.   a) Seal any unused openings in the common venting   system.   Sceller toutes les ouvertures non utilisées du sys-   tème d'évacuation.   f) After it has been determined that each appliance   remaining connected to the common venting system   properly vents when tested as outlined above, return   doors, windows, exhaust fans, fireplace dampers   and any other gas-burning appliance to their   previous condition of use.   b) Visually inspect the venting system for proper size   and horizontal pitch and determine there is no   blockage or restriction, leakage, corrosion and other   deficiencies which could cause an unsafe condition.   Inspecter de façon visuelle le système d'évacu-ation   pour déterminer la grosser et l'inclinaison   horizontale qui conviennent et s'assurer que le   système est exempt d'obstruction, d'étranglement   de fruite, de corrosion et autres défaillances qui   pourraient présenter des risques.   Une fois qu'il a été d éterminé, selon la métode   indiquée ci-dessus, que chaque appareil raccordé   au système d'évacuation est mis à l'air libre de façor   adéquate. Remettre les portes et les fenêtres, les   ventilateurs, les registres de cheminées et les   appareils au gaz à leur position originale.   c) Insofar as is practical, close all building doors and   windows and all doors between the space in which   the appliances remaining connected to the common   venting system are located and other spaces of the   building. Turn on clothes dryers and any appliance   not connected to the common venting system. Turn   on any exhaust fans, such as range hoods and   bathroom exhaust, so they will operate at maximum   speed. Do not operate a summer exhaust fan for a   boiler installation. Close fireplace dampers.   g) Any improper operation of the common venting   system should be corrected so the installation   conforms with the National Fuel Gas Code, ANSI   Z223.1/NFPA 54. When resizing any portion of the   common venting system, the common venting system   should be resized to approach the minimum size as   determined using the appropriate tables in Appendix   F in the National Fuel Gas Code, ANSI Z223.1/ NFPA   54 and or CSA B149 Installation Codes.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Tout mauvais fonctionnement du systéme d'évacu-   Page 15   WARNING: Failure to connect a condensate trap   or pump to the flue collector can result in   excessive levels of carbon monoxide which can   cause severe personal injury or death!   tion commun devrait étré corrigé de façor que   l'installation soit conforme au National Fue Gas Code,   ANSI Z223.1/NFPA 54 et (ou) aux codes d'in-   stallation CSA-B149. Si la grosseur d'une section du   système d' évacuation doit étré modifiée, le système   devrait étré modifié pour respecter les valeurs   minimales des tableaux pertinents de l'appendice F   du National Fuel Gas Code, ANSI Z223.1/ NFPA 54   et (ou) des codes d'installation CSA-B149.   HEATING SYSTEM PIPING   CAUTION: All heating system piping must be   installed in accordance with the ANSI/ASME Boiler   and Pressure Vessel Code, Section IV. All applicable   local codes and ordinances must also be followed.   If the boiler is installed above any radiation   elements it must be fitted with a low water cutoff   device installed above the normal boiler water level!   CONDENSATE PIPING   A small amount of condensate is generated on start up.   To prevent an excess amount of condensate collecting   in the flue collector a condensate drain has been   provided. A condensate trap or pump MUST be   connected to the condensate fitting in the bottom of the   flue collector.   The GS110 hot water boiler comes from the factory   ready to be piped to the heating system. Each boiler is   equipped with a safety relief valve which must be piped   in accordance with the ANSI/ASME Boiler and Pressure   Vessel Code, Section IV, see Figure 13.   A trap can be made by tie wrapping a 4” loop in a piece   of vinyl hose attached to the condensate drain fitting.   The trap must be filled with water to prevent flue   gassses from escaping, see Figures 12 A and B.   Table 7 - Boiler Water Volume   Boiler   Model   Water Volume   Gallons   1.8   Liters   6.8   A condensate hose has been supplied with   boiler and is located inside the literature bag.   Installing contractor will have to continue the   run of condensate to a nearby drain or pump.   GS110-3   GS110-4   GS110-5   GS110-6   GS110-7   2.4   9.1   3.0   11.4   13.6   15.9   3.6   4.2   Figure 12A- Condensate Trap   * 1-1/2 " Supply and Return Tappings   Figure 13 - Relief Valve Piping   Figure 12B- Condensate Trap   SIOM-75   Page 16   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Ensure that the boiler is level from front to back and   from side to side. Use metal shims to level the boiler.   NEVER use combustible materials for shims.   Pump Away Bypass   The system bypass shown in Figure 15 should be used   on single zone systems, or multiple zone systems using   zone valves, when the circulator is installed in the supply   piping. The bypass must be installed between the supply   and return pipes on the pressure side of the circulator.   Bypass Piping   CAUTION: Never connect this boiler directly to a   large volume system, in-floor radiant system, snow   melt system or any other system that would cause   the steady state water temperature in the boiler to   drop below 140°F. To prevent damage due to   excessive condensation, one of the following piping   options must be used or the boiler warranty will be   voided!   Figure 15 - Pump Away Bypass Piping   CAUTION: The blend pump arrangement shown in   Figure 16 must be used when the flow from any   zone in a multiple zone system is less than 4 GPM   or boiler short cycling on the high limit will occur!   For the three systems listed below, adjust the bypass   valve to divert some of the heated water back into the   boiler's return piping. When adjusted correctly the   temperature of the boiler water will exceed 140°F within   five minutes of a warm start. A plug valve should be   used as the bypass valve for best system performance.   NOTE: Some of the circulator's capacity will be used   in the blending process for the first two systems.   Large heating systems may require a larger   circulator.   Pumped Blend Bypass   The system bypass shown in Figure 16 should be used   on multiple zone systems. The bypass must be installed   between the supply and return pipes on the suction side   of the zone circulators. The bypass valve must be   installed on the pressure side of the bypass circulator.   System Bypass   The system bypass shown in Figure 14 should be used   on single zone systems, or multiple zone systems using   zone valves, when the circulator is installed in the return   piping. The bypass must be installed between the supply   and return pipes on the suction side of the circulator.   Figure 16 - Pumped Bypass Piping   Figure 14 - System Bypass Piping   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 17   Figure 17 - TACO 007 Performance Curve   Piping For Use With Cooling Units   The boiler, when used in connection with a refrigera-tion   system must be installed so the chilled medium is piped   in parallel with the boiler. Appropriate valves must be   used to prevent the chilled water from entering the   boiler.   10   8 6 When a boiler is connected to a heating coil that may be   exposed to refrigerated air from an air handling device, the   piping system must be equipped with flow-control valves or   some other automatic means of preventing gravity   circulation of the boiler water during the cooling cycle.   4 Circulators   TACO 007 CIRCULATOR   PERFORMANCE CURVE   The TACO 007 circulator supplied with the boiler is sized   for use in a closed heating system with a 30 psi   maximum operating pressure. If the 007 circulator does   not have the required capacity for the system in which   it is to be installed, an extra zone circulator or a higher   capacity circulator will be needed. Figure 17 depicts the   performance curve for the TACO 007 circulator.   2 0 0 5 10   15   20   25   FLOW - GPM   Page 18   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   ormance criteria were met   Safe lighting and other perf   GAS SUPPLY PIPING   ly provided on   with the gas manifold and control assemb   The GS110 hot water boiler comes from the factory   ready to be piped to the gas supply. The gas supply can   be piped from the left or right side of the boiler.   GS110   the boiler when the boiler underwent tests specified in   ANSI Z21.13. All gas connections MUST be leak tested   ation.   before putting the boiler into oper   Section   Size   Connection   Tapping   Table 8 - Gas Pipe Capacity   Pipe length in feet   40 50 60   Gas pipe Capacity (ft3/hr)   278 190 152 130 115 105 90   Nominal   Iron Pipe   Size, (in)   1/2"   1/2"   1/2"   3/4"   3/4"   3 4 5 6 7 10   20   30   80 100 150   3 79 64   /4   ″ 520 350 285 245 215 195 170 150 120   1050 730 590 500 440 400 350 305 250   1600 1100 890 760 670 610 530 460 380   1″   11/4   11/2   ″ ″ If for any reason the boiler is not for the type of gas   available at the installation site, call the nearest Smith   Cast Iron Boiler distributor to resolve the problem.   Note: Maximum pipe capacity in ft3/hr is based on a 0.60 specific   gravity gas at a pressure of 0.5 psig and a 0.3" WC pressure drop.   Figure 18 depicts the proper way to connect the boiler   to the gas supply piping. The manual shut-off valve   MUST be installed in the supply piping. It should be   approximately 5 feet above the floor. Provide a sediment   trap/drip leg at the bottom of the vertical section of the   gas supply pipe. A ground joint union should be installed   between the boiler gas controls and the supply piping.   Each of these items is needed to ensure long life and   ease of servicing. Always use a pipe sealant that is   suitable for use with LP gas.   t Table 9 - Equivalent Pipe Length Char   Type of pipe fitting   Nominal   Iron Pipe   Size, (in)   Tee   Gas Valve   (full port)   90° Elbow   Gas Cock   (branch flow)   Equivalent length of pipe fitting in feet   3 2.6   3.5   4.0   5.2   5.2   6.9   0.6   0.8   0.9   1.2   1.5   1.9   2.3   3.0   / 4 ″ 1″   11/4   11/2   8.0   ″ ″ 10.3   Whenever the gas supply piping is pressure tested the   Figure 18 - Gas Supply Piping   ust be protected. If the test pres-   boiler gas controls m   a) isolate   sure is equal to, or less than 1/2 psig (3.5 kP   ual shut off valve, see   the boiler by closing it's man   Figure 18. If the test pressure is greater than 1/2 psig   (3.5 kPa), disconnect the boiler and it's individual shut-   off valve from the gas supply piping.   or   WARNING: Never use an open flame to test f   ved leak   ys use an appro   gas leaks. Alwa   Failure to comply with this   detection method.   xplosion!   WARNING could result in an e   WIRING   ELECTRICAL   CAUTION: Label all wires prior to disconnection   ols. Wiring errors can cause   when servicing contr   erous operation!   improper and dang   ATTENTION: Au moment de l'entretien des   vant de les   CAUTION: Always use a wrench on the gas valve   body when making gas connections to it. Never   over-tighten the piping entering the gas valve body   or the gas valve will be damaged!   commandes, étiquetez tous les fils a   s de câblage peuvent   débrancher. Des erreur   entraîner un fonctionnement inadéquat et   onctionne   dangereux. S'assurer que l'appareil f   ois l'entretirn terminé.   adéquatement une f   Table 8 should be used to ensure that the gas supply   piping is sized properly. If more than one appliance is   supplied by the same supply pipe, the piping must be   sized based on the maximum possible demand. Do not   neglect the pressure drop due to pipe fittings. Table 9   should be used in conjunction with Table 8 to ensure   that the gas supply piping is sized properly.   The electrical connections to this boiler/water heater   must be made in accordance with all applicable local   ical   vision of the National Electr   codes and the latest re   Code, ANSI /NFPA-70.   orm   Installation should also conf   with CSA C22.1 Canadian Electrical Code Part I if   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 19   installed in Canada. Install a separate 120 volt 15 amp   Once the flame has been proven, the system is in   circuit for the boiler. A properly rated shut-off switch   should be located at the boiler. The boiler must be   grounded in accordance with the authority having   jurisdiction, or if none, the latest revision of the National   Electrical Code, ANSI/NFPA-70.   Steady-State heating mode. The control will continuously   monitor the thermostat, limit switch, pressure switch, and   flame sense. If the thermostat opens, the control will   de-energize the gas valve and begin post-purge. If the   limit switch opens, the control will de-energizes the gas   valve, run through post-purge, and wait for the limit   switch to re-close before attempting re-ignition. If flame   is lost, the control will de-energize the gas valve, run   through post-purge, and go to pressure switch proving   mode for re-ignition. If the pressure switch opens for   more than 0.1 seconds the inducer is turned off for 30   seconds, then the control goes to the pressure switch   proving mode for a re-ignition attempt.   Line voltage field wiring of any controls or other devices   must use copper conductors with a minimum size of #14   awg. Low voltage wiring must not be less than #18 awg   with a neoprene, thermoplastic or other equivalent   insulation having a minimum insulation thickness of   0.012 inches.   Refer to Figures 19A and 19B for proper wiring   connections.   When the thermostat is satisfied the post purge period   starts. A post-purge will be performed at any time the   gas valve has been on and is turned off, except for loss   of pressure switch, when a post-purge would be   ineffective. The post-purge must be completed before a   new ignition sequence can start.   Thermostat Installation   ALWAYS follow the instructions included with the ther-   mostat to be used to control the boiler. Proper location   of the thermostat will ensure efficient trouble-free   operation of the boiler. Mount the thermostat to an inside   wall at a height approximately five feet above the floor.   Avoid placing the thermostat in areas that will not pro-   vide an accurate measurement of the room temperature.   Locating the thermostat behind a door, in an alcove,   close to a source of thermal radiation or in a drafty area   will cause poor or sporadic heating.   In the event that the flame signal is lost after the flame   has been proven, the system will turn off the gas valve   within 2.0 seconds, perform the post-purge, and repeat   the ignition sequence. As a preventative measure to   avoid nuisance shutdown due to a flickering flame, the   flame must be lost for a minimum of 0.5 seconds.   Control Outputs:   Induced draft blower - 1.75 Amps @ 120 VAC.   OPERATIONAL SEQUENCE   The control energizes the circulator motor when the   thermostat contacts are closed. The control then checks   that the limit switch is closed, if not the control will wait   for the limit switch to close. With the limit switch closed   the pressure switch contacts are checked. If the   pressure switch contacts are open the blower motor is   energized. If the pressure switch contacts aren’t open   the control will wait 45 seconds then lock out. The   PURGE light will flash to indicate a pressure switch fault.   Also, if the pressure switch does not close within 5   minutes of the blower being turned on, the control will   lock out with the PURGE light flashing to indicate a   pressure switch fault.   Circulator Pump - 2.7 Amps @ 120 VAC.   Hot Surface Igniter - 5.0 Amp resistive @ 120 VAC.   Gas Valve - 0.6 Amp @ 24 VAC, 0.45 power factor.   The pre-purge period begins when the pressure switch   contacts close. At the end of the pre-purge period, the   control energizes the HSI igniter for an HSI warm-up   period. This condition will be indicated by illumination of   the IGNITER light. A one second trial for ignition will take   place. In the event ignition is not achieved by the end of   the first trial for ignition period, the control will run through   a post purge and then de-energize the inducer. When   the pressure switch contacts open the control will begin   a new ignition sequence. Failure to establish flame after   the third attempt will result in ignition lock-out and the   VALVE light on the control will flash.   Page 20   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Figure 19A - Wiring Connection Diagram   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 21   Figure 19B - Wiring Ladder Diagram   B Page 22   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   FORYOUR SAFETY READ BEFORE OPERATING   WARNING: If you do not follow these instrucitons exactly, a fire or explosion may result   causing property damage, personal injury or loss of life.   A. This appliance does not have a pilot. It is   • If you cannot reach your gas supplier, call the fire   department.   equipped with an ignition device which   automatically lights the burner. Do not try to light   the burner by hand.   C. Use only your hand to push in or turn the gas   control knob. Never use tools. If the knob will not   push in or turn by hand, don't try to repair it, call   a qualified service technician. Force or attempted   repair may result in a fire or explosion.   B. BEFORE OPERATING smell all around the   appliance area for gas. Be sure to smell next to   the floor because some gas is heavier than air   and will settle on the floor.   D. Do not use this appliance if any part has been   under water. Immediately call a qualified service   technician to inspect the appliance and to replace   any part of the control system and any gas control   that has been under water.   WHAT TO DO IF YOU SMELL GAS   • Do not try to light any appliance.   • Do not tough any electric switch; do not use any   phone in your building.   • Immediately call your gas supplier from a neighbor's   phone. Follow the gas suppliers instructions.   OPERATING INSTRUCTIONS   1. STOP! Read the safety information above.   2. Turn off all electric power to the appliance.   3. Set the thermostat to lowest setting.   5. Remove control access panel.   6. Turn the gas control knob clockwise   to the   full “OFF” position, on the White Rodgers 36E   push the knob before turning it.   4. This appliance is equipped with an ignition device,   which automatically lights the burner. Do not try   to light the burner by hand!   7. “Wait five (5) minutes** to clear out any gas. Then   smell for gas, including near the floor. If you smell   gas, STOP! Follow “B” in the safety information   above (to the left) on this label. If you don't smell   gas, go to the next step.”   8. Turn the gas control knob counterclockwise   to “ON”.   9. Replace control access panel.   10. Turn on all electric power to the appliance.   11. Set thermostat to desired setting.   12. If the appliance will not operate, follow the   instructions “TO TURN OFF GAS TO   APPLIANCE” and call your service technician or   gas supplier.   TO TURN OFF GAS TO APPLIANCE   1. Turn off all electric power to the appliance.   2. Set the thermostat to lowest setting.   3. Remove control access panel.   4. Push in gas control knob slightly and turn   clockwise   to “OFF”. Do not force.   5. Replace control access panel.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 23   POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE   AVERTISSEMENT. Quinconque ne respecte pas à la lettre les instructions dans la présente   notice risque de déclencher un incendie ou une explosion entraînant des dommages, des   blessures ou la mort.   • Si vous ne pouvez rejoindre le fournisseur, appelez   le service de incendies.   A. Cet appareil ne comporte pas de veilleuse. Il est   muni d'un dispositif d'allumage qui allume   automatique la brûleur. Ne tentez pas d'allumer   la brûleur manuellement.   C. Ne poussez ou tournez la maneette d'admission   du gaz qu'à la main; ne jamais utiliser d'outil. Si   la manette reste coincée ; ne pas tenter de la   réparer; appelez un technicien qualifié. Le fait de   forcer la manette ou de la réparer peut déclencher   une explosion ou un incendie.   B. AVANT DE FAIRE FONCTIONNER, reniflez tout   autour de l'appareil pour déceler une odeur de   gaz. Reniflez près du plancher, car certains gaz   sont plus lourds que l'air et peuvent s'accumuler   au niveau du sol.   D. N'utilisez pas cet appareil s'il a été plongé dans   l'eau, même partiellement. Faites inspecter   l'appareil par un tecnicien qualifié et remplacez   toute partie du système de contrôle et toute   commande qui ont été plongés dans l'eau.   QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ   • Ne pas tenter d'allumer d'appareil.   • Ne touchez à aucun interrupteur; ne pas vous servir   des téléphones se trouvant dans le bâtiment.   • Appelez immédiatement votre fournisseur de gaz   depuis un voisin. Suives les instructions du   fournisseur.   INSTRUCTIONS DE MISE EN MARCHE   1. ARRÊTEZ! Lisez les instructions de sécurité sur   la portion supérieure de cette étiquette.   7. <<Attendre cinq (5) minutes** pour laisser   échapper tout le gaz. Reniflez tout autour de   l'appareil, y compris près du plancher, pour   déceler une odeur de gaz. Si vous sentez une   odeur de gaz, ARRÊTEZ! Passez à l'étape B des   instructions de sécurité sur la portion supérieure   (à gauche) de cette étiquette. S'il n'y a pas   d'odeur de gaz, passez à l'étape suivante.>>   2. Mette le thermostat à la température la plus   basse.   3. Coupez l'alimentation électrique de l'appareil.   4. Cet appareil est équipé d'un dispositif d'allumage   automatique la brûleur.   8. Tourner le bouton de commande de gaz vers la   gauche   , en position de marche “ON”.   9. Replacer le panneau de parte du réchauffer.   10. Rétablìr toute l'alimentation électrique de la   chaudiere.   11. Mette le thermostat thermostat sur le régleage   désiré.   5. Enlever le panneau de parte du réchauffer.   12. Si l'appareil ne fonctionné pas, voir les instructions   de “COÙPURE DE L'ARRIVE DE GAZ A LA   CHAUDIERE” et appeler un technicien reparateur   ou le fournisseur de gaz.   6. Tourner le bouton de commande de gaz vers la   droite   , en position d'arrêt “OFF”. Ne pas   forcer!   COÙPURE DE L'ARRIVE DE GAZ A LA CHAUDIERE   1. Mette le thermostat à la température la plus basse.   4. Tourner le bouton de commande de gaz vers la   droite   forcer!   , en position d'arrêt "OFF". Ne pas   2. Si un entretien doit être effectué, coupez   l'alimentation électrique de l'appareil.   5. Replacer le panneau de parte du réchauffer.   3. Lever le panneau de parte du réchauffer.   Page 24   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   B. Read, understand and follow the operating   instructions, on pg. 22 of this manual.   BOILER SET UP   NOTE: Before starting the boiler, turn off the   C. Raise the thermostat at least 5 degrees above the   room temperature. A delay of about 30 seconds will take   place as the silicon carbide ignitor heats up. Once the   ignitor is hot, the main gas valve will open and the burner   should light. If the burner fails to light the system will   make two more ignition attempts. If the burner lights, but   goes out within 4 seconds, the system will make three   ignition attempts. If the burner has not lit after the last   ignition try, the gas valve will close and the system will   go into lock out. DO NOT attempt to reset the system   until the ignition system has been inspected and the   problem resolved. Once the problem has been resolved   and 5 minutes have passed since the last ignition attempt,   reset the system by turning the thermostat to it's lowest   setting and then back to where it was or by momentarily   interrupting the electrical power to the boiler.   electrical supply going to it. Make sure that gas is   available at the gas valve inlet. Open the valves in   the return and supply piping. Failure to take these   precautions will prevent the boiler from operation   properly.   Fill the boiler and all of the radiation with water. Make   sure that the system is completely purged of air.   Review these instructions and make sure that the boiler   installation complies with ALL of the instructions up to   this point.   BOILER OPERATION   WARNING: Before operating read and   understand the instructions contained in this   manual. Do not attempt to operate this boiler if   it has not been installed in accordance with the   guidelines set forth in this manual. Read and   fully understand the operating instructions in   the “For Your Safety Read Before Operating”   section of this manual, pg 22 & 23. Failure to   comply with this WARNING could result in a fire   or explosion!   D. With the burner in operation the manometer should   show 1.9"W.C.manifold pressure. If not, see the BOILER   CHECKING & ADJUSTMENT section.Close the manual   shutoff valve in the gas supply line.As soon as the burner   flame goes out, open the manual shutoff valve.A normal   ignition sequence should take place.   E. With the burner in operation, interrupt the power to   the control circuit by lowering and raising the thermo-   stat. A normal ignition sequence should follow.   Should overheating occur or the gas supply fail to shut   off, do not turn off or disconnect the electrical supply to   the pump. Instead, shut off the gas supply at a location   external to the appliance.   F. To test the ignition safety shutoff device, close the   manual shutoff valve in the gas supply line. Within 6   seconds of main burner flame extinction, the main gas   valve solenoid should close with an audible noise. The   igniter should glow and make three attempts at ignition.   After unsuccessfully attempting to light the burner the   ignition module should lock out.   En cas de surchauffe ou si l’alimentation de gaz ne peut   être coupée, ne pas couper ni débrancher l’alimentation   électrique de la ponpe. Fermer plutôt le robinet   d’admission de gaz à l’extérieur de l’appareil..   Open the manual shutoff valve in the gas supply line.   Reset the ignition control system by interrupting, then   restoring electrical power to the boiler. A normal ignition   sequence should take place.   Do not use this appliance if any part has been under   water. Immediately call a qualified service technician to   inspect the appliance and to replace any part of the   control system and any gas control that has been under   water.   N’utiliisez pas cet appareil s’il a été plongé dans l’eau,   même partiellement. Faites inspecter l’appareil par un   tecnicien qualifié et remplacez toute partie du système   de contrôle et toute commande qui ont été plongés dans   l’eau.   Direct Ignition System   A. Connect a manometer to the pressure ports shown   in Figure 20. Make sure that the gas supply piping has   been purged of air and that all gas joints up to the gas   valve have been thoroughly checked for leaks. Wait at   least five minutes for any gas to dissipate before turning   on the electrical power.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 25   Figure 20- Air and Manifold Pressure   PROPANE GAS:   The input rate for LP units is factory set based on the   orifice size. The manifold pressure must be set at 1.9"   W.C. and the orifice supplied with the boiler used unless   the unit is to be derated for altitude.   BOILER CHECKING & ADJUSTMENT   INPUT RATE   Gas appliances are rated based on sea level operation   with no adjustment required at elevations up to 2000   feet. At elevations above 2000 feet, input ratings should   be reduced by 4% for each 1000 feet above sea level.   Check the input rate as follows:   CAUTION: Never increase the input to the boiler   above that for which it is rated. Doing so can cause   premature failure of the boiler!   GAS PRESSURE ADJUSTMENT   NATURAL GAS:   1. Turn off all other gas appliances that use the same   gas meter as the boiler.   NATURAL GAS:   Optimum results are obtained when the boiler is   operated at its full input rating, with 1.9" W.C. of manifold   pressure.The manifold pressure should not be more that   5% off this value. The gas valve pressure regulator has   been preset at the factory. If adjustment is necessary   the following steps must be followed:   2. Call the gas company for the gas heating value.   3. Start the boiler and let it run for 15 minutes.   4. Using the gas meter and a stopwatch, clock the time   that it takes to burn 10 cubic feet of gas and divide   the time by 10.   5. Insert the heating value and the time, in seconds,   into the formula below.   1. Connect each side of a manometer to the two   pressure ports shown in Figure 20 to obtain the   manifold pressure.   Input Rate = Heating Value(Btu/ft3)(3600 s/hr)   Flow Rate(s/ft3)   2. Connect a flue gas analyzer to the vent pipe.   3. Rotate the regulator adjustment screw clockwise to   increase the manifold pressure, counterclockwise to   decrease it. Never force the regulator adjustment   screw or the gas valve will be damaged!   4. The CO2 reading should fall between 7% and 9%   with a CO reading of less than 50 ppm air free.   5. Adjust the air damper using the screw on the front   of the filter box if the CO2 and CO readings are not   within the range given in step 4.   EXAMPLE: If the heating value = 1000 Btu/ft3   and the flow rate = 36 s/ft3   Input Rate = (1000 Btu/ft3)(3600 s/hr)   36 s/ft3   Input Rate = 100,000 Btu/hr   6. Recheck the manifold pressure and adjust it if   necessary.   7. Replace the regulator adjustment screw cap and   pressure port caps once the boiler is properly set   up.   If the computed rate deviates by more than 5% from the   rated input value of the unit adjust the gas valve   pressure accordingly. DO NOT adjust the manifold   pressure by more than 5%. If a proper rate cannot be   maintained without adjusting the manifold pressure   beyond the 5% limit, the burner orifice must be replaced.   If the input rate is too low go to the next larger size   orifice. if the input rate is too high, go to the next smaller   size orifice.   PROPANE GAS:   A manifold pressure of 1.9" W.C. must be maintained   for proper operation of the boiler. If the manifold   pressure is off by more than 5% or if the CO2 and CO   readings are not within the range specified in step 4   above, adjust it according to steps 1 through 7 above.   Page 26   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Main Burner Flame   A properly adjusted main burner flame will produce a   Burner Box Removal & Replacement   tight blue flame pattern about 1/2 inch tall from the   burner’s surface, Figure 21. A yellow floating or tall   stringy flame is not normal and must be corrected.   CAUTION:The burner box should not be removed!   Careless handling can damage the burner.   WARNING:The ceramic combusiton chamber in   the burner box and its gasket contain crystalline   silica. Wear a tightly fitted dust mask when   servicing the burner and gently handle the   burner and its gasket to prevent inhalation of   airborne fibers. Crystalline silica fibers have   been identified as carcinogenic, or possibly   carcinogenic when inhaled.   WARNING:Yellow, floating flames indicate a lack   of combustion air. DO NOT operate the boiler   until the problem is solved or severe personal   injury or death may occur!   Figure 21 - Burner Flame   If you suspect a problem within the burner assembly,   please contact a local manufacturer representative.   TIGHT BLUE FLAME   Condensate System   Ensure that the condensate removal system is sound   and working properly.   Vent System   YELLOW FLOATING FLAME   The entire vent system must be thoroughly inspected   for any signs of blockage, corrosion or leaks.   Immediately replace any unsound vent system piping.   Remove any foreign matter in or near the vent terminal   or around the boiler that might obstruct the flow of   combustion and ventilation air.   Thermostat Adjustment   Set the heat anticipator to 1.1 amps when controlling   the boiler directly. For zoned systems set the heat   anticipator to match the amp draw of the zone valves   or pump relays.   Blower Motor   Every 3 to 6 months, lubricate the inducer motor using   2 drops of 20W non detergent motor oil in each oil port.   BOILER MAINTENANCE   The boiler should be cleaned and inspected once a   year, before each heating season. Refer to Figures 22   for component identification   Low Water Cutoff   If the boiler has been equipped with a low water cut-   off device, follow the manufacturer's instructions for   cleaning and to confirm proper operation   CAUTION: Servicing, inspection and adjustment   must be done by a trained technician in accordance   with all applicable local and national codes.   Improper servicing or adjustment could damage the   boiler!   Relief Valve   The relief valve should vent water when the test lever   is lifted. It should not weep or discharge water at normal   system pressure. NEVER try to clean or repair the relief   valve! If the valve fails replace it!   Control Panel   Use a soft brush and/or a vacuum cleaner to ensure that   the electrical components are free from dust or deposits   that would impair the boiler's performance.   Aquastat High Limit   The aquastat high limit controls the maximum water   temperature in the boiler. It is adjustable from 140°F   (60°C) to 220°F (104°C). If the water temperature   reaches the set temperature before the demand for heat   has been met, the aquastat high limit should shut the   burners off. The outlet water temperature should never   exceed 220°F (104°C). If the aquastat high limit fails to   function properly replace it.   Air Filter   1. Remove the front jacket panel.   2. Remove the filter box cover and filter.   3. Wash the filter in warm water. Shake out all excess   moisture before reinstalling.   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 27   The symptoms of CO poisoning are often confused with   INSTRUCTIONS TO THE INSTALLER   those of influenza, and the highest incidence of   poisoning occurs at the onset of cold weather or during   flu season. A victim may not experience any symptoms,   only one symptom, or a few symptoms. Suspect the   presence of carbon monoxide if symptoms tend to   disappear when you leave your home.   The INSTALLER must give this copy of the INSTAL-   LATION AND OPERATING INSTRUCTIONS to the   boiler owner and make sure that the owner or operator   has a basic understanding of the following:   1. The operating instructions, the type of ignition   system installed and how it operates.   2. What the labels on the boiler say.   3. How to start up and shut off the boiler.   4. How to turn the gas and electrical power on or off.   5. What to do if the boiler ignition system locks out.   6. Where to check the system temperature and   pressure and what they should be.   7. The importance of reading, understanding and   following these instructions.   8. The importance of visually inspecting the vent   system on a monthly basis.   The following signs may indicate the presence of carbon   monoxide:   • Hot gases from appliance, venting system, pipes or   chimney, escaping into the living space.   • Flames coming out around the appliance.   • Yellow colored flames in the appliance.   • Stale or smelly air.   • The presence of soot or carbon in or around the   appliance.   • Very high unexplained humidity inside the building.   If any of the symptoms of CO poisoning occur, or if any   of the signs of carbon monoxide are present, VACATE   THE PREMISES IMMEDIATELY AND CONTACT A   QUALIFIED HEATING SERVICE COMPANY OR THE   GAS COMPANY OR THE FIRE DEPARTMENT!   The INSTALLER MUST make sure that the owner   knows to shut the boiler off and call for service if the   following conditions occur:   1. Yellow lazy flames or flames outside the jacket.   2. Gas smell or other strange odors.   WARNING: Improper installation, adjustment,   alteration, service or maintenance can cause   property damage, personal injury exposure to   hazardous materials or loss of life. Installation   and service must be performed by a qualified   installer, service agency or the gas supplier who   must read and follow the supplied instructions   before installing, servicing or removing this   boiler. This boiler contains crystalline silica   materials that have been identified as   carcinogenic or possibly carcinogenic to   humans when inhaled.   3. Discoloration of the boiler or surrounding materials.   4. Water leaking from the heating system piping or   relief valve.   5. Flue products leaking from the vent system into the   living space. Dampness or condensation in the   building is a good indicator of this condition.   6. The boiler's flame rollout safety system is actuated.   7. Control malfunction or sporadic operation.   Any appliance that burns natural gas, propane gas, fuel   oil, wood or coal is capable of producing carbon   monoxide (CO). Carbon Monoxide (CO) is a gas, which   is odorless, colorless and tasteless but is very toxic. If   your Smith boiler is not working properly, or is not vented   properly, dangerous levels of CO may accumulate. CO   is lighter than air and thus may travel throughout the   building.   AVERTISSEMENT: Une installation, un réglage,   une modification, une réparation ou un entretien   non comforme aux normes peut entraîner des   dommages matériels, des blessures exposition   à des matières dangereuses ou la mort.   L'installation et l'entretien doivent être effectués   par un installateur ou un service d'entretien   qualifié ou le fournisseur de gaz qui doivent   avoir lu les instructions fournies avant de faire   l'installation, l'entretien ou l'enlèvement de la   chaudière et les respecter, Cette chaudière   contient des matériaux qui ont été identifiés   comme étant cancérogènes ou pouvant l' être.   BRIEF EXPOSURE TO HIGH CONCENTRATIONS OF   CO, OR PROLONGED EXPOSURE TO LESSER   AMOUNTS OF CO MAY RESULT IN CARBON MON-   OXIDE POISONING! EXPOSURE CAN BE FATAL   AND EXPOSURE TO HIGH CONCENTRATIONS MAY   RESULT IN THE SUDDEN ONSET OF SYMPTOMS   INCLUDING UNCONSCIOUSNESS.   Symptoms of CO poisoning include the following:   Dizziness, vision problems, shortness of breath,   headaches, loss of muscle control, unclear thinking,   nausea, weakness and unconsciousness.   Page 28   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Page 29   SERVICE AND REPLACEMENT PARTS LIST   Model Size with Item Quantities Below   Ref #   Name of Part   Part #   3 4 5 6 7 1 Rear, Top, Front & Inner Panels   59450   59451   59452   59453   59454   59495   59496   50064   50065   55532   1 1 1 1 1 1 1 2 3 4 Left Jacket Side Panel   1 1 1 1 1 1 1 1 1 1 1 Right Jacket Side Panel   Gas Valve, White Rodgers 36E65   Gas Valve, White Rodgers 36D27   Blower, Fasco 702110816   1 1 1 1 1 1 1 1 5 6 7 8 1 1 1 1 1 1 1 1 1 1 1 1 Transformer, Honeywell AT140B-1016, 40 VA 51032   Ignition Control, UTC 1013-13B   Pressure Switch   51196   .45 WC 55539   .49 WC 55540   .54 WC 55541   60133   1 1 2 1 1 1 1 9 Terminal Strip, 2 position   Terminal Strip, 3 position   Gas Tube   2 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 2 1 1 1 1 10   11   12   13   14   60134   59396   Filter   50524   Limit Control, Honeywell L6008A-1242   Burner Box Assembly, NG Orifice   includes items 15 thru 22 installed   50524   70-1050   70-1051   70-1052   70-1053   70-1054   70-1055   70-1056   70-1057   70-1058   70-1059   03-1006   03-1007   61023   1 1 1 1 1 Burner Box Assembly, LP Orifice   includes items 15 thru 22 installed   1 1 1 1 1 1 1 1 1 15   16   17   18   19   20   RH Mounting Bracket   1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 LH Mounting Bracket   Barbed Fitting   Male Connector 1/2"   60861   Compression Spring LC-045H-0   Main Gas Orifice, Natural Gas   0 - 2000' (consult factory for high altitude)   20-1000   59434   59514   1 59437   1 1 59398   1 59399   1 Main Gas Orifice, LP   59433   1 0 - 2000' (consult factory for high altitude)   59515   1 59435   59436   1 59516   1 1 1 1 1 1 1 3 1 4 21   22   23   24   O-Ring   06-1002   59499   1 1 1 1 1 1 3 1 4 1 1 1 1 1 1 3 1 4 1 1 1 1 1 1 3 1 4 1 1 1 1 1 1 3 1 4 Blower Outlet Gasket   Ground Rod PSE ME8   Igniter, Norton 601XBM NG   Igniter, Crystal Tech, LP   Flame Sensor, PSE ME7   Spring Clip   50038   50033   16-1000   50037   25   26   27   28   59449   Gasket   59497   1/4-20 x 2-1/4" Screw   60824   Page 30   GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS   Model Size with Item Quantities Below   Ref #   29   30   Name of Part   Thermal Switch   Block Assembly   Part #   59481   72076   72077   72078   72079   72080   59456   59459   59460   59461   59462   59463   59427   59428   59429   59430   59431   59392   03-1033   03-1034   03-1035   03-1036   03-1037   59432   72070   72071   61988   60265   76001   76002   76003   76004   76004   76005   76006   3 1 1 4 1 5 1 6 1 7 1 1 1 6 1 1 6 1 6 31   32   Jacket Bracket   6 1 6 1 Frame Cross Members   1 1 33   Flue Collector   1 1 1 2 1 1 2 1 2 34   35   5/16-18 X 7-1/2" Stud   Flue Collector Clamp   2 1 2 1 1 1 1 1 1 1 1 1 1 36   37   Drain Filtting PEM CLS-0428-1   Right Base Frame Assembly   Left Base Frame Assembly   Relief Valve   1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 38   N/S   N/S   See   Fig.   20A   Temperature & Pressure Gauge   Transformer Primary Harness, P1   Transformer Secondary Harness, P2   Control Harness, P3   1 1 1 1 1 1 1 1 Circulator Harness, P4   HSI Harness, P6   1 1 1 1 1 1 1 1 1 L1, L2 Harness, P7   260 NORTH ELM STREET WESTFIELD, MA 01085   TEL. (413) 562-9631 FAX: (413) 562-3799   |