Emerson Process Management HF300 User Manual

Instruction Manual  
Form 5715  
June 2007  
HF300 Series  
FIELDVUER HF300 Series HARTR Filters  
Introduction  
FIELD INSTRUMENT CONNECTIONS (FLD)  
Scope of Manual  
This instruction manual includes installation and  
R
maintenance information for the FIELDVUE HF300  
R
Series HART Filters. Refer to separate manuals for  
additional information on other FIELDVUE products  
used with the HART filters, such as DVC6000 Series  
digital valve controllers, and Type 2530H1 HART  
interchange multiplexers.  
HART COMMUNICATION  
CONNECTIONS (COMM)  
Control system refers to a distributed control system  
(DCS), programmable logic controller (PLC), or a  
stand-alone controller that provides a control signal  
to the FIELDVUE instrument.  
CONTROL SYSTEM  
CONNECTIONS (SYS)  
Do not install, operate, or maintain HF300 Series  
HART filters without first D being fully trained and  
qualified in valve, actuator and accessory  
W8283 / IL  
installation, operation and maintenance and  
D
carefully reading and understanding the contents of  
the manual. If you have any questions about these  
instructions, contact your Emerson Process  
R
R
Figure 1. FIELDVUE HF300 Series HART Filters  
Managementt sales office before proceeding.  
The Type HF340 HART filter is a passive device that  
is inserted in-line with both wires of a HART 4 to 20  
mA DC output loop. The purpose of the filter is to  
effectively isolate the control system analog output  
from modulated HART communication signals. The  
filter receives a 4 to 20 mA DC current signal from  
the control system, which it shunts with a capacitor  
and then passes through an inductor. The low AC  
impedance of the capacitor prevents sudden  
changes in the control system current output from  
interfering with the HART communication. The high  
AC impedance of the inductor permits HART  
communication on the instrument side of the filter. It  
also prevents the voltage modulation in the HART  
loop from being seen by, or having an affect on, the  
control system output. The filter introduces a  
maximum input-to-output voltage drop of 2 volts DC  
at 20 mA as long as the output load voltage is less  
than 14 volts DC.  
Description  
used with HART-based FIELDVUE instrumentation,  
such as DVC6000 Series digital valve controllers.  
These filters are used when this instrumentation is  
connected to a 4 to 20 mA DC control system output  
that was not designed for the HART (Highway  
Addressable Remote Transducer) communication  
protocol.  
The HF300 Series HART filters consist of the Type  
HF340 HART filter that provides filtering and  
isolation between the control system and FIELDVUE  
instrument and the Type HF341 communication tap.  
The Type HF341 does not provide any filtering. It is  
simply a straight through device that provides a  
convenient connection for HART communication.  
 
Instruction Manual  
Form 5715  
June 2007  
HF300 Series  
HART MULTIPLEXER NETWORK  
TYPE 2530H1 HART INTERCHANGE  
MULTIPLEXER OR OTHER HART  
MULTIPLEXER  
COMM TERMINALS  
SYS TERMINALS  
FIELD  
DEVICES  
FLD TERMINALS  
+
+
+
HF300 SERIES HART FILTER  
+
+
+
375 FIELD  
COMMUNICATOR  
CONTROL  
SYSTEM OUTPUT  
TERMINALS  
Figure 2. Typical HF300 Series HART Filter Installation  
Shields  
Installation  
If using shielded wiring on both sides of the filter, the  
shield should connect across the filter. If the filter  
connects directly to the control system output and  
shielded loop wiring is being used, connect the  
shield to system ground on the instrument side of  
the filter.  
Series filters mount on a type 35 DIN rail. To install  
the filter, provide a temporary means of process  
control, then take the loop out of service. Remove  
the DIN interconnect blocks from the rail without  
disconnecting existing wiring. Install the filter on the  
rail. Disconnect the wires from the control system  
output side of the interconnect blocks and connect  
them to the SYS terminals on the filter, taking care to  
maintain correct polarity. Disconnect the wires from  
the field side of the interconnect blocks and connect  
them to the FLD terminals on the filter, taking care to  
maintain correct polarity.  
HART Wiring Connections  
The COMM terminals on the filter provide a  
convenient means to tap into the loop wiring for  
HART communication. A HART Interchange  
multiplexer or the 375 Field Communicator can be  
connected to these terminals, or they may be left  
with no connections.  
3
 
Instruction Manual  
Form 5715  
June 2007  
HF300 Series  
problem that may appear initially to be a filter  
Corrective Maintenance  
malfunction. For the filter to operate properly, the  
control system must have a compliance voltage that  
is at least 2 volts higher than the voltage required to  
drive the loop to maximum current. Refer to the  
appropriate instrument instruction manual for  
information on determining the control system  
compliance voltage.  
The most likely malfunction of a loop containing an  
HF300 Series HART filter is reverse polarity  
installation of one of the wire pairs. The Type HF340  
filter will work with either polarity, but misconnection  
could result in the wrong polarity reaching the field  
instrument. If the loop is not operating properly,  
check the polarity of the voltage at the inputs and  
outputs of the filter and at the inputs of the  
instrument.  
Excessive load voltage will interfere with filter  
operation. A transient clamping device limits the  
output voltage to a nominal 15 volts. If the voltage at  
the output (due to the total impedances connected)  
is greater than 14 volts DC at maximum loop current,  
some of the current may be shunted by the clamping  
device.  
If the instrument appears to operate properly in the  
loop, but communication with a non-isolated  
multiplexer or PC modem is not possible, it may help  
to reverse the wires to the COMM terminals. The  
Type HF340 filter inserts a high impedance in the +  
side of the loop only. A reversal of the connections  
to the SYS and FLD terminals of the filter will result  
in the control loop operating properly, but inoperative  
HART communication.  
The Type HF340 filter is protected against accidental  
over-current from sources up to 30 volts DC. If an  
over-current condition occurs, the filter may be  
inoperative for several seconds thereafter.  
Inadequate control system compliance voltage will  
not support filter operation. This is an installation  
Fisher and FIELDVUE are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of  
Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.  
HART is a mark owned by the HART Communication Foundation. All other marks are the property of their respective owners.  
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are  
not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.  
We reserve the right to modify or improve the designs or specifications of such products at any time without notice.  
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use and  
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.  
Emerson Process Management  
Marshalltown, Iowa 50158 USA  
Cernay 68700 France  
Sao Paulo 05424 Brazil  
Singapore 128461  
E
F
i
s
h
e
r
C
o
n
t
r
o
l
s
I
n
t
e
r
n
a
t
i
o
n
a
l
L
L
C
2
0
0
1
,
2
0
0
7
;
A
l
l
R
i
g
h
t
s
R
e
s
e
r
v
e
d
P
r
i
n
t
e
d
i
n
U
S
A

AGFA sensor 510 X User Manual
Behringer Car Speaker B812NEO User Manual
Blaupunkt IVMR 7001 User Manual
Blaupunkt IVSC 5502 User Manual
Chromalox CHPES 6A User Manual
Clarion TTX 7503Z TTX7503Z User Manual
Harman Kardon Car Stereo System User Manual
Heat Glo LifeStyle COSMO I30 User Manual
JVC Adixxion Digital Camcorder GC XA1BUS User Manual
JVC CS D3000 User Manual