York Sunline 2000 60 User Manual

255040-YTG-A-0506  
®
DESCRIPTION  
YORK Sunline 2000™ units are convertible single package  
air conditioners with a common cabinet and a common roof  
curb for the 3, 4, 5 and 6 ton sizes. The units were designed  
for light commercial and commercial applications. They can  
easily be installed on a roof curb, slab, roof jack or frame.  
TECHNICAL GUIDE  
All units include:  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
AND SINGLE PACKAGE  
Powder Paint finish that meets ASTM-B-117 1000 hour  
salt spray standards  
Permanently lubricated motors  
AIR CONDITIONERS  
Bottom or side air discharge configuration capability  
(field convertible)  
D(CE, CG) 036, 048, 060 & 072  
3, 4, 5 & 6 NOMINAL TONS  
Manufactured under the quality standards of ISO9001  
Copper tube/aluminum fin coils  
10.0 SEER (3, 4, & 5 Ton), 9.0 EER (6 Ton)  
Easy access to all components  
Rigging holes in base rails for lifting  
Fork lift slots on three sides  
Single point power connection  
Complete factory package - tested, charged and wired  
CSA agency listing on all units  
WARRANTY  
Factory Limited Parts Warranty  
One-year parts warranty  
A Five-year parts warranty on the compressor and  
electric heat elements.  
Ten-year parts warranty on the gas-fired heat  
exchangers.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
255040-YTG-A-0506  
PRODUCT NOMENCLATURE  
PRODUCT CATEGORY  
D
5
C
E
0
3
6
A
2
5
VOLTAGE CODE  
D = Single Package Air Conditioner  
(Air Cooled)  
25 = 208/230-3-60  
46 = 460-3-60  
58 = 575-3-60  
PRODUCT GENERATION  
3 = 3rd Generation  
5 = 5th Generation  
FACTORY INSTALLED  
HEAT  
NOMINAL COOLING  
CAPACITY  
PRODUCT IDENTIFIER  
CE = Cooling  
A = Cooling Only  
036 = 3 Ton  
048 = 4 Ton  
060 = 5 Ton  
072 = 6 Ton  
D
8
C
G
0
3
6
N
0
4
0
2
5
PRODUCT CATEGORY  
VOLTAGE CODE  
D = Single Package Air Conditioner  
(Air Cooled)  
25 = 208/230-3-60  
46 = 460-3-60  
58 = 575-3-60  
PRODUCT GENERATION  
NOMINAL GAS HEATING  
OUTPUT CAPACITY  
3 = 3rd Generation  
8 = 8th Generation  
040 = 40 MBH  
060 = 60 MBH  
079 = 79 MBH  
099 = 99 MBH  
PRODUCT IDENTIFIER  
CG = Gas/Electric  
NOMINAL COOLING  
CAPACITY  
FACTORY INSTALLED  
HEAT  
036 = 3 Ton  
048 = 4 Ton  
060 = 5 Ton  
072 = 6 Ton  
N = Gas Heat Installed  
Unitary Products Group  
3
 
255040-YTG-A-0506  
alarm on ignition failures, compressor lockouts and  
repeated limit switch trips.  
FEATURES  
All units are self-contained and assembled on full perimeter  
base rails with forklift holes on three sides and holes for over-  
head rigging. Every unit is completely piped, wired, charged  
and tested at the factory to simplify the field installation and to  
provide years of dependable operation.  
Nuisance Trip Protection- To prevent nuisance  
trouble calls, the control board uses a “three strikes,  
you’re out” philosophy. The high and low-pressure  
switches and the freezestats must trip three times  
within two hours before the unit control board will  
lock out the compressor.  
All models (including those with an economizer) are suitable for  
either bottom or horizontal duct connections. For bottom duct,  
remove the sheet metal panels from the supply and return air  
openings through the base of the unit. For horizontal duct,  
remove the supply and return air panels on the rear of the unit.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
All models are available with the “factory mounted” outdoor  
air damper option:  
Single enthalpy economizer  
Supply air blowers are equipped with either a direct drive or a  
belt drive that can be adjusted to meet the exact require-  
ments of the job.  
All units have long lasting powder paint cabinets with 1000  
hour salt spray test approval under ASTM-B117 procedures.  
All compressors are equipped with internal pressure relief.  
Every refrigerant circuit includes a liquid line filter-drier, a high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch to protect all system compo-  
nents.  
All models are CSA listed.  
Warranty - All models include a one-year limited parts  
warranty on the complete unit. Compressors and electric  
heater elements carry a five-year warranty. Gas heat  
exchangers carry a 10-year parts warranty.  
Control boards have standardized a number of features  
previously available only as options or by utilizing addi-  
tional controls.  
Gas Heat Operation - All single phase models with gas  
heat have minimum annual fuel utilization efficiency  
(AFUE) of 80%. All three phase models with gas heat  
have minimum steady state efficiency of 80%. Each sec-  
tion includes a durable heat exchanger with aluminized  
steel, a redundant gas valve, spark ignition, power vent-  
ing, an ignition module for 100% shut-off and all of the  
safety controls required to meet the latest ANSI stan-  
dards.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0ºF outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit  
or through a knockout in the piping panel on the front of  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti short cycle delay can be temporarily  
overridden with the push of a button.  
the unit.  
Electric Heat Operation - All electric heat models are  
wired for a single power source and include a bank of  
nickel chromium elements mounted at the discharge of  
the supply air blower to provide a high velocity and uni-  
form distribution of air across the heating elements.  
Every element is fully protected against excessive tem-  
perature by thermal limit switches.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable and are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
gas valve, if applicable, and the temperature limit  
switch on gas heat units. The unit control board will  
The power supply wiring can be routed into the control  
box through a threaded pipe connection (field supplied)  
in the base pan of the unit or through a knockout in the  
wiring panel on the side of the unit.  
4
Unitary Products Group  
 
255040-YTG-A-0506  
20 GAUGE ALUMINIZED  
STEEL TUBULAR HEAT  
EXCHANGER  
POWER VENTOR MOTOR  
WITH POST PURGE CYCLE  
DIRECT OR  
BELT DRIVE  
BLOWER  
HIGH EFFICIENCY  
COMPRESSOR  
ECONOMIZER  
HOOD  
COPPER TUBE/  
ALUMINUM FIN  
CONDENSING  
COIL  
SLIDE-IN  
ECONOMIZER  
FULL PERIMETER  
BASE RAILS WITH  
FORKLIFT SLOTS  
AND LIFTING HOLES  
SIDE RETURN  
AIR DUCT OPENING  
KNOCKOUT FOR SIDE  
GAS SUPPLY ENTRY  
BOTTOM  
RETURN  
AIR DUCT  
OPENING  
3/4” PVC FEMALE  
CONDENSATE DRAIN  
LOW VOLTAGE CONTROL  
BOARD  
KNOCKOUTS FOR  
SIDE POWER AND  
CONTROL ENTRY  
FIGURE 1 - UNIT CUTAWAY  
FACTORY-INSTALLED OPTIONS  
FIELD-INSTALLED ACCESSORIES  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to  
some pre-set position whenever the supply air blower is  
operating and will drive fully closed when the blower unit  
shuts down.  
PHENOLIC COATED CONDENSER COILS - Special  
TM  
coating process that utilizes Technicoat 10-1 pro-  
cesses. Coating is applied by total immersion of the com-  
plete coil for maximum protection.  
BELT DRIVE INDOOR FAN - Includes belt drive indoor  
fan and motor with unit access for belt adjustment and  
service.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
Unitary Products Group  
5
     
255040-YTG-A-0506  
ELECTRIC HEATERS wired for single point power sup-  
ply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
The power exhaust option can only be used on bot-  
tom duct configurations.  
BAROMETRIC RELIEF DAMPER - This damper acces-  
sory can be used to relieve internal building air pressure  
on units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
ROOF CURBS - Eight and fourteen-inch high roof curbs  
provide a water-tight seal between the unit and the finished  
roof. These full perimeter curbs meet the requirements of  
the National Roofing Contractors Association (NRCA) and  
are shipped knocked-down for field assembly.  
Roof curbs are designed to fit inside the base rails of the  
unit and include both a wood nailing strip and duct  
hanger supports.  
ENTHALPY ACCESSORY CONTROL KIT - This kit  
contains the required components to convert a single  
enthalpy economizer to dual enthalpy.  
HIGH ALTITUDE NATURAL GAS - Burner orifices and  
pilot orifices are provided for proper furnace operation at  
altitudes up to 6,000 feet.  
BURGLAR BARS - Mount in the supply and return  
openings to prevent entry into the duct work.  
PROPANE - Burner orifices, pilot orifices and gas valve  
parts are provided to convert a natural gas furnace to  
propane.  
FLUE EXHAUST EXTENSION KIT - In locations with  
wind or weather conditions which may interfere with  
proper exhausting of furnace combustion products, this  
kit can be installed to prevent the flue exhaust from  
entering nearby fresh air intakes.  
HIGH ALTITUDE PROPANE - Burner orifices and pilot  
orifices are provided for proper furnace operation at alti-  
tudes up to 6,000 feet. This accessory supplements the  
basic propane conversion kit.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
LOW NOX KIT- Required to reduce the emission of  
nitrogen oxides below 40 nanograms per joule.  
HAIL GUARD -Hail Guard Kit is available to prevent unit  
from hail damage. This is a sloped hood that fits above  
the condenser coil.  
POWER EXHAUST - Our single input economizer  
options are available with power exhaust. Whenever the  
outdoor air intake dampers are opened for free cooling,  
the exhaust fan will be energized to prevent the condi-  
tioned space from being over-pressurized during econo-  
mizer operation.  
GAS PIPING KIT - This kit supplies all necessary fittings  
and shut off valve.  
6
Unitary Products Group  
255040-YTG-A-0506  
1
TABLE 1: SOUND POWER RATING  
-12  
SOUND POWER (db 10  
Watts)  
ESP  
BLOWER  
UNIT  
SIZE  
Octave Band Centerline Frequency (Hz)  
dB(A)  
@
10Ft.2  
CFM  
SWL  
dB(A)  
IWG SPEED  
KW  
63  
125  
250  
500  
1,000  
2,000  
4,000  
8,000  
036  
048  
060  
072  
1,200  
1,600  
2,000  
2,200  
0.6  
0.55  
0.45  
0.3  
LOW  
HIGH  
HIGH  
HIGH  
0.60  
0.80  
1.00  
1.35  
84  
85  
86  
87  
84  
85  
86  
87  
74  
75  
76  
77  
67  
68  
69  
70  
69  
70  
71  
72  
62  
63  
64  
65  
57  
58  
59  
60  
52  
53  
54  
55  
74  
75  
76  
77  
41  
42  
43  
44  
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The  
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan  
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-  
tee requiring a dBA value or sound data in any other form than sound power level ratings.  
2. At a distance of 10 feet from the blower.  
1
1
TABLE 2: CAPACITY RATINGS - (ARI 210/240)  
TABLE 3: GAS HEAT RATINGS  
EER2  
SEER3  
10.0  
10.0  
10.0  
-
MODEL  
MBH  
MBH  
INPUT  
MBH  
OUTPUT  
AFUE  
(%)  
TEMP  
RISE ºF  
MODEL  
D(CE, CG)036  
D(CE, CG)048  
D(CE, CG)060  
D(CE, CG)072  
36.0  
47.4  
59.0  
72.0  
9.1  
DCG036N040  
DCG036N079  
50  
100  
40  
80  
80.9  
80.5  
15 - 45  
40 - 70  
9.0  
9.1  
DCG048N060  
DCG048N099  
75  
125  
60  
100  
80.9  
80.3  
25 - 55  
45 - 75  
9.0  
1. 80/67°F Indoor and 95°F outdoor.  
DCG060N079  
DCG060N099  
100  
125  
80  
100  
80.5  
80.3  
25 - 55  
35 - 65  
2. EER = Energy Efficiency Ratio at full load - the cooling  
capacity in Btu’s per hour (Btuh) divided by the power  
input in watts, expressed in Btuh per watt (Btuh/watt).  
3. SEER = Seasonal Energy Efficiency Ratio.  
DCG072N079  
DCG072N099  
100  
125  
80  
100  
80.5  
80.3  
25 - 55  
35 - 65  
1. All units are single-stage heating.  
Unitary Products Group  
7
     
255040-YTG-A-0506  
TABLE 4: D(CE, CG)036 COOLING CAPACITIES (3 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
45  
43  
39  
40  
44  
41  
38  
39  
42  
40  
36  
37  
41  
38  
35  
36  
39  
37  
34  
34  
3.1  
3.0  
3.0  
2.9  
3.1  
3.0  
3.0  
2.9  
3.1  
3.0  
3.0  
2.9  
3.1  
3.0  
3.0  
2.9  
3.1  
3.0  
3.0  
2.9  
35  
43  
39  
40  
31  
39  
38  
39  
28  
35  
36  
37  
26  
32  
35  
36  
24  
30  
34  
34  
30  
38  
39  
40  
28  
35  
38  
39  
25  
32  
36  
37  
23  
30  
35  
36  
21  
27  
33  
34  
26  
34  
39  
40  
24  
31  
37  
39  
22  
28  
35  
37  
20  
27  
33  
35  
19  
25  
30  
33  
21  
29  
34  
35  
20  
27  
33  
35  
18  
25  
31  
34  
17  
24  
30  
32  
16  
22  
28  
30  
17  
25  
30  
31  
16  
23  
29  
31  
15  
22  
28  
31  
14  
21  
27  
29  
14  
20  
25  
27  
-
-
43  
41  
36  
38  
42  
39  
36  
37  
41  
38  
35  
36  
39  
37  
33  
34  
38  
36  
32  
33  
3.3  
3.3  
3.3  
3.2  
3.3  
3.3  
3.3  
3.2  
3.3  
3.2  
3.3  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
3.2  
3.1  
35  
41  
36  
38  
31  
37  
36  
37  
28  
34  
35  
36  
26  
32  
33  
34  
23  
29  
32  
33  
30  
38  
36  
38  
27  
35  
36  
37  
24  
31  
35  
36  
23  
29  
33  
34  
21  
26  
31  
33  
26  
34  
36  
38  
23  
31  
35  
36  
21  
28  
34  
35  
20  
26  
31  
32  
18  
24  
29  
30  
21  
29  
32  
33  
20  
27  
31  
32  
18  
25  
30  
32  
17  
23  
28  
30  
16  
21  
26  
27  
17  
25  
27  
29  
16  
23  
27  
28  
14  
21  
27  
28  
14  
20  
25  
27  
13  
19  
24  
25  
-
-
20  
25  
26  
-
16  
21  
22  
-
21  
23  
24  
-
16  
18  
20  
-
1750  
19  
25  
27  
-
16  
21  
23  
-
19  
23  
25  
-
15  
19  
21  
-
1475  
1200  
1050  
900  
18  
25  
27  
-
15  
21  
24  
-
18  
24  
25  
-
15  
20  
22  
-
18  
24  
26  
-
15  
21  
23  
-
17  
22  
24  
-
14  
20  
21  
-
17  
23  
25  
15  
20  
22  
16  
21  
22  
14  
19  
20  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
105°F  
SENSIBLE CAPACITY1  
115°F  
EVAPORATOR  
COIL  
SENSIBLE CAPACITY1  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
41  
38  
34  
35  
40  
37  
33  
34  
39  
36  
32  
33  
37  
35  
31  
32  
36  
33  
30  
31  
3.7  
3.7  
3.7  
3.6  
3.7  
3.6  
3.7  
3.6  
3.7  
3.6  
3.6  
3.6  
3.6  
3.6  
3.6  
3.5  
3.6  
3.6  
3.6  
3.5  
34  
38  
34  
35  
30  
36  
33  
34  
27  
34  
32  
33  
25  
31  
31  
32  
22  
28  
30  
31  
29  
37  
34  
35  
26  
34  
33  
34  
24  
30  
32  
33  
22  
28  
31  
32  
20  
25  
29  
30  
25  
33  
34  
35  
23  
30  
33  
34  
20  
27  
32  
33  
19  
25  
29  
30  
17  
23  
27  
28  
20  
28  
30  
31  
19  
26  
29  
30  
17  
24  
29  
29  
16  
22  
27  
27  
15  
20  
24  
25  
16  
24  
25  
26  
15  
22  
25  
26  
14  
20  
25  
26  
13  
19  
24  
24  
12  
18  
22  
22  
-
-
39  
36  
32  
33  
38  
35  
31  
32  
37  
34  
30  
31  
36  
32  
29  
30  
34  
31  
28  
28  
4.1  
4.0  
4.0  
4.0  
4.1  
4.0  
4.0  
4.0  
4.1  
4.0  
4.0  
3.9  
4.1  
4.0  
4.0  
3.9  
4.0  
4.0  
4.0  
3.9  
33  
36  
32  
33  
30  
34  
31  
32  
26  
33  
30  
31  
24  
30  
29  
30  
21  
27  
28  
28  
28  
36  
32  
33  
26  
33  
31  
32  
23  
30  
30  
31  
21  
27  
29  
29  
19  
24  
28  
28  
24  
32  
32  
33  
22  
29  
31  
32  
20  
26  
30  
31  
18  
24  
28  
28  
16  
22  
25  
25  
19  
27  
27  
28  
18  
25  
27  
28  
16  
23  
27  
27  
15  
21  
25  
25  
14  
19  
22  
23  
15  
23  
23  
24  
14  
21  
23  
24  
13  
20  
24  
24  
12  
18  
22  
22  
11  
17  
20  
20  
-
-
19  
21  
22  
-
15  
16  
17  
-
18  
18  
19  
-
14  
14  
15  
-
1750  
18  
21  
22  
-
14  
17  
18  
-
17  
19  
20  
-
13  
15  
16  
-
1475  
1200  
1050  
900  
17  
22  
23  
-
14  
19  
19  
-
16  
20  
21  
-
13  
17  
17  
-
16  
21  
21  
-
13  
18  
18  
-
15  
19  
19  
-
12  
16  
16  
-
15  
19  
20  
13  
17  
17  
14  
17  
17  
11  
15  
15  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE  
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input  
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.  
NOMINAL RATING  
8
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 5: D(CE, CG)048 COOLING CAPACITIES (4 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
60  
55  
51  
49  
58  
53  
49  
47  
56  
51  
47  
46  
54  
49  
45  
44  
52  
47  
43  
42  
4.1  
4.1  
4.0  
3.9  
4.1  
4.1  
4.0  
3.9  
4.1  
4.1  
4.0  
3.9  
4.1  
4.1  
4.0  
3.9  
4.1  
4.1  
4.0  
3.9  
44  
53  
51  
49  
41  
49  
49  
47  
38  
46  
47  
46  
35  
42  
45  
44  
32  
39  
43  
42  
39  
48  
51  
49  
36  
45  
49  
47  
34  
41  
47  
46  
31  
38  
45  
44  
29  
35  
43  
42  
33  
42  
51  
49  
31  
40  
48  
47  
29  
37  
45  
46  
27  
34  
42  
43  
25  
32  
39  
39  
28  
37  
45  
44  
26  
35  
43  
43  
25  
32  
41  
41  
23  
30  
38  
39  
22  
28  
36  
36  
23  
32  
40  
39  
21  
30  
38  
38  
20  
28  
36  
37  
19  
26  
34  
35  
18  
25  
32  
32  
-
-
60  
52  
48  
47  
57  
50  
46  
45  
55  
48  
44  
44  
53  
47  
43  
42  
51  
45  
41  
41  
4.5  
4.5  
4.4  
4.3  
4.5  
4.5  
4.4  
4.3  
4.6  
4.5  
4.4  
4.4  
4.5  
4.5  
4.4  
4.3  
4.5  
4.4  
4.3  
4.3  
44  
52  
48  
47  
41  
49  
46  
45  
38  
45  
44  
44  
35  
41  
43  
42  
32  
38  
41  
41  
39  
47  
48  
47  
36  
44  
46  
45  
33  
40  
44  
44  
31  
38  
43  
42  
28  
35  
41  
41  
33  
42  
48  
47  
31  
39  
46  
45  
29  
36  
44  
44  
27  
34  
41  
41  
25  
31  
38  
38  
28  
36  
42  
42  
26  
34  
41  
40  
24  
31  
40  
39  
23  
30  
37  
37  
21  
28  
35  
34  
23  
31  
37  
36  
21  
29  
36  
36  
20  
27  
35  
35  
19  
26  
33  
33  
18  
24  
31  
31  
-
-
26  
34  
33  
-
21  
29  
28  
-
25  
32  
31  
-
20  
26  
26  
-
2000  
25  
33  
33  
-
20  
28  
28  
-
24  
31  
31  
-
19  
26  
26  
-
1800  
1600  
1400  
1200  
24  
32  
32  
-
19  
27  
28  
-
23  
31  
30  
-
18  
26  
26  
-
22  
30  
31  
-
19  
26  
27  
-
22  
29  
29  
-
18  
25  
25  
-
21  
29  
29  
18  
25  
25  
21  
28  
27  
17  
24  
24  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
105°F  
SENSIBLE CAPACITY1  
115°F  
EVAPORATOR  
COIL  
SENSIBLE CAPACITY1  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
56  
49  
45  
44  
55  
48  
43  
43  
53  
46  
42  
41  
51  
44  
40  
40  
49  
42  
38  
38  
5.1  
5.0  
4.9  
4.9  
5.0  
5.0  
4.9  
4.9  
5.0  
4.9  
4.9  
4.8  
5.0  
4.9  
4.8  
4.8  
4.9  
4.9  
4.8  
4.8  
42  
49  
45  
44  
39  
47  
43  
43  
36  
44  
42  
41  
33  
41  
40  
40  
30  
37  
38  
38  
37  
46  
45  
44  
34  
43  
43  
43  
32  
40  
42  
41  
29  
37  
40  
40  
27  
34  
38  
38  
31  
40  
45  
44  
29  
38  
43  
43  
28  
35  
42  
41  
26  
33  
39  
38  
23  
30  
36  
35  
26  
35  
39  
39  
24  
33  
38  
38  
23  
31  
37  
37  
22  
29  
35  
34  
20  
27  
32  
32  
21  
29  
34  
33  
20  
28  
33  
33  
19  
26  
33  
32  
18  
25  
31  
30  
16  
23  
29  
28  
-
-
53  
46  
41  
41  
52  
45  
40  
40  
51  
44  
39  
39  
48  
42  
37  
37  
46  
39  
35  
35  
5.6  
5.5  
5.4  
5.4  
5.5  
5.4  
5.4  
5.4  
5.5  
5.4  
5.3  
5.3  
5.5  
5.3  
5.3  
5.3  
5.4  
5.3  
5.3  
5.3  
40  
46  
41  
41  
38  
45  
40  
40  
35  
44  
39  
39  
32  
40  
37  
37  
29  
36  
35  
35  
35  
44  
41  
41  
33  
42  
40  
40  
31  
39  
39  
39  
28  
36  
37  
37  
26  
33  
35  
35  
29  
39  
41  
41  
28  
37  
40  
40  
26  
35  
39  
39  
24  
32  
36  
36  
22  
29  
33  
33  
24  
33  
36  
35  
23  
32  
35  
35  
22  
30  
35  
34  
20  
28  
32  
32  
19  
26  
29  
29  
19  
28  
30  
30  
18  
27  
30  
30  
17  
26  
30  
30  
16  
24  
28  
28  
15  
22  
26  
26  
-
-
24  
28  
28  
-
19  
23  
22  
-
23  
25  
25  
-
17  
20  
19  
-
2000  
23  
28  
28  
-
18  
23  
23  
-
22  
26  
25  
-
17  
21  
20  
-
1800  
1600  
1400  
1200  
22  
28  
28  
-
17  
24  
23  
-
21  
26  
25  
-
17  
21  
21  
-
21  
27  
26  
-
17  
23  
22  
-
20  
24  
24  
-
16  
20  
20  
-
20  
25  
25  
16  
22  
21  
19  
22  
22  
15  
19  
19  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE  
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input  
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.  
NOMINAL RATING  
Unitary Products Group  
9
 
255040-YTG-A-0506  
TABLE 6: D(CE, CG)060 COOLING CAPACITIES (5 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
68  
62  
57  
55  
67  
62  
56  
54  
66  
61  
55  
53  
63  
58  
53  
51  
60  
56  
51  
49  
4.9  
4.8  
4.7  
4.7  
4.9  
4.8  
4.7  
4.7  
4.9  
4.8  
4.7  
4.6  
4.8  
4.7  
4.6  
4.6  
4.8  
4.7  
4.6  
4.6  
50  
62  
57  
55  
48  
59  
56  
54  
45  
55  
55  
53  
41  
51  
53  
51  
37  
46  
51  
49  
44  
56  
57  
55  
42  
53  
56  
54  
39  
50  
55  
53  
36  
46  
53  
51  
33  
42  
51  
49  
38  
50  
57  
55  
36  
47  
56  
54  
34  
44  
55  
53  
31  
41  
51  
49  
29  
38  
47  
45  
32  
43  
51  
48  
30  
41  
50  
48  
29  
39  
50  
48  
27  
36  
47  
44  
25  
34  
43  
41  
25  
37  
44  
42  
24  
35  
45  
42  
23  
34  
45  
42  
22  
32  
42  
40  
21  
30  
39  
37  
-
-
65  
60  
53  
51  
65  
59  
53  
50  
64  
58  
52  
50  
61  
56  
50  
47  
58  
53  
47  
45  
5.6  
5.3  
5.3  
5.4  
5.4  
5.2  
5.2  
5.3  
5.3  
5.1  
5.1  
5.2  
5.4  
5.1  
5.2  
5.2  
5.4  
5.2  
5.2  
5.3  
50  
60  
53  
51  
47  
57  
53  
50  
44  
54  
52  
50  
40  
49  
50  
47  
36  
44  
47  
45  
43  
54  
53  
51  
41  
51  
53  
50  
39  
48  
52  
50  
35  
44  
50  
47  
32  
40  
47  
45  
37  
48  
53  
51  
35  
45  
53  
50  
33  
43  
52  
50  
31  
39  
48  
46  
28  
36  
44  
42  
31  
42  
47  
44  
29  
40  
47  
44  
28  
38  
47  
44  
26  
35  
43  
41  
24  
32  
40  
38  
24  
35  
41  
38  
23  
34  
41  
39  
22  
32  
42  
39  
21  
30  
39  
36  
20  
28  
36  
34  
-
-
31  
38  
36  
-
24  
32  
29  
-
29  
34  
32  
-
23  
28  
25  
-
2500  
30  
39  
36  
-
24  
33  
31  
-
28  
35  
33  
-
22  
29  
27  
-
2250  
2000  
1750  
1500  
28  
39  
37  
-
23  
34  
32  
-
27  
36  
34  
-
22  
31  
28  
-
27  
37  
35  
-
22  
32  
30  
-
25  
34  
32  
-
21  
29  
27  
-
26  
35  
33  
21  
31  
29  
24  
32  
29  
20  
27  
25  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
105°F  
SENSIBLE CAPACITY1  
115°F  
EVAPORATOR  
COIL  
SENSIBLE CAPACITY1  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
61  
55  
49  
47  
61  
54  
48  
46  
60  
54  
48  
46  
57  
51  
45  
43  
54  
48  
43  
41  
6.1  
5.9  
5.9  
5.9  
6.0  
5.9  
5.8  
5.8  
6.0  
5.8  
5.7  
5.8  
6.0  
5.8  
5.7  
5.8  
6.0  
5.8  
5.7  
5.8  
48  
55  
49  
47  
45  
53  
48  
46  
42  
52  
48  
46  
38  
47  
45  
43  
34  
42  
43  
41  
41  
52  
49  
47  
39  
49  
48  
46  
37  
47  
48  
46  
34  
42  
45  
43  
30  
38  
43  
41  
35  
46  
49  
47  
33  
44  
48  
46  
32  
41  
48  
46  
29  
38  
44  
42  
26  
34  
39  
38  
29  
39  
42  
40  
28  
38  
42  
40  
26  
36  
43  
41  
24  
33  
39  
37  
22  
30  
35  
34  
22  
33  
36  
34  
22  
32  
37  
35  
21  
31  
37  
35  
19  
28  
34  
32  
18  
26  
31  
30  
-
-
57  
50  
44  
42  
57  
50  
44  
42  
57  
50  
44  
42  
53  
46  
41  
39  
49  
43  
38  
37  
6.7  
6.6  
6.5  
6.5  
6.6  
6.5  
6.4  
6.4  
6.6  
6.5  
6.4  
6.3  
6.5  
6.4  
6.3  
6.3  
6.5  
6.4  
6.3  
6.2  
46  
50  
44  
42  
43  
50  
44  
42  
41  
50  
44  
42  
37  
45  
41  
39  
33  
40  
38  
37  
39  
50  
44  
42  
38  
47  
44  
42  
36  
45  
44  
42  
32  
41  
41  
39  
28  
36  
38  
37  
33  
43  
44  
42  
32  
42  
44  
42  
30  
40  
44  
42  
27  
36  
39  
38  
24  
32  
35  
34  
27  
37  
38  
36  
26  
36  
38  
36  
25  
34  
38  
37  
23  
31  
35  
33  
20  
28  
31  
30  
20  
31  
31  
30  
20  
30  
32  
31  
20  
29  
33  
32  
18  
26  
30  
29  
16  
24  
27  
26  
-
-
27  
30  
28  
-
20  
23  
21  
-
24  
25  
23  
-
18  
19  
17  
-
2500  
26  
31  
29  
-
20  
25  
23  
-
24  
26  
25  
-
18  
20  
19  
-
2250  
2000  
1750  
1500  
25  
32  
30  
-
20  
27  
25  
-
24  
28  
26  
-
18  
22  
21  
-
24  
30  
28  
-
19  
25  
23  
-
22  
25  
24  
-
17  
21  
19  
-
22  
27  
26  
18  
23  
21  
20  
23  
22  
16  
19  
18  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE  
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input  
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.  
NOMINAL RATING  
10  
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 7: D(CE, CG)072 COOLING CAPACITIES (6 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
80  
80  
70  
68  
82  
82  
71  
69  
83  
83  
73  
71  
79  
79  
69  
67  
74  
74  
65  
63  
5.7  
5.7  
5.5  
5.6  
5.7  
5.7  
5.5  
5.6  
5.7  
5.7  
5.5  
5.6  
5.7  
5.7  
5.5  
5.6  
5.6  
5.6  
5.4  
5.5  
63  
76  
70  
68  
60  
73  
71  
69  
58  
70  
73  
71  
54  
65  
69  
67  
50  
60  
65  
63  
55  
68  
70  
68  
53  
65  
71  
69  
51  
63  
73  
71  
48  
59  
69  
67  
44  
55  
65  
63  
47  
60  
70  
68  
46  
58  
70  
69  
44  
56  
70  
71  
41  
53  
66  
67  
39  
50  
62  
63  
40  
53  
62  
60  
38  
51  
62  
62  
37  
49  
63  
64  
35  
47  
60  
61  
34  
44  
57  
58  
32  
45  
55  
52  
31  
43  
55  
55  
30  
42  
56  
57  
29  
40  
54  
54  
28  
39  
51  
52  
-
-
77  
77  
71  
71  
76  
76  
70  
70  
75  
75  
69  
69  
73  
73  
67  
67  
71  
71  
65  
65  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.3  
6.2  
6.3  
63  
75  
71  
71  
60  
73  
70  
70  
58  
70  
69  
69  
53  
65  
67  
67  
49  
59  
65  
65  
55  
68  
71  
71  
53  
66  
70  
70  
51  
64  
69  
69  
47  
59  
66  
66  
43  
54  
63  
63  
47  
60  
71  
71  
46  
58  
69  
70  
44  
57  
68  
68  
41  
52  
63  
63  
38  
48  
58  
58  
40  
53  
63  
63  
39  
51  
62  
62  
37  
50  
61  
61  
35  
46  
57  
57  
33  
43  
53  
53  
32  
45  
56  
56  
31  
44  
55  
55  
30  
43  
54  
54  
29  
40  
51  
51  
27  
38  
47  
47  
-
-
37  
47  
45  
-
30  
39  
37  
-
37  
48  
48  
-
30  
40  
40  
-
2700  
36  
48  
47  
-
29  
41  
40  
-
36  
48  
48  
-
29  
40  
40  
-
2550  
2400  
2100  
1800  
35  
49  
50  
-
28  
42  
43  
-
36  
47  
47  
-
29  
40  
40  
-
34  
47  
48  
-
28  
41  
42  
-
34  
45  
45  
-
28  
38  
39  
-
34  
46  
47  
28  
41  
42  
32  
42  
42  
27  
37  
37  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
105°F  
SENSIBLE CAPACITY1  
115°F  
EVAPORATOR  
COIL  
SENSIBLE CAPACITY1  
TOTAL  
CAP.1  
TOTAL  
CAP.1  
POWER  
INPUT2 kW  
POWER  
INPUT2 kW  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
MBH  
MBH  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
76  
71  
64  
64  
76  
71  
64  
64  
75  
70  
64  
64  
73  
68  
61  
61  
70  
65  
59  
59  
7.1  
7.1  
7.0  
7.0  
7.1  
7.1  
7.0  
7.0  
7.1  
7.1  
7.0  
7.0  
7.1  
7.1  
7.0  
7.0  
7.1  
7.0  
7.0  
6.9  
61  
70  
64  
64  
59  
69  
64  
64  
56  
68  
64  
64  
52  
63  
61  
61  
47  
57  
59  
59  
53  
66  
64  
64  
51  
64  
64  
64  
49  
61  
64  
64  
45  
56  
61  
61  
41  
51  
58  
58  
45  
58  
64  
64  
44  
56  
64  
64  
43  
54  
63  
63  
39  
50  
58  
58  
36  
46  
54  
53  
38  
50  
56  
56  
37  
49  
56  
56  
36  
48  
56  
56  
33  
44  
52  
52  
31  
41  
48  
48  
30  
43  
49  
49  
29  
42  
49  
49  
29  
41  
49  
49  
27  
38  
46  
46  
25  
35  
43  
43  
-
-
75  
65  
57  
57  
76  
66  
58  
58  
76  
66  
59  
59  
73  
63  
56  
56  
69  
60  
53  
53  
7.9  
7.8  
7.8  
7.7  
7.9  
7.9  
7.8  
7.7  
8.0  
7.9  
7.8  
7.7  
7.9  
7.8  
7.7  
7.7  
7.8  
7.8  
7.7  
7.6  
59  
65  
57  
57  
57  
66  
58  
58  
55  
66  
59  
59  
50  
61  
56  
56  
45  
55  
53  
53  
51  
64  
57  
57  
49  
61  
58  
58  
48  
59  
59  
59  
44  
54  
56  
56  
40  
49  
53  
53  
43  
56  
57  
57  
42  
54  
58  
58  
41  
52  
59  
58  
37  
48  
54  
53  
34  
44  
49  
49  
36  
48  
50  
50  
35  
47  
51  
50  
34  
45  
52  
51  
31  
42  
48  
47  
29  
39  
44  
44  
28  
41  
42  
42  
27  
40  
43  
43  
27  
38  
45  
44  
25  
36  
42  
41  
23  
33  
39  
38  
-
-
35  
41  
41  
-
27  
34  
34  
-
33  
34  
34  
-
25  
27  
27  
-
2700  
34  
42  
42  
-
27  
35  
34  
-
32  
36  
36  
-
25  
29  
29  
-
2550  
2400  
2100  
1800  
34  
42  
42  
-
27  
35  
35  
-
32  
38  
37  
-
25  
31  
30  
-
32  
40  
40  
-
26  
34  
34  
-
30  
35  
35  
-
24  
29  
29  
-
30  
38  
37  
25  
32  
32  
28  
33  
33  
23  
28  
27  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE  
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input  
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.  
NOMINAL RATING  
Unitary Products Group  
11  
 
255040-YTG-A-0506  
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
AIR  
UNIT  
FLOW  
CFM  
0.20  
WATTS RPM  
0.30  
WATTS RPM  
0.40  
WATTS RPM  
0.50  
WATTS RPM  
0.60  
WATTS RPM  
0.70  
WATTS RPM  
0.80  
TONNAGE  
RPM  
WATTS  
-
1700  
1600  
1500  
1400  
1300  
1200  
1100  
1000  
900  
835  
705  
880  
745  
923  
898  
871  
844  
816  
-
795  
740  
685  
640  
590  
-
969  
942  
917  
889  
862  
834  
809  
782  
-
860  
790  
730  
680  
635  
585  
550  
510  
-
1013  
986  
960  
932  
907  
881  
855  
829  
797  
970  
840  
775  
720  
675  
630  
590  
545  
500  
-
-
-
811  
655  
854  
695  
1029  
1003  
975  
951  
927  
900  
872  
843  
900  
825  
765  
715  
665  
625  
858  
540  
-
-
782  
610  
827  
650  
1046  
1018  
995  
970  
942  
919  
890  
905  
790  
750  
705  
665  
625  
580  
-
-
-
-
-
-
-
-
-
-
-
-
798  
595  
31,2  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
-
WATTS  
1700  
1600  
1500  
1400  
1300  
1200  
1100  
1000  
900  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1055  
1036  
1011  
987  
963  
936  
875  
780  
735  
690  
655  
615  
-
-
-
-
-
-
-
-
-
31, 2  
1066  
1047  
1028  
1005  
980  
850  
765  
720  
680  
645  
-
-
-
-
-
-
-
-
-
1075  
1060  
1040  
1020  
800  
750  
695  
660  
-
-
-
-
-
1084  
1068  
1050  
775  
715  
670  
-
-
-
-
-
-
1089  
1053  
735  
680  
1090  
690  
1. 230/460/575 Volts  
2. For 208 Volts multiply values by 0.95.  
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table  
for resistance values on applications other than gas / electric units with side duct airflows.  
12  
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
AIR  
UNIT  
FLOW  
CFM  
0.20  
WATTS RPM  
0.30  
WATTS RPM  
0.40  
WATTS RPM  
0.50  
WATTS RPM  
0.60  
WATTS RPM  
0.70  
WATTS RPM  
0.80  
WATTS  
TONNAGE  
RPM  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
843  
860  
880  
925  
919  
893  
867  
840  
818  
-
1005  
956  
930  
906  
881  
858  
842  
833  
-
1065  
993  
970  
944  
920  
898  
882  
867  
858  
847  
1145  
1030  
1008  
985  
961  
940  
922  
904  
893  
880  
1195  
1067  
1046  
1025  
1001  
980  
1235  
1170  
1100  
1030  
950  
817  
775  
854  
850  
920  
995  
905  
815  
740  
695  
650  
-
1065  
980  
900  
820  
755  
705  
665  
640  
1125  
1040  
970  
890  
835  
765  
725  
680  
790  
700  
828  
760  
840  
-
-
-
-
-
-
-
-
-
-
-
-
802  
670  
745  
41, 2  
-
-
-
-
-
-
-
-
-
-
665  
-
-
-
-
962  
895  
-
942  
820  
-
932  
785  
-
-
-
916  
730  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
1103  
1085  
1064  
1040  
1020  
1003  
982  
WATTS  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
1270  
1210  
1145  
1075  
1005  
945  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1102  
1081  
1060  
1044  
1024  
1010  
992  
1180  
1115  
1050  
995  
920  
870  
815  
-
-
1121  
1100  
1086  
1067  
1053  
1034  
1140  
1085  
1035  
965  
-
41, 2  
-
-
880  
1107  
1099  
1080  
1000  
960  
970  
835  
920  
953  
780  
855  
905  
1. 230/460/575 Volts  
2. For 208 Volts multiply values by 0.95.  
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for  
resistance values on applications other than gas / electric units with side duct airflows.  
Unitary Products Group  
13  
 
255040-YTG-A-0506  
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
0.40 0.50 0.60  
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS  
UNIT  
AIR FLOW  
CFM  
0.20  
0.30  
0.70  
0.80  
TONNAGE  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
1059  
1560  
1077  
1590  
1095  
1074  
1049  
1022  
983  
941  
894  
855  
-
1630  
1525  
1370  
1190  
1080  
1000  
885  
815  
-
1114  
1094  
1069  
1044  
1010  
976  
940  
903  
884  
864  
-
1650  
1560  
1440  
1250  
1100  
1020  
940  
1134  
1116  
1090  
1066  
1039  
1009  
980  
1660  
1595  
1475  
1350  
1160  
1050  
980  
1158  
1140  
1116  
1090  
1064  
1040  
1014  
988  
1685  
1620  
1505  
1410  
1260  
1100  
1020  
940  
1181  
1167  
1142  
1117  
1092  
1070  
1047  
1022  
1001  
987  
1720  
1640  
1535  
1440  
1340  
1225  
1095  
970  
1032  
1405  
1054  
1470  
1005  
1260  
1024  
1275  
980  
1160  
1002  
1170  
930  
1060  
957  
1070  
51, 2  
877  
950  
908  
975  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
860  
950  
905  
815  
925  
850  
964  
880  
910  
-
-
770  
908  
805  
948  
835  
870  
-
-
-
882  
740  
926  
780  
965  
830  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
1.10 1.20 1.30  
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS  
UNIT  
AIR FLOW  
CFM  
0.90  
1.00  
1.40  
1.50  
TONNAGE  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193  
1170  
1148  
1121  
1100  
1079  
1058  
1035  
1020  
1004  
1665  
1580  
1480  
1385  
1285  
1180  
1060  
960  
-
-
-
-
-
-
-
-
-
-
-
-
-
1202  
1180  
1155  
1133  
1110  
1090  
1071  
1056  
1038  
1620  
1530  
1425  
1340  
1240  
1135  
1030  
965  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1190  
1169  
1143  
1122  
1103  
1088  
1070  
1475  
1385  
1280  
1190  
1100  
1035  
925  
-
-
-
-
-
-
-
-
51, 2  
1205  
1178  
1158  
1134  
1118  
1101  
1445  
1330  
1240  
1140  
1065  
980  
-
-
-
-
-
-
1222  
1196  
1164  
1145  
1130  
1375  
1295  
1175  
1105  
1045  
-
-
-
-
-
-
-
-
1197  
1170  
1158  
1205  
1130  
1075  
-
-
900  
1198  
1184  
1150  
1110  
860  
880  
1. 230/460/575 Volts  
2. For 208 Volts multiply values by 0.95.  
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for  
resistance values on applications other than gas / electric units with side duct airflows.  
14  
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
AIR  
UNIT  
FLOW  
CFM  
0.20  
WATTS RPM  
0.30  
WATTS RPM  
0.40  
WATTS RPM  
0.50  
WATTS RPM  
0.60  
WATTS RPM  
0.70  
WATTS RPM  
0.80  
WATTS  
TONNAGE  
RPM  
1150  
1100  
1045  
985  
930  
-
3200  
3000  
2800  
2600  
2400  
2200  
2000  
1800  
2325  
1182  
1129  
1074  
1015  
958  
905  
-
2425  
1212  
1157  
1102  
1045  
990  
933  
-
2525  
-
-
-
-
-
-
-
-
2010  
2090  
1780  
1475  
1300  
1070  
-
2150  
1850  
1540  
1350  
1160  
-
1185  
1131  
1075  
1020  
965  
919  
-
2225  
1940  
1630  
1400  
1210  
1025  
-
1215  
1160  
1103  
1051  
997  
2290  
2025  
1715  
1430  
1250  
1100  
925  
1242  
1190  
1135  
1081  
1028  
982  
2360  
2075  
1760  
1490  
1285  
1130  
1005  
-
-
1700  
1217  
1163  
1111  
1060  
1014  
968  
2130  
1825  
1600  
1325  
1160  
1030  
1425  
61, 2  
1240  
-
-
-
-
950  
-
-
-
-
-
909  
939  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
-
WATTS  
3200  
3000  
2800  
2600  
2400  
2200  
2000  
1800  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1245  
1193  
1142  
1090  
1045  
998  
2190  
1920  
1675  
1380  
1175  
1050  
-
-
-
-
-
-
-
-
-
-
1222  
1173  
1124  
1077  
1028  
1990  
1730  
1450  
1200  
1060  
1250  
1205  
1155  
1109  
1058  
2060  
1800  
1550  
1275  
1060  
-
-
-
-
-
-
-
61, 2  
1234  
1186  
1140  
1087  
1885  
1640  
1360  
1075  
-
-
-
-
-
-
1217  
1170  
1118  
1710  
1460  
1150  
1249  
1205  
1148  
1775  
1545  
1250  
-
-
1235  
1176  
1600  
1360  
1. 230/460/575 Volts  
2. For 208 Volts multiply values by 0.95.  
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for  
resistance values on applications other than gas / electric units with side duct airflows.  
Unitary Products Group  
15  
 
255040-YTG-A-0506  
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION  
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG  
0.30 0.40 0.50  
WATTS  
UNIT  
MOTOR SPEED  
0.20  
0.60  
TONNAGE  
CFM  
-
WATTS  
-
CFM  
-
WATTS  
-
CFM  
1699  
1582  
1421  
1868  
1714  
1604  
2274  
2145  
2029  
2361  
WATTS  
825  
CFM  
1650  
1524  
1367  
1795  
1650  
1541  
2167  
2071  
1965  
2260  
CFM  
1570  
1410  
1315  
1722  
1589  
1490  
2096  
1990  
1905  
2178  
WATTS  
755  
HI  
MED  
LOW  
HI  
785  
720  
650  
880  
765  
695  
1045  
990  
910  
1350  
31  
1684  
1487  
1996  
1804  
1681  
2400  
2290  
2150  
2461  
800  
1631  
1464  
1933  
1765  
1640  
2338  
2214  
2100  
2402  
780  
750  
690  
710  
690  
670  
620  
960  
936  
910  
845  
41  
MED  
LOW  
HI  
838  
810  
785  
735  
760  
738  
715  
670  
1155  
1105  
1020  
1480  
1125  
1065  
990  
1095  
1030  
950  
1010  
950  
51  
61  
MED  
LOW  
HI  
880  
1440  
1395  
1305  
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG  
UNIT  
MOTOR SPEED  
0.70  
0.80 0.90  
1.00  
TONNAGE)  
CFM  
1430  
1324  
1246  
1635  
1508  
1416  
1990  
1911  
1816  
2101  
WATTS  
725  
CFM  
1360  
1260  
1185  
1544  
1407  
1337  
1887  
1828  
1724  
2000  
WATTS  
700  
CFM  
1280  
1185  
1110  
1419  
1306  
1230  
1771  
1724  
1644  
1914  
WATTS  
680  
CFM  
1180  
1100  
1020  
1300  
1195  
1120  
1629  
1604  
1531  
1830  
WATTS  
655  
HI  
MED  
LOW  
HI  
31  
650  
630  
610  
590  
605  
590  
570  
545  
820  
790  
765  
740  
41  
MED  
LOW  
HI  
705  
675  
645  
625  
645  
620  
595  
575  
980  
945  
905  
855  
51  
61  
MED  
LOW  
HI  
920  
885  
835  
798  
838  
800  
770  
710  
1260  
1205  
1155  
1110  
1. Side Duct application (230/460/575 Volts)  
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance  
values.  
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA  
BELT  
(NOTCHED)  
1
ADJUSTABLE MOTOR PULLEY  
FIXED BLOWER PULLEY  
OUTSIDE PITCH  
MOTOR  
BLOWER  
RANGE  
(RPM)  
MODEL  
SIZE  
OUTSIDE  
DIA.  
(IN.)  
PITCH  
DIA.  
(IN.)  
PITCH  
LENGTH QTY.  
DESIG-  
NATION  
BORE DESIG-  
(IN.)  
BORE DESIG-  
HP FRAME  
DIA.  
(IN.)  
DIA.  
(IN.)  
NATION  
(IN.)  
NATION  
(IN.)  
37.3  
37.3  
37.3  
37.3  
3 TON  
4 TON  
5 TON  
6 TON  
790/1120 1 1/2  
790/1120 1 1/2  
850/1220 1 1/2  
900/1250 1 1/2  
56  
56  
56  
56  
1VL40  
1VL40  
1VL40  
1VL44  
2.7-3.7  
2.7-3.7  
2.7-3.7  
3.1-4.1  
2.4-3.4  
2.4-3.4  
2.4-3.4  
2.8-3.8  
5/8  
5/8  
5/8  
7/8  
AK61  
AK61  
AK56  
AK56  
5.9  
5.9  
5.4  
5.4  
5.7  
5.7  
5.2  
5.2  
1
1
1
1
A36  
A36  
A36  
A36  
1
1
1
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located  
in the moving air, upstream of any heating device.  
16  
Unitary Products Group  
   
255040-YTG-A-0506  
TABLE 14: STATIC RESISTANCES  
RESISTANCE, IWG  
CFM  
DESCRIPTION  
1000  
1200  
0.08  
0.05  
0.07  
0.07  
0.10  
1400  
0.09  
0.06  
0.08  
0.08  
0.12  
1600  
0.11  
0.07  
0.09  
0.09  
0.14  
1800  
2000  
0.15  
0.10  
0.13  
0.11  
0.18  
2200  
2400  
0.20  
0.14  
0.17  
0.14  
0.23  
2600  
0.23  
0.16  
0.20  
0.16  
0.26  
2800  
0.26  
0.19  
0.23  
0.19  
0.29  
3000  
0.30  
0.22  
0.26  
0.22  
0.32  
ECONOMIZER1 3  
0.07  
0.04  
0.06  
0.06  
0.08  
0.13  
0.08  
0.11  
0.10  
0.16  
0.17  
0.12  
0.15  
0.12  
0.20  
ELECTRIC  
HEATERS1  
7-15KW  
20-30KW  
BOTTOM DUCT CONNECTIONS1  
COOLING ONLY2  
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.  
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.  
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air  
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 15: ELECTRIC HEATER CFM LIMITATIONS  
MINIMUM SUPPLY AIR CFM  
UNITMODELSIZE NOMINAL  
VOLTAGE  
HEATER SIZE NOMINAL KW  
TONS  
5
7
10  
15  
20  
30  
208/230-3-60  
460-3-60  
1100  
1100  
1100  
-
1200  
1200  
1200  
1300  
1300  
1300  
1600  
1600  
1600  
1800  
1800  
1800  
1200  
1200  
1200  
1300  
1300  
1300  
1600  
1600  
1600  
1800  
1800  
1800  
1300  
1300  
1300  
1300  
1300  
1400  
1600  
1600  
1600  
1800  
1800  
1800  
-
3
-
-
575-3-60  
-
-
208/230-3-60  
460-3-60  
1300  
1300  
1300  
-
-
4
5
6
-
-
575-3-60  
-
-
208/230-3-60  
460-3-60  
1600  
1600  
1600  
1600  
1800  
1800  
-
1600  
1600  
1800  
1800  
1800  
1800  
-
575-3-60  
-
208/230-3-60  
460-3-60  
1800  
-
-
575-3-60  
Unitary Products Group  
17  
   
255040-YTG-A-0506  
TABLE 16: ELECTRICAL DATA - D(CE, CG)036-072 DIRECT DRIVE  
COMPRESSORS  
ID  
MIN.  
CIRCUIT  
AMPACITY  
(AMPS)  
19.9  
19.9  
24.9  
33.3  
46.8  
60.7  
19.9  
21.4  
28.1  
37.4  
53.3  
69.2  
10.8  
13  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER  
MODEL NO.  
HEATER  
KW  
HEATER  
AMPS  
VOLTAGE  
RLA  
LRA  
SIZE  
(AMPS)  
25  
25  
30  
35  
50  
70  
25  
30  
30  
40  
60  
70  
15  
15  
20  
25  
35  
15  
15  
25  
30  
30  
30  
35  
35  
50  
70  
30  
30  
35  
40  
60  
70  
15  
15  
20  
25  
35  
15  
15  
25  
30  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
--  
4
--  
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
2
5.6  
8
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
6.8  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
--  
4
5.6  
8
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
6.8  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
208-3-60  
11.4  
11.4  
90.0  
90.0  
1.3  
1.3  
4.4  
4.4  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2
2CE04510525  
2CE04510725  
2
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
None  
D(CE, CG)  
036  
(3.0)  
2
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
8.2  
2
460-3-60  
575-3-60  
6.2  
5.0  
45.0  
36.0  
0.8  
0.8  
2.2  
2.2  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
17.9  
23.2  
32.1  
8.7  
14.9  
21.3  
27.7  
23.9  
23.9  
25.7  
34  
47.5  
61.4  
23.9  
23.9  
28.8  
38.1  
54.1  
70  
11.9  
13  
17.9  
23.2  
32.1  
9.7  
14.9  
21.3  
27.7  
2
2
None  
2CE04511058  
2CE04511558  
2CE04512058  
None  
2
2CE04510525  
2CE04510725  
2
208-3-60  
230-3-60  
14.1  
14.1  
105.0  
105.0  
1.3  
1.3  
5.0  
5.0  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2
2CE04510525  
2CE04510725  
2
2CE04511025  
2CE04511525  
2CE04512025  
None  
D(CE, CG)  
048  
(4.0)  
2
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
8.2  
2
460-3-60  
575-3-60  
7.1  
5.8  
55.0  
44.0  
0.8  
0.8  
2.2  
2.2  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
2
2
None  
2CE04511058  
2CE04511558  
2CE04512058  
18  
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 16: ELECTRICAL DATA - D(CE, CG)036-072 DIRECT DRIVE (CONT.)  
COMPRESSORS  
ID  
MIN.  
CIRCUIT  
AMPACITY  
(AMPS)  
27.9  
27.9  
27.9  
36  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER  
MODEL NO.  
HEATER  
KW  
HEATER  
AMPS  
VOLTAGE  
RLA  
LRA  
SIZE  
(AMPS)  
35  
35  
35  
40  
50  
70  
90  
35  
35  
40  
45  
60  
80  
100  
20  
20  
20  
25  
35  
50  
15  
20  
25  
30  
40  
40  
40  
40  
50  
50  
70  
90  
40  
40  
40  
50  
60  
80  
100  
25  
25  
25  
25  
35  
50  
15  
20  
25  
30  
40  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
--  
4
5.6  
8
11.9  
15.9  
22.2  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
--  
--  
2
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
2
208-3-60  
16.0  
16.0  
125.0  
125.0  
1.3  
1.3  
6.6  
6.6  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
49.5  
63.4  
85.3  
27.9  
27.9  
30.8  
40.1  
56.1  
72  
97.3  
14.1  
14.3  
19.3  
24.6  
33.4  
47.4  
11.3  
16  
22.4  
28.8  
39.9  
31.7  
31.7  
31.7  
36.3  
49.8  
63.7  
85.5  
31.7  
31.7  
31.7  
40.4  
56.3  
72.2  
97.5  
16.3  
16.3  
19.7  
24.9  
33.8  
47.8  
13  
2
2CE04510525  
2
2CE04510725  
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
D(CE, CG)  
060  
(5.0)  
2
2CE04510746  
6.8  
8.2  
2
2CE04511046  
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
--  
4
5.6  
8
11.9  
15.9  
22.2  
--  
5.3  
7.5  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
460-3-60  
575-3-60  
8.0  
6.4  
66.5  
50.0  
0.8  
0.8  
3.3  
3.3  
2
2CE04511546  
2
2CE04512046  
2
2CE04513046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
None  
2
2CE04510525  
2
2CE04510725  
208-3-60  
230-3-60  
18.9  
18.9  
146.0  
146.0  
1.3  
1.3  
6.8  
6.8  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2
2CE04510525  
2
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
10.6  
15.9  
21.2  
29.6  
--  
D(CE, CG)  
072  
(6.0)  
2
2CE04510746  
6.8  
8.2  
2
2CE04511046  
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
9.5  
7.6  
73.0  
58.4  
0.8  
0.8  
3.6  
3.6  
2
2CE04511546  
2
2CE04512046  
2
2CE04513046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
16.3  
22.7  
29.1  
40.2  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
Unitary Products Group  
19  
255040-YTG-A-0506  
TABLE 17: ELECTRICAL DATA - D(CE, CG)036-072 BELT DRIVE  
COMPRESSORS  
ID  
MIN.  
CIRCUIT  
AMPACITY  
(AMPS)  
20.8  
20.8  
25.9  
34.3  
47.8  
61.7  
20.8  
22.4  
29.1  
38.4  
54.3  
70.2  
11.1  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER  
MODEL NO.  
HEATER  
KW  
HEATER  
AMPS  
VOLTAGE  
RLA  
LRA  
SIZE  
(AMPS)  
30  
30  
30  
35  
50  
70  
30  
30  
30  
40  
60  
80  
15  
15  
20  
25  
35  
15  
20  
25  
30  
35  
35  
35  
35  
50  
70  
35  
35  
35  
40  
60  
80  
15  
15  
20  
25  
35  
15  
20  
25  
30  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
--  
4
--  
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
2
5.6  
8
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
6.8  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
--  
4
5.6  
8
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
6.8  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
208-3-60  
11.4  
11.4  
90.0  
90.0  
1.3  
1.3  
5.2  
5.2  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2
2CE04510525  
2CE04510725  
2
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
None  
D(CE, CG)  
036  
(3.0)  
2
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
8.2  
13.5  
18.4  
23.7  
32.6  
8.9  
15.2  
21.6  
28  
24.1  
24.1  
25.9  
34.3  
47.8  
61.7  
24.1  
24.1  
29.1  
38.4  
54.3  
70.2  
12.3  
13.5  
18.4  
23.7  
32.6  
9.9  
2
460-3-60  
575-3-60  
6.2  
5.0  
45.0  
36.0  
0.8  
0.8  
2.6  
2.0  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
2
2
None  
2CE04511058  
2CE04511558  
2CE04512058  
None  
2
2CE04510525  
2CE04510725  
2
208-3-60  
230-3-60  
14.1  
14.1  
105.0  
105.0  
1.3  
1.3  
5.2  
5.2  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2
2CE04510525  
2CE04510725  
2
2CE04511025  
2CE04511525  
2CE04512025  
None  
D(CE, CG)  
048  
(4.0)  
2
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
8.2  
2
460-3-60  
575-3-60  
7.1  
5.8  
55.0  
44.0  
0.8  
0.8  
2.6  
2.0  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
2
2
None  
2CE04511058  
2CE04511558  
2CE04512058  
15.2  
21.6  
28  
20  
Unitary Products Group  
 
255040-YTG-A-0506  
TABLE 17: ELECTRICAL DATA - D(CE, CG)036-072 BELT DRIVE (CONT.)  
COMPRESSORS  
ID  
MIN.  
CIRCUIT  
AMPACITY  
(AMPS)  
26.5  
26.5  
26.5  
34.3  
47.8  
61.7  
83.5  
26.5  
26.5  
29.1  
38.4  
54.3  
70.2  
95.5  
13.4  
13.5  
18.4  
23.7  
32.6  
46.6  
10.6  
15.2  
21.6  
28  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER  
MODEL NO.  
HEATER  
KW  
HEATER  
AMPS  
VOLTAGE  
RLA  
LRA  
SIZE  
(AMPS)  
35  
35  
35  
40  
50  
70  
90  
35  
35  
40  
40  
60  
80  
100  
20  
20  
20  
25  
35  
50  
15  
20  
25  
30  
40  
40  
40  
40  
45  
50  
70  
90  
40  
40  
40  
45  
60  
70  
100  
20  
20  
20  
25  
35  
50  
15  
20  
25  
30  
40  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
--  
4
5.6  
8
11.9  
15.9  
22.2  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
--  
--  
2
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
2
208-3-60  
16.0  
16.0  
125.0  
125.0  
1.3  
1.3  
5.2  
5.2  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2
2CE04510525  
2
2CE04510725  
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
D(CE, CG)  
060  
(5.0)  
2
2CE04510746  
6.8  
8.2  
2
2CE04511046  
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
--  
4
5.6  
8
11.9  
15.9  
22.2  
--  
5.3  
7.5  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
460-3-60  
575-3-60  
8.0  
6.4  
66.5  
50.0  
0.8  
0.8  
2.6  
2.0  
2
2CE04511546  
2
2CE04512046  
2
2CE04513046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
None  
39.1  
29.9  
29.9  
29.9  
34  
47.5  
61.4  
83.3  
29.9  
29.9  
29.9  
38.1  
54.1  
70  
95.3  
15.2  
15.2  
18.3  
23.6  
32.4  
46.4  
12.1  
15.2  
21.6  
28  
2
2CE04510525  
2
2CE04510725  
208-3-60  
230-3-60  
18.9  
18.9  
146.0  
146.0  
1.3  
1.3  
5.0  
5.0  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2
2CE04510525  
2
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
10.6  
15.9  
21.2  
29.6  
--  
D(CE, CG)  
072  
(6.0)  
2
2CE04510746  
6.8  
8.2  
2
2CE04511046  
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
9.5  
7.6  
73.0  
58.4  
0.8  
0.8  
2.5  
2.0  
2
2CE04511546  
2
2CE04512046  
2
2CE04513046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
39.1  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
Unitary Products Group  
21  
255040-YTG-A-0506  
TABLE 18: PHYSICAL DATA  
D(CE, CG)  
MODELS  
Centrifugal Blower (Dia. x Wd. in.)  
036  
12 X 10  
1/2  
048  
060  
12 X 10  
1
072  
12 X 11  
1
12 X 10  
3/4  
EVAPORATOR  
BLOWER  
Fan Motor HP (Direct Drive)  
Fan Motor HP (Belt Drive)  
Rows Deep  
1 1/2  
3
1 1/2  
3
1 1/2  
3
1 1/2  
4
EVAPORATOR  
COIL  
Fins Per Inch  
13  
13  
13  
13  
Face Area (Sq. Ft.)  
Propeller Dia. (in.)  
Fan Motor Hp  
3.6  
4.3  
5.1  
5.1  
24  
24  
24  
24  
CONDENSER  
FANS  
1/4  
1/4  
1/4  
1/4  
Nom. CFM  
3400  
1
3400  
1
3400  
1
3400  
2
Rows Deep  
CONDENSER  
COILS  
Fins Per Inch  
16  
16  
22  
16  
Face Area (Sq. Ft.)  
17.1  
17.1  
17.1  
16.7  
COMPRESSOR  
(Qty. Per Unit)  
Scroll Type  
1
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)  
Quantity Per Unit (14” X 25” X 1” or 2“)  
Total Face Area (sq. ft.)  
2
1
2
1
2
1
2
1
AIR  
FILTERS  
6.3  
6.3  
6.3  
6.3  
Refrigerant 22  
(lbs./oz.)  
CHARGE  
5/8  
6/8  
6/8  
10/0  
1
TABLE 19: ELECTRIC HEAT CORRECTION FACTORS  
kW CAP. MULTI-  
TABLE 20: VOLTAGE LIMITATIONS  
VOLTAGE  
NOMINAL VOLTAGE  
VOLTAGE  
POWER SUPPLY  
PLIER  
MIN.  
187  
414  
540  
MAX.  
208  
230  
460  
575  
0.75  
0.92  
0.92  
0.92  
208  
240  
480  
600  
208/230-3-60  
460-3-60  
253  
506  
630  
575-3-60  
1. Utilization Range “A” in accordance with ARI Standard  
110.  
22  
Unitary Products Group  
     
255040-YTG-A-0506  
TYPICAL POWER WIRING  
REFER TO THE ELECTRICAL DATA  
TABLES TO SIZE THE DISCONNECT  
SWITCH, OVERCURRENT PROTEC-  
TION AND WIRING.  
TYPICAL CONTROL WIRING  
COOLING ONLY (24 VOLT THERMOSTAT)  
COOLING / HEATING (24 VOLT THERMOSTAT)  
THERMOSTAT1 UNIT TERMINAL  
THERMOSTAT1  
TERMINALS  
TERMINALS  
STRIP TB1  
UNIT TERMINAL  
STRIP TB1  
RV  
R
RH  
ADD  
JUMPER  
24 VOLT  
TRANSFORMER  
YC  
GF  
Y1  
Y2  
G
RC  
Y
R
Y1  
Y2  
W1  
W2  
G
24 VOLT  
TRANSFORMER  
W
G
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER  
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.  
C
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
MULTI STAGE  
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND  
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF  
HEAT, USE THERMOSTAT 2TH0471024.  
1
THERMOSTAT  
TERMINALS  
UNIT TERMINAL  
STRIP TB1  
RC  
RH  
Y1  
24 VOLT  
TRANSFORMER  
ADD  
JUMPER  
R
Y1  
Y2  
W1  
W2  
G
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
SINGLE STAGE  
2
3
Y2  
W1  
THERMOSTAT1  
TERMINALS  
4
W2  
UNIT TERMINAL  
STRIP TB1  
G
B
RH  
RC  
Y
C
R
Y1  
W1  
G
LED 1  
X
ADD  
JUMPER  
NOT  
USED  
LED 2  
COM  
A1  
OCC  
W
4
G
ADD  
JUMPER  
C
A2  
24 VOLT  
TRANSFORMER  
T
TO REMOTE SENSOR  
2TH040702224 IF USED  
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).  
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.  
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).  
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT  
2TH04700224.  
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE  
ELECTRIC HEATER.  
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR  
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY  
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE  
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.  
FIGURE 2 -  
TYPICAL FIELD POWER & CONTROL WIRING  
Unitary Products Group  
23  
 
255040-YTG-A-0506  
FIGURE 3 -  
UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW  
FIGURE 4 -  
UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW  
24  
Unitary Products Group  
   
255040-YTG-A-0506  
DETAIL “A”  
FIGURE 5 -  
UNIT WITH ECONOMIZER RAINHOOD  
DETAIL “B”  
FIGURE 6 -  
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD  
Unitary Products Group  
25  
   
255040-YTG-A-0506  
FIGURE 7 -  
UNIT DIMENSIONS (REAR VIEW)  
TABLE 22: MINIMUM CLEARANCES  
LOCATION  
CLEARANCE  
24” (Cooling/Electric Heat)  
32” (Gas Heat)  
Front  
Rear  
FILTER  
ACCESS  
12” (Less Economizer)  
36” (With Economizer or Fixed  
Air/Motorized Damper)  
BLOWER MOTOR  
ACCESS  
DOT PLUGS  
24” (Less Economizer)  
36” (With Economizer)  
Left Side (Filter Access)  
FIELD-SUPPLIED  
DISCONNECT SWITCH  
LOCATION  
Right Side (Cond. Coil)  
Below Unit1  
24”  
0”  
MOUNTING BRACKET  
FOR DICONNECT SWITCH  
(Shipped attached to the  
blower housing inside  
72” (For  
Condenser Air Discharge)  
A,B  
WIRING ENTRY  
(See Detail “B”)  
the blower compartment)  
Above Unit2  
CONTROL BOX  
ACCESS  
DISCONNECT SWITCH LOCATION  
AND MOTOR ACCESS PANEL FOR  
UNIT WITH “BELT-DRIVE” OPTION  
1. Units may be installed on combustible floors made  
from wood or class A, B, or C roof covering material.  
2. Units must be installed outdoors. Overhanging struc-  
tures or shrubs should not obstruct condenser air dis-  
charge outlet.  
FIGURE 8 -  
DISCONNECT/BLOWER ACCESS LOCA-  
TION  
TABLE 21: UTILITIES ENTRY  
HOLE  
OPENING SIZE (DIA.)  
USED FOR  
Side  
Bottom  
Side  
1
2
A
7/8” KO  
Control Wiring  
Power Wiring  
B
2” KO  
Bottom  
C
D
1-5/8” KO  
1-1/2” KO  
Gas Piping (Front)  
Gas Piping (Bottom)  
1. Opening in the bottom to the unit can be located by the  
side in the insulation.  
2. Do not remove the 2” knockout ring.  
26  
Unitary Products Group  
         
255040-YTG-A-0506  
FIGURE 9 -  
TYPICAL APPLICATIONS  
Unitary Products Group  
27  
 
255040-YTG-A-0506  
BACK OF UNIT  
BACK OF UNIT  
821/4  
A
A
447/8  
447/8  
821/4  
B
D
F
X
X
B
C
E
APPROXIMATE  
APPROXIMATE  
CENTER OF GRAVITY  
CENTER OF GRAVITY  
CONDENSER COIL  
END OF UNIT  
CONDENSER COIL  
END OF UNIT  
C
D
FRONT OF UNIT  
FRONT OF UNIT  
Y
Y
FIGURE 10 - FOUR AND SIX POINT LOADING  
TABLE 23: D(CE, CG) 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION  
4-Point Loading (lb)  
6-Point Loading (lb)  
UNIT  
TOTAL  
A
B
C
D
A
B
C
82  
D
E
F
125  
134  
139  
137  
148  
152  
142  
155  
158  
160  
173  
175  
123  
132  
136  
134  
145  
149  
140  
153  
155  
157  
170  
172  
157  
168  
173  
171  
184  
190  
178  
194  
197  
200  
216  
219  
160  
171  
177  
174  
188  
194  
181  
198  
201  
203  
220  
223  
84  
90  
83  
104  
112  
115  
113  
123  
126  
118  
129  
131  
133  
144  
146  
105  
113  
117  
115  
124  
128  
119  
131  
132  
134  
146  
147  
107  
114  
118  
116  
126  
129  
121  
132  
134  
136  
147  
149  
DCE036 Cooling/ Electric  
DCG036N040  
565  
605  
625  
615  
665  
685  
640  
700  
710  
720  
780  
790  
89  
88  
93  
92  
91  
DCG036N079  
91  
90  
89  
DCE048 Cooling/ Electric  
DCG048N060  
99  
98  
96  
102  
95  
100  
94  
99  
DCG048N099  
93  
DCE060 Cooling/ Electric  
DCG060N079  
104  
105  
107  
116  
117  
103  
104  
106  
114  
116  
101  
103  
104  
113  
114  
DCG060N099  
DCE072 Cooling/ Electric  
DCG072N079  
DCG072N099  
TABLE 24: CENTER OF GRAVITY  
DIMENSION  
3 - 5 TON  
40-¾”  
6 TON  
X
Y
44”  
22”  
19-¾”  
28  
Unitary Products Group  
     
255040-YTG-A-0506  
TABLE 25: OPERATING WEIGHTS (LBS.)  
MODEL SIZE  
DCE (Cooling Only)  
3 TON  
565  
605  
-
4 TON  
5 TON  
640  
-
6 TON  
720  
-
615  
-
N040  
N060  
N079  
N099  
BASIC  
UNIT  
665  
-
-
-
DCG  
(Gas/Electric)  
625  
-
700  
710  
780  
790  
685  
Economizer  
Motorized Damper  
50  
26  
18  
23  
28  
92  
10  
5
5 - 7 kW  
10 - 15 kW  
20 - 30 kW  
OPTIONS  
OR  
ACCY.  
Electric Heater  
Roof Curb  
Barometric Relief / Fixed Air Damper  
Belt-Drive Blower  
FIGURE 11 - ROOF CURB DIMENSIONS  
Unitary Products Group  
29  
   
255040-YTG-A-0506  
FIGURE 12 - COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 208/230V AND 460V DIAGRAM  
30  
Unitary Products Group  
 
255040-YTG-A-0506  
FIGURE 13 - COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 575 VOLT DIAGRAM  
Unitary Products Group  
31  
 
255040-YTG-A-0506  
FIGURE 14 - COOLING UNIT WITH ELECTRIC HEAT CONTROL CIRCUIT 208/230V, 460V AND 575V  
DIAGRAM  
32  
Unitary Products Group  
 
255040-YTG-A-0506  
FIGURE 15 - COOLING UNIT POWER CIRCUIT 208/230-3-60 DIRECT DRIVE INDOOR BLOWER DIAGRAM  
Unitary Products Group  
33  
 
255040-YTG-A-0506  
FIGURE 16 - COOLING UNIT POWER CIRCUIT 208/230-3-60 BELT DRIVE INDOOR BLOWER DIAGRAM  
34  
Unitary Products Group  
 
255040-YTG-A-0506  
FIGURE 17 - COOLING UNIT POWER CIRCUIT 460-3-60 DIRECT DRIVE INDOOR BLOWER DIAGRAM  
Unitary Products Group  
35  
 
255040-YTG-A-0506  
FIGURE 18 - COOLING UNIT POWER CIRCUIT 460-3-60 BELT DRIVE INDOOR BLOWER DIAGRAM  
36  
Unitary Products Group  
 
255040-YTG-A-0506  
FIGURE 19 - COOLING UNIT POWER CIRCUIT 575-3-60 DIRECT DRIVE INDOOR BLOWER DIAGRAM  
Unitary Products Group  
37  
 
255040-YTG-A-0506  
FIGURE 20 - COOLING UNIT POWER CIRCUIT 575-3-60 BELT DRIVE INDOOR BLOWER DIAGRAM  
38  
Unitary Products Group  
 
255040-YTG-A-0506  
UNIT CABINET  
GUIDE SPECIFICATIONS  
Unit cabinet shall be constructed of G90 galvanized steel,  
with exterior surfaces coated with a non-chalking, powdered  
paint finish, certified at 1000 hours salt spray test per  
ASTMB117 standards. Indoor blower section shall be insu-  
lated with a minimum 1/2” thick insulation, coated on the air-  
side. Aluminum foil faced insulation shall be used in the  
furnace compartment and be fastened with ridged fasteners  
to prevent insulation from entering the air stream. Cabinet  
panels shall be “large” size, easily removable for servicing  
and maintenance. Full perimeter base rails shall be provided  
to assure reliable transit of equipment, overhead rigging and  
proper sealing on roof curb applications. Disposable 1" filters  
shall be furnished and be accessible through a removable  
access door, sealed airtight. Units filter track shall be  
designed to accommodate either 1” or 2” filters. Fan perfor-  
mance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evaporator  
fan performance without removing panels or creating air by-  
pass of the coils. Condensate pan shall be internally sloped  
and conform to ASHRAE 62-89 self-draining standards. Con-  
densate connection shall be a minimum of 3/4” I.D. female  
and be a ridged mount connection.  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility.  
TM  
York's Sunline 2000 units are convertible single package-  
units. Although the units are primarily designed for curb  
mounting on a roof, they can also be slab-mounted at ground  
level or set on steel beams above a finished roof. Cooling  
only and cooling with gas heat models are available with a  
wide variety of factory-mounted options and field-installed  
accessories to make them suitable for almost every applica-  
tion. All units are self-contained and assembled on full perim-  
eter base rails with holes in the four corners for overhead  
rigging. Every unit is completely piped, wired, charged and  
tested at the factory to simplify the field installation and to  
provide years of dependable operation. All models (including  
those with an economizer) are suitable for either bottom or  
horizontal duct connections. Models with power exhaust are  
suitable for bottom duct connections only. For bottom duct,  
remove the sheet metal panels from the supply and return air  
openings through the base of the unit. For horizontal duct,  
remove the supply and return air panels on the rear of the  
unit.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
The indoor fan shall be direct drive, multi-speed, or a factory  
installed belt drive assembly that includes an adjustable pitch  
motor pulley. Job site selected brake horsepower (B.H.P.) shall  
not exceed the motors nameplate horsepower rating, plus the  
service factor. Units shall be designed not to operate above  
service factor. Fan wheel shall be double-inlet type with for-  
ward-curved blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant air volume. Bearings shall be sealed  
and permanently lubricated for longer life and no maintenance.  
All non-Scroll compressors include crankcase heaters and all  
compressors have internal pressure relief. Every refrigerant  
circuit includes a liquid line filter-drier, a discharge line high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch.The unit control circuit  
includes a 75 VA transformer, a 24-volt circuit breaker and a  
relay board with a compressor lockout circuit, a terminal strip  
for thermostat wiring, plus an additional set of pin connectors  
to simplify the interface of additional field controls. All units  
have long lasting powder paint cabinets with 1000 hour salt  
spray test approval under ASTMB117 procedures. All models  
are CSA listed. All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater ele-  
ments carry a 5-year warranty. Aluminized steel tubular heat  
exchangers carry a 10-year warranty.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to a  
corrosion resistant steel spider bracket and shall be dynami-  
cally balanced for smooth operation. The outdoor fan motor  
shall be totally enclosed with permanently lubricated bear-  
ings, internally protected against overload conditions and  
staged independently.  
DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat  
and designed for outdoor mounted installation.  
REFRIGERANT COMPONENTS  
Compressor:  
The 3 thru 5 ton units shall have SEER ratings of 10.0 and  
the 6 ton unit shall have minimum EER ratings of 9.0. They  
shall have built-in field convertible duct connections for down  
discharge supply/return or horizontal discharge supply/return,  
and be available with factory installed options or field installed  
accessories. The units shall be factory wired, piped, charged  
with R-22 refrigerant and factory tested prior to shipment. All  
unit wiring shall be both numbered and color coded. All units  
the cooling performance shall be rated in accordance with  
DOE and ARI test procedures. Units shall be CSA listed,  
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.  
a. Shall be internally protected with internal high-pres-  
sure relief and over temperature protection.  
b. Shall have internal spring isolation and sound muf-  
fling to minimize vibration and noise, and be exter-  
nally isolated on a dedicated, independent  
mounting.  
Coils:  
a. Evaporator and condenser coils shall have alumi-  
num plate fins mechanically bonded to seamless  
Unitary Products Group  
39  
 
255040-YTG-A-0506  
internally enhanced copper tubes with all joints  
brazed. Special Phenolic coating shall be available  
as a factory option.  
GAS HEATING SECTION  
Shall be designed with induced draft combustion with post  
purge logic, energy saving direct spark ignition, and redun-  
dant main gas valve. Venter wheel shall be constructed of  
stainless steel for corrosion resistance. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 25°F. Burners shall be of the  
inshot type, constructed of aluminum coated steel and con-  
tain air mixture adjustments. All gas piping shall enter the unit  
cabinet at a single location through either the side or curb,  
without any field modifications. Integrated control boards  
shall provide timed control of evaporator fan functioning and  
burner ignition. Heating section shall be provided with the fol-  
lowing minimum protection:  
b. Evaporator and Condenser coils shall be of the  
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
a. Independent fixed-orifice expansion devices.  
b. Filter drier/strainer to eliminate any moisture or for-  
eign matter.  
c. Accessible service gage connections on both suc-  
tion and liquid lines to charge, evacuate, and mea-  
sure refrigerant pressure during any necessary  
servicing or troubleshooting without losing charge.  
a. Primary and auxiliary high-temperature limit  
switches.  
d. The refrigeration system shall provide at least 15°F  
of sub-cooling at design conditions.  
b. Induced draft motor speed sensor.  
c. Flame roll out switch (manual reset).  
d. Flame proving controls.  
UNIT CONTROLS  
a. Unit shall be complete with self-contained low-volt-  
age control circuit protected by a resetable circuit  
breaker on the 24-volt transformer side.  
e. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
b. Unit shall incorporate a lockout circuit which pro-  
vides reset capability at the space thermostat or  
base unit, should any of the following standard  
safety devices trip and shut off compressor.  
ELECTRIC HEATING SECTION  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 5 thru 30 KW, offering two  
stages of capacity - 16 KW and above on 208/230 volt heat-  
ers and 20 KW and above on 460 and 575 volt heaters. The  
heating section shall have a primary limit control(s) and auto-  
matic reset to prevent the heating element system from oper-  
ating at an excessive temperature. The heating section  
assembly shall slide out of the unit for easy maintenance and  
service. Units with Electric Heating shall be wired for a single  
point power supply with branch circuit fusing (where  
required).  
c. Loss-of-charge/Low-pressure switch.  
d. High-pressure switch.  
e. Freeze-protection thermostat, evaporator coil.  
f. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
g. Unit shall incorporate “AUTO RESET” compressor  
over temperature, over current protection.  
h. Unit shall operate with conventional thermostat  
designs and have a low voltage terminal strip for  
easy hook-up.  
UNIT OPERATING CHARACTERISTICS  
a. Unit shall be capable of starting and running at  
125°F outdoor temperature, exceeding maximum  
load criteria of ARI Standard 210/240.  
i.  
Unit control board shall have on-board diagnostics  
and fault code display.  
b. The compressor, with standard controls, shall be  
capable of operation down to 0°F outdoor tempera-  
ture.  
j.  
Standard controls shall include anti-short cycle and  
low voltage protection, and permit cooling operation  
down to 0°F.  
c. Unit shall be provided with fan time delay to prevent  
cold air delivery before heat exchanger warms up  
(Gas heat only).  
k. Control board shall monitor each refrigerant safety  
switch independently.  
l.  
Control board shall retain last 5 fault codes in non  
volatile memory, which will not be lost in the event of  
a power loss.  
ELECTRICAL REQUIREMENTS  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
40  
Unitary Products Group  
255040-YTG-A-0506  
STANDARD LIMITED WARRANTIES  
BAROMETRIC RELIEF DAMPER - Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit.  
Compressor 5 Years  
Heat Exchanger 10 Years  
Electric Heat Element 5 Years  
Other Parts 1 Year  
PROPANE CONVERSION KIT - Contains new orifices  
and gas valve parts to convert from natural to L.P. gas.  
One per unit required.  
HIGH ALTITUDE - NATURAL GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude.  
OPTIONAL OUTDOOR AIR (Shall be made available by  
either/or):  
ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER- Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in CFM of outdoor air to  
meet the minimum ventilation requirement of the condi-  
tioned space during normal operation. During econo-  
mizer operation, a mixed-air temperature control shall  
modulate the outdoor and return air damper assembly to  
prevent the supply air temperature from dropping below  
55°F. Changeover from compressor to economizer oper-  
ation shall be provided by an integral electronic enthalpy  
control that feeds input into the basic module. The out-  
door intake opening shall be covered with a rain hood  
that matches the exterior of the unit. Water eliminator/fil-  
ters shall be provided. Simultaneous economizer/com-  
pressor operation is also possible. Dampers shall fully  
close on power loss.  
HIGH ALTITUDE - PROPANE GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude. Must be used with propane conversion kit.  
LOW NOX - Required to reduce the emission of nitrogen  
oxides below 40 nanograms per joule.  
GAS PIPING - Contains 1/2” pipe nipples, fittings and  
gas cock (including panel assess gaskets) required for  
bottom gas supply connection with external shut off.  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
ELECTRIC HEATERS  
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -  
Contains all hood panels and the hardware for assem-  
bling.  
MANUAL OUTDOOR AIR DAMPER  
COIL GUARD KIT - Guard for condenser coil.  
HAIL GUARD  
FLUE EXHAUST EXTENSION  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
TECHNICOAT PHENOLIC COATED CONDENSER  
COIL  
ROOF CURB - 14"and 8” high, full perimeter curb with  
wood nailer (shipped knocked-down).  
ELECTRONIC SINGLE ENTHALPY ECONOMIZER  
Unitary Products Group  
41  
255040-YTG-A-0506  
42  
Unitary Products Group  
255040-YTG-A-0506  
Unitary Products Group  
43  
Subject to change without notice. Printed in U.S.A.  
255040-YTG-A-0506  
Copyright © 2006 by Unitary Products. All rights reserved.  
Supersedes: 530.18-TG1Y (500)  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Lexmark X364dw User Manual
Lexmark X 748de User Manual
Panasonic Cu E18jkk User Manual
Ricoh Aficio Mp C2500 Series User Manual
Samsung Avmbh070ea B 0 User Manual
Samsung Avmkc035ea B 0 User Manual
Sanyo Seb 013seb 013 User Manual
Schumacher Se 1052 User Manual
Schumacher Xcs15 User Manual
York Ahp18 User Manual