Ariston Boiler 41 116 07 User Manual

Installation  
Instructions  
Type C Boilers  
G.C.N: 41-116-06  
41-116-07  
LEAVE THESE INSTRUCTIONS  
WITH THE END-USER  
Country of destination: GB  
This manual is an integral and essential part of the product. It should be kept  
with the appliance so that it can be consulted by the user and our authorised  
personnel.  
1.  
GENERAL  
INFORMATION  
Please carefully read the  
instructions and notices about the  
unit contained in this manual, as  
they provide important information  
regarding the safe installation, use  
and maintenance of the product.  
For operating instructions please  
consult the separate User’s Manual.  
Read the instructions and recommendations in these Installation Instructions  
carefully to ensure proper installation, use and maintenance of the  
appliance.  
1.1  
GENERAL INSTRUCTIONS  
Keep this manual in a safe place. You may need it for your own reference  
while our Servicing Centre technicians or your installer may need to consult  
it in the future.  
This is an appliance for the production of central heating (C.H.).  
This appliance must be used only for the purpose for which it is designed.  
The manufacturer declines all liability for damage caused by improper or  
negligent use.  
No asbestos or other hazardous materials have been used in the fabrication  
of this product.  
Before connecting the appliance, check that the information shown on the  
data plate and the table in section 7 comply with the electric, water and gas  
mains of the property.You will find the data plate on the reverse of the control  
panel.  
The gas with which this appliance operates is also shown on the label at the  
bottom of the boiler.  
Do not install this appliance in a damp environment or close to equipment  
which spray water or other liquids.  
Do not place objects on the appliance.  
Do not allow children or inexperienced persons to use the appliance without  
supervision.  
If you smell gas in the room, do not turn on light switches, use the  
telephone or any other object which might cause sparks.  
Open doors and windows immediately to ventilate the room.  
Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the  
gas cylinder and call your Gas Supplier immediately.  
If you are going away for a long period of time, remember to shut the mains  
gas tap or the gas cylinder valve.  
Always disconnect the appliance either by unplugging it from the mains or  
turning off the mains switch before cleaning the appliance or carrying out  
maintenance.  
In the case of faults or failure, switch off the appliance and turn off the gas  
tap. Do not tamper with the appliance.  
For repairs, call your local Authorised Servicing Centre and request the use  
of original spare parts. For in-guarantee repairs contact MTS (GB) Limited.  
Check the following at least once a year:  
1 - Check the seals for the water connections; replace any faulty seals.  
2 - Check the gas seals; replace any faulty gas seals.  
3 - Visual check of the entire unit.  
3
4 - Visual check of the combustion process or analysis of combustion by-  
products (see section 4.5) and cleaning of the burner if needed.  
5 - If called for by point. 3, dismantling and cleaning of the combustion  
chamber.  
6 - If called for by point. 4, dismantling and cleaning of the burner jets.  
7 - Visual check of the primary heat exchanger:  
-
-
check for overheating in the blade assembly;  
clean the exhaust fan if needed.  
8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load  
and full load.  
9 - Check of the heating safety systems:  
-
-
safety device for maximum temperature (overheat thermostat);  
safety device for maximum pressure (safety valve).  
10- Check of the gas safety systems:  
-
safety device for lack of gas or flame ionisation (detection  
electrode);  
-
safety device for gas cock.  
11- Check of the electrical connection (make sure it complies with the  
instructions in the manual).  
12- General check of the combustion by-products of the  
discharge/ventilation system.  
13- Check of the general performance of the unit.  
FIG. 1.0  
1.2  
OVERALL VIEW  
LEGEND:  
1.  
2.  
3.  
Flue connector  
Air intake for twin pipe flue systems  
Fan  
4.  
5.  
6.  
Combustion chamber hood  
Main heat exchanger  
Safety thermostat  
7.  
8.  
9.  
Combustion chamber  
Combustion chamber insulation panel  
Detection electrode  
Ignition electrodes  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
Burner  
Regulation thermostat  
Frost thermostat  
Pump pressure switch  
Safety valve (3 bar)  
Automatic By-pass  
Gas valve  
Spark generator  
Boiler drain valve  
Circulation pump with automatic air release valve  
Expansion vessel  
Air pressure take-off point  
Air pressure switch  
Combustion analysis points  
4
The technical information and instructions provided herein below are  
intended for the installer so that the unit may be installed correctly and  
safely.  
2.  
INSTALLATION  
The installation and initial start up of the boiler must be by a CORGI  
Registered Installer in compliance with the installation standards currently in  
effect, as well as with any and all local health and safety standards i.e.  
CORGI .  
2.1  
REFERENCE STANDARDS  
This appliance must be installed by a competent installer in  
accordance with current Gas Safety (installation & use)  
Regulations.  
The installation of this appliance must be in accordance with the relevant  
requirements of the current Gas Safety (installation & use) Regulations, the  
Local Building Regulations, the current I.E.E. Wiring Regulations, the  
byelaws of the local water authority, and in Scotland, in accordance with the  
Building Standards (Scotland) Regulation and Health and Safety document  
No. 635 “Electricity at work regulations 1989”.  
Installation should also comply with the following British Standard Codes of  
Practice:  
BS 7593:1992 Treatment of water in domestic hot water central  
heating systems  
BS 5546:1990 Installation of hot water supplies for domestic  
purposes  
BS 5440-1:1990 Flues  
BS 5440-2:1989 Air supply  
BS 5449:1990 Forced circulation hot water systems  
BS 6789:1987 Installation of gas fired hot water boilers of rated  
input not exceeding 60kW  
BS 6891:1989 Installation of low pressure gas pipe up to 28mm  
BS 7671:1992 IEE wiring regulations  
BS 4814:1990 Specification for expansion vessels  
BS 5482:1994 Installation of LPG  
2.2  
SITING THE APPLIANCE  
The appliance may be installed in any room or indoor area, although  
particular attention is drawn to the requirements of the current I.E.E. Wiring  
Regulations, and in Scotland, the electrical provisions of the Building  
Regulations applicable in Scotland, with respect to the installation of the  
appliance in a room containing a bath or shower.  
Where a room-sealed appliance is installed in a room containing a bath  
or shower the appliance and any electrical switch or appliance control,  
utilising mains electricity should be situated so that it cannot be  
touched by a person using the bath or shower.  
The location must permit adequate space for servicing and air circulation  
around the appliance as indicated in paragraph 2.4.  
The location must permit the provision of an adequate flue and termination.  
For unusual locations special procedures may be necessary.  
BS 6798-1987 gives detailed guidance on this aspect.  
A compartment used to enclose the appliance must be designed specifically  
for this purpose. No specific ventilation requirements are needed for the  
installation within a cupboard.  
This appliance is not suitable for outdoor installation.  
The type C appliances (in which the combustion circuit, air vent intake  
and combustion chamber are air-tight with respect to the room in  
which the appliance is installed) can be installed in any type of room.  
Secondary ventilation is not required with this boiler. The boiler must be  
installed on a solid, permanent wall to prevent access from the rear.  
5
2.3  
OVERALL DIMENSIONS  
LEGEND:  
60 mm  
A
C
E
= Central Heating Flow (3/4)  
= Gas Inlet (3/4)  
= Central Heating Return (3/4)  
mm = Clearances  
2.4  
CLEARANCES  
450 mm  
In order to allow for access to the interior of the boiler for  
maintenance purposes, the boiler must be installed in  
compliance with the minimum clearances indicated in FIG. 2.1  
2.5  
MOUNTING THE APPLIANCE  
132  
132  
Fasten the boiler in place using the template and anchors  
supplied with the unit. It is highly recommended that a  
spirit level be used to position the boiler so that it is  
perfectly level.  
C
E
FIG. 2.1  
For additional information, please consult the instructions  
contained in the connection kit and the flue kit.  
2.6  
ELECTRICAL CONNECTION  
For safety purposes, have a competent person carefully  
check the electrical system in the property, as the  
manufacturer will not be held liable for damage caused by  
the failure to earth the appliance properly or by anomalies  
in the supply of power. Make sure that the residential  
electrical system is adequate for the maximum power  
absorbed by the unit, which is indicated on the rating plate.  
In addition, check that the section of cabling is appropriate  
for the power absorbed by the boiler.  
N
L
E
The boiler operates with alternating current, as indicated in  
the technical information table in section 7, where the  
maximum absorbed power is also indicated. Make sure  
that the connections for the neutral and live wires  
correspond to the indications in the diagram. The  
appliance electrical connections are situated on the  
reverse of the control panel under the inspection cover  
(see the servicing manual for further information)  
FIG. 2.2  
IMPORTANT!  
In the event that the power supply cord must be changed,  
replace it with one with the same specifications. Make the  
connections to the terminal board located within the  
control panel, as follows:  
- The yellow-green wire should be connected to the  
terminal marked with the “  
symbol;  
- The blue wire should be connected to the terminal  
marked “N”;  
- The brown wire should be connected to the terminal  
6
marked L.  
Note: The diagrams for the electrical system are indicated in section 2.12.  
Warning, this appliance must be earthed.  
External wiring to the appliance must be carried out by a competent person  
and be in accordance with the current I.E.E. Regulations and applicable  
local regulations. The microSYSTEM range of boilers are supplied for  
connection to a 230 V~ 50 Hz supply.  
The supply must be fused at 3 A.  
The method of connection to the electricity supply must facilitate complete  
electrical isolation of the appliance, by the use of a fused double pole  
isolator having a contact separation of at least 3 mm in all poles or  
alternatively, by means of a 3 A fused three pin plug and unswitched  
shuttered socket outlet both complying with BS 1363.  
The point of connection to the Electricity supply must be readily accessible  
and adjacent to the appliance unless the appliance is installed in a bathroom  
when this must be sited outside the bathroom (see section 2.2).  
The local gas region contractor connects the gas meter to the service pipe.  
If the gas supply for the boiler serves other appliances ensure that an  
adequate supply is available both to the boiler and the other appliances  
when they are in use at the same time.  
Pipe work must be of an adequate size. Pipes of a smaller size than the  
boiler inlet connection should not be used.  
2.7  
2.8  
GAS CONNECTION  
VIEW OF THE BOILER CONNECTIONS  
WATER CONNECTIONS  
FIG. 2.4  
E
D
B
C
A
F
FIG. 2.3  
LEGEND:  
A = Central Heating Flow  
C = Gas Inlet  
E = Central Heating Return  
F = Safety Valve  
G = Pump transportation screw  
(remove before igniting the boiler)  
H = Automatic By-pass pipe  
CENTRAL HEATING  
Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990,  
the following notes are given for general guidance.  
7
PIPE WORK:  
Copper tubing to BS EN 1057:1996 is recommended for water pipes.  
Jointing should be either with capillary soldered or compression fittings.  
Where possible pipes should have a gradient to ensure air is carried  
naturally to air release points and water flows naturally to drain taps.  
The appliance has a built-in automatic air release valve, however it should  
be ensured as far as possible that the appliance heat exchanger is not a  
natural collecting point for air.  
Except where providing useful heat, pipes should be insulated to prevent  
heat loss and avoid freezing.  
Particular attention should be paid to pipes passing through ventilated  
spaces in roofs and under floors.  
BY-PASS:  
The appliance includes an automatic by-pass valve, which protects the main  
heat exchanger in case of reduced or interrupted water circulation through  
the heating system, due to the closing of thermostatic valves or radiator  
valves within the system.  
SYSTEM DESIGN:  
This boiler is suitable only for sealed systems.  
Drain Cocks:  
These must be located in accessible positions to permit the draining of the  
whole system and should be fitted at all low points. The taps must be at least  
15mm nominal size and manufactured in accordance with BS 2870:1980.  
SAFETY VALVE DISCHARGE:  
The discharge should terminate facing downward on the exterior of the  
building in a position where discharging (possibly boiling water & steam) will  
not create danger or nuisance, but in an easily visible position, and not  
cause damage to electrical components and wiring.  
The discharge must not be over an entrance or a window or any other type  
of public access.  
AIR RELEASE POINTS:  
These must be fitted at all high points where air naturally collects and must  
be sited to facilitate complete filling of the system.  
The appliance has an integral sealed expansion vessel to accommodate the  
increase of water volume when the system is heated.  
It can accept up to 6 litre (1.3 gal) of expansion water. If the heating circuit  
has an unusually high water content, calculate the total expansion and add  
an additional sealed expansion vessel with adequate capacity. This should  
be located on the return pipe work as close as possible to the pump inlet.  
MAINS WATER FEED - CENTRAL HEATING:  
There must be no direct connection to the mains water supply even through  
a non-return valve, without the approval of the Local Water Authority.  
FILLING:  
A temporary method for initially filling the system and replacing lost water  
during servicing and initial filling (in accordance with current Water  
Regulations), is provided as an integral part of the connection kit (see FIG.  
2.4). The flexible hose must be removed once the system has been filled.  
RESIDUAL HEAD OF THE BOILER  
8
FLUE SYSTEM  
2.9 FLUE CONNECTIONS  
The provision for satisfactory flue termination must be made in accordance  
with BS 5440-1.  
The appliance must be installed so that the flue terminal is exposed to outside air.  
The terminal must not discharge into another room or space such as an  
outhouse or lean-to.  
It is important that the position of the terminal allows a free passage of air  
across it at all times.  
The terminal should be located with due regard for the damage or  
discolouration that might occur on buildings in the vicinity.  
In cold or humid weather water vapour may condense on leaving the flue  
terminal.  
The effect of such plumingmust be considered.  
If the terminal is less than 2 metres above a balcony, above ground or above  
a flat roof to which people have access, then a suitable terminal guard must  
be fitted. When ordering a terminal guard, quote the appliance model  
number.  
A suitable terminal guard is available from:  
TOWER FLUE COMPONENTS  
Morley Road  
Tonbridge  
Kent TN9 1RA  
The minimum acceptable spacing from the terminal to obstructions and  
ventilation openings are specified in FIG. 2.5.  
TERMINAL POSITION  
mm  
A - Directly below an openable window or other opening  
B - Below gutters, soil pipes or drain pipes  
C - Below eaves  
D - Below balconies or car-port roof  
E - From vertical drain pipes and soil pipes  
F - From internal or external corners  
G - Above ground or balcony level  
H - From a surface facing a terminal  
I - From a terminal facing a terminal  
J - From an opening in the car port  
(e.g. door, window) into dwelling  
K - Vertically from a terminal in the same wall  
L - Horizontally from a terminal in the same wall  
300  
75  
200  
200  
75  
300  
300  
600  
1200  
BC  
F
G
F
D
J
HI  
A
E
1200  
1500  
300  
K
L
G
FIG. 2.5  
The boiler is designed to be connected to a coaxial flue discharge system.  
Ø 60/100 mm  
FIG. 2.6  
9
In addition, it is also possible to use a split (twin pipe)  
system by fitting a special adaptor to the flue connector  
and using the aperture for the air vent intake located on  
the top part of the combustion chamber.  
To utilise the air intake it is necessary to:  
1. Remove the bottom of the air intake by cutting it with a  
suitable knife (see FIG. 2.7);  
2. Insert the elbow into the air intake until it reaches the  
lower end. (There is no need to use gaskets or sealing  
compounds).  
FIG. 2.7  
Ø 80 mm  
FIG. 2.8  
IMPORTANT!  
COAXIAL SYSTEMS  
For all flue systems, a restrictor  
must always be inserted into the  
boilers flue connector; the  
restrictor must be Ø 46 or Ø 41 in  
diameter depending on the length  
of piping indicated in TABLE 2.1.  
FIG 2.9 and FIG 2.10 illustrate some  
of the various designs for coaxial or  
twin pipe flue systems.  
For further information on  
discharge/ventilation accessories,  
see the FLUE PIPE ACCESSORIES  
MANUAL.  
FIG. 2.9  
10  
TABLE 2.1  
Maximum  
Extension  
Exhaust/Air  
Risk of Condensation Forming  
Piping not insulated  
Piping insulated  
ø 46 restrictor NO restrictor ø 46 restrictor NO restrictor  
Exhaust  
Type  
Restrictor  
ø 46 mm  
21 RFFI  
C12 (xx)  
C32 (xx)  
C42 (xx)  
Coaxial  
Systems  
ø 60/100  
L min = 0.5 m  
L max = 1 m  
L = 4 m  
NONE  
NONE  
NONE  
NONE  
Maximum  
Extension  
Exhaust/Air  
Risk of Condensation Forming  
Piping not insulated  
Piping insulated  
ø 41 restrictor NO restrictor ø 41 restrictor NO restrictor  
Exhaust  
Type  
Restrictor  
ø 41 mm  
28 RFFI  
Coaxial  
Systems  
ø 60/100  
C12 (xx)  
C32 (xx)  
C42 (xx)  
L min = 0.5 m  
L max = 1 m  
L = 4 m  
NONE  
NONE  
NONE  
NONE  
Exhaust  
Type  
Restrictor  
ø 46 mm  
Maximum  
Extension  
Exhaust/Air  
Risk of Condensation Forming  
Piping insulated  
Piping not insulated  
21 RFFI  
ø 46 restrictor NO restrictor  
ø 46 restrictor NO restrictor  
C12 (xy)  
C32 (xy)  
C42 (xy)  
34 m  
34 m  
34 m  
L max = 25 m  
L max = 22 m  
12.5 m  
14.0 m  
16.0 m  
17.8 m  
3.0 m  
3.3 m  
4.5 m  
4.8 m  
Twin Pipe  
Systems  
ø 80/80  
C52 (xy)  
C82 (xy)  
31 m  
Exhaust  
Type  
Restrictor  
ø 41 mm  
Maximum  
Extension  
Exhaust/Air  
Risk of Condensation Forming  
Piping insulated  
Piping not insulated  
28 RFFI  
ø 41 restrictor NO restrictor  
ø 41 restrictor NO restrictor  
C12 (xy)  
C32 (xy)  
C42 (xy)  
62 m  
62 m  
62 m  
L max = 38 m  
L max = 34 m  
19 m  
19 m  
31 m  
31 m  
8 m  
8 m  
11 m  
11 m  
Twin Pipe  
Systems  
ø 80/80  
C52 (xy)  
C82 (xy)  
54 m  
In calculating the lengths of the pipes, the  
maximum length Lmust also take into  
consideration the values for the  
exhaust/air intake end terminals, as well  
as 90° elbows for coaxial systems.  
The C52 types must comply with the  
following requirements:  
TWIN PIPE  
SYSTEMS  
1 - The exhaust/ air intake pipes must  
have the same diameter of ø 80 mm.  
2 - If elbows are to be inserted into the  
air intake and/or exhaust system, the  
calculation of the overall length must  
take into consideration the values for  
each elbow, see the FLUE PIPE  
ACCESSORIES MANUAL.  
3 - The exhaust pipe must protrude by at  
least 0.5 m above the top of the roof  
in the event that it is located on the  
opposite side of the building to the  
side with the air intake (this condition  
is not obligatory when the air intake  
and exhaust are located on the same  
side of the building).  
FIG. 2.10  
11  
To connect a room thermostat and/or time clock, it is necessary to:  
2.10 ROOM THERMOSTAT  
CONNECTION  
1. - Open the control panel as indicated in section 4.3;  
2.- Remove screws Aand remove the inspection cover from the reverse of the control  
panel;  
3. - For the room-thermostat connect the thermostat switching wires to the position 5 and  
6 and remove the wire link (for three-wire thermostats connect the neutral to terminal  
N);  
4. - For the time clock connect the clock switching wires to the positions 3 and 4 and  
connect the clock motor electrical supply to the terminals marked L and N.  
Note: A frost thermostat is built-in to the appliance.  
For connection to control systems with zone valves for hot water cylinders  
see section 3.  
A
12  
2.11 ELECTRICAL DIAGRAM  
LEGEND:  
A11 - Overheat Thermostat  
A12 - Spark Generator/Gas Valve Supply  
A13 - Detection Electrode  
A - On/Off Switch  
B - On/Off L.E.D.  
C - Heating Switch  
D - Heating L.E.D.  
E - Reset Button  
Colours:  
Wh  
Bl  
-White  
-Blue  
F - Ignition Failure (Lockout) L.E.D.  
Gry  
Brn  
Blk  
Rd  
-Grey  
-Brown  
-Black  
-Red  
A01 - Pump Pressure Switch  
A02 - Frost Thermostat  
A03 - Modulator  
Grn/Yll-Yellow/Green  
A04 - Circulation Pump  
A05 - Regulation Thermostat  
A06 - External Control System  
A07 - Time Clock Connector  
A08 - External (Room) Thermostat  
A09 - Air Pressure Switch  
A10 - Fan  
FIG. 2.12  
13  
FIG. 2.13  
2.12 GAS AND WATER CIRCUITS  
FIG. 2.14  
LEGEND:  
1. Fan  
2. Main heat exchanger  
3. Overheat thermostat  
4. Burner  
5. Ignition electrodes  
6. Detection electrode  
7. Regulation thermostat  
8. Frost thermostat  
9. Gas valve  
17  
16  
1
2
3
4
10. Pump pressure switch  
11. Safety valve (3 bar)  
12. Boiler drain valve  
13. Automatic by-pass  
14. Pressure gauge  
15. Circulation pump with automatic  
air release valve  
5
6
7
16. Expansion vessel  
17. Air pressure switch  
8
9
15  
A. Central Heating Flow  
B. Inlet Gas  
C. Central Heating Return  
14  
13  
10  
11  
12  
14  
The microSYSTEM can be connected to a storage cylinder (both open-vented and  
unvented) for the production of domestic hot water (D.H.W.). Cylinders of different  
capacities can be used depending on site requirements (see TABLE 3.1 for a  
selection of ARISTON unvented cylinders).  
3.  
D.H.W. STORAGE  
CYLINDER  
3.1  
2 PORT AND 3 PORT VALVE  
INSTALLATIONS  
2 port valve installation  
3 port valve installation  
FIG. 3.1  
FIG. 3.3  
FIG. 3.2  
Wiring to 2 port valve installation  
using an external 2 channel  
programmer  
Type Danfoss FP715  
Type Honeywell ST6400C  
15  
Wiring to 3 port valve installation  
using an external 2 channel  
programmer  
Type Danfoss FP715  
Type Honeywell ST6400C  
NOTE: When using a 3 port valve installation in conjunction with an unvented cylinder it  
will be necessary to use a 2 port valve on the cylinder flow connection in addition  
to the 3- port valve to satisfy Building Regulations.  
FIG. 3.4  
TABLE 3.1  
Technical Data Capacity  
It.  
Coil  
C.H.W.  
D.H.W.  
Max Heating Heat Ioss  
Output  
Surface  
Flow/rate Flow/rate  
2
3
MODEL  
m
m /h  
It/h  
kW  
kWh/24h  
Contract STI 125 Indirect  
125  
0.75  
0.5  
1
2
194  
266  
340  
11.3  
15.5  
19.8  
2
Comfort STI 125 Indirect  
Contract STI 150 Indirect  
125  
150  
0.75  
0.93  
0.5  
1
2
256  
353  
451  
14.9  
20.5  
26.2  
2.2  
2.4  
Comfort STI 150 Indirect  
Contract STI 210 indirect  
150  
200  
0.93  
0.93  
0.5  
1
2
256  
353  
451  
14.9  
20.5  
26.2  
Comfort STI 210 Indirect  
Contract STI 300 Indirect  
200  
300  
0.93  
0.93  
0.5  
1
2
256  
353  
451  
14.9  
20.5  
26.2  
2.9  
SB 125 Indirect  
SB 150 Indirect  
SB 200 Indirect  
125  
150  
200  
1
1
0.5  
1
2
190  
318  
496  
11  
18.5  
28.8  
1.72  
1.75  
2.1  
0.5  
1
2
190  
318  
496  
11  
18.5  
28.8  
1.3  
0.5  
1
2
190  
318  
496  
11  
18.5  
28.8  
16  
3.2  
DOMESTIC HOT WATER  
PRIORITY KIT  
The microSYSTEM is able to be connected to a specially designed  
kit for the management of D.H.W. production. This kit gives priority to  
production of D.H.W. unlike traditional systems where the boiler  
power is split between C.H. and D.H.W. This generally enables a  
smaller storage cylinder to be chosen as the boilers full output will be  
channelled into the cylinder allowing for a quick heat-up.  
Boiler  
microSYSTEM  
21 RFFI  
microSYSTEM  
28 RFFI  
Cylinder  
Contract STI 125 Indirect  
Comfort STI 125 Indirect  
Contract STI 150 Indirect  
Comfort STI 150 Indirect  
Contract STI 210 Indirect  
Comfort STI 210 Indirect  
Contract STI 300 Indirect  
SB 125 Indirect  
The kit (ARISTON part number 706329) can be obtained from an  
ARISTON supplier.  
The kit consits of:  
1) Electronic module able to plug into the boilers P.C.B;  
2) 3-way priority valve with actuator for connection to the boilers  
flow outlet;  
3) A limit thermostat (80˚C) to check the water temperature of the  
heating flow to the cylinder, to be installed within the boiler;  
4) Pipes and accessories.  
SB 150 Indirect  
SB 200 Indirect  
TABLE 3.2  
= Ideal  
= Possible  
MTS (GB) Limited support the  
you will find a copy of the  
initiative. Within the information pack  
logbook. It is important that this is  
4.  
COMMISSIONING  
completed in the presence of your customer, they are shown how to use it,  
and it is signed by them. Please instruct your customer that they must have  
4.1  
INITIAL PREPARATION  
their  
logbook with them whenever they contact a service engineer  
or us.  
Preliminary electrical system checks to ensure electrical safety must be  
carried out by a competent person i.e. polarity, earth continuity, resistance to  
earth and short circuit.  
FILLING THE HEATING SYSTEM:  
Remove the panels of the case and lower the control panel (see section  
3.3 for further information).  
Open the central heating flow and return cocks supplied with the  
connection kit (there are two isolation points on the return connection).  
Unscrew the cap on the automatic air release valve one full turn and leave  
open permanently.  
Close all air release valves on the central heating system.  
Gradually open valve(s) at the filling point (filling-loop) connection to the  
central heating system until water is heard to flow, do not open fully.  
Open each air release tap starting with the lowest point and close it only  
when clear water, free of air, is visible.  
Purge the air from the pump by unscrewing anticlockwise and  
removing the pump plug and also manually rotate the pump shaft in  
the direction indicated by the pump label to ensure the pump is free.  
Refit the pump plug.  
Continue filling the system until at least 1.5 bar registers on the pressure  
gauge.  
Inspect the system for water leaks and remedy any leaks discovered.  
GAS SUPPLY:  
Inspect the entire installation including the gas meter, test for soundness  
and purge the supply as described in BS 6891:1988.  
Open the gas cock (supplied with the connection kit) to the appliance and  
check the gas connections on the appliance for leaks.  
17  
When the installation and filling are completed turn on the central heating  
system (section 4.4) and run it until the temperature has reached the boiler  
operating temperature. The system must then be immediately flushed  
through.  
The flushing procedure must be in line with BS 7593:1992 code of practice for  
treatment of water in domestic hot water central heating systems.  
During this operation, we highly recommend the use of a central heating  
flushing detergent (Fernox Superfloc or equivalent), whose function is to  
dissolve any foreign matter that may be in the system.  
Substances different from these could create serious problems to the  
pump or other components.  
The use of an inhibitor in the system such as Fernox MB-1 or equivalent is  
strongly recommended to prevent corrosion (sludge) damaging the boiler and  
system.  
Failure to carry out this procedure may invalidate the appliance  
warranty.  
4.2  
CONTROL PANEL  
LEGEND:  
A - On/ Off button  
B - On/ Off L.E.D. green (frost protection active)  
C - Central Heating button  
D - Cental Heating active L.E.D. green  
E - Ignition failure (lockout) and/ or overheat reset button  
F - Ignition failure (lockout) and/ or overheat L.E.D. red  
G - Central heating temperature adjustment  
H - Energy Saving System (ESS)  
I
- Knock-out for time clock  
FIG. 4.1  
J
- Heating system pressure gauge  
4.3  
REMOVING THE  
FRONT PANEL  
In order to access the inside of the boiler, it is necessary to  
unscrew the fastening screws Aof the control panel  
located on the lower part of the panel itself.  
1
The control panel moves downward and when pulled  
forward rotates on two lateral hinges.  
The panel stays in a semi-horizontal position, which allows  
access to the inner parts of the boiler.  
In order to increase the manoeuvring space, it is possible  
to raise the control panel and rotate it to a fully horizontal  
position.  
A
2
3
18  
4
5
B
To dismantle the front casing panel it is necessary to:  
1 - Remove the two screws B;  
2 - Move the front casing panel up and lift forward.  
THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS FOLLOWS:  
1. Make sure that:  
4.4 INITIAL START-UP  
-the screw on the automatic air valve has been loosened when the  
system is full;  
- If the water pressure in the system is below 1.5 bar, bring it up to the  
appropriate level;  
-Ensure that the gas cock is closed;  
-Make sure that the electrical connection has been made properly and  
that the earth wire is connected to an efficient earthing system;  
-Supply power to the boiler by pushing the On/Off button A(see  
FIG.4.1) - the L.E.D. Bwill illuminate. Then push the button Cin for  
central heating - the L.E.D. Dwill illuminate. This will start the  
circulation pump. After 7 seconds, the boiler will signal a shutdown due  
to ignition failure. Leave the boiler as it is until all of the air has been bled  
from the system.  
-Loosen the cap on the head of the pump to eliminate any air pockets;  
-Repeat the procedure for bleeding the radiators of air;  
-Check the system pressure and, if it has dropped, open the filling loop  
again to bring the pressure back up to 1.5 bar.  
2. Make sure that all gate valves are open;  
3. Turn on the gas cock and check the seals on the connections with an  
approved soap solution and eliminate any leaks.  
4. Press the reset button Efor the lighting system; the spark will light the  
main burner. If the burner does not light the first time, repeat the  
procedure.  
5. Check the minimum and maximum pressure values for the gas going to  
the burner; adjust it if needed using the values indicated in the table in  
section 5 (See the relative section for burner pressure adjustment within  
the servicing manual).  
4.5  
COMBUSTION ANALYSIS  
The flue connector has two apertures, readings can be  
taken for the temperature of the combustion by-products  
and of the combustion air, as well as of the concentrations  
FIG. 4.2  
2
2
of O and CO , etc. .  
To access these intakes it is necessary to unscrew the front  
screw and remove the metal plate with sealing gasket.  
To achieve the best test conditions, turn the central heating  
adjustment knob Gto the maxposition and remove the  
electrical connection to the heating sensor (see section 6.).  
This will allow the appliance to operate at the maximum  
heating power.  
19  
4.6  
FUME DISCHARGE  
MONITORING  
In the boiler, it is possible to monitor the correct operation of  
the flue exhaust/air intake, checking for a loss of general  
pressure in the system. Through the use of a differential  
manometer connected to the test points of the combustion  
chamber, it is possible to detect the P of operation of the air  
pressure switch.  
The value detected should not be less than 0.55 mbar under  
conditions of maximum thermal power in order for the boiler  
to function properly and without interruption.  
FIG. 4.3  
The boiler is fitted with the following devices (see section 4.2 for references).  
1 - IGNITION FAILURE:  
4.7  
BOILER SAFETY SYSTEMS  
This indicates ignition failure when a flame is not detected within 7  
seconds of starting an ignition sequence. The L.E.D. Fwill illuminate  
to signal the shutdown status.  
The system can be reset by pressing and releasing the button Eafter  
checking to make sure that the gas cock is open.  
2 - INSUFFICIENT SYSTEM PRESSURE:  
In the event of insufficient water pressure in the heating system, a  
safety device will shutdown the boiler. Check the system pressure on  
the pressure gauge Jand if it is less than 0.4 bar refill the system to  
1.5 bar. Once the system pressure is at the correct level the boiler will  
ignite automatically.  
3 - OVERHEATING:  
This control shuts off the boiler in the case where the primary circuit  
reaches a temperature in excess of 105°C.  
The red L.E.D. Fwill illuminate to signal this shutdown status.  
The system can be reset by waiting a few minutes for the primary  
exchanger to cool down and then by pressing and releasing the E”  
button.  
4. ANTI-FROST DEVICE:  
The boiler is equipped with a device that, in the event of the water  
temperature going below 6°C, the burner ignites at the minimum power  
until the boiler water reaches a temperature of 16°C.  
This device operates only if the boiler is functioning perfectly and:  
- the system pressure is sufficient;  
- the boiler is powered electrically - L.E.D. Billuminated;  
- the gas is turned on.  
5 - EXHAUST DISCHARGE ANOMALY SHUTDOWN:  
The boiler is fitted with safety devices, which in the event of defective  
discharge of exhaust fumes, automatically interrupts the gas supply,  
thereby shutting off the boiler.  
The shutdown of the boiler is temporary and when the discharge state  
of exhaust fumes has returned to normal, the boiler automatically turns  
back on  
The heating system must be emptied as follows:  
- Turn off the boiler;  
4.8  
DRAINING THE SYSTEM  
- Attach a hose pipe and open the drain valve;  
- Empty the system at the lowest points (where present). When the heating  
system is unused for an extended period of time, it is recommended that you  
add antifreeze with an ethylene glycol base to the water in the  
heating lines and radiators if the ambient temperature drops below 0°C during  
the winter.  
This makes repeated draining of the entire system unnecessary.  
20  
TABLE 5.1  
5.  
GAS ADJUSTMENTS  
Liquid Butane Gas Liquid Propane Gas  
CATEGORY II2H3+  
Methane Gas  
G20  
G30  
G31  
Lower Wobbe Index (15°C;1013mbar)  
Nominal Delivery Pressure  
MJ/m3h  
mbar  
45.67  
20  
80.58  
29  
80.58  
37  
Minimum Delivery Pressure  
mbar  
17  
20  
25  
21 RFFI  
Main Burner: n. 12 jets (ø)  
Consumption (15°C; 1013mbar)  
Consumption (15°C; 1013mbar)  
Gas Burner Pressure:  
mm  
1.30  
2.4 - 1.05  
----  
0.77  
----  
1.78 - 0.78  
0.77  
----  
1.76 - 0.77  
m3/h  
Kg/h  
max - min  
mbar  
8.5 - 1.7  
27.5 - 6.2  
37.4 - 8.0  
28 RFFI  
Main Burner: n. 14 jets (ø)  
Consumption (15°C; 1013mbar)  
Consumption (15°C; 1013mbar)  
Gas Burner Pressure:  
1.30  
3.15 -1.26  
----  
0.77  
----  
1.78 - 0.78  
0.77  
----  
1.76 - 0.77  
m3/h  
Kg/h  
max - min  
mbar  
11.0 - 1.6  
27.7 - 4.6  
35.5 - 6.0  
[1 mbar = 10,197 mmc.a.]  
The outlet pressure of the gas cock is obtained by completely loosening the  
screw on the solenoid. The maximum pressure of the gas to the burner will  
be equal to the nominal delivery pressure minus the head loss within the  
gas valve.  
The boiler can be converted to use either methane (natural) gas (G20)  
or LPG (G30 - G31) by an Authorised Service Centre.  
The operations that must be performed are the following:  
1. Replace the jets on the main burner (see table in section 5);  
2. Adjust the maximum and minimum thermal capacity values for the boiler  
(see table in section 5);  
5.1  
CHANGING THE  
TYPE OF GAS  
3. Replace the gas rating plate;  
4. Adjust the maximum thermal power setting;  
5. Adjust the soft-light feature (open the cover of the regulation screw on the  
gas valve (see FIG. 5.1). Rotate clockwise from min. to max. as per  
installation requirements).  
FIG. 5.1  
21  
It is recommended that the following inspections be carried out on the  
boiler at least once a year:  
6.  
MAINTENANCE  
1 - Check the seals for the water connections; replace any faulty seals.  
2 - Check the gas seals; replace any faulty gas seals.  
3 - Visual check of the entire unit.  
4 - Visual check of the combustion process or analysis of combustion by-  
products (see section 4.5) and cleaning of the burner if needed.  
5 - If called for by point. 3, dismantling and cleaning of the combustion  
chamber.  
6 - If called for by point. 4, dismantling and cleaning of the burner jets.  
7 - Visual check of the primary heat exchanger:  
-
-
check for overheating in the blade assembly;  
clean the exhaust fan if needed.  
8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load  
and full load.  
9 - Check of the heating safety systems:  
-
-
safety device for maximum temperature (overheat thermostat);  
safety device for maximum pressure (safety valve).  
10- Check of the gas safety systems:  
-
safety device for lack of gas or flame ionisation (detection  
electrode);  
-
safety device for gas cock.  
11- Check of the electrical connection (make sure it complies with the  
instructions in the manual).  
12- General check of the combustion by-products of the  
discharge/ventilation system.  
13- Check of the general performance of the unit.  
22  
23  
6.  
TECHNICAL INFORMATION  
28 RFFI  
21 RFFI  
CE Certification  
63AU4549  
63AU4549  
Heat Input  
Heat Output  
max/min kW  
max/min kW  
%
%
%
%
%
Kg/h  
mbar  
m3/h  
m3  
22.7/10.0  
21.0/8.7  
92.8  
29.8/12.0  
27.8/10.5  
93.5  
Efficiency of Nominal Heat Input  
Efficiency at 30% of Nominal Heat Input  
Heat Loss to the Casing (T=50°C)  
Flue Heat Loss with Burner Operating  
Flue Heat Loss with Burner Off  
Maximum Discharge of Fumes (G20)  
Residual Discharge Head  
Consumption at Nominal Capacity(G20)  
Gas Consumption after 10 Minutes*  
(15°C, 1013 mbar) (G30-G31)  
90.8  
1.2  
6.0  
0.2  
46.2  
0.70  
2.4  
90.7  
0.2  
6.3  
0.4  
60  
1.60  
3.15  
0.37  
0.32/0.39  
1.78/1.76  
117.2  
6.81  
Kg/h  
2.34/2.31  
128.8  
6.9  
Temp. of exhaust fumes at nominal capacity °C  
2
CO Content  
%
2
O Content  
%
9
8.1  
CO Content  
Minimum Ambient Temperature  
ppm  
°C  
20  
+5  
48  
+5  
Head Loss on Water Side (max) (T=20°C) mbar  
200  
200  
Residual Head of System  
bar  
0.25  
82/42  
6
1
130  
0.25  
82/42  
6
1
130  
Heating Temperature  
max/min °C  
Expansion Vessel Capacity  
Expansion Vessel Pre-load Pressure  
Maximum Water Content of System  
Maximum Heating Pressure  
l
bar  
l
bar  
3
3
Nominal Pressure  
Natural Gas (G20) mbar  
20  
20  
LPG (G30-G31)  
mbar  
V/Hz  
W
30-37  
230/50  
155  
30-37  
230/50  
155  
Electrical Supply  
Power Consumption  
Protection Grade of Electrical System  
Internal Fuse Rating  
Weight  
IP  
X4D  
FAST 2 AT  
39  
X4D  
FAST 2 AT  
39  
Kg  
G.C. Number  
41-116-06  
41-116-07  
*Calculated at 70% maximum output  
Manufacturer:  
Merloni TermoSanitari SpA - Italy  
Commercial subsidiary: MTS (GB) LIMITED  
MTS Building  
Hughenden Avenue  
High Wycombe  
Bucks HP13 5FT  
Telephone: (01494) 755600  
Fax: (01494) 459775  
Technical Service Hot Line: (01494) 539579  
Servicing  
Instructions  
Type C Boilers  
G.C.N: 41-116-06  
41-116-07  
LEAVE THESE INSTRUCTIONS  
WITH THE END-USER  
Country of destination: GB  
1.  
SERVICING INSTRUCTIONS  
TABLE OF CONTENTS  
1.1  
1.2  
REPLACEMENT OF PARTS  
TO GAIN GENERAL ACCESS  
- Removing the front panel  
- Removing the sealed chamber front cover  
- Removing the side panels  
1.3  
ACCESS TO THE COMBUSTION CHAMBER  
- Removing the combustion cover  
- Removing the burner and jets  
- Removing the electrodes  
- Removing the main heat exchanger  
- Removing the air pressure switch  
- Removing the fan  
1.4  
1.5  
SERVICING AND REMOVAL OF THE GAS VALVE  
- Setting the gas pressures  
- Removing the spark generator  
- Removing the gas valve  
ACCESS TO THE WATER CIRCUIT  
- Removing the pump pressure switch  
- Removing the safety valve  
- Removing the automatic air vent  
- Removing the pump  
- Removing the pressure gauge  
- Removing the expansion vessel  
- Removing the overheat thermostat  
- Removing the frost thermostat  
- Removing the regulation thermostat  
1.6  
ACCESS TO THE CONTROL SYSTEM  
- Checking the fuses  
- Removing the P.C.B.s  
2.  
2.1  
3.  
4.  
FAULT FINDING  
FAULT FINDING GUIDE (FLOW-CHARTS)  
ELECTRICAL DIAGRAMS  
SHORT SPARE PARTS LIST  
2
2. The control panel moves downward and when pulled forward,  
rotates on two lateral hinges; the panel stays in a semi-  
horizontal position, which allows access to the inner parts of  
the boiler (FIG. 1.2);  
3. In order to increase the manouvering space, it is possible to  
raise the control panel and rotate it to a fully horizontal position  
(FIG. 1.3);  
4. Remove the screws “B” from the front panel bottom lip  
(FIG. 1.4);  
5. Lift the front panel up and forward from the raised screws at the  
the top of the casing (FIG. 1.5).  
1.  
SERVICING INSTRUCTIONS  
To ensure efficient safe operation, it is recommended that the  
boiler is serviced annually by a competent person.  
Before starting any servicing work, ensure both the gas and  
electrical supplies to the boiler are isolated and the boiler is  
cool.  
Before and after servicing, a combustion analysis should be made  
via the flue sampling point (please refer to the Installation Manual  
for further details).  
After servicing, preliminary electrical system checks must be  
carried out to ensure electrical safety (i.e. polarity, earth continuity,  
resistance to earth and short circuit).  
FIG. 1.4  
1.1  
REPLACEMENT OF PARTS  
The life of individual components varies and they will need  
servicing or replacing as and when faults develop.  
B
The fault finding sequence chart in chapter 2 will help to locate  
which component is the cause of any malfunction, and instructions  
for removal, inspection and replacement of the individual parts are  
given in the following pages.  
1.2  
TO GAIN GENERAL ACCESS  
All testing and maintenance operations on the boiler require the  
control panel to be lowered. This will also require the removal of  
the casing.  
1.2.1 Removing the front panel  
1. Loosen the fastening screws “A” of the control panel located on  
the lower part of the panel itself. (FIG. 1.1);  
FIG. 1.1  
A
FIG. 1.5  
FIG. 1.2  
FIG. 1.3  
3
1.2.2 Removing the sealed chamber front cover  
1.2.3 Removing the side panels  
1. Remove the screws “C” (FIG. 1.6);  
2. Lift the sealed chamber front cover from the locating pins  
(FIG. 1.7).  
1. Remove the four screws “D” for each side panel (FIG.1.8);  
2. Pull the panel away from the boiler at the base, then lift the  
panel up and remove from the boiler.  
FIG. 1.8  
D
D
C
C
D
FIG. 1.6  
FIG. 1.7  
4
1.3  
ACCESS TO THE COMBUSTION CHAMBER  
1.3.1 Removing the combustion cover  
1. Remove the screws “E” (FIG. 1.9);  
2. Lift off the combustion cover.  
Fig. 1.11  
1.3.3 Removing the electrodes  
Before carrying out this procedure, unscrew and slide the  
burner forward (see previous section).  
1. Remove rubber gasket “G” (FIG. 1.12);  
E
E
E
2. To remove the detection electrode disconnect the cable  
at its connection point close to the P.C.B. (FIG. 1.13);  
FIG. 1.12  
FIG. 1.9  
1.3.2 Removing the burner and jets  
G
1. Remove the screws “F” from the burner (FIG. 1.10);  
2. Remove the burner (FIG. 1.11);  
3. Disconnect the electrodes (see section 1.3.3);  
4. Remove the jets using a No. 7 socket spanner;  
5. Replace in reverse order.  
FIG. 1.10  
F
F
FIG. 1.13  
5
3. Remove screw “H” (FIG. 1.14);  
1.3.4 Removing the main heat exchanger  
4. Gently slide the electrode downward (FIG. 1.15).  
1. Drain the boiler of water;  
2. Release the overheat thermostat sensor “I” (FIG. 1.16);  
3. Release the two connection nuts “J” connecting the  
exchanger to the flow and return pipes (FIG. 1.17);  
4. Remove the heat exchanger by sliding forward (FIG.  
1.18).  
FIG. 1.14  
H
I
Fig. 1.16  
FIG. 1.15  
J
To replace, repeat the steps in reverse order, paying  
particular attention to the following:  
a -Centre the electrode in the positioning hole carefully,  
otherwise the electrode may break;  
FIG. 1.17  
b -Ensure that the left hand and right hand electrodes are  
located the correct way round (facing each other), to  
give the correct spark gap;  
c -Check that the cables have been connected correctly;  
d -Check that the rubber gasket covers the cable/ electrode  
connection point completely.  
FIG. 1.18  
6
1.3.5 Removing the air pressure switch  
1.3.6 Removing the fan  
1. Disconnect the electrical connections “K” and silicone  
pipes “Lfrom their connection points (FIG. 1.19);  
2. Remove screws “M” on the top of the sealed chamber  
(FIG. 1.20);  
3. Lift out the air pressure switch (FIG. 1.21);  
4. Unscrew to remove the switch from the plate.  
1. Disconnect electrical connections “N” and silicon pipe “O”  
(FIG.1.22);  
2. Remove screw “P” and remove the fan collar clamp “Q”  
(FIG.1.23);  
3. Remove screws “R” (FIG.1.24);  
4. Remove fan and mounting plate (FIG.1.25).  
FIG. 1.19  
FIG. 1.22  
K
L
N
L
O
FIG. 1.20  
Q
P
M
FIG. 1.23  
M
R
R
FIG. 1.24  
FIG. 1.21  
FIG. 1.25  
7
1.4  
SERVICING AND REMOVAL  
OF THE GAS VALVE  
Setting the minimum and the maximum power of the boiler  
1. Check that the supply pressure to the gas valve is a minimum of 20 mbar  
for natural gas. Turn off the gas supply at the isolation point under the  
boiler  
1.4.1 Setting the gas pressures  
1
2. To do this, slacken the screw “A”.  
Fit the pipe of the pressure gauge to the inlet pressure test point of the gas  
valve “B”.  
Turn on the gas supply at the isolation point under the boiler and with  
the boiler running, read the inlet working pressure on the gauge.  
When you have completed this operation, turn off the gas supply at the  
isolation point under the boiler, remove the pressure gauge and tighten  
the screw “A” securely into its housing to seal off the gas. Turn on the gas  
supply at the isolation point under the boiler and test the screw for  
gas escaping with an approved soap and water solution.  
3. To check the pressure supplied by the gas valve to the burner, with the  
boiler turned off, slacken the screw “C”. Fit the pipe of the pressure gauge  
to the outlet pressure test point of the gas valve “D”.  
B
A
VG002Ac  
Disconnect the compensation pipe “E”either from the gas valve or from  
the sealed chamber.  
2
4. Push the On/Off button to “ON” position -green light- and push the Heating  
button to “ON” position -green light-  
Turn on the boiler by setting the external controls.  
D
Adjust the 10mm nut “F” on the modureg to set the gas pressure Turn the  
nut clockwise to increase and anti clockwise to decrease the pressure until  
the required pressure is achieved (see TABLE A page 9)  
5. To set the minimum power, disconnect the supply cable from the modureg  
and adjust screw “G” whilst holding nut “F”.  
E
C
Turn the screw clockwise to increase the pressure and anticlockwise to  
decrease the pressure until the required pressure is achieved (see TABLE  
A page 9)  
6. When you have completed the above operations, turn off the external  
controls, re-connect the supply terminal to the modureg on the gas valve  
and replace the cap on the screw of the modureg.  
VG002Ad  
3
Setting pressure for soft ignition.  
The soft light pressure is factory set.  
If the ignition is not regular (e.g: not complete burner ignition or ignition  
noise) check the soft light regulator position.  
The soft light pressure will need adjusting as follows:  
- Turn off electrical supply;  
F
- referring to diagram 5, open the dust cap of the soft light regulator, by  
unscrewing in clockwise direction the white screw;  
- turn the adjustment screw one step in the direction max to increase or in  
the direction min to decrease the soft light pressure;  
- after each adjustment of the regulator, turn on the electrical supply and  
recheck burner ignition (wait 20 seconds between each cycle to allow  
the gas valves’ internal servo system to reset). When the required level  
is achieved, close the dust cap.  
VG002Af  
4
7. Remove the pipe from the pressure gauge and connect screw “C” to the  
pressure outlet in order to seal off the gas.  
8. Carefully check the pressure outlets for gas leaks (valve inlet and outlet).  
G
5
IMPORTANT!  
Whenever you disassemble  
and reassemble the gas  
connections, always check for  
leaks using an approved soap  
and water solution.  
VG002Ae  
8
Regulating the heating power for  
natural gas (G20)  
21 kW  
28 kW  
OPERATING POWER  
CG005A  
Regulating the heating power for  
butane gas (G30)  
21 kW  
28 kW  
OPERATING POWER  
CG004A  
Regulating the heating power for  
propane gas (G31)  
21 kW  
28 kW  
OPERATING POWER  
CG006A  
TABLE A  
2.4  
84.7  
37.0  
1.78  
0.78  
62.8  
27.5  
1.76  
0.77  
62.1  
27.2  
1.05  
20  
8.5  
1.7  
14.6  
3.1  
27.5  
6.2  
10.7  
37.4  
8.0  
3.3  
0.7  
2.4  
3.15  
1.26  
111.1  
44.5  
2.34  
0.94  
82.6  
33.2  
2.31  
0.93  
81.5  
32.8  
11  
10.8  
1.8  
4.3  
0.6  
27.7  
4.6  
35.5  
6.0  
13.8  
2.3  
1.6  
14 x 1.30  
14 x 0.77  
14 x 0.77  
9
1.4.2 Removing the spark generator  
1.4.3 Removing the gas valve  
1. Disconnect ignition leads Sby pulling upward  
(FIG. 1.26);  
Important! Before removing the gas valve, ensure the gas  
supply is turned off.  
2. Remove the screw T(FIG. 1.27);  
3. Remove the spark generator by pulling forward from the  
gas valve.  
1. Disconnect all the cables from the solenoid and  
modureg;  
2. Remove the spark generator (see previous section);  
3. Release the top nut U(FIG. 1.28);  
4. Remove the screws Vfrom the bottom of the gas valve  
pipe (FIG. 1.29);  
5. Remove the gas valve (FIG. 1.30).  
S
U
FIG. 1.26  
FIG. 1.28  
V
V
T
FIG. 1.29  
FIG. 1.27  
FIG. 1.30  
10  
1. 5. 2 Removing the safety valve  
1.5  
ACCESS TO THE WATER CIRCUIT  
1. Loosen nut Y(FIG. 1.33);  
2. Disconnect the discharge pipe work from below the  
boiler;  
Important! Before any component is removed, the boiler  
must be drained of all water.  
3. Unscrew and remove the valve.  
1.5.1 Removing the pump pressure switch  
1. Remove the cable of the pump pressure switch W”  
(Fig. 1.31);  
2. Unscrew the pump pressure switch by using a spanner  
on the nut X(FIG. 1.32);  
3. Remove the pump pressure switch.  
Y
FIG. 1.33  
W
FIG. 1.31  
1.5.3 Removing the automatic air vent  
1. Unscrew valve top Z(FIG. 1.34);  
2. Remove valve complete with float (FIG 1.35).  
Z
X
FIG. 1.32  
FIG. 1.34  
FIG. 1.35  
11  
1.5.4 Removing the pump  
1. Remove the U-clips A1and B1(FIG. 1.36);  
2. Remove the retaining clip C1(FIG. 1.37);  
3. Release the nut D1(FIG. 1.38);  
4. Remove the pipe E1(FIG. 1.39);  
5. Remove the screw F1(FIG. 1.40);  
6. Remove the pump (FIG. 1.41).  
E1  
A1  
FIG. 1.39  
B1  
F1  
FIG. 1.36  
FIG. 1.40  
C1  
FIG. 1.37  
FIG. 1.41  
D1  
FIG. 1.38  
12  
1.5.5 Removing the pressure gauge  
1.5.6 Removing the expansion vessel  
1. Remove the U-clip G1and remove the pressure gauge  
coupling (FIG. 1.42);  
1. Release nuts H1and remove the gas pipe (FIG. 1.44);  
2. Release nut I1(FIG. 1.45);  
2. Push the pressure gauge through the control panel from  
the rear (FIG. 1.43).  
3. Remove lock-nut J1(FIG. 1.46);  
4. Remove the expansion vessel (FIG. 1.47).  
H1  
G1  
H1  
FIG. 1.44  
FIG. 1.42  
I1  
FIG. 1.45  
FIG. 1.43  
J1  
FIG. 1.46  
FIG. 1.47  
13  
1.5.6 Removing the overheat thermostat  
1. Disconnect the overheat thermostat electrical  
connections K1(FIG. 1.48);  
2. Then remove the thermostat from its mounting by  
releasing the securing clip (FIG. 1.49).  
FIG. 1.51  
K1  
1.5.8 Removing the regulation thermostat  
1. Remove the regulation thermostat sensor from its  
mounting by releasing the securing clip M1(FIG. 1.52);  
2. Separate the facia panel from the rear of the control  
panel (see section 1.6.2);  
FIG. 1.48  
3. Remove the electrical connections N1 from the  
regulation thermostat (FIG. 1.53);  
4. Pull the regulation knob from the spindle of the  
thermostat;  
5. Remove the thermostat from the control panel facia by  
unscrewing the mounting screws.  
FIG. 1.49  
M1  
1.5.7 Removing the frost thermostat  
1. Disconnect the frost thermostat electrical connection  
L1(FIG. 1.50);  
2. Then remove the thermostat from its mounting by  
releasing the securing clip (FIG. 1.51).  
FIG. 1.52  
L1  
N1  
FIG. 1.53  
FIG. 1.50  
14  
1.6.2 Removing the P.C.B.s  
1.6  
ACCESS TO THE CONTROL SYSTEM  
1. Isolate electricity;  
2. Remove the screws O1(FIG. 1.56);  
3. Separate the facia panel from the rear of the control  
panel;  
Important! Isolate the electrical supply to the boiler before  
accessing the control panel.  
4. Unplug all electrical connections from the P.C.B. and  
remove the screws P1and remove the P.C.B. (FIG.  
1.57).  
1.6.1 Checking the fuse  
1. Remove the inspection cover on the reverse of the  
control panel (FIG. 1.54);  
2. Remove the fuse mounted on the reverse of the  
inspection cover (FIG. 1.55).  
O1  
O1  
O1  
O1  
O1  
O1  
FIG. 1.56  
FIG. 1.54  
P1  
P1  
P1  
P1  
FIG. 1.57  
FIG. 1.55  
15  
2.  
FAULT FINDING  
It is possible to detect and correct any defect by using the standard fault  
finding diagrams described in this chapter.  
2.1  
FAULT FINDING GUIDE  
(FLOW-CHARTS)  
PRELIMINARY CHECKS  
MAKE SURE THAT:  
1 - THERE IS SUFFICIENT  
WATER IN THE SYSTEM  
2 - THE GAS IS TURNED ON  
3 - THE ELECTRICAL SUPPLY  
IS TURNED ON  
PRESS THE  
ON/OFF BUTTON  
IS  
THE SUPPLY  
NO  
NO  
L.E.D. ILLUMINATED?  
1 - CHECK THE FUSES  
2 - CHECK THERE IS POWER  
SUPPLIED TO THE P.C.B.S  
3 - CHECK/REPLACE THE P.C.B.  
(CT1)  
YES  
PRESS THE CENTRAL  
HEATING BUTTON  
IS  
THE L.E.D.  
ILLUMINATED?  
1 - CHECK THE INTEGRITY  
OF THE L.E.D.  
2 - CHECK/REPLACE THE P.C.B.  
(CT1)  
YES  
IS THE  
TIME CLOCK/  
PROGRAMMER  
AND/OR ROOM THERMOSTAT  
CALLING FOR  
NO  
HEATING?  
YES  
FROST  
PROTECTION IS  
ACTIVATED <5¡C. IS THE  
FROSTPROTECTION  
REQUESTED?  
NO  
YES  
A
B063  
16  
A
IS THE PUMP  
RUNNING?  
NO  
YES  
POWER TO  
THE PUMP?  
NO  
YES  
1 - CHECK THE PUMP CABLE  
2 - CHECK/REPLACE P.C.B.  
(CT1)  
3 - CHECK THE SYSTEM  
PRESSURE GAUGE IS AT  
1.5 BAR  
1 - CHECK THE OPERATION  
OF THE PUMP  
2 - RELEASE/REPLACE THE  
PUMP  
IS THE FAN  
RUNNING?  
NO  
YES  
BOILER  
SHUTDOWN?  
1 - RESET THE BOILER  
YES  
NO  
B
1 - CHECK/REPLACE AIR  
PRESSURE SWITCH  
AND CABLE  
INTERNAL  
P.C.B. PROTECTION  
ACTIVATED?  
YES  
NO  
2 - CHECK IF THE RESET  
IS JAMMED  
3 - CHECK/REPLACE  
DETECTION ELECTRODE  
NO  
1 - CHECK/REPLACE FAN  
CONNECTION CABLE  
2 - CHECK/REPLACE P.C.B.  
3 - CHECK/REPLACE AIR  
PRESSURE SWITCH  
POWER TO  
THE FAN?  
YES  
1 - REPLACE THE FAN  
B063  
17  
B
1 - CHECK AIR PRESSURE  
SWITCH CABLE  
2 - CHECK/REPLACE AIR  
PRESSURE SWITCH  
3 - CHECK/REPLACE P.C.B.  
(CBM2)  
IS THE  
AIR PRESSURE SWITCH  
ACTIVATED?  
CHECK  
P ON PRESSURE  
TEST POINT  
P 0.5 mbar  
NO  
YES  
P0.5 mbar  
1 - CHECK EXHAUST DISCHARGE  
2 - CHECK VENTURI AND TUBES  
3 - CHECK THE FAN EFFICIENCY  
4 - REPLACE FAN  
1 - CHECK/REPLACE IGNITION  
ELECTRODES  
2 - CHECK THE CABLES  
3 - CHECK SPARK GENERATOR  
4 - CHECK IGNITION ELECTRODE  
CABLES  
DOES  
THE SPARK  
SEQUENCE  
START?  
5 - CHECK/REPLACE P.C.B. (CBM2)  
NO  
NO  
YES  
1 - CHECK POWER SUPPLY TO  
THE GAS VALVE  
IS THE BURNER  
ALIGHT?  
2 - CHECK OPERATION OF THE  
4 - CHECK/REPLACE P.C.B. (CBM2)  
GAS VALVE  
3 - REPLACE THE GAS VALVE  
YES  
HAS THE  
YES  
BOILER SAFETY  
SHUTDOWN BEEN  
ACTIVATED?  
PRESS THE RESET  
BUTTON  
1 - CHECK IF THE FLAME  
STRIKES THE DETECTION  
ELECTRODE  
NO  
BOILER  
WORKING?  
2 - CHECK THE SOFT-LIGHT  
4 - CHECK/REPLACE  
P.C.B. (CBM2)  
NO  
GAS PRESSURE  
3 - CHECK/REPLACE DETECTION  
ELECTRODE  
YES  
NORMAL  
OPERATION  
FAULT LIST  
POSSIBLE CAUSES  
IS  
THERE STILL  
A PROBLEM?  
NOISEY OPERATION  
1
- MAIN HEAT EXCHANGER FAULTY OR BLOCKED  
WITH LIME-SCALE DEPOSITS  
- LOW HEATING SYSTEM WATER PRESSURE  
- CHECK GAS PRESSURES  
YES  
NO  
- CHECK HEATING THERMOSTAT  
- CHECK FAN  
- CHECK PUMP  
DECREASE/INCREASE OF HEATING CIRCUIT  
PRESSURE  
2
3
4
- CHECK FOR LEAKS ON THE HEATING CIRCUIT  
- FAULTY FILLING LOOP  
- FAULTY EXPANSION VESSEL  
NORMAL  
OPERATION  
REPEATED SHUTDOWNS  
- FAULTY DETECTION ELECTRODES  
- CHECK GAS PRESSURES  
- CHECK FLAME DETECTION ELECTRICAL CIRCUIT  
- FAULTY HEATING THERMOSTAT  
- FAULTY OVERHEAT THERMOSTAT  
- PRESENCE OF AIR IN THE HEATING CIRCUIT  
- CHECK BURNER PRESSURES  
REPEATED OPERATION OF SAFETY THERMOSTAT  
- CHECK EXCHANGER FLUEWAY  
5 INSUFFICCIENT RAADIATOORR TEMPERATURE  
- CHECK HEATING THERMOSTAT  
- CHECK BY-PASS  
- CHECK GAS PRESSURE  
B063  
18  
A06 - External Control System  
A07 - Time Clock Connector  
A08 - External (Room) Thermostat  
A09 - Air Pressure Switch  
A10 - Fan  
A11 - Overheat Thermostat  
A12 - Spark Generator/Gas Valve Supply  
A13 - Detection Electrode  
3.  
ELECTRICAL  
DIAGRAMS  
LEGEND:  
A - On/Off Switch  
B - On/Off L.E.D.  
C - Heating Switch  
D - Heating L.E.D.  
E - Reset Button  
Colours:  
Wh  
Bl  
-White  
-Blue  
F - Ignition Failure (Lockout) L.E.D.  
Gry  
Brn  
Blk  
Rd  
-Grey  
-Brown  
-Black  
-Red  
A01 - Pump Pressure Switch  
A02 - Frost Thermostat  
A03 - Modulator  
Grn/Yll-Yellow/Green  
A04 - Circulation Pump  
A05 - Regulation Thermostat  
SE011A  
B063  
19  
SF008A  
B063  
20  
4.  
SHORT SPARE  
PARTS LIST  
microSYSTEM 21/28 RFFI  
71 11 70 69 68  
67 66 65 64 11 63 62  
61  
304  
1
2
60  
59  
3
4
72  
64  
5
6
7
11  
64  
11  
74  
73  
64  
301  
302  
303  
106  
8
9
107  
105  
58  
57  
56  
104  
103  
10  
75  
11  
12  
11  
12  
102  
101  
76  
77  
55  
54  
100  
53  
52  
51  
79  
80  
96  
95  
99  
78  
97  
98  
80  
13  
81  
82  
94  
50  
13  
14  
83  
49  
48  
47  
93  
88  
87  
89  
15  
16  
17  
47  
92  
84  
46  
45  
91  
90  
86  
31  
85  
13  
19  
13  
18  
19  
20  
21 22 23  
24  
13  
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 38 37 38 4041 42 43 44  
33  
352  
351  
353  
354  
21/28 RFFI  
B063  
21  
microSYSTEM 21/28 RFFI  
Key  
no.  
G.C. part  
no.  
ARISTON  
Part No.  
Description  
2
5
13  
16  
18  
19  
21  
22  
23  
25  
26  
27  
29  
30  
31  
33AB  
33CD  
45  
Expansion vessel  
Gasket 3/8"  
Gasket 3/4"  
Thermostat (frost)  
Flow group  
Gasket 1/2"  
Safety valve (1/4" 3 bar)  
Gasket 1/4"  
Pump pressure switch  
Spark Generator  
Gasket  
Gas valve  
Auto air vent  
Return group  
O-ring  
Pump  
Pump  
Thermostat (regulation)  
P.C.B. (CBM2 AT-FFI2X)  
Pressure gauge  
Gasket  
Air pressure switch  
Air pressure switch  
Gasket  
O-ring (2.65 x 10.27)  
Fan  
Fan  
Main exchanger  
Main exchanger  
Thermostat (overheat)  
Burner 12 ramp (natural gas)  
Burner 12 ramp (LPG)  
Burner 14 ramp (natural gas)  
Burner 14 ramp (LPG)  
Burner jet (natural gas 1.30)  
Burner jet (LPG 0.77)  
P.C.B. (CT1)  
1
998616  
573521  
573520  
570760  
998612  
573528  
998447  
569390  
998627  
999542  
574279  
999475  
998809  
999476  
998424  
998836  
999091  
999577  
999499  
999245  
998517  
998484  
571651  
997182  
998943  
998489  
999894  
998620  
998893  
999538  
998618  
998669  
998887  
998939  
998433  
998434  
999501  
950030  
998623  
998622  
998624  
998644  
998643  
998738  
998961  
999207  
998716  
998717  
164 282  
164 225  
1
1
1
1
164 229  
164 261  
1
1
1
1
1
1
1
1
1
1
1
1
1
48  
49  
55  
60AB  
60CD  
73  
E03 818  
1
1
75  
76AB  
76CD  
78AB  
78CD  
81  
83A  
83B  
83C  
83D  
87AC  
87BD  
93  
95  
97  
98  
99  
351  
352  
353  
354AB  
354CD  
361  
362  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fast fuse 2AT  
Electrode (ignition R.H.)  
Electrode (ignition L.H.)  
Detection electrode  
O-ring (A.A.V.)  
Auto air vent  
Gasket (pump head)  
Pump head  
Pump head  
Burner jet 1.30 full kit (natural gas)  
Burner jet 0.77 full kit (LPG)  
E24 076  
E24 075  
B063  
22  
NOTES  
B063  
23  
Manufacturer:  
Merloni TermoSanitari SpA - Italy  
Commercial subsidiary: MTS (GB) LIMITED  
MTS Building  
Hughenden Avenue  
High Wycombe  
Bucks HP13 5FT  
Telephone: (01494) 755600  
Fax: (01494) 459775  
Technical Service Hot Line: (01494) 539579  

Bil Jax Bicycle Accessories et 4000 User Manual
Breville BES900XL User Manual
Bushnell Binoculars 280751 User Manual
Canon HF M40 User Manual
Canon MV 3i MC User Manual
Carson SA 441 83F User Manual
Epson Camera Accessories 800 User Manual
GE FCM5 User Manual
JBL CS300 1 User Manual
JL Audio 15Wv2 4 User Manual