BMC and BMC-6X Installation and Operation Manual
BMC
BMC-6X
AND
HYDRONIC MODULATING BOILER CONTROL AND EXTENSION
• INSTALLATION AND OPERATION INSTRUCTIONS MANUAL
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
B
---
---
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
C
D
C
US
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
A
RUN
C
SHUTDOWN
/TSTAT
/SETBACK
EXTENSION
MODULE
SYSTEM
PROVE
OUTDOOR SYSTEM
TEMP TEMP
B
D
PWR
SYS
A
B
C
D
CUR / VLT CUR / VLT CUR / VLT CUR / VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
RS-485
L
1
N
2
T
O
T
O
O
O
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
This Weil McLain control is strictly an operating control; it should never be used as a
primary limit or safety control. All equipment must have its own certified limit and safety
controls required by local codes. The installer must verify proper operation and correct any
safety problems prior to the installation of this Weil McLain control.
WARNING
Part Number 550-100-072/0408
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
BMC LAYOUT
Program Switch to restrict access to
function changes. This switch is
covered with Wiring Enclosure.
The digital display shows the system status, set point,
lead stage <in brackets>, and status of each stage.
To view and adjust settings, press the appropriate buttons.
Buttons function is presented on
Bottom Row of display.
LED indicates the
associated relay status.
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
B
C
D
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
---
---
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
C
US
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
RUN
C
SHUTDOWN
/TSTAT
/SETBACK
EXTENSION
MODULE
SYSTEM
PROVE
OUTDOOR SYSTEM
TEMP TEMP
A
B
D
PWR
SYS
A
B
C
D
CUR / VLT CUR / VLT CUR / VLT CUR / VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
RS-485
L
1
N
2
T
O
T
O
O
O
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
Four N.O. Boiler startup relay
When connecting Outdoor and System
Sensors, no Polarity is observed.
Prove terminals must be connected
for BMC to operate boilers.
120VAC Power
outputs. Each is wired in series
with each boiler's limit circuit.
System Output controls
pumps, valves, or other
system components.
Four modulation outputs can be 0-5V,
Connect Extension panels to
add additional stages using
a 6 pin phone line only (cable
provided with BMC-6X).
0-10V, 1-5V, 2-10V, or 4-20ma. Go to
Startup Menu to determine the type of
output for each stage.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
BMC OVERVIEW
SEQUENCES UP TO 4 FULLY MODULATING STAGES.
The BMC is the perfect control whenever multiple fully modulating stages are required for hydronic heating applications. The BMC
controls the on/off and the modulation of each stage to maintain precise system set point control.
PID TYPE LOGIC
The BMC’s control algorithms allow it to look at the rate of change in the system. If the system temperature is changing quickly, the BMC
will react quickly to adjust the modulating stages’output. If the system temperature changes slowly, the BMC will make slow and gradual
output adjustments. Therefore, the BMC adapts to specific system requirements and minimizes fluctuations around the set point.
CONTROLS 0-5 V, 0-10 V, 1-5V, 2-10V, OR 4-20 MA MODULATING MOTORS
The BMC is designed to accurately control the output from 0 to 100% of modulation for each of these different types of motors. One
BMC can even control a variety of the above different motors.
ONLY ONE SENSOR
When Set Point sensor type is selected, the BMC requires only one sensor located in the common output header of all stages. However,
when Reset is selected, an additional Outdoor Sensor is required for Outdoor Reset Ratio input.
DIGITAL DISPLAY OF ALL SYSTEM SETTINGS
The BMC’s alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to follow
menu system allows users to quickly make changes to any system setting without having to learn any specialized codes or keyboard
commands.
AUTOMATIC ROTATION AMONG STAGES
Rotating the first stage to be activated on a call for output promotes even wear on each stage. The BMC has three modes of rotation:
Manual, Last On, or Time. The Time rotates the lead stage every selected time period from every hour to every 60 days.
OUTDOOR RESET
The BMC has a hydronic outdoor temperature reset function. This allows the BMC to change the set point based on outdoor temperature.
Furthermore, additional settings have been added to fine tune this operation, like Offset, Minimum, and Maximum Water Temperature
and night setback schedule.
STANDBY BOILERS
Each of the BMC stages can be configured as a Standby boiler with an adjustable Standby delay. A boiler can be used as a backup during
extended large demand periods.
SYSTEM OUTPUT
In Set Point mode, this output can be used to activate a system pump, combustion air damper, or perform any other function that is required
when any stage is active. In Outdoor Reset mode, the System Output will activate whenever the outdoor temperature is below the Outdoor
Cutoff setting. A System Prove input checks the status of components activated by the System output before stages can be activated.
STAGING (NORMAL) OR PARALLEL MODULATION
The BMC can stage boilers as needed. That will allow it to increase the modulation on the lead boiler. When the lead boiler reaches
its modulation start point adjustment and does not satisfy the load, the BMC will start the next boiler and so on... Moreover, the BMC
allows for a parallel mode that can modulate several boilers together as a one large boiler. This mode is useful for boilers with lower
water content, which are usually more efficient at lower firing points.
ADD UP TO 16 BOILER STAGE (OPTIONAL)
As a stand-alone, the BMC is designed to control four modulating boilers. However, it has the capability of expanding its control to two
extension panels each with six boiler stages. Thus, the BMC can control a total of up to 16 boiler stages.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
UNDERSTANDING OPERATION CONCEPT
1:4 1:3
1:2
1:1.5
220
210
200
190
180
170
160
150
140
130
120
110
100
The BMC has multiple operating modes that satisfy most hydronic systems. It can change the
System Set Point based on outdoor temperature (Outdoor Reset) or it can modulate its stages
to achieve an adjustable fixed Set Point.
1:1.25
1:1
In Outdoor Reset, the BMC controls a hot water heating system to provide a building with
comfortable and even heat levels. The BMC varies the temperature of the circulating heating
water in response to changes in the outdoor temperature. The heating water temperature is
controlled through the modulation of stages.
1.25:1
1.5:1
2:1
3:1
4:1
The BMC also controls the system circulating pump with an adjustable Outdoor Cutoff. When
the outdoor temperature is above Outdoor Cutoff, the pump is off and no heating water is
circulated through the system. When the outdoor temperature drops below the Outdoor Cutoff,
the system pump relay is activated and the heating water circulates through the system. The
temperature of the heating water is controlled by the Reset Ratio, Water Offset, and changes
with Outdoor temperature.
50
30
0
-10
70 60
40
20 10
-20
Outdoor Temperature (in °F)
Reset Ratio is Presented as
Outdoor Temp. : Water Temp. Ratio
Reset Ratio Curves
RESET RATIO/OUTDOOR RESET
1:4
1:1
130
When a building is being heated, heat escapes through the walls, doors, and windows to
the colder outside air. The colder the outside temperature, the more heat escapes. If you
120
With a 0° Offset, the
can input heat into the building at the same rate that it is lost out of the building, then
the building temperatures will remain constant. The Reset Ratio is an adjustment that
lets you achieve this equilibrium between heat input and heat loss.
ratio curves begin at
100° Water Temperature.
110
4:1
100
70
60
50
40
Outdoor Temperature
The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature
: Heating Water Temperature) ratio. This means that for every degree the outdoor
temperature drops, the temperature of the heating water will increase one degree. The
starting point of the curves is adjustable, but comes factory selected at 70°F Outdoor
Temp. and 100°F Water Temp. For example with a 1.00 (OD):1.00 (SYS) ratio, if the
outdoor temperature is 50°F, this means the temperature has fallen 20° from the starting
point of 70°F. Therefore, the heating water temperature will increase 20° to 120°F.
1:4
1:1
110
100
90
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
-20 Offset
50
4:1
8070
60
40
Each building has different heat loss characteristics. A very well insulated building will
not lose much heat to the outside air, and may need a Reset Ratio of 2.00 (OD):1.00
(SYS) (Outdoor:Water). This means the outdoor temperature would have to drop
2 degrees to increase the water temperature 1 degree. On the other hand, a poorly
insulated building with insufficient radiation may need a Reset Ratio of 1.00 (OD):2.00
(SYS). This means that for each degree the outdoor temperature dropped the water
temperature will increase 2 degrees. The BMC has a full range of Reset Ratios to match
any buildings heat loss characteristics.
Outdoor Temperature
1:4
1:1
150
140
130
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
4:1
120
A heating curve that relies not only on Outdoor temperature but also on type of radiation
will improve heat comfort. The following are suggested initial settings for different
types of radiation based on average building insulation and heat loss. The contractor
can fine tune these adjustments based on the specific building need.
90
+20 Offset
100
70
60
50
40
Outdoor Temperature
Type of Radiation in Building
Radiators (Steel & Cast Iron)
Baseboard (Finned copper tube& Cast Iron)
Radiant (High Mass/Concrete)
Radiant (Low Mass/Joists)
Reset Ratio
Offset
0˚F
1.00 (OD) : 1.00 (SYS)
1.00 (OD) : 1.00 (SYS)
4.00 (OD) : 1.00 (SYS)
2.00 (OD) : 1.00 (SYS)
1.00 (OD) : 1.00 (SYS)
WARNING
When controlling a non condensing
boiler directly without the use of a
mixing valve, minimum boiler water
temperature must be set to boiler
manufacturer specifications. In that
case, system temperature must not go
below such temperature.
0˚F
-10˚F
-10˚F
20˚F
Fan Coils & Air Handlers
5
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
MAKE SURE YOU HAVE THE RIGHT CONTROL
If you need the BCP-8W to do additional tasks that either are not listed or do not know how to set them, contact Weil McLain.
INITIAL SETUP
Setting an Initial Program will ease the configuration of the BMC and will give the opportunity to utilize many of the energy saving
features and give more comfortable heat when needed.
The program should consist of the following:
•
•
•
•
•
•
Selecting the features that your system can utilize,
Installation: Install the Control, switches and sensors,
Setting the System Startup,
Setting the System Settings,
Setting the Stages
Adjusting Reset Ratio and Water Offset (In Reset Mode Only)
SELECTING THE SYSTEM FEATURES
The BMC has been designed with Hydronic building heating as the primary purpose. With this in mind, many of the BMC features can
be utilized to ease, enhance and improve your system performance. Some of these features are listed in this section.
OUTDOOR RESET OR SET POINT
•
The BMC can control the System Temperature either by adjusting the calculated temperature according to the Outdoor Temperature
(Outdoor Reset) or by maintaining an adjustable Set Point. The earlier relies on an Outdoor Sensor (supplied with the control) and
achieves better fuel savings in addition to better comfort.
NUMBER OF STAGES
•
The BMC can be configured to control up to 4 modulating boilers. It can control up to 16 boiler stages using a maximum of two
BMC-6X Panels
MODULATION MODE
•
The BMC can stage boilers using one of two methods. Normal Modulation Mode, allows it to increase the modulation of the lead
boiler. When the lead boiler reaches its modulation start point adjustment and does not satisfy the load, the BMC will start the next
boiler and so on. This mode targets boilers that can run more efficient at higher modulation rates.
The Parallel Modulation Mode can modulate several boilers together as a one large boiler. This mode is useful for boilers that are
more efficient at lower firing points.
•
MODULATING SIGNAL
•
The BMC is designed to accurately control the output from 0 to 100% of modulation for each of these different types of motors. One
BMC can even control a variety of the above different modulation motors.
AUTOMATIC ROTATION AMONG BOILERS
•
Rotating the first burner to be activated on a call for output promotes even wear on all burners. The BMC has three modes of rotation:
Manual, Last-ON, or Time automatically rotating every selected time period from every hour to every 60 days.
STANDBY BOILER
•
Any boiler can be configured as a Standby boiler. It withholds a specific boiler from being included in the Lead Rotation. However,
the Standby boiler will be fired only as a backup when all other stages combined cannot satisfy the demand and after an adjustable
delay period.
SETBACK OR DAY/NIGHT SCHEDULING
Two Setback modes are available for the BMC:
•
•
The Day/Night Scheduling provides an adjustable time-based schedule for the Setback.
The Setback mode uses an external signal to switch the operation of the BMC in and out of setback mode.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
System Run-On
•
This feature lets the BMC run the SYS relay for a longer period after the boilers have been turned off. When this relay is used to
control a pump, it helps in dissipating the excess heat from the boilers combustion chamber.
INSTALLATION
Each of the BMC or BMC-6X consists of three primary enclosure components.
•
•
•
The Enclosure Display Module: contains the display, buttons, LEDs and electric wiring terminals. It has two screws to hold it
to the base. A program configuration switch, used to adjust BMC settings, is placed above the terminals. This switch is enclosed
with the enclosure wiring cover for security. Wiring terminals are of the plug-in type to ease installation and removal.
The Enclosure Base: contains the holes to mount and hold the control against the wall or any flat surface. All other enclosure
components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the
bottom to easy installation.
The Enclosure Wiring Cover: seals the wires from the external environment. It has two screws to hold it the base and a hole to
secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been
provided.
Enclosure Display Module
MOUNTING THE ENCLOSURE
•
•
Select a location near the equipment to be controlled.
The surface should be flat and sufficiently wide and strong to hold the BMC
or BMC-6X.
•
•
Keep the control away from extreme heat, cold, or humidity. Ambient
operating temperature is from 20 to 120°F.
Remove the Enclosure Wiring Cover from the control enclosure by
removing the two bottom screws.
•
•
Remove the Enclosure Display Module by removing the middle screws.
Screw the Enclosure Base to the surface through the upper and lower
mounting holes on the back of the enclosure.
•
•
•
Replace the Enclosure Display Module and replace the middle screws.
Do not replace the enclosure wiring cover until all wiring is done.
When purchasing a padlock for the enclosure, the maximum shank diameter
should not exceed ¼"
Enclosure Wiring Cover
Enclosure Base
Hole for optional lock
Mounting Base
Display Mounting Screws
Wiring Cover Mounting Screws
7
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
Immersion Heating System Sensor
INSTALL THE SENSORS
Immersion Well
3/8" ID 1/2" NPT
Common Supply Pipe
HEATING SYSTEM SENSOR (HSS) INSTALLATION
Shield
LOCATING HSS
•
Put the Heating System sensor approximately 10' feet past the last boiler on
the common supply header but before any major takeoffs.
Heating System
Sensor
Sensor Probe
•
The sensor must be located where it sees the output of all the boiler stages. If
a boiler is piped so that the sensor does not see its output, the BMC will not
sequence the boilers correctly.
Strap-On Heating System Sensor
Common Supply Pipe
Pipe Insulation
•
•
Only use a Standard Brass Tube sensor (389-900-230).
The sensor wires can be extended up to 500' using a shielded 2-conductor
cable (Belden #8760 or equivalent). Do not ground the shield at the sensor
but at the panel using one of the terminals marked with an “O”.
Do not run sensor wires in conduit with line voltage wiring.
•
IMMERSION HEATING SYSTEM SENSOR (HSS) INSTALLATION
Shield
Sensor Probe
•
•
Install a 3/8"ID 1/2"NPT immersion well (592-300-023 or equivalent).
Insert the sensor probe of the supplied sensor into the well.
ALERT
STRAP-ON HEATING SYSTEM SENSOR (HSS) INSTALLATION
If the HSS can not sense the correct
heating system water temperature being
supplied to the building, the BMC will not
provide comfortable heat levels. Be sure
the HSS is located on a main supply pipe
which can not easily be isolated from the
system.
•
Strap the sensor to the pipe using metal clamps. Do not over tighten the
clamp.
•
Strap pipe insulation around the sensor and pipe.
OUTDOOR SENSOR INSTALLATION
Outdoor Sensor
•
•
Only use the Weil McLain sensor included with the unit (389-900-229).
Locate the sensor in the shade on the north side of the building. The sensor
should never be in direct sunlight.
Seal around
sensor and wall
•
Be sure the location is away from doors, windows, exhaust fans, vents, or
other possible heat sources.
Outdoor
Sensor
•
•
•
The sensor should be mounted approximately 10' feet above ground level.
Adhere the Outdoor Label provided to the back of the sensor base.
Use the Enclosure Base bottom knockout for the conduit. Use the locknut to
hold the conduit and enclosure base together. Screw the cover to the base.
If screws are used to affix the enclosure to the wall, make sure to seal around
the sensor and wall except from the bottom.
snap-in
location
Mounting
screws
location
•
•
Shield
not connected
The sensor wires can be extended up to 500' using shielded 2-conductor cable
(#18/2). Do not ground the shield at the sensor but at the control using the
terminal marked with an “O”.
Outdoor Label
on back of Sensor
•
Do not run sensor wires in conduit with line voltage wiring.
Outdoor
drip-hole
Conduit
WARNING
The BMC is an operating control only. All boilers must have all
safety and limit controls required by code. It is the responsibility
of the installer to verify that all the safety and limits are working
properly before the BMC is installed.
ALERT
Determining the proper location for the Outdoor Sensor is very important. The BMC will base the heat on the
outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice,
its reading will be different from the actual Outdoor temperature (OD).
8
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
WIRING
PWR
L
1
N
2
WIRING THE POWER (TERMINALS 1, 2)
•
•
•
•
•
Bring the 120VAC 60Hz power wires through the bottom Knockout of the enclosure.
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Connect the hot line to terminal marked L.
120VAC
Power Source
Connect the neutral line to the terminal marked N.
Weil McLain recommends installing a surge suppressor on the power source to the BMC.
WARNING
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Weil McLain recommends installing a surge suppressor on the power source to the BMC.
OUTDOOR SYSTEM
TEMP TEMP
PRO
/DHW
WARNING
T
O
T
O
25 26 27 28 29
Connect the shield at the control terminal end and cut the shield wire at the sensor end.
WIRING THE SENSORS
SYSTEM SENSOR WIRING (TERMINALS 27, 28)
•
•
A BMC must be connected to a temperature sensor located in the common header.
The BMC is designed to be connected to a 389-900-230 temperature sensor for immersion in a 3/8ID
well (592-300-023 or equivalent). Contact the factory for additional temperature sensor options.
Temperature sensor wires can be extended up to 500’ by splicing shielded
2-conductor cable (Belden #8760 or equivalent (#18/2)).
•
•
•
Temperature sensors have no polarity. Connect the two wires from the
sensor to the BMC terminals marked SYSTEM TEMP 27, 28.
Connect the sensor shield to the circled terminal 28 with one of the sensor wires.
OUTDOOR SYSTEM
TEMP TEMP
PR
/D
T
O
T
O
25 26 27 28 29
OUTDOOR SENSOR WIRING (TERMINALS 25, 26)
•
•
When Outdoor Reset is selected, the BMC will vary the system Set Point based on outdoor temperature.
Whether in Set Point or Outdoor Reset modes, the outdoor sensor can be used as an Outdoor Cutoff. The BMC
will disable all boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature. This
feature will automatically be activated when an outdoor sensor is connected.
For an outdoor sensor use a Weil McLain outdoor sensor (389-900-229).
•
•
The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent
(#18/2)).
t
•
•
Temperature sensors have no polarity. Connect the wires from the outdoor sensor to the BMC terminals marked
OUTDOOR TEMP - 25, 26.
Connect the shield to the circled terminal 26 with one of the sensor wires.
EM
P
PROVE
/DHW
SHUTDOWN
/SETBACK
WIRING THE SHUTDOWN, TSTAT, OR SETBACK (TERMINALS 31, 32)
O
O
O
•
•
•
The Shutdown will be available when selected as the Shutdown/Tstat/Setback mode from the Startup menu. See
page 15. This will provide the user with a customizable Day/Night Schedule. See page 21.
The Shutdown feature can be used whenever it is desirable to turn off the BMC stage outputs from a remote
location or another controller (i.e. EMS input).
28 29 30 31 32
The Tstat option, when selected from the Shutdown/Tstat/Setback startup menu, provide the capability of
controlling the operation of the BMC based on a thermostat input.
•
•
The thermostat will provide the BMC with a call for heat by shorting terminals 31 and 32.
When the Shutdown input is enabled by closing the dry contact, or when the Tstat input is disabled by opening
the dry-contact, all active boilers will immediately modulate down to low for the Soft-Off period, then turn off.
The System Output relay will remain active until the System Delay is over and then it will turn off.
Shutdown,
T-Stat, or
Setback Signal
•
•
•
•
When Setback is selected in the Startup, a BMS/EMS or external clock can provide a Setback signal using these input terminals.
The signal must be a dry contact only. No voltage can be placed across the SHUTDOWN/TSTAT/SETBACK terminals.
Bring the two wires from the dry contact to the terminals marked SHUTDOWN/TSTAT/SETBACK- 31,32.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
DOOR SYSTEM
EMP TEMP
PROVE
/DHW
SHUTDOW
/SETBACK
WIRING THE PROVE (TERMINALS 29, 30)
O
T
O
O
O
•
The Prove feature is provided to check system component operation and must be selected in the Startup Menu.
See page 15.
26 27 28 29 30 31 32
•
•
A typical use of this feature is to check for pump flow before firing any boiler.
If the PROVE input is open on a call, the BMC will enable only the System Output. All boiler outputs will be
off when the PROVE input is open.
•
•
A factory-installed jumper provides the System Prove signal. Do not remove the jumper unless it will be
replaced by a System Prove signal or use the terminals for DHW call.
Bring the two wires from the dry contact to the terminals marked PROVE - 29, 30. No voltage can be placed
across the PROVE terminals
Prove Signal
WARNING
The PROVE input cannot be used as a safety limit. All equipment must have its own
certified limit and safety controls as required by local codes. If Prove is selected in the
startup menu, no boiler stage will start unless Prove terminals are shorted. DO NOT
remove the PROVE jumper supplied unless replacing it with a Prove signal.
DOOR SYSTEM
EMP TEMP
PROVE
/DHW
SHUTDOW
/SETBACK
O
T
O
O
O
5 26 27 28 29 30 31 32
WIRING THE DOMESTIC HOT WATER CALL DHW (TERMINALS 29, 30)
•
DHW can be used to raise system Set Point to 200°F or Maximum Water temperature, whichever is lower.
DHW with or without Priority must be selected in the Startup Menu. See page 15.
DHW Call terminals are dry contact N.O. terminals.
Wire an aquastat or other controls to provide closure on the DHW Call terminals.
Remove the jumper on the DHW terminals for proper operation.
DHW Signal
•
•
•
WIRING THE SYSTEM OUTPUT (TERMINALS 3, 4)
SYS
A
3
4
5
6
System Output Operation in Set Point Mode
•
The SYS output relay will energize when the outdoor temperature drops below the Outdoor Cutoff or whenever
a boiler output is active. If no outdoor sensor is connected and the last boiler relay has de-energized, the SYS
relay will remain energized for a period set by the System Run-On. See page 20.
L
N
•
•
No boilers will be activated until the prove input is shorted. If a Prove is not required, the factory-installed
jumper should remain connected.
System Pump
or Pump Starter
A typical use of the SYS output is to activate a system pump starter. The pump can run whenever there is a call
for heat. When heat is no longer required, the pump will stay active for an adjustable Pump Run-On delay.
System Output Operation in Reset Mode
•
•
•
The SYS output relay will energize whenever the outdoor temperature is below the Outdoor Cutoff.
The SYS will remain constantly energized while the outdoor temperature is below the Outdoor Cutoff.
When the outdoor temperature rises 2°F above the Outdoor Cutoff, the SYS output will remain energized for
the period set by the System Run-On. See page 20.
•
•
•
•
The SYS output has one Normally Open (N.O.) relay contact rated for (1/8HP).
The N.O. contacts are dry contacts only. They do not source any voltage.
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Each N.O. contact is capable of switching 6A resistive at 120VAC.
WIRING THE BOILERS
A
B
C
5
6
7
8
9
10 11
WIRING THE BOILER OUTPUTS (A TERMINALS 5, 6), (B TERMINALS 7, 8), ...
•
•
•
•
•
•
•
Each boiler output (A through D) has one Normally Open (N.O.) relay contact.
The N.O. contacts are dry contacts only. They do not source any voltage.
Each N.O. contact is capable of switching 1Amp inductive (1/8HP), or 6A resistive at 120VAC.
Total output of all boilers, including the SYS, must not exceed 15A.
Boiler
Boiler Enable
Output
Wire the N.O. relay contacts in series with the unit’s limit circuit.
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Note that some boilers may not require the use of these outputs.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
A
WIRING TO MODULATING MOTORS
CUR / VLT CUR
GND mA VLT GND
+
The BMC can modulate any combination of the following motors. The Output Type must be selected properly
before connecting any output wires to avoid damage components. See Output Type on page 11.
-
-
+
13 14 15 16 1
WIRING THE 4-20MA MODULATING MOTORS (A TERMINALS 13, 14), (B TERMINALS 16, 17),...
•
•
•
•
The BMC can operate up to four 4-20 mA modulating motors.
4-20mA
+
-
The BMC-6X can operate up to six 4-20 mA modulating motors.
Burner
Motor
The BMC and the BMC-6X sources 24VDC excitation voltage for the 4-20mA signal.
Wire the (-) from the modulating motor to the boiler terminal on the BMC marked (GND). That is for boiler A,
the modulating (-) terminal will be 13.
Wire the (+) from the modulating motor to the boiler terminal on the BMC marked (mA). That is for boiler A,
the modulating (-) terminal will be 14.
Boiler 4-20mA
Modulation Output
•
C
D
UR / VLT CUR / VLT
D
mA VLT GND mA VLT
WIRING THE VOLTAGE MODULATING MOTORS (A TERMINALS 13, 15), (B TERMINALS 16, 18),...
-
+
+
+
+
9 20 21 22 23 24
•
•
•
The BMC can operate up to four 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.
The BMC-6X can operate up to six 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.
Wire the (GND) from the modulating motor to the boiler terminal on the BMC marked (GND). That is for
boiler D, the modulating (GND) terminal will be 22.
Voltage
GND
•
Wire the (V+) from the modulating motor to the boiler terminal on the BMC marked (VLT+). That is for
boiler D, the modulating (V+) terminal will be 23.
V+
Burner
Motor
Boiler Voltage
Modulation Output
CONNECTING TO THE BMC-6X PANELS
•
The BMC is equipped with a 6-pin phone socket (RS485) to connect to extension panels. The BMC-6X is equipped with two
6-pin phone sockets to connect to BMC and an additional BMC-6X.
•
•
•
•
Configure the Output Types (see page 11) after connecting the Extension panels to be able to configure their outputs.
Only 6-wire phone cable must be used for proper operation.
Connection cable is provided as part of the BMC-6X package.
Phone cables must be of a 6-wire with 6-pin terminals. Phone cables can extend up to 100'.
BMC
BMC-6X A
BMC
BMC-6X
Full Modulation Sequencing Control
Full Modulation Sequencing Extension
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
B
C
D
E K
G M
F L
C
US
INPUT RATINGS:
115VAC 60Hz 30VA MAX
H N
ENCLOSED
ENERGY
,
---
---
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
MANAGEMENT
EQUIPMENT
USE COPPER WIRE,
I
O
J
P
CLASS
1
WIRE ONLY.
LISTED
99RA
Use Copper Conductors Only.
Comm
Power
C
US
ENCLOSED
ENERGY
CAUTION: Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
RUN
C
Ext
A
Ext
B
SHUTDOWN
EXTENSION
MODULE
OUTDOOR SYSTEM
TEMP TEMP
PROVE
/DHW
A
CUR
B
D
VLT
EXTENSION
MODULE
PWR
SYS
A
B
C
D
/TSAT
I
O
J
P
/
PWR
E
3
K
4
F
5
L
G
7
M
8
H
9
N
I
O
J
P
/
VLT CUR
/
VLT CUR
/
VLT CUR
/
/SETBACK
CUR
/
VLT CUR
VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
L
1
N
2
T
O
T
O
O
O
RS-485
GND GND GND mA VLT mA VLT
GND
GND
GND
L
1
N
2
RS-485
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
6
10 11 12 11 12
13 14 15
17 18 19 20 21
23 24 25 26 27 29 30
28
16
22
BMC-6X B
BMC-6X
Full Modulation Sequencing Extension
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
E K
G M
F L
Connecting BMC to
Two Extension Panels
using RS485
C
US
H N
ENCLOSED
ENERGY
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
MANAGEMENT
EQUIPMENT
I
O
J
P
LISTED
99RA
Use Copper Conductors Only.
Comm
Power
CAUTION: Risk of Electric Shock.
More than one disconnect switch may be required
to de-energize the equipment before servicing.
Ext
A
Ext
B
EXTENSION
MODULE
I
O
J
P
/
PWR
E
3
K
4
F
5
L
G
7
M
8
H
9
N
I
O
J
P
CUR
/
VLT CUR
VLT
GND GND GND mA VLT GND mA VLT
GND
GND
GND
L
1
N
2
RS-485
6
10 11 12 11 12
13 14 15
17 18 19 20 21
23 24 25 26 27 29 30
28
16
22
11
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
MENU SEQUENCE
----------- SETTINGS ------------
------------- SEASON --------------
Winter
Summer
------- OUTDOOR CUTOFF -------
Season
Winter
70 F
Set Point
<System Settings>
<Maintenance>
<Histories>
65
F
[]
<System Startup>
BACK
SAVE
BACK
SAVE
BACK
SELECT
Reset Ratio
------------ SET POINT ----------
--- MINIMUM WATER TEMP ----
70
F
[]
70
F
STARTUP
[]
BACK
SAVE
-------- SYSTEM STARTUP ------
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
(START)
to continue
--- MAXIMUM WATER TEMP ----
240
F
BACK
START
[]
------------- WARNING ------------
BACK
SAVE
THESE SETTINGS
CHANGE PRIMARY
BACK
SAVE
SYSTEM FUNCTIONS.
-------------- OFFSET -------------
--- SYS= 91 F, 10:57Am ---
BACK
CONTINUE
+0
F
[]
-------- ARE YOU SURE? -------
No
Yes
BACK
SAVE
BACK
NEXT
--- OD= 54 F, 11:36Am ---
HISTORIES
BACK
SAVE
Reset Options
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
----- EMS 20ma SETPOINT-----
BACK
EXIT
220
F
Reset C
[
]
BACK
SAVE
BACK
SAVE
Set Point
------ EMS INPUT MODE -------
Disable
Enable
------ EMS 4ma SETPOINT------
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
120
F
[
]
BACK
SAVE
BACK
SAVE
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
----- PROVE/DHW SHARING ----
Prove
DHW Without Priority
DHW With Priority
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
Setback Input
---------- BOOST MODE ---------
30 Minutes
Disabled
--------- SENSOR FAULT --------
All Off
All On
----- SETBACK/SHUTDOWN -----
Shutdown Input
Tstat Input
Setback Input
BACK
SAVE
BACK
SAVE
BACK
SAVE
12
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
---------------- GAIN --------------
----------- SETTINGS ------------
Season
Set Point
Winter
70 F
+0
F
[]
<System Settings>
<Maintenance>
<Histories>
SYSTEM SETTINGS1
BACK
SAVE
---------- SETTINGS 1 ----------
<System Startup>
Gain
+0
Time
0.0min
0min
BACK
SELECT
Lead Rotation
Purge Delay
Lag Delay
-------- LEAD ROTATION -------
Manual
Time
<More Settings>
Last-On
BACK
SELECT
MAINTENANCE
BACK
SAVE
---------- MAINTENANCE ---------
--- AUTO ROTATE PERIOD ---
System Trim
+0 F
+0 F
45sec
Outdoor Trim
Soft-Off Delay
<Output Trim>
<Configuration>
SYSTEM SETTINGS2
24hrs
[]
---------- SETTINGS 2 ----------
BACK
SELECT
Standby Time
System Run-On
Setback
Last Stage Hold
Set Time
10min
0min
0 F
0 F
12:03Pm
BACK
SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
------- SOFT-OFF DELAY --------
<Day/Night Schedules>
BACK
SELECT
45sec
[]
BACK
SAVE
--- DAY/NIGHT SCHEDULES ---
BACK
SAVE
Set Time
Day Schedule
Night Schedule
**:**
**:**
**:**
--------- PURGE DELAY ---------
-- OUTDOOR SENSOR TRIM ----
0.0min
[]
BACK
SELECT
+0
F
[]
BACK
SAVE
-------------- SETBACK -----------
BACK
SAVE
----------- LAG DELAY -----------
0
F
--- SYSTEM SENSOR TRIM ----
[]
0min
[]
BACK
SAVE
+0
F
[]
BACK
SAVE
-------- SYSTEM RUN-ON --------
BACK
SAVE
0min
[]
------ CONFIGURATION 1 ------
v1.00c
------ LAST STAGE HOLD ------
Reset F
Normal
Day/Night Schedules
All Off
BACK
SAVE
0
F
[]
-------- STANDBY DELAY --------
BACK
NEXT
BACK
SAVE
10min
[]
----- SET PRESENT TIME -----
11:**Pm
------ CONFIGURATION 2 ------
A=4-20ma
C=0-5v
B=0-10v
D=2-10v
BACK
SAVE
BACK
SAVE
BACK
EXIT
-------- STAGE A TRIM --------
Output Trim
<Prev Stage>
<Next Stage>
+0.0
ALERT
To be able to change the BMC
settings the Program/Run Switch
must be set to Program. The switch
is located under the Enclosure
Wiring Cover for security. The
Enclosure Wiring Cover can be
securely closed using a lock.
BACK
SELECT
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[]
BACK
SAVE
13
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
STARTUP SETTINGS
ALERT
A good practice after performing any Startup menu modifications is to
check all operating settings and adjustments to match the new settings.
PROGRAM CHANGE SETTINGS
To be able to change the BMC settings the Program/Run Switch must be set to Program. The
switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover
can be securely closed using a lock.
PROGRAM
RUN
STARTUP SEQUENCE
-------- SYSTEM STARTUP ------
Button: MENU/<System Startup>
(START)
to continue
•
•
When powered, the BMC performs a self diagnostics-test on its components.
On the first power up, the System Startup screen will appear after the initialization is
complete. If it doesn’t, the BMC has already been configured.
•
The System Startup menu sets the main parameters like the type of sensor, the type of
output, and the modulating mode.
BACK
START
SENSOR TYPE
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Set Point °F, Set Point °C, Reset °F, Reset °C
Button: MENU/<System Startup>/..../Sensor type
Default: Set Point °F
•
Reset mode is only available if an outdoor sensor is connected to terminals 25 and 26.
DO NOT select Reset without an outdoor sensor.
Reset C
•
•
The same Weil McLain temperature sensor can display in either °F or °C.
If °F is selected, all temperatures and settings will be displayed in degrees Fahrenheit and
the BMC will operate as a Set Point Control in degrees Fahrenheit.
If °C is selected, all temperatures and settings will be displayed in degrees Celsius and
the BMC will operate as a Set Point Control in degrees Celsius.
Set point mode does not require an outdoor sensor. If an outdoor sensor is connected in
Set Point mode it will be used only as an outdoor cutoff point. That is, to turn the boilers
and system pump off.
BACK
SAVE
•
•
------ EMS INPUT MODE -------
Disable
Enable
EMS INPUT MODE (AVAILABLE IN SET POINT ONLY)
Disable, Enable
Default: Disable
BACK
SAVE
4mAAdjustable from 70ºF/21ºC to 200ºF/93ºC
20mAAdjustable from 90ºF/32ºC to 240ºF/116ºC
Button: MENU/<System Startup>/..../EMS Input Mode
Default: 140ºF/ 60ºC
Default: 200ºF/ 93ºC
------ EMS 4ma SETPOINT------
120 F
•
•
•
•
This allows the BMC to receive an external set point from an EMS/BMS system.
[
]
You must select the 4mA (min) and 20 mA (max) Set Points in the following screen.
The 4mA can be set to any temperature between 70ºF to 200ºF.
The 20mA can be set to any temperature between 90ºF to 240ºF. However, the minimum
must be 20ºF higher than the 4mA setting.
BACK
SAVE
•
Connect the 4-20mA EMS Control Interface to the BMC RS485 connection.
------- OUTPUT A TYPE --------
SELECTING THE OUTPUT TYPE
4-20ma
0-10v
0-5v
2-10v
1-5v
4-20mA, 0-5V, 0-10V, 1-5V, or 2-10V Outputs
Default: 0-10V
Button: MENU/<System Startup>/..../Output A type/Output B type
•
Outputs can be configured for 4-20mA operation (current) or the voltage range can be
BACK
SAVE
selected (0-5V, 0-10V, 1-5V, 2-10V).
•
•
Check the modulating motor to determine its control requirements.
When using Extension panels, connect them prior to configuring the Output Type. Otherwise, the BMC will not configure them
properly.
•
Select the appropriate Output Type for each of the boilers. The BMC can have a different Output type for each boiler.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
SELECTING THE MODULATING MODE
------ MODULATION MODE ------
Normal
Parallel
Normal, Parallel
Default: Normal
Button: MENU/<System Startup>/..../Modulating Mode
•
Some modulating boilers perform better as their modulation increases. For these
units, it is advantageous to run one unit at high modulation than several units at lower
modulation. If the units used are of this type, select Normal. This is the recommended
setting for typical steel and cast iron boilers or boilers with low turndown ratios.
BACK
SAVE
•
There are many condensing boilers that run more efficiently at lower modulation. If it is more energy efficient to run several
units at lower modulation than one at high, select Parallel. This is typically used on water-tube boilers, low mass boilers, or
burners with high turndown ratios.
----- PROVE/DHW SHARING ----
PROVE/DOMESTIC HOT WATER (DHW)
Prove, DHW Without Priority, DHW With Priority
Button: MENU/<System Startup>/..../Prove-DHW Sharing
Prove
DHW Without Priority
DHW With Priority
Default: Prove
•
•
Input Terminals 29 and 30 can be used with either of the above features.
BACK
SAVE
When Prove is selected, the BMC will not start any boiler stage unless Prove terminals
are connected.
•
•
Using those terminals to connect to an aquastat for a Domestic Hot Water call and selecting either of the DHW options will
raise the calculated water temperature to the lower of 200°F or Max Water Temperature.
Domestic Hot Water Without Priority allows the SYS relay, mostly controlling a primary system pump, to remain energized
during a domestic hot water call (aquastat call on terminals 29 and 30). In Summer, Shutdown, No Tstat call for heat, or when
outdoor temperature is above Outdoor Cutoff, a DHW call will energize the SYS relay. After the DHW call termination, the
SYS relay will continue to run for the System Run-On period before turning off.
•
However, Domestic Hot Water With Priority de-energizes the SYS relay during a domestic hot water call (aquastat call on
terminals 29 and 30) for a period of one hour. If after the hour period the DHW call still exist, the SYS relay will energize and
the BMC will continue in the higher temperature setting until the domestic hot water call has terminated.
----- SETBACK/SHUTDOWN -----
Shutdown Input
Tstat Input
SHUTDOWN/TSTAT/SETBACK MODE
Shutdown Input, Tstate Input, Setback Input
Button: MENU/<System Startup>/..../Setback\Shutdown
Default: Shutdown Input
Setback Input
•
•
•
The BMC has two levels of heat, a Normal/Day and a Setback/Night. The Normal is
BACK
SAVE
good for when buildings are occupied and people are active. The Setback/Night holds a
lower system temperature and is for when buildings are unoccupied or inactive.
When Shutdown or Tstat are selected, the Day/Night Schedules (see page 21) will be available in the operating menu.
Terminals 31 and 32 will function as a Shutdown (Turn off boilers when shorted) or Tstat (Turn off boilers when opened) of the
heat functions. However, a call for DHW will bring the boilers on.
When Setback is selected, the External Signal option will switch the BMC to Setback mode when shorted on terminals 31 and
32. This allows the BMC to be managed by an external device or control to provide setback. No scheduling or boost menu
options will be available with Setback.
---------- BOOST MODE ---------
30 Minutes
Disabled
BOOST MODE (NOT AVAILABLE WITH SETBACK)
30 Minutes, Disabled
Default: 30 Minutes
Button: MENU/<System Startup>/..../Boost Mode
•
•
•
If you do not want a Boost simply select Disabled from the Boost Menu.
Boost is only available if Shutdown or Tstat is selected as a previous option.
BACK
SAVE
The morning Boost is designed to return the building to comfortable ambient temperatures after the cooler Night (Setback)
period. The BMC will accomplish this by running elevated water temperatures (will add Setback setting to calculated water
temperature) for 30 minutes before the start of the Day schedule setting. That is, if the normal day set point at a specific outdoor
was 145˚F and the Setback setting was 20˚F, the boost will raise the system calculated temperature to 165˚F for 30 minutes
before the start of the Day Schedule setting.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
SENSOR FAULT
--------- SENSOR FAULT --------
All Off
All On
All Off, All On
Default: All On
Button: MENU/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of all output stages that are set to Auto
when a sensor reads Short or Open.
BACK
SAVE
RESET MODE
•
When All-On is selected, the BMC will turn all boilers On to a 100% when System reads Short or Open and Outdoor is below
Outdoor Cutoff. When Outdoor reads Short or Open, the BMC will turn all boilers On to a 100%.
When All-Off is selected, the BMC will turn all boilers Off when either System or Outdoor sensor reads Short or Open.
•
SET POINT MODE
•
•
•
When All-On is selected, the BMC will turn all boilers On to a 100% when the System sensor reads Short or Open.
When All-Off is selected, the BMC will turn all boilers Off when the System sensor reads Short or Open.
The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.
SETTING THE CONTROL TO FACTORY DEFAULTS
To Reset the BMC control to its original factory defaults, power down the control. Hold
TOTAL CLEAR STARTED
down the two right most buttons while powering the control back up until the Total
Clear Startedscreen appears. The Display will direct you to the Startup menu to
program the control after the defaults are loaded.
Release buttons
and
Please Wait
NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.
ALERT
Do not turn off power to control until all Startup settings have been made. Otherwise, the next
power-up will be set to many Startup factory settings that might not fit your application.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
OPERATING SETTINGS
PROGRAM CHANGE SETTINGS
PROGRAM
RUN
To be able to change the BMC settings the Program/Run Switch must be set to Program. The
switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover
can be securely closed using a lock.
------------- SEASON --------------
Winter
Summer
SEASON
Winter, Summer
Default: Winter
Button: MENU/Season
•
The BMC will turn all boiler relays off when it is in Summer setting. However, a DHW
call will bring boilers back on if needed. The Message Display Line will display Summer
to show status.
When in Winter, the BMC will activate the Sys relay whenever the Outdoor temperature
(OD) falls to or below the Outdoor Cutoff setting. In addition, it will begin heating
whenever the System temperature (SYS) falls below the Set Point Temperature. The
Message Display Line will not display any season information when in Winter.
When the heating season is over, it is a good practice to switch the BMC to Summer
setting. This will allow DHW calls to operate the boilers when needed.
BACK
SAVE
ALERT
•
DO NOT turn power off to the
BMC when heating season is
over. If you do so, the battery
will run down and will have to
be replaced. Instead, switch to
Summer.
•
SET POINT (NOT ADJUSTABLE IN EMS MODE)
Adjustable from 70ºF/ 21ºC to 250ºF/ 121ºC
Button: MENU/Set Point
------------ SET POINT ----------
Default: 140ºF/ 60ºC
70 F
•
•
•
The Set point is the temperature value the BMC will use to control the system.
[]
It only be available when Set Point is selected as the Sensor Type. See page 14.
The BMC will increase, decrease or hold the modulation of the boilers to maintain the
system temperature around the Set point. The amount of fluctuate around the set point
depends on the Modulation Mode, System Settings, and Stage Settings.
If the EMS Mode was Enabled, the Set Point will be set by the EMS/BMS system and
will be available to be read but not changed on the display.
BACK
SAVE
•
RESET RATIO
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
Adjustable 1.00ºOD : 4.00ºSys to 4.00ºOD : 1.00ºSys
Button: MENU/Set Point
Default: 1.00ºOD : 1.00ºSys
•
•
It's only be available when Reset is selected as the Sensor Type. See page 14.
The Reset Ratio determines how the System water temperature (SYS) will vary with
Outside temperature (OD). With any of the ratios, the colder it becomes outside,
the hotter the temperature of the system water. The ratios are adjustable from 1.00
(OD):4.00 (SYS) to 4.00 (OD):1.00 (SYS). (See Understanding Operation Concept on
page 5)
•
With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase
rapidly as the outside temperature falls, hitting the maximum of 240°F at 24°F outside
temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS)
will increase slowly as the outside temperature falls. Even at -30°F, the system water
will only be 125°F, and at 24°F outside, the system water will be 112°F. Such a low
BACK
SAVE
Reset Ratio might be used with radiant floor heating applications.
1:4
1:1
•
•
With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good
130
120
Warmer
place to start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside
temperature falls, the system water temperature is increased one degree.
If required: Adjust the RESET RATIO in cold weather. If the ambient building
temperatures are too cold in cold weather, move the ratio to a higher selection. That is,
if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25
(SYS). If the building temperatures are too warm in cold weather, move the ratio to
a lower selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the
selection to 1.25 (OD):1.00 (SYS).
Colder
110
4:1
100
70
60
50
40
Outdoor Temperature
17
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
OUTDOOR CUTOFF TEMPERATURE
------- OUTDOOR CUTOFF -------
Adjustable Off, from 20ºF/ to70ºC - 100ºF, On
Button: MENU/Set Point/Outdoor Cutoff
Default: 60ºF/ 16ºC
in Set Point
65 F
Button: MENU/Set Point/Offset/Outdoor Cutoff
in Reset
[]
•
•
•
•
If the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear
after the temperature Set Point has been selected.
BACK
SAVE
When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the
BMC will control and modulate boilers to hold the calculated temperature.
When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the BMC will turn all boilers off. The System
relay will remain energized for the Run-On delay then de-energize.
The Outdoor Cutoff can be set from 20°F to 100°F. In addition, the Setting can be set to ON or OFF. In the ON position, the
System Relay will run regardless of the Outdoor temperature (OD) and the burner stages will be active to hold the calculated
water temperature. (Note: The lowest water temperature the BMC will circulate is 70°F. If the Outdoor Cutoff is turned ON
and the Season is set to Winter, the BMC will circulate at least 70°F water even in the hottest of weather.) In the OFF position,
the system pump will always be off and all burner stages will be off.
OFFSET
-------------- OFFSET -------------
Adjustable from 50Fº/28Cº to (-50Fº/-28Cº)
Button: MENU/Set Point/Offset
Default: 0Fº/0Cº
in Reset only
+0 F
•
The Offset setting lets you adjust the starting points of the Reset Ratio curves. This
[]
means that, regardless of the Outdoor temperature (OD), or the Reset Ratio that has
been selected, when the Offset setting is changed, that change is directly added to or
subtracted from the calculated temperature. For example, if the Set Point temperature
was 130°F and the Offset was changed from 0° to 10° (an increase of 10°), then the Set
Point temperature would increase to 140°F
BACK
SAVE
•
•
The Offset setting does not change the ratio selection. For instance, with 1.00 (OD):1.00 (SYS) Reset Ratio, the System water
temperature (SYS) will always increase one degree for each degree change in the Outdoor temperature (OD). What the Offset
does is add or subtract a constant temperature value. (See Understanding Operation Concept on page 5)
If required: Adjust the Water Offset in mild weather. If the ambient building temperatures are too warm in the mild weather,
decrease the Water Offset. If the ambient building temperatures are too cold in the mild weather, increase the Water Offset. The
rule of thumb for baseboard radiation is to change the Offset 4°F for every 1°F you wish to change the building temperatures.
In radiant heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building temperature.
--- MINIMUM WATER TEMP ----
MINIMUM WATER TEMP
Adjustable from 70ºF/21ºC to 180ºF/82ºC
Default: 140ºF/ 60ºC
in Reset only
70 F
[]
Button: MENU/Set Point/Offset/Outdoor Cutoff/Minimum Water Temp
•
The Minimum Water Temperature must be set to the boiler manufacturer’s specification.
BACK
SAVE
The BMC will calculate the Set Point based on the Outdoor temperature (OD), the Reset
Ratio, and the Offset value. The BMC will control all boilers modulation to
hold either the Set Point temperature, or the Minimum Water Temperature, whichever is higher.
•
The Minimum Water Temperature must be at least 20°F lower than the Maximum Temperature (See next setting).
MAXIMUM WATER TEMP
--- MAXIMUM WATER TEMP ----
Adjustable 90ºF/21ºC - 240ºF/116ºC
Default: 200ºF/93ºC
Button: MENU/Set Point/Offset/..../Maximum Water Temperature
in Reset only
240 F
•
•
•
This is the highest temperature heating water the BMC will circulate through the heating
[]
system. It is available in Reset mode only.
When using a radiation system, it should be set according to the tubing or floor
manufacturer’s specification.
The Maximum Temperature must be at least 20°F higher than the Minimum Temperature
(See previous setting).
BACK
SAVE
18
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
---------- SETTINGS 1 ----------
SYSTEM SETTINGS
The Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for
enhanced comfort and more fuel savings. The BMC behaves differently based on the selected
Control Modes (see Startup Settings).
Gain
+0
Time
0.0min
0min
Button: MENU/<System Settings>
Lead Rotation
Purge Delay
Lag Delay
<More Settings>
BACK
SELECT
•
•
•
•
•
Gain
•
•
•
•
System Run-On
Setback
Last Stage Hold
Day/Night Schedules
---------- SETTINGS 2 ----------
Lead Rotation
Purge Delay
Lag Delay
Standby Time
Standby Time
System Run-On
Setback
10min
0min
0 F
Last Stage Hold
Set Time
0 F
12:03Pm
<Day/Night Schedules>
ALERT
BACK SELECT
To be able to change the BMC settings the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.
PROGRAM
RUN
GAIN
---------------- GAIN --------------
Adjustable from -10 to +10
Button: MENU/<System Settings>/Gain
Default: 0
+0
F
•
The Gain adjusts the aggressiveness of the BMC PID logic to control how much
[]
modulation is changed when the system temperature is different from the Set Point.
A Gain of 0 is a good starting point for all systems.
If during normal load conditions, the system temperature tends to oscillate significantly,
decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15
minutes before evaluating how the change has affected the system.
If during normal load conditions the system temperature tends to remain consistently
below the Set Point (or consistently above the Set Point), increase the Gain by two
numbers (for example, from 0 to 2). Wait for at least 15 minutes before evaluating how
the change has affected the system.
•
•
BACK
SAVE
-------- LEAD ROTATION -------
Manual
Time
•
Last-On
BACK
SAVE
--- AUTO ROTATE PERIOD ---
LEAD BOILER ROTATION
24hrs
[]
Adjustable Manual, Time (1 hr to 60 Days), Last-On
Button: MENU/<System Settings>/Lead Rotation
Default: Time (24Hours)
•
•
The Lead Boiler is the first boiler brought on when output is required.
The Lead Boiler can be rotated automatically, manually or based on Last-On. The
automatic rotation is recommended.
BACK
SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
•
•
The current Lead Boiler is shown in brackets on the main display.
Only boilers which are set to Auto Mode can be Lead. Therefore, not all the boilers may
be available when manually selecting a new Lead Boiler.
BACK
SAVE
PURGE DELAY
--------- PURGE DELAY ---------
Adjustable from 0.0min to 10.0min
Button: MENU/<System Settings>/Purge Delay
Default: 1.0min
0.0min
•
•
Many boilers go through a purge cycle before they are brought on line.
[]
When the BMC activates a boiler, it does not start to calculate its output until the Purge
Delay is over. This allows the boiler to fully come online and begin producing output.
The Purge Delay helps prevent short cycling of a newly activated burner. Once the
burner is activated, it MUST run through the entire Purge Delay period.
The minimum Purge Delay setting MUST be set to the time required by the boiler
manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5min will equal 90 seconds.)
The Message Display Line will display Purge Delay and the amount of time remaining
in the purge.
BACK
SAVE
•
•
•
ALERT
Set Purge Delay as per boiler
manufacturer recommendation.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
LAG DELAY
----------- LAG DELAY -----------
Adjustable from 0min to 60min
Default: 0min
Button: MENU/<System Settings>/Lag Delay
0min
[]
•
The Lag Delay requires the previous stage to remain at 100% modulation for the full
period of the Lag Delay before another Stage can be activated. For example, if the Lag
Delay was set to 10 minutes, the Lead Stage would need to remain at 100% modulation
for a full ten minutes (never backing down to even 99%) before a lag stage could be
activated. The Message Display Line will display Lag Delay and the remaining time.
Set the Lag Delay to 0 min when two or more Stages will generally be needed to hold the load.
The Lag Delay is useful in installations where one unit should usually have enough output to hold the load unless it fails or load
conditions become extreme.
BACK
SAVE
•
•
•
•
The Lag Delay overrides the value of the Modulation Start % selected for each stage. Regardless of that setting, the previous
stage must reach 100% and stay there before the lag stage can be activated.
The full Lag Delay must always elapse regardless of what happens to system temperature. Therefore, set the Lag Delay to 0 min
if you want smooth set point control using multiple units.
STANDBY DELAY
-------- STANDBY DELAY --------
Adjustable from 1min to 60min
Default: 10min
Button: MENU/<System Settings>/<More Settings>/Standby Time
10min
[]
•
•
•
The Standby Delay only applies to boilers in Standby Mode. See Mode on page 25.
A boiler can be set to be a Standby boiler using the Stage Menu.
A Standby boiler can only be activated after all the boilers in Auto Mode have run at
100% modulation for the full Standby Time.
BACK
SAVE
•
•
Standby boilers are used for backup or extreme load conditions only. A Standby boiler
can never be a Lead Stage
The full Standby Delay must always elapse regardless of what happens to system temperature. Therefore, shorter Standby
Times will result in smoother set point operation in extreme conditions. Longer Standby Times may prevent a Standby boiler
from firing if the other boilers can eventually meet the load, or if the load decreases.
SYSTEM RUN-ON
-------- SYSTEM RUN-ON --------
Adjustable from 0min to 360min
Default: 0min
Button: MENU/<System Settings>/<More Settings>/System run-On
0min
[]
•
The SYS relay will energize whenever the Outdoor temperature (OD) is below the
Outdoor Cutoff and the Shutdown is Open or the Tstat is closed. When the Outdoor
temperature increases 2°F above the Outdoor Cutoff after the last burner relay has de-
energized, the SYS relay will stay on for a period set by the System Run-On.
A common use for the System Run-On is to control a system pump in a heating system. The extra time helps transfer the heat
from the boilers to the heating system.
The System Run-On time should be set based on the size and type of the boilers and pumps. In general, a boiler with low
water content and high horsepower will need a longer System Run-On than a boiler with the same horsepower and more water
content. (Refer to boiler manufacturer recommendation)
BACK
SAVE
•
•
SETBACK
-------------- SETBACK -----------
Adjustable from 0F°/0C° to 75F°/42C°
Button: MENU/<System Settings>/<More Settings>/Setback
Default: 0F°/0C°
0
F
•
The Setback feature can be used to provide the BMC with a lower temperature Set Point
when less load is required.
[]
•
•
The lower Set Point will appear on the main display indicating this condition.
For example, if the calculated temperature is 180°F and the Setback is 20°F, then when
in Setback, the BMC will hold a Set Point of 160°F.
BACK
SAVE
•
•
A typical use for Setback is to provide less system temperature to a building during the
night or on the weekends when building is not occupied, but heat is still required.
The amount of Setback selected is subtracted from the Set Point when a Setback Input
Signal is received or the Night Time schedule setting started.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
If Setback Input is selected as a Shutdown/Tstat/Setback Mode (See page 15), the Setback will not be activated unless a Short
dry contact signal is received on the Shutdown/Tstat/Setback terminals (31 and 32) as a signal.
If Shutdown Input or Tstat Input is selected as a Shutdown/Tstat/Setback Mode (See page 15), the Setback will be activated only
when Night Schedule time has started.
•
•
ALERT
When using Soft-Off and Last Stage Hold, the last boiler stage will not turn off
until both parameters have elapsed. In this case, Soft-Off will start after the Last
Stage Hold.
LAST STAGE HOLD
------ LAST STAGE HOLD ------
Adjustable from 0F°/0C° to 30F°/17C°
Default: 0F°/0C°
Button: MENU/<System Settings>/<More Settings>/Last Stg Hold
0
F
•
•
The Last Stage Hold prevents short cycling of the Lead Stage during low load periods.
[]
In low load conditions, the system might require less output than the lowest fire on one
Stage. When the BMC brings on the Lead Stage, the Set Point is quickly exceeded, and
the BMC turns the Lead Stage off.
BACK
SAVE
•
•
To prolong the run time during this type of condition, use the Last Stage Hold setting to
let the system temperature exceed the Set Point by the number of degrees selected.
For example, with a Set Point of 160°F and a Last Stage Hold setting of 10°F, the Lead
Stage boiler will remain on, at low modulation, until the Set Point reaches 170°F.
In many cases, it is better to overshoot slightly than to short cycle a boiler.
When Soft-Off is set to other than 0 seconds, the Lead Boiler will need to remain at or
exceed the Last Stage Hold for the Soft-Off period before turning off.
•
•
WARNING
AVOIDING CONFLICTING BOILER LIMITS
The temperature limits set on
the boilers must be higher than
the BMC Set Point. Read the
section at left for details that
will prevent erratic system
operation.
•
The temperature limits set on the boilers MUST be set considerably higher than the
BMC’s Set Point for the reasons detailed below.
•
•
The BMC sensor is located in a common header some distance from the boilers.
As the temperature rises in the header and before reaching the sensor location, energy is
dissipated. Therefore, the temperature in the header could be lower than that registered
by boiler sensors.
•
•
In addition to the normal drop experienced between the boiler’s temperature and that
read by the BMC sensor, the Last Stage Hold setting must be accounted for. The boiler limit must be set above the Set Point
PLUS the Last Stage Hold PLUS the normal drop experienced in the piping.
Using the previous example of a 10°F Last Stage Hold with a 160°F Set Point, the boilers’ limits must be set enough over 170°F
to prevent the boilers’ internal limits being reached. In this situation, the boiler high limit should be set at approximately 180°F
or higher to prevent the difference in boiler temperature vs. header temperature causing erratic operation.
DAY/NIGHT SCHEDULES
--- DAY/NIGHT SCHEDULES ---
Set Time
Day Schedule
Night Schedule
**:**
**:**
**:**
(Available when "Shutdown or Tstat" is selected from the Shutdown/Tstat/
Setback Startup menu option only)
Button: MENU/<System Settings>/<More Settings>/Day/Night Schedules
•
•
The BMC has two levels of heat. The Day level is used when a building is occupied and
people are active.
The Night (Setback) level is used when a building is not occupied, or when people are
sleeping. This setting reduces the calculated temperature by the Setback setting (See
page 20). If the Day calculated water temperature was 150˚F and the Setback was 20˚F,
the Night Schedule will run at (150˚F - 20˚F) = 130˚F.
If the Boost feature is being used, it uses the Day Schedule as a Boost ending point. That is, if the Day Schedule is set to start
at 6:00AM, the Boost will start 30 minutes prior to the Day setting at 5:30AM. The BMC will then raise the calculated water
temperature by the Setback amount. Using the previous example, at 5:30AM the BMC will raise the calculated water to 170˚F
(150˚F + 20˚F) until 6:00AM.
BACK
SELECT
•
21
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
----- SET PRESENT TIME -----
SET TIME
Button: MENU/<System Settings>/<More Settings>/Set Time
Button: MENU/<System Settings>/<More Settings>/<Day/Night Schedules>/Set Time
11:**Pm
•
Adjust the time by selecting Time from the menu and then scrolling through the hours
then select Save. Then, scroll through the minutes then select Save. If the hours are to
be set to PM, scroll through the AM hours to reach the PM hours.
BACK
SAVE
ALERT
Remember that the battery is the backup for the Time. If no power is supplied to the BMC and there
was no battery or battery had no power, time values will be lost and will need to be reset.
--- OD= 54 F, 11:36Am ---
HISTORY
Button: MENU/<Histories>
The BMC provides users with a graphical history of the System and Outdoor temperatures for
the previous 24 hours. The temperatures are sampled every 12 minutes. That is, readings of
both System and Outdoor temperatures are recorded and stored every 12 minutes for the last
24 hours.
BACK
EXIT
•
To view the values of specific time period, use the two middle buttons to scroll to that
time and read the upper left temperature.
--- OD= 54 F, 11:36Am ---
•
The first screen will be the System Temperature History. By clicking on the Next
button, you'll be able to view the Outdoor Temperature History.
BACK
EXIT
22
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
---------- MAINTENANCE ---------
MAINTENANCE
The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In
addition, you'll have access to view the Startup configuration settings.
System Trim
+0 F
+0 F
45sec
Button: MENU/<Maintenance>
Outdoor Trim
Soft-Off Delay
<Output Trim>
<Configuration>
BACK
SELECT
ALERT
To be able to change the BMC settings the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.
PROGRAM
RUN
SYSTEM & OUTDOOR SENSOR TRIM
--- SYSTEM SENSOR TRIM ----
Adjustable from -5F°/-3C° to +5F°/+3C°
Button: MENU/<Maintenance>/System Trim
Button: MENU/<Maintenance>/Outdoor Trim
Default: 0°F
+0
F
[]
•
The Weil McLain thermistor type sensors are very accurate, and normally require no
calibration. Sometimes it may be desirable to make small adjustments to the displayed
value for either the Outdoor temperature (OD) or the System temperature (SYS). The
Trim setting can adjust the displayed value by 5°F.
Do not use the Trim setting to make the Outdoor temperature sensor match that reported
on the radio or TV. Outdoor temperature can vary widely over a broadcast range. Only
trim the outdoor sensor based on an accurate thermometer reading taken where the
sensor is located.
BACK
SAVE
-- OUTDOOR SENSOR TRIM ----
•
+0
F
[]
BACK
SAVE
SOFT-OFF DELAY
------- SOFT-OFF DELAY --------
Adjustable from 0sec to 60sec
Default: 45sec
Button: MENU/<Maintenance>/Soft-Off Delay
45sec
[]
•
•
•
•
When a stage is no longer needed, the Soft-Off keeps that stage burner in Low Fire prior
to turning it off.
The display will show a percent that is equal to the Ignition % for the stage in Soft-Off
delay. That number will blink for the Soft-Off delay period.
If during the Soft-Off delay period the BMC needed that stage to turn back on, the stage
will be released from the Soft-Off delay and resume normal operation.
On a Shutdown initiation or Tstat termination any stage that was on will go into Soft-Off
delay before fully turning off.
BACK
SAVE
ALERT
When using Soft-Off and Last Stage Hold, the last boiler stage will not turn off until both parameters have
elapsed. In this case, Soft-Off will start after the Last Stage Hold has been reached or exceeded.
OUTPUT TRIM
-------- STAGE A TRIM --------
Adjustable from -5 to +5
Default: 0
Output Trim
<Prev Stage>
<Next Stage>
+0.0
Button: MENU/<Maintenance>/Output Trim
•
•
•
Each of the stages controlled by the BMC has a separate Output Trim setting.
Output Trim acts as an adjustment to a stage output percent to match the burner motor.
After adjusting the Output Trim, test the operation to make sure the results match your
expectation.
BACK
SELECT
ALERT
DO NOT use the Output Trim for a Stage unless it is absolutely necessary. Test
burner operation and modulation output matching after adjusting the Output Trim.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
CONFIGURATION
------ CONFIGURATION 1 ------
v1.00c
Reset F
Normal
Button: MENU/<Maintenance>/<Configuration>
•
This menu option provides a consolidated view of the BMC's Startup and Stage settings.
Day/Night Schedules
All Off
BACK
NEXT
DISPLAY
The BMC display layout provides a variety of information that gives an immediate picture of
the operation status. The display shows four boilers at a time. When extensions are present,
the two middle buttons scrolls the screen to view additional boilers. Moreover, all the
information is brightly displayed. It can be viewed in brightly or dimly lit rooms.
------ CONFIGURATION 2 ------
A=4-20ma
C=0-5v
B=0-10v
D=2-10v
•
The buttons' functionality changes based on the screen and menu level. The buttons'
functionality is displayed on a dark background on the screen bottom line.
BACK
EXIT
•
•
Horizontal arrows are to scroll through the available stages.
Outdoor Temp
System Temp
Vertical arrows are to scroll through the menu functions
when in menus or to change values of settings when in its
specific screen.
OD=35
F
SYS=98
F
Message Display Line
•
•
The Top line displays the available sensor values.
The second line displays the Target set point. However,
it will display any messages pertaining to the operation or
status.
The third line will list the boiler stages. Any additional
stages can be scrolled to using the two middle buttons.
The Lead boiler letter will be bracketed. See Lead Boiler
Operation on page 19.
Prepurge Delay:67
Boilers and their
A
B
C
D
Modulation Status
50%
15%
---
---
STAGE
MENU
•
•
Button functions
Button
The fourth line lists each boiler modulation status. See
Display Boiler Modulation Status for possible status.
DISPLAY BOILER MODULATION STATUS
The BMC boiler modulation status gives immediate access to each boiler status. The following list show all possible boiler status:
•
•
•
•
•
•
---
97%
ON
OFF
m95%
C/E
Boiler is off due to no call for heat.
Boiler is modulating at the indicated percentage.
Boiler Stage Mode is set to ON and boiler is firing at 100% (boiler is in bypass). See Mode on page 25.
Boiler Stage Mode is set to OFF and boiler stage is unavailable or boiler does not exist. See Mode on page 25.
Boiler Stage Mode is set to Manual and set to the specified percent. See Mode on page 25.
Boiler on Extension panel is NOT communicating back to the BMC. See connecting extensions on page 11.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
DISPLAY MESSAGES
The BMC normal display layout reserved the second line for message indications. The following is a list of the most common
Message Display Line information:
•
•
•
•
•
Summer
The control is set to Summer. No heat is active. See Season on page 17.
The Shutdown Terminals are Shorted. No boilers will be active. See Shutdown on pages 15 and 9.
The EMS is below 2mA or above 22mA. See EMS input and External Set Point pages 14 and 31.
The Tstat Terminals are Shorted. Boilers will be active.
There is a DHW (Domestic Hot Water) call. The BMC will Raise system Set Point to the indicated
temperature. DHW increases calculated temperature to 200˚F or Max Water Temperature, whichever
is lower. See DHW setting on page 15.
Shutdown Active
Shutdown by EMS
Tstat Call
DHW Call (171˚F)
•
•
•
•
•
•
Purge Delay: 23
Lag Delay: 123
The current boiler is in purge cycle and the remaining purge time in seconds is 23. See Purge Delay
on page 19.
The lead boiler is at 100% and the remaining purge time to start the lag boiler in seconds is 123. See
Lag Delay on page 20.
The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when
system temperature reaches 150˚F. See Last Stage Hold on page 21.
The System relay is ON for the System Run-On Delay. This example shows that it will remain in
System Run-On for an additional 46 seconds before turning off. See System Run-On on page 20.
The System relay is ON and the prove terminals are open before the lead boiler relay can energize.
See Prove setting on page 15.
Holding Until 150˚F
System Run-On: 46
Waiting for Prove
Prove Failure
After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize.
However, the System relay will remain energized. See Prove setting on page 15.
----- STAGE A SETTINGS ----
BOILER STAGE SETTINGS
Button: STAGE/
The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In
addition, you'll have access to view the Startup configuration settings.
Mode
Off
1%
Ignition %
Mode Start %
<Prev Stage>
<Next Stage>
Copy Settings
75%
•
In most installations, all active boiler adjustments are the same, but each can be
configured differently if desired.
BACK
SELECT
•
•
•
•
If the boilers are not set up properly, the BMC operation may appear to be erratic.
When the STAGEbutton is depressed, the Boiler A Settings menu will be shown.
Make all the appropriate settings for Boiler A (See below).
After completing all the settings for Boiler A (See below), you have the option of
copying these settings to all other boilers. Everything but the Mode -- Auto/Standby/
Manual/Off/On -- will be copied.
Then select the Next Stage option from the menu to bring up the Boiler B Settings menu
and make all the settings. Continue until all boilers have been set.
If a BMC-6X is connected to the BMC, scrolling through stages using the Next and Prev
Stage menu options will scroll through the BMC-6X stages as well.
CAUTION
Remember to set the Mode
for each stage. For Stages
that do not have a boiler,
contractor must change their
Mode to OFF. Otherwise the
BMC will include them in the
modulation calculation and
rotation. That might have dire
effects on system response.
•
•
ALERT
To be able to change the BMC settings, the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.
PROGRAM
RUN
MODE
------- STAGE A MODE --------
Auto
Standby
Manual
Off
Auto, Standby, Manual, Off, On
Button: STAGE/Mode
Default: Auto
•
The BMC only controls the modulation of boilers set to Auto or (after a delay) those set
to Standby. None of the other settings is recommended for output boilers connected to
active units.
On
BACK
SAVE
•
•
Any boiler without an active unit connected must be set to Off.
The following list describes the MODE options:
25
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
Auto -
The BMC will control the boiler’s operation to maintain the desired Set Point. Only boilers set to Auto can be Lead
boilers.
Standby Standby boilers can only be activated when all boilers in Auto have been at 100% modulation for a selectable period of
time. Standby is generally used when you want a specific boiler to be available in extreme load conditions. Note that a
Standby boiler Cannot be a Lead boiler.
Manual The Manual Mode should only be used when testing a boiler. Manual overrides the Prove input. The exact percent of
modulation for a boiler can be set with the Manual mode. Once selected, the unit will immediately turn on and modulate to
the selected percentage.
Off
Any output Boiler A through D not connected to a physical unit should be set to Off. The Off Mode can also be used to
disable units that are being serviced.
On
The On Mode should only be used when testing a boiler. The On Mode overrides the PROVE input. Once set to On the
boiler will immediately start firing and modulate to 100%.
IGNITION %
------------ STAGE A ------------
IGNITION POINT
Adjustable from 1% to 50%
Button: STAGE/Ignition %
Default: 1%
1%
•
The Ignition Point is the percent of modulation that must be attained before the unit can
be activated.
[
]
•
•
For most modern power draft units, the Ignition Point should be set at 1%.
Older units or atmospheric units may require the modulating fuel valve to be open from
20-50% before proper ignition can be attained. Check with the boiler manufacturer if
you are in doubt about the minimum position of the fuel valve for ignition.
BACK
SAVE
MODULATION START %
Adjustable from 0% to 100%
Button: STAGE/Mod Start %
------------ STAGE A ------------
MODULATION START
Default: 75%
75%
•
The Modulation Start determines at what modulation percent the previous boiler should
[
]
be for the current boiler to be activated.
•
For example, if the Modulation Start for Boiler B is set to 75%, then when Boiler A
reaches 75% modulation plus Ignition%, Boiler B (if Boiler B is in Auto Mode and is not
already on) will be brought on at the Ignition % level.
BACK
SAVE
•
•
•
When modulation is decreasing, the lag unit will remain on at the Ignition % modulation until the previous boiler reaches 40%
of lag boiler's Modulation Start, or 2% above the Ignition Point, whichever is higher.
Using the same example, as the load decreases, Boiler B would modulate down to its Ignition %. Boiler A would then modulate
down to 30%. Only then would Boiler B turn off.
If the Lag Delay is set to anything other than 0, a boiler must always go up to 100% modulation before the next boiler is
activated. However, the Modulation Start % should still be set correctly, because it will be valid when modulation is decreasing.
COPY SETTINGS - BOILER A ONLY
-------- COPY SETTINGS -------
Button: STAGE/Copy Settings
From Stage A
to all other stages
•
If all the active boilers will have the same Ignition Start Point and Modulation Point,
they can be set for Boiler A and then copied to the other boilers.
•
It is still required to select the Mode for all other boilers as the Mode is NOT copied.
BACK
COPY
ALERT
The Mode MUST be set for each boiler. The Copy Settings command will not set the
Mode for the remaining boilers. Only Ignition % and Modulation Start % are copied.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
TROUBLESHOOTING
SENSOR INPUTS
Temperature Sensor Chart
TEMPERATURE
Display shows Sensor OPEN or SHORT
Value
(in Ohms)
When OPEN, Check the sensor is connected and the wires are continuous to the BMC. Finally
follow the procedure for Incorrect Temperature or Pressure Display. When SHORT Remove the
wires from the sensor terminals. The display should change to read OPEN. If it does not, the
BMC may be damaged.
°F
-30
-20
-10
0
°C
-34
-29
-23
-18
-12
-7
117720
82823
59076
42683
31215
23089
19939
17264
14985
13040
11374
9944
8714
7653
5941
4649
3667
2914
2332
1879
1524
1243
1021
842
Display shows an Incorrect Temperature
10
Remove the wires from the sensor terminals. The display should change to read OPEN. If it
does not, the BMC may be damaged. Take an ohm reading across the detached sensor wires.
The ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor
may be damaged.
20
25
-4
30
-1
35
2
40
4
CONTROL OPERATION
No Heat
45
7
50
10
13
16
21
27
32
38
43
49
54
60
66
71
77
82
88
93
99
104
110
116
121
•
•
Season - Make sure that the Season is set to Winter. Check Message Display Line on page 24.
Prove - Even though, the system relay may be energized, the BMC will not energize and stage
relays unless the Prove is shorted. Check Message Display Line on page 24.
Shutdown - The BMC will activate stage outputs when the Shutdown terminals are short.
Check Message Display Line on page 24.
Tstat - The BMC will activate stage outputs when the Tstat terminals are open. Check Message
Display Line on page 24.
Sensor Fault - When the Sensor Fault is set to All Off in the startup menu (see page 16), the
System sensor fault (in all Sensor Type modes) or the Outdoor sensor fault (in Reset mode) will
de-energize all stage relays. Check the display for sensor values.
System or Outdoor Sensor - If the System or Outdoor sensor reading was higher that the
actual temperature, the BMC might not bring any stage on. Check "Display shows an Incorrect
Temperature" section.
55
60
70
•
•
•
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
•
699
Too Much Heat
Check if the control has any of the following:
583
•
Domestic Hot Water call - The BMC will raise the temperature of the system to either 200˚F or
Maximum Water Temperature on a DHW call, connected to terminals 29 and 30. Check to see
if there is a call for DHW and the length of time it lasts.
Reset Ratio and Offset - If excessive heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset (See Understanding Operating Concept on page 5). If excessive heat
occurs year round, reduce the Offset.
489
412
349
•
297
253
217
•
•
Boiler Mode Settings - The BMC will only modulate boilers their mode is set to Auto or
Standby. Check to if any boiler stage is set to Manual or On. See Mode on page 25.
Control Settings - The Last Stage Hold will allow only the Lead boiler to stay on for an
additional number of degrees. If the setting is too high, and only the Lead boiler is on, the
system can over heat. Reduce the Last Stage Hold setting. See page 21.
187
Too Little Heat
Check if the control has any of the following:
•
Reset Ratio and Offset - If reduced heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset (See Understanding Operating Concept on page 5). If reduced heat
occurs year round, increase the Offset.
Setback and Day/Night Schedule - If reduced heat occurs only during specific hours, check
the Day/Night Schedule and the Setback values. Either reduce the Setback setting (See page
20).
•
27
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
•
Boiler Mode Settings - The BMC will only modulate boilers their mode is set to Auto or Standby. Check if any boiler stage is set
to Manual, Off, or Standby. See Mode on page 25.
Boilers are Short-Cycling
•
•
Lag Delay - Increase the Lag Delay only if all boilers tend to short-cycle.
Last Stage Hold - Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
System is Overshooting or Undershooting
•
•
Gain - If the system is overshooting reduce the Gain.
Gain - If the system is undershooting increase the Gain.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
MULTIPLE MODULATING BOILERS
DIRECT HEATING PIPING DIAGRAM
Outdoor
Sensor
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
B
INPUT RATINGS:
115VAC 60Hz 30VA MAX
USE COPPER WIRE,
CLASS WIRE ONLY.
,
---
---
C
D
1
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
A
RUN
C
EXTENSION
MODULE
B
D
OUTDOOR SYSTEM
TEMP TEMP
PROVE
/DHW
SHUTDOWN
/SETBACK
PWR
SYS
A
B
C
D
CUR
/
VLT CUR
/
VLT CUR
/
VLT CUR
/
VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
L
1
N
2
T
O
T
O
O
O
RS-485
-
+
+
-
+
+
-
+
+
-
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
120VAC
Boiler 1
Boiler 2
Boiler 3
Boiler 4
System
Sensor
Building Heating Loop
System:
The BMC provides 4 modulating boilers. The boilers are piped in Reverse Return on the primary loop. The System
output is controlling the System Pump.
Weil McLain is aware that each installation is unique. Thus, Weil McLain is not responsible for any installation related to
any electrical or plumbing diagram generated by Weil McLain. The provided illustrations are to demonstrate Weil McLain’s
control operating concept only.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
MULTIPLE MODULATING BOILERS
DIRECT HEATING WIRING DIAGRAM
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
4-20mA Modulating
INPUT RATINGS:
B
C
D
115VAC 60Hz , 30VA MAX
---
---
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
Outputs
C
US
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
A
RUN
C
SHUTDOWN
EXTENSION
MODULE
SYSTEM
PROVE
OUTDOOR SYSTEM
TEMP TEMP
B
D
PWR
SYS
A
B
C
D
/TSTAT
CUR / VLT CUR / VLT CUR / VLT CUR / VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
/SETBACK
RS-485
L
1
N
2
T
O
T
O
O
O
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
4 - 20 mA
Signal Outputs
L
N
L
N
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
B
C
D
Voltage Modulating
Outputs
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
---
---
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
C
US
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
RUN
C
SHUTDOWN
EXTENSION
MODULE
OUTDOOR SYSTEM SYSTEM
A
B
D
PWR
SYS
A
B
C
D
/TSTAT
TEMP
TEMP
PROVE
CUR / VLT CUR / VLT CUR / VLT CUR / VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
/SETBACK
RS-485
L
1
N
2
T
O
T
O
O
O
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
Voltage
Signal Outputs
L
N
L
30
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
MULTIPLE MODULATING BOILERS
EXTERNAL 4-20MA SET POINT
USING 4-20MA EMS INTERFACE
BMC
Full Modulation Sequencing Control
SYSTEM
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
A
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
B
---
---
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
C
D
C
US
ENCLOSED
ENERGY
420MOD EMS Interface
MANAGEMENT
EQUIPMENT
LISTED
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
99RA
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
PROGRAM
A
RUN
C
420MOD
SHUTDOWN
EXTENSION
MODULE
OUTDOOR SYSTEM
B
D
SYSTEM
PROVE
4-20mA INPUT
RS485
PWR
SYS
A
B
C
D
/TSTAT
TEMP
TEMP
CUR / VLT CUR / VLT CUR / VLT CUR / VLT
GND mA VLT GND mA VLT GND mA VLT GND mA VLT
Signal GND
/SETBACK
+
1
EXTENSION
2
CONNECTORS
3
RS-485
L
1
N
2
T
O
T
O
O
O
-
-
-
-
+
+
+
+
+
+
+
+
3
4
5
6
7
8
9
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32
To EMS/BMS
4-20mA Set Point
4 - 20 mA
Signal Outputs
L
N
L
N
31
Download from Www.Somanuals.com. All Manuals Search And Download.
BMC and BMC-6X Installation and Operation Manual
SPECIFICATIONS
Voltage Input: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 VAC 60 Hz
Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 VA Max
Operating Temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20°F/-7°C to 120°F/49°C
Operating Humidity: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20% to 80%
Dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11"W x 9" H x 3 ¾" D
Weight: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 pounds
BMC SPECIFICATIONS
Lead Stage Rotation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 1440 Hours (60 days)), Manual, Last-On
Pump Output: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1) N.O. S.P.S.T
Boiler Modes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Auto, Manual (0% - 100%), Standby, On, Off
Standby Time: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 60 minutes
Modulating Output Types: . . . Total of four outputs. Can be either Current (4-20mA) or VDC (0-5V, 0-10V, 1-5V, 2-10V)
Output Relay Ratings: . . . . . . (5) 1 Amp inductive (1/8HP), 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits
Add-On BMC-6X Panels: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .up to two BMC-6X Panels using RS485
Ignition Point %: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 50%
Modulation Start Point %: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 100%
Modulation Modes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Normal or Parallel
Temperature Display: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fahrenheit or Celsius.
Display: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each)
LED: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1) System Output relay, (4) Boiler Output relays
Sensor Ranges: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Outdoor temperature sensor -35°F/-37°C to 250°F/121°C
Heating system sensor -35°F/-37°C to 250°F/121°C
Outdoor Cutoff Range: . . . . . . . . . . . . . . . . . . . . . . . . . . . .20°F/-7°C to 100°F/38°C, ON and OFF
Reset Ratio Range: . . . . . . . . . . . . . . . . . . . . . . . . (1.00 : 4.00) to (4.00 : 1.00) (Outdoor : System Water)
Offset Adjustment: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40F°/-22C° to + 40F°/+22C
Minimum Water Temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70°F/21°C to 170°F/77°C
Maximum Water Temperature (Reset Only): . . . . . . . . . . . . . . . . . . . .
Set Point Temperature Range: . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EMS Temperature Range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90°F/32°C to 240°F/116°C
70°F/21°C to 250°F/121°C
70°F/21°C to 240°F/116°C
Domestic Hot Water: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . with Priority or without Priority
Pump Run-On: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 360 minutes
Purge Delay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0 to 10.0 minutes
Lag Delay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 60 minutes
Last Stage Hold: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0F°/0°C to 30F°/17C°
Schedules: . . . . . . . . . . . . . . . . . (1) Day and (1) Night (Setback) settings per day (Require Shutdown or Tstat mode)
Night Setback: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0F°/0C° to 75F°/42C°
Power Backup: . . . . . . . . Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages).
External Inputs: . . . . . . . . . .Tstat Input/Shutdown Input/Setback Input, and Prove Input/DHW Input (Dry Contacts Only)
Season: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Winter and Summer.
BMC-6X SPECIFICATIONS
(Each BMC-6X can add up to (6) additional modulating boilers. A maximum of two BMC-6Xs can be added to a single BMC.)
Extension Numbering: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Toggle Switch A or B
Boiler Outputs: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (6) N.O. S.P.S.T.
Modulating Output Types: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (6) 4-20mA, 0-5V, 0-10V, 1-5V, 2-10V
Output Relay Ratings: . . . . . . . . . . . 1 Amp inductive (1/8HP), 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits
Connection to BMC and another extension: . . . . . . . . Two RS485 connections using 6 wire phone cable (Cable is provided)
500 Blaine Street
Michigan City, Indiana 46360
219-879-6561
Part Number 550-100-072/0408
32
Download from Www.Somanuals.com. All Manuals Search And Download.
|