| KBXII-SER Rev C   Service Manual   Models: 400 - 801   This manual must only be used   ƽ WARNING   by a qualified heating installer /   service technician. Read all   instructions, including this manual   and the Knight XL Installation and   OperationManual, beforeinstalling.   Perform steps in the order given.   Failure to comply could result in   severe personal injury, death, or   substantial property damage.   Save this manual for future reference.   Service Manual   Please read before proceeding   Installer   – Read all instructions,   When calling or writing about the boiler   – Please have the boiler model and serial   number from the boiler rating plate.   ƽ WARNING   NOTICE   including this manual and the Knight   XL Installation and Operation Manual,   before installing. Perform steps in the   order given.   Consider piping and installation when   determining boiler location (see the Knight   XL Installation and Operation Manual).   User – This manual is for use only by   a qualified heating installer/service   Any claims for damage or shortage   in shipment must be filed immediately   against the transportation company by the   consignee.   technician. Refer to the Knight XL User’s   Information Manual for your reference.   Have this boiler serviced/inspected by   a qualified service technician at least   annually.   Failure to comply with the above could   result in severe personal injury, death or   substantial property damage.   Handling ceramic fiber materials   REMOVAL OF COMBUSTION CHAMBER LINING   The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers   can be converted to cristobalite in very high temperature applications. The International Agency for   Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite   from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this   appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions   would have to be created to convert the ceramic fibers in this appliance to cristobalite.   ƽ WARNING   The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic   materials it is advisable that the installer follow these safety guidelines.   Avoid breathing dust and contact with skin and eyes.   • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA   requirements for cristobalite at the time this document was written. Other types of respirators may   be needed depending on the job site conditions. Current NIOSH recommendations can be found on   manufacturers, and phone numbers are also listed on this website.   • Wear long-sleeved, loose fitting clothing, gloves, and eye protection.   Apply enough water to the combustion chamber lining to prevent airborne dust.     Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.   Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.   NIOSH stated First Aid.     Eye: Irrigate immediately.   Breathing: Fresh air.   3 Service Manual   Please read before proceeding   When servicing boiler –   • To avoid electric shock, disconnect electrical supply   before performing maintenance.   • To avoid severe burns, allow boiler to cool before   performing maintenance.   Boiler operation –   • Do not block flow of combustion or ventilation air to   the boiler.   • Should overheating occur or gas supply fail to shut off,   do not turn off or disconnect electrical supply to   circulator. Instead, shut off the gas supply at a location   external to the appliance.   • Do not use this boiler if any part has been under water.   The possible damage to a flooded appliance can be   extensive and present numerous safety hazards. Any   appliance that has been under water must be replaced.   Boiler water –   • Thoroughly flush the system (without boiler   connected) to remove sediment. The high-efficiency   heat exchanger can be damaged by build-up or   corrosion due to sediment.   • Do not use petroleum-based cleaning or sealing   compounds in the boiler system. Gaskets and seals in   the system may be damaged. This can result in   substantial property damage.   • Do not use “homemade cures” or “boiler patent   medicines”. Serious damage to the boiler, personnel,   and/or property may result.   • Continual fresh make-up water will reduce boiler life.   Mineral buildup in the heat exchanger reduces heat   transfer, overheats the stainless steel heat exchanger, and   causes failure. Addition of oxygen carried in by makeup   water can cause internal corrosion. Leaks in boiler   piping must be repaired at once to prevent the   introduction of makeup water.   Freeze protection fluids –   • NEVER use automotive antifreeze. Use only inhibited   propylene glycol solutions which are specifically   formulated for hydronic systems. Ethylene glycol is   toxic and can attack gaskets and seals used in hydronic   systems.   4 Service Manual   What is in this manual?   Service   Maintenance   • Service and maintenance schedules   • Address reported problems   • Inspect boiler area and boiler interior   • Clean condensate trap   • Check all piping for leaks   • Check air openings   Near boiler piping   • Typical system components   The Knight XL display   • Display panel readout, buttons and their functions   • Flue vent system and air piping   • Check water system   • Check expansion tank   Control module inputs   • Control module inputs and options   • Check boiler relief valve   • Inspect ignition electrode   • Check ignition ground wiring   • Check all boiler wiring   • Check control settings   • Perform start-up and checks   • Check burner flame   • Check flame signal   • Check flue gas temperature   • General maintenance   Control module outputs   • Control module outputs and options   General   • How the boiler operates   • How the control module operates   • Access modes -- user and installer   • Sequence of operation -- Domestic Hot Water   (DHW)/space heating   • Review with owner   Control panel menu access   • Cleaning boiler heat exchanger   • Oiled bearing circulators   • Accessing programming mode and locating menus   (See separate guide covering the interface.)   Troubleshooting   Control panel parameter access   • Accessing and changing parameters from the display panel   • Troubleshooting table - No display   • Checking temperature sensors   • Sensor tables   • Troubleshooting table - Fault messages displayed on   boiler interface   Quick start information -- parameter   table   • An index of available adjustments and readouts, where to   access them and where to find detailed information.   • Combustion analysis procedure   • Gas valve adjustment procedure   Knight XL operation   • A: General   • B: Temperature Setting   • C: Data Logging   • D: Functions   • E: DHW Settings   • F: Outdoor Reset   • G: Anti-cycling   • H: Control Modes   • I: Circulation Pumps   • J: Building Management System (BMS)   • K: Service Notification   5 Service Manual   1 Service   Near boiler piping   This piping reference is included to specify the Near Boiler Piping specific to the Knight XL. This piping scheme is important   for proper operation of the SMART SYSTEM control. See the Knight XL Installation and Operation Manual for more detailed   piping diagrams.   DOMESTIC HOT   WATER PUMP   DIRT SEPARATOR   INDIRECT   SYSTEM SENSOR   DOMESTIC   HOT WATER   TANK   SYSTEM PUMP   Y-STRAINER   (RECOMMENDED)   BOILER PUMP   TO FLOOR   DRAIN   6 Service Manual   1 Service   (continued)   The Knight XL display   NAVIGATION DIAL   The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the   NAVIGATION dial (in the center):   MENU = Left SELECT Key   SETPOINTS = NAVIGATION Dial - Pressing Down   SHDN = Right SELECT Key   7 Service Manual   1 Service   Control inputs   SYSTEM PUMP SPEED CONTROL   GAS PRESSURE SWITCH   DHW THERMOSTAT   ROOM THERMOSTAT /   ZONE CONTROL   LOW VOLTAGE   CONNECTION   BOARD   FLOW SWITCH   SYSTEM SENSOR   OUTDOOR SENSOR   SEQUENCER / BUILDING   MANAGMENT SYSTEM   LOW WATER CUTOFF   O-TEMP   HEAT EXCHANGER SWITCH   INLET TEMPERATURE   SENSOR   OUTLET TEMPERATURE /   HI-LIMIT SENSOR   FLUE GAS SENSOR   AIR PRESSURE SWITCH   LOUVER PROVING SWITCH   FLAME SENSOR   BLOCKED DRAIN SWITCH   SMART CONTROL   MODULE   DISPLAY PANEL   PC INTERFACE   IMG00006   8 Service Manual   1 Service   (continued)   Control outputs   ALARM BELL   LOW VOLTAGE   CONNECTION   BOARD   LOUVER RELAY   RUN TIME CONTACTS   BUILDING MANAGEMENT   SYSTEM   BOILER PUMP   SYSTEM PUMP   DHW PUMP   IGNITOR   BLOWER   SMART CONTROL   MODULE   GAS VALVE   DISPLAY PANEL   PC INTERFACE   9 Service Manual   1 Service   Access modes   General Operation   How the boiler operates   User   The user can adjust space heating and tank target temperatures   by pressing the NAVIGATION dial when “SETPOINTS” is   flashing at the bottom of the display. The date and time, and   the temperature units can also be changed.   The Knight XL uses an advanced stainless steel heat   exchanger and an electronic control module that allows   fully condensing operation. The blower pulls in gas and air   and pushes flue products out of the boiler through the heat   exchanger and flue piping. The control module regulates   blower speed to control boiler firing rate. The gas valve   senses the amount of air flowing into the boiler and allows   only the right amount of gas to flow.   Installer   Most parameters are available only to the installer, accessible   by entering the installer password (5309).   How the control module operates   Saving parameters (reference the Parameter Table -   Table 1-4 on pages 15 - 18 of this manual)   The Knight XL control module receives input from boiler   sensors. The control module activates and controls the   blower and gas valve to regulate heat input and switches   boiler, DHW and system pumps on and off as needed.   The user/installer programs the module to meet system   needs by adjusting control parameters. These parameters   set operating temperatures and boiler operating modes.   Boiler operation can be based on boiler outlet water   temperature, boiler return water temperature or system   supply temperature, depending on the parameter setting.   Please note that the brackets ([]) denote   screen status.   NOTICE   To save parameters and exit programming:   Press the RIGHT SELECT [SAVE] key and then press the   RIGHT SELECT [HOME] key.   To enter a parameter and continue programming:   Press the RIGHT SELECT [SAVE] key 1 time to return to the   parameter listings; press again to return to the menu listings.   Remember to press the RIGHT SELECT [HOME] key when   finished programming in order to save the changes made.   Sequence of operation   Table 1-1 shows control module normal sequences of   operation for space heating and DHW operation. The   combined operation sequence is for a typical application,   programmed to provide DHW priority.   10   Service Manual   1 Service   (continued)   Table 1-1 Sequence of Operation   OPERATION   DISPLAY   1. Upon a call for heat, the gas pressure switch(es) must be closed.   2. Once the gas pressure switch(es) are closed, the control turns   on the appropriate pumps (system and boiler pumps for space   heating, DHW pump for DHW). The flow switch and/or LWCO   must close.   3. The control turns on power to the louver relay. The louver   proving switch, air pressure switch, and blocked drain switch   must close.   4. The control starts a 15 second prepurge cycle by initiating the   blower.   5. The control starts a 4 second trial for ignition by firing the spark   electrode and opening the gas valve.   6. If flame is not detected within 1 second after the sparking   ends, the control will perform a 10 second post-purge, then start   another prepurge cycle and try to light the burner again. On   the 501 and larger models, the control will lock out if this second   attempt also fails. On the 400 model, the control will perform a   total of 4 attempts before locking out.   7. If flame is detected, it holds the firing rate steady for 5 seconds   to let the flame stabilize, then it begins to modulate the firing rate   based on a set point or some other command (such as a 0-10V   BMS signal).   11   Service Manual   1 Service   Table 1-1 (continued from previous page) Sequence of Operation   OPERATION   DISPLAY   8. If the space heating call for heat is active, and the tank thermostat   or sensor starts a DHW call for heat, the boiler will switch to the   DHW mode. If programmed for normal DHW operation (not as a   zone), the DHW pump will turn on first, then the boiler pump will   turn off 2 seconds later. This will divert the boiler’s outlet water   from the heating system and send it to the tank coil instead. The   control will then modulate to maintain the outlet temperature to   the DHW boiler set point.   9. If the boiler is not part of a Cascade, and both the space heating   and DHW calls for heat remain active long enough, the boiler will   switch back and forth between the two heating modes until one   of them is satisfied.   10. Once both calls for heat are satisfied, the control will turn off the   burner. The blower will continue to run during a 10 second   postpurge.   11. Any pumps that are running will continue to run for their   respective pump delay times before turning off, unless   programmed to remain on continuously. A 60 second anti-cycle   period will start, which will delay any new call for heat until it   times out.   12. In Standby, ready to start a new cycle.   12   Service Manual   1 Service   (continued)   Display panel menu access   Table 1-2 Use this procedure to access menus from the display panel   SCREEN   STATUS   BUTTON   OPERATION   DISPLAY   [SHDN]   Press the RIGHT SELECT soft key [SHDN].   [YES]   Press the LEFT SELECT soft key [YES].   Press and hold the LEFT SELECT soft key [MENU]   for five (5) seconds.   [MENU]   Rotate the NAVIGATION dial clockwise until 5 is   displayed (first digit on the left).   Press the NAVIGATION dial to select the next digit.   Rotate the NAVIGATION dial clockwise until 3 is   shown in the display.   Press the NAVIGATION dial 2 times to move to the last   digit. Rotate the NAVIGATION dial counterclockwise   until 9 is displayed.   [SAVE]   Press the RIGHT SELECT soft key [SAVE].   Rotate the NAVIGATION dial counterclockwise to   select a category.   13   Service Manual   1 Service   Display panel parameter access   Table 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Settings, MIN   SH Setpt   SCREEN   STATUS   BUTTON   OPERATION   DISPLAY   This example shows how to access parameter Temperature Settings. The first display shown is at the beginning   of the menu listings, after entering the installer access code.   Rotate the NAVIGATION dial counterclockwise until   the arrow (>) is next to TEMPERATURE SETTINGS.   Press the NAVIGATION dial one time.   Rotate the NAVIGATION dial counterclockwise until   the arrow (>) is next to MIN SETPT.   Press the NAVIGATION dial one time.   Rotate the NAVIGATION dial to the desired   temperature.   [SAVE]   [EXIT]   Press the RIGHT SELECT soft key [SAVE] one time.   Press the LEFT SELECT soft key [EXIT] if all desired   changes have been made.   [HOME]   Press the LEFT SELECT soft key [HOME].   14   Service Manual   1 Service   (continued)   Parameter table   Table 1-4 This table lists SMART SYSTEM control module parameters and where to access them   User Access   Installer Access   See   Page   Menu   Description   Display Modify Display Modify   Time and Date   19   19   19   19   19   19   19   19   19   19   20   20   20   20   20   20   20   20   20   20   20   20   Yes   No   Yes   No   No   No   No   No   No   Yes   No   Yes   No   No   No   No   Yes   No   No   Yes   No   No   Yes   No   Yes   No   No   No   No   No   No   Yes   No   Yes   No   No   No   No   Yes   No   No   Yes   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   No   Yes   No   Software Version (read only)   Temperature Units (ºC/ºF)   SH Night Setback Offset   SH Night Setback On Times   SH Night Setback Off Times   DHW Night Setback Offset   DHW Night Setback On Times   DHW Night Setback Off Times   Night Setback Override   Display Timeout   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   No   SH1 Set Point   Minimum SH Set Point   Maximum SH Set Point   SH1 Offset   Yes   Yes   Yes   Yes   No   Yes   Yes   Yes   Yes   No   SH1 Differential   SH2 Set Point   SH2 Offset   Yes   Yes   No   Yes   Yes   No   SH2 Differential   SH3 Set Point   SH3 Offset   Yes   Yes   Yes   Yes   SH3 Differential   Reset Log Errors   20   No   No   Yes   Yes   Service Mode Delay   20   20   20   20   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Freeze Protection Pump On   Freeze Protection Burner On   Freeze Protection Burner Differential   15   Service Manual   1 Service   Parameter table   Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where   to access them   User Access   Installer Access   See   Page   Menu   Description   Display Modify Display Modify   DHW Boiler Set Point   21   21   21   21   21   21   No   Yes   No   No   No   No   No   Yes   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Tank Set Point   Tank Set Point Differential   DHW Boiler Offset   DHW Boiler Differential   SH/DHW Switching Time   DHW/SH Switching Time   Tank Minimum Set Point   Tank Maximum Set Point   DHW Type   21   21   21   21   21   22   22   22   22   22   23   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Fan Speed Limiting for DHW   Outdoor 1 Low   Outdoor 1 High   Set Point 1 at Low Outdoor Temp 1   Set Point 1 at High Outdoor Temp 1   Outdoor Air Shutdown SH1   Outdoor Air Shutdown Differential SH1   Shift Reset Curve SH1   Outdoor 2 Low   23   22   22   22   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Outdoor 2 High   Set Point 2 at Low Outdoor Temp 2   Set Point 2 at High Outdoor Temp 2   Outdoor Air Shutdown SH2   Outdoor Air Shutdown Differential SH2   Shift Reset Curve SH2   22   22   23   23   22   22   22   22   22   23   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Outdoor 3 Low   Outdoor 3 High   Set Point 3 at Low Outdoor Temp 3   Set Point 3 at High Outdoor Temp 3   Outdoor Air Shutdown SH3   Outdoor Air Shutdown Differential SH3   Shift Reset Curve SH3   23   No   No   Yes   Yes   16   Service Manual   1 Service   (continued)   Parameter table   Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where   to access them   User Access   Installer Access   See   Page   Menu   Description   Display Modify Display Modify   Boost Temperature   23   23   No   No   No   No   Yes   Yes   Yes   Yes   Boost Time   Anti-Cycling Time   Anti-Cycling Override Differential   Ramp Delay   23   23   23   24   24   24   24   25   25   25   25   25   25   25   25   25   26   26   26   26   26   26   26   26   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Ramp Settings   Controlling Sensor   BMS Tstat Input   BMS   ModBus   ModBus T/O   Cascade Address   Cascade Type   Max Cascade Set Point   Cascade Offset   Cascade Differential   Min On/Off Time   Min Next On Time   System Pump Delay   Boiler Pump Delay   DHW Pump Delay   Boiler Pump Anti-Seize Delay   Boiler Pump Min Voltage   System Pump Type   DHW Pump Anti-Seize Delay   System Pump Anti-Seize Delay   17   Service Manual   1 Service   Parameter table   Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where   to access them   User Access   Installer Access   See   Page   Menu   Description   Display Modify Display Modify   BMS Type   26   26   26   26   26   27   27   27   27   27   27   27   27   27   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   No   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Yes   Volts at Min   Volts at Max   Rate at Min Volts   Rate at Max Volts   Set Point at Min Volts   Set Point at Max Volts   On Volts   Off Differential Volts   Service Notification Months   Service Notification Running Time   Service Notification Cycles   Reset Maintenance Reminder   Service Name and Phone Number   18   Service Manual   1 Service   (continued)   Viewable and changeable control parameters   Space Heating (SH) and Domestic Hot Water (DHW)   Night Setback On Times   Before changing parameters, note the   settings so that the unit can be returned to   its original operating parameters.   CAUTION   This is the time in which the SH Night Setback Offset becomes   active. There are 7 start times and 7 stop times each for the   space heating and DHW night setback features. Both may be   set to any time within a 7-day week. These settings are referred   to as triggers. Multiple start or stop triggers may be set within a   single day, if desired. When a start trigger and a stop trigger are   set to the same time, the stop trigger has priority. The installer   may adjust the space heating night setback start triggers by   accessing the SH Night Setback On Times parameter. The DHW   start triggers in the DHW Night Setback On Times parameter.   This screen shows the start trigger number, the day of the week,   and the time of day.   General   Time and Date   The control uses an internal clock for the night setback   feature and for logging of events. For these features to   work correctly, the clock must be set when the boiler is first   installed or anytime the boiler has been powered off for more   than four (4) hours. This parameter must be accessed to set   the clock.   The internal clock does not adjust for   Daylight Savings Time and therefore,   will require a manual adjustment.   NOTICE   Please note that the brackets ([]) denote   NOTICE   screen status.   1. When the screen is first accessed, start trigger number 1   is shown. If a different trigger number is desired, the   installer can rotate the NAVIGATION dial until the   desired trigger number is displayed. Once the desired trigger   number is selected, the installer can press the NAVIGATION   dial and the day of the week will start to flash.   2. The installer can adjust the day of the week to the one he   wishes to set. Once the day is set, the installer can press the   NAVIGATION dial and the hour will begin to flash.   3. After setting the hour, the installer can press the   NAVIGATION dial and the minutes will flash. Once all   settings have been made, the installer can press the RIGHT   SELECT [SAVE] key. The installer can now select a   different trigger and adjust the settings for that trigger.   4. Once all adjustments are made, the installer can press the   RIGHT SELECT [SAVE] key to save all of the new settings   and return to the General menu, or press the LEFT SELECT   [EXIT] key to return to the General menu without saving the   changes.   Software Version   The software version allows the user to view the software   version in use by the control. This software controls the   operation of the boiler. When a new software version   becomes available, the existing control can be replaced with a   new control to update the software.   Software version is read only.   Temperature units (°C / °F)   The control can be configured to display temperature in   either °C or °F. This parameter can be changed by the user   or the installer by accessing the Temperature Units parameter.   The default is °F.   Space Heating (SH) and Domestic Hot Water (DHW)   Night Setback Offset   Once the unit’s internal clock has been set correctly, the   Night Setback feature can be used to program a lower set   point during unoccupied times. Both the space heating and   DHW can be programmed for night setback. When in night   setback, the control reduces the set point by a fixed amount.   For space heating, it subtracts the space heating night setback   offset from each of the SH user set points (SH1, 2, and 3 Set   point parameters), or the calculated outdoor reset set point (if   lower). For DHW, it subtracts the DHW night setback offset   from the tank set point (Tank Set point parameter).   Space Heating (SH) and Domestic Hot Water (DHW)   Night Setback Off Times   The corresponding space heating night setback stop triggers are   set by accessing the SH Night Setback Off Times parameter. The   stop triggers for the DHW night setback feature can be adjusted   by accessing the DHW Night Setback Off Times parameter. The   adjustment procedure for these parameters is identical to the   space heating start triggers described above.   Night Setback Override   NOTE: The DHW night setback will not work without a tank   Any Night Setback On trigger currently active or scheduled   within the next seven (7) days can be skipped. To skip a trigger,   press the MENU key for 5 seconds, enter the user password,   and press the SAVE key. Rotate the NAVIGATION dial to NSB   OVERRIDE, and press the NAVIGATION dial. A list of the   current (if active) and upcoming NSB On triggers will appear.   sensor installed.   The installer may adjust the space heating night setback   offset by accessing the SH Night Setback Offset parameter and   the DHW night setback offset by accessing the DHW Night   Setback Offset parameter. The minimum setting is 0°F (0°C)   and the maximum setting is 90°F (50°C).   19   Service Manual   1 Service   SH1 - SH3 Differential Set Point   Rotate the NAVIGATION dial to select the trigger you wish   to skip and press the NAVIGATION dial. “SK” will appear   next to that trigger. You can rotate the NAVIGATION dial   again to select another trigger if you wish. If you wish to   reinstate a skipped trigger, re-select that trigger and press   the NAVIGATION dial again. The “SK” next to that trigger   will disappear. Press the HOME key to save these skipped   triggers. If you selected any currently active trigger(s), the   current Night Setback will be cancelled.   The SH differential sets how many degrees below the offset   the temperature has to drop before the boiler turns back   on. This parameter can only be changed by the installer by   accessing the SH1, 2 and 3 Differential Set point parameters.   The range is 0°F to 60°F. The default is 20°F.   Data Logging   Reset log errors   The reset log errors function clears the last 10 errors log.   Display Timeout   Functions   Service Mode Delay   This is the time in which the display remains illuminated.   The range is 10 seconds to 10 minutes. The default is 3   minutes.   By pressing the pin button on the front of the display for   five (5) seconds, the control will be placed in Service Mode.   This will override all other heat demands. The Service Mode   allows the installer to set the unit to any firing rate for the   purpose of combustion analysis. The delay sets the length of   time the boiler will stay in the Service Mode if no keys have   been pressed before going back to its original state. This   parameter can only be changed by the installer by accessing   the Service Mode Delay parameter. The time range of this   parameter is 1 to 10 minutes. The default value is 10 minutes.   Temperature Settings   Space Heating (SH1, SH2, SH3) Set Point   Mixing valves are required for the   protection of any low temperature loops.   CAUTION   There are three (3) individual user set points for better zone   control. These are listed as SH1 Set Point through SH3 Set   Point. If multiple set points are calling for heat the highest set   point has priority. The range is SH Minimum Set point to SH   Maximum Set point. The default is 125°F (52°C).   Freeze Protection Pump On   The SMART SYSTEM control will turn on the boiler and   system pump outputs whenever the inlet temperature drops   below this setting. This is done to prevent the water in the   heat exchanger from freezing. Certain low-temperature   applications (such as snow melt) can operate at temperatures   around freezing, so this setting needs to be lowered in these   cases. The installer can adjust the temperature at which the   pump outputs are turned on by accessing Freeze Protection   Pump On parameter. The minimum setting is -3°F (-19°C),   and the maximum setting is 45°F (7.2°C). The default setting   is 45°F (7.2°C).   Space Heating (SH) Minimum Set Point   The SH minimum set point sets the minimum water   temperature set point that can be used for space heating   operation. The user or installer will not be able to program   the control with a lower SH set point. This parameter can   only be changed by the installer by accessing Minimum SH   Set point parameter. The temperature range of this parameter   is 32°F (0°C) to the space heating maximum set point. The   default value is 32°F (21°C).   Never put the Freeze Protection Pump   on a setting lower than the Freeze   Protection Burner On setting.   NOTICE   Space Heating (SH) Maximum Set Point   Freeze Protection Burner On   The SH maximum set point sets the maximum water   temperature set point that can be used for space heating. The   user or installer will not be able to program the control with a   higher SH set point. This parameter can only be changed by   the installer by accessing Maximum SH Set point parameter.   The temperature range of this parameter is the space heating   minimum set point to 180°F (82°C). The default value is   180°F (82°C).   If running the pumps does not prevent the inlet temperature   from falling closer to freezing, the SMART SYSTEM control   will fire the burner at low fire. The installer can adjust the   temperature at which the burner fires by adjusting the Freeze   Protection Burner On parameter. The minimum setting is   -3°F (-19°C), and the maximum setting is 45°F (7.2°C). The   default setting is 37°F (2.8°C).   Never put the Freeze Protection Pump   NOTICE   SH1 - SH3 Offset Set Point   on a setting lower than the Freeze   Protection Burner On setting.   The SH offset sets how many degrees above set point the   temperature has to go before the boiler will shut off. This   parameter can only be changed by the installer by accessing   parameters SH1, 2 and 3 Offset Set point parameters. The   temperature range of these parameters is 0°F to 20°F. The   default value is 10°F.   Freeze Protection Burner Differential   Once the burner has started firing due to a low inlet   temperature, the inlet temperature must increase by this   amount before the burner turns back off. The installer can   adjust this differential by accessing the Freeze Protection   Burner Differential parameter. The minimum setting is 0°F,   and the maximum is 20°F. The default setting is 5°F (2.8°C).   20   Service Manual   1 Service   (continued)   DHW/SH Switching Time   DHW Settings   When a boiler has a DHW demand and it receives a space   heating demand, the SMART SYSTEM control will start a   timer. Once the timer expires, it will stop the DHW demand   and service the space heating demand. The installer can adjust   the length of time the boiler will service the DHW demand   by accessing the DHW/SW Switching Time parameter. The   minimum setting is 0 minutes and the maximum setting is 50   minutes. The default setting is 30 minutes.   DHW Boiler Set Point   When a DHW call for heat becomes active, the control will   use the DHW boiler set point to determine the firing rate of   the boiler based on the boiler outlet water temperature, or   system temperature when DHW is programmed as a zone.   This parameter can be changed by the installer by accessing   the DHW Boiler Set point parameter. The temperature range   of this parameter is 68°F (20°C) to 180°F (82°C). The default   value is 180°F (82°C).   Tank Minimum Set Point   This setting controls the minimum tank set point for the tank   temperature. The installer can adjust this by accessing the Tank   Minimum Set point parameter. The minimum setting is 60°F   (16°C) and the maximum setting is the maximum tank set point   (Tank Maximum Set point parameter). The default value is 60°   (16°C).   DHW Tank Set Point   By installing a tank sensor, the SMART SYSTEM control can   perform the tank thermostat function. The SMART SYSTEM   control automatically detects the presence of this sensor, and   generates a DHW call for heat when the tank temperature   drops below the tank set point differential (Tank Set point   Differential parameter), and finishes the call for heat when   the tank temperature reaches tank set point + offset. This   parameter can be changed by the installer by accessing the   DHW Tank Set point parameter. The temperature range of   this parameter tank minimum set point to tank maximum set   point. The default value is 125°F (52°C).   Tank Maximum Set Point   This setting controls the maximum tank set point for the tank   temperature. The installer can adjust this by accessing the Tank   Maximum Set point parameter. The minimum setting is the   minimum tank set point (Tank Minimum Set point parameter)   and the maximum setting is 190°F (88°C). The default value is   140°F (60°C).   Tank Set Point Differential   When a tank sensor is installed, the tank temperature must   drop this amount below the tank set point (DHW Tank   Set point parameter) before the boiler turns back on. The   installer can adjust this setting by accessing the Tank Set point   Differential parameter. The minimum setting is 0° (0°C), and   the maximum is 40°F (22°C). The default setting is 6°F (3°C).   DHW Type   This parameter determines whether the Knight XL boiler treats   the indirect DHW tank as a separate load, or as a zone on the   primary loop. When programmed as a separate load, the boiler   will turn on the DHW pump and then turn off the boiler pump   when an indirect DHW demand begins. When programmed as   a zone, the boiler will turn on the DHW pump, leave the boiler   pump on and change the system set point to the DHW boiler set   point (DHW Boiler Set point parameter).   DHW Boiler Offset   This parameter reflects the degrees above DHW boiler set   point the temperature has to go before the boiler will shut off.   The range is 0°F (0°C) to 40°F (22°C). The default setting is   10°F (6°C).   This setting may be changed by the installer by accessing the   DHW Type parameter. The choices are NORMAL and ZONE.   The default setting is NORMAL.   DHW Boiler Differential   This parameter reflects the degrees below DHW boiler set   point the temperature has to go before the boiler turns back   on. The range is 0°F (0°C) to 60°F (33°C). The default setting   is 20°F (13°C).   Fan Speed Limiting for Indirect DHW Tank   This parameter determines the maximum fan speed (and   therefore the maximum rate) to be used when heating an   indirect DHW tank. This setting may be used when the tank is   unable to accept all of the BTU’s available from the boiler. This   parameter may be adjusted by the installer by accessing the Fan   Speed Limiting for Indirect DHW Tank parameter. The default   value is the maximum fan speed for that model.   SH/DHW Switching Time   When a boiler has a space heating demand and it receives   a DHW demand, it will immediately switch to the DHW   demand and start a timer. Once the timer has expired, the   boiler will switch back to the space heating demand and start   another timer. Once this timer expires, it will switch back to   the DHW demand. The installer can adjust the length of time   the boiler will service the space heating demand by accessing   SH/DHW Switching Time parameter. The minimum setting   is 0 minutes and the maximum setting is 50 minutes. The   default time is 30 minutes.   21   Service Manual   1 Service   Set Point (1 - 3) at Low Outdoor Temperature   Outdoor Reset   When the outdoor air temperature drops to the Outdoor   (1 - 3) Low parameters, the calculated set point will be at   this setting (FIG. 1-1). If the outdoor air temperature drops   further, the set point will continue to increase above this   setting. However, if SH1, SH2, and SH3 are set lower, the   water temperature will be limited by these set points instead.   These parameters can be changed by the installer by accessing   the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low   Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3   parameters. The temperature range of this parameter is 68°F   (20°C) to 180°F (82°C). The default value is 180°C (82°C).   The option of controlling up to three (3) different outdoor   resets for low outdoor temperatures is available.   Outdoor (1 - 3) Low   When the outdoor air temperature drops to this point, the   water temperature will be at the Set point 1 at Low Outdoor   Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point   3 at Low Outdoor Temp 3 parameters (FIG. 1-1). If the   outdoor air temperature drops further, the set point will   continue to increase above this setting. This parameter can   be changed by the installer by accessing the Outdoor (1-3)   Low parameter. The temperature range of this parameter is   -39°F (-39°C) to high outdoor temperature set point. The   default value is 25°F (-4°C).   Set Point (1 - 3) at High Outdoor Temperature   When the outdoor air temperature rises to or above Outdoor   (1 - 3) High parameters, the calculated set point will be at this   setting (FIG. 1-1). These parameters can be changed by the   installer by accessing the Set point 1 at High Outdoor Temp 1,   Set point 2 at High Outdoor Temp 2 and Set point 3 at High   Outdoor Temp 3 parameters. The temperature range of this   parameter is 68°F (20°C) to 190°F (88°C). The default value   is 70°F (21°C).   Outdoor (1 - 3) High   When the outdoor air temperature rises to or above this   point, the water temperature will be at the Set point 1 at High   Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and   Set point 3 at High Outdoor Temp 3 parameters (FIG. 1-1).   This parameter can be changed by the installer by accessing   the Outdoor (1-3) High parameter. The temperature range   of this parameter is low outdoor temperature set point to   104°F (40°C). The default value is 70°F (21°C).   Outdoor Air Shutdown (SH1 - SH3)   When the outdoor temperature rises above this point, the   control will block all SH demands (DHW demands will still   be active). These parameters can be changed by the installer   by accessing the Outdoor Air Shutdown SH1, SH2, and SH3   parameters. The temperature range of this parameter is 32°F   (0°C) to 104°F (40°C). The default value is 70°F (21°C).   Figure 1-1 Outdoor Air Reset Curve   SET POINT AT   LOW OUTDOOR   TEMPERATURE   (SH1, SH2, SH3)   SET POINT   SET POINT AT   HIGH OUTDOOR   TEMPERATURE   HIGH OUTDOOR   TEMPERATURE   LOW OUTDOOR   TEMPERATURE   22   Service Manual   1 Service   (continued)   Outdoor Air Shutdown Differential (SH1 - SH3)   Anti-Cycling   The outdoor air shutdown differential parameter is the   number of degrees below Outdoor Air Shutdown SH1, SH2,   and SH3 parameters the outdoor air temperature must go   before the boiler will respond to a SH demand. These   parameters can be changed by the installer by accessing   the Outdoor Air Shutdown Differential SH1, SH2, and SH3   parameters The temperature range of this parameter is 0°F   (0°C) to 54°F (30°C). The default value is 10°F (6°C).   Anti-Cycling Time   Once a SH demand has been satisfied, a set amount of time must   elapse before the control will respond to a new SH demand. The   control will block the new heat demand and anti-cycling will   be shown in the display until the time has elapsed or the water   temperature drops below the Anti-Cycling Override Differential   parameter. This parameter can be changed by the installer by   accessing the Anti-Cycling Time parameter. The time range for   this parameter is 1 minute to 10 minutes. The default value is   1 minute.   Shift Reset Curve (SH1 - SH3)   There is a shift reset curve for each outdoor reset. The shift   reset curve parameter shifts the actual set point above or   below the calculated set point by the number of degrees in   this parameter. These parameters can be changed by the   installer by accessing the Shift Reset Curve SH1, SH2, and   SH3 parameters. The temperature range of this parameter   is -17°F (-10°C) to 18°F (10°C). The default value is 0°F   (0°C). This feature will be active if this parameter is set to   anything other than 0°F (0°C).   Anti-Cycling Override Differential   The control will bypass the anti-cycling time if the inlet   water temperature drops too much. The control will use the   inlet water temperature the boiler was at when it shut off as   the starting point. If the inlet temperature drops below the   temperature parameter the control will abort anti-cycling and   allow the boiler to fire. This parameter can be changed by   the installer by accessing the Anti-Cycling Override Differential   parameter. The temperature range of this parameter is 0°F (0°C)   to 54°F (30°C). The default value is 10°F (6°C).   Boost Temperature   If a SH demand lasts longer than the programmed time   delay setting and there have been no DHW demands, the   control will increase the water temperature set point by the   amount in this parameter. If the SH demand continues   through another time period, the set point will be increased   again. This will continue until either the SH demand ends,   a maximum of 20 increases has occurred, or SH1, SH2,   SH3 maximum set point has been reached. Once the SH   demand has been satisfied the set point will revert back   to its calculated setting. The boost temperature can be   changed by the installer by accessing the Boost Temperature   parameter. The temperature range of this parameter is 0°F   (0°C) to 25°F (14°C). The default value is 0°F (0°C). This   feature will be active if this parameter is set to anything   other than 0°F (0°C).   Ramp Delay (Enable / Disable)   This parameter allows the installer to enable or disable the SH   ramp delay. The default setting is disabled.   Boost Time   The boost time parameter sets the amount of time that must   elapse with a SH demand before the water temperature   calculated set point will be increased. This parameter can   be changed by the installer by accessing the Boost Time   parameter. The time range for this parameter is 0 minute   to 50 minutes. The default value is 0 minutes.   23   Service Manual   1 Service   Ramp Settings   Control modes   Controlling Sensor   Please note that the brackets ([]) denote   screen status.   NOTICE   The SH controlling sensor parameter selects the sensor the   control will use to regulate the boiler firing rate. This parameter   is adjustable by the installer by accessing the Controlling Sensor   parameter. The sensor selections are as follows: The outlet   sensor regulates the firing rate based on the outlet water   temperature of the boiler and the inlet sensor regulates the   firing rate based on the inlet water temperature of the boiler.   If the outlet sensor is selected, and the optional system supply   sensor is connected, the control will regulate the firing rate   based on the system supply sensor temperature. The default   sensor is the Outlet Sensor.   The SMART SYSTEM control can be programmed to limit   the firing rate for a fixed period of time at the start of a   space heating demand. There are six (6) possible limits,   each with their own time delay. The first limit applies as   soon as the burner starts. Once its time delay expires, the   second limit is applied and its timer begins. The control   steps through these limits until the 6th (sixth) limit expires.   Note, however, that the 6th limit will also limit the rate for   the rest of that heat demand. The installer can adjust the   firing limits and time delays by accessing the Ramp Settings   parameter. Once this parameter is selected, the screen will   show the step number, the time delay for that step and the   limit value corresponding with that step. If the installer   wishes to adjust one of the values in that step, he can press   the NAVIGATION dial until the value he wishes to change   is flashing. The installer can then rotate the NAVIGATION   dial to adjust that value. If the installer presses the RIGHT   SELECT [SAVE] key while the limit value is flashing,   the step value will flash again. The installer can then   select the next step and adjust the delay and limit values   corresponding with that step.   BMS Thermostat Input   When controlling the boiler through the 0 - 10V BMS input or   through ModBus, the boiler can be enabled one of two ways.   With the BMS Thermostat Input parameter set to ACTIVE,   the boiler will be enabled by closing the Heat/Loop Demand 1   input. When set to INACTIVE, the boiler will be enabled by the   voltage level on the 0 - 10V input (in the case of 0 - 10V BMS   control), or the 0 - 10V input value received through ModBus.   The default value is INACTIVE.   BMS   When finished, the installer can press the RIGHT SELECT The set point or modulation of the boiler may be controlled   [SAVE] key to store the new settings, or the LEFT SELECT through the 0 - 10V BMS input or through ModBus. When the   [EXIT] key to return to the Anti-Cycling parameter list BMS parameter is set to INACTIVE, the 0 - 10V input will be   without saving the changes. The delay value can be set ignored. When set to ACTIVE, the set point or modulation will   between 0 minutes and 20 minutes. The limit value can be be controlled by the voltage on the 0 - 10V input (in the case   set between 0% and 100%.   of 0 - 10V BMS control), or the 0 - 10V input value received   through ModBus. The default value is INACTIVE.   Figure 1-2 Ramp Delay Interval   24   Service Manual   1 Service   When BMS is set to ACTIVE (see BMS Active / Inactive)   and the boiler is being controlled through ModBus, set   ModBus parameter to ACTIVE. Otherwise, set the ModBus   parameter to INACTIVE. Note that the boiler can still   be monitored by ModBus with this parameter set to   INACTIVE. The default value is INACTIVE.   (continued)   ModBus   As the calculated load increases further and both boilers ramp   up to 90%, it lowers the rate of the first two (2) boilers to 60%   and brings the next boiler on at 60%. The three (3) boilers   then modulate together. As the calculated load decreases, the   boilers will reach a lower threshold (default = 30%), at which   time the last boiler (the third in our example) will turn off and   the Cascade will increase the rates of the remaining boilers to   provide the equivalent total output as before ((3 x 30%) / 2 =   45% in our example).   ModBus T/O   The amount of time the unit controls will wait to receive   a communication string from the BMS controller before   reverting back to its own internal parameters. This   parameter is adjustable by the installer by accessing the   ModBus T/O parameter. The adjustment range of this   parameter is 5 seconds to 2 minutes. The default value is   10 seconds.   Maximum Cascade Set Point   This parameter determines the set point used by the individual   boilers in a Cascade. When a boiler is commanded to fire by   the Leader boiler, it will attempt to achieve this temperature at   its outlet. The Leader boiler will limit the modulation of the   last boiler to fire in order to hold the temperature at the system   supply sensor to the user set point. If any of the boiler outlet   temperatures reach the maximum cascade set point, the boiler   will then modulate down on its own in order to keep its outlet   temperature within the maximum cascade set point. Therefore,   this parameter can be used to limit the outlet temperatures of   all the boilers in a Cascade. Note that this parameter does   not apply when the boiler is heating an indirect DHW tank.   This parameter is adjustable by the installer by accessing the   Maximum Cascade Set Point parameter. The temperature   range of this parameter is 32° (0°C) to 190°F (88°C). The   default maximum cascade set point is 185°F (85°C).   Cascade Address   The boiler designated as the Leader needs to be programmed   with address 0. All the Member boilers require addresses   from 1 to 7, and the addresses must be different for each   Member. The addresses can be in any order, regardless   of the order in which the units are wired together. This   parameter is adjustable by the installer by accessing the   Cascade Address parameter. The outdoor air (if used) and   system supply sensor must be connected to the Leader   boiler. The default address is 1.   Cascade Offset   If installing the boilers in an existing system, the new   boilers should be programmed as the Leader and/or the   higher number addresses.   This parameter determines how much the temperature must   go above set point before the lead boiler will turn off. This   parameter can be adjusted by the installer by accessing the   Cascade Offset parameter. The temperature range of this   parameter is 0° to 20°F (11°C) The default value is 10°F (6°C).   Cascade Type (L/L / EFF)   There are two (2) options for the way a Cascade divides the   load between its heaters. The first is Lead/Lag, designated   as L/L in the menu. This method is used when it is desired   to have the least amount of total flow through the boilers.   This method will modulate the last two (2) boilers. This   provides for smooth transitions when a boiler turns on or   off. When the last boiler reaches 100% and the calculated   load is still increasing, it will start the next boiler at 20%   and reduce the previous boiler to 80%, thus eliminating   the sudden jump in total output of the Cascade. When the   calculated load is decreasing and the last boiler gets down   to 20% fire, it will hold it there and start lowering the firing   rate on the next-to-last boiler. When the next-to-last boiler   reaches 20%, it will turn the last boiler off and raise the   rate of the next-to-last boiler to 40%, thus eliminating the   sudden drop in total output of the Cascade.   Cascade Differential   This parameter determines how much the temperature must   go below the turn off temperature (Set point + Offset) before   the lead boiler turns on. This parameter can be adjusted by the   installer by accessing the Cascade Differential parameter. The   temperature range of this parameter is 0°F to 60°F (33°C) The   default value is 20°F (11°C).   Minimum On/Off Time   In order to prevent units in a Cascade from short cycling,   this parameter defines the minimum ON and OFF time for   each unit. The installer can adjust this time by accessing the   Minimum On/Off Time parameter. The minimum setting is 0   seconds and the maximum setting is 10 minutes. The default   is 30 seconds.   Minimum Next On Time   The other Cascade divider method is Efficiency   Optimization, designated as EFF in the menu. This   method is used, as the name implies, when it is desired   to have the most efficient system. When the first boiler   reaches a certain rate (default = 90%), it lowers its rate   to 45% and turns on the next boiler at 45%. The two (2)   boilers then modulate at the same rate.   In order to reduce the risk of temperature overshoot with   a Cascade, this parameter defines the minimum time delay   from starting one unit until the next unit may be started. The   installer can adjust this time delay by accessing the Minimum   Next On Time parameter. The minimum setting is 0 minutes   and the maximum setting is 10 minutes. The default is 60   seconds.   25   Service Manual   1 Service   DHW Pump Anti-Seize Delay   Circulation pumps   If the boiler pump does not run for 24 hours, it will be turned   on briefly to prevent it from seizing. The length of time it runs   is determined by the DHW Pump Anti-Seize Delay parameter.   The range of this setting is 0 seconds to 50 minutes. The default   setting is 20 seconds.   System Pump Delay   The system pump delay parameter sets the length of time the   system pump (if connected) will run after a SH demand has   been satisfied. This parameter is adjustable by the installer by   accessing the System Pump Delay parameter. The time range   for this parameter is 1 second to 40 minutes. The default time   is 30 seconds.   System Pump Anti-Seize Delay   If the boiler pump does not run for 24 hours, it will be turned   on briefly to prevent it from seizing. The length of time it runs   is determined by the System Pump Anti-Seize Delay parameter.   The range of this setting is 0 seconds to 50 minutes. The default   setting is 20 seconds.   Boiler Pump Delay   The SH pump delay parameter sets the length of time the   boiler pump will run after a SH demand has been satisfied.   Setting the delay time to 0 will disable the pump. This   parameter is adjustable by the installer by accessing the Boiler   Pump Delay parameter. The time range for this parameter is   1 second to 40 minutes. The default time is 30 seconds.   BMS   BMS Type   DHW Pump Delay   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus, the 0 - 10V signal can be interpreted   as either a modulation command or a set point. When the BMS   Type parameter is set to POWER, the 0 - 10V signal will control   the modulation. When set to SETPOINT, the 0 - 10V signal   will control the SH set point. The default setting is SETPOINT.   The DHW pump delay parameter sets the length of time the   DHW pump (if connected) will run after a DHW demand has   been satisfied. This parameter is adjustable by the installer by   accessing the DHW Pump Delay parameter. The time range   for this parameter is 10 seconds to 40 minutes. The default   time is 1 minute.   Volts at Minimum   Boiler Pump Anti-Seize Delay   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus, the Volts at Minimum parameter   should be set to the minimum voltage signal sent to the   SMART SYSTEM control. The range of this parameter is 0.0V   to the Volts at Maximum value. The default setting is 2.0V.   If the boiler pump does not run for 24 hours, it will be   turned on briefly to prevent it from seizing. The length of   time it runs is determined by the Boiler Pump Anti-Seize   Delay parameter. The range of this setting is 0 seconds to 50   minutes. The default setting is 20 seconds.   Boiler Pump Minimum Voltage   Volts at Maximum   The speed of the boiler pump can be controlled by the   SMART SYSTEM control in order to maintain a minimum   T through the heat exchanger. Thus, as the firing rate   decreases, the speed of the boiler pump can decrease as well.   The SMART SYSTEM control outputs a 0 - 10V signal to the   boiler pump to control its speed. The Boiler Pump Minimum   Voltage parameter determines the minimum voltage given to   the boiler pump, thereby setting its minimum speed. The   range of this setting is 2.5V to 10V. The default setting is   3.5V.   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus, the Volts at Maximum parameter   should be set to the maximum voltage signal sent to the   SMART SYSTEM control. The range of this parameter is the   Volts at Minimum value to 10.0V. The default value is 10.0V.   Rate at Minimum Volts   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Type is programmed as   POWER, the modulation percentage represented by the Volts   at Minimum parameter is set by the Rate at Minimum Volts   parameter. The minimum value is 0% and the maximum is   the Rate at Maximum Volts setting. The default value is 20%.   System Pump Type   The system pump can be programmed to operate in response   to any of the Room Thermostat inputs, or to run continuously   until the boiler goes into Outdoor Shutdown. To program   the system pump to operate only with a space heating call   for heat, set the System Pump Type parameter to CFH. To   program the system pump to run continuously until outdoor   shutdown starts, set the System Pump Type parameter to   WWSD. The default setting is CFH.   Rate at Maximum Volts   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Type is programmed as   POWER, the modulation percentage represented by the Volts   at Maximum parameter is set by the Rate at Maximum Volts   parameter. The minimum value is the Rate at Minimum Volts   setting and the maximum is 100%. The default value is 100%.   26   Service Manual   1 Service   (continued)   Set Point at Minimum Volts   Service Notification Cycles   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Type is programmed as   SETPOINT, the set point represented by the Volts at Minimum   parameter is set by the Set Point at Maximum Volts parameter.   The minimum value is 32°F (0°C) and the maximum is the   Set Point at Maximum Volts setting. The default value is 70°F   (21°C).   When the boiler control determines that a scheduled   service is due based on the number of boiler cycles, the   boiler display will alternate the standard boiler display   text with the message SERVICE DUE every 5 seconds.   This parameter is adjustable by the installer by accessing   the Service Notification Cycles parameter. The range for   this parameter is 0 cycles to 100,000 cycles. The default is   50,000 cycles.   Set Point at Maximum Volts   Reset Maintenance Reminder   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Type is programmed as   SETPOINT, the set point represented by the Volts at Maximum   parameter is set by the Set Point at Maximum Volts parameter.   The minimum value is the Set Point at Minimum Volts setting   and the maximum is 190°F (88°C). The default value is 180°F   (82°C).   Once servicing has been completed, the service notification   counter should be reset. This parameter can be reset by   the installer by accessing the Reset Maintenance Reminder   parameter. Once accessed, press the RESET key to reset the   service notification counter.   Service Name and Phone Number   On Volts   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Thermostat Input is set   to INACTIVE, the On Volts parameter determines the 0 - 10V   BMS input voltage at which the boiler is enabled. The minimum   value is 0.5V and the maximum is 10.0V. The default value is   2.0V.   Please note that the brackets ([]) denote   screen status.   NOTICE   When a Maintenance Reminder timer or counter has   expired, a Maintenance Reminder screen will appear on the   display. By programming the installer’s name and phone   number, this information will appear on the Maintenance   Reminder Screen at that time. This can be programmed by   accessing the Service Name and Phone Number parameter.   When selected, another menu will appear with PHONE   and NAME.   Off Differential Volts   When programmed for BMS control through the 0 - 10V BMS   input or through ModBus and the BMS Thermostat Input is set   to INACTIVE, the Off Differential Volts parameter determines   how far below the On Volts setting the 0 - 10V BMS input   voltage must be in order to disable the boiler. The minimum   value is 0.2V and the maximum is the On Volts setting. The   default value is 1.0V.   1. Rotate the NAVIGATION dial to point to the   name/phone number to program and press the   NAVIGATION dial. The screen will now display the   selected item (either PHONE or NAME).   2. Press the NAVIGATION dial again. A cursor will   appear at the bottom of the screen. By rotating the   NAVIGATION dial, various numbers and characters   will appear. When the desired number/character is   found, press the NAVIGATION dial. The cursor will   move to the next position.   Service Notification   Service Notification in Months   When the boiler control determines that a scheduled service is   due based on days of installation, the boiler display will alternate   the standard boiler display text with the message SERVICE DUE   every 5 seconds. This parameter is adjustable by the installer by   accessing the Service Notification in Months parameter. The time   range for this parameter is 0 months to 100 months. The default   time is 12 months.   3. Repeat this procedure until the entire message is   entered. If you make a mistake and wish to back up   one character, rotate the NAVIGATION dial until   the back arrow () character is displayed and press the   NAVIGATION dial.   This feature has been disabled by the manufacturer. To enable   this feature change parameter K1 to the desired time range.   4. When finished, press the RIGHT SELECT [SAVE] key   to return to the previous menu.   Service Notification Running Time   When the boiler control determines that a scheduled service is   due based on the hours of actual operation, the boiler display   will turn yellow and a new status screen will appear informing   the installer that maintenance is required. This parameter is   adjustable by the installer by accessing the Service Notification   Running Time parameter. The time range for this parameter is   0 hours to 17,500 hours. The default time is 8,760 hours.   27   Service Manual   2 Maintenance   Maintenance and annual startup   Table 2-1 Service and Maintenance Schedules   Owner maintenance   Service technician   (see the Knight XL User’s Information Manual for   instructions)   (see the following pages for instructions)   General:   • Address reported problems   • Check boiler area   • Inspect interior; clean and vacuum if   necessary;   • Check pressure/temperature   gauge   Daily   • Clean condensate trap and fill with fresh   water   • Check for leaks (water, gas, flue,   condensate)   • Verify flue and air lines in good condition   and sealed tight   • Check vent piping   • Check air piping   • Check system water pressure/system   piping/expansion tank   Monthly   • Check air and vent termination   screens   • Check control settings   • Check ignition and flame sense   electrodes (sand off any deposits; clean   and reposition)   • Check relief valve   • Check condensate drain system   • Check air vents   • Check wiring and connections   • Perform start-up checkout and   performance verification per Section 10   in the Knight XL Installation and   Operation Manual.   •Test low water cutoff (if used)   Periodically   • Reset button (low water cutoff)   • Flame inspection (stable, uniform)   • Flame signal (at least 10 microamps at   high fire)   • Check boiler piping (gas and   water) for leaks   Every   6 months   • Clean the heat exchanger if flue   temperature is more than 54°F (30°C)   above return water temperature.   • Operate relief valve   If combustion or performance   indicate need:   •Shut boiler down (unless boiler   used for domestic hot water)   End   of season   • Clean heat exchanger   • Remove and clean burner using   compressed air only   months   • Clean the blower wheel   28   Service Manual   2 Maintenance   (continued)   Follow the Service and maintenance procedures given throughout this manual and in component literature   shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler   or system. Failure to follow the directions in this manual and component literature could result in severe   personal injury, death, or substantial property damage.   ƽ WARNING   The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance   and care of the boiler designated in Table 2-1 and explained on the following pages must be performed to   assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could   result in equipment failure.   ƽ WARNING   Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except   as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical   shock, causing severe personal injury or death.   ƽ WARNING   Address reported problems   Figure 2-1 Condensate Trap   1. Inspect any problems reported by the owner and correct   before proceeding.   RETAINING   SCREW   2” PVC CAP WITH   BLOCKED DRAIN SWITCH   Inspect boiler area   1. Verify that boiler area is free of any combustible materials,   gasoline and other flammable vapors and liquids.   PVC TEE ASSEMBLY   (FACTORY SUPPLIED)   2. Verify that air intake area is free of any of the contaminants   listed in Section 1 of the Knight XL Installation and   Operation Manual. If any of these are present in the   boiler intake air vicinity, they must be removed. If   they cannot be removed, reinstall the air and vent lines   per this manual and the Knight XL Installation and   Operation Manual.   CONDENSATE FROM   HEAT EXCHANGER   TO FLOOR   DRAIN   Inspect boiler interior   The condensate trap must be filled with   water during all times of boiler operation   to avoid flue gas emission from the   condensate drain line. Failure to fill the   trap could result in severe personal injury   or death.   1. Remove the front access cover and inspect the interior of   the boiler.   ƽ WARNING   2. Vacuum any sediment from inside the boiler and   components. Remove any obstructions.   Clean condensate trap   Check all piping for leaks   1. Inspect the condensate drain line, condensate PVC   fittings, and condensate trap.   Eliminate all system or boiler leaks.   ƽ WARNING   Continual fresh makeup water will   reduce boiler life. Minerals can build   up in sections, reducing heat transfer,   overheating heat exchanger, and causing   heat exchanger failure. Leaking water may   also cause severe property damage.   2. Remove the PVC cap retaining screw from the PVC cap   (FIG. 2-1).   3. Remove the 2 inch PVC cap with the switch located at the   top of the trap (FIG. 2-1).   4. Remove any sediment in the trap.   1. Inspect all water and gas piping and verify to be leak free.   5. Fill with fresh water until the water begins to pour out of   the drain.   2. Look for signs of leaking lines and correct any problems   found.   6. Replace the cap. Press the cap onto the trap until the cap   makes contact with the drain.   3. Check gas line using the procedure found in Section 7   - Gas Connections of the Knight XL Installation and   Operation Manual.   7. Replace the retaining screw.   29   Service Manual   2 Maintenance   Safety relief valves should be re-inspected   AT LEAST ONCE EVERY THREE YEARS,   by a licensed plumbing contractor or   authorized inspection agency, to ensure   that the product has not been affected by   corrosive water conditions and to ensure   that the valve and discharge line have not   been altered or tampered with illegally.   Certain naturally occurring conditions   may corrode the valve or its components   over time, rendering the valve inoperative.   Such conditions are not detectable unless   the valve and its components are physically   removed and inspected. This inspection   must only be conducted by a plumbing   contractor or authorized inspection   agency – not by the owner. Failure to   re-inspect the boiler relief valve as directed   could result in unsafe pressure buildup,   which can result in severe personal injury,   death, or substantial property damage.   Flue vent system and air piping   ƽ WARNING   1. Visually inspect the entire flue gas venting system and air   piping for blockage, deterioration or leakage. Repair any   joints that show signs of leakage. Verify that air inlet pipe   is connected and properly sealed.   2. Verify that boiler vent discharge and air intake are clean   and free of obstructions.   Failure to inspect for the above conditions   and have them repaired can result in   severe personal injury or death.   ƽ WARNING   Check water system   1. Verify all system components are correctly installed and   operational.   2. Check the cold fill pressure for the system. Verify it is   correct (must be a minimum of 12 psi (82.7 kPa)).   3. Watch the system pressure as the boiler heats up (during   testing) to ensure pressure does not rise too high.   Excessive pressure rise indicates expansion tank sizing or   performance problem.   Following installation, the valve lever   must be operated AT LEAST ONCE   A YEAR to ensure that waterways are   clear. Certain naturally occurring   mineral deposits may adhere to the valve,   rendering it inoperative. When manually   operating the lever, water will discharge   and precautions must be taken to avoid   contact with hot water and to avoid water   damage. Before operating lever, check   to see that a discharge line is connected   to this valve directing the flow of hot   water from the valve to a proper place of   disposal. Otherwise severe personal injury   may result. If no water flows, valve is   inoperative. Shut down the boiler until a   new relief valve has been installed.   ƽ WARNING   4. Inspect automatic air vents and air separators. Remove   air vent caps and briefly press push valve to flush vent.   Replace caps. Make sure vents do not leak. Replace any   leaking vents.   Check expansion tank   1. Expansion tanks provide space for water to move in   and out as the heating system water expands due to   temperature increase or contracts as the water cools.   Tanks may be open, closed or diaphragm or bladder   type. See Section 6 - Hydronic Piping of the Knight XL   Installation and Operation Manual for suggested best   location of expansion tanks and air eliminators.   2. After following the above warning directions, if the relief   valve weeps or will not seat properly, replace the relief   valve. Ensure that the reason for relief valve weeping is   the valve and not over-pressurization of the system due   to expansion tank waterlogging or undersizing.   Check boiler relief valve   1. Inspect the relief valve and lift the lever to verify flow.   Before operating any relief valve, ensure that it is piped   with its discharge in a safe area to avoid severe scald   potential. Read Section 6 - Hydronic Piping of the   Knight XL Installation and Operation Manual before   proceeding further.   30   Service Manual   2 Maintenance   (continued)   Inspect ignition and flame sense   electrodes   Figure 2-2 Burner Assembly - Model 400   1. Remove the ignition and flame sense electrodes from the   boiler heat exchanger access cover.   2. Remove any deposits accumulated on the ignition/flame   sense electrode using sandpaper. If the electrodes cannot   be cleaned satisfactorily, replace with new ones.   AIR / GAS ARM   3. Replace ignition/flame sense electrode, making sure   gasket is in good condition and correctly positioned.   Check ignition ground wiring   1. Inspect boiler ground wire from the heat exchanger   BURNER   GASKET   access cover to ground terminal strip.   2. Verify all wiring is in good condition and securely   attached.   SCREWS   (QTY. 5)   3. Check ground continuity of wiring using continuity   meter.   Figure 2-3 Burner Assembly - Model 501   4. Replace ground wires if ground continuity is not   satisfactory.   Check all boiler wiring   1. Inspect all boiler wiring, making sure wires are in good   AIR / GAS ARM   condition and securely attached.   Check control settings   1. Set the SMART SYSTEM control module display to   Parameter Mode and check all settings. See Section 1 of   this manual. Adjust settings if necessary. See Section 1 of   this manual for adjustment procedures.   BURNER   GASKET   2. Check settings of external limit controls (if any) and   adjust if necessary.   SCREWS   (QTY. 5)   Perform start-up and checks   Figure 2-4 Burner Assembly - Models 601 - 801   1. Start boiler and perform checks and tests specified in   Section 10 - Start-up of the Knight XL Installation and   Operation Manual.   2. Verify cold fill pressure is correct and that operating   pressure does not go too high.   AIR ARM   Check burner flame   1. Inspect flame through observation window.   2. If the flame is unsatisfactory at either high fire or low fire,   turn off boiler and allow boiler to cool down. Remove the   burner and clean it thoroughly using a vacuum cleaner   or compressed air. Do not use compressed air to clean   burner if performed inside a building.   BURNER   GASKET   SCREWS   (QTY. 5)   3. Remove the burner, reference FIG.’s 2-2 thru 2-4.   4. When replacing the burner, ensure gasket is in good   condition and positioned correctly (FIG.’s 2-2 thru 2-4).   31   Service Manual   2 Maintenance   7. Brush the heat exchanger while dry using a nylon bristle   brush. Caution: DO NOT use a metal brush. Re-vacuum   the heat exchanger.   Check flame signal   1. At high fire the flame signal shown on the display should   be at least 10 microamps.   8. Finish cleaning using a clean cloth dampened with warm   water. Rinse out debris with a low pressure water supply.   2. A lower flame signal may indicate a fouled or damaged   flame sense electrode. If cleaning the flame sense electrode   does not improve, ground wiring is in good condition,   and ground continuity is satisfactory, replace the flame   sense electrode.   9. Allow the heat exchanger to thoroughly dry.   10. Remove the field supplied rear refractory cover from the   back of the combustion chamber of the heat exchanger and   reassemble.   3. See Section 3 - Troubleshooting in this manual for other   procedures to deal with low flame signal.   11. Close isolation valves on piping to isolate boiler from   system. Attach a hose to the boiler drain and flush boiler   thoroughly with clean water by using purging valves to   allow water to flow through the water make-up line to the   boiler.   Review with owner   1. Review the Knight XL User’s Information Manual with   the owner.   2. Emphasize the need to perform the maintenance schedule   specified in the Knight XL User’s Information Manual   (and in this manual as well).   12. Perform start-up and check-out procedures in the Check   Flame and Combustion - Section 10 - Startup of the   Installation and Operation Manual.   3. Remind the owner of the need to call a licensed contractor   should the boiler or system exhibit any unusual behavior.   13. Replace the access cover and restore boiler to operation.   4. Remind the owner to follow the proper shutdown   procedure and to schedule an annual start-up at the   beginning of the next heating season.   Table 2-2 Heat Exchanger Cleaning Kits   Kit   Part   Component   Description   Model   Cleaning boiler heat exchanger   Number Number   For recommended materials; including brush, appropriate   extension(s), refractory cover, and detailed instructions see   Table 2-2 - Heat Exchanger Cleaning Kits.   CTN20005   Rear Refractory Cover   Nylon 4" Wheel Brush*   MSC20083*   400   KIT30063   MSC20084   3mm Allen Wrench   1/4" x 24" Drill Extension   Rear Refractory Cover   Nylon 4" Wheel Brush*   1/4" x 12" Drill Extension   1/4" x 24" Drill Extension   1. Shut down boiler:   MSC20086   CTN20005   • Follow the “To Turn Off Gas to Appliance” instructions   for the boiler in Section 10 - Startup of the Installation   and Operation Manual.   • Do not drain the boiler unless it will be exposed to   freezing temperatures. If using freeze prevention fluid   in system, do not drain.   MSC20083*   KIT30064   501 - 801   MSC20085   MSC20086   * Do NOT use a metal brush. Only use   the kit provided brush or an equivalent   replacement nylon brush.   ƽ CAUTION   2. Allow time for the boiler to cool to room temperature if   it has been firing.   3. Remove the nuts securing the heat exchanger access cover   to the heat exchanger and set aside.   Figure 2-5 Rope Gasket - Heat Exchanger Door   4. Remove the heat exchanger access cover, burner, and   gas/air arm assembly.   ROPE GASKET   The boiler contains ceramic fiber   ƽ WARNING   materials. Use care when handling these   materials per instructions on page 3 of   this manual. Failure to comply could   result in severe personal injury.   5. Remove the condensate hose from the heat exchanger   end. Connect a field supplied 3/4” diameter hose to   a drain pan. Using field supplied means, cover the   refractory in the back of the combustion chamber of the   heat exchanger.   CAUTION: IF GASKET IS DAMAGED   DO NOT REUSE, THE HEAT EXCHANGER DOOR   MUST BE REPLACED.   Rope gasket is intended for sealing combustion   (FIG. 2-5). If damaged DO NOT reuse, the   heat exchanger door must be replaced. Consult   factory for replacement heat exchanger door   (kit WTR3080 and WTR3086).   NOTICE   6. Use a vacuum cleaner to remove any accumulation on the   boiler heating surfaces. Do not use any solvent.   32   Service Manual   3 Troubleshooting   Label all wires prior to disconnection   Check control module fuses   ƽ WARNING   when servicing controls. Wiring errors   can cause improper and dangerous   operation. Always disconnect power   to the boiler before servicing. Failure   to comply could result in severe   personal injury, death, or substantial   property damage.   ALWAYS check control module fuses before   NOTICE   replacing control module or any major   components (blower, etc.). If one of these   fuses is blown, it can prevent the control   module or other components from operating.   1. Turn OFF the power to the boiler at the external line   switch.   Never jumper (bypass) any device   except for momentary testing as   outlined in the Troubleshooting   chart. Severe personal injury, death,   or substantial property damage can   result.   ƽ WARNING   2. Remove top access cover.   3. Remove the control module cover.   4. Inspect fuses F1, F2, and F3, see FIG 3-1 below.   Figure 3-1 Control Module Fuses   Before troubleshooting:   1. Have the following items:   a. Voltmeter that can check 120 VAC, 24 VAC, and   12 VDC.   b. Continuity checker.   c. Contact thermometer.   F3 - .80 AMP FUSE   24V DC POWER SUPPLY   2. Check for 120 VAC (minimum 102 VAC to maximum   132 VAC) to boiler.   F1 - 5 AMP FUSE   PUMPS   F2 - 3.15 AMP FUSE   BLOWER   3. Make sure thermostat is calling for heat and contacts   (including appropriate zone controls) are closed.   Check for 24 VAC between thermostat wire nuts and   ground.   5. The boiler is shipped with three (3) spare fuses in a plastic   bag attached to the control module cover.   4. Make sure all external limit controls are installed and   operating.   6. If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15   amps and F1 is 5 amps).   Check the following:   Note: Fuses F1, F2, and F3 are all slow blow fuses.   1. Wire connectors to control module are securely   plugged in at the module and originating control.   Do not jumper fuse or replace with any fuse   ƽ WARNING   except as specified. Failure to comply could   result in severe personal injury, death, or   substantial property damage.   2. Gas pressures:   • Maximum: 14 inches w.c. (3.5 kPa) (natural and   LP) with no flow (lockup) or with boiler on   • Minimum: 4 inches w.c. (1.0 kPa) (natural),   8 inches w.c. (2.0 kPa) (LP) with gas flowing (verify   during boiler startup)   7. Install control module cover and top access cover after fuse   inspection.   8. Restore power to the boiler at the external line switch and   verify boiler operation (Section 10 - Start-up in the Knight   XL Installation and Operation Manual) after completing   boiler service.   33   Service Manual   3 Troubleshooting   Table 3-1 Troubleshooting Chart - No Display   FAULT   CAUSE   CORRECTIVE ACTION   • Check external line switch, fuse, or breaker.   - No 120 vac supplied to unit.   • Check position of ON/OFF switch. Turn switch to the   ON position.   • Check 120 vac through the ON/OFF switch.   • Check wiring harness connection between display   board and main control board. Connect   harness at both points.   No Display   - No voltage through the switch.   - Bad display board.   • Replace switch.   • Replace board.   - Bad main control board.   • Replace the main control board.   • Replace fuse F3 on the main control board, see   page 33 of this manual.   - Blown fuse.   - Main control board temperature set point   satisfied.   • Review temperature setting.   - Remote thermostat satisfied.   • Review remote thermostat setting.   - Outside air temperature above Warm • Check location of outside air sensor.   Check   No Burner   Operation   Weather Shutdown (WWSD) set point for   main control board.   resistance of outdoor air sensor and compare to Table   3-2B on page 35 of this manual.   • Consult display for specific fault. Refer to fault   descriptions on page 37 of this manual for corrective   actions.   - Unit locked out on fault.   - Unit in Shutdown Mode.   • Take unit out of Shutdown Mode.   • Check ramp delay parameter settings. Optional PC   software required.   - Ramp delay active.   • Turn ramp delay feature off. See page 23 of this   manual for instructions on how to turn this feature off.   Unit Does   • Check BMS parameter settings.   software required.   Optional PC   Not Modulate - Boiler controlled by BMS.   Above 50%   • Verify that the flue sensor is located in the flue outlet.   • Check wiring connections at the flue sensor.   - Flue sensor open.   • Check the resistance of the flue sensor and compare   to Table 3-2D on page 35 of this manual.   34   Service Manual   3 Troubleshooting   (continued)   Checking temperature sensors   The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The   following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the   sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor   It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These   devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL   Installation and Operation Manual for correct terminal location.   Table 3-2A - Inlet Water/System Sensor Resistance vs.   Table 3-2B - Outdoor Air Sensor Resistance vs.   Temperature   Temperature   Temperature Resistance Temperature Resistance   Temperature Resistance Temperature Resistance   -50   -40   -30   -20   10   490,813   336,606   234,196   165,180   118,018   85,362   20   30   40   50   60   70   80   46,218   34,558   26,099   19,900   15,311   11,883   9,299   50   68   18,780   12,263   8,194   5,592   3,893   2,760   158   176   194   212   1,990   1,458   1,084   817   86   104   122   140   0 10   62,465   Table 3-2C - Outlet Water Sensor Resistance vs. Temperature   S1a   S1b   (Wire Color - R/BK and Y)   (Wire Color - G and Y)   Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance   50   68   19,553   12,690   8,406   5,715   3,958   2,786   158   176   194   212   2,004   1,464   1,084   816   50   68   40,030   25,030   16,090   10,610   7,166   158   176   194   212   3,478   2,492   1,816   1,344   86   86   104   122   140   104   122   140   4,943   Table 3-2D - Flue Sensor Resistance vs. Temperature   S3a   S3b   (Wire Color - W/B and Y)   (Wire Color - PR and Y)   Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance   50   68   40,030   25,030   16,090   10,610   7,166   158   176   194   212   3,478   2,492   1,816   1,344   50   68   258,500   125,500   80,220   52,590   35,270   24,160   158   176   194   212   16,870   12,000   8,674   86   86   104   122   140   104   122   140   6,369   4,943   35   Service Manual   3 Troubleshooting   Table 3-3 Troubleshooting Chart - Noisy System   FAULT   CAUSE   CORRECTIVE ACTION   - Supply gas problem. Natural gas • Refer to Section 7 - Gas Connections of the Knight   pressures should be between 4 inches XL Installation and Operation Manual for detailed   w.c. and 14 inches w.c. LP gas pressures information concerning the gas supply.   should be between 8 inches w.c. and 14   inches w.c.   - Gas/air mixture problem.   • Refer to the Gas Valve Adjustment Procedure on   page 47 of this manual for the proper gas valve setting.   Verify that the vent/air intake lengths do not exceed the   maximum listed in the General Venting section of the   Knight XL Installation and Operation Manual.   - Dirty/damaged burner.   • Refer to page 31 in this manual for the burner removal   and inspection procedure. Clean or replace the burner   as necessary.   Noisy   Operation   - Low water flow through the heat exchanger. • Refer to Section   6 - Hydronic Piping of the   Knight XL Installation and Operation Manual for   minimum flow rates. Verify that the boiler is piped in a   primary/secondary fashion and that the boiler and   system pump are running on a call for heat.   - Air in the piping system.   • Properly purge all air from the piping system.   • Verify system pressure is a minimum of 12 psi.   - Low system water pressure.   - Blown fuse.   No Pump   Operation -   Boiler Pump   System Pump   or   • Replace fuse F1 on the control board, see page 33 of   this manual.   Note: Make sure pump amperage does not exceed   1.8 amps.   DHW Pump   • Replace pump.   - Faulty pump.   - Internal fault on control board.   • Replace main control board.   - System pressure exceeds relief valve • Lower the system pressure below the 30 psi rating of   setting.   the supplied relief valve or replace the standard relief   valve with a higher rated valve up to the maximum   pressure of the heat exchanger.   Relief Valve   Opening   • Improperly sized expansion tank.   36   Service Manual   3 Troubleshooting   (continued)   Table 3-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Reset the pressure switches.   • Measure the supply gas pressure to determine cause   of failure. Natural gas pressures should be between   4 - 14 inches w.c. and LP gas pressures   should be between 8 - 14 inches w.c.   - Either the optional manual reset low gas   pressure switch or the optional manual reset • Refer to Section 7 - Gas Connections of the Knight   Gas Pressure SW   (will require a manual   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   high gas pressure switch tripped.   XL Installation and Operation Manual for detailed   information concerning the gas supply.   • Correct the supply gas pressure if necessary.   • Check for a loose or misplaced jumper if pressure   switches are not installed.   • Check for a loose or misplaced jumper on the Low   Voltage Connection Board.   - The gas pressure switch contacts on the   Low Voltage Connection Board are open.   • Check for the addition of a device wired across the   gas pressure switch terminals on the Low Voltage   Connection Board.   • Check boiler pump operation on a call for heat.   • Check for closed valves or obstructions in the boiler   piping.   Flow Switch/   LWCO   - Either the optional flow switch or the optional   low water cutoff is not making.   • Verify system is full of water and all air has been   purged from the system.   (will require a manual   reset once condition has   been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • Check for loose or misplaced jumpers if flow switch or   LWCO is not installed.   • Replace fuse F3 on the control board, see page 33   of this manual.   - Blown fuse.   • Check condensate tube from unit to floor drain for   proper installation and obstructions.   Blocked Drain SW   (will require a manual   reset once condition has   been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • Inspect condensate trap for blockage. Clean if   necessary.   The blocked drain switch has detected   excessive condensate build up inside the   unit.   • Check for loose wiring connection at wire harness   plug.   • Bad blocked drain switch. Replace switch.   37   Service Manual   3 Troubleshooting   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   APS:   • Check the wiring connections to switch. Wires should   be connected to the common and normally closed   terminals.   • Air intake lengths exceed the maximum allowed   lengths. Refer to Section 3 - General Venting of the   Knight XL Installation and Operation Manual for   proper lengths.   • Check for obstruction or blockage in the air   intake pipes or at terminations.   APS / HEX   Temp Sw   • Check reference hoses connected to the air pressure   switch for blockage or obstruction.   Open   • Inspect the burner. Reference page 31 of this manual   for removal and cleaning procedures. Replace if   necessary.   Either the air pressure switch contacts are   open, or the O-temp heat exchanger switch   has opened.   (will require a manual   reset once the condition   has been corrected.   Press the RESET button   on the SMART SYSTEM   display to reset.)   • Inspect the heat exchanger. Reference page 32 of   this manual for removal and cleaning procedures.   Replace if necessary.   • Faulty air pressure switch. Replace switch.   O-TEMP HEX SWITCH   • Inspect the back of the inner combustion chamber at   burner level for refractory breakdown / missing.   Replace heat exchanger if refractory is broken and unit   has fired.   • Check continuity across two contacts. Wires should be   connected at both poles of the normally closed switch.   • Faulty O-Temp HEX Switch. Replace switch.   • The control board will release the call for heat after a   set time period.   The main control board has received a call   for heat too quickly after the previous call for   heat has ended.   Anti-cycling   • The control board will release the call for heat if the   outlet temperature drops too quickly.   • Inspect spark electrode and associated wiring for   damage and connection. Reference page 31 of this   manual for removal and cleaning procedures.   Replace if necessary.   Flame Fail Ign   (will require a manual   reset once the condition   has been corrected.   Press the RESET button   on the SMART SYSTEM   display to reset.)   • Check for proper electrical grounding of the unit.   The unit has failed to prove main burner   ignition after four (4) attempts.   • Check incoming supply gas pressure. Natural gas   pressures should be between 4 - 14 inches w.c. and   LP gas pressures should be between 8 - 14 inches w.c.   Refer to Section 7 - Gas Connections of the Knight   XL Installation and Operation Manual for detailed   information concerning the gas supply.   38   Service Manual   3 Troubleshooting   (continued)   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   The unit has failed to prove main burner • Verify that the plastic hose from the gas valve to the air   ignition after four (4) attempts.   inlet is connected and is not damaged.   • Verify that the vent/air intake pipes are correctly   installed and that there are no obstructions.   • Check for 24 vac to the gas valve at the 2-pin   connection on the side of the main control board during   the ignition attempt. If no voltage is present, replace   the main control board.   • If 24 vac is present at the main control board, check   the wiring between the main control board and the gas   valve. Replace the wiring if necessary. Do not   disconnect the wiring from the gas valve and attempt to   measure voltage at that point. The main control board   can detect if the gas valve is not connected and will   display the Gas Valve or Gas Valve Fail fault.   Flame Fail Ign   (cont’d)   (will require a manual   reset once the condition   has been corrected.   Press the RESET button   on the SMART SYSTEM   display to reset.)   • If 24 vac is present, check the outlet of the valve to   ensure the valve is flowing gas. With a manometer   connected to the outlet tap of the gas valve, when the   unit is in the prepurge period, there should be a   negative pressure present.   When the valve is   energized a change in pressure should occur. If the   pressure change does not occur, the gas valve is not   opening. Replace the gas valve.   • Inspect flame sensor and associated wiring.   Reference page 31 of this manual for removal and   cleaning procedures. Replace if necessary.   • Inspect and clean the heat exchanger as necessary.   Reference page 32 of this manual for cleaning   procedures.   • Inspect the burner. Reference page 31 of this manual   for removal and cleaning procedures. Replace if   necessary.   • Replace the main control board.   Flame Sequence   (will require a manual   reset once the condition   has been corrected.   Press the RESET button   on the SMART SYSTEM   display to reset.)   • Check supply voltage for proper polarity.   • Check external wiring for voltage feedback.   • Check the flame rod and make sure it is clean.   • Check the internal wiring for bad connections.   • Replace main control board.   The flame detector circuit is seeing a flame   signal while no flame is present.   39   Service Manual   3 Troubleshooting   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Adjust the set point of the auto reset limit to a higher   setting up to a maximum of 200°F. Reference the   Knight XL Installation and Operation Manual for   adjusting procedures.   • Verify that the system is full of water and that all air   has been properly purged from the system.   • Verify that the boiler is piped properly into the heating   system. Refer to Section 6 - Hydronic Piping of the   Knight XL Installation and Operation Manual   for the proper piping methods for the Knight XL boiler.   • Check 120 vac to boiler pump motor on a call for   heat. If voltage is not present, check wiring back to   the main control board.   The outlet water temperature has exceeded   the setting of the automatic reset high limit.   • Replace the main control board if necessary.   Outlet ARHL   • If 120 vac is present on a call for heat and the boiler   pump is not operating, replace the pump.   • If the system pump is a variable speed pump, ensure   that the system flow is not less than the boiler flow.   • If operating on something other than an outlet sensor,   check temperature setting of the main control board.   • If the optional manual reset high limit has tripped,   check setting of the device.   • Check resistance of water sensors and compare to   Table 3-2A on page 35 of this manual. Replace   sensor if necessary.   • Replace high limit.   • Adjust the set point of the manual reset limit to a higher   setting up to a maximum of 210°F. Reference the   Knight XL Installation and Operation Manual for   adjusting procedures.   Outlet MRHL   (will require a manual   reset once the condition   has been corrected.   Press the RESET   button on the SMART   SYSTEM display to   reset.)   • Verify that the system is full of water and that all air   has been properly purged from the system.   The outlet water temperature has exceeded   the setting of the manual reset high limit.   • Verify that the boiler is piped properly into the heating   system. Refer to Section 6 - Hydronic Piping of the   Knight XL Installation and Operation Manual   for the proper piping methods for the Knight XL boiler.   • Check 120 vac to boiler pump motor on a call for   heat. If voltage is not present, check wiring back to   the main control board.   40   Service Manual   3 Troubleshooting   (continued)   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Replace the main control board if necessary.   • If 120 vac is present on a call for heat and the boiler   pump is not operating, replace the pump.   Outlet MRHL   (cont’d)   • If the system pump is a variable speed pump, ensure   that the system flow is not less than the boiler flow.   (will require a manual   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • If operating on something other than an outlet sensor,   check temperature setting of the main control board.   The outlet water temperature has exceeded   the setting of the manual reset high limit.   • If the optional manual reset high limit has tripped,   check setting of the device.   • Check resistance of water sensors and compare to   Table 3-2A on page 35 of this manual. Replace   sensor if necessary.   • Replace high limit.   • Vent/air intake lengths exceed the maximum allowed   lengths. Refer to Section 3 - General Venting of the   Knight XL Installation and Operation Manual for   proper lengths.   Fan Low/High   OR   • Check for obstruction or blockage in the vent/air   intake pipes or at terminations.   Fan Speed Low/ The actual fan RPM is 30% lower than what   is being called for.   High   (will require a manual   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • Check the wiring connections at the fan and at the   main control board.   • Replace the fan.   • Replace the main control board.   • Replace fuse F2 on the control board, see page 33   of this manual.   Blown fuse.   • Check wiring harness connection at the gas valve and   at the main control board.   GV/Relay   Fail   (will require a manual   • Replace the gas valve wire harness.   • Replace the gas valve.   The main control board did not detect the   gas valve.   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • Replace the main control board.   • Check the sensors and their associated wiring.   Repair or replace the sensor or wiring if damaged.   Sensor Open   (will require a manual   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   Either the inlet water or outlet water • Measure the resistance of the sensors and compare   temperature sensor has been disconnected.   the resistance to the tables on page 35 of this   manual.   • Replace the sensor if necessary.   41   Service Manual   3 Troubleshooting   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Check the sensors and their associated wiring.   Repair or replace the sensor or wiring if damaged.   Sensor Shorted   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   Either the inlet water or outlet water • Measure the resistance of the sensors and compare   temperature sensor has been shorted.   the resistance to the tables on page 35 of this   manual.   SYSTEM display to reset.)   • Replace the sensor if necessary.   Louver Proving   Sw   • Check function of remote devices.   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   SYSTEM display to reset.)   An optional remote proving switch is not   making.   • Check for loose or misplaced jumper if auxiliary   proving switch is not installed.   • Check wiring to sensor.   connected and not damaged. Reconnect / repair   wiring if necessary.   Make sure wiring is   Inlet Sensor   Fault   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   SYSTEM display to reset.)   The control reads the inlet sensor as open   or shorted.   • Measure the resistance of the sensor and compare to   the resistance in Table 3-2A on page 35 of this manual.   Replace sensor if necessary.   • Replace control module.   • Check wiring to sensor.   connected and not damaged. Reconnect / repair   wiring if necessary.   Make sure wiring is   Outlet Sensor   Fault   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   SYSTEM display to reset.)   The control reads the inlet sensor as open   or shorted.   • Measure the resistance of the sensor and compare to   the resistance in Table 3-2C on page 35 of this manual.   Replace sensor if necessary.   • Replace control module.   • Check wiring to sensor.   Make sure wiring is   connected and not damaged. Reconnect / repair   wiring if necessary.   Outlet Temp Diff   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   • Measure the resistance of the sensor and compare to   the resistance in Table 3-2C on page 35 of this manual.   Replace sensor if necessary.   The control module reads an excessive   temperature difference between the two   sensors.   • Restore control parameter defaults from optional PC   software.   SYSTEM display to reset.)   • Replace control module.   42   Service Manual   3 Troubleshooting   (continued)   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Check wiring to sensor. Make sure wiring is   connected and not damaged. Reconnect / repair   wiring if necessary.   Flue Sensor Fault   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   The control reads the flue sensor as open   or shorted.   • Measure the resistance of the sensor and compare   to the resistance in Table 3-2D on page 35 of this   manual. Replace the sensor if necessary.   SYSTEM display to reset.)   • Replace control module.   • Check wiring to sensor. Make sure wiring is   connected and not damaged. Reconnect / repair   wiring if necessary.   Flue Temp Diff   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   • Measure the resistance of the sensor and compare to   the resistance in Table 3-2D on page 35 of this   manual. Replace sensor if necessary.   The control module reads an excessive   temperature difference between the two   sensors.   • Restore control parameter defaults from optional PC   software.   SYSTEM display to reset.)   • Replace control module.   • Inspect the heat exchanger. Reference page 32 of   this manual for the procedure on how to clean the flue   side of the heat exchanger.   Flue Temp Limit   (will require a manual reset   once the condition has been   corrected. Press the RESET   button on the SMART   • Inspect the flue sensor and associated wiring.   Measure the resistance of the flue sensor and   compare to Table 3-2D on page 35 of this manual.   Replace the sensor if necessary.   The stack temperature has exceeded the   Flue Temp Limit set parameters.   SYSTEM display to reset.)   • Verify that the vent/air intake pipes are properly   installed and that there are no obstructions.   • Replace the main control board.   • Restore the parameter defaults from the optional PC   software.   The control module has detected parameter   settings that are out of range.   Fatal Error   • Replace control module.   • Reset control module.   43   A lockout occurs at the same time as a   power outage.   Memory Error   Service Manual   3 Troubleshooting   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Inspect the heat exchanger. Reference page 32 of   this manual for the procedure on how to clean the flue   side of the heat exchanger.   • Inspect the flue sensor and associated wiring.   Measure the resistance of the flue sensor and   compare to Table 3-2D on page 35 of this manual.   Replace the sensor if necessary.   The stack temperature has exceeded the set   parameters for the boiler.   Flue Temp High   • Verify that the vent/air intake pipes are properly   installed and that there are no obstructions.   • Replace the main control board.   • Verify that the system is full of water and that all air   has been properly purged from the system.   • Verify that the boiler is piped properly into the heating   system. Refer to Section 6 - Hydronic Piping of the   Knight XL Installation and Operation Manual   for the proper piping methods for the Knight XL boiler.   • Check for 120 vac to the boiler pump motor on a call   for heat. If voltage is not present, check the wiring   back to the main control board. Replace the main   control board if necessary.   Delta T High   The temperature rise across the heat   exchanger has exceeded the set parameters   for the boiler.   • If 120 vac is present on a call for heat and the boiler   pump is not operating, replace the pump.   • Verify that the boiler pump is set to the proper speed   or that the pump is the proper size. Reference   Section   6 - Hydronic Piping of the Knight   XL Installation and Operation Manual for boiler   pump specifications.   • Verify that the system is full of water and that all air   has been properly purged from the system.   • Verify that the boiler is piped properly into the heating   system. Refer to Section 6 - Hydronic Piping of the   Knight XL Installation and Operation Manual   for the proper piping methods for the Knight XL boiler.   • Check for 120 vac to the boiler pump motor on a call   for heat. If voltage is not present, check wiring back   to the main control board. Replace the main control   board if necessary.   Outlet Temp   High   Outlet water temperature has exceeded the   maximum outlet water temperature.   • If 120 vac is present on a call for heat and the boiler   pump is not operating, replace the pump.   • Verify that the boiler pump is set to the proper speed   or that the boiler pump is the proper size. Reference   Section 6 - Hydronic Piping of the Knight XL   Installation and Operation Manual for boiler pump   specifications.   • Replace the main control board.   44   Service Manual   3 Troubleshooting   (continued)   Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface   FAULT   DESCRIPTION   CORRECTIVE ACTION   • Check set point of the external control.   • Check the wiring between the external control and the   unit.   Rem Ctrl Flt   External control is cycling too often.   • Replace the control.   Parameters   Progr   (will require a manual   reset once the condition   has been corrected. Press   the RESET button on the   SMART SYSTEM display   to reset.)   • Press the ENTER/RESET button on the SMART   SYSTEM display panel.   After downloading parameters from a laptop,   the main control board must be reset.   • Establish a heating load to remove the heat from the   boiler loop.   • Verify that the system is full of water and that all air   has been properly purged from the system.   • Verify that the boiler is piped properly into the heating   system. Refer to Section 6 - Hydronic Piping of the   Knight   XL   Installation   and   Operation   Manual for the proper piping methods for the Knight   XL boiler.   While the unit is in Service Mode, the outlet   temperature has exceeded 185°F.   • Check 120 vac to the boiler pump motor on a call for   heat. If voltage is not present, check the wiring back   to the main control board. Replace the main control   board if necessary.   Service Blk   • If 120 vac is present on a call for heat and the boiler   pump is not operating, replace the pump.   • Verify that the boiler pump is set to the proper speed   or that the boiler pump is the proper size. Reference   Section   6 - Hydronic Piping of the Knight   XL Installation and Operation Manual for boiler   pump specifications.   • Check 120 vac supply to the transformer.   • Check wiring connections at the low voltage   terminal strip.   120 vac input to the main control board has   dropped below 80 vac.   Low 24 vac   • Check the wire size/length to remote devices.   • Replace the transformer.   The main control board has detected an   internal fault.   • Replace the main control board.   • Replace the main control board.   Watch Dog Error   The main control board has detected an   internal fault.   Write EEProm   The main control board has detected an   internal fault.   • Replace the main control board.   CRC Parameters   The main control board has detected an   internal fault.   • Replace the main control board.   No Error Stored   45   Service Manual   3 Troubleshooting   Combustion Analysis Procedure   Table 3-5 Flue Products   Natural Gas   CO2 O2   8.0% - 10% 3.0% - 6.5% 9.0% - 11%   1. Turn the main power off to the boiler by placing the “On/   Off” switch in the OFF position.   Propane   CO2   O2   2. Remove the flue temperature sensor from the flue pipe   connection. Note: Combustion measurements will be   made at this point.   4.1% - 6.9%   8. Once the combustion analysis is complete, test the safety   shutoff device by turning the manual shutoff valve to the   OFF position and ensuring that the boiler shuts down   and registers an alarm. Open the manual shutoff valve,   reset the control, and return to Service Mode.   3. Turn the main power on to the boiler by placing the   “On/Off” switch in the ON position.   4. Place the boiler into the active position by pressing the   RIGHT SELECT [ON] key (see page 7).   9. Turn the main power off to the boiler and replace the flue   temperature sensor into the flue pipe connection.   5. Locate the pinhole button below the RESET button on   the display board (see page 7). Insert a thin wire (such as   a paper clip) into the hole and press the button once and   hold for 5 seconds to place the boiler into Service Mode.   In Service Mode the boiler will fire at ignition speed and   will then modulate up to full fire.   10. Place the boiler back into normal operation.   You must replace the flue gas temperature   ƽ WARNING   sensor to prevent flue gas spillage into   the room. Failure to comply could result   in severe personal injury, death, or   substantial property damage.   6. Remove the flue temperature sensor. Insert the probe   from a combustion analyzer into the hole left by the   removal of the flue temperature sensor.   7. Once the boiler has modulated up to full fire, measure   the combustion. The values should be in the range listed   in Table 3-5 above. The CO levels should be less than   150 ppm for a properly installed unit.   If the combustion is not within the specified range,   reference the chart below for possible causes and   corrective actions.   Table 3-6 Troubleshooting Chart - Combustion Levels   POSSIBLE CAUSE   CORRECTIVE ACTION   • Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual   for the proper venting and air intake methods for the Knight XL boiler.   Vent/Air Intake Length   or Obstruction   • Check for obstructions at the vent/air intake terminals.   • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation   Manual for the proper gas supply for the Knight XL boiler.   Gas Supply Pressure   • Refer to page 31 of this manual for burner removal and cleaning procedures.   • Replace burner if necessary.   Dirty/Damaged Burner   Gas Valve Adjustment   • Refer to page 47 of this manual for the gas valve adjustment procedure.   46   Service Manual   3 Troubleshooting   (continued)   Gas valve adjustment procedure   Figure 3-3 Gas Valve Adjustment: Model 501   If adjustment of the gas valve is deemed necessary, use the   following procedures: (Note: The procedures below are   model specific.)   Under normal operating conditions this   valve should not need adjusting.   CAUTION   Model 400   Locate the throttle adjustment screw on the top of the gas   valve, see FIG. 3-2. Using a screwdriver, turn the screw 1/8   turn counterclockwise to increase CO2 levels or 1/8 turn   clockwise to decrease CO2 levels. After one adjustment on   the valve, follow the Combustion Analysis Procedure on   page 46 of this manual to measure the combustion.   If combustion is still not within the specified range,   repeat the procedure. This procedure SHOULD NOT   be performed more than four (4) times. If after four (4)   adjustments and the combustion is still not within the   specified range, revisit the possible causes in Table 3-6 on   page 46 or replace the gas valve.   Models 601 - 801   Locate the throttle adjustment screw on top of the gas valve,   see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4   turn counterclockwise to increase CO2 levels or a 1/4 turn   clockwise to decrease CO2 levels. After one adjustment on the   valve, follow the Combustion Analysis Procedure on page 46   of this manual to measure the combustion.   Figure 3-2 Gas Valve Adjustment: Model 400   THROTTLE ADJUSTMENT   SCREW   If combustion is still not within the specified range, repeat   the procedure. This procedure SHOULD NOT be performed   more than four (4) times. If after four (4) adjustments and   the combustion is still not within the specified range, revisit   the possible causes in Table 3-6 on page 46 or replace the gas   valve.   Figure 3-4 Gas Valve Adjustment: Models 601 - 801   Model 501   THROTTLE   ADJUSTMENT   SCREW   Locate the throttle adjustment screw on top of the gas valve,   see FIG. 3-3. Using a screwdriver, turn the screw a 1/4 turn   counterclockwise to increase CO2 levels or a 1/4 turn   clockwise to decrease CO2 levels. After one adjustment on   the valve, follow the Combustion Analysis Procedure on   page 46 of this manual to measure the combustion.   (REMOVE BLUE CAP)   If combustion is still not within the specified range,   repeat the procedure. This procedure SHOULD NOT   be performed more than four (4) times. If after four (4)   adjustments and the combustion is still not within the   specified range, revisit the possible causes in Table 3-6 on   page 46 or replace the gas valve.   47   Revision Notes: Revision A (ECO #C05747) initial release. Reflects   the new model numbers for the Knight XL upgrade.   Revision B (ECO #C06234) reflects changes made to the Service   Notification parameter.   Revision C (ECO #C07981) reflects changes made to the parameter   table, parameter descriptions, updates to the troubleshooting chart, and   the addition of the O-temp HEX switch. .   KBXII-SER Rev C   5/11   |