Smith Cast Iron Boilers GB300 User Manual

GB300-IOM-4  
GB300  
NATURAL OR PROPANE GAS BOILER  
INSTALLATION & OPERATING MANUAL  
Designed and tested according to A.S.M.E. Boiler and Pressure Vessel Code, Section  
IV for a maximum allowable working pressure of 80 psi US, 50 psi Canada water,  
15 psi steam.  
CAUTION: Do not use automotive anti-freeze in the boiler waterways. If the use of  
antifreeze is necessary an anti-freeze specifically formulated for hydronic heating  
systems must be used!  
Water treatment is not recommended. This boiler uses gaskets made from ethylene  
propylene, EPT, to seal the section ports. Consult a water treatment professional before  
adding any chemicals to the boiler water to ensure that they are compatible with the  
gaskets. Failure to comply with this caution can result in failure of the gaskets voiding  
the warranty.  
WARNING: If the information in this manual is not followed exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of  
this or any other appliance.  
WHAT TO DO IFYOU SMELL GAS:  
• Do not try to light any appliance.  
• Do not touch any electrical switch. Do not use any phone in your building.  
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's  
instructions.  
• If you cannot reach your gas supplier, call the fire department.  
A qualified installer, service agency or the gas supplier, must perform installation  
and service.  
INSTALLER READ THESE INSTRUCTIONS CAREFULLY.  
THEY WILL SAVEYOU VALUABLE TIME WHEN ASSEMBLING THE BOILER.  
THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER.  
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  
Page 3  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
WARNING: Never install a GB300(S,W) boiler on  
top of combustible flooring! Failure to comply  
with this warning may result in a fire causing  
extensive property damage, severe personal  
BOILER RATINGS & CAPACITIES  
Before undertaking the installation of the GB300(S,W)  
boiler check the boiler rating plate to ensure that the boiler  
has been sized properly for the job. The rating label has  
been packed with the controls.The “Net I=B=R Ratings”  
injury or death!  
specify the equivalent amount of direct cast iron radiation  
4. DO NOT install this boiler in a location that would  
that the boiler can supply under normal conditions. Also  
subject any of the gas ignition components to direct  
ensure that the boiler has been set up for the type of gas  
contact with water or excessive moisture during operation  
available at the installation site. Other important  
or servicing. A full concrete foundation is recommended  
considerations are the availability of an adequate  
to protect the boiler from moisture and debris, Figure 1.  
electrical supply, fresh air for combustion and a suitable  
chimney or vent system.  
NOTE: The boiler must be assembled on a level, non-  
combustible surface. If the floor is not level a pad  
must be poured to provide a level surface. If a  
concrete block base is used level it using non-  
combustible shims or grout.  
BOILER LOCATION  
1. Locate the boiler in an area that provides good  
access to the unit. Servicing may require the removal of  
jacket panels. Allow a minimum clearance of 2 ft, 0.61 m  
between adjacent construction and the boiler sides and  
5. DO NOT place this boiler in a location that would  
draft hood. A minimum clearance of 4 ft, 1.22 m must be  
restrict the introduction of combustion air into the boiler.  
maintained between the front of the boiler and adjacent  
construction. Accessibility clearances should take  
WARNING: Never store combustible materials,  
precedence over fire protection clearances, or use which  
gasoline or any product containing flammable  
ever is greater.  
vapors or liquids in the vicinity of the boiler.  
Failure to comply with this warning can result in  
2. An optimum site will be level, central to the piping  
an explosion or fire causing extensive property  
system, close to a chimney and have adequate fresh air  
damage, severe personal injury or death!  
for combustion.  
3. Ensure that the floor is structurally sound and will  
support the weight of the boiler. Never install a  
GB300(S,W) on a concrete floor that contains wires,  
cables, water pipes or hoses. This boiler is designed for  
non combustible floors only! Never install this boiler on  
combustible materials or carpeting even if a non-  
combustible foundation material is placed over them!  
Figure 1  
Concrete Block Base Construction  
Page 4  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Each opening must have a minimum free area of  
COMBUSTION AIR & VENTILATION  
1 in2/1000 Btu/hr, 2200 mm2/kW based on the total  
input rating of ALL gas utilization equipment in the  
confined area. Each opening must be no less than  
100 in2, 64,516 mm2 in size.The upper opening must be  
within 12 in, 300 mm of, but not less than 3 in, 80 mm  
from, the top of the enclosure.The bottom opening must  
be within 12 in, 300 mm of, but not less than 3 in, 80 mm  
from, the bottom of the enclosure.  
WARNING: This boiler must be supplied with  
combustion air in accordance with Section 5.3,  
Air for Combustion & Ventilation, of the latest  
revision of the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and all applicable local building  
codes. Canadian installations must comply with  
CAN/CGA B149.1 or .2 Installation Code. Failure  
to provide adequate combustion air for this boiler  
can result in excessive levels of carbon  
monoxide which can result in severe personal  
injury or death!  
All Air From Outside The Building  
When installed in a confined space two permanent  
openings communicating directly with, or by ducts to,  
the outdoors or spaces that freely communicate with the  
outdoors must be present. The upper opening must be  
within 12 in, 300 mm of, but not less than 3 in, 80 mm  
from, the top of the enclosure.The bottom opening must  
be within 12 in, 300 mm of, but not less than 3 in, 80 mm  
from, the bottom of the enclosure.  
WARNING: Never operate a GB300 in an  
environment subjected to a negative pressure  
unless it is DirectVented. Failure to comply with  
this warning can result in excessive levels of  
carbon monoxide causing severe personal injury  
or death!  
Where directly communicating with the outdoors  
or communicating with the outdoors through vertical  
ducts, each opening shall have a minimum free area  
of 1 in2/4000 Btu/hr, 550 mm2/kW of the total input  
rating of all of the equipment in the enclosure.  
To operate properly and safely this boiler requires a  
continuous supply of air for combustion. Oxygen is used  
by the boiler burners to burn the gas. NEVER store  
objects on or around the boiler. In addition, air is also  
used to assist in the safe disposal of the products of  
combustion. This air is known as dilution air and mixes  
with the products of combustion to assist in their exit  
through the flue pipe and chimney. An adequate supply  
of air must be available to replace the air used by these  
processes.  
Where communicating with the outdoors through  
horizontal ducts, each opening shall have a minimum  
free area of 1 in2/2000 Btu/hr, 1100 mm2/kW of the  
total input rating of all of the equipment in the enclosure.  
When ducts are used, they must have the same cross-  
sectional area as the free area of the opening to which  
they connect.  
Older buildings often have enough natural infiltration to  
provide an adequate amount of combustion air provided  
that the demand for combustion air is not too great.  
When calculating the free area necessary to meet the  
make-up air requirements of the enclosure, consideration  
must be given to the blockage effects of louvers, grills  
and screens. Screens must have a minimum mesh size  
of 1/4 in, 6.4 mm. If the free area through a louver or grill  
is not known ducts should be sized per Table 1 below.  
Buildings that are relatively new or “tight” will most likely  
require the installation of a fresh air duct or other means  
of providing make-up air. Any building utilizing other gas  
burning appliances, a fireplace, wood stove or any type  
of exhaust fan must be checked for adequate combustion  
air when all of these devices are in operation at one time.  
Sizing of an outside air duct must be done to meet the  
requirements of all such devices.  
Table 1 Make-up Air Duct Sizing  
Required Cross Sectional Duct Area  
Input 1/4 in, 6.4 mm  
(MBH) Wire Screen  
Metal  
Louvers  
Wooden  
Louvers  
All Air From Inside The Building  
If the boiler is to be located in a confined space  
minimum clearances of 2 ft, 0.61 m must be maintained  
between the boiler and any adjacent construction. When  
installed in a confined space two permanent openings  
communicating with an additional room(s) are required.  
The combined volume of these spaces must have  
sufficient volume to meet the criteria for an unconfined  
space. The total air requirements of all gas utilization  
equipment, fireplaces, wood stoves or any type of  
exhaust fan must be considered when making this  
determination.  
in2  
400 100  
600 150  
800 200  
1000 250  
1200 300  
1400 350  
1600 400  
1800 450  
2000 500  
cm2  
645  
968  
1290  
1613  
1935  
2258  
2581  
2903  
3226  
in2  
cm2  
858  
1290  
1723  
in2  
cm2  
133  
200  
267  
333  
400  
467  
533  
600  
667  
400  
600  
800  
2581  
3871  
5161  
6452  
7742  
9032  
2148 1000  
2581 1200  
3013 1400  
3439 1600 10,323  
3871 1800 11,613  
4303 2000 12,904  
Page 5  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
When more than one appliance is connected to the same  
chimney flue the flue must be large enough to safely  
CHIMNEY & VENT PIPE CONNECTIONS  
vent the combined output of all the appliances.  
WARNING: The vent installation must be in  
accordance with Part 7,Venting of Equipment, of  
the National Fuel Gas Code, ANSI Z223.1/NFPA54-  
latest revision or applicable provisions of the  
local building codes. Canadian installa-tions  
must comply with CAN /CGA B149.1 or .2  
Installation Code. Improper venting of this boiler  
can result in excessive levels of carbon  
monoxide, which can result in severe personal  
injury or death!  
WARNING: If an appliance using any type of a  
mechanical draft system operating under  
positive pressure is connected to a chimney flue,  
never connect any other appliances to this flue.  
Doing so can result in the accumulation of  
carbon monoxide which can cause severe  
personal injury or death!  
VENT CONNECTIONS  
Chimney Inspection & Sizing  
Always use a type B or single wall galvanized metal vent  
pipe the same diameter as the draft hood flue collar. Use  
the shortest, straightest vent system possible for the  
installation. If horizontal runs exceed 6 feet they must  
be supported at maximum 6 foot intervals with overhead  
hangers. The vent system should be sloped up towards  
the chimney at a minimum rate of 1/4 inch/foot and  
terminate flush with the inside of the chimney flue.  
Fasten each connection with at least 3 corrosion  
resistant sheet metal screws.  
If this boiler will be connected to a masonry chimney, a  
thorough inspection of the chimney must be performed.  
Ensure that the chimney is clean, properly constructed  
and properly sized.Table 2 lists the equivalent breeching  
and flue sizes required for the GB300 boilers.  
Table 2 Vent Outlet, Equivalent Breeching  
& Chimney Size  
Equivalent Breeching  
Vent Outlets  
& Chimney size  
Boiler  
Model  
Diameter  
inches  
# of outlets/dia. in inches  
WARNING: Never modify or alter any part of the  
boiler’s draft hood.This includes the removal or  
alteration of any baffles. Never install a vent pipe  
of a diameter different than that of the boiler  
draft hood flue collar. Failure to comply with this  
warning can result in severe personal injury or  
death.  
mm  
254  
305  
305  
356  
356  
356  
381  
381  
381  
406  
432  
432  
432  
432  
432  
GB300-5  
GB300-6  
GB300-7  
GB300-8  
GB300-9  
GB300-10  
GB300-11  
GB300-12  
GB300-13  
GB300-14  
GB300-15  
GB300-16  
GB300-17  
GB300-18  
GB300-19  
1@10  
1@12  
10  
12  
12  
14  
14  
14  
15  
15  
15  
16  
17  
17  
17  
17  
17  
1@12  
2@10  
2@10  
2@10  
2@12  
Always provide a minimum clearance of 6 inches between  
type C vent pipe and any combustible materials. Type  
B1 vent may be used, clearance between it and any  
combustible material must be as listed.  
2@12  
2@12  
1@12, 2@10  
4@10  
4@10  
WARNING: Failure to maintain minimum  
clearances between vent connectors and any  
combustible material can result in a fire causing  
extensive property damage, severe personal  
injury or death!  
4@10  
4@10  
4@10  
NOTE: These sizes are based on a 20 foot chimney height.  
Page 6  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
c. Where it is practical, close all building doors and  
COMMON VENT SYSTEMS  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system.  
If an existing boiler is removed from a common venting  
system, the common venting system may then be too  
large for the proper venting of the remaining appliances  
connected to it. At the time of removal of an existing  
boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation.  
Turn on any exhaust fans, such as range hoods and  
bathroom exhaust, so they will operate at maximum  
speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
Au moment du retrait d'une chaudière existante, les  
mesures suivantes doivent être prises pour chaque  
appareil toujours raccordé au système d'évacuation  
commun et qui fonctionne alors que d'autres appareils  
toujours raccordés au système d'évacuation ne fonction-  
nent pas: système d'évacuation.  
Dans la mesure du possible, fermer toutes les portes  
et les fenêtres du bâtiment et toutes les portes entre  
l'espace où les appareils toujours raccordés du  
système d'évacuation sont installés et les autres  
espaces du bâtiment. Mettre en marche les  
sécheuses, tous les appareils non raccordés au  
système d'évacuation commun et tous les  
ventilateurs d'extraction comme les hottes de  
cuisinère et les ventilateurs des salles de bain.  
S'assurer que ces ventilateurs fonctionnent à la  
vitesse maximale. Ne pas faire fonctionner les  
ventilateurs d'été. Fermer les registres des  
cheminées.  
a. Seal any unused openings in the common venting  
system.  
Sceller toutes les ouvertures non utilisées du  
système d'évacuation.  
b. Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe condition.  
d. Place in operation the appliance being inspected.  
Follow the lighting instructions.Adjust thermostat so  
appliance will operate continuously.  
Inspecter de façon visuelle le système d'évacu-ation  
pour déterminer la grosser et l'inclinaison horizontale  
qui conviennent et s'assurer que le système est  
exempt d'obstruction, d'étranglement de fruite, de  
corrosion et autres défaillances qui pourraient  
présenter des risques.  
Mettre l'appareil inspecté en marche. Suivre les  
instructions d'allumage. Régler le thermostat de  
façon que l'appareil fonctionne de façon continue.  
Page 7  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
g. Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54. When resizing any portion of the  
common venting system, the common venting  
system should be resized to approach the minimum  
size as determined using the appropriate tables in  
Part 11 in the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54.  
e. Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame  
of a match or candle, or smoke from a cigarette, cigar  
or pipe.  
Faire fonctionner le brûleur principal pendant 5 min  
ensuite, déterminer si le coupe-tirage déborde à  
l'ouverture de décharge. Utiliser la flamme d'une  
allunette ou d'une chandelle ou la fumée d'une  
cigarette, d'un cigare ou d'une pipe.  
Tout mauvais fonctionnement du systéme d'évacu-  
tion commun devrait étré corrigé de façor que l'instal-  
lation soit conforme au National Fuel Gas Code,  
ANSI  
f. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers and  
any other gas-burning appliance to their previous  
condition of use.  
Z223.1/NFPA 54 et (ou) aux codes d'installation  
CSA-B149. Si la grosseur d'une section du système  
d' évacuation doit étré modifiée, le système devrait  
étré modifié pour respecter les valeurs minimales  
des tableaux pertinents de l'appendice F du National  
Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) des  
codes d'installation CSA-B149.  
Une fois qu'il a été d éterminé, selon la métode  
indiquée ci-dessus, que chaque appareil raccordé  
au système d'évacuation est mis à l'air libre de façor  
adéquate. Remettre les portes et les fenêtres, les  
ventilateurs, les registres de cheminées et les  
appareils au gaz à leur position originale.  
Figure 2A  
Vertical Venting Using A Metal Chimney System And Inside Air(GB300 Series)  
2 FT 0.6 m  
10 FT 3.4 m  
3 FT 0.9 m  
3 FT 0.9 m  
Page 8  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 2B  
Dual Flue Outlets And Inside Air (GB300 Series)  
2 FT 0.6 m  
10 FT 3.4 m  
3 FT 0.9 m  
5 FT 4.5 m  
Figure 2C  
Vertical Venting Using A Masonry Chimney And Inside Air (GB300 Series)  
10 FT 3.1 m  
3 FT 0.9 m  
3 FT 0.9 m  
Page 9  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 2D  
Dual Flue Outlets Using A Masonry Chimney And Inside Air (GB300 Series)  
10 FT 3.1 m  
3 FT 0.9 m  
3 FT 0.9 m  
Figure 2E  
Common Vents And Inside Air (GB300 Series)  
10 FT 3.1 m  
3 FT 0.9 m  
3 FT 0.9 m  
Page 10  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 2F  
Dual Flue Outlets With Two Boilers Using A Masonry Chimney And Inside Air (GB300 Series)  
10 FT 3.1 m  
3 FT 0.9 m  
3 FT 0.9 m  
Figure 2G  
Horizontal Venting And Inside Air (GB300)  
BUILDING OVERHANG  
4 FT 1.2 M MAX.  
PITCH PIPE DOWN TOWARDS TERMINAL  
CAP 1/4 IN. PER FOOT 20MM/M OF RUN TO  
ALLOW FOR CONDENSATE DRAINAGE  
3 FT 0.9 m  
3 FT 0.9 m  
1.5 FT 0.5m MINIMUM  
DISTANCE FROM  
EXHAUST TO MAXIMUM  
SNOW LINE.  
Page 11  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
A box with a number from 63265 to 63272, Burner Base  
Panels Less Sides, contains the burner base front and  
rear panels and the burner base baffle, Figure 4.  
BOILER ASSEMBLY  
Locate the boiler installation site based on the guidelines  
set forth in the previous pages. A full concrete block  
foundation is recommended to protect the boiler from  
moisture and debris.Use solid blocks to support the boiler  
and hollow blocks for the rest, Figure 1. Align the hollow  
blocks so air can flow through them.  
Figure 4  
Burner Base Box 63265 to 63272  
WARNING: Never install a GB300(S,W) boiler on  
top of combustible flooring! Failure to comply  
with this warning may result in a fire causing  
property damage, severe personal injury or  
death!  
Burner Base Assembly General Instructions  
WARNING:The burner base must be assembled  
as outlined below. Do not make substitutions for  
the hardware or materials supplied for the burner  
base assemblies. Failure to comply with this  
warning may result in property damage, severe  
personal injury or death!  
The 5/16 stainless steel nuts and bolts used to assemble  
the burner base panels are supplied in the X1 box, that  
has a number from 72700 to 72707 on it, Figure 5.  
Use care not to damage or dislodge the ceramic  
insulation board on the base panels during assembly.  
Check the contents of the burner base cartons against  
the enclosed packing list to ensure that all of the required  
parts are present.If they are not, contact your Smith Cast  
Iron Boiler distributor or contact the Smith Customer  
Service Department.  
WARNING: If any of the burner base insulation  
panels are broken or damaged they must be  
replaced with factory supplied panels. Failure to  
comply with this warning may result in property  
damage, severe personal injury or death!  
The burner base panels are factory insulated to simplify  
field assembly of the burner base.  
Figure 5  
X1 Box 72700 to 72707  
Box 63273, Burner Base Side Panels & Brackets,  
contains the left & right burner base side panels, manifold  
brackets and the jacket brackets, Figure 3.  
Figure 3  
Burner Base Box 63273  
Page 12  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Burner Base Assembly 5 through 12 Sections  
Figure 8 Burner Base Rear Panel Detail, 5 - 12 Sect  
Loosely attach the base baffle to the side panels using 4  
5/16 stainless steel nuts. Install the burner base front,  
side and rear panels as shown in Figures 6, 7, 8 and  
9A.  
Use a spirit level to ensure that the burner base panels  
are plumb before tightening the stainless steel nuts and  
bolts.  
The factory installed refractory retention bracket(s) must  
be centered on each piece of refractory board Figure  
9B. If the bracket is not centered reposition bracket.  
There is (1) bracket for each section of refractory.  
Figure 6  
Burner Base Side Panels, 5 - 12  
Figure 9A  
Burner Base Rear Panel, 5 - 12 Sect  
Figure 7  
Burner Base Front Panel, 5 - 12 Sect  
Figure 9B  
Refractory Retension Bracket  
Page 13  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Burner Base Assembly 13 through 21 Sections  
Box 72694, X7 Splice Channels, contains the burner  
base front, intermediate and rear channels and  
additional 5/16" nuts and bolts, Figure 10.  
With the burner base intermediate channel and baffles  
level, attach the front and rear channels to the  
intermediate channel. Bolt the burner base side panels  
to the base baffles, Figure 12.  
Figure 10  
X7 Box 72694  
Figure 12  
Burner Base Baffle Front and Rear  
Splice Channel Assembly  
13 to 21 Sections  
The base baffles must be attached to the intermediate  
base channel before the side, front and rear panels are  
assembled, Figure 11.  
Figure 11  
Burner Base Baffle and Intermediate  
Splice Channel Assembly  
13 to 21 Sections  
Intermediate  
Base Baffle  
Splice Channel  
Page 14  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Bolt the front and rear base panels in place, Figure 13.  
Figure 13B  
Center the factory installed refractory retention brackets  
on the rear base panel so that the bracket is in the middle  
of each refractory board Figure 13B.  
Figure 13A  
Burner Base, Side Front and Rear  
13 to 21 Sections Panel Assembly  
Figure 14A  
Base Rear Channel Bolt Holes  
Figure 14B  
Base Rear Channel  
NOTE: Do not install the two lower bolts in the base  
rear panel,Figure 14A. These holes are used to attach  
the base rear channel on 6 -12 section rear panels  
and 13-21, Figure 14B.  
Page 15  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
NOTE:The base front panels bolt to the inside of the  
front base splice channel, Figure 15.  
Figure 18  
Manifold Attachments  
Figures 15  
Base Front Panel Detail  
Locate the Burner Box. It is marked with a number from  
72724 to 72731. Install three burner tubes in the base,  
one on each end and one in the middle. Slide the closed  
end of the burner tube through the slot in the burner  
base rear panel. The notch in the burner must engage  
the burner base rear panel, Figure 19.  
Use a spirit level to plumb the front and rear panels  
before tightening the nuts and bolts, Figure 16.  
Temporarily attach the manifold brackets and manifold,  
Figures 17 and 18.  
Figure 19  
Burner Tube Installation  
Figure 16  
Plumbing Base  
Notch  
Notch  
Engaged  
Figure 17  
Manifold Bracket Attachment  
Adjust the manifold and base so the burner tube orifice  
bracket is approximately in the middle of the orifice on  
all three burners, Figure 20.  
Figure 20  
Burner Tube Adjustment  
Page 16  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Bolt the insulation splice panel bracket to the front base  
Figure 22B  
Burner Base Splice Insulation Boards  
channel, Figure 21. Install the two insulation boards in  
the spaces between the two front and two rear burner  
base panels. Firmly but carefully press the insulation  
boards in place and insert the nails through the top and  
bottom holes, Figure 22A&B.  
Orientate and install splice refractory retainer.Center the  
retainer over the splice refractory and mating base  
panels.The retainer should fit snuggly with the flat edge  
on the outside of the base and the angled edge mating  
flush to the refractory. Once insulation boards are  
installed, slide the retention bracket over the top of the  
base splice as shown in Figures 22C and 22D.Tighten  
all bolts in base.  
Figure 21  
Burner Base Splice Panel Bracket  
Figure 22C  
Figure 22D  
Figure 22A  
Burner Base Splice Insulation Boards  
NOTE: Check all of the bolts in the base to ensure  
they are tight before removing the burner tubes and  
manifold.  
Page 17  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Ceramic Blanket Installation  
Figure 25  
Ceramic Blanket Placement  
Before installing the cast iron sections a ceramic blanket  
gasket must be installed on the burner base. Locate the  
roll of ceramic blanket and can of spray adhesive supplied  
in the X1 box. Spray two heavy coats of adhesive on the  
top of the burner base waiting for the adhesive to tack  
up between coats, Figure 23.  
Figure 23  
Ceramic Blanket Adhesive Application  
Cast Iron Section Assembly  
WARNING:Never stand the cast iron sections up  
without adequate support. They may fall over  
resulting in property damage or severe personal  
injury!  
Clean and inspect each section before assembly. Use a  
wire brush and a clean rag to remove rust and debris  
from the rope seal grooves and seal ports.  
When the second coat of adhesive is tacky place a  
strip of ceramic blanket along each side of the base,  
Figure 24.  
CAUTION: Never use any petroleum-based cleaners  
to clean the cast iron sections. Residue from the  
cleaner will result in the failure of the hydronic seals!  
Figure 24  
Ceramic Blanket Placement  
Using a tape measure, mark the midpoint of the burner  
base on the front and rear panels, Figures 26A and  
26B.  
Figure 26A  
Marking Burner Base Front Midpoint  
Lay strips of ceramic blanket along the front and back of  
the base making sure to overlap the ends as shown in  
Figure 25.  
WARNING: The ceramic blanket must be  
overlapped as shown in Figure 25 to prevent the  
escape of flue gases. Failure to properly seal the  
cast iron sections to the boiler base can result  
in excessive levels of carbon monoxide which  
can result in severe personal injury or death!  
-
Page 18  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 26B  
Marking Burner Base Rear Midpoint  
Figure 28  
Figure 29  
Figure 30  
Ceramic Rope Application  
Trimming Ceramic Rope  
Casting w/ Ceramic Rope  
Apply two coats of the spray adhesive supplied with the  
boiler to the rope seal grooves, Figure 27.Allow time for  
the first coat to become tacky before applying the second  
coat.  
CAUTION: Do not get any of the spray adhesive in  
the seal ports or premature failure of the seals may  
occur voiding the warranty!  
Figure 27  
Ceramic Rope Adhesive Application  
When the second coat is tacky lay the rope seal into the  
three rope groves and press in place. Trim the rope off  
flush with the edge of the cast iron section. The rope  
seal is to be applied only to one side of each cast iron  
section, Figures 28, 29 and 30.  
Page 19  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
To ensure that the assembled sections will be centered  
on the burner base the cast iron sections should be  
assembled from the midpoint of the burner base outward.  
Figure 33  
Figure 34  
Figure 35  
Front View - Odd Numbered Models  
Rear View - Odd Numbered Models  
Section Placement on Burner Base  
On boilers having an even number of sections the first  
intermediate section should be placed so it’s side surface  
lines up with the midpoint marked on the burner base  
front and rear panels, Figures 31 and 32.  
For boilers having an odd number of sections, the  
centerline of the first intermediate section should line up  
directly with the midpoint marks on the burner base front  
and rear panels, Figures 33 and 34.  
Refer to Table 3 for the location of the intermediate  
sections with steam riser tappings, the flue collector  
brackets and the front jacket channel bracket. With the  
rope seal in place set the first section on the base making  
sure that the section is supported and will not fall over.  
The large top port should be above the front of the burner  
base, Figure 35.Set the hydronic seals from the X1 Box  
in the port openings before carefully bringing the next  
section along side of it, Figures 36 and 37.  
Figure 31  
Front View - Even Numbered Models  
Figure 32  
Rear View - Even Numbered Models  
CAUTION: Do not use adhesives or sealants on the  
hydronic gaskets. The application of adhesives or  
sealants may result in the failure of the hydronic  
seals voiding the warranty!  
Page 20  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 36  
Lower Port Seal Placement  
Install the draw rods, nuts and washer and slightly  
tighten the nuts. Only one washer is to be placed on  
each draw rod, Figure 38, to torque sections together.  
Figure 38  
Draw Rod Installation  
Figure 37  
Upper Port Seal Placement  
Table 3  
Steam Riser, Flue Collector Bracket & Jacket Splice Channel Bracket Locations  
Section Numbered from Left to Right  
Boiler  
Model  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
LOCATION OF ITEM  
- 3" Steam Riser Section Location  
FCB - Flue Collector Bracket Section Location  
14  
15  
16  
17  
18  
19  
20  
21  
GB300-5 FCB  
GB300-6 FCB  
GB300-7 FCB  
GB300-8 FCB  
GB300-9 FCB  
GB300-10 FCB  
GB300-11 FCB  
GB300-12 FCB  
GB300-13 FCB  
GB300-14 FCB  
GB300-15 FCB  
GB300-16 FCB  
GB300-17 FCB  
GB300-18 FCB  
GB300-19 FCB  
GB300-20 FCB  
GB300-21 FCB  
4P  
5P  
FCB  
FCB  
6P  
7P  
FCB  
FCB  
JSB - Jacket Splice Channel Bracket Section Location  
#P - Pilot Burner Tube Location  
8P  
9P  
FCB  
FCB  
19P  
# Represents burner position from LH side of boiler  
10P  
11P  
FCB  
20P  
FCB  
FCB &  
JSB  
FCB &  
JSB  
6P  
7P  
7P  
FCB  
FCB  
26P  
FCB &  
JSB  
FCB &  
JSB  
22P  
23P  
FCB  
8P  
8P  
9P  
9P  
FCB  
31P  
FCB &  
JSB  
FCB &  
JSB  
25P  
FCB  
FCB  
FCB &  
JSB  
FCB &  
JSB  
28P  
29P  
FCB  
10P  
10P  
FCB  
FCB &  
JSB  
FCB  
Page 21  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Make sure that the sections are square with the burner  
base. Align the bottom front edge of the sections so  
they’re flush with the face of the burner base front panel,  
Figure 39. Lift the next section into place being careful  
not to damage the ceramic blanket or hydronic seals and  
install the draw rods, washer and nuts.  
Figure 40  
Flue Collector Box 63203 to 63210  
Use a spirit level to ensure that the first two sections are  
plumb, Figure 39.Once plumb, open the Flue Collector  
Box. The box will have a number from 63203 to 63210  
on it, Figure 40.Remove the flue baffles and install them  
as shown in Figure 41. The flue baffles must be  
inserted so they’re as high in the openings as  
possible. Once all the flue baffles are installed, evenly  
torque each washer backed draw rod nut to 30 ft lbs,  
42 Nm Figure 42.  
WARNING:The flue baffles must be installed as  
shown in Figures 40 and 41.The flue baffles must  
not be changed or altered in any way. Failure to  
comply with this warning can result in excessive  
levels of carbon monoxide which can result in  
severe personal injury or death!  
Figure 41  
Flue Baffle Placement  
Repeat this process for the remaining sections. Once  
the draw rods have been torqued install the four “J” bolts,  
washer and nuts from the X1 Box that fasten the heat  
exchanger to the burner base, Figure 43.  
Figure 39  
Confirming Sections Are Plumb  
Figure 42  
Draw RodTorquing - 30 ft/lbs, 42 Nm  
Page 22  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 43  
“J” Bolt Installation  
Figure 45  
Top Jacket Splice Panel Bracket  
CAST IRON PRESSURE TEST  
NOTE: Before filling the sections with water  
temporarily set the flue collector(s) on top of the  
sections to locate the flue collector brackets, Figure  
44. On 13 to 21 section models attach the top jacket  
splice panel bracket, Figure 45. Also mark the  
intermediate casting that the flue collectors rest on.  
Install a valve in the top and bottom tapping of the left  
end section to vent any trapped air and allow boiler  
draining after pressure test completion.Connect a water  
pressure gage sized for the required test pressure to one  
of the end castings. Plug all the other tapped openings.  
Fill the cast iron sections with water leaving the top valve  
open until all of the air has been bled from the sections.  
Figure 44  
Flue Collector Bracket Installation  
Page 23  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
NOTE: All assembled boiler sections shall pass the  
hydrostatic tests prescribed in Section IV of the  
ASME Boiler and Pressure Vessel Code.  
WARNING: The ceramic blanket must be  
overlapped as shown in Figure 47A & B to  
prevent the escape of flue gases. Failure to  
properly seal the flue collector to the boiler  
sections can result in excessive levels of carbon  
monoxide which can result in severe personal  
injury or death!  
CAUTION: Do not connect any boiler controls during  
the pressure test or they will be damaged!  
Completed boiler blocks must be tested as follows:  
Figure 47A  
Ceramic Blanket Placement 5-12 Sect.  
Steam Boilers - the assembled boiler sections shall be  
subjected to a hydrostatic test pressure of not less than  
45 psig, 315 kPa.  
Water Boilers - the assembled boiler sections shall be  
subjected to a hydrostatic test pressure of not less than  
1 1/2 times the maximum allowable working pressure.  
The hydrostatic pressure shall not exceed the required  
test pressure by more than 10 psig, 70 kPa during the  
test.  
Maintain the test pressure while carefully checking for  
leaks. If a leak is found it must be eliminated. Once the  
cast iron sections have proven to be watertight drain them  
and remove the plugs from any tappings that will be used  
in service.  
Figure 47B  
Ceramic Blanket Placement 13-21 Sect.  
FLUE COLLECTOR INSTALLATION  
A single draft hood is used on the 5 through 12 section  
boilers, two are used on the 13 to 21 section boilers.  
The Draft Hood(s) are packed in a box marked with a  
number from 63187 to 63194.  
Apply two coats of the spray adhesive to the top of the  
casings where the flue collectors will rest. When the  
second coat of adhesive is tacky place strips of ceramic  
blanket on the castings, Figures 46 and 47A & B.  
Figure 46  
Flue Collector Ceramic Blanket Placement  
Page 24  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Position the flue collector(s) on the boiler sections with  
Attach the draft hood(s) to the flue collector(s) using the  
#10 screws provided, Figure 50. On the 13 through 21  
section boilers it will be necessary to lift one draft hood/  
flue collector up to install the six screws on the two inner  
sides, Figure 51.  
the draft hood opening(s) at the rear of the boiler. The  
sides of the flue collector(s) should lie along the center  
of each end section, Figure 48. Attach the flue collector(s)  
to the flue collector mounting brackets using the #10  
sheet metal screws supplied, Figure 49.  
Figure 48  
Flue Collector Placement  
Figure 50  
Draft Hood Installation  
Figure 49  
Flue Collector Bracket Installation  
Figure 51  
Draft Hood Attachment 13 to 21 Sections  
Page 25  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Clean Out Covers  
Figures 54  
Clean Out Cover Bolt Location  
The clean out covers and mounting hardware are  
packaged in the Burner Box with a number from 72724  
to 72731 on it, Figure 52  
Figure 52  
Clean Out Cover & Hardware  
.
Place the foil-backed insulation over the studs with the  
foil against the boiler, Figure 55. Install the clean out  
cover(s) so the bent edges face out and hand tighten  
the wing nuts so the insulation is fully compressed,  
Figure 56.  
Arrange the clean out cover(s) in front of the boiler so  
the mounting stud locations can be determined. Attach  
the mounting studs to the heat exchanger as shown in  
Figures 53 and 54.  
Figure 55  
Clean Out Cover Insulation  
Figures 53  
Clean Out Cover Bolt Assembly  
Figure 56  
Clean Out Cover Installation  
Page 26  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 59  
Burner Tube w/ Pilot Bkt. and Pilot  
MANIFOLD, BURNER AND PILOT INSTALLATION  
Box 63273, Base Panel Sides, contains the manifold  
brackets. Bolt the left and right manifold brackets to the  
front burner base side panel flanges, Figures 16 and 57.  
Figure 57  
Manifold Bracket Attachment  
Figure 60  
1/4" Pilot Tube  
Place the manifold on the brackets and bolt it to the  
brackets leaving the 5/16 bolts finger tight, Figure 58.  
Figure 58  
Manifold Installations  
Insert the tubing into the brass ferule on the pilot and  
tighten it with a wrench, Figure 61. Bend tubing to run  
parallel to burner tube exiting front of boiler. Avoid tight  
radius.  
Figure 61  
Burner Tube and Pilot Assembly  
The burners are in the Burner Box that has a number  
from 72724 to 72731 on it. Locate the burner with the  
pilot mounting bracket welded to it, Figure 59.There will  
be two burners with pilot mounting brackets for 13 through  
21 section boilers.  
Attach the pilot(s) to the burner tube(s) using the allen  
head screw(s) provided, Figure 59. Remove the roll of  
1/4" aluminum tubing and cut an 36" long piece from it,  
Figure 60. Ream and clean the tubing so it’s free from  
burrs.  
Page 27  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Install the supplied 1/8" stainless steel bleed line on  
continuous pilot boilers equipped with V88A gas valves.  
The bleed line must be located in a fixed position relative  
to the pilot burner and allowing for the escaping gases  
to be readily ignited by the pilot. Use the supplied  
fasteners to connect the bleed line to the valve bleed  
orifice and to the pilot-mounting bracket on the burner  
tube. Intermittent pilot boilers must vent the V88A bleed  
orifice to atmosphere external to the building. The bleed  
line and provisions to locate the line are supplied by  
the customer. The bleed line on intermittent boilers does  
not need to be stainless. Aluminum tubing is  
recommended, but all installations must follow local  
laws and codes. The burning vent gas must not in any  
way affect the pilot flame sensor on the pilot burner.  
Follow all applicable local codes.  
Pull the tubes forward over the brass orifices in the  
manifold engaging the notch in the flattened part of the  
burners with rear panel, Figures 63 and 64.  
Table 3 has the proper location for the burner tube with  
pilot assembly(s).  
Figure 63  
Burner Tubes on Manifold  
Install the burner tubes by sliding the flattened ends  
through the slots in the rear panel, Figure 62.  
Figure 62  
Burner Tube Through Rear Base Panel  
Figure 64  
BurnerTube LockedTo Rear Base Panel  
Page 28  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
When all of the burner tubes are in place adjust the  
NOTE:Before installing the jacket, any nipples, steam  
risers or short pieces of pipe that will penetrate the  
jacket should be installed in the cast iron sections.  
Do not attach any fittings or other devices that would  
prevent the jacket panels from fitting over them.  
manifold so the burner tube orifice brackets are positioned  
midway along the cylindrical portion of the orifice, Figure  
65. Make sure all of the burner tubes are locked into  
the base rear panel as shown in Figure 64.  
Figure 65  
Burner Tube Placement on Orifice  
NOTE:There are two jacket boxes for the 5 through  
12 section models.The 13 through 21 section models  
will come with 4 jacket boxes.  
Open the Box(s) that are marked with a number from  
55177 to 55184, Jacket Less Sides, Figure 67, and  
remove the jacket rear panel(s).  
Figure 67  
Box 55177 to 55184, Jacket Less Sides  
WARNING: The burner tubes must be installed  
as described above. Make sure that the notch  
on each burner tube is locked into the rear burner  
base panel, Figure 64. Failure to properly install  
the burner tubes could result in a fire or  
explosion causing extensive property damage,  
severe personal injury or death!  
JACKET INSTALLATION  
Bolt the jacket brackets found in Box 63273 to the lower  
rear flange of the burner base side panels, Figure 66.  
Figure 66  
Rear Jacket Bracket Attachment  
Page 29  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
The jacket should be assembled using the black screws  
provided. On 5 through 12 section models slide the rear  
panel behind the draft hood flanges with the grill side on  
the floor, Figures 68, 69 & 70.On 13 to 21 section boilers  
open Box 55185, Jacket Splice Box, Figure 71. Screw  
the two rear jacket panels to the rear jacket panel splice  
panel, Figure 72, before sliding the panels behind the  
draft hoods.  
Figures 71  
Box 72694, Jacket Splice Box  
Figures 68  
Figures 69  
Figures 70  
Rear Panel Installation, 5 through 12  
Rear Panel Installation, 5 through 12  
Rear Jacket Panel Installation Detail  
Figures 72  
Rear Panel Installation, 13 through 21  
Fasten the rear jacket panel(s) to the inner draft hood  
and flue collector flanges using the holes provided,  
Figure 73.  
Figures 73  
Rear Panel Installation  
Page 30  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Remove the left and right jacket side panels from Box  
Figure 76  
Jacket Side Panel Installation  
55175, Jacket Side Panels. Remove the knockouts  
necessary to attach the water or steam piping and  
controls.  
NOTE: All jacket panel joints must be made so the  
panels are metal to metal.The insulation on the edges  
of the front, top and rear panels must be pushed  
behind the side panel flanges before fastening the  
panel together, Figure 74.  
Figure 74  
Jacket Insulation Detail  
Locate the top jacket panel(s), Figure 77.  
Figure 77  
Top Jacket Panels  
Slip the rear flange of one of the side panels between  
the rear panel and the jacket-mounting bracket, Figure  
75.  
Figure 75  
Jacket Side Panel Installation  
If the removal of knockouts is required to accommodate  
any piping they should be removed at this time. Place  
the rear top jacket panel on top of the boiler, Figure 78.  
On 13 through 21 section boilers two top jacket panels  
are required. These panels should be screwed to the  
top splice panel before being placed on the boiler,  
Figure 79. Make sure that the splice panel flanges are  
between the edge of the top panel(s) and the insulation,  
Figure 80. Attach the edges of the top jacket panel(s)  
so they are metal to metal with the top flanges on both  
side panels.  
Fasten the side and rear panels together using the bottom  
three holes, Figure 76. Align the bottom screw hole with  
the hole in the jacket bracket and fasten them to the  
bracket. Attach the opposite side panel the same way.  
Page 31  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 78  
Rear Top Jacket Panel, 5 through 12  
Figure 81  
FrontTop Jacket Panel, 13 through 21  
Figure 79  
RearTop Jacket Panel, 13 through 21  
Bend the top panel(s) down along the perforation and  
attach the front portion of the top to the flange edges  
of each side panel, Figure 82.  
Figure 82  
Front Top Jacket Panel Detail  
Install the front jacket top panel(s), Figures 80 and 81.  
Figures 80 FrontTop Jacket Panel, 5 through 12  
Page 32  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
On 13-21 section models a splice kit is required  
Figure 84  
Upper Front Splice Panel  
to assemble the front jacket panels. The splice kit is  
shown in Figure 71. The splice panel sits on the splice  
panel brackets shown in Figure 45 and Figure 83.  
Figure 84 shows the upper front splice panel in place.  
The panels sits on top of the flue collector and is  
inserted in the bracket mount. The bottom front splice  
panel mounts to the lower bracket and is fastened to  
the top splice panel using two jacket screws provided  
as shown in Figure 85.  
Figure 83  
Splice Panel Brackets  
Figure 85  
Bottom Front Splice Panel  
Page 33  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Install the front access panels as shown in Figure 86  
5-12 sect and Figure 87 13-21 section using the  
supplied screws.  
Attach the front grill side panels to the grill top panels as  
shown in Figure 88. There are two grill assemblies and  
a splice grill for 13-21 section models. Splice grill  
assembles exactly like the full size grill panels Figure  
89 The splice grill must be inserted in the middle of the  
boiler in line with the jacket splice panel. Install grill(s)  
over manifold and burners, Figure 90.  
Figure 86  
Front Access Panel 5 - 12 Sect  
Figure 88  
Grill Assembly  
Figure 89  
Splice Grill Assembly  
Figure 87  
Front Access Panel 13 - 21 Sect  
Figure 90  
Installed Grill  
Page 34  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Gas Train Assemblies  
All threaded gas train connections must be made using  
Pilot Assembly  
a pipe compound that is resistant to the actions of  
liquefied petroleum gases. Pipe connections should be  
secure and tested for leaks. This boiler is designed to  
allow for the installation of the gas train on either the  
left or right side of the boiler. Locate the gas train in the  
most ideal location, but ensure that the train and controls  
are protected from water and other possible damage.  
Install the supplied pipe cap on the manifold end  
opposite the location of the gas train. Install the supplied  
reducer coupling to the manifold where the gas train will  
be located.  
The pilot assembly must be performed after the  
installation of the control box.  
The pilot assemblies are fed gas through 1/4" aluminum  
tubing. The tubing is supplied in a bulk roll and must be  
cut to fit in the field. Use an appropriate tubing cutter to  
cut the rolls to length. Debur and clean all cuts to ensure  
a clean line without blockage or interference. Use a  
tubing bender to bend the tube and the supplied tubing  
clamps to fasten it to the boiler jacket. Figure 92 and  
Figure 93 show a recommended layout of the pilot  
tubing. The gas train instruction manual shows the  
component layout and how the fittings are arranged on  
the purchased gas train page.  
Refer to the Gas Train Assembly Instructions for a  
detailed diagram of how the fittings should be arranged  
and assembled. The instructions are arranged by gas  
train assemblies. Look up the purchased gas train and  
confirm all parts for that train are accounted for.  
Assemble the train as depicted in the instructions. Refer  
to the GAS SUPPLY PIPING section of this manual to  
make the final connection to the main gas supply.  
Figure 92  
Single Pilot Tubing Run 5 - 12 Sect  
For installations in Canada a manual shutoff valve must  
be installed between the manifold and the first gas valve.  
On gas trains with two valves the V88A valve must be  
installed first (closest to supply), followed by the regulating  
valve closest to manifold, Figure 91. Refer to diagrams  
in gas train assembly book.  
Figure 91  
Gas Train,Valve Orientation  
Figure 93  
Double Pilot Tubing Run 13 - 21 Sect  
For installations in Canada a manual shutoff valve must  
be installed between the pilots.  
The pilot tubing runs must be done in a neat, workman  
like manner.Use the provided tubing clamps and screws  
to attach the pilot tubing to the jacket as required.  
Page 35  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 94  
Water & Steam Control Tapings  
HEATING SYSTEM PIPING  
3
NOTE: The boiler jacket must be installed before  
connecting the heating system piping and controls.  
6
5
4
1
All heating system piping must be installed by a qualified  
technician in accordance with the latest revision of the  
ANSI/ASME Boiler and Pressure Vessel Code, Section  
IV, and ANSI/ASME CSD-1, Standard for Controls and  
Safety Devices for Automatically Fired Boilers. All  
applicable local codes and ordinances must also be  
followed. A minimum clearance of 1" must be maintained  
between heating system pipes and all combustible  
construction.  
7
6
8
8
8
2
Tapping  
Size  
4"  
Water  
Supply & Optional  
Tankless Heater  
Steam  
Optional Safty Valve  
Location &  
CAUTION: Improper piping of this boiler can cause  
flooding and extensive property damage!  
1
Skim Tapping  
Return & Boiler  
Drain/Blowoff  
Steam Relief Valve &  
Optional Control  
Tree Location  
N/A  
2
3
3"  
Return & Boiler  
Drain/Blowoff  
Water Relief Valve  
Ensure that the boiler is level from front to back and from  
side to side. Use metal shims to level the boiler. NEVER  
use wood, plastic or other combustible materials as  
shims.  
1-1/2"  
4
5
6
3/4"  
3/4"  
3/4"  
Temp./Pressure Gauge2  
High Limit2  
Operating Control2  
Gauge Glass3  
Control Tree  
If a boiler is installed above any radiation elements it  
must be fitted with a low water cutoff device.  
(see Figure 99)  
Optional Probe  
LWCO3  
Optional Float  
LWCO’s3  
7
8
3/4"  
1"  
Optional Probe  
WATER BOILER PIPING CONNECTIONS  
LWCO  
Optional Float  
LWCO’s  
The supply and return connections should be sized to  
suit the system, see Figure 94 & Table 4. Do not pipe  
the supply from the bottom port or the return to the top  
port, the boiler will not work properly.  
Notes:  
1. The left end section contains the same tappings as the right end  
section.  
2. These controls must be located on the supply piping side of the  
boiler.  
3. These controls must be located on the steam equalizer piping  
side of the boiler.  
Page 36  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Table 4  
Supply & Return Pipe Sizing  
Piping For Use With Cooling Units  
The boiler, when used in connection with a refrigeration  
system, must be installed so the chilled medium is piped  
in parallel with the boiler. Appropriate valves must be  
used to prevent the chilled water from entering the boiler.  
Boiler Model  
5 - 10 section  
11 - 21 section  
Supply Size (in) Return Size (in)  
3"  
4"  
3"  
3"  
Install the Pressure Relief Valve in the 1 1/2 NPT  
opening in the top of the end section opposite the gas  
controls. Pipe the discharge of the Pressure Relief Valve  
to prevent scalding in the event of a discharge, see  
Figure 93. The discharge piping must be sized the same  
as the Pressure Relief Valve outlet.  
When a boiler is connected to a heating coil that may  
be exposed to refrigerated air from an air handling  
device, the piping system must be equipped with flow-  
control valves or some other automatic means of  
preventing gravity circulation of the boiler water during  
the cooling cycle.  
CAUTION: If the relief valve must be installed on the  
same end as the gas controls, provisions to protect  
the controls from water in the event of a discharge  
must be made.  
Steam Boiler Piping Connections  
Table 3, contains the steam riser location schedule.Riser,  
equalizer and header pipe sizes are located in Table 5.  
A typical single boiler piping arrangement is shown in  
Figure 95. Figures 97 & 97A contain typical piping  
diagrams for steam boilers in battery. The steam piping  
should be pitched so the condensate flows in the direction  
of steam travel.  
Locate the Theraltemeter, Low Water Cutoff Device, Hi  
Limit Control and Operating Control per Figures 94 & 95.  
Optional controls must be installed in accordance with the  
control manufacturers instructions and Figure 94.  
Figure 95  
Single Water Boiler Piping  
ASME  
Safety  
Valve  
Hi Limit  
Control  
Temperature  
Pressure Gage  
Operating  
Control  
Page 37  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 97  
Water Boilers in Battery  
Preferred Location  
Of Circulating Pump  
ASME  
Safety  
Valve  
Expansion Tank  
External  
Low-water  
Cutoff  
Expansion Tank  
ASME  
Safety  
Valve  
Pressure  
Reducing  
Valve  
Maximum  
Temperature  
Limit Control  
Hi Limit  
Control  
Hi Limit  
Control  
Temperature  
Pressure Gage  
Blowoff  
Valves  
Stop  
Valve  
Maximum  
Temperature  
Limit Control  
Hi Limit  
Control  
Blowoff  
Valve  
Internal  
Low-water  
Cutoff  
Temperature  
Pressure Gage  
Check Valve  
Air Vent  
Check  
Valve  
Stop  
Valve  
Alternate Arrangement  
With Diaphragm Expansion  
Tank (Required On Each  
Boiler)  
Figure 97A  
Typical Single Boiler Steam Piping  
Stop Valve  
Steam Main  
Pres.  
Controls  
ASME  
Safety  
Valve  
F & T  
Trap  
LWCO  
Steam Gage  
Gage Glass  
Stop Valve  
Check Valve  
Blowoff  
Valve  
Page 38  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 98  
Typical Steam Piping - Gravity Return for Multiple Boilers  
Stop Valve  
ASME  
Safety  
Valve  
Stop Valve  
To Return  
Header  
F & T  
Trap  
Pres.  
Controls  
ASME  
Safety  
Valve  
Steam Gage  
LWCO  
& Gage  
Glass  
Stop Valve  
Check Valve  
Water Column  
& Gage Glass  
Blowoff Valves  
Check Valve  
Stop Valve  
LWCO  
Press.  
Controls  
Steam  
Gage  
Blowoff Valves  
Figure 98A  
Typical Steam Piping - Pumped Return for Multiple Boilers  
Stop Valve  
ASME  
Safety  
Valve  
Stop Valve  
F & T Trap  
High Level  
“Spill”  
ASME  
Safety  
Valve  
To Receiver  
Tank  
LWCO  
Pump  
Control  
& Gage  
Glass  
Pres.  
Controls  
Pres.  
Controls  
Steam Gage  
Stop Valve  
To Receiver  
Tank  
F & T Trap  
High Level  
“Spill”  
Check Valve  
Pump Control  
& Gage Glass  
Blowoff Valves  
LWCO  
Solenoid Valve  
Stop Valve  
Check Valve  
Steam  
Gage  
Solenoid Valve  
Page 39  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
CAUTION:Make up water connections must be made  
to the return piping, not directly to the boiler or boiler  
damage may result.  
Table 6 should be used to ensure that the gas supply  
piping is sized properly. If more than one appliance is  
supplied by the same supply pipe, the piping must be  
sized based on the maximum possible demand. Do not  
neglect the pressure drop due to pipe fittings. Table 6  
should be used in conjunction with Table 7 to ensure  
that the supply piping has the capacity to meet the  
demand.  
Locate the boiler blow off preferably opposite the return  
piping connections. Blow off valves must be sized equal  
to, or larger than, the steam relief valve. Any discharge  
piping is to be full size to the point of discharge.  
Assemble the control tree and low water cutoff as shown  
in Figure 99. Use Figure 94 to locate the control tree  
and low water cutoff on the boiler.  
Table 6  
Gas Pipe Capacity  
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas  
at a pressure of 0.5 psig or less and a 0.3" WC pressure drop.  
Nominal  
Iron Pipe 10  
Size, (in)  
1"  
1-1/4"  
1-1/2"  
2"  
2 1/2"  
3"  
Pipe length in feet  
40 50 60  
Maximum gas volume of pipe, (ft3/hr)  
20  
30  
80 100 150  
Table 5  
Boiler Model  
GB300-5 to -9  
GB300-10 to -15 2 @ 3"  
GB300-16 to -21 3 @ 3"  
Riser, Equalizer & Header Pipe Sizes  
Risers  
Equalizer Header  
520 350 285 245 215 195 170 150 120  
1050 730 590 500 440 400 350 305 250  
1600 1100 890 760 670 610 530 460 380  
3050 2100 1650 1450 1270 1150 990 870 710  
4800 3300 2700 2300 2000 1850 1600 1400 1130  
8500 5900 4700 4100 3600 3250 2800 2500 2000  
1 @ 3"  
1-1/2"  
2"  
3"  
3"  
4"  
5"  
Figure 99  
Steam Control Tree  
Note:  
Multiply the gas volume by 0.62 for propane flow capacity in ft3/hr.  
Multiply the propane flow capacity by 2500 Btu/ft3 to determine the  
propane Btu/hr capacity for a given pipe size and length.  
STEAM  
GAUGE  
MANUAL RESET  
HIGH LIMIT  
Table 7  
Equivalent Pipe Length Chart  
PET COCK  
SYPHON  
OPERATIG  
CONTROL  
Nominal  
Type of pipe fitting  
Iron Pipe  
Size, (in)  
1"  
1-1/4"  
1-1/2"  
2"  
90 Elbow  
Tee1  
Gate Valve2 Gas Cock2  
Equivalent pipe length, (ft)  
2.6  
3.5  
4.0  
5.2  
6.2  
5.2  
6.9  
8.0  
10.3  
12.3  
0.6  
0.8  
0.9  
1.2  
1.4  
1.5  
1.9  
2.3  
3.0  
3.7  
SYPHON  
2-1/2"  
3"  
7.7  
15.3  
1.8  
4.5  
Notes: 1. For flow through branch.  
2. For flow at full open.  
GAUGE  
GLASS  
L.W.C.O.  
(OPT.)  
Figure 100 depicts the proper way to connect the boiler  
to the gas supply piping. The manual shut-off valve  
MUST be installed in the supply piping. It should be  
approximately 5 feet above the floor. Provide a sediment  
trap at the bottom of the vertical section of the gas  
supply pipe upstream of the gas controls. A ground joint  
union should be installed between the boiler gas  
controls and the supply piping. Each of these items are  
needed to ensure long life and ease of servicing.  
Always use a pipe sealant that is suitable for use with  
LP gas.  
GAS SUPPLY PIPING  
WARNING: Check the boiler rating plate to make  
sure that the boiler is for the type of gas that will  
be used. If it isn’t, do not connect the boiler to  
the gas supply. Failure to comply with this  
warning can result in extensive property damage,  
severe personal injury or death!  
CAUTION: Always use a wrench on the gas valve  
body when making gas connections to it. Never over-  
tighten the piping entering the gas valve body or gas  
valve failure may result!  
The GB300(S,W) boiler comes from the factory ready to  
be piped to the gas supply. If for any reason the boiler is  
not for the type of gas available at the installation site,  
call the nearest Smith Cast Iron Boiler distributor to  
resolve the problem.  
Page 40  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 100  
Gas Supply Piping  
ELECTRICAL WIRING  
TO GAS SUPPLY  
Electrical Power Connections  
PILOT SHUTOFF VALVE  
MANUAL  
SHUTOFF  
VALVE  
GAS PRESSURE  
TEST TAPPING  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation! Verify proper  
operation after servicing.  
PILOT FILTER  
PILOT GAS PRESSURE  
REGGULATOR  
The electrical connections to this boiler must be made  
in accordance with all applicable local codes and the  
latest revision of the National Electrical Code, ANSI/  
NFPA-70. Installation should also conform with CSA  
C22.1 Canadian Electrical Code Part I if installed in  
Canada. Install a separate 120 volt 15 amp circuit for  
the boiler. A shut-off switch should be located at the  
boiler. The boiler must be grounded in accordance with  
the authority having jurisdiction, or if none, the latest  
revision of the National Electrical Code, ANSI/NFPA-70.  
TO PILOT(S)  
GROUND  
INSTALL MANUAL  
SHUTOFF VALVE  
5FT. ABOVE FLOOR  
WHERE REQUIRED  
BY LOCAL CODES.  
JOINT  
UNION  
TO GAS  
CONTROL(S)  
SEDIMENT TRAP & DRIP LEG  
( TO EXTEND TO FLOOR )  
Line voltage field wiring of any controls or other devices  
must conform to the temperature limitation of typeT wire  
at 95°F(35°C) above room temperature. Use copper  
conductors with a minimum size of #14 awg.  
When applicable, provisions for vent, bleed and gas  
relief lines must be made in accordance with the latest  
revision of ANSI Z223.1.  
The incoming line voltage is connected to the boiler using  
the supplied junction box and transformer.All high voltage  
connections must be contained inside the junction box  
leaving only 24 volt termination exposed. The junction  
box MUST be located on the side were the boiler controls  
are located and on the jacket panel in the upper right  
hand corner (1/2" max from the top and 1/2" max from  
the front side of the jacket panel). Failure to mount the  
junction box and transformer in this area will cause wire  
harness length to not be of the proper size, resulting in  
the inability to connect the termination points and  
harnesses together. See Figure 101 Transformer  
Location.  
Safe lighting and other performance criteria were met  
with the gas manifold and control assembly provided on  
the boiler. All gas connections MUST be leak tested  
before putting the boiler into operation.  
WARNING: Never use an open flame to test for  
gas leaks. Always use an approved leak detection  
method. Failure to comply with this warning can  
cause extensive property damage, severe  
personal injury or death!  
Whenever the gas supply piping is pressure tested the  
boiler gas controls must be protected. If the test  
pressure is equal to, or less than 1/2 psig (3.5 kPa)  
isolate the boiler by closing it's manual shut off valve. If  
the test pressure is greater than, or equal to 1/2 psig  
(3.5 kPa), disconnect the boiler and its individual shut-  
off valve.  
Figure 101  
Transformer Location  
Page 41  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Use the factory supplied wiring schematic booklet to  
connect power to the boiler.The schematic booklet also  
BOILER OPERATION  
depicts how to interconnect the boiler controls, using the  
supplied wire harness.Before connecting any harnesses,  
the control panel and wire duct must be attached to the  
boiler using the supplied fasteners.There are prepunched  
holes in the jacket panel to help locate and install these  
components. Use as many fasteners as required to  
secure control panel and wire duct to front jacket panel.  
Prepunched holes are for locating purposes only and  
may not securely fasten components. Run the wire  
harnesses inside the plastic wire duct between  
termination points, see Figure 102. Instructions for  
cutting, locating and mounting the wire duct can be found  
in the electrical book. The wire harnesses' identification  
and mounting location information can also be found in  
the electrical wiring diagram book.  
WARNING: Before proceeding read and fully  
understand the instructions contained in this  
manual. Do not attempt to operate this boiler if  
it has not been installed in accordance with the  
guidelines set forth in this manual. Failure to  
comply with this warning can result in extensive  
property damage, severe personal injury or  
death!  
Water Boilers  
Fill the boiler and all of the radiation with water to the  
required system pressure.Completely purge the system  
of air and adjust the system pressure as needed.  
Steam Boilers  
Fill the boiler with water to a level 1" below the normal  
water level line of 33 1/4". Clean the newly installed  
sections as outlined below:  
Figure 102  
Wire Duct and Control Box  
CAUTION: Do NOT use any petroleum based  
cleaners to clean the boiler or the hydronic seals will  
be damaged!  
1. Pipe the skimmer tapping on the front of one of the  
end sections to a floor drain using 1 1/2" pipe.  
2. Adjust the boiler water level until water begins to  
flow out of the skim piping at a slow rate.  
3. Fire the boiler and maintain a water temperature of  
180°F to 200°F. It may be necessary to cycle the boiler.  
Thermostat Installation  
4. Adjust the water feed to prevent the build up of  
pressure within the boiler.Continue the skimming process  
until the discharge runs clear.  
If a thermostat is to be used to control the boiler always  
follow the instructions included with the thermostat.  
Proper location of the thermostat will ensure efficient  
trouble-free operation of the boiler.Mount the thermostat  
to an inside wall at a height approximately five feet above  
the floor. Avoid placing the thermostat in areas that will  
not provide an accurate measurement of the room  
temperature. Locating the thermostat behind a door, in  
an alcove, close to a source of thermal radiation or in a  
drafty area will cause poor or sporadic heating.  
5. Shut the boiler off and allow the boiler to cool to  
100°F. Remove the skim piping and plug the tapping.  
Open the blowdown valve and flush the boiler until the  
discharge runs clear.  
6. Close the blowdown valve and fill the boiler with  
water to a level 1" below the normal water level line.  
7. Check the traps and vents for proper operation.  
Page 42  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
10. Push and hold down the red button on the pilotstat.  
LIGHTING INSTRUCTIONS  
Light the pilot with a match and wait approximately one  
(1) minute before releasing the button.The button should  
pop back and the pilot(s) remain lit. For two pilot systems  
repeat this procedure for the other pilot. If a pilot will not  
stay lit after several tries, adjust pilot reg to higher  
pressure. Turn reg clockwise to increase and  
countercloskwise to decrease pressure. If pilot still fails  
to light, close the manual pilot valve and call your service  
technician or gas supplier.  
A. If this appliance is equipped with a continuous pilot  
it must be lit by hand. Follow the lighting instructions  
exactly when lighting the pilot. If this appliance is  
equipped with an intermittent pilot, the ignition control  
will automatically light the pilot. Follow the operating  
instructions and do not try to light the pilot or burner  
by hand.  
B. BEFORE LIGHTING smell all around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
11. With the pilot(s) lit, turn on all electric power to the  
appliance.  
C. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the  
control system and any gas control which has been  
under water.  
12. Open the manual main gas shut-off valve.  
13. Set the operating control so there's a call for heat.  
14. The burners should light with proper boiler operation.  
CAUTION: To prevent being burned, stand clear of  
the boiler during ignition and don't touch any hot  
metal parts.  
15. A boiler designed for use with natural gas should  
have a manifold gas pressure of 3.5" WC on High Fire  
and 0.8" WC on Low Fire for 2 stage units. On an LP  
boiler, the manifold pressure should be 10" WC on  
highfire, 2 stage firing not avaialble on LP models. To  
adjust the manifold gas pressure see the GAS  
PRESSURE ADJUST-MENT instructions in the BOILER  
CHECKING & ADJUSTMENT section.  
Continuous Pilot Systems  
1. STOP! Read the safety information above. If, at any  
time, the boiler will not operate properly, follow the  
instructions “TO TURN OFF GAS TO BOILER” and call  
your service technician or gas supplier.  
16. Test the ignition safety shutoff device. Close the  
manual pilot valve. Within three minutes the pilotstat  
should close de-energizing the main gas valve(s).  
Repeat steps 9 through 14. Disconnect the thermo-  
couple from the pilotstat, the main burners should go  
out. Extinguish the pilot and reconnect the thermo-  
couple. There should be NO gas flow to the main  
burners with the pilot out! If gas flow is detected,  
immediately turn the main manual shut-off valve off and  
have the problem corrected.  
2. Set the operating control to off or its lowest setting.  
3. Turn off all electric power to the boiler.  
4. Close the manual main and pilot gas shut-off valves.  
5. Wait five (5) minutes** to clear out any gas. Then  
smell for gas, including near the floor. If you smell gas,  
STOP! Follow “B” in the safety information above (to the  
left) on the label. If you don’t smell gas, go to the next  
step.  
Intermittent Pilot Ignition Systems  
1. STOP! Read the safety information above. If, at any  
time, the boiler will not operate properly, follow the  
instructions “TO TURN OFF GAS TO BOILER” and call  
your service technician or gas supplier.  
6. Remove the front grill(s).  
7. Connect a manometer having a minimum capacity  
of 20" WC to the outlet pressure port of the gas valve.  
Make sure that the gas supply piping has been purged  
of air and that all gas joints up to the manifold have been  
thoroughly checked for leaks.  
2. Set the operating control to off or its lowest setting.  
3. Turn off all electric power to the boiler.  
8. Locate the pilot(s).  
4. Close the manual main and pilot gas shut-off valves.  
9. Open the petcock pilot valve.  
5. Wait five (5) minutes** to clear out any gas. Then  
smell for gas, including near the floor. If you smell gas,  
STOP! Follow “B” in the safety information above (to the  
left) on the label. If you don’t smell gas, go to the next  
step.  
Page 43  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
6. Remove the front grill(s).  
To Turn Off Gas To Boiler  
1. Set the operating control to its lowest setting.  
7. Connect a manometer having a minimum capacity  
of 20" WC to the outlet pressure port of the gas valve.  
Make sure that the gas supply piping has been purged  
of air and that all gas joints up to the gas valve have  
been thoroughly checked for leaks.  
2. Turn off all electric power to the appliance if service  
is to be performed.  
3. Close the manual main and pilot gas shut-off valves.  
8. Open the petcock pilot valve.  
BOILER CHECKING & ADJUSTMENT  
PILOT ADJUSTMENT  
The pilot burner flame should envelope 3/8" to 1/2" of  
the thermocouple tip or flame-sensing probe, depending  
on the pilot type.Figure 103 depicts an intermittent pilot,  
but the adjustment dimensions for a continuous pilot  
would be the same.To adjust the pilot the following steps  
must be taken:  
9. Turn on all electric power to the boiler.  
10. Set the operating control to the desired setting.  
11. The pilot(s) should automatically light. Do not try to  
light the pilot(s) by hand!  
12. With the pilot(s) lit, open the main gas shut-off valve.  
13. The burners should light with proper boiler operation.  
1. Remove the cap next to the pilot tube fitting on the  
gas valve or on the separate pilot gas regulator where  
one is used.  
14. A boiler designed for use with natural gas should  
have a manifold gas pressure of approximately 3.5" WC  
on high fire and 0.8" WC on low fire. For an LP boiler,  
the manifold pressure should be 10" WC. To adjust the  
manifold gas pressure see the GAS PRESSURE  
ADJUSTMENT instructions in the BOILER CHECKING  
AND ADJUSTMENT section.  
2. Turn the pilot adjustment screw on the valve  
counterclockwise to increase the flame, clockwise to  
decrease it. On the separate pilot gas regulator turn the  
regulator screw clockwise to increase the flame,  
counterclockwise to decrease it.  
3. Replace the pilot adjustment screw cap.  
15. With the burners in operation, close the manual  
shutoff valve in the gas supply line. As soon as the main  
burner flames go out, open the manual shutoff valve. A  
normal ignition sequence should take place. If the  
burners fail to light the system will make two more  
ignition attempts. If the burners have not lit after the last  
ignition try, the gas valve will close and the system will  
go into lock out. DO NOT attempt to reset the system  
until the ignition system has been inspected and the  
problem resolved.  
Figure 103  
Pilot Flame Adjustment  
SCREWS  
BRASS FERULE  
1/4" TUBING  
With the burners in operation, interrupt the power to the  
control circuit by lowering the operating control.The main  
burners should go out. Reset the operating control, a  
normal ignition sequence should follow.  
Gas Pressure Adjustment  
To test the ignition safety shutoff device, close the  
manual shutoff valve in the gas supply line. Within 6  
seconds of main burner flame extinction, the main gas  
valve solenoid should close with an audible noise.  
NATURAL GAS: Optimum results are obtained when  
the boiler is operated at its full input rating, with 3.3"WC  
to 3.7" WC and 1.0" to 0.8" on low fire of manifold  
pressure.The manifold pressure should not vary outside  
this range. The gas valve pressure regulator has been  
preset at the factory. If adjustment is necessary the  
following steps must be followed:  
A sparking noise should be heard while the ignition  
module tries to light the pilot. After 1 minute the module  
should lockout and the try for ignition end. Open the  
manual shutoff valve in the gas supply line and reset the  
ignition control system. A normal ignition sequence  
should take place.  
NOTE: The Honeywell VR8404 valve is factory set  
and cannot be field adjusted  
Page 44  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
1. Attach a 20" manometer to the tap on the manifold.  
DO NOT adjust the manifold pressure by more than 5%.  
If a proper rate cannot be maintained without adjusting  
the manifold pressure beyond the 5% limit, the main  
burner orifices must be replaced. If the input rate is too  
low, go to the next lager size main burner orifices. If the  
input rate is too high, go to the next smaller size.  
2. Remove the regulator adjustment screw cap from  
the gas regulator. On systems that do not use a  
separate gas regulator, remove the adjustment screw  
cap from the gas valve body on the valve closest to the  
gas supply piping.  
CAUTION: Never increase the input to the boiler  
above that for which it is rated. Doing so can cause  
premature failure of the boiler!  
3. Rotate the regulator adjustment screw clockwise to  
increase the manifold pressure, counterclockwise to  
decrease it.  
Low Water Cutoff  
4. Replace the regulator adjustment screw cap and  
pressure tap plug.  
Ensure that the low water cutoff device(s) function  
properly. Test in accordance with the manufacturer’s  
instructions included with the device(s).  
CAUTION: Never force the regulator adjustment  
screw beyond the stop limits or damage to the  
regulator will occur!  
Thermostat Adjustment  
For a thermostat that employs an adjustable heat  
anticipator, adjust the anticipator to match the current  
measured in the thermostat circuit. An increased  
anticipator setting may be necessary if the unit cycles  
frequently. If the room temperature over-shoots the  
thermostat setting, reduce the anticipator setting.  
PROPANE GAS:A manifold pressure of 10"WC must  
be maintained for proper operation of the boiler. If the  
manifold pressure is off by more than 5% adjust it  
according to steps 1 through 4 above.  
Input Rate  
Gas appliances are rated based on sea level operation  
with no adjustment required at elevations up to 2000 feet.  
At elevations above 2000 feet, input ratings should be  
reduced by 4% for each 1000 feet above sea level.  
BOILER MAINTENANCE  
CAUTION: Servicing, inspection and adjustment  
must be done by a trained technician in accordance  
with all applicable local and national codes. Improper  
servicing or adjustment can damage the boiler!  
Check the input rate as follows:  
1. Turn off all other gas appliances that use the same  
gas meter as the boiler.  
The boiler should be cleaned and inspected once a year,  
before each heating season. Make sure that the  
burners and ignition components are free from dust,  
soot, dirt, corrosion or other deposits that would impair  
the boiler’s performance.  
2. Call your gas supplier and ask for the heating value  
of the gas.  
3. Start the boiler and let it run for 15 minutes.  
Burner Removal  
1. Close the manual shutoff valves in the gas supply  
lines and turn off electrical power to the boiler.  
4. Using the gas meter and a stop watch, clock the  
time that it takes to burn 10 cubic foot of gas and divide  
this time by 10.  
2. Remove the front grill(s).  
5. Insert the heating value and the time, in seconds,  
into the formula below.  
Input = (heating value, Btu/hr)(3600)/(time, seconds)  
3. Lift the rear of the burner up and slide it towards  
the back of the boiler. When the orifice bracket is clear  
of the orifice lower the burner and remove it by sliding  
it forward and out from the boiler.  
If the computed rate deviates by more than 5% from the  
rated input value of the unit adjust the manifold pressure  
accordingly.  
4. Inspect each burner for damage or signs of  
deterioration. Use a brush or compressed air to remove  
any debris from the burner ports.  
NOTE:The HoneywellVR8404 valve is factory set and  
can-not be field adjusted  
Page 45  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
3. The relief valve should vent water when the test lever  
is lifted. It should not weep or discharge water at normal  
system pressure. NEVER try to clean or repair the relief  
valve! If the valve fails to operate properly, replace it!  
Burner Installation  
1. DO NOT install damaged or badly corroded burners,  
replace them.  
2. Install the burners by sliding the rear of the burner  
tube into the slot located in the base rear panel. Slide  
the burner into the slot far enough so that the burner  
bracket clears the orifice on the manifold. Pull the burner  
back onto the orifice making sure that the notch in the  
crimped portion of the burners engages the rear burner  
base panel locking it into place.  
4. The aquastat high limit controls the maximum water  
temperature in the boiler. It is adjustable from 140°F  
(60°C) to 240°F (116°C). If the water temperature  
reaches the set temperature before the demand for heat  
has been met, the aquastat high limit should shut the  
boiler off. The water temperature should never exceed  
the maximum set point of 240°F (60°C). The aquastat  
high limit cannot be repaired. If it fails to function  
properly replace it.  
3. Replace the front grill(s).  
Heat Exchanger Cleaning  
5. Visually check the pilot and main burner flames to  
ensure proper operation, see Figure 103 & 104.  
The burners should be removed to protect them from  
falling rust and scale. Follow the BURNER REMOVAL  
instructions in this manual.  
WARNING:Yellow, floating flames indicate a lack  
of combustion air. Do not operate the boiler until  
the problem is solved or severe personal injury  
or death may occur!  
1. Remove the front grill(s) and front access panel(s).  
2. Remove the clean out covers and insulation, Figure  
55 & 56.  
Figure 104  
Main Burner Flames  
3. Clean each flue passage with a wire brush.  
4. Vacuum out the burner base and clean and inspect  
all of the components. Replace any damaged or badly  
corroded parts.  
5. Replace the insulation and clean out covers,  
6. Replace the front access panel.  
NORMAL  
(HARD FLAME)  
LIFTING  
(TOO MUCH AIR)  
7. Install the burners following the BURNER  
INSTALLATION procedure outlined in this section.  
8. Replace the front grill(s).  
Vent System  
Thoroughly inspect the vent system for any signs of  
blockage, corrosion or leakage.Immediately replace any  
unsound vent system piping.  
YELLOW TIPPING  
(MARGINAL)  
YELLOW FLAME  
(TOO LITTLE AIR)  
Controls  
Use the BOILER OPERATION and BOILER CHECKING  
AND ADJUSTMENT sections of this manual for  
reference.  
1. Check the thermostat or operating controls for  
proper operation.  
2. A float type low water cutoff device must be flushed  
out.  
Page 46  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
6
56  
55  
58  
59  
54  
10  
46  
6
45  
44  
42  
38  
50  
53  
39  
40  
52  
41  
37  
27  
49  
48  
14  
28  
13  
29  
12  
15  
Page 47  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref # Name of Part  
Part #  
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21  
Jacket Less Sides Panels  
55177  
1
55178  
55179  
55180  
55181  
55182  
55183  
55184  
55176  
55185  
1
2
1
1
1
2
1
1
1
2
1
1
1
1
2
1
1
1
1
2
1
1
1
1
Jacket Side Panels, Left & Right  
Jacket Splice Panels, Front, Top,  
Rear & Grill  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6
Jacket Screws  
60442 32 32 32 32 32 32 32 32 62 62 62 62 62 62 62 62 62  
Flue Collector  
63203  
63204  
63205  
63206  
63207  
63208  
63209  
63210  
63187  
63188  
63189  
63190  
63191  
63192  
63193  
63194  
1
1
1
1
1
2
1
1
1
2
1
1
1
2
1
1
1
2
1
1
1
2
1
10  
Draft Hood  
1
1
2
1
1
1
2
1
1
1
1
2
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
Flue Collector & Draft Hood Hardware 72715  
1
1
1
1
1
1
1
1
1
Page 48  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref # Name of Part  
Part #  
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21  
12  
Manifold Less Orifices  
63243  
1
63244  
63245  
63246  
63247  
63248  
63249  
63250  
63253  
63254  
63255  
63256  
63257  
63258  
63259  
63260  
63261  
60093  
60242  
63251  
63262  
63282  
63283  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13  
14  
Orifices, Natural Gas  
8
8
7
1
7
1
1
1
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40  
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40  
Orifices, LP Gas  
Burner Tubes Less Pilot Bracket w/Shutter NG  
Burner Tubes w/Pilot Bracket w/Shutter NG  
Burner Tubes Less Pilot Bracket LP  
Burner Tubes w/Pilot Bracket LP  
9
1
9
1
1
1
11 13 15 17 19 21 22 24 26 28 30 32 34 36 38  
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
11 13 15 17 19 21 22 24 26 28 30 32 34 36 38  
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
15  
Robertshaw 7000 DERHC, Natural Gas, 1" 51186  
Robertshaw LP Conversion Kit  
51083  
72733  
Honeywell V88A-1618, Natural Gas, 1"  
1
1
1
1
1
1
1
1
1
1
Honeywell V8943B-1010, Natural Gas, 1" 50169  
Honeywell V88A-1618, LP Gas, 1" 72733  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Honeywell V8943C-1018, LP Gas, 1" 50174  
Honeywell V88A-1626, Natural Gas, 1-1/4" 72734  
Honeywell V8943B-1028, Natural Gas, 1-1/4" 50170  
1
1
1
1
1
1
1
1
15  
Honeywell V8944B-1019 Natural Gas, 1"  
50177  
1
1
1
1
1
1
Honeywell V8944B-1027 Natural Gas, 1-1/4" 50178  
Honeywell V8944B-1035 Natural Gas, 1-1/2" 50179  
Honeywell V88A-1626, LP Gas, 1-1/4" 72734  
Honeywell V8943C-1026, LP Gas, 1-1/4" 50175  
Honeywell V88A-1634, Natural or LP Gas, 1-1/2" 72735  
Honeywell V8943B-1036, Natural Gas, 1-1/2" 50171  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 49  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref # Name of Part  
Part #  
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21  
Manual Main Shut Off Valve, 1"  
62023  
1
1
1
1
1
1
Manual Main Shut Off Valve, 1-1/4"  
Manual Main Shut Off Valve, 1-1/2"  
Manual Pilot Shut Off Valve,  
62024  
62025  
62028  
50961  
72743  
72739  
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
Pilot Regulator RV12LT  
Pilot Ass'y PSE-NA29, Natural Gas  
Pilot Ass'y PSE-NA29, LP Gas  
Intermittent Pilot Ignition Controls  
Pilot, Intermittent, Natural Gas  
50978  
50998  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
LP Pilot Orifice for the above pilot  
Intermittent Ignition Module, S8610M 51180  
Pilot Gas Solenoid Valve V8046C-1014 1/4" 51099  
Continuous Pilot Ignition Controls  
Pilot, Continuous, Natural Gas  
LP Pilot Orifice for the above pilot  
Pilot Flame Sense Switch  
Automatic Pilot Switch  
50972  
50998  
51188  
50970  
63265  
63266  
63267  
63268  
63269  
63270  
63271  
63272  
63273  
72694  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
27 + 28 Burner Base Less Sides  
1
1
1
1
2
1
1
1
2
1
1
1
1
2
1
1
1
1
2
1
1
1
1
1
1
29  
Burner Base Side Panels  
Burner Base Splice Plates  
Burner Base Bolts  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
60246 12 12 12 12 12 12 12 12 32 32 32 32 32 32 32 32 32  
60245 16 16 16 16 16 16 16 16 40 40 40 40 40 40 40 40 40  
Burner Base Nuts  
37  
38  
39  
Base to Section Insulation, (25 foot roll) 60201  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
Cast Iron Section, Right Side  
Cast Iron Section, Intermediate  
w/o tapping  
3650  
3666  
40  
Cast Iron Section, Intermediate  
w/ 3" tapping, (steam boilers)  
3649  
1
1
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
Page 50  
GB300 BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref # Name of Part  
Part #  
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21  
41  
42  
Cast Iron Section, Left Side  
3651  
1
1
1
1
1
1
9
9
9
1
1
1
1
1
1
1
1
1
1
1
Gasket, Upper Port  
Gasket, Lower Port  
3/8" Rope, 42" length  
Draw Rod 1/2" x 7-1/2"  
1/2 Flat Washer  
60248  
60249  
71601  
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
10 11 12 13 14 15 16 17 18 19 20  
10 11 12 13 14 15 16 17 18 19 20  
10 11 12 13 14 15 16 17 18 19 20  
44  
45  
46  
48  
60358 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60  
62098 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60  
60875 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120  
1/2 Hex Nut  
Cleanout Cover  
69696  
69697  
69698  
69699  
65135  
65136  
65137  
65138  
72695  
72696  
1
1
1
2
2
2
1
1
2
4
4
4
3
1
2
2
1
3
1
2
1
1
4
1
2
1
1
1
2
1
2
49  
50  
Cleanout Cover Insulation  
1
1
3
1
2
2
1
3
1
1
2
2
1
1
4
1
1
2
2
1
1
1
1
2
2
1
2
1
Cleanout Cover Hardware Set  
Cleanout Cover Hardware Set  
2
1
1
4
4
4
2
2
2
Water Controls & Trim  
52  
53  
Temperature Pressure Gauge  
Aquastat L4006A  
60265  
50511  
50502  
50507  
61997  
61998  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Well 3/4" x 3"  
Aquastat, (manual reset) L4006E  
3/4" x 1" Relief Valve 40#, (water)  
1" x 1-1/4" Relief Valve 40#, (water)  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
54  
1-1/4" x 1 1/2" Relief Valve 40#, (water) 61999  
Steam Controls & Trim  
54  
1" x 1" Relief Valve 15#, (steam)  
61982  
1
1
1
1
1
1-1/4" x 1-1/2" Relief Valve 15#, (steam) 61983  
1
1
1
1
1
1
1
1-1/2" x 2" Relief Valve 15#, (steam)  
Steam Pressuretrol PA404A-1009  
L4079B-1033 Steam Pressuretrol, (manual reset)  
Steam Gauge  
61984  
50493  
50495  
60268  
61931  
51005  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
55  
56  
58  
59  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Gauge Glass Set  
M&M 67-S-2 Low Water Cut-off  
Page 51  
WARNING  
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon  
monoxide (CO).  
Carbon Monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic.  
If your Smith boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate.  
CO is lighter than air and thus may travel throughout the building. BRIEF EXPOSURE TO HIGH  
CONCENTRATIONS OF CO, OR PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY RESULT IN  
CARBON MONOXIDE POISONING.  
EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT IN THE  
SUDDEN ONSET OF SYMPTOMS INCLUDING UNCONSCIOUSNESS.  
Symptoms of CO poisoning include the following:  
dizziness  
headaches  
nausea  
vision problems  
loss of muscle control  
weakness  
shortness of breath  
unclear thinking  
unconsciousness  
The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning  
occurs at the onset of cold weather or during flu season. A victim may not experience any symptoms, only one  
symptom, or a few symptoms. Suspect the presence of carbon monoxide if symptoms tend to disappear when  
you leave your home.  
The following signs may indicate the presence of carbon monoxide:  
• Hot gases from appliance, venting system, pipes or chimney, escaping into the living space.  
• Flames coming out around the appliance.  
• Yellow colored flames in the appliance.  
• Stale or smelly air.  
• The presence of soot or carbon in or around the appliance.  
• Very high unexplained humidity inside the building.  
If any of the symptoms of CO poisoning occur, or if any of the signs of carbon monoxide are present, VACATE  
THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED HEATING SERVICE COMPANY OR THE GAS  
COMPANY OR THE FIRE DEPARTMENT.  
To reduce the risk of CO poisoning, have your heating system “tuned up” by a licensed heating contractor or the  
gas company - preferably before each heating season. Also have the service company check your chimney or  
vent pipes for blockage.  
Your home should also be adequately ventilated, particularly if you have insulated your home.  
ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS  
SHOULD PERFORM WORK ON YOUR SMITH BOILER!  
WARNING: Install, operate and maintain unit in accordance with manufacture’s instructions to avoid  
exposure to fuel substances or substances from incomplete combustion which can cause death or  
serious illness. The State of California has determined that these substances may cause cancer, birth  
defects, or other reproductive harm. Also, install and service this product to avoid exposure to airborne  
particles of glasswool fibers and/or ceramic fibers known to the State of California to cause cancer  
through inhalation.The ceramic combustion chamber in the burner box and its gasket contain crystalline  
silica. Wear a tightly fitted dust mask when servicing the burner and gently handle the burner and its  
gasket to prevent inhalation of airborne fibers. Crystalline silica fibers have been identified as  
carcinogenic, or possibly carcinogenic when inhaled.  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  

VidaBox Car Stereo System MAGNUM User Manual
Tiffen Glimmerglass & Bronze Glimmerglass Filters User Manual
Swann SW211 DPE User Manual
Sony Walkman WM FX290W User Manual
Sony HANDYCAM XR550V User Manual
Sony Dog Mount for Action Cam AKADM1 User Manual
Sony Camcorder CX280 User Manual
Sony Blu ray Player BDP S470 User Manual
Samsung GH68 34355F User Manual
Samsung digital SC D363 User Manual