Siemens Sqm5 User Manual

Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5…  
Reversing Actuators  
ISO 9000 and 14000  
REGISTERED FIRM  
¤
Description  
SQM5... reversing actuators are used for the positioning of flow control valves, butterfly  
valves, dampers, or any application requiring rotary motion. The SQM5… actuators  
accommodate control input signals of 4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA,  
position proportional and floating control. The available output signals include  
4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA, and 0 to 1000 Ω. SQM5… actuators  
are available with up to six internal, easily adjustable switches.  
A selection of exchangeable circuit boards provide a variety of functions including  
auto/manual selector switch, manual forward/reverse toggle switch, zero and span  
adjustment, parallel or master/slave operation, split range control, input signal override,  
and selectable electronic linearization.  
The SQM5… is engineered for precision. It is particularly well suited for applications  
requiring a high degree of modulating accuracy and repeatability. Drive shaft play is  
limited to 0.3° with a modulating accuracy of 250 repositions through 90° of travel.  
The SQM5… actuator may be mounted in any position. A selection of mounting  
brackets and shafts provides installation flexibility and allows for the simple  
replacement of most competitive actuators.  
Modulating accuracy of 250 repositions through 90°  
Two limit switches, plus up to four internal auxiliary switches  
Fully closed “economy position” switch  
Features  
Drive shaft and cam drum disengagement clutches  
Auto/manual switch, manual control forward/reverse toggle switch  
UL, CSA approved 24 and 110 Vac versions  
CE approved 220 Vac versions  
Field reversible clockwise (cw) or counterclockwise (ccw) operation  
Various torque ratings and running times available  
Selection of field exchangeable single-ended and dual-ended shafts  
Mounting brackets to replace competitive actuators  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Table Of Contents  
Application  
Page 2  
Product Numbers  
Product numbers for pre-assembled UL/CSA/CE-approved  
actuators, Table 1  
Product numbers for accessories, Table 2  
SQM5… Product Number Identification Legend  
Installation and Operating Instructions  
Shaft Installation  
Page 4  
Page 5  
Page 6  
Page 7  
Page 8  
Page 8  
Page 8  
Page 9  
Page 9  
Rotational Direction Verification  
Actuator Mounting  
Switch Adjustment  
Shaft Adjustment  
Cam Drum Adjustment  
Wiring  
Electrical Connection  
Grounding  
Page 9  
Page 9  
Wiring Connections  
AGA56.1… circuit boards  
AGA56.41/42/43… circuit boards  
AGA56.9… circuit boards  
Commissioning  
Page 10  
Page 11  
Page 13  
Modulation Adjustment  
Zero Adjustment  
Span Adjustment  
Page 15  
Page 15  
Page 15  
Page 16  
Cover Installation  
Features  
SQM5x.xxxxxZx actuators  
SQM5x.xxxxxGx actuators  
SQM5x.xxxxxHx actuators  
SQM5x.xxxxxKx actuators  
SQM5x.xxxxxAx actuators  
Service Guide  
Page 16  
Page 18  
Page 18  
Page 18  
Page 18  
Reversing Rotational Direction  
Shaft Installation  
Circuit Board Installation  
AGA56.41/42/43…  
Page 18  
Page 20  
Page 20  
Page 20  
Page 22  
Page 24  
Page 25  
Page 26  
Page 29  
AGA56.9A  
AGA56.1A97  
Potentiometer Removal/Installation  
Specification Data  
Dimensions  
Siemens Building Technologies, Inc.  
Page 3  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Table 1. Product Numbers for Pre-assembled Actuators.  
Product Numbers  
Torque1  
Running  
Input Control Signals3  
Product Number  
220 V  
Time 2  
[lb-in]  
90°@ 60  
110 V  
24 V  
Hzsec  
90  
90  
90  
90  
90  
90  
90  
8
8
8
8
8
8
8
ccw  
cw  
ccw  
cw  
ccw  
cw  
ccw  
ccw  
cw  
ccw  
ccw  
cw  
ccw  
ccw  
ccw  
cw  
ccw  
ccw  
ccw  
ccw  
cw  
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
SQM50.261R1G3  
SQM50.261R1G3R  
SQM50.264R1A  
SQM50.264R2A  
SQM50.264R1A0R  
SQM50.264R1A3  
SQM50.264R1G3R  
SQM50.264R1G4  
SQM50.361R1G3  
SQM50.361R1G3R  
SQM50.361R1G7  
SQM50.364R1G3  
SQM50.364R1G3R  
SQM50.461R1A  
SQM50.461R1A3  
SQM50.461R1G3  
SQM50.461R1G3R  
SQM50.461R1H3  
SQM50.461R1Z3  
SQM50.461R1Z7  
SQM50.464R1A  
x
x
x
x
x
x
x
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
140  
200  
200  
200  
200  
200  
200  
200  
200  
200  
310  
310  
310  
310  
310  
400  
400  
400  
400  
400  
400  
12  
12  
12  
12  
12  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
37  
37  
37  
37  
37  
50  
50  
50  
50  
50  
50  
x
x
x
x
x
x
x
x
x
SQM50.464R8A  
SQM50.464R8G3  
SQM50.464R1A0R  
SQM50.464R1A3  
SQM50.464R1A3R  
SQM50.464R1G3  
SQM50.464R1G3R SQM50.464R2G3R  
SQM50.464R1G7  
ccw  
cw  
ccw  
cw  
ccw  
cw  
x
x
x
x
SQM50.464R1G7R  
SQM50.464R1H3  
ccw  
ccw  
ccw  
ccw  
ccw  
ccw  
cw  
ccw  
ccw  
cw  
ccw  
ccw  
ccw  
ccw  
ccw  
ccw  
ccw  
ccw  
cw  
x
x
SQM50.464R8H3  
SQM50.464R8Z3  
x
x
SQM50.464R1Z3  
SQM53.464R1A  
SQM53.464R1A3  
SQM53.464R1G3  
SQM53.464R1G7  
SQM53.464R1G7R  
SQM53.464R1Z3  
SQM53.467R1Z3  
SQM53.467R1Z3R  
SQM50.464R2Z3  
x
x
x
x
x
x
x
x
x
x
x
x
SQM53.464R2Z3  
SQM53.467R2A3  
SQM56.564R1A  
SQM56.564R1G4  
SQM56.564R1G7  
SQM56.564R1H4  
SQM56.564R1Z3  
SQM56.664R1G3  
SQM56.664R1Z3  
SQM56.667R1A3R  
SQM56.667R1G3  
SQM56.667R1G7R  
SQM56.667R1Z3  
x
x
x
x
x
x
x
x
x
x
ccw  
cw  
ccw  
x
x
x
x
x
1. Torque will vary with the selection of the shaft. See Specifications.  
2. Running time for 135° Æ multiply by 1.5. For 50 Hz Æ multiply by 1.2  
3. SQM5x.xxxxxZx models also accept a 0 to 20 mA input signal.  
Page 4  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Table 2. Product Numbers for Accessories.  
Shafts  
Electronic Circuit Boards  
AGA58.1 10 mm round with key. Gear end only.  
AGA58.2 12 mm round with key. Gear end only.  
AGA58.3 9 mm square. Dual-ended.  
AGA58.4 3/8 inch square. Dual-ended.  
AGA58.7 14 mm round with key. Gear end only.  
For exact shaft sizes, see Dimensions.  
AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxxAx  
AGA56.9A87 24 Vac  
AGA56.9A17 110 Vac  
AGA56.9A27 220 Vac  
AGA56.41A87 24 Vac  
AGA56.41A17 110 Vac  
AGA56.41A27 220 Vac  
AGA56.42A87 24 Vac  
AGA56.42A17 110 Vac  
AGA56.42A27 220 Vac  
AGA56.43A87 24 Vac  
AGA56.43A17 110 Vac  
AGA56.43A27 220 Vac  
(Z) board for SQM5x.xxxxxZx  
(Z) board for SQM5x.xxxxxZx  
(Z) board for SQM5x.xxxxxZx  
(G) board for SQM5x.xxxxxGx  
(G) board for SQM5x.xxxxxGx  
(G) board for SQM5x.xxxxxGx  
(H) board for SQM5x.xxxxxHx  
(H) board for SQM5x.xxxxxHx  
(H) board for SQM5x.xxxxxHx  
(K) board for SQM5x.xxxxxKx  
(K) board for SQM5x.xxxxxKx  
(K) board for SQM5x.xxxxxKx  
Crank Arm, Push Rods  
338 031 Crank arm kit. Includes two crank arms for  
connecting the AGA58.4 shaft to a 1/2-inch  
damper shaft with two ball joints. (Does not include  
push rod.)  
338 041 5/16" damper push rod, 12 inches long.  
338 042 5/16" damper push rod, 15 inches long.  
338 043 5/16" damper push rod, 18 inches long.  
338 044 5/16" damper push rod, 24 inches long.  
338 045 5/16" damper push rod, 36 inches long.  
338 046 5/16" damper push rod, 48 inches long.  
See Product Number Identification Legend, Figure 1.  
Mounting Brackets & Adapters  
AGA57.3 for replacement of Honeywell MOD III, IV  
actuators  
AGA57.4 for replacement of Honeywell M640/740/940 and  
Barber Colman EA20/40/50/60 actuators. Directly  
adaptable to Eclipse butterfly valves.  
ASK33.9 mounting kit for direct attachment to Siemens  
VKF41... butterfly valve. (Shaft AGA58.1  
required)  
Potentiometers  
ASZ12.803 and ASZ12.30 1000Ω, 90°  
ASZ12.833 and ASZ12.33 1000Ω, 135°  
ASZ22.803 and ASZ22.30 1000/1000Ω double  
potentiometer, 90°  
ASZ22.833 and ASZ22.33 1000/1000Ω double  
potentiometer, 135°  
ASZ16.703 135Ω, 90° (wire wound)  
ASZ16.733 135Ω, 135° (wire wound)  
ASZ66.733 135Ω/135Ω, double potentiometer 135°  
(wire wound)  
Additional potentiometer models available. See  
Siemens technical data sheet 7921.  
Siemens Building Technologies, Inc.  
Page 5  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Product Number Identification Legend  
For actuator identification only. To select product numbers for ordering, see Table 1.  
Figure 1. SQM5… Product Number Identification Legend.  
SQM5  
0
.
4
8
0
R
1
Z
3
R
Actuator family  
Torque in-lb @ 60 (50) Hz.  
0
0
3
6
6
90 for 8 (10) sec. running time  
140 for 12 (15), 25 (30), 37 (45) sec.  
200 for 25 (30) sec.  
310 for 37 (45) sec.  
400 for 50 (60), 75 (90)sec.  
Running time for 90°  
Not all actuator running times are  
available in each torque.  
Refer to table 1  
60 Hz.  
50 Hz.  
2
10 sec.  
2
3
4
5
6
8 sec.  
12 sec.  
25 sec.  
37 sec.  
50 sec.  
3
4
5
6
15 sec.  
30 sec.  
45 sec.  
60 sec.  
Number of SPDT switches  
2 limit and 4 auxiliary switches  
6
Shaft selection  
no shaft (shaft must be ordered separately)  
round 10 mm, single ended (for use with VKF41... butterfly valves)  
square 3/8 inch, dual ended  
0
1
4
7
round 14 mm, single ended  
Approvals  
R
UL recognized, CSA certified  
Operating voltage (Vac @50-60 Hz)  
1
2
8
110-120 Vac  
220-240 Vac  
24 Vac  
Internal circuit board (SQM5x.xxxxx G, H, K , Zx actuators require potentiometer ASZ…)  
A
G
H
K
Z
AGA56.1A97 (position proportional control)  
AGA56.41A... (4 to 20 mA input)  
AGA56.42A... (0 to 135 Ohm input)  
AGA56.43A... (0 to 10 Vdc input)  
AGA56.9... (all inputs/outputs, linearization, split ranging, override and pre-set positioning)  
(1000 Ohm required when using SQM5x.xxxxx G, H, K, Zx actuators)  
Potentiometer  
3
4
ASZ12.30 (1000 ohm, 90°)  
ASZ12.33 (1000 Ohm, 135°)  
7
8
B
C
L
ASZ22.30 (1000/1000 Ohm, 90°)  
ASZ22.33 (1000/1000 Ohm, 135°)  
ASZ16.703 (135 Ohm, 90°)  
ASZ16.733 (135 Ohm, 135°)  
ASZ66.733 (135/135 Ohm, 135°)  
Rotational Direction  
Clockwise (when facing gear end. See Figure 6 .)  
(Product numbers ending without R are ccw)  
R
Page 6  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Installation and  
Operation  
SQM5… actuators are sometimes shipped without the shaft installed. To install the  
selected shaft:  
Instructions  
1. Loosen the two screws on the actuator cover corners. See Figure 2.  
2. Lift the screws and raise the cover. See Figure 3.  
Shaft Installation  
Figure 3.  
Figure 2.  
3. Each shaft is supplied with two washers and a “C” clip. See Figure 4. Using  
spreading pliers, remove the “C” clip and the washers from the shaft.  
KEY END  
INSERT END  
SHAFT KEY  
WASHERS ON  
BOTH SIDES  
OF THE BEARING  
C-CLIP  
Figure 4.  
4. Insert the “insert end” of the shaft into the “gear end” of the actuator.  
5. Push the shaft until the “insert end” reaches just short of the brass bushing at the  
other end of the actuator.  
6. Put one of the washers on the insert end of the shaft. See Figure 5.  
WASHERS  
Figure 5.  
7. Line up the “shaft key” with the key slot on the “gear end” of the actuator and slide  
the shaft until the “insert end” is completely through the brass bushing.  
8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers,  
install the “C” clip.  
Siemens Building Technologies, Inc.  
Page 7  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Actuator model numbers that end with “R” are factory configured for clockwise (cw),  
minimum to maximum rotation when facing the gear end of the actuator, or  
counterclockwise (ccw) rotation when facing the other end of the actuator. The gear end  
of the actuator is the side opposite of the visual position indicator.  
Rotational Direction  
Verification  
To field reverse the direction of rotation, see Service Guide, “Reversing Rotational  
Direction”.  
Actuator Mounting  
SQM5… actuators can be mounted in any orientation using the four 1/4"-20 UNC  
tapped holes located on the bottom corners of the actuator base. Optional base  
mounting brackets are available. See Table 2.  
SQM5… actuators can also be face mounted using self tapping screws in combination  
with the various holes on the face of the actuator gear end.  
ACTUATOR  
POSITION SCALE  
SWITCH CAM I  
SET AT MAXIMUM  
ACTUATOR POSITION  
INDICATING DIAL  
DIAL POINTER  
SWITCH CAM II  
SET AT ZERO ("ECONOMY")  
ACTUATOR POSITION  
INDICATING POINTER  
CAM DRUM  
ASZ... (1000 Ohm)  
FEEDBACK POTENTIOMETER  
SWITCH CAM III  
SET AT MINIMUM  
50  
30  
50  
30  
50  
30  
10  
0
10  
CAM DRUM  
RELEASE BUTTON  
30  
50  
10  
0
10  
0
10  
0
0
0
0
70  
SINGLE SWITCH  
CAM POINTER  
GEAR END  
DOUBLE SWITCH CAM POINTER  
Figure 6. Component Identification on the Cam Drum Side of the SQM5… Actuator.  
Switch Adjustment  
All SQM5…actuators are factory wired with Switch I (maximum), Switch II (fully closed  
“economy position”) and Switch III (minimum). The individual switch cams I, II, and III  
are factory set to 90°, 0° and 10° respectively.  
See Figure 6.  
NOTE: The single switch cam pointers are used together with the black scales when  
configured for counterclockwise (ccw) operation.  
The double switch cam pointers are used together with the red scales when  
configured for clockwise (cw) operation.  
The individual switch cams can be adjusted by hand or with the use of the tool  
attached to the outside of the hinged switch terminal protection lid.  
Page 8  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Switch Adjustment,  
Continued  
NOTE: If a potentiometer is installed, the adjustable range of the switches depends  
on the range of the potentiometer.  
SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°.  
SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be  
adjusted only between 0 and 90°.  
SQM5x.xxxxxx4 actuators have a 135° potentiometer and the switches must  
be adjusted only between 0 and 135°.  
Shaft Adjustment  
The actuator shaft can be disengaged by pressing the silver shaft release button. The  
button is located above the grounding screw, under the hinged terminal protection  
cover, and to the right of the auto/manual switch. After pressing the shaft release button  
in and slightly upward, the shaft can be manually rotated. After the shaft has been  
manually aligned to the closed position, re-engage the shaft by pushing the shaft  
release button downwards.  
See Figure 6.  
Once the shaft has been set, the cam drum must be manually aligned by pressing and  
holding the black cam drum release button (see Figure 6). Rotate the cam drum until  
the “0” mark on the actuator position scale (left scale on the cam drum) is aligned with  
the gray actuator position indicating pointer.  
Cam Drum Adjustment  
See Figure 6.  
Position Indicating Dial  
Adjustment  
The actual position of the SQM5… actuator is indicated by the gray actuator position  
indicating pointer (see Figure 6). The position is also displayed by the indicating dial  
through the housing’s window. Ensure that the actuator position indicating dial is  
aligned with the actuator position scale. If necessary, rotate the dial in the clockwise  
direction.  
CAUTION:  
Turning the dial in the counterclockwise direction may loosen the  
potentiometer locking screw.  
Wiring  
SQM5… actuators are equipped with two removable conduit connection plates located  
on the upper corner of the gear housing. Each plate is provided with two threaded  
connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is  
recommended.  
Electrical Connection  
Grounding  
CAUTION:  
To avoid electro-magnetic interference, the SQM5… actuators must be  
grounded.  
The ground terminal is located to the right of the auto/manual switch.  
Disconnect the circuit board wire marked 51 during high voltage testing.  
Reconnect it to the grounding terminal after the test.  
Siemens Building Technologies, Inc.  
Page 9  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Wiring Connections  
NOTE: SQM5… actuators require a single source, single phase power supply.  
Wiring connections vary depending on which AGA56…. circuit board is installed.  
AGA56.1… circuit boards.  
Manual Operation  
See Figures 7 and 8.  
1. Set the AUTO/MAN switch in the MAN position.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to the double terminal block, located on the left side of the gray  
switch housing.  
4. Only terminal "L" must be to enable manual operation. The actuator can now be  
driven to the maximum position (switch cam I) or the fully closed "economy  
position" (switch cam II) by using the toggle switch located to the left of the  
AUTO/MAN switch.  
Automatic Operation  
1. Set the AUTO/MAN switch in the AUTO position.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to the double terminal block located on the left side of the gray  
switch housing.  
4. Connect line voltage to terminal A to drive the actuator in the opening direction.  
5. Connect line voltage to terminal Z to drive the actuator in the closing direction.  
CAUTION:  
Do not power terminals A and Z simultaneously. Actuator damage will occur.  
A
L
Z
AGA56.1A97  
51  
actuator switch  
I Maximum/High fire  
MAN  
AUTO  
shown in  
auto position  
II  
III  
IV...VI  
"Economy"/Fully closed  
Minimum/Low fire  
Auxilliary  
1
1
2
13  
N
c
b
4
3
5
6
2
V
VI  
I
II  
IV  
III  
13 23  
wire leads  
ASZ...  
(1000 Ohm)  
M
11 21  
12 22  
14 24  
15 25  
16 26  
21 12  
a
Figure 7. Basic Functional Diagram of AGA56.1…  
Page 10  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Wiring, Continued  
A
A
Z
Z
L
L
MAN.  
0
AUTO.  
AGA56.1A97  
Figure 8. AGA56.1A97 Terminal/Auto-Manual Board.  
Manual Operation  
AGA56.41/42/43…  
Circuit Boards.  
1. Set the AUTO/MAN switch in the MAN position.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to terminal N.  
See Figures 9 and 10.  
4. Only terminal "L" must be powered to enable manual operation. The actuator can  
now be driven to the maximum (high fire) position (switch cam I) or the fully closed  
"economy position" (switch cam II) by using the toggle switch located to the left of  
the AUTO/MAN switch.  
Automatic Operation  
1. Set the AUTO/MAN switch in the AUTO position.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to terminal N.  
4. Connect line voltage at all times to terminal L to provide power to the electronic  
circuit board.  
5. Connect line voltage to terminal LR to provide power when modulating. Connect  
line voltage to Terminal LR only after removing power on terminals A and Z  
(otherwise actuator damage may result).  
6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire  
purge) position.  
Once the maximum position is reached, terminal 11 (on switch I) will be energized  
to provide position feedback.  
7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)  
position. Once the minimum position is reached, terminal 23 (on switch III) will be  
energized to provide position feedback. Adjustment of switch III will determine the  
low-fire stop position. Switch III (low fire) must be set at a higher position than  
switch II (fully closed). Terminal ZL may be energized only after removing power  
from terminals A, Z, 13, and LR.  
8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy  
position (switch II).  
9. Connect the input control signal wires to the appropriate terminals. See Figure 9.  
CAUTION:  
Do not power terminals A and Z simultaneously. Actuator damage will  
occur.  
Siemens Building Technologies, Inc.  
Page 11  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Wiring, Continued  
A
13 ZL  
LR  
N
Z
L
AGA56.4...  
Y+  
AGA56.41...  
("G" board 4...20 mA)  
Y-  
(+2 V)  
B
U
M
Y
AGA56.42...  
("H" board  
0-135 Ohm)  
135 Ohm  
REG  
OPE  
MAX  
MIN  
W
R
MAX  
MIN  
0...2 V  
MIN  
MAX  
Y
M
Y
AGA56.43...  
("K" board 0...10 V)  
51  
MIN MAX  
MAN  
AUTO  
shown in  
actuator switch  
auto position  
I Maximum/High fire  
II  
III  
IV...VI  
"Economy"/Fully closed  
Minimum/Low fire  
Auxilliary  
N
1
2
13  
3
c
b
1
2
3
4
5
6
I
II  
III  
13 23  
wire leads  
IV  
V
VI  
ASZ...  
(1000 Ohm)  
M
11 21  
12 22  
14 24  
15  
25  
16  
26  
21 12  
a
Figure 9. Basic Functional Diagram of AGA56.4…  
OPE MAX MIN  
Y-  
Y+  
ZL  
N
13  
LR  
A
Z
L
OPE MAX MIN  
Y
M
U
ZL  
N
13  
LR  
A
Z
L
MAX  
MAX  
MIN  
MIN  
MAN.  
AUTO.  
MAN.  
0
0
AUTO.  
AGA56.42A...  
AGA56.41A...  
"H" Board  
0 to 135 ohm  
"G" Board  
4 to 20mA  
ZL  
13  
LR  
A
Z
L
N
OPE MAX MIN  
Y
M
MAX  
MIN  
MAN.  
AUTO.  
0
AGA56.43A...  
"K" Board  
0 to 10V  
Figure 10. AGA56.41/42/43… Terminal and Trim Potentiometer Boards.  
Page 12  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
AGA56.9… Circuit  
Boards  
Manual Operation  
1. Set the AUTO/MAN switch in the MAN position.  
See Figures 11 and 12.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to terminal N.  
4.  
Only terminal "L" must be powered to enable manual operation. The actuator can  
now be driven to the maximum (high fire) position (switch cam I) or the fully closed  
"economy position" (switch cam II) by using the toggle switch located to the left of  
the AUTO/MAN switch.  
Automatic Operation  
1. Set the AUTO/MAN switch in the AUTO position.  
2. Connect ground to the screw located below the shaft release button.  
3. Connect neutral to terminal N.  
4. Connect line voltage at all times to terminal L to provide power to the electronic  
circuit board.  
5. Connect line voltage to terminal L1 to provide power when modulating. Connect line  
voltage to terminal L1 only after removing power on terminals A and Z (otherwise  
actuator damage may result).  
6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire  
purge) position. Once the maximum position is reached, terminal 11 (on switch I)  
will be energized to provide position feedback.  
7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)  
position. Once the minimum position is reached, terminal 23 (on switch III) will be  
energized to provide position feedback. Adjustment of switch III will determine the  
low-fire stop position. Switch III (low fire) must be set at a higher position than  
switch II (fully closed). Terminal ZL may be energized only after removing power  
from terminals A, Z, 13, and LR.  
8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy  
position (switch II).  
9. Connect the input control signal wires to the appropriate terminals. See Figure 11.  
CAUTION:  
Do not power terminals A and Z simultaneously. Actuator damage will  
occur.  
Siemens Building Technologies, Inc.  
Page 13  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Wiring, Continued  
N
A
L
Z
ZL  
L
1
P
AGA56.9...  
SHIFT  
ZF  
POS  
LIN  
20 mA  
18 mA 16 mA  
4...20 mA  
14 mA  
MAX  
75%  
M
0
or 12 mA  
10 mA  
8
6
mA  
mA  
ZF  
=
50%  
25%  
MIN  
POS  
4
mA  
(+2 V)  
B
U
4
MIN25% 50%75% MAX  
Y0...3  
Y0...3  
Y0...3  
135 Ohm  
W
R
M
0...2 V  
Y
0
POS  
M
1
2
REG  
4...20 mA  
0...10 V  
Y
3
OPE  
MAX  
MIN  
MAX  
MIN  
J1  
M
LIN  
Y
1
MIN  
MAX  
Y0...3  
M
0...20 mA  
MAX  
MIN  
Y2  
51  
U
3
4...20 mA  
0...20 mA  
1
2
U2  
0...10 V  
U
1
MAN  
AUTO  
shown in  
auto position  
J2  
actuator switch  
I Maximum/High fire  
common  
M
II  
III  
IV...VI  
"Economy"/Fully closed  
Minimum/Low fire  
Auxilliary  
N
1
2
13  
3
c
b
1
2
3
4
5
6
II  
IV  
V
VI  
I
III  
13 23  
wire leads  
ASZ...  
(1000 Ohm)  
M
11 21  
12 22  
14 24  
15  
25  
16  
26  
21 12  
a
Figure 11. Basic Functional Diagram of AGA56.9…  
U
M
Y
0
Y
1
Y
2
Y
3
L
P
L
N
A
Z
ZL  
4
1
1
2
1
2
OPE  
MAX  
MIN  
J1  
J2  
LIN  
MAX POS MIN  
U1...U3  
JUMPERS  
3-POSITION  
SWITCH  
POT. METERS  
ZF  
M
M
U
U
U
3
1
2
MAN.  
0
AUTO.  
AGA56.9A...  
Figure 12. AGA56.9… Terminal and Trim Potentiometer/Jumper Board.  
Page 14  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Modulation Adjustment  
The blue trim potentiometers allow the adjustment of the minimum (zero) and  
maximum (span) positions.  
See Figures 10 and 12.  
The factory setting of the MIN trim potentiometer is rotated fully counter clockwise.  
The factory setting of the MAX trim potentiometer is rotated fully clockwise.  
Zero Adjustment  
Set the OPE/MAX/MIN slide switch to MIN. The blue MIN trim potentiometer can now  
be gently adjusted to the required minimum position. Return the OPE/MAX/MIN slide  
switch to OPE for operation.  
NOTE: Do not set switch cam I higher than:  
90° when using feedback potentiometers ASZxx.30  
135° when using feedback potentiometers ASZxx.33  
Span Adjustment  
Set the OPE/MAX/MIN slide switch to MAX. The blue MAX trim potentiometer can now  
be gently adjusted to the required maximum position. Return the OPE/MAX/MIN slide  
switch to OPE for operation.  
NOTE: The actual minimum and maximum  
modulating range is determined either  
by the setting of the MIN and MAX trim  
potentiometers or the setting of switch  
Example of limit switch I and III  
and trim potentiometer settings  
cam III (Minimum) and switch cam I  
(Maximum). The actuator can never  
modulate outside of the range set by  
switch cam I and III. If the MIN and MAX  
trim potentiometers are set outside the  
setting range of switch cams I and III,  
then the switch cam settings determine  
the modulating range. If a soft stop is  
desired, the modulating range can be  
defined by the trim potentiometers if the  
MIN and MAX trim potentiometers are  
set inside the setting range of switch  
cams I and III. See the example in  
Figure 13.  
0 deg.  
Figure 13. Switch cam and Trim  
Potentiometer Setting.  
Siemens Building Technologies, Inc.  
Page 15  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
1. Lift the two screws on the cover corners and slide the cover end into the grooves  
at the gear end of the actuator. See Figure 14.  
Cover Installation  
2. Press the cover into place and then press the screws inward and tighten. See  
Figure 15.  
Figure 14.  
Figure 15.  
Features of  
SQM5x.xxxxxZx  
Actuators  
SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This  
circuit board provides the following features:  
Multiple Input Signals  
The AGA56.9A… circuit board accepts the following input signals:  
Line voltage  
Power to A drives the actuator open to the setting of switch cam I (Maximum).  
Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).  
Power to Z drives the actuator closed to the setting of switch cam II (Economy).  
4 to 20 mA (Signal to Y3, common to M)  
0 to 135 Ω (Slide wire signal to Y0, potentiometer connected to M and U4)  
0 to 10 Vdc (Signal to Y1, common to M)  
0 to 20 mA (Signal to Y2, common to M)  
Multiple Output Signals  
The AGA56.9A… circuit board provides the following output signals:  
4 to 20 mA (Signal from U3, common to M)  
0 to 10Vdc (Signal from U1, common to M)  
0 to 20mA (Signal from U2, common to M)  
Double potentiometers ASZ22… provide additional output signals.  
Page 16  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Electronic Linearization  
Function  
Butterfly valves have non-linear flow characteristics. Near the fully closed position, a  
small change in the valve’s position will produce a very large change in flow. Near the  
fully open position, a large position change will produce a relatively small change in flow.  
The linearization function is intended to minimize the initial steep flow curve  
characteristics of a typical butterfly valve. The linearization function is enabled when  
Jumper J1 is in position 1 (upper position). Consequently, the actuator will make smaller  
rotational movements when subjected to lower input signals and larger rotational  
movements when subjected to higher input signals.  
For example (based on a 90° modulating range), a change in input signal from 4 to 8 mA  
will cause a rotational movement of 11.25°. An equal change from 16 to 20 mA will cause  
a rotational movement of 45°. Thus, with the linearization function enabled, the change in  
flow is closely proportional to the change in input signal.  
The linearization function is disabled when Jumper J1 is in position 2 (lower position).  
When disabled, the rotational movement of the shaft is proportional to the input signal.  
Input Signal Override  
Parallel Operation  
Line voltage to terminal P will drive the actuator to a pre-set adjustable position,  
overriding all modulating input signals. Use the potentiometer marked POS to adjust the  
override position to any setting within the setting range of switch cams I and III.  
NOTE: The input signal override can also be used for the ignition position of burners if  
different from the low fire position.  
Set Jumper J2 in position 1 (upper position) to configure the actuator for parallel  
operation. Input signals Y0, Y1, Y2 or Y3 are directly shunted to output signals U1, U2  
and U3. All output signals are available regardless of which input signal is applied.  
Master/Slave Operation  
Split Ranging  
Set J2 in position 2 (lower position) to configure the actuator for master/slave operation.  
The output signals U1, U2 and U3 reflect actual shaft position.  
AGA56.9… circuit boards have a modulating signal shift feature which can be used for  
split ranging. If no signal is present on Y0, Y1, Y2 or Y3, the actuator will modulate  
through the full rotational range in response to a 12 to 20 mA signal applied at ZF. If a  
maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through  
the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum  
signal can be easily achieved by bridging terminals U4 and Y0.) See Figure 16.  
NOTE: It is possible to configure the actuator for split range operation 12 to 4 mA and  
20 to 12 mA. Consult your authorized Siemens Building Technologies  
combustion products sales representative for details.  
20 mA18 mA16 mA14 mA12 mA  
MAX  
10 mA  
8 mA  
6 mA  
4 mA  
75%  
50%  
25%  
MIN  
MIN 25% 50% 75% MAX  
Y0...3  
Figure 16. Split Ranging.  
Siemens Building Technologies, Inc.  
Page 17  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Features of  
SQM5x.xxxxxGx actuators contain the AGA56.41A… circuit board with terminals Y- and  
Y+ for 4 to 20 mA modulating input.  
SQM5x.xxxxxGx,  
SQM5x.xxxxxHx,  
SQM5x.xxxxxKx  
Actuators  
SQM5x.xxxxxHx actuators contain the AGA56.42A… circuit board with terminals Y, M  
and U for 0 to 135 Ω modulating input.  
SQM5x.xxxxxKx actuators contain the AGA56.43A… circuit board with terminals Y and M  
for 0 to 10 Vdc modulating input.  
Input Signals  
The AGA56.4xA… circuit boards accept the following additional input signal:  
Line voltage  
Power to A drives the actuator open to the setting of switch cam I (Maximum).  
Power to Z drives the actuator closed to the setting of switch cam II (Economy).  
Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).  
Output Signals  
The AGA56.4xA… circuit boards do not provide output signals. Install a double  
potentiometer ASZ22…to obtain a 0 to 1000 Ω actuator position output signal.  
Features of  
SQM5x.xxxxxAx  
Actuators  
The AGA56.1A97… circuit boards accept the following additional input signal:  
Line voltage  
Input Signals  
Power to A drives the actuator open to the setting of switch cam I (Maximum).  
Power to Z drives the actuator closed to the setting of switch cam II (Economy).  
Power to switch III, terminal 3 drives the actuator to the setting of switch cam III  
(Minimum).  
Output Signals  
The AGA56.1A97 circuit board provides no output signals. Install an ASZ… potentiometer  
to obtain an actuator position output signal.  
Service Guide  
WARNING:  
Disconnect the power supply to the actuator before performing any service  
functions.  
Reversing Rotational  
Direction  
1. Disconnect the wires marked 21 and 12, and reverse.  
2. Adjust all switch cams to the desired settings (see Figure 6):  
For CCW rotation use the black cam drum scales and the single switch cam  
pointers.  
For CW rotation, use the red cam drum scales and the double switch cam pointers.  
NOTE: Press and hold the black cam drum release button to rotate the cam drum.  
This will give easy access to the switch cams and a better view of the cam  
drum scales.  
If no potentiometer ASZ… is installed, the reversing procedure is complete. If a  
potentiometer ASZ… is installed, complete Steps 3 through 9.  
Page 18  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Reversing Rotational Direction,  
Continued  
POSITION  
INDICATION  
POINTER  
POSITION  
INDICATION  
POINTER  
POSITION  
m i n .  
m a x .  
INDICATION  
POINTER  
m i n .  
m a x .  
POSITION  
INDICATION  
POINTER  
m i n .  
m a x .  
m i n .  
m a x .  
Clockwise  
Counterclockwise  
Figure 17. Reversing Rotational Direction on the ASZ Potentiometer.  
GEAR WITH MARK "0"  
FOR CLOCKWISE  
ROTATION  
GEAR WITH MARK "1" FOR  
COUNTERCLOCKWISE ROTATION  
BOARD  
ALIGNMENT  
SCREW  
BOARD  
ALIGNMENT  
SCREW  
TERMINAL  
BLOCK  
TERMINAL  
BLOCK  
POTENTIOMETER GEAR  
ALIGNMENT POINTER  
POTENTIOMETER GEAR  
ALIGNMENT POINTER  
POTENTIOMETER  
POTENTIOMETER  
POTENTIOMETER GEAR  
ATTACHMENT SCREW  
POTENTIOMETER GEAR  
ATTACHMENT SCREW  
Figure 17a. Reversing Rotational Direction on the ASZ Potentiometer (Gear Models).  
3. Disconnect the blue and brown wires from the terminal block located on the ASZ…  
potentiometer circuit board and reverse. The black wire remains connected to the  
middle terminal. See Figures 17 and 17a.  
4. Remove the white plastic actuator position-indicating dial by gently pulling while rotating  
in the clockwise direction. See Figure 6.  
5. The actuator position indicating pointer, located near the actuator gear end of the cam  
drum, must point to the “0” mark on the actuator position scale (scale on the cam drum  
nearest to the actuator gear end). Press and hold the black cam drum release button  
while manually rotating the cam drum.  
6. Loosen the black potentiometer cam attachment screw approximately one turn. Gently  
wedge a small screwdriver between the potentiometer and the gray plastic housing.  
Gently twist the screwdriver until the potentiometer releases from the cam drum shaft.  
7. Change potentiometer end position:  
Manually rotate the potentiometer position indication pointer exactly to the other  
end mark (see Figure 17).  
Gear models (see Figure 17a):  
For clockwise rotation, manually rotate the potentiometer gear until the white line  
next to the “0” mark on the potentiometer gear face is exactly in alignment with the  
potentiometer gear alignment pointer.  
For counterclockwise rotation, manually rotate the potentiometer gear until the  
white line next to the “1” mark on the potentiometer gear face is exactly in  
alignment with the potentiometer gear alignment pointer  
Page 19  
Siemens Building Technologies, Inc.  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Reversing Rotational  
Direction, Continued  
8. Firmly tighten the black potentiometer cam attachment screw while manually  
holding the potentiometer position indication pointer in alignment. Check the  
alignment again.  
9. Re-install the white actuator-indicating dial by gently pressing it onto the  
potentiometer cam attachment screw. Align scale position “0” on the actuator  
position indicating dial with the dial pointer by rotating the dial in the clockwise  
direction to avoid loosening the potentiometer cam attachment screw.  
Shaft Installation  
See Installation and Operation Instructions.  
Preparation Before  
Circuit Board Installation  
WARNING:  
Disconnect the power supply to the actuator before replacing the circuit  
boards.  
The black circuit board mounting  
bracket, installed on the inside base of  
the SQM5… actuator has four vertical,  
slotted circuit board supports. Remove  
the terminal section and circuit board(s)  
from the mounting bracket.  
The actuator motor capacitor is  
attached to the lower section of the gray  
plastic switch housing using snap-on  
holding clips. Gently pull the capacitor  
forward until it unclips and temporarily  
place it on top of the gear housing. See  
CAPACITOR  
Figure 18.  
Figure 18.  
CAUTION:  
Do not disconnect any capacitor wiring.  
AGA56.41/42/43  
Circuit Board  
Installation  
1. Remove the AGA56.41/42/43…  
TERMINAL  
SECTION  
circuit board from the packaging. The  
circuit board is shipped as one board.  
2. Separate the board at the perforation  
by holding the circuit board at both  
ends and gently bending the board  
until it separates.  
3. Move the terminal section containing  
the auto/manual switch to the  
opposite end of the base circuit  
board.  
BASE  
CIRCUIT  
BOARD  
4. From the switch housing side of the  
actuator, guide the base circuit board  
into the bottom of the circuit board  
mounting bracket. See Figure 19.  
Figure 19.  
Page 20  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
AGA56.41/42/43  
Circuit Board  
Installation,  
Continued  
5. Re-install the actuator motor capacitor.  
See Figure 20.  
6. Gently guide the terminal section into  
the support slots and slide the terminal  
board downward until both supports  
snap into place. Ensure that the four  
brown wires and the flat white  
connector cable which connect the two  
circuit boards are positioned correctly  
in their respective corners allowing the  
board to freely slide into place without  
pinching either wire. See Figure 21.  
CAPACITOR  
Figure 20.  
7. Connect the bundled blue, black and  
brown potentiometer wires to the  
terminal block located on the ASZ…  
potentiometer circuit board. See  
Potentiometer Installation.  
TERMINAL  
SECTION  
Figure 21.  
Siemens Building Technologies, Inc.  
Page 21  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
AGA56.41/42/43  
Circuit Board  
Installation, Continued  
8. Make the following connections to the  
actuator: See Figure 22.  
18 17 16 15 14 13 12 11  
28 27 26 25 24 23 22 21  
a. Connect the wire, marked “1” from  
the circuit board to switch I,  
terminal 1.  
8
7
6
5
4
3
2
1
VIII VII VI  
V
IV  
III  
II  
I
b. Connect the wire, marked “2” from  
the circuit board to switch II,  
terminal 2.  
13  
c. Connect the wire, marked “3” from  
the circuit board to switch III,  
terminal 3.  
d. Connect the wire, marked “13”  
from the circuit board to switch III,  
terminal 13.  
3
2
N
1
TERMINAL  
BLOCK  
e. Connect the blue neutral wire  
marked “N” to the double terminal  
block located on the outer end of  
the switch housing  
MAN.  
0
AUTO  
f. Connect the grounding wire  
marked "51" to the ground terminal  
located to the right of the  
auto/manual switch.  
N
Figure 22.  
AGA56.9A…  
Circuit Board  
Installation  
1. Remove the ASZ... potentiometer if  
already installed on the SQM5...  
actuator. See Potentiometer  
Removal/Installation Instructions.  
2. Remove the AGA56.9A… circuit  
boards from the packaging. The three  
separate AGA56.9A circuit boards are  
shipped in a circuit board mounting  
bracket.  
3. Remove the two upright circuit boards  
from the mounting bracket by gently  
pulling aside the vertical supports and  
sliding the boards upward. Remove  
the base circuit board from the bottom  
of the mounting bracket. Discard the  
shipping mounting bracket.  
Page 22  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
AGA56.9A…  
Circuit Board  
Installation, Continued  
4. Guide the base circuit board from the  
switch housing side of the actuator into  
the bottom of the circuit board mounting  
bracket. See Figure 23.  
5. Re-install the actuator motor capacitor.  
See Figure 24.  
6. Gently guide the terminal board into the  
support slots and slide the terminal  
board downward until both supports  
snap into place. See Figure 25.  
BASE  
CIRCUIT  
BOARD  
7. See Figure 26 and make the following  
connections to the actuator:  
Figure 23.  
a. Connect the wire, marked “1” from  
the circuit board to switch I,  
terminal 1.  
b. Connect the wire, marked “2” from  
the circuit board to switch II,  
terminal 2. Connect the white wire,  
marked “3” from the circuit board to  
switch III, terminal 3.  
c. Connect the wire, marked “13” from  
the circuit board to switch III,  
terminal 13.  
CAPACITOR  
d. Connect the neutral wire, marked  
“N” to the double terminal block  
located on the outer end of the  
switch housing.  
Figure 24.  
TERMINAL  
SECTION  
e. Connect the grounding wire marked  
"51" to the ground terminal located  
to the right of the auto/manual  
switch.  
Figure 25.  
Siemens Building Technologies, Inc.  
Page 23  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
AGA56.9A…  
Circuit Board  
Installation, Continued  
8. Gently guide the L-shaped circuit  
board containing the three blue trim  
potentiometers into the vertical support  
slots located on the cam drum side of  
the actuator. See Figure 27.  
18 17 16 15 14 13 12 11  
28 27 26 25 24 23 22 21  
8
7
6
5
4
3
2
1
VIII VII VI  
V
IV  
III  
II  
I
13  
9. Slide the circuit board downward until  
both supports snap into place. Install  
the ASZ… potentiometer. (See  
Potentiometer Removal/Installation  
Instructions.)  
3
2
N
1
10. Connect the bundled blue, black and  
brown potentiometer wires to the  
terminal block located on the ASZ…  
potentiometer circuit board.  
MAN.  
0
AUTO  
N
Figure 26.  
-
L SHAPED  
CIRCUIT  
BOARD  
Figure 27.  
AGA56.1A97  
Circuit Board  
Installation  
1. Install the AGA56.1A97 circuit board into the two slotted circuit board supports  
located on the switch housing side of the actuator.  
2. Gently guide the AGA56.1A97 circuit board into the support slots and slide the board  
downward until both supports snap into place.  
3. Make the following connections to the actuator:  
a. Connect the wire, marked “1” from the circuit board to switch I, terminal 1.  
b. Connect the wire, marked “2” from the circuit board to switch II, terminal 2.  
c. Connect the wire, marked “13” from the circuit board to switch III, terminal 13.  
Page 24  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Potentiometer  
Removal  
9. Remove the white plastic actuator position-indicating dial by gently pulling while  
rotating in the clockwise direction. See Figure 6.  
10. Disconnect the blue, black and brown wire from the potentiometer terminal block. See  
Figure 17.  
11. Remove the silver potentiometer alignment screw.  
12. Loosen the black potentiometer cam attachment screw approximately one turn.  
13. Gently wedge a small screwdriver between the potentiometer and the gray plastic  
housing.  
14. Carefully twist the screwdriver until the potentiometer releases from the cam drum  
shaft. Remove the ASZ… potentiometer.  
Potentiometer  
Installation  
1. Install the new ASZ… potentiometer by gently sliding the bushing over the cam drum  
shaft.  
2. Align the potentiometer alignment screw hole with the hole in the gray plastic housing  
and install the potentiometer alignment screw. See Figures 17 and 17a.  
3. The actuator position indicating pointer, located near the actuator gear end of the cam  
drum, must point to the “0” mark on the actuator position scale. See Figure 6. The  
scale is located on the cam drum nearest to the actuator gear end. Press and hold  
the black cam drum release button while manually rotating the cam drum.  
4. If installing a potentiometer without gear, manually rotate the potentiometer pointer  
until the pointer is exactly in the “min” position. See Figure 17. Firmly tighten the  
black potentiometer cam attachment screw while manually holding the potentiometer  
pointer in alignment. Check the alignment again.  
5. If installing a gear model potentiometer, manually rotate the potentiometer gear until  
the white line next to the “0” or “1” mark on the potentiometer gear face is exactly in  
alignment with the potentiometer gear alignment pointer. See Figure 17a.  
For counterclockwise (ccw) operation the line beside the “1” mark must exactly align  
with potentiometer gear alignment pointer. For clockwise (cw) operation the line  
beside the “0” mark must exactly align with potentiometer gear alignment pointer.  
Firmly tighten the black potentiometer cam attachment screw while manually holding  
the potentiometer gear in alignment. Check the alignment again.  
6. Connect the bundled blue, black and brown potentiometer wires to the terminal block  
located on the ASZ… potentiometer board. See Potentiometer Installation and  
Figures 17 and 17a.  
7. Re-install the white actuator-indicating dial by gently pressing it onto the  
potentiometer cam attachment screw. Align scale position “0” on the actuator position  
indicating dial with the dial pointer by rotating the dial in the clockwise direction to  
avoid loosening the potentiometer gear attachment screw. See Figure 6.  
Siemens Building Technologies, Inc.  
Page 25  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Specifications  
SQM5... Reversing actuator  
Agency approvals  
UL, CSA, CE  
SQM5... Reversing  
Actuator  
Operating voltage  
24 Vac +10%-15%  
110 Vac-15% to 120 Vac +10%  
220 Vac-15% to 240 Vac +10%  
Operating frequency  
Power consumption  
Type of motor  
50 to 60 Hz  
20 VA  
Reversing synchronous motor  
100%  
Duty cycle  
Torque  
See Table 1.  
Maximum shaft torque  
AGA58.1  
90 lb-in  
AGA58.2  
200 lb-in  
220 lb-in  
270 lb-in  
400 lb-in  
See Table 1.  
AGA58.3  
AGA58.4  
AGA58.7  
Timings  
Rotational range of operation  
SQM5x.xxxxxA models  
SQM5x.xxxxxx3 models  
SQM5x.xxxxxx4 models  
SQMSx.xxxxxx6 models  
Direction of rotation  
Shaft  
0° to 160°  
0° to 90°  
0° to 135°  
0° to 160°  
Reversible  
Selectable. See Table 2.  
Custom versions on request  
Shaft disengagement  
Number of auxiliary switches  
Limit switches  
Independent, cam and drive shaft  
4 switches (standard, maximum 6)  
2 switches (standard)  
Electrical rating of auxiliary switches  
Mounting position  
7.5 (3) A, 250 Vac  
Optional  
Ambient operating temperature  
Shipping temperature  
NEMA ratings  
-5°F to 140°F (-20°C to 60°C)  
-58°F to 140°F (-50°C to 60°C)  
NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13  
Connections  
Switches  
Boards  
Spade connectors  
Screwed and spade connectors  
Dimensions  
Weight  
See Figures 28 through 31.  
7.3 lb (3.3 kg)  
Housing  
Aluminum pressure die casting  
Lexan  
Enclosure (cover)  
Motor  
Lock resistant  
Disengagements  
Manual for drive and cam shaft  
Page 26  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Conduit connection  
Two removable inserts with two  
1/2-inch NPSM threads.  
Specifications  
Each insert allows insertion of entire  
cable tree for easy servicing  
SQM5... Reversing  
Actuator, Continued  
Gears and bearings  
Mounting  
Maintenance-free  
Four 1/4"-20 UNC screws in bottom  
Face mounting at gear side also  
possible  
Adaptation to other actuator brands  
Screw pattern and shaft height  
Adaptation with AGA57... adapters  
See Table 2.  
AGA56.1A97 Switch circuit board  
Operating voltage  
Voltage independent  
50 to 60 Hz  
Circuit Boards  
AGA56.1A97  
Operating frequency  
Auto/manual switch  
2-position switch  
Manual toggle switch  
3-position switch  
Ambient operating temperature  
Shipping temperature  
-5°F to 140°F (-20°C to 60°C)  
-58°F to 140°F (-50°C to 60°C)  
0.22 lb (0.1 kg)  
Weight  
AGA56.41A… Electronic circuit boards  
Single potentiometer  
ASZ... (1000 ohm) is required  
Operating voltage  
24 Vac +10%-15%  
110 Vac -15% to 120 Vac +10%  
220 Vac -15% to 240 Vac +10%  
50 to 60 Hz  
AGA56.41A…  
Operating frequency  
Ambient operating temperature  
Shipping temperature  
Input signal  
-5°F to 140°F (-20°C to 60°C)  
-58°F to 140°F (-50°C to 60°C)  
4 to 20 mA  
Impedance  
Current input  
300 Ω  
Zero adjustment  
MIN: 0 to 75%  
MAX: min 100%  
2-position switch  
3-position switch  
0.7 lb (0.33 kg)  
Span adjustment  
Auto/manual switch  
Manual toggle switch  
Weight  
AGA56.42A… Electronic circuit boards  
Same specifications as AGA56.41A  
except  
Input signal  
Impedance  
Current input  
Voltage input  
0 to 135 ohm  
AGA56.42A…  
300 Ω  
100K Ω  
Siemens Building Technologies, Inc.  
Page 27  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Specifications,  
continued  
AGA56.43A…  
AGA56.43A… Electronic circuit boards  
Same specifications as AGA56.41A  
except:  
Input signal  
Impedance  
Voltage input  
0 to 10 Vdc  
100K Ω  
AGA56.9A… Multi function electronic  
circuit boards  
Operating voltage  
Single potentiometer  
ASZ... (1000 ohm) is required  
24 Vac +10%-15%  
AGA56.9A  
110 Vac -15% to 120 Vac +10%  
220 Vac -15% to 240 Vac +10%  
Operating frequency  
Input signals  
50 to 60 Hz  
4 to 20 mA  
0 to 20 mA  
0 to 10 Vdc  
0 to 135 ohm  
Impedance  
Current input  
Voltage input  
Output signals  
300 Ω  
100K Ω  
4 to 20 mA  
0 to 20 mA  
0 to 10 Vdc  
Max output load  
Current output  
<600 ohm  
Voltage output  
> 1.5K ohm  
Zero adjustment  
MIN: 0 to 75%  
MAX: min-100%  
4 to 20 mA on terminal ZF  
Span adjustment  
Split ranging (SHIFT)  
Input signal override (POS)  
Line voltage (... Vac) on terminal P  
adjust with POS potentiometer  
Ambient operating temperature  
Shipping temperature  
Auto/manual switch  
Manual toggle switch  
Weight  
-5°F to 140°F (-20°C to 60°C)  
-58°F to 140°F (-50°C to 60°C)  
2-position switch  
ASZ... Potentiometers  
3-position switch  
0.7 lb (0.33 kg)  
ASZ... Potentiometers  
Versions  
Single and double potentiometer  
See Table 2 and Data Sheet 7921.  
< 0.3% related to drive shaft  
Resistor values  
Hysteresis  
Page 28  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Dimensions  
The first dimension given is measured in inches. Millimeters are shown in parentheses.  
5/8  
(16)  
1-3/16  
(30)  
Pg 13.5 / 1/2"  
NPSM  
ALLOW 3.5" SPACE FOR  
COVER REMOVAL  
1/4  
(6)  
M 8  
1-3/16  
(30)  
1-7/16  
(36)  
5-1/4  
(133)  
3/8  
(10)  
2-5/8  
(67)  
7-1/16  
(180)  
7-1/16  
(180)  
1/8  
(3.5)  
1/16  
(1)  
1/4"-20  
UNC  
4-7/16  
(113)  
3-1/8  
(80)  
5-3/16  
(132)  
6-7/16  
(164)  
5/16  
(8.5)  
5/16  
(7.5)  
Figure 28. SQM5x.xxxRxx Dimensions.  
Siemens Building Technologies, Inc.  
Page 29  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
SQM5… Reversing Actuators  
Dimensions, Continued  
6-7/16  
(164)  
11/16  
(18)  
9/16  
(14.5)  
4-1/16  
(103.3)  
4-7/8  
(123.8)  
AGA57.3  
4-7/16  
(113)  
3-1/8  
(80)  
C
L
4 X 1/4  
(7)  
4 X 1/4  
(7)  
1/8  
(3)  
Figure 29. Mounting Bracket AGA57.3.  
7-5/16  
(185)  
1-9/16  
(40)  
2-1/4  
(57.15)  
7/16  
(11)  
6-7/16  
(164)  
5/16  
(7.94)  
5/16  
(7.94)  
5-5/16  
(135)  
4-7/16  
(113)  
4-3/4  
(120.65)  
4-7/16  
(113)  
AGA57.4  
4
5/16  
(8.73)  
(101.5)  
3-1/8  
(80)  
1-3/8  
(35)  
C
L
3-1/8  
(80)  
2-3/8  
(60.4)  
5/16  
(8.73)  
2-1/2  
(63.5)  
5/16  
(7.94)  
2-3/8  
(60.64)  
1-5/8  
(42)  
2
1-11/16  
(43)  
(50.8)  
1-1/2  
(38.1)  
45  
45  
1/2  
(12.5)  
13/16  
(20.3)  
13/16  
(20.3)  
1/8  
(3)  
All non-sized holes  
O 5/16 (7.62)  
Figure 30. AGA57.4 Mounting Bracket.  
Page 30  
Siemens Building Technologies, Inc.  
SQM5… Reversing Actuators  
Technical Instructions  
Document No. 155-517P25  
July 9, 2007  
Dimensions, Continued  
7.09  
GEAR SIDE  
(180)  
1
(25.5)  
0.39  
(10)  
0.31  
(8)  
0.79  
(20)  
0.35  
(9)  
0.12  
(3)  
AGA58.1  
AGA58.2  
AGA58.3  
0.44  
(11.2)  
1
(25.5)  
0.79  
(20)  
0.47  
(12)  
0.35  
(9)  
0.12  
(3)  
0.52  
(13.2)  
0.81  
(20.5)  
0.85  
(21.5)  
0.35  
(9)  
0.35  
(9)  
0.35  
(9)  
0.43  
(11)  
M5 x 9  
M5 x 9  
0.67  
(17)  
0.78  
(19.8)  
0.42  
(10.6)  
0.42  
(10.6)  
0.375  
(9.5)  
0.375  
(9.5)  
0.27  
(6.9)  
0.27  
(6.9)  
AGA58.4  
8-32 UNC  
28 x 0.56  
(14.2)  
8-32 UNC  
28 x 0.56  
(14.2)  
0.05  
(1.3)  
0.05  
(1.3)  
0.55  
(14)  
1.71  
(43.5)  
1.10  
(28)  
0.20  
(5)  
0.20  
(5)  
AGA58.7  
0.60  
(15.1)  
Figure 31. Shaft Dimensions.  
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as  
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.  
© 2007 Siemens Building Technologies, Inc.  
Your feedback is important to us. If you have  
comments about this document, please send them  
Document No.155-517P25  
Country of Origin: US  
Siemens Building Technologies, Inc.  
1000 Deerfield Parkway  
Buffalo Grove, IL 60089-4513  
U.S.A.  
Page 31  

Panasonic Kx Mc6260 User Manual
Samsung All In One Printer Scx 4728fd User Manual
Samsung As12a5 A6 Mc User Manual
Samsung Avmhc128ca0 User Manual
Sanyo Twicell Hf C1u User Manual
Schumacher Sc 200a User Manual
Soleus Air Air Conditioner Ph5 13r 35d User Manual
Sony Mv 100car User Manual
Toshiba Gf632 User Manual
York Dm072 User Manual