Print Form
™
ECO-i Submittal Data
CHDZ14053
Heat Recovery: 12 tons VRF Outdoor Unit
Job Name:
Location:
Approval:
Date:
Engineer:
Construction:
Unit #:
Drawing #:
Submitted to:
Submitted by:
Reference:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also avilable
Capacities
Fan
Cooling: Btu/h
Power Input: KW
Heating: Btu/h
Power Input: KW
153,600
13.3
170,600
13.2
Quantity/Type:
Fan Motor Output (KW):
1 Propeller
0.7
Power Supply
V/PH/Hz.
208-230 / 3 / 60
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
59
70
80/67
95
25
Pipe Length (feet):
Weight (lbs):
789
Level Difference (feet):
0
Refrigerant:
410A
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
70
47/43
25
Coil
Coil Face Area (sq. ft.):
Number of Rows:
22.5
4
Level Difference (feet):
0
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
Operating Range
Cooling: °F DB:
Heating: °F DB:
Yes
Yes
25 + 32 x 2
14 to 109
-4 to 59
Compressor
External Finish:
Electrostatic Powder Coating
Quantity/Type:
1 Inverter driven rotary & 2 fxed speed scroll
Capacity Control Range:
10-100%
|