ECO-i Submittal Data  
CHDZ14053  
Heat Recovery: 12 tons VRF Outdoor Unit  
Job Name:  
Location:  
Approval:  
Date:  
Engineer:  
Construction:  
Unit #:  
Drawing #:  
Submitted to:  
Submitted by:  
Reference:  
Compressor Warranty: 6 Years  
Parts Warranty: 1 Year  
Coil Coated to Protect Against Corrosion  
Salt Protection also avilable  
Capacities  
Fan  
Cooling: Btu/h  
Power Input: KW  
Heating: Btu/h  
Power Input: KW  
153,600  
13.3  
170,600  
13.2  
Quantity/Type:  
Fan Motor Output (KW):  
1 Propeller  
0.7  
Power Supply  
V/PH/Hz.  
208-230 / 3 / 60  
Cooling Mode Nominal Conditions  
Indoor: °F DB/°F WB  
Outdoor: °F DB  
Minimum circuit Amps (MCA): Amps  
Max. Overcurrent Protection (MOCP):  
59  
70  
80/67  
95  
25  
Pipe Length (feet):  
Weight (lbs):  
789  
Level Difference (feet):  
0
Refrigerant:  
410A  
Heating Mode Nominal Conditions  
Indoor: °F DB  
Outdoor: °F DB/ °F WB  
Pipe Length (feet):  
70  
47/43  
25  
Coil  
Coil Face Area (sq. ft.):  
Number of Rows:  
22.5  
4
Level Difference (feet):  
0
Protection Devices  
High Pressure Switch:  
Overcurrent (CT Method):  
Crankcase Heaters (W):  
Operating Range  
Cooling: °F DB:  
Heating: °F DB:  
Yes  
Yes  
25 + 32 x 2  
14 to 109  
-4 to 59  
Compressor  
External Finish:  
Electrostatic Powder Coating  
Quantity/Type:  
1 Inverter driven rotary & 2 fxed speed scroll  
Capacity Control Range:  
10-100%  

Lexmark E234 User Manual
Lexmark Menus And Messages C522 User Manual
Lexmark X 952de User Manual
Lotus M111elise User Manual
Microboards Technology Cd Disc To Disc Office Copier Ii User Manual
Savin Dsc338 User Manual
Smc Networks Robo Cylinder Rgd7ad User Manual
Snapper Car Ms5053 User Manual
Sony Found Not Kdl 40w4100 User Manual
Xerox M35 User Manual